CPX200N Installer Manual EN v1.6

Download as pdf or txt
Download as pdf or txt
You are on page 1of 106

ALARM CONTROL UNIT

CPX200N

Installation and
programming manual

Version of the manual: v1.6


Date of issue: 2015.06.26
Firmware version: 1.1.3
GPRS transmitter configurator version: 1.3.48.1
DECLARATION OF COMPLIANCE
We, EBS Sp. z o.o., declare with full responsibility that the present product
meets all requirements provided for in the Directive 1999/5/EC of European
Parliament and Council dated 9 March 1999. The copy of the “Declaration of
Compliance” can be found at http://www.ebs.pl/en/certificates/ .

IMPORTANT INFORMATION
Crossed symbol of a trash bin means that at the territory of European Union, the
product, after finishing its useful life, shall be disposed of in a separate, specially
dedicated collection point. It refers to the equipment itself and its accessories
marked with that symbol. The products shall not be disposed of together with
non-sortable municipal waste.
The content of the document is presented “as is”. The present document shall
not be deemed to be providing any warranties, either express or implicit, including but not
limited to, any implied warranties of merchantability or fitness for a particular purpose, unless it
is required by relevant law. The manufacturer reserves the right to amend the present
document or withdraw it any time, without notice.
The manufacturer of the equipment promotes the sustainable development policy. It reserves
the right to modify and improve any functions of the product described in the present document
without previous notice.
The availability of particular functionalities will depend on the software version of the
equipment. Details can be found at the nearest dealer of the equipment.
In no event, the Manufacturer shall be held liable for any loss of data or loss of profits or any
specific, incidental, consequential or indirect damages caused in any way.

MANUFACTURER
EBS Sp. z o.o.
59 Bronislawa Czecha St.
04-555 Warsaw, POLAND
E-mail : [email protected]
Technical support: [email protected]
Webpage : www.ebs.pl

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 2 / 106


CONTENT:
1. INTRODUCTION .............................................................................................................................. 6
2. CONTROL UNIT FUNCTIONS ........................................................................................................... 7
2.1. FUNCTIONAL CHARACTERISTIC ........................................................................................................ 7
2.2. ELECTRICAL CHARACTERISTIC ......................................................................................................... 8
3. INSTALLATION AND WIRING ......................................................................................................... 9
3.1. SEQUENCE OF INSTALLATION........................................................................................................... 9
3.2. DESCRIPTION OF PCB ELEMENTS ................................................................................................... 10
3.3. DESCRIPTION OF SCREWED CONNECTORS OF THE CONTROL UNIT ................................................. 11
3.4. CONFIGURATION OF INPUT LINES .................................................................................................. 12
3.5. SAMPLE CONNECTION OF A SIGNALLING DEVICE ............................................................................ 14
3.5.1. INTERNAL SIGNALLING DEVICE WITHOUT INDEPENDENT SOURCE OF POWER SUPPLY ............ 14
3.5.2. EXTERNAL SIGNALLING DEVICE WITH INDEPENDENT SOURCE OF POWER SUPPLY .................. 15
3.6. KP10 KEYPAD ................................................................................................................................. 16
3.6.1. DESCRIPTION OF KEYPAD ELEMENTS ..................................................................................... 16
3.6.2. KEYPAD SPECIFICATION ......................................................................................................... 18
3.6.3. KEYPAD INSTALLATION .......................................................................................................... 18
3.6.4. ADDRESSING DEVICES CONNECTED TO THE KEYPAD BUS ....................................................... 18
4. ALARM CONTROL UNIT CONFIGURATION .................................................................................... 19
4.1. ZONE BLOCKING ............................................................................................................................ 19
4.2. ADDING A NEW USER ..................................................................................................................... 19
4.3. USER DELETE ................................................................................................................................. 20
4.4. CHANGE OF USER CODE ................................................................................................................. 20
4.5. PROGRAMMING TIME ..................................................................................................................... 20
4.6. PROGRAMMING DATE ..................................................................................................................... 21
4.7. RESTORING A DEFAULT USERS CODE ............................................................................................. 21
5. ALARM CONTROL UNIT HANDLING .............................................................................................. 22
5.1. ARMING THE SYSTEM ..................................................................................................................... 22
5.2. ARMING THE SYSTEM WITH FAULT ................................................................................................. 22
5.3. DISARMING THE SYSTEM ............................................................................................................... 22
5.4. PARTITION HANDLING ................................................................................................................... 23
5.4.1. ARMING / DISARMING WITH SELECTING PARTITIONS ............................................................. 23
5.4.2. QUICK ARMING / DISARMING PARTITIONS ............................................................................. 23
5.5. ALARM DISPLAY ............................................................................................................................. 24
5.6. ALARM MUTE ................................................................................................................................. 24
5.7. ALARM MEMORY ............................................................................................................................. 24
5.8. FAULTS MEMORY............................................................................................................................ 25
6. SERVICE MODE ............................................................................................................................. 27
6.1. ACTIVATION OF SERVICE MODE ..................................................................................................... 28
6.2. EXIT FROM SERVICE MODE............................................................................................................. 28
6.3. INSTALLER CODE ........................................................................................................................... 28
6.4. POWER LOSS ................................................................................................................................. 28
6.5. RESET TO DEFAULT SETTINGS ....................................................................................................... 28
6.6. SYSTEM OPTIONS .......................................................................................................................... 29
6.7. USERS REMOTE MANAGEMENT ....................................................................................................... 29
6.8. ZONES CONFIGURATION ................................................................................................................ 29
6.9. OUTPUTS CONFIGURATION ............................................................................................................ 31

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 3 / 106


6.10. PARTITION CONFIGURATION .......................................................................................................... 32
6.11. TEXT MESSAGES CONFIGURATION .................................................................................................. 34
7. CONFIGURATION WIZARD ........................................................................................................... 43
7.1. PRELIMINARY NOTES ..................................................................................................................... 43
7.2. COMPUTER – REQUIREMENTS ........................................................................................................ 43
7.3. PROGRAM FUNCTIONS ................................................................................................................... 43
7.3.1. MENU-> FILE ......................................................................................................................... 44
7.3.2. MENU-> OPERATIONS ............................................................................................................ 48
7.3.3. MENU -> HELP ....................................................................................................................... 49
7.4. DEVICE PROGRAMMING .................................................................................................................. 50
7.4.1. LOCAL PROGRAMMING ........................................................................................................... 50
7.4.2. REMOTE PROGRAMMING ........................................................................................................ 50
8. PROGRAMMABLE PARAMETERS.................................................................................................... 52
8.1. ACCESS .......................................................................................................................................... 52
8.1.1. PARAMETERS ......................................................................................................................... 52
8.1.2. ACCESS POINT NAME ............................................................................................................. 53
8.1.3. PRIMARY SERVER PARAMETERS .............................................................................................. 54
8.1.4. SECONDARY SERVER PARAMETERS ......................................................................................... 55
8.1.5. ACCESS .................................................................................................................................. 55
8.2. TRANSMISSION .............................................................................................................................. 57
8.3. INPUTS/OUTPUTS .......................................................................................................................... 58
8.3.1. ZONES ................................................................................................................................... 58
8.3.2. PARTITIONS ........................................................................................................................... 61
8.3.3. OUTPUTS ............................................................................................................................... 63
8.4. SYSTEM OPTIONS .......................................................................................................................... 64
8.4.1. SHOW FAILURES HISTORY WITH SYSTEM DIODE .................................................................... 64
8.4.2. IGNORE ATS FAILURE ............................................................................................................. 64
8.4.3. TURN AUTOMATIC OVERRIDE FOR FAILURE OFF ..................................................................... 64
8.5. USERS ........................................................................................................................................... 65
8.6. MONITORING ................................................................................................................................. 66
8.6.1. EVENTS.................................................................................................................................. 66
8.6.2. ADDITIONAL DATA ................................................................................................................. 67
8.7. RESTRICTIONS ............................................................................................................................... 68
8.7.1. SMS AND DATA CALLS (CSD) .................................................................................................. 68
8.7.2. REMOTE COMMANDS .............................................................................................................. 71
8.8. SMS NOTICES ................................................................................................................................ 72
8.8.1. PHONES ................................................................................................................................. 72
8.8.2. MESSAGES ............................................................................................................................. 73
8.8.3. EVENTS.................................................................................................................................. 74
8.8.4. OPTIONS ............................................................................................................................... 75
8.8.5. SMS FORWARD ...................................................................................................................... 76
8.9. LINK CONTROL............................................................................................................................... 77
8.9.1. GSM ....................................................................................................................................... 77
8.9.2. GPRS ..................................................................................................................................... 78
8.10. FIRMWARE ..................................................................................................................................... 78
8.11. DEVICE MONITORING..................................................................................................................... 79
8.12. EVENTS HISTORY ........................................................................................................................... 80
9. LED INDICATION .......................................................................................................................... 82

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 4 / 106


9.1. NETWORK LOG-IN .......................................................................................................................... 82
9.2. GSM RANGE ................................................................................................................................... 82
9.3. TRANSMISSION .............................................................................................................................. 82
9.4. PROGRAMMING .............................................................................................................................. 83
9.5. FIRMWARE UPDATE ........................................................................................................................ 83
9.6. NO SIM CARD OR SIM CARD DAMAGED ........................................................................................... 83
9.7. SYSTEM ERROR .............................................................................................................................. 83
10. EXTRAS ......................................................................................................................................... 84
10.1. REMOTE COMMANDS AND CONFIGURABLE PARAMETERS................................................................. 84
10.1.1. CONFIGURATION PARAMETERS .............................................................................................. 84
10.1.2. GENERAL COMMANDS............................................................................................................. 86
10.1.3. COMMANDS FOR MANAGING THE USERS IN CP ....................................................................... 90
10.1.4. COMMANDS FOR MANAGING THE PARTITIONS, ZONES AND OUTPUTS..................................... 97
11. CHANGE HISTORY ....................................................................................................................... 106

LIST OF DRAWINGS AND DIAGRAMS


DRAWING 1. DESCRIPTION OF PCB ELEMENTS ................................................................................................ 10
DRAWING 2. DESCRIPTION OF SCREWED CONNECTORS OF THE CONTROL UNIT ............................................. 12
DRAWING 3. CONFIGURATION OF INPUT LINES .............................................................................................. 13
DRAWING 4. SAMPLE CONNECTION OF INTERNAL SIGNALLING DEVICE WITHOUT INDEPENDENT SOURCE OF
POWER SUPPLY .............................................................................................................................................. 14
DRAWING 5. SAMPLE CONNECTION OF EXTERNAL SIGNALLING DEVICE WITH INDEPENDENT SOURCE OF POWER
SUPPLY .......................................................................................................................................................... 15
DRAWING 6. KP10 KEYPAD ............................................................................................................................. 16

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 5 / 106


1. INTRODUCTION
Thank you for choosing EBS alarm control unit.
CPX200N is a simple, functional alarm control unit integrated with GSM/GPRS/SMS transmitter,
intended for small- and medium- sized facilities. The central unit is equipped with 3 outputs and
7 zones with the possibility to be divided into 2 partitions. Dedicated KP10 LED keypad was
designed in a modern, discreet style. Portable size, large, comfortable buttons and simple
installation contribute to indisputable advantage of our system.
The product was designed in accordance with the requirements of EN 50131 standards, Grade
2, Environmental class II.
2. CONTROL UNIT FUNCTIONS

2.1. FUNCTIONAL CHARACTERISTIC

ZONES
 7 zones with the NC / NO / EOL-NC / EOL-NO / DEOL-NC / DEOL-NO configuration
possibility
 Detection lines – instant, delayed, 24h burglary, arming/disarming, 24h tamper, interior
delay, 24h burglary silent, 24h fire
PROGRAMMABLE OUTPUTS
 1 monitored alarm output, high-current (max. current 1.1A)
 2 monitored alarm outputs, low-current (max. current 50mA)
FEEDING OUTPUTS
 1 signalling device output (max. current 350mA)
 1 detector output (max. current 350mA)
 1 keypad output (max. current 100mA)
PARTITIONS
 2 partitions with the possibility to assign any number of zones to each of them
KEYBOARD
 cooperation with LED keyboard KP10
 ability to connect up to three keypads
TRANSMISSION
 Transmission of signals through GPRS/SMS module
 Encryption of data transfer using AES standard
 Communication with monitoring station using dedicated OSM.2007 server that ensures
the reliability of data transfer thanks to a redundancy function
 Control of GSM/GPRS connection – automatic restoration of connection with monitoring
station or switching to secondary server
CONFIGURATION
 Local, using KP10 keypad or a computer
 Remote through GPRS, SMS or CSD
USERS
 1 admin code (main)
 1 service code
 8 user codes
 Possibility to restrict the scope of authorisation to a few codes only
SYSTEM OPTIONS
 Automatic diagnosis of basic system components
 Possibility to review faults, alarm memories, event log
 System/technical event history up to 5000 events

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 7 / 106


2.2. ELECTRICAL CHARACTERISTIC

Supply voltage: 18VAC (16-20VAC)


Required transformer Power: min. 20VA
Current consumption average/max: 120mA / 1100mA @18VAC
(average measured@: fully charged battery,
established connection with server, connected keypad,
no sensors connected)
Average current consumption; lack of 60mA / 80mA
external supply (without keypad/ with
keypad):
(fully charged battery, no sensors connected,
established connection with server)
Charging current: max. 350mA
(measured with totalny discharged battrey)
Charging voltage: 13.8V
Supported bartery type: Lead-acid 12V
Low voltage – event treshold: 11V
Voltage battery cut off level: below 9V
Working temperature: -10ºC to +55ºC
Working humidity: 5% to 93%
PCB dimensions: 152mm x 78mm x 30mm

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 8 / 106


3. INSTALLATION AND WIRING

3.1. SEQUENCE OF INSTALLATION

1. Develop installation diagram accounting for the location of control unit, keypad,
detectors and other system components.

2. Install the control unit in hardly accessible place with uninterrupted power supply
ensured.

3. Install the keypad in a location convenient for a user and connect it with the control unit.
For description of keypad installation, please refer to chapter 3.6.2.

NOTE: Maximum length of cables connecting the control unit with the
keypad, at the core diameter 0.5mm2 cannot exceed 200m.

4. Install detectors and door and window reed relays. Connect the installed elements with
control unit. For sample configuration of zones, please refer to chapter 3.4.

5. Install and connect signalling devices with the control unit. For sample signalling devices
connection diagrams, please refer to chapter 3.5.

6. Complete the remaining cable connections.

7. Connect power supply and a battery with the control unit.

8. Program the functions of the control unit. Programming procedure was described in the
chapters below.

NOTE: If you use more than one keyboard in the system, be sure to
address each assignment of the keyboard (see ch. 3.6.4).

9. Verify the operation of the system and all its components.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 9 / 106


3.2. DESCRIPTION OF PCB ELEMENTS

Drawing 1. Description of PCB elements

1. GSM Antenna Connector (female SMA)


GSM antenna is delivered separately as one of the optional system components. It is
recommended to use antenna with cable that allows finding adequate position ensuring
optimal GSM range. The control unit is compatible with GSM antenna with male SMA
connector.

2. Slot of SIM Card


The control unit is equipped with integrated GSM/GPRS/SMS transmitter. SIM card with
active GPRS transmission is necessary to communicate with the server. The card shall be
installed in the slot indicated in the drawing.

NOTE: Before you insert the card, make sure that PIN code
authorisation is deactivated, or PIN code is compliant with the code
programmed in the control unit. Default factory PIN code of the control
unit is 1111.

3. Yellow “STATUS” LED


For the detailed description of “STATUS” LED operation, please refer to chapter 9.

4. Red “ERROR” LED


For the detailed description of “ERROR” LED operation, please refer to chapter 9.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 10 / 106


5. Green “OK” LED
For the detailed description of “OK” LED operation, please refer to chapter 9.

6. Connector of “CONF” Programming Device


“CONF” IDC10 connector allows the control unit configuration using dedicated GD-PROG
programming device and any computer equipped with RS232 port.

7. “PROG” Button for Default Settings Restoration


Pressing the button for 10s during connecting the control unit with power supply will delete
all users and restore the default admin code. Default admin code is 1111.

8. “START” Button for Battery Activation of Control Unit Without the Mains
Power Supply
If the control unit is activated in the situation of power supply fault, press the button after
connecting the unit to the battery.

9. Screwed Connectors of the Control Unit


For detailed information on feeding, input and output connectors, please refer to chapter
3.3.

10. Assembly Holes of the Control Unit (132x61mm hole span)


The above holes are intended for the control unit to be assembled in any type of casing. In
option a dedicated plastic OBDNA casing can be ordered (the casing includes appropriate
230VAC/18VAC transformer).

3.3. DESCRIPTION OF SCREWED CONNECTORS OF THE CONTROL


UNIT

NOTE: Any assembly and installation works shall be carried out with
power supply off and battery disconnected.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 11 / 106


Drawing 2. Description of screwed connectors of the control unit

3.4. CONFIGURATION OF INPUT LINES

All input lines are fully configurable and can operate as normally closed (NC)) or normally
open (NO) as well as with assigned parameters (EOL-NO or EOL-NC) using 2.2kΩ resistors
or with assigned double parameters (DEOL-NO or DEOL-NC) using 1.1kΩ resistors. Both
resistor types are included in the delivery of the control unit. Various configurations of input
lines are presented in the drawing 3.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 12 / 106


Drawing 3. Configuration of input lines

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 13 / 106


3.5. SAMPLE CONNECTION OF A SIGNALLING DEVICE

3.5.1. Internal Signalling Device Without Independent Source of


Power Supply

Drawing 4. Sample connection of internal signalling device without independent source of power
supply

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 14 / 106


3.5.2. External Signalling Device with Independent Source of Power
Supply

Drawing 5. Sample connection of external signalling device with independent source of power supply

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 15 / 106


3.6. KP10 KEYPAD

3.6.1. Description of Keypad Elements

Drawing 6. KP10 Keypad

1. Keypad Buttons
0-9 buttons and * as well as # are intended for keypad and control unit operation. After
first pressing any button, the keypad is backlit. After a few-second idle time, backlight
gets automatically dimmed. In order to make codes easier to remember, buttons are
marked with the alphabet.

2. ALARM LED (red):


Flashing light – means that alarms were present in the system (alarm memory).
Constant light – means that system is in alarm state.
Off – system is operating correctly.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 16 / 106


3. ARMED LED (red):
Flashing light – means that time for exit in any of partitions is counted.
Constant light – at least one partition is armed
Off – partitions disarmed.

4. SYSTEM LED (yellow):


Flashing light - means that in the control unit’s memory there are faults that has already
ceased (there was power loss, but it has already restored).
Constant light – there is a fault in the system that was not removed.
Off – no fault in the system.

5. PROG LED (blue):


Flashing slowly – service function is activated and it is one of the user functions.
Flashing – data will be entered.
Constant light – installer service function is activated.

6. 1 - 8 LEDs (red)

When LED goes on during normal operation, it means that the line it is assigned to was
disrupted. Flashing LED means the zone was interlocked. After activating service
functions, LEDs display data.

7. Screwed Connectors

The connectors for connecting cables joining the keypad with the alarm control unit.

8. Cable Entry
It is a place for entering the connection cables.

9. Assembly Holes
The keypad was equipped with four round assembly holes for proper fastening the
keypad.

10. Casing Opening Latch


To open the casing it is recommended to use flat 2.5-5mm screwdriver. Insert it slightly
in indicated hole and gently perform a lever movement toward the rear side of the
casing.

11. Anti-Sabotage Switch


After the keypad is assembled the switch contact is closed. Unauthorised disassembly of
the keypad will send the message to the alarm control unit. In order to eliminate surface
unevenness, a spring is located on the switch lever.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 17 / 106


3.6.2. KEYPAD SPECIFICATION

Power supply voltage: 10 – 13.8 VDC


Power consumption: typ. 20 mA, max. 70 mA
Keypad weight: 70 g
Size of casing: 99 x 82 x 19 mm
Keypad type: LED, 8 status LEDs, 4 mode LEDs (ALARM, ARMED,
SYSTEM, PROG)
Button layout: Standard telephone keypad 3 x 4 buttons

3.6.3. Keypad Installation

1. KP10 keypad is intended for inside installation, on dry and even surface. Usually, it
is installed on wall, near the entrance door, 120-140 cm high from the ground.

2. To open the keypad casing – insert a flat screwdriver in the bottom part of the
casing and press the latch. Then carefully take both parts of the casing apart,
starting from the casing’s bottom.

3. Mark and drill holes in the wall to install the rear part of the casing.

4. Screw the rear part of the casing to the wall.

5. Connect cables joining the keypad with the alarm control unit. Keypad terminals
marked: KT, KR, KP, KG shall be connected with KT, KR, KP, KG terminals in the
alarm control unit (see drg. 2.)

6. Assembly the rear part of the casing with the front one starting from the casing’s
top. Make sure that the keypad is well assembled and sabotage switch is pressed
in.

3.6.4. Addressing devices connected to the keypad bus

Each keypad to be connected to the bus must have its own individual address from the 1
to 3 range. Addresses must not repeat (the control panel does not suport devices having
identical addresses). It is recommended that consecutive addresses be assigned starting
from 1. In keypads, the address is set by software means. By default, address 1 is set.
Programing keypad address:
1. Remove the keypad from the wall (tamper switch should be open).

2. At the same time, press and hold the and , or , which


means a new keypad address.

3. After about 5 seconds the keypad will display the programmed keypad address.

4. After programming the keypad address, reset the control panel CPX200N.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 18 / 106


4. ALARM CONTROL UNIT CONFIGURATION

4.1. ZONE BLOCKING

The zone blocking function allows de-activating stand-by mode of any zones or bypassing
any damaged lines. Also, zones which are not in stand-by mode and which the user has
access to can be blocked. Zones remain blocked until de-arming. System informs the user
about that fact with slowly flashing LED marked with the number of the blocked zone.
Zone blocking:

1. Enter the number of the function and confirm with . Enter the user code
and press . 3-tone beep will confirm the correct code input.

Note: If incorrect code is entered the keyboard will emit long constant
sound. Enter the correct code once again.

2. Using buttons numbered 1 to 7 select zones you want to block.


3. Change the zones blocking status by pressing numbered buttons (LEDs with relevant
zone number will go on/off). Press to confirm blocking of selected zones. 3 beeps
will confirm the change. To cancel the entered changes, press .

4.2. ADDING A NEW USER

You can add a new user code here. New codes can be added by the administrator only. 3
beeps will confirm the successfully entered function.

Note: Individual codes cannot be the same; if any code is the same as
another one, it will not be recorded.

To add a new user:

1. Enter the function code and press to confirm.

2. Enter the admin code and confirm it with . 3 beeps will confirm the correct code
input.
3. Numbers of already existing users will be displayed.
4. Enter the ID of newly added user (1 to 8), other than already added ID numbers, and
press to confirm. Numbers of partitions a new user can have access to will be
displayed.
5. To activate/deactivate LED of an appropriate partition, press 1 or 2. When the access is
set, press to confirm. All LEDs shall be off now.

6. Enter the code of a newly added user (4 to 7 digits) and press to confirm.

7. Enter the code of a newly added user again and press to finish adding or to
exit without saving changes.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 19 / 106


8. Successful adding a new user will be confirmed with 3 beeps, otherwise a constant
sound will be emitted.

4.3. USER DELETE

You can delete a user here. Codes can be deleted by the administrator only. 3 beeps will
confirm the successfully entered function.

Note: You cannot delete Admin account (user no. 0) and Installer
account (user no. 9)

To delete a user:

1. Enter the function code ' and press to confirm.

2. Enter the admin code and confirm it with . 3 beeps will confirm the correct code
input.
3. Numbers of already existing users will be displayed.

4. Enter the ID code (1- 8) of a user to be deleted and press to confirm or to


exit without saving changes.
5. Successful deletion of a user will be confirmed with 3 beeps, otherwise a constant sound
will be emitted.

4.4. CHANGE OF USER CODE

The user can change its code here. 3 beeps will confirm the successfully entered function.

<User code > <Code> <Code>

Where:
User code - Code of a user changing the password.
Code – New access code (from 4 to 7 digits).

4.5. PROGRAMMING TIME

You can change system time here. Time can be changed by the administrator only. 3 beeps
will confirm the successfully entered function.

< Administrator code > <hh> <mm>

where:

Administrator code – Administrator code.

hh – Hours.

mm – Minutes.

In any moment you can press to exit without saving changes.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 20 / 106


4.6. PROGRAMMING DATE

You can change system date here. Date can be changed by the administrator only. 3 beeps
will confirm the successfully entered function.

< Administrator code > <YY> <MM> DD>

where:

Administrator code – Administrator Code.

YY – Year.

MM – Month.

DD – Day.

In any moment you can press to exit without saving changes.

4.7. RESTORING A DEFAULT USERS CODE

Pressing the PROG button on CPX200N panel for 10s during the connection of the alarm
control unit power supply will delete all programmed users and restore the default admin
and installer code.
Default admin code is: 1111.
Default installer code is: 2222.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 21 / 106


5. ALARM CONTROL UNIT HANDLING

5.1. ARMING THE SYSTEM

1. Enter your code and press . 3 beeps will confirm the code.

Note: If incorrect code is entered the keypad will emit long constant
sound. Repeat the arming process by entering the correct code.

2. Leave the facility before the time for leaving expires. That state is indicated by
intermittent sound and quick flashing the ARMED LED on the keypad until the system
gets fully armed. If the chirps are activated the arming will be confirmed by one chirp of
siren.

Note: If the partition is not plugged any zones and/or outputs, the
partition is not armed.

5.2. ARMING THE SYSTEM WITH FAULT

If during the arming any faults are present in the system, the keypad will indicate it with
flashing ARMED and SYSTEM LEDs and long constant sound audio signal. LEDs 1 to 8 will
indicate which system errors are present. That state will maintain for 10 seconds. If there is
no possibility to quickly remove faults, press to arm the system. Pressing will
cancel the arming process.

Note: Remove the causes of faults as soon as possible.

Error codes:
1 – Damage or disruption of detector
2 – Damage of signalling device or signalling device active
3 – Damage of internal connection or sabotage
4 – AC power supply damage
5 – Battery damage
6 – ATS damage
8 – Other damages

5.3. DISARMING THE SYSTEM

1. Enter the facility through the entrance door. Intermittent sound and slow flashing of
ARMED LED on the keypad will remind of the need to disarm the system before the delay
time for entrance expires.
2. Enter the code and press . 3-tone beep of the keypad will confirm the correct code
input. The partition the user has access to will be disarmed. If the chirps are activated
the disarming will be confirmed by two chirps of siren. If the user has access to all

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 22 / 106


partitions, all of them will be disarmed. If there is no armed partitions in the system,
ARMED LED will be deactivated.
3. The system can be disarmed in different way - by changing the partition state. See item
chapter 5.4.
4. When system is disarmed, alarm will be muted (deactivated).

Note: Incorrect code input will be signalled with a long constant


sound. Enter the correct code immediately and press .

5.4. PARTITION HANDLING

5.4.1. ARMING / DISARMING WITH SELECTING PARTITIONS

1. Enter the number of the function and confirm using . Then enter the user
code and press . 3-tone beep will confirm the correct code input.

Note: If incorrect code is entered the keypad will emit long constant
sound. Enter the correct code once again.

2. LEDs 1 and 2 will display the current partition state. LED on – partition armed, LED off -
partition disarmed. Only LEDs indicating the partitions the user has access to will be on.
3. To change the partition state press buttons with partition numbers (LEDs with relevant
partition number will go on/off). Confirm the change of partition state using
button. 3 beeps will confirm the change. To cancel the entered changes, press .
4. If partition arming was selected, the keypad will indicate counting the time for leaving
the facility. Leave the facility before the time for leaving expires. After it is armed the
ARMED LED will be constantly on.
5. If partition disarming is selected, the relevant partition will be immediately disarmed.

Note: If the partition is not plugged any zones and/or outputs, the
partition is not armed.

5.4.2. QUICK ARMING / DISARMING PARTITIONS

1. Enter the number of the function ( for partition one or for


partition two) and confirm using . Then enter the user code and press . 3-tone
beep will confirm the correct code input.

Note: If incorrect code is entered the keypad will emit long constant
sound. Enter the correct code once again.

2. If partition arming was selected, the keypad will indicate counting the time for leaving
the facility. Leave the facility before the time for leaving expires. After it is armed the
ARMED LED will be constantly on.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 23 / 106


3. If partition disarming is selected, the relevant partition will be immediately disarmedEnter
the number of the function and confirm using . Then enter the user code and
press .

Note: If the partition is not plugged any zones and/or outputs, the
partition is not armed.

5.5. ALARM DISPLAY

If red ALARM LED flashes when the system is armed, it means that while you were absent
some alarms occurred (numbers of lines that initiated them will be displayed as well) which
have already ceased. But, if ALARM LED emits constant light, it means that system still is in
alarm state. Exercise caution! If you suspect any intruder to be present in the facility, leave
the facility immediately and call security guards.

5.6. ALARM MUTE

1. To mute (deactivate) the alarm, enter the code and press . 3 beeps will confirm the
code. Also, the system will be disarmed.
2. In order to identify the alarm type, please refer to Alarm Memory chapter of the present
manual.

5.7. ALARM MEMORY

- Display of alarm memory

The function displays the history of alarms that occurred in the system. When the function is
activated, ALARM and PROG LEDs are flashing slowly and all alarms that occurred since last
arming are displayed. LEDs 1- 7 display the information from which zones the alarm was
activated. LED 8 indicates that alarm has been triggered from the source other than input
zone. To clear the alarms memory, press . To exit without clearing the alarms memory,
press .
Alarm source types:
1 – Sabotage of zone 1
2 – Sabotage of zone 2
3 – Sabotage of zone 3
4 – Sabotage of zone 4
5 – Sabotage of zone 5
6 – Sabotage of zone 6
7 – Sabotage of zone 7
8 – Other alarm

If LED 8 is active (ie. blinks or on), pressing displays the alarm source type. After pressing
the button corresponding to active LED, the detailed information about the alarm source within
selected type is displayed. Anytime is pressed, contents of the main level of alarms

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 24 / 106


memory function is displayed. Other alarms history can also be accessed by selecting following
code from the main menu: .

Other alarm source types:


2 – Keypads tamper
Other alarm source types -> Keypads tamper:
1 – Keypad tamper 1
2 – Keypad tamper 2
3 – Keypad tamper 3

Note: Alarms memory is cleared after the system is armed.

5.8. FAULTS MEMORY

- Display of faults memory


The function displays faults that are present in the system. When the function is activated,
SYSTEM and PROG LEDs are flashing slowly and all faults that are currently present in the
system are displayed. Led 1 – 8 display information on the cause of fault. To clear the faults
memory, press . To exit without clearing the faults memory, press .
Faults description:
1 – Sabotage of zones
2 – Fault of output 1 - 3
3 – Fault of feeding output
4 – AC fault
5 – Battery fault
6 – ATS fault
7 – Other damages
To display more detailed information on faults, press or button. To
return to the main fault menu, press or press to exit the function.
Button 1 – Sabotage of zones:
1 – Sabotage of zone 1
2 – Sabotage of zone 2
3 – Sabotage of zone 3
4 – Sabotage of zone 4
5 – Sabotage of zone 5
6 – Sabotage of zone 6
7 – Sabotage of zone 7
Button 2 – Fault of output 1 - 3:
1 – Fault of output 1
2 – Fault of output 2
3 – Fault of output 3
Button 3 – Fault of feeding output:

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 25 / 106


1 – Fault of feeding output + KP
2 – Fault of feeding output +AUX1
3 – Fault of feeding output +AUX2
Button 7 – Other damages:
1 – Clock fault
2 – Fault of central unit settings
3 – Keypads tamper
Button 3 – Other damages > Keypads tamper:
1 – Keypad tamper 1
2 – Keypad tamper 2
3 – Keypad tamper 3

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 26 / 106


6. SERVICE MODE
Service mode is intended for configuration of basic parameters related to zones, outputs and
partitions. It allows to manually, using a keypad, program all correlations necessary for correct
system operation.
After the service mode is initiated a number of service functions are available. To configure the
system, enter the number of function and its arguments, related to the function, as following:

<Number of function> <Argument>

where:
Number of function – a number of one of available service functions,
Argument – the argument of a given service function (of BIT or DEC type).

Each service function has one of two argument types: binary (BIT) or decimal (DEC) . Handling
each of the two types of arguments is presented below:

Binary type (BIT)


When the binary argument type function is entered, the current option status is displayed with
LEDs relevant to a given option of the function on/off. Press 1 to 8 buttons to change the status
of LED and the option it corresponds to. The installer can change the option status as many
times as they want. When the desired status is set, press to confirm or to exit
without saving changes.

Decimal type (DEC)


Service function that accepts decimal type arguments can also accept any length strings of
decimal numbers, not exceeding the maximum length pre-defined for the function. When a
character is entered, a cursor gets automatically ready for entering the next character. Press
to save currently entered changes and exit the service function, press to cancel
entered changes and exit the service function. Before you press any key on a keypad, the
currently programmed parameter value is displayed. It is presented by displaying subsequent
digits of the parameter with a short pause in between. When all digits of the parameter are
displayed, the pause is longer.
After pressing the numerical button, the lately entered digit is displayed on a keypad. The way
the digits are displayed on a keypad is presented in the table below:
Entered digit LEDs on
0 12345678
1 12345678
2 12345678
3 12345678
4 12345678
5 12345678
6 12345678
7 12345678
8 12345678
9 12345678

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 27 / 106


6.1. ACTIVATION OF SERVICE MODE

To activate the service mode the installer code authorisation is required.

<Installer code>

3 beeps will confirm the correct input of the code and function number. PROG LED on will
inform that currently, the user is in service mode. When any service function is entered,
PROG LED will be blinking. After exit from the function, PROG LED will be lit constantly
again, informing that the user is in the main service mode menu.

6.2. EXIT FROM SERVICE MODE

To exit the service mode press and confirm with . Using that function will trigger
the control unit’s reset using configured parameters.
The device will exit test mode automatically after 5 minutes without pressing the buttons
and system will restart.

6.3. INSTALLER CODE

The installer code can be changed here. 3 beeps will confirm the successfully entered
function.

<Installer code> <Installer code>

where:
Installer code – new installer code (from 4 to 7 digits)
You can press any time to exit without saving changes.

6.4. POWER LOSS

The function determines time in seconds after which failure is to be reported. The function’s
argument is of decimal type. 3 beeps will confirm the successfully entered function.
To change /configure the time:

<Time>
where:
Time – time in seconds
You can press any time to exit without saving changes.

6.5. RESET TO DEFAULT SETTINGS

That function resets the settings to their default configuration, accessible from the service
mode level. In order to protect the settings against accidental modification, the function is to
be additionally confirmed with installer code. 3 beeps will confirm the successfully entered
function. Using that function will trigger the control unit’s reset using default parameters.

<Installer code>

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 28 / 106


You can press any time to exit without saving changes.

6.6. SYSTEM OPTIONS

That function allow to switch on and switch off additional options of the system. The
argument of the function is BIT type. By pressing 1, 2 and 3 keys, you can switch on/off
proper option. 3 beeps will confirm the successfully entered function.

<Options>
Where:
Options – number of option (BIT type parameter):
 1 – enable faults memory indication – when is switched off, LED SYSTEM does not
show by blinking the faults that are not active; you can display inactive faults by
choosing “faults memory” user function
 2 – disable ATS monitoring. If his option is enabled, ATS failure isn’t signaled to the
user in any way on the keypad and it doesn’t cause arm prevention.
 3 – disable automatic arm prevention overriding when fault. If this option is disabled
and at least on fault is active in the system, arm prevention isn’t signaled to the user
during partition arming. Instead arm prevention is automatically overridden. If option
is enabled, faults causes arm prevention which can be overridden by user.

You can press any time to exit without saving changes.

6.7. USERS REMOTE MANAGEMENT

That function allow to switch on or switch off remote users management. The argument of
the function is BIT type. By pressing key 1, you can switch on/off option. 3 beeps will
confirm the successfully entered function.

<Options>
Where:
Options – number of option (BIT type parameter):
 1 – Users remote management enable – when is swiched on

You can press any time to exit without saving changes.

6.8. ZONES CONFIGURATION

Zones can be configured using complex service functions, after activation of which, all the
parameters related to the relevant zone can be given subsequently or in a form of series of
service functions that configure one zone-related parameter. Addresses of zone
configuration functions are defined as per the following pattern:

<XX> <Y>
where:
XX – determines the number of zone from 01 to 07; entering number 00 will change the
parameters for all zones in the system,
Y – number of parameter related to a given zone:

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 29 / 106


 0 – complex function, the initiation of which configures the parameters listed below
as another set of parameters;
 1 – type of zone response (DEC type parameter):
o 0 – instant
o 1 – delay
o 2 – 24h burglary
o 3 – arming/disarming
o 4 – 24h tamper
o 5 – interior delayed
o 6 – 24h burglary silent
o 7 – 24h fire
 2 – delay in seconds for the circuit of selected “delay” response type (DEC type
parameter). For other response types the parameter is irrelevant.
 3 – operation mode (DEC type parameter):
o 0 – unused circuit
o 1 – NC mode
o 2 – NO mode
o 3 – EOL/NC mode
o 4 – EOL/NO mode
o 5 – DEOL/NC mode
o 6 – DEOL/NO mode
 4 – number of alarms after which the zone will be automatically blocked until re-
arming (DEC type parameter). If 0, zone will not be blocked.
 5 – zone options (BIT type parameter):
o 1 – circuit ignored during arming – i.e. can be violated during partition arming
(e.g. delay circuits shall be set to that option).
o 2 – generates alarm when violated after arming
 6 – sensitivity in milliseconds, i.e. after what time the input is considered to change
its status – default value; 400ms
Example:
a) change of a single parameter – operation mode of number 2 zone into NO
operation mode:

b) change of sensitivity of all zones into 200 milliseconds:

c) change of many parameters at the time for zone 1 using complex functions – zone
1 is to be set as immediate circuit, in NC mode, to be blocked after 8 violations
and generate alarm when violated after arming, with the 500ms sensitivity:

……

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 30 / 106


Note: In case of complex function (programming many
parameters at the time) after the parameter is entered and confirmed
with , the parameter is saved in the configuration memory and
the system waits for entering another parameter, and so on, until all
parameters of the complex service function are entered. Press
to cancel changes entered in currently configured parameter only and
exit service function – previously entered parameters, confirmed with
, will not be cancelled.

6.9. OUTPUTS CONFIGURATION

Outputs, similar as zones, can be configured using complex service functions after activation
of which, all the parameters related to the relevant output can be given subsequently or in a
form of series of service functions that configure one output-related parameter. Addresses
of output configuration functions are defined as per the following pattern:

<XX> <Y>
where:
XX – determines the number of output from 01 to 03; entering number 00 will change the
parameters for all outputs in the system,
Y – number of parameter related to a given output:
 0 – complex function, the initiation of which configures the parameters listed below
as another set of parameters;
 1 – type of output (DEC type parameter):
o 0 – not used,
o 1 – signalling alarm,
o 2 – stand-by indicator,
o 3 – power failure,
o 4 – ATS failure – no communication with receiving server.
o 5 – GSM signal jamming indicator
o 6 – chirp no arm/disarm
o 7 – chirp no arm/disarm and signalling alarm
 2 – time of output activation in seconds (DEC type parameter); if 0 is set, output will
operate in bi-stable mode.
It is possible to configure the chirp options using following patterns:
a. chirp signal duration:

<X> , where <X> is the time in miliseconds


b. interval duration between two following chirps:

<X> , where <X> is the time in miliseconds


NOTE: Chirp configuration is common for all outputs
Example:
a) change of a single parameter – operation mode of number 2 output into bi-stable
operation mode:

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 31 / 106


b) change of 3 output type into triggered by power failure:

c) change of many parameters at the time for output 1 using complex function –
output 1 is to be set as alarm signalling with activation time 120 seconds:

Note: In case of complex function (programming many


parameters at the time) after the parameter is entered and confirmed
with the parameter is saved in the configuration memory and the
system waits for entering another parameter, and so on, until all
parameters of the complex service function are entered. Press to
cancel changes entered in currently configured parameter only and
exit service function – previously entered parameters, confirmed with
, will not be cancelled.

6.10. PARTITION CONFIGURATION

Partition configuration can be configured similarly as zones and outputs, using complex
service functions after activation of which, all the parameters related to the relevant
partition can be given subsequently or in a form of series of service functions that configure
one partition-related parameter. Addresses of partition configuration functions are defined
as per the following pattern:

<XX> <Y>
where:
XX – determines the number of partition from 01 to 02; entering number 00 will change
the parameters for both partitions,
Y – number of parameter related to a selected partition:
 0 – complex function, the initiation of which configures the parameters listed below
as another set of parameters;
 1 – zones belonging to partition (BIT type parameter),
 2 – outputs belonging to partition (BIT type parameter),
 3 – time for leaving the partition in seconds (DEC type parameter),
 4 – alarm time in the partition in seconds (DEC type parameter),
 5 – partition options (BIT type parameter):
o 1 – quiet signalling of time for entering (during counting the time for entering, the
buzzer in a keypad is not active)
o 2 – quiet signalling of time for leaving (during counting the time for leaving, the
buzzer in a keypad is not active)
 6 – auto-arming time (DEC type parameter, time of day written in the 24-hour
notation in the form HHMM),
 7 – auto-arming option (BIT type parameter):

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 32 / 106


o 1 – auto-arming activation/deactivation
 8 – auto-disarming time (DEC type parameter, time of day written in the 24-hour
notation in the form HHMM),
 9 – auto-disarming option (BIT type parameter):
o 1 – auto-disarming activation/deactivation

Notes:
Execution of complex function 3006 (auto-arming time for all paritions) will copy
activation/deactivation option from the first partition to the second partition.
Execution of complex function 3007 (auto-arming activation/deactivation for all paritions)
will copy auto-arming time from the first partition to the second partition.
Execution of complex function 3008 (auto-disarming time for all paritions) will copy
activation/deactivation option from the first partition to the second partition.
Execution of complex function 3009 (auto-disarming activation/deactivation for all
paritions) will copy auto-disarming time from the first partition to the second partition.
If the time in the device is set forward (eg. when the time is changed to Daylight saving
time), and arming or disarming time is in the period which has been ommited, then the
hour will be not used. Eg. If the auto-arming time is set to 2:30, and time was changed
forward from 2:00 to 3:00, the control panel will not arm.

Examples:
a) change of a single parameter – assigning 1, 2, 3 zones to the first partition:

b) change of time for leaving both partitions into 60 seconds:

c) change of many parameters at the time for partition 2 using complex function –
zones 2, 4, 5 and output 1 to belong to partition 2, time for leaving the one to be
45 seconds, alarm time in partition 2 to be 120s and signalling of time for entering
and leaving was quiet:

……

Note: In case of complex function (programming many


parameters at the time) after the parameter is entered and confirmed
with , the parameter is saved in the configuration memory and
the system waits for entering another parameter, and so on, until all
parameters of the complex service function are entered. Press to
cancel changes entered in currently configured parameter only and
exit service function – previously entered parameters, confirmed with
, will not be cancelled.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 33 / 106


6.11. TEXT MESSAGES CONFIGURATION

In order for installer to be able to configure text messages, administrator has to grant him
necessary permission first. This can be achieved by typing in following code:
<administrator code> .
Next, installer’s access to text messages can be changed by pressing the key. This will
toggle led 1. When the led is active, installer is granted the access, when led is inactive,
installer is refused access to text messages. Choice of installer’s permissions can be
accepted by pressing the button.
CPX200N can store up to 10 phone numbers and up to 32 text messages. If, for any reason,
the SMS can not be send at the moment, it will be send as soon as the connection with the
GSM network is re-established but not later than 1 day after the occurrence of the event
triggering SMS send request (text messages get expired and are deleted). Message should
contain only characters from English alphabet. Furthermore, if the text contains any spaces,
content of the message, starting from the equation mark (=) till the end of the message,
should be enclosed in quotes (" ").

Intaller can configure the text messages using following commands:

Acquiring the state of partitions


Command syntax XXXX GETARMED
Command description Acquiring the information which partitions are
armed/disarmed
XXXX – user code
Example: 1234 GETARMED
Feedback message PARTITION1:X, PARTITION2:Y
or
GETARMED:ERROR

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 34 / 106


Feedback message PARTITION1:X, PARTITION2:Y - Information about
description partitions arm/disarm state.
PARTITION1,PARTITION2 – default partitions names,
they can be changed with the SETNAME command
X,Y – partition states, possibile values:
0 – disarmed
1 – armed
GETARMED:ERROR – command rejected by the
system

Setting the name of partition


Command syntax XXXX SETNAME=PARTITION,NR,VALUE
Command description Acquiring the information which partitions are
armed/disarmed
XXXX – user code
NR – number of the partition, possibile values: 1 or 2
VALUE – new name of the partition
Example 1:
1234 SETNAME=PARTITION,1,Cellar
Example 2:
1234 SETNAME="PARTITION,2,Kids Room"
Feedback message SETNAME::OK or SETNAME:ERROR
Feedback message SETNAME::OK – command accepted
description SETNAME:ERROR – command rejected by the system

Getting the name of partition

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 35 / 106


Command syntax XXXX GETNAME=PARTITION,NR
Command description Acquiring the name of the partition
XXXX – user code
NR – number of the partition, possibile values: 1 or 2
Example: 1234 GETNAME=PARTITION,1
Feedback message GETNAME=PARTITION,NR,VALUE
or
GETNAME:ERROR
Feedback message GETNAME=PARTITION,NR,VALUE – partition name
description GETNAME:ERROR – command rejected by the system

Setting the phone number


Command syntax XXXX SETTELNUM=ID,NUMBER
Command description Setting the phone number for pointed index on the
phone number list
XXXX – user code
ID – index of phone number on the list, possible
values: 1 to 10
NUMBER – phone number, on which the texts will be
send
Example: 1234 SETTELNUM=3,800123456
Feedback message SETTELNUM:OK
or
SETTELNUM:ERROR
Feedback message SETTELNUM:OK – command accepted
description SETTELNUM:ERROR – command rejected by the
system

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 36 / 106


Getting the phone number
Command syntax XXXX GETTELNUM=ID
Command description XXXX – user code
ID – index of phone number on the list, possible
values: 1 to 10
Example: 1234 GETTELNUM=2
Feedback message GETTELNUM=ID,NUMBER
or
GETTELNUM:ERROR
Feedback message GETTELNUM=ID,NUMBER – information about phone
description number
GETTELNUM:ERROR – command rejected by the
system

Setting the content of text message


Command syntax XXXX SETMESSAGE=ID,MESSAGE
Command description Setting the content of text message under the
pointed index
XXXX – user code
ID – index of text, possible values: 1 to 32
MESSAGE – content of the text message
Example: 1234 SETMESSAGE=4,Robbery
Feedback message SETMESSAGE:OK or SETMESSAGE:ERROR
Feedback message SETMESSAGE:OK – command accepted
description SETMESSAGE:ERROR – command rejected by the
system

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 37 / 106


Getting the content of text message
Command syntax XXXX GETMESSAGE=ID
Command description Getting the content of text message under the
pointed index
XXXX – user code
ID – index of text, possible values: 1 to 32
Example: 1234 GETMESSAGE=30
Feedback message GETMESSAGE=ID,MESSAGE
or
GETMESSAGE:ERROR
Feedback message GETMESSAGE=ID,MESSAGE – information about the
description contents of text message
GETMESSAGE:ERROR – command rejected by the
system

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 38 / 106


Assigning a text message and a phone number to the event
Command syntax XXXX SETUSERSMS=EVENT,TELNUM,MSG_ID
Command description Assigning a text message and a phone number to the
event. The text will be send to the phone number
when this event occurs.
XXXX – user code
EVENT – a short name of the event, possible event
names are listed at the end of this chapter
TELNUM – ten-digit chain of zeroes and ones. Each
digit (counting from the left) represents an index of
the phone number – first digit for the first phone
number, second digit for the second number, and so
on.
0 – message will not be send to this number
1 – message will be send to this number
Example:
1234 SETUSERSMS=ARM1,1000000110,6
Means, that when ARM1 event occurs (partition 1
armed), text message number 6 will be sent to phone
numbers with indexes 1,8 and 9.
Feedback message SETUSERSMS=EVENT,TELNUM,MSG_ID:OK
or
SETUSERSMS=EVENT,TELNUM,MSG_ID:ERROR
Feedback message SETUSERSMS=EVENT,TELNUM,MSG_ID:OK –
description command accepted
SETUSERSMS=EVENT,TELNUM,MSG_ID:ERROR –
command rejected by the system

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 39 / 106


Getting a text message content and a phone number assigned to the
event
Command syntax XXXX GETUSERSMS=EVENT
Command description Getting the content of a text message and a phone
number assigned to the specified event.
XXXX – user code
EVENT – a short name of the event, possible event
names are listed at the end of this chapter
Example: 1234 GETUSERSMS=ARM1
Feedback message GETUSERSMS=EVENT:TELNUM,MSG_ID
or
GETUSERSMS=EVENT:ERROR
Feedback message GETUSERSMS=EVENT:TELNUM,MSG_ID –
description information about text message and phone number
assinged to the event
GETUSERSMS=EVENT:ERROR – command rejected
by the system

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 40 / 106


List of events handled by the SETUSERSMS and GETUSERSMS commands
Alias name Description
ARM1 Partition 1 armed
ARM2 Partition 2 armed
DISARM1 Partition 1 disarmed
DISARM2 Partition 2 disarmed
INPUT1 Violation of zones 1…7
(to INPUT7)
INPUT1-OFF Violation of zones 1…7 ended
(to INPUT7-OFF)
INPUT1-TAMPER Sabotage of zones 1…7
(to INPUT7-TAMPER)
INPUT1-TAMPEREND Sabotage of zones 1…7 ended
(to INPUT7-TAMPEREND)
INPUT1-LOCK Bypass of zones 1…7
(to INPUT7-LOCK)
INPUT1-UNLOCK Bypass of zones 1…7 ended
(to INPUT7-UNLOCK)
OUTPUT1-ON Zones 1…3 triggered
(to OUTPUT3-ON)
OUTPUT1-OFF Zones 1…3 trigger ended
(to OUTPUT3-OFF)
OUTPUT1-TAMPER Fault of zones 1…3
(to OUTPUT3-TAMPER)
OUTPUT1-TAMPEREND Fault of zones 1…3 ended
(to OUTPUT3-TAMPEREND)
POWER-FAIL Power failure
POWER-OK Power failure ended
BATTERY-FAIL Battery failure
BATTERY-OK Battery failure ended
AUX1-FAIL Failure of auxiliary output 1
AUX2-FAIL Failure of auxiliary output 2
AUX1-OK Failure of auxiliary output 1 ended
AUX2-OK Failure of auxiliary output 2 ended

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 41 / 106


KEYPAD1-LOST Failure of keypad 1..3
(to KEYPAD3-LOST)
KEYPAD1-OK Failure of keypad 1..3 ended
(to KEYPAD3-OK)
KEYPAD1-TAMPER Sabotage of keypad 1…3
(to KEYPAD3-TAMPER)
KEYPAD1-TAMPEREND Sabotage of keypad 1…3 ended
(to KEYPAD3-TAMPEREND)
JAMMING-BEGIN GSM jamming
JAMMING-END GSM jamming ended

List of errors sent as feedback messages


Alias name Description
ERROR-PERMISSION Permission to issue this command was not granted
ERROR-FORMAT Wrong command syntax
ERROR-VALUE Wrong parameter value
ERROR-EMPTY Parameter value missing
ERROR Other error

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 42 / 106


7. CONFIGURATION WIZARD

7.1. PRELIMINARY NOTES

The configuration wizard of GPRS transmitters can be downloaded from www.ebs.pl


(login: ebs, password: ebs). Activate the option of installation wizard which leads through
the program installation process. By default it will be installed in C:\Program Files\EBS\
directory. The installation wizard can also create shortcuts to the program on the desktop
and in the Windows menu.
If it is the first use of the equipment, SIM card shall not be inserted into the slot until the
equipment is programmed using the above software. Otherwise, SIM card can be blocked
during the attempts of giving an incorrect PIN code. Alternatively, you can use SIM card
with PIN code authorisation deactivated.
In case of remote programming, SIM card must be inserted before the configuration settings
transmission is initiated. In this case use either SIM cards with PIN code authorisation
deactivated or change the PIN code using a mobile phone before the card is inserted into
the equipment.

7.2. COMPUTER – REQUIREMENTS

The minimum requirements for PC computer on which the configuration wizard is to be


installed are the following:
Hardware:
 Processor Pentium II 400MHz,
 64 MB RAM,
 1GB HDD,
 RS-232 serial port,
 Colour screen (min. 15”, resolution min. 800x600),
 Keypad,
 Mouse,
Software:
 Operating system: Windows 2000, Windows XP, Windows Vista or Windows 7,
 .NET Framework 2.0 software (delivered with a configuration installation wizard).

7.3. PROGRAM FUNCTIONS

After the program is installed and started, the main window will be displayed on the screen.
From that level you can access both, program functions and programmable parameters (see
chapter 7).
The main program window was divided into a few areas.
Main menu: located in the top section of the window, contains control and program
configuration functions.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 43 / 106


The main menu is composed of the following:

Main menu is also reflected in the visual form of icons on a taskbar:

7.3.1. Menu-> File

7.3.1.1. Menu-> New

Opens a new set of parameters. In this option configuration parameters of the


equipment can be edited.

Select a relevant type of the equipment: CPX200N

7.3.1.2. File -> Open

If you have a file with recorded settings you can use it for programming another
equipment. First, indicate a directory where the file was saved, then give the file
name. User can modify the received data. In order to be effective the implemented
changes must be sent to the equipment.

7.3.1.3. File -> Save

If you program many pieces of equipment in various configurations, you do not need
to remember each configuration. You can save all settings on your hard drive under a
specific name and read it later on. The function records all information from the
configuration wizard’s windows on a hard drive. After calling the function, a window
asking for file name is displayed. By default, data is saved in files with CMI extension
(Configuration Memory Image).

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 44 / 106


7.3.1.4. Menu-> Language

This option allows selecting one of available languages (defined in enclosed external
language files).

7.3.1.5. File -> Connections

Before you start the equipment programming, define the type of connection to be
used.
There are two programming methods available: local and remote.

7.3.1.5.1. Local connection

Local connection means that configuration wizard (or, in fact, a computer, on


which it is installed) is directly connected to a relevant connector of the alarm
control unit. The connection is executed through a dedicated programming cable
using RS-232 serial port.
To program the equipment or perform other activities (i.e. read the settings from
the equipment, change the firmware, etc.) you have to define the connection
parameters.

For the above purpose you shall use the above window, available after activating
File option from the Main Menu and selecting Connection function or after clicking
icon on a taskbar and opening RS-232 tab.
Define:
 Connection name, e.g. Local
 Select serial port, e.g. COM 4
Click [Add] button to confirm the setting. The connection is saved (and moved to
the table). From that moment the program will enable a wire connection with the
equipment and allows reading and recording the parameters in the equipment’s
memory.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 45 / 106


7.3.1.5.2. Remote connection

As explained above the equipment and software allows full configuration using
GPRS connection or CSD channel. For such programming mode the connection
parameters shall be adequately defined.

GPRS connection
The configuration of that mode requires the activation of File option from Main
Menu, and selecting Connection function (or clicking icon on a taskbar) and
opening GPRS tab.
The following window will be displayed on the screen.

Define:
 Connection name, e.g. Remote
 Select analyser name, e.g. primary
 Enter analyser name, e.g. www.ebs.pl
 Enter the port on which analyser will listen to instructions, e.g. 9000
Click [Add] button to confirm the setting. The connection is saved (and moved to
the table). From that moment the program will enable a remote connection with
the equipment and allows reading and saving the parameters in the equipment’s
memory.

NOTE: Such parameters as analyser’s name, analyser’s


address, port refer to the settings of the OSM.2007
monitoring system receiver. Remote programming is available
only in case the above mentioned equipment (software) is
used.
CSD connection
The configuration of that mode requires activation of File option from Main Menu,
and selecting Connection function (or clicking icon on a taskbar) and opening
GSM Modem tab.
 The window will be displayed on the screen where you define:

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 46 / 106


 Connection name, e.g. Remote CSD
 Serial port to which the GSM modem is connected to (e.g. Wavecom
Fastrack)
 PIN code of SIM card installed in the GSM modem, e.g. 1111
 Serial port parameters: Number of bits per second (e.g. 115200), Data Bits
(8), Parity (none), Stop Bits (1).

Click [Add] button to confirm the setting. The connection is saved (and moved to the
table). From that moment the program will enable a remote connection with the
equipment and allows reading and saving the parameters in the equipment’s
memory.

NOTE: Remote configuration via CSD channel is available only in


case the CSD data transfer is active for both SIM card inserted in
the equipment and SIM card installed in GSM modem.
Additionally, the control unit must accept CSD connections – see
item 5.5.2. Authorised numbers of GSM modems.
Programming through CSD connection is possible also when OSM.2007 system is
installed, with at least one GSM modem connected. If the device is registered for the
server (serial number and SIM card number – see OSM.2007 Manual) you can use the
connection via OSM. Provided that no GPRS connection is established. Programming
attempt (via GPRS connection – see the above) will end with a question whether you
want to use a modem connected to the server. If the answer is yes, the procedure
will continue as in case of other programming channels.

7.3.1.6. File -> Archiving

All configuration wizard’s settings, both these read from devices and these saved in
the equipment are automatically recorded on a hard drive. If, during configuration
wizard’s installation no directories were changed, the files can be found in e.g.:
C:\Program Files\EBS\KonfiguratorLX\configs\CPX200N_20000\

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 47 / 106


CPX200N_20000 directory contains all files related to programming the CPX200N type
device of the serial number 20000. Files names contain date and time of the
operation and its type (recording/reading). The files are recorded with .cmi extension.

7.3.1.7. File -> End

Ends the program operation.

7.3.2. Menu-> Operations

7.3.2.1. Operations -> Read

The function reads the data saved in the memory of GPRS module. Data is exchanged
through the port selected in the section “Select connection type” (see the description
of “Configuration” option below). A correct readout is confirmed with relevant
message. You can save the data downloaded from the equipment in a file (see item
6.3.1.3.), and then use it for other devices.
You can use that function after you define a type and parameters of the connection.
E.g. for local connection the following window is displayed:

where:
Port - serial port that the module is currently connected to.
Access code – service code of the equipment
For detailed description of connection configuration, please refer to item 7.3.1.5.

7.3.2.2. Operations -> Send

The function is similar to the above, but it allows recording data to the memory of
EEPROM module. It is also possible to set internal timer of the device. For the above
you have to check the box “Set the time” and enter a respective date and time. A
correct entry is confirmed with a relevant message.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 48 / 106


7.3.2.3. Operations -> Restore default settings

In case the “Read” operation results in an error message (e.g. when access code is
not known) you can return to default settings. For the above select that function. The
screen displays the message “Do you want to overwrite the parameters with default
settings?” Upon confirmation the connection definition window will be displayed:

The operation is possible using local connection only. After the operation is completed
the equipment parameters will return to default factory settings.

7.3.2.4. Operations -> Event History

The function enables to read out the events lately recorded in the memory of the
equipment. Please refer to chapter 5.10.

7.3.2.5. Operations -> Equipment Monitoring

The function allows the on-going monitoring of the equipment condition. Please refer
to chapter 5.9.

7.3.3. Menu -> Help

Select this function for additional information about the program.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 49 / 106


7.4. DEVICE PROGRAMMING

In order to program the equipment, first you have to establish a connection with the
equipment. Depending on the connection mode two programming methods are available.

7.4.1. Local Programming

For local programming of the equipment, you should:


 In PROG mode connect GD-PROG service cable between CONF connector (on device’s
PCB) and computer’s COM port, defined in Connections -> RS-232 option.
 Connect the power supply to the alarm control unit. Upon connecting the power
supply and detecting the programming cable, the module will indicate it with LEDs:
the green one will go on and the red one will flash quickly.
 Start the configuration wizard and define the options of the equipment (please refer
to chapter 8).

NOTE: Enter correct PIN code for used SIM card.

 Select Send function. The window will appear where you have to select the previously
defined local connection (chapter 6.3.1.5.1). Copy the settings into the memory of
the equipment.
 Switch the power off and disconnect the programming cable or switch the
programming device into DEBUG mode.
 Insert SIM card.
 Re-connect the power supply.
 The equipment is ready for operation.

7.4.2. Remote Programming

Remote programming of the equipment is possible in two cases:


 User has a configuration wizard of GPRS transmitters and computer-connected GSM
modem.
 User works based on the receiver of OSM.2007 monitoring system.
In the first case remote programming is carried out via CSD channel and the procedure is
the same as for local programming, with the only difference that in the options of a
connection the “GSM modem” shall be selected (please refer to chapter 6.3.1.5.2 – CSD
connection.

NOTE: Remote configuration via CSD channel is available only in


case the CSD data transfer is active for both SIM card inserted in
the equipment and SIM card installed in GSM modem.
In the second case, in accordance with chapter 6.3.1.5.2 - GPRS connection, you shall
define remote connection based on OSM.2007 parameters. Since OSM.2007 receives
(and sends) information only from equipment that is registered in its database, the first
operation you have to do for remote programming it to properly register the equipment.
The procedure is described in OSM.2007 user manual.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 50 / 106


7.4.2.1. First programming of the equipment

As no access parameters to GPRS network and OSM.2007 are defined in the


equipment, you shall start the programming with defining the parameters.
Irrespectively of the input method, first you have to register the equipment in the
OSM.2007 database.
Before starting the remote programming, you have to make sure that the SIM card
was inserted (subject to conditions defined in chapter 7.1.5.3) and the equipment
was connected to power supply. The user must know the serial number of the
equipment and SIM card telephone number.
The programming procedure is the following:
 Using the pad of OSM.2007 device, indicate with the cursor the correct equipment
in ‘Equipment’ tab.
 Click “Config” option and then indicate “Set configuration” function. A list of
parameters will be displayed.
 Enter server address, server port and APN. When clicking OK, the system will send
entered parameters to the equipment (SMS).
 Wait until the equipment reports to the server (in Equipment tab, it will be marked
green).
 Start the software and define the options of the equipment (for description, please
refer to chapter 7).
 Select Send function. The window will appear where you have to select the
previously defined remote connection (chapter 6.3.1.5.2). Copy the settings into
the memory of the equipment.
 Close the configuration wizard’s window after you finish the data input.
 The equipment is ready for data transmission.

7.4.2.2. Reprogramming of equipment.

As access parameters to GPRS network and OSM.2007 are defined in the equipment,
you can proceed with programming any time.
If the equipment is installed in a secured facility, i.e. it has a SIM card inserted and it
is connected to power supply, the programming procedure in the following:
 Start the configuration wizard software and define the options of the equipment
(for description, please refer to chapter 7).
 Select Send function. The window will appear where you have to select the
previously defined remote connection (chapter 6.3.1.5.2). Copy the settings into
the memory of the equipment.
 Close the configuration wizard’s window after you finish the data input.
 The equipment is ready for data transmission in accordance with new settings.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 51 / 106


8. PROGRAMMABLE PARAMETERS
Parameters available in configuration wizard were divided into groups: Access, Transmission,
Entrances/Exits, Monitoring, Restrictions, SMS Messages, Connection Control, Firmware.
Each of the groups will be described in detail further on.

8.1. ACCESS

8.1.1. Parameters

8.1.1.1. Equipment operation mode

Depending on user’s preferences, the equipment can operate in one of 4 modes (to
be selected from a drop list):
 GPRS & SMS: GPRS transmission (TCP/IP protocol) in standard and in case of
problems with that connection, automatic switch into SMS mode
 SMS: Transmission only in SMS mode without the attempt of establishing a GPRS
connection
 GPRS: GPRS transmission (TCP/IP protocol) in standard. In case of any problems
with that connection, no remote connection is possible
 No server connection: no transmission with server, remote communication with a
user is possible only via SMS messages

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 52 / 106


8.1.1.2. GPRS test period

At a pre-defined interval the equipment sends “Test” signal that informs the
monitoring station that the device is operating. In that box, you can determine at
what interval defined in seconds the message will be sent.

8.1.1.3. SMS mode after a number of unsuccessful attempts

Here you define the number of attempts to connect with the server. If during the
attempts no connection is established, after they terminate, the device will switch into
SMS mode. In this mode the equipment still attempts to connect with the server, at
an interval defined in item 7.1.3.3.

8.1.1.4. SMS test period

The function is the same as for GPRS. It refers to the situation of any problems with
GPRS transmission, when the equipment automatically switches into SMS mode (it
also refers to the operation mode via SMS only). Sending a test SMS message as
often as in case of GPRS transmission is usually undesirable. That parameter allows
significant extension of interval between tests (time in minutes) or disabling that
option.

8.1.1.5. Telephone number of a server

If to the server application (e.g. OSM.2007) a GSM modem is connected, here you
have to enter its number. SMS messages will be sent to this number in case the
equipment encounters problems with GPRS transmission.
In case the box remains empty or 0 is entered, the equipment will operate in GPRS
mode only.

NOTE: This box will be inactive in case the GPRS operation mode
of the equipment was defined.

8.1.1.6. Send SMS events immediately

In case the GPRS connection is lost, information on upcoming events will be sent by
SMS immediately, even in case the equipment has not switched to SMS mode yet.

8.1.2. Access Point Name

8.1.2.1. APN

The parameter depends on GSM network operator whose GPRS service will be used.
It defines the name of access point to GPRS network. There is a possibility to obtain a
private access point. In this case its name will be given by a particular GSM network
operator.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 53 / 106


8.1.2.2. User ID

Most often it is not required while using public APN. For private APN, you should
obtain that parameter from the operator (without it no access to GPRS network can
be granted).

8.1.2.3. User password

Most often it is not required while using public APN. For private APN, you should
obtain that parameter from the operator (without it no access to GPRS network can
be granted).

NOTE: Using private APN increases the system security.

8.1.2.4. DNS1 and DNS2

It defines the address of primary and secondary DNS (Domain Name System). If
server address was entered as a domain name at least one DNS address must be
entered.

8.1.3. Primary Server Parameters

8.1.3.1. Server IP Address

It is the IP address of a monitoring system receiver (OSM.2007) or a computer on


which “Communication server” software is installed, e.g. 89.123.115.8. The address
can be given as a server’s domain name, e.g. modul.gprs.com. In such a case at least
one DNS server address is required.

8.1.3.2. Server port

It defines a port which was dedicated in the server for the receipt of data from the
equipment.

8.1.3.3. Interval between subsequent attempts of establishing connection


with a server.

The programmed equipment with SIM card inserted will automatically attempt to
establish connection with a server. Here you can define an interval (in seconds) after
which the equipment will retry to connect with a server, in case the previous attempt
was unsuccessful.

8.1.3.4. Number of attempts of establishing connection with a server.

You can define how many times the equipment will try to connect with the server in
case of subsequent faults. After a defined number of attempts, the equipment will
initiate the procedure of connecting with secondary server. The option is active only
in case the secondary server parameters were defined.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 54 / 106


8.1.3.5. Sequence of connections with servers

If you check this box, the equipment will try to establish a connection with primary
server, irrespectively of the secondary server parameters set (in particular, the
number of connection attempts).

8.1.4. Secondary Server Parameters

8.1.4.1. Server IP Address

It is the IP address of a secondary (redundant) monitoring system receiver


(OSM.2007) or a computer on which “Communication server” software is installed,
e.g. 89.130.125.82. The address can be given as a server’s domain name, e.g.
monitor.gprs.com. In such a case at least one DNS server address is required.

8.1.4.2. Server port

It defines a port which was dedicated in the server for the receipt of data from the
equipment.

8.1.4.3. Interval between subsequent attempts of establishing connection


with a server.

If the equipment cannot connect with primary server, after the defined number of
attempts it will initiate the procedure of connecting with a secondary server. Here you
can define an interval (in seconds) after which the equipment will retry to connect
with a server, in case the previous attempt was unsuccessful.

8.1.4.4. Number of attempts of establishing connection with a server.

You can define how many times the equipment will try to connect with a secondary
server. In case of subsequent unsuccessful attempts, after the defined number of
attempts is executed, the equipment will return to the procedure of connecting to
primary server.

8.1.4.5. Time for disconnection

If you check this box, the equipment will disconnect the secondary server after a
defined time. The following operation depends on the Connection sequence
parameter (refer to 7.1.3.5). If the option is active the equipment will try to connect
to primary server. In case the option is inactive, the equipment will complete the
procedure of connecting to secondary server first, and in case it is unsuccessful, it will
move on to attempting the connection with primary server.

8.1.5. Access

8.1.5.1. Service code

It secures the equipment against unauthorised access. It is used for both, equipment
programming and for its remote control (in TCP/IP or SMS mode). Default factory
setting is 0000. It should be changed at first equipment start-up (programming). It
can be composed of up to seven alphanumerical characters.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 55 / 106


8.1.5.2. Installer’s service code

Installer’s service code is used for equipment programming process using KP10
keypad. Default factory setting is 2222. It should be changed at first equipment start-
up (programming). The code can be composed of from four to seven digits.
Installer’s service code could be read and change remotely via OSM.2007 Console or
by sending SMS message. In case of reading Installer’s service code via OSM.2007
Console, please send following Custorm command:
GETPARAM=3,1
The answer with current Installer’s service code appears in the bottom part of the
Console window.
Installer’s service code could be changed via OSM.2007 Console. In such case, please
send following Custom command:
SETPARAM=3,1,new_code
where new_code should containt from 4 up to 7 digits.
The way of reading and changing Installer’s service code by SMS message is
described in the chapter SMS RECEIPT

8.1.5.3. SIM Card PIN code

Since the equipment uses GSM network for its operation, it is necessary to obtain a
SIM card from a mobile network operator. You have to set a PIN code of a SIM card
dedicated for operation in particular equipment before its first use. It is necessary for
automatic start up of the system. In case you have a card without the PIN code, you
can enter any value in that box, e.g. 0000.
If you enter incorrect PIN code, the system will not start after inserting the card and
switching the power supply on and you will not be able to use the card until you
enter the PUK code (using any GSM phone).
Default factory PIN code entered in the equipment is: 1111.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 56 / 106


8.2. TRANSMISSION

For the maximum transmission security the data transmitted are encrypted using AES. The
option can be used for both, GPRS and SMS transmissions.
In case encrypted transmission was selected, you can enter own data encryption key (DEK)
(256 bits - 0-9 and A-F characters) or use default setting.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 57 / 106


8.3. INPUTS/OUTPUTS

The alarm control unit has 7 fully configurable zones and 3 software controlled outputs.
Zones can be freely divided into two partitions. Each of zones and outputs has a number of
programmable parameters defined below.

8.3.1. Zones

8.3.1.1. Zone mode

The parameter allows for determining the stable input line state. Any change of that
state causes alarm message to be sent. Input can be NC or NO type. The following
configuration types are available: NC / NO / EOL-NC / EOL-NO / DEOL-NC / DEOL-
NO. NC type input must be closed for the whole time. Line interruption causes its
induction. NO type input remains open. It activates when closed. EOL and DEOL (with
parameters or double parameters assigned) differ with 1 or 2 resistors allowing
distinguishing alarm from sabotage. Electric diagrams for all configuration types were
described in chapter 3.4.

8.3.1.2. Response type

 Instant – disruption of the line causes immediate alarm, if the system is armed.
 Delay – that type of line is usually used for detectors operation at the facility
entries. The line switches into alarm state after the expiration of programmed
time for entrance. If the system is armed, the line activation initiates counting the

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 58 / 106


time for entrance to a particular partition. The system should be disarmed before
the expiration of programmed time in order not to trigger the alarm.
 24h burglary – that line causes immediate alarm irrespectively of whether the
system is armed or not.
 Arming/disarming – the line can be used for arming or disarming the system.
In case the line is activated with the system disarmed, the partition assigned to
the line is armed. In case the line is activated with the system armed, the partition
assigned to the line is disarmed.
 24h tamper – the line can be used for connecting tamper/sabotage circuits. In
case of trigger when partition is disarmed, it raises the fault. In case of trigger
when partition is armed, it raises the alarm.
 Interior delay – the line can be used when keypad is not in the first partition
which could be triggered during access to the keypad. In case of the interior delay
partition is triggered, system checks if time for enter is counting. If yes, the line is
treated as delay line. If not, the lien is treated as instant line.
 24H burglary silent – sends a report to the central station but provides no
keypad display or sounding.
 24H fire – works like 24H burglary.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 59 / 106


8.3.1.3. Interlocking

The option allows interlocking any input line, which means that any changes of state
at this input are ignored and not reported to monitoring station.
You can set the set permanently blocking input ("Permanent"), or turn on the
blocking after a given number of input violations.
If you select "After time for exit", the input line will be blocked if the line was violated
when arming. In this case, an event about blocked line will be generated, which
allows to inform the monitoring station about the problem with the line. This lock will
last until disarming. If the input is selected as the "Alarm after time for exit", then
"Interlocking after time for exit" has priority - the zone will be blocked and will not
generate an alarm.
If the line is set to "After time for exit" and is violated or sabotaged after the time for
exit, then is automatically bloked (bypass is activated). User can unlock the input by
use the function 50 # (block inputs).

8.3.1.4. Sensitivity

That parameter defines a minimum time the change must maintain at the particular
zone, to be detected by a transmitter. Default factory setting of the parameter is 400
ms.

8.3.1.5. Delay

The parameter is active for delayed type zones only. It defines a time from the zone
disruption was detected after which an alarm is generated.

8.3.1.6. Alarm after time for exit

Enabling this option causes the panel immediately generates an alarm when the zone
was violated when the system is armed.

8.3.1.7. Ignore during arming

Zone can be violated during partition arming (e.g. delay circuits shall be set to that
option).

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 60 / 106


8.3.2. Partitions

8.3.2.1. Partittion 1 / 2

In that tab you can assign the zones from 1 to 7 to the specific monitoring partitions.
If the zone is not assigned to any of the partitions (and it is not of 24H type), all
events received from that zone (disruption/return) will be ignored.

8.3.2.2. Entrance / Exit

The parameter allows switching off the indication of time for entrance / exit displayed
by KP10 keypad.

8.3.2.3. Time for exit

It is time for leaving the partition. Assigned zones will be active (monitored) after the
expiration of pre-defined time, counting from the time the arming zone was
disrupted.

8.3.2.4. Alarm time

The parameter defines the time the alarm will be indicated by KP10 keypad.

8.3.2.5. Partition name

The parameter allows you to give any name for the partition.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 61 / 106


8.3.2.6. Timer

In this section, you can set the parameters of automatic arming and disarming the
partition.

You can set the time for arming/disarming and you can independently turn on and off
each time. By clicking the check box, located on the left side of the time field, you
can activate/deactivate the time. If auto-arming/disarming is off, the time field is
grayed out.

When the partition is automatically armed / disarmed, to the monitoring station is


sent a report that was done by the user with the number 253.

At the time of auto-arming, exit time is starting. During the exit time, the user may at
any time to stop arming with the code. Then the system will not be armed.

If there is a fault in the system, they not prevent arming (like remote control and
remote command).

For each input line is available „Interlocking after time for exit” option. If this option
is active, in the case of arming with violated zone, after time for exit, will be
generated event about blocked zone. Zone blocking will continue until partition
disarming (see item 8.3.1.3. Interlocking).

When set to the same time arming and disarming, the system will first be disarmed
and then immediately armed.

If the time in the device is set forward (eg. when the time is changed to Daylight
saving time), and arming or disarming time is in the period which has been ommited,
then the hour will be not used. Eg. If the auto-arming time is set to 2:30, and time
was changed forward from 2:00 to 3:00, the control panel will not arm.

Times of arming and disarming can also configure by remote command via GPRS or
SMS.

NOTE: To use the auto-arming/disarming function, you should do


a firmware upgrade to version 1.1.1 or higher, then read and
write the configuration of the device using “GPRS transmitters
configurator” program in version 1.3.45.023 or higher.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 62 / 106


8.3.3. Outputs

8.3.3.1. Outputs 1 / 2 / 3

Types of outputs:
 Non-used – Output is inactive
 Alarm – Output is activated when alarm is detected.
 Standby indicator – Output is activated when the assigned partition is armed.
 Power supply fault – Output is activated when power supply fault is detected.
 Communication loss – Output is activated when information transmission to
server is not possible.
 Chirp – The output is activated when arming (1 chirp) or disarming (2 chirps).
The minimum duration of the chirp signal possible to set from the configurator is
40ms. In the case of set time for exit chirp is generated after arming, similarly in
the case of the time for entry chirp is generated after disarming.
 Alarm & chirp – The output is activated when alarm is detected or when
arming/disarming.

8.3.3.2. Partition 1 / 2

The parameter allows assigning particular monitoring partitions to outputs.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 63 / 106


8.3.3.3. Activation time

The parameter defines the time the output is to be active.

8.3.3.4. Bistable

This parameter sets the output to the bistable work.

8.4. SYSTEM OPTIONS

8.4.1. Show failures history with SYSTEM diode

Selecting this option indicates that a fault occurred in the system and be completed. This
condition will be indicated by flashing SYSTEM LEDs on the keyboard KP10 until cleared
the fault memory.

8.4.2. Ignore ATS failure

Selecting this option turns off signaling a loss of communication with the server on KP10
keypad.

8.4.3. Turn automatic override for failure off

Selecting this option enables the system fault signal when arming.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 64 / 106


8.5. USERS

This option allows user managing. To be able to manager the users one has to press the
‘Edit’ button first and the input the correct administrator code. Granted the authorization, it
will be possible to edit the users’ passwords and partition priviliages.
After editing press the ‘Accept changes’ button, and then upload the configuration to the
device. When uploading a configuration, "Write users" option must be selected in the writing
options.
Users’ configuration changes can be made only via programming cable. Users update is not
possible remotely via GPRS.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 65 / 106


8.6. MONITORING

That option allows determining which of available signals generated by the equipment will
be transmitted to the monitoring station.

NOTE: The “Configuration change” event refers to configuration


change via SMS or via GPRS instructions only.

8.6.1. Events

8.6.1.1. GPRS ON/OFF

In these columns you can check which signals are to be reported to the monitoring
station via GPRS transmission. You have the option to send information on both,
alarms (change of zone state from idle into active) and returns of zones states from
active into idle (normalisation). In order to transmit a particular signal you have to
check it (by clicking a relevant check box on the right hand side).
Press [Clear] button to remove all checked signals.
Press [Reverse] to reverse the check into the opposite ones.

8.6.1.2. SMS ON/OFF

In these columns you can check which signals are to be reported to the monitoring
station via SMS message – when the equipment is not connected with server via

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 66 / 106


GPRS connection. You have the option to send information on both, alarms (change
of input state from idle into active) and returns of zone states from active into idle
(normalisation). In order to transmit a particular signal you have to check it (by
clicking a relevant check box on the right hand side).
Press [Clear] button to remove all checked signals.
Press [Reverse] to reverse the check into the opposite ones.

8.6.1.3. Power loss

One of the additional options of the equipment is the control of supplying voltage. As
transient power losses can occur in some facilities, you can avoid reporting them by
entering the time after which the information will be sent. The value of the parameter
means that power loss must last for that pre-defined time for the equipment to
recognize it a factual power loss and to send a relevant message.

8.6.2. Additional data

The Additional data functionality allows for defining kinds of additional data which will be
transmitted together with events to monitoring station via GPRS/SMS. The data may
become valuable information about device's work conditions though it may increase
amount of bytes sent through GSM network. It is possible to define two separate sets of
additional data kinds: for test events (sent periodically according to setting on Access
tab) and for other events. Put a mark next to the name of data kind to turn on
transmission of this data kind to monitoring station. Empty field means that this kind of
data will be not transmitted.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 67 / 106


The adjustable parameters are:
 Power status - information about connected charger and battery charging
 GSM status - status about connection to GSM network, type of connection to
server (GPRS/SMS), information about ongoing phone calls
 GSM signal level quality - quality of connection to GSM network (CSQ and BER
parameters)
 Battery voltage - voltage of battery in millivolt unit

8.7. RESTRICTIONS

8.7.1. SMS and data calls (CSD)

8.7.1.1. Authorised SMS Telephone Numbers

The user can restrict a remote access to the equipment (via SMS) from pre-defined
telephone numbers. Created list of telephone numbers (up to 5) means that the
equipment can be controlled from these telephone numbers only.
Available options are:
 Restrict all: Means no possibility of communication.
 Allow all: Means that communication is allowed from any telephone number.
 Allow selected: Means that communication is allowed only from these listed
telephone numbers. You can define up to 5 telephone numbers.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 68 / 106


When ‘Allow selected’ box is selected you receive access to an edit box. Enter the
subsequent numbers in the box and click [Add] button to move the number to the
table below. To remove the number from the table, place the cursor in a particular
number line and click [Remove].
“Remove all” option will clear all the numbers from the table.

NOTE: Incoming SMSs are authorised by comparing the number


from which the SMS arrived with the ones that are entered in the
table. It is allowed to enter only a part of the number in the table
e.g. 1234. Then, all numbers containing the stipulated sequence,
e.g. 600123456 or 601234567 will be accepted.

NOTE: If modem connected to OSM.2007 server will be used for


sending SMS, its telephone number must be added to the above
list.

8.7.1.2. Authorised GSM Modems Numbers

For connections in CSD channel the user can restrict a remote access to the
equipment via GSM modems. Created list of numbers (up to 5) means that the
equipment can communicate with these numbers only.
Available options are:
 Restrict all: Means no possibility of communication.
 Allow all: Means that communication is allowed from any telephone number.
 Allow selected: Means that communication is allowed only from these listed
telephone numbers. You can define up to 5 numbers.
When ‘Allow selected’ box is checked, you receive access to an edit box. Enter the
subsequent numbers in the box and click [Add] button to move the number to the
table below. To remove the number from the table, place the cursor in a particular
number line and click [Remove].
“Remove all” option will clear all the numbers from the table.

NOTE: Incoming CSD connection is authorised by comparing the


number from which it arrived with the ones that are entered in
the table. It is allowed to enter only a part of the number in the
table e.g. 1234. Then, all numbers containing the stipulated
sequence, e.g. 600123456 or 601234567 will be accepted.

NOTE: If modem connected to OSM.2007 server will be used for


incoming CSD connection, its telephone number must be added
to the above list.

8.7.1.3. Validity Period of Outcoming SMS

The user can define time for the equipment to transfer information via SMS. Validity
period is defined separately for the following groups of information:
 SMS tests to server
 SMS events sent to server

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 69 / 106


 SMS events sent to the user
 Replies to commands
You have an option to select among the values on a drop list by clicking the arrow
next to the check box. Available options are: 5, 10, 15, 30 minutes; 1, 2, 6, 12 hours;
1, 7 days; MAX (no validity period set).

8.7.1.4. Outcoming SMS

The user can restrict the number of SMS to be sent by the equipment. As GPRS shall
be the primary transmission mode, this restriction is important mainly for economic
reasons.
Check the [Activate SMS restrictions] check box to activate the access to information
groups subject to restrictions:
 SMS tests to server
 SMS events sent to server
 SMS events sent to the user
 Replies to commands
 Restrictions are defined by specifying two values:
 Max number of SMS: Defines a maximum number of SMS sent in a time unit
(please refer to ‘Counter reset’ parameter). This option protects the user
against sending too large volume of SMS, e.g. in case of a fault.
 Counter reset: That parameter defines time (in minutes) after which the
counter of SMS sent is to be reset.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 70 / 106


8.7.2. Remote commands

8.7.2.1. Users remote management enable

Selecting this option allows you to remotely configure user accounts.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 71 / 106


8.8. SMS NOTICES

8.8.1. Phones

CPX200N can notify users about occurrence of certain events by text message. In order to
add user’s number to the notification list, one has to type in the number next to the number
index. Device can handle up to 10 phone numbers

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 72 / 106


8.8.2. Messages

Text for each message has to typed in the Messages tab. These messages can be later
assigned to specific events in the Events tab.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 73 / 106


8.8.3. Events

In order to assign a message to an event, one has to select Event Type, and for that Event
Type in the Message column, select one of the messages defined before. To assign a
number to an event, a corresponding column from Num 1 to Num 10 has to be checked.
From now on, whenever this event occurs, a text containing selected message will be send
to the selected phone numbers.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 74 / 106


8.8.4. Options

For the user to be able to use his smartphone application, Cooperation with smartphone
option has to be checked in the Options tab.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 75 / 106


8.8.5. SMS Forward

The equipment is able to transfer the received SMS messages to pre-defined telephone
numbers in accordance with pre-defined rules. The function may prove necessary in case
of account info sent via SMS. In this box you can enter up to 5 rules intended for transfer
of SMS messages.
Each rule is composed of a set: a fragment of a sender’s telephone number and correct
telephone number of a recipient. In extreme situation a fragment of sender’s telephone
number can be composed of an empty sequence, which means it is applicable to any
telephone number. Rules are processed in accordance with a pre-defined sequence from
the beginning to the end, i.e. the result of processing of a given rule does not influence
the processing of the subsequent rules. It also means that a given SMS message can be
sent to a few telephone numbers or that the same SMS can be sent a few times to the
same telephone number. Such a case occurs when the condition that refers to a sender’s
telephone number is met for at least two rules having the same recipient’s number.

NOTE: The user is responsible for correct entering the telephone


numbers that prevents any turmoil in sending SMS messages.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 76 / 106


8.9. LINK CONTROL

These options allow automatic equipment’s response in case the connection with the
monitoring station is lost. It refers to situations when the equipment lost the connection
with GSM network or GPRS transmission is not possible.

8.9.1. GSM

Activating that function (checking the [Activate] box) allows the access to parameters
defining the equipment’s response after leaving GSM network.
You can define after what time from the moment the connection was lost the equipment
shall initiate activities aiming at its restoration. The time is selected in a [Reset after] box
and is defined in minutes.
Then, define what activity shall be initiated by the equipment. Select by checking an
appropriate box at the response description:
 Modem reset
 Device reset
In case the equipment lost the GSM connection, it shall wait for a defined period of time
after the fact was ascertained and then it shall perform stipulated tasks.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 77 / 106


8.9.2. GPRS

Activating that function (checking the [Activate] box) allows the access to parameters
defining the equipment’s response after losing connection with a server.
You can define after what time from the moment the connection was lost the equipment
shall initiate activities aiming at its restoration. The time is selected in a [Reset after] box
and is defined in minutes.
Then, define what activity shall be initiated by the equipment. Select by checking an
appropriate box at the response description:
 Modem reset
 Device reset
In case the equipment lost the GPRS connection, it shall wait for a defined period of time
after the fact was ascertained and then it shall perform stipulated tasks.

8.10. FIRMWARE

The equipment has integrated bootloader that enables module software update. During the
programming all that process information is displayed.
The following activities shall be performed:
 Start configuration wizard,
 Go to wizard’s “Firmware” option,

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 78 / 106


 Open a file with a new firmware (click [Open] to indicate a location of an appropriate
file),
 Select the file transmission method: local.
 Click [Start] button. The software replacement procedure will be initiated.
 The course of recording is displayed in special software’s window.
 Close the configuration wizard after you finish the recording.
 Wait a few couple of seconds for the equipment to re-start.
Since now the equipment will operate under the control of a new firmware.

NOTE: The firmware update procedure shall be carried out with special
care as improperly performed operation can prevent the correct
operation of the equipment.

8.11. DEVICE MONITORING

The function “Device Monitoring” allows the on-going monitoring of the control unit’s
condition. In order to use that functionality, connect the alarm control unit to a PC computer
via GD-PROG cable in DEBUG mode and then, in “Port” box select an appropriate RS232
port. Monitor allows the control of the following parameters:
 Condition of mains power supply
 GSM network signal strength and bit error ratio (BER)

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 79 / 106


 Condition of zones
 Condition of outputs
 Equipment type/ serial number
 PCB version
 Equipment time
Changes of all parameters are also displayed in a text form in ‘Log’ box.

8.12. EVENTS HISTORY

The function enables to read out the events lately recorded in the memory of the
equipment. The control unit has an event log memory where about 5 thousand technical
events can be recorded. You can review the events history via GPRS and RS232 connection.
In the second situation, first you have to connect the equipment to a PC computer via GD-
PROG cable. Then, in the “Event History” box select an appropriate RS232 port or GPRS
connection, enter access code and click “Read” button. After correct reading you will get the
access to “Filtering” and “Graphs” functions which allow you a quick diagnosis of the
equipment.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 80 / 106


CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 81 / 106
9. LED INDICATION
The equipment indicates its current state using 3 LEDs, installed directly on PCB.

9.1. NETWORK LOG-IN

After SIM card is inserted and power supply connected to the equipment, the GSM network
log-in attempt is undertaken.
LEDs
Description OK ERROR STATUS
(green) (red) (yellow)
GSM network
log-in
attempt

9.2. GSM RANGE

GSM signal strength is indicated by flashing green LED (1-8 blinks). The operation mode of
the equipment is indicated by green LED which goes on for 2 seconds after the range is
indicated. In case the LED does not go on for 2 seconds after the range is indicated, it
means SMS mode of equipment operation. Range indication is interrupted during data
transmission, after which the GSM range is displayed.
LEDs
Description OK STATUS
ERROR (red)
(green) (yellow)
GSM range = 8
GPRS mode

GSM range = 6
SMS mode

9.3. TRANSMISSION

During data transmission green LED indicates the data sending.


LEDs
Description OK ERROR STATUS
(green) (red) (yellow)
GPRS
transmission

SMS
transmission

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 82 / 106


9.4. PROGRAMMING

After the programming cable is detected, LEDs start indicating the programming state.
LEDs
Description OK ERROR STATUS
(green) (red) (yellow)
Service
cable
connected

Programmin
g in CSD
mode

9.5. FIRMWARE UPDATE

During programming the bootloader activity is indicated. In case of error during updating
process, bootloader remains in the equipment and repeated equipment programming is
possible.
LEDs
Description OK ERROR STATUS
(green) (red) (yellow)
No software in the
equipment

Software update

Decryption of
firmware received

9.6. NO SIM CARD OR SIM CARD DAMAGED

In case of any problems with SIM card the equipment indicates it with a red ERROR LED and
green OK LED.
LED Indication

OK (green)

ERROR (red)

9.7. SYSTEM ERROR

During the equipment’s operation errors can occur. Error is indicated by constant light of red
LED and most often it means a communication problem with a modem or SIM card.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 83 / 106


10. EXTRAS

10.1. REMOTE COMMANDS AND CONFIGURABLE PARAMETERS

The control unit receives SMS in a specially designed form. If SMS that was received by the
equipment is not correct, it gets automatically deleted and the equipment does not initiate
any activity. The following format of the message is accepted, and it allows sending a few
commands in one SMS message, while each of them must be separated with a SPACE:
ACCESS CODE█COMMAND/PARAM█COMMAND/PARAM█………
where:
ACCESS CODE - access code of the equipment, may be either a service code, user
code or administrator code. In case the command requires authorisation by administrator
code (e.g. CPGETUSERS), this code should be passed to the command only once, either as
access code or as a parameter passed along with the command. In other words, whenever
access code is not an administrator code and the command has to be authorised by the
administrator code, it has to be passed as a command’s parameter.
█ - space
COMMAND/PARAM - instruction (see the tables below)
The newly configured parameter will be taken into account when the device will need to use
it, there is no need to restart the unit. However, there are parameters, changes to which will
be detected only in special circumstances, for example – the server address. If it is changed
when the device is online, a restart is needed. When CPX200N boots up, it will connect to
the newly configured address.
In order to delete a parameter, the message has to contain the name of the parameter
followed by the equation mark ( = ). For example, to delete the number to which text
messages are sent, one has to send a following text: “XXXX SMS=”, where XXXX is the
access code.

ATS – (Alarm Transmission System) – is a special type of user, meaning the monitoring
station. The user is authorized by the main access code to the device (the code to read the
configuration via a cable). ATS is also authorized by encryption keys. If the command is sent
through an encrypted transmission, code is not required.
User – regular user with the ability to arm and disarm the partition to which they have
rights, and other rights described in the user manual. Several regular users may be in the
system.
Administrator – a special user who has privileges to add and delete other users.

10.1.1. Configuration Parameters

10.1.1.1. APN

Format: APN=apn_name

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 84 / 106


Limitations: Data length to 31 characters, can be changed by ATS only

Description Configures the APN through which data will be sent by GPRS

10.1.1.2. UN

Format: UN=username

Limitations: Data length to 31 characters, can be changed by ATS only

Description Sets the user name for APN

10.1.1.3. PW

Format: PW=password

Limitations: Data length to 31 characters, can be changed by ATS only

Description Sets the password for APN

10.1.1.4. SERVER

Format: SERVER=server_address

Limitations: Data length to 31 characters, can be changed by ATS only

Description Sets the OSM server address with which the device exchanges data.
adres_serwera can be given in the domain format,
eg.device.mycompany.com domain or IP address, such as 173.194.69.94

10.1.1.5. PORT

Format: PORT=port

Limitations: A number between 1-65535, can be changed by ATS only

Description Sets the OSM server address with which the device exchanges data

10.1.1.6. SMS

Format: SMS=phone_number

Limitations: Data length to 15 characters, can be changed by ATS only

Description Sets the phone number for sending SMS with the events in the absence of
GPRS communication. If the number is not configured sending SMS
messages will not be available. phone_number may contain a prefix of the
country.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 85 / 106


10.1.1.7. SMSPERIOD

Format: SMSPERIOD=time_in_minutes

Limitations: String representig a number, can be changed by ATS only

Description Sets the SMS test period, the time is given in minutes.

10.1.1.8. DT

Format: DT=YY/MM/DD,hh:mm

Limitations: Data length of 14 characters, can be changed only by ATS or


Administrator

Description Sets date and hour

10.1.2. General commands

They provide the execution of various tasks remotely, or the querying of certain parameters. If
the command is sent via SMS , the response is sent back to the telephone number from which
the command came. Do not send several commands in one SMS message or one frame, since
only one command will be executed , and it will not necessarily be the first command in the list.

10.1.2.1. DISC

Format: DISC

Limitations: Can be executed by ATS only

Description Disconnects TCP connection with OSM server

10.1.2.2. KILL

Format: KILL

Limitations: Can be executed by ATS only

Description Restarts the GSM modem in the device. This results in breaking a GPRS
session and deregistration from the GSM network and re-registration to
GSM and GPRS network when you restart the modem

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 86 / 106


10.1.2.3. RESET

Format: RESET

Limitations: Can be executed by ATS only

Description Restarts the whole device. This results in breaking a GPRS session and
deregistration from the GSM network and re-registering to GSM and GPRS
network when you restart the device and modem

10.1.2.4. DESC

Format: DESC

Limitations: Can be executed by ATS only

Description Returns a string with a description of the device containing firmware


version and serial number

10.1.2.5. GETCFG

Format: GETCFG

Limitations: Returns max. 160 characters, can be executed by ATS only

Description Gets the current, basic configuration of the device. The parameters are
returned in the following order:
SERVER:PORT, _APN_UN_PW,_DNS0
Where:
_ Space character (asci 0x20)
SERVER – OSM server address
PORT – OSM server port
APN – APN name by means of which the GPRS session is compiled
UN – APN user name
PW –APN password
DNS0 –DNS server address

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 87 / 106


10.1.2.6. OUT

Format: OUT=o,s[,time]

Limitations: Can be executed only by ATS or administrator

Description Sets the “s” status on “o” output. The “s” status is equal to 1 for switching
on, and 0 for switching off. If you want to switch on eg. the output 2,
send the command OUT = 2,1. Switching off the output 2 is done by
sending the command OUT = 2,0. If the output is switched on, the
switch-on time is equal to the configured time, or if the time parameter is
specified, the output is switched on for the specified number of seconds.
If the time parameter is equal to 0, the output is bistable switched on ie.
it will be only switched off when you send the command that disables the
output.

10.1.2.7. FLUSH

Format: FLUSH=x

Limitations: x is equal to 0 or 1, possible to execution only by ATS

Description For x = 0 it clears the queue of outstanding events to be sent to the OSM
server. This results in the loss of outstanding events - the device
generates then an event indicating the fact.
For x = 1 it clears the event log of the device.

10.1.2.8. SENDSMS

Format: SENDSMS=phone_no,text_wihout_spaces

Limitations: This command does not work when sent via SMS; possible to execution
only by ATS

Description Allows you to send the SMS to the specified phone number (phone_no)
with the specified content. This command is a tool with which you can get
information about the phone number of the SIM card installed in the
device when connected to the OSM server using GPRS.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 88 / 106


10.1.2.9. GETSTATUS

Format: GETSTATUS

Limitations: Can be executed by ATS, administrator or user.

Description Gets the current status of the device.


The returned data are in the following format:
zones,partitions,outputs,battery_voltage,voltage_AC,0x0,0x0,
blocked_zones

where:
zones – means the current zone status. It is a bit-vector, where bit 1
(counting from 0) means the zone 1 , bit 2 the zone 2, etc. If the zone is
impaired, the bit is set.
partitions – means the current partition status. It is a bit-vector, where bit
0 means the partition 1 and bit 1 the partition 2 (otherwise than for the
zone and outputs where bit 1 means the zone /output 1). If the partition
is armed or counts down the time to output the corresponding bit is set.
outputs – means the current status of outputs. It is a bit-vector, where bit
1 (counting from 0) means the output 1, bit 2 the output 2 and bit 3 the
output 3. If the output is enabled the bit is set.
Battery_voltage – battery voltage in mV (12000 = 12V). If the battery is
not connected, the readings may be incorrect, and be around 9V (9000)
voltage_AC – AC voltage at the AC terminals of CPX200N (downstream
the transformer) in mV (18000 = 18V)
blocked_zones – means the current status of the zone blockade. It is a
bit-vector, where bit 1 (counting from 0) means the zone 1, bit 2 the zone
2 itd. If the zone is blocked, the bit is set.

10.1.2.10. GETPARAM

Format: GETPARAM=parameter

Limitations: Parameter is equal to APN or UN or PW or Server or PORT or SMS or


SMSPERIOD or as id_typu , index, possible to execution only by ATS

Description Allows you to retrieve the value of a proper configuration parameter. The
configuration parameters are described in the section on parameters. It is
a twin command with SETPARAM.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 89 / 106


10.1.3. Commands for managing the users in CP

10.1.3.1. CPGETUSERS

Format: CPGETUSERS[= adminPassword]

Limitations: This command only works when sent through an encrypted way, you
must know the administrator password (the user id == 0). The command
needs the option “Allow remote user management” to be set active in the
Configurator. Can be executed only by ATS or administrator. If the
command is executed by the ATS, give adminPassword.

Description Gets a list of users defined in the device. adminPassword is the system
administrator password. The command returns:
CPGETUSERS:id:name:partitions,…
Where id is the user number, name is the text user name (which may be
empty), partitions is the bit-vector specifying the partitions to which the
user is authorized - bit 0 corresponds to the partition 1 , bit 1 to the
partition 2. The user with id == 0 is the administrator

CPGETUSERS:EPERMISIONS
If the administrator password specified is incorrect

CPGETUSERS:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPGETUSERS:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 90 / 106


10.1.3.2. CPGETUSERID

Format: CPGETUSERID=password

Limitations: This command only works when sent through an encrypted way and the
option “Allow remote user management” is set to active in the
Configurator. Possible to execution only by ATS

Description Verifies the user code specified as an argument of the command - checks
whether a user with the specified code exists.
Password is the password of the user, id is the user number, partitions
are the partitions to which the user is authorized - bit 0 corresponds to
the partition 1 , bit 1 to the patition 2. The command returns:

CPGETUSERID:EOK,id,partitions
If the user with the specified code exists

CPGETUSERID:EPERMISIONS
If the specified password is incorrect

CPGETUSERID:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPGETUSERID:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 91 / 106


10.1.3.3. CPSETUSERPARTITIONS

Format: CPSETUSERPARTITIONS=id,partitions[,adminPassword]

Limitations: This command only works when sent through an encrypted way, you
must know the administrator password (the user id == 0), id ranging
from 1 to 8 inclusive. The command needs the option “Allow remote user
management” to be set active in the Configurator. Can be executed only
by ATS or administrator. If the command is executed by ATS, specify
adminPassword

Description Sets the user authorization to the partition. Id is the number of the user
whose authorizations are changed, the partitions is the bit-vector with the
partitions to which the user should have the authorization - bit 0
corresponds to the partition 1, bit 1 to the partition 2 , adminPassword is
the system administrator password. The command returns:

CPSETUSERPPARTITIONS:EOK,id,partitions
If the change of the partition assignment was successful

CPSETUSERPARTITIONS:ENOT_EXISTS,id,partitions
If the specified user does not exist

CPSETUSERPARTITIONS:EPERMISIONS,id,partitions
If the administrator password specified is incorrect

CPSETUSERPARTITIONS:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPSETUSERPARTITIONS:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 92 / 106


10.1.3.4. CPSETUSERPASSWORD

Format: CPSETUSERPASSWORD=id,password[,adminPassword]

Limitations: This command only works when sent through an encrypted way, you
must know the administrator password (the user id == 0), id ranging
from 1 to 8 inclusive. The command needs the option “Allow remote user
management” to be set active in the Configurator. Can be executed only
by ATS or administrator. If the command is executed by ATS, specify
asminPassword

Description Changes the user's password. Id is the user identifier whose password is
changed, the password is his new password and the adminPassword is
the system administrator password. The command returns:

CPSETUSERPASSWORD:EOK,id
It the command is completed sucessfully

CPSETUSERPASSWORD:ENOT_EXISTS,id
If the specified user does not exist

CPSETUSERPASSWORD:EPERMISIONS,id
If the administrator password specified is incorrect

CPSETUSERPASSWORD:ELENGTH,id
If the new password is too short or too long or does not consist of digits

CPSETUSERPASSWORD:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPSETUSERPASSWORD:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 93 / 106


10.1.3.5. CPADDUSER

Format: CPADDUSER=id,partitions,password[,adminPassword]

Limitations: This command only works when sent through an encrypted way, you
must know the administrator password (the user id == 0), id ranging
from 1 to 8 inclusive. The command needs the option “Allow remote user
management” to be set to active in the Configurator. Can be executed
only by ATS or administrator. If the command is executed by ATS, specify
adminPassword

Description Adds a new user. Id is the user number, partitions are the partitions to
which the user will have the authorization - bit 0 corresponds to the
partition 1, bit 1 to the partition 2 , password is the password of newly
created user and adminPassword is the the system administrator
password. The command returns:

CPADDUSER:EOK,id,partitions
When a user is added

CPADDUSER:EALREADY_EXISTS,id,partitions
If the specified user already exists

CPADDUSER:EID,id,partitions
If the specified user ID is incorrect

CPADDUSER:EPERMISIONS,id,partitions
If you can not create a user because the password is incorrect
(administrator or user)

CPADDUSER:ELENGTH,id
If the new password is too short or too long or does not consist of digits

CPADDUSER:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPADDUSER:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 94 / 106


10.1.3.6. CPDELUSER

Format: CPDELUSER=id[,adminPassword]

Limitations: This command only works when sent through an encrypted way, you
must know the administrator password (the user id == 0), id ranging
from 1 to 8 inclusive. The command needs the option “Allow remote user
management” to be set active in the Configurator. Can be executed only
by ATS or administrator. If the command is executed by ATS, specify
adminPassword

Description Delete the user. Id is the user number, adminPassword is the system
administrator password. The command returns:

CPDELUSER:EOK,id
If the user is deleted

CPDELUSER:ENOT_EXISTS,id
If the specified user does not exist

CPDELUSER:EPERMISIONS,id
If you can not delete a user because the administrator password is
incorrect

CPDELUSER:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPDELUSER:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 95 / 106


10.1.3.7. CPSETADMINPASSWORD

Format: CPSETADMINPASSWORD=newPassword

Limitations: This command only works when sent through an encrypted way, you do
not need to know the administrator password (the user id == 0). The
command needs the option “Allow remote user management” to be set
active in the Configurator. Can be executed only by ATS or administrator.

Description Changes the main user password - the system administrator. The
command is designed to give the ability to remotely restore the password
(by monitoring station employees) if it is forgotten. NewPassword is the
new password of the main user. The command returns:
CPSETADMINPASSWORD:EOK

CPSETADMINPASSWORD:ENOT_ALLOWED
If the command is sent via open SMS or the configuration does not allow
remote management of users

CPSETADMINPASSWORD:ELENGTH
If the new password is too short or too long or does not consist of digits

CPSETADMINPASSWORD: EPERMISIONS
If the password can not be changed because it is already used by another
user. If you type the current administrator password, the command
returns EOK.

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 96 / 106


10.1.4. Commands for managing the partitions, zones and outputs

10.1.4.1. CPGETSTATUS

Format: CPGETSTATUS[=password]

Limitations: You must know the administrator or user password. Can be executed by
ATS, administrator or user. If the command comes from ATS and was not
authorized with a code, enter the password
Description password is the system administrator or user password. The command
returns:
CPGETSTATUS:Ready,CurrentPartitionAlarms,alarmHistory,zoneTampers,
keypadTampers,zones,zonesLock,partitions,outputs,batteryVoltage,
powerSupplyVoltage,silentAlarms,zonesComFailures,zonesPowerFailures
Where:
Ready takes the value 1 if the system is ready for arming , 0 if it is not
ready.
CurrentPartitionAlarms is a bit-vector determining whether the current
partitions are in alarm condition. Bit 0 corresponds to the first partition,
bit 1 corresponds to the second partition.
alarmHistory a bit-vector indicating the alarm memory from the last
arming. Bit 1 (counting from 0), corresponding to the zone 1,... bit 7
corresponds to the zone 7, bit 10 is the alarm from the keypad tampering.
zoneTampers is a bit-vector indicating the zone tampering. Bit 1 (counting
from 0) means the zone 1.
keypadTampers is the alarm from the keypads tampering. Bit 0 means the
keypad 1.
zones – means the current status of the zones. It is a bit-vector, where
the bit 1 (counting from 0) means the zone 1, bit 2 means the zone 2,
etc. If the zone is impaired, the bit is set.
zonesLock – means the current status of the zone blockade. It is a bit-
vector, where bit 1 (counting from 0) means the zone 1, bit 2 means the
zone 2, etc. If the zone is blocked, the bit is set.
partitions – means the current status of the partitions. It is a bit-vector,
where bit 0 means the partition 1, the bit 1 the partition 2 (otherwise
than for the zones and outputs where bit 1 means the zone/output 1). If
the partition is armed or counts down, the time to output the
corresponding bit is set.
outputs – means the current status of outputs. It is a bit-vector, where bit
1 (counting from 0) means the output 1, bit 2 means the output 2 and bit
3 means the output 3. If the output is enabled, the bit is set.
batteryVoltage – battery voltage in mV (12000 = 12V). If the battery is
not connected, the readings may be incorrect, and be around 9V (9000)

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 97 / 106


powerSupplyVoltage – AC voltage at AC terminals of CPX200N
(downstream the transformer) in mV (18000 = 18V).
silentAlarms is a bit-vector indicating the quiet alarm memory since the
last arming (arming cancels the alarm memory). Bit 1 (counting from 0),
corresponds to the zone 1, … bit 7 corresponds to the zone 7.
zonesComFailures – is a bit-vector indicating the communication failures
between wireless detectors and control panel. Bit 1 (counting from 0),
corresponds to the zone 1, … bit 16 corresponds to the zone 16.
zonesPowerFailures – is a bit-vector indicating detectors power failures in
wireless detectors (means low battery in wireless detectors). Bit 1
(counting from 0), corresponds to the zone 1, … bit 16 corresponds to the
zone 16.

CPGETSTATUS:EPERMISIONS
If the specified password is incorrect

CPGETSTATUS:ENOT_ALLOWED
If the command was sent via open SMS

CPDELUSER:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 98 / 106


10.1.4.2. CPGETFAILURES

Format: CPGETFAILURES[= password]

Limitations: You must know the administrator or user password. Can be executed
by ATS, administrator or user. If the command comes from ATS and
was not authorized with a code, enter the password

Description password is the system administrator or user password


The command returns:

CPGETFAILURES:outFailures,powerOutFailures,powerInFailures,keyp
adCommFailures,keypadPowerFailures,otherFailures
Where:
outFailures is a bit-vector informing about the failures of outputs. Bit
1 (counting from 0) means the output 1.
powerOutFailures is a bit-vector informing about the failures of
power supply outputs. Bit 0 means the output KPOUT, bit 1 means
the output AUX1, bit 2 means the output AUX2.
powerInFailures is a bit-vector informing about the failures of power
supply. Bit 0 means the supply network failures, bit 1 means the
battery failure.
keypadCommFailures is a bit-vector informing about the failures of
communication with keypads. Bit 0 means the keypad 1.
keypadPowerFailures is a bit-vector informing about the power
supply failures reported by keypads. Bit 0 means the keypad 1.
otherFailures is a bit-vector determining the current system failures.
The meaning of bits is as follows:
bit 0 – loss of clock
bit 1 – configuration memory failure

CPGETFAILURES:EPERMISIONS
If the specified password is incorrect

CPGETFAILURES:ENOT_ALLOWED
If the command was sent via open SMS

CPDELUSER:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 99 / 106


10.1.4.3. CPSETPARTITIONS

Format: CPSETPARTITIONS=partitions[,password]

Limitations: You must know the administrator or user password. Can be executed by
ATS, administrator or user. If the command comes from ATS and was not
authorized with a code, enter the password

Description Arms the specified partitions. partitions a bit-vector indicating which


partition one wants to arm. Bit 0 is the partition 1 , bit 1 is the partition 2.
Bit setting means that one wants to arm the partition. Sending a
command with the partition argument equal to zero, has no sense, since
it does not change anything - if the partitions is 0, the user's password is
not checked and the status returned by the command is equal to EOK.
Password is the code of the user who performs arming. The specified
partitions will be armed from the user’s id to which the code belongs. The
command returns:
CPSETPARTITIONS=partitionList: EOK
If the command is executed. partitionList is the list of partitions which has
been armed (note that partitionList may be different from partitions, if the
user does not have permissions to desired partitions).

CPSETPARTITIONS=partitions,password:EFORMAT
If the data format is incorrect (partitions,password are the command
arguments)

CPSETPARTITIONS=partitions:EPERMISIONS
If the user with the specified password does not exist

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 100 / 106


10.1.4.4. CPUNSETPARTITIONS

Format: CPUNSETPARTITIONS=partitions[,password]

Limitations: You must know the administrator or user password. Can be executed
by ATS, administrator or user. If the command comes from ATS and
was not authorized with a code, enter the password

Description Disarms the specified partitions. Partitions is a bit-vector specifying


which partitions you want to disarm. Bit 0 is the partition 1, bit 1 is
the partition 2. Setting the bit means that one wants to disarm the
partition. Sending a command with the partition argument equal to
zero, has no sense, since it does not change anything - if the
partitions is 0, the user's password is not checked and the status
returned by the command is equal to EOK. Password is the code of
the user, who performs disarming. The specified partitions will be
armed from the user’s id to whome the code belongs. The command
returns:
CPUNSETPARTITIONS=partitionList:EOK
If the command is executed. partitionList is the list of partitions
which has been disarmed (note that partitionList may be different
from partitions, if the user does not have permissions to desired
partitions).

CPUNSETPARTITIONS=partitions,password:EFORMAT
If the data format is incorrect (partitions,password are the command
arguments)

CPUNSETPARTITIONS=partitions:EPERMISIONS
If the user with the specified password does not exist

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 101 / 106


10.1.4.5. CPZONESLOCK

Format: CPZONESLOCK=zones[,password]

Limitations: You must know the administrator or user password. Can be executed by
ATS, administrator or user. If the command comes from ATS and was not
authorized with a code, enter the password

Description Blocks permanently the given zones. It generates the events


INPUTx_LOCK.
zones is a bit-vector indicating the zones, which one wants to block. Bit 1
(counting from 0) means the zone 1. Sending a command with the
argument of zones equal to 0, has no sense, since it does not change
anything. Password is the system administrator or user password, who
has authorizations to the partition containing the blocked zones.
The command returns:
CPZONESLOCK:EOK,zones
If the command is executed

CPZONESLOCK:ENOT_ALLOWED
If the command was sent via open SMS

CPZONESLOCK:EFORMAT
If the format of the sent command is incorrect

CPZONESLOCK:EPERMISIONS
If the user has not authorization to the proper partition

CPZONESLOCK:ENOT_EXISTS
If the user with the specified password does not exist

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 102 / 106


10.1.4.6. CPZONESUNLOCK

Format: CPZONESUNLOCK=zones[,password]

Limitations: You must know the administrator or user password. Can be executed
by ATS, administrator or user. If the command comes from ATS and
was not authorized with a code, enter the password

Description Removes permanent and temporary blockade from the given zones.
It generates the events INPUTx_UNLOCK.
zones is a bit-vector indicating the zones, which one wants to
unblock. Bit 1 (counting from 0) means the zone 1. Sending the
commands with the argument of zones equal to 0, has no sense,
since it does not change anything. Password is the system
admiinistrator or user password.
The command returns:
CPZONESUNLOCK:EOK,zones - if the command is executed

CPZONESUNLOCK:ENOT_ALLOWED
If the command was sent via open SMS

CPZONESUNLOCK:EFORMAT
If the format of the sent command is incorrect

CPZONESUNLOCK:EPERMISIONS
If the user has not authorization to the proper partition

CPZONESUNLOCK:ENOT_EXISTS
If the user with the specified password does not exist

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 103 / 106


10.1.4.7. CPPARTITIONSGETZONES

Format: CPPARTITIONSGETZONES[= password]

Limitations: You must know the administrator or user password. Can be executed by
ATS, administrator or user. If the command comes from ATS and was not
authorized with a code, enter the password

Description password is the system administrator or user password


Returns a list of zones assigned to the partition in the format
CPPARTITIONSGETZONES:P1Zones,P2Zones
Where: P1Zones, P2Zones are the bit-vectors indicating which zones are
assigned to the first and second partition respectively. Bit 1 (counting
from 0) means the zone 1.

CPPARTITIONSGETZONES:EPERMISIONS
If the specified password is incorrect

CPPARTITIONSGETZONES:ENOT_ALLOWED
If the command was sent via open SMS

CPPARTITIONSGETZONES:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 104 / 106


10.1.4.8. CPPARTITIONSGETOUTPUTS

Format: CPPARTITIONSGETOUTPUTS[= password]

Limitations: You must know the administrator or user password. Can be executed by
ATS, administrator or user. If the command comes from ATS and was not
authorized with a code, enter the password

Description password is the system admiinistrator or user password


Returns a list of outputs assigned to the partition in the format
CPPARTITIONSGETOUTPUTS:P1Outputs,P2Outputs
Where P1Outputs,P2OUtputs are the bit-vectors indicating which outputs
are assigned to the first and second partition respectively. Bit 1. (counting
from 0) means the output 1.

CPPARTITIONSGETOUTPUTS:EPERMISIONS
If the specified password is incorrect

CPPARTITIONSGETOUTPUTS:ENOT_ALLOWED
If the command was sent via open SMS

CPPARTITIONSGETOUTPUTS:EFORMAT
If the format of the sent command is incorrect

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 105 / 106


11. CHANGE HISTORY
Date / Version / Firmware Description
19.07.2012 / i0.1 / 0.6.0 First version of the manual
14.09.2012 / i0.2 / 0.7.0 Second version of the manual
16.11.2012 / i0.3 / 0.9.0 Major change in the way of using keypad
Description of how to read and change installer’s service
22.11.2012 / i0.4 / 0.9.0
code remotely
27.11.2012 / i0.5 / 0.9.0 Added service mode
28.11.2012 / i0.6 / 0.9.0 Updated types of input response, power consumption
Added function to program time and date. Added restore
29.11.2012 / i0.7 / 0.10.0
default installer code. Added power supply specification.
19.12.2012 / i0.8 / 0.10.0 Changed translation
15.01.2013 / i0.8d / 0.12.0 Change in arming singalization when fault occurs
Added 24H Burglary silent zone in Service Mode.
25.03.2013 / i0.9 / 0.13.0
Updated “Programmable parameters” section.
Adding a description of the programming keypad address.
Added “Users remote management” section in Service Mode
18.04.2013 / i0.9a / 0.14.0
Updated the description of the “Faults Memory” and “Alarms
Memory”.
Minor fixes description “Control unit functions” and “Alarm
20.05.2013 / i0.9b / 0.14.0
Memory”
11.09.2013 / i0.10a / 0.18.0 Added GSM signal jamming indicator output
Added a 31# function – Other alarms (same as entering
additional options indicated by 8th diode).
24.10.2013 / i0.10b / 0.19.0
Changed “user code” to “administrator code” in the
descriptions of functions used to change time and date.
Added sms handling. Service code changed (0000). Updated
10.01.2014 / i1.0 / 1.0 configurator screen (to version 1.3.29.11). Added the ‘Users’
option.
Added info about remote commands and parameteres
23.01.2014 / i1.1 / 1.0
configurable by sms
04.06.2014 / i1.2 / 1.0rc12 Added chirp functionality
Added “24h fire” zone. Changed CPGETSTATUS,
12.08.2014 / i1.3 / 1.0rc16
CPSETPARTITIONS and CPUNSETPARTITIONS commands.
23.10.2014 / i1.4 / 1.0rc17 Changes in drawings
Added auto-arming/disarming. Added temperature and
08.04.2015 / i1.5 / 1.1.1
humidity range.
26.06.2015 / i1.6 / 1.1.3 ‘Users’ tab description update

CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL 106 / 106

You might also like