IET Control Engineering Series 50

Programming Industrial Control Programming

Systems Using IEC 1131-3


Programming Industrial Control
Systems Using IEC 1131-3
Revised Edition
Industrial Control
IEC 1131-3 is the international standard for the design of software for industrial control
systems. It defines a set of related graphical and textual languages that bring significant
benefits throughout the control system life-cycle – benefits for system integrators, control
system engineers and end-users alike. The standard marks the beginning for well-
Robert Lewis is the UK
expert on two IEC working
groups defining the PLC
programming language
Systems Using
IEC 1131-3
standard (IEC 1131-3) and
structured, re-usable and maintainable software for industrial control systems.
developing a new standard
This new edition has been revised and updated to include all IEC proposed amendments for specifying reusable
and corrections for the planned 1999 edition of IEC 1131-3, agreed by the IEC working software function blocks
group in spring 1998. The book now includes IEC 1131-3 ‘frequently asked questions’ and for distributed industrial
a summary of future developments influencing the next generation of PLC languages, and manufacturing systems

Revised Edition
(IEC 1499). He is a
plus an overview of IEC 1499 standard on function blocks.
Fellow of the IET and has
Although primarily for programmable logic controllers (PLCs), IEC 1131-3 concepts will also been concerned with the
influence the design of software for fieldbus devices. development of control
systems for a wide range of
This book introduces all the concepts of the IEC 1131-3 standard and provides examples industrial applications for over
of the languages related typical industrial control problems. It will be of interest to 15 years. One of his particular
everyone involved in specifying or developing software for industrial or manufacturing interests is the application
applications. The text will also be of value to students and engineers with a general of graphical programming
interest in new techniques for industrial or manufacturing applications. The text will also techniques to the design of
be of value to students and engineers with a general interest in new techniques for industrial control software.
industrial control systems.

R.W. Lewis
Lewis

The Institution of Engineering and Technology


www.theiet.org
0 85296 950 3
978-0-85296-950-2

CE050 HB cover.indd 1 15/08/2007 10:23:08


IET control engineering series 50
Series Editors: Professor D.P. Atherton
Professor G.W. Irwin

Programming
Industrial Control
Systems Using
IEC 1131-3
Revised Edition

CE050 i_iii picas.indd 1 15/08/2007 10:24:41


Other volumes in this series:
Volume 2 Elevator traffic analysis, design and control, 2nd edition G.C. Barney and
S.M. dos Santos
Volume 8 A history of control engineering, 1800–1930 S. Bennett
Volume 14 Optimal relay and saturating control system synthesis E.P. Ryan
Volume 18 Applied control theory, 2nd edition J.R. Leigh
Volume 20 Design of modern control systems D.J. Bell, P.A. Cook and N. Munro (Editors)
Volume 28 Robots and automated manufacture J. Billingsley (Editor)
Volume 30 Electromagnetic suspension: dynamics and control P.K. Sinha
Volume 32 Multivariable control for industrial applications J. O’Reilly (Editor)
Volume 33 Temperature measurement and control J.R. Leigh
Volume 34 Singular perturbation methodology in control systems D.S. Naidu
Volume 35 Implementation of self-tuning controllers K. Warwick (Editor)
Volume 37 Industrial digital control systems, 2nd edition K. Warwick and D. Rees (Editors)
Volume 38 Parallel processing in control P.J. Fleming (Editor)
Volume 39 Continuous time controller design R. Balasubramanian
Volume 40 Deterministic control of uncertain systems A.S.I. Zinober (Editor)
Volume 41 Computer control of real-time processes S. Bennett and G.S. Virk (Editors)
Volume 42 Digital signal processing: principles, devices and applications N.B. Jones
and J.D.McK. Watson (Editors)
Volume 43 Trends in information technology D.A. Linkens and R.I. Nicolson (Editors)
Volume 44 Knowledge-based systems for industrial control J. McGhee, M.J. Grimble and
A. Mowforth (Editors)
Volume 47 A history of control engineering, 1930–1956 S. Bennett
Volume 49 Polynomial methods in optimal control and filtering K.J. Hunt (Editor)
Volume 50 Programming industrial control systems using IEC 1131-3 R.W. Lewis
Volume 51 Advanced robotics and intelligent machines J.O. Gray and D.G. Caldwell
(Editors)
Volume 52 Adaptive prediction and predictive control P.P. Kanjilal
Volume 53 Neural network applications in control G.W. Irwin, K. Warwick and K.J. Hunt
(Editors)
Volume 54 Control engineering solutions: a practical approach P. Albertos, R. Strietzel
and N. Mort (Editors)
Volume 55 Genetic algorithms in engineering systems A.M.S. Zalzala and P.J. Fleming
(Editors)
Volume 56 Symbolic methods in control system analysis and design N. Munro (Editor)
Volume 57 Flight control systems R.W. Pratt (Editor)
Volume 58 Power-plant control and instrumentation D. Lindsley
Volume 59 Modelling control systems using IEC 61499 R. Lewis
Volume 60 People in control: human factors in control room design J. Noyes and
M. Bransby (Editors)
Volume 61 Nonlinear predictive control: theory and practice B. Kouvaritakis and
M. Cannon (Editors)
Volume 62 Active sound and vibration control M.O. Tokhi and S.M. Veres
Volume 63 Stepping motors: a guide to theory and practice, 4th edition P.P. Acarnley
Volume 64 Control theory, 2nd edition J. R. Leigh
Volume 65 Modelling and parameter estimation of dynamic systems J.R. Raol, G. Girija
and J. Singh
Volume 66 Variable structure systems: from principles to implementation
A. Sabanovic, L. Fridman and S. Spurgeon (Editors)
Volume 67 Motion vision: design of compact motion sensing solution for autonomous
systems J. Kolodko and L. Vlacic
Volume 69 Unmanned marine vehicles G. Roberts and R. Sutton (Editors)
Volume 70 Intelligent control systems using computational intelligence techniques
A. Ruano (Editor)

CE050 ii_iv picas.indd 1 15/08/2007 10:25:34


Programming
Industrial Control
Systems Using
IEC 1131-3
Revised Edition

R.W. Lewis

The Institution of Engineering and Technology

CE050 i_iii picas.indd 2 15/08/2007 10:24:42


Published by The Institution of Engineering and Technology, London, United Kingdom
First edition © 1998 The Institution of Electrical Engineers
Reprint with new cover © 2007 The Institution of Engineering and Technology
First published 1998
Reprinted 2007

This publication is copyright under the Berne Convention and the Universal Copyright
Convention. All rights reserved. Apart from any fair dealing for the purposes of research
or private study, or criticism or review, as permitted under the Copyright, Designs and
Patents Act, 1988, this publication may be reproduced, stored or transmitted, in any
form or by any means, only with the prior permission in writing of the publishers, or in
the case of reprographic reproduction in accordance with the terms of licences issued
by the Copyright Licensing Agency. Inquiries concerning reproduction outside those
terms should be sent to the publishers at the undermentioned address:
The Institution of Engineering and Technology
Michael Faraday House
Six Hills Way, Stevenage
Herts, SG1 2AY, United Kingdom
www.theiet.org
While the author and the publishers believe that the information and guidance given
in this work are correct, all parties must rely upon their own skill and judgement when
making use of them. Neither the author nor the publishers assume any liability to
anyone for any loss or damage caused by any error or omission in the work, whether
such error or omission is the result of negligence or any other cause. Any and all such
liability is disclaimed.
The moral rights of the author to be identified as author of this work have been
asserted by him in accordance with the Copyright, Designs and Patents Act 1988.

British Library Cataloguing in Publication Data


A catalogue record for this product is available from the British Library

ISBN (10 digit) 0 85296 950 3


ISBN (13 digit) 978-0-85296-950-2

Printed in the UK by Short Run Press Ltd, Exeter

CE050 ii_iv picas.indd 2 15/08/2007 10:25:34


Contents

Preface xi
Acknowledgments xiii
Abbreviations and conventions xv
1 Introduction 1
1.1 The start of a new generation 2
1.2 The growing PLC market 5
1.3 Towards'open systems' 6
1.4 Deficiencies of current PLC software 8
1.5 Ladder programming 8
1.6 The deficiencies of conventional ladder programming 15
1.7 IEC 1131-3: improving software quality 15
1.8 The main features of EEC 1131-3 18
1.9 Function blocks — software integrated circuits 22
1.10 Software encapsulation 24
1.11 Inter-system portability 25
1.12 Inter-language portability 26
1.13 Graphical programming tools 27
1.14 Future developments 28
2 IEC 1131-3 concepts 31
2.1 The IEC software model 31
2.2 Communications model 47
3 Common elements 53
3.1 Common programming elements 54
3.2 Character set 54
3.3 Identifiers 54
3.4 Language keywords 55
3.5 Comments 56
3.6 Data types 56
3.7 Use of generic data types 63
3.8 Initial values of elementary data types 65
3.9 Derived data types 65
3.10 Default initial values 68
3.11 Variables 69
vi Programming industrial control systems using IEC1131-3
3.12 Variable initialisation 76
3.13 FUNCTIONS 77
3.14 Function type declarations 78
3.15 Functions for overloaded data types 80
3.16 Invoking functions in Structured Text 80
3.17 Data type conversion functions 82
3.18 Numerical functions 84
3.19 Functions equivalent to ST operators 84
3.20 Bit string functions 86
3.21 Boolean bitwise functions 87
3.22 Selection functions 88
3.23 Comparison functions 89
3.24 Character string functions 91
3.25 Functions for handling times and dates 93
3.26 Time related conversion functions 95
3.27 Functions for enumerated data types 96
3.28 Function execution control 96
3.29 FUNCTION BLOCKS 98
3.30 Function block usage 99
3.31 Defining function block types 100
3.32 Declaring function block instances 100
3.33 Function block example 101
3.34 PROGRAMS 103
3.35 Program usage 103
3.36 Defining program types 104
3.37 Declaring program instances 105
3.38 RESOURCES 106
3.39 Resource usage 107
3.40 TASKS 107
3.41 Non-preemptive and preemptive scheduling 108
3.42 Task declarations 110
3.43 Assigning programs and function blocks to tasks 111
3.44 Function block and program execution rules 111
3.45 CONFIGURATIONS 112
3.46 Configuration example 113

4 Structured Text 117


4.1 Structured Text language 117
4.2 Assignment statements 118
4.3 Expressions 119
4.4 Operators 119
4.5 Expression evaluation 120
4.6 Statements 122
4.7 Calling function blocks 122
4.8 Conditional statements 124
Contents vii

4.9 Iteration statements 127


4.10 Implementation dependencies 130
4.11 Structured Text examples 130
4.12 Solving a quadratic equation 131
4.13 Calculating average, max and min values 131
4.14 Tank control function block 132

5 Function Block Diagram 135


5.1 FBD graphical elements 136
5.2 Methodology 137
5.3 Signal flow 139
5.4 Network layout 141
5.5 Function execution control 142
5.6 Jumps and labels 143
5.7 Network evaluation rules 144
5.8 Portability between ST and FBD 145
5.9 FBD function block example 146
5.10 Continuous function chart 147

6 Ladder Diagram 151


6.1 LD background 151
6.2 LD graphical symbols 153
6.3 Methodology — relay logic 157
6.4 Connecting function blocks 158
6.5 Using functions in LD 159
6.6 Feedback paths 160
6.7 Jumps and labels 161
6.8 Network evaluation rules 162
6.9 Portability between ST, FBD and LD 162
6.10 Ladder Diagram layout 164
6.11 LD program example 165

7 Instruction List 169


7.1 DL background 169
7.2 IL language structure 170
7.3 Comments 172
7.4 Instruction semantics 172
7.5 Operators 175
7.6 Calling functions and function blocks 177
7.7 Defining functions and function blocks 179
7.8 Function block operators 179
7.9 Deficiencies and proposed extensions 180
7.10 Portability between IL and other languages 181
7.11 Good programming style 182
7.12 IL program example 182
viii Programming industrial control systems using IEC1131-3
8 Sequential Function Chart 185
8.1 SFC background 185
8.2 Chart structure 186
8.3 Simultaneous sequences 190
8.4 Steps 191
8.5 Transitions 193
8.6 Actions 196
8.7 Action qualifiers 201
8.8 SFC execution 208
8.9 SFC rules of evolution 209
8.10 Safe and unsafe design 212
8.11 Top down design 214
8.12 Macro steps 216
8.13 Good programming style 217
8.14 Scope of names within SFC networks 217
8.15 SFC textual form 218
8.16 SFC example 219

9 Function blocks 223


9.1 Function blocks as software building blocks 223
9.2 Function block usage 226
9.3 Standard function blocks 227
9.4 Example blocks 236
9.5 Designing function blocks 245

10 Programming example 247


10.1 Steam turbine control example 247
10.2 Design approach 249
10.3 Control problem decomposition 254
10.4 Program decomposition 257
10.5 Low level function blocks 262
10.6 Signal flow 263

11 Programming station facilities 265


11.1 IEC programming station features overview 265
11.2 Programming station — feature summary 268
11.3 IEC complaint implementation 274

12 Communications 277
12.1 Background to IEC 1131 part 5 277
12.2 Communications model 279
12.3 PLC functional model 280
12.4 PLC status information 281
12.5 Communications function blocks 284
12.6 MMS mapping 291
Contents ix
Appendix 1 EEC 1131-3 keywords 295

Appendix 2 IEC 1131-3 amendments 299


Typed literals 299
Enumerated data types 300
Temporary variables 300
Type conversion functions 301
Functions of time data types 301
Pulse action qualifiers 302
Action control 302
Function invocation with VAR_IN_OUT 302
Support for double-byte strings 303
RETAIN and NON_RETAIN variable attributes 303
Use of directly represented variables in function blocks 304
Extended initialisation facilities 304
Amended Instruction List (EL) 307
Production rules 307

Appendix 3 IEC 1131-3 frequently asked questions (FAQ) 309

Appendix 4 IEC 1131-3 future developments 315


What is the IEC 1499 Function Block standard? 317

Bibliography 319

Index 321
Preface

The PLC programming languages standard has come from a desire to improve the
programming techniques for industrial control systems - not only to enhance
software quality but to boost development productivity generally. Although the
focus of this book is on the use of the PLC programming languages standard, IEC
1131-3, it is also about the need to change our whole approach to designing
control systems. It is time to update our methods and techniques for control
system design and start to use modern software engineering practices.
Compared with the computing world, where new programming languages,
improved graphical user interfaces and advanced packages for personal computers
are being introduced almost every month, change in the world of industrial control
systems moves at a much slower pace.
This is quite understandable - with control systems that can manage anything
from complex petro-chemical plants, smelting furnaces and automobile
production lines to theme-park roller coasters, there is no scope for error - such
systems must be robust and reliable twenty-four hours a day. Heavy financial
losses and even lives can be at stake if these systems fail to operate as expected.
Innovations and techniques have to prove that they can survive the rigours of
industry before they can be accepted. For these reasons, any new fad or technique
is viewed with healthy cynicism before being used in anger. So why should
anyone take the IEC 1131-3 PLC languages standard seriously? The answer is
simple. IEC 1131-3 is not another invention from a standards committee.
The DEC 1131-3 standard is built on well proven techniques which are in use
today in different forms in many proprietary control products. For example, the
standard includes Ladder Diagram, a standardised form of ladder programming
which will be familiar to PLC programmers, and Sequential Function Chart, a
graphical sequencing language which is based on Grafcet - a technique that has
been in use for a number of years.
The standard has brought many common practices and techniques together to
produce a well defined suite of languages. Beyond that, the standard provides a
framework for developing well structured control software. With facilities to
package proven solutions as function blocks which can be re-used over and over
xii Programming industrial control systems using IEC1131-3
again, the standard can also directly improve productivity - right from the point of
analysing an application through to commissioning and long term maintenance.
The first revision of the IEC 1131-3 standard was published in 1993 and is now
being implemented by a number of the major PLC manufacturers. It is now
forming the basis of the next generation of programmable controllers. I trust that
this book conveys part of this new excitement.
Acknowledgments

Firstly, I would like to acknowledge the contributions of all the members of the
IEC task force (IEC 65B/WG7/TF3) responsible for drafting the PLC languages
standard. Without their diligence, perseverance and sheer enthusiasm, part 3 of the
IEC 1131 standard would not exist. Particular thanks go to the chairman, Dr
James Christensen of Allen-Bradley, for ensuring that the standard is well written,
concise and unambiguous.
Special thanks to David Beaumont of CEGELEC Projects for inviting me to
take over his role in the DEC task force as the UK representative and for giving me
the opportunity to become directly involved in the development of the standard.
I would like to thank Dr Laurie Burrow of CEGELEC and Paul Roper of
Engineering and Technical Services Ltd. for Volunteering' to check some of the
text. I also wish to thank Kloepper and Wiege Software GmbH for the opportunity
to review the Multiprog IEC 1131-3 programming system.
I must also mention Dr Mathew Bransby of National Power for his enthusiasm
for the standard and permission to use some power station plant specifications as
background material for some of the programming examples.
I wish to thank Silvertech Ltd. for material on the use of function blocks in
safety related applications.
Finally, I must give special thanks to my family Sue, Martin and Daniel, for
leaving me in peace in the attic to get on with the typing!

RWL
Abbreviations and conventions

EEROM Electrically erasable read only memory


FB Function block
FBD Function Block Diagram graphical language
FIP Fieldbus implementation based on a French standard
HVAC Heating, venting and air conditioning system
IEC International Electro-technical Commission
EL Instruction List language
ISA Instrument Society of America
ISO International Standards Organisation
ISP Integrated Software Project - Fieldbus implementation using existing
IEC standards
LD Ladder Diagram graphical language
MAP Manufacturing Automation Protocol
MMS Manufacturing Message Specification
OSI Open Systems Interconnection
PC Personal computer 1
PID Three term controller, proportional, integral, derivative closed-loop
control algorithm
PLC Programmable logic controller
POU Program organization unit
RAM Random access memory
SCADA Supervisory, control and data acquisition system
SFC Sequential Function Chart graphical language
ST Structured Text language

In the IEC 1131-3 standard, the abbreviation PC refers to a programmable controller. To avoid confusion with the
widespread use of PC as personal computer, a programmable controller is referred to as a programmable logic
controller or PLC within this book
xvi Programming industrial control systems using IEC1131-3

The following font and style is used to distinguish examples of textual programming
language from ordinary text :

BEGIN
A := A + 1 0 0 . 5 ; (* Comment *)
END

The suppression of superfluous detail in textual language examples is indicated using


an 'ellipsis' as follows:

Note: From 1 January 1997, the DSC has changed the numbering scheme for industrial
standards. Some standards which formerly had a four digit identifier have been
renumbered by prefixing the identifier with a '6'. The full identifier for the PLC
standard, formerly IEC 1131 is now IEC 61131. Similarly, the DEC Function Block
standard IEC 1499 has become DEC 61499. For brevity, the original four digit
numbering scheme has been retained in this book.
Chapter 1

Introduction

Using this book

This book has been written as a user guide and tutorial for the new international
standard EEC 1131-3 for programmable logic controllers (PLCs). If you are not
familiar with the background and purpose of the standard it is recommended that
you read through this introductory chapter.
If you are considering designing or writing control programs using any of the
DEC 1131-3 languages for the first time, you are advised to gain an understanding
of how programs are structured and can be built up from various software
elements; this is reviewed in Chapter 2, 'IEC 1131-3 concepts'. This chapter will
also explain how the standard provides a selection of programming languages for
developing different parts of a control program.
Later chapters give specific details on using each of the IEC 1131-3 languages.
The suitability of each language for solving different types of industrial control
problems is described along with techniques and examples.
Facilities in the DEC 1131-3 and an accompanying standard DEC 1131-5 for
communicating with other PLCs and devices are discussed in Chapter 12,
'Communications'.

Although it is the intention that this book should accurately describe the
languages and concepts of the standard, you should always refer to the
published IEC 1131-3 standard for all formal definitions of any part of the
standard. Alternative interpretations are described in the text in situations
where some minor details in the standard are ambiguous.
2 Programming industrial control systems using IEC1131-3

1.1 The start of a new generation

Every industry reaches a degree of maturity when there is a need to consolidate


different designs and approaches. Inevitably a point is reached where standards
start to emerge by various means. Standards may evolve through de-factoiise of a
particular technique or approach. In other situations, a standard may be foisted on
the industry through statutory regulations.
Consider any industry that involves building systems or providing services
using different components, where the components are manufactured in different
locations, different companies or even different countries. There is clearly always
a need to have standards of some form for the disparate components to work
together harmoniously. Progress with many of the early industries of the industrial
revolution was stalled until standards were developed. Railway networks could
only grow when a standard gauge was adopted; public power utilities could only
start to distribute electrical power efficiently with the acceptance of standard
supply voltages and AC frequencies.
The programmable logic controller (PLC) market has reached such a turning
point. During the last ten to fifteen years a wide range of different programming
techniques has been used to write programs for industrial control applications.
Control applications have been developed in BASIC, FORTH, C, Structured
English, Instruction List and numerous other proprietary languages.
One particular programming technique, ladder logic, has gained wide
acceptance because its understanding is fairly intuitive. Although it has been
adopted by most PLC manufacturers, each company's implementation uses its own
particular dialect. As a result, unfortunately, the only thing that can be said of all
of these programming languages is that they are all different.
For people involved with such systems, from technicians, maintenance
personnel and system designers to plant managers, this results in inefficient use of
time and money. If plant personnel or a company has to work with a number of
different control systems, there is clearly a waste of human resources involved in
training staff in skills in many different control languages.
Having so many PLC languages can also result in misunderstandings which, in
some cases, could have disastrous results. Just consider the maintenance engineer
who, in the middle of the night, is requested by a harassed plant manager to
diagnose rapidly a safety interlock fault on a production line because the line has
stopped. The system may involve two PLCs made by different vendors. In this
situation, subtle differences in interpreting the two ladder diagram programs could
Chapter I Introduction 3
lead the engineer to a faulty diagnosis and possibly to making a hazardous
modification to one of the programs.
Fortunately, the international industrial community has recognised that a new
standard for programmable logic controllers is required. A working group within
the International Electro-technical Commission (DEC) was set up in 1979 to look
at the complete design of programmable logic controllers, including the hardware
design, installation, testing, documentation, programming and communications.
The EEC is a sister organisation to the International Standardisation Organisation
(ISO) based in Geneva and has committees and working groups formed from
representatives put forward by standardisation bodies of most industrial countries
of the world.

Technical Committee Advisory group

fcii WG1 : Terms and Conditions

Industrial process WG4: Interface characteristics


. Measurement and Control WG6: standardisation of Function Blocks

WG7: Documentation of software for


for process control systems

Sub-committees

SC65B SC65C
Digital
Devices Communications

Service Conditions WG5 : Temperature sensors WG1 : Message data format

WG4 Electromagnetic WG6 : Methods of testing & WG3: Programmable Measuring


Evaluation of performance Apparatus
Interference
of system elements
WG8 Evaluation of System WG6 :1ntersubsystem
WQ7 : Programmable control Communications
Properties
Systems
WG9 . Safe software
WG9 : Final control elements
WG10: Functional safety of PES
Working Groups
WG11 :Batch control systems

Figure LI IEC Working Group structure 1993


4 Programming industrial control systems using IEC1131-3
Note: This book was revised in Autumn 1998 to reflect the corrections and
amendments proposed by the IEC for the second edition of IEC 1131-3.
The second edition is planned to be published in late Summer 1999.
EEC 1131-3 Technical Report Type 2 — This report contains proposals
for possible future enhancements and extensions for a third edition of IEC
1131-3 to be developed after 2000.

The DEC technical committee TC65, which is concerned with standards related to
industrial-process measurement and control, established Working Group 7 to
develop the PLC standard. This working group, which is now designated IEC
65B/WG7, quickly realised that standardisation of all of the issues regarding PLC
design was beyond the capability of a single group. A number of specialist task
forces were therefore established to develop different parts of the standard. Task
Force 3 has had the primary objective of developing a new language standard,
which has become part 3 of the IEC PLC standard 1131.
Throughout this book part 3, the PLC Languages standard, will be referred to
simply as IEC 1131-3. Figure 1.1 depicts the structure of the IEC standardisation
groups in existence in 1993 when the 1131-3 standard was first published.
Although this book is primarily concerned with PLC software, Working Group
7 is developing a complete suite of standards that addresses all aspects of PLCs
and their application to industrial-process measurement and control. The various
parts of the full IEC 1131 standard are listed in Table 1.1.

Table L 1 Parts of the IEC 1131 standard

Part Title Contents Published

Parti General information Definition of basic 1992


terminology and concepts.
Part 2 Equipment requirements Electronic and mechanical 1992
and tests construction and
verification tests.
Part 3 Programmable languages PLC software structure, 1993
languages and program
execution.
Part 4 User guidelines Guidance on selection, 1995
installation, maintenance
of PLCs.
Chapter 1 Introduction 5

Table 1.1 Continued

Part Title Contents Published

Part 5 Messaging service Software facilities to Planned


specification communicate with other publication
devices using 1998
communications based on
MAP Manufacturing
Messaging Services.
Part 6 Communications via Software facilities of PLC Awaiting
fieldbus communications using completion
IEC fieldbus. of fieldbus
standards
Part 7 Fuzzy control Software facilities, 1997
programming including standard
function blocks for
handling fuzzy logic
within PLCs.
Part 8 Guidelines for the Application and Planned
implementation of implementation guidelines publication
languages for for the ffiC 1131-3 1998
programmable controllers languages.

1.2 The growing PLC market

The application of this standard is set to have a major impact on the rapidly
growing industrial process control and instrumentation market, a market which
has grown significantly over the last ten years. It is estimated that this market in
Europe alone, while still in recession, was worth $1.52bn in 1995 and will
continue to rise by 5% per annum to reach $2.14bn by 2002. A global compound
market growth rate of at least 5% is possible well past 2002. As PLCs are the
backbone of most automation projects of the process control and instrumentation
sector, the PLC market can be expected to increase by an even greater proportion.
With many of the functions that were previously offered in separate instruments,
6 Programming industrial control systems using IEC1131-3
such as closed loop PID control, now being integrated into PLCs, the PLC market
can be expected to expand in many new directions.
The PLC market can be differentiated by size into: micro PLCs with up to 100
Input and Output (I/O) points, small PLCs with between 100 and 200 I/O points,
medium PLCs with 250 to 1000 I/O points and large PLCs with upwards of 1000
I/O points. It is in the micro and small PLC market sectors that the biggest growth
is expected.
Most industrial sectors use PLCs; however the main applications that are
expected to increase include food and beverage, power generation, water, glass,
cement, plastics and rubber. The largest share will however continue to be in
chemical and petrochemical sectors. In Europe, the introduction of stringent safety
or environmental regulations is causing industries such as utilities and water
treatment to upgrade their control systems.
The re-equipping of much of the industrial base of Eastern Europe, particularly
in heavy industry, steel production and processing of staple food products, will
also require an inevitable increase in the demand for PLC based control systems.
In the long term, the de-skilling and automation of production lines and
manufacturing processes will lead to the development of the iights-out' factory
where there is no longer any significant requirement for production workers or
operators. The complete 'lights-out' factory will behave as a single machine
dedicated to the production of a range of products. Such levels of automation will
not be achievable without a large investment in control systems, particularly
PLCs.
In a large number of these industrial sectors and future applications, there will
be an almost continuous demand for cost savings through improved
manufacturing efficiency and process optimisation.
This means that PLCs will be required to integrate readily with other systems
and devices and be sufficiently flexible that the control strategies for new
processes can be quickly brought on stream. The maturing industrial control
market is now starting to ask for 'open system' products which can be easily
integrated into both manufacturing cells and plant-wide computer systems.

1.3 Towards 'open systems'

The term 'open system' is probably one of the most abused of all those found in
computer marketing literature and unfortunately has become somewhat devalued.
However, in principle, an 'open system' product is one that adopts current
industrial standards and techniques so that integration with other 'open system'
Chapter 1 Introduction 7
products is straightforward and without undue trauma. There are few standards
suitable for industrial systems that actually address all the requirements for
developing complex industrial applications.
The most notable attempt to bring harmony into an industry so full of disparate
control devices, instruments, communications protocols and PLCs was started by
General Motors (GM) in the USA with the development of the MAP
(Manufacturing Automation Protocol). In the mid-1980s, there were few common
methods available for connecting control devices from different vendors so that
they could communicate sensibly.
The integration of different devices usually meant the development of complex
software in the form of communications drivers. A driver translates between
communications messages in one format sent by one device and messages of a
different format as expected by the other device and vice versa, a technique known
as protocol conversion. GM realised that a large proportion of the time and cost of
building large systems, particularly for automating car production lines, could be
saved by having a common communications standard.
The MAP standard has now stabilised but has not been particularly successful
for a number of reasons. The hardware costs to provide a communications
interface from a PLC into a MAP network can be very high and the end-to-end
communications performance has not been very impressive. Even when a fully
compliant control device such as a PLC is connected to a MAP network, a
significant problem still remains: how to transfer meaningful information between
devices which have probably been programmed in different languages.
The Instrument Society of America (ISA) standardisation work to develop a
Fieldbus standard for the interconnection of distributed field devices such as
pressure sensors, temperature controllers and valve positioners has taken a long
time to come to fruition. Although Fieldbus does address some of the issues
regarding the structure of software within devices, the Fieldbus standard is not
proposing any particular techniques or languages for developing programs within
devices;
To summarise, the industrial instrumentation and control systems need an 'open
systems' approach to build large systems using equipment from different
manufacturers. Until the EEC 1131-3 standard was published in March 1993, there
was no suitable standard that defined the way control systems such as PLCs could
be programmed. Communications standards only addressed how information
could be exchanged.
8 Programming industrial control systems using IEC1131-3

1.4 Deficiencies of current PLC software

Apart from the fact that PLCs are all programmed differently, there are a number
of notable problems when trying to program complex control applications using
many of the current PLC languages.

1.5 Ladder programming

Ladder programming has evolved from the electrical wiring diagrams that are used
in the car industry for describing relay control schemes. For small systems ladder
programming has served the industry well. The basic programming skills needed
to develop small applications using ladder programs can be learnt relatively
quickly and the graphical presentation can be understood almost intuitively. The
technique is particularly easy to understand by people who are familiar with
simple electronic or electrical circuits. Consequently, it is well accepted by
electricians and plant technicians.
For the maintenance engineer, this programming technique is also very popular
because faults can be quickly traced. Most PLC programming stations generally
provide an animated display that can clearly identify the live state of contacts in
rungs of a ladder program while a PLC is running. This provides a very powerful
on-line diagnostic facility that can clearly show up any logic paths through ladder
rungs that are incorrect.

Normally Open Contact


Out
Normally Closed Contact \ P u t Coil
Ladder Rung
Doorl \ Alarm OilPres Ready
12.2 \ 13.2 12.1 Q5.1

II—c , Power Rail


Switchl
13.3

Figure 1.2 Features of a ladder program


Chapter 1 Introduction 9
With the increase in memory size of many of today's PLCs, ladder programming
can now be used to build very large systems, bringing significant software
development problems. It is often very difficult to build well structured programs
using ladder programs because generally there is limited or no support for
procedures, subroutines or program blocks.
In this simple example, an output coil 'Ready' is powered, i.e. is set on, when
contacts 'Doorl' or *S witch V are made, contact * Alarm' is off, and contact
'OilPres' is on.

Weak software structure

Most PLCs offering ladder programming support a limited number of subroutines


or program blocks. It can be difficult to break a complex program down
hierarchically. There are generally very limited facilities for passing parameters
between program blocks. As a result it is hard to break a large program down into
smaller parts that have clear interfaces with each other. Consequently, as it is
usually possible for one part of a Ladder Diagram program to read and set contacts
and outputs used in any other part of the program, it is very difficult to have truly
encapsulated data.
Encapsulation, the ability to hide internal information within program blocks so
that it cannot be interfered with by other parts of a program, is very important for
creating good quality, maintainable software.
The lack of data encapsulation can be a serious problem with large programs
especially if they are written by different programmers. Each programmer must
always be sure that only certain global registers and memory areas are modified
when communicating information between different parts of a large program.
There is always a danger that an internal data register of one program block is
modified by faulty code in another block. Clearly, with PLCs controlling large
plant and machinery, such faults could result in unpredictable and catastrophic
control behaviour.

Low levels of software re-use

Some large programs may use the same logic strategy or algorithm over and over
again. For example, consider a program for PLC based fire and gas safety systems
for a large petro-chemical plant. Such systems may use the same logic strategy for
detecting the presence of fire in hundreds of different plant areas using a fire
detection voting algorithm. Because fire detectors are notoriously unreliable, there
10 Programming industrial control systems using IEC1131-3
is usually a requirement for at least two detectors in an area to register a fire
before extinguishants are released.
Such systems are usually written by repeating the same set of ladder rungs
hundreds of times with just minor modifications to read different input values or
set different outputs. This can result in very large and unmanageable programs.
Writing repeated logic in a block that can be called many times cai^ greatly
reduce the size of programs and produce programs that are easier to maintain. In
many ladder program based PLCs, facilities for re-using software in this way are
usually limited and difficult to use.

Poor data structure

There are also problems using structured data with ladder programs. Typically
data is stored and addressed in single memory bits or registers. Using a single bit
is fine for holding the status of simple flags and digital inputs and outputs.
Similarly, registers, which generally hold 16 bits, can be used for counters and
analogue values. However, with many complex applications, there is usually a
requirement to group data together as a structure. PLC ladder programs do not
normally have any facilities for structured data and yet it is a standard feature of
most high level languages such as PASCAL and C.
For example, consider a pressure sensor that is connected to a PLC digital input
that detects when a certain threshold pressure is reached. The PLC hardware I/O
management system will create a single bit within the PLC memory that reflects
the state of the connected sensor. However, a single bit may be insufficient to
reflect all of the states of the sensor. The application may require that the sensor
can be disabled and placed in a test mode, that a time is recorded when the sensor
becomes active, that a sensor alarm is raised when the sensor is 'on' for more than
a prescribed period and so on.
All of this extra information associated with the sensor should ideally be stored
as a single structure that can be addressed using a common unique name. With
complex ladder programs, such data are often spread out throughout the PLC
memory so that the chances of accidentally addressing data bits associated with a
different sensor are very high. With no formal'data structure support, the PLC
programming system is generally unable to give the programmer any warning
when such data violations occur.
Chapter 1 Introduction 11

Limited support for sequencing

Many industrial applications require that the PLC programs generally require one
or more sequences of operations depending on various operational states of the
controlled process.
For example, consider starting a conveyor belt for a production line: the
program may need to check that certain auxiliary equipment is in a known initial
state; it may then need to assign speeds to the conveyor drive motors as a series of
steps. After each speed change, the PLC may need to check that the speed of the
whole line has stabilised before making the next speed step. When the working
speed is reached, it may need to activate other machines and equipment on the
line.
The conventional approach to this type of problem using ladder programming is
to assign a bit to each state of the sequence and to each transition that triggers a
change from one state to the next. The sequence is programmed in three parts: (1)
ladder rungs for detecting the transitions from one state to the next, (2) rungs
switching between states and (3) rungs to perform actions or operations when
particular states are active. Figure 1.3 depicts part of a ladder program for solving
the conveyor start-up example.

Stepi Equip.OK Trans1_2 Transition Rungs

Step2 Speed_Stable Trans2_3

HI II <>-

Stepi Step2 Step3 Ready Stepi Step Rungs

I—14H4-4HI—<>-

Stepi Speed 1 Step Actions

Step2 Speed2
h -< > —

Figure 1.3 Sequencing using ladder programming


12 Programming industrial control systems using IEC1131-3
It is clear that ladder programs can produce sequential behaviour in this way;
however with large programs which may have sequences with hundreds of steps,
this approach can quickly become very unwieldy and difficult to maintain. The
main problem is that the control of the sequence is mixed in with the application
logic so that the overall behaviour is difficult to understand.

Note: Many PLC vendors are now offering Grafcet or Sequential Function Charts
from the IEC 848 standard; we will see that this is a superior method of
defining sequences. Sequential Function Charts are part of the IEC 1131-3
standard and will be discussed in some detail in later chapters.

Limited execution control

Figure 1.4 depicts the way ladder programs are normally executed. Most PLCs
continuously execute a cyclic scan. The cycle starts with the hardware 170 system
gathering the latest values of all input signals and storing their values in fixed
regions in memory.
The rungs of the ladder program are then executed in a fixed order starting at
the first rung. During the program scan, new values of physical outputs, as
determined from the logic of the various ladder rungs, are initially written to an
output memory region. Finally, when the ladder program has completed, all the
output values held in memory are written out to the physical outputs by the PLC
hardware in one operation.

Outputs
Written from PLC
Memory

Figure 1.4 Scanning ladder programs


Chapter 1 Introduction 13
This simple execution scheme is easy to understand and is quite adequate for a
wide range of elementary PUC applications. However there are a number of
problems with this approach. Generally, the frequency of the ladder program
execution depends to a large extent on the length and complexity of the ladder
program. Add more rungs and the scan time will lengthen; this can cause
problems when designing systems that need to respond within a guaranteed
period.
For example, consider a requirement of a PLC system to control a plastics
extrusion machine. The PLC may need to control motor drives for handling the
plastics feed screw and extrudate haul-off, while at the same time controlling
mechanical interlocks and operator displays and managing the delivery of plastics
feedstock.
To protect the expensive extruder barrel, the PLC should rapidly activate motor
drive trips within, say, 100 milliseconds if certain alarm signals such as a 'melt
over-pressure' are detected. The pressure of molten plastics or the melt pressure is
a critical parameter in an extruder and may suddenly increase due to some form of
blockage further along the barrel. A high internal pressure may cause the barrel to
distort or even explode.
In this case, critical sections of the ladder program detecting the alarm
conditions will need to execute within, say, 50 milliseconds to always meet the
100 millisecond deadline. It may be acceptable for long sections of the ladder
program handling the other less critical extruder functions to ran less frequently.
Consequently, the programmer may need to spend time and effort arranging the
scheduling of the different parts of the program to meet these deadlines.
Generally this can be achieved by running the faster logic sections every 50
milliseconds and switching in different sections of the less critical ladder rungs in
the background.
Although most PLCs provide some facilities to select when various sections of
rungs are scanned, such as the master control relays in Allen-Bradley PLC-5s, it is
generally very difficult for the programmer to have full control over the execution
rates of different parts of the program.
When PLC programs are also used for running closed loop control algorithms
such as the three term PID ( proportional, integral, derivative), the problems are
compounded. For good control, the period between updates of the PID algorithm
is critical, i.e. the time between the ladder program scans should be stable and
generally of a known duration.
This may be difficult to realise in practice. There is always a possibility that just
adding a few new rungs or modifying a ladder program can change the scan
14 Programming industrial control systems using IEC1131-3
execution time. This may subtly change the timing of certain closed loop control
algorithms so that the whole system behaves differently. This lack of deterministic
behaviour is one of the main criticisms of using conventional ladder programs in
PLC applications for process control.
We will see that the EEC 1131-3 standard has given some attention to this
problem and has provided comprehensive execution control of different program
elements.

Cumbersome arithmetic operations

Finally, performing arithmetic operations using ladder programs can also be very
cumbersome. There is a wide range of different techniques available but like
ladder programming itself, the approach tends to vary from PLC product to
product. One common approach is the use of arithmetic blocks. Such blocks can
be triggered by the activation of a ladder rung. Figure 1.5 depicts arithmetic blocks
that might be used to calculate the average of two analogue values held in
registers.
Average
1 ADD
1 R12
R13
R20

Average
1 DIV
1 R20
2
R21

Figure 1.5 Arithmetic operations in ladder programs

As with the other ladder programming features, performing simple arithmetic


operations in this way is straightforward. Trying to perform complex calculations
involving dozens of variables can be a nightmare and can result in programs that
are very difficult to maintain.
Because PLC programming stations generally only allow a few ladder rungs to
be visible at a time, it is only possible to see a small part of a complex calculation
at a time. As a PLC programmer remarked, 'It's like trying to write a program
through a small key-hole'.
Chapter 1 Introduction 15

1.6 The deficiencies of conventional ladder programming

The following table summarises the main faults with conventional ladder program
based PLCs.

1. The ladder symbols and facilities vary between different PLC


products.
2. Poor facilities for structured or hierarchical program
decomposition.
3. Limited facilities for software re-use.
4. Poor facilities for addressing and manipulating data
structures.
5. Limited facilities for building complex sequences.
6. Limited control over program execution.
7. Facilities for arithmetic operations are cumbersome.

For people who work with PLCs every day, this summary may seem to be
somewhat harsh. With very good programming standards, use of program
generators, off-line documentation tools and the application of information
technology (IT) using databases to manage data addressing and so on, many of
these deficiencies can be circumvented to some degree but never completely
ignored.
Considering the wide range of PLC applications from the control of automobile
production lines, brewing, water treatment and fun-fair roller-coasters to treatment
of radioactive waste, it is remarkable that quality systems can be delivered despite
these limitations. But at what cost and effort ?

1.7 IEC 1131-3: improving software quality

One of the major objectives of the new EEC 1131-3 PLC programming standard is
to widen the understanding of PLC programs. With PLCs being used in so many
industries, and with many applications concerned with safety, it is important that
programs, and subsequently the behaviour of controlled plant, can be understood
by a wide range of industrial personnel. A PLC program should be relatively easy
16 Programming industrial control systems using IEC 1131-3
to follow by technicians, plant managers and process engineers alike, as well as by
the programmer.
By having a consistent approach to programming, the standard will also of
course reduce the learning-curve for all people who need to deal with PLCs -
especially if they have to deal with products from different vendors.
Before detailing the new features in the standard it is worth considering all the
attributes of software and the software development process that contribute to
improvements in software quality. These quality attributes are described in part 8
of the EEC 1131 standard that provides guidelines on the application and
implementation of IEC 1131-3. These attributes can be used as part of a quality
checklist for any piece of software and are particularly relevant to PLC software.
We will see that many of the features of the IEC standard directly improve many
of these quality attributes of PLC software.

Capability

This describes the extent to which a system can perform its intended design
function. This is influenced by factors:

Responsiveness The time required for the system to produce


appropriate responses to a specified combination
of external events.
Processing capacity The extent to which the system can meet
scheduling deadlines under specified sets of
conditions.
Storage capacity The extent to which the system can retain in
memory all the required programs and data
under specified sets of conditions.
Chapter 1 Introduction 17

Availability

This describes the proportion of time in the life of a system when it is available for
its intended function. This is influenced by factors such as:

Reliability The ability of the system to continue to perform all its


intended functions over a specified period of time and
range of conditions. An inverse measure of reliability is
mean time between failures (MTBF).
Maintainability The ease with which the system can be restored to full
capability after the occurrence of one or more faults from
a specified set. An inverse measure of maintainability is
mean time to repair (MTTR); availability is often defined
by the expression MTBF/(MTBF+MTTR).
Integrity The degree to which the system can continue to
perform all its intended functions over a specified
range of threats, including both unintended user actions
and intentionally hostile actions.

Usability

This describes the ease with which a specified set of users can acquire and
exercise the ability to interact with the system in order to perform its intended
functions. This is influenced by factors such as:

Entry requirements The amount of formal and informal training required


before the user can learn to interact with the system (e.g.
prerequisite educational level, skill-sets in the use of
operating systems, windows, menus, etc.).
Learning The training required for a user meeting a specified set
requirements of entry requirements, to learn to interact with the system
to perform a specified set of system functions.
User productivity The number of system-related operations per unit time
which can be performed by a user with a specified
level of training and experience.
Congeniality The extent to which a user prefers to utilise the system
software to perform the intended system functions,
with respect to alternative activities that may or may
not be system-related.
In other words - is the system user friendly ?
18 Programming industrial control systems using IEC1131-3

Adaptability

This describes the ease with which the system may be changed in various ways
from its initial intended functions. This is influenced by factors such as:

Improvability The ease with which the existing capability, availability^


and/or usability can be upgraded without significantly
changing the system functionality.
Extensibility The ease with which new functionality can be added to
the system.
Portability The ease with which system functionality can be
moved from one system to another.
Reusability The ease with which the functional capabilities of an
existing software element can be used in a new or in a
different system.

It is the intention that IEC 1131-3 based PLC software will have significantly
better software quality attributes, as described, than software generated for
conventional PLCs. This is achieved by new language features and providing
different programming languages for solving different types of industrial control
problem.

1.8 The main features of IEC 1131-3


The IEC working group responsible for the 1131-3 standard started by reviewing
commonly used techniques and languages as offered by various PLC
manufacturers. They then rationalised the different languages and numerous
dialects of ladder programming to create a new set of languages. Considering that
the major PLC companies including Allen-Bradley and Siemens have active
members in the IEC group, it is a notable achievement that the group has been
able to come to a consensus and produce a robust and working standard.
The major new features offered by IEC 1131-3 are summarised as follows:

l.The standard encourages well structured, 'top-down* or 'bottom-up'


program development. The standard allows a program to be broken down
into functional elements that are referred to as program organisation units or
POUs. POUs include functions, function blocks and programs. These will be
described in detail in later chapters. Any IEC software element can be
constructed hierarchically from other more primitive elements.
Chapter 1 Introduction 19

2. The standard requires that there is strong data typing. This means that the
PLC program station should be able to detect when a programmer
erroneously attempts to write the wrong type of data to a variable. For
example, assigning the value 1 as a bit, to a memory location designated to
receive the value of a time duration as 1 second, would be detected as an
error before the program is down-loaded into the PLC. This will remove a
major source of programming errors in conventional PLC ladder programs.
3. Facilities are provided so that different parts of a program can be executed at
different times, at different rates and in parallel, i.e. there is support for full
execution control. For example, part of a PLC program may need to scan
every 50 ms to ensure that all changes of state read in from mechanical limit
switches are detected, while another part of a program monitoring
temperature sensors may only need to scan every second. IEC 1131-3
provides facilities so that the programmer can decide to run these different
parts at different rates, by assigning the parts to different tasks.
4. There is full support for describing sequences so that complex sequential
behaviour can be easily broken down using a concise graphical language
called Sequential Function Chart. This allows a sequence to be described in
terms of steps, their actions and transitions between steps. There is full
support for sequences that call alternative sequences and for sequences to call
other sequences that run in parallel. For example, a PLC program may be
required to control two independent reactor vessels. After the PLC program
has initialised, the sequences handling the two vessels can be programmed to
run in parallel and can then run independently of each other.
5. There is support for defining data structures so that data elements that are
associated can be passed between different parts of a program as if they were
a single entity. For example, a pump controlled by a PLC may have a status
bit defining whether it is operational or not, an analogue output defining the
required speed setting, an analogue input defining its measured speed and so
on. All of these data elements can be defined as in a single 'pump' data
structure. It is then possible to pass all of this information as a single variable
between different program organisation units. This improves program
readability and ensures that associated data is always accessed correctly.
6. The standard provides flexible language selection, i.e. a set of three
graphical and two textual languages for expressing different parts of a control
application. The system designer is free to choose the language that is most
20 Programming industrial control systems using IEC 1131-3

suitable to solve a part of an application program. Different parts of a


program can be expressed in any of the languages.
7. IEC 1131-3 provides standardised languages and methods of program
execution so that a wide range of technological problems can be programmed
as vendor-independent software elements. In other words, a large
proportion of software written for IEC 1131-3 compliant PLCs should be
portable and will run on PLCs from different vendors.

The new IEC 1131-3 languages that will be described fully in later chapters are
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List and
Sequential Function Chart.

Structured Text (ST) - A high level textual language that encourages structured
programming. It has a language structure (syntax) that strongly resembles
PASCALS
IFSPEED1 > 100.0 THEN
Flow_Rate := 50.0 + Offset_A1;
ELSE
Flowjtete := 100.0; Steam := ON;
ENDJF;

Function Block Diagram (FBD) — A graphical language for depicting signal


and data flows through function blocks — reusable software elements.

OnDelay_J
TON
High_Press- IN Alarm Inch 2
Q1 - Over_Press
T#30s PT RS
Q1 Alarm P12
Enable - AND R1
Alarm Clr-

Some features of the IEC textual languages have also been influenced by ADA, a high level language designed for
the American Department of Defence (DOD), 1979.
Chapter 1 Introduction 21
Ladder Diagram (LD) — A graphical language that is based on relay ladder
logic, a technique commonly used to program current generation PLCs.

0VR1
SW1 I I I I
SW2 II II
II EN ENO
X65 SUB SPEED
1

Instruction List (IL) — A low level 'assembler like' language that is based on
similar languages found in a wide range of today's PLCs.

LD R1
JMPC RESET
LD PRESS_1
ST MAX_PRESS
RESET: LD 0
ST A X43

Sequential Function Chart (SFC) — A graphical language for depicting


sequential behaviour of a control system. It is used for defining control sequences
that are time- and event-driven.

Start N PUMPS Ready

— Ready

I
Vacuum — S DEPRESS Checks N PRESS CHK

In addition to the new languages, the EEC 1131-3 standard also formally defines a
number of powerful new concepts, notably the use of function blocks.
22 Programming industrial control systems using IEC 1131-3

1.9 Function blocks — software integrated circuits


We have already said that DEC 1131-3 encourages the development of well-
structured software that can be designed either from top-down or bottom-up. One
of the main features in the standard to support this is the use of function blocks.
A function block is part of a control program that is packaged so that it can be
re-used in different parts of the same program, or even in a different program or
project. A function block may provide the software solution to some small
problem, such as creating a pulse timer, or may provide the control to a major
piece of plant or machinery, for example the control of a pressure vessel.
The ability to store data as well as the algorithm within the function block gives
the IEC function block significant advantages over similar concepts found in other
languages, such as subroutines in FORTRAN and functions in C. A function block
describes both the behaviour of data and the data structure.
The IEC standard ensures the use of well defined interfaces into function
blocks, i.e. that there are formal definitions for each input and output parameter.
Function blocks designed by different programmers can therefore be readily
interconnected because each input and output parameter must use data types
derived from data types defined within the standard.
Function blocks should be regarded as the basic building blocks of a control
system. The standard provides facilities so that well defined algorithms or control
strategies written in any of the IEC languages can be packaged as re-usable
software elements. Function blocks not only encourage well structured design, but
in the long term can greatly speed up the application development. This is
especially true when developing similar applications where high re-use of standard
solutions, as function blocks, should be possible.
Through the increased use of function blocks, we may start to see the
development of 'vendor-neutral' industrial software; in other words, markets
emerging for libraries of function blocks designed for solving a wide range of
different industrial applications that can run in any manufacturer's product.
Although IEC 1131-3 defines a few rudimentary function blocks, there are
currently no plans to define a range of standard industrial blocks for, say, signal
ramps, filters, PID control, etc. However, in the current work on Fieldbus
standardisation, the idea of having a standard range of blocks that can intemperate
across a fieldbus network between different vendors' products is being pushed
very strongly.
Comparisons have been made between function blocks and objects found in
object oriented programming. Function blocks contain encapsulated data, and
Chapter 1 Introduction 23
have methods associated with that data, i.e. the algorithm or control strategy.
However, other features found in object oriented languages such as inheritance
and polymorphism are not supported.
The function block concept may be more clearly understood by hardware
analogy. In many ways, function blocks can be compared with integrated circuits
(ICs) or 'silicon chips' which are used every day by electronic engineers. The use
of ICs has clearly revolutionised the design of electronic hardware - no one would
now consider building a system up from primitive circuits unless there are some
very special reasons. Like ICs, function blocks can provide 'off-the-shelf
solutions to common control problems and so could be set to revolutionise the
development of control software.

Electronic Integrated IEC1131-3 Standard Function Block


Circuit On-delay Timer

Ton
IN Q

PT ET

Input Variables Output Variables


Figure 1.6 Comparison between ICs andfunction blocks

The idea of considering re-usable software as ICs was first put forward by Brad
Cox in 1986 2. As the world began to accept the object oriented approach for
mainstream software development, he predicted that software vendors would start
to market libraries of useful software objects.
Unfortunately, this has not developed in quite the way that he foresaw, mainly
because there is such a wide variety of different object oriented languages. Objects
developed for one language are not directly compatible with any of the others, e.g.
C++, Objective C, Smalltalk 80. However, a market has recently developed for
object libraries (as software components) for Microsoft's Visual Basic3. If IEC
1131-3 products become the norm, it is possible to foresee markets for application
specific function block libraries developing, for example, for PBD algorithms,
fuzzy logic controllers, alarm handlers and so on.

"Object oriented programming - An evolutionary approach", Brad J. Cox, 1986

^ Visual Basic is a trade mark ofMicrosoft Corporation.


24 Programming industrial control systems using IEC1131-3

1.10 Software encapsulation


Packaging software using encapsulation and information hiding, so that software
internals are not readily assessable, is important in improving software quality.
Encapsulation is the ability to handle a collection of software elements as a single
entity, for example packaging a number of data items in a single data structure.

Table 1.2 IEC 1131-3 software elements


IEC element Description Encapsulation Hiding

Data Procedure Data Procedure


Structure Used for forming a new Yes No No No
composite from a
number of data types
Function Used for calling re- No Yes Yes Yes
usable software
procedures
Function Used to package Yes Yes Yes Yes
block software procedures and
data
Program Used to build entire IEC Yes Yes Yes Yes
programs from other
elements
Action Used to package a set of No Yes No No
operations for use in
sequence steps
Access path Used to allow access to Yes No Yes No
one or more items of
data from a remote
device

'Information hiding' is the restriction of external access to data and procedures


within an encapsulated element. For example, in a large control project, ponsider
the benefits of making parts of a well tried and tested control strategy into
function blocks, each with a small set of external parameters providing all the
required program control. System designers are then able to build up larger
applications simply by connecting the proven blocks — intimate knowledge of
how the block has been coded internally is not required.
Chapter 1 Introduction 25
It is only necessary to understand the 'functionality' provided by a function
block and use of its external parameters. As the system designer is only able to
change the values of external parameters, the danger of using a packaged control
strategy with conflicting or inconsistent data and control signals is very much
reduced.
In contrast, consider the situation where the re-usable code is not packaged as a
function block, and the system designer is able literally to copy the code from
previous control solutions. There is now every danger that the code will be
modified or that its internal data are accidentally over-written. The chances of the
code behaving as originally designed and tested in this situation are significantly
reduced.
Apart from function blocks, BBC 1131-3 provides a number of language
elements for encapsulating both software procedures and data. These will be
discussed in more detail in further chapters of this book. Table 1.2 lists the main
software elements in the EEC standard. The table emphasises that data and code
(procedure) encapsulation and information hiding are characteristics of many of
the IEC software elements.

1.11 Inter-system portability


A major benefit for end-users using BBC 1131-3 compliant products will be the
possibility of being able to port control system software to different products.
Software developed for one manufacturer's PLC product family should
theoretically be able to ran on any other IEC compliant system. Clearly, this could
have a major impact on sourcing PLC equipment and will generally open up the
PLC market.
The choice of a PLC supplier for a new project should be determined more by
the suitability of the hardware, I/O sub-system and price than by the types of
languages that the PLC supports.
Such a high level of software portability, referred to as inter-system portability,
may be difficult to realise in practice. The EEC 1131-3 standard defines numerous
tables of features and only requires that PLC vendors list those features that they
decide to implement. In other words, the EEC 1131-3 standard does not require or
expect every language feature to be implemented!
The normal chances then of finding two vendors who will choose to implement
exactly the same set of features may not be very high. Without products having the
same set of language features, the possibility of being able to port software
between such systems will be slight.
26 Programming industrial control systems using IEC1131-3
As the IEC standard is not explicit about compliance requirements, any PLC
vendor can claim to be IEC 1131-3 compliant by simply implementing one or two
simple language features. Because of EEC 1131-3's weak compliance requirements
and the possibility that the dream of truly portable control software was in
jeopardy, a number of companies concerned with promoting EEC 1131-3*l>ased
products formed the PLCopen trade association. PLCopen has been actively
involved with defining different compliance levels with the objective that products
that have the same compliance level will support a known level of software
portability.
It is worth noting that membership of PLCopen has continually grown since it
was formed in 1992 illustrating the widening international impact of IEC 1131-3.
At the end of 1993 it had members from over 41 different companies and
organisations. By 1997 it had almost 100 members representing most of the major
PLC vendors and some important end-users. Its main office is in the Netherlands
but there are also supporting offices in Japan and the USA. By the summer of
1997, 11 products had achieved the PLCopen base level compliance for the
Instruction List (IL) language. Other products are in the process of being evaluated
for EL compliance. PLCopen is also developing test suites for compliance testing
to the other IEC 1131-3 languages.
One aspect of the standard that may also reduce the portability of software
between different systems is the provision for implementation dependent
parameters. EEC 1131-3 defines over thirty parameters that can be defined by the
PLC vendor. These include features such as the maximum number of array
subscripts, the maximum number of function specifications and the maximum
number of CASE selections. Clearly, for software to be truly portable, it must be
built on systems that have very similar or identical IEC 1131-3 implementation
dependent parameters.
The IEC 1131-3 standard has been criticised for defining too many optional
features that may be implemented at the discretion of the PLC vendor. Having
compliance levels that demand the implementation of a well defined set of
features as proposed by PLCopen should help to circumvent this problem.

1.12 Inter-language portability


By providing various languages for expressing control software, IEC 1131-3
allows the software designer to choose the most suitable language for the problem
in hand. Software elements such as function blocks can be programmed in any of
the languages. The designer may select a particular language because it more
Chapter 1 Introduction 27
clearly matches his or her mental realisation of the solution or simply because it is
more familiar.
Although it was never a fundamental objective of the IEC group while
developing the 1131-3 standard, it is generally possible to convert software
elements expressed in one language into any of the other languages.
It is certainly possible to solve the same control problem using any of the
languages although in some cases the algorithm may be slightly different.
However, some IEC language implementors have developed systems that will
automatically convert between any two languages, say, from Ladder Diagram to
Function Block Diagram, or Instruction List to Structured Text and so on. For
example, a function block can be programmed using Function Block Diagram by
one programmer, reviewed in Ladder Diagram format by a maintenance engineer
and then documented in Structured Text for a code walk-through. This gives the
exciting possibility that the person reviewing the software is able to choose a
language that he or she finds the easiest to understand.
There are a few features in some languages that cannot be ported accurately to
the other languages. Nevertheless the common set of features in the IEC languages
is sufficiently large to allow a major proportion of software to be converted
between any two languages. Problems that prohibit complete inter-language
portability may be resolved in later revisions of the standard.

1.13 Graphical programming tools


The IEC 1131-3 standard is beginning to have a significant impact on the type of
facilities being offered by programming stations used to design and program the
next generation of PLCs and industrial control systems. The days when PLCs are
programmed on character based screens using primitive graphics and obscure
keyboard command sequences are numbered.
State-of-the-art IEC based graphical programming stations are now emerging
that provide many of the facilities found with computer aided software
engineering (CASE) systems, now commonly used for large scale mainstream
software development. Many IEC programming systems offer graphical
programming screens with multiple windows, mouse operation, pull-down menus,
built-in hypertext help and so on. Such stations are also able to apply certain
software verification checks as the software is being developed. For example,
when two function blocks are connected, the system can check that the data types
of all connected parameters are compatible.
28 Programming industrial control systems using IEC1131-3
We will start to see a new generation of PLC programming stations that provide
many of the facilities needed for the complete PLC system design life-cycle - from
initial system analysis, top-level design, coding, system building, testing and on-
line diagnostics through to maintenance.

1.14 Future developments


A second edition of IEC 1131-3 is planned for publication in the middle of 1999.
This will include the amendments outlined in Appendix 2. These generally
enhance the usability of the standard rather than adding any major new features.
In the longer term, probably by the end of 2000, a major new revision of the
IEC 1131-3 standard is being proposed. The new features that are likely to be
considered will include a standard file exchange format to allow IEC 1131-3
designs to be ported between different vendors' programming stations,
improvements for developing safety critical applications and compatibility with
the EEC 1499 Function Block standard. IEC 1499 which is currently being
developed by DEC working group SC65/WG6 will address the use of function
blocks in distributed applications that encompass both PLC and fieldbus devices.
It is the intention that IEC 1499 will provide a consistent function block
methodology across PLC and DCS systems.

Summary
The main reasons for developing the IEC 1131-3 standard are:

• that there have been no consistent methods for programming PLCs;


• that conventional PLC ladder programming languages have a number of
deficiencies that discourage the development of quality software.

Use of EEC 1131-3 languages is bringing a number of benefits, to both the PLC
software developer and the end-user:
• IEC 1131-3 provides a variety of languages for solving different types of
industrial control problem.
• It encourages the development of quality software through well structured
design, the use of encapsulation and information hiding.
Chapter 1 Introduction 29
Use of BBC 1131-3 will allow the same control software to be developed for
different PLC products.
Formalisation of re-usable software, especially function blocks, should result
in improving the productivity of system designers through the provision of
off-the-shelf solutions.
IEC programming tools are emerging that offer support for the complete PLC
software life-cycle.
Chapter 2

IEC 1131-3 concepts

Among the more important aspects of any programming system is the provision
for software to be decomposed into small manageable parts. In this chapter we
will review how complex programs can be broken down into different software
elements which have clear and formal interfaces with each other. We will also see
how the standard provides a number of different languages for developing
software building blocks.
The reasons why the IEC software standard encourages programs to be
constructed using either a top-down or bottom-up design approach will also be
discussed.
You are advised to read this chapter first in order to gain an understanding of
the main concepts in the IEC standard and how software is structured before
proceeding to the chapters on specific IEC languages.

2.1 The IEC software model

In the course of developing the IEC 1131-3 standard, the EEC working group has
had to consider the wider context of a PLC program. Every program has to exist in
and interact with an environment. What is the nature of the boundary between a
program and the rest of a system? Clearly, it is not possible to define the structure
of a PLC program without a good understanding of its interfaces and interactions
with the control system and external plant.
When a program is loaded into a PLC and is running, it requires the following
types of interface to function:

• I/O interfaces: With every PLC system there is a requirement to read values
coming from physical input channels that may be connected to sensors of
various types such as micro-switches, pressure transducers, thermocouples
etc. On the output side, there is a requirement to update values of physical
output channels to drive a variety of actuators such as valve positioners,
solenoids, servos, heaters and so on.
32 Programming industrial control systems using IEC1131-3
• Communications interfaces: Most PLC systems are required to exchange
information with other devices and PLCs, drive operator displays and panels.
• System interfaces: There is also always at requirement for a system interface
between the PLC program and PLC hardware. System services are required to
ensure that the program can be initialised and run (executed) correctly as
intended by the program designer. In practice, these services are generally
provided by a combination of PLC hardware and embedded system software -
sometimes referred to as system firmware.

ly—^ Continuous
Continm Signal
Position

Physical Transducer Plant


Physical Regulator

Actuator |

_j
Actuator
Controller

Sampled Signal Control Output


Hardware
LJLL Jl Output
Driver
EC 1131-3 Software

=n-
Control Program

Figure 2.1 Using a PLC system for direct digital control

Traditionally many PLCs have been used in plant control applications where
they provide interlock logic and alarm monitoring of purely digital signals. In such
applications, inputs would typically come from digital sensors such as
microswitches, and outputs would drive digital devices such as relays and
indicators.
Chapter 2IEC1131-3 concepts 33
PLCs are now being used more frequently to provide complete plant control. In
many cases that includes providing direct digital control (DDC) - sometimes
referred to as closed loop control. Figure 2.1 depicts the principal components of
a direct digital control system using a PLC. By converting continuous signals from
a transducer into digital samples, a PLC control system can apply control
algorithms such as a three term controller - proportional, integral, derivative
(PID), to produce the desired output control signal that, in turn, can be used to
position an actuator. The figure shows the speed of a steam turbine being
controlled by a steam valve.

Note: From general control theory, the 'sampling rule' sets the theoretical
minimum rate at which a signal should be sampled in order to represent it
completely as a sequence of numbers. In practice establishing the
appropriate sampling rate for stable and responsive control may require
detailed information on equipment response times, plant time constants etc.
The theory behind this analysis is not in the scope of this book. It will
always be necessary to calculate minimum acceptable sample rates for
different control loops when designing a DDC system. However, with the
IEC 1131-3 standard this is made somewhat easier because the designer
now has the flexibility of being able to configure different parts of a control
program to scan at different rates. 1

The software and concepts that come within the scope of the EEC 1131-3 standard
are shown outlined in Figure 2.1. The standard assumes that the values of external
sensors and transducers are available from particular PLC memory locations. It
also assumes that output values to drive actuators and indicators will be sent by
updating certain PLC memory locations. The mapping of PLC memory to
input/output (I/O) devices is not defined in the standard and will vary significantly
from one manufacturer's PLC to another.
The main elements of the IEC software model needed to provide the PLC
software environment are shown in Figure 2.2.
The model is layered - each layer hiding many of the features of the layers
beneath it. We will now review the main features of this model to see how they
are used together to build software for a PLC control application.

The provision of multiple tasks is an optional feature. Some PLC vendors may choose to provide a fixed set of
tasks with only a limited selection of scan times.
34 Programming industrial control systems using IEC1131-3

Configuration

Resource
Task Task

Program \ Progi

Global and directly'[represented variables

Access paths

Key
| Variables

FB Function Blocks
Communication functions
Access paths
( defined in IEC 1131 Part 5) Execution control path

Figure 2.2 IEC 1131-3 software model

Configurations

At the highest level, the software for a particular control problem is contained in a
configuration2. Existing at the outer layer of the entire PLC software model, a
configuration is defined as a language element that corresponds to the
programmable controller system.
Generally a configuration equates with the software required for one PLC. With
large complex applications such as the automation of an entire production line,
there may be a requirement for several PLCs to interact with each other, in which
case the software for each PLC would be regarded as a separate configuration.
A configuration is able to communicate with other IEC configurations within
different PLC systems via defined interfaces - all of which must be formally
specified using standard language elements.

^In IEC 1131-3 terminology, the word 'configuration' applies to the entire software that defines the behaviour of a
PLCfor a specific application. It should not be confused with the actual process of configuring a system.
Chapter 2IEC1131-3 concepts 35

Resources

Within each configuration there are one or more resources. A resource provides
support for all of the features needed for the execution of programs.
In software engineering terms, the resource may be regarded as the interface
into a 'virtual machine' that is able to execute an IEC program. Itfc main function
is to provide a support system to run programs.
An IEC program cannot function unless it is loaded into a resource. Normally a
resource will exist within a PLC, but there is no reason why an IEC resource may
not be provided by other systems. For example, a resource may be simulated
within a personal computer to support PLC program testing. If it is possible to
create an EEC resource, then it should be possible to execute IEC programs.
An interesting feature of a resource is that it is a subdivision of the software and
may also reflect the physical structure of the PLC in which it resides. For example,
the software for a PLC with multiple processor cards may be designed to have a
resource on each card. The control of a resource in a configuration should be
capable of independent operation - i.e. it should not be influenced by other
resources.
One of the main functions of a resource is to provide an interface between a
program and the physical I/O channels of the PLC.

The standard tersely defines a resource as:

4
A language element corresponding to a "signal processing function" and its
man-machine interface and sensor and actuator interface functions, if any as
defined in IEC 1131-1'

It is interesting that the standard allows a configuration to contain a number of


resources and for each resource to be able to support more than one program. This
gives the exciting possibility of a PLC being able to load, start and execute a
number of totally independent programs.

Note: In the course of designing the IEC standard, the working group considered
an ideal software model that can support all future control requirements.
Control systems and PLCs that can run multiple programs within multiple
resources clearly may not be readily implemented using today's technology.
With the development of yet lower cost and higher performance micro-
processors and memory, this may clearly become a future possibility.
36 Programming industrial control systems using IEC1131-3
Programs

An IEC program can be built from a number of different software elements each
of which may be written in any one of the different IEC languages. Typically a
program consists of a number of interconnected function blocks that are able to
exchange data through software connections. A program can read and write to I/O
variables and communicate with other programs. The execution of different parts
of a program, for example selected function blocks, may be controlled using
tasks.

IEC 1131-3 defines a program as:


'A logical assembly of all programming elements and constructs necessary for
the intended signal processing required for the control of a machine or
process by a programmable controller system.'

Tasks

A task can be configured to control a set of programs and/or function blocks


either to execute periodically or upon the occurrence of a specified trigger. In this
context, a single program or function block execution implies that all the software
elements within the program are processed once.
In the IEC model, there are no hidden or implied mechanisms for execution of
programs. In other words, a program or function block will remain completely
dormant unless it is (a) assigned to a specific task and (b) the task is configured to
execute periodically or when triggered by a specified variable changing state.
However, note that function blocks not explicitly associated with a particular
task will always execute in the same task as their parent program.

Function blocks

The function block concept is one of the most important features within the IEC
1131-3 standard for supporting software hierarchical design. Using function
blocks it is possible to create a program from smaller more manageable blocks. As
any function block can also be programmed using other function blocks, it is
possible to create a program that is well structured and truly hierarchical.
A function block has two main features: it defines data as a set of input and
output parameters that can be used as software connections to other blocks and
internal variables, and also has an algorithm, a piece of code that runs every time
the function block is executed. The algorithm processes the current values on the
Chapter 2 IEC 1131-3 concepts 37
input parameters and the values of internal variables to produce a new set of
values for output parameters. In some cases the algorithm may create new values
to update values of internal variables which may be local, i.e. declared within the
function block, or global, i.e. declared at the program, resource or configuration
level.
Because a function block is able to store values, it has a defined state. We will
see that this is an important property that allows function blocks to be used to
solve a wide range of control problems. For example, function blocks can be
provided for closed loop control using PID or fuzzy-logic algorithms.
The standard specifies a range of standard function blocks for commonly
required facilities including R-S bistables, counters, timers and real-time clocks.
More importantly, IEC 1131-3 also allows the designer to produce new function
blocks which can be built up from existing function blocks and other software
elements.

Functions

The standard also specifies the use of functions that, understandably, are often
confused with function blocks. Functions are not shown in the software model in
Figure 2.1, but are discussed here to clarify what might otherwise be a misleading
concept.
A function is a software element which when executed, with a particular set of
input values, produces one primary result. The best examples are mathematical
functions such as SIN() and COS() which produce one result for each particular
input value. However, an amendment to the 1993 revision of EEC 1131-3 allows
functions to also have VAR_IN_OUT parameters: see Section 3.11. This allows a
function to modify the value of variables that are passed as VAR_IN__OUT
parameters. For example, an array passed as a VARJNJ3UT parameter could be
modified within a function. A VAR_IN_OUT parameter is similar to a value
passed by reference in languages such as PASCAL.
A large number of different types of function are specified in the standard for
handling different types of data. Apart from trigonometric functions, there are
functions for handling strings of characters, processing dates and time, selecting
values and so on; Chapter 3 'Common elements' describes all the standard
functions.

The difference between functions and function blocks


It is important to understand the difference between functions and function blocks.
A function has no internal storage; it will always produce the same result for the
38 Programming industrial control systems using IEC1131-3

same set of input values every time it executes. A function only has a single
primary output.3
In contrast a function block may have numerous outputs. More significantly, a
function block will not necessarily produce the same set of output values if it
executes repeatedly with the same set of input values.
For example, consider a ramp function block that is used to increase the value
of an output steadily from, say, a lower value to a higher target value at a given
rate. Although the input values that define the ramp rate and final target value
remain unchanged, every time the ramp function block is run, the output value
will increase by a small amount until it reaches the desired target value. This is
because a function block is able to store values in both output variables and
internal storage.

Local and global variables

The standard permits variables to be declared within different software elements


such as programs and function blocks. Variables can be given meaningful names
and can contain different types of data. Variables are, by default, defined as local
and can only be accessed within the containing software element. Local variables
can be declared in a configuration, resource, program, function block or function.
Variables may also be defined as global. A global variable declared in a
program can be accessed from within all software elements within the program,
including within nested function blocks.
Similarly, global variables may also be defined at the resource level and
accessible to all software elements within the resource or at configuration level
where they are accessible by all software elements in the entire configuration.
Global variables typically provide a mechanism for transferring information and
data between programs or between function blocks residing within different
programs.

Directly represented variables

Memory locations within a PLC can be addressed directly using directly


represented variables. The format of this type of variable may be familiar to
anyone who has developed ladder programs and is in common use in many PLCs,

In the graphical languages, a function may have an additional input EN and output ENOfor explicit execution
control - see Section 3.28. Note also that the value of inputs that are declared as VAR_IN_OUT parameters
may be modified within the function.
Chapter 2IEC1131-3 concepts 39

for example %IW100, %Q75. Directly represented variables allow data to be


written to and read from known memory locations within a PLC.
The use of such variables is restricted; they can only be declared and accessed
within programs. The IEC has not permitted the use of directly represented
variables within function blocks because their use would result in software that
cannot be easily re-used.
It should be noted that the memory layout and, consequently, the addresses of
directly represented variables will generally change between different
applications. This means that software that uses a significant number of directly
addressed variables will be difficult to re-use in other applications.
Since all programs within a configuration can generally access data stored in
PLC memory, directly represented variables provide another way for programs to
exchange information.

Access paths

So far we have reviewed the elements of the IEC software model that go together
to form a configuration. We shall now look at the last feature of the model -
access paths that provide facilities for transferring data and information between
different EEC configurations. Each configuration may have a number of designated
named variables which can be accessed by other remote configurations.
The standard assumes that there is some form of communications facility
available to exchange data between different configurations but it is not specific
about what form the communications should take. For example, configurations
could communicate using a network based on Ethernet or Fieldbus or exchange
data via a proprietary backplane bus. The lower layer protocols that might be used
to provide communications facilities are beyond the scope of the IEC 1131-3
standard.
Access paths are provided by special variables declared using a construct
known as VAR__ACCESS. Such variables may be read, or written to, by other
remote configurations. In other words, the system designer can specify a set of
variables that formally define the interface that a configuration presents to all
other remote configurations.
Part 5 of the IEC 1131 standard defines communications function blocks that
provide services to read and write to access variables in remote configurations.
These are discussed in more detail in Chapter 12 'Communications'.
40 Programming industrial control systems using IEC1131-3

Controlflow

Generally configurations and resources are responsible for the control and
execution of elements within them. We will see that starting a configuration sets
off a chain reaction that will result in starting all software elements that exist
within it.
IEC 1131-3 states that external facilities (which are outside the scope of the
standard) that are provided for the operator interface', for 'programming, testing
and monitoring' or by the 'operating system' can be used to start and stop
configurations and resources. Normally a PLC programming station will provide
facilities to load and start various software elements including configurations and
resources. The actual mechanisms to implement these facilities are not specified in
the standard and will vary from one manufacturer's PLC to another.

The standard describes the behaviour for system start-up and shut-down.

Start-up
• When a configuration is started, all global variables are initialised and all
resources are then started.
• When a resource is started, all variables within the resource are initialised,
and all tasks are then enabled.
• Once tasks are enabled, all programs and function blocks assigned to the
tasks will start to execute.
Shut-down
• When a configuration is stopped, all contained resources are stopped.
• When a resource is stopped, all tasks are disabled with the result that
programs and function blocks cease to execute.

Note that programs do not always have control over the execution of all the
function blocks that they contain. Certain function blocks may be assigned to tasks
that cause them to execute periodically or in response to specific triggers. The
time when a function block executes may not necessarily be synchronised with the
time when its parent program executes.
Chapter 2IEC1131-3 concepts 41
Mapping the software model to real systems

Models are fine in theory but how can this software model be used in a real PLC
system? Mapping the various parts of this software model onto a real system is
very much an implementation issue.
Generally with small PLC systems with only one main processor (CPU) board,
the model will typically degenerate to have one configuration, one resource and
one program. The configuration contains all the software that defines the entire
behaviour of the PLC system. The resource represents the capabilities of the
processor board, while the program represents the signal processing part of the
software - in a conventional PLC this would represent the ladder program. In a
small PLC, the configuration will generally contain software to control a single
item of plant or a machine.

Configuration
Resource

ffV|$

Figure 2.3 Small PLC with a single processor

With larger systems with multiple processors the mapping becomes more
complex. The entire PLC may still be regarded as a single configuration. Each
processor board will generally represent a resource. Depending on the memory
and real-time multi-tasking capabilities of the processor, each resource may
support one or more programs. An example of a multi-processor PLC is shown in
Figure 2.4.
With large distributed systems, for example having many processors on a fast
network using a fibre optic Fieldbus, various clusters of processing nodes may be
regarded as one configuration or as a number of different configurations. How
clusters of processors are aggregated into configurations is very much an
implementation question. It will depend on how closely the various processors
have to work together and how configurations are arranged to control the major
items of plant.
42 Programming industrial control systems using IEC1131-3

Multi-processor PLC

w
Configuration
Resource Resource Resource
'rojjram Pfo$$r8ffi

Figure 2.4 Multi-processor PLC

Figure 2.5 shows a number of processing nodes that are able to communicate
via some form of high speed bus or network. Each node could be a single PLC
processor board.
Configurations A and B are formed from resources that exist in processing
nodes that are able to exchange data via a communications system. On condition
that the communications system is able to allow clusters of resources to 'see' a
common set of global and directly represented variables, configurations can be
formed from resources that need not necessarily be physically near each other or
even be in adjacent nodes in a network.
IEC 1131-3 provides language elements for defining and building
configurations but does not describe mechanisms for managing distributed
configurations. Clearly, this may become an important issue to be resolved in
future work on the standard.
Chapter 2 IEC 1131-3 concepts 43

Distributed Processing Nodes on a High Speed Network

i \
i \ ;

nSi
. \
( \

Configuratidn A \ / / Configuration b
Resource Resource Resource Resource Resource

m
1118
rflllll

Figure 2.5 Distributed processing

Mapping applications to IEC configurations

We have seen that IEC 1131-3 allows fairly complex configurations to be built
from a number of resources and programs. The concept of an application is not
defined in the DEC 1131-3 standard. We will discuss it here as it is an important
part of the software model, particularly when we consider the design of PLC
systems that are capable of controlling different units of plant or machinery.
Clearly the end product of any configured PLC system is the solution of an
industrial control problem.
A single solution, or more formally an application, must encompass all the
control requirements to start-up, control and shut-down a machine or plant unit.
The control will typically need to include the handling of physical sensors and
actuators, interlocks and control loops, scheduling of events, the interaction with
operator terminals and communications with remote devices. To achieve this an
application may require the interaction of a number of IEC programs loaded into
one or more resources.
Because DEC 1131-3 allows resources to be loaded and started independently,
there is no reason why a large PLC system cannot handle a number of independent
applications simultaneously. For example, a PLC system may be running several
44 Programming industrial control systems using IEC1131-3
applications that independently control a number of reactor vessels, steam
generators and compressors, while monitoring critical environmental conditions.
Each application can be loaded and started independently if loaded into different
resources.
The smallest application will always require one program. It is not feasible to
have totally independent applications running within one program. This is because
it is not possible to load, start and stop different parts of a program without
disturbing the whole program.

Figure 2.6 Mapping applications to resources

However, we will see that a program can itself handle parallel activities through
the use of tasks and parallel sequences within Sequential Function Charts.
Therefore, once initialised, and running, a program is able to control
independently different machines or units of plant. However remember that, if it is
necessary to modify the software in one part of the program, it may be necessary
to stop the whole program in order to re-load a new version.

Program organisation units

The IEC standard describes programs, function blocks and functions as program
organisation units or POUs. These software elements have the important
property that their behaviour can be used repeatedly in different parts of an
application. The behaviour and structure of a program organisation unit, such as a
function block, are defined by a type declaration. Copies of function blocks made
from a particular type are referred to as function block instances.
For example, a function block library may contain a Motor_Starter function
block. A programmer may decide to create, say, six copies of this block within a
Chapter 2IEC1131-3 concepts 45
program in order to control six different motors. Each copy will behave
independently of the others, but will exhibit the same functionality, because each
instance will use the same piece of code or algorithm. However, each copy will
have its own private data area. Similarly, multiple instances of a particular type of
program can be made within different resources. Multiple copies of particular
functions can be made within IEC languages.
Program organisation units encourage software re-use right through from the
macro level, with programs, through to re-use at a micro level, with function
blocks and functions. The type definition of a program organisation unit can be
regarded as a prototype from which instances with identical behaviour can be
created. Therefore, each instance of a POU, for example each function block, can
be assured to be error free provided that there are no errors in the associated type
definition.

Table 2.1 Program organisation units


POU type Replicated as: Comments
Program type Program instance Provides macro level re-use
of software, e.g. programs
for boiler control, conveyor
line management
Function block type Function block Allows complex through to
instance simple control strategies and
algorithms to be re-used, e.g.
PID control, ramp, filter, lag
Function type Function Used for commonly required
data manipulation functions,
e.g. COS, SIN, MAX,
CONCAT

Unlike other high level languages such as PASCAL, IEC 1131-3 specifically
forbids the use of recursion within POUs. For example, a function cannot call
itself within the code of its own declaration. This is clearly because recursive
software is difficult to test and its real-time performance is not predictable.
Programs and function blocks can be programmed using any of the IEC
lanaguages, i.e. Structured Text, Ladder Diagram, Function Block Diagram,
Instruction List or Sequential Function Chart. As functions have no retained state
information they can be programmed in all languages except Sequential Function
Chart.
46 Programming industrial control systems using IEC1131-3

Hierarchical design

One of the great strengths of the E C 1131-3 standard is the strong emphasis on
hierarchical design. We have seen that a program can be defined as a network of
function blocks and functions. Each function block is a copy or an instance of a
type definition.
A function block type definition may in turn be defined using instances of other
function block types and so on. This allows complex programs to be broken down
first into large function blocks representing major areas of functionality that in
turn can be broken down into smaller blocks representing more focused areas of
functionality. Ultimately, at the bottom level function blocks can either be defined
using functions and textual language statements or be supplied from standard
libraries.
Most IEC 1131-3 based systems will provide libraries containing a wide variety
of different function block types, e.g. PID, ramp, filter, lag. With some systems it
will also be possible to create project specific function block types, for example
for a proprietary control strategy for a particular type of plant. The same applies to
functions which can also be defined hierarchically. The program designer is able
to define new functions using language statements operators and other functions -
some may be taken from standard libraries, e.g. COS(), LOG().
The number of layers of hierarchical decomposition may vary between different
proprietary PLC systems. However, some ability for hierarchical decomposition is
essential to be in keeping with the spirit of IEC 1131-3.
In Figure 2.7 we can see an example of a program Al that is constructed from a
network of connected function block instances. Function block instance Rl has
behaviour defined by its type definition. Within the definition for function block
type R there is an instance XI of function block type X.

Note: IEC programming stations will usually provide facilities to allow the
designer to 'push-down' on any function block to reveal its type definition,
so that exploring the design hierarchy is generally fairly straightforward.
Chapter 2IEC1131-3 concepts 47
Program Instance A1 of Program Type A

Function Block
Instance R1 of Type

Function Block Type R


ifinition

Function Block
Instance X1 of Type X

unction Block Type X


Definition

Figure 2.7 Hierarchical software decomposition

2.2 Communications model

Internal communications

Various mechanisms are provided to enable information to be exchanged between


program organisation units, i.e. between programs, function blocks and functions.
Within a program, function blocks and functions can be interconnected
graphically to form a network. For example, values of variables can be passed
from function block outputs to one or more function block inputs. Functions can
also be used to modify values or produce derived values to be passed on to further
functions or function blocks.
48 Programming industrial control systems using IEC1131-3

Figure 2.8 Internal communications example

At the program level, program inputs can be used to pass data into internal
functions and function blocks from external variables. Generally program inputs
will be connected to variables that are associated with data coming from physical
devices such as PLC input sensors. Similarly program outputs which are driven
from outputs of function blocks and functions within the program are generally
connected to variables associated with physical output devices.
Figure 2.8 shows some examples of internal communication paths between
program organisation units. Program Progl is defined using three function blocks
FBI, FB2 and FB3 and a function MAX. The input parameter A of FB3 is
produced by taking the maximum value of parameters X and Y from function
blocks FBI and FB2 respectively, produced by the MAX function. Parameter C of
FB3 forms a feedback path passing data back to input Z of FB2. Program input
parameter P_IN allows data to be passed into the program, in this case to input W
of FBI. Output parameter P_OUT allows data to be passed out from the output B
of function block FB3.
In this example program input P_IN is configured to receive the current value of
directly represented variable %I10.3, which could be the memory location of the
value from a particular input sensor. Program output P__OUT is connected to
directly represented variable %Q12.1 that could, for example, be the memory
location for updating the value of a particular output device.
The Function Block Diagram language allows such data paths to be depicted
graphically. However, data can also be exchanged between POUs using Ladder
Diagram language and the textual languages, Structured Text and Instruction List.
Chapter 2IEC1131-3 concepts 49

Using globals
Global variables can also be used to exchange data between function blocks and
other POUs. Global variables can be defined at the configuration, resource or
program level. Globals are accessible to all program organisation units contained
within the parent entity in which they are declared. For example, a global variable
declared within a program is accessible to function blocks and functions within
that program. Global variables defined at the configuration level can be accessed
by all programs and function blocks within all resources contained in the
configuration.

CONFIGURATION

PROGRAM X PROGRAM Y
VARJEXTERNAL VAR__EXTERNAL
SetPoint :REAL: SetPoint :REAL;
END_VAR END VAR

VAR__GLOBAL
$-SetPoint :REAL;
END VAR

Figure 2.9 Internal communications using globals

Figure 2.9 depicts the use of a global variable to exchange data between
function blocks FB_1 and FB__2 in different programs. The global variable
SetPoint is declared within the Resource A. By declaring the SetPoint as an
external variable in both programs it is accessible by function blocks in both
programs. In this example, the output OUT of function block FB_1 is used to
update the global SetPoint. Function block FB__2 is able to read the current value
of SetPoint on its input SP.
Globals are a very flexible method of exchanging data between different
programs and function blocks. However because the data can be written and read
from global variables at various points within a program or function block,
programs developed using numerous global variables can be difficult to
50 Programming industrial control systems using IEC1131-3
understand. Data flows created by directly connecting inputs and outputs of
programs and function blocks can be depicted graphically and result in more
understandable and therefore more maintainable software.

External communications

Part 3 of the IEC 1131 standard only partly defines the external communications
facilities required to exchange data between programs in different configurations.
Nevertheless, Part 5 of IEC 1131 defines a family of communications function
blocks that can be used to exchange data over a network. The IEC 1131-5 function
blocks were primarily designed to operate over a MAP based network using the
Manufacturing Messaging Specification (MMS). However some manufacturers
may choose to provide similar function blocks to run over their own proprietary
networks.

CONFIGURATION C1 CONFIGURATION C2

PROGRAMY

'RCV

Figure 2 JO Using communications function blocks

An example of using the IEC 1131-5 communications function blocks is shown


in Figure 2.10. The figure depicts the transfer of data from an output of a function
block FB_1 in configuration Cl to the input of a function block FB__2 in a remote
configuration C2. A communications function block of type SEND is used to
provide network addressing facilities and control the data transfer to a
communications function block in a remote configuration, in this case to a
function block of type RCV, i.e. for receiving data.
The communications function blocks hide the complexity of handling network
data transfers and significantly simplify the design of networked applications.
Chapter 2IEC1131-3 concepts 51

Using access paths

Access variables provide a method in IEC 1131-3 for making particular variables
accessible from remote devices.

CONFIGURATION C1 CONFIGURATION C2

PROGRAM X

ISiHIll
i 1
sV

; VAR.ACCESS

SPX : X.SP_OUT REAL READ ONLY

v
Figure 2.11 External communications access paths

Communications function blocks defined in part 5 of the IEC 1131 standard


which is concerned with PLC communications can also be used to read and write
to ACCESS variables in a remote configuration. Figure 2.11 depicts the use of a
READ function block to update input SP of function block FB_2 from the value
of the variable read from a remote configuration Cl.
The value of this variable originates from the output OUT of function block
FB_1. The value of FBI.OUT is assigned to program X output parameter
SP_OUT. An ACCESS variable named SPX provides external 'read only' access
across the communications system to the value of program output X.SP_OUT.
The READ function block declared within program Y is only able to read the
value of X.SP__OUT using the alias SPX from within the configuration Cl.
The use of communications function blocks is discussed in more detail in
Chapter 12.
Access variables may also be read and written to by other devices on a
communications system, such as cell controllers and SCADA work stations.
52 Programming industrial control systems using IEC1131-3

Summary

We have seen that the IEC 1131-3 standard has adopted a well defined and formal
model for the design of software within a PLC system. The model has been
developed to cater for typical industrial applications of PLCs, including use in
direct digital control systems.

The IEC 1131-3 software model has a number of strengths:

• It is flexible and can be applied to a wide range of different PLC


architectures.
• It is suitable for both small scale systems and large distributed systems.
• It encourages hierarchical design decomposition.
• Software can be designed for re-use as program organisation units (POUs),
i.e. as programs, function blocks and functions.
• It provides facilities for exchanging information via communications
networks.
Chapter 3

Common elements

In this chapter we introduce many of the common programming elements that are
used with all of the IEC languages. An understanding of how elements such as
variables and data types are used is necessary before it is possible to go on to
develop programs using Structured Text or any of the other languages.
We will see that IEC 1131-3 provides an extensive range of common elements
that can be used both with the textual languages Structured Text (ST) and
Instruction List (EL), and with the graphical languages Function Block Diagram
(FBD) and Ladder Diagram (LD).
Note: The languages ST, IL, FBD and LD and the common elements discussed in
this chapter can be used within action blocks and transitions to construct
Sequential Function Charts (SFCs) for describing time- and event-driven
behaviour - for further information see Chapter 8, 'Sequential Function
Chart'.

In this chapter we will include descriptions of elements for:

• Naming software elements using identifiers, such as for variables;


• Declaring variables using standard types of data;
• Declaring variables from derived data types, structures and arrays of data;
• Establishing the default initial values for certain types of data;
• Ensuring that variables are initialised correctly.

We will then proceed to describe the main software building blocks of the
language, for which the IEC has the generic name program organisation units or
POUs. These are specifically functions, function blocks and programs.
Finally we will discuss how complete PLC system configurations can be
declared using resources, tasks and programs.
This chapter covers all common programming elements with the exception of
steps, transitions and actions which are discussed in Chapter 8, 'Sequential
Function Chart'.
54 Programming industrial control systems using IEC1131-3

3.1 Common programming elements


The IEC standard defines a large number of common features and elements that
apply to all the programming languages. The internal behaviour of program
organisation units, i.e. programs, function blocks and functions, can be described
using any one of five different languages. However, irrespective of the language
used, the variables and data types handled by all POUs are described using the
same common programming elements.
For example, input and output variables of a function block will be described in
the same terms whether the function block is programmed using Ladder Diagram,
Function Block Diagram or Instruction List.

3.2 Character set


To ensure that IEC programs can be readily ported to different systems, all textual
information should use a restricted set of letters, digits and characters. The
standard requires that only characters from standard ISO 646 "Basic code table"
are used. In practice, this character set is fairly generous and uses characters that
are in everyday use on a PC; there are no unusual symbols.
The standard provides alternatives where there are conflicts between pound sign
'£' and number or hash sign '#'. Where a national character set does not have a
vertical bar character T for character based graphics, an exclamation mark can be
used.
The use of special national characters, such as JE, is not permitted but such
letters could be included as a national extension to the standard.
Optionally lower case letters can be used but they are not significant in language
elements; for example, Heaterl and HEATER 1 are treated as identical. However
lower case letters are still significant if used to define printable strings such as
'Load Job la1. Upper and lower case letters can be used within comments.
Note: Identifiers are ease insensitive but language keywords are case sensitive and
should always be in uppercase.

3.3 Identifiers
Identifiers are used for naming different elements within the DEC languages, for
example for naming variables, new data types, function blocks and programs.
Chapter 3 Common elements 55
An identifier can be any string of letters, digits and underlines provided that:
(a) The first character is not a digit;
(b) There are not two or more underline characters together.
The standard provides options for supporting identifiers with lower case letters,
and identifiers with a leading underline character. There can be no embedded
spaces.
The following are acceptable identifiers when all options permitted by the
standard are supported:

W123_PV W12_3PV aTempl _PROG1 S

The following are illegal:


W123 PV W12 3PV ITempa Q%TY12 *

The standard states that at least the first six characters should be tested for
uniqueness. The following two identifiers may therefore be regarded as identical
on some systems:

A12345_XY A12345_GG

Consequently to avoid the possibility of ambiguous identifiers, when developing


software that may be ported to different PLC systems, always ensure that the first
six characters are unique.

3.4 Language keywords

Keywords are special words1 that are used within the IEC languages to define
different constructs or the start and end of particular software elements. For
example, a function type definition is framed with keywords FUNCTION and
ENDJUNCTION.
A full list of keywords used by the IEC 1131-3 standard is given in Appendix 1.
As a general rule, the use of identifiers that may be confused with language
keywords should be avoided even though many language compilers may be able to
distinguish between them from their position in the program. Avoid identifiers
such as:

Keywords should be in upper case characters. However, an amendment to the 1993 standard for the second
edition of IEC 1131-3 proposes that mixed case keywords should be allowed.
56 Programming industrial control systems using IEC1131-3
x
TYPE TRUE PROGRAM TASK RETURN STEP FUNCTION

The identifiers of IEC 1131-3 standard function blocks and functions as described
in Appendix 1 should be regarded as reserved, such as:

TON RS SIN COS *

3.5 Comments
Various length comments from short to multi-line can be inserted in any of the
IEC languages. With the exception of Instruction List language where there are
some restrictions, comments can be placed wherever it is acceptable to insert one
or more spaces.2 Comments are framed by the characters (* *).

Examples are:
(** Activate Pump *)
(*
(* Main turbine interlock logic *)

3.6 Datatypes
As PLCs are now being used in an ever widening range of industrial applications,
IEC 1131-3 recognises the need for handling a variety of different types of data.
The standard provides a comprehensive range of standard elementary data types
designed for dealing with values of typical industrial variables.
The range3 includes floating point (REAL)4 numbers for arithmetic
computations, integers for counts and identities, booleans for logic operations,
times and dates for timing and managing batch systems, strings for holding textual
information and bits, bytes and words for low level device operations.
The format of literals for each data type is also given in the following
descriptions. A literal is a constant that defines how a given value for a particular
data type is represented; e.g. integer literals are 12, 342, 0. Where the data type of
a literal may be ambiguous, the data type can be prefixed, e.g. INT#12, LINT#342.

^ Comments nested within comments will be regarded as an error.

3
There is no requirement for a PLC product to support all data types defined in IEC 1131-3.

Where an informal data type is given in the text, the formal IEC data type may sometimes be given in parentheses,
e.g.floatingpoint (REAL).
Chapter 3 Common elements 57

Integer

There are a number of different integer types defined. Integers are used for holding
values such as counts and identities, i.e. whole numbers. The 'unsigned' set of
integers should be used where there is no requirement to hold negative values and
where the increased positive range can be exploited. The type of integer used for a
particular variable will depend on the range of values that need to be stored in the
variable.

Table 3.1 Integer data types


IEC data type Description Bits Range
SINT Short integer 8 -128 to+127
INT Integer 16 -32768 to 32767
DINT Double integer 32 -2 31 to+2 31 -l
LINT Long integer 64 -2 63 to +263-l
USINT Unsigned short integer 8 0 to 255
UINT Unsigned integer 16 0 to 216-1
UDINT Unsigned double integer 32 0to2 3 2 -l
ULINT Unsigned long integer 64 0to2 6 4 -l

For example, if a variable is going to be used to count the number of items on a


conveyor belt, and the number can never exceed 100, then an integer of type SINT
would be suitable.
However, if an integer variable was going to be used to count pulses from a
shaft encoder where large positive and negative values can be expected, then a
long integer LINT would be recommended.

Integer literals

These can be represented using decimal values, e.g. -123 0 +463 23_123

As binary values, i.e. base 2 values, e.g. 2#1111_1 111 (255 decimal)
2#0000_1000 (8 decimal)

As octal, i.e. base 8 values, e.g. 8#377 (255 decimal)


8#020 (16 decimal)

As hexadecimal, i.e. base 16 values, e.g. 16#FF (255 decimal)


16#A0 (160 decimal)

Note: The standard allows the underline character '_' to be inserted into numeric
literals to aid readability; otherwise it has no significance.
55 Programming industrial control systems using IEC1131-3

Floatingpoint (REAL)

Table 3.2 Floating point (REAL) data types

Data type Description Bits Range

REAL Real numbers 32 ±10±38 Notel

LREAL Long real numbers 64 ±1O ±3O8 Note 2

Note 1: REAL values have a precision of 1 part in 2 23


Note 2: LREAL values have a precision of 1 part in 2 52

The data types REAL and LREAL are used to store a wide range of floating point
values, i.e. analogue values that can be either positive or negative, and can be
from very large to very small fractional values, e.g. 342.0032, -0.000123,
+1345000.0. The LREAL variable can store values of a much larger range and
higher precision than REAL.
The format is defined by standard IEC 559; this is identical to the commonly
used IEEE floating point number format.
Typical uses of REAL and LREAL data types are:

• Holding the values from analogue inputs, such as from pressure transducers,
thermocouples, strain gauges, tachometers;
• Within algorithms used for closed loop control such as PID;
• Driving analogue outputs such as valve position actuators.

REAL literals

These can be represented using normal decimals and can be distinguished from
integer literals by the presence of a decimal point. For large and very small values,
the exponential notation can be used giving, the power of ten by which the number
can be multiplied; either upper case 'E' or lower case 'e' can be used to denote the
ten's exponential value, e.g.

10.123,+12_123.21, -0.001298, -1.65E-10, 0.9E20, 0.3276e+14


Chapter 3 Common elements 59

Duration (TIME)

Datatype Description Sits Usage


TIME Time duration ^ote3 Storing the
duration of time
after an event

Note 3: The length and precision of this data type are implementation dependent.
The TIME data type is used to store durations, i.e. in days, hours, minutes,
seconds and milliseconds.

Typical uses of this data type are:

• Defining the duration of a process phase; for example, heat


treatment of materials, timing how long a moulding should be at a
given temperature.
• Defining time-outs for particular events to occur; for example,
timing when a valve should shut and raising an error condition if the
close condition does not occur within a specified duration.

TIME literals
There are two forms of time literals provided, short form and long form. The short
form is concise and fairly readable but where improved readability is required, the
long form can be used.
In both forms the following letters are used:
d = days, h = hours, m = minutes, s = seconds, ms = milliseconds

Short form examples:


T#12d3h3s defines 12 days, 3 hours and 3 seconds
T#3s56ms defines 3 seconds and 56 milliseconds

Long form examples:


TIME#6d_10m defines 6 days and 10 minutes
TIME#16d_5h_3m__4s defines 16 days, 5 hours, 3 minutes and 4 seconds

The last field of a time literal can also be given in a decimal format.
Examples:
T#12d3.5h defines 12 days, 3.5 hours
T#10.12s defines 10.12 seconds
60 Programming industrial control systems using IEC1131-3
The most significant unit in the time duration literal can 'overflow'. For example
the following are accepted:

T#61m5s - equivalent to T#lhlm5s


TME#25h_3m - equivalent to TIME#ld_lh_3m

Dates and times of day

Table 33 Dates and times of day data types

Data type Description Bits Usage


DATE Calendar date Note 4 Storing calendar
dates
TIME_OF_DAY Time of day Note 4 Storing times of the
or TOD day, i.e. real time
clock
DATE_AND_TIME Date and time of day Note 4 Storing the date
orDT and the time of day

Note 4: The length of this data type is implementation dependent.

These date and time data types have a wide range of uses particularly in batch
oriented applications.
Typical usage of dates and times of day are:

• Recording the date and time of events and alarm conditions for fault
diagnosis and process audit purposes.
• Controlling when certain events occur during the day, the week or
even the year. For example, a reactor could be pre-heated
automatically early every Monday morning ready for the weekly
batch run.
• Recording when power fails and power resumes to calculate the
system down-time.

Time of day and date literals

There are two forms of time of day and date literals, short form and long form.
The short form is concise and fairly readable but where improved readability is
required, the long form can be used.
Chapter 3 Common elements 61
Table 3.4 Dates and times of day literal prefixes

Data type Short form Long form


DATE D# DATE#
TIMEJDFJDAY TOD# TIME_OF_DAY#
DATE_AND_TIME DT# DATE^AND_TME#

Examples of DATE literals are:


D#1994-06-10 - 10th June 1994
d#1995-01-13 - 13th January 1995
DATE#200Q-l(M5 - 15th October 2000

Examples ofTIME_OF_DAY literals are:


TOD#10:10:30 - 10 o'clock, 10 minutes and 30 seconds
TOD#23:59:59 - 1 second to midnight
TIME_OF_DAY#05:00:00.56 - 0.56 seconds past 5

Examples ofDATE_AND_TIME literals are:


DT#1993-06-12-15:36:55.40 - 12th June 1993, at 15 hours, 36 minutes and
55.4 seconds
DATE_AND_TIME#1995-02-01-12:00:00 - midday on 1st February 1995

Strings

Datatype Description Bits Usage


STRING Character strings Note 5 Storing textual
information

Note 5: The method used to store this data type is implementation dependent.
Character strings can be used to hold textual information which may consist
of both printable and non-printable characters.

Typical uses are:

• Holding batch identities, e.g. 7OB_X32A3';


• Messages for operator displays, e.g. 'Starting Vessel Purge';
• Messages to be sent via communications drivers to other devices.
62 Programming industrial control systems using IEC1131-3

STRING literals

A string literal defines a number of printable and non-printable characters. All


string literals should be framed using a single quote character ('). Non-printable
characters can be inserted by prefixing the hexadecimal value of the character
(given as two hexadecimal digits) with a dollar $. There are also a number of
reserved letters which can be used after the dollar to denote commonly used
control characters. Techniques for embedding control characters are shown in the
following table:

Table 3.5 Embedding control characters within strings

Code Interpretation
$$ Single dollar sign
$' Single quote character
$L or $1 A line feed character
$N or $n A new line character
$P or $p Form feed, new page
$R or $r Carriage return character
$T or $t Tabulation, i.e. tab character

Examples of string literals are:


'Batch number AX45_^65'
'End of report $N' — embedded line feed
'$01$02$10> — 3 characters with decimal codes 1, 2 and 16
" — an empty or null string

Bit strings

Table 3.6 Bit string data types

Data type Description Bits Usage


BOOL Bit string of 1 bit 1 Digital, logical
states
BYTE Bit string of 8 bits 8 Binary information
WORD Bit string of 16 bits 16
DWORD Bit string of 32 bits 32 •I M

LWORD Bit string of 64 bits 64 H it


Chapter 3Common elements 63
A range of bit string variables is provided for storing binary information. These
data types may be required when setting various status bits to be sent to remote
devices and instruments or when handling low level interfaces to the PLC
hardware.

Boolean

The Boolean data type is used to define the state of boolean variables, such as
those associated with digital inputs and outputs.

IEC data type Description


BOOL Has two states, FALSE
equivalent to 0, and
TRUE equivalent to 1.

A boolean variable can be assigned logical values FALSE or TRUE. Alternatively


the logical values 0 and 1 can be used.
Boolean variables are typically used in interlock or combinatorial logic and for
holding the states of devices, for example whether a pump is 'ON' or 'OFF'.
Single bits within the PLC memory are normally defined as variables of type
BOOL.

Boolean literals
FALSE and TRUE can be used to define the literal values of booleans and are
treated as reserved language keywords.

FALSE 0
TRUE 1

Bit string literals


Bit string literals are used to define the contents of bit strings having multiple bits.
The same representation as defined for integers, e.g. 146, 2#1101, 16#FFAC, can
be used.

3.7 Use of generic data types

The elementary data types that have similar properties are organised in a hierarchy
as shown in Figure 3.1.
64 Programming industrial control systems using IEC1131-3
Generic data types that start with the prefix ANY_ can be used for describing
variables in function and function blocks where there is support for overloaded
inputs and outputs. Overloaded refers to the ability of a variable to be used for
different types of data.
For example, a function AVE() for calculating the average value of two inputs
could have inputs and an output all of data type ANYJNUM. This would imply
that the function can be used with any data type from the hierarchy that comes
under the generic data type ANYJNUM. In other words AVE could be used with
different types of numeric data, such as decimal values (REAL), or integers (INT,
UINT). A number of the IEC standard functions such as MAX() are described
using generic data types indicating that the same function can be used for a variety
of different types of data.

ANY_DERIVED

ANY_ELEMENTARY

ANY_MAGNITUDE

t
- ANY_NUM

LREAL

REAL

t
- ANYJNT

LINT, DINT, INT, SINT

ULINT, UDINT, UNIT, USINT


L
TIME

- ANY_BIT

LWORD, DWORD, WORD, BYTE, BOOL

- ANY_STRING

j - STRING

LwSTRING

L- ANY_DATE

I- DATE_AND_TIME

L D A T E , TIME_OF_DAY

Figure 3.1 Hierarchy of elementary data types

Note 1: A PLC manufacturer should list the functions that support data type
overloading. User-defined functions cannot be overloaded, i.e. cannot be
defined using the ANY_... data types. Generic data types ANY_... are not
EEC keywords.
Note 2: The standard requires that all inputs and outputs for an overloaded function
must be of the same data type. This should always be checked by the
language compiler.
Note 3: All subranges and array subscripts are data types ANY_INT.
Note 4: The generic type of a directly derived type will be the same as the generic
type of the elementary type from which it was derived.
Chapter 3 Common elements 65

3.8 Initial values of elementary data types

An important principle in the DEC standard is that all variables have a known
initial value. By default all variables are initialised to zero or in the case of strings
to an empty null string. Dates default to the value of D#0001-01-01.
We will see that these default initial values can be overridden when a variable
of a particular data type is declared.

3.9 Derived data types

To assist program readability and ensure that data are used consistently, new data
types can be defined from the elementary data types. A new data type is declared
by framing the definition with TYPE and END_TYPE.
For example, all values for pressures could be held in a derived data type called
PRESSURE which is based on the REAL data type. The type can be declared as:

TYPE
PRESSURE : REAL;
END__TYPE ;

Structured data types


New composite data types can be derived by defining a structure from existing
data types. A structure is declared by framing the definition with STRUCT and
ENDJSTRUCT. Each element of the composite data can be given a meaningful
name.
For example, the data from a pressure sensor may consist of the following
information:

(a) The current pressure as an analogue value;


(b) The status of the device, i.e. operating or faulty;
(c) The calibration date;
(d) The maximum safe operating value;
(e) The number of alarms in the current operating period.
This can all be defined in a single structure as a new data type
PRESSUREJSENSOR:
66 Programming industrial control systems using IEC1131-3
TYPE PRESSURE__SENSOR:
STRUCT
INPUT: PRESSURE;
STATUS: BOOL;
CALIBRATION: DATE;
HIGHJLIMIT: REAL;
ALARM__COUNT: INT;
END_STRUCT;
END TYPE

Enumerated data types

Enumerated data types allow different states of a value to be given different


names.
For example, all devices within a particular system may have a number of
different operational modes. A data type suitable for variables holding device
modes would be:

TYPE DEVICE_MODE:
(INITIALISING,RUNNING,STANDBY,FAULTY);
END_TYPE

In this case, variables of type DEVICE_MODE can only be assigned values from
the list of named states, i.e. as given in the enumerated list5.
To avoid ambiguities when using enumerated variables sharing identical
enumerated literals, the data type of a particular enumeration literal can be
specified using a prefix in the form *<data type>#\ Examples are:

TYPE
VALVE__MODE: (OPEN, SHUT, FAULT);
PUMP_MODE: (RUNNING, OFF, FAULT) ;
END__TYPE;
IF AX100 = PUMP_MODE#FAULT THEN
XV23 = VALVE_MODE#OPEN;

^The standard does not permit a value to be associated with a named state or for enumerated values to be used to
index arrays.
Chapter 3 Common elements 67
Sub-range data types
There is often a requirement to restrict the range of values that can be assigned to
integer types of variable. A sub-range can be specified that limits the value range.
For example, variables used to store voltages for controlling a set of DC motors
may be restricted to values +12 volts and -6 volts. A suitable data type for
MOTOR_VOLTS would be:

TYPE
MOTOR_VOLTS: INT(-6..+12);
END_TYPE

It is expected that the programming station or compiler will provide range checks
that ensure the variables of sub-range data types are only assigned values inside
the range.

Array data types


In many PLC applications there is a requirement for variables that can store arrays
of values. These are sometimes referred to as multi-element variables. An array
can consist of multiple elementary data types or other derived data types.
For example, consider a variable required to hold a set of operating pressures
for various points around a steam vessel. Suitable data types would be:

TYPE VESSEL_PRESS_DATA :
ARRAY[1. .2 0] OF PRESSURE;
END_TYPE

TYPE VESSEL_MATRIX :
ARRAY [ 1. . 3 , 1. . 4 ] OF VESSEL__PRESS_DATA ;
END_TYPE
Note: PRESSURE is also a derived type. VESSEL_MATRIX is a two dimensional
array of 3 by 4 elements where each element is itself a
VESSEL_PRESS_DATA array.

The number of array dimensions and depth of array nesting that is supported, i.e.
number of levels at which arrays can exist within other arrays, is not defined in the
standard and will vary between different products.
In Structured Text, the value of an array subscript may be given as an integer
literal or any expression that produces an integer result.
68 Programming industrial control systems using IEC1131-3

3.10 Default initial values

All derived data types can be assigned new initial values that will override the
defaults of the elementary data types. The new default value is defined with the
type definition.

Examples:

TYPE PRESSURE: REAL := 1.0; (* Default 1 bar *)


END_TYPE

TYPE PRESSURE_SENSOR:
STRUCT
INPUT: PRESSURE := 2.0; (* Override default *)
STATUS: BOOL := 0; (* Default 0 *)
CALIBRATION:
DATE := DT#1994-01-10; (* Install Date*)
HIGH_LIMIT: REAL := 30.0; (* Default limit*);
ALARM_COUNT: INT := 0; (* No alarms *)
END_STRUCT;
END_TYPE

TYPE DEVICE_MODE:
(INITIALISING, RUNNING, STANDBY, FAULTY )
:= STANDBY; (* Default enumerated value *)
END_TYPE
In array initialisation, each element in the array can be assigned a value. In the
following example the first ten elements are assigned the value 1.1, the next five
the value 1.3 and the last five the value 1.7.
VAR
VESSEL_PRESS_DATA: ARRAY[1..20] OF PRESSURE
:= [10(1.1), 5(1.3), 5(1.7)];
END_VAR

It is possible to define new defaults for structured data types that are used in new
derived data types.

Example:

TYPE GAS_PRESSURE_SENSOR :
PRESSURE_SENSOR ( PRESSURE := 4 . 0 ,
HIGH__LIMIT := 4 0 . 0 ) ;
END_TYPE

GASJPRESSUREJSENSOR is a data type derived from PRESSUREJSENSOR


with different default initialisation values for PRESSURE and HIGH LIMIT.
Chapter 3 Common elements 69

3-11 Variables

Variables can be declared at the beginning of each definition for the different
program organisation units (POUs), i.e. programs, function blocks and functions.
There are different categories of variables depending on whether the variable is
used as an input parameter, as an output parameter, or internally within the POU.
Note that input, output and input/output variables provide the external interfaces
of POUs such as function blocks.
Global variables are a category of variable that can be declared in programs,
resources and configurations. By declaring variables within a POU to be
'external', it is possible to access the value of global variables declared outside the
POU. External variables declared in function blocks can reference any global
variables defined within a configuration, resource or program that contains the
function block.
A list of one or more variables in each category is declared using a particular
keyword; the end of each list is terminated with the keyword ENDJVAR. Within
each list, each variable identifier is followed by its data type which may be
elementary or derived.
If there are a number of variables of the same data type, a list of identifiers can
be given as a list separated by commas.

Example:

A,B,C : REAL;
IN1,IN2 : INT;

i.e. three variables of type REAL, and two of type INT.

Internal variables

A list of variables used within a POU (i.e. local variables) is declared using the
keyword VAR.

Example:

VAR
AVE_SPEED : REAL;
Inhibit : BOOL;
END_VAR

i.e. one internal variable of type REAL and one of type BOOL.
70 Programming industrial control systems using IEC1131-3

Input variables

A list of variables, which act as input parameters to a POU and are supplied values
from external sources, is declared using keyword VARJNPUT. Input variables
will be required for programs, function blocks and functions.

Example:
VAR_INPUT
SetPoint : REAL;
Max_Count: USINT;
END__VAR
i.e. two input variables (otherwise known as input parameters) of type floating
point (REAL) and unsigned short integer (USINT).

Output variables

A list of variables, which act as output parameters to a POU and provide values to
be written to external variables, is declared using keyword VAR_OUTPUT.
Output variables will be required for programs and function blocks but not
functions.

Example:
VAR_OUTPUT
Message : STRING(IO);
Status : BOOL;
END_VAR
This defines two output variables (otherwise known as output parameters), one a
string of 10 characters and the other boolean.

Input/output variables

A list of variables, which act both as input and output parameters and can be
modified within the POU, is declared using keyword VARJN_OUT. These
variables receive values from external variables but can be modified within the
POU. Externally the value of these variables is accessible in the same way as other
output parameters. However, it is important to note that the value of an
input/output variable is stored in a variable that is external to the POU.
Chapter 3 Common elements 71

A typical use of this category Variable defined outside


of variable is for controlling the the function block Jnst_A
mode of a function block. r _\.
Consider a function block with an
input/output variable called
AUTO. Assume that the function
block AUTO parameter is
connected to an external variable Input/Output Variable
, ,4_T , ,^^^ ™ , n . modified within the function
MAINJMODE. The value of the block body
initial mode, e.g. INIT, can be
written to the MAJN_MODE variable by software outside the function block.
When the function block executes, it has access to the AUTO variable which, in
this case, could cause the function block to initialise. The function block can
signal the change of mode by writing, say, READY directly to the AUTO
parameter. The new mode is accessible either at the function block output AUTO
or from the source variable MAJN_MODE.
Input/output variables behave in a manner that is similar to the 'call by
reference' feature found in languages such as PASCAL.
When large multi-element variables are passed into a program organisation unit
such as a function block, with some implementations it may be more efficient to
declare parameters as VAR_IN_OUT rather than using VARJNPUT or
VARJ3UTPUT. VARJN_OUT only requires that the address of the variable is
passed, rather than copying of the whole variable.

Note: In Function Block Diagram and Ladder Diagram graphical languages, a


VARJNJDUT variable is depicted as being an input and an output
connected by a horizontal line.

Example:
TYPE MODE_LIST :
( INIT, READY, RUNNING, STOPPED ) ;
ENDJTYPE
VAR__IN_OUT
AUTO : MODE_LIST;
END_VAR

Global variables

Global variables can be declared at configuration, resource or program level. They


can be accessed by any POU that exists within the configuration, resource or
program in which the global is declared using external variables.
72 Programming industrial control systems using IEC1131-3
For example, consider a configuration LINE__1 that contains a program called
PRODUCTS. Inside the program is a function block called RampJSpeed. A
global, such as Line_Speed declared at the configuration level, can be accessed
within function block Ramp_Speed by declaring an external variable that
references Line_Speed.
Generally, globals and externals are used to provide access to key process
values within programs and function blocks.

Example:

VAR__GLOBAL
Line__Speed : LREAL;
Job_Number : INT;
END__VAR

This defines two global variables, one a double precision floating point (LREAL)
and one a 16 bit integer.

External variables

External variables can be declared within POUs and provide access to global
variables defined at the configuration, resource and program level.

Example:

VAR__EXTERNAL
Line__Speed : LREAL;
Job_Number : INT;
END_VAR

i.e. declaration of external variables for referencing two global variables of type
double precision floating point (LREAL) and integer.

Temporary variables

The EEC 1131-3 amendment allows temporary variables to be declared within


POUs using the VARJTEMP construct. Such variables will be placed in a
temporary memory area, e.g. such as on a stack, which is cleared when the POU
invocation terminates.
Chapter 3 Common elements 73
Example:

VAR_TEMP
RESULT : REAL;
END_VAR;
RESULT := AF18 * XV23 * XV767 + 54.2;
OUTl := SQRT(RESULT);

Directly represented variables

This category of variable allows PLC memory locations6 to be referenced directly,


i.e. without using an identifier. All identities of directly represented variables start
with a % character. This is followed by a one or two letter code that defines
whether the memory location is associated with inputs, outputs or internal
memory, and the type of memory organisation, e.g. as bits, bytes or words.
PLC memory is considered to be organised into three major regions: (I) input
locations for receiving values from channels such as analogue and digital input
modules, (Q) output locations for values to be sent on to output channels, and (M)
internal memory locations for holding intermediate values.

Table 3.7 Directly represented variable codes

First letter code Interpretation


I Input memory location
Q Output memory location
M Internal memory

Second letter code Interpretation


X Bit
B Byte (8 bits)
W Word (16 bits)
D Double word (32 bits)
L Long word (64 bits)

Note: If the second letter code is not given, the memory organisation is assumed to
be as bits.

An amendment to the IEC1131-3 1993 edition allows directly represented variables to be used within program
and function block type definitions. However, such type definitions may not be re-usable on other systems.
74 Programming industrial control systems using IEC1131-3
The last part of the identity consists of one or more numeric fields separated by
periods (.) to represent the memory location. The way this is interpreted will vary
from product to product and is not defined in the standard. However, the numeric
fields will be regarded as forming a hierarchical address which can be used to
identify hardware sub-divisions, modules, channels etc.

Examples:
%I100 (* Input memory bit 100 *)
%IX100 (* Ditto *)
%IW122 (* Input memory word 122 *)
%IW1O.1.21 (* This could represent - *)
(* rack 10, module 1, channel 21 *)
%QL1OO (* Output memory long word 100 *)
%MW132 (* Memory location word 132 *)

Variable attributes

Variables can also have the following additional attributes: RETAIN,


CONSTANT and AT.

RETAIN
This indicates that the values of a list of variables will be retained from when the
PLC loses power, to when the power is returned and the PLC warm starts.
Note: With some implementations of PLCs based on IEC 1131-3 , the default is
to retain the value of all variables during power failure.
Example:
(* Retain the speed profile array *)
(* and maximum speed on warm starts *)
VARJDUT RETAIN
Speed_Profile: ARRAY[1..4] OF REAL;
Max__Speed REAL;
END_VAR

CONSTANT
This attribute indicates that the values of a list of variables cannot be modified.
For example, the variable may be initialised with the value of a critical tuning
parameter and therefore should not be changed while the program is running. The
programming station or compiler should check that the value of such variables
cannot be changed. This attribute cannot be used with external variables.7

^It may be very difficult for a compiler to check for illegal write accesses toaPOU in which a CONSTANT is made
available via a VAR_EXTERNAL.
Chapter 3 Common elements 75

Example:

(* Define Startup speed and gear ratio as


constants*)
VAR CONSTANT
StartUp_Speed: REAL := 12.3; (* Metres / sec **)
GearJRatio: SINT := 12;
END VAR

Note: The use of VAR_EXTERNAL CONSTANT indicates that the constant


value has been declared as a global value externally from the current POU.

AT
This is used to fix the PLC memory location for any particular variable. For
example, a variable INPUT_1 may be fixed at input memory location 100 where
the value of channel 1 is stored by the PLC hardware input multiplexor. The AT
attribute can only be used with global variables and variables declared in
programs. Note that variables that do not have the AT attribute, are automatically
assigned a memory location by the programming station or compiler.

Example:

(* Define scan data array to start at input memory *)


(* location word 10, and digital outputs at *)
(* output memory bit 120 *)
VAR
SCAN_DATA AT %IW10: ARRAY[1..8] OF SINT;
DIG_OUTPUTS AT %QX120: ARRAY[0..15] OF BOOL;
END VAR

It is also possible to use the AT attribute to declare that particular data types exist
in certain memory locations.

Example:

(* Declare that an integer exists at input memory


100 and a real exists at output memory 210 *)
VAR
AT %IW100: INT;
AT %QD210: REAL;
END VAR
76 Programming industrial control systems using IEC1131-3
Access variables

A list of variables can be declared that provide references by which remote


devices and other remote IEC 1131-3 based programs can access certain variables.
Access variables provide what the IEC standard calls 'access paths' to named
variables. Access variables can only reference the following types of variable:
• Input or output variables of a program;
• Global variables;
• Directly represented variables.
Access variables can reference multi-element data type variables, such as arrays,
or a selected element of a multi-element data type variable.
Access variables can have attributes READ_ONLY to indicate that the remote
device can only read the referenced variable, or READ_WRITE to indicate that
the variable can be both read and written.

Example:

The following access variables provide remote access paths to three variables,
LINE1.START_UP, an input parameter of a program called LINE1, SPEED
and LENGTH which are global variables. Communications facilities, which
are outside the scope of the IEC 1131-3 standard, are able to use the access
paths LINE_START_UP, LINE^SPEED and GOOD_CABLE to read and
write to LINE.START_UP and SPEED, and read LENGTH.

VAR__ACCESS
LINE__START_UP : LINEl. START_UP : BOOL READ_WRITE ;
LINE_SPEED: SPEED: REAL READ_WRITE;
GOOD_CABLE: LENGTH: INT READ_ONLY;
END_VAR

3.12 Variable initialisation


An initial value for a variable can be given in the variable declaration. This will
override the default initial value defined for the data type. Since external variables
reference global variables they cannot be given initial values.
Chapter 3 Common elements 77
Examples:

VAR
ProcessJRuns : INT := 10; (*Initial runs = 10 *)
Max__Temp : REAL := 350.0; (^Initial value 350.0 *)
END_VAR

VAR
(* Initialise word at input memory *)
(* location 100 to binary 1001 *)
AT %I100: WORD := 2#0000_1001;
END__VAR

VAR_OUTPUT
(* Initial operator message *)
Message: STRING(12) := 'Operational';
(* Set-up Speed profile *)
Speeds: ARRAY[1..4] OF REAL :=
10.1, 2(20.5), 33.1;
ENDJVAR

In the following example we use the data type PRESSURE_SENSOR discussed in


Section 3.9 'Derived data types'. The example shows how selected elements
within a structured variable can be given initial values. These can override default
initial values defined in the data type declaration.

VAR__GLOBAL
SENSOR1: PRESSURE_SENSOR(PRESSURE := 4.0,
HIGH_LIMIT := 50.0 ) ;
END VAR

3.13 FUNCTIONS

We will now consider the common elements provided to define new types of
program organisation units; we will start with functions. A function is a re-usable
software element that, when executed with a particular set of input values, always
produces a primary value as a result.
Examples are trigonometric functions such as SIN (sine) and COS (cosine),
mathematical functions such as SQRT (square root) and text string handling
functions such as INSERT (inserts a text string into another text string). Functions
can be used in any of the programming languages, for example:

Max_Diff_Press := MAX( ABS(PresslA-PresslB),


ABS(Press2A-Press2B));
78 Programming industrial control systems using IEC1131-3
Press"! A *
SUB •••••MB ABS
PressiB,

MAX Max_Diff_Press
Press2A,— —
SUB ABS
Press2B._

Figure 3.2 Example using functions in ST and FBD

In this example, the maximum differential pressure Max_Diff_Press is calculated


from the maximum value of two pressure differences. The same functions are
used in the Structured Text language and in the Function Block Diagram. The
SUB function is equivalent to subtraction. The ABS function calculates the
absolute value, i.e. any negative value is converted into a positive value. The
MAX function returns the maximum value of the two inputs.
The important characteristic of all functions is that they cannot store values
within internal variables; this contrasts with function blocks that can store values
in internal and output variables.
There is a wide range of standard functions which are described in the following
sections. Additional user defined functions can be declared using any of the DEC
languages. Standard and user defined functions can be used within declarations of
other functions, function blocks and programs.
In the following function definitions, where a function has multiple inputs of
different data types, a diagram of a function may be shown to clarify how it is
used in the graphical languages.

3.14 Function type declarations

New function types can be declared by framing the declaration with the text
FUNCTION and ENDJFUNCTION.
Consider the following example:

FUNCTION AVE_REAL : REAL


VAR_INPUT
INPUT1, INPUT2 : REAL;
END_VAR
AVE_REAL := (INPUT1 + INPUT2)/2;
END__FUNCTION
Chapter 3 Common elements 79
The data type of the result, in this case REAL, is given following the function
name. The assignment statement to AVE_REAL creates the value returned by the
function.
A function definition contains a list of input and internal variable declarations
followed by software that describes the algorithm. This software can be described
using one of the following IEC languages :

Structured Text, Function Block Diagram,


Ladder Diagram, Instruction List

The function examples given in this chapter use Structured Text.


An amendment for the second edition of IEC 1131-3 allows inputs to functions
to be declared as type VAR_IN_OUT. This implies that variables that are passed
as VAR_JN_OUT may be modified within the function body.

Example:

FUNCTION INCREMENT : BOOL


VAR_IN_OUT
COUNT : INT;
END__VAR
VAR__INPUT
MAX : INT;
END_VAR

COUNT := COUNT + 1;
INCREMENT := (COUNT >= MAX);
END_FUNCTION

(* Example using INCREMENT() function *)


JOBCOUNT : INT;
MaxFlag : BOOL := FALSE;

IF INCREMENT(COUNT := JOBCOUNT,MAX := 100) THEN


MaxFlag := TRUE;
END_IF;

The value of JobCount is incremented within the INCREMENT function body


until the value reaches 100.
80 Programming industrial control systems using IEC1131-3

3.15 Functions for overloaded data types

In Section 3.7 we discussed the hierarchy of elementary IEC data types and
associated generic data types such as ANY_NUM. The PLC manufacturer may
provide functions that can be used with a variety of different and yet related data
types. This avoids the need to have a large number of similar functions each one
for a specific data type.
For example, the standard function SQRT (square root) can be used with input
values of type ANY_REAL. From Figure 3.1, ANY_REAL is shown as a generic
data type which is applicable to both variables of type REAL and LREAL.
The function SQRT is said to support overloaded data type variables. The
following Structured Text statements demonstrate how the SQRT function can be
used with the two data types.

VAR
Small_Num, Small_sqrt : REAL;
Large_Num/ Large_sqrt : LREAL;
END_VAR;
Small_sqrt := SQRT(Small_Num);
Large_sqrt := SQRT(Large_Num);

Generally the data type of the output of overloaded functions is the same as the
input(s). In the previous example, notice that the result of the function is being
assigned to the same type as the input parameter.
The data type conversion functions that are discussed in Section 3.17 are an
exception to this general rule.
The IEC 1131-3 standard states that the provision of overloaded functions is an
optional feature. In practice designing a compiler to handle overloaded variables
can be more complex. For PLC products that do not support this option, standard
functions for specific data types should adopt the naming convention of appending
an underscore '_' and the data type name to the function name.
For example, two forms of the SQRT function, SQRT_REAL and
SQRTJUREAL, should be provided for REAL and LREAL data types
respectively.

3.16 Invoking functions in Structured Text


When a function is called (i.e. invoked) the function parameter values can be
assigned literals, values or expressions. When a function is called, the parameter
Chapter 3 Common elements 81
names come from the identifiers given to the input variables that are declared in
the function type definition.
The following Structured Text statements demonstrate how the AVE_REAL
function could be called.

VAR
INI : REAL := 10.0; (* Initialise variables *)
IN2 : REAL := 20.0;
IN3 : REAL := 4.0;
AVE1, AVE2, AVE3 : REAL := 0.0;
END_VAR

AVE1 := AVE_REAL( INPUT1 := INI,


INPUT2 := IN2);(* AVE1 assigned to 15.0*)
AVE2 := AVE_REAL(
INPUT2 := IN3 + 4 . 0 ,
INPUT1 := 6.0) ; (* AVE2 assigned to 7.0 *)
AVE3 := AVE_REAL(
INPUT1 := 4.0 );(* AVE3 assigned to 2.0*)

Note 1: In the AVE2 assignment, the order of parameters is reversed. The standard
allows parameter names to be given in any order.
Note 2: In the AVE3 assignment, one of the parameters is not used; in this case the
unused input parameter will take the default value, i.e. 0.0. Remember that
all variables of REAL data type will default to 0.0 unless initialised with a
particular value.

Many of the IEC 1131-3 standard functions do not have formal parameter names,
in which case the function is called with a list of values. This reduces the need for
unnecessary text where parameter names would be superfluous.

Example:

VAR
ALARM_MES SAGE : STRING(10);
END_VAR
VAR_EXTERNAL
REPORT: STRING(15);
END__VAR

REPORT := CONCAT('ALARM',ALARM_MESSAGE);

Note 3: CONCAT is one of the standard string functions that is used to


concatenate, i.e. join text strings together. It does not have parameter
names.
82 Programming industrial control systems using IEC1131-3

3.17 Data type conversion functions

The IEC 1131-3 languages require strict data type checking. For example, it is not
possible to assign the value of a type REAL variable directly to an input of a
function of type INT. The programming station or language compiler must always
ensure that data types are used consistently. For situations where it is necessary to
perform calculations, comparisons and other operations with different data types,
the standard defines a wide range of data type conversion functions. The naming
convention for such functions is :

< I n p u t d a t a type>_JTO__<Output d a t a type>

Examples:
VAR
COUNT : INT;
RAMP_RATE : REAL;
STATUS : WORD;
DISPLAY_VAL : STRING(16);
END__VAR

(* Convert integer to real *)


RAMP_RATE : = INT__TO_REAL (
• COUNT ) ;

(* Convert integer to WORD *)


STATUS := INT_TO_WORD( COUNT ) ;

(* Convert a floating point REAL to a


* string using the normal numeric representation
*)
DISPLAY_VAL : = REAL__TO_STRING ( RAMP_RATE );

Floating point (REAL) numbers are converted into integers by rounding the
decimal (fractional) portion to the nearest integer. Examples are: 2.6 is rounded to
3, -1.5 is rounded to -2; this is in accordance with IEC 559.
When converting to a string of characters (i.e. STRING) data type, the value
will be converted into its normal representation, e.g. integer 12 will be converted
to string value '12', a floating point value 154.001 will be converted to string
value 4 154.001'.
Chapter 3 Common elements 83
Converting binary coded decimal (BCD)

A special set of data conversion functions is also defined for converting binary
coded decimal (BCD) values held in bit string data types BYTE, WORD,
DWORD and LWORD to integer data types SINT, INT and DINT and vice versa.

Example:
VAR
VALUE : INT;
BCD_VALUE :WORD := 2#0001_0100_0010; (* BCD 142 *)
END__VAR
(* Convert BCD value to integer *)
VALUE := BCD_TO__INT( BCD_VALUE ) ; (* value = 142 *)

Truncating floating point (REAL) values

A standard function called TRUNC is provided to convert any floating point


number to any integer. This function can convert a value of generic data type
ANY_REAL to return a value of generic data type ANY_NUM: see Section 3.7
for details on generic data types.
The TRUNC function removes the decimal (fractional) part of the floating point
value to produce an integer equivalent to the whole number portion of the
decimal.

Example:
VAR
Shaft_rpm : LREAL;
Pulse__Count : INT;
ENDJVAR

Shaft_rpm : = 3200.45;
(* Truncate to produce Pulse Count of 32 00 *)
Pulse_Count := TRUNC(Shaft_rpm);

Error detection

There can be situations while running a program where data type conversion may
not yield sensible values.
For example, when converting a REAL to a SINT, a value that is too large to be
stored in a SINT (which is only 8 bits) may be produced. In these situations, the
PLC should provide run-time error detection and reporting facilities. However,
note that such facilities are not currently defined in the standard.
84 Programming industrial control systems using IEC1131-3

3.18 Numerical functions

The standard defines a set of numerical functions that includes most of those in
common use; they are listed in Table 3.8. All of these functions support data type
overloading (see Section 3.7). The result is always the same data type as the input
value.

Table 3.8 Numerical functions

Function name Data type Description


ABS ANY.NUM Absolute value (negative values
become positive)
SQRT ANY_REAL Square root
LN ANYJREAL Natural logarithm
LOG ANY_REAL Logarithm
EXP ANY.REAL Natural exponential
SIN ANY_REAL Sine of input as radians
COS ANY.REAL Cosine of input as radians
TAN ANYJREAL Tangent of input as radians
ASIN ANY_REAL Principal arc-sine, result in radians
ACOS ANY_REAL Principal arc-cosine, result in radians
ATAN ANY_REAL Principal arc-tangent, result in
radians

3.19 Functions equivalent to ST operators

All of the Structured Text arithmetic operators such as '+' and '-' are also
provided as standard functions.
These functions fit into two categories, extensible and non-extensible functions.
An extensible function is one where the number of inputs can vary depending on
the requirements, e.g. the ADD function can add two, three or more inputs. These
functions all support overloaded data types as discussed in Section 3.15.
Chapter 3 Common elements 85
Table 3.9 Extensible arithmetic functions

Function Data type ST Description


name operator
ADD ANY..NUM + Addition,
result := 11 +12 + ..
MUL ANYJNUM * Multiplication,
result := 11 * 12 * ..

Examples of using extensible arithmetic functions:

Fault_Count:= ADD( Devi, Dev2, AB_34, AB_32, AX_32);


Total_Revs := MUL( Gearl, Gear2, Gear3, 1200 );

These function calls are equivalent to the following Structured Text statements:

Fault_Count := Devi + Dev2 + AB_34 + AB_32 + AX_J32;


Total_Revs := Gearl * Gear2 * Gear3 * 1200;

Table 3.10 Non-extensible arithmetic functions

Function Data type ST Description


name operator
SUB ANY_NUM Subtraction,
-
result := 11 -12;
DIV ANYJWM / Division,
result := 11 /12, Note l
MOD ANYJNT MOD Modulus,
result := 11 MOD 12, Note 2
EXPT ANY_REAL #* Exponential,
Note 3 result :=I1 12 , Note 3
MOVE ANY Result := 11, assigns the value
of 11 to the result for any data
type

Note 1: With integer division, the result will always be the same data type as the
first input parameter II; any fractional remainder is truncated.

Examples of the integer division (DIV) function are:


A := D I V ( 1 2 , 3 ) ; (* A i s 4 *)
A := D I V ( 1 4 , 5 ) ; (* A i s 2 *)
A := D I V ( - 4 , 3 ) ; (* A i s - 1 *)
86 Programming industrial control systems using IEC1131-3
Note 2: Modulus operation is only valid with integer values and is equivalent to the
following Structured Text expression :
I F ( B l = 0 ) THEN
Result := 0;
ELSE
Result := II - (11/12)*I2;
END_IF

Examples of the MOD function are :


A : = MOD(.12,3) ; (* A i s 0 *)
A : = M O D ( 1 4 , 3 ) ; (* A i s 2 *)
A := M O D ( - 4 , 3 ) ; (* A i s - 1 *)

Note 3: The exponential function can only take integer exponents; 12 can only be of
type ANY_INT. The result is always the same data type as input 1 (II).

These functions are provided to allow Structured Text statements involving


operators to be expressed in the other languages.

3.20 Bit string functions

These functions provide shift operations for values of bit-string data types. All the
functions have the general form :
Result := SHL( IN := I n p u t _ J B i t _ S t r i n g ,
N := B i t _ S h i f t s ) ;

The general form of these functions when presented graphically is :

SHL
ANY_BIT- IN •ANY
ANY INT-

Table 3.11 Bit-string functions

Function Data type Description


name
SHL ANY_BIT Shift bit-string n bit positions left, zero fill
on the right.
SHR ANY_BIT Shift bit-string right n bit positions, zero
fill on the left.
ROR ANY.BIT Shift bit-string right, rotate by n bit
positions.
ROL ANY.BIT Shift bit-string left, rotate by n bit
positions.
Chapter 3 Common elements 87

All bit-string shift functions are applicable to overloaded data type ANYJBIT, i.e.
they can be used with data types BOOL, BYTE, WORD, DWORD and LWORD.

Example:
VAR
t _ 8 : BYTE;
G_8 : BYTE;
END VAR

t_8 := 2#0011_0101;
G_8 := SHL ( t_8, 4 ) ; (* G__8 = 2#0101_0000 *)

3.21 Boolean bitwise functions

These functions can be used with bit-string values for logical operations. When
used with values of boolean (BOOL) data type, they provide the normal logical
operations. With data types that have multiple bits, the function applies to bits in
matching bit positions in the parameter values. This is best demonstrated by the
examples given after the table. These functions all have equivalent Structured
Text operators.
With the exception of the NOT function, these are all extensible functions that
can take two or more input parameters and support the overloaded data type
ANY_BIT.
The standard allows functions to be represented both by function name and
optionally by special symbols as shown in the table.

Table 3.12 Boolean bitwise functions

Function Data type Symbol Description


name
AND ANY_BIT & Results 11 & 12 &...
OR ANY_BIT >=1 Result := 11 OR 12 OR...
Notel
XOR ANYJBIT =2k+l Result := 11 XOR 12 XOR..
Notel
NOT BOOL Result := NOT 11

Note 1: These symbols can only be used to represent boolean functions


in the Ladder Diagram and Function Block Diagram languages; they
cannot be used in the textual languages.
88 Programming industrial control systems using IEC1131-3
Examples of using extensible boolean functions:

Confirm := AND( Swl, Sw2, AB_1, AB_2, AX_2);


Trip_l := OR ( OverTempl, 0verTemp2, UnderPress ) ;

These function calls are equivalent to the following Structured Text statements:

Confirm := Swl & Sw2 & AB_1 & AB_2 & AX_2;
Trip_l := OverTempl OR 0verTemp2 OR UnderPress;

Examples of bitwise logical functions:

VAR
Mask : WORD := 16#FF01;
Status: WORD := 16#0A02;
X_54 : WORD;
END_VAR
X_54 := Mask XOR Status; (* X_54 = 16#F503 *)

3.22 Selection functions

A wide range of standard selection functions, as listed in Table 3.13, are provided
to enable one value to be selected from a number of given values according to
certain criteria. These functions can be used with any data type, i.e. generic data
type ANY.
The selected value is always the same data type as the inputs; all selection
inputs for any particular function call should be of the same data type.
The SEL function is particularly useful as it allows one of two values to be
selected depending on a boolean condition.

Examples of selection functions:

(* When flag is TRUE, A =230.0 otherwise A =120.0 *)


A:= SEL ( G:= Flag, INO := 120.0, INI := 230.0 ) ;

(* Select the maximum temperature *)


TempMax := MAX( TempA, TempB, TempC, TempD ) ;

(* Limit soaktime to between 2 and 4 hours *)


SoakTime := LIMIT(MN:=T#2h,IN:=JobTime,MX:=T#4h);

(* Select value from next input channel *)


value := MUX(K:= ChanNo,INO:=Chan0, INl:=Chanl,
IN2 : =Chan3 ) ;
Chapter 3 Common elements 89
Table 3.13 Selection functions
Function Data type Graphical form Description
name
SEL ANY Selection
SEL If G = TRUE then
BOOL G ANY
Result := INI ELSE
ANY INO
ANY IN1 Result := INO

MAX ANY Maximum


ANY MAX Result := maximum
ANY
ANY value of all inputs.
ANY

NUN ANY Minimum


ANY MIN Result := minimum
ANY
ANY value of all inputs.
ANY

LIMIT ANY Limit


LIMIT Result is the value of
ANY MN ANY IN limited between a
ANY IN
ANY MX
minimum value of MN
and a maximum of
MX.
MUX ANY Multiplexer
MUX Result is the value of
ANYJNT- ANY
the input selected by
ANY
ANY the value of K
(see examples).

3.23 Comparison functions

Comparison functions are provided, as listed in Table 3.14, for comparing values
of the same data type. All comparison functions return a boolean (BOOL) data
type. These functions can be used with all data types, i.e. generic data type ALL.
90 Programming industrial control systems using IEC1131-3
Table 3.14 Comparison functions

Function name Symbol Description


GT > Greater than
Result := INI > IN2
GE >= Greater than or equal
Result := INI >= IN2
=
EQ Equality
Result := INI = IN2
LE <= Less than or equal
Result := INI <= IN2
LT < Less than
Result := INI < IN2
NE <> Inequality
Result := INI <> IN2 Note l

These functions can also be used as operators in Structured Text, in which case
the appropriate symbol should be used.
With the exception of the inequality comparison function, the rest can be used
with multiple inputs, in which case the comparison is made between a sequence of
inputs and ANDing the result - see the following examples.
These functions can also be used to compare character strings, in which case,
when shorter strings are compared with longer strings, the shorter string is
considered to be extended with characters which have a code value of zero. The
comparison is based on the value of the numeric codes and compares characters
from left to right. The standard bases all character codes on the character set
defined in ISO/IEC 646.

Examples of comparison functions:


(* Set output TRUE if speed 1 less than speed 2 *)
Output__l : = LT ( Speedl, Speed2 ) ;

(* Comparison using Structured Text operator *)


Output_l := Speedl > Speed2;
Example of using extensible inputs with comparison functions:
(* Check that boiler pressures all decrease *)
(* from PI to P4 *)
PressOK := GT ( Pi,P2,P3,P4 );
(* Equivalent Structured Text expression *)
PressOK := PI > P2 & P2 > P3 & P3 > P4;
Chapter 3 Common elements 91

3.24 Character string functions

A comprehensive range of character string functions is defined that enable strings


containing textual or non-printable character codes to be manipulated. The use of
standard string functions can greatly simplify string handling, for example when
constructing operator messages or messages for transmission to remote devices.

Table 3.15 Character string functions

Function Graphical form Description


name
LEFT Extract left string
LEFT Result is the string formed from
STRING
STRING IN L characters from the leftmost
ANYJNT L character of string IN.

RIGHT Extract right string


RIGHT Result is the string formed from
STRING
STRING IN L characters from the rightmost
ANYJNT L part of string IN.

MID Extract mid string


MID Result is a string extracted from
STRING IN STRING the input string IN starting at
ANYJNT L'
ANYJNT P character position P, and L
characters long.
CONCAT Concatenate strings
CONCAT Result is a string formed by
STRING STRING joining the input strings
together. This is an extensible
STRING
function that can take two or
more input strings.
92 Programming industrial control systems using IEC 1131-3
Table 3.16 Character string functions - continued

Function Graphical form Description


name
INSERT Insert string
INSERT The result is formed by the
STRING • IN1 STRING string IN2 being inserted into
STRING • IN2
string INI, P character positions
ANYJNT" P
from the start of IN 1.
DELETE Delete string
DELETE The result is formed by a string
STRING IN STRING of characters L in length, being
ANYJNT L
ANYJNT-*— P deleted from the input string IN,
starting from character position
P.
REPLACE Replace string
REPLACE The result is formed by
STRING IN1 —STRING replacing L characters in string
STRING IN2
INI, starting at position P, with
ANYJNT L
ANYJNT P character string in IN2.

LEN Length
LEN Result is length of the input
STRING — INT
string.

FIND Find string


FIND Result is the position where
STRING IN1 INT string IN2 is first found in string
STRING IN2
INI.
If string IN2 is not found in INI,
the result is 0.

Note 1: It is an IEC convention that the first character in a string is considered to be


at position 1. If the length of a string is L, then the last character in the
l
string is at position L.
Note 2: The maximum length of strings that can be supported by a PLC is not
defined in the standard.
Chapter 3 Common elements 93
A range of different errors may occur due to inappropriate values for inputs to
these functions. For example, using the CONCAT function could result in
producing a string that is beyond the maximum supported string length. The
treatment of such errors is not defined in the standard but will clearly need to be
addressed in any implementation of IEC 1131-3.
The following example shows how the character string functions can be used to
build up typical batch related strings:

VAR
Recipe_Spec : STRING(12) := 'Recipe_x_141';
Recipe : STRING(14);
Job_Code : STRING(3);
Batch : STRING(20);
Batchld : INT := 7;
END__VAR

(* Extract Job Code 141 *)


Job__Code: = RIGHT ( IN:= Recipe_Spec, L := 3 ) ;

(* Create Recipe name /Recipe_A7X_141/ *)


Recipe := REPLACE( INI:= Recipe_Spec,IN2: = ' A7X',
L:=l, P:= 8 ) ;

(* Build the Batch description*)


(* as /Recipe__A7X_141_7/ *)
Batch := CONCAT(
Recipe,'_' ,INT_TO_STRING(Batchld));

3.25 Functions for handling times and dates

The following functions can also be used in computations involving durations


(TIME), dates (DATE) and times of day (TME_OF_DAY). These can be
particularly useful for time related calculations, such as creating time stamps,
determining when sensors need to be calibrated or deciding when items of plant
need maintenance. Time handling functions are particularly useful for batch
oriented systems.
In the following descriptions, each function is regarded as having two inputs,
INlandIN2.

ADD (Structured Text + operator)

The ADD function or operator can be used with the following combinations of
time and date data types.
94 Programming industrial control systems using IEC1131-3

INI IN2 Result


TIME TIME TIME
TIME_OFJDAY TIME TME__OF_DAY
DATE_AND_TIME TIME DATE_AND_TIME

For example, adding a duration (TIME) to a time of day (T1ME_OFJDAY) will


produce an advanced time of day.

SUB (Structured Text — operator)

The SUB (subtract) function or operator can be used with the following
combinations of time and date data types.

INI IN2 Result


TIME TIME TIME
DATE DATE TIME
TIME_OF_DAY TIME TIMEJDF.DAY
TIME_OF_DAY TIME^OFJDAY TIME
DATE_ANDJTIME TIME DATE_AND_TIME
DATE_AND_TIME DATE_AND_TIME TIME

For example, subtracting a date (DATE) from another date will produce a duration
(TIME) subtracting a duration from time of day will produce an earlier time of
day.

MUL and DFV (Structured Text * and / operators)

MUL (multiply) and DIV (divide) functions or their equivalent Structured Text
operators can be used to scale durations (TIME).

INI IN2 Result


TIME ANY.NUM TIME

Example:
VAR
TIME : processTime := T#2h;
TIME : jobTime;
REAL : scale := 1.5;
END VAR
Chapter 3 Common elements 95
(* Set jobTime to 3.0 hours *)
JobTime := MUL( processTime,scale

(* Equivalent Structured Text *)


JobTime := processTime * scale;

CONCAT

The string concatenation function CONCAT can be used to append a time of day
to a date to create a date and time.

INI IN2 Result


DATE TIME_OF_DAY DATE_AND_TIME

Example:
VAR
DATE : startDate := DATE#1994-03-19;
TIME : alarmTime := TIME_0F_DAY#13 :15 : 00 ;
DATE_AND_TIME : timeStamp;
END_VAR

(* Set time stamp to 1994-03-19-13:15:00 *)


timeStamp := CONCAT ( startDate,alarmTime);

3.26 Time related conversion functions

Two special conversion functions are provided to extract times of day and dates
from the compound date and time data type.

DATE_ANDJTIME_TO_TIME_OF__DAY

This function can be used to extract the time of day from a compound date and
time of day.

DATEJLND_TIME_TO_DATE

This can be used to extract the date from a compound date and time of day.

Example:
VAR
DATE_AND_TIME :
event := DATE#1995-03-20-12:15:00;
DATE : eventDate;
96 Programming industrial control systems using IEC1131-3
TIME_OF__DAY : eventTime;
END_VAR
(* Extract the time of day as 12:15:00 *)
eventTime :=
DATE_AND_TIME_TO_TIME_OF_DAY ( event ) ;
(* Extract the date as 1995-03-20 *)
eventDate := DATE_AND_TIME_TO_DATE( event ) ;

3.27 Functions for enumerated data types

Table 3.17 Functions to handle enumerated values

Function Structured Description


name Text symbol
SEL The selection (SEL) function can be used to
select one of two enumerated values depending
on a boolean condition.
MUX The multiplexor (MUX) function can be used to
select one from a number of enumerated values
depending on the value of an integer selector.
EQ — The equality (EQ) function can be used to test
the equality of two enumerated values of the
same data type.
NE O The inequality (NE) function can be used to test
that two enumerated values are not the same.

Enumerated data types, as discussed in Section 3.9, can only be used with a few of
the standard functions or with their equivalent Structured Text operators. This is
primarily because an enumerated data type does not have any intrinsic value that
can be converted to or compared with a numerical data type.

3.28 Function execution control

If a function is used in either of the graphical languages, Ladder Diagram (LD) or


Function Block Diagram (FBD), it is possible to control when the function
executes using a special input called EN. When a function is connected in a
Ladder Diagram rung or is part of a Function Block Diagram network, the
execution enable input EN (a boolean variable) should be set TRUE for the
function to be executed. While the EN input is FALSE, the function remains
dormant and does not assign a value to its output.
Chapter 3 Common elements 97
Similarly, each function used in either LD or FBD networks has an extra
boolean output ENO which is asserted TRUE when the function execution is
successfully completed.
If a function fails to execute owing, for example, to an error such as an
arithmetic overflow, or division by zero, the ENO output remains FALSE.
By chaining the ENO output from one function to the EN input of a following
function, it is possible to ensure that functions in a chain only succeed in
producing a valid result when they all execute without error.

CALC ADD SQRT DONE


I— EN ENO EN ENO
A1 — X1
B1

Figure 3.3 EN and ENO example

Figure 3.3 depicts a typical use of the execution control parameters EN and
ENO in the Ladder Diagram (LD) language. (See Chapter 6 for further details on
LD.)
When the variable CALC becomes TRUE, the ADD function is executed using
the current values of Al and Bl. If the ADD function completes successfully, the
ENO output is asserted. This in turn enables execution of the SQRT (square root)
function which takes the value from the ADD function as input. When the SQRT
function completes (assuming the input is a positive number), the ENO output is
asserted TRUE. The DONE variable only becomes TRUE when both functions
execute successfully and produce the result XL
All functions may have an EN input and ENO output but in the first revision of
D3C 1131-3 these could only be used in the graphical languages LD and FBD.
However, an amendment to IEC 1131-3 now also allows their use in Structured
Text. Note that the values of EN and ENO can be changed and tested within
function bodies that are written in any of the EEC 1131 languages.
The portion of ladder program depicted in Figure 3.3 could be expressed in
Structured Text as follows:
IF CALC THEN
SUM := ADD(A1,B1, ENO => Tempi);
IF Tempi THEN
XI := SQRT ( SUM, ENO => DONE ) ;
END_IF;
END_IF;
98 Programming industrial control systems using IEC1131-3
Notel: The => operator is used to transfer the ENO output value to an external
variable.
Note2: When expressing graphical links involving functions, additional temporary
variables may sometimes be needed when the same functionality is
expressed in Structured Text.

When defining a new function type, the EN and ENO variables are implicitly
available. In other words, it is not necessary to declare them. However they can be
accessed within the function body as if they were normal variables using
languages such as Structured Text.
EN and ENO are implicitly defined as follows:

VAR_INPUT
EN : BOOL := 1;
END_VAR
VAR_OUTPUT
ENO : BOOL;
END_VAR

Example setting ENO within a function written in Instruction List:

LD Count (* Load Count *)


GT 100 (* Is it greater than 100? *)
ST ENO (* Set ENO if yes *)

Example setting ENO within a function written in Structured Text:

ENO := (Count > 100);

3.29 FUNCTION BLOCKS

Function blocks are a category of program organisation unit (POU) that allows a
specified algorithm or set of actions to be applied to a given set of data to produce
a new set of output data. In a control system, function blocks are ideal for
algorithms such as PID used for closed loop control, for counters, ramps, filters
and so on.
A function block has a defined set of input variables, output variables, and
variables for internal storage and temporary data; it also has specific software or
an algorithm which behaves as a set of rules, actions or transformations. When a
function block executes, it evaluates all its variables; that includes not only the
input and internal variables but also the output variables. During its execution, the
algorithm creates new values for the output and internal variables.
Chapter 3 Common elements 99
A function block has a significant feature which is not available with functions,
and that is data persistency. Because a function block can hold data values
between each execution it can be used to provide a wide range of system building
blocks that require retained state.
A function block type is a specification of the data structure and algorithm for a
named type of block. A function block instance is a particular set of data values
held in structures as defined by the function block type, and that can be
transformed by an algorithm that is specified in the function block type definition.

3.30 Function block usage

The following points apply to the use of function blocks:

• It is only possible to access the input and output parameters of a function block
instance externally. Internal variables are not accessible.
• A function block instance is only invoked if explicitly requested either because
(a) the function block instance is part of a graphical network of connected
blocks which form a program organisation unit or (b) it is invoked by a call in
the textual languages Structured Text or Instruction List.
• Instances of a particular function block type can be used in other function block
or program type definitions.
• Function block instances are always declared using variable declarations within
a POU, such as a program or function block. By default, variable declarations
are local with the result that function block instances are only visible within the
immediate POU. However, function block instances may be declared as globals
using the VAR_GLOBAL construct. They are then accessible within any
program or function block that exists within the resource or configuration in
which the global instances are declared.
• It is possible to pass a function block instance as an input to another program,
function block or function. This leads to some interesting and novel possibilities
in programming. For example, a tuning function block could in turn be invoked
with different instances of different PID function blocks in order to tune a
number of control loops.
100 Programming industrial control systems using IEC1131-3
• The current values of function block input and output parameters can be
accessed in the textual languages as if the instance data were held in data
structure. For example, the output parameter OUT of function block instance
C1 can be accessed as C1 .OUT.
• A function block instance can also be represented in the graphical languages
Function Block Diagram (FBD) and Ladder Diagram (LD); this is discussed in
detail in the following chapters.

3.31 Defining function block types

A function block type definition is introduced by the IEC keyword


FUNCTIOlsLBLOCK and terminated by END_FUNCTIONJBLOCK. The
definition contains a list of input, output and internal variable declarations
followed by software that describes the algorithm. This software, sometimes
referred to as the function block body, can be described using one of the following
EEC languages:

Structured Text, Function Block Diagram, Ladder Diagram,


Sequential Function Chart, Instruction List

Function block type definitions may also contain instances of other function
blocks and external variables, i.e. that reference global variables declared at the
program, resource or configuration level.
The declaration of global and directly represented variables, i.e. those that make
reference to absolute PLC addresses, was not permitted in the IEC 1131-3 1993
edition but is allowed in the proposed amendment for the second edition.
EEC 1131-3 defines a number of standard function blocks; these are described in
Chapter 9, 'Function blocks'.

3.32 Declaring function block instances

Function block instances can be declared using the same constructs as variables.
In effect, a function block instance is really a data structure which has an
associated algorithm defined in the function block type definition. Function block
instances can only be declared within program or function block type definitions.
Creating a copy or instance of a function block from the function block type is
called 'instantiation1.
Chapter 3 Common elements 101
For example assuming that SPEED.RAMP, PRESS_MONITOR are function
block types that have already been defined, then examples of instance declarations
of these blocks are:

VAR
Linel__Ramp, Line2__ramp : SPEED__RAMP;
END_VAR
(* Instance data retained on warm start *)
VAR RETAIN
Press_X32, Press_X54 : PRESS__MONITOR;
END_VAR

(* Global function block *)


VAR_GLOBAL
Main_Press : PRESS_MONITOR;
END__VAR

(* Reference to a function block instance *)


(* Passed into another POU *)
VAR_INPUT
PressMon : PRESSJYIONITOR;
END_VAR

3.33 Function block example

Consider the following example of a simple function block called COUNTER.


This has one input MODE and one integer output OUT. MODE can only have
three values RESET,
COUNT and HOLD, i.e. COUNTER
it is an enumerated data ModeType |MODE OUT I INT
type. When the function
block is in the RESET
mode, the output is always zero; when in the COUNT mode, the output increases
by one on each execution; when in the HOLD mode, the value of OUT is held at
its last value.
To use the appropriate IEC 1131-3 terminology, when the software associated
with a function block type is executed to update the data of a function block
instance, the instance is said to have been 'invoked'.
Assume that the definition for the enumerated ModeType is:

TYPE
ModeType : ( RESET, COUNT, HOLD ) := RESET;
END TYPE
102 Programming industrial control systems using IEC1131-3
The function block type definition for COUNT is:

FUNCTIONJBLOCK COUNTER
(* Define the external interface *)
VAR_INPUT
MODE : ModeType := RESET;
END_VAR
VAR__OUTPUT
OUT : INT := 0;
END_VAR

(* Define the algorithm *)


IF MODE = RESET THEN
OUT := 0;
ELSIF MODE = COUNT THEN
OUT := OUT + 1;
END__IF;
END_FUNCTIONJBLOCK

An instance of the COUNTER function block can be declared within other


program organisation units, such as other function blocks. The following fragment
of Structured Text shows how an instance Cl of COUNTER could be declared
and used.

PROGRAM COUNT1
VAR_INPUT
InputMode : ModeType;
END_VAR
VAR_OUTPUT
Max_Count : INT;
END_VAR
VAR
Cl : COUNTER;
END VAR

(* Invoke the function block Cl *)


(* with the mode set according to the value of *)
(* InputMode, an input parameter to the program*)

Cl(MODE := InputMode);
(* Assign the output to a variable *)
Max_Count := C1.OUT;
END_PROGRAM

The following table shows an example of states of the input and output parameters
of function block Cl, which might exist just prior to and after a series of calls to
Cl, i.e. invocations of Cl. The time between invocations will depend on the task
Chapter 3 Common elements 103
configuration and their execution rates which might range from say 10 ms to
several hours. The example assumes that function block instance Cl and the
parent program execute in the same task.
Notice that the value of InputMode is assigned to MODE just as the function
block is invoked. Although the values of output parameters cannot change unless
the instance is invoked, the values can always be read and assigned to other
variables, in which case the output values are relevant to the last function block
invocation.

Table 3.18 Function block invocation states example


Values between invocations time >
Variable Initial 1 2 3 4 5
state
InputMode RESET RESET COUNT COUNT HOLD HOLD
RESET RESET RESET COUNT COUNT HOLD
0 0 0 1 2 2
0 0 0 1 2 2

3.34 PROGRAMS

A program is the largest form of program organisation unit and can be declared at
the resource level. A program is very similar to a function block in concept and
provides a large re-usable software component. It is defined by a program type
definition which, as for function block types, has input, output and internal
variable declarations and a body which contains software describing the program's
behaviour.

3.35 Program usage

Programs are generally regarded as large software building blocks. A typical PLC
project may make use of extensive libraries of function block types, but have
relatively few types of program. A program might be used for example to control a
major item of plant such as a steam turbine, a reactor vessel or a production cell.
Apart from the following distinguishing features, programs are very similar to
function blocks.
104 Programming industrial control systems using IEC 1131-3
• Programs may contain declarations of directly represented variables that
allow PLC memory to be accessed using hierarchical memory addresses.
• Programs may contain declarations of global variables. These can be
referenced within function blocks using external variables.
• Programs may contain access variables (VAR_ACCESS) that allow named
variables to be read and written to by remote devices using communication
services.
• They may not contain instances of other programs, i.e. programs cannot be
nested.
• Programs may contain instances of function blocks which may optionally be
executed under the control of different tasks.
• Instances of programs can only be declared within resources.

3.36 Defining program types

A program type definition is introduced by the IEC keyword PROGRAM and


terminated by END_PROGRAM. The definition contains a list of input, output
and internal variable declarations followed by software that describes the
behaviour of the program. The program body can be described using one of the
following IEC languages:

Structured Text, Function Block Diagram, Ladder Diagram,


Sequential Function Chart, Instruction List

Program definitions typically contain instances of function blocks, internal


variables and external variables, i.e. that reference global variables declared at the
resource or configuration level, and directly represented variables.

Example:
PROGRAM fermenter
VAR_INPUT(* Program inputs *)
Reagent_Code : INT;
Sterilise : BOOL;
Ferment_Period : TIME;
END_VAR
VAR_OUTPUT (* Program outputs *)
Yield : REAL;
Status : WORD;
Chapter 3 Common elements 105
END_VAR
VAR (* Internal variables and function blocks *)
pHJLoop, Temp__Loop : PID;
Phase : INT := 1;
END_VAR
(* Body not shown in example but
* can be ST, FBD, LD
* SFC or IL
*)
END PROGRAM

3.37 Declaring program instances

An instance of a program of a certain type is declared using the keyword


PROGRAM followed by the identifier and type of program.

Examples:
PROGRAM Linel : Fermenter;
PROGRAM CTl,CT2 : COUNT1;

Linel is an instance of a program type called Fermenter; CT1 and CT2 are
instances of program type COUNT 1.
A program declaration in a resource can also contain connections between
program inputs and outputs to variables declared outside the program.

Example:
PROGRAM Linel : Fermenter( Reagent_Code := Al,
Sterilise := A2,
Ferment_Period := FTIME,
Yield => AJ_43, Status => KX56 ) ;

Program instance Linel will be run with resource variables or globals Al, A2,
FTIME supplying the values for program inputs Reagent_Code, Sterilise and
Ferment_Period respectively. Program outputs Yield and Status are written to
variables AJ_43 and KX56. These could be declared within the parent resource or
as globals at resource or configuration level. Program inputs and outputs can also
be connected to directly represented variables, i.e. to PLC memory or hardware
references.
106 Programming industrial control systems using IEC1131-3
In some cases it may be necessary for the program to be assigned to run under
the control of a particular task, for example because it must respond to changing
plant conditions within a certain deadline. (Tasks are described in Section 3.40.)
The keyword WITH can be used to assign a task to the program instance or to a
designated function block instance within the program.

Example:
PROGRAM Line2 WITH Slow_task : Packaging^Line,
Speed := %IW21_10,
ProductJRate => %QW33_81,
Sampler1 WITH FastJTask,
Sealerl WITH Fast_Task ) ;

Line 2 is an instance of program type PackagingJLine which runs under the


control of the Slow_task task. Program input variable Speed is supplied a value
that comes from a directly represented variable that might, for example, be
associated with a particular PLC input channel. Program output Product_Rate is
written to a certain PIX! memory reference, that again could be associated with a
PLC output channel. Function block instances Sampled and Sealerl declared
within the program are defined to run in the FastJTask.

Note: An amendment to the EEC 1131-3 1993 edition allows the => operator to
be used in both Structured Text program and function block invocations. It
indicates that the value of output variable on the left is passed to the
variable given on the right of the operator.

3.38 RESOURCES

A resource corresponds to a processing facility that is able to execute IEC


programs. A resource is defined within a configuration using the keyword
RESOURCE, this is followed by an identifier and the type of processor on which
the resource will be loaded. The resource definition that follows contains a list of
variable declarations, tasks and program declarations; the definition is terminated
with the keyword END_RESOURCE.

Note: Processor types are not defined in IEC 1131-3 and will varyfromproduct
to product; typical types might be PROC_386, LCM_68000.
Chapter 3 Common elements 107

3.39 Resource usage

A resource may contain the following:

• Global variable declarations;


• Access paths, i.e. access variables that permit remote access to
named variables;
• Variable declarations including external variable declarations
that reference globals at the configuration level;
• Program declarations;
• Task definitions that can be assigned to programs and function
blocks within the resource.
A full example is shown in Section 3.45 'Configurations'.

3.40 TASKS

In the design of a real-time system, the designer requires flexible and configurable
control over the execution rates of different parts of the program. Generally the
different parts should execute at rates determined by the requisite responsiveness
of the system and a need to optimise the use of the PLC processing capacity. For
example, in applications handling temperature control of objects of high thermal
mass such as in a furnace, the associated function blocks could execute, say, every
minute and still provide stable control. In contrast, function blocks involved in
interlock logic for, say, a fast acting packaging machine might need to be executed
every 5 ms.
Tasks are associated with a particular resource and are considered to execute
under the control of the resource.

Note: IEC 1131-3 assumes that tasks in different resources always execute
independently. However some form of timing synchronisation between
resources may be provided in some implementations.

The standard allows designated function blocks and programs to be assigned to


different tasks. A task is a scheduling facility that executes either periodically or in
response to a particular boolean variable changing state. Each task may be
assigned an interval, i.e. that defines the time between each execution and a
priority (0 is considered highest, then 1, 2 etc.).
108 Programming industrial control systems using IEC1131-3

3.41 Non-preemptive and preemptive scheduling

Where there are multiple tasks declared, each task is generally assigned a different
interval and priority. The moment in time at which a particular task is executed
depends on the type of scheduling regime, the priorities and intervals of the other
tasks and how long each of the other tasks has been ready and waiting to execute.
A PLC can provide two methods of scheduling - non-preemptive and
preemptive. The method adopted can significantly alter the behaviour of the
system.

Non-preemptive scheduling

We will consider non-preemptive scheduling first. With this scheduling regime,


once a task is executing, it always continues until all the programs and function
block instances assigned to it have been executed once. The task then terminates;
the next to execute is the waiting task with the highest priority, or if there are
several tasks with the same priority, it is the task that has been waiting the longest.
Once a task has executed, it is not considered for scheduling again until a period
equal to the task interval has elapsed.
Designing an operating system or executive based on non-preemptive
scheduling is generally more straightforward than preemptive scheduling.
However, non-preemptive systems tend to have poor characteristics for stable
control.
The actual real-time interval between task executions may vary considerably as
it depends on how long the other tasks take to complete. If one task occasionally
takes significantly longer to execute, then all other tasks may be delayed. This can
result in erratic task execution, i.e. it is not always possible to predict when certain
tasks will execute. Such systems are said to be non-deterministic and generally
should not be used for time critical applications.

Preemptive scheduling

Preemptive scheduling is required for deterministic systems, i.e. control systems


that are required to have consistent timing relationships between events, for
example where certain control algorithms are updated at precise and regular
periods. With this regime, irrespective of what task is currently executing, when a
higher priority task interval elapses it is immediately scheduled. The currently
Chapter 3 Common elements 109

active task is suspended. When the higher priority task terminates, the suspended
task of lower priority continues. Where there are several priority levels, a number
of tasks may have started execution but be suspended while higher priority tasks
execute.

Non-preemptive Scheduling

100 200 300 400 500 600


Time Milliseconds —>
Preemptive Scheduling
Task C Interrupted

100 200 300 400 500 600


Time Milliseconds—>

Task A, Priority 0, Interval 100ms


Task B, Priority 1, Interval 200ms
Task C, Priority 2, Interval 300ms

Figure 3.4 Non-preemptive and preemptive scheduling

Figure 3.4 compares the execution timing of three tasks under non-preemptive
and pre-emptive scheduling regimes. Tasks A, B and C have priorities 0, 1, 2
respectively (task A with priority 0 is highest). Task A should execute every
100 ms, B every 200 ms and C every 300 ms. With non-preemptive scheduling,
notice that tasks A and B are delayed after C executes. Task A is further delayed
when it attempts to execute after 500 ms.
110 Programming industrial control systems using 1EC1131-3
In contrast, with pre-emptive scheduling, task A always executes every 100 ms,
and B every 200 ms, although it has to wait for the higher priority task to
complete. Task C is interrupted to allow first A and then B to execute.
Note: Products that allow resources to support multi-tasking scheduling facilities
will require mechanisms to indicate when tasks over-run, i.e. when the time
taken to complete a task is longer than the task interval. Ideally
programming systems should also offer facilities to measure and optimise
processor utilisation.

3.42 Task declarations

A task declaration is introduced using the keyword TASK followed by the task
identifier and optional values for the following three parameters:

Table 3.19 Task declaration parameters

Task Data type Description


parameter
SINGLE BOOL A Boolean variable whose value 'on the rising
edge', i.e. on changing from 0 to 1, will cause
the task to be scheduled for execution once.
Notel
INTERVAL TIME The period that should elapse between
subsequent task executions. Provided that this
parameter is not zero, and the SINGLE
parameter is 0, the task will execute
periodically. Note 1
PRIORITY UINT The task priority level. 0 is regarded as
highest, i.e. 0,1,2,3 are decreasing priority
levels.
Note 1: The task will not be scheduled while the value of the SINGLE parameter is 1.

Tasks can also be declared graphically; this is discussed in Chapter 5, 'Function


Block Diagram' using a special graphical format called 'Continuous Function
Chart'.
Note: The number of tasks supported, the range of priority levels and the range of
values allowed for task intervals will vary from product to product.

Examples of task declarations are:


TASK FAST_INTERLOCKS (INTERVAL : =t#3 0ms, PRIORITY: =0 ) ;
TASK LOGJTASK (SINGLE : = LogFlag, PRIORITY: =3 ) ;
TASK CONTROL_TASK (INTERVAL := t#50Oms , PRIORITY: =1) ;
Chapter 3 Common elements 111

3.43 Assigning programs and function blocks to tasks

Programs and function block instances can be assigned to different tasks.


Arranging parts of a program to execute at different rates may be required to meet
certain system performance criteria, like ensuring that particular outputs are
always updated within a certain time in response to a given change in input values.
A function block or program is associated with a task using the keyword WITH,
as shown in the program declaration example in Section 3.37.
Function block instances that are not assigned to tasks execute in the same task
as the parent program.
Any program that is not allocated to a task is by default executed at the lowest
priority and will be re-scheduled as soon as it completes, i.e. it runs continually in
the background.

3.44 Function block and program execution rules

IEC 1131-3 defines rules for function block and program execution. These are
required to ensure that where values are being passed between, say, function block
instances that are running in different tasks, the values are always consistent, i.e.
are all produced as a result of a particular task execution. The rules are:

• If more than one input value of a function block A comes from outputs of a
function block B, then the system should ensure that all the values from B are
produced by the same execution of B.
This is to ensure data concurrency and avoid unpredictable behaviour that
could result from A executing with some input values produced by, say, the
latest execution of B and some by a previous execution of B.
• In situations where a number of function blocks are assigned to the same task,
and all take values from outputs of a function block B running in a different
task, then again their input values should all come from the same execution
ofB.

To summarise, when sets of values are passed from function blocks running in one
task, to those in another, the values should all be produced in the same task
execution.
112 Programming industrial control systems using IEC1131-3
The way this is implemented is not specified. However, the rules imply that
when a task initially executes, it should first gather and store all the values of
function block inputs arising from function blocks in other tasks. The task then
executes all its assigned programs and function blocks. New function block output
values created during this time need to be held in a temporary data buffer. At the
point where the task execution terminates, all new output values are then copied
from the temporary buffer into the normal outputs in one operation, i.e. other tasks
should not be able to interrupt during the buffer copy.

3.45 CONFIGURATIONS

A configuration defines the software for a complete PLC or programmable control


system and will always include at least one but, in some cases, many resources. A
configuration is specific to a particular type of PLC product and the arrangement
of the PLC hardware. It can only be used to create software for another PLC if the
hardware is identical.
Generally, a configuration will correspond to a particular arrangement of PLC
hardware which will include specific:

• processing resources (such as processor boards with certain types of micro-


processor);
• memory addresses for input and output channels;
• system capabilities (e.g. maximum number of tasks and execution rates).

A configuration is introduced with the keyword CONFIGURATION and is


terminated with the keyword END_CONFIGURATION. The definition can either
be in a textual format or graphical. The graphical format is described in Chapter 5,
'Function Block Diagram'.
Chapter 3 Common elements 113

3.46 Configuration example

The following example depicts many of the features of a configuration:


CONFIGURATION unit_l_config
VAR_GLOBAL
G_speed_setpoint : REAL;
G_runUp_Time : TIME;
G_Log_Event AT %M100 : BOOL;
G_Log__Data : ARRAY [ 1. . 10 0 ] OF INT ;
END_VAR
RESOURCE Resl ON Proc_386
VAR_GLOBAL
ALARM_FLAG : BOOL;
END_VAR
TASK IO_SCAN_TASK
(INTERVAL:= t#100ms,PRIORITY:= 0 ) ;
TASK CONTROL_TASK
(INTERVAL:= t#2 0 0ms,PRIORITY:= 1) ;
TASK PROG_TASK
(INTERVAL:= t#400ms,PRIORITY:= 2 ) ;
PROGRAM turbinel WITH PROG_TASK: turbine (
speed_setpoint := G_speed__setpoint/
runUp_time := G_runUp__Time,
speed_pv := %ID200,
actuator_output => %QW310,
loopl WITH CONTROLJTASK,
rampl WITH CONTROLJTASK,
io_scannerl WITH IO__SCAN_TASK ) ;
END_RESOURCE

RESOURCE Res2 ON Proc_8044


TASK LOG_TASK
(SINGLE:= G_Log_Event, INTERVAL:= t # 0ms);
PROGRAM loggerl WITH LOG_TASK: log (
data => G_LOG_DATA) ;
PROGRAM diagnosel : diagnostics;
END_RESOURCE

VAR_ACCESS
UNIT1_START: Resl.Turbinel.Start:
BOOL READ_WRITE;
UNIT1__ALARM: Res 1. ALARM_FLAG:
BOOL READ_ONLY;
UNIT1__LOG: G_Log_Event: BOOL READ_WRITE;
UNIT1_DATA: G_Log_Data: ARRAY[1. .10 0] OF
INT READ_ONLY;
END_VAR
END_CONFIGURATION
114 Programming industrial control systems using 1EC1131-3
This example assumes that a PLC system has two processors of type PROC_386
and PROCL8044.
There are two resources Resl and Res2 that exist on the two processors. Resl
contains a program instance turbine 1 which has input and output connections to
global variables and to direct PLC memory. Notice that within program turbine 1,
function block instances loopl, rampl and io_scannerl are configured to run
under the control of particular periodic tasks.
The global variables e.g. G_speed_setpoint declared at the configuration level,
can be accessed within all programs and function blocks.
Res2 contains two programs loggerl and diagnosel. Loggerl runs under the
control of an event driver task LOGJTASK. This will only execute when the
global variable changes from 0 to 1, i.e. on a rising edge, and then writes out data
to a global array GJLog_Data. The program diagnosel runs continually at low
priority in a background task.
A number of access variables are provided so that remote devices can reference
certain variables. For example, UNIT1_ALARM is the external reference to
ALARMJFLAG, a boolean global variable declared within resource Resl.
UNIT 1_START provides remote access to an input variable of program Turbine 1.
Using communications services, a remote operator station might for example
write to UNIT1_START to initiate a turbine run up sequence within the program
turbine 1 and monitor UN1T1_ALARM to check for alarms. By writing to
UNIT1JLOG, a data logging program loggerl is executed once to update log data.
This can then be read from the operator station via access variable UNIT 1JDATA.

Note: Variables within a resource are identified by a hierarchical name, starting


with the resource name followed by the name of the variable or instance
within it, e.g. Resl.Turbine 1.Start.

Summary

In this chapter we have reviewed most of the common elements of the IEC
languages. The main points covered in this chapter can be summarised as follows:
• The standard defines a diverse range of data types and functions suitable for
developing most types of application to be found in the industrial control
arena.
• It is possible for control software to be built from a range of well defined
elements, that include standard data types through to the larger software
elements such as functions and function blocks.
Chapter 3 Common elements 115
• There is support for hierarchical software structures. For example, elementary
data types can be used to define user derived data types which in turn can be
used in program organisation units such as functions and function blocks.
• Higher 'functionality' functions and function blocks can be readily built up
from definitions of more primitive types. This permits either a top-down or
bottom-up design approach to software development.

The following chapters will review how the behaviour of program organisation
units can be described using different textual and graphical languages.
Chapter 4

Structured Text

This chapter describes Structured Text, a high level textual language, which is the
first of the IEC languages in the set:
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List
and Sequential Function Chart.
Structured Text or ST can be used to express the behaviour of functions, function
blocks and programs. It can also be used within the Sequential Function Charts to
express the behaviour of steps, actions and transitions.
In this chapter we will review:
• How to assign values to variables;
• How to create simple and complex expressions;
• The use of arithmetic, boolean and comparison operators;
• Calling functions and function blocks;
• Using language constructs for conditional statements and repeating a number
of statements (iteration);
• How to create nested language constructs.

4.1 Structured Text language

Structured Text or ST is a high level language which has a syntax that on first
appearance is very similar to PASCAL. Although there are some minor
similarities to PASCAL, ST is a distinct language that has been specifically
developed for industrial control applications.
The ST language has a comprehensive range of constructs for assigning values
to variables, calling functions and function blocks, for creating expressions, for
:onditional evaluation of selected statements and for iteration, i.e. repeating
selected sections of code.
118 Programming industrial control systems using IEC1131-3
The language statements can be written in a fairly free style where tabs, line
feed characters and comments can be inserted anywhere between keywords and
identifiers, i.e. wherever a space character is required. For the software developer,
ST is fairly straightforward to learn and use. It is a language that is easy to read
and understand, particularly when written using meaningful identifiers and well
annotated with comments.
Structured Text is a general purpose high-level language for expressing
different types of behaviour involving a variety of different types of data. It is
particularly useful for complex arithmetic calculations

Note: The IEC 1131-3 standard only defines Structured Text as the language that
consists of statements that can be used to assign values to variables, for
example within function block and program bodies. However, many
implementors have come to regard all the textual language as defined in
Chapter 3 which is used to define common elements, such as variable
declarations, as also being part of the Structured Text language.

4.2 Assignment statements

Assignment statements are used to change the value stored within a variable or the
value returned by a function. An assignment statement has the following general
format:

X := Y;

where Y represents an expression that produces a new value for the variable X
when the assignment statement is evaluated. The value assigned should be of the
same data type as the variable.
The expression can be very simple, e.g. a literal constant, or complex, e.g.
involving many nested expressions. The assigned variable can be a simple or
multi-element variable such as an array or structure.
The following fragment of Structured Text contains a variety of assignment
statements:

TYPE Alarm
STRUCT
TimeOn : DATE_AND_TIME ;
Duration : TIME;
END_STRUCT;
END__TYPE
VAR
Chapter 4 Structured Text 119
Rate,Al REAL;
Count INT;
Alarm Alarm;
Alarm2 Alarm;
Profile ARRAY[1..10] OF REAL;
RTC1 RTC; (* Real time clock *)
END VAR

Rate := 13.1; (* Literal value i.e. constant *)


Count := Count + 1;(* Simple expression *)
Al := LOG(Rate); (* Value from a function *)
Alarml.TimeOn:= RTC1.CDT;(* Value from a function *)
(* block output parameter*)
Alarm2 := Alarml; (* Multi-element variable *)

(* Value from a complex expression assigned to *)


(* a single element of an array *)
Profile[3] := 10.3 + SQRT(( Rate + 2.0 ) *
( Al / 2.3 ));

Note: The PLC operating system should always ensure that assignment operations
are completed, i.e. are atomic operations. For example, when an assignment
involves copying the values for a multi-element variable, such as from one
array variable to another, it should not be possible to access any array
element until the array has been completely updated.

4.3 Expressions

Expressions are used to calculate or evaluate values derived from other variables
and constants. Structured Text expressions always produce a value of a particular
data type, which can be either an elementary or a derived data type. An expression
can involve one or more operators, variables and functions.
Composite expressions can be built up by nesting simpler expressions. This
allows ST to be used to perform complex arithmetic computations and data
manipulations involving different types of data.

Note: The programming station or ST compiler should always ensure that


expressions will produce values of the correct data type to match the
variable being assigned.

4.4 Operators

The standard defines a range of operators for arithmetic and boolean operations as
listed in Table 4.1.
120 Programming industrial control systems using IEC 1131-3
Table 4.1 Structured Text operators

Operator Description Precedence


(...) Parenthesised expression Highest
Function(...) Parameter list of a function, function
evaluation
** Exponentiation, i.e. raising to a power
Negation
NOT Boolean complement, i.e. value with
opposite sign
* Multiplication
/ Division
MOD Modulus operation
+ Addition
Subtraction
<, >, <=, >= Comparison operators
Equality
<> Inequality
AND,& Boolean AND
XOR Boolean exclusive OR
OR Boolean OR Lowest
Note: The standard allows each operator to have an equivalent function. For the
arithmetic operators' equivalent functions, see Chapter 3, Section 19;
similarly for the boolean operators' equivalent functions, see Chapter 3,
Section 21. The behaviour of the equivalent function is identical to that of
the related operator.

Examples of ST operator usage:

Area := PI * R * R;
V := K ** (-W * T ) ; (* K to the power of -W * T *)
Volts := Amps * Ohms;
Start := OilPress AND Steam AND Pump;
Status:= (Valvel = Open) XOR (Valvel = Shut);

4.5 Expression evaluation

Expressions are evaluated in a particular order depending on the precedence of the


operators and other sub-expressions. Bracketed i.e. parenthesised expressions
Chapter 4 Structured Text 121
have the highest precedence, followed by functions. Operators of the highest
precedence are evaluated first, followed by lower precedence operators, down to
the lowest. The precedence of the different types of operator is shown in Table
4.1, going from the bracketed expression, highest, down to the OR operator,
lowest. Where operators have the same precedence, they are then evaluated left to
right.

Consider the following example:


(Assume Speedl = 50.0, Speed2 = 60.0, Press = 30.0)

Rate := Speedl/10.0+Speed2/20.0-SQRT(Press+6.0);

Evaluation order:

Speedl/10.0 =5.0
Speed2/20.0 =3.0
Press + 6 . 0 =36.0
SQRT(Press+6.0) = 6 . 0
5+3 = 8 . 0 (Speedl/10.0 + Speed2/20.0)
8.0-6.0 = 2 . 0 (8 - SQRT(Press+6.0))
Rate is assigned the value 2.0

Consider the evaluation order with the addition of brackets added as shown:

Rate :=Speedl/10.0
+ Speed2/(20.0 - SQRT(Press+6.0));

Now the expression (20 - SQRT(Press+6.0)) has higher precedence and will be
evaluated before its value is used as a divisor for Speed2.
The value for Rate in this case will be:

Rate = 5 + 60/(20.0 - 6.0)


Rate = 5 + 60/14.0
Rate = 9.287

With boolean operators, the expression is only evaluated up to the point where the
value can be resolved.

For example consider the following expression (A, B, D and E are boolean
variables):

Startup := A AND B AND D AND E;


722 Programming industrial control systems using 1EC1131-3

If A is false, then StartUp will be assigned the value of FALSE, and the rest of the
expression will not be evaluated.

4.6 Statements

The Structured Text language has a range of constructs for calling function blocks,
conditional evaluation of statements and iteration, i.e. repeating sections of code.

4.7 Calling function blocks

A function block instance can be invoked (i.e. the code body can be executed to
update the data associated with the instance) by calling the function block instance
name with suitable input parameter values. If parameter values are not provided,
the current input parameter values as remaining from the last invocation are used.
If the function block instance has not been invoked before, any input parameters
that are not assigned will take default values as given in the function block type
definition.
The function block instance invocation has the following general form:

FunctionBlocklnstance(
InputParameterl:=ValueExpressionl,
InputParameter2:=ValueExpression2, ...);

The ValueExpression should create a value of a data type that matches the
function block input parameter. The values can be produced by expressions of any
complexity.

Example:

REAL 1 p v QUT | REAL

REAL —

CONTROLMODE —

Consider an instance 'Loopl' of a function block type called SimpleControl,


which could be, for example, a simple type of PID controller. The Mode input
parameter can take two values AUTO, MANUAL, i.e. it is an enumerated type;
assume the default value is AUTO.
Chapter 4 Structured Text 123
Fragment of Structured Text calling the function block Loopl:
VAR
Loopl : SimpleControl;
END_VAR

(* Initial invocation *)
Loopl(PV := Inputl.Out + Offset, SP := 100.0);

(* Further code ....*)

(* Subsequent invocation *)
Loopl(PV:= Inputl.Out + Offset, Mode:= MANUAL);
In the first invocation of Loopl, parameter Mode is not assigned, and therefore its
default value AUTO is taken. In the second invocation, the parameter SP is not
assigned; therefore the value as remaining from the last invocation is used, i.e.
100.0.
Note: The standard states that assigning values to function block inputs outside a
function block invocation is not permitted. However a number of
implementations of IEC 1131-3 allow such assignments.
For example: Loopl.Mode := Manual;
The new value assigned to Mode is used the next time Loopl is invoked.
Being able to assign values to function block input parameters ahead of
invocation is a useful facility. However such assignments may not be
portable to other products.

The values of function block instance output parameters are always available and
can be assigned to other variables.

Example:
FlowRate := L o o p l . O u t ;

This will assign FlowRate with the value generated by the last invocation of the
Loopl instance.
An amendment to the IEC 1131-3 1993 edition allows the value of an output
variable to be directly assigned to a variable using the => operator.

Example:

VAR
XI2 : REAL;
END_VAR

L o o p l ( P V : = %IW100, SP := 210.0,OUT => X 1 2 ) ;


124 Programming industrial control systems using IEC1131-3

4.8 Conditional statements

Conditional statements are provided so that selected statements will be executed


when certain conditions exist.

IF... THEN... ELSE

Selected ST statements can be evaluated depending on the value returned by a


boolean expression using the IF ... THEN construct. This takes the general form:

IF <boolean expression> THEN


<statements...>
END_IF;

The boolean expression can be any expression that returns a TRUE or FALSE
boolean result, e.g. the state of a single boolean variable or a complex expression
involving numerous variables.
Alternative statements can be executed using the IF ... THEN ... ELSE construct
in the form:

IF <boolean expression> THEN


<statements...>
ELSE
<statements...>
END__IF ;

Examples of conditional execution:

IF Collision THEN
Speed := 0;
Brakes := ON;
END_IF;
IF (Gate = CLOSED) AND
(Pump = ON) AND (Temp > 200.0) THEN
Control_State := Active;
ELSE
Control_State := Hold;
PumpSpeed := 10.0;
END_IF;

As IF ... THEN and IF ... THEN ... ELSE constructs are also statements, they can
be nested within other conditional statements to create more complex conditional
statements.
Chapter 4 Structured Text 125
For example:

IF FlowRate > 230.0 THEN


IF FlameSize > 4.0 THEN
Fuel := 4000.0;
ELSE
Fuel := 2000.0;
END_IF;
ELSE
Fuel := 1000.0;
END_IF;

Further statements can be conditionally executed within the IF...THEN construct,


using the ELSIF ... THEN... ELSE construct, which has the general form:

IF <boolean expression> THEN


<statements...>
ELSIF <boolean expression> THEN
<statements...>
ELSE
<statements...>
ENDJEF;

Any number of additional ELSIF sections can be added to the IF ... THEN
construct.

For example:

I F A>B THEN
D := 1;
ELSIF A = B +2 THEN
D := 2 ;
ELSIF A = B - 3 THEN
D := 4 ;
ELSE
D := 3 ;
END_IF ;

CASE

The CASE conditional statement is provided so that selected statements can be


executed depending on the value of an expression that returns an integer result e.g.
the value of a single integer variable or the integer value from a complex
expression. The integer expression should return a value of data type INT.
126 Programming industrial control systems using IEC 1131-3
The set of statements which have an integer selector value that matches the
value of the integer expression are executed. If no match is found, the statements
preceded by ELSE are executed.
The CASE construct has the following general form:

CASE <integer expression> OF


<integer selector valuel> : <statements...>
<integer selector value2> : <statements...>

ELSE
<statements...>
END_CASE;

The <integer selector value> can define one value, several values or a range of
values1.

1: (* Value 1 *)
2 , 3 , 4 M * Values 2,3 and 4 *)
5..10:(* Values 5 through 10 *)

Example:
CASE speed_setting OF
1 : speed := 10.0;
2 : speed := 20.4;
3 : speed := 3 0.0; fanl := ON;
4,5 : speed := 50.0; fan2 := ON;
6..10 : speed := 60.0; water := ON;
ELSE
speed = 0; SpeedFault := TRUE;
END_CASE;

An amendment to the IEC 1131-3 1993 edition allows enumerated variables to be


also used in CASE statements.

Example:

TYPE
SPEED: (STOPPED, SLOW, MEDIUM, FAST);
END_TYPE

VAR
pumpSpeed : SPEED;
rate : REAL;

*The .. construct is used to indicate a range of integer values, e.g. 5..10 means 5 to 10.
Chapter 4 Structured Text 127

alarm AT %Q141 : BOOL;


END_VAR
CASE pumpSpeed OF

STOPPED :: rate := O.Or


SLOW :: rate := 20.4;
MEDIUM :: rate := 30.0;

ELSE

rate := C); alarm := TRUE;

END CASE;

4.9 Iteration statements

Iteration statements are provided for situations where it is necessary to repeat one
or more statements a number of times depending on the state of a particular
variable or condition.
Care should be taken when using iteration statements to avoid situations that
result in creating endless loops. Iteration statements may also significantly
increase the time to execute different software elements, such as function blocks.

FOR... DO

The FOR ... DO construct allows a set of statements to be repeated depending on


the value of an iteration variable. This is an integer variable of data type SINT,
INT or DINT which is used to count the statement executions. This construct
takes the general form:

FOR <initialise iteration variable>


TO <final value expression>
BY <increment expression> DO
<statements. .-.>
END__FOR;

The FOR ... DO construct can be used to count iterations counting either up or
down and using any size increment until a final value is reached. The BY keyword
is optional; if omitted, the iteration variable will increase by 1.
The test to check whether the value of the iteration variable has reached the
final value is always made before executing the statements. It is therefore possible
for the final increment to cause the value of the iteration variable to exceed the
final value, in which case no further statements within the FOR ... DO will be
128 Programming industrial control systems using IEC1131-3
executed. The standard states that the final value of the iteration variable is
implementation dependent. It is therefore recommended that its value is not used
outside the FOR loop.
The statements within a FOR ... DO construct should not modify variables that
will affect the expressions for the final and increment values.
Examples:

FOR I:= 100 TO 1 BY -1 DO


channel[I].status := ON;
END_FOR;

FOR T := FarmSize-1 TO TankMax*2 DO


tankNo := T; vessel(tank:= T ) ;
END_FOR;

WHILE... DO

The WHILE ... DO construct allows one or more statements to be executed while
a particular boolean expression remains true. The boolean expression is tested
prior to executing the statements; if it is false the statements within the WHILE ...
DO are not executed. This construct takes the general form:

WHILE <boolean e x p r e s s i o n > DO


<statements...>
END_.WHILE

Example:

WHILE Value < (MaxValue - 10.0) DO


bridgel();
Value := Value + b r i d g e l . P o s i t i o n ;
END_WHILE

REPEAT... UNTIL

The REPEAT ... UNTIL construct allows one or more statements to be executed
while a particular boolean expression remains true. The boolean expression is
tested after executing the statements; if it is true, the statements within the
REPEAT ... DO are executed again. This construct takes the general form:

REPEAT
<statements...>
UNTIL <boolean expression>
END REPEAT
Chapter 4 Structured Text 129
Example:

tries := 0;
REPEAT
tries := tries + 1;
switchgearl(Mode := DISABLE);
UNTIL (switchgearl.State = OFF) OR (tries > 4)
END_REPEAT

EXIT
This statement can only be used within iteration statements and allows iteration
loops to be ended prematurely. When an EXIT statement is reached, execution
continues immediately from the end of the iteration construct; no further part of
the iteration construct is executed.

Example:

Fault := FALSE;
FOR I:= 1 TO 20 DO
FOR J := 0 TO 9 DO
IF FaultList[I,J] THEN
FaultNo := 1*10 + J;
Fault := TRUE; EXIT;
END_IF;
END_FOR;
IF Fault THEN EXIT; END_IF;
ENDJFOR;

In this example, a two-dimensional boolean array FaultList is scanned. If any


element is TRUE, the scan is terminated. An EXIT statement is used in each FOR
loop to terminate the loop when a fault is found.

RETURN

This statement can only be used within function and function block bodies and is
used to return prematurely from the code body. The RETURN statement causes
execution to continue from the end of the function or function block body. 2

2
It is recommended that the RETURN construct is used sparingly.'The behaviour of function and function blocks
with multiple exit paths may be difficult to understand.
130 Programming industrial control systems using IEC1131-3
Example:

FUNCTION_BLOCK TEST_POWER
VAR__INPUT
CURRENT, V0LTS1, VOLTS2, VOLTS3 : REAL;
END_VAR
VAR_OUTPUT
OVERVOLTS : BOOL;
END__VAR

IF VOLTS1*CURRENT > 100 THEN


OVERVOLTS := TRUE; RETURN;
END_IF;
IF VOLTS2*(CURRENT+10.0) > 100 THEN
OVERVOLTS := TRUE; RETURN;
END_IF;
IF VOLTS3*(CURRENT+20.0) > 100 THEN
OVERVOLTS := TRUE;
END_IF;
END__FUNCTION_BLOCK;

In this example, if any test fails, the output OVERVOLTS is set true and the
RETURN statement called to terminate the function block execution.

4.10 Implementation dependencies

The IEC 1131 standard sets no limits on the level of complexity that can be
expressed in a set of Structured Text statements. However, the standard does state
that some implementations may limit certain aspects of the language. For
example, there may be limitations on the length of expressions, length of
statements, length of comments, number of CASE selections and so on. These
limitations may arise because of ST compiler restrictions or because of
performance constraints in the target programmable controller.
A list of language features that may have implementation dependent limits is
given in an annex at the end of the IEC 1131-3 standard. Because each product
may apply different limits to these language features, this may affect the
portability of Structured Text between products.

4.11 Structured Text examples

The following examples demonstrate some of the language features that have been
reviewed in this chapter.
Chapter 4 Structured Text 131

4.12 Solving a quadratic equation

The following fragment of Structured Text calculates the two roots of a quadratic
equation; assume that all the variables are of the REAL data type.

tempA := b*b - 4*a*c;


IF tempA > 0.0 THEN
tempB := SQRT(tempA);
x_Rootl := (- b + tempB)/2*a;
x_Root2 := (- b - tempB)/2*a;
ELSE
msg := 'Imaginary Roots';
END_IF;

Note: In a real time control system, floating point calculations such as the square
root function shown in this example can use up significant processing time.
Where possible, save intermediate results in temporary variables to avoid
recalling identical code. It is also advisable to ensure that illegal operations
such as taking the square root of a negative number do not occur.

4.13 Calculating average, max and min values

The following ST example calculates the average, and the maximum and
minimum values of a set of values read in from a set of input channels.

TYPE T_Channel:
STRUCT
value : REAL; state : BOOL;
END_STRUCT;
END_TYPE
TYPE
T__Inputs: ARRAY[1..3 2] OF T_Channel;
END__TYPE

VAR
max: REAL :=0; (*Set to minimum possible value*)
min: REAL :=1000.0;(*Set to max. possible value *)
input : T_Inputs AT %IW13 0; (* Input channels *)
sum: LREAL :=0.0; (* To hold values total *)
average: LREAL;
END_VAR

FOR I:= 1 TO 32 DO
sum : = REAL_TO__LREAL (input [ I ] . value) + sum;
IF input[I].value > max THEN
max := input[I].value;
END_IF;
IF input[I].value < min THEN
132 Programming industrial control systems using IEC1131-3
min := input[I].value;
END_IF;
END_FOR;
average := sum / 32.0;

The FOR...DO statement is used to scan the values of all the input channels to
calculate the total value for the average, and the maximum and minimum values.
The sum is held in the double precision LREAL to improve the accuracy of the
result.

Note: This example could also be written using the selection functions MAX() and
MIN() as described in Chapter 3, Section 22.

4.14 Tank control function block

The following example describes how ST statements can be used to define the
body, i.e. the algorithm of a function block. Consider a function block that
controls a tank used to process some type of liquid, which might typically be in
part of a food manufacturing or pharmaceutical process. The tank can be filled and
emptied using fill and empty valves as depicted in Figure 4.1. The weight of the
tank is monitored by a load cell.
The function block monitors the tank Weight to determine whether the tank is
full or empty by comparing the Weight with two inputs FullWeight and
EmptyWeight.
The block provides a Command input which can have four modes, 1 to fill the
tank, 2 to hold the contents, 3 to activate a stirrer and 4 to empty the tank. If the
tank is in the correct State the appropriate valves are opened or shut to control the
tank level.
The stirrer can only operate if the tank is full; otherwise the command is
ignored.

StirSpeed TankControl
SINT Command FillValve — T._VALVE
REAL Weight EmptyValve —T._VALVE
REAL FullWeight StirSpeed —T_ _REAL
REAL EmptyWeight
Weight
EmptyValve

Figure 4.1 Tank control function block example


Chapter 4 Structured Text 133
(* Vessel State *)
TYPE T_STATE: (FULL,NOT_FULL,EMPTIED); END_TYPE

.(* Valve State *)


TYPE T_VALVE: (OPEN,SHUT); END_TYPE

FUNCTION_BLOCK TankControl

VAR_IN (* Input parameters *)


Command : SINT;
Weight : REAL;
FullWeight, EmptyWeight : REAL;
END_VAR

VAR_OUTPUT (* Output parameters *)


FillValve : T_VALVE := SHUT;
EmptyValve: T__VALVE := SHUT;
StirSpeed : REAL := 0.0;
END_VAR

VAR (* Internal variables *)


State : T__STATE := EMPTIED;
END_VAR

(* Function Block Body *)

(* Check the vessel state *)


IF Weight >= FullWeight THEN (* Is it full? *)
State := FULL;
ELSIF Weight <= EmptyWeight THEN (* or empty?*)
State := EMPTIED;
ELSE
State := NOT_FULL;
END_IF;
(* Process the command mode *)
CASE Command OF
1 : EmptyValve = SHUT; (* FILL Tank *)
FillValve = SEL(G:= State = FULL,
IN0:= OPEN, IN1:= SHUT);
2 : EmptyValve = SHUT; (* HOLD contents*)
FillValve = SHUT;
4 : FillValve = SHUT; (* EMPTY Tank *)
EmptyValve = OPEN;
END_CASE;

(* Control the stirrer speed *)


StirSpeed := SEL(G:=((Command = 3)
AND(State = FULL));
IN0:= 0.0; INI:=100.0);

END FUNCTION_BLOCK
134 Programming industrial control systems using IEC1131-3
The first IF... ELSIF statement in the function block body monitors the weight of
the tank and sets the tank state, i.e. Full, Not_Full or Empty. The CASE statement
checks the command mode and selects the appropriate valve settings.
Notice that the FillValve is set according to the comparison expression 'State =
FULL'. While the state is not FULL, this expression is false (i.e. 0) and FillValve
is set to the value of select function (SEL) input INO, i.e. OPEN. As soon as the
state is FULL, the expression becomes true (i.e. 1) and FillValve is then set to the
value of input IN 1, i.e. SHUT.
A further select function ensures that the StirSpeed is only set to 100.0 when the
Command mode is 3 and the tank state is FULL.
Typically a function block such as this will be associated with a task so that the
algorithm is re-evaluated, say, every 100 milliseconds.
In a real application additional code would generally be needed to check for
jammed valves, filter the weight signal which may be noisy due to liquid
movement, check for abnormal changes in tank weight and so on.

Summary

In this chapter we have reviewed all the features of the Structured Text language.
The main features can be summarised as:

• ST is an expressive language that can be used for programming a wide range


of industrial applications.
• It is a high level language with strong data type checking and a formal
syntax3.
• ST can be used to assign values to variables of different data types.
• Values can be calculated using expressions that can be simple or complex.
• The expressions can involve functions or values from function block outputs.
• ST has facilities for conditional evaluation of statements, for repeating
sections of code and for calling functions and function blocks.
• ST can be used to describe the behaviour of program organisation units, i.e.
functions, function blocks and programs.

A full set of production rules that define the syntax of all textual components of the languages, including
Structured Text, is given in Annex B of the IEC 1131-3 standard.
Chapter 5

Function Block Diagram

This chapter describes Function Block Diagram, the first graphical language of the
IEC languages in the set:
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List
and Sequential Function Chart.
Function Block Diagram or FBD can be used to express the behaviour of
functions, function blocks and programs as a set of interconnected graphical
blocks. It can also be used within the Sequential Function Charts to express the
behaviour of steps, actions and transitions.
FBD is based on viewing a system in terms of the flow of signals between
processing elements. This is very similar to signal flows depicted in electronic
circuit diagrams.
In this chapter we will review:

• Common graphical symbols and conventions that apply to FBD and also to
the other graphical languages, i.e. Ladder Diagram and Sequential Function
Chart;
• How to depict both simple and complex expressions;
• How to show signal flow between functions and function blocks;
• How to assign values to variables;
• How to handle signal feedback;
• The rules for function block evaluation;
• Restrictions on the portability of code between ST and FBD.
136 Programming industrial control systems using IEC1131-3

5.1 FBD graphical elements

The standard defines types of lines and interconnections for all the graphical
languages, i.e. for Function Block Diagram, Ladder Diagram and Sequential
Function Chart. IEC 1131-3 allows normal characters such as _ and 1 to be used
to depict graphical objects; this is called semi-graphical representation. However,
the standard also allows full graphical representation. The use of full graphics has
been adopted by most of the current implementations of the standard.
The graphical representation used in the Function Block Diagram language is
shown in Table 5.1.

Table 5.1 Function Block Diagram graphic representation


Graphical feature Semi-graphic form Full graphic
Horizontal and
vertical lines

Interconnection of
horizontal and
vertical signal flows

Crossing horizontal
and vertical signal
flows
i i
Signal flow corners
--+ +

Blocks with
connections

—i i

Connectors ->LOAD JOB>


-> LOAD JOB>
>LOAD JOB>- > LOAD JOB>
Chapter 5 Function Block Diagram 137
There may be minor differences between the full graphic representation shown
in Table 5.1 and the forms used in some implementations of the standard. Full
graphic representation is not defined in the standard as the formats of lines, boxes
and connections may depend on the resolution and capabilities of the graphics
system.
Some implementations may adopt alternative graphic formats because of
particular company house styles. The standard describes the main graphical
features but not the fine detail. For example, a function block may have right
angled or rounded corners, be shown with a shadowed outline or be filled with a
contrasting colour or shade.
The standard does not specify the format of line intersections and cross-overs in
full graphic implementations. Some means of distinguishing between cross-overs
and junctions will be required.
Note: In this book the following conventions have been used in Function Block
Diagrams.

Line cross-overs

Tee junctions L

5.2 Methodology

The Function Block Diagram language, FBD, can be used to express the
behaviour of programs, functions and function blocks. It can also be used to
describe steps, actions and transitions within the Sequential Function Chart
language as reviewed in Chapter 8.
Function Block Diagram should be used where the problem involves the flow of
signals between control blocks. An FBD network can be regarded as analogous to
an electrical circuit diagram where electrical connections depict signal paths
between components. Typical uses of FBD include describing control loops and
logic. Some program developers who are familiar with electrical circuits or using
graphical programming techniques may prefer to use FBD to using a textual
language such as Structured Text.
Within FBD certain graphical conventions apply. A function block is depicted
as a rectangular block with inputs entering from the left and outputs exiting on the
right. Function block type name is always shown within the block, whereas the
name of the function block instance is always shown above the block. The formal
names of function block inputs and outputs are shown within the block at the
appropriate input and output points.
138 Programming industrial control systems using IEC1131-3
To avoid cluttering diagrams, implementations of the FBD editor on some
program stations only depict input and output parameters using their 'pin'
numbers. In this case, the full input and output parameter names are accessible by
other means, for example by a command from a pull-down menu.
The order in which inputs and outputs are depicted in the function block should
always be the same.

LOADED_WT
TankControM
Switchi

ThumbSwitch TankControl

32JHSJ234 - Input Position Command

>AVE_WEIGHT > Weight RHValve - RLL

FullWeight BnptyValve - EMPTY

2.5 BnptyWeight StirSpeed - STIR


Weigheri

Weigher

EMPTYJUXJ Offset Weight

Weighed
Weigher > AVEJ/VEIGHT >

Offset Weight

ZO

Figure 5.1 Tank control Function Block Diagram example

The main features of the Function Block Diagram language are shown in Figure
5.1 which depicts part of a tank filling program. TankControl 1 is the name of an
instance of the TankControl function block type. The 'Command' input, which
selects the mode of the TankControl function block, is driven by the 'Position'
output from function block Switchi; this is an instance of function block type
ThumbSwitch. This function block reads the current value from a thumbwheel
switch and represents the value at the output 'Position'.
The average weight of the tank is calculated from the function blocks Weigher 1
and Weigher2 using ADD and DFV functions - also depicted as rectangular
blocks. The signal AVE_WEIGHT is the name of a cross-diagram connector; it is
used to aid readability and avoid a graphical connection that would be difficult to
draw. It has no significance as far as the program behaviour is concerned.
LOADED_WT is the name of a variable supplying the value of the 'FullWeight'
input of the TankControl 1 block.
Chapter 5 Function Block Diagram 139
Notice that literal constants such as 2.5 can be used as direct input values to
functions and function blocks.
Outputs from functions and function blocks can be used to supply values to
variables. The outputs FillValve, EmptyValve and StirSpeed of the TankControll
function block are used to update variables FILL, EMPTY and STIR.

Note: The LOADED_WT signal path has been deliberately placed at the top of
the diagram to demonstrate a signal path cross-over. To aid readability,
diagrams should be arranged to minimise signal path cross-overs.

For further details on the TankControl function block see Chapter 4, Section 14.

5.3 Signal flow

In a Function Block Diagram network, the signals are considered to flow from the
outputs of functions or function blocks to the inputs of other functions and
function blocks.
The outputs of function blocks are updated as a result of function block
evaluations. Changes of signal states and values therefore naturally propagate
from left to right across the FBD network.

Note: The standard implies that signal flows that represent different data types are
all depicted using continuous black lines of the same thickness. However,
some program station implementations may choose to represent signal
flows of particular data types using different colours and line styles.

Negation of boolean signals

When using boolean signals, negated inputs of functions and function blocks can
be shown using a small circle at the input point. Similarly, negated outputs can be
shown by placing a small circle at the output.
Implementations that do not support this feature may use the NOT function for
signal value negation.
In Figure 5.2, the upper and lower FBD networks are functionally equivalent.
140 Programming industrial control systems using IEC 1131-3
Sw1
Pumpi
PumpMotor

Inhibit Status P1_Sp

Trip

VA12

Sw1
Pumpi
PumpSwitch
pos PumpMotor
P1_Sp
Inhibit Status NOT
X3 ADD
NOT Trip
TEST1 NOT
OR

VA12

Figure 5.2 Negating boolean signals example

Feedback paths

The standard allows signal paths to be fed back from function block outputs to
inputs of blocks on the left of the network, i.e. to the inputs of preceding blocks,
as shown in Figure 5.3.

Loopi Loadi

MainControl Simulator
ProcessValue Output FlowRate Level
200.0 SetPoint Bror Model

SECD_ORDER

— HIGH_ERROR
0.15

Figure 5.3 FBD feedback example


Chapter 5 Function Block Diagram 141
In Figure 5.3, an explicit feedback path is shown where the output Level from
function block Loadl is fed back to the input Process Value of the preceding block
Loopl.
Implicit feedback paths can also be created by using connectors that link the
output parameters from blocks on the right of the network to inputs of preceding
blocks.
A feedback path implies that a value within the feedback path is retained after
the FBD network is evaluated and used as the starting value on the next network
evaluation. However there is no provision in IEC 1131-3 to designate the point in
the feedback path where it is broken between network evaluations.
Consider Figure 5.3: there are two ways the feedback path can be evaluated. If
function block Loopl is evaluated before Loadl, then at the start of each network
evaluation, input Process Value will be set to the value of Loadl.Level as retained
from the previous evaluation. Alternatively, if Loadl is evaluated before Loopl,
then input FlowRate will be set to the value of Loopl.Output as retained from the
previous evaluation.
As the same FBD network can be interpreted by a PLC system to imply either
order of evaluation, the behaviour of networks with feedback paths may vary
subtly between different implementations.

Note: When an FBD network is initialised, the first function block input parameter
in a feedback path will be initialised using the input's initial value as
defined within the function block type definition.

The standard states that implementations may provide a facility so that the order in
which function blocks are evaluated in a network can be defined explicitly, for
example by giving the function block evaluation order in a list. However, the
technique to be used is not defined.

5.4 Network layout

Function Block Diagram networks should be arranged so that the main signal
flows can be traced easily. Where possible,blocks should be placed to reduce
signal path cross-overs and unnecessary changes in signal path direction.

FBD network limitations

The standard does not define specific limitations on the size or complexity of an
FBD network. However, it does allow an implementation to limit the number of
142 Programming industrial control systems using IEC1131-3
function block type specifications and the number of function block instances that
can be supported in one configuration. Such limits may therefore affect the
complexity and size of FBD networks that can be produced when using certain
PLC products.

5.5 Function execution control

By default the execution control of functions in an FBD network is implicit from


the position of the function in the network. For example, in Figure 5.3, the
comparison function '>=' is evaluated after function block Loopl.
However, the control of functions can be made explicit by using the function
enable input EN. The EN input is a boolean variable that allows a function to be
selectively evaluated. When the EN input is TRUE the function will be evaluated.
However, while the value of EN remains FALSE the function will not be
evaluated and its output value will not be generated.
The function output ENO is a boolean variable that indicates that the function
has completed its evaluation by the ENO value changing from FALSE to TRUE,
i.e. a rising edge. By chaining functions together using EN and ENO, it is possible
to trigger certain values to be generated when particular conditions arise.
Consider Figure 5.4: as long as either boolean variable add_Acid or pH_High is
false, the assignment ':=' and ADD functions are not evaluated. When add_Acid
and pH_High are both true, the EN input of the assignment function is asserted
TRUE. This causes the assignment function to be evaluated and move the value
100.0 to the variable StirRate. When the function evaluation is complete, the
output ENO is asserted which in turn causes the ADD function to be evaluated.

add Acid AND


pH High i EN ENO

ADD
EN ENO —• speedOK
speec
— pumpSpeed
offset

Figure 5.4 Explicit function execution example


Chapter 5 Function Block Diagram 143
Note: The standard is unclear on the use of output values from functions that have
EN set false.
Note: A function that has an internal error, such as an arithmetic overflow, will
not assert ENO when the evaluation is complete. The value of ENO can
therefore also be used to indicate when the result of a function is valid.

5.6 Jumps and labels

It is possible to transfer control from one part of an FBD network to another using
a graphical 'jump' facility. Sections of FBD networks can be identified using
'labels'. By assigning a boolean signal to a label identifier, it is possible to transfer
control to another part of the network, i.e. associated with the label.
Boolean signals that cause a jump in network evaluation order should be
followed by a double arrow and the label identifier.

GasLevel —<
' GAS_ALARM
0.15 — M i

1 < GAS_OK

GAS ALARM:
ENABLE wmmmm
AND
SIREN
MX12 mmmum

Figure 5.5 FBD jump example

In Figure 5.5, when the value of GasLevel exceeds 0.15, control is transferred to
the section of the FBD network identified by the label GAS_ALARM.

Note: BBC 1131-3 does not clarify what happens to the rest of a network after a
jump has been triggered. One interpretation is that all linked blocks in the
network are evaluated before the jump is made. An alternative
interpretation is that the network evaluation ceases immediately, and the
network identified by the label is started. For this reason, IEC guideline on
using IEC 1131-3 now recommends that jumps within the FBD network
should not be used.

If selective evaluation of FBD networks is required, then place the different FBD
sections within action blocks of a Sequential Function Chart.
144 Programming industrial control systems using IEC1131-3

5.7 Network evaluation rules

The order in which function blocks and functions within an FBD are evaluated
will vary from product to product. The standard does not attempt to define a strict
network evaluation order, although, generally, functions and function blocks on
the left of the network will be evaluated before those on the right. Some
implementations may also evaluate blocks in an order that runs from top to bottom
of the diagram.
However, the following rules should always apply and ensure that data
transferred between functions and function blocks are consistent.

• 'No element in a network shall be evaluated unless the states of all inputs have
been evaluated.' In other words, a function or function block should not be
evaluated unless all of the input values that come from other elements are
available.
• The evaluation of a network element shall not be complete until the states of
all of its outputs have been evaluated,' i.e. outputs of a function block should
not be considered available until all outputs have all been updated.
• 'The evaluation of a network is not complete until the outputs of all of its
elements have been evaluated.' All outputs of all functions and function
blocks should be updated before an FBD network is considered to be
complete.
• When data are transferred from one FBD network to another, all the values
coming from elements in the first network should be produced by the same
network evaluation. The second network should not start evaluation until all
the values from the first network are available.

The last rule is particularly applicable to the situation where sets of function
blocks in an FBD network are running under the control of different tasks. For
example, a set of function blocks under the control of a task that executes every
100 milliseconds may produce output values that are transferred to a second set of
function blocks under the control of a different task, for example, that runs every
500 milliseconds.
In this situation, the values of outputs transferred from the first set of blocks to
the second should all be created by the same 100 millisecond task evaluation.
Chapter 5 Function Block Diagram 145

5.8 Portability between ST and FBD

There is an assumption by many implementors of the IEC 1131-3 standard that


there should be a one to one correspondence between all of the IEC languages. In
other words, it should be possible to translate any language into any one of the
others. However, it has never been the deliberate intention of the IEC working
group that a 100% correspondence should exist. In practice, there is a limited set
of core features in each language that can be translated successfully into the other
languages. There are also features that are very difficult and, in a few cases,
impossible to translate.
Most constructs used in FBD networks can be translated into Structured Text.
ST can easily represent the invocation of functions and function blocks and the
associated passing of parameter values. For example, the following Structured
Text statements are equivalent to the FBD network given in Figure 5.3:

VAR
MainControl : Loopl;
Simulator : Loadl;
END_VAR

(* Invoke the function blocks with *)


(* parameter connections *)
Loopl(ProcessValue := Loadl.Level,
SetPoint := 200.0 ) ;
Loadl(FlowRate : = Loopl.Output,
Model := SECD_ORDER);
HIGH_ERROR := Loopl.Output >= 0.15;

Note: A number of functions, such as the greater or equal comparison *>=', can be
represented in Structured Text as either operators or functions.

Functions that have explicit execution control as discussed in Section 5.5 cannot
be represented in Structured Text; there is no syntax for handling functions with
the second output ENO!
Translation of Structured Text into FBD networks is even more problematic.
Constructs such as IF...THEN, CASE, FOR, WHILE, REPEAT cannot be directly
represented graphically except with some ingenuity. It is also not possible to
reference elements in an array or structure. For example, the following ST
statements have no FBD equivalent:

FOR I := 1 TO 100 DO
rate[I] := 100;
END_FOR;
146 Programming industrial control systems using IEC1131-3
Structured Text should be regarded as the language with the feature super-set.
Translation from FBD to ST is always possible provided that explicit function
execution control is not used. Translation in the other direction from ST to FBD
can only apply to a subset of the ST constructs.

5.9 FBD function block example

DAMPER

BOOL ReqOpen DemandOpen BOOL

BOOL ReqClose DemandClose BOOL

BOOL OpenLS Discrepancy BOOL


BOOL CloseLS

TIME MoveTimeOut

Position

ReqOpen DemandOpen

ReqClose — DemandClose
Timeri

OpenLS Ol I I ' M IN Q I— Discrepancy


I . 1 PT
DemandClose
CloseLS
MoveTimeOut

Figure 5.6 Damper function block example

Figure 5.6 is an example of a Function Block Diagram being used to describe


the behaviour of a function block for controlling an air damper. Such an air
damper might, for example, be used to control the air flow into a furnace or the air
for ventilating a region of plant.
The signals ReqOpen and ReqClose signal the requested position for the
damper. The requested position is held in an RS bistable function block. The
output from the * Position' bistable and the inverted output are used to produce the
Chapter 5 Function Block Diagram 147
signals DemandOpen and DemandClose. These signals drive actuators that move
the air damper into the requested position.
Limit switches on the damper signal back the actual position of the damper on
the input signals, OpenLS and CloseLS. The limit switch signals are compared
with the demanded position using the AND functions. If either check fails, e.g. the
position Open is demanded but the limit switch signal OpenLS is not true, the 'on
delay' timer Timerl is started.
If the damper fails to move to the requested position and assert the required
limit switch within the time given by the MoveTimeOut input, Timerl will raise
the Discrepancy signal.

Note: The RS bistable and TON timer are IEC standard function blocks as
described in Chapter 9.

5.10 Continuous function chart

There is a special form of function block diagram which is used to depict the top
level structure of a resource and the assignment of programs and function blocks
to tasks: see Chapter 3, Section 42. Although this form of FBD is not given a
particular name in the standard, it has become commonly known as a 'Continuous
function chart'.
The main difference between a Continuous function chart and a Function Block
Diagram is that it also shows the resource and task assignments. Each function
block is depicted with the name of the task which controls its execution, as shown
in Figure 5.7. Programs may also have the name of their task depicted in a similar
manner in a text box at the bottom of the program definition.
If a function block within a program executes under the same task as its parent
program, the task association is said to be implicit. In this case, the task name does
not need to be shown in the function block graphic.
The format of Continuous function charts is shown in Figure 5.7. Many of
the smaller details, such as showing the variables that are assigned to function
block inputs, have not been shown to aid clarity.
148 Programming industrial control systems using IEC1131-3

Packager
Status
Speed Rate

Figure 5.7 Continuous function chart example

Summary

Function Block Diagram is an ideal language to express control behaviour where


the solution can be considered as a network of software blocks. FBD is very
similar to an electrical circuit diagram, where the lines between the blocks depict
signal flows.

• FBD can be used in a wide range of problems including boolean logic and
'closed loop' control.
• Although the standard provides a mechanism through the 'jump' construct
for controlling the execution of sections of an FDB network, FBD is only
really suitable for behaviour that is continuous. For problems that involve
sequencing of some form, the behaviour should be expressed using the
Sequential Function Chart (SFC) language as discussed in Chapter 8.
Chapter 5 Function Block Diagram 149
• There is not always a one-to-one correspondence between Function Block
Diagram and the other languages. FBD networks can generally be translated
into Structured Text; translation from ST to FBD is not always
straightforward and, in some cases, is not possible.
• The FBD language can also be used to show the top level structure of
resources and programs in a form called Continuous function charts. ,
Chapter 6

Ladder Diagram

In this chapter we will review Ladder Diagram, the second graphical language of
the EEC languages in the set:
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List
and Sequential Function Chart.
Ladder Diagram can be used to express the behaviour of functions, function
blocks and programs, and also actions and transitions in Sequential Function
Charts.
In this chapter we will review:

• The graphical symbols and conventions used to describe Ladder Diagrams;


• How Ladder Diagram is based on a concept of 'power flow' between contacts
which can control the operation of notional 'coils' that represent variables;
• How to develop complex boolean logic expressions;
• How to control functions and function blocks through using connections on a
Ladder Diagram 'rung';
• How to control ladder rung execution using 'jumps' and 'labels';
• Restrictions on the portability of code between ST, FBD and LD.

6.1 LD background

Ladder Diagram has been developed by the IEC by considering the most
commonly used symbols and terminology used in mainstream PLCs. To anyone
who is already familiar with writing programs using 'relay ladder', the symbols
defined in IEC 1131-3 will not bring any unwelcome surprises.
152 Programming industrial control systems using IEC1131-3
If you are not familiar with this form of graphical programming, it is
recommended that you read the introduction given in Chapter 1 where some of the
main features and limitations of the language are discussed.
Ladder Diagram is based on a technique used to design logic using relays. A
Ladder Diagram always has a left hand vertical power rail that notionally supplies
power through contacts spread out along horizontal rungs.
Each contact represents the state of a boolean variable. For example, a contact
may depict the state of a limit switch or heat sensor. When all contacts in a
horizontal rung are made, i.e. in the 'true' state, power can flow along the rail and
operate a coil on the right of the rung. Contacts which are normally open present a
'true' state when the contacts are closed. Conversely contacts that are normally
held closed, present a 'true' state when the contacts are opened. By arranging
alternative paths through a network of contacts it is possible to describe various
logic conditions.

Pum
DrainShut DoorShut PD°wn

Manual
H r—

\ Power Flow j Right Power rail


Left Power rail Contact Cof/

Figure 6.1 Ladder Diagram concepts

Figure 6.1 depicts the main features of the Ladder Diagram language. In this
example, PumpDown represents a relay coil which is activated when power is able
to flow from the left hand power rail. PumpDown is actually a boolean variable
which is set to a true state either when contacts DrainShut and DoorShut are ON,
or when contact Manual is ON. The contacts represent the states of boolean
variables.
Using the Structured Text language, the Ladder Diagram in Figure 6.1 is
equivalent to:

PumpDown := (DrainShut AND DoorShut) OR Manual;

In Ladder Diagram a contact is assumed to have states ON and OFF (for a


normally open contact these states are sometimes referred to as CLOSED and
Chapter 6 Ladder Diagram 153
OPEN) which are equivalent to boolean states 1 (true) and 0 (false). A contact
always represents the state of the associated boolean variable. A contact provides
a 'read only' access to the state of the boolean variable; it cannot be used to
change the value of the variable.
On the other hand, a coil provides 'write only' access and can only be used to
update the state of the associated boolean variable when notional power flow can
occur via contacts from the left hand power rail.
The standard allows the use of the right hand power rail to be optional. Ladder
Diagrams are still quite understandable if the right power rail is not shown.
The network that is associated with the logic for one coil is called a 'ladder
rung'.

6.2 LD graphical symbols

The graphical representation used in the Ladder Diagram language is shown in


Table 6.1. There may be minor differences between the full graphic representation
shown in Table 6.1 and the forms used in some implementations of the standard.

Table 6.1 Ladder Diagram graphic representation

Graphical feature Semi-graphic form Full graphic


Horizontal link
(power flow)
Interconnection of
horizontal and
vertical power
flows

Left hand power |


rail connection I

1
Right hand power
rail connection I
. +

Connectors >LOAD_JOB> -> LOAD_JOB>


(same as for FBD)
LOAD_JOB>
>LOAD_JOB>
154 Programming industrial control systems using IEC1131-3
Full graphic representation is not defined in the standard for Ladder Diagram
because the formats of lines, boxes and connections may depend on the resolution
and capabilities of the graphics provided by the programming system.
The symbols for different types of contacts and coils are shown in Tables 6.2,
6.3 and 6.4. Although not shown in these tables, the name of the associated
variable is always displayed directly above the symbol as shown in Figure 6.1.
A range of different contact types is provided to detect normal and inverse
states, and rising and falling edges of power flow of the associated boolean
variable.

Table 6.2 Ladder Diagram contact symbols

Graphical feature Semi-graphic Full graphic


form
Normally open contact
Normally open contact where power I I
flow occurs from left to right when the
associated variable is 1.
Normally closed contact
Normally closed contact where power IM |/ [
flow occurs from left to right when the
associated variable is 0.
Positive transition-sensing contact
Positive rising edge transition contact IpI
where power flow occurs for one
Ladder Diagram evaluation when the
associated variable changes from 0 to
J.
Negative transition-sensing contact
Negative falling edge transition INI
contact where power flow occurs for
one Ladder Diagram evaluation when
the associated variable changes from 1
to 0.

Note: The exclamation mark *!' can be used in place of the vertical bar T in the
semi-graphical symbols for contacts.
Chapter 6 Ladder Diagram 155
Table 6.3 Ladder Diagram coil symbols

Graphical Feature Semi-graphic Full graphic


form
Coil
The coil is set to the state according ( ) ( }
to the power flow coming from the
left hand link. If power flow is ON,
the coil state is set to ON.
Negated coil
(l}
The negated coil is set to the (/)
opposite state to the power flow
coming from the left hand link. If the
power flow is ON, the coil state is
set to OFF.
SET coil
This coil is set to the ON state when (s) (S)
there is power flow coming from the
left hand link. The coil remains set
until it is RESET.
RESET coil ^
(R)
This coil is reset to the OFF state Ov
when there is power flow coming
from the left hand link. The coil
remains OFF until it is SET.

Coil symbols allow the associated variable to be set or cleared on the presence
of power flow. The SET and RESET coils allow a variable to be latched on and
then cleared by a different condition some time later.
A number of special coil symbols are provided as shown in Table 6.4. The
retentive coils can be used where the states of variables need to be held through
PLC power failure and resumption. This type of coil may be required for holding
the state of critical variables such as plant operation modes, positions of interlocks
and so on, i.e. variables that need to be in the correct state when the PLC is
powered up following power failure.
Variables associated with retentive coils are automatically declared using
VAR RETAIN.
156 Programming industrial control systems using IEC 1131-3
Table 6.4 Ladder Diagram special coil symbols

Graphical feature Semi-graphic Full graphic


form
Retentive memory coil
The same behaviour as the normal (M) (M
coil, except that the state of the
associated variable is retained on PLC
power fail.
SET retentive memory coil
The same behaviour as the SET coil (SM)---
except that the state of the associated
variable is retained on PLC power
fail.
RESET Retentive Memory coil
(RM)---
The same behaviour as the RESET
coil except that the state of the
associated variable is retained on PLC
power fail.
Positive transition-sensing coil
If the power flow on the left hand link (P)
changes from OFF to ON, the variable
associated with the coil is set ON for
one ladder rung evaluation.
Negative transition-sensing coil
If the power flow on the left hand link (N)
changes from ON to OFF, the variable
associated with the coil is set ON for
one ladder rung evaluation.

The positive and negative transition-sensing coils are used to detect a change in
state in the power flow. With these types of coil, the associated variable is only set
ON for one evaluation of the Ladder Diagram.

Switch Trigger
Chapter 6 Ladder Diagram 157
Consider the example of a contact connected directly to a positive transition-
sensing coil. The behaviour of the coil over a number of Ladder Diagram
evaluations is shown in the following table - notice that the Trigger variable is
only set ON once when the Switch changes from OFF to ON.

Evaluation Switch Trigger


1 OFF OFF
2 ON ON
3 ON OFF
4 OFF OFF

6.3 Methodology — relay logic

From the nature of electrical circuits, contacts in a horizontal rung represent


logical AND operations. Alternative paths from the main rung provided by
vertical paths represent logical OR operations.

A1 A2 A3 XI

Figure 6.2 Ladder Diagram AND logic example

In Figure 6.2, the Ladder Diagram logic is equivalent to the following


Structured Text:

XI : = A l AND A2 AND A3

The use of alternative power flow paths via other horizontal rungs connected by
vertical paths provides logical OR operations.
In Figure 6.3, the addition of alternative power paths modifies the logic. The
Structured Text statement equivalent for this rung is now:

XI := ( Al OR Bl AND A2 AND A3 ) OR ( Cl AND C2 ) ;


158 Programming industrial control systems using IEC1131-3

A2 A3 X1

C1 C2

Figure 63 Ladder Diagram OR logic example

6.4 Connecting function blocks

Function blocks can be connected into Ladder Diagram rungs provided that they
have boolean inputs and outputs. Inputs can be driven directly from Ladder
Diagram rungs; outputs can provide power flows for driving coils.

MOTOR_X1

SW1 MOTOR_CONT INHIB 2 MTR 2


P START MOTOR-
SW2
STOP
P
FORWARD

2300.0 - MAX SPEED SPD 2


BATCHCNT- CYCLES

Figure 6.4 Connecting function blocks example

Figure 6.4 is an example of a function block connected into a ladder rung being
used to control an electric motor. Notice that boolean inputs START and STOP^
are driven directly by power flows controlled by contacts. In this case, SW1 and
SW2 are boolean variables that represent the states of external push switches. The
contacts are positive transition-sensing so that the function block only receives a
power flow when the switches are first depressed.
Chapter 6 Ladder Diagram 159
The FORWARD input is connected directly to the left power rail indicating that
this input is permanently in the ON (true) state.
Inputs that are not of the boolean data type may be connected to named
variables. In this example, the CYCLES input value comes from a variable
BATCHCNT. Inputs may also be asssigned values from outputs of other function
blocks.
In addition, inputs may be assigned constant values, e.g. a literal value such as
2300.0.
Boolean function block outputs may be connected into horizontal power flows.
In this example, variable MTRJ2 is only set ON when the function block output
MOTOR is ON and the variable INHIB_2 is OFF.
Note: The standard states that each function block needs at least one boolean input
connected via a horizontal rung to the left hand power rail in order to be
evaluated. It is unclear in the text whether function blocks will be evaluated
when all such power flows are OFF due to the states of contacts in the
horizontal rungs.
The IEC technical report on the application of IEC 1131-3 states that the
evaluation of function blocks can be made explicit using the EN and ENO
parameters as discussed in the next section.

6.5 Using functions in LD

Functions may be provided with an additional boolean input EN and an additional


output ENO for use in the graphical languages. EN provides a power flow signal
into a function. When EN is ON, i.e. 1, the function is enabled and can evaluate its
inputs to produce an output. When the function evaluation is complete, the ENO
output can be used to provide power flow to other functions or to a coil. The use
of EN and ENO is also discussed in Chapter 3, Section 28.

CHECK MAX
— P EN ENO

TEMPI •
TEMP2 •
TEMP3 -

1000.0
Figure 6.5 Using EN and ENO example
160 Programming industrial control systems using IEC1131-3
Figure 6.5 depicts an example of using EN and ENO to control the evaluation
of functions. Both functions are dormant until the variable CHECK changes from
OFF to ON. The positive transition-sensing contact causes power to flow into
function MAX for one evaluation. The MAX function delivers the maximum
value of variables TEMPI, TEMP2 and TEMP3 at its output and at the same time
sets it's ENO output to ON.
This, in turn, allows the 'greater than' (GT) comparison function to be
evaluated. It compares the value from the MAX function with 1000.0. If the value
is greater, the GT function sets its output ON that changes the state of variable
COOL to ON; otherwise COOL remains OFF. In either case, when the
comparison is complete, the ENO is set ON, which sets variable COMPLETE to
ON, indicating that the temperature check has been completed.
An amendment to the 1993 edition of IEC 1131-3 for the second edition
proposes that function blocks may also have the EN and ENO execution control
input and outputs.

6.6 Feedback paths

It is possible to create Ladder Diagram rungs which contain feedback loops, i.e.
where one or more values used in contacts, and as function and function block
inputs, come from variables that are updated when the rungs are evaluated.

START PERMIT FAN

Figure 6.6 LD feedback example

An example of a feedback path in Ladder Diagram is shown in Figure 6.6.


Unlike the use of feedback in Function Block Diagram, in Ladder Diagram there
is no ambiguity about where the feedback path is broken between evaluations. In
Ladder Diagram, all external input values such as those associated with contacts
are gathered before each rung is evaluated.
Chapter 6 Ladder Diagram 161
In this example, where the rung uses the state of its own output, the value of
FAN associated with a contact is always the value resulting from the previous
evaluation.
However, if the value of FAN is used in any following rungs, the latest
evaluated state is used.

6.7 Jumps and labels

Using a graphical jump it is possible to transfer control from one part of an LD


network to another identified by a label. Assigning a power flow to a label
identifier transfers control to another part of the network that is associated with
the label.

PRESSURE

/l
OXYGEN
SPARGE

SPARGE:

SPG ENABLE SPARGER

Figure 6.7 LD jump example

In Figure 6.7, when variables OXYGEN or PRESSURE are OFF, control is


transferred to the section of the LD network identified by the label SPARGE. The
transfer cannot occur until the network section containing the jump has been fully
evaluated.

Note: IEC 1131-3 does not clarify what happens to the rest of an LD network after
a jump has been actioned. It is assumed that the ladder rungs following a
jump are not evaluated.
For this reason, the EEC guidelines on using EEC 1131-3 now recommend
that jumps within an LD network should not be used.
If selective evaluation of an LD network is required, then place the different
LD sections within action blocks of a Sequential Function Chart.
162 Programming industrial control systems using IEC1131-3

6.8 Network evaluation rules


The order in which rungs of a Ladder Diagram network are evaluated is specified
in the standard. PLC ladder rungs are always scanned from the top of a Ladder
Diagram to the bottom.
This follows the normal convention; PLCs scan ladder programs from the first
rung through to the last; the rungs are evaluated in the same order as drawn.
The following rules, that also apply to Function Block Diagram networks,
ensure that the result of an LD network evaluation is unambiguous and consistent:

1. 'No element in a network shall be evaluated unless the states of all inputs
have been evaluated.' In other words, a ladder rung, a function or function
block should not be evaluated unless all of the input values that come from
other elements are available.
2. 'The evaluation of a network element shall not be complete until the states of
all of its outputs have been evaluated,' i.e. outputs of a function block should
not be considered available until all outputs have all been updated; a coil
should not change state until all paths in the rung have been evaluated.
3. The evaluation of a network is not complete until the outputs of all of its
elements have been evaluated.' All outputs of all functions, function blocks
and ladder coils should be updated before an LD network is considered to be
complete.
4. When data are transferred from one network to another, all the values coming
from elements in the first network should be produced by the same network
evaluation. The second network should not start evaluation until all the
values from the first network are available.
Note: There are situations, particularly with networks that involve feedback, where
the application of rule 1 may not be possible. For example, in a network
involving feedback it is not possible to provide the initial value of feedback
variables prior to evaluating the network.

6.9 Portability between ST, FBD and LD


Networks described using Ladder Diagram, as with Function Block Diagram, are
not always readily translated into the other IEC languages. Simple ladder rungs
involving mainly AND and OR logic, such as the example rung shown in Figure
6.3, can certainly be expressed in Structured Text and in most cases they can also
be expressed using FBD. The following FBD network is equivalent to the rung
shown in Figure 6.3.
Chapter 6 Ladder Diagram 163

A2
AND
A3 OR X1
A1
B1

C1 AND
C2
Figure 6.8 FBD logic equivalent

With the 1993 edition of IEC 1131-3, it is very difficult to translate Ladder
Diagram rungs involving functions, where EN and ENO are used to pass power
flow, into Structured Text. As each function can only have a single output, there is
no construct in the ST language that can represent the behaviour of ENO. With
some ingenuity, it might be possible to re-express the behaviour of a ladder rung
into Structured Text. However, fully automatic one-to-one translation from LD
into ST would not be easy to accomplish.
However, an amendment to the 1993 edition of IEC 1131-3 proposes that
functions expressed in Structured Text may have multiple outputs: see Chapter 3,
Section 28. It will then be relatively straightforward to translate from LD into ST.
Nevertheless, as FBD also allows EN and ENO to be used for function and
function block evaluation control, translation between FBD and LD should also be
fairly straightforward. Figure 6.9 depicts the FBD network using EN and ENO
that is equivalent to the LD network in the example in Figure 6.5.
Note: The positive transition-sensing contact has been replaced by a rising edge
detecting function block (R TRIG). This is one of the standard IEC
function blocks that are discussed in Chapter 9.

R TRIG1

RTRIG MAX GT
CHECK CLK Q EN ENO EN ENO COMPLETE

TEMPI•
COOL
TEMP2•
TEMP3 -

1000.0

Figure 6.9 FBD equivalent using EN and ENO


164 Programming industrial control systems using IEC1131-3
Translation from Structured Text into LD networks (as with FBD) is not always
possible. Constructs such as DF...THEN, CASE, FOR, WHILE, REPEAT cannot
be represented directly in LD rungs. It is also not possible to reference elements in
an array or structure. For example, the following ST statements have no LD
equivalent:

FOR I := 1 TO 100 DO
rate[I] := 100;
END_FOR;

Apart from simple logic expressions, direct language translation between


Structured Text and Ladder Diagram is not always possible.

6.10 Ladder Diagram layout

Ladder Diagram can be very effective at describing digital logic in a form that is
easy to program and understand. However, use of LD for applications such as
arithmetic computations, closed loop control, and sequencing can result in a large
number of complex rungs that can be very difficult to program and maintain.
It is therefore recommended that sections of LD be kept fairly short. Where
applications are complex, the problem should be broken down into a number of
well-partitioned sections. Each section can then be programmed, say, as a function
block or function. Ideally LD should be used to describe program organisation
units that deal primarily with combinational logic.
The tendency of some programmers, who are very familiar with programming
in ladder logic, to write large sections of a program as a long series of complex
ladder rungs should be avoided. Such an approach will lose many of the benefits
of improved software structure that should be inherent with EEC 1131-3.
When developing Ladder Diagram networks it is worth reviewing the standard
set of functions and function blocks. In many cases, a Ladder Diagram network
can be simplified by using, say, a built-in function.

LD limitations

There are no specific limitations in the standard that only apply to Ladder Diagram
networks. For example, there are no limits on the number of contacts or vertical
and horizontal paths that can exist as part of a single LD rung.
However, the standard does allow for product dependent limits on the number
of function block type specifications, the number of function block instances and
Chapter 6 Ladder Diagram 165
the number of functions that can be supported in one configuration. Such limits
may therefore affect the complexity and size of LD networks that can be produced
when using certain PLC products.
In practice, the programming system for a PLC will probably have a limit on the
width of LD rungs and therefore the number of contacts that can be used in one
rung. There will also generally be a limit on the number of rungs used in, say, a
definition of a function or a function block.

6.11 LD program example

• FD1
FD2
A Alarm X\\\\\\\\Vl

ClearAlarm
Fire Area A1
FireWaming LED
FD3
MAN1

ALARM.SR
ALARM

Figure 6.10 Ladder Diagram fire alarm example


166 Programming industrial control systems using IEC1131-3
Figure 6.10 is an example of a part of a fire alarm system programmed using
Ladder Diagram. A fire area is monitored by three fire detectors FD1, FD2 and
FD3. There is also a manual push button MAN1 which can be used to trigger the
fire alarm. Certain fire detectors can be unreliable and can erroneously signal the
presence of fire. To prevent false alarms, the system only triggers the alarm if two
or more fire detectors are tripped, i.e. the system is required to perform 2 out of 3
voting.
This is achieved by simply checking for the various combinations of detectors.
If any two are ON, then the Alarm_SR function block, a standard RS bistable, is
set ON. This in turn drives the Alarm coil.
The Alarm can only be cleared by pushing the ClearAlarm button. The positive
transition-sensing contact ensures that if the button remains depressed, a new
alarm can still occur. With an SR bistable, the Set signal has a priority over the
Reset. This ensures that the Alarm will continue to be ON if the ClearAlarm
signal occurs while two or more detectors are ON.
If any fire detector is ON, a Fire Warning LED indicator is illuminated. If this
remains lit after the alarm is cleared, this can indicate either that a detector is
faulty or that there is a localised fire near a detector.
Note: This example is used purely to demonstrate the LD language and does not
represent all the functionality required for an effective fire alarm system.
Note: The RS bistable is one of the IEC standard function blocks as described in
Chapter 9.

Summary
Ladder Diagram is suitable for expressing the behaviour of parts of programs that
are primarily concerned with combinational logic.

• The language is based on relay logic diagrams, is intuitive and is easy to


learn. It is particularly suitable for logic involving complex AND and OR
operations.
• Facilities are provided to allow function blocks and functions to be called
from Ladder Diagram rungs.
• Although IEC 1131-3 provides a mechanism through the 'jump' construct for
controlling the execution of sections of an LD network, the use of jumps
should be avoided. It is recommended that all sequencing and selective
execution of LD is performed using the Sequential Function Chart (SFC)
language as discussed in Chapter 8.
Chapter 6 Ladder Diagram 167
Ladder Diagram does not always have a one-to-one correspondence with
languages such as Function Block Diagram and Structured Text. LD
networks containing function calls using EN and ENO cannot be readily
converted into Structured Text. However, it is fairly straightforward to
translate between LD and FBD.
Chapter 7

Instruction List

In this chapter we will review Instruction List; this is the fourth language of the
IEC languages in the set:
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List
and Sequential Function Chart.
Instruction List is a low level language that can be used to express the behaviour
of functions, function blocks and programs, and also actions and transitions in
Sequential Function Charts.
In this chapter we will review:

• The basic structure of the Instruction List language;


• The behaviour of standard operators;
• How to control the flow of program execution using conditional operators,
jumps and labels;
• How to call function blocks and functions in IL;
• Guidelines on writing IL;
• Restrictions on the portability of code between IL and the other IEC
languages.

7.1 IL background

Instruction List is a low level language which has a structure similar to a simple
machine assembler. The IEC has developed Instruction List by reviewing the
many low level languages offered by a wide range of PLC manufacturers. The IL
language, as defined in IEC 1131-3, provides a range of operators that represent
those most commonly found in proprietary instruction list languages of current
day PLCs.
170 Programming industrial control systems using IEC 1131-3
The basic structure of Instruction List is very simple and easy to learn. It is ideal
for solving small straightforward problems where there are few decision points
and where there are a limited number of changes in program execution flow.
A number of the manufacturers offering IEC 1131-3 based PLCs have chosen to
support IL in preference to Structured Text. For a PLC designer, one of the main
advantages of IL over ST is that IL is far easier to implement. It is fairly straight-
forward to develop a PLC that can interpret IL instructions directly. With some
systems it is possible to download IL programs to a PLC without going through a
program compile and build process. In contrast, Structured Text generally has to
be compiled to the native micro-processor assembler of the PLC, such as an 80486
assembler, before it can be down-loaded and run.
Instruction List is sometimes regarded as the language into which all the other
IEC languages can be translated. It is the base language of an EEC compliant PLC,
into which all other languages such as Structured Text and Function Block
Diagram can be converted. However, there are implementors who have taken a
different view, and tend to regard IL as a language strictly for small PLCs and
treat Structured Text as the base language.
It should be emphasised that the IEC 1131-3 standard does not imply that any
particular language should be treated as the base language. Instruction List is
merely another language which can be used, if preferred, for solving certain
control problems.
As is found when using any machine assembler language, there are a number of
disadvantages to using Instruction List over using a high level language such as
Structured Text. For example, it is not possible to check the structure of a section
of an IL program with the same rigour as a section written in ST. It is also harder
to follow the program flow in IL than in ST.
Perhaps one advantage of EL is that, in some circumstances, it may be used to
write tight, optimised code for performance critical sections of a program.

7.2 IL language structure

Instruction List is a language which consists of a series of instructions where each


instruction is on a new line. An instruction consists of an operator followed by one
or more operands. An operand is the 'subject' of the operator. Operands represent
variables or constants as defined in Chapter 3, 'Common elements'. A few
operators can take a series of operands, in which case each operand should be
separated by a comma.
Chapter 7 Instruction List 171

Each instruction may either use or change the value stored in a single register.
The standard refers to this register as the 'result' of an instruction. The 'result' can
be overwritten with a new value, modified or stored in a variable. The result
register is sometimes alternatively referred to as the accumulator or 'accu'.
IL also provides comparison operators which can compare the value of a
variable with the register value, i.e. with the current result. The result of the
comparison is written back to the register. Various types of jump instruction are
provided that can test the current register value and, if appropriate, jump to a
named label. Labels can be used to identify various entry points for jump
instructions. Each label should be followed by a colon.
The following figure depicts the main features of the IL language:

Label Operator Operand Comment


\
\
\ LD Speed (* Load Speed and *)
\ GT 1000 (* Test if > 1000 *)
\ JMPCN VOLTS_OK (* Jump if not *)
\ LD Volts (* Load Volts and *)
* SUB 10 (* Reduce by 10 *)
ST Volts (* Store Volts *)
VOLTS_OK: LD 1 (* Load 1 and store *)
ST %Q75 (* in output 75 *)
Figure 7.1 IL language structure

The IL instructions in Figure 7.1 are equivalent to the following Structured Text
statements:

IF Speed > 1000 Then


Volts := Volts - 10;
END__IF;
%Q75 := 1;

Consider the first line of the IL example; LD represents the load operator, and
Speed is the operand and identifies the value of an integer variable. The LD
instruction loads the current value of variable Speed into the result register.
The 'greater than' GT operator compares the value of the register with literal
(constant) 1000. If the value of the register is greater than 1000, the result of the
GT operator will be 1 which is equivalent to a boolean true value. Otherwise it
will be set to 0, a boolean false value.
172 Programming industrial control systems using IEC1131-3
It is important to note that the value of Speed is no longer available in the
register and that the datatype of the value in the register has changed from integer
(INT) to boolean (BOOL).
The JMPNC instruction jumps to the label VOLTS__OK if the result register
contains 0, i.e. when the comparison fails.
If the comparison is successful, the jump is not made and the instructions that
follow are executed. In this case, the value of variable Volts is loaded into the
register. The SUB operator subtracts 10 from the register. The ST operator then
stores the result back to variable Volts.
The last two instructions load 1 into the 'result' register and then store the
register value into the output 75.
In order to improve readability of the language, IL instructions are structured so
that labels, operators and operands appear in fixed tabulation (tab) positions.

7.3 Comments

Instruction List comments have the same format as in Structured Text. However,
with DL, a comment can only be placed at the end of the line. It is not acceptable
for a comment to appear at the beginning of a line or between an operator and an
operand.
One or more blank lines can be inserted between instructions to break up long
sequences of instructions and aid readability.

7.4 Instruction semantics

The standard states that the general behaviour or semantics of an IL instruction for
the majority of operators can be described by the following expression:

NewResult := CurrentResult Operator Operand

'CurrentResult' represents the value currently held in the 'result' register prior to
the instruction being executed; it is the value left over from the previous
instruction.
'NewResult' is the new value to be loaded into the 'result' register as produced
by executing the instruction. It is the value produced by the 'Operator' acting on
values of 'CurrentResult' and the 'Operand'. The 'NewResult' becomes the
'CurrentResult' for the next instruction.
Chapter 7 Instruction List 173
For example, consider the instruction 'SUB 10' in Figure 7.1 that uses the
Subtract operator. This is equivalent to the expression:
NewResult := CurrentResult SUB 10
The SUB operator takes 10 from the 'CurrentResult' and stores the value in the
'NewResult'.
With comparison operators, the 'CurrentResult' is compared with the operand.
The 'NewResult' is set to 1 (true) if the comparison is successful; otherwise it is
set to 0 (false).
For example, the behaviour of the comparison instruction 'GT 1000' in Figure
7.1 that uses the 'greater than' operator, is equivalent to:
NewResult := CurrentResult GT 1000
A few IL operators do not fit this general model. For example, the ST (store)
operator can be described by the expression:
Operand := C u r r e n t R e s u l t
This is because the function of the ST operator is to store the current value held in
the result register into the location defined by the Operand field.
Tables 7.1 and 7.2 describe the standard IL operators. Additional text and notes
are given with the tables to describe the operator behaviour.

Deferred execution

Special modifiers called the parenthesis (or bracket) modifiers allow sections of IL
instructions to be deferred, i.e. to produce intermediate results that do not affect
the current 'result register'. This has the same effect as the use of brackets in
normal arithmetic and boolean expressions.
For example:
LD A (* Add A to B*)
ADD B (* hold the value in result reg. *)
MUL( A (* Defer MUL until (A-B) available *)
SUB B
) (* Now multiply by (A-B) *)
In this example, when the MUL operator is reached, the result of A + B is held in
the result register. The left bracket '( ' following the MUL operator indicates that
the multiply operation will be deferred until the right bracket ')' operator is
reached. The value of operand A is then loaded into a temporary result register.
The SUB B instruction produces the value of A - B , which is held in the
temporary result register. The final ')' operator takes the value in the temporary
174 Programming industrial control systems using IEC1131-3
result register and multiplies it by the value held in the main result register. This
sequence of instructions is equivalent to:
result := (A + B) * (A - B ) ;
Note: There is no precedence with IL operators. Hence the brackets are needed in
this expression, i.e. around (A + B), to indicate that the add operator occurs
before the multiplication operator.

The parenthesis operators provide a similar function to a stack. A number of


deferred operators can be active at any time allowing fairly complex nested
operations to be performed.
Consider the following example:

LD X (* Load X 1 *)
ADD( B (* D e f e r ADD, l o a d B 2 *)
MUL( C (* D e f e r MUL, l o a d C 3 *)
ADD D (* Add D 4 *)
) (* Multiply result 5 *)
) (* Add result 6 *)
This is equivalent to:
X + (B * ( C + D) )
The following table shows how the deferred instructions in the example cause
values to be stored in a stack of result registers. The table gives the values in the
•op three result registers that exist after each instruction in this example has been
evaluated.

Instruction Top Top-1 Top-2


result register result register result register
1 X
2 X B
3 X B C
4 X B C+D
5 X B*(C+D)
6 X+B*(C+D)
Note: The standard does not indicate that the use of jump instructions within
parenthesised sections is illegal. Clearly, in practice, jumps from within
parenthesised instructions may produce unpredictable results and should be
avoided.

Modifiers

Some EL operators can take single letter modifiers after the operator mnemonic
that change the semantics of the instruction.
Chapter 7 Instruction List 175
If the operand contains a boolean value, the 'N' modifier can be used to negate
its value. With jump operators, the *N' modifier indicates that the jump will use
the negated value of the 'result register'.
The ' C modifier can only be used with jump operators and indicates that a
jump is made conditionally on the boolean value of the result register.

For example:
LD %IX10 (* Load Input 10 *)
ANDN Switchl (* AND NOT switchl *)
JMPNC Labi (* Jump if Not true *)
The ANDN operator inverts the value of Switchl and ANDs the result with the
value of input 10 (%K10). The JMPNC jump operator jumps to label 'Labi' if
the result is not boolean true.

7.5 Operators

The main IL operators are listed in Table 7.1; the comparison operators and
instructions concerned with changing the flow of execution control are listed in
Table 7.2.

Table 7.1 Main IL operators

Operator Modifiers Operand Comments


LD N ANYX Load operand into result register
ST N ANY! Store result register into operand
S Note 2 BOOL Set operand true
R Note 2 BOOL Reset operand false
AND N,( ANY i Boolean AND
& N,( ANY i Boolean AND (equivalent to
AND)
OR N,( ANY i Boolean OR
XOR N,( ANY i Boolean,exclusive OR
NOT ANYi Logical negation (one's
complement)
ADD ( ANYi Addition
SUB ( ANYi Subtraction
MUL ( ANYi Multiplication
DIV ( ANYi Division
MOD ( ANYi Modulo-division
176 Programming industrial control systems using IEC1131-3
Table 7.2 IL comparison and jump operators

Operator Modifiers Operand Comments


GT ( ANYi Comparison greater than
GE ( ANYi Comparison greater than, equal
EQ ( ANYi Comparison equal
NE ( ANYi Comparison not equal
LE ( ANYi Comparison less than, equal
LT ( ANYi Comparison less than
JMP C,N LABEL Jump to label
CAL C,N NAME Call function block, see
following sections on the
alternative call syntax
RET C,N Return from function or function
block (see Note 4)
Execute the last deferred
operator

Note 1: Operators that can take operands of data type ANY are said to be
'overloaded'. That is, the operator can be used with any of the different
elementary data types such as integers SINT, INT, time data types such as
DATE_AND_TIME, floating point values of type REAL and so on. For a
full list of elementary data types see Chapter 3, 'Common Elements'. The
operator will only produce a valid result if the current value in the result
register is of the same data type as the operand.
Note 2: The Set and Reset operators can only be used with operands of boolean
data type.
Note 3: Operators that can have more than one modifier may be used with either or
both modifiers. For example there are four forms of the AND operator:

Operator Semantics
AND Boolean AND
AND ( Deferred boolean AND
ANDN ( Deferred boolean AND, invert deferred result
ANDN Invert boolean AND

Note 4: The RET operator is used to return from a function or function block. The
modifier C means that the return is made conditionally. If the result register
contains boolean true, i.e. 1, the return is made. The N indicates that the
result register should be inverted, i.e. false for the return to be made.
With JMP, CAL and RET instructions, the negate 'N' modifier can only be
used with the condition modifier 'C\ and indicates that the jump is made
conditionally on the negated value of the result register, i.e. when the value
is boolean 0 (false).
Chapter 7 Instruction List 177

7.6 Calling functions and function blocks

Within Instruction List, the standard provides three different formats of the CAL
operator for calling function blocks, and two alternative formats for calling
functions. The syntax for calling functions and function blocks is not the same.

Calling a function block using a formal call with an input list

With this format, the CAL operator is followed by a list of function block
parameters with their values. Each input parameter must be identified by name.
The value of each parameter can be given directly or calculated and passed into
the IL current result register (accumulator).
Example:
CAL LOOPl(
SP:= 300.0
PV : = (
LD %IW20
ADD 10

This calls function block instance LOOPl with parameter SP set to 300.0 and
parameter PV set to the value of input word 20 plus 10.

Calling a function block using an informal call

In this format, the values to each input should be set-up prior to calling the
function block.

Example:
LD 300.0
ST LOOPl .SP
LD %IW20
ADD 10
ST LOOPl .PV
CAL LOOPl

This is equivalent to the previous example; LOOPl is called with parameter SP


set to 300.0 and parameter PV set to the value of input word 20 plus 10.
178 Programming industrial control systems using IEC1131-3

Calling function blocks using input operators

This format can only be used with some of the IEC standard function blocks as
defined in Chapter 9. A number of IL operators are reserved for use with
commonly used function blocks such as the SR (Set/Reset) bistable, or the CTU
up-counter. A full list of such operators is given in the next section. They are
provided as a short-hand form for calling commonly used function blocks.
Example:
SI Latchl
LD 10
PV CTU1
CU CTU1
The SI operator can only be used with an SR bistable. In this case the SI
instruction causes Latchl, a function block instance of type SR, to be set.
The PV (preset value) operator can only be used with counter function blocks.
In the example, the PV instruction loads 10 from the result register into the PV
parameter of the up-counter function block CTU1. The CU instruction calls the
up-counter function block with the counter enable parameter set true, i.e. to start
counting.
Note: Parameters that are not supplied in a function block call will either
take the previous value they were assigned, or take their
default value from initialisation.

Calling functions using a formal call *,

In a formal function call, the function name is given, followed by the values of the
input parameters.
Example:
SHR(
IN := %IW30
N:= 10
)
An amendment to the 1993 edition of IEC 1131-3 for the second edition proposes
that when a formal call is made to a function, then optionally the value of the first
parameter can be supplied directly from the current result.
Example:
LD %IW3 0
SHR(
N:= 10
)
ST %QW1OO
Chapter 7 Instruction List 179
Calling functions using an informal call

In an informal function call, the function name is given, followed by the values of
the input parameters. The value of the first parameter is supplied by the current
result.

Example:
LD %IW30
SHR 10
ST %QW100

The SHR (shift right) function requires two input parameters. In this example, the
first parameter is loaded from the current result, i.e. the contents of input word 30;
the second parameter has value 10, i.e. the count of bits for the shift operation.
The result from the function is returned as the current result. This is loaded to
output word 100.

7.7 Defining functions and function blocks

Instruction List can be used to define the behaviour of functions and function
blocks. When used to define a function, the value returned by the function is
provided by the last value in the result register (accumulator).
When used to define function blocks, EL can reference the function block inputs
(VARJNPUT) and write values to outputs (VARJ3UTPUTS) that are declared
in the function block declaration.
For further details on using IL to define functions see Section 7.12 IL program
example'.

7.8 Function block operators

The full list of reserved operators for use with standard function blocks is given in
Table 7.3.
180 Programming industrial control systems using IEC1131-3
Table 7.31L Function block operators

Operator Function block Comments


type
S1,R SR bistable Set and Reset the SR bistable.
S,R1 RS bistable Set and Reset the RS bistable.
CLK R__Trig, rising edge Clock input to the rising edge detector
detector function block.
CLK F_Trig, falling edge Clock input to the falling edge detector
detector function block.
CU,R,PV CTU, Control parameters for the CTU up-
up-counter counter function block, to count-up
(CU), reset (R) and load (PV).
CD,PV CTD, Control parameters for the CTD down-
down-counter counter, to count-down (CD), load LD
and set the count minimum (PV).
CU,CD,R, CTUD, Control parameters; same as for up- and
PV up/down-counter down-counters.
IN,PT TP, pulse timer Control parameters for the pulse timer,
to start timing (IN) and set-up the pulse
time (PT).
IN,PT TON, on delay timer Control parameters for the on-delay
timer, to start timing (IN) and set-up the
delay time (PT).
IN,PT TOF, off delay timer Control parameters for the on-delay
timer, to start timing (IN) and set-up the
off-delay time (PT).

7.9 Deficiencies and proposed extensions

Of all the five IEC languages, the definition of the Instruction List language has
been found to be the most contentious. The semantics, i.e. the way the instructions
operate, are not always fully described in the standard.
One of the main problems is that the standard does not fully define the
behaviour of a conceptual processor, or virtual machine, that can execute EL
instructions. For example, it is unclear how the result register stores values of
different data types. It is particularly difficult to see how the accumulator can be
Chapter 7 Instruction List 181
used to store multi-element variables, such as structured variables, arrays or
strings.
The run-time behaviour for various error conditions is also not documented. For
example, the behaviour following the use of an operator with an inappropriate
data type is not described.

7.10 Portability between IL and other languages

The conversion of sections of Instruction List into the other languages is very
difficult. It could be achieved if a restricted range of IL operators were used and
the instructions written using a strict format.
Conversion of the other languages into IL is easier but by no means always
straightforward.
For example consider the following section of a Function Block Diagram:

StartSR

— Start

Reset

This can be written in Instruction List as follows:

LD Testl (* Testl OR *)
OR Test2 (* Test2 *)
AND Swl (* AND Swl *)
AND %IX3 (* AND input 3 *)
ST StartSR .SI (* Set input of StartSR *)
LD Reset (* Load value of Reset *)
ST StartSR .R (* Store in reset input *)
CAL StartSR (* Call fb. StartSR *)
LD StartSR • Ql (* Load output Ql *)
ST Start (* and store in Start *)

The execution control parameters EN and ENO used in the FBD and LD
anguages can be used in EL. They are treated as extra parameters of a function or
"unction block.
182 Programming industrial control systems using IEC1131-3

7.11 Good programming style

Because Instruction List is a fairly low level language, great care should be taken
in laying out the code to ensure that it is easy to read and maintain. It is important
that EL instructions are well commented. Jump instructions should be used
sparingly so that the flow of execution through the code is easy to follow.
Particular care should be taken to ensure that the value in the result register is
always appropriate for an IL operator.

7.12 IL program example

In this example we will consider the use of IL for defining a function for
calculating the travel distance between two points on a flat surface. Such a
function might be required for controlling a numerically controlled (NC) machine
that needs to traverse between two drilling points. Assume that the positions of the
two points are given by x and y co-ordinates as shown in Figure 7.2.

4 x1,y1
•BOOL
y1-y2 REAL
•REAL
REAL
x2,y2 REAL
x1-x2 REAL
REAL

Figure 7.2 IL function example

From trigonometry, the distance between the two points can be expressed in
Structured Text as:

Travel_distance := SQRT (( X1-X2)*(X1-X2)


+ (Y1-Y2)*(Y1-Y2));

Assume that this function will be used in the graphical languages. The ENO
output signal is therefore required for passing execution control on to other
functions when the function has completed successfully, see Chapter 5, Section 5.
If the travel distance is less than TMax, the function should set ENO to indicate
that it has computed the travel distance successfully. If the travel distance exceeds
Chapter 7 Instruction List 183
TMax, the computation has produced a travel distance outside the range of the
controlled machine, in which case the ENO output should not be set.
The full definition of a function TRAVEL() to calculate the required movement
expressed using Instruction List is as follows:

FUNCTION TRAVEL : REAL


VAR_INPUT
XI,X2,Yl,Y2 : REAL; (* X and Y Co-ordinates *)
TMax : REAL: (* Maximum travel distance *)
END_VAR
VAR
temp : REAL; (* Intermediate values *)
END__VAR

LD Yl
SUB Y2 (* Subtract Y2 from Yl *)
ST Temp (* Store Y1-Y2 in Temp *)
MUL Temp (* Multiply by Temp to square *)
ADD( XI (* Defer ADD *)
SUB X2 (* Subtract XI from X2 *)
ST Temp (* Store X1-X2 in Temp *)
MUL Temp (* Multiply by Temp to square *)
) (* Add two squared values *)
CAL SQRT (* Call Square root fun. *)
ST TRAVEL (* Setup function result*)
GT TMax (* Greater than TMax ? *)
JMPC ERR (* Yes, Jump to Error *)
S ENO (* Set ENO *)
RET (* Normal return *)

ERR:
RET (*•Error return, ENO not set *)

END_FUNCTION

Note: The value for the SQRT function is supplied from the current result, as discussed in
Section 7.6.
184 Programming industrial control systems using IEC1131-3

Summary
Instruction List is a low level textual language which can be used for describing
the behaviour of functions and function blocks, and actions and transitions used in
the Sequential Function Charts.

• It is simple to implement and can be directly intepreted within a PLC. It has


therefore been adopted by a number of PLC manufacturers for their small to
medium sized PLCs.
• It can be used to write tight, optimised code for performance critical
operations.
• Operators are provided to manipulate variables of all the elementary data
types, call functions and function blocks.
• It is ideal for solving small straightforward problems where there are few
decision points and where there are a limited number of changes in program
execution flow.
• Care should always be taken when developing programs using IL as there are
only limited language validation checks that can be undertaken on a
programming station. The majority of language violations, such as data type
inconsistencies, can only be detected at run-time.
• Conversion from IL into the other EEC languages is not always possible.
However, conversion from the other languages into IL can generally be
achieved.
Chapter 8

Sequential Function Chart

This chapter reviews the DEC Sequential Function Chart (SFC) graphical
language; this is the final language of the EEC languages in the set:
Structured Text, Function Block Diagram, Ladder Diagram, Instruction List
and Sequential Function Chart.
SFC is a powerful graphical technique for describing the sequential behaviour of a
control program. This chapter includes:

• The basic concepts of the Sequential Function Chart language;


• The definition of sequences in terms of steps and transitions;
• The use of the other various TEC languages for defining the behaviour of SFC
elements, i.e. steps, transitions and actions;
• How to define when actions are executed;
• The use of SFC for top down design;
• Safe and unsafe chart designs.

8.1 SFC background

The definition of the IEC Sequential Function Chart language has been derived
from current techniques that are used for depicting sequential behaviour. Many
PLC manufacturers have offered some form of graphical language for describing
sequences for a number of years. The majority of the European based PLC
manufacturers now provide Grafcet, a graphical language based on a French
national standard.
Describing the behaviour of a system in terms of states and transitions, depicted
as circles and arcs, was originally defined in a methodology called Petri-net. Petri-
net is now a well established technique, particularly in computer systems design,
for formally describing the behaviour of programs that have multiple states.
186 Programming industrial control systems using IEC1131-3

Grafcet was evolved from Petri-net as an industrial form of the methodology. In


1988, the IEC published the standard IEC 848, Treparation of function charts for
control systems'. This defines a graphical language for depicting sequences based
very closely on ideas from the French Grafcet standard.
Most of the definitions in IEC 848 have been directly imported into the IEC
1131-3 standard to form the Sequential Function Chart language. SFC therefore
has many features that resemble Grafcet and IEC 848. The main enhancements to
the methodology have been due to the need to integrate SFC with the other EEC
1131-3 languages.
SFC allows all the sequential aspects of a control program to be described. SFC
can be used at the top level to show the main phases of a process, such as 'Start-
up', 'Pumping', 'Emptying', or the main states of a machine, like 'Running',
'Stopped' etc. It can also be used at any other level. For example, SFC can be used
at a low level to describe the behaviour of a function block handling a serial
communications device with various states, such as 'Off, 'Carrier Detected',
'Transmitting' and so on.
One of the most important aspects of SFC is that it shows the main states of a
system, all the possible changes of state and the reasons why those changes could
occur.
SFC language can be used to partition a control problem so that only those
aspects relevant to a particular phase need to be considered and executed. This is
very important from a performance point of view because only code concerning
active steps is executed.
One or more separate SFC networks can be used to describe the behaviour of
programs, function blocks or action blocks. Each separate SFC network has a
single initial step which is activated when the associated program organisation
unit is initialised.

8.2 Chart structure

A sequence in SFC is depicted as a series of steps shown as rectangular boxes


connected by vertical lines as shown in Figure 8.1. Each step represents a
particular state of the system being controlled. Each connecting line has a
horizontal bar representing a transition. A transition is associated with a condition
which, when true, causes the step before the transition to be deactivated and the
step that follows the transition to be activated. The flow of control is generally
down the page, but branches can be used to go back to earlier steps.
Chapter 8 Sequential Function Chart 187

The 'Fill' step remains active Initial Step


while the vessel is being filled ^ „ - Transition
Start
with reactants. Transition Condition
When the VesselFull signal is StartSwitch = 1
detected, the Till' step is
Fill
deactivated and the 'Stir' step is
started. The 'Stir' step's duration VesselFull = 1
is timed using an elapse timer Stir
function block called Timer 1.
Timeii.ET = T#1h
When Timerl's elapsed time
reaches 1 hour, the 'Stir' step Drain
ceases and the 'Drain' step StartSwitch = 0
becomes active.
Stop
The final 'Stop' step is reached
when the StartSwitch is placed in
the 'Off position.

Figure 8.1 Main SFC features

Start
Divergent path

StartSwitch = 1 Named Transition

Fill

Tran2 Tran3
Stir Filter
Tran4 TranS

Drain

StartSwitch = 0 StartSwitch = 1
Stop
Convergent path /

Branch with directional arrows


Figure 8.2 Divergent and convergent paths
188 Programming industrial control systems using IEC1131-3

The example in Figure 8.1 depicts part of a sequence that might be used to
describe the main phases of a process controlling a reactor vessel.
The 'Start* step is concerned with holding the vessel in a ready state waiting for
the operator to press the start switch. The 'Fill' step becomes active after the
operator has initiated the process by setting the StartSwitch to the 'On' state. As
the 'Fill' step is activated, the 'Start' step is deactivated in the same instant.
Figure 8.2 depicts the use of divergent and convergent paths in SFCs to provide
alternative sequences. In this example, there are two alternative process phases
'Stir' or 'Filter' which could, for example, be selected according to a batch type
entered by the operator. Tran4 and Tran5 represent named transitions where the
transition condition is defined in another part of the SFC.
These transitions will typically define conditions that will cause the process step
to terminate; for example, this could be determined by the process elapse time or
some form of process completion parameter such as viscosity or pressure. When
either of the conditions for transitions from the 'Stir' or 'Filter' steps becomes
true, the 'Drain' step is activated to collect the product. If the StartSwitch remains
'ON', the process is re-started.
Note that the sequence starts with the initial step 'Start'. All SFC sequences
must have an initial step. This should be depicted by a rectangular box containing
vertical bars. The initial step is the first step to be activated whenever an SFC is
started. The initial step remains active until the condition of the following
transition becomes true. In the example, the transition condition following the
'Start' step is described using a Structured Text expression.
An SFC sequence will process through all the linked steps. The flow of active
steps is referred to as the 'sequence evolution'.
Each step can be associated with one or more actions. Actions which are
described in later sections of this chapter define the behaviour that occurs when
the step is active, e.g. an action may start a pump, open a valve and so on.
A transition can either be described directly on the Sequential Function Chart
using ST, FBD or LD or can be described on an associated diagram using any of
the languages ST, FBD, LD or IL, in which case the definition is associated with
the name of the transition. For example, in Figure 8.2, the name 'Tran2' is a
transition whose definition is given in an associated diagram.
Alternative steps in a sequence can be selected using a divergence construct
where more than one transition is associated with leaving a step. In this example,
the conditions of both transitions Tran2' and 'Tran3' are evaluated when the
'Fill' step is active. Normally, transition conditions are tested from left to right.
We will see later that the order in which transitions are tested can be changed. If
Chapter 8 Sequential Function Chart 189
the condition associated with any transition in a divergent path becomes true, the
current step is deactivated and the step that follows the transition with the true
condition is activated.
A divergent sequence can rejoin another sequence using a convergent path. Any
number of divergent and convergent paths can be used in a Sequential Function
Chart enabling complex sequential behaviour to be depicted.
Branches can be used with directional arrows to indicate where transition paths
lead back to earlier steps.

Semigraphic representation

The IEC 1131-3 standard defines a semigraphic representation of SFC symbols


using textual characters. This is defined for programming systems that are unable
to provide full graphics.
Figure 8.3 depicts part of Figure 8.2 using the IEC semigraphic representation:

Start

+ StartSwitch = 1

+ Trans1 + Trans2
I i
Figure 8.3 SFC semigraphic representation
All the Sequential Function Charts depicted in the rest of this book will use the
full graphic form as this is the form most commonly provided by the latest
implementations of IEC 1131-3.
Note: The standard does not define how symbols should appear using full graphics.
For example, one system may use shaded boxes for steps, another coloured
boxes. However, the layout and topology of an SFC should be the same on
all IEC compliant systems.
190 Programming industrial control systems using IEC1131-3

8.3 Simultaneous sequences

We have seen how it is possible to use divergent paths to enter alternative


sequences. Using a divergent path, only one step in one of the alternative
sequences can be active at any time. However, using a construct, which the IEC
standard defines as a simultaneous sequence divergence, it is possible to activate
parallel sequences.
This is a particularly useful facility and is commonly required in many batch
process applications. The main sequence can be used for sequencing the primary
process phases, while secondary parallel sequences can be monitoring that the
process is running within normal operating constraints. For example, a parallel
sequence could check that plant temperatures and pressures are within operating
limits, and, if they are not, initiate a shut-down sequence.
There are situations where the parallel sequences are no longer required, in
which case a construct called a simultaneous sequence convergence can be used to
bring two or more parallel sequences back into a single sequence.
Figure 8.4 is an example of an SFC which depicts how the behaviour of
simultaneous sequences can be depicted using the divergence and convergence
constructs; both constructs are depicted by a pair of parallel horizontal lines.

Start

StartSwitch = 1
Simultaneous Sequence Divergence
Fill
Trani

Stir TempCks Monitor

Tran2 Tran3

Drain PressCks
-L.
Tran4
Stop Simultaneous Sequence Convergence

Figure 8.4 Using simultaneous sequences


Chapter 8 Sequential Function Chart 191

In Figure 8.4, if step 'Fill' is active while the condition for transition Tranl
becomes true, three steps 'Stir', TempCks' and 'Monitor' are simultaneously
activated, starting three simultaneous sub-sequences.
Simultaneous sequences continue independently until a convergence is reached.
In this case, when all three sub-sequences reach their last step, i.e. when steps
'Drain', 'PressCks' and 'Monitor' are all active and the condition for Tran4 is
true, the three steps are deactivated and the following step 'Stop' is activated. The
three simultaneous sequences are brought back into one sequence.

Note: The transition closing a simultaneous convergence, e.g. Tran4, is not


evaluated until all the last steps of all sub-sequences going to the
convergence are active. For example, if steps 'Drain' and 'Monitor' are
active but 'PressCks' is not active, Tran4 will not be evaluated.

8.4 Steps

Each step within an SFC should be given a unique name and should only appear
once in a Sequential Function Chart. Step and transition names are local to the
program organisation unit, e.g. function block or program, in which the SFC
exists.
There are two forms of step, both shown in Figure 8.1:
1 Normal steps: these are depicted in rectangular boxes with the step
name in the centre of the box.
2 Initial steps: these are also depicted in identical rectangular boxes but
with vertical bars. Only one initial step should be given for any SFC and
it defines the step that will be activated when the PLC is cold-started.

The behaviour of any step can be described by associating one or more action
blocks with the step. Each action block can be described using any of the EEC
languages, i.e. ST, FBD, LD or IL. Action blocks are described in detail in Section
8.6.

Step executing and time variables

Every step is associated with two variables that can be used within the rest of the
SFC to synchronise and monitor step activation.
192 Programming industrial control systems using IEC1131-3

(1) The step active flag (.X) is a boolean variable that is only set true while a
particular step is active. This can be tested within other parts of an SFC, for
example within other simultaneous sequences, to check that a particular step is
active. This variable has the form <StepName>.X. The step box can also
provide this variable as a graphical output for driving boolean variables.
For example, in Figure 8.4, the condition for transition Tran3 could
contain the ST expression:
Drain.X = 1
This will result in the transition from step 'TempCks' to 'PressCks' only
occurring when the 'Drain' step is activated, i.e. the condition is only true when
the 'Drain' step is active.
The following figure depicts how the step active flag (.X) can be
connected directly to a boolean variable. Valve 1 is only set to 1 when the 'Fill'
step is active.

Start

StartSwitch = 1

Fill Valvel

Trani ^ -—-
Direct Connection from the step's (.X) active flag.

(2) Each step also has an elapse time (.T) variable of data type TIME. When a step
is first activated, the elapse time variable is set to zero. While a step is active, it
is updated to indicate how long the step has been active. When the step ceases
to be active, the .T variable retains the elapse time, i.e. it records how long a
step was active the last time it was activated. The elapse time can be accessed in
the form <StepName>.T, e.g. Fill.T.

The elapse time can be very useful for timing how long a step is active. Consider
the following example:

StartSwitch = 1

Fill

Fi»,T>T#10m
itir I
Chapter 8 Sequential Function Chart 193
The transition from the Till' step contains an ST expression for the condition
'Fill.T is greater than 10 minutes1. This has the effect of ensuring that the Till'
step remains active for exactly 10 minutes. At that point the transition condition is
true, the Till' step is deactivated and the next step 'Stir' is activated.
The elapse time can also be used for diagnosing sequencing faults, e.g. to check
that all steps are active for their expected times.

8.5 Transitions

The standard provides a wide range of different constructs for describing


transition conditions using text or graphics. We have already seen that a transition
can be described using Structured Text, e.g. the condition 'StartSwitch = V as
shown in Figure 8.2.
Note: Every transition must have a condition. A transition that always occurs can
be depicted using a boolean literal 'TRUE'.

The different ways of expressing transition conditions are listed as follows:

Structured Text

Example
Any ST expression that results in
Heat a boolean result can be used to
(Tempi > 2000) AND (Press > 20) describe a transition condition.
Cool

Ladder Diagram

A ladder rung can be used as a


transition condition. When the
rung provides a power flow, the
transition condition becomes true.
194 Programming industrial control systems using IEC 1131-3

Function Block Diagram

Example

Beari
MotorChecks I Any Function Block Diagram
Vibration PreCheck network that generates a boolean
Tanki _ Fuel output can be connected to a
Gas1 Pressure transition. In this example,
Power MotorChecks is a function that
I sets a boolean signal Go to 1
(true), when values of inputs
Vibration, Fuel and Pressure are
within operating limits.

Transition connector

Example
A transition connector can
Wait be used in situations where
>TransNewBatch > mm the transition condition is
Batch shown in another part of a
1 Sequential Function Chart.

1 Ready NewJob Enable


—| | 1| 1 | ->TransNewBatch >

Named transition

Example
I Transitions can be identified by
Stepi name. The definition of the named
—|— Transi transition can then be defined on
Step2 another diagram or page using any of
1 the IEC languages ST, FBD, LD or
IL.
Chapter 8 Sequential Function Chart 195

Transition definition using ST

Example
TRANSITION Trans1 : A named transition condition can be
:= AB1 AND CX3 OR CX5 described using a Structured Text
AND (TX3 >= 100.2); expression. The expression should
END TRANSITION
only return a boolean value.
Note that the assignment symbol
:= is required to indicate that the
value is assigned to the transition
condition.

Transition definition using FBD

Example
TRANSITION TRANSGO : The definition of a named
transition condition can be
IN1 — AND defined graphically using
Enablei — AD
Function Block Diagram
TransGo language. The final output of
i— the FBD network provides
IN2 —
AND
J the value of the transition
Enable2 — condition.
END_TRANSITION

Transition definition using LD

Example
TRANSITION TRANS21 : A named transition

-< H
1 %IX21 EX10 FDIR21 Trans21 I condition can be defined
I II—II I K " using a Ladder Diagram
rung. The coil, which is set
END_TRANSITION by power flow in the rung,
has the same name as the
transition. When the coil is
set, the transition condition
is true.
196 Programming industrial control systems using IEC1131-3

Transition definition using IL

Example
TRANSITION T r a n s 2 1 : A named transition can also be defined
LD %IX21 using the Instruction List language. The
AND EX10
value of result register after executing the
AND FDIR21
END_TRANSITION IL instructions defines the value of the
transition condition. When the value, that
should be boolean data type, is 1 the
transition condition is true.

8.6 Actions

Up to now we have only considered steps as being used to describe the states of a
plant or machine. In a real system, each step is required to perform certain control
actions that are applicable for that particular state.
In SFC methodology, every step can be associated with one or more actions. An
action contains a description of some behaviour that should occur as a result of the
step being activated. An action is depicted as a rectangular box that is attached to
a step. The description of an action can be given using any of the IEC languages,
i.e. ST, FBD, LD or IL.

Action
Action Qualifier ; Indicator Variable

Start N PromptOperator StartSwitch

— StartSwitch = 1

r ill P OpenValves

I"ran1 N StartPump

MainPump := ON;
Pumpi := ON;

Action Description
Figure 8.5 Main features of SFC actions
Chapter 8 Sequential Function Chart 197
Figure 8.5 depicts the main features of SFC actions. Every action has a name
which should be unique within the current program organisation unit, e.g. unique
within the current function block that contains the SFC.
An action can either be described on another diagram or page or, if its
behaviour is fairly trivial, it can be described as part of the SFC, as shown for the
action 'StartPump' in Figure 8.5. Any of the IEC languages can be used to
describe the behaviour of an action. There is no restriction within the standard on
the level of complexity of networks or number of language statements used to
define an action.
Each action has a qualifier that determines when the action is executed. In this
example, the 'N' qualifier indicates that the action is executed while the
associated step is active. A range of qualifiers is defined in the standard and is
described in the next section.
An action box may optionally have an indicator variable. This is only used for
annotation purposes. The indicator variable names a key variable that is changed
within the action and indicates that the action has completed its execution. In
Figure 8.5, action TromptOperator' signals the operator that the process can be
started. As a result, the operator sets a switch called Starts witch to 1. Starts witch
is therefore shown as a key variable of the TromptOperator' action and indicates
that it has finished.
Any step may have any number of actions or none. A step with no actions
simply waits for its transition conditions to become true; it performs a 'wait'
function.
An action may also be associated with more than one step. For example, the
action 'OpenValves' shown in Figure 8.5 could also be used in other process
steps, such as in a 'CLEANING' step concerned with setting valve positions for
cleaning the reactor, i.e. wherever the same valve operations are required the same
action can be called.
The behaviour of some actions may be too complex to draw directly on the SFC
diagram, in which case the behaviour can be defined on another diagram or page
using any of the IEC languages including SFC.
The following examples show how the various IEC languages can be used to
describe actions.
198 Programming industrial control systems using IEC 1131-3

Action defined using Ladder Diagram

Example
Pump_Control The behaviour of an action can be
described graphically using the
%IX30 X10 AL1 Pumpi
Ladder Diagram language.
The rungs are enclosed in a
Pumpi V1 AuxSwi AuxX1 rectangular box, with the name of
the action placed at the top.
Pump2

Action defined using Function Block Diagram

Example
Stir_Control The behaviour of an action can be
StirJLoop described graphically using the
PID Function Block Diagram
1000.0 SP OUT —StirDrive language.
StirSpeed PV The FBD network is enclosed in
a rectangular box, with the name
GT
1500.0 —OverSpeed of the action placed at the top.
StirSpeed Note: If an action is configured
-
to execute continually it can be
used to contain feedback control
loops. For example, an action
could be used to bring a set of PID
control loops into operation
during a particular process phase.
Chapter 8 Sequential Function Chart 199

Action defined using Sequential Function Chart

Example
Dosing
The behaviour of an action
can also be described using an
SFC. This allows complex
Dosei N AddX1
sequential behaviour to be
— Dose1.T> T#2m
built up hierarchically.
AdjustpH — N AddAcid One of the indicator
— pHVal < 0.7 variables of an action in the
SFC can be used as an
Dose3 N AddX2 Rdy
indicator variable in the
action at the next level up.

Note: For an action to be able to execute its own SFC, it should be configured to
execute continually for a period of sufficient duration to allow its SFC to
complete.

Action defined using Structured Text

Example
The behaviour of an
ACTION OpenValves : action can be described
IF BatchType = "AB0_100" THEN
textually using a series of
ValveAB := OPEN;
ELSE statements in Structured
ValveAC := OPEN; Text.
END_IF; A variable changed by
DrainValve := CLOSE; an ST statement can be
Vent := OPEN; used as the action
END_ACTION
indicator variable.
200 Programming industrial control systems using IEC1131-3

Action defined using Instruction List

Example
ACTION AddX2 : Actions can also be
LD 1 described textually
ST TankX2.Enable
using Instruction List.
LD 100
ST TankX2.ShotLevel A variable changed by
CAL TankX2 one of the TL
S X2_Added instructions can be used
END ACTION as the action indicator
variable.

Use of actions in graphical languages

The use of actions is not restricted to SFC. Actions can also be called within FBD
and LD languages as shown in Figure 8.6
In the FBD language, the action is activated when its boolean input is true. In
LD, the action is activated when there is a power flow into the action block. In
both languages, the action indicator variable can be used to signal when the action
is complete.
Although the standard allows actions to be used in the graphical languages in
this way, such use is not recommended. Functions. and function blocks with
defined inputs and outputs provide a better structure for partitioning program
behaviour.

%IX10 Enable AHShut


N ShutDrain V1

Using Action Blocks in Ladder Diagram

%IX10 AND
N ShutDrain V1 — AHShut
Enable —

Using Action Blocks in Function Block Diagram

Figure 8.6 Using actions in graphical languages


Chapter 8 Sequential Function Chart 201

8.7 Action qualifiers


So far we have considered actions which are configured to execute continually
while their associated steps are active. Such actions all have the 'N' qualifier.
Remember that the qualifier is always given in the first field of the action block as
shown in Figure 8.5.
The standard defines a range of qualifiers which define precisely when a
particular action executes in relation to its associated step.
For example, the T)' qualifier (time delayed) allows an action to start execution
a defined time after its associated step is activated.
An action can also be set active, using an 'S' qualifier, in one step and continue
to execute until reset, using the 'R' qualifier, in another step. This may occur
many steps, or some considerable time, later. Such actions that persist for more
than one step are said to be * stored*. The full range of qualifiers defined in the
standard is given in Table 8.1.

Table 8.32 SFC action qualifiers

Qualifier Description
None Non-stored, default, same as 'N'.
N Non-stored, executes while associated step is active.
R Resets a stored action.
S Sets an action active, i.e. stored.
L Note 1 Time limited action, terminates after a given period.
D Note 1 Time delayed action, starts after a given period.
P A pulse action that only executes once when a step is activated,
and once when the step is deactivated.
PI Note 2 A pulse action that only executes once when a step is activated.
PO Note 2 A pulse action that only executes once when a step is deactivated.
SD Note 1 Stored and time delayed. The action is set active after a given
period, even if the associated step is deactivated before the delay
period.
DS Note 1 Action is time delayed and stored. If the associated step is
deactivated before the delay period, the action is not stored.
SL Note 1 Stored and time limited. The action is started and executes for a
given period.

Note 1: These qualifiers all require a time period.


Note 2: These action qualifiers are proposed in the 1998 IEC 1131-3
amendments for the second edition.
202 Programming industrial control systems using IEC1131-3

Care should be taken selecting action qualifiers to ensure that actions only execute
when required. The behaviour of all stored actions, that continue to execute long
after their associated steps have been deactivated, requires careful scrutiny.
The behaviour of the different qualifier types is best understood from the
following timing diagrams:

W non stored action qualifier

StepA.X
StepA N Actioni
Actioni
T1 T1

The action 'Actioni' executes continually while 'StepA' is active, i.e. while the
step's .X executing flag is 1. It then executes one last time after the step is
deactivated.

'S' set and 'R' reset action qualifiers

Stepl.X
Stepi —S Actioni
T1

Actioni

StepN.X

StepN —R Actioni TN

TN

The S qualifier causes the action 'Action 1' to begin execution immediately the
step becomes active; the action is stored. The action continues to execute until an
action block with an R qualifier that references 'Action 1' is reached. This resets
the stored action and it ceases one execution after the step 'StepN' is activated. If
a stored action is never reset, it will continue to execute indefinitely.
Chapter 8 Sequential Function Chart 203
'U time limited action qualifier

Stepi .X
Stepi - L Action 1
T#4s T1
T1 Actioni
4s

Stepi .X
T1

Actioni

4s

The action 'Actioni' starts to execute when 'Stepl' becomes active. It continues
to execute until a given period has elapsed. If the step is deactivated before the
action's period has elapsed, the action ceases execution. In both cases, the action
executes one last time, i.e. either after the period has elapsed or after the step has
been deactivated.

<
D> time delayed action qualifier

Stepi Actioni
T#4s
T1

Stepi .X
T1

Actioni
4s
204 Programming industrial control systems using IEC1131-3

When the given time period has elapsed, timed from when step 'Stepl' becomes
active, the action starts to execute. It continues to execute while 'Stepi' is active.
It then executes one last time after the step is deactivated. If the step is not active
for longer than the delay period, the action does not execute.

'Py pulse action qualifier

Stepi .X
Stepi - P Actioni
T1
T1 Actioni

With the P qualifier, the action executes once when * Stepi' is activated.
Note: If the standard is implemented exactly as written, the pulse action T ' also
executes a second time from the rule that action statements or networks
shall be executed one final time after the falling edge of the action
qualifier. In some implementations of IEC 1131-3 the pulse action is not
executed a second time on the falling edge of the action qualifier. This
may lead to a difference in program behaviour when ported to different
systems.

'PI' and fP0y pulse action qualifiers

Stepi .X
Stepi P1 Actioni
T1
PO Action2
Actioni
Action2

The IEC 1131-3 amendment for the second edition defines two additional action
qualifiers PO and PI. With the PI qualifier, the action executes once when 'Stepi'
is activated; the PO qualifier executes the action once when the step is de-
activated. These should be used in preference to the T ' qualifier.
Chapter 8 Sequential Function Chart 205

'SD' stored and time delayed action qualifier

StepLX

StepN.X

Actioni

4s
StepN - R Actioni StepLX

StepN.X
TN
Actioni

4s

On 'StepT being activated, the action is stored but does not start to execute until
the time period has elapsed. The action continues to execute until it is referenced
in a later step with an R reset qualifier. Even if 'Stepl' is deactivated before the
time period has elapsed, the action will still start to execute after the time period.
However, the stored action will not execute, if the same action is called with R
qualifier, before the time period has elapsed.

'DS' time delayed and stored action qualifier

StepLX
Stepi -IDS Actioni
StepN.X
T#4s
T1 Actioni

4s
StepN - R Actioni StepLX

StepN.X
TN
Actioni
206 Programming industrial control systems using IEC1131-3

On 'Stepl' being activated, the action is delayed. After the time period has
elapsed, the action is stored and starts to execute. The action continues to execute
until it is referenced in a later step with an R reset qualifier. If 'Stepl' is
deactivated before the time period has elapsed, the action will not be stored and it
does not execute.

'SU stored and time limited action qualifier

Stepl .X

StepN.X

Actioni

StepN - R Actioni Stepl .X

-TN StepN.X

Actioni

When step 'Stepl' becomes active, the action 'Actioni' is stored and begins to
execute. It continues to execute until the time period has elapsed. Even if 'Stepl'
is deactivated before the period has elapsed, the action still executes for the
complete time period.
However, the stored action will cease execution, if the same action is called
with R qualifier, before the time period has elapsed. In all cases, the action will
execute one last time either after the period has elapsed or after the stored action
has been reset.

The action^control function block


The standard defines a conceptual action control function block to describe the
behaviour of all action qualifiers. Each action is assumed to be controlled by one
instance of this function block. The action control function block does not actually
exist! It is defined in the standard purely as a means of describing the action
execution behaviour. The output of the action control function block is called 'Q'
and when true results in an action being executed.
Chapter 8 Sequential Function Chart 207

The standard states that while Q is true, the action associated with the control
function block is executed. It also states that all action 'statements or networks
shall be executed one final time after the falling edge of Q \ As a result, actions
execute once more after the action's associated qualifier is cleared.
This feature has led to some misunderstanding of how actions execute. The
extra execution, that occurs after the associated action has deactivated, can lead to
some subtle and unexpected side-effects.
For example, consider an action with a T ' pulse qualifier, defined in Structured
Text as:

ACTION COUNTING :
COUNT := COUNT + 1;
END_ACTION

Assume this is an action that is associated with a step and is called Al. Every time
Al is active, COUNT is incremented by one. However, every time Al is
deactivated, COUNT is incremented again due to the rule that action statements
'execute one final time on the falling edge of Q \
The standard has provided this feature so that an action can reset certain
variables after an action block has been deactivated. However, the double
execution of the T* action is an oversight. An amendment to the 1993 version of
the DEC 1131-3 standard provides access to the action qualifier (.Q). It is then
possible to test when an action is executing for the last time because Q will be
false.
It is possible by using certain function blocks that are triggered from the rising
edge of the action qualifier (.Q) to ensure that selected operations only occur once
within action blocks.
For example it might be necessary to count the number of times a motor is
switched on. This can be achieved in a single action block using the 'P' pulse
qualifier. Using an Up-counter function block that counts on the rising edge of the
'CountUp' action qualifier, ensures that the count only increases once.

MotorOn P CountUp

—L-TR1
CTU1(CU:=CountUp.Q);
208 Programming industrial control systems using IEC1131-3

Although the 'CountUp' action is executed twice (once as the P action is


activated, once when it is deactivated), the 'Up-counter' only counts once as it
detects the rising edge on input CU.
Note: The PO and PI action qualifiers defined in the IEC 1131-3
amendment now solve this problem because the action is
only executed once.

8.8 SFC execution

SFC networks can be used to describe both the behaviour of program organisation
units (POU), i.e. programs and function blocks, and the behaviour of actions (see
Section 8.6). In both cases, the execution of the associated SFC network follows
the same rules.
Every program organisation unit is associated with a task. The task is
responsible for periodically executing the language elements within the POU.
Generally, POUs are executed at a regular rate, for example every 500 ms. An
active action executes at the same rate as the SFC that contains it.
An SFC within a POU will be evaluated every time the POU executes.
Similarly, an SFC within an action will be evaluated every time the action
executes.
The SFC evaluation rules are:

1. The initial step of an SFC is always activated when the POU executes after
system initialisation. Any actions associated with the initial step are executed.
2. At the start of each evaluation, the current set of active steps is determined.
All transitions that are associated with active steps are evaluated.
3. Actions which nominally ceased execution in the previous SFC evaluation
are executed one last time.
4. All actions which are active are executed.
5. Any active steps that precede transition conditions that are true are
deactivated and their succeeding steps are activated.
6. Any actions, having an execution enabling condition that ceases, are marked
as inactive, for example, an action with a time limited *L' qualifier when the
time period has elapsed. Such actions are executed one last time in the next
SFC evaluation.
Chapter 8 Sequential Function Chart 209

8.9 SFC rules of evolution

The IEC 1131-3 standard defines a number of constraints on the way SFC
networks are designed and interpreted to ensure that the behaviour is
unambiguous.

1. Two steps can never be directly linked; they should always be separated by
one transition.
2. Two transitions can never be directly linked; they should always be separated
by a step.
3. If a transition from one step leads to two or more steps, then such steps
initiate simultaneous sequences. Simultaneous sequences continue
independently.
4. When designing an SFC, the time to clear a transition, deactivate preceding
steps and activate succeeding steps may be regarded as occurring
instantaneously.
5. Where more than one transition condition is true at the same time, all the
deactivations and activations of associated steps appear to occur in zero time.
The designer should not consider the effects due to timing differences
between transitions that occur simultaneously.
6. A transition condition of a step is not evaluated until all the behaviour
resulting from the active step has propagated through the program
organisation unit. For example, if a step is activated that has a transition
condition that is always true, all the applicable actions are executed once
before the step is deactivated.

Note: In a PLC the time to process SFC steps and transitions may become
significant, especially if the SFC is running in a very fast task.

Evolution of divergent paths

Where there are two or more transitions from one step, the sequence can diverge
to one of a selected number of steps. Even if more than one transition condition is
true simultaneously, only one path is selected. The selected path is determined by
the precedence of the transition.
210 Programming industrial control systems using IEC1131-3

Stepi Stepi

i 2 X
1
-Tr1 -Tr2 -Tr2

Step2 Step3 Step2 Step3

Default, Left to Right Precedence User defined Precedence

Figure 8.7 Precedence of divergent paths

The standard allows the precedence of transition conditions to be modified.


Consider the transitions shown in the left SFC of Figure 8.7. Left to right
evaluation is the normal default. If transitions Trl and Tr2 are both true
simultaneously, the transition is always made to 'Step2\ i.e. the leftmost step. The
default transition priority may be shown in SFC networks by an asterisk placed at
the centre of the divergent branches. If an asterisk is not present, the default left to
right evaluation is always assumed.
It is possible to override the default precedence by numbering the transitions.
The transition with the lowest number then has the highest priority. Consider the
SFC shown on the right of Figure 8.7; if both Trl and Tr2 are true simultaneously,
then the transition is made to 'Step3\ User defined precedence is denoted by
numbered transitions and placing an asterisk at the centre of the branches.

Drill

Job = 4 AND RDY NOT (Job = 4) AND RDY

Turn Grind

Figure 8.8 Mutually exclusive divergent paths

To avoid ambiguous situations that may occur when transitions become true
simultaneously, it is good practice to ensure that transition conditions in divergent
paths are always mutually exclusive, as shown in Figure 8.8. This ensures that the
flow through an SFC network is easier to follow and complies with the
requirements of the original function chart standard IEC 848.
Chapter 8 Sequential Function Chart 211

Sequence skip
A divergent path may also be used to skip a section of a sequence. In this situation
the divergent path contains no steps, as shown in the SFC on the left side of
Figure 8.9.

t L
lUneStartl LineRdy
- | - TrNextPack

- OilPres < 3.0 - OilPres >= 3.0

StartOit Label

- Oil = 1 (* Open *) - LB1 = 1

OHPump Glue

- Pump = 1 (* On *) - GL1 = 1

Filter Check

- f - Filter = 0 (* On *) TrReWork
-TrCheckOK -
I
LineReady EndBatch

I I
Sequence Skip Sequence Loop
Figure 8.9 Special forms of divergent paths

Sequence loop
A divergent path can also be used to repeat a section of sequence by branching
back to an earlier step. If required to add clarity, arrows may be used to indicate
the direction of flow in branches, as shown on the right side of Figure 8.9.

Simultaneous convergence

Pumpi Pump2 MainGen

H i - TrGo

OnLlne SelectAuto

Figure 8.10 Convergent simultaneous sequences


272 Programming industrial control systems using IEC1131-3

A number of simultaneous sequences can converge to a single transition, and then


diverge to a different number of simultaneous sequences. This construct can be
regarded as a 'rendezvous'. All simultaneous sequences going into such a
transition must be complete before the transition condition is evaluated. In Figure
8.10, steps 'Pumpl', Tump2' and 'MainGen' must all be active for the transition
to be tested.
At the point when all preceding steps are active and the transition is cleared, all
preceding steps are then deactivated and the succeeding steps activated. This all
happens in one instant.

8.10 Safe and unsafe design

Certain arrangements of branches in SFC networks can lead to unsafe designs.


Situations where a divergent path branches out of a simultaneous sequence can
lead to sequences that never complete or that behave unpredictably.

Stepi
an Tr1
T"

Step2 StepA
-TrA
X
«••
-Tr2

Step3 StepB

- Tr3 -TrB11 - TrB2


Step4 StepC | StepD |

TrX TrD
StepX
TrY

Figure 8.11 Unsafe SFC


Chapter 8 Sequential Function Chart 213
Figure 8.11 depicts an unsafe SFC network. If the divergent path to 'StepD' is
taken, the sequence execution returns to an earlier step 'Stepl'. As a consequence,
one of the steps within the sub-sequence 'Step2' to 'Step4' will remain active. As
execution of the SFC continues, it is possible for more than one step to become
active in the same sub-sequence, resulting in unpredictable behaviour.

| Stepl
J
Tr1

Step2
am
-Tr2
StepA

-TrA
X Step2

-Tr2
StepA

-TrA
y
Step3 StepB Step3 StepB
Tr
-Tr3 -TrB1
"h I -Tr3

Step4
_-TrB 1 -

| StepD
TrB2

|
Step4 StepC | StepD StepC

-TrC -TrD

- h TrX StepE
itepX

TrX
StepX

Figure 8.12 Unreachable SFC

Figure 8.12 depicts another form of unsafe SFC. In the SFC on the left, 'StepX'
is unreachable because transition TrX is never evaluated. This is because steps
'StepC and 'StepD' are mutually exclusive; it is never possible for all the steps
going into the simultaneous sequence convergence to be active. By adding a
further step as shown on the right, transition TrX can be evaluated and step
'StepX' reached. Although step 'StepE' may contain no actions, it is required to
indicate that the sequence initiated by step 'StepA' has completed.
Generally the same number of sequences that are initiated by simultaneous
divergence should terminate at a simultaneous convergence.
Some programming systems are able to analyse SFC networks and check for
unsafe constructs. However, care should always be taken, particularly when using
simultaneous sequences, to avoid unpredictable behaviour.
214 Programming industrial control systems using IEC1131-3

Detecting unsafe SFCs

It is possible for an SFC compiler to detect some forms of unsafe SFC construct
by repeatedly applying the following simple algorithm. A complete chart should
resolve down to a single step. If it does not, the SFC has an unsafe design.

Replace Step-transition with a Replace Transition-step-transition


single step with a single transition.
I

-L

Replace divergences of sequence Replace simultaneous sequence-


selection with a single transition. divergences with a single step..

1 1

8.11 Top down design

One of the main uses of Sequential Function Charts is as an aid to developing the
top down design of a complex process or operation. SFC is primarily used to
describe the main changes in state that occur over time. Whenever designing the
top level SFC for any control system, start by identifying the main states.
Chapter 8 Sequential Function Chart 215
For example, consider the design of a furnace for the heat treatment of steel
ingots. This might have the following main states:

'IDLE' The furnace is not in use and cold


'HEATING' The furnace is being heated to the working temperature
'EMPTY' The furnace does not contain any ingots
'LOADING' The furnace door is open; the ingot is being moved into
position
'READY' The furnace contains an ingot;
the furnace door is shut
'TREATING' The furnace is loaded and at the working temperature
'FINISHED' The heat treatment process is complete and ingots can
be unloaded
'COOLING' The furnace is cooling from its working temperature

Although these are the main states, there are typically many minor states that exist
within each of the main states. For example, during the 'TREATING' state it may
be necessary to cycle through a number of different temperatures represented by
states such as 'RAMP TEMPERATURE', 'HOLD TEMPERATURE', etc.

Loading

Action. HeatProfile

Hold Temperature

Each process or plant state can normally be represented as a step in an SFC. It is


good design practice to represent minor states that exist within the main process
states, as steps in an SFC at a lower level in the design hierarchy. This can be
achieved by creating an SFC within an action block, encapsulating the SFC in a
function block or using a macro step (see Section 8.12). For example, the
TREATING' step might have an action called 'HEATPROFILE' which calls an
SFC that generates a profile of temperatures.
276 Programming industrial control systems using IEC1131-3

Why the process changes from one state to another should also be considered.
The change from 'IDLE' to 'HEATING' may occur, for example, because a new
ingot has been delivered to the furnace and the operator has initiated a treatment
cycle. The reasons for the changes of state can be translated into transitions. Each
transition generally occurs because of an event such as the operator activating a
switch, the furnace reaching a working temperature, or a period of time elapsing.
The SFC allows the control problem to be broken down hierarchically into steps
and smaller sequences that can then be analysed in detail. It is then possible to
focus on the behaviour in each particular state.

8.12 Macro steps

Although not defined in the standard, many implementations of IEC 1131-3 also
support the concept of macro steps to help structure large SFCs. A macro step can
be used to hide a complex section of a Sequential Function Chart at a lower level.
This allows a large SFC to be broken down into a number of layers without
changing the way the complete SFC executes.
Consider Figure 8.13. 'Conveyor' is an example of a macro step that contains a
complex section of SFC. In effect, when the SFC executes, the macro step is
replaced by the 'Conveyor' macro step definition. In this case, the step evolution
into the macro is from 'LineStart' directly to 'ConvStart' and then back from
'Ready' to 'Feeds'. It is important to note that although the transition condition
following a macro step may become true while the macro step is active, the
transition will not be made until the last step in the macro definition has been
reached.
Conveyor Macro Step

ConvStart

— — Speed = 2&6 — Product = 12 - — Products 15

ConveyoM Conveyor2

— Rate = 60 - - R a t e = 72
mm

i Ready
\

Figure 8.13 Macro step example


Chapter 8 Sequential Function Chart 217
Note: Macro steps can be regarded as a means to organise large SFCs. They do
not change the way the SFC executes. However some implementations have
added additional run-time support for macro steps e.g. diagnostics for
showing macro step status.

8.13 Good programming style

To ensure that Sequential Function Charts are always easy to follow and maintain,
the following points should always be considered:

• Use meaningful names for steps, transitions and actions wherever possible.
• Try to keep each SFC small and focused on the main behaviour being
considered at that level in the design hierarchy; all detailed behaviour should
be contained within action blocks and depicted in SFCs at lower levels.
• Try to reduce the interaction between different simultaneous sequences to a
minimum.
• Avoid allowing actions of steps within different simultaneous sequences from
changing the same variables. For example, avoid steps in different sequences
from changing the same function block input parameter.
• Care should be taken where an action contains a sub-sequence that can be
stopped in any state by the 'top' level sequence. The 'top' level sequence
must always ensure that all incomplete operations arising from suspended
sub-sequences are correctly 'tidied-up'. This problem commonly arises when
sequences are prematurely halted by some form of plant trip condition.

8.14 Scope of names within SFC networks

All names for steps, transitions, transition connectors and actions should be
unique within the program organisation unit (e.g. function block) that contains the
SFC network.
However SFC networks within function blocks, such as those called within
action blocks, are limited to the scope of their associated program organisation
unit. In other words, there may be many steps called 'Start' provided that they all
exist in different function blocks or programs.
Note: SFC elements within an action block are considered to be within the same
scope as the outer SFC.
275 Programming industrial control systems using IEC1131-3

8.15 SFC textual form

Sequential Function Charts can also be described textually. The standard provides
a language syntax so that a complete SFC can be described in textual statements.
The textual form can be used for storing SFCs as text. One of the main uses could
be as an intermediate form for porting SFC designs between different PLC
systems.
If all actions and transitions are also described using a textual language, i.e.
Structured Text or Instruction List, the complete SFC design can be described in a
set of text files that can be imported into other systems. In the future, software
analysis tools may be developed to check the SFC structure formally from the
textual SFC definition.
The following set of text statements describe the fragment of SFC shown in
Figure 8.5.
INITIAL_STEP Start:
Prompt__Operator (N, StartSwitch) ;
END_STEP

TRANSITION FROM Start TO Fill :


StartSwitch = 1;
END_TRANSITION

STEP FILL :
OpenValves(P) ;
StartPump(N);
END_STEP

ACTION StartPump :
MainPump := ON;
Pumpl := ON;
END_ACTION
The step body between the keywords STEP and END_STEP contains a set of
actions associated with the step. It may contain no actions for a null step. The
initial step is identified using the keyword INITIALJSTEP.
The action association is described with the following arguments:
ActionName ( Q u a l i f i e r , Timed__Qualif i e r ,
indicator_variable );
The Time_Qualifier field may be omitted if it is not applicable for the qualifier.
The indicator variable is optional.
Chapter 8 Sequential Function Chart 219

Examples are:
Action_StartUp(L/ T#2m, Ready);
Action_Stop(P,Stopped);

The transition definition may have one or more steps after the FROM keyword.
More than one step indicates that the transition is being used to terminate a
number of simultaneous sequences. It may also have more than one step after the
TO keyword. This indicates that the transition is being used to initiate a number of
simultaneous sequences.
For example, the following definition could be used to describe the transition
TrGo shown in Figure 8.10:
TRANSITION FROM (Pumpl, Pump2 , MainGen)
TO (OnLine, SelectAuto)
:= (GO = 1 ) ;
END_TRANSITION

The definition of an action is defined by any number of ST or IL statements


given between the keywords ACTION and END_ACTION.

8.16 SFC example


We will now consider using SFC to Brake
program an industrial lift, the sort of
lift that might, for example, be found Motor
in a warehousing system. Proximity Switches
The lift can be requested to stop at — Floor Switch
any floor and can be raised or
lowered by a motorised winch. When
the lift is within a small distance of
any floor level, a proximity micro-
switch is activated. There are two
proximity switches, just above and
below the lift stop position. When the
lift is approaching a selected floor,
the proximity switch signals that the
lift should slow down and inch
slowly towards the stop position for
the selected floor.
A floor micro-switch is activated when the lift is at the correct level to signal
that the lift door can be opened.
220 Programming industrial control systems using IEC1131-3

LJ^ s PowerOn
N ResetLfft Ready
- - Ready

PoorOpen
FloorCall > 0 AND (CloseDoor
OR DoorOpen.T > T#1 Os)
Shutting | 1 N | ShutPoor Shut
U
- U Shut
MotorControl
MoveLift
Apply Brake
Proximity[FloorCaiq = 1 OR Fault

| Inching Motorlnching Fault


T#5s
Checks | - [ N | CheckLimits | Fault
- - Floor[Fk)orCall] = 1 AND NOT Fault
- - Fault OR EmergStop
Stopping | — | S | Apply Brake | ChkFault
— - Stopping.T > T#2s

Opening | — | N | Open Door |Open


- - Fault
- — Open
InchFault

Halted N Alarm
S Apply Brake
R PowerOn

Figure 8.14 SFC lift control example

Part of an SFC to control the lift is shown in Figure 8.14. The initial step 'Init'
sets a stored action 'PowerOn' which controls the main power feed to the motor
and door mechanism. This action remains active until it is reset as a result of a
fault condition in the 'Halted' step.
There are two simultaneous sequences which are initiated by the transition
condition 'Ready'; this indicates that the lift has been moved to its starting
position and the lift door has been opened.
The main sequence starts with the 'DoorOpen' step. This step remains active
until a 'FloorCall' value has been detected and either 10 seconds have elapsed or
the 'DoorClose' button has been detected. The 'FloorCall' signal contains the
number of the floor where the lift is requested to go next. To keep the example
simple, the logic that selects the called floor is not shown but might need to
include floor priority, lift request wait times etc.
The 'Shutting' step calls the action 'ShutDoor'; this step remains active until
the door microswitch 'Shut' is detected. The 'MoveLift' step resets the stored
Chapter 8 Sequential Function Chart 221
action 'ApplyBrake' and activates the 'MotorControl' action that is responsible
for ramping the winch motor up to speed to move the lift towards the selected
floor. When the 'Proximity' switch signal for the called floor is detected, the
'MotorControl' action ceases. Note that the 'Proximity' and 'Floor' switches are
held in an array which is indexed by the value of 'FloorCall'.
The 'Inching' step calls an action 'Motorlnching' that is time limited, i.e. it can
be active for up to 5 seconds. If the 'Floor' microswitch is detected within this
time, the 'Stopping' step is activated. This in turn sets the stored action
'ApplyBrake' which controls the winch brake. After 2 seconds, the 'Opening' step
calls an action to open the lift door.

Fault detection
The second simultaneous sequence is concerned with monitoring the health of the
lift. The action 'CheckLimits' contains logic that monitors such things as, that the
lift is moving in the correct direction, is within operating speed limits, and is
within lift shaft limits. On detecting an out of limits condition, the action block
sets the 'Fault' signal true.
In the main sequence, the 'Fault' signal can cause the 'MoveLift' step to cease
immediately, the 'Inching' step to be prematurely deactivated and the 'InchFault'
step to be activated.
Notice that if the 'Floor' switch is not detected during the 'Motorlnching'
action, the 'Fault' signal is set true. This also results in the 'InchFault' step being
activated.
If 'InchFault' and 'ChkFault' are both active, the simultaneous sequences both
terminate, and the 'Halted' step is activated. This resets the power, activates an
alarm and applies the winch brake.
Note: This example is used to demonstrate the SFC language and should not be
considered as representative of a control system for an industrial lift where
there are issues concerning safety.

Summary
We have seen that Sequential Function Chart provides a flexible and intuitive
method for graphically programming sequences of actions in a control system.
Some of the main features are:

• SFC is based on established standards and accepted industrial practice.


• SFC allows alternative sequences to be selected using divergent paths.
222 Programming industrial control systems using IEC1131-3

• There is support for running sequences in parallel using simultaneous


sequences.
• Actions and transitions can be programmed using any of the IEC languages.
• A wide range of action qualifiers is provided to give full control over when
actions start and stop.
• There is support for hierarchical top down design.
• SFC can be used at any design level, at the top level within a program or at a
low level within a function block.
• A textual form is provided to enable SFC designs to be ported to different
PLC systems.
Chapter 9

Function blocks

The use of function blocks is one of the most important concepts formalised by
the DEC 1131-3 standard. Using function blocks in the design of control software
has many benefits including improving software quality and productivity, as
reviewed in the introduction - see Chapter 1, Section 9.
In this chapter we will consider:

• The definition of function block types;


• Re-use of function blocks using function block instances;
• Definition and use of IEC standard function blocks;
• A review of some of the example function blocks.

9.1 Function blocks as software building blocks

The IEC 1131-3 standard encourages the development of well-structured software


that can be designed using either a top-down or bottom-up approach. An
important concept that underpins this objective is the use of function blocks.
A function block is a well packaged element of software that can be re-used in
different parts of an application or even in different projects. A function block can
provide a software solution to a small problem, or to the control of a major unit of
plant.
A function block describes the behaviour of data, the data structure and an
external interface defined as a set of input and output parameters. An important
characteristic is that the input and output parameters can only use data types as
defined within the standard.
Function blocks are the basic building blocks of a control system and can have
algorithms written in any of the IEC languages as described in earlier chapters.
Well designed function blocks should have use in a wide range of applications and
projects.
224 Programming industrial control systems using IEC1131-3
DEC 1131-3 defines a small repertoire of fairly rudimentary function blocks.
There has been no intention to define a comprehensive range of industrial function
blocks. This may be because obtaining agreement on a range of general purpose
blocks would have probably held up the publication of the standard.
A function block is a type of program organisation unit (POU) which provides
an encapsulated algorithm that transforms data within the function block structure.
When a function block executes, it evaluates all its variables, which include input,
internal and output variables. During its execution, the algorithm creates new
values for both the internal and output variables.
A significant feature of a function block is data persistency. Each block can
hold data values between each execution, i.e. it has retained state. In some cases, if
variables are defined using the RETAIN attribute as discussed in Chapter 3,
Section 11, values may be retained between PLC power cycles.

Function block type definitions

A definition for a function block type has two parts:

(1) a specification of the data structure consisting of input parameters, internal


variables and output parameters using textual declarations as given in
Chapter 3 'Common elements';
(2) an algorithm expressed using either Structured Text, Function Block
Diagram, Ladder Diagram, Instruction List or Sequential Function Chart.

Function Block
Type Definition

Variable Declarations

Function Block
Instances

Figure 9.1 Function block types and instances


Chapter 9 Function blocks 225
Function block instances

A function block instance is a particular set of data values held in structures as


defined by the function block type. The data in a function block instance can be
transformed by the algorithm that is specified in the function block type definition.
The instance only contains data that are unique to a particular application of the
function block. This is an important characteristic. Although a function block may
have a long and complex algorithm, the memory requirements to hold the
variables for each instance of the block may be fairly modest.
Instances of well designed function blocks will generally require less memory
than replicas of the equivalent software. The relationship between function block
types and instances is shown in Figure 9.1.

Function block example

Consider a DELAY function block, that provides an 'N Sample' delay from the
input XIN to output XOUT; this is one of the example blocks defined in the IEC
1131-3 standard. The format for describing the external view of a function block
is as shown. Note that inputs are on the left and outputs on the right.

Function Block Type

DELAY
BOOL RUN

REAL XIN
XOUT REAL
INT -J— N

Output Parameters
Input Parameters

Each parameter is depicted with its name and data type. The function block type
is always given just inside the top edge of the block.
The DELAY block is able to delay an input signal by a given number of
samples. This is achieved by using an internal array as a circular buffer. Each time
the function block executes, a sample is stored at a point in the circular buffer.
The output value is obtained by taking a sample from the buffer that is N positions
behind the input point.
The signal delay produced by this block is proportional to the function block
execution scan rate. For example, a scan rate of 100 ms, and a value of N of 100,
will give a 10 second delay.
226 Programming industrial control systems using IEC1131-3
The definition of the DELAY function block is as follows:

FUNCTION_BLOCK DELAY
(* Variable declarations *)
VAR_INPUT (* Input parameters *)
RUN : BOOL; (* Set to 1 to RUN the block,
i.e. activate the delay *)
XIN : REAL; (* Input to be delayed *)
N : INT; (* Delay sample width *)
END_VAR
VAR_OUTPUT (* Output parameters *)
XOUT : REAL; (* Delayed output *)
END_VAR
VAR (* Internal Variables *)
X : ARRAY[0..127] OF REAL; (^Circular buffer *)
I, IXIN, IXOUT : INT := 0;
END_VAR

(* Algorithm *)
IF RUN THEN
(* Increment the index for the input *)
(* save input value in circular buffer *)
IXIN := MODCEXIN + 1, 128); X(IXIN) := XIN;
(* Increment the index for the output *)
(* save output value in circular buffer *)
IXOUT := MOD(IXOUT +1,128); XOUT := X(IXOUT);
ELSE
(* Reset index values, clear the buffer *)
XOUT := XIN; IXIN := N; IXOUT :=0;
FOR I := 0 TO N DO
X[I] := XIN;
END__FOR;
END__IF;
END_FUNCTION_BLOCK

The DELAY type definition consists of two distinct parts: (1) variable
declarations and (2) an algorithm. The same algorithm is called when any instance
of the DELAY block is executed but with a different set of instance variables.

9.2 Function block usage

The following points, which are discussed more fully in Section 3.29, summarise
the main points concerning the use of IEC function blocks.
Chapter 9 Function blocks 227
• Externally, it is only possible to access the input and output parameters of a
function block instance. Internal variables are not accessible by other program
elements declared outside the function block.
Note: In some IEC 1131-3 implementations, diagnostic facilities may allow
internal variables to be monitored and changed.

• A function block instance is only executed if explicitly requested because


either (a) the function block instance is part of a graphical network of
connected blocks which form a program organisation unit or (b) it is called in
one of the textual languages, i.e. Structured Text or Instruction List.
• Instances of a particular function block type can be used in other function
block or program type definitions. An instance of a function block cannot be
used within its own type definition - recursion is not allowed.
• Function block instances that are declared as globals using the
VAR_GLOBAL construct, are accessible anywhere within a whole resource
or configuration.
• It is possible to pass a function block instance as an input to another program,
function block or function. This leads to some interesting programming
possibilities but can give rise to some unexpected side-effects.
• The current values of function block output parameters can always be
accessed in the same way as accessing data for a structure, e.g. Off_timerl.Q.

9.3 Standard function blocks

The EEC 1131-3 standard defines a small range of fairly basic function blocks.
However, it is quite surprising how frequently the standard blocks are used when
constructing more complex blocks. The symbols for the standard blocks are based
closely on the IEC standard 617-12 'Graphical symbols for diagrams'.

Bistables

SR bistable Algorithm as Function Block Diagram

SR 51 OR
BOOL SI Ql BOOL Ql

BOOL R R - 0 AND

Ql
228 Programming industrial control systems using IEC1131-3
The SR bistable is a latch where the Set dominates. If the Set and Reset signals are
both true, the output Ql will be 1 (true).

RS bistable Algorithm as Function Block Diagram


M —n AND
RS — Ql
BOOL — S Q1 — BOOL s — OR
BOOL — R1
Ql

The RS bistable is a latch where the Reset dominates. If the Set and Reset signals
are both true, the output Ql will be 0 (false).

Note: Both SR and RS bistables are defined using Function Block Diagram in
which the output value Ql is used in a feedback path. The use of feedback
in graphical languages is discussed in Chapter 5, Section 3.

Semaphore Algorithm in Structured Text

— BOCL FUNCTION_BLOCK SEMA


VAR__INPUT
CLAIM , RELEASE : BOOL;
END_VAR
The Semaphore is designed to VAR_OUTPUT
BUSY : BOOL;
allow competing tasks to share a
END__VAR
particular resource. VAR
A particular Semaphore instance X : BOOL := 0;
END_VAR
can be claimed by calling the BUSY := X;
function block with the input IF CLAIM THEN
CLAIM set to true. If the X:= 1;
ELSEIF RELEASE THEN
semaphore is not already in use, BUSY := 0; X := 0;
the output BUSY is returned as END__IF;
FALSE indicating that the claim END__FUNCTION_BLOCK
was successful.

Subsequent calls of the function block to claim the semaphore will all return
with BUSY set to TRUE, indicating that the claim has failed. The semaphore can
be released by calling the function block with the RELEASE input true.
Chapter 9 Function blocks 229
The Semaphore function block SEMA provides a mechanism to allow software
elements mutually exclusive access to certain resources, i.e. it allows a resource to
be shared between two or more software clients.
For example, consider a PRINTER function block that sends messages to a
ticket printer. It can only send one message at a time and therefore can only be
servicing one task at a time. There may be many other points within different tasks
that also require access to the same function block to send messages. The
Semaphore can be used to prevent more than one task accessing the PRINTER
function block at any one time.
In such situations, it is likely that an instance of the Semaphore function block
will need to be declared as global to be accessible from many different function
blocks. Whenever any task detects that the Semaphore for the printer is busy, it
should wait and attempt to claim the Semaphore some time later.
Note: It has been said that the IEC 1131-3 definition of the SEMA function block
is not an efficient way to control mutually exclusive access to resources.
Ideally the Semaphore mechanism should be built into the low level task
management of the PLC. An amendment to the 1993 edition of IEC 1131-3
removes the SEMA function block from the standard.

Edge detection
The two edge detecting function blocks 'Rising edge trigger' RJTRIG and
Tailing edge trigger' FJTRIG are provided to detect the changing state of a
boolean signal. The outputs of both blocks produce a single pulse when an edge is
detected.

Rising edge detector Algorithm in Structured Text


RJTRIG
FUNCTION_BLOCK R_TRIG
BOOL CLK Q BOOL VAR_INPUT
CLK : BOOL;
END__VAR
VAR_OUTPUT
Q : BOOL;
END_VAR
VAR
M : BOOL := 0;
END_VAR
Q := CLK AND NOT M;
M := CLK;
Function Block Executions END_FUNCTION_BLOCK

When the CLK input goes true, the output Q is true for one function block
execution. The output Q then remains false until a new rising edge is detected.
230 Programming industrial control systems using IEC1131-3
Falling edge detector Algorithm in Structured Text

F_TRIG FUNCTIONJBLOCK F_TRIG


BOOL CLK Q BOOL VAR__INPUT
CLK : BOOL;
END_VAR
VAR_OUTPUT
Q : BOOL;
END_VAR
VAR
CLK J M : BOOL := 1;
END_VAR
Q — Q := NOT CLK
AND NOT M;
Function Block Executions
M := NOT CLK;
END FUNCTION BLOCK

When the CLK input goes from true to false, the output Q is true for one function
block execution. The output Q then remains false until a new falling edge is
detected.
Note: These blocks may detect additional edges when there is power-failure or
power-recovery. Whether spurious power cycle edges are detected will
depend on the implementation and whether the internal state of the edge
detection blocks is held in retained memory.

Reserved keywords R_EE)GE and F_EDGE can be used as additional attributes


of boolean input variables of function blocks and programs. They imply that an
instance of the appropriate edge detection function block should be associated
with the input.

Edge detecting inputs Algorithm in Structured Text

FUNCTIONJBLOCK EDGE_CHECK
BOOL VAR_INPUT
CLK1 : BOOL R_EDGE;
CLK2 : BOOL F_EDGE;
END_VAR
VAR_OUTPUT
A rising edge input is shown by a OUT : BOOL;
left-to-right arrow (see CLK1). A END_VAR
falling edge input is shown by a OUT := CLK1 OR CLK2;
END_FUNCTION_BLOCK
right-to-left arrow (see CLK2).

In this example, the output OUT is true when either CLK1 detects a rising edge
input or CLK2 detects a falling edge.
Chapter 9 Function blocks 231

Counters

A set of general purpose counter function blocks is provided. These are designed
to be used in a wide range of applications, for example counting pulses, shaft
rotations, completed product batches and so on.

Up-counter Algorithm in Structured Text

CTU FUNCTION_BLOCK CTU


BOOL — » CU Q BOOL VAR_INPUT
BOOL R
CU : BOOL R_TRIG;
CV INT R : BOOL;
INT PV
PV : INT;
END_VAR
VAR_OUTPUT
The up-counter block CTU can be Q : BOOL;
used to signal when a count has CV: INT;
END_VAR
reached a maximum value. IF R THEN
The CTU block counts the number CV := 0;
of Rising edges' detected at the input ELSIF CU
AND (CV < PV) THEN
CU. PV defines the maximum value CV := CV + 1;
for the counter. Each time the END_IF;
function block is called with a new Q := (CV >= PV ) ;
END_FUNCTION BLOCK
rising edge on CU, the counter output
CV is incremented by one.

When the counter reaches the PV value, the Q output is set true and the counting
stops. The reset input R can be used to set the output Q to false, and clear the
count CV to zero.

Down-counter Algorithm in Structured Text


CTD
BOOL — » CD Q BOOL FUNCTIO1SLBLOCK CTD
VAR_INPUT
BOOL LD
CV INT
CD : BOOL R_TRIG;
INT PV LD : BOOL;
PV : INT;
END_VAR
The down-counter block CTD can be VAR_OUTPUT
used to signal when a count has Q : BOOL;
reached zero, on counting down from a CV: INT;
END_VAR
preset value.
232 Programming industrial control systems using IEC1131-3
The CTD block counts down I F LD THEN
CV := PV;
the number of Rising edges'
ELSIF CD AND (CV > PV)
detected at the input CD. PV CV := CV - 1;
defines the starting value for END I F ;
the counter. Each time the Q := (CV <= 0 ) ;
END_FUNCTION BLOCK
function block is called with a
new rising edge on CD, the
counter output CV is
decremented by one.

When the counter reaches zero, the Q output is set true and the counting stops.
The load signal LD can be used to clear the counter output Q to false, and load the
count CV with the preset value PV.

Up-down counter Algorithm in Structured Text


FUNCTION_BLOCK CTUD
CTUD VAR_INPUT
BOOL — * CU QU BOOL CU, CD : BOOL R__TRIG;
BOOL CD QD BOOL R, LD : BOOL;
BOOL R PV : INT;
BOOL LD END__VAR
INT PV CV INT VAR_OUTPUT
QU, QD : BOOL;
The up-down counter block CTUD CV: INT;
END_VAR
has two inputs CU and CD. It can be IF R THEN
used to both count up on one input CV := 0;
and down on the other. ELSIF LD THEN
CV := PV;
The CTUD block counts up the ELSIF CU
number of 'rising edges' detected at AND (CV < PV) THEN
CV := CV + 1;
the input CU and counts down the
ELSIF CD
'rising edges' detected on CD. PV AND (CV > 0) THEN
defines the maximum value for the CV := CV - 1;
END_IF;
counter. QU := (CV >= PV);
If the counter output CV reaches QD := (CV <= 0 ) ;
zero, the QD output is set true and END_FUNCTION_BLOCK
the counting down stops. If CV
reaches the maximum value PV, the
QU output is set true and the
counting up stops.
Chapter 9 Function blocks 233
The load signal LD can be used to preset the counter output CV with the value
PV. Similarly, the reset signal R can be used to clear the counter output to zero.
The up-down counter could be used, for example, to count items placed on and
taken off a conveyor belt. The count value would indicate how many items are on
the belt at any time.
Note: If any of the counter function blocks are executed with count inputs, such as
CU, continually held true, they will not detect any rising edges and
therefore will not count!

Timers

The standard defines a small set of standard timer function blocks. These can be
used in a wide range of applications, for example measuring the time to add
reactants to a reactor vessel, eliminating switch bounce, timing mechanical
interlocks etc.
The timer blocks are generally used in the graphical languages where there are
simple timing requirements. For complex timing operations involving sequencing,
it is recommended that Sequential Function Charts and actions with timing
qualifiers are used: see Chapter 8, Section 6.
The functionality of all the timer function blocks is implemented typically as
part of PLC system firmware, i.e. as system routines - because the timers are
closely connected with the operating system timing.

Pulse timer Timing diagram

BOOL IN
TP
Q BOOL
IN
PT
nn
TIME
~l 1
TIME PT ET
Q

The pulse timer block can be used to generate output pulses of a given time
duration.
As input IN goes true, the output Q follows and remains true for the pulse
duration as specified by time input PT. While the pulse output is true, the elapsed
time ET is increased. On the termination of the pulse, the elapsed time is held
until the beginning of the next pulse, at which point it is reset.
The output Q will remain true until the pulse time has elapsed, irrespective of
the state of the input IN.
234 Programming industrial control systems using IEC1131-3
On-delay timer Timing diagram

TOF
BOOL IN Q BOOL

PT ET — TIME
TIME

Note: The on-delay timer can be


represented alternatively using T—0' in
place of the text TON' in the FBD and
LD graphical languages.

The on-delay timer can be used to delay setting an output true, for a fixed period
after an input becomes true.
As input IN goes true, the elapsed time at output ET starts to increase. When the
elapsed time reaches the time specified by the input PT, the output goes true, and
the elapsed time is held.
The output Q remains true until the input IN goes false. If the input is not true
longer than the delay time specified in PT, the output remains false.

Off-delay timer Timing diagram

TON
IN
BOOL IN Q BOOL
PT PT

n
PT ET I TIME
TIME

JL
Note: The off-delay timer can be
represented alternatively using '0—T'in
ET
place of the text TOF'in the FBD and
LD graphical languages.

The off-delay timer can be used to delay setting an output false, for a fixed period
after an input goes false, i.e. the output is held on for a given period longer than
the input.
As input IN goes true, the output Q follows and remains true until the input IN
is false for the period specified in input PT. As input IN goes false, the elapsed
time ET starts to increase. It continues to increase until it reaches the period given
by PT, at which point the output is set false and the elapsed time is held.
Chapter 9 Function blocks 235
If the input is only false for a period shorter than the input PT, the output
remains true.
A typical use of an off-delay timer is in removing short glitches from noisy
input signals, say, from mechanical sensors. An input has to be off for a specified
time before its change of state is detected at the timer output.

Real time clock


The real time clock has
many uses including time
RTC
EN Q BOOL
stamping, setting dates
BOOL
and times of day in batch
DATE_AND_TIME PDT CDT DATE_AND_TIME
reports, in alarm
messages and so on.

The behaviour of the real time clock function block is unusual because of the
need to set the initial clock value.
The RTC function block can be set to the current time by calling the function
block with the input RUN set to true (1), provided that either:

(a) the function block has been previously executed with the input RUN set to
false (0), or
(b) the function block is being executed for the first time.

The input parameter PDT (Preset Date and Time) should be set to the initial date
and time. Thereafter, the current date and time can be read by calling the RTC
function block with the input RUN set to 1; the value of input PDT is then
ignored. The value of CDT does not change until the RTC function block is called
again.
The value of the output CDT is not defined if the RTC function block is called
with the input RUN set to 0.

Note: The IEC amendment to the 1993 edition of the 1131-3 standard
removes the Real Time Clock (RTC) function block definition from the
standard because it has proved to be very difficult to implement.

It is likely that many PLCs will only support one instance of the RTC function
block. However, by declaring the RTC function block instance as a global
variable, the current date and time can be obtained anywhere within programs and
function blocks.
236 Programming industrial control systems using IEC1131-3
The real time clock generally will need to be set by operator interaction at some
point when a system is first put on-line. The current time can then be obtained by
executing the RTC function block.

RTC example:

CONFIGURATION SYSTEM_ABC
VARJ3L0BAL
RTC_Clockl : RTC;
END_VAR
PROGRAM PR0G1
VAR_EXTERNAL
RTC_Clockl : RTC;
END_VAR

IF SetClock = True THEN


(* Set clock *)
RTC_Clockl(RUN := 0 ) ;
RTC_Clockl(RUN := 1,
PDT := InputTime ) ;
ELSE
(* Update current time *)
RTC_Clockl(RUN :=1);
CurrentTime:= RTC_Clockl.CDT;

There may be situations where a PLC can support more than one instance of an
RTC function block, in which case each RTC instance will behave as a separate
clock. This might be useful when dealing with the times and dates across different
time zones. For example, one RTC could be set to the local data and time, while a
second RTC instance is preset with the date and time for a different time zone.

9.4 Example blocks

We will now look at a few example function blocks. Some of these are described
in the EEC 1131-3 standard. They are provided to demonstrate the capabilities of
function blocks. For industrial applications it is likely that these function blocks
would require significantly more functionality.
Chapter 9 Function blocks 237
Integral Algorithm in Structured Text

INTEGRAL
BOOL RUN Q BOOL FUNCTION_BLOC
R1 VAR_INPUT
BOOL XOUT REAL
RUN • BOOL Integrate
REAL XIN
1, Hold 0 *)
REAL XO R l : BOOL; ( Reset *)
TIME CYCLE XIN REAL (* Input for
integral *)
XO : REAL; (* Initial
The INTEGRAL function block value *)
CYCLE : TIME; (*Cycle
integrates the value of input XIN time *)
over time. The integration can be END_VAR
reset to a preset value XO by VAR__OUTPUT
Q : BOOL; (* 1 = Not
setting the reset input Rl to true. Reset *)
The CYCLE time defines the XOUT: REAL; (*Int. Out*)
time between function block END_VAR
Q := NOT Rl;
executions. The output XOUT is IF Rl THEN
integrated while the RUN input is XOUT := XO;
ELSIF RUN THEN
true; otherwise the integration XOUT := XOUT + XIN *
value is held. TIME_TO_REAL(CYCLE);
The Q output is true while the END_IF;
END_FUNCTION BLOCK
integral is not being reset.

We will see that the INTEGRAL function block is a useful building block in
creating control loop algorithms, such as a PID function block. Other more general
uses include, for example, calculating the energy used for an item of plant, such as
a pump or fan motor, by integrating power over 'running hours'.
238 Programming industrial control systems using IEC1131-3
Derivative Algorithm in Structured Text

FUNCTION_BLOCK DERIVATIVE
DERIVATIVE VAR_INPUT
BOOL RUN XOUT REAL RUN : BOOL;(*0 =Reset *)
XIN : REAL; (* Input
REAL XIN
for derivative *)
TIME CYCLE CYCLE : TIME;(*Cycle
time *)
END_VAR
VAR_OUTPUT
XOUT:REAL; (* Deriv Out *)
The DERIVATIVE function END_VAR
block produces an output XOUT VAR
proportional to the rate of change XI, X2, X3 : REAL;
END_VAR
of the input XIN IF RUN THEN
The derivative is calculated XOUT := ( 3.0 *
(XIN - X3) +
while the RUN input is true.
XI - X2 )/(10.0 *
With RUN set false, the TIME_TO_REAL (CYCLE) ) ;
derivative output is reset to zero. X3 := X2; X2 := XI;
XI := XIN;
The function block CYCLE time ELSE
is required in calculating the (* Reset *)
change of input value over time. XOUT := 0.0; XI := XIN;
X2 := XIN; X3 := XIN;
END_IF;
END FUNCTION_BLOCK
XIN _

XOUT. K_
The DERIVATIVE function block is mainly used in creating control loop
algorithms; it is an important component of the PID function block. It could also
have uses in creating alarms or monitoring critical process parameters where the
rate of change is important.
Chapter 9 Function blocks 239

PID The PID (proportional, integral,


derivative) function block provides the
classical three term controller for closed
PID loop control. It can be used in a wide
BOOL AUTO XOUT REAL
range of applications where there is a
REAL PV
requirement for stable control using
REAL SP feedback of the process value.
REAL XO The setpoint SP input defines the
REAL KP required value for the process value PV.
TR When the function block is in AUTO it
REAL
calculates the appropriate value for the
REAL TD
output XOUT to move the process
TIME CYCLE
closer to the desired setpoint value. The
PED algorithm can be tuned to give
control with minimum overshoot and
steady-state error.

Closed loop control as provided by the PID function block is useful where the
process is subject to disturbances caused by external factors or unpredictable
disturbances. Examples are when controlling the pressure of a reactor vessel and
the pressure changes suddenly due to additional gas being liberated in a chemical
reaction, and when controlling a furnace and the internal temperature is affected
by changes in the ambient air temperature.
Tuning and the design of PID algorithms are complex topics which are outside
the scope of this book. The following figure provides a brief outline of the main
features of the algorithm:

In a typical application, the output XOUT is used to drive an actuator of some


form that directly affects the process, e.g. the speed of a pump producing
compressed air, the position of a valve delivering gas to a furnace.
240 Programming industrial control systems using IEC 1131-3
The full definition of the example PID block as given in the standard is as
follows:
FUNCTION^BLOCK PID
VAR_INPUT
AUTO : BOOL; (* 0 - Manual, 1 -Automatic *)
PV REAL; (* Process variable *)
SP REAL; (* Set point *)
XO REAL; (* Manual output adjustment *)
KP REAL; (* Proportional constant *)
TR REAL; (* Reset time *)
TD REAL; (* Derivative Time constant *)
CYCLE TIME; (* Fun. Blk cycle time *)
END_VAR
VAR_OUTPUT
XOUT : REAL;
END_VAR
VAR
ERROR REAL; (* Process error PV-SP *)
ITERM INTEGRAL; (* Integral component *)
DTERM DERIVATIVE; (* Derivative component
END_VAR
(* PID Algorithm expressed using FBD *)

PV
ERROR
SP
ITERM
INTEGRAL
AUTO RUN Q
R1 XOUT ->ITERM_XOUT >
XIN
TR

XO
ERROR
IT CYCLE

DTERM
DERIVATIVE
RUN XOUT ->DTERM_XOUT >
XIN

CYCLE CYCLE

KP
ERROR
XOUT
>ITERM_XOUT
/ + [T
TR

>DTERM_XOUT > -
*
TD

END FUNCTION_BLOCK
Chapter 9 Function blocks 241
PID is an example of a composite function block that is built up from using
more primitive blocks - in this case using instances of the INTEGRAL and
DERIVATIVE function blocks.

Ramp
This RAMP function block is
RAMP modelled on the example given in the
BOOL — RUN RAMP BOOL standard but with the addition of a
REAL — XO XOUT REAL 'Holdback' feature. The RAMP block
REAL — XI
— TR
produces an output XOUT that ramps
TIME
TIME — CYCLE from an initial value XO to a target
BOOL — HOLDBACK value of XI in a time period given by
REAL — ERROR the input TR.
REAL — PV
The ramping function is activated
while the RUN input is true;
otherwise it is reset.
If the HOLDBACK input is true,
the ramping function is held while the
absolute error between the output
XOUT and the process value input PV
Time
exceeds the ERROR value.

A holdback feature is a normal requirement for a process ramp. It is needed to


ensure that the process has time to 'catch up' with the ramp value.
For example, consider slowly ramping up the speed of a conveyor belt. For
some reason, owing to temporary extra loading on the belt, the speed falls
significantly behind the speed demanded by the ramp.
Without holdback, the demanded speed may greatly exceed the actual speed. If
the extra loading is removed, there is a danger that the belt will suddenly
accelerate in speed to catch up with the ramp speed. Holdback can ensure that the
speed never increases dramatically. The ramp is held to ensure that the demanded
speed and actual speed never differ by a value greater than specified by the
ERROR input.

Note: The ramp can be used both for increasing (ramping-up) and decreasing
(ramping-down) values.

The full function block definition is as follows:


242 Programming industrial control systems using IEC 1131-3
FUNCTION_BLOCK RAMP
VAR_INPUT
RUN : BOOL; (* Ramp active 1, Reset 0
XO : REAL; (* Initial value *)
XI : REAL; (* Target value *)
TR : REAL; (* Ramp duration *)
CYCLE : TIME; (* Cycle time *)
HOLDBACK : BOOL; (* Holdback when true *)
ERROR : REAL; (* Error for holdback *)
PV : REAL; (* Process value *)
END_VAR
VAR_OUTPUT
RAMP BOOL; (* 1 = When Ramping *)
XOUT: REAL; (* Ramping output*)
END_VAR
VAR
XI : REAL; (* Intermediate ramp value *)
T : TIME := T#0s; (* Time into ramp *)
END VAR
(* Algorithm *)
IF RUN THEN

(* Holdback if PV differs from XOUT by ERROR *)


IF (HOLDBACK AND ABS(PV - XOUT) < ERROR)
OR NOT HOLDBACK THEN
XOUT := XO + (XI - XO) *
TIME_TO__REAL (T) / TIME_TO_REAL (TR) ;
T := T + CYCLE;
RAMP := TRUE;

ELSE
(* Not ramping because of Holdback *)
RAMP := FALSE;
XOUT := XO; XI := XO; T:= T#0s;

END_IF;

END_IF;

END_FUNCTION_BLOCK
Chapter 9 Function blocks 243
Hysteresis
The HYSTERESIS function block
provides a hysteresis boolean output
HYSTERISIS driven by the difference of two
REAL XIN1 Q BOOL floating point (REAL) inputs X3N1
REAL XIN2
and XIN2.
REAL EPS
If XIN1 exceeds XIN2 by the value
specified by input EPS, the output Q
is true. The output Q remains true
until the input XIN1 is less than the
value XIN2, by the value of EPS. The
value of Q then becomes false.
The diagram depicts how the output
Q changes as XIN1 increases and
decreases.

A hysteresis function block has a wide range of uses. A typical use is in


building alarm function blocks where the alarm is triggered by an input
exceeding a threshold value. Once the alarm is on, it remains on until the input is
less than the threshold value by a specified amount.
The function block type specification is as follows:

FUNCTIONJBLOCK HYSTERESIS
VAR_INPUT
XIN1, XIN2 : REAL;
EPS : REAL; (^Hysteresis band +ve and -ve *)
END_VAR;
VAR_OUTPUT
Q : BOOL := 0;(* Initial value is 0 *)
END_VAR
IF Q THEN
IF XIN1 < (XIN2 - EPS) THEN
Q := 0; (* XIN1 decreasing *)
END_IF;
ELSEIF XIN1 > (XIN2 + EPS) THEN
Q := 1; (* XIN1 increasing *)
END_IF;
END_FUNCTION_BLOCK
244 Programming industrial control systems using IEC1131-3
Ratio monitor
The ratio_monitor function block
RATIO_MONITOR checks that one process value PV1 is
REAL PV1 ALARM — BOOL always a given ratio (defined by input
REAL PV2
TOTALERR BOOL RATIO) of a second process value
REAL RATIO
PV2.
TIME TIMON If the error between the values of
TIME TIMOFF
PV1 and PV2, as required to maintain
REAL TOLERANCE
RESET
the ratio, goes outside the given
BOOL
TIME CYCLE TOLERANCE, an alarm timer is
started. If the error exists for longer
than the time specified by TIMON,
the ALARM output is set on.

An off-delay timer is started that ensures that the ALARM stays on for at least a
period defined by the TIMOFF input.
The error between the desired ratio value of PV1 and the measured value is
accumulated by integrating the ratio error over time. The output TOTALJERR
defines the integrated error. This value can be cleared using the RESET input.
The ratio_monitor could be used, for example, when feeding two reactants into
a process, such as when controlling the gas/air mixture for a gas fired brick kiln.
The value of the TOTAL_ERR output gives a quality measure of how well the
ratio is being maintained.
The ratio monitor is an example of a composite function block defined using
more elementary blocks.
The function block type specification is as follows:

FUNCTION_BLOCK RATIOJYIONITOR
VAR_INPUT
PV1, PV2 : REAL; (*Process values *)
RATIO : REAL; (*Ratio between PVl and PV2 *)
TIMON : TIME; (*Time before Alarm is active*)
TIMOFF: TIME; (*Time Alarm is held on *)
TOLERANCE : REAL; (* Acceptable abs. error *)
RESET : BOOL; (* 1 to clear total error *)
CYCLE : TIME; (* Fun. block scan time *)
END_VAR;
VAR_OUTPUT
ALARM : BOOL := 0; (* Ratio error Alarm i
TOTAL_ERR : REAL : = 0; (* Integrated error *]
END VAR
Chapter 9 Function blocks 245
VAR
Errorlnt : INTEGRAL;(* Error Integrator *)
TimerOn : TON; (* Alarm on timer *)
TimerOff: TOF; (* Alarm off timer *)
Error : REAL;
END_VAR
(* Check error between process values *)
Error := ABS( PVl - RATIO * PV2);

IF RESET THEN
(* Reset integrator *)
Errorlnt( Rl := 1, XO := 0.0 ) ;
ELSE
(*Integrate error *)
Errorlnt (RUN := 1, Rl := 0,
XIN := Error, CYCLE := CYCLE ) ;
TOTAL_ERR := Errorlnt.XOUT;
END__IF ;
(* Call alarm timers if alarm is active *)
TimerOn ( EN:= Error > TOLERANCE, PT := TIMON) ;
TimerOff( EN: = TimerOn.Q, PT := TIMOFF);
ALARM := TimerOff.Q;
END_FUNCTION_BLOCK

9.5 Designing function blocks

When designing a new function block type it is always worth considering all the
possible current and future uses of the block. There are many advantages to
developing a library of well proven blocks that can be applied to a wide range of
problems.
On the other hand, care should be taken not to build so many features into the
block that it becomes unwieldy to use.
For more complex blocks consider all the interactions that the block may have
with its environment. In particular, consider facilities for:
• Operator control and override
• Commissioning and tuning
• Testing
• Monitoring its internal behaviour

Up to now we have only considered function blocks that are defined using the TEC
languages. However, there may be situations where it is necessary to develop a
function block algorithm using a language such as ' C or 'PASCAL'. This
normally applies to function blocks that need to interact closely with the PLC
operating system.
246 Programming industrial control systems using IEC1131-3
In some cases, the algorithm may become part of the system software. Provided
that the block has input and output parameters that are defined using the EEC data
types, it can be used within IEC languages just like any other block.

Summary
The main features of this chapter can be summarised as:
• Function blocks are important software building blocks for constructing
control systems using proven solutions.
• Using function blocks speeds software development.
• Function blocks allow PLC memory to be used more efficiently than simply
copying identical software.
• IEC 1131-3 defines a small repertoire of elementary, yet very useful, function
blocks that includes bistables, timers and counters.
• The standard blocks can be used effectively to construct some very powerful
composite function blocks.
In the long term, new types of function block will undoubtedly emerge and
become commonplace as the technique of building systems from function blocks
gains wider acceptance.
Chapter 10

Programming example

We have now covered all the features of the IEC 1131-3 standard. In this chapter,
we will look more closely at the application of IEC 1131-3 to industrial control
problems. In particular, the chapter will focus on the following aspects of
designing IEC 1131-3 based systems:

• The definition of external interfaces;


• The analysis and breakdown of the control problem into more manageable
components, that can be defined as programs and function blocks;
• The partitioning of the control software to run in different PLC resources;
• Selecting the most appropriate programming language;
• Defining the total configuration.

10.1 Steam turbine control example

The example application that we will review in some detail concerns the control
of a boiler water feed pump. A water feed pump is used to maintain the water
level in the steam drum of a large boiler, as might be found in an oil- or coal-fired
power station. The water level in the main boiler must be controlled within safe
operating limits.
The level can fluctuate as the steam from the main boiler is used by the power
generation turbine or by other services. If the level drops, there is a danger that the
boiler riser tubes that absorb heat from the burners will overheat and distort. If the
level goes too high, there is a danger that water droplets will pass into the
superheated steam supply and damage the main generator turbine blades.
The boiler water feed pump which is driven by a small steam turbine off the
main steam supply, pumps de-aerated water (typically re-cycled from condensed
steam), under high pressure into the steam drum to maintain the water level.
248 Programming industrial control systems using 1EC1131-3
In this example application, we will consider some of the control aspects of the
feed pump steam turbine and the interactions of its control system with the rest of
the plant.

Steam Drum

Superheated
Steam

Boiler House

Boiler Water Feed


Pump
Burners

Figure 10.1 Boiler water feed system

Boiler Feed Water

Steam Exhaust Valve


Discharge Valve
Dx>—>-
Feed Pump Steam Turbine

Shaft Oil Pump Bearing GovenOr

Barring Motor

Suction Valve

" Auxiliary Oil Pump J Emergency Stop Valve

Oil Tank Steam Inlet Valve

Figure 10.2 Boiler water feed pump


Chapter 10 Programming example 249
Figure 10.1 depicts the main features of the boiler feed pump. A steam turbine
is connected on the same shaft as the feed pump and provides the motive power. It
also drives a shaft oil pump that supplies oil for the pump bearings and to power a
hydraulic speed governor.
The operator can initiate the pump start-up from the central control room and
specify the time for the pump to ramp up to full speed and the initial operating
speed. The turbine is ramped up to speed by opening the steam inlet and exhaust
valves. To allow the turbine rotor and casing temperatures to stabilise, the turbine
is first brought up to an intermediate speed and held at that speed until the casing
temperature matches the steam inlet temperature. The steam supply is then
increased slowly by opening the steam inlet valve, until the turbine reaches the
operating speed.
When the pump is at operating speed, about 3000 rpm, the suction and
discharge valves are opened to allow the feed water to be delivered to the steam
drum. At this point, the control system switches over to 'modulating control'. A
special algorithm is used to regulate the turbine speed according to certain critical
process values; these include the drum water level, the feed water supply rate and
feed water valve positions. The requested speed signal produced by the
modulating control algorithm is used to trim the turbine speed via a hydraulic
speed governor.
To cease pumping, which can be triggered by an operator or an emergency shut-
down condition, the steam supply is stopped by closing first the steam inlet and
then the exhaust valves. As the turbine slows and stops rotating, an electrical
barring motor is brought into operation to keep the turbine turning at a slow speed.
This ensures that the shaft does not distort as it cools.
An auxiliary electrical oil pump can be brought into operation to maintain oil
pressure in the bearings. This can occur whenever the speed of the turbine is too
low for the shaft oil pump to be effective, or when the bearing oil pressure is
critically low.

10.2 Design approach

The design of the control system for the water feed pump can be considered in the
following phases:
1. Identification of the external interfaces to the control system, i.e. definition of
all the inputs from the main sensors and outputs to actuators, such as to
valves and switchgear.
250 Programming industrial control systems using IEC1131-3
2. Definition of the main signals exchanged between the control system and the
rest of the plant.
3. Definition of all operator interactions, overrides and supervisory data.
4. Analysis of the control problem broken down from the top level into the main
control areas; these will then become IEC program organisation units, i.e.
IEC programs and function blocks.
5. Definition of any low level function blocks required.
6. Definition of the scan cycle time requirements for the different programs and
function blocks.
7. Detailed design of the program and function blocks.

Figure 10.3 shows the main interfaces between the control system and the plant.
The primary function is to regulate the speed of the water feed pump to maintain
the steam drum water level. However, the complete control system will need to
monitor over a hundred input signals that define the state of the plant, including
valve position sensors, temperatures, oil pressures etc. There are also numerous
outputs for setting steam valves, and controlling auxiliary electrical equipment.

Steam Drum

, WaterLevel Water Feed Pump


Boiler Water Feed Pump
Control System PumpSpeed

Water Flow Rate Pump Mode ^ -


Pump Fault
Plant Supervision I
Signals |
I Actuators for valves,
I Auxiliary Oil pump etc.

Variables accessable by
Serial Communications the local area network for
link for Operator Start-up supervision and control

Figure 10.3 Boiler water feed control system


Chapter 10 Programming example 251

Defining specific data types

In every project it is likely that specific data types are required to represent data in
a form that is compatible with the local problem domain. Type definitions should
be defined so that they are applicable across the whole project.

Examples:

(* Type definition for pump mode *)


TYPE PumpMode : (
NotAvailable, (* Pump not available
for operation *)
Stopped, (* Pump stopped *)
Barring, (* Pump rotating at barring speed*)
Ramping, (* Speed being ramped *)
Running (* At operating speed *)
)
END_TYPE
(* Speed Ramp definition *)
TYPE RampSpec
Target : REAL; (* Target speed for ramp *)
Duration : TIME;(* Ramp duration *)
ENDJTYPE

Definition of plant inputs and outputs

All signals from input sensors concerned with the pump operation, including valve
positions, oil pressure sensors, switchgear and temperatures should be defined.
Similarly, definitions are required for all the main output signals needed to drive
actuators, such as for valve controllers and for operating switchgear, e.g. when
powering-up the auxiliary oil pump. Although the main I/O signals will be
identified at the start of the design, additional signals may need to be added as the
control requirements become clearer.
It is good policy to define a naming convention so that the source and purpose
of each signal are clear from the signal name. Each signal should be defined with a
data type and should be clearly identified as being a system input or output. In a
large project it is likely that a database will be used to hold and access all I/O
signal information.
The manner by which signal values are read into or sent out to external devices
will vary from PLC to PLC. In this example we have assumed that the PLC
hardware is configured so that I/O values are available at pre-defined memory
locations.
252 Programming industrial control systems using IEC1131-3
Example:
(* System Inputs *)
PlJLocal AT %IX10 : BOOL; (* Local Control *)
Pl_PumpSpeed AT %ID50 : REAL;(*Pump revolutions *)
Pl__FlowRate AT %ID51 : REAL; (* Water flow rate *)
Pl_DrumLevel AT %ID52 : REAL;(* Steam drum level*)
Pl___CasingTemp AT %ID53 : REAL;(*Casing Temp *)

(* System Outputs *)
Pl_SteamIV AT %QD80 : REAL;(*Inlet Valve Pos.*)
Pl_SteamEV AT %QX81 : BOOL;(*Exhaust Valve *)
Pl_SuctionV AT %QX10 : BOOL;(*Suction Valve *)
Pl_DischgV AT %QX11 : BOOL;(*Discharge Valve*)

The prefix T l _ ' indicates that a signal is associated with pump 1. This is for
possible future expansion - a second pump could be controlled using signals
prefixed T 2 _ \

Definition of external interfaces

Although this example focuses specifically on the control of the water feed pump,
we must not forget that the definition of interfaces with the rest of the plant and
other control systems is an important part of the system design. It is likely that the
pump control system will have both direct hard-wired signals from other systems
and one or more communications interfaces.
The signals and interactions on all of these interfaces need to be defined.
Variables that are permitted to be accessed via a plant local area network can be
declared using the VAR_ACCESS construct, as discussed in Chapter 2, Section 2.

Example:
(* Direct Main Control Inputs *)
Pl_StartPermit AT %IX200 :
BOOL; (* Main Start-up enable *)
Pl_PumpTrip AT %1X201 :
BOOL; (* Emergency Pump Trip *)

(* Main Control Outputs *)


Pl_PumpMode AT %QW400 :
PumpMode; (* Pump operation mode *)
Pl_PumpFault AT %QX401 :
BOOL; (* Pump operating fault*)
Chapter 10 Programming example 253
(* ACCESS paths for comms network *)

(* Path name to Boiler Feed Pump 1, Speed *)


A__BFPlSpeed : Pl_PumpSpeed : REAL READ_ONLY;

(* Path name to the Boiler Feed Pump 1, Mode *)


A_BFPlMode : Pl_PumpMode : PumpMode READ_ONLY;

Definition of operator interactions

Interactions with human operators via direct wired switches and indicators can be
treated as normal input and output signals.
However, interactions via a communications interface may require the use of
special communications function blocks. For example, if a proprietary serial
communications interface is being used, it may be necessary to develop a low
level function block, say written in ' C \ Handling of serial communications is not
covered by TEC 1131-3.
For this example, we have assumed that a low level function block
'Operator_Data_Request' has been developed. This provides an interface with a
remote operator panel or display station. It sends a message to the operator and
then signals when a response has been returned. The block has two flags,
'Message Ready' and 'DataJValid', which act as semaphores to signal when the
operator message can be updated and when the date entered by the operator is
valid.

Operator_Data_Request

STRING Operator_Message Data REAL

BOOL Message_Ready Messagejteady BOOL

BOOL Data.Valid Data_Valid BOOL

This block is used within the turbine run-up sequence to request the ramp-up
speed and time.

Note: Message_Ready and DataJValid are examples of VAR_IN_OUT variables,


i.e. they provide inputs and outputs. The use of VAR_IN_OUT variables is
described in Chapter 3, Section 11.
254 Programming industrial control systems using IEC1131-3

10.3 Control problem decomposition

In this water feed pump CONFIGURATION BFP1_Control


example, the principal
control functions can be - ttih &J A
; : ,-• " ModuJatingControi

split between (a) the TASK TASK


sequencing and auxiliary MainTask ModCntTask
SuperTask
control, and (b) the TASK
PROGRAM AnalScanTask
modulating control. MainControll
We have assumed that / l ' ;•' , '

the PLC provides two GLOBAL and local


PROGRAM
ModControll
processing resources. The variables for
this resource ' ' ' ' ..
Main resource will run GLOBAL and local
variables for
the main control this resource
sequence for the turbine
start-up and control all
GLOBAL
the auxiliary functions. Variables for complete configuration

The second resource,


ModulatingControl, is ACCESS paths
Variables accessible to plant local area network
concerned with scanning
analogue input signals
and running the
modulating control
algorithm.
The control software within both resources is encapsulated in program blocks, i.e.
MainControll and ModControll. The entire control software is contained in a
Configuration BFPl_Control.
Global variables used by software within both resources are defined at the
configuration level. These are global variables that either represent inputs and
outputs to the system, which are required in both resources, or are globals used to
exchange information between the two resources. For example, the
ModulatingControl is activated when the pump is revolving at its operating speed.
This can be signalled by the MainControll program setting a boolean global
variable Pl_Auto.
Global variables that are only required within a particular resource are declared
at the resource level. For example, the constant MaxPumpSpeed is only relevant
to the MainControll program and therefore is defined as a global variable within
Chapter 10 Programming example 255
the Main resource. Defining the global variables in the resource where they are
used can help to simplify the overall design.
Because there is unrestricted access to globals from all lower level software, the
number of global variables should be minimised where possible. In this example,
all key variables are passed into or out of the programs via formal input and output
variables. Although this produces well-structured software, it does result in the
main programs having a large number of input/output variables.
Access paths are declared to provide external paths to selected variables. In this
case, communications access is restricted to a few principal variables, such as
pump speed and operating mode. Additional 'read' access paths to other variables
could also be provided for supervisory purposes, such as alarm monitoring. Direct
write access to the internal control variables is not provided because of the danger
of accidentally disrupting the integrity of the control system.
It is assumed that diagnostic facilities, outside the scope of IEC 1131-3, are
available during system commissioning to establish various tuning constants.
Each resource contains one or more task definitions. The task, MainTask, runs
the main program block and most of the function blocks within the MainControl
resource. A second task, Supertask, is concerned with running a pump supervisory
function block. As this block is concerned with monitoring slowly changing inputs
such as temperature and vibration levels, it runs at a slower rate.
There is one task in the ModulatingControl resource, ModCntTask, that is
responsible for running the modulating control function blocks and function
blocks for the signal conditioning of analogue inputs.
Part of the textual definition of this configuration follows. (The characters ...
indicate that additional statements have been suppressed for clarity.)

CONFIGURATION BFPl_Control
(* Globals at config. level *)
VAR__GLOBAL
(* System Inputs *)
Pl_Local AT %IX10 : BOOL; (* Local Control *)
Pl_PumpSpeed AT %ID50 : REAL;(* Pump revs/min *)
Pl_FlowRate AT %ID51 : REAL;, (* Water flow rate*)
(* Direct Main Control Inputs *)
Pl_StartPermit AT %IX200 :
BOOL; (* Main Start-up enable *)
Pl_PumpTrip AT %1X201 :
BOOL; (* Emergency Pump Trip *)
Pl_StartUp AT %IX202 :
BOOL; (* Start Pump run-up *)
256 Programming industrial control systems using IEC1131-3
(* System Outputs *)
Pl__SteamIV AT %QD80 : REAL; (*Inlet Valve Pos.*)
(*• Main Control Outputs *)
Pl_PumpMode AT %QW400 :
PumpMode; (* Pump operation mode *)
Pl__PumpFault AT %QW401 :
BOOL; (* Pump operating fault*)

(* Configuration level, shared globals *)


Pl__Auto : BOOL; (* Modulating Control Auto *)
END_VAR

RESOURCE MainControl
VAR_GLOBAL CONSTANT
(* Define all the global constants *)
Seq_Scan_Period : TIME := T#100ms;
MaxPumpSpeed : REAL := 4000;
END_VAR
VAR
(* Resource level variables *)
(* System Inputs *)
Pl_AOP_Press AT %ID533 : REAL; (* Aux oil
pump pressure *)

(* System Outputs *)
Pl_SteamEV AT %QX81 : BOOL; (*Exhaust Valve *)
Pl_SuctionV AT %QX1O : BOOL;(*Suction Valve *)
PlJDischgV AT %QX11 : BOOL;(^Discharge Valve*)

END_VAR
(* Task definitions *)
TASK MainTask (INTERVAL := Seq_Scan_Period,
PRIORITY := 5 ) ;
TASK SuperTask (INTERVAL := T#500ms,
PRIORITY := 10) ;
(* Call the MainControll Program *)
PROGRAM MainControll WITH MainTask :
MainControl(
(* List of input variable connections *)
Startup := Pl_StartUp, (* Pump run-up *)
Local := Pl_Local, (* Local control mode*)
PumpSpeed := Pl_PumpSpeed,
FlowRate := PlJFlowRate,
PumpTrip := Pl_PumpTrip,

(* List output variable connections *)


Auto => Pl_Auto,
PumpMode => Pl_PumpMode,
PumpFault => Pl_PumpFault,
SteamlV => Pl__SteamIV, (*Inlet valve *)
Chapter 10 Programming example 257
SteamEV => Pl_SteamEV, (*Exhaust valve*)
SuctionV => Pl_SuctionV, (*Suction valve*)
PlJDischgV => Pl_DischgV, (*Discharge valve*)

(*Assign supervision fun. blk to superTask *)


PumpSupervision With SuperTask;

END_RESOURCE
RESOURCE ModulatingControl

END_RESOURCE
VAR__ACCESS
(* V a r i a b l e s a c c e s s i b l e v i a cornms network *)
A_BFPlSpeed : Pl_J?umpSpeed : REAL READ_ONLY;
A_JBFPlMode : Pl_PumpMode : PumpMode READ__ONLY;
A__BFPlSuction :
MainControl.Pl_SuctionV : BOOL READ_ONLY;

END_VAR
END CONFIGURATION

Note: The configuration of a large system may run into many hundreds of lines.
However with many IEC implementations, this can be automatically
produced by the programming station.

10.4 Program decomposition

We will now look more closely at one of the program blocks for this system. Note
that MainControll is a program instance of type MainControl. This allows for
future system expansion; a second pump could be controlled by simply creating a
second program instance, i.e. MainControl2, and linking it to a set of inputs and
outputs associated with the second pump.
The program type MainControl consists of a number of function block
instances, as depicted in Figure 10.4.
Each function block in Figure 10.4 is concerned with controlling a specific part
of the boiler water feed pump. Where possible, all logic concerning the behaviour
of a particular part of the plant is contained within a specific function block.
The behaviour of each top level function block within the MainControl program
is summarised as follows:
258 Programming industrial control systems using IEC1131-3

TurbineSequence function block

This block contains the main turbine run-up sequence. In response to the Startup
signal, this block sequences through the various steps to bring the pump up to
operating speed. This includes requesting the ramp-up time and target speed from
the operator, opening the steam inlet and exhaust valves, holding the ramp at an
intermediate speed until the turbine casing temperature has settled, and setting the
Auto signal when the pump reaches operating speed. The Auto signal allows the
modulating control program to take over the speed control of the turbine.

Startup TurbineSequence
• Auto
Local
- SteamEV
PumpSpeed
- Steam IV
FlowRate

PumpSupervision
PumpFault

CasingTemp 0M3rTemp
Vibration

SuctionDischarge
- SuctionV
SuctionVPosition
DischgV
DischargeVPosition

AuxOilPump Demand_AOP
OilPress
AuxPumpSG

BarringMotor
DemancLBAR
BarMotorSG

Figure 10A Decomposition of the MainControl program

Note: The Function Block Diagram language is ideal for depicting the top
level program structure. In this figure, only the primary signals are shown
to illustrate the main program structure. Function block input and output
names are also not shown to avoid cluttering the diagram. In the full
system, each function block may have up to thirty to forty inputs and
outputs.
Chapter 10 Programming example 259

PumpSupervision function block

This block is concerned with checking that the turbine and pump are functioning
within normal operating limits. It runs continually and checks that the bearing
temperatures, vibration levels and casing temperatures are acceptable. Any
discrepancy results in raising the PumpFault output. This is checked by the
TurbineSequence, and can halt the turbine speed ramp-up.

SuctionDischarge function block

When the pump speed is near to its operating speed, the water feed suction and
discharge valves can be opened. This block ensures that these valves are only
opened when the correct conditions exist. It also checks the valve position sensors
to ensure that the valves have moved to the requested positions.

AuxOHPump

Maintaining a good oil pressure in the bearings is critical to the health of the pump
and turbine. This block continually checks that the oil pressure is always above a
critical minimum value. If the pressure falls below a critical level for more than a
few seconds, the auxiliary electrical oil pump is immediately powered-up. The
block also checks the motor switchgear to ensure that it has operated as requested
and that the auxiliary pump, when operating, delivers oil at the expected pressure.

BarringMotor function block

When the pump is taken out of operation, the turbine is allowed to slow down
until it stops. At this point a barring motor is engaged to keep the turbine shaft
rotating at a slow speed. This function block ensures that the barring motor is
engaged and powered-up when requested by a signal from the TurbineSequence
function block. The block also ensures that the power to the barring motor is
removed when the turbine speed is increased as part of the normal speed ramp-up.

TurbineSequence function block


The TurbineSequence function block is primarily concerned with sequencing
through the main steps needed to bring the turbine up to its operating speed. Its
behaviour can best be described using a Sequential Function Chart. A part of the
turbine start-up sequence is depicted in Figure 10.5.
260 Programming industrial control systems using IEC1131-3

StandBy

- Startup
< Restart <
Checks N A1_Pump_lnterlocks ()hecksOK

— ChecksOK
SetupRamp N A2_RampTime TimeRdy

— TimeRdy

StartRamp 1— N A3_RampSpeed RampRdy

— RampRdy -NOTC

RalseSpeed A4 Ramping ChksFault - A10_ChksFault


S
1
P A5_OpenValves

— PumpSpeed > HoldSpeed

HoldSpeed |- S A6_CheckTemp TempOK

R A4_Ramping

—TempOK

Ramp - S A4_Ramping RampEnd

t RampEnd

Figure10.5 Turbine sequence SFC

The actions requested by the SFC can be described in any of the IEC languages.
For example, the following Ladder Diagram given in Figure 10.6 describes the
logic for the A3_RampSpeed action block. This uses an instance of the
Operator_Data_Request function block to prompt the operator to supply the target
speed for the turbine run-up. The rising edge of the StartRamp.X signal, that
becomes true when the StartRamp step is active, is used to set the message ready
signal, Msg_Rdy. This triggers the Operator_Data_Request function block to send
the prompt 'Ramp Speed* to the operator.
When the speed value has been received, the function block sets the ramp ready
signal, RampRdy, an indicator variable that is tested in the transition that follows
the step.
Chapter 10 Programming example 261
Msg_Rdy

Operator_Req1
EN Operator_Data_Request

"Ramp Speed" Operator_Message Data RampSpeed


Msg_Rdy Message_Ready Message.Ready
SpeedRdy Data_Valid Data_Valid RampRdy

Figure 10.6 Action block A3 JRampSpeed

As a further example, the following Structured Text statements describe the


A5_OpenValves action block.

ACTION A5_0penValves
StEmergStopCtl(Position := OPEN,Time := T#15s)
StExhaustCtl(Position := OPEN,Time := T#15s)
END_ACTION

This action block calls two function blocks, StEmergStopCtl and StExhaustCtl.
These open the steam emergency stop valve and exhaust valves ready for the
turbine speed run-up. They are both instances of the valve controller function
block, ValveControl, described in a later section.

PumpSupervision function block


This block continually checks that pump and turbine temperatures and vibration
measurements are within operating limits. In Figure 10.7 we have shown part of
this block described using Function Block Diagram language, but Ladder Diagram
or Structured Text would have been equally applicable.
As the block is concerned with monitoring relatively slowly changing inputs, it
can be scanned at a lower rate than the other blocks in the MainControl program.
In the configuration definition, the PumpSupervision function block is associated
with the task called SuperTask, which scans every 500 milliseconds.
Part of the logic for the PumpSupervision function block is depicted in Figure
10.7. The high vibration signals are 'ORed' and passed into an on-delay timer.
This ensures that the signals are steady for 5 seconds before the over vibration and
pump fault signals are raised.
262 Programming industrial control systems using IEC1131-3
Vibrationi Timeri
> —i

VibMax -r-
1_ OR TON
CTKI
EN
f\
Q

t
Vibration2 -L > j —

1
PT

OR — PumpFault
T#5s

'
Tempi —• >

TempMax —r- OR

Temp2
> J~
Figure 10.7PumpSupervision function block

10.5 Low level function blocks

So far we have mainly concentrated on the top-down decomposition of the system


design into smaller software elements, i.e. into resources, programs and function
blocks. However, it is equally important to look for standard software solutions to
similar problems that occur in many places throughout the design.
In this example, there are numerous valves to be controlled. Apart from the
steam inlet valve which is opened proportionally, the rest of the valves can be
controlled using instances of the same valve controller function block.
When the signal from the control system drives a valve actuator to open or close
a valve, there is a requirement to check that the valve takes up the required
position within a prescribed time. Each valve is fitted with limit switches which
indicate when the valve is either fully opened or closed.
The ValveControl function block provides all the logic required to move the
valve into the required position, check that the valve is in position and, if not,
raise a fault signal indicating that the demanded valve movement has not been
detected.
Figure 10.8 shows how the ValveControl function block is linked with the valve
actuator. Limit switches on the valve gear feed back the detected valve position.
Note: The logic for this block is very similar to the air damper function block
described in Chapter 5, Section 9.

Many other function blocks could be considered for this system, such as a
switchgear control block for starting electrical equipment, e.g. auxiliary oil pump
and barring motor. With forethought, such blocks can be designed so that they are
applicable in other systems.
Chapter 10 Programming example 263
Steam Exhaust Valve Actuator
StExhaustCtl

ValveControl
StExhaust Position Demand

Opened
State StExhaustState Valve travel limit sensors
Closed Fault StExhaustFault
StExhaustTest Test
T#30s Time

Figurel0.8 ValveControl function block

10.6 Signal flow

Because IEC based software can be deeply nested, signal values tnay need to flow
through a number of layers from source to destination. As a result, the value of a
particular signal may appear at different levels under different names.
Consider the demand signal for the steam exhaust valve that originates from an
instance of the ValveControl function block called StExhaustCtl. This function
block exists within the TurbineSequence function block and directly drives the
TurbineSequence output SteamEV from its output Demand. In turn,
TurbineSequence is an instance within the program MainControll. The output
SteamEV of TurbineSequence directly drives the program output SteamEV.
Finally, the value of the program output SteamEV is written to a resource level
variable, Pl_SteamEV.

MainControll PROGRAM Resource Level


Variables
TurbineSequence
StExhaustCtl
SteamEV.
at%QX81

Figure 10.9 Signal flow example


264 Programming industrial control systems using IEC1131-3
The signal flow from function block output StExhaustCtl.Demand through to
the resource level variable Pl_SteamEV is shown in Figure 10.9.
Similar signal flows exist from input signals through to inputs of internal
function blocks.
Although many software layers may exist in a large system, the layers should
not normally result in any decrease in system performance. With good compiler
design, the transfer of signal values across software block interfaces should not
add any significant processing overheads.
Note: Particular care is required when debugging IEC programs. The context and
scope of each variable is always required. For example, the variable
SteamEV, as an output of TurbineSequence, should not be confused with
the output SteamEV of program MainControll.

Summary
In this chapter we have reviewed:
• How an industrial control system problem can be broken down into smaller
more focused areas.
• How the design can be constructed to run on different PLC processing
resources.
• The use of programs and function blocks to construct a hierarchical top-down
design.
• The development of re-usable function blocks that can be applied to solve the
same problem many times within the same system.
• How different languages can be used to describe function blocks and action
blocks.
Chapter 11

Programming station facilities

Producing a programming station that provides all the software management, the
graphical and textual editors, the build system and run-time diagnostics required
for programming EEC 1131-3 based PLCs is a major software development
undertaking.
In this chapter we will review the many aspects of an IEC 1131-3 programming
station, particularly:

• Requirements for an intuitive user interface;


• Support for hierarchical design decomposition;
• Library management for re-usable software elements;
• Built-in program consistency checks;
• Provisions for selecting different programming languages;
• On-line diagnostics.

11.1 DEC programming station features overview

Any programming system for control applications based on IEC 1131-3 requires a
wide range of features to ensure that programs can be readily developed and
maintained by control engineers using a 'user friendly' and robust development
environment.
We have seen that IEC 1131-3 style control programs are developed using a
top-down design approach where programs generally consist of a hierarchy of
graphical diagrams and textual definitions. A programming system should
therefore offer facilities that encourage engineers to exploit the benefits of well
structured top-down program design.
The main function of a programming system is to provide control engineers and
system programmers with facilities to translate their program concepts into a
structured and validated set of program diagrams and definitions for which run-
time, executable programs can be rapidly created.
266 Programming industrial control systems using IEC1131-3
Apart from an understanding of the control system languages, engineers using
such a programming system should not require any particular or specialist
computer skills. Full use should be made of windows style graphical user interface
and mouse selection techniques.
The control of all programming facilities should be intuitive through use of well
annotated command buttons, menu options or intelligible command icons.
Information on using most facilities should be available on-line through help
screens or menu descriptions. Where possible a programming system should offer
facilities to validate graphical and textual languages.
Automatic checks should be built into the system to validate such things as: that
consistent and correct data types are being used, that graphical diagrams are
complete and sound, and that textual languages have the correct syntax.

Support for hierarchical design


Where programs are hierarchical, the programming system should provide
facilities so that it is possible to 'push-down' on elements in a diagram to view
lower level diagrams and program elements.
For example, when viewing a Function Block Diagram, it should be possible to
examine the definition behind any element shown on the diagram. This may
involve displaying another function block diagram at a lower level in the system
hierarchy that depicts the behaviour of a selected function block. If appropriate,
the user should be able to close any diagram and return automatically to the parent
diagram at a higher level.
Generally, medium to large projects will be developed by a team of engineers. It
should therefore be possible to organise and manage all files that constitute a
control system as a 'project'.

Multiple users
Facilities are required to allow multiple users to work on a single project
simultaneously from different development platforms and then to be able to merge
their different program elements into the final system.

Re-use of standard solutions


Through its design, the programming system should promote the re-use of
software elements such as IEC programs, function blocks and functions. There
should be facilities for creating, storing and retrieving standard elements and for
managing software libraries of standard elements.
Chapter 11 Programming station facilities 267
Over the course of several projects, it is probable that a range of common
software solutions will emerge. The ability to turn such solutions rapidly into new
standard elements such as functions and function blocks is clearly important in
improving software quality and shortening system development times.

Function Block Libraries Programming Station

Configuration Files

Figure 11A IEC1131-3 programming station

Building the downloadable software executable

When a complete control program has been developed, the programming system
should assist in the creation of the run-time executable. Where possible, the
system should provide facilities to allow the executable program to be down-
loaded into the control system hardware e.g. into non-volatile memory or
EEROM.
The status and identity of any down-loaded control program should always be
accessible.

Run-time diagnostics
After a control program has been down-loaded, the system should provide on-line
diagnostic facilities. It should be possible to display the values of run-time
variables, such as the values on function block inputs and outputs. Ideally the
values of run-time variables should be displayed in the context of the diagrams
used to define the control program.
268 Programming industrial control systems using IEC1131-3
To support commissioning, full read and write access should be given to run-
time variables for system tuning, for making final adjustments to configuration
parameters and for calibration of critical sensor measurements.
Access protection facilities should be provided to ensure that all program
changes either off or on-line are controlled and authorised using some form of
security key, such as a password.

System documentation
Comprehensive documentation of a control software design is important for
software validation and maintenance purposes. The programming system should
have facilities to print-out all graphical diagrams and text that go together to form
a control program.
All print-outs should be organised as a single document with appropriate cross-
reference lists to enable the location and use of different software elements to be
found rapidly.

11.2 Programming station — feature summary

The following list summarises the main features of a programming system for
developing control systems based on IEC 1131-3:

• User interface — Ideally a graphical user interface (GUI) should be provided


which makes full use of window/icon/mouse techniques with access to all
facilities via menus, command buttons or icons.

• Multiple views — Programming productivity can be enhanced with facilities


that support multiple views of the software (e.g. using windows). It should be
possible to view different parts of the software simultaneously so that different
parts of a control program can be examined and compared.
Facilities that allow selected parts of textual and graphical programs to be cut
and pasted between views will also help general software productivity. In addition
graphical editors should provide zoom and pan facilities so that diagrams may be
larger than the physical window size on the computer screen.
Chapter 11 Programming station facilities 269
• Intelligent graphical editors — Graphical editors allow diagrams to be
developed in a user-friendly and intuitive manner. For example, graphical lines
that define connections between graphical objects should be retained when objects
are moved, e.g. when a function block is moved, the lines that connect the block
with other blocks should stay attached. This technique is known as rubber-
banding.

• On-line help facilities — A comprehensive built-in help system should be


provided describing all the main facilities including the IEC programming
languages, the standard functions and function blocks.

• Different languages — It should be possible to select any of the various IEC


graphical and textual programming languages for developing different parts of an
application for handling control aspects such as: (a) continuous control, (b)
interlock logic, (c) alarms, (d) sequencing, (e) interfaces to SCADA and external
devices.

• Data base import/export facilities — For large projects, a programming


station should provide facilities to allow design information to be imported, for
example directly from plant diagrams and instrumentation schedules.
As a minimum requirement, there should at least be an import facility for signal
names and I/O descriptions from textual files, databases or other packages such as
spreadsheets.
Similarly, there should be some means to export design information, such as I/O
signal names, physical hardware I/O addresses etc. to other databases or to other
packages.

• Hierarchical design — To support an essential feature of the EEC 1131-3


design philosophy, the programming station should allow the user to break a
control system design down hierarchically into smaller more manageable parts, for
example into programs and function blocks.
When using the programming station to examine an existing application, the
design decomposition and structure should be easy to understand and explore.
270 Programming industrial control systems using IEC1131-3

Program Lln«1
f t l . Edit Option* Build Protect H»h>
t H°\p V12
Program Line 1

Line Program Line


LX_L1 -Status_L1 Function Block
LX status
Test_L1 1Test Output -Output1_Li

j Local Speed
MAX!

XI

Figure 11.2 Windows showing design decomposition

• Navigation facilities — With designs that can be broken down into so many
different diagrams and layers, it is important that facilities are provided to enable
elements that may be on different diagrams to be found rapidly. This is
particularly important when elements, such as function blocks, can be used at
different levels in the design hierarchy.
It is also necessary to be able to trace signals from diagram to diagram, for
example from a system input, through into the top level program, on into the
program level function blocks and so on into the deeper levels of the design.

• Program validation — During program development, built-in facilities should


be available to validate program elements. Checks should include data type
consistency, language syntax and correct diagram composition.
There should also be inter-diagram checks to ensure that inputs and outputs
connecting hierarchical diagrams exist and are used correctly, for example that all
function block inputs and outputs shown in a top level diagram exist in the
associated function block type definition.
Chapter 11 Programming station facilities 271
• Library management — Facilities should be provided for packaging standard
software solutions as re-usable elements such as functions and function blocks.
Standard elements should be stored in software libraries which are readily
accessible. It should be possible to identify and retrieve different revisions of
standard software elements as and when necessary.

• Project management — With large projects, a programming station should


clearly be able to support simultaneous control software development on multiple
platforms. This may require support for operation of several programming systems
via a network.
Facilities are also needed to allow control programs to be built by merging
source files that have been developed on multiple platforms and to manage sets of
program source files as a 'project'. For example, all files associated with a given
project should be saved and retrieved as a set of files.

• Project configuration management — It is particularly important that


facilities are provided to identify the revisions of files as required for a given
control program build. Ideally, all the build files should be generated
automatically.

• Documentation — All information for all sections of a control program, which


may be written in different languages, should be available in hard-copy form.
All hard-copy should be organised to form a single coherent document that
describes the complete control program.
Indexes and cross-references should be available to enable any software element
or I/O point to be found easily.

• Access protection — Security key protection to prevent program changes by


unauthorised personnel should be provided. It is particularly important that on-line
changes to a control system are security protected.

• System build — The system build process should re-check the consistency of
the complete control program. This includes ensuring that all inter-diagram signal
connections are consistent, e.g. that all connections have the correct data type and
that all function block inputs and outputs that are used in diagrams are actually
defined for the associated function block types.
272 Programming industrial control systems using IEC1131-3

PRG_FBD:FBD
LEVEL_StM:TLC

DRAIN 1.0RAIN
TEWP.SIKC.TLC

TLC_L*vetTLC
TLCLTawTLC
COH.TOCTJ-.DDN.'IEXr
COK STRU 1.-C0N 5TBU

PRGJ.O:t.D

Figure 11.3 Example programming system screens


a Function Block Diagram editor
b Ladder Diagram editor
Chapter 11 Programming station facilities 273

Global variables HQDUS OF


BQOT.PLC 2 0 0 0 j 1 : P0B0T_X;- R0B0T_X + 2 0 0 ;
fti '& WLSTH1 INIT.STR J.000 R0B0T_Z : - RQBOT_Z + ADPJUSB ;
$ 1 PLC_RUN'
I F ROBOT X >« ROBOT RAHOE POS 1 THEH
l + i i j ] INf STR2INIT STR
fi
2: R0B0T_X:» R0B0TJX - 200;
R0BOT~Z : » ROBOT_Z - ADD ABH ;
7-2;
I F ROBOT X O ROBOT PAMGE KEG 1 THEH
USER.DATA_OF_CONTAINE H0DU3-..1;
LEVEL.SIM TLC
DRAINJ DRAIN EHD_CA3E;
ROBOT Y:= ROBOT X
TLC.Level TLC
TLC Terr^TLC
CONTEXT J CX!N_TE>a
C0N_STRLL1 COH_STRU
PRG_LO.LD

PRGJLIL
PR6_SFC SFC

am
SFC/

L J Actiom
c! m DANCE_R
V1SURO_BQT
ROBOT
ROBOTV

Figure 11.3 c Example of using a Sequential Function Chart to position a robot


Screen shotsfromthe MULTIPROG programming system
Courtesy of Kloepper and Wiege Software GmbH

It is also important that PLC address ranges are correct and assigned
consistently, e.g. that direct PLC addresses, such as %I101, are not multiply
assigned, i.e. assigned to more than one variable.
During the control program build and down-load process, the programming
system should ensure that the executable program is configured correctly for the
target hardware. For example, the system should check that the built program is
consistent with the memory capacity of the target PLC and that the design scan
times for different program sections can be achieved.
When coming on-line to the control system, the programming system should be
able to identify any executable control programs that are already loaded into the
PLC. It should also be able to associate the loaded executable programs with their
original source files.
274 Programming industrial control systems using IEC1131-3
It is important that build information, including the identity and revision of all
standard elements such as functions and function blocks, which have been used to
create a particular software build, is readily available.

• On-line diagnostics — For commissioning industrial control systems it is


essential that the programming system provides support for on-line data
monitoring. Ideally there should also be options to view graphical programs as
they execute showing live signal values, such as at function block inputs and
outputs.
With Sequential Function Charts, the programming station should highlight all
active steps. If a program is not sequencing through steps as expected, it should be
quite clear from the highlighted steps which transitions are holding up the
sequence.

• On-iine software modification — For system tuning, final system


configuration and calibration, support for minor in-situ program modification is a
useful feature that can save significant time.
However, modifications should be restricted to safe and valid changes. The user
should take particular care when making direct changes to a loaded program. It is
unlikely that a programming station will be able to check on-line changes with the
same rigour as it can check programs built off-line.
All on-line modifications should be recorded for quality audit purposes. If
appropriate, the user should have the option to select thatchanges made to the on-
line program also update the associated source files. For example, if control loop
tuning parameters are changed via a diagnostic screen, the new values should
optionally become part of the control program configuration.

11.3 IEC compliant implementation

A PLC offering an IEC 1131-3 based programming station should come with a
comprehensive compliance statement. This should identify all the optional
features of the standard that have been implemented.
Within the standard there are a large number of optional language features.
Each feature is listed in a table and assigned a feature number.
For example, table 12 in the standard defines data type declaration features;
feature 5 is the ability to support structured variables. The PLC may provide or
exclude the feature.
Chapter 11 Programming station facilities 2 75
A product may either claim to be fully compliant or provide a list of compliance
tables in the following format.

Examples:

Table Number Feature Number Features description


18 6 Array initialisation
22 1 Functions for integer to
real type conversion

The standard states that it is not possible to claim a compliant feature if the feature
is implemented using any additional language construct that is not defined in the
standard. For example, it is not possible to claim that array initialisation is
supported by using another method, such as initialising arrays by directly
assigning bits to PLC memory.
The compliance statement should also list all the values of the implementation
dependent parameters. These are parameters defined by IEC 1131-3 that may vary
between products, generally because of limitations of the PLC hardware or
operating system: for example the maximum length of identifiers that can be used,
the maximum comment length, the maximum number of array subscripts.

Error detection

The standard defines over twenty different categories of software error condition.
These include errors such as:

— numerical result exceeds range for data type,


— invalid character position specified in a string function,
— return from a function without assigning a value.

Ideally, most of the errors in language syntax and usage should be detected by the
programming station while the software is being developed. Other errors will only
be found when the configuration is being built. Finally there are errors such as
'division by zero in an arithmetic expression', which can only be detected when
the software is executing.
The standard requires that the compliance statement includes a detailed
description on how each category of error is treated and where it is detected in the
software life-cycle.
276 Programming industrial control systems using IEC1131-3

Summary

In this chapter we have briefly reviewed the features of a programming station


suitable for developing software for EEC based PLCs. As the standard has only
recently been published, there are few PLC products on the market today that can
offer all the features discussed in this chapter.
As it has been estimated that it can take at least twenty-five man-years to
develop a full featured IEC based programming station it may be some time
before products start to appear in number.
More sophisticated systems will emerge in due course as the cost of computer
hardware continues to fall and the use of graphical programming techniques
becomes more widespread.
To summarise, the main features that we should come to expect include:
• An interface that is truly 'user friendly';
• Support for formally decomposing complex designs;
• A selection of programming languages;
• Support for re-use of standard solutions;
• Error avoidance and early error detection;
• Powerful, graphical run-time diagnostics.
Chapter 12

Communications

So far we have only considered part 3 of the IEC 1131 PLC standard. As we have
seen, IEC 1131-3 addresses all aspects related to programming PLC based control
systems. However, it does not address communications between PLCs.
This chapter reviews part 5 of the IEC 1131 standard, which focuses solely on
PLC communications. In this chapter we will review:

• The main scope of the IEC 1131-5 standard;


• The communications model;
• The PLC functional model;
• Accessing PLC status information;
• Communications function blocks;
• Mapping of communications function blocks on to MMS.

12.1 Background to IEC 1131 part 5

The only feature defined in the IEC 1131-3 standard that goes any way towards
providing inter-PLC communications is the VAR_ACCESS construct. This
simply defines access paths to named variables within the PLC application
software. IEC 1131-3 does not define how the communications facilities are
provided or controlled. The PLC communications model showing the use of the
VAR_ACCESS construct is discussed in Chapter 2, Section 2.
Part 5 of the IEC 1131-3 standard is concerned with facilities that can allow
PLCs that are connected via a communications network to exchange status and
control information and initiate executive commands, such as re-starting resources
and downloading configurations.

Note: It is the intention that this chapter provides an overview of the main
concepts defined in part 5 of the IEC 1131 standard that deals with PLC
communications. For full details see the 1995 edition of IEC 1131-5.
278 Programming industrial control systems using IEC1131-3
TEC 1131-5 is concerned with all the external communications aspects of a PLC.
There are two aspects to communications services; part 5 addresses:

1. server facilities — the behaviour of the PLC required to support and


respond to external service requests;
2. client facilities — the services that a PLC can request from other PLCs.

The standard is intended to be independent of the underlying communications


protocols. It therefore assumes that various communications layers, such as the
physical layer, data link layer and so on, as defined in the ISO seven layer model,
exist or that their equivalent behaviour is provided by the communications
subsystems.
EEC 1131-5 effectively exists above the applications layer of the International
Standardisation Organisation (ISO) reference model.
The ISO model consists of seven layers that provide the following facilities:

Physical layer: controls the low-level exchange of information bits including


transmission rates, and bit encoding over the transmission medium.

Link layer: responsible for the reliable Communications Layers


transmission of information units (packets or
blocks) and their dispatch to addressed stations on APPLICATION \\w\\\
the network.
PRESENTATION
Network layer: establishes virtual paths between
SESSION
stations in the network, e.g. transmitting a stream
TRANSPORT
of data packets from end to end via switching
nodes. NETWORK
LINK
Transport layer: responsible for transporting
messages between communications partners. It PHYSICAL
controls the data flow and ensures that the data are
not corrupted and arrive in the correct order. OSI reference model

Session layer: controls the exchange of messages in the transport connection, e.g.
establishing a communications session, controlling the re-start after interruption.

Presentation layer: decodes or re-encodes data to ensure that data can be


transferred between systems where data encoding is different.

Application layer: a set of protocols, i.e. message transactions to provide specific


facilities, e.g. file transfer, database queries etc.
Chapter 12 Communications 279
In many industrial networks, many of the ISO layers are either null or collapsed
to produce a smaller layered stack. This is generally necessary to improve the
communications response time and throughput.
The nature of these underlying communications layers is all hidden by facilities
defined within DEC 1131-5. This theoretically allows PLCs to communicate over
any type of network. Of course, this will depend on providing the appropriate
software to map the facilities required by IEC 1131-5 on to the communications
subsystem.
For example, IEC 1131-5 compliant PLCs may be able to communicate via
MAP1 based networks using the Manufacturing Message Specification (MMS)
applications layer, via Ethernet and TCP/IP or via a Fieldbus based protocol.
Communications facilities defined in IEC 1131-5 are developed from concepts
derived from the languages standard, IEC 1131-3; these are namely access paths
and communications function blocks.
Communications function blocks and associated data types are defined using
concepts and languages defined in IEC 1131-3.

12.2 Communications model

The main features of the top-level communications model defined by the IEC
1131-5 standard are depicted in Figure 12.1. A PLC may behave as a server, by
providing information and responding to service requests, or as a client, requesting
information and initiating service requests. Other devices, such as a supervisory
system or other non-EC 1131-3 compliant devices, may also act as clients and
request information and services from a PLC server.
Communications protocols, such as Ethernet, will generally allow an indefinite
number of server and client PLCs to co-exist on the same network. Note that, in
some cases, a PLC may behave as a server to some PLCs and as a client to others.
The IEC 1131-5 standard only defines the communications facilities within
PLCs, e.g. PLCs A and B as shown in Figure 12.1. It does not cover the behaviour
within external client devices.

MAP, an industrial communications standard initiated by General Motors, is discussed in Chapter 1, Section 3.
280 Programming industrial control systems using IEC1131-3

Supervisory System

Client

Communications Network
i
Client Client Server

Communicating Programmable Programmable


Device Logic Controller A Logic Controller B

Machine or Plant Machine or Plant

Figure 12.1 IEC 1131-5 communications model

The IEC 1131-5 standard states that each PLC may optionally provide
communications facilities to support the following application-specific functions:

• Device verification
• Data acquisition
• Control
• Program execution and I/O control
• Application program transfer
• Synchronisation between user applications
• Alarm reporting
• Connection management

12.3 PLC functional model

Figure 12.2 depicts the main functional aspects of a PLC. The executable program
defined using the IEC 1131-3 languages requires the support of a number of
subsystems. Remote PLCs, devices and supervisory systems all require
communications services to monitor their health and status and, in some cases,
control each of these functional subsystems.
For example, a supervisory system may require access to the program
diagnostics for analysing a program fault. A remote PLC may need to monitor the
Chapter 12 Communications 281

Other systems

Communications Man-Machine
Interface Facilities
External Functions Operator
Power
supply Programming
Diagnostics
Facilities Application
programmer
Signal Processing
Functions Operating System
Application Application Program
Program Storage/Memory
Execution
Data
Functions Storage/Memory

Interface Functions
Sensors and Actuators

Machine /Plant
/Process
Figure 12.2 PLC functional model

health of the PLC hardware, e.g. to check that the I/O scanning, memory and
power supplies are fully operational.

12.4 PLC status information

The IEC 1131-5 standard states that status information is provided for each of the
main subsystems as listed in Table 12.1.

Table 12.1 PLC Subsystems

No. Subsystem
1 PLC, complete system
2 I/O subsystem
3 Processing unit
4 Power supply subsystem
5 Memory subsystem
6 Communications interface
7 Implementation specific subsystems
282 Programming industrial control systems using IEC 1131-3
For each subsystem, the status information will be presented as a data structure
having a standard format and defined using IEC 1131-3 data types. For example,
the status information for the complete PLC includes the items listed in Table
12.2.

Table 12.2 Main PLC summary status

Item Description
1 Health Good All subsystems are fully
operational.
2 Warning At least one subsystem is in
the warning state; no
subsystem has the bad state.
3 Bad At least on subsystem has
the bad state.
T Running If true, at least one part of the application
software is running and controlling some
aspects of the PLC's behaviour.
Local control If true, the PLC is under some form of local
control, e.g. by the operator. This may limit
the network access or disable the PLC's
reception of remote executive commands.
No outputs disabled If true, indicates that the PLC has full control
over all outputs. If one or more outputs have
been forced to take particular values, e.g.
while debugging, then this item will be false.
No inputs disabled If true, this indicates that the PLC can access
the real values of all inputs. If this is not true,
it indicates that one or more input values
cannot be accessed, e.g. as may occur in the
early stages of commissioning.
I/O forced If true, indicates that either (a) one or more
inputs are being forced by the PLC's local
programming and diagnostic system to take
particular values or (b) the values of one or
more outputs have been overridden by the
local programming and diagnostic system.
Chapter 12 Communications 283

Item Description
9 I/O subsystem If true, it indicates that the 'WARNING' or
'BAD' state is associated with an I/O
subsystem.
10 Processing unit If true, this attribute indicates that
subsystem 'WARNING' or 'BAD' is caused by a
processing unit subsystem.
11 Power supply If true, this attribute indicates that
subsystem 'WARNING' or 'BAD' is caused by a power
supply subsystem.
12 Memory subsystem If true, this attribute indicates that
'WARNING' or 'BAD' is caused by a
memory subsystem.
13 Communications If true, this attribute indicates that
subsystem 'WARNING' or 'BAD' is caused by a
communications subsystem.
14 Implementer If true, this attribute indicates that
specified subsystem 'WARNING' or 'BAD' is caused by an
implementer-specified subsystem.

Each subsystem within the PLC has status information containing a similar set
of items. The status of each subsystem (and any subsystems contained therein) has
an initial item called 'health', which can take one of three states:
GOOD — The subsystem has not detected any faults — it is fully
operational.

WARNING — The subsystem has detected one or more faults, which may
limit its ability to completely perform its intended function. For
example, an I/O subsystem may occasionally be reading erroneous
values from certain inputs.

BAD — The subsystem has detected one or more faults which implies that
the subsystem is unable to perform its intended function.
The status information for each subsystem may also supply product specific status
details, such as additional error diagnostics, operational states, and local operator
key states.
Each set of status items will be defined as an IEC data structure. IEC 1131-5
states that such status information shall be accessible via pre-defined access paths
284 Programming industrial control systems using IEC1131-3
or from directly represented variables at defined fixed addresses. The standard
defines a complex set of reserved direct addresses for accessing the status of each
subsystem within a PLC.
For example, %S0 is the direct address for the main PLC state; %SS3 is the
direct address of the state of subsystem 3.

12.5 Communications function blocks

We will now review the set of communications function blocks that are defined by
the EEC 1131-5 standard to allow IEC compliant PLCs to exchange information
and control signals.
Table 12.3 lists the facilities provided by the standard communications function
blocks.

Table 12.3 Communications function blocks

Communications Facility Communications Function Block


Connection management CONNECT
Device verification STATUS, USTATUS
Data acquisition READ, USEND, URCV
Control WRITE, SEND, RCV
Alarm report NOTIFY, ALARM
Variable scope management REMOTEJVAR

Connection management
Communications function blocks read and write to remote PLCs via
communications channels. A channel can be established by calling an instance of
the CONNECT function block and supplying it with the full network address of a
remote PLC. The CONNECT block returns a local identity of a channel.
Subsequently, all communications function blocks which need to communicate
with the particular remote PLC can use the open channel.

Device verification
The STATUS and USTATUS blocks provide facilities to read the status of remote
PLCs. These would typically be used to ensure that a remote PLC is fully
operational at the start and at regular intervals during a joint control operation.
Chapter 12 Communications 285
Data acquisition

This concerns reading the values of variables from remote PLCs. The standard
supports two methods:

1. Polled: The READ function block can be used to read the values
of selected variables, either periodically or on a specific
trigger condition.

2. Programmed: The data messages are supplied on a time or condition


determined by the remote PLC. The USEND block in a
remote PLC can be used to send unsolicited data which
are received locally by the URCV block.

Control

Two methods are provided for the interaction of local and remote control
software:

1. Parametric: This allows a local PLC to modify the behaviour of a


remote PLC by writing values to key variables. The
WRITE function block allows values to be written to
selected 'access path' variables in a remote PLC.

2. Interlocked: This provides a control transaction where a local PLC


requests that a remote PLC performs an operation and
then signals back that the operation is complete. This can
be achieved using the SEND function block in the local
PLC (client) and the RCV block in the remote PLC
(server).

Alarm report

A PLC can signal selected remote PLCs when certain predetermined alarm
conditions arise. Remote PLCs can then send an acknowledgement back to the
local PLC to indicate that the alarm has been received. The ALARM and NOTIFY
function blocks can be used to generate acknowledged and unacknowledged
alarms, respectively.
286 Programming industrial control systems using IEC1131-3

Function blocks outline description

The following descriptions provide an overview of each block. In the EEC 1131-5
standard the behaviour of each block is formally defined using timing and state
transition diagrams.

CONNECT
This block is used to establish a
CONNECT communications channel to a
BOOL EN_C DONE — BOOL
remote PLC partner. The
BOOL PARTNER ERROR - BOOL
STATUS -INT remote PLC should have a
ID - CHANNEL unique address (e.g. node
address) on the network.
The channel ID can be used by other function blocks when communicating with
the remote PLC. The EN_C input is an enable that should be true to make the
channel connection.
Note: The data type of PARTNER is implementation specific.

STATUS
The STATUS block provides
STATUS remote status information for
BOOL > REQ NDR — BOOL device verification.
CHANNEL The status information is only
ID ERROR — BOOL

STATUS — NT requested on the rising edge of


PHYS — NT the REQ input. PHYS defines
LOG —NT the physical status, LOG the
LOCAL ARRAY[0i.7] OF WORD
logical status, including
software status, and LOCAL
contains additional imple-
mentation specific status.
Physical status refers to the PLC hardware; logical status concerns the status of the
application software.
The input ID should specify the channel identity as established by the
CONNECT block. NDR is set if a new user data message is received, i.e. if the
status information has changed. If the ERROR output is false, the other outputs
provide status information from the remote PLC.
Chapter 12 Communications 287

USTATUS
The USTATUS block provides status
USTATUS
information from a remote PLC.
BOOL BLR NDR — BOOL
CHANNEL ERROR — BOOL
While USTATUS enable input EN_R
ID
STATUS — NT is true, the status information is
PHYS — NT updated whenever the status of the
LOG —NT
LOCAL —ARRAVPL7J OF WORD
remote device changes. PHYS defines
the physical status, LOG the logical
status, including software status, and
LOCAL contains additional imple-
mentation specific status.

READ
READ The READ block polls a remote PLC
BOOL REQ NDR "BOOL for values of one or more variables. A
CHANNEL - ID ERROR -BOOL list of variables can be requested by
STATUS INT
Note 1 VAR_1 RD_1 ANY
supplying names as inputs. After a
short delay due to the network
Note 1 VAR_n RD_n — ANY communications, the values of the
selected
Note 1: Can be VAR.ADDR data type; variables are presented on the
see the REMOTE.VAR function block. function block outputs.
The READ block only fetches new values for the selected variables on the rising
edge of the REQ input.

WRITE
The WRITE block writes one or more
values to one or more variables within
a remote PLC. A list of variable
names specify access variables in the
remote PLC. The DONE output
Notel
ANY
becomes true when the remote write
operation has completed.

Note 1: Can be VAR_ADDR data type;


see the REMOTEJVAR function block.

Note 2: Inputs and outputs of the READ and WRITE blocks concerned with remote
variables use the generic data type ANY, implying that the data type will
change to match the type of variable being read or written. The use of data
type ANY is discussed in Chapter 3, Section 7.
288 Programming industrial control systems using IEC1131-3
The READ and WRITE function blocks use extensible inputs and outputs, i.e. the
number of inputs and outputs can be changed to suit the set of variables being
addressed; see Chapter 3, Section 19.

USEND
The USEND function is used to
USEND transmit data to a particular instance
BOOL ' REQ DONE -BOOL
ERROR -BOOL
of a URCV function block existing in
CHANNEL - ID
STRING - R jD STATUS -INT a remote PLC. The name of the
ANY - SD_1 remote URCV instance should be
supplied at the R_ID input. The
ANY SD_n
number of SD_n inputs is extensible.

URCV
The URCV block receives data for
URCV one or more variables from an
BOOL EN_R NRD "BOOL
instance of a USEND block in a
CHANNEL ID ERROR -BOOL

STATUS -INT
remote PLC. The R__ID input is used
STRING RJD
to specify the instance name of the
RD_1 -ANY
remote USEND block. The number of
RD_n -ANY RD_n outputs is extensible.
Note that the number of variables and the variable data types of the SD_i inputs of
the USEND block should match the RD_i outputs of the URCV block. Figure
12.3 depicts an example of USEND and URCV blocks being used to transmit job
details.
PLC_A PLC_A
URCV.JOB
USEND.JOB
URCV
USEND
URCVJOB . — RJD USEND^OB RJD
JobName, ~~ SD_1 \ y RD_1 — Name
JobPrtorfty — SD_2>\ / RD_2 — Priority
TimePendirig r*- SD_3\\ / RD_3 — Pending

Communications System

Figure 12.3 Using USEND and URCVfunction blocks


Chapter 12 Communications 289
SEND
The SEND block provides an
SEND interlocked data exchange with an RCV
BOOL REQ NRD "BOOL
block in a remote PLC. The SEND
BOOL R ERROR -BOOL

|D STATUS -INT
block transmits the values of one or
CHANNEL

STRING RJD RD_1


more variables to a remote RCV block
-ANY
ANY SD_1 : corresponding to the channel ID
RD_m — ANY established by the CONNECT block.
ANY SD_n
The number of SD_n inputs is
extensible.
The name of the remote RCV block should be specified at input R_ID. On
receiving the data values, the remote PLC then returns a set of values as a
response to the SEND block. These then appear at outputs RD_1 to RD_m.

RCV
RCV The RCV block receives a set of values
BOOL- EN_R NRD BOOL
RD_1 to RD_n from a remote SEND
BOOL- RESP ERROR -BOOL
block. In response, it transmits back a
CHANNEL- ID STATUS -INT
further set of values SD_1 to SD_m to
STRING- RJD RD_1 ANY
the SEND block. The number of SDjm
ANY- SD_1
RD_n -ANY inputs and number of RD__n outputs are
ANY- SD_m extensible.

Note: The send data, the response data or both may be empty, i.e. where no SD_n
inputs and corresponding RD_n outputs are defined.

The SEND function block instance requests that the RCV instance in a remote
PLC executes an application operation and returns the result of the operation to
the SEND instance. The SEND and RCV function block pair have the effect of
implementing remote procedure calls.
290 Programming industrial control systems using IEC 1131-3
ALARM
The ALARM block sends values of
ALARM one or more variables to a remote
BOOL EN_R DONE BOOL
PLC as identified by the channel ID.
BOOL EVENT ERROR • BOOL
CHANNEL - ID STATUS . INT
The alarm can be characterised by a
STRING • EVJD ACK_UP . BOOL severity level. The reason for the
INT . . BOOL
SEVERITY ACK_DN alarm or event is passed to the E V J D
ANY-
SD_1 input. This block expects that the
ANY SD_n remote PLC will acknowledge the
reception of the alarm. The number of
SD_n inputs is extensible.

The rising edge of the EVENT input is used to signal when an alarm or event
condition has occurred. The falling edge of the EVENT input signals when the
condition no longer exists i.e. has cleared.

NOTIFY
The NOTIFY-block can be used to
NOTIFY report an event or an alarm to a remote
BOOL EVENT DONE] BOOL
PLC but unlike the ALARM block does
CHANNEL ID ERROR BOOL

EVJ D STATUS INT not require an acknowledgement.


STRING
INT SEVERITY
The number of SD_n inputs is
ANY SD_1 extensible.
ANY SD_n

REMOTE.VAR
The REMOTE_VAR function block can
REMOTE_VAR be used to obtain an implementation
SCOPES SCOPE • VAR_ADDR specific address of a named variable. The
STRING - SCOPE_NAME
SCOPE identifies the name scopes of the
STRING - NAME
(notel)-
various IEC 1131-3 languages or other
SUB
implementation specific scopes as
defined in Table 12.4.
Chapter 12 Communications 291
The input SCOPE_NAME contains the identity of the name scope for a given
variable. The variable name is given by input NAME. SUB contains the name of a
sub-element or an index.
Note: Although not explicitly stated in IEC 1131-5, it is assumed that
REMOTE_VAR can only reference VAR_ACCESS variables.

For example, the following input values will request the remote implementation
specific address of the first element of an array SPEEDS defined as a
VAR_ACCESS variable contained in program instance PRG1, held in resource
RES1, defined within configuration CONFIG 1.
SCOPE := 2 ,
SCOPEJSTAME := 'C0NFIG1.RES1.PR0GRM1',
NAME := 'SPEEDS',
SUB := 1
The implementation specific address, e.g. the memory location, is returned in a
reserved data type called VAR_ADDR. The READ and WRITE communications
function blocks can reference variables using an address specified as a
VAR_ADDR data type. This mechanism allows variables to be referenced
efficiently using the implementation specific internal addressing scheme.
A VAR_ADDR can be regarded as a remote PLC software handle for an IEC
1131-3 variable and as such may be transitory in nature.

Table 12.4 Values of name scopes

Name scope of IEC 1131-3 Value


Configuration 0
Resource 1
Program 2
Function block instance 3
Reserved for future extensions 4
Reserved for future standards 4..9
Implementation specific >99

12.6 MMS mapping

Part of the EEC 1131-5 standard concerns the mapping of the communications
function blocks on to services specified in the MMS (Manufacturing Message
Specification) standard ISO/IEC 9506-5. MMS is the application layer specified
for MAP (Manufacturing Automation Protocol) - an industrial communications
system initiated by General Motors (GM) in the USA in the mid 1980s.
292 Programming industrial control systems using IEC1131-3
The MMS standard defines a set of services that allow industrial devices, cell
controllers and supervisory systems to exchange information over a
communications network. Each service is specified as a transaction. A defined set
of data items is transmitted to a remote device, which is then required to respond
with one of a defined set of responses. The structure of request and response
information is sufficiently flexible to allow for additional implementation specific
data.
The MMS mapping defined in the standard covers all the facilities as listed in
Table 12.3. Each function block will use a defined subset of the MMS services.
For example, the STATUS block will use the MMS Status service. It is envisaged
that the implementation of each communications block will call a defined set of
MMS services. This will allow DEC compliant devices to be able to interoperate
on any MMS based network.
Using MMS also makes it possible for devices on an MMS network, which are
not implemented using the IEC 1131-3 standard, to communicate with IEC 1131-3
based PLCs. For example, a numerically controlled (NC) lathe on an MMS
network could respond to a STATUS function block invoked within an IEC 1131-
3 based PLC, provided that it supports the necessary MMS service subset.
IEC 1131-5 defines the mapping between IEC 1131-3 and MMS and data types.

Examples of some IEC 1131-5 MMS mappings:

IEC 1131-3 data type MMS type description class and size
BOOL boolean
SINT integer 8
INT integer 16
DINT integer 32
LINT integer 64
USINT unsigned 8
REAL floating-point 32,8

Note: The full MMS data type mapping is given in Table 49 of the IEC 1131-5
standard.

IEC 1131-5 also defines rules for data type compatibility, the mapping of IEC
1131-3 name scopes to the various MMS domains and the MMS transactions
required to support the interaction of the IEC 1131-5 communications function
blocks.
Chapter 12 Communications 293

Summary
In this chapter we have outlined the main concepts defined in the IEC 1131-5
communications standard. To summarise:
• DEC 1131-5 uses concepts from the PLC languages standard - specifically
access variables and function blocks.
• The status of each subsystem within the PLC, such as memory, I/O system
etc., can be accessed as a standard structure at a fixed communications
address.
• Standard communications function blocks are defined to support a range of
facilities, such as device verification and data acquisition.
• Many of the function blocks have a server or client role. For example, a
local USEND block exchanges data with a remote URCV block.
• Variables within remote PLCs can be addressed using the implementor's
own addressing scheme.
• The communications function blocks are designed to map on to MMS
services so that PLCs compliant with IEC 1131-5 can intemperate on an
MMS based network.
Appendix 1

IEC 1131-3 keywords

This appendix contains a list of keywords used in the IEC languages. To avoid the
possibility of having ambiguous language identifiers, the names of the following
keywords should be regarded as reserved and not used as identifiers; see Chapter 3
for further details on identifiers.

Keywords Comments
N R S L D P SD DS SL Action block qualifiers used in
Sequential Function Charts
ACTION END^ACTION Declares an action block body
ARRAY OF Array variable definition
AT Used to associate variables with
directly represented variables
CASE OF ELSE ENDJ2ASE Case statement in Structured Text
CONFIGURATION Declares a configuration body
END_CONFIGURATION
CONSTANT Attribute of a variable
ENENO Control of functions and function
blocks in Ladder Diagram language
EXIT To exit from an iteration loop in
Structured Text
FALSE Boolean literal (constant) for false or =
0
F_EDGE Falling edge data type
FOR TO BY DO END_FOR Iteration constructs in Structured Text
FUNCTION END_FUNCTION Declares a function body
FUNCTION_BLOCK Declares a function block body
END_FUNCTIONJBLOCK
IF THEN ELSIF ELSE END J F Conditional statements in Structured
Text
INITIAL_STEP END_STEP Declares an initial step body
296 Programming industrial control systems using IEC 1131-3

Keywords Comments
NON_RETAIN Attribute of a variable that defines
that its value is never retained when
there is a powerfail1
PROGRAM WITH Used to configure a program
PROGRAM ENDJPROGRAM Declares a program body
R_EDGE Rising edge data type
READ_ONLY READ_WRITE Attributes of a variable
REPEAT UNTIL END_REPEAT Iteration constructs in Structured
Text
RESOURCE ON Used in resource configuration
ENDJRESOURCE
RETAIN Attribute of a variable that defines
that the value is retained during a
powerfail
RETURN Defines an early exit from a function
or function block
STEPENDJSTEP Declares a step body
STRUCT END_STRUCT Used to declare a structured data type
TASK Used to declare a task
TRANSITION FROM TO Declares a transition body
ENDJTRANSITION
TRUE Boolean literal (constant) for true or
=1
TYPE END__TYPE Declares a derived data type

1
Keyword added as an amendment to the 1993 edition of IEC 1131-3.
Appendix 1IEC1131-3 keywords 297

Keywords Comments
VAR ENDJVAR Declares a set of variables

VAR_INPUT ENDJVAR Declares a set of input variables

VAR_IN_OUT END_VAR Declares a set of input/output


variables
VAR.OUTPUT END_V AR Declares a set of output variables
V AR_EXTERN AL ENDJVAR Declares a set of external variables
VAR_ACCESS END_VAR Declares a set of access variables
VAR_GLOB AL END.VAR Declares a set of global variables
WHILE DO ENDJWHILE Iteration construct in Structured
Text
WITH Used to associate a program or
function block with a task

Note that the following should also be considered to be reserved:


• Standard data type names, e.g. BOOL, REAL
• Standard function and function block names, e.g. SIN, COS, RS, TON
• Textual operators in the Instruction List language, e.g. LD, ST, ADD, DIV
• Textual operators in the Structured Text language, e.g. NOT, MOD, XOR
Appendix 2

IEC 1131-3 amendments

This appendix summarises the main amendments to the 1993 revision of the IEC
1131-3 standard currently proposed by the IEC Task Force, IEC 65B/WG7/TF3,
to go into the second edition of IEC 1131-3 planned to be published in 1999.
At the time of writing this appendix, autumn 1998, these amendments have
been incorporated in the second edition of DEC 1131-3. The draft of the second
edition will be distributed to national standardisation bodies for review and
comment during the spring of 1999. The second edition is planned for publication
late summer 1999.
The fact that the IEC is working on new editions of IEC 1131-3 indicates that it
is an emerging standard that will continue to be refined and extended as users start
to apply the IEC 1131-3 concepts and languages to the development of
mainstream control system software.

Typed literals

There are situations where the type of data represented by literal values, such as
12.43, 73, 2#1001, is ambiguous. This is a particular problem in the Instruction
List (IL) language; for example, when a literal value is used with a load (LD)
instruction, the type of data loaded into the IL register cannot be specified.
It is proposed that all literals can be prefixed with their data type in the form
'<data type> #'. Examples are:
SINT#46 (* Short integer literal *)
LREAL#12.65 (* Long REAL literal *)
PRESSURE#43.2 (* Literal of user type PRESSURE *)
BOOL#1 (* Boolean literal *)

With bit string data types and integer literals, the representation format can be
included in the prefix (see Section 3.6). Examples are:
WORD#16#FF00(* Word literal in hexadecimal *)
BYTE#2#11010011 (* Byte literal in binary *)
300 Programming industrial control systems using IEC1131-3

Enumerated data types

There are several deficiencies with the use of enumerated data types in the 1993
revision of the standard. As with literals, the data type of a particular enumerated
value is ambiguous. For example, there may be several enumerated type
definitions using the enumeration string 'ON'. It is therefore proposed that the
data type of a particular enumeration literal can be specified using a prefix in the
form '<data type>#\ Examples are:

TYPE
VALVE_MODE: (OPEN, SHUT, FAULT);
PUMP_MODE: (RUNNING,OFF,FAULT);
END_TYPE;
IF AX100 = PUMP_MODE#FAULT THEN
XV23 = VALVE_MODE#OPEN;

The syntax of Structured Text is to be extended to allow enumerated variables to


be used in CASE statements, e.g.

TYPE
BATCHJTYPE: ( SMALL, LARGE, CUSTOM);
ENDJTYPE;
VAR
NEW_BATCH: BATCH_TYPE;
END_VAR;

CASE NEW__BATCH OF
SMALL: ... (* Small batch *)
LARGE: ... (* Large batch *)
CUSTOM: ... (* Custom size batch *)
ELSE

Temporary variables

With the 1993 revision of IEC 1131-3, there is no provision to create variables
within programs and function blocks to hold temporary values. Values held in
variables declared using the VAR construct within POUs always persist between
POU invocations. Using such variables for temporary values can result in an
inefficient use of memory.
There is a proposal that temporary variables can be declared using a
VAR_TEMP construct. Such variables will be placed in a temporary memory
Appendix 2IEC1131-3 amendments 301
area, e.g. such as on a stack, which is cleared when the POU invocation
terminates. For example:

VARJTEMP
RESULT : REAL;
END_VAR;

RESULT := AF18 * XV23 * XV767 + 54.2;


OUT1 := SQRT(RESULT);

Type conversion functions

There are a number of BCD (binary coded decimal) data type conversion functions
where the name of the function is not consistent with the data type of the initial or
converted variable. An amendment is proposed to provide BCD conversion
functions that include the data type of the BCD value in their name.
Examples of some new BCD type conversion functions are:

WORD_BCD_TO_UINT() Converts a word bit string containing a BCD


value to an unsigned integer.
UINT_TO_BCD__DWORD() Converts an unsigned integer to a BCD value in
a double word bit string.

Data type conversion functions will be provided for BCD values held in BYTE,
WORD, DWORD and LWORD variables.

Functions of time data types

There are also conflicts with the rules for overloading functions for time and date
calculations. The following new functions are therefore proposed:

ADD__T_T(...) Adds a duration time to another duration time to


produce a new duration time.
ADD_TOD_T(...) Adds a time of day to a duration time to produce
a time of day.
CONCAT_D_TOD(...) Concatenates a date and a time of day to
produce a new date and time.
302 Programming industrial control systems using IEC1131-3

Pulse action qualifiers

The pulse action qualifier P actually causes an action to execute twice, once when
the action is first activated and again after the action's associated qualifier Q is
cleared (see page 196). To provide a more consistent single pulse behaviour two
further action qualifiers are proposed:

Qualifier Description
PI Single pulse action when the action qualifier becomes true (rising
edge)
PO Single pulse action when the action qualifier becomes false (falling
edge)

Action control

It is proposed that the action qualifier Q can be tested within an action. This
allows an action to detect when it is executing for the last time, i.e. on the falling
edge of Q. The proposed behaviour is already described in Chapter 8, Section 8.7
* Action qualifiers'.

Function invocation with VARJN_OUT

An amendment to the second edition of DEC 1131-3 allows inputs to functions to


be declared as type VAR_JN_OUT if required. This implies that variables that are
passed as VAR_IN_OUT may be modified within the function body. This is
similar to passing a variable by 'reference' rather than by 'value'. This feature has
been added to allow functions to work more efficiently with multi-element
variables, i.e. structures and arrays.

For example:
FUNCTION S e t T e s t s : INT
VAR_IN_J3UT
Tests[1..10] : INT;
END_VAR
VAR_INPUT
TestValue : INT;
END_VAR
VAR
II : INT;
Appendix 2IEC1131-3 amendments 303
Count : INT := 0;
END..VAR

FOR II := 1 TO 10 DO
Count := Tests[II] + Count;
Tests[II] := TestValue;
END_FOR;
SetTests := Count;
END_FUNCTION

(* Example using SetTests() function *)


VAR
M20__Tests[l. .10] : INT;
Alarm : BOOL := FALSE;
END_VAR;

IF SetTests (Tests := M20_JTests,


TestValue := 10) > 20 THEN
Alarm := TRUE;
END_IF;

The function 'SetTests' sets the value of all elements of the array 'Tests' to 10. It
also calculates the original sum of all values in the 'Tests' array and returns the
value as the result of the function invocation.

Support for double-byte strings

An additional data type 'WSTRING' is proposed to allow strings to be defined to


hold double-byte characters. These are required for handling messages in
languages with complex character sets, such as Japanese. The string handling
functions will be overloaded so that they can be used with double byte strings.

RETAIN and NONJtETAIN variable attributes

The use of the RETAIN attribute with multi-element variables such as structures
and function block instances is modified in the second edition of IEC 1131-3.
When RETAIN is used with a multi-element variable it applies to all contained
variables except those that are declared with a NON_RETAIN attribute.
NON_RETAIN is a new attribute and indicates that the variable's value is not
retained during a powerfail and its default initial value is to be used after a warm
restart. If NON_RETAIN is applied to a multi-element variable, then it applies to
all contained variables that are not declared with a RETAIN attribute.
304 Programming industrial control systems using IEC1131-3

Use of directly represented variables in function blocks

It is proposed that variables within function block bodies can be declared with the
AT attribute so that they can be fixed at particular memory or I/O locations. It will
also be possible to use directly represented variables within function blocks. This
has been added to allow function blocks to be used for 'modularisation' of large
programs. In other words, it permits a large program to be broken down into a set
of smaller function blocks. Allowing memory and I/O addresses to be embedded
inside function blocks helps to simplify the overall design.
However, it should be noted that function blocks that contain directly
represented variables generally will not be re-usable in other systems.

Extended initialisation facilities

One major shortcoming of the 1993 revision of IEC 1131-3 has been the lack of
facilities to define configuration parameters for function blocks, programs and
complete configurations. Complex function blocks, such as for an advanced PDD
controller, generally require a large number of configuration parameters, e.g. for
defining tuning parameters, operating modes and time constants. In order to make
such blocks general purpose, all configuration parameters required for the internal
algorithm need to be brought out to the block's outer interface. In many cases, this
results in having a function block with an overly complex interface with many
inputs only required once when the block is first called.
For these reasons, the following new features to improve initialisation facilities
are proposed:

Function block instance initialisation

To avoid the need to invoke a function block instance simply to define its initial
input values, i.e. to set-up input values needed to configure the internal algorithm,
it is proposed that initial values for inputs and internal variables can be defined
directly when the function block instance is declared.
For example, setting the initial input values for an instance of the Ramp
function block:
Appendix 2IEC1131-3 amendments 305

VAR PressureRamp :
RAMP := ( CYCLE := T#1S, (* Set initial values
for *)
TR := T#3 0M); (* Cycle and Ramp
durations *)
ENELVAR
Note: Initial values for variables given in the function block instance declaration
will overwrite any default initial values defined in the function block type
definition.

Configuration initialisation

Most large IEC 1131-3 configurations will generally necessitate the definition of
many constants and I/O addresses in order to uniquely tailor the configuration for
use with a specific PLC system or application. Users have found that there is
sometimes a requirement to re-configure a proven DEC 1131-3 configuration for
use on different hardware or on a different application, e.g. to change a
configuration to work on a slightly different set of PLCs, or on a slightly different
production line or process. In such cases, the configurations may only differ in
terms of configuration parameters such as algorithm tuning parameters and the
addresses of I/O points.
To support this requirement, it is therefore proposed that a 'baseline'
configuration can be created. Configuration specific values can then be defined in
a single construct called VAR_CONFIG. This defines specific values that are used
to redefine the initial values of specified program inputs, program internal
variables and function blocks.
Consider the following example:
CONFIGURATION LINE_3

RESOURCE MACHINE1 ON PROC_486

PROGRAM PRG1 : PRG1_TYPE (...

PROGRAM PRG2 : PRG2_TYPE (


'. . .

END_RESOURCE
(* Define Line 3 specific data *)
VAR_CONFIG
MACHINE1.PRG1.LINE_LENGTH : INT := 20;
MACHINE1.PRG1.SPEED : REAL := 6.6;
MACHINE1.PRG2.RATE1 : TON := (PT := T#1M);
END_VAR
END_CONFIGURATION
306 Programming industrial control systems using IEC1131-3

This example shows how the initial values of variables LINEJLENGTH and
SPEED, declared within program PRG1, and resource MACHINE 1 can be
initialised to specific values. RATE1, which is declared within program PRG2, is
an instance of an on-delay timer (TON) that is initialised with a specific time
duration for input PT. The VAR_CONFIG can contain the initial values for any
variable within a program, except variables declared using VAR_TEMP, VAR
CONSTANT or VAR_IN_OUT. Each variable must be identified by
concatenating the resource name, program name, function block instance name
and so on, down through the block hierarchy.

'Wild-card* direct addresses

The definition of direct addresses for some variables, i.e. addresses used with the
AT construct, is another aspect of a configuration which may require redefinition
when a configuration is modified to work on a different physical system.
For example, a sensor connected to a PLC input may be at a particular physical
input channel and I/O rack position in one system but be connected to a
completely different physical input channel and rack in another. In order to use the
same software, i.e. the same IEC 1131-3 configuration in the two systems, it is
necessary to redefine the direct address used for the input. With the 1993 revision
of IEC 1131-3, changing direct addresses of variables can only be achieved by
modifying various variable declarations throughout the configuration and then
recompiling the configuration.
It is proposed that each variable for which the direct address is to be redefined is
declared using a * wild-card' address specified as an asterisk. Such variables are
considered to be 'not located'. Examples are:

VAR INPUT1 AT %IX* :BOOL;(^Boolean input not located *)


VAR VALV1 AT %QW* : INT; (*Integer output not located *)

The location of such variables can be specified in the VAR_CONFIG construct.


For example, the following statements will define the location of these variables;
assume that INPUT 1 and VALV1 are declared within resource RES1.

VAR__CONFIG
RES1.INPUT1 AT %IX100 : BOOL;(* Locate inputl *)
RES1.VALV1 AT %QW210 : INT;(* Locate valve 1 *)
END VAR
Appendix 2IEC1131-3 amendments 307
It is assumed that initial values for the variables specified in VAR_CONFIG will
be applied as the last process before creating the program object data that are
downloaded into the PLC.
Note: An error will be reported when the configuration is built if any variable
declared with an un-located direct address is not given a valid direct
address.

Amended Instruction List (IL)

There is a proposal to improve the description of the Instruction List (IL)


language. Many of the proposals are already described in Chapter 7, 'Instruction
List'.

Production rules

Many of these new features will result in changes to the production rules (i.e.
structure and syntax) for the textual languages. It is intended that wherever
possible the changes will be backward compatible' and should not significantly
impact on existing programming systems.

Summary

A number of other amendments are currently being considered to update the 1993
revision of DEC 1131-3. All of these changes are still under review and should not
be considered part of the standard until officially published by the EEC.
Appendix 3

IEC 1131-3 frequently asked questions (FAQ)

The following list is a compilation of frequently asked questions about IEC 1131-
3. The reader should be aware that it has been the author's best intention that the
answers to these questions are correct. However, in due course, it is possible that
changes in new editions of the standard may modify or possibly invalidate some of
the answers.

• Will IEC 1131-3 reduce the innovation of new languages and concepts for
PLCs?

The main objective of DEC 1131-3 has been to standardise existing PLC
languages. There is no intention that IEC 1131-3 should reduce the development
of new PLC languages. Any PLC vendor is free to provide extensions and
additional languages where required. Because the standard allows proprietary
function blocks to be programmed in non-IEC 1131-3 languages such as C++, it is
always possible to provide extensions fairly Seamlessly', e.g. packaged as
function blocks. This is well demonstrated by DEC 1131-7 "Fuzzy control
programming" which defines language extensions for implementing fuzzy logic
encapsulated as function blocks.

• Why does IEC 1131-3 have 'resources'? Is a resource just another name
for a PLC?

A resource is a general name for anything that is able to provide the appropriate
access to I/O systems and services to allow IEC 1131-3 programs to execute.
Normally a PLC that can execute IEC 1131-3 programs can be regarded as a
single resource. However, other processors, such as a personal computer (PC), if
able to support the execution of IEC 1131-3 programs may also be regarded as
resources.
310 Programming industrial control systems using IEC1131-3

• IEC 1131-3 seems to be very complicated. Is it still possible to create


simple Ladder programs by users unfamiliar with IEC 1131-3?

An IEC 1131-3 system can still be programmed as a single Ladder program if


required. Programming systems may provide an option to create a simple IEC
1131-3 configuration containing one resource, one task, and one program instance
of a program type. All of this could be created automatically so the user is only
concerned with developing a single ladder program. Function blocks and other
DEC 1131-3 constructs do not need to be used.

• Will IEC 1131-3 languages result in applications that run more slowly
and require more memory than using simple ladder?

Attempting to implement IEC 1131-3 constructs such as function blocks on PLCs


that were originally only designed to support ladder programs, will inevitably have
performance and memory overheads. PLCs specifically designed with firmware to
support the execution of IEC 1131-3 programs should not be noticeably slower
than classical ladder based PLCs. The improvements in software structure from
IEC 1131-3 should allow users to be able to write more efficient applications that
will be significantly easier to maintain than monolithic ladder programs. IEC
1131-3 languages tend to run more efficiently on new 'soft PLCs' than on
traditional ladder based PLCs.

• Is it really possible to port IEC 1131-3 software from one vendor's PLC to
another?

No it is not possible simply to take an application that runs on one type of PLC
and copy it over to another type. There are several problems preventing the direct
porting of IEC 1131-3 software.
1. The PLC I/O systems use different addressing schemes.
2. The task scan rates supported on different PLCs vary.
3. Each PLC vendor may have implemented a different subset of IEC
1131-3 features.
4. Similarly each vendor may have different values for implementation
specific parameters such as maximum array sizes, string lengths etc.
5. Finally there is not a standard file format in which to store and port
DEC 1131-3 applications.
Appendix 3IEC1131-3 frequently asked questions 311

Notwithstanding these constraints, at the function and function block level, it may
be possible to re-implement identical POUs on different vendors' PLCs. Textual
source code for POUs developed in ST or BL can be ported between different types
of PLCs.

• Is it possible to automatically convert between IEC 1131-3 languages: for


example, can a POU written using LD be viewed and edited in ST or
FBD?

This is a favourite IEC 1131-3 myth. There has never been any intention that it
should be possible to convert any language into any other language. If a restricted
subset of each language is used some limited portability may be possible but there
are some significant problems. For example, there is no way to represent
expressions involving array variables in the FBD language.

• Can function blocks also have execution control variables EN and ENO,
like functions?

The standard is not explicit about whether function blocks may have execution
control variables, e.g. for connecting function blocks within ladder rungs.
However, from the IEC 1131 languages user guidelines (part 8 of the IEC 1131
standard), it is implied that for consistency, both functions and function blocks
should use EN and ENO variables for execution control in ladder diagrams. It is
an implementation decision whether function blocks have EN and ENO variables
that can be used in the FBD language for explicit execution control. This may be
useful in eliminating execution order ambiguities that might arise in FBD
networks.

• In a full graphic implementation of FBD, is there any way to distinguish


between lines that cross over and lines that join?

The graphical format of lines, crossovers and junctions in full graphic


implementations of languages LD, FDB and SFC is not specified in IEC 1131-3. It
is an implementation decision outside the scope of the standard how fine graphic
details, such as 'line crossovers', are depicted.
312 Programming industrial control systems using IEC1131-3

• Where are type definitions actually defined and what is their scope?

All type definitions for data types and POUs can be regarded as outside the entire
IEC 1131-3 configuration and apply to all entities within the configuration, i.e. all
type definitions have global scope. This is as if all type definitions exist in a
conceptual 'header file' that is pre-processed before any entity within a
configuration is compiled. Extensions to IEC 1131-3 are now being considered to
provide a more flexible range of type scopes. With large applications, more
specific type scopes may be necessary, such as a library scope for type definitions
that only apply to POUs within a specific library.

• Do IEC 1131-3 languages enforce data type consistency?

All IEC 1131-3 languages except JL enforce strict data type consistency, i.e. it is
not possible to directly assign (or connect) variables of one data type to variables
of different data types. Data type conversion functions are necessary to convert the
values of variables to the appropriate type; e.g. an INT value should be converted
to a REAL value before being assigned to a REAL variable. In the IL language, it
is not always possible for a compiler to check that the type of value in the
accumulator will match the data type of any variable to be loaded from the
accumulator. With IL, run-time checks are required to ensure data type
consistency.

• When are the actions in an SFC actually executed?

Every SFC is encapsulated in a function block or program POU. When the POU is
invoked, e.g. because it has been scheduled by a task, the contained SFC is
evaluated once, i.e.
• The current set of active steps is determined.
• All transitions associated with active steps are evaluated
• Actions which nominally ceased execution in the previous SFC
evaluation (because their Q flag has been cleared) are executed one
last time.
• All actions that are active are executed once.
• Any active steps that precede transition conditions that are true are
deactivated and their succeeding steps are activated.
Appendix 3IEC1131-3 frequently asked questions 313
The encapsulating POU should be repeatedly invoked for the SFC to progress
through its various steps.

• How can the execution of all actions in an SFC be halted and the SFC be
restarted?

The execution of all actions in an SFC can be halted by suspending the invocation
of the encapsulating POU: see "When are the actions in an SFC actually
executed?"
If, at a later time, the POU is again repeatedly invoked, the active actions in the
contained SFC will continue to be executed. The only way to re-start an SFC from
its initial step and clear all active actions is for the resource containing the POU to
have a 'cold start'. A jump back to the initial step is always possible using an
explicit branch, e.g. back from the last step in a sequence. However, this cannot
guarantee to clear any stored actions or simultaneous sequences which may have
been started.

• Can more than one variable be fixed at the same direct address using the
AT construct?

The standard does not forbid this. Allowing variables to be at the same or to use
overlapping memory locations is an implementation issue. This however may
invalidate data type consistency - see "Do IEC 1131-3 languages enforce data type
consistency?"

• When using the AT attribute, does the size of a memory location specified
by a direct address have to match the size of the variable?

The standard is unclear; there are two ways of interpreting the purpose of the
direct address. It specifies either (a) the actual memory location, in which case the
location size and variable type size should match, or (b) the starting address from
which the variable will be located, in which case sizes do not need to match.

• When are user specified initialisation values for variables used?

User specified initial values apply to non-retentive variables both at 'cold restart'
and 'warm restart', but they only apply to retentive variables at 'cold restart'. On
'warm restart' retentive variables have the same values as existed when their
314 Programming industrial control systems using IEC1131-3

resource stopped executing, e.g. due to a power outage. The 1131-3 amendment
allows initialisation values defined by the VAR_CONFIG construct to override
type specific initial. values. Therefore, VAR_CONFIG specified initial values
apply at 'cold restart' or 'warm restart' for non-retentive variables, and to 'cold
restart' for retentive variables.

• Can function block instances be passed as inputs to other blocks?

Yes, if function block FBI is passed as an input to a second function block FB2, it
is possible to invoke the function block FBI within the body of FB2. Any input
parameters of FBI not defined in the invocation call within FB2 will take values
defined by earlier invocations of FBI made outside FB2. Function block instances
should be passed as VARJNLOUT parameters as otherwise the values produced
within the internal invocation will not be preserved.

• Are the assignments of inputs and outputs to programs at the resource


level fixed or can they change dynamically?

They are fixed. Programs are the highest level IEC 1131-3 programmable
organisation units. It is not possible to have language statements outside a
program. In a resource declaration it is only possible to assign input and output
variables to the program interface. If it is necessary to change the inputs used by
part of a program, then all inputs concerned should be passed to the program and
any dynamic selection of particular inputs should be done within the program
body, e.g. switching between two different sets of sensors.
Appendix 4

IEC 1131-3 future developments

Considerable progress in the adoption of IEC 1131-3 languages has been made in
the three years since this book was first published in 1995. At that time, the
PLCopen trade association promoting IEC 1131-3 products had a membership of
about 40 companies and organisations. Now in the spring of 1998, PLCopen's
membership has grown to almost 100 indicating that interest in IEC 1131-3 is
rapidly increasing. Most of the major PLC manufacturers now have an active
interest in EEC 1131-3. Originally the main interest in IEC 1131-3 was centred in
Europe, but interest is now truly international with involvement of companies
from the US, Japan and Europe.
Since 1993 a wide range of automation products have appeared on the market
that have adopted some aspects of the IEC 1131-3 standard; these range from
programming support software for traditional ladder based PLCs, through to 'soft
P L C products, and programmable SCADA.
Worldwide, the market for PLCs and automation products is still showing
healthy growth. Related to this growth in automation, there is also going to be a
considerable increase in the demand for software. It is estimated that the European
market alone for automation and process control software will be at least $2500
million by 2001. It is therefore likely that the demand for IEC 1131-3 based
products is also going to increase dramatically.
As companies started to develop products complying with the 1993 edition of
IEC 1131-3, small inconsistencies and errors in the standard were uncovered. The
IEC task force, 65B/WG7/TF3 developing IEC 1131-3, categorised these as being
either corrections to the published standard — generally typographical errors, or
amendments, which require minor technical modifications. All corrections and
amendments to the 1993 edition have now been collated and reviewed by
international standardisation bodies. There is a good chance that these will be
incorporated into the second edition of IEC 1131-3 which should be published
towards the end of 1998 or early 1999.
316 Programming industrial control systems using IEC1131-3

Looking forward, the third edition of IEC 1131-3 is likely to have significantly
more technical changes. The exact nature and format of these changes are still
being considered but the main issues to be addressed are likely to be:

• Harmonisation with the function block standard IEC 1499;


• Additional features for safety critical software;
• Support for working with devices operating across Fieldbus networks;
• Extensions to bring IEC 1131-3 closer to Object Oriented languages.

The most significant new direction for PLC applications that is foreseen in the
near future is the development of truly distributed applications. No longer will
system engineers be concerned about an application that runs solely on a single
PLC. Future systems are most likely to involve distributed applications that run
over a variety of network topologies. For example, large automation applications
are likely to communicate across the Internet, factory local area networks (LANs)
and proprietary networks.
As applications become more distributed, it will become more difficult to
identify the true boundaries of the application. This is synonymous with the
structure of the Internet World Wide Web where it is sometimes difficult to
identify the boundaries of a Web site - as one site may have links with other sites
and become dependent on them. Handling complex distributed automation
applications and dealing with issues such as version control and on-line
maintenance will prove to be particularly challenging.
To achieve large scale distributed applications for industrial control, and yet
enable the creation of flexible systems that can be re-engineered as industrial and
business needs change, will require a completely new approach to software design
- a new technology based on the interaction of distributed objects. There are
several software technologies already well advanced that are set to have an
influence in this area. CORBA (Common Object Request Broker Architecture) is
a new standard for designing distributed objects that is being developed by a
consortium of leading software vendors - the Object Management Group (OMG).
OPC (OLE for Process Control) based on Microsoft's OLE/COM (Object
Linking and Embedding, Common Object Model) technology will allow software
in the form of software components to interoperate regardless of where they are
located, be it in a remote industrial controller in a blast furnace or in the PC of the
production manager's office. Internet technology using Java and the World Wide
Web is also being considered for the development of software components for
Appendix 4IEC1131-3 future developments 317

manufacturing systems. There are even industrial devices emerging, such as smart
valves that are able to execute embedded Java code directly.
The industrial community has long been aware that the ready interconnection of
software components, such as in the form of function blocks, will have major
advantages especially for end-users. These advantages will include improved
software productivity through re-use of standard solutions and improved design
flexibility by being able to plug-and-play software and devices from different
vendors. So far, the new standards all enable 'technical integration' of distributed
components, but the next major hurdle is 'semantic integration'. We may be able
to link and exchange data between software in a remote industrial controller and a
control algorithm running in a PC, but will the connection be meaningful?

What is the IEC 1499 Function Block standard?

The EEC is currently developing a new standard IEC 1499 that defines how
function blocks can be used in distributed industrial process, measurement and
control systems.
As we have seen from IEC 1131-3 applications, function blocks are a well-
established concept for defining robust, re-usable software components. A
function block can provide a software solution to a small problem, such as the
control of a valve, or control, a major unit of plant, such as a complete production
line. Function blocks allow industrial algorithms to be encapsulated in a form that
can be readily understood and applied by people who are not software specialists.
Each block has a defined set of input parameters, which are read by the internal
algorithm when it executes. The results from the algorithm are written to the
block's outputs. Complete applications can be built from networks of function
blocks formed by interconnecting block inputs and outputs.
It is anticipated that the Application Layer part of the Fieldbus communications
stack will provide the software interface to allow remote function blocks to
interoperate over Fieldbus. However, IEC 1499 is being developed as a generic
standard that is also applicable in other industrial sectors, in fact wherever there is
a requirement for software components that behave as function blocks, such as in
building management systems.
IEC 1499 defines a general model and methodology for describing function
blocks in a format that is independent of implementation. The methodology can be
used by a system designer to describe how a distributed control system is
constructed by interconnecting function blocks on different processing resources.
318 Programming industrial control systems using IEC1131-3

Summary

During the next few years the main focus of IEC 1131-3 standardisation work is
clearly going to concern language concepts and extensions for building distributed
applications. Recent developments in the use of distributable software components
and concepts such as re-usable software as function blocks are likely to have a
major impact in this area.
The IEC and the international standardisation bodies have done a great deal of
work to create standards in this area. In the long term, the unification of software
languages and architectures for distributed industrial control applications will
bring major economic advantages to end-users and system builders alike.
Bibliography

Cox BJ. (1986). Object Oriented Programming, An Evolutionary Approach.


Addison Wesley.
International Electrotechnical Commission (1992). Programmable controllers
Part 1 General information, IEC 1131-1, EEC Geneva.
International Electrotechnical Commission (1993). Programmable controllers
Part 3 Programming Languages, IEC 1131-3, IEC Geneva (also British
Standard BS EN 1131-3 : 1993).
International Electrotechnical Commission (1988). Preparation of function
charts for control systems, IEC 848, EEC Geneva.
International Electrotechnical Commission SC65B/WG7/TF7 (December
1993). Programmable controllers Part 5 : Communications, IEC Task Force
working draft.
Norme Francaise Enregistree (June 1982). Function Chart 'Grafcet' for the
description of logic control systems. NF C03-190.
Parr B. A. (1993). Programmable Controllers, An Engineer's Guide. BH
Newnes.

Related papers

Boudreaux J.C. (1988). Requirements for global programming languages,


MAPL Symposium on manufacturing application languages, Ottawa.
Juer J. and Hughes I.P. (1991). IEC 65B Control Languages - a practical view.
IEE Conference, Software Engineering for Real Time Systems, Cirencester,
England.
Lewis R.W. (1993). The new IEC 1131 standard for programmable controller
languages brings the benefits of 'Open Systems'. IEE International Workshop,
Software Engineering for Real Time Applications, Cirencester, England.
320 Programming industrial control systems using IEC 1131-3

PLCOpen

For further information on companies and products using IEC 1131-3 contact:

PLCopen
PO Box 2077
5300 CN Zaltbommel
Netherlands
Index

Access protection, 271 Boiler water feed pump, 247


ACTION, 199 Boolean, 56, 89
textual form, 218 expressions, 121
Actuator, 33, 35,43, 251 signal negation in FBD, 139
ADA, 20 Boolean logic, 157
ADD, 93, 97 BYTE, 62
Air Damper, 146
Alarm, 13, 23, 32, 60, 65, 114, 221 C language, 22, 245, 253
monitoring, 255 Calculation using ST, 131
Alarm function blocks, 243 Call by reference, 71
Algorithm, 36, 98, 239 Character set, 54
Alternative sequences, 188 Closed loop control, 98
AND, logic function, 87 Comment, 56
ANY, 64 Commissioning, 268
Application Communications
mapping to configurations, 44 access paths, 51, 107, 114
steam turbine example, 247-64 accessing variables, 76
ARRAY, 67 alarm reporting, 285
Assignment, 118 connection management, 284
AT, 75 data acquisition, 285
overlapping addresses, 313 device verification, 284
using, 313 external, 50
Automation, 6 Function Blocks, 284-90
RCV, 50
Base Language SEND, 50
asILorST, 170 internal, 47
Batch, 56, 93 using globals, 49
applications using SFC, 190 remote control, 285
string handling, 93 serial, 253
BCD Communications model, 279
converting, 83 Communications networks, 7, 277
Binary literals, 57 Comparison
Bistables, 228 functions, 89
Bit wise operations, 87 using LD, 160
322 Index
Compiler times of day, 60
data type checks, 119 DATE, 60
overloaded data types, 80 DATE_AND_TIME, 60
Structured Text, 170 Debugging, 264
Compliance levels, 26 Decimal values, 58
Compliant statement, 275 Design analysis, 249
Composite function block, 241 Design decomposition, 254
Conditional execution of code, 124 Deterministic execution, 14
Configuration, 34, 112 Diagnostics
example, 255 on-line, 274
overview, 112-14 run-time, 267
Configuration management, 271 DINT, 57
CONSTANT, 74 Direct Digital Control, 33
Continuous function chart, 147 Distributed systems, 41, 316
Control characters DIV, divide, 85, 94
embedding, 62 Divergence path, 189
Control flow, 40 Documentation, 268, 271
Conveyor belt Double byte strings, 303
counting, 233 DWORD, 62
Counting, 57, 231
Edge detecting, 230
Data base, import/export, 269 EN and ENO, 97
Data encapsulation, 9, 24 controlling ENO in IL, 182
Data persistency, 224 in Structured Text, 97
Data structure, 19 using in LD, 159
Data type using with function blocks, 311
array, 67 Encapsulation, 24
bit string, 63 Energy calculation, 237
boolean, 63 ENO
character strings, 61 difficulty representing in ST, 163
consistency, 312 no textual equivalence, 145
conversion, 82, 301 Enumerated data
derived, 65 amendments, 300
example, 251 restrictions, 96
edge detecting input, 230 Error detection, 275
enumerated, 66, 126 Errors
floating point (REAL), 58 data conversion, 83
generic, 63 Ethernet, 279
hierarchy, 63 PLC communications, 39
integer, 57 EXIT, 129
introduced, 56 EXPT, exponential, 85
overloading in IL, 176 Extensible function blocks
scope, 312 communications, 288
structures, 65 Extensible functions, 87
time, 59 External communications, 39
Index 323
External interfaces, 252 body, 100
calling in IL, 177
FALSE, boolean literal, 63 calling in LD, 158
Fault detection communications, 50
using SFC, 221 comparison with ICs, 23
FBD, see Function Block Diagram concept, 36
Feedback, 228 counter example, 101
defining, 140 CTD Down-counter, 231
evaluation rule conflict, 162 CTU Up-counter, 231
Fieldbus, 279 CTUD Up-down counter, 232
interoperability, 22 declaration, 100-101
PLC communications, 39 design, 245
standards, 7 edge detection
Floating point (REAL), 56 FJTRIG
rounding to integer, 82 falling edge, 229
FOR..DO, 127 inLD, 163
Function, 78 RJTRIG
as ST operators, 84 rising edge, 229
bit string, 86 Example
boolean, bitwise, 87 DELAY, 225
called in LD, 159 DERIVATIVE, 238
calling in EL, 177 HYSTERESIS, 243
calling in ST, 80 INTEGRAL, 237
compared to function block, 37 PID three term controller, 239
comparison, 89 RAMP, 241
date and time, 93, 301 RATIO_MONITOR, 244
declaration, 78 TurbineSequence, 259
ENandENO,98 Valve Control, 262
execution, 96-98 execution rules, 111
execution control instance, 44, 100, 225
EN..ENO, 142 passed as input parameter, 227
extensible, 85 interconnections, 36
libraries, 46 libraries, 46
numerical, 84 low level blocks, 262
overloaded data types, 80 overview, 22, 98-100
overview, 77 passed as an input, 314
returning a value in IL, 179 RS Bistable, 166,228
selection, 88 RTC Real Time Clock, 235
standard types, 77-98 SEMA Semaphore, 228
string manipulation, 91 software building blocks, 223
Function block, 250 SR Bistable, 228
accessing inputs and outputs, 123 standard range, 37
algorithm in "C" or PASCAL, 245 standard types, 227-36
as a software building block, 22 TOF Off-delay Timer, 234
as inputs to FBs, 99 TON On-delay Timer, 234
324 Index
TP Pulse Timer, 233 avoiding ambiguity, 55
type definition, 100, 224 me
usage rules, 226 PLC Standardisation, 3
using modes, 132 Technical Committee 65,4
Function Block Diagram, 20 ffiC 1131-3
Action, use of, 200 compliance, 274
evaluation rules, 144 defining a new standard, 4
evaluation rules as LD, 162 definition, 4
example, 146 disclaimer, 1
introduction, 136 formal definitions, 1
jumps and labels., 143 languages overview, 20
like electrical circuit, 137 main features, 18
methodology, 137-39 publication, 7
network layout, 141 software elements overview, 24
order of evaluation, 141 Technical Report Type 2,4
signal flow, 139 ffiC 1131-5
tank control example, 138 communications example, 51
FUNCTION_BLOCK, 100, 224 communications standard, 39,
277-80
Gas/air mixture control, 244 ffiC 1499
Globals, 38,49, 105, 107, see harmonisation, 316
Variable, global overview, 317
example, 254 DSC 65B/WG7,4
in function blocks, 100, 227 DEC 848
Real Time Clock, 235 basis for SFC, 186
Grafcet, 12 IL, see Instruction List
basis for SFC, 185 Indicator variable, 197
Graphic Information exchange, 254
avoid cluttering, 138 Information hiding, 24
conventions, 137 INITIAL.STEP, 218
full, 137 Initialisation
style, 137 array, 68
Graphic representation, 137 configurations, 304
format, 311 default defined, 68
Graphical editors, 269 function blocks, 304
variables, 65
Heat treatment, 215 Instantiation, 44, 100
Help, on-line, 269 Instruction List, 21
Hexadecimal literals, 57 accumulator, 171
Hierarchical design, 46, 214, 266 background, 169-70
example, 46 bracketed expressions, 173
Windows, 269 calling functions and function
Holdback, 241 blocks, 177
comments, 172
Identifiers, 54 current result, 171
Index 325
deferred execution, 173 retentive coils, 155
deficiencies and extensions, 180 Set and Reset, 155
disadvantages, 170 ST equivalent, 152
example, numerical control, 182 Ladder program sequencing, 12
input operators, 178 Ladder programming
modifiers, 174 background, 2, 8
operator precedence, 174 deficiencies, 7
operators, 175 dialects, 2
portability to other languages, 181 PID control, 13
reserved function block operators, poor data structure, 10
179 scan timing, 13
semantics, how instructions use in large programs, 9
behave, 172 Language conversion, 311
structure, 170-72 Language selection, 19
INT, 57 LD, see Ladder Diagram
Integer, 56, 57, 101,125 Library management, 271
division, 85 Lights out factory, 6
literal, 56 LIMIT, limit function, 89
Invocation, 102 LINT, 57
ISA, 7 Literals
ISO, 3 bit string, 63
seven layer model, 278 boolean, 63
ISO/EEC 646, character set, 90 character string, 62
data types defined, 299
Keywords, 55, Appendix 1 floating point (REAL), 58
integer, 57
Ladder Diagram, 21 introduced, 56
Action, use of, 200 time, 59
background, 151-53 time of day, 60
calling functions, 159 LREAL, 58
connecting function blocks, 158 LWORD, 62
detecting normal and inverse
states, 154 Man-machine interface, 35
example, 260 MAP, 7, 279
feedback paths, 160 Market growth, 5
fire alarm example, 166 PLCs and software, 315
graphical symbols, 153-56 Mathematical functions, 84
jumps and labels, 161 MAX, maximum function, 89
layout, 164 Micro PLCs, 6
limitations, 164 MIN, minimum function, 89
methodology/power flow, 157 MMS, 50, 279
network evaluation rules, 162 mapping to IEC 1131-5, 291
portability to ST, FBD, 162 MOD, modulus, 85
positive, negative transition Mode control, 71
sensing, 156 Motor control, 220
326 Index
MOVE, assignment, 85 Plant interaction, 248
MUL, multiply, 94 Plant supervision, 261
Multiple processors, 41 PLC
Multiple users, 266 address ranges, assigning, 273
MUX, 96 cold-start, 191
Multiplexor function, 89 communications, 32
communications server, 279
Namescopes, 291 environment, 31
Navigation, across diagrams, 270 functional model, 280
Noisy input signals hardware diagnostics, 281
glitch removing, 235 hardware resources, 112
NON_RETAIN, 303 I/O addressing
Non-deterministic, 108 example, 251
Non-printable characters, 62 I/O channels, 35
Non-volatile memory, 267 I/O interfaces, 31
NOT, logic function, 87 market, 5
Number ranges, 57 memory
decimal, 58 program access, 104
Numerical Control example, 182 memory addresses, 39, 73, 100
memory mapping, 33
Object oriented programming, 22 multiple processors, 41-43
Octal literals, 57 physical structure, 35
On-line software modification, 274 processing capacity, 107
Open systems, 6 project, 103
Operator interfacing, 253 scanning ladder rungs, 162
OR, logic function, 87 status information, 281
Overloaded data types, 64 subsystem health, 283
system firmware, 233
Parallel activities, 44 system interfaces, 32
Parallel sequences, 190 PLCopen, 26, 320
PASCAL, 20,45, 71, 117, 245 Portability
Performance between languages, 26
floating point calculations, 131 between ST and FBD, 145
of IEC 1131-3 implementations, limitations, 310
310 Precedence, operators in ST, 120
optimising with IL, 170 Program, 36, 48, 104, 107, 250, 254
SFC execution, 209 as highest level POU, 314
Petrinet, 185 declaration, 105
PID decomposition, 257
as function block, 37 overview, 103
calling in Structured Text, 122 partitioning, 200
closed loop control, 33 types, 104
Function Block example, 239 usage, 103
in Action blocks, 198 Program down-load, 267
tuning multiple blocks, 99
Index 327
Program organisation unit, 18,44- Semigraphic, 137, 189
45,102,103,191,197,209 Sensor, 32, 35,43, 65, 251
described using SFC, 208 calibration, 93
design, 250 pressure, 68
Function Block, 98, 224 Sequencing, 185
introduction, 53 example
name scope, 217 turbine control, 258
variable declaration, 69 Sequential Function Chart, 21
Program style Action
avoiding multiple ladder rungs, associating with steps, 196
164 control, 302
in SFC, 217 Indicator variable, 197
limit use of globals, 50, 255 on separate diagram, 197
naming convention, 251 pulse qualifiers, 302
using IL, 182 Qualifier, 197, 201
Programming station, 46, 265-75 using different languages, 196
configuration generation, 257 Action Control function block, 206
overview, 27 background, 169-70
Project management, 271 design validation, 214
divergent paths
Ramping, 241 precedence, 209
Reactor vessel example, industrial lift, 165-66
controlling using SFC, 188 example, steam turbine, 259
READ-ONLY, 76 execution explained, 312
READ_WRTTE, 76 execution rules, 208
REAL, 58 halting execution, 313
Real Time Clock, 235 Macro steps, 216
Real-time multi-tasking, 41 real time monitoring, 274
Recursion, not allowed, 45 rules of evolution, 209
Relay ladder, 151 safe and unsafe design, 212
Remote procedure calls, 289 scope of names, 217
Resource, 35, 103, 105,114, 254, semigraphic representation, 189
255,263 sequence
multiple processors, 35 convergence, 212
overview, 106 divergence/convergence, 189
why use, 309 loop, 211
RETAIN, 74, 303 skip, 211
simultaneous sequences, 190
Sampling theory, 33 Step
Scan times, checking, 273 executing and time variables,
Scopes, 291 191
SEL, 96 timing, 192
selection function, 89 types, 191
using select function in ST, 134 structure, 186
Selecting values, 88 textual form, 218
328 Index
top down design, 214 String handling, 91
Transition comparison, 90
avoiding ambiguity, 210 double bytes, 303
different languages, 193 errors, 93
SFC, see Sequential Function Chart Strong data typing, 19
Shift functions, 86 STRUCT, 65
Signal Flow, 263 Structured Text, 20
Signal processing function, 35 assignment, 118
SINT, 57 calling function blocks, 122
Software interfaces, 22 conditional statement
Software model CASE, 125
application, 43-44 IF..THEN, 124
configuration, 34 EXIT, 129
function block, 36 expression, 119
main features, 31-34 expression evaluation, 120
mapping to real systems, 41-43 FOR..DO, 127
program, 36 function block example, 132
resource, 35 implementation dependencies, 130
task including common elements, 118
definition, 36 introduction, 117
use with programs, 36 iteration
Software quality FOR..DO, 127
attributes, 15 REPEAT..UNTEL, 128
Software re-use, 22,45, 223, 267 WHILE..DO, 128
SQRT, 97 operators, 119
using function in EL, 182 operators as functions, 120
ST, see Structured Text quadratic equation example, 131
Standard Function Blocks, 22, 227 RETURN, 129
Standard industrial blocks, 22 statement, 122
Standard libraries, 46 SUB, subtract, 85, 94
Steam valve, 33 Supervisory system, 279
Step, 218 Switchgear, 251
as sequence element, 186 Syntax checking, 266
STRING, 61 System
String function shut-down, 40
CONCAT,91 start-up, 40
use with date and time, 95 System build, 271
DELETE, 92 System commissioning, 255
FIND, 92 System interfacing, 31
INSERT, 92
LEFT, 91 TASK, 110
LEN, 92 Tasks, 19, 36
MID, 91 assigned using WITH, 106
REPLACE, 92 declaration, 110
RIGHT, 91 defining, 111
Index 329
definition example, 255 access path, 39, 51,277
overview, 107-11 predefined, 283
preemptive/non-preemptive, 108 attributes, 74
Three term controller, see PID cold and warm re-start values, 313
TIME, 59 constant, 74
Time and date conversion, 95 declaration, 69
TIMEJDFJDAY, 60 directly represented, 39, 73,284
Timers, 233 restrictions, 39
Timing use in function blocks, 304
control of in sequences, 201 external, 72
Transitions, 193 function block, usage in, 104
Trigonometric functions, 84 fixing location using AT, 75
TRUE, boolean literal, 63 global, 38, 69,71
Truncation program, usage in, 104
decimal values, 83 hierarchical names, 114
Tuning performance, 111 initialisation, 76
TYPE, 65 input, 70
input/output, 70
UDINT, 57 inputs, outputs example, 251
UINT, 57 local, 38, 69
ULINT, 57 output, 70
USINT, 57 remote access, 76
sub-range, 67
Validation, 270 temporary, 72, 300
Value time, 94
sub-range, 67 value retaining, 74
Valve control, 262 Variableaddress, 291
Valve controller, 251 Vendor-independent software, 20
VAR, 69 Virtual machine
VAR.ACCESS, 76, see Variable forIL, 180
access path Voting 2 out of 3, 166
example, 252
VAR_ADDR, 291 Warm re-start
VARJEXTERNAL, 72 retaining values, 74, 303
VAR_GLOBAL, 71, 99, see Weighing, 132
Variable global WHILE, 128
VAR__IN_OUT, 253 Windows, user interface, 266
described, 70 WITH, 111
use with functions, 79, 302 task assignment, 106
VAR_INPUT, 70 WORD, 62
VAR_OUTPUT, 70 WSTRING, 303
VARJTEMP, 72, 300
Variable XOR, exclusive OR function, 87
IET Control Engineering Series 50

Programming Industrial Control Programming

Systems Using IEC 1131-3


Programming Industrial Control
Systems Using IEC 1131-3
Revised Edition
Industrial Control
IEC 1131-3 is the international standard for the design of software for industrial control
systems. It defines a set of related graphical and textual languages that bring significant
benefits throughout the control system life-cycle – benefits for system integrators, control
system engineers and end-users alike. The standard marks the beginning for well-
Robert Lewis is the UK
expert on two IEC working
groups defining the PLC
programming language
Systems Using
IEC 1131-3
standard (IEC 1131-3) and
structured, re-usable and maintainable software for industrial control systems.
developing a new standard
This new edition has been revised and updated to include all IEC proposed amendments for specifying reusable
and corrections for the planned 1999 edition of IEC 1131-3, agreed by the IEC working software function blocks
group in spring 1998. The book now includes IEC 1131-3 ‘frequently asked questions’ and for distributed industrial
a summary of future developments influencing the next generation of PLC languages, and manufacturing systems

Revised Edition
(IEC 1499). He is a
plus an overview of IEC 1499 standard on function blocks.
Fellow of the IET and has
Although primarily for programmable logic controllers (PLCs), IEC 1131-3 concepts will also been concerned with the
influence the design of software for fieldbus devices. development of control
systems for a wide range of
This book introduces all the concepts of the IEC 1131-3 standard and provides examples industrial applications for over
of the languages related typical industrial control problems. It will be of interest to 15 years. One of his particular
everyone involved in specifying or developing software for industrial or manufacturing interests is the application
applications. The text will also be of value to students and engineers with a general of graphical programming
interest in new techniques for industrial or manufacturing applications. The text will also techniques to the design of
be of value to students and engineers with a general interest in new techniques for industrial control software.
industrial control systems.

R.W. Lewis
Lewis

The Institution of Engineering and Technology


www.theiet.org
0 85296 950 3