Manual TFT8210H Tecnofluid V3.0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Electromagnetic Flow Meter - TVM

Transmitter Operation Manual


(TFT8210-V3.0)
CATALOG

1. Product Function Specification PAGE 3


1.1 Base function
1.2 Working conditions
1.3 Connection type with sensor
1.4 Transmitter outline dimension and type
2. Transmitter Operation And Parameter Setting .PAGE 6
2.1 Keyboard Definition and Display
2.2 Transmitter Menu Structure
2.3 Transmitter Parameter Description
2.4 How to Setup The Parameter
3. Wiring Diagram And Output Define PAGE 16
3.1 Integral Type Wiring Diagram
3.2 Separate Type Wiring Diagram
3.3 Battery Power Flow Transmitter wiring Diagram (3.6V)
3.4 Connection Between Transmitter And Sensor
3.5 Frequency Output Mode
3.6 Pulse Equivalent Output Mode
3.7 Analog Output Mode(4-20Ma)
4. Key Points of Attention PAGE 19
4.1 Installation
4.2 Power On And Preheat
4.3 Set The Instrument Parameters Correctly
4.4 Calibrate The Zero of Flowmeter
4.5 Relationship Between Battery Life And Sensor Size
5.Packing and Storage PAGE 21
6.Appendix .PAGE 21
Appendix 1: Flow Meter Transmitter Mode
Appendix 2: Electromagnetic Flow Meter Mode (TFT8210)
Appendix 3: Outline Dimension (Insert Electromagnetic Flowmeter)
Appendix 4: Outline Dimension (Flange Type Electromagnetic Flowmeter)
Appendix RS485 Communication Address Table

II
1. Product Function Specification
1.1 Base Function
Implementation standards
《JJG-1033-2007 electromagnetic flowmeter》。
Suitable to Size of the Sensor (mm):
1,2,3、6、8,10、15、20、25、32、40、50、65、80、100、125、150、200、250、300、350、400、
450、500、600、650,700、800、900、1000、1100,1200、1300,1400、1500,1600、1700,1800、2000、
2200、2400、2600、2800、3000
Power Supply
Power supply :85VAC --- 265VAC or or 110vac to 420vac or 24vdc or 3.6v lithium battery
The Velocity Range:
0.01 - 15 m / s, velocity resolution: 0.5 mm / sec
Requirement For Sensor And Excitation (AC and DC power supply type)
Excitation current can be set to 125mA、160mA、250mA
250mA excitation current is suitable to the resistance of two coil:35~ 65Ω;
125mA excitation current is suitable to the resistance of two coil: 65 ~ 120Ω
excitation frequency:25HZ;12.5HZ,6.25HZ,3.125HZ
Empty-Pipe Check And Full-Pipe Check
Automatic & continuous measure the condition of liquid and diplay the empty pipe and full pipe message.
do not need the full -pipe calibration and Avoid false alarm
Output Signal (AC and DC power supply type)
Current output: 4 to 20mA,load;resistance:0~750Ω,Base deviation:0.1%±10µA。
Frequency output: Frequency range is 100~5000Hz;Photoelectric isolation, isolation voltage:> 1000VDC;
Pulse equivalent output: user defined pulse width,automatic conversion to square wave at high
requency ;Photoelectric isolation, isolation voltage:> 1000VDC;
Alarm Output
Alarm output contact:H-ALM and L-ALM ; Photoelectric isolation, isolation voltage:> 1000VDC;Output
driver:Maximum withstand voltage 36VDC, maximum load current 30mA.
Communcation
Communication :RS485 (standard)、HART (option)
MODBUS interface:RTU format,Physical interface:RS-485,Electrical isolation:1000V;
HART interface:Support standard HART protocol
Language And LCD Dispaly
English ,With LCD,display flow rate , total flow , velocity etc
three internal accumulator, record positive total flow and reverse total flow and net total
3.6V battery power emf type with backligh 。

3
Nonlinear Correction Function:Multi segment linear correction,suitable to variety of sensors
Automatic Zero Calibration Function
Quick Response, Response time of 0.3 seconds
Electrode Self-Cleaning Function
Protection
with lightning protection circuit design. High efficiency anti interference circuit, suitable for all kinds of harsh .
Grade of Protection: IP65 or IP68
1.2 Working conditions
Ambient temperature:–20~+65℃;Relative humidity:5%~90%;Power: less than 10W (after connecting the
sensor).
1.3 Connection type with sensor
Integral type and Separate type (converter is connected to the junction box of the sensor through the cable )
1.4 Transmitter outline dimension and type
According to the size of the sensor, we offer four kinds of transmitter housing, As shown in the figure below,
please note: the PCBboard, software and menus and functions are be the same, only the size of housing and
shape of the housing is different..
⚫ Integral type(TFT8210HM1)

⚫ Integral type(TFT8210HM2)

4
⚫ Integral type(TFT8210HS)

⚫ Integral type(TFT8210HB)

⚫ Separate type(TFT8210R)

5
2. Transmitter Operation And Parameter Setting
2.1 Keyboard Definition and Display

Figure A

Figure B

Left shift, parameter setting confirmation key and exit sub directory key

fast descending button to go to <factory setup>, digital up key。

move up and down keys

move right, enter the parameter setting and exit key

Press or , you can Switch between figure A and figure B

6
2.2 Transmitter Menu Structure

Main Menu Sub-Menu


FlowRate Setup Flow Rate Setup
Total Flow Setup Demcial
Cacuate Flow Range
Output Setup Sub-Menu low-cutoff
Communcation Setup 4 mA Caculation Low Alarm
Factory Setup 20 mA Caculation High Alarm
Energy Parmeter Zero Point Caculation Damping Time
Sub-Menu Sub-Menu Bid Direction
Excitation Frequency Upper Limit Frequency Actual Direction
Energy Unit Sensor Size Pulse Equivalent
Specific heat Ration k-Factor Pulse Width Sub-Menu
Correction Factor Actual Zero Active Level Total Flow Setup
Clear Total Energy Linear Correction Sub-Menu Demical
Caculate Temperature Density Protocol Clear Total Flow
Empty Pipe Check Baud Rate Preset Positive Total Flow
Lower Limit of Empty-Pipe Check Mode Preset Reverse Total Flow
Upper Limit of Empty-Pipe Device No
Filter Parameter Setup
Language

2.3 Transmitter Parameter Description

⚫ Flow Parameter Setting

option: L/s L/m L/h m3/s m3/m m3/h USG/s USG/m USG/h Kg/s
Kg/m Kg/h t/s t/m t/h
PV Unit
default = m3/h ;define the unit of the flow rate
L (liter), h(hour), t(ton), s(second) , m(minute)

option: 0 1 2 3 ,default = 1
PV Decimal
define the decimal point position of the flow rate.

Float point: 99999999.00-0.00 m3/h ,default = 100.0 m3/h


When the instantaneous flow rate reaches this set value, the output
Flow range current is 20mA,
Change this parameter will affect: current output, high and low flow
alarm, etc。

Float point: 9.90 ~ 0.00 % ,default = 0.0 %


Low flow cut-off
The set value is a percentage.of flow range

7
Float point: 99.00 ~ 0.00 % ,default = 0.0 %
This value is a percentage of flow range. for example, if this value is
setup to ten(10), then Equivalent to ten percent(10%) of flow range. If
Low alarm
the Absolute value of instantaneous flow < (flow range × 10%),then the
reansmitter willl otput the high alarm signal ,the contact of high alarm will
close 。

Float point: 99.00 ~ 1.00 % ,default = 90.0 %


This value is a percentage of flow range. for example, if this value is
setup to ten(10), then Equivalent to ten percent(10%) of flow range. If
High alarm
the Absolute value of instantaneous flow > (flow range × 10%),then the
reansmitter willl otput the high alarm signal ,the contact of high alarm will
close 。

Float point: 30.0 ~0.1 ,default = 0.1


NOTE: for this type transmitter , no need to set damping time, flow
Damping time
measurement is very stable. So you can keep the damptime is default
“0.1”。

Option:bid、reverse、positive ;default = bid


When set to positive, the reverse flowrate will not be displayed (display
Bid flow direction zero);When set to reverse, the forward flow rate will not be displayed
(display zero);When set to Bi-directional,the positive and negative flow
can be displayed。

Actual flow direction Option:reverse、positive;default = positive

⚫ Total Flow Setup:Define the relevant parameters of the total flow。

option: L(liter) m³ USG Kg t(ton) ,default value :m³


Total flow unit
define the total flow unit

option : 0 1 2 3 ,default value : 1


Decimal
define the decimal point bit of the total flow value

option: No Yes ,default value : No


Clear the total flow
Clear total flow
Note: if the "Flow Over!" alarm information, please timely clear or
preset the total flow to avoid affecting measurement.

Float point: 9999999999 ~ 0.00 m³ ,default = the current total flow.


Positive total preset After setting this value, the current total flow will be covered by this set
value.

Float point: 9999999999 ~ 0.00 m³ ,default = the current total flow


Reverse total preset After setting this value, the current total flow will be covered by this set
value.

8
⚫ Caculation:Ajust analog output and zero value of flow meter

Float point: 5.0~3.0 ,default = 0.0


After you go to thie item, please use the Precision current meter to
4mA caculate measure the current output value . if this result is not 4.0mA, then input
the actual value which measure to this position .then The instrument will
automatically complete the calibration operation .

Float point: 21.0 ~19.0 ,default = 0.0


After you go to thie item, please use the Precision current meter to
20mA calculate measure the current output value . if this result is not 20.0mA, then
input the actual value which measure to this position .then The
instrument will automatically complete the calibration operation .

option: No / Yes ,default = No


When the fluid is static in the pipeline and completely filled with the
pipeline, the zero value is equal to the voltage difference between the
two signal electrodes of the electromagnetic flowmeter.
Note: after the implementation of zero calibration, if the zero value
Calculate zero
is high, please check the sensor。
In general, the zero value can not exceed 2mV. If the zero value is
more than 2mv , then the accuaracy of the flow mter is not ok .
If the zero value is high, but the sensor has no quality problem,
you can reduce the excitation frequency to reduce the zero value.

⚫ Pulse Output Setup:setup the parameter of pulse output or frequency output

Floating point: 5000.0 - 100.0 Hz ,default = 2000.0


Output Frequency(Hz)=flow rate(m3/h)÷ Flow range(m3/h)×
Upper frequency limi(Hz)
For example , the flowrate is 100m3/h, and the flow range is 200m3/h ,
Upper frequency limit
and the “upper frequency limit “is set to 2000HZ, then this time , the
output frequency is 1000HZ
Note:
if use the “frequency output”then must set “Pulse equivalent”= 0

Floating point: 9999.0 – 0.0 ,default = 0.0


When the pulse equivalent = 0.0, then output frequency signal
Pulse equivalent When the pulse equivalent > 0.0, the pulse output is determined by
the "pulse equivalent".
The “pulse equivalent” unit is “liter per one pulse”

Floating point: 1000.0 ~ 0.0 ms ,default = 0.0


Pulse width(ms)
When this value is "0", the duty cycle of the output pulse is 1:1

9
option: Low(Active low) High(active high)
default = Low(Active low)
this parameter is related to the "pulse width".
When set to“ Low”, the set value of the pulse width is used as the
Active level
pulse width of the pulse output low level.
When set to “high”, the set value of the pulse width is used as the
pulse width of the pulse output high level.
In general, this parameter does not need to be set.

⚫ Communcation Setup:setup RS485 communcation parameter

option: Modbus-RTU Modbus-ASCII


Communication Protocol
default: Modbus-RTU

option: 1200 2400 4800 9600 19200 38400


Baud Rate default = 19200
Note: Please set the baud rate ≥ 9600

option: 7 8 ,default = 8
Data Bit
Note: if use RTU protocol,prohibit to choose “7”

option: None , Odd , Even


Check Mode
default = Even

Device No data: 247 ~ 1 ,default = 1

⚫ Factory Parameter Setup:

Password 052500 . Setup the key parameters ,

Option: 25HZ, 12.5HZ .6.25HZ . 3.125HZ


Default value = 6.25HZ
If the sensor size is greater than DN500, select 3.125HZ;
If the sensor size is less than DN500, select 6.25HZ;
Excitation Frequency If the inductance of the sensor is very small, you can choose 25HZ
If the zero value is high, but the sensor has no quality problem,
you can reduce the excitation frequency to reduce the zero value.
If the flow rate is not very stable, you can try to reduce the
excitation frequency.

option: 1,2,3、6、8,10、15、20、25、32、40、50、65、80、
100、125、150、200、250、300、350、400、450、500、550、600、
Sensor Size 650,700、800、900、1000、1100,1200、1300,1400、1500,1600、
1700,1800、2000、2200、2400、2600、2800、3000 mm
default value = 50 mm

10
Floating point: 9.9000~0.0100 ,default = 0.1
This parameter is determined when the real flow calibration is carried
out. This parameter is only related to the sensor, which indicates the
characteristic value of the sensor.
k-factor
New Sensor K = the old Sensor K ×〔flowrate of the Calibrated
flowmeter ÷actual flow rate〕
After you finished the test by water , then need setup the final
K-fator at here.

default:0.0 , unit:mv.(votage)
When the fluid is still in the pipeline and completely filled with the
pipeline, the zero value is equal to the voltage difference between the
two electrodes of the electromagnetic flowmeter.
Actual Zero
Note: after the implementation of zero calibration, if the zero value
is high, please check the sensor。
In general, the zero value can not exceed 2mV. If the zero value is
more than 2mv , then the accuaracy of the flow mter is not ok .

the correction range: the default value is 0 ~ 2m/s (refers to the scope
of the role of nonlinear correction value)。
Linear Correction
default value =0.0 mv
修正值=(被校表流量-标准表流量)/标准表流量*当前被校表电压值


Float point: 999999~0.1 kg/m3 default = 1000.0 kg/m3
Density When you need to use the quality unit, set the exact density!
If the unit is Volume unit,then this item have no any affect.

option: enable or prohibit ,default = enable


If you select “prohibit’, then the flowmeter transmitter does not
Empty Pipe Check
carry out empty-pipe detection. then Even if there is no water, it
may be show the flow rate.

Float point,default = 3500


TFT8210 type EMF transmitter can measure the resistance
betweenelectrodes automatically. For three electrode flowmter or
four electrodes flow meter or the flowmeter with ground ring, If the
pipeis fully filled with water, then the resistance value is about the
Lower limit of empty
2200 ,because of the different conductivity of the fluid, this value
pipe (as shown in right
may be somewhat different, and For separate type flow meters, the
picture)
length of the cable also affects this value. In fact, most of the fluid ,
this value is basically between 2000-3300 when the Fluid filled
pipe. And when the pipe is empty (no water), then the value will
become to about 4000 to 4500, So we setup the “Lower limit of
empty-pipe” to 3500. And this is type value.

11
If you setup the “Lower limit of empty-pipe” to 3500, the meaning
is that the flowmeter determines the current state to “empty
pipe(no water in pipe)” when the actual measurement value >3500.
If the actual measurement value <3500, then the flowmeter
determines that the pipe is filled with liquid.
The actual measurement value is appeared in the left of this menu.
Lower limit of empty
In some cases it may be possible to change this setting.
pipe (as shown in right
picture)

Float point,default = 5500


TFT8210 type EMF transmitter can measure the resistance
betweenelectrodes automatically. For two electrode flowmter or
the flow meter which is not well connected to ground, If the pipe
is fully filled with water, then the resistance value maybe >6000
,because of the different conductivity of the fluid, this value may
be somewhat different, and For separate type flow meters, the
lengthof the cable also affects this value. And when the pipe is
Upper limit of empty empty (nowater), then the value will become to about 4000 to
pipe 4500, So we setup the “upper limit of empty-pipe” to 5500. And
this is type value.
If you setup the “upper limit of empty-pipe” to 5500, the meaning
is that the flowmeter determines the current state to “empty
pipe(no water in pipe)” when the actual measurement value <5500.
If the actual measurement value >5500, then the flowmeter
determines that the pipe is filled with liquid.
The actual measurement value is appeared in the left of this menu.
In some cases it may be possible to change this setting.

For all electromagnetic flowmeter, whether it is the two electrode


or three electrode or with ground ring. TFT8210 Transmitter
determines the “empty pipe(no water in pipe )” according to actual
measurement value and “upper limit empty-pipe” and “lower limit
empty-pipe”.
If “lower limit empty-pipe”< = actual value <= “upper limit empty-
pipe”, then the flowmeter determines to “empty pipe(no water in
pipe”.
If actual value < “lower limit empty-pipe” ,then “full-pipe(filled
water)”
If actual value> “upper imit empty-pipe”, then also “full-pipe”

12
Filter time: default =0,option : 0、1、2
Note: In the normal state, the filtering time is “0”, and meet the
requirements of the corresponding time for 0.3 seconds.
If the flowrate is very instable , and the sensor is ok ,and this instability
condition is caused by the fluid, then you can change the ”filter time”
to “1”.
Filter-parameter setup
Filtering threshold:default =1,option: 1、2、3、4、5

⚫ Energy Parameter Setting:Define the relevant parameters of the energy meter, and please
note: this menu will appear when you purchase the energy meter.

option: GJ/H , Kc/H , KW


Energy unit
default: GJ/H

Heat capacity ratio Float point:0.000 - 10.0 ,default = 4.2

Correction factor Default = 1.0

option: No Yes ,default = No


Clear total energy
if select the “yes”, then clear the total energy value to zero

The temperature measuring circuit of the converter is calibrated by using


Calculate temperature
high precision precision resistance box.

2.4 How to Setup The Parameter

Figure 1: flow rate display interface

press to parameter setup menu,As shown in Figure 2:

13
Flow Rate Setup
Total Flow Setup
Caculation
Output Setup
Communcation

Figure 2

After the interface is shown in Figure 2,press or then you can choose different set items。

Press then return to the flow display interface(figure 1);

Press or move the cursor to the sub menu,press go to sub menu to setup the parameter,

for example , we need setup the “flowrate parameter”,when this item become light,pree , then will display
the menu as shown in figure 3 :

Flow Rate Unit


Demcial
Flow Range
Low Flow Cut-off
Low Alarm

Figure 3

Press or to select the item which you want to modify,The selected item will brighten,if need return

to the menu as shown in figure 2,then press ;If you need to enter the next level of items,then press
to setup the parameters as shown in figure 4:

Figure 4

In this case , press or to modify the parameter,for example, as shown in figure 4, you need

change the flowrate unit from " m³/h ” to " m³/m ”,then press ,the flowrate unit will become to “ m³/m ”,
as shown in figure 5:

14
Figure 5

After you modify the parameter , if you need save,then press ,The system will prompt the "confirmation"
and "exit" option, as shown in Figure 6:

图6

In this case,press ,then save the setup and back(as shown in figure 3);if do not need save the

parameter,then press to back(as shown in figure 3)。

15
3. Wiring Diagram And Output Define
3.1 Integral Type Wiring Diagram (AC and DC Power Supply Type)

Pulse or requency
meter Power
supply

Current
meter

Note:
The driving ability of high alarm
and low alarm is 24VDC/30mA,
24vdc power
and can drive more than 800 ohm
impedance relays, valves and
alarm lights, etc。

24vdc power

The meaning of each terminal is as follows


Identification Function Remarks
L AC 85 - 265V L : AC220V power supply (fire line)
N AC 85 - 265V N : AC220V power supply (Zero line)
24V DC 18 - 36V + Power supply 24V+
COM DC 18~36v - Power supply 24V-
+ 4~20Ma + The load resistance is less than or equal
4-20mA
- 4~20mA - to 500.ohm
+ Frequency & pulse output +
Pulse
- Frequency & pulse output -
+ RS485 +
RS485 RS485 output
- RS485 -
+ High alarm output +
Alarm H
- High alarm output - Suggest use 24VDC intermediate relay,
+ Low alarm output + Load current ≤ 30mA
Alarm L
- low alarm output -

16
3.2 Separate Type Wiring Diagram (AC and DC Power Supply Type)

thermal resistance

Sensor Coil Electrode


of sensor

Identification Funcation Remarks


L AC 85~265V L: AC 86-220V fire line
PE
N AC 85~265V N : AC 86-220V zero line
24V DC 16~36V + 24VDC+ power supply
com DC 16~36V - 24VDC- power supply
I+ 4~20mA output The load resistance is less than or
I- 4~20mAoutput equal to 500.ohm
F+ Frequency&pulse output +
F- Frequency&pulse output -
RS+ RS485 +
RS485 output terminal
RS- RS485 -
TH + Connect to inlet temperature sensor
Pt100 or Pt1000
TH -
TL+
Pt100 or Pt1000 Connect to outlet temperature senssor
TL -
coil1 (X)
connecting to excitation coil of sensor。
coil2 (Y)
SIGA electrode A Connect to signal electrode A
GND Signal ground Connect to the grounding electrode
SIGB electrode B Connect to Signal electrode B

17
3.3 Battery Power Flow Transmitter wiring Diagram (3.6V lithium battery)

3.6V Battery Power


Main Board

3.4 Connection Between Transmitter And Sensor

Connect to coil of sensor

Connect to coil of sensor

two core line (connect to the coil of sensor, three core wire with shield connection to the electrode of sensor .

3.5 Frequency Output Mode:


Frequency output range is 0 to 5000HZ, the frequency output corresponds to the percentage of flowrate.

Flow Rate
F= Upper Frequency Limit
Flow Range
Frequency output mode is generally used to control the occasion, because it reflects the percentage of traffic,
if the user is used for measurement occasions, it should choose the pulse output mode。
The frequency output is provided with an internal 24VDC power supply and NPN way。
If you need use the frequency output mode , then three parameters must setup:
⚫ Setup “upper frequency limit”
⚫ Setup “flow range” (corresponding to upper frequency limit)
⚫ Setup “Pulse equivalent value” = 0

3.6 Pulse Equivalent Output Mode:


Pulse equivalent value:0.001L,0.01L,0.1L,1L,0.001 M3 。The user should pay attention to the matching
of the flow range and the pulse equivalent when selecting the pulse equivalent。If the flowrate is too large and the

18
pulse equivalent selection is too small, it will cause the upper limit of the pulse output, so the pulse output
frequency should be limited to the following 3000Hz. If the flowrate is small and the pulse equivalent is too large, it
will cause the meter to output a pulse for a long time。In addition, it must be explained that the pulse output is
different with the frequency output, the pulse output is a pulse equivalent to output a pulse, therefore, the pulse
output is not very uniform. The general measurement of the pulse should use the counter meter, not choose the
frequency meter。
The pulse output is provided with an internal 24VDC power supply and NPN way。

3.7 Analog Output Mode(4-20Ma)


The current output corresponds to the percentage of instantaneous flow。The current output is provided with

an internal 24VDC power supply.。

Flow Rate
I0 = 16 + 4.0
Flow Range
For 4 ~ 20mA signal system, the current zero is 4mA. Therefore, in order to improve the resolution of the
output analog current, the flow range of the flowmeter should be selected properly.
3.6V battery power EMF type have no 4 to 20 Ma signal output .

4. Key Points of Attention


4.1 Installation
The flow meter is installed correctly on the pipe to ensure the straight pipe section and the installation position
and the grounding to meet the requirements,as shown in the following figure:

straight length:5×D straight length:3×D

Grounding resistance
less than 10 ohm
Inet

19
20
4.2 Power On And Preheat

The flow meter need to be warm up for at least 15 minutes after power on .

4.3 Set The Instrument Parameters Correctly


Go to <factory setup>, setup the Reduced excitation frequency and size and another parameters
Go to <flowrate parameter setup>, setup the flowrate and another parameters
If use frequency output ,then go to <output parameter setup>, set the “up frequency “
If use Pulse equivalent output , then go to <output parameter setup>, set the Pulse equivalent.

4.4 Calibrate The Zero of Flowmeter


The zero calibration of flowmeter is very important for Instrument accuracy. Make sure that the pipe is filled with
fluid and is in a static state and grounding , by using the automatic test function of the converter, the zero point of
the instrument is obtained. Please note: the actual zero value must less 2mv , if the actual zero value is more than
2mv, maybe the accuracy will be affected.If the actual zero value is more than 2 mv, you must check the following
item:
⚫ the sensor maybe not ok;
⚫ the grounding resistance maybe is not meet the requirement.
⚫ Reduced excitation frequency and calculate the zero again .

4.5 Relationship Between Battery Life And Sensor Size

Battery Life
Battery Type
Size ≤DN150 DN200≤Size ≤DN350 DN400≤Size ≤DN600
Internal Battery 33 months 30 months 26 months
External Battery 72 months 72 months 72 months

If your sensor size is big ,and need long battery life , then need install external battery..and different size , the
external battery capacity is different. If the size is greater than DN600, then the internal battery life is short than 26
months , so suggest use external battery .if you need install external battery , then ask usd , we can provide the
battery parameters and Installation method.

5.Packing and Storage


TFT8210 seial flow meter transmitter is packed in a special foam box to prevent damage during
transportation,Random files include: operation manual, certificate, packing list, etc. In order to prevent the
instrument from being damaged during transport, please keep the packing status of the manufacturing plant before
it arrives at the installation site。Storage sites should possess the following conditions: placed in the interior and
rainproof and moisture-proof and small mechanical vibration。

21
6.Appendix
Appendix 1: Flow Meter Transmitter Mode

TFT821 Electromagnetic Flowmeter Transmitter


0
H Integral type
R Separate(Remote) type, with Wall mounted shell

P Only PCB
S Integral type, with 1608 shell
M1 Integral type, with 84mm-Abb shell
M2 Integral type, with 97mm-Abb shell
B Integral type, with big -size shell

1 3.6v battery
2 24vdc power supply
3 86vac to 265vac power supply
4 100vac to 420 vac power supply

R RS485 communcation
H HART communcation

1 Suitable to 30~65 ohm (Total resistance of two coil)


2 Suitable to 70~120 ohm (Total resistance of two coil)

22
Appendix 2: Electromagnetic Flow Meter Mode (TFT8210)

TFT821 Electromagnetic Flowmeter Transmitter


0
H Integral type
R Separate(Remote) type, with Wall mounted shell
S Integral type, with 1608 shell
M1 Integral type, with 84mm-Abb shell
M2 Integral type, with 97mm-Abb shell
B Integral type, with big -size shell
1 3.6v battery
2 24vdc power supply
3 86vac to 265vac power supply
4 100vac to 420 vac power supply
R RS485 communcation
H HART communcation
P PTFE Lining
R Rubber Lining
F FEP Lining
0 SS316L electrode
1 Hastelloy B electrode
2 Hastelloy C electrode
3 Titanium electrode
4 Tantalum electrode
5 Platinum electrode
0 PN1.0 mPa
1 PN16 mPa
2 PN25 mPa
3 PN40 mPa
4 PN63 mPa
5 JIS 10K
6 JIS 20K
7 ANSI Class 150
8 ANSI Class 300
9 ANSI Class 600
0 IP65
1 IP68
A Accuracy 0.25%
B Accuracy 0.5%

23
Appendix 3: Outline Dimension (Insert Electromagnetic Flowmeter)

Appendix 4: Outline Dimension (Flange Type Electromagnetic Flowmeter)

24
Appendix "RS485 Communication Address Table

Appendix 5: Instrument variable address definition


The following is a list of data variables that are supported by the instrument, the data are HEX type
Register
Register Read write
Variable name start
length instruction command
address
Coil Type
Clear total flow 0091 *** *** 05
Int Type
Flow rate unit 0000 0001 03 06
Flow rate decimal 0008 0001 03 06
Total unit 0010 0001 03 06
Total flow decimal 0018 0001 03 06
Pulse level 0050 0001 03 06
Device No 0078 0001 03 06
Modbus mode 0058 0001 03 ***
baud rate 0060 0001 03 ***
Date bit 0068 0001 03 ***
Check mode 0070 0001 03 ***
Long type
Total flow extend 0500 0002 03 ***
Total flow 0502 0002 03 ***
Float Type
Damping time 0020 0002 03 10
Low cut-off 0030 0002 03 10
Upper frequency limit 0038 0002 03 10
Pulse equivalent 0040 0002 03 10
pulse width 0048 0002 03 10
Low alarm 00C0 0002 03 10
High alarm 00D0 0002 03 10
density 0098 0002 03 10
Flow rate 0708 0002 03 ***
Total flow 0504 0002 03 ***
Double Type
Flow range 0028 0004 03 10
Sensor k-factor 0088 0004 03 10
Total flow 0090 0004 03 ***
Flow rate 0700 0004 03 ***

Note:
⚫ The start address data is 16 binary , if need 10 binary , then need convert.
⚫ The data bit is 32 bit.
⚫ If connect to PLC ,maybe the start address will add “1” , for example , if the start address is 0708 ,
then will becom 0709 ( for PLC)

25
Appendix 6: Fault Code
0x01 Invalid instruction code
0x02 Invalid register address
0x30 Parameter over limit
0x31 Super lower limit of parameters
0x32 Parameter selection error
0x40 Invalid register length
The register does not support the current
0x41
instruction code
0x42 Register not specified
0x43 Instantaneous flow unit does not exist
0x44 Total unit does not exist
0x45 Maximum frequency output over limit
0x46 Minimum frequency output
0x47 Maximum flow rate over the upper limit
0x48 Duty cycle over limit
0xFE Data frame confusion
0xFF Data frame check error

Appendix 7: Definition of Common Units


m3/h 0
m3/m 1
m3/s 2
L/h 3
L/m 4
L/s 5
USG/h 6
Flow rate USG/m 7
USG/s 8
kg/h 9
kg/m 10
kg/s 11
t/h 12
t/m 13
t/s 14
L 0
m3 1
Total flow USG 2
kg 3
t 4

26
Appendix 8: Symbolic Code Definition
RTU 0
Modbus mode
ASCII 1
Even check 0
Check mode Parity check 1
No parity 2
1200bps 0
2400bps 1
4800bps 2
Baud rate
9600bps 3
19200bps 4
38400bps 5
7 bit 0
Data bit
8 bit 1
小数点后0位 0
小数点后1位 1
Decimal
小数点后2位 2
小数点后3位 3

Appendix 9:Size Code Definition


Size Code Size Code

DN1 0 DN600 27

DN1.5 1 DN700 28

DN2 2 DN750 29

DN3 3 DN800 30

DN4 4 DN900 31

DN5 5 DN1000 32

DN6 6 DN1100 33

DN8 7 DN1200 34

DN10 8 DN1300 35

DN15 9 DN1350 36

DN20 10 DN1400 37

DN25 11 DN1500 38

DN32 12 DN1600 39

DN40 13 DN1700 40

DN50 14 DN1800 41

DN65 15 DN2000 42

DN80 16 DN2100 43

27
DN100 17 DN2200 44

DN125 18 DN2300 45

DN150 19 DN2400 46

DN200 20 DN2500 47

DN250 21 DN2600 48

DN300 22 DN2700 49

DN350 23 DN2800 50

DN400 24 DN2900 51

DN450 25 DN3000 52

DN500 26

28