Sap 4
Sap 4
Fig. shows the schematic arrangement of current differential protection for a 3-phase alternator.
Identical current transformer pairs CT1 and CT2 are placed on either side of each phase of the stator
windings. The secondaries of each set of current transformers are connected in star ; the two neutral
points and the corresponding terminals of the two star groups being connected together by means of
a four-core pilot cable. Thus there is an independent path for the currents circulating in each pair of
current transformers and the corresponding pilot P. The relay coils are connected in star, the neutral
point being connected to the current-transformer common neutral and the outer ends one to each of
the other three pilots. In order that burden on each current transformer is the same, the relays are
connected across equipotential points of the three pilot wires and these equipotential points would
naturally be located at the middle of the pilot wires. The relays are generally of electromagnetic
type and are arranged for instantaneous action since fault should be cleared as quickly as possible.
Operation. Under normal operating conditions, the current at both ends of each winding will be
equal and hence the currents in the secondaries of two CTs connected in any phase will also be
equal. Therefore, there is balanced circulating current in the pilot wires and no current flows
through the operating coils (R1, R2 and R3) of the relays. When an earth-fault or phase-to-phase
fault occurs, this condition no longer holds good and the differential current flowing through the
relay circuit operates the relay to trip the circuit breaker.
(i) Suppose an earth fault occurs on phase R due to breakdown of its insulation to earth as shown in
Fig. The current in the affected phase winding will flow through the core and frame of the machine
to earth, the circuit being completed through the neutral earthing resistance. The currents in the
secondaries of the two CTs in phase R will become unequal and the difference of the two currents
will flow through the corresponding relay coil (i.e. R1), returning via the neutral pilot.
Consequently, the relay operates to trip the circuit breaker.
(ii) Imagine that now a short-circuit fault occurs between the phases Y and B as shown in Fig. The
short-circuit current circulates via the neutral end connection through the two windings and through
the fault as shown by the dotted arrows. The currents in the secondaries of two CTs in each affected
phase will become unequal and the differential current will flow through the operating coils of the
relays (i.e. R2 and R3) connected in these phases. The relay then closes its contacts to trip the circuit
breaker.
Limitations. The two circuits for alternator protection shown above have their own limitations.
It is a general practice to use neutral earthing resistance in order to limit the destructive effects of
earth-fault currents. In such a situation, it is impossible to protect whole of the stator windings of a
star-connected alternator during earth-faults. When an earth-fault occurs near the neutral point,
there may be insufficient voltage across the short-circuited portion to drive the necessary current
round the fault circuit to operate the relay. The magnitude of unprotected zone depends upon the
value of earthing resistance and relay setting.
Makers of protective gear speak of “protecting 80% of the winding” which means that faults in
the 20% of the winding near the neutral point cannot cause tripping i.e. this portion is unprotected.
It is a usual practice to protect only 85% of the winding because the chances of an earth fault
occurring near the neutral point are very rare due to the uniform insulation of the winding
throughout.
Modified Differential Protection for Alternators
The modified arrangement is shown in Fig. The modifications affect only the relay connections and
consist in connecting two relays for phase-fault protection and the third for earth-fault protection
only. The two phase elements (PC and PA) and balancing resistance (BR) are connected in star and
the earth relay (ER) is connected between this star point and the fourth wire of circulating current
pilot-circuit.
Operation. Under normal operating conditions, currents at the two ends of each stator winding
will be equal. Therefore, there is a balanced circulating current in the phase pilot wires and no
current flows through the operating coils of the relays. Consequently, the relays remain inoperative.
If an earth-fault occurs on any one phase, the out-of-balance secondary current in CTs in that
phase will flow through the earth relay ER and via pilot S1 or S2 to the neutral of the current
transformers.
This will cause the operation of earth relay only. If a fault occurs between two phases, the out of-
balance current will circulate round the two transformer secondaries via any two of the coils PA,
BR, PC (the pair being decided by the two phases that are faulty) without passing through the earth
relay ER. Therefore, only the phase-fault relays will operate.
Fig. shows the schematic arrangement of a balanced earth-fault protection for a 3-phase alternator.
It consists of three line current transformers, one mounted in each phase, having their secondaries
connected in parallel with that of a single current transformer in the conductor joining the star point
of the alternator to earth. A relay is connected across the transformers secondaries. The protection
against earth faults is limited to the region between the neutral and the line current transformers.
Operation. Under normal operating conditions, the currents flowing in the alternator leads and
hence the currents flowing in secondaries of the line current transformers add to zero and no current
flows through the relay. Also under these conditions, the current in the neutral wire is zero and the
secondary of neutral current transformer supplies no current to the relay.
If an earth-fault develops at F2 external to the protected zone, the sum of the currents at the
terminals of the alternator is exactly equal to the current in the neutral connection and hence no
current flows through the relay. When an earth-fault occurs at F1 or within the protected zone, these
currents are no longer equal and the differential current flows through the operating coil of the
relay. The relay then closes its contacts to disconnect the alternator from the system.
Earth Fault Protection
The earth fault protection is provided by following types
1. Sensitive earth fault protection
2. Residual earth fault relay
3. Earth fault protection by CBCT (Core balance current transformer)
The neutral has a CT and CT secondary contains two earth fault relays 1 and 2. The CT introduced
in neutral increase the sensitivity. The earth fault protections relay 1 and 2 have different
sensitivities. The earth fault relay 1 can protect about 90% winding. This relay is instantaneous type
the earth fault relay 2 can protect about 95 % winding. This relay is IDMT relay (Inverse definite
minimum time relay). This is necessary because the earth fault protection should not be too
sensitive. Some faults are transient in nature and these faults are temporary. Also external faults are
present. This relay should not operate in such conditions. Hence IDMT Earth resistance relay is
used which incorporates time delay factor.
Earth fault condition - When earth fault takes place, IR +IY+IB≠ 0 hence a residual current is
produced and earth fault relay coil is energized due to this residual current. The relay coil operates
the trip circuit of circuit breaker. The circuit breaker disconnects alternator from system.
Normal condition-During normal operating condition, the vector sum of three line current is zero IR
+IY+IB= 0 .Hence there is no residual current or zero sequence current is present in primary. Hence
there is no current in CT secondary and earth fault relay coil does not operate.
Earth fault condition - When earth fault takes place IR +IY+IB≠ 0, hence residual current or zero
sequence current is produced. This will setup resultant flux in the core. This causes flow of current
in CT secondary. The earth fault relay coil is energized and operates the trip circuit of circuit
breaker. The circuit breaker disconnects alternator from the system.
Overheating Protection
The overheating takes place due to following reasons 1) shorted laminations due to insulation
damage 2) Failure of cooling system of alternator 3) Sustained over loading.
The overheating protection can be obtained by following methods. (1) By monitoring inlet and
outlet temperature of cooling medium (2) By using RTD (resistance temperature detector)
The alternator has cooling system. A coolant is continuously circulated to take away the heat
developed in alternator stator part. The coolant is in the form of gas (hydrogen) or liquid (water).
The coolant inlet temperature is less compare coolant outlet temperature. Under normal conditions,
this difference is within specified limits. The inlet outlet temperature is continuously monitored by
temperature monitoring system.
When fault develops, there is more temperature rise and there is drastic difference between inlet and
outlet temperature. This is measured by temperature monitoring systems. It gives signal to alarm
system and the alarm sound. Thus indication of overheating condition is obtained.
The system can also generate trip signal and operate the circuit breaker.
Wheatstone's bridge principle is used to detect overheating. P, Q and 5 are the fixed value
resistances. The RTD is connected in one arm as shown. This RTD is kept in stator slot of
alternator.
When temperature is within limits, point a and b are at same potential and relay coil does not carry
any current i.e. bridge is balanced. When overheating occurs, RTD resistance changes causing
imbalance and some potential difference is created across a and b. The relay coil is thus energised
and relay operates the alarm circuit.
The generator might have been connected to a common system of supply to which other generators
are working in parallel. In this case loss of field causes this generator to take the magnetising
current from the common bus-bars. In such condition it runs as the "Induction Generator". The
magnetising current is very large and it is supplied by other generator units. This affects the system
and other units.
When running as an Induction generator its power output reduces. In its rotor slip frequency e.m.f.
is induced. In case of wound rotor generator it gives rise to circulating currents in the rotor body
and slots and temperature increases. Stator windings became hot and also bus-bars are overheated.
The protective system in case of field failure case by using "under-current relay".Stator winding of
generator is connected to the common bus bar. Rotor field winding receives excitation from the
exciter.
In the field circuit an undercurrent relay coil is connected across a low resistance shunt. In normal
condition the voltage drop across a shunt is very very minor and relay does not operate. But under
field failure the excitation current becomes much more and a considerable voltage drop appears
across the shunt which sends the current in relay trip coil which operates the relay and C.B. contacts
are opened.
(1) Large capacity alternators operate over wide band of field current so relay may operate at low
value of field current i.e. malfunctioning may take place.
(1) If field currents is totally interrupted i.e. dc current value is zero, then ac current will still flow
in the field winding operate because the rotor winding is still rotating and stator is connected to line
i.e. 3 phase supply. And the relay will not operate. The solution for this problem is to use offset
Mho relay.
The tripping zone or range of Mho relay is shown by Mho relay characteristics on R-X diagram.
The alternator impedance characteristic during loss of excitation is also shown.
If it enters the Mho relay characteristics, the Mho relay operates and it operates the trip circuit
which causes opening of circuit breaker (CB).
Figure shows scheme for one phase only. It is identical for other phases.
Under normal working conditions the two currents in the stator wind S1 and S2 are identical and by
virtue of the cross connected CT secondaries the relay current is zero, hence no relay operation. But
when one of the windings is faulty (inter turn fault) its current differs and hence the two CT
secondary currents are different, due which the difference current is diverted through the relay coil
to operate it leading to isolation of the alternator from the power system.
TRANSFORMER PROTECTION
Faults likely to occur in a power transformer:
1. Earth fault
2. Overloads and overheating
3. Incipient faults below oil level resulting into decomposition of oil
4. Through faults
5. High voltage surges due to lightning or switching
6. Tap changer faults
7. Phase-to-phase, Phase-to-ground faults
8. Saturation of magnetic core
9. Inter-turn and winding faults
Problems;-
1) Difference in length of pilot wires on either side of relay may lead to mal operation due to
unequal resistance on the two sides.
2) Minor Difference in CT ratios of identically rated CTs may lead to improper operation in some
cases.
3) Magnetizing current in rush may lead to unnecessary operation of relay.
4) Due tap changing unbalance conditions may be created. (I1 – I2 = 0). When fault occurs in the
protected zone balance is disturbed, the rated CTs may lead to improper.
These can be overcome by using %differential protection.
Earth fault protection for star-delta transformer (core balance current transfer):
The three leads of the primary winding of star–delta transformer are taken through the core of a
current transformer which carries a single secondary winding. The operating coil of a relay is
connected to this secondary. Under normal conditions(i.e.no fault to earth), the vector sum of the
three phase currents is zero and there is no resultant flux in the core of current transformer no matter
how much the load is out of balance. Consequently, no current flows through the relay and it
remains inoperative. However, on the occurrence of an earth fault, the vector sum of three phase
currents is no longer zero. The resultant current sets up flux in the core of CT, ultimately induces an
e.m.f. in the secondary winding which energizes the trip coil and protects the faulty transformer.
Fig. 4.5.22 shows the arrangement of earth fault protection scheme for transformer.
The three CTS are connected in lines and an earth fault relay is connected across
these CTS.
When earth fault does not take place, the sum of three secondary currents of CT is
zero. i.e. IR + IB + IY = 0
The sum of these currents is called residual current. When earth fault develops, the
sum of three currents is not zero, the residual current flows through earth fault relay.
This protection is also called unrestricted earth fault protection. In another scheme,
the relay is connected in neutral of the transformer. The neutral acts as CT primary.
When fault occurs, the fault current flows through this earth connection and
secondary current increases causing earth fault relay operation.
The amount of neutral current flowing does depend on type of earthing system
provided. This is also called unrestricted earth fault protection.
Over-Current & earth fault protection of transformer:
Simple over-current & earth fault protection of transformer against external short circuit
and excessive overloads is shown in the above figure. The over-current and earth fault relays may
be of inverse and definite minimum time type or definite time relays. The over-current relay has
three elements; one for each phase winding. The normal range of current setting available on IDMT
over-current relay is 50% to 200%. Due to excessive overload or any external fault, when over-
current flows through the transformer winding, the corresponding phase CT supply the current to
over-current relay. The relay depending upon its setting, sends trip command to the circuit breaker
and the transformer is disconnected from load or fault.
Buchholz relay: It is gas actuated relay installed in the pipe connecting conservator to main tank of
oil filled transformers for protection against all kinds of faults.
Function of Buchholz relay:
It is used for the protection of transformers from the faults occurring inside the transformer. Short
circuit faults such as inter-turn faults, incipient winding faults, core faults etc. may occur due to the
impulse breakdown of the insulation. To protect transformer against these faults, Buchholz relay is
used.
Location of buchholz relay: Buchholz relay is a gas
actuated relay used with oil immersed transformer
usually installed in the pipe connecting the
conservator to the main tank.
Applications of buchholz relay: Normally for the transformers of capacities 500 kVA or more in
various substations, generating stations etc. It is universal practice to use Buchholz relay on all oil
immersed transformers having rating in excess of 500 kVA at generation power plant, receiving
sub-station, distribution sub-station, power transformers in industry etc.
Above parameters are sensed by appropriate sensors. The sensor output is fed to analog to digital
(A/D) converter. It converts the respective analog signals into digital form. The microprocessor has
set reference values stored in the memory.
The input voltage, oil level, temperature, output current are continuously monitored. These values
can be seen on LCD display which is interfaced with microprocessor
When any parameter exceeds the permissible limit or set reference, the microprocessor sends
command to relay driver circuit.
The relay driver circuits operate respective relays (R1 or R2) depending upon the command. e.g. If
overload takes place, the current sensor senses overload condition and microprocessor sends
command to relay driver circuit. The relay driver circuit operates relay R2. Thus load is
disconnected from transformer. In the similar way R. operates for over voltage condition or
excessive temperature rise condition.