Airtower With SC2 9 - 6917 - 43USE
Airtower With SC2 9 - 6917 - 43USE
Airtower With SC2 9 - 6917 - 43USE
Screw Compressor
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
Manufacturer:
KAESER KOMPRESSOREN SE
96410 Coburg • PO Box 2143 • GERMANY • Tel. +49-(0)9561-6400 • Fax +49-(0)9561-640130
www.kaeser.com
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
Original instructions
/KKW/SSXC 2.23 en Z1 SBA-SCHRAUBEN-TRI-VOLTAGE-AC-SC2IO
/KKW/SSC 2.13 Z1
20220712 083349
Contents
ev Y
2.2 Options ............................................................................................................................. 4
2.3 Weight .............................................................................................................................. 5
n
2.4 Temperature ..................................................................................................................... 5
R R
2.5 Ambient conditions ........................................................................................................... 6
io
2.6 Ventilation ........................................................................................................................ 6
2.7 Pressure ........................................................................................................................... 7
o NA
2.8 Air receiver .......................................................................................................................
2.9 Flow rate (constant delivery volume relative to intake conditions) ...................................
7
7
is
2.10 Cooling Oil Recommendation .......................................................................................... 8
2.10.1 Basic Information ................................................................................................ 8
2.10.2 KAESER Lubricants ............................................................................................ 8
2.11 Cooling oil charge quantity ............................................................................................... 9
2.12 Motors and power ............................................................................................................ 9
I
2.12.1 Compressor motor: ............................................................................................. 9
IM
ev Y
4.9 Safety devices .................................................................................................................. 30
n
4.10 Operating panel SIGMA CONTROL 2 ............................................................................. 31
R R
5 Installation and Operating Conditions
io
5.1 Ensuring safety ................................................................................................................ 34
5.2 Installation conditions ....................................................................................................... 34
5.2.1
5.2.2
o NA
Determining location and clearances ..................................................................
Ensuring adequate ventilation ............................................................................
34
35
is
5.3 Operating the machine in a compressed air system ........................................................ 36
6 Installation
6.1 Ensuring safety ................................................................................................................ 37
6.2 Reporting Transport Damage ........................................................................................... 38
I
6.3 Connecting the machine to the compressed air network ................................................. 38
IM
8 Operation
8.1 Switching on and off ......................................................................................................... 49
8.1.1 Switching on ....................................................................................................... 49
Su
10 Maintenance
10.1 Ensuring safety ................................................................................................................ 56
10.2 Following the maintenance plan ....................................................................................... 57
10.2.1 Logging maintenance work ................................................................................. 57
10.2.2 Resetting maintenance interval counters ............................................................ 57
10.2.3 Regular maintenance tasks ................................................................................ 57
10.2.4 Cooling oil changing interval ............................................................................... 59
10.2.5 Regular service tasks ......................................................................................... 59
10.3 Clean or replace the filter mat .......................................................................................... 59
10.4 Cooler maintenance ......................................................................................................... 60
10.5 Change the air filter .......................................................................................................... 61
ev Y
10.6 Compressor motor maintenance ...................................................................................... 62
n
10.7 Changing the drive belt .................................................................................................... 62
10.8 Checking the safety relief valve activating pressure ........................................................ 63
R R
10.8.1 Checking the compressor safety relief valve ...................................................... 64
io
10.8.2 Checking the air receiver safety relief valve ....................................................... 64
10.8.3 Performing the test ............................................................................................. 65
o NA
10.9 Checking the overheating safety shutdown function ........................................................ 66
is
10.10 Testing the EMERGENCY STOP push button ................................................................. 66
10.11 Checking the cooling oil level ........................................................................................... 67
10.12 Venting the machine (depressurizing) .............................................................................. 67
10.13 Replenishing cooling oil ................................................................................................... 69
10.13.1 Venting the machine (depressurizing) ................................................................ 70
I
10.13.2 Topping off with cooling oil and test run ............................................................. 71
IM
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
Fig. 12 Recommended machine placement and dimensions [in] ........................................................... 35
n
Fig. 13 Compressed pipework ................................................................................................................ 38
Fig. 14 Connecting the condensate drain ............................................................................................... 40
R R
Fig. 15 Inlet valve filling port ................................................................................................................... 46
io
Fig. 16 Switching on and off ................................................................................................................... 49
Fig. 17 Switching off in an emergency ................................................................................................... 50
Fig. 18
o NA
Switching on and off from a remote control center ..................................................................... 50
is
Fig. 19 Using the timer for switching on and off ..................................................................................... 51
Fig. 20 Acknowledging messages .......................................................................................................... 52
Fig. 21 Filter mat .................................................................................................................................... 60
Fig. 22 Oil cooler .................................................................................................................................... 61
Fig. 23 Change the air filter .................................................................................................................... 62
I
Fig. 24 Drive belt maintenance ............................................................................................................... 63
IM
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
Tab. 12 Flow rate [cfm] ............................................................................................................................ 7
n
Tab. 13 Cooling oil charge quantity ......................................................................................................... 9
Tab. 14 Compressor motor ...................................................................................................................... 9
R R
Tab. 15 Compressor motor: Rated speed ............................................................................................... 9
io
Tab. 16 Sound emission .......................................................................................................................... 10
Tab. 17 Supply 208V/3/60Hz ................................................................................................................... 11
Tab. 18
o NA
Supply 230V/3/60Hz ................................................................................................................... 11
is
Tab. 19 Supply 460V/3/60Hz ................................................................................................................... 11
Tab. 20 Model .......................................................................................................................................... 12
Tab. 21 Compressed air system .............................................................................................................. 12
Tab. 22 Refrigerant system ..................................................................................................................... 12
Tab. 23 Rated power supply 115V / 1ph / 60Hz ...................................................................................... 13
I
Tab. 24 Danger Areas ............................................................................................................................. 20
IM
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
➤ Enter details from the machine nameplate and individual items of equipment in the table in
n
chapter 2.
R R
io
1.2 Further documents
o NA
Further documents included with this operator manual are:
is
■ Certificate of acceptance / operating instructions for the pressure vessel
■ User manual for SIGMA CONTROL 2
1.3 Copyright
EL
This service manual is copyright protected. Queries regarding use or duplication of the documenta‐
tion should be referred to KAESER. Correct use of information will be fully supported.
tt
1.4.1 Warnings
Warning notices indicate dangers that may result in injury when disregarded.
bj
Warning notices indicate three levels of danger identified by the corresponding signal word:
Signal term Meaning Consequences of disregard
DANGER Warns of an imminent danger Will very likely result in death or severe injury
Su
WARNING Warns of a potentially imminent danger May result in death or severe injury
CAUTION Warns of a potentially dangerous situa‐ May result in a moderate physical injury
tion
Warning notices preceding a chapter apply to the entire chapter, including all sub-sections.
Example:
Warning notes referring to a sub-section or the subsequent action are integrated into the procedure
and numbered as an action.
ev Y
Example:
1.
n
The type and source of the imminent danger is shown here!
The possible consequences of ignoring a warning are shown here.
R R
If you ignore the warning notice, the "WARNING" signal word indicates that a lethal or severe
io
injury may occur.
➤ The measures required to protect yourself from danger are shown here.
o NA
2. Always read and comply with warning instructions.
is
1.4.2 Potential damage warnings
Contrary to the warnings shown above, damage warnings do not indicate a potential personal in‐
jury.
I
IM
Example:
tt
Material Here you will find details on special tools, operating materials or spare parts.
Precondition Here you will find conditional requirements necessary to carry out the task.
The conditions relevant to safety shown here will help you to avoid dangerous situations.
Option H1 ➤ This symbol denotes lists of actions comprising one stage of a task.
Operating instructions with several steps are numbered in the sequence of the operating steps.
Information relating to one option only are marked with an option code (e.g., H1 indicates that
this section applies only to machines with machine mountings). Option codes used in this oper‐
ator manual are explained in chapter 2.2.
ev Y
Information referring to potential problems are identified by a question mark.
The cause is named in the help text ...
n
➤ ... as is a solution.
R R
io
This symbol identifies important information or measures regarding the protection of the envi‐
ronment.
Further information
o NA
Further subjects are introduced here.
is
I
IM
EL
tt
PR
ec
bj
Su
2 Technical Data
2.1 Nameplate
The machine's nameplate provides the model designation and important technical information.
The nameplate is located on the air receiver.
➤ Enter the data from the nameplate here as a reference:
Feature Value
ev Y
Rotary screw compressor
n
Material No.:
R R
Serial No.:
io
Ambient temperature
Rated power
o NA
Max. working pressure PS
is
Rated motor speed
Power Supply of Compressor
Phase:
I
Frequency:
IM
Voltage
Full load current
Full load current drive motor
Short circuit current (rms sym.)
EL
Phase:
PR
Frequency:
ec
Voltage
Full load current
Full load current drive motor
Short circuit current (rms sym.)
bj
2.2 Options
The table contains a list of possible options. The options for this machine are shown near the
nameplate.
ev Y
Available: ✓
n
Not available: —
R R
Tab. 4 Options
io
2.3 Weight
o NA
is
The values shown are maximum values. The actual weight of individual machines depends on
equipment fitted.
Tab. 5 Weight
2.4 Temperature
EL
Typical airend discharge 150 – 200 150 – 200 150 – 200 150 – 200
ec
down) [°F]
Tab. 6 Temperature
Su
ev Y
ture [°F]
n
Inlet air temperature [°F] 40 – 115 40 – 115 40 – 115 40 – 115
R R
* Higher altitudes are permissible only after consultation with the manufacturer.
io
Tab. 7 Ambient conditions
o NA
is
I
IM
EL
2.6 Ventilation
The values given are minimum guide values.
7.5C
Inlet aperture Z see fig‐ 2.2 2.2 2.2 2.2
ure 12 [sq.ft.]
Su
(free area)
Extractor for forced venti‐ 883 1001 1236 1530
lation:
Flow rate [cfm] at 0.4 in.
wc
Tab. 8 Ventilation
2.7 Pressure
Maximum working pressure: see nameplate
ev Y
217 — 230 230 230
n
Tab. 9 Safety relief valve activating pressure
R R
io
2.8 Air receiver
o NA
is
Volume
125 12 16 21 28
160 9 13 17 24
217 — 9 13 19
Flow rate as per ISO 1217:2009 (Annex C)
ev Y
tensive internal corrosion. Water may be condensed decreasing the lubricity.
n
Lubricants in rotary compressors do much more than lubricate. During the compression process, it
acts as a sealant in the airend which is important for maximum efficiency. The lubricant also ab‐
R R
sorbs much of the heat of compression to cool the airend and reduce the temperature of the com‐
io
pressed air. It’s not enough that a compressor cooling oil lubricates well, it must stand up to the
heat, pressure and contaminants that are present in every air compressor.
o NA
is
2.10.2 KAESER Lubricants
KAESER synthetic lubricants should be stored in a protected location to prevent contamination. Do
not re-use drums; flush and send to reconditioner.
Although the KAESER synthetic is not highly flammable, it will burn. While KAESER synthetic com‐
I
pressor cooling oil is less flammable than equal viscosity mineral oils, it cannot be classified as a
IM
fire-resistant fluid. It has a flash point above 460 °F. Since the user has total control over the condi‐
tions of the compressor lubricant, he assumes total responsibility for its safe usage.
Material Safety Data Sheets are available for each lubricant from your authorized
KAESER SERVICE representative.
Regardless of the lubricant selected, the KAESER SIGMA lubricants will separate readily from wa‐
EL
ter. If condensate occurs it can easily be removed. Let the compressor sit so that any water can
drain back to the separator tank and separate to the bottom. See chapter 10.14 proper draining
procedure.
tt
KAESER has several lubricants available that are specially formulated to match these demands.
They feature excellent lubricity, outstanding demulsibility (ability to separate from water), and long
PR
life.
ec
M-SERIES
■ M-Series SIGMA compressor cooling oils are semi-synthetic lubricants.
■ M-Series SIGMA compressor cooling oils are the highest quality petroleum lubricants. M–460
is specially blended to provide reliable performance in KAESER screw compressors.
bj
S-SERIES
■ S-Series SIGMA compressor cooling oils are synthetic lubricants.
Su
■ S-Series SIGMA compressor cooling oils are formulated from the most advanced synthetic lu‐
bricants. These ”synthetic” lubricants begin as high quality petroleum feed stock. They are then
refined, processed and purified into fluids with very consistent molecular structure. These oils
are carefully blended to produce extremely consistent lubricants with superior properties.
SIGMA synthetic lubricants feature all the advantages of both PAO and diester fluids.
■ S-460 lubricant is recommended for compressors operating in ambient temperatures between
40 °F and 105 °F.
ev Y
2.11 Cooling oil charge quantity
n
AIRTOWER 3C AIRTOWER 4C AIRTOWER 5C AIRTOWER
R R
7.5C
io
Total charge [qt] 3.0 3.0 3.0 3.0
o NA
Topping up volume [qt] 0.13 0.13 0.13 0.13
is
(minimum–maximum)
ev Y
n
2.14 Power Supply
R R
Basic requirements
io
The machine is designed for an electrical supply according to National Electric Code (NEC), edi‐
o NA
tion 2020, particularly article 670 and NFPA 79, edition 2021, particularly section 4.4. In the ab‐
is
sence of any user-specified alternatives, the limits given in these standards must be adhered to.
Consult manufacturer for any other specific power supply.
The incoming line within the control panel should be as short as possible.
If external sensors or communication lines are to be connected to the machine, use shielded ca‐
bles and insert the same through EMC fittings into the control panel.
I
IM
Three-phase
Do NOT operate package on any unsymmetrical power supply. Also do NOT operate package on
power supplies such as a three-phase WYE system with the center point not solidly grounded or
three-phase (open) delta.
EL
The machine requires a symmetrical three-phase power supply transformer with a WYE configura‐
tion output as shown in Figure 2 and Figure 3. In a symmetrical three phase supply the phase an‐
gles and voltages are all the same.
tt
Fig. 2 Three-phase star (wye system); 4 wire; center point solidly grounded
bj
Su
Fig. 3 Three-phase star (wye system); 3 wire; grounded center point solidly grounded
Further information Please contact an authorized KAESER service representative for options.
The electrical diagram 13.3 contains further specifications for electrical connection.
ev Y
local codes allow. Neither the minimum ground wire size as pointed out in 2020 NEC table 250.122
n
nor using conduit as the sole ground connection is recommended.
R R
io
Rated power supply 208V, 3-ph, 60Hz
o NA 7.5C
is
Pre-fuse [A] 15 15 20 30
Supply per phase and AWG14 AWG14 AWG12 AWG10
ground (75 °C)
Consumption [A] 9.4 12 15 20
I
Tab. 17 Supply 208V/3/60Hz
IM
7.5C
Pre-fuse [A] 15 15 20 25
Supply per phase and AWG14 AWG14 AWG12 AWG10
tt
Pre-fuse [A] 10 10 10 15
Supply per phase and AWG14 AWG14 AWG14 AWG14
Su
Tab. 20 Model
ev Y
Compressed air system
n
CT 4 CT 8
R R
io
Pressure drop [psi] 3 3
(referred to 100 psig
working pressure)
Maximum permissible
o NA 232 232
is
working pressure [psig]
Refrigerant system
I
IM
The refrigerated dryer contains a refrigerant that is classified as a fluoridated global warming gas.
This refrigerant is required for the function.
The refrigerant system is hermetically sealed.
CT 4 CT 8
EL
CT 4 CT 8
Pre-fuse [A] 15 15
ev Y
Supply per phase and AWG14 AWG14
n
ground (75 °C)
R R
Consumption [A] 3.2 5.1
io
Tab. 23 Rated power supply 115V / 1ph / 60Hz
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
Disregard of warning or safety instructions can cause serious injuries!
n
➤ Use this machine only if it is in a technically perfect condition and only for the purpose for
R R
which it is intended; observe all safety measures and the instructions in the operator manual.
io
➤ Immediately rectify (have rectified) any faults that could be detrimental to safety!
o NA
is
3.2 Specified use
The machine is intended solely for generating compressed air for industrial use. Any other use is
considered incorrect. The manufacturer is not liable for any damages that may result from incorrect
use. The user alone is liable for any risks incurred.
I
➤ Keep to the specifications listed in this service manual.
IM
➤ Operate the machine only within its performance limits and under the permitted ambient condi‐
tions.
➤ Do not use compressed air for breathing purposes unless it is specifically treated.
➤ Do not use compressed air for any application that will bring it into direct contact with food
EL
➤ Do not operate the machine in areas in which specific requirements with regard to explosion
protection are in force.
Su
ev Y
■ have received adequate training and authorization to operate electrical and compressed air de‐
vices.
n
■ Additional qualifications for compressors with refrigerated dryers:
R R
─ Adequate training and authorization on refrigeration devices.
io
Authorized installation and maintenance personnel have the following qualifications:
■
o NA
are of legal age,
is
■ have read, are conversant with and adhere to the safety instructions and sections of the opera‐
tor manual applicable to installation and maintenance,
■ are fully conversant with the safety concepts and regulations of electrical and compressed air
engineering,
I
■ are able to recognize the possible dangers of electrical and compressed air devices and take
IM
─ must be able to recognize the possible dangers of refrigeration devices and take appropri‐
ate measures to safeguard persons and property.
tt
➤ Ensure that operating, installation and maintenance personnel are qualified and authorized to
carry out their tasks.
PR
3.5 Dangers
Basic instructions
Su
The following describes the various forms of danger that can occur during machine operation.
Basic safety instructions are found in this operator manual at the beginning of each chapter in the
section entitled “Safety”.
Warning instructions are found before a potentially dangerous task.
Electricity
The machine is designed, as standard, for separate power supplies to the compressor and
refrigerated dryer.
Touching voltage carrying components can result in electric shocks, burns or death.
ev Y
➤ All power supplies must be fitted with lockable disconnecting devices by the user.
➤ Allow only qualified and authorized electricians or trained personnel under the supervision of a
n
qualified and authorized electrician to carry out work on electrical equipment according to elec‐
R R
trical engineering rules.
io
➤ Before commissioning or recommissioning the machine, the user must ensure adequate pro‐
tection against electric shock from direct or indirect contact.
o NA
➤ Before starting any work on electrical equipment:
is
Switch off and lock out/tag out the power supply disconnecting device and verify the absence
of any voltage.
➤ Switch off any external power sources.
These could be connections to floating relay contacts or electrical machine heating, for exam‐
ple.
I
➤ Use fuses corresponding to machine power.
IM
➤ Check regularly that all electrical connections are tight and in proper condition.
Forces of compression
Compressed air is contained energy. Uncontrolled release of this energy can cause serious injury
EL
or death. The following information concerns work on components that could be under pressure.
➤ Close shut-off valves or otherwise isolate the machine from the distribution network to ensure
that no compressed air can flow back into the machine.
tt
nents (e.g. pipes and vessels) as this influences the component’s resistance to pressure.
ec
The composition of the compressed air must be suitable for the actual application in order to pre‐
bj
Spring force
Springs under tension or compression are a contained force. Uncontrolled release of this energy
can cause serious injury or death.
Minimum pressure / check valves, safety relief valves and inlet valves are powerfully spring-loaded.
➤ Do not open or dismantle any valves.
Rotating components
Touching the fan wheel, the coupling or the belt drive while the machine is switched on can result
in serious injury.
➤ Do not open the enclosure while the machine is switched on.
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the absence
of any voltage.
ev Y
➤ Wear close-fitting clothes and a hair net if necessary.
n
➤ Ensure that all covers and safety guards are in place and secured before restarting.
R R
io
Temperature
High temperatures are generated during compression. Touching hot components may cause inju‐
ries.
o NA
is
➤ Avoid contact with hot components.
These include, for example, compressor airends, oil and compressed air lines, coolers, oil sep‐
arator tanks, motors, and machine heaters.
➤ Wear protective clothing.
I
➤ If welding is carried out on or near the machine, take adequate measures to prevent sparks or
IM
Noise
The enclosure absorbs the machine noise to a tolerable level and is only effective if closed.
EL
Operating fluids/materials
PR
The operating fluids and materials used can cause adverse health effects. Suitable safety meas‐
ec
Modifications, additions to, and conversions of the machine or the controller can result in unpredict‐
able dangers.
➤ Do not convert or modify the machine!
➤ Obtain written approval by the manufacturer prior to any technical modification or expansion of
the machine, the controller, or the control programs.
ev Y
If dimensioned appropriately, safety relief valves reliably prevent an impermissible rise in pressure.
New dangers may arise if you modify or extend the compressed air network or system.
n
➤ When extending or modifying the compressed air system:
R R
Check the blow-off capacity of safety relief valves on air receivers and in compressed air lines
io
before installing a new machine.
➤ If the blow-off capacity is insufficient:
o NA
Install safety relief valves with a larger blow-off capacity.
is
3.5.2 Safe machine operation
The following is information supporting you in the safe handling of the machine during individual
product life phases.
I
IM
When working on the machine you may be exposed to dangers that can result in accidents with
severe adverse health effects.
➤ Wear protective clothing as necessary.
EL
■ Safety boots
PR
■ Eye protection
■ Ear protection
ec
Transporting
The weight and size of the machine require safety measures during its transport to prevent acci‐
bj
dents.
➤ Use suitable lifting gear that conforms to local safety regulations.
➤ Allow transportation only by personnel trained in the safe movement of loads.
Su
Assembly
➤ Only use only electrical cables that are suitable and approved for the surroundings and electri‐
cal loads applied.
➤ Never dismantle compressed air pipes until they are fully vented.
➤ Only use pressure lines that are suitable and approved for the maximum working pressure and
the intended medium.
➤ Do not allow connection pipes to be placed under mechanical stress.
➤ Do not induce any forces into the machine via the connections, so that the compressive forces
must be balanced by bracing.
Positioning
A suitable installation location for the machine prevents accidents and faults.
ev Y
➤ Install the machine in a suitable compressor room.
n
➤ Ensure sufficient and suitable lighting such that the display can be read and work carried out
R R
comfortably and safely.
io
➤ Ensure accessibility so that all work on the machine can be carried out without danger or hin‐
drance.
o NA
➤ If installed outdoors, the machine must be protected from frost, direct sunlight, dust, rain and
is
splashing water.
➤ Do not operate in areas in which specific requirements regarding explosion protection are in
force.
➤ Ensure adequate ventilation.
➤ Place the machine in such a manner that the working conditions in its environment are not im‐
I
paired.
IM
➤ Do not position the machine in warm cooling outlet air from other machines.
➤ Keep suitable fire extinguishing agents ready for use.
tt
During commissioning, operation and maintenance you may be exposed to dangers resulting from,
e.g., electricity, pressure and temperature. Careless actions can cause accidents with severe ad‐
ec
ev Y
n
De-commissioning, storage and disposal
R R
Improper handling of old operating fluids and components represent a danger for the environment.
io
➤ Drain off fluids and dispose of them according to environmental regulations.
These include, for example, compressor oil and cooling water.
o NA
➤ Have refrigerant disposed of by authorized bodies only.
is
➤ Dispose of the machine in accordance with local environmental regulations.
preparation.
No personnel during transport.
ec
ply cables.
Operation Within a 3 ft radius of the machine. Operating personnel
Maintenance Within the machine. Maintenance personnel
Su
Further information More information on safety devices is contained in chapter 4, section 4.9.
ev Y
working life of 20 years. The working life starts with the commissioning, and is not extended by
times during which the machine was not in use.
n
R R
The following components are affected:
io
■ Airend discharge temperature sensor (Pt100 sensor for measuring the compression discharge
temperature)
■
o NA
EMERGENCY STOP push button
is
■ Main contactor
1. The components of the safety functions must be replaced by an authorized KAESER service
representative after a working life of 20 years.
2. Have an authorized KAESER service representative check the reliability of the safety func‐
I
tions.
IM
ev Y
10 Severe injury could result from touching the belt drive or fan blade!
n
➤ Operate the machine only with fully closed safety guards, access doors and
R R
panels.
io
➤ Isolate from the power supply and lock out before opening any machine enclo‐
sure or guard.
11
o NA
Injury and/or contamination can result from breathing compressed air!
is
Contamination of food can result from using untreated compressed air for food pro‐
cessing!
➤ Never breathe untreated compressed air.
➤ Air from this compressor must meet OSHA 29 CFR1910.134 and
FDA 21 CFR178.3570 standards, if used for breathing or food processing. Use
I
proper compressed air treatment.
IM
25 Ear damage and burns can result from loud noise and/or oil mist when the safety
relief valve opens!
➤ Wear ear protection and protective clothing.
➤ Close all access doors and cover panels.
ev Y
3.9 Emergency situations
n
3.9.1 Correct fire fighting
R R
io
Suitable measures
o NA
Calm and prudent action can safe lives in the event of a fire.
is
➤ Keep calm.
➤ Give the alarm.
➤ Shut off supply lines if possible.
Main disconnecting device (all poles)
Cooling water (if present)
I
Heat recovery (if present)
IM
Extinguishing substances
Foam
Carbon dioxide
PR
Sand or soil
ec
Eye contact
➤ Rinse open eyes thoroughly for a few minutes under running water.
➤ Seek medical help if irritation persists.
Skin contact
Inhalation
Ingestion
ev Y
➤ Seek medical aid.
n
3.9.3 Injury from Handling Refrigerant
R R
io
Eye contact:
o NA
Severe eye irritation, watering, reddening and swelling of the eyelids.
is
Risk of caustic burns and frostbite.
➤ Open eyelids wide to allow product to evaporate.
➤ Hold the eyelid wide and rinse the eye with running water.
➤ Consult an ophthalmologist if you experience lasting pains.
I
Skin contact:
IM
Inhalation:
tt
3.10 Warranty
This operator manual contains no independent warranty commitment. Our general terms and con‐
Su
■ incorrect maintenance,
■ incorrect repair.
Correct maintenance and repair includes the use of original spare parts and operating materials.
➤ Obtain confirmation from KAESER that your specific operating conditions are suitable.
ev Y
➤ Do not allow cooling oil to escape to the environment or into the sewage system.
n
➤ Store and dispose of operating materials and replaced parts in accordance with local environ‐
R R
mental protection regulations.
io
➤ Observe national regulations.
This applies particularly to parts contaminated with compressor cooling oil.
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
Fig. 5 Enclosure overview
1 Enclosure 4 Refrigeration dryer
2 Condensate drain viewing window 5 Bracket
I
3 Air receiver
IM
Safe and reliable operation is only assured with the enclosure closed.
ec
The enclosure 1 is removed by tipping forward (A) then lifting off (B).
bj
Install the enclosure in the reverse order from removal, making sure the bracket 5 engages in the
guides.
Su
ev Y
n
R R
io
o NA
is
Fig. 6 Machine overview
I
1 Inlet valve 7 Oil separator tank
IM
Cooling oil is injected into the airend. It lubricates moving parts and forms a seal between the ro‐
PR
tors and between the rotors and the airend casing. This direct cooling in the compression chamber
ensures a very low airend discharge temperature.
ec
Cooling oil recovered from the compressed air in the oil separator tank 7 and oil separator car‐
tridge 10 gives up its heat in the oil cooler 9 . The oil then flows through the oil filter 4 and back to
the point of injection. Air pressure within the machine keeps the oil circulating. A separate pump is
not necessary. A thermostatically regulated fan keeps the cooling oil at optimum temperature.
bj
Compressed air passes through the minimum pressure / check valve 2 into the air receiver 12 .
The minimum pressure / check valve ensures sufficient internal pressure to maintain cooling oil cir‐
culation.
Compressed air is cooled in the receiver and chilled in the refrigerated dryer 11 . Most of the mois‐
Su
ev Y
n
R R
io
Fig. 7 Refrigerated dryer
o NA
is
1 Refrigerated dryer
2 Condensate drain
3 Display: Controller power
The downstream refrigerated dryer removes moisture from the compressed air.
I
The condensate is removed via a condensate drain.
IM
The Controller power display is illuminated in green when the voltage supply of the refrigerated dry‐
er is activated.
The compressed air stored in the air receiver smooths out peaks in air consumption. The air receiv‐
er is sized specifically for the machine and may not be used for another purpose.
tt
This condensate drain only works when the refrigerated dryer is switched on.
➤ Condensate may be drained manually if the dryer is switched off.
ec
Floating relay contacts are provided for the transfer of signals and messages.
Information on location, loading capacity and type of message or signal is found in the electrical
diagram.
Su
If the floating relay contacts are connected to an external voltage source, voltage may be
present even when the machine is isolated from the power supply.
4.6 Options
The options available for your machine are described below.
ev Y
Input-Output-Module (IOM):
n
■ Module with digital and analog
R R
inputs and outputs.
io
Tab. 26 Components
4.6.2 Option H1 o NA
is
Machine mountings
These mountings allow the machine to be anchored firmly to the floor.
I
IM
STOP
READY
bj
LOAD
ev Y
system pressure between the set minimum and maximum values.
n
The machine automatically continues to run under LOAD if the duty cycle is too low. This
event lasts a few minutes, at maximum.
R R
A sufficient duty cycle prevents harmful condensate.
io
4.8
o NA
Refrigerated dryer control modes
is
The controller can work in the following control modes:
■ CONTINUOUS
CONTINUOUS
I
IM
In this mode the refrigerated dryer runs continuously, even if the compressor is not running.
The refrigerated dryer is switched off together with the compressor.
The following safety devices are provided and must not be modified or disabled.
■ EMERGENCY STOP push button:
tt
The EMERGENCY STOP push button shuts down the compressor immediately. The motor is
stopped. The pressure system is vented.
PR
The safety pressure monitor protects the refrigerant circuit of the refrigerated dryer against ex‐
cessive pressure. It cannot be set.
■ Enclosure and covers for moving parts and electrical connections:
Su
ev Y
n
R R
io
o NA
is
I
Fig. 9 Keys – overview
IM
Tab. 27 Keys
Indicators
ev Y
n
R R
io
o NA
is
I
IM
14 Indicator field or Graphic display with 8 lines and 30 characters per line.
Display
15 Alarm Flashes red to indicate a machine alarm.
tt
down.
17 Warning Flashes in yellow in the following events:
■ Maintenance necessary
■ Warning message
bj
controller
19 LOAD Continuous green light when the machine is running in LOAD.
20 IDLE Display without function.
21 Remote control Continuous green light when the machine is in remote control.
22 Timer control Continuous green light when the machine is controlled by the
timer.
Tab. 28 Indicators
RFID reader
RFID is the abbreviation for “Radio Frequency Identification” and enables the identification of per‐
sons or objects.
Placing a suitable transponder in front of the KAESER RFID reader of the controller will automati‐
ev Y
cally activate the communication between transponder and SIGMA CONTROL 2.
A suitable transponder is the KAESER RFID Equipment Card. Two of them have been provided
n
with the machine.
R R
io
Typical application:
■ Users log on at the machine.
o NA
(Manual input of the password not required.)
is
I
IM
RFID Key.
PR
Further information More information about the use of KAESER RFID technology is provided in the
SIGMA CONTROL 2 operating manual.
bj
Su
ev Y
Complying with safety warnings
n
Disregard of safety warnings can cause unforeseeable dangers!
R R
➤ Strictly forbid fire, open flame and smoking.
io
➤ If welding is carried out on or near the machine, take adequate measures to prevent sparks or
heat from igniting oil vapors or parts of the machine.
o NA
➤ Do not store inflammable material in the vicinity of the machine.
is
➤ The machine is not explosion-proof!
Do not operate in areas in which specific requirements with regard to explosion protection are
in force.
➤ Ensure sufficient and suitable lighting such that the display can be read and work carried out
comfortably and safely.
I
➤ Keep suitable fire extinguishing agents ready for use.
IM
■ Ensure the appropriate composition of the air within the machine room:
─ Clean with no damaging contaminants (e.g., dust, fibers, fine sand).
─ Free of explosive or chemically unstable gases or vapors.
tt
The machine is intended for installation in an appropriate machine room. Information on distances
from walls and ventilation is given below.
The distances quoted are recommended distances and ensure unhindered access to all ma‐
Su
chine parts.
➤ Please consult an authorized KAESER service representative if you cannot comply with
these recommendations.
Precondition The floor must be level, firm and capable of bearing the weight of the machine.
ev Y
n
R R
io
Fig. 12
o NA
Recommended machine placement and dimensions [in]
is
A Exhaust fan
Z Ventilation inlet air opening
➤ Make sure that the temperature of the machine is at least 37°F before starting.
➤ Heat the machine room adequately or install an auxiliary heater.
2. Ensure adequate lighting so that all work on the machine can be carried out without danger or
hindrance.
EL
3. Ensure that the indicators can be read without glare and that the controller display cannot be
damaged by direct sunlight (UV radiation).
4. Ensure that all air inlet and exhaust air openings of the enclosure remain opened.
5. If installed outdoors, the machine must be protected from frost, direct sunlight, dust, and rain.
tt
PR
➤ Consult with KAESER if you cannot ensure the conditions for adequate ventilation of the
machine room.
Su
1. Ensure that the flow rate of fresh air is at least the same as the flow rate taken by the machine
and exhaust fan from the machine room.
2. Make sure that the machine and exhaust fan can only operate when the ventilation inlet air
opening is actually open.
3. Keep the inlet and exhaust openings free of obstructions so that the cooling air can flow freely
through the room.
4. Ensure clean air in order to support the proper functioning of the machine.
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
6 Installation
6.1 Ensuring safety
Follow the instructions below for safe installation.
Warning instructions are located before a potentially dangerous task.
ev Y
Complying with safety warnings
n
Disregard of safety warnings can cause unforeseeable dangers.
R R
➤ Follow the instructions in chapter 3 "Safety and Responsibility".
io
➤ Installation work may only be carried out by authorized personnel.
➤ Make sure that no one is working on the machine.
o NA
➤ Ensure that all service doors and panels are locked.
is
When working on live components
Touching voltage carrying components can result in electric shocks, burns or death.
➤ Work on electrical equipment may only be carried out by authorized electricians.
I
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the absence
IM
of any voltage.
➤ Check that the floating relay contacts are voltage-free.
Compressed air is contained energy. Uncontrolled release of this energy can cause serious injury
or death. The following safety concerns relate to any work on components that could be under
pressure.
tt
➤ Close shut-off valves or otherwise isolate the machine from the compressed air network to en‐
sure that no compressed air can flow back into the machine.
PR
➤ Check all hose couplings in the compressed air system with a handheld pressure gauge to en‐
sure that they all read 0 psig.
➤ Do not open or dismantle any valves.
bj
Touching voltage carrying components can result in electric shocks, burns or death.
Touching the fan wheel or belt drive while the machine is running can result in serious injury.
Su
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the absence
of any voltage.
➤ Do not open the cabinet while the machine is switched on.
ev Y
➤ Use fluoroelastomers as sealing material for seals.
n
➤ Note the electrochemical voltage sequence.
R R
➤ Contact an authorized KAESER service representative concerning suitable materials for
io
the compressed air network.
o NA
is
I
IM
2 Shut-off valve
1. Serious injury or death can result from loosening or opening components under
pressure!
tt
Further information The dimensional drawing in chapter 13.2 provides the size and position of the connection ports.
Condensate line
Feature Value
Max. length [ft]
1) 50
Max. delivery head [ft] 16
Material Copper
(pressure-resistant, cor‐ Stainless steel
rosion-proof)
Plastics
Hose line
ev Y
1)
For longer lengths, please contact KAESER before installation.
n
Tab. 30 Condensate line
R R
io
Condensate collecting line
Feature
o NA Value
is
Gradient [%] ≥3
Max. length [ft]
1) 65
Material Copper
(pressure-resistant, cor‐ Stainless steel
I
rosion-proof)
Plastics
IM
Hose line
1)
For longer lengths, please contact KAESER before installation.
<350 3/4
350 – 730 1
PR
>1410 2
1)
Compressed air flow rate as guide for the condensate volume to be expected
ev Y
n
R R
io
Fig. 14
o NA
Connecting the condensate drain
is
1 Threaded connection 5 Shut-off valve
2 Condensate line A Delivery head
3 Condensate collecting line B Length of the condensate collecting line
4 Screw plug
I
Depending on the machine model, you may have several condensate drains.
IM
Further information The dimensional drawing in chapter 13.2 provides the size and position of the connection port.
EL
Use suitable shielded, copper-core cable (e.g.: LIYCY 2 x0.75 mm2 for ambient temperature up to
30°C and laying method C).
ec
By means of a pressure transducer, the pressure in the compressed air network can be measured
at any selected location and this signal used to regulate the compressor.
Su
This ensures optimum compressor regulation with regard to the network pressure at the selected
location.
Safety monitoring of the machine's internal pressure is unaffected.
An authorized KAESER SERVICE representative will be glad to provide support on planning
and executing an individual solution.
1. Install the pressure transducer at the selected location in the compressed air network.
2. Using a suitable cable, connect the pressure transducer to a spare analog input.
➤ Connect as large an area of the shielding as possible to the mounting plate in the control
cabinet or use an EMC fitting to make contact.
3. When commissioning the machine with a SIGMA CONTROL 2, select the <Network actual
pressure> setting in the <AII> menu.
4. Select and activate the used analog input (AII).
Further information The electrical diagram in chapter 13.3 contains further details of the pressure transducer connec‐
tion.
ev Y
n
6.6 Option T2
R R
Refrigerated dryer: Connecting the transformer according to the
io
power supply.
o NA
The refrigerated dryer transformer has tappings for various power supply voltages.
is
1. Check that the correct connections are made for the supply voltage provided for the machine.
2. If necessary, re-connect the transformer to match the power supply voltage.
Further information The electrical diagram in chapter 13.3 contains further details of the power supply connection.
I
IM
This is a Tri-Voltage machine. The machine can be set up to one of the following supply voltages:
■ 208V
tt
■ 230V
PR
■ 460V
ec
1. Have the power supply connected only by authorized installation personnel or an authorized
electrician.
2. Carry out safety measures as stipulated in relevant regulations and in national accident pre‐
vention regulations . In addition, observe the regulations of the local electricity supplier.
bj
Material The required jumpers (also known as ’bridges’ or ’links’) are provided in the control cabinet.
➤ Open the control cabinet and connect the motor in accordance with the electrical diagram.
ev Y
Adjusting the overload protection cutout
n
➤ Check the overload protection relay setting.
R R
io
AIRTOWER 3C AIRTOWER 4C AIRTOWER 5C AIRTOWER
7.5C
208V, 3-ph, 60Hz [A]
o NA 5.7 7.1 9.5 12.2
is
230V, 3-ph, 60Hz [A] 5.3 6.7 9.5 11.7
460V, 3-ph, 60Hz [A] 2.6 3.4 4.7 5.9
➤ Open the control cabinet and connect the control transformer in accordance with the electrical
diagram.
Each power supply must have its own isolating device. Both isolating devices must be switch‐
ed off before working on the electrical equipment. This is possible by a mechanical locking
tt
➤ Ensure that both power supplies are always switched off together.
1. Test the overcurrent protection cut-out to ensure that the time it takes to disconnect in re‐
sponse to a fault is within the permitted limit.
bj
2. Select supply cable conductor cross-sections and fuses in accordance with local regulations.
3. All power supplies must be fitted with lockable isolating devices by the user.
This could be, for example, a load disconnect switch with fused input. If a circuit breaker is
Su
6.8 Options
6.8.1 Option H1
Anchoring the machine
➤ Use appropriate fixing bolts to anchor the machine.
Further information Details of the fixing holes are contained in the dimensional drawing in chapter 13.2.
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
7 Initial Start-up
7.1 Ensuring safety
Here you will find instructions for a safe commissioning of the machine.
Warning instructions are located before a potentially dangerous task.
ev Y
Complying with safety warnings
n
Ignoring safety warnings can cause unforeseeable dangers.
R R
➤ Follow the instructions in chapter 3 "Safety and Responsibility".
io
➤ Commissioning tasks may only be carried out by authorized personnel!
➤ Make sure that no one is working on the machine.
o NA
➤ Ensure that all service doors and panels are locked.
is
When working on live components
Touching voltage carrying components can result in electric shocks, burns or death.
➤ Work on electrical equipment may only be carried out by authorized electricians.
I
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the absence
IM
of any voltage.
➤ Check that the floating relay contacts are voltage-free.
Compressed air is contained energy. Uncontrolled release of this energy can cause serious injury
or death. The following safety concerns relate to any work on components that could be under
pressure.
tt
➤ Close shut-off valves or otherwise isolate the machine from the compressed air network to en‐
sure that no compressed air can flow back into the machine.
PR
➤ Check all hose couplings in the compressed air system with a handheld pressure gauge to en‐
sure that they all read 0 psig.
➤ Do not open or dismantle any valves.
bj
Touching voltage carrying components can result in electric shocks, burns or death.
Touching the fan wheel or belt drive while the machine is running can result in serious injury.
Su
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the absence
of any voltage.
➤ Do not open the cabinet while the machine is switched on.
ev Y
longer than
n
3 months ➤ Manually fill the airend with cooling oil.
R R
12 months ➤ Change the oil filter.
io
➤ Change the oil separator cartridge.
➤ Change the cooling oil.
o NA
➤ Manually fill the airend with cooling oil.
is
36 months ➤ Have the overall technical condition checked by an authorized KAESER
service representative.
chapter
➤ Are the operators fully familiar with safety regulations? –
➤ Have all the installation conditions been fulfilled? 5
tt
➤ Are the tolerance limits of the power supply within the permissible tol‐ 13.3
ec
➤ Is the drive motor overload protection switch set according to the 7.4
power supply voltage?
➤ Have all electrical connections been checked for tightness? –
Su
ev Y
With star-delta starting, the phase current is fed via the overload protection relay. This phase cur‐
n
rent is 0.58-times the rated motor current.
To prevent the overload protection relay from being triggered by voltage fluctuations, temperature
R R
influences or component tolerances, the setting can be higher than the arithmetical phase current.
io
➤ Check the overload protection relay setting.
o NA
The overload protection relay shuts the machine down despite being correctly set?
is
➤ Contact an authorized KAESER service representative.
of more than 3 months it is necessary to manually add a quantity of cooling oil into the airend. In
order to avoid that the cooling oil exceeds the permissible level, drain the required quantity from
the de-pressurized oil separator tank.
Chapter 10.14 provides detailed information on how to drain cooling oil from the oil separator tank.
EL
ev Y
3. If required:
n
Change the display language as described in chapter 7.8.
4. Press the «ON» key.
R R
io
The drive motor runs up and after a short time the machine switches to LOAD and delivers
compressed air.
o NA
➤ Watch for any faults occurring in the first hour of operation.
is
➤ After the first 50 operating hours, check all electrical connections and tighten where nec‐
essary.
Does the machine stop because the compressor motor is rotating in the wrong direction?
➤ Switch off and lock out/tag out the power supply disconnecting device and verify the ab‐
sence of any voltage.
I
➤ Changeover phase lines L1 and L2.
IM
➤ Acknowledge any existing alarm messages and switch the machine on again.
Do not set the set point pressure of the machine higher than the maximum working pressure
of the compressed air system.
PR
The machine may not toggle more than twice per minute between LOAD and IDLE.
ec
2. Press the «UP» or «DOWN» keys until the current language is shown as active line (inverse):
88 psig 176 ° F
–––––––– de_DE Deutsch –––––––– Current language (active line)
▶1 xxxxxxxxxx Submenu
▶2 xxxxxxxxxx Submenu
▶3 xxxxxxxxxx Submenu
▶4 xxxxxxxxxx Submenu
▶5 xxxxxxxxxx Submenu
ev Y
▶6 xxxxxxxxxx Submenu
n
3. Use the «Return» key to switch to setting mode.
R R
The language display flashes.
io
4. Move to the required language with «UP »or «DOWN».
5. Confirm the setting with the «Enter» key.
o NA
is
Result The display texts are now in the selected language.
Further information Detailed information can be found in the SIGMA CONTROL 2 operating manual.
I
IM
EL
tt
PR
ec
bj
Su
8 Operation
8.1 Switching on and off
Always switch the machine on with the «ON» key and off with the «OFF» key.
A power supply disconnecting device has been installed by the user.
ev Y
n
R R
io
o NA
is
I
Fig. 16 Switching on and off
IM
8.1.1 Switching on
EL
If a power failure occurs, the machine is not prevented from automatic restarting.
It can start automatically again as soon as power is restored.
Result The compressor motor starts as soon as system pressure is lower than the setpoint pressure (cut-
bj
off pressure).
Result 7 The Voltage applied to controller LED and the Controller voltage LED (see fig. 7) are extinguish‐
ed. The machine is switched off and disconnected from the power supply.
ev Y
n
R R
io
Fig. 17 Switching off in an emergency
9 EMERGENCY STOP push button
o NA
is
Switching off
Result The EMERGENCY STOP push button remains latched after actuation.
The compressor's pressure system is vented and the machine is prevented from automatically re-
I
starting.
IM
Switching on
1. Turn the EMERGENCY STOP push button in the direction of the arrow to unlatch it.
2. Acknowledge any existing alarm messages.
1. Attach an easily seen notice to the machine that warns of remote operation.
ev Y
n
Remote control: Risk of injury caused by unexpected starting!
R R
➤ Before starting, make sure that no one is working on the machine and that it can be safely
io
started.
o NA
is
3. Press the «Remote control» key.
The Remote control LED lights. The machine can be remotely controlled.
1. Attach an easily seen notice to the machine that warns of time-controlled operation:
Su
Further information Detailed information can be found in the SIGMA CONTROL 2 operating manual.
ev Y
Messages are displayed on the "new value" principle:
n
■ Message coming: LED flashes
R R
■ Message acknowledged: LED illuminates
io
■ Message going: LED off
or
o NA
is
■ Message coming: LED flashes
■ Message going: LED flashes
■ Message acknowledged: LED off
I
IM
EL
tt
PR
ec
Alarm message
An alarm shuts the machine down automatically. The red alarm LED flashes.
Su
If the machine was switched off with the EMERGENCY STOP button:
➤ Unlatch the EMERGENCY STOP button (turn in direction of the arrow) before acknowl‐
edging the alarm message.
Further information Please refer to the SIGMA CONTROL 2 operating manual for a list of possible fault messages dur‐
ing operation.
Warning message
If maintenance work is to be carried out or if a warning is displayed before an alarm, the yel‐
low warning LED flashes.
ev Y
The system displays the appropriate message.
n
Precondition The danger of an alarm is passed,
R R
maintenance has been carried out.
io
➤ Acknowledge the message with the «Acknowledge» key.
o NA
The warning LED extinguishes.
is
Further information A list of possible alarm messages occurring during operation can be found in the service manual
SIGMA CONTROL 2 .
I
IM
EL
tt
PR
ec
bj
Su
ev Y
─ System messages Y
n
─ Diagnostic messages D
R R
■ Other faults (without indication): See chapter 9.2
io
The messages valid for your machine are dependent on how the individual machine is equipped.
o NA
1. Do not attempt fault rectification measures other than those given in this manual!
is
2. In all other cases:
Have the fault rectified by an authorized KAESER SERVICE representative.
Further information Detailed information for the various messages can be found in the user manual
SIGMA CONTROL 2.
I
IM
er:
Connect dryer transformer in
PR
Machine runs but produces no Inlet valve not opening or only Call authorized KAESER Serv‐
compressed air. opening partially. ice representative.
Venting valve not closing. Call authorized KAESER Serv‐
ice representative.
bj
Air consumption is greater than Check the air system for leaks.
the capacity of the compressor. Shut down the consumer(s).
ev Y
The differential between cut-in Check switching differential.
and cut-out pressure too is
n
small.
R R
Cooling oil leaking into the floor Hose coupling or maintenance Remove coupling or mainte‐
io
pan. hose still plugged into the nance hose.
quick-release coupling on the
is
Oil cooler leaking. Call authorized KAESER Serv‐
ice representative.
Leaking joints. Tighten joints.
Replace seals.
I
Cooling oil consumption too Unsuitable oil is being used. Use SIGMA FLUID cooling oil.
IM
high. Oil separator cartridge split. Change the oil separator car‐
tridge.
Oil level in the oil separator Drain off oil until the correct lev‐
tank too high. el is reached.
EL
10 Maintenance
10.1 Ensuring safety
Follow the instructions below to ensure safe machine maintenance.
Warning instructions are located before a potentially dangerous task.
ev Y
Complying with safety notes
n
Disregard of safety notes can cause unforeseeable dangers!
R R
➤ Follow the instructions in chapter 3 “Safety and Responsibility”.
io
➤ Maintenance work may only be carried out by authorized personnel.
➤ Use the safety sign below to advise others that the machine is currently being serviced:
o NA
is
Sign Meaning
Serious injury or death can result from activating the machine during service!
➤ Do not activate the machine.
I
Tab. 41 Warn others that the machine is being serviced.
IM
➤ Before switching on, make sure that nobody is working on the machine and all access doors
and panels are closed and locked.
➤ Switch off and lock out the power supply disconnecting device and verify the absence of volt‐
age.
PR
Compressed air is contained energy. Uncontrolled release of this energy can cause serious injury
or death. The following safety concerns relate to any work on components that could be under
bj
pressure.
➤ Close shut-off valves or otherwise isolate the machine from the compressed air network to en‐
sure that no compressed air can flow back into the machine.
Su
Touching the fan wheel, the coupling, or the drive while the machine is switched on can result in
serious injury.
➤ Switch off and lock out the power supply disconnecting device and verify the absence of volt‐
age.
➤ Do not open the cabinet while the machine is switched on.
ev Y
10.2 Following the maintenance plan
n
10.2.1 Logging maintenance work
R R
io
The maintenance intervals given are those recommended for KAESER original components
with average operating conditions.
o NA
➤ In adverse conditions, perform maintenance work at shorter intervals.
is
Adverse conditions are, e.g.:
■ high temperatures
■ much dust
■ high number of load changes
I
■ low load
IM
➤ Adjust the maintenance intervals with regard to local installation and operating condi‐
tions.
➤ Document all maintenance and service work.
EL
This enables the frequency of individual maintenance tasks and deviations from our recom‐
mendations to be determined.
According to the way a machine is equipped, sensors and/or maintenance interval counters moni‐
tor the operational state of important functional devices. Required maintenance work is shown on
SIGMA CONTROL 2.
➤ Reset the maintenance interval counter as described in the SIGMA CONTROL 2 operating
manual.
Su
➤ Take note of the controller's service messages and carry out tasks in a timely manner, taking
ambient and operating conditions into account:
ev Y
Drain condensate manually.
n
Up to 1000 h Clean the cooler. 10.4
R R
Check the air filter. 10.5
io
Cooler: 10.3
Clean the filter mat.
is
Up to 3000 h Cooler: 10.3
Change the filter mat.
Up to 6000 h Condensate drain: 10.17.2.2
At least every 2 years Change the service unit.
I
Display: Maintain the drive belt. 10.7
IM
➤ Please observe national regulations regarding the use of cooling oil in oil-injected screw com‐
pressors.
➤ Check operating conditions and adjust intervals as necessary.
ev Y
n
KAESER LUBRICANTS
SIGMA Lubricant Description Maximum Recommended Change Interval
R R
io
First oil change Subsequent oil change
M-460 ISO 46 Semi-Synthetic 2000 Hours 3000 Hours
o NA Lubricant
is
S-460 ISO 46 Synthetic Lu‐ 6000 Hours 8000 Hours
bricant
S-680 ISO 68 Synthetic Lu‐ 6000 Hours 8000 Hours
bricant
I
FG-460 ISO 46 Food Grade 2000 Hours 3000 Hours
Synthetic Fluid
IM
into account:
PR
ev Y
n
R R
io
o NA
is
Fig. 21 Filter mat
1 Filter mat
I
No tools are needed to remove the filter mat.
IM
Regular cleaning of the cooler ensures the reliable cooling of the machine and the compressed air.
Frequency of maintenance is mainly dependent on local operating conditions.
ec
ev Y
n
R R
io
Fig. 22 Oil cooler
1 Oil cooler
o NA
is
Cleaning the cooler
Do not use sharp objects to clean the cooler. It could cause damage.
Avoid creating clouds of dust.
➤ Dry brush the oil cooler and use a vacuum cleaner to suck up the dirt.
I
IM
sentative.
PR
ec
ev Y
n
R R
io
Fig. 23 Change the air filter
1 Fastener
2 Air filter
o NA
is
3 Air filter housing
1. Release the fasteners at the air filter housing and remove the air filter.
2. Clean all parts and sealing surfaces.
I
3. Insert the new air filter into the housing.
IM
The motor bearings of the compressor motor are permanently greased. Re-greasing is not neces‐
sary.
➤ Have the motor bearings checked by an authorized KAESER service representative during the
course of a visit.
tt
PR
➤ Switch off and lock out / tag out the power supply disconnecting device, verify the ab‐
sence of all voltage.
ev Y
n
R R
io
Fig. 24 Drive belt maintenance
1 Fixing screw 5 Tensioning device
2
o NA
Pivot point fixing screw 6 Belt guard
is
3 Tensioning nut 7 Turn lock
4 Markings 8 Belt pulley
Use the appropriate tool and secure the compressor motor while fitting the new drive belt.
1. Open turn locks 7 and remove the belt guard 6 .
2. Loosen the tensioning nut 3 by approx. 0.4 inches.
3. Undo all fixing screws 1 .
EL
4. Move the compressor motor aside and secure it in position with one of the screws 1 .
5. Place the new drive belt over the belt pulley.
6. Tension the belt with the tensioning nut 3 until both markings 4 coincide.
tt
and 2 .
ec
In order to check the safety relief valve's activating pressure, the machine's working pressure is
raised above the activating pressure of the valve.
ev Y
n
R R
io
o NA
is
I
IM
ev Y
n
R R
io
Fig. 26 Air receiver: Check the safety relief valve
1 Safety relief valve
2
o NA
Copper gasket
is
4 Service fitting
1. Loosen the safety relief valve 1 and remove together with the copper gasket 2 .
2. Fit the service fitting 4 with copper gasket 2 in place of the safety relief valve.
3. Carry out an inspection as described in section 10.8.3.
I
4. Switch the machine off and depressurize completely.
IM
The machine starts and runs under LOAD as long as the «ON» button is held down. Pressure in
the receiver to be checked rises. The time taken until the safety relief valve blows off depends on
PR
the volume of the air receiver. The machine switches to READY as soon as the «ON» button is
released.
ec
➤ Follow the detailed description of this procedure in the SIGMA CONTROL 2 operating
manual
➤ Never operate the machine without a correctly functioning safety relief valve.
➤ Have a defective safety relief valve replaced immediately.
bj
Excessive noise is caused when the safety relief valve blows off.
There is danger of scalding from hot oil.
There is danger of injury from bursting components and compressed air.
➤ Close the enclosure.
➤ Wear ear and eye protection.
➤ Abort the test if the working pressure rises 10 % above the activating pressure of the valve.
2. Log on to SIGMA CONTROL 2 with password access level 2.
3. Observe the display of pressure on SIGMA CONTROL 2 and call up the test function.
4. Risk of burns due to released cooling oil and compressed air when blowing off
the safety relief valve!
➤ Close all access doors, replace and secure all removable panels.
➤ Wear eye protection.
5. End the test as soon as the safety relief valve blows off or working pressure exceeds the ac‐
tuating pressure of the safety relief valve by nearly 14.5 psig.
6. If necessary, vent the machine and replace the defective safety relief valve.
7. Deactivate the test function.
ev Y
10.9 Checking the overheating safety shutdown function
n
R R
The machine should shut down if the airend discharge temperature reaches a maximum of 230 °F.
io
➤ Check the safety shutdown function as described in the SIGMA CONTROL 2 operating man‐
ual.
o NA
The machine does not shut down?
is
➤ Have the safety shutdown function checked by an authorized KAESER SERVICE repre‐
sentative.
The safety function of the EMERGENCY STOP push button is no longer ensured.
➤ Shut down the machine immediately and call an authorized KAESER SERVICE repre‐
sentative.
2. Turn the EMERGENCY STOP push button in the direction of the arrow to unlatch it.
3. Acknowledge the alarm message.
The ideal situation is with the oil level around the optimum mark when the machine is running.
Operating state Minimum oil level Maximum oil level
LOAD
ev Y
Tab. 45 Permissible cooling oil level under LOAD
n
Precondition The machine has been running at least 5 minutes under LOAD.
R R
io
o NA
is
I
IM
➤ Check the cooling oil level with machine running under LOAD.
Result As soon as the minimum level is reached: Replenish the cooling oil.
tt
The machine must be isolated from the compressed air network and completely vented be‐
fore undertaking any work on the pressure system.
Su
Material The maintenance hose with hose coupling and shut-off valve needed for venting is stowed beneath
the oil separator tank.
ev Y
n
R R
io
o NA
is
I
Fig. 29 Venting the machine
IM
7 Shut-off valve
➤ Close the user's shut-off valve between the machine and the air distribution network.
PR
If no shut-off valve is provided by the user, the complete air distribution network must be ven‐
ted.
ec
➤ Check that the oil separator tank pressure gauge reads 0 psig.
The pressure gauge does not read 0 psig after automatic venting?
➤ Make sure that the user's shut-off valve is closed or that the complete air system is ven‐
Su
ted.
➤ With the shut-off valve closed, insert the male plug in hose fitting 6 into the hose cou‐
pling 3 .
➤ Slowly open the shut-off valve 7 to release pressure.
➤ Disconnect the male plug in hose fitting 6 and close the shut-off valve 7 .
➤ If manual venting does not bring the oil separator tank pressure gauge to zero: Contact
an authorized KAESER service representative.
After shutting down the compressor and venting the oil separator tank, the machine is still un‐
der pressure from the air system or the section from the shut-off valve to the minimum pres‐
sure/check valve. The air cooler pressure gauge 9 shows this pressure.
1. With the shut-off valve closed, insert the male plug in hose fitting 6 into the hose coupling 1 .
2. Slowly open the shut-off valve 7 to release pressure.
The pressure gauge 9 on the air receiver indicates 0 psig.
3. Disconnect the male plug in hose fitting 6 and close the shut-off valve 7 .
ev Y
The air receiver pressure gauge does not read 0 psig after venting?
n
➤ Contact an authorized KAESER service representative.
R R
Result The machine is fully depressurized when both pressure gauges 2 and 9 show 0 psig after manual
io
venting.
o NA
is
10.13 Replenishing cooling oil
The machine must be isolated from the compressed air network and completely vented be‐
fore undertaking any work on the pressure system.
I
Material The maintenance hose with hose coupling and shut-off valve needed for venting is stowed beneath
IM
ev Y
n
Escaping oil mist is damaging to health.
R R
io
➤ Do not direct the maintenance hose at persons while venting.
➤ Do not inhale the oil mist.
o NA
is
Isolating the machine from the air system
➤ Close the user's shut-off valve between the machine and the air distribution network.
If no shut-off valve is provided by the user, the complete air network must be vented.
I
IM
The pressure gauge does not read 0 psig after automatic venting?
➤ Make sure that the user's shut-off valve is closed or that the complete air system is ven‐
ted.
tt
➤ With the shut-off valve closed, insert the male plug in hose fitting 6 into the hose cou‐
pling 3 .
PR
➤ If manual venting does not bring the oil separator tank pressure gauge to zero: Contact
an authorized KAESER service representative.
After shutting down the compressor and venting the oil separator tank, the machine is still un‐
der pressure from the air system or the section from the shut-off valve to the minimum pres‐
sure/check valve. The air receiver pressure gauge 9 shows this pressure.
Su
1. With the shut-off valve closed, insert the male plug in hose fitting 6 into the hose coupling 1 .
2. Slowly open the shut-off valve 7 to release pressure.
3. Disconnect the male plug in hose fitting 6 and close the shut-off valve 7 .
The air receiver pressure gauge does not read 0 psig after venting?
➤ Contact an authorized KAESER service representative.
Result The machine is fully depressurized when both pressure gauges 2 and 9 show 0 psig after manual
venting.
A sticker on the oil separator tank specifies the type of oil used.
1. Compressed air!
Compressed air and components under pressure can injure or cause death if the contained en‐
ev Y
ergy is suddenly released.
n
➤ Fully vent all pressurized components and enclosures.
2. The machine could be damaged by unsuitable oil!
R R
io
➤ Never mix different types of oil.
➤ Never top off with a different type of oil to that already used in the machine.
o NA
3. Slowly unscrew the filler plug 4 .
is
4. Top off to bring the oil to the correct level.
5. Replace the filler plug's sealing ring if necessary and screw the plug into the filler port.
2. Open the user's shut-off valve between the machine and the compressed air network.
3. Start the machine and check the oil level again after approx. 10 minutes of operation, top off if
necessary.
4. Switch off the machine and check for leaks.
EL
Compressed air helps to expel the oil. This compressed air can be taken either from the compres‐
sor itself or from an external source.
The machine must be isolated from the compressed air network and completely vented be‐
Su
ev Y
n
R R
io
o NA
is
I
IM
7 Shut-off valve
PR
ec
bj
Su
Changing the cooling oil with internal pressure Oil change with an external compressed air
source
The machine has been running for at least 5 mi‐ The power supply disconnecting device is
nutes in LOAD mode. switched off,
The machine is completely vented to atmos‐ lockout and tagout the device,
pheric pressure, verify the absence of any voltage.
i.e. both pressure gauges 2 and 9 (see Fig 29) The machine is completely vented to atmos‐
are showing 0 psig. pheric pressure,
1. Close the shut-off valve 10 in the venting i.e. both pressure gauges 2 and 9 (see Fig 29)
line. are showing 0 psig.
ev Y
2. Start the machine and watch the oil separa‐ An external source of compressed air is availa‐
n
tor tank pressure gauge 2 until it reads 43– ble.
R R
73 psig. 1. Close the shut-off valve 10 in the venting
io
3. Switch off the machine. line.
4. Wait at least 2 minutes to allow the oil to 2. With the shut-off valve closed, insert the
o NA
flow back to the separator tank. plug-in hose fitting 6 into the hose cou‐
pling 3 .
is
3. Connect the maintenance hose to the exter‐
nal air supply.
4. Open the shut-off valve 7 until the pressure
gauge 2 on the oil separator tank reads 43–
I
73 psig.
IM
➤ Turn the belt pulley only in the direction of the indicating arrow on the airend.
tt
PR
ec
bj
1
2 Belt guard
3 Belt pulley
ev Y
3. Place the other end of the maintenance hose in the oil receptacle and secure it in place.
n
4. Open the shut-off valve 11 .
R R
5. Slowly open the shut-off valve 7 in the maintenance hose and allow oil and air to drain com‐
io
pletely.
Pressure gauge on the oil separator tank indicates 0 psig.
o NA
6. Close the shut-off valve 11 and unplug the male plug-in hose fitting.
is
➤ Dispose of used oil in accordance with environment protection regulations.
1. Compressed air!
Compressed air and components under pressure can injure or cause death if the energy con‐
tained within is suddenly released.
➤ Fully vent all pressurized components and enclosures.
2. Slowly unscrew the filler plug 4 (see Fig. 31).
EL
2. Open the user's shut-off valve between the machine and the compressed air network.
3. Switch on the electrical power supply via the power supply disconnecting device and reset the
maintenance interval counter.
4. Start the machine and check the cooling oil level again after about 10 minutes, topping up if
bj
necessary.
5. Switch off the machine and visually check for leaks.
Su
All the cooling oil has run out of the filter 1–2 minutes after shutting down. A cooling oil receptacle
is not needed.
ev Y
➤ Wear long-sleeved clothing and protective gloves.
n
R R
io
o NA
is
I
IM
2 Direction to unscrew
3 Oil separator cartridge
tt
1. Unscrew the oil filter counterclockwise and wipe off any drops of oil.
2. Lightly oil the new filter's gasket.
ec
2. Open the user's shut-off valve between the machine and the air distribution network.
3. Switch on the power supply and reset the maintenance interval counter.
4. After approx. 10 minutes of operation: Check the cooling oil level and top off if necessary.
5. Switch off the machine and check for leaks.
ev Y
─ Oil filter
n
─ Air filter
R R
All the cooling oil has run out of the separator cartridge 1–2 minutes after shutting down. A cooling
io
oil receptacle is not needed.
1. Unscrew the oil separator cartridge counterclockwise and wipe off any drops of oil.
ev Y
3. Switch on the power supply and reset the maintenance interval counter.
n
4. Start the machine and run it for 10 minutes, then stop it and visually check for leaks.
R R
io
10.17 Maintaining the refrigerated dryer
o NA
Repairs may only be carried out by certified personnel.
is
Material Compressed air for blowing out
Cleaning cloth
Vacuum cleaner
I
IM
EL
tt
PR
ec
damaged.
Avoid creating clouds of dust.
ev Y
The Power LED lights.
The sight glass is removed.
n
R R
io
o NA
is
I
Fig. 36 Checking the condensate drain
IM
1 Power LED
2 «TEST» key
Result As soon as the condensate drain opens, you will feel a short burst at the condensate line.
PR
Service the condensate drain if you do not experience a burst during manual test.
ec
The condensate drain cannot be cleaned. The service unit must be changed if condensate does
not drain.
bj
ev Y
n
R R
io
o NA
is
I
Fig. 37 Changing the service unit
IM
1.
PR
Serious injury or death can result from loosening or opening components under
pressure!
ec
5. Carefully loosen the union nut 13 at the shut-off valve 9 until remaining residual air has esca‐
ped through the venting holes.
6. Unscrew the screw-in part 11 from the service unit and place aside.
Su
Use only genuine KAESER service units to ensure correct function of the condensate drain.
Precondition Make sure that the top of the service unit and the contact springs are clean and dry.
2. Carefully insert the sensor 3 of the control module 2 in the opening 4 of the service unit.
3. Place the snap fastener 5 of the control module into the service unit eyes.
4. Press the control module against the service unit until the snap fastener can be heard clicking
into place.
5. At the screw-in part 11 , replace old sealing material with new sealing tape.
6. Install the screw-in part in the service unit.
7. If necessary, insert a new O-ring 10 .
8. Tighten the union nut 13 at the shut-off valve 9 .
9. Attach the condensate hose.
ev Y
10. Open the shut-off valve upstream of the condensate drain.
n
11. Replace the enclosure.
R R
io
10.18 Air receiver maintenance
o NA
Condensate is removed automatically by the refrigerated dryer's condensate drain. A dirt trap pro‐
is
tects the condensate drain from contamination that would impair its function. The condensate drain
only functions when the dryer is in operation.
➤ Condensate can be drained manually from the air receiver when the dryer is not operat‐
ing.
I
IM
Material If required:
Dirt trap strainer
O-ring
EL
tt
PR
ec
3 8
4 O-ring 9 Hose coupling (condensate drainage)
6 Male plug in hose fitting 11 Shut-off valve (condensate drainage)
7 Shut-off valve
Su
ev Y
Wear eye and hearing protection.
n
1. With the shut-off valve closed, insert the male plug in hose fitting 6 into the hose coupling 9 .
R R
io
2. Open the shut-off valve 11 .
3. Slowly open the shut-off valve 7 in the maintenance hose and allow the condensate to drain
completely.
o NA
is
All condensate is drained when only compressed air is blown out.
4. Close the shut-off valve 11 and unplug the male plug in hose fitting.
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
KAESER spare parts and operating materials are all genuine KAESER parts. They are specifically
R R
designed for use in KAESER machines.
io
Unsuitable or poor quality spare parts and operating fluids/materials may result in damage to the
machine or significantly impair its proper function.
o NA
Damage to the machine can also result in personal injury.
is
There is risk of personal injury or damage to the machine resulting from the use of unsuita‐
ble spare parts or operating fluids/materials!
➤ Use only original parts and operating fluids/materials.
I
➤ Have an authorized KAESER service representative carry out regular maintenance.
IM
Name Number
Air filter cartridge 1250
Filter mat 1050
EL
Service module
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
SEG-5405_01
Kondensatableiter / Condensate drain
Service-Kit
( Option )
ev Y
n
R R
io
o NA
is
I
6307
9022
IM
EL
tt
PR
ec
bj
Su
9603
9602
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
➤ The following tasks are to be performed by authorized personnel only.
n
12.1.1 Temporary decommissioning
R R
io
Precondition The machine can be started at regular intervals.
o NA
➤ Run the machine once a week for at least 30 minutes under LOAD to ensure sufficient protec‐
tion against corrosion.
is
12.1.2 Long-term decommissioning
Precondition Immediately prior to decommissioning, run the machine under LOAD for at least 30 minutes.
I
IM
If the machine is equipped with a condensate drain, drain condensate from the condensate drain.
1. Drain condensate from the condensate drain and dispose of according to applicable environ‐
mental protection regulations.
2. Remove the user-supplied condensate lines.
tt
The condensate drains are not supplied with power when the machine is switched off?
➤ Detach and drain the condensate drains.
PR
ec
12.2 Packing
A wooden crate is required for overland transport to protect the machine from mechanical damage.
Other measures must be taken for the transport of machines by sea or air. Please contact an au‐
thorized KAESER SERVICE representative for more information.
Material Desiccant
Plastic sheeting
Wooden crate
ev Y
2. Wrap the machine fully in plastic sheeting.
n
3. Protect the machine in a wooden crate against mechanical damages.
R R
io
12.3 Storage
o NA
Moisture can lead to corrosion, particularly on the surfaces of the airend and in the oil separator
is
tank.
Frozen moisture can damage components, valve diaphragms and gaskets.
The following measures also apply to machines not yet commissioned.
Please consult with KAESER if you have questions to the appropriate storage and commis‐
I
sioning.
IM
12.4 Transport
tt
12.4.1 Safety
PR
Weight and center of gravity determine the most suitable method of transportation. The center of
ec
Precondition Transport only by forklift truck or suitable lifting gear and only by personnel trained in the safe
transportation of loads.
ev Y
1. Machine damage caused by an unsecured enclosure.
n
➤ Prior to transporting, remove the enclosure and transport separately.
R R
2. Take note of the center of gravity.
io
3. Drive the forks completely under the machine or pallet and lift carefully.
12.4.3
o NA
Transport with a crane
is
Only suitable and approved load-carrying and attachment devices ensure proper transport of the
machine with a crane. Suitable crossbeams ensure sufficient distance of the attachment resources
from the machine housing to prevent damage.
The machine is not equipped with fixing points.
I
Examples of unsuitable fixing points:
IM
■ Pipe sockets
■ Flanges
■ Attached components such as centrifugal separators, condensate drains, or filters
■ Rain protection covers
EL
➤ Consult KAESER if you require suitable load-carrying and attachment devices or have
questions regarding the correct use.
tt
Precondition Load-carrying and attachment devices meet the local safety regulations.
PR
The crane, load-carrying and attachment devices or the lifted machine do not endanger personnel.
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
Fig. 40 Transporting with a crane
IM
ces!
➤ Comply with permissible load limits.
➤ Comply with specific safety information of used load-carrying and attachment devices.
tt
■ Ensure proper distribution of the fixing points relative to the center of gravity position (sym‐
metrical load distribution).
ec
■ Ensure equal slope angles of 15° to 45° for attachment devices with multiple strands.
─ Slope angles between 45° and 60° may be unsuitable.
─ Slope angles larger than 60° are prohibited.
■ Ensure the maximum incline of 6° of the machine to the horizontal.
bj
12.5 Disposal
When disposing of a machine, drain out all liquids and remove old filters.
ev Y
ment protection regulations.
n
R R
Compressors with refrigeration dryers
io
The refrigerant circuit still contains both refrigerant and oil.
➤ Refrigerant and oil must be drained and disposed of by authorized personnel.
o NA
is
12.5.1 Battery disposal in accordance with local environmental regulations.
Batteries contain substances that are harmful to living beings and the environment. For this reason,
batteries must not be disposed of with unsorted residential waste. They must be disposed of in ac‐
cordance with local environmental regulations. This procedure facilitates the handling and recycling
I
of batteries.
IM
Further information Refer to the SIGMA CONTROL 2user manual for details regarding battery removal and replace‐
ment.
Su
13 Annex
13.1 Pipeline and instrument flow diagram (P+I diagram)
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
Air cooling
5 5/8
Machine mountings
1 1/8
Air discharge
10 3/8
bj
4
Y
11 1/8
44 1/8 9
K1
H1
Code:
ec
PR
tt
Air discharge
2 1/2
Cooling air outlet
2 1/4
ATTENTION!
Y
Electrical connections
CG : Centre of gravity
CG
EL
15
19 3/8
24 3/8
1/8
1 3/4
11 3/4
7 3
is
o NA
Status
Änderungs-Nr.
Dokument TZD
Dokument TZM
io
FREIGEGEBEN
R R
10219789 D 00
10219789 USE 00
Projektion
n
58
ev Y
A3
Original
35 5/8 7 7/8
Maßstab
Bezeichnung
27 1/2
3 3/4
Gez.
SXC.2 K1
Bearb.
d i a. 3 7/8
13 1/4
3 7/
8
d ia
Name
. 1/
38 5/8
2
33 7/8
28 1/8
H1
USE
Sprache
1/8
1 1/2
5 1/2
Blatt
6 3/4
5 1/2
1 von 1
02.02.2012
Dimensional Drawing 13.2
Annex 13
13 Annex
13.3 Electrical Diagram
ev Y
n
R R
io
o NA
is
I
IM
EL
tt
PR
ec
bj
Su
9_6917 43 USE
Wiring Diagram
ATTENTION !!! AIRTOWER 3C/4C/5C/7.5C
The unit is non-functional when delivered.
Before connecting the electrical supply,
PR
13
Power supply:
bj EL
WYE system with center point solidly grounded
Electrical Diagram
103
n
104
Lfd. Nr. Benennung Zeichnungsnummer (Kunde) Zeichnungsnummer (Hersteller) Blatt Anlagenkennzeichen
No. Name Drawing No. (customer) Drawing No. (manufacturer) Page Unit designation
1 cover page DSXC-U3107.00 1
2 list of contents ZSXC-U3107.00 1
3 general instructions USXC-U3107.00 1
4 electrical component parts list USXC-U3107.00 2
5 electrical component parts list USXC-U3107.00 3
6 wiring diagram power supply, refrigeration dryer SSXC-U3107.00 1
7 wiring diagram power unit SSXC-U3107.00 2
8 wiring diagram control SSXC-U3107.00 3
13
13.3
PR
9 wiring diagram air dryer control SSXC-U3107.00 4
10 wiring diagram control voltage tapping SSXC-U3107.00 5
Su
11 wiring diagram power supply unit SSXC-U3107.00 6
12 wiring diagram IO-module configuration SSXC-U3107.00 7
13 wiring diagram sensors/actuators SSXC-U3107.00 8
14 wiring diagram volt-free contacts SSXC-U3107.00 9
Annex
9_6917 43 USE
n
1 2 3 4 5 6 7 8
general instructions
9_6917 43 USE
control cabinet wiring for non-designated conductors
ATTENTION !!! primary circuits ungrounded: black, UL-Style 1015, CSA-TEW
Install supplies, grounding and shock protection primary circuits grounded: grey, UL-Style 1015, CSA-TEW
to local safety regulations. control voltage AC 115V ungrounded: red, 18AWG UL-Style 1015, CSA-TEW
Do not make or break control voltage AC 115V grounded: white, 18AWG UL-Style 1015, CSA-TEW
live plug-in connectors.
PR
control voltage DC ungrounded: blue, 18AWG UL-Style 1015, CSA-TEW
13
13.3
bj EL
Electrical Diagram
-M4 vent motor Oil cooler -X7 power supply unit, digital inputs -3X31 terminalbox refrigeration dryer
-Q1 main contactor -X8 digital inputs, digital outputs
-Q2 delta contactor -X9 analog inputs, 4-20mA, Pt100
-Q3 wye contactor -X10 Relay outputs sensors/actuators
o NA
-Q4 motor starter vent motor oil cooler -B1 pressure transducer Network pressure
-S1 EMERGENCY STOP pushbutton -B2 safety air pressure switch-direction of rotation
-T11 control transformer -B30 safety pressure controller
-T21 power unit -B40 temperature probe airend discharge temperature
R R
-K1 bypass valve
refrigeration dryer
-4FU fuses
-K34 condensate drain
-M30 compressor motor
ev Y
-M31 vent motor
-Q30 motor starter
-P34 indicating light mains voltage refrigeration dryer
is
c Date 13.03.2019 general instructions =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 1
SC2 MCSIO USXC-U3107.00
C Change Date Name 3 Sht.
io
105
n
13 Annex
13.3 Electrical Diagram
2
3 Sht.
page
model
AIRTOWER 3 C AIRTOWER 4 C AIRTOWER 5 C AIRTOWER 7.5 C
machine power supply 208 V ±10 %, 60 Hz 208 V ±10 %, 60 Hz 208 V ±10 %, 60 Hz 208 V ±10 %, 60 Hz
230 V ±10 %, 60 Hz 230 V ±10 %, 60 Hz 230 V ±10 %, 60 Hz 230 V ±10 %, 60 Hz
USXC-U3107.00
+
=
motor -M1 3 hp 4 hp 5 hp 7,5 hp
diagram 1, Sht. 2 (208+ 230 V) diagram 1, Sht. 2 (208+ 230 V) diagram 1, Sht. 2 (208+ 230 V) diagram 1, Sht. 2 (208+ 230 V)
supply terminals -X01:1U/1V/1W 7.3149.01890 7.3149.01890 7.3149.01890 7.3149.01890
Wieland WKFN6D1/2/35 WKFN6D1/2/35 WKFN6D1/2/35 WKFN6D1/2/35
Stripped length 12 mm 12 mm 12 mm 12 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
-X01:GRD 7.3149.01910 7.3149.01910 7.3149.01910 7.3149.01910
Wieland WKFN6D1/2/SL/35 WKFN6D1/2/SL/35 WKFN6D1/2/SL/35 WKFN6D1/2/SL/35
Stripped length 12 mm 12 mm 12 mm 12 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
SC2 MCSIO
ev Y
-X02:2U / -4FU 7.3320.00050 7.3320.00050 7.3320.00050 7.3320.00050
Wieland AMBUS EASYSWITCH AMBUS EASYSWITCH AMBUS EASYSWITCH AMBUS EASYSWITCH
n
Torque 22 lb-in 22 lb-in 22 lb-in 22 lb-in
Stripped length 11 mm 11 mm 11 mm 11 mm
R R
-X02:N 7.3149.01810 7.3149.01810 7.3149.01810 7.3149.01810
io
Wieland WKFN4/35 WKFN4/35 WKFN4/35 WKFN4/35
Stripped length 11 mm 11 mm 11 mm 11 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
AIRTOWER 3C/4C/5C/7.5C
-X02:GRD
Wieland
7.3149.01830
WKFN4SL/35
o NA
7.3149.01830
WKFN4SL/35
7.3149.01830
WKFN4SL/35
7.3149.01830
WKFN4SL/35
is
Stripped length 11 mm 11 mm 11 mm 11 mm
setting: 4,6 A (208 V) setting: 6,2 A (208 V) setting: 8,3 A (208 V) setting: 10,9 A (208 V)
setting: 4,3 A (230 V) setting: 5,8 A (230 V) setting: 8,3 A (230 V) setting: 10,4 A (230 V)
PR
NEC 430.32(C) incremental NEC 430.32(C) incremental NEC 430.32(C) incremental NEC 430.32(C) incremental
setting: 5,2 A (208 V) setting: 6,9 A (208 V) setting: 9,3 A (208 V) setting: 12,2 A (208 V)
Siemens setting: 4,8 A (230 V) setting: 6,5 A (230 V) setting: 9,3 A (230 V) setting: 11,6 A (230 V)
ec
13.03.2019
Taubmann
Büchner
EMERGENCY STOP pushbutton -S1 7.3217.0 / QRUV 7.3217.0 / QRUV 7.3217.0 / QRUV 7.3217.0 / QRUV
auxiliary contact Schlegel 7.3218.0 / MHTOO 7.3218.0 / MHTOO 7.3218.0 / MHTOO 7.3218.0 / MHTOO
indicator light -P34 7.5720.0 7.5720.0 7.5720.0 7.5720.0
Date
3
3 Sht.
page
model
AIRTOWER 3 C AIRTOWER 4 C AIRTOWER 5 C AIRTOWER 7.5 C
machine power supply 460 V ±10 %, 60 Hz 460 V ±10 %, 60 Hz 460 V ±10 %, 60 Hz 460 V ±10 %, 60 Hz
USXC-U3107.00
motor -M1 3 hp 4 hp 5 hp 7,5 hp
+
=
diagram 2, Sht. 2 (460 V) diagram 2, Sht. 2 (460 V) diagram 2, Sht. 2 (460 V) diagram 2, Sht. 2 (460 V)
supply terminals -X01:1U/1V/1W 7.3149.01890 7.3149.01890 7.3149.01890 7.3149.01890
Wieland WKFN6D1/2/35 WKFN6D1/2/35 WKFN6D1/2/35 WKFN6D1/2/35
Stripped length 12 mm 12 mm 12 mm 12 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
-X01:GRD 7.3149.01910 7.3149.01910 7.3149.01910 7.3149.01910
Wieland WKFN6D1/2/SL/35 WKFN6D1/2/SL/35 WKFN6D1/2/SL/35 WKFN6D1/2/SL/35
Stripped length 12 mm 12 mm 12 mm 12 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
-X02:2U / -4FU 7.3320.00050 7.3320.00050 7.3320.00050 7.3320.00050
SC2 MCSIO
ev Y
Wieland AMBUS EASYSWITCH AMBUS EASYSWITCH AMBUS EASYSWITCH AMBUS EASYSWITCH
Torque 22 lb-in 22 lb-in 22 lb-in 22 lb-in
n
Stripped length 11 mm 11 mm 11 mm 11 mm
-X02:N 7.3149.01810 7.3149.01810 7.3149.01810 7.3149.01810
R R
Wieland WKFN4/35 WKFN4/35 WKFN4/35 WKFN4/35
io
Stripped length 11 mm 11 mm 11 mm 11 mm
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
-X02:GRD 7.3149.01830 7.3149.01830 7.3149.01830 7.3149.01830
AIRTOWER 3C/4C/5C/7.5C
Wieland
Stripped length
WKFN4SL/35
11 mm
o NA
WKFN4SL/35
11 mm
WKFN4SL/35
11 mm
WKFN4SL/35
11 mm
is
Handling fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12 fig. 2, Sht. 12
NEC 430.32(C) incremental NEC 430.32(C) incremental NEC 430.32(C) incremental NEC 430.32(C) incremental
Siemens setting: 2,4 A setting: 3,3 A setting: 4,7 A setting: 5,8 A
PR
Block B0406056 (160 VA) B0406056 (160 VA) B0406056 (160 VA) B0406056 (160 VA)
power supply -T21 7.7605P0 7.7605P0 7.7605P0 7.7605P0
Prodrive PSDC24/2.5 PSDC24/2.5 PSDC24/2.5 PSDC24/2.5
cables -W19.1 7G14 AWG 7G14 AWG 7G12 AWG 7G12 AWG
600 V, 90°C 600 V, 90°C 600 V, 90°C 600 V, 90°C
Su
13.03.2019
Taubmann
Büchner
cables -W19.2 6x14 AWG 6x14 AWG 6x12 AWG 6x12 AWG
600 V, 90°C 600 V, 90°C 600 V, 90°C 600 V, 90°C
compressor control -K20 7.9700.0 7.9700.0 7.9700.0 7.9700.0
Prodrive SIGMA CONTROL 2 MCSIO SIGMA CONTROL 2 MCSIO SIGMA CONTROL 2 MCSIO SIGMA CONTROL 2 MCSIO
Released
Drawn
Date
EMERGENCY STOP pushbutton -S1 7.3217.0 / QRUV 7.3217.0 / QRUV 7.3217.0 / QRUV 7.3217.0 / QRUV
auxiliary contact Schlegel 7.3218.0 / MHTOO 7.3218.0 / MHTOO 7.3218.0 / MHTOO 7.3218.0 / MHTOO
Name
1L1
/2.1
1L2
/2.1
1L3
/2.1
11L1
/5.1
11L2
/5.1
GRD
/2.1
12AWG green/yellow
600V 90°C
GRD2
1GRD
13
PR
X2
-P34
Su
14AWG
mains voltage air dryer
X1
grey
green
600V 90°C
10AWG green/yellow
18AWG
600V 90°C 14AWG
Annex
18AWG
1GRD
-X01 red
stickers on outside black red 18AWG
600V 90°C
of cabinet 600V 90°C 600V 90°C white
EL
-X30 600V 90°C
bj
control panel 1
Warning!
Mortal danger from multiply power supplies! 10AWG green/yellow -X30
Electrical Diagram
2
6
-Q30
1GRD
Touching electrically live components can cause -X01
18AWG
1
2
GNYE
7A Class CC
2
Isolate the machine from all power phases. 5G14AWG 5G14AWG
pivoting motor base
14AWG
600V 90°C 600V 90°C
green/yellow
1GRD
2GRD
2N
-X01
-X02
-X02
-4FU
I distribution terminal box in the dryer -3X31 GRD
600V 90°C
1V
1U
1W
tt
3 wire + 1 ground 2 wire + 1 ground
2U
power supply cable power supply cable -3X31 1 -3X31 1 -3X31 1
for compressor for refrigerated dryer N N N base plate air dryer
-F0.1 GRD GRD
-F0.2
o NA
15A Class J
-W170 -W171 -W80
main disconnect,
2
4
6
8
10
-Q0 3G14AWG 3G18AWG 2x18AWG
fuse supplied
600V 90°C 600V 90°C 600V 90°C
by user
R R
L/+
N/-
1
3
5
7
9
For field wiring:
L1
L2
GRD
L1
L2
GRD
-K34
Use 75°C copper
supply line cross-section ande conductors only! M M
2N
fusing see operating manual
1L1
1L2
1L3
2L1
Feed line connection 1~ 1~
1GRD
2GRD
see page 12
3-phase power supply for the compressor additional 115V, 1-ph, 60Hz power supply
ev Y
-M30 -M31
according to the machine nameplate for the refrigeration dryer
Function: input voltage input voltage compressor motor vent motor condensate drain
Group of function: compressor refrigeration dryer power unit refrigeration dryer refrigeration dryer
=
c Date 13.03.2019
is wiring diagram
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 1
D Change Date Name power supply, refrigeration dryer SC2 MCSIO SSXC-U3107.00 12 Sht.
io
9_6917 43 USE
n
1 2 3 4 5 6 7 8
1L1
/1.8
1L2
9_6917 43 USE
/1.8
1L3
/1.8
12AWG 12AWG
PR
13
1
3
5
1
3
5
1
3
5
1
3
5
1
3
5
1
3
5
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
ATTENTION !!!
component -B25 14AWG Adjust the setting 14AWG
black depending on black
Electrical Diagram
3
5
3
5
97
95
97
95
Adjust the setting -B25 600V 90°C the mains voltage -B25 600V 90°C
ec
depending on
IM
**** Use the ****
2
4
6
2
4
6
98
98
96
overload relay
with suitable
/3.3 96
Use the
-W19.1 setting range -W19.1
overload relay
**** ****
with suitable -W19.2
I
GRD
W3 V4
setting range ****
tt
ATTENTION !!! W1 V2
GRD
W3 V4 component -M1,-X1
ATTENTION !!! V3 U4
component -M1 W1 V2
Check the correct M
V1 U2
V3 U4 connection of 3~
Check the correct
o NA
M the motor according U3 W4
connection of V1 U2
3~ to the mains voltage
the motor according U1 -M1 W2
U3 W4
to the mains voltage ****
-W19.2
U1 -M1 W2
R R
****
**** -X1 3
2
diagram 1 1
208V/230V diagram 2
ev Y
460V
**** performance-related components,
see: electrical component parts list
109
n
110
1 2 3 4 5 6 7 8
95
21
-B25 -Q1
/2.2 2
96
22
7
13
X7 X7
10
X7
11
13.3
PR
-K20 -K20 -K20
DI_PA DI 1.01 DI 1.02
Su
/7.2 /7.2 /7.2
11
10
9
2
1
X10 X10 X10 X10
13
13
21
21
-Q1 -Q3 -Q2 -Q3
2 3 4 3
I
14
14
22
22
tt
A1
A1
A1
A1
-Q1 -Q3 -Q2 -Q4
A2
A2
A2
A2
o NA
-X11 01 L02
/5.1
1 2 1 2 1 2 1 2
/2.2 /2.4 /2.3 /5.5
3 4 3 4 3 4 3 4
R R
/2.2 /2.4 /2.3
5 6 5 6 5 6 5 6
/2.2 /2.4 /2.3
13 14 13 14 13 14 13 14
2 3
21 22 21 22 21 22
4 4 3
31 32
/9.4
43 44
/9.5
ev Y
Function:
Group of function: wye-delta changeover
=
c Date 13.03.2019
is wiring diagram
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 3
control SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
9_6917 43 USE
n
1 2 3 4 5 6 7 8
-X31 7 2L+
9_6917 43 USE
/6.4
3
-W179
2
-3X31
1
-W172
-B30
P
PR
13
13.3
>21 bar
Su
2
-W172 safety air pressure switch
(Pressure limiter) Refrigerant compressor
3
-3X31 -K20 -K20
DI 1.03 DOR 1.03
/7.2 /7.2
4
-W179
Annex
12
4
5
X7 X10
bj EL
8
-X31
10
-X31
Electrical Diagram
A1
-Q30
o NA
A2
2L-
/6.4
R R
1 2
/1.5
3 4
5 6
/1.5
13 14
ev Y
Function:
Group of function:
is
c Date 13.03.2019 wiring diagram =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 4
air dryer control SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
111
n
112
1 2 3 4 5 6 7 8
11
21
-S1
600V 90°C 600V 90°C 600V 90°C
-X11 GRD2
1
3
5
22
12
-1FU -2FU -3FU EMERGENCY STOP
2
1,5A 1,5A 1,5A -Q4
2
4
6
Class CC Class CC Class CC /3.5
13
1
3
13.3
-X11
PR
8
9
14AWG black X7
14AWG
Su
600V 90°C 14AWG
black -K20 DI_PA DI
black
14AWG green/yellow 600V 90°C DI 1.00
600V 90°C /7.2
600V 90°C
4
-T11 -X11 EMERGENCY STOP
Annex
-X11 GRD1
8
7
14AWG X10
5
grey model-specific -X11
U1
Z
U2
GRD
of the transformer according
600V 90°C electrical diagram
03
-X11
1~ -K20-X10:1
/3.6 P+
16AWG green/yellow
600V 90°C -M4
0,73A
I
GRD1
-X11
tt
L02 -X11 02 02 L02
/3.6 /6.1
o NA
R R
ev Y
Function: 115V/1ph/60Hz EMERGENCY STOP
Group of function: control voltage tapping safety chain
=
c Date 13.03.2019
is wiring diagram
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 5
control voltage tapping SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
9_6917 43 USE
n
1 2 3 4 5 6 7 8
9_6917 43 USE
/5.8
L02 01 L02
/5.8
-K20
MCS
1x4mm² X5
PR
1x2,5mm²
SD card
13
green/yellow
13.3
green/yellow
500V 70°C
Su
-X11 GRD2 500V 70°C X6
P24
M24
Ethernet RS485-FC
1
2
X7
control cabinet door X1 X3
/7.2
Annex
bj EL
Electrical Diagram
24V=
+
-
tt I
N - 2L-
/4.5
2,5A -
short circuit proof
1x1,5mm²
o NA
green/yellow
500V 70°C
GRD2
-X11
R R
ev Y
1) Reset: Switch off L1 for 3 minutes
Function: 24V DC
Group of function:
is
control voltage
c Date 13.03.2019 wiring diagram =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 6
power supply unit SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
113
n
9_6917 43 USE AIRTOWER 3C–7.5C Tri-Voltage 114
Operator Manual Screw Compressor
c
a
b
Function:
D Change
1
Group of function:
Date
Name
Date
Drawn
Released
2
-K20
Büchner
Taubmann
13.03.2019
Su
1
P24 24V /6.4
2
M24 0V /6.4
3
IOM
DI_PA
4
DI_PA
bj
5
DI_PA
6
DI_PA
3
7
DI_PA /3.2
X7
8
DI_PA /5.7
9
DI 1.00 /5.7
ec
10
DI 1.01 /3.3
11
DI 1.02 /3.4
PR
12
DI 1.03 /4.3
13
DI 1.04
tt
14
DI 1.05
1
4
DI_PA /8.5
2
DI 1.06 /8.5
3
DI_PA
EL
4
DI 1.07
5
DOT 1.00 /8.7
X8
6
M /8.7
7
DOT 1.00 /8.6
8 /8.6
M
IM
9
DOT 1.01
5
10
I
M
/3.5 1 1 /8.2
DOR COM AII_PA
wiring diagram
/3.5 2 2 /8.2
DOR 1.04 AII 1.00
3 3 /8.2
FE
IO-module configuration
/4.4 4 4
DOR COM GND
/4.4 5 5
DOR 1.03 AII_PA
is
6 6
AII 1.01
X10
o NA
AIRTOWER 3C/4C/5C/7.5C
7 7
DOR COM FE
6
X9
8 8 /8.3
/5.7 DOR COM AIR 1.00
/3.4 9 9 /8.3
io
DOR 1.02 AIR 1.00
/3.3 10 10 /8.3
R R
DOR 1.01 FE
/3.2 11 11
DOR 1.00 AIR 1.01
12
n
AIR 1.01
13
FE
ev Y
SC2 MCSIO
7
+
=
SSXC-U3107.00
8
page
12 Sht.
7
Electrical Diagram 13.3
Annex 13
1 2 3 4 5 6 7 8
9_6917 43 USE
-B1 -B40
P
1
-B2
4...20mA P
2
Pt100
+ - >1,0 bar
1
2
1
4
PR
13
13.3
1
2
BN
BK
1
2
-W115 -W117 -W104
Su
2x0,5mm² 2x0,34mm² 2x0,5mm²
500V 70°C 250V 80°C 500V 70°C
Annex
1
2
3
8
9
1
2
X9 X9 X8
10
bj EL
-K20 AII_PA AII FE -K20 AIR_A AIR_B FE -K20 DI_PA DI
8
6
X8 X8
tt I
24VDC / max. 0,1A
1
2
R R
1
2
-K1
ev Y
Function:
Group of function:
is
c Date 13.03.2019 wiring diagram =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 8
sensors/actuators SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
115
n
116
1 2 3 4 5 6 7 8
13
13.3
PR
volt-free contacts
Su
User's connection
Annex
bj EL
31
43
-Q1 -Q1
/3.2 /3.2
Electrical Diagram
16
17
15
IM
-X11 -X11 -X11
9_6917 43 USE
n
1 2 3 4 5 6 7 8
9_6917 43 USE
Inputs/outputs for use by others ** pre-allocated
*** available for use
example connections
For Field Wiring:
digital output, User's connection
Use Copper Conductors Only!
24V DC/0,3A
Connect Control Device Only!
max. cable length 30m
PR
13
13.3
control ON **
Su
-K20 DOT 1.01
DOT M
9
10
X8
Annex
bj EL
possible connections for AII 1.01
Electrical Diagram
4
5
3
4
4
5
6
7
4
5
6
7
X7 X7 X8 X9 X9
13
14
11
12
13
R R
-K20 DI_PA DI -K20 DI_PA DI -K20 DI_PA DI -K20 GND AII_PA AII FE -K20 GND AII_PA AII FE -K20 AIR_A AIR_B FE
117
n
118
1 2 3 4 5 6 7 8
1L1
1L2
-1FU
-2FU
not connected (nc) correctly
on the primary side.
13
0
13.3
nc
Therefore the compressor
PR
208V
230V
460V
-T11 is non-functional at the
Su
-X11 GRD2 status on delivery !
Connect the line L2 to the
Annex
0
115V
correct transformer terminal
according to the mains voltage.
bj EL
L02
-3FU
Electrical Diagram
1L1
1L2
1L1
1L2
1L1
1L2
-1FU
-2FU
-1FU
-2FU
-1FU
-2FU
o NA
0
0
0
nc
nc
nc
208V
230V
460V
208V
230V
460V
208V
230V
460V
0
115V
0
115V
0
115V
ev Y
L02
-3FU
L02
-3FU
L02
-3FU
c Date 13.03.2019
is wiring diagram =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 11
transformer diagrams SC2 MCSIO SSXC-U3107.00
D Change Date Name 12 Sht.
io
9_6917 43 USE
n
1 2 3 4 5 6 7 8
fig. 1: Handling: Control line terminal fig. 10: Feed line connection
9_6917 43 USE
PR
13
13.3
Su
Annex
bj EL
Electrical Diagram
119
n
120
cable-no.
-W19.2 connection 460V
-W19.1 ****
13
13.3
PR
1
3
3
5
1
V3
U3
W3
connection
GRD
Su
GRD1
inside
destination
name of device
-1FU
-Q1
-2FU
-Q1
-X11
-M1
-M1
-M1
-M1
control panel
-Q1
Annex
location
/1.2
/1.2
/1.3
/2.3
/2.6
/2.6
/2.6
/1.3
/1.2
bj EL
jumper wire
Electrical Diagram
total 9 terminals
total 3 terminals
terminal strip
1U
1V
1V
1W
1GRD
1GRD
1
2
3
1GRD
1U
1GRD
V2
U2
W2
connection
I
external
destination
tt
name of device
-supply
-supply
unit frame
-M1
-M1
-M1
-supply
-supply
-W19.2 connection 460V
-s.b.c. *
o NA
cable-no.
R R
ev Y
* supply line cross-section
see operating manual
**** performance-related components,
see: electrical component parts list
s.b.c. = supplied by customer
c Date 13.03.2019
isterminal connection =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 1
H Change Date Name terminal strip -X01,-X1 SC2 MCSIO KSXC-U3107.00 2 Sht.
io
9_6917 43 USE
n
121 AIRTOWER 3C–7.5C Tri-Voltage 9_6917 43 USE
Operator Manual Screw Compressor
c
a
b
destination destination
cable-no. terminal strip cable-no.
inside external
H Change
link
location
connection
connection
jumper wire
terminal-no.
Date
name of device
name of device
terminal legend
Name
-W80 2x18AWG 600V 90°C
-W29 4G20AWG 600V 90°C
-W172 2x18AWG 600V 90°C
Date
Drawn
Released
Büchner
Taubmann
13.03.2019
Su
-T11 0 03 /5.2
-Q4 1 4 /5.5 -M4 U1
BU BN
-Q1 43 15 /9.4 1)
-Q1 32 16 /9.4 1)
-Q1 44 17 /9.5 1)
PR
18
tt
4 3
2 1
1
1
terminal connection
1
1
2
2
2
2
is
GN
YE
o NA
AIRTOWER 3C/4C/5C/7.5C
GN
-X11 GRD2 GRD /1.7 base plate air dryer
YE
io
R R
n
ev Y
SC2 MCSIO
GNYE = green/yellow
+
=
KSXC-U3107.00
page
2
2 Sht.
Electrical Diagram 13.3
Annex 13
122
1 2 3 4 5 6 7 8
-C4
13
13.3
PR
-X11
-X30
Su
-X31
-Q30
Annex
-Q4
-1FU
-2FU
EL
-3FU
bj
-4FU
-X02
Electrical Diagram
-X1
c Date 13.03.2019
is lay-out =
b Drawn Taubmann +
a Released Büchner
AIRTOWER 3C/4C/5C/7.5C page 1
Switchboard SC2 MCSIO ASXC-U3107.00
I Change Date Name 1 Sht.
io
9_6917 43 USE
n