Solid state audio-visual annunciator of minimum 12 windows shall
be provided however exact number of windows shall be finalised
during detailing. The annunciator shall be provided with flasher units, audible alarm, test, reset, Accept features as elaborated above. 15) Selection & control switches and other miscellaneous items All selection switches for voltage & current measurements shall be suitable for 3 phases and phase to neutral measurements. The remote/ local selector switches provided on the switchboard shall be lockable in each position. The control switches shall be pistol grip, spring loaded and trip-neutral-close type with sequence device. The switchgear and control panels shall have inscription plates for all panels with anodised lettering. Control bus shall be continuous copper conductors insulated throughout for full voltage. Push-in type insulation box shall be provided at tapping points. The control wiring in the switchgear shall be carried out with single core stranded copper conductor PVC cable of 1.5 sq. mm size (min.) with 6 sq. mm open type terminals. Protection circuit wiring shall be carried out with 2.5 sq. mm size (min.) copper conductor adopting 10 sq. mm open type terminals. Separate terminal blocks shall be provided for each voltage class and carry the specific terminal number and voltage indicated thereon. Separate terminal blocks shall be provided for external connections in the relay chamber. At least 20% spare terminals shall be provided for future purposes. Control cable terminations shall be provided in the front portion of the cubicle only in the relay chamber. All devices, wires and the terminal blocks within the panel shall be clearly identified by durable and legible tags (stickers shall not be acceptable) corresponding to those used in the applicable schematic drawings or wiring diagrams. All panels shall be provided with space heaters with ON/OFF switch along with a thermostat and a 10 amp. plug socket for hand lamp connection. Space heater wattage shall be mentioned for each panel. Inter-partition separators on control terminal block shall be provided for control terminals of each circuit breaker. Drive panels shall however be controlled from Drive end or its control panel. 16) Cable Chambers The cable end termination chamber for each panel shall have adequate space for the termination of required number, type and BSP PAGE 3.36 CET/01/BH/3981/TS/UT/R-5 SUPER ACCLRT. COOLING, PLATE MILL size of cables and shall be provided with suitable bracings to support the weight of the cables without undue stress on the terminals. These chambers shall be complete with all accessories and shall form integral part of the cubicle and shall be freely accessible for cable connection. 17) Following general features shall also be provided: Panels shall be painted with post office red colour. Mimic diagram shall be shown on the cubicle both sides. Nomenclature of the relays and meters shall be written on panel by paint (stickers shall not be used) 18) Other Accessories Supply of each of the HT Switchgear shall necessarily include the following accessories.
a) Earthing equipment suitable for 1 No. for line side &
earthing the bus/cable for each 1No.for bus side breaker b) Device for hand charging of 1 Lot breakers. c) Breaker rack in / rack out device. 1 set d) High voltage tester 1 no. f) Wheel mounted trolley for attending 02 nos relays & meters- g) Special device for ensuring 1 Set mechanical interlocks (if any) h) Special tools & tackles 1 Set
3.7.5.6 Remote Terminal Unit (RTU)
RTU shall have IEC 61850 protocol. RTU shall be suitable for all data transfer of the parameters for which meters have been provided and breaker ON, OFF, TRIP status. Type of the RTU shall be same as being procured by BSP under modernisation programme. Before finalisation of the offer, the bidder shall get the information from BSP about the type of RTU to be installed in the substation for new pump house. 3.7.5.7 415 V Switchgear BSP PAGE 3.37 CET/01/BH/3981/TS/UT/R-5 SUPER ACCLRT. COOLING, PLATE MILL Standards
The 415 V switchgear and the relevant components shall comply with the following standard specifications and to the specific Indian standards mentioned in the respective clauses:
IS / IPSS Code & Year Title
IS: 1248 (Part1-1993) (Part Direct acting indicating analogue electrical 2-6, 9-1983) (Part 7, 8- measuring instruments & their accessories 1984) IS: 2705-(Part 1-4)-1992 Current transformer IS: 3156-(Part 1-4)-1992 Voltage transformers IS: 3231(Part 1-3)-1992 Electrical Relays for power system protection IS: 5578 –1984 Guide for marking insulated conductor. IS: 11353-1985 Guide for uniform marking & identification of conductor and terminals IS: 8623 (Part 1-3)-1993 Low voltage switchgear and control gear assemblies. IS: 10118 (Part 1-4)-1982 Code of practice for Selection, installation and Maintenance of Switchgear and Control gear. IS: 11182 (Part 1,2-1984) Guide for evaluation of insulation system of (Part 3,5,6,7-1986) Electrical Equipment. IS: 13947(Part 1-5)-1993 Specification for LV switchgear and control gear
3.1.1.1 Technical parameters of 415 V Switchgear
S. Specific aspects Technical features
No. 1. Voltage 415 V + 10% 2. Phase 3 phase & Neutral 3. Frequency 50 Hz + 5% 4. Neutral system Solidly grounded 5. System Fault level 50 kA (RMS) for 1 second 6. Rated Insulation 2.5 kV for 1 min Voltage
BSP PAGE 3.38 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL S. Specific aspects Technical features No. 7. Duty Continuous operation 8. Construction 9. Type of board Single Front, Compartmentalised, modular & Drawout 10. Mounting Vertical, Floor mounted, Free standing 11. Sheet Steel type & Cold Rolled sheet steel, 2 mm & 1.6 mm thickness (for door). 12. Degree of protection IP 42 of enclosure 13. Front access Hinged door 14. Back access & Bolted coves; Back clearance- minimum clearance 800 mm 15. Future extension Provision on both side by addition of new provision vertical section 16. Cabling Space Side Cable Alley 18. Height of panels Maximum 2350 mm including base channel 19. Busbar arrangement Top horizontal 20. Power feed to Sleeved busbar droppers for connection outgoing modules of cables (bottom entry) 21. Power feed to Through sheet steel enclosed non incomers segregated phase bus ducts (top entry) 22. General features Shall have facilities to simplify inspection, testing, maintenance, cleaning at site without disrupting process / prolonged shutdowns 23. Busbar a) Main horizontal 3 Phase and neutral (RYBN) at top busbar b) Busbar Material (Make: Aluminium Alloy INDALCO/ HINDALCO) 24. Maximum 900C BSP PAGE 3.39 CET/01/BH/3981/TS/UT/R-5 SUPER ACCLRT. COOLING, PLATE MILL S. Specific aspects Technical features No. temperature rise including the specified ambient temperature and derating factor if any 25. Insulation Heat Shrunk PVC Sleeve. 26. Short time withstand 50 kA (RMS) for 1 sec current of Neutral Bus 27. Short time withstand 50 kA (RMS) for 1 sec current of earth bus 28. Earth busbar Galvanised steel earth Busbar of adequate size & running throughout the length of panels at bottom 29. Colour coding IS 5578: 1984 IS 11353: 1985 30. Clearance between 25 mm (minimum) Phase & Phase and Phase & Earth / Neutral
31. Air Circuit Breakers
a) Type Electrically operated with closing coil, tripping coil, motorised spring charging mechanism for all circuit breakers- incomers, Buscoupler & outgoing feeders. All breakers shall have direct acting adjustable microprocessor based releases for over current, short circuit & earth fault protection. b) Drawout type Yes c) Cubicle door can be Yes closed when ACB is in Isolated position d) Rated Interrupting 50 kA (RMS)
BSP PAGE 3.40 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL S. Specific aspects Technical features No. capacity (symmetrical) e) Rated making Current 105 kA peak f) Total Tripping time 100 milli second (adjustable)- typical g) Adjustable short Yes circuit releases h) Adjustable over load Yes releases i) Anti-pumping & trip All breakers shall have mechanical anti free features pumping and trip free features. For incomers and buscouplers, Electrical anti- pumping feature shall also be provided. j) Protection -For incomers Microprocessor based release shall be &buscoupler and provided in the ACBs for short circuit outgoing feeders protection , overload protection and earth fault protection with provision of signalling memorization till it is acknowledged. All ACBs shall have 240 V AC shunt trip releases. The setting range of short circuit protection shall have instantaneous setting facility.
-For Incomers In addition to above microprocessor
based protection release standby E/F protection shall be provided in Incomers only by using IDMTL relay self-powered CDG-11 relay of M/s Alstom Ltd. or equivalent approved make and neutral CT. 32. Metering a) Ammeter Ammeter with selector switch for incomers & all outgoing feeders b) Voltmeters Voltmeter with selector switch for incomers & phase healthy indication lamps for all three phases of incomers BSP PAGE 3.41 CET/01/BH/3981/TS/UT/R-5 SUPER ACCLRT. COOLING, PLATE MILL S. Specific aspects Technical features No. 33. Wiring a) Power Circuit Insulated (1.1 kV) Flexible Copper Wire/ strip b) Control circuit Copper 2.5 mm2 multi strand PVC wire, insulated c) Inter panel Wiring To be completed in each transportable Section. Provision for inter shipping section wiring shall be provided with complete termination facility 34. Control Transformer 2 nos. adequately rated with auto changeover switch (minimum 2 kVA each) 35. Indication lamps LED cluster All the indicting lamps should be of LVGP type (Low Volt Glow Protection) 36. CT & PT As required
37. Safety Shall be complete with approved safety
devices against hazards and provision for safe access of operation & maintenance personnel for operation & maintenance functions of equipment & components.
3.7.5.8 Motor Control Centre (MCC)
MCC shall be designed with two incoming Air Circuit Breaker (ACB) and buscoupler ACB. 20% spare feeders and minimum one spare feeder of each type shall be maintained in MCC. Technical Particulars
1. Reference Standards IS 60947 : 2004- Low Voltage
Switchgear and Control gear IS 8623 (Part 1-3): 1993- Low voltage switchgear and control gear assemblies 2. Supply system & variation Voltage 415 V+10%
BSP PAGE 3.42 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL Phase 3 & Neutral Frequency 50 Hz + 5% 3. Neutral system Solidly grounded 4. System Fault level 50 kA (RMS) for 1 second 5. Rated Insulation 2.5 kV for 1 min Voltage 6. Construction a) Type of board Single front compartmentalised & fixed type with components mounted on removable plate. b) Degree of IP-54 protection c) Mounting Vertical, Floor mounted, Free standing d) Front access Hinged door e) Back access & No back access clearance f) Future extension Provision on both side by addition of provision new vertical section. g) Sheet Steel type & Cold Rolled sheet steel, 2mm & 1.6 thickness mm (for door). h) Paint Shade No.631 (light grey) of IS 5: 1994 i) Cabling Space Side Cable Alley 7. Busbar a) Main horizontal 3 Phase and neutral (RYBN) busbar b) Busbar Material Aluminium Alloy c) Max. temp. rise 900C including the specified ambient temp. and derating factor if any d) Busbar Top horizontal arrangement
BSP PAGE 3.43 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL e) Power feed to Sleeved busbar dropper outgoing module f) Insulation Heat Shrunk PVC Sleeve g) Short time 50 kA (RMS) for 1 sec withstand current of Neutral Bus h) Short time 50 kA (RMS) for 1 sec withstand current of earth bus i) Colour coding IS 5578: 1984 IS 11353: 1985 j) Clearance between 25 mm (minimum) between Phase Phase & Phase and and phase and 19 mm ( min) between Phase & Earth / phase &earth/neutral Neutral 8. Component Details 8.1 Incomer ACB a) Draw out type Yes b) Cubicle door can be Yes closed when ACB is in Isolated position c) Deration of rating No duration for cubicle mounting and ambient temp. d) Rated Interrupting 50 kA (RMS) capacity (symmetrical) e) Rated making 150 kA peak Current f)Protection Overload, short circuit and earth fault protection through microprocessor based adjustable release. g) Under voltage trip Yes
BSP PAGE 3.44 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL 8.2 MCCB for incoming and outgoing feeders a) Rated Interrupting 50 kA (RMS) capacity (symmetrical) b) Current limiting Yes, for all motor feeders. type c) Capacity to protect Type 2 Co-ordination IS13947 (Part downstream 4/Sec 1): 1993 equipment 8.3 Contactors (Power) a) Utilisation Category AC3 for non-reversible feeders AC4 for all reversible feeder b) Coil voltage (VR) 240V AC V c) Drop out voltage 50 %VR d) Pick up 85-110 % VR e) Auxiliary Contacts 2 NO + 2 NC, 10A, 240 VAC. & rating 8.4 Wiring a) Power Circuit Insulated (1.1 kV) Flexible Copper Wire / strip b) Control circuit Copper 2.5 mm2 multi strand PVC wire, insulated 8.5 Control Transformer 2 nos. with auto changeover switch 8.6 Indication lamps LED cluster with luminous intensity min. 100 mcd. 8.7 CT & PT As required 8.8 Ammeter For incomer & all motor feeders 8.9 Voltmeters For incomer 8.10 Overload protection of EMPR for all motor feeders motor feeders
3.7.5.9 Power Distribution Board (PDB)
Power distribution board (PDB) shall be complete with MCCBs, Aluminium bus bar, ammeters & voltmeters, power & control terminal boards, clustered LED lamps for indications, necessary protections including power & control cables.
BSP PAGE 3.45 CET/01/BH/3981/TS/UT/R-5
SUPER ACCLRT. COOLING, PLATE MILL The PDBs shall meet the specifications given below:
Type Sheet steel clad, fully compartmentalized, non draw
out, indoor type, floor mounted, free standing conforming to IS 8623 (Part 1-3): 1993- Low voltage switchgear and control gear assemblies Enclosure IP54 Incomer 2 nos incomers and buscoupler of suitable rating MCCBs Outgoing MCCBs (no. & rating as required), 20% spare feeders feeders shall be provided. Busbars 3 ph, 4 wire, electrolytic grade Aluminium MCCBs All MCCBs shall be of 50kA breaking capacity with short circuit, overload and earth fault protection. Auxiliary loads The PDB shall meet the Power requirement of Air conditioning, ventilation, hoist, illumination, repair facilities, any other load as required at detail engineering stage.
3.7.5.10 HT & LT Motors
System Voltage and Design basis
a) Motors and their accessories shall be designed for continuous
operation under the stipulated site condition without exceeding permissible temperature rise over ambient. This specification does not include roller table motors. b) All motors and accessories shall conform to the latest revision of the Indian Electricity Rules as regards safety, earthing and essential provisions specified therein for installation and operation of Electrical plants. c) Standards The motors shall comply with the following publications of standard specification of ISS and IPSS:
IPSS:1-03-018-95 General purpose HT Squirrel cage Induction