00 The Full Grid Code I6R21
00 The Full Grid Code I6R21
ISSUE 6
REVISION 21
4 March 2024
© 2024 Copyright owned by National Grid Electricity System Operator Limited, all rights reserved.
No part of this publication may be reproduced in any material form (including photocopying and restoring in
any medium or electronic means and whether or not transiently or incidentally) without the written permission
of National Grid Electricity System Operator Limited, except:
1. to the extent that any party who is required to comply (or is exempt from complying) with the provisions
under the Electricity Act 1989 reasonably needs to reproduce this publication to undertake its licence or
statutory duties within Great Britain (or any agent appointed so to act on that party’s behalf); and
2. in accordance with the provisions of the Copyright, Designs and Patents Act 1988.
THE GRID CODE
CONTENTS
CONTENTS* (C)
PREFACE* (P)
REVISIONS* (R)
*does not constitute part of the Grid Code
P.1. The Grid Code sets out the operating procedures and principles governing the relationship
between The Company and all Users of the National Electricity Transmission System, be
they Generators, DC Converter owners, Suppliers or Non-Embedded Customers. The
Grid Code specifies day-to-day procedures for both planning and operational purposes and
covers both normal and exceptional circumstances.
Access Group A group of Connection Points within which a User declares under the
Planning Code
(a) An interconnection and/or
(b) A need to redistribute Demand between those Connection Points
either pre-fault or post-fault
Where a single Connection Point does not form part of an Access
Group in accordance with the above, that single Connection Point shall
be considered to be an Access Group in its own right.
Access Period A period of time in respect of which each Transmission Interface Circuit
is to be assessed as whether or not it is capable of being maintained as
derived in accordance with PC.A.4.1.4. The period shall commence and
end on specified calendar weeks.
Act The Electricity Act 1989 (as amended by the Utilities Act 2000 and the
Energy Act 2004).
Active Control Based Droop The Active Control Based Power output supplied by a Grid Forming
Power Plant through controlled means (be it manual or automatic).
For GBGF-I this is equivalent to a Synchronous Generating Unit with a
traditional governor coupled to its prime mover.
Active Control Based Droop Power is used by The Company to
control System Frequency changes through the instruction of Primary
Response and Secondary Response.
Active Control Based The Active Power output supplied by a Grid Forming Plant through
Power controlled means (be it manual or automatic) of the positive phase
sequence Root Mean Square Active Power produced at fundamental
System Frequency by the control system of a Grid Forming Unit.
For GBGF-I, this is equivalent to a Synchronous Generating Unit with
a traditional governor coupled to its prime mover.
Active Control Based Power includes Active Power changes that
results from a change to the Grid Forming Plant Owners available set
points that have a 5 Hz limit on the bandwidth of the provided response.
Active Control Based Power also includes Active Power components
produced by the normal operation of a Grid Forming Plant that comply
with the Engineering Recommendation P28 limits. These Active
Power components do not have a 5 Hz limit on the bandwidth of the
provided response.
Active Control Based Power does not include Active Power
components proportional to System Frequency, slip or deviation that
provide damping power to emulate the natural damping function provided
by a real Synchronous Generating Unit.
Active Energy The electrical energy produced, flowing or supplied by an electric circuit
during a time interval, being the integral with respect to time of the
instantaneous power, measured in units of watt-hours or standard
multiples thereof, ie:
1000 Wh = 1 kWh
1000 kWh = 1 MWh
1000 MWh = 1 GWh
1000 GWh = 1 TWh
Active Frequency The injection or absorption of Active Power by a Grid Forming Plant to
Response Power or from the Total System during a deviation of the System Frequency
away from the Target Frequency.
For a GBGF-I this is very similar to Primary Response but with a
response time to achieve the declared service capability (which could be
the Maximum Capacity or Registered Capacity) within 1 second.
For GBGF-I this can rapidly inject or absorb Active Power in addition to
the phase-based Active Inertia Power to provide a system with desirable
NFP plot characteristics.
Active Frequency Response Power can be produced by any viable
control technology.
Active Inertia Power The injection or absorption of Active Power by a Grid Forming Plant to
or from the Total System during a System Frequency change.
The transient injection or absorption of Active Power from a Grid
Forming Plant to the Total System as a result of the ROCOF value at
the Grid Entry Point or User System Entry Point. This requires a
sufficient energy storage capacity of the Grid Forming Plant to meet the
Grid Forming Capability requirements specified in ECC.6.3.19.
For the avoidance of doubt, this includes the rotational inertial energy of
the complete drive train of a Synchronous Generating Unit.
Active Inertia Power is an inherent capability of a Grid Forming Plant
to respond naturally, within less than 5ms, to changes in the System
Frequency.
For the avoidance of doubt, the Active Inertia Power has a slower
frequency response compared with Active Phase Jump Power.
Active Power The product of voltage and the in-phase component of alternating current
measured in units of watts and standard multiples thereof, ie:
1000 Watts = 1 kW
1000 kW = 1 MW
1000 MW = 1 GW
1000 GW = 1 TW
Active ROCOF Response The Active Inertia Power developed from a Grid Forming Plant plus the
Power Active Frequency Response Power that can be supplied by a Grid
Forming Plant when subject to a rate of change of the System
Frequency.
AF Rules Has the meaning given to “allocation framework” in section 13(2) of the
Energy Act 2013.
Aggregator Impact Matrix Defined for an Additional BM Unit or a Secondary BM Unit. Provides
data allowing The Company to model the result of a Bid-Offer
Acceptance on each of the Grid Supply Points within the GSP Group
over which the Additional BM Unit or Secondary BM Unit is defined.
Alternate Member Shall mean an alternate member for the Panel Members elected or
appointed in accordance with this GR.7.2(a) or (b).
Anchor DC Converter Test A test carried out by an Anchor DC Converter Owner on an Anchor DC
Converter while the Anchor DC Converter is disconnected from all
external electrical power supplies from the Total System.
Anchor Generating Unit A test carried out on an Anchor Generating Unit or a CCGT unit or a
Test Power Generating Module, as the case may be, at an Anchor Power
Station while the Anchor Power Station remains energised from the
Total System.
Anchor HVDC System Test A test carried out by an Anchor HVDC System Owner while the Anchor
HVDC System is disconnected from all external electrical power supplies
from the Total System.
The ability of a Restoration Contractor’s Plant to Start-Up from
Anchor Plant Capability
Shutdown and to energise and maintain a part of the Total System upon
instruction from The Company or Relevant Transmission Licensee (in
Scotland) or relevant Network Operator, within a defined time period,
without an external electrical power supply from the Total System. In the
case of a Local Joint Restoration Plan the defined period of time is
within 2 hours of an instruction from The Company or Relevant
Transmission Licensee. In the case of a Distribution Restoration
Zone Plan, the defined period of time is within 8 hours of an instruction
from relevant Network Operator.
Anchor Plant Test A test conducted on Plant to confirm it is capable of meeting the
requirements of an Anchor Restoration Contract.
Anchor Power Station Test A test carried out by an Anchor Generator at an Anchor Power Station
while that Anchor Power Station is disconnected from all external
electrical power supplies from the Total System.
Anchor Restoration In the case of a Local Joint Restoration Plan or Offshore Local Joint
Contract Restoration Plan, a contract between The Company and an Anchor
Restoration Contractor for the provision of an Anchor Plant Capability.
In the case of a Distribution Restoration Zone Plan is an agreement
between The Company and relevant Network Operator and Anchor
Restoration Contractor for the provision of an Anchor Plant Capability.
Anchor Plant Unit Test A test carried out on a Generating Unit or a CCGT Unit or a Power
Generating Module, or a HVDC System or a DC Converter as the case
may be, at the site of an Anchor Plant while the Anchor Plant is supplied
from all external power supplies.
Annual Average Cold Spell A particular combination of weather elements which gives rise to a level
Conditions or ACS of peak Demand within a Financial Year which has a 50% chance of
Conditions being exceeded as a result of weather variation alone.
Apparatus Other than in OC8, means all equipment in which electrical conductors
are used, supported or of which they may form a part. It includes Users’
equipment which imposes Demand on the System.
In OC8, it means High Voltage electrical circuits forming part of a System
on which Safety Precautions may be applied to allow work and/or testing
to be carried out on a System.
Apparent Power The product of voltage and of alternating current measured in units of
voltamperes and standard multiples thereof, ie:
1000 VA = 1 kVA
1000 kVA = 1 MVA
Approved Fast Track Has the meaning given in GR.26.7, provided that no objection is received
Proposal pursuant to GR.26.12.
Authorised Certifier An entity that issues Equipment Certificates and Power Generating
Module Documents and whose accreditation is given by the United
Kingdom Accreditation Service or such other body as may be established
from time to time to carry out the function of accreditation.
Authorised Electricity Any person (other than The Company) who is authorised under the Act
Operator to generate, participate in the transmission of, distribute or supply
electricity which shall include any Interconnector Owner or
Interconnector User.
Authority for Access An authority which grants the holder the right to unaccompanied access
to sites containing exposed HV conductors.
Authority, The The Authority established by section 1 (1) of the Utilities Act 2000.
Automatic Voltage The continuously acting automatic equipment controlling the terminal
Regulator or AVR voltage of a Synchronous Generating Unit or Synchronous Power
Generating Module by comparing the actual terminal voltage with a
reference value and controlling by appropriate means the output of an
Exciter, depending on the deviations.
Auxiliary Diesel Engine A diesel engine driving a Power Generating Module or Generating Unit
which can supply a Unit Board or Station Board, which can start without
an electrical power supply from outside the Power Station within which it
is situated.
Auxiliary Energy Supplies An electricity supply (which could be derived from an Auxiliary Diesel
Engine or Auxiliary Gas Turbine or other source of energy) that is
necessary to power the auxiliary and ancillary equipment on which a
Power Generating Module or HVDC System or DC Converter or other
item of Plant relies for it to be capable of generating Active or Reactive
Power and which is generally supplied via a Unit Board or Station
Board, or equivalent. Auxiliary Energy Supplies must beavailable
without an external electrical power supply from the Total System.
Auxiliary Energy Supplies do not include the mains-independent light
current supplies necessary to operate Critical Tools and Facilities.
Auxiliary Gas Turbine A Gas Turbine Unit, which can supply a Unit Board or Station Board,
which can start without an electrical power supply from outside the Power
Station within which it is situated.
Average Conditions That combination of weather elements within a period of time which is the
average of the observed values of those weather elements during
equivalent periods over many years (sometimes referred to as normal
weather).
Back-Up Protection A Protection system which will operate when a system fault is not cleared
by other Protection.
Balancing and Settlement The code of that title as from time to time amended.
Code or BSC
Balancing Code or BC That portion of the Grid Code which specifies the Balancing Mechanism
process.
Balancing Mechanism Has the meaning set out in The Company’s Transmission Licence
Baseline Forecast Has the meaning given to the term ‘baseline forecast’ in Section G of the
BSC.
BM Unit Has the meaning set out in the BSC, except that for the purposes of the
Grid Code the reference to “Party” in the BSC shall be a reference to
User.
BM Unit Data The collection of parameters associated with each BM Unit, as described
in Appendix 1 of BC1.
British Standards or BS Those standards and specifications approved by the British Standards
Institution.
BSC Panel Has meaning set out for “Panel” in the BSC.
Business Day Any week day (other than a Saturday) on which banks are open for
domestic business in the City of London.
Capacity Market The Capacity Market Rules, The Electricity Capacity Regulations
Documents 2014 and any other Regulations made under Chapter 3 of Part 2 of the
Energy Act 2013 which are in force from time to time.
Capacity Market Rules The rules made under section 34 of the Energy Act 2013 as modified from
time to time in accordance with that section and The Electricity Capacity
Regulations 2014.
Cascade Hydro Scheme The matrix described in Appendix 1 to BC1 under the heading Cascade
Matrix Hydro Scheme Matrix.
CfD Counterparty A person designated as a “CfD counterparty” under section 7(1) of the
Energy Act 2013.
CfD Documents The AF Rules, The Contracts for Difference (Allocation) Regulations
2014, The Contracts for Difference (Definition of Eligible Generator)
Regulations 2014 and The Contracts for Difference (Electricity Supplier
Obligations) Regulations 2014 and any other regulations made under
Chapter 2 of Part 2 of the Energy Act 2013 which are in force from time
to time.
CCGT Module Matrix The matrix described in Appendix 1 to BC1 under the heading CCGT
Module Matrix.
CCGT Module Planning A matrix in the form set out in Appendix 3 of OC2 showing the combination
Matrix of CCGT Units within a CCGT Module which would be running in relation
to any given MW output.
Closed Distribution System A distribution system classified as a Closed Distribution System by the
or CDSO Authority which distributes electricity within a geographically confined
industrial, commercial or shared services site and does not supply
household Customers, without prejudice to incidental use by a small
number of households located within the area served by the System and
with employment or similar associations with the owner of the System.
CM Administrative Parties The Secretary of State, the CM Settlement Body, and any CM
Settlement Services Provider.
CM Settlement Body the Electricity Settlements Company Ltd or such other person as may
from time to time be appointed as Settlement Body under regulation 80 of
the Electricity Capacity Regulations 2014.
CM Settlement Services any person with whom the CM Settlement Body has entered into a
Provider contract to provide services to it in relation to the performance of its
functions under the Capacity Market Documents.
Code Administrator Means The Company carrying out the role of Code Administrator in
accordance with the General Conditions.
Combined Cycle Gas A collection of Generating Units (registered as a CCGT Module (which
Turbine Module or CCGT could be within a Power Generating Module) under the PC) comprising
Module one or more Gas Turbine Units (or other gas based engine units) and
one or more Steam Units where, in normal operation, the waste heat
from the Gas Turbines is passed to the water/steam system of the
associated Steam Unit or Steam Units and where the component units
within the CCGT Module are directly connected by steam or hot gas lines
which enable those units to contribute to the efficiency of the combined
cycle operation of the CCGT Module.
Commercial Ancillary Ancillary Services, other than System Ancillary Services, utilised by
Services The Company in operating the Total System if a User (or other person
such as a Demand Response Provider) has agreed to provide them
under an Ancillary Services Agreement or under a Bilateral
Agreement with payment being dealt with under an Ancillary Services
Agreement or in the case of Externally Interconnected System
Operators or Interconnector Users, under any other agreement (and in
the case of Externally Interconnected System Operators and
Interconnector Users includes Ancillary Services equivalent to or
similar to System Ancillary Services).
Committed Level The expected Active Power output from a BM Unit after accepting a Bid-
Offer Acceptance or RR Instruction or a combination of Bid-Offer
Acceptances and RR Instructions.
Committed Project Data relating to a User Development once the offer for a CUSC Contract
Planning Data is accepted.
Common Collection Busbar A busbar within a Power Park Module to which the higher voltage side
of two or more Power Park Unit generator transformers are connected.
Completion Date Has the meaning set out in the Bilateral Agreement with each User to
that term or in the absence of that term to such other term reflecting the
date when a User is expected to connect to or start using the National
Electricity Transmission System. In the case of an Embedded
Medium Power Station or Embedded DC Converter Station or
Embedded HVDC System having a similar meaning in relation to the
Network Operator’s System as set out in the Embedded Development
Agreement.
Compliance Processes or That portion of the Grid Code which is identified as the Compliance
CP Processes.
Compliance Statement A statement completed by the relevant User confirming compliance with
each of the relevant Grid Code provisions, and the supporting evidence
in respect of such compliance, of its:
Generating Unit(s); or,
Power Generating Modules (including DC Connected Power Park
Modules and/or Electricity Storage Modules); or,
CCGT Module(s); or,
Power Park Module(s); or,
DC Converter(s); or
HVDC Systems; or
Plant and Apparatus at an EU Grid Supply Point owned or operated by
a Network Operator; or
Network Operator’s entire distribution System where such Network
Operator’s distribution System comprises solely of Plant and
Apparatus procured on or after 7 September 2018 and was connected
to the National Electricity Transmission System on or after 18 August
2019. In this case, all connections to the National Electricity
Transmission System would comprise only of EU Grid Supply Points;
or
Plant and Apparatus at an EU Grid Supply Point owned or operated by
a Non-Embedded Customer where such Non-Embedded Customer is
defined as an EU Code User;
In the form provided by The Company to the relevant User or another
format as agreed between the User and The Company.
Configuration 1 AC One or more Offshore Power Park Modules that are connected to an
Connected Offshore Power AC Offshore Transmission System and that AC Offshore
Park Module Transmission System is connected to only one Onshore substation and
which has one or more Transmission Interface Points.
Configuration 2 AC One or more Offshore Power Park Modules that are connected to a
Connected Offshore Power meshed AC Offshore Transmission System and that AC Offshore
Park Module Transmission System is connected to two or more Onshore substations
at its Transmission Interface Points.
Configuration 1 DC One or more DC Connected Power Park Modules that are connected
Connected Power Park to an HVDC System or Transmission DC Converter and that HVDC
Module System or Transmission DC Converter is connected to only one
Onshore substation and which has one or more Transmission Interface
Points.
Configuration 2 DC One or more DC Connected Power Park Modules that are connected
Connected Power Park to an HVDC System or Transmission DC Converter and that HVDC
Module System or Transmission DC Converter is connected to more than one
Onshore substation at its Transmission Interface Points.
Connection Entry Capacity Has the meaning set out in the CUSC.
Connected Planning Data Data which replaces data containing estimated values assumed for
planning purposes by validated actual values and updated estimates for
the future and by updated forecasts for Forecast Data items such as
Demand.
Connection Point A Grid Supply Point or Grid Entry Point, as the case may be.
Connection Site A Transmission Site or User Site, as the case may be.
Consumer Representative Means the person appointed by the Citizens Advice or the Citizens
Advice Scotland (or any successor body) representing all categories of
customers, appointed in accordance with GR.4.2(b)
Contingency Reserve The margin of generation over forecast Demand which is required in the
period from 24 hours ahead down to real time to cover against
uncertainties in Large Power Station availability and against both
weather forecast and Demand forecast errors.
Control Based Reactive The Reactive Power supplied by a Grid Forming Plant through
Power controlled means based on operator adjustment selectable setpoints
(these may be manual or automatic).
Control Calls Telephone calls whose destination and/or origin is a Control Centre or
Control Point, either from dedicated control desk telephone systems or
dedicated telephone handsets, and which, for the purpose of Control
Telephony, have the right to exercise priority over (ie. disconnect) a call
of a lower status.
Control Centre A location used for the purpose of control and operation of the National
Electricity Transmission System or DC Converter Station owner's
System or HVDC System Owner’s System or a User System other than
a Generator's System or an External System.
Control Engineer A person nominated by the relevant party for the control of its Plant and
Apparatus.
Control Person The term used as an alternative to "Safety Co-ordinator" on the Site
Responsibility Schedule only.
Control Phase
The Control Phase follows on from the Programming Phase and covers
the period down to real time.
Core Industry Document In relation to a Core Industry Document, the body(ies) or entity(ies)
Owner responsible for the management and operation of procedures for making
changes to such document
CUSC Has the meaning set out in The Company’s Transmission Licence
CUSC Framework Has the meaning set out in The Company’s Transmission Licence.
Agreement
CUSC Party As defined in the The Company’s Transmission Licence and “CUSC
Parties” shall be construed accordingly.
Customer A person to whom electrical power is provided (whether or not they are
the same person as the person who provides the electrical power).
Customer Demand The level above which a Supplier has to notify The Company of its
Management Notification proposed or achieved use of Customer Demand Management which is
Level 12 MW in England and Wales and 5 MW in Scotland.
Customer Generating Plant A Power Station or Generating Unit or Power Generating Module of a
Customer to the extent that it operates the same exclusively to supply all
or part of its own electricity requirements, and does not export electrical
power to any part of the Total System.
Damping Factor (ζ) The ratio of the actual damping to critical damping.
For a GBGF-I the open loop phase angle, for an open loop gain of one,
is measured from the systems Nichols Chart.
This angle is used to define the system’s equivalent Damping Factor that
is the same as the Damping Factor of a second order system with the
same open loop phase angle.
Alternatively, the Damping Factor refers to the damping of a specific
oscillation mode that is associated with the second order system created
by the power to angle transfer function as show in Figure PC.A.5.8.1(a)
and PCA.5.8.1(b).
Data Registration Code or That portion of the Grid Code which is identified as the Data Registration
DRC Code.
Data Validation, The rules relating to validity and consistency of data, and default data to
Consistency and Defaulting be applied, in relation to data submitted under the Balancing Codes, to
Rules be applied by The Company under the Grid Code as set out in the
document “Data Validation, Consistency and Defaulting Rules” - Issue 8,
dated 25th January 2012. The document is available on the National Grid
website or upon request from The Company.
DC Connected Power Park A Power Park Module that is connected to one or more HVDC
Module Interface Points.
DC Network All items of Plant and Apparatus connected together on the direct current
side of a DC Converter or HVDC System.
Defence Service Provider A User with a legal or contractual obligation to provide a service
contributing to one or several measures of the System Defence Plan or
a party with a contract to meet one or more measures of the System
Defence Plan.
Defined Active Damping The Active Damping Power supplied by a GBGF-I when it is operating
Power at the Grid Oscillation Value defined in Table PC.A.5.8.2
De-Load The condition in which a Genset has reduced or is not delivering electrical
power to the System to which it is Synchronised.
𝜟𝒇 Deviation from Target Frequency
Demand The demand of MW and MVAr of electricity (i.e. both Active and Reactive
Power), unless otherwise stated.
Demand Aggregation A process where one or more Demand Facilities or Closed Distribution
Systems can be controlled by a Demand Response Provider either as
a single facility or Closed Distribution System for the purposes of
offering one or more Demand Response Services.
Demand Control Any or all of the following methods of achieving a Demand reduction:
(a) Customer voltage reduction initiated by Network Operators
(other than following an instruction from The Company);
(b) Customer Demand reduction by Disconnection initiated by
Network Operators (other than following an instruction from The
Company);
(c) Demand reduction instructed by The Company;
(d) automatic low Frequency Demand Disconnection;
(e) emergency manual Demand Disconnection.
Demand Control The level above which a Network Operator has to notify The Company
Notification Level of its proposed or achieved use of Demand Control which is 12 MW in
England and Wales and 5 MW in Scotland.
Demand Facility A facility which consumes electrical energy and is connected at one or
more Grid Supply Points to the National Electricity Transmission
System or connection points to a Network Operator’s System. A
Network Operator’s System and/or auxiliary supplies of a Power
Generating Module do no constitute a Demand Facility.
Demand Facility Owner A person who owns or operates one or more Demand Units within a
Demand Facility. A Demand Facility Owner who owns or operates a
Demand Facility which is directed connected to the Transmission
System shall be treated as a Non-Embedded Customer.
Demand Response Active Demand within a Demand Facility or Closed Distribution System that
Power Control is available for modulation by The Company or Network Operator or
Relevant Transmission Licensee, which results in an Active Power
modification.
Demand Response Provider A party (other than The Company) who owns, operates, controls or
manages Main Plant and Apparatus (excluding storage equipment)
which was first connected to the Total System on or after 18 August 2019
and who had placed Purchase Contracts for its Main Plant and
Apparatus on or after 7 September 2018 or is the subject of a
Substantial Modification on or after 18 August 2019 and has an
agreement with The Company to provide a Demand Response
Service(s). The party may be one or more Customers, a Network
Operator or Non-Embedded Customer or EU Code User contracting
bilaterally with The Company for the provision of services, or may be a
third party providing Demand Aggregation from many individual
Customers.
Demand Response A Demand Response Service derived from Reactive Power or
Reactive Power Control Reactive Power compensation devices in a Demand Facility or Closed
Distribution System that are available for modulation by The Company
or Network Operator or Relevant Transmission Licensee.
Demand Response A Demand Response Service derived from Demand within a Demand
Transmission Constraint Facility or Closed Distribution System that is available for modulation
Management by The Company or Network Operator or Relevant Transmission
Licensee to manage transmission constraints within the System.
The above Demand Response Services are not exclusive and do not
preclude Demand Response Providers from negotiating other services
for demand response capability with The Company. Where such
services are negotiated they would still be treated as a Demand
Response Service.
Demand Response That portion of the Grid Code which is identified as the Demand
Services Code (DRSC) Response Services Code being applicable to Demand Response
Providers.
Demand Response System A Demand Response Service derived from a Demand within one or
Frequency Control more Demand Facilities or Closed Distribution Systems that is
available for the reduction or increase in response to Frequency
fluctuations, made by an autonomous response from those Demand
Facilities or Closed Distribution Systems to diminish these
fluctuations.
Demand Response Unit A document, issued either by the Non-Embedded Customer, Demand
Document (DRUD) Facility Owner or the CDSO to The Company or the Network Operator
(as the case may be) for Demand Units with demand response and
providing a Demand Response Service which confirms the compliance
of the Demand Unit with the technical requirements set out in the Grid
Code and provides the necessary data and statements, including a
statement of compliance.
Demand Response Very A Demand Response Service derived from a Demand within a Demand
Fast Active Power Control Facility or Closed Distribution System that can be modulated very fast
in response to a Frequency deviation, which results in a very fast Active
Power modification.
Demand Unit An indivisible set of installations containing equipment which can be
actively controlled at one or more sites by a Demand Response
Provider, Demand Facility Owner, CDSO or by a Non Embedded
Customer, either individually or commonly as part of Demand
Aggregation through a third party who has agreed to provide Demand
Response Services.
Designed Minimum The output (in whole MW) below which a Genset or a DC Converter at a
Operating Level DC Converter Station (in any of its operating configurations) has no High
Frequency Response capability.
De-synchronised Island A formal procedure as set out in OC9.5.4 for the purpose of
Procedure Synchronising Power Islands
Detailed Planning Data Detailed additional data which The Company requires under the PC in
support of Standard Planning Data, comprising DPD I and DPD II.
Detailed Planning Data The Detailed Planning Data categorised as such in the DRC, and
Category II or DPD II submitted in accordance with PC.4.4.2 or PC.4.4.4 as applicable.
Disconnection The physical separation of Users (or Customers) from the National
Electricity Transmission System or a User System as the case may
be.
Discrimination The quality where a relay or protective system is enabled to pick out and
cause to be disconnected only the faulty Apparatus.
Disputes Resolution The procedure described in the CUSC relating to disputes resolution.
Procedure
Dynamic Parameters Those parameters listed in Appendix 1 to BC1 under the heading BM Unit
Data – Dynamic Parameters.
Dynamic Reactive Plant and Apparatus capable of injecting or absorbing Reactive Power
Compensation Equipment in a controlled manner which includes but is not limited to Synchronous
Compensators, Static Var Compensators (SVC), or STATCOM devices.
E&W Transmission System Collectively NGET’s Transmission System and any E&W Offshore
Transmission Systems.
E&W User A User in England and Wales or any Offshore User who owns or
operates Plant and/or Apparatus connected (or which will at the OTSUA
Transfer Time be connected) to an E&W Offshore Transmission
System.
Earth Fault Factor At a selected location of a three-phase System (generally the point of
installation of equipment) and for a given System configuration, the ratio
of the highest root mean square phase-to-earth power Frequency
voltage on a sound phase during a fault to earth (affecting one or more
phases at any point) to the root mean square phase-to-earth power
Frequency voltage which would be obtained at the selected location
without the fault.
Earthing Device A means of providing a connection between a conductor and earth being
of adequate strength and capability.
Electricity Council That body set up under the Electricity Act, 1957.
Electricity Distribution The licence granted pursuant to Section 6(1) (c) of the Act.
Licence
Electricity Storage The conversion of electrical energy into a form of energy which can be
stored, the storing of that energy, and the subsequent reconversion of
that energy back into electrical energy.
Electricity Storage Module Is either one or more Synchronous Electricity Storage Unit(s) or Non-
Synchronous Electricity Storage Unit(s) which could also be part of a
Power Generating Module. For the avoidance of doubt, Non-
Controllable Electricity Storage Equipment would not be considered
to be classed as an Electricity Storage Module or as an Electricity
Storage Unit.
Electricity Supply Industry The unincorporated members' club of that name formed inter alia to
Arbitration Association promote the efficient and economic operation of the procedure for the
resolution of disputes within the electricity supply industry by means of
arbitration or otherwise in accordance with its arbitration rules.
Electricity Supply Licence The licence granted pursuant to Section 6(1) (d) of the Act.
Electronic Power Converter Electrical Plant and Apparatus which uses switched solid state power
electronic devices to produce a real voltage waveform, that has a
fundamental component with harmonics.
Embedded Person The party responsible for a Medium Power Station not subject to a
Bilateral Agreement or DC Converter Station not subject to a Bilateral
Agreement or HVDC System not subject to a Bilateral Agreement
connected to or proposed to be connected to a Network Operator’s
System.
EMR Administrative Parties Has the meaning given to “administrative parties” in The Electricity
Capacity Regulations 2014 and each CfD Counterparty and CfD
Settlement Services Provider.
EMR Documents The Energy Act 2013, The Electricity Capacity Regulations 2014, the
Capacity Market Rules, The Contracts for Difference (Allocation)
Regulations 2014, The Contracts for Difference (Definition of Eligible
Generator) Regulations 2014, The Contracts for Difference (Electricity
Supplier Obligations) Regulations 2014, The Electricity Market Reform
(General) Regulations 2014, the AF Rules and any other regulations or
instruments made under Chapter 2 (contracts for difference), Chapter 3
(capacity market) or Chapter 4 (investment contracts) of Part 2 of the
Energy Act 2013 which are in force from time to time.
Engineering The documents referred to as such and issued by the Energy Networks
Recommendations Association or the former Electricity Council.
Energisation Operational A notification (in respect of Plant and Apparatus (including OTSUA)
Notification or EON which is directly connected to the National Electricity Transmission
System) from The Company to a User confirming that the User can in
accordance with the Bilateral Agreement and/or Construction
Agreement, energise such User’s Plant and Apparatus (including
OTSUA) specified in such notification.
Estimated Registered Data Those items of Standard Planning Data and Detailed Planning Data
which either upon connection will become Registered Data, or which for
the purposes of the Plant and/or Apparatus concerned as at the date of
submission are Registered Data, but in each case which for the seven
succeeding Financial Years will be an estimate of what is expected.
European Compliance That portion of the Grid Code which is identified as the European
Processes or ECP Compliance Processes.
European Connection That portion of the Grid Code which is identified as the European
Conditions or ECC Connection Conditions being applicable to EU Code Users.
Exciter The source of the electrical power providing the field current of a
synchronous machine.
Excitation System The equipment providing the field current of a machine, including all
regulating and control elements, as well as field discharge or suppression
equipment and protective devices.
Excitation System No-Load The minimum value of direct voltage that the Excitation System is able
Negative Ceiling Voltage to provide from its terminals when it is not loaded, which may be zero or
a negative value.
Excitation System On-Load Shall have the meaning ascribed to the term 'Excitation system on load
Positive Ceiling Voltage ceiling voltage' in IEC 34-16-1:1991[equivalent to British Standard
BS4999 Section 116.1: 1992].
Excitation System No-Load Shall have the meaning ascribed to the term 'Excitation system no load
Positive Ceiling Voltage ceiling voltage' in IEC 34-16-1:1991[equivalent to British Standard
BS4999 Section 116.1: 1992].
Existing AGR Plant The following nuclear advanced gas cooled reactor plant (which was
commissioned and connected to the Total System at the Transfer
Date):-
(a) Dungeness B
(b) Hinkley Point B
(c) Heysham 1
(d) Heysham 2
(e) Hartlepool
(f) Hunterston B
(g) Torness
Existing AGR Plant In respect of each Genset within each Existing AGR Plant which has a
Flexibility Limit safety case enabling it to so operate, 8 (or such lower number which when
added to the number of instances of reduction of output as instructed by
The Company in relation to operation in Frequency Sensitive Mode
totals 8) instances of flexibility in any calendar year (or such lower or
greater number as may be agreed by the Nuclear Installations
Inspectorate and notified to The Company) for the purpose of assisting
in the period of low System NRAPM and/or low Localised NRAPM
provided that in relation to each Generating Unit each change in output
shall not be required to be to a level where the output of the reactor is less
than 80% of the reactor thermal power limit (as notified to The Company
and which corresponds to the limit of reactor thermal power as contained
in the "Operating Rules" or "Identified Operating Instructions" forming part
of the safety case agreed with the Nuclear Installations Inspectorate).
Existing Gas Cooled Both Existing Magnox Reactor Plant and Existing AGR Plant.
Reactor Plant
Export and Import Limits Those parameters listed in Appendix 1 to BC1 under the heading BM Unit
Data – Export and Import Limits.
External Interconnection Apparatus for the transmission of electricity to or from the National
Electricity Transmission System or a User System into or out of an
External System. For the avoidance of doubt, a single External
Interconnection may comprise several circuits operating in parallel.
External Interconnection Plant or Apparatus which comprises a circuit and which operates in
Circuit parallel with another circuit and which forms part of the External
Interconnection.
Externally Interconnected A person who operates an External System which is connected to the
System Operator or EISO National Electricity Transmission System or a User System by an
External Interconnection.
Fault Current Interruption The time interval from fault inception until the end of the break time of the
Time circuit breaker (as declared by the manufacturers).
Fault Ride Through The capability of Power Generating Modules (including DC Connected
Power Park Modules) and HVDC Systems to be able to remain
connected to the System and operate through periods of low voltage at
the Grid Entry Point or User System Entry Point caused by secured
faults.
Fast Start A start by a Genset with a Fast Start Capability.
Fast Start Capability The ability of a Genset to be Synchronised and Loaded up to full Load
within 5 minutes.
Issue 6 Revision 21 GD 04 March 2024
27 of 84
Fast Track Criteria A proposed Grid Code Modification Proposal that, if implemented,
(a) would meet the Self-Governance Criteria; and
(b) is properly a housekeeping modification required as a result of some
error or factual change, including but not limited to:
(i) updating names or addresses listed in the Grid Code;
(ii) correcting any minor typographical errors;
(iii) correcting formatting and consistency errors, such as
paragraph numbering; or
(iv) updating out of date references to other documents or
paragraphs
Fault Current Interruption The time interval from fault inception until the end of the break time of the
Time circuit breaker (as declared by the manufacturers).
Fault Ride Through The capability of Power Generating Modules (including DC Connected
Power Park Modules) and HVDC Systems to be able to remain
connected to the System and operate through periods of low voltage at
the Grid Entry Point or User System Entry Point caused by secured
faults.
Final Generation Outage An outage programme as agreed by The Company with each Generator
Programme and each Interconnector Owner at various stages through the
Operational Planning Phase and Programming Phase which does not
commit the parties to abide by it, but which at various stages will be used
as the basis on which National Electricity Transmission System
outages will be planned.
Final Physical Notification Has the meaning set out in the BSC.
Data
Final Report A report prepared by the Test Proposer at the conclusion of a System
Test for submission to The Company (if it did not propose the System
Test) and other members of the Test Panel.
Financial Year Bears the meaning given in Condition A1 (Definitions and Interpretation)
of The Company’s Transmission Licence.
Flicker Severity A measure of the visual severity of flicker derived from the time series
(Short Term) output of a flickermeter over a 10 minute period and as such provides an
indication of the risk of Customer complaints.
Forecast Data Those items of Standard Planning Data and Detailed Planning Data
which will always be forecast.
Frequency The number of alternating current cycles per second (expressed in Hertz)
at which a System is running.
Frequency Containment means, in the context of Balancing Services, the Active Power reserves
Reserves (FCR) available to contain System Frequency after the occurrence of an
imbalance.
Frequency Response An interval used intentionally to make the Frequency control
Deadband unresponsive.
In the case of mechanical governor systems, the Frequency Response
Deadband is the same as Frequency Response Insensitivity.
Frequency Response The inherent feature of the control system specified as the minimum
Insensitivity magnitude of change in the Frequency or input signal that results in a
change of output power or output signal.
Frequency Restoration Means, in the context of Balancing Services, the Active Power reserves
Reserves (FRR) available to restore System Frequency to the nominal Frequency.
Frequency Sensitive AGR Each Generating Unit in an Existing AGR Plant for which the
Unit Generator has notified The Company that it has a safety case agreed
with the Nuclear Installations Inspectorate enabling it to operate in
Frequency Sensitive Mode, to the extent that such unit is within its
Frequency Sensitive AGR Unit Limit. Each such Generating Unit shall
be treated as if it were operating in accordance with BC3.5.1 provided
that it is complying with its Frequency Sensitive AGR Unit Limit.
Frequency Sensitive Mode A Genset, or Type C Power Generating Module or Type D Power
Generating Module or DC Connected Power Park Module or HVDC
System operating mode which will result in Active Power output
changing, in response to a change in System Frequency, in a direction
which assists in the recovery to Target Frequency, by operating so as to
provide Primary Response and/or Secondary Response and/or High
Frequency Response.
Fuel Security Code The document of that title designated as such by the Secretary of State,
as from time to time amended.
Gas Turbine Unit A Generating Unit driven by a gas turbine (for instance by an aero-
engine).
Gas Zone Diagram A single line diagram showing boundaries of, and interfaces between,
gas-insulated HV Apparatus modules which comprise part, or the whole,
of a substation at a Connection Site (or in the case of OTSDUW Plant
and Apparatus, Transmission Interface Site), together with the
associated stop valves and gas monitors required for the safe operation
of the National Electricity Transmission System or the User System,
as the case may be.
GBGF Fast Fault Current The ability of a Grid Forming Plant to supply reactive current, that starts
Injection to be delivered into the Total System in less than 5ms when the voltage
falls below 90% of its nominal value at the Grid Entry Point or User
System Entry Point.
GB Grid Forming - Inverter Is any Power Park Module, HVDC System, DC Converter, OTSDUW
or GBGF-I Plant and Apparatus, Non-Synchronous Electricity Storage Module,
Dynamic Reactive Compensation Equipment or any Plant and
Apparatus (including a smart load) which is connected or partly
connected to the Total System via an Electronic Power Converter
which has a Grid Forming Capability (GBGF-I).
General Conditions or GC That portion of the Grid Code which is identified as the General
Conditions.
Generating Plant Demand The difference between Output Usable and forecast Demand.
Margin
Generating Unit Data The Physical Notification, Export and Import Limits and Other
Relevant Data only in respect of each Generating Unit (which could be
part of a Power Generating Module):
(a) which forms part of the BM Unit which represents that Cascade
Hydro Scheme;
(b) at an Embedded Exemptable Large Power Station, where the
relevant Bilateral Agreement specifies that compliance with BC1
and/or BC2 is required:
(i) to each Generating Unit, or
(ii) to each Power Park Module where the Power Station
comprises Power Park Modules.
Generator Performance A diagram which shows the MW and MVAr capability limits within which
Chart a Generating Unit will be expected to operate under steady state
conditions.
Governance Rules or GR That portion of the Grid Code which is identified as the Governance
Rules.
Great Britain or GB The landmass of England and Wales and Scotland, including internal
waters.
Grid Code Fast Track A proposal to modify the Grid Code which is raised pursuant to GR.26
Proposals and has not yet been approved or rejected by the Grid Code Review
Panel.
Grid Code Modification The procedures for the modification of the Grid Code (including the
Procedures implementation of Approved Modifications) as set out in the
Governance Rules.
Grid Code Modification A proposal to modify the Grid Code which is not yet rejected pursuant to
Proposal GR.15.5 or GR.15.6 and has not yet been implemented.
Grid Code Objectives Means the objectives referred to in Paragraph 1b of Standard Condition
C14 of The Company’s Transmission Licence.
Grid Code Review Panel or The panel with the functions set out in GR.1.2.
Panel
Grid Code Review Panel The vote of Panel Members undertaken by the Panel Chairperson in
Recommendation Vote accordance with Paragraph GR.22.4 as to whether in their view they
believe each proposed Grid Code Modification Proposal, or
Workgroup Alternative Grid Code Modification would better facilitate
achievement of the Grid Code Objective(s) and so should be made.
Grid Code Review Panel The vote of Panel Members undertaken by the Panel Chairperson in
Self-Governance Vote accordance with GR.24.9 as to whether they believe each proposed Grid
Code Modification Proposal, as compared with the then existing
provisions of the Grid Code and any Workgroup Alternative Grid Code
Modification set out in the Grid Code Modification Self-Governance
Report, would better facilitate achievement of the Grid Code
Objective(s).
Grid Entry Point An Onshore Grid Entry Point or an Offshore Grid Entry Point.
Grid Forming Active Power Grid Forming Active Power is the inherent Active Power produced by
Grid Forming Plant that includes Active Inertia Power plus Active
Phase Jump Power plus Active Damping Power.
Grid Forming Capability Is (but not limited to) the capability a Power Generating Module, HVDC
Converter (which could form part of an HVDC System), Generating
Unit, Power Park Module, DC Converter, OTSDUW Plant and
Apparatus, Electricity Storage Module, Dynamic Reactive
Compensation Equipment or any Plant and Apparatus (including a
smart load) whose supplied Active Power is directly proportional to the
difference between the magnitude and phase of its Internal Voltage
Source and the magnitude and phase of the voltage at the Grid Entry
Point or User System Entry Point and the sine of the Load Angle. As
a consequence, Plant and Apparatus which has a Grid Forming
Capability has a frequency of rotation of the Internal Voltage Source
which is the same as the System Frequency for normal operation, with
only the Load Angle defining the relative position between the two. In
the case of a GBGF-I, a Grid Forming Unit forming part of a GBGF-I
shall be capable of sustaining a voltage at its terminals irrespective of the
voltage at the Grid Entry Point or User System Entry Point for normal
operating conditions.
For GBGF-I, the control system, which determines the amplitude and
phase of the Internal Voltage Source, shall have a response to the
voltage and System Frequency at the Grid Entry Point or User System
Entry Point) with a bandwidth that is less than a defined value as shown
by the control system’s NFP Plot. Exceptions to this requirement are only
allowed during transients caused by System faults, voltage dips/surges
and/or step or ramp changes in the phase angle which are large enough
to cause damage to the Grid Forming Plant via excessive currents.
Grid Forming Electronic A Grid Forming Plant whose output is derived from an Electronic Power
Power Converter Converter with a GBGF-I capability.
Grid Forming Plant A site which contains Plant and Apparatus which is classified as either
a GBGF-S or a GBGF-I
Grid Forming Plant Owner The owner or operator of a Grid Forming Plant.
Grid Forming Unit A Power Park Unit or Electricity Storage Unit or a Synchronous
Power Generating Unit or individual Load with a Grid Forming
Capability.
Grid Oscillation Value An injected test frequency signal applied at nominal System Frequency
with a superimposed oscillatory response overlayed onto the nominal
System Frequency with an amplitude of 0.05 Hz peak to peak at a
frequency of 1 Hz and is used for determining the rating of the Defined
Active Damping Power.
Headroom The Power Available (in MW) less the actual Active Power exported
from the Power Park Module (in MW).
High Voltage or HV For E&W Transmission Systems, a voltage exceeding 650 volts. For
Scottish Transmission Systems, a voltage exceeding 1000 volts.
Historic Frequency Data System Frequency data at a maximum of one second intervals for the
whole month, published by The Company as detailed in OC3.4.4.
Houseload Operation Operation which ensures that a Power Station is able to continue to
supply its in-house load in the event of System faults resulting in Power-
Generating Modules being disconnected from the System and tripped
onto their auxiliary supplies
HP Turbine Power Fraction Ratio of steady state mechanical power delivered by the HP turbine to the
total steady state mechanical power delivered by the total steam turbine
at Registered Capacity or Maximum Capacity.
Implementation Date Is the date and time for implementation of an Approved Modification as
specified in accordance with Paragraph GR.25.3.
Incident Centre A centre established by The Company or a User as the focal point in The
Company or in that User, as the case may be, for the communication
and dissemination of information between the senior management
representatives of The Company, or of that User, as the case may be,
and the relevant other parties during a Joint System Incident in order to
avoid overloading The Company's, or that User's, as the case may be,
existing operational/control arrangements.
Independent Back-Up A Back-Up Protection system which utilises a discrete relay, different
Protection current transformers and an alternate operating principle to the Main
Protection systems(s) such that it can operate autonomously in the event
of a failure of the Main Protection.
Independent Main A Main Protection system which utilises a physically discrete relay and
Protection different current transformers to any other Main Protection.
Indicated Constraint The difference between a constraint boundary transfer limit and the
Boundary Margin difference between the sum of BM Unit Maximum Export Limits and the
forecast of local Demand within the constraint boundary.
Indicated Imbalance The difference between the sum of Physical Notifications for BM Units
comprising Generating Units or CCGT Modules or Power Generating
Modules and the forecast of Demand for the whole or any part of the
System.
Inertia Constant He For a GBGF- I Electronic Power Converter the Inertia Constant He, is
measured in MWsec/MVA and produced by the Active ROCOF
Response Power.
Instructor Facilities A device or system which gives certain Transmission Control Centre
instructions with an audible or visible alarm, and incorporates the means
to return message acknowledgements to the Transmission Control
Centre.
Integral Equipment Test or A test on equipment, associated with Plant and/or Apparatus, which
IET takes place when that Plant and/or Apparatus forms part of a
Synchronised System and which, in the reasonable judgement of the
person wishing to perform the test, may cause an Operational Effect.
Intellectual Property" or Patents, trade marks, service marks, rights in designs, trade names,
"IPRs copyrights and topography rights (whether or not any of the same are
registered and including applications for registration of any of the same)
and rights under licences and consents in relation to any of the same and
all rights or forms of protection of a similar nature or having equivalent or
similar effect to any of the same which may subsist anywhere in the world.
Interconnector Owner Has the meaning given to the term in the Connection and Use of
System Code.
Interface Point Capacity The maximum amount of Active Power transferable at the Interface
Point as declared by a User under the OTSDUW Arrangements
expressed in whole MW.
Interface Point Target The nominal target voltage/power factor at an Interface Point which a
Voltage/Power factor Network Operator requires The Company to achieve by operation of the
relevant Offshore Transmission System.
Intermittent Power Source The primary source of power for a Generating Unit or Power Generating
Module that cannot be considered as controllable, e.g. wind, wave or
solar. For the avoidance of doubt, the output from an Electricity Storage
Module would not be considered to be an Intermittent Power Source.
Internal Voltage Source or For a GBGF-S, a real magnetic field, that rotates synchronously with the
IVS System Frequency under normal operating conditions, which as a
consequence induces an internal voltage (which is often referred to as
the Electro Motive Force (EMF)) in the stationary generator winding that
has a real impedance.
In a GBGF-I, switched power electronic devices are used to produce a
voltage waveform, with harmonics, that has a fundamental rotational
component called the Internal Voltage Source (IVS) that rotates
synchronously with the System Frequency under normal operating
conditions.
For a GBGF-I there must be an impedance with only real physical values,
between the Internal Voltage Source and the Grid Entry Point or User
System Entry Point.
For the avoidance of doubt, a virtual impedance, is not permitted in
GBGF-I.
IP Turbine Power Fraction Ratio of steady state mechanical power delivered by the IP turbine to the
total steady state mechanical power delivered by the total steam turbine
at Registered Capacity or Maximum Capacity.
Joint System Incident An Event wherever occurring (other than on an Embedded Medium
Power Station or an Embedded Small Power Station) which, in the
opinion of The Company or a User, has or may have a serious and/or
widespread effect, in the case of an Event on a User(s) System(s) (other
than on an Embedded Medium Power Station or Embedded Small
Power Station), on the National Electricity Transmission System, and
in the case of an Event on the National Electricity Transmission
System, on a User(s) System(s) (other than on an Embedded Medium
Power Station or Embedded Small Power Station).
Legally Binding Decisions Any relevant legally binding decision or decisions of the European
of the European Commission and/or the Agency, but a binding decision does not include
Commission and/or the a decision that is not, or so much of a decision as is not, Retained EU
Agency Law.
Limited Frequency A mode whereby the operation of the Genset or Power Generating
Sensitive Mode Module (or DC Converter at a DC Converter Station or HVDC Systems
exporting Active Power to the Total System) is Frequency insensitive
except when the System Frequency exceeds 50.4Hz, from which point
Limited High Frequency Response must be provided. For Power
Generating Modules (including DC Connected Power Park Modules)
and HVDC Systems, operation in Limited Frequency Sensitive Mode
would require Limited Frequency Sensitive Mode – Overfrequency
(LFSM-O) capability and Limited Frequency Sensitive Mode –
Underfrequency (LFSM-U) capability.
Limited Frequency A Power Generating Module (including a DC Connected Power Park
Sensitive Mode – Module) or HVDC System operating mode which will result in Active
Overfrequency or LFSM-O Power output reduction in response to a change in System Frequency
above a certain value.
Limited Frequency A Power Generating Module (including a DC Connected Power Park
Sensitive Mode – Module) or HVDC System operating mode which will result in Active
Underfrequency or LFSM-U Power output increase in response to a change in System Frequency
below a certain value.
Load Factor The ratio of the actual output of a Generating Unit or Power Generating
Module to the possible maximum output of that Generating Unit or
Power Generating Module.
Load Management Block A block of Demand controlled by a Supplier or other party through the
means of radio teleswitching or by some other means.
A plan produced and agreed by The Company, Transmission
Local Joint Restoration
Licensee, Restoration Contractors and a Network Operator under
Plan
OC9.4.7.7, detailing the agreed method and procedure by which The
Company or Transmission Licensee in Scotland will instruct
aRestoration Contractor with an Anchor Plant to energise, part of the
Total System within 2 hours of that instruction and subsequently meet
complementary blocks of local Demand so as to form a Power Island. A
Local Joint Restoration Plan may require the use of Top Up
Restoration Plant.
A Local Joint Restoration Plan is distinct from and falls outside the
provisions of a Distribution Restoration Zone Plan.
Local Safety Instructions For safety co-ordination in England and Wales, instructions on each User
Site and Transmission Site, approved by NGET’s or User's relevant
manager, setting down the methods of achieving the objectives of
NGET's or the User's Safety Rules, as the case may be, to ensure the
safety of personnel carrying out work or testing on Plant and/or
Apparatus on which their Safety Rules apply and, in the case of a User,
any other document(s) on a User Site which contains rules with regard to
maintaining or securing the isolating position of an Isolating Device, or
maintaining a physical separation or maintaining or securing the position
of an Earthing Device.
Local Switching Procedure A procedure produced under OC7.6 detailing the agreed arrangements in
respect of carrying out of Operational Switching at Connection Sites
and parts of the National Electricity Transmission System adjacent to
those Connection Sites.
Localised Negative Reserve That margin of Active Power sufficient to allow transfers to and from a
Active Power Margin or System Constraint Group (as the case may be) to be contained within
Localised NRAPM such reasonable limit as The Company may determine.
Low Frequency Relay Has the same meaning as Under Frequency Relay.
Low Voltage or LV For E&W Transmission Systems a voltage not exceeding 250 volts. For
Scottish Transmission Systems, a voltage exceeding 50 volts but not
exceeding 1000 volts.
Main Protection A Protection system which has priority above other Protection in
initiating either a fault clearance or an action to terminate an abnormal
condition in a power system.
Market Operation Data A computer system operated by The Company and made available for
Interface System (MODIS) use by Customers connected to or using the National Electricity
Transmission System for the purpose of submitting EU Transparency
Availability Data to The Company.
Market Suspension Has the meaning given to the term ‘Market Suspension Threshold’ in
Threshold Section G of the BSC.
Materially Affected Party Any person or class of persons designated by the Authority as such.
Maximum Export Capacity The maximum continuous Apparent Power expressed in MVA and
maximum continuous Active Power expressed in MW which can flow
from an Offshore Transmission System connected to a Network
Operator's User System, to that User System.
Maximum Capacity or Pmax The maximum continuous Active Power which a Power Generating
Module can supply to the Total System, less any demand associated
solely with facilitating the operation of that Power Generating Module
and not fed into the System. In the case of an Electricity Storage
Module, the Maximum Capacity is the maximum continuous Active
Power which an Electricity Storage Module can export to the Total
System less any demand associated with facilitating the operation of that
Electricity Storage Module when fully charged and operating in a mode
analogous to Generation.
Maximum Generation A service utilised by The Company in accordance with the CUSC and
Service or MGS the Balancing Principles Statement in operating the Total System.
Maximum Generation An agreement between a User and The Company for the payment by
Service Agreement The Company to that User in respect of the provision by such User of a
Maximum Generation Service.
Maximum HVDC Active The maximum continuous Active Power which an HVDC System can
Power Transmission exchange with the network at each Grid Entry Point or User System
Capacity (PHmax) Entry Point as specified in the Bilateral Agreement or as agreed
between The Company and the HVDC System Owner.
Maximum Import Capability The maximum continuous Active Power that a Network Operator or
Non-Embedded Customer can import from the Transmission System
at the Grid Supply Point, as specified in the Bilateral Agreement.
Maximum Import Capacity The maximum continuous Apparent Power expressed in MVA and
maximum continuous Active Power expressed in MW which can flow to
an Offshore Transmission System connected to a Network Operator's
User System, from that User System.
Maximum Import Power The maximum continuous Active Power which an Electricity Storage
Module can import from the Total System, when fully discharged and
operating in a mode analogous to Demand.
Medium Voltage or MV For E&W Transmission Systems a voltage exceeding 250 volts but not
exceeding 650 volts.
Mills Milling plant which supplies pulverised fuel to the boiler of a coal fired
Power Station.
Minimum Generation The minimum output (in whole MW) which a Genset can generate or DC
Converter at a DC Converter Station or Electricity Storage Module
can import or export to the Total System under stable operating
conditions, as registered with The Company under the PC (and amended
pursuant to the PC). For the avoidance of doubt, the output may go below
this level as a result of operation in accordance with BC3.7.
Minimum Active Power The minimum continuous Active Power which an HVDC System can
Transmission Capacity exchange with the System at each Grid Entry Point or User System
(PHmin) Entry Point as specified in the Bilateral Agreement or as agreed
between The Company and the HVDC System Owner.
Minimum Import Capacity The minimum input (in whole MW) into a DC Converter at a DC
Converter Station or HVDC System at an HVDC Converter (in any of
its operating configurations) at the Onshore Grid Entry Point (or in the
case of an Embedded DC Converter or an Embedded HVDC
Converter at the User System Entry Point) at which a DC Converter or
HVDC Converter can operate in a stable manner, as registered with The
Company under the PC (and amended pursuant to the PC).
Minimum Regulating Level The minimum Active Power, as specified in the Bilateral Agreement or
as agreed between The Company and the Generator or HVDC System
Owner, down to which the Power Generating Module (including a DC
Connected Power Park Module) or HVDC System can control Active
Power.
Mothballed DC Connected A DC Connected Power Park Module that has previously generated
Power Park Module which the Generator plans not to use to generate for the remainder of the
current Financial Year but which could be returned to service.
Mothballed HVDC System An HVDC System that has previously imported or exported power which
the HVDC System Owner plans not to use to import or export power for
the remainder of the current Financial Year but which could be returned
to service.
Mothballed HVDC An HVDC Converter which is part of an HVDC System that has
Converter previously imported or exported power which the HVDC System Owner
plans not to use to import or export power for the remainder of the current
Financial Year but which could be returned to service.
Mothballed Generating Unit A Generating Unit that has previously generated which the Generator
plans not to use to generate for the remainder of the current Financial
Year but which could be returned to service. For the avoidance of doubt
a Mothballed Generating Unit could be part of a Power Generating
Module.
Mothballed Power A Power Generating Module that has previously generated which the
Generating Module Generator plans not to use to generate for the remainder of the current
Financial Year but which could be returned to service.
Mothballed Power Park A Power Park Module that has previously generated which the
Module Generator plans not to use to generate for the remainder of the current
Financial Year but which could be returned to service.
Multiple Point of A double (or more) Point of Connection, being two (or more) Points of
Connection Connection interconnected to each other through the User’s System.
MSID Has the meaning a set out in the BSC, covers Metering System Identifier.
National Electricity The Onshore Transmission System and, where owned by Offshore
Transmission System Transmission Licensees, Offshore Transmission Systems.
National Electricity The amount of electricity supplied from the Grid Supply Points plus:-
Transmission System
Demand • that supplied by Embedded Large Power Stations, and
• exports from the National Electricity Transmission System
across External Interconnections, and
• National Electricity Transmission System Losses,
and, for the purposes of this definition, includes:-
• the Demand taken by Station Transformers and, Pumped
Storage Units and Electricity Storage Modules’.
National Electricity Has the meaning set out in Schedule 1 of The Company's Transmission
Transmission System Licence.
Operator Area
National Electricity A computer file produced by The Company which in The Company’s
Transmission System view provides an appropriate representation of the National Electricity
Study Network Data File Transmission System for a specific point in time. The computer file will
contain information and data on Demand on the National Electricity
Transmission System and on Large Power Stations including Genset
power output consistent with Output Usable and The Company’s view
of prevailing system conditions.
National Electricity A warning issued by The Company to Users (or to certain Users only) in
Transmission System accordance with OC7.4.8.2, which provides information relating to
Warning System conditions or Events and is intended to:
(a) alert Users to possible or actual Plant shortage, System problems
and/or Demand reductions;
(b) inform of the applicable period;
(c) indicate intended consequences for Users; and
(d) enable specified Users to be in a state of readiness to receive
instructions from The Company.
National Electricity A warning issued by The Company, in accordance with OC7.4.8.5, which
Transmission System is intended to invite a response from and to alert recipients to a decreased
Warning - Electricity Margin System Margin.
Notice
National Electricity
A warning issued by The Company, in accordance with OC7.4.8.12,
Transmission System
Warning – which is intended to provide short term notice, where possible, to
Embedded Generation those Network Operators who are likely to receive Embedded
Control Imminent Generation Control instructions from The Company within 30
minutes.
National Electricity A warning issued by The Company, in accordance with OC7.4.8.6, which
Transmission System is intended to alert recipients that there is a high risk of Demand reduction
Warning - High Risk of being implemented and which may normally result from an Electricity
Demand Reduction Margin Notice.
National Electricity A warning issued by The Company, in accordance with OC7.4.8.8, which
Transmission System is intended to alert Users of the risk of widespread and serious System
Warning - Risk of System disturbance which may affect Users.
Disturbance
Network Data The data to be provided by The Company to Users in accordance with
the PC, as listed in Part 3 of the Appendix to the PC.
Network Gas Supply Has the meaning set out in the BSC.
Emergency
Network Operator A person with a User System directly connected to the National
Electricity Transmission System to which Customers and/or Power
Stations (not forming part of the User System) are connected, acting in
its capacity as an operator of the User System, but shall not include a
person acting in the capacity of an Externally Interconnected System
Operator or a Generator in respect of OTSUA.
Nichols Chart For a GBGF-I, a chart derived from the open loop Bode Plots that are
used to produce an NFP Plot. The Nichols Chart plots open loop gain
versus open loop phase angle. This enables the open loop phase for an
open loop gain of 1 to be identified for use in defining the GBGF-I’s
equivalent Damping Factor.
No-Load Field Voltage Shall have the meaning ascribed to that term in IEC 34-16-1:1991
[equivalent to British Standard BS4999 Section 116.1 : 1992].
Non-CUSC Party A Party who does not accede to the Connection and Use of System
Code (CUSC).
Non-Controllable Electricity An item of storage Plant, including but not limited to a Synchronous
Storage Equipment Flywheel or Synchronous Compensation Equipment or Regenerative
Braking whose active output power cannot be independently controlled.
Non-Embedded Customer A Customer in Great Britain, except for a Network Operator acting in
its capacity as such, receiving electricity direct from the Onshore
Transmission System irrespective of from whom it is supplied.
Non-Synchronous A Power Park Unit which can produce electrical energy by converting or
Electricity Storage Unit re-converting another source of energy such that the frequency of the
generated voltage is not inherently in synchronism with the frequency of
the System.
Normal CCGT Module A CCGT Module other than a Range CCGT Module.
Novel Unit A tidal, wave, wind, geothermal, or any similar, Generating Unit.
Offshore Means wholly or partly in Offshore Waters, and when used in conjunction
with another term and not defined means that the associated term is to
be read accordingly.
Offshore DC Converter Any User Apparatus located Offshore used to convert alternating
current electricity to direct current electricity, or vice versa. An Offshore
DC Converter is a standalone operative configuration at a single site
comprising one or more converter bridges, together with one or more
converter transformers, converter control equipment, essential protective
and switching devices and auxiliaries, if any, used for conversion.
Offshore HVDC Converter Any User Apparatus located Offshore used to convert alternating
current electricity to direct current electricity, or vice versa. An Offshore
HVDC Converter is a standalone operative configuration at a single site
comprising one or more converter bridges, together with one or more
converter transformers, converter control equipment, essential protective
and switching devices and auxiliaries, if any, used for conversion.
Offshore Generating Unit Unless otherwise provided in the Grid Code, any Apparatus located
Offshore which produces electrical energy by converting or re-converting
another source of energy, including, an Offshore Synchronous
Generating Unit or Offshore Non-Synchronous Generating Unit
which could also be part of a Power Generating Module or Electricity
Storage Module
Offshore Platform A single structure comprising of Plant and Apparatus located Offshore
which includes one or more Offshore Grid Entry Points.
Offshore Power Park String A collection of Offshore Generating Units or Power Park Units or Non-
Synchronous Electricity Storage Unit that are powered by an
Intermittent Power Source, joined together by cables forming part of a
User System with a single point of connection to an Offshore
Transmission System. The connection to an Offshore Transmission
System may include a DC Converter or HVDC Converter.
Offshore Tender Process The process followed by the Authority to make, in prescribed cases, a
determination on a competitive basis of the person to whom an offshore
transmission licence is to be granted.
Offshore Transmission An agreement entered into by The Company and a Network Operator
Distribution Connection in respect of the connection to and use of a Network Operator’s User
Agreement System by an Offshore Transmission System.
Offshore Transmission Such person in relation to whose Transmission Licence the standard
Licensee conditions in Section E (offshore transmission owner standard conditions)
of such Transmission Licence have been given effect, or any person in
that prospective role who has acceded to the STC.
Offshore Transmission A system consisting (wholly or mainly) of high voltage electric lines and
System used for the transmission of electricity from one Power Station to a sub-
station or to another Power Station or between sub-stations, and
includes any Plant and Apparatus (including OTSUA) and meters in
connection with the transmission of electricity but does not include any
Remote Transmission Assets. An Offshore Transmission System
extends from the Interface Point, or the Offshore Grid Entry Point(s)
and may include Plant and Apparatus located Onshore and Offshore
and, where the context permits, references to the Offshore
Transmission System includes OTSUA.
Offshore Transmission OTSDUW Plant and Apparatus constructed and/or installed by a User
System User Assets or under the OTSDUW Arrangements which form an Offshore
OTSUA Transmission System that once transferred to a Relevant
Transmission Licensee under an Offshore Tender Process will
become part of the National Electricity Transmission System.
Offshore Waters Has the meaning given to “offshore waters” in Section 90(9) of the Energy
Act 2004.
Offshore Works In relation to a particular User, means those assumptions set out in
Assumptions Appendix P of the relevant Construction Agreement as amended from
time to time.
Onshore Means within Great Britain, and when used in conjunction with another
term and not defined means that the associated term is to be read
accordingly.
Onshore DC Converter Any User Apparatus located Onshore with a Completion Date after 1st
April 2005 used to convert alternating current electricity to direct current
electricity, or vice versa. An Onshore DC Converter is a standalone
operative configuration at a single site comprising one or more converter
bridges, together with one or more converter transformers, converter
control equipment, essential protective and switching devices and
auxiliaries, if any, used for conversion. In a bipolar arrangement, an
Onshore DC Converter represents the bipolar configuration.
Onshore Generating Unit Unless otherwise provided in the Grid Code, any Apparatus located
Onshore which produces electrical energy by converting or re-converting
another source of energy, including, an Onshore Synchronous
Generating Unit or Onshore Non-Synchronous Generating Unit
which could also be part of a Power Generating Module or an Electricity
Storage Module.
Onshore Grid Entry Point A point at which a Onshore Generating Unit or a CCGT Module or a
CCGT Unit or an Onshore Power Generating Module or a Onshore
DC Converter or an Onshore HVDC Converter or a Onshore Power
Park Module or an Onshore Electricity Storage Module or an External
Interconnection, as the case may be, which is directly connected to the
Onshore Transmission System connects to the Onshore
Transmission System.
Onshore HVDC Converter Any User Apparatus located Onshore used to convert alternating
current electricity to direct current electricity, or vice versa. An Onshore
HVDC Converter is a standalone operative configuration at a single site
comprising one or more converter bridges, together with one or more
converter transformers, converter control equipment, essential protective
and switching devices and auxiliaries, if any, used for conversion. In a
bipolar arrangement, an Onshore HVDC Converter represents the
bipolar configuration.
Onshore Power Park A collection of Non-Synchronous Generating Units that are powered
Module by an Intermittent Power Source or connected through power electronic
conversion technology or Non-Synchronous Electricity Storage Units,
joined together by a System (registered as a Power Park Module under
the PC) with a single electrical point of connection directly to the Onshore
Transmission System (or User System if Embedded) with no
intermediate Offshore Transmission System connections. The
connection to the Onshore Transmission System (or User System if
Embedded) may include a DC Converter or HVDC Converter.
Onshore Transmission The system consisting (wholly or mainly) of high voltage electric lines
System owned or operated by Onshore Transmission Licensees or operated
by The Company and used for the transmission of electricity from one
Power Station to a substation or to another Power Station or between
substations or to or from Offshore Transmission Systems or to or from
any External Interconnection, and includes any Plant and Apparatus
and meters owned or operated by any Onshore Transmission Licensee
in connection with the transmission of electricity but does not include any
Remote Transmission Assets.
On-Site Generator Site A site which is determined by the BSC Panel to be a Trading Unit under
the BSC by reason of having fulfilled the Class 1 or Class 2 requirements
as such terms are used in the BSC.
Operating Code or OC That portion of the Grid Code which is identified as the Operating Code.
Operating Reserve The additional output from Large Power Stations or the reduction in
Demand, which must be realisable in real-time operation to respond in
order to contribute to containing and correcting any System Frequency
fall to an acceptable level in the event of a loss of generation or a loss of
import from an External Interconnection or mismatch between
generation and Demand.
Operational Day The period from 0500 hours on one day to 0500 on the following day.
Operation Diagrams Diagrams which are a schematic representation of the HV Apparatus and
the connections to all external circuits at a Connection Site (and in the
case of OTSDUW, Transmission Interface Site), incorporating its
numbering, nomenclature and labelling.
Operational Effect Any effect on the operation of the relevant other System which causes
the National Electricity Transmission System or the System of the
other User or Users, as the case may be, to operate (or be at a materially
increased risk of operating) differently to the way in which they would or
may have operated in the absence of that effect.
Operational Planning Planning through various timescales the matching of generation output
with forecast National Electricity Transmission System Demand
together with a reserve of generation to provide a margin, taking into
account outages of certain Generating Units or Power Generating
Modules, of parts of the National Electricity Transmission System and
of parts of User Systems to which Power Stations and/or Customers
are connected, carried out to achieve, so far as possible, the standards
of security set out in The Company’s Transmission Licence, each
Relevant Transmission Licensee’s Transmission Licence or
Electricity Distribution Licence, as the case may be.
Operational Planning Phase The period from 8 weeks to the end of the 5th year ahead of real time
operation.
Operational Procedures Management instructions and procedures, both in support of the Safety
Rules and for the local and remote operation of Plant and Apparatus,
issued in connection with the actual operation of Plant and/or Apparatus
at or from a Connection Site.
Operational Switching Operation of Plant and/or Apparatus to the instruction of the relevant
Control Engineer. For the avoidance of doubt, the operation of
Transmission Plant and/or Apparatus forming part of the National
Electricity Transmission System will be to the instruction of the
Relevant Transmission Licensee.
OTSDUW Arrangements The arrangements whereby certain aspects of the design, consenting,
construction, installation and/or commissioning of transmission assets are
capable of being undertaken by a User prior to the transfer of those
assets to a Relevant Transmission Licensee under an Offshore
Tender Process.
OTSDUW Data and The data and information to be provided by Users undertaking OTSDUW,
Information to The Company in accordance with Appendix F of the Planning Code.
OTSDUW Development and The timetable for both the delivery of OTSDUW Data and Information
Data Timetable and OTSDUW Network Data and Information as referred to in Appendix
F of the Planning Code and the development of the scope of the
OTSDUW.
OTSDUW Network Data and The data and information to be provided by The Company to Users
Information undertaking OTSDUW in accordance with Appendix F of the Planning
Code.
OTSDUW Plant and Plant and Apparatus, including any OTSDUW DC Converter, designed
Apparatus by the User under the OTSDUW Arrangements.
OTSUA Transfer Time The time and date at which the OTSUA are transferred to a Relevant
Transmission Licensee.
Out of Synchronism The condition where a System or Generating Unit or Power Generating
Module cannot meet the requirements to enable it to be Synchronised.
Output Usable or OU The forecast value (in MW), profiled across the time period affected by
the unplanned or planned Event of the level at which the Genset can
export to the Grid Entry Point, or in the case of Embedded Power
Stations, to the User System Entry Point. In addition, for a Genset
powered by an Intermittent Power Source the forecast value is based
upon the Intermittent Power Source being at a level which would enable
the Genset to generate at Registered Capacity.
For the purpose of OC2 only, the term Output Usable shall include the
terms Interconnector Export Capacity and Interconnector Import
Capacity where the term Output Usable is being applied to an External
Interconnection.
Over-excitation Limiter Shall have the meaning ascribed to that term in IEC 34-16-1:1991
[equivalent to British Standard BS4999 Section 116.1: 1992].
Panel Members’ The recommendation in accordance with the "Grid Code Review Panel
Recommendation Recommendation Vote".
Part 1 System Ancillary Ancillary Services which are required for System reasons and which
Services must be provided by Users in accordance with the Connection
Conditions or European Connection Conditions. An exhaustive list of
Part 1 System Ancillary Services is included in that part of CC.8.1 or
ECC.8.1 headed Part 1.
Part 2 System Ancillary Ancillary Services which are required for System reasons and which
Services must be provided by a User if the User has agreed to provide them under
a Bilateral Agreement. A non-exhaustive list of Part 2 System Ancillary
Services is included in that part of CC.8.1 or ECC.8.1 headed Part 2.
Part Load The condition of a Genset, or Cascade Hydro Scheme which is Loaded
but is not running at its Maximum Export Limit.
For a GBGF-I this is the larger of either the: -
Peak Current Rating
• The registered maximum steady-state current plus the maximum
additional current to supply the Active ROCOF Response
Power plus the Defined Active Damping Power; or.
• The registered maximum steady-state current plus the maximum
additional current to supply the Phase Jump Angle limit power,
or.
This is the maximum short term total current as declared by the Grid
Forming Plant Owner in accordance with PC.A.5.8.1.
Permit for Work for In respect of E&W Transmission Systems, a document issued by the
proximity work Relevant E&W Transmission Licensee or an E&W User in accordance
with its respective Safety Rules to enable work to be carried out in
accordance with OC8A.8 and which provides for Safety Precautions to
be applied and maintained. An example format of a Relevant E&W
Transmission Licensee’s permit for work is attached as Appendix E to
OC8A.
In respect of Scottish Transmission Systems, a document issued by a
Relevant Scottish Transmission Licensee or a Scottish User in
accordance with its respective Safety Rules to enable work to be carried
out in accordance with OC8B.8 and which provides for Safety
Precautions to be applied and maintained. Example formats of Relevant
Scottish Transmission Licensees’ permits for work are attached as
Appendix E to OC8B.
Partial Shutdown The same as a Total Shutdown except that all generation has ceased in
a separate part of the Total System and there is no electricity supply from
External Interconnections or other parts of the Total System to that
part of the Total System and, therefore, that part of the Total System is
shutdown, with the result that it is not possible for that part of the Total
System to begin to function again without The Company’s directions
relating to System Restoration.
Phase Jump Angle The difference in the measured phase angle of the voltage at the Grid
Entry Point or User System Entry Point in a given mains half cycle
compared with the measured phase angle of the voltage at the Grid Entry
Point or User System Entry Point in the previous mains half cycle.
Phase Jump Angle Limit The maximum Phase Jump Angle when applied to a GBGF-I which will
result in a linear controlled response without activating current limiting
functions. This is specified for a System angle near to zero which will be
considered to be the normal operating angle under steady state
conditions.
Phase Jump Angle The maximum Phase Jump Angle change when applied to a GBGF-I
Withstand which will result in the GBGF-I remaining in stable operation with current
limiting functions activated. This is specified for a System angle near to
zero which will be considered to be the normal operating angle under
steady state conditions.
Phase (Voltage) Unbalance The ratio (in percent) between the rms values of the negative sequence
component and the positive sequence component of the voltage.
Physical Notification Data that describes the BM Participant’s best estimate of the expected
input or output of Active Power of a BM Unit and/or (where relevant)
Generating Unit, except in the instance of a Stage 2 or higher Network
Gas Supply Emergency, with the accuracy of the Physical Notification
being commensurate with Good Industry Practice.
Planning Code or PC That portion of the Grid Code which is identified as the Planning Code.
Planned Outage An outage of a Large Power Station or of part of the National Electricity
Transmission System, or of part of a User System, co-ordinated by The
Company under OC2.
Plant Fixed and movable items used in the generation and/or supply and/or
transmission of electricity, other than Apparatus.
Point of Isolation The point on Apparatus (as defined in OC8A.1.6.2 and OC8B.1.7.2) at
which Isolation is achieved.
Power Available A signal prepared in accordance with good industry practice, representing
the instantaneous sum of the potential Active Power available from each
individual Power Park Unit within the Power Park Module calculated
using any applicable combination of electrical or mechanical or
meteorological data (including wind speed) measured at each Power
Park Unit at a specified time. Power Available shall be a value between
0MW and Registered Capacity or Maximum Capacity which is the sum
of the potential Active Power available of each Power Park Unit within
the Power Park Module. A unit that is not generating or supplying power
will be considered as not available. For the avoidance of doubt, the
Power Available signal would be the Active Power output that a Power
Park Module could reasonably be expected to export at the Grid Entry
Point or User System Entry Point taking all the above criteria into
account including Power Park Unit constraints such as optimisation
modes but would exclude a reduction in the Active Power export of the
Power Park Module instructed by The Company (for example) for the
purposes selecting a Power Park Module to operate in Frequency
Sensitive Mode or when an Emergency Instruction has been issued.
Power Park Module The matrix described in Appendix 1 to BC1 under the heading Power
Availability Matrix Park Module Availability Matrix.
Power Station An installation comprising one or more Generating Units or Power Park
Modules or Power Generating Modules or Electricity Storage
Modules (even where sited separately) owned and/or controlled by the
same Generator, which may reasonably be considered as being
managed as one Power Station.
Power System Stabiliser or Equipment controlling the Exciter output via the voltage regulator in such
PSS a way that power oscillations of the synchronous machines are
dampened. Input variables may be speed, frequency or power (or a
combination of these).
Preface The preface to the Grid Code (which does not form part of the Grid Code
and therefore is not binding).
Preliminary Notice A notice in writing, sent by The Company both to all Users identified by
it under OC12.4.2.1 and to the Test Proposer, notifying them of a
proposed System Test.
Preliminary Project Data relating to a proposed User Development at the time the User
Planning Data applies for a CUSC Contract but before an offer is made and accepted.
Primary Response The automatic increase in Active Power output of a Genset or, as the
case may be, the decrease in Active Power Demand in response to a
System Frequency fall. This increase in Active Power output or, as the
case may be, the decrease in Active Power Demand must be in
accordance with the provisions of the relevant Ancillary Services
Agreement which will provide that it will be released increasingly with
time over the period 0 to 10 seconds from the time of the start of the
Frequency fall on the basis set out in the Ancillary Services Agreement
and fully available by the latter, and sustainable for at least a further 20
seconds. The interpretation of the Primary Response to a – 0.5 Hz
frequency change is shown diagrammatically in Figure CC.A.3.2 and
Figure ECC.A.3.2
Private Network A network which connects to a Network Operator’s System and that
network belongs to a User who is not classified as a Generator, Network
Operator or Non-Embedded Customer.
Programming Phase The period between the Operational Planning Phase and the Control
Phase. It starts at the 8 weeks ahead stage and finishes at 17:00 on the
day ahead of real time.
Proposal Notice A notice submitted to The Company by a User which would like to
undertake a System Test.
Proposed Implementation The proposed date(s) for the implementation of a Grid Code
Date Modification Proposal or Workgroup Alternative Grid Code
Modification such date(s) to be either (i) described by reference to a
specified period after a direction from the Authority approving the Grid
Code Modification Proposal or Workgroup Alternative Grid Code
Modification or (ii) a Fixed Proposed Implementation Date.
Protection Apparatus A group of one or more Protection relays and/or logic elements
designated to perform a specified Protection function.
Pumped Storage A hydro unit in which water can be raised by means of pumps and stored
to be used for the generation of electrical energy;
Pumped Storage Generator A Generator which owns and/or operates any Pumped Storage Plant.
Pumped Storage Plant A Power Station comprising Pumped Storage Generating Units.
Pumped Storage Unit A Generating Unit within a Pumped Storage Plant. For the avoidance
of doubt, a Pumped Storage Unit is not considered to form part of an
Electricity Storage Unit unless specifically declared by the Generator.
Purchase Contracts A final and binding contract for the purchase of the Main Plant and
Apparatus.
Q/Pmax The ratio of Reactive Power to the Maximum Capacity. The
relationship between Power Factor and Q/Pmax is given by the
formula:-
𝑸
Power Factor = Cos [arctan[ ]]
𝑷𝒎𝒂𝒙
For example, a Power Park Module with a Q/P value of +0.33 would
equate to a Power Factor of Cos(arctan0.33) = 0.95 Power Factor lag.
Range CCGT Module A CCGT Module where there is a physical connection by way of a steam
or hot gas main between that CCGT Module and another CCGT Module
or other CCGT Modules, which connection contributes (if open) to
efficient modular operation, and which physical connection can be varied
by the operator.
Rated Field Voltage Shall have the meaning ascribed to that term in IEC 34-16-1:1991
[equivalent to British Standard BS4999 Section 116.1: 1992].
Reactive Energy The integral with respect to time of the Reactive Power.
Reactive Power The product of voltage and current and the sine of the phase angle
between them measured in units of voltamperes reactive and standard
multiples thereof, ie:
1000 VAr = 1 kVAr
1000 kVAr = 1 MVAr
Regenerative Braking A method of braking in which energy is extracted from the parts braked,
which may be returned directly to the System and the purpose of the
braking is motion control.
Regulations The Utilities Contracts Regulations 1996, as amended from time to time.
Parts of the Grid Code that are referenced in Governance Rules Annex
Regulated Sections
GR.B as amended from time to time with the approval of the Authority.
Reheater Time Constant Determined at Registered Capacity, the reheater time constant will be
construed in accordance with the principles of the IEEE Committee
Report "Dynamic Models for Steam and Hydro Turbines in Power System
Studies" published in 1973 which apply to such phrase.
Rejected Grid Code A Grid Code Modification Proposal in respect of which the Authority
Modification Proposal has decided not to direct The Company to modify the Grid Code
pursuant to The Company’s Transmission Licence in the manner set
out herein or, in the case of a Grid Code Self Governance Proposals,
in respect of which the Grid Code Review Panel has voted not to
approve.
Related Person Means, in relation to an individual, any member of their immediate family,
their employer (and any former employer of theirs within the previous 12
months), any partner with whom they are in partnership, and any
company or Affiliate of a company in which they or any member of their
immediate family controls more than 20% of the voting rights in respect
of the shares of the company;
Relevant E&W As the context requires NGET and/or an E&W Offshore Transmission
Transmission Licensee Licensee.
Relevant Transmission Means National Grid Electricity Transmission plc (NGET) in its
Licensee Transmission Area or SP Transmission plc (SPT) in its Transmission
Area or Scottish Hydro-Electric Transmission Ltd (SHETL) in its
Transmission Area or any Offshore Transmission Licensee in its
Transmission Area.
Remote Transmission Any Plant and Apparatus or meters owned by NGET which:
Assets
(a) are Embedded in a User System and which are not directly
connected by Plant and/or Apparatus owned by NGET to a sub-
station owned by NGET; and
(b) are by agreement between NGET and such User operated under
the direction and control of such User.
Replacement Reserves (RR) Means, in the context of Balancing Services, the Active Power reserves
available to restore or support the required level of FRR to be prepared
for additional system imbalances, including generation reserves;
Responsible Manager A manager who has been duly authorised by a User or a Relevant
Transmission Licensee to sign Site Responsibility Schedules on
behalf of that User or Relevant Transmission Licensee as the case may
be.
Restoration Service A User or a party with a legal or contractual obligation to provide a service
Provider contributing to one or several measures of the System Restoration Plan.
Restoration Service Test A test carried out on a Plant to confirm it has an Anchor Plant Capablity
or Top Up Restoration Capability.
Re-synchronisation The bringing of parts of the System which have become Out of
Synchronism with any other System back into Synchronism, and like
terms shall be construed accordingly.
Retained EU Law 31 December 2020 as defined in European Union (Withdrawal) Act 2018
as amended by the European Union (Withdrawal Agreement) Act 2020.
Restricted Applies to a TERRE Bid which has been marked so that it will be passed
to the TERRE Central Platform but will not be used in the auction.
Safety From The System That condition which safeguards persons when work is to be carried out
on or near a System from the dangers which are inherent in the System.
Safety Key A key unique at the Location capable of operating a lock which will cause
an Isolating Device and/or Earthing Device to be Locked.
Safety Rules The rules of the Relevant Transmission Licensee or a User that seek
to ensure that persons working on Plant and/or Apparatus to which the
rules apply are safeguarded from hazards arising from the System.
Scottish User A User in Scotland or any Offshore User who owns or operates Plant
and/or Apparatus connected (or which will at the OTSUA Transfer Time
be connected) to a Scottish Offshore Transmission System.
Secondary BM Unit Has the same meaning set out in the BSC.
Secured Event Has the meaning set out in the Security and Quality of Supply
Standard.
Security and Quality of The version of the document entitled ‘Security and Quality of Supply
Supply Standard (SQSS) Standard’ established pursuant to the Transmission Licence in force at
the time of entering into the relevant Bilateral Agreement.
Self-Governance A Grid Code Modification Proposal that does not fall within the scope
Modifications of a Significant Code Review and that meets the Self-Governance
Criteria or which the Authority directs is to be treated as such any
direction under GR.24.4.
Self-Governance Statement The statement made by the Grid Code Review Panel and submitted to
the Authority:
(a) confirming that, in its opinion, the Self-Governance Criteria are met
and the proposed Grid Code Modification Proposal is suitable for the
Self-Governance route; and
(b) providing a detailed explanation of the Grid Code Review Panel’s
reasons for that opinion.
Settlement Period A period of 30 minutes ending on the hour and half-hour in each hour
during a day.
Seven Year Statement A statement, prepared by The Company in accordance with the terms of
The Company’s Transmission Licence, showing for each of the seven
succeeding Financial Years, the opportunities available for connecting
to and using the National Electricity Transmission System and
indicating those parts of the National Electricity Transmission System
most suited to new connections and transport of further quantities of
electricity.
SF6 Gas Zone A segregated zone surrounding electrical conductors within a casing
containing SF6 gas.
In the case of Auxiliaries, the state where they are de-energised and not
capable of fulfilling their function until restarted or resupplied.
Significant Code Review Means the period commencing on the start date of a Significant Code
Review as stated in the notice issued by the Authority, and ending in the
circumstances described in GR.16.6 or GR.16.7, as appropriate.
Significant Code Review Means the period commencing on the start date of a Significant Code
Phase Review as stated in the notice issued by the Authority, and ending in the
circumstances described in GR.16.6 or GR.16.7, as appropriate.
Significant Event An Event, as defined in OC3.4.1.
Single Intraday Coupling The continuous process where collected orders are matched and cross-
zonal capacity is allocated simultaneously for different bidding zones in
the intraday market.
Single Line Diagram A schematic representation of a three-phase network in which the three
phases are represented by single lines. The diagram shall include (but
not necessarily be limited to) busbars, overhead lines, underground
cables, power transformers and reactive compensation equipment. It
shall also show where Large Power Stations are connected, and the
points at which Demand is supplied.
Single Point of Connection A single Point of Connection, with no interconnection through the
User’s System to another Point of Connection.
Site Common Drawings Drawings prepared for each Connection Site (and in the case of
OTSDUW, Transmission Interface Site) which incorporate Connection
Site (and in the case of OTSDUW, Transmission Interface Site) layout
drawings, electrical layout drawings, common protection/ control
drawings and common services drawings.
Site Responsibility A schedule containing the information and prepared on the basis of the
Schedule provisions set out in Appendix 1 of the CC and Appendix E1 of the ECC.
Slope The ratio of the steady state change in voltage, as a percentage of the
nominal voltage, to the steady state change in Reactive Power output, in
per unit of Reactive Power capability. For the avoidance of doubt, the
value indicates the percentage voltage reduction that will result in a 1 per
unit increase in Reactive Power generation.
Speeder Motor Setting The minimum and maximum no-load speeds (expressed as a percentage
Range of rated speed) to which the turbine is capable of being controlled, by the
speeder motor or equivalent, when the Generating Unit terminals are on
open circuit.
Standard Product Means a harmonised balancing product defined by all EU TSOs for the
exchange of balance services.
Specific Product Means in the context of Balancing Services a product that is not a
standard product.
Start Time The time named as such in an instruction issued by The Company
pursuant to the BC.
In the case of a Generating Unit is the action of bringing a Generating
Start-Up
Unit from Shutdown to Synchronous Speed.
Steam Unit A Generating Unit whose prime mover converts the heat-energy in
steam to mechanical energy.
Storage User A Generator who owns or operates one or more Electricity Storage
Modules. For the avoidance of doubt:
(a) Retained EU Law (Commission Regulation (EU) 2016/631,
Commission Regulation (EU) 2016/1388 and Commission
Regulation (EU) 2016/1485) shall not apply to Storage
Users; and
(b) the European Connection Conditions (ECC’s) shall apply
to Storage Users on the basis set out in Paragraph
ECC1.1(d).
Synchronous Electricity A Synchronous Power Generating Module which can convert or re-
Storage Module convert electrical energy from another source of energy such that the
frequency of the generated voltage, the rotor speed and the frequency of
network voltage are in a constant ratio and thus in synchronism. For the
avoidance of doubt a Synchronous Electricity Storage Module could
comprise of one or more Synchronous Electricity Storage Units.
Synchronous Electricity A Synchronous Generating Unit which can supply or absorb electrical
Storage Unit energy such that the frequency of the generated voltage, the rotor speed
and the frequency of the equipment are in constant ratio and thus in
synchronism with the network.
Synchronising Generation The amount of MW (in whole MW) produced at the moment of
synchronising.
Synchronising Group A group of two or more Gensets) which require a minimum time interval
between their Synchronising or De-Synchronising times.
Synchronous Area An area covered by synchronously interconnected Transmission
Licensees, such as the Synchronous Areas of Continental Europe,
Great Britain, Ireland-Northern Ireland and Nordic and the power systems
of Lithuania, Latvia and Estonia, together referred to as ‘Baltic’ which are
part of a wider Synchronous Area;
Issue 6 Revision 21 GD 04 March 2024
73 of 84
Synchronous The operation of rotating synchronous Apparatus for the specific purpose
Compensation of either the generation or absorption of Reactive Power.
Synchronous Electricity A Synchronous Power Generating Module which can convert and
Storage Module reconvert electrical energy from another source of energy such that the
frequency of the generated voltage, the rotor speed and the frequency of
network voltage are in a constant ratio and thus in synchronism. For the
avoidance of doubt a Synchronous Electricity Storage Module could
comprise of one or more Synchronous Electricity Storage Units.
Synchronous Electricity A Synchronous Generating Unit which can supply and absorb electrical
Storage Unit energy such that the frequency of the generated voltage, the rotor speed
and the frequency of the equipment are in constant ratio and thus in
synchronism with the network.
Synchronous Flywheel An item of synchronously rotating Plant for the specific purpose of
contributing inertia to the System. One or more Synchronous Flywheels
would not be considered to form an Electricity Storage Module unless
it could be operated in a controllable manner for its AC input and output
power.
Synchronous Generating A diagram showing the Active Power (MW) and Reactive Power (MVAr)
Unit Performance Chart capability limits within which a Synchronous Generating Unit at its
stator terminals (which is part of a Synchronous Power Generating
Module) will be expected to operate under steady state conditions.
Synchronous Power- An indivisible set of installations which can convert or re-convert electrical
Generating Module energy from another source of energy such that the frequency of the
supplied voltage, the rotor speed and the frequency of network voltage
are in a constant ratio and thus in synchronism. For the avoidance of
doubt, a Synchronous Power Generating Module could comprise of
one or more Synchronous Generating Units or one or more
Synchronous Electricity Storage Units.
Synchronous Power The matrix described in Appendix 1 to BC1 under the heading
Generating Module Matrix Synchronous Power Generating Module Matrix.
Synchronous Power A matrix in the form set out in Appendix 5 of OC2 showing the combination
Generating Module of Synchronous Generating Units within a Synchronous Power
Planning Matrix Generating Module which would be running in relation to any given MW
output.
Synchronous Power Has the same meaning as a Synchronous Generating Unit and would
Generating Unit be considered to be part of a Power Generating Module.
System Ancillary Services Collectively Part 1 System Ancillary Services and Part 2 System
Ancillary Services.
System Constraint A limitation on the use of a System due to lack of transmission capacity
or other System conditions.
System Constrained That portion of Registered Capacity or Registered Import Capacity not
Capacity available due to a System Constraint.
System Constraint Group A part of the National Electricity Transmission System which, because
of System Constraints, is subject to limits of Active Power which can
flow into or out of (as the case may be) that part.
System Defence Plan A document prepared by The Company, as published on its Website,
outlining how the requirements of the “defence plan”, as provided for by
Retained EU Law (Commission Regulation (EU) 2017/2196), has been
implemented within the GB Synchronous Area.
System Fault Dependability A measure of the ability of Protection to initiate successful tripping of
Index or Dp circuit-breakers which are associated with a faulty item of Apparatus. It
is calculated using the formula:
Dp = 1 – F1/A
Where:
A = Total number of System faults
F1 = Number of System faults where there was a failure to trip a circuit-
breaker.
System Incidents Report A report submitted to the GCRP on a monthly basis, containing, but not
limited to, a list of Significant Events, as detailed in OC3.4.1.
System Negative Reserve That margin of Active Power sufficient to allow the largest loss of Load
Active Power Margin or at any time.
System NRAPM
System Operator - Has the meaning set out in The Company’s Transmission Licence
Transmission Owner Code
or STC
System Restoration The procedure necessary for a recovery from a Total Shutdown or
Partial Shutdown.
System Restoration Region Those regions of the Total System as defined in Appendix 1 of OC9.
System Tests Tests which involve simulating conditions, or the controlled application of
irregular, unusual or extreme conditions, on the Total System, or any part
of the Total System, but which do not include commissioning or
recommissioning tests or any other tests of a minor nature.
System to Demand Intertrip An intertrip scheme which disconnects Demand when a System fault has
Scheme arisen to prevent abnormal conditions occurring on the System.
Target Frequency That Frequency determined by The Company, in its reasonable opinion,
as the desired operating Frequency of the Total System or of a relevant
Power Island. This will normally be 50.00Hz plus or minus 0.05Hz,
except in exceptional circumstances as determined by The Company for
example which may be operating the System during disputes affecting
fuel supplies or following a Total Shutdown or Partial Shutdown where
Power Islands are established, and each Power Island has its own
unique Frequency.
TERRE Auction Period A period of time lasting one hour and starting and ending on the hour (e.g.
from 10:00 to 11:00). Hence there are 24 TERRE Auction Periods in a
day.
TERRE Data Validation and A document produced by the central TERRE project detailing the correct
Consistency Rules format of submissions for TERRE.
TERRE Gate Closure 60 minutes before the start of the TERRE Auction Period (note still
ongoing discussions if this may become 55 minutes).
Test Programme A programme submitted by the Test Panel to The Company, the Test
Proposer, and each User identified by The Company under OC12.4.2.1,
which states the switching sequence and proposed timings of the
switching sequence, a list of those staff involved in carrying out the
System Test (including those responsible for the site safety) and such
other matters as the Test Panel deems appropriate.
The Company Control The nominated person employed by The Company to direct the
Engineer operation of the National Electricity Transmission System or such
person as nominated by The Company.
Top Up Restoration Plant Plant owned and operated by a Top Up Restoration Contractor.
Top Up Restoration Plant A test conducted on a Top Up Restoration Plant to confirm it is capable
Test of meeting the requirements of a Top Up Restoration Contract.
Total Shutdown The situation existing when all generation has ceased and there is no
electricity supply from External Interconnections and, therefore, the
Total System has shutdown with the result that it is not possible for the
Total System to begin to function again without The Company’s
directions relating to System Restoration.
Total System The National Electricity Transmission System and all User Systems
in the National Electricity Transmission System Operator Area.
Transfer Date Such date as may be appointed by the Secretary of State by order under
section 65 of the Act.
Transmission Means, when used in conjunction with another term relating to equipment
or a site, whether defined or not, that the associated term is to be read as
being part of or directly associated with the National Electricity
Transmission System, and not of or with the User System.
Transmission Area Has the meaning set out in the Transmission Licence of a
Transmission Licensee.
Transmission Connected A Demand Facility which has a Grid Supply Point to the National
Demand Facilities Electricity Transmission System.
Transmission DC Converter Any Transmission Licensee Apparatus (or OTSUA that will become
Transmission Licensee Apparatus at the OTSUA Transfer Time) used
to convert alternating current electricity to direct current electricity, or vice
versa. A Transmission Network DC Converter (which could include an
HVDC System owned by an Offshore Transmission Licensee or
Generator in respect of OTSUA) is a standalone operative configuration
at a single site comprising one or more converter bridges, together with
one or more converter transformers, converter control equipment,
essential protective and switching devices and auxiliaries, if any, used for
conversion.
Transmission Interface Means the electrical point of connection between the Offshore
Point Transmission System and an Onshore Transmission System.
Transmission Interface Site The site at which the Transmission Interface Point is located.
Transmission Licensee The Company and any Onshore Transmission Licensee or Offshore
Transmission Licensee.
Transmission Site Means a site owned (or occupied pursuant to a lease, licence or other
agreement) by a Relevant Transmission Licensee in which there is a
Connection Point. For the avoidance of doubt, a site owned by a User
but occupied by the Relevant Transmission Licensee as aforesaid, is a
Transmission Site.
Turbine Time Constant Determined at Registered Capacity, the turbine time constant will be
construed in accordance with the principles of the IEEE Committee
Report "Dynamic Models for Steam and Hydro Turbines in Power System
Studies" published in 1973 which apply to such phrase.
Type A Power Generating A Power-Generating Module (including an Electricity Storage
Module Module) with a Grid Entry Point or User System Entry Point below
110 kV and a Maximum Capacity of 0.8 kW or greater but less than
1MW;
Type B Power Generating A Power-Generating Module (including an Electricity Storage Module)
Module with a Grid Entry Point or User System Entry Point below 110 kV and
a Maximum Capacity of 1MW or greater but less than 10MW;
Type C Power Generating A Power-Generating Module (including an Electricity Storage Module)
Module with a Grid Entry Point or User System Entry Point below 110 kV and
a Maximum Capacity of 10MW or greater but less than 50MW;
Type D Power Generating A Power-generating Module: (including an Electricity Storage
Module Module):
with a Grid Entry Point or User System Entry Point at, or greater
than, 110 kV; or
with a Grid Entry Point or User System Entry Point below 110 kV and
with Maximum Capacity of 50MW or greater
Unbalanced Load The situation where the Load on each phase is not equal.
Under-excitation Limiter Shall have the meaning ascribed to that term in IEC 34-16-1:1991
[equivalent to British Standard BS4999 Section 116.1: 1992].
Under Frequency Relay An electrical measuring relay intended to operate when its characteristic
quantity (Frequency) reaches the relay settings by a decrease in
Frequency.
Unit Load Controller The time constant, expressed in units of seconds, of the power output
Response Time Constant increase which occurs in the Secondary Response timescale in
response to a step change in System Frequency.
Unresolved Issues Any relevant Grid Code provisions or Bilateral Agreement requirements
identified by The Company with which the relevant User has not
demonstrated compliance to The Company’s reasonable satisfaction at
the date of issue of the Preliminary Operational Notification and/or
Interim Operational Notification and/or Limited Operational
Notification and which are detailed in such Preliminary Operational
Notification and/or Interim Operational Notification and/or Limited
Operational Notification.
User Data File Structure The file structure given at DRC 18 which will be specified by The
Company which a Generator or DC Converter Station owner or HVDC
System Owner must use for the purposes of the CP or the ECP to submit
DRC data Schedules and information demonstrating compliance with the
Grid Code and, where applicable, with the CUSC Contract(s), unless
otherwise agreed by The Company.
User Development In the PC means either User's Plant and/or Apparatus to be connected
to the National Electricity Transmission System, or a Modification
relating to a User's Plant and/or Apparatus already connected to the
National Electricity Transmission System, or a proposed new
connection or Modification to the connection within the User System.
User Self Certification of A certificate, in the form attached at CP.A.2.(1) or ECP.A.2.(1) completed
Compliance by a Generator or DC Converter Station owner or HVDC System
Owner to which the Compliance Statement is attached which confirms
that such Plant and Apparatus complies with the relevant Grid Code
provisions and where appropriate, with the CUSC Contract(s), as
identified in the Compliance Statement and, if appropriate, identifies any
Unresolved Issues and/or any exceptions to such compliance and
details the derogation(s) granted in respect of such exceptions.
User Site A site owned (or occupied pursuant to a lease, licence or other
agreement) by a User in which there is a Connection Point. For the
avoidance of doubt, a site owned by a Relevant Transmission Licensee
but occupied by a User as aforesaid, is a User Site.
In the event of a voltage magnitude and phase change at the Grid Entry
Point or User System Entry Point, a Grid Forming Plant will
instantaneously (within 5ms) supply Voltage Jump Reactive Power to
the Total System as a result of the voltage magnitude change.
Water Time Constant Bears the meaning ascribed to the term "Water inertia time" in IEC308.
Website The site established by The Company on the World-Wide Web for the
exchange of information among Users and other interested persons in
accordance with such restrictions on access as may be determined from
time to time by The Company.
Weekly ACS Conditions Means that particular combination of weather elements that gives rise to
a level of peak Demand within a week, taken to commence on a Monday
and end on a Sunday, which has a particular chance of being exceeded
as a result of weather variation alone. This particular chance is
determined such that the combined probabilities of Demand in all weeks
of the year exceeding the annual peak Demand under Annual ACS
Conditions is 50%, and in the week of maximum risk the weekly peak
Demand under Weekly ACS Conditions is equal to the annual peak
Demand under Annual ACS Conditions.
A number of the terms listed above are defined in other documents, such as the Balancing and Settlement
Code and the Transmission Licence. Appendix 1 sets out the current definitions from the other documents
of those terms so used in the Grid Code and defined in other documents for ease of reference, but does not
form part of the Grid Code.
GD.2 Construction of References
GD.2.1 In the Grid Code:
(i) a table of contents, a Preface, a Revision section, headings, and the Appendix to this
Glossary and Definitions are inserted for convenience only and shall be ignored in
construing the Grid Code;
(ii) unless the context otherwise requires, all references to a particular paragraph, sub-
paragraph, Appendix or Schedule shall be a reference to that paragraph, sub-paragraph
Appendix or Schedule in or to that part of the Grid Code in which the reference is made;
(iii) unless the context otherwise requires, the singular shall include the plural and vice versa,
references to any gender shall include all other genders and references to persons shall
include any individual, body corporate, corporation, joint venture, trust, unincorporated
association, organisation, firm or partnership and any other entity, in each case whether
or not having a separate legal personality;
(iv) references to the words "include" or "including" are to be construed without limitation to
the generality of the preceding words;
(v) unless there is something in the subject matter or the context which is inconsistent
therewith, any reference to an Act of Parliament or any Section of or Schedule to, or other
provision of an Act of Parliament shall be construed at the particular time, as including a
reference to any modification, extension or re-enactment thereof then in force and to all
instruments, orders and regulations then in force and made under or deriving validity from
the relevant Act of Parliament;
(vi) where the Glossary and Definitions refers to any word or term which is more particularly
defined in a part of the Grid Code, the definition in that part of the Grid Code will prevail
(unless otherwise stated) over the definition in the Glossary & Definitions in the event
of any inconsistency;
(vii) a cross-reference to another document or part of the Grid Code shall not of itself impose
any additional or further or co-existent obligation or confer any additional or further or co-
existent right in the part of the text where such cross-reference is contained;
(viii) nothing in the Grid Code is intended to or shall derogate from The Company's statutory
or licence obligations;
(ix) a "holding company" means, in relation to any person, a holding company of such person
within the meaning of section 736, 736A and 736B of the Companies Act 1985 as
substituted by section 144 of the Companies Act 1989 and, if that latter section is not in
force at the Transfer Date, as if such latter section were in force at such date;
Issue 6 Revision 21 GD 04 March 2024
83 of 84
(x) a "subsidiary" means, in relation to any person, a subsidiary of such person within the
meaning of section 736, 736A and 736B of the Companies Act 1985 as substituted by
section 144 of the Companies Act 1989 and, if that latter section is not in force at the
Transfer Date, as if such latter section were in force at such date;
(xi) references to time are to London time; and
(xii) (a) Save where (b) below applies, where there is a reference to an item of data being
expressed in a whole number of MW, fractions of a MW below 0.5 shall be rounded
down to the nearest whole MW and fractions of a MW of 0.5 and above shall be
rounded up to the nearest whole MW;
(b) In the case of the definition of Registered Capacity or Maximum Capacity, fractions
of a MW below 0.05 shall be rounded down to one decimal place and fractions of a
MW of 0.05 and above shall be rounded up to one decimal place.
(xiii) For the purposes of the Grid Code, physical quantities such as current or voltage are not
defined terms as their meaning will vary depending upon the context of the obligation.
For example, voltage could mean positive phase sequence root mean square voltage,
instantaneous voltage, phase to phase voltage, phase to earth voltage. The same issue
equally applies to current, and therefore the terms current and voltage should remain
undefined with the meaning depending upon the context of the application. Retained EU
Law (Commission Regulation (EU) 2016/631) defines requirements of current and
voltage but they have not been adopted as part of EU implementation for the reasons
outlined above.
(xiv) Except where expressly stated to the contrary, reference to Commission Regulations
means the Commission Regulation (EU) as it forms part of Retained EU Law, as such
regulation may be amended.
CONTENTS
(This contents page does not form part of the Grid Code)
To reflect different types of data, Preliminary Project Planning Data and Committed Project
Planning Data are themselves divided into:
(a) those items of Standard Planning Data and Detailed Planning Data which will always
be forecast, known as Forecast Data; and
(b) those items of Standard Planning Data and Detailed Planning Data which relate to
Plant and/or Apparatus which upon connection will become Registered Data, but which
prior to connection, for the seven succeeding Financial Years, will be an estimate of what
is expected, known as Estimated Registered Data.
Connected Planning Data
PC.5.5 The PC requires that, at the time that a Statement of Readiness is submitted under the
Bilateral Agreement and/or Construction Agreement, any estimated values assumed for
planning purposes are confirmed or, where practical, replaced by validated actual values and
by updated estimates for the future and by updated forecasts for forecast data items such as
Demand. In the case of an Embedded Development the relevant Network Operator will
update any estimated values assumed for planning purposes with validated actual values as
soon as reasonably practicable after energisation. This data is then termed Connected
Planning Data.
To reflect the three types of data referred to above, Connected Planning Data is itself divided
into:
PC.5.7 Committed Project Planning Data and Connected Planning Data will each contain both
Standard Planning Data and Detailed Planning Data.
PC.6 PLANNING STANDARDS
PC.6.1 The Company shall apply the Licence Standards relevant to it in the planning and
development of the National Electricity Transmission System. The Company shall procure
that each Relevant Transmission Licensee shall apply the Licence Standards relevant to
planning and development, in the planning and development of the Transmission System of
each Relevant Transmission Licensee and that a User shall apply the Licence Standards
relevant to planning and development, in the planning and development of the OTSUA.
PC.6.2 In relation to Scotland, Appendix C lists the technical and design criteria applied in the planning
and development of each Relevant Transmission Licensee's Transmission System. The
criteria are subject to review in accordance with each Relevant Transmission Licensee’s
Transmission Licence conditions. Copies of these documents are available from The
Company on request. The Company will charge an amount sufficient to recover its
reasonable costs incurred in providing this service.
PC.7.9 A User may at any time, in writing, request further specified National Electricity
Transmission System network data in order to provide The Company with viable User
network data (as required under this PC). Upon receipt of such request, The Company shall
consider, and where appropriate provide such National Electricity Transmission System
network data to the User as soon as reasonably practicable following the request.
PC.A.1 INTRODUCTION
PC.A.1.1 The Appendix specifies data requirements to be submitted to The Company by Users, and
in certain circumstances to Users by The Company.
PC.A.1.2 Submissions by Users
(a) Planning data submissions by Users shall be:
(i) with respect to each of the seven succeeding Financial Years (other than in the
case of Registered Data which will reflect the current position and data relating to
Demand forecasts which relates also to the current year);
(ii) provided by Users in connection with a CUSC Contract (PC.4.1, PC.4.4 and PC.4.5
refer);
(iii) provided by Users on a routine annual basis in calendar week 24 of each year to
maintain an up-to-date data bank (although Network Operators may delay the
submission of data (other than that to be submitted pursuant to PC.3.2(c) and
PC.3.2(d)) until calendar week 28). In addition the structural data in DRC Schedule
5 Tables 5(a), 5(b), 5(d), 5(e) , 5(f) and DRC Schedule 13 (Lumped system
susceptance (PC.A.2.3) only) provided by Network Operators by calendar week 28
shall be updated by calendar week 50 of each year (again which may be delayed as
above until week 2 of the following calendar year). Where from the date of one
annual (or in the case of Schedule 5 or Schedule 13 the calendar week 50)
submission to another there is no change in the data (or in some of the data) to be
submitted, instead of re-submitting the data, a User may submit a written statement
that there has been no change from the data (or some of the data) submitted the
previous time; and
(iv) provided by Network Operators in connection with Embedded Development
(PC.4.4 refers).
(b) Where there is any change (or anticipated change) in Committed Project Planning Data
or a significant change in Connected Planning Data in the category of Forecast Data
or any change (or anticipated change) in Connected Planning Data in the categories of
Registered Data or Estimated Registered Data supplied to The Company under the
PC, notwithstanding that the change may subsequently be notified to The Company
under the PC as part of the routine annual update of data (or that the change may be a
Modification under the CUSC), the User shall, subject to PC.A.3.2.3 and PC.A.3.2.4,
notify The Company in writing without delay.
(c) The notification of the change will be in the form required under this PC in relation to the
supply of that data and will also contain the following information:
(i) the time and date at which the change became, or is expected to become, effective;
(ii) if the change is only temporary, an estimate of the time and date at which the data
will revert to the previous registered form.
(d) The routine annual update of data, referred to in (a)(iii) above, need not be submitted in
respect of Small Power Stations or Embedded installations of direct current converters
which do not form a DC Converter Station or HVDC System (except as provided in
PC.3.2.(c)), or unless specifically requested by The Company, or unless otherwise
specifically provided.
PC.A.1.3 Submissions by The Company
Network Data release by The Company shall be:
(a) with respect to the current Financial Year;
PC.A.2.2.5 For each transformer shown on the Single Line Diagram provided under PC.A.2.2.1, each
User (including those undertaking OTSDUW) shall provide the following details:
Rated MVA
Voltage Ratio
Winding arrangement
Positive sequence reactance (max, min and nominal tap)
Positive sequence resistance (max, min and nominal tap)
Zero sequence reactance
PC.A.2.2.5.1. In addition, for all interconnecting transformers between the User's Supergrid Voltage
System and the User's Subtransmission System throughout Great Britain and, in Scotland
and Offshore, also for all interconnecting transformers operating at 132kV or greater between
the User’s System and the User’s Subtransmission System (and any OTSUA) the User
shall supply the following information:-
Tap changer range
Tap change step size
Tap changer type: on load or off circuit
Earthing method: Direct, resistance or reactance
Impedance (if not directly earthed )
PC.A.2.2.6 Each User shall supply the following information about the User’s equipment installed at a
Transmission Site (or in the case of OTSUA, all OTSDUW Plant and Apparatus):-
(a) Switchgear. For all circuit breakers:-
Rated voltage (kV)
Operating voltage (kV)
Rated 3-phase rms short-circuit breaking current, (kA)
Rated 1-phase rms short-circuit breaking current, (kA)
Rated 3-phase peak short-circuit making current, (kA)
Rated 1-phase peak short-circuit making current, (kA)
Rated rms continuous current (A)
DC time constant applied at testing of asymmetrical breaking abilities (secs)
In the case of OTSDUW Plant and Apparatus operating times for circuit breaker,
Protection, trip relay and total operating time should be provided.
(b) Substation Infrastructure. For the substation infrastructure (including, but not limited to,
switch disconnectors, disconnectors, current transformers, line traps, busbars, through
bushings, etc):-
Rated 3-phase rms short-circuit withstand current (kA)
Rated 1-phase rms short-circuit withstand current (kA).
Rated 3-phase short-circuit peak withstand current (kA)
In addition, if an equivalent Single Line Diagram has been provided the data items listed
under the following parts of PC.A.2.5.6(a) shall be provided:-
(xi), (xii), (xiii);
In addition, for a Power Park Module (including DC Connected Power Park Modules) in
which one or more of the Power Park Units utilise a protective control such as a crowbar
circuit:-
the data items listed under the following parts of PC.A.2.5.6(a) shall be provided:-
(xiv), (xv);
All of the above data items shall be provided in accordance with the detailed provisions of
PC.A.2.5.6(c), (d), (f).
Should actual data in respect of fault infeeds be unavailable at the time of the application for
a CUSC Contract or Embedded Development Agreement, a limited subset of the data,
representing the maximum fault infeed that may result from all of the plant types being
considered, shall be submitted. This data will, as a minimum, represent the root mean square
of the positive, negative and zero sequence components of the fault current for both single
phase and three phase solid faults at the Grid Entry Point (or User System Entry Point if
Embedded) at the time of fault application and 50ms following fault application. Actual data
in respect of fault infeeds shall be submitted to The Company as soon as it is available, in
line with PC.A.1.2
PC.A.2.5.6 Data Items
(a) The following is the list of data utilised in this part of the PC. It also contains rules on the
data which generally apply:-
(i) Root mean square of the symmetrical three-phase short circuit current infeed at the
instant of fault, (I1");
(ii) Root mean square of the symmetrical three-phase short circuit current after the
subtransient fault current contribution has substantially decayed, (I 1');
(iii) the zero sequence source resistance and reactance values of the User's System
as seen from the node on the Single Line Diagram provided under PC.A.2.2.1 (or
Power Generating Module or Station Transformer high voltage terminals or
Generating Unit terminals or DC Converter terminals or HVDC System terminals,
as appropriate) consistent with the infeed described in PC.A.2.5.1.(b);
(iv) root mean square of the pre-fault voltage at which the maximum fault currents were
calculated;
(v) the positive sequence X/R ratio at the instant of fault;
(vi) the negative sequence resistance and reactance values of the User's System seen
from the node on the Single Line Diagram provided under PC.A.2.2.1 (or Power
Generating Module or Station Transformer high voltage terminals, or Generating
Unit terminals or DC Converter terminals or HVDC System terminals as
appropriate) if substantially different from the values of positive sequence resistance
and reactance which would be derived from the data provided above;
Issue 6 Revision 21 PC 04 March 2024
27 of 93
(vii) A continuous trace and a table showing the root mean square of the positive,
negative and zero sequence components of the short circuit current between zero
and 140ms at 10ms intervals;
(viii) The Active Power (or Interface Point Capacity being exported pre-fault by the
OTSDUW Plant and Apparatus) being generated pre-fault by the Power Park
Module (including DC Connected Power Park Modules) and by each type of
Power Park Unit;
(ix) The reactive compensation shown explicitly on the Single Line Diagram that is
switched in;
(x) The Power Factor of the Power Park Module (including DC Connected Power
Park Modules) and of each Power Park Unit type;
(xi) The positive sequence X/R ratio of the equivalent at the Common Collection
Busbar or Interface Point in the case of OTSUA;
(xii) The minimum zero sequence impedance of the equivalent seen from the Common
Collection Busbar or Interface Point in the case of OTSUA;
(xiii) The number of Power Park Units represented in the equivalent Power Park Unit;
(xiv) The additional rotor resistance and reactance (if any) that is applied to the Power
Park Unit under a fault condition;
(xv) A continuous trace and a table showing the root mean square of the positive,
negative and zero sequence components of the retained voltage at the fault point
and Power Park Unit terminals, or the Common Collection Busbar if an equivalent
Single Line Diagram and associated data as described in PC.A.2.2.2 is provided or
Interface Point in the case of OTSUA, representing the limiting case, which may
involve the application of a non-solid fault, required to not cause operation of the
protective control;
(b) In considering this data, unless the User notifies The Company accordingly at the time
of data submission, The Company will assume that the time constant of decay of the
subtransient fault current corresponding to the change from I 1" to I1', (T") is not
significantly different from 40ms. If that assumption is not correct in relation to an item of
data, the User must inform The Company at the time of submission of the data.
(c) The value for the X/R ratio must reflect the rate of decay of the d.c. component that may
be present in the fault current and hence that of the sources of the initial fault current. All
shunt elements and loads must therefore be deleted from any system model before the
X/R ratio is calculated.
(d) In producing the data, the User may use "time step analysis" or "fixed-point-in-time
analysis" with different impedances.
(e) If a fixed-point-in-time analysis with different impedances method is used, then in relation
to the data submitted under (a) (i) above, the data will be required for "time zero" to give
I1". The figure of 120ms is consistent with a decay time constant T" of 40ms, and if that
figure is different, then the figure of 120ms must be changed accordingly.
(f) Where a "time step analysis" is carried out, the X/R ratio may be calculated directly from
the rate of decay of the d.c. component. The X/R ratio is not that given by the phase angle
of the fault current if this is based on a system calculation with shunt loads, but from the
Thévenin equivalent of the system impedance at the instant of fault with all non-source
shunts removed.
PC.A.3.2.3 Notwithstanding any other provision of this PC, the CCGT Units within a CCGT Module,
details of which are required under paragraph (g) of PC.A.3.2.2, can only be amended in
accordance with the following provisions:-
(a) if the CCGT Module is a Normal CCGT Module, the CCGT Units within that CCGT
Module can only be amended such that the CCGT Module comprises different CCGT
Units if The Company gives its prior consent in writing. Notice of the wish to amend the
CCGT Units within such a CCGT Module must be given at least 6 months before it is
wished for the amendment to take effect;
(b) if the CCGT Module is a Range CCGT Module, the CCGT Units within that CCGT
Module and the Grid Entry Point at which the power is provided can only be amended
as described in BC1.A1.6.4.
PC.A.3.2.4 Notwithstanding any other provision of this PC, the Power Park Units within a Power Park
Module (including DC Connected Power Park Modules), and the Power Park Modules
(including DC Connected Power Park Modules) within a BM Unit, details of which are
required under paragraph (k) of PC.A.3.2.2, can only be amended in accordance with the
following provisions:-
(a) if the Power Park Units within that Power Park Module can only be amended such that
the Power Park Module comprises different Power Park Units due to
repair/replacement of individual Power Park Units if The Company gives its prior
consent in writing. Notice of the wish to amend a Power Park Unit within such a Power
Park Module (including DC Connected Power Park Modules) must be given at least 4
weeks before it is wished for the amendment to take effect;
(b) if the Power Park Units within that Power Park Module (including DC Connected
Power Park Modules) and/or the Power Park Modules (including DC Connected
Power Park Modules) within that BM Unit can be selected to run in different Power Park
Modules and/or BM Units as an alternative operational running arrangement the Power
Park Units within the Power Park Module, the BM Unit of which each Power Park
Module forms part, and the Grid Entry Point at which the power is provided can only be
amended as described in BC1.A.1.8.4.
PC.A.3.2.5 Notwithstanding any other provision of this PC, the Synchronous Generating Units within a
Synchronous Power Generating Module, and the Synchronous Power Generating
Modules within a BM Unit, details of which are required under paragraph (l) of PC.A.3.2.2,
can only be amended in accordance with the following provisions:-
(a) if the Synchronous Generating Units within that Synchronous Power Generating
Module can only be amended such that the Synchronous Power Generating Module
comprises different Synchronous Generating Units due to repair/replacement of
individual Synchronous Generating Units if The Company gives its prior consent in
writing. Notice of the wish to amend a Synchronous Generating Unit within such a
Synchronous Power Generating Module must be given at least 4 weeks before it is
wished for the amendment to take effect;
(e) for each type of Power Park Unit in a Power Park Module not connected to the Total
System by a DC Converter or HVDC System:
Rated MVA
Rated MW
Rated terminal voltage
Inertia constant, (MWsec/MVA)
Additionally, for Power Park Units that are squirrel-cage or doubly-fed induction
Issue 6 Revision 21 PC 04 March 2024
36 of 93
generators driven by wind turbines:
Stator reactance.
Magnetising reactance.
Rotor resistance (at rated running)
Rotor reactance (at rated running)
The generator rotor speed range (minimum and maximum speeds in RPM) (for
doubly-fed induction generators only)
Converter MVA rating (for doubly-fed induction generators only)
For a Power Park Unit consisting of a synchronous machine in combination with a back-
to-back DC Converter or HVDC Converter, or for a Power Park Unit not driven by a
wind turbine, the data to be supplied shall be agreed with The Company in accordance
with PC.A.7.
This information should only be given in the data supplied in accordance with PC.4.4 and
PC.4.5.
PC.A.3.4 General Generating Unit, Power Park Module (including DC Connected Power Park
Modules), Power Generating Module, HVDC System and DC Converter Data
PC.A.3.4.1 The point of connection to the National Electricity Transmission System or the Total
System, if other than to the National Electricity Transmission System, in terms of
geographical and electrical location and system voltage is also required.
PC.A.3.4.2 (a) Type of Generating Unit (ie Synchronous Power Generating Unit within a Power
Generating Module, Synchronous Generating Unit, Non-Synchronous Generating
Unit, DC Converter, Power Park Module (including DC Connected Power Park
Modules) or HVDC System).
(b) In the case of a Synchronous Generating Unit (including Synchronous Generating
Units within a Synchronous Power Generating Module) details of the Exciter
category, for example whether it is a rotating Exciter or a static Exciter or in the case of
a Non-Synchronous Generating Unit the voltage control system.
(c) Whether a Power System Stabiliser is fitted.
PC.A.3.4.3 Each Generator shall supply The Company with the production type(s) used as the primary
source of power in respect of each Generating Unit (including Synchronous Generating
Units within a Synchronous Power Generating Module), selected from the list set out below:
- Biomass
- Fossil brown coal/lignite
- Fossil coal-derived gas
- Fossil gas
- Fossil hard coal
- Fossil oil
- Fossil oil shale
- Fossil peat
- Geothermal
- Hydro pumped storage
- Hydro run-of-river and poundage
- Hydro water reservoir
- Marine
- Nuclear
PC.A.3.4.4 In the case of an Electricity Storage Module or Electricity Storage Unit, each Generator
shall supply The Company with the production type(s) used as the primary Electricity
Storage source (including Synchronous Electricity Storage Units within a Synchronous
Electricity Storage Module), selected from the list set out below:
-Chemical
Ammonia
Hydrogen
Synthetic Fuels
Drop-in Fuels
Methanol
Synthetic Natural Gas
-Electrical
Supercapacitors
Superconducting Magnetic ES (SMES)
-Mechanical
Adiabatic Compressed Air
Diabatic Compressed Air
Liquid Air Energy Storage
Pumped Hydro
Flywheels
-Thermal
Latent Heat Storage
Thermochemical Storage
Sensible Heat Storage
-Electrochemical
Classic Batteries
Lead Acid
Lithium Polymer (Li-Polymer)
Metal Air
Nickle Cadmium (Ni-Cd)
Sodium Nickle Chloride (Na-NiCl2)
Lithium Ion (Li–ion)
Sodium Ion (Na–ion)
Lithium Sulphur (Li-S)
Sodium Sulphur(Na-S
Nickle –Metal Hydride (Ni-MH)
Flow Batteries
Vanadium Red-Oxide
Zinc – Iron (Zn –Fe)
Zinc – Bromine (Zn –Br)
Other
Embedded
PC.A.5.1.2 Each Generator, in respect of its existing, or proposed, Embedded Large Power Stations
and its Embedded Medium Power Stations subject to a Bilateral Agreement and each
Network Operator in respect of Embedded Medium Power Stations not subject to a
Bilateral Agreement within its System shall provide The Company with data relating to each
of those Large Power Stations and Medium Power Stations, both current and forecast, as
specified in PC.A.5.2, PC.A.5.3, PC.A.5.4 and PC.A.5.7 as applicable.
Each DC Converter Station owner or HVDC System Owner, or Network Operator in the
case of an Embedded DC Converter Station or Embedded HVDC System not subject to a
Bilateral Agreement within its System with existing or proposed HVDC Systems or DC
Converter Stations shall provide The Company with data relating to each of those HVDC
Systems or DC Converter Stations, both current and forecast, as specified in PC.A.5.2 and
PC.A.5.4.
However, no data need be supplied in relation to those Embedded Medium Power Stations
or Embedded DC Converter Stations or Embedded HVDC Systems if they are connected
at a voltage level below the voltage level of the Subtransmission System except in
connection with an application for, or under a, CUSC Contract or unless specifically requested
by The Company under PC.A.5.1.4.
GB Generators, DC Converter Station owners, EU Generators and HVDC System Owners
shall ensure that the models supplied in respect of their Plant and Apparatus provide a true
and accurate behaviour of the plant as built as required under PC.A.5.3.2(c), PC.A.5.4.2(a)
and PC.A.5.4.3 and verified through the Compliance Processes (CP) or European
Compliance Processes (ECP) as applicable
PC.A.5.1.3 Each Network Operator need not submit Planning Data in respect of Embedded Small
Power Stations unless required to do so under PC.A.1.2(b), PC.A.3.1.4 or unless specifically
requested under PC.A.5.1.4 below, in which case they will supply such data.
For the avoidance of doubt, Demand data associated with Generators undertaking OTSDUW
which utilise an OTSDUW DC Converter should supply data under PC.A.4.
PC.A.5.3 Synchronous Power Generating Modules, Synchronous Generating Unit and Associated
Control System Data
PC.A.5.3.1 The data submitted below are not intended to constrain any Ancillary Services Agreement
PC.A.5.3.2 The following Synchronous Generating Unit (including Synchronous Generating Units
within a Synchronous Power Generating Module) and Power Station data should be
supplied:
(a) Synchronous Generating Unit Parameters
Rated terminal volts (kV)
Maximum terminal voltage set point (kV)
Option 2
Excitation System Nominal Response
Rated Field Voltage
No-Load Field Voltage
Excitation System On-Load Positive Ceiling Voltage
Excitation System No-Load Positive Ceiling Voltage
Excitation System No-Load Negative Ceiling Voltage
Stator Current Limiter (applicable only to Synchronous Power Generating
Modules)
Details of Excitation System (including PSS if fitted) described in block diagram
form showing transfer functions of individual elements.
Details of Over-excitation Limiter described in block diagram form showing transfer
functions of individual elements.
Details of Under-excitation Limiter described in block diagram form showing
transfer functions of individual elements.
The block diagrams submitted after 1 January 2009 in respect of the Excitation
System (including the Over-excitation Limiter and the Under-excitation Limiter)
for Generating Units with a Completion date after 1 January 2009 or subject to a
Modification to the Excitation System after 1 January 2009, should have been
verified as far as reasonably practicable by simulation studies as representing the
expected behaviour of the system.
(d) Governor Parameters
Incremental Droop values (in %) are required for each Generating Unit at six MW
loading points (MLP1 to MLP6) as detailed in PC.A.5.5.1 (this data item needs only be
provided for Large Power Stations).
(ii) Governor Parameters (for Non-Reheat Steam Units and Gas Turbine Units)
Governor average gain
Speeder motor setting range
Time constant of steam or fuel governor valve
Governor valve opening limits
Governor valve rate limits
Issue 6 Revision 21 PC 04 March 2024
49 of 93
Time constant of turbine
Governor block diagram
The following data items need only be supplied for Large Power Stations:
(iii) Boiler & Steam Turbine Data
Boiler Time Constant (Stored Active Energy) s
HP turbine response ratio:
proportion of Primary Response arising from HP turbine %
HP turbine response ratio:
proportion of High Frequency Response arising from HP turbine %
[End of Option 1]
Option 2
(i) Governor and associated prime mover Parameters - All Generating Units (including
Synchronous Generating Units within a Synchronous Power Generating
Module)
Governor Block Diagram showing transfer function of individual elements
including acceleration sensitive elements.
Governor Time Constant (in seconds)
Speeder Motor Setting Range (%)
Average Gain (MW/Hz)
Governor Deadband need only be provided for Large Power Stations owned
and operated by GB Generators (and both Frequency Response Deadband
and Frequency Response Insensitivity should be supplied in respect of Type
C and D Power Generating Modules within Large Power Stations and
Medium Power Stations excluding Embedded Medium Power Stations not
subject to a Bilateral Agreement*) owned and oprated by EU Code
Generators.
- Maximum Setting Hz
- Normal Setting Hz
- Minimum Setting Hz
Where the Generating Unit governor does not have a selectable Governor
Deadband (or Frequency Response Deadband and Frequency Response
Insensitivity)* facility as specified above, then the actual value of the Governor
Deadband or (Frequency Response Deadband and Frequency Response
Insensitivity)* need only be provided.
The block diagrams submitted after 1 January 2009 in respect of the governor
system for Generating Units with a Completion date after 1 January 2009 or
subject to a Modification to the governor system after 1 January 2009, should
have been verified as far as reasonably practicable by simulation studies as
representing the expected behaviour of the system.
(iii) Governor and associated prime mover Parameters - Gas Turbine Units
Inlet Guide Vane Time Constant (in seconds)
Inlet Guide Vane Opening Limits (%)
Inlet Guide Vane Opening Rate Limits (%/second)
Inlet Guide Vane Closing Rate Limits (%/second)
Fuel Valve Constant (in seconds)
Fuel Valve Opening Limits (%)
Fuel Valve Opening Rate Limits (%/second)
Fuel Valve Closing Rate Limits (%/second)
Waste Heat Recovery Boiler Time Constant (in seconds)
(iv) Governor and associated prime mover Parameters - Hydro Generating Units
Guide Vane Actuator Time Constant (in seconds)
Guide Vane Opening Limits (%)
Guide Vane Opening Rate Limits (%/second)
Guide Vane Closing Rate Limits (%/second)
Water Time Constant (in seconds)
(v) Governor Parameters – Synchronous Electricity Storage Units
For Synchronous Electricity Storage Modules which are derived from
compressed air energy storage systems, the following data should be provided.
For other Synchronous Electricity Storage Modules, data should be supplied
as required by The Company in accordance with PC.A.7
Valve Actuator Time Constant (in seconds)
Data items marked with a hash (#) should be applicable to a Genset which has been
Shutdown for 48 hours.
PC.A.5.4 Power Park Module, Non-Synchronous Generating Unit and Associated Control System Data
PC.A.5.4.1 The data submitted below are not intended to constrain any Ancillary Services Agreement
PC.A.5.4.2 The following Power Park Unit, Power Park Module and Power Station data should be
supplied in the case of a Power Park Module not connected to the Total System by a DC
Converter or HVDC System (and in the case of PC.A.5.4.2(f) any OTSUA):
Where a Manufacturer’s Data & Performance Report exists in respect of the model of the
Power Park Unit, the User may subject to The Company’s agreement, opt to reference the
Manufacturer’s Data & Performance Report as an alternative to the provision of data in
accordance with PC.A.5.4.2 except for:
(1) the section marked thus # at sub paragraph (b); and
(2) all of the harmonic and flicker parameters required under sub paragraph (h); and
(3) all of the site specific model parameters relating to the voltage or frequency control
systems required under sub paragraphs (d) and (e),
which must be provided by the User in addition to the Manufacturer’s Data & Performance
Report reference.
(a) Power Park Unit model
A mathematical model of each type of Power Park Unit (including Electricity Storage
Units) capable of representing its transient and dynamic behaviour under both small and
large disturbance conditions. The model shall include non-linear effects and represent all
equipment relevant to the dynamic performance of the Power Park Unit as agreed with
The Company. The model shall be suitable for the study of balanced, root mean square,
positive phase sequence time-domain behaviour, excluding the effects of electromagnetic
transients, harmonic and sub-harmonic frequencies.
The rotor power coefficient (Cp) versus tip speed ratio () curves for a range of blade
angles (where applicable) together with the corresponding values submitted in
tabular format. The tip speed ratio () is defined as R/U where is the angular
velocity of the rotor, R is the radius of the wind turbine rotor and U is the wind speed.
The electrical power output versus generator rotor speed for a range of wind speeds
over the entire operating range of the Power Park Unit, together with the
corresponding values submitted in tabular format.
The blade angle versus wind speed curve together with the corresponding values
submitted in tabular format.
The electrical power output versus wind speed over the entire operating range of the
Power Park Unit, together with the corresponding values submitted in tabular
format.
Transfer function block diagram, including parameters and description of the
operation of the power electronic converter and fault ride through capability (where
applicable). For any Power Park Units in a Power Park Module with a Completion
Date after 1 September 2022 and any Power Park Units subject to a control system
change or Modification after 1 September 2022 control system models in
accordance with PC.A.9 should be supplied. For the avoidance of doubt, a User may
submit control system models as detailed in PC.A.9 for any Power Park Unit
regardless of Power Park Module Completion Date as an alternative to this
paragraph.
For a Power Park Unit consisting of a synchronous machine in combination with a back
to back DC Converter or HVDC System, or for a Power Park Unit not driven by a wind
turbine, the data to be supplied shall be agreed with The Company in accordance with
PC.A.7.
(c) Torque / speed and blade angle control systems and parameters
For the type of Power Park Unit (as applicable), details of the torque / speed controller
and blade angle controller in the case of a wind turbine and power limitation functions
(where applicable) described in block diagram form showing transfer functions and
parameters of individual elements.
(d) Voltage/Reactive Power/Power Factor control system parameters
* Data items marked with an asterisk are already requested under part 1, PC.A.3.3.1, to
facilitate an early assessment by The Company as to whether detailed stability studies
will be required before an offer of terms for a CUSC Contract can be made. Such data
items have been repeated here merely for completeness and need not, of course, be
resubmitted unless their values, known or estimated, have changed.
* Data items marked with an asterisk are already requested under part 1, PC.A.3.3.1, to
facilitate an early assessment by The Company as to whether detailed stability studies will be
required before an offer of terms for a CUSC Contract can be made. Such data items have
been repeated here merely for completeness and need not, of course, be resubmitted unless
their values, known or estimated, have changed.
PC.A.5.5 Response Data For Frequency Changes
The information detailed below is required to describe the actual frequency response capability
profile as illustrated in Figure CC.A.3.1 of the Connection Conditions or Figure ECC.A.3.1
of the European Connection Conditions, and need only be provided for each:
(i) Genset at Large Power Stations; and
(ii) Generating Unit (including Synchronous Generating Units within a Synchronous
Power Generating Module), Power Park Module (including a DC Connected Power
Park Module) or CCGT Module at a Medium Power Station or DC Converter Station
or HVDC System that has agreed to provide Frequency response in accordance with a
CUSC Contract.
In the case of (ii) above for the rest of this PC.A.5.5 where reference is made to Gensets,
it shall include such Generating Units (including Synchronous Generating Units within
a Synchronous Power Generating Module), CCGT Modules, Power Park Modules
(including DC Connected Power Park Modules), HVDC Systems and DC Converters
as appropriate, but excludes OTSDUW Plant and Apparatus utilising OTSDUW DC
Converters.
PC.A.5.6.2 Generators, HVDC System Owners and DC Converter Station owners must also notify The
Company of any significant factors which may prevent the Mothballed Power Generating
Module, Mothballed Generating Unit, Mothballed Power Park Module (including DC
Connected Power Park Modules), Mothballed HVDC Systems or Mothballed DC
Converter at a DC Converter Station achieving the estimated values provided under
PC.A.5.6.1 above, excluding factors relating to Transmission Entry Capacity.
PC.A.5.6.3 Alternative Fuel Information
The following data items must be supplied with respect to each Generating Unit (including
Synchronous Generating Units within a Synchronous Power Generating Module) whose
main fuel is gas.
For each alternative fuel type (if facility installed):
(a) Alternative fuel type e.g. oil distillate, alternative gas supply
(b) For the changeover from main to alternative fuel:
- Time to carry out off-line and on-line fuel changeover (minutes).
- Maximum output following off-line and on-line changeover (MW).
- Maximum output during on-line fuel changeover (MW).
- Maximum operating time at full load assuming typical and maximum possible stock
levels (hours).
- Maximum rate of replacement of depleted stocks (MWh electrical/day) on the basis
of Good Industry Practice.
- Is changeover to alternative fuel used in normal operating arrangements?
- Number of successful changeovers carried out in the last of The Company’s
Financial Year (choice of 0, 1-5, 6-10, 11-20, >20).
The data items/text in (a) and (b) below must be supplied, by each Generator and HVDC
System Owner and DC Converter Station owner to The Company. In the case of
Generators, the data supplied should be with respect to each BM Unit at any directly
connected Power Station or Large Power Station. For the avoidance of doubt, the data
required under PC.A.5.7.1(a) and (b) below, i) does not need to be supplied in respect of
Restoration Contractors Plant and ii), only needs to be supplied in respect of each BM Unit
at a Large Power Station or any directly connected Power Station and does not need to
include Generating Unit data;
(a) The expected time for each BM Unit to be Synchronised following a Total Shutdown
or Partial Shutdown. The assessment should include the Power Stations or HVDC
Systems or DC Converter Stations ability to re-synchronise all BM Units, if all were
running immediately prior to the Total Shutdown or Partial Shutdown once auxiliary
supplies have been restored, or supplies have been restored to the User’s Site where
the Plant was running immediately prior to the Shutdown) and at time intervals of 12
hours, 24 hours, 36 hours, 48 hours and 72 hours before the BM Unit had been
Shutdown. Additionally this should highlight any specific issues (i.e. those that would
have an impact on the BM Unit’s time to be Synchronised) that may arise, as time
progresses without external supplies being restored or the availability of primary fuel
supplies. In submitting this data, Generators, HVDC System Owners and DC
Converter Station owners should be aware of the requirements in CC.7.11 or
ECC.7.11.
(b) Block Loading Capability. This should be provided in either graphical or tabular
format showing the estimated block loading capability from 0MW to Registered
Capacity and the time between each incremental step. Any particular Active Power
loading points at which the BM Unit should be operated until further changes in output
can be accommodated should also be identified. The data of each BM Unit should be
provided for the condition of a Generating Unit (which was running immediately prior
to the Shutdown) and at time intervals of 12 hours, 24 hours, 36 hours, 48 hours and
72 hours before the BM Unit had been Shutdown. In the case of an HVDC System
or DC Converter Station, data should be provided when the HVDC System or DC
Converter Station (which was running immediately prior to the Shutdown) and at
time intervals of 12 hours, 24 hours, 36 hours, 48 hours and 72 hours prior to the
HVDC System or DC Converter Station had been Shutdown. The block loading
assessment should be done against a frequency variation of 47.5Hz – 52Hz.
PC.A.5.7.2 Where a Network Operator has a Distribution Restoration Zone Plan in place, the data
specified in this section shall be submitted as required under PC.A.1.2 by Network Operators
to The Company annually by calendar week 28. This information may also be requested by
The Company from the relevant Network Operator during System Restoration and should
be provided by Network Operators where reasonably practicable. Restoration Contractors
party to a Distribution Restoration Zone Plan shall, where reasonably practicable, submit
the relevant information to the Network Operator who shall then supply the relevant
information to The Company. The following data shall be provided;
Issue 6 Revision 21 PC 04 March 2024
62 of 93
(a) The expected time for each Restoration Contractor’s Plant to Re-Synchronise to
the Network Operator’s System following a Total Shutdown or Partial Shutdown.
The assessment should include the Restoration Contractor’s ability to Re-
Synchronise all their Plant, if all were running immediately prior to the Total
Shutdown or Partial Shutdown. Additionally, the data and supporting text should
highlight any specific issues (eg those that would affect the time before which the
Restoration Contractor’s Plant could be energised) that may arise as time
progresses from Shutdown without external supplies being restored or the
availability of primary fuel supplies..
(b) The Restoration Contractor’s Plants Block Loading Capability as required in
PC.A.5.7.1(b).
PC.A.5.7.3 From 31st December 2026 onwards, all Users and Restoration Contractors are required to
confirm annually they comply with the applicable requirements of OC5.7. In the case of
Generators, HVDC System Owners, DC Converter owners, Non-Embedded Customers,
and Network Operators this confirmation shall be provided in their Week 24 submission.
From 1st January 2024 until 31st December 2026, evidence to support the work Generators,
HVDC System Owners, DC Converter owners, Non-Embedded Customers, and Network
Operators are carrying out to achieve these requirements on or after 31st December 2026
shall be provided in their Week 24 submission.
PC.A.5.7.4 From 1st January 2025 onwards, Restoration Contractors, Generators, HVDC System
Owners and DC Converter owners, shall supply the governor setting information in
accordance with the applicable requirements of CC.6.3.7(g), (h) and (i) or ECC.6.3.7.3.8.
PC.A.5.8.1 The following data need only be supplied by Users (be they a GB Code User or EU Code
User) or Non-CUSC Parties who wish to offer a Grid Forming Capability as provided for
ECC.6.3.19.3. Where such a Grid Forming Capability is provided then the following data
items and models are to be supplied.
(i) Each GBGF-I shall be designed so as not to interact and affect the operation,
performance, safety or capability of other User’s Plant and Apparatus connected to
the Total System. To achieve this requirement, each User shall be required to submit
a Network Frequency Perturbation Plot and Nichols Chart (or equivalent as
agreed with The Company) which shall be assessed in accordance with the
requirements of ECP.A.3.9.3.
Each User or Non-CUSC Party is required to supply a high level equivalent
architecture diagram of their Grid Forming Plant as shown in Figure PC.A.5.8.1
together with the equivalent linear classical block diagram model (using the Laplace
Operator) of their Grid Forming Plant which should preferably be in the general
form shown in Figure PC.A.5.8.1 (a) or Figure PC.A.5.8.1 (b). When submitting
either Figure PC.A.5.8.1 (a) or Figure PC.A.5.8.1 (b), each User or Non-CUSC
Party can use their own design, that may be very different to Figures PC.A.5.8.1 (a)
or PC.A.5.8.1 (b), but should contain all relevant functions that can include simulation
models and other equivalent data and documentation.
Each User or Non-CUSC Party shall provide a model of their Grid Forming Plant
which provides a true and accurate reflection of its Grid Forming Capability.
Figure PC.A.5.8.1 (a) Preferred simplified diagram of a GBGF-I with a Power System
Stabiliser “PSS” that can add damping to the GBGF-I’s closed loop function shown by
the solid red line and the dotted blue line.
Figure PC.A.5.8.1 (b) – Preferred simplified diagram of a system with a droop control
ability that can add Control-Based Active Droop Power. This diagram does not add
extra closed loop damping to the GBGF-I’s closed loop function shown by the solid red
line and the dotted blue line.
(ii) In order to participate in the Grid Forming Capability market, User’s and Non-
CUSC Parties are required to provide data of their GBGF-I in accordance with
Figures PC.A.5.8.1(a) and PC.A.5.8.1(b). Users and Non-CUSC Parties in respect
of Grid Forming Plants should indicate if the data is submitted on a unit or
aggregated basis. Table PC.A.5.8.1(a) defines the notation used in Figure PC.5.8.1
Table PC.A.5.8.1
(iii) In order to participate in a Grid Forming Capability market, User’s and Non-CUSC Parties
are also required to provide the data of their GBGF-I in accordance with Table PC.A.5.8.1.2
to The Company. The details and arrangements for Users and Non-CUSC Parties
participating in this market shall be published on The Company’s Website.
Table PC.A.5.8.2
H = Installed MWs / Rated installed MVA
(equation 1)
He = (Active ROCOF Response Power at 1 Hz / s x System Frequency) / ( Installed MVA x 2 )
(equation 2)
PC.A.8 To allow a User to model the National Electricity Transmission System, The Company will
provide, upon request, the following Network Data to Users, calculated in accordance with
Good Industry Practice:
To allow a User to assess undertaking OTSDUW and except where provided for in Appendix
F, The Company will provide upon request the following Network Data to Users, calculated
in accordance with Good Industry Practice:
PC.A.8.1 Single Point of Connection
For a Single Point of Connection to a User's System (and OTSUA), as a Transmission
System voltage source, the data (as at the HV side of the Point of Connection (and in the
case of OTSUA, each Interface Point and Connection Point) reflecting data given to The
Company by Users) will be given to a User as follows:
The data items listed under the following parts of PC.A.8.3:
(a) (i), (ii), (iii), (iv), (v) and (vi) and the data items shall be provided in accordance with the
detailed provisions of PC.A.8.3 (b) - (e).
PC.A.8.2 Multiple Point of Connection
For a Multiple Point of Connection to a User's System equivalents suitable for use in
loadflow and fault level analysis shall be provided. These equivalents will normally be in the
form of a π model or extension with a source (or demand for a loadflow equivalent) at each
node and a linking impedance. The boundary nodes for the equivalent shall be either at the
Connection Point (and in the case of OTSDUW, each Interface Point and Connection
Point) or (where The Company agrees) at suitable nodes (the nodes to be agreed with the
User) within the National Electricity Transmission System. The data at the Connection
Point (and in the case of OTSDUW, each Interface Point and Connection Point) will be
given to a User as follows:
The data items listed under the following parts of PC.A.8.3:-
(a) (i), (ii), (iv), (v), (vi), (vii), (viii), (ix), (x) and (xi)
and the data items shall be provided in accordance with the detailed provisions of PC.A.8.3
(b) - (e).
When an equivalent of this form is not required The Company will not provide the data items
listed under the following parts of PC.A.8.3:-
(a) (vii), (viii), (ix), (x) and (xi)
PC.A.8.3 Data Items
(a) The following is a list of data utilised in this part of the PC. It also contains rules on the
data which generally apply.
(i) symmetrical three-phase short circuit current infeed at the instant of fault from the
National Electricity Transmission System, (I1");
(ii) symmetrical three-phase short circuit current from the National Electricity
Transmission System after the subtransient fault current contribution has
substantially decayed, (I1');
(iii) the zero sequence source resistance and reactance values at the Point of
Connection (and in case of OTSUA, each Interface Point and Connection Point),
consistent with the maximum infeed below;
(iv) the pre-fault voltage magnitude at which the maximum fault currents were calculated;
(v) the positive sequence X/R ratio at the instant of fault;
(vi) the negative sequence resistance and reactance values of the National Electricity
Transmission System seen from the Point of Connection (and in case of OTSUA,
each Interface Point and Connection Point), if substantially different from the
PC.B.1 The diagrams below show three examples of single line diagrams, showing the detail that
should be incorporated in the diagram. The first example is for an Network Operator
connection, the second for a Generator connection, the third for a Power Park Module
electrically equivalent system.
Notes:
(1) The electrically equivalent Power Park Unit consists of a number of actual Power Park
Units of the same type ie. any equipment external to the Power Park Unit terminals is
considered as part of the equivalent network. Power Park Units of different types shall
be included in separate electrically equivalent Power Park Units. The total number of
equivalent Power Park Units shall represent all of the actual Power Park Units in the
Power Park Module (which could be a DC Connected Power Park Module).
(2) Separate electrically equivalent networks are required for each different type of
electrically equivalent Power Park Unit. The electrically equivalent network shall include
all equipment between the Power Park Unit terminals and the Common Collection
Busbar.
(3) All Plant and Apparatus including the circuit breakers, transformers, lines, cables and
reactive compensation plant between the Common Collection Busbar and Substation
A shall be shown.
PC.C.1 Planning and design of the SPT and SHETL Transmission Systems is based generally, but
not totally, on criteria which evolved from joint consultation among various Transmission
Licensees responsible for design of the National Electricity Transmission System.
PC.C.2 The above criteria are set down within the standards, memoranda, recommendations and
reports and are provided as a guide to system planning. It should be noted that each scheme
for reinforcement or modification of the Transmission System is individually designed in the
light of economic and technical factors associated with the particular system limitations under
consideration.
PC.C.3 The tables below identify the literature referred to above, together with the main topics
considered within each document.
PART 1 – SHETL's TECHNICAL AND DESIGN CRITERIA
PC.D.1 Pursuant to PC.3.4, The Company will not disclose to a Relevant Transmission Licensee
data items specified in the below extract:
PC DATA
DATA DESCRIPTION UNITS
REFERENCE CATEGORY
Option 1
Part of Option 2
PC.A.5.3.2 (d)
Option 2 (i) All Generating Units (including Synchronous
Generating Units forming part of a Synchronous
Power Generating Module)
Governor Deadband or
(Frequency Response Deadband and Frequency
Response Insensitivity)*
Maximum Hz DPD II
Normal Hz DPD II
Minimum Hz DPD II
MW Export MW SPD
MW Import
PC.E.1 In the absence of any relevant Electrical Standards, Offshore Transmission Licensees
and Generators undertaking OTSDUW are required to ensure that all equipment used in the
construction of their network is:
(i) Fully compliant and suitably designed to any relevant Technical Specification;
(ii) Suitable for use and operation in an Offshore environment, where such parts of the
Offshore Transmission System and OTSDUW Plant and Apparatus are located in
Offshore Waters and are not installed in an area that is protected from that Offshore
environment, and
(iii) Compatible with any relevant Electrical Standards or Technical Specifications at the
Offshore Grid Entry Point and Interface Point.
PC.E.2 The table below identifies the technical and design criteria that will be used in the design and
development of an Offshore Transmission System and OTSDUW Plant and Apparatus.
* Note:- Items 2, 3 and 4 above shall only apply at the Interface Point.
PC.F.1 Introduction
PC.F.1.1 Appendix F specifies data requirements to be submitted to The Company by Users and
Users by The Company in respect of OTSDUW.
PC.F.1.2 Such User submissions shall be in accordance with the OTSDUW Development and Data
Timetable in a Construction Agreement.
PC.F.1.3 Such submissions shall be issued to The Company with the offer of a CUSC Contract in the
case of the data in Part 1 and otherwise in accordance with the OTSDUW Development and
Data Timetable in a Construction Agreement.
PC.F.2. OTSDUW Network Data and Information
PC.F.2.1 With the offer of a CUSC Contract under the OTSDUW Arrangements The Company shall
provide:
(a) the site specific technical design and operational criteria for the Connection Site;
(b) the site specific technical design and operational criteria for the Interface Point, and
(c) details of The Company’s preliminary identification and consideration of the options
available for the Interface Point in the context of the User’s application for connection
or modification, the preliminary costs used by The Company in assessing such options
and the Offshore Works Assumptions including the assumed Interface Point identified
during these preliminary considerations.
PC.F.2.2 In accordance with the OTSDUW Development and Data Timetable in a Construction
Agreement The Company shall provide the following information and data to a User:
(a) equivalent of the fault infeed or fault level ratings at the Interface Point (as identified in
the Offshore Works Assumptions)
(b) notification of numbering and nomenclature of the HV Apparatus comprised in the
OTSDUW;
(i) past or present physical properties, including both actual and designed physical
properties, of Plant and Apparatus forming part of the National Electricity
Transmission System at the Interface Point at which the OTSUA will be connected
to the extent it is required for the design and construction of the OTSDUW, including
but not limited to:
(ii) the voltage of any part of such Plant and Apparatus;
(iii) the electrical current flowing in or over such Plant and Apparatus;
(iv) the configuration of any part of such Plant and Apparatus
(v) the temperature of any part of such Plant and Apparatus;
(vi) the pressure of any fluid forming part of such Plant and Apparatus
(vii) the electromagnetic properties of such Plant and Apparatus; and
(viii) the technical specifications, settings or operation of any Protection Systems
forming part of such Plant and Apparatus.
(c) information necessary to enable the User to harmonise the OTSDUW with construction
works elsewhere on the National Electricity Transmission System that could affect the
OTSDUW;
(d) information related to the current or future configuration of any circuits of the Onshore
Transmission System with which the OTSUA are to connect;
(e) any changes which are planned on the National Electricity Transmission System in
the current or following six Financial Years and which will materially affect the planning
or development of the OTSDUW.
Issue 6 Revision 21 PC 04 March 2024
92 of 93
PC.F.2.3 At the Users reasonable request, additional information and data in respect of the National
Electricity Transmission System shall be provided.
PC.F.2.4 OTSDUW Data And Information
PC.F.2.4.1 In accordance with the OTSDUW Development and Data Timetable in a Construction
Agreement, the User shall provide to The Company, the following information and data
relating to the OTSDUW Plant and Apparatus in accordance with Appendix A of the Planning
Code.
CONTENTS
(This contents page does not form part of the Grid Code)
CC.2 OBJECTIVE
CC.2.1 The objective of the CC is to ensure that by specifying minimum technical, design and operational
criteria, the basic rules for connection to the National Electricity Transmission System and (for
certain GB Code Users) to a User's System are similar for all GB Code Users of an equivalent
category and will enable The Company to comply with its statutory and Transmission Licence
obligations.
CC.2.2 In the case of any OTSDUW, the objective of the CC is to ensure that by specifying the minimum
technical, design and operational criteria, the basic rules relating to an Offshore Transmission
System designed and constructed by an Offshore Transmission Licensee or designed and/or
constructed by an GB Code User under the OTSDUW Arrangements are equivalent.
CC.2.3 Provisions of the CC which apply in relation to OTSDUW and OTSUA, and/or a Transmission
Interface Site, shall (in any particular case) apply up to the OTSUA Transfer Time, whereupon such
provisions shall (without prejudice to any prior non-compliance) cease to apply, without prejudice to
the continuing application of provisions of the CC applying in relation to the relevant Offshore
Transmission System and/or Connection Site. It is the case therefore that in cases where the
OTSUA becomes operational prior to the OTSUA Transfer Time that a GB Generator is required
to comply with this CC both as it applies to its Plant and Apparatus at a Connection
Site\Connection Point and the OTSUA at the Transmission Interface Site/Transmission
Interface Point until the OTSUA Transfer Time and this CC shall be construed accordingly.
CC.2.4 In relation to OTSDUW, provisions otherwise to be contained in a Bilateral Agreement may be
contained in the Construction Agreement, and accordingly a reference in the CC to a relevant
Bilateral Agreement includes the relevant Construction Agreement.
CC.3 SCOPE
CC.3.1 The CC applies to The Company and to GB Code Users, which in the CC means:
(a) GB Generators (other than those which only have Embedded Small Power Stations),
including those undertaking OTSDUW;
(b) Network Operators;
(c) Non-Embedded Customers;
(d) DC Converter Station owners;
(e) BM Participants and Externally Interconnected System Operators who are also GB Code
Users in respect of CC.6.5, CC.7.9, CC.7.10 and CC.7.11 only; and
CC.3.2 The above categories of GB Code User will become bound by the CC prior to them generating,
distributing, supplying or consuming, as the case may be, and references to the various categories
should, therefore, be taken as referring to them in that prospective role as well as to GB Code Users
actually connected.
CC.3.3 Embedded Medium Power Stations not subject to a Bilateral Agreement and Embedded DC
Converter Stations not subject to a Bilateral Agreement Provisions.
The following provisions apply in respect of Embedded Medium Power Stations not subject to a
Bilateral Agreement and Embedded DC Converter Stations not subject to a Bilateral
Agreement.
CC.3.3.1 The obligations within the CC that are expressed to be applicable to GB Generators in respect of
Embedded Medium Power Stations not subject to a Bilateral Agreement and DC Converter
Station Owners in respect of Embedded DC Converter Stations not subject to a Bilateral
Agreement (where the obligations are in each case listed in CC.3.3.2) shall be read and construed
as obligations that the Network Operator within whose System any such Medium Power Station
or DC Converter Station is Embedded must ensure are performed and discharged by the GB
Generator or the DC Converter Station owner. Embedded Medium Power Stations not subject
to a Bilateral Agreement and Embedded DC Converter Stations not subject to a Bilateral
Agreement which are located Offshore and which are connected to an Onshore GB Code Users
System will be required to meet the applicable requirements of the Grid Code as though they are an
Onshore GB Generator or Onshore DC Converter Station Owner connected to an Onshore User
System Entry Point.
CC.3.3.2 The Network Operator within whose System a Medium Power Station not subject to a Bilateral
Agreement is Embedded or a DC Converter Station not subject to a Bilateral Agreement is
Embedded must ensure that the following obligations in the CC are performed and discharged by
the GB Generator in respect of each such Embedded Medium Power Station or the DC Converter
Station owner in the case of an Embedded DC Converter Station:
CC.5.1
CC.5.2.2
CC.5.3
CC.6.1.3
CC.6.1.5 (b)
CC.6.3.2, CC.6.3.3, CC.6.3.4, CC.6.3.6, CC.6.3.7, CC.6.3.8, CC.6.3.9, CC.6.3.10, CC.6.3.12,
CC.6.3.13, CC.6.3.15, CC.6.3.16
CC.6.4.4
CC.6.5.6 (where required by CC.6.4.4)
that would otherwise have been specified in a Bilateral Agreement will be notified to the relevant
Network Operator in writing in accordance with the provisions of the CUSC and the Network
Operator must ensure such requirements are performed and discharged by the GB Generator or
the DC Converter Station owner.
CC.3.4 In the case of Offshore Embedded Power Stations connected to an Offshore GB Code User’s
System which directly connects to an Offshore Transmission System, any additional
requirements in respect of such Offshore Embedded Power Stations may be specified in the
relevant Bilateral Agreement with the Network Operator or in any Bilateral Agreement between
The Company and such Offshore Embedded Power Station.
CC.3.5 In the case of a GB Generator undertaking OTSDUW connecting to an Onshore Network
Operator’s System, any additional requirements in respect of such OTSDUW Plant and Apparatus
will be specified in the relevant Bilateral Agreement with the GB Generator. For the avoidance of
doubt, requirements applicable to GB Generators undertaking OTSDUW and connecting to a
Network Operator’s System, shall be consistent with those applicable requirements of GB
Generators undertaking OTSDUW and connecting to a Transmission Interface Point.
CC.4 PROCEDURE
CC.4.1 The CUSC contains certain provisions relating to the procedure for connection to the National
Electricity Transmission System or, in the case of Embedded Power Stations or Embedded DC
Converter Stations, becoming operational and includes provisions relating to certain conditions to
be complied with by GB Code Users prior to and during the course of The Company notifying the
GB Code User that it has the right to become operational. The procedure for a GB Code User to
become connected is set out in the Compliance Processes.
CC.5 CONNECTION
CC.5.1 The provisions relating to connecting to the National Electricity Transmission System (or to a
User's System in the case of a connection of an Embedded Large Power Station or Embedded
Medium Power Station or Embedded DC Converter Station) are contained in:
(a) the CUSC and/or CUSC Contract (or in the relevant application form or offer for a CUSC
Contract);
(b) or, in the case of an Embedded Development, the relevant Distribution Code and/or the
Embedded Development Agreement for the connection (or in the relevant application form or
offer for an Embedded Development Agreement),
and include provisions relating to both the submission of information and reports relating to
compliance with the relevant Connection Conditions for that GB Code User, Safety Rules,
commissioning programmes, Operation Diagrams and approval to connect (and their equivalents
in the case of Embedded Medium Power Stations not subject to a Bilateral Agreement or
Embedded DC Converter Stations not subject to a Bilateral Agreement). References in the CC
to the "Bilateral Agreement” and/or “Construction Agreement" and/or “Embedded Development
Agreement” shall be deemed to include references to the application form or offer therefor.
CC.5.2 Items For Submission
For the avoidance of doubt, disconnection, by frequency or speed based relays is not permitted within
the frequency range 47.5Hz to 51.5Hz, unless agreed with The Company in accordance with
CC.6.3.12.
Grid Voltage Variations
CC.6.1.4 Subject as provided below, the voltage on the 400kV part of the National Electricity Transmission
System at each Connection Site with a GB Code User (and in the case of OTSDUW Plant and
Apparatus, a Transmission Interface Point) will normally remain within 5% of the nominal value
unless abnormal conditions prevail. The minimum voltage is -10% and the maximum voltage is +10%
unless abnormal conditions prevail, but voltages between +5% and +10% will not last longer than 15
minutes unless abnormal conditions prevail. Voltages on the 275kV and 132kV parts of the National
Electricity Transmission System at each Connection Site with a User (and in the case of
OTSDUW Plant and Apparatus, a Transmission Interface Point) will normally remain within the
limits 10% of the nominal value unless abnormal conditions prevail for example but not limited to,
situations such as during System Restoration. At nominal System voltages below 132kV the
voltage of the National Electricity Transmission System at each Connection Site with a User
(and in the case of OTSDUW Plant and Apparatus, a Transmission Interface Point) will normally
remain within the limits 6% of the nominal value unless abnormal conditions prevail for example but
not limited to, situations such as during System Restoration. Under fault conditions, voltage may
collapse transiently to zero at the point of fault until the fault is cleared. The normal operating ranges
of the National Electricity Transmission System are summarised below:
The Company and a GB Code User may agree greater or lesser variations in voltage to those set
out above in relation to a particular Connection Site, and insofar as a greater or lesser variation is
agreed, the relevant figure set out above shall, in relation to that GB Code User at the particular
Connection Site, be replaced by the figure agreed.
Vsteadystate
%Vsteadystate = │100 x │
Vn
and
Vmax
%Vmax =100 x ;
Vn
(ii) Vn is the nominal system voltage;
(iii) Vsteadystate is the voltage at the end of a period of 1 s during which the rate of change of
system voltage over time is ≤ 0.5%;
Issue 6 Revision 21 CC 04 March 2024
8 of 99
(iv) Vsteadystate is the difference in voltage between the initial steady state voltage prior to the
RVC (V0) and the final steady state voltage after the RVC (V0’);
(v) Vmax is the absolute change in the system voltage relative to the initial steady state
system voltage (V0);
(vi) All voltages are the r.m.s. of the voltage measured over one cycle refreshed every half a
cycle as per BS EN 61000-4-30; and
(vii) The applications in the ‘Example Applicability’ column are examples only and are not
definitive.
NOTE 1: 6% is permissible for 100 ms reduced to 3% thereafter as per Figure CC.6.1.7 (1).
If the profile of repetitive voltage change(s) falls within the envelope given in Figure CC.6.1.7 (1) , the
assessment of such voltage change(s) shall be undertaken according to the recommendations for
assessment of flicker and shall conform to the planning levels provided for flicker.
If any part of the voltage change(s) falls outside the envelope given in Figure CC.6.1.7(1), the assessment
of such voltage changes, repetitive or not, shall be done according to the guidance and limits for RVCs.
NOTE 2: No more than 1 event is permitted per day, consisting of up to 4 RVCs, each separated by at least 10
minutes with all switching completed within a two-hour window.
NOTE 3: −10% is permissible for 100 ms reduced to -6% until 2 s then reduced to -3% thereafter as per Figure
CC.6.1.7 (2).
NOTE 4: +6% is permissible for 0.8 s from the instant the event begins then reduced to +3% thereafter as per Figure
CC.6.1.7 (2).
NOTE 5: −12% is permissible for 100 ms reduced to −10% until 2 s then reduced to -3% thereafter as per Figure
CC.6.1.7 (3).
(b) The voltage change limit is the absolute maximum allowed of either the phase-to-earth voltage
change or the phase-to-phase voltage change, whichever is the highest. The limits do not apply
to single phasor equivalent voltages, e.g. positive phase sequence (PPS) voltages. For high
impedance earthed systems, the maximum phase-to-phase, i.e. line voltage, should be used for
assessment.
(c) The RVCs in Category 2 and 3 should not exceed the limits depicted in the time dependent
characteristic shown in Figure CC.6.1.7 (2) and Figure CC.6.1.7 (3) respectively. These limits
do not apply to: 1) fault clearance operations; or 2) immediate operations in response to fault
conditions; or 3) operations relating to post fault system restoration (for the avoidance of doubt
this third exception pertains to a fault that is external to the Users Plant and Apparatus).
(d) Any RVCs permitted in Category 2 and Category 3 should be at least 10 minutes apart.
(e) The value of Vsteadystate should be established immediately prior to the start of a RVC. Following
a RVC, the voltage should remain within the relevant envelope, as shown in Figures CC.6.1.7
(1), CC.6.1.7 (2), CC.6.1.7 (3), until a Vsteadystate condition has been satisfied.
V0+3%
V0
V0−3%
V0−6%
V0−10%
V0+6%
V0+3%
V0
V0−3%
V0−10%
V0−12%
(f) The voltage change between two steady state voltage conditions should not exceed 3%. (The limit is based
on 3% of the nominal voltage of the system (Vn) as measured at the Point of Common Coupling. The step
voltage change as measured at the customer’s supply terminals or equipment terminals could be greater.
For example: The step voltage change limit stated in BS EN 61000-3-3 and BS EN 61000-3-11 is 3.3%
when measured at the equipment terminals.)
(g) The limits apply to voltage changes measured at the Point of Common Coupling.
(h) Category 3 events that are planned should be notified to The Company in advance.
NOTE 1: The magnitude of Pst is linear with respect to the magnitude of the voltage changes giving rise to it.
NOTE 2: Extreme caution is advised in allowing any excursions of P st and Plt above the planning level.
The values and figures referred to in this paragraph CC.6.1.7 are derived from Engineering
Recommendation P28 Issue 2.
CC.6.1.8 Voltage fluctuations at a Point of Common Coupling with a fluctuating Load directly connected to
an Offshore Transmission System (or in the case of OTSDUW, OTSDUW Plant and Apparatus)
shall not exceed the limits set out in the Bilateral Agreement.
Sub-Synchronous Resonance and Sub-Synchronous Torsional Interaction
CC.6.1.9 The Company shall ensure that GB Code Users' Plant and Apparatus will not be subject to
unacceptable Sub-Synchronous Oscillation conditions as specified in the relevant Licence
Standards.
CC.6.1.10 The Company shall ensure where necessary, and in consultation with Relevant Transmission
Licensees where required, that any relevant site specific conditions applicable at a GB Code User's
Connection Site, including a description of the Sub-Synchronous Oscillation conditions considered
in the application of the relevant License Standards, are set out in the GB Code User's Bilateral
Agreement.
Any alternative Protection settings shall be included in the Restoration Plan. Normal and
alternative Protection settings shall be agreed between The Company and/or Relevant
Transmission Licensee and/or Network Operator and Restoration Contractor as part of
developing a Restoration Plan.
a) From the normal to the alternative Protection settings and control settings on their Plant
and Apparatus; and:-
b) From the alternative to the normal Protection settings and control settings whilst their Plant
remains in service,
Any alternative Protection settings or control settings shall be included in the Restoration Plan.
Normal and alternative Protection settings and control settings shall be agreed between The
Company and the Network Operator as part of developing a Restoration Plan.
Figure 1
Point A is equivalent 0.95 leading Power Factor at Rated MW output or Interface Point
(in MVAr) to Capacity in the case of OTSDUW Plant and Apparatus
Point B is equivalent 0.95 lagging Power Factor at Rated MW output or Interface Point
(in MVAr) to: Capacity in the case of OTSDUW Plant and Apparatus
Point C is equivalent -5% of Rated MW output or Interface Point Capacity in the case
(in MVAr) to: of OTSDUW Plant and Apparatus
Point D is equivalent +5% of Rated MW output or Interface Point Capacity in the case
(in MVAr) to: of OTSDUW Plant and Apparatus
(d) All Onshore Non-Synchronous Generating Units and Onshore Power Park Modules in
Scotland with a Completion Date after 1 April 2005 and before 1 January 2006 must be capable
of supplying Rated MW at the range of power factors either:
(i) from 0.95 lead to 0.95 lag as illustrated in Figure 1 at the User System Entry Point for
Embedded GB Generators or at the HV side of the 33/132kV or 33/275kV or 33/400kV
transformer for GB Generators directly connected to the Onshore Transmission System.
With all Plant in service, the Reactive Power limits defined at Rated MW will apply at all
Active Power output levels above 20% of the Rated MW output as defined in Figure 1.
These Reactive Power limits will be reduced pro rata to the amount of Plant in service, or
(ii) from 0.95 lead to 0.90 lag at the Onshore Non-Synchronous Generating Unit (including
Power Park Unit) terminals. For the avoidance of doubt GB Generators complying with
this option (ii) are not required to comply with CC.6.3.2(b).
(e) The short circuit ratio of Offshore Synchronous Generating Units at a Large Power Station
shall be not less than 0.5. At a Large Power Station all Offshore Synchronous Generating
Units, Offshore Non-Synchronous Generating Units, Offshore DC Converters and
Offshore Power Park Modules must be capable of maintaining:
(i) zero transfer of Reactive Power at the Offshore Grid Entry Point for all GB Generators
with an Offshore Grid Entry Point at the LV Side of the Offshore Platform at all Active
Power output levels under steady state voltage conditions. The steady state tolerance on
Reactive Power transfer to and from an Offshore Transmission System expressed in
MVAr shall be no greater than 5% of the Rated MW, or
(ii) a transfer of Reactive Power at the Offshore Grid Entry Point at a value specified in the
Bilateral Agreement that will be equivalent to zero at the LV Side of the Offshore
Platform. In addition, the steady state tolerance on Reactive Power transfer to and from
an Offshore Transmission System expressed in MVAr at the LV Side of the Offshore
Platform shall be no greater than 5% of the Rated MW, or
(iii) the Reactive Power capability (within an associated steady state tolerance) specified in
the Bilateral Agreement if any alternative has been agreed with the GB Generator
Offshore Transmission Licensee and The Company. In the case of Generators and/or
DC Converter owners who are GB Code User’s and also Restoration Contractors who
own and operate Anchor Plant and/or Top Up Restoration Plant, or GB Code Users
who own and operate Plant and Apparatus which is operating with a Grid Forming
Capability in service, the Reactive Power capability requirements at the Offshore Grid
Entry Point shall be agreed between the Restoration Contractor or GB Code User the
Offshore Transmission Licensee and The Company in order to facilitate the operation
of an Offshore Local Joint Restoration Plan.
(f) In addition, a Genset shall meet the operational requirements as specified in BC2.A.2.6.
CC.6.3.3 Each Generating Unit, DC Converter (including an OTSDUW DC Converter), Power Park Module
and/or CCGT Module must be capable of:
(a) continuously maintaining constant Active Power output for System Frequency changes within
the range 50.5 to 49.5 Hz; and
(c) For the avoidance of doubt, in the case of a Generating Unit or Power Park Module (or
OTSDUW DC Converters at the Interface Point) using an Intermittent Power Source where
the mechanical power input will not be constant over time, the requirement is that the Active
Power output shall be independent of System Frequency under (a) above and should not drop
with System Frequency by greater than the amount specified in (b) above.
(d) A DC Converter Station must be capable of maintaining its Active Power input (i.e. when
operating in a mode analogous to Demand) from the National Electricity Transmission
System (or User System in the case of an Embedded DC Converter Station) at a level not
greater than the figure determined by the linear relationship shown in Figure 3 for System
Frequency changes within the range 49.5 to 47 Hz, such that if the System Frequency drops
to 47.8 Hz the Active Power input decreases by more than 60%.
100% of Active
Power Input
40% of Active
Power Input
Figure 3
(e) At a Large Power Station, in the case of an Offshore Generating Unit, Offshore Power Park
Module, Offshore DC Converter and OTSDUW DC Converter, the GB Generator shall
comply with the requirements of CC.6.3.3. GB Generators should be aware that Section K of
the STC places requirements on Offshore Transmission Licensees which utilise a
Transmission DC Converter as part of their Offshore Transmission System to make
appropriate provisions to enable GB Generators to fulfil their obligations.
(f) In the case of an OTSDUW DC Converter the OTSDUW Plant and Apparatus shall provide a
continuous signal indicating the real time frequency measured at the Interface Point to the
Offshore Grid Entry Point.
CC.6.3.4 At the Grid Entry Point, the Active Power output under steady state conditions of any Generating
Unit, DC Converter or Power Park Module directly connected to the National Electricity
Transmission System or in the case of OTSDUW, the Active Power transfer at the Interface Point,
under steady state conditions of any OTSDUW Plant and Apparatus should not be affected by
voltage changes in the normal operating range specified in paragraph CC.6.1.4 by more than the
change in Active Power losses at reduced or increased voltage. In addition:
(a) For any Onshore Generating Unit, Onshore DC Converter and Onshore Power Park
Module or OTSDUW Plant and Apparatus, the Reactive Power output under steady state
conditions should be fully available within the voltage range 5% at 400kV, 275kV and 132kV
and lower voltages, except for an Onshore Power Park Module or Onshore Non-
Synchronous Generating Unit if Embedded at 33kV and below (or directly connected to the
Onshore Transmission System at 33kV and below) where the requirement shown in Figure
4 applies.
(b) At a Large Power Station, in the case of an Offshore Generating Unit, Offshore DC
Converter and Offshore Power Park Module where an alternative reactive capability has been
agreed with the GB Generator, as specified in CC.6.3.2(e) (iii), the voltage / Reactive Power
requirement shall be specified in the Bilateral Agreement. The Reactive Power output under
steady state conditions shall be fully available within the voltage range 5% at 400kV, 275kV
and 132kV and lower voltages.
105%
100%
95%
Power Factor 0.95 Lead at Rated 1.0 Power Factor 0.95 lag at Rated MW
MW output or Onshore Grid output or Onshore Grid Entry Point
Entry Point equivalent Power equivalent Power Factor if connected
Factor if connected to the to the Onshore Transmission
Onshore Transmission System System in Scotland or optionally in
in Scotland Scotland for Plant with a Completion
Date before 1 January 2006 Power
Factor 0.9 lag at an Onshore Non-
synchronous Generating Unit or
Onshore Power Park Unit Terminals
Figure 4
Control Arrangements
CC.6.3.6 (a) Each:
(i) Offshore Generating Unit in a Large Power Station or Onshore Generating Unit; or,
(ii) Onshore DC Converter with a Completion Date on or after 1 April 2005 or Offshore DC
Converter at a Large Power Station; or,
(iii) Onshore Power Park Module in England and Wales with a Completion Date on or after
1 January 2006; or,
(iv) Onshore Power Park Module in operation in Scotland on or after 1 January 2006 (with a
Completion Date after 1 July 2004 and in a Power Station with a Registered Capacity
of 50MW or more); or,
(v) Offshore Power Park Module in a Large Power Station with a Registered Capacity of
50MW or more;
CC.6.3.7 (a) Each Generating Unit, DC Converter or Power Park Module (excluding Onshore Power
Park Modules in Scotland with a Completion Date before 1 July 2004 or Onshore Power Park
Modules in a Power Station in Scotland with a Registered Capacity less than 50MW or
Offshore Power Park Modules in a Large Power Station located Offshore with a Registered
Capacity less than 50MW) must be fitted with a fast acting proportional Frequency control
device (or turbine speed governor) and unit load controller or equivalent control device to
provide Frequency response under normal operational conditions in accordance with
Balancing Code 3 (BC3). In the case of a Power Park Module the Frequency or speed
control device(s) may be on the Power Park Module or on each individual Power Park Unit or
be a combination of both. The Frequency control device(s) (or speed governor(s)) must be
designed and operated to the appropriate:
(i) European Specification; or
(ii) in the absence of a relevant European Specification, such other standard which is in
common use within the European Community (which may include a manufacturer
specification);
as at the time when the installation of which it forms part was designed or (in the case of
modification or alteration to the Frequency control device (or turbine speed governor)) when
the modification or alteration was designed.
The European Specification or other standard utilised in accordance with sub-paragraph
CC.6.3.7 (a) (ii) will be notified to The Company by the GB Generator or DC Converter Station
owner or, in the case of an Embedded Medium Power Station not subject to a Bilateral
Agreement or Embedded DC Converter Station not subject to a Bilateral Agreement, the
relevant Network Operator:
(i) as part of the application for a Bilateral Agreement; or
(ii) as part of the application for a varied Bilateral Agreement; or
(iii) in the case of an Embedded Development, within 28 days of entry into the Embedded
Development Agreement (or such later time as agreed with The Company); or
(iv) as soon as possible prior to any modification or alteration to the Frequency control device
(or governor); and
Issue 6 Revision 21 CC 04 March 2024
27 of 99
(b) The Frequency control device (or speed governor) in co-ordination with other control devices
must control the Generating Unit, DC Converter or Power Park Module Active Power Output
with stability over the entire operating range of the Generating Unit, DC Converter or Power
Park Module; and
(c) The Frequency control device (or speed governor) must meet the following minimum
requirements:
(i) Where a Generating Unit, DC Converter or Power Park Module becomes isolated from
the rest of the Total System but is still supplying Customers, the Frequency control
device (or speed governor) must also be able to control System Frequency below 52Hz
unless this causes the Generating Unit, DC Converter or Power Park Module to operate
below its Designed Minimum Operating Level when it is possible that it may, as detailed
in BC 3.7.3, trip after a time. For the avoidance of doubt, the Generating Unit, DC
Converter or Power Park Module is only required to operate within the System
Frequency range 47 - 52 Hz as defined in CC.6.1.3;
(ii) the Frequency control device (or speed governor) must be capable of being set so that it
operates with an overall speed Droop of between 3% and 5%. For the avoidance of doubt,
in the case of a Power Park Module the speed Droop should be equivalent of a fixed
setting between 3% and 5% applied to each Power Park Unit in service;
(iii) in the case of all Generating Units, DC Converter or Power Park Module other than the
Steam Unit within a CCGT Module the Frequency control device (or speed governor)
deadband should be no greater than 0.03Hz (for the avoidance of doubt, ±0.015Hz). In the
case of the Steam Unit within a CCGT Module, the speed Governor Deadband should
be set to an appropriate value consistent with the requirements of CC.6.3.7(c)(i) and the
requirements of BC3.7.2 for the provision of Limited High Frequency Response;
For the avoidance of doubt, the minimum requirements in (ii) and (iii) for the provision of System
Ancillary Services do not restrict the negotiation of Commercial Ancillary Services between
The Company and the GB Code User using other parameters; and
(d) A facility to modify, so as to fulfil the requirements of the Balancing Codes, the Target
Frequency setting either continuously or in a maximum of 0.05 Hz steps over at least the range
50 0.1 Hz should be provided in the unit load controller or equivalent device.
(e) (i) Each Onshore Generating Unit and/or CCGT Module which has a Completion Date
after 1 January 2001 in England and Wales, and after 1 April 2005 in Scotland, must be
capable of meeting the minimum Frequency response requirement profile subject to and
in accordance with the provisions of Appendix 3.
(ii) Each DC Converter at a DC Converter Station which has a Completion Date on or after
1 April 2005 and each Offshore DC Converter at a Large Power Station must be capable
of meeting the minimum Frequency response requirement profile subject to and in
accordance with the provisions of Appendix 3.
(iii) Each Onshore Power Park Module in operation in England and Wales with a Completion
Date on or after 1 January 2006 must be capable of meeting the minimum Frequency
response requirement profile subject to and in accordance with the provisions of Appendix
3.
(iv) Each Onshore Power Park Module in operation on or after 1 January 2006 in Scotland
(with a Completion Date on or after 1 April 2005 and a Registered Capacity of 50MW or
more) must be capable of meeting the minimum Frequency response requirement profile
subject to and in accordance with the provisions of Appendix 3.
(v) Each Offshore Generating Unit in a Large Power Station must be capable of meeting
the minimum Frequency response requirement profile subject to and in accordance with
the provisions of Appendix 3.
(vi) Each Offshore Power Park Module in a Large Power Station with a Registered
Capacity of 50 MW or greater, must be capable of meeting the minimum Frequency
response requirement profile subject to and in accordance with the provisions of Appendix
Issue 6 Revision 21 CC 04 March 2024
28 of 99
3.
(vii) Subject to the requirements of CC.6.3.7(e), Offshore Generating Units at a Large Power
Station, Offshore Power Park Modules at a Large Power Station and Offshore DC
Converters in a Large Power Station shall comply with the requirements of CC.6.3.7. GB
Generators should be aware that Section K of the STC places requirements on Offshore
Transmission Licensees which utilise a Transmission DC Converter as part of their
Offshore Transmission System to make appropriate provisions to enable GB
Generators to fulfil their obligations.
(viii) Each OTSDUW DC Converter must be capable of providing a continuous signal indicating
the real time frequency measured at the Interface Point to the Offshore Grid Entry Point.
(f) For the avoidance of doubt, the requirements of Appendix 3 do not apply to:
(i) Generating Units and/or CCGT Modules which have a Completion Date before 1
January 2001 in England and Wales, and before 1 April 2005 in Scotland, for whom the
remaining requirements of this clause CC.6.3.7 shall continue to apply unchanged: or
(ii) DC Converters at a DC Converter Station which have a Completion Date before 1 April
2005; or
(iii) Onshore Power Park Modules in England and Wales with a Completion Date before 1
January 2006 for whom only the requirements of Limited Frequency Sensitive Mode
(BC3.5.2) operation shall apply; or
(iv) Onshore Power Park Modules in operation in Scotland before 1 January 2006 for whom
only the requirements of Limited Frequency Sensitive Mode (BC3.5.2) operation shall
apply; or
(v) Onshore Power Park Modules in operation after 1 January 2006 in Scotland which have
a Completion Date before 1 April 2005 for whom the remaining requirements of this clause
CC.6.3.7 shall continue to apply unchanged; or
(vi) Offshore Power Park Modules which are in a Large Power Station with a Registered
Capacity less than 50MW for whom only the requirements of Limited Frequency
Sensitive Mode (BC3.5.2) operation shall apply; or
(g) Restoration Contractors shall be capable of operating their Generating Units or DC Converters
or Power Park Modules such that the Frequency control device (or turbine speed governor) and
unit load controller or equivalent control device can be switched to Frequency control only with no
load influence, during the early stages of a System Restoration whilst in island operation.
(h) Generators and DC Converter owners shall advise The Company of the capability of operating
their Generating Units or Power Park Modules or DC Converters such that the Frequency
control device (or turbine speed governor) and unit load controller or equivalent control device can
be switched to Frequency control only with no load influence, during the early stages of System
Restoration whilst in island operation. If there is a suitable capability, The Company and the User
shall agree on how it shall be used and kept available.
(i) In addition to the requirements of CC.6.3.7 (g) and CC.6.3.7(h) the following shall apply:-
(i) Changes to any control schemes and settings identified from CC.6.3.7(g) and (h) shall be
agreed between The Company and/or Relevant Transmission Licensee and/or Network
Operator as recorded in the Restoration Plan.
(ii) During System Restoration, any changes to the schemes and settings defined in
CC.6.3.7(g) and (h) of the different control devices of the Generating Unit or Power Park
Module or Restoration Contractor’s Plant or DC Converter shall be coordinated and
agreed between the Relevant Transmission Licensee, the GB Generator, Restoration
Contractor and DC Converter owner as part of a Restoration Plan.
Excitation and Voltage Control Performance Requirements
(vi) In particular, other control facilities, including constant Reactive Power output control
modes and constant Power Factor control modes (but excluding VAr limiters) are not
required. However, if present in the excitation or voltage control system they will be
disabled unless the Bilateral Agreement records otherwise. Operation of such control
facilities will be in accordance with the provisions contained in BC2.
(b) Excitation and voltage control performance requirements applicable to Offshore Generating
Units at a Large Power Station, Offshore Power Park Modules at a Large Power Station
and Offshore DC Converters at a Large Power Station.
A continuously acting automatic control system is required to provide either:
(i) control of Reactive Power (as specified in CC.6.3.2(e) (i) (ii)) at the Offshore Grid Entry
Point without instability over the entire operating range of the Offshore Generating Unit,
Offshore DC Converter or Offshore Power Park Module. The performance requirements
for this automatic control system will be specified in the Bilateral Agreement or;
(ii) where an alternative reactive capability has been specified in the Bilateral Agreement, in
accordance with CC.6.3.2 (e) (iii), the Offshore Generating Unit, Offshore Power Park
Module or Offshore DC Converter will be required to control voltage and / or Reactive
Power without instability over the entire operating range of the Offshore Generating Unit,
Offshore Power Park Module or Offshore DC Converter. The performance requirements
of the control system will be specified in the Bilateral Agreement.
In addition to CC.6.3.8(b) (i) and (ii) the requirements for excitation control facilities, including
Power System Stabilisers, where in The Company’s view these are necessary for system
reasons, will be specified in the Bilateral Agreement. Reference is made to on-load
commissioning witnessed by The Company in BC2.11.2.
Steady state Load Inaccuracies
CC.6.3.9 The standard deviation of Load error at steady state Load over a 30 minute period must not exceed
2.5 per cent of a Genset’s Registered Capacity. Where a Genset is instructed to Frequency
sensitive operation, allowance will be made in determining whether there has been an error
according to the governor droop characteristic registered under the PC.
For the avoidance of doubt in the case of a Power Park Module allowance will be made for the full
variation of mechanical power output.
Negative Phase Sequence Loadings
CC.6.3.10 In addition to meeting the conditions specified in CC.6.1.5(b), each Synchronous Generating Unit
will be required to withstand, without tripping, the negative phase sequence loading incurred by
clearance of a close-up phase-to-phase fault, by System Back-Up Protection on the National
Electricity Transmission System or User System located Onshore in which it is Embedded.
Neutral Earthing
CC.6.3.11 At nominal System voltages of 132kV and above the higher voltage windings of a transformer of a
Generating Unit, DC Converter, Power Park Module or transformer resulting from OTSDUW must
be star connected with the star point suitable for connection to earth. The earthing and lower voltage
winding arrangement shall be such as to ensure that the Earth Fault Factor requirement of
paragraph CC.6.2.1.1 (b) will be met on the National Electricity Transmission System at nominal
System voltages of 132kV and above.
Frequency Sensitive Relays
In addition to the requirements of CC.6.3.15.1 (a) each Synchronous Generating Unit, each
with a Completion Date on or after 1 April 2005 shall:
(i) remain transiently stable and connected to the System without tripping of any
Synchronous Generating Unit for balanced Supergrid Voltage dips and associated
durations on the Onshore Transmission System (which could be at the Interface Point)
anywhere on or above the heavy black line shown in Figure 5a. Appendix 4A and Figures
CC.A.4A.3.2 (a), (b) and (c) provide an explanation and illustrations of Figure 5a; and,
15
Figure 5b
(ii) provide Active Power output at the Grid Entry Point or in the case of an OTSDUW, Active
Power transfer capability at the Transmission Interface Point, during Supergrid Voltage
dips on the Onshore Transmission System as described in Figure 5b, at least in
proportion to the retained balanced voltage at the Onshore Grid Entry Point (for Onshore
Power Park Modules) or Interface Point (for OTSDUW Plant and Apparatus and
Offshore Power Park Modules) (or the retained balanced voltage at the User System
Entry Point if Embedded) except in the case of a Non-Synchronous Generating Unit or
OTSDUW Plant and Apparatus or Power Park Module where there has been a reduction
in the Intermittent Power Source or in the case of OTSDUW Active Power transfer
capability in the time range in Figure 5b that restricts the Active Power output or in the
case of an OTSDUW Active Power transfer capability below this level and shall generate
maximum reactive current (where the voltage at the Grid Entry Point, or in the case of an
OTSDUW Plant and Apparatus, the Interface Point voltage, is outside the limits specified
in CC.6.1.4) without exceeding the transient rating limits of the OTSDUW Plant and
Apparatus or Power Park Module and any constituent Power Park Unit; and,
(iii) restore Active Power output (or, in the case of OTSDUW, Active Power transfer
capability), following Supergrid Voltage dips on the Onshore Transmission System as
described in Figure 5b, within 1 second of restoration of the voltage at the:
Onshore Grid Entry Point for directly connected Onshore Power Park Modules or,
Interface Point for OTSDUW Plant and Apparatus and Offshore Power Park
Modules or,
User System Entry Point for Embedded Onshore Power Park Modules or,
User System Entry Point for Embedded Medium Power Stations which comprise
Power Park Modules not subject to a Bilateral Agreement and with an Onshore
Issue 6 Revision 21 CC 04 March 2024
36 of 99
User System Entry Point (irrespective of whether they are located Onshore or
Offshore)
to the minimum levels specified in CC.6.1.4 to at least 90% of the level available
immediately before the occurrence of the dip except in the case of a Non-Synchronous
Generating Unit, OTSDUW Plant and Apparatus or Power Park Module where there
has been a reduction in the Intermittent Power Source in the time range in Figure 5b that
restricts the Active Power output or, in the case of OTSDUW, Active Power transfer
capability below this level. Once the Active Power output or, in the case of OTSDUW,
Active Power transfer capability has been restored to the required level, Active Power
oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at least that
which would have been delivered if the Active Power was constant
- the oscillations are adequately damped.
For the avoidance of doubt a balanced Onshore Transmission System Supergrid Voltage
meets the requirements of CC.6.1.5 (b) and CC.6.1.6.
CC.6.3.15.2 Fault Ride Through applicable to Offshore Generating Units at a Large Power Station, Offshore
Power Park Modules at a Large Power Station and Offshore DC Converters at a Large Power
Station who choose to meet the fault ride through requirements at the LV side of the Offshore
Platform
(a) Requirements on Offshore Generating Units, Offshore Power Park Modules and Offshore
DC Converters to withstand voltage dips on the LV Side of the Offshore Platform for up to
140ms in duration as a result of faults and / or voltage dips on the Onshore Transmission
System operating at Supergrid Voltage.
(i) Each Offshore Generating Unit, Offshore DC Converter, or Offshore Power Park
Module and any constituent Power Park Unit thereof shall remain transiently stable and
connected to the System without tripping of any Offshore Generating Unit, or Offshore
DC Converter or Offshore Power Park Module and / or any constituent Power Park Unit
or, in the case of Plant and Apparatus installed on or after 1 December 2017, reactive
compensation equipment, for any balanced or unbalanced voltage dips on the LV Side of
the Offshore Platform whose profile is anywhere on or above the heavy black line shown
in Figure 6. For the avoidance of doubt, the profile beyond 140ms in Figure 6 shows the
minimum recovery in voltage that will be seen by the Generator’s Plant and Apparatus
following clearance of the fault at 140ms. Appendix 4B and Figures CC.A.4B.2 (a) and (b)
provide further illustration of the voltage recovery profile that may be seen. It should be
noted that in the case of an Offshore Generating Unit, Offshore DC Converter or
Offshore Power Park Module (including any Offshore Power Park Unit thereof) which
is connected to an Offshore Transmission System which includes a Transmission DC
Converter as part of that Offshore Transmission System, the Offshore Grid Entry Point
voltage may not indicate the presence of a fault on the Onshore Transmission System.
The voltage dip will affect the level of Active Power that can be transferred to the Onshore
Transmission System and therefore subject the Offshore Generating Unit, Offshore
DC Converter or Offshore Power Park Module (including any Offshore Power Park Unit
thereof) to a load rejection.
100%
94%
60%
15%
Figure 6
V/VN is the ratio of the actual voltage on one or more phases at the LV Side of the Offshore
Platform to the nominal voltage of the LV Side of the Offshore Platform.
(ii) Each Offshore Generating Unit, or Offshore Power Park Module and any constituent
Power Park Unit thereof shall provide Active Power output, during voltage dips on the LV
Side of the Offshore Platform as described in Figure 6, at least in proportion to the
retained voltage at the LV Side of the Offshore Platform except in the case of an
Offshore Non-Synchronous Generating Unit or Offshore Power Park Module where
there has been a reduction in the Intermittent Power Source in the time range in Figure
6 that restricts the Active Power output below this level and shall generate maximum
reactive current without exceeding the transient rating limits of the Offshore Generating
Unit or Offshore Power Park Module and any constituent Power Park Unit or, in the
case of Plant and Apparatus installed on or after 1 December 2017, reactive
compensation equipment. Once the Active Power output has been restored to the
required level, Active Power oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at least that
which would have been delivered if the Active Power was constant
- the oscillations are adequately damped
and;
(iii) Each Offshore DC Converter shall be designed to meet the Active Power recovery
characteristics as specified in the Bilateral Agreement upon restoration of the voltage at
the LV Side of the Offshore Platform.
(b) Requirements of Offshore Generating Units, Offshore Power Park Modules, to withstand
voltage dips on the LV Side of the Offshore Platform greater than 140ms in duration.
(1b) Requirements applicable to Offshore Synchronous Generating Units to withstand voltage dips
on the LV Side of the Offshore Platform greater than 140ms in duration.
In addition to the requirements of CC.6.3.15.2. (a) each Offshore Synchronous Generating Unit
shall:
(i) remain transiently stable and connected to the System without tripping of any Offshore
Synchronous Generating Unit for any balanced voltage dips on the LV side of the
Offshore Platform and associated durations anywhere on or above the heavy black line
Issue 6 Revision 21 CC 04 March 2024
38 of 99
shown in Figure 7a. Appendix 4B and Figures CC.A.4B.3.2 (a), (b) and (c) provide an
explanation and illustrations of Figure 7a. It should be noted that in the case of an Offshore
Synchronous Generating Unit which is connected to an Offshore Transmission
System which includes a Transmission DC Converter as part of that Offshore
Transmission System, the Offshore Grid Entry Point voltage may not indicate the
presence of a voltage dip on the Onshore Transmission System. The voltage dip will
affect the level of Active Power that can be transferred to the Onshore Transmission
System and therefore subject the Offshore Generating Unit, to a load rejection.
(ii) provide Active Power output, during voltage dips on the LV Side of the Offshore Platform
as described in Figure 7a, at least in proportion to the retained balanced or unbalanced
voltage at the LV Side of the Offshore Platform and shall generate maximum reactive
current (where the voltage at the Offshore Grid Entry Point is outside the limits specified
in CC.6.1.4) without exceeding the transient rating limits of the Offshore Synchronous
Generating Unit and,
(iii) within 1 second of restoration of the voltage to 1.0p.u of the nominal voltage at the LV Side
of the Offshore Platform, restore Active Power to at least 90% of the Offshore
Synchronous Generating Unit's immediate pre-disturbed value, unless there has been a
reduction in the Intermittent Power Source in the time range in Figure 7a that restricts the
Active Power output below this level. Once the Active Power output has been restored
to the required level, Active Power oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at least that
which would have been delivered if the Active Power was constant
- the oscillations are adequately damped
(2b) Requirements applicable to Offshore Power Park Modules to withstand voltage dips on the
LV Side of the Offshore Platform greater than 140ms in duration.
In addition to the requirements of CC.6.3.15.2. (a) each Offshore Power Park Module and / or
any constituent Power Park Unit, shall:
(i) remain transiently stable and connected to the System without tripping of any Offshore
Power Park Module and / or any constituent Power Park Unit, for any balanced voltage
15
Figure 7b
(ii) provide Active Power output, during voltage dips on the LV Side of the Offshore Platform
as described in Figure 7b, at least in proportion to the retained balanced or unbalanced
voltage at the LV Side of the Offshore Platform except in the case of an Offshore Non-
Synchronous Generating Unit or Offshore Power Park Module where there has been
a reduction in the Intermittent Power Source in the time range in Figure 7b that restricts
the Active Power output below this level and shall generate maximum reactive current
(where the voltage at the Offshore Grid Entry Point is outside the limits specified in
CC.6.1.4) without exceeding the transient rating limits of the Offshore Power Park Module
and any constituent Power Park Unit or reactive compensation equipment. For Plant and
Apparatus installed on or after 1 December 2017, switched reactive compensation
equipment (such as mechanically switched capacitors and reactors) shall be controlled
such that it is not switched in or out of service during the fault but may act to assist in post
fault voltage recovery; and,
(iii) within 1 second of the restoration of the voltage at the LV Side of the Offshore Platform
(to the minimum levels specified in CC.6.1.4) restore Active Power to at least 90% of the
Offshore Power Park Module's immediate pre-disturbed value, unless there has been a
reduction in the Intermittent Power Source in the time range in Figure 7b that restricts the
Active Power output below this level. Once the Active Power output has been restored
to the required level, Active Power oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at least that
which would have been delivered if the Active Power was constant
- the oscillations are adequately damped
CC.6.3.15.3 Other Requirements
Instructor Facilities
CC.6.5.7 The User shall accommodate Instructor Facilities provided by The Company for the receipt of
operational messages relating to System conditions.
Electronic Data Communication Facilities
CC.6.5.8 (a) All BM Participants must ensure that appropriate electronic data communication facilities are
in place to permit the submission of data, as required by the Grid Code, to The Company.
(b) In addition,
(1) any GB Code User that wishes to participate in the Balancing Mechanism;
or
(2) any BM Participant in respect of its BM Units at a Power Station where the Construction
Agreement and/or a Bilateral Agreement has a Completion Date on or after 1 January
2013 and the BM Participant is required to provide all Part 1 System Ancillary Services
in accordance with CC.8.1 (unless The Company has otherwise agreed)
must ensure that appropriate automatic logging devices are installed at the Control Points of
its BM Units to submit data to and to receive instructions from The Company, as required by
the Grid Code. For the avoidance of doubt, in the case of an Interconnector User, the Control
Point will be at the Control Centre of the appropriate Externally Interconnected System
Operator.
(c) Detailed specifications of these required electronic facilities will be provided by The Company
on request and they are listed as Electrical Standards in the Annex to the General Conditions.
For the avoidance of doubt, where The Company has agreed with a BM Participant that Control
Telephony is not required and where the BM Participant does not have a continuously staffed
Control Point the BM Participant may be unable to act as a Defence Service Provider and shall
be unable to act as a Restoration Contractor where these require Control Telephony or a Control
Point in respect of the specification of any such services falling into these categories.
CC.7.10.1 From 04/09/2024 The Company, each Generator, DC Converter Station owner, Network
Operator, Non-Embedded Customer and each Restoration Contractor with a continuously
staffed Control Point or Control Centre as provided for in CC.7.9 shall
(i) Ensure they have the appropriate Critical Tools and Facilities necessary to control their assets
during System Restoration, from their Control Point or Control Centre as appropriate for a
minimum period of 72 hours (or such longer period as agreed between the Generator, DC
Converter Station owner, Network Operator, Non-Embedded Customer and/or Restoration
Contractor and The Company) following a Total Shutdown or Partial Shutdown.
(ii) Ensure as far as reasonably practical that they have adequate control equipment redundancy
in place so that in the event of a failure of one or more components of the control system its
function is unimpaired.
(iii) Report on the results of their management and testing for their Critical Tools and Facilities on
request by The Company.
CC.7.10.2 From 04/09/2024 each BM Participant including a Virtual Lead Party with a continuously staffed
Control Point as provided for in CC.7.9 (excluding those BM Participants covered by the
requirements of CC.7.10.1), shall:-
(i) Ensure they have the appropriate Critical Tools and Facilities (as defined in clause (c) of
the definition of Critical Tools and Facilities in the Grid Code Glossary and Definitions) for
a minimum period of 72 hours (or such longer period as agreed between the BM Participant
including a Virtual Lead Party and The Company) following a Total Shutdown or Partial
Shutdown.
(iii) Report on the results of their management and testing for their Critical Tools and Facilities
on request by The Company.
CC.7.10.3 In the case of a BM Participant or Virtual Lead Party which has an Anchor Restoration Contract
or Top Up Restoration Contract in respect of one or more of its aggregated Plants, the
requirements of CC.7.10.1 shall only apply between the Control Point of the BM Participant or
Virtual Lead Party and that Plant with an Anchor Plant Capability or Top Up Restoration
Capability. For other non-contracted Plants under the control of the BM Participant or Virtual
Lead Party, the requirements of CC.7.10.2 shall continue to apply.
CC.7.10.4 Where a Network Operator installs a Distribution Restoration Zone Control System to facilitate
operation of a Distribution Restoration Zone Plan, the high level functional requirements of the
Distribution Restoration Zone Control System shall be in accordance with the guidance provided
in the applicable Electrical Standard listed in the annex to the General Conditions.
CC.7.10.5 Network Operators shall ensure that their substations which are required to be operable during
System Restoration have 72 hour electrical supply resilience to facilitate Network Operators being
able to:
• restore auxiliary supplies to Transmission substations;
• switch Demand in accordance with a Restoration Plan;
• support The Company in satisfying the requirements of the Electricity System Restoration
Standard.
CC.7.10.6 The Company, each GB Code User and Restoration Contractor shall ensure their Critical Tools
and Facilities are cyber secure accordance with the Security of Network and Information System
(NIS) Regulations. This requirement applies to The Company, GB Code Users and Restoration
Contractors at all times.
CC.7.10.7 Notwithstanding the requirements of CC.7.10.1, The Company, each GB Code User and
Restoration Contractor shall ensure that their Critical Tools and Facilities are sufficiently robust
and reliable such that they are capable of handling, processing and prioritising the significant
volumes of data that could reasonably be expected to occur during System Restoration.
CC.7.10.8 Where an Offshore Generator is connected to an Offshore Transmission System and the
Offshore Transmission Licensee does not have Critical Tools and Facilities installed on its
Offshore Transmission System, The Company will make an allowance for the Critical Tools and
Facilities required to be installed by the Offshore Generator.
CC.7.11 Obligations on and Assurance from The Company, GB Code Users and Restoration Contractors
during Total Shutdown and Partial Shutdown conditions
CC.7.11.1 In respect of The Company, its Apparatus shall be designed such that it can safely shutdown and
does not pose a risk to personnel or Apparatus in the event of a total loss of supply.
CC.7.11.2 All GB Code Users and Restoration Contractors shall ensure their Plant and Apparatus can
safely shut down and does not pose a risk to Plant and/or personnel in the event of a total loss of
supplies at a GB Code User’s Site(s) or Restoration Contractor’s site be it caused by a Total
Shutdown, Partial Shutdown or such other event. In satisfying this requirement, Generators, DC
Converter owners and Restoration Contractors shall be able to demonstrate to The Company
that in the event supplies were to be lost to their Site, then on the restoration of supplies, their Plant
can be made operational and begin to operate in at least the same way and as quickly as would be
expected for a cold start following a Total System Shutdown or Partial System Shutdown in
accordance with the data submitted in PC.A.5.7 in accordance with the Week 24 process. For GB
Issue 6 Revision 21 CC 04 March 2024
55 of 99
Code Users where they believe this requirement is cost prohibitive or technically impossible, such
GB Code Users shall discuss the issue with The Company, and The Company shall inform The
Authority of the details agreed. Where such an issue cannot be agreed by The Company, following
all reasonable attempts, or where the capability provided by the GB Code User cannot be agreed
by The Company as being sufficient after examining all reasonable alternative solutions through the
Compliance Processes, the GB Code User may apply for a derogation from the Grid Code.
CC.7.11.3 The requirements of CC.7.11.1 and CC.7.11.2 shall apply for a period of total loss of supplies to The
Company’s operational sites or a GB Code User’s Site or Restoration Contractor’s site of up to
72 hours. GB Code Users and Restoration Contractors shall confirm to The Company that the
total loss of supplies to their Site for a period of up to 72 hours shall not result in damage to Plant
and Apparatus such that it would then be unable to operate upon the restoration of electrical supplies
to the site.
CC.7.11.4 Network Operators shall ensure that in coordination with The Company and relevant
Transmission Licensees, they have the capability to switch Demand at sufficient speed to support
The Company in satisfying the requirements of the Electricity System Restoration Standard. This
requirement assumes:
• the successful implementation of Restoration Plans,
• the successful delivery of the obligations of Restoration Contractors who are parties to
these plans; and
• the further requirements of OC9 have been implemented.
(d) GB Generators in respect of Medium Power Stations (except Embedded Medium Power
Stations) are obliged to provide in respect of Reactive Power only:
and Part 2 lists the System Ancillary Services which GB Generators or Restoration Contractors
will provide only if agreement to provide them is reached with The Company or in the case where a
Restoration Contractor is party to a Distribution Restoration Zone Plan, agreement is reached
with The Company and Network Operator:
Part 1
(a) Reactive Power supplied (in accordance with CC.6.3.2) otherwise than by means of
synchronous or static compensators (except in the case of a Power Park Module where
synchronous or static compensators within the Power Park Module may be used to provide
Reactive Power)
(b) Frequency Control by means of Frequency sensitive generation - CC.6.3.7 and BC3.5.1
Issue 6 Revision 21 CC 04 March 2024
56 of 99
Part 2
(c) Frequency Control by means of Fast Start - CC.6.3.14.
(d) Anchor Plant Capability or Top Up Restoration Capability - CC.6.3.5
(e) System to Generator Operational Intertripping.
(f) Services provided by Restoration Contractors.
CC.A.1.1 Principles
Types of Schedules
CC.A.1.1.1 At all Complexes (which in the context of this CC shall include, Interface Sites until the OTSUA
Transfer Time) the following Site Responsibility Schedules shall be drawn up using the relevant
proforma attached or with such variations as may be agreed between The Company and Users, but
in the absence of agreement the relevant proforma attached will be used. In addition, in the case of
OTSDUW Plant and Apparatus, and in readiness for the OTSUA Transfer Time, the User shall
provide The Company with the necessary information such that Site Responsibility Schedules in
this form can be prepared by the Relevant Transmission Licensees for the Transmission
Interface Site:
(a) Schedule of HV Apparatus
(b) Schedule of Plant, LV/MV Apparatus, services and supplies;
(c) Schedule of telecommunications and measurements Apparatus.
Other than at Generating Unit, DC Converter, Power Park Module and Power Station locations,
the schedules referred to in (b) and (c) may be combined.
New Connection Sites
CC.A.1.1.2 In the case of a new Connection Site each Site Responsibility Schedule for a Connection Site
shall be prepared by The Company in consultation with relevant GB Code Users at least 2 weeks
prior to the Completion Date (or, where the OTSUA is to become Operational prior to the OTSUA
Transfer Time, an alternative date) under the Bilateral Agreement and/or Construction
Agreement for that Connection Site (which may form part of a Complex). In the case of a new
Interface Site where the OTSUA is to become Operational prior to the OTSUA Transfer Time each
Site Responsibility Schedule for an Interface Site shall be prepared by The Company in
consultation with relevant GB Code Users at least 2 weeks prior to the Completion Date under the
Bilateral Agreement and/or Construction Agreement for that Interface Site (which may form part
of a Complex) (and references to and requirements placed on “Connection Site” in this CC shall
also be read as “Interface Site” where the context requires and until the OTSUA Transfer Time).
Each GB Code User shall, in accordance with the timing requirements of the Bilateral Agreement
and/or Construction Agreement, provide information to The Company to enable it to prepare the
Site Responsibility Schedule.
Sub-division
CC.A.1.1.3 Each Site Responsibility Schedule will be subdivided to take account of any separate Connection
Sites on that Complex.
Scope
CC.A.1.1.4 Each Site Responsibility Schedule shall detail for each item of Plant and Apparatus:
(a) Plant/Apparatus ownership;
(b) Site Manager (Controller) (except in the case of Plant/Apparatus located in SPT’s
Transmission Area);
(c) Safety issues comprising applicable Safety Rules and Control Person or other responsible
person (Safety Co-ordinator), or such other person who is responsible for safety;
(d) Operations issues comprising applicable Operational Procedures and Control Engineer;
(e) Responsibility to undertake statutory inspections, fault investigation and maintenance.
Each Connection Point shall be precisely shown.
1 Details of circuits traversing the Connection Site are only needed from the date which is the earlier of the date when the Site Responsibility
Schedule is first updated and 15th October 2004. In Scotland or Offshore, from a date to be agreed between The Company and the
Relevant Transmission Licensee.
Issue 6 Revision 21 CC 04 March 2024
59 of 99
CC.A.1.1.15 When an GB Code User identified on a Site Responsibility Schedule, or The Company, as the
case may be, becomes aware that an alteration to the Site Responsibility Schedule is necessary
urgently to reflect, for example, an emergency situation which has arisen outside its control, the GB
Code User shall notify The Company, or The Company shall notify the GB Code User, as the case
may be, immediately and will discuss:
(a) what change is necessary to the Site Responsibility Schedule;
(b) whether the Site Responsibility Schedule is to be modified temporarily or permanently;
(c) the distribution of the revised Site Responsibility Schedule.
The Company will prepare a revised Site Responsibility Schedule as soon as possible, and in any
event within seven days of it being informed of or knowing the necessary alteration. The Site
Responsibility Schedule will be confirmed by GB Code Users and signed on behalf of The
Company and GB Code Users and the Relevant Transmission Licensee (by the persons referred
to in CC.A.1.1.9) as soon as possible after it has been prepared and sent to GB Code Users for
confirmation.
Responsible Managers
CC.A.1.1.16 Each GB Code User shall, prior to the Completion Date under each Bilateral Agreement and/or
Construction Agreement, supply to The Company a list of Managers who have been duly
authorised to sign Site Responsibility Schedules on behalf of the GB Code User and The
Company shall, prior to the Completion Date under each Bilateral Agreement and/or
Construction Agreement, supply to that GB Code User the name of the Relevant Transmission
Licensee’s Responsible Manager and each shall supply to the other any changes to such list six
weeks before the change takes effect where the change is anticipated, and as soon as possible after
the change, where the change was not anticipated.
De-commissioning of Connection Sites
CC.A.1.1.17 Where a Connection Site is to be de-commissioned, whichever of The Company or the GB Code
User who is initiating the de-commissioning must contact the other to arrange for the Site
Responsibility Schedule to be amended at the relevant time.
AREA
COMPLEX: SCHEDULE:
CONNECTION SITE:
AREA
COMPLEX: SCHEDULE:
CONNECTION SITE:
NOTES:
Basic Principles
(1) Where practicable, all the HV Apparatus on any Connection Site shall be shown on one
Operation Diagram. Provided the clarity of the diagram is not impaired, the layout shall
represent as closely as possible the geographical arrangement on the Connection Site.
(2) Where more than one Operation Diagram is unavoidable, duplication of identical information
on more than one Operation Diagram must be avoided.
(3) The Operation Diagram must show accurately the current status of the Apparatus e.g.
whether commissioned or decommissioned. Where decommissioned, the associated
switchbay will be labelled "spare bay".
(4) Provision will be made on the Operation Diagram for signifying approvals, together with
provision for details of revisions and dates.
(5) Operation Diagrams will be prepared in A4 format or such other format as may be agreed
with The Company.
(6) The Operation Diagram should normally be drawn single line. However, where appropriate,
detail which applies to individual phases shall be shown. For example, some HV Apparatus
is numbered individually per phase.
CC.A.4A.1 Scope
The fault ride through requirement is defined in CC.6.3.15.1 (a), (b) and CC.6.3.15.3. This
Appendix provides illustrations by way of examples only of CC.6.3.15.1 (a) (i) and further
background and illustrations to CC.6.3.15.1 (1b) (i) and CC.6.3.15.1 (2b) (i) and is not intended
to show all possible permutations.
CC.A.4A.2 Short Circuit Faults At Supergrid Voltage On The Onshore Transmission System Up To 140ms
In Duration
For short circuit faults at Supergrid Voltage on the Onshore Transmission System (which
could be at an Interface Point) up to 140ms in duration, the fault ride through requirement is
defined in CC.6.3.15.1 (a) (i). Figures CC.A.4A.1 (a) and (b) illustrate two typical examples of
voltage recovery for short-circuit faults cleared within 140ms by two circuit breakers (a) and
three circuit breakers (b) respectively.
CC.A.4A.3 Supergrid Voltage Dips On The Onshore Transmission System Greater Than 140ms In
Duration
CC.A.4A3.1 Requirements applicable to Synchronous Generating Units subject to Supergrid Voltage
dips on the Onshore Transmission System greater than 140ms in duration.
For balanced Supergrid Voltage dips on the Onshore Transmission System having
durations greater than 140ms and up to 3 minutes, the fault ride through requirement is defined
in CC.6.3.15.1 (1b) and Figure 5a which is reproduced in this Appendix as Figure CC.A.4A3.1
and termed the voltage–duration profile.
This profile is not a voltage-time response curve that would be obtained by plotting the
transient voltage response at a point on the Onshore Transmission System (or User
System if located Onshore) to a disturbance. Rather, each point on the profile (i.e. the heavy
black line) represents a voltage level and an associated time duration which connected
Synchronous Generating Units must withstand or ride through.
Figures CC.A.4A3.2 (a), (b) and (c) illustrate the meaning of the voltage-duration profile for
voltage dips having durations greater than 140ms.
CC.A.4A3.2 Requirements applicable to Power Park Modules or OTSDUW Plant and Apparatus subject
to Supergrid Voltage dips on the Onshore Transmission System greater than 140ms in
duration.
For balanced Supergrid Voltage dips on the Onshore Transmission System (which could
be at an Interface Point) having durations greater than 140ms and up to 3 minutes the fault
ride through requirement is defined in CC.6.3.15.1 (2b) and Figure 5b which is reproduced in
this Appendix as Figure CC.A.4A3.3 and termed the voltage–duration profile.
Figure CC.A.4A3.3
CC.A.4B.1 Scope
The fault ride through requirement is defined in CC.6.3.15.2 (a), (b) and CC.6.3.15.3. This
Appendix provides illustrations by way of examples only of CC.6.3.15.2 (a) (i) and further
background and illustrations to CC.6.3.15.2 (1b) and CC.6.3.15.2 (2b) and is not intended to
show all possible permutations.
CC.A.4B.2 Voltage Dips On The LV Side Of The Offshore Platform Up To 140ms In Duration
For voltage dips on the LV Side of the Offshore Platform which last up to 140ms in duration,
the fault ride through requirement is defined in CC.6.3.15.2 (a) (i). This includes Figure 6
which is reproduced here in Figure CC.A.4B.1. The purpose of this requirement is to translate
the conditions caused by a balanced or unbalanced fault which occurs on the Onshore
Transmission System (which may include the Interface Point) at the LV Side of the
Offshore Platform.
V/VN is the ratio of the voltage at the LV side of the Offshore Platform to the nominal voltage
of the LV side of the Offshore Platform.
Figure CC.A.4B.1
Figures CC.A.4B.2 (a) and CC.A.4B.2 (b) illustrate two typical examples of the voltage
recovery seen at the LV Side of the Offshore Platform for a short circuit fault cleared within
140ms by (a) two circuit breakers and (b) three circuit breakers on the Onshore Transmission
System.
CCA.4B.3 Voltage Dips Which Occur On The LV Side Of The Offshore Platform Greater Than 140ms
In Duration
CC.A.4B.3.1 Requirements applicable to Offshore Synchronous Generating Units subject to voltage dips
which occur on the LV Side of the Offshore Platform greater than 140ms in duration.
In addition to CC.A.4B.2 the fault ride through requirements applicable to Offshore
Synchronous Generating Units during balanced voltage dips which occur at the LV Side of
the Offshore Platform and having durations greater than 140ms and up to 3 minutes are
defined in CC.6.3.15.2 (1b) and Figure 7a which is reproduced in this Appendix as Figure
CC.A.4B3.1 and termed the voltage–duration profile.
This profile is not a voltage-time response curve that would be obtained by plotting the
transient voltage response at the LV Side of the Offshore Platform to a disturbance. Rather,
each point on the profile (i.e. the heavy black line) represents a voltage level and an associated
time duration which connected Offshore Synchronous Generating Units must withstand or
ride through.
Figure CC.A.4B3.1
CC.A.4B.3.2 Requirements applicable to Offshore Power Park Modules subject to Voltage which occur
on The LV Side Of The Offshore Platform greater than 140ms in duration.
In addition to CCA.4B.2 the fault ride through requirements applicable for Offshore Power
Park Modules during balanced voltage dips which occur at the LV Side of the Offshore
Platform and have durations greater than 140ms and up to 3 minutes are defined in
CC.6.3.15.2 (2b) (i) and Figure 7b which is reproduced in this Appendix as Figure CC.A.4B.4
and termed the voltage–duration profile.
Figure CC.A.4B.4
Figure CC.A.4B.5(c)
(b) Operating time: Relay operating time shall not be more than 150 ms;
(e) Output contacts: Two output contacts per stage to be capable of repetitively
making and breaking for 1000 operations:
CC.A.5.4.3 Each Network Operator and Relevant Transmission Licensee shall aim to execute testing
on its low frequency demand disconnection relays installed within its network and in service
at least once every three years, although this may be extended to no more than every five
years if considered to be required for operational purposes.
48.8 5
48.75 5
48.7 10
48.6 7.5 10
48.5 7.5 10
48.4 7.5 10 10
48.2 7.5 10 10
48.0 5 10 10
47.8 5
Total % Demand 60 40 40
Table CC.A.5.5.1a
CC.A.6.2.8.3 The GB Generator shall also make provision to prevent any over-excitation restriction of the
generator when the Excitation System is under manual control, other than that necessary to
ensure the Onshore Generating Unit is operating within its design limits.
CC.A.7.1 Scope
CC.A.7.1.1 This Appendix sets out the performance requirements of continuously acting automatic voltage
control systems for Onshore Non-Synchronous Generating Units, Onshore DC
Converters, Onshore Power Park Modules and OTSDUW Plant and Apparatus at the
Interface Point that must be complied with by the GB Code User. This Appendix does not
limit any site specific requirements that may be included in a Bilateral Agreement where in
The Company's reasonable opinion these facilities are necessary for system reasons.
CC.A.7.1.2 Proposals by GB Generators to make a change to the voltage control systems are required
to be notified to The Company under the Planning Code (PC.A.1.2(b) and (c)) as soon as
the GB Generator anticipates making the change. The change may require a revision to the
Bilateral Agreement.
CC.A.7.2 Requirements
CC.A.7.2.1 The Company requires that the continuously acting automatic voltage control system for the
Onshore Non-Synchronous Generating Unit, Onshore DC Converter or Onshore Power
Park Module or OTSDUW Plant and Apparatus shall meet the following functional
performance specification. If a Network Operator has confirmed to The Company that its
network to which an Embedded Onshore Non-Synchronous Generating Unit, Onshore
DC Converter, Onshore Power Park Module or OTSDUW Plant and Apparatus is
connected is restricted such that the full reactive range under the steady state voltage control
requirements (CC.A.7.2.2) cannot be utilised, The Company may specify in the Bilateral
Agreement alternative limits to the steady state voltage control range that reflect these
restrictions. Where the Network Operator subsequently notifies The Company that such
restriction has been removed, The Company may propose a Modification to the Bilateral
Agreement (in accordance with the CUSC contract) to remove the alternative limits such that
the continuously acting automatic voltage control system meets the following functional
performance specification. All other requirements of the voltage control system will remain as
in this Appendix.
CC.A.7.2.2 Steady State Voltage Control
CC.A.7.2.2.1 The Onshore Non-Synchronous Generating Unit, Onshore DC Converter, Onshore
Power Park Module or OTSDUW Plant and Apparatus shall provide continuous steady state
control of the voltage at the Onshore Grid Entry Point (or Onshore User System Entry
Point if Embedded) (or the Interface Point in the case of OTSDUW Plant and Apparatus)
with a Setpoint Voltage and Slope characteristic as illustrated in Figure CC.A.7.2.2a. It
should be noted that where the Reactive Power capability requirement of a directly connected
Onshore Non-Synchronous Generating Unit, Onshore DC Converter, Onshore Power
Park Module in Scotland, or OTSDUW Plant and Apparatus in Scotland as specified in
CC.6.3.2 (c), is not at the Onshore Grid Entry Point or Interface Point, the values of Qmin
and Qmax shown in this figure will be as modified by the 33/132kV or 33/275kV or 33/400kV
transformer.
CC.A.7.2.2.2 The continuously acting automatic control system shall be capable of operating to a Setpoint
Voltage between 95% and 105% with a resolution of 0.25% of the nominal voltage. For the
avoidance of doubt, values of 95%, 95.25%, 95.5% … may be specified, but not intermediate
values. The initial Setpoint Voltage will be 100%. The tolerance within which this Setpoint
Voltage shall be achieved is specified in BC2.A.2.6. For the avoidance of doubt, with a
tolerance of 0.25% and a Setpoint Voltage of 100%, the achieved value shall be between
99.75% and 100.25%. The Company may request the GB Generator to implement an
alternative Setpoint Voltage within the range of 95% to 105%. For Embedded GB
Generators the Setpoint Voltage will be discussed between The Company and the relevant
Network Operator and will be specified to ensure consistency with CC.6.3.4.
CC.A.7.2.2.3 The Slope characteristic of the continuously acting automatic control system shall be
adjustable over the range 2% to 7% (with a resolution of 0.5%). For the avoidance of doubt
values of 2%, 2.5%, 3% may be specified, but not intermediate values. The initial Slope setting
will be 4%. The tolerance within which this Slope shall be achieved is specified in BC2.A.2.6.
For the avoidance of doubt, with a tolerance of 0.5% and a Slope setting of 4%, the achieved
value shall be between 3.5% and 4.5%. The Company may request the GB Generator to
implement an alternative slope setting within the range of 2% to 7%. For Embedded GB
Generators the Slope setting will be discussed between The Company and the relevant
Network Operator and will be specified to ensure consistency with CC.6.3.4.
Figure CC.A.7.2.2c
(iii) the magnitude of the Reactive Power output response produced within 1 second shall
vary linearly in proportion to the magnitude of the step change.
(iv) within 2 seconds from achieving 90% of the response as defined in CC.A.7.2.3.1 (ii), the
peak to peak magnitude of any oscillations shall be less than 5% of the change in steady
state Reactive Power.
(v) following the transient response, the conditions of CC.A.7.2.2 apply.
MVArs
Required response at 1
second
0.2 1 Seconds
Figure CC.A.7.2.3.1a
(a) changing its Reactive Power output from its maximum lagging value to its maximum
leading value, or vice versa, then reverting back to the initial level of Reactive Power
output once every 15 seconds for at least 5 times within any 5 minute period; and
(b) changing its Reactive Power output from zero to its maximum leading value then
reverting back to zero Reactive Power output at least 25 times within any 24 hour
period and from zero to its maximum lagging value then reverting back to zero
Reactive Power output at least 25 times within any 24 hour period. Any subsequent
restriction on reactive capability shall be notified to The Company in accordance with
BC2.5.3.2, and BC2.6.1.
In all cases, the response shall be in accordance to CC.A.7.2.3.1 where the change in
Reactive Power output is in response to an on-load step change in Onshore Grid Entry
Point or Onshore User System Entry Point voltage, or in the case of OTSDUW Plant and
Apparatus an on-load step change in Transmission Interface Point voltage.
CONTENTS
(This contents page does not form part of the Grid Code)
(b) the minimum technical, design and operational criteria with which The Company will
comply in relation to the part of the National Electricity Transmission System at the
Connection Site with Users. In the case of any OTSDUW Plant and Apparatus, the
ECC also specify the minimum technical, design and operational criteria which must be
complied with by the User when undertaking OTSDUW.
(c ) The requirements of Retained EU Law (Commission Regulation (EU) 2016/631) shall
not apply to
(i) Power Generating Modules that are installed to provide backup power and
operate in parallel with the Total System for less than 5 minutes per calendar
month while the System is in normal state. Parallel operation during
maintenance or commissioning of tests of that Power Generating Module shall
not count towards that five minute limit.
(ii) Power Generating Modules connected to the Transmission System or
Network Operators System which are not operated in synchronism with a
Synchronous Area.
(iii) Power Generating Modules that do not have a permanent Connection Point
or User System Entry Point and used by The Company to temporarily provide
power when normal System capacity is partly or completely unavailable.
(iv) Electricity Storage Modules.
(d) Storage Users are required to comply with the entirety of the ECC but are not subject
to the requirements of Retained EU Law (Commission Regulation (EU) 2016/631,
Commission Regulation (EU) 2016/1388 and Commission Regulation (EU) 2016/1485).
The requirements of the ECC shall therefore be enforceable against Storage Users
under the Grid Code only (and not under any of the aforementioned Retained EU Law)
and any derogation sought by a Storage User in respect of the ECC shall be deemed
a derogation from the Grid Code only (and not from the aforementioned Retained EU
Law).
ECC.3 SCOPE
ECC.3.1 The ECC applies to The Company and to Users, which in the ECC means:
(a) EU Generators (other than those which only have Embedded Small Power Stations),
including those undertaking OTSDUW including Power Generating Modules, and DC
Connected Power Park Modules. For the avoidance of doubt, Electricity Storage
Modules are included within the definition of Power Generating Modules for which the
requirements of the ECC would be equally applicable.
(b) Network Operators but only in respect of:-
(i) Network Operators who are EU Code Users
(ii) Network Operators who only have EU Grid Supply Points
(iii) Embedded Medium Power Stations not subject to a Bilateral Agreement as
provided for in ECC.3.2, ECC.3.3, EC3.4, EC3.5, ECC5.1, ECC.6.4.4 and
ECA.3.4;
(iv) Notwithstanding the requirements of ECC3.1(b)(i)(ii) and (iii), Network
Operators who own and/or operate EU Grid Supply Points, are only required
to satisfy the requirements of this ECC in relation to each EU Grid Supply Point.
Network Operators in respect of all other Grid Supply Points should continue
to satisfy the requirements as specified in the CCs.
(c) Non-Embedded Customers who are also EU Code Users;
(d) HVDC System Owners who are also EU Code Users;
(e) BM Participants and Externally Interconnected System Operators who are also EU
Code Users in respect of ECC.6.5, ECC.7.9, ECC.7.10 and ECC.7.11 only; and.
ECC.3.2 The above categories of User will become bound by the applicable sections of the ECC prior
to them generating, distributing, storing, supplying or consuming, as the case may be, and
references to the various categories should, therefore, be taken as referring to them in that
prospective role.
ECC.3.3 Embedded Medium Power Stations not subject to a Bilateral Agreement and Embedded
HVDC Systems not subject to a Bilateral Agreement Provisions.
The following provisions apply in respect of Embedded Medium Power Stations not subject
to a Bilateral Agreement and Embedded HVDC Systems not subject to a Bilateral
Agreement.
ECC.3.3.1 The obligations within the ECC that are expressed to be applicable to EU Generators in
respect of Embedded Medium Power Stations not subject to a Bilateral Agreement and
HVDC System Owners in respect of Embedded HVDC Systems not subject to a Bilateral
Agreement (where the obligations are in each case listed in ECC.3.3.2) shall be read and
construed as obligations that the Network Operator within whose System any such Medium
Power Station or HVDC System is Embedded must ensure are performed and discharged
by the EU Generator or the HVDC Owner. Embedded Medium Power Stations not subject
to a Bilateral Agreement and Embedded HVDC Systems not subject to a Bilateral
Agreement which are located Offshore and which are connected to an Onshore User
System will be required to meet the applicable requirements of the Grid Code as though they
are an Onshore Generator or Onshore HVDC System Owner connected to an Onshore
User System Entry Point.
ECC.3.3.2 The Network Operator within whose System a Medium Power Station not subject to a
Bilateral Agreement is Embedded or a HVDC System not subject to a Bilateral Agreement
is Embedded must ensure that the following obligations in the ECC are performed and
discharged by the EU Generator in respect of each such Embedded Medium Power Station
or the HVDC System Owner in the case of an Embedded HVDC System:
ECC.5.1
ECC.5.2.2
ECC.5.3
ECC.6.1.3
ECC.6.1.5 (b)
ECC.6.3.2, ECC.6.3.3, ECC.6.3.4, ECC.6.3.6, ECC.6.3.7, ECC.6.3.8, ECC.6.3.9,
ECC.6.3.10, ECC.6.3.12, ECC.6.3.13, ECC.6.3.15, ECC.6.3.16
ECC.6.4.4
ECC.6.5.6 (where required by ECC.6.4.4)
that would otherwise have been specified in a Bilateral Agreement will be notified to the
relevant Network Operator in writing in accordance with the provisions of the CUSC and the
Network Operator must ensure such requirements are performed and discharged by the
Generator or the HVDC System owner.
ECC.3.4 In the case of Offshore Embedded Power Generating Modules connected to an Offshore
User’s System which directly connects to an Offshore Transmission System, any
additional requirements in respect of such Offshore Embedded Power Generating Modules
may be specified in the relevant Bilateral Agreement with the Network Operator or in any
Bilateral Agreement between The Company and such Offshore Generator.
ECC.3.5 In the case of a Generator undertaking OTSDUW connecting to an Onshore Network
Operator’s System, any additional requirements in respect of such OTSDUW Plant and
Apparatus will be specified in the relevant Bilateral Agreement with the EU Generator. For
the avoidance of doubt, requirements applicable to EU Generators undertaking OTSDUW
and connecting to a Network Operator’s User System, shall be consistent with those
applicable requirements of Generators undertaking OTSDUW and connecting to a
Transmission Interface Point.
ECC.3.6 The requirements of this ECC shall apply to EU Code Users in respect of Power
Generating Modules (including DC Connected Power Park Modules and Electricity
Storage Modules) and HVDC Systems.
ECC.4 PROCEDURE
ECC.4.1 The CUSC contains certain provisions relating to the procedure for connection to the National
Electricity Transmission System or, in the case of Embedded Power Stations or
Embedded HVDC Systems, becoming operational and includes provisions relating to certain
conditions to be complied with by EU Code Users prior to and during the course of The
Company notifying the User that it has the right to become operational. The procedure for an
EU Code User to become connected is set out in the Compliance Processes.
ECC.5 CONNECTION
ECC.5.1 The provisions relating to connecting to the National Electricity Transmission System (or
to a User's System in the case of a connection of an Embedded Large Power Station or
Embedded Medium Power Stations or Embedded HVDC System) are contained in:
(a) the CUSC and/or CUSC Contract (or in the relevant application form or offer for a CUSC
Contract);
(b) or, in the case of an Embedded Development, the relevant Distribution Code and/or
the Embedded Development Agreement for the connection (or in the relevant
application form or offer for an Embedded Development Agreement),
ECC.6.1.2.1.3 For the avoidance of doubt, disconnection, by frequency or speed based relays is not
permitted within the frequency range 47.5Hz to 51.5Hz. EU Generators should however be
aware of the combined voltage and frequency operating ranges as defined in ECC.6.3.12 and
ECC.6.3.13.
ECC.6.1.2.1.4 The Company in co-ordination with the Relevant Transmission Licensee and/or Network
Operator and a User may agree on wider variations in frequency or longer minimum operating
times to those set out in ECC.6.1.2.1.2 or specific requirements for combined frequency and
voltage deviations, for example but not limited to, situations such as during System
Restoration. Any such requirements in relation to Power Generating Modules shall be in
accordance with ECC.6.3.12 and ECC.6.3.13. A User shall not unreasonably withhold
consent to apply wider frequency ranges or longer minimum times for operation taking account
of their economic and technical feasibility.
ECC.6.1.2.2 Grid Frequency variations for HVDC Systems and Remote End HVDC Converter Stations
ECC.6.1.2.2.1 HVDC Systems and Remote End HVDC Converter Stations shall be capable of staying
connected to the System and remaining operable within the frequency ranges and time
periods specified in Table ECC.6.1.2.2 below. This requirement shall continue to apply during
the Fault Ride Through conditions defined in ECC.6.3.15
Table ECC.6.1.2.2 – Minimum time periods HVDC Systems and Remote End HVDC Converter Stations
shall be able to operate for different frequencies deviating from a nominal value without
disconnecting from the National Electricity Transmission System
ECC.6.1.2.2.2 The Company in coordination with the Relevant Transmission Licensee and a HVDC
System Owner may agree wider frequency ranges or longer minimum operating times if
required to preserve or restore system security, for example but not limited to, situations such
as during System Restoration. If wider frequency ranges or longer minimum times for
operation are economically and technically feasible, the HVDC System Owner shall not
unreasonably withhold consent.
ECC.6.1.2.2.3 Not withstanding the requirements of ECC.6.1.2.2.1, an HVDC System or Remote End HVDC
Converter Station shall be capable of automatic disconnection at frequencies specified by
The Company and/or Relevant Network Operator.
ECC.6.1.2.2.4 In the case of Remote End HVDC Converter Stations where the Remote End HVDC
Converter Station is operating at either nominal frequency other than 50Hz or a variable
frequency, the requirements defined in ECC6.1.2.2.1 to ECC.6.1.2.2.3 shall apply to the
Remote End HVDC Converter Station other than in respect of the frequency ranges and
time periods.
ECC.6.1.2.3 Grid Frequency Variations for DC Connected Power Park Modules
ECC.6.1.2.3.1 DC Connected Power Park Modules shall be capable of staying connected to the Remote
End DC Converter network at the HVDC Interface Point and operating within the Frequency
ranges and time periods specified in Table ECC.6.1.2.3 below. Where a nominal frequency
other than 50Hz, or a Frequency variable by design is used as agreed with The Company
and the Relevant Transmission Licensee the applicable Frequency ranges and time
periods shall be specified in the Bilateral Agreement which shall (where applicable) reflect
the requirements in Table ECC.6.1.2.3 .
Table ECC.6.1.2.3 – Minimum time periods a DC Connected Power Park Module shall be able to operate
for different frequencies deviating from a nominal value without disconnecting from the
System
ECC.6.1.2.3.2 The Company in coordination with the Relevant Transmission Licensee and a Generator
may agree wider frequency ranges or longer minimum operating times if required to preserve
or restore system security and to ensure the optimum capability of the DC Connected Power
Park Module, for example but not limited to, situations such as during System Restoration.
If wider frequency ranges or longer minimum times for operation are economically and
technically feasible, the EU Generator shall not unreasonably withhold consent.
ECC.6.1.3 Not used
ECC.6.1.4 Grid Voltage Variations
The Company and a User may agree greater variations or longer minimum time periods of
operation in voltage to those set out above in relation to a particular Connection Site, and
insofar as a greater variation is agreed, the relevant figure set out above shall, in relation to
that User at the particular Connection Site, be replaced by the figure agreed.
ECC.6.1.4.2 Grid Voltage Variations for all DC Connected Power Park Modules
ECC.6.1.4.2.1 All DC Connected Power Park Modules shall be capable of staying connected to the Remote
End HVDC Converter Station at the HVDC Interface Point and operating within the voltage
ranges and time periods specified in Tables ECC.6.1.4.2(a) and ECC.6.1.4.2(b) below. The
applicable voltage range and time periods specified are selected based on the reference 1pu
voltage.
Table ECC.6.1.4.2(b) – Minimum time periods for which DC Connected Power Park Modules shall be
capable of operating for different voltages deviating from reference 1pu without
disconnecting from the network where the nominal voltage base is from 300kV up to and
including 400kV.
ECC.6.1.4.2.2 The Company and a EU Generator in respect of a DC Connected Power Park Module may
agree greater voltage ranges or longer minimum operating times. If greater voltage ranges
or longer minimum times for operation are economically and technically feasible, the EU
Generator shall not unreasonably withhold any agreement .
ECC.6.1.4.2.3 For DC Connected Power Park Modules which have an HVDC Interface Point to the
Remote End HVDC Converter Station, The Company in coordination with the Relevant
Transmission Licensee may specify voltage limits at the HVDC Interface Point at which the
DC Connected Power Park Module is capable of automatic disconnection.
ECC.6.1.4.2.4 For HVDC Interface Points which fall outside the scope of ECC.6.1.4.2.1, ECC.6.1.4.2.2 and
ECC.6.1.4.2.3, The Company in coordination with the Relevant Transmission Licensee
shall specify any applicable requirements at the Grid Entry Point or User System Entry
Point.
ECC.6.1.4.2.5 Where the nominal frequency of the AC collector System which is connected to an HVDC
Interface Point is at a value other than 50Hz, the voltage ranges and time periods specified
by The Company in coordination with the Relevant Transmission Licensee shall be
proportional to the values specified in Table ECC.6.1.4.2(a) and Table ECC.6.1.4.2(b)
ECC.6.1.4.3 Grid Voltage Variations for all Remote End HVDC Converters
ECC.6.1.4.3.1 All Remote End HVDC Converter Stations shall be capable of staying connected to the
HVDC Interface Point and operating within the voltage ranges and time periods specified in
Tables ECC.6.1.4.3(a) and ECC.6.1.4.3(b) below. The applicable voltage range and time
periods specified are selected based on the reference 1pu voltage.
Table ECC.6.1.4.3(a) – Minimum time periods for which a Remote End HVDC Converter shall be capable
of operating for different voltages deviating from reference 1pu without disconnecting from
the network where the nominal voltage base is 110kV or above and less than 300kV.
Voltage Range (pu) Time Period for Operation (s)
0.85pu – 0.9pu 60 minutes
0.9pu – 1.05pu Unlimited
Table ECC.6.1.4.3(b) – Minimum time periods for which a Remote End HVDC Converter shall be capable
of operating for different voltages deviating from reference 1pu without disconnecting from
the network where the nominal voltage base is from 300kV up to and including 400kV.
ECC.6.1.4.3.2 The Company and a HVDC System Owner may agree greater voltage ranges or longer
minimum operating times which shall be in accordance with the requirements of ECC.6.1.4.2.
ECC.6.1.4.3.4 For HVDC Interface Points which fall outside the scope of ECC.6.1.4.3.1 The Company in
coordination with the Relevant Transmission Licensee shall specify any applicable
requirements at the Grid Entry Point or User System Entry Point.
ECC.6.1.4.3.5 Where the nominal frequency of the AC collector System which is connected to an HVDC
Interface Point is at a value other than 50Hz, the voltage ranges and time periods specified
by The Company in coordination with the Relevant Transmission Licensee shall be
proportional to the values specified in Table ECC.6.1.4.3(a) and Table ECC.6.1.4.3(b)
Voltage Waveform Quality
ECC.6.1.5 All Plant and Apparatus connected to the National Electricity Transmission System, and
that part of the National Electricity Transmission System at each Connection Site or, in
the case of OTSDUW Plant and Apparatus, at each Interface Point, should be capable of
withstanding the following distortions of the voltage waveform in respect of harmonic content
and phase unbalance:
(a) Harmonic Content
The Electromagnetic Compatibility Levels for harmonic distortion on the Onshore
Transmission System from all sources under both Planned Outage and fault outage
conditions, (unless abnormal conditions prevail) shall comply with Engineering
Recommendation G5. The Electromagnetic Compatibility Levels for harmonic
distortion on an Offshore Transmission System will be defined in relevant Bilateral
Agreements.
Engineering Recommendation G5 contains planning criteria which The Company will
apply to the connection of non-linear Load to the National Electricity Transmission
System, which may result in harmonic emission limits being specified for these Loads in
the relevant Bilateral Agreement. The application of the planning criteria will take into
account the position of existing GB Code User’s and EU Code Users’ Plant and
Apparatus (and OTSDUW Plant and Apparatus) in relation to harmonic emissions. EU
Code Users must ensure that connection of distorting loads to their User Systems do
not cause any harmonic emission limits specified in the Bilateral Agreement, or where
no such limits are specified, the relevant planning levels specified in Engineering
Recommendation G5 to be exceeded.
(b) Phase Unbalance
Under Planned Outage conditions, the weekly 95 percentile of Phase (Voltage)
Unbalance, calculated in accordance with IEC 61000-4-30 and IEC 61000-3-13, on the
National Electricity Transmission System for voltages above 150kV should remain, in
England and Wales, below 1.5%, and in Scotland, below 2%, and for voltages of 150kV
and below, across GB below 2%, unless abnormal conditions prevail and Offshore (or in
the case of OTSDUW, OTSDUW Plant and Apparatus) will be defined in relevant
Bilateral Agreements.
The Phase Unbalance is calculated from the ratio of root mean square (rms) of negative
phase sequence voltage to rms of positive phase sequence voltage, based on 10-minute
average values, in accordance with IEC 61000-4-30.
Voltage Fluctuations
ECC.6.1.7 Voltage changes at a Point of Common Coupling on the Onshore Transmission System
shall not exceed:
(a) The limits specified in Table ECC.6.1.7(a) with the stated frequency of occurrence, where:
(i)
Vsteadystate
%Vsteadystate = │100 x │ and
Vn
Vmax
%Vmax =100 x ;
Vn
(ii) Vn is the nominal system voltage;
(iii) Vsteadystate is the voltage at the end of a period of 1 s during which the rate of change
of system voltage over time is ≤ 0.5%;
(iv) Vsteadystate is the difference in voltage between the initial steady state voltage prior
to the RVC (V0) and the final steady state voltage after the RVC (V0’);
(v) Vmax is the absolute change in the system voltage relative to the initial steady state
system voltage (V0);
(vi) All voltages are the r.m.s. of the voltage measured over one cycle refreshed every
half a cycle as per BS EN 61000-4-30; and
(vii) The applications in the ‘Example Applicability’ column are examples only and are
not definitive.
NOTE 1: 6% is permissible for 100 ms reduced to 3% thereafter as per Figure ECC.6.1.7 (1) .
If the profile of repetitive voltage change(s) falls within the envelope given in Figure ECC.6.1.7 (1) , the
assessment of such voltage change(s) shall be undertaken according to the recommendations for
assessment of flicker and shall conform to the planning levels provided for flicker.
If any part of the voltage change(s) falls outside the envelope given in Figure ECC.6.1.7(1), the
assessment of such voltage changes, repetitive or not, shall be done according to the guidance and limits
for RVCs.
NOTE 2: No more than 1 event is permitted per day, consisting of up to 4 RVCs, each separated by at least 10
minutes with all switching completed within a two-hour window.
NOTE 3: −10% is permissible for 100 ms reduced to -6% until 2 s then reduced to -3% thereafter as per Figure
ECC.6.1.7 (2).
NOTE 4: +6% is permissible for 0.8 s from the instant the event begins then reduced to +3% thereafter as per Figure
ECC.6.1.7 (2).
NOTE 5: −12% is permissible for 100 ms reduced to −10% until 2 s then reduced to -3% thereafter as per Figure
ECC.6.1.7 (3).
NOTE 6: +6% is permissible for 0.8 s from the instant the event begins then reduced to +3% thereafter as per Figure
ECC.6.1.7 (3).
NOTE 7: These are examples only. Customers may opt to conform to the limits of another category providing the
frequency of occurrence is not expected to exceed the ‘Maximum number of occurrence’ for the chosen
category.
(b) The voltage change limit is the absolute maximum allowed of either the phase-to-earth
voltage change or the phase-to-phase voltage change, whichever is the highest. The limits
do not apply to single phasor equivalent voltages, e.g. positive phase sequence (PPS)
voltages. For high impedance earthed systems, the maximum phase-to-phase, i.e. line
voltage, should be used for assessment.
(c) The RVCs in Category 2 and 3 should not exceed the limits depicted in the time dependent
characteristic shown in Figure ECC.6.1.7 (2) and Figure ECC.6.1.7 (3) respectively.
These limits do not apply to: 1) fault clearance operations; or 2) immediate operations in
response to fault conditions; or 3) operations relating to post fault system restoration (for
the avoidance of doubt this third exception pertains to a fault that is external to the Users
plant and apparatus).
(d) Any RVCs permitted in Category 2 and Category 3 should be at least 10 minutes apart.
(e) The value of Vsteadystate should be established immediately prior to the start of a RVC.
Following a RVC, the voltage should remain within the relevant envelope, as shown in
Figures ECC.6.1.7 (1), ECC.6.1.7 (2), ECC.6.1.7 (3), until a Vsteadystate condition has been
satisfied.
V0+6%
V0+3%
V0
V0−3%
V0−6%
V0−10%
V0+6%
V0+3%
V0
V0−3%
V0−10%
V0−12%
Planning level
Supply system Flicker Severity Short Flicker Severity Long Term
Nominal voltage Term (Pst) (Plt)
Up to and including 33 kV 0.9 0.7
66kV and greater 0.8 0.6
NOTE 1: The magnitude of Pst is linear with respect to the magnitude of the voltage changes giving rise to it.
NOTE 2: Extreme caution is advised in allowing any excursions of Pst and Plt above the planning level.
The values and figures referred to in this paragraph ECC.6.1.7 are derived from Engineering
Recommendation P28 Issue 2.
ECC.6.1.8 Voltage fluctuations at a Point of Common Coupling with a fluctuating Load directly
connected to an Offshore Transmission System (or in the case of OTSDUW, OTSDUW
Plant and Apparatus) shall not exceed the limits set out in the Bilateral Agreement.
Any alternative Protection settings shall be included in the Restoration Plan. Normal and
alternative Protection settings shall be agreed between The Company and/or Relevant
Transmission Licensee and/or Network Operator as part of developing a Restoration Plan.
A Power Generating Module (other than a Power Park Unit), HVDC Equipment or
OTSDUW Plant and Apparatus) with Back-Up Protection or Independent Back-Up
Protection will also be required to withstand, without tripping, the loading incurred during
the clearance of a fault on the National Electricity Transmission System by breaker
fail Protection at a nominal voltage of greater than 132kV or of a fault cleared by Back-
Up Protection where the EU Generator (including in the case of OTSDUW Plant and
Apparatus or DC Connected Power Park Module) or HVDC System is connected at
132kV and below. This will permit Discrimination between the Generator in respect of
OTSDUW Plant and Apparatus or DC Connected Power Park Modules or HVDC
System Owners’ Back-Up Protection or Independent Back-Up Protection and the
Back-Up Protection provided on the National Electricity Transmission System and
other Users' Systems.
ECC.6.2.2.6.2 The parameters of different control modes of the HVDC System shall be able to be changed
in the HVDC Converter Station, if required by The Company in coordination with the
Relevant Transmission Licensee and in accordance with ECC.6.2.2.6.4.
ECC.6.2.2.6.3 Any change to the schemes or settings of parameters of the different control modes and
protection of the HVDC System including the procedure shall be agreed with The Company
in coordination with the Relevant Transmission Licensee and the HVDC System Owner.
ECC.6.2.2.6.4 The control modes and associated set points shall be capable of being changed remotely, as
specified by The Company in coordination with the Relevant Transmission Licensee.
ECC.6.2.2.7 Control Schemes and Settings
ECC.6.2.2.9 Synchronising
ECC.6.2.2.9.1 For any Power Generating Module directly connected to the National Electricity
Transmission System or Type D Power Generating Module, synchronisation shall be
performed by the EU Generator only after instruction by The Company in accordance with
the requirements of BC.2.5.2.
ECC.6.2.2.9.2 Each Power Generating Module directly connected to the National Electricity
Transmission System or Type D Power Generating Module shall be equipped with the
necessary synchronisation facilities. Synchronisation shall be possible within the range of
frequencies specified in ECC.6.1.2.
ECC.6.2.3 Requirements at EU Grid Supply Points relating to Network Operators and Non-Embedded
Customers
ECC.6.2.3.1 Protection Arrangements for EU Code Users in respect of Network Operators and Non-
Embedded Customers
ECC.6.2.3.1.1 Protection arrangements for EU Code Users in respect of Network Operators and Non-
Embedded Customers User Systems directly connected to the National Electricity
Transmission System, shall meet the requirements given below:
Fault Clearance Times
(a) The required fault clearance time for faults on Network Operator and Non-Embedded
Customer equipment directly connected to the National Electricity Transmission
System, and for faults on the National Electricity Transmission System directly
connected to the Network Operator’s or Non-Embedded Customer's equipment, from
fault inception to the circuit breaker arc extinction, shall be set out in each Bilateral
Agreement. The fault clearance time specified in the Bilateral Agreement shall not be
shorter than the durations specified in (i), (ii) and (iii) below:
(i) 80ms for connections operating at a nominal voltage of greater than 300kV
(ii) 100ms for connections operating at a nominal voltage of greater than 132kV and up
to 300kV
(iii) 120ms for connections operating at a nominal voltage of greater than 132kV and
below
but this shall not prevent the User or The Company or Relevant Transmission
Licensee from selecting a shorter fault clearance time on its own Plant and Apparatus
provided Discrimination is achieved.
For the purpose of establishing the Protection requirements in accordance with
ECC.6.2.3.1.1 only, the point of connection of the Network Operator or Non-Embedded
Customer equipment to the National Electricity Transmission System shall be
deemed to be the low voltage busbars at an EU Grid Supply Point, irrespective of the
ownership of the equipment at the EU Grid Supply Point.
Any alterations to the busbar protection settings at the EU Grid Supply Point (whether by
The Company, the Relevant Transmission Licensee, the Network Operator or the Non
Embedded Customer) shall be agreed between The Company (in co-ordination with the
Relevant Transmission Licensee) and the Network Operator or Non Embedded
Customer in accordance with the Grid Code (ECC.6.2.3.4). No alterations are to be made to
Issue 6 Revision 21 ECC 04 March 2024
28 of 147
any busbar protection schemes unless agreement has been reached between The Company,
the Relevant Transmission Licensee, the Network Operator or Non Embedded
Customer.
a) From the normal to the alternative Protection settings on their Plant and Apparatus;
and:-
b) From the alternative to the normal Protection settings whilst their Plant remains in
service,
Any alternative Protection settings shall be included in the Restoration Plan. Normal and
alternative Protection settings shall be agreed between The Company and the Network
Operator as part of developing a Restoration Plan.
ECC.6.2.3.8.2 Subject to the requirements of ECC.6.2.3.8.1, any changes to the schemes and settings,
defined in ECC.6.2.3.8.1 of the different control devices of the Network Operator’s or Non-
Embedded Customer’s System at the EU Grid Supply Point shall be coordinated and
agreed between The Company, the Relevant Transmission Licensee, the Network
Operator or Non Embedded Customer. Network Operators shall have the ability to switch
between alternative control settings on their Plant and Apparatus if they are required to do
so to be able to satisfy their obligations of a Restoration Plan. Any alternative control settings
shall be included in the Restoration Plan.
ECC.6.2.3.9 Ranking of Protection and Control
ECC.6.2.3.9.1 The Network Operator or the Non Embedded Customer who owns or operates an EU Grid
Supply Point shall set the Protection and control devices of its System, in compliance with
the following priority ranking, organised in decreasing order of importance:
(a) National Electricity Transmission System Protection;
(b) Protection equipment at each EU Grid Supply Point;
(c) Frequency control (Active Power adjustment);
Figure ECC.6.3.2.3
ECC.6.3.2.3.4 In addition, to the requirements of ECC.6.3.2.3.1 – ECC.6.3.2.3.3 the short circuit ratio of
all Onshore Synchronous Generating Units with an Apparent Power rating of less than
1600MVA shall not be less than 0.5. The short circuit ratio of Onshore Synchronous
Generating Units with a rated Apparent Power of 1600MVA or above shall be not less
than 0.4.
ECC.6.3.2.4 Reactive Capability for Type C and D Power Park Modules, HVDC Equipment and
OTSDUW Plant and Apparatus at the Interface Point
ECC.6.3.2.4.1 EU Generators or HVDC System Owners which connect an Onshore Type C or
Onshore Type D Power Park Module or HVDC Equipment to a Non Embedded
Customers System or private network, may be required to meet additional reactive
compensation requirements at the point of connection between the System and the Non
Embedded Customer or private network where this is required for System reasons.
Figure ECC.6.3.2.4(a)
ECC.6.3.2.4.3 All Onshore Type C or Type D Power Park Modules or HVDC Converters at a HVDC
Converter Station with a Grid Entry Point or User System Entry Point voltage at or
below 33kV or Remote End HVDC Converter Station with an HVDC Interface Point
Voltage at or below 33kV shall be capable of satisfying the Reactive Power capability
requirements at the Grid Entry Point or User System Entry Point as defined in Figure
ECC.6.3.2.4(b) when operating at Maximum Capacity. In the case of Remote End HVDC
Converters The Company in co-ordination with the Relevant Transmission Licensee
may agree to alternative reactive capability requirements to those specified in Figure
ECC.6.3.2.4(b), where it is demonstrated that it is uneconomic and inefficient to do so, for
example in the case of new technologies or advanced control strategies. For the avoidance
of doubt, the requirements for Offshore Power Park Modules and DC Connected Power
Park Modules are defined in ECC.6.3.2.5 and ECC.6.3.2.6.
ECC.6.3.2.6.2 All AC Connected Configuration 2 Offshore Power Park Modules and Configuration
2 DC Connected Power Park Modules shall be capable of satisfying the Reactive Power
capability requirements at the Offshore Grid Entry Point as defined in Figure
ECC.6.3.2.6(b) when operating below Maximum Capacity. With all Plant in service, the
Reactive Power limits will reduce linearly below 50% Active Power output as shown in
Figure ECC.6.3.2.6(b) unless the requirement to maintain the Reactive Power limits
defined at Maximum Capacity (or Interface Point Capacity in the case of OTSDUW Plant
and Apparatus) under absorbing Reactive Power conditions down to 20% Active Power
output has been specified with The Company. These Reactive Power limits will be
reduced pro rata to the amount of Plant in service. The Company in co-ordination with the
Relevant Transmission Licensee may agree to alternative reactive capability
requirements to those specified in Figure ECC.6.3.2.6(b), where it is demonstrated that it
is uneconomic and inefficient to do so, for example in the case of new technologies or
advanced control strategies.
(c) For the avoidance of doubt, in the case of a Power Generating Module including a DC
Connected Power Park Module using an Intermittent Power Source where the
mechanical power input will not be constant over time, the requirement is that the Active
Power output shall be independent of System Frequency under (a) above and should
not drop with System Frequency by greater than the amount specified in (b) above.
(d) An HVDC System must be capable of maintaining its Active Power input (i.e. when
operating in a mode analogous to Demand) from the National Electricity Transmission
System (or User System in the case of an Embedded HVDC System) at a level not
greater than the figure determined by the linear relationship shown in Figure ECC.6.3.3(b)
for System Frequency changes within the range 49.5 to 47 Hz, such that if the System
Frequency drops to 47.8 Hz the Active Power input decreases by more than 60%.
100% of Active
Power Input
40% of Active
Power Input
ECC.6.3.6.1.2 Active Power control in respect of HVDC Systems and Remote End HVDC Converter
Stations
ECC.6.3.6.1.2.1 HVDC Systems shall be capable of adjusting the transmitted Active Power upon receipt of
an instruction from The Company which shall be in accordance with the requirements of
BC2.6.1.
ECC.6.3.6.1.2.2 The requirements for fast Active Power reversal (if required) shall be specified by The
Company. Where Active Power reversal is specified in the Bilateral Agreement, each
HVDC System and Remote End HVDC Converter Station shall be capable of operating
from maximum import to maximum export in a time which is as fast as technically feasible or
in a time that is no greater than 2 seconds except where a HVDC Converter Station Owner
has justified to The Company that a longer reversal time is required.
ECC.6.3.6.1.2.3 Where an HVDC System connects various Control Areas or Synchronous Areas, each
HVDC System or Remote End HVDC Converter Station shall be capable of responding to
instructions issued by The Company under the Balancing Code to modify the transmitted
Active Power for the purposes of cross-border balancing.
ECC.6.3.6.1.2.4 An HVDC System shall be capable of adjusting the ramping rate of Active Power variations
within its technical capabilities in accordance with instructions issued by The Company . In
case of modification of Active Power according to ECC.6.3.15 and ECC.6.3.6.1.2.2, there
shall be no adjustment of ramping rate.
ECC.6.3.6.1.2.5 If specified by The Company, in coordination with the Relevant Transmission Licensees,
the control functions of an HVDC System shall be capable of taking automatic remedial
actions including, but not limited to, stopping the ramping and blocking FSM, LFSM-O, LFSM-
U and Frequency control. The triggering and blocking criteria shall be specified by The
Company.
ECC.6.3.7.1.3 Each Power Generating Module (including DC Connected Power Park Modules) or HVDC
Systems which is providing Limited High Frequency Response (LFSM-O) must continue to
provide it until the Frequency has returned to or below 50.4Hz or until otherwise instructed by
The Company. EU Generators in respect of Gensets and HVDC Converter Station
Owners in respect of an HVDC System should also be aware of the requirements in
BC.3.7.2.2.
ECC.6.3.7.1.4 Steady state operation below the Minimum Stable Operating Level in the case of Power
Generating Modules including DC Connected Power Park Modules or Minimum Active
Power Transmission Capacity in the case of HVDC Systems is not expected but if System
operating conditions cause operation below the Minimum Stable Operating Level or
Minimum Active Power Transmission Capacity which could give rise to operational
difficulties for the Power Generating Module including a DC Connected Power Park Module
or HVDC Systems then the EU Generator or HVDC System Owner shall be able to return
the output of the Power Generating Module including a DC Connected Power Park Module
to an output of not less than the Minimum Stable Operating Level or HVDC System to an
output of not less than the Minimum Active Power Transmission Capacity.
ECC.6.3.7.1.5 All reasonable efforts should in the event be made by the EU Generator or HVDC System
Owner to avoid such tripping provided that the System Frequency is below 52Hz in
accordance with the requirements of ECC.6.1.2. If the System Frequency is at or above
52Hz, the requirement to make all reasonable efforts to avoid tripping does not apply and the
EU Generator or HVDC System Owner is required to take action to protect its Power
Generating Modules including DC Connected Power Park Modules or HVDC Converter
Stations.
(iii) The actual delivery of Active Power Frequency Response in LFSM-U mode shall take
into account
(iv) In LFSM_U Mode, the Power Generating Module (including DC Connected Power
Park Modules) and HVDC Systems, shall be capable of providing a power increase
up to its Maximum Capacity or Maximum HVDC Active Power Transmission
Capacity (as applicable).
ECC.6.3.7.2.3.3 Where an Electricity Storage Module is exporting Active Power to the Total System
(including zero) and the System Frequency falls below 49.5Hz the requirements of
ECC.6.3.7.2.1 and ECC.6.3.7.2.2 shall apply.
ECC.6.3.7.3.4 HVDC Systems shall also meet the following minimum requirements:
(i) HVDC Systems shall be capable of responding to Frequency deviations in each
connected AC System by adjusting their Active Power import or export as shown in
Figure 6.3.7.3.4(a) with the corresponding parameters in Table 6.3.7.3.4(a).
Parameter Setting
Active Power as a percentage of 10%
Maximum Capacity (frequency
ǀ𝜟𝑷𝟏 ǀ
response range) ( )
𝑷𝒎𝒂𝒙
In the case of an Electricity Storage Module, an allowance will be made for the storage
reserve capability of the Electricity Storage Module.
ECC.6.3.13.3 Each HVDC System and Remote End HVDC Converter Station when connected and
synchronised to the System, shall be capable of withstanding without tripping a rate of change
of Frequency up to and including ±2.5Hz per second as measured over the previous 1 second
period. Voltage dips may cause localised rate of change of Frequency values in excess of
±2.5 Hz per second for short periods, and in these cases, the requirements under ECC.6.3.15
(fault ride through) supersedes this clause. For the avoidance of doubt, this requirement
relates to the capabilities of HVDC Systems and Remote End HVDC Converter Stations
only and does not impose the need for rate of change of Frequency protection nor does it
impose a specific setting for anti-islanding or loss-of-mains protection relays.
ECC.6.3.13.4 Each DC Connected Power Park Module when connected to the System, shall be capable
of withstanding without tripping a rate of change of Frequency up to and including ±2.0Hz per
second as measured over the previous 1 second period. Voltage dips may cause localised
rate of change of Frequency values in excess of ±2.0 Hz per second for short periods, and in
these cases, the requirements under ECC.6.3.15 (fault ride through) supersedes this clause.
For the avoidance of doubt, this requirement relates to the capabilities of DC Connected
Power Park Modules only and does not impose the need for rate of change of Frequency
protection nor does it impose a specific setting for anti-islanding or loss-of-mains protection
relays.
Issue 6 Revision 21 ECC 04 March 2024
58 of 147
ECC.6.3.13.5 As stated in ECC.6.1.2, the System Frequency could rise to 52Hz or fall to 47Hz and the
System voltage at the Grid Entry Point or User System Entry Point could rise or fall within
the values outlined in ECC.6.1.4. Each Type C and Type D Power Generating Module
(including DC Connected Power Park Modules) or any constituent element must continue to
operate within this Frequency range for at least the periods of time given in ECC.6.1.2 and
voltage range as defined in ECC.6.1.4 unless The Company has agreed to any simultaneous
overvoltage and underfrequency relays and/or simultaneous undervoltage and over frequency
relays which will trip such Power Generating Module (including DC Connected Power Park
Modules), and any constituent element within this Frequency or voltage range. In the case
of Grid Forming Plant, Grid Forming Plant Owners are also required to satisfy the System
Frequency and System voltage requirements as defined in ECC.6.3.19.
ECC.6.3.14.1 It may be agreed in the Bilateral Agreement that a Genset shall have a Fast-Start
Capability. Such Gensets may be used for Operating Reserve and their Start-Up may be
initiated by Frequency-level relays with settings in the range 49Hz to 50Hz as specified
pursuant to OC2.
ECC.6.3.15.1 General Fault Ride Through requirements, principles and concepts applicable to Type B,
Type C and Type D Power Generating Modules and OTSDUW Plant and Apparatus
subject to faults up to 140ms in duration
ECC.6.3.15.1.1 ECC.6.3.15.1 – ECC.6.3.15.8 section sets out the Fault Ride Through requirements on
Type B, Type C and Type D Power Generating Modules, OTSDUW Plant and
Apparatus and HVDC Equipment that shall apply in the event of a fault lasting up to
140ms in duration.
ECC.6.3.15.1.2 Each Power Generating Module, Power Park Module, HVDC Equipment and OTSDUW
Plant and Apparatus is required to remain connected and stable for any balanced and
unbalanced fault where the voltage at the Grid Entry Point or User System Entry Point
or (HVDC Interface Point in the case of Remote End DC Converter Stations or
Interface Point in the case of OTSDUW Plant and Apparatus) remains on or above the
heavy black line defined in sections ECC.6.3.15.2 – ECC.6.3.15.7 below. For up to 30
minutes following such a fault event each Power Generating Module, Power Park
Module, HVDC Equipment and OTSDUW Plant and Apparatus is required to remain
connected and stable provided System operating conditions have returned within those
specified in ECC.6.1.
ECC.6.3.15.1.3 The voltage against time curves defined in ECC.6.3.15.2 – ECC.6.3.15.7 expresses the
lower limit (expressed as the ratio of its actual value and its reference 1pu) of the actual
course of the phase to phase voltage (or phase to earth voltage in the case of
asymmetrical/unbalanced faults) on the System voltage level at the Grid Entry Point or
User System Entry Point (or HVDC Interface Point in the case of Remote End HVDC
Converter Stations or Interface Point in the case of OTSDUW Plant and Apparatus)
during a symmetrical or asymmetrical/unbalanced fault, as a function of time before, during
and after the fault.
ECC.6.3.15.2 Voltage against time curve and parameters applicable to Type B Synchronous Power
Generating Modules
ECC.6.3.15.3 Voltage against time curve and parameters applicable to Type C and D Synchronous
Power Generating Modules connected below 110kV
Figure ECC.6.3.15.3 - Voltage against time curve applicable to Type C and D Synchronous
Power Generating Modules connected below 110kV
ECC.6.3.15.4 Voltage against time curve and parameters applicable to Type D Synchronous Power
Generating Modules connected at or above 110kV
ECC.6.3.15.5 Voltage against time curve and parameters applicable to Type B, C and D Power Park
Modules connected below 110kV
Figure ECC.6.3.15.5 - Voltage against time curve applicable to Type B, C and D Power
Park Modules connected below 110kV
ECC.6.3.15.6 Voltage against time curve and parameters applicable to Type D Power Park Modules with
a Grid Entry Point or User System Entry Point at or above 110kV, DC Connected Power
Park Modules at the HVDC Interface Point or OTSDUW Plant and Apparatus at the
Interface Point.
Figure ECC.6.3.15.6 - Voltage against time curve applicable to Type D Power Park Modules with a Grid
Entry Point or User System Entry Point at or above 110kV, DC Connected Power Park
Modules at the HVDC Interface Point or OTSDUW Plant and Apparatus at the Interface
Point.
Table ECC.6.3.15.6 Voltage against time parameters applicable to a Type D Power Park Modules with a
Grid Entry Point or User System Entry Point at or above 110kV, DC Connected Power
Park Modules at the HVDC Interface Point or OTSDUW Plant and Apparatus at the
Interface Point.
ECC.6.3.15.7 Voltage against time curve and parameters applicable to HVDC Systems and Remote End
HVDC Converter Stations
Table ECC.6.3.15.7 Voltage against time parameters applicable to HVDC Systems and Remote End HVDC
Converter Stations
(vii) Each Type B, Type C and Type D Power Generating Module, HVDC System and
OTSDUW Plant and Apparatus at the Interface Point shall be designed such that
upon clearance of the fault on the Onshore Transmission System and within 0.5
seconds of restoration of the voltage at the Grid Entry Point or User System Entry
Point or HVDC Interface Point in the case of a Remote End HVDC Converter
Stations or Interface Point in the case of OTSDUW Plant and Apparatus to 90% of
nominal voltage or greater, Active Power output (or Active Power transfer capability
in the case of OTSDW Plant and Apparatus or Remote End HVDC Converter
Stations) shall be restored to at least 90% of the level immediately before the fault.
Once Active Power output (or Active Power transfer capability in the case of
OTSDUW Plant and Apparatus or Remote End HVDC Converter Stations) has
been restored to the required level, Active Power oscillations shall be acceptable
provided that:
- The total Active Energy delivered during the period of the oscillations is at least
that which would have been delivered if the Active Power was constant
- The oscillations are adequately damped.
- In the event of power oscillations, Power Generating Modules shall retain
steady state stability when operating at any point on the Power Generating
Module Performance Chart.
For AC Connected Onshore and Offshore Power Park Modules comprising
switched reactive compensation equipment (such as mechanically switched capacitors
and reactors), such switched reactive compensation equipment shall be controlled
such that it is not switched in or out of service during the fault but may act to assist in
post fault voltage recovery.
ECC.6.3.15.9 General Fault Ride Through requirements for faults in excess of 140ms in duration.
ECC.6.3.15.9.1 General Fault Ride Through requirements applicable to HVDC Equipment and OTSDUW
DC Converters subject to faults and voltage dips in excess of 140ms.
ECC.6.3.15.9.2 Fault Ride Through requirements for Type C and Type D Synchronous Power Generating
Modules and Type C and Type D Power Park Modules and OTSDUW Plant and Apparatus
subject to faults and voltage disturbances on the Onshore Transmission System in excess
of 140ms
(i) remain transiently stable and connected to the System without tripping of any
Synchronous Power Generating Module for balanced Supergrid Voltage dips
and associated durations on the Onshore Transmission System (which could be
at the Interface Point) anywhere on or above the heavy black line shown in Figure
ECC.6.3.15.9(a) Appendix 4 and Figures EA.4.3.2(a), (b) and (c) provide an
explanation and illustrations of Figure ECC.6.3.15.9(a); and,
Figure ECC.6.3.15.9(a)
(ii) provide Active Power output at the Grid Entry Point, during Supergrid Voltage
dips on the Onshore Transmission System as described in Figure
ECC.6.3.15.9(a), at least in proportion to the retained balanced voltage at the
Onshore Grid Entry Point (for Onshore Synchronous Power Generating
Modules) or Interface Point (for Offshore Synchronous Power Generating
Modules) (or the retained balanced voltage at the User System Entry Point if
Embedded) and shall generate maximum reactive current (where the voltage at the
Grid Entry Point is outside the limits specified in ECC.6.1.4) without exceeding the
transient rating limits of the Synchronous Power Generating Module and,
(iii) restore Active Power output following Supergrid Voltage dips on the Onshore
Transmission System as described in Figure ECC.6.3.15.9(a), within 1 second of
restoration of the voltage to 1.0pu of the nominal voltage at the:
to at least 90% of the level available immediately before the occurrence of the dip.
Once the Active Power output has been restored to the required level, Active
Power oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at
least that which would have been delivered if the Active Power was constant
- the oscillations are adequately damped.
(iv) For up to 30 minutes following such a Supergrid Voltage dip on the Onshore
Transmission System each Synchronous Power Generating Module is required to
remain connected and stable provided System operating conditions have returned
within those specified in ECC.6.1
(b) Requirements applicable to Type C and Type D Power Park Modules and OTSDUW
Plant and Apparatus (excluding OTSDUW DC Converters) subject to Supergrid
Voltage dips on the Onshore Transmission System greater than 140ms in duration.
(i) remain transiently stable and connected to the System without tripping of any
OTSDUW Plant and Apparatus, or Power Park Module and / or any constituent
Power Park Unit, for balanced Supergrid Voltage dips and associated durations
on the Onshore Transmission System (which could be at the Interface Point)
anywhere on or above the heavy black line shown in Figure ECC.6.3.15.9(b).
Appendix 4 and Figures EA.4.3.4 (a), (b) and (c) provide an explanation and
illustrations of Figure ECC.6.3.15.9(b) ; and,
15
Figure ECC.6.3.15.9(b)
(iii) restore Active Power output (or, in the case of OTSDUW, Active Power transfer
capability), following Supergrid Voltage dips on the Onshore Transmission
System as described in Figure ECC.6.3.15.9(b), within 1 second of restoration of
the voltage to 0.9 pu of the nominal voltage at the:
Onshore Grid Entry Point for directly connected Onshore Power Park
Modules or,
Interface Point for OTSDUW Plant and Apparatus and Offshore Power
Park Modules or,
User System Entry Point for Embedded Onshore Power Park Modules or ,
User System Entry Point for Embedded Medium Power Stations which
comprise Power Park Modules not subject to a Bilateral Agreement and with
an Onshore User System Entry Point (irrespective of whether they are
located Onshore or Offshore)
to at least 90% of the level available immediately before the occurrence of the dip
except in the case of a Non-Synchronous Generating Unit, OTSDUW Plant and
Apparatus or Power Park Module where there has been a reduction in the
Intermittent Power Source in the time range in Figure ECC.6.3.15.9(b) that
restricts the Active Power output or, in the case of OTSDUW, Active Power transfer
capability below this level. Once the Active Power output or, in the case of
OTSDUW, Active Power transfer capability has been restored to the required level,
Active Power oscillations shall be acceptable provided that:
- the total Active Energy delivered during the period of the oscillations is at
least that which would have been delivered if the Active Power was constant
- the oscillations are adequately damped.
(iv) For up to 30 minutes following such a Supergrid Voltage dip on the Onshore
Transmission System each Power Park Module and / or any constituent Power Park
Unit and OTSDUW Plant and Apparatus is required to remain connected and stable
provided System operating conditions have returned within those specified in ECC.6.1.
(i) In the case of a Power Park Module (excluding Non-Synchronous Electricity Storage
Modules), the requirements in ECC.6.3.15.9 do not apply when the Power Park Module
(excluding Non-Synchronous Electricity Storage Modules) is operating at less than
5% of its Rated MW or during very high primary energy source conditions when more
than 50% of the Power Park Units in a Power Park Module have been shut down or
disconnected under an emergency shutdown sequence to protect User’s Plant and
Apparatus.
(ii) In addition to meeting the conditions specified in ECC.6.1.5(b) and ECC.6.1.6, each Non-
Synchronous Generating Unit, OTSDUW Plant and Apparatus or Power Park
Module and any constituent Power Park Unit thereof will be required to withstand,
without tripping, the negative phase sequence loading incurred by clearance of a close-
up phase-to-phase fault, by System Back-Up Protection on the Onshore
Transmission System operating at Supergrid Voltage.
ECC.6.3.15.11.1 The HVDC System shall be capable of finding stable operation points with a minimum
change in Active Power flow and voltage level, during and after any planned or
unplanned change in the HVDC System or AC System to which it is connected. The
Company shall specify the changes in the System conditions for which the HVDC
Systems shall remain in stable operation.
ECC.6.3.15.11.2 The HVDC System owner shall ensure that the tripping or disconnection of an HVDC
Converter Station, as part of any multi-terminal or embedded HVDC System, does not
result in transients at the Grid Entry Point or User System Entry Point beyond the limit
specified by The Company in co-ordination with the Relevant Transmission Licensee.
ECC.6.3.15.11.3 The HVDC System shall withstand transient faults on HVAC lines in the network adjacent
or close to the HVDC System, and shall not cause any of the equipment in the HVDC
System to disconnect from the network due to autoreclosure of lines in the System.
ECC.6.3.15.11.4 The HVDC System Owner shall provide information to The Company on the resilience
of the HVDC System to AC System disturbances.
ECC.6.3.16.1 General Fast Fault Current injection, principles and concepts applicable to Type B, Type
C and Type D Power Park Modules and HVDC Equipment
Issue 6 Revision 21 ECC 04 March 2024
68 of 147
ECC.6.3.16.1.1 In addition to the requirements of ECC.6.1.4, ECC.6.3.2, ECC.6.3.8 and ECC.A.7, each
Type B, Type C and Type D Power Park Module or each Power Park Unit within a Type
B, Type C and Type D Power Park Module or HVDC Equipment shall be required to
satisfy the following requirements unless operating in a Grid Forming Capability mode in
which case the requirements of ECC.6.3.19 shall apply instead. For the purposes of this
requirement, current and voltage are assumed to be positive phase sequence values.
ECC.6.3.16.1.2 For any balanced fault which results in the positive phase sequence voltage falling below
the voltage levels specified in ECC.6.1.4 at the Grid Entry Point or User System Entry
Point (if Embedded), each Type B, Type C and Type D Power Park Module or each
Power Park Unit within a Type B, Type C and Type D Power Park Module or HVDC
Equipment shall, as a minimum (unless an alternative type registered solution has
otherwise been agreed with The Company), be required to inject a reactive current above
the heavy black line shown in Figure ECC.16.3.16(a)
Figure ECC.6.3.16(a)
ECC.6.3.16.1.3 Figure ECC.6.3.16(a) defines the reactive current (IR) to be supplied under a faulted condition
which shall be dependent upon the pre-fault operating condition and the retained voltage at
the Grid Entry Point or User System Entry Point voltage. For the avoidance of doubt, each
Power Park Module (and any constituent element thereof) or HVDC Equipment, shall be
required to inject a reactive current (IR) which shall be not less than its pre-fault reactive current
and which shall as a minimum increase with the fall in the retained voltage each time the
voltage at the Grid Entry Point or User System Entry Point (if Embedded) falls below 0.9pu
whilst ensuring the overall rating of the Power Park Module (or constituent element thereof)
or HVDC Equipment shall not be exceeded.
Figure ECC.16.3.16(b)
Figure ECC.16.3.16(c)
ECC.6.3.16.1.5 The injected reactive current (IR)shall be above the shaded area shown in Figure
ECC.6.3.16(b) and Figure ECC.6.3.16(c) with priority being given to reactive current injection
with any residual capability being supplied as active current. Under any faulted condition,
where the voltage falls outside the limits specified in ECC.6.1.4, there would be no requirement
for each Power Park Module or constituent Power Park Unit or HVDC Equipment to exceed
its transient or steady state rating of 1.0pu as defined in ECC.6.3.16.1.7.
Issue 6 Revision 21 ECC 04 March 2024
70 of 147
ECC.6.3.16.1.6 For any planned or switching events (as outlined in ECC.6.1.7 of the Grid Code) or unplanned
events which results in temporary power frequency over voltages (TOV’s), each Type B, Type
C and Type D Power Generating Module or each Power Park Unit within a Type B, Type
C or Type D Power Park Module or HVDC Equipment will be required to satisfy the transient
overvoltage limits specified in the Bilateral Agreement.
ECC.6.3.16.1.7 For the purposes of this requirement, the maximum rated current is taken to be the maximum
current each Power Park Module (or the sum of the constituent Power Park Units which
are connected to the System at the Grid Entry Point or User System Entry Point) or HVDC
Converter is capable of supplying. In the case of a Power Park Module this would be the
maximum rated current at the Grid Entry Point (or User System Entry Point if Embedded)
when the Power Park Module is operating at rated Active Power and rated Reactive
Power (as required under ECC.6.3.2) whilst operating over the nominal voltage range as
required under ECC.6.1.4 at the Grid Entry Point (or User System Entry Point if
Embedded). In the case of a Power Park Unit forming part of a Type B, Type C and Type
D Power Park Module, the maximum rated current expected would be the maximum current
supplied from each constituent Power Park Unit when the Power Park Module is operating
at rated Active Power and rated Reactive Power over the nominal voltage operating range
as defined in ECC.6.1.4 less the contribution from the reactive compensation equipment.
For example, in the case of a 100MW Power Park Module (consisting of 50 x 2MW Power
Park Units and +10MVAr reactive compensation equipment) the Rated Active Power at the
Grid Entry Point (or User System Entry Point if Embedded) would be taken as 100MW
and the rated Reactive Power at the Grid Entry Point or (User System Entry Point if
Embedded) would be taken as 32.8MVArs (ie Rated MW output operating at 0.95 Power
Factor lead or 0.95 Power Factor lag as required under ECC.6.3.2.4). In this example, the
maximum rating of each constituent Power Park Unit is obtained when the Power Park
Module is operating at 100MW, and +32.8MVAr less 10MVAr equal to 22.8MVAr or
– 32.8MVAr (less the reactive compensation equipment component of 10MVAr (ie -
22.8MVAr) when operating within the normal voltage operating range as defined under
ECC.6.1.4 (allowing for any reactive compensation equipment or losses in the Power Park
Module array network).
For the avoidance of doubt, the total current of 1.0pu would be assumed to be on the MVA
rating of the Power Park Module or HVDC Equipment (less losses). Under all normal and
abnormal conditions, the steady state or transient rating of the Power Park Module (or
any constituent element including the Power Park Units) or HVDC Equipment,
would not be required to exceed the locus shown in Figure 16.3.16(d).
Figure ECC.16.3.16(d)
ECC.6.3.16.1.14 In the case of a unbalanced fault, the Generator or HVDC System Owner shall confirm
to The Company their ability to prevent transient overvoltages arising on the remaining
healthy phases and the control strategy employed.
ECC.6.3.19.1 In order for the National Electricity Transmission System to satisfy the stability
requirements defined in the National Electricity Transmission System Security and
Quality of Supply Standards, it is an essential requirement that an appropriate volume of
Grid Forming Plant is available and capable of providing a Grid Forming Capability.
ECC.6.3.19.2 Grid Forming Capability is not a mandatory requirement but one which will be delivered
through market arrangements, the details of which shall be published on The Company’s
Website. Grid Forming Capability can be implemented by any technology including
Electronic Power Converters with a GBGF- I ability, rotating Synchronous Generating
Units or a combination of the two.
Issue 6 Revision 21 ECC 04 March 2024
75 of 147
ECC.6.3.19.3 As noted in ECC.6.3.19.2, Grid Forming Capability is not a mandatory requirement, however
where a User (be they a GB Code User or EU Code User) or Non-CUSC Party wishes to
offer a Grid Forming Capability, then they will be required to ensure their Grid Forming
Plant meets the following requirements.
(i) The Grid Forming Plant must fully comply with the applicable requirements of the
Grid Code including but not limited to the Planning Code (PC), Connection
Conditions (CC’s) or European Connection Conditions (ECC’s) (as applicable),
Compliance Processes (CP’s) or European Compliance Processes (ECP’s) (as
applicable), Operating Codes (OC’s), Balancing Codes (BC’s) and Data
Registration Code (DRC).
(ii) Each GBGF-I shall comprise an Internal Voltage Source and reactance. For the
avoidance of doubt, the reactance between the Internal Voltage Source and Grid
Entry Point or User System Entry Point (if Embedded) within the Grid Forming
Plant can only be made by a combination of several physical discrete reactances.
This could include the reactance of the Synchronous Generating Unit or Power
Park Unit or HVDC System or Electricity Storage Unit or Dynamic Reactive
Compensation Equipment and the electrical Plant and Apparatus connecting the
Synchronous Generating Unit or Power Park Unit or HVDC System or Electricity
Storage Unit (such as a transformer) to the Grid Entry Point or User System Entry
Point (if Embedded).
(iii) In addition to meeting the requirements of CC.6.3.15 or ECC.6.3.15, each Grid
Forming Plant is required to remain in synchronism with the Total System and
maintain a Load Angle whose value can vary between 0 and 90 degrees (π/2
radians).
(iv) When subject to a fault or disturbance, or System Frequency change, each Grid
Forming Plant shall be capable of supplying Active ROCOF Response Power,
Active Phase Jump Power, Active Damping Power, Active Control Based
Power, Control Based Reactive Power, Voltage Jump Reactive Power and
GBGF Fast Fault Current Injection.
(v) Each GBGF-I shall be capable of:-
(a) Providing a symmetrical ability for importing and exporting Active ROCOF
Response Power, Active Phase Jump Power, Active Damping Power and
Active Control Based Power under both rising and falling System Frequency
conditions. Such requirements will apply over the full System Frequency range
as detailed in CC.6.1.2 and CC.6.1.3 or ECC.6.1.2 (as applicable). In satisfying
these requirements, User’s and Non-CUSC Parties should be aware of (but not
limited to) the exclusions in CC.6.3.3, CC.6.3.7 and BC3.7.2.1 (as applicable for
GB Code User’s) or ECC.6.1.2, ECC.6.3.3, ECC.6.3.7 and BC3.7.2.1(b)(i) (as
applicable for EU Code User’s and Non-CUSC Parties) during System
Frequencies between 47Hz – 52Hz, excluding CC.6.1.3 or ECC.6.1,2.1,2 for a
Grid Forming Plant with time limited output ratings. For the avoidance of doubt,
an asymmetrical response is permissible as agreed with The Company when
required to protect User’s and Non-CUSC Parties Plant and Apparatus or
asymmetry in energy availability.
(b) Operating as a voltage source behind a real reactance.
(c) being designed so as not to cause any undue interactions which could cause
damage to the Total System or other User’s Plant and Apparatus.
(d) include an Active Control Based Power part of the control system that can
respond to changes in the Grid Forming Plant or external signals from the Total
System available at the Grid Entry Point or User System Entry Point but with
a bandwidth below 5 Hz to avoid AC System resonance problems.
(e) meeting the requirements of ECC.6.3.13 irrespective of being owned or operated
by a GB Code User, EU Code User or Non-CUSC Party.
(f) GBGF-I with an importing capability mode of operation such as DC Converters,
HVDC Systems and Electricity Storage Modules are required to have a
Issue 6 Revision 21 ECC 04 March 2024
76 of 147
predefined frequency response operating characteristic over the full import and
export range which is contained within the envelope defined by the red and blue
lines shown in Figure ECC.6.3.19.3. This characteristic shall be submitted to The
Company. For the avoidance of doubt, Grid Forming Plants which are only
capable of exporting Active Power to the Total System are only required to
operate over the exporting power region
.
Figure ECC.6.3.19.3
(vi) Each User or Non-CUSC Party shall design their GBGF-I system with an equivalent
Damping Factor of between 0.2 and 5.0. It is down to the User or Non-CUSC Party
to determine the Damping Factor, whose value shall be agreed with The Company.
It is typical for the Damping Factor to be less than 1.0, though this will be dependent
upon the parameters of the Grid Forming Plant and the equivalent System
impedance at the Grid Entry Point or User System Entry Point.
The output of the Grid Forming Plant shall be designed such that following a
disturbance on the System, the Active Power output and Reactive Power output
shall be adequately damped. The damping shall be judged to be adequate if the
corresponding Active Power response to a disturbance decays with a response that
is in line with the response of second order system that has the same equivalent
Damping Factor.
(vii) Each GBGF-I shall be designed so as not to interact and affect the operation,
performance, safety or capability of other User’s Plant and Apparatus connected to
the Total System. To achieve this requirement, each User and Non-CUSC Party
shall be required to submit the data required in PC.A.5.8
ECC.6.3.19.4 In addition to the requirements of ECC.6.3.19.1 – ECC.6.3.19.3 each Grid Forming Plant
shall also be capable of: -
(i) satisfying the requirements of ECC.6.3.19.5.
(ii) operating at a minimum short circuit level of zero MVA at the Grid Entry Point or User
System Entry Point.
(iii) providing any additional quality of supply requirements, including but not limited to
reductions in the permitted frequency of Temporary Power System Over-voltage
events (TOV’s) and System Frequency bandwidth limitations, as agreed with The
Company. Such requirements will be pursuant to the terms of the Bilateral Agreement.
For the avoidance of doubt, this requirement is in addition the minimum quality of supply
requirements detailed in CC.6.1.5, CC.6.1.6 and CC.6.1.7 (as applicable) or ECC.6.1.5,
ECC.6.1.6 and ECC.6.1.7 (as applicable),
ECC.6.3.19.5 GBGF Fast Fault Current Injection
Figure ECC.6.3.19.5(a)
ECC.6.3.19.5.2 Figure ECC.6.3.19.5(a) defines the reactive current to be supplied under a faulted condition
which shall be dependent upon the pre-fault operating condition and the retained voltage at
the Grid Entry Point or User System Entry Point voltage. For the avoidance of doubt, each
Grid Forming Plant (and any constituent element thereof), shall be required to inject a
reactive current which shall be not less than its pre-fault reactive current and which shall as a
minimum, increase each time the voltage at the Grid Entry Point or User System Entry Point
(if Embedded) falls below 0.9pu whilst ensuring the overall rating of the Grid Forming Plant
(or constituent element thereof) shall not be exceeded.
Figure ECC.6.3.19.5(b)
ECC.6.3.19.5.4 The injected current shall be above the shaded area shown in Figure ECC.6.3.19.5(b) for
the duration of the fault clearance time which for faults on the Transmission System cleared
in Main Protection operating times shall be up to 140ms. Under any faulted condition,
where the voltage falls outside the limits specified in CC.6.1.4 or ECC.6.1.4 (as applicable),
there will be no requirement for each Grid Forming Plant or constituent part to exceed its
transient or steady state rating as defined in Table PC.A.5.8.2.
ECC.6.3.19.5.5 For any planned or switching events (as outlined in CC.6.1.7 or ECC.6.1.7 of the Grid Code)
or unplanned events which results in Temporary Power System Over Voltages (TOV’s),
each Grid Forming Plant will be required to satisfy the transient overvoltage limits specified
in the Bilateral Agreement.
ECC.6.3.19.5.6 For the purposes of this requirement, the maximum rated current will be the Peak Current
Rating declared by the Grid Forming Plant Owner in accordance with Table PC.A.5.8.2.
ECC.6.3.19.5.7 Each Grid Forming Plant shall be designed to ensure a smooth transition between voltage
control mode and Fault Ride Through mode in order to prevent the risk of instability which
could arise in the transition between the steady state voltage operating range as defined
under CC.6.1.4 or ECC.6.1.4 (as applicable) and abnormal conditions where the retained
voltage falls below 90% of nominal voltage. Such a requirement is necessary to ensure
adequate performance between the pre-fault operating condition of the Grid Forming Plant
and its subsequent behaviour under faulted conditions. Grid Forming Plant Owners are
required to both advise and agree with The Company the control strategy employed to
mitigate the risk of such instability.
ECC.6.3.19.5.8. Each Grid Forming Plant shall be designed to reduce the risk of transient over voltage
levels arising following clearance of the fault and in order to mitigate the risk of any form of
instability which could result. The requirements for the maximum transient overvoltage
withstand capability and associated time duration, shall be agreed between the User or Non-
CUSC Party and The Company as part of the Bilateral Agreement.
ECC.6.5.2.3 Calls made and received over Control Telephony and System Telephony may be recorded
and subsequently replayed for commercial and operational reasons.
Issue 6 Revision 21 ECC 04 March 2024
83 of 147
ECC.6.5.3 Not Used
ECC.6.5.4 Obligations in respect of Control Telephony and System Telephony
ECC.6.5.4.1 Where The Company requires Control Telephony, Users are required to use the Control
Telephony to communicate with The Company and / or the Transmission Licensees’ in
respect of all Connection Points with the National Electricity Transmission System, all
Embedded Large Power Stations, Embedded HVDC Systems and Network Operator’s
Control Centres as appropriate. The Company shall provide Control Telephony interface
equipment at the User’s Control Point or the Network Operators Control Centre as
appropriate. Where the EU Code User’s or Network Operators Control Centre telephony
equipment is not capable of providing the required facilities or is otherwise incompatible with
the Transmission Control Telephony, The Company shall provide a Control Telephony
handset(s). Details of and relating to the Control Telephony requirements are contained in
the Bilateral Agreement with EU Code User’s.
ECC.6.5.4.2 Where in The Company’s sole opinion the installation of Control Telephony is not
practicable at a User’s Control Point(s), The Company shall specify in the Bilateral
Agreement whether System Telephony is required. Where System Telephony is required
by The Company, the User shall ensure that System Telephony is installed.
ECC.6.5.4.3 Where System Telephony is installed, EU Code Users are required to use the System
Telephony for communication with The Company and the relevant Transmission
Licensees’ Control Engineers in respect of those Control Point(s) for which it has been
installed. Details of and relating to the System Telephony required are contained in the
Bilateral Agreement.
ECC.6.5.4.4 Where Control Telephony or System Telephony is installed, routine testing of such facilities
may be required by The Company (not normally more than once in any calendar month). The
User and The Company shall use reasonable endeavours to agree a test programme and
where The Company requests the assistance of the User in performing the agreed test
programme the User shall provide such assistance. The Company requires the EU Code
User to test the backup power supplies feeding its Control Telephony facilities at least once
every 5 years.
ECC.6.5.4.5 Control Telephony and System Telephony shall only be used for the purposes of
operational voice communication between The Company and the relevant User.
ECC.6.5.4.6 Control Telephony contains emergency calling functionality to be used for operational
communication only under normal and emergency conditions. Functionality enables The
Company and Users to utilise a priority call in the event of an emergency. The Company
and EU Code Users shall only use such priority call functionality for urgent operational
communications.
ECC.6.5.5 Technical Requirements for Control Telephony and System Telephony
ECC.6.5.5.1 Detailed information on the technical interfaces and support requirements for Control
Telephony is provided in the Control Telephony Electrical Standard identified in the Annex
to the General Conditions. Where additional information, or information in relation to Control
Telephony applicable in Scotland, is requested by Users, this will be provided, where
possible, by The Company.
ECC.6.5.5.2 System Telephony shall consist of a dedicated telephone connected to an appropriate public
communications network that shall be configured by the relevant User. The Company shall
provide a dedicated free phone number (UK only), for the purposes of receiving incoming calls
to The Company, which Users shall utilise for System Telephony. System Telephony shall
only be utilised by The Company’s Control Engineer and the User’s Responsible
Engineer/Operator for the purposes of operational communications.
ECC.6.5.6 Operational Metering
(c) Detailed specifications of these required electronic facilities will be provided by The
Company on request and they are listed as Electrical Standards in the Annex to the
General Conditions.
Facsimile Machines
ECC.6.5.9 Each User and The Company shall provide a facsimile machine or machines:
(a) in the case of Generators, at the Control Point of each Power Station and at its Trading
Point;
(b) in the case of The Company and Network Operators, at the Control Centre(s); and
(c) in the case of Non-Embedded Customers and HVDC Equipment owners at the Control
Point.
ECC.6.6.1.10 Detailed specifications for Grid Forming Capability Plant dynamic performance including
triggering criteria, sample rates, the communication protocol and recorded data shall be
specified by The Company in the Bilateral Agreement.
ECC.6.6.3.3 The User will provide all relevant signals for this purpose in the form of d.c. voltages within the
range -10V to +10V. In exceptional circumstances some signals may be accepted as d.c.
voltages within the range -60V to +60V with prior agreement between the User and The
Company. All signals shall:
(i) in the case of an Onshore Power Generating Module or Onshore HVDC Convertor
Station, be suitably terminated in a single accessible location at the Generator or HVDC
Converter Station owner’s site.
(ii) in the case of an Offshore Power Generating Module and OTSDUW Plant and
Apparatus, be transmitted onshore without attenuation, delay or filtering which would
result in the inability to fully demonstrate the objectives of the test, or identify any potential
safety or plant instability issues, and be suitably terminated in a single robust location
normally located at or near the onshore Interface Point of the Offshore Transmission
System to which it is connected.
ECC.6.6.3.4 All signals shall be suitably scaled across the range. The following scaling would (unless The
Company notify the User otherwise) be acceptable to The Company:
(a) 0MW to Maximum Capacity or Interface Point Capacity 0-8V dc
(b) Maximum leading Reactive Power to maximum lagging Reactive Power -8 to 8V dc
(c) 48 – 52Hz as -8 to 8V dc
(d) Nominal terminal or connection point voltage -10% to +10% as -8 to 8V dc
ECC.6.6.3.5 The User shall provide to The Company a 230V power supply adjacent to the signal terminal
location.
ECC.7.10.1 From 04/09/2024 The Company, each Generator, HVDC System Owner, Network
Operator, Non-Embedded Customer and each Restoration Contractor with a continuously
staffed Control Point or Control Centre as provided for in ECC.7.9 shall:-
(i) Ensure they have the appropriate Critical Tools and Facilities, necessary to control their
assets for System Restoration, from their Control Point or Control Centre, as
appropriate, for a minimum period of 72 hours (or such longer period as agreed between
the Generator, HVDC System Owner, Network Operator, Non-Embedded Customer
Issue 6 Revision 21 ECC 04 March 2024
96 of 147
and/or Restoration Contractor and The Company) following a Total Shutdown or
Partial Shutdown.
(ii) Ensure as far as reasonably practical that they have adequate control equipment
redundancy in place so that in the event of a failure of one or more components of the
control system its function is unimpaired.
(iii) Report on the results of their management and testing for their Critical Tools and
Facilities on request from The Company.
ECC.7.10.2 From 04/09/2024 each BM Participant including a Virtual Lead Party with a continuously
staffed Control Point as provided for in ECC.7.9 (excluding those BM Participants covered
by the requirements of ECC.7.10.1), shall:-
(i) Ensure they have the appropriate Critical Tools and Facilities (as defined in clause
(c) of the definition of Critical Tools and Facilities in the Grid Code Glossary and
Definitions) for a minimum period of 72 hours (or such longer period as agreed
between the BM Participant including a Virtual Lead Party and The Company)
following a Total Shutdown or Partial Shutdown.
(ii) Ensure as far as reasonably practical that they have adequate control equipment
redundancy in place at their Control Point so that in the event of a failure of one or
more components of their Critical Tools and Facilities its function is unimpaired.
(iii) Report on the results of their management and testing for their Critical Tools and
Facilities on request by The Company.
ECC.7.10.3 In the case of a BM Participant or Virtual Lead Party which has an Anchor Restoration
Contract or Top Up Restoration Contract in respect of one or more of its aggregated Plants,
the requirements of ECC.7.10.1 shall only apply between the Control Point of the BM
Participant or Virtual Lead Party and that Plant with an Anchor Plant Capability or Top Up
Restoration Capability. For other non-contracted Plants under the control of the BM
Participant or Virtual Lead Party, the requirements of ECC.7.10.2 shall continue to apply.
ECC.7.10.4 Where a Network Operator installs a Distribution Restoration Zone Control System to
facilitate operation of a Distribution Restoration Zone Plan, the high level functional
requirements of the Distribution Restoration Zone Control System shall be in accordance
with the guidance provided in the applicable electrical standard listed in the annex to the
General Conditions.
ECC.7.10.5 Network Operators shall ensure that their substations which are required to be operable
during System Restoration have 72 hour electrical supply resilience to facilitate Network
Operators being able to:
• restore auxiliary supplies to Transmission substations;
• switch Demand in accordance with a Restoration Plan;
• support The Company in satisfying the requirements of the Electricity System
Restoration Standard.
ECC.7.10.6 The Company, each EU Code User and Restoration Contractor shall ensure their Critical
Tools and Facilities are cyber secure accordance with the Security of Network and
Information System (NIS) Regulations. This requirement applies to The Company, EU Code
Users and Restoration Contractors at all times.
ECC.7.10.7 Notwithstanding the requirements of ECC.7.10.1, The Company, each EU Code User and
Restoration Contractor shall ensure that their control systems, communications systems,
operational metering and telemetry systems including SCADA, are sufficiently robust and
reliable such that they are capable of handling, processing and prioritising the significant
volumes of data that could reasonably be expected to occur during System Restoration.
ECC.7.11 Obligations on and Assurance from The Company, EU Code Users and Restoration
Contractors during Total Shutdown and Partial Shutdown conditions
ECC.7.11.1 In respect of The Company, its Apparatus shall be designed such that it can safely shutdown
and does not pose a risk to personnel or Apparatus in the event of a total loss of supply.
ECC.7.11.2 All EU Code Users and Restoration Contractors shall ensure their Plant and Apparatus
can safely shut down and does not pose a risk to Plant and/or personnel in the event of a total
loss of supplies at a EU Code User’s Site(s) or Restoration Contractor’s site be it caused
by a Total Shutdown, Partial Shutdown or such other event. In satisfying this requirement,
Generators, HVDC System Owners and Restoration Contractors shall be able to
demonstrate to The Company that in the event supplies were to be lost to their Site, then on
the restoration of supplies, their Plant can be made operational and begin to operate in at
least the same way and as quickly as would be expected for a cold start following a Total
System Shutdown or Partial System Shutdown in accordance with the data submitted in
PC.A.5.7 in accordance with the Week 24 process. For EU Code Users where they believe
this requirement is cost prohibitive or technically impossible, such EU Code Users shall
discuss the issue with The Company, and The Company shall inform The Authority of the
details agreed. Where such an issue cannot be agreed by The Company following all
reasonable attempts or where the capability provided by the EU Code User cannot be agreed
by The Company as being sufficient after examining all reasonable alternative solutions
through the Compliance Processes, the EU Code User may apply for a derogation from the
Grid Code.
ECC.7.11.3 The requirements of ECC.7.11.1 and ECC.7.11.2 shall apply for a period of total loss of
supplies to The Company’s operational sites or an EU Code User’s Site or Restoration
Contractor’s site of up to 72 hours. EU Code Users and Restoration Contractors shall
confirm to The Company that the total loss of supplies to their Site for a period of up to 72
hours shall not result in damage to Plant and Apparatus such that it would then be unable to
operate upon restoration of electrical supplies to the site.
ECC.7.11.4 Network Operators shall ensure that in coordination with The Company and relevant
Transmission Licensees, they have the capability to switch Demand at sufficient speed to
support The Company in satisfying the requirements of the Electricity System Restoration
Standard. This requirement assumes:
• the successful implementation of Restoration Plans;
• the successful delivery of the obligations of Restoration Contractors who are
parties to these plans; and
• the further requirements of OC9 have been implemented.
ECC.A.1.1 Principles
Types of Schedules
ECC.A.1.1.1 At all Complexes (which in the context of this ECC shall include, Interface Sites until the
OTSUA Transfer Time) the following Site Responsibility Schedules shall be drawn up using
the relevant proforma attached or with such variations as may be agreed between The
Company and EU Code Users, but in the absence of agreement the relevant proforma
attached will be used. In addition, in the case of OTSDUW Plant and Apparatus, and in
readiness for the OTSUA Transfer Time, the User shall provide The Company with the
necessary information such that Site Responsibility Schedules in this form can be prepared
by the Relevant Transmission Licensees for the Transmission Interface Site:
(a) Schedule of HV Apparatus
(b) Schedule of Plant, LV/MV Apparatus, services and supplies;
(c) Schedule of telecommunications and measurements Apparatus.
Other than at Power Generating Module (including DC Connected Power Park Modules)
and Power Station locations, the schedules referred to in (b) and (c) may be combined.
New Connection Sites
ECC.A.1.1.2 In the case of a new Connection Site each Site Responsibility Schedule for a Connection
Site shall be prepared by The Company in consultation with relevant Users at least 2 weeks
prior to the Completion Date (or, where the OTSUA is to become Operational prior to the
OTSUA Transfer Time, an alternative date) under the Bilateral Agreement and/or
Construction Agreement for that Connection Site (which may form part of a Complex). In
the case of a new Interface Site where the OTSUA is to become Operational prior to the
OTSUA Transfer Time each Site Responsibility Schedule for an Interface Site shall be
prepared by The Company in consultation with relevant Users at least 2 weeks prior to the
Completion Date under the Bilateral Agreement and/or Construction Agreement for that
Interface Site (which may form part of a Complex) (and references to and requirements
placed on “Connection Site” in this ECC shall also be read as “Interface Site” where the
context requires and until the OTSUA Transfer Time). Each User shall, in accordance with
the timing requirements of the Bilateral Agreement and/or Construction Agreement ,
provide information to The Company to enable it to prepare the Site Responsibility
Schedule.
Sub-division
ECC.A.1.1.3 Each Site Responsibility Schedule will be subdivided to take account of any separate
Connection Sites on that Complex.
Scope
ECC.A.1.1.4 Each Site Responsibility Schedule shall detail for each item of Plant and Apparatus:
(a) Plant/Apparatus ownership;
(b) Site Manager (Controller) (except in the case of Plant/Apparatus located in SPT’s
Transmission Area);
(c) Safety issues comprising applicable Safety Rules and Control Person or other
responsible person (Safety Co-ordinator), or such other person who is responsible for
safety;
(d) Operations issues comprising applicable Operational Procedures and control engineer;
(e) Responsibility to undertake statutory inspections, fault investigation and maintenance.
1 Details of circuits traversing the Connection Site are only needed from the date which is the earlier of the date when the Site
Responsibility Schedule is first updated and 15th October 2004. In Scotland or Offshore, from a date to be agreed between The
Company and the Relevant Transmission Licensee.
Issue 6 Revision 21 ECC 04 March 2024
101 of 147
Urgent Changes
ECC.A.1.1.15 When a User identified on a Site Responsibility Schedule, or The Company, as the case
may be, becomes aware that an alteration to the Site Responsibility Schedule is necessary
urgently to reflect, for example, an emergency situation which has arisen outside its control,
the User shall notify The Company, or The Company shall notify the User, as the case may
be, immediately and will discuss:
(a) what change is necessary to the Site Responsibility Schedule;
(b) whether the Site Responsibility Schedule is to be modified temporarily or permanently;
(c) the distribution of the revised Site Responsibility Schedule.
The Company will prepare a revised Site Responsibility Schedule as soon as possible, and
in any event within seven days of it being informed of or knowing the necessary alteration.
The Site Responsibility Schedule will be confirmed by Users and signed on behalf of The
Company and Users and the Relevant Transmission Licensee (by the persons referred to
in ECC.A.1.1.9) as soon as possible after it has been prepared and sent to Users for
confirmation.
Responsible Managers
ECC.A.1.1.16 Each User shall, prior to the Completion Date under each Bilateral Agreement and/or
Construction Agreement, supply to The Company a list of Managers who have been duly
authorised to sign Site Responsibility Schedules on behalf of the User and The Company
shall, prior to the Completion Date under each Bilateral Agreement and/or Construction
Agreement, supply to that User the name of its Responsible Manager and the name of the
Relevant Transmission Licensee’s Responsible Manager and each shall supply to the
other any changes to such list six weeks before the change takes effect where the change is
anticipated, and as soon as possible after the change, where the change was not anticipated.
De-commissioning of Connection Sites
ECC.A.1.1.17 Where a Connection Site is to be de-commissioned, whichever of The Company or the User
who is initiating the de-commissioning must contact the other to arrange for the Site
Responsibility Schedule to be amended at the relevant time.
AREA
COMPLEX: SCHEDULE:
CONNECTION SITE:
AREA
COMPLEX: SCHEDULE:
CONNECTION SITE:
NOTES:
Basic Principles
(1) Where practicable, all the HV Apparatus on any Connection Site shall be shown on one
Operation Diagram. Provided the clarity of the diagram is not impaired, the layout shall
represent as closely as possible the geographical arrangement on the Connection Site.
(2) Where more than one Operation Diagram is unavoidable, duplication of identical information
on more than one Operation Diagram must be avoided.
(3) The Operation Diagram must show accurately the current status of the Apparatus e.g.
whether commissioned or decommissioned. Where decommissioned, the associated
switchbay will be labelled "spare bay".
(4) Provision will be made on the Operation Diagram for signifying approvals, together with
provision for details of revisions and dates.
(5) Operation Diagrams will be prepared in A4 format or such other format as may be agreed
with The Company.
(6) The Operation Diagram should normally be drawn single line. However, where appropriate,
detail which applies to individual phases shall be shown. For example, some HV Apparatus
is numbered individually per phase.
ECC.A.3.1 Scope
The frequency response capability is defined in terms of Primary Response, Secondary
Response and High Frequency Response. In addition to the requirements defined in
ECC.6.3.7 this appendix defines the minimum frequency response requirements for:-
(a) each Type C and Type D Power Generating Module
(b) each DC Connected Power Park Module
(c) each HVDC System
For the avoidance of doubt, this appendix does not apply to Type A and Type B Power
Generating Modules.
OTSDUW Plant and Apparatus should facilitate the delivery of frequency response services
provided by Offshore Generating Units and Offshore Power Park Units.
The functional definition provides appropriate performance criteria relating to the provision of
Frequency control by means of Frequency sensitive generation in addition to the other
requirements identified in ECC.6.3.7.
In this Appendix 3 to the ECC, for a Power Generating Module including a CCGT Module or
a Power Park Module or DC Connected Power Park Module, the phrase Minimum
Regulating Level applies to the entire CCGT Module or Power Park Module or DC
Connected Power Park Module operating with all Generating Units Synchronised to the
System.
The minimum Frequency response requirement profile is shown diagrammatically in Figure
ECC.A.3.1. The capability profile specifies the minimum required level of Frequency
Response Capability throughout the normal plant operating range.
ECC.A.3.2 Plant Operating Range
The upper limit of the operating range is the Maximum Capacity of the Power Generating
Module or Generating Unit or CCGT Module or HVDC Equipment.
The Minimum Stable Operating Level may be less than, but must not be more than, 65%
of the Maximum Capacity. Each Power Generating Module and/or Generating Unit and/or
CCGT Module and/or Power Park Module or HVDC Equipment must be capable of
operating satisfactorily down to the Minimum Regulating Level as dictated by System
operating conditions, although it will not be instructed to below its Minimum Stable Operating
Level . If a Power Generating Module or Generating Unit or CCGT Module or Power Park
Module, or HVDC Equipment is operating below Minimum Stable Operating Level because
of high System Frequency, it should recover adequately to its Minimum Stable Operating
Level as the System Frequency returns to Target Frequency so that it can provide Primary
and Secondary Response from its Minimum Stable Operating Level if the System
Frequency continues to fall. For the avoidance of doubt, under normal operating conditions
steady state operation below the Minimum Stable Operating Level is not expected. The
Minimum Regulating Level must not be more than 55% of Maximum Capacity.
In the event of a Power Generating Module or Generating Unit or CCGT Module or Power
Park Module or HVDC Equipment load rejecting down to no less than its Minimum
Regulating Level it should not trip as a result of automatic action as detailed in BC3.7. If the
load rejection is to a level less than the Minimum Regulating Level then it is accepted that
the condition might be so severe as to cause it to be disconnected from the System.
ECC.A.3.3 Minimum Frequency Response Requirement Profile
FAULT RIDE THROUGH REQUIREMENTS FOR TYPE B, TYPE C AND TYPE D POWER GENERATING
MODULES (INCLUDING OFFSHORE POWER PARK MODULES WHICH ARE EITHER AC CONNECTED
POWER PARK MODULES OR DC CONNECTED POWER PARK MODULES), HVDC SYSTEMS AND
OTSDUW PLANT AND APPARATUS
ECC.A.4A.1 Scope
The Fault Ride Through requirements are defined in ECC.6.3.15. This Appendix provides
illustrations by way of examples only of ECC.6.3.15.1 to ECC.6.3.15.10 and further
background and illustrations and is not intended to show all possible permutations.
ECC.A.4A.2 Short Circuit Faults At Supergrid Voltage On The Onshore Transmission System Up To
140ms In Duration
For short circuit faults at Supergrid Voltage on the Onshore Transmission System (which
could be at an Interface Point) up to 140ms in duration, the Fault Ride Through requirement
is defined in ECC.6.3.15. In summary any Power Generating Module (including a DC
Connected Power Park Module) or HVDC System is required to remain connected and
stable whilst connected to a healthy circuit. Figure ECC.A.4.A.2 illustrates this principle.
Figure ECC.A.4.A.2
The criteria for assessment is based on a voltage against time curve at each Grid Entry Point
or User System Entry Point. The voltage against time curve at the Grid Entry Point or User
System Entry Point varies for each different type and size of Power Generating Module as
detailed in ECC.6.3.15.2. – ECC.6.3.15.7.
The voltage against time curve represents the voltage profile at a Grid Entry Point or User
System Entry Point that would be obtained by plotting the voltage at that Grid Entry Point
or User System Entry Point before during and after the fault. This is not to be confused with
a voltage duration curve (as defined under ECC.6.3.15.9) which represents a voltage level
and associated time duration.
The post fault voltage at a Grid Entry Point or User System Entry Point is largely influenced
by the topology of the network rather than the behaviour of the Power Generating Module
itself. The EU Generator therefore needs to ensure each Power Generating Module remains
connected and stable for a close up solid three phase short circuit fault for 140ms at the Grid
Entry Point or User System Entry Point.
Two examples are shown in Figure EA.4.2(a) and Figure EA4.2(b). In Figure EA.4.2(a) the
post fault profile is above the heavy black line. In this case the Power Generating Module
must remain connected and stable. In Figure EA4.2(b) the post fault voltage dips below the
heavy black line in which case the Power Generating Module is permitted to trip.
Figure EA.4.2(a)
The process for demonstrating Fault Ride Through compliance against the requirements of
ECC.6.3.15 is detailed in ECP.A.3.5 and ECP.A.6.7 (as applicable).
ECC.A.4A.3 Supergrid Voltage Dips On The Onshore Transmission System Greater Than 140ms In
Duration
For balanced Supergrid Voltage dips on the Onshore Transmission System having
durations greater than 140ms and up to 3 minutes, the Fault Ride Through requirement is
defined in ECC.6.3.15.9.2.1(a) and Figure ECC.6.3.15.9(a) which is reproduced in this
Appendix as Figure EA.4.3.1 and termed the voltage–duration profile.
This profile is not a voltage-time response curve that would be obtained by plotting the
transient voltage response at a point on the Onshore Transmission System (or User
System if located Onshore) to a disturbance. Rather, each point on the profile (ie the heavy
black line) represents a voltage level and an associated time duration which connected
Synchronous Power Generating Modules must withstand or ride through.
Figures EA.4.3.2 (a), (b) and (c) illustrate the meaning of the voltage-duration profile for
voltage dips having durations greater than 140ms.
ECC.A.4A3.2 Requirements applicable to Power Park Modules or OTSDUW Plant and Apparatus subject
to Supergrid Voltage dips on the Onshore Transmission System greater than 140ms in
duration
For balanced Supergrid Voltage dips on the Onshore Transmission System (which could
be at an Interface Point) having durations greater than 140ms and up to 3 minutes the Fault
Ride Through requirement is defined in ECC.6.3.15.9.2.1(b) and Figure ECC.6.3.15.9(b)
which is reproduced in this Appendix as Figure EA.4.3.3 and termed the voltage–duration
profile.
This profile is not a voltage-time response curve that would be obtained by plotting the
transient voltage response at a point on the Onshore Transmission System (or User
System if located Onshore) to a disturbance. Rather, each point on the profile (ie the heavy
black line) represents a voltage level and an associated time duration which connected Power
Park Modules or OTSDUW Plant and Apparatus must withstand or ride through.
Figures EA.4.3.4 (a), (b) and (c) illustrate the meaning of the voltage-duration profile for
voltage dips having durations greater than 140ms.
Figure EA.4.3.3
(b) Operating time: Relay operating time shall not be more than 150 ms;
(d) Direction Tripping interlock for forward or reverse power flow capable of
being set in either position or off
(f) Output contacts: Two output contacts per stage to be capable of repetitively
In the case of Network Operators who are GB Code Users, the above requirements only apply
to a relay (if any) installed at the EU Grid Supply Point. Network Operators who are also GB
Code Users should continue to satisfy the requirements for low frequency relays as specified in
the CCs as applicable to their System.
48.8 5
48.75 5
48.7 10
48.6 7.5 10
48.5 7.5 10
48.4 7.5 10 10
48.2 7.5 10 10
48.0 5 10 10
47.8 5
Total % Demand 60 40 40
Table ECC.A.5.5.1a
Note – the percentages in table ECC.A.5.5.1a are cumulative such that, for example, should
the frequency fall to 48.6 Hz in NGET’s Transmission Area, 27.5% of the total Demand
connected to the National Electricity Transmission System in NGET’s Transmission Area
shall be disconnected by the action of Low Frequency Relays.
The percentage Demand at each stage shall be allocated as far as reasonably practicable.
The cumulative total percentage Demand is a minimum.
ECC.A.6.1 Scope
ECC.A.6.1.1 This Appendix sets out the performance requirements of continuously acting automatic
excitation control systems for Type C and Type D Onshore Synchronous Power
Generating Modules that must be complied with by the User. This Appendix does not limit
any site specific requirements where in The Company's reasonable opinion these facilities
are necessary for system reasons.
ECC.A.6.1.2 Where the requirements may vary the likely range of variation is given in this Appendix. It may
be necessary to specify values outside this range where The Company identifies a system
need, and notwithstanding anything to the contrary The Company may specify values outside
of the ranges provided in this Appendix 6. The most common variations are in the on-load
excitation ceiling voltage requirements and the response time required of the Exciter. Actual
values will be included in the Bilateral Agreement.
ECC.A.6.1.3 Should an EU Generator anticipate making a change to the excitation control system it shall
notify The Company under the Planning Code (PC.A.1.2(b) and (c)) as soon as the EU
Generator anticipates making the change. The change may require a revision to the Bilateral
Agreement.
ECC.A.6.2 Requirements
ECC.A.6.2.1 The Excitation System of a Type C or Type D Onshore Synchronous Power Generating
Module shall include an excitation source (Exciter), and a continuously acting Automatic
Voltage Regulator (AVR) and shall meet the following functional specification. Type D
Synchronous Power Generating Modules are also required to be fitted with a Power
System Stabiliser in accordance with the requirements of ECC.A.6.2.5.
ECC.A.6.2.3 Steady State Voltage Control
ECC.A.6.2.3.1 An accurate steady state control of the Onshore Synchronous Power Generating Module
pre-set Synchronous Generating Unit terminal voltage is required. As a measure of the
accuracy of the steady-state voltage control, the Automatic Voltage Regulator shall have
static zero frequency gain, sufficient to limit the change in terminal voltage to a drop not
exceeding 0.5% of rated terminal voltage, when the output of a Synchronous Generating
Unit within an Onshore Synchronous Power Generating Module is gradually changed from
zero to rated MVA output at rated voltage, Active Power and Frequency.
ECC.A.6.2.4 Transient Voltage Control
ECC.A.6.2.4.1 For a step change from 90% to 100% of the nominal Onshore Synchronous Generating
Unit terminal voltage, with the Onshore Synchronous Generating Unit on open circuit, the
Excitation System response shall have a damped oscillatory characteristic. For this
characteristic, the time for the Onshore Synchronous Generating Unit terminal voltage to
first reach 100% shall be less than 0.6 seconds. Also, the time to settle within 5% of the voltage
change shall be less than 3 seconds.
ECC.A.6.2.4.2 To ensure that adequate synchronising power is maintained, when the Onshore Power
Generating Module is subjected to a large voltage disturbance, the Exciter whose output is
varied by the Automatic Voltage Regulator shall be capable of providing its achievable upper
and lower limit ceiling voltages to the Onshore Synchronous Generating Unit field in a time
not exceeding that specified in the Bilateral Agreement. This will normally be not less than
50 ms and not greater than 300 ms. The achievable upper and lower limit ceiling voltages may
be dependent on the voltage disturbance.
ECC.A.6.2.4.3 The Exciter shall be capable of attaining an Excitation System On Load Positive Ceiling
Voltage of not less than a value specified in the Bilateral Agreement that will be:
not less than 2 per unit (pu)
ECC.A.6.2.8.3 The EU Generator shall also make provision to prevent any over-excitation restriction of the
Onshore Synchronous Generating Unit when the Excitation System is under manual
control, other than that necessary to ensure the Onshore Power Generating Module is
operating within its design limits.
ECC.A.7.1 Scope
ECC.A.7.1.1 This Appendix sets out the performance requirements of continuously acting automatic voltage
control systems for Onshore Power Park Modules, Onshore HVDC Converters Remote
End HVDC Converter Stations and OTSDUW Plant and Apparatus at the Interface Point
that must be complied with by the User. This Appendix does not limit any site specific
requirements where in The Company's reasonable opinion these facilities are necessary for
system reasons. The control performance requirements applicable to Configuration 2 AC
Connected Offshore Power Park Modules and Configuration 2 DC Connected Power
Park Modules are defined in Appendix E8.
ECC.A.7.1.2 Proposals by EU Generators or HVDC System Owners to make a change to the voltage
control systems are required to be notified to The Company under the Planning Code
(PC.A.1.2(b) and (c)) as soon as the Generator or HVDC System Owner anticipates making
the change. The change may require a revision to the Bilateral Agreement.
ECC.A.7.1.3 In the case of a Remote End HVDC Converter at a HVDC Converter Station, the control
performance requirements shall be specified in the Bilateral Agreement. These requirements
shall be consistent with those specified in ECC.6.3.2.4. In the case where the Remote End
HVDC Converter is required to ensure the zero transfer of Reactive Power at the HVDC
Interface Point then the requirements shall be specified in the Bilateral Agreement which
shall be consistent with those requirements specified in ECC.A.8 . In the case where a wider
reactive capability has been specified in ECC.6.3.2.4, then the requirements consistent with
those specified in ECC.A.7.2 shall apply with any variations being agreed between the User
and The Company.
ECC.A.7.2 Requirements
ECC.A.7.2.1 The Company requires that the continuously acting automatic voltage control system for the
Onshore Power Park Module, Onshore HVDC Converter or OTSDUW Plant and
Apparatus shall meet the following functional performance specification. If a Network
Operator has confirmed to The Company that its network to which an Embedded Onshore
Power Park Module or Onshore HVDC Converter or OTSDUW Plant and Apparatus is
connected is restricted such that the full reactive range under the steady state voltage control
requirements (ECC.A.7.2.2) cannot be utilised, The Company may specify alternative limits
to the steady state voltage control range that reflect these restrictions. Where the Network
Operator subsequently notifies The Company that such restriction has been removed, The
Company may propose a Modification to the Bilateral Agreement (in accordance with the
CUSC contract) to remove the alternative limits such that the continuously acting automatic
voltage control system meets the following functional performance specification. All other
requirements of the voltage control system will remain as in this Appendix.
ECC.A.7.2.2 Steady State Voltage Control
ECC.A.7.2.2.1 The Onshore Power Park Module, Onshore HVDC Converter or OTSDUW Plant and
Apparatus shall provide continuous steady state control of the voltage at the Onshore Grid
Entry Point (or Onshore User System Entry Point if Embedded) (or the Interface Point in
the case of OTSDUW Plant and Apparatus ) with a Setpoint Voltage and Slope
characteristic as illustrated in Figure ECC.A.7.2.2a.
ECC.A.7.2.2.2 The continuously acting automatic control system shall be capable of operating to a Setpoint
Voltage between 95% and 105% with a resolution of 0.25% of the nominal voltage. For the
avoidance of doubt values of 95%, 95.25%, 95.5% … may be specified, but not intermediate
values. The initial Setpoint Voltage will be 100%. The tolerance within which this Setpoint
Voltage shall be achieved is specified in BC2.A.2.6. For the avoidance of doubt, with a
tolerance of 0.25% and a Setpoint Voltage of 100%, the achieved value shall be between
99.75% and 100.25%. The Company may request the EU Generator or HVDC System
Owner to implement an alternative Setpoint Voltage within the range of 95% to 105%. For
Embedded Generators and Embedded HVDC System Owners the Setpoint Voltage will
be discussed between The Company and the relevant Network Operator and will be
specified to ensure consistency with ECC.6.3.4.
ECC.A.7.2.2.3 The Slope characteristic of the continuously acting automatic control system shall be
adjustable over the range 2% to 7% (with a resolution of 0.5%). For the avoidance of doubt
values of 2%, 2.5%, 3% may be specified, but not intermediate values. The initial Slope setting
will be 4%. The tolerance within which this Slope shall be achieved is specified in BC2.A.2.6.
For the avoidance of doubt, with a tolerance of 0.5% and a Slope setting of 4%, the achieved
value shall be between 3.5% and 4.5%. The Company may request the EU Generator or
HVDC System Owner to implement an alternative slope setting within the range of 2% to 7%.
For Embedded Generators and Onshore Embedded HVDC Converter Station Owners the
Slope setting will be discussed between The Company and the relevant Network Operator
and will be specified to ensure consistency with ECC.6.3.4.
Figure ECC.A.7.2.2c
ECC.A.7.2.2.4 Figure ECC.A.7.2.2b shows the required envelope of operation for -, OTSDUW Plant and
Apparatus, Onshore Power Park Modules and Onshore HVDC Converters except for
those Embedded at 33kV and below or directly connected to the National Electricity
Transmission System at 33kV and below. Figure ECC.A.7.2.2c shows the required envelope
of operation for Onshore Power Park Modules Embedded at 33kV and below, or directly
connected to the National Electricity Transmission System at 33kV and below. The
enclosed area within points ABCDEFGH is the required capability range within which the
Slope and Setpoint Voltage can be changed.
ECC.A.7.2.2.5 Should the operating point of the, OTSDUW Plant and Apparatus or Onshore Power Park
Module, or Onshore HVDC Converter deviate so that it is no longer a point on the operating
characteristic (figure ECC.A.7.2.2a) defined by the target Setpoint Voltage and Slope, the
continuously acting automatic voltage control system shall act progressively to return the value
to a point on the required characteristic within 5 seconds.
− 1 second where the step is sufficiently large to require a change in the steady
state Reactive Power output from zero to its maximum leading value or
maximum lagging value as required by ECC.6.3.2 (or, if appropriate
ECC.A.7.2.2.6 or ECC.A.7.2.2.7);
(iii) the magnitude of the Reactive Power output response produced within 1 second shall
vary linearly in proportion to the magnitude of the step change.
(iv) within 5 seconds from achieving 90% of the response as defined in ECC.A.7.2.3.1 (ii),
the peak to peak magnitude of any oscillations shall be less than 5% of the change in
steady state maximum Reactive Power.
(v) following the transient response, the conditions of ECC.A.7.2.2 apply.
MVArs
Required response at 1
second
0.2 1 Seconds
Figure ECC.A.7.2.3.1a
ECC.A.7.2.3.2 OTSDUW Plant and Apparatus or Onshore Power Park Modules or Onshore HVDC
Converters shall be capable of
(a) changing its Reactive Power output from its maximum lagging value to its maximum
leading value, or vice versa, then reverting back to the initial level of Reactive Power
output once every 15 seconds for at least 5 times within any 5 minute period; and
(b) changing its Reactive Power output from zero to its maximum leading value then
reverting back to zero Reactive Power output at least 25 times within any 24 hour
period and from zero to its maximum lagging value then reverting back to zero Reactive
In all cases, the response shall be in accordance to ECC.A.7.2.3.1 where the change in
Reactive Power output is in response to an on-load step change in Onshore Grid Entry
Point or Onshore User System Entry Point voltage, or in the case of OTSDUW Plant and
Apparatus an on-load step change in Transmission Interface Point voltage.
ECC.A.7.3.2 The Onshore Power Park Module or OTSDUW Plant and Apparatus or Onshore HVDC
Converter shall be capable of setting the Reactive Power setpoint anywhere in the Reactive
Power range as specified in ECC.6.3.2.4 with setting steps no greater than 5 MVAr or 5%
(whichever is smaller) of full Reactive Power, controlling the reactive power at the Grid Entry
Point or User System Entry Point if Embedded to an accuracy within plus or minus 5MVAr
or plus or minus 5% (whichever is smaller) of the full Reactive Power.
ECC.A.7.3.3 Any additional requirements for Reactive Power control mode of operation shall be specified
by The Company in coordination with the relevant Network Operator..
ECC.A.7.4.1 As defined in ECC.6.3.8.4.3, Power Factor control mode of operation is not required in
respect of Onshore Power Park Modules or OTSDUW Plant and Apparatus or Onshore
HVDC Converters unless otherwise specified by The Company in coordination with the
relevant Network Operator. However where there is a requirement for Power Factor control
ECC.A.7.4.2 The Onshore Power Park Module or OTSDUW Plant and Apparatus or Onshore HVDC
Converter shall be capable of controlling the Power Factor at the Grid Entry Point or User
System Entry Point (if Embedded) within the required Reactive Power range as specified
in ECC.6.3.2.2.1 and ECC.6.3.2.4 to a specified target Power Factor. The Company shall
specify the target Power Factor value (which shall be achieved within 0.01 of the set Power
Factor), its tolerance and the period of time to achieve the target Power Factor following a
sudden change of Active Power output. The tolerance of the target Power Factor shall be
expressed through the tolerance of its corresponding Reactive Power. This Reactive Power
tolerance shall be expressed by either an absolute value or by a percentage of the maximum
Reactive Power of the Onshore Power Park Module or OTSDUW Plant and Apparatus or
Onshore HVDC Converter. The details of these requirements being pursuant to the terms of
the Bilateral Agreement.
ECC.A.7.4.3 Any additional requirements for Power Factor control mode of operation shall be specified by
The Company in coordination with the relevant Network Operator.
ECC.A.8.1 Scope
ECC.A.8.1.1 This Appendix sets out the performance requirements of continuously acting automatic voltage
control systems for Configuration 2 AC Connected Offshore Power Park Modules and
Configuration 2 DC Connected Power Park Modules that must be complied with by the EU
Code User. This Appendix does not limit any site specific requirements that may be specified
where in The Company's reasonable opinion these facilities are necessary for system
reasons.
ECC.A.8.1.2 These requirements also apply to Configuration 2 DC Connected Power Park Modules. In
the case of a Configuration 1 DC Connected Power Park Module the technical performance
requirements shall be specified by The Company. Where the EU Generator in respect of a
DC Connected Power Park Module has agreed to a wider reactive capability range as
defined under ECC.6.3.2.5 and ECC.6.2.3.6 then the requirements that apply will be specified
by The Company and which shall reflect the performance requirements detailed in ECC.A.8.2
below but with different parameters such as droop and Setpoint Voltage.
ECC.A.8.1.3 Proposals by EU Generators to make a change to the voltage control systems are required
to be notified to The Company under the Planning Code (PC.A.1.2(b) and (c)) as soon as
the Generator anticipates making the change. The change may require a revision to the
Bilateral Agreement.
ECC.A.8.2 Requirements
ECC.A.8.2.1 The Company requires that the continuously acting automatic voltage control system for the
Configuration 2 AC connected Offshore Power Park Module and Configuration 2 DC
Connected Power Park Module shall meet the following functional performance
specification.
ECC.A.8.2.2 Steady State Voltage Control
ECC.A.8.2.2.1 The Configuration 2 AC connected Offshore Power Park Module and Configuration 2 DC
Connected Power Park Module shall provide continuous steady state control of the voltage
at the Offshore Connection Point with a Setpoint Voltage and Slope characteristic as
illustrated in Figure ECC.A.8.2.2a.
Figure ECC.A.8.2.2a
Figure ECC.A.8.2.2b
ECC.A.8.2.2.4 Figure ECC.A.8.2.2b shows the required envelope of operation for Configuration 2 AC
connected Offshore Power Park Module and Configuration 2 DC Connected Power Park
Module. The enclosed area within points ABCDEFGH is the required capability range within
which the Slope and Setpoint Voltage can be changed.
ECC.A.8.2.2.5 Should the operating point of the Configuration 2 AC connected Offshore Power Park or
Configuration 2 DC Connected Power Park Module deviate so that it is no longer a point
on the operating characteristic (Figure ECC.A.8.2.2a) defined by the target Setpoint Voltage
and Slope, the continuously acting automatic voltage control system shall act progressively to
return the value to a point on the required characteristic within 5 seconds.
− 1 second where the step is sufficiently large to require a change in the steady
state Reactive Power output from zero to its maximum leading value or
(iii) the magnitude of the Reactive Power output response produced within 1 second shall
vary linearly in proportion to the magnitude of the step change.
(iv) within 5 seconds from achieving 90% of the response as defined in ECC.A.8.2.3.1 (ii),
the peak to peak magnitude of any oscillations shall be less than 5% of the change in
steady state maximum Reactive Power.
(v) following the transient response, the conditions of ECC.A.8.2.2 apply.
MVArs
Required response at 1
second
0.2 1 Seconds
Figure ECC.A.8.2.3.1a
(a) changing their Reactive Power output from maximum lagging value to maximum
leading value, or vice versa, then reverting back to the initial level of Reactive Power
output once every 15 seconds for at least 5 times within any 5 minute period; and
(b) changing Reactive Power output from zero to maximum leading value then reverting
back to zero Reactive Power output at least 25 times within any 24 hour period and
from zero to its maximum lagging value then reverting back to zero Reactive Power
output at least 25 times within any 24 hour period. Any subsequent restriction on
reactive capability shall be notified to The Company in accordance with BC2.5.3.2,
and BC2.6.1.
In all cases, the response shall be in accordance to ECC.A.8.2.3.1 where the change in
Reactive Power output is in response to an on-load step change in Offshore Grid Entry
Point or Offshore User System Entry Point voltage or HVDC Interface Point voltage.
ECC.A.8.3.3 Any additional requirements for Reactive Power control mode of operation shall be specified
by The Company.
ECC.A.8.4.1 Power Factor control mode of operation is not required in respect of Configuration 2 AC
connected Offshore Power Park Modules or Configuration 2 DC Connected Power Park
Modules unless otherwise specified by The Company. However where there is a
requirement for Power Factor control mode of operation, the following requirements shall
apply.
ECC.A.8.4.3 Any additional requirements for Power Factor control mode of operation shall be specified by
The Company.
CONTENTS
(This contents page does not form part of the Grid Code)
DRSC.1 INTRODUCTION 2
DRSC.2 OBJECTIVE 2
DRSC.3 SCOPE 2
DRSC.4 GENERAL PROVISIONS 3
DRSC.5 SPECIFIC PROVISIONS FOR DEMAND UNITS WITH DEMAND 3
RESPONSE ACTIVE POWER CONTROL AND TRANSMISSION
CONSTRAINT MANAGEMENT
DRSC.6 SPECIFIC PROVISIONS FOR DEMAND UNITS WITH DEMAND 4
RESPONSE FREQUENCY CONTROL
DRSC.7 SPECIFIC PROVISIONS FOR DEMAND UNITS WITH DEMAND 4
RESPONSE VERY FAST ACTIVE POWER CONTROL
DRSC.8 DATA REQUIRED BY THE COMPANY FROM DEMAND RESPONSE PROVIDER’S 5
DRSC.9 OPERATIONAL METERING REQUIREMENTS 5
DRSC.11.3 COMPLIANCE 6
PART I
DRSC.4.2 Demand Response Providers who own, operate, control or manage Plant and Apparatus
or Demand Unit(s) within a Demand Facility and/or Closed Distribution System(s) or on
an aggregated basis may provide Demand Response Services to The Company. Demand
Response Providers can offer Demand Response Services on an individual or collective
basis and increase or decrease their Demand in accordance with the terms of their Ancillary
Services agreement.
DRSC.4.3 The Demand Response Services specified in DRSC.4.1 are not exclusive and do not preclude
Demand Response Providers from negotiating other services with The Company. These
services would be pursuant to the terms of the Ancillary Services agreement.
DRSC.5 SPECIFIC PROVISIONS FOR DEMAND UNITS WITH DEMAND RESPONSE ACTIVE
POWER CONTROL AND TRANSMISSION CONSTRAINT MANAGEMENT
DRSC.5.1 Where a Demand Response Provider provides Demand Response Active Power Control,
Demand Response Reactive Power Control or Demand Response Transmission
Constraint Management to The Company, then the following requirements as detailed below
shall apply. For the avoidance of doubt, these requirements shall apply either individually or
where it is not part of a Demand Facility, collectively as part of a Demand Aggregation
scheme through a Demand Response Provider. Demand Response Providers shall
ensure that any Demand Unit which they own, operate, control or manage and which is used
to provide Demand Response Services shall:-
(a) Be capable of satisfying the Frequency range requirements as specified in ECC.6.1.2.1.
(b) Be capable of satisfying the voltage range requirements as specified in ECC.6.1.4.1.
(c) Be capable of controlling the power consumption from the Total System in accordance
with the terms of the Ancillary Services agreement.
(d) Be capable of receiving instructions from The Company either directly or through a third
party to modify their demand in accordance with the Demand Response Service they
have agreed to provide..
(e) Be capable of adjusting its Real Power or Reactive Power flow within a time period
pursuant to the terms of the Ancillary Services agreement.
(f) Be capable of full execution of an instruction issued by The Company to modify its power
flow.
(g) Be capable of further demand changes as instructed by The Company, following the
execution of a previous instruction issued by The Company in accordance with the
Ancillary Services agreement. Any such instruction shall not exceed the normal safe
operating conditions of the Demand Response Provider’s Plant and Apparatus or
Demand Unit(s) which could cause such equipment to trip. Instructions to modify Active
Power or Reactive Power flow may have immediate or delayed effects but in any event
would need to comply with the requirements of the Ancillary Services agreement.
(h) Notify The Company of any change in the available capacity in accordance with the
relevant Ancillary Services agreement.
(i) Be capable of withstanding a rate of change of System Frequency of up to a maximum
of 1Hz/s measured over a 500ms time frame.
DRSC.9.1 The operational metering data required to be submitted to The Company will vary depending
upon the type of Demand Response Service provided. Demand Response Providers may
be required to install such operational metering equipment in accordance with the Ancillary
Services agreement.
DRSC.10.1 Demand Response Providers may be required to be fitted with communication and instruction
facilities to enable The Company to instruct them in the operational timeframe. These
requirements will vary depending upon the type of Demand Response Service provided and
will be set out in the Ancillary Services agreement.
PART II
DRSC.11.1.1 Demand Response Providers who enter into an agreement with The Company to provide
Ancillary Services are required to undertake a compliance process to ensure the Plant and
Apparatus or Demand Unit(s) which they own, operate, control or manage, satisfies the
requirements of the Ancillary Services agreement and the Demand Response Services
Code. For the avoidance of doubt, Demand Response Providers who are also EU Code
Users, will also be required to satisfy the requirements of the applicable requirements of the
European Compliance Processes (ECP’s).
DRSC.11.1.2 Each Demand Response Provider, shall confirm to The Company its ability to comply with
the requirements of the Ancillary Services agreement.
DRSC.11.1.3 Each Demand Response Provider shall notify The Company of any change to the Plant or
Apparatus which they own, operate, control or manage such they are no longer able to
satisfy the conditions specified in the Ancillary Services agreement and/or the relevant
provisions of the DRSC. Such changes shall be notified to The Company in accordance
with the terms of the Ancillary Services agreement.
DRSC.11.2.2 The format of the Demand Response Unit Document (DRUD) shall take the form shown
Issue 6 Revision 4 DRS 03 August 2021
5 of 11
in DRSC.A.1 and shall provide sufficient information to demonstrate the Plant and
Apparatus or Demand Unit(s) which a Demand Response Provider owns, operates,
controls or manages, is capable of satisfying the full requirements of the Ancillary
Services agreement and the applicable requirements of the DRSC. The compliance
requirements can be simplified to a single operational notification stage as well as be
reduced as agreed with The Company. Demand Response Providers shall be required
to submit a new DRUD for each subsequent Demand Unit added to its portfolio.
DRSC.11.2.3 When the Demand Response Provider has submitted a final DRUD to the satisfaction
of The Company, which clearly demonstrates full compliance with the Ancillary
Services agreement, The Company shall issue a Final Operational Notification to the
Demand Response Provider.
DRSC.11.3 COMPLIANCE
DRSC.11.3.1.1 Demand Response Providers are required to satisfy the requirements of the Ancillary
Services agreement which shall include satisfying the applicable requirements of this
Demand Response Services Code.
DRSC.11.3.1.2 Should the Demand Response Provider wish to modify the technical capability of the
Plant and Apparatus or Demand Unit(s) which it owns, operates, controls or manages
and which affects its compliance with the Ancillary Services agreement, it should notify
and agree any timescales for the change with The Company prior to making any change.
DRSC.11.3.1.3 Any operational incidents or failure of the Plant and Apparatus or Demand Unit(s)
owned, operated, controlled or managed by the Demand Response Provider which
impacts its ability to satisfy the compliance requirements detailed in this Demand
Response Services Code shall be notified to The Company as soon as possible after
occurrence of the incident.
DRSC.11.3.1.4 Any planned test schedules and procedures to verify compliance of the Plant and
Apparatus or Demand Unit(s) owned, operated, controlled or managed by the Demand
Response Provider shall be submitted to The Company in advance of the tests. The
Company shall assess the test schedules and procedures in a timely manner prior to
agreeing that the Demand Response Provider can carry out the tests.
DRSC.11.3.1.5 The Company may witness such tests and record the performance of the Plant and
Apparatus owned, operated, controlled or managed by the Demand Response
Provider to verify compliance with the Ancillary Services agreement and the Demand
Response Services Code.
DRSC.11.3.2.1 The Company shall assess the compliance of the Demand Response Provider and
shall undertake monitoring throughout the life time of the Plant and Apparatus or
Demand Unit(s) owned, operated, controlled or managed by the Demand Response
Provider to ensure compliance with the requirements of the Ancillary Services
agreement. The Company shall inform the Demand Response Provider of the
outcome of such assessment.
DRSC.11.3.2.2 The Company may require Demand Response Providers to carry out compliance
tests and simulations according to a repeat plan or general scheme or replacement of
equipment which may have an impact on the compliance of the Plant and Apparatus
or Demand Units owned, operated, controlled or managed by the Demand Response
Provider as detailed in DRSC.11.3.1.3 and DRSC.11.3.1.4. The Company shall
inform the Demand Response Provider of the results of these tests.
Issue 6 Revision 4 DRS 03 August 2021
6 of 11
DRSC.11.3.2.3 As part of this compliance process, the Demand Response Provider shall provide the
following items:-
(a) Relevant documentation and certificates associated with the compliance process.
(b) Details of the technical data required to ensure compliance with the Ancillary
Services agreement.
(c) Steady state and dynamic models (as applicable) of their Demand Units or Plant and
Apparatus (or equivalent) as required and agreed with The Company.
(d) Timelines for the submission of system data required to perform System studies.
(e) Study results showing the expected steady state and dynamic performance of the
Plant and Apparatus or Demand Unit(s) or the performance of their Demand
Response Service on an aggregated basis as required and agreed with The
Company.
(f) Submission of registered Equipment Certificates or otherwise as agreed with The
Company.
(g) Conditions and procedures for the use of relevant Equipment Certificates issued by
an Authorised Certifier to a Demand Response Provider or equivalent to the
satisfaction of The Company.
DRSC.11.3.2.4 If compliance tests or simulations cannot be carried out as agreed between the Demand
Response Provider and The Company due to reasons attributable to The Company, then
The Company shall not unreasonably withhold the Operational Notification referred to in
DRSC.11.2.3.
DRSC.11.4.1.1 The purpose of compliance testing is to ensure that the Plant and Apparatus or Demand
Unit(s) owned, operated, controlled or managed by a Demand Response Provider is
capable of satisfying the requirements of the Ancillary Services agreement and applicable
sections of this Demand Response Services Code in addition to verifying that the models
and data submitted provide a true and accurate representation of the Plant as built.
DRSC.11.4.1.2 Notwithstanding the minimum requirements for compliance testing detailed in DRSC.11.4 of
this Demand Response Services Code, The Company shall:-
(a) Allow the Demand Response Provider to carry out an alternative set of tests provided
that they are efficient and sufficient to demonstrate that the Plant and Apparatus or
Demand Unit(s) owned, operated, controlled or managed by a Demand Response
Provider is capable of satisfying the requirements of the Ancillary Services agreement
and the applicable sections of the Demand Response Services Code.
(b) Require the Demand Response Provider to carry out additional or alternative tests
(where reasonable) to those specified in DRSC.11.5 where they would otherwise be
insufficient to demonstrate compliance with the Ancillary Services agreement.
(c) Require the Demand Response Provider to be responsible for carrying out the tests
in accordance with the requirements specified in DRSC.11.4 and DRSC.11.5 of the
Demand Response Services Code. The Company shall cooperate with the Demand
Response Provider and will not unduly delay the scheduling of the tests.
DRSC.11.4.1.3 The Company may witness such tests (either on site or remotely from The Company’s
control room) to record the performance of the Demand Response Providers
Issue 6 Revision 4 DRS 03 August 2021
7 of 11
capability to verify compliance with the Ancillary Services agreement and the Demand
Response Services Code. Where The Company witnesses the tests remotely, the
Demand Response Provider shall provide the monitoring equipment necessary to
record all relevant test signals and measurements in addition to ensuring that necessary
representatives from the Demand Response Provider are available on site for the
entire testing period. Signals specified by The Company shall be provided, if for
selected tests, The Company wishes to use its own equipment to record performance.
The Company will inform the Demand Response Provider if it wishes to witness the
tests.
DRSC.11.5 Compliance Testing for Demand Response Providers with Demand Response Active
Power Control, Reactive Power Control and Transmission Constraint Management.
DRSC.11.5.1.1 Demand Response Providers who have signed an Ancillary Services agreement
with The Company to provide Demand Response Active Power Control, Demand
Response Reactive Power Control or Demand Response Transmission
Constraint Management, are required to demonstrate (through site tests) the
capability of the Plant and Apparatus or Demand Unit(s) they own, operate, control
or manage to satisfy the requirements of the Ancillary Services agreement and the
applicable requirements of DRSC.5. The site tests should demonstrate the capability
of the Demand Response Providers ability to operate with instruction over the agreed
timeframes, Demand range and duration pursuant to the terms of the Ancillary
Services agreement. The tests can be completed individually or as part of a Demand
aggregation scheme.
DRSC.11.5.1.2 The tests shall be carried out either by instruction from The Company’s Control Centre
or by site tests through injections applied to the Plant and Apparatus or Demand
Unit(s) owned, operated, controlled or managed by the Demand Response Provider.
DRSC.11.5.1.3 The test shall be deemed as passed if the requirements of the Ancillary Services
agreement have been satisfied and the applicable requirements of DRSC.5
demonstrated to the satisfaction of The Company.
DRSC.11.5.2.1 Demand Response Providers who have signed an Ancillary Services agreement
with The Company to provide Demand Response Active Power Control, Demand
Response Reactive Power Control or Demand Response Transmission
Constraint Management and have also agreed to disconnect or reconnect (or both)
static compensation facilities when receiving an instruction from The Company in
accordance with the requirements of the Ancillary Services agreement and DRSC.5.3,
shall be required to demonstrate the performance of the Plant and Apparatus or
Demand Unit(s) they own, operate, control or manage to satisfy these requirements.
These requirements can be demonstrated individually or collectively as part of a
demand aggregation scheme.
DRSC.11.5.2.2 The tests shall be carried out either by instruction from The Company’s Control Centre
or by site tests resulting in the disconnection and subsequent re-connection of the static
compensation facilities.
DRSC.11.5.2.3 The test shall be deemed as passed if the requirements of the Ancillary Services agreement
have been satisfied and the applicable requirements of DRSC.5.3 demonstrated to the
satisfaction of The Company.
Issue 6 Revision 4 DRS 03 August 2021
8 of 11
DRSC.11.6 Compliance Simulation
DRSC.11.6.1.1 Demand Response Providers who agree to provide Demand Response Very Fast Active
Power Control are required to demonstrate their ability to satisfy the requirements of the
Ancillary Services agreement and DRSC.7 through necessary simulation studies to the
satisfaction of The Company.
DRSC.11.6.1.2 Demand Response Providers who have contracted to provide a Demand Response Very
Fast Active Power Control service, are required to submit further simulation studies where
there has been a development, replacement or modernisation of the Plant and Apparatus or
Demand Unit(s)_ owned, operated, controlled or managed by the Demand Response
Provider, or The Company has identified a non–compliance with the Demand Response
Provider’s ability to satisfy the requirements of the Ancillary Services agreement or
DRSC.7.
DRSC.11.6.1.3 Notwithstanding the requirements of DRSC.11.6.1.1 and DRSC.11.6.1.2 The Company shall
be entitled to:-
(a) Allow the Demand Response Provider to carry out an alternative set of simulations
provided that they are efficient and sufficient to demonstrate that the Plant and Apparatus
or Demand Unit(s) owned, operated, controlled or managed by the Demand Response
Provider is capable of satisfying the requirements of the Ancillary Services agreement
and the applicable sections of the Demand Response Services Code.
(b) Require the Demand Response Provider to carry out additional or alternative
simulations to those specified in DRSC11.6.1.1 and DRSC.11.6.1.28 where they would
otherwise be insufficient to demonstrate compliance with the Ancillary Services
agreement.
DRSC.11.6.1.4 The Company may check that the Demand Response Provider complies with the
requirements of the Ancillary Services agreement and the applicable sections of the
Demand Response Services Code by carrying out its own compliance simulations based on
the simulation reports, models and test measurements.
DRSC.11.6.1.5 The Company will supply upon request from the Demand Response Provider, data to enable
the Demand Response Provider to carry out the required simulations in accordance with the
requirements of the Ancillary Services agreement and DRSC.11.6.
DRSC.11.7 Additional Testing requirements for Non-Embedded Customers and CUSC Parties who are also
Demand Response Providers
DRSC.11.7.1 Non-Embedded Customers and CUSC Parties who are also Demand Response
Providers shall be required to execute a demand modification test after two consecutive
unsuccessful responses in the operational environment or at least every year as agreed
with The Company.
DRSC.11.7.2 Each Non-Embedded Customer and CUSC Party who are also Demand Response
Providers and provide demand response low frequency demand disconnection shall execute a
low frequency demand disconnection test at least once every three years.
Compliance Requirements
DRSC Requirement Compliance Demand Response Provider
Y/N Statement
Declaration
I declare that for all the Demand Response Provider’s information associated with this contract:
1. Compliance with the requirements of the Demand Response Services Code is achieved.
2. The commissioning checks have been successfully completed.
Name:
Signature:
Company Name:
Position:
I confirm that I have witnessed the commissioning checks in this document on behalf of
____________________________ and that the results are an accurate record of the checks
Name:
Signature:
Company Name:
CONTENTS
(This contents page does not form part of the Grid Code)
CP.2 OBJECTIVE
CP.2.1 The objective of the CP is to ensure that there is a clear and consistent process for
demonstration of compliance by GB Code Users with the Connection Conditions and
Bilateral Agreement which are similar for all GB Code Users of an equivalent category and
will enable The Company to comply with its statutory and Transmission Licence
obligations.
CP.2.2 Provisions of the CP which apply in relation to OTSDUW and OTSUA shall (in any particular
case) apply up to the OTSUA Transfer Time, whereupon such provisions shall (without
prejudice to any prior non-compliance) cease to apply.
CP.2.3 In relation to OTSDUW, provisions otherwise to be contained in a Bilateral Agreement may
be contained in the Construction Agreement, and accordingly a reference in the CP to a
relevant Bilateral Agreement includes the relevant Construction Agreement.
CP.3 SCOPE
CP.3.1 The CP applies to The Company and to GB Code Users, which in the CP means:
(a) GB Generators (other than in relation to Embedded Small Power Stations or
Embedded Medium Power Stations not subject to a Bilateral Agreement) including
those undertaking OTSDUW.
(b) Network Operators;
(c) Non-Embedded Customers;
(d) DC Converter Station owners (other than those which only have Embedded DC
Converter Stations not subject to a Bilateral Agreement).
CP.8.1 No later than 4 calendar years and 6 months after the issue of a Final Operational
Notification, The Company will notify the Generator or DC Converter Station owner that
confirmation of continued compliance with the requirements of the Grid Code and/or the
Bilateral Agreement is required.
CP.8.2 No later than 5 calendar years after the issue of a Final Operational Notification the
Generator or DC Converter Station owner shall confirm that the Plant and/or Apparatus
(including OTSUA if applicable) is fully compliant with the requirements of the Grid Code
and/or the Bilateral Agreement. The confirmation of compliance will include:
(a) a Compliance Statement and a User Self Certification of Compliance signed by the
GB Code User and a statement of any requirements that the Generator or DC
Converter Station owner has identified that have not been met together with a copy of
the derogation in respect of the same from the Authority.
(b) complete set of relevant Planning Code data (both Standard Planning Data and
Detailed Planning Data), with validated actual values and updated estimates for the
future including Forecast Data items such as Demand. Simulation studies and results
from tests detailed in Appendix CP.A.3 and OC5 are not required as part of the
Compliance Repeat Plan.
The process illustrated in CP.A.1.1 applies to all GB Code Users energising passive network Plant and
Apparatus including Distribution Network Operators, Non-Embedded Customers, Generators and DC
Converter Station owners. This process is a subset of the full process for Generators and DC Converter
Station owners shown in CP.A.1.2. This diagram illustrates the process in the CP and includes references in
brackets to specific Grid Code clauses.
This diagram illustrates the process in the CP and includes references in brackets to specific Grid Code
clauses. For the avoidance of doubt this process does not apply to Embedded Medium Power Stations not
subject to a Bilateral Agreement and Embedded DC Converter Stations not subject to a Bilateral
Agreement.
This diagram illustrates the process in the CP and includes references in brackets to specific Grid Code
clauses.
This diagram illustrates the process in the CP and includes references in brackets to specific Grid Code
clauses. For the avoidance of doubt this process does not apply to Embedded Medium Power Stations not
subject to a Bilateral Agreement and Embedded DC Converter Stations not subject to a Bilateral
Agreement.
This diagram illustrates the process in the CP and includes references in brackets to specific Grid Code
clauses. For the avoidance of doubt this process does not apply to Embedded Medium Power Stations not
subject to a Bilateral Agreement and Embedded DC Converter Stations not subject to a Bilateral
Agreement.
Power Station/ DC
[Name of Connection Site/site of connection]
Converter Station:
OTSUA [Name of Interface Site]
This User Self Certification of Compliance records the compliance by the GB Code User in respect of
[NAME] Power Station/DC Converter Station [and, in the case of OTSDUW Arrangements, OTSUA] with
the Grid Code and the requirements of the Bilateral Agreement and Construction Agreement dated [ ]
with reference number [ ]. It is completed by the Power Station/DC Converter Station owner in the case of
Plant and/or Apparatus (including OTSUA) connected to the National Electricity Transmission System
and for Embedded Plant.
We have recorded our compliance against each requirement of the Grid Code which applies to the Power
Station/DC Converter Station/OTSUA, together with references to supporting evidence and a commentary
where this is appropriate, and have provided this to The Company. A copy of the Compliance Statement is
attached.
Supporting evidence, in the form of simulation results, test results, manufacturer’s data and other
documentation, is attached in the User Data File Structure.
The GB Code User hereby certifies that, to the best of its knowledge and acting in accordance with Good
Industry Practice, [the Power Station is compliant with the Grid Code and the Bilateral Agreement] [the
OTSUA is compliant with the Grid Code and the Construction Agreement] in all aspects [with the following
Unresolved Issues*] [with the following derogation(s)**]:
Connection
Requirement Ref: Issue
Condition
* Include for Interim User Self Certification of Compliance ahead of Interim Operational Notification.
** Include for final User Self Certification of Compliance ahead of Final Operational Notification where derogation(s) have been granted.
If no derogation(s) required delete wording and Table.
CP.A.3.3.4 In the case of a Power Park Module where the load flow simulation studies show that the
individual Power Park Units deviate from nominal voltage to meet the Reactive Power
requirements, then evidence must be provided from factory (e.g. in a Manufacturer’s Data
& Performance Report) or site testing that the Power Park Unit is capable of operating
continuously at the operating points determined in the load flow simulation studies.
CP.A.3.4 Voltage Control and Reactive Power Stability
CP.A.3.4.1 In the case of a Power Station containing Power Park Modules and/or OTSUA the
Generator shall provide a report to demonstrate the dynamic capability and control stability
of the Power Park Module. The report shall contain:
(i) a dynamic time series simulation study result of a sufficiently large negative step in
System voltage to cause a change in Reactive Power from zero to the maximum
lagging value at Rated MW.
(ii) a dynamic time series simulation study result of a sufficiently large positive step in
System voltage to cause a change in Reactive Power from zero to the maximum
leading value at Rated MW.
(iii) a dynamic time series simulation study result to demonstrate control stability at the
lagging Reactive Power limit by application of a -2% voltage step while operating within
5% of the lagging Reactive Power limit.
(iv) a dynamic time series simulation study result to demonstrate control stability at the
leading Reactive Power limit by application of a +2% voltage step while operating
within 5% of the leading Reactive Power limit.
(v) a dynamic time series simulation study result of a sufficiently negative step in System
voltage to cause a change in Reactive Power from the maximum leading value to the
maximum lagging value at Rated MW.
The Generator should also provide the voltage control study specified in CP.A.3.7.4.
CP.A.3.4.2 All the above studies should be completed with a nominal network voltage for zero Reactive
Power transfer at the Grid Entry Point or User System Entry Point if Embedded or, in the
case of OTSUA, Interface Point unless stated otherwise and the fault level at the HV
connection point at minimum as agreed with The Company.
CP.A.3.4.3 The Company may permit relaxation from the requirements of CP.A.3.4.1(i) and (ii) for
voltage control if the Power Park Modules are comprised of Power Park Units in respect of
which the GB Code User has in its submissions to The Company, referenced an
appropriate Manufacturer’s Data & Performance Report which is acceptable to The
Company for voltage control.
CP.A.3.4.4 In addition, The Company may permit a further relaxation from the requirements of
CP.A.3.4.1(iii) and (iv) if the GB Code User has in its submissions to The Company
referenced an appropriate Manufacturer’s Data & Performance Report for a Power Park
Module mathematical model for voltage control acceptable to The Company.
CP.A.3.5 Fault Ride Through
CP.A.3.5.1 The Generator, (including where undertaking OTSDUW) or DC Converter Station owner
shall supply time series simulation study results to demonstrate the capability of Non-
Synchronous Generating Units, DC Converters, Power Park Modules and OTSUA to
meet CC.6.3.15 by submission of a report containing:
CP.A.3.5.5 In the case of a Power Park Module with a Registered Capacity greater or equal to
100MW, the studies detailed in CP.A.3.5.1 should be repeated with 50% of the Power Park
Units Synchronised to the Total System. In the case of a Power Station containing
multiple Power Park Modules or multiple Offshore Power Park Modules connected to an
Offshore Transmission System or OTSDUW the study should include all Power Park
Modules with 50% of the Power Park Units Synchronised to the Total System.
CP.A.3.5.6 In the case of DC Networks the studies detailed in CP.A.3.5.1 should be repeated to
demonstrate compliance during foreseeable running arrangements resulting from outages of
major Plant and Apparatus (for example outage of an HVDC cable or converter). For these
conditions, the DC Converter Active Power transfer may be reduced to levels appropriate
to the planned operating regime. The Generator or DC Converter Station Owner shall
consult The Company on alternative running arrangements and agree with The Company
the running arrangements that will be studied prior to the DC Converter Station Owner
undertaking the studies. For the avoidance of doubt, compliance of DC Converter Station
with Fault Ride Through requirements remains the responsibility of the DC Converter
Station Owner under all operating conditions.
CP.A.3.6.5 The simulation study shall be performed for both control modes, Frequency Sensitive
Mode (FSM) and Limited Frequency Sensitive Mode (LFSM). The simulation study results
should indicate Active Power and Frequency in the island system that includes the
Generating Unit, DC Converter or Power Park Module.
CP.A.3.6.6 To allow validation of the model used to simulate load rejection in accordance with
CC.6.3.7(c)(i) as described, a further simulation study is required to represent the largest
positive Frequency injection step or fast ramp (BC1 and BC3 of Figure 2) that will be applied
as a test as described in OC5.A.2.8 and OC5.A.3.6.
CP.A.3.7 Voltage and Frequency Controller Model Verification and Validation
Figure CP.A.3.7.2
The simulation study shall show Active Power output (MW) and the equivalent of
Frequency injected.
CP.A.3.7.3 To demonstrate the Excitation System model the Generator shall submit simulation studies
representing the response of the Synchronous Generating Unit as follows:
(i) operating open circuit at rated terminal voltage and subjected to a 2% step increase in
terminal voltage reference.
(ii) operating at Rated MW, nominal terminal voltage and unity Power Factor subjected to
a 2% step increase in the voltage reference. Where a Power System Stabiliser is
included within the Excitation System this shall be in service.
The simulation study shall show the terminal voltage, field voltage of the Generating Unit,
Active Power, Reactive Power and Power System Stabiliser output signal as appropriate.
CONTENTS
(This contents page does not form part of the Grid Code)
ECP
Page 1 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 6 69
COMPLIANCE TESTING OF POWER PARK MODULES ............................................. 69
APPENDIX 7 82
COMPLIANCE TESTING FOR HVDC EQUIPMENT ..................................................... 82
APPENDIX 8 92
SIMULATION STUDIES AND COMPLIANCE TESTING FOR NETWORK OPERATORS
AND NON-EMBEDDED CUSTOMERS PLANT AND APPARATUS ....... 92
ECP
Page 2 of 99
Issue 6 Revision 17 04 September 2023
EUROPEAN COMPLIANCE PROCESSES
ECP.1 INTRODUCTION
ECP
Page 3 of 99
Issue 6 Revision 17 04 September 2023
OTSUA, the OTSUA Transfer Time) when changes or
Modifications are made.
ECP.1.3 Where a Generator or HVDC System Owner and/or The Company are
required to apply for a derogation to the Authority, this is not in respect of
OTSUA.
ECP.2 OBJECTIVE
ECP.2.1 The objective of the ECP is to ensure that there is a clear and consistent
process for demonstration of compliance by Users with the European
Connection Conditions and Bilateral Agreement and will enable The
Company to comply with its statutory and Transmission Licence
obligations. For the avoidance of doubt, the requirements of the European
Compliance Processes do not apply to Demand Response Providers
unless they are also an EU Code User and have entered into a CUSC
Contract with The Company.
ECP.2.2 Provisions of the ECP which apply in relation to OTSDUW and OTSUA shall
(in any particular case) apply up to the OTSUA Transfer Time, whereupon
such provisions shall (without prejudice to any prior non-compliance) cease
to apply.
ECP
Page 4 of 99
Issue 6 Revision 17 04 September 2023
ECP.2.3 In relation to OTSDUW, provisions otherwise to be contained in a Bilateral
Agreement may be contained in the Construction Agreement, and
accordingly a reference in the ECP to a relevant Bilateral Agreement
includes the relevant Construction Agreement.
ECP.3 SCOPE
ECP.3.1 The ECP applies to The Company and to Users, which in the ECP means:
(d) HVDC System Owners (other than those which only have
Embedded HVDC Systems not subject to a Bilateral Agreement).
(e) Grid Forming Plant Owners who own and operate a Grid Forming
Plant and intend to satisfy the requirements of ECC.6.3.19
ECP.3.2 The above categories of User will become bound by the ECP prior to them
generating, distributing, supplying or consuming, or in the case of OTSUA,
transmitting, as the case may be, and references to the various categories
should, therefore, be taken as referring to them in that prospective role.
ECP.3.3 For the avoidance of doubt, Demand Response Providers do not need to
satisfy the requirements of this ECP unless they are also defined as an EU
Code User and have a CUSC Contract with The Company. Where a
Demand Response Provider is not an EU Code User and does not have a
CUSC Contract with The Company, the requirements of the Demand
Response Services Code shall only apply.
ECP.3.4 For the avoidance of doubt, this ECP does not apply to GB Code Users other
than in respect of Network Operator’s EU Grid Supply Points.
ECP.4.1 The CUSC Contract(s) contain certain provisions relating to the procedure
for connection to the National Electricity Transmission System or, in the
case of Embedded Power Stations or Embedded HVDC Systems,
becoming operational and include provisions to be complied with by Users
prior to and during the course of The Company notifying the User that it has
the right to become operational. In addition to such provisions, this ECP sets
out in further detail the processes to be followed to demonstrate compliance.
While this ECP does not expressly address the processes to be followed in
the case of OTSUA connecting to a Network Operator’s User System prior
to OTSUA Transfer Time, the processes to be followed by The Company
and the Generator in respect of the OTSUA in such circumstances shall be
ECP
Page 5 of 99
Issue 6 Revision 17 04 September 2023
consistent with those set out below by reference to OTSUA directly
connected to the National Electricity Transmission System.
ECP.4.2 The provisions contained in ECP.5 to ECP.7 detail the process to be followed
in order for the User’s Plant and Apparatus (including OTSUA) to become
operational. This process includes
(iv) for operating by using the Grid Supply Point an ION for;
ECP.4.2.1 The provisions contained in ECP.5 relate to the connection and energisation
of User’s Plant and Apparatus (including OTSUA) to the National
Electricity Transmission System or where Embedded, to a User’s
System.
ECP.4.2.2 The provisions contained in ECP.6 and ECP.7 provide the process for
Generators, HVDC System Owners, Grid Forming Plant Owners,
Network Operators and Non-Embedded Customers to demonstrate
compliance with the Grid Code and with, where applicable, the CUSC
Contract(s) prior to and during the course of such Generator’s, HVDC
System Owner’s (including OTSUA up to the OTSUA Transfer Time),
Network Operator’s and Non-Embedded Customer’s Plant and
Apparatus) becoming operational.
ECP.4.2.3 The provisions contained in ECP.8 detail the process to be followed to confirm
continued compliance (the “Compliance Repeat Plan”).
ECP.4.2.4 The provisions contained in ECP.9 detail the process to be followed when:
(a) a Generator’s or HVDC System Owner’s, or Grid Forming Plant
Owner’s, or Network Operator’s or Non-Embedded Customer’s
Plant and/or Apparatus (including the OTSUA) is unable to comply
with any provisions of the Grid Code and Bilateral Agreement; or,
(b) following any notification by a Generator or a HVDC System Owner
or a Grid Forming Plant Owner or a Network Operator or a Non-
Embedded Customer under the PC of any change to its Plant and
Apparatus (including any OTSUA); or,
(c) a Modification to a Generator’s or a HVDC System Owner’s or a
Grid Forming Plant Owner’s or a Network Operator’s or a Non-
Embedded Customer’s Plant and/or Apparatus.
ECP
Page 6 of 99
Issue 6 Revision 17 04 September 2023
ECP.4.2.4 For Grid Forming Plant Owners, the Operational Notification Process of
this ECP shall apply in relation to the type of Plant to which the Grid Forming
Capability is provided (be it a GBGF-S or GBGF-I),
ECP.4.3.1 In the case of Embedded Medium Power Stations not subject to a Bilateral
Agreement and Embedded HVDC Systems not subject to a Bilateral
Agreement, ensuring the obligations of the ECC and Appendix E of the
relevant Bilateral Agreement between The Company and the host Network
Operator are performed and discharged by the relevant party. For the
avoidance of doubt the process in this ECP does not apply to Embedded
Medium Power Stations not subject to a Bilateral Agreement and
Embedded HVDC Equipment not subject to a Bilateral Agreement.
ECP.5.1.1 Certain provisions relating to the connection and energisation of the User’s
Plant and Apparatus at the Connection Site and OTSUA at the
Transmission Interface Point and in certain cases of Embedded Plant and
Apparatus are specified in the CUSC and/or CUSC Contract(s). For other
Embedded Plant and Apparatus, the Distribution Code, the DCUSA and
the Embedded Development Agreement for the connection specify
equivalent provisions. Further detail on this is set out in ECP.5 below.
ECP.5.2 The items for submission prior to the issue of an Energisation Operational
Notification are set out in ECC.5.2.
ECP.5.3 In the case of a Generator or HVDC System Owner the items referred to in
ECC.5.2 shall be submitted using the Power Generating Module Document
or User Data File Structure as applicable.
ECP.5.4 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the User wishing to energise its
Plant and Apparatus (including passive OTSUA) for the first time, the User
will submit to The Company a Certificate of Readiness to Energise High
Voltage Equipment which specifies the items of Plant and Apparatus
(including OTSUA) ready to be energised in a form acceptable to The
Company.
ECP.5.5 If the relevant obligations under the provisions of the CUSC and/or CUSC
Contract(s) and the conditions of ECP.5 have been completed to The
Company’s reasonable satisfaction then The Company shall issue an
Energisation Operational Notification. Any dynamically controlled reactive
compensation OTSUA (including Statcoms or Static Var Compensators) shall
not be Energised until the appropriate Interim Operational Notification has
been issued in accordance with ECP.6.
ECP
Page 7 of 99
Issue 6 Revision 17 04 September 2023
ECP.6.1.1 The following provisions apply in relation to the notification process in in
respect of a Power Station consisting of Type A Power Generating
Modules.
ECP.6.1.2 Not less than 7 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator wishing to
Synchronise its Plant and Apparatus for the first time, the Generator will:
(viii) The contact details of the Generator and the installer and their
signatures.
ECP.6.1.3.2 The items referred to in ECP.6.1.3 shall be submitted by the Generator in the
form of an Installation Document for each applicable Power Generating
Module.
ECP
Page 8 of 99
Issue 6 Revision 17 04 September 2023
ECP.6.1.5 When the requirements of ECP.6.1.2 to ECP.6.1.4 have been met, The
Company will notify the Generator that the Power Generating Module may
(subject to the Generator having fulfilled the requirements of ECP.6.1.3
where that applies) be Synchronised to the Total System.
ECP.6.1.6 Not less than 7 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator wishing to
decommission its Plant and Apparatus, the Generator will submit to The
Company a Notification of User’s Intention to Disconnect.
ECP.6.2.2 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator wishing to
Synchronise its Plant and Apparatus or dynamically controlled OTSUA for
the first time the Generator or HVDC Equipment owner will:
ECP.6.2.3 Items for submission prior to issue of the Interim Operational Notification.
(i) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data), with any estimated values assumed for
planning purposes confirmed or, where practical, replaced by
validated actual values and by updated estimates for the future and
by updated forecasts for Forecast Data items such as Demand;
PC.A.5.4.2
PC.A.5.4.3.2,
ECC.6.3.4,
ECC.6.3.7.3.1 to ECC.6.3.7.3.6,
ECC.6.3.15, ECC.6.3.16
ECC.A.6.2.5.6
ECC.A.7.2.3.1
ECP
Page 9 of 99
Issue 6 Revision 17 04 September 2023
as applicable to the Power Generating Module(s) or dynamically
controlled OTSUA unless agreed otherwise by The Company;
(v) a detailed schedule of the tests and the procedures for the tests
required to be carried out by the Generator under ECP.7.2 to
demonstrate compliance with relevant Grid Code requirements.
Such schedule to be consistent with Appendix ECP.A.5 (in the case
of a Synchronous Power Generating Module) or Appendix
ECP.A.6 (in the case of a Power Park Modules) and OTSUA as
applicable);
ECP.6.2.3.2 The items referred to in ECP.6.2.3 shall be submitted by the Generator in the
form of a Power Generating Module Document (PGMD) for each applicable
Power Generating Module.
(i) those tests required to establish the open and short circuit
saturation characteristics of the Synchronous Power
Generating Module (as detailed in Appendix ECP.A.4.3) to
enable assessment of the short circuit ratio in accordance
with ECC.6.3.2. Such tests may be carried out at a location
other than the Power Station site and supplied in the form of
an Equipment Certificate or as otherwise agreed by The
Company; and
ECP.6.2.5 The Company shall assess the schedule of tests submitted by the Generator
with the Notification of User’s Intention to Synchronise under ECP.6.2.3
and shall determine whether such schedule has been completed to The
Company’s satisfaction.
ECP.6.2.6 When the requirements of ECP.6.2.2 to ECP.6.2.5 have been met, The
Company will notify the Generator that the:
ECP
Page 10 of 99
Issue 6 Revision 17 04 September 2023
Synchronous Power Generating Module,
CCGT Module,
Power Park Module or
Dynamically controlled OTSUA
ECP.6.2.6.1 The Interim Operational Notification will be time limited, the expiration date
being specified at the time of issue. The Interim Operational Notification
may be renewed by The Company.
ECP.6.2.6.2 The Generator must operate the Power Generating Module or OTSUA in
accordance with the terms, arising from the Unresolved Issues, of the
Interim Operational Notification. Where practicable, The Company will
discuss such terms with the Generator prior to including them in the Interim
Operational Notification.
ECP.6.2.6.3 The Interim Operational Notification will include the following limitations:
(i) 20% of the Maximum Capacity of the Power Park Module (or
the output of a single Power Park Unit where this exceeds 20%
of the Power Station’s Maximum Capacity)
until the Generator has completed the voltage control tests (detailed
in ECP.A.6.2) (including in respect of any dynamically controlled
OTSUA) to The Company’s reasonable satisfaction. Following
successful completion of this test each additional Power Park Unit
should be included in the voltage control scheme as soon as is
technically possible (unless The Company agrees otherwise).
ECP
Page 11 of 99
Issue 6 Revision 17 04 September 2023
maximum Active Power output and Reactive Power output of the
Synchronous Power Generating Module or CCGT module prior to
the successful commissioning of the Power System Stabiliser to The
Company’s satisfaction, if applicable.
ECP.6.2.7 Other than Unresolved Issues that are subject to tests required under
ECP.7.2 to be witnessed by The Company, the Generator must resolve any
Unresolved Issues prior to the commencement of the tests, unless The
Company agrees to a later resolution. The Generator must liaise with The
Company in respect of such resolution. The tests that may be witnessed by
The Company are specified in ECP.7.2.
ECP.6.2.8 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator wishing to
commence tests required under ECP.7 to be witnessed by The Company,
the Generator will notify The Company that the Power Generating
Module(s) as applicable is ready to commence such tests.
ECP.6.2.9 The items referred to at ECP.7.3 shall be submitted by the Generator after
successful completion of the tests required under ECP.7.2.
ECP.6.3.2 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator or HVDC System
Owner wishing to Synchronise its Plant and Apparatus or dynamically
controlled OTSUA for the first time the Generator or HVDC System Owner
will:
ECP.6.3.3 Items for submission prior to issue of the Interim Operational Notification.
(a) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data), with any estimated values assumed for
planning purposes confirmed or, where practical, replaced by
validated actual values and by updated estimates for the future and
by updated forecasts for Forecast Data items such as Demand;
ECP
Page 12 of 99
Issue 6 Revision 17 04 September 2023
(c) any items required by ECP.5.2, updated by the EU Code User as
necessary;
PC.A.5.4.2
PC.A.5.4.3.2,
ECC.6.3.4,
ECC.6.3.7.3.1 to ECC.6.3.7.3.6,
ECC.6.3.15, ECC.6.3.16
ECC.A.6.2.5.6
ECC.A.7.2.3.1
(e) a detailed schedule of the tests and the procedures for the tests
required to be carried out by the Generator or HVDC System Owner
under ECP.7.2 to demonstrate compliance with relevant Grid Code
requirements. Such schedule to be consistent with Appendix
ECP.A.5 (in the case of Synchronous Power Generating Modules)
or Appendix ECP.A.6 (in the case of Power Park Modules and
OTSUA as applicable) or Appendix ECP.A.7 (in the case of HVDC
Equipment; and
ECP
Page 13 of 99
Issue 6 Revision 17 04 September 2023
(i) those tests required to establish the open and short circuit
saturation characteristics of the Synchronous Power
Generating Module (as detailed in Appendix ECP.A.5.3) to
enable assessment of the short circuit ratio in accordance
with ECC.6.3.2. Such tests may be carried out at a location
other than the Power Station site; and
ECP.6.3.5 The Company shall assess the schedule of tests submitted by the Generator
or HVDC System Owner with the Notification of User’s Intention to
Synchronise under ECP.6.3.1 and shall determine whether such schedule
has been completed to The Company’s satisfaction.
ECP.6.3.6 When the requirements of ECP.6.3.2 to ECP.6.3.5 have been met, The
Company will notify the Generator or HVDC System Owner that the:
Synchronous Power Generating Module,
CCGT Module,
Power Park Module
Dynamically controlled OTSUA or
HVDC Equipment,
ECP.6.3.6.1 The Interim Operational Notification will be time limited, the expiration date
being specified at the time of issue. The Interim Operational Notification
may be renewed by The Company for up to a maximum of 24 months from
the date of the first issue of the Interim Operational Notification. The
Company may only issue an extension to an Interim Operational
Notification beyond 24 months provided the Generator or HVDC System
Owner has applied for a derogation for any remaining Unresolved Issues
to the Authority as detailed in ECP.10.
ECP.6.3.6.2 The Generator or HVDC System Owner must operate the Power
Generating Module or HVDC Equipment in accordance with the terms,
arising from the Unresolved Issues, of the Interim Operational
Notification. Where practicable, The Company will discuss such terms with
the Generator or HVDC System Owner prior to including them in the
Interim Operational Notification.
ECP.6.3.6.3 The Interim Operational Notification will include the following limitations:
ECP
Page 14 of 99
Issue 6 Revision 17 04 September 2023
Total System only for the purposes of active control of voltage and
Reactive Power and not for the purpose of exporting Active Power.
(ii) 50MW
until the Generator has completed the voltage control tests (detailed
in ECP.A.6.3.2) to The Company’s reasonable satisfaction. Following
successful completion of this test, each additional Power Park Unit
should be included in the voltage control scheme as soon as is
technically possible (unless The Company agrees otherwise).
ECP.6.3.7 Other than Unresolved Issues that are subject to tests required under
ECP.7.2 to be witnessed by The Company, the Generator or HVDC System
Owner must resolve any Unresolved Issues prior to the commencement of
the tests, unless The Company agrees to a later resolution. The Generator
or HVDC System Owner must liaise with The Company in respect of such
resolution. The tests that may be witnessed by The Company are specified
in ECP.7.2.
ECP.6.3.8 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator or HVDC System
Owner wishing to commence tests required under ECP.7 to be witnessed by
The Company, the Generator or HVDC System Owner will notify The
ECP
Page 15 of 99
Issue 6 Revision 17 04 September 2023
Company that the Power Generating Module(s) or HVDC Equipment(s)
as applicable is ready to commence such tests.
ECP.6.3.9 The items referred to at ECP.7.3 shall be submitted by the Generator or the
HVDC System Owner after successful completion of the tests required under
ECP.7.2.
ECP.6.4.2 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Network Operator or Non-
Embedded Customer wishing to operate its Plant and Apparatus by using
the EU Grid Supply Point for the first time, the Network Operator or Non-
Embedded Customer will:
ECP.6.4.3 Items for submission prior to issue of the Interim Operational Notification.
(a) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data), with any estimated values assumed for
planning purposes confirmed or, where practical, replaced by
validated actual values and by updated estimates for the future and
by updated forecasts for Forecast Data items such as Demand;
PC.A.2.2
PC.A.2.3
PC.A.2.4
PC.A.2.5.2
PC.A.2.5.3
PC.A.2.5.4
PC.A.2.5.6
PC.A.4
PC.A.6.1.3
PC.A.6.3
PC.A.6.7.1
ECP
Page 16 of 99
Issue 6 Revision 17 04 September 2023
(e) a detailed schedule of the tests and the procedures for the tests
required to be carried out by the Network Operator or Non-
Embedded Customer under ECP.7.8 (or Equipment Certificates
as relevant) to demonstrate compliance with relevant Grid Code
requirements. Such schedule is to be consistent with Appendix
ECP.A.8.
ECP.6.4.5 The Company shall assess the schedule of tests submitted by the Network
Operator or Non-Embedded Customer with the Notification of User’s
Intention to Operate under ECP.6.4.1 and shall determine whether such
schedule has been completed to The Company’s satisfaction.
ECP.6.4.6 When the requirements of ECP.6.4.2 to ECP.6.4.5 have been met, The
Company will notify the Network Operator or Non-Embedded Customer
that the Plant and Apparatus may (subject to the Network Operator or Non-
Embedded Customer having fulfilled the requirements of ECP.6.4.3 where
that applies) be operated by using the EU Grid Supply Point through the
issue of an Interim Operational Notification.
ECP.6.4.6.1 The Interim Operational Notification will be time limited, the expiration date
being specified at the time of issue. The Interim Operational Notification
may be renewed by The Company for up to a maximum of 24 months from
the date of the first issue of the Interim Operational Notification. The
Company may only issue an extension to an Interim Operational
Notification beyond 24 months provided the Network Operator or Non-
Embedded Customer has applied for a derogation for any remaining
Unresolved Issues to the Authority as detailed in ECP.10.
ECP.6.4.8 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Network Operator or Non-
Embedded Customer wishing to commence tests required under
ECP.7.8(e) and ECP.A.8 to be witnessed by The Company the Network
Operator or Non-Embedded Customer will notify The Company that the
Network Operator or Non-Embedded Customer as applicable is ready to
commence such tests.
ECP
Page 17 of 99
Issue 6 Revision 17 04 September 2023
ECP.7 FINAL OPERATIONAL NOTIFICATION
ECP.7.1 The following provisions apply in relation to the issue of a Final Operational
Notification in respect of a Power Station consisting of Type B, Type C and
Type D Power Generating Modules or an HVDC System.
ECP.7.2 Tests to be carried out prior to issue of the Final Operational Notification.
ECP.7.2.2 In the case of any Power Generating Module, OTSUA (if applicable) or
HVDC Equipment these tests will reflect the relevant technical requirements
and will comprise one or more of the following:
ECP
Page 18 of 99
Issue 6 Revision 17 04 September 2023
(e) any further tests reasonably required by The Company and agreed
with the EU Code User to demonstrate any aspects of compliance
with the Grid Code and the CUSC Contracts.
ECP.7.2.3 The Company’s preferred range of tests to demonstrate compliance with the
ECCs are specified in Appendix ECP.A.5 (in the case of Synchronous
Power Generating Modules) or Appendix ECP.A.6 (in the case of a Power
Park Modules or OTSUA (if applicable)) or Appendix ECP.A.7 (in the case
of HVDC Equipment and are to be carried out by the EU Code User with the
results of each test provided to The Company. The EU Code User may carry
out an alternative range of tests if this is agreed with The Company. The
Company may agree a reduced set of tests where there is a relevant
Manufacturers Data & Performance Report as detailed in ECP.10 or an
applicable Equipment Certificate has been accepted.
ECP.7.2.4 In the case of Offshore Power Park Modules which do not contribute to
Offshore Transmission Licensee Reactive Power capability as described
in ECC.6.3.2.5 or ECC.6.3.2.6 or Voltage Control as described in
ECC.6.3.8.5 the tests outlined in ECP.7.2.2 (a) and ECP.7.2.2 (b) are not
required. However, the offshore Reactive Power transfer tests outlined in
ECP.A.5.8 shall be completed in their place.
ECP.7.2.5 Following completion of each of the tests specified in this ECP.7.2, The
Company will notify the Generator or HVDC System Owner whether, in the
opinion of The Company, the results demonstrate compliance with the
relevant Grid Code conditions. When the Generator or HVDC System
Owner submits test results to The Company, the Generator or HVDC
System Owner may request The Company to advise when the notification
is expected to be provided. The Company should not unduly delay the
notification.
ECP.7.2.6 The Generator or HVDC System Owner is responsible for carrying out the
tests and retains the responsibility for safety and personnel during the test.
ECP.7.3 Items for submission prior to issue of the Final Operational Notification
(a) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data), with validated actual values and updated
estimates for the future including Forecast Data items such as
Demand;
ECP
Page 19 of 99
Issue 6 Revision 17 04 September 2023
(e) results from the tests required in accordance with ECP.7.2 carried
out by the Generator to demonstrate compliance with relevant Grid
Code requirements including the tests witnessed by The Company;
and
ECP.7.6 The following provisions apply in relation to the issue of a Final Operational
Notification in respect of Network Operators and Non-Embedded
Customers Plant and Apparatus.
ECP.7.7 Prior to the issue of a Final Operational Notification the Network Operator
and Non-Embedded Customer must have addressed the Unresolved
Issues to The Company’s satisfaction to demonstrate compliance with the
relevant Grid Code provisions.
ECP.7.8 Prior to the issue of a Final Operational Notification the Network Operator
and Non-Embedded Customer must submit to The Company to The
Company’s satisfaction:
(a) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data), with validated actual values and updated
estimates for the future including Forecast Data items such as
Demand;
(b) any items required by ECP.5.2 and ECP.6.4 updated by the User as
necessary;
ECP
Page 20 of 99
Issue 6 Revision 17 04 September 2023
(c) evidence to The Company’s reasonable satisfaction that
demonstrates that the models and/or parameters as required under
PC.A.2.2, PC.A.2.3, PC.A.2.4, PC.A.2.5, PC.A.4 and PC.A.6 (as
applicable), supplied to The Company provide a reasonable
representation of the behaviour of the User’s Plant and Apparatus;
(e) results from the tests and simulations required in accordance with
ECP.A.8 carried out by the Network Operator or Non-Embedded
Customer to demonstrate compliance with relevant Grid Code
requirements including any tests witnessed by The Company; and
ECP.7.9 The items referred to at ECP.7.8 shall be submitted by the Network Operator
or Non-Embedded Customer after successful completion of the tests
required under ECP.7.8.
ECP.7.10 If the requirements of ECP.7.8 have been successfully met, The Company
will notify the Network Operator or Non-Embedded Customer that
compliance with the relevant Grid Code provisions has been demonstrated
for Network Operators or Non-Embedded Customers Plant and
Apparatus as applicable through the issue of a Final Operational
Notification.
ECP.8.1 No later than 4 calendar years and 6 months after the issue of a Final
Operational Notification, The Company will notify the Generator or HVDC
System Owner that confirmation of continued compliance with the
requirements of the Grid Code and/or the Bilateral Agreement.
ECP.8.2 No later than 5 calendar years after the issue of a Final Operational
Notification, the Generator or HVDC System Owner shall confirm that the
Plant and/or Apparatus (including OTSUA if applicable) is fully compliant with
the requirements of the Grid Code and/or the Bilateral Agreement. The
confirmation of compliance will include:
(a) a Compliance Statement and a User Self Certification of Compliance
signed by the EU Code User and a statement of any requirements that
the Generator or HVDC System Owner has identified that have not been
met together with a copy of the derogation in respect of the same from
The Authority.
ECP
Page 21 of 99
Issue 6 Revision 17 04 September 2023
(b) complete set of relevant Planning Code data (both Standard Planning
Data and Detailed Planning Data), with validated actual values and
updated estimates for the future including Forecast Data items such as
Demand. Simulation Studies and results from tests detailed in Appendix
ECP.A.3 – ECP.A.8 inclusive are not required as part of the Compliance
Repeat Plan.
For the avoidance of doubt the Generator or HVDC System Owner is
responsible for ensuring that Plant and/or Apparatus (including OTSUA if
applicable) remains compliant with the relevant clauses of the Grid Code and/or
the Bilateral Agreement and/or connection site conditions notified by The
Company.
ECP.8.3 If the requirements of ECP.8.2 have been completed to The Company’s
satisfaction, The Company will notify the Generator or HVDC System Owner
that compliance with the relevant Grid Code provisions has been demonstrated
for the Power Generating Module(s), including DC Connected Power Park
Module(s) and OTSUA, if applicable or HVDC Equipment as applicable
through the issue of a Final Operational Notification subject to Compliance
Repeat Plan (ECP.8) no later than 5 years from the date of issue. In respect of
an Embedded Power Station or Embedded DC Converter Station other
than Embedded Medium Power Stations not subject to a Bilateral
Agreement and Embedded HVDC Systems not subject to a Bilateral
Agreement, The Company will notify the Network Operator that a Final
Operational Notification has been issued.
ECP.8.4 If a Final Operational Notification cannot be issued because the
requirements of ECP.8.2 have not been successfully met prior to 5 years from
the date of issue of the Final Operational Notification, then The Company
will issue the Generator or HVDC System Owner (where licensed in respect
of its activities) a Limited Operational Notification with respect to the
Unresolved Issues. The provisions of ECP.9 shall then apply.
ECP.9.1 Following the issue of a Final Operational Notification for a Power Station
consisting of Type B, Type C or Type D Power Generating Module or an
HVDC System or Network Operators or Non-Embedded Customers
Plant and Apparatus if:
ECP
Page 22 of 99
Issue 6 Revision 17 04 September 2023
the Generator or HVDC System Owner to then follow the process
in ECP.9.2 to ECP.9.11; or,
ECP.9.4 Except where the provisions of ECP.9.3 apply, where the restriction notified in
ECP.9.2 is not resolved in 28 days, then
(i) the Generator or HVDC System Owner with input from and
discussion of conclusions with The Company, and the Network
Operator where the Synchronous Power Generating Module,
CCGT Module, Power Park Module or Power Station as applicable
is Embedded, shall undertake an investigation to attempt to determine
the causes of and determine a solution to the non-compliance. Such
investigation shall continue for no longer than 56 days. During such
investigation, the Generator or HVDC System Owner shall provide to
The Company the relevant data which has changed due to the
restriction in respect of ECP.7.3.1 as notified to the Generator or
ECP
Page 23 of 99
Issue 6 Revision 17 04 September 2023
HVDC System Owner by The Company as being required to be
provided; or
ECP.9.5.1 Following the issue of a Final Operational Notification, The Company will
issue to the Generator, HVDC System Owner, Network Operator or Non-
Embedded Customer a Limited Operational Notification if:
(a) by the end of the 56 day period referred to at ECP.9.4, the investigation
has not resolved the non-compliance to The Company’s satisfaction; or
ECP.9.5.2 The Limited Operational Notification will be time limited (in the case of Type
D Power Generating Modules, HVDC Systems, Network Operator’s or
Non-Embedded Customer’s Plant and Apparatus to expire no later than 12
months from the start of the non-compliance or restriction or from reconnection
following a change). The Company may agree a longer duration in the case of
a Limited Operational Notification following a Modification or whilst the
Authority is considering the application for a derogation in accordance with
ECP.10.1.
ECP.9.5.3 The Limited Operational Notification will notify the Generator, HVDC
System Owner, Network Operator or Non-Embedded Customer of any
restrictions on the operation of the Synchronous Power Generating
Module(s), CCGT Module(s), Power Park Module(s), OTSUA if applicable,
HVDC Equipment or Plant and Apparatus and will specify the Unresolved
Issues. The Generator, HVDC System Owner, Network Operator or Non-
Embedded Customer must operate in accordance with any notified
restrictions and must resolve the Unresolved Issues.
ECP.9.5.4 The User and The Company will be deemed compliant with all the relevant
provisions of the Grid Code provided operation is in accordance with the
Limited Operational Notification, whilst it is in force, and that the provisions
of and referred to in ECP.9 are complied with.
ECP
Page 24 of 99
Issue 6 Revision 17 04 September 2023
ECP.9.5.5 The Unresolved Issues included in a Limited Operational Notification will
show the extent that the provisions of ECP.7.2 (testing) and ECP.7.3 (final data
submission) or ECP.7.8 (d) - (e) (testing) and ECP7.8 (a) – (c) (data
submission, as applicable, shall apply. In respect of selecting the extent of any
tests which may in The Company’s view reasonably be needed to
demonstrate the restored capability and in agreeing the time period in which
the tests will be scheduled, The Company shall, where reasonably practicable,
take account of the Generator or HVDC System Owner’s input to contain its
costs associated with the testing.
(a) updated Planning Code data (both Standard Planning Data and
Detailed Planning Data);
(d) a detailed schedule of the tests and the procedures for the tests
required to be carried out by the Generator, HVDC Equipment
Station, Network Operator or Non-Embedded Customer to
demonstrate compliance with relevant Grid Code requirements as
agreed by The Company. The schedule of tests shall be consistent
with Appendix ECP.A.5, Appendix ECP.A.6 or Appendix ECP.A.8 as
appropriate; and
ECP
Page 25 of 99
Issue 6 Revision 17 04 September 2023
with the relevant provisions of the ECCs prior to the Synchronous Power
Generating Module being Synchronised to the Total System:
(a) those tests required to establish the open and short circuit saturation
characteristics of the Synchronous Power Generating Module (as
detailed in Appendix ECP.A.5.3) to enable assessment of the short
circuit ratio in accordance with ECC.6.3.2.3.4 or ECC.6.3.2.5. Such
tests may be carried out at a location other than the Power Station
site; and
(b) open circuit step response tests (as detailed in Appendix ECP.A.5.2)
to demonstrate compliance with ECC.A.6.2.4.1.
ECP.9.6 In the case of a change or Modification, not less than 28 days, or such
shorter period as may be acceptable in The Company’s reasonable opinion:
ECP.9.7 Other than Unresolved Issues that are subject to tests to be witnessed by
The Company, the Generator, HVDC System Owner, Network Operator
or Non-Embedded Customer must resolve any Unresolved Issues prior to
the commencement of the tests, unless The Company agrees to a later
resolution. The Generator, HVDC System Owner, Network Operator or
Non-Embedded Customer must liaise with The Company in respect of such
resolution. The tests that may be witnessed by The Company are specified
in ECP.7.2.2.
ECP.9.8 Not less than 28 days, or such shorter period as may be acceptable in The
Company’s reasonable opinion, prior to the Generator or HVDC System
Owner wishing to commence tests listed as Unresolved Issues to be
witnessed by The Company, the Generator or HVDC System Owner will
notify The Company that the Synchronous Power Generating Module(s),
CCGT Module(s), Power Park Module(s), OTSUA if applicable or HVDC
Equipment as applicable is ready to commence such tests.
ECP.9.10 Where the Unresolved Issues have been resolved a Final Operational
Notification will be issued to the User.
ECP.9.11 If a Final Operational Notification has not been issued by The Company as
referred to at ECP.9.5.2 (or where agreed following a Modification by the
ECP
Page 26 of 99
Issue 6 Revision 17 04 September 2023
expiry time of the LON) then the Generator, HVDC System Owner, Network
Operator or Non-Embedded Customer (where licensed in respect of its
activities) and The Company shall apply to the Authority for a derogation.
ECP.10.1 Whilst the Authority is considering the application for a derogation, the
Interim Operational Notification or Limited Operational Notification will
be extended to remain in force until the Authority has notified The Company
and the Generator, HVDC System Owner, Network Operator or Non-
Embedded Customer of its decision. Where the Generator or HVDC
System Owner is not licensed, The Company may propose any necessary
changes to the Bilateral Agreement with such unlicensed Generator or
HVDC System Owner.
(a) grants a derogation in respect of the Plant and/or Apparatus, then The
Company shall issue Final Operational Notification once all other
Unresolved Issues are resolved; or
(b) decides a derogation is not required in respect of the Plant and/or
Apparatus then The Company will reconsider the relevant Unresolved
Issues and may issue a Final Operational Notification once all other
Unresolved Issues are resolved; or
(c) decides not to grant any derogation in respect of the Plant and/or
Apparatus, then there will be no Operational Notification in place and
The Company and the User shall consider its rights pursuant to the
CUSC.
ECP
Page 27 of 99
Issue 6 Revision 17 04 September 2023
ECP.11.1.3 The process to be followed by Power Park Unit manufacturers submitting a
Manufacturer’s Data & Performance Report is agreed by The Company.
ECP.11.2 indicates the specific Grid Code requirement areas in respect of
which a Manufacturer’s Data & Performance Report may be submitted.
ECP.11.1.4 The Company will maintain and publish a register of those Manufacturer’s
Data & Performance Reports which The Company has received and
accepted as being an accurate representation of the performance of the
relevant Plant and / or Apparatus. Such register will identify the manufacturer,
the model(s) of Power Park Unit(s) to which the report applies and the
provisions of the Grid Code in respect of which the report contributes towards
the demonstration of compliance. The inclusion of any report in the register
does not in any way confirm that any Power Park Modules which utilise any
Power Park Unit(s) covered by a report is or will be compliant with the Grid
Code.
ECP.11.5 It is the responsibility of the EU Code User to ensure that the correct reference
for the Manufacturer’s Data & Performance Report is used and the EU Code
User by using that reference accepts responsibility for the accuracy of the
information. The EU Code User shall ensure that the manufacturer has kept
The Company informed of any relevant variations in plant specification since
the submission of the relevant Manufacturer’s Data & Performance Report
which could impact on the validity of the information.
ECP
Page 28 of 99
Issue 6 Revision 17 04 September 2023
ECP.11.6 The Company may contact the Power Park Unit manufacturer directly to
verify the relevance of the use of such Manufacturer’s Data & Performance
Report. If The Company believe the use some or all of such Manufacturer’s
Data & Performance Report information is incorrect or the referenced data is
inappropriate, then the reference to the Manufacturer’s Data & Performance
Report may be declared invalid by The Company. Where, and to the extent
possible, the data included in the Manufacturer’s Data & Performance
Report is appropriate, the compliance assessment process will be continued
using the data included in the Manufacturer’s Data & Performance Report.
ECP.11.7 In the case of a co-located site, for example Electricity Storage Modules or
Grid Forming Plant connected within a new or existing Power Station, The
Company will accept demonstration of compliance at the Grid Entry Point or
User System Entry Point (if Embedded) through a combination of the
capabilities of the Power Generating Modules and Electricity Storage
Modules (which could include Grid Forming Plant) or Electricity Storage
Modules and Generating Units or Power Park Modules (which could include
Grid Forming Plant). Generators or Grid Forming Plant Owners should
however be aware that for the purposes of compliance, full Grid Code
compliance should be demonstrated when, for example, the Electricity
Storage Module or Grid Forming Plant is out of service and the remaining
Power Generating Module is in service or the Electricity Storage Module or
Grid Forming Plant is in service and the Power Generating Module is out of
service. Equally, The Company will accept Manufacturer’s Data &
Performance Reports for the purposes of proving compliance at co-located
sites.
APPENDIX 1
NOT USED
ECP
Page 29 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 2
This User Self Certification of Compliance records the compliance by the EU Code User in
respect of [NAME] Power Station/HVDC Equipment Station with the Grid Code and the
requirements of the Bilateral Agreement and Construction Agreement dated [ ] with
reference number [ ]. It is completed by the Power Station/HVDC System Owner in the case
of Plant and/or Apparatus connected to the National Electricity Transmission System and
for Embedded Plant.
We have recorded our compliance against each requirement of the Grid Code which applies
to the Power Station/HVDC Equipment Station, together with references to supporting
evidence and a commentary where this is appropriate, and have provided this to The
Company. A copy of the Compliance Statement is attached.
Supporting evidence, in the form of simulation results, test results, manufacturer’s data and
other documentation, is attached in the User Data File Structure.
The EU Code User hereby certifies that, to the best of its knowledge and acting in accordance
with Good Industry Practice, the Power Station is compliant with the Grid Code and the
Bilateral Agreement in all aspects [with the following Unresolved Issues*] [with the following
derogation(s)**]:
Connection
Requirement Ref: Issue
Condition
* Include for Interim User Self Certification of Compliance ahead of Interim Operational
Notification.
** Include for final User Self Certification of Compliance ahead of Final Operational
Notification where derogation(s) have been granted. If no derogation(s) required delete
wording and Table.
ECP
Page 30 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 3
SIMULATION STUDIES
ECP.A.3.1 SCOPE
ECP.A.3.1.1 This Appendix sets out the simulation studies required to be submitted to The
Company to demonstrate compliance with the European Connection
Conditions unless otherwise agreed with The Company. This Appendix
should be read in conjunction with ECP.6 with regard to the submission of the
reports to The Company. Where there is any inconsistency in the technical
requirements in respect of which compliance is being demonstrated by
simulation in this Appendix and ECC.6.3 and the Bilateral Agreement, the
provisions of the Bilateral Agreement and ECC.6.3 prevail. The studies
specified in this Appendix will normally be sufficient to demonstrate
compliance. However, The Company may agree an alternative set of studies
proposed by the Generator or HVDC System Owner provided The Company
deem the alternative set of studies sufficient to demonstrate compliance with
the Grid Code and the Bilateral Agreement.
ECP.A.3.1.2 The Generator or HVDC System Owner shall submit simulation studies in the
form of a report to demonstrate compliance. In all cases the simulation studies
must utilise models applicable to the Synchronous Power Generating
Module, HVDC Equipment or Power Park Module with proposed or actual
parameter settings. Reports should be submitted in English with all diagrams
and graphs plotted clearly with legible axes and scaling provided to ensure any
variations in plotted values is clear. In all cases, the simulation studies must be
presented over a sufficient time period to demonstrate compliance with all
applicable requirements.
ECP.A.3.1.4 The Company will permit relaxation from the requirement ECP.A.3.2 to
ECP.A.3.8 where an Equipment Certificate for the Power Generating
Module or HVDC Equipment has been provided which details the
characteristics from appropriate simulations on a representative installation
with the same equipment and settings and the performance of the Power
Generating Module or HVDC Equipment can, in The Company’s opinion,
reasonably represent that of the installed Power Generating Module or HVDC
Equipment.
ECP.A.3.1.5 For Type B, Type C and Type D Power Generating Modules the relevant
Equipment Certificate must be supplied in the Power Generating Module
Document or Users Data File structure as applicable. For HVDC Equipment
the relevant Equipment Certificates must be supplied in the Users Data File
structure.
ECP.A.3.1.6 In the case of a co-located site, for example Electricity Storage Modules or
Grid Forming Plant connected within a new or existing Power Station, The
Company will accept simulation studies to demonstrate compliance at the Grid
Entry Point or User System Entry Point (if Embedded) through a
combination of the capabilities of the Power Generating Modules (which
could include Grid Forming Plant) and Electricity Storage Modules or
Electricity Storage Modules (which could include Grid Forming Plant) and
Generating Units or Power Park Modules. Generators should however be
aware that for the purposes of simulations, full Grid Code compliance should
be demonstrated when, for example, the Electricity Storage Module or Grid
ECP
Page 31 of 99
Issue 6 Revision 17 04 September 2023
Forming Plant is out of service and the remaining Power Generating Module
is in service or the Electricity Storage Module or Grid Forming Plant is in
service and the Power Generating Module is out of service.
(ii) open circuit time series simulation study of the response of the
Excitation System to a +10% step change from 90% to 100%
terminal voltage.
(iv) gain and phase Bode diagrams for the open loop frequency domain
response of the Synchronous Power Generating Module
Excitation System with and without the Power System Stabiliser.
These should be in a suitable format to allow assessment of the
phase contribution of the Power System Stabiliser and the gain
and phase margin of the Excitation System with and without the
Power System Stabiliser in service.
(v) an eigenvalue plot to demonstrate that all modes remain stable when
the Power System Stabiliser gain is increased by at least a factor
of 3 from the designed operating value.
(vi) gain Bode diagram for the closed loop on load frequency domain
response of the Synchronous Power Generating Module
Excitation System with and without the Power System Stabiliser.
The Synchronous Power Generating Module operating at full load
and at unity power factor. These diagrams should be in a suitable
format to allow comparison of the Active Power damping across the
frequency range specified in ECC.A.6.2.6.3 with and without the
Power System Stabiliser in service.
ECP
Page 32 of 99
Issue 6 Revision 17 04 September 2023
OTSDUW Plant and Apparatus at the Interface Point the Power System
Stabiliser tuning simulation study report required by ECC.A.7.2.4.1 or
ECC.A.8.2.4 or required by the Bilateral Agreement shall contain:
(i) the Voltage Control System model including the Power System
Stabiliser with settings as required under the Planning Code
(PC.A.5.4) and Bilateral Agreement.
(ii) on load time series dynamic simulation studies of the response of the
Voltage Control System with and without the Power System
Stabiliser to 2% and 10% steps in the reference voltage and a three
phase short circuit fault applied to the Grid Entry Point or the
Interface Point in the case of OTSDUW Plant and Apparatus for
100ms. The simulation studies should be carried out operating at full
Active Power and maximum leading Reactive Power import
condition with the fault level at the Supergrid HV connection point at
minimum or as otherwise agreed with The Company. The results
should show appropriate signals to demonstrate the expected
damping performance of the Power System Stabiliser.
ECP.A.3.3.1 (a) For a Synchronous Power Generating Module, the Generator shall
supply simulation studies to demonstrate the capability to meet
ECC.6.3.2 by submission of a report containing load flow simulation
study results to demonstrate:
(b) For an OSTUA with an Interface Point above 33kV or Power Park
Modules with a Grid Entry Point or User System Entry Point above
33kV, the Generator shall demonstrate the capability to meet ECC.6.3.2
by submission of a report containing load flow simulation study results to
demonstrate operation at points A, B, E and F in accordance with Figure
ECC.A.7.2.2(b) or Figure ECC.A.8.2.2(b). The studies should be run with
both the OTSUA and Power Park Module operating at Maximum
Capacity and at the Minimum Stable Operating Level.
ECP
Page 33 of 99
Issue 6 Revision 17 04 September 2023
(c) For an OSTUA with an Interface Point at or below 33kV or Power Park
Modules with a Grid Entry Point or User System Entry Point at or
below 33kV, a load flow simulation study results to demonstrate operation
at points A, B, E and F in accordance with Figure ECC.A.7.2.2(c) or
Figure ECC.A.8.2.2(b). The studies should be run with both the OTSUA
and Power Park Module operating at Maximum Capacity and at the
Minimum Stable Operating Level.
(d) For an HVDC system, the HVDC System Owner shall supply simulation
studies to demonstrate the capability to meet ECC.6.3.2 by submission
of a report containing load flow simulation study results to demonstrate
operation at points A, B, E and F in accordance with Figure
ECC.A.7.2.2(b). The studies should be run with both the HVDC System
operating at the Maximum HVDC Active Power Transmission
Capacity and Minimum HVDC Active Power Transmission Capacity.:
ECP.A.3.3.2 In the case of a Synchronous Power Generating Module the terminal voltage
in the simulation should be the nominal voltage for the machine.
ECP.A.3.3.3 In the case of a Power Park Module where the load flow simulation studies
show that the individual Power Park Units deviate from nominal voltage to
meet the Reactive Power requirements then evidence must be provided from
factory (e.g. in a Manufacturer’s Data & Performance Report) or site testing
that the Power Park Unit is capable of operating continuously at the operating
points determined in the load flow simulation studies.
ECP.A.3.4.1 This section applies to HVDC Equipment; and Type C & Type D Power Park
Modules to demonstrate the voltage control capability and Type B Power Park
Modules to demonstrate the voltage control capability if specified by The
Company.
(ii) a dynamic time series simulation study result of a sufficiently large positive
step in System voltage to cause a change in Reactive Power from zero
to the maximum leading value at Rated MW.
ECP
Page 34 of 99
Issue 6 Revision 17 04 September 2023
(v) a dynamic time series simulation study result of a sufficiently large
negative step in System voltage to cause a change in Reactive Power
from the maximum leading value to the maximum lagging value at Rated
MW.
The Generator should also provide the voltage control study specified in
ECP.A.3.7.4.
ECP.A.3.4.2 All the above studies should be completed with a network operating at the
voltage applicable for zero Reactive Power transfer at the Grid Entry Point
or User System Entry Point if Embedded or, in the case of OTSUA, Interface
Point unless stated otherwise. The fault level at the HV connection point should
be set at the minimum level as agreed with The Company.
ECP.A.3.5.1 This section applies to Type B, Type C and Type D Power Generating
Modules and HVDC Equipment to demonstrate the modules Fault Ride
Through and Fast Fault Current injection capability.
The Generator or HVDC System Owner shall supply time series simulation
study results to demonstrate the capability of Synchronous Power
Generating Module, HVDC Equipment, and Power Park Modules and
OTSUA to meet ECC.6.3.15 and ECC.6.3.16 by submission of a report
containing:
(i) a time series simulation study of a 140ms three phase short circuit fault
with a retained voltage as detailed in table A.3.5.1 below applied at the
Grid Entry Point or (User System Entry Point if Embedded) of the
Power Generating Module or HVDC Equipment or OTSUA.
(ii) a time series simulation study of 140ms unbalanced short circuit faults
with a retained voltage as detailed in table 1 on the faulted phase(s)
applied at the Grid Entry Point or (User System Entry Point if
Embedded) of the Power Generating Module or HVDC Equipment
or OTSUA. The unbalanced faults to be simulated are:
ECP
Page 35 of 99
Issue 6 Revision 17 04 September 2023
the Supergrid HV connection point at minimum or as otherwise agreed
with The Company as detailed in ECC.6.3.15.8.
ECP
Page 36 of 99
Issue 6 Revision 17 04 September 2023
connection point shall be used which may be calculated from the
maximum fault level at the User System Entry Point.
ECP.A.3.5.3 In the case of a Power Park Module the studies detailed in ECP.A.3.5.1 should
be repeated to demonstrate compliance during foreseeable running
arrangements resulting from outages of major Plant and Apparatus (for
example outage of the main export cable in the case of OTSDUW or module
step up transformer where alternative export connections are possible). For
these conditions, the Power Park Module Active Power output may be
reduced to levels appropriate to the planned operating regime proposed by the
Generator. The Generator shall consult The Company on alternative running
arrangements and agree with The Company the running arrangements that
will be studied prior to the Generator undertaking the studies. For the
avoidance of doubt, compliance of a Power Park Module with Fault Ride
Through requirements remains the responsibility of the Generator under all
operating conditions.
ECP.A.3.5.4 In the case of a Power Park Module with a Registered Capacity greater or
equal to 100MW, the studies detailed in ECP.A.3.5.1 should be repeated with
50% of the Power Park Units Synchronised to the Total System. In the case
of a Power Station containing multiple Power Park Modules or multiple
Offshore Power Park Modules connected to an Offshore Transmission
System or OTSDUW the study should include all Power Park Modules with
50% of the Power Park Units Synchronised to the Total System.
ECP.A.3.5.5 In the case of HVDC Equipment the studies detailed in ECP.A.3.5.1 should be
repeated to demonstrate compliance during foreseeable running arrangements
resulting from outages of major Plant and Apparatus (for example outage of
an HVDC cable or convertor. For these conditions, the HVDC Equipment
Active Power transfer may be reduced to levels appropriate to the planned
operating regime. The Generator or HVDC System Owner shall consult The
Company on alternative running arrangements and agree with The Company
the running arrangements that will be studied prior to the Generator or HVDC
System Owner undertaking the studies. For the avoidance of doubt,
compliance of HVDC Equipment with Fault Ride Through requirements
remains the responsibility of the Generator or HVDC System Owner under all
operating conditions.
ECP.A.3.6.1 This section applies to Type B, Type C and Type D Power Generating
Modules, HVDC Equipment to demonstrate the capability to modulate Active
Power at high frequency as required by ECC6.3.7.3.5(ii).
ECP
Page 37 of 99
Issue 6 Revision 17 04 September 2023
Equipment can control the power island Frequency to less than 52Hz
consistent with ECC.6.3.7.3.5(ii). Where transient excursions above 52Hz
occur the Generator or HVDC Equipment Owner should ensure that the
duration above 52Hz is less than any high Frequency protection system
applied to the Power Generating Module or HVDC Equipment.
ECP.A.3.6.3 For HVDC Equipment and Power Park Modules consisting of units
connected wholly by power electronic devices the simulation methodology may
be modified by the addition of a Synchronous Power Generating Module
(G2) connected as indicated in Figure ECP.A.3.6.2. This additional
Synchronous Power Generating Module should have an inertia constant of
3.5MWs/MVA, be initially operating at rated power output and unity Power
Factor. The mechanical power of the Synchronous Power Generating
Module (G2) should remain constant throughout the simulation.
ECP.A.3.6.4 At the start of the simulation study the Power Generating Module or HVDC
Equipment will be operating maximum Active Power output. The Power
Generating Module or HVDC Equipment will then be islanded from the Total
System but still supplying load “X” by the opening of a breaker, which is not
the Power Generating Module or HVDC Equipment connection circuit
breaker (the governor should therefore, not receive any signals that the breaker
has opened other than the reduction in load and subsequent increase in
speed). A schematic arrangement of the simulation study is illustrated by
Figure ECP.A.3.6.1.
ECP
Page 38 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.3.6.5 A simulation study shall be performed for Type B, C & D Power Generating
Modules in Limited Frequency Sensitive Mode (LFSM) and Frequency
Sensitive Mode (FSM) for Type C & D Power Generating Modules. The
simulation study results should indicate Active Power and Frequency.
ECP.A.3.6.6 To allow validation of the model used to simulate load rejection in accordance
with ECC.6.3.7.3.5 as described, a further simulation study is required to
represent the largest positive Frequency injection step or fast ramp (BC1 and
BC3 of Figure 2) that will be applied as a test as described in ECP.A.5.8 and
ECP.A.6.6.
ECP.A.3.6.7 The above suite of simulation studies equally apply for Electricity Storage
Modules when in an export mode of operation and should also demonstrate
transition to an import mode of operation in line with the stated Droop
characteristics of the Electricity Storage Module when in an import mode of
operation. Three simulation studies need to be carried out:
ECP.A.3.6.8 To demonstrate the LFSM-U low Frequency control when operating in Limited
Frequency Sensitive Mode the Generator or HVDC System Owner shall
submit a simulation study representing the response of the Power Generating
Module or HVDC Equipment operating at 80% of Maximum Capacity. The
simulation study event shall be equivalent to:
ECP
Page 39 of 99
Issue 6 Revision 17 04 September 2023
(ii) 60 seconds of steady state with the measured System Frequency
depressed to the same level as in ECP.A.3.6.8.1 (i) as illustrated in
Figure ECP.A.3.6.1 below.
(iii) then increase of the measured System Frequency ramped over 10
seconds to cause a reduction in Active Power output back to the
original Active Power level followed by at least 60 seconds of steady
output.
Frequency (Hz)
∆F
10 60 10 60
Time (seconds)
Figure ECP.A.3.6.1
Operation of Electricity Storage Modules in an import mode of operation
during low System Frequencies
ECP.A.3.6.9 For Generators in respect of Electricity Storage Modules who are unable to
deload from an import mode of operation to an export mode of operation during
low System Frequencies as defined in ECC.6.3.7.2.3 and have agreed with
The Company that they can comply with the requirements of OC6.6.6 as
provided for in ECC.6.3.7.2.3.1, the simulation studies as detailed in
ECP.A.3.6.10 shall apply.
For Generators in respect of Electricity Storage Modules who can satisfy the
requirements of ECC.6.3.7.2.3 (except ECC.6.3.7.2.3.1 to which OC6.6.6
refers) the simulation studies as detailed in ECP.A.3.6.11 shall apply.
ECP.A.3.6.10 The Generator shall submit a simulation study representing the response of
the Electricity Storage Module operating at Maximum Import Power
followed by a simulated fall in System Frequency. The simulation study shall
demonstrate that:-
ECP.A.3.6.11 For Generators in respect of Electricity Storage Modules who can satisfy the
Droop requirements of ECC.6.3.7.2.3, the Generator shall submit simulation
studies representing the response of the Electricity Storage Module. The
simulation studies shall comprise:-
ECP
Page 40 of 99
Issue 6 Revision 17 04 September 2023
(i) Initial conditions where the Electricity Storage Module shall be
operating at its Maximum Import Power with the Electricity Storage
Module in Limited Frequency Sensitive Mode.
(ii) A simulation signal shall be applied which ramps the System
Frequency from 50Hz to 49.0Hz at a rate of 2Hz/s. The System
Frequency shall be held at 49.0Hz for 60s and the then ramped back
to 50Hz in 10s as shown in Figure ECP.3.6.4.
Figure ECP.A.3.6.4
ECP
Page 41 of 99
Issue 6 Revision 17 04 September 2023
Figure ECP.A.3.6.5
ECP
Page 42 of 99
Issue 6 Revision 17 04 September 2023
Figure ECP.A.3.6.6
ECP.A.3.7.1 For Type C and Type D Synchronous Power Generating Modules, HVDC
Equipment, OTSDUW Plant and Apparatus or Power Park Modules, the
Generator (including those undertaking OTSDUW) or HVDC System Owner
shall provide simulation studies to verify that the proposed controller models
supplied to The Company under the Planning Code are fit for purpose. These
simulation study results shall be provided in the timescales stated in the
Planning Code.
Frequency (Hz)
-0.2
-0.5
10 20 30 60
Time (seconds)
ECP
Page 43 of 99
Issue 6 Revision 17 04 September 2023
Figure ECP.A.3.7.2
The simulation study shall show Active Power output (MW) and the equivalent
of Frequency injected.
ECP.A.3.7.3 To demonstrate the Excitation System model the Generator shall submit
simulation studies representing the response of the Synchronous Power
Generating Module as follows:
(i) operating open circuit at rated terminal voltage and subjected to a 10%
step increase in terminal voltage reference from 90% to 100%.
(ii) operating at Rated MW, nominal terminal voltage and unity Power
Factor subjected to a 2% step increase in the voltage reference. Where
a Power System Stabiliser is included within the Excitation System
this shall be in service.
The simulation study shall show the Synchronous Power Generating Module
terminal voltage, field voltage, Active Power, Reactive Power and Power
System Stabiliser output signal as appropriate.
ECP.A.3.7.4 To demonstrate the Voltage Controller model the Generator (including those
undertaking OTSDUW) or HVDC System Owner shall submit a simulation
study representing the response of the HVDC Equipment, OTSDUW Plant
and Apparatus or Power Park Module operating at Rated MW and unity
Power Factor at the connection point to a 2% step increase in the voltage
reference. The simulation study shall show the terminal voltage, Active
Power, Reactive Power and Power System Stabiliser output signal as
appropriate.
ECP.A.3.7.5 To validate that the excitation and voltage control models submitted under the
Planning Code are a reasonable representation of the dynamic behaviour of
the Synchronous Power Generating Module, OTSDUW Plant and
Apparatus, HVDC Equipment or Power Park Module as built, the Generator
or HVDC System Owner shall repeat the simulation studies outlined above but
using the operating conditions of the equivalent tests. The simulation study
results shall be displayed overlaid on the actual test results.
ECP.A.3.7.6 For Type C and Type D Synchronous Power Generating Modules or HVDC
Equipment to validate that the governor/load controller/plant or Frequency
control models submitted under the Planning Code is a reasonable
representation of the dynamic behaviour of the Synchronous Power
Generating Module or HVDC Equipment Station as built, the Generator or
HVDC System Owner shall repeat the simulation studies outlined above but
using the operating conditions of the equivalent tests. The simulation study
results shall be displayed overlaid on the actual test results.
ECP.A.3.8.3 The simulation studies should utilise the HVDC Equipment control system
models including the settings as required under the Planning Code
ECP
Page 44 of 99
Issue 6 Revision 17 04 September 2023
(PC.A.5.3.2). The network conditions for the above simulation studies should
be discussed with The Company prior to commencing any simulation studies.
ECP.A.3.9.1 This section applies to Users and Non-CUSC Parties who own and operate
GBGF-I Plant to demonstrate the ability of their Grid Forming Plant to satisfy
the requirements of ECC.6.3.19. For the avoidance of doubt these
requirements are not necessary from owner and operators of GBGF-S Plant.
ECP.A.3.9.2 For initial approval Users and Non-CUSC Parties are required to submit the
following data of their Grid Forming Plant to The Company: -
a) The representation of their Grid Forming Plant in a format either the same
as Figure PC.A.5.8.1 of PC.A.5.8.1 or in an equivalent format.
e) For the items a) to d) the User or Non-CUSC Party can submit the data in
any equivalent format as agreed with The Company.
ECP.A.3.9.3 For GBGF-I, the User or Non-CUSC Party may be required to supply other
versions of the Network Frequency Perturbation Plot for different input and
output signals as defined by The Company.
ECP.A.3.9.4 For final approval, Users and Non-CUSC Parties are required to demonstrate
that the GBGF_I model is capable of supplying Active ROCOF Response
Power, and Active Phase Jump Power, and submit a full 3 phase simulation
study in the time domain representing the response of the Grid Forming Plant
over a range of operating conditions. The simulation study shall comprise of
the following stages.
Figure ECP.A.3.9.4
ii) The first simulation test is to demonstrate that the GBGF-I model is
capable of supplying Active ROCOF Response Power to the Total
System as a result of a System Frequency change. In this
simulation, with the Grid Forming Plant initially running at Registered
Capacity or Maximum Capacity, the Grid System Frequency is
increased from 50Hz to 51Hz at a rate of 1Hz/s with measurements of
ECP
Page 45 of 99
Issue 6 Revision 17 04 September 2023
the Grid Forming Plant’s Active ROCOF Response Power, System
Frequency and time in (ms). The simulation is required to assess
correct operation of the Grid Forming Plant without saturating.
Repeat for 50Hz to 49Hz at 1Hz.s
iii) The second simulation test is to demonstrate the GBGF-I’s ability to
supply Active ROCOF Response Power and asses its withstand
capability under extreme System Frequencies. The Grid System
Frequency is increased from 50Hz to 52Hz at a rate of 1Hz/s with
measurements of the Active ROCOF Response Power, System
Frequency and time in (ms). This is repeated when the Grid System
Frequency is increased from 50Hz to 52Hz at a rate of 2 Hz/s with
measurements of the Active ROCOF Response Power, System
Frequency and time in (ms). Repeat for 50Hz to 48 Hz at 1 Hz/s and
50Hz to 48 Hz at 2 Hz/s.
iv) The third simulation is to demonstrate the Grid Forming Plant’s ability
to supply Active ROCOF Response Power over the full System
Frequency range.
(a) With the System Frequency set to 50Hz, the Grid Forming Plant
should be initially running at 75% Maximum Capacity or 75%
Registered Capacity, zero MVAr output and both Limited
Frequency Sensitive Mode and Frequency Sensitive Mode
disabled.
(b) The System Frequency is then increased from 50Hz to 52Hz at
a rate of 1Hz/s over a 2 second period. Allow conditions to
stabilise for 5 seconds and then decrease the System Frequency
from 52Hz to 47Hz at a rate of 1Hz/s over a 5 second period. Allow
conditions to stabilise.
(c) Record results of phase based Active ROCOF Response Power,
Reactive Power, voltage and System Frequency.
(d) The simulation now needs to be re-run in the opposite direction.
The same initial conditions should be applied as per
ECP.A.3.9.2iv) (a).
(e) The System Frequency is then decreased from 50Hz to 47Hz at
a rate of 1Hz/s over a 3 second period. Allow conditions to
stabilise for 5 seconds and then increase the System Frequency
from 47Hz to 52Hz at a rate of 1Hz/s over a 5 second period. Allow
conditions to stabilise.
(f) Record results of Active ROCOF Response Power, Reactive
Power, voltage and System Frequency.
(g) The simulation is required to ensure the Grid Forming Plant can
deliver Active ROCOF Response Power without going into
saturation and that a behaviour that is equivalent to pole slipping
does not occur.
v) The fourth simulation is to demonstrate the Grid Forming Plant’s
ability to supply Active Phase Jump Power under normal operation.
(a) With the System Frequency set to 50Hz, the Grid Forming Plant
should initially be running at Maximum Capacity or Registered
Capacity or a suitable loading point to demonstrate Grid Forming
Capability as agreed with The Company, zero MVAr output and
all control actions (e.g. Limited Frequency Sensitive Mode,
Frequency Sensitive Mode and voltage control) disabled.
(b) Apply a positive phase jump of the Phase Jump Angle Limit
value at the Grid Entry Point or User System Entry Point.
ECP
Page 46 of 99
Issue 6 Revision 17 04 September 2023
(c) Record traces of Active Power, Reactive Power, voltage, current
and System Frequency for a period of 10 seconds after the step
change in phase has been applied. Repeat with a negative phase
jump.
vi) The fifth simulation is to demonstrate the Grid Forming Plant’s ability
to supply Active Phase Jump Power under extreme conditions.
(a) With the System Frequency set to 50Hz, the Grid Forming Plant
should be initially running at its Minimum Stable Operating Level
or Minimum Stable Generation, zero MVAr output and all control
actions (e.g. Limited Frequency Sensitive Mode, Frequency
Sensitive Mode and voltage control) disabled.
(b) Apply a phase jump equivalent to the positive Phase Jump Angle
Withstand value at the Grid.
(c) Record traces of Active Power, Reactive Power, voltage, current
and System Frequency for a period of 10 seconds after the step
change in phase has been applied. Repeat with a negative phase
jump.
(d) Repeat steps (a), (b) and (c) of ECP.A.3.9.4(vi) but on this
occasion apply a phase jump equivalent to the positive Phase
Jump Angle Limit at the Grid.
(a) With the System Frequency set to 50Hz, the Grid Forming Plant
should be initially running at its Maximum Capacity or Registered
Capacity, zero MVAr output and all control actions (e.g., Limited
Frequency Sensitive Mode, Frequency Sensitive Mode, GBGF
Fast Fault Current Injection, Fault Ride Through and voltage
control other than current limiters) disabled.
(b) Apply a solid three phase short circuit fault at the Grid Entry Point
or User System Entry Point for 140ms.
(c) Record traces of Active Power, Reactive Power, voltage, current
and System Frequency for a period of 10 seconds after the fault
has been applied. The GBGF-I’s current limit should be observed
to operate.
(d) Repeat steps (a) to (c) but on this occasion with Fault Ride
Through, GBGF Fast Fault Current Injection, Limited
Frequency Sensitive Mode and voltage control switched into
service.
(e) Record traces of Active Power, Reactive Power, voltage, current
and System Frequency for a period of 10 seconds after the fault
has been applied and confirm correct operation.
ECP
Page 47 of 99
Issue 6 Revision 17 04 September 2023
i) The User or Non-CUSC Party in respect of GBGF-I should supply a
simulation study to The Company equivalent to Figure ECP.A.3.9.5.
Figure ECP.A.3.9.5
The GBGF-I model should take the equivalent form shown in either Figure
ECP.A.3.9.6(a) or Figure ECP.A.3.9.6(b) as applicable. Each User or Non-
CUSC Party can use their own design, that may be very different to Figures
ECP.A.3.9.6(a) or ECP.A.3.9.6 (b) but should contain all relevant functions. In
either case the following tests should be completed, and results supplied to
ECP
Page 48 of 99
Issue 6 Revision 17 04 September 2023
verify the following criteria: -
Figure ECP.A.3.9.6(a)
Figure ECP.A.3.9.6(b)
ECP
Page 49 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 4
ECP.A.4.1 During any tests witnessed on-site by The Company, the following signals
shall be provided to The Company by the Generator undertaking OTSDUW
or HVDC System Owner in accordance with ECC.6.6.3.
ECP
Page 50 of 99
Issue 6 Revision 17 04 September 2023
• Line-line Voltage (kV) at the Grid Entry
Point or (User System Entry Point if
Embedded).
ECP.A.4.3.2 The Company accept that the signals specified in ECP.A.4.3.1(c) may have
lower effective sample rates than those required in ECC.6.6.3 although any
signals supplied for connection to The Company’s recording equipment which
do not meet at least the sample rates detailed in ECC.6.6.3 should have the
actual sample rates indicated to The Company before testing commences.
ECP
Page 51 of 99
Issue 6 Revision 17 04 September 2023
(iii) In the case of Offshore Power Park Modules and OTSDUA signals
ECP.A.4.3.1(a) will be provided at the Interface Point by the Offshore
Transmission Licensee pursuant to the STC or by the Generator
when OTSDUW Arrangements apply.
ECP.A.4.3.4 Options ECP.A.4.3.3 (ii) and (iii) will only be available on condition that;
(a) all signals outlined in ECP.A.4.3.1 are recorded and made available to
The Company by the Generator or HVDC System Owner from the
Power Park Module or OTSDUA or HVDC Equipment control
systems as a download once the testing has been completed; and
(b) the full test results are provided by the Generator HVDC System
Owner within 2 working days of the test date to The Company unless
The Company agrees otherwise; and
(c) all data is provided with a sample rate in accordance with ECC.6.6.3.3
unless The Company agrees otherwise; and
(c) The transducers shall either have a response time no greater than
50ms to reach 90% of output, or no greater than 300ms to reach
99.5%.
ECP.A.4.3.6 In the case of a GBGF-I system, the following signals shall be supplied to The
Company by the Grid Forming Plant Owner in accordance with ECC.6.6.3.
For the avoidance of doubt, User’s and Non-CUSC Parties will also be
required to undertake the necessary testing of their Plant in accordance with
the requirements of ECC.A.4 and OC5 as applicable.
ECP
Page 52 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.4.3.7 Testing not witnessed by The Company on-site
ECP.A.4.3.7.1.1 Where The Company has decided not to witness testing on-site, the results
shall be submitted to The Company in spreadsheet format with the signal
data in columns arranged as follows. Signal data denoted by “#” is not
essential but if not provided the column should remain in place but without
values entered. Where two signal names are given in a column these are
alternatives related to the type of plant under test.
ECP.A.4.3.7.1.2 Where The Company has requested addition signals to be recorded prior
to the testing these signals shall be placed in columns to the right of the
spreadsheet.
ECP.A.4.3.7.2.1 Onshore Synchronous Generating Unit Excitation System and Reactive
Capability
ECP.A.4.3.7.3.1 Onshore Power Park Modules Voltage Control & Reactive Capability
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8
1 Time Active Reactive Connectio Speed Freq Logic / Statcom or
Power Power n Point /Frequenc Injectio Test Windfarm
Voltage y n Start Reactive
# # # Power
#
ECP
Page 53 of 99
Issue 6 Revision 17 04 September 2023
Col 9 Col 10 Col 11 Col 12 Col 13 Col 14 Col 15 Col 16
1 Power
Availa
ble
Wind Wind Voltage
2 State
Speed Direction Setpoint
of
Charg
e
# Columns may be left blank but the column must still be included in the files
ECP.A.4.3.7.3.2 Offshore Power Park Modules Voltage Control & Reactive Capability
ECP.A.4.3.8.1 Where test results are completed without the presence of The Company but
are relied upon as evidence of the compliance they should be accompanied by
a logsheet. This sheet should be legible, in English and detail the items as
indicated below:
Time and Date of test;
ECP
Page 54 of 99
Issue 6 Revision 17 04 September 2023
Name of Power Station and Power Generating Module if applicable;
Name of Test engineer(s) and company name;
Name of Users representative(s) and company name;
Type of testing being undertake eg Voltage Control;
Ambient conditions eg. temperature, pressure, wind speed, wind direction;
and
Controller settings, eg voltage slope, frequency droop, voltage setpoint, UEL
& OEL settings
ECP.A.4.3.8.2 For each test the following items should be recorded as relevant to the type of
test being undertaken. Where there is uncertainty on the information to be
recorded this should be discussed with The Company in advance of the test.
ECP
Page 55 of 99
Issue 6 Revision 17 04 September 2023
System Frequency;
For CCGT Modules, Active Power for the individual units (GT &ST);
For boiler plant, HP steam pressure;
Droop setting of controller if applicable;
Number of Power Park Units in service in each Power Park Module, if
applicable; and
For offshore connections Offshore Grid Entry Point Active Power for
each Power Park Module.
ECP.A.4.3.8.3 Material changes during the test period should be recorded e.g. Generating
Units tripping / starting, changes to tapchange positions.
ECP
Page 56 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 5
ECP.A.5.1 SCOPE
ECP.A.5.1.1 This Appendix sets out the tests contained therein to demonstrate compliance
with the relevant clauses of the European Connection Conditions of the Grid
Code. This Appendix shall be read in conjunction with the ECP with regard to
the submission of the reports to The Company.
ECP.A.5.1.2 The tests specified in this Appendix will normally be sufficient to demonstrate
compliance however The Company may:
(i) agree an alternative set of tests provided The Company deem the
alternative set of tests sufficient to demonstrate compliance with the
Grid Code and Bilateral Agreement; and/or
If:
then notwithstanding the provisions above, the full testing requirements set out
in this Appendix will be applied.
ECP.A.5.1.3 The Generator is responsible for carrying out the tests set out in and in
accordance with this Appendix and the Generator retains the responsibility for
the safety of personnel and plant during the test. The Company will witness
all of the tests outlined or agreed in relation to this Appendix unless The
Company decides and notifies the Generator otherwise. Reactive Capability
tests may be witnessed by The Company remotely from The Company
control centre. For all on site, The Company witnessed tests the Generator
should ensure suitable representatives from the Generator and manufacturer
(if appropriate) are available on site for the entire testing period. In all cases
the Generator shall provide suitable monitoring equipment to record all
relevant test signals as outlined below in ECP.A.6.1.5.
ECP
Page 57 of 99
Issue 6 Revision 17 04 September 2023
Generator shall complete the Integral Equipment Test procedure in
accordance with OC.7.5.
ECP.A.5.1.7 The Company will permit relaxation from the requirement ECP.A.5.2 to
ECP.A.5.9 where an Equipment Certificate for the Synchronous Power
Generating Module has been provided which details the characteristics from
tests on a representative machine with the same equipment and settings and
the performance of the Synchronous Power Generating Module can, in The
Company’s opinion, reasonably represent that of the installed Synchronous
Power Generating Module at that site. For Type B, Type C and Type D
Power Generating Modules the relevant Equipment Certificate must be
supplied in the Power Generating Module Document or Users Data File
structure as applicable.
ECP.A.5.1.8 In the case of a co-located site, for example Electricity Storage Modules or
Grid Forming Plant connected within a new or existing Power Station, The
Company will accept test results to demonstrate compliance at the Grid Entry
Point or User System Entry Point (if Embedded) through a combination of
the capabilities of the Power Generating Modules (which could include Grid
Forming Plant) and Electricity Storage Modules or Electricity Storage
Modules (which could include a Grid Forming Plant) and Generating Units
or Power Park Modules. Generators should however be aware that for the
purposes of testing, full Grid Code compliance should be demonstrated when,
for example, the Electricity Storage Module or Grid Forming Plant is out of
service and the remaining Power Generating Module is in service or the
Electricity Storage Module or Grid Forming Plant is in service and the
Power Generating Module is out of service. In the case of a Synchronous
Electricity Storage Module, The Company would expect the full set of tests
to be completed as detailed in ECP.A.5.2 to ECP.A.5.9.
ECP.A.5.2.1 The open circuit step response of the Excitation System will be tested by
applying a voltage step change from 90% to 100% of the nominal
Synchronous Power Generating Module terminal voltage, with the
Synchronous Power Generating Module on open circuit and at rated speed.
ECP.A.5.2.2 The test shall be carried out prior to synchronisation in accordance with CP.6.4.
This is not witnessed by The Company unless specifically requested by The
Company. Where The Company is not witnessing the tests, the Generator
shall supply the recordings of the following signals to The Company in an
electronic spreadsheet format:
ECP.A.5.2.3 Results shall be legible, identifiable by labelling, and shall have appropriate
scaling.
ECP.A.5.3.1 The test shall normally be carried out prior to synchronisation in accordance
with ECP.6.2.4 or ECP.6.3.4 Equipment Certificates or Manufacturer’s Test
Certificates may be used where appropriate may be used if agreed by The
Company.
ECP
Page 58 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.5.3.2 This is not witnessed by The Company. Graphical and tabular representations
of the results in an electronic spreadsheet format showing per unit open circuit
terminal voltage and short circuit current versus per unit field current shall be
submitted to The Company.
ECP.A.5.3.3 Results shall be legible, identifiable by labelling, and shall have appropriate
scaling.
ECP.A.5.4.1 The time domain performance of the Excitation System shall be tested by
application of voltage step changes corresponding to 1% and 2% of the nominal
terminal voltage.
(ii) The time domain performance of the Excitation System shall be tested
by application of voltage step changes corresponding to 1% and 2% of
the nominal terminal voltage, repeating with and without the PSS in
service.
(iii) The frequency domain tuning of the PSS shall also be demonstrated by
injecting a 0.2Hz-3Hz band limited random noise signal into the
Automatic Voltage Regulator Setpoint with the Synchronous
Generating Unit operating at points specified by The Company (up to
rated MVA output).
(iv) The PSS gain margin shall be tested by increasing the PSS gain
gradually to threefold and observing the Synchronous Generating Unit
steady state Active Power output.
(v) The interaction of the PSS with changes in Active Power shall be tested
by application of a +0.5Hz frequency injection to the governor while the
Synchronous Generating Unit is selected to Frequency Sensitive
Mode.
(vii) Where the Bilateral Agreement requires that the PSS is in service, at a
specified loading level, additional testing witnessed by The Company
will be required during the commissioning process before the
Synchronous Power Generating Module may exceed this output level.
(viii) Where the Excitation System includes a PSS, the Generator shall
provide a suitable noise source to facilitate noise injection testing.
ECP
Page 59 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.5.4.3 The following typical procedure is provided to assist Generators in drawing up
their own site specific procedures for The Company witnessed PSS Tests.
ECP.A.5.5.4 The Under-excitation Limiter will normally be tested at low active power
output and at maximum Active Power output.
ECP.A.5.6.2 If the Over-excitation Limiter has multiple levels to account for heating
effects, an explanation of this functionality will be necessary and if appropriate,
a description of how this can be tested.
ECP
Page 61 of 99
Issue 6 Revision 17 04 September 2023
hold
• Wait until Over-excitation Limiter operates after sufficient
time delay to bring back the excitation back to the limit.
• Remove step returning AVR voltage setpoint to nominal.
Over-excitation Limit restored to its normal operating value.
PSS on.
ECP.A.5.7.3 The test procedure, time and date will be agreed with The Company and will
be to the instruction of The Company control centre and shall be monitored
and recorded at both The Company control centre and by the Generator.
ECP.A.5.7.4 Where the Generator is recording the voltage, Active Power and Reactive
Power at the HV connection point the voltage for these tests Active Power
and Reactive Power at the Synchronous Power Generating Module
terminals may also be included. The results shall be supplied in an electronic
spreadsheet format. Where applicable the Synchronous Power Generating
Module transformer tapchanger position should be noted throughout the test
period.
ECP
Page 62 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.5.8.1 The governor and load controller response performance will be tested by
injecting simulated frequency deviations into the governor and load controller
systems. Such simulated frequency deviation signals must be injected
simultaneously at both speed governor and load controller setpoints. For
CCGT modules, simultaneous injection into all gas turbines, steam turbine
governors and module controllers is required.
ECP.A.5.8.2 Prior to witnessing the governor tests set out in ECP.A.5.8.6, The Company
requires the Generator to conduct the preliminary tests detailed in
ECP.A.5.8.4 and send the results to The Company for assessment unless
agreed otherwise by The Company. The results should be supplied in an
electronic spreadsheet format. These tests shall be completed at least two
weeks prior to the witnessed governor response tests.
ECP.A.5.8.4 Prior to conducting the full set of tests as per ECP.A.5.8.6, Generators are
required to conduct a preliminary set of tests below to confirm the frequency
injection method is correct and the plant control performance is within
expectation. The test numbers refer to Figure 1 below. With the plant running
at 80% of full load, the following frequency injections shall be applied.
ECP.A.5.8.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at
a minimum rate of 1 Hz to allow The Company to assess the plant
performance from the initial transients (seconds) to the final steady state
conditions (5-15 minutes depending on the plant design). This is not witnessed
by The Company. The Generator shall supply the recordings including data
to The Company in an electronic spreadsheet format. Results shall be legible,
identifiable by labelling, and shall have appropriate scaling.
ECP
Page 63 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.5.8.6 The tests are to be conducted at a number of different Module Load Points
(MLP). The load points are conducted as shown below unless agreed
otherwise by The Company.
ECP.A.5.8.7 The tests are divided into the following three types;
ECP.A.5.8.8 There should be sufficient time allowed between tests for control systems to
reach steady state. Where the diagram states ‘HOLD’ the current injection
should be maintained until the Active Power (MW) output of the Synchronous
Power Generating Module or CCGT Module has stabilised or 90 seconds,
whichever is the longer. The frequency response capability test (see Figure 1)
injection signal shall be returned to zero at the same rate at which it was
applied. The Company may require repeat tests should the tests give
unexpected results. When witnessed by the Company each test should be
carried out as a separate injection, when not witnessed by the Company there
must be sufficient time allowed between tests for the Plant to have reached a
stable steady state operating condition or 90 seconds, whichever is the longer.
ECP
Page 64 of 99
Issue 6 Revision 17 04 September 2023
0.6
HOLD
HOLD
-0.4
HOLD
HOLD
-0.6
-0.8
Response (MW)
+
Typical
HF Ramp
HF Ramp
HF Ramp
LF Ramp
LF Ramp
LF Ramp
LF Event
LF Event
Profile 1
Profile 2
+0.5Hz
+0.1Hz
+0.2Hz
-0.2Hz
-0.1Hz
-0.5Hz
Load
Point
MLP6 * * 1 2 3 * 4 *
MLP5 5 * * 6 * * 7 *
MLP4 8 9 10 11 12 13 14 *
MLP3 15 * * * * * 16 17
MLP2 18 * * 19 20 21 * 22
MLP1 23 * * 24 25 * * 26
ECP
Page 65 of 99
Issue 6 Revision 17 04 September 2023
HOLD*
1.6
1.2
0.8
HOLD BC2/ BC4
Frequency (Hz)
HOLD
HOLD
0.4
HOLD
0 2s (J) 32s
0
0 1s 0 30s
HOLD
HOLD
-0.4
BC5
HOLD
-0.8 BC6
HOLD*
-1.2
HOLD
-1.6 -2Hz
Response (MW)
BC6
+
BC5
Typical
_ BC4
BC2
Load Point +2.0* +0.02 -0.2 +0.2 -0.5 +0.5 +/-0.6 -1.0 -2.0 0**
MLP6 BC1 O BC2 L
MLP6 LFSM BC3 BC4
MLP5 A
MLP4 D/E F G *H I J M
MLP4 LFSM BC5/6 N
MLP3
MLP2 P Q
MLP1 K
Figure 2: Frequency Response Capability LFSM-O, LFSM-U and FSM Step Response Tests
ECP.A.5.8.9 The Target Frequency adjustment facility should be demonstrated from the
normal control point within the range of 49.9Hz to 50.1Hz by step changes to
the Target Frequency setpoint as indicated in ECP.A.5.8 Figure 3 while
operating at MLP4.
ECP.A.5.9.1 Where the plant design includes active control function or functions to deliver
ECC.6.3.3 compliance, the Generator will propose and agree a test procedure
with The Company, which will demonstrate how the Synchronous Power
Generating Module Active Power output responds to changes in System
Frequency and ambient conditions (e.g. by Frequency and temperature
injection methods).
ECP.A.5.9.2 The Generator shall inform The Company if any load limiter control is
additionally employed.
ECP.A.5.9.3 With the setpoint to the signals specified in ECP.A.4, The Company will agree
with the Generator which additional control system parameters shall be
monitored to demonstrate the functionality of ECC.6.3.3 compliance systems.
Where The Company recording equipment is not used, results shall be
supplied to The Company in an electronic spreadsheet format
ECP
Page 67 of 99
Issue 6 Revision 17 04 September 2023
(iii) The test result shall demonstrate the ability of the Electricity Storage
Module to meet the requirements of ECC.6.3.7.2.3. When the test
injection signal is held at 49.0Hz, the Active Power output of the
Synchronous Electricity Storage Module should achieve a steady
state operating point in no more than 0.5 seconds and this should be
maintained whilst the test Frequency signal is held at 49.0Hz.
(iv) The above tests described (i) – (iii) above shall be repeated but the
minimum test frequency applied shall be to 48.8Hz as shown in Figure
5.
(v) The above tests shall be repeated when the Synchronous Electricity
Storage Module is operating at 40% of its Maximum Import Power.
ECP.A.5.8 Figure 4
ECP.A.5.8 Figure 5
ECP
Page 68 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 6
ECP.A.6.1 SCOPE
ECP.A.6.1.1 This Appendix outlines the general testing requirements for Power Park
Modules and OTSDUA to demonstrate compliance with the relevant aspects
of the Grid Code, Ancillary Services Agreement and Bilateral Agreement.
The tests specified in this Appendix will normally be sufficient to demonstrate
compliance however The Company may:
If:
then notwithstanding the provisions above, the full testing requirements set out
in this Appendix will be applied.
ECP.A.6.1.2 The Generator is responsible for carrying out the tests set out in and in
accordance with this Appendix and the Generator retains the responsibility for
the safety of personnel and plant during the test. The Company will witness
all of the tests outlined or agreed in relation to this Appendix unless The
Company decides and notifies the Generator otherwise. Reactive Capability
tests may be witnessed by The Company remotely from The Company
control centre. For all on site The Company witnessed tests the Generator
ECP
Page 69 of 99
Issue 6 Revision 17 04 September 2023
must ensure suitable representatives from the Generator and / or Power Park
Module manufacturer (if appropriate) and/or OTSDUA manufacturer (if
appropriate) are available on site for the entire testing period. In all cases and
in addition to any recording of signals conducted by The Company, the
Generator shall record all relevant test signals as outlined in ECP.A.4.
ECP.A.6.1.3 In addition to the dynamic signals supplied in ECP.A.4 the Generator shall
inform The Company of the following information prior to the commencement
of the tests and any changes to the following, if any values change during the
tests:
ECP.A.6.1.4 The Generator shall submit a detailed schedule of tests to The Company in
accordance with CP.6.3.1, and this Appendix.
ECP.A.6.1.5 Prior to the testing of a Power Park Module or OTSDUA, the Generator shall
complete the Integral Equipment Tests procedure in accordance with
OC.7.5.
ECP.A.6.1.6 Partial Power Park Module or OTSDUA testing as defined in ECP.A.6.2 and
ECP.A.6.3 is to be completed at the appropriate stage in accordance with
ECP.6, ECP6.4A, ECP6.4B.
ECP.A.6.1.8 Where OTSDUW Arrangements apply and prior to the OTSUA Transfer
Time any relevant OTSDUW Plant and Apparatus shall be considered within
the scope of testing described in this Appendix. Performance shall be
assessed against the relevant Grid Code requirements for OTSDUW Plant
and Apparatus at the Interface Point and other Generator Plant and
Apparatus at the Offshore Grid Entry Point. This Appendix should be read
accordingly.
ECP.A.6.1.9 The Company will permit relaxation from the requirement ECP.A.6.2 to
ECP.A.6.8 where an Equipment Certificate for the Power Park Module has
been provided which details the characteristics from tests on a representative
installation with the same equipment and settings and the performance of the
Power Park Module can, in The Company’s opinion, reasonably represent
that of the installed Power Park Module at that site. For Type B, Type C and
Type D Power Park Modules, the relevant Equipment Certificate must be
supplied in the Power Generating Module Document or Users Data File
structure as applicable.
ECP.A.6.1.10 In the case of a co-located site, for example Electricity Storage Modules or
Grid Forming Plant connected within a new or existing Power Station, The
Company will accept test results to demonstrate compliance at the Grid Entry
Point or User System Entry Point (if Embedded) through a combination of
the capabilities of the Power Generating Modules (which could include a Grid
Forming Plant) and Electricity Storage Modules or Electricity Storage
Modules (which could include a Grid Forming Plant) and Generating Units
or Power Park Modules. Generators should however be aware that for the
purposes of testing, full Grid Code compliance should be demonstrated when,
for example, the Electricity Storage Module or Grid Forming Plant is out of
service and the remaining Power Generating Module is in service or the
Electricity Storage Module or Grid Forming Plant is in service and the Power
Generating Module is out of service. In the case of a Non-Synchronous
ECP
Page 70 of 99
Issue 6 Revision 17 04 September 2023
Electricity Storage Module, The Company would expect the full set of tests
to be completed as detailed in ECP.A.6.2 to ECP.A.6.8.
ECP.A.6.2 Pre 20% (or <50MW) Synchronised Power Park Module Basic Voltage
Control Tests
ECP.A.6.2.1 Before 20% of the Power Park Module (or 50MW if less) has commissioned,
either voltage control test ECP.A.6.5.6(i) or (ii) must be completed in
accordance with ECP.6, ECP.6A or ECP.6B. In the case of an Offshore
Power Park Module the test must be completed by the Generator undertaking
OTSDUW or the Offshore Transmission Licencee under STCP19-5.
ECP.A.6.2.2 In the case of an Offshore Power Park Module which provides all or a portion
of the Reactive Power capability as described in ECC.6.3.2.5.2 or
ECP.6.3.2.6.3 and / or voltage control requirements as described in
ECC.6.3.8.5 to enable an Offshore Transmission Licensee to meet the
requirements of STC Section K, the Generator is required to cooperate with
the Offshore Transmission Licensee to conduct the 20% voltage control test.
The results in relation to the Offshore Power Park Module will be assessed
against the requirements in the Bilateral Agreement.
ECP.A.6.3 Power Park Modules with Maximum Capacity ≥100MW Pre 70% Power
Park Module Tests
ECP.A.6.3.1 Before 70% but with at least 50% of the Power Park Module commissioned
the following Limited Frequency Sensitive tests as detailed in ECP.A.6.6.2
must be completed.
(a) BC3
(b) BC4
ECP.A.6.4.1 This section details the procedure for demonstrating the reactive capability of
an Onshore Power Park Module or an Offshore Power Park Module or
OTSDUA which provides all or a portion of the Reactive Power capability as
described in ECC.6.3.2.5.2 or ECP.6.3.2.6.3 as applicable (for the avoidance
of doubt, an Offshore Power Park Module which does not provide part of the
Offshore Transmission Licensee Reactive Power capability as described in
ECC.6.3.2.5.1 and ECP.6.3.2.6.1 should complete the Reactive Power
transfer / voltage control tests as per section ECP.A.6.8). These tests should
be scheduled at a time where there are at least 95% of the Power Park Units
within the Power Park Module in service. There should be sufficient MW
resource forecasted in order to generate at least 85% of Maximum Capacity
of the Power Park Module.
ECP.A.6.4.2 The tests shall be performed by modifying the voltage set-point of the voltage
control scheme of the Power Park Module or OTSDUA by the amount
necessary to demonstrate the required reactive range. This is to be conducted
for the operating points and durations specified in ECP.A.6.4.5.
ECP
Page 71 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.6.4.4 In the case where the Reactive Power metering point is not at the same
location as the Reactive Power capability requirement, then an equivalent
Reactive Power capability for the metering point shall be agreed between the
Generator and The Company.
(vii) Operation at less than 20% Maximum Capacity and unity Power
Factor for 5 minutes. This test only applies to systems which do not
offer voltage control below 20% of Maximum Capacity.
ECP.A.6 Within this ECP, lagging Reactive Power is the export of Reactive Power
from the Power Park Module to the Total System and leading Reactive
Power is the import of Reactive Power from the Total System to the Power
Park Module or OTSDUA.
ECP
Page 72 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.6.5.1 This section details the procedure for conducting voltage control tests on
Onshore Power Park Modules or OTSDUA or an Offshore Power Park
Module which provides all or a portion of the voltage control capability as
described in ECC.6.3.8.5 (for the avoidance of doubt, Offshore Power Park
Modules which do not provide part of the Offshore Transmission Licensee
voltage control capability as described in CC6.3.8.5 should complete the
Reactive Power transfer / voltage control tests as per section ECP.A.6.8).
These tests should be scheduled at a time when there are at least 95% of the
Power Park Units within the Power Park Module in service. There should be
sufficient MW resource forecasted in order to generate at least 65% of
Maximum Capacity of the Onshore Power Park Module. An Embedded
Generator or Embedded Generators undertaking OTSDUW should also
liaise with the relevant Network Operator to ensure all requirements covered
in this section will not have a detrimental effect on the Network Operator’s
System.
ECP.A.6.5.2 The voltage control system shall be perturbed with a series of step injections
to the Power Park Module voltage setpoint, and where possible, multiple up-
stream transformer taps. In the case of an Offshore Power Park Module
providing part of the Offshore Transmission Licensee voltage control
capability this may require a series of step injections to the voltage setpoint of
the Offshore Transmission Licensee control system.
ECP.A.6.5.3 For steps initiated using network tap changers, the Generator will need to
coordinate with The Company or the relevant Network Operator as
appropriate. The time between transformer taps shall be at least 10 seconds
as per ECP.A.6.5 Figure 1.
ECP.A.6.5.4 For a step injection into the Power Park Module or OTSDUA voltage setpoint,
steps of ±1%, ±2% and ±4% (or larger if required by The Company) shall be
applied to the voltage control system setpoint summing junction. The injection
shall be maintained for a minimum of 10 seconds as per ECP.A.6.5 Figure 2.
ECP.A.6.5.5 Where the voltage control system comprises of discretely switched Plant and
Apparatus (eg. mechanically switched shunt reactors or capacitors) additional
tests will be required to demonstrate that overall performance of the voltage
control system when switching these devices as part of the response is in
accordance with Grid Code and Bilateral Agreement requirements.
(i)
Voltage
Time
1 tap
10s
minimum
ECP
Page 73 of 99
Issue 6 Revision 17 04 September 2023
(ii)
Applied
Voltage
Step 4%
2%
1% Time
10s
minimum
ECP.A.6.5 Figure 2 – Step injection sequence for voltage control tests
ECP.A.6.5.7 In the case of OTSDUA, where the Bilateral Agreement specifies additional
damping facilities, additional testing to demonstrate these damping facilities
may be required.
ECP.A.6.5.8 In the case of Power Park Modules that do not provide voltage control down
to zero Active Power a test to demonstrate the smooth transition from voltage
control mode to unity Power Factor shall be carried out. The Power Park
Module voltage setpoint should be altered to produce lagging Reactive Power
or absorbing leading Reactive Power at a low Active Power level where
voltage control is provided. The Power Park Module Active Power should
then be reduced to zero Active Power as a ramp over a short period (60
seconds is suggested).
ECP.A.6.6.1 This section describes the procedure for performing frequency response
testing on a Power Park Module. These tests should be scheduled at a time
where there are at least 95% of the Power Park Units within the Power Park
Module in service. There should be sufficient MW resource forecasted in order
to generate at least 65% of Maximum Capacity of the Power Park Module.
ECP.A.6.6.4 Prior to conducting the full set of tests as per ECP.A.6.6.6, Generators are
ECP
Page 74 of 99
Issue 6 Revision 17 04 September 2023
required to conduct the preliminary set of tests below to confirm the frequency
injection method is correct and the plant control performance is within
expectation. The test numbers refer to Figure 1 below. The test should be
conducted when sufficient MW resource is forecast in order to generate at least
65% of Maximum Capacity of the Power Park Module. The following
frequency injections shall be applied when operating at module load point 4.
ECP.A.6.6.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at
a minimum rate of 1 Hz to allow The Company to assess the plant
performance from the initial transients (seconds) to the final steady state
conditions (5-15 minutes depending on the plant design). This is not witnessed
by The Company. The Generator shall supply the recordings including data
to The Company in an electronic spreadsheet format. Results shall be legible,
identifiable by labelling, and shall have appropriate scaling.
ECP.A.6.6.6 The tests are to be conducted at a number of different Module Load Points
(MLP). In the case of a Power Park Module the module load points are
conducted as shown below unless agreed otherwise by The Company.
ECP.A.6.6.7 The tests are divided into the following two types;
ECP
Page 75 of 99
Issue 6 Revision 17 04 September 2023
(ii) System islanding and step response tests as shown by ECP.A.6.6.
Figure 2.
(iii) Frequency response tests in Limited Frequency Sensitive Mode
(LFSM) to demonstrate LFSM-O and LFSM-U capability as shown by
ECP.A.6.6 Figure 2.
ECP.A.6.6.8 There should be sufficient time allowed between tests for control systems to
reach steady state (depending on available power resource). Where the
diagram states ‘HOLD’ the current injection should be maintained until the
Active Power (MW) output of the Power Park Module has stabilised or 90
seconds, whichever is the longer. All frequency response tests should be
removed over the same timescale for which they were applied. The Company
may require repeat tests should the response volume be affected by the
available power, or if tests give unexpected results. When witnessed by The
Company each test should be carried out as a separate injection, when not
witnessed by The Company there must be sufficient time allowed between
tests for the Active Power (MW) output of the Power Park Module to have
stabilised or 90 seconds, whichever is the longer.
0.6
HOLD
0.4
Frequency (Hz)
HOLD
0.2
HOLD
0 10s 30s 60s 10s 10s 10s 0 10s 30s 60s
0
10s 10s 10s
HOLD
-0.2
HOLD
HOLD
-0.4
HOLD
HOLD
-0.6
-0.8
Response (MW)
+
Typical
_
HF Ramp
HF Ramp
HF Ramp
LF Ramp
LF Ramp
LF Ramp
LF Event
LF Event
Profile 1
Profile 2
+0.5Hz
+0.1Hz
+0.2Hz
-0.2Hz
-0.1Hz
-0.5Hz
Load
Point
MLP6 * * 1 2 3 * 4 *
MLP5 5 * * 6 * * 7 *
MLP4 8 9 10 11 12 13 14 *
MLP3 15 * * * * * 16 17
MLP2 18 * * 19 20 21 * 22
MLP1 23 * * 24 25 * * 26
ECP
Page 76 of 99
Issue 6 Revision 17 04 September 2023
HOLD*
1.6
1.2
0.8
HOLD BC2/ BC4
Frequency (Hz)
HOLD
HOLD
0.4
HOLD
0 2s (J) 32s
0
0 1s 0 30s
HOLD
HOLD
-0.4
BC5
HOLD
-0.8 BC6
HOLD*
-1.2
HOLD
-1.6 -2Hz
Response (MW)
BC6
+
BC5
Typical
_ BC4
BC2
Load Point +2.0* +0.02 -0.2 +0.2 -0.5 +0.5 +/-0.6 -1.0 -2.0 0**
MLP6 BC1 O BC2 L
MLP6 LFSM BC3 BC4
MLP5 A
MLP4 D/E F G *H I J M
MLP4 LFSM BC5/6 N
MLP3
MLP2 P Q
MLP1 K
ECP.A.6.6.9 The Target Frequency adjustment facility should be demonstrated from the
ECP
Page 77 of 99
Issue 6 Revision 17 04 September 2023
normal control point within the range of 49.9Hz to 50.1Hz by step changes to
the Target Frequency setpoint as indicated in ECP.A.6.6 Figure 3 while
operating at MLP4.
(iii) The test result shall demonstrate the ability of the Electricity Storage
Module to meet the requirements of ECC.6.3.7.2.3. When the test
injection signal is held at 49.0Hz, the Active Power output of the Non-
Synchronous Electricity Storage Module should achieve a steady
state operating point in no more than 0.5 seconds and this should be
maintained whilst the test Frequency signal is held at 49.0Hz.
(iv) The above tests described (i) – (iii) above shall be repeated but the
minimum test frequency applied shall be to 48.8Hz as shown in Figure
5.
(v) The above tests shall be repeated when the Non-Synchronous
Electricity Storage Module is operating at 40% of its Maximum
Import Power.
ECP
Page 78 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.6.6 Figure 4
ECP.A.6.6 Figure 5
ECP.A.6.7.1 This section describes the procedure for conducting Fault Ride Through tests
on a single Power Park Unit as required by ECP.7.2.2(d).
ECP.A.6.7.2 The test circuit will utilise the full Power Park Unit (e.g. in the case of a wind
turbine it would include the full wind turbine nacelle structure, all inverters and
converters along with step up transformer to medium voltage, all control
systems including pitch control emulation) and shall be conducted with
sufficient power input resource available to produce at least 95% of the
Maximum Capacity of the Power Park Unit. The test will comprise of a
number of controlled short circuits applied to a test network to which the Power
Park Unit is connected, typically comprising of the Power Park Unit
transformer and a test impedance or other decoupling equipment to shield the
connected network from voltage dips at the Power Park Unit terminals.
ECP
Page 79 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.6.7.3 In each case, the tests should demonstrate the minimum voltage at the Power
Park Unit terminals or High Voltage side of the Power Park Unit transformer
which the Power Park Unit can withstand for the length of time specified in
ECP.A.6.7.5. Any test results provided to The Company should contain
sufficient data pre and post fault in order to determine steady state values of
all signals, and the power recovery timescales.
ECP.A.6.7.4 In addition to the signals outlined in ECP.A.4.2. the following signals from either
the Power Park Unit terminals or High Voltage side of the Power Park Unit
transformer should be provided for this test only:
At a suitable frequency rate for fault ride through tests as agreed with The
Company.
ECP.A.6.7.5 The tests should be conducted for the times and fault types indicated in
ECC.6.3.15 as applicable.
ECP.A.6.8 Reactive Power Transfer / Voltage Control Tests for Offshore Power Park
Modules
ECP.A.6.8.1 In the case of an Offshore Power Park Module which provides all or a portion
of the Reactive Power capability as described in ECP.6.3.2.5.2 or ECP.6.3.6.3
and / or voltage control requirements as described in ECC.6.3.8.5 to enable an
Offshore Transmission Licensee to meet the requirements of STC Section
K, the testing, will comprise of the entire control system responding to changes
at the onshore Interface Point. Therefore, the tests in this section ECP.A.6.8
will not apply. The Generator shall cooperate with the relevant Offshore
Transmission Licensee to facilitate these tests as required by The Company.
The testing may be combined with testing of the corresponding Offshore
Transmission Licensee requirements under the STC. The results in relation
to the Offshore Power Park Module will be assessed against the
requirements in the Bilateral Agreement.
ECP.A.6.8.2 In the case of an Offshore Power Park Module which does not provide part
of the Offshore Transmission Licensee Reactive Power capability the
following procedure for conducting Reactive Power transfer control tests on
Offshore Power Park Modules and / or voltage control system as per
ECC.6.3.2.5 and ECC.6.3.2.6 apply. These tests should be carried out prior to
20% of the Power Park Units within the Offshore Power Park Module being
synchronised, and again when at least 95% of the Power Park Units within
the Offshore Power Park Module in service. There should be sufficient power
resource forecast to generate at least 85% of the Maximum Capacity of the
Offshore Power Park Module.
ECP
Page 80 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.6.8.3 The Reactive Power control system shall be perturbed by a series of system
voltage changes and changes to the Active Power output of the Offshore
Power Park Module.
ECP.A.6.8.5 The Active Power output of the Offshore Power Park Module should be
varied by applying a sufficiently large step to the frequency controller
Setpoint/feedback summing junction to cause a 10% change in output of the
Maximum Capacity of the Offshore Power Park Module in a time not
exceeding 10 seconds. This test does not need to be conducted provided that
the frequency response tests as outlined in ECP.A.6.6 are completed.
Voltage
Time
1 tap
>10s
ECP.A.6.8 Figure 1 – Transformer tap sequence for reactive transfer tests
<=10s
Time
Active
Power
Change 10% of
Registered Capacity
ECP
Page 81 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 7
ECP.A.7.1 SCOPE
ECP.A.7.1.1 This Appendix outlines the general testing requirements for HVDC System
Owners to demonstrate compliance with the relevant aspects of the Grid
Code, Ancillary Services Agreement and Bilateral Agreement. The tests
specified in this Appendix will normally be sufficient to demonstrate compliance
however The Company may:
iv) agree a reduced set of tests for subsequent HVDC Equipment following
successful completion of the first HVDC Equipment tests in the case of an
installation comprising of two or more HVDC Systems or DC Connected
Power Park Modules which The Company reasonably considers to be
identical.
If:
ECP.A.7.1.2 The HVDC System Owner is responsible for carrying out the tests set out in
and in accordance with this Appendix and the HVDC System Owner retains
the responsibility for the safety of personnel and plant during the test. The
HVDC System Owner is responsible for ensuring that suitable arrangements
are in place with the Externally Interconnected System Operator to facilitate
testing. The Company will witness all of the tests outlined or agreed in relation
to this Appendix unless The Company decides and notifies the HVDC System
Owner otherwise. Reactive Capability tests if required, may be witnessed by
The Company remotely from The Company control centre. For all on site at
The Company witnessed tests, the HVDC System Owner must ensure
suitable representatives from the HVDC System Owner and / or HVDC
Equipment manufacturer (if appropriate) are available on site for the entire
testing period. In all cases and in addition to any recording of signals
conducted by The Company, the HVDC System Owner shall record all
relevant test signals as outlined in ECP.A.4.
ECP
Page 82 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.7.1.3 In addition to the dynamic signals supplied in ECP.A.4 the HVDC System
Owner shall inform The Company of the following information prior to the
commencement of the tests and any changes to the following, if any values
change during the tests:
ECP.A.7.1.4 The HVDC System Owner shall submit a detailed schedule of tests to The
Company in accordance with CP.6.3.1, and this Appendix.
ECP.A.7.1.5 Prior to the testing of HVDC Equipment, the HVDC System Owner shall
complete the Integral Equipment Tests procedure in accordance with
OC.7.5.
ECP.A.7.1.7 The Company will permit relaxation from the requirement ECP.A.7.2 to
ECP.A.7.5 where an Equipment Certificate for HVDC Equipment has been
provided which details the characteristics from tests on a representative
installation with the same equipment and settings and the performance of the
HVDC Equipment can, in The Company’s opinion, reasonably represent that
of the installed HVDC Equipment at that site. The relevant Equipment
Certificate must be supplied in the Users Data File structure.
ECP.A.7.1.8 The Company may agree a reduction from the requirement ECP.A.7.2 to
ECP.A.7.5 for on-site testing where suitable factory acceptance testing on a
representative installation with the same equipment and settings of the HVDC
Equipment that can, in The Company’s opinion, reasonably represent the
performance of the installed HVDC Equipment at that site. This is also
conditional on The Company and the DC Converter Station owner agreeing
sufficient on site testing of the fully commissioned DC Converter Station to
demonstrate that the factory acceptance tests are valid. If in the reasonable
opinion of The Company, the on-site testing does not demonstrate the factory
acceptance tests are valid then the full set of on-site tests should be carried
out.
ECP.A.7.2.1 This section details the procedure for demonstrating the reactive capability of
HVDC Equipment. These tests should be scheduled at a time where there are
sufficient MW resource forecasted in order to import and export full Maximum
Capacity of the HVDC Equipment.
ECP.A.7.2.2 The tests shall be performed by modifying the voltage set-point of the voltage
control scheme of the HVDC Equipment by the amount necessary to
demonstrate the required reactive range. This is to be conducted for the
operating points and durations specified in ECP.A.7.2.5.
ECP.A.7.2.3 Embedded HVDC System Owners should liaise with the relevant Network
Operator to ensure the following tests will not have an adverse impact upon
the Network Operator’s System as per OC.7.5. In situations where the tests
have an adverse impact upon the Network Operator’s System, The
Company will only require demonstration within the acceptable limits of the
Network Operator. For the avoidance of doubt, these tests do not negate the
requirement to produce a complete HVDC Equipment performance chart as
specified in OC2.4.2.1
ECP.A.7.2.4 In the case where the Reactive Power metering point is not at the same
ECP
Page 83 of 99
Issue 6 Revision 17 04 September 2023
location as the Reactive Power capability requirement, then an equivalent
Reactive Power capability for the metering point shall be agreed between the
HVDC System Owner and The Company.
ECP.A.7.2.5 The following tests shall be completed for both importing and exporting of Active
Power for a DC Converter:
ECP.A.7.2.6 For the avoidance of doubt, lagging Reactive Power is the export of Reactive
Power from the HVDC Equipment to the Total System and leading Reactive
Power is the import of Reactive Power from the Total System to the HVDC
Equipment.
ECP
Page 84 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.7.4 Voltage Control Tests
ECP.A.7.4.1 This section details the procedure for conducting voltage control tests on
HVDC Equipment. These tests should be scheduled at a time where there is
sufficient MW resource in order to import and export Maximum Capacity of
the HVDC Equipment. An Embedded HVDC System Owner should also
liaise with the relevant Network Operator to ensure all requirements covered
in this section will not have a detrimental effect on the Network Operator’s
System.
ECP.A.7.4.2 The voltage control system shall be perturbed with a series of step injections
to the HVDC Equipment voltage Setpoint, and where possible, multiple up-
stream transformer taps.
ECP.A.7.4.3 For steps initiated using network tap changers the HVDC System Owner will
need to coordinate with The Company or the relevant Network Operator as
appropriate. The time between transformer taps shall be at least 10 seconds
as per ECP.A.7.4 Figure 1.
ECP.A.7.4.4 For step injection into the HVDC Equipment voltage setpoint, steps of ±1%,
±2% and ±4% shall be applied to the voltage control system setpoint summing
junction. The injection shall be maintained for 10 seconds as per ECP.A.7.4
Figure 2.
ECP.A.7.4.5 Where the voltage control system comprises of discretely switched plant and
apparatus, additional tests will be required to demonstrate that its performance
is in accordance with Grid Code and Bilateral Agreement requirements.
(i)
Voltage
Time
1 tap
10s
minimum
ECP
Page 85 of 99
Issue 6 Revision 17 04 September 2023
(ii)
Applied
Voltage
Step 4%
2%
1% Time
10s
minimum
ECP.A.7.4 Figure 2 – Step injection sequence for voltage control tests
ECP.A.7.5.1 This section describes the procedure for performing frequency response
testing on HVDC Equipment. These tests should be scheduled at a time where
there is sufficient MW resource in order to import and export full Maximum
Capacity of the HVDC Equipment. The HVDC System Owner is responsible
for ensuring that suitable arrangements are in place with the Externally
Interconnected System Operator to facilitate the Active Power changes
required by these tests
ECP.A.7.5.4 Prior to conducting the full set of tests as per ECP.A.7.5.6, HVDC System
Owners are required to conduct a preliminary set of tests below to confirm the
frequency injection method is correct and the plant control performance is
within expectation. The test numbers refer to Figure 1 below. These tests
should be scheduled at a time where there is sufficient MW resource in order
to export full Maximum Capacity from the HVDC Equipment. The following
frequency injections shall be applied when operating at module load point 4.
ECP
Page 86 of 99
Issue 6 Revision 17 04 September 2023
(Figure1)
8 • Inject -0.5Hz frequency fall over 10 sec
• Hold for a further 20 sec
• At 30 sec from the start of the test, Inject a +0.3Hz
frequency rise over 30 sec.
• Hold until conditions stabilise
• Remove the injected signal as a ramp over 10
seconds
13 • Inject - 0.5Hz frequency fall over 10 sec
• Hold until conditions stabilise
• Remove the injected signal as a ramp over 10
seconds
14 • Inject +0.5Hz frequency rise over 10 sec
• Hold until conditions stabilise
• Remove the injected signal as a ramp over 10
seconds
H • Inject - 0.5Hz frequency fall as a stepchange
• Hold until conditions stabilise
• Remove the injected signal as a stepchange
I • Inject +0.5Hz frequency rise as a stepchange
• Hold until conditions stabilise
• Remove the injected signal as a stepchange
ECP.A.7.5.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at
a minimum rate of 1Hz to allow The Company to assess the plant performance
from the initial transients (seconds) to the final steady state conditions (5-15
minutes depending on the plant design). This is not witnessed by The
Company. The HVDC System Owner shall supply the recordings including
data to The Company in an electronic spreadsheet format. Results shall be
legible, identifiable by labelling, and shall have appropriate scaling.
ECP.A.7.5.6 The tests are to be conducted at a number of different Module Load Points
(MLP). In the case of HVDC Equipment the load points are conducted as
shown below unless agreed otherwise by The Company.
ECP
Page 87 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.7.5.7 The tests are divided into the following two types;
ECP.A.7.5. Fig 1 and 2 are shown for the Importing of Active Power, simulated
frequency polarity should be reversed when exporting Active Power.
ECP.A.7.5.8 There should be sufficient time allowed between tests for control systems to
reach steady state (depending on available power resource). Where the
diagram states ‘HOLD’ the current injection should be maintained until the
Active Power (MW) output of the HVDC Equipment has stabilised or 90
seconds whichever is the longer. All frequency response tests should be
removed over the same timescale for which they were applied. The Company
may require repeat tests should the response volume be affected by the
available power, or if tests give unexpected results. When witnessed by The
Company each test should be carried out as a separate injection, when not
witnessed by The Company there must be sufficient time allowed between
tests for the Active Power (MW) output of the HVDC Equipment to have
stabilised or 90 seconds, whichever is the longer.
ECP.A.7.5.9 The target frequency adjustment facility should be demonstrated from the
normal control point within the range of 49.9Hz to 50.1Hz by step changes to
ECP
Page 90 of 99
Issue 6 Revision 17 04 September 2023
the Target Frequency setpoint as indicated in ECP.A.7.5 Figure 3 while
operating at MLP4.
ECP
Page 91 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 8
SIMULATION STUDIES AND COMPLIANCE TESTING FOR NETWORK OPERATORS AND
NON-EMBEDDED CUSTOMERS PLANT AND APPARATUS
ECP.A.8.1.1 Network Operators shall comply with the following applicable requirements in
respect of EU Grid Supply Points:
(i) Demand disconnection schemes;
(ii) Synchronising; and/or
(iii) low frequency demand disconnection;
ECP.A.8.1.2 The requirements for demand disconnection, other than low frequency demand
disconnection, are pursuant to the requirements of the Bilateral Agreement.
Any requirements for testing shall be agreed with the User where such
requirements are applicable.
ECP.A.8.1.3 The requirements for synchronising (where applicable) shall be pursuant to the
requirements of the Bilateral Agreement and ECC.6.2.3.10. Any
requirements for testing (as applicable) shall be agreed with the User and
carried out during the commissioning process.
ECP.A.8.1.4 Network Operators who are EU Code Users must demonstrate compliance
with the low frequency demand disconnection requirements of ECC.6.4.3,
ECC.A.5 and OC.6.6 for their entire distribution System.
ECP.A.8.2.1 The requirements for operational metering (where required) shall be pursuant
to the requirements of the Bilateral Agreement and ECC.6.5.6. Any applicable
requirements for testing shall be agreed with the User and carried out during
the commissioning process. An Equipment Certificate may be used for this
purpose where agreed with The Company.
ECP.A.8.3.2 The requirements for demand disconnection, other than low frequency demand
disconnection, are pursuant to the requirements of the Bilateral Agreement.
Any requirements for testing shall be agreed with the User.
ECP.A.8.3.3 The requirements for synchronising (where applicable) shall be pursuant to the
requirements of the Bilateral Agreement and ECC.6.2.3.10. Any
requirements for testing (as applicable) shall be agreed with the User and
carried out during the commissioning process.
ECP
Page 92 of 99
Issue 6 Revision 17 04 September 2023
ECP.A.8.3.4 Non-Embedded Customers who are EU Code Users must demonstrate
compliance with the low frequency demand disconnection requirements of
ECC.6.4.3, ECC.A.5 and OC.6.6 of their System.
ECP.A.8.4.1 The requirements for operational metering (where required)) shall be pursuant
to the requirements of the Bilateral Agreement and ECC.6.5.6. Any applicable requirements
for testing shall be agreed with the User and carried out during the commissioning process. An
Equipment Certificate may be used for this purpose where agreed with The
Company.ECP.A.8.5 Common Provisions on Compliance Simulations
ECP.A.8.5.1 Users are required to provide simulation studies or equivalent information to the
satisfaction of The Company in the following circumstances.
(c) The Company may check that the Network Operator or Non-Embedded
Customer complies with the requirements of the Grid Code by carrying out
its own compliance simulations based on the simulation reports, models and
test measurements submitted under the Data Registration Code.
.
ECP.A.8.5.3 The Company will supply (under PC.A.8) upon request to the Network
Operator or Non-Embedded Customer, data to enable the Network
Operator or Non-Embedded Customer to carry out the required simulations
or supply the equivalent information required under the Data Registration
Code.
ECP.A.8.6.1 Networks Operators who are also EU Code Users, are required to provide
simulation studies (or make available equivalent information) at each EU Grid
Supply Point to demonstrate compliance with the Reactive Power capability
requirements set out in ECC.6.4.5. The study or equivalent information
provided shall include a steady state simulation model under both maximum
ECP
Page 93 of 99
Issue 6 Revision 17 04 September 2023
and minimum demand conditions. In addition, the model or equivalent
information provided shall include the conditions when the Reactive Power
export is at an Active Power flow of less than 25% of the Maximum Import
Capability as detailed under ECC.6.4.5.2. In all cases the models or equivalent
information submitted shall be agreed and approved with The Company.
ECP.A.8.7.1 None Embedded Customers who are also EU Code Users are required at
each EU Grid Supply Point to provide simulation studies (or equivalent
information) to demonstrate compliance with the Reactive Power capability
requirements set out in ECC.6.4.5. The study or equivalent information
provided shall include a steady state simulation model under both maximum
and minimum demand conditions and with and without on-site generation. In
all cases the models or equivalent information submitted shall be agreed and
approved with The Company.
ECP.A.8.8.1 To satisfy the requirements of ECC.6.4.5, EU Code Users who are either
Network Operators or Non-Embedded Customers shall ensure their Plant
and Apparatus is equipped (where applicable), with the necessary equipment
to measure the Active Power and Reactive Power, at each EU Grid Supply
Point. The requirement for and time frame for compliance monitoring shall be
agreed between The Company and the EU Code User for each EU Grid
Supply Point.
ECP
Page 94 of 99
Issue 6 Revision 17 04 September 2023
APPENDIX 9
COMPLIANCE TESTING FOR GRID FORMING PLANT
ECP.A.9.1 SCOPE
ECP.A.9.1.1 This Appendix outlines the general testing requirements for Users or Non-
CUSC Parties to demonstrate compliance with the relevant aspects of the Grid
Code, Ancillary Services Agreement and Bilateral Agreement. The tests
specified in this Appendix will normally be sufficient to demonstrate compliance
of a GBGF-I, however The Company may:
iv) agree a reduced set of tests for the subsequent GBGF-I following successful
completion of the first Grid Forming tests in the case of an installation
comprising of two or more GBGF-Is which The Company reasonably
considers to be identical if: -
ECP.A.9.1.2 The User or Non-CUSC Party is responsible for carrying out the tests set out
in and in accordance with this Appendix and the User or Non-CUSC Party
retains the responsibility for the safety of personnel and plant during the test.
The Company will witness all of the tests outlined or agreed in relation to this
Appendix unless The Company decides and notifies the User or Non-CUSC
Party otherwise. For all on site at The Company witnessed tests, the User or
Non-CUSC Party must ensure suitable representatives from the Grid
Forming Plant’s manufacturer (if appropriate) are available on site for the
entire testing period. In all cases and in addition to any recording of signals
conducted by The Company, the User or Non-CUSC Party shall record all
relevant test signals as outlined in ECP.A.4.
ECP.A.9.1.3 In addition to the dynamic signals supplied in ECP.A.4, the User or Non-CUSC
Party shall inform The Company of the following information prior to the
commencement of the tests and any changes to the following, if any values
change during the tests:
ECP.A.9.1.4 The User or Non-CUSC Party shall submit a detailed schedule of tests to The
Company in accordance with ECP.6.3.1, and this Appendix.
ECP.A.9.1.5 Prior to the testing of the GBGF-I the User or Non-CUSC Party shall complete
ECP
Page 95 of 99
Issue 6 Revision 17 04 September 2023
the Integral Equipment Tests procedure in accordance with OC.7.5.
ECP.A.9.1.7 The Company will permit relaxation from the requirements in ECP.A.9.1.9
where an Equipment Certificate for GBGF-I has been provided which details
the characteristics from tests on a representative installation with the same
equipment and settings and the performance of the GBGF-I can, in The
Company’s opinion, reasonably represent that of the installed GBGF-I at that
site. The relevant Equipment Certificate must be supplied in the Users Data
File Structure.
ECP.A.9.1.8 Prior to any GBGF-I tests taking place, the User or Non-CUSC Party shall
have completed the relevant compliance tests on the GBGF-I, Power
Generating Module or Generating Unit as required under ECP.A.5 or OC5.
A.2 (as relevant) or Power Park Module as required under ECP.A.6 or OC5.
A.3 (as applicable) or HVDC Systems or DC Converters as required under
ECP.A.7 or OC5. A.4 (as applicable).
ECP.A.9.1.9.1 This section details the procedure for demonstrating Active ROCOF
Response Power. Ideally if the test is being completed as part of a type test
on an isolated network and it is possible to change the frequency of the isolated
network then the tests should be completed using a variable network
Frequency. The Company recognise that it is not possible in a large number
of cases to adjust the network frequency of the network to which the Grid
Forming Plant is connected. If a suitable test network is not available,
performance of the GBGF-I will need to be demonstrated through online
monitoring as detailed in CC.6.6 or ECC.6.6 and simulation studies as required
under ECP.A.3.9.4 will be required during the Interim Operational
Notification Process as provided for under CP.6 or ECP.6 (as applicable).
ECP.A.9.1.9.2 In this test, with the Grid Forming Plant initially running at full load, the test
network frequency is ideally increased from 50Hz to 51 Hz at a rate of 1Hz/s
with measurements of the Grid Forming Plant’s Active ROCOF Response
Power, System Frequency and time in (ms). The test is required to assess
correct operation of the Grid Forming Plant without saturating. This test is
then repeated for a 50 Hz to 49 Hz at a rate of 1Hz/s.
ECP.A.9.1.9.3 These tests are required to assess the Grid Forming Plant’s withstand
capabilities under extreme System Frequencies.
(i) For Grid Forming Plant comprising a GBGF-I the frequency of the test
network is increased from 50Hz to 52Hz at a rate of 2Hz/s with
measurements of the Grid Forming Plant’s Active ROCOF Response
Power, System Frequency and time in (ms).
(ii) For a Grid Forming Plant comprising a GBGF-I the frequency of the
test network is increased from 50Hz to 52Hz at a rate of 1Hz/s with
measurements of the Grid Forming Plant’s Active ROCOF Response
Power, System Frequency and time in (ms).
(iii) For Grid Forming Plant comprising a GBGF-I the frequency of the test
network is decreased from 50Hz to 47 Hz at a rate of 2Hz/s with
measurements of the Grid Forming Plant’s Active ROCOF Response
Power, System Frequency and time in (ms).
ECP
Page 96 of 99
Issue 6 Revision 17 04 September 2023
(iii) For Grid Forming Plant comprising a GBGF-I the frequency of the test
network is decreased from 50Hz to 47 Hz at a rate of 1Hz/s with
measurements of the Grid Forming Plant’s Active ROCOF Response
Power, System Frequency and time in (ms).
ECP.A.9.1.9.4 This test is to demonstrate the Grid Forming Plant’s ability to supply Active
ROCOF Response Power over the full System Frequency range.
(a) With the frequency of the test network set to 50Hz, the GBGF-I
should be initially running at 75% Maximum Capacity or
Registered Capacity, zero MVAr output and both Limited
Frequency Sensitive Mode and Frequency Sensitive Mode
disabled.
(b) The frequency is then increased from 50Hz to 52Hz at a rate of
1Hz/s over a 2 second period. Allow conditions to stabilise for 5
seconds and then decrease the frequency from 52Hz to 47Hz at
a rate of 1Hz/s over a 5 second period. Allow conditions to
stabilise.
(c) Record results of Active ROCOF Response Power, Reactive
Power, voltage and frequency.
(d) The test now needs to be re-run in the opposite direction. The
same initial conditions should be applied as per ECP.A.9.1.9.4(a).
(e) The frequency is then decreased from 50Hz to 47Hz at a rate of
1Hz/s over a 3 second period. Allow conditions to stabilise for 5
seconds and then increase the frequency from 47Hz to 52Hz at a
rate of 1Hz/s over a 5 second period. Allow conditions to stabilise.
(f) Record results of Active ROCOF Response Power, Reactive
Power, voltage and frequency.
ECP.A.9.1.9.5 This test is to demonstrate the Grid Forming Plant’s ability to supply Active
Phase Jump Power under normal operation.
(a) With the frequency of the test network set to 50Hz, the GBGF-I
should be initially running at Maximum Capacity or Registered
Capacity or at its agreed deloaded point, zero MVAr output and
all control actions (e.g. Limited Frequency Sensitive Mode,
Frequency Sensitive Mode and voltage control) disabled.
(b) Apply a positive phase jump of up to the Phase Jump Angle Limit
at the Grid Entry Point or User System Entry Point (if
Embedded).
(c) This test can then be repeated by injecting the same angle into the
Grid Forming Plant’s control system (as indicatively shown in
Figure ECP.A.9.1.9.5). This specific test can be repeated on site
as required for a routine performance evaluation test. It should be
noted that Figure ECP.A.9.1.9.5 is a simplified representation.
Each Grid Forming Plant Owner can use their own design, that
may be very different to Figure ECP.A.9.1.9.5 but should contain
all relevant functions that can include test points and other
equivalent data and documentation. Any additional signals,
measurements, parameters and tests shall be agreed between the
Grid Forming Plant Owner and The Company.
(d) Repeat tests (b) and (c) with a negative injection up to the Phase
Jump Angle Limit.
(e) Record traces of Active Power, Reactive Power, voltage, current
and frequency for a period of 10 seconds after the step change in
phase has been applied.
ECP
Page 97 of 99
Issue 6 Revision 17 04 September 2023
Figure ECP.A.9.1.9.5
As part of these tests, the corresponding Active Power change resulting from
a phase shift will be a function of the local reactance and the location of where
the phase shift is applied in addition to any additional upstream impedance
between the GBGF-I and phase step location.
ECP.A.9.1.9.6 This test is to demonstrate the Grid Forming Plant’s ability to supply Active
Phase Jump Power under extreme conditions. Where it is not possible to
undertake this test as part of a type test, The Company will accept
demonstration through a combination of simulation studies as required under
ECP.A.3.9.4(vi) and online monitoring as required under ECC.6.6.1.9.
(a) With the frequency of the test network set to 50Hz, the Grid
Forming Plant should be initially running at its Minimum Stable
Operating Level or Minimum Stable Generation, zero MVAr
output and all control actions (e.g., Limited Frequency Sensitive
Mode, Frequency Sensitive Mode and voltage control) disabled.
(b) Apply a phase jump of 60 degrees at the connection point of the
GBGF-I or into the Grid Forming Plant’s control system as shown
in Figure ECP.A.9.1.9.5.
(c) Record traces of Active Power, Reactive Power, voltage, current
and frequency for a period of 10 seconds after the step change in
phase has been applied.
(d) Repeat steps (a), (b) and (c) of ECP.A.9.1.9.6 but on this occasion
apply a phase jump equivalent to the positive Phase Jump Angle
Limit at the Grid.
ECP.A.9.1.9.7 This test is to demonstrate the GBGF-Is ability to supply Active Phase Jump
Power, Fault Ride Through and GBGF Fast Fault Current Injection during
a faulted condition. Where it is not possible to undertake this test as part of
a type test, The Company will accept demonstration through a combination
of simulation studies as required under ECP.A.3.9.4(vii) and online
monitoring as required under CC.6.6 and ECC.6.6.1.9.
(a) With the frequency set to 50Hz, the Grid Forming Plant should
be initially running at its Maximum Capacity or Registered
Capacity or at an alternative loading point as agreed with The
Company, zero MVAr output and all control actions (e.g., Limited
ECP
Page 98 of 99
Issue 6 Revision 17 04 September 2023
Frequency Sensitive Mode, Frequency Sensitive Mode and
voltage control) disabled.
(b) Apply a solid three phase short circuit fault at the connection point
in the test network forming part of the type test for 140ms or
alternatively the equivalent of a zero retained voltage for 140ms.
(c) Record traces of Active Power, Reactive Power, voltage, current
and frequency for a period of 10 seconds after the fault has been
applied.
(d) Repeat steps (a) to (c) but on this occasion with fault ride through,
GBGF Fast Fault Current Injection Limited Frequency
Sensitive Mode and voltage control switched into service.
(e) Record traces of Active Power, Reactive Power, voltage, current
and frequency for a period of 10 seconds after the step change in
phase has been applied and confirm correct operation.
ECP.A.9.1.9.8 The final test required is to demonstrate the GBGF-I is capable of contributing
to Active Damping Power. The Grid Forming Plant Owner should configure
their Grid Forming Plant in form or equivalent (as agreed with The Company)
as shown in Figure ECP.A.3.9.6(a) or Figure ECP.A.3.9.6(b) as applicable.
Each Grid Forming Plant Owner can use their own design, that may be very
different to Figures ECP.A.3.9.6(a) or ECP.A.3.9.6 (b) but should contain all
relevant functions.
As part of this test, the Grid Forming Plant Owner is required to inject a signal
into the Grid Forming Plant controller. The results supplied need to verify the
following criteria:-
<END OF ECP>
ECP
Page 99 of 99
Issue 6 Revision 17 04 September 2023
OPERATING CODE NO. 1
(OC1)
DEMAND FORECASTS
CONTENTS
(This contents page does not form part of the Grid Code)
OC1.2 OBJECTIVE
The objectives of OC1 are to:
OC1.2.1 enable the provision of data to The Company by Users in the Programming Phase, Control
Phase and Post-Control Phase; and
OC1.2.2 provide for the factors to be taken into account by The Company when Demand forecasting
in the Programming Phase and Control Phase.
OC1.3 SCOPE
OC1 applies to The Company and to Users which in this OC1 means:
(a) Network Operators, and
(b) Suppliers.
CONTENTS
(This contents page does not form part of the Grid Code)
(c) The Company and each in respect of outages of all Embedded Large Power
Network Operator Stations and in respect of outages of other Plant
and/or Apparatus relating to such Embedded
Large Power Stations;
OC2.4.1.2 Data Provison of Output Usable of Power Generating Modules, Generating Units,
External Interconnection Circuits and Power Park Modules and the Publication of National
Surplus.
OC2.4.1.2.1 In the event that:
a) a Generator referred to in OC2.3.1(a) experiences any unplanned change to the
availability of a Generating Unit and/or Power-Generating Module and/or Power
Park Module or makes a future plan which would impact the availability of a Generating
Unit and/or Power-Generating Module and/or Power Park Module resulting in a
change of level in the Output Usable of that Generating Unit and/or Power-
Generating Module and/or Power Park Module below or above its previously notified
availability, which is expected to last one Settlement Period or longer and up to three
years ahead; or
b) an Interconnector Owner referred to in OC2.3.1(e) experiences any unplanned
change to the availability of an External Interconnection Circuit or makes a future
plan which would impact the availability of an External Interconnection Circuit
resulting in any change in the Output Usable of that External Interconnection Circuit
below or above its previously notified availability, which is expected to last one
Settlement Period or longer and up to three years ahead; or
c) a Restoration Contractors referred to in OC2.3.1(f) experiences any unplanned
change to the availability of their Plant and Apparatus or makes a future plan which
would impact the availability of their Plant and Apparatus which would affect their ability
to contribute to a Local Joint Restoration Plan.
The Generator, Interconnector Owner or Restoration Contractor as provided for in
OC2.3.1(f) shall provide The Company with the best estimate of the revised available Output
Usable profile using one of The Company’s recommended platforms.
For Generators subject to EU Transparency Regulations the Generator shall provide the data
within 1 hour of the unplanned change in availability occurring, and for a planned change to
the availability, the Generator shall provide the data within 1 hour of planning the availability
change in line with EU Transparency Regulations. For Generators not subject to EU
Transparency Regulations the Generator shall provide the data within 24 hours of the
unplanned change in availabiity occurring, and for a planned change to the availability, the
Generator shall provide the data within 24 hours of planning the availability change.
For an unplanned change in availability, the Interconnector Owner shall provide the data
within 1 hour of the unplanned change in availability occurring, and for a planned change to
the availability, the Interconnector Owner shall provide the data within 1 hour of planning the
availability change in line with EU Transparency Regulations.
If the Generator referred to in OC2.3.1(a) provides information relating to multi-shaft
Generating Units then the detail of the individual shaft availability levels, that have been
summed to produce the Output Usable should also be defined within 24 hours.
The Company will then consider the updated Output Usable and takes this into account
in the next calculation and submission to BMRA.
OC2.4.1.2.3 The Company retains the right to contact Generators with Large Power Stations,
Interconnector Owners and Network Operators in reference to planned outages of their
assets in timescales beyond the European Requirements (3 years) up to the 5 year ahead
period to assist in the operational planning of National Electricity Transmisson System
outages.
OC2.4.1.3 Planning of National Electricity Transmission System Outages
OC2.4.1.3.1 Operational Planning Phase - Planning for Financial Years 2 to 5 inclusive ahead
The Company shall plan National Electricity Transmission System outages required in
Years 2 to 5 inclusive required as a result of construction or refurbishment works. This
contrasts with the planning of National Electricity Transmission System outages required
in Years 0 and 1 ahead, when The Company also takes into account National Electricity
Transmission System outages required as a result of maintenance.
Users should bear in mind that The Company will plan the National Electricity
Transmission System outage programme on the basis of the previous year's Final
Generation Outage Programme and if in the event a Generator's, an Interconnector
Owner’s or Network Operator's outages differ from those contained in the Final Generation
Outage Programme, or in the case of Network Operators, those known to The Company,
in any way conflict with the National Electricity Transmission System outage programme,
The Company need not alter the National Electricity Transmission System outage
programme.
This Operational Planning Margin requirements indication will also note the possible level of
High Frequency Response to be utilised by The Company in connection with the operation
of the Balancing Mechanism in the week beginning with the Operational Day commencing
during the subsequent Monday, which level shall be purely indicative.
OC2.4.7 In the event that:
OC2.4.8 The Company will for each day publish the actual largest secured loss of generation (i.e. the
loss of generation against which, as a requirement of the Licence Standards, the National
Electricity Transmission System must be secured) or loss of import from External
Interconnections for each settlement period on The Company’s website.
MW
Rated MW F G
Output
100%
50%
20%
MVAr
A E C D B
LEADING LAGGING
Point A is equivalent (in MVAr) to: 0.95 leading Power Factor at Rated MW output
Point B is equivalent (in MVAr) to: 0.95 lagging Power Factor at Rated MW output
Line F is equivalent (in MVAr) to: Leading Power Factor Reactive Despatch Network Restriction
Line G is equivalent (in MVAr) to: Lagging Power Factor Reactive Despatch Network Restriction
0MW to 150MW
/
151MW to 250MW
/ /
251MW to 300MW
/ /
301MW to 400MW
/ / /
401MW to 450MW
/ / /
451MW to 550MW
/ / / /
Number of units
Power Park Module [unique identifier]
POWER PARK POWER PARK UNITS
UNIT AVAILABILITY Type A Type B Type C Type D
Description
(Make/Model)
Number of units
The Power Park Module Planning Matrix may have as many columns as are required to provide information
on the different make and model for each type of Power Park Unit in a Power Park Module and as many
rows as are required to provide information on the Power Park Modules within each BM Unit. The description
is required to assist identification of the Power Park Units within the Power Park Module and correlation with
data provided under the Planning Code.
POWER 1st 2nd 3rd 4th 5th 6th 1st 2nd 3rd
GENERATING GT GT GT GT GT GT ST ST ST
MODULE
OUTPUT USABLE
MW
0MW to 150MW
/
151MW to 250MW
/ /
251MW to 300MW
/ /
301MW to 400MW
/ / /
401MW to 450MW
/ / /
451MW to 550MW
/ / / /
CONTENTS
(This contents page does not form part of the Grid Code)
OC3.2 OBJECTIVE
OC3.2.1 The objective of OC3 is for The Company to produce a monthly report of incidents and
frequency data. The report and data are important to industry and the Grid Code Review
Panel as they help monitor the effectiveness of the technical requirements in the Grid Code
and Distribution Code.
OC3.3 SCOPE
OC3 applies to The Company.
OC3.4 SYSTEM INCIDENTS REPORT
OC3.4.1 The Company shall prepare and submit to the Grid Code Review Panel monthly a report
titled the System Incidents Report, which shall contain:
(a) a record of each and all of any of the following Events, defined as Significant Events, on
the National Electricity Transmission System:
(i) a loss of infeed or exfeed (import or export including generation, Demand and
interconnection) of =>250MW;
(ii) a Frequency excursion outside the limits 49.7-50.3Hz;
(iii) a fault on the National Electricity Transmission System which:
A. could be linked to the known or reported tripping of 250MW or more as
reported in (i) above; and/or
B. (as detailed in section CC6.1.4) is linked to a change in the Transmission
System voltage of
I. 300kV or greater: > +/-5% for >15min; or
II. 132kV up to 300kV: > +/- 10% for >15min;
(iv) any known demand disconnected >=50MW from the National Electricity
Transmission System or other lesser demand if notified to The Company; and
(v) any Demand Control action taken;
(b) a report of each such Significant Event including the following data in relation to each
Significant Event as appropriate and available:
(i) the time(s) in hh.mm.ss of the Significant Event and any potentially related
occurrences;
(ii) any known or reported loss of Embedded Power Station(s) with locations and
ratings where available;
(iii) the Frequency record (in table and graphical format) at <=1 second intervals for
1 minute before and 1 minute after the Significant Event;
(iv) the Frequency (to 2 decimal places) immediately before the Significant Event;
(v) the Frequency (to 2 decimal places) immediately after the Significant Event;
(vi) the maximum rate of change of Frequency recorded during the Significant
Event over a specified time period of 500ms;
OC3.4.4 The Company shall prepare and publish monthly on the Website, in a spreadsheet form,
System Frequency data at a maximum of one second intervals for the whole month
(Historic Frequency Data) in accordance with the following timescales:
OC3.4.5 The Company will use best endeavours to provide a report or reports (based on either the
historic reporting methodology, or on the Significant Incidents Reports methodology, or a
mix of the two), on events for the period from 1 November 2017 until the first System
Incidents Report pursuant to this Operating Code, such a report or reports to be made
available within 4 months of implementation date of the modification.
OC.3.5.1 The Company shall prepare and publish on their website a report giving date, time and
location of actual three phase, three phase to earth, phase to phase and phase to earth fault
events on the National Electricity Transmission System. Information shall be published as
soon as reasonably practicable following such an event. For faults in which a fault ride through
issue was found, where available, appropriate waveform information will be provided.
OC3.6.2 Where The Company believes that it is appropriate to identify a particular User, connection
site or Plant and Apparatus, The Company shall in the first instance consult the relevant
User and/or manufacturer as applicable to seek agreement for publication.
OC3.6.3 If permission for publication is not granted by the User and/or manufacturer and The
Company believes that it is appropriate to identify a particular User, connection site or Plant
and Apparatus, The Company may ask the Authority for guidance regarding publication.
NOT USED
CONTENTS
(This contents page does not form part of the Grid Code)
OC5.2 OBJECTIVE
The objectives of OC5 are to establish:
(a) that Users comply with the CC or ECC as applicable (including in the case of OTSUA
prior to the OTSUA Transfer Time);
OC5.3 SCOPE
OC5 applies to The Company and to Users, which in OC5 means:
(a) Generators (including those undertaking OTSDUW);
(b) Network Operators;
(c) Non-Embedded Customers;
(d) Suppliers; and
(e) DC Converter Station owners or HVDC Equipment Owners.
OC5.4 MONITORING
OC5.4.1 Parameters to be monitored
The Company will monitor the performance of:
(a) BM Units against their expected input or output derived from their Final Physical
Notification Data and agreed Bid-Offer Acceptances issued under BC2;
(b) compliance by Users with the CC or ECC as applicable; and
(c) the provision by Users of Ancillary Services which they are required or have agreed to
provide.
OC5.4.2 Procedure for Monitoring
OC5.4.2.1 In the event that a BM Unit fails persistently, in The Company's reasonable view, to follow,
in any material respect, its expected input or output or a User fails persistently to comply with
the CC or ECC as applicable, or fails to comply in the case of CC.6.3.15 or ECC 6.3.15 as
applicable, and in the case of response to Frequency, BC3 or to provide the Ancillary
Services it is required, or has agreed, to provide, The Company shall notify the relevant User
giving details of the failure and of the monitoring that The Company has carried out.
OC5.4.2.2 The relevant User will, as soon as possible, and in the case of a failure to comply with the
requirements of CC.6.3.15 or ECC.6.3.15 as applicable, within 2 hours in respect of a
notification to this effect under OC10 or a longer time period only where agreed by The
Company, provide The Company with an explanation of the reasons for the failure and details
of the action that it proposes to take to:
(a) enable the BM Unit to meet its expected input or output or to provide the Ancillary
Services it is required or has agreed to provide, within a reasonable period, or
(b) in the case of a Power Generating Module, Generating Unit (excluding a Power Park
Unit), CCGT Module, Power Park Module, OTSUA (prior to the OTSUA Transfer
Time), HVDC Equipment or DC Converter to comply with the CC or ECC as applicable
and in the case of response to Frequency, BC3 or to provide the Ancillary Services it
is required or has agreed to provide, within a reasonable period.
Genset.
OC5.7.1 General
As provided for in OC9.1.1 there are two ways in which the Total System (or disconnected
part of the Total System in the case of a Partial Shutdown) can be re-established. These
being a top-down approach using Local Joint Restoration Plans or a bottom-up approach
using Distribution Restoration Zone Plans which are necessary in order to satisfy the
requirements of the Electricity System Restoration Standard.
To help achieve this objective, it is essential that Restoration Contractors test their Plant
and Apparatus at regular intervals to demonstrate that there is a high level of confidence that
they will be able to satisfy the requirements of the Grid Code and their Anchor Restoration
Contracts or Top Up Restoration Contracts.
(a) The Company and/or relevant Network Operator shall require a Restoration
Contractor to carry out testing in order to demonstrate that its Plant and Apparatus has
the appropriate capability.
(i) In the case of an Anchor Generating Unit, The Company and/or relevant Network
Operator shall require the Restoration Contractor to carry out a test (either a
Anchor Generating Unit Test or a Anchor Power Station Test) in order to
demonstrate that an Anchor Plant has Anchor Plant Capability.
(ii) In the case of either an Anchor HVDC System or Anchor DC Converter, The
Company or relevant Network Operator shall require the Restoration Contractor
to carry out a test (an Anchor HVDC System Test or Anchor DC Converter Test),
in order to demonstrate that an Anchor HVDC System or Anchor DC Converter has
Anchor Plant Capability.
(iii) In the case of an EU Generator with an Anchor Plant Capability who is also a
Restoration Contractor, The Company and/or relevant Network Operator may also
require the Restoration Contractor to carry out a test (a Quick Resynchronisation
Unit Test) in order to demonstrate that its Anchor Power Station has Quick Re-
Synchronisation Capability.
(iv) In the case of a Top Up Restoration Plant, The Company and/or relevant Network
Operator shall require the Top Up Restoration Contractor to demonstrate that the
requirements of their Top Up Restoration Contract can be fulfilled.
(b) Where The Company and/or relevant Network Operator requires a Restoration
Contractor to undertake testing, the following requirements shall apply:-
(i) Each Anchor Generating Unit within an Anchor Power Station shall be required
to undertake an Anchor Generating Unit Test at least once every three years. The
Company and/or relevant Network Operator shall not require the Anchor
Generating Unit Test to be carried out on more than one Generating Unit at that
Anchor Power Station at the same time, and would not, in the absence of
exceptional circumstances, expect any of the other Generating Units at the Anchor
Power Station to be directly affected by the Anchor Generating Unit Test.
(c) When The Company and/or relevant Network Operator wishes a Restoration
Contractor to carry out either an Anchor Generating Unit Test, an Anchor Power
Station Test, an Anchor System HVDC Test, Quick Re-Synchronisation Test or Top
Up Restoration Test, it shall notify the relevant Restoration Contractor at least 7 days
prior to the time of the test with details of the proposed test.
OC5.7.2 Procedures for Restoration Service Tests
OC5.7.2.1 Anchor Generating Unit Tests
(a) The relevant Generating Unit shall be Synchronised and Loaded.
(b) All the Auxiliary Energy Supplies in the Anchor Power Station in which that
Generating Unit is situated, shall be Shutdown.
(c) The Generating Unit shall be De-Loaded and De-Synchronised and all alternating
current electrical supplies to its Auxiliaries shall be disconnected.
(d) The Auxiliary Energy Supplies to the relevant Generating Unit shall be started, and
shall re-energise the Unit Board of the relevant Generating Unit.
(e) The Auxiliaries of the relevant Generating Unit shall be fed by the Auxiliary Energy
Supplies, via the Unit Board, to enable the relevant Generating Unit to return to
Synchronous Speed.
(f) The relevant Generating Unit shall be Synchronised to the System but not Loaded,
unless a subsequent instruction is issued by The Company or relevant Network
Operator under BC2.
A dead line charge test would require the steps detailed in (i) and (ii) below to be
undertaken. A remote synchronisation test would require the steps detailed in (i) – (iii)
below to be undertaken.
i) Start-Up of one or more of the Generating Units at the Anchor Power Station
under normal operational conditions;
ii) Re-energisation of a dead test section of the Total System as defined in the
Local Joint Restoration Plan or Distribution Restoration Zone Plan as
appropriate; and
iii) Demonstration of the ability to synchronise to a section of the Total System at a
location remote from the Anchor Power Station’s Grid Entry Point or User
System Entry Point (as the case may be).
A dead line charge test is to demonstrate the Anchor Generating Unit’s ability to charge
a pre-defined dead part of the Total System and its ability to control the voltage on that
part of the Total System.
A remote synchronisation test is used to demonstrate the successful operation of a
Transmission Licensee’s or Network Operator’s system synchronising facilities across
individual circuit breakers which are either i) a necessary part of a Local Joint
Restoration Plan or ii) defined in a Distribution Restoration Zone Plan.
When planning a dead line charge test, consideration shall be given to the effect the test
will have on Customers supplied from the part of the Total System that needs to be de-
energised, including whether their supplies would need to be interrupted to undertake the
test. Where possible, tests should be conducted to avoid interruption to Customer
supplies however where this is not possible, alternative tests or computer simulation
exercises can be agreed between The Company, Relevant Transmission Licensee (as
applicable), the Network Operator (as applicable) and the Restoration Contractor.
Where it is identified that routine testing cannot be undertaken which is critical to
restoration of the Total System, from a strategic perspective, as a result of interruption
to Customer supplies, consideration should be given to System reconfiguration where
such a change is technically and economically viable which would be agreed between
The Company, Relevant Transmission Licnesee and Network Operator (as
appropriate).
(h) In respect of EU Generators, the above tests defined in OC5.7.2.1(a) – (g) shall be
assessed against the requirements of ECC.6.3.5.3.
(i) The Company and/or Network Operator shall agree with Anchor Restoration
Contractor when the above tests have been completed.
A dead line charge test would require the steps detailed in OC5.7.2.3(d) (i) and (ii) to be
undertaken. A remote synchronisation test would require the steps detailed in
OC5.7.2.3(d) (i) – (iii) to be undertaken.
i) Start-Up of the HVDC System or DC Converter Station under normal
operational conditions.
ii) Re-energisation of a dead test section of the Total System as defined in the
Local Joint Restoration Plan or Distribution Restoraion Zone Plan as
appropriate.
Issue 6 Revision 21 OC5 04 March 2024
14 of 58
iii) Demonstration of the ability to synchronise to a section of the Total System at a
location remote from the HVDC System or DC Converter Station Grid Entry
Point or User System Entry Point (as the case may be).
A dead line charge test is to demonstrate the HVDC System or DC Converter Stations
ability to charge a pre-defined dead part of the Total System and its ability to control the
voltage on that part.
A remote synchronisation test is used to demonstrate the successful operation of a
Transmission Licensee’s or Network Operator’s system synchronising facilities across
individual circuit breakers which are either necessary part of a Local Joint Restoration
Plan or defined in a Distribution Restoration Zone Plan.
When planning a dead line charge test, consideration shall be given to the effect the test
will have on Customers supplied from the part of the Total System that needs to be de-
energised, including whether their supplies would need to be interrupted to undertake the
test. Where possible, tests should be conducted to avoid interruption to Customer
supplies however where this is not possible, alternative tests or computer simulation
exercises can be agreed between The Company, Relevant Transmission Licensee (as
applicable), Network Operator (as applicable) and Restoration Contractor. Where it
is identified that routine testing cannot be undertaken which is critical to restoration of the
Total System, from a strategic perspective, as a result of interruption to Customer
supplies, consideration should be given to System reconfiguration where such a change
is technically and economically viable which would be agreed between the The
Company, Relevant Transmission Licnesee and Network Operator (as appropriate).
OC5.7.2.4 Top Up Restoration Plant Tests
Top Up Restoration Contractors have contracts with The Company and where appropriate
Network Operators, to provide a service in respect of their Top Up Plant to contribute to a
Local Joint Restoration Plan or Distribution Restoration Zone Plan. As provided for in
OC9.4.7.7.4 and OC9.4.7.8.4, Top Up Restoration Contractors will be generally be
instructed to prepare their Top Up Restoration Plant immediately after instructions are issued
to Restoration Contractors in respect of their Anchor Plant such that a Top Up Restoration
Contractor can deliver the service they have agreed to provide, without delay, upon
restoration of external site supplies. The purpose of these tests is to demonstrate that Top
Up Restoration Plant has the capability in accordance with the requirements of the Top Up
Restoration Contract.
(a) Prior to the test, the relevant Transmission Licensee and/or Network Operator shall
reconfigure its System as necessary to enable the test of the relevant Plant and
Apparatus to be completed whilst having due regard for the safety of Plant and
Apparatus and personnel on or adjacent to its System, and for the public.
(b) The relevant Plant and/or Apparatus shall be operating normally, i.e. in the operational
state it is anticipated to be in if a Shutdown were to occur.
(c) All the Auxiliary Energy Supplies which relate to the relevant Plant and/or Apparatus
shall be Shutdown.
(d) The Plant and/or Apparatus shall be de-loaded, De-Synchronised and Shutdown as
appropriate and all alternating current electrical supplies to its Auxiliaries shall be
disconnected.
(e) Auxiliary Energy Supplies at the Top Up Plant shall be started, and shall re-energise
either directly, or via the Station Board or the Unit Board of the relevant Plant.
(f) With the Auxiliaries available the relevant Plant and/or Apparatus should be in a
position to return to a condition when it is ready to be reconnected and/or Synchronised
to the System.
(g) Relevant Top Up Restoration Plant shall be Synchronised to the System and shall be
Loaded with Active Power and/or Reactive Power as agreed with The Company and/or
the Network Operator, unless an overriding instruction has been given directly by The
Company or from The Company to the Network Operator under BC2.
Issue 6 Revision 21 OC5 04 March 2024
15 of 58
(h) The Company and/or Network Operator shall agree with the Top Up Restoration
Contractor when the test has been completed.
OC5.7.2.5 Quick Re-synchronisation Unit Test
xi) Report the service level agreement compliance of their telephony systems including
infrastructure and service provision as provided for CC.6.5.4 or ECC.6.5.4.
xii) The resilience of voice systems including power supplies by its ability to withstand a
minimum of 72 hours during System Restoration.
As part of these exercises, Restoration Contractors and Users are required to inform The
Company of any assumptions they make and any reasons why they would be unable to fufil
their obligations.
In addition, from 1st January 2024 until 31st December 2026 desk top and computer exercises
and tests in relation to items i) to xii) may be carried out by agreement with The Company,
Users and Restoration Contractors.
OC.5.7.4.3 In addition to the above requirements, from 31 December 2026 onwards, Users and
Restoration Contractors are also required to provide an annual statement confirming that
their Plant and Apparatus has the capability to satisfy the requirements of OC.5.7 through
their Week 24 data submission.
OC5.7.5 In addition to the requirements of OC5.7.4.2 the following assurance tests shall be undertaken
at least once every three years.
i) Users, BM Participants and Restoration Contractors shall undertake tests or
otherwise demonstrate their Critical Tools and Facilities satisfy the requirements of
CC.6.5.4.4, CC.6.5.5.1, CC.7.10 and CC.7.11 or ECC.6.5.4.4, ECC.6.5.5.1, ECC.7.10
and ECC.7.11 as applicable.
ii) User’s, BM Participants and Restoration Contractors shall undertake tests or
otherwise demonstrate that their Critical Tools and Faciliaties are sufficiently robust
and reliable enough to manage the high volumes of data and alarms that are expected
to be generated during System Restoration in accordance with the requirements of
CC.7.10.7 and/or ECC.7.10.7.
OC5.7.6 The Company, as part of its regular System Restoration assurance activities, will ensure
Users and Restoration Contractors are capable of satisfying the applicable requirements of
OC5.7.
OC5.8 PROCEDURES APPLYING TO EMBEDDED MEDIUM POWER STATIONS NOT SUBJECT
TO A BILATERAL AGREEMENT AND EMBEDDED DC CONVERTER STATIONS NOT
SUBJECT TO A BILATERAL AGREEMENT
OC5.8.1 Compliance Statement
Each Network Operator shall ensure that each Embedded Person provides to the Network
Operator upon The Company's request:
(a) written confirmation that each such Power Generating Module, Generating Unit, Power
Park Module, HVDC Equipment, or DC Converter complies with the requirements of
the CC and ECC; and
(b) evidence, where requested, reasonably satisfactory to The Company, of such
compliance. Such a request shall not normally be made by The Company more than
twice in any calendar year in respect of any Generator’s Power Generating Module,
Generating Unit or Power Park Module or HVDC System Owner’s HVDC System, or
DC Converter owner's DC Converter.
The Network Operator shall provide the evidence or written confirmation required under
OC5.8.1 (a) and (b) forthwith upon receipt to The Company.
OC5.8.2 Network Operator’s Obligations To Facilitate Tests
If:
(a) the Network Operator fails to procure the confirmation referred to at OC5.8.1(a); or
(b) the evidence of compliance is not to The Company’s reasonable satisfaction,
Issue 6 Revision 21 OC5 04 March 2024
18 of 58
then, The Company shall be entitled to require the Network Operator to procure access upon
terms reasonably satisfactory to The Company to enable The Company to witness the
Embedded Person carrying out the tests referred to in OC5.8.3 in respect of the relevant
Embedded Medium Power Station or Embedded DC Converter Station or Embedded
HVDC System.
OC5.8.3 Testing Of Embedded Medium Power Stations Not Subject To A Bilateral Agreement Or
Embedded DC Converter Stations Not Subject To A Bilateral Agreement or Embedded HVDC
Equipment Not Subject To A Bilateral Agreement
The Company may, in accordance with the provisions of OC5.8.2, at any time (although not
normally more than twice in any calendar year in respect of any particular Embedded Medium
Power Station not subject to a Bilateral Agreement or Embedded DC Converter Station
or Embedded HVDC Equipment not subject to a Bilateral Agreement) issue an instruction
requiring the Network Operator within whose System the relevant Medium Power Station
not subject to a Bilateral Agreement or DC Converter Station or HVDC Equipment not
subject to a Bilateral Agreement is Embedded, to require the Embedded Person to carry
out a test.
Such test shall be carried out at a time no sooner than 48 hours from the time that the
instruction was issued, on any one or more of the Generating Units, Power Generating
Modules, Power Park Modules or DC Converters or HVDC Equipment comprising part of
the relevant Embedded Medium Power Station or Embedded DC Converter Station or
HVDC System and should only be to demonstrate that:
(a) the relevant Generating Unit, Power Generating Module, Power Park Module or DC
Converter or HVDC Equipment meets the requirements of the paragraphs in the CC or
ECC which are applicable to such Generating Units, Power Generating Modules,
Power Park Module or DC Converter or HVDC Equipment;
(b) the Reactive Power capability registered with The Company under OC2 meets the
requirements set out in CC.6.3.2 or ECC.6.3.2 as applicable.
The instruction may only be issued where, following consultation with the relevant Network
Operator, The Company has:
(c) confirmed to the relevant Network Operator the manner in which the test will be
conducted, which shall be consistent with the principles established in OC5.5.3; and
(d) received confirmation from the relevant Network Operator that the relevant Generating
Unit, Power Generating Module, Power Park Module or DC Converter or HVDC
Equipment would not then be unavailable by reason of forced outage or Planned
Outage expected prior to the instruction.
The relevant Network Operator is responsible for ensuring the performance of any test so
required by The Company and the Network Operator shall ensure that the Embedded
Person retains the responsibility for ensuring the safety of personnel and plant during the test.
OC5.8.4 Test Failures/Re-Tests and Disputes
The relevant Network Operator shall:
(a) ensure that provisions equivalent to OC5.5.5, OC5.5.6 and OC5.6 apply to Embedded
Medium Power Stations not the subject of a Bilateral Agreement, Embedded DC
Converter Stations not the subject of a Bilateral Agreement or Embedded HVDC
Equipment not the subject of a Bilateral Agreement within its System in respect of test
failures, re-tests and disputes as to test failures and re-tests;
(b) ensure that the provisions equivalent to OC5.5.5, OC5.5.6 and OC5.6 referred to in
OC5.8.4(a) are effective so that The Company may require, if it so wishes, the provision
to it of any reports or other information equivalent to those or that to which The Company
would be entitled in relation to test failures, re-tests and disputes as to test failures and
re-tests under the provisions of OC5.5.5, OC5.5.6 and OC5.6; and
OC5.A.1.3.1 The Company accept that the signals specified in OC5.A.1.3(c) may have lower effective
sample rates than those required in CC.6.6.2 although any signals supplied for connection to
The Company’s recording equipment which do not meet at least the sample rates detailed in
CC.6.6.2 should have the actual sample rates indicated to The Company before testing
commences.
OC5.A.1.3.2 For all The Company witnessed testing either;
(i) the Generator or DC Converter Station owner shall provide to The Company all signals
outlined in OC5.A.1.3 direct from the Power Park Module control system without any
attenuation, delay or filtering which would result in the inability to fully demonstrate the
objectives of the test, or identify any potential safety or plant instability issues, and with a
signal update rate corresponding to CC.6.6.2.1; or
OC5.A.1.4.3.1 Onshore Power Park Modules Voltage Control & Reactive Capability
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8
1 Time Active Reactive Connection Speed Freq Logic / Statcom
Power Power Point /Frequency Injection Test or
Voltage # # Start Windfarm
# Reactive
Power #
Col 9 Col 10 Col 11 Col 12 Col 13 Col 14 Col 15 Col 16
1 Power
Available Wind Wind Voltage
2 State of Speed Direction Setpoint
Charge
# Columns may be left blank but the column must still be included in the files
OC5.A.1.4.3.2 Offshore Power Park Modules Voltage Control & Reactive Capability
OC5.A.1.5.1 Where test results are completed without any prescence of The Company but are relied upon
as evidence of the compliance they should be accompanied by a logsheet. This sheet should
be legible, in English and detail the items as indicated below:
OC5.A.1.5.2 For each test the following items should be recorded as relevant to the type of test being
undertaken. Where there is uncertainty on the information to be recorded this should be
discussed with The Company in advance of the test.
OC5.A.1.5.3 Material changes during the test period should be recorded e.g. Generating Units tripping /
starting, changes to tapchange positions.
OC5.A.2.8.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at a minimum rate
of 1 Hz to allow The Company to assess the plant performance from the initial transients
(seconds) to the final steady state conditions (5-15 minutes depending on the plant design).
This is not witnessed by The Company. The Generator shall supply the recordings including
data to The Company in an electronic spreadsheet format. Results shall be legible, identifiable
by labelling, and shall have appropriate scaling.
OC5.A.2.8.7 The tests are divided into the following two types;
(i) Frequency response volume tests as per OC5.A.2.8. Figure 1. These tests consist of
Frequency profile and ramp tests.
(ii) System islanding and step response tests as shown by OC5.A.2.8. Figure 2.
OC5.A.2.8.8 There should be sufficient time allowed between tests for control systems to reach steady
state. Where the diagram states ‘HOLD’ the current injection should be maintained until the
Active Power (MW) output of the Generating Unit or CCGT Module has stabilised or 90
seconds, which ever is the longer. The frequency response capability test (see Figure 1)
injection signal shall be returned to zero at the same rate at which it was applied. The
Company may require repeat tests should the tests give unexpected results. When witnessed
by The Company each test should be carried out as a separate injection; when not witnessed
by The Company there must be sufficient time allowed between tests for the Plant to have
reached a stable steady state operating condition or 90 seconds, whichever is the longer.
0.4
Frequency (Hz)
HOLD
0.2
HOLD
0 10s 30s 60s 10s 10s 10s 0 10s 30s 60s
0
10s 10s 10s
HOLD
-0.2
HOLD
HOLD
-0.4
HOLD
HOLD
-0.6
-0.8
Response (MW)
+
Typical
HF Ramp
HF Ramp
HF Ramp
LF Ramp
LF Ramp
LF Ramp
LF Event
LF Event
Profile 1
Profile 2
+0.5Hz
+0.1Hz
+0.2Hz
-0.2Hz
-0.1Hz
-0.5Hz
Load
Point
MLP6 * * 1 2 3 * 4 *
MLP5 5 * * 6 * * 7 *
MLP4 8 9 10 11 12 13 14 *
MLP3 15 * * * * * 16 17
MLP2 18 * * 19 20 21 * 22
MLP1 23 * * 24 25 * * 26
0.4
Frequency (Hz)
HOLD
HOLD
0.2
0 1s (G) 31s
0 2s (A,J) 32s
0
0 1s 0 30s
HOLD
-0.2 HOLD
-0.4
HOLD HOLD
-0.6
-0.5Hz (K)
-2Hz (A,J)
-0.8
Response (MW)
+
Typical
Load Point +2.0* +0.02 -0.2 +0.2 -0.5 +0.5 +0.6 -0.5 -2.0 + 0**
MLP6 BC1 BC2 L
MLP6 LFSM BC3 BC4
MLP5 A
MLP4 D/E F G H I J M
*
MLP4 LFSM N
MLP3
MLP2
MLP1 K
* This will generally be +2.0Hz unless an injection of this size causes a reduction in plant output
that takes the operating point below Designed Minimum Operating Level in which case an
appropriate injection should be calculated in accordance with the following:
For example, 0.9Hz is needed to take an initial output 65% to a final output of 20%. If the
initial output was not 65% and the Designed Minimum Operating Level is not 20% then the
injected step should be adjusted accordingly as shown in the example given below
** Tests L and M in Figure 2 shall be conducted if in this range of tests the System Frequency
feedback signal is replaced by the injection signal rather than the injection signal being added
to the System Frequency signal. The tests will consist of monitoring the Generating Unit and
CCGT Module in Frequency Sensitive Mode during normal System Frequency variations
without applying any injection. Test N in figure 2 shall be conducted in all cases. All three tests
should be conducted for a period of at least 10 minutes.
OC5.A.2.8.9 The target frequency adjustment facility should be demonstrated from the normal Control
Point within the range of 49.9Hz to 50.1Hz by step changes to the target frequency setpoint
as indicated in OC5.A.2.8 Figure 3.
OC5.A.3.1 Scope
OC5.A.3.1.1 This Appendix outlines the general testing requirements for Power Park Modules and OTSUA
to demonstrate compliance with the relevant aspects of the Grid Code, Ancillary Services
Agreement and Bilateral Agreement and apply only to GB Generators. The testing
requirements applicable to EU Generators are specified in ECP.A.6. The tests specified in
this Appendix will normally be sufficient to demonstrate compliance however The Company
may:
(i) agree an alternative set of tests provided The Company deem the alternative set of tests
sufficient to demonstrate compliance with the Grid Code, Ancillary Services
Agreement and Bilateral Agreement; and/or
(ii) require additional or alternative tests if information supplied to The Company during the
compliance process suggests that the tests in this Appendix will not fully demonstrate
compliance with the relevant section of the Grid Code, Ancillary Services Agreement
or Bilateral Agreement; and/or
(ii) require additional tests if a Power System Stabiliser is fitted; and/or
(iv) agree a reduced set of tests if a relevant Manufacturer's Data & Performance Report
has been submitted to and deemed to be appropriate by The Company; and/or
(v) agree a reduced set of tests for subsequent Power Park Modules or OTSUA following
successful completion of the first Power Park Module or OTSUA tests in the case of a
Power Station comprised of two or more Power Park Modules or OTSUA which The
Company reasonably considers to be identical.
If:
(a) the tests performed pursuant to OC5.A.3.1.1(iv) do not replicate the results contained in
the Manufacturer’s Data & Performance Report or
(b) the tests performed pursuant to OC5.A.3.1.1(v) in respect of subsequent Power Park
Modules or OTSUA do not replicate the full tests for the first Power Park Module or
OTSUA, or
(c) any of the tests performed pursuant to OC5.A.3.1.1(iv) or OC5.A.3.1.1(v) do not fully
demonstrate compliance with the relevant aspects of the Grid Code, Ancillary Services
Agreement and / or Bilateral Agreement,
then notwithstanding the provisions above, the full testing requirements set out in this
Appendix will be applied.
OC5.A.3.1.2 The Generator is responsible for carrying out the tests set out in and in accordance with this
Appendix and the Generator retains the responsibility for the safety of personnel and plant
during the test. The Company will witness all of the tests outlined or agreed in relation to this
Appendix unless The Company decides and notifies the Generator owner otherwise.
Reactive Capability tests may be witnessed by The Company remotely from the The
Company control centre. For all on site during The Company witnessed tests, the Generator
must ensure suitable representatives from the Generator and / or Power Park Module
manufacturer (if appropriate) and/or OTSUA manufacturer (if appropriate) are available on site
for the entire testing period. In all cases and in addition to any recording of signals conducted
by The Company, the Generator shall record all relevant test signals as outlined in OC5.A.1.
OC5.A.3.1.3 In addition to the dynamic signals supplied in OC5.A.1, the Generator shall inform The
Company of the following information prior to the commencement of the tests and any
changes to the following, if any values change during the tests:
(i) All relevant transformer tap numbers; and
(ii) Number of Power Park Units in operation
Voltage
Time
1 tap
10s
minimum
(ii)
Applied
Voltage
Step 4%
2%
1% Time
10s
minimum
OC5.A.3.5 Figure 2 – Step injection sequence for voltage control tests
OC5.A.3.5.7 In the case of OTSUA where the Bilateral Agreement specifies additional damping facilities,
additional testing to demonstrate these damping facilities may be required.
OC.A.3.5.8 In the case of Power Park Modules that do not provide voltage control down to zero Active
Power a test to demonstrate the smooth transition from voltage control mode to unity Power
Factor shall be carried out. The Power Park Module voltage setpoint should be altered to
produce lagging Reactive Power or absorbing leading Reactive Power at a low Active
Power level where voltage control is provided. The Power Park Module Active Power should
then be reduced to zero Active Power as a ramp over a short period (60 seconds is
suggested).
OC5.A.3.6.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at a minimum rate
of 1 Hz to allow The Company to assess the plant performance from the initial transients
(seconds) to the final steady state conditions (5-15 minutes depending on the plant design).
This is not witnessed by The Company. The Generator shall supply the recordings including
data to The Company in an electronic spreadsheet format. Results shall be legible, identifiable
by labelling, and shall have appropriate scaling.
Full Frequency Response Testing Schedule Witnessed by The Company
OC5.A.3.6.6 The tests are to be conducted at a number of different Module Load Points (MLP). In the case
of a Power Park Module the module load points are conducted as shown below unless agreed
otherwise by The Company.
0.4
Frequency (Hz)
HOLD
0.2
HOLD
0 10s 30s 60s 10s 10s 10s 0 10s 30s 60s
0
10s 10s 10s
HOLD
-0.2
HOLD
HOLD
-0.4
HOLD
HOLD
-0.6
-0.8
Response (MW)
+
Typical
_
HF Ramp
HF Ramp
HF Ramp
LF Ramp
LF Ramp
LF Ramp
LF Event
LF Event
Profile 1
Profile 2
+0.5Hz
+0.1Hz
+0.2Hz
-0.2Hz
-0.1Hz
-0.5Hz
Load
Point
MLP6 * * 1 2 3 * 4 *
MLP5 5 * * 6 * * 7 *
MLP4 8 9 10 11 12 13 14 *
MLP3 15 * * * * * 16 17
MLP2 18 * * 19 20 21 * 22
MLP1 23 * * 24 25 * * 26
HOLD
HOLD
0.2
0 1s (G) 31s
0 2s (A,J) 32s
0
0 1s 0 30s
HOLD
-0.2 HOLD
-0.4
HOLD HOLD
-0.6
-0.5Hz (K)
-2Hz (A,J)
-0.8
Response (MW)
+
Typical
Load Point +2.0* +0.02 -0.2 +0.2 -0.5 +0.5 +0.6 -0.5 -2.0 + 0**
MLP6 BC1 BC2 L
MLP6 LFSM BC3 BC4
MLP5 A
MLP4 D/E F G H I J M
*
MLP4 LFSM N
MLP3
MLP2
MLP1 K
* This will generally be +2.0Hz unless an injection of this size causes a reduction in plant output
that takes the operating point below Designed Minimum Operating Level in which case an
appropriate injection should be calculated in accordance with the following:
For example 0.9Hz is needed to take an initial output 65% to a final output of 20%. If the initial
output was not 65% and the Designed Minimum Operating Level is not 20% then the
injected step should be adjusted accordingly as shown in the example given below
** Tests L and M in Figure 2 shall be conducted if in this range of tests the System Frequency
feedback signal is replaced by the injection signal rather than the injection signal being added
to the System Frequency signal. The tests will consist of monitoring the Power Park Module
in Frequency Sensitive Mode during normal System Frequency variations without applying
any injection. Test N in Figure 2 shall be conducted in all cases. All three tests should be
conducted for a period of at least 10 minutes.
OC5.A.3.6.9 The Target Frequency adjustment facility should be demonstrated from the normal control
point within the range of 49.9Hz to 50.1Hz by step changes to the Target Frequency setpoint
as indicated in OC5.A.3.6 Figure 3.
Voltage
Time
1 tap
>10s
OC5.A.3.8 Figure 1 – Transformer tap sequence for reactive transfer tests
<=10s
Time
Active
Power
10% of
Change
Registered Capacity
OC5.A.4.1.1 This Appendix outlines the general testing requirements for DC Converter Station owners to
demonstrate compliance with the relevant aspects of the Grid Code, Ancillary Services
Agreement and Bilateral Agreement and apply only to DC Converter Station owners. The
testing requirements applicable to HVDC System Owners are specified in ECP.A.7. The tests
specified in this Appendix will normally be sufficient to demonstrate compliance however The
Company may:
(i) agree an alternative set of tests provided The Company deem the alternative set of tests
sufficient to demonstrate compliance with the Grid Code, Ancillary Services
Agreement and Bilateral Agreement; and/or
(ii) require additional or alternative tests if information supplied to The Company during the
compliance process suggests that the tests in this Appendix will not fully demonstrate
compliance with the relevant section of the Grid Code, Ancillary Services Agreement
or Bilateral Agreement; and/or
(iii) require additional tests if control functions to improve damping of power system
oscillations and/or subsynchronous resonance torsional oscillations required by the
Bilateral Agreement or included in the control scheme and active; and/or
(iv) agree a reduced set of tests for subsequent DC Converters following successful
completion of the first DC Converter tests in the case of a Power Station comprised of
two or more DC Converters which The Company reasonably considers to be identical.
If:
(a) the tests performed pursuant to OC5.A.4.1.1(iv) in respect of subsequent DC Converters
do not replicate the full tests for the first DC Converter, or
(b) any of the tests performed pursuant to OC5.A.4.1.1(iv) do not fully demonstrate
compliance with the relevant aspects of the Grid Code, Ancillary Services Agreement
and / or Bilateral Agreement,
then notwithstanding the provisions above, the full testing requirements set out in this
Appendix will be applied.
OC5.A.4.1.2 The DC Converter Station owner is responsible for carrying out the tests set out in and in
accordance with this Appendix and the DC Converter Station owner retains the responsibility
for the safety of personnel and plant during the test. The DC Converter Station owner is
responsible for ensuring that suitable arrangements are in place with the Externally
Interconnected System Operator to facilitate testing. The Company will witness all of the
tests outlined or agreed in relation to this Appendix unless The Company decides and notifies
the DC Converter Station owner otherwise. Reactive Capability tests if required, may be
witnessed by The Company remotely from the The Company control centre. For all on site
The Company witnessed tests the DC Converter Station owner must ensure suitable
representatives from the DC Converter Station owner and / or DC Converter manufacturer
(if appropriate) are available on site for the entire testing period. In all cases and in addition
to any recording of signals conducted by The Company the DC Converter Station owner
shall record all relevant test signals as outlined in OC5.A.1.
OC5.A.4.1.3 In addition to the dynamic signals supplied in OC5.A.1 the DC Converter Station owner shall
inform The Company of the following information prior to the commencement of the tests and
any changes to the following, if any values change during the tests:
(i) All relevant transformer tap numbers.
OC5.A.4.1.4 The DC Converter Station owner shall submit a detailed schedule of tests to The Company
in accordance with CP.6.3.1, and this Appendix.
Voltage
Time
1 tap
>10s
OC5.A.4.3 Figure 1 – Transformer tap sequence for reactive transfer tests
<=10s
Time
Active
Power
10% of
Change
Registered Capacity
Voltage
Time
1 tap
10s
minimum
(ii)
Applied
Voltage
Step 4%
2%
1% Time
10s
minimum
OC5.A.4.4 Figure 2 – Step injection sequence for voltage control tests
OC5.A.4.5.5 The recorded results (e.g. Finj, MW and control signals) should be sampled at a minimum rate
of 1 Hz to allow The Company to assess the plant performance from the initial transients
(seconds) to the final steady state conditions (5-15 minutes depending on the plant design).
This is not witnessed by The Company. The DC Converter Station owner shall supply the
recordings including data to The Company in an electronic spreadsheet format. Results shall
be legible, identifiable by labelling, and shall have appropriate scaling.
Full Frequency Response Testing Schedule Witnessed by The Company
OC5.A.4.5.6 The tests are to be conducted at a number of different Module Load Points (MLP). In the case
of a DC Converter the module load points are conducted as shown below unless agreed
otherwise by The Company.
0.6
HOLD
0.4
Frequency (Hz)
HOLD
0.2
HOLD
0 10s 30s 60s 10s 10s 10s 0 10s 30s 60s
0
10s 10s 10s
HOLD
-0.2
HOLD
HOLD
-0.4
HOLD
HOLD
-0.6
-0.8
Response (MW)
+
Typical
_
HF Ramp
HF Ramp
HF Ramp
LF Ramp
LF Ramp
LF Ramp
LF Event
LF Event
Profile 1
Profile 2
+0.5Hz
+0.1Hz
+0.2Hz
-0.2Hz
-0.1Hz
-0.5Hz
Load
Point
MLP6 * * 1 2 3 * 4 *
MLP5 5 * * 6 * * 7 *
MLP4 8 9 10 11 12 13 14 *
MLP3 15 * * * * * 16 17
MLP2 18 * * 19 20 21 * 22
MLP1 23 * * 24 25 * * 26
0.4
Frequency (Hz)
HOLD
HOLD
0.2
0 1s (G) 31s
0 2s (A,J) 32s
0
0 1s 0 30s
HOLD
-0.2 HOLD
-0.4
HOLD HOLD
-0.6
-0.5Hz (K)
-2Hz (A,J)
-0.8
Response (MW)
+
Typical
Load Point +2.0* +0.02 -0.2 +0.2 -0.5 +0.5 +0.6 -0.5 -2.0 + 0**
MLP6 BC1 BC2 L
MLP6 LFSM BC3 BC4
MLP5 A
MLP4 D/E F G H I J M
*
MLP4 LFSM N
MLP3
MLP2
MLP1 K
* This will generally be +2.0Hz unless an injection of this size causes a reduction in plant output
that takes the operating point below the Designed Minimum Operating Level in which case
an appropriate injection should be calculated in accordance with the following:
For example 0.9Hz is needed to take an initial output of 65% to a final output of 20%. If the
initial output was not 65% and the Designed Minimum Operating Level is not 20% then the
injected step should be adjusted accordingly as shown in the example given below
** Tests L and M in Figure 2 shall be conducted if in this range of tests the System Frequency
feedback signal is replaced by the injection signal rather than the injection signal being added
to the System Frequency signal. The tests will consist of monitoring the DC Converter in
Frequency Sensitive Mode during normal System Frequency variations without applying
any injection. Test N in Figure 2 shall be conducted in all cases. All three tests should be
conducted for a period of at least 10 minutes.
OC5.A.4.6.9 The Target Frequency adjustment facility should be demonstrated from the normal Control
Point within the range of 49.9Hz to 50.1Hz by step changes to the Target Frequency setpoint
as indicated in OC5.A.4.6 Figure 3.
Issue 6 Revision 21 OC5 04 March 2024
57 of 58
OC5.A.4.6. Figure 3 – Target Frequency setting changes
DEMAND CONTROL
CONTENTS
(This contents page does not form part of the Grid Code)
The list of pre-designated protected sites is compiled and kept up to date by Network
Operators in accordance with the terms set out in the Electricity Supply Emergency Code.
OC6.1.6 Connections between Large Power Stations and the National Electricity Transmission
System and between such Power Stations and a User System will not, as far as possible,
be disconnected by The Company pursuant to the provisions of OC6 insofar as that would
interrupt supplies
(a) for the purposes of operation of the Power Station (including Start-Up and shutting
down);
(b) for the purposes of keeping the Power Station in a state such that it could be Started-up
when it is off-Load for ordinary operational reasons; or
(c) for the purposes of compliance with the requirements of a Nuclear Site Licence.
OC6.2 OBJECTIVE
OC6.2.1 The overall objective of OC6 is to require the provision of facilities to enable The Company to
achieve reduction in Demand that will either avoid or relieve operating problems on the
National Electricity Transmission System, in whole or in part, and thereby to enable The
Company to instruct Demand Control in a manner that does not unduly discriminate against,
or unduly prefer, any one or any group of Suppliers or Network Operators or Non-
Embedded Customers. It is also to ensure that The Company is notified of any Demand
Control utilised by Users other than following an instruction from The Company.
OC6.2.2 For certain Grid Supply Points in Scotland it is recognised that it may not be possible to meet
the requirements in OC6.4.5(b), OC6.5.3(b) (in respect of Demand Disconnection only),
OC6.5.6 (ii), OC6.6.2 (c) and OC6.7.2 (b). In these circumstances The Company and the
relevant Network Operator(s) will agree equivalent requirements covering a number of Grid
Supply Points. If The Company and the relevant Network Operator fail to agree equivalent
requirements covering a number of Grid Supply Points, then the relevant Network Operator
will apply the provisions of OC6.4.5(b), OC6.5.3(b) (in respect of Demand Disconnection
only), OC6.5.6(ii), OC6.6.2(c) and OC6.7.2(b) as evenly as reasonably practicable over the
relevant Network Operator’s entire System.
OC6.3 SCOPE
OC6.3.1 OC6 applies to The Company and to Users which in OC6 means:
(a) Generators; and
(b) Network Operators.
It also applies to The Company in relation to Non-Embedded Customers.
OC6.3.2 Explanation
OC6.3.2.1 (a) Although OC6 does not apply to Suppliers, the implementation of Demand Control may
affect their Customers.
(b) In all situations envisaged in OC6, Demand Control is exercisable:
(i) by reference to a Network Operator's System; or
(ii) by The Company in relation to Non-Embedded Customers.
(c) Demand Control in all situations relates to the physical organisation of the Total System,
and not to any contractual arrangements that may exist.
OC6.3.2.2 (a) Accordingly, Demand Control will be exercisable with reference to, for example, five per
cent (or such other figure as may be utilised under OC6.5) tranches of Demand by a
Network Operator.
(b) For a Supplier, whose Customers may be spread throughout a number of User
Systems (and the National Electricity Transmission System), to split its Customers
into five per cent (or such other figure as may be utilised under OC6.5) tranches of
Demand would not result in Demand Control being implemented effectively on the Total
System.
each Network Operator will abide by the instructions of The Company, which
should specify whether a voltage reduction or Demand Disconnection stage is
required; or
(iii) if the instruction relates to less than 20 per cent of its total Demand, is in four
Demand Disconnection stages each of which can reasonably be expected to
deliver between four and six per cent Demand reduction,
each Network Operator will abide by the instructions of The Company with regard to
Demand reduction under OC6.5 without delay.
(b) The Demand reduction must be achieved within the Network Operator's System as far
as possible uniformly across all Grid Supply Points (unless otherwise specified in the
National Electricity Transmission System Warning - High Risk of Demand
Reduction) either by Customer voltage reduction or by Demand Disconnection.
(c) Demand Control initiated by voltage reduction shall be initiated as soon as possible but
in any event no longer than two minutes from the instruction being received from The
Company, and completed within 10 minutes of the instruction being received from The
Company.
(e) Each Network Operator must notify The Company in writing by calendar week 24 each
year, for the succeeding Financial Year onwards, whether Demand Control is to be
implemented either:
together with the magnitude of the voltage reduction stages (where applicable) and for
Demand Disconnection stages, the demand reduction anticipated. Thereafter, any
changes must be notified in writing to The Company at least 10 Business Days prior to
Issue 6 Revision 20 OC6 15 December 2023
6 of 12
the change coming into effect.
OC6.5.4 (a) Where The Company wishes to instruct a Demand reduction of more than 20 per cent
of a Network Operator's Demand, it shall, if it is able, issue a National Electricity
Transmission System Warning - High Risk of Demand Reduction to the Network
Operator by 1600 hours on the previous day. The warning will state the percentage level
of Demand reduction that The Company may want to instruct.
(b) The National Electricity Transmission System Warning - High Risk of Demand
Reduction will specify the percentage of Demand reduction that The Company may
require in integral multiples of the percentage levels notified by Users under OC6.5.3(e)
up to (and including) 20 per cent and integral multiples of between 4 and 6 per cent above
20 per cent and will not relate to more than 40 per cent of Demand on the User System
of a Network Operator.
(c) If The Company has issued the National Electricity Transmission System Warning -
High Risk of Demand Reduction by 1600 hours on the previous day, on receipt of it,
the relevant Network Operator shall make available the percentage reduction in
Demand specified for use within the period of the National Electricity Transmission
System Warning.
(d) If The Company has not issued the National Electricity Transmission System
Warning - High Risk of Demand Reduction by 1600 hours the previous day, but after
that time, the Network Operator shall make available as much of the required Demand
reduction as it is able, for use within the period of the National Electricity Transmission
System Warning.
OC6.5.5 (a) If The Company has given a National Electricity Transmission System Warning -
High Risk of Demand Reduction to a Network Operator, and has issued it by 1600
hours on the previous day, it can instruct the Network Operator to reduce its Demand
by the percentage specified in the National Electricity Transmission System Warning.
(b) The Company accepts that if it has not issued the National Electricity Transmission
System Warning - High Risk of Demand Reduction by 1600 hours on the previous day
or if it has issued it by 1600 hours on the previous day, but it requires a further percentage
of Demand reduction (which may be in excess of 40 per cent of the total Demand on the
User System of the Network Operator from that set out in the National Electricity
Transmission System Warning), it can only receive an amount that can be made
available at that time by the Network Operator.
(c) Where the instruction relates to not more than 20 per cent of its total Demand each
Network Operator will implement the instruction, in accordance with OC6.5.3.
(d) Where a single instruction relates to more than 20 per cent of its total Demand each
Network Operator will:
(i) implement that part of the instruction relating to up to and including 20 per cent of
Demand Reduction in accordance with OC6.5.3.
(ii) once these instructions have been implemented by the Network Operator, any
further Demand Disconnection above those implemented in OC6.5.5(d)(i) shall take
up to 5 additional minutes from the instruction being received from The Company for
each extra 4 to 6 per cent of Demand being disconnected.
(e) Where The Company issues a Network Operator with consecutive instructions to
reduce Demand, the Network Operator will complete instructions in the order they were
issued by The Company and will not start to execute any instruction until any preceding
instruction has been completed, unless agreed with The Company.
OC6.5.6 Once a Demand reduction has been applied by a Network Operator at the instruction of The
Company, the Network Operator may interchange the Customers to whom the Demand
reduction has been applied provided that,
Issue 6 Revision 20 OC6 15 December 2023
7 of 12
(i) the percentage of Demand reduction at all times within the Network Operator's System
does not change; and
(ii) at all times it is achieved within the Network Operator's System as far as possible
uniformly across all Grid Supply Points (unless otherwise specified in the National
Electricity Transmission System Warning - High Risk of Demand Reduction if one
has been issued),
until The Company instructs that Network Operator in accordance with OC6.
OC6.5.7 Each Network Operator will abide by the instructions of The Company with regard to the
restoration of Demand under OC6.5 without delay. It shall not restore Demand until it has
received such instruction. The restoration of Demand must be achieved as soon as possible
and the process of restoration must begin within 2 minutes of the instruction being given by
The Company.
OC6.5.8 In circumstances of protracted shortage of generation or where a statutory instruction has
been given (eg. a fuel security period) and when a reduction in Demand is envisaged by The
Company to be prolonged, The Company will notify the Network Operator of the expected
duration.
OC6.5.9 The Network Operator will notify The Company in writing that it has complied with The
Company's instruction under OC6.5, within five minutes of so doing, together with an
estimation of the Demand reduction or restoration achieved, as the case may be.
OC6.5.10 The Company may itself implement Demand reduction and subsequent restoration on Non-
Embedded Customers as part of a Demand Control requirement and it will organise the
National Electricity Transmission System so that it will be able to reduce Demand by
Disconnection of, or Customer voltage reduction to, all or any Non-Embedded Customers.
Equivalent provisions to those in OC6.5.4 shall apply to issuing a National Electricity
Transmission System Warning - High Risk of Demand Reduction to Non-Embedded
Customers, as envisaged in OC7.4.8.
OC6.5.11 Pursuant to the provisions of OC1.5.6, the Network Operator will supply to The Company
details of the amount of Demand reduction or restoration actually achieved.
Notes:
1. Data to be provided annually by week 24 to cover the following year.
CONTENTS
(This contents page does not form part of the Grid Code)
OC6B.2 OBJECTIVE
OC6B.2.1 The overall objective of OC6B is concerned with the provisions to be made by
Network Operators to reduce the Active Power output from Embedded Power
Stations that will either avoid or relieve operational issues, in whole or in part, and
thereby to enable The Company to instruct Embedded Generation Control in a
manner that does not unduly discriminate against, or unduly prefer, any one or any
group of Generators or Suppliers or Network Operators.
OC6B.3 SCOPE
OC6B.3.1 OC6B applies to The Company and to Users which in OC6B means:
(a) Generators; and
(b) Network Operators.
OC6B.3.2 Explanation
OC6B.3.2.3 Network Operators may where necessary (for example where timescales do not
allow otherwise) implement Embedded Generation Control instructions by
Embedded Generation De-energisation based on Registered Capacity so long
as reasonable endeavours are employed by the Network Operator to ensure that
the reduction in Active Power output specified in the instruction from The Company
is achieved.
OC6B.3.2.4 An instruction from The Company to the Network Operator will be given to allow
the Network Operator to arrange with Embedded Power Stations subject to
Embedded Generation Control to resume normal operation. Such arrangements
shall not commence until such an instruction has been received.
OC6B.3.2.5 The existence of any other arrangements for the management of Embedded Power
Stations by a Network Operator will not relieve a Network Operator from the
Embedded Generation Control provisions of this OC6B.
OPERATIONAL LIAISON
CONTENTS
(This contents page does not form part of the Grid Code)
OC7.3.1 OC7 applies to The Company and to Users, which in OC7 means:
(a) Generators (other than those which only have Embedded Small Power Stations or
Embedded Medium Power Stations) and including Generators undertaking OTSDUW;
(b) Network Operators;
(c) Non-Embedded Customers;
(d) Suppliers (for the purposes of National Electricity Transmission System Warnings);
(e) Externally Interconnected System Operators (for the purposes of National Electricity
Transmission System Warnings); and
(f) DC Converter Station owners and HVDC System Owners.
The procedure for operational liaison by The Company with Externally Interconnected
System Operators is set out in the Interconnection Agreement with each Externally
Interconnected System Operator.
OC7.6 also applies to Relevant Transmission Licensees.
OC7.4 PROCEDURE
OC7.4.1 The term "Operation" means a scheduled or planned action relating to the operation of a
System (including an Embedded Power Station).
OC7.4.2 The term "Event" means an unscheduled or unplanned (although it may be anticipated)
occurrence on, or relating to, a System (including an Embedded Power Station) including,
without limiting that general description, faults, incidents and breakdowns and adverse
weather conditions being experienced.
OC7.4.3 The term "Operational Effect" means any effect on the operation of the relevant other System
which causes the National Electricity Transmission System or the Systems of the other
User or Users, as the case may be, to operate (or be at a materially increased risk of
operating) differently to the way in which they would or may have normally operated in the
absence of that effect.
OC7.4.4 References in this OC7 to a System of a User or User's System shall not include Embedded
Small Power Stations or Embedded Medium Power Stations, unless otherwise stated.
OC7.4.5 Requirement To Notify Operations
OC7.4.5.1 Operation On The National Electricity Transmission System
In the case of an Operation on the National Electricity Transmission System, which will
have (or may have) an Operational Effect on the System(s) of a User or Users, The
Company will notify the User or Users whose System(s) will, or may, in the reasonable
opinion of The Company, be affected, in accordance with OC7.
OC7.4.5.2 Operation On a User's System
In the case of an Operation on the System of a User which will have (or may have) an
Operational Effect on the National Electricity Transmission System (including an
equivalent to an Operation on the equivalent of a System of a User or other person connected
to that User's System which, via that User System, will or may have an Operational Effect
on the National Electricity Transmission System), the User will notify The Company in
accordance with OC7. Following notification by the User, The Company will notify any other
User or Users on whose System(s) the Operation will have, or may have, in the reasonable
opinion of The Company, an Operational Effect, in accordance with OC7 and will notify any
Externally Interconnected System Operator on whose System the Operation will have, or
may have, in the reasonable opinion of The Company, an Operational Effect, if it is required
to do so by the relevant Interconnection Agreement.
OC7.4.5.3 Examples Of Situations Where Notification By The Company Or a User may be Required
Issue 6 Revision 5 OC7 23 August 2021
3 of 22
Whilst in no way limiting the general requirement to notify in advance set out in OC7.4.5.1 and
OC7.4.5.2, the following are examples of situations where notification in accordance with
OC7.4.5 will be required if they will, or may, have an Operational Effect:
(a) the implementation of a planned outage of Plant and/or Apparatus which has been
arranged pursuant to OC2;
(b) the operation (other than, in the case of a User, at the instruction of The Company) of
any circuit breaker or isolator/disconnector or any sequence or combination of the two; or
(c) voltage control.
OC7.4.5.4 Operations Caused By Another Operation Or By An Event
An Operation may be caused by another Operation or an Event on another's System
(including an Embedded Power Station) (or by the equivalent of an Event or Operation on
the System of an Externally Interconnected System Operator or Interconnector User) and
in that situation the information to be notified is different to that where the Operation arose
independently of any other Operation or Event, as more particularly provided in OC7.4.5.6.
OC7.4.5.5 Form
A notification and any response to any questions asked under OC7.4.5, of an Operation which
has arisen independently of any other Operation or of an Event, shall be of sufficient detail to
describe the Operation (although it need not state the cause) and to enable the recipient of
the notification reasonably to consider and assess the implications and risks arising (provided
that, in the case of an Operation on a User's System which The Company is notifying to
other Users under OC7.4.5.2, The Company will only pass on what it has been told by the
User which has notified it) and will include the name of the individual reporting the Operation
on behalf of The Company or the User, as the case may be. The recipient may ask questions
to clarify the notification and the giver of the notification will, insofar as it is able, answer any
questions raised, provided that, in the case of an Operation on a User's System which The
Company is notifying to other Users under OC7.4.5.2, in answering any question, The
Company will not pass on anything further than that which it has been told by the User which
has notified it. The Company may pass on the information contained in the notification as
provided in OC7.4.5.6.
OC7.4.5.6 (a) A notification by The Company of an Operation under OC7.4.5.1 which has been caused
by another Operation (the "first Operation") or by an Event on a User's System, will
describe the Operation and will contain the information which The Company has been
given in relation to the first Operation or that Event by the User. The notification and any
response to any questions asked (other than in relation to the information which The
Company is merely passing on from a User) will be of sufficient detail to enable the
recipient of the notification reasonably to consider and assess the implications and risks
arising from the Operation on the National Electricity Transmission System and will
include the name of the individual reporting the Operation on behalf of The Company.
The recipient may ask questions to clarify the notification and The Company will, insofar
as it is able, answer any questions raised, provided that in relation to the information
which The Company is merely passing on from a User, in answering any question The
Company will not pass on anything further than that which it has been told by the User
which has notified it.
(b) Where a User is reporting an Operation or an Event which itself has been caused by an
incident or scheduled or planned action affecting (but not on) its System, the notification
to The Company will contain the information which the User has been given by the
person connected to its System in relation to that incident or scheduled or planned action
(which the User must require, contractually or otherwise, the person connected to its
System to give to it) and The Company may pass on the information contained in the
notification as provided in this OC7.4.5.6.
(c) The issue of the National Electricity Transmission System Warning - High Risk of
Embedded Generation Reduction is intended to enable recipients to plan ahead on the
various aspects of Embedded Generation Control.
NATIONAL OC7.4.8.5 Fax or Generators, Network All timescales when Insufficient generation Offers of increased availability from
ELECTRICITY other Suppliers, Operators, Non- at the time there is available to meet forecast Generators or DC Converter Station
TRANSMISSION electronic Externally Interconected Embedded not a high risk of Demand plus Operating owners. HVDC System Owners and
Issue 6 Revision 5
WARNING – means System Operators, DC Customers Demand reduction. Margin. Interconnector Users.
ELECTRICITY MARGIN Converter Station owners
NOTICE and HVDC System Primarily 1200 hours Notification that if not Suppliers notify The Company of any
Owners onwards for a future improved Demand additional Customer Demand Management
period. reduction may be that they will initiate.
instructed.
NATIONAL OC7.4.8.6 Fax or Generators, All timescales where Insufficient generation Offers of increased availability from
ELECTRICITY other Suppliers, there is a high risk of available to meet forecast Generators or DC Converter Station owners
TRANSMISSION electronic Network Operators, Demand Reduction. Demand plus Operating or HVDC System Owners and
SYSTEM WARNING – means Non-Embedded Margin and/or a high risk of Interconnector Users.
High risk of Demand Customers, Primarily 1200 hours Demand Reduction being
Reduction Externally Interconnected onwards for a future instructed. Suppliers notify The Company of any
System Operators, DC period additional Customer Demand Management
Converter Station Owners, (May be issued locally as that they will initiate.
HVDC System Owners demand reduction risk only
for circuit overloads) Specified Network Operators and Non-
OC7
Embedded Customers to prepare their
20 of 22
Demand Reduction arrangements and take
actions as necessary to enable compliance
with The Company instructions that may
follow.
NATIONAL OC7.4.8.7 Fax/Telep Specified Users only: (to None Within 30 minutes of Possibility of Demand Network Operators specified to prepare to
ELECTRICITY hone or whom an instruction is to anticipated Reduction within 30 take action as necessary to enable them to
TRANSMISSION other be given) instruction minutes comply with any subsequent The Company
SYSTEM WARNING – electronic Network Operators, Non- instruction for Demand reduction.
Demand Control means Embedded Customers
Imminent
NATIONAL OC7.4.8.12 Fax/Telep Generators, DC Converter Suppliers Control room time Risk of, widespread system Recipients take steps to warn operational
ELECTRICITY hone or Station owners, HVDC scales disturbance to whole or staff and maintain plant or apparatus such
TRANSMISSION other System Owners, part of the National that they are best able to withstand the
SYSTEM WARNING – electronic Network Operators, Non- Electricity Transmission disturbance.
Risk of System means Embedded Customers, System
Disturbance Externally Interconnected
System Operators who
may be affected.
23 August 2021
Alert, Instruction, Notification or Warning Type Reference Warning ofor Consequence
Issue 6 Revision 5
Automatic Low Frequency Demand Disconnection Grid Code OC6.6 Automatic Demand Disconnection Applied
Grid Code Emergency Instruction (to Network Operator) Grid Code BC2.9.1.4 Emergency Instruction(s) issued.
Grid Code Emergency Instruction (to Interconnectors) Grid Code BC2.9.1.4 May require departure from normal Balancing Market Operation in accordance with BC2
System NRAPM Grid Code BC1.5.5 Inadequate Negative Reserve Active Power Margin (nationally)
OC7
21 of 22
Localised NRAPM Grid Code BC1.5.5 Inadequate Negative Reserve Active Power Margin (locally)
Cancellation of National Electricity System Warning Grid Code OC7.4.8.9 Noted warning no longer applicable.
STC Emergency Instruction to Transmission Owner¹ STC Section C Part Two (7) Discontinue Outage within Emergency Return to Service Time
ESEC Implementation Grid Code OC6.1.5 Commencing rota disconnection across affected Network Operators licence areas.
Request to increase Active Energy transferred into the NETS, or reduce Active Energy transferred into its
Emergency Assistance Requests Grid Code BC2.9.6
External System
23 August 2021
¹Identification of the specific equipment affected is not required to be included within the published alert.
< END OF OPERATING CODE NO. 7 >
SAFETY CO-ORDINATION
CONTENTS
(This contents page does not form part of the Grid Code)
OC8.2 OBJECTIVE
OC8.2.1 The objective of OC8 is to achieve:
(i) Safety From The System when work on or near a System necessitates the provis ion
of Safety Precautions on another System on HV Apparatus up to a Connection
Point; and
(ii) Safety From The System when work is to be carried out at a User’s Site or a
Transmission Site (as the case may be) on equipment of the User or a Relevant
Transmission Licensee (as the case may be) where the work or equipment is near t o
HV Apparatus on the Implementing Safety Co-ordinator’s System.
OC8.3 SCOPE
OC8.3.1 OC8 applies to The Company and to Users, which in OC8 means:
(a) Generators (including where undertaking OTSDUW);
(b) Network Operators; and
(c) Non-Embedded Customers.
OC8 also applies to Relevant Transmission Licensees.
The procedures for the establishment of safety co-ordination by The Company in relation t o
External Interconnections are set out in Interconnection Agreements with relevant
persons for the External Interconnections.
OC8.4 PROCEDURE
OC8.4.1 Safety Co-Ordination In Respect Of The E&W Transmission Systems Or The S y st ems Of
E&W Users
OC8.4.1.1 OC8 Appendix 1, OC8A, applies when work is to be carried out on or near to the E&W
Transmission System or the Systems of E&W Users or when Safety Precautions are
required to be established on the E&W Transmission System or the Systems of E&W
Users when work is to be carried out on or near to the Scottish Transmission S yste m or
the Systems of Scottish Users.
CONTENTS
(This contents page does not form part of the Grid Code)
OC8A.2 OBJECTIVE
OC8A.2.1 The objective of OC8A is to achieve:-
(i) Safety From The System when work on or near a System necessitates the provision
of Safety Precautions on another System on HV Apparatus up to a Connection
Point (or, in the case of OTSUA, Transmission Interface Point); and
OC8A.4 PROCEDURE
OC8A.4.1 Approval of Local Safety Instructions
OC8A.4.1.1 (a) In accordance with the timing requirements of its Bilateral Agreement, each E&W
User will supply to the Relevant E&W Transmission Licensee a copy of its Local
Safety Instructions relating to its side of the Connection Point at each Connection
Site, or in the case of OTSUA a copy of its Local Safety Instructions relating to its
side of the Transmission Interface Point at each Transmission Interface Site.
(b) In accordance with the timing requirements of each Bilateral Agreement, the Relevant
E&W Transmission Licensee will supply to each E&W User a copy of its Local Safety
Instructions relating to the Transmission side of the Connection Point at each
Connection Site, or in the case of OTSUA a copy of its Local Safety Instructions
relating to the Transmission side of the Transmission Interface Point at each
Transmission Interface Site.
(c) Prior to connection, the Relevant E&W Transmission Licensee and the E&W User
must have approved each other's relevant Local Safety Instructions in relation to
Isolation and Earthing.
OC8A.4.1.2 Either party may require that the Isolation and/or Earthing provisions in the other party’s
Local Safety Instructions affecting the Connection Site (or, in the case of OTSUA,
Transmission Interface Site) should be made more stringent in order that approval of the
other party’s Local Safety Instructions can be given. Provided these requirements are not
unreasonable, the other party will make such changes as soon as reasonably practicable.
These changes may need to cover the application of Isolation and/or Earthing at a place
remote from the Connection Site (or, in the case of OTSUA, Transmission Interface Site),
depending upon the System layout. Approval may not be withheld because the party
required to approve reasonably believes the provisions relating to Isolation and/or Earthing
are too stringent.
OC8A.4.1.3 If, following approval, a party wishes to change the provisions in its Local Safety
Instructions relating to Isolation and/or Earthing, it must inform the other party. If the
change is to make the provisions more stringent, then the other party merely has to note the
changes. If the change is to make the provisions less stringent, then the other party needs to
approve the new provisions and the procedures referred to in OC8A.4.1.2 apply.
RISSP NUMBER
PART 1
Safety Precautions have been established by the Implementing Safety Co-ordinator (or by another User on that User's
System connected to the Implementing Safety Co-ordinator's System) to achieve (in so far as it is possible from that side of
the Connection Point/Transmission Interface Point) Safety From The System on the following HV Apparatus on the
Requesting Safety Co-ordinator's System: [State identity - name(s) and, where applicable, identification of the HV circuit(s)
up to the Connection Point/Transmission Interface Point]:
______________________________________________________________________________________________
______________________________________________________________________________________________
Further Safety precautions required on the Requesting Safety Co-ordinator’s System as notified by the Implementing
Safety Co-ordinator.
______________________________________________________________________________________________
(a) ISOLATION
[State the Location(s) at which Isolation has been established (whether on the Implementing Safety Co-ordinator's System
or on the System of another User connected to the Implementing Safety Co-ordinator's System). For each Location,
identify each point of Isolation. For each point of Isolation, state the means by which the Isolation has been achieved, and
whether, immobilised and Locked, Caution Notice affixed, other safety procedures applied, as appropriate.]
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
(b) EARTHING
[State the Location(s) at which Earthing has been established (whether on the Implementing Safety Co-ordinator's System
or on the System of another User connected to the Implementing Safety Co-ordinator's System). For each Location,
identify each point of Earthing. For each point of Earthing, state the means by which Earthing has been achieved, and
whether, immobilised and Locked, other safety procedures applied, as appropriate].
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
1.3 ISSUE
2.1 CANCELLATION
Safety Precautions have been established by the Implementing Safety Co-ordinator (or by another User on that User's
System connected to the Implementing Safety Co-ordinator's System) to achieve (in so far as it is possible from that side of
the Connection Point/Transmission Interface Point) Safety From The System on the following HV Apparatus on the
Requesting Safety Co-ordinator's System: [State identity - name(s) and, where applicable, identification of the HV circuit(s)
up to the Connection Point/Transmission Interface Point]:
______________________________________________________________________________________________
______________________________________________________________________________________________
Recording of notification given to the Requesting Safety Co-ordinator concerning further Safety Precautions required on the
Requesting Safety Co-ordinator’s System.
(a) ISOLATION
[State the Location(s) at which Isolation has been established (whether on the Implementing Safety Co-ordinator's System
or on the System of another User connected to the Implementing Safety Co-ordinator's System). For each Location,
identify each point of Isolation. For each point of Isolation, state the means by which the Isolation has been achieved, and
whether, immobilised and Locked, Caution Notice affixed, other safety procedures applied, as appropriate.]
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
(b) EARTHING
[State the Location(s) at which Earthing has been established (whether on the Implementing Safety Co-ordinator's System
or on the System of another User connected to the Implementing Safety Co-ordinator's System). For each Location,
identify each point of Earthing. For each point of Earthing, state the means by which Earthing has been achieved, and
whether, immobilised and Locked, other safety procedures applied, as appropriate].
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
1.3 ISSUE
2.1 CANCELLATION
l have received confirmation from _________________________________________ (name of the Requesting Safety Co-
ordinator) at ________________________________________ (location) that the Safety Precautions set out in paragraph 1.2
are no longer required and accordingly the RISSP is cancelled.
NGSC Number:
NGET Safety Circular (NGSC) ..........................
Date:
RISSP prefixes - Issue x Issued By:
Example
Pursuant to the objectives of The Grid Code, Operating Code 8A1 - Safety Co-ordination, this circular will be
used in relation to all cross boundary safety management issues with the Relevant E&W Transmission
Licensee customers. Of particular note will be the agreed prefixes for the Record of Inter System Safety
Precautions (RISSP) documents.
Equipment Identification………………………………….………………………………………………………………………
………………………………………………………………………………………………………………………………………
Work to be done
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
Primary Earths
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
Actions taken to avoid Danger by draining, venting, purging and containment or dissipation of stored energy*
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
Further precautions to be taken during the course of the work to avoid System derived hazards*
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………
State whether this Permit for Work must be personally retained yes no
Issued (Signed)
Competent Person
CONTENTS
(This contents page does not form part of the Grid Code)
OC8B.1.7.3 For the purpose of the co-ordination of safety relating to HV Apparatus the term “Safety
Precautions” means Isolation and/or Earthing.
OC8B.2 OBJECTIVE
OC8B.2.1 The objective of OC8B is to achieve:-
(i) Safety From The System when work on or near a System necessitates the provision
of Safety Precautions on another System on HV Apparatus up to a Connection
Point (or, in the case of OTSUA, Transmission Interface Point); and
(ii) Safety From The System when work is to be carried out at a Scottish User’s Site or a
Transmission Site (as the case may be) on equipment of the Scottish User or the
Relevant Scottish Transmission Licensee (as the case may be) where the work or
equipment is near to HV Apparatus on the Implementing Safety Co-ordinator’s
System.
OC8B.3 SCOPE
OC8B.3.1 OC8B applies to The Company, Relevant Scottish Transmission Licensees and to
Scottish Users, which in OC8 means:-
(a) Generators (including where undertaking OTSDUW);
(b) Network Operators; and
(c) Non-Embedded Customers.
The procedures for the establishment of safety co-ordination by The Company in relation to
External Interconnections are set out in Interconnection Agreements with relevant
persons for the External Interconnections.
OC8B.4 PROCEDURE
OC8B.4.1 Approval Of Safety Rules
OC8B.4.1.1 (a) In accordance with the timing requirements of its Bilateral Agreement, each Scottish
User will supply to the Relevant Scottish Transmission Licensee a copy of its Safety
Rules relating to its side of the Connection Point at each Connection Site or in the
case of OTSUA a copy of its Local Safety Instructions relating to its side of the
Transmission Interface Point at each Transmission Interface Site.
(b) In accordance with the timing requirements of each Bilateral Agreement, the Relevant
Scottish Transmission Licensee will supply to each Scottish User a copy of its
Safety Rules relating to the Transmission side of the Connection Point at each
Connection Site or in the case of OTSUA a copy of its Local Safety Instructions
relating to the Transmission side of the Transmission Interface Point at each
Transmission Interface Site.
(c) Prior to connection the Relevant Scottish Transmission Licensee and the Scottish
User must have approved each other’s relevant Safety Rules in relation to Isolation
and Earthing.
OC8B.4.1.2 Either party may require that the Isolation and/or Earthing provisions in the other party’s
Safety Rules affecting the Connection Site (or, in the case of OTSUA, Transmission
Interface Site) should be made more stringent in order that approval of the other party’s
Safety Rules can be given. Provided these requirements are not unreasonable, the other
party will make such changes as soon as reasonably practicable. These changes may need
to cover the application of Isolation and/or Earthing at a place remote from the Connection
Site (or, in the case of OTSUA, Transmission Interface Site), depending upon the System
layout. Approval may not be withheld because the party required to approve reasonably
believes the provisions relating to Isolation and/or Earthing are too stringent.
OC8B.4.1.3 If, following approval, a party wishes to change the provisions in its Safety Rules relating to
Isolation and/or Earthing, it must inform the other party. If the change is to make the
provisions more stringent, then the other party merely has to note the changes. If the change
is to make the provisions less stringent, then the other party needs to approve the new
provisions and the procedures referred to in OC8B.4.1.2 apply.
OC8B.4.2 Safety Co-ordinators
Part 1
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
(a) ISOLATION
State the Locations(s) at which Isolation has been established on the Implementing
Safety Co-ordinator's System. For each Location, identify each point of Isolation. For
each point of Isolation state, the means by which the Isolation has been achieved, and
whether, immobilised and Locked, Caution Notice affixed, other Safety Precautions
applied, as appropriate.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
State the Locations(s) at which Earthing has been established on the Implementing
Safety Co-ordinator's System. For each Location, identify each point of Earthing. For
each point of Earthing state, the means by which the Earthing has been achieved, and
whether, immobilised and Locked, other Safety Precautions applied, as appropriate.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
1.3 ISSUE
PART 2
2.1 CANCELLATION
PART 1
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
(a) ISOLATION
State the Location(s) at which isolation has been established on the Implementing
Safety Co-ordinator's System. For each Location, identify each point of Isolation. For
each point of Isolation state, the means by which the Isolation has been achieved, and
whether, immobilised and Locked, Caution Notice affixed, other Safety Precautions
applied, as appropriate.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
State the Location(s) at which Earthing has been established on the Implementing
Safety Co-ordinator's System. For each Location, identify each point of Earthing. For
each point of Earthing state, the means by which the Earthing has been achieved, and
whether, immobilised and Locked, other Safety Precautions applied, as appropriate.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
1.3 ISSUE
PART 2
2.1 CANCELLATION
Not Used
1. ISSUE
To …………………………………………………………………………..………………….……………………………..
The following High Voltage Apparatus has been made safe in accordance with the Operational Safety Rules for the work detailed on this
Permit-to-Work to proceed:
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
Other precautions (see Operational Safety Rules 3.2.1(b), 4.6.2(c) and 5.5.3), and any special instructions:
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
……………………………………………………………………………………..……………………………………….……..….
Circuit Identification Issued: Colour …...…………. No. of wristlets …….………..… No. of step bolts ………..………
_____________________________________________________________________________________________
2. RECEIPT
I accept responsibility for carrying out the work on the Apparatus detailed on this Permit-to-Work, applying additional earths as
necessary. No attempt will be made by me, or by the persons under my charge, to work on any other Apparatus.
_____________________________________________________________________________________________
3. CLEARANCE
All persons under my control have been withdrawn and warned that it is no longer safe to work on the Apparatus detailed on this Permit-
to Work.
All gear, tools and additional earths have/have not* been removed. The works is/is not* complete.
All circuit identification equipment issued as above has been returned
_____________________________________________________________________________________________
4. CANCELLATION
………………………………………………….…………………………………………………………………………
(iii) WORK TO BE DONE …………………………………………………………………………………….
……………………………………………………….…………………………………………………………………...
……………………………………………………….…………………………………………………………………...
……………………………………………………….…………………………………………………………………...
_____________________________________________________________________________________________
2. (i) PRECAUTIONS TAKEN TO ACHIEVE SAFETY FROM THE SYSTEM: State points at which Plant/Apparatus has been
Isolated and specify position(s) of Earthing Devices applied. State actions taken to avoid Danger by draining, venting,
purging and containment or dissipation of stored energy.
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
Caution Notices have been affixed to all points of isolation
(ii) FURTHER PRECAUTIONS TO BE TAKEN DURING THE COURSE OF WORK TO AVOID SYSTEM DERIVED HAZARDS
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
…………………………………………….………………………………………………………………….………….
This Permit for Work must only be transferred under the Personal Supervision of a Senior Authorised
Person* ………………………………………..
Signed …………………………………………. being a Senior Authorised Person. Time: ……….. Date: …………….
____________________________________________________________________________________________
3. ISSUE
(i) Key Safe Key (No.)* …..….. (ii) Earthing Schedule* …….... (iii) Portable Drain Earths (No. off)* ………………
(iv) Selected Person’s Report (No.)* ………………….. (v) Circuit Identification Flags (No. off)* ……………………
for the issue of this Permit for Work Time: ……… Date: ………………
_____________________________________________________________________________________________
Issue 6 Revision 12 OC8B 09 March 2022
30 of 31
4. RECEIPT
I understand and accept my responsibilities under the ScottishPower Safety Rules as recipient of this Permit for Work and
acknowledge receipt of the items in Section 3.
Signed ……………………………………….. Name (Block Letters) ………………………………………………………….
being a Competent Person in the employ of Firm/Dept …………………………………… Time ………. Date …………
_____________________________________________________________________________________________
TRANSFER RECORD
†Signature of Person receiving re-issued Document in accordance with conditions detailed in Section 4.
_____________________________________________________________________________________________
5. CLEARANCE: I certify that all persons working under this Permit for Work have been withdrawn from, and warned not to work
on, the Plant/Apparatus in Section 1. All gears, tools, Drain Earths and loose material have been removed and guards and
access doors have been replaced, except for:
…………………………………………….………………………………………………………………….…………………
…………………………………………….………………………………………………………………….…………………
…………………………………………….………………………………………………………………….…………………
_____________________________________________________________________________________________
6. CANCELLATION: I certify that all items issued under Section 3 have been accounted for and the Control
Person(s)* …………………………………. informed of the cancellation and of any restrictions on returning
the Plant/Apparatus to service.
_____________________________________________________________________________________________
CONTINGENCY PLANNING
CONTENTS
(This contents page does not form part of the Grid Code)
OC9.3 SCOPE
OC9.3.1 OC9 applies to The Company and to Users, which in OC9 means:-
(a) Generators;
(b) Network Operators;
(c) Non-Embedded Customers;
(d) HVDC System Owners;
(e) DC Converter owners including DC Converter Station owners
(f) Restoration Contractors; and
(h) Relevant Transmission Licensees as provided for in the STC.
OC9.3.2 The procedure for the establishment of emergency support/contingency planning between
The Company and Externally Interconnected System Operators is set out in the
Interconnection Agreement with each Externally Interconnected System Operator.
In the event of a Total Shutdown or Partial Shutdown, The Company will, as soon as
reasonably practical, inform Users (or, in the case of a Partial Shutdown, Users which in
The Company's opinion need to be informed) and the BSCCo that a Total Shutdown, or, as
the case may be, a Partial Shutdown, exists and that The Company intends to implement
System Restoration. The Company shall (as soon as is practicable) determine, in its
reasonable opinion, the time and date with effect from which the Total Shutdown or Partial
Shutdown commenced and notify the BSCCo of that time and date.
In the event of a Total Shutdown and following such notification, in accordance with the
provisions of the BSC, the BSCCo will determine the Settlement Period with effect from
which the Balancing Mechanism is suspended.
In the event of a Partial Shutdown and following such notification, the Balancing Mechanism
will not be suspended until such time and date that the Market Suspension Threshold has
been met, or deemed to have been met, in accordance with the provisions of the BSC. The
Company shall carry out the monitoring activities required by paragraph G3.1 of the BSC.
Following determination by The Company pursuant to its obligations under the BSC that the
Market Suspension Threshold has been met, or deemed to have been met, The Company
shall (as soon as practicable) inform the BSCCo of that time and date at which the Market
Suspension Threshold was met, or deemed to have been met, and the BSCCo will
determine the Settlement Period in accordance with the provisions of the BSC with effect
from which the Balancing Mechanism will be suspended.
Should The Company determine that the Total System is capable of returning to normal
operation without meeting the Market Suspension Threshold, The Company will follow the
procedure given in OC9.4.7.11.
System Restoration will conclude with effect from the time and date determined in
accordance with OC9.4.7.6.3(d).
In respect of Scottish Transmission Systems, in exceptional circumstances, as specified in
the Local Joint Restoration Plan, SPT or SHETL, may invoke such Local Joint Restoration
Plan for its own Transmission System and Scottish Offshore Transmission Systems
connected to it and operate within its provisions. Scottish Transmission Licensees, may
instruct relevant Network Operators to activate one or more Distribution Restoration Zone
Plans.
OC9.4.7 SYSTEM RESTORATION PROCEDURE
OC9.4.7.1 The procedure necessary for a recovery from a Total Shutdown or Partial Shutdown is
known as a System Restoration. The procedure for a Partial Shutdown is the same as that
for a Total Shutdown except that it applies only to a part of the Total System. It should be
remembered that a Partial Shutdown may affect parts of the Total System which are not
themselves shutdown.
OC9.4.7.3 The Company will determine and instruct relevant Users to start System Restoration. These
instructions will normally recognise any applicable Local Joint Restoration Plan and/or
Distribution Restoration Zone Plan. User’s shall abide by The Company's instructions
during System Restoration, even if these conflict with the general overall strategy outlined in
OC9.4.7.6.3 or any applicable Local Joint Restoration Plan and/or Distribution
Restoration Zone Plan although a User may still reject an Emergency Instruction but only
on safety grounds (relating to personnel or plant) and this must be notified to The Company
immediately by telephone in accordance with the requirements of BC2.9.2.1. The Company's
and/or Network Operator’s instructions may (although this list should not be regarded as
exhaustive) be issued to;-
(a) Restoration Contractors relating to the start of supplying Active Power and subsequent
pick up of Demand;
(b) Network Operators or Non-Embedded Customers relating to the restoration of
Demand;
(c) Generators or HVDC System Owners or DC Converter Station owners relating to the
preparations for starting to supply Active Power when an external power supply is made
available to it;
(d) Network Operators to activate a Distribution Restoration Zone Plan.
Each of the above cases may include the requirement to undertake switching.
In respect of Scottish Transmission Systems, SPT and SHETL will act on The Company’s
behalf in accordance with its duties under the relevant Local Joint Restoration Plan or
Distribution Restoration Zone Plan. Restoration Contractors in Scotland shall abide by
SPT’s or SHETL’s instructions given in accordance with the Local Joint Restoration Plan
or Network Operator’s instructions given in accordance with the Distribution Restoration
Zone Plan.
OC9.4.7.4 (a) System Restoration following a Total Shutdown or where the Balancing Mechanism
has been suspended following a Partial Shutdown
During System Restoration where the Balancing Mechanism has been suspended, all
instructions by The Company to Users will be deemed to be Emergency Instructions under
BC2.9.2.2 (iii). All such Emergency Instructions will recognise any differing operational
capabilities (however termed) set out in the relevant Ancillary Services Agreement in
preference to the declared operational capability as registered pursuant to BC1 (or as
amended from time to time in accordance with the BC).
(b) System Restoration following a Partial Shutdown where the Balancing Mechanism
has not been suspended
During a Partial Shutdown where the Balancing Mechanism has not been suspended, all
instructions to Users connected to the Power Island will be deemed to be Emergency
Instructions under BC2.9.2.2 (iv). All such Emergency Instructions will recognise any
differing operational capabilities (however termed) set out in the relevant Ancillary Services
Agreement in preference to the declared operational capability as registered pursuant to BC1
(or as amended from time to time in accordance with the BC).
During System Restoration where the Balancing Mechanism has not been suspended, The
Company may issue instructions to Network Operators in England and Wales to activate a
Distribution Restoration Zone Plan. Such instructions will be deemed to be Emergency
Instructions under BC2.9.2.2 (iv). The Network Operator will be responsible for the
operation of the Distribution Restoration Zone which will take into account the capabilities
of Restoration Contractor’s Plant and other Plant and Apparatus within the Network
Operator’s System. Such instructions would be pursuant to the terms of the Distribution
Restoration Zone Plan.
In Scotland, Relevant Transmission Licensee’s may issue instructions (which would be
deemed to be Emergency Instructions) to Scottish Network Operators, to activate on one
or more Distribution Restoration Zone Plans.
OC9.4.7.5 Requirements to inform The Company and/or Network Operator where a Genset, HVDC
System, DC Converter or Restoration Contractor’s Plant and Apparatus cannot operate
within its safe operating limits during the Demand restoration process
OC9.4.7.5.1 If following the successful initiation and subsequent termination of a Local Joint Restoration
Plan or Distribution Restoration Zone Plan and during the wider System Restoration process,
any Genset or HVDC System or DC Converter Station or Restoration Contractor’s Plant and
Apparatus cannot, because of the Demand being experienced, keep within its safe operating
parameters, the Generator or HVDC System Owner or DC Converter Station owner or
Restoration Contractor shall, inform The Company and relevant Network Operator. The
Company or relevant Network Operator (as appropriate) will, where possible, either instruct
Demand to be altered or will re-configure the Total System or will instruct a User or Restoration
Contractors to re-configure its System in order to alleviate the problem being experienced by
the Genset or HVDC System or DC Converter or Restoration Contractor’s Plant and
OC9.4.7.6 Local Joint Restoration Plan and Distribution Restoration Zone Plan Establishment, Testing
and Provisions
The Company shall propose to the parties to a Restoration Plan a date for the exercise to
take place. All the Restoration Plan parties will jointly share the task of planning, preparing,
participating in, and facilitating the exercises, which will normally be in desktop format or as
otherwise agreed. The precise timing of the exercise for each Restoration Plan will be agreed
by all parties, but will not be less than once every 3 years. These exercises shall be run as
part of the wider assurance activities as provided for under OC5.7.4
OC9.4.7.7.2 The Company will advise the relevant Network Operator of the requirement to switch its
User System so as to segregate its Demand and to carry out such other actions as set out in
the Local Joint Restoration Plan. The relevant Network Operator will then operate in
accordance with the provisions of the Local Joint Restoration Plan.
OC9.4.7.7.3 The Company, in coordination with Relevant Transmission Licensees, will ensure that
switching carried out on the National Electricity Transmission System and other actions
are as set out in the Local Joint Restoration Plan.
OC9.4.7.7.4 Following notification from the Anchor Restoration Contractor that their Anchor Plant is
ready to accept load and, where provided for in the Local Joint Restoration Plan, Top Up
Restoration Contractors are in a position to subsequently synchronise to the Total System
as soon as external site supplies are restored, The Company will instruct the Anchor
Restoration Contractor (as provided for in OC9.4.5.2.2) to energise part of the Total
System. The Anchor Restoration Contractor and the relevant Network Operator will then,
in accordance with the requirements of the Local Joint Restoration Plan, establish
communication and agree the output of the relevant Anchor Plant and the connection of
Demand so as to establish a Power Island. As part of establishing a Power Island, The
Company may instruct one or more Top Up Restoration Contractors to subsequently
synchronise their Plant and Apparatus to the System to facilitate supplying more Demand
in the Power Island in accordance with the requirements of the Local Joint Restoration
Plan. During this period, Restoration Contractors will be required to regulate the output of
their relevant Plant to the Demand prevailing in the Power Island in which it is situated, on
the basis that it will (where practicable) seek to maintain the Target Frequency. The
Restoration Contractor’s Plant and Apparatus will (where practical) also seek to follow the
requirements relating to Reactive Power (which may include the requirement to maintain a
target voltage) set out in the Local Joint Restoration Plan.
OC9.4.7.7.5 Operation in accordance with the Local Joint Restoration Plan will be terminated by The
Company or relevant Transmission Licensee in Scotland (by notifying the Network
Operator and relevant Restoration Contractors) immediately after successfully connecting
the Power Island to another Power Island, or to the User System of another Network
Operator, or to the synchronising of Gensets at other Power Stations (which are not owned
and operated by Restoration Contractors) or HVDC Systems or DC Converter Stations.
Operation in accordance with the Local Joint Restoration Plan will also terminate in the
circumstances provided for in OC9.4.7.6.3(d) if an agreement is not reached or if The
Company states that it does not wish the remainder of the Local Joint Restoration Plan to
apply. Users will then comply with the Bid-Offer Acceptances or Emergency Instructions
of The Company.
The Company will subsequently interconnect the expanded Power Islands detailed in
OC9.4.7.9 to form larger Power Islands which will then be connected to form an integrated
system as detailed in OC9.5 which is a fundamental component of the Electricity System
Restoration Standard. This should eventually achieve the re-establishment of the Total
System or that part of the Total System subject to the Partial Shutdown, as the case may
be. The interconnection of Power Islands will utilise the provisions of all or part of OC9.5 (Re-
Synchronisation of De-synchronised Power Islands) and in such a situation such
provisions will be part of the System Restoration.
In making the determination that the Total System could return to normal operation, The
Company, would consider, amongst other things, the following areas:
(a) the extent to which the National Electricity Transmission System is contiguous and
energised;
(b) the integrity and stability of the National Electricity Transmission System and its
ability to operate in accordance with the Licence Standards;
(c) the impact that returning to normal may have on transmission constraints and the
corresponding ability to maximise the Demand connected; and
(d) the volume of generation, Electricity Storage or Demand not connected to the
National Electricity Transmission System; and
(e) the functionality of normal communication systems (ie electronic data communication
facilities, Control Telephony, etc).
In the event that the Balancing Mechanism has been suspended, it will not resume until the
start of the Settlement Period determined by the BSC Panel in accordance with paragraph
G3.1.2(d)(i) of the BSC.
For the avoidance of doubt, until resumption of the Balancing Mechanism, The Company is
likely to continue to issue Emergency Instructions in accordance with BC2.9.
Users shall use reasonable endeavours to submit Physical notifications ten hours prior to
the start of the Settlement Period determined by the BSC Panel in accordance with
paragraph G3.1.2(d)(i) of the BSC and as notified by The Company to Users, in preparation
for a return to normal operations.
In the event that the Balancing Mechanism has not been suspended and The Company has
determined that the Total System has returned to normal operation, The Company shall
inform Users and the BSCCo as soon as possible of the time and date at which (in The
Company’s determination) the Total System returned to normal operation.
OC9.4.7.12 The provisions of this OC9 shall cease to apply with effect from either:
(a) Where the Balancing Mechanism was suspended, the start of the Settlement Period
that the Balancing Mechanism resumed normal operation, as determined by the BSC
Panel and notified by the BSCCo in accordance with the provisions of the BSC; or
(b) Where the Balancing Mechanism was not suspended, the end of the Settlement
Period determined and notified by the BSCCo (in accordance with the provisions of the
BSC) and corresponding to the time and date that The Company determined that the
Total System had returned to normal operation.
OC9.4.7.13 Unless an Interconnector has an Anchor Restoration Contract, The Company will,
pursuant to the Interconnection Agreement with Externally Interconnected System
Operators, agree with Externally Interconnected System Operators when their
transmission systems can be Re-Synchronised, if they have become separated.
OC9.5.2.2 Direct Data Submission between Generators, HVDC System Owners, DC Converter Station
Owners and Network Operators
(a) In this section, OC9.5.2.2, relevant loading and other operational parameters are
exchanged directly between Generators, and/or HVDC System Owners and DC
Converter Station Owners and Network Operators.
Issue 6 Revision 21 OC9 04 March 2024
16 of 23
(b) The Company will issue an Emergency Instruction and/or a Bid-Offer Acceptance, to
the Generator and/or HVDC System Owner and/or DC Converter Station Owner to
"float" local Demand and maintain Frequency at Target Frequency. In this situation,
the Generator and/or HVDC System Owner and/or DC Converter Station owner will
be required to regulate the output of its Genset(s) at the Power Station in question to
the Demand prevailing in the Power Island in which it is situated, until Re-
Synchronisation takes place, on the basis that it will (where practicable) seek to maintain
the Target Frequency.
(c) The Network Operator is required to be in contact with the Generator and/or HVDC
System Operator and/or DC Converter Station owner so that the Network Operator
can supply data to the Generator and/or HVDC System Owner and/or DC Converter
Station owner on Demand changes within the Power Island.
(d) If more than one Generating Unit and/or HVDC System and/or DC Converter is
Synchronised to the Power Island, or is connected to the Power Island and available
to generate although not Synchronised, the Network Operator will need to liaise with
The Company to agree which Generating Units and/or HVDC Systems and/or DC
Converter stations will be utilised to accommodate changes in Demand in the Power
Island. The Network Operator will then maintain contact with the relevant Generator(s)
and/or HVDC System Owner(s) and/or DC Converter Station Owner(s) in relation to
that Plant.
(e) The Generator at the Power Station and/or HVDC System Owner and/or DC Converter
Station owner must contact the Network Operator if the level of Demand which it has
been asked to meet as a result of the Emergency Instruction and/or Bid-Offer
Acceptance to "float" and the detail on Demand passed on by the Network Operator,
is likely to cause problems for safety reasons (whether relating to personnel or Plant
and/or Apparatus) in the operation of its Generating Unit(s) or HVDC System(s) or DC
Converter Station(s), in order that the Network Operator can alter the level of Demand
which that Generator and/or HVDC System Owner and/or DC Converter Station owner
needs to meet. Any decision to operate outside any relevant parameters is one entirely
for the Generator and/or HVDC System Owner and/or DC Converter Station owner.
OC9.5.2.3 Control Features
(a) A system may be established in relation to a part of the National Electricity
Transmission System and a Network Operator’s User System, if agreed between The
Company and the Network Operator and any relevant Generator(s), HVDC System
Owner or DC Converter Station Owner, whereby upon a defined fault(s) occurring,
manual or automatic control features will operate to protect the National Electricity
Transmission System and relevant Network Operator’s User System and
Generator(s), HVDC System Owner(s) or DC Converter Station Owner(s) Plant and
simplify the restoration of Demand in the Power Island.
(b) In agreeing the establishment of such a system of control features, The Company will
need to consider its impact on the operation of the National Electricity Transmission
System.
(c) The Company will work with Network Operators involved in the wider System
Restoration process to help balance generation and Demand, and help ensure that it
does not have a destabilising effect on the Total System.
CONTENTS
(This contents page does not form part of the Grid Code)
OC10.2 OBJECTIVE
The objective of OC10 is to facilitate the provision of more detailed information, in writing, of
Significant Incidents which were initially orally reported under OC7 and to enable joint
investigations to take place if The Company and the relevant Users agree.
OC10.3 SCOPE
OC10.3.1 OC10 applies to The Company and to Users, which in OC10 means:-
(a) Generators (other than those which only have Embedded Small Power Stations and/or
Embedded Medium Power Stations);
(b) Network Operators;
(c) Non-Embedded Customers;
(d) DC Converter Station owners; and
(e) HVDC System Owners.
The procedure for Event information supply between The Company and Externally
Interconnected System Operators is set out in the Interconnection Agreement with each
Externally Interconnected System Operator.
OC10.4 PROCEDURE
OC10.4.1 Reporting
OC10.4.1.1 Written Reporting Of Events By Users To The Company
In the case of an Event which was initially reported by a User to The Company orally and
subsequently determined by The Company to be a Significant Incident, and accordingly
notified by The Company to a User pursuant to OC7, the User will give a written report to The
Company, in accordance with OC10. The Company will not pass on this report to other
affected Users but may use the information contained therein in preparing a report under OC10
to another User (or in a report which The Company is required to submit under an
Interconnection Agreement) in relation to a Significant Incident (or its equivalent under an
Interconnection Agreement or STC) on the National Electricity Transmission System which
has been caused by (or exacerbated by) the Significant Incident on the User's System.
OC10.4.1.2 Written Reporting Of Events By The Company To Users
In the case of an Event which was initially reported by The Company to a User orally and
subsequently determined by the User to be a Significant Incident, and accordingly notified by
the User to The Company pursuant to OC7, The Company will give a written report to the
User, in accordance with OC10. The User will not pass on the report to other affected Users
but:
MATTERS, IF APPLICABLE TO THE SIGNIFICANT INCIDENT AND TO THE RELEVANT USER (OR THE
COMPANY, AS THE CASE MAY BE) TO BE INCLUDED IN A WRITTEN REPORT GIVEN IN
ACCORDANCE WITH OC10.4.1 AND OC10.4.2
2. Location.
3. Plant and/or Apparatus directly involved (and not merely affected by the Event).
5. Demand (in MW) and/or generation (in MW) interrupted and duration of interruption.
6. Power Generating Module, Generating Unit, Power Park Module, HVDC System or DC
Converter - Frequency response (MW correction achieved subsequent to the Significant
Incident).
7. Power Generating Module, Generating Unit, Power Park Module, HVDC System or DC
Converter - MVAr performance (change in output subsequent to the Significant Incident).
CONTENTS
(This contents page does not form part of the Grid Code)
OC11.1.1 Operating Code No.11 ("OC11") sets out the requirement that:
(c) OTSDUW HV Apparatus on both Users’ Sites and the Transmission Sites;
shall have numbering and nomenclature in accordance with the system used from time to
time by The Company.
OC11.1.2 The numbering and nomenclature (if required under the system of numbering and nomenclature
used from time to time by The Company) of each item of HV Apparatus shall be included in the
Operation Diagram prepared for each Transmission Site or User Site, as the case may be.
Further provisions on Operation Diagrams are contained in the Connection Conditions or
European Connection Conditions and in each Bilateral Agreement.
OC11.1.3 In OC11, the term "HV Apparatus" includes any SF6 Gas Zones associated with any HV
Apparatus.
OC11.1.4 In OC11 the term "OTSDUW HV Apparatus" applies to any HV Apparatus installed by a User as
OTSDUW until it is accepted on to the National Electricity Transmission System at which time for
the purposes of OC11 it will be termed Transmission HV Apparatus.
OC11.2 OBJECTIVE
OC11.2.1 The overall objective of OC11 is to ensure, so far as possible, the safe and effective operation of
the Total System and to reduce the risk of human error faults by requiring, in certain
circumstances, that the numbering and nomenclature of Users’ HV Apparatus and OTSDUW HV
Apparatus shall be in accordance with the system used from time to time by The Company.
OC11.3 SCOPE
OC11.3.1 OC11 applies to The Company and to Users, which in OC11 means:-
(a) Generators;
OC11.4 PROCEDURE
OC11.4.1.1 The term "User Site" means a site owned (or occupied pursuant to a lease, licence or other
agreement) by a User in which there is a Connection Point (and in the case of OTSDUW, where
there is a Connection Point or an Interface Point). For the avoidance of doubt, where a site is
owned by a Relevant Transmission Licensee but occupied by a User (as aforesaid), the site is a
User Site.
OC11.4.1.2 The term "Transmission Site" means a site owned (or occupied pursuant to a lease, licence or
other agreement) by a Relevant Transmission Licensee in which there is a Connection Point (or
in the case of OTSDUW, an Interface Point). For the avoidance of doubt, where a site is owned by
a User but occupied by a Relevant Transmission Licensee (as aforesaid), the site is an
Transmission Site.
Issue 6 Revision 0 OC11 05 March 2021
2 of 4
OC11.4.2 Transmission HV Apparatus Or OTSDUW HV Apparatus On Users' Sites
(b) when the Relevant Transmission Licensee is to install its HV Apparatus on a User’s Site,
The Company shall (unless it gives rise to a Modification under the CUSC, in which case the
provisions of the CUSC as to the timing apply) notify the relevant User of the numbering and
nomenclature to be adopted for that HV Apparatus at least eight months prior to proposed
installation. When OTSDUW HV Apparatus is to be installed on a User’s Site, The Company
shall notify the relevant User of the numbering and nomenclature to be adopted for that
OTSDUW HV Apparatus at least eight months prior to proposed installation;
(c) in the case of HV Apparatus, the notification will be made in writing to the relevant User and
will consist of both a proposed Operation Diagram incorporating the proposed new
Transmission HV Apparatus to be installed, its proposed numbering and nomenclature,
and the date of its proposed installation. In the case of OTSDUW HV Apparatus, the
notification will be provided as part of the OTSDUW Network Data and Information;
(d) the relevant User will respond in writing to The Company within one month of the receipt of
the notification, confirming receipt and confirming either that any other HV Apparatus of the
relevant User on such User Site does not have numbering and/or nomenclature which could
be confused with that proposed by The Company, or, to the extent that it does, that the
relevant other numbering and/or nomenclature will be changed before installation of the
Transmission HV Apparatus or OTSDUW HV Apparatus;
(e) the relevant User will not install, or permit the installation of, any HV Apparatus, including
OTSDUW HV Apparatus on such User Site which has numbering and/or nomenclature
which could be confused with Transmission HV Apparatus which is either already on that
User Site or which The Company has notified that User will be installed on that User Site.
(a) User HV Apparatus and any OTSDUW HV Apparatus on Transmission Sites shall have
numbering and nomenclature in accordance with the system used from time to time by The
Company;
(b) when a User is to install its HV Apparatus on an Transmission Site, or it wishes to replace
existing HV Apparatus on a Transmission Site and it wishes to adopt new numbering and
nomenclature for such HV Apparatus, the User shall (unless it gives rise to a Modification
under the CUSC in which case the provisions of the CUSC as to the timing apply) notify The
Company of the details of the HV Apparatus and the proposed numbering and nomenclature
to be adopted for that HV Apparatus, at least eight months prior to proposed installation;
(c) the notification will be made in writing to The Company and shall consist of both a proposed
Operation Diagram incorporating the proposed new HV Apparatus of the User to be
installed, its proposed numbering and nomenclature, and the date of its propose d
installation;
(d) The Company will respond in writing to the User within one month of the receipt of the
notification stating whether or not The Company accepts the User's proposed numbering
and nomenclature and, if they are not acceptable, it shall give details of the numbering and
nomenclature which the User shall adopt for that HV Apparatus;
(e) when a User is to install OTSDUW HV Apparatus on a Transmission Site, The Company
shall notify the relevant User of the numbering and nomenclature to be adopted for that HV
Apparatus at least eight months prior to proposed installation. This notification will be
provided as part of the OTSDUW Network Data and Information.
OC11.4.4 Changes
Issue 6 Revision 0 OC11 05 March 2021
3 of 4
Where The Company in its reasonable opinion has decided that it needs to change the existing
numbering or nomenclature of Transmission HV Apparatus on a User’s Site or of Users’ HV
Apparatus on a Transmission Site:
In either case the notification shall indicate the reason for the proposed change.
OC11.4.5 Users will be provided upon request with details of The Company's then current numbering and
nomenclature system in order to assist them in planning the numbering and nomenclature for
their HV Apparatus or OTSDUW HV Apparatus on Transmission Sites and OTSDUW HV
Apparatus on Users’ Sites.
OC11.4.6 When a User installs HV Apparatus or OTSDUW HV Apparatus which is the subject of OC11, the
User shall be responsible for the provision and erection of clear and unambiguous labelling
showing the numbering and nomenclature. Where a User is required by OC11 to change the
numbering and/or nomenclature of HV Apparatus which is the subject of OC11, the User will be
responsible for the provision and erection of clear and unambiguous labelling by the required
date.
When a Relevant Transmission Licensee installs HV Apparatus which is the subject of OC11,
The Company shall be responsible for the provision and erection of a clear and unambiguous
labelling showing the numbering and nomenclature. Where The Company in coordination with
the Relevant Transmission Licensee changes the numbering and /or nomenclature of HV
Apparatus which is the subject of OC11, The Company in coordination with the Relevant
Transmission Licensee will be responsible for the provision and erection of clear and
unambiguous labelling showing the numbering and nome nclature by the required date.
OC11.4.7 For sites in England and Wales, The Company will not change its system of numbering and
nomenclature in use immediately prior to the Transfer Date (which is embodied in OM5
(Operation Memorandum No.5 - Numbering and Nomenclature of HV Apparatus on the CEGB
Grid System Issue 3 June 1987)), other than to reflect new or newly adopted technology or HV
Apparatus. For the avoidance of doubt, this OC11.4.7 refers to the system of numbering and
nomenclature, and does not preclude changes to the numbering and/or nomenclature of HV
Apparatus which are necessary to reflect newly installed HV Apparatus, or re-configuration of HV
Apparatus installed, and similar changes being made in accordance with that system of
numbering and nomenclature.
SYSTEM TESTS
CONTENTS
(This contents page does not form part of the Grid Code)
OC12.2 OBJECTIVE
The overall objectives of OC12 are:
OC12.2.1 to ensure, so far as possible, that System Tests proposed to be carried out either by:
(a) a User (or certain persons in respect of Systems Embedded within a Network
Operator’s System) which may have an effect on the Total System or any part of the
Total System (in addition to that User's System) including the National Electricity
Transmission System; or
(b) by The Company which may have an effect on the Total System or any part of the Total
System (in addition to the National Electricity Transmission System)
do not threaten the safety of either their personnel or the general public, cause minimum threat
to the security of supplies and to the integrity of Plant and/or Apparatus, and cause minimum
detriment to The Company and Users;
OC12.2.2 to set out the procedures to be followed for establishing and reporting System Tests.
OC12.3 SCOPE
OC12 applies to The Company and to Users, which in OC12 means:-
(a) Generators other than in respect of Embedded Medium Power Stations and
Embedded Small Power Stations (and the term Generator in OC12 shall be
constructed accordingly);
(b) Network Operators;
(c) Non-Embedded Customers; and
(d) DC Converter Station owners other than in respect of Embedded DC Converter
Stations.
(e) HVDC System Owners other than in respect of Embedded HVDC Systems.
The procedure for the establishment of System Tests on the National Electricity
Transmission System, with Externally Interconnected System Operators which do not
affect any User, is set out in the Interconnection Agreement with each Externally
Interconnected System Operator. The position of Externally Interconnected System
Operators and Interconnector Users is also referred to in OC12.4.2.
OC12.3.2 Each Network Operator will liaise within The Company as necessary in those instances
where an Embedded Person intends to perform a System Test which may have an effect on
the Total System or any part of the Total System (in addition to that Generator’s or other
User’s System) including the National Electricity Transmission System. The Company is
not required to deal with such persons.
OC12.3.3 Each Network Operator shall be responsible for co-ordinating with the Embedded Person
or such other person and assessing the effect of any System Tests upon:
Issue 6 Revision 19 OC12 04 December 2023
2 of 6
(a) any Embedded Medium Power Station, Embedded Small Power Stations,
Embedded HVDC System or Embedded DC Converter Station within the Network
Operator’s System; or
(b) any other User connected to or within the Network Operator’s System.
The Company is not required to deal with such persons.
OC12.4 PROCEDURE
OC12.4.1 Proposal Notice
OC12.4.1.1 Where a User (or in the case of a Network Operator, a person in respect of Systems
Embedded within its System, as the case may be) has decided that it would like to undertake
a System Test it shall submit a notice (a "Proposal Notice”) to The Company at least twelve
months in advance of the date it would like to undertake the proposed System Test.
OC12.4.1.2 The Proposal Notice shall be in writing and shall contain details of the nature and purpose of
the proposed System Test and shall indicate the extent and situation of the Plant and/or
Apparatus involved.
OC12.4.1.3 If The Company is of the view that the information set out in the Proposal Notice is
insufficient, it will contact the person who submitted the Proposal Notice (the "Test
Proposer") as soon as reasonably practicable, with a written request for further information.
The Company will not be required to do anything under OC12 until it is satisfied with the
details supplied in the Proposal Notice or pursuant to a request for further information.
OC12.4.1.4 If The Company wishes to undertake a System Test, The Company shall be deemed to
have received a Proposal Notice on that System Test
OC12.4.1.5 Where, under OC12, The Company is obliged to notify or contact the Test Proposer, The
Company will not be so obliged where it is The Company that has proposed the System
Test. Users and the Test Panel, where they are obliged under OC12 to notify, send reports
to or otherwise contact both The Company and the Test Proposer, need only do so once
where The Company is the proposer of the System Test.
OC12.4.2 Preliminary Notice And Establishment Of Test Panel
OC12.4.2.1 Using the information supplied to it under OC12.4.1 The Company will determine, in its
reasonable estimation, which Users, other than the Test Proposer, may be affected by the
proposed System Test. If The Company determines, in its reasonable estimation, that an
Externally Interconnected System Operator and/or Interconnector User (or Externally
Interconnected System Operators and/or Interconnector Users) may be affected by the
proposed System Test, then (provided that the Externally Interconnected System Operator
and/or Interconnector User (or each Externally Interconnected System Operator and/or
Interconnector User where there is more than one affected) undertakes to all the parties to
the Grid Code to be bound by the provisions of the Grid Code for the purposes of the System
Test) for the purposes of the remaining provisions of this OC12, that Externally
Interconnected System Operator and/or Interconnector User (or each of those Externally
Interconnected System Operators and/or Interconnector Users) will be deemed to be a
User and references to the Total System or to the Plant and/or Apparatus of a User will be
deemed to include a reference to the Transmission or distribution System and Plant and/or
Apparatus of that Externally Interconnected System Operator and/or Interconnector
User or (as the case may be) those Externally Interconnected System Operators and/or
Interconnector Users. In the event that the Externally Interconnected System Operator
and/or Interconnector User (or any of the Externally Interconnected System Operators
and/or Interconnector Users where there is more than one affected) refuses to so undertake,
then the System Test will not take place.
OC12.4.2.2 The Company will appoint a person to co-ordinate the System Test (a "Test Co-ordinator")
as soon as reasonably practicable after it has, or is deemed to have, received a Proposal
Notice and in any event prior to the distribution of the Preliminary Notice referred to below.
The Test Co-ordinator shall act as Chairperson of the Test Panel and shall be an ex-officio
member of the Test Panel.
Issue 6 Revision 19 OC12 04 December 2023
3 of 6
(a) Where The Company decides, in its reasonable opinion, that the National Electricity
Transmission System will or may be significantly affected by the proposed System
Test, then the Test Co-ordinator will be a suitably qualified person nominated by The
Company after consultation with the Test Proposer and the Users identified under
OC12.4.2.1.
(b) Where The Company decides, in its reasonable opinion, that the National Electricity
Transmission System will not be significantly affected by the proposed System Test,
then the Test Co-ordinator will be a suitably qualified person nominated by the Test
Proposer after consultation with The Company.
(c) The Company will, as soon as reasonably practicable after it has received, or is deemed
to have received, a Proposal Notice, contact the Test Proposer where the Test Co-
ordinator is to be a person nominated by the Test Proposer and invite it to nominate a
person as Test Co-ordinator. If the Test Proposer is unable or unwilling to nominate a
person within seven days of being contacted by The Company then the proposed
System Test will not take place.
OC12.4.2.3 The Company will notify all Users identified by it under OC12.4.2.1 of the proposed System
Test by a notice in writing (a "Preliminary Notice”) and will send a Preliminary Notice to the
Test Proposer. The Preliminary Notice will contain:
(a) the details of the nature and purpose of the proposed System Test, the extent and
situation of the Plant and/or Apparatus involved and the identity of the Users identified
by The Company under OC12.4.2.1 and the identity of the Test Proposer;
(b) an invitation to nominate within one month a suitably qualified representative (or
representatives, if the Test Co-ordinator informs The Company that it is appropriate for
a particular User including the Test Proposer) to be a member of the Test Panel for the
proposed System Test;
(c) the name of the The Company representative (or representatives) on the Test Panel for
the proposed System Test; and
(d) the name of the Test Co-ordinator and whether they were nominated by the Test
Proposer or by The Company.
OC12.4.2.4 The Preliminary Notice will be sent within one month of the later of either the receipt by The
Company of the Proposal Notice, or of the receipt of any further information requested by
The Company under OC12.4.1.3. Where The Company is the proposer of the System Test,
the Preliminary Notice will be sent within one month of the proposed System Test being
formulated.
OC12.4.2.5 Replies to the invitation in the Preliminary Notice to nominate a representative to be a
member of the Test Panel must be received by The Company within one month of the date
on which the Preliminary Notice was sent to the User by The Company. Any User which
has not replied within that period will not be entitled to be represented on the Test Panel. If
the Test Proposer does not reply within that period, the proposed System Test will not take
place and The Company will notify all Users identified by it under OC12.4.2.1 accordingly.
OC12.4.2.6 The Company will, as soon as possible after the expiry of that one month period, appoint the
nominated persons to the Test Panel and notify all Users identified by it under OC12.4.2.1
and the Test Proposer, of the composition of the Test Panel.
OC12.4.3 Test Panel
OC12.4.3.1 A meeting of the Test Panel will take place as soon as possible after The Company has
notified all Users identified by it under OC12.4.2.1 and the Test Proposer of the composition
of the Test Panel, and in any event within one month of the appointment of the Test Panel.
CONTENTS
(This contents page does not form part of the Grid Code)
BC1.2 OBJECTIVE
The procedure for the submission of BM Unit Data and/or Generating Unit Data is intended
to enable The Company to assess which BM Units and Generating Units (which could be
part of a Power Generating Module) are expected to be operating in order that The Company
can ensure (so far as possible) the integrity of the National Electricity Transmission
System, and the security and quality of supply.
Where reference is made in this BC1 to Generating Units and/or Power Generating
Modules (unless otherwise stated) it only applies:
(a) to each Generating Unit which forms part of the BM Unit of a Cascade Hydro Scheme;
and
(b) at an Embedded Exemptable Large Power Station where the relevant Bilateral
Agreement specifies that compliance with BC1 is required:
(i) to each Generating Unit which could be part of a Synchronous Power Generating
Module, or
(ii) to each Power Park Module where the Power Station comprises Power Park
Modules.
BC1.3 SCOPE
BC1 applies to The Company and to Users, which in this BC1 means:-
(a) BM Participants;
(b) Externally Interconnected System Operators; and
(c) Network Operators.
(ii) any change is possible to the Physical Notification of a BM Unit within an Existing
AGR Plant within the Existing AGR Plant Flexibility Limit;
in relation to periods of low System NRAPM or (as the case may be) low Localised
NRAPM. The Company will also notify each Externally Interconnected System
Operator of the anticipated low System NRAPM or Localised NRAPM and request
assistance in obtaining changes to Physical Notifications from BM Units in that
External System.
(d) Following Gate Closure, the procedure of BC2.9.4 will apply. In this case The
Company will also endeavor, where time allows, to issue a National Electricity
Transmission System Warning – High Risk of Embedded Generation
Reduction and/or a National Electricity Transmission
System Warning Embedded Generation Control Imminent as applicable.
• for a change greater than 300MW and less than 1000MW 50MW per minute;
unless prior arrangements have been discussed and agreed with The Company. This
limitation is not intended to limit the Run-Up or Run-Down Rates provided as Dynamic
Parameters.
In the case where a BM Unit is affected by a Network Gas Supply Emergency load shedding
event, once Stage 2 or higher has been declared, then their Physical Notifications shall
represent the User's best estimate of the contracted power position of the affected BM Unit
at the time of the event, taking into account any mitigating actions to reduce the difference
between the contracted power position and the volume to be shed.
An example of the format of Physical Notification is shown below. The convention to be
applied is that where it is proposed that the BM Unit will be importing, the Physical
Notification is negative.
From To
Data Name BMU name Time From
level Time To Level
(MW) MW)
PN , TAGENT , BMUNIT01 , 2001-11-03 06:30 , 77 , 2001-11-03 07:00 , 100
PN , TAGENT , BMUNIT01 , 2001-11-03 07:00 , 100 , 2001-11-03 07:12 , 150
PN , TAGENT , BMUNIT01 , 2001-11-03 07:12 , 150 , 2001-11-03 07:30 , 175
A linear interpolation will be assumed between the Physical Notification From and To
Issue 6 Revision 15 BC1 07 December 2022
16 of 27
levels specified for the BM Unit by the BM Participant.
From To
Data Name BMU name Time Fromlevel Time To level
(MW) (MW)
MEL , TAGENT , BMUNIT01 , 2001-11-03 05:00 , 410 , 2001-11-03 09:35 , 410
MEL , TAGENT , BMUNIT01 , 2001-11-03 09:35 , 450 , 2001-11-03 12:45 , 450
For each BM Unit for each Up to 10 Bid-Offer Pairs as defined in the BSC.
Settlement Period:
0MW to 150MW /
151MW to 250MW / /
251MW to 300MW / /
301MW to 400MW / / /
401MW to 450MW / / /
451MW to 550MW / / / /
BM Unit Name
Power Park Module [unique identifier]
POWER PARK POWER PARK UNITS
UNIT AVAILABILITY Type A Type B Type C Type D
Description
(Make/Model)
Number of units
Power Park Module [unique identifier]
POWER PARK POWER PARK UNITS
UNIT AVAILABILITY Type A Type B Type C Type D
Description
(Make/Model)
Number of units
BC1.A.1.8.2 In the absence of the correct submission of a Power Park Module Availability Matrix the last
submitted (or deemed submitted) Power Park Module Availability Matrix shall be taken to
be the Power Park Module Availability Matrix submitted hereunder.
BC1.A.1.8.3 The Company will rely on the Power Park Units, Power Park Modules and BM Units
specified in such Power Park Module Availability Matrix running as indicated in the Power
Park Module Availability Matrix when it issues an instruction in respect of the BM Unit.
BC1.A.1.8.4 Subject as provided in PC.A.3.2.4 any changes to Power Park Module or BM Unit
configuration, or availability of Power Park Units which affects the information set out in the
Power Park Module Availability Matrix must be notified immediately to The Company in
accordance with the relevant provisions of BC1. Initial notification may be by telephone. In
some circumstances, such as a significant re-configuration of a Power Park Module due to
an unplanned outage, a revised Power Park Module Availability Matrix must be supplied on
The Company's request.
0MW to 150MW /
151MW to 250MW / /
251MW to 300MW / /
301MW to 400MW / / /
401MW to 450MW / / /
451MW to 550MW / / / /
BC1.A.10.1 For each Additional BM Unit and Secondary BM Unit the relevant BM Participant
will submit data relating to the effect of a Bid-Off Acceptance on each Grid Supply
Point within the GSP Group over which the Additional BM Unit or Secondary BM
Unit was defined.
BC1.A.10.2 For each Additional BM Unit and Secondary BM Unit the relevant BM Participant
will also provide the post-codes and MSIDs that make up the Additional BM Unit or
Secondary BM Unit
BMU Name
Operational Day from which values apply
Grid Supply Point % Impact Grid Supply Point % Impact
Target Data
Release Time Period Start Time Period End Time
02:00 02:00 D0 05:00 D+1
10:00 10:00 D0 05:00 D+1
16:00 05:00 D+1 05:00 D+2
16:30 16:30 D0 05:00 D+1
22:00 22:00 D0 05:00 D+2
In this table, D0 refers to the current day, D+1 refers to the next day and D+2 refers to the day
following D+1.
In all cases, data will be ½ hourly average MW values calculated by The Company.
Information to be released includes:
National Information
(i) National Indicated Margin;
(ii) National Indicated Imbalance;
(iii) Updated forecast of National Electricity Transmission System Demand.
CONTENTS
(This contents page does not form part of the Grid Code)
BC2.2 OBJECTIVE
The procedure covering the operation of the Balancing Mechanism and the issuing of
instructions to Users is intended to enable The Company as far as possible to maintain the
integrity of the National Electricity Transmission System together with the security and
quality of supply.
Where reference is made in this BC2 to Power Generating Modules or Generating Units
(unless otherwise stated) it only applies:
(a) to each Generating Unit which forms part of the BM Unit of a Cascade Hydro Scheme;
and
(b) at an Embedded Exemptable Large Power Station where the relevant Bilateral
Agreement specifies that compliance with BC2 is required:
(i) to each Generating Unit which could be part of a Synchronous Power Generating
Module, or
(ii) to each Power Park Module where the Power Station comprises Power Park
Modules.
BC2.3 SCOPE
BC2 applies to The Company and to Users, which in this BC2 means:-
(a) BM Participants;
(b) Externally Interconnected System Operators, and
(c) Network Operators.
In the case where a BM Unit is affected by a Network Gas Supply Emergency load shedding
event, once Stage 2 or higher has been declared, then their Physical Notifications shall
represent the User's best estimate of the contracted power position of the affected BM Unit
at the time of the event, taking into account any mitigating actions to reduce the difference
between the contracted power position and the volume to be shed.
Each BM Participant must, applying Good Industry Practice, ensure that each of its BM
Units follows the Physical Notification in respect of that BM Unit, except where the
generation output of a BM Unit for an affected site only is reduced as a result of a Stage 2 or
higher Network Gas Supply Emergency load shedding event , (and each of its Generating
Units follows the Physical Notification in the case of Physical Notifications supplied under
BC1.4.2(a)(2)) that is prevailing at Gate Closure (the data in which will be utilised in producing
the Final Physical Notification Data in accordance with the BSC) subject to variations arising
from:
(a) the issue of Bid-Offer Acceptances which have been confirmed by the BM Participant;
or
(b) instructions by The Company in relation to that BM Unit (or a Generating Unit) which
require, or compliance with which would result in, a variation in output or input of that BM
Unit (or a Generating Unit); or
(c) compliance with provisions of BC1, BC2 or BC3 which provide to the contrary.
BC2.6 COMMUNICATIONS
Electronic communications are always conducted in GMT. However, the input of data and
display of information to Users and The Company and all other communications are
conducted in London time.
BC2.6.1 Normal Communication With Control Points
(a) With the exception of BC2.6.1(c) below, Bid-Offer Acceptances and, unless otherwise
agreed with The Company, Ancillary Service instructions shall be given by automatic
logging device and will be given to the Control Point for the BM Unit. For all Planned
Maintenance Outages the provisions of BC2.6.5 will apply. For Generating Units
(including DC Connected Power Park Modules (if relevant)) communications under
BC2 shall be by telephone unless otherwise agreed by The Company and the User.
(b) Bid-Offer Acceptances and Ancillary Service instructions must be formally
acknowledged immediately by the BM Participant (or the relevant person on its behalf)
via the Control Point for the BM Unit or Generating Unit in respect of that BM Unit or
that Generating Unit. The acknowledgement and subsequent confirmation or rejection,
within two minutes of receipt, is normally given electronically by automatic logging device.
If no confirmation or rejection is received by The Company within two minutes of the
issue of the Bid-Offer Acceptance, then The Company will contact the Control Point
for the BM Unit by telephone to determine the reason for the lack of confirmation or
rejection. Any rejection must be given in accordance with BC2.7.3 or BC2.8.3.
(c) In the event of a failure of the logging device or an outage of The Company’s computer
system, Bid-Offer Acceptances and instructions will be given, acknowledged, and
confirmed or rejected by telephone. The provisions of BC2.9.7 are also applicable.
(d) In the event that in carrying out the Bid-Offer Acceptances or providing the Ancillary
Services, or when operating at the level of the Final Physical Notification Data as
provided in BC2.5.1, an unforeseen problem arises, caused on safety grounds (relating
to personnel or plant), The Company must be notified without delay by telephone.
(e) The provisions of BC2.5.3 are also relevant.
(f) Submissions of revised MVAr capability may be made by facsimile transmission, using
the format given in Appendix 3 to BC2.
(g) Communication will normally be by telephone for any purpose other than Bid-Offer
Acceptances, in relation to Ancillary Services or for revisions of MVAr data.
(h) Submissions of revised availability of Frequency Sensitive Mode may be made by
facsimile transmission, using the format given in Appendix 4 to BC2. This process should
only be used for technical restrictions to the availability of Frequency Sensitive Mode.
BC2.6.2 Communication With Control Points In Emergency Circumstances
The Company will issue Emergency Instructions direct to the Control Point for each BM
Unit [or Generating Unit] in Great Britain. Emergency Instructions to a Control Point will
normally be given by telephone (and will include an exchange of operator names).
BC2.6.3 Communication With Network Operators In Emergency Circumstances
(iii) during System Restoration situation where the Balancing Mechanism has been
suspended, any instruction given by The Company will (unless The Company specifies
otherwise) be deemed to be an Emergency Instruction and need not be pre-fixed with
the words ‘This is an Emergency Instruction’; and
(iv) during System Restoration where the Balancing Mechanism has not been suspended,
any instruction issued to Restoration Contractors or to Network Operators which are
part of an invoked Local Joint Restoration Plan will (unless The Company specifies
otherwise) be deemed to be an Emergency Instruction and need not be prefixed with
the words ‘This is an Emergency Instruction’. Equally during a System Restoration
where the Balancing Mechanism has not been suspended, any instruction to Network
Operators which are part of an activated Distribution Restoration Zone Plan will
(unless The Company specifies otherwise) be deemed to be an Emergency Instruction
and need not be prefixed by the words “This is an Emergency Instruction”.
BC2.9.2.3 In all cases under this BC2.9, except BC2.9.1.2 (e) where The Company issues an
Emergency Instruction to a BM Participant which is not rejected under BC2.9.2.1, the
Emergency Instruction shall be treated as a Bid-Offer Acceptance. For the avoidance of
doubt, any Emergency Instruction issued to a Network Operator or to an Externally
Interconnected System Operator or in respect of a Generating Unit that does not form part
of a BM Unit, will not be treated as a Bid-Offer Acceptance.
BC2.9.2.4 In the case of BC2.9.1.2 (e) (ii) where The Company issues an Emergency Instruction
pursuant to a Maximum Generation Service Agreement, payment will be dealt with in
accordance with the CUSC and the Maximum Generation Service Agreement.
BC2.9.2.5 In the case of BC2.9.1.2 (e) (iii) where The Company issues an Emergency Deenergisation
Instruction, payment will be dealt with in accordance with the CUSC, Section 5.
BC2.9.2.6 In the case of BC2.9.1.2 (e) (i), upon receipt of an Emergency Instruction by a Generator
during a System Restoration, the provisions of Section G of the BSC relating to
compensation shall apply.
BC2.9.3 Examples of Emergency Instructions
Issue 6 Revision 21 BC2 04 March 2024
16 of 39
BC2.9.3.1 In the case of a BM Unit or a Generating Unit, Emergency Instructions may include an
instruction for the BM Unit or the Generating Unit to operate in a way that is not consistent
with the Dynamic Parameters and/or Export and Import Limits.
BC2.9.3.2 In the case of a Generator, Emergency Instructions may include:
(a) an instruction to trip one or more Gensets (excluding Operational Intertripping); or
(b) an instruction to trip Mills or to Part Load a Generating Unit (as defined in the Glossary
and Definitions and not limited by BC2.2); or
(c) an instruction to Part Load a Power Generating Module and/or CCGT Module or Power
Park Module; or
(d) an instruction for the operation of CCGT Units within a CCGT Module (on the basis of
the information contained within the CCGT Module Matrix) when emergency
circumstances prevail (as determined by The Company in The Company's reasonable
opinion); or
(e) an instruction to generate outside normal parameters, as allowed for in 4.2 of the CUSC;
or
(f) an instruction for the operation of Generating Units within a Cascade Hydro Scheme
(on the basis of the additional information supplied in relation to individual Generating
Units) when emergency circumstances prevail (as determined by The Company in The
Company’s reasonable opinion); or
(g) an instruction for the operation of a Power Park Module (on the basis of the information
contained within the Power Park Module Availability Matrix) when emergency
circumstances prevail (as determined by The Company in The Company's reasonable
opinion).
BC2.9.3.3 Instructions to Network Operators relating to the Operational Day may include:
(a) a requirement for Demand reduction and disconnection or restoration pursuant to OC6;
(b) an instruction to effect a load transfer between Grid Supply Points;
(c) an instruction to switch in a System to Demand Intertrip Scheme;
(d) an instruction to split a network;
(e) an instruction to disconnect an item of Plant or Apparatus from the System;
(f) requirement for Embedded Generation Control or restoration pursuant to OC6B; or
(g) an instruction to activate a Distribution Restoration Zone Plan as provided for in
OC9.4.7.8.1.
BC2.9.4 Maintaining Adequate System and Localised NRAPM (Negative Reserve Active Power
Margin)
BC2.9.4.1 Where The Company is unable to satisfy the required System NRAPM or Localised NRAPM
by following the process described in BC1.5.5, The Company will issue an Emergency
Instruction to exporting BM Units for De-Synchronising on the basis of Bid-Offer Data
submitted to The Company in accordance with BC1.4.2(d). If The Company is still unable to
satisfy the required System NRAPM or Localised NRAPM then The Company may issue
Emergency Instructions to Network Operator(s) as set out under OC6B to carry
out Embedded Generation Control.
BC2.9.4.2 In the event that The Company is unable to differentiate between exporting BM Units
according to Bid-Offer Data, The Company will instruct a BM Participant to Shutdown a
specified exporting BM Unit for such period based upon the following factors:
(a) effect on power flows (resulting in the minimisation of transmission losses);
BC2.9.8.1 Within the GB Synchronous Area, the National Electricity Transmission System shall
be determined to be in an emergency state when operational security analysis indicates one or
more of the following situations occurring:
a) A situation where there is (or could be) a violation of one or more operational criteria as
defined under the Security and Quality of Supply Standard (SQSS); or
d) There is a failure of the computing facilities used to control and operate the National
Electricity Transmission System or unplanned outages of Electronic Communication
and Computing Facilities as provided for in BC2.9.7 or the loss of communication,
computing and data facilities with other Transmission Licensees as provided for in
STCP 06-4.
BC2.9.8.2 While the National Electricity Transmission System is in an emergency state if, after
issuing National Electricity Transmission System Warnings and Emergency Instructions in
Issue 6 Revision 21 BC2 04 March 2024
20 of 39
accordance with (but not limited to) the requirements under OC7.4 and BC2.9, the situation
deteriorates to such an extent that it results in:-
a) a Total Shutdown, The Company will suspend the market in accordance with the
provisions of OC9.4.6; or
b) a Partial Shutdown, The Company will suspend the market but only where
the Market Suspension Threshold has been met in accordance with OC9.4.6.
BC2.11 LIAISON WITH GENERATORS FOR RISK OF TRIP AND AVR TESTING
BC2.11.1 A Generator at the Control Point for any of its Large Power Stations may request The
Company's agreement for one of the Gensets at that Power Station to be operated under a
risk of trip. The Company's agreement will be dependent on the risk to the National
Electricity Transmission System that a trip of the Genset would constitute.
BC2.11.2 (a) Each Generator at the Control Point for any of its Large Power Stations will operate
its Synchronised Gensets (excluding Power Park Modules) with:
(i) AVRs in constant terminal voltage mode with VAR limiters in service at all times.
AVR constant Reactive Power or Power Factor mode should, if installed, be
disabled; and
(ii) its generator step-up transformer tap changer selected to manual mode,
unless released from this obligation in respect of a particular Genset by The Company.
For example, for a BM Unit ABCD-1 acceptance logged with a start time at 1400 hours and
with a FPN at 300MW:
“BM Unit ABCD-1 Bid-Offer Acceptance timed at 1400 hours. Acceptance consists of 4
MW/Time points as follows:
300MW at 1400 hours
400MW at 1415 hours
400MW at 1450 hours
300MW at 1500 hours”
(b) Ancillary Service instructions for Reactive Power will normally follow the form:
(a) an exchange of operator names;
(b) BM Unit Name;
(c) Time of instruction;
(d) Type of instruction (MVAr, VOLT, SETPOINT, SLOPE or TAPP)
(e) Target Value
(f) Target Time.
The times required in the instruction are expressed as London time.
For example, for BM Unit ABCD-1 instructed at 1400 hours to provide 100MVAr by 1415
hours:
“BM Unit ABCD-1 message timed at 1400 hours. MVAr instruction. Unit to plus 100 MVAr
target time 1415 hours.”
Instruction Type of
Description
Name Instruction
MVAr Output The individual MVAr output from the Genset onto the MVAr
National Electricity Transmission System at the Grid
Entry Point (or onto the User System at the User System
Entry Point in the case of Embedded Power Stations),
namely on the higher voltage side of the generator step-up
transformer or Grid Entry Point or User System Entry
Point in the case of a Power Generating Module. In
relation to each Genset, where there is no HV indication,
The Company and the Generator will discuss and agree
equivalent MVAr levels for the corresponding LV indication.
Target Voltage Target voltage levels to be achieved by the Genset on the VOLT
Levels National Electricity Transmission System at the Grid
Entry Point (or on the User System at the User System
Entry Point in the case of Embedded Power Stations,
namely on the higher voltage side of the generator step-
up transformer or Grid Entry Point or User System Entry
Point in the case of a Power Generating Module. Where
a Genset is instructed to a specific target voltage, the
Generator must achieve that target within a tolerance of
±1 kV (or such other figure as may be agreed with The
Company) by tap changing on the generator step-up
transformer, or adjusting the Genset terminal voltage,
subject to compliance with CC.6.3.8 (a) (v) or
ECC.6.3.8.3.3 (as applicable), to a value that is equal to
or higher than 1.0p.u. of the rated terminal voltage, or a
combination of both. In relation to each Genset, where
there is no HV indication, The Company and the
Generator will discuss and agree equivalent voltage
levels for the corresponding LV indication.
Tap Changes Details of the required generator step-up transformer tap TAPP
changes in relation to a Genset. The instruction for tap
changes may be a Simultaneous Tap Change
instruction, whereby the tap change must be effected by
the Generator in response to an instruction from The
Company issued simultaneously to relevant Power
Stations. The instruction, which is normally preceded by
advance notice, must be effected as soon as possible, and
in any event within one minute of receipt from The
Company of the instruction.
For a Simultaneous Tap Change, change Genset
generator step-up transformer tap position by one [two] taps
to raise or lower (as relevant) System voltage, to be
executed at time of instruction.
BC2.A.2.7 In addition, the following provisions will apply to Reactive Power instructions:
(a) In circumstances where The Company issues new instructions in relation to more than
one BM Unit at the same Power Station at the same time, tapping will be carried out by
the Generator one tap at a time either alternately between (or in sequential order, if more
than two), or at the same time on, each BM Unit.
(b) Where the instructions require more than two taps per BM Unit and that means that the
instructions cannot be achieved within 2 minutes of the instruction time (or such longer
period as The Company may have instructed), the instructions must each be achieved
with the minimum of delay after the expiry of that period.
Full Output In the case of a Synchronous Generating Unit (as defined in the
Glossary and Definitions ((which could be part of a Synchronous
Power Generating Module) and not limited by BC2.2) is the MW
output measured at the generator stator terminals representing the
LV equivalent of the Registered Capacity at the Grid Entry Point,
and in the case of a Non-Synchronous Generating Unit (excluding
Power Park Units), HVDC Converter or DC Converter or Power
Park Module is the Registered Capacity at the Grid Entry Point.
Minimum Output In the case of a Synchronous Generating Unit (as defined in the
Glossary and Definitions ((which could be part of a Synchronous
Power Generating Module) and not limited by BC2.2 ) is the MW
output measured at the generator stator terminals representing the
LV equivalent of the Minimum Generation or Minimum Stable
Operating Level at the Grid Entry Point, and in the case of a Non-
Synchronous Generating Unit (excluding Power Park Units),
HVDC Converter or DC Converter or Power Park Module is the
Minimum Generation or Minimum Stable Operating Level or
Minimum Active Power Transmission Capacity at the Grid Entry
Point.
BC2.A.3.2 The following provisions apply to faxed submission of revised MVAr data:
(a) The fax must be transmitted to The Company (to the relevant location in accordance with
GC6) and must contain all the sections from the relevant part of Annexure 1 and from
either Annexure 2 or 3 (as applicable) but with only the data changes set out. The
"notification time" must be completed to refer to the time of transmission, where the time
is expressed as London time.
(b) Upon receipt of the fax, The Company will acknowledge receipt by sending a fax back to
the User. The acknowledgement will either state that the fax has been received and is
legible or will state that it (or part of it) is not legible and will request re-transmission of
the whole (or part) of the fax.
(c) Upon receipt of the acknowledging fax the User will, if requested, re-transmit the whole
or the relevant part of the fax.
(d) The provisions of paragraphs (b) and (c) then apply to that re-transmitted fax.
Optional
Logo
Sent By : ........................................................................................................
................................................................................
Legibility of FAX :
Acceptable
REVISED REACTIVE POWER CAPABILITY DATA – GENERATING UNITS EXCLUDING POWER PARK
MODULES AND DC CONVERTERS
Generating Unit*
* For a Synchronous Power Generating Module and/or CCGT Module and/or a Cascade Hydro Scheme,
the redeclaration is for a Generating Unit within a Synchronous Power Generating Module and/or CCGT
Module and/or Cascade Hydro Scheme. For BM Units, quote The Company BM Unit id, for other units
quote the Generating Unit id used for OC2.4.1.2 Outage Planning submissions. Generating Unit has the
meaning given in the Glossary and Definitions and is not limited by BC2.2.
REVISION TO THE REACTIVE POWER CAPABILITY AT THE GENERATING UNIT STATOR TERMINALS
(at rated terminal volts) AS STATED IN THE RELEVANT ANCILLARY SERVICES AGREEMENT:
AT RATED MW
AT MINIMUM
OUTPUT (MW)
COMMENTS e.g. generator transformer tap restrictions, predicted end time if known
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________
REVISED REACTIVE POWER CAPABILITY DATA – POWER PARK MODULES, HVDC CONVERTERS
AND DC CONVERTERS
* For BM Units quote The Company BM Unit id, for other units quote the id used for OC2.4.1.2 Outage Planning
submissions
AT RATED MW
AT 50% OF RATED
MW
AT 20% OF RATED MW
AT 0% OF RATED
MW
COMMENTS e.g. generator transformer tap restrictions, predicted end time if known
_________________________________________________________________________
_________________________________________________________________________
Genset or DC Converter
The availability of the above unit to operate in Frequency Sensitive Mode is as follows:
Contract Mode e.g. A Availability for operation in Frequency Sensitive Mode [Y/N]
_________________________________________________________________________
_________________________________________________________________________
Time:
Date:
Signature:
CONTENTS
(This contents page does not form part of the Grid Code)
BC3.2 OBJECTIVE
The procedure for The Company to direct System Frequency control is intended to enable
(as far as possible) The Company to meet the statutory requirements of System
Frequency control.
BC3.3 SCOPE
BC3 applies to The Company and to GB Code Users and EU Code Users, whic h in t his
BC3 means:
(a) GB Generators with regard to their Large Power Stations (except those Large Power
Stations with a Registered Capacity less than 50MW comprising of Power Park
Modules),
(b) EU Generators with regard to their Large Power Stations,
(c) Network Operators,
(d) DC Converter Station owners and HVDC System Owners,
(e) other providers of Ancillary Services,
(f) Externally Interconnected System Operators.
(b) (i) The Company will specify within the range agreed with Generators and/or EIS Os
and/or DC Converter Station owners or HVDC System Owners (if so agreed as
described in BC3.1.3), Low Frequency Relay settings to be applied to Gensets or
DC Converters at DC Converter Stations or HVDC Systems pursuant to
BC3.6.1 (a) and instruct the Low Frequency Relay initiated res ponse plac ed in
and out of service.
(ii) Generators and/or EISOs and/or DC Converter Station owners or HVDC System
Owners (if so agreed as described in BC3.1.3) will comply with The Company
instructions for Low Frequency Relay settings and Low Frequency Relay
initiated response to be placed in or out of service. Generators or DC Conve rte r
Station owners or HVDC System Owners or EISOs may not alter such Low
Frequency Relay settings or take Low Frequency Relay initiated response out of
service without The Company's agreement (such agreement not to be
unreasonably withheld or delayed), except for safety reasons.
BC3.6.2 Low Frequency Relay Initiated Response from Demand and other Demand Modification
arrangements (which may include a DC Converter Station or HVDC System when Importing
Active Power from the Total System)
(a) The Company may, pursuant to an Ancillary Services Agreement, ut ilis e De mand
with the capability of Low Frequency Relay initiated Demand reduction in establishing
its requirements for Frequency Control.
(b) (i) The Company will specify within the range agreed, the Low Frequency Relay
settings to be applied pursuant to BC3.6.2 (a), the amount of Demand reduction to
be available and will instruct the Low Frequency Relay initiated response to be
placed in or out of service.
(ii) Users will comply with The Company instructions for Low Frequency Relay
settings and Low Frequency Relay initiated Demand reduction to be placed in or
out of service. Users may not alter such Low Frequency Relay settings or take
Low Frequency Relay initiated response out of service without The Company's
agreement, except for safety reasons.
(iii) In the case of any such Demand which is Embedded, The Company will notify
the relevant Network Operator of the location of the Demand, the amount of
Demand reduction to be available, and the Low Frequency Relay settings.
(c) The Company may also utilise other Demand modification arrangements purs uant t o
an agreement for Ancillary Services, in order to contribute towards Operating
Reserve.
(b) (i) The rate of change of Active Power output must be at a minimum rate of 2 per
cent of output per 0.1 Hz deviation of System Frequency above 50.4 Hz.
(ii) The reduction in Active Power output must be continuously and linearly
proportional, as far as is practicable, to the excess of Frequency above 50. 4 Hz
and must be provided increasingly with time over the period specified in (iii) below.
(iii) As much as possible of the proportional reduction in Active P ower out put must
result from the frequency control device (or speed governor) action and must be
achieved within 10 seconds of the time of the Frequency increase above 50.4 Hz.
(iv) The residue of the proportional reduction in Active Power output which results
from automatic action of the Genset (or DC Converter at a DC Converter
Station) output control devices other than the frequency control devices (or speed
governors) must be achieved within 3 minutes from the time of the Frequency
increase above 50.4 Hz.
(v) Any further residue of the proportional reduction which results from non-automat ic
action initiated by the Generator or DC Converter Station owner shall be initiated
within 2 minutes, and achieved within 5 minutes, of the time of the Frequency
increase above 50.4 Hz.
(c) Each GB Code User in respect of a Genset (or DC Converter at a DC Converter
Station) which is providing Limited High Frequency Response in ac cordance wit h
BC3.7.2 must continue to provide it until the Frequency has returned to or below 50. 4
Hz or until otherwise instructed by The Company.
BC.3.7.2.2 Plant in Limited Frequency Sensitive Mode applicable to EU Code Users
EU Code Users in respect of Gensets and HVDC Systems are required to operate in
Limited Frequency Sensitive Mode at all times unless ins truc ted by The Com pany t o
operate in Frequency Senstive Mode. Where EU Code Users Gensets and HVDC
Systems are required to operate in Limited Frequency Senstive Mode , then the
requirements of ECC.6.3.7.1 and ECC.6.3.7.2 shall apply. For the avoidance of doubt , t he
requirements defined in BC.3.7.2.1 do not apply to New Generators and HV DC S yste m
Owners.
BC3.7.3 Plant Operation to below Minimum Generation or Minimum Stable Operating Level
TERRE PROCESSES
CONTENTS
(This contents page does not form part of the Grid Code)
BC4.2 OBJECTIVE
This procedure facilitates the participation of BM Participants in the TERRE market.
Particpation in TERRE is voluntary for BM Participants.
BC4.3 SCOPE
BC4 applies to :-
(a) The Company;
(b) BM Participants;
(b) Externally Interconnected System Operators; and
(c) Network Operators.
All BM Participants who wish to participate in TERRE must have successfully completed the
prequalification process to be a RR provider as detailed in BC5.
BC4.4.2 Minimum Technical Requirements
All BM Participants who wish to participate in TERRE must have the following
capabilities:
(a) BM Participants must have the ability to submit data and receive instructions by the use
of electronic data communication facilities as provided for in CC.6.5.8 or ECC.6.5.8.
(b) BM Participants must be capable of following an RR Instruction issued by The
Company.
(c) BM Participants must be able to provide Physical Notifications.
(d) BM Participants must be able to provide a subset of Dynamic Parameters (as detailed
in BC4.5.2).
(e) BM Participants must provide operational metering for their total output and for any
individual component that may have an output greater than 1MW. This metering must
have the following accuracy;
a. For a BM Unit with either a Generation Capacity greater than 100MW or
Demand Capacity greater than 100MW, a metering accuracy better than 0.5%.
TERRE Bids must follow the formats and rules in the TERRE Data Validation and
Consistency Rules.
The Company shall provide data in accordance with the requirements of the BSC. The
following data items will be provided:
(a) TERRE Bids and details of those restricted
(b) Final Physical Notifications
(c) RR activations
(d) RR Instructions
(e) Interconnector Volumes per 15 minute period of the TERRE Activation Period
(f) The TERRE clearing price
(g) Volume of GB need met
BC4.9 Outages of computer systems leading to the suspension of the TERRE market
The TERRE market operates in short processing times meaning that Planned Maintenance
Outages or unplanned computer system failures can result in the suspension of the TERRE
market.
Suspension of the TERRE market in GB will occur in the following circumstances:
(b) Outages of computer systems leading to the suspension of the TERRE market as
provided for in BC4.9; or
(c) Operators of the TERRE Central Platform notify The Company that
the TERRE market has been or is to be suspended.
Where the TERRE market has been suspended as a result of item (a) above, or is to be or
has been suspended as a result of items (b) or (c) above, The Company will as soon as
reasonably practical, inform Users and the BSCCo that the TERRE market is to be or has
been suspended. The Company will notify Users and the BSSCo if
the TERRE market suspension arose as a result of a Total Shutdown or Partial
Shutdown event (which triggers System Restoration) or another condition in accordance
with the requirements of the BSC.
In the case of TERRE market suspension under BC4.10 (b) or (c), The Company shall (as
soon as is practicable) determine, in its reasonable opinion, the time and date from when
the TERRE market is to be suspended. The Company shall also
notify Users and the BSCCo of the time of TERRE market suspension and the reason for
the suspension.
Where the TERRE market has been suspended, it will not be resumed until the start of a
defined Settlement Period which shall be determined:-
i) by the BSC Panel in accordance with section G3.1.8 of the BSC (in the case of
a Total Shutdown or Partial Shutdown event (which triggers a System
Restoration); or
ii) by section Q.5.A of the BSC (in the case of TERRE market suspension for any other
reason other than System Restoration).
In the case of TERRE market suspension as a result of another event as provided for under
BC4.10(b) or BC4.10(c), Users shall use reasonable endeavours to submit TERRE Bids as
soon as possible after notification from The Company of the Settlement Period from when
the TERRE market is to be resumed.
PREQUALIFICATION PROCESSES
CONTENTS
(This contents page does not form part of the Grid Code)
BC5.1 PREQUALIFICATION................................................................................................... 2
BC5.1.1 Prequalification Timelines ................................................................................... 3
BC5.2 FCR PREQUALIFICATION PROCESS ........................................................................... 3
BC5.2.1 FCR Minimum Technical Requirements ................................................................. 3
BC5.3 FRR PREEQUALIFICATION PROCESS ........................................................................ 5
BC5.3.1 FRR Minimum Technical Requirements ................................................................ 5
BC5.4 RR PREQUALIFICATION PROCESS ............................................................................ 5
BC5.4.1 RR Minimum Technical Requirements .................................................................. 5
The Company shall list the current status and dates of potential status changes of
Balancing Services as Frequency Containment Reserves (FCR), Frequency
Restoration Reserves (FRR) or Replacement Reserves (RR) or existing GB.
Where a Balancing Service has been approved as a Standard Product or Specific
Product providing FCR, FRR or RR, The Company shall ensure that prequalification
processes for that Balancing Service follows the processes as set out here. The
Company shall ensure that each relevant Balancing Service requires a formal
application from the FCR, FRR or RR provider to prequalify.
BC5.1.1.1 The following minimum timescales shall be apply to the FCR, FRR and RR
prequalification processes;
(a) Within 8 weeks of a formal application from the FCR, FRR or RR provider The
Company shall confirm the application is complete or incomplete (from the
perspective of information provision)
(b) If the application is incomplete the FCR, FRR, or RR provider shall submit the
additional required information within 4 weeks of a request from The
Company or it will be presumed that the application has been withdrawn.
(c) For units connected to distribution networks, The Company shall liaise with
the relevant DNO(s) to identify potential limitations imposed on the proposed
Balancing Services Provider by the distribution networks.
(d) Within 3 months of confirming that all information has been provided, The
Company shall confirm if the potential FCR, FRR or RR provider meets the
requirements in BC5.2.1, BC5.3.1 or BC5.4.1 respectively.
BC5.1.1.2 The Company shall re-assess the qualification of FCR, FRR or RR
providing units or groups:
(f) An FCR provider shall guarantee the continuous availability of FCR, with the exception
of a forced outage of a FCR providing unit, during the period of time in which it is
obliged to provide FCR.
(g) Each FCR provider shall inform The Company, as soon as possible, about any
changes in the actual availability of its FCR providing unit and/or its FCR providing
group, in whole or in part, relevant for the results of this prequalification.
The relevant DNOs will identify potential distribution network restrictions, based on
technical reasons, on the provision of the proposed Balancing Service by the reserve
providing groups or units.
BC 5.3 FRR PREQUALIFICATION PROCESS
The Company shall ensure that each relevant Balancing Service prequalification
process shall, as a minimum, require the FRR provider to submit a self-certification of
the FRR Minimum Technical Requirements as defined in BC5.3.1 and BC5.3.2.
BC5.3.1 FRR Minimum Technical Requirements
Each FRR providing unit and each FRR providing group shall;
(a) activate FRR in accordance with the setpoint received from The Company;
(b) ensure that the FRR activation of the FRR providing units within a reserve
providing group can be monitored. For that purpose the FRR provider shall be
capable of supplying to The Company real-time measurements of the
connection point or another point of interaction agreed with The Company
concerning:
(i) time-stamped scheduled Active Power output;
(ii) time-stamped instantaneous Active Power for:
— each FRR providing unit,
(d) be capable of activating its complete manual reserve capacity on FRR within the
FRR full activation time;
(e) fulfil the FRR availability requirements;
(f) fulfil the ramping rate requirements
(g) inform The Company about a reduction of the actual availability of its FRR
providing unit or its FRR providing group or a part of its FRR providing group
as soon as possible.
Issue 6 Revision 0 BC5 05 March 2021
BC5.3.2 In addition to the requirements in BC5.3.1, where a relevant Balancing
Service is provided by reserve providing groups or units located in the distribution
systems, The Company shall ensure that the prequalification process requires the
following to be specified;
(a) voltage levels and connection points of the reserve providing units or groups;
(b) the DNO(s) who operate the distribution systems to which the reserve providing
units or groups are connected;
(c) the type of Active Power reserves;
(d) themaximum reserve capacity provided by the reserve providing units or groups at
each connection point; and
(e) the maximum rate of change of Active Power for the reserve providing units or
group
The relevant DNOs will identify potential distribution network restrictions, based on
technical reasons, on the provision of the proposed Balancing Service by the reserve
providing groups or units.
The Company shall ensure that each relevant Balancing Service prequalification
process shall, as a minimum, require the RR provider to submit a self-certification of
the RR Minimum Technical Requirements as defined in BC5.4.1 and BC5.4.2.
(i) the time-stamped scheduled a Active Power output, for each RR providing unit
and group and for each Power Generating Module or Demand unit of
a RR providing group with maximum Active Power output larger than or equal
to 1.5 MW;
(ii) the time-stamped instantaneous Active Power, for each RR providing unit
and group, and for each Power Generating Module or Demand unit of
a RR providing group with a maximum Active Power output greater than or
equal to 1.5 MW;
CONTENTS
(This contents page does not form part of the Grid Code)
DRC.2 OBJECTIVE
The objective of the DRC is to:
DRC.2.1 List and collate all the data to be provided by each category of User to The Company under
the Grid Code.
DRC.2.2 List all the data to be provided by The Company to each category of User under the Grid
Code.
DRC.3 SCOPE
DRC.3.1 The DRC applies to The Company, Users and Restoration Contractors, which in this DRC
means:-
(a) Generators (including those undertaking OTSDUW and/or those who own and/or
operate DC Connected Power Park Modules);
(b) Network Operators;
(c) DC Converter Station owners and HVDC System Owners;
(d) Suppliers;
(e) Non-Embedded Customers;
(f) Externally Interconnected System Operators;
(g) Interconnector Users;
(h) BM Participants; and
(i) Pumped Storage Generators and Generators in respect of Electricity Storage
Modules.
(j) Restoration Contractors (which would be pursuant to the requirements of their Anchor
Restoration Contract or Top Up Restoration Contract).
DRC.3.2 For the avoidance of doubt, the DRC applies to both GB Code Users and EU Code Users.
User Schedule
All Suppliers 12
All BM Participants 8
Restoration Contractors 2, 3, 6, 16
Notes:
(1) Network Operators must provide data relating to Small Power Stations and/or
Customer Generating Plant Embedded in their Systems when such data is requested
by The Company pursuant to PC.A.3.1.4 or PC.A.5.1.4.
(2) The data in schedules 1, 14 and 15 need not be supplied in relation to Medium Power
Stations connected at a voltage level below the voltage level of the Subtransmission
System except in connection with a CUSC Contract or unless specifically requested by
The Company.
(3) Each Network Operator within whose System an Embedded Medium Power Station
not subject to a Bilateral Agreement or Embedded DC Converter Station not subject
to a Bilateral Agreement is situated shall provide the data to The Company in respect
of each such Embedded Medium Power Station or Embedded DC Converter Station
or HVDC System.
(4) In the case of Schedule 2, Generators, HVDC System Owners, DC Converter Station
owners or Network Operators in the case of Embedded Medium Power Stations not
subject to a Bilateral Agreement or Embedded DC Converter Stations not subject to
a Bilateral Agreement, would only be expected to submit data in relation to Standard
Planning Data as required by the Planning Code.
(5) In the case of Generators undertaking OTSDUW, the Generator will need to supply User
data in accordance with the requirements of Large or Small Power Stations (as defined
in DRC.6.2) up to the Offshore Grid Entry Point. In addition, the User will also need to
submit Offshore Transmission System data in between the Interface Point and its
Connection Points in accordance with the requirements of Schedule 18.
(6) In the case of Restoration Contractors, data only needs to be provided by a
Restoration Contractor where such a Restoration Contractor is not a CUSC Party
and the data has not been submitted. In this case the data to be submitted would be
would be pursuant to the the terms of the Anchor Restoration Contract or Top Up
Restoration Contract.
ABBREVIATIONS:
SPD = Standard Planning Data DPD = Detailed Planning Data
CUSC Contract = User data which may be CUSC App. Form = User data which may be
submitted to the Relevant submitted to the
Transmission Licensees Relevant
by The Company, Transmission
following the acceptance Licensees by The
by a User of a CUSC Company, following an
Contract. application by a User for
a CUSC Contract.
Note:
All parameters, where applicable, are to be measured at nominal System Frequency
+ these SPD items should only be given in the data supplied with the application for a CUSC
Contract.
* Asterisk items are not required for Small Power Stations and Medium Power Stations
Information is to be given on a Unit basis, unless otherwise stated. Where references to CCGT
Modules are made, the columns "G1" etc should be amended to read "M1" etc, as appropriate
□ These data items may be submitted to the Relevant Transmission Licensees from The
Company in respect of the National Electricity Transmission System. The data may be
submitted to the Relevant Transmission Licensees in a summarised form e.g. network model;
the data transferred will have been originally derived from data submitted by Users to The
Company.
■ these data items may be submitted to the Relevant Transmission Licensee from The Company
in respect to Relevant Units only. The data may be submitted to the Relevant Transmission
Licensee in a summarised form e.g. network model; the data transferred will have been originally
derived from data submitted by Users to The Company.
IMPEDANCES:
(Unsaturated)
Direct axis synchronous reactance % on MVA □ DPD I
(PC.A.5.3.2(a))
Direct axis transient reactance % on MVA □ ■ SPD+
(PC.A.3.3.1(a)& PC.A.5.3.2(a)
Direct axis sub-transient reactance % on MVA □ DPD I
(PC.A.5.3.2(a))
Quad axis synch reactance (PC.A.5.3.2(a)) % on MVA □ DPD I
Quad axis sub-transient reactance % on MVA □ DPD I
(PC.A.5.3.2(a))
Stator leakage reactance (PC.A.5.3.2(a)) % on MVA □ DPD I
Armature winding direct current % on MVA □ DPD I
resistance. (PC.A.5.3.2(a))
Issue 6 Revision 21 DRC 04 March 2024
13 of 126
In Scotland, negative sequence resistance % on MVA □ DPD I
(PC.A.2.5.6 (a) (iv)
Note:- the above data item relating to armature winding direct-current resistance need only be provided by Generators in relation to
Generating Units or Synchronous Generating Units within Power Generating Modules commissioned after 1st March
1996 and in cases where, for whatever reason, the Generator is aware of the value of the data item.
TIME CONSTANTS
(Short-circuit and Unsaturated)
Direct axis transient time constant S □ DPD I
(PC.A.5.3.2(a))
Direct axis sub-transient time constant S □ DPD I
(PC.A.5.3.2(a))
Quadrature axis sub-transient time constant S □ DPD I
(PC.A.5.3.2(a))
Stator time constant (PC.A.5.3.2(a)) S □ DPD I
MECHANICAL PARAMETERS
(PC.A.5.3.2(a))
The number of turbine generator masses □ DPD II
Diagram showing the Inertia and Kgm2 □ DPD II
parameters for each turbine generator mass DPD II
for the complete drive train
Diagram showing Stiffness constants and Nm/rad □ DPD II
parameters between each turbine generator DPD II
mass for the complete drive train
Number of poles □ DPD II
Relative power applied to different parts of % □ DPD II
the turbine
Torsional mode frequencies Hz □ DPD II
Modal damping decrement factors for the □ DPD II
different mechanical modes
Note: The data items requested under Option 1 below may continue to be provided by Generators in relation to Generating
Units on the System at 9 January 1995 (in this paragraph, the "relevant date") or they may provide the new data items
set out under Option 2. Generators must supply the data as set out under Option 2 (and not those under Option 1) for
Generating Unit and Synchronous Power Generating Unit excitation control systems commissioned after the relevant
date, those Generating Unit or Synchronous Power Generating Unit excitation control systems recommissioned for
any reason such as refurbishment after the relevant date and Generating Unit or Synchronous Power Generating Unit
excitation control systems where, as a result of testing or other process, the Generator is aware of the data items listed
under Option 2 in relation to that Generating Unit or Synchronous Power Generating Unit.
Option 1
Option 2
Note: The data items requested under Option 1 below may continue to be provided by Generators in relation to Generating Units
on the System at 9 January 1995 (in this paragraph, the "relevant date") or they may provide the new data items set out
under Option 2. Generators must supply the data as set out under Option 2 (and not those under Option 1) for Generating
Unit and Synchronous Power Generating Unit governor control systems commissioned after the relevant date, those
Generating Unit and Synchronous Power Generating Unit governor control systems recommissioned for any reason
such as refurbishment after the relevant date and Generating Unit and Synchronous Power Generating Unit governor
control systems where, as a result of testing or other process, the Generator is aware of the data items listed under Option
2 in relation to that Generating Unit and Synchronous Power Generating Unit.
Option 1
End of Option 2
Maximum Hz DPD II
Normal Hz DPD II
Minimum Hz DPD II
*Output Usable (on a monthly basis) MW SPD (except in relation to CCGT Modules when
(PC.A.3.2.2(b)) required on a unit basis under the Grid Code,
this data item may be supplied under Schedule
3)
Number & Type of Power Park Units within □ SPD
each Power Park Module (PC.A.3.2.2(k))
Number & Type of Offshore Power Park SPD
Units within each Offshore Power Park
String and the number of Offshore Power
Park Strings and connection point within
each Offshore Power Park Module
(PC.A.3.2.2.(k))
In the case where an appropriate Reference the SPD
Manufacturer’s Data & Performance Manufacturer’s
Report is registered with The Company then Data &
subject to The Company’s agreement, the Performance
report reference may be given as an Report
alternative to completion of the following
sections of this Schedule 1 to the end of page
11 with the exception of the sections marked
thus # below.
□ ■
Point of connection to the National Electricity Text SPD
Transmission System (or the Total System
if Embedded) of the DC Converter Station or
HVDC System configuration in terms of
geographical and electrical location and
system voltage
□ ■
Minimum Generation MW SPD
□ ■
Minimum Import Capacity MW
Details of converter transformer tap changer control system in block Diagram DPD II
diagram form showing transfer functions of individual elements □
including parameters. (Only required for DC Converters and
HVDC Systems connected to the National Electricity
Transmission System.)
MW Export
Nominal loading rate MW/s DPD I
Maximum (emergency) loading rate MW/s DPD I
MW Import
Nominal loading rate MW/s DPD I
Maximum (emergency) loading rate MW/s DPD I
NOTE: Users are referred to Schedules 5 & 14 which set down data required for all Users directly
connected to the National Electricity Transmission System, including Power Stations. Generators
undertaking OTSDUW Arrangements and are utilising an OTSDUW DC Converter are referred to
Schedule 18.
This schedule contains the Genset Generation Planning Parameters required by The Company to facilitate
studies in Operational Planning timescales.
For a Generating Unit including those within a Power Generating Module (other than a Power Park Unit)
at a Large Power Station, the information is to be submitted on a unit basis and for a CCGT Module or Power
Park Module at a Large Power Station the information is to be submitted on a module basis, unless otherwise
stated.
Where references to CCGT Modules or Power Park Modules at a Large Power Station are made, the
columns "G1" etc should be amended to read "M1" etc, as appropriate. 6Contractors, data only needs to be
provided by a Restoration Contractor where they are not a CUSC Party and the data has not been submitted.
In this case the data to be submitted would be would be pursant to the the terms of the Anchor Restoration
Contract or Top Up Restoration Contract if required.
OUTPUT CAPABILITY
(PC.A.3.2.2)
Registered Capacity on a station and unit basis
(on a station and module basis in the case of MW □ ■ SPD
a CCGT Module or Power Park Module at a
Large Power Station)
REGIME UNAVAILABILITY
RUN-UP PARAMETERS
PC.A.5.3.2(f) & OC2.4.2.1(a)
Run-up rates (RUR) after 48 hour (Note that for DPD only a single value of run-up rate from Synch Gen to Registered
Shutdown: Capacity is required)
(See note 2 page 3)
MW Level 1 (MWL1) MW ■ DPD II -
OC2
MW Level 2 (MWL2) MW ■ DPD II -
OC2
Run-Down Rates (RDR): (Note that for DPD only a single value of run-down rate from Registered Capacity to de-
synch is required)
MWL2 MW ■ DPD II
OC2
RDR from RC to MWL2 MW/Min ■ DPD II
OC2
MWL1 MW ■ DPD II
OC2
RDR from MWL2 to MWL1 MW/Min ■ DPD II
OC2
RDR from MWL1 to de-synch MW/Min ■ DPD II
OC2
DATA to DATA
DATA DESCRIPTION UNITS RTL CAT. GENSET OR STATION DATA
CUSC CUSC G1 G2 G3 G4 G5 G6 STN
Contract App.
Form
REGULATION PARAMETERS
OC2.4.2.1(a)
Regulating Range MW ■ DPD II
Load rejection capability while still MW ■ DPD II
Synchronised and able to supply Load.
NOTES:
(1) To allow for different groups of Gensets within a Power Station (e.g., Gensets with the same
operator) each Genset may be allocated to one of up to four Synchronising Groups. Within each
such Synchronising Group the single synchronising interval will apply but between
Synchronising Groups a zero synchronising interval will be assumed.
(2) The run-up of a Genset from synchronising block load to Registered Capacity or Maximum
Capacity is represented as a three stage characteristic in which the run-up rate changes at two
intermediate loads, MWL1 and MWL2. The values MWL1 & MWL2 can be different for each
Genset.
OUTPUT PROFILES
CUSC CUSC
Contract App.
Form
In the case of Large Power Stations whose output MW F. yrs 1 - 7 Week 24 SPD
may be expected to vary in a random manner (e.g.,
wind power) or to some other pattern (e.g., Tidal)
sufficient information is required to enable an
understanding of the possible profile
Notes: 1. The week numbers quoted in the Update Time column refer to standard weeks in the
current year.
3. The Governor Droop should be provided for each Generating Unit (excluding Power Park Units), Power Park Module, HVDC Converter or DC Converter. The Response Capability should be provided for each
Genset or DC Converter.
4. Primary, Secondary and High Frequency Response are defined in CC.A.3.2 or ECC.A.3.2 and are based on a frequency ramp of 0.5Hz over 10 seconds. Primary Response is the minimum value of response
between 10s and 30s after the frequency ramp starts, Secondary Response between 30s and 30 minutes, and High Frequency Response is the minimum value after 10s on an indefinite basis.
5. For plants which have not yet Synchronised, the data values of MLP1 to MLP6 should be as described above. For plants which have already Synchronised, the values of MLP1 to MLP6 can take any value
between Designed Operating Minimum Level or Minimum Regulating Level and Registered Capacity or Maximum Capacity. If MLP1 is not provided at the Designed Minimum Operating Level, the value of
the Designed Minimum Operating Level should be separately stated.
6. For the avoidance of doubt Transmission DC Converters and OTSDUW DC Converters must be capable of providing a continuous signal indicating the real time frequency measured at the Transmission
Interface Point to the Offshore Grid Entry Point (as detailed in CC.6.3.7(e)(vii) and CC.6.3.7(e)(viii) or ECC.6.3..3.1.1(f) to enable Offshore Power Generating Modules, Offshore Generating Units, Offshore
Power Park Modules and/or Offshore DC Converters to satisfy the frequency response requirements of CC.6.3.7 or ECC.6.3.7.
7. Alternative governor settigs shall be supplied by Generators, HVDC System Owners and DC Converter Owners where operation is required as part of System Restoration - as required in CC.6.3.5 or
Issue 6 Revision 21 DRC 04 March 2024
41 of 126
ECC.6.3.5.2 and ECC.6.3.5.5(vii).
The data in this Schedule 5 is required from Users who are connected to the National Electricity
Transmission System via a Connection Point (or who are seeking such a connection). Generators
undertaking OTSDUW should use DRC Schedule 18 although they should still supply data under Schedule 5
in relation to their User’s System up to the Offshore Grid Entry Point.
Table 5 (a)
A Single Line Diagram showing all or part of the User’s System is SPD
required. This diagram shall include:-
The Single Line Diagram may also include additional details of the ■ ■
User’s Subtransmission System, and the transformers
connecting the User’s Subtransmission System to a lower
voltage. With The Company’s agreement, it may also include
details of the User’s System at a voltage below the voltage of the
Subtransmission System.
The data below is all Standard Planning Data. Details are to be given for all circuits shown on the Single Line Diagram
Table 5 (d)
Years Node 1 Node 2 Rated Operating Positive Phase Sequence % on 100 Zero Phase Sequence (self) % on Zero Phase Sequence (mutual) % on
Valid Voltage Voltage kV MVA 100 MVA 100 MVA
kV
R X B R X B R X B
Notes
1. Data should be supplied for the current, and each of the seven succeeding Financial Years. This should be done by showing for which years the data is valid in
the first column of the Table.
The data below is all Standard Planning Data, and details should be shown below of all transformers shown on the Single Line Diagram. Details of Winding Arrangement,
Tap Changer and earthing details are only required for transformers connecting the User’s higher voltage system with its Primary Voltage System.
Table 5 (e)
Direct/
ON/
Res/
OFF
Rea
Direct/
ON/
Res/
OFF
Rea
Direct/
ON/
Res/
OFF
Rea
Direct/
ON/
Res/
OFF
Rea
Direct/
ON/
Res/
OFF
Rea
*If Resistance or Ractance please give impedance value
Notes
1. Data should be supplied for the current, and each of the seven succeeding Financial Years. This should be done by showing for which years the data is valid in the first
column of the Table
2. For a transformer with two secondary windings, the positive and zero phase sequence leakage impedances between the HV and LV1, HV and LV2, and LV1 and LV2
windings are required.
Years Connection Switch No Rated Operating Rated short-circuit breaking Rated short-circuit peak Rated rms DC time constant
Valid Point Voltage kV Votage kV current making current continuous at testing of
rms rms current (A) asymmetrical
breaking ability
(s)
3 Phase kA 1 Phase kA
3 Phase kA 1 Phase kA
rms rms
Notes
(d) For Generating Units (other than Power Park Units) ■ DPD II
having a circuit breaker at the generator terminal voltage
clearance times for electrical faults within the
Generating Unit zone must be declared.
(d) an indication of which items of equipment may be out of service simultaneously during Planned
Outage conditions
(b) for all transformers connecting the User's Subtransmission System to a lower voltage:
Rated MVA
Voltage Ratio
Positive phase sequence resistance
Positive Phase sequence reactance
Tap-changer range
Number of tap steps
Tap-changer type: on-load or off-circuit
AVC/tap-changer time delay to first tap movement
AVC/tap-changer inter-tap time delay
(The Company advises Network Operators of National Years 2-5 Week 28)
Electricity Transmission System outages affecting their
Systems)
Network Operator informs The Company if unhappy with ■ " Week 30 OC2
proposed outages)
Network Operator details of relevant outages affecting the ■ Year 1 Week 32 OC2
Total System (OC2.4.1.3.3)
(The Company informs Users of aspects that may affect Year 1 Week 34)
their Systems) (OC2.4.1.3.3)
Users inform The Company if unhappy with aspects as ■ Year 1 Week 36 OC2
notified
(OC2.4.1.3.3)
The data below is to be provided to The Company as required for compliance with the applicable Retained
EU Law (Commission Regulation (EU) No 543/2013 (OC2.4.2.3)). Data provided under Article Numbers
7.1(a), 7.1(b), 15.1(a), 15.1(b), and 15.1(c) and 15.1(d) is to be provided using MODIS.
ECR USERS
FREQUENCY OF
ARTICLE DATA DESCRIPTION PROVIDING
SUBMISSION
No. DATA
All data in this schedule 7 is categorised as Standard Planning Data (SPD) and is required for existing and
agreed future connections. This data is only required to be updated when requested by The Company.
CODE DESCRIPTION
- No information collated under this Schedule will be transferred to the Relevant Transmission Licensees
CODE DESCRIPTION
OC1.7 From 31 December 2026 and during normal system operation, The Company
shall publish on a daily basis, 60% and 100% of the peak National Demand,
under pre System shutdown conditions for the following day, based on the latest
forecast that would feed into the System Restoration Regional targets by means
of messages inputted by The Company to the Balancing Mechanism
Reporting Service (BMRS).
From 31 December 2026 and during System Restoration, The Company shall
publish for each System Restoration Region, the Demand that is used to
calculate the National Demand on an hourly basis on a reasonable endeavours
basis by means of messages inputted by The Company to the Balancing
Mechanism Reporting Service (BMRS).
OC2 Surpluses and Output Useable (OU) requirements for each Generator over
varying timescales
BC3 Location, amount, and Low Frequency Relay settings of any Low Frequency
Relay initiated Demand reduction for Demand which is Embedded.
- No information collated under this Schedule will be transferred to the Relevant Transmission
Licensees
- In respect of OC1, the data would also be supplied to Restoration Contractors
1. The Transmission Licence requires The Company to publish annually the Seven Year
Statement which is designed to provide Users and potential Users with information to enable
Issue 6 Revision 21 DRC 04 March 2024
62 of 126
them to identify opportunities for continued and further use of the National Electricity
Transmission System.
When a User is considering a development at a specific site, certain additional information may
be required in relation to that site which is of such a level of detail that it is inappropriate to include
it in the Seven Year Statement. In these circumstances, the User may contact The Company
who will be pleased to arrange a discussion and the provision of such additional information
relevant to the site under consideration as the User may reasonably require.
2. The Transmission Licence also requires The Company to offer terms for an agreement for
connection to and use of the National Electricity Transmission System and further information
will be given by The Company to the potential User in the course of the discussions of the terms
of such an agreement.
The following information is required from each Network Operator and from each Non-Embedded Customer. The data
should be provided in calendar week 24 each year (although Network Operators may delay the submission until
calendar week 28).
DATA DESCRIPTION F. Yr. F. Yr. F. Yr. F. Yr. F. Yr. F. Yr. F. Yr. F. Yr. UPDATE DATA CAT
0 1 2 3 4 5 6 7 TIME
LV1 ■ ■
LV2 ■ ■
LV3 ■ ■
EHV ■ ■
HV ■ ■
Traction ■ ■
Lighting ■ ■
User System Losses ■ ■
NOTES:
Demand and Active Energy data should relate to the point of connection to the National Electricity
Transmission System and should be net of the output (as reasonably considered appropriate by the
User) of all Embedded Small Power Stations, Medium Power Stations and Customer Generating
Plant. Auxiliary demand of Embedded Power Stations should be included in the demand data
submitted by the User at the Connection Point. Users should refer to the PC for a full definition of
the Demand to be included.
3. Demand profiles and Active Energy data should be for the total System of the Network Operator,
including all Connection Points, and for each Non-Embedded Customer. Demand Profiles should
give the numerical maximum demand that in the User's opinion could reasonably be imposed on the
National Electricity Transmission System.
4. In addition the demand profile is to be supplied for such days as The Company may specify, but such
a request is not to be made more than once per calendar year.
The following information is required from each Network Operator and from each Non-Embedded Customer.
The data should be provided in calendar week 24 each year (although Network Operators may delay the
submission until calendar week 28).
Connection Point:
DATA DESCRIPTION Outturn Outturn F.Yr F.Yr F.Yr. F.Yr. F.Yr. F.Yr F.Yr F.Yr DATA CAT
(CUSC Contract □ & CUSC Application Form ■) Weather
1 2 3 4 5 6 7 8
Corrected
Date of a), b), c), d) or e) as denoted above. PC.A.4.3.3
Time of a), b), c), d) or e) as denoted above. PC.A.4.3.3
Connection Point Demand (MW) PC.A.4.3.1
Connection Point Demand (MVAr) PC.A.4.3.1
Deduction made at Connection Point for
Small Power Stations, Medium Power
PC.A.4.3.2(a)
Stations and Customer Generating Plant
(MW)
Reference to valid Single Line Diagram PC.A.4.3.5
Reference to node and branch data. PC.A.2.2
Note: The following data block can be repeated for each post fault network revision that may impact on the Transmission System.
Access Group:
Note: The following data block to be repeated for each Connection Point with the Access Group.
Name of associated Connection Point within
PC.A.4.3.1
the same Access Group:
Demand at associated Connection Point
PC.A.4.3.1
(MW)
Demand at associated Connection Point
PC.A.4.3.1
(MVAr)
Deduction made at associated Connection
Point for Small Power Stations, Medium
PC.A.4.3.2(a)
Power Stations and Customer Generating
Plant (MW)
Summated PC.A.3.1
Capacity of all .4(a)
these
Generating
Units
Where the Network Operator’s System places a constraint on the capacity of an Embedded Large Power
Station
PC.A.3.2
Station Name
.2(c)
Generating PC.A.3.2
Unit .2(c)
System PC.A.3.2
Constrained .2(c)(i)
Capacity
Reactive PC.A.3.2
Despatch .2(c)(ii)
Network
Restriction
Table 11(c)
For each Embedded Small Power Station of 1MW and above, the following information is required, effective 2015 in line with the Week 24 data submissions.
DATA An Connection Generator Technology CHP (Y/N) Registered Lowest Where it Control Control mode Loss of Loss of mains
DESCRIPTION Embedded Date unit Type capacity in voltage exports mode voltage target mains protection
Small (Financial Reference / Production MW (as node on electricity and reactive protection settings
Power Year for type defined in the most from wind PV range or target pf type
Station generator the up-to-date or storage, (as appropriate)
reference connecting Distribution Single the
unique to after week Code) Line geographical
each 24 2015 Diagram to location of the
Network which it primary or
Operator connects or higher
where it will voltage
export most substation to
of its power which it
connects
DATA CAT PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4 PC.A.3.1.4
(a) (a) (a) (a) (a) (a) (a) (a) (a) (a)
NOTES:
1. 'F.Yr.' means 'Financial Year'. F.Yr. 1 refers to the current financial year.
2. All Demand data should be net of the output (as reasonably considered appropriate by the User) of all Embedded
Small Power Stations, Embedded Medium Power Stations and Customer Generating Plant. Generation and /
or Auxiliary demand of Embedded Large Power Stations should not be included in the demand data submitted by
the User. Users should refer to the PC for a full definition of the Demand to be included.
3. Peak Demand should relate to each Connection Point individually and should give the maximum demand that in
the User's opinion could reasonably be imposed on the National Electricity Transmission System. Users may
submit the Demand data at each node on the Single Line Diagram instead of at a Connection Point as long as
the User reasonably believes such data relates to the peak (or minimum) at the Connection Point.
In deriving Demand any deduction made by the User (as detailed in note 2 above) to allow for Embedded Small
Power Stations, Embedded Medium Power Stations and Customer Generating Plant is to be specifically stated
as indicated on the Schedule.
4. The Company may at its discretion require details of any Embedded Small Power Stations or Embedded Medium
Power Stations whose output can be expected to vary in a random manner (e.g. wind power) or according to some
other pattern (e.g. tidal power)
5. Where more than 95% of the total Demand at a Connection Point is taken by synchronous motors, values of the
Power Factor at maximum and minimum continuous excitation may be given instead. Power Factor data should
allow for series reactive losses on the User's System but exclude reactive compensation network susceptance
specified separately in Schedule 5.
6. Where a Reactive Despatch Network Restriction is in place which requires the generator to maintain a target
voltage set point this should be stated as an alternative to the size of the Reactive Despatch Network Restriction.
Table 11 (d)
Network
Operator
Aggregate
Registered
Capacity Number of
Fuel Type Total MW PGMs Comments
Biomass
Fossil brown coal/lignite
Fossil coal-derived gas
Fossil gas
Fossil hard coal
Fossil oil
Fossil oil shale
Fossil peat
Geothermal
Hydro pumped storage
Hydro run-of-river and poundage
Hydro water reservoir
Marine
Nuclear
Other renewable
Solar
Waste
Wind offshore
Wind onshore
Other
The following information is required from each Network Operator and where indicated with an
asterisk from Externally Interconnected System Operators and/or Interconnector Users and
a Pumped Storage Generator and Generators in respect of Electricity Storage Modules.
Where indicated with a double asterisk, the information is only required from Suppliers.
Demand Control
For each half hour MW Wks 2-8 ahead 1000 Mon OC1
For each half hour MW Days 2-12 ahead 1200 Wed OC1
Cumulative percentage of
Connection Point Demand
(Active Power) which can be
disconnected by the following times
from an instruction from The
Company
Note: All demand refers to that at the time of forecast National Electricity Transmission System
peak demand.
Network Operators may delay the submission until calendar week 28
No information collated under this schedule will be transferred to the Relevant Transmission
Licensees (or Generators undertaking OTSDUW).
The data in this Schedule 13 is all Standard Planning Data, and is required from all Users other than
Generators who are connected to the National Electricity Transmission System via a Connection Point
(or who are seeking such a connection). A data submission is to be made each year in Week 24 (although
Network Operators may delay the submission until Week 28). A separate submission is required for each
node included in the Single Line Diagram provided in Schedule 5.
DATA DESCRIPTION UNITS F.Yr F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to
0 1 2 3 4 5 6 7 RTL
SHORT CIRCUIT INFEED TO THE CUSC CUSC
Contract App.
NATIONAL ELECTRICITY Form
TRANSMISSION SYSTEM FROM
USERS SYSTEM AT A CONNECTION
POINT
(PC.A.2.5)
□ ■
Name of node or
Connection Point
- at instant of fault kA □ ■
- Resistance % on 100 □ ■
- Reactance % on 100 □ ■
DATA DESCRIPTION UNITS F.Yr F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to
0 1 2 3 4 5 6 7 RTL
SHORT CIRCUIT INFEED TO THE CUSC CUSC
Contract App.
NATIONAL ELECTRICITY Form
TRANSMISSION SYSTEM FROM
USERS SYSTEM AT A CONNECTION
POINT
Negative sequence
impedances
of User’s System as seen
from
the Point of Connection or
node on the Single Line
Diagram (as appropriate).
If no data is given, it will be
assumed that they are equal
to the positive sequence
values.
- Resistance % on □ ■
100
- Reactance % on □ ■
100
The data in this Schedule 14 is all Standard Planning Data, and is to be provided by Generators, with
respect to all directly connected Power Stations, all Embedded Large Power Stations and all
Embedded Medium Power Stations connected to the Subtransmission System. A data submission is
to be made each year in Week 24.
Fault infeeds via Unit Transformers
A submission should be made for each Generating Unit (including those which are part of a
Synchronous Power Generating Module) with an associated Unit Transformer. Where there is more
than one Unit Transformer associated with a Generating Unit, a value for the total infeed through all
Unit Transformers should be provided. The infeed through the Unit Transformer(s) should include
contributions from all motors normally connected to the Unit Board, together with any generation (e.g.
Auxiliary Gas Turbines) which would normally be connected to the Unit Board, and should be
expressed as a fault current at the Generating Unit terminals for a fault at that location.
DATA DESCRIPTION UNITS F.Yr. F.Yr. F.Yr F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to
0 1 2 3 4 5 6 7 RTL
CUSC CUSC
(PC.A.2.5) Contract App.
Form
Name of Power Station □ ■
- at instant of fault kA □ ■
- Resistance % on 100 □ ■
- Reactance % on 100 □ ■
DATA DESCRIPTION UNITS F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to
0 1 2 3 4 5 6 7 RTL
CUSC CUSC
(PC.A.2.5) Contract App.
Form
Number of Station □ ■
Transformers
- at instant of fault kA □ ■
- after subtransient □ ■
fault
current contribution kA
has substantially
decayed
- Resistance % on □ ■
100
- Reactance % on □ ■
100
Note 1. The pre-fault voltage provided above should represent the voltage within the range 0.95 to 1.05
that gives the highest fault current
Issue 6 Revision 21 DRC 04 March 2024
80 of 126
Note 2. % on 100 is an abbreviation for % on 100 MVA
DATA DESCRIPTION UNITS F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to
0 1 2 3 4 5 6 7 RTL
CUSC CUSC
(PC.A.2.5) Contract App.
Form
Name of Power Station □ ■
DATA UNITS F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA DATA
DESCRIPTION 0 1 2 3 4 5 6 7 to DESCRIPTION
RTL
CUSC CUSC App. Form
Contract
- A continuous time Graphical
trace and table and
showing the root tabular □ ■
mean square of
the positive, kA
negative and zero versus s
sequence
components of the
fault current from
the time of fault
inception to 140ms
after fault inception
at 10ms intervals
- A continuous pu versus
time trace and s
table showing □ ■
the positive,
negative and
zero sequence
components of
retained voltage
at the terminals
or Common
Collection
Busbar, if
appropriate
- A continuous pu versus
time trace and s
table showing □ ■
the root mean
square of the
positive,
negative and
zero sequence
components of
retained voltage
at the fault
point, if
appropriate
DATA UNITS F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA DATA
DESCRIPTION 0 1 2 3 4 5 6 7 to DESCRIPTION
RTL
CUSC CUSC App. Form
Contract
For Power Park
Units that utilise a
protective control,
such as a crowbar
circuit,
- additional rotor % on □ ■
resistance MVA
applied to the
Power Park
Unit under a □ ■
fault situation
- additional rotor % on
reactance MVA
applied to the
Power Park
Unit under a
fault situation.
Positive sequence
X/R ratio of the □ ■
equivalent at time of
fault at the Common
Collection Busbar
Minimum zero
sequence impedance
of the equivalent at a □ ■
Common Collection
Busbar
Active Power MW
generated pre-fault □ ■
Number of Power
Park Units in □ ■
equivalent generator
Items of reactive □ ■
compensation
switched in pre-fault
Note 1. The pre-fault voltage provided above should represent the voltage within the range 0.95 pu to 1.05
pu that gives the highest fault current
Notes
1. The time periods identified in the above table represent the estimated time it would take to return the
Mothballed Power Generating Module, Mothballed Generating Unit, Mothballed Power Park Module
(Mothballed DC Connected Power Park Modules), Mothballed HVDC Systems, Mothballed HVDC
Converters or Mothballed DC Converter at a DC Converter Station to service once a decision to return has
been made.
2. Where a Mothballed Power Generating Module, Mothballed Generating Unit, Mothballed Power Park
Module (including a Mothballed DC Connected Power Park Module), Mothballed HVDC System,
Mothballed HVDC Converter or Mothballed DC Converter at a DC Converter Station can be physically
returned in stages covering more than one of the time periods identified in the above table then information
should be provided for each applicable time period.
3. The estimated notice to physically return MW output to service should be determined in accordance with Good
Industry Practice assuming normal working arrangements and normal plant procurement lead times.
4. The MW output values in each time period should be incremental MW values, e.g. if 150MW could be returned
in 2 – 3 months and an additional 50MW in 3 – 6 months then the values in the columns should be Nil, Nil, 150,
50, Nil, Nil, 200 respectively.
5. Significant factors which may prevent the Mothballed Power Generating Module, Mothballed Generating Unit,
Mothballed Power Park Module (Mothballed DC Connected Power Park Module). Mothballed HVDC
System, Mothballed HVDC Converter or Mothballed DC Converter at a DC Converter Station achieving the
estimated values provided in this table, excluding factors relating to Transmission Entry Capacity, should be
appended separately.
The following data items for alternative fuels need only be supplied with respect to each Generating Unit
whose primary fuel is gas including those which form part of a Power Generating Module.
Notes
1. Where a Generating Unit has the facilities installed to generate using more than one
alternative fuel type details of each alternative fuel should be given.
2. Significant factors and their effects which may prevent the use of alternative fuels achieving the
estimated values provided in this table (e.g. emissions limits, distilled water stocks etc.) should
be appended separately.
- No information collated under this Schedule will be transferred to the Relevant Transmission Licensees
The following data/text items are required from each Generator for each BM Unit at a Large Power
Station as detailed in PC.A.5.7. Data is not required for Restoration Contractors Plant and Apparatus.
The data should be provided in accordance with PC.A.1.2 and also, where possible, upon request from
The Company during a System Restoration. For Restoration Contractors who are party to a
Distribution Restoration Zone Plan, the data submitted should be supplied as part of Schedule 16 Part
II of this Data Registration Code.
a) Expected time for the first and subsequent BM Units to be Tabular or DPD II
Synchronised, at time intervals of 12 hours, 24 hours, 36 hours, Graphical
48 hours and 72 hours from the restoration of external power
supplies, assuming external power supplies are not available at
the User’s Site.
b) Describe any likely issues that would have a significant impact Text DPD II
on a BM Unit’s time to be Synchronised arising as a direct
consequence of the inherent design or operational practice of the
Power Station and/or BM Unit, e.g. limited barring facilities, time
from a Total Shutdown or Partial Shutdown at which batteries
would be discharged or the availability of primary fuel supplies .
a) Expected time for the first and subsequent BM Units to Tabular or DPD II
be Synchronised, at time intervals of 12 hours, 24 hours, Graphical
36 hours, 48 hours and 72 hours from the restoration of
external power supplies, assuming external power supplies
are not available at the User’s Site.
b) Describe any likely issues that would have a significant Text DPD II
impact on a BM Units time to be Synchronised arising as a
direct consequence of the inherent design or operational
practice of the HVDC System or DC Converter Station
and/or BM Unit, e.g. time from a Total Shutdown or Partial
Shutdown at which batteries would be discharged.
The expected time for each Restoration Contractor’s Plant to Tabular or DPD II
connect to the Network Operator’s System following a Total Graphical
Shutdown or Partial Shutdown. The assessment should include
the Restoration Contractor’s ability to reconnect or re-
synchronise all their Plant, to the Total System at time intervals of
12 hours, 24 hours, 36 hours, 48 hours and 72 hours from the
restoration of external power supplies.
Additionally, the data and supporting text should highlight any Tabular or DPD II
specific issues (eg those that would affect the time before which Graphical
the Restoration Contractor’s Plant could be energised) that
may arise as time progresses from Shutdown without external
supplies being restored or the availability of primary fuel supplies.
Submissions by Users using this Schedule 17 shall commence in 2011 and shall then continue in each
year thereafter
Access Group
Comments
The data in this Schedule 18 is required from Generators who are undertaking OTSDUW and connecting
to a Transmission Interface Point.
OTSDUW DEMANDS
This Single Line Diagram shall depict the arrangement(s) of all of the ■ ■ SPD
existing and proposed load current carrying Apparatus relating to both
existing and proposed Interface Points and Connection Points,
showing electrical circuitry (i.e. overhead lines, underground cables
(including subsea cables), power transformers and similar equipment),
operating voltages, circuit breakers and phasing arrangements
Operational Diagrams of all substations within the OTSDUW Plant and ■ ■ SPD
Apparatus
Notes
1. For information equivalent STC Reference: STCP12-1m Part 3 – 2.1 Branch Data
2. In the case where an overhead line exists within the OTSDUW Plant and Apparatus the Mutual inductances should also be provided.
The data below is Standard Planning Data, and details should be shown below of all transformers shown on the Single Line Diagram
Notes
1 For information the corresponding STC Reference is STCP12-1: Part 3 – 2.4 Transformers
The data below is all Standard Planning Data, and details should be shown below of all transformers shown on the Single Line Diagram
HV VH LV VL PSS/E Rating Tran Positive Phase Positive Phase EQUIVALENT ZPS PARAMETERS (FLIP) The The
NODE (kV) NODE (kV) Circuit (MVA) s- Sequence Sequence Com- Com
Taps
form Reactance % on Resistance % on pany -
Earth-
er 100MVA 100MVA Win- Shee pany
ing
ding
Impe- ZOH ZOL ZOT t Code
Type Arra Dflt X/R=20
dance
Range Step (Onlo nge
Max Min Nom Max Min Nom metho
+% to - size ad ment ROH XOH ROL XOL ROT XOT
Tap Tap Tap Tap Tap Tap d
% % Offlo % % % % % %
ad) 100 100 100 100 100 100
MVA MVA MVA MVA MVA MVA
Notes
The data below is all Standard Planning Data, and should be provided for all OTSUA switchgear (i.e. circuit breakers, load disconnectors and disconnectors)
Notes:
1.For information STC Reference: STCP12-1: Part 3 - 2.5 Reactive Compensation Equipment
2. Data relating to continuously variable reactive compensation equipment (such as statcoms or SVCs)
should be entered on the SVC Modelling table.
3. For the avoidance of doubt this includes any AC Reactive Compensation equipment included within the
OTSDUW DC Converter other than harmonic filter data which is to be entered in the harmonic filter data
table.
PC.A.2.4.1(e) A mathematical representation in block diagram format to model the control of any
dynamic compensation plant. The model should be suitable for RMS dynamic stability
type studies in which the time constants used should not be less than 10ms.
HV Node LV Node Control Nominal Target Max Min MVAr Slope % Voltage Normal R1 X1 R0 Z0 Trasnf Connection
Node Voltage Voltage MVAr at at HV Dependent Running PPS_R PPS_X ZPS_R ZPS_X Winding (Direct/
(kV) (kV) HV Q Limit Mode Type Tertiary)
Notes:
1.For information the equivalent STC Reference is: STCP12-1: Part 3 - 2.7 SVC Modelling Data
Filter Description
Manufacturer Model Filter Type Filter connection Notes
type (Delta/Star,
Grounded/
Ungrounded)
Parameter as applicable
Filter Capacitance Inductance (milli- Resistance Notes
Component (R, (micro-Farads) Henrys) (Ohms)
C or L)
Filter frequency characteristics (graphs) detailing for frequency range up to 10kHz and higher
Notes:
1. For information STC Reference: STCP12-1: Part 3 - 2.8 Harmonic Filter Data
The information listed below may be requested by The Company from each User undertaking OTSDUW with
respect to any Interface Point or Connection Point to enable The Company to assess transient overvoltage
on the National Electricity Transmission System.
(a) Busbar layout plan(s), including dimensions and geometry showing positioning of any current and
voltage transformers, through bushings, support insulators, disconnectors, circuit breakers, surge
arresters, etc. Electrical parameters of any associated current and voltage transformers, stray
capacitances of wall bushings and support insulators, and grading capacitances of circuit breakers;
(b) Electrical parameters and physical construction details of lines and cables connected at that busbar.
Electrical parameters of all plant e.g., transformers (including neutral earthing impedance or zig-zag
transformers if any), series reactors and shunt compensation equipment connected at that busbar (or
to the tertiary of a transformer) or by lines or cables to that busbar;
(c) Basic insulation levels (BIL) of all Apparatus connected directly, by lines or by cables to the busbar;
(d) Characteristics of overvoltage Protection devices at the busbar and at the termination points of all
lines, and all cables connected to the busbar;
(e) Fault levels at the lower voltage terminals of each transformer connected to each Interface Point or
Connection Point without intermediate transformation;
(f) The following data is required on all transformers within the OTSDUW Plant and Apparatus.
(g) An indication of which items of equipment may be out of service simultaneously during Planned
Outage conditions.
The information given below, both current and forecast, where not already supplied in this Schedule 14 may
be requested by The Company from each User if it is necessary for The Company to evaluate the
production/magnification of harmonic distortion on National Electricity Transmission System. The impact
of any third party Embedded within the User’s System should be reflected:-
(a) Overhead lines and underground cable circuits (including subsea cables) of the User's OTSDUW
Plant and Apparatus must be differentiated and the following data provided separately for each type:-
(b) for all transformers connecting the OTSDUW Plant and Apparatus to a lower voltage:-
Rated MVA
Voltage Ratio
Positive phase sequence resistance
Positive phase sequence reactance
Equivalent positive phase sequence interconnection impedance with other lower voltage points
The minimum and maximum Demand (both MW and MVAr) that could occur
Harmonic current injection sources in Amps at the Connection Points and Interface Points
(d) an indication of which items of equipment may be out of service simultaneously during Planned
Outage conditions
The information listed below, where not already supplied in this Schedule 14, may be requested by The
Company from each User undertaking OTSDUW with respect to any Connection Point or Interface Point if
it is necessary for The Company to undertake detailed voltage assessment studies (e.g. to examine potential
voltage instability, voltage control co-ordination or to calculate voltage step changes on the National
Electricity Transmission System).
(a) For all circuits of the User’s OTSDUW Plant and Apparatus:-
(b) for all transformers connecting the User's OTSDUW Plant and Apparatus to a lower voltage:-
Rated MVA
Voltage Ratio
Positive phase sequence resistance
Positive Phase sequence reactance
Tap-changer range
Number of tap steps
Tap-changer type: on-load or off-circuit
AVC/tap-changer time delay to first tap movement
AVC/tap-changer inter-tap time delay
The information listed below, both current and forecast, and where not already supplied under this Schedule
14, may be requested by The Company from each User undertaking OTSDUW with respect to any
Connection Point or Interface Point where prospective short-circuit currents on Transmission equipment
are close to the equipment rating.
(a) For all circuits of the User’s OTSDUW Plant and Apparatus:-
Positive phase sequence resistance
Positive phase sequence reactance
Positive phase sequence susceptance
Zero phase sequence resistance (both self and mutuals)
Zero phase sequence reactance (both self and mutuals)
Zero phase sequence susceptance (both self and mutuals)
(b) For all transformers connecting the User's OTSDUW Plant and Apparatus to a lower voltage:-
Rated MVA
Voltage Ratio
Positive phase sequence resistance (at max, min and nominal tap)
Positive Phase sequence reactance (at max, min and nominal tap)
Zero phase sequence reactance (at nominal tap)
Tap changer range
Earthing method: direct, resistance or reactance
Impedance if not directly earthed
Fault infeed data to be submitted by OTSDUW Plant and Apparatus providing a fault infeed (including
OTSDUW DC Converters) (PC.A.2.5.5)
A submission is required for OTSDUW Plant and Apparatus (including OTSDUW DC Converters at each
Transmission Interface Point and Connection Point. The submission shall represent operating conditions
that result in the maximum fault infeed. The fault current from all auxiliaries of the OTSDUW Plant and
Apparatus at the Transmission Interface Point and Connection Point shall be included. The fault infeed
shall be expressed as a fault current at the Transmission Interface Point and also at each Connection
Point.
Should actual data in respect of fault infeeds be unavailable at the time of the application for a CUSC Contract
or Embedded Development Agreement, a limited subset of the data, representing the maximum fault infeed
that may result from the OTSDUW Plant and Apparatus, shall be submitted. This data will, as a minimum,
represent the root mean square of the positive, negative and zero sequence components of the fault current
for both single phase and three phase solid faults at each Connection Point and Interface Point at the time
of fault application and 50ms following fault application. Actual data in respect of fault infeeds shall be
submitted to The Company as soon as it is available, in line with PC.A.1.2.
DATA DESCRIPTION UNITS F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. F.Yr. DATA to RTL
0 1 2 3 4 5 6 7
CUSC CUSC
(PC.A.2.5) Contract App.
Form
Name of OTSDUW Plant and
Apparatus
□ ■
Note 1. The pre-fault voltage provided above should represent the voltage within the range 0.95 to 1.05 that
gives the highest fault current
Prefault load 6hr 95% Line 580 132 95% Line 540 123 95% Line 465 106
exceeds line 20m Line 580 132 Line 540 123 Line 465 106
prefault
10m mva Line 580 132 mva Line 540 123 mva Line 465 106
continuous rating
5m 125 Line 580 132 116 Line 540 123 100 Line 465 106
3m Line 580 132 Line 540 123 Line 465 106
6hr 90% Line 580 132 90% Line 540 123 90% Line 465 106
20m Line 580 132 Line 540 123 Line 465 106
Short Term 10m mva Line 580 132 mva Line 540 123 mva Line 465 106
Overloads 5m 118 Line 580 132 110 Line 540 123 95 Line 465 106
3m Line 580 132 Line 540 123 Line 465 106
Limiting Item 6hr 84% Line 580 132 84% Line 540 123 84% Line 465 106
and permitted 20m Line 590 135 Line 545 125 Line 470 108
overload 10m mva Line 630 144 mva Line 580 133 mva Line 495 113
values 5m 110 Line 710 163 103 Line 655 149 89 Line 555 126
for different 3m Line 810 185 Line 740 170 Line 625 143
times and
pre-fault loads 6hr 75% Line 580 132 75% Line 540 123 75% Line 465 106
20m Line 595 136 Line 555 126 Line 475 109
10m mva Line 650 149 mva Line 600 137 mva Line 510 116
5m 99 Line 760 173 92 Line 695 159 79 Line 585 134
3m Line 885 203 Line 810 185 Line 685 156
6hr 60% Line 580 132 60% Line 540 123 60% Line 465 106
20m Line 605 138 Line 560 128 Line 480 110
10m mva Line 675 155 mva Line 620 142 mva Line 530 121
5m 79 Line 820 187 73 Line 750 172 63 Line 635 145
3m Line 985 226 Line 900 206 Line 755 173
6hr 30% Line 580 132 30% Line 540 123 30% Line 465 106
20m Line 615 141 Line 570 130 Line 490 112
10m mva Line 710 163 mva Line 655 150 mva Line 555 127
5m 39 Line 895 205 36 Line 820 187 31 Line 690 158
3m Line 1110 255 Line 1010 230 Line 845 193
6hr
20m
10m
5m
3m
6hr
20m
10m
5m
3m
Notes or
Restrictions
Detailed
Notes: 1. For information the equivalent STC Reference: STCP12-1: Part 3 - 2.6 Thermal Ratings
2. The values shown in the above table is example data.
Protection Schedules(PC.A.6.3)
Data schedules for the protection systems associated with each primary plant item including:
Protection, Intertrip Signalling & operating times
Intertripping and protection unstabilisation initiation
Synchronising facilities
Delayed Auto Reclose sequence schedules
A diagram of the scheme and an explanation of how the system will operate and what plant will be affected
by the scheme’s operation.
Substation: _______________________________
A diagram of the scheme and an explanation of how the system will operate and what plant will be effected
by the schemes operation.
Substation:________________________________
A diagram of the scheme and an explanation of how the system will operate and what plant will be effected
by the schemes operation
Substation: __________________________
Location Details:
Transmission Interface
Generator Interface
1. Substation Type:
2. Voltage Control: (short description of voltage control system. To include mention of modes i.e.
Voltage, manual etc. Plus control step increments i.e. 0.5% or 0.33kV)
3. Energisation Switching Information: (The standard energisation switching process from dead.)
4. Intertrip Systems:
5. Reactive Plant Outage: (A short explanation of any system re-configurations required to facilitate
the outage of any reactive plant which form part of the OTSDUW Plant and Apparatus equipment.
Also any generation restrictions required).
6. Harmonic Filter Outage: (An explanation as to any OTSDUW Plant and Apparatus reconfigurations
required to facilitate the outage and maintain the system within specified Harmonic limits, also any
generation restrictions required).
■
OTSDUW DC CONVERTER DATA Text □ SPD+
□ ■
If the busbars at the Interface Point or Section SPD
Connection Point are normally run in separate Number
sections identify the section to which the
OTSDUW DC Converter configuration is □ ■
connected MW SPD+
OTSDUW DC CONVERTER
TRANSFORMER
(PC.A.5.4.3.1)
MVA □ DPD II
Rated MVA
□
Winding arrangement kV DPD II
□
Nominal primary voltage kV DPD II
Nominal secondary (converter-side) voltage(s) □
Positive sequence reactance % on □ DPD II
Maximum tap MVA □ DPD II
Nominal tap % on DPD II
Minimum tap MVA
Positive sequence resistance % on □ DPD II
□
Maximum tap MVA DPD II
□
Nominal tap □
DPD II
Minimum tap % on □ DPD II
Zero phase sequence reactance MVA □ DPD II
Tap change range % on DPD II
Number of steps MVA
% on
MVA
% on
MVA
+% / -%
Diagram □ DPD II
Details of inverter mode control system,
in block diagram form showing transfer
functions of individual elements including
parameters (as applicable).
The following data need only be supplied by Users (be they a GB Code User or EU Code User) or Non-
CUSC Parties who wish to offer a Grid Forming Capability as provided for ECC.6.3.19.3. Where such a
Grid Forming Capability is provided then the following data items and models are to be supplied in respect
of each Grid Forming Plant.
In order to participate in the Grid Forming Capability market, User’s and Non-CUSC Parties are required to
provide data of their GBGF-I in accordance with Figures PC.A.5.8.1(a) and PC.A.5.8.1(b) Users and Non-
CUSC Parties in respect of Grid Forming Plants should indicate if the data is submitted on a unit or
aggregated basis. Table 1 below defines the notation used in Figure PC.5.8.1
Table 1
In order to participate in a Grid Forming Capability market, User’s and Non-CUSC Parties are also required
to provide the data of their GBGF-I in accordance with the Table below to The Company. The details and
arrangements for Users and Non-CUSC Parties participating in this market shall be published on The
Company’s Website.
Table 2
H = Installed MWs / Rated installed MVA
(equation 1)
He = (Active ROCOF Response Power at 1 Hz / s x System Frequency) / ( Installed MVA x 2 )
(equation 2)
CONTENTS
(This contents page does not form part of the Grid Code)
GC.2 SCOPE
GC.2.1 The General Conditions apply to all Users (including, for the avoidance of doubt, The
Company).
GC.6 MISCELLANEOUS
GC.6.1 Data and Notices
GC.6.1.1 Data and notices to be submitted either to The Company or to Users under the Grid Code
(other than data which is the subject of a specific requirement of the Grid Code as to the
manner of its delivery) shall be delivered in writing either by hand or sent by first-class pre-
paid post, or by facsimile transfer or by electronic mail to a specified address or addresses
previously supplied by The Company or the User (as the case may be) for the purposes of
submitting that data or those notices.
GC.6.1.2 References in the Grid Code to “in writing” or “written” include typewriting, printing, lithography,
and other modes of reproducing words in a legible and non-transitory form and in relation to
submission of data and notices includes electronic communications.
GC.6.1.3 Data delivered pursuant to paragraph GC.6.1.1, in the case of data being submitted to The
Company, shall be addressed to the Transmission Control Centre at the address notified
by The Company to each User prior to connection, or to such other Department within The
Company or address, as The Company may notify each User from time to time, and in the
case of notices to be submitted to Users, shall be addressed to the chief executive of the
addressee (or such other person as may be notified by the User in writing to The Company
from time to time) at its address(es) notified by each User to The Company in writing from
time to time for the submission of data and service of notices under the Grid Code (or failing
which to the registered or principal office of the addressee).
GC.6.1.4 All data items, where applicable, will be referenced to nominal voltage and Frequency unless
otherwise stated.
GC.12.3 The Company has obligations under the EMR Documents to inform EMR
Administrative Parties of certain data. The Company may pass on User data to an EMR
Administrative Party where The Company is required to do so under an EMR
Document.
GC.12.4 The Company may use User data for the purpose of carrying out its EMR Functions.
GC.16.1 In relation to the System Defence Plan, System Restoration Plan and Test Plan the
following provisions shall apply.
GC.16.2 If a User or The Company, wishes to raise a change to the System Defence Plan, System
Restoration Plan or Test Plan, they shall notify the Panel Secretary of the proposed change
to the System Defence Plan, System Restoration Plan or Test Plan.
In respect of the System Defence Plan the proposal shall not change the characteristics of
the service to be provided or the conditions for aggregation, as any such changes that relate
to the terms and conditions for Defence Service Providers; as set out in Article 4 paragraph
4 of Retained EU Law (Commission Regulation (EU) 2017/2196), as amended by Statutory
Instrument 533 (2019); is subject to a separate change procedure. That notification must
contain details of the proposal, including an explanation of why the proposal is being made.
Additional Requirements
(b) Electronic data communications facilities and other requirements applicable in all
Transmission Areas.
EDL Instruction Interface Valid Reason Codes Issue 5 20th Jan 2022
GC.A.2.7 Data:
Each Scottish User must provide, or enable a SPT or SHETL to provide, The Company, as
soon as reasonably practicable upon request, with all data which The Company needs in
order to implement, with effect from Go-Live, the GB Grid Code in relation to Scotland. This
data will include, without limitation, the data that a new User is required to submit to The
Company under CC.5.2. The Company is also entitled to receive data on Scottish Users
over SPT or SHETL’s SCADA links to the extent that The Company needs it for use in testing
and in order to implement, with effect from Go-Live, the GB Grid Code in relation to Scotland.
After Go-Live such data shall, notwithstanding GC.A.1.2, be treated as though it had been
provided to The Company under the enduring provisions of the GB Grid Code.
GC.A.2.8 Verification of Data etc:
The Company shall be entitled to request from a Scottish User (which shall comply as soon
as reasonably practicable with such a request) confirmation and verification of any information
(including data) that has been received by SPT or SHETL under an existing Grid Code and
passed on to The Company in respect of that Scottish User. After Go-Live such information
(including data) shall, notwithstanding GC.A.1.2, be treated as though provided to The
Company under the enduring provisions of the GB Grid Code.
GC.A.2.9 Grid Code Review Panel:
(a) The individuals whose names are notified to The Company by the Authority prior to Go-
Active as Panel Members (and Alternate Members, if applicable) are agreed by Users
(including Scottish Users) and The Company to constitute the Panel Members and
Alternate Members of the Grid Code Review Panel as at the first meeting of the Grid Code
Review Panel after Go-Active as if they had been appointed as Panel Members (and
Alternate Members) pursuant to the relevant provisions of the Constitution and Rules of the
Grid Code Review Panel incorporating amendments equivalent to the amendments to GC.4.2
and GC.4.3 designated by the Secretary of State in accordance with the provisions of the
Energy Act 2004 for the purposes of Condition C14 of The Company’s Transmission
Licence.
(b) The provisions of GC.4 of the GB Grid Code shall apply to, and in respect of, Scottish Users
from Go-Active.
GC.A.2.10 Interim GB SYS:
Where requirements are stated in, or in relation to, the GB Grid Code with reference to the
Seven Year Statement, they shall be read and construed as necessary as being with
reference to the Interim GB SYS.
GC.A.2.11 General Conditions:
The provisions of GC.4, GC.12 and GC.13.2 of the GB Grid Code shall apply to and be
complied with by Scottish Users in respect of this Appendix Part A to the General
Conditions.
GC.A.3 Cut-over
GC.A.3.1 It is anticipated that it will be appropriate for arrangements to be put in place for final transition
to BETTA in the period up to and following (for a temporary period) Go-Live, for the purposes
of:
PART B
GC.B.1 Introduction
GC.B.1.1 This Appendix Part B to the General Conditions deals with issues arising out of the transition
associated with the approval and implementation of Grid Code Modification Proposal
GC0112 (Modifications relating to the separation of System operations and Transmission
Owner roles).
GC.B.1.2 This Appendix Part B sets out the arrangements such that:
B.1.2.1 the Post GC0112 Grid Code reflects the Transfer of the System Operator
Role;
B.1.2.2 arrangements can be put in place prior to the SO Transfer Date to enable the
Issue 6 Revision 21 GC 04 March 2024
16 of 18
transition of the operations with NGET under the Pre GC0112 Grid Code to
operations with The Company under the Post GC0112 Grid Code; and
GC.B.1.3 The provisions of the Post GC0112 Grid Code shall be suspended until the SO Transfer
Date except for this Appendix Part B (and any related definitions within it) which will take
immediate effect on the Implementation Date for GC0112.
GC.B.1.4 In this (and solely for the purposes of this) Appendix Part B the following terms have the
following meaning:
B.1.4.1 the term “Grid Code Related Agreements/Documents" shall mean each or any of those
agreements or documents entered into under or envisaged by the Pre GC0112 Grid Code
prior to the SO Transfer Date which continue on and after the SO Transfer Date;
B.1.4.2 the term “GC0112" shall mean Grid Code Modification Proposal 0112 (Amendments
relating to the transfer of the system operator functions from NGET to NGESO);
B.1.4.3 the term “NGET” shall mean National Grid Electricity Transmission plc;
B.1.4.4 the term “NGESO” shall mean National Grid Electricity System Operator Limited;
B.1.4.5 the term “Post GC0112 Grid Code" means the version of the Grid Code as amended by
GC0112;
B.1.4.6 the term “Pre GC Grid Code” means the version of the Grid Code prior to amendment by
GC0112;
B.1.4.7 the term “SO Transfer Date” means the date on which NGET’s Transmission Licence is
transferred in part to NGESO to reflect the Transfer of the System Operator Role; and
B.1.4.8 the term “Transfer of the System Operator Role” means the the transfer, by means of the
transfer in part of NGET’s Transmission Licence, of the system operator role to NGESO.
GC.B.1.5 Without prejudice to any specific provision under this Appendix Part B as to the time within
which or the manner in which any party should perform its obligations under this Appendix
Part B, where a party is required to take any step or measure under this Appendix Part B,
such requirement shall be construed as including any obligation to:
B.1.5.2 do such associated or ancillary things as may be necessary to complete such step
or measure as quickly as reasonably practicable.
CONTENTS
(This contents page does not form part of the Grid Code)
PART A
GR.1 INTRODUCTION...........................................................................................................................2
PART B
GR.2 CODE ADMINISTRATOR .............................................................................................................2
GR.3 GRID CODE REVIEW PANEL ......................................................................................................2
GR.4 APPOINTMENT OF PANEL MEMBERS ......................................................................................4
GR.5 TERM OF OFFICE ........................................................................................................................5
GR.6 REMOVAL FROM OFFICE ..........................................................................................................5
GR.7 ALTERNATES..............................................................................................................................6
GR.8 MEETINGS ..................................................................................................................................7
GR.9 PROCEEDINGS AT MEETINGS .................................................................................................9
GR.10 QUORUM .....................................................................................................................................9
GR.11 VOTING .................................................................................................................................... 10
GR.12 PROTECTIONS FOR PANEL MEMBERS ............................................................................... 10
PART C
GR.13 GRID CODE MODIFICATION REGISTER ............................................................................... 11
GR.14 CHANGE CO-ORDINATION .................................................................................................... 11
GR.15 GRID CODE MODIFICATION PROPOSALS ........................................................................... 12
GR.16 SIGNIFICANT CODE REVIEW ................................................................................................. 15
GR.17 AUTHORITY LET MODIFICATIONS ........................................................................................ 17
GR.18 GRID CODE MODIFICATION PROPOSAL EVALUATION...................................................... 19
GR.19 PANEL PROCEEDINGS ........................................................................................................... 19
GR.20 WORKGROUPS ....................................................................................................................... 21
GR.21 THE CODE ADMINISTRATOR CONSULTATION ................................................................... 25
GR.22 GRID CODE MODIFICATION REPORTS ................................................................................ 27
GR.23 URGENT MODIFICATIONS ..................................................................................................... 28
GR.24 SELF-GOVERNANCE .............................................................................................................. 33
GR.25 IMPLEMENTATION .................................................................................................................. 36
GR.26 FAST TRACK ............................................................................................................................ 37
ANNEX GR.A ELECTION OF USERS' PANEL MEMBERS ................................................................ 39
ANNEX GR.B REGULATED SECTIONS MAPPING OF EGBL ARTICLE 18 TERMS AND CONDITIONS
FOR BALANCING SERVICE PROVIDERS AND BALANCING RESPONSIBLE PARTIES TO THE GRID
CODE…………………………………………………………………………………………………………… 40
Page i of 44
Issue 6 Revision 19 04 December 2023
PART A
GR.1 INTRODUCTION
GR.1.1 This section of the Grid Code sets out how the Grid Code is to be amended and the
procedures set out in this section, to the extent that they are dealt with in the Code
Administration Code of Practice, are consistent with the principles contained in the Code
Administration Code of Practice. Where inconsistencies or conflicts exist between the Grid
Code and the Code Administration Code of Practice, the Grid Code shall take precedence.
GR.1.2 There is a need to bring proposed amendments to the attention of Users and others, to
discuss such proposals and to report on them to the Authority and in furtherance of this,
the Governance Rules set out the functions of a Grid Code Review Panel and
Workgroups and for consultation by the Code Administrator.
GR.1.3 For the purpose of these Governance Rules the term “User” shall mean any person who
is under any obligation or granted any rights under the Grid Code.
PART B
GR.2.2 The Code Administrator shall in conjunction with other code administrators, maintain,
publish, review and (where appropriate) amend from time to time the Code Administration
Code of Practice approved by the Authority provided that any amendments to the Code
Administration Code of Practice proposed by the Code Administrator are approved by
the Grid Code Review Panel prior to being raised by the Code Administrator, and any
amendments to be made to the Code Administration Code of Practice are approved by
the Authority.
GR.3.1.1 The Grid Code Review Panel shall be the standing body to carry out the functions
referred to in GR.3.2
GR.3.1.2 The Grid Code Review Panel shall comprise the following members:
(a) the person appointed as the chairperson of the Grid Code Review Panel (the
“Panel Chairperson”) in accordance with GR.4.1, who shall (subject to GR.11.4) be
a voting member unless they are an employee of The Company in which case they
will be a non-voting member;
(b) the following members, appointed in accordance with GR.4.2 (a), who shall be non-
voting members:
Page 2 of 44
Issue 6 Revision 19 04 December 2023
(i) a representative of The Company appointed in accordance with
GR.4.2(c);
(ii) two representatives of the Network Operators;
(iii) a representative of Suppliers;
(iv) a representative of the Onshore Transmission Licensees;
(v) a representative of the Offshore Transmission Licensees;
(vi) four representatives of the Generators;
(vii) the Consumer Representative, appointed in accordance with GR.4.2(b);
(viii) the person appointed (if the Authority so decides) by the Authority in
accordance with GR.4.4;
(d) a secretary (the “Panel Secretary”), who shall be a person appointed and provided by
the Code Administrator to assist the Grid Code Review Panel and who shall be
responsible for the administration of the Grid Code Review Panel and Grid Code
Modification Proposals. The Panel Secretary will be a non-voting member of the
Grid Code Review Panel.
GR.3.2 Functions of the Grid Code Review Panel and the Code Administrator’s Role
(a) The Grid Code Review Panel shall have the functions assigned to it in these
Governance Rules.
(b) Without prejudice to GR.3.2(a) and to the further provisions of these Governance
Rules, the Grid Code Review Panel shall endeavour at all times to operate:
(d) Subject to notifying Users, the Code Administrator will, with the Authority’s
approval, apply to the Authority for a revision or revisions to the Implementation Date
where the Code Administrator becomes aware of any circumstances which is likely
to mean that the Implementation Date is unachievable, which shall include as a result
of a Legal Challenge, at any point following the approval of the Grid Code
Modification Proposal.
(e) In the event that the Authority’s decision to approve or not to approve a Grid Code
Modification Proposal is subject of Legal Challenge (and the party raising such
Legal Challenge has received from the relevant authority the necessary permission to
proceed) then the Code Administrator will, with the Authority’s approval, apply to
the Authority for a revision or revisions to the Proposed Implementation Date in the
Grid Code Modification Report in respect of such Grid Code Modification Proposal
as necessary such that if such Grid Code Modification Proposal were to be approved
following such Legal Challenge the Proposed Implementation Date would be
achievable.
Page 3 of 42
Issue 6 Revision 19 04 December 2023
(f) Prior to making any request to the Authority for any revision pursuant to
GR.3.2(d) (including where it is necessary as a result of a Legal Challenge) or
GR.3.2(e) the Code Administrator shall consult on the revision with Users and
such other person who may properly be considered to have an appropriate
interest in it in accordance with GR.21.2 and GR.21.8. The request to the
Authority shall contain copies of (and a summary of) all written representations
or objections made by consultees during the consultation period.
(i) shall act impartially and in accordance with the requirements of the Grid
Code; and
(ii) shall not be representative of, and shall act without undue regard to the
particular interests of the persons or body of persons by whom they were
appointed as Panel Member and any Related Person from time to time.
(b) Such a person shall not be appointed as a Panel Member or an Alternate Member
(as the case may be) unless they shall have first:
(i) confirmed in writing to the Code Administrator for the benefit of all Users that
they agree to act as a Panel Member or Alternate Member in accordance
with the Grid Code and acknowledges the requirements of GR.3.3 (a) and
GR.3.3(c);
(ii) where that person is employed, provided to the Panel Secretary a letter from
their employer agreeing that they may act as Panel Member or Alternate
Member, and that the requirement in GR.3.3(a)(ii) shall prevail over their
duties as an employee.
(c) A Panel Member or Alternate Member shall, at the time of appointment and upon any
change in such interests, disclose (in writing) to the Panel Secretary any such interests
(in relation to the Grid Code) as are referred to in GR.3.3(a)(ii).
(d) Upon a change in employment of a Panel Member or Alternate Member, they shall
so notify the Panel Secretary and shall endeavour to obtain from their new employer
and provide to the Panel Secretary a letter in the terms required in GR.3.3(b)(ii); and
they shall be removed from office if they do not do so within a period of sixty (60) days
after such change in employment.
(a) The Panel Chairperson shall be a person appointed (or re-appointed) by The
Company, having particular regard to the views of the Grid Code Review Panel, and
shall act independently of The Company.
(b) A person shall be appointed or re-appointed as the Panel Chairperson where the
Authority has approved such appointment or reappointment and The Company has
given notice to the Panel Secretary of such appointment, with effect from the date of
such notice or (if later) with effect from the date specified in such notice.
Page 4 of 42
Issue 6 Revision 19 04 December 2023
(b) The Citizens Advice or the Citizens Advice Scotland may appoint one person as a
Panel Member representing customers by giving notice of such appointment to the
Panel Secretary, and may remove and re-appoint by notice.
(c) The Company shall appoint the The Company representative referred to at
GR.3.1.2(c)(i) and shall give notice of the identity of such person to the Panel
Secretary, and may remove and re-appoint by notice to the Panel Secretary.
(d) The BSC Panel shall appoint a representative to be the member of the Grid Code
Review Panel referred to at GR.3.1.2(c) (iii) and shall give notice of the identity of such
person to the Panel Secretary, and may remove and re-appoint by notice to the Panel
Secretary.
GR.4.3. The Authority shall from time to time notify the Panel Secretary of the identity of the
Authority representative referred to at GR.3.1.2(b)(ii).
(a) If in the opinion of the Authority there is a class or category of person (whether or not
a User) who have interests in respect of the Grid Code but whose interests:
(i) are not reflected in the composition of Panel Members for the time being
appointed; but
(ii) would be so reflected if a particular person was appointed as an additional
Panel Member, then the Authority may at any time appoint (or re-appoint)
that person as a Panel Member by giving notice of such appointment to the
Panel Secretary but in no event shall the Authority be able to appoint more
than one person so that there could be more than one such Panel Member.
(b) A person appointed as a Panel Member pursuant to this GR.4.4 shall remain
appointed, subject to GR.5 and GR.6, notwithstanding that the conditions by virtue of
which they were appointed (for example that the interests they reflect are otherwise
reflected) may cease to be satisfied.
No person other than an individual shall be appointed a Panel Member or their alternate.
The term of office of a Panel Member, the Panel Chairperson and Alternate Members
shall be a period expiring on 31 December every second year. A Panel Member, the Panel
Chairperson and Alternate Member shall be eligible for reappointment on expiry of their
term of office.
GR.6.1 A person shall cease to hold office as the Panel Chairperson, a Panel Member or an
Alternate Member:
Page 5 of 42
Issue 6 Revision 19 04 December 2023
(v) die; or
(vi) are convicted on an indictable offence; or
(d) if the Grid Code Review Panel resolves (and the Authority does not veto such resolution
by notice in writing to the Panel Secretary within fifteen (15) Business Days) that they
should cease to hold office on grounds of their serious misconduct;
(e) if the Grid Code Review Panel resolves (and the Authority does not veto such resolution
by notice in writing to the Panel Secretary within fifteen (15) Business Days) that they
should cease to hold office due to a change in employer notwithstanding compliance with
GR.3.3(d).
GR.6.2 A Grid Code Review Panel resolution under GR.6.1(d) or (e) shall, notwithstanding any other
paragraph, require the vote in favour of at least all Panel Members less one (other than the
Panel Member or Alternate Member who is the subject of such resolution) and for these
purposes an abstention shall count as a vote cast in favour of the resolution. A copy of any such
resolution shall forthwith be sent to the Authority by the Panel Secretary.
GR.6.3 A person shall not qualify for appointment as a Panel Member or Alternate Member if at the
time of the proposed appointment they would be required by the above to cease to hold that
office.
GR.6.4 The Panel Secretary shall give prompt notice to The Company, all Panel Members, all Users
and the Authority of the appointment or re-appointment of any Panel Member or Alternate
Member or of any Panel Member or Alternate Member ceasing to hold office and publication
on the Website and (where relevant details are supplied to the Panel Secretary) despatch by
electronic mail shall fulfil this obligation.
GR.7 ALTERNATES
The Panel Chairperson shall preside at every meeting of the Grid Code Review Panel at
which they are present. If they are unable to be present at a meeting, they may appoint an
alternate (who shall be a senior employee of The Company) to act as the Panel Chairperson,
who may or may not be a Panel Member. If neither the Panel Chairperson nor their alternate
is present at the meeting within half an hour of the time appointed for holding the meeting, the
Panel Members present may appoint one of their number to be the chairperson of the meeting.
(a) At the same time that the parties entitled to vote in the relevant election appoint Elected
Panel Members under GR.4.2(a), they shall appoint the following Alternate Members:
(i) one alternate representative of the Suppliers;
(ii) one alternate representative of the Onshore Transmission Licensees;
(iii) one alternate representative of the Offshore Transmission Licensees; and
(iv) two alternate representatives of the Generators.
In the event that the election process fails to appoint an Alternate Member for any of the
Elected Panel Members, each Elected Panel Member shall be entitled (but not obligated)
to each at their own discretion nominate their own Alternate Member.
(b) Any Panel Member that is not an Elected Panel Member shall be entitled (but not
obligated) to each at their own discretion nominate their own Alternate Member.
(c) A Panel Member shall give notice to the Panel Secretary in the event it will be represented
by an Alternate Member for any one Grid Code Review Panel meeting.
(d) Where a Panel Member has nominated an Alternate Member in accordance with
GR.7.2(a) or (b), they may remove such Alternate Member, by giving notice of such
removal, and any nomination of a different Alternate Member, to the Panel Secretary. A
Page 6 of 42
Issue 6 Revision 19 04 December 2023
Panel Member may not choose as their Alternate Member: any party who is already
acting as an Alternate Member for another Panel Member; or another Panel Member.
(e) All information to be sent by the Panel Secretary to Panel Members pursuant to these
Governance Rules shall also be sent by the Panel Secretary to each Alternate Member by
electronic mail (where relevant details shall have been provided by each Alternate Member).
(b) The Panel Secretary shall promptly notify all Panel Members and Users of
appointment or removal by any Panel Member of any alternate and publication on the
Website and (where relevant details have been provided to the Panel Secretary)
despatch by electronic mail shall fulfil this obligation.
(a) Where the Panel Chairperson or a Panel Member has appointed an alternate:
(ii) the Alternate Member shall have the same voting rights the Panel Member
in whose place they are attending;
(iii) GR.8, GR.9, GR.10, GR.11 and GR.12 shall apply to the Alternate Member
as if they were the appointing Panel Member and a reference to a Panel
Member elsewhere in the Grid Code shall, unless the context otherwise
requires, include their duly appointed Alternate Member.
(iv) for the avoidance of doubt, the appointing Panel Member shall not enjoy any
of the rights transferred to the Alternate Member at any meeting at which, or
in relation to any matter on which, the Alternate Member acts on their behalf.
GR.8 MEETINGS
GR.8.1 Meetings of the Grid Code Review Panel shall be held at regular intervals and at least
every 2 months at such time and such place as the Grid Code Review Panel shall decide.
GR.8.2 A regular meeting of the Grid Code Review Panel may be cancelled if:
(a) the Panel Chairperson considers, having due regard to the lack of business in the
agenda, that there is insufficient business for the Grid Code Review Panel to conduct
and requests the Panel Secretary to cancel the meeting;
(b) the Panel Secretary notifies all Panel Members, not less than five (5) Business Days
Page 7 of 42
Issue 6 Revision 19 04 December 2023
before the date for which the meeting is to be convened, of the proposal to cancel the
meeting; and
(c) by the time three (3) Business Days before the date for which the meeting is or
is to be convened, no Panel Member has notified the Panel Secretary that they object
to such cancellation.
GR.8.3 If any Panel Member wishes, acting reasonably, to hold a special meeting (in addition to
regular meetings under GR.8.1) of the Grid Code Review Panel:
(a) they shall request the Panel Secretary to convene such a meeting and inform the
Panel Secretary of the matters to be discussed at the meeting;
(b) the Panel Secretary shall promptly convene the special meeting for a day as soon as
practicable but not less than five (5) Business Days after such request.
GR.8.4 Any meeting of the Grid Code Review Panel shall be convened by the Panel Secretary
by notice (which will be given by electronic mail if the relevant details are supplied to the
Panel Secretary) to each Panel Member (and to the Authority):
(a) setting out the date, time and place of the meeting and (unless the Grid Code Review
Panel has otherwise decided) given at least five (5) Business Days before the date of
the meeting;
(b) accompanied by an agenda of the matters for consideration at the meeting and any
supporting papers available to the Panel Secretary at the time the notice is given (and
the Panel Secretary shall circulate to Panel Members any late papers as and when
they are received by them).
GR.8.5 The Panel Secretary shall send a copy of the notice convening a meeting of the Grid Code
Review Panel, and the agenda and papers accompanying the notice, to the Panel
Members and Alternate Members, and publication on the Website and despatch by
electronic mail (if the relevant details are supplied to the Panel Secretary) shall fulfil this
obligation.
GR.8.6 Any Panel Member (or, at the Panel Member’s request, the Panel Secretary) may notify
matters for consideration at a meeting of the Grid Code Review Panel in addition to those
notified by the Panel Secretary under GR.8.4 by notice to all Panel Members and persons
entitled to receive notice under GR.8.5, not less than three (3) Business Days before the
date of the meeting.
GR.8.7 The proceedings of a meeting of the Grid Code Review Panel shall not be invalidated by
the accidental omission to give or send notice of the meeting or a copy thereof or any of
the accompanying agenda or papers to, or failure to receive the same by, any person
entitled to receive such notice, copy, agenda or paper.
GR.8.8 A meeting of the Grid Code Review Panel may consist of a conference between Panel
Members who are not all in one place but who are able (by telephone or otherwise) to
speak to each of the others and to be heard by each of the others simultaneously.
GR.8.9 With the consent of all Panel Members (whether obtained before, at or after any such
meeting) the requirements of this GR.8 as to the manner in and notice on which a meeting
of the Grid Code Review Panel is convened may be waived or modified provided that no
meeting of the Grid Code Review Panel shall be held unless notice of the meeting and its
agenda has been sent to the persons entitled to receive the same under GR.8.5 at least 24
hours before the time of the meeting.
GR.8.10 Subject to GR.8.11, no matter shall be resolved at a meeting of the Grid Code Review
Panel unless such matter was contained in the agenda accompanying the Panel
Secretary’s notice under GR.8.4 or was notified in accordance with GR.8.6.
GR.8.11 Where:
Page 8 of 42
Issue 6 Revision 19 04 December 2023
(a) any matter (not contained in the agenda and not notified pursuant to GR.8.4 and
GR.8.6) is put before a meeting of the Grid Code Review Panel, and
(b) in the opinion of the Grid Code Review Panel it is necessary (in view of the urgency of the
matter) that the Grid Code Review Panel resolve upon such matter at the meeting, the
Grid Code Review Panel may so resolve upon such matter, and the Grid Code Review
Panel shall also determine at such meeting whether the decision of the Grid Code Review
Panel in relation to such matter should stand until the following meeting of the Grid Code
Review Panel, in which case (at such following meeting) the decision shall be reviewed
and confirmed or (but not with effect earlier than that meeting, and only so far as the
consequences of such revocation do not make implementation of the Grid Code or
compliance by Users with it impracticable) revoked.
GR.9.1 Subject as provided in the Grid Code, the Grid Code Review Panel may regulate the
conduct of and adjourn and reconvene its meetings as it sees fit.
GR.9.2 Meetings of the Grid Code Review Panel shall be open to attendance by a representative
of any User (including any Authorised Electricity Operator; The Company or a
Materially Affected Party), the Citizens Advice or the Citizens Advice Scotland and
any person invited by the Panel Chairperson and/or any other Panel Member.
GR.9.3 The Panel Chairperson and any other Panel Member may invite any person invited by
them under GR.9.2, and/or any attending representative of a User, to speak at the meeting
(but such person shall have no vote).
GR.9.4 As soon as practicable after each meeting of the Grid Code Review Panel, the Panel
Secretary shall prepare and send (by electronic mail or otherwise) to Panel Members the
minutes of such meeting, which shall be (subject to GR.9.5) approved (or amended and
approved) at the next meeting of the Grid Code Review Panel after they were so sent,
and when approved (excluding any matter which the Grid Code Review Panel decided
was not appropriate for such publication) shall be placed on the Website.
GR.9.5 If, following the circulation of minutes (as referred to in GR.9.4), the meeting of the Grid
Code Review Panel at which they were to be approved is cancelled pursuant to GR.8.2,
such minutes (including any proposed changes thereto which have already been received)
shall be recirculated with the notification of the cancellation of the meeting of the Grid Code
Review Panel. Panel Members shall confirm their approval of such minutes to the Panel
Secretary (by electronic mail) no later than five (5) Business Days following such minutes
being re-circulated. If no suggested amendments are received within such five (5)
Business Days period, the minutes will be deemed to have been approved. If the minutes
are approved, or deemed to have been approved, (excluding any matter which the Grid
Code Review Panel decided was not appropriate for such publication) they shall be placed
on the Website. If suggested amendments are received within such five (5) Business
Days period, the minutes shall remain unapproved and the process for approval (or
amendment and approval) of such minutes at the next meeting of the Grid Code Review
Panel, as described in GR.9.4, shall be followed.
GR.10 QUORUM
GR.10.1 No business shall be transacted at any meeting of the Grid Code Review Panel unless a
quorum is present throughout the meeting.
GR.10.2 Subject to GR.10.4, a quorum shall be 6 Panel Members who have a vote present (subject
to GR.8.8) in person or by their alternates, of whom at least one shall be appointed by The
Company. Where a Panel Member is represented by an Alternate Member, that
Alternate Member cannot represent any other Panel Member at the same meeting.
GR.10.3 If within half an hour after the time for which the meeting of the Grid Code Review Panel
has been convened a quorum is not present (and provided the Panel Secretary has not
been notified by Panel Members that they have been delayed and are expected to arrive
within a reasonable time):
Page 9 of 42
Issue 6 Revision 19 04 December 2023
(a) the meeting shall be adjourned to the same day in the following week (or, if that day is
not a Business Day the next Business Day following such day) at the same time;
(b) the Panel Secretary shall give notice of the adjourned meeting as far as practicable in
accordance with GR.8.
GR.10.4 If at the adjourned meeting there is not a quorum present within half an hour after the time
for which the meeting was convened, those present shall be a quorum.
GR.11 VOTING
GR.11.1 At any meeting of the Grid Code Review Panel any matter to be decided which shall
include the Grid Code Review Panel Recommendation Vote shall be put to a vote of
those Panel Members entitled to vote in accordance with these Governance Rules upon
the request of the Panel Chairperson or any Panel Member.
GR.11.2 Subject to GR.11.4, in deciding any matter at any meeting of the Grid Code Review Panel
each Panel Member other than the Panel Chairperson shall cast one vote.
GR.11.3 Except as otherwise expressly provided in the Grid Code, and in particular GR.6.2, any
matter to be decided at any meeting of the Grid Code Review Panel shall be decided by
simple majority of the votes cast at the meeting (an abstention shall not be counted as a
cast vote).
GR11.4 The Panel Chairperson shall not cast a vote as a Panel Member but shall have a casting
vote on any matter where votes are otherwise cast equally in favour of and against the
relevant motion. Where the vote is in respect of a Grid Code Modification Proposal the
Panel Chairperson may only use such casting vote to vote against such Grid Code
Modification Proposal. The Panel Chairperson will have a free vote in respect of any
other vote. Where any person other than the actual Panel Chairperson is acting as
chairperson they shall not have a casting vote.
GR.11.5 Any resolution in writing signed by or on behalf of all Panel Members shall be valid and
effectual as if it had been passed at a duly convened and quorate meeting of the Grid Code
Review Panel. Such a resolution may consist of several instruments in like form signed by
or on behalf of one or more Panel Members.
GR.12.1 Subject to GR.12.2 all CUSC Parties shall jointly and severally indemnify and keep
indemnified each Panel Member, the Panel Secretary and each member of a Workgroup
(“Indemnified Persons”) in respect of all costs (including legal costs), expenses, damages
and other liabilities properly incurred or suffered by such Indemnified Persons when acting
in or in connection with their office under the Grid Code, or in what they in good faith
believe to be the proper exercise and discharge of the powers, duties, functions and
discretions of that office in accordance with the Grid Code, and all claims, demands and
proceedings in connection therewith other than any such costs, expenses, damages or
other liabilities incurred or suffered as a result of the wilful default or bad faith of such
Indemnified Person.
GR.12.2 The indemnity provided in GR.12.1 shall not extend to costs and expenses incurred in the
ordinary conduct of being a Panel Member or Panel Secretary, or member of a
Workgroup including, without limitation, accommodation costs and travel costs or any
remuneration for their services to the Grid Code Review Panel or Workgroup.
GR.12.3 The Users agree that no Indemnified Person shall be liable for anything done when acting
properly in or in connection with their office under the Grid Code, or anything done in what
they in good faith believe to be the proper exercise and discharge of the powers, duties,
functions and discretions of that office in accordance with the Grid Code. Each CUSC
Party hereby irrevocably and unconditionally waives any such liability of any Indemnified
Person and any rights, remedies and claims against any Indemnified Person in respect
thereof.
Page 10 of 42
Issue 6 Revision 19 04 December 2023
GR.12.4 Without prejudice to GR.12.2, nothing in GR.12.3 shall exclude or limit the liability of an
Indemnified Person for death or personal injury resulting from the negligence of such
Indemnified Person.
PART C
GR.13.1 The Code Administrator shall establish and maintain a register (“Grid Code Modification
Register”) in a form as may be agreed with the Authority from time to time, which shall
record the matters set out in GR.13.3.
GR.13.2 The purpose of the Grid Code Modification Register shall be to assist the Grid Code
Review Panel and to enable the Grid Code Review Panel, Users and any other persons
who may be interested to be reasonably informed of the progress of Grid Code
Modification Proposals and Approved Modifications from time to time.
GR.13.3 The Grid Code Modification Register shall record in respect of current outstanding Grid
Code Review Panel business:
(a) details of each Grid Code Modification Proposal (including the name of the
Proposer, the date of the Grid Code Modification Proposal and a brief description
of the Grid Code Modification Proposal);
(c) the current status and progress of each Grid Code Modification Proposal, if
appropriate the anticipated date for reporting to the Authority in respect thereof, and
whether it has been withdrawn, rejected or implemented for a period of three (3) months
after such withdrawal, rejection or implementation or such longer period as the
Authority may determine;
(d) the current status and progress of each Approved Modification, each Approved Grid
Code Self-Governance Proposal, and each Approved Fast Track Proposal; and
(e) such other matters as the Grid Code Review Panel may consider appropriate from
time to time to achieve the purpose of GR.13.2.
GR.13.4 The Grid Code Modification Register (as updated from time to time and indicating the
revisions since the previous issue) shall be published on the Website or (in the absence,
for whatever reason, of the Website) in such other manner and with such frequency (being
not less than once per month) as the Code Administrator may decide in order to bring it
to the attention of the Grid Code Review Panel, Users and other persons who may be
interested.
GR.14.1 The Code Administrator shall establish (and, where appropriate, revise from time to time)
joint working arrangements for change co-ordination with each Core Industry Document
Owner and with the STC Modification Panel to facilitate the identification, co-ordination,
making and implementation of change to Core Industry Documents and the STC
consequent on a Grid Code Modification Proposal, including, but not limited to, changes
that are appropriate in order to avoid conflict or inconsistency as between the Grid Code
and any Core Industry Document and the STC, in a full and timely manner.
GR.14.2 The working arrangements referred to in GR.14.1 shall be such as to enable the
consideration, development and evaluation of Grid Code Modification Proposals, and
the implementation of Approved Modifications, to proceed in a full and timely manner
and enable changes to Core Industry Documents and the STC consequent on an
amendment to be made and given effect wherever possible (subject to any necessary
consent of the Authority) at the same time as such Grid Code Modification Proposal is
made and given effect.
Page 11 of 42
Issue 6 Revision 19 04 December 2023
GR.15 GRID CODE MODIFICATION PROPOSALS
(a) by any User; any Authorised Electricity Operator liable to be materially affected by
such a proposal; the Citizens Advice or the Citizens Advice Scotland;
GR.15.2 A Standard Modification shall follow the procedure set out in GR.18 to GR.22.
GR.15.3 A Grid Code Modification Proposal shall be submitted in writing to the Panel Secretary and,
subject to the provisions of GR.15.4 below, shall contain the following information in relation to
such proposal:
(b) the name of the representative of the Proposer who shall represent the Proposer in
person for the purposes of this GR.15;
(c) a description (in reasonable but not excessive detail) of the issue or defect which the
proposed modification seeks to address;
(d) a description (in reasonable but not excessive detail) of the proposed modification and
of its nature and purpose;
(e) where possible, an indication of those parts of the Grid Code which would require
amendment in order to give effect to (and/or would otherwise be affected by) the
proposed modification and an indication of the nature of those amendments or effects;
(f) the reasons why the Proposer believes that the proposed modification would better
facilitate achievement of the Grid Code Objectives as compared with the current
version of the Grid Code together with background information in support thereof;
(g) the reasoned opinion of the Proposer as to why the proposed modification should not
fall within a current Significant Code Review, whether the proposed modification
should be treated as a Self-Governance Modification or whether the proposed
modification fails to meet the Self- Governance Criteria and as a result should
proceed along the Standard Modification route;
(h) the reasoned opinion of the Proposer as to whether that impact is likely to be material
and if so an assessment of the quantifiable impact of the proposed modification on
greenhouse gas emissions, to be conducted in accordance with such current guidance
on the treatment of carbon costs and evaluation of the greenhouse gas emissions as
may be issued by the Authority from time to time;
(i) where possible, an indication of the impact of the proposed modification on Core
Industry Documents and the STC;
(j) where possible, an indication of the impact of the proposed modification on relevant
computer systems and processes used by Users.
Page 12 of 42
Issue 6 Revision 19 04 December 2023
(k) whether or not (and to the extent) that in the proposer’s view the Grid Code
Modification Proposal constitutes an amendment to the Regulated Sections of the
Grid Code.
GR.15.4 The Proposer of a Grid Code Fast Track Proposal is not required to provide the items
referenced at GR.15.3 (f) – (j) inclusive, unless either:
(a) the Grid Code Review Panel has, pursuant to GR.26.5 or GR.26.6, not agreed
unanimously that the Grid Code Fast Track Proposal meets the Fast Track Criteria,
or has not unanimously approved the Grid Code Fast Track Proposal; or
(b) there has been an objection to the Approved Fast Track Proposal pursuant to
GR.26.12, whereupon the Proposer shall be entitled to provide the additional
information required pursuant to GR.15.3 for a Grid Code Modification Proposal
within 28 days of the Panel Secretary’s request. Where the Proposer fails to provide
the additional information in accordance with such timescales, the Panel Secretary
may reject such proposal in accordance with GR.15.5.
GR.15.5 If a proposal fails in any material respect to provide the information in GR.15.3 (excluding (e), (i)
and (j) thereof), the Panel Secretary may reject such proposal provided that:
(a) the Panel Secretary shall furnish the Proposer with the reasons for such rejection;
(b) the Panel Secretary shall report such rejection to the Grid Code Review Panel at
the next Grid Code Review Panel meeting, with details of the reasons;
(c) if the Grid Code Review Panel decides or the Authority directs to reverse the Panel
Secretary’s decision to refuse the submission, the Panel Secretary shall notify the
Proposer accordingly and the proposal shall be dealt with in accordance with these
Governance Rules;
(d) nothing in these Governance Rules shall prevent a Proposer from submitting a
revised proposal in compliance with the requirements of GR.15.3 in respect of the same
subject-matter.
GR.15.6 Without prejudice to the development of a Workgroup Alternative Grid Code Modification(s)
pursuant to GR.20.13 and GR.20.18, the Grid Code Review Panel shall direct in the case of (a),
and may direct in the case of (b), the Panel Secretary to reject a proposal pursuant to GR.15,
other than a proposal submitted by The Company pursuant to a direction issued by the Authority
following a Significant Code Review in accordance with GR.16.4, or an Authority Led
modification, if and to the extent that such proposal has, in the opinion of the Grid Code Review
Panel, substantially the same effect as:
(b) a Rejected Grid Code Modification Proposal, where such proposal is made at any
time within two (2) months after the decision of the Authority not to direct The
Company to modify the Grid Code pursuant to the Transmission Licence in the
manner set out in such Grid Code Modification Proposal, and the Panel Secretary
shall notify the Proposer accordingly.
GR.15.7 Promptly upon receipt of a Grid Code Modification Proposal, the Panel Secretary
shall:
(a) allocate a unique reference number to the Grid Code Modification Proposal;
(b) enter details of the Grid Code Modification Proposal on the Grid Code
Modification Register;
(c) reserve the right to modify the title or summary of the Grid Code Modification
Proposal to better reflect the content or intent of the proposal. If such changes are
made these shall be agreed by the Proposer, or where this cannot be achieved by the
Page 13 of 42
Issue 6 Revision 19 04 December 2023
Grid Code Review Panel at their next meeting; and
(d) note whether in the proposer’s view the Grid Code Modification Proposal
constitutes an amendment to the Regulated Sections of the Grid Code.
GR.15.8 Subject to GR.8.6 and GR.26, where the Grid Code Modification Proposal is received
more than ten (10) Business Days prior to the next Grid Code Review Panel meeting,
the Panel Secretary shall place the Grid Code Modification Proposal on the agenda of
the next Grid Code Review Panel meeting and otherwise shall place it on the agenda of
the next succeeding Grid Code Review Panel meeting.
GR.15.9 It shall be a condition to the right to make a proposal to modify the Grid Code under this
GR.15 that the Proposer:
(a) grants a non-exclusive royalty free licence to all Users who request the same covering
all present and future rights, IPRs and moral rights it may have in such proposal (as
regards use or application in Great Britain); and
(b) warrants that, to the best of its knowledge, information and belief, no other person has
asserted to the Proposer that such person has any IPRs or normal rights or rights of
confidence in such proposal, and, in making a proposal, a Proposer which is a Grid
Code Party shall be deemed to have granted the licence and given the warranty in (a)
and (b) above.
(c) The provisions of this GR.15.9 shall apply to any WG Consultation Alternative
Request, and also to a Relevant Party supporting a Grid Code Modification
Proposal in place of the original Proposer in accordance with GR.15.10 (a) for these
purposes the term Proposer shall include any such Relevant Party or a person
making such a WG Consultation Alternative Request.
GR.15.10 Subject to GR.16.1, which deals with the withdrawal of a Grid Code Modification
Proposal made pursuant to a direction following a Significant Code Review, a Proposer
may withdraw their support for a Standard Modification by notice to the Panel Secretary
at any time prior to the Grid Code Review Panel Recommendation Vote undertaken in
relation to that Standard Modification pursuant to GR.22.4, and a Proposer may withdraw
their support for a Grid Code Modification Proposal that meets the Self-Governance
Criteria by notice to the Panel Secretary at any time prior to the Grid Code Review Panel
Self-Governance Vote undertaken in relation to that Grid Code Modification Proposal
pursuant to GR.24.9, and a Proposer may withdraw their support for a Grid Code Fast
Track Proposal by notice to the Panel Secretary at any time prior to the Panel’s vote on
whether to approve the Grid Code Fast Track Proposal pursuant to GR.26 in which case
the Panel Secretary shall forthwith:
(a) notify those parties specified in GR.15.1 as relevant in relation to the Grid Code
Modification Proposal in question (a “Relevant Party”) that they have been notified
of the withdrawal of support by the Proposer by publication on the Website and (where
relevant details are supplied) by electronic mail. A Relevant Party may within five (5)
Business Days notify the Panel Secretary that it is prepared to support the Grid Code
Modification Proposal in place of the original Proposer. If such notice is received,
the name of such Relevant Party shall replace that of the original Proposer as the
Proposer, and the Grid Code Modification Proposal shall continue. If more than one
notice is received, the first received shall be utilised;
(b) if no notice of support is received under (a), the matter shall be discussed at the next
Grid Code Review Panel meeting. If the Grid Code Review Panel so agrees, it may
notify Relevant Parties that the Grid Code Modification Proposal is to be withdrawn,
and a further period of five (5) Business Days shall be given for support to be indicated
by way of notice;
(c) if no notice of support is received under (a) or (b), the Grid Code Modification
Proposal shall be marked as withdrawn on the Grid Code Modification Register;
Code Administrator as Critical Friend.
Page 14 of 42
Issue 6 Revision 19 04 December 2023
GR.15.11 The Code Administrator shall provide assistance insofar as is reasonably practicable and
on reasonable request to parties with an interest in the Grid Code Modification Proposal
process that request it in relation to the Grid Code, as provided for in the Code
Administration Code of Practice, including, but not limited to, assistance with:
(c) Their involvement in, and representation during, the Grid Code Modification
Proposal process (including but not limited to Grid Code Review Panel, and/or
Workgroup meetings) as required or as described in the Code Administration Code
of Practice;
(d) Helping the Proposer and Workgroup by producing draft legal text once a clear
solution has been developed to support the discussion and understanding of a Grid
Code Modification Proposal; and
GR.16.1 If any party specified under GR.15.1 (other than the Authority) makes a Grid Code
Modification Proposal during a Significant Code Review Phase, unless exempted by
the Authority or unless GR.16.4(b) applies, the Grid Code Review Panel shall assess
whether the Grid Code Modification Proposal falls within the scope of a Significant
Code Review and the applicability of the exceptions set out in GR.16.4 and shall notify the
Authority of its assessment, its reasons for that assessment and any representations
received in relation to it as soon as practicable.
GR.16.2 The Grid Code Review Panel shall proceed with the Grid Code Modification Proposal
made during a Significant Code Review Phase in accordance with GR.18
(notwithstanding any consultation undertaken pursuant to GR.16.5 and its outcome),
unless directed otherwise by the Authority pursuant to GR.16.3.
GR.16.3 Subject to GR.16.4, the Authority may at any time direct that a Grid Code Modification
Proposal made during a Significant Code Review Phase falls within the scope of a
Significant Code Review and must not be made during the Significant Code Review
Phase. If so directed, the Grid Code Review Panel will not proceed with that Grid Code
Modification Proposal, and the Proposer shall decide whether the Grid Code
Modification Proposal shall be withdrawn or suspended until the end of the Significant
Code Review Phase. If the Proposer fails to indicate its decision whether to withdraw or
suspend the Grid Code Modification Proposal within twenty-eight (28) days of the
Authority’s direction, it shall be deemed to be suspended. If the Grid Code Modification
Proposal is suspended, it shall be open to the Proposer at the end of the Significant
Code Review Phase to indicate to the Grid Code Review Panel that it wishes that Grid
Code Modification Proposal to proceed, and it shall be considered and taken forward in
the manner decided upon by the Grid Code Review Panel at the next meeting, and it is
open to the Grid Code Review Panel to take into account any work previously undertaken
in respect of that Grid Code Modification Proposal. If the Proposer makes no indication
to the Grid Code Review Panel within twenty-eight (28) days of the end of the Significant
Code Review Phase as to whether or not it wishes the Grid Code Modification Proposal
to proceed, it shall be deemed to be withdrawn.
GR.16.4 A Grid Code Modification Proposal that falls within the scope of a Significant Code
Review may be made where:
(a) the Authority so determines, having taken into account (among other things)
the urgency of the subject matter of the Grid Code Modification Proposal;
or
Page 15 of 42
Issue 6 Revision 19 04 December 2023
(b) the Grid Code Modification Proposal is made by The Company pursuant
to a direction from the Authority; or
GR.16.5 Where a direction under GR.16.3 has not been issued, GR.16.4 does not apply
and the Grid Code Review Panel considers that a Grid Code Modification
Proposal made during a Significant Code Review Phase falls within the scope
of a Significant Code Review, the Grid Code Review Panel may consult on its
suitability as part of the Standard Modification route set out in GR.19, GR.20,
GR.21 and GR.22.
GR.16.6 If, within twenty eight (28) days after the Authority has published its Significant
Code Review conclusions:
(a) the Authority issues directions to The Company, including directions to The
Company to make a Grid Code Modification Proposal, The Company
shall comply with those directions and The Company and all Users shall
treat the Significant Code Review Phase as ended on the date on which
The Company makes a Grid Code Modification Proposal in accordance
with the Authority’s directions;
(b) the Authority issues to the The Company a statement that no directions
under sub-paragraph (a) will be issued in relation to a Grid Code
Modification Proposal, The Company and all Users shall treat the
Significant Code Review Phase as ended on the date of such statement;
(c) the Authority raises a Grid Code Modification Proposal in accordance with
GR.15.1(c) or GR.17 The Company and all Users shall treat the Significant
Code Review Phase as ended;
(d) the Authority issues a statement that it will continue work on the Significant
Code Review, The Company and all Users shall treat the Significant Code
Review Phase as continuing until it is brought to an end in accordance with
GR.16.7;
(e) neither directions under sub-paragraph (a) nor a statement under sub-
paragraphs (b) or (d) have been issued, nor a Grid Code Modification
Proposal under sub-paragraph (c) has been made, the Significant Code
Review Phase will be deemed to have ended.The Authority's published
conclusions and directions to The Company will not fetter any voting rights
of the Panel Members or the procedures informing the Grid Code
Modification Report.
(a) the Authority issues a statement that the Significant Code Review Phase
has ended;
GR.16.8 Any Grid Code Modification Proposal in respect of a Significant Code Review
that is not an Authority-Led Modification raised pursuant to GR.17 shall be
treated as a Standard Modification and shall proceed through the process for
Standard Modifications set out in GR.18, GR.19, GR.20, GR.21 and GR.22.
GR.16.9 The Company may not, without the prior consent of the Authority, withdraw a
Grid Code Modification Proposal made pursuant to a direction issued by the
Authority pursuant to GR.16.4(b)).
GR.16.10 Where a Grid Code Modification Proposal has been raised in accordance with
GR.16.4(b) or GR.15.1(a), or by the Authority under GR.15.1(c) and it is in
respect of a Significant Code Review, the Authority may issue a direction (a
“backstop direction”), which requires such proposal(s) and any alternatives to be
withdrawn and which causes the Significant Code Review Phase to
recommence.
GR.17.2 An Authority-led Modification may be submitted where the Significant Code Review
Phase is extended by a statement issued by the Authority as described in GR.16.6(d), or
where a direction is issued under GR.16.10.
GR.17.3 The Authority may submit its proposed Authority-Led Modification to the Code
Administrator, together with such supplemental information as the Authority considers
appropriate.
GR.17.4 Upon receipt of the Authority’s proposal under GR.17.3, the Code Administrator shall
prepare a written report on the proposal (the "Authority-Led Modification Report").
Where the Code Administrator does not reasonably believe the information provided by
the Authority under 17.3 to be sufficient for it to prepare an Authority-Led Modification
Report the Code Administrator will notify the Authority as soon as reasonably practical.
The Authority-Led Modification Report must be consistent with the information provided
by the Authority under GR.17.3, and shall:
(b) set out the legal text of the proposed Authority-Led Modification;
(d) include a summary of the views (including any recommendations) from parties
consulted in respect of the proposed Authority-Led Modification;
(e) include an analysis of whether (and, if so, to what extent) the proposed Authority-Led
Modification would better facilitate achievement of the Grid Code Objective(s) with
a detailed explanation of the Authority’s reasons for its assessment, including, where
the impact is likely to be material, an assessment of the quantifiable impact of the
proposed Authority-Led Modification on greenhouse gas emissions, to be conducted
in accordance with such current guidance on the treatment of carbon costs and
evaluation of the greenhouse gas emissions as may be issued by the Authority from
time to time, and providing a detailed explanation of the Authority’s reasons for that
assessment;
Page 17 of 42
Issue 6 Revision 19 04 December 2023
(f) specify the proposed implementation timetable (including the Proposed
Implementation Date);
(i) the impact of the proposed Authority-Led Modification on the Core Industry
Documents and the STC;
(ii) the changes which would be required to the Core Industry Documents and
the STC in order to give effect to the proposed Authority-Led Modification;
(iii) the mechanism and likely timescale for the making of the changes referred to
in (ii);
(iv) the changes and/or developments which would be required to central computer
systems and, if practicable, processes used in connection with the operation of
arrangements established under the Core Industry Documents and the STC;
(v) the mechanism and likely timescale for the making of the changes referred to
in (iv);
(vi) an estimate of the costs associated with making and delivering the changes
referred to in (ii) and (iv), such costs are expected to relate to: for (ii) the costs
of amending the Core Industry Document(s) and STC and for (iv) the costs
of changes to computer systems and possibly processes which are established
for the operation of the Core Industry Documents and the STC, together with
an analysis and a summary of representations in relation to such matters,
including any made by Small Participants, the Citizens Advice and the
Citizens Advice Scotland;
(h) contain, to the extent such information is available to the Code Administrator, an
assessment of the impact of the proposed Authority-Led Modification on Users in
general (or classes of Users), including the changes which are likely to be required to
their internal systems and processes and an estimate of the development, capital and
operating costs associated with implementing the changes to the Grid Code and to
Core Industry Documents and the STC;
(i) include copies of (and a summary of) all written representations or objections made by
parties consulted by the Authority in respect of the proposed Authority-Led
Modification and subsequently maintained; and
(j) have appended a copy of any impact assessment prepared by Core Industry
Document Owners and the STC committee and the views and comments of the Code
Administrator in respect thereof.
GR.17.5 Where the Authority-Led Modification Report is received more than ten (10) Business
Days prior to the next Grid Code Review Panel meeting, the Panel Secretary shall place
the proposed Authority-Led Modification on the agenda of the next Grid Code Review
Panel meeting and otherwise shall place it on the agenda of the next succeeding Grid
Code Review Panel meeting.
GR.17.6 In the case of Authority-Led Modifications GR.22 shall apply, save for GR.22.1 and
GR.22.2 and the Authority-Led Modification Report shall be used as the draft Grid Code
Modification Report.
GR.17.7 Where an Authority-Led Modification has been approved in accordance with Section
GR.22, GR.25 (Implementation) shall apply.
GR.18.1 This GR.18 is subject to the Urgent Modification procedures set out in GR.23 and the
Significant Code Review procedures set out in GR.16.
GR.18.2 A Grid Code Modification Proposal shall, subject to GR.15.8, be discussed by the Grid
Code Review Panel at the next following Grid Code Review Panel meeting convened.
Page 18 of 42
Issue 6 Revision 19 04 December 2023
GR.18.3 The Proposer’s representative shall attend such Grid Code Review Panel meeting and
the Grid Code Review Panel may invite the Proposer’s representative to present their
Grid Code Modification Proposal to the Grid Code Review Panel.
GR.18.4 The Grid Code Review Panel shall evaluate each Grid Code Modification Proposal
against the Self-Governance Criteria.
GR.18.5 The Grid Code Review Panel shall follow the procedure set out in GR.24 in respect of any
Modification that the Grid Code Review Panel considers meets the Self-Governance
Criteria unless the Authority makes a direction in accordance with GR.24.2 and in such a
case that Modification shall be a Standard Modification and shall follow the procedure
set out in GR.19, GR.20, GR.21 and GR.22.
GR.18.6 Unless the Authority makes a direction in accordance with GR.24.4, a Modification that
the Grid Code Review Panel considers does not meet the Self-Governance Criteria shall
be a Standard Modification and shall follow the procedure set out in GR.19, GR.20,
GR.21 and GR.22.
GR.18.7 The Grid Code Review Panel shall evaluate each Grid Code Fast Track Proposal
against the Fast Track Criteria.
GR.18.8 The Grid Code Review Panel shall follow the procedure set out in GR.26 in respect of any
Grid Code Fast Track Proposal. The provisions of GR.19 to GR.24 shall not apply to a
Grid Code Fast Track Proposal.
GR.18.9 The Grid Code Review Panel shall evaluate each Grid Code Modification Proposal
and determine whether the Grid Code Modification Proposal constitutes an
amendment to the Regulated Sections of the Grid Code and, if a change to the areas
set out in Table 1 of the GR.B annex which details the Regulated Sections, its expected
impact on the objectives of Retained EU Law (Commission Regulation (EU) 2017/2195)
(and in the event of disagreement The Company’s view shall prevail).
GR.19.1
(a) The Code Administrator and the Grid Code Review Panel shall together establish a
timetable to apply for the Grid Code Modification Proposal process. That timetable
must comply with any direction(s) issued by the Authority setting and/or amending a
timetable in relation to a Grid Code Modification Proposal that is in the respect of a
Significant Code Review.
(b) The Grid Code Review Panel shall establish the part of the timetable for the
consideration by the Grid Code Review Panel and by a Workgroup (if any) which
shall be no longer than six months unless in any case the particular circumstances of
the Grid Code Modification Proposal (taking due account of its complexity,
importance and urgency) justify an extension of such timetable, and provided the
Authority, after receiving notice, does not object, taking into account all those issues.
(c) The Code Administrator shall establish the part of the timetable for the consultation
to be undertaken by the Code Administrator under these Governance Rules and
separately the preparation of a Grid Code Modification Report to the Authority.
Where the particular circumstances of the Grid Code Modification Proposal (taking
due account of its complexity, importance and urgency) justify an extension of such
timescales and provided the Authority, after receiving notice, does not object, taking
into account all those issues, the Code Administrator may revise such part of the
timetable.
(d) In setting such a timetable, the Grid Code Review Panel and the Code Administrator
shall exercise their respective discretions such that, in respect of each Grid Code
Modification Proposal, a Grid Code Modification Report may be submitted to the
Authority as soon after the Grid Code Modification Proposal is made as is
consistent with the proper evaluation of such Grid Code Modification Proposal,
Page 19 of 42
Issue 6 Revision 19 04 December 2023
taking due account of its complexity, importance and urgency.
(e) Having regard to the complexity, importance and urgency of particular Grid Code
Modification Proposals, the Grid Code Review Panel may determine the priority of
Grid Code Modification Proposals and may (subject to any objection from the
Authority taking into account all those issues) adjust the priority of the relevant Grid
Code Modification Proposal accordingly.
GR.19.2 In relation to each Grid Code Modification Proposal, the Grid Code Review Panel shall
determine at any meeting of the Grid Code Review Panel whether to:
(a) amalgamate the Grid Code Modification Proposal with any other Grid Code
Modification Proposal;
(b) invite the Proposer to further develop their Grid Code Modification Proposal before
presenting it to a subsequent meeting of the Grid Code Review Panel or to withdraw
their modification proposal;
(c) establish a Workgroup of the Grid Code Review Panel, to consider the Grid Code
Modification Proposal;
(d) review the evaluation made pursuant to GR.18.4, taking into account any new
information received; or
(e) proceed directly to wider consultation (in which case the Proposer’s right to vary their
Grid Code Modification Proposal shall lapse).
GR.19.3 The Grid Code Review Panel may decide to amalgamate a Grid Code Modification
Proposal with one or more other Grid Code Modification Proposals where the subject-
matter of such Grid Code Modification Proposals is sufficiently proximate to justify
amalgamation on the grounds of efficiency and/or where such Grid Code Modification
Proposals are logically dependent on each other. Such amalgamation may only occur with
the consent of the Proposers of the respective Grid Code Modification Proposals. The
Authority shall be entitled to direct that a Grid Code Modification Proposal is not
amalgamated with one or more other Grid Code Modification Proposals.
GR.19.4 Without prejudice to each Proposer’s right to withdraw their Grid Code Modification
Proposal prior to the amalgamation of their Grid Code Modification Proposal where Grid
Code Modification Proposals are amalgamated pursuant to GR.19.3:
(a) such Grid Code Modification Proposals shall be treated as a single Grid Code
Modification Proposal;
(b) references in these Governance Rules to a Grid Code Modification Proposal shall
include and apply to a group of two or more Grid Code Modification Proposals so
amalgamated; and
(c) the Proposers of each such Grid Code Modification Proposal shall cooperate in
deciding which of them is to provide a representative for any Workgroup in respect of
the amalgamated Grid Code Modification Proposal and, in default of agreement, the
Panel Chairperson shall nominate one of the Proposers for that purpose.
GR.19.5 In respect of any Grid Code Modification Proposal that the Grid Code Review Panel
determines to proceed directly to wider consultation in accordance with GR.19.2, the Grid
Code Review Panel, may at any time prior to the Grid Code Review Panel
Recommendation Vote having taken place decide to establish a Workgroup of the Grid
Code Review Panel and the provisions of GR.20 shall apply. In such case the Grid Code
Review Panel shall be entitled to adjust the timetable referred to at GR.19.1(b) and the
Code Administrator shall be entitled to adjust the timetable referred to at GR.19.1(c),
provided that the Authority, after receiving notice, does not object.
GR.19.6 Where the Grid Code Review Panel according to GR.19.2(b) invites the Proposer to
further develop their Grid Code Modification Proposal, on presenting this to a
Page 20 of 42
Issue 6 Revision 19 04 December 2023
subsequent meeting of the Grid Code Review Panel, the Panel will determine a way
forward from the options in GR.19.2 (a), (c), (d) and (e) or invite the Proposer to withdraw
their modification proposal.
GR.19.7 Where the Grid Code Review Panel according to GR.19.2(b) or GR.19.6 invites the
Proposer to further develop or withdraw their modification and this is declined, the Panel
will determine a way forward from the options in GR.19.2 (a), (c), (d) or (e).
GR.20 WORKGROUPS
GR.20.1 If the Grid Code Review Panel has decided not to proceed directly to wider consultation
(or where the provisions of GR.19.5, GR.23.10 or GR.25.5 apply), a Workgroup will be
established by the Grid Code Review Panel to assist the Grid Code Review Panel in
evaluating whether a Grid Code Modification Proposal better facilitates achieving the
Grid Code Objectives and whether a Workgroup Alternative Grid Code Modification(s)
would, as compared with the Grid Code Modification Proposal, better facilitate achieving
the Grid Code Objectives in relation to the issue or defect identified in the Grid Code
Modification Proposal.
GR.20.2 A single Workgroup may be responsible for the evaluation of more than one Grid Code
Modification Proposal at the same time, but need not be so responsible.
GR.20.3 A Workgroup shall comprise at least five (5) persons (who may be Panel Members)
selected by the Grid Code Review Panel from those nominated by Users, the Citizens
Advice or the Citizens Advice Scotland for their relevant experience and/or expertise in
the areas forming the subject-matter of the Grid Code Modification Proposal(s) to be
considered by such Workgroup (and the Grid Code Review Panel shall ensure, as far as
possible, that an appropriate cross-section of representation, experience and expertise is
represented on such Workgroup) provided that there shall always be at least one member
representing The Company and if, and only if, the Grid Code Review Panel is of the view
that a Grid Code Modification Proposal is likely to have an impact on the STC, the Grid
Code Review Panel may invite the STC committee to appoint a representative to become
a member of the Workgroup. A representative of the Authority may attend any meeting
of a Workgroup as an observer and may speak at such meeting.
GR.20.4 The Code Administrator shall in consultation with the Grid Code Review Panel appoint
the chairperson of the Workgroup who shall act impartially and as an independent
chairperson.
GR.20.5 No Workgroup or meeting of a Workgroup will be considered quorate with less than five
(5) persons, not including the Code Administrator representative or the chairperson of the
Workgroup. Where insufficient persons are nominated to a Workgroup for it to be quorate,
the Code Administrator will report this to the next meeting of the Grid Code Review
Panel. The Panel may:
(b) Reconsider their decision on how to progress the Grid Code Modification Proposal
as allowed under GR.19.2; or
(c) Request that those parties that have nominated themselves to a Workgroup which is
less than quorate should proceed as a Limited Membership Workgroup, subject to
the following additional checks and balances:
(i) A Limited Membership Workgroup shall always hold a Workgroup
Consultation in addition to the mandatory Code Administrator
Consultation.
(ii) Prior to the Workgroup Consultation, a draft of this shall be circulated to
the Grid Code Review Panel for five (5) days or another timescale as
agreed by the Panel for approval.
(iii) At the same time as the Workgroup Consultation is initiated, the Code
Administrator shall again formally seek nominations and if quoracy is not
Page 21 of 42
Issue 6 Revision 19 04 December 2023
established then again seek advice from the Panel on how to proceed from
the options set out in GR.20.5.
Where a Workgroup remains non-quorate, and with the permission of the Panel, a
Limited Membership Workgroup may continue following a Workgroup
Consultation as if it were a standard Workgroup.
(b) To provide a report on progress to the next meeting of the Grid Code
Review Panel.
The Authority may also at any point instruct the Code Administrator to seek
further nominations for membership.
(a) A member of the Workgroup unable to attend will be invited by the Code
Administrator to send an alternate;
(b) All members will be invited to participate by telephone, webinar or other
equivalent if not able to attend in person;
(c) A meeting may proceed as a Workgroup meeting as long as none of the
members either present or absent raise an objection to this, however no voting
can take place unless the Code Administrator has obtained enough votes to
be quorate from members not in attendance or from all members of a Limited
Membership Workgroup. This shall include where there has not been an
opportunity to check with all Workgroup members to see if they have an
objection (typically where a change of plans or circumstances has occurred
too late to achieve this);
(d) If any Workgroup member objects to the progressing of a Workgroup without
them, they must communicate this to the Code Administrator at least 24
hours before the meeting indicating that they will not be present and do not
wish the meeting to take place. The Code Administrator will then endeavour
to rearrange the meeting to accommodate such a member’s availability;
(e) Where a Workgroup member is repeatedly unavailable, as guidance on 3
consecutive occasions, and does not give permission for the Workgroup to
proceed without them as in (d), under GR.20.7 the Grid Code Review Panel
may choose to replace or remove them.
GR.20.8 The Grid Code Review Panel may add further members or the Workgroup chairperson
may add or vary members to a Workgroup.
GR.20.9 The Grid Code Review Panel may (but shall not be obliged to) replace or remove any
member or observer of a Workgroup appointed pursuant to GR.20.3 at any time if such
member is unwilling or unable for whatever reason to fulfil that function and/or is
deliberately and persistently disrupting or frustrating the work of the Workgroup.
GR.20.10 The Grid Code Review Panel shall determine the terms of reference of each Workgroup
and may change those terms of reference from time to time as it sees fit.
GR.20.11 The terms of reference of a Workgroup must include provision in respect of the following
matters:
(a) those areas of a Workgroup’s powers or activities which require the prior approval of
the Grid Code Review Panel;
(b) the seeking of instructions, clarification or guidance from the Grid Code Review Panel,
Page 22 of 42
Issue 6 Revision 19 04 December 2023
including on the suspension of a Workgroup Alternative Grid Code Modification(s)
during a Significant Code Review Phase;
(c) the timetable for the work to be done by the Workgroup, in accordance with the
timetable established pursuant to GR.19.1 (save where GR.19.5 applies); and
In addition, prior to the taking of any steps which would result in the undertaking of a
significant amount of work (including the production of draft legal text to modify the Grid
Code in order to give effect to a Grid Code Modification Proposal and/or Workgroup
Alternative Grid Code Modification(s), with the relevant terms of reference setting out
what a significant amount of work would be in any given case), the Workgroup shall seek
the views of the Grid Code Review Panel as to whether to proceed with such steps and,
in giving its views, the Grid Code Review Panel may consult the Authority in respect
thereof.
GR.20.12 Subject to the provisions of this GR.20.12 and unless otherwise determined by the Grid
Code Review Panel, the Workgroup shall develop and adopt its own internal working
procedures for the conduct of its business and shall provide a copy of such procedures to
the Panel Secretary in respect of each Grid Code Modification Proposal for which it is
responsible. Unless the Grid Code Review Panel otherwise determines, meetings of each
Workgroup shall be open to attendance by a representative of any User, (including any
Authorised Electricity Operator; The Company or a Materially Affected Party), the
Citizens Advice, the Citizens Advice Scotland, the Authority and any person invited by
the chairperson, and the chairperson of a Workgroup may invite any such person to speak
at such meetings, other than the Authority who may speak at any time as per GR.20.3.
GR.20.13 After development by the Workgroup of the Grid Code Modification Proposal, and (if
applicable) after development of any draft Workgroup Alternative Grid Code
Modification(s), the Workgroup may (subject to the provisions of GR.20.19) consult
(“Workgroup Consultation”) on the Grid Code Modification Proposal and, if applicable,
on any draft Workgroup Alternative Grid Code Modification(s) with:
(c) The date proposed by the Code Administrator as the Proposed Implementation
Date.
GR.20.15 Workgroup Consultation papers will be copied to Core Industry Document Owners and
the secretary of the STC committee.
GR.20.16 Any Authorised Electricity Operator; the Citizens Advice or the Citizens Advice
Scotland, The Company or a Materially Affected Party may (subject to GR.20.20) raise
a Workgroup Consultation Alternative Request in response to the Workgroup
Consultation. Such Workgroup Consultation Alternative Request must include:
(a) the information required by GR.15.3 (which shall be read and construed so that any
references therein to “amendment proposal” or “proposal” shall be read as “request”
and any reference to “Proposer” shall be read as “requester”); and
Page 23 of 42
Issue 6 Revision 19 04 December 2023
(b) sufficient detail to enable consideration of the request including details as to how the
request better facilitates the Grid Code Objectives than the current version of the Grid
Code, than the Grid Code Modification Proposal and than any draft Workgroup
Alternative Grid Code Modification(s).
GR.20.17 The Workgroup shall consider and analyse any comments made or any Workgroup
Consultation Alternative Request made by any User (including any Authorised
Electricity Operator; The Company or a Materially Affected Party), the Citizens Advice
and the Citizens Advice Scotland in response to the Workgroup Consultation.
GR.20.18 If a majority of the members of the Workgroup or the chairperson of the Workgroup
believe that the Workgroup Consultation Alternative Request may better facilitate the
Grid Code Objectives than the Grid Code Modification Proposal, the Workgroup shall
develop it as a Workgroup Alternative Grid Code Modification(s) or, where the
chairperson of the Workgroup agrees, amalgamate it with one or more other draft
Workgroup Alternative Grid Code Modification(s) or Workgroup Consultation
Alternative Request(s);
GR.20.19 Unless the Grid Code Review Panel directs the Workgroup otherwise pursuant to
GR.20.20, and provided that a Workgroup Consultation has been undertaken in respect
of the Grid Code Modification Proposal, no further Workgroup Consultation will be
required in respect of any Workgroup Alternative Grid Code Modification(s) developed
in respect of such Grid Code Modification Proposal.
GR.20.20 The Grid Code Review Panel may, at the request of the chairperson of the Workgroup,
direct the Workgroup to undertake further Workgroup Consultation(s). At the same time
as such direction the Grid Code Review Panel shall adjust the timetable referred to at
GR.19.1(b) and the Code Administrator shall be entitled to adjust the timetable referred
to at GR.19.1 (c), provided that the Authority, after receiving notice, does not object. No
Workgroup Consultation Alternative Request may be raised by any User (including any
Authorised Electricity Operator; The Company or a Materially Affected Party), the
Citizens Advice and the Citizens Advice Scotland during any second or subsequent
Workgroup Consultation.
GR.20. 21 The Workgroup shall finalise the Workgroup Alternative Grid Code Modification(s)
for inclusion in the report to the Grid Code Review Panel.
(a) Each Workgroup chairperson shall prepare a report to the Grid Code Review
Panel responding to the matters detailed in the terms of reference in accordance
with the timetable set out in the terms of reference.
(b) If a Workgroup is unable to reach agreement on any such matter, the report must
reflect the views of the members of the Workgroup.
(c) The report will be circulated in draft form to Workgroup members and a period of
not less than five (5) Business Days or if all Workgroup members agree three (3)
Business Days given for comments thereon. Any unresolved comments made
shall be reflected in the final report.
GR.20.23 The chairperson or another member (nominated by the chairperson) of the Workgroup shall
attend the next Grid Code Review Panel meeting following delivery of the report and may
be invited to present the findings and/or answer the questions of Panel Members in respect
thereof. Other members of the Workgroup may also attend such Grid Code Review Panel
meeting.
GR.20.24 At the meeting referred to in GR.20.23 the Grid Code Review Panel shall consider the
Workgroup’s report and shall determine whether to:-
(a) refer the proposed Grid Code Modification Proposal back to the Workgroup for
further analysis (in which case the Grid Code Review Panel shall determine the
timetable and terms of reference to apply in relation to such further analysis); or
GR.20.25 Subject to GR.16.4 if, at any time during the assessment process carried out by the
Workgroup pursuant to this GR.20, the Workgroup considers that a Grid Code
Modification Proposal or any Workgroup Alternative Grid Code Modification(s) falls
within the scope of a Significant Code Review, it shall consult on this as part of the
Workgroup Consultation and include its reasoned assessment in the report to the Grid
Code Review Panel prepared pursuant to GR.20.22. If the Grid Code Review Panel
considers that the Grid Code Modification Proposal or the Workgroup Alternative Grid
Code Modification(s) falls within the scope of a Significant Code Review, it shall consult
with the Authority. If the Authority directs that the Grid Code Modification Proposal or
Workgroup Alternative Grid Code Modification(s) falls within the scope of the Significant
Code Review, the Grid Code Modification Proposal and any Workgroup Alternative
Grid Code Modification(s) shall be suspended or withdrawn during the Significant Code
Review Phase, in accordance with GR.16.3.
GR.20.26 The Proposer may, at any time prior to the final evaluation by the Workgroup (in
accordance with its terms of reference and working practices) of that Grid Code
Modification Proposal against the Grid Code Objectives, vary their Grid Code
Modification Proposal on notice (which may be given verbally) to the chairperson of the
Workgroup provided that such varied Grid Code Modification Proposal shall address the
same issue or defect originally identified by the Proposer in their Grid Code Modification
Proposal.
GR.20.27 The Grid Code Review Panel may (but shall not be obliged to) require a Grid Code
Modification Proposal to be withdrawn if, in the Panel’s opinion, the Proposer of that Grid
Code Modification Proposal is deliberately and persistently disrupting or frustrating the
work of the Workgroup and that Grid Code Modification Proposal shall be deemed to
have been so withdrawn. In the event that a Grid Code Modification Proposal is so
withdrawn, the provisions of GR.15.10 shall apply in respect of that Grid Code Modification
Proposal.
GR.21.1 In respect of any Grid Code Modification Proposal where a Workgroup has been
established GR.21.2 to GR.21.6 shall apply.
GR.21.2 After consideration of any Workgroup report on the Grid Code Modification Proposal and
if applicable any Workgroup Alternative Grid Code Modification(s) by the Grid Code
Review Panel and a determination by the Grid Code Review Panel to proceed to wider
consultation, the Code Administrator shall bring to the attention of and consult on the Grid
Code Modification Proposal and if applicable any Workgroup Alternative Grid Code
Modification(s) with:
GR.21.3 The consultation will be undertaken by issuing a Consultation Paper (and its provision in
electronic form on the Website and in electronic mails to Users and such other persons,
who have supplied relevant details, shall meet this requirement). The consultation shall last
for a minimum of one month unless it is deemed to be an Urgent Modification. For Urgent
Modifications the Grid Code Review Panel shall confirm the proposed drafting for the Grid
Code Modification Proposal and any Workgroup Alternative Grid Code Modification(s)
do not include changes to Regulated Sections; provided there are no proposed changes to
a Regulated Section then a shorter consultation duration can be applied if approved by the
Authority, otherwise the standard one month consultation will apply.
(b) the date proposed by the Code Administrator as the Proposed Implementation
Date and, where the Workgroup terms of reference require and the dates proposed
by the Workgroup are different from those proposed by the Code Administrator,
those proposed by the Workgroup. In relation to a Grid Code Modification Proposal
that meets the Self-Governance Criteria, the Code Administrator may not propose
an implementation date earlier than the sixteenth (16) Business Day following the
publication of the Grid Code Review Panel’s decision to approve or reject the Grid
Code Modification Proposal. Views will be invited on these dates.
GR.21.5 Where the Grid Code Review Panel is of the view that the proposed text to amend the
Grid Code for a Grid Code Modification Proposal or Workgroup Alternative Grid Code
Modification(s) is not needed in the Grid Code Modification Report, the Grid Code
Review Panel shall consult (giving its reasons as to why it is of this view) with the Authority
as to whether the Authority would like the Grid Code Modification Report to include the
proposed text to amend the Grid Code. If it does not, no text needs to be included. If it
does, and no detailed text has yet been prepared, the Code Administrator shall prepare
such text to modify the Grid Code in order to give effect to such Grid Code Modification
Proposal or Workgroup Alternative Grid Code Modification(s) and shall seek the
conclusions of the relevant Workgroup before consulting those identified in GR.21.2.
GR.21.6 Consultation Papers will be copied to Core Industry Document Owners and the
secretary of the STC committee.
GR.21.7 In respect of any Grid Code Modification Proposal where a Workgroup has not been
established GR.21.8 to GR.21.11 shall apply.
GR.21.8 After determination by the Grid Code Review Panel to proceed to wider consultation, such
consultation shall be conducted by the Code Administrator on the Grid Code
Modification Proposal with:
GR.21.9 The consultation will be undertaken by issuing a Consultation Paper (and its provision in
electronic form on the Website and in electronic mails to Users and such other persons,
who have supplied relevant details, shall meet this requirement). The consultation shall last
for a minimum of one month unless it is deemed to be an Urgent Modification. For Urgent
Modifications the Grid Code Review Panel shall confirm the proposed drafting for the
Grid Code Modification Proposal and any Workgroup Alternative Grid Code
Modification(s) do not include changes to Regulated Sections; provided there are no
proposed changes to a Regulated Section then a shorter consultation duration can be
applied if approved by the Authority, otherwise the standard one month consultation will
apply.
(a) the proposed drafting for the Grid Code Modification Proposal (unless the Authority
decides none is needed in the Grid Code Modification Report under GR.21.11) and
will incorporate The Company’s and the Grid Code Review Panel’s initial views on
the way forward; and
(b) the date proposed by the Code Administrator as the Proposed Implementation
Date. Views will be invited on this date.
Page 26 of 42
Issue 6 Revision 19 04 December 2023
GR.21.11 Where the Grid Code Review Panel is of the view that the proposed text to amend the
Grid Code for a Grid Code Modification Proposal is not needed, the Grid Code Review
Panel shall consult (giving its reasons to why it is of this view) with the Authority as to
whether the Authority would like the Grid Code Modification Report to include the
proposed text to amend the Grid Code. If it does not, no text needs to be included. If it
does, and no detailed text has yet been prepared, the Code Administrator shall prepare
such text to modify the Grid Code in order to give effect to such Grid Code Modification
Proposal and consult those identified in GR.21.2.
GR.22.1 Subject to the Code Administrator’s consultation having been completed, the Grid Code
Review Panel shall prepare and submit to the Authority a report (the "Grid Code
Modification Report") in accordance with this GR.22 for each Grid Code Modification
Proposal which is not withdrawn.
GR.22.1A Where a Grid Code Modification Proposal or any Workgroup Alternative Grid Code
Modification constitutes an amendment to the Regulated Sections, the Panel will
consider any consultation responses received and any further work required to assess
these as required under GR.18.9.
GR.22.2 The matters to be included in a Grid Code Modification Report shall be the following (in
respect of the Grid Code Modification Proposal):
(a) A description of the Grid Code Modification Proposal and any Workgroup
Alternative Grid Code Modification(s), including the details of, and the rationale for,
any variations made (or, as the case may be, omitted) by the Proposer together with
the views of the Workgroup;
(c) a summary (agreed by the Grid Code Review Panel) of the views (including any
recommendations) from Panel Members in the Grid Code Review Panel
Recommendation Vote and the conclusions of the Workgroup (if there is one) in
respect of the Grid Code Modification Proposal and of any Workgroup Alternative
Grid Code Modification(s);
(d) an analysis of whether (and, if so, to what extent) the Grid Code Modification
Proposal and any Workgroup Alternative Grid Code Modification(s) would better
facilitate achievement of the Grid Code Objective(s) with a detailed explanation of the
Grid Code Review Panel’s reasons for its assessment, including, where the impact is
likely to be material, an assessment of the quantifiable impact of the Grid Code
Modification Proposal and any Workgroup Alternative Grid Code Modification(s)
on greenhouse gas emissions, to be conducted in accordance with such current
guidance on the treatment of carbon costs and evaluation of the greenhouse gas
emissions as may be issued by the Authority from time to time, and providing a
detailed explanation of the Grid Code Review Panel’s reasons for that assessment;
(e) an analysis of whether (and, if so, to what extent) any Workgroup Alternative Grid
Code Modification(s) would better facilitate achievement of the Grid Code
Objective(s) as compared with the Grid Code Modification Proposal and any other
Workgroup Alternative Grid Code Modification(s) and the current version of the
Grid Code, with a detailed explanation of the Grid Code Review Panel’s reasons for
its assessment, including, where the impact is likely to be material, an assessment of
the quantifiable impact of the Workgroup Alternative Grid Code Modification(s) on
greenhouse gas emissions, to be conducted in accordance with such current guidance
on the treatment of carbon costs and evaluation of the greenhouse gas emissions as
may be issued by the Authority from time to time, and providing a detailed explanation
of the Grid Code Review Panel’s reasons for that assessment;
(f) the Proposed Implementation Date taking into account the views put forward during
the process described at GR.21.4 (b) such date to be determined by the Grid Code
Page 27 of 42
Issue 6 Revision 19 04 December 2023
Review Panel in the event of any disparity between such views and those of the Code
Administrator;
(i) the impact of the Grid Code Modification Proposal and any Workgroup
Alternative Grid Code Modification(s) on the Core Industry Documents
and the STC;
(ii) the changes which would be required to the Core Industry Documents and
the STC in order to give effect to the Grid Code Modification Proposal and
any Workgroup Alternative Grid Code Modification(s);
(iii) the mechanism and likely timescale for the making of the changes referred to
in (ii);
(iv) the changes and/or developments which would be required to central computer
systems and, if practicable, processes used in connection with the operation
of arrangements established under the Core Industry Documents and the
STC;
(v) the mechanism and likely timescale for the making of the changes referred to
in (iv);
(vi) an estimate of the costs associated with making and delivering the changes
referred to in (ii) and (iv), such costs are expected to relate to: for (ii) the costs
of amending the Core Industry Document(s) and STC and for (iv) the costs
of changes to computer systems and possibly processes which are
established for the operation of the Core Industry Documents and the STC,
together with an analysis and a summary of representations in relation to such
matters, including any made by Small Participants, the Citizens Advice and
the Citizens Advice Scotland;
(h) to the extent such information is available to the Code Administrator, an assessment
of the impact of the Grid Code Modification Proposal and any Workgroup
Alternative Grid Code Modification(s) on Users in general (or classes of Users in
general), including the changes which are likely to be required to their internal systems
and processes and an estimate of the development, capital and operating costs
associated with implementing the changes to the Grid Code and to Core Industry
Documents and the STC;
(i) copies of (and a summary of) all written representations or objections made by
consultees during the consultation in respect of the Grid Code Modification Proposal
and any Workgroup Alternative Grid Code Modification(s) and subsequently
maintained;
(j) a copy of any impact assessment prepared by Core Industry Document Owners and
the STC committee and the views and comments of the Code Administrator in respect
thereof;
(k) whether or not, in the opinion of The Company, the Grid Code Modification Proposal
(or any Workgroup Alternative Grid Code Modification(s)) should be made.
(l) The Company’s justification for including or not including the views resulting from the
relevant consultation in the Grid Code Modification Report.
(m) where a Grid Code Modification Proposal or any Workgroup Alternative Grid
Code Modification(s) constitutes an amendment to the areas set out in table 1 of
the GR.B annex which details the Regulated Sections, the expected impact on the
objectives of Retained EU Law (Commission
Regulation (EU) 2017/2195).
GR.22.3 A draft of the Grid Code Modification Report will be circulated by the Code
Administrator to Users, Panel Members and such other persons who may properly be
considered to have an appropriate interest in it (and its provision in electronic form on the
Website and in electronic mails to Users and Panel Members, who must supply relevant
details, shall meet this requirement) and a period of no less than five (5) Business Days
given for comments to be made thereon. Any unresolved comments made shall be
Page 28 of 42
Issue 6 Revision 19 04 December 2023
reflected in the final Grid Code Modification Report.
GR.22.4 A draft of the Grid Code Modification Report shall be tabled at a meeting of the Grid
Code Review Panel prior to submission of that Grid Code Modification Report to the
Authority as set in accordance with the timetable established pursuant to GR.19.1, and at
which the Panel may consider any minor changes to the legal drafting, which may include
any issues identified through the Code Administrator consultation, and:
(i) if the change required is a typographical error the Grid Code Review Panel may
instruct the Code Administrator to make the appropriate change and the Panel
Chairperson will undertake the Grid Code Review Panel Recommendation
Vote; or
(ii) if the change required is not considered to be a typographical error then the Grid
Code Review Panel may direct the Workgroup to review the change. If the
Workgroup unanimously agree that the change is minor the Grid Code Review
Panel may instruct the Code Administrator to make the appropriate change and
the Panel Chairperson will undertake the Grid Code Review Panel
Recommendation Vote, otherwise for changes that are not considered to be
minor the Code Administrator shall issue the Grid Code Modification
Proposal for further Code Administrator consultation, after which the Panel
Chairperson will undertake the Grid Code Review Panel Recommendation
Vote; or
(iii) In the case of a modification that had been directed pursuant to GR.19.2(e) to
proceed directly to wider consultation without the formation of a Workgroup, and
if the change required is not considered to be a typographical error, then the Grid
Code Review Panel may direct the Code Administrator in conjunction with the
Proposer to review the change. If the Grid Code Review Panel, the Code
Administrator and the Proposer agree that the change is minor the Grid Code
Review Panel may instruct the Code Administrator to make the appropriate
change and the Panel Chairperson will undertake the Grid Code Review Panel
Recommendation Vote, otherwise for changes that are not considered to be
minor the Code Administrator shall issue the Grid Code Modification
Proposal for further Code Administrator consultation after which the Panel
Chairperson will undertake the Grid Code Review Panel Recommendation
Vote. In the case of a change that is not considered to be minor, the Grid Code
Review Panel may also consider whether to establish a Workgroup of the Grid
Code Review Panel, to further consider the Grid Code Modification Proposal,
in which case the procedures set out within GR.20 will be followed as required;
or
(iv) if a change is not required after consideration, the Panel Chairperson will
undertake the Grid Code Review Panel Recommendation Vote.
GR.22.5 A draft of the Grid Code Modification Report following the Grid Code Review Panel
Recommendation Vote will be circulated by the Code Administrator to Panel Members
(and in electronic mails to Panel Members, who must supply relevant details, shall meet this
requirement) and a period of no less than five (5) Business Days given for comments to be
made on whether the Grid Code Modification Report accurately reflects the views of the
Panel Members as expressed at the Grid Code Review Panel Recommendation Vote. Any
unresolved comments made shall be reflected in the final Grid Code Modification Report.
GR.22.6 Each Grid Code Modification Report shall be addressed and furnished to the Authority
and none of the facts, opinions or statements contained in such may be relied upon by any
other person.
GR.22.7 Subject to GR.22.9 to GR.22.12, in accordance with the Transmission Licence, the
Authority may approve the Grid Code Modification Proposal or a Workgroup Alternative
Grid Code Modification(s) contained in the Grid Code Modification Report (which shall
then be an "Approved Modification" until implemented).
GR.22.8 The Code Administrator shall copy (by electronic mail to those persons who have supplied
Page 29 of 42
Issue 6 Revision 19 04 December 2023
relevant details to the Code Administrator) the Grid Code Modification Report to:
GR.22.9.1 Where the Proposed Implementation Date included in a Grid Code Modification Report
is a Fixed Proposed Implementation Date and the Authority considers that the Fixed
Proposed Implementation Date is or may no longer be appropriate or might otherwise
prevent the Authority from making such decision by reason of the effluxion of time the
Authority may direct the Grid Code Review Panel to recommend a revised Proposed
Implementation Date.
(a) specify that the revised Proposed Implementation Date shall not be prior
to a specified date;
(b) specify a reasonable period (taking into account a reasonable period for
consultation) within which the Grid Code Review Panel shall be requested
to submit its recommendation; and
(c) provide such reasons as the Authority deems appropriate for such request
(and in respect of those matters referred to in GR.22.9.2 (a) and (b) above).
GR.22.9.3 Before making a recommendation to the Authority, the Grid Code Review Panel will
consult on the revised Proposed Implementation Date, and may in addition consult on
any matters relating to the Grid Code Modification Report which in the Grid Code
Review Panel’s opinion have materially changed since the Grid Code Modification
Report was submitted to the Authority and where it does so the Grid Code Review
Panel shall report on such matters as part of its recommendation under Grid Code
GR.22.9.4, with:
GR.22.9.4 Following the completion of the consultation held pursuant to GR.22.9.3 the Grid Code
Review Panel shall report to the Authority with copies of all the consultation responses
and recommending a Revised Proposed Implementation Date.
GR.22.9.5 The Authority shall notify the Grid Code Review Panel as to whether or not it intends to
accept the Revised Proposed Implementation Date and where the Authority notifies the
Grid Code Review Panel that it intends to accept the Revised Proposed Implementation
Date, the Revised Proposed Implementation Date shall be deemed to be the Proposed
Implementation Date as specified in the Grid Code Modification Report.
If:
(a) the Authority has not given notice of its decision in respect of a Grid Code
Modification Report within two (2) calendar months (in the case of an Urgent
Modification), or four (4) calendar months (in the case of all other Grid Code
Modification Proposals) from the date upon which the Grid Code Modification
Report was submitted to it; or
(b) the Grid Code Review Panel is of the reasonable opinion that the circumstances
relating to the Grid Code Modification Proposal and/or Workgroup Alternative Grid
Page 30 of 42
Issue 6 Revision 19 04 December 2023
Code Modification which is the subject of a Grid Code Modification Report have
materially changed, the Grid Code Review Panel may request the Panel Secretary
to write to the Authority requesting the Authority to give an indication of the likely
date by which the Authority’s decision on the Grid Code Modification Proposal will
be made.
GR.22.11 If the Authority determines that the Grid Code Modification Report is such that the
Authority cannot properly form an opinion on the Grid Code Modification Proposal and
any Workgroup Alternative Grid Code Modification(s), or where the Grid Code
Modification Proposal and/or any Workgroup Alternative Grid Code Modification(s)
constitutes an amendment to the Regulated Sections of the code, where the Authority
requires an amendment to the Grid Code Modification Proposal and/or any Workgroup
Alternative Grid Code Modification(s) in order to approve it, it may issue a direction to
the Grid Code Review Panel:
(a) specifying the additional steps (including drafting or amending existing drafting
associated with the Grid Code Modification Proposal and any Workgroup
Alternative Grid Code Modification(s), revision (including revision to the timetable),
analysis or information that it requires in order to form such an opinion; and
(b) requiring the Grid Code Modification Report to be revised and to be resubmitted.
GR.22.12 If a Grid Code Modification Report is to be revised and re-submitted in accordance with
a direction issued pursuant to GR.22.11, it shall be re-submitted as soon after the
Authority’s direction as is appropriate (and in the case of an amendment to the areas set
out in table 1 of the GR.B annex which details the Regulated Sections of the code within
2 months), taking into account the complexity, importance and urgency of the Grid Code
Modification Proposal and any Workgroup Alternative Grid Code Modification(s). The
Grid Code Review Panel shall decide on the level of analysis and consultation required in
order to comply with the Authority’s direction and shall agree an appropriate timetable for
meeting its obligations. Once the Grid Code Modification Report is revised, the Grid
Code Review Panel shall carry out its Grid Code Review Panel Recommendation Vote
again in respect of the revised Grid Code Modification Report and re-submit it to the
Authority in compliance with GR.22.4 to GR.22.6.
GR.23.1 If a Relevant Party recommends to the Panel Secretary that a proposal should be treated
as an Urgent Modification in accordance with this GR.23, the Panel Secretary shall notify
the Panel Chairperson who shall then, in accordance with GR.23.2 (a) to (e) inclusive,
and notwithstanding anything in the contrary in these Governance Rules, endeavour to
obtain the views of the Grid Code Review Panel as to the matters set out in GR.23.3. If
for any reason the Panel Chairperson is unable to do that, the Panel Secretary shall
attempt to do so (and the measures to be undertaken by the Panel Chairperson in the
following paragraphs shall in such case be undertaken by the Panel Secretary).
GR.23.2 (a) The Panel Chairperson shall determine the time by which, in their opinion, a decision
of the Grid Review Panel is required in relation to such matters, having regard to the
degree of urgency in all circumstances, and references in this GR.23.1 to the “time
available” shall mean the time available, based on any such determination by the Panel
Chairperson;
(b)The Panel Secretary shall, at the request of the Panel Chairperson, convene a
meeting or meetings (including meetings by telephone conference call, where
appropriate) of the Grid Code Review Panel in such manner and upon such notice as
the Panel Chairperson considers appropriate, and such that, where practicable within
the time available, as many Panel Members as possible may attend;
(c) Each Panel Member shall be deemed to have consented, for the purposes of GR.8.9.
to the convening of such meeting or meetings in the manner and on the notice
determined by the Panel Chairperson. GR.8.10 shall not apply to any such business.
(d) Where:
Page 31 of 42
Issue 6 Revision 19 04 December 2023
(i) it becomes apparent, in seeking to convene a meeting of the Grid Code
Review Panel within the time available, that quorum will not be present; or
(ii) it transpires that the meeting of the Grid Code Review Panel is not quorate
and it is not possible to rearrange such meeting within the time available, the
Panel Chairperson shall endeavour to contact each Panel Member
individually in order to ascertain such Panel Member’s vote, and (subject to
GR.23.2 (e)) any matter to be decided shall be decided by a majority of those
Panel Members who so cast a vote. Where, for whatever reason no decision
is reached, the Panel Chairperson shall proceed to consult with the
Authority in accordance with GR.23.5;
(e) Where the Panel Chairperson is unable to contact at least four Panel
Members within the time available and where:
(i) It is only The Company, who has recommended that the proposal should
be treated as an Urgent Modification, then those Panel Members
contacted shall decide such matters, such decision may be a majority
decision. Where in such cases no decision is made for whatever reason, the
Panel Chairperson shall proceed to consult with the Authority in
accordance with GR.23.5; or
(ii) any User (including any Authorised Electricity Operator; The Company
or a Materially Affected Party), the Citizens Advice or the Citizens
Advice Scotland has recommended that the proposal should be treated as
an Urgent Modification, then the Panel Chairperson may decide the
matter (in consultation with those Panel Members (if any) which they
manage to contact) provided that the Panel Chairperson shall include
details in the relevant Grid Code Modification Report of the steps which
they took to contact other Panel Members first.
(b) the procedure and timetable to be followed in respect of such Urgent Modification.
GR.23.4 The Panel Chairperson or, in their absence, the Panel Secretary shall forthwith provide
the Authority with the recommendation (if any) ascertained in accordance with GR.23.2
(a) to (e) inclusive, of the Grid Code Review Panel as to the matters referred to in GR.23.2,
and shall consult the Authority as to whether such Grid Code Modification Proposal is
an Urgent Modification and, if so, as to the procedure and timetable which should apply
in respect thereof.
GR.23.5 If the Grid Code Review Panel has been unable to make a recommendation in
accordance with GR.23.2.(d) or GR.23.2(e) as to the matters referred to in GR.23.3 then
the Panel Chairperson or, in their absence, the Panel Secretary may recommend
whether they consider that such proposal should be treated as an Urgent Modification
and shall forthwith consult the Authority as to whether such Grid Code Modification
Proposal is an Urgent Modification and, if so, as to the procedure and timetable that
should apply in respect thereof.
(a) not treat any Grid Code Modification Proposal as an Urgent Modification except
with the prior consent of the Authority;
(b) comply with the procedure and timetable in respect of any Urgent Modification
approved by the Authority; and
(c) comply with any direction of the Authority issued in respect of any of the matters on
which the Authority is consulted pursuant to GR.23.4 or GR.23.5.
Page 32 of 42
Issue 6 Revision 19 04 December 2023
GR.23.7 For the purposes of this GR.23.7, the procedure and timetable in respect of an Urgent
Modification may (with the approval of the Authority pursuant to GR.23.4 or GR.23.5)
deviate from all or part of the Grid Code Modification Procedures or follow any other
procedure or timetable approved by the Authority except for the duration of the Code
Administrator consultation for modifications relating to Regulated Sections which shall
be for one month. Where the procedure and timetable approved by the Authority in respect
of an Urgent Modification do not provide for the establishment (or designation) of a
Workgroup the Proposer’s right to vary the Grid Code Modification Proposal pursuant
to GR.15.10 and GR.20.26 shall lapse from the time and date of such approval.
GR.23.8 The Grid Code Modification Report in respect of an Urgent Modification shall include:
(a) a statement as to why the Proposer believes that such Grid Code
Modification Proposal should be treated as an Urgent Modification;
(b) any statement provided by the Authority as to why the Authority believes
that such Grid Code Modification Proposal should be treated as an Urgent
Modification;
(c) any recommendation of the Grid Code Review Panel (or any
recommendation of the Panel Chairperson) provided in accordance with
GR.23 in respect of whether any Grid Code Modification Proposal should
be treated as an Urgent Modification; and
(d) the extent to which the procedure followed deviated from the process for
Standard Modifications (other than the procedures in this GR.23).
GR.23.9 Each Panel Member shall take all reasonable steps to ensure that an Urgent Modification
is considered, evaluated and (subject to the approval of the Authority) implemented as
soon as reasonably practicable, having regard to the urgency of the matter and, for the
avoidance of doubt, an Urgent Modification may (subject to the approval of the Authority)
result in the Grid Code being amended on the day on which such proposal is submitted.
GR.23.10 Where an Urgent Modification results in an amendment being made in accordance with
GR.25, the Grid Code Review Panel may or (where it appears to the Grid Code Review
Panel that there is a reasonable level of support for a review amongst Users) shall
following such amendment, establish a Workgroup on terms specified by the Grid Code
Review Panel to consider and report as to whether any alternative amendment could, as
compared with such amendment better facilitate achieving the Grid Code Objectives in
respect of the subject matter of that Urgent Modification.
GR.24 SELF-GOVERNANCE
GR.24.1 If the Grid Code Review Panel, having evaluated a Grid Code Modification Proposal
against the Self-Governance Criteria, pursuant to GR.18.4, considers that the Grid Code
Modification Proposal meets the Self-Governance Criteria, the Grid Code Review
Panel shall submit to the Authority a Self-Governance Statement setting out its
reasoning in reasonable detail.
GR.24.2 The Authority may, at any time prior to the Grid Code Review Panel’s determination
made pursuant to GR.24.9, give written notice that it disagrees with the Self-Governance
Statement and may direct that the Grid Code Modification Proposal proceeds through
the process for Standard Modifications set out in GR.19, GR.20, GR.21 and GR.22.
GR.24.3 Subject to GR.24.2, after submitting a Self-Governance Statement, the Grid Code
Review Panel shall follow the procedure set out in GR.19, GR.20, GR.21 and GR.22.
GR.24.4 The Authority may issue a direction to the Grid Code Review Panel in relation to a
Modification to follow the procedure set out for Modifications that meet the Self-
Governance Criteria, notwithstanding that no Self-Governance Statement has been
submitted or a Self-Governance Statement has been retracted.
Page 33 of 42
Issue 6 Revision 19 04 December 2023
GR.24.5 Subject to the Code Administrator’s consultation having been completed pursuant to
GR.21, the Grid Code Review Panel shall prepare a report (the “Grid Code Modification
Self-Governance Report”).
GR.24.6 The matters to be included in a Grid Code Modification Self-Governance Report shall
be the following (in respect of the Grid Code Modification Proposal):
(a) details of its analysis of the Grid Code Modification Proposal against the Self-
Governance Criteria;
(c) the date on which the Grid Code Review Panel Self-Governance Vote shall take
place, which shall not be earlier than seven (7) days from the date on which the Grid
Code Modification Self- Governance Report is furnished to the Authority in
accordance with GR.24.8; and
(d) such other information that is considered relevant by the Grid Code Review Panel.
GR.24.7 A draft of the Grid Code Modification Self-Governance Report will be circulated by the
Code Administrator to Users and Panel Members (and its provision in electronic form on
the Website and in electronic mails to Users and Panel Members, who must supply
relevant details, shall meet this requirement) and a period of no less than five (5) Business
Days given for comments to be made thereon. Any unresolved comments made shall be
reflected in the final Grid Code Modification Self-Governance Report.
GR.24.8 Each Grid Code Modification Self-Governance Report shall be addressed and furnished
to the Authority and none of the facts, opinions or statements contained in such Grid Code
Modification Self-Governance Report may be relied upon by any other person.
GR.24.9 Subject to GR.24.11, if the Authority does not give written notice that its decision is
required pursuant to GR.24.2, or if the Authority determines that the Self-Governance
Criteria are satisfied in accordance with GR.24.4, then the Grid Code Modification Self-
Governance Report shall be tabled at the Panel Meeting following submission of that
Grid Code Modification Self-Governance Report to the Authority at which the Panel
Chairperson will undertake the Grid Code Review Panel Self-Governance Vote and
the Code Administrator shall give notice of the outcome of such vote to the Authority
as soon as possible thereafter.
GR.24.10 If the Grid Code Review Panel vote to approve the Grid Code Modification Proposal
pursuant to GR.24.9 (which shall then be an “Approved Grid Code Self-Governance
Proposal”) until implemented).
GR.24.11 The Grid Code Review Panel may at any time prior to the Grid Code Review Panel’s
determination retract a Self-Governance Statement subject to GR.24.4, or if the
Authority notifies the Grid Code Review Panel that it has determined that a Grid Code
Modification Proposal does not meet the Self-Governance Criteria the Grid Code
Review Panel shall treat the Grid Code Modification Proposal as a Standard
Modification and shall comply with GR.22, using the Grid Code Modification Self-
Governance Report as a basis for its Grid Code Modification Report.
GR.24.12 The Code Administrator shall make available on the Website and copy (by electronic
mail to those persons who have supplied relevant details to the Code Administrator) the
Grid Code Modification Self-Governance Report prepared in accordance with GR.24 to:
GR.24.13 A User (including any Authorised Electricity Operator; The Company or a Materially
Affected Party), the Citizens Advice or the Citizens Advice Scotland may appeal to the
Authority the approval or rejection by the Grid Code Review Panel of a Grid Code
Page 34 of 42
Issue 6 Revision 19 04 December 2023
Modification Proposal and any Workgroup Alternative Grid Code Modification(s) in
accordance with GR.24.9, provided that the Panel Secretary is also notified, and the
appeal has been made up to and including fifteen (15) Business Days after the Grid Code
Review Panel Self-Governance Vote has been undertaken pursuant to GR.24.9. If such
an appeal is made, implementation of the Grid Code Modification Proposal shall be
suspended pending the outcome. The appealing User (including any Authorised
Electricity Operator; The Company or a Materially Affected Party), the Citizens Advice
or the Citizens Advice Scotland must notify the Panel Secretary of the appeal when the
appeal is made.
GR.24.14 The Authority shall consider whether the appeal satisfies the following criteria:
(a) The appealing party is, or is likely to be, unfairly prejudiced by the implementation
or non-implementation of that Grid Code Modification Proposal or Workgroup
Alternative Grid Code Modification(s); or
(b) The appeal is on the grounds that, in the case of implementation, the Grid Code
Modification Proposal or Workgroup Alternative; or
(c) Grid Code Modification(s) may not better facilitate the achievement of at least
one of the Grid Code Objectives; or
(d) The appeal is on the grounds that, in the case of non-implementation, the Grid
Code Modification Proposal or Workgroup Alternative Grid Code
Modification(s) may better facilitate the achievement of at least one of the Grid
Code Objectives; and
(e) It is not brought for reasons that are trivial, vexatious or have no reasonable
prospect of success and if the Authority considers that the criteria are not
satisfied, it shall dismiss the appeal.
GR.24.15 Following any appeal to the Authority, a Grid Code Modification Proposal or
Workgroup Alternative Grid Code Modification(s) shall be treated in accordance with
any decision and/or direction of the Authority following that appeal.
GR.24.16 If the Authority quashes the Grid Code Review Panel’s determination in respect of a Grid
Code Modification Proposal or Workgroup Alternative Grid Code Modification(s)
made in accordance with GR.24.9 and takes the decision on the relevant Grid Code
Modification Proposal and any Workgroup Alternative Grid Code Modification(s)
itself, following an appeal to the Authority, the Grid Code Review Panel’s determination
of that Grid Code Modification Proposal and any Workgroup Alternative Grid Code
Modification(s) contained in the relevant Grid Code Modification Self Governance
Report shall be treated as a Grid Code Modification Report submitted to the Authority
pursuant to GR.22.6 (for the avoidance of doubt, subject to GR.22.8 to GR.22.12) and the
Grid Code Review Panel’s determination shall be treated as its recommendation pursuant
to GR.22.4.
GR.24.17 If the Authority quashes the Grid Code Review Panel’s determination in respect of a Grid
Code Modification Proposal or Workgroup Alternative Grid Code Modification(s)
made in accordance with GR.24.9, the Authority may, following an appeal to the
Authority, refer the Grid Code Modification Proposal back to the Grid Code Review
Panel for further re-consideration and a further Grid Code Review Panel Self-
Governance Vote.
GR.24.18 Following an appeal to the Authority, the Authority may confirm the Grid Code Review
Panel’s determination in respect of a Grid Code Modification Proposal or Workgroup
Alternative Grid Code Modification(s) made in accordance with GR.24.9.
GR.25 IMPLEMENTATION
GR.25.1 The Grid Code shall be modified either in accordance with the terms of the direction by the
Authority relating to, or other approval by the Authority of, the Grid Code Modification
Page 35 of 42
Issue 6 Revision 19 04 December 2023
Proposal or any Workgroup Alternative Grid Code Modification(s) contained in the
relevant Grid Code Modification Report, or in respect of Grid Code Modification
Proposals or any Workgroup Alternative Grid Code Modification(s) that are subject to
the determination of the Grid Code Review Panel pursuant to GR.24.9, in accordance with
the relevant Grid Code Modification Self-Governance Report subject to the appeal
procedures set out in GR.24.13 to GR.24.18.
GR.25.2 The Code Administrator shall forthwith notify (by publication on the Website and, where
relevant details are supplied by electronic mail):
GR.25.3 A modification of the Grid Code shall take effect from the time and date specified in the
direction, or other approval, from the Authority referred to in GR.25.1 or, in the absence
of any such time and date in the direction or approval, from 00:00 hours on the day falling
ten (10) Business Days after the date of such direction, or other approval, from the
Authority. A modification of the Grid Code pursuant to GR.24.9 shall take effect, subject
to the appeal procedures set out in GR.24.13 to GR.24.18, from the time and date specified
by the Code Administrator in its notice given pursuant to GR.25.2, which shall be given
after the expiry of the fifteen (15) Business Day period set out in GR.24.13 to allow for
appeals, or where an appeal is raised in accordance with GR.24.13, on conclusion of the
appeal in accordance with GR.24.15 or GR.24.18 but where conclusion of the appeal is
earlier than the fifteen (15) Business Day period set out in GR.24.13, notice shall be given
after the expiry of this period. A modification of the Grid Code pursuant to GR.26 shall take
effect from the date specified in the Grid Code Modification Fast Track Report.
GR.25.4 A modification made pursuant to and in accordance with GR.25.1 shall not be impaired or
invalidated in any way by any inadvertent failure to comply with or give effect to this Section.
GR.25.5 If a modification is made to the Grid Code in accordance with the Transmission Licence
but other than pursuant to the other Grid Code Modification Procedures in these
Governance Rules, the Grid Code Review Panel shall determine whether or not to submit
the modification for review by a Workgroup established on terms specified by the Grid
Code Review Panel to consider and report as to whether any alternative modification
could, as compared with such modification better facilitate achieving the Grid Code
Objectives in respect of the subject matter of the original modification. Where such a
Workgroup is established the provisions of GR.20 shall apply as if such a modification
were a Grid Code Modification Proposal.
Transitional Issues
GR.25.6 Notwithstanding the provisions of GR.25.3, Modification GC0132 changes the Grid Code
process for Grid Code Modification Proposals and therefore may affect other Grid Code
Modification Proposals which have not yet become Approved Modifications.
Consequently, this GR.25.6 deals with issues arising out of the implementation of
Modification GC0132. In particular this deals with which version of the Grid Code process
for Grid Code Modification Proposals will apply to Grid Code Modification Proposal(s)
which were already instigated prior to the implementation of Modification GC0132.
Any Grid Code Modification Proposal in respect of which a Grid Code Modification
Report has been sent to the Authority prior to the date and time of implementation of
Modification GC0132 is known as an “Old Modification”. Any Grid Code Modification
Proposal in respect of which a Grid Code Modification Report has not been sent to the
Authority as at the date and time of implementation of Modification GC0132 is known as
a “New Modification”. The Grid Code provisions which will apply to any Old
Modification(s) are the provisions of the Grid Code in force immediately prior to the
Page 36 of 42
Issue 6 Revision 19 04 December 2023
implementation of GC0132. The provisions of the Grid Code which will apply to any New
Modifications are the provisions of the Grid Code in force and as amended from time to
time.
GR.25.7 Notwithstanding the provisions of GR.25.3, Modification GC0131 changes the Grid Code
process for Grid Code Modification Proposals and therefore may affect other Grid Code
Modification Proposals which have not yet become Approved Modifications.
Consequently, this GR.25.7 deals with issues arising out of the implementation of
Modification GC0131. In particular this deals with which version of the Grid Code process
for Grid Code Modification Proposals will apply to Grid Code Modification Proposal(s)
which were already instigated prior to the implementation of Modification GC0131.
Any Grid Code Modification Proposal in respect of which a Grid Code Modification
Report has been sent to the Authority prior to the date and time of implementation of
Modification GC0131 is known as an “Old GC0131 Modification”. Any Grid Code
Modification Proposal in respect of which a Grid Code Modification Report has not
been sent to the Authority as at the date and time of implementation of Modification
GC0131 is known as a “New GC0131 Modification”. The Grid Code provisions which will
apply to any Old GC0131 Modification(s) are the provisions of the Grid Code in force
immediately prior to the implementation of GC0131. The provisions of the Grid Code which
will apply to any New GC0131 Modifications are the provisions of the Grid Code in force
from time to time.
GR.26.1 Where a Proposer believes that a modification to the Grid Code which meets the Fast
Track Criteria is required, a Grid Code Fast Track Proposal may be raised. In such case
the Proposer is only required to provide the details listed in GR.15.3 (a), (b), (c), (d), (e)
and (k).
GR.26.2 Provided that the Panel Secretary receives any modification to the Grid Code which the
Proposer considers to be a Grid Code Fast Track Proposal, not less than ten (10)
Business Days (or such shorter period as the Panel Secretary may agree, provided that
the Panel Secretary shall not agree any period shorter than five (5) Business Days) prior
to the next Grid Code Review Panel meeting, the Panel Secretary shall place the Grid
Code Fast Track Proposal on the agenda of the next Grid Code Review Panel meeting,
and otherwise, shall place it on the agenda of the next succeeding Grid Code Review
Panel meeting.
GR.26.3 To facilitate the discussion at the Grid Code Review Panel meeting, the Code
Administrator will circulate a draft of the Grid Code Modification Fast Track Report to
Users, the Authority and Panel Members (and its provision in electronic form on the
Website and in electronic mails to Users, the Authority and Panel Members, who must
supply relevant details, shall meet this requirement) for comment not less than five (5)
Business Days ahead of the Grid Code Review Panel meeting which will consider
whether or not the Fast Track Criteria are met and whether or not to approve the Grid
Code Fast Track Proposal.
GR.26.4 It is for the Grid Code Review Panel to decide whether or not a Grid Code Fast Track
Proposal meets the Fast Track Criteria and if it does, to determine whether or not to
approve the Grid Code Fast Track Proposal.
GR.26.5 The Grid Code Review Panel’s decision that a Grid Code Fast Track Proposal meets
the Fast Track Criteria pursuant to GR.26.4 must be unanimous.
GR.26.6 The Grid Code Review Panel’s decision to approve the Grid Code Fast Track Proposal
pursuant to GR.26.4 must be unanimous.
GR.26.7 If the Grid Code Review Panel vote unanimously that the Grid Code Fast Track
Proposal meets the Fast Track Criteria and to approve the Grid Code Fast Track
Proposal (which shall then be an “Approved Fast Track Proposal”) until implemented,
or until an objection is received pursuant to GR.26.12), then subject to the objection
Page 37 of 42
Issue 6 Revision 19 04 December 2023
procedures set out in GR.26.12 the Grid Code Fast Track Proposal will be implemented
by The Company without the Authority’s approval. If the Grid Code Review Panel do
not unanimously agree that the Grid Code Modification Proposal meets the Fast Track
Criteria and/or do not unanimously agree that the Grid Code Fast Track Proposal should
be made, then the Panel Secretary shall, in accordance with GR.15.4(a) notify the
Proposer that additional information is required if the Proposer wishes the Grid Code
Modification Proposal to continue.
GR.26.8 Provided that the Grid Code Review Panel have unanimously agreed to treat a Grid Code
Modification Proposal as a Grid Code Fast Track Proposal and unanimously approved
that Grid Code Fast Track Proposal, the Grid Code Review Panel shall prepare and
approve the Grid Code Modification Fast Track Report for issue in accordance with
GR.26.11.
GR.26.9 The matters to be included in a Grid Code Modification Fast Track Report shall be the
following (in respect of the Grid Code Fast Track Proposal):
(a) a description of the proposed modification and of its nature and purpose;
(b) details of the changes required to the Grid Code, including the proposed legal text to
modify the Grid Code to implement the Grid Code Fast Track Proposal;
(d) the intended implementation date, from which the Approved Fast Track Proposal will
take effect, which shall be no sooner than fifteen (15) Business Days after the date of
notification of the Grid Code Review Panel’s decision to approve; and
(e) details of how to object to the Approved Fast Track Proposal being made
GR.26.10 Upon approval by the Grid Code Review Panel of the Grid Code Modification Fast Track
Report, the Code Administrator will issue the report in accordance with GR.26.11.
GR.26.11 The Code Administrator shall copy (by electronic mail to those persons who have
supplied relevant details to the Code Administrator) the Grid Code Modification Fast
Track Report prepared in accordance with GR.26 to:
GR.26.12 A User, any Authorised Electricity Operator; The Company or a Materially Affected
Party, the Citizens Advice, the Citizens Advice Scotland or the Authority may object to
the Approved Fast Track Proposal being implemented, and shall include with such
objection the reasons for the objection. Any such objection must be made in writing
(including by email) and be clearly stated to be an objection to the Approved Fast Track
Proposal in accordance with this GR.26 of the Grid Code and be notified to the Panel
Secretary by the date up to and including fifteen (15) Business Days after notification of
the Grid Code Review Panel’s decision to approve the Grid Code Fast Track Proposal.
If such an objection is made the Approved Fast Track Proposal shall not be implemented.
The Panel Secretary will notify each Panel Member and the Authority of the objection.
The Panel Secretary shall notify the Proposer, in accordance with GR.15.4A that
additional information is required if the Proposer wishes the Grid Code Modification
Proposal to continue.
Page 38 of 42
Issue 6 Revision 19 04 December 2023
ANNEX GR.A - ELECTION OF USERS' PANEL MEMBERS
1. The election process has two main elements: nomination and selection.
2. The process will be used to appoint Panel Members in the category of Supplier, Generator, Offshore
Transmission Owner and Onshore Transmission Owner.
3. The Code Administrator will publish the Election timetable by [September] in the year preceding the start
of each term of office of Panel Members.
4. Each step of the process set out below will be carried out in line with the published timetable.
5. The Code Administrator will establish an Electoral Roll from representatives of parties listed on CUSC
Schedule 1 or designated by the Authority as a Materially Affected Party as at 31st August in the year
preceding the start of each term of office of Panel Members.
6. The Code Administrator will keep the Electoral Roll up to date.
Nomination Process
7. Each party on the Electoral Roll may nominate a candidate to stand for election for the Grid Code Review
Panel.
8. Parties may only nominate a candidate for their own category; a Supplier may nominate a candidate for
the Supplier Panel Member seat and a Generator may nominate a candidate for the Generator Panel
Member seats. If a party able to nominate a candidate is both a Supplier and a Generator, they may
nominate a candidate in each category.
9. The nominating party must complete the nomination form which will be made available by the Code
Administrator and return it to the Code Administrator by the stated deadline.
10. The Code Administrator will draw up a list of candidates for each category of election.
11. Where there are fewer candidates than seats available or the same number of candidates as seats
available, no election will be required and the nominated candidate(s) will be elected. The Code
Administrator will publish a list of the successful candidates on the Grid Code website and circulate the
results by email to the Grid Code circulation list.
Selection Process
12. The Code Administrator will send a numbered voting paper to each party on the electoral roll for each of
the elections in which they are eligible to vote. The voting paper will contain a list of candidates for each
election and will be sent by email.
13. Each eligible party may vote for one [1] candidate for each of the Supplier, Offshore Transmission
Owner and Onshore Transmission Owner seats and four [4] candidates for the Generator seats.
14. Panel Members will be elected using the First Past the Post method.
15. In the event of two or more candidates receiving the same number of votes, the Code Administrator will
draw lots to decide who is elected.
16. The Code Administrator will publish the results of the election on the Grid Code website and circulate
the results by email to the Grid Code circulation list.
17. The Code Administrator will send an Election Report to Ofgem after the election is complete.
Page 39 of 42
Issue 6 Revision 19 04 December 2023
ANNEX GR.B Regulated Sections
The Grid Code sections identified in Tables 1 and 2 are considered to be Regulated Sections.
Table 1 - Mapping of Electricity Balancing Regulation Article 18 Terms and Conditions for Balancing
Service Providers and BalancingResponsible Parties to the Grid Code
Commission
Regulation
(EU) Grid Code
Description
2017/2195 Reference
Reference
(Retained EU
Law)
define reasonable and justified requirements for the provisions BC1, BC2, BC3 &
18.4.a
of balancing services; BC4
Page 40 of 42
Issue 6 Revision 19 04 December 2023
BC1.4.2,3,4, BC1
the requirements on data and information to be delivered to
18.6. d Appendix 1
the connecting TSO to calculate the imbalances;
BC2.5.1,
Table 2 - Mapping of Network Code on Emergency and Restoration (NCER) Article 4(4) Terms and
Conditions for System Defence and System Restoration Service Providers to the Grid Code
Page 41 of 42
Issue 6 Revision 19 04 December 2023
4(4) (b) the possibility of and conditions DRSC1, DRSC2, DRSC4
(b) for aggregation; and ECC/CC 6.5
BC1.4
BC1. A.10
BC
Page 42 of 42
Issue 6 Revision 19 04 December 2023
REVISIONS
(R)
R.1 The Company’s Transmission Licence sets out the way in which changes to the Grid Code
are to be made and reference is also made to The Company's obligations under the General
Conditions.
R.2 All pages re-issued have the revision number on the lower left hand corner of the page and
date of the revision on the lower right hand corner of the page.
R.3 The Grid Code was introduced in March 1990 and the first issue was revised 31 times. In
March 2001 the New Electricity Trading Arrangements were introduced and Issue 2 of the
Grid Code was introduced which was revised 16 times. At British Electricity Trading and
Transmission Arrangements (BETTA) Go-Active Issue 3 of the Grid Code was introduced
and subsequently revised 35 times. At Offshore Go-active Issue 4 of the Grid Code was
introduced and has been revised 13 times since its original publication. Issue 5 of the Grid
Code was published to accommodate the changes made by Grid Code Modification A/10
which has incorporated the Generator compliance process into the Grid Code, which was
revised 47 times. Issue 6 was published to incorporate all the non-material amendments as a
result of modification GC0136.
R.4 This Revisions section provides a summary of the sections of the Grid Code changed by each
revision to Issue 6.
R.5 All enquiries in relation to revisions to the Grid Code, including revisions to Issues 1, 2, 3, 4
and 5 should be addressed to the Grid Code development team at the following email address:
[email protected]
Revision Section Related Effective Date
Modification