DT-96E / DT-72E ENG

TEMPERATURE CONTROLLER
General Specifications
µP based, digital temperature controller with a single output
Sensor: T/C, Fe-Const, J Type
ON-OFF Control form
Adjustable Hysteresis Value
Adjustable Upper Limit for SET Value
Displays SET and Process Values
Cold-junction compensation for T/C
Excellent linearity with oC/mV look up table
High accuracy
EEPROM memory to store settings
Dimensions: for DT-96E 96x96mm, for DT-72E 72x72mm
Easy connection with plug-in connectors

Technical Specifications
Panel Hole Sizes : for DT-96E 90x90mm, for DT-72E 70x70mm
Display : 1x3 Digit 7 Segment display
Measuring Scale : 0 oC....600 oC
SET Invertal : o o
0 C....600 C (limited with Up.L value)
Hysteresis Interval : 0 oC....50 oC
Sensor : Fe-Const, J type T/C
Resolution : ±1 oC
Accuracy : ± %0.3 (Over full scale)
Control Form : ON-OFF
Out : Relay (NO + NC), 250VAC, 2A, Resistive Load
Supply Voltage : 100....240VAC, 50/60 Hz
Power Cons. : < 6VA
Line Comp. : 0 oC....50 oC
Operating Temp. : o
-20 C....55 C
o

Altitude : < 2000m


Failure : Out is OFF in case of sensor failure, measurement out of range or hardware fails
to measure input signal.

Error Message
or : Displays “or” message in case of sensor failure, measurement out of range or
hardware fails to measure input signal

! Warning:
Use shielded and twisted signal cables and connect shield to ground on device side. Use correct compensation cables for
T/C sensors. Correct T/C cable directly to the device connectors. Keep all signal cables away from circuit breakers,
devices/cables emitting electrical noise and power cables.
Take precauitons against environmental conditions like humidity, vibration, pollution and high/low temperature during
installation.
Use a fuse (slow 250mA 250VAC) on supply input of the device. Use appropriate cables for supply connections. Apply safety
regulations during installation.

1 MADE IN TURKEY
Connection (for DT-96E):

N
L1
L2
L3

2A

Temperature Controller
DT-96E
Resistance
3 100 .. 240 VAC
!
50/60Hz 6VA
4
5 no 17

+
+
6 Out 18
T/C
nc
7 - 19
-
Fe Const
J Type

Out:
250VAC
max. 2A
resistive load

Connection (for DT-72E):

N
L1
L2
L3

2A

Temperature
Controller
DT-72E
Resistance
3 100 .. 240 VAC 13
+

50/60Hz 6VA
4 14
T/C
5 no - 15
Fe Const
-
6 Out J Type
7 nc

Out: !
250VAC
max. 2A
resistive load

2
Dimensions (for DT-96E) :
10mm 15mm
96mm 66mm

96mm

Dimensions (for DT-72E) :


6mm
15mm
72mm 74mm
72mm

Reading SET Value:

Press one of the


buttons. or
(UP or DOWN)

Read Read “Set” code and SET value in a


SET cyclic manner. Wait for 2 seconds without
Value pressing any button. Display automatically
switches to measured temperature reading.

Wait for 2 sec.

Back to measured
temperature
reading

3
Adjusting SET Value:

Press one of the


buttons. or
(UP or DOWN)

Read “Set” code and SET value in a


Enter cyclic manner. Enter new SET Value by usig
SET 0.....600 oC up and/or down buttons. Wait for 2 seconds without
Value pressing any button. New SET value is
entered automatically.

Wait for 2 sec.

New SET Value


entered

Adjusting Hysteresis and Upper Limit Values


Press UP and DOWN
buttons at the same
time during Power ON +
Read and select hysteresis value.
Enter
Wait for 5 seconds without pressing
Hys 0.....50 oC
any button. New hysteresis value
Value
is saved to EEPROM.

Wait for 5 sec.

Read and select Upper Limit Value


for SET Value.
Enter
Wait for 5 seconds without pressing
Up.L 0.....600 oC
any button. New Upper Limit Value
Value
is saved to EEPROM.

Wait for 5 sec.

New
Values
Entered

OUT; Control Form (ON-OFF):

OUT
ON
OUT relay is OFF when process value (PV)
is greater then or equal to SET value.
OUT relay is ON when PV is less then or equal
to (SET-Hys) value.

PV
(SET-Hys) SET