0% found this document useful (0 votes)
9 views50 pages

MetercatLite User Guide

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views50 pages

MetercatLite User Guide

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

MetercatLite™ software

User manual

TM42-3055B
CONTENTS

Introduction............................................................................................................................................... 1
General procedure.................................................................................................................................... 3
Parameters ............................................................................................................................................... 5
MetercatLite switches...................................................................................................................5
/? .................................................................................................................................... 5
/ver................................................................................................................................. 5
/loc ................................................................................................................................. 5
/pwd or /pwdh ............................................................................................................... 5
/ovr................................................................................................................................. 6
Global section ...............................................................................................................................6
AUTOID_STRATEGY .........................................................................................................6
REPORT_FILENAME ........................................................................................................6
SHOW_PROGRESS..........................................................................................................7
Communication section ................................................................................................................7
CHANNEL_TYPE ..............................................................................................................8
PROTOCOL_TYPE ............................................................................................................8
PEER_ADDRESS..............................................................................................................8
PEER_PORT .....................................................................................................................9
CALLED_AP_TITLE ...........................................................................................................9
RAS_DIAL_NAME ............................................................................................................9
PORT_NAME ....................................................................................................................9
BAUD ...............................................................................................................................9
USER_ID ....................................................................................................................... 10
PASSWORD .................................................................................................................. 10
Program section ......................................................................................................................... 10
PROGRAM_FILENAME ................................................................................................. 13
METER_ID_1_MODE .................................................................................................... 14
METER_ID_1 ................................................................................................................ 14
METER_ID_2_MODE .................................................................................................... 14
METER_ID_2 ................................................................................................................ 14
LINE_FREQUENCY ........................................................................................................ 14
USE_SYSTEM_TIME_ZONE .......................................................................................... 15
TIME_ZONE_NAME ...................................................................................................... 15
C1222_IP_ADDRESS ................................................................................................... 15
C1222_SUBNET_MASK............................................................................................... 15
Contents ii

C1222_DEFAULT_GATEWAY ....................................................................................... 15
DNP_SOURCE_ADDR ................................................................................................... 15
DNP_DESTINATION_ADDR .......................................................................................... 15
METERING_APP ........................................................................................................... 16
CT and VT ..................................................................................................................... 16
DEMAND_OVERLOAD .................................................................................................. 17
USE_ADJUSTED_KH..................................................................................................... 17
ADJUSTED_KH ............................................................................................................. 17
REGISTER_MULTIPLIER ............................................................................................... 17
KYZ_VALUE and KYZ_DIVISOR .................................................................................... 18
SERVICE_TEST_COMP_MODE..................................................................................... 18
SERVICE_TEST_COMP_FILENAME .............................................................................. 18
PQM_COMP_MODE ..................................................................................................... 19
PQM_COMP_FILENAME............................................................................................... 19
INSTRUM_PROFILE_COMP_MODE ............................................................................. 19
INSTRUM_PROFILE_COMP_FILENAME ...................................................................... 19
REMOTE_COMP_MODE ............................................................................................... 20
REMOTE_COMP_FILENAME ........................................................................................ 20
PORT_x_DEVICE_ID ..................................................................................................... 20
Call origination parameters for ports 1 and 2 ........................................................... 20
ACB board (WIC-Wireless) GPRS APN Passwords ...................................................... 21
ACB_PRIMARY_GPRS_PASSWORD ............................................................................ 21
ACB_ALTERNATE_GPRS_PASSWORD_1 .................................................................... 21
ACB_ALTERNATE_GPRS_PASSWORD_2 .................................................................... 21
ACB_ALTERNATE_GPRS_PASSWORD_3 .................................................................... 22
ACB C12.22 protocol ................................................................................................... 22
ACB_C1222_IP_ADDRESS .......................................................................................... 22
ACB_C1222_SUBNET_MASK ..................................................................................... 22
ACB_C1222_DEFAULT_GATEWAY .............................................................................. 22
ACB_C1222_PORT_NUMBER ..................................................................................... 22
ACB C12.21 protocol ................................................................................................... 22
ACB_C1221_IP_ADDRESS .......................................................................................... 23
ACB_C1221_SUBNET_MASK ..................................................................................... 23
ACB_C1221_DEFAULT_GATEWAY .............................................................................. 23
ACB_C1221_PORT_NUMBER ..................................................................................... 23
ACB Modbus protocol .................................................................................................. 23
ACB_MODBUS_ADDRESS ........................................................................................... 23
ACB DNP protocol ........................................................................................................ 23
ACB_DNP_SOURCE_ADDR .......................................................................................... 24
ACB_DNP_DESTINATION_ADDR ................................................................................. 24
ACB DL/T protocol ....................................................................................................... 24
ACB_DLT_ADDRESS .................................................................................................... 24
Contents iii

Read task section ...................................................................................................................... 24


A3 ALPHA meter and A1800 ALPHA meter reading task parameters ...................... 26
TASK ............................................................................................................................. 26
STORAGE_MODE ......................................................................................................... 26
reading_storage_folder ............................................................................................... 27
READING_FILENAME_ID ............................................................................................. 27
Load profiling parameters........................................................................................... 27
Instrumentation profiling parameters ........................................................................ 28
Log and data set parameters ..................................................................................... 28
LAN_BOARD_DATA ...................................................................................................... 29
READER_NOTES .......................................................................................................... 29
Time_DIFF_LIMIT ......................................................................................................... 29
PERFORM_DEMAND_RESET....................................................................................... 29
Time synch mode ........................................................................................................ 30
REXUniversal meter reading task parameters ........................................................... 30
TASK ............................................................................................................................. 30
STORAGE_MODE ......................................................................................................... 31
reading_storage_folder ............................................................................................... 31
READING_FILENAME_ID ............................................................................................. 31
Log and data set parameters ..................................................................................... 31
READER_NOTES .......................................................................................................... 32
PERFORM_DEMAND_RESET....................................................................................... 32
REX2 meter reading task parameters ........................................................................ 32
TASK ............................................................................................................................. 32
STORAGE_MODE ......................................................................................................... 32
reading_storage_folder ............................................................................................... 33
READING_FILENAME_ID ............................................................................................. 33
Load_PROFILE_MODE ................................................................................................. 33
READER_NOTES .......................................................................................................... 34
IP AxisLink router reading task parameters ............................................................... 34
TASK ............................................................................................................................. 34
STORAGE_MODE ......................................................................................................... 34
reading_storage_folder ............................................................................................... 34
READING_FILENAME_ID ............................................................................................. 35
LAN_BOARD_DATA ...................................................................................................... 35
READER_NOTES .......................................................................................................... 35
DLMS protocol parameters ....................................................................................................... 36
DLMS_PHYSICAL_ADDRESS ....................................................................................... 36
DLMS_PASSWORD ...................................................................................................... 36
Alternative time setting parameters ......................................................................................... 37
TIME_ZONE_OFFSET ................................................................................................... 37
DST_OFFSET ................................................................................................................ 37
Contents iv

DST_SWITCH_TIME.HOUR ........................................................................................... 37
DST_SWITCH_TIME.MINUTE ....................................................................................... 37
Appendix ................................................................................................................................................. 39
Time zones ................................................................................................................................. 39
Legal notices ........................................................................................................................................... 43
Trademarks ................................................................................................................................ 43
Copyright ..................................................................................................................................... 43
Generated................................................................................................................................... 43
Introduction

MetercatLite is a command line application that allows programming


the following device families:
 A3 ALPHA® and A1800 ALPHA meters using the optical port
 REXUniversal® meters using the optical port
 IP AxisLink® using the USB port

MetercatLite also supports the use of the Read tasks (diagnostic and
billing) for the following device families:
 A3 ALPHA and A1800 ALPHA meters
 REX/REX2 meters
 REXUniversal meters
 IP AxisLink devices

MetercatLite requires Microsoft Windows Vista or later. If you are


communicating with a meter, an optical probe (such as the Elster
UNICOM III probe) is required.

For more information:


See the Metercat installation manual (TM42-3050) for information
on installing MetercatLite.

1
Introduction

Notes:

2
General procedure

To use MetercatLite, you must open a command prompt window and


change directories to the MetercatLite location. The default location
of MetercatLite.exe is C:\Program Files <x86>\Elster\Metercat.
File Description
The defaults file contains the complete list
of available parameters (global,
communication, and task). Any parameters
not specified in the command file or in the
Defaults
.PED file are read from the defaults file.
Note: Be sure to create a backup copy of the
defaults file in case you need to revert back
to the original file that MetercatLite installs.
MetercatLite execution is controlled by a set
of parameters that you define in the
Command command file. Parameters set in the
command file override the corresponding
parameters in the defaults file.
Contains the Metercat program to be written
Metercat .PED
to the devices.

Note: If users don't have administrative privileges on the


computer, copies of the files should be in a folder that is
accessible to all users.
When specifying a file name, you can use just the file name to have
MetercatLite only search in the current directory for the file. You can
also specify the full path to the file.
 Basic command form: MetercatLite command_file_name
Example: MetercatLite command.txt
 Extended command form: MetercatLite command_file_name
defaults_file_name
Example: MetercatLite command.txt defaults.txt
MetercatLite identifies the connected device and attempts to
program or read it. When the attempt is complete, MetercatLite will
generate a completion report indicating the status (whether it
succeeded or failed) and any relevant information about the attempt.

3
General procedure

Notes:

4
Parameters

MetercatLite switches
/?
Example: MetercatLite /?
Displays the command line help information for the MetercatLite
executable.

/VER
Example: MetercatLite /ver
Displays the MetercatLite version information.

/LOC
Example: MetercatLite /loc pt_BR
While MetercatLite is distributed in US English, you can create
translation files for export text generated by MetercatLite. For more
information, see the Metercat internationalization manual (TM42-
3052).
Languages included in flies Code
US English (ANSI terminology) en_US
Portuguese (Brazil) pt_BR
Russian ru_RU
Romanian ro_RO
Spanish (Spain) es_ES
Chinese (Simplified) zh_CN
French (France) fr_FR

The font used by the command prompt may need to be changed to


correctly display certain languages.
1 Click on the command prompt window icon located on the top-
left corner of the Command Prompt window.
2 Select Properties and then click the Font tab.
3 Configure the fonts as appropriate for your selected language.

/PWD OR /PWDH
Example: MetercatLite /pwd 00000000000000000000 command.txt
defaults.txt

5
Parameters

Example: MetercatLite /pwdh


30303030303030303030303030303030 command.txt defaults.txt
MetercatLite requires the unrestricted password to program the
meter. The password can be provided in the command file or at the
command line prompt. Also, specifying the password at the
command prompt overrides any password value stored in the
command file.
Use /pwd to specify the password in decimal format; use /pwdh to
specify the password in hexadecimal format.

/OVR
Example: MetercatLite /ovr "section-name|parameter-
name|value"
This switch overrides a parameter in the command file. Use the
boolean values 0 and 1 for the values TRUE and FALSE, respectively.

Global section
Sample
//****************************************************************************
//****** GLOBAL parameters ***************************************************
//****************************************************************************
[GLOBAL]
REPORT_FILENAME= "Reports\McatLiteReportProgram.html"
SHOW_PROGRESS = TRUE
AUTOID_STRATEGY = {"A3_A1800"} // "REX" option for REX meter identification

The global section of the defaults file and the command file contain
the values for the system parameters.
To embed special characters in a string-type parameter, you must
prefix the string with C and use the backslash \ before the special
character.
Example: METER_ID_1 = C"1234\'567\'890"
The example results in 1234'567'890 being programmed in the meter
for METER_ID_1.

AUTOID_STRATEGY
The AUTOID_STRATEGY parameter specifies the meter family for which
the device identification will be attempted using the optical probe.
It is recommended to leave the option as A3_A1800. The REX option is
for future extension and should not be used.

REPORT_FILENAME
The REPORT_FILENAME parameter allows you to specify the path and
file name for the MetercatLite Completion Report.

6
MetercatLite user guide

SHOW_PROGRESS
The SHOW_PROGRESS parameter allows you specify whether to display
the percent progress of the command execution in the Command
Prompt window. Valid values are:
 FALSE - the percentage completion of task progress will not be
displayed in the Command Prompt window
 TRUE - (default) the percentage completion will be displayed in
the Command Prompt window

Communication section
Sample
//****************************************************************************
//****** COMMUNICATION parameters ********************************************
//****************************************************************************
[COMMUNICATION]

// ---------------------------------------------------------------------------
// Uncomment the parameters for the desired Protocol/Channel combination
// ---------------------------------------------------------------------------

// ---------------------------------------------------------------------------
// ---- Optical Probe channel; ANSI C12.18 protocol (A3/A1800) ---------------
// ---------------------------------------------------------------------------
CHANNEL_TYPE = CHANNEL_OPTICAL_PROBE
PROTOCOL_TYPE = PROTOCOL_ANSI_C12_18
PORT_NAME = "COM1"// "COMx"

// Baud rate for optical probe:


// 300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200
BAUD = 9600

// ---------------------------------------------------------------------------
// ---- Optical Probe channel; ANSI C12.21 protocol (REXU) -------------------
// ---------------------------------------------------------------------------
//CHANNEL_TYPE = CHANNEL_OPTICAL_PROBE // Default CHANNEL_TYPE value
//PROTOCOL_TYPE = PROTOCOL_REX_C12_21
//PORT_NAME = "COM1" // "COMx"

// ---------------------------------------------------------------------------
// ---- TCP/IP channel; ANSI C12.22 protocol (IPAL= IPAxisLink) --------------
// ---------------------------------------------------------------------------
//CHANNEL_TYPE = CHANNEL_SOCKET
//PROTOCOL_TYPE = PROTOCOL_ANSI_C12_22

//PEER_ADDRESS = "192.168.0.7" // device IP address


//PEER_PORT = 1153 // device port number

//CALLED_AP_TITLE = "1.3.6.1.4.1.33507.100.273" // device APTitle

// To connect to the IP AxisLink router using the USB port on the device,
// a PPP connection must be created in Windows > Network Connections.
// Set RAS_DIAL_NAME to the exact name of the PPP connection to allow

7
Parameters

// MetercatLite to automatically launch the PPP connection when programming


// the IP AxisLink device. Alternatively do not configure this parameter and
// manually launch the PPP connection before running MetercatLite.
//RAS_DIAL_NAME = "Type name here"

// ---------------------------------------------------------------------------
// ---- Common communication parameters --------------------------------------
// ---------------------------------------------------------------------------
USER_ID = 2 // 2 to 9999

// Meter unrestricted password for A3/A1800/IPAL; max length = 20 ASCII char;


// Meter unrestricted seed for REU; max length = 16 bytes (binary format)
// If parameter value is less than max length then is padded by binary zeros

// ASCII format - use for A3/A1800/IPAL


PASSWORD = "00000000000000000000"
// Binary format - use for REXU. Can be copied and pasted right from the Metercat
// Passwords Management Seed Set.
//PASSWORD = H"30303030303030303030303030303030"

To embed special characters in a string-type parameter, you must


prefix the string with C and use the backslash \ before the special
character.
Example: METER_ID_1 = C"1234\'567\'890"
The example results in 1234'567'890 being programmed in the meter
for METER_ID_1.

CHANNEL_TYPE
The CHANNEL_TYPE parameter specifies the connection type
depending on the device:
 for A3/A1800 and REXUniversal use CHANNEL_OPTICAL_PROBE
 for IPAxisLink (IPAL) use TCP/IP - CHANNEL_SOCKET
Example: CHANNEL_TYPE = CHANNEL_OPTICAL_PROBE

PROTOCOL_TYPE
The PROTOCOL_TYPE parameter specifies the ANSI protocol used for
communicating with the device:
 for A3/A1800 ALPHA use PROTOCOL_ANSI_C12_18
 for IP AxisLink (IPAL) use PROTOCOL_ANSI_C12_22
Example: PROTOCOL_TYPE = PROTOCOL_ANSI_C12_18

PEER_ADDRESS
If using TCP/IP C12.22 communication, the PEER_ADDRESS parameter
specifies the IP Address of the device.
Example: PEER_ADDRESS = "192.168.0.7"

8
MetercatLite user guide

PEER_PORT
If using TCP/IP C12.22 communication, the PEER_PORT parameter
specifies the port number used for connecting with the device.
Example: PEER_PORT = 1153

CALLED_AP_TITLE
If using TCP/IP C12.22 communication, the CALLED_AP_TITLE
parameter specifies the AP Title of the device.
Example: CALLED_AP_TITLE = "1.3.6.1.4.1.33507.100.273"

RAS_DIAL_NAME
For connecting with the IP AxisLink router, the RAS_DIAL_NAME
parameter specifies the PPP connection name that was created in
Windows > Network Connections.
See TM42-4002 IP AxisLink Router Installation and Administration
Guide for details.
Example: RAS_DIAL_NAME = "IPAL 79584"

PORT_NAME
The PORT_NAME parameter specifies the COM port number used by
the optical probe.
Example: PORT_NAME = "COM2"

BAUD
The BAUD parameter specified the baud rate used by the optical
probe. Valid values are as follows:
 300
 600
 1200
 2400
 4800
 9600 (default)
 14400
 19200
 28800
 38400
 57600
 115200
Example: BAUD = 14400

9
Parameters

USER_ID
The USER_ID parameter specifies the identification number of the
user executing the command file. This number will be programmed
into the meter as the Programmer Number on the meter’s Status >
Identification viewset. Valid values are in the range of 2 to 9999.
Example: USER_ID=2

PASSWORD
The PASSWORD parameter specifies the unrestricted access password
that MetercatLite uses to authenticate against the connected meter.
For A3/A1800 ALPHA meters and IP AxisLink devices the password is
a sequence of 20 ASCII characters
Example: PASSWORD = "00000000000000000000"
For REXUniversal meters the password parameter is a sequence of
16 binary bytes, specified in hexadecimal notation
Example: PASSWORD = H"30303030303030303030303030303030"

Program section
Sample
//****************************************************************************
//**** TASK parameters *******************************************************
//**** Uncomment one of: "Program", "IPALProgram", "REXUProgram" tasks *******
//****************************************************************************
//****************************************************************************
//************ A3/A1800 Program Task *****************************************
//****************************************************************************
//[TASK="Program"]
//PROGRAM_FILENAME = "C:\Program Files\Elster\Metercat\Programs\A3R LP program.ped"
// ID1 (Account ID) programming mode: VALUE | FACTORY_SERIAL_NUMBER | UTILITY_SERIAL_NUMBER
METER_ID_1_MODE = VALUE
// Applied only if METER_ID_1_MODE = VALUE; max length = 20 char
METER_ID_1 = ""
// ID2 (Meter ID) programming mode: FACTORY_SERIAL_NUMBER | VALUE | UTILITY_SERIAL_NUMBER
METER_ID_2_MODE = FACTORY_SERIAL_NUMBER
// Applied only if METER_ID_2_MODE = VALUE; max length = 20 char
METER_ID_2 = ""
// Meter Clock Source: Internal Oscillator used if LINE_FREQUENCY=FALSE
LINE_FREQUENCY = TRUE
// Use System Time Zone: TRUE | FALSE
USE_SYSTEM_TIME_ZONE = TRUE
// Meter is programmed according to TIME_ZONE_NAME if USE_SYSTEM_TIME_ZONE = FALSE
// See possible values of TIME_ZONE_NAME in the MetercatLite User Guide
TIME_ZONE_NAME = ""
// Metering Application: PROGRAM_VALUE | PRIMARY | SECONDARY
METERING_APP = PROGRAM_VALUE
// CT and VT ratios: These are 'pair' parameters, both of them are overridden or neither are.
// If both parameters are not specified then Program Values are used.
// If one of these parameters is missing but the other is specified then the task assumes
// that the missing parameter has a value of 1.0 and CT × VT overrides the Program value.
//CT = 1.0 // 1.00 to 9999.99
//VT = 1.0 // 1.00 to 9999.99
// Demand Overload: program value is used when the parameter is commented

10
MetercatLite user guide

//DEMAND_OVERLOAD = 0 // 0.0000 to 999999.9999

USE_ADJUSTED_KH = FALSE
// Adjusted_Kh is used only if USE_ADJUSTED_KH = TRUE
// If USE_ADJUSTED_KH=TRUE and ADJUSTED_KH parameter is commented then minimum value (0.001)
is assumed
//ADJUSTED_KH = 1.0 // 0.001 to 999.999
// Register_Multiplier is used only if USE_ADJUSTED_KH=FALSE
// Register_Multiplier: program value is used when the parameter is commented
//REGISTER_MULTIPLIER = 1.0 // 0.1 to 1000000
// KYZ_value and KYZ_divisor:
// 1) if both parameters are defined then KYZ_value
// is used if the meter supports it, otherwise KYZ_divisor is used
// 2) If only one parameter is defined (the other is
// commented) then the program task will use exactly that parameter
// (if it is not supported the task will fail)
// 3) If both parameters are commented then the program value of either KYZ_value
// or KYZ_divisor is used, depending on what the meter supports
//
//KYZ_VALUE = 1 // 0.000001 to 100.000000
//KYZ_DIVISOR = 1 // 1 to 999
// ---------------------------------------------------------------------------
// ---- Components Options ---------------------------------------------------
// ---------------------------------------------------------------------------
// Service Test Component = DO_NOT_CHANGE | PROGRAM_VALUE | OVERRIDE
SERVICE_TEST_COMP_MODE = PROGRAM_VALUE
SERVICE_TEST_COMP_FILENAME = “”
// PQM component = DO_NOT_CHANGE | PROGRAM_VALUE | OVERRIDE
PQM_COMP_MODE = PROGRAM_VALUE
PQM_COMP_FILENAME = “”
// Instrumentation Profiling Config Component = DISABLE | PROGRAM_VALUE | OVERRIDE
INSTRUM_PROFILE_COMP_MODE = PROGRAM_VALUE
INSTRUM_PROFILE_COMP_FILENAME = “”
// Remote component = DO_NOT_CHANGE | DISABLE | PROGRAM_VALUE | OVERRIDE
REMOTE_COMP_MODE = PROGRAM_VALUE
REMOTE_COMP_FILENAME = “”
// ---------------------------------------------------------------------------
// ---- Remote Component override parameters ---------------------------------
// ---------------------------------------------------------------------------
// Values specified in the PORT_x_DEVICE_ID parameters are programmed only
// if all the following conditions are met:
// a) the program contains a Remote component
// b) PORT_x is set to ‘Direct Connect’ or ‘Internal Modem’ or ‘External Modem’
PORT_1_DEVICE_ID = 1//1-254; 1= Always Master
PORT_2_DEVICE_ID = 1//1-254; 1= Always Master
// Values specified in the PORT_x call origination parameters are programmed only
// if all the following conditions are met:
// a) the program contains a Remote component
// b) PORT_x is set to "Internal Modem" or "External Modem'
// c) The remote component has both options 'Enable Billing Calling' and
// 'Specify a Single Date and Time at Program Time' set for PORT_x
PORT_1_CALL_ORIG_DATE_TIME.YEAR = 90 // YY
PORT_1_CALL_ORIG_DATE_TIME.MONTH = 1
PORT_1_CALL_ORIG_DATE_TIME.DAY = 1
PORT_1_CALL_ORIG_DATE_TIME.HOUR = 0 // 0-23
PORT_1_CALL_ORIG_DATE_TIME.MINUTE = 0
PORT_2_CALL_ORIG_DATE_TIME.YEAR = 90// YY
PORT_2_CALL_ORIG_DATE_TIME.MONTH = 1
PORT_2_CALL_ORIG_DATE_TIME.DAY = 1
PORT_2_CALL_ORIG_DATE_TIME.HOUR = 0 // 0-23
PORT_2_CALL_ORIG_DATE_TIME.MINUTE = 0

11
Parameters

// ---------------------------------------------------------------------------
// ---- SpOB Component override parameters -----------------------------------
// ---------------------------------------------------------------------------
// Program value is used when a parameter is commented
// ACB board (WIC-Wireless) GPRS APN Passwords
//ACB_PRIMARY_GPRS_PASSWORD = ""; // string up to 64 characters, only required if its a GPRS
module
//ACB_ALTERNATE_GPRS_PASSWORD_1 = ""; // string up to 64 characters, corresponds to alternate
APN username 1
//ACB_ALTERNATE_GPRS_PASSWORD_2 = ""; // string up to 64 characters, corresponds to alternate
APN username 2
//ACB_ALTERNATE_GPRS_PASSWORD_3 = ""; // string up to 64 characters, corresponds to alternate
APN username 3
// ACB board C12.22 protocol parameters
//ACB_C1222_IP_ADDRESS = "192.168.0.2"
//ACB_C1222_SUBNET_MASK = "255.255.255.0"
//ACB_C1222_DEFAULT_GATEWAY = "192.168.0.1"
//ACB_C1222_PORT_NUMBER = "1153"
// ACB board C12.21 protocol parameters
//ACB_C1221_IP_ADDRESS = "192.168.0.2"
//ACB_C1221_SUBNET_MASK = "255.255.255.0"
//ACB_C1221_DEFAULT_GATEWAY = "192.168.0.1"
//ACB_C1221_PORT_NUMBER = "1000"
// ACB board MODBUS protocol parameter
//ACB_MODBUS_ADDRESS = 1 // 0 to 255
// ACB board DNP protocol parameters
//ACB_DNP_SOURCE_ADDR = 1 // 0 to 65519
//ACB_DNP_DESTINATION_ADDR = 2 // 0 to 65519
// ACB board DLT protocol parameter
//ACB_DLT_ADDRESS = "123456789012" // string of 12 decimal numbers (each must be 0 to 9)
// ---------------------------------------------------------------------------
// ---- DLMS protocol parameters (only A1800)---------------------------------
// ---------------------------------------------------------------------------
// The following parameters are applied only if programmed Remote Component has
// "DLMS and ANSI" Protocol Type option
//DLMS_PHYSICAL_ADDRESS = 16 // 16 to 16382
// When DLMS_PASSWORD parameter is commented then DLMS password is not programmed in the meter
// i.e. DLMS password in the meter is left unchanged
// DLMS password is up to 20 binary bytes, where each character must be entered
// in a hex notation, one byte as 2 hex characters.
// If entered password has less characters than max allowed, then it is padded
// with ANSI space characters (0x20 or "20" hex)
//DLMS_PASSWORD = ""// string up to 40 characters 0-9/A-F;
//****************************************************************************
//************ IP AxisLink Program Task **************************************
//****************************************************************************
//[TASK="IPALProgram"]
//PROGRAM_FILENAME = ""
// ID1 (Account ID) programming mode: VALUE | FACTORY_SERIAL_NUMBER | UTILITY_SERIAL_NUMBER
METER_ID_1_MODE = VALUE
// Applied only if METER_ID_1_MODE = VALUE; max length = 20 char
METER_ID_1 = ""
// ID2 (Meter ID) programming mode: FACTORY_SERIAL_NUMBER | VALUE | UTILITY_SERIAL_NUMBER
METER_ID_2_MODE = FACTORY_SERIAL_NUMBER
// Applied only if METER_ID_2_MODE = VALUE; max length = 20 char
METER_ID_2 = ""
// Use System Time Zone: TRUE | FALSE
USE_SYSTEM_TIME_ZONE = TRUE
// Meter is programmed according to TIME_ZONE_NAME if USE_SYSTEM_TIME_ZONE = FALSE
// See possible values of TIME_ZONE_NAME in the MetercatLite User Guide
TIME_ZONE_NAME = ""

12
MetercatLite user guide

// ---------------------------------------------------------------------------
// ---- Network Component override parameters --------------------------------
// ---------------------------------------------------------------------------
//C1222_IP_ADDRESS = "192.168.0.7"
//C1222_SUBNET_MASK = "255.255.255.0"
//C1222_DEFAULT_GATEWAY = "192.168.0.1"
// ---------------------------------------------------------------------------
// ---- DNP Component override parameters ------------------------------------
// ---------------------------------------------------------------------------
//DNP_SOURCE_ADDR = 4 // 0 to 65535
//DNP_DESTINATION_ADDR = 3 // 0 to 65535
//****************************************************************************
//************ REXU Program Task *****************************************
//****************************************************************************
//[TASK="REXUProgram"]
//PROGRAM_FILENAME = ""
// ID1 (Account ID) programming mode: VALUE | FACTORY_SERIAL_NUMBER | UTILITY_SERIAL_NUMBER
//METER_ID_1_MODE = VALUE
// Applied only if METER_ID_1_MODE = VALUE; max length = 20 char
//METER_ID_1 = ""
// ID2 (Meter ID) programming mode: FACTORY_SERIAL_NUMBER | VALUE | UTILITY_SERIAL_NUMBER
//METER_ID_2_MODE = FACTORY_SERIAL_NUMBER
// Applied only if METER_ID_2_MODE = VALUE; max length = 20 char
//METER_ID_2 = ""
// Use System Time Zone: TRUE | FALSE
//USE_SYSTEM_TIME_ZONE = TRUE
// Meter is programmed according to TIME_ZONE_NAME if USE_SYSTEM_TIME_ZONE = FALSE
// See possible values of TIME_ZONE_NAME in the MetercatLite User Guide
//TIME_ZONE_NAME = ""
//****************************************************************************
// **** Alternative Time setting parameters **********************************
// **** Applicable to "Program", "IPALProgram" and "REXUProgram tasks ********
//****************************************************************************
// The following parameters can be used alternatively to USE_SYSTEM_TIME_ZONE
// and TIME_ZONE_NAME parameters.
// TZ Offset in minutes; Default value = 0 (GMT)
//TIME_ZONE_OFFSET = 0 // -780 to 780 minutes (-13 to 13 hours) must be divisable by 5 minutes
// Daylight Saving time offset in minutes; Default value = 60 minutes
//DST_OFFSET = 60 // 0 to 180 minutes (0 to 3 hours) must be divisable by 5 minutes
// Daylight Saving time switch time; Default value is 2:00.
//DST_SWITCH_TIME.HOUR = 2 // 0 to 23
//DST_SWITCH_TIME.MINUTE = 0 // 0 to 59
//****************************************************************************

PROGRAM_FILENAME
The PROGRAM_FILENAME parameter specified the path and file name
for the Metercat PED file to be used in programming the connected
meter.
To use a PED file specified in the command file you must specify the
path and file name:
Example: PROGRAM_FILENAME = “C:\path\filename.PED”
If only the file name is specified, MetercatLite will look for the file in
the MetercatLite installation folder.
Example: PROGRAM_FILENAME = “filename.PED”

13
Parameters

METER_ID_1_MODE
The METER_ID_1_MODE (Account ID) parameter specifies the source of
the value to be programmed as the ID1. Valid values are:
 VALUE - (default) uses the value specified by METER_ID_1 in the
command file
 FACTORY_SERIAL_NUMBER - uses the meter’s factory serial number

 UTILITY_SERIAL_NUMBER - uses the utility’s serial number stored


in the meter
Example: METER_ID_1_MODE = VALUE

METER_ID_1
If the METER_ID_1_MODE is VALUE, the value entered for METER_ID_1
will be programmed as ID1 in the connected meter. A valid value is a
maximum of 20 characters in length.
Example: METER_ID_1 = “ABCDEFGHIJKLMNOPQRST”

METER_ID_2_MODE
The METER_ID_2_MODE (Meter ID) parameter specified the source of
the value to be programmed as the ID2. Valid values are:
 VALUE - uses the value specified by METER_ID_2 in the
command file
 FACTORY_SERIAL_NUMBER - (default) uses the meter’s factory
serial number
 UTILITY_SERIAL_NUMBER - uses the utility’s serial number stored
in the meter
Example: METER_ID_2_MODE = VALUE

METER_ID_2
If the METER_ID_2_MODE is VALUE, the value entered for METER_ID will
be programmed as ID2 in the connected meter. A valid value is a
maximum of 20 characters in length.
Example: METER_ID_2 = “ABCDEFGHIJKLMNOPQRST”

LINE_FREQUENCY
The LINE_FREQUENCY parameter specifies the meter’s clock source.
Valid values are:
 TRUE - (default) the clock source is from the line frequency

 FALSE - the clock source is the meter’s internal oscillator

Example: LINE_FREQUENCY = FALSE

14
MetercatLite user guide

USE_SYSTEM_TIME_ZONE
See TIME_ZONE_OFFSET, DST_OFFSET, DST_SWITCH_TIME.HOUR, and
DST_SWITCH_TIME.MINUTE for an alternative use for time zone.

The USE_SYSTEM_TIME_ZONE parameter specifies whether to use the


computer’s system time zone setting. Valid values are:
 TRUE - (default) the time zone setting configured on the
MetercatLite computer will be programmed into the connected
meter
 FALSE - the value entered for TIME_ZONE_NAME will be
programmed into the connected meter
Example: USE_SYSTEM_TIME_ZONE = TRUE

TIME_ZONE_NAME
See TIME_ZONE_OFFSET, DST_OFFSET, DST_SWITCH_TIME.HOUR, and
DST_SWITCH_TIME.MINUTE for an alternative use for time zone.

If USE_SYSTEM_TIME_ZONE = FALSE, the TIME_ZONE_NAME parameter


specifies the time zone programmed into the connected meter.
Example: TIME_ZONE_NAME = "Eastern Standard Time"

C1222_IP_ADDRESS
The C1222_IP_ADDRESS parameter specifies the IP address assigned
to the device using ANSI C12.22 protocol.
Example: C1222_IP_ADDRESS = "192.168.0.7"

C1222_SUBNET_MASK
The C1222_SUBNET_MASK parameter specifies the subnet mask used
with the IP address for the connection using ANSI C12.22 protocol.
Example: C1222_SUBNET_MASK = "255.255.255.0"

C1222_DEFAULT_GATEWAY
The C1222_DEFAULT_GATEWAY parameter specifies the default
gateway IP address to which the WIC directs its outbound
communications.
Example: C1222_DEFAULT_GATEWAY = "192.168.0.1"

DNP_SOURCE_ADDR
The DNP_SOURCE_ADDR parameter specifies the DNP source address
for the device.
Example: DNP_SOURCE_ADDR = 4

DNP_DESTINATION_ADDR
The DNP_DESTINATION_ADDR parameter specifies the DNP destination
address for the device.
Example: DNP_DESTINATION_ADDR = 3

15
Parameters

METERING_APP
The METERING_APP parameter specifies the meter’s position relative
to a transformer. Valid values are:
 PROGRAM_VALUE - default

 PRIMARY

 SECONDARY
If PROGRAM_VALUE is specified, the setting specified in the PED file will
be programmed into the meter.
If PRIMARY is specified, transformer ratios will be used to calculate
the measured energy and demand quantities.
If SECONDARY is specified, transformer ratios will not be used to
calculate adjusted Ke and the energy and demand quantities will not
be adjusted.
Example: METERING_APP = SECONDARY

CT AND VT
The CT parameter and VT parameter specify the transformer ratios
used in the meter. Valid values are in the range of 1.00 to 9999.99.
If both parameters are not specified then values set in the PED file
are used.
Example:
//CT = 1.0

//VT = 1.0
These are paired parameters: either both are overridden or neither of
them is. If one of these parameters is missing but the other is
specified then the task assumes the missing parameter has a value
of 1.0 and CT × VT overrides the PED program value.
Example:
//CT = 1.0

VT = 1.0
or
CT = 1.0

//VT = 1.0

16
MetercatLite user guide

DEMAND_OVERLOAD
The DEMAND_OVERLOAD parameter specifies the demand overload
value to be programmed into the meter. Valid values are 0.0000 to
999999.9999.
Example: DEMAND_OVERLOAD=10.0000
To use the value specified in the PED file, comment the parameter
using two slashes (//):
Example: //DEMAND_OVERLOAD=0

USE_ADJUSTED_KH
The USE_ADJUSTED_KH parameter indicates whether the value
specified in the ADJUSTED_KH parameter will be programmed in the
meter. Valid values are:
 TRUE - the ADJUSTED_KH value will be programmed into the meter

 FALSE - (default) the REGISTER_MULTIPLIER value will be


programmed into the meter
Example: USE_ADJUSTED_KH = FALSE

ADJUSTED_KH
If USE_ADJUSTED_KH is TRUE, the ADJUSTED_KH value will be
programmed in the meter. The value of REGISTER_MULTIPLIER (if any)
is ignored. Valid value is in the range of 0.001 to 999.999.
Example: ADJUSTED_KH = 10.000
If USE_ADJUSTED_KH is TRUE and ADJUSTED_KH is commented using
two slashes (//), MetercatLite programs ADJUSTED_KH = 0.001.
Example: //ADJUSTED_KH = 1.0

REGISTER_MULTIPLIER
If USE_ADJUSTED_KH = FALSE, the REGISTER_MULTIPLIER parameter
value will be programmed in the meter. The value of ADJUSTED_KH (if
any) is ignored. Valid values are in the range of 0.1 to 1000000.
Example: REGISTER_MULTIPLIER = 1.0
To use the value specified in the PED file, comment the
REGISTER_MULTIPLIER parameter using two slashes (//):

Example: //REGISTER_MULTIPLIER = 10.0

17
Parameters

KYZ_VALUE AND KYZ_DIVISOR


If both KYZ_VALUE and KYZ_DIVISOR parameters are defined then
KYZ_VALUE is used if the meter supports it, otherwise KYZ_DIVISOR is
used. Valid values are:
 KYZ_VALUE = 0.000001 to 100.000000

 KYZ_DIVISOR = 1 to 999

If only one parameter is defined (that is, the other parameter is


commented) then the program task will use exactly that parameter (if
it is not supported the task will fail).
Example:
KYZ_VALUE = 1

//KYZ_DIVISOR = 1
To use the value specified in the PED file, comment both parameters
using two slashes (//). Then the program value of either KYZ_VALUE
or KYZ_DIVISOR is used, depending on what the meter supports.
Example:
//KYZ_VALUE = 1

//KYZ_DIVISOR = 1

SERVICE_TEST_COMP_MODE
The SERVICE_TEST_COMP_MODE parameter specifies the source for the
Service Test component to be programmed into the connected
meter. Valid values are:
 DO_NOT_CHANGE - keep the existing Service Test component that
is programmed in the meter
 PROGRAM_VALUE - (default) use the value specified in the PED file

 OVERRIDE - overrides the value specified in the PED file using the
component specified by SERVICE_TEST_COMP_FILENAME
Example: SERVICE_TEST_COMP_MODE = PROGRAM_VALUE

SERVICE_TEST_COMP_FILENAME
The SERVICE_TEST_COMP_FILENAME parameter specifies the PCD
filename of the Service Test Component to be programmed in the
meter. This parameter is ignored unless the OVERRIDE option is
selected for SERVICE_TEST_COMP_MODE.
Example: SERVICE_TEST_COMP_FILENAME =
“service_test_comp.pcd”

18
MetercatLite user guide

PQM_COMP_MODE
The PQM_COMP_MODE parameter specifies the source for the PQM
component to be programmed into the connected meter. Valid
values are:
 DO_NOT_CHANGE - keep the existing PQM component that is
programmed in the meter
 PROGRAM_VALUE - (default) use the value specified in the PED file

 OVERRIDE - overrides the value specified in the PED file using the
component specified by PQM_COMP_FILENAME
Example: PQM_COMP_MODE = PROGRAM_VALUE

PQM_COMP_FILENAME
The PQM_COMP_FILENAME parameter specifies the PCD filename of the
PQM Component to be programmed in the meter. This parameter is
ignored unless the OVERRIDE option is selected for PQM_COMP_MODE.
Example: PQM_COMP_FILENAME = “PQM_comp.pcd”

INSTRUM_PROFILE_COMP_MODE
The INSTRUM_PROFILE_COMP_MODE parameter specifies the source for
the Instrumentation Profiling Config component to be programmed
into the connected meter. Valid values are:
 DISABLE - disables the Instrumentation Profiling Config
component
 PROGRAM_VALUE - (default) use the value specified in the PED file

 OVERRIDE - overrides the value specified in the PED file using the
component specified by INSTRUM_PROFILE_COMP_FILENAME
Example: INSTRUM_PROFILE_COMP_MODE = PROGRAM_VALUE

INSTRUM_PROFILE_COMP_FILENAME
The INSTRUM_PROFILE_COMP_FILENAME parameter specifies the PCD
filename of the Instrumentation Profile Component to be
programmed in the meter. This parameter is ignored unless the
OVERRIDE option is selected for INSTRUM_PROFILE_COMP_MODE.

Example: INSTRUM_PROFILE_COMP_FILENAME =
“instr_profile_comp.pcd”

19
Parameters

REMOTE_COMP_MODE
The REMOTE_COMP_MODE parameter specifies the source for the
Remote component to be programmed into the connected meter.
Valid values are:
 DO_NOT_CHANGE - keep the existing Instrumentation Profiling
Config component that is programmed in the meter
 DISABLE - disables the Remote component

 PROGRAM_VALUE - (default) use the value specified in the PED file

 OVERRIDE - overrides the value specified in the PED file using the
component specified by REMOTE_COMP_FILENAME
Example: REMOTE_COMP_MODE = PROGRAM_VALUE

REMOTE_COMP_FILENAME
The REMOTE_COMP_FILENAME parameter specifies the PCD filename of
the Remote Component to be programmed in the meter. This
parameter is ignored unless the OVERRIDE option is selected for
REMOTE_COMP_MODE.

Example: REMOTE_COMP_FILENAME = “remote_comp.pcd”

PORT_X_DEVICE_ID
Values specified in the PORT_x_DEVICE_ID parameters are
programmed only if all the following conditions are met:
 the program contains a Remote component
 the Remote component Port 1 or Port 2 in the PED file is set to
one of the following:
o Direct Connect
o Internal Modem
o External Modem
Valid values are 1-254 (where 1= Always Master).
Examples:
PORT_1_DEVICE_ID = 1

PORT_2_DEVICE_ID = 1

CALL ORIGINATION PARAMETERS FOR PORTS 1 AND 2


Values specified in the call origination parameters are programmed
only if all the following conditions are met:
 the program contains a Remote component
 the Remote component Port 1 or Port 2 in the PED file is set to
one of the following:
o Internal Modem
o External Modem

20
MetercatLite user guide

 the Remote component Port 1 or Port 2 in the PED file has the
following options enabled:
o Enable Billing Calling
o Specify a Single Date and Time at Program Time
Example:
PORT_1_CALL_ORIG_DATE_TIME.YEAR = 90 // YY

PORT_1_CALL_ORIG_DATE_TIME.MONTH = 1

PORT_1_CALL_ORIG_DATE_TIME.DAY = 1

PORT_1_CALL_ORIG_DATE_TIME.HOUR = 0 // 0-23

PORT_1_CALL_ORIG_DATE_TIME.MINUTE = 0

PORT_2_CALL_ORIG_DATE_TIME.YEAR = 90// YY
PORT_2_CALL_ORIG_DATE_TIME.MONTH = 1

PORT_2_CALL_ORIG_DATE_TIME.DAY = 1

PORT_2_CALL_ORIG_DATE_TIME.HOUR = 0 // 0-23

PORT_2_CALL_ORIG_DATE_TIME.MINUTE = 0

ACB BOARD (WIC-WIRELESS) GPRS APN PASSWORDS


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate over
GPRS

ACB_PRIMARY_GPRS_PASSWORD
A string up to 64 characters, only required if its a GPRS module
Example: ACB_PRIMARY_GPRS_PASSWORD = "";

ACB_ALTERNATE_GPRS_PASSWORD_1
A string up to 64 characters, corresponds to alternate APN username
1
Example: ACB_ALTERNATE_GPRS_PASSWORD_1 = "";

ACB_ALTERNATE_GPRS_PASSWORD_2
A string up to 64 characters, corresponds to alternate APN username
2
Example: ACB_ALTERNATE_GPRS_PASSWORD_2 = "";

21
Parameters

ACB_ALTERNATE_GPRS_PASSWORD_3
A string up to 64 characters, corresponds to alternate APN username
3
Example: ACB_ALTERNATE_GPRS_PASSWORD_3 = "";

ACB C12.22 PROTOCOL


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate using
ANSI C12.22 protocol

ACB_C1222_IP_ADDRESS
The ACB_C1222_IP_ADDRESS parameter specifies the IP address for
the C12.22 advanced communications board.
Example: ACB_C1222_IP_ADDRESS = "192.168.0.2"

ACB_C1222_SUBNET_MASK
The ACB_C1222_SUBNET_MASK parameter specifies the subnet mask
for the C12.22 advanced communications board.
Example: ACB_C1222_SUBNET_MASK = "255.255.255.0"

ACB_C1222_DEFAULT_GATEWAY
The ACB_C1222_DEFAULT_GATEWAY parameter specifies the gateway
for the C12.22 advanced communications board.
Example: ACB_C1222_DEFAULT_GATEWAY = "192.168.0.1"

ACB_C1222_PORT_NUMBER
The ACB_C1222_PORT_NUMBER parameter specifies the port number
for the C12.22 advanced communications board.
Example: ACB_C1222_PORT_NUMBER = "1153"

ACB C12.21 PROTOCOL


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate using
ANSI C12.21 protocol
 the DHCP option is not set in the Special Option Board
Component
To use the value specified in the PED file, comment a parameter
using two slashes, //. Then the program value for the ACB C12.21
parameter is used.

22
MetercatLite user guide

ACB_C1221_IP_ADDRESS
The ACB_C1221_IP_ADDRESS parameter specifies the IP address for
the C12.21 advanced communications board.
Example: ACB_C1221_IP_ADDRESS = "192.168.0.2"

ACB_C1221_SUBNET_MASK
The ACB_C1221_SUBNET_MASK parameter specifies the subnet mask
for the C12.21 advanced communications board.
Example: ACB_C1221_SUBNET_MASK = "255.255.255.0"

ACB_C1221_DEFAULT_GATEWAY
The ACB_C1221_DEFAULT_GATEWAY parameter specifies the gateway
for the C12.21 advanced communications board.
Example: ACB_C1221_DEFAULT_GATEWAY = "192.168.0.1"

ACB_C1221_PORT_NUMBER
The ACB_C1221_PORT_NUMBER parameter specifies the gateway for the
C12.21 advanced communications board.
Example: ACB_C1221_PORT_NUMBER = "1000"

ACB MODBUS PROTOCOL


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate using
Modbus protocol
To use the value specified in the PED file, comment a parameter
using two slashes, //. Then the program value for the ACB Modbus
parameter is used.

ACB_MODBUS_ADDRESS
The ACB_MODBUS_ADDRESS parameter specifies the address for the
ModBus advanced communications board.
Example: ACB_MODBUS_ADDRESS = 1 // 0 to 255

ACB DNP PROTOCOL


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate using
DNP protocol
To use the value specified in the PED file, comment a parameter
using two slashes, //. Then the program value for the ACB DNP
parameter is used.

23
Parameters

ACB_DNP_SOURCE_ADDR
The ACB_DNP_SOURCE_ADDR parameter specifies the source address
for the DNP advanced communications board.
Example: ACB_DNP_SOURCE_ADDR = 1 // 0 to 65519

ACB_DNP_DESTINATION_ADDR
The ACB_DNP_DESTINATION_ADDR parameter specifies the destination
address for the DNP advanced communications board.
Example: ACB_DNP_DESTINATION_ADDR = 2 // 0 to 65519

ACB DL/T PROTOCOL


These parameters are applied if all the following conditions are met:
 the PED program contains a Special Option Board component
 the ACB board in the meter has capability to communicate using
DL/T protocol
To use the value specified in the PED file, comment the parameter
using two slashes (//). Then the program value for the ACB DLT
parameter is used.

ACB_DLT_ADDRESS
The ACB_DLT_ADDRESS parameter specifies the destination address
for the DL/T advanced communications board.
Example: ACB_DLT_ADDRESS = "123456789012" // string of 12
decimal numbers (each must be 0 to 9)

Read task section


Sample
//****************************************************************************
//************ A3/A1800 Diagnostic and Billing Read Tasks ********************
//****************************************************************************
//[TASK="DiagnosticRead"] // "Diagnostic Read - A3/A1800"
//[TASK="BillingRead"] // "Billing Read - A3/A1800"
// Reading file Storage Mode: NONE | APPEND | REPLACE
//STORAGE_MODE = REPLACE // default in [TASK="DiagnosticRead"]
//STORAGE_MODE = APPEND // default in [TASK="BillingRead"]
// Reading MSR file storage folder. MSR file is saved to /Diagnostic or /Billing
// subfolder depend on used task.
//READING_STORAGE_FOLDER = "./"
// Reading Filename ID (ID1 aka "Account" or ID2 aka "Meter Id"): METER_ID_1 | METER_ID_2
// READING_FILENAME_ID = METER_ID_1
// Interval Data (Load Profile): NONE | ALL | UNREAD | NUMBER_OF_DAYS
// [TASK="BillingRead"] task supports additional option: UNREAD_WITH_UPDATE
//LOAD_PROFILE_MODE = ALL
//LOAD_PROFILE_DAYS = 1 // 1-999 used when LOAD_PROFILE_MODE = NUMBER_OF_DAYS
// Interval Data (Instrumentation):: NONE | ALL | UNREAD | NUMBER_OF_DAYS
// [TASK="BillingRead"] task supports additional option: UNREAD_WITH_UPDATE
//INSTRUMENTATION_PROFILE_MODE = ALL
//INSTRUMENTATION_PROFILE_DAYS = 1 // 1-999 used when INSTRUMENTATION_PROFILE_MODE =
NUMBER_OF_DAYS

24
MetercatLite user guide

// History Log Data: NONE | ALL


//HISTORY_LOG = ALL
// Event Log Data: NONE | ALL
//EVENT_LOG = ALL
// PQM and Sag Logs Data: NONE | ALL
//PQM_SAG_LOGS = ALL
// Self Read Data: NONE | ALL
//SELF_READ_DATA = ALL
// Harmonic Content Data: NONE | ALL
//HARMONIC_DATA = NONE
// Gatekeeper/Node Data: STATUS_ONLY | ALL
//LAN_BOARD_DATA = STATUS_ONLY
// Reader Notes. Could contain a multi-line note e.g. C"12345 \x0A 67890".
//READER_NOTES = ""
// Report a warning if PC and meter time difference is greater than asked limit.
// Verification is not occurred when TIME_DIFF_LIMIT is not defined.
//TIME_DIFF_LIMIT.HOUR = 0 // 0-23
//TIME_DIFF_LIMIT.MINUTE = 0 // 0-59
// e.g. if TIME_DIFF_LIMIT.HOUR = 1 and TIME_DIFF_LIMIT.MINUTE = 15 then the
// warning is reported when meter time differs for more than 75 minutes.
// Only [TASK="BillingRead"] "Billing Read - A3/A1800" task option.
// Perform Demand Reset: TRUE/FALSE
//PERFORM_DEMAND_RESET = FALSE
// Only [TASK="BillingRead"] "Billing Read - A3/A1800" task option.
// Time Adjustment Criteria: NEVER | ALWAYS | IN_RANGE
//TIME_SYNCH_MODE = NEVER
// If TIME_SYNCH_MODE = IN_RANGE then enter low and high bounds.
// Meter time is synchronized with PC time if time difference is in range:
// TIME_SYNCH_LOW_BOUND <= MeterPCTimeDifference <= TIME_SYNCH_HIGH_BOUND.
// If time difference is out of required range then a warning is reported.
//TIME_SYNCH_LOW_BOUND.HOUR = 0 // 0-23
//TIME_SYNCH_LOW_BOUND.MINUTE = 0 // 0-59
//TIME_SYNCH_HIGH_BOUND.HOUR = 0 // 0-23
//TIME_SYNCH_HIGH_BOUND.MINUTE = 0 // 0-59
//****************************************************************************
//************ REXU Diagnostic and Billing Read Tasks ************************
//****************************************************************************
//[TASK="REXUDiagRead"] // "Diagnostic Read - REXU"
//[TASK="REXUBillingRead"] // "Billing Read - REXU"
// Reading file Storage Mode: NONE | APPEND | REPLACE
//STORAGE_MODE = REPLACE // default in [TASK="REXUDiagRead"]
//STORAGE_MODE = APPEND // default in [TASK="REXUBillingRead"]
// Reading MSR file storage folder. MSR file is saved to /Diagnostic or /Billing
// subfolder depend on used task.
//READING_STORAGE_FOLDER = "./"
// Reading Filename ID (ID1 aka "Account" or ID2 aka "Meter Id"): METER_ID_1 | METER_ID_2
// READING_FILENAME_ID = METER_ID_1
// Interval Data (Load Profile): NONE | ALL
//LOAD_PROFILE_MODE = ALL
// Interval Data (Instrumentation):: NONE | ALL
//INSTRUMENTATION_PROFILE_MODE = ALL
// Event Log Data: NONE | ALL
//EVENT_LOG = ALL
// Self Read Data: NONE | ALL
//SELF_READ_DATA = ALL
// Reader Notes. Could contain a multi-line note e.g. C"12345 \x0A 67890".
//READER_NOTES = ""
// Only [TASK="REXUBillingRead"] "Billing Read - REXU" task option.
// Perform Demand Reset: TRUE/FALSE
//PERFORM_DEMAND_RESET = FALSE
//****************************************************************************

25
Parameters

//************ REX/REX2 Diagnostic Read Task *********************************


//****************************************************************************
//[TASK="REXDiagRead"] // "Diagnostic Read - REX"
// Reading file Storage Mode: NONE | APPEND | REPLACE
//STORAGE_MODE = REPLACE
// Reading MSR file storage folder. MSR file is saved to /Diagnostic subfolder.
//READING_STORAGE_FOLDER = "./"
// Reading Filename ID (ID1 aka "Account" or ID2 aka "Meter Id"): METER_ID_1 | METER_ID_2
// READING_FILENAME_ID = METER_ID_1
// Interval Data (Load Profile): NONE | ALL
//LOAD_PROFILE_MODE = ALL
// Reader Notes. Could contain a multi-line note e.g. C"12345 \x0A 67890".
//READER_NOTES = ""
//****************************************************************************
//************ IP AxisLink Diagnostic Read Task ******************************
//****************************************************************************
//[TASK="IPALDiagRead"] // "Diagnostic Read - IPAL"
// Reading file Storage Mode: NONE | APPEND | REPLACE
//STORAGE_MODE = REPLACE
// Reading MSR file storage folder. MSR file is saved to /Diagnostic subfolder.
//READING_STORAGE_FOLDER = "./"
// Reading Filename ID (ID1 aka "Account" or ID2 aka "Meter Id"): METER_ID_1 | METER_ID_2
// READING_FILENAME_ID = METER_ID_1
// Event Log Data: NONE | ALL
//EVENT_LOG = ALL
// Gatekeeper Data: STATUS_ONLY | ALL
//LAN_BOARD_DATA = STATUS_ONLY
// Reader Notes. Could contain a multi-line note e.g. C"12345 \x0A 67890".
//READER_NOTES = ""

A3 ALPHA METER AND A1800 ALPHA METER READING


TASK PARAMETERS

TASK
The TASK parameter specifies the kind of reading to perform.
 BillingRead - Obtains information from the requested A3
ALPHA/A1800 ALPHA meter. Basic data-altering activity is
allowed relating to billing data is allowed.
 DiagnosticRead - Obtains information from the requested A3
ALPHA/A1800 ALPHA meter without the possibility of altering the
data within the meter, performing a demand reset, or updating
any of the log/data set unread markers. A diagnostic read will
not clear statuses or change the time.
Example: TASK = "BillingRead"

STORAGE_MODE
The STORAGE_MODE parameter specifies how the generated reading
file (.msr) can be stored on the PC.
 NONE - No stored reading file is created.

 APPEND - A new stored reading file is created with each read. No


data is overwritten. This is the default storage mode for a billing
read task.

26
MetercatLite user guide

 REPLACE - A new stored reading file overwrites the most recent


stored reading file for the same meter. This is the default storage
mode for a diagnostic read task.
Example: STORAGE_MODE = REPLACE

READING_STORAGE_FOLDER
Using the READING_STORAGE_FOLDER parameter, you can specify the
folder that the billing readings and diagnostic readings will be stored
in. You can select the same folder that the MetercatLite.exe file is
located in; or, you may specify any valid, existing, and accessible
path (that is, you must have sufficient privileges in the existing folder
to save the .msr file).
 Example 1: To select the same folder that MetercatLite.exe is
located in: READING_STORAGE_FOLDER = "./"
 Example 2: To specify any folder using its complete path:
READING_STORAGE_FOLDER = "c:/path/folder"

Note: MetercatLite uses the forward slash / character.


MetercatLite will automatically create up to 2 subfolders in the
READING_STORAGE_FOLDER location. The Billing subfolder is used to
store billing read files, and the Diagnostic subfolder is used to store
diagnostic read files.

READING_FILENAME_ID
The READING_FILENAME_ID parameter determines how the stored
reading gets its name. Metercat (and MetercatLite) supports two ID
parameters used in reports and by the PC for identifying the meter.
By default, the values are used as follows:
 METER_ID_1 is used to identify the account number

 METER_ID_2 is used for the meter ID. For more information


regarding these parameters
See the Metercat documentation for more information on the Site ID
labels.
Example: READING_FILENAME_ID = METER_ID_1

LOAD PROFILING PARAMETERS


The load profiling parameters control how data is read and handled.
You can choose either LOAD_PROFILE_MODE to select a generic range
of load profiling records or LOAD_PROFILE_DAYS to select a specific
number of days.

LOAD_PROFILE_MODE parameters:
 NONE - does not read or store load profiling data

 ALL - All load profiling data is read

 UNREAD - Only load profiling data that is marked as "unread" will


be read.

27
Parameters

 UNREAD_WITH_UPDATE - Only load profiling data that is marked as


"unread" will be read; the unread marker will be updated to
indicate that the load profiling data up to this point has been
read. UNREAD_WITH_UPDATE is only available if you are
performing a billing read.
Example: LOAD_PROFILE_MODE = ALL

LOAD_PROFILE_DAYS parameters:
You may specify the number of days from 1 to 999.
Example: LOAD_PROFILE_DAYS = 30

INSTRUMENTATION PROFILING PARAMETERS


The instrumentation profiling parameters control how data is read
and handled. You can choose either
INSTRUMENTATION_PROFILE_MODE to select a generic range of
instrumentation profiling records or INSTRUMENTATION_PROFILE_DAYS
to select a specific number of days.

INSTRUMENTATION_PROFILE_MODE parameters:
 NONE - Does not read or store instrumentation profiling data

 ALL - All instrumentation profiling data is read

 UNREAD - Only instrumentation profiling data that is marked as


"unread" will be read.
 UNREAD_WITH_UPDATE - Only instrumentation profiling data that is
marked as "unread" will be read; the unread marker will be
updated to indicate that the instrumentation profiling data up to
this point has been read. UNREAD_WITH_UPDATE is only
available if you are performing a billing read.
Example: INSTRUMENTATION_PROFILE_MODE = ALL

INSTRUMENTATION_PROFILE_DAYS parameters:
You may specify the number of days from 1 to 999.
Example: INSTRUMENTATION_PROFILE_DAYS = 30

LOG AND DATA SET PARAMETERS


You can control how the data from the following logs and data sets
are handled:
 HISTORY_LOG

 EVENT_LOG

 PQM_SAG_LOGS

 SELF_READ_DATA

 HARMONIC_DATA
You can specify one of the following values for each of the logs and
data sets:

28
MetercatLite user guide

 ALL - All of the log's or data set's data is read

 NONE - Does not read or store the data

Example: HARMONIC_DATA = NONE

LAN_BOARD_DATA
If the meter is installed with a gatekeeper module or an EA_NIC
option board, you can control how the board's data is handled using
LAN_BOARD_DATA.

 STATUS_ONLY - only the status information is returned with the


reading.
 ALL - all of the board's data is read and returned with the
reading.
Example: LAN_BOARD_DATA = STATUS_ONLY

READER_NOTES
The READER_NOTES parameter allows you to store a multi-line note in
the reading. To embed special characters in a string-type parameter,
you must prefix the string with C and use the backslash \ before the
special character.
Example: C"12345 \x0A 67890"
The example results in the following being stored in the reading as a
multi-line note:
12345
67890

TIME_DIFF_LIMIT
You can control whether a warning is generated if the meter's time is
off by the specified value. You must specify the
TIME_DIFF_LIMIT.HOUR (from 0 to 23) and the
TIME_DIFF_LIMIT.MINUTE (0 to 59).

 If these parameters are not set, the reading does not check the
meter's time.
 If these parameters are both set to 0, the reading will generate a
warning if the meter's time is off by any value.
Example:
 TIME_DIFF_LIMIT.HOUR = 1

 TIME_DIFF_LIMIT.MINUTE = 15
In the example, a warning is reported if the meter's time differs for
more than 75 minutes.

PERFORM_DEMAND_RESET
If you are performing a billing read, PERFORM_DEMAND_RESET specifies
whether the reading will also initiate a demand reset.

29
Parameters

 TRUE - The billing read will perform a demand reset.

 FALSE - No demand reset will be performed.

Example: PERFORM_DEMAND_RESET = FALSE

TIME SYNCH MODE


If you are performing a billing read, the TIME_SYNCH_MODE specifies
when a meter time adjustment is handled.
 NEVER - A billing read will never adjust the meter time.

 ALWAYS - A billing read will always adjust the meter time.

 IN_RANGE - A billing read will only adjust the meter time if the
error is within a specified range. If the meter time error is outside
the range, the billing read will contain a warning; however, the
time is not adjusted.
Example: TIME_SYNCH_MODE = IN_RANGE
If you are specifying a range, you must specify the low end of the
range (in hours and minutes) and the high end of the range (in hours
and minutes). Meter time is synchronized with the PC time if the time
difference is in the range TIME_SYNCH_LOW_BOUND <= Meter PC time
difference <= TIME_SYNCH_HIGH_BOUND.
 TIME_SYNCH_LOW_BOUND.HOUR - Must be a value between 0 and
23
 TIME_SYNCH_LOW_BOUND.MINUTE - Must be a value between 0 and
59
 TIME_SYNCH_HIGH_BOUND.HOUR - Must be a value between 0 and
23
 TIME_SYNCH_HIGH_BOUND.MINUTE - Must be a value between 0
and 59

REXUNIVERSAL METER READING TASK PARAMETERS

TASK
The TASK parameter specifies the kind of reading to perform.
 REXUBillingRead- Obtains information from the requested
REXUniversal meter. Basic data-altering activity is allowed
relating to billing data is allowed.
 REXUDiagRead - Obtains information from the requested
REXUniversal meter without the possibility of altering the data
within the meter, performing a demand reset, or updating any of
the log/data set unread markers. A diagnostic read will not clear
statuses or change the time.
Example: TASK = "REXUBillingRead"

30
MetercatLite user guide

STORAGE_MODE
The STORAGE_MODE parameter specifies how the generated reading
file (.msr) can be stored on the PC.
 APPEND - A new stored reading file is created with each read. No
data is overwritten. This is the default storage mode for a billing
read task.
 REPLACE - A new stored reading file overwrites the most recent
stored reading file for the same meter. This is the default storage
mode for a diagnostic read task.
Example: STORAGE_MODE = REPLACE

READING_STORAGE_FOLDER
Using the READING_STORAGE_FOLDER parameter, you can specify the
folder that the billing readings and diagnostic readings will be stored
in. You can select the same folder that the MetercatLite.exe file is
located in; or, you may specify any valid, existing, and accessible
path (that is, you must have sufficient privileges in the existing folder
to save the .msr file).
 Example 1: To select the same folder that MetercatLite.exe is
located in: READING_STORAGE_FOLDER = "./"
 Example 2: To specify any folder using its complete path:
READING_STORAGE_FOLDER = "c:/path/folder"

Note: MetercatLite uses the forward slash / character.


MetercatLite will automatically create up to 2 subfolders in the
READING_STORAGE_FOLDER location. The Billing subfolder is used to
store billing read files, and the Diagnostic subfolder is used to store
diagnostic read files.

READING_FILENAME_ID
The READING_FILENAME_ID parameter determines how the stored
reading gets its name. Metercat (and MetercatLite) supports two ID
parameters used in reports and by the PC for identifying the meter.
By default, the values are used as follows:
 METER_ID_1 is used to identify the account number

 METER_ID_2 is used for the meter ID. For more information


regarding these parameters
See the Metercat documentation for more information on the Site ID
labels.
Example: READING_FILENAME_ID = METER_ID_1

LOG AND DATA SET PARAMETERS


You can control how the data from the following logs and data sets
are handled. Note that for load profile and instrumentation profile
data, the parameters are named slightly differently than the
remaining log and data set parameters.

31
Parameters

 LOAD_PROFILE_MODE

 INSTRUMENTATION_PROFILE_MODE

 EVENT_LOG

 SELF_READ_DATA
You can specify one of the following values for each of the logs and
data sets:
 ALL - All of the log's or data set's data is read

 NONE - Does not read or store the data

Example: LOAD_PROFILE_MODE = ALL

READER_NOTES
The READER_NOTES parameter allows you to store a multi-line note in
the reading. To embed special characters in a string-type parameter,
you must prefix the string with C and use the backslash \ before the
special character.
Example: C"12345 \x0A 67890"
The example results in the following being stored in the reading as a
multi-line note:
12345
67890

PERFORM_DEMAND_RESET
If you are performing a billing read, PERFORM_DEMAND_RESET specifies
whether the reading will also initiate a demand reset.
 TRUE - The billing read will perform a demand reset.

 FALSE - No demand reset will be performed.

Example: PERFORM_DEMAND_RESET = FALSE

REX2 METER READING TASK PARAMETERS

TASK
For the REX2 meter, the TASK can only be a diagnostic read. Billing
reads are not supported.
 REXDiagRead - Obtains information from the requested REX2
meter without the possibility of altering the data within the
meter, performing a demand reset, or updating any of the
log/data set unread markers. A diagnostic read will not clear
statuses or change the time.
Example: TASK = "REXDiagRead"

STORAGE_MODE
The STORAGE_MODE parameter specifies how the generated reading
file (.msr) can be stored on the PC.

32
MetercatLite user guide

 NONE - No stored reading file is created.

 APPEND - A new stored reading file is created with each read. No


data is overwritten. This is the default storage mode for a billing
read task.
 REPLACE - A new stored reading file overwrites the most recent
stored reading file for the same meter. This is the default storage
mode for a diagnostic read task.
Example: STORAGE_MODE = REPLACE

READING_STORAGE_FOLDER
Using the READING_STORAGE_FOLDER parameter, you can specify the
folder that the billing readings and diagnostic readings will be stored
in. You can select the same folder that the MetercatLite.exe file is
located in; or, you may specify any valid, existing, and accessible
path (that is, you must have sufficient privileges in the existing folder
to save the .msr file).
 Example 1: To select the same folder that MetercatLite.exe is
located in: READING_STORAGE_FOLDER = "./"
 Example 2: To specify any folder using its complete path:
READING_STORAGE_FOLDER = "c:/path/folder"

Note: MetercatLite uses the forward slash / character.


MetercatLite will automatically create up to 2 subfolders in the
READING_STORAGE_FOLDER location. The Billing subfolder is used to
store billing read files, and the Diagnostic subfolder is used to store
diagnostic read files.

READING_FILENAME_ID
The READING_FILENAME_ID parameter determines how the stored
reading gets its name. Metercat (and MetercatLite) supports two ID
parameters used in reports and by the PC for identifying the meter.
By default, the values are used as follows:
 METER_ID_1 is used to identify the account number

 METER_ID_2 is used for the meter ID. For more information


regarding these parameters
See the Metercat documentation for more information on the Site ID
labels.
Example: READING_FILENAME_ID = METER_ID_1

LOAD_PROFILE_MODE
The LOAD_PROFILE_MODE parameter controls how the data from
interval data.
 ALL - All of the interval data is read

 NONE - Does not read or store the data

Example: LOAD_PROFILE_MODE = ALL

33
Parameters

READER_NOTES
The READER_NOTES parameter allows you to store a multi-line note in
the reading. To embed special characters in a string-type parameter,
you must prefix the string with C and use the backslash \ before the
special character.
Example: C"12345 \x0A 67890"
The example results in the following being stored in the reading as a
multi-line note:
12345
67890

IP AXISLINK ROUTER READING TASK PARAMETERS

TASK
For the IP AxisLink router, the TASK can only be a diagnostic read.
Billing reads are not supported.
 IPALDiagRead - Obtains information from the requested IP
AxisLink router without the possibility of altering the data within
the meter. A diagnostic read will not clear statuses or change the
time.
Example: TASK = "IPALDiagRead"

STORAGE_MODE
The STORAGE_MODE parameter specifies how the generated reading
file (.msr) can be stored on the PC.
 NONE - No stored reading file is created.

 APPEND - A new stored reading file is created with each read. No


data is overwritten. This is the default storage mode for a billing
read task.
 REPLACE - A new stored reading file overwrites the most recent
stored reading file for the same meter. This is the default storage
mode for a diagnostic read task.
Example: STORAGE_MODE = REPLACE

READING_STORAGE_FOLDER
Using the READING_STORAGE_FOLDER parameter, you can specify the
folder that the billing readings and diagnostic readings will be stored
in. You can select the same folder that the MetercatLite.exe file is
located in; or, you may specify any valid, existing, and accessible
path (that is, you must have sufficient privileges in the existing folder
to save the .msr file).
 Example 1: To select the same folder that MetercatLite.exe is
located in: READING_STORAGE_FOLDER = "./"
 Example 2: To specify any folder using its complete path:
READING_STORAGE_FOLDER = "c:/path/folder"

34
MetercatLite user guide

Note: MetercatLite uses the forward slash / character.


MetercatLite will automatically create up to 2 subfolders in the
READING_STORAGE_FOLDER location. The Billing subfolder is used to
store billing read files, and the Diagnostic subfolder is used to store
diagnostic read files.

READING_FILENAME_ID
The READING_FILENAME_ID parameter determines how the stored
reading gets its name. Metercat (and MetercatLite) supports two ID
parameters used in reports and by the PC for identifying the meter.
By default, the values are used as follows:
 METER_ID_1 is used to identify the account number

 METER_ID_2 is used for the meter ID. For more information


regarding these parameters
See the Metercat documentation for more information on the Site ID
labels.
Example: READING_FILENAME_ID = METER_ID_1

LAN_BOARD_DATA
If the IP AxisLink router is installed with a gatekeeper module, you
can control how the board's data is handled using LAN_BOARD_DATA.
 STATUS_ONLY - only the status information is returned with the
reading.
 ALL - all of the board's data is read and returned with the
reading.
Example: LAN_BOARD_DATA = STATUS_ONLY

READER_NOTES
The READER_NOTES parameter allows you to store a multi-line note in
the reading. To embed special characters in a string-type parameter,
you must prefix the string with C and use the backslash \ before the
special character.
Example: C"12345 \x0A 67890"
The example results in the following being stored in the reading as a
multi-line note:
12345
67890

35
Parameters

DLMS protocol parameters


Note: For use in the A1800 ALPHA meter only
The following parameters are applied only if programmed Remote
Component has "DLMS and ANSI" Protocol Type option.

DLMS_PHYSICAL_ADDRESS
A number in range of 16 to 16382
Example: DLMS_PHYSICAL_ADDRESS = 16

DLMS_PASSWORD
When DLMS_PASSWORD parameter is commented out, then DLMS
password is not programmed in the meter i.e. DLMS password in the
meter is left unchanged.
DLMS password is up to 20 binary bytes, where each character must
be entered in a hex notation, one byte as 2 hex characters.
If entered password has fewer characters than max allowed, then it
is padded with ANSI space characters (0x20 or "20" hex) string up to
40 characters (0-9/A-F).
Example: DLMS_PASSWORD = ""

36
MetercatLite user guide

Alternative time setting parameters


TIME_ZONE_OFFSET
To use system time and time zone, you must comment out all of the
following parameters:
 TIME_ZONE_OFFSET

 DST_OFFSET

 DST_SWITCH_TIME.HOUR

 DST_SWITCH_TIME.MINUTE
Example: TIME_ZONE_OFFSET = 0 // -780 to 780 minutes (-13 to
13 hours) must be divisible by 5 minutes

DST_OFFSET
Daylight Saving Time (DST) offset used by the area.
Example: DST_OFFSET = 60 // 0 to 180 minutes (0 to 3 hours)
must be divisible by 5 minutes

DST_SWITCH_TIME.HOUR
Hour at which DST goes into effect.
Example: DST_SWITCH_TIME.HOUR = 2 // 0 to 23

DST_SWITCH_TIME.MINUTE
Minute at which DST goes into effect.
Example: DST_SWITCH_TIME.MINUTE = 0 // 0 to 59

37
Appendix

Time zones
When specifying the time zone for use in MetercatLite, the following
list specifies the valid values that can be used:
 Afghanistan Standard Time
 Alaskan Standard Time
 Arab Standard Time
 Arabian Standard Time
 Arabic Standard Time
 Armenian Standard Time
 Atlantic Standard Time
 AUS Central Standard Time
 AUS Eastern Standard Time
 Azerbaijan Standard Time
 Azores Standard Time
 Canada Central Standard Time
 Cape Verde Standard Time
 Caucasus Standard Time
 Cen. Australia Standard Time
 Central America Standard Time
 Central Asia Standard Time
 Central Brazilian Standard Time
 Central Europe Standard Time
 Central European Standard Time
 Central Pacific Standard Time
 Central Standard Time
 Central Standard Time (Mexico)
 China Standard Time
 Dateline Standard Time
 E. Africa Standard Time

39
Appendix

 E. Australia Standard Time


 E. Europe Standard Time
 E. South America Standard Time
 Eastern Standard Time
 Egypt Standard Time
 Ekaterinburg Standard Time
 Fiji Standard Time
 FLE Standard Time
 Georgian Standard Time
 GMT Standard Time
 Greenland Standard Time
 Greenwich Standard Time
 GTB Standard Time
 Hawaiian Standard Time
 India Standard Time
 Iran Standard Time
 Jerusalem Standard Time
 Jordan Standard Time
 Korea Standard Time
 Mexico Standard Time
 Mexico Standard Time 2
 Mid-Atlantic Standard Time
 Middle East Standard Time
 Montevideo Standard Time
 Mountain Standard Time
 Mountain Standard Time (Mexico)
 Myanmar Standard Time
 N. Central Asia Standard Time
 Namibia Standard Time
 Nepal Standard Time
 New Zealand Standard Time
 Newfoundland Standard Time
 North Asia East Standard Time
 North Asia Standard Time
 Pacific SA Standard Time

40
MetercatLite user guide

 Pacific Standard Time


 Pacific Standard Time (Mexico)
 Romance Standard Time
 Russian Standard Time
 SA Eastern Standard Time
 SA Pacific Standard Time
 SA Western Standard Time
 Samoa Standard Time
 SE Asia Standard Time
 Malay Peninsula Standard Time
 South Africa Standard Time
 Sri Lanka Standard Time
 Taipei Standard Time
 Tasmania Standard Time
 Tokyo Standard Time
 Tonga Standard Time
 US Eastern Standard Time
 US Mountain Standard Time
 Venezuela Standard Time
 Vladivostok Standard Time
 W. Australia Standard Time
 W. Central Africa Standard Time
 W. Europe Standard Time
 West Asia Standard Time
 West Pacific Standard Time
 Yakutsk Standard Time

41
Legal notices

Trademarks
Metercat, AlphaPlus, ALPHA, ALPHA Plus, REX, REX2, REXUniversal,
IP AxisLink, EnergyAxis are trademarks and/or registered trademarks
of Elster.
All other product names may be trademarks and/or registered
trademarks of their respective owners.

Copyright
No part of this software or documentation may be reproduced,
transmitted, processed, or recorded by any means or form, electronic
mechanical, photographic, translated to another language, or be
released to any third party without the express written consent of
Elster.
© 2015 by Elster. All rights reserved.

Generated
Last generated & updated: 04 June 2015 at 16:23

43
Elster Solutions © 2015 by Elster. All rights reserved.
208 S Rogers Lane Information herein is subject to change without notice.
Raleigh, NC 27610-2144 Product specifications cited may change. Contact your
Elster representative for the most current product
information.

You might also like