Protomont Nsshoeu 1KV - 0
Protomont Nsshoeu 1KV - 0
Protomont Nsshoeu 1KV - 0
Application
For flexible use and fixed installation open-cast mining applications, in quarries, on construction sites and similar applications, with heavy
mechanical stresses. The cables can be used indoors as well as outdoors, in explosion-hazard areas, in industry and in agriculture. They can be
used permanently in waste water up to 40°C at a depth of max. 2000 m and in industrial water, cooling water, surface water, rainwater and mixed
water - and in groundwater and seawater to a more limited extent. The requirements for accessibility and inspection depend on the consistency
of the water.In aggressive water or composed of special substances, the cable's resistance properties should be tested. In other respects the
specifications of DIN VDE 0298 part 3 applies.
Global data
Brand PROTOMONT
Type designation NSSHOEU
Standard DIN VDE 0250-812
Certifications / Approvals MA – China
MSHA P-189-3
Fire Certificate of Russian Federation
TR-Certificate
GOST K
GOST B
Notes on installation
Notes on installation Maximum submersing depth 2000 meters
Design features
Conductor Copper, tinned, finely stranded (class 5) in accordance with DIN EN 60228 / IEC 60228
Insulation PROTOLON, Basic material: EPR, Compound type: 3GI3 in accordance with DIN EN 50363
Core identification Up to 5 cores: colored in gray, black, brown, blue, green/yellow
from 6 cores: light gray with black digits
Core arrangement Three main conductors laid-up together with the protective-earth conductor, from 50 mm² with
protective-earth conductor split into three in the outer interstices
Inner sheath Vulcanized rubber compound, Basic material: EPR, Compound type: GM1B in accordance with DIN
EN 50363 (not for single-core cables)
Outer sheath Vulcanized rubber compound, synthetic elastomer compound e.g. CPE, Compound: 5GM5 in
accordance with DIN EN 50363, Color: Yellow
Electrical parameters
Rated voltage 0.6/1 kV (600/1000V)
Max. permissible operating voltage AC 0.7/1.2 kV
Max. permissible operating voltage DC 0.9/1.8 kV
AC test voltage - main cores 3 kV (5 Min.)
Chemical parameters
Reaction to fire DIN EN 60332-1-2
Resistance to oil DIN EN 60811-404
Weather resistance Unrestricted use outdoors and indoors, resistant to ozone and moisture
Water resistance DIN EN 50525-2-21
Thermal parameters
Max. permissible temperature at conductor 90 °C
Max. short circuit temperature of the conductor 250 °C
Max. permissible water temperature 40 °C (At higher water temperatures, a shortened cable service life is to be expected)
Ambient temperature for fixed installation min -40 °C ; max +80 °C
Ambient temperature in fully flexible operation min -25 °C ; max +60 °C
Mechanical parameters
Max. tensile load on the conductor 15 N/mm²
Torsional stress +/- 100 °/m
Min. bending radius Acc. to DIN VDE 0298 part 3
PROTOMONT NSSHOEU 0,6/1 kV Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
Revision: 14. Mar 2018 Austraße 99 96465 Neustadt b. Coburg subject to change.
phone.: +49 30 3675 40 © Prysmian Group, Germany 2015
email: [email protected] www.prysmiangroup.com
Number of cores x Part Conduc- Outer Outer Bending Bending Weight Con- Nominal Induc- Current Short
cross section number tor diameter diameter radius radius (approx.) ductor operating tance carrying Circuit
diameter min. max. fixed free kg/km resis- capacitance nom. capacity Current
max. mm mm min. moving tance µF/km mH/ (1) (conduc-
mm mm min. at 20°C km A tor)
mm max. max.
Ω/km (1s)
kA
PROTOMONT
NSSHÖU-O 1x…
1x16 20004811 5.4 10.6 11.6 235 1.21 0.42 0.26 103 2.29
1x25 20008654 6.3 12.8 14 56 70 355 0.7839 0.42 0.26 137 3.58
1x35 20004812 7.4 13.9 15.1 60 76 450 0.554 0.49 0.25 169 5.01
1x50 20004813 8.8 15.6 17.1 68 86 610 0.386 0.51 0.25 211 7.15
1x70 20004814 10.6 17.7 19.2 77 96 825 0.272 0.59 0.24 261 10.01
1x95 20004815 12.1 19.7 21.2 85 106 1050 0.206 0.6 0.24 314 13.59
1x120 20004816 14.3 22.4 23.9 96 120 1360 0.161 0.69 0.23 367 17.16
1x150 20004817 15.9 24.4 25.9 104 130 1640 0.129 0.69 0.23 422 21.45
1x185 20069571 17.5 27.2 29.4 118 147 2040 0.106 0.68 0.23 481 26.46
1x240 20004818 20.3 30.4 32.6 130 163 2600 0.0801 0.73 0.23 571 34.32
1x300 20004819 23.1 34.6 36.8 147 184 3270 0.0641 0.76 0.23 681 42.9
1x400 20154805 26.2 38.5 40.5 4210 0.0486 0.76 0.24 828 57.2
PROTOMONT
NSSHÖU-O 2x…
2x1,5 20004826 1.6 10.6 12.2 49 61 160 13.3 0.22 0.33 23 0.21
2x2,5 20008593 1.9 11.7 13.3 53 67 205 7.98 0.23 0.32 30 0.36
2x4 2.4 14.5 16.5 66 83 295 4.95 0.26 0.31 41 0.57
PROTOMONT
NSSHÖU-O 3x…
3x1,5 1.6 11.1 12.7 51 64 180 13.3 0.22 0.33 23 0.21
3x2,5 20004872 1.9 12.2 13.8 55 69 230 7.98 0.23 0.32 30 0.36
3x4 2.4 14.7 16.7 67 84 340 4.95 0.26 0.31 41 0.57
3x6 2.9 15.7 17.7 71 89 415 3.3 0.3 0.29 53 0.86
3x10 20141441 3.9 20 21.1 89 112 650 1.91 0.32 0.28 74 1.43
3x16 5.4 23.1 25.1 100 126 890 1.21 0.42 0.26 99 2.29
3x25 20004897 6.3 26.8 28.5 116 146 1300 0.784 0.42 0.26 131 3.58
3x35 20004837 7.5 29.9 32.9 132 165 1730 0.554 0.49 0.25 162 5.01
3x50 20148227 8.9 35.2 38.3 2400 0.386 0.55 0.27 202 7.15
3x70 20008777 10.6 39.1 42.1 3820 0.272 0.57 0.28 250 10.01
PROTOMONT
NSSHÖU-J 3x…
3x1,5 20004827 1.6 11.1 12.7 51 64 180 13.3 0.22 0.33 23 0.21
3x2,5 20004828 1.9 12.2 13.8 55 69 230 7.98 0.23 0.32 30 0.36
3x4 20007174 2.4 15.2 17.2 69 86 340 4.95 0.26 0.31 41 0.57
3x6 2.9 16.6 18.6 74 93 415 3.3 0.3 0.29 53 0.86
PROTOMONT
NSSHÖU-O 4x…
4x1,5 20085843 1.6 12 13.1 210 13.3 0.22 0.33 23 0.21
PROTOMONT
NSSHÖU-J 4x…
4x1,5 20004838 1.6 11.8 13.4 54 67 210 13.3 0.22 0.33 23 0.21
4x2,5 20004839 1.9 14.1 16.1 64 81 310 7.98 0.23 0.32 30 0.36
4x4 20004840 2.4 15.7 17.7 71 89 410 4.95 0.26 0.31 41 0.57
4x6 20004841 2.9 16.9 18.9 76 95 500 3.3 0.3 0.29 53 0.86
4x10 20004842 3.9 21.1 23.1 92 116 800 1.91 0.32 0.28 74 1.43
4x16 20004843 5.4 25.9 27.6 113 141 1160 1.21 0.42 0.26 99 2.29
4x16+4x2,5 20004871 5.4 27.1 30.1 1433 1.21 0.42 0.26 99 2.29
4x25 20004844 6.3 29.8 32.8 131 164 1700 0.7839 0.42 0.26 131 3.58
PROTOMONT NSSHOEU 0,6/1 kV Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
Revision: 14. Mar 2018 Austraße 99 96465 Neustadt b. Coburg subject to change.
phone.: +49 30 3675 40 © Prysmian Group, Germany 2015
email: [email protected] www.prysmiangroup.com
Number of cores x Part Conduc- Outer Outer Bending Bending Weight Con- Nominal Induc- Current Short
cross section number tor diameter diameter radius radius (approx.) ductor operating tance carrying Circuit
diameter min. max. fixed free kg/km resis- capacitance nom. capacity Current
max. mm mm min. moving tance µF/km mH/ (1) (conduc-
mm mm min. at 20°C km A tor)
mm max. max.
Ω/km (1s)
kA
4x25+1x(4x1,5)ST 20220185 6.3 32.4 35.4 2000 0.784 0.42 0.26 131 3.58
4x35 20004845 7.5 32.7 35.7 143 179 2150 0.554 0.49 0.25 162 5.01
4x50 20004846 8.8 38.1 41.1 164 206 2980 0.386 0.51 0.25 202 7.15
4x70 20004847 10.6 42.1 45.1 180 226 3910 0.272 0.59 0.24 250 10.01
4x95 20004848 12.1 48.2 52.2 209 261 5120 0.206 0.6 0.24 301 13.59
4x120 20016763 14.2 54.6 58.6 234 293 6570 0.161 0.69 0.23 352 17.16
4x150 20023637 16.1 60.8 64.8 259 324 7990 0.129 0.7 0.23 404 21.45
4x185 20007494 17.9 67.3 71.3 285 357 9820 0.106 0.71 0.23 461 26.46
4x240 20060343 20.3 73.7 77.7 311 389 12100 0.0801 0.73 0.23 547 34.32
PROTOMONT
NSSHÖU-J 3x…/…
3x50/25 20004863 8.8 38.4 41.4 166 207 2820 0.386 0.51 0.25 202 7.15
3x70/35 20004864 10.6 42.3 45.3 181 227 3670 0.272 0.59 0.24 250 10.01
3x95/50 20004865 12.1 48.1 52.1 208 261 4840 0.206 0.6 0.24 301 13.59
3x120/70 20004866 14.2 54.6 58.6 234 293 6250 0.161 0.69 0.23 352 17.16
3x150/70 20004868 16.1 60 64 256 320 7500 0.129 0.7 0.23 404 21.45
3x185/95 20004867 17.9 67.3 71.3 285 357 9290 0.106 0.71 0.23 461 26.46
3x240/120 20196331 20.2 73 77 11000 0.08 0.73 0.23 547 34.32
PROTOMONT
NSSHÖU-J 3x…
+3x.../3
3x185+3x95/3 17.9 60.7 64.7 259 324 8690 0.106 0.71 0.23 461 26.46
PROTOMONT
NSSHÖU-J 5x…
5x1,5 20004855 1.6 12.7 14.3 57 72 245 13.3 0.22 0.33 23 0.21
5x2,5 20004856 1.9 15.2 17.2 69 86 360 7.98 0.23 0.32 30 0.36
5x4 20004857 2.4 17 19 76 95 475 4.95 0.26 0.31 41 0.57
5x6 20004858 2.9 19.1 21.1 84 106 625 3.3 0.3 0.29 53 0.86
5x10 20004859 3.9 23 25 100 125 955 1.91 0.32 0.28 74 1.43
5x16 20004860 5.4 27.4 30.4 122 152 1380 1.21 0.42 0.26 99 2.29
5x25 20004861 6.3 32.4 35.4 142 177 2030 0.7839 0.42 0.26 131 3.58
5x35 20006970 7.5 36.9 39.9 160 200 2700 0.554 0.49 0.25 162 5.01
5x70 20024963 10.6 47 51 5000 0.272 0.57 0.24 202 7.15
5x95 20023910 12.1 53.4 57.4 6325 0.206 0.65 0.24 250 10.01
5x120 20023647 14.1 59.6 63.6 7980 0.161 0.68 0.24 352 17.16
5x185 20211472 17.8 74.6 78.7 12010 0.106 0.71 0.23 461 26.46
5x240 20062184 20.2 79.9 84.9 15160 0.08 0.73 0.23 547 34.32
PROTOMONT
NSSHÖU-J …x1,5
7x1,5 20004891 1.6 15.2 17.2 69 86 365 13.3 0.22 0.33 15 0.21
8x1,5 20004890 1.6 16.6 18.6 74 93 410 13.3 0.22 0.33 14 0.21
10x1,5 20004886 1.6 17.7 19.7 79 99 455 13.3 0.22 0.33 13 0.21
12x1,5 20023911 1.6 17.7 25 540 20.3 0.22 0.33 13 0.21
7x10+5x1,5ST 20004896 3.9 26 29 1420 1.91 0.33 0.28 28 1.43
19x1,5 20023912 1.6 17.7 21.7 760 23.7 0.22 0.33 13 0.21
24x1,5 20088402 1.6 24.3 27.3 109 137 920 13.3 0.22 0.33 9 0.21
PROTOMONT
NSSHÖU-J …x2,5
7x2,5 20004887 1.9 17.4 19.4 78 97 485 7.98 0.24 0.32 19 0.36
10x2,5 20174408 2 20.4 21.4 92 115 630 7.98 0.24 0.32 16 0.36
PROTOMONT NSSHOEU 0,6/1 kV Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
Revision: 14. Mar 2018 Austraße 99 96465 Neustadt b. Coburg subject to change.
phone.: +49 30 3675 40 © Prysmian Group, Germany 2015
email: [email protected] www.prysmiangroup.com
Number of cores x Part Conduc- Outer Outer Bending Bending Weight Con- Nominal Induc- Current Short
cross section number tor diameter diameter radius radius (approx.) ductor operating tance carrying Circuit
diameter min. max. fixed free kg/km resis- capacitance nom. capacity Current
max. mm mm min. moving tance µF/km mH/ (1) (conduc-
mm mm min. at 20°C km A tor)
mm max. max.
Ω/km (1s)
kA
12x2,5 20004874 1.9 21.2 23.2 93 116 725 7.98 0.24 0.32 16 0.36
18x2,5 20004892 1.9 24.5 27.5 110 138 1035 7.98 0.24 0.32 13 0.36
19x2,5 20025547 2 26 28 1100 7.98 0.24 0.32 13 0.36
24x2,5 1.9 28.3 31.3 125 157 1320 7.98 0.23 0.32 12 0.36
PROTOMONT
NSSHÖU-J …x4
7x4 20059552 2.4 20.5 22.5 90 113 685 4.95 0.26 0.31 17 0.57
12x4 20040505 2.4 25.6 28.6 114 143 1030 4.95 0.26 0.31 21 0.57
PROTOMONT
NSSHÖU-J …x10
7x4+5x1,5ST 20004893 2.4 24.1 26.1 901 4.95 0.26 0.31 17 0.57
(1) Nominal current carrying capacity for multicore cable or three single-core cables in trefoil in permanent operation with DC or AC with 50 up to
60 Hz at 30°C ambient temperature, free in air, three cores loaded. (see also VDE 0298-4)
PROTOMONT NSSHOEU 0,6/1 kV Prysmian Kabel und Systeme GmbH Technical data, dimensions and weights are
Revision: 14. Mar 2018 Austraße 99 96465 Neustadt b. Coburg subject to change.
phone.: +49 30 3675 40 © Prysmian Group, Germany 2015
email: [email protected] www.prysmiangroup.com