TLK48 I
TLK48 I
TLK 48 1
1.1
1.2
2
2.1
INSTRUMENT DESCRIPTION
GENERAL DESCRIPTION
FRONT PANEL DESCRIPTION
PROGRAMMING
FAST PROGRAMMING OF SET POINT
2.2 SELECTION OF CONTROL STATE AND PARAMETER
PROGRAMMING
MICROPROCESSOR-BASED 2.3
2.4
PARAMETER PROGRAMMING LEVELS
CONTROL STATES
DIGITAL 2.5
3
ACTIVE SET POINT SELECTION
INFORMATION ON INSTALLATION AND USE
2 - PROGRAMMING
2.1 - FAST PROGRAMMING OF THE SET POINT To enter the menu “ConF” select the option “ConF”, press the key
This procedure permits rapid programming of the active Set Point“P” and the display will show “0”.
and possibly the alarm thresholds (see par 2.3) At this request, enter, using keys “UP” and “DOWN”, the number
reported on the last page of this manual and push key “P”.
Push key “P”, then release it and the display will visualise “SP n”
If an incorrect password is entered, the instrument exit from
(where n is the number of the Set Point active at that moment)
programming mode.
alternatively to the programmed value.
If the password is correct, the display will visualise the code
To modify the value, press “UP” key to increase it or the “DOWN”
key to decrease it. identifying the first group of parameters (“ ]SP “) and with keys “UP”
These keys change the value one digit at a time but if they are and “DOWN” it will be possible to select the desired group of
pressed for more than one second, the value increases or parameters.
Once the desired group of parameters has been selected, the code
decreases rapidly and, after two seconds in the same condition, the
identifying the first parameter of the selected group will be
changing speed increases in order to allow the desired value to be
reached rapidly. visualised by pushing the “P” key.
Once the desired value has been reached, by pushing key P it is Again using the “UP” and “DOWN” keys, it is possible to select the
desired parameter and, if the key “P” is pressed, the display will
possible to exit by the fast programming mode or it is possible to
visualise the alarm thresholds (see par. 2.3). alternatively show the parameter’s code and its programming value,
To exit the fast Set programming it is necessary to push key P, which can be modified by using the “UP” or “DOWN” keys.
Once the desired value has been programmed, push key “P” once
after the visualisation of the last Set Point, or alternatively, if no key
more: the new value will be memorised and the display will show
is pressed for approx. 15 seconds, the display will return to normal
functioning automatically. only the code of the selected parameter.
By using the “UP” or “DOWN” keys, it is then possible to select a
new parameter (if present) and modify it as described above.
2.2 - SELECTION OF THE CONTROL STATE AND PARAMETER To select another group of parameters, keep the “UP” or “DOWN”
PROGRAMMING key pressed for approx. 2 sec., afterwards the display will return to
By pushing key "P" and holding it down for approx. 2 sec. it is visualise the code of the group of parameters.
possible to enter into the main selection menu.
made in the group referring to the alarm to the alarm (“]AL1”, “]AL2”, (cooling) off off
]
“ AL3”).
If 2.rEG output is used to control compressor is possible to use the
“Compressor Protection” function that has the meaning to avoid
4.3 - ON/OFF CONTROL (1.rEG) compressor “short cycles”.
All the parameters referring to the ON/OFF control are contained in This function allows a control by time on the output 2.rEG
]
the group “ rEG”. activation, independently by the temperature control request.
This type of control can be obtained by programming par."Cont" = The protection is a “delayed after deactivation” type.
On.FS or = On.FA and works on the output programmed as 1.rEG, This protection permits to avoid the output activation for a time
depending on the measure, on the active Set Point “SP”, on the programmable on par. “CPdt” (expressed in sec.); the output
functioning mode "Func” and on the hysteresis "HSEt". activation will occurs only after the elapsing of time “CPdt”.
The instrument carries out an ON/OFF control with symmetric The time programmed on parameter “CPdt” is counted starting from
hysteresis if “Cont" = On.FS or with asymmetrical hysteresis if the last output deactivation.
“Cont” = On.FA. Obviously, whether during the time delay caused by the
PV PV
compressor protection function, the regulator request should stop,
SP
H S Et
the output activation foreseen after time “CPdt” would be erased.
SP
H SE t
The function is not active programming “CPdt” =OFF.
tim e tim e The led relative to 2.rEG output blinks during the phases of output
O UT
ON ON ON
OUT
ON ON ON activation delay, caused by “Compressor Protection” function.
1 .rE G o ff o ff 1 .rE G o ff o ff
If it is desired an automatic cycle from the power on instead it is Note: In all the examples that follow is made reference to the alarm
necessary to program the par. "nSP" = 2, to program the two Set AL1. Naturally the operation of the other alarms results analogous.
Point values "SP1" and "SP2" and naturally to program the par.
"SLor", "dur.t" and "SLoF" with the desired values. Have now access at the group “]AL1”, and program on par.
“OAL1” , to which output the alarm signal has to be sent.
In this case at the end of the cycle all the ramps won't be more
active. The alarm functioning is instead defined by parameters :
"AL1t " - ALARM TYPE
PV "Ab1" - ALARM CONFIGURATION
[U n it] “AL1” - ALARM THRESHOLD
d u r .t
SP1 “AL1L” - LOW ALARM THRESHOLD (for band alarm) OR
SLoF
SLor MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high
SP2
alarm)
“AL1H” - HIGH ALARM THRESHOLD (for band alarm) OR
AUTO
MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high
t im e [ m in .]
change
S et
alarm)
Examples with starts from values lower than SP and with “HAL1” - ALARM HYSTERESIS
decreasing of SP. “AL1d” - ALARM ACTIVATION DELAY (in sec.)
PV PV
tim e
AL1 O N O N
HAL1 +0
HAL1 o ff o ff
AL1 Ab1 O N
+1 o ff o ff
ON ON time ON ON time
OUT OUT exemple with absolute low alarm
AL1 off off off AL1 off off off
ALARM DELAY: the alarm output may behave in two different
LoAb HiAb ways depending on the value added to par. “Ab1”.
LodE = DEVIATION LOW ALARM: The alarm is activated when the +0 = ALARM NOT DELAYED: The alarm is immediately activated
process value goes below the value [SP + AL1] and will be when the alarm condition occurs.
deactivated when it goes above the value [SP + AL1 + HAL1]. +2 = ALARM DELAYED: When the alarm condition occurs, delay
With this mode is possible to program the minimum and the counting begins, as programmed on par. “AL1d” (expressed in
maximum set of “AL1” by “AL1L” and “AL1H” parameters. sec.) and the alarm will be activated only after the elapsing of that
HidE = DEVIATION HIGH ALARM: The alarm is activated when the time.
process value goes above the value [SP + AL1] and will be ALARM LATCH: : the alarm output may behave in two different
ways depending on the value added to par. “Ab1”.
deactivated when it goes below the value [SP + AL1 - HAL1].
With this mode is possible to program the minimum and the + 0 = ALARM NOT LATCHED: The alarm remains active in alarm
conditions only.
maximum set of “AL1” by “AL1L” and “AL1H” parameters.
+ 4 = ALARM LATCHED: The alarm is active in alarm conditions
PV PV and remains active even when these conditions no longer exist,
until the correctly programmed key “U”, (“USrb”=Aac) has been
SP
HAL1
pushed.
AL1 P V
-AL1
HAL1 SP
AL1
ON ON ON ON
OUT time OUT time
tim e
AL1 off off off AL1 off off off O N
+0 o ff o ff
LodE HidE A b1 O N
LHAb = ABSOLUTE BAND ALARM: The alarm is activated when
+4 o ff
the process value goes under the alarm threshold set on parameter
"AL1L" or goes higher than the alarm threshold set on parameter exemple with absolute high alarm
"AL1H" and will be deactivated when it goes below the value [AL1H
- HAL1] or when it goes above the value [AL1L + HAL1]. ALARM AKNOWLEDGEMENT: : the alarm output may behave in
LHdE = DEVIATION BAND ALARM: The alarm is activated when two different ways depending on the value added to par. “Ab1”.
the process value goes below the value [SP + AL1L] or goes above + 0 = ALARM NOT AKNOWLEDGED: The alarm always remains
than the value [SP + AL1H] and will be deactivated when it goes active in alarm conditions.
below the value [SP + AL1H - HAL1] or when it goes above the + 8 = ALARM AKNOWLEDGED: The alarm is active in alarm
value [SP + AL1L + HAL1]. conditions and can be deactivated by key “U” if properly
PV PV programmed (“USrb”=ASi), and also if alarm conditions still exist.
AL1H ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION
HAL1 HAL1
AL1H ALARMS ONLY): the alarm output may behave in two different
SP ways, depending on the value added to par. “Ab1”.
HAL1 - AL1L HAL1
AL1L +0 = NORMAL BEHAVIOUR: The alarm is always activated when
there are alarm conditions.
+16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,
OUT ON ON time
OUT ON ON time when Set Point change, the instrument is in alarm condition, the
AL1 AL1 alarm is not activated. It will be activated only when the process
off off off off off off
value is in non-alarm conditions and then back in alarm conditions.
LHAb LHdE
45
7 - TECHNICAL DATA
min. 15 mm
Power supply: 24 VAC/VDC, 100... 240 VAC +/- 10%
Frequency AC: 50/60 Hz
Power consumption: 5 VA approx.
Input/s: 1 input for temperature probes: tc J,K,S ; infrared sensors
TECNOLOGIC IRS J e K; RTD Pt 100 IEC; PTC KTY 81-121 (990 RECOMMENDED
4..20 mA
44.5
48
SET
TLK48 a b c d e ff g
a : POWER SUPPLY
L = 24 VAC/VDC
H = 100... 240 VAC
b : INPUT
C = thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100)
E = thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC)
I = normalized signals 0/4..20 mA
V = normalized signals 0..1 V, 0/1..5 V, 0/2..10 V.
c : OUTPUT OUT1
R = Relay
O = VDC for SSR
d : OUTPUT OUT2
R = Relay
O = VDC for SSR
- = None
e : OUTPUT OUT3
R = Relay
O = VDC for SSR
- = None
g: SPECIAL VERSIONS