Kohler Sizing Generators For Motor Starting A Practical Guide To Understanding How Motor Starting Loads Affect Generator Performance
Kohler Sizing Generators For Motor Starting A Practical Guide To Understanding How Motor Starting Loads Affect Generator Performance
AUTHORS INTRODUCTION
DAN KRUEGER
Director of Sales, South Region
Today’s standby power loads are more complex than ever before. In many
RICK VAN MAAREN industrial and commercial applications, standby generator must supply
Senior Staff Engineer
power to a mixture of linear and nonlinear loads in addition to large motor
KOHLER Power Systems loads that cycle on and off. Of all the diverse loads a standby generator must
supply, applications with motors present the most sizing issues. The dynamic
interactions of motors and generators–along with the impact of motor
starters, system inertia, motor loading, frequency dip, generator preload and
nonlinear loading–make manual generator sizing difficult, if not impossible.
Not only is sizing an application with large motors complex, but different
generator manufacturers have different approaches for specifying a standby
power system that will function reliably. Each major generator manufacturer
has created generator-sizing software to help with this complex task, but
due to manufacturers’ differing approaches to motor starting, this software
can yield quite different results—sometimes specifying a larger and more
expensive generator or too small a generator than is necessary for reliable
operation. The purpose of this article is to explain how motors affect
generator performance and how sizing software, such as Kohler Power
Solutions Center, deals with motor loads. Armed with
this understanding, power system specifiers will be able to select the most
cost-effective and reliable generator for motor-starting applications.
BASIC CHARACTERISTICS OF MOTOR LOADS The motor-starting kVA can be determined by
the motor’s nameplate. The National Electrical
Motor loads cause difficulty because a motor
Manufacturers Association (NEMA) sets design
draws high current when started at full voltage.
standards for motors and has established a
Starting current is typically six times a motor’s
NEMA code-letter designation for classifying
rated full-load current, and this inrush current
motors according to the ratio of locked-rotor
stays high until the motor reaches about 75
kVAs (LRKVAs) per horsepower. These code
percent of rated speed. When a motor is started
letters range from A to V, covering motors with an
on normal utility power, the high inrush current will
LRKVA-per-horsepower ratio of 3.14 or less to a
cause only a small voltage dip because the utility
ratio of 22.4 LRKVA-per-horsepower or more.
is a more robust voltage source. However, when
See Figure 1.
a motor is started on generator power, the high
inrush currents (measured in kilovolt-amperes or For example, a 50 hp Code F motor requires 279.5
KVAs) can result in a large voltage dip LRKVA per horsepower upon starting
that can inhibit the motor from reaching its (50 hp x 5.59 LRKVA per hp = 279.5 LRKVA/hp).
operating speed. LRKVA is also known as “starting kVA” or “SKVA.”
Small motors have a higher NEMA code letter and
The challenge, then, is to size the generator
correspondingly higher LRKVA-per-horsepower
to handle the motor-starting load, but also to
requirement than large motors. Typical motor sizes
minimize the impact on the other connected loads
and codes are shown in Figure 2.
that may be affected by voltage dips or frequency
dips. Therefore, when sizing a generator, it is
critical to accurately predict voltage dips and to VOLTAGE DIP
understand how much excess starting capability
is available in the motor and what amount of The kVA requirements of a motor running at full
voltage dip can be allowed. The most common load and rated speed are normally less than one
methodology for sizing generators for motor kVA per horsepower. With the possible exception
starting focuses on understanding allowable of small motors, it would be overly conservative
instantaneous voltage dips, as the primary criteria. to size a generator set simply by matching the
However, there is one manufacturer that considers alternator’s kVA to the motor’s kVA. This would
allowable sustained voltage dips as the primary typically result in a generator with more than
criteria for motor-starting load. twice the capacity necessary. However, due to the
dynamic interaction of the system components,
kVA per Horsepower several characteristics combine to make this
Letter Designation
with Locked Rotor
approach impractical.
A 0–3.14
B 3.15–3.54 The first characteristic is power factor. Three-
C 3.55–3.99 phase generator sets are usually rated in kVA at
D 4.0–4.49 0.8 power factor. Starting power factors of motors
E 4.5–4.99 vary from 0.3 to 0.5 and increase towards unity as
F 5.0–5.59 the motor accelerates and its kVA demand drops.
G 5.6–6.29 With a 0.4 power-factor load, a typical generator is
H 6.3–7.00 capable of producing nearly twice its continuous-
J 7.1–7.99 rated kVA for the time required to accelerate a
K 8.0–8.99 motor to the speed at which its kVA requirement
L 9.0–9.99 drops sharply. The generator engine will not stall
M 10.0–11.10 even though it is being asked to supply more than
N 11.2–12.49 its rated kVA, because low power-factor loads
P 12.5–13.99 (see Figure 3) do not require as much horsepower
R 14.0–15.99 as higher power-factor loads. This generator
S 16.0–17.99 characteristic allows satisfactory motor-starting
T 18.0–19.99 results with a generator half the size predicted by
U 20.0–22.39 the conservative approach, which matches the
V 22.4 and up generator 0.8 power-factor kVA rating to the
Figure 1: Locked Rotor Indicating Code Letters motor-LRKVA rating.
Source: 2006 NEMA
AMPS OR KVA
0.4 Power Factor = 50% HP Factor
Figure 3. Engine Power Required
Figure 3: Engine
forPower Required
Low Power for Load
Factor
Low Power-Factor Load
Source: Kohler Power Systems
4 4
Line Circuit
Line Circuit
Start
Start
2 2
Run Run
Time Time
voltage dip during motor starting. For example, 60% Fast Responding
Exciter
a 50 percent preloaded generator may dip an 50% Conventional Exciter
additional 2 percent compared to the 40%
V2 +%
100
performance, the following fundamental criteria -%
V3
for motor starting must be accomplished–and 95
voltage dip is considered to be the first step for V1 = Voltage dip T0 = Point at which load is applied
V2 = Maximum transient voltage overshoot T1 = Time to recover to a specified band
motor starting by most generator and alternator V3 = Recovery voltage T2 = Time to recover to and remain
manufacturers. Typical motors are designed to V4 = Steady-state regulator within the specified band
40.0%
Finally, due to the complexity of total system
35.0% The entire red shaded area is not
30.0% available if the motor starting loads and the dynamics of the generator and
contacts drop out at a 35% voltage
25.0% dip. At a 20% voltage dip motor-starting applications, it’s important to
requirement, the area of available
20.0% LRKVA is further reduced. utilize proven generator-sizing software to
15.0% ensure performance of the entire system in its
10.0% specific application.
Nameplate
5.0% LRKVA
0.0%
0 500 1000 1500 2000 2500 3000 3500
Motor Nameplate LRKVA
Dan Krueger is the Director of Sales for the Southern region for Kohler
Power Systems. He has worked within the power generation industry for
more than 20 years in manufacturing, product and business management,
and sales both domestically and internationally. Krueger joined Kohler
in 1998, primarily working with the engineering community, supporting
system sales and providing training on KOHLER ® products and paralleling
switchgear systems.
Rick Van Maaren is a Senior Staff Engineer with Kohler Power Systems.
He has worked in alternator development of standby, marine, residential
and mobile generators for more than 30 years. He holds a bachelor's
degree in electrical engineering from Michigan Technological University, is a
registered professional engineer in the state of Wisconsin, a senior member
of the Institute of Electrical and Electronics Engineers (IEEE) and a holder
of seven patents. He has authored an IEEE Industry Applications Society
(IAS) paper titled Rotor Lamination Design for Surface Permanent Retention at
High Speeds and a chapter of the Electrical Generating Systems Association
(EGSA) On-Site Power Generation reference book
titled "Permanent Magnet Generators".
KOHLERPOWER.COM
Printed in U.S.A. G26-7 KPS 103 1/18 © 2018 by Kohler Co.