Download

Download as pdf or txt
Download as pdf or txt
You are on page 1of 856

Relion 650 SERIES

Transformer protection RET650


Version 2.2 IEC
Technical manual
Document ID: 1MRK504170-UEN
Issued: June 2023
Revision: J
Product version: 2.2

© 2017 - 2023 Hitachi Energy. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written permission from
Hitachi Energy, and the contents thereof must not be imparted to a third party, nor used for any
unauthorized purpose.

The software and hardware described in this document is furnished under a license and may be used
or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit
(https://www.openssl.org/). This product includes cryptographic software written/developed by: Eric
Young ([email protected]) and Tim Hudson ([email protected]).

Trademarks
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Energy
company. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest Hitachi Energy representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that each
intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and/or product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or entity applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken
to exclude or mitigate such risks.

This document has been carefully checked by Hitachi Energy, but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall Hitachi Energy be responsible
or liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits
(Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by Hitachi
Energy in accordance with the product standard EN 60255-26 for the EMC directive, and with the
product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.
1MRK504170-UEN Rev. J Table of contents

Table of contents

Section 1 Introduction..................................................................................................33
1.1 This manual.........................................................................................................................33
1.1.1 Presumptions for Technical Data.......................................................................................33
1.2 Intended audience...............................................................................................................33
1.3 Product documentation....................................................................................................... 34
1.3.1 Product documentation set................................................................................................34
1.3.2 Document revision history................................................................................................. 35
1.3.3 Related documents........................................................................................................... 36
1.4 Document symbols and conventions...................................................................................36
1.4.1 Symbols.............................................................................................................................36
1.4.2 Document conventions......................................................................................................37
1.5 IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping....................................................39

Section 2 Available functions...................................................................................... 43


2.1 Main protection functions.................................................................................................... 43
2.2 Back-up protection functions............................................................................................... 43
2.3 Control and monitoring functions.........................................................................................44
2.4 Communication................................................................................................................... 47
2.5 Basic IED functions............................................................................................................. 48

Section 3 Analog inputs...............................................................................................51


3.1 Introduction..........................................................................................................................51
3.2 Function block..................................................................................................................... 51
3.3 Signals.................................................................................................................................51
3.4 Settings............................................................................................................................... 52
3.5 Monitored data.................................................................................................................... 56
3.6 Operation principle.............................................................................................................. 56
3.7 Technical data..................................................................................................................... 57

Section 4 Binary input and output modules.............................................................. 59


4.1 Binary input......................................................................................................................... 59
4.1.1 Binary input debounce filter...............................................................................................59
4.1.2 Oscillation filter.................................................................................................................. 59
4.1.3 Settings............................................................................................................................. 59
4.1.3.1 Setting parameters for binary input modules............................................................... 59
4.1.3.2 Setting parameters for binary input/output module...................................................... 60

Section 5 Local Human-Machine-Interface LHMI.......................................................61


5.1 Local HMI screen behaviour................................................................................................61
5.1.1 Identification...................................................................................................................... 61
5.1.2 Settings............................................................................................................................. 61
5.2 Local HMI signals................................................................................................................ 61
5.2.1 Identification...................................................................................................................... 61

Transformer protection RET650 1


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

5.2.2 Function block................................................................................................................... 61


5.2.3 Signals...............................................................................................................................61
5.3 Basic part for LED indication module.................................................................................. 62
5.3.1 Identification...................................................................................................................... 62
5.3.2 Function block................................................................................................................... 62
5.3.3 Signals...............................................................................................................................62
5.3.4 Settings............................................................................................................................. 63
5.4 LCD part for HMI function keys control module ..................................................................63
5.4.1 Identification...................................................................................................................... 63
5.4.2 Function block................................................................................................................... 64
5.4.3 Signals...............................................................................................................................64
5.4.4 Settings............................................................................................................................. 64
5.5 Operation principle.............................................................................................................. 65
5.5.1 Local HMI.......................................................................................................................... 65
5.5.1.1 Keypad......................................................................................................................... 66
5.5.1.2 Display......................................................................................................................... 68
5.5.1.3 LEDs............................................................................................................................ 70
5.5.2 LED configuration alternatives.......................................................................................... 71
5.5.2.1 Functionality ................................................................................................................ 71
5.5.2.2 Status LEDs................................................................................................................. 71
5.5.2.3 Indication LEDs............................................................................................................ 72
5.5.3 Function keys.................................................................................................................... 79
5.5.3.1 Functionality ................................................................................................................ 79
5.5.3.2 Operation principle ...................................................................................................... 79
5.5.3.3 Enabling and Disabling Authority on Function keys..................................................... 80

Section 6 Differential protection................................................................................. 81


6.1 Transformer differential protection T2WPDIF and T3WPDIF ............................................. 81
6.1.1 Identification...................................................................................................................... 81
6.1.2 Functionality ..................................................................................................................... 81
6.1.3 Function block................................................................................................................... 83
6.1.4 Signals...............................................................................................................................84
6.1.5 Settings............................................................................................................................. 86
6.1.6 Monitored data.................................................................................................................. 91
6.1.7 Operation principle............................................................................................................ 91
6.1.7.1 Function calculation principles..................................................................................... 92
6.1.7.2 Logic diagram.............................................................................................................108
6.1.8 Technical data..................................................................................................................112
6.2 High impedance differential protection, single phase HZPDIF ......................................... 113
6.2.1 Identification.................................................................................................................... 113
6.2.2 Functionality ................................................................................................................... 113
6.2.3 Function block................................................................................................................. 114
6.2.4 Signals.............................................................................................................................114
6.2.5 Settings............................................................................................................................114
6.2.6 Monitored data.................................................................................................................114
6.2.7 Operation principle.......................................................................................................... 115

2 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

6.2.7.1 Logic diagram.............................................................................................................116


6.2.8 Technical data..................................................................................................................117
6.3 Low impedance restricted earth fault protection REFPDIF .............................................. 117
6.3.1 Identification.................................................................................................................... 117
6.3.2 Functionality.................................................................................................................... 117
6.3.3 Function block................................................................................................................. 118
6.3.4 Signals.............................................................................................................................118
6.3.5 Settings............................................................................................................................118
6.3.6 Monitored data.................................................................................................................119
6.3.7 Operation principle.......................................................................................................... 119
6.3.7.1 Fundamental principles of the restricted earth fault protection...................................119
6.3.7.2 Restricted earth fault protection, low impedance differential protection ....................121
6.3.7.3 Calculation of differential current and bias current.....................................................122
6.3.7.4 Detection of external earth faults............................................................................... 123
6.3.7.5 Algorithm of the restricted earth fault protection........................................................ 125
6.3.8 Technical data................................................................................................................. 125

Section 7 Current protection..................................................................................... 127


7.1 Instantaneous phase overcurrent protection PHPIOC ..................................................... 127
7.1.1 Identification.................................................................................................................... 127
7.1.2 Functionality ................................................................................................................... 127
7.1.3 Function block................................................................................................................. 127
7.1.4 Signals.............................................................................................................................127
7.1.5 Settings........................................................................................................................... 127
7.1.6 Monitored data................................................................................................................ 128
7.1.7 Operation principle ......................................................................................................... 128
7.1.8 Technical data................................................................................................................. 129
7.2 Directional phase overcurrent protection, four steps OC4PTOC ..................................... 129
7.2.1 Function revision history..................................................................................................129
7.2.2 Identification.................................................................................................................... 130
7.2.3 Functionality ................................................................................................................... 130
7.2.4 Function block................................................................................................................. 131
7.2.5 Signals.............................................................................................................................131
7.2.6 Settings........................................................................................................................... 133
7.2.7 Monitored data................................................................................................................ 138
7.2.8 Operation principle.......................................................................................................... 138
7.2.9 Technical data................................................................................................................. 144
7.3 Instantaneous residual overcurrent protection EFPIOC ...................................................145
7.3.1 Identification.................................................................................................................... 145
7.3.2 Functionality ................................................................................................................... 145
7.3.3 Function block................................................................................................................. 145
7.3.4 Signals.............................................................................................................................145
7.3.5 Settings........................................................................................................................... 146
7.3.6 Monitored data................................................................................................................ 146
7.3.7 Operation principle ......................................................................................................... 146
7.3.8 Technical data................................................................................................................. 147

Transformer protection RET650 3


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

7.4 Directional residual overcurrent protection, four steps EF4PTOC ................................... 148
7.4.1 Function revision history..................................................................................................148
7.4.2 Identification.................................................................................................................... 148
7.4.3 Functionality ................................................................................................................... 148
7.4.4 Function block................................................................................................................. 149
7.4.5 Signals.............................................................................................................................149
7.4.6 Settings........................................................................................................................... 150
7.4.7 Monitored data................................................................................................................ 156
7.4.8 Operation principle.......................................................................................................... 156
7.4.8.1 Operating quantity within the function........................................................................ 156
7.4.8.2 Internal polarizing.......................................................................................................157
7.4.8.3 External polarizing for earth-fault function..................................................................159
7.4.8.4 Directional detection for earth fault function ..............................................................159
7.4.8.5 Base quantities within the protection..........................................................................159
7.4.8.6 Internal earth-fault protection structure...................................................................... 159
7.4.8.7 Four residual overcurrent steps................................................................................. 159
7.4.8.8 Directional supervision element with integrated directional comparison function...... 161
7.4.8.9 Second harmonic blocking element........................................................................... 163
7.4.8.10 Switch on to fault feature............................................................................................165
7.4.8.11 Phase selection element............................................................................................ 167
7.4.9 Technical data................................................................................................................. 168
7.5 Four step directional negative phase sequence overcurrent protection NS4PTOC .........169
7.5.1 Function revision history..................................................................................................169
7.5.2 Identification.................................................................................................................... 169
7.5.3 Functionality ................................................................................................................... 169
7.5.4 Function block................................................................................................................. 170
7.5.5 Signals.............................................................................................................................170
7.5.6 Settings........................................................................................................................... 171
7.5.7 Monitored data................................................................................................................ 175
7.5.8 Operation principle ......................................................................................................... 175
7.5.8.1 Operating quantity within the function........................................................................ 175
7.5.8.2 Internal polarizing facility of the function.................................................................... 176
7.5.8.3 External polarizing for negative sequence function....................................................176
7.5.8.4 Internal negative sequence protection structure........................................................ 176
7.5.8.5 Four negative sequence overcurrent stages..............................................................177
7.5.8.6 Directional supervision element with integrated directional comparison function...... 178
7.5.9 Technical data................................................................................................................. 179
7.6 Thermal overload protection, two time constants TRPTTR ..............................................180
7.6.1 Identification.................................................................................................................... 180
7.6.2 Functionality ................................................................................................................... 180
7.6.3 Function block................................................................................................................. 180
7.6.4 Signals.............................................................................................................................181
7.6.5 Settings........................................................................................................................... 181
7.6.6 Monitored data................................................................................................................ 182
7.6.7 Operation principle ......................................................................................................... 182
7.6.8 Technical data................................................................................................................. 186

4 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

7.7 Breaker failure protection CCRBRF ................................................................................. 186


7.7.1 Function revision history..................................................................................................186
7.7.2 Identification.................................................................................................................... 186
7.7.3 Functionality ................................................................................................................... 187
7.7.4 Function block................................................................................................................. 187
7.7.5 Signals.............................................................................................................................187
7.7.6 Settings........................................................................................................................... 188
7.7.7 Monitored data................................................................................................................ 189
7.7.8 Operation principle ......................................................................................................... 189
7.7.9 Technical data................................................................................................................. 194
7.8 Overcurrent protection with binary release BRPTOC........................................................194
7.8.1 Function revision history..................................................................................................194
7.8.2 Identification.................................................................................................................... 195
7.8.3 Functionality ................................................................................................................... 195
7.8.4 Function block................................................................................................................. 195
7.8.5 Signals.............................................................................................................................195
7.8.6 Settings........................................................................................................................... 196
7.8.7 Monitored data................................................................................................................ 196
7.8.8 Operation principle.......................................................................................................... 196
7.8.9 Technical data................................................................................................................. 197
7.9 Pole discordance protection CCPDSC..............................................................................198
7.9.1 Identification.................................................................................................................... 198
7.9.2 Functionality ................................................................................................................... 199
7.9.3 Function block................................................................................................................. 199
7.9.4 Signals.............................................................................................................................199
7.9.5 Settings........................................................................................................................... 200
7.9.6 Monitored data................................................................................................................ 200
7.9.7 Operation principle.......................................................................................................... 200
7.9.7.1 Pole discordance signaling from circuit breaker ........................................................202
7.9.7.2 Unsymmetrical current detection................................................................................203
7.9.8 Technical data................................................................................................................. 203
7.10 Directional underpower protection GUPPDUP..................................................................203
7.10.1 Identification.................................................................................................................... 203
7.10.2 Functionality ................................................................................................................... 203
7.10.3 Function block................................................................................................................. 204
7.10.4 Signals.............................................................................................................................204
7.10.5 Settings........................................................................................................................... 205
7.10.6 Monitored data................................................................................................................ 206
7.10.7 Operation principle.......................................................................................................... 206
7.10.7.1 Low pass filtering....................................................................................................... 208
7.10.7.2 Calibration of analog inputs........................................................................................208
7.10.8 Technical data................................................................................................................. 209
7.11 Directional overpower protection GOPPDOP ...................................................................209
7.11.1 Identification.................................................................................................................... 210
7.11.2 Functionality.................................................................................................................... 210
7.11.3 Function block................................................................................................................. 211

Transformer protection RET650 5


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

7.11.4 Signals.............................................................................................................................211
7.11.5 Settings........................................................................................................................... 212
7.11.6 Monitored data................................................................................................................ 213
7.11.7 Operation principle.......................................................................................................... 213
7.11.7.1 Low pass filtering....................................................................................................... 215
7.11.7.2 Calibration of analog inputs........................................................................................215
7.11.8 Technical data................................................................................................................. 216

Section 8 Voltage protection..................................................................................... 217


8.1 Two step undervoltage protection UV2PTUV ...................................................................217
8.1.1 Identification.................................................................................................................... 217
8.1.2 Functionality ................................................................................................................... 217
8.1.3 Function block................................................................................................................. 217
8.1.4 Signals.............................................................................................................................218
8.1.5 Settings........................................................................................................................... 218
8.1.6 Monitored data................................................................................................................ 220
8.1.7 Operation principle ......................................................................................................... 220
8.1.7.1 Measurement principle...............................................................................................221
8.1.7.2 Time delay..................................................................................................................221
8.1.7.3 Blocking......................................................................................................................226
8.1.7.4 Design........................................................................................................................ 227
8.1.8 Technical data................................................................................................................. 228
8.2 Two step overvoltage protection OV2PTOV .....................................................................228
8.2.1 Identification.................................................................................................................... 228
8.2.2 Functionality OV2PTOV ................................................................................................. 228
8.2.3 Function block................................................................................................................. 229
8.2.4 Signals.............................................................................................................................229
8.2.5 Settings........................................................................................................................... 230
8.2.6 Monitored data................................................................................................................ 232
8.2.7 Operation principle ......................................................................................................... 232
8.2.7.1 Measurement principle...............................................................................................232
8.2.7.2 Time delay..................................................................................................................233
8.2.7.3 Blocking......................................................................................................................238
8.2.7.4 Design........................................................................................................................ 238
8.2.8 Technical data................................................................................................................. 239
8.3 Two step residual overvoltage protection ROV2PTOV .................................................... 240
8.3.1 Function revision history..................................................................................................240
8.3.2 Identification.................................................................................................................... 240
8.3.3 Functionality ................................................................................................................... 240
8.3.4 Function block................................................................................................................. 241
8.3.5 Signals.............................................................................................................................241
8.3.6 Settings........................................................................................................................... 241
8.3.7 Monitored data................................................................................................................ 243
8.3.8 Operation principle.......................................................................................................... 243
8.3.8.1 Measurement principle...............................................................................................243
8.3.8.2 Time delay..................................................................................................................243

6 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

8.3.8.3 Blocking......................................................................................................................249
8.3.8.4 Design........................................................................................................................ 249
8.3.9 Technical data................................................................................................................. 250
8.4 Overexcitation protection OEXPVPH ............................................................................... 250
8.4.1 Identification.................................................................................................................... 250
8.4.2 Functionality ................................................................................................................... 250
8.4.3 Function block................................................................................................................. 251
8.4.4 Signals.............................................................................................................................251
8.4.5 Settings........................................................................................................................... 251
8.4.6 Monitored data................................................................................................................ 252
8.4.7 Operation principle.......................................................................................................... 252
8.4.7.1 Measured voltage.......................................................................................................254
8.4.7.2 Operate time of the overexcitation protection............................................................ 255
8.4.7.3 Cooling....................................................................................................................... 258
8.4.7.4 Overexcitation protection function measurands......................................................... 258
8.4.7.5 Overexcitation alarm.................................................................................................. 259
8.4.7.6 Logic diagram.............................................................................................................259
8.4.8 Technical data................................................................................................................. 259
8.5 Voltage differential protection VDCPTDV .........................................................................260
8.5.1 Function revision history..................................................................................................260
8.5.2 Identification.................................................................................................................... 260
8.5.3 Functionality ................................................................................................................... 260
8.5.4 Function block................................................................................................................. 261
8.5.5 Signals.............................................................................................................................261
8.5.6 Settings........................................................................................................................... 261
8.5.7 Monitored data................................................................................................................ 262
8.5.8 Operation principle.......................................................................................................... 262
8.5.9 Technical data................................................................................................................. 263
8.6 Loss of voltage check LOVPTUV ..................................................................................... 264
8.6.1 Identification.................................................................................................................... 264
8.6.2 Functionality ................................................................................................................... 264
8.6.3 Function block................................................................................................................. 264
8.6.4 Signals.............................................................................................................................264
8.6.5 Settings........................................................................................................................... 265
8.6.6 Operation principle.......................................................................................................... 265
8.6.7 Technical data................................................................................................................. 266

Section 9 Frequency protection................................................................................ 267


9.1 Underfrequency protection SAPTUF ................................................................................267
9.1.1 Identification.................................................................................................................... 267
9.1.2 Functionality ................................................................................................................... 267
9.1.3 Function block................................................................................................................. 267
9.1.4 Signals.............................................................................................................................267
9.1.5 Settings........................................................................................................................... 268
9.1.6 Operation principle.......................................................................................................... 268
9.1.6.1 Measurement principle...............................................................................................269

Transformer protection RET650 7


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

9.1.6.2 Time delay..................................................................................................................269


9.1.6.3 Voltage dependent time delay....................................................................................269
9.1.6.4 Blocking......................................................................................................................270
9.1.6.5 Design........................................................................................................................ 271
9.1.7 Technical data................................................................................................................. 272
9.2 Overfrequency protection SAPTOF ..................................................................................272
9.2.1 Identification.................................................................................................................... 273
9.2.2 Functionality ................................................................................................................... 273
9.2.3 Function block................................................................................................................. 273
9.2.4 Signals.............................................................................................................................273
9.2.5 Settings........................................................................................................................... 274
9.2.6 Operation principle.......................................................................................................... 274
9.2.6.1 Measurement principle...............................................................................................274
9.2.6.2 Time delay..................................................................................................................274
9.2.6.3 Blocking......................................................................................................................275
9.2.6.4 Design........................................................................................................................ 275
9.2.7 Technical data................................................................................................................. 276
9.3 Rate-of-change of frequency protection SAPFRC ........................................................... 276
9.3.1 Identification.................................................................................................................... 276
9.3.2 Functionality ................................................................................................................... 276
9.3.3 Function block................................................................................................................. 277
9.3.4 Signals.............................................................................................................................277
9.3.5 Settings........................................................................................................................... 277
9.3.6 Operation principle.......................................................................................................... 278
9.3.6.1 Measurement principle...............................................................................................278
9.3.6.2 Time delay..................................................................................................................278
9.3.6.3 Blocking......................................................................................................................278
9.3.6.4 Design........................................................................................................................ 279
9.3.7 Technical data................................................................................................................. 280

Section 10 Secondary system supervision................................................................283


10.1 Current circuit supervision CCSSPVC ............................................................................. 283
10.1.1 Identification.................................................................................................................... 283
10.1.2 Functionality ................................................................................................................... 283
10.1.3 Function block................................................................................................................. 283
10.1.4 Signals.............................................................................................................................283
10.1.5 Settings........................................................................................................................... 284
10.1.6 Operation principle.......................................................................................................... 284
10.1.7 Technical data................................................................................................................. 285
10.2 Fuse failure supervision FUFSPVC...................................................................................286
10.2.1 Identification.................................................................................................................... 286
10.2.2 Functionality ................................................................................................................... 286
10.2.3 Function block................................................................................................................. 286
10.2.4 Signals.............................................................................................................................286
10.2.5 Settings........................................................................................................................... 287
10.2.6 Monitored data................................................................................................................ 288

8 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

10.2.7 Operation principle.......................................................................................................... 288


10.2.7.1 Zero and negative sequence detection...................................................................... 288
10.2.7.2 Delta current and delta voltage detection...................................................................290
10.2.7.3 Dead line detection.................................................................................................... 292
10.2.7.4 Main logic................................................................................................................... 293
10.2.8 Technical data................................................................................................................. 296
10.3 Voltage based delta supervision DELVSPVC....................................................................296
10.3.1 Identification.................................................................................................................... 296
10.3.2 Functionality.................................................................................................................... 296
10.3.3 Function block................................................................................................................. 297
10.3.4 Signals.............................................................................................................................297
10.3.5 Settings........................................................................................................................... 298
10.3.6 Monitored data................................................................................................................ 298
10.3.7 Operation principle.......................................................................................................... 298
10.3.7.1 Minimum signal level check....................................................................................... 299
10.3.7.2 Mode of operation...................................................................................................... 299
10.3.7.3 Instantaneous 1 cycle / 2 cycle ................................................................................. 299
10.3.7.4 RMS/DFT based supervision..................................................................................... 300
10.3.7.5 Angle based supervision or vector shift supervision.................................................. 300
10.3.8 Technical data................................................................................................................. 302
10.4 Current based delta supervision DELISPVC.....................................................................302
10.4.1 Identification.................................................................................................................... 302
10.4.2 Functionality.................................................................................................................... 302
10.4.3 Function block................................................................................................................. 303
10.4.4 Signals.............................................................................................................................303
10.4.5 Settings........................................................................................................................... 304
10.4.6 Monitored data................................................................................................................ 304
10.4.7 Operation principle.......................................................................................................... 304
10.4.7.1 Minimum signal level check....................................................................................... 305
10.4.7.2 Mode of operation...................................................................................................... 305
10.4.7.3 Instantaneous 1 cycle / 2 cycle ................................................................................. 305
10.4.7.4 RMS/DFT based supervision..................................................................................... 306
10.4.7.5 2nd Harmonic blocking................................................................................................306
10.4.7.6 3rd Harmonic based adaption.....................................................................................307
10.4.8 Technical data................................................................................................................. 308
10.5 Delta supervision of real input DELSPVC......................................................................... 308
10.5.1 Identification.................................................................................................................... 308
10.5.2 Functionality.................................................................................................................... 308
10.5.3 Function block................................................................................................................. 308
10.5.4 Signals.............................................................................................................................309
10.5.5 Settings........................................................................................................................... 309
10.5.6 Operation principle.......................................................................................................... 309

Section 11 Control........................................................................................................ 311


11.1 Synchrocheck, energizing check, and synchronizing SESRSYN......................................311
11.1.1 Identification.................................................................................................................... 311

Transformer protection RET650 9


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

11.1.2 Functionality ................................................................................................................... 311


11.1.3 Function block................................................................................................................. 312
11.1.4 Signals.............................................................................................................................312
11.1.5 Settings........................................................................................................................... 314
11.1.6 Monitored data................................................................................................................ 316
11.1.7 Operation principle.......................................................................................................... 316
11.1.7.1 Basic functionality...................................................................................................... 316
11.1.7.2 Logic diagrams...........................................................................................................317
11.1.8 Technical data................................................................................................................. 326
11.2 Interlocking ....................................................................................................................... 327
11.2.1 Functionality ................................................................................................................... 327
11.2.2 Operation principle ......................................................................................................... 328
11.2.3 Logical node for interlocking SCILO ...............................................................................330
11.2.3.1 Identification............................................................................................................... 330
11.2.3.2 Functionality .............................................................................................................. 330
11.2.3.3 Function block............................................................................................................ 330
11.2.3.4 Signals....................................................................................................................... 330
11.2.3.5 Logic diagram.............................................................................................................331
11.2.4 Interlocking for busbar earthing switch BB_ES .............................................................. 331
11.2.4.1 Identification............................................................................................................... 331
11.2.4.2 Functionality .............................................................................................................. 331
11.2.4.3 Function block............................................................................................................ 332
11.2.4.4 Logic diagram.............................................................................................................332
11.2.4.5 Signals....................................................................................................................... 332
11.2.5 Interlocking for line bay ABC_LINE ................................................................................ 332
11.2.5.1 Identification............................................................................................................... 333
11.2.5.2 Functionality .............................................................................................................. 333
11.2.5.3 Function block............................................................................................................ 334
11.2.5.4 Logic diagram.............................................................................................................335
11.2.5.5 Signals....................................................................................................................... 340
11.2.6 Interlocking for transformer bay AB_TRAFO ..................................................................342
11.2.6.1 Identification............................................................................................................... 342
11.2.6.2 Functionality .............................................................................................................. 342
11.2.6.3 Function block............................................................................................................ 343
11.2.6.4 Logic diagram.............................................................................................................343
11.2.6.5 Signals....................................................................................................................... 345
11.2.7 Position evaluation POS_EVAL.......................................................................................346
11.2.7.1 Identification............................................................................................................... 346
11.2.7.2 Functionality .............................................................................................................. 346
11.2.7.3 Function block............................................................................................................ 346
11.2.7.4 Logic diagram.............................................................................................................346
11.2.7.5 Signals....................................................................................................................... 347
11.3 Apparatus control.............................................................................................................. 347
11.3.1 Functionality ................................................................................................................... 347
11.3.2 Operation principle.......................................................................................................... 348
11.3.3 Error handling..................................................................................................................349

10 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

11.3.4 Bay control QCBAY......................................................................................................... 351


11.3.4.1 Functionality .............................................................................................................. 352
11.3.4.2 Function block............................................................................................................ 352
11.3.4.3 Signals....................................................................................................................... 352
11.3.4.4 Settings...................................................................................................................... 352
11.3.4.5 Operation principle..................................................................................................... 353
11.3.5 Local/Remote switch LOCREM.......................................................................................354
11.3.5.1 Function block............................................................................................................ 355
11.3.5.2 Signals....................................................................................................................... 355
11.3.5.3 Settings...................................................................................................................... 356
11.3.5.4 Operation principle..................................................................................................... 356
11.3.6 Switch controller SCSWI................................................................................................. 357
11.3.6.1 Functionality .............................................................................................................. 357
11.3.6.2 Function block............................................................................................................ 358
11.3.6.3 Signals....................................................................................................................... 358
11.3.6.4 Settings...................................................................................................................... 360
11.3.6.5 Operation principle..................................................................................................... 360
11.3.6.6 Interaction with switch on process bus.......................................................................365
11.3.7 Circuit breaker SXCBR....................................................................................................366
11.3.7.1 Functionality .............................................................................................................. 366
11.3.7.2 Function block............................................................................................................ 366
11.3.7.3 Signals....................................................................................................................... 366
11.3.7.4 Settings...................................................................................................................... 367
11.3.7.5 Operation principle..................................................................................................... 367
11.3.8 Circuit switch SXSWI.......................................................................................................370
11.3.8.1 Functionality .............................................................................................................. 371
11.3.8.2 Function block............................................................................................................ 371
11.3.8.3 Signals....................................................................................................................... 371
11.3.8.4 Settings...................................................................................................................... 372
11.3.8.5 Operation principle..................................................................................................... 372
11.3.9 Proxy for signals from switching device via GOOSE XLNPROXY ................................. 376
11.3.9.1 Functionality .............................................................................................................. 376
11.3.9.2 Function block............................................................................................................ 376
11.3.9.3 Signals....................................................................................................................... 376
11.3.9.4 Settings...................................................................................................................... 377
11.3.9.5 Operation principle..................................................................................................... 378
11.3.9.6 Position supervision................................................................................................... 378
11.3.9.7 Command response evaluation................................................................................. 378
11.3.10 Bay reserve QCRSV....................................................................................................... 379
11.3.10.1 Functionality .............................................................................................................. 379
11.3.10.2 Function block............................................................................................................ 380
11.3.10.3 Signals....................................................................................................................... 380
11.3.10.4 Settings...................................................................................................................... 381
11.3.10.5 Operation principle..................................................................................................... 381
11.3.11 Reservation input RESIN................................................................................................ 383
11.3.11.1 Functionality .............................................................................................................. 383

Transformer protection RET650 11


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

11.3.11.2 Function block............................................................................................................ 383


11.3.11.3 Signals....................................................................................................................... 383
11.3.11.4 Settings...................................................................................................................... 384
11.3.11.5 Operation principle..................................................................................................... 384
11.4 Voltage control...................................................................................................................386
11.4.1 Function revision history..................................................................................................386
11.4.2 Identification.................................................................................................................... 386
11.4.3 Functionality ................................................................................................................... 387
11.4.4 Automatic voltage control for tap changer, TR1ATCC ....................................................387
11.4.4.1 Operation principle..................................................................................................... 387
11.4.5 Tap changer control and supervision, 6 binary inputs TCMYLTC .................................. 389
11.4.5.1 Operation principle..................................................................................................... 389
11.4.6 Function block................................................................................................................. 393
11.4.7 Signals.............................................................................................................................394
11.4.8 Settings........................................................................................................................... 396
11.4.9 Monitored data................................................................................................................ 399
11.4.10 Operation principle.......................................................................................................... 399
11.4.11 Technical data................................................................................................................. 400
11.5 Logic rotating switch for function selection and LHMI presentation SLGAPC...................401
11.5.1 Identification.................................................................................................................... 401
11.5.2 Functionality ................................................................................................................... 401
11.5.3 Function block................................................................................................................. 402
11.5.4 Signals.............................................................................................................................402
11.5.5 Settings........................................................................................................................... 403
11.5.6 Monitored data................................................................................................................ 403
11.5.7 Operation principle.......................................................................................................... 404
11.5.7.1 Graphical display........................................................................................................404
11.6 Selector mini switch VSGAPC...........................................................................................405
11.6.1 Identification.................................................................................................................... 405
11.6.2 Functionality ................................................................................................................... 405
11.6.3 Function block................................................................................................................. 406
11.6.4 Signals.............................................................................................................................406
11.6.5 Settings........................................................................................................................... 406
11.6.6 Operation principle.......................................................................................................... 407
11.7 Generic communication function for double point indication DPGAPC.............................407
11.7.1 Identification.................................................................................................................... 407
11.7.2 Functionality ................................................................................................................... 407
11.7.3 Function block................................................................................................................. 408
11.7.4 Signals.............................................................................................................................408
11.7.5 Settings........................................................................................................................... 408
11.7.6 Operation principle.......................................................................................................... 408
11.8 Single point generic control 8 signals SPC8GAPC........................................................... 409
11.8.1 Identification.................................................................................................................... 409
11.8.2 Functionality ................................................................................................................... 409
11.8.3 Function block................................................................................................................. 409
11.8.4 Signals.............................................................................................................................409

12 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

11.8.5 Settings........................................................................................................................... 410


11.8.6 Operation principle.......................................................................................................... 410
11.9 AutomationBits, command function for DNP3.0 AUTOBITS............................................. 411
11.9.1 Identification.................................................................................................................... 411
11.9.2 Functionality ................................................................................................................... 411
11.9.3 Function block................................................................................................................. 411
11.9.4 Signals.............................................................................................................................412
11.9.5 Settings........................................................................................................................... 413
11.9.6 Operation principle ......................................................................................................... 413
11.10 Single command, 16 inputs SINGLECMD.........................................................................413
11.10.1 Identification.................................................................................................................... 413
11.10.2 Functionality ................................................................................................................... 413
11.10.3 Function block................................................................................................................. 414
11.10.4 Signals.............................................................................................................................414
11.10.5 Settings........................................................................................................................... 415
11.10.6 Operation principle.......................................................................................................... 415

Section 12 Logic........................................................................................................... 417


12.1 Tripping logic SMPPTRC ..................................................................................................417
12.1.1 Function revision history..................................................................................................417
12.1.2 Identification.................................................................................................................... 417
12.1.3 Functionality ................................................................................................................... 417
12.1.4 Function block................................................................................................................. 418
12.1.5 Signals.............................................................................................................................418
12.1.6 Settings........................................................................................................................... 420
12.1.7 Operation principle.......................................................................................................... 420
12.1.7.1 Logic diagram.............................................................................................................425
12.1.8 Technical data................................................................................................................. 428
12.2 General start matrix block SMAGAPC.............................................................................. 429
12.2.1 Identification.................................................................................................................... 429
12.2.2 Functionality ................................................................................................................... 429
12.2.3 Function block................................................................................................................. 429
12.2.4 Signals.............................................................................................................................429
12.2.5 Settings........................................................................................................................... 430
12.2.6 Operation principle.......................................................................................................... 430
12.3 Trip matrix logic TMAGAPC.............................................................................................. 434
12.3.1 Identification.................................................................................................................... 434
12.3.2 Functionality ................................................................................................................... 435
12.3.3 Function block................................................................................................................. 435
12.3.4 Signals.............................................................................................................................435
12.3.5 Settings........................................................................................................................... 436
12.3.6 Operation principle.......................................................................................................... 437
12.3.7 Technical data................................................................................................................. 438
12.4 Logic for group alarm ALMCALH...................................................................................... 438
12.4.1 Identification.................................................................................................................... 438
12.4.2 Functionality ................................................................................................................... 438

Transformer protection RET650 13


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

12.4.3 Function block................................................................................................................. 438


12.4.4 Signals.............................................................................................................................438
12.4.5 Settings........................................................................................................................... 439
12.4.6 Operation principle.......................................................................................................... 439
12.4.7 Technical data................................................................................................................. 440
12.5 Logic for group warning WRNCALH..................................................................................440
12.5.1 Identification.................................................................................................................... 440
12.5.2 Functionality ................................................................................................................... 440
12.5.3 Function block................................................................................................................. 440
12.5.4 Signals.............................................................................................................................440
12.5.5 Settings........................................................................................................................... 441
12.5.6 Operation principle.......................................................................................................... 441
12.5.7 Technical data................................................................................................................. 442
12.6 Logic for group indication INDCALH................................................................................. 442
12.6.1 Identification.................................................................................................................... 442
12.6.2 Functionality ................................................................................................................... 442
12.6.3 Function block................................................................................................................. 442
12.6.4 Signals.............................................................................................................................442
12.6.5 Settings........................................................................................................................... 443
12.6.6 Operation principle.......................................................................................................... 443
12.6.7 Technical data................................................................................................................. 443
12.7 Basic configurable logic blocks......................................................................................... 444
12.7.1 AND function block..........................................................................................................444
12.7.1.1 Function block............................................................................................................ 444
12.7.1.2 Signals....................................................................................................................... 445
12.7.1.3 Technical data............................................................................................................ 445
12.7.2 Controllable gate function block GATE............................................................................445
12.7.2.1 Function block............................................................................................................ 445
12.7.2.2 Signals....................................................................................................................... 445
12.7.2.3 Settings...................................................................................................................... 446
12.7.2.4 Technical data............................................................................................................ 446
12.7.3 Inverter function block INV.............................................................................................. 446
12.7.3.1 Function block............................................................................................................ 446
12.7.3.2 Signals....................................................................................................................... 446
12.7.3.3 Technical data............................................................................................................ 446
12.7.4 Loop delay function block LLD........................................................................................ 446
12.7.4.1 Function block............................................................................................................ 447
12.7.4.2 Signals....................................................................................................................... 447
12.7.4.3 Technical data............................................................................................................ 447
12.7.5 OR function block............................................................................................................447
12.7.5.1 Function block............................................................................................................ 447
12.7.5.2 Signals....................................................................................................................... 448
12.7.5.3 Technical data............................................................................................................ 448
12.7.6 Pulse timer function block PULSETIMER....................................................................... 448
12.7.6.1 Function block............................................................................................................ 448
12.7.6.2 Signals....................................................................................................................... 448

14 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

12.7.6.3 Settings...................................................................................................................... 449


12.7.6.4 Technical data............................................................................................................ 449
12.7.7 Reset-set with memory function block RSMEMORY...................................................... 449
12.7.7.1 Function block............................................................................................................ 449
12.7.7.2 Signals....................................................................................................................... 450
12.7.7.3 Settings...................................................................................................................... 450
12.7.7.4 Technical data............................................................................................................ 450
12.7.8 Set-reset with memory function block SRMEMORY....................................................... 450
12.7.8.1 Function block............................................................................................................ 451
12.7.8.2 Signals....................................................................................................................... 451
12.7.8.3 Settings...................................................................................................................... 451
12.7.8.4 Technical data............................................................................................................ 451
12.7.9 Settable timer function block TIMERSET........................................................................ 451
12.7.9.1 Function block............................................................................................................ 452
12.7.9.2 Signals....................................................................................................................... 452
12.7.9.3 Settings...................................................................................................................... 452
12.7.9.4 Technical data............................................................................................................ 453
12.7.10 Exclusive OR function block XOR................................................................................... 453
12.7.10.1 Function block............................................................................................................ 453
12.7.10.2 Signals....................................................................................................................... 453
12.7.10.3 Technical data............................................................................................................ 454
12.8 Extension logic package....................................................................................................454
12.9 Fixed signals FXDSIGN.................................................................................................... 454
12.9.1 Functionality ................................................................................................................... 454
12.9.2 Function block................................................................................................................. 454
12.9.3 Signals.............................................................................................................................454
12.9.4 Settings........................................................................................................................... 455
12.9.5 Operation principle.......................................................................................................... 455
12.10 Boolean 16 to Integer conversion B16I............................................................................. 455
12.10.1 Identification.................................................................................................................... 455
12.10.2 Functionality ................................................................................................................... 455
12.10.3 Function block................................................................................................................. 456
12.10.4 Signals.............................................................................................................................456
12.10.5 Monitored data................................................................................................................ 457
12.10.6 Settings........................................................................................................................... 457
12.10.7 Operation principle.......................................................................................................... 457
12.10.8 Technical data................................................................................................................. 458
12.11 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC............458
12.11.1 Identification.................................................................................................................... 458
12.11.2 Functionality ................................................................................................................... 458
12.11.3 Function block................................................................................................................. 458
12.11.4 Signals.............................................................................................................................459
12.11.5 Settings........................................................................................................................... 459
12.11.6 Monitored data................................................................................................................ 459
12.11.7 Operation principle.......................................................................................................... 459
12.11.8 Technical data................................................................................................................. 460

Transformer protection RET650 15


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

12.12 Integer to boolean 16 conversion IB16..............................................................................460


12.12.1 Identification.................................................................................................................... 460
12.12.2 Functionality ................................................................................................................... 460
12.12.3 Function block................................................................................................................. 461
12.12.4 Signals.............................................................................................................................461
12.12.5 Setting parameters .........................................................................................................461
12.12.6 Operation principle.......................................................................................................... 462
12.12.7 Technical data................................................................................................................. 463
12.13 Integer to boolean conversion with logical node representation, 16 bit ITBGAPC............463
12.13.1 Identification.................................................................................................................... 463
12.13.2 Functionality ................................................................................................................... 463
12.13.3 Function block................................................................................................................. 463
12.13.4 Signals.............................................................................................................................464
12.13.5 Settings........................................................................................................................... 464
12.13.6 Operation principle.......................................................................................................... 464
12.13.7 Technical data................................................................................................................. 465
12.14 Elapsed time integrator with limit transgression and overflow supervision TEIGAPC.......465
12.14.1 Identification.................................................................................................................... 465
12.14.2 Functionality.................................................................................................................... 466
12.14.3 Function block................................................................................................................. 466
12.14.4 Signals.............................................................................................................................466
12.14.5 Settings........................................................................................................................... 467
12.14.6 Operation principle.......................................................................................................... 467
12.14.6.1 Operation accuracy.................................................................................................... 468
12.14.6.2 Memory storage......................................................................................................... 468
12.14.7 Technical data................................................................................................................. 469
12.15 Comparator for integer inputs INTCOMP.......................................................................... 469
12.15.1 Identification.................................................................................................................... 469
12.15.2 Functionality ................................................................................................................... 469
12.15.3 Function block................................................................................................................. 469
12.15.4 Signals.............................................................................................................................469
12.15.5 Settings........................................................................................................................... 470
12.15.6 Monitored data................................................................................................................ 470
12.15.7 Operation principle.......................................................................................................... 470
12.16 Comparator for real inputs REALCOMP........................................................................... 471
12.16.1 Identification.................................................................................................................... 471
12.16.2 Functionality ................................................................................................................... 471
12.16.3 Function block................................................................................................................. 471
12.16.4 Signals.............................................................................................................................471
12.16.5 Settings........................................................................................................................... 471
12.16.6 Operation principle.......................................................................................................... 471
12.16.7 Technical data................................................................................................................. 472
12.17 Hold maximum and minimum of input HOLDMINMAX......................................................473
12.17.1 Identification.................................................................................................................... 473
12.17.2 Functionality ................................................................................................................... 473
12.17.3 Function block................................................................................................................. 473

16 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

12.17.4 Signals.............................................................................................................................473
12.18 Converter for Integer to Real INT_REAL...........................................................................474
12.18.1 Identification.................................................................................................................... 474
12.18.2 Functionality ................................................................................................................... 474
12.18.3 Function block................................................................................................................. 474
12.18.4 Signals.............................................................................................................................474
12.19 Definable constant for logic function CONST_INT............................................................ 474
12.19.1 Identification.................................................................................................................... 474
12.19.2 Functionality ................................................................................................................... 474
12.19.3 Function block................................................................................................................. 475
12.19.4 Signals.............................................................................................................................475
12.19.5 Settings........................................................................................................................... 475
12.20 Analog input selector for integer values INTSEL...............................................................475
12.20.1 Identification.................................................................................................................... 475
12.20.2 Functionality ................................................................................................................... 475
12.20.3 Function block................................................................................................................. 476
12.20.4 Signals.............................................................................................................................476
12.21 Definable limiter LIMITER................................................................................................. 477
12.21.1 Identification.................................................................................................................... 477
12.21.2 Functionality ................................................................................................................... 477
12.21.3 Function block................................................................................................................. 477
12.21.4 Signals.............................................................................................................................477
12.21.5 Settings........................................................................................................................... 477
12.22 Absolute value ABS...........................................................................................................478
12.22.1 Identification.................................................................................................................... 478
12.22.2 Functionality ................................................................................................................... 478
12.22.3 Function block................................................................................................................. 478
12.22.4 Signals.............................................................................................................................478
12.23 Polar to rectangular converter POL_REC......................................................................... 478
12.23.1 Identification.................................................................................................................... 478
12.23.2 Functionality ................................................................................................................... 478
12.23.3 Function block................................................................................................................. 479
12.23.4 Signals.............................................................................................................................479
12.24 Radians to degree angle converter RAD_DEG.................................................................479
12.24.1 Identification.................................................................................................................... 479
12.24.2 Functionality ................................................................................................................... 479
12.24.3 Function block................................................................................................................. 479
12.24.4 Signals.............................................................................................................................480
12.24.5 Monitored data................................................................................................................ 480
12.25 Definable constant for logic function CONST_REAL........................................................ 480
12.25.1 Identification.................................................................................................................... 480
12.25.2 Functionality ................................................................................................................... 480
12.25.3 Function block................................................................................................................. 480
12.25.4 Signals.............................................................................................................................481
12.25.5 Signals.............................................................................................................................481
12.26 Analog input selector for real values REALSEL................................................................ 481

Transformer protection RET650 17


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

12.26.1 Identification.................................................................................................................... 481


12.26.2 Functionality ................................................................................................................... 481
12.26.3 Function block................................................................................................................. 482
12.26.4 Signals.............................................................................................................................482
12.27 Store value for integer inputs STOREINT......................................................................... 483
12.27.1 Identification.................................................................................................................... 483
12.27.2 Functionality ................................................................................................................... 483
12.27.3 Function block................................................................................................................. 483
12.27.4 Signals.............................................................................................................................483
12.28 Store value for real inputs STOREREAL...........................................................................483
12.28.1 Identification.................................................................................................................... 483
12.28.2 Functionality ................................................................................................................... 484
12.28.3 Function block................................................................................................................. 484
12.28.4 Signals.............................................................................................................................484
12.29 Degree to radians angle converter DEG_RAD..................................................................484
12.29.1 Identification.................................................................................................................... 484
12.29.2 Functionality ................................................................................................................... 484
12.29.3 Function block................................................................................................................. 485
12.29.4 Signals.............................................................................................................................485
12.29.5 Monitored data................................................................................................................ 485

Section 13 Monitoring.................................................................................................. 487


13.1 Measurements...................................................................................................................487
13.1.1 Function revision history..................................................................................................487
13.1.2 Identification.................................................................................................................... 487
13.1.3 Functionality ................................................................................................................... 488
13.1.4 Function block................................................................................................................. 489
13.1.5 Signals.............................................................................................................................490
13.1.6 Settings........................................................................................................................... 493
13.1.7 Monitored data................................................................................................................ 503
13.1.8 Operation principle.......................................................................................................... 505
13.1.8.1 Measurement supervision.......................................................................................... 505
13.1.8.2 Measurements CVMMXN.......................................................................................... 509
13.1.8.3 Phase current measurement CMMXU....................................................................... 513
13.1.8.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU.......... 514
13.1.8.5 Voltage and current sequence measurements VMSQI, CMSQI................................ 514
13.1.9 Technical data................................................................................................................. 514
13.2 Insulation gas monitoring function SSIMG........................................................................ 516
13.2.1 Function revision history..................................................................................................516
13.2.2 Identification.................................................................................................................... 516
13.2.3 Functionality ................................................................................................................... 516
13.2.4 Function block................................................................................................................. 517
13.2.5 Signals.............................................................................................................................517
13.2.6 Settings........................................................................................................................... 518
13.2.7 Monitored data................................................................................................................ 518
13.2.8 Operation principle.......................................................................................................... 518

18 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

13.2.9 Technical data................................................................................................................. 519


13.3 Insulation liquid monitoring function SSIML ..................................................................... 520
13.3.1 Function revision history..................................................................................................520
13.3.2 Identification.................................................................................................................... 520
13.3.3 Functionality ................................................................................................................... 520
13.3.4 Function block................................................................................................................. 521
13.3.5 Signals.............................................................................................................................521
13.3.6 Settings........................................................................................................................... 522
13.3.7 Monitored data................................................................................................................ 522
13.3.8 Operation principle.......................................................................................................... 522
13.3.9 Technical data................................................................................................................. 523
13.4 Breaker monitoring SSCBR...............................................................................................524
13.4.1 Function revision history..................................................................................................524
13.4.2 Identification.................................................................................................................... 524
13.4.3 Functionality ................................................................................................................... 524
13.4.4 Function block................................................................................................................. 525
13.4.5 Signals.............................................................................................................................525
13.4.6 Settings........................................................................................................................... 526
13.4.7 Monitored data................................................................................................................ 527
13.4.8 Operation principle.......................................................................................................... 527
13.4.8.1 Circuit breaker contact operation time....................................................................... 529
13.4.8.2 Circuit breaker status................................................................................................. 531
13.4.8.3 Remaining life of circuit breaker ................................................................................531
13.4.8.4 Accumulated contact abrasion .................................................................................. 532
13.4.8.5 Circuit breaker operation cycles ................................................................................533
13.4.8.6 Circuit breaker operation monitoring.......................................................................... 534
13.4.8.7 Circuit breaker spring charge monitoring .................................................................. 534
13.4.8.8 Circuit breaker gas pressure indication .....................................................................535
13.4.8.9 Coil Open Indication...................................................................................................536
13.4.9 Technical data................................................................................................................. 536
13.5 Event function EVENT.......................................................................................................536
13.5.1 Identification.................................................................................................................... 536
13.5.2 Functionality ................................................................................................................... 536
13.5.3 Function block................................................................................................................. 537
13.5.4 Signals.............................................................................................................................537
13.5.5 Settings........................................................................................................................... 538
13.5.6 Operation principle.......................................................................................................... 540
13.6 Disturbance report DRPRDRE.......................................................................................... 541
13.6.1 Identification.................................................................................................................... 541
13.6.2 Functionality ................................................................................................................... 541
13.6.3 Function block................................................................................................................. 542
13.6.4 Signals.............................................................................................................................543
13.6.5 Settings........................................................................................................................... 545
13.6.6 Monitored data................................................................................................................ 555
13.6.7 Operation principle.......................................................................................................... 558
13.6.8 Technical data................................................................................................................. 563

Transformer protection RET650 19


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

13.7 Logical signal status report BINSTATREP........................................................................ 564


13.7.1 Identification.................................................................................................................... 564
13.7.2 Functionality.................................................................................................................... 564
13.7.3 Function block................................................................................................................. 564
13.7.4 Signals.............................................................................................................................564
13.7.5 Settings........................................................................................................................... 565
13.7.6 Operation principle.......................................................................................................... 565
13.8 Measured values expander block RANGE_XP................................................................. 566
13.8.1 Identification.................................................................................................................... 566
13.8.2 Functionality ................................................................................................................... 566
13.8.3 Function block................................................................................................................. 566
13.8.4 Signals.............................................................................................................................566
13.8.5 Operation principle ......................................................................................................... 567
13.9 Limit counter L4UFCNT.....................................................................................................567
13.9.1 Identification.................................................................................................................... 567
13.9.2 Functionality ................................................................................................................... 567
13.9.3 Operation principle.......................................................................................................... 567
13.9.3.1 Design........................................................................................................................ 568
13.9.3.2 Reporting....................................................................................................................569
13.9.4 Function block................................................................................................................. 569
13.9.5 Signals.............................................................................................................................569
13.9.6 Settings........................................................................................................................... 569
13.9.7 Monitored data................................................................................................................ 570
13.9.8 Technical data................................................................................................................. 570
13.10 Running hour-meter TEILGAPC .......................................................................................570
13.10.1 Identification.................................................................................................................... 570
13.10.2 Functionality ................................................................................................................... 570
13.10.3 Function block................................................................................................................. 571
13.10.4 Signals.............................................................................................................................571
13.10.5 Settings........................................................................................................................... 572
13.10.6 Operation principle.......................................................................................................... 572
13.10.6.1 Operation accuracy.................................................................................................... 573
13.10.6.2 Memory storage......................................................................................................... 573
13.10.7 Technical data................................................................................................................. 574
13.11 Fault current and voltage monitoring function FLTMMXU ................................................ 574
13.11.1 Function revision history..................................................................................................574
13.11.2 Identification.................................................................................................................... 574
13.11.3 Functionality.................................................................................................................... 574
13.11.4 Function block................................................................................................................. 575
13.11.5 Signals.............................................................................................................................575
13.11.6 Settings........................................................................................................................... 576
13.11.7 Monitored data................................................................................................................ 576
13.11.8 Operation principle.......................................................................................................... 577
13.11.9 Technical data................................................................................................................. 580

Section 14 Metering......................................................................................................581

20 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

14.1 Pulse-counter logic PCFCNT............................................................................................ 581


14.1.1 Identification.................................................................................................................... 581
14.1.2 Functionality ................................................................................................................... 581
14.1.3 Function block................................................................................................................. 581
14.1.4 Signals.............................................................................................................................581
14.1.5 Settings........................................................................................................................... 582
14.1.6 Monitored data................................................................................................................ 582
14.1.7 Operation principle.......................................................................................................... 582
14.1.8 Technical data................................................................................................................. 584
14.2 Function for energy calculation and demand handling ETPMMTR................................... 584
14.2.1 Identification.................................................................................................................... 584
14.2.2 Functionality ................................................................................................................... 584
14.2.3 Function block................................................................................................................. 585
14.2.4 Signals.............................................................................................................................585
14.2.5 Settings........................................................................................................................... 586
14.2.6 Monitored data................................................................................................................ 587
14.2.7 Operation principle.......................................................................................................... 587
14.2.8 Technical data................................................................................................................. 590

Section 15 Ethernet...................................................................................................... 591


15.1 Access point...................................................................................................................... 591
15.1.1 Introduction .....................................................................................................................591
15.1.2 Settings........................................................................................................................... 591
15.2 Access point diagnostics................................................................................................... 592
15.2.1 Functionality ................................................................................................................... 592
15.2.2 Function block................................................................................................................. 593
15.2.3 Signals.............................................................................................................................593
15.2.4 Monitored data................................................................................................................ 593
15.3 Redundant communication................................................................................................594
15.3.1 Identification.................................................................................................................... 594
15.3.2 Functionality.................................................................................................................... 594
15.3.3 Operation principle.......................................................................................................... 594
15.4 Rapid spanning tree protocol (RSTP)............................................................................... 596
15.4.1 Introduction......................................................................................................................596
15.4.2 Configuring RSTP in the IED...........................................................................................596
15.4.3 RSTP parameters............................................................................................................598
15.4.4 Supported network topologies.........................................................................................598
15.4.4.1 Star topology.............................................................................................................. 598
15.4.4.2 Ring and star topology............................................................................................... 599
15.4.4.3 Ring topology............................................................................................................. 599
15.4.5 RSTP status.................................................................................................................... 601
15.4.6 Performance measurements........................................................................................... 602
15.4.7 Reset to factory defaults..................................................................................................602
15.5 Merging unit.......................................................................................................................602
15.5.1 Introduction .....................................................................................................................602
15.5.2 Settings........................................................................................................................... 603

Transformer protection RET650 21


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

15.5.3 Monitored data................................................................................................................ 603


15.6 Routes............................................................................................................................... 608
15.6.1 Introduction .....................................................................................................................608
15.6.2 Settings........................................................................................................................... 608
15.6.3 Monitored data................................................................................................................ 608

Section 16 Station communication............................................................................. 609


16.1 Communication protocols..................................................................................................609
16.2 Communication protocol diagnostics.................................................................................609
16.3 Simple Network Management Protocol (SNMP)............................................................... 610
16.3.1 Introduction......................................................................................................................610
16.3.1.1 Configuration of SNMP parameters........................................................................... 610
16.3.1.2 Object Identifiers Information supported.................................................................... 614
16.4 IEC 61850-8-1 communication protocol............................................................................ 616
16.4.1 Functionality ................................................................................................................... 616
16.4.2 Communication interfaces and protocols ....................................................................... 617
16.4.3 Settings........................................................................................................................... 617
16.4.4 Technical data................................................................................................................. 617
16.4.5 Generic communication function for single point indication SPGAPC, SP16GAPC....... 618
16.4.5.1 Functionality .............................................................................................................. 618
16.4.5.2 Function block............................................................................................................ 618
16.4.5.3 Signals....................................................................................................................... 618
16.4.5.4 Settings...................................................................................................................... 619
16.4.5.5 Monitored data........................................................................................................... 619
16.4.5.6 Operation principle .................................................................................................... 620
16.4.6 Generic communication function for Measured Value MVGAPC.................................... 620
16.4.6.1 Functionality .............................................................................................................. 620
16.4.6.2 Function block............................................................................................................ 620
16.4.6.3 Signals....................................................................................................................... 621
16.4.6.4 Settings...................................................................................................................... 621
16.4.6.5 Monitored data........................................................................................................... 622
16.4.6.6 Operation principle .................................................................................................... 622
16.4.7 GOOSE function block to receive a protection activation information GOOSEACRCV.. 622
16.4.7.1 Identification............................................................................................................... 622
16.4.7.2 Functionality............................................................................................................... 622
16.4.7.3 Function block............................................................................................................ 622
16.4.7.4 Signals....................................................................................................................... 623
16.4.7.5 Settings...................................................................................................................... 623
16.4.7.6 Operation principle..................................................................................................... 623
16.4.8 GOOSE function block to receive a double point value GOOSEDPRCV....................... 624
16.4.8.1 Identification............................................................................................................... 624
16.4.8.2 Functionality .............................................................................................................. 624
16.4.8.3 Function block............................................................................................................ 624
16.4.8.4 Signals....................................................................................................................... 625
16.4.8.5 Settings...................................................................................................................... 625
16.4.8.6 Operation principle .................................................................................................... 625

22 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

16.4.9 GOOSE function block to receive an integer value GOOSEINTRCV............................. 626


16.4.9.1 Identification............................................................................................................... 626
16.4.9.2 Functionality .............................................................................................................. 626
16.4.9.3 Function block............................................................................................................ 626
16.4.9.4 Signals....................................................................................................................... 627
16.4.9.5 Settings...................................................................................................................... 627
16.4.9.6 Operation principle .................................................................................................... 627
16.4.10 GOOSE function block to receive a measurand value GOOSEMVRCV.........................628
16.4.10.1 Identification............................................................................................................... 628
16.4.10.2 Functionality .............................................................................................................. 628
16.4.10.3 Function block............................................................................................................ 628
16.4.10.4 Signals....................................................................................................................... 629
16.4.10.5 Settings...................................................................................................................... 629
16.4.10.6 Operation principle .................................................................................................... 629
16.4.11 GOOSE function block to receive a single point value GOOSESPRCV......................... 630
16.4.11.1 Identification............................................................................................................... 630
16.4.11.2 Functionality .............................................................................................................. 630
16.4.11.3 Function block............................................................................................................ 630
16.4.11.4 Signals....................................................................................................................... 631
16.4.11.5 Settings...................................................................................................................... 631
16.4.11.6 Operation principle .................................................................................................... 631
16.4.12 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV...................632
16.4.12.1 Functionality............................................................................................................... 632
16.4.12.2 Function block............................................................................................................ 633
16.4.12.3 Signals....................................................................................................................... 633
16.4.12.4 Settings...................................................................................................................... 635
16.4.12.5 Operation principle..................................................................................................... 635
16.4.13 GOOSE binary receive GOOSEBINRCV........................................................................ 636
16.4.13.1 Function block............................................................................................................ 636
16.4.13.2 Signals....................................................................................................................... 637
16.4.13.3 Settings...................................................................................................................... 638
16.4.13.4 Operation principle..................................................................................................... 638
16.4.14 GOOSE function block to receive a switching device GOOSEXLNRCV.........................639
16.4.14.1 Identification............................................................................................................... 639
16.4.14.2 Functionality .............................................................................................................. 639
16.4.14.3 Function block............................................................................................................ 639
16.4.14.4 Signals....................................................................................................................... 640
16.4.14.5 Settings...................................................................................................................... 641
16.4.14.6 Operation principle..................................................................................................... 641
16.5 IEC/UCA 61850-9-2LE communication protocol............................................................... 641
16.5.1 Introduction......................................................................................................................641
16.5.2 Function block................................................................................................................. 641
16.5.3 Signals.............................................................................................................................642
16.5.3.1 Output signals............................................................................................................ 642
16.5.4 Settings........................................................................................................................... 642
16.5.5 Monitored data................................................................................................................ 643

Transformer protection RET650 23


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

16.5.6 Operation principle.......................................................................................................... 647


16.5.6.1 Conditional blocking................................................................................................... 650
16.5.6.2 IEC 61850 quality expander QUALEXP.....................................................................653
16.5.7 Technical data................................................................................................................. 654
16.6 LON communication protocol............................................................................................ 655
16.6.1 Functionality ................................................................................................................... 655
16.6.2 Settings........................................................................................................................... 655
16.6.3 Operation principle.......................................................................................................... 655
16.6.4 Technical data................................................................................................................. 671
16.7 SPA communication protocol............................................................................................ 671
16.7.1 Functionality ................................................................................................................... 671
16.7.2 Design............................................................................................................................. 671
16.7.3 Settings........................................................................................................................... 672
16.7.4 Operation principle.......................................................................................................... 672
16.7.4.1 Communication ports................................................................................................. 677
16.7.5 Technical data................................................................................................................. 677
16.8 IEC 60870-5-103 communication protocol........................................................................ 678
16.8.1 Introduction .....................................................................................................................678
16.8.2 Measurands for IEC 60870-5-103 I103MEAS.................................................................678
16.8.2.1 Functionality............................................................................................................... 678
16.8.2.2 Identification............................................................................................................... 678
16.8.2.3 Function block............................................................................................................ 678
16.8.2.4 Signals....................................................................................................................... 679
16.8.2.5 Settings...................................................................................................................... 679
16.8.3 Measurands user defined signals for IEC 60870-5-103 I103MEASUSR........................ 679
16.8.3.1 Functionality............................................................................................................... 679
16.8.3.2 Identification............................................................................................................... 680
16.8.3.3 Function block............................................................................................................ 680
16.8.3.4 Signals....................................................................................................................... 680
16.8.3.5 Settings...................................................................................................................... 680
16.8.4 Function status auto-recloser for IEC 60870-5-103 I103AR........................................... 681
16.8.4.1 Functionality............................................................................................................... 681
16.8.4.2 Identification............................................................................................................... 681
16.8.4.3 Function block............................................................................................................ 681
16.8.4.4 Signals....................................................................................................................... 681
16.8.4.5 Settings...................................................................................................................... 682
16.8.5 Function status earth-fault for IEC 60870-5-103 I103EF.................................................682
16.8.5.1 Functionality............................................................................................................... 682
16.8.5.2 Identification............................................................................................................... 682
16.8.5.3 Function block............................................................................................................ 682
16.8.5.4 Signals....................................................................................................................... 682
16.8.5.5 Settings...................................................................................................................... 682
16.8.6 Function status fault protection for IEC 60870-5-103 I103FLTPROT..............................683
16.8.6.1 Functionality............................................................................................................... 683
16.8.6.2 Identification............................................................................................................... 683
16.8.6.3 Function block............................................................................................................ 683

24 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

16.8.6.4 Signals....................................................................................................................... 684


16.8.6.5 Settings...................................................................................................................... 684
16.8.7 IED status for IEC 60870-5-103 I103IED........................................................................ 685
16.8.7.1 Functionality............................................................................................................... 685
16.8.7.2 Identification............................................................................................................... 685
16.8.7.3 Function block............................................................................................................ 685
16.8.7.4 Signals....................................................................................................................... 685
16.8.7.5 Settings...................................................................................................................... 685
16.8.8 Supervison status for IEC 60870-5-103 I103SUPERV................................................... 686
16.8.8.1 Functionality............................................................................................................... 686
16.8.8.2 Identification............................................................................................................... 686
16.8.8.3 Function block............................................................................................................ 686
16.8.8.4 Signals....................................................................................................................... 686
16.8.8.5 Settings...................................................................................................................... 686
16.8.9 Status for user defined signals for IEC 60870-5-103 I103USRDEF............................... 687
16.8.9.1 Functionality............................................................................................................... 687
16.8.9.2 Identification............................................................................................................... 687
16.8.9.3 Function block............................................................................................................ 687
16.8.9.4 Signals....................................................................................................................... 687
16.8.9.5 Settings...................................................................................................................... 688
16.8.10 Function commands for IEC 60870-5-103 I103CMD...................................................... 689
16.8.10.1 Functionality............................................................................................................... 689
16.8.10.2 Identification............................................................................................................... 689
16.8.10.3 Function block............................................................................................................ 689
16.8.10.4 Signals....................................................................................................................... 689
16.8.10.5 Settings...................................................................................................................... 690
16.8.11 IED commands for IEC 60870-5-103 I103IEDCMD........................................................ 690
16.8.11.1 Functionality............................................................................................................... 690
16.8.11.2 Identification............................................................................................................... 690
16.8.11.3 Function block............................................................................................................ 690
16.8.11.4 Signals....................................................................................................................... 690
16.8.11.5 Settings...................................................................................................................... 691
16.8.12 Function commands user defined for IEC 60870-5-103 I103USRCMD..........................691
16.8.12.1 Functionality............................................................................................................... 691
16.8.12.2 Identification............................................................................................................... 691
16.8.12.3 Function block............................................................................................................ 691
16.8.12.4 Signals....................................................................................................................... 692
16.8.12.5 Settings...................................................................................................................... 692
16.8.13 Function commands generic for IEC 60870-5-103 I103GENCMD..................................692
16.8.13.1 Functionality............................................................................................................... 692
16.8.13.2 Identification............................................................................................................... 693
16.8.13.3 Function block............................................................................................................ 693
16.8.13.4 Signals....................................................................................................................... 693
16.8.13.5 Settings...................................................................................................................... 693
16.8.14 IED commands with position and select for IEC 60870-5-103 I103POSCMD................ 693
16.8.14.1 Functionality............................................................................................................... 693

Transformer protection RET650 25


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

16.8.14.2 Identification............................................................................................................... 694


16.8.14.3 Function block............................................................................................................ 694
16.8.14.4 Signals....................................................................................................................... 694
16.8.14.5 Settings...................................................................................................................... 694
16.8.15 IED commands with position for IEC 60870-5-103 I103POSCMDV............................... 695
16.8.15.1 Functionality............................................................................................................... 695
16.8.15.2 Identification............................................................................................................... 695
16.8.15.3 Function block............................................................................................................ 695
16.8.15.4 Signals....................................................................................................................... 695
16.8.15.5 Settings...................................................................................................................... 696
16.8.16 Operation principle ......................................................................................................... 696
16.8.16.1 General ..................................................................................................................... 696
16.8.16.2 Communication ports................................................................................................. 704
16.8.17 Technical data................................................................................................................. 704
16.9 MULTICMDRCV and MULTICMDSND..............................................................................704
16.9.1 Functionality ................................................................................................................... 705
16.9.2 Design............................................................................................................................. 705
16.9.2.1 General...................................................................................................................... 705
16.9.3 Function block................................................................................................................. 705
16.9.4 Signals.............................................................................................................................706
16.9.5 Settings........................................................................................................................... 707
16.9.6 Operation principle.......................................................................................................... 707
16.10 Activity logging parameters ACTIVLOG............................................................................ 707
16.10.1 Activity logging ACTIVLOG............................................................................................. 707
16.10.2 Settings........................................................................................................................... 708
16.11 IEC61850SIM.................................................................................................................... 709
16.11.1 IEC 61850 simulation mode............................................................................................ 709
16.11.1.1 Identification............................................................................................................... 709
16.11.1.2 Functionality............................................................................................................... 709
16.11.1.3 Function block............................................................................................................ 709
16.11.1.4 Signals....................................................................................................................... 709
16.11.1.5 Settings...................................................................................................................... 709
16.11.1.6 Monitored Data...........................................................................................................710

Section 17 Security.......................................................................................................711
17.1 Authority check ATHCHCK................................................................................................711
17.1.1 Identification.................................................................................................................... 711
17.1.2 Functionality ................................................................................................................... 711
17.1.3 Operation principle ......................................................................................................... 711
17.1.3.1 Authorization with Central Account Management enabled IED................................. 714
17.2 Authority management AUTHMAN................................................................................... 715
17.2.1 Identification.................................................................................................................... 715
17.2.2 AUTHMAN.......................................................................................................................715
17.2.3 Settings........................................................................................................................... 716
17.3 FTP access with password FTPACCS.............................................................................. 716
17.3.1 Identification.................................................................................................................... 716

26 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

17.3.2 FTP access with TLS, FTPACCS....................................................................................716


17.3.3 Settings........................................................................................................................... 716
17.4 Authority status ATHSTAT................................................................................................. 717
17.4.1 Identification.................................................................................................................... 717
17.4.2 Functionality ................................................................................................................... 717
17.4.3 Function block................................................................................................................. 717
17.4.4 Signals.............................................................................................................................717
17.4.5 Settings........................................................................................................................... 717
17.4.6 Operation principle ......................................................................................................... 717
17.5 Self supervision with internal event list INTERRSIG......................................................... 718
17.5.1 Functionality ................................................................................................................... 718
17.5.2 Function block................................................................................................................. 718
17.5.3 Signals.............................................................................................................................718
17.5.4 Settings........................................................................................................................... 718
17.5.5 Operation principle.......................................................................................................... 718
17.5.5.1 Internal signals........................................................................................................... 719
17.5.5.2 Supervision of analog inputs...................................................................................... 721
17.5.6 Technical data................................................................................................................. 721
17.6 Change Lock function CHNGLCK..................................................................................... 721
17.6.1 Functionality ................................................................................................................... 721
17.6.2 Function block................................................................................................................. 722
17.6.3 Signals.............................................................................................................................722
17.6.4 Operation principle ......................................................................................................... 722
17.7 Denial of service DOS....................................................................................................... 723
17.7.1 Functionality ................................................................................................................... 723
17.7.2 Operation principle ......................................................................................................... 723

Section 18 Basic IED functions................................................................................... 725


18.1 Time synchronization TIMESYNCHGEN...........................................................................725
18.1.1 Functionality ................................................................................................................... 725
18.1.2 Settings........................................................................................................................... 725
18.1.3 Description of SyncLostMode..........................................................................................729
18.1.4 Operation principle ......................................................................................................... 730
18.1.4.1 General concepts....................................................................................................... 730
18.1.4.2 Real-time clock (RTC) operation................................................................................732
18.1.4.3 Synchronization alternatives...................................................................................... 733
18.1.4.4 Process bus IEC/UCA 61850-9-2LE synchronization................................................ 736
18.1.4.5 Precision Time Protocol (PTP) .................................................................................. 736
18.1.5 Technical data................................................................................................................. 737
18.2 Parameter setting groups.................................................................................................. 738
18.2.1 Functionality ................................................................................................................... 738
18.2.2 Function block................................................................................................................. 738
18.2.3 Signals.............................................................................................................................738
18.2.4 Settings........................................................................................................................... 739
18.2.5 Operation principle.......................................................................................................... 739
18.3 Test mode functionality TESTMODE.................................................................................740

Transformer protection RET650 27


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

18.3.1 Functionality ................................................................................................................... 740


18.3.2 Function block................................................................................................................. 740
18.3.3 Signals.............................................................................................................................741
18.3.4 Settings........................................................................................................................... 741
18.3.5 Operation principle ......................................................................................................... 741
18.4 IED identifiers TERMINALID............................................................................................. 742
18.4.1 Functionality ................................................................................................................... 742
18.4.2 Settings .......................................................................................................................... 742
18.5 Product information PRODINF.......................................................................................... 742
18.5.1 Functionality ................................................................................................................... 742
18.5.2 Settings .......................................................................................................................... 743
18.5.3 Factory defined settings.................................................................................................. 743
18.6 Signal matrix for binary inputs SMBI................................................................................. 743
18.6.1 Functionality.................................................................................................................... 743
18.6.2 Function block................................................................................................................. 744
18.6.3 Signals.............................................................................................................................744
18.6.4 Operation principle.......................................................................................................... 744
18.7 Signal matrix for binary outputs SMBO ............................................................................ 745
18.7.1 Functionality.................................................................................................................... 745
18.7.2 Function block................................................................................................................. 745
18.7.3 Signals.............................................................................................................................745
18.7.4 Operation principle.......................................................................................................... 745
18.8 Signal matrix for analog inputs SMAI................................................................................ 745
18.8.1 Functionality ................................................................................................................... 746
18.8.2 Function block................................................................................................................. 746
18.8.3 Signals.............................................................................................................................747
18.8.4 Settings........................................................................................................................... 748
18.8.5 Operation principle ......................................................................................................... 749
18.8.5.1 Frequency values.......................................................................................................749
18.8.6 SMAI incorrect calculated phase-earth........................................................................... 750
18.9 Summation block 3 phase 3PHSUM................................................................................. 751
18.9.1 Functionality ................................................................................................................... 751
18.9.2 Function block................................................................................................................. 751
18.9.3 Signals.............................................................................................................................751
18.9.4 Settings........................................................................................................................... 751
18.9.5 Operation principle ......................................................................................................... 752
18.10 Primary system values PRIMVAL......................................................................................752
18.10.1 Identification.................................................................................................................... 752
18.10.2 Functionality ................................................................................................................... 752
18.10.3 Settings........................................................................................................................... 752

Section 19 IED hardware..............................................................................................753


19.1 Overview........................................................................................................................... 753
19.1.1 Variants of case size with local HMI display....................................................................753
19.1.2 Case from the front and rear sides..................................................................................754
19.2 Hardware modules............................................................................................................ 754

28 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

19.2.1 Overview......................................................................................................................... 754


19.2.2 Numeric module (NUM)...................................................................................................755
19.2.2.1 Introduction ............................................................................................................... 755
19.2.2.2 Functionality............................................................................................................... 755
19.2.2.3 Technical data............................................................................................................ 756
19.2.3 Power supply module (PSM)...........................................................................................757
19.2.3.1 Introduction ............................................................................................................... 757
19.2.3.2 Design........................................................................................................................ 757
19.2.3.3 Technical data............................................................................................................ 757
19.2.4 Local human-machine interface (Local HMI)...................................................................758
19.2.5 Transformer input module (TRM).................................................................................... 758
19.2.5.1 Introduction ............................................................................................................... 758
19.2.5.2 Design........................................................................................................................ 758
19.2.5.3 Technical data............................................................................................................ 759
19.2.6 Binary input module (BIM)...............................................................................................760
19.2.6.1 Introduction ............................................................................................................... 760
19.2.6.2 Design........................................................................................................................ 760
19.2.6.3 Signals....................................................................................................................... 763
19.2.6.4 Settings...................................................................................................................... 763
19.2.6.5 Monitored data........................................................................................................... 763
19.2.6.6 Technical data............................................................................................................ 764
19.2.7 Binary output modules (BOM)......................................................................................... 765
19.2.7.1 Introduction ............................................................................................................... 765
19.2.7.2 Design........................................................................................................................ 765
19.2.7.3 Signals....................................................................................................................... 766
19.2.7.4 Settings...................................................................................................................... 767
19.2.7.5 Monitored data........................................................................................................... 767
19.2.7.6 Technical data............................................................................................................ 771
19.2.8 Binary input/output module (IOM)................................................................................... 771
19.2.8.1 Introduction ............................................................................................................... 771
19.2.8.2 Design........................................................................................................................ 772
19.2.8.3 Signals....................................................................................................................... 774
19.2.8.4 Settings...................................................................................................................... 774
19.2.8.5 Monitored data........................................................................................................... 775
19.2.8.6 Technical data............................................................................................................ 776
19.2.9 Serial and LON communication module (SLM) .............................................................. 778
19.2.9.1 Introduction ............................................................................................................... 778
19.2.9.2 Design........................................................................................................................ 778
19.2.9.3 Technical data............................................................................................................ 780
19.2.10 Galvanic RS485 communication module........................................................................ 780
19.2.10.1 Introduction ............................................................................................................... 780
19.2.10.2 Design........................................................................................................................ 780
19.2.10.3 Serial optical and RS485 communication channel settings....................................... 781
19.2.10.4 Parameter list for optical and RS485 communication channel...................................783
19.2.10.5 Technical data............................................................................................................ 783
19.2.11 IRIG-B time synchronization module IRIG-B...................................................................783

Transformer protection RET650 29


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Table of contents 1MRK504170-UEN Rev. J

19.2.11.1 Introduction ............................................................................................................... 783


19.2.11.2 Design........................................................................................................................ 783
19.2.11.3 Encoding.................................................................................................................... 784
19.2.11.4 TimeZoneAs1344....................................................................................................... 784
19.2.11.5 Settings...................................................................................................................... 785
19.2.11.6 Technical data............................................................................................................ 785
19.3 Dimensions........................................................................................................................786
19.3.1 Case with protective cover.............................................................................................. 786
19.3.2 Case without protective cover......................................................................................... 789
19.3.3 Flush mounting dimensions.............................................................................................791
19.3.4 Side-by-side flush mounting dimensions.........................................................................791
19.3.5 Wall mounting dimensions.............................................................................................. 792
19.4 Mounting alternatives........................................................................................................ 793
19.4.1 Flush mounting................................................................................................................793
19.4.1.1 Overview.................................................................................................................... 793
19.4.1.2 Mounting procedure for flush mounting......................................................................793
19.4.2 Wall mounting..................................................................................................................794
19.4.2.1 Overview.................................................................................................................... 794
19.4.2.2 Mounting procedure for wall mounting....................................................................... 794
19.4.2.3 How to reach the rear side of the IED........................................................................ 795
19.4.3 19” panel rack mounting..................................................................................................795
19.4.3.1 Overview.................................................................................................................... 795
19.4.3.2 Mounting procedure for 19” panel rack mounting...................................................... 796
19.4.4 Side-by-side 19” rack mounting.......................................................................................796
19.4.4.1 Overview.................................................................................................................... 796
19.4.4.2 Mounting procedure for side-by-side rack mounting.................................................. 797
19.4.4.3 IED mounted with a RHGS6 case..............................................................................797
19.4.5 Side-by-side flush mounting............................................................................................798
19.4.5.1 Overview.................................................................................................................... 798
19.4.5.2 Mounting procedure for side-by-side 19" rack mounting............................................799
19.5 Technical data................................................................................................................... 799
19.5.1 Enclosure........................................................................................................................ 799
19.5.2 Electrical safety............................................................................................................... 800
19.5.3 Connection system..........................................................................................................800
19.5.4 Influencing factors........................................................................................................... 800
19.5.5 Type tests according to standard.................................................................................... 802

Section 20 Labels......................................................................................................... 805


20.1 Labels on IED....................................................................................................................805

Section 21 Connection diagrams ............................................................................... 807

Section 22 Inverse time characteristics..................................................................... 809


22.1 Application.........................................................................................................................809
22.2 Principle of operation ........................................................................................................811
22.2.1 Mode of operation............................................................................................................811
22.3 Inverse characteristics ......................................................................................................815

30 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Table of contents

Section 23 Glossary..................................................................................................... 841

Transformer protection RET650 31


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
32
1MRK504170-UEN Rev. J Section 1
Introduction

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v21

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.

1.1.1 Presumptions for Technical Data GUID-1E949E38-E04D-4374-A086-912C25E9F93C v3

The technical data stated in this document are only valid under the following circumstances:

1. Main current transformers with 1 A or 2 A secondary rating are wired to the IED 1 A rated CT
inputs.
2. Main current transformer with 5 A secondary rating are wired to the IED 5 A rated CT inputs.
3. CT and VT ratios in the IED are set in accordance with the associated main instrument
transformers. Note that for functions which measure an analogue signal which do not have
corresponding primary quantity the 1:1 ratio shall be set for the used analogue inputs on the
IED. Example of such functions are: HZPDIF, ROTIPHIZ and STTIPHIZ.
4. Parameter IBase used by the tested function is set equal to the rated CT primary current.
5. Parameter UBase used by the tested function is set equal to the rated primary phase-to-phase
voltage.
6. Parameter SBase used by the tested function is set equal to:
• √3 × IBase × UBase
7. The rated secondary quantities have the following values:
• Rated secondary phase current Ir is either 1 A or 5 A depending on selected TRM.
• Rated secondary phase-to-phase voltage Ur is within the range from 100 V to 120 V.
• Rated secondary power for three-phase system Sr = √3 × Ur × Ir
8. For operate and reset time testing, the default setting values of the function and BOM module
are used if not explicitly stated otherwise.
All reset times are measured using BOM output contacts if not explicitly stated otherwise. The
operate/reset times are determined by characteristics of the output module used.
9. During testing, signals with rated frequency have been injected if not explicitly stated otherwise.

1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11

This manual addresses system engineers and installation and commissioning personnel, who use
technical data during engineering, installation and commissioning, and in normal service.

The system engineer must have a thorough knowledge of protection systems, protection equipment,
protection functions and the configured functional logic in the IEDs. The installation and
commissioning personnel must have a basic knowledge in handling electronic equipment.

Transformer protection RET650 33


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 1 1MRK504170-UEN Rev. J
Introduction

1.3 Product documentation

1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual

Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN-US

Figure 1: The intended use of manuals throughout the product lifecycle


The engineering manual contains instructions on how to engineer the IEDs using the various tools
available within the PCM600 software. The manual provides instructions on how to set up a PCM600
project and insert IEDs to the project structure. The manual also recommends a sequence for the
engineering of protection and control functions, as well as communication engineering for IEC 61850.

The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the chronological
order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The manual can
also be used by system engineers and maintenance personnel for assistance during the testing
phase. The manual provides procedures for the checking of external circuitry and energizing the IED,
parameter setting and configuration as well as verifying settings by secondary injection. The manual
describes the process of testing an IED in a station which is not in service. The chapters are
organized in the chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of the
IED. The manual also describes how to identify disturbances and how to view calculated and
measured power grid data to determine the cause of a fault.

34 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 1
Introduction

The application manual contains application descriptions and setting guidelines sorted per function.
The manual can be used to find out when and for what purpose a typical protection function can be
used. The manual can also provide assistance for calculating settings.

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per function. The
manual can be used as a technical reference during the engineering phase, installation and
commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols supported by the IED.
The manual concentrates on the vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the IED. The
manual should be used in conjunction with the corresponding communication protocol manual.

The cyber security deployment guideline describes the process for handling cyber security when
communicating with the IED. Certification, Authorization with role based access control, and product
engineering for cyber security related events are described and sorted by function. The guideline can
be used as a technical reference during the engineering phase, installation and commissioning
phase, and during normal service.

1.3.2 Document revision history GUID-BD82A13A-6FA0-4E33-BDBF-23B5A0CF968F v4

Document Date Product revision History


revision
- 2017–05 2.2.0 First release for product version 2.2
A 2017-10 2.2.1 Ethernet ports with RJ45 connector added. enhancements/
updates made to GENPDIF, ZMFPDIS and ZMFCPDIS.
B 2018-03 2.2.1 Document enhancements and corrections
C 2019-05 2.2.1 PTP enhancements and corrections
D Document not released
E 2020-09 2.2.4 Added new functions ALGOS, ALSVS and IEC 61850SIM.
Added APC5 apparatus control function. Included instances for
functions HZPDIF, NS4PTOC, GUPPDUP, GOPPDOP,
VDCPTOV, LOVPTUV, DELVSPVC, DELISPVC, DELSPVC,
SESRSYN. Removed instances for functions SCILO, SCSWI,
XLNPROXY, GOOSEXLNRCV. Instances updated for functions
EF4PTOC, TRPTTR, UV2PTUV, OV2PTOV, ROV2PTOV,
OEXPVPH, SAPTUF, SAPTOF, SAPFRC, FUFSPVC and
SXCBR.
F 2021-06 2.2.5 Functions FLTMMXU, BRPTOC, HOLDMINMAX, INT_REAL,
CONST_INT, INTSEL, LIMITER, ABS, POL_REC, RAD_DEG,
CONST_REAL, REALSEL, STOREINT, STOREREAL,
DEG_RAD and RSTP added. Updates/enhancements made to
functions ZMFPDIS, OC4PTOC, EF4PTOC, NS4PTOC,
STBPTOC, DRPRDRE, SXSWI and SXCBR.
G 2022-07 2.2.5.4 Introduced RIA600, which is a software implementation of the
IED LHMI panel.
H Document not released
J 2023-06 2.2.6 SNMP support, IEC 61850 Ed2.1, new variants of single mode
SFP added. Functions C1RADR, GOOSEACRCV,
SNMPSERVERCONF, and SNMPUSERCONF added.
Functions INTERRSIG, SETGRPS, TERMINALID, OC4PTOC,
EF4PTOC, NS4PTOC, OEXPVPH, VDCPTDV, SCSWI,
SXSWI, TCMYLTC, VSGAPC, SMPPTRC, BTIGAPC, IB16,
ITBGAPC, CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI,
VNMMXU, SSCBR, SPGAPC, SP16GAPC, MVGAPC,
IEC61850-8-1, LD0LLN0, AP_1, FLTMMXU, and AP_FRONT
updated.

Transformer protection RET650 35


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 1 1MRK504170-UEN Rev. J
Introduction

1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v10

Documents related to RET650 Document numbers


Application manual 1MRK504169-UEN
Commissioning manual 1MRK504171-UEN
Product guide 1MRK504172-BEN
Technical manual 1MRK504170-UEN
Type test certificate 1MRK504172-TEN

650 series manuals Document numbers


Operation manual 1MRK500128-UEN
Engineering manual 1MRK511420-UEN
Installation manual 1MRK514027-UEN
Communication protocol manual, DNP3 1MRK511413-UUS
Communication protocol manual, IEC 60870-5-103 1MRK511416-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK511414-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK511415-UEN
Communication protocol manual, LON 1MRK511417-UEN
Communication protocol manual, SPA 1MRK511418-UEN
Point list manual, DNP3 1MRK511419-UUS
Accessories guide IEC: 1MRK514012-UEN
Cyber security deployment guideline 1MRK511421-UEN
Connection and Installation components 1MRK513003-BEN
Test system, COMBITEST 1MRK512001-BEN
Application guide, Communication set-up 1MRK505382-UEN

1.4 Document symbols and conventions

1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13

The electrical warning icon indicates the presence of a hazard which could result in
electrical shock.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution hot surface icon indicates important information or warning about the
temperature of product surfaces.

Class 1 Laser product. Take adequate measures to protect the eyes and do not view
directly with optical instruments.

The caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could result in
corruption of software or damage to equipment or property.

36 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 1
Introduction

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a
certain function.

Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. It is important that the user fully complies with all
warning and cautionary notices.

1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v9

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal name may
be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be connected to
another function block in the application configuration to achieve a valid application
configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned then
the dimension is in millimeters.
• Logic diagrams describe the signal logic of the function block and are bordered by dashed lines.
In a logic diagram, input and output signal paths are shown as lines that touch the outer border
of the diagram. Input signals are always on the left-hand side and output signals are on the
right-hand side.
Input and output signals can be configured using PCM600. They can be connected to the inputs
and outputs of other functions and to binary inputs and outputs. Examples of input signals are
BLKTR, BLOCK, and VTSZ. Examples of output signals are TRIP, START, STL1, STL2, and
STL3.
• Frames with a shaded area on the right-hand side represent setting parameters. These
parameters can only be set via the PST or LHMI. Their values are high (1) only when the
corresponding setting parameter is set to the symbolic value specified within the frame.
Example is the signal Timer tPP=On. Their logical values correspond automatically to the
selected setting value.
• Internal signals are illustrated graphically and end approximately 2 mm from the frame
edge. If an internal signal path cannot be drawn with a continuous line, the same signal
name is used where the signal should continue, see figure 2 and figure 3. Example of the
internal signal is BLK.
• Signal paths that extend beyond the logic diagram and continue in another diagram will be
approximately 2 mm from the frame edge, see figure 3 and figure 4. Examples are
STNDL1N, STNDL2N, STNDL3N, STNDL1L2, STNDL2L3, and STNDL3L1.

Transformer protection RET650 37


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 1 1MRK504170-UEN Rev. J
Introduction

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 2: Logic diagram example with intermediate output signals

IEC00000488-TIFF V1 EN-US

Figure 3: Logic diagram example with intermediate input signals

38 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 1
Introduction

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 4: Logic diagram example with a parameter input

Illustrations are used as an example and might show other products than the one the
manual describes. The example that is illustrated is still valid.

1.5 IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v10

Function block names are used in ACT and PST to identify functions. Respective function block
names of Edition 1, Edition 2, and Edition 2.1 logical nodes are shown in the table below.

Table 1: IEC 61850 Edition 1, Edition 2, and Edition 2.1 mapping

Function block name Edition 1 logical nodes Edition 2 and Edition 2.1 logical
nodes
- - ALGOS
- - ALSVS
AGSAL AGSAL AGSAL
SECLLN0
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BRPTOC BRPTOC BRPTOC
BTIGAPC B16IFCVI BTIGAPC
CCPDSC CCRPLD CCPDSC
CCRBRF CCRBRF CCRBRF
CCSSPVC CCSRDIF CCSSPVC
Table continues on next page

Transformer protection RET650 39


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 1 1MRK504170-UEN Rev. J
Introduction

Function block name Edition 1 logical nodes Edition 2 and Edition 2.1 logical
nodes
CMMXU CMMXU CMMXU
CMSQI CMSQI CMSQI
CVMMXN CVMMXN CVMMXN
DELISPVC DELISPVC DELISPVC
DELSPVC DELSPVC DELSPVC
DELVSPVC DELVSPVC DELVSPVC
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
EF4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR GEN4PHAR
GEN4PHAR PH1PTOC
PH1PTOC
EFPIOC EFPIOC EFPIOC
ETPMMTR ETPMMTR ETPMMTR
FLTMMXU FLTMMXU FLTMMXU
FUFSPVC SDDRFUF FUFSPVC
GUPPDUP GUPPDUP GUPPDUP
PH1PTRC
GOPPDOP GOPPDOP GOPPDOP
PH1PTRC
HZPDIF HZPDIF HZPDIF
INDCALH INDCALH INDCALH
ITBGAPC IB16FCVB ITBGAPC
L4UFCNT L4UFCNT L4UFCNT
LD0LLN0 LLN0 LLN0
LOVPTUV LOVPTUV LOVPTUV
LPHD LPHD LPHD
MVGAPC MVGGIO MVGAPC
NS4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR PH1PTOC
GEN4PHAR
PH1PTOC
OC4PTOC OC4LLN0 GEN4PHAR
GEN4PHAR PH3PTOC
PH3PTOC PH3PTRC
PH3PTRC
OEXPVPH OEXPVPH OEXPVPH
OOSPPAM OOSPPAM OOSPPAM
OOSPTRC
OV2PTOV GEN2LLN0 OV2PTOV
OV2PTOV PH1PTRC
PH1PTRC
PCFCNT PCGGIO PCFCNT
PHPIOC PHPIOC PHPIOC
QCBAY QCBAY BAY/LLN0
QCRSV QCRSV QCRSV
RCHLCCH RCHLCCH RCHLCCH
REFPDIF REFPDIF REFPDIF
Table continues on next page

40 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 and Edition 2.1 logical
nodes
ROV2PTOV GEN2LLN0 PH1PTRC
PH1PTRC ROV2PTOV
ROV2PTOV
SAPFRC SAPFRC SAPFRC
SAPTUF SAPTUF SAPTUF
SAPTOF SAPTOF SAPTOF
SCHLCCH SCHLCCH SCHLCCH
SDEPSDE SDEPSDE SDEPSDE
SDEPTOC
SDEPTOV
SDEPTRC
SESRSYN RSY1LLN0 AUT1RSYN
AUT1RSYN MAN1RSYN
MAN1RSYN SYNRSYN
SYNRSYN
SLGAPC SLGGIO SLGAPC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
T3WPDIF T3WPDIF T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TCMYLTC TCMYLTC TCMYLTC
TEIGAPC TEIGGIO TEIGAPC
TEILGAPC TEILGGIO TEILGAPC
TMAGAPC TMAGGIO TMAGAPC
TR1ATCC TR1ATCC TR1ATCC
TRPTTR TRPTTR TRPTTR
UV2PTUV GEN2LLN0 PH1PTRC
PH1PTRC UV2PTUV
UV2PTUV
VDCPTOV VDCPTOV VDCPTOV
VMMXU VMMXU VMMXU
VMSQI VMSQI VMSQI
VNMMXU VNMMXU VNMMXU
VSGAPC VSGGIO VSGAPC
VRPVOC VRLLN0 PH1PTRC
PH1PTRC PH1PTUV
PH1PTUV VRPVOC
VRPVOC
WRNCALH WRNCALH WRNCALH

Transformer protection RET650 41


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
42
1MRK504170-UEN Rev. J Section 2
Available functions

Section 2 Available functions


GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v2

The following tables list all the functions available in the IED. Those functions that are not
exposed to the user or do not need to be configured are not described in this manual.

Table 2: Example of quantities

2 = number of basic instances


0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)
C30 =1/2 CB application. For the pre-configured variants

2.1 Main protection functions GUID-F871E970-5508-43FE-A2A8-68A4679BE52B v2

IEC 61850 or
ANSI Function description Transformer
function name
RET650 (A01) RET650 (A05)
Differential protection
T2WPDIF 87T Transformer differential protection, two winding 1
T3WPDIF 87T Transformer differential protection, three winding 1
HZPDIF 87 High impedance differential protection, single phase 2 3
REFPDIF 87N Restricted earth fault protection, low impedance 2 3

2.2 Back-up protection functions GUID-06D023C0-3F72-4D89-A0A5-F4B452234B7B v2

IEC 61850 or
ANSI Function description Transformer
function name
RET650 (A01) RET650 (A05)
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection 2 3
OC4PTOC 51_671) Directional phase overcurrent protection, four steps 2 3
EFPIOC 50N Instantaneous residual overcurrent protection 2 3
EF4PTOC 51N_67N2) Directional residual overcurrent protection, four steps 4 5
NS4PTOC 46I2 Directional negative phase sequence overcurrent protection, four 1 2
steps
TRPTTR 49 Thermal overload protection, two time constants 2 3
CCRBRF 50BF Breaker failure protection 2 3
CCPDSC 52PD Pole discordance protection 2 3
GUPPDUP 37 Directional underpower protection 1 1
GOPPDOP 32 Directional overpower protection 1 1
BRPTOC 50 Overcurrent protection with binary release 2 3
Voltage protection
UV2PTUV 27 Two step undervoltage protection 1 2
OV2PTOV 59 Two step overvoltage protection 1 2
ROV2PTOV 59N Residual overvoltage protection, two steps 1 2
OEXPVPH 24 Overexcitation protection 1 2
Table continues on next page

Transformer protection RET650 43


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 2 1MRK504170-UEN Rev. J
Available functions

IEC 61850 or
ANSI Function description Transformer
function name
RET650 (A01) RET650 (A05)
VDCPTDV 87V Voltage differential protection 2 2
LOVPTUV 27 Loss of voltage check 1 2
Frequency protection
SAPTUF 81 Underfrequency protection 4 4
SAPTOF 81 Overfrequency protection 4 4
SAPFRC 81 Rate-of-change of frequency protection 2 2

1) 67 requires voltage
2) 67N requires voltage

2.3 Control and monitoring functions GUID-AE265B38-C04D-4415-BAA4-EFB62EAFAFF1 v2

IEC 61850 or Transformer


ANSI Function description
function name
RET650 (A01) RET650 (A05)
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing 1 1
APC5 Control functionality for a single bay, max 5 objects (1CB), including 1 1
interlocking (see Table 3)
QCBAY Bay control 1 1
LOCREM Handling of local/remote switch positions 1 1
LOCREMCTRL LHMI control of the permitted source to operate (PSTO) 1 1
SXCBR Circuit breaker 6 9
TR1ATCC 90 Automatic voltage control for tapchanger, single control 1 1
TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 1 1
SLGAPC Logic rotating switch for function selection and LHMI presentation 15 15
VSGAPC Selector mini switch 30 30
DPGAPC Generic communication function for Double Point indication 16 16
SPC8GAPC Single point generic control function, 8 signals 5 5
AUTOBITS Automation bits, command function for DNP3.0 3 3
SINGLECMD Single command, 16 inputs 8 8
I103CMD Function commands for IEC 60870-5-103 1 1
I103GENCMD Function commands for IEC 60870-5-103, generic 50 50
I103POSCMD IED commands with position and select for IEC 60870-5-103 50 50
I103POSCMDV IED direct commands with position for IEC 60870-5-103 50 50
I103IEDCMD IED commands for IEC 60870-5-103 1 1
I103USRCMD Function commands user defined for IEC 60870-5-103 4 4
Secondary system supervision
CCSSPVC 87 Current circuit supervision 2 3
FUFSPVC Fuse failure supervision 1 2
DELVSPVC 7V_78V Voltage delta supervision 4 4
DELISPVC 7I Current delta supervision 4 4
DELSPVC 78 Real delta supervision, real 4 4
Logic
SMPPTRC 94 Tripping logic 6 6
SMAGAPC General start matrix block 6 6
Table continues on next page

44 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 2
Available functions

IEC 61850 or Transformer


ANSI Function description
function name
RET650 (A01) RET650 (A05)
STARTCOMB Start combinator 32 32
TMAGAPC Trip matrix logic 12 12
ALMCALH Logic for group alarm 5 5
WRNCALH Logic for group warning 5 5
INDCALH Logic for group indication 5 5
AND, GATE, INV, Basic configurable logic blocks (see Table 4) 40-420 40-420
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
FXDSIGN Fixed signal function block 1 1
B16I Boolean to integer conversion, 16 bit 18 18
BTIGAPC Boolean to integer conversion with logical node representation, 16 bit 16 16
IB16 Integer to Boolean 16 conversion 24 24
ITBGAPC Integer to boolean conversion with logical node representation, 16 bit 16 16
TEIGAPC Elapsed time integrator with limit transgression and overflow 12 12
supervision
INTCOMP Comparator for integer inputs 30 30
REALCOMP Comparator for real inputs 30 30
HOLDMINMAX Hold minimum and maximum of input 20 20
INT_REAL Converter integer to real 20 20
CONST_INT Definable constant for logic functions 10 10
INTSEL Analog input selector for integer values 5 5
LIMITER Definable limiter 20 20
ABS Absolute value 20 20
POL_REC Polar to rectangular converter 20 20
RAD_DEG Radians to degree angle converter 20 20
CONST_REAL Definable constant for logic functions 10 10
REALSEL Analog input selctor for real values 5 5
STOREINT Store value for integer inputs 10 10
STOREREAL Store value for real inputs 10 10
DEG_RAD Degree to radians angle converter 20 20
Monitoring
CVMMXN Power system measurement 6 6
CMMXU Current measurement 10 10
VMMXU Voltage measurement phase-phase 6 6
CMSQI Current sequence measurement 6 6
VMSQI Voltage sequence measurement 6 6
VNMMXU Voltage measurement phase-earth 6 6
AISVBAS General service value presentation of analog inputs 1 1
SSIMG 63 Insulation supervision for gas medium 21 21
SSIML 71 Insulation supervision for liquid medium 3 3
SSCBR Circuit breaker condition monitoring 6 9
EVENT Event function 20 20
Table continues on next page

Transformer protection RET650 45


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 2 1MRK504170-UEN Rev. J
Available functions

IEC 61850 or Transformer


ANSI Function description
function name
RET650 (A01) RET650 (A05)
DRPRDRE, Disturbance report 1 1
A1RADR-
A3RADR,
B1RBDR-
B22RBDR,
C1RADR
SPGAPC Generic communication function for single point indication, 1 input 96 96
SP16GAPC Generic communication function for single point indication, 16 inputs 16 16
MVGAPC Generic communication function for measured values 24 24
BINSTATREP Logical signal status report 3 3
RANGE_XP Measured value expander block 66 66
I103MEAS Measurands for IEC 60870-5-103 1 1
I103MEASUSR Measurands user defined signals for IEC 60870-5-103 3 3
I103AR Function status auto-recloser for IEC 60870-5-103 1 1
I103EF Function status earth-fault for IEC 60870-5-103 1 1
I103FLTPROT Function status fault protection for IEC 60870-5-103 1 1
I103IED IED status for IEC 60870-5-103 1 1
I103SUPERV Supervision status for IEC 60870-5-103 1 1
I103USRDEF Status for user defined signals for IEC 60870-5-103 20 20
L4UFCNT Event counter with limit supervision 30 30
TEILGAPC Running hour meter 6 6
FLTMMXU Fault current and voltage monitoring 3 3
Metering
PCFCNT Pulse-counter logic 16 16
ETPMMTR Function for energy calculation and demand handling 6 6

Table 3: Number of function instances in APC5

Function name Function description Total number of instances


SCILO Interlocking 5
BB_ES 2
ABC_LINE 1
AB_TRAFO 1
SCSWI Switch controller 5
SXSWI Circuit switch 4
QCRSV Reservation function block for apparatus 2
control
RESIN1 1
RESIN2 59
POS_EVAL Evaluation of position indication 5
XLNPROXY Proxy for signals from switching device via 7
GOOSE
GOOSEXLNRCV GOOSE function block to receive a 7
switching device

46 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 2
Available functions

Table 4: Total number of instances for basic configurable logic blocks

Basic configurable logic block Total number of instances


AND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40

2.4 Communication GUID-C1FB7B84-2F43-4F15-9264-F33832C8036B v2

IEC 61850 or function


ANSI Function description Transformer
name
RET650 (A01) RET650 (A05)
Station communication
LONSPA, SPA SPA communication protocol 1 1
ADE LON communication protocol 1 1
HORZCOMM Network variables via LON 1 1
PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM 1 1
RS485PROT Operation selection for RS485 1 1
RS485GEN RS485 1 1
DNPGEN DNP3.0 communication general protocol 1 1
CHSERRS485 DNP3.0 for EIA-485 communication protocol 1 1
CH1TCP, CH2TCP, DNP3.0 for TCP/IP communication protocol 1 1
CH3TCP, CH4TCP
CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol 1 1
MSTSER DNP3.0 serial master 1 1
MST1TCP, MST2TCP, DNP3.0 for TCP/IP communication protocol 1 1
MST3TCP, MST4TCP
DNPFREC DNP3.0 fault records for TCP/IP and EIA-485 communication 1 1
protocol
IEC 61850-8-1 IEC 61850 1 1
IEC 61850SIM IEC 61850 simulation mode 1 1
GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59 59
GOOSEBINRCV GOOSE binary receive 16 16
GOOSEDPRCV GOOSE function block to receive a double point value 64 64
GOOSEINTRCV GOOSE function block to receive an integer value 32 32
GOOSEMVRCV GOOSE function block to receive a measurand value 60 60
GOOSESPRCV GOOSE function block to receive a single point value 64 64
ALGOS Supervision of GOOSE subscription 100 100
MULTICMDRCV/ Multiple command receive and send 60/10 60/10
MULTICMDSND
OPTICAL103 IEC 60870-5-103 Optical serial communication 1 1
RS485103 IEC 60870-5-103 serial communication for RS485 1 1
Table continues on next page

Transformer protection RET650 47


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 2 1MRK504170-UEN Rev. J
Available functions

IEC 61850 or function


ANSI Function description Transformer
name
RET650 (A01) RET650 (A05)
AGSAL Generic security application component 1 1
LD0LLN0 IEC 61850 LD0 LLN0 1 1
SYSLLN0 IEC 61850 SYS LLN0 1 1
LPHD Physical device information 1 1
PCMACCS IED configuration protocol 1 1
SECALARM Component for mapping security events on protocols such as 1 1
DNP3 and IEC103
FSTACCSNA Field service tool access via SPA protocol over Ethernet 1 1
communication
FSTACCS Field service tool access 1 1
GOOSEACRCV GOOSE function block to receive a protection activation 16 16
information
IEC 61850-9-2 Process bus communication, 4 merging units 1-P31 1-P31
ACTIVLOG Activity logging 1 1
ALTRK Service tracking 1 1
PRP IEC 62439-3 Parallel redundancy protocol 1-P23 1-P23
HSR IEC 62439-3 High-availability seamless redundancy 1-P24 1-P24
RSTP IEC 62439-3 Rapid spanning tree protocol 1-P25 1-P25
SNMPSERVERCONF SNMPServerConfiguration 1 1
SNMPUSERCONF SNMPUserConfiguration 2 2
AP_1-AP_4 AccessPoint_ABS1-AccessPoint_ABS4 1 1
AP_FRONT Access point front 1 1
PTP Precision time protocol 1 1
ROUTE_1-ROUTE_6 Route_ABS1-Route_ABS6 1 1
FRONTSTATUS Access point diagnostic for front Ethernet port 1 1
SCHLCCH Access point diagnostic for non-redundant Ethernet port 4 4
RCHLCCH Access point diagnostic for redundant Ethernet ports 2 2
DHCP DHCP configuration for front access point 1 1
QUALEXP IEC 61850 quality expander 32 32

2.5 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v15

Table 5: Basic IED functions

IEC 61850 or function Description


name
INTERRSIG
Self supervision with internal event list
SELFSUPEVLST
TIMESYNCHGEN Time synchronization module
BININPUT, SYNCHCAN, Time synchronization
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
TIMEZONE
DSTBEGIN GPS time synchronization module
DSTENABLE Enables or disables the use of daylight saving time
Table continues on next page

48 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 2
Available functions

IEC 61850 or function Description


name
DSTEND GPS time synchronization module
IRIG-B Time synchronization
SETGRPS Number of setting groups
ACTVGRP Active parameter setting group
TESTMODE Test mode functionality
CHNGLCK Change lock function
TERMINALID IED identifiers
PRODINF Product information
SYSTEMTIME System time
LONGEN LON communication
RUNTIME IED Runtime component
SMBI Signal matrix for binary inputs
SMBO Signal matrix for binary outputs
SMAI1 - SMAI12 Signal matrix for analog inputs
3PHSUM Summation block 3 phase
ATHSTAT Authority status
ATHCHCK Authority check
AUTHMAN Authority management
FTPACCS FTP access with password
SPACOMMMAP SPA communication mapping
SPATD Date and time via SPA protocol
BCSCONF Basic communication system
GBASVAL Global base values for settings
PRIMVAL Primary system values
SAFEFILECOPY Safe file copy function
ALTMS Time master supervision
ALTIM Time management
CAMCONFIG Central account management configuration
CAMSTATUS Central account management status
TOOLINF Tools information
COMSTATUS Protocol diagnostic

Table 6: Local HMI functions

IEC 61850 or function Description


name
LHMICTRL Local HMI signals
LANGUAGE Local human machine language
SCREEN Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600
FNKEYMD1–
FNKEYMD5
Table continues on next page

Transformer protection RET650 49


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 2 1MRK504170-UEN Rev. J
Available functions

IEC 61850 or function Description


name
LEDGEN General LED indication part for LHMI
OPENCLOSE_LED LHMI LEDs for open and close keys
GRP1_LED1– Basic part for CP HW LED indication module
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

50 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 3
Analog inputs

Section 3 Analog inputs SEMOD55010-1 v3

3.1 Introduction SEMOD55003-5 v11

Analog input channels must be configured and set properly in order to get correct measurement
results and correct protection operations. For power measuring, all directional and differential
functions, the directions of the input currents must be defined in order to reflect the way the current
transformers are installed/connected in the field ( primary and secondary connections ). Measuring
and protection algorithms in the IED use primary system quantities. Setting values are in primary
quantities as well and it is important to set the data about the connected current and voltage
transformers properly.

An AISVBAS reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channel's phase angle will always be fixed to zero degrees and remaining analog channel's
phase angle information will be shown in relation to this analog input. During testing and
commissioning of the IED, the reference channel can be changed to facilitate testing and service
values reading.

The IED has the ability to receive analog values from primary equipment, that are
sampled by Merging units (MU) connected to a process bus, via the IEC 61850-9-2 LE
protocol.

The availability of VT inputs depends on the ordered transformer input module (TRM)
type.

3.2 Function block SEMOD116577-1 v5

The hardware channels appear in the signal matrix tool (SMT) and in ACT when a TRM is
included in the configuration with the hardware configuration tool. In the SMT or the ACT,
they can be mapped to the desired virtual input (SMAI) of the IED and used internally in
the configuration.

3.3 Signals
PID-3923-OUTPUTSIGNALS v7

Table 7: TRM_7I_5U Output signals

Name Type Description


STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

Transformer protection RET650 51


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 3 1MRK504170-UEN Rev. J
Analog inputs

PID-3924-OUTPUTSIGNALS v7

Table 8: TRM_9I_3U Output signals

Name Type Description


STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-6598-OUTPUTSIGNALS v6

Table 9: TRM_10I_2U Output signals

Name Type Description


STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(I) STRING Analogue current input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

3.4 Settings
SEMOD129840-4 v2
Dependent on ordered IED type.

52 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 3
Analog inputs

PID-4153-SETTINGS v8

Table 10: AISVBAS Non group settings (basic)

Name Values (Range) Unit Step Default Description


PhaseAngleRef TRM40-Ch1 - Ch12 - - TRM40-Ch1 Reference channel
TRM41-Ch1 - Ch12 for phase angle
MU1-L1I - L4I presentation
MU1-L1U - L4U
MU2-L1I - L4I
MU2-L1U - L4U
MU3-L1I - L4I
MU3-L1U - L4U
MU4-L1I - L4I
MU4-L1U - L4U
MU5-L1I - L4I
MU5-L1U - L4U
MU6-L1I - L4I
MU6-L1U - L4U
MU7-L1I - L4I
MU7-L1U - L4U
MU8-L1I - L4I
MU8-L1U - L4U
MU9-L1I - L4I
MU9-L1U - L4U
MU10-L1I - L4I
MU10-L1U - L4U
MU11-L1I - L4I
MU11-L1U - L4U
MU12-L1I - L4I
MU12-L1U - L4U

GUID-72A8BEE0-2430-4C94-A1E0-9B6A0D149FE2 v2

All the visible parameter selections are not supported by the 650-series IED.

PID-3923-SETTINGS v7

Table 11: TRM_7I_5U Non group settings (basic)

Name Values (Range) Unit Step Default Description


CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

Transformer protection RET650 53


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 3 1MRK504170-UEN Rev. J
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-3924-SETTINGS v7

Table 12: TRM_9I_3U Non group settings (basic)

Name Values (Range) Unit Step Default Description


CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

54 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 3
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-6598-SETTINGS v6

Table 13: TRM_10I_2U Non group settings (basic)

Name Values (Range) Unit Step Default Description


CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

Transformer protection RET650 55


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 3 1MRK504170-UEN Rev. J
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

3.5 Monitored data


PID-6531-MONITOREDDATA v3

Table 14: AISVBAS Monitored data

Name Type Values (Range) Unit Description


Status INTEGER 0=Ok - Service value status
1=Error
2=AngRefLow
3=Uncorrelated

PID-3923-MONITOREDDATA v6

Table 15: TRM_7I_5U Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-3924-MONITOREDDATA v6

Table 16: TRM_9I_3U Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-6598-MONITOREDDATA v6

Table 17: TRM_10I_2U Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

3.6 Operation principle SEMOD55028-5 v9

The direction of a measured current depends on the connection of the CT. The main CTs are typically
star connected and can be connected with the star point towards the object or away from the object.
This information must be set in the IED.

Once the CT direction settings is correctly entered the internal IED convention of the directionality is
defined as follows:

56 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 3
Analog inputs

• Positive value of current or power means that the quantity has the direction into the protected
object.
• Negative value of current or power means that the quantity has the direction out from the
protected object.

For directional functions the directional conventions are defined as follows (see Figure 5)

• Forward means the direction is into the object.


• Reverse means the direction is out from the object.

Definition of direction Definition of direction


for directional functions for directional functions
Reverse Forward Forward Reverse
Protected Object
Line, transformer, etc
e.g. P, Q, I e.g. P, Q, I
Measured quantity is Measured quantity is
positive when flowing positive when flowing
towards the object towards the object

Set parameter Set parameter


CTStarPoint CTStarPoint
Correct Setting is Correct Setting is
"ToObject" "FromObject"

en05000456.vsd
IEC05000456 V1 EN-US

Figure 5: Internal convention of the directionality in the IED


If the settings of the primary CT is correct, that is CTStarPoint set as FromObject or ToObject
according to the plant condition, then a positive quantity always flows towards the protected object,
and a Forward direction always looks towards the protected object.

The settings of the IED is performed in primary values. The ratios of the main CTs and VTs are,
therefore, basic data for the IED. The user has to set the rated secondary and primary currents and
voltages of the CTs and VTs to provide the IED with their rated ratios.

The CT and VT ratio and the name on respective channel is done under IED Configuration /HW
Configuration /ADM in the Parameter Settings Tool or under Main menu /Configuration /Analog
modules in the HMI.

3.7 Technical data SEMOD55412-1 v1

M16988-1 v11

Table 18: TRM - Energizing quantities, rated values and limits for protection transformer

Description Value
Frequency
Rated frequency fr 50/60 Hz
Operating range fr ± 10%
Current inputs
Rated current Ir 1 or 5 A
Operating range (0-100) x Ir
Thermal withstand 100 × Ir for 1 s *)
30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously

Table continues on next page

Transformer protection RET650 57


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 3 1MRK504170-UEN Rev. J
Analog inputs

Description Value
Dynamic withstand 250 × Ir one half wave
Burden < 20 mVA at Ir = 1 A
< 150 mVA at Ir = 5 A
*) max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs **)
Rated voltage Ur 110 or 220 V
Operating range 0 - 340 V
Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

SEMOD53376-2 v6

Table 19: CT and VT circuit connectors

Connector type Rated voltage and current Maximum conductor area


Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm 2 (AWG12)

58 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 4
Binary input and output modules

Section 4 Binary input and output modules


4.1 Binary input

4.1.1 Binary input debounce filter GUID-AE43976C-E966-484C-AF39-89B2B12F56DC v5

The debounce filter eliminates bounces and short disturbances on a binary input.

A time counter is used for filtering. The time counter is increased once in a millisecond when a binary
input is high, or decreased when a binary input is low. A new debounced binary input signal is
forwarded when the time counter reaches the set DebounceTime value and the debounced input
value is high or when the time counter reaches 0 and the debounced input value is low. The default
setting of DebounceTime is 1 ms.

The binary input ON-event gets the time stamp of the first rising edge, after which the counter does
not reach 0 again. The same happens when the signal goes down to 0 again.

4.1.2 Oscillation filter GUID-41B89E6F-50C3-44BF-9171-3CC82EB5CA15 v5

Binary input wiring can be very long in substations and there are electromagnetic fields from for
example nearby breakers. An oscillation filter is used to reduce the disturbance from the system
when a binary input starts oscillating.

An oscillation counter counts the debounced signal state changes during 1 s. If the counter value is
greater than the set value OscBlock, the input signal is blocked. The input signal is ignored until the
oscillation counter value during 1 s is below the set value OscRelease.

4.1.3 Settings
GUID-07348953-4A72-444B-A31A-030ABEA8E0C4 v1

OscBlock must always be set to a value greater than OscRelease. If this is not done,
oscillation detection will not function correctly, and the resulting behaviour will be
undefined.

4.1.3.1 Setting parameters for binary input modules


PID-3473-SETTINGS v2

Table 20: BIM Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Operation Off/On
On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

Transformer protection RET650 59


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 4 1MRK504170-UEN Rev. J
Binary input and output modules

4.1.3.2 Setting parameters for binary input/output module


PID-4050-SETTINGS v2

Table 21: IOMIN Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Binary input/output module in operation
On (On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

60 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

Section 5 Local Human-Machine-Interface LHMI


5.1 Local HMI screen behaviour
GUID-490B84C3-6255-458A-A366-7091D7343C8F v1

Instead of the LHMI the Remote IED Access tool, RIA600, can be used and perform all of
the actions that a physical LHMI can.
Information about LHMI working procedures is also valid when the operation is performed
through RIA600. For more information on RIA600 operations, see manual Remote HMI
client RIA600 user guide (1MRK 511 619-UEN).

5.1.1 Identification
GUID-84392EFF-4D3F-4A67-A6ED-34C6E98574D6 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI screen behaviour SCREEN - -

5.1.2 Settings

5.2 Local HMI signals

5.2.1 Identification
GUID-03AB7AEE-87D3-4F3C-B6B9-B1EB1B538E38 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI signals LHMICTRL - -

5.2.2 Function block GUID-A8AC51E9-5BD7-4A80-9576-4816F14DD08D v2

LHMICTRL
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD

IEC09000320-1-en.vsd
IEC09000320 V1 EN-US

Figure 6: LHMICTRL function block

5.2.3 Signals
PID-3992-INPUTSIGNALS v6

Table 22: LHMICTRL Input signals

Name Type Default Description


CLRLEDS BOOLEAN 0 Input to clear the LCD-HMI LEDs

Transformer protection RET650 61


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

PID-3992-OUTPUTSIGNALS v6

Table 23: LHMICTRL Output signals

Name Type Description


HMI-ON BOOLEAN Backlight of the LCD display is active
RED-S BOOLEAN Red LED on the LCD-HMI is steady
YELLOW-S BOOLEAN Yellow LED on the LCD-HMI is steady
YELLOW-F BOOLEAN Yellow LED on the LCD-HMI is flashing
CLRPULSE BOOLEAN A pulse is provided when the LEDs on the LCD-HMI are cleared
LEDSCLRD BOOLEAN Active when the LEDs on the LCD-HMI are not active

5.3 Basic part for LED indication module

5.3.1 Identification
GUID-6E36C0BC-F284-4C88-A4A8-9535D3BE8B14 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Basic part for LED indication module LEDGEN - -
Basic part for LED indication HW GRP1_LED1 - - -
module GRP1_LED15

GRP2_LED1 -
GRP2_LED15

GRP3_LED1 -
GRP3_LED15

5.3.2 Function block GUID-BDB5797F-F27E-4FEE-9FDB-1C9E2F572BB6 v3

LEDGEN
BLOCK NEWIND
RESET ACK

IEC09000321-1-en.vsd
IEC09000321 V1 EN-US

Figure 7: LEDGEN function block

GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN-US

Figure 8: GRP1_LED1 function block


The GRP1_LED1 function block is an example. The 15 LEDs in each of the three groups have a
similar function block.

5.3.3 Signals
PID-4114-INPUTSIGNALS v5

Table 24: LEDGEN Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Input to block the operation of the LEDs
RESET BOOLEAN 0 Input to acknowledge/reset the indication LEDs

62 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

PID-4114-OUTPUTSIGNALS v5

Table 25: LEDGEN Output signals

Name Type Description


NEWIND BOOLEAN New indication signal if any LED indication input is set
ACK BOOLEAN A pulse is provided when the LEDs are acknowledged

PID-1697-INPUTSIGNALS v18

Table 26: GRP1_LED1 Input signals

Name Type Default Description


HM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1
HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1
HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 1

5.3.4 Settings
PID-4114-SETTINGS v6

Table 27: LEDGEN Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Operation Off/On
On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance

PID-1697-SETTINGS v18

Table 28: GRP1_LED1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


SequenceType Follow-S - - Follow-S Sequence type for LED 1, local HMI alarm
Follow-F group 1
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green

5.4 LCD part for HMI function keys control module GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2

5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
LCD part for HMI Function Keys Control FNKEYMD1 - - -
module FNKEYMD5

Transformer protection RET650 63


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

5.4.2 Function block


GUID-A803A728-5CFC-4606-98E4-793E873B99D4 v3

FNKEYMD1
ENABLE ^FKEYOUT1
^LEDCTL1

IEC09000327 V2 EN-US

Figure 9: FNKEYMD1 function block


Only the function block for the first button is shown above. There is a similar block for every function
key button.

5.4.3 Signals
PID-7424-INPUTSIGNALS v1

Table 29: FNKEYMD1 Input signals

Name Type Default Description


ENABLE BOOLEAN 1 Enable input for function key
LEDCTL1 BOOLEAN 0 LED control input for function key

PID-7424-OUTPUTSIGNALS v1

Table 30: FNKEYMD1 Output signals

Name Type Description


FKEYOUT1 BOOLEAN Output controlled by function key

5.4.4 Settings
PID-7424-SETTINGS v1

Table 31: FNKEYMD1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


Mode Off - - Off Output operation mode
Toggle
Pulsed
PulseTime 0.001 - 60.000 s 0.001 0.200 Pulse time for output controlled by
LCDFn1
LabelOn 0 - 18 - 1 LCD_FN1_ON Label for LED on state
LabelOff 0 - 18 - 1 LCD_FN1_OFF Label for LED off state
ReqAuthority Off - - On User authorization needed for function
On key operation

PID-7990-SETTINGS v1

Table 32: FNKEYTY1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


Type Off - - Off Function key type
Menu shortcut
Control
MenuShortcut - 0 Menu shortcut for function key

64 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

GUID-BCE87D54-C836-40EE-8DA7-779B767059AB v2

For setting ReqAuthority, when users are configured through local or central account
management, the default behavior of the function keys are to only operate if a user is
logged in, and the user have the required rights. This authentication check can be
configured to be bypassed per function key by changing the ReqAuthority from ON to
OFF. To be able to change this, the user changing it have to have the Security advanced
right.

MenuShortcut values are product dependent and created dynamically depending on the product
main menu.

5.5 Operation principle

5.5.1 Local HMI AMU0600442 v16

IEC13000239 V4 EN-US

Figure 10: Local human-machine interface


The LHMI of the IED contains the following elements

Transformer protection RET650 65


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

• Keypad
• Display (LCD)
• LED indicators
• Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

5.5.1.1 Keypad AMU0600428 v19

The LHMI keypad contains push-buttons which are used to navigate in different views or menus. The
push-buttons are also used to acknowledge alarms, reset indications, provide help and switch
between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured either as menu
shortcut or control buttons.

66 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

IEC15000157 V3 EN-US

Figure 11: LHMI keypad with object control, navigation and command push-buttons and
RJ-45 communication port

1...5 Function button


6 Close
7 Open
8 Escape
9 Left
10 Down
11 Up
12 Right
13 Key
14 Enter
15 Remote/Local
16 Uplink LED
17 Not in use
18 Multipage
19 Menu
20 Clear
21 Help
22 Communication port
23 Programmable indication LEDs

Transformer protection RET650 67


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

24 IED status LEDs

5.5.1.2 Display GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13

The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320 x
240 pixels. The character size can vary. The amount of characters and rows fitting the view depends
on the character size and the view that is shown.

The display view is divided into four basic areas.

IEC15000270-1-en.vsdx

IEC15000270 V1 EN-US

Figure 12: Display layout

1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)

• The path shows the current location in the menu structure. If the path is too long to be shown, it
is truncated from the beginning, and the truncation is indicated with three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in and the object
identification string which is settable via the LHMI or with PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the right.
The text in content area is truncated from the beginning if it does not fit in the display
horizontally. Truncation is indicated with three dots.

68 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

IEC15000138-1-en.vsdx

IEC15000138 V1 EN-US

Figure 13: Truncated path


The number after : (colon sign) at the end of the function instance, for example, 1 in SMAI1:1,
indicates the number of that function instance.

The function key button panel shows on request what actions are possible with the function buttons.
Each function button has a LED indication that can be used as a feedback signal for the function
button control action. The LED is connected to the required signal with PCM600.

IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US

Figure 14: Function button panel


The indication LED panel shows on request the alarm text labels for the indication LEDs. Three
indication LED pages are available.

Transformer protection RET650 69


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US

Figure 15: Indication LED panel


The function button and indication LED panels are not visible at the same time. Each panel is shown
by pressing one of the function buttons or the Multipage button. Pressing the ESC button clears the
panel from the display. Both panels have a dynamic width that depends on the label string length.

5.5.1.3 LEDs AMU0600427 v15

The LHMI includes three status LEDs above the display: Ready, Start and Trip.

There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate three
states with the colors: green, yellow and red. The texts related to each three-color LED are divided
into three panels.

There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LED group
can indicate 45 different signals. Altogether, 135 signals can be indicated since there are three LED
groups. The LEDs are lit according to priority, with red being the highest and green the lowest priority.
For example, if on one panel there is an indication that requires the green LED to be lit, and on
another panel there is an indication that requires the red LED to be lit, the red LED takes priority and
is lit. The LEDs can be configured with PCM600 and the operation mode can be selected with the
LHMI or PCM600.

Information panels for the indication LEDs are shown by pressing the Multipage button. Pressing that
button cycles through the three pages. A lit or un-acknowledged LED is indicated with a highlight.
Such lines can be selected by using the Up/Down arrow buttons. Pressing the Enter key shows
details about the selected LED. Pressing the ESC button exits from information pop-ups as well as
from the LED panel as such.

The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there are
un-acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, press the
Clear button to enter the Reset menu (refer to description of this menu for details).

There are two additional LEDs which are next to the control buttons and . These LEDs can
indicate the status of two arbitrary binary signals by configuring the OPENCLOSE_LED function
block. For instance, OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker
open/close status on the LEDs.

70 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

IEC16000076-1-en.vsd
IEC16000076 V1 EN-US

Figure 16: OPENCLOSE_LED connected to SXCBR

5.5.2 LED configuration alternatives

5.5.2.1 Functionality GUID-1A03E0EF-C10F-4797-9D9F-5CCA86CA29EB v5

The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) controls
and supplies information about the status of the indication LEDs. The input and output signals of the
function blocks are configured with PCM600. The input signal for each LED is selected individually
using SMT or ACT. Each LED is controlled by the GRPn_LEDx (n=1-3) function block that controls
the color and the operating mode.

Each indication LED on local HMI can be set individually to operate in 6 different sequences; two as
follow type and four as latch type. Two of the latching sequence types are intended to be used as a
protection indication system, either in collecting or restarting mode, with reset functionality. The other
two are intended to be used as signalling system in collecting mode with acknowledgment
functionality.

5.5.2.2 Status LEDs GUID-4822DF9C-E343-442B-B3F1-3FA8CD8DF234 v5

There are three status LEDs above the LCD in front of the IED: green, yellow and red.

The green LED has a fixed function that presents the healthy status of the IED. The yellow and red
LEDs are user configured. The yellow LED can be used to indicate that a disturbance report is
triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to indicate a
trip command.

Here is a typical configuration of the status LEDs:

• Green LED: unlit > no power; blinking > startup or abnormal situation (IED is not in service);
steady > IED is in service
• Yellow LED: unlit > no attention required; blinking > IED is in Testmode (IED is not in normal
service), or IED is in simulation mode or IED IEC 61850 mod value is set other than its normal
value; steady > at least one of the signals configured to turn the yellow LED on has been active
• Red LED: unlit > no attention required; blinking > user performs a common write from PCM600;
steady > at least one of the signals configured to turn the red LED on has been active

The yellow and red status LEDs are configured in the disturbance recorder function, DRPRDRE, by
connecting a start or trip signal from the actual function to a BxRBDR binary input function block
using the PCM600, and configuring the setting to Off, Start or Trip for that particular signal.

Transformer protection RET650 71


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

5.5.2.3 Indication LEDs


Operating modes GUID-B67F1ED3-900B-4D34-8EEB-A3005999CE50 v4

Collecting mode

• LEDs that are used in the collecting mode of operation are accumulated continuously until the
unit is acknowledged manually. This mode is suitable when the LEDs are used as a simplified
alarm system. When all three inputs (red, yellow and green) are connected to different sources
of events for the same function block, collecting mode shows the highest priority LED color that
was activated since the latest acknowledgment was made. If a number of different indications
were made since the latest acknowledgment, it is not possible to get a clear view of what
triggered the latest event without looking at the sequence of events list. A condition for getting
the sequence of events is that the signals have been engineered in the disturbance recorder.

Re-starting mode

• In the re-starting mode of operation each new start resets all previous active LEDs and activates
only those which appear during one disturbance. Only LEDs defined for re-starting mode with
the latched sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a new
disturbance. A disturbance is defined to end a settable time after the reset of the activated input
signals or when the maximum time limit has elapsed. In sequence 6, the restarting or reset
mode means that upon occurrence of any new event, all previous indications will be reset. This
facilitates that only the LED indications related to the latest event is shown.

Acknowledgment/reset GUID-E6727E8F-C28B-4295-AE21-BC5643363805 v3

• From local HMI


• The active LED indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a common signal for all
the operating sequences and LEDs. The function is positive edge triggered, not level
triggered. The acknowledgment/reset is performed via the button and menus on the
LHMI.

• From function input


• The active LED indications can also be acknowledged/reset via an input, CLRLEDS, to the
function block LHMICTRL. This input can for example be configured to a binary input
operated from an external push button or a function button. The function is positive edge
triggered, not level triggered. This means that even if the button is continuously pressed,
the acknowledgment/reset only affects indications active at the moment when the button is
first pressed.

• Automatic reset
• The automatic reset can only be performed for LED indications defined for re-starting
mode with the latched sequence type 6 (LatchedReset-S). When the automatic reset of
the LEDs has been performed, still persisting indications will be indicated with a steady
light.

Operating sequence GUID-DFCA880B-308C-4334-94DF-97C7765E8C13 v5


The sequences can be of type Follow or Latched. For the Follow type, the LED follows the input
signal completely. For the Latched type, each LED latches to the corresponding input signal until it is
reset.

The figures below show the function of available sequences selectable for each LED separately. The
following 6 sequences are available:

72 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

• Sequence 1: Follow-S
• Sequence 2: Follow-F
• Sequence 3: LatchedAck-F-S
• Sequence 4: LatchedAck-S-F
• Sequence 5: LatchedColl-S
• Sequence 6: LatchedReset-S

For sequence 1 and 2, which are of the Follow type, the acknowledgment (Ack ) /reset function is not
applicable because the indication shown by the LED follows its input signal. Sequence 3 and 4,
which are of the Latched type with acknowledgement, are only working in collecting (Coll) mode.
Sequence 5 is working according to Latched type and collecting mode while Sequence 6 is working
according to Latched type and re-starting (Reset) mode. The letters S and F in the sequence names
have the meaning S = Steady and F = Flash.

At the activation of the input signal to any LED, the indication on the corresponding LED obtains a
color that corresponds to the activated input, and operates according to the selected sequence
diagrams shown below.

In the sequence diagrams the different statuses of the LEDs are shown using the following symbols:

= No indication = Steady light = Flash

G= Green Y= Yellow R= Red


IEC09000311.vsd
IEC09000311 V1 EN-US

Figure 17: Symbols used in the sequence diagrams

Sequence 1 (Follow-S) SEMOD56072-39 v4


This sequence follows the corresponding input signals all the time with a steady light. It does not
react on acknowledgment or reset. Every LED is independent of the other LEDs in its operation.

Activating
signal

LED

IEC01000228_2_en.vsd
IEC01000228 V2 EN-US

Figure 18: Operating Sequence 1 (Follow-S)


GUID-107FE952-3B4C-4C01-831A-3147E652327C v4
If inputs for two or more colors are active at the same time to the same LED, the priority color it
shows is in accordance with the color described above. An example of the operation when two colors
are activated in parallel to the same LED is shown in figure19.

Activating
signal GREEN

Activating
signal RED

LED G G R G

IEC09000312_1_en.vsd
IEC09000312 V1 EN-US

Figure 19: Operating sequence 1, two colors

Transformer protection RET650 73


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

Sequence 2 (Follow-F) SEMOD56072-47 v2


This sequence is the same as Sequence 1, Follow-S, but the LEDs are flashing instead of showing
steady light.

Sequence 3 LatchedAck-F-S SEMOD56072-50 v2


This sequence has a latched function and works in collecting mode. Every LED is independent of the
other LEDs in its operation. At the activation of the input signal, the indication starts flashing. After
acknowledgment the indication disappears if the signal is not present any more. If the signal is still
present after acknowledgment it gets a steady light.

Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN-US

Figure 20: Operating Sequence 3 LatchedAck-F-S


GUID-CC607709-5344-4C88-AA97-6395FD335E55 v5

The sequence described below is valid only if the same function block is used for all three
colour LEDs.

When an acknowledgment is performed, all indications that appear before the indication with higher
priority has been reset, will be acknowledged, independent of if the low priority indication appeared
before or after acknowledgment. In figure 21 it is shown the sequence when a signal of lower priority
becomes activated after acknowledgment has been performed on a higher priority signal. The low
priority signal will be shown as acknowledged when the high priority signal resets.

Activating
signal GREEN

Activating
signal RED

R R G
LED

Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN-US

Figure 21: Operating Sequence 3 (LatchedAck-F-S), 2 colors involved


GUID-A652A49D-F016-472D-8D38-6D3E75DAB1DB v3
If all three signals are activated the order of priority is still maintained. Acknowledgment of indications
with higher priority will acknowledge also low priority indications, which are not visible according to
figure 22.

74 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G Y R R Y

Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN-US

Figure 22: Operating sequence 3, three colors involved, alternative 1


GUID-071B9EB5-A1D2-49C5-9458-4D21B7E068BE v3
If an indication with higher priority appears after acknowledgment of a lower priority indication the
high priority indication will be shown as not acknowledged according to figure 23.

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G G R R Y

Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN-US

Figure 23: Operating sequence 3, three colors involved, alternative 2

Sequence 4 (LatchedAck-S-F) SEMOD56072-64 v1


This sequence has the same functionality as sequence 3, but steady and flashing light have been
alternated.

Sequence 5 LatchedColl-S SEMOD56072-67 v4


This sequence has a latched function and works in collecting mode. At the activation of the input
signal, the indication will light up with a steady light. The difference to sequence 3 and 4 is that
indications that are still activated will not be affected by the reset that is, immediately after the
positive edge of the reset has been executed a new reading and storing of active signals is
performed. Every LED is independent of the other LEDs in its operation.

Transformer protection RET650 75


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

Activating
signal

LED

Reset

IEC01000235_2_en.vsd
IEC01000235 V2 EN-US

Figure 24: Operating Sequence 5 LatchedColl-S


GUID-4D52D221-F54F-4966-95B1-6ED6C536CEC9 v3
That means if an indication with higher priority has reset while an indication with lower priority still is
active at the time of reset, the LED will change color according to figure25.

Activating
signal GREEN

Activating
signal RED

R G
LED

Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN-US

Figure 25: Operating sequence 5, two colors

Sequence 6 LatchedReset-S SEMOD56072-75 v4


In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are automatically
reset at a new disturbance when activating any input signal for other LEDs set to Sequence 6
LatchedReset-S. Also in this case indications that are still activated will not be affected by manual
reset, that is, immediately after the positive edge of that the manual reset has been executed a new
reading and storing of active signals is performed. LEDs set for sequence 6 are completely
independent in its operation of LEDs set for other sequences.

Timing diagram for sequence 6 SEMOD56072-86 v4


Figure 26 shows the timing diagram for two indications within one disturbance.

76 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

Disturbance
tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN-US

Figure 26: Operating sequence 6 (LatchedReset-S), two indications within same disturbance
Figure 27 shows the timing diagram for a new indication after tRestart time has elapsed.

Disturbance Disturbance

tRestart tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN-US

Figure 27: Operating sequence 6 (LatchedReset-S), two different disturbances


Figure 28 shows the timing diagram when a new indication appears after the first one has reset but
before tRestart has elapsed.

Transformer protection RET650 77


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN-US

Figure 28: Operating sequence 6 (LatchedReset-S), two indications within same disturbance
but with reset of activating signal between
Figure 29 shows the timing diagram for manual reset.

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN-US

Figure 29: Operating sequence 6 (LatchedReset-S), manual reset

78 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 5
Local Human-Machine-Interface LHMI

5.5.3 Function keys

5.5.3.1 Functionality GUID-BED38E9A-C90D-4B7F-AA20-42821C4F6A1C v3

Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of the LCD, that
can be configured either as menu shortcut or control buttons. Each button has an indication LED that
can be configured in the application configuration.

When used as a menu shortcut, a function button provides a fast way to navigate between default
nodes in the menu tree. When used as a control, the button can control a binary signal.

5.5.3.2 Operation principle GUID-977C3829-B19B-457E-8A4D-45317226EF22 v3

Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from the LHMI
function keys. By pressing a function button on the LHMI, the output status of the actual function
block will change. These binary outputs can in turn be used to control other function blocks, for
example, switch control blocks, binary I/O outputs etc.

FNKEYMD1 - FNKEYMD5 function block also has a number of settings and parameters that control
the behavior of the function block. These settings and parameters are normally set using the PST.

Operating sequence GUID-84CA7C61-4F83-4F86-A07F-BF9EC4E309BF v5


The operation mode is set individually for each output, either OFF, TOGGLE or PULSED.

Setting OFF

This mode always sets the outputs to a low value (0).

Input value

Output value

IEC09000330-2-en.vsd

IEC09000330 V2 EN-US

Figure 30: Sequence diagram for setting OFF


Setting TOGGLE

In this mode the output toggles each time the function key has been pressed for more than 500ms.
Note that the input attribute is reset each time the function block executes. The function block
execution is marked with a dotted line below.

Input value
500ms 500ms 500ms

Output value

IEC09000331_1_en.vsd

IEC09000331 V2 EN-US

Figure 31: Sequence diagram for setting TOGGLE


Setting PULSED

Transformer protection RET650 79


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 5 1MRK504170-UEN Rev. J
Local Human-Machine-Interface LHMI

In this mode the output sets high (1) when the function key has been pressed for more than 500ms
and remains high according to set pulse time. After this time the output will go back to 0. The input
attribute is reset when the function block detects it being high and there is no output pulse.

Note that the third positive edge on the input attribute does not cause a pulse, since the edge was
applied during pulse output. A new pulse can only begin when the output is zero; else the trigger
edge is lost.

Input value
500ms 500ms 500ms 500ms

pulse time pulse time pulse time


Output value

IEC09000332_2_en.vsd

IEC09000332 V2 EN-US

Figure 32: Sequence diagram for setting PULSED

Input function GUID-8EA4AE21-7A74-403A-84AE-D5CEF9292A63 v2


All function keys work the same way: When the LHMI is configured so that a certain function button is
of type CONTROL, then the corresponding input on this function block becomes active, and will light
the yellow function button LED when high. This functionality is active even if the function block
operation setting is set to off. It has been implemented this way for safety reasons; the idea is that
the function key LEDs should always reflect the actual status of any primary equipment monitored by
these LEDs.

5.5.3.3 Enabling and Disabling Authority on Function keys GUID-27413370-00F4-477D-886F-30359C788B55 v1

When users are configured through local or central account management, the default behavior of the
function keys are to only operate if a user is logged in, and the user have the required rights. This
authentication check can be configured to be bypassed per function key by changing the
ReqAuthority from ON to OFF. To be able to change this, the user changing it have to have the
Security advanced right.

Authority can be disabled using parameter Authority. Each function key has the parameter Authority,
which can be enabled or disabled using LHMI or PCM 600. User must have Security Advanced rights
to configure the Authority parameter of the function key.

The possible values for the Authority parameter are as below:

• Enabled: Requires authentication


• Disabled: No user authentication

If there is no User Account Management or Central Account Management configured in


the IED then this parameter has no effect and the function key can be operated without
any authentication.

80 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Section 6 Differential protection


6.1 Transformer differential protection T2WPDIF and
T3WPDIF IP14639-1 v3

6.1.1 Identification
M15074-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Transformer differential protection, two- T2WPDIF 87T
winding
3Id/I

SYMBOL-BB V1 EN-US

Transformer differential protection, T3WPDIF 87T


three-winding
3Id/I

SYMBOL-BB V1 EN-US

6.1.2 Functionality M16104-3 v19

The Transformer differential protection is provided with internal CT ratio matching, vector group
compensation and settable zero sequence current elimination.

The function can be provided with two or three three-phase sets of current inputs if enough HW is
available. All current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer in multi-breaker station arrangements.

Two-winding applications
two-winding power
transformer
xx05000048.vsd
IEC05000048 V1 EN-US

two-winding power
transformer with
unconnected delta
xx05000049.vsd tertiary winding
IEC05000049 V1 EN-US

two-winding power
transformer with two
circuit breakers and
xx05000050.vsd two CT-sets on one
IEC05000050 V1 EN-US
side
two-winding power
transformer with two
circuit breakers and
two CT-sets on both
sides

xx05000051.vsd
IEC05000051 V1 EN-US

Three-winding applications
Table continues on next page

Transformer protection RET650 81


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

three-winding power
transformer with all
three windings
connected

xx05000052.vsd
IEC05000052 V1 EN-US

three-winding power
transformer with two
circuit breakers and
two CT-sets on one
side

xx05000053.vsd
IEC05000053 V1 EN-US

Autotransformer with
two circuit breakers
and two CT-sets on
two out of three sides

xx05000057.vsd
IEC05000057 V1 EN-US

Figure 33: CT group arrangement


for differential protection

Stabilization is included for inrush and overexcitation currents respectively, cross-blocking is also
available. Adaptive stabilization is also included for system recovery inrush and CT saturation during
external faults. A high set unrestrained differential current protection element is included for a very
high speed tripping at high internal fault currents.

Included is an sensitive differential protection element based on the theory of negative sequence
current component. This element offers the best possible coverage of power transformer windings
turn to turn faults.

82 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

6.1.3 Function block IP12643-1 v1

SEMOD54397-4 v5

T2WPDIF
I3PW1CT1* TRIP
I3PW1CT2* TRIPRES
I3PW2CT1* TRIPUNRE
I3PW2CT2* TRNSUNR
TAPOLTC1 TRNSSENS
OLTC1AL START
BLOCK STL1
BLKRES STL2
BLKUNRES STL3
BLKNSUNR BLK2H
BLKNSSEN BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000249_2_en.vsd
IEC06000249 V2 EN-US

Figure 34: T2WPDIF function block


SEMOD54551-4 v5

T3WPDIF
I3PW1CT1* TRIP
I3PW1CT2* TRIPRES
I3PW2CT1* TRIPUNRE
I3PW2CT2* TRNSUNR
I3PW3CT1* TRNSSENS
I3PW3CT2* START
TAPOLTC1 STL1
TAPOLTC2 STL2
OLTC1AL STL3
OLTC2AL BLK2H
BLOCK BLK2HL1
BLKRES BLK2HL2
BLKUNRES BLK2HL3
BLKNSUNR BLK5H
BLKNSSEN BLK5HL1
BLK5HL2
BLK5HL3
BLKWAV
BLKWAVL1
BLKWAVL2
BLKWAVL3
IDALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG

IEC06000250_2_en.vsd
IEC06000250 V2 EN-US

Figure 35: T3WPDIF function block

Transformer protection RET650 83


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

6.1.4 Signals
PID-6758-INPUTSIGNALS v1

Table 33: T2WPDIF Input signals

Name Type Default Description


I3PW1CT1 GROUP - Three phase winding primary CT1
SIGNAL
I3PW1CT2 GROUP - Three phase winding primary CT2
SIGNAL
I3PW2CT1 GROUP - Three phase winding secondary CT1
SIGNAL
I3PW2CT2 GROUP - Three phase winding secondary CT2
SIGNAL
TAPOLTC1 INTEGER 1 Most recent tap position reading on OLTC 1
OLTC1AL BOOLEAN 0 OLTC1 alarm
BLOCK BOOLEAN 0 Block of function
BLKRES BOOLEAN 0 Block of trip for restrained differential feature
BLKUNRES BOOLEAN 0 Block of trip for unrestrained differential feature
BLKNSUNR BOOLEAN 0 Block of trip for unrestr. neg. seq. differential feature
BLKNSSEN BOOLEAN 0 Block of trip for sensitive neg. seq. differential feature

PID-6758-OUTPUTSIGNALS v1

Table 34: T2WPDIF Output signals

Name Type Description


TRIP BOOLEAN General, common trip signal
TRIPRES BOOLEAN Trip signal from restrained differential protection
TRIPUNRE BOOLEAN Trip signal from unrestrained differential protection
TRNSUNR BOOLEAN Trip signal from unrestr. neg. seq. diff. protection
TRNSSENS BOOLEAN Trip signal from sensitive neg. seq. diff. protection
START BOOLEAN Common start signal from any phase
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
BLK2H BOOLEAN Common second harmonic block signal from any phase
BLK2HL1 BOOLEAN Second harmonic block signal, phase L1
BLK2HL2 BOOLEAN Second harmonic block signal, phase L2
BLK2HL3 BOOLEAN Second harmonic block signal, phase L3
BLK5H BOOLEAN Common fifth harmonic block signal from any phase
BLK5HL1 BOOLEAN Fifth harmonic block signal, phase L1
BLK5HL2 BOOLEAN Fifth harmonic block signal, phase L2
BLK5HL3 BOOLEAN Fifth harmonic block signal, phase L3
BLKWAV BOOLEAN Common block signal, waveform criterion, from any phase
BLKWAVL1 BOOLEAN Block signal, waveform criterion, phase L1
BLKWAVL2 BOOLEAN Block signal, waveform criterion, phase L2
BLKWAVL3 BOOLEAN Block signal, waveform criterion, phase L3
IDALARM BOOLEAN Alarm for sustained diff currents in all three phases
OPENCT BOOLEAN An open CT was detected
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a delay ...
IDL1 REAL Value of the instantaneous differential current, phase L1
Table continues on next page

84 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Name Type Description


IDL2 REAL Value of the instantaneous differential current, phase L2
IDL3 REAL Value of the instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fundamental freq. diff. current, phase L1
IDL2MAG REAL Magnitude of fundamental freq. diff. current, phase L2
IDL3MAG REAL Magnitude of fundamental freq. diff. current, phase L3
IBIAS REAL Magnitude of the bias current, which is common to all phases
IDNSMAG REAL Magnitude of the negative sequence differential current

PID-6757-INPUTSIGNALS v1

Table 35: T3WPDIF Input signals

Name Type Default Description


I3PW1CT1 GROUP - Three phase winding primary CT1
SIGNAL
I3PW1CT2 GROUP - Three phase winding primary CT2
SIGNAL
I3PW2CT1 GROUP - Three phase winding secondary CT1
SIGNAL
I3PW2CT2 GROUP - Three phase winding secondary CT2
SIGNAL
I3PW3CT1 GROUP - Three phase winding tertiary CT1
SIGNAL
I3PW3CT2 GROUP - Three phase winding tertiary CT2
SIGNAL
TAPOLTC1 INTEGER 1 Most recent tap position reading on OLTC 1
TAPOLTC2 INTEGER 1 Most recent tap position reading on OLTC 2
OLTC1AL BOOLEAN 0 OLTC1 alarm
OLTC2AL BOOLEAN 0 OLTC2 alarm
BLOCK BOOLEAN 0 Block of function
BLKRES BOOLEAN 0 Block of trip for restrained differential feature
BLKUNRES BOOLEAN 0 Block of trip for unrestrained differential feature
BLKNSUNR BOOLEAN 0 Block of trip for unrestr. neg. seq. differential feature
BLKNSSEN BOOLEAN 0 Block of trip for sensitive neg. seq. differential feature

GUID-C76675EF-0201-484E-90CE-124B584F6438 v1

TAPOLTC1, TAPOLTC2, OLTC1AL and OLTC2AL are not supported by the 650 products
due to hardware restrictions.

PID-6757-OUTPUTSIGNALS v1

Table 36: T3WPDIF Output signals

Name Type Description


TRIP BOOLEAN General, common trip signal
TRIPRES BOOLEAN Trip signal from restrained differential protection
TRIPUNRE BOOLEAN Trip signal from unrestrained differential protection
TRNSUNR BOOLEAN Trip signal from unrestr. neg. seq. diff. protection
TRNSSENS BOOLEAN Trip signal from sensitive neg. seq. diff. protection
START BOOLEAN Common start signal from any phase
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
Table continues on next page

Transformer protection RET650 85


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Name Type Description


BLK2H BOOLEAN Common second harmonic block signal from any phase
BLK2HL1 BOOLEAN Second harmonic block signal, phase L1
BLK2HL2 BOOLEAN Second harmonic block signal, phase L2
BLK2HL3 BOOLEAN Second harmonic block signal, phase L3
BLK5H BOOLEAN Common fifth harmonic block signal from any phase
BLK5HL1 BOOLEAN Fifth harmonic block signal, phase L1
BLK5HL2 BOOLEAN Fifth harmonic block signal, phase L2
BLK5HL3 BOOLEAN Fifth harmonic block signal, phase L3
BLKWAV BOOLEAN Common block signal, waveform criterion, from any phase
BLKWAVL1 BOOLEAN Block signal, waveform criterion, phase L1
BLKWAVL2 BOOLEAN Block signal, waveform criterion, phase L2
BLKWAVL3 BOOLEAN Block signal, waveform criterion, phase L3
IDALARM BOOLEAN Alarm for sustained diff currents in all three phases
OPENCT BOOLEAN An open CT was detected
OPENCTAL BOOLEAN Open CT Alarm output signal. Issued after a delay ...
IDL1 REAL Value of the instantaneous differential current, phase L1
IDL2 REAL Value of the instantaneous differential current, phase L2
IDL3 REAL Value of the instantaneous differential current, phase L3
IDL1MAG REAL Magnitude of fundamental freq. diff. current, phase L1
IDL2MAG REAL Magnitude of fundamental freq. diff. current, phase L2
IDL3MAG REAL Magnitude of fundamental freq. diff. current, phase L3
IBIAS REAL Magnitude of the bias current, which is common to all phases
IDNSMAG REAL Magnitude of the negative sequence differential current

6.1.5 Settings
PID-6758-SETTINGS v1

Table 37: T2WPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
SOTFMode Off - - On Operation mode for switch onto fault
On
tAlarmDelay 0.000 - 60.000 s 0.001 10.000 Time delay for diff currents alarm level
IDiffAlarm 0.05 - 1.00 IB 0.01 0.20 Dif. cur. alarm, multiple of base curr,
usually W1 curr.
IdMin 0.10 - 0.60 IB 0.01 0.30 Section1 sensitivity, multi. of base curr,
usually W1 curr.
IdUnre 1.00 - 100.00 IB 0.01 10.00 Unrestr. prot. limit, multiple of Winding 1
rated current
CrossBlockEn Off - - On Operation Off/On for cross-block logic
On between phases
NegSeqDiffEn Off - - On Operation Off/On for neg. seq. differential
On protections
IMinNegSeq 0.02 - 0.20 IB 0.01 0.04 Neg. seq. curr. must be higher than this
level to be used
NegSeqROA 30.0 - 120.0 Deg 0.1 60.0 Operate Angle for int. / ext. neg. seq. fault
discriminator

86 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Table 38: T2WPDIF Group settings (advanced)

Name Values (Range) Unit Step Default Description


EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, multiple of Winding 1
rated current
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, multiple of Winding 1
rated current
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate-restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 0.1 15.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 0.1 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
OpenCTEnable Off - - Off Open CT detection feature. Open
On CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 3.000 Open CT: time in s to alarm after an open
CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff. function
is activated
tOCTUnrstDelay 0.10 - 6000.00 s 0.01 10.00 Unrestrained diff. protection blocked after
this delay, in s

Table 39: T2WPDIF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSelW1 1 - 12 - 1 1 Global base selector for winding 1
GlobalBaseSelW2 1 - 12 - 1 1 Global base selector for winding 2
ConnectTypeW1 WYE (Y) - - WYE (Y) Connection type of winding 1: Y-wye or D-
Delta (D) delta
ConnectTypeW2 WYE (Y) - - WYE (Y) Connection type of winding 2: Y-wye or D-
Delta (D) delta
ClockNumberW2 0 [0 deg] - - 0 [0 deg] Phase displacement between W2 &
1 [30 deg lag] W1=HV winding, hour notation
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ZSCurrSubtrW1 Off - - On Enable zer. seq. current subtraction for
On W1 side, On / Off
ZSCurrSubtrW2 Off - - On Enable zer. seq. current subtraction for
On W2 side, On / Off
TconfigForW1 No - - No Two CT inputs (T-config.) for winding 1,
Yes YES / NO
CT1RatingW1 1 - 99999 A 1 3000 CT primary rating in A, T-branch 1, on
transf. W1 side
CT2RatingW1 1 - 99999 A 1 3000 CT primary in A, T-branch 2, on transf.
W1 side
TconfigForW2 No - - No Two CT inputs (T-config.) for winding 2,
Yes YES / NO
CT1RatingW2 1 - 99999 A 1 3000 CT primary rating in A, T-branch 1, on
transf. W2 side
Table continues on next page

Transformer protection RET650 87


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Name Values (Range) Unit Step Default Description


CT2RatingW2 1 - 99999 A 1 3000 CT primary rating in A, T-branch 2, on
transf. W2 side
LocationOLTC1 Not Used - - Not Used Transformer winding where OLTC1 is
Winding 1 (W1) located
Winding 2 (W2)
LowTapPosOLTC1 0 - 10 - 1 1 OLTC1 lowest tap position designation
(e.g. 1)
RatedTapOLTC1 1 - 100 - 1 6 OLTC1 rated tap/mid-tap position
designation (e.g. 6)
HighTapPsOLTC1 1 - 100 - 1 11 OLTC1 highest tap position designation
(e.g. 11)
TapHighVoltTC1 1 - 100 - 1 1 OLTC1 end-tap position with winding
highest no-load voltage
StepSizeOLTC1 0.01 - 30.00 % 0.01 1.00 Voltage change per OLTC1 step in
percent of rated voltage

PID-6757-SETTINGS v1

Table 40: T3WPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
SOTFMode Off - - On Operation mode for switch onto fault
On feature
tAlarmDelay 0.000 - 60.000 s 0.001 10.000 Time delay for diff currents alarm level
IDiffAlarm 0.05 - 1.00 IB 0.01 0.20 Dif. cur. alarm, multiple of base curr,
usually W1 curr.
IdMin 0.10 - 0.60 IB 0.01 0.30 Section1 sensitivity, multi. of base curr,
usually W1 curr.
IdUnre 1.00 - 100.00 IB 0.01 10.00 Unrestr. prot. limit, multi. of base curr.
usually W1 curr.
CrossBlockEn Off - - On Operation Off/On for cross-block logic
On between phases
NegSeqDiffEn Off - - On Operation Off/On for neg. seq. differential
On protections
IMinNegSeq 0.02 - 0.20 IB 0.01 0.04 Neg. seq. curr. limit, mult. of base curr,
usually W1 curr.
NegSeqROA 30.0 - 120.0 Deg 0.1 60.0 Operate Angle for int. / ext. neg. seq. fault
discriminator

Table 41: T3WPDIF Group settings (advanced)

Name Values (Range) Unit Step Default Description


EndSection1 0.20 - 1.50 IB 0.01 1.25 End of section 1, multi. of base current,
usually W1 curr.
EndSection2 1.00 - 10.00 IB 0.01 3.00 End of section 2, multi. of base current,
usually W1 curr.
SlopeSection2 10.0 - 50.0 % 0.1 40.0 Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 % 0.1 80.0 Slope in section 3 of operate-restrain
characteristic, in %
I2/I1Ratio 5.0 - 100.0 % 0.1 15.0 Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 % 0.1 25.0 Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
Table continues on next page

88 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Name Values (Range) Unit Step Default Description


OpenCTEnable Off - - Off Open CT detection feature. Open
On CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 s 0.001 3.000 Open CT: time in s to alarm after an open
CT is detected
tOCTResetDelay 0.100 - 10.000 s 0.001 0.250 Reset delay in s. After delay, diff. function
is activated
tOCTUnrstDelay 0.10 - 6000.00 s 0.01 10.00 Unrestrained diff. protection blocked after
this delay, in s

Table 42: T3WPDIF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSelW1 1 - 12 - 1 1 Global base selector for winding 1
GlobalBaseSelW2 1 - 12 - 1 1 Global base selector for winding 2
GlobalBaseSelW3 1 - 12 - 1 1 Global base selector for winding 3
ConnectTypeW1 WYE (Y) - - WYE (Y) Connection type of winding 1: Y-wye or D-
Delta (D) delta
ConnectTypeW2 WYE (Y) - - WYE (Y) Connection type of winding 2: Y-wye or D-
Delta (D) delta
ConnectTypeW3 WYE (Y) - - Delta (D) Connection type of winding 3: Y-wye or D-
Delta (D) delta
ClockNumberW2 0 [0 deg] - - 0 [0 deg] Phase displacement between W2 &
1 [30 deg lag] W1=HV winding, hour notation
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ClockNumberW3 0 [0 deg] - - 5 [150 deg lag] Phase displacement between W3 &
1 [30 deg lag] W1=HV winding, hour notation
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ZSCurrSubtrW1 Off - - On Enable zer. seq. current subtraction for
On W1 side, On / Off
ZSCurrSubtrW2 Off - - On Enable zer. seq. current subtraction for
On W2 side, On / Off
ZSCurrSubtrW3 Off - - On Enable zer. seq. current subtraction for
On W3 side, On / Off
TconfigForW1 No - - No Two CT inputs (T-config.) for winding 1,
Yes YES / NO
CT1RatingW1 1 - 99999 A 1 3000 CT primary rating in A, T-branch 1, on
transf. W1 side
CT2RatingW1 1 - 99999 A 1 3000 CT primary in A, T-branch 2, on transf.
W1 side
TconfigForW2 No - - No Two CT inputs (T-config.) for winding 2,
Yes YES / NO
Table continues on next page

Transformer protection RET650 89


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Name Values (Range) Unit Step Default Description


CT1RatingW2 1 - 99999 A 1 3000 CT primary rating in A, T-branch 1, on
transf. W2 side
CT2RatingW2 1 - 99999 A 1 3000 CT primary rating in A, T-branch 2, on
transf. W2 side
TconfigForW3 No - - No Two CT inputs (T-config.) for winding 3,
Yes YES / NO
CT1RatingW3 1 - 99999 A 1 3000 CT primary rating in A, T-branch 1, on
transf. W3 side
CT2RatingW3 1 - 99999 A 1 3000 CT primary rating in A, T-branch 2, on
transf. W3 side
LocationOLTC1 Not Used - - Not Used Transformer winding where OLTC1 is
Winding 1 (W1) located
Winding 2 (W2)
Winding 3 (W3)
LowTapPosOLTC1 0 - 10 - 1 1 OLTC1 lowest tap position designation
(e.g. 1)
RatedTapOLTC1 1 - 100 - 1 6 OLTC1 rated tap/mid-tap position
designation (e.g. 6)
HighTapPsOLTC1 1 - 100 - 1 11 OLTC1 highest tap position designation
(e.g. 11)
TapHighVoltTC1 1 - 100 - 1 1 OLTC1 end-tap position with winding
highest no-load voltage
StepSizeOLTC1 0.01 - 30.00 % 0.01 1.00 Voltage change per OLTC1 step in
percent of rated voltage
LocationOLTC2 Not Used - - Not Used Transformer winding where OLTC2 is
Winding 1 (W1) located
Winding 2 (W2)
Winding 3 (W3)
LowTapPosOLTC2 0 - 10 - 1 1 OLTC2 lowest tap position designation
(e.g. 1)
RatedTapOLTC2 1 - 100 - 1 6 OLTC2 rated tap/mid-tap position
designation (e.g. 6)
HighTapPsOLTC2 1 - 100 - 1 11 OLTC2 highest tap position designation
(e.g. 11)
TapHighVoltTC2 1 - 100 - 1 1 OLTC2 end-tap position with winding
highest no-load voltage
StepSizeOLTC2 0.01 - 30.00 % 0.01 1.00 Voltage change per OLTC2 step in
percent of rated voltage

GUID-59946A76-7C82-4259-8304-32DDD8A0F8AA v1

LocationOLTC1, LowTapPosOLTC1, RatedTapOLTC1, HighTapPsOLTC1,


TapHighVoltTC1, StepSizeOLTC1, LocationOLTC2, LowTapPosOLTC2, RatedTapOLTC2,
HighTapPsOLTC2, TapHighVoltTC2 and StepSizeOLTC2 are not supported by the 650
products due to hardware restrictons.

90 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

6.1.6 Monitored data


PID-6758-MONITOREDDATA v1

Table 43: T2WPDIF Monitored data

Name Type Values (Range) Unit Description


IDL1MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L1
IDL2MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L2
IDL3MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L3
IBIAS REAL - A Magnitude of the bias current, which is
common to all phases
IDNSMAG REAL - A Magnitude of the negative sequence
differential current

PID-3713-MONITOREDDATA v6

Table 44: T3WPDIF Monitored data

Name Type Values (Range) Unit Description


IDL1MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L1
IDL2MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L2
IDL3MAG REAL - A Magnitude of fundamental freq. diff.
current, phase L3
IBIAS REAL - A Magnitude of the bias current, which is
common to all phases
IDNSMAG REAL - A Magnitude of the negative sequence
differential current

6.1.7 Operation principle


M13039-3 v8
The task of the power transformer differential protection is to determine whether a fault is within the
protected zone, or outside of the protected zone. The protected zone is limited by the position of
current transformers (see Figure 36), and in principle can include more objects than just a
transformer. If the fault is found to be internal, the faulty power transformer must be quickly
disconnected from the system.

The main CTs are normally supposed to be star connected. The main CTs can be earthed in anyway
(that is, either "ToObject" or "FromObject"). However internally the differential function will always use
reference directions towards the protected transformer as shown in Figure 36. Thus the IED will
always internally measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in Figure 36. For more information see
the Application manual.

Transformer protection RET650 91


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

IW1 IW2

Z1S1 Z1S2
E1S1 E1S2

IW1 IW2

IED

en05000186.vsd
IEC05000186 V1 EN-US

Figure 36: Typical CT location and definition of positive current direction


Even in a healthy power transformer, the currents are generally not equal when they flow through it.
This is due to the ratio of the number of turns of the windings and the connection group of the
protected transformer. Therefore the differential protection must first correlate all currents to each
other before any calculation can be performed.

First, compensation for the protected transformer transformation ratio and connection group is made,
and only then are the currents compared phase-wise. This makes external auxiliary (interposing)
current transformers unnecessary. Conversion of all currents to the common reference side of the
power transformer is performed by pre-programmed coefficient matrices, which depends on the
protected power transformer transformation ratio and connection group. Once the power transformer
vector group, rated currents and voltages have been entered by the user, the differential protection is
capable to calculate off-line matrix coefficients required in order to perform the on-line current
comparison by means of a fixed equation.

The negative-sequence-current-based internal-external fault discriminator, is used with advantage in


order to determine whether a fault is internal or external. It not only positively discriminates between
internal and external faults, but can also independently detect minor faults which may not be sensed
by the "usual" differential protection based on operate-restrain characteristic.

For all differential functions it is the common trip that is used to initiate a trip of a breaker.
The separate trip signals from the different parts lacks the safety against maloperation.
This will in some cases result in a 6 ms time difference between, for example restrained
trip is issued and common trip is issued. The separate trip signals are only used for
information purpose of which part that has caused the trip.

6.1.7.1 Function calculation principles M13039-12 v4

To make a differential IED as sensitive and stable as possible, restrained differential characteristics
have been developed and is now adopted as the general practice in the protection of power
transformers. The protection should be provided with a proportional bias, which makes the protection
operate for a certain percentage differential current related to the current through the transformer.
This stabilizes the protection under through fault conditions while still permitting the system to have
good basic sensitivity. The following chapters explain how these quantities are derived.

Fundamental frequency differential currents M13039-15 v10


The fundamental frequency differential current is a vectorial sum (sum of fundamental frequency
phasors) of the individual phase currents from the different sides of the protected power transformer.

Before any differential current can be calculated, the power transformer phase shift, and its
transformation ratio, must be accounted for. Conversion of all currents to a common reference is
performed in two steps:

92 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

• all current phasors are phase-shifted to (referred to) the phase-reference side, (whenever
possible the first HV winding with star connection)
• all currents magnitudes are always referred to the first winding of the power transformer
(typically transformer high-voltage side)

The two steps of conversion are made simultaneously on-line by the pre-programmed coefficient
matrices, as shown in equation 1 for a two-winding power transformer, and in equation 2 for a three-
winding power transformer.

These are the internal compensation within the differential function. The protected power
transformer data is always entered per its nameplate. The Differential function will
correlate nameplate data and select proper reference windings.

é IDL1 ù é IL1_ W 1 ù é IL1_ W 2 ù


ê IDL 2 ú = A × ê IL 2 _ W 1ú + Un _ W 2 × B × ê IL 2 _ W 2 ú
ê ú ê ú Un _ W 1 ê ú
êë IDL3 úû êë IL3 _ W 1úû êë IL3 _ W 2 úû

1 2 3
EQUATION1880 V1 EN-US (Equation 1)

where:
1. is the resulting Differential Currents
2. is the current contribution from the W1 side
3. is the current contribution from the W2 side

é IDL1 ù é IL1_ W 1 ù é IL1_ W 2 ù é IL1_ W 3 ù


ê IDL 2 ú = A × ê IL 2 _ W 1ú + Un _ W 2 × B × ê IL 2 _ W 2 ú + Un _ W 3 × C × ê IL 2 _ W 3ú
ê ú ê ú Un _ W 1 ê ú Un _ W 1 ê ú
êë IDL3 úû êë IL3 _ W 1úû êë IL3 _ W 2 úû êë IL3 _ W 3 úû

1 2 3 4
EQUATION1556 V2 EN-US (Equation 2)

where:
1. is the resulting Differential Currents
2. is the current contribution from the W1 side
3. is the current contribution from the W2 side
4. is the current contribution from the W3 side

and where, for equation 1 and equation 2:


IDL1 is the fundamental frequency differential current in phase L1 (in W1 side primary
amperes)
IDL2 is the fundamental frequency differential current in phase L2 (in W1 side primary
amperes)
IDL3 is the fundamental frequency differential current in phase L3 (in W1 side primary
amperes)
IL1_W1 is the fundamental frequency phase current in phase L1 on the W1 side
IL2_W1 is the fundamental frequency phase current in phase L2 on the W1 side
IL3_W1 is the fundamental frequency phase current in phase L3 on the W1 side
Table continues on next page

Transformer protection RET650 93


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

IL1_W2 is the fundamental frequency phase current in phase L1 on the W2 side


IL2_W2 is the fundamental frequency phase current in phase L2 on the W2 side
IL3_W2 is the fundamental frequency phase current in phase L3 on the W2 side
IL1_W3 is the fundamental frequency phase current in phase L1 on the W3 side
IL2_W3 is the fundamental frequency phase current in phase L2 on the W3 side
IL3_W3 is the fundamental frequency phase current in phase L3 on the W3 side
Ur_W1 is transformer rated phase-to-phase voltage on the W1 side (setting parameter)
Ur_W2 is transformer rated phase-to-phase voltage on the W2 side (setting parameter)
Ur_W3 is transformer rated phase-to-phase voltage on the W3 side (setting parameter)
A, B and C are three by three matrices with numerical coefficients

Values of the matrix A, B and C coefficients depend on:

1. The Power transformer winding connection type, such as star (Y/y) or delta (D/d)
2. The Transformer vector group such as Yd1, Dy11, YNautod5, Yy0d5 and so on, which introduce
phase displacement between individual windings currents in multiples of 30°.
3. The Settings for elimination of zero sequence currents for the individual windings.

When the end user enters all these parameters, transformer differential function automatically
calculates the matrix coefficients. During this calculations the following rules are used:

For the phase reference, the first winding with set star (Y) connection is always used. For example, if
the power transformer is a Yd1 power transformer, the HV winding (Y) is taken as the phase
reference winding. If the power transformer is a Dy1, then the LV winding (y) is taken for the phase
reference. If there is no star connected winding, such as in Dd0 type of power transformers, then the
HV delta winding (D) is automatically chosen as the phase reference winding.

The fundamental frequency differential currents are in general composed of currents of all
sequences, that is, the positive-, the negative-, and the zero-sequence currents. If the zero-sequence
currents are eliminated (see section "Optional Elimination of zero sequence currents"), then the
differential currents can consist only of the positive-, and the negative-sequence currents. When the
zero-sequence current is subtracted on one side of the power transformer, then it is subtracted from
each individual phase current.

As it can be seen from equation 1 and equation 2 the first entered winding (W1) is always taken for
ampere level reference (current magnitudes from all other sides are always transferred to W1 side).
In other words, within the differential protection function, all differential currents and bias current are
always expressed in HV side primary Amperes.

It can be shown that the values of the matrix A, B & C coefficients (see equation 1 and equation 2)
can be pre-calculated in advance depending on the relative phase shift between the reference
winding and other power transformer windings.

Table 45 summarizes the values of the matrices for all standard phase shifts between windings.

94 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Table 45: Matrices for differential current calculation

Matrix with Zero Sequence Matrix with Zero Sequence Reduction set to
Reduction set to On Off
Matrix for Reference Winding
é 2 -1 -1ù é1 0 0 ù
1 ê
× -1 2 -1ú ê0 1 0 ú
3 ê ú ê ú
ëê -1 -1 2 ûú êë0 0 1 úû
EQUATION1227 V1 EN-US (Equation 3) EQUATION1228 V1 EN-US (Equation 4)
Matrix for winding with 30° Not applicable. Matrix on the left used.
lagging é 1 -1 0 ù
1
× ê 0 1 -1ú
3 ê ú
ëê -1 0 1 úû
EQUATION1229 V1 EN-US (Equation 5)
Matrix for winding with 60°
lagging é1 -2 1ù é 0 -1 0 ù
1 ê
× 1 1 -2 ú ê 0 0 -1ú
3 ê ú ê ú
êë -2 1 1 úû êë -1 0 0 úû
EQUATION1230 V1 EN-US (Equation 6) EQUATION1231 V1 EN-US (Equation 7)
Matrix for winding with 90° Not applicable. Matrix on the left used.
lagging é0 -1 1ù
1
×ê 1 0 -1ú
3 ê ú
êë -1 1 0 úû
EQUATION1232 V1 EN-US (Equation 8)
Matrix for winding with 120°
lagging é -1 -1 2 ù é0 0 1 ù
1 ê
× 2 -1 -1ú ê1 0 0 ú
3 ê ú ê ú
êë -1 2 -1úû ëê0 1 0 úû
EQUATION1233 V1 EN-US (Equation 9) EQUATION1234 V1 EN-US (Equation 10)
Matrix for winding with 150° Not applicable. Matrix on the left used.
lagging é-1 0 1 ù
1
× ê 1 -1 0 ú
3 ê ú
êë 0 1 -1úû
EQUATION1235 V1 EN-US (Equation 11)
Matrix for winding which is in
opposite phase é -2 1 1ù é -1 0 0 ù
1 ê
× 1 -2 1 ú ê 0 -1 0 ú
3 ê ú ê ú
ëê 1 1 -2 ûú êë 0 0 -1úû
EQUATION1236 V1 EN-US (Equation 12) EQUATION1237 V1 EN-US (Equation 13)
Matrix for winding with 150° Not applicable. Matrix on the left used.
leading é-1 1 0 ù
1
× ê 0 -1 1 ú
3 ê ú
ëê 1 0 -1ûú
EQUATION1238 V1 EN-US (Equation 14)
Matrix for winding with 120°
leading é -1 2 -1ù é0 1 0 ù
1 ê
× -1 -1 2 ú ê0 0 1 ú
3 ê ú ê ú
êë 2 -1 -1úû êë1 0 0 úû
EQUATION1239 V1 EN-US (Equation 15) EQUATION1240 V1 EN-US (Equation 16)
Table continues on next page

Transformer protection RET650 95


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Matrix with Zero Sequence Matrix with Zero Sequence Reduction set to
Reduction set to On Off
Matrix for winding with 90° Not applicable. Matrix on the left used.
leading é 0 1 -1ù
1 ê
× -1 0 1 ú
3 ê ú
ëê 1 -1 0 úû
EQUATION1241 V1 EN-US (Equation 17)
Matrix for winding with 60°
leading é1 1 -2 ù é 0 0 -1ù
1 ê ê -1 0 0 ú
× -2 1 1ú
3 ê ú ê ú
êë 1 -2 1 úû êë 0 -1 0 úû
EQUATION1242 V1 EN-US (Equation 18) EQUATION1243 V1 EN-US (Equation 19)
Matrix for winding with 30° Not applicable. Matrix on the left used.
leading é 1 0 -1ù
1
× ê -1 1 0 ú
3 ê ú
ëê 0 -1 1 úû
EQUATION1244 V1 EN-US (Equation 20)

By using this table complete equation for calculation of fundamental frequency differential currents
for two winding power transformer with YNd5 vector group and enabled zero sequence current
reduction on HV side will be derived. From the given power transformer vector group the following is
possible to be concluded:

1. The HV star (Y) connected winding will be used as the reference winding and zero sequence
currents shall be subtracted on that side
2. The LV winding is lagging for 150°

With the help of table 45, the following matrix equation can be written for this power transformer:

é IDL1ù é 2 -1 -1ù é IL1_ W1ù é-1 0 1 ù é IL1_ W 2 ù


ê IDL2ú = 1 × ê-1 2 -1ú × ê IL2 _ W1ú + Ur _ W 2 × 1 × ê 1 -1 0 ú × ê IL2 _ W 2ú
ê ú 3 ê ú ê ú Ur _ W1 3 ê ú ê ú
êë IDL3ûú êë-1 -1 2 ûú ëê IL3_ W1ûú êë 0 1 -1ûú ëê IL3_ W 2 ûú
EQUATION2015 V1 EN-US (Equation 21)

where:
IDL1 is the fundamental frequency differential current in phase L1 (in W1 side primary
amperes)
IDL2 is the fundamental frequency differential current in phase L2 (in W1 side primary
amperes)
IDL3 is the fundamental frequency differential current in phase L3 (in W1 side primary
amperes)
IL1_W1 is the fundamental frequency phase current in phase L1 on the W1 side
IL2_W1 is the fundamental frequency phase current in phase L2 on the W1 side
IL3_W1 is the fundamental frequency phase current in phase L3 on the W1 side
IL1_W2 is the fundamental frequency phase current in phase L1 on the W2 side
IL2_W2 is the fundamental frequency phase current in phase L2 on the W2 side
IL3_W2 is the fundamental frequency phase current in phase L3 on the W2 side
Ur_W1 is transformer rated phase-to-phase voltage on the W1 side (setting parameter)
Ur_W2 is transformer rated phase-to-phase voltage on the W2 side (setting parameter)

96 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

As marked in equation 1 and equation 2, the first term on the right hand side of the equation,
represents the total contribution from the individual phase currents from the W1 side to the
fundamental frequency differential currents, compensated for eventual power transformer phase
shift. The second term on the right hand side of the equation, represents the total contribution from
the individual phase currents from the W2 side to the fundamental frequency differential currents,
compensated for eventual power transformer phase shift and transferred to the power transformer
W1 side. The third term on the right hand side of the equation, represents the total contribution from
the individual phase currents from the W3 side to the fundamental frequency differential currents,
compensated for eventual power transformer phase shift and transferred to the power transformer
W1 side. These current contributions are important, because they are used for calculation of
common bias current.

The fundamental frequency differential currents are the "usual" differential currents, the magnitudes
which are applied in a phase-wise manner to the operate - restrain characteristic of the differential
protection. The magnitudes of the differential currents can be read as service values from the
function and they are available as outputs IDL1MAG, IDL2MAG, IDL3MAG from the differential
protection function block. Thus they can be connected to the disturbance recorder and automatically
recorded during any external or internal fault condition.

Differential current alarm M13039-436 v6


Fundamental frequency differential current level is monitored all the time within the differential
function. As soon as all three fundamental frequency differential currents are above the set threshold
defined by setting parameter IDiffAlarm a delay on pickup timer is started. When the pre-set time,
defined by setting parameter tAlarmDelay, has expired the differential current alarm is generated and
output signal IDALARM is set to logical value one. This feature can be effectively used to provide
alarm when load tap changer position compensation is used and something in the whole
compensation chain goes wrong. This alarm can be as well used with some additional IED
configuration logic to desensitize the differential function.

Bias current M13039-179 v5


The bias current is calculated as the highest current amongst all individual winding current
contributions to the total fundamental frequency differential currents, as shown in equation and
equation . All individual winding current contributions are already referred to the power transformer
winding one side (power transformer HV winding) and therefore they can be compared regarding
their magnitudes. There are six (or nine in the case of a three-winding transformer) contributions to
the total fundamental differential currents, which are the candidates for the common bias current. The
highest individual current contribution is taken as a common bias (restrain) current for all three
phases. This "maximum principle" makes the differential protection more secure, with less risk to
operate for external faults and in the same time brings more meaning to the breakpoint settings of
the operate - restrain characteristic.

It shall be noted that if the zero-sequence currents are subtracted from the separate contributions to
the total differential current, then the zero-sequence component is automatically eliminated from the
bias current as well. This ensures that for secondary injection from just one power transformer side
the bias current is always equal to the highest differential current regardless of the fault type. During
normal through-load operation of the power transformer, the bias current is equal to the maximum
load current from two (three) -power transformer windings.

The magnitudes of the common bias (restrain) current expressed in HV side amperes can be read as
service value from the function. At the same time it is available as an output IBIAS from the
differential protection function block. It can be connected to the disturbance recorder and
automatically recorded during any external or internal fault condition.

For application with so called "T" configuration, that is, two restraint CT inputs from one side of the
protected power transformer, such as in the case of breaker-and-a-half schemes the primary CT
ratings can be much higher than the rating of the protected power transformer. In order to determine
the bias current for such T configuration, the two separate currents flowing in the T-side are scaled
down to the protected power transform level by means of additional settings. This is done in order to
prevent unwanted de-sensitizing of the overall differential protection. In addition to that, the resultant
currents (the sum of two currents) into the protected power transformer winding, which is not directly

Transformer protection RET650 97


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

measured is calculated, and included in the common bias calculation. The rest of the bias calculation
procedure is the same as in protection schemes without breaker-and-a-half arrangements.

Optional Elimination of zero sequence currents M13039-185 v8


To avoid unwanted trips for external earth-faults, the zero sequence currents should be subtracted on
the side of the protected power transformer, where the zero sequence currents can flow at external
earth -faults.

The zero sequence currents can be explicitly eliminated from the differential currents and common
bias current calculation by special, dedicated parameter settings, which are available for every
individual winding.

Elimination of the zero sequence component of current is necessary whenever:

• the protected power transformer cannot transform the zero sequence currents to the other side.
• the zero sequence currents can only flow on one side of the protected power transformer.

In most cases, power transformers do not properly transform the zero sequence current to the other
side. A typical example is a power transformer of the star-delta type, for example YNd1.
Transformers of this type do not transform the zero sequence quantities, but zero sequence currents
can flow in the earthed star- connected winding. In such cases, an external earth-fault on the star-
side causes zero sequence current to flow on the star-side of the power transformer, but not on the
other side. This results in false differential currents - consisting exclusively of the zero sequence
currents. If high enough, these false differential currents can cause an unwanted disconnection of the
healthy power transformer. They must therefore be subtracted from the fundamental frequency
differential currents if an unwanted trip is to be avoided.

For delta windings this feature shall be enabled only if an earthing transformer exists within the
differential zone on the delta side of the protected power transformer.

Removing the zero sequence current from the differential currents decreases to some extent the
sensitivity of the differential protection for internal earth -faults. In order to counteract this effect to
some degree, the zero sequence current is subtracted not only from the three fundamental frequency
differential currents, but from the bias current as well.

Restrained and unrestrained limits of the differential protection M13039-194 v8


The power transformer differential protection function uses two limits, to which actual magnitudes of
the three fundamental frequency differential currents are compared at each execution of the function.

The unrestrained (that is, non-stabilized, "instantaneous") part of the differential protection is used for
very high differential currents, where it should be beyond any doubt, that the fault is internal. This
settable limit is constant and not proportional to the bias current. Neither harmonic, nor any other
restrain is applied to this limit, which is therefore allowed to trip the power transformer
instantaneously.

The restrained (stabilized) part of the differential protection compares the calculated fundamental
differential (operating) currents and the bias (restrain) current, by applying them to the operate -
restrain characteristic. Practically, the magnitudes of the individual fundamental frequency differential
currents are compared with an adaptive limit. This limit is adaptive because it is dependent on the
bias (that is, restrain) current magnitude. This limit is called the operate - restrain characteristic. It is
represented by a double-slope, double-breakpoint characteristic, as shown in figure 37. The
restrained characteristic is determined by the following 5 settings:

98 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

1. IdMin (Sensitivity in section 1, multiple of trans. HV side rated current set under the parameter
RatedCurrentW1)
2. EndSection1 (End of section 1, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
3. EndSection2 (End of section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
4. SlopeSection2 (Slope in section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)
5. SlopeSection3 (Slope in section 2, as multiple of transformer HV side rated current set under the
parameter RatedCurrentW1)

For three-winding transformer, if the HV winding is not the one with highest power rating, the
parameters of operate-bias characteristic (Idmin, EndSection1 and EndSection2) will be adapted by
multiplying a scale factor Smax/S1 so that the winding with highest power rating is taken into
account. Smax and S1 can be calculated from the rated voltage and current for each winding.

The restrained characteristic in figure 37 is defined by the settings:

1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3

operate current
[ times IBase ]
Operate
5
unconditionally

UnrestrainedLimit
4

Operate
3
conditionally

2
Section 1 Section 2 Section 3

SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5

EndSection1 restrain current


EndSection2 [ times IBase ]

en05000187-2.vsd
IEC05000187 V2 EN-US

Figure 37: Description of the restrained, and the unrestrained operate characteristics

where:

slope = D Ioperate × 100%


D Irestrain
EQUATION1246 V1 EN-US

Transformer protection RET650 99


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

The operate - restrain characteristic is tailor-made and can be designed freely by the user after his
needs. The default characteristic is recommended to be used. It gives good results in a majority of
applications. The operate - restrain characteristic has in principle three sections with a section-wise
proportionality of the operate value to the bias (restrain) current. The reset ratio is in all parts of the
characteristic equal to 0.95.

Section 1: This is the most sensitive part on the characteristic. In section 1, normal currents flow
through the protected circuit and its current transformers, and risk for higher false differential currents
is relatively low. An un-compensated on-load tap-changer is a typical reason for existence of the
false differential currents in this section. The slope in section 1 is always zero percent.

Section 2: In section 2, a certain minor slope is introduced which is supposed to cope with false
differential currents proportional to higher than normal currents through the current transformers.

Section 3: The more pronounced slope in section 3 is designed to result in a higher tolerance to
substantial current transformer saturation at high through-fault currents, which may be expected in
this section.

The operate - restrain characteristic should be designed so that it can be expected that:

• for internal faults, the operate (differential) currents are always with a good margin above the
operate - restrain characteristic
• for external faults, the false (spurious) operate currents are with a good margin below the
operate - restrain characteristic

The differential protection can be temporarily desensitized by applying the adaptive DC biasing
method. When the external fault is detected, this adaptive DC biasing method will temporarily shift
the operate-bias characteristic by adding DC components to the operate level IdMin. The DC
component is extracted online form the instantaneous differential currents and the highest DC in all
three phases is selected to be added to IdMin. This feature improves the security of the differential
function against the CT errors during heavy external faults followed by CT saturation. The adaptive
DC biasing will be reset if either of the conditions below is fulfilled:

• The external fault signal disappears and no DC components exist in the phase currents.
• The differential currents become higher than the bias current.

The adaptive DC biasing feature is disabled when NegSeqDiffEn is set to Off.

Fundamental frequency negative sequence differential currents M13039-226 v7


Existence of relatively high negative sequence currents is in itself a proof of a disturbance on the
power system, possibly a fault in the protected power transformer. The negative-sequence currents
are a measurable indication of an abnormal condition, similar to the zero sequence current. One of
the several advantages of the negative sequence currents compared to the zero sequence currents
is that they provide coverage for phase-to-phase and power transformer turn-to-turn faults.
Theoretically, the negative sequence currents do not exist during symmetrical three-phase faults,
however they do appear during initial stage of such faults for a long enough time (in most cases) for
the IED to make the proper decision. Further, the negative sequence currents are not stopped at a
power transformer by the Yd, or Dy connection type. The negative sequence currents are always
properly transformed to the other side of any power transformer for any external disturbance. Finally,
the negative sequence currents are not affected by symmetrical through-load currents.

For power transformer differential protection applications, the negative sequence based differential
currents are calculated by using exactly the same matrix equations, which are used to calculate the
traditional phase-wise fundamental frequency differential currents. The same equation shall be fed by
the negative sequence currents from the two power transformer sides instead of individual phase
currents, as shown in matrix equation 23 for a case of two-winding, YNd5 power transformer.

100 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

é IDL1 _ NS ù é2 -1 -1ù é INS _ W 1 ù é -1 0 1 ù é INS _ W 2 ù


ê IDL 2 _ NS ú = 1 × ê -1 2 -1 × ê a × INS _ W 1 ú +
ú Ur _ W 2
×
1
×ê1 -1 0 ú × ê a × INS _ W 2 ú
ê ú 3 ê ú ê 2 ú Ur _ W 1 3 ê ú ê 2 ú
êë IDL3 _ NS úû êë -1 -1 2úû êë a × INS _ W 1úû êë 0 1 -1ú
û êë a × INS _ W 2 úû

1 2 3

EQUATION1247 V1 EN-US (Equation 23)

where:
1. is the Negative Sequence Differential Currents
2. is the Negative Sequence current contribution from the W1 side
3. is the Negative Sequence current contribution from the W2 side

and where:
IDL1_NS is the negative sequence differential current in phase L1 (in
W1 side primary amperes)
IDL2_NS is the negative sequence differential current in phase L2 (in
W1 side primary amperes)
IDL3_NS is the negative sequence differential current in phase L3 (in
W1 side primary amperes)
INS_W1 is the negative sequence current on the W1 side in primary
amperes (phase L1 reference)
INS_W2 is the negative sequence current on the W2 side in primary
amperes (phase L1 reference)
Ur_W1 is the transformer rated phase-to-phase voltage on the W1
side (setting parameter)
Ur_W2 is the transformer rated phase-to-phase voltage on W2 side
(setting parameter)

a is the complex operator for sequence quantities,

j ×120
o 1 3
a=e =- + j×
2 2
EQUATION1248 V1 EN-US (Equation 24)

Because the negative sequence currents always form the symmetrical three phase current system
on each transformer side (that is, negative sequence currents in every phase will always have the
same magnitude and be phase displaced for 120 electrical degrees from each other), it is only
necessary to calculate the first negative sequence differential current that is, IDL1_NS.

As marked in equation 23, the first term on the right hand side of the equation, represents the total
contribution of the negative sequence current from the W1 side compensated for eventual power
transformer phase shift. The second term on the right hand side of the equation, represents the total
contribution of the negative sequence current from the W2 side compensated for eventual power
transformer phase shift and transferred to the power transformer W1 side. These negative sequence
current contributions are phasors, which are further used in directional comparisons, to characterize
a fault as internal or external. See section "Internal/external fault discriminator" for more information.

The magnitudes of the negative sequence differential current expressed in the HV side A can be
read as service values from the function. In the same time it is available as outputs IDNSMAG from
the differential protection function block. Thus, it can be connected to the disturbance recorder and
automatically recorded during any external or internal fault condition.

Transformer protection RET650 101


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Internal/external fault discriminator M13039-280 v7


The internal/external fault discriminator is a very powerful and reliable supplementary criterion to the
traditional differential protection. It is recommended that this feature shall be always used (that is,
On) when protecting three-phase power transformers. The internal/external fault discriminator
detects even minor faults, with a high sensitivity and at high speed, and at the same time
discriminates with a high degree of dependability between internal and external faults.

The internal/external fault discriminator responds to the magnitudes and the relative phase angles of
the negative-sequence fault currents at the different windings of the protected power transformer.
The negative sequence fault currents must first be referred to the same phase reference side, and
put to the same magnitude reference. This is done by the matrix expression (see equation ).

Operation of the internal/external fault discriminator is based on the relative position of the two
phasors representing the winding one (W1) and winding two (W2) negative sequence current
contributions, respectively, defined by expression shown in equation . It performs a directional
comparison between these two phasors. First, the LV side phasor is referred to the HV side (W1
side): both the magnitude, and the phase position are referred to the HV (W1 side). Then the relative
phase displacement between the two negative sequence current phasors is calculated. In case of
three-winding power transformers, a little more complex algorithm is applied, with two directional
tests. The overall directional characteristic of the internal/external fault discriminator is shown in
figure 38, where the directional characteristic is defined by two setting parameters:

1. IMinNegSeq
2. NegSeqROA

90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement
NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped
Angle)

180 deg 0 deg

IMinNegSeq

External Internal
fault fault
region region

270 deg en05000188-3-en.vsd


IEC05000188 V3 EN-US

Figure 38: Operating characteristic of the internal/external fault discriminator


In order to perform directional comparison of the two phasors their magnitudes must be high enough
so that one can be sure that they are due to a fault. On the other hand, in order to guarantee a good
sensitivity of the internal/external fault discriminator, the value of this minimum limit must not be too
high. Therefore this limit value, called IminNegSeq, is settable in the range of 0.02 to 0.20 times the
IBase of the power transformer winding one. The default value is 0.04. Note that, in order to enhance
stability at higher fault currents, the relatively very low threshold value IminNegSeq is dynamically
increased at currents higher than normal currents: if the bias current is higher than 110% of
IBase ,then 10% of the bias current is added to the IminNegSeq. Only if the magnitudes of both

102 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

negative sequence current contributions are above the actual limit, the relative position between
these two phasors is checked. If either of the negative sequence current contributions, which should
be compared, is too small (less than the set value for IminNegSeq), no directional comparison is
made in order to avoid the possibility to produce a wrong decision. This magnitude check guarantees
stability of the algorithm, when the power transformer is energized. The setting NegSeqROA
represents the Relay Operate Angle, which determines the boundary between the internal and
external fault regions. It can be selected in a range from ±30 degrees to ±90 degrees, with a step of
0.1 degree. The default value is ±60 degrees. The default setting ±60 degree favours security in
comparison to dependability.

If the above condition concerning magnitudes is fulfilled, the internal/external fault discriminator
compares the relative phase angle between the negative sequence current contributions from W1
and W2 sides of the power transformer using the following two rules:

• If the negative sequence current contributions from the W1 and the W2 sides are in phase, the
fault is internal (that is, both phasors are within protected zone)
• If the negative sequence currents contributions from W1 and W2 sides are 180 degrees out of
phase, the fault is external (that is, W1 phasors is outside protected zone)

For example, for any unsymmetrical external fault, ideally the respective negative sequence current
contributions from the W1 and W2 power transformer sides will be exactly 180 degrees apart and
equal in magnitude, regardless the power transformer turns ratio and phase displacement. An
example is shown in figure 39, which shows trajectories of the two separate phasors representing the
negative sequence current contributions from the HV and LV sides of an Yd5 power transformer
(after compensation of the transformer turns ratio and phase displacement) by using equation ) for an
unsymmetrical external fault. Observe that the relative phase angle between these two phasors is
180 electrical degrees at any point in time. No current transformer saturation was assumed for this
case.

"steady state"
for HV side 90
neg. seq. phasor
60

150 30

10
ms

180 0
0.1 kA
0.2 kA
0.3 kA
10 0.4 kA
ms
210 330

"steady state"
240 for LV side
270 neg. seq. phasor

Contribution to neg. seq. differential current from HV side


Contribution to neg. seq. differential current from LV side

en05000189.vsd
IEC05000189 V1 EN-US

Figure 39: Trajectories of Negative Sequence Current Contributions from HV and LV sides of
Yd5 power transformer during external fault

Transformer protection RET650 103


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Under external fault conditions, the relative angle is theoretically equal to 180 degrees. During
internal faults, the angle shall ideally be 0 degrees, but due to possible different negative sequence
source impedance angles on the W1 and W2 sides of the protected power transformer, it may differ
somewhat from the ideal zero value. However, during heavy faults, CT saturation might cause the
measured phase angle to differ from 180 degrees for an external, and from 0 degrees for an internal
fault. See figure 40 for an example of a heavy internal fault with transient CT saturation.

Dire ctiona l Compa ris on Crite rion: Inte rna l fa ult a s s e e n from the HV s ide
90
e xcurs ion
120 60
from 0 de gre e s
35 ms due to CT
s a tura tion
150 30
de finite ly
a n inte rna l
fa ult

180 0
trip c o mmand
in 12 ms
e xte rna l
fa ult Inte rna l fa ult
0.5 kA de cla re d 7 ms
re gion
210 330 a fte r inte rna l
fa ult occure d
1.0 kA

240 300
1.5 kA
270
HV s ide contribution to the tota l ne ga tive s e que nce diffe re ntia l curre nt in kA
Dire ctiona l limit (within the re gion de limite d by ± 60 de gre e s is inte rna l fa ult)

en05000190.vsd
IEC05000190 V1 EN-US

Figure 40: Operation of the internal/external fault discriminator for internal fault with CT
saturation
It shall be noted that additional security measures are implemented in the internal/external fault
discriminator algorithm in order to guarantee proper operation with heavily saturated current
transformers. The trustworthy information on whether a fault is internal or external is typically
obtained in about 10ms after the fault inception, depending on the setting IminNegSeq, and the
magnitudes of the fault currents. During heavy faults, approximately 5ms time to full saturation of the
main CT is sufficient in order to produce a correct discrimination between internal and external faults.

Unrestrained, and sensitive negative sequence protections M13039-320 v5


Two sub functions, which are based on the internal/external fault discriminator with the ability to trip a
faulty power transformer, are parts of the traditional power transformer differential protection.

The unrestrained negative sequence differential protection M13039-323 v6


The unrestrained negative sequence protection is activated if one or more start signals have been
set by the traditional differential protection algorithm. This happens because one or more of the
fundamental frequency differential currents entered the operate region on the operate - restrain
characteristic. So, this protection is not independent of the traditional restrained differential protection
- it is activated after the first start signal has been placed.

If the same fault has been positively recognized as internal, then the unrestrained negative sequence
differential protection places its own trip request.

104 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Any block signals by the harmonic and/or waveform criteria, which can block the traditional
differential protection are overridden, and the differential protection operates quickly without any
further delay.

This logic guarantees a fast disconnection of a faulty power transformer for any internal fault.

If the same fault has been classified as external, then generally, but not unconditionally, a trip
command is prevented. If a fault is classified as external, further analysis of the fault conditions is
initiated. If all the instantaneous differential currents in phases where start signals have been issued
are free of harmonic pollution, then a (minor) internal fault, simultaneous with a predominant external
fault can be suspected. This conclusion can be drawn because at external faults, major false
differential currents can only exist when one or more current transformers saturate. In this case, the
false instantaneous differential currents are polluted by higher harmonic components, the 2nd, the 5th
etc.

Sensitive negative sequence based turn-to-turn fault protection M13039-328 v4


The sensitive, negative sequence current based turn-to-turn fault protection detects the low level
faults, which are not detected by the traditional differential protection until they develop into more
severe faults, including power transformer iron core. The sensitive protection is independent from the
traditional differential protection and is a very good complement to it. The essential part of this
sensitive protection is the internal/external fault discriminator. In order to be activated, the sensitive
protection requires no start signal from the traditional power transformer biased differential
protection. If magnitudes of HV and LV negative sequence current contributions are above the set
limit for IminNegSeq, then their relative positions are determined. If the disturbance is characterized
as an internal fault, then a separate trip request will be placed. Any decision on the way to the final
trip request must be confirmed several times in succession in order to cope with eventual CT
transients. This causes a short additional operating time delay due to this security count. For very low
level turn-to-turn faults the overall response time of this protection is about 30ms.

Instantaneous differential currents M13039-331 v5


The instantaneous differential currents are calculated from the instantaneous values of the input
currents in order to perform the harmonic analysis and waveform analysis upon each one of them
(see section "Harmonic and waveform block criteria" for more information).

The instantaneous differential currents are calculated using the same matrix expression as shown in
equation and equation . The same matrices A, B and C are used for these calculations. The only
difference is that the matrix algorithm is fed by instantaneous values of currents, that is, samples.

Harmonic and waveform block criteria M13039-334 v4


The two block criteria are the harmonic restrain and the waveform restrain. These two criteria have
the power to block a trip command by the traditional differential protection, which produces start
signals by applying the differential currents, and the bias current, to the operate - restrain
characteristic.

Harmonic restrain M13039-337 v8


The harmonic restrain is the classical restrain method traditionally used with power transformer
differential protections. The goal is to prevent an unwanted trip command due to magnetizing inrush
currents at switching operations, or due to magnetizing currents at over-voltages.

The magnetizing currents of a power transformer flow only on one side of the power transformer and
are therefore always the cause of false differential currents. The harmonic analysis (the 2nd and the
5th harmonic) is applied to the instantaneous differential currents. Typical instantaneous differential
currents during power transformer energizing are shown in figure 41. The harmonic analysis is only
applied in those phases where start signals have been set. For example, if the content of the 2nd
harmonic in the instantaneous differential current of phase L1 is above the setting I2/I1Ratio, then a
block signal is set for that phase, which can be read as BLK2HL1 output of the differential protection.

After the transformer has been energized (the energizing period has elapsed and the inrush currents
have disappeared), the 2nd harmonic blocking is conditionally activated if NegSeqDiffEn is set to On.
When the fault cannot be identified as internal or external, the 2nd harmonic blocking signal is

Transformer protection RET650 105


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

activated only if the differential current is smaller than the bias current. If the differential current
becomes equal to or higher than the bias current, the differential function will be released regardless
of the 2nd harmonic blocking signal.

The 2nd harmonic analysis always supervises the restrained differential criterion if
NegSeqDiffEn is set to Off.

Waveform restrain M13039-341 v4


The waveform restrain criterion is a good complement to the harmonic analysis. The waveform
restrain is a pattern recognition algorithm, which looks for intervals within each fundamental power
system cycle with low instantaneous differential current. This interval is often called current gap in
protection literature. However, within differential function this criterion actually searches for long-
lasting intervals with low rate-of-change in instantaneous differential current, which are typical for the
power transformer inrush currents. Block signals BLKWAVLx are set in those phases where such
behavior is detected. The algorithm does not require any end user settings. The waveform algorithm
is automatically adapted dependent only on the power transformer rated data.

IEC05000343 V1 EN-US

Figure 41: Inrush currents to a transformer as seen by a protective IED. Typical is a high
amount of the 2nd harmonic, and intervals of low current, and low rate-of-change
of current within each period.

Cross-blocking between phases M13039-384 v9


The basic definition of the cross-blocking is that one of the three phases can block operation (that is,
tripping) of the other two phases due to the harmonic pollution of the differential current in that phase
(that is, waveform, 2nd or 5th harmonic content). In differential algorithm the user can control the
cross-blocking between the phases via the setting parameter CrossBlockEn=On.

When parameter CrossBlockEn=On cross blocking between phases is introduced. There is no time
settings involved, but the phase with the operating point above the set bias characteristic (in the
operate region) will be able to cross-block the other two phases if it is itself blocked by any of the
previously explained restrained criteria. As soon as the operating point for this phase is below the set
bias characteristic (that is, in the restrain region) cross blocking from that phase will be inhibited. In
this way cross-blocking of a temporary nature is achieved. It should be noted that this is the default
setting value for this parameter.

When parameter CrossBlockEn=Off, any cross blocking between phases will be disabled. It is
recommended to use the value Off with caution in order to avoid the unwanted tripping during initial
energizing of the power transformer.

106 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Switch onto fault feature M13039-499 v8


The transformer differential function has a built-in, advanced switch onto fault feature. This feature
can be enabled or disabled by a setting parameter SOTFMode. When enabled this feature ensures
quick differential protection tripping in cases where a transformer is energized with an internal fault
(for example, forgotten earthing on transformer LV side). Operation of this feature is based on the
fact that a current gap (term current gap is explained under waveblock feature above) will exist within
the first power system cycle when healthy power transformer is energized. If this is not the case the
waveblock criterion will reset quickly. This quick reset of the waveblock criterion will temporarily
disable the second harmonic blocking feature of the differential protection function. This
consequently ensures fast operation of the transformer differential function for a switch onto a fault
condition. It shall be noted that this feature is only active during initial power transformer energizing,
under the first 4 cycles, 80 ms for 50Hz and 66.7 ms for 60Hz. When the switch onto fault feature is
disabled by the setting parameter SOTFMode, the waveblock and second harmonic blocking
features work in parallel and are completely independent from each other.

Open CT detection feature M13039-440 v8


Transformer differential protection has a built-in, advanced open CT detection feature.

A sudden inadvertently opened CT circuit may cause an unexpected and unwanted operation of the
Transformer differential protection under normal load conditions. Damage of secondary equipment
may occur due to high voltage from open CT circuit outputs. It is always an advantage, from the point
of view of security and reliability, to have the open CT detection function to block the transformer
differential protection function in case of an open CT condition, and produce an alarm signal to the
operational personnel to quickly correct the open CT condition.

The built-in open CT feature can be enabled or disabled by the setting parameter OpenCTEnable
(Off/On). When enabled, this feature tries to prevent mal-operation when a loaded main CT
connected to Transformer differential protection is by mistake open circuited on the secondary side.
Note that this feature can only detect interruption of one CT phase current at a time. If two or even all
three-phase currents of one set of CTs are accidentally interrupted at precisely the same time, this
feature cannot operate. Transformer differential protection generates a trip signal if the false
differential current is sufficiently high. An open CT circuit is typically detected in 12–14 ms, and if the
load in the protected circuit is relatively high, about the nominal load, the unwanted trip cannot
always be prevented. Still, the information about what was the cause of the open CT secondary
circuit, is vital.

The principle applied to detect an open CT is a simple pattern recognition method, similar to the
waveform check used by the Power transformer differential protection in order to detect the
magnetizing inrush condition. The open CT detection principle is based on the fact that for an open
CT, the current in the phase with the open CT suddenly drops to zero (that is, as seen by the
protection), while the currents of the other two phases continue as before.

The open CT function is supposed to detect an open CT under normal conditions, that is, with the
protected multi-terminal circuit under normal load (10...110% of the rated load). If the load currents
are very low or zero, the open CT condition cannot be detected. In addition to load condition
requirement, Open CT function also checks the differential current on faulty phase. If the differential
current is lower than 50% of IdMin, the open CT condition cannot be detected. Therefore, the Open
CT algorithm only detects an open CT if the load on the power transformer is 10...110% of rated load
and the differential current is higher than 50% of IdMin on that phase. The search for an open CT
starts 60 seconds (50 seconds in 60 Hz systems) after the transformer is energized. The Open CT
detection feature can also be explicitly deactivated by setting: OpenCTEnable = 0 ( Off).

If an open CT is detected and the output OPENCT set to 1, then all the differential functions are
blocked, except the unrestrained (instantaneous) differential. An alarm signal is also produced after a
settable delay (tOCTAlarmDelay) to report to operational personnel for quick remedy actions once
the open CT is detected. When the open CT condition is removed (that is, the previously open CT is
reconnected), the functions remain blocked for a specified interval of time, which is also defined by a
setting (tOCTResetDelay). This is to prevent an eventual mal-operation after the reconnection of the
previously open CT secondary circuit.

Transformer protection RET650 107


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

The open CT algorithm provides detailed information about the location of the defective CT
secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in which an open
CT condition has been detected. These indications are provided via the following outputs from the
Transformer differential protection function:

1. Output OPENCT provides instant information to indicate that an open CT circuit has been
detected.
2. Output OPENCTAL provides a time-delayed alarm that the open CT circuit has been detected.
Time delay is defined by the parameter tOCTAlarmDelay.
3. Integer output OPENCTIN provides information on the local HMI regarding which open CT
circuit has been detected (1=CT input No 1; 2=CT input No 2).
4. Integer output OPENCTPH provides information on the local HMI regarding in which phase an
open CT circuit has been detected (1=Phase L1; 2= Phase L2; 3= Phase L3).

Once the open CT condition is declared, the algorithm stops to search for further open CT circuits. It
waits until the first open CT circuit has been corrected. Note that once the open CT condition has
been detected, it can be reset automatically within the differential function. It is not possible to
externally reset an open CT condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:

• Bias current is for at least one minute smaller than 110%


• The open CT condition in the defective CT circuit has been corrected (for example, current
asymmetry disappears)
• The above two conditions are fulfilled for a longer time than defined by the setting parameter
tOCTResetDelay

If an open CT has been detected in a separate group of three CTs, the algorithm is reset either when
the missing current returns to the normal value, or when all three currents become zero. After the
reset, the open CT detection algorithm starts again to search for open CT circuits within the protected
zone.

6.1.7.2 Logic diagram M13043-3 v9

The simplified internal logics, for transformer differential protection are shown in the following figures.

108 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

ADM Differential function


Trafo
Data

A/D conversion scaling with CT

Phasor calculation of individual

Open CT logic on W1 side


Instantaneous (sample based) IDL1

Phasors & samples


phase current
Differential current, phase L1
ratio

IDL2

Derive equation to calculate differential currents


Instantaneous (sample based)
Differential current, phase L2

Instantaneous (sample based) IDL3


Differential current, phase L3

Negative sequence diff current IDNSMAG


& NS current contribution from
A/D conversion scaling with CT

Phasor calculation of individual

individual windings
Open CT logic on W2 side
phase current

IDL1MAG
Fundamental frequency (phasor
based) Diff current, phase L1 &
ratio

phase current contributions from


individual windings
Phasors & samples

IDL2MAG
Fundamental frequency (phasor
based) Diff current, phase L2 &
phase current contributions from
individual windings
IDL3MAG
Fundamental frequency (phasor
based) Diff current, phase L3 &
phase current contributions from
individual windings
MAX IBIAS

Settings for Zer. Seq.


Current Reduction

en06000554-3-en.vsd
IEC06000544 V3 EN-US

Figure 42: Treatment of measured currents within IED for transformer differential function
Figure 42 shows how internal treatment of measured currents is done in case of a two-winding
transformer.

The following currents are inputs used in the power transformer differential protection function. They
must all be expressed in power system (primary) A.

1. Instantaneous values of currents (samples) from the HV, and LV sides for two-winding power
transformers, and from the HV, the first LV, and the second LV side for three-winding power
transformers.
2. Currents from all power transformer sides expressed as fundamental frequency phasors with
their real and imaginary parts. These currents are calculated within the protection function by the
fundamental frequency Fourier filters.
3. Negative sequence currents from all power transformer sides expressed as phasors. These
currents are calculated within the protection function by the symmetrical components module.

The power transformer differential protection:

Transformer protection RET650 109


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

1. Calculates three fundamental frequency differential currents and one common bias current. The
zero-sequence component can optionally be eliminated from each of the three fundamental
frequency differential currents and at the same time from the common bias current.
2. Calculates three instantaneous differential currents. They are used for harmonic, and waveform
analysis. Instantaneous differential currents are useful for post-fault analysis using disturbance
recording
3. Calculates negative-sequence differential current. Contributions to it from both (all three) power
transformer sides are used by the internal/external fault discriminator to detect and classify a
fault as internal or external.

BLKUNRES

IdUnre a TRIPUNREL1
b>a AND
b
IDL1MAG

IBIAS STL1
AND
BLOCK
BLKRES

TRIPRESL1
AND
OR 1

IDL1
to fault logic

2nd BLK2HL1
Switch on

Harmonic

Wave BLKWAVL1
block

5th BLK5HL1
Harmonic
Cross Block
Cross Block to L2 or L3
from L2 or L3 AND
OR
AND
OpCrossBlock=On

en06000545.vsd
IEC06000545 V1 EN-US

Figure 43: Transformer differential protection simplified logic diagram for Phase L1

Internal/ extFault
Neg.Seq. Diff External intFault
Current Fault
Contributions discrimin ≈60-80 ms
ator TRNSSENS
t
OpNegSeqDiff=On
2s
IBIAS t AND
a
150 % a>b S
b blk2h
R
a
110 % a≤ b
b
OpenCT

STL1
AND
STL2
OR
STL3

IEC05000167-TIFF V3 EN-US

Figure 44: Transformer differential protection simplified logic diagram for external/internal
fault discriminator

110 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

TRIPRESL1
TRIPRESL2 TRIPRES
OR
TRIPRESL3

TRIPUNREL1
TRIPUNREL2 TRIPUNRE
OR
TRIPUNREL3

TRIP
TRNSSENS OR
TRNSUNR

en05000278.vsd
IEC05000278 V1 EN-US

Figure 45: Transformer differential protection internal grouping of tripping signals

STL1
STL2 START
OR
STL3

BLK2HL1
BLK2HL2 BLK2H
OR
BLK2HL3
blk2h

BLK5HL1
BLK5HL2 BLK5H
OR
BLK5HL3

BLKWAVL1
BLKWAVL2 BLKWAV
OR
BLKWAVL3

IEC05000279-TIFF V3 EN-US

Figure 46: Transformer differential protection internal grouping of logical signals


Logic in figures 43, 44, 45 and 46 can be summarized as follows:

1. The three fundamental frequency differential currents are applied in a phase-wise manner to two
limits. The first limit is the operate-restrain characteristic, while the other is the high-set
unrestrained limit. If the first limit is exceeded, a start signal START is set. If the unrestrained
limit is exceeded, an immediate unrestrained trip TRIPUNRE and common trip TRIP are issued.
2. If a start signal is issued in a phase the harmonic and the waveform block signals are checked.
Only a start signal, which is free of all of its block signals can result in a trip command. If the
cross-block logic scheme is applied, then only if all phases with set start signal are free of their
respective block signals, a restrained trip TRIPRES and common trip TRIP are issued
3. If a start signal is issued in a phase, and the fault has been classified as internal, then any
eventual block signals are overridden and unrestrained negative-sequence trip TRNSUNR and
common trip TRIP are issued without any further delay. This feature is called the unrestrained
negative-sequence protection 110% bias.
4. The sensitive negative sequence differential protection is independent of any start signals. It is
meant to detect smaller internal faults such as turn-to-turn faults, which are often not detected
by the traditional differential protection. The sensitive negative sequence differential protection
starts whenever both contributions to the total negative sequence differential current (that must
be compared by the internal/external fault discriminator) are higher than the value of the setting
IMinNegSeq. If a fault is positively recognized as internal, and the condition is stable with no

Transformer protection RET650 111


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

interruption for at least one fundamental frequency cycle the sensitive negative sequence
differential protection TRNSSENS and common trip TRIP are issued. This feature is called the
sensitive negative sequence differential protection.
5. If a start signal is issued in a phase (see signal STL1), even if the fault has been classified as an
external fault, the instantaneous differential current of that phase (see signal IDL1) is analyzed
for the 2nd and the 5th harmonic contents (see the blocks with the text inside: 2nd Harmonic;
Wave block and 5th Harmonic). If there is less harmonic pollution. than allowed by the settings
I2/I1Ratio, and I5/I1Ratio, (then the outputs from the blocks 2nd harmonic and 5th harmonic is
0) then it is assumed that a minor simultaneous internal fault must have occurred. Only under
these conditions a trip command is allowed (the signal TRIPRESL1 is = 1). The cross-block logic
scheme is automatically applied under such circumstances. (This means that the cross block
signals from the other two phases L2 and L3 is not activated to obtain a trip on the TRIPRESL1
output signal in figure 43)
6. All start and blocking conditions are available as phase segregated as well as common (that is
three-phase) signals.

IDL1 MAG
a
a>b
I Diff Alarm b

IDL2 MAG tAlarm Delay


a
& IDALARM
a>b t
I Diff Alarm b

IDL3 MAG
a
a>b
I Diff Alarm b

en06000546.vsd
IEC06000546 V1 EN-US

Figure 47: Differential current alarm logic

6.1.8 Technical data IP12646-1 v1

M13046-1 v16

Table 46: T2WPDIF/T3WPDIF technical data

Function Range or value Accuracy


Operating characteristic Default Settings IEC 60255-187-1
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio -
Unrestrained differential current limit ()IBase on high voltage winding ±1.0% of set value
±1.0% of I r
Second harmonic blocking (5.0-100.0)% of fundamental ±1.0% of Ir
differential current Note: fundamental magnitude =
100% of Ir
Fifth harmonic blocking (5.0-100.0)% of fundamental ±5.0% of Ir
differential current Note: fundamental magnitude =
100% of Ir
Connection type for each of the Y or D -
windings
Phase displacement between high 0–11 -
voltage winding, W1 and each of the
windings, W2 and W3. Hour notation
Table continues on next page

112 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Function Range or value Accuracy


*Operate time at 0 to 10 x IdMin, Min. = 25 ms -
restrained function Max. = 35 ms
*Reset time at 10 x IdMin to 0, Min. = 5 ms -
restrained function Max. = 15 ms
*Operate time at 0 to 10 x Idunre, Min. = 5 ms -
unrestrained function Max. = 15 ms
*Reset time at 10 x Idunre to 0, Min. = 15 ms -
unrestrained function Max. = 35 ms
**Operate time, unrestrained negative Min. = 10 ms -
sequence function Max. = 20 ms
**Reset time, unrestrained negative Min. = 10 ms -
sequence function Max. = 30 ms
Critical impulse time 2 ms typically at 0 to 5 x IdMin -
*Note: Data obtained with single three-phase input current group.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both
sides as pre- and after-fault currents. The fault is performed by increasing one phase current to double on one side
and decreasing same phase current to zero on the other side.

6.2 High impedance differential protection, single phase


HZPDIF IP14239-1 v4

6.2.1 Identification M14813-1 v4

IEC 61850 IEC 60617 ANSI/IEEE C37.2


Function description
identification identification device number

High impedance differential protection,


HZPDIF Id 87
single phase

SYMBOL-CC V2 EN-US

6.2.2 Functionality M13071-3 v14

High impedance differential protection, single phase (HZPDIF) functions can be used when the
involved CT cores have the same turns ratio and similar magnetizing characteristics. It utilizes an
external CT secondary current summation by wiring. Actually all CT secondary circuits which are
involved in the differential scheme are connected in parallel. External series resistor, and a voltage
dependent resistor which are both mounted externally to the IED, are also required.

The external resistor unit shall be ordered under "" in the Product Guide.

HZPDIF can be used to protect tee-feeders or busbars, reactors, motors, auto-transformers,


capacitor banks and so on. One such function block is used for a high-impedance restricted earth
fault protection. Three such function blocks are used to form three-phase, phase-segregated
differential protection.

HZPDIF can be used as high impedance REF protection.

Transformer protection RET650 113


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

6.2.3 Function block M13737-3 v3

HZPDIF
ISI* TRIP
BLOCK ALARM
BLKTR MEASVOLT

IEC05000363-2-en.vsd
IEC05000363 V2 EN-US

Figure 48: HZPDIF function block

6.2.4 Signals IP14244-1 v2

PID-6990-INPUTSIGNALS v1

Table 47: HZPDIF Input signals

Name Type Default Description


ISI GROUP - Single phase current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

PID-6990-OUTPUTSIGNALS v1

Table 48: HZPDIF Output signals

Name Type Description


TRIP BOOLEAN Trip signal
ALARM BOOLEAN Alarm signal
MEASVOLT REAL Measured RMS voltage on CT secondary side

6.2.5 Settings IP14245-1 v2

PID-6990-SETTINGS v1

Table 49: HZPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
U>Alarm 5 - 500 V 1 10 Alarm voltage level in volts on CT
secondary side
tAlarm 0.000 - 60.000 s 0.001 5.000 Time delay to activate alarm
U>Trip 10 - 900 V 1 100 Operate voltage level in volts on CT
secondary side
SeriesResistor 50 - 20000 Ohm 1 250 Value of series resistor in Ohms

6.2.6 Monitored data


PID-6990-MONITOREDDATA v1

Table 50: HZPDIF Monitored data

Name Type Values (Range) Unit Description


MEASVOLT REAL - kV Measured RMS voltage on CT secondary
side

114 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

6.2.7 Operation principle IP14242-1 v2

M13075-3 v11
High impedance protection system is a simple technique which requires that all CTs, used in the
protection scheme, have relatively high knee point voltage, similar magnetizing characteristic and the
same ratio. These CTs are installed in all ends of the protected object. In order to make a scheme all
CT secondary circuits belonging to one phase are connected in parallel. From the CT junction points
a measuring branch is connected. The measuring branch is a series connection of one variable
setting resistor (or series resistor) RS with high ohmic value and an over-current element. Thus, the
high impedance differential protection responds to the current flowing through the measuring branch.
However, this current is result of a differential voltage caused by this parallel CT connection across
the measuring branch. Non-linear resistor (that is, metrosil) is used in order to protect entire scheme
from high peak voltages which may appear during internal faults. Typical high impedance differential
scheme is shown in Figure 49. Note that only one phase is shown in this figure.

RS

3 U
I
1
I> (50) 5

2
GUID-5CEAF088-D92B-45E5-B98F-3083894A694C V1 EN-US

Figure 49: HZPDIF scheme


Where in the Figure:

1. shows one main CT secondary winding connected in parallel with all other CTs, from the same
phase, connected to this scheme.
2. shows the scheme earthing point.

It is of utmost importance to insure that only one earthing point exists in such protection
scheme.

3. shows the setting (stabilizing) resistor RS.


4. shows the over-current measuring element.

The series connection of stabilizing resistor and over-current element is designated as


measuring branch.

5. shows the non-linear resistor (that is, metrosil).


6. U is the voltage across the CT paralleling point (for example, across the measuring branch).
7. I is the current flowing through the measuring branch.

U and I are interrelated in accordance with the following formula U=RS × I.

Due to the parallel CT connections the high impedance differential relay can only measure one
current and that is the relay operating quantity. That means that there is no any stabilizing quantity
(that is, bias) in high-impedance differential protection schemes. Therefore in order to guaranty the

Transformer protection RET650 115


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

stability of the differential relay during external faults the operating quantity must not exceed the set
pickup value. Thus, for external faults, even with severe saturation of some of the current
transformers, the voltage across the measuring branch shall not rise above the relay set pickup
value. To achieve that a suitable value for setting resistor RS is selected in such a way that the
saturated CT secondary winding provides a much lower impedance path for the false differential
current than the measuring branch. In case of an external fault causing current transformer
saturation, the non-saturated current transformers drive most of the spill differential current through
the secondary winding of the saturated current transformer and not through the measuring brunch of
the relay. The voltage drop across the saturated current transformer secondary winding appears also
across the measuring brunch, however it will typically be relatively small. Therefore, the pick-up value
of the relay has to be set above this false operating voltage.

See the application manual for operating voltage and sensitivity calculation.

6.2.7.1 Logic diagram M13075-9 v5

The logic diagram shows the operation principles for the 1Ph High impedance differential protection
function HZPDIF, see Figure 50.

The function utilizes the raw samples from the single phase current input connected to it. Thus the
twenty samples per fundamental power system cycle are available to the HZPDIF function. These
current samples are first multiplied with the set value for the used stabilizing resistor in order to get
voltage waveform across the measuring branch. The voltage waveform is then filtered in order to get
its RMS value. Note that used filtering is designed in such a way that it ensures complete removal of
the DC current component which may be present in the primary fault current. The voltage RMS value
is then compared with set Alarm and Trip thresholds. Note that the TRIP signal is intentionally
delayed on drop off for 30 ms within the function. The measured RMS voltage is available as a
service value from the function. The function has block and trip block inputs available as well.

IEC05000301 V1 EN-US

Figure 50: Logic diagram for 1Ph High impedance differential protection HZPDIF

116 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

6.2.8 Technical data IP14246-1 v1

M13081-1 v13

Table 51: HZPDIF technical data

Function Range or value Accuracy


Operate voltage (10-900) V ±1.0% of Ir
I=U/R
Reset ratio >95% -
Maximum continuous power See1) -
Operate time at 0 to 10 x Ud Min. = 5 ms
Max. = 15 ms
Reset time at 10 x Ud to 0 Min. = 75 ms
Max. = 95 ms
Critical impulse time 2 ms typically at 0 to 10 x Ud -

1) The value U2Trip/ R should always be lower than Stabilizing resistor thermal rating to allow continuous activation
during testing. If this value is exceeded, testing should be done with a transient faults. Typical value for the thermal
rating of the resistor is 100W.

6.3 Low impedance restricted earth fault protection


REFPDIF IP14640-1 v6

6.3.1 Identification
M14843-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Restricted earth fault protection, low REFPDIF 87N
impedance
IdN/I

SYMBOL-AA V1 EN-US

6.3.2 Functionality IP12418-1 v2

M13047-3 v20
Restricted earth-fault protection, low-impedance function (REFPDIF) can be used on all directly or
low-impedance earthed windings. The REFPDIF function provides high sensitivity and high speed
tripping as it protects each winding separately and thus does not need inrush stabilization.

The REFPDIF function is a percentage biased function with an additional zero sequence current
directional comparison criterion. This gives excellent sensitivity and stability during through faults.

Transformer protection RET650 117


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

6.3.3 Function block M13736-3 v9

REFPDIF
I3P* TRIP
I3PW1CT1* START
I3PW2CT1* DIROK
BLOCK BLK2H
IRES
IN
IBIAS
IDIFF
ANGLE
I2RATIO

IEC09000275_1_en.vsd
IEC09000275 V1 EN-US

Figure 51: REFPDIF function block

6.3.4 Signals IP12658-1 v2

PID-1904-INPUTSIGNALS v17

Table 52: Input signals for the function block REFPDIF (REF1-)

Signal Description
I3P Group signal for neutral current input
I3PW1CT1 Group signal for primary CT1 current input
I3PW2CT1 Group signal for secondary CT1 current input
BLOCK Block of function

PID-7411-OUTPUTSIGNALS v1

Table 53: REFPDIF Output signals

Name Type Description


TRIP BOOLEAN Trip by restricted earth fault protection function
START BOOLEAN Start by restricted earth fault protection function
DIROK BOOLEAN Directional Criteria has operated for internal fault
BLK2H BOOLEAN Block due to 2-nd harmonic
IRES REAL Magnitude of fund. freq. residual current
IN REAL Magnitude of fund. freq. neutral current
IBIAS REAL Magnitude of the bias current
IDIFF REAL Magnitude of fund. freq. differential current
ANGLE REAL Direction angle from zerosequence feature
I2RATIO REAL Second harmonic ratio

6.3.5 Settings IP12660-1 v2

PID-7411-SETTINGS v1

Table 54: REFPDIF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

118 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Table 55: REFPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IdMin 4.0 - 100.0 %IB 0.1 10.0 Maximum sensitivity in % of IBase
CTFactorPri1 1.0 - 10.0 - 0.1 1.0 CT factor for HV side CT1 (CT1rated/
HVrated current)
CTFactorPri2 1.0 - 10.0 - 0.1 1.0 CT factor for HV side CT2 (CT2rated/
HVrated current)
CTFactorSec1 1.0 - 10.0 - 0.1 1.0 CT factor for MV side CT1 (CT1rated/
MVrated current)
CTFactorSec2 1.0 - 10.0 - 0.1 1.0 CT factor for MV side CT2 (CT2rated/
MVrated current)

Table 56: REFPDIF Group settings (advanced)

Name Values (Range) Unit Step Default Description


ROA 60 - 119 Deg 1 60 Relay operate angle for zero sequence
directional feature if protected winding
neutral point is grounded via resistor
increase ROA to 115 degrees

6.3.6 Monitored data


PID-7411-MONITOREDDATA v1

Table 57: REFPDIF Monitored data

Name Type Values (Range) Unit Description


IRES REAL - A Magnitude of fund. freq. residual current
IN REAL - A Magnitude of fund. freq. neutral current
IBIAS REAL - A Magnitude of the bias current
IDIFF REAL - A Magnitude of fund. freq. differential
current
ANGLE REAL - deg Direction angle from zerosequence
feature
I2RATIO REAL - - Second harmonic ratio

6.3.7 Operation principle IP16290-1 v2

6.3.7.1 Fundamental principles of the restricted earth fault protection M5447-3 v17

Restricted earth fault protection, low impedance function (REFPDIF) detects earth faults on earthed
power transformer windings, most often an earthed star winding. REFPDIF is a unit protection of the
differential type. Since REFPDIF is based on the zero sequence current, which theoretically only
exists in case of an earth fault, REFPDIF can be made very sensitive regardless of normal load
currents. It is the fastest protection a power transformer winding can have. The high sensitivity and
the high speed tend to make such a protection unstable. Special measures must be taken to make it
insensitive to conditions for which it should not operate, for example, heavy through faults of phase-
to-phase type or heavy external earth faults.

REFPDIF is a differential protection of the low impedance type. All three-phase currents, and the
neutral point current, must be fed separately to REFPDIF. The fundamental frequency components of
all currents are extracted from all input currents, while other eventual zero sequence components,
such as the 3rd harmonic currents, are fully suppressed. Then the residual current phasor is
calculated from the three line current phasors. This zero sequence current phasor is added to the
neutral current vectorially, in order to obtain differential current.

Transformer protection RET650 119


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

The following facts may be observed from Figure 52 and Figure 53, where the three line CTs are
shown as connected together in order to measure the residual 3Io current, for the sake of simplicity.

These three zone of protection


zero-sequence
currents are not measured
Izs1
L1 L1

Power Izs1
L2 L2
system
Izs1 L3
L3
3Izs1

Uzs Current in the neutral


IL1+ IL2+IL3 = 3I0 (measured as IN ) serves
3I0 = 3Izs1 IN = -3Izs1 as a directional reference
Ifault (Summation in the IED) because it has the same
direction for both internal
Return path through
transformer and external faults.
Return path via
power system
External
fault
block operate Zero-sequence differential
region
IN current for external fault
3I0
Idiff = abs(3I0 + IN )
block Idiff = 3Izs1 - 3Izs1 = 0
ROA
External Internal
fault block fault
ROA = Relay Operate Angle
region region
IEC09000107-3-en.vsd
IEC09000107-3 V1 EN-US

Figure 52: Zero sequence currents at an external earth fault

zone of protection

Izs2 Izs1
L1 L1
Power Izs2 Izs1
L2 L2
system
Izs2 Izs1 L3
L3
3Izs1

Uzs Current in the neutral


IL1+ IL2+IL3 = 3I0 (measured as IN ) serves
IN = -3Izs1 as a directional reference
3I0 = -3Izs2 Ifault
(Summation in the IED) because it has the same
direction for both internal
and external faults.
Return path via Return path
power system through transformer
External
Zero-sequence differential
fault
block operate
region current for internal fault
3I0 Idiff = abs(3I0 + IN )
Idiff = 3Izs2 + 3Izs1 > 0
block IN (reference) Idiff = Ifault
ROA
External Internal
fault
block fault ROA = Relay Operate Angle
region region
IEC09000108-3-en.vsd
IEC09000108-3 V1 EN-US

Figure 53: Zero sequence currents at an internal earth fault

1. For an external earth fault (Figure 52), the residual current 3Io and the neutral current IN have
equal magnitude, but they are seen within the IED as 180 degrees out-of-phase if the current
transformers are connected as in Figure 52, which is the Hitachi Energy recommended
connection. The differential current becomes zero as both CTs ideally measure exactly the same
component of the earth fault current.
2. For an internal fault, the total earth fault current is composed generally of two zero sequence
currents. One zero sequence current (3IZS1) flows towards the power transformer neutral point

120 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

and into the earth, while the other zero sequence current (3IZS2) flows into the connected power
system. These two primary currents can be expected to have approximately opposite directions
(about the same zero sequence impedance angle is assumed on both sides of the earth fault).
However, on the secondary CT sides of the current transformers, they will be approximately in
phase if the current transformers are oriented as in Figure "", which is the orientation
recommended by Hitachi Energy. The magnitudes of the two currents may be different,
dependent on the magnitudes of zero sequence impedances on both sides. No current can flow
towards the power system, if the only point where the system is earthed, is at the protected
power transformer. Likewise, no current can flow into the power system, if the winding is not
connected to the power system (circuit breaker open and power transformer energized from the
other side).
3. For both internal and external earth faults, the current in the neutral connection IN always has
the same direction, which is towards the earth (except in case of autotransformers where the
direction can vary).
4. The two internally processed zero sequence currents are 3Io and IN. The vectorial sum is the
REFPDIF differential current, which is equal to Idiff = IN +3Io .

The line zero sequence (residual) current is calculated from 3 line (terminal) currents. A bias quantity
must give stability against false operations due to high through fault currents. To stabilize REFPDIF
at external faults, an operate-bias characteristic is used.

REFPDIF should also be stable against heavy phase-to-phase internal faults, not including earth.
These faults may also give false zero sequence currents due to saturated line CTs. Such faults,
however are without neutral current, and can thus be eliminated as a source of danger.

As an additional measure against unwanted operation, a directional check is made in agreement with
the above points 1 and 2. Operation is only allowed if the currents 3Io and IN (as shown in Figure 52
and Figure 53) are both within the operating region. By taking a smaller ROA, REFPDIF can be
made more stable under heavy external fault conditions, as well as under the complex conditions,
when external faults are cleared by other protections.

6.3.7.2 Restricted earth fault protection, low impedance differential protection M5447-20 v14

Restricted earth fault protection, (REFPDIF) is a protection of low impedance differential type, a unit
protection, whose settings are independent of any other protection. It has some advantages
compared to the transformer differential protection. It is less complicated, as no current phase
correction or magnitude correction is needed, not even in the case of an eventual on-load tap
changer (OLTC). REFPDIF is not sensitive to inrush and overexcitation currents. The thing to take
into account is an eventual current transformer saturation.

The differential protection REFPDIF calculates a differential current and a bias current. In case of
internal earth faults, the differential current is theoretically equal to the total earth fault current. The
bias to give stability to REFPDIF. The bias current is a measure of how high the currents are and how
difficult the conditions are under which the CTs operate. With a high bias, difficult conditions can be
suspected, and it will be more likely that the calculated differential current has a component of a false
current, primarily due to CT saturation. This “law” is formulated by the operate-bias characteristic.
This characteristic divides the Idiff - Ibias plane in two areas. The area above the operate-bias
characteristic is the operate area (trip), while the one below is the restrain (block) area, see Figure
55.

Calculation of operate bias characteristic

End of zone 1:

Endzone1 = 125%

End of zone 2:

Endzone2 =

Transformer protection RET650 121


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

(100 − IdMin)
EndZone2 = 125 +
0.7
IECEQUATION20201 V1 EN-US (Equation 24)

SlopeSection2:

The slope in section 2 (see Figure 55) of operate-restrain characteristic is fixed to 70%. The slope
section 2, starts at end of zone 1, continues until end of zone 2.

SlopeSection3:

The slope in section 3 (see Figure 55) of operate-restrain characteristic is fixed to 100%. The slope
section 3, starts at end of zone 2 and continues.

REFPDIF uses an operate-bias characteristic shown in Figure 55, using a setting IdMin see Table 7.

Table 59: Setting range of IdMin, end zones and slopes

IdMin default IdMin min (zone IdMin max (zone End of zone 1 Slope section 2 Slope section 3
(zone 1) 1) 1) (fixed) (fixed) (fixed)
% of IBase % of IBase % of IBase % of IBase % of IBase % of IBase
10 4 100 125 70 100

IEC20000410-1-en.vsdx
IEC20000410 V1 EN-US

Figure 55: Representation of Operate-bias characteristics at different IdMin setting values


Figure 55 represents the Operate-bias characteristics at different IdMin setting values

The highest individual current contribution is taken as a common bias (restrain) current among all
phase currents or neutral current. This "maximum principle" makes the differential protection more
secure, with less risk to operate for external faults and in the same time brings more meaning to the
breakpoint settings of the operate-restrain characteristic.

6.3.7.3 Calculation of differential current and bias current M5447-47 v13

The differential current (operate current), as a fundamental frequency phasor, is calculated as (with
designations as in Figure 52 and Figure 53):

122 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

Idiff = IN + 3 Io
EQUATION1533 V1 EN-US (Equation 25)

where:

IN is current in the power transformer neutral as a fundamental frequency phasor.

3Io is residual current of the power transformer terminal currents as a phasor.

If there are two three-phase CT inputs, as in breaker-and-a-half configurations, then their respective
residual currents are added within the REFPDIF function so that:

I3PW1 = I3PW1CT1 + I3PW1CT2

where the signals are defined in the input and output signal tables for REFPDIF.

The bias current is a measure (expressed internally as a true fundamental frequency current in
Amperes) of how difficult the conditions are under which the instrument current transformers operate.
Dependent on the magnitude of the bias current, the corresponding zone (section) of the operate-
bias characteristic is applied, when deciding whether to trip, or not to trip. In general, the higher the
bias current, the higher the differential current required to produce a trip.

The bias current is the highest current of all separate input currents to REFPDIF, that is, of current in
phase L1, phase L2, phase L3, and the current in the neutral point (designated as IN in Figure and
in Figure Figure).

If there are two feeders included in the zone of protection of REFPDIF, as in case of an auto-
transformer with two feeders included on both sides, then the respective bias current is found as the
relatively highest of the following currents:

1
current 1 = max( I 3PW 1CT1) 
CTFactor Pr i1
EQUATION1526 V2 EN-US (Equation 26)

1
current  2 = max( I 3PW 1CT 2) 
CTFactor Pr i 2
EQUATION1527 V2 EN-US (Equation 27)

1
current 3 = max( I 3PW 2CT1) 
CTFactorSec1
EQUATION1528 V2 EN-US (Equation 28)

1
current  4 = max( I 3PW 2CT 2) 
CTFactorSec2
EQUATION1529 V2 EN-US (Equation 29)

current 5 = IN
EQUATION1530 V2 EN-US (Equation 30)

The bias current is thus generally equal to none of the input currents. If all primary ratings of the CTs
were equal to IBase, then the bias current would be equal to the highest current in Amperes. IBase
shall be set equal to the rated current of the protected winding where REFPDIF function is applied.

6.3.7.4 Detection of external earth faults M5447-75 v12

External faults are more common than internal earth faults for which the restricted earth fault
protection should operate. It is important that the restricted earth fault protection remains stable

Transformer protection RET650 123


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

during heavy external earth and phase-to-phase faults, and also when such a heavy external fault is
cleared by some other protection such as overcurrent, or earth fault protection. The conditions during
a heavy external fault, and particularly immediately after the clearing of such a fault may be complex.
The circuit breaker’s poles may not open exactly at the same moment, some of the CTs may still be
highly saturated, and so on.

The detection of external earth faults is based on the fact that for such a fault a high neutral current
appears first, while a false differential current only appears if one or more current transformers
saturate.

An external earth fault is thus assumed to have occurred when a high neutral current suddenly
appears, while at the same time the differential current Idiff remains low, at least for a while. This
condition must be detected before a trip request is placed within REFPDIF. Any search for external
fault is aborted if a trip request has been placed. A condition for a successful detection is that it takes
not less than 4ms for the first CT to saturate.

For an internal earth fault, a true differential current develops immediately, while for an external fault
it only develops if a CT saturates. If a trip request comes first, before an external fault could be
positively detected, then it must be an internal fault.

If an external earth fault has been detected, then the REFPDIF is temporarily desensitized.

Directional criterion M5447-110 v13


The directional criterion is applied in order to positively distinguish between internal and external
earth faults. This check is an additional criterion, which should prevent malfunctions at heavy
external earth faults, and during the disconnection of such faults by other protections. Earth faults on
lines connecting the power transformer occur much more often than earth faults on a power
transformer winding. It is important that the Restricted earth fault protection, low impedance
(REFPDIF) must remain stable during an external fault, and immediately after the fault has been
cleared by some other protection.

For an external earth faults with no CT saturation, the residual current in the lines (3Io) and the
neutral current (IN in Figure 52) are theoretically equal in magnitude and are 180 degrees out-of-
phase. The current in the neutral (IN) serves as a directional reference because it has the same
direction for both internal and external earth faults. The directional criterion in REFPDIF protection
makes it a current-polarized protection.

However, if one or more CTs saturate under external fault conditions, then the measured currents 3Io
and IN may no longer be equal, nor will their positions in the complex plane be exactly 180 degrees
apart. There is a risk that the resulting false differential current Idiff enters the operate area of the
operate-restrain characteristic under external fault conditions. If this happens, a directional test may
prevent a malfunction.

A directional check is only executed if:

1. a trip request signal has been issued (REFPDIF function START signal set to 1)
2. the residual current in lines (3Io) is at least 3% of the IBase current.

If a directional check is either unreliable or not possible to do, due to too small currents, then the
direction is cancelled as a condition for an eventual trip.

If a directional check is executed, the REFPDIF protection operation is only allowed if currents 3Io
and IN (as seen in Figure 52 and Figure 53) are both within the operating region determined by the
set value of ROA, in degrees.

ROA = 60 to 119 deg; where ROA stands for Relay Operate Angle.

Second harmonic analysis M5447-106 v13


When energizing a transformer a false differential current may appear in earth fault protection, low
impedance function (REFPDIF). The phase CTs may saturate due to a high DC component with a

124 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 6
Differential protection

long duration, but the current through the neutral CT does not have either the same DC component
or the same amplitude and the risk for saturation of this CT is not as high. As a result, the differential
current due to the saturation may be so high that it reaches the operate characteristic. A calculation
of the content of 2nd harmonic in the neutral current is made when the neutral current, residual
current and bias current are within some windows and some timing criteria are fulfilled. If the ratio
between second and fundamental harmonic exceeds the preset value of 40% 40%, REFPDIF is
blocked.

6.3.7.5 Algorithm of the restricted earth fault protection M5447-95 v14

1. Check if current in the neutral Ineutral (IN) is less than 50% of the base sensitivity Idmin. If yes,
only service values are calculated, and rest of the REFPDIF algorithm is not executed.
2. If current in the Ineutral (IN) is more than 50% of Idmin, then determine the bias current Ibias.
3. Determine the differential (operate) current Idiff as a phasor, and calculate its magnitude.
4. Check if the point P(Ibias, Idiff) is above the operate-bias characteristic. If yes, increment the trip
request counter by 1. If the point P(Ibias, Idiff) is found to be below the operate-bias
characteristic, then the trip request counter is reset to zero.
5. If the trip request counter is still zero, search for an eventual heavy external earth fault. The
search is only made if the neutral current is at least 50% of the Idmin current. If an external earth
fault has been detected, a flag is set which remains set until the external fault has been cleared.
The external fault flag is reset to zero when Ineutral falls below 50% of the base sensitivity
Idmin. Any search for an external fault is aborted if trip request counter is greater than zero.
6. As long as the external fault persists, an additional temporary trip condition is introduced. This
means that REFPDIF is temporarily desensitized.
7. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), so that trip request
counter is greater than zero, a directional check can be made. The directional check is made
only if Iresidual (3Io) is more than 3% of the IBase current. If the result of the check means
“external fault”, then the internal trip request is reset. If the directional check cannot be
executed, then direction is no longer a condition for a trip.
8. When neutral current, residual current and bias current are within some windows and some
timing criteria are fulfilled, the ratio of 2nd to fundamental harmonic is calculated. If it is found to
be above 40%, the trip request counter is reset and TRIP remains zero.
9. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), a directional check
can be made. The directional check is made only if Iresidual (3Io) is more than 3% of the IBase
current. If the result of the check means “external fault”, then the internal trip request is reset. If
the directional check cannot be executed, then the direction is no longer a condition for a trip.
10. Finally, the trip request counter is checked. If the trip request counter is greater or equal than 2
and at the same time the actual bias current is at least 50% of the highest bias current Ibiasmax
(Ibiasmax is the highest recording of any of the three phase currents measured during the
disturbance), REFPDIF will set output TRIP to 1. Otherwise, the TRIP signal remains zero.
11. Finally, a check is made if the trip request counter is equal to, or higher than 2. If yes, and at the
same instance of time tREFtrip, the actual bias current at this instance of time tREFtrip is at least
50% of the highest bias current Ibiasmax (Ibiasmax is the highest recording of any of the three
phase currents measured during the disturbance), then REFPDIF sets output TRIP to 1. If the
counter is less than 2, the TRIP signal remains zero.

6.3.8 Technical data IP12661-1 v1

M13062-1 v24

Table 60: REFPDIF technical data

Function Range or value Accuracy


Operating characteristic Default Settings IEC 60255-187-1
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio -
Minimum pickup, IdMin (4.0-100.0)% of IBase ±1.0% of Ir

Table continues on next page

Transformer protection RET650 125


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 6 1MRK504170-UEN Rev. J
Differential protection

Function Range or value Accuracy


Directional characteristic
Operate time, trip at 0 to 10 x IdMin Min. = 15 ms -
Max. = 30 ms
Reset time, trip at 10 x IdMin to 0 Min. = 15 ms -
Max. = 30 ms
Second harmonic blocking ±1.0% of Ir

126 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Section 7 Current protection


7.1 Instantaneous phase overcurrent protection PHPIOC IP14506-1 v6

7.1.1 Identification
M14880-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous phase overcurrent PHPIOC 50
protection
3I>>

SYMBOL-Z V1 EN-US

7.1.2 Functionality M12910-3 v15

The instantaneous three phase overcurrent (PHPIOC) function has a low transient overreach and
short tripping time to allow use as a high set short-circuit protection function.

7.1.3 Function block M12602-3 v6

PHPIOC
I3P* TRIP
BLOCK TRL1
ENMULT TRL2
TRL3

IEC04000391-2-en.vsd
IEC04000391 V2 EN-US

Figure 56: PHPIOC function block

7.1.4 Signals IP11433-1 v2

PID-6914-INPUTSIGNALS v3

Table 61: PHPIOC Input signals

Name Type Default Description


I3P GROUP - Three phase current
SIGNAL
BLOCK BOOLEAN 0 Block of function
ENMULT BOOLEAN 0 Enable current start value multiplier

PID-6914-OUTPUTSIGNALS v3

Table 62: PHPIOC Output signals

Name Type Description


TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3

7.1.5 Settings IP11434-1 v2

Transformer protection RET650 127


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

PID-6914-SETTINGS v3

Table 63: PHPIOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OpMode 2 out of 3 - - 1 out of 3 Select operation mode 2-out of 3 / 1-out
1 out of 3 of 3
IP>> 5 - 2500 %IB 1 200 Operate phase current level in % of IBase

Table 64: PHPIOC Group settings (advanced)

Name Values (Range) Unit Step Default Description


IP>>Min 5 - 2500 %IB 1 5 Minimum used operate phase current
level in % of IBase, if IP>> is less than
IP>>Min then IP>> is set to IP>>Min
IP>>Max 5 - 2500 %IB 1 2500 Maximum used operate phase current
level in % of IBase, if IP>> is greater than
IP>>Max then IP>> is set to IP>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 65: PHPIOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

7.1.6 Monitored data


PID-6914-MONITOREDDATA v3

Table 66: PHPIOC Monitored data

Name Type Values (Range) Unit Description


IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

7.1.7 Operation principle M12913-3 v8

The sampled analogue phase currents are pre-processed in a discrete Fourier filter (DFT) block. The
RMS value of each phase current is derived from the fundamental frequency components, as well as
sampled values of each phase current. These phase current values are fed to the instantaneous
phase overcurrent protection 3-phase output function PHPIOC. In a comparator the RMS values are
compared to the set operation current value of the function (IP>>).

If a phase current is larger than the set operation current a signal from the comparator for this phase
is set to true. This signal will, without delay, activate the output signal TRLn (n=1,2,3) for this phase
and the TRIP signal that is common for all three phases.

There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the parameter is set to 1 out
of 3, any phase trip signal will be activated. If the parameter is set to 2 out of 3, at least two phase
signals must be activated for trip.

There is also a possibility to activate a preset change of the set operation current (StValMult) via a
binary input (ENMULT). In some applications the operation value needs to be changed, for example,
due to transformer inrush currents.

128 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

The operation current value IP>>, is limited to be between IP>>Max and IP>>Min. The default values
of the limits are the same as the setting limits for IP>>, and the limits can only be used for reducing
the allowed range of IP>>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If IP>> is set
outside IP>>Max and IP>>Min, the closest of the limits to IP>> is used by the function. If IP>>Max is
smaller then IP>>Min, the limits are swapped. The principle of the limitation is shown in Figure 57.

IP>>Max
MAX hi

u y
IP>>_used
IP>>

MIN lo
IP>>Min
IEC17000016-1-en.vsdx
IEC17000016 V1 EN-US

Figure 57: Logic for limitation of used operation current value

PHPIOC can be blocked using the binary input BLOCK.

7.1.8 Technical data IP11435-1 v1

M12336-1 v14

Table 67: PHPIOC technical data

Function Range or value Accuracy


Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio > 95% at (50–2500)% of IBase -
Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 30 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time at 0 to 10 x Iset Min. = 5 ms -
Max. = 15 ms
Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 40 ms
Critical impulse time 2 ms typically at 0 to 10 x Iset -
Dynamic overreach < 5% at t = 100 ms -

7.2 Directional phase overcurrent protection, four steps


OC4PTOC SEMOD129998-1 v8

7.2.1 Function revision history GUID-154CAE8E-8FD4-460C-852D-6E5C93545F0D v2

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
Table continues on next page

Transformer protection RET650 129


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Document Product History


revision revision
D 2.2.1 -
E 2.2.4 -
F 2.2.5 • The harmonic restraint function changed to freeze the definite and IDMT timers.
• The maximum value of the settings IMin1, IMin2, IMin3 and IMin4 has been
decreased to 1000.0 % of IBase.

H 2.2.6 -
J 2.2.6 Minimum value changed to 0.01 for k1,k2,k3 and k4 settings

7.2.2 Identification
M14885-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional phase overcurrent OC4PTOC 51_67
protection, four steps

TOC-REVA V2 EN-US

7.2.3 Functionality M12846-3 v18

Directional phase overcurrent protection, four steps (OC4PTOC) has an inverse or definite time delay
for each step.

All IEC and ANSI inverse time characteristics are available together with an optional user defined
time characteristic.

The directional function needs voltage as it is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.

A second harmonic blocking level can be set for the function and can be used to block each step
individually.

130 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.2.4 Function block M12609-3 v8

OC4PTOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKTR TR3
BLKST1 TR4
BLKST2 TRL1
BLKST3 TRL2
BLKST4 TRL3
ENMULT1 TR1L1
ENMULT2 TR1L2
ENMULT3 TR1L3
ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
ST2NDHRM
DIRL1
DIRL2
DIRL3
STDI RCND
IEC06000187-4-en.vsdx
IEC06000187 V4 EN-US

Figure 58: OC4PTOC function block

7.2.5 Signals
PID-8147-INPUTSIGNALS v1

Table 68: OC4PTOC Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of Step1
BLKST2 BOOLEAN 0 Block of Step2
BLKST3 BOOLEAN 0 Block of Step3
BLKST4 BOOLEAN 0 Block of Step4
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
Table continues on next page

Transformer protection RET650 131


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Type Default Description


ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-8147-OUTPUTSIGNALS v1

Table 69: OC4PTOC Output signals

Name Type Description


TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
TR3 BOOLEAN Common trip signal from step3
TR4 BOOLEAN Common trip signal from step4
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
TR3L1 BOOLEAN Trip signal from step3 phase L1
TR3L2 BOOLEAN Trip signal from step3 phase L2
TR3L3 BOOLEAN Trip signal from step3 phase L3
TR4L1 BOOLEAN Trip signal from step4 phase L1
TR4L2 BOOLEAN Trip signal from step4 phase L2
TR4L3 BOOLEAN Trip signal from step4 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2
ST3 BOOLEAN Common start signal from step3
ST4 BOOLEAN Common start signal from step4
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3
ST3L1 BOOLEAN Start signal from step3 phase L1
ST3L2 BOOLEAN Start signal from step3 phase L2
ST3L3 BOOLEAN Start signal from step3 phase L3
ST4L1 BOOLEAN Start signal from step4 phase L1
ST4L2 BOOLEAN Start signal from step4 phase L2
ST4L3 BOOLEAN Start signal from step4 phase L3
Table continues on next page

132 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Type Description


ST2NDHRM BOOLEAN Second harmonic detected
DIRL1 INTEGER Direction for phase1
DIRL2 INTEGER Direction for phase2
DIRL3 INTEGER Direction for phase3
STDIRCND INTEGER Binary coded start and directional information

7.2.6 Settings
PID-8147-SETTINGS v1

Table 70: OC4PTOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Table 71: OC4PTOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
AngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)
AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)
StartPhSel 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3)
3 out of 3
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for step
ANSI Very inv. 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I1> 5 - 2500 %IB 1 1000 Operating phase current level for step 1 in
% of IBase
t1 0.000 - 60.000 s 0.001 0.000 Definite time delay / additional time delay
for IDMT characteristics of step 1
k1 0.01 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
IMin1 1 - 1000 %IB 1 100 Minimum operate current for step1 in % of
IBase
Table continues on next page

Transformer protection RET650 133


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step
1
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for step
ANSI Very inv. 2
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2> 5 - 2500 %IB 1 500 Operating phase current level for step 2 in
% of IBase
t2 0.000 - 60.000 s 0.001 0.400 Definite time delay / additional time delay
for IDMT characteristics of step 2
k2 0.01 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
IMin2 1 - 1000 %IB 1 50 Minimum operate current for step2 in % of
IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step
2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for step
ANSI Very inv. 3
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page

134 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


I3> 5 - 2500 %IB 1 250 Operating phase current level for step 3 in
% of IBase
t3 0.000 - 60.000 s 0.001 0.800 Definite time delay / additional time delay
for IDMT characteristics of step 3
k3 0.01 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 3
IMin3 1 - 1000 %IB 1 33 Minimum operate current for step3 in % of
IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step
3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for step
ANSI Very inv. 4
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I4> 5 - 2500 %IB 1 175 Operating phase current level for step 4 in
% of IBase
t4 0.000 - 60.000 s 0.001 2.000 Definite time delay / additional time delay
for IDMT characteristics of step 4
k4 0.01 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay
for step 4
IMin4 1 - 1000 %IB 1 17 Minimum operate current for step4 in % of
IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves
for step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step
4

Table 72: OC4PTOC Group settings (advanced)

Name Values (Range) Unit Step Default Description


IMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection in %
of IBase
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in %
of fundamental curr
I1>Max 5 - 2500 %IB 1 2500 Maximum used operating phase current
level for step 1 in % of IBase, if I1> is
greater than I1>Max then I1> is set to
I1>Max
Table continues on next page

Transformer protection RET650 135


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


I1>Min 5 - 2500 %IB 1 5 Minimum used operating phase current
level for step 1 in % of IBase, if I1> is less
than I1>Min then I1> is set to I1>Min
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
IEC Reset
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 1
HarmBlock1 Off - - Off Enable block of step 1 from harmonic
On restrain
I2>Max 5 - 2500 %IB 1 2500 Maximum used operating phase current
level for step 2 in % of IBase, if I2> is
greater than I2>Max then I2> is set to
I2>Max
I2>Min 5 - 2500 %IB 1 5 Minimum used operating phase current
level for step 2 in % of IBase, if I2> is less
than I2>Min then I2> is set to I2>Min
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
IEC Reset
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 2
HarmBlock2 Off - - Off Enable block of step 2 from harmonic
On restrain
I3>Max 5 - 2500 %IB 1 2500 Maximum used operating phase current
level for step 3 in % of IBase, if I3> is
greater than I3>Max then I3> is set to
I3>Max
I3>Min 5 - 2500 %IB 1 5 Minimum used operating phase current
level for step 3 in % of IBase, if I3> is less
than I3>Min then I3> is set to I3>Min
Table continues on next page

136 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


ResetTypeCrv3 Instantaneous - - Instantaneous Selection of reset curve type for step 3
IEC Reset
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 3
HarmBlock3 Off - - Off Enable block of step 3 from harmonic
On restrain
I4>Max 5 - 2500 %IB 1 2500 Maximum used operating phase current
level for step 4 in % of IBase, if I4> is
greater than I4>Max then I4> is set to
I4>Max
I4>Min 5 - 2500 %IB 1 5 Minimum used operating phase current
level for step 4 in % of IBase, if I4> is less
than I4>Min then I4> is set to I4>Min
ResetTypeCrv4 Instantaneous - - Instantaneous Selection of reset curve type for step 4
IEC Reset
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 4
HarmBlock4 Off - - Off Enable block of step 4 from harmonic
On restrain

Transformer protection RET650 137


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.2.7 Monitored data


PID-8147-MONITOREDDATA v1

Table 73: OC4PTOC Monitored data

Name Type Values (Range) Unit Description


DIRL1 INTEGER 0=No direction - Direction for phase1
1=Forward
2=Reverse
DIRL2 INTEGER 0=No direction - Direction for phase2
1=Forward
2=Reverse
DIRL3 INTEGER 0=No direction - Direction for phase3
1=Forward
2=Reverse
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

7.2.8 Operation principle M12883-3 v11

Directional phase overcurrent protection, four steps OC4PTOC is divided into four different sub-
functions. For each step x , where x is step 1, 2, 3 and 4, an operation mode is set by DirModex: Off/
Non-directional/Forward/Reverse.

The protection design can be divided into four parts:

• The direction element


• The harmonic restraint blocking function
• The four step overcurrent function
• The mode selection

If VT inputs are not available or not connected, setting parameter DirModex shall be left
to default value, Non-directional.

138 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

4 step overcurrent
Direction dirPh1Flt element faultState
faultState
Element One element for each
dirPh2Flt step
I3P dirPh3Flt START

U3P

TRIP

Harmonic harmRestrBlock
Restraint
Element

enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4

IEC05000740-3-en.vsdx

IEC05000740 V3 EN-US

Figure 59: Functional overview of OC4PTOC


M12883-16 v13
A common setting for all steps, StartPhSel, is used to specify the number of phase currents to be
high to enable operation. These settings can be chosen: 1 out of 3, 2 out of 3 or 3 out of 3.

Using a parameter setting MeasType within the general settings for the function OC4PTOC, it is
possible to select the type of the measurement used for all overcurrent stages. Either discrete
Fourier filter (DFT) or true RMS filter (RMS) can be selected.

If the DFT option is selected, only the RMS value of the fundamental frequency component of each
phase current is derived. The influence of the DC current component and higher harmonic current
components are almost completely suppressed. If the RMS option is selected, then the true RMS
value is used. The true RMS value includes the contribution from the current DC component as well
as from the higher current harmonic in addition to the fundamental frequency component.

In a comparator, the DFT or RMS values are compared to the set operation current value of the
function (I1>, I2>, I3> or I4>) for each phase current. If a phase current is larger than the set
operation current, outputs START, STx, STL1, STL2 and STL3 are activated without delay. Output
signals STL1, STL2 and STL3 are common for all steps. This means that the lowest set step will
initiate the activation. The START signal is common for all three phases and all steps. It shall be
noted that the selection of measured value (DFT or RMS) do not influence the operation of
directional part of OC4PTOC.

Service values for individually measured phase currents are available on the local HMI for OC4PTOC
function, which simplifies testing, commissioning and in service operational checking of the function.

A harmonic restrain of the function can be chosen. A set 2nd harmonic current in relation to the
fundamental current is used.

The function can be directional. The direction of a fault is given as the current angle in relation to the
voltage angle. The fault current and fault voltage for the directional function are dependent on the
fault type. The selection of the measured value (DFT or RMS) does not influence the operation of the
directional part of OC4PTOC. To enable directional measurement at close-in faults, causing a low
measured voltage, the polarization voltage is a combination of the apparent voltage (85%) and a
memory voltage (15%). The following combinations are used.

Transformer protection RET650 139


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Phase-phase short circuit:

U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN-US (Equation 31)

U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN-US (Equation 32)

U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN-US (Equation 33)

Phase-earth short circuit:

U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN-US (Equation 34)

U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN-US (Equation 35)

U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN-US (Equation 36)

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the set
base voltage UBase. So the directional element can be used for all unsymmetrical faults including
close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive sequence
voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current (7% of the set terminal
rated current IBase), the condition seals in.
• If the fault has caused tripping, the trip endures.
• If the fault was detected in the reverse direction, the measuring element in the reverse
direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function and an angle
window ROADir.

140 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Reverse

Uref

RCA
ROA

ROA Forward

Idir

en05000745.vsd
IEC05000745 V1 EN-US

Figure 60: Directional characteristic of the phase overcurrent protection


The default value of AngleRCA is –55°. The parameter AngleROA gives the angular distance from
AngleRCA to define the directional borders.

A minimum current for the directional phase start current signal can be set. IMinOpPhSel is the start
level for the directional evaluation of IL1, IL2 and IL3. The directional signals release the overcurrent
measurement in the respective phases if their current amplitudes are higher than the start level
(IMinOpPhSel) and the direction of the current is according to the set direction of the step.

If no blocking signals are active, the start signal will start the timer of the steps. The time
characteristic for each step can be chosen as definite time delay or an inverse time delay
characteristic. A wide range of standardized inverse time delay characteristics is available. It is also
possible to create a tailor made time characteristic.

The possibilities for inverse time characteristics are described in section "Inverse characteristics".

Transformer protection RET650 141


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

HarmBlockx = Enabled
Freeze Timers
AND
2ndH_FreezeTimers_int

EMULTX

IMinx Characteristx=DefTime
X T b tx
F a>b
a t
TRx
AND AND
|IOP|
a OR
a>b
b

STx
IxMult AND
X T
F
Inverse
Ix>
AND

AND
Characteristx=Inverse

txmin
DirModex=Off t

OR STEPx_DIR_Int

DirModex=Non-directional

DirModex=Forward AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int

IEC12000008‐2‐en.vsdx
IEC12000008 V3 EN-US

Figure 61: Simplified logic diagram for OC4PTOC

I3P
DFWDLx

U3P DFWDLxx

DREVLx
Directional
Element
AngleRCA DREVLxx FORWARD_int

Directional
AngleROA Release REVERSE_int
Block

STLx

Greater
IMinOpPhSel Comparator
x‐ means three phases 1,2 and 3
xx – means phase to phase 12,23,31

IEC15000266-2-en.vsdx
IEC15000266 V2 EN-US

Figure 62: OC4 directional release block diagram


Different types of reset time can be selected as described in section "Inverse characteristics".

142 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

There is a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the set operation current
via a binary input ENMULTx (enable multiplier). In some applications the operation value needs to be
changed, for example due to changed network switching state.

The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The default values of
the limits are the same as the setting limits for Ix>, and the limits can only be used for reducing the
allowed range of Ix>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If Ix> is set outside
Ix>Max and Ix>Min, the closest of the limits to Ix> is used by the function. If Ix>Max is smaller then
Ix>Min, the limits are swapped. The principle of the limitation is shown in Figure 63.

Ix>Max
MAX hi

u y
Ix>_used
Ix>

MIN lo
Ix>Min

IEC17000018-1-en.vsdx
IEC17000018 V1 EN-US

Figure 63: Logic for limitation of used operation current value

The STDIRCND output provides an integer signal that depends on the start and directional
evaluation and is derived from a binary coded signal as described in Table 74.

Table 74: Code description for STDIRCND output signal

STDIRCND Description
bit 0 (1) General start
bit 1 (2) Direction detected in forward
bit 2 (4) Direction detected in reverse
bit 3 (8) Start in phase L1
bit 4 (16) Forward direction detected in phase L1
bit 5 (32) Reverse direction detected in phase L1
bit 6 (64) Start in phase L2
bit 7 (128) Forward direction detected in phase L2
bit 8 (256) Reverse direction detected in phase L2
bit 9 (512) Start in phase L3
bit 10 (1024) Forward direction detected in phase L3
bit 11 (2048) Reverse direction detected in phase L3

All four steps in OC4PTOC can be blocked from the binary input BLOCK. The binary input BLKSTx
(x=1, 2, 3 or 4) blocks the operation of the respective step.

The start signals from the function can be blocked by the binary input BLKST. The trip signals from
the function can be blocked by the binary input BLKTR.
GUID-E3980B2D-EEDA-4BF1-A07D-E7B721130554 v7
A harmonic restrain of the directional phase overcurrent protection function OC4PTOC can be
chosen. If the ratio of the 2nd harmonic component in relation to the fundamental frequency
component in a phase current exceeds the preset level defined by the parameter 2ndHarmStab
setting, any of the four overcurrent stages can have their timers selectively frozen by the parameter
HarmBlockx setting. When the 2nd harmonic restraint feature is active, the OC4PTOC function
output signal ST2NDHRM will be set to the logical value one.

Transformer protection RET650 143


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

Extract 2ndH_FreezeTimers_Int
fundamental
current component
X
2ndHarmStab

IEC13000014-3-en.vsdx
IEC13000014 V3 EN-US

Figure 64: Second harmonic blocking

When enabled, the 2nd harmonic blocking function is used to freeze the Definite and/or
the Inverse Characteristics internal timers. When the function detects a 2nd harmonic
higher than the set threshold, the internal function timers are frozen but START outputs
continues to be active as long as the measured current is above the set pickup level.
Internal timers will again resume timing when harmonic content becomes smaller than the
set threshold and the measured current is higher than the pickup value. If TRIP output is
already active when harmonic blocking signal appears the TRIP output will not be
affected.

When DirModex is set to Forward/Reverse and Ix> is set at its minimum value, that is,
5.0% of IBase, the operation from the respective overcurrent step takes place at 20.0% of
IBase. This is done to avoid unintentional maloperations during unbalanced loading
conditions that might appear in power systems and the unbalanced loading condition
might lead to a neutral current in the range of 10.0% to 15.0% of IBase.

7.2.9 Technical data


M12342-1 v23

Table 75: OC4PTOC technical data

Function Range or value Accuracy


Operate current, step 1-4 ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio -
Minimum operate current, step 1-4 % of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Relay characteristic angle (RCA)
Relay operating angle (ROA) (40.0–89.0) degrees ±2.0 degrees
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir
Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Minimum operate time for inverse (0.000-60.000) s
curves , step 1-4
Inverse time characteristics, see curve types
table 751, table 752 and table 753
Operate time, start non-directional at 0 Min. = 15 ms -
to 2 x Iset
Max. = 30 ms
Reset time, start non-directional at 2 x Min. = 15 ms -
Iset to 0
Max. = 30 ms
Table continues on next page

144 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Function Range or value Accuracy


Operate time, start non-directional at 0 Min. = 5 ms -
to 10 x Iset Max. = 20 ms
Reset time, start non-directional at 10 x Min. = 20 ms -
Iset to 0 Max. = 35 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Operate frequency, directional 38-83 Hz -
overcurrent
Operate frequency, non-directional 10-90 Hz -
overcurrent

7.3 Instantaneous residual overcurrent protection EFPIOC IP14508-1 v3

7.3.1 Identification
M14887-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous residual overcurrent EFPIOC 50N
protection
IN>>

IEF V1 EN-US

7.3.2 Functionality M12701-3 v16

The Instantaneous residual overcurrent protection (EFPIOC) has a low transient overreach and short
tripping times to allow use for instantaneous earth-fault protection, with the reach limited to less than
typical eighty percent of the transformer impedance at minimum source impedance. EFPIOC can be
configured to measure the residual current from the three-phase current inputs or the current from a
separate current input.

7.3.3 Function block M12614-3 v6

EFPIOC
I3P* TRIP
BLOCK
BLKAR
ENMULT

IEC06000269-3-en.vsdx
IEC06000269 V3 EN-US

Figure 65: EFPIOC function block

7.3.4 Signals IP11448-1 v2

Transformer protection RET650 145


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

PID-6915-INPUTSIGNALS v4

Table 76: EFPIOC Input signals

Name Type Default Description


I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKAR BOOLEAN 0 Block input for auto reclose
ENMULT BOOLEAN 0 Enable current multiplier

PID-6915-OUTPUTSIGNALS v4

Table 77: EFPIOC Output signals

Name Type Description


TRIP BOOLEAN Trip signal

7.3.5 Settings IP11449-1 v2

PID-6915-SETTINGS v4

Table 78: EFPIOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IN>> 5 - 2500 %IB 1 200 Operate residual current level in % of
IBase

Table 79: EFPIOC Group settings (advanced)

Name Values (Range) Unit Step Default Description


IN>>Min 5 - 2500 %IB 1 5 Minimum used operate residual current
level in % of IBase, if IN>> is less than
IN>>Min then IN>> is set to IN>>Min
IN>>Max 5 - 2500 %IB 1 2500 Maximum used operate residual current
level in % of IBase, if IN>> is greater than
IN>>Max then IN>> is set to IN>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 80: EFPIOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

7.3.6 Monitored data


PID-6915-MONITOREDDATA v4

Table 81: EFPIOC Monitored data

Name Type Values (Range) Unit Description


IN REAL - A Residual current

7.3.7 Operation principle M12704-3 v8

The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of the residual current, as well as from the sample
values the equivalent RMS value is derived. This current value is fed to the Instantaneous residual

146 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

overcurrent protection (EFPIOC). In a comparator the RMS value is compared to the set operation
current value of the function (IN>>).

If the residual current is larger than the set operation current a signal from the comparator is set to
true. This signal will, without delay, activate the output signal TRIP.

There is also a possibility to activate a preset change of the set operation current via a binary input
(enable multiplier ENMULT). In some applications the operation value needs to be changed, for
example, due to transformer inrush currents.

The operation current value IN>>, is limited to be between IN>>Max and IN>>Min. The default values
of the limits are the same as the setting limits for IN>>, and the limits can only be used for reducing
the allowed range of IN>>. This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is reasonable. If IN>> is set
outside IN>>Max and IN>>Min, the closest of the limits to IN>> is used by the function. If IN>>Max is
smaller then IN>>Min, the limits are swapped. The principle of the limitation is shown in Figure 66.

IN>>Max
MAX hi

u y
IN>>_used
IN>>

MIN lo
IN>>Min

IEC17000015-1-en.vsdx
IEC17000015 V1 EN-US

Figure 66: Logic for limitation of used operation current value

EFPIOC function can be blocked from the binary input BLOCK. The trip signals from the function can
be blocked from the binary input BLKAR, that can be activated during single pole trip and
autoreclosing sequences.

7.3.8 Technical data IP11450-1 v1

M12340-2 v10

Table 82: EFPIOC technical data

Function Range or value Accuracy


Operate current ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio -
Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Operate time at 0 to 10 x Iset Min. = 5 ms -
Max. = 15 ms
Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 35 ms
Critical impulse time -
Dynamic overreach < 5% at t = 100 ms -

Transformer protection RET650 147


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.4 Directional residual overcurrent protection, four steps


EF4PTOC IP14509-1 v8

7.4.1 Function revision history GUID-0F9199B0-3F86-45E0-AFC2-747052A20AE1 v3

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.4 The phase selection logic is added to allow phase segregated trip. The new phase
selections outputs added to this release are PHSELL1, PHSELL2 and PHSELL3. The
setting EnPhaseSel is added to enable or disable phase selection. The maximum value
changed to 2000.0 % of IBase for IMin1, IMin2, IMin3 and IMin4 settings.
E 2.2.5 The harmonic restrain function changed to freeze the definite and IDMT timers.
H 2.2.6 -
J 2.2.6 Minimum value changed to 0.01 for k1,k2,k3 and k4 settings

7.4.2 Identification
M14881-1 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional residual overcurrent EF4PTOC 4(IN>)
51N_67N
protection, four steps
4
alt
4
TEF-REVA V2 EN-US

7.4.3 Functionality M13667-3 v20

EF4PTOC has an inverse or definite time delay independent for each step.

All IEC and ANSI time-delayed characteristics are available together with an optional user-defined
characteristic.

EF4PTOC can be set to be directional or non-directional independently for each step.

IDir, UPol and IPol can be independently selected to be either zero sequence or negative sequence.

A second harmonic blocking can be set individually for each step.

The residual current can be calculated by summing the three-phase currents or taking the input from
the neutral CT.

EF4PTOC also provides very fast and reliable faulty phase identification for phase selective tripping
and subsequent reclosing during earth fault.

148 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.4.4 Function block M12619-3 v9

EF4PTOC
I3P* TRIP
I3PDIR* TRIN1
I3PPOL* TRIN2
U3P* TRIN3
BLOCK TRIN4
BLKTR TRSOTF
BLKST1 START
BLKST2 STIN1
BLKST3 STIN2
BLKST4 STIN3
BLKPHSEL STIN4
ENMULT1 STSOTF
ENMULT2 STFW
ENMULT3 STRV
ENMULT4 PHSELL1
CBPOS PHSELL2
CLOSECB PHSELL3
OPENCB 2NDHARMD

IEC06000424-6-en.vsdx
IEC06000424 V6 EN-US

Figure 67: EF4PTOC function block

7.4.5 Signals IP11453-1 v3

PID-8149-INPUTSIGNALS v1

Table 83: EF4PTOC Input signals

Name Type Default Description


I3P GROUP - Group connection for operate current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
I3PPOL GROUP - Group connection for polarizing current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
BLKPHSEL BOOLEAN 0 Block phase selection
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command

Transformer protection RET650 149


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

PID-8149-OUTPUTSIGNALS v1

Table 84: EF4PTOC Output signals

Name Type Description


TRIP BOOLEAN General trip signal
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault function
STFW BOOLEAN Start signal forward direction
STRV BOOLEAN Start signal reverse direction
PHSELL1 BOOLEAN Start of phase selection, phase L1
PHSELL2 BOOLEAN Start of phase selection, phase L2
PHSELL3 BOOLEAN Start of phase selection, phase L3
2NDHARMD BOOLEAN 2nd harmonic block signal

7.4.6 Settings IP11454-1 v2

PID-8149-SETTINGS v1

Table 85: EF4PTOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
SeqTypeIDir Zero seq - - Zero seq Choice of measurand for directional
Neg seq current
SeqTypeIPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq current
SeqTypeUPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq voltage

Table 86: EF4PTOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay Characteristic Angle (RCA)
PolMethod Voltage - - Voltage Type of polarization
Current
Dual
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization in
% of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization in
% of IBase
Table continues on next page

150 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


RNPol 0.50 - 1000.00 Ohm 0.01 5.00 Real part of source impedance used for
current polarisation
XNPol 0.50 - 3000.00 Ohm 0.01 40.00 Imaginary part of source imp. used for
current polarisation
IN>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in %
of fundamental curr
BlkParTransf Off - - Off Enable blocking at energizing of parallel
On transformers
UseStartValue IN1> - - IN4> Current level blk at parallel transf (step1,
IN2> 2, 3 or 4)
IN3>
IN4>
SOTF Off - - Off SOTF operation mode (Off/SOTF/
SOTF Undertime/SOTF&Undertime)
UnderTime
SOTF&UnderTime
ActivationSOTF Open - - Open Select signal to activate SOTF: CB-Open/
Closed -Closed/ -Close cmd
CloseCommand
StepForSOTF Step 2 - - Step 2 Select start from step 2 or 3 to start SOTF
Step 3
HarmBlkSOTF Off - - Off Enable harmonic restrain function in
On Under-time logic
tSOTF 0.000 - 60.000 s 0.001 0.200 Time delay for SOTF
t4U 0.000 - 60.000 s 0.001 1.000 Switch-onto-fault active time
ActUnderTime CB position - - CB position Select signal to activate under time (CB
CB command Pos / CB Command)
tUnderTime 0.000 - 60.000 s 0.001 0.300 Time delay for under time
EnPhaseSel Off - - Off Enable phase selection
On
DirMode1 Off - - Non-directional Directional mode of step 1 (Off, Non-dir,
Non-directional Forward, Reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN1> 1 - 2500 %IB 1 100 Residual current operate level for step 1
in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Definite time delay / additional time delay
for IDMT characteristics of step 1
Table continues on next page

Transformer protection RET650 151


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


k1 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 2000.00 %IB 1.00 100.00 Minimum operate residual current for step
1 in % of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 1
IN1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current setting
value for step 1
HarmBlock1 Off - - On Enable block of step 1 from harmonic
On restrain
DirMode2 Off - - Non-directional Directional mode of step 2 (Off, Non-dir,
Non-directional Forward, Reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN2> 1 - 2500 %IB 1 50 Residual current operate level for step 2
in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Definite time delay / additional time delay
for IDMT characteristics of step 2
k2 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 2000.00 %IB 1.00 50 Minimum operate residual current for step
2 in % of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 2
IN2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current setting
value for step 2
HarmBlock2 Off - - On Enable block of step 2 from harmonic
On restrain
DirMode3 Off - - Non-directional Directional mode of step 3 (Off, Non-dir,
Non-directional Forward, Reverse)
Forward
Reverse
Table continues on next page

152 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN3> 1 - 2500 %IB 1 33 Residual current operate level for step 3
in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Definite time delay / additional time delay
for IDMT characteristics of step 3
k3 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 2000.00 %IB 1.00 33 Minimum operate residual current for step
3 in % of IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 3
IN3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current setting
value for step 3
HarmBlock3 Off - - On Enable block of step 3 from harmonic
On restrain
DirMode4 Off - - Non-directional Directional mode of step 4 (Off, Non-dir,
Non-directional Forward, Reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN4> 1 - 2500 %IB 1 17 Residual current operate level for step 4
in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Definite time delay / additional time delay
for IDMT characteristics of step 4
k4 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
Table continues on next page

Transformer protection RET650 153


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


IMin4 1.00 - 2000.00 %IB 1.00 17 Minimum operate residual current for step
4 in % of IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 4
IN4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current setting
value for step 4
HarmBlock4 Off - - On Enable block of step 4 from harmonic
On restrain

Table 87: EF4PTOC Group settings (advanced)

Name Values (Range) Unit Step Default Description


IN1>Max 1 - 2500 %IB 1 2500 Maximum used operate residual current
level for step 1 in % of IBase, if IN1> is
greater than IN1>Max then IN1> is set to
IN1>Max
IN1>Min 1 - 2500 %IB 1 1 Minimum used operate residual current
level for step 1 in % of IBase, if IN1> is
less than IN1>Min then IN1> is set to
IN1>Min
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 1
IN2>Max 1 - 2500 %IB 1 2500 Maximum used operate residual current
level for step 2 in % of IBase, if IN2> is
greater than IN2>Max then IN2> is set to
IN2>Max
IN2>Min 1 - 2500 %IB 1 1 Minimum used operate residual current
level for step 2 in % of IBase, if IN2> is
less than IN2>Min then IN2> is set to
IN2>Min
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 2
Table continues on next page

154 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 2
IN3>Max 1 - 2500 %IB 1 2500 Maximum used operate residual current
level for step 3 in % of IBase, if IN3> is
greater than IN3>Max then IN3> is set to
IN3>Max
IN3>Min 1 - 2500 %IB 1 1 Minimum used operate residual current
level for step 3 in % of IBase, if IN3> is
less than IN3>Min then IN3> is set to
IN3>Min
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 3
IN4>Max 1 - 2500 %IB 1 2500 Maximum used operate residual current
level for step 4 in % of IBase, if IN4> is
greater than IN4>Max then IN4> is set to
IN4>Max
IN4>Min 1 - 2500 %IB 1 1 Minimum used operate residual current
level for step 4 in % of IBase, if IN4> is
less than IN4>Min then IN4> is set to
IN4>Min
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 4
Table continues on next page

Transformer protection RET650 155


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 4

7.4.7 Monitored data


PID-8149-MONITOREDDATA v1

Table 88: EF4PTOC Monitored data

Name Type Values (Range) Unit Description


IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
IPol REAL - A Polarizing current level
UPOLIANG REAL - deg Polarizing angle between voltage and
current
IPOLIANG REAL - deg Polarizing current angle

7.4.8 Operation principle IP12992-1 v2

M13941-51 v8
This function has the following four analog inputs on its function block in the configuration tool:

1. I3P, input used for the operating quantity. Supplies the zero-sequence magnitude measuring
functionality.
2. U3P, input used for the voltage polarizing quantity. Supplies either the zero or the negative
sequence voltage to the directional functionality
3. I3P and U3P also supply current and voltage samples for faulty phase selection functionality.
4. I3PPOL, input used for the current polarizing quantity. Provides polarizing current to the
directional functionality. This current is normally taken from the grounding of a power
transformer.
5. I3PDIR, input used for directional detection. Supplies either the zero or the negative sequence
current to the directional functionality.

These inputs are connected from the corresponding pre-processing function blocks in the
configuration tool in PCM600.

7.4.8.1 Operating quantity within the function M13941-58 v10

The function always uses residual current (3I0) for its operating quantity. The residual current can be:

1. Directly measured (when a dedicated CT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block connected to EF4PTOC function input I3P). This
dedicated IED CT input can be, for example, connected to:
• Parallel connection of current instrument transformers in all three phases (Holm-Green
connection).
• One single core balance current instrument transformer (cable CT).
• One single current instrument transformer located between power system star point and
earth (current transformer located in the star point of a star connected transformer
winding).
• One single current instrument transformer located between two parts of a protected object
(current transformer located between two star points of double star shunt capacitor bank).
2. Calculated from three-phase current input within the IED (when the fourth analog input of the
pre-processing block, connected to EF4PTOC function Analog Input I3P, is not connected to a

156 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

dedicated CT input of the IED in PCM600). In such a case, the pre-processing block will
calculate 3I0 from the first three inputs into the pre-processing block by using the following
formula (will take 3I0 from SMAI AI3P and will be connected to I3PDIR and I3P inputs.

If the zero sequence current is selected,

Iop = 3I0 = IL1 + IL2 + IL3


EQUATION1874 V2 EN-US (Equation 37)

where:
IL1, IL2, and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the fundamental
frequency component of the residual current is derived. The phasor magnitude is used within the
EF4PTOC protection to compare it with the set operation current value of the four steps (IN1>, IN2>,
IN3>, or IN4>).

If the residual current is larger than the set operation current and the step is used in non-directional
mode a signal from the comparator for this step is set to true. This signal will, without delay, activate
the output signal STINx (x=step 1-4) for this step and a common START signal.

7.4.8.2 Internal polarizing M13941-82 v12

A polarizing quantity is used within the protection in order to determine the direction to the earth fault
(forward/reverse).

The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected, the protection will use the residual voltage -3U0 as the polarizing
quantity U3P.

This voltage can be:

1. Directly measured (when a dedicated VT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block connected to EF4PTOC function input U3P). This
dedicated IED VT input shall be then connected to the open delta winding of a three-phase main
VT.
2. Calculated from three-phase voltage input within the IED (when the fourth analog input of the
pre-processing block, connected to EF4PTOC analog function input U3P, is NOT connected to a
dedicated VT input of the IED in PCM600). In such a case, the pre-processing block will
calculate -3U0 from the first three inputs into the pre-processing block by using the following
formula:

UPol = -3U 0 = -(UL1 + UL2 + UL3)


EQUATION1875 V2 EN-US (Equation 39)

where:

UL1, UL2, and UL3 are fundamental frequency phasors of three individual phase voltages.

In order to use this, all three phase-to-earth voltages must be connected to three IED VT
inputs.

The residual voltage is pre-processed by a discrete Fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.

Transformer protection RET650 157


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

This phasor is used together with the phasor of the operating directional current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable voltage polarizing the
magnitude of polarizing voltage shall be bigger than a minimum level defined by setting parameter
UPolMin.

It shall be noted that residual voltage (-3U0) or negative sequence voltage (-3U2) is used to
determine the location of the earth fault. This ensures the required inversion of the polarizing voltage
within the earth-fault function.

Current polarizing
When current polarizing is selected, the function will use an external residual current (3I0) as the
polarizing quantity IPol. This current can be:

1. Directly measured (when a dedicated CT input of the IED is connected in PCM600 to the fourth
analog input of the pre-processing block, connected to EF4PTOC function input I3PPOL). This
dedicated IED CT input is then typically connected to one single current transformer located
between power system star point and earth (current transformer located in the star point of a
star connected transformer winding).
• For some special line protection applications, this dedicated IED CT input can be
connected to a parallel connection of current transformers in all three phases (Holm-
Green connection).
2. Calculated from three phase current input within the IED (when the fourth analog input into the
pre-processing block, connected to EF4PTOC function analog input I3PPOL, is NOT connected
to a dedicated CT input of the IED in PCM600). In such case, the pre-processing block will
calculate 3I0 from the first three inputs into the pre-processing block by using the following
formula:

IPol = 3I0 = IL1 + IL2 + IL3


EQUATION2018 V2 EN-US (Equation 41)

where:
IL1, IL2, and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete fourier filter. Thus the phasor of the fundamental
frequency component of the polarizing current is derived. This phasor is then multiplied with the pre-
set equivalent zero-sequence source impedance in order to calculate the equivalent polarizing
voltage UIPol in accordance with the following formula:

UIPol = Z 0s × IPol = (RNPol + j × XNPol) × IPol


EQUATION1877 V2 EN-US (Equation 42)

which will be then used, together with the phasor of the operating current, in order to determine the
direction to the earth fault (forward/reverse).

In order to enable current polarizing, the magnitude of the polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.

Dual polarizing
When dual polarizing is selected, the function will use the vectorial sum of the voltage based and
current based polarizing in accordance with the following formula:

UTotPol=UPol  UIPol=UPol  Z 0s  IPol  UPol   RNPol  jXNPol   Ipol


IECEQUATION2408 V2 EN-US (Equation 43)

UPol and IPol can be either zero sequence component or negative sequence component depending
upon the user selection.

158 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Then the phasor of the total polarizing voltage UTotPol will be used, together with the phasor of the
operating current, to determine the direction of the earth fault (forward/reverse).

7.4.8.3 External polarizing for earth-fault function M13941-144 v6

The individual steps within the protection can be set as non-directional. When this setting is selected,
it is possible via the function binary input BLKSTx to provide external directional control (that is,
torque control) by, for example, using one of the following functions if available in the IED:

1. Distance protection directional function.


2. Negative sequence polarized general current and voltage multi purpose protection function.

7.4.8.4 Directional detection for earth fault function GUID-FC382DD3-E2C8-455E-8CD5-1DE1793DD178 v6

Zero sequence components will be used for detecting directionality for the earth fault function. In
some cases, zero sequence quantities might detect directionality incorrectly. In such a scenario,
negative sequence quantities will be used. The user can select either zero sequence components or
negative sequence components for detecting directionality with the parameter SeqTypeIPol. I3PDIR
input is always connected to the same source as I3P input.

7.4.8.5 Base quantities within the protection M13941-152 v6

The base quantities are entered as global settings for all functions in the IED. Base current (IBase)
shall be entered as rated phase current of the protected object in primary amperes. Base voltage
(UBase) shall be entered as rated phase-to-phase voltage of the protected object in primary kV.

7.4.8.6 Internal earth-fault protection structure M13941-157 v5

The protection is internally divided into the following parts:

1. Four residual overcurrent steps.


2. Directional supervision element for residual overcurrent steps with integrated directional
comparison step for communication based earth-fault protection schemes (permissive or
blocking).
3. Second harmonic blocking element with additional feature for sealed-in blocking during
switching of parallel transformers.
4. Switch on to fault feature with integrated Under-Time logic for detection of breaker problems
during breaker opening or closing sequence.

7.4.8.7 Four residual overcurrent steps M13941-166 v9

Each overcurrent step uses operating quantity Iop (residual current) as the measuring quantity. Each
of the four residual overcurrent steps has the following built-in facilities:

• Directional mode can be set to Off/Non-directional/Forward/Reverse. By this parameter setting


the directional mode of the step is selected.
• Residual current start value.
• Type of operating characteristic (inverse or definite time). By this parameter setting it is possible
to select inverse or definite time delay for the earth-fault protection. Most of the standard IEC
and ANSI inverse characteristics are available. For the complete list of available inverse curves,
please refer to section "Inverse characteristics".
• Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this parameter setting
it is possible to select the reset characteristic of the step. For the complete list of available reset
curves, please refer to section "Inverse characteristics".
• Time delay related settings. By these parameter settings the properties like definite time delay,
minimum operating time for inverse curves, reset time delay and parameters to define user
programmable inverse curve are defined.

Transformer protection RET650 159


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

• Supervision by second harmonic blocking feature (On/Off). By this parameter setting it is


possible to prevent operation of the step if the second harmonic content in the residual current
exceeds the preset level.
• Multiplier for scaling of the set residual current pickup value by external binary signal. By this
parameter setting it is possible to increase residual current pickup value when function binary
input ENMULTx has logical value 1.
• The operation current value INx>, is limited to be between INx>Max and INx>Min. The default
values of the limits are the same as the setting limits for INx>, and the limits can only be used for
reducing the allowed range of INx>. This feature is used when remote setting of the operation
current value is allowed, making it possible to ensure that the operation value used is
reasonable. If INx> is set outside INx>Max and INx>Min, the closest of the limits to INx> is used
by the function. If INx>Max is smaller then INx>Min, the limits are swapped. The principle of the
limitation is shown in Figure 68.

INx>Max
MAX hi

INx>_used
INx> u y

MIN lo
INx>Min

IEC17000017-2-en.vsdx
IEC17000017 V2 EN-US

Figure 68: Logic for limitation of used operation current value

Simplified logic diagram for one residual overcurrent step is shown in Figure 69.

160 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

HarmBlockx = Enabled
Freeze Timers
AND
2ndH_FreezeTimers_int

EMULTX

IMinx Characteristx=DefTime
X T b tx
F a>b
a t
TRINx
AND AND
|IOP|
a OR
a>b
b

STINx
INxMult AND
X T
F
Inverse
INx>
AND

AND
Characteristx=Inverse

txmin
DirModex=Off t

OR STEPx_DIR_Int

DirModex=Non-directional

DirModex=Forward AND OR
FORWARD_Int
DirModex=Reverse
AND
REVERSE_Int

IEC10000008-7-en.vsdx

IEC10000008 V7 EN-US

Figure 69: Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output signals for respective
step, and STINx and TRINx, can be blocked from the binary input BLKSTx. The trip signals from the
function can be blocked from the binary input BLKTR.

7.4.8.8 Directional supervision element with integrated directional comparison


function M13941-179 v11

At least one of the four residual overcurrent steps shall be set as directional in order to
enable execution of the directional supervision element and the integrated directional
comparison function.

The protection has an integrated directional feature. As the operating quantity current Iop is always
used, the polarizing method is determined by the parameter setting polMethod. The polarizing
quantity will be selected by the function in one of the following three ways:

1. When polMethod = Voltage, UPol will be used as polarizing quantity.


2. When polMethod = Current, IPol will be used as polarizing quantity.
3. When polMethod = Dual, UPol + IPol · ZNPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element, as shown in
Figure 70, in order to determine the direction of the earth fault.

Transformer protection RET650 161


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Operating area

STRV
0.6 * IN>DIR
Characteristic for reverse
release of measuring steps
-RCA -85 deg
Characteristic
for STRV 40% of
IN>DIR RCA +85 deg

RCA
65° Upol = -3U 0

-RCA +85 deg

RCA -85 deg


Characteristic for forward
release of measuring steps
IN>DIR

STFW

I op = 3I0

Operating area
Characteristic
for STFW IEC11000243-1-en.ai
IEC11000243 V1 EN-US

Figure 70: Operating characteristic for earth-fault directional element using the zero
sequence components
The relevant setting parameters for the directional supervision element are:

• The directional element will be internally enabled to operate as soon as Iop is bigger than 40%
of IN>Dir and the directional condition is fulfilled in the set direction.
• The relay characteristic angle AngleRCA, which defines the position of forward and reverse
areas in the operating characteristic.

The directional comparison will set the output binary signals:

1. STFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than setting
parameter IN>Dir and directional supervision element detects fault in forward direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than 60% of
setting parameter IN>Dir and directional supervision element detects fault in reverse direction.

These signals shall be used for communication based earth-fault teleprotection communication
schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional comparison
step is shown in Figure 71:

162 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

| IopDir |
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b STFW
IN>Dir b AND
FORWARD_Int

X
0.4

FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR
UPolMin

Characteristic
Directional
polMethod=Dual IPolMin
UPol T
I3PDIR
0.0 F
polMethod=Current
OR
UTotPol
IPol AND REVERSE_Int
T RVS
F

UIPol
RNPol STAGE1_DIR_Int
X T
Complex 0.0 STAGE2_DIR_Int
Number 0.0 F OR
XNPol STAGE3_DIR_Int
STAGE4_DIR_Int

BLOCK AND

IEC07000067-7-en.vsdx

IEC07000067 V7 EN-US

Figure 71: Simplified logic diagram for directional supervision element with integrated directional comparison
step

7.4.8.9 Second harmonic blocking element M13941-200 v11

A harmonic restrain can be chosen for each step by a parameter setting HarmBlockx. If the ratio of
the 2nd harmonic component in relation to the fundamental frequency component in the residual
current exceeds the preset level (defined by parameter 2ndHarmStab), output signal 2NDHARMD is
set to logical value one and the harmonic restraining feature to the function block will be applicable.

Blocking from the 2nd harmonic element activates if all of three criteria are satisfied:

1. The fundamental frequency component of the current > 7% of IBase


2. The second harmonic component > 7% of IBase
3. The ratio of the 2nd harmonic component in relation to the fundamental frequency component in
the residual current exceeds the preset level defined by the parameter 2ndHarmStab setting

In addition to the basic functionality explained above, the 2nd harmonic blocking can be set in such
way to seal-in until residual current disappears. This feature might be required to stabilize EF4PTOC
during switching of parallel transformers in the station. In case of parallel transformers there is a risk
of sympathetic inrush current. If one of the transformers is in operation, and the parallel transformer
is switched in, the asymmetric inrush current of the switched-in transformer will cause partial
saturation of the transformer already in service. This is called transferred saturation. The 2nd
harmonic of the inrush currents of the two transformers is in phase opposition. The summation of the
two currents thus gives a small 2nd harmonic current. The residual fundamental current is however
significant. The inrush current of the transformer in service before the parallel transformer energizing,

Transformer protection RET650 163


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

is a little delayed compared to the first transformer. Therefore, we have high 2nd harmonic current
component initially. After a short period this current is however small and the normal 2nd harmonic
blocking resets. If the BlkParTransf function is activated, the 2nd harmonic restrain signal is latched
as long as the residual current measured by the relay is larger than a selected step current level by
using setting UseStartValue.

This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-in feature is
activated when all of the following three conditions are simultaneously fulfilled:

1. Feature is enabled by entering setting parameter BlkParTransf = On.


2. Basic 2nd harmonic restraint feature has been active for at least 70ms.
3. Residual current magnitude is higher than the set start value for one of the four residual
overcurrent stages. By a parameter setting UseStartValue it is possible to select which one of
the four start values that will be used (IN1> or IN2> or IN3> or IN4>).

Once Block for Parallel Transformers is activated, the basic 2nd harmonic blocking signal is sealed-in
until the residual current magnitude falls below a value defined by parameter setting UseStartValue
(see condition 3 above).

Simplified logic diagram for 2nd harmonic blocking feature is shown in Figure 72.

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

Extract
fundamental
current component
X
2ndHarmStab

q-1

0-70ms OR 2ndH_FreezeTimers_int
AND OR
0

BlkParTransf=On
|IOP|
a
a>b
b
Use_PUValue
Pickup1>
Pickup2>
Pickup3>
Pickup4>

ANSI13000015-2-en.vsdx

ANSI13000015 V2 EN-US

Figure 72: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature

164 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

When enabled, the 2nd harmonic blocking function is used to freeze the Definite and/or
the Inverse Characteristics internal timers. When the function detects a 2nd harmonic
higher than the set threshold, the internal function timers are frozen but START outputs
continues to be active as long as the measured current is above the set pickup level.
Internal timers will again resume timing when harmonic content becomes smaller than the
set threshold and the measured current is higher than the pickup value. If TRIP output is
already active when harmonic blocking signal appears the TRIP output will not be
affected.

7.4.8.10 Switch on to fault feature M13941-211 v5

Integrated in the four step residual overcurrent protection are the switch on to fault logic (SOTF) and
the under-time logic. The setting parameter SOTF is set to activate SOTF, the under-time logic or
both. When the circuit breaker is closing there is a risk to close it onto a permanent fault, for example
during an autoreclosing sequence. The SOTF logic will enable fast fault clearance during such
situations. The time during which SOTF and under-time logics will be active after activation is defined
by the setting parameter t4U.

The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected by setting
parameter StepForSOTF. The setting parameter ActivationSOTF can be set for activation of CB
position open change, CB position closed change or CB close command. In case of a residual
current start from step 2 or 3 (dependent on setting) the function will give a trip after a set delay
tSOTF. This delay is normally set to a short time (default 200 ms).

The under-time logic acts as a circuit breaker pole-discordance protection, but it is only active
immediately after breaker switching. The under-time logic can only be used in solidly or low
impedance grounded systems.

The under-time logic always uses the start signal from the step 4. The under-time logic will normally
be set to operate for a lower current level than the SOTF function. The under-time logic can also be
blocked by the 2nd harmonic restraint feature. This enables high sensitivity even if power transformer
inrush currents can occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The under-time logic is activated either from
change in circuit breaker position or from circuit breaker close and open command pulses. This
selection is done by setting parameter ActUnderTime. In case of a start from step 4 this logic will give
a trip after a set delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms).

Transformer protection RET650 165


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

SOTF

200 ms
Open
t
t4U
200 ms
Closed
t ActivationSOTF

Close command
tSOTF
AND t
AND
STIN2

StepForSOTF
STIN3

SOTF
BLOCK
OFF
SOTF
UNDERTIME
UnderTime TRIP

tUnderTime
SOTF or
AND
2nd Harmonic HarmResSOFT t UnderTime

OR

Open

Close OR

t4U

ActUnderTime
Close command AND

STIN4

IEC06000643-7-en.vsdx

IEC06000643 V7 EN-US

Figure 73: Simplified logic diagram for SOTF and under-time features
M13941-3 v6
Simplified logic diagram for the complete EF4PTOC function is shown in Figure 74:

signal to communication scheme


Directional Check
Element

4 step over current


INPol Direction
operatingCurrent element
Element
3U0 One element for each
earthFaultDirection step
3I0
angleValid
I3PDIR
DirMode
enableDir

harmRestrBlock
3I0 Harmonic
Restraint 1
Element TRIP


start step 2, 3 and 4

Blocking at parallel
transformers
SwitchOnToFault
TRSOTF

CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4

DirectionalMode1-4

IEC06000376-4-en.vsdx
IEC06000376 V4 EN-US

Figure 74: Functional overview of EF4PTOC

166 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.4.8.11 Phase selection element GUID-81F5DC32-C8AF-4EF4-BEF6-8335A9197617 v1

The phase selection element provides very fast and reliable faulty phase identification for phase
selective tripping and subsequent reclosing during earth faults. The operation of the phase selection
element is based on both voltage phasor comparison and current change criteria. This measuring
principle successfully distinguishes the faulty phase with minimum influence from load current or
other disturbances, such as power swing. The phase selection feature can be enabled by setting
EnPhaseSel.

The faulty phases are primarily identified by a delta current criteria. Per-phase and phase-to-phase
delta currents are calculated and compared with different criteria to determine if there is a single
phase or phase-to-phase to earth fault. In case the fault cannot be identified by the delta current
criteria, a voltage phasor based method will be applied by comparing the angle between the voltage
phasor and the zero sequence current. The voltage phasor based method is applicable for forward
direction single phase to ground faults. If a three phase disturbance has been identified (for example,
during power swing), the voltage based method will be temporarily disabled until the disturbance
disappears.

The operation of the phase selection element is controlled by the measured zero sequence current.
When the measured zero sequence current is above the operate level (60% of IN>Dir), phase
selection is released. Once the faulty phase is selected, the selected phase will be latched until the
zero sequence current drops below the operate level.

Outputs PHSELL1, PHSELL2, and PHSELL3 are used to indicate the selected faulty phases. The
outputs are released when general START from EF4 function is TRUE.

The phase selection element will be blocked by the external input BLKPHSEL or when the circuit
breaker position is open. The CBPOS input will be high when the circuit breaker is closed and it will
be low when the circuit breaker is open. The CBPOS input provides the CB position to phase
selection element.

I3P Phase selection by


delta current AND S Q
SR AND
R
3I0 a
a>b
0.6* IN>Dir
b PHSELLx
OR
CBPOS

tON = 20ms
Phase selection by
U3P voltage and zero
AND 1s AND
sequence current
phasor

No 3 Phase Disturbance

STFW

IEC20000563-2-en.vsdx

IEC20000563 V2 EN-US

Figure 75: Simplified logic diagram for Phase selection

Transformer protection RET650 167


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.4.9 Technical data IP11455-1 v2

M15223-1 v19

Table 89: EF4PTOC technical data

Function Range or value Accuracy


Operate current, step 1-4 (1-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio > 95% at (10-2500)% of IBase -
Relay characteristic angle (-180 to 180) degrees ±2.0 degrees
(RCA)
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms
1-4 whichever is greater
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms
step 1-4 whichever is greater
Definite Reset Time 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±40 ms
2.0 x Iset to (0 - 0.8) x Iset whichever is greater
Operate time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±10.0% or ±40 ms
0.0 x Iset to (2.0 - 20.0) x Iset whichever is greater
Reset time for Iset = 1% (ANSI) 0.01 ≤ k ≤ 15.00, ±12.0% or ±160 ms
2.0 x Iset to (0 - 0.4) x Iset whichever is greater.
Operate time for Iset = 1% (IEC) 0.01 ≤ k ≤ 15.00, ±8.0% or ±100 ms
0.0 x Iset to (2.0 - 20.0) x Iset whichever is greater
Reset time for Iset = 1% (IEC) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms
2.0 x Iset to (0 - 0.4) x Iset whichever is greater
Operate time for Iset = 1% (RI&RD) 0.01 ≤ k ≤ 15.00, ±2.0% or ±40 ms
0.0 x Iset to (2.0 - 20.0) x Iset whichever is greater
Reset time for Iset = 1% (RI&RD) 0.000 ≤ tReset ≤ 60.000, ±0.2% or ±50 ms
2.0 x Iset to (0 - 0.4) x Iset whichever is greater
Inverse time characteristics, see Table 751, 16 curve types See Table 751,
Table 752 and Table 753 Table 752 and Table
753
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir
Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur
Minimum polarizing current (2-100)% of IBase ±1.0% of Ir
Real part of source Z used for current (0.50-1000.00) W/phase -
polarization
Imaginary part of source Z used for current (0.50–3000.00) W/phase -
polarization
*Operate time, start non-directional at 0 to 2 x Min. = 15 ms -
Iset Max. = 30 ms
*Reset time, start non-directional at 2 x Iset to Min. = 15 ms -
0 Max. = 30 ms
*Operate time, start non-directional at 0 to 10 Min. = 5 ms -
x Iset Max. = 20 ms
*Reset time, start non-directional at 10 x Iset Min. = 20 ms -
to 0 Max. = 35 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.

168 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.5 Four step directional negative phase sequence


overcurrent protection NS4PTOC GUID-E8CF8AA2-AF54-4FD1-A379-3E55DCA2FA3A v1

7.5.1 Function revision history GUID-FEAFB742-D0DA-4F9E-B4AC-84E568301282 v3

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.4 Maximum value changed to 2000.0 % of IBase for IMin1, IMin2, IMin3 and IMin4 settings.

E 2.2.5 -
H 2.2.6 -
J 2.2.6 Minimum value changed to 0.01 for k1,k2,k3 and k4 settings

7.5.2 Identification
GUID-E1720ADA-7F80-4F2C-82A1-EF2C9EF6A4B4 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Four step negative sequence NS4PTOC 46I2
overcurrent protection
I2

alt

IEC10000053 V2 EN-US

7.5.3 Functionality GUID-485E9D36-0032-4559-9204-101539A32F47 v6

Four step directional negative phase sequence overcurrent protection (NS4PTOC) has an inverse or
definite time delay independent for each step separately.

All IEC and ANSI time delayed characteristics are available together with an optional user defined
characteristic.

The directional function is voltage polarized.

NS4PTOC can be set directional or non-directional independently for each of the steps.

Transformer protection RET650 169


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.5.4 Function block GUID-8EDB8B12-0D86-4F6B-A1FB-F5D0C72AA545 v3

NS4PTOC (46I2)
I3P* TRIP
I3PDIR* TR1
U3P* TR2
BLOCK TR3
BLKTR TR4
BLKST1 START
BLKST2 ST1
BLKST3 ST2
BLKST4 ST3
ENMULT1 ST4
ENMULT2 STFW
ENMULT3 STRV
ENMULT4

IEC10000054 V3 EN-US

Figure 76: NS4PTOC function block

7.5.5 Signals
PID-8148-INPUTSIGNALS v1

Table 90: NS4PTOC Input signals

Name Type Default Description


I3P GROUP - Group connection for operate current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-8148-OUTPUTSIGNALS v1

Table 91: NS4PTOC Output signals

Name Type Description


TRIP BOOLEAN General trip signal
TR1 BOOLEAN Trip signal from step 1
TR2 BOOLEAN Trip signal from step 2
TR3 BOOLEAN Trip signal from step 3
TR4 BOOLEAN Trip signal from step 4
START BOOLEAN General start signal
ST1 BOOLEAN Start signal step 1
ST2 BOOLEAN Start signal step 2
Table continues on next page

170 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Type Description


ST3 BOOLEAN Start signal step 3
ST4 BOOLEAN Start signal step 4
STFW BOOLEAN Forward directional start signal
STRV BOOLEAN Reverse directional start signal

7.5.6 Settings
PID-8148-SETTINGS v1

Table 92: NS4PTOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Table 93: NS4PTOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
UPolMin 1 - 100 %UB 1 5 Minimum voltage level for polarization in
% of UBase
I2>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-1> 1 - 2500 %IB 1 100 Negative sequence current op level for
step 1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Definite time delay / additional time delay
for IDMT characteristics of step 1
k1 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 2000.00 %IB 1.00 100.00 Minimum current for step 1
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 1
Table continues on next page

Transformer protection RET650 171


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 1
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-2> 1 - 2500 %IB 1 50 Negative sequence current op level for
step 2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Definite time delay / additional time delay
for IDMT characteristics of step 2
k2 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 2000.00 %IB 1.00 50 Minimum current for step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-3> 1 - 2500 %IB 1 33 Negative sequence current op level for
step 3 in % of IBase
Table continues on next page

172 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


t3 0.000 - 60.000 s 0.001 0.800 Definite time delay / additional time delay
for IDMT characteristics of step 3
k3 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 2000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-4> 1 - 2500 %IB 1 17 Negative sequence current op level for
step 4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Definite time delay / additional time delay
for IDMT characteristics of step 4
k4 0.01 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
IMin4 1.00 - 2000.00 %IB 1.00 17 Minimum current for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 4

Table 94: NS4PTOC Group settings (advanced)

Name Values (Range) Unit Step Default Description


ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 1
Table continues on next page

Transformer protection RET650 173


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 1
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse reset
time curve for step 2
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 3
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip time
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip time
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip time
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip time
curve for step 4
Table continues on next page

174 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse reset
time curve for step 4

7.5.7 Monitored data


PID-8148-MONITOREDDATA v1

Table 95: NS4PTOC Monitored data

Name Type Values (Range) Unit Description


IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
UPOLIANG REAL - deg Polarizing angle between voltage and
current

7.5.8 Operation principle GUID-8923EC0B-A5BA-431B-9699-EB67E2637560 v3

Four step negative sequence overcurrent protection NS4PTOC function has the following three
“Analog Inputs” on its function block in the configuration tool:

1. I3P, input used for “Operating Quantity”.


2. U3P, input used for “Polarizing Quantity”.
3. I3PDIR, input used for "Directional finding"

These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.

7.5.8.1 Operating quantity within the function GUID-8F0A5BDE-AC98-4188-9085-42A8DF00C476 v3

Four step negative sequence overcurrent protection NS4PTOC function always uses negative
sequence current (I2) for its operating quantity. The negative sequence current is calculated from
three-phase current input within the IED. The pre-processing block calculates I2 from the first three
inputs into the pre-processing block by using the following formula:

1
I2 =
3
(
× IL1 + a × IL 2 + a × IL 3
2
)
EQUATION2266 V2 EN-US (Equation 44)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
a is so called operator which gives a phase shift of 120 deg, that is, a = 1∠120 deg
a2 similarly gives a phase shift of 240 deg, that is, a2 = 1∠240 deg

The phasor magnitude is used within the NS4PTOC protection to compare it with the set operation
current value of the four steps (I1>, I2>, I3> or I4>). If the negative sequence current is larger than
the set operation current and the step is used in non-directional mode a signal from the comparator
for this step is set to true. This signal, without delay, activates the output signal STx (x=1 - 4) for this
step and a common START signal.

Transformer protection RET650 175


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.5.8.2 Internal polarizing facility of the function GUID-B00FE98B-F269-4F1B-AC03-68250798851B v3

A polarizing quantity is used within the protection to determine the direction to the fault (Forward/
Reverse).

Four step negative sequence overcurrent protection NS4PTOC function uses the voltage polarizing
method.

NS4PTOC uses the negative sequence voltage -U2 as polarizing quantity U3P. This voltage is
calculated from three phase voltage input within the IED. The pre-processing block calculates -U2
from the first three inputs into the pre-processing block by using the following formula:

1
UPol = -U 2 = - × (UL1 + a 2 × UL 2 + a × UL3 )
3
EQUATION2267 V2 EN-US

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.
To use this all three phase-to-earth voltages must be connected to three IED VT inputs.

This phasor is used together with the phasor of the operating current, in order to determine the
direction to the fault (Forward/Reverse).To enable voltage polarizing the magnitude of polarizing
voltage must be bigger than a minimum level defined by setting UpolMin.

Note that –U2 is used to determine the location of the fault. This ensures the required inversion of the
polarizing voltage within the function.

7.5.8.3 External polarizing for negative sequence function GUID-21930E81-1B40-4BA4-B1D8-3B365327AEF6 v1

The individual steps within the protection can be set as non-directional. When this setting is selected
it is then possible via function binary input BLKSTx (where x indicates the relevant step within the
protection) to provide external directional control (that is, torque control) by for example using one of
the following functions if available in the IED:

• Distance protection directional function


• Negative sequence polarized general current and voltage multi purpose protection function

7.5.8.4 Internal negative sequence protection structure GUID-A6B9B3F1-A1FE-4653-A8AF-61FCCF19CE95 v1

The protection is internally divided into the following parts:

• Four negative sequence overcurrent steps


• Directional supervision element for negative sequence overcurrent steps with integrated
directional comparison step for communication based negative sequence protection schemes
(permissive or blocking)

Each part is described separately in the following sections.

176 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.5.8.5 Four negative sequence overcurrent stages GUID-D8ACB136-2BA6-4ADA-A096-5C38BD12DB72 v2

Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as measuring
quantity. Every of the four overcurrent stage has the following built-in facilities:

• Operating mode (Off/ Non-directional /Forward / Reverse). By this parameter setting the
operating mode of the stage is selected. Note that the directional decision (Forward/Reverse) is
not made within the overcurrent stage itself. The direction of the fault is determined in common
“Directional Supervision Element” described in the next paragraph.
• Negative sequence current pickup value.
• Type of operating characteristic (Inverse or Definite Time). By this parameter setting it is
possible to select Inverse or definite time delay for negative sequence overcurrent function.
Most of the standard IEC and ANSI inverse characteristics are available. For the complete list of
available inverse curves, refer to Chapter "Inverse characteristics"
• Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this parameter setting it
is possible to select the reset characteristic of the stage. For the complete list of available reset
curves, refer to Chapter "Inverse characteristics"
• Time delay related settings. By these parameter settings the properties like definite time delay,
minimum operating time for inverse curves, reset time delay and parameters to define user
programmable inverse curve are defined.
• Multiplier for scaling of the set negative sequence current pickup value by external binary signal.
By this parameter setting it is possible to increase negative sequence current pickup value when
function binary input ENMULTx has logical value 1.

Simplified logic diagram for one negative sequence overcurrent stage is shown in the following
figure:

Characteristic=DefTime tDT
AND
a TRIP
a>b OR
EnaMultiplier b

MULTVAL START
AND
X T
F
I2>
tMinIDMT
AND tIDMT

Inverse

Characteristic=Inverse

DirMode=Off OR DIR_Selected

DirMode=Non-directional
DirMode=Forward
AND OR
DIRFW
DirMode=Reverse

AND
DIRRV

IEC09000683 V4 EN-US

Figure 77: Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4
NS4PTOC can be completely blocked from the binary input BLOCK. The start signals from
NS4PTOC for each stage can be blocked from the binary input BLKSTx. The trip signals from
NS4PTOC can be blocked from the binary input BLKTR.

Transformer protection RET650 177


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.5.8.6 Directional supervision element with integrated directional comparison


function GUID-F54E21F7-7C99-41D6-BEC6-2D6EC6D2B2A3 v3

At least one of the four negative sequence overcurrent steps must be set as directional in
order to enable execution of the directional supervision element and the integrated
directional comparison function.

The operating and polarizing quantity are then used inside the directional element, as shown in figure
78, to determine the direction of the fault.

Reverse
Area

AngleRCA Upol=-U2

Forward
Area
Iop = I2

IEC10000031-1-en.vsd
IEC10000031 V1 EN-US

Figure 78: Operating characteristic for fault directional element

Two relevant setting parameters for directional supervision element are:

• Directional element is internally enable to operate as soon as Iop is bigger than 40% of I>Dir
and the directional condition is fulfilled in set direction.
• Relay characteristic angle AngleRCA which defines the position of forward and reverse areas in
the operating characteristic.

Directional comparison step, built-in within directional supervision element, set NS4PTOC output
binary signals:

1. STFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area, see fig 78
(Operating quantity magnitude is bigger than setting I>Dir)
2. STRV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse area, see fig 78.
(Operating quantity magnitude is bigger than 60% of setting I>Dir)

178 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

These signals must be used for communication based fault teleprotection communication schemes
(permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional comparison
step is shown in figure 79:

IEC07000067-4 V3 EN-US

Figure 79: Simplified logic diagram for directional supervision element with integrated directional comparison
step

7.5.9 Technical data GUID-10E9194D-3AE9-4D0F-867E-473E6F4BF443 v2

GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v8

Table 96: NS4PTOC technical data

Function Range or value Accuracy


Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Reset ratio > 95% at (10-2500)% of IBase -
Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1 - 4
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1 - 4
Inverse time characteristics, see table 751, 16 curve types See table 751, table 752 and table 753
table 752 and table 753
Minimum operate current, step 1 - 4 (1.00 - 10000.00)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Relay characteristic angle (RCA) (-180 to 180) degrees ±2.0 degrees
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur
Operate time, start non-directional at 0 to 2 Min. = 15 ms -
x Iset Max. = 30 ms

Table continues on next page

Transformer protection RET650 179


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Function Range or value Accuracy


Reset time, start non-directional at 2 x Iset Min. = 15 ms -
to 0 Max. = 30 ms
Operate time, start non-directional at 0 to Min. = 5 ms -
10 x Iset Max. = 20 ms
Reset time, start non-directional at 10 x Iset Min. = 20 ms -
to 0 Max. = 35 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -
Impulse margin time 15 ms typically -
Transient overreach <10% at τ = 100 ms -

7.6 Thermal overload protection, two time constants


TRPTTR IP14513-1 v4

7.6.1 Identification
M14877-1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Thermal overload protection, two time TRPTTR 49
constants

SYMBOL-A V1 EN-US

7.6.2 Functionality M13243-3 v12

If a power transformer reaches very high temperatures the equipment might be damaged. The
insulation within the transformer will experience forced ageing. As a consequence of this the risk of
internal phase-to-phase or phase-to-earth faults will increase.

The thermal overload protection (TRPTTR) estimates the internal heat content of the transformer
(temperature) continuously. This estimation is made by using a thermal model of the transformer with
two time constants, which is based on current measurement.

Two warning levels are available. This enables actions in the power system to be done before
dangerous temperatures are reached. If the temperature continues to increase to the trip value, the
protection initiates a trip of the protected transformer.

The estimated time to trip before operation is presented.

7.6.3 Function block M13299-3 v6

TRPTTR
I3P* TRIP
BLOCK START
COOLING ALARM1
ENMULT ALARM2
RESET LOCKOUT
WARNING

IEC06000272_2_en.vsd
IEC06000272 V2 EN-US

Figure 80: TRPTTR function block

180 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.6.4 Signals
PID-4148-INPUTSIGNALS v4

Table 97: TRPTTR Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
COOLING BOOLEAN 0 Cooling input Off / On. Changes Ib setting and time constant
ENMULT BOOLEAN 0 Enable Multiplier for currentReference setting
RESET BOOLEAN 0 Reset of function

PID-4148-OUTPUTSIGNALS v4

Table 98: TRPTTR Output signals

Name Type Description


TRIP BOOLEAN Trip Signal
START BOOLEAN Start signal
ALARM1 BOOLEAN First level alarm signal
ALARM2 BOOLEAN Second level alarm signal
LOCKOUT BOOLEAN Lockout signal
WARNING BOOLEAN Warning signal: Trip within set warning time

7.6.5 Settings
PID-6862-SETTINGS v1

Table 99: TRPTTR Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IRef 10.0 - 1000.0 % 1.0 100.0 Reference current in %
IRefMult 0.01 - 10.00 - 0.01 1.00 Multiplication Factor for reference current
IBase1 30.0 - 250.0 %IB 1.0 100.0 Base current,IBase1 without Cooling input
in % of IBase
IBase2 30.0 - 250.0 %IB 1.0 100.0 Base Current,IBase2, with Cooling input
ON in % of IBase
Tau1 0.10 - 500.00 Min 0.01 60.00 Time constant without cooling input in
min, with IBase1
Tau2 0.10 - 500.00 Min 0.01 60.00 Time constant with cooling input in min,
with IBase2
IHighTau1 30.0 - 250.0 %IB1 1.0 100.0 Current Sett, in % of IBase1 for rescaling
TC1 by TC1-IHIGH
Tau1High 5 - 2000 %tC1 1 100 Multiplier in % to TC1 when current is >
IHIGH-TC1
ILowTau1 30.0 - 250.0 %IB1 1.0 100.0 Current Set, in % of IBase1 for rescaling
TC1 by TC1-ILOW
Tau1Low 5 - 2000 %tC1 1 100 Multiplier in % to TC1 when current is <
ILOW-TC1
IHighTau2 30.0 - 250.0 %IB2 1.0 100.0 Current Set, in % of IBase2 for rescaling
TC2 by TC2-IHIGH
Tau2High 5 - 2000 %tC2 1 100 Multiplier in % to TC2 when current is
>IHIGH-TC2
Table continues on next page

Transformer protection RET650 181


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


ILowTau2 30.0 - 250.0 %IB2 1.0 100.0 Current Set, in % of IBase2 for rescaling
TC2 by TC2-ILOW
Tau2Low 5 - 2000 %tC2 1 100 Multiplier in % to TC2 when current is <
ILOW-TC2
ITrip 50.0 - 250.0 %IBx 1.0 110.0 Steady state operate current level in % of
IBasex
Alarm1 50.0 - 99.0 %Itr 1.0 80.0 First alarm level in % of heat content trip
value
Alarm2 50.0 - 99.0 %Itr 1.0 90.0 Second alarm level in % of heat content
trip value
ResLo 10.0 - 95.0 %Itr 1.0 60.0 Lockout reset level in % of heat content
trip value
ThetaInit 0.0 - 95.0 % 1.0 50.0 Initial Heat content, in % of heat content
trip value
Warning 1.0 - 500.0 Min 0.1 30.0 Time setting, below which warning would
be set (in min)
tPulse 0.01 - 0.30 s 0.01 0.10 Length of the pulse for trip signal (in sec).

Table 100: TRPTTR Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

7.6.6 Monitored data


PID-4148-MONITOREDDATA v3

Table 101: TRPTTR Monitored data

Name Type Values (Range) Unit Description


HEATCONT REAL - % Percentage of the heat content of the
transformer
I-MEASUR REAL - % Current measured by the function in % of
the rated current
TTRIP INTEGER - - Estimated time to trip (in min)
TRESLO INTEGER - - Estimated time to reset of the function (in
min)
TTRIPCAL INTEGER 0=Not Active - Calculated time status to trip: not active/
1=Long Time long time/active
2=Active
TRESCAL INTEGER 0=Not Active - Calculated time status to reset: not active/
1=Long Time long time/active
2=Active

7.6.7 Operation principle M13249-3 v8

The sampled analog phase currents are pre-processed and for each phase current the true RMS
value of each phase current is derived. These phase current values are fed to the protection function.

From the largest of the three phase currents a relative final temperature (heat content) is calculated
according to the expression:

182 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

2
æ I ö
Q final =ç ÷÷
ç I ref
è ø
EQUATION1171 V1 EN-US (Equation 45)

where:
I is the largest phase current
Iref is a given reference current

If this calculated relative temperature is larger than the relative temperature level corresponding to
the set operate (trip) current, then the start output signal START will be activated.

The actual temperature at the actual execution cycle is calculated as:

If Q final > Q n
EQUATION1172 V1 EN-US (Equation 46)

æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-

è ø
EQUATION1173 V1 EN-US (Equation 47)

If Q final < Qn
EQUATION1174 V1 EN-US (Equation 48)

Dt
Qn = Q final - ( Q final - Qn -1 ) × e
-
t

EQUATION1175 V1 EN-US (Equation 49)

where:
Qn is the calculated present temperature
Q n-1 is the calculated temperature at the previous time step
Q final is the calculated final (steady state) temperature with the actual current
Dt is the time step between calculation of the actual and final temperature
t is the thermal time constant of the protected circuit given in minutes. There are different time
constants depending on the cooling used. Please refer to manufacturer's manuals for details

The calculated transformer relative temperature can be monitored and it is exported from the function
as a real figure HEATCONT.

When the transformer temperature reaches any of the set alarm levels Alarm1 or Alarm2 the
corresponding output signal ALARM1 or ALARM2 is activated. When the temperature of the object
reaches the set trip level which corresponds to continuous current equal to ITrip the output signal
TRIP is activated.

There is also a calculation of the time to operation with the present current. This calculation is only
performed if the final temperature is calculated to be above the operation temperature:

Transformer protection RET650 183


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1176 V1 EN-US (Equation 50)

The calculated time to trip can be monitored and it is exported from the function as an integer output
TTRIP.

After a trip there can be a lockout to inhibit reconnecting the tripped circuit. The output lockout signal
LOCKOUT is activated when the temperature of the object is above the set lockout release
temperature setting ResLo.

The time to lockout release is calculated by the following cooling time calculation.

æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q - Q
è final n ø
EQUATION1177 V1 EN-US (Equation 51)

In the above equation, the final temperature is calculated according to equation 45. The calculated
component temperature can be monitored as it is exported from the function as a real figure,
TRESLO.

When the current is so high that it has given a start signal START, the estimated time to trip is
continuously calculated and given as analogue output TTRIP. If this calculated time get less than the
setting time Warning, set in minutes, the output WARNING is activated.

In case of trip a pulse with a set duration tPulse is activated.

184 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Final Temp START


> TripTemp

RESET HEATCONT
Calculation
of heat
content

I3P
Calculation
ENMULT of final
temperature
ALARM1
Actual Temp >
Alarm1,Alarm2
ALARM2
Temp

Current base used


TRIP
Actual Temp
> TripTemp

S LOCKOUT
Management of R
COOLING setting
parameters: Tau,
Actual Temp
IBase Tau used
< Recl
Temp

TTRIP
Calculation
of time to
WARNING
trip

Calculation
of time to TRESCAL
reset of
lockout

IEC05000833-2-en.vsd

IEC05000833 V2 EN-US

Figure 81: Functional overview of TRPTTR

Transformer protection RET650 185


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.6.8 Technical data IP13072-1 v1

M13266-2 v10

Table 102: TRPTTR technical data

Function Range or value Accuracy


Base current 1 and 2 (30–250)% of IBase ±1.0% of Ir
Operate time: Time constant τ = (0.10–500.00) IEC 60255-149, ±5.0% or 250 ms whichever is
minutes greater
∑ I 2 , I p2 ⌡
t < σ √ ln  2 
 I , ITrip 2 
 
EQUATION1356 V3 EN-US (Equation 52)

I = actual measured current


Ip = load current before overload
occurs
ITrip = steady state operate
current level in % of IBasex
Alarm level 1 and 2 (50–99)% of heat content operate ±2.0% of heat content trip
value
Operate current (50–250)% of IBase ±1.0% of Ir
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip

7.7 Breaker failure protection CCRBRF IP14514-1 v6

7.7.1 Function revision history GUID-3A043295-3AE3-437E-BBE9-D7FD6F349892 v3

Document Product History


revision revision
A 2.2.1 I>BlkCBPos setting functionality correction.
B 2.2.1 -
C 2.2.1 -
D 2.2.4 -
E 2.2.5 -
H 2.2.6 -

7.7.2 Identification
M14878-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker failure protection, 3-phase CCRBRF 50BF
activation and output
3I>BF

SYMBOL-U V1 EN-US

186 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.7.3 Functionality M11550-6 v20

Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding breakers in
case the own breaker fails to open. CCRBRF measurement criterion can be current based, CB
position based or an adaptive combination of these two conditions.

A current based check with extremely short reset time is used as check criterion to achieve high
security against inadvertent operation.

CB position check criteria can be used where the fault current through the breaker is small.

CCRBRF provides three different options to select how t1 and t2 timers are run:

1. By external start signals which is internally latched


2. Follow external start signal only
3. Follow external start signal and the selected FunctionMode

CCRBRF can be single- or three- phase initiated to allow its use with single phase tripping
applications. For the three-phase application of the CCRBRF the current criteria can be set to
operate only if “2 elements operates out of three phases and neutral” for example; two phases or one
phase plus the residual current start. This gives a higher security to the backup trip command.

The CCRBRF function can be programmed to give a single- or three- phase retrip to its own breaker
to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to mistakes during
testing.

7.7.4 Function block M11944-3 v9

CCRBRF
I3P* TRBU
BLOCK TRBU2
START TRRET
STL1 TRRETL1
STL2 TRRETL2
STL3 TRRETL3
CBCLDL1 CBALARM
CBCLDL2 STALARM
CBCLDL3
CBFLT

IEC18001006-1-en.vsd
IEC18001006 V1 EN-US

Figure 82: CCRBRF function block

7.7.5 Signals
PID-7233-INPUTSIGNALS v1

Table 103: CCRBRF Input signals

Name Type Default Description


I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start for breaker failure protection function
STL1 BOOLEAN 0 Start signal for phase L1
STL2 BOOLEAN 0 Start signal for phase L2
STL3 BOOLEAN 0 Start signal for phase L3
CBCLDL1 BOOLEAN 0 Circuit breaker closed in phase L1
Table continues on next page

Transformer protection RET650 187


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Type Default Description


CBCLDL2 BOOLEAN 0 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 0 Circuit breaker closed in phase L3
CBFLT BOOLEAN 0 CB faulty, unable to trip. Backup trip instantaneously

PID-7233-OUTPUTSIGNALS v1

Table 104: CCRBRF Output signals

Name Type Description


TRBU BOOLEAN Backup trip by breaker failure protection function
TRBU2 BOOLEAN Second backup trip by breaker failure protection function
TRRET BOOLEAN Retrip by breaker failure protection function
TRRETL1 BOOLEAN Retrip by breaker failure protection function phase L1
TRRETL2 BOOLEAN Retrip by breaker failure protection function phase L2
TRRETL3 BOOLEAN Retrip by breaker failure protection function phase L3
CBALARM BOOLEAN Alarm for faulty circuit breaker
STALARM BOOLEAN External start signal timed out, when by setting StartMode the
external start signal is followed (i.e. when is NOT Latched)

7.7.6 Settings
PID-7233-SETTINGS v1

Table 105: CCRBRF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Table 106: CCRBRF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
FunctionMode Current - - Current Selection of measurement principle:
CB Pos Current / CB Position / Current or CB
Current or CB Pos Position
StartMode LatchedStart - - LatchedStart Select how t1 and t2 timers are run: By
FollowStart external start signals which is internally
FollowStart&Mode latched / Follow the external start signal
only / Follow external start signal and
selected FunctionMode
tStartTimeout 0.5 - 600.0 s 0.1 1.0 Time delay after which the external start
signal will be ignored, when by setting
StartMode the external start signal is
followed (i.e. when is NOT Latched)
BuTripMode 2 out of 4 - - 1 out of 3 Select backup trip mode when t2 timer
1 out of 3 expires and current measurement is used:
1 out of 4 2 elements operate out of three phases
and neutral / 1 element operates out of
three phases / 1 element operates out of
three phases and neutral
RetripMode Off - - Off Select retrip mode when t1 timer expires:
UseFunctionMode Off / use FunctionMode to check / always
Always without any check
IPh> 5 - 200 %IB 1 10 Operate phase current level in % of IBase
IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
Table continues on next page

188 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Name Values (Range) Unit Step Default Description


t1 0.000 - 60.000 s 0.001 0.000 Time delay of retrip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip
t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip at multi-phase
start. It can be used to speed up backup
trip command for multi-phase faults on
OHLs
tPulse 0.010 - 60.000 s 0.001 0.200 Minimum trip pulse duration

Table 107: CCRBRF Group settings (advanced)

Name Values (Range) Unit Step Default Description


I>BlkCBPos 5 - 200 %IB 1 20 I> in % of IBase to block operation based
on CB Position when
FunctionMode=Current or CB Pos
t3 0.000 - 60.000 s 0.001 0.030 Additional time delay which is added to t2.
It can be used as a second backup trip
tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for alarm when faulty circuit
breaker indicated

7.7.7 Monitored data


PID-7233-MONITOREDDATA v1

Table 108: CCRBRF Monitored data

Name Type Values (Range) Unit Description


IL1 REAL - A Measured current in phase L1
IL2 REAL - A Measured current in phase L2
IL3 REAL - A Measured current in phase L3
IN REAL - A Measured residual current

7.7.8 Operation principle M16914-3 v13

Breaker failure protection CCRBRF is initiated from the protection trip command, either from
protection functions within the IED or from external protection devices.

To this function the three-phase current input and/or change to: the breaker normally open auxiliary
contact (i.e. "52a" or "closed") shall be connected. On OHL feeders where single pole auto-reclosing
is used, auxiliary contact from each CB pole shall be connected separately

The input START signal (i.e. initiate signal) can be phase selective or common (for all three phases).
Phase selective start signals enable single pole retrip functionality. This means that a second attempt
to open the same breaker can be done phase-selective. The retrip attempt is made after a set time
delay t1. For transmission lines, single pole trip and auto-reclosing is often used. The retrip function
can be phase selective if it is initiated from the phase selective line protection.

The retrip function can be done with or without current FunctionMode check. With this check, the
retrip is only performed if the circuit breaker is still seen as closed when t1 timer has elapsed.

The START signal will also start the backup trip timer. The function detects the successful breaker
opening, either by detection of low current through RMS evaluation and a special adapted current
algorithm or by monitoring the circuit breaker status using normally open auxiliary contact from the
breaker. The special algorithm enables a very fast detection of successful breaker opening, which is,
fast resetting of the current measurement. If the function has not detected breaker opening before
the backup timer has run-out its time a backup trip is initiated.

Further the following possibilities are available:

Transformer protection RET650 189


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

• Three phase (i.e. common) start/initiation via input START or individual start/initiation per phase
by using phase segregated inputs STLx.
• The minimum length of the retrip pulse, the backup trip pulse and the second backup trip pulse
are settable. This pulse duration is defined by a parameter setting tPulse. The retrip pulse, the
backup trip pulse and the second backup trip pulse will however sustain as long as there is an
indication of closed breaker.
• If the current detection is used it is possible to use three different options: 1 out of 3 where it is
sufficient to detect failure to open (high current) in one pole, 1 out of 4 where it is sufficient to
detect failure to open (high current) in one pole or high residual current and 2 out of 4 where at
least two currents (phase current and/or residual current) shall be high for breaker failure
detection.
• The current detection level for the residual current can be set different from the setting of phase
current detection.
• It is possible to have different backup time delays for single-phase faults and for multi-phase
faults.
• It is possible to have instantaneous backup trip function if the circuit breaker is incapable to clear
faults, for example, at low gas pressure. This will happen when input signal CBFLT has logical
value one and timer tCBAlarm has expired. This situation will be indicated via output signal
CBALARM.

The selection of measurement criterion is done with setting parameter FunctionMode, to determine if
the breaker has opened or not:

• Option 1 - Current: Compares the measured phase current magnitude to setting IPh> (operate
phase current level in % of IBase), and the measured residual current magnitude to setting IN>
(Operate residual current level in % of IBase). Criterion is active (i.e. breaker did not open yet) if
the measured current magnitudes are higher than the set values.

• Option 2 - CB Pos: This criterion is active (i.e. breaker did not open yet in phase Lx) if the binary
input CBCLDLx has logical value one. Thus function simply follows the status of CB pole
normally open auxiliary contact (i.e. "52a" or "closed") which shall be connected to this input.
If TRBU has been given and CBCLDLx still has value one, TRBU and TRRET will internally be
reset intentionally after approximately 10 seconds. Another way of resetting TRBU and TRRET
is either to shortly activate BLOCK input or setting CCRBRF to blocked when the IED is in
TestMode.
• Option 3 - Current or CB Pos: It uses a combination of Current or CB Pos criteria. Note that
Current criterion will be then always used, while the CB Pos criterion will be only enabled and
used if current is smaller than set value I>BlkCBPos at the moment when external START signal
has been received. It is recommended to set value for I>BlkCBPos higher than the set value for
IPh>.
If TRBU has been given and CBCLDLx still has value one and if the CB Pos criterion is
used,TRBU and TRRET will internally be reset intentionally after approximately 10 seconds.
Another way of resetting TRBU and TRRET is either to shortly activate BLOCK input or setting
CCRBRF to blocked when the IED is in TestMode.

By the setting StartMode it is possible to select how t1 and t2 timers are run and consequently how
output commands are given from the function:

• Option 1 - LatchedStart: “By external start signals which is internally latched”.


When function is once started by external START signal, the timers t1 and t2 will always elapse
and then measurement criterion defined by parameter FunctionMode will be always checked in
order to verify if the appropriate command shall be given out from the function. Timers cannot be
stopped by removing the external START signal. Function can be started again only when all of
the following three timers t1, t2 and fixed timer of 150 ms in function internal design has expired
and the measurement criterion defined by parameter FunctionMode has been deactivated, see
Figure 83.

• Option 2 - FollowStart: “Follow the external start signal only”.


The timers t1 and t2 will run while external START signal is present. If they elapse then
measurement criterion defined by parameter FunctionMode will be checked in order to verify if

190 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

the appropriate command shall be given out from the function. Timers can be always stopped by
resetting the external START signal, see Figure 84.

• Option 3- FollowStart&Mode: “Follow external start signal and selected FunctionMode”.


The timers t1 and t2 will run while external START signal is present and in the same time the
measurement criterion defined by parameter FunctionMode is active. If they elapse then the
appropriate command will be given out from the function. Timers can be stopped by resetting the
external START signal or if the measurement criterion de-activates, see Figure 85.

When one of the two “follow modes” is used, there is a settable timer tStartTimeout which will block
the external START input signal when it times-out. This will automatically also reset the t1 and t2
timers and consequently prevent any backup trip command. At the same time the STALARM output
from the function will have logical value one. To reset this signal external START signal shall be
removed. This is done in order to prevent unwanted operation of the breaker failure function for
cases where a permanent START signal is given by mistake (e.g. due to a fault in the station battery
system). Note that any backup trip command will inhibit running of tStartTimeout timer.

The BLOCK signal overrides any StartMode condition and resets START signal, running of t1 and t2
timers and all function outputs.

30ms t1 30ms
START OR TRRET
S Q t AND

t2 30ms
OR TRBU
t AND

Current Check
CB Position Check OR

150ms
AND
t
NOT

IEC18001002-1-en.vsdx

IEC18001002 V1 EN-US

Figure 83: Simplified overall logic for LatchedStart

t1
START OR TRRET
t AND

Current Check
CB Position Check OR

t2
TRBU
t AND
OR

IEC18001003-1-en.vsdx
IEC18001003 V1 EN-US

Figure 84: Simplified overall logic for FollowStart

Transformer protection RET650 191


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

START t1 TRRET
AND t

Current Check
CB Position Check OR t2 TRBU
t

IEC18001004-1-en.vsdx
IEC18001004 V1 EN-US

Figure 85: Simplified overall logic for FollowStart&Mode


The BuTripMode setting defines how many measurement elements must operate, when current
criterion is used, to determine if the CB is opened or not:

• 2 elements operate out of three phases and neutral


• 1 element operates out of three phases
• 1 element operates out of three phases and neutral

Note that it is possible to set several timers for the backup trip as described below:

1. Timer t2 is used when function is started in one phase only (i.e. for single-phase to ground fault
on an OHL (Over Head Lines) when single-pole auto-reclosing is used).
2. Timer t2MPh is used when function is started in at least two phases. This will allow to have
shorter backup trip times for a multi-phase fault on an OHL Note that for a protected object
which are always tripped three-phase (e.g. transformers, generators, reactors, cables, etc.) this
timer shall always be set to the same value as t2 timer.
3. Timer t3 can be used to give a second backup trip command. It can be used in stations having
small DC battery which is not capable to trip all surrounding breakers at once. Note that t3 timer
will only start when t2 timer expires.

The RetripMode defines how retrip feature will behave:

• Off: The retrip command to the own circuit breaker is permanently disabled.
• UseFunctionMode: Retrip command to the own circuit breaker is given only if measurement
criterion defined by setting parameter FunctionMode is still active when set timer t1 expires (e.g.
if FunctionMode=Current and current magnitude is higher than set value IPh> when t1 expires,
the retrip command will be issued).
• Always: Retrip command to the own circuit breaker is given always when set timer t1 expires
without any further checks.

The simplified logic for the function is given in the following figures.

StartMode

LatchedStart

FollowStart
1 FollowStart&Mode OR

START 30ms
int startL1
STL1 OR AND S Q
BLOCK
NOT

int reset
OR R
NOT

TRBU
NOT int startAlarmL1

tStartTimeout
AND t NOT
AND AND int startAlarmL2 STALARM
From other OR
phases int startAlarmL3

IEC18001005-1-en.vsdx

IEC18001005 V1 EN-US

Figure 86: Start logic for all three Function Modes of operation

192 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

IL1
a
a>b NOT
IPh> b

FunctionMode
Current
CB Pos OR AND int reset
OR
1
Current or CB Pos 150 ms
int startL1
t
OR AND
t1
t
t2
t OR
t2MPh
t

AND

CBCLDL1
NOT

IEC18001007-1-en.vsdx

IEC18001007 V1 EN-US

Figure 87: Reset logic in latched mode

StartMode
LatchedStart
FollowStart
1 FollowStart&Mode OR AND

int retrip
currPh1Check
CB Position Check OR
AND t1 30ms
OR AND
int startL1 t OR

t1
t

BLOCK

RetripMode
Off tPulse
TRRETL1
UseFunctionMode AND OR AND
1
Always

TRRETL2 TRRET
TRRETL3
OR

tPulse
From other
AND phases

IEC18001008-2-en.vsdx

IEC18001008 V2 EN-US

Figure 88: Simplified retrip logic

StartMode
LatchedStart

1 FollowStart
FollowStart&Mode OR AND

currCheck
CB Position Check OR
backupTripL1
t2
AND t 30ms
OR AND
OR OR
int startL1

BLOCK

t2MPh tPulse TRBU


int startL2 From backupTripL2 OR AND
2 of 3 OR
int startL3 t other backupTripL3
phases

t3
t TRBU2
OR
AND
tPulse

CBFLT tCBAlarm CBALARM


t
IEC18001009-2-en.vsdx

IEC18001009 V2 EN-US

Figure 89: Simplified backup trip logic

Transformer protection RET650 193


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

When the function Start mode is set to LatchedStart and the function mode is set CB Pos, Re-trip,
and Backup trip will internally operate and latch. To reset these two signals the breaker position has
to indicate that the CB is open.

To avoid continuous lockout of Re-trip and Back up trip signals, the signals are rested internally
under the following conditions:

1. When the function blocking input is activated breaker position input (CBCLDLxx) will internally
be forced to zero in all phases (that is simulating that CB is open), which will reset Re-
trip(TRRET) and back up trip (TRBU) output signals.
2. If TRBU is active for 10 seconds, then the activated breaker position input (CBCLDLxx) will
internally be forced to zero which will reset both RETRIP and TRBU.
3. When using FunctionMode=Current/CB pos, the same behavior is applicable only when the CB
pos part is active; that is, when the measured current is below the set value I>BlkCBPos.

7.7.9 Technical data IP10269-1 v1

M12353-1 v16

Table 109: CCRBRF technical data

Function Range or value Accuracy


Operate phase current (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Reset ratio, residual current > 95% -
Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir
Reset ratio > 95% -
Operate time for current detection 10 ms typically -
Reset time for current detection 15 ms maximum -
Time delay for retrip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for backup trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for backup trip at multi-phase start at 0 (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
to 2 x Iset
Additional time delay for a second backup trip at 0 (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
to 2 x Iset
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Minimum trip pulse duration (0.010-60.000) s ±0.2% or ±5 ms whichever is greater

7.8 Overcurrent protection with binary release BRPTOC GUID-0C91A3D4-EDB4-4CE8-85AF-44901F81B702 v1

7.8.1 Function revision history GUID-23898A65-D896-479E-9122-E8D9D6CC4FEB v2

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
Table continues on next page

194 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Document Product History


revision revision
D 2.2.4 -
E 2.2.5 New function release
H 2.2.6 -

7.8.2 Identification GUID-FB950979-9387-43A7-B1D7-D5D392EA6638 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overcurrent protection with binary BRPTOC 3I> 50
release

7.8.3 Functionality GUID-17DA02BB-B0C0-4AE9-8441-DDA4082A776B v4

Overcurrent protection with binary release (BRPTOC) is a simple, non-directional three-phase


overcurrent protection function with definite time delay. A single step is available within the function.
The current pickup level and definite time delay can be set independently. It is possible to release the
function operation via a binary signal. If the binary signal is not connected, the function will
automatically operate in a continuous mode of operation. Several function instances are available.

From the measured three-phase currents, various types of measurement modes such as DFT, Peak,
and Peak-to-peak can be selected for the BRPTOC operation.

Peak and Peak-to-Peak measurement mode allow this function to be used as instantaneous over-
current protection as well. If required by application, short time delay can also be applied.

BRPTOC can be used for different line and transformer protection applications. If required, it can also
be used to supervise on-load tap-changer operation.

7.8.4 Function block GUID-391B0308-F1A5-494F-BA0F-804A3D8F3F0C v3

BRPTOC
I3P* TRIP
BLOCK START
BLKTR STL1
RELEASE STL2
STL3
IEC21000231 V2 EN-US

7.8.5 Signals
PID-7755-INPUTSIGNALS v2

Table 110: BRPTOC Input signals

Name Type Default Description


I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
RELEASE BOOLEAN 1 Release of protection

Transformer protection RET650 195


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

PID-7755-OUTPUTSIGNALS v2

Table 111: BRPTOC Output signals

Name Type Description


TRIP BOOLEAN General trip
START BOOLEAN General start
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3

7.8.6 Settings
PID-7755-SETTINGS v2

Table 112: BRPTOC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
MeasType DFT - - DFT Selection between DFT, Peak and Peak-
Peak to-peak measurements
Peak to peak

Table 113: BRPTOC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
I> 5 - 2500 %IB 1 200 Operate current level in % of IBase
tDelay 0.000 - 60.000 s 0.001 0.025 Time delay

7.8.7 Monitored data


PID-7755-MONITOREDDATA v2

Table 114: BRPTOC Monitored data

Name Type Values (Range) Unit Description


IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

7.8.8 Operation principle GUID-615ABC71-399B-425A-822A-AEDE51EDD69E v4

Using a parameter setting MeasType within the general settings for the function BRPTOC, it is
possible to select the type of the measurements such as DFT, Peak, and Peak-to-peak used for
overcurrent operation.

If the DFT option is selected, only the RMS value of the fundamental frequency component of each
phase current is derived. The influence of the DC current component and higher harmonic current
components are completely suppressed.

If the Peak-to-peak option is selected, the influence of CT saturation is almost suppressed.

The peak-to-peak measurement efficiently suppress the DC current component from the measured
phase currents. On the contrary, when Peak measurement mode is selected, it allows the DC current
component into the measurement signal for the BRPTOC function.

196 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

If the Peak/Peak-to-peak option is selected, RMS equivalent phase currents are derived and
therefore, the set value of I> is remained intact irrespective of any type of the measurement mode.

These phase current values are fed to a comparator in the overcurrent protection with binary release
function BRPTOC. In a comparator, the RMS values are compared to the set operating current value
of the function I>.

If a phase current is larger than the set operating current, comparator output signal for this phase will
be high. This signal will, in combination with the release signal (RELEASE input), activate the timer
for the TRIP signal. If the current magnitude remains high during the timer tdelay, the TRIP output
signal is activated. The function can be blocked by activation of the BLOCK input.

I3P* IL1
a
IL2 a>b
IL3 b STL1
AND

a
a>b
b STL2
AND

a
a>b
I> b STL3
AND

RELEASE START
1
BLOCK

tDelay
TRIP
t AND
BLKTR

GUID-CAC3BE85-59F2-4264-A060-CA53DF9CA3E8 V1 EN-US

Figure 90: Simplified logic diagram for overcurrent protection with binary release

7.8.9 Technical data


GUID-754FFD93-04C7-4129-B658-32F17F272211 v5

Table 115: BRPTOC technical data

Function Range or value Accuracy


Operating current (5-2500)% of IBase DFT:
± 1.0% of Ir at I ≤ Ir
± 1.0% of I at I > Ir
Peak and Peak to peak:
± 2.5% of Ir at I ≤ Ir
± 2.5% of I at I > Ir
Reset ratio > 95% at (25-2500)% of IBase -
Independent time delay at 0 to 2 x Iset (0.000-60.000) s DFT:
±0.2% or ±30 ms whichever is greater
Peak to peak:
±0.2% or ±25 ms whichever is greater
Peak:
±0.2% or ±20 ms whichever is greater
Table continues on next page

Transformer protection RET650 197


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Function Range or value Accuracy


Operate time, start at 0 to 1.2 x Iset DFT: -
Min.= 15 ms
Max. = 30 ms
Peak to peak:
Min.= 10 ms
Max. =25 ms
Peak:
Min.= 5 ms
Max. = 20 ms
Reset time, start at 1.2 x Iset to 0 < 60 ms -
Operate time, start at 0 to 2 x Iset DFT: -
Min.= 10 ms
Max. = 25 ms
Peak to peak:
Min.= 5 ms
Max. =20 ms
Peak:
Min.= 5 ms
Max. = 15 ms
Reset time, start at 2 x Iset to 0 < 60 ms -
Operate time, start at 0 to 5 x Iset DFT: -
Min.= 5 ms
Max. = 20 ms
Peak to peak:
Min.= 5 ms
Max. =15 ms
Peak:
Min.= 5 ms
Max. = 10 ms
Reset time, start at 5 x Iset to 0 < 60 ms -
Critical impulse time DFT: -
10 ms typically at 0 to 2 x Iset
Peak to peak:
5 ms typically at 0 to 2 x Iset
Peak:
1 ms typically at 0 to 2 x Iset

7.9 Pole discordance protection CCPDSC IP14516-1 v5

7.9.1 Identification
M14888-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pole discordance protection CCPDSC 52PD

PD

SYMBOL-S V1 EN-US

198 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.9.2 Functionality M13269-3 v15

An open phase can cause negative and zero sequence currents which cause thermal stress on
rotating machines and can cause unwanted operation of zero sequence or negative sequence
current functions.

Normally the own breaker is tripped to correct such a situation. If the situation persists the
surrounding breakers should be tripped to clear the unsymmetrical load situation.

The Pole discordance protection function (CCPDSC) operates based on information from auxiliary
contacts of the circuit breaker for the three phases with additional criteria from unsymmetrical phase
currents when required.

7.9.3 Function block M17149-3 v7

CCPDSC
I3P* TRIP
BLOCK START
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL

IEC13000305-1-en.vsd
IEC13000305 V1 EN-US

Figure 91: CCPDSC function block

7.9.4 Signals
PID-3525-INPUTSIGNALS v8

Table 116: CCPDSC Input signals

Name Type Default Description


I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKDBYAR BOOLEAN 0 Block of function at CB single phase auto re-closing cycle
CLOSECMD BOOLEAN 0 Close order to CB
OPENCMD BOOLEAN 0 Open order to CB
EXTPDIND BOOLEAN 0 Pole discordance signal from CB logic
POLE1OPN BOOLEAN 1 Pole one opened indication from CB
POLE1CL BOOLEAN 0 Pole one closed indication from CB
POLE2OPN BOOLEAN 1 Pole two opened indication from CB
POLE2CL BOOLEAN 0 Pole two closed indication from CB
POLE3OPN BOOLEAN 1 Pole three opened indication from CB
POLE3CL BOOLEAN 0 Pole three closed indication from CB

PID-3525-OUTPUTSIGNALS v8

Table 117: CCPDSC Output signals

Name Type Description


TRIP BOOLEAN Trip signal to CB
START BOOLEAN Trip condition TRUE, waiting for time delay

Transformer protection RET650 199


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.9.5 Settings
PID-3525-SETTINGS v8

Table 118: CCPDSC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
tTrip 0.000 - 60.000 s 0.001 0.300 Time delay between trip condition and trip
signal
ContSel Off - - Off Contact function selection
PD signal from CB
Pole pos aux cont.
CurrSel Off - - Off Current function selection
CB oper monitor
Continuous monitor
CurrUnsymLevel 0 - 100 % 1 80 Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel 0 - 100 %IB 1 10 Current magnitude for release of the
function in % of IBase

Table 119: CCPDSC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

7.9.6 Monitored data


PID-3525-MONITOREDDATA v6

Table 120: CCPDSC Monitored data

Name Type Values (Range) Unit Description


IMin REAL - A Lowest phase current
IMax REAL - A Highest phase current

7.9.7 Operation principle


M13273-3 v6
The detection of pole discordance can be made in two different ways. If the contact based function is
used an external logic can be made by connecting the auxiliary contacts of the circuit breaker so that
a pole discordance is indicated, see figure 92.

circuit breaker

Pole discordance signal from circuit breaker

en05000287.vsd

IEC05000287 V2 EN-US

Figure 92: Pole discordance external detection logic


This binary signal is connected to a binary input of the IED. The appearance of this signal will start a
timer that will give a trip signal after the set time delay.

200 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

There is also a possibility to connect all phase selective auxiliary contacts (phase contact open and
phase contact closed) to binary inputs of the IED, see figure 93.

C.B.

poleOneClosed from C.B.

poleTwoClosed from C.B.

poleThreeClosed from C.B.

+
poleOneOpened from C.B.

poleTwoOpened from C.B.

poleThreeOpened from C.B.

en05000288.vsd
IEC05000288 V1 EN-US

Figure 93: Pole discordance signals for internal logic


In this case the logic is realized within the function. If the inputs are indicating pole discordance the
trip timer is started. This timer will give a trip signal after the set delay.

Pole discordance can also be detected by means of phase selective current measurement. The
sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. From the
fundamental frequency components of each phase current the RMS value of each phase current is
derived. The smallest and the largest phase current are derived. If the smallest phase current is
lower than the setting CurrUnsymLevel times the largest phase current the settable trip timer (tTrip) is
started. The tTrip timer gives a trip signal after the set delay. The TRIP signal is a pulse 150 ms long.
The current based pole discordance function can be set to be active either continuously or only
directly in connection to breaker open or close command.

The function also has a binary input that can be configured from the autoreclosing function, so that
the pole discordance function can be blocked during sequences with a single pole open if single pole
autoreclosing is used.
M13946-3 v7
The simplified block diagram of the current and contact based Pole discordance protection function
CCPDSC is shown in figure 94.

Transformer protection RET650 201


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

BLOCK
OR
BLKDBYAR

PolPosAuxCont

AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR

PD Signal from CB
AND
EXTPDIND

CLOSECMD t+200 ms
OR
OPENCMD

AND

Unsymmetry current
detection

en05000747.vsd
IEC05000747 V1 EN-US

Figure 94: Simplified block diagram of pole discordance function CCPDSC - contact and
current based
CCPDSC is blocked if:

• The IED is in TEST mode and CCPDSC has been blocked from the local HMI
• The input signal BLOCK is high
• The input signal BLKDBYAR is high

The BLOCK signal is a general purpose blocking signal of the pole discordance protection. It can be
connected to a binary input in the IED in order to receive a block command from external devices or
can be software connected to other internal functions in the IED itself in order to receive a block
command from internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.

The BLKDBYAR signal blocks the pole discordance operation when a single phase autoreclosing
cycle is in progress. It can be connected to the output signal 1PT1 on SMBRRECfunction block. If the
autoreclosing function is an external device, then BLKDBYAR has to be connected to a binary input
in the IED and this binary input is connected to a signalization “1phase autoreclosing in progress”
from the external autoreclosing device.

If the pole discordance protection is enabled, then two different criteria can generate a trip signal
TRIP:

• Pole discordance signaling from the circuit breaker.


• Unsymmetrical current detection.

7.9.7.1 Pole discordance signaling from circuit breaker M13946-18 v4

If one or two poles of the circuit breaker have failed to open or to close the pole discordance status,
then the function input EXTPDIND is activated from the pole discordance signal derived from the
circuit breaker auxiliary contacts (one NO contact for each phase connected in parallel, and in series
with one NC contact for each phase connected in parallel) and, after a settable time interval tTrip
(0-60 s), a 150 ms trip pulse command TRIP is generated by the Polediscordance function.

202 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.9.7.2 Unsymmetrical current detection M13946-21 v4

Unsymmetrical current indicated if:

• any phase current is lower than CurrUnsymLevel of the highest current in the three phases.
• the highest phase current is greater than CurrRelLevel of IBase.

If these conditions are true, an unsymmetrical condition is detected and the internal signal INPS is
turned high. This detection is enabled to generate a trip after a set time delay tTrip if the detection
occurs in the next 200 ms after the circuit breaker has received a command to open trip or close and
if the unbalance persists. The 200 ms limitation is for avoiding unwanted operation during
unsymmetrical load conditions.

The pole discordance protection is informed that a trip or close command has been given to the
circuit breaker through the inputs CLOSECMD (for closing command information) and OPENCMD
(for opening command information). These inputs can be connected to terminal binary inputs if the
information are generated from the field (that is from auxiliary contacts of the close and open push
buttons) or may be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).

7.9.8 Technical data


M13279-1 v10

Table 121: CCPDSC technical data

Function Range or value Accuracy


Operate current (0–100)% of IBase ±1.0% of Ir
Independent time delay between trip condition (0.000-60.000) s ±0.2% or ± 30 ms whichever is
and trip signal greater

7.10 Directional underpower protection GUPPDUP SEMOD156693-1 v4

7.10.1 Identification
SEMOD158941-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional underpower protection GUPPDUP 37
P<
2
SYMBOL-LL V2 EN-US

7.10.2 Functionality SEMOD155787-4 v6

The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that it does not cover
bearing losses and ventilation losses. Then, the synchronous generator becomes a synchronous
motor and starts to take electric power from the rest of the power system. This operating state, where
individual synchronous machines operate as motors, implies no risk for the machine itself. If the
generator under consideration is very large and if it consumes lots of electric power, it may be
desirable to disconnect it to ease the task for the rest of the power system.

Transformer protection RET650 203


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the
low forward power protection is to protect the turbine and not to protect the generator itself.

Figure 95 illustrates the low forward power and reverse power protection with underpower and
overpower functions respectively. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active power from
the generator is less than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1% depending on the type of turbine.

When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN-US

Figure 95: Protection with underpower IED and overpower IED

7.10.3 Function block SEMOD172623-4 v4

GUPPDUP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000027-2-en.vsd
IEC07000027 V2 EN-US

Figure 96: GUPPDUP function block

7.10.4 Signals
PID-3709-INPUTSIGNALS v6

Table 122: GUPPDUP Input signals

Name Type Default Description


I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

204 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

PID-3709-OUTPUTSIGNALS v6

Table 123: GUPPDUP Output signals

Name Type Description


TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBase
Q REAL Reactive power in MVAr
QPERCENT REAL Reactive power in % of SBase

7.10.5 Settings
PID-3709-SETTINGS v6

Table 124: GUPPDUP Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OpMode1 Off - - UnderPower Operation mode for stage 1 Off / On
UnderPower
Power1 0.0 - 500.0 %SB 0.1 1.0 Stage 1 underpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off - - UnderPower Operation mode for stage 2 Off / On
UnderPower
Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of SBase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2

Table 125: GUPPDUP Group settings (advanced)

Name Values (Range) Unit Step Default Description


k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in %
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in %
SBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
Table continues on next page

Transformer protection RET650 205


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Name Values (Range) Unit Step Default Description


UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir

Table 126: GUPPDUP Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

7.10.6 Monitored data


PID-3709-MONITOREDDATA v5

Table 127: GUPPDUP Monitored data

Name Type Values (Range) Unit Description


P REAL - MW Active Power in MW
PPERCENT REAL - % Active power in % of SBase
Q REAL - MVAr Reactive power in MVAr
QPERCENT REAL - % Reactive power in % of SBase

7.10.7 Operation principle


SEMOD172136-4 v4
A simplified scheme showing the principle of the power protection function is shown in figure 97. The
function has two stages with individual settings.

206 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) < t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) < t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC09000018-2-en.vsd
IEC09000018 V2 EN-US

Figure 97: Simplified logic diagram of the power protection function


The function will use voltage and current phasors calculated in the pre-processing blocks. The
apparent complex power is calculated according to chosen formula as shown in table 128.

Table 128: Complex power calculation

Set value: Mode Formula used for complex power calculation


L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN-US (Equation 53)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN-US (Equation 54)
PosSeq
S = 3 × U PosSeq × I PosSeq*
EQUATION1699 V1 EN-US (Equation 55)
L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN-US (Equation 56)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN-US (Equation 57)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN-US (Equation 58)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN-US (Equation 59)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN-US (Equation 60)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN-US (Equation 61)

Transformer protection RET650 207


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

The active and reactive power is available from the function and can be used for monitoring and fault
recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this angle
is 0° the active power component P is calculated. If this angle is 90° the reactive power component Q
is calculated.

The calculated power component is compared to the power pick up setting Power1(2). For directional
underpower protection, a start signal START1(2) is activated if the calculated power component is
smaller than the pick up value. For directional overpower protection, a start signal START1(2) is
activated if the calculated power component is larger than the pick up value. After a set time delay
TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At activation of any of
the two stages a common signal START will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The absolute hysteresis of the
stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-power1(2)). For generator low forward power
protection the power setting is very low, normally down to 0.02 p.u. of rated generator power. The
hysteresis should therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) + Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would be
too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the minimal
value.

If the measured power drops under the drop-power1(2) value, the function will reset after a set time
DropDelay1(2). The reset means that the start signal will drop out and that the timer of the stage will
reset.

7.10.7.1 Low pass filtering SEMOD172136-39 v4

In order to minimize the influence of the noise signal on the measurement it is possible to introduce a
recursive, low pass filtering of the measured values for S (P, Q). This will make slower measurement
response to the step changes in the measured quantity. Filtering is performed in according to the
following recursive formula:

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 62)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
SCalculated is the new calculated value in the present execution cycle
k is settable parameter by the end user which influence the filter properties
TD

Default value for parameter k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is without any additional delay). When k is set to value bigger than 0,
the filtering is enabled. A typical value for k=0.92 in case of slow operating functions.

7.10.7.2 Calibration of analog inputs SEMOD172136-57 v3

Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100% of
rated current and voltage. The compensation below 5% and above 100% is constant and linear in
between, see example in figure 98.

208 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

IEC05000652 V2 EN-US

Figure 98: Calibration curves


The first current and voltage phase in the group signals will be used as reference and the amplitude
and angle compensation will be used for related input signals.

Analog outputs (Monitored data) from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of base power:
PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of base power:
QPERCENT.

7.10.8 Technical data SEMOD175153-1 v1

SEMOD175152-2 v11

Table 129: GUPPDUP technical data

Function Range or value Accuracy


Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr
for Step 1 and Step 2 ±1.0% of S at S > Sr
where

S r = 1.732 × U r × I r
Characteristic angle (-180.0–180.0) degrees ±2.0 degrees
for Step 1 and Step 2
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 2 x Sr to 0.5 x Sr and k=0.000

7.11 Directional overpower protection GOPPDOP SEMOD172360-1 v4

Transformer protection RET650 209


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.11.1 Identification
SEMOD176574-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional overpower protection GOPPDOP 32
P>
2
DOCUMENT172362-IMG158942
V2 EN-US

7.11.2 Functionality SEMOD172356-4 v5

The task of a generator in a power plant is to convert mechanical energy available as a torque on a
rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that it does not cover
bearing losses and ventilation losses. Then, the synchronous generator becomes a synchronous
motor and starts to take electric power from the rest of the power system. This operating state, where
individual synchronous machines operate as motors, implies no risk for the machine itself. If the
generator under consideration is very large and if it consumes lots of electric power, it may be
desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the
reverse power protection is to protect the turbine and not to protect the generator itself.

Figure 99 illustrates the low forward power and reverse power protection with underpower and
overpower functions respectively. The underpower IED gives a higher margin and should provide
better dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active power from
the generator is less than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1%.

When IED with a metering class input CTs is used pickup can be set to more sensitive value
(e.g.0,5% or even to 0,2%).

Underpower IED Overpower IED

Operate
Q Q
Operate
Line Line

Margin Margin
P P

Operating point Operating point


without without
turbine torque turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN-US

Figure 99: Reverse power protection with underpower IED and overpower IED

210 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.11.3 Function block SEMOD172667-4 v4

GOPPDOP
I3P* TRIP
U3P* TRIP1
BLOCK TRIP2
BLOCK1 START
BLOCK2 START1
START2
P
PPERCENT
Q
QPERCENT

IEC07000028-2-en.vsd
IEC07000028 V2 EN-US

Figure 100: GOPPDOP function block

7.11.4 Signals
PID-3710-INPUTSIGNALS v7

Table 130: GOPPDOP Input signals

Name Type Default Description


I3P GROUP - Current group connection
SIGNAL
U3P GROUP - Voltage group connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2

PID-3710-OUTPUTSIGNALS v7

Table 131: GOPPDOP Output signals

Name Type Description


TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active power P in MW
PPERCENT REAL Active power P in % of SBase
Q REAL Reactive power Q in MVAr
QPERCENT REAL Reactive power Q in % of SBase

Transformer protection RET650 211


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

7.11.5 Settings
PID-3710-SETTINGS v7

Table 132: GOPPDOP Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OpMode1 Off - - OverPower Operation mode for stage 1 Off / On
OverPower
Power1 0.0 - 500.0 %SB 0.1 120.0 Stage 1 overpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off - - OverPower Operation mode for stage 2 Off / On
OverPower
Power2 0.0 - 500.0 %SB 0.1 120.0 Stage 2 overpower setting in Angle2
direction in % of SBase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2

Table 133: GOPPDOP Group settings (advanced)

Name Values (Range) Unit Step Default Description


k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % of
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % of
SBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir

212 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

Table 134: GOPPDOP Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode L1, L2, L3 - - Pos Seq Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

7.11.6 Monitored data


PID-3710-MONITOREDDATA v6

Table 135: GOPPDOP Monitored data

Name Type Values (Range) Unit Description


P REAL - MW Active power P in MW
PPERCENT REAL - % Active power P in % of SBase
Q REAL - MVAr Reactive power Q in MVAr
QPERCENT REAL - % Reactive power Q in % of SBase

7.11.7 Operation principle


SEMOD172154-4 v3
A simplified scheme showing the principle of the power protection function is shown in figure 101.
The function has two stages with individual settings.

Chosen current
phasors P

Complex Derivation of S(angle)


S(angle) > t TRIP1
power S(composant)
Chosen voltage Power1
calculation in Char angle
phasors Q
START1

S(angle) > t TRIP2


Power2
START2

P = POWRE

Q = POWIM

IEC06000567-2-en.vsd
IEC06000567 V2 EN-US

Figure 101: Simplified logic diagram of the power protection function


The function will use voltage and current phasors calculated in the pre-processing blocks. The
apparent complex power is calculated according to chosen formula as shown in table 136.

Transformer protection RET650 213


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Table 136: Complex power calculation

Set value: Mode Formula used for complex power calculation


L1, L2, L3
S = U L1 × I L1* + U L 2 × I L 2* + U L 3 × I L 3*
EQUATION1697 V1 EN-US (Equation 63)
Arone
S = U L1L 2 × I L1* - U L 2 L 3 × I L 3*
EQUATION1698 V1 EN-US (Equation 64)
PosSeq
S = 3 × U PosSeq × I PosSeq*
EQUATION1699 V1 EN-US (Equation 65)
L1L2
S = U L1L 2 × ( I L1* - I L 2* )
EQUATION1700 V1 EN-US (Equation 66)
L2L3
S = U L 2 L 3 × ( I L 2* - I L 3* )
EQUATION1701 V1 EN-US (Equation 67)
L3L1
S = U L 3 L1 × ( I L 3* - I L1* )
EQUATION1702 V1 EN-US (Equation 68)
L1
S = 3 × U L1 × I L1*
EQUATION1703 V1 EN-US (Equation 69)
L2
S = 3 × U L 2 × I L 2*
EQUATION1704 V1 EN-US (Equation 70)
L3
S = 3 × U L 3 × I L 3*
EQUATION1705 V1 EN-US (Equation 71)

The active and reactive power is available from the function and can be used for monitoring and fault
recording.

The component of the complex power S = P + jQ in the direction Angle1(2) is calculated. If this angle
is 0° the active power component P is calculated. If this angle is 90° the reactive power component Q
is calculated.

The calculated power component is compared to the power pick up setting Power1(2). A start signal
START1(2) is activated if the calculated power component is larger than the pick up value. After a set
time delay TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At
activation of any of the two stages a common signal START will be activated. At trip from any of the
two stages also a common signal TRIP will be activated.

To avoid instability there is a settable hysteresis in the power function. The absolute hysteresis of the
stage1(2) is Hysteresis1(2) = abs (Power1(2) – drop-power1(2)). For generator reverse power
protection the power setting is very low, normally down to 0.02 p.u. of rated generator power. The
hysteresis should therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) – Hysteresis1(2)

For small power1 values the hysteresis1 may not be too big, because the drop-power1(2) would be
too small. In such cases, the hysteresis1 greater than (0.5 · Power1(2)) is corrected to the minimal
value.

If the measured power drops under the drop-power1(2) value the function will reset after a set time
DropDelay1(2). The reset means that the start signal will drop out ant that the timer of the stage will
reset.

214 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 7
Current protection

7.11.7.1 Low pass filtering SEMOD172154-37 v4

In order to minimize the influence of the noise signal on the measurement it is possible to introduce
the recursive, low pass filtering of the measured values for S (P, Q). This will make slower
measurement response to the step changes in the measured quantity. Filtering is performed in
accordance with the following recursive formula:

S = k × SOld + (1 - k ) × SCalculated
EQUATION1959 V1 EN-US (Equation 72)

Where
S is a new measured value to be used for the protection function
Sold is the measured value given from the function in previous execution cycle
SCalculated is the new calculated value in the present execution cycle
k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is, without any additional delay). When k is set to value bigger than 0,
the filtering is enabled. A typical value for k = 0.92 in case of slow operating functions.

7.11.7.2 Calibration of analog inputs SEMOD172154-55 v2

Measured currents and voltages used in the Power function can be calibrated to get class 0.5
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100% of
rated current and voltage. The compensation below 5% and above 100% is constant and linear in
between, see example in figure 102.

IEC05000652 V2 EN-US

Figure 102: Calibration curves


The first current and voltage phase in the group signals will be used as reference and the amplitude
and angle compensation will be used for related input signals.

Transformer protection RET650 215


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7 1MRK504170-UEN Rev. J
Current protection

Analog outputs from the function can be used for service values or in the disturbance report. The
active power is provided as MW value: P, or in percent of base power: PPERCENT. The reactive
power is provided as Mvar value: Q, or in percent of base power: QPERCENT.

7.11.8 Technical data SEMOD175160-1 v1

SEMOD175159-2 v9

Table 137: GOPPDOP technical data

Function Range or value Accuracy


Power level (0.0–500.0)% of SBase ±1.0% of Sr at S ≤ Sr
for Step 1 and Step 2 ±1.0% of S at S > Sr

Characteristic angle (-180.0–180.0) degrees ±2.0 degrees


for Step 1 and Step 2
Operate time, start at 0.5 x Sr to 2 x Sr and Min. =10 ms
k=0.000 Max. = 25 ms
Reset time, start at 2 x Sr to 0.5 x Sr and Min. = 35 ms
k=0.000 Max. = 55 ms
Independent time delay to operate for Step 1 (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
and Step 2 at 0.5 x Sr to 2 x Sr and k=0.000

216 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Section 8 Voltage protection


8.1 Two step undervoltage protection UV2PTUV IP14544-1 v3

8.1.1 Identification
M16876-1 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step undervoltage protection UV2PTUV 27

3U<

V2 EN-US
SYMBOL-R-2U-GREATER-THAN

8.1.2 Functionality M13789-3 v14

Undervoltages can occur in the power system during faults or abnormal conditions. The two-step
undervoltage protection function (UV2PTUV) can be used to open circuit breakers to prepare for
system restoration at power outages or as a long-time delayed back-up to the primary protection.

UV2PTUV has two voltage steps, each with inverse or definite time delay.

It has a high reset ratio to allow settings close to the system service voltage.

8.1.3 Function block M13794-3 v7

UV2PTUV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000276-2-en.vsd
IEC06000276 V2 EN-US

Figure 103: UV2PTUV function block

Transformer protection RET650 217


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.1.4 Signals
PID-3586-INPUTSIGNALS v7

Table 138: UV2PTUV Input signals

Name Type Default Description


U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3586-OUTPUTSIGNALS v7

Table 139: UV2PTUV Output signals

Name Type Description


TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

8.1.5 Settings
PID-3586-SETTINGS v7

Table 140: UV2PTUV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 1
Inverse curve B
Prog. inv. curve
Table continues on next page

218 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Name Values (Range) Unit Step Default Description


OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3) from step 1
3 out of 3
U1< 1.0 - 100.0 %UB 0.1 70.0 Voltage setting/start val (DT & IDMT) in %
of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
IntBlkSel1 Off - - Off Internal (low level) blocking mode, step 1
Block of trip
Block all
IntBlkStVal1 1 - 50 %UB 1 20 Voltage setting for internal blocking in %
of UBase, step 1
tBlkUV1 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level) blocking
for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 2
Inverse curve B
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3) from step 2
3 out of 3
U2< 1.0 - 100.0 %UB 0.1 50.0 Voltage setting/start val (DT & IDMT) in %
of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
IntBlkSel2 Off - - Off Internal (low level) blocking mode, step 2
Block of trip
Block all
IntBlkStVal2 1 - 50 %UB 1 20 Voltage setting for internal blocking in %
of UBase, step 2
tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level) blocking
for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 141: UV2PTUV Group settings (advanced)

Name Values (Range) Unit Step Default Description


tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 1
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
Table continues on next page

Transformer protection RET650 219


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Name Values (Range) Unit Step Default Description


CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 2
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 2

Table 142: UV2PTUV Non group settings (basic)

Name Values (Range) Unit Step Default Description


ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh RMS
PhN RMS
PhPh DFT
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

8.1.6 Monitored data


PID-3586-MONITOREDDATA v6

Table 143: UV2PTUV Monitored data

Name Type Values (Range) Unit Description


UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

8.1.7 Operation principle M15326-3 v11

Two-step undervoltage protection (UV2PTUV) is used to detect low power system voltage. If one,
two or three phase voltages decrease below the set value, a corresponding START signal is
generated. The parameters OpMode1 and OpMode2 influence the requirements to activate the
START outputs: the measured voltages 1 out of 3, 2 out of 3, or 3 out of 3 have to be lower than the
corresponding set point to issue the corresponding START signal.

220 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

UV2PTUV has two voltage-measuring steps with separate time delays. If the voltage remains below
the set value for the chosen time delay, the corresponding trip signal is issued. To avoid an unwanted
trip due to the disconnection of the related high-voltage equipment, a voltage-controlled blocking of
the function is available: if the voltage is lower than the set blocking level, the function is blocked and
no START or TRIP signal is generated. The time delay characteristic is individually chosen for each
step and can be either definite time delay or inverse time delay.

To avoid oscillations of the output START signal, a hysteresis has been included.

8.1.7.1 Measurement principle M15326-6 v7

Depending on the value of the ConnType parameter, UV2PTUV can be set to measure phase-to-
earth fundamental value, phase-to-phase fundamental value, phase-to-earth true RMS value or
phase-to-phase true RMS value, and compares it against the set values, U1< and U2<. The voltage-
related settings are made in percentage of the base voltage which is set in kV phase-to-phase
voltage. This means operation for phase-to-earth voltage under:

UBase(kV )
U (%) ·
3
EQUATION1429 V3 EN-US (Equation 73)

and operation for phase-to-phase voltage under:

U < (%) × UBase(kV)


EQUATION1990 V1 EN-US (Equation 74)

When the phase-to-earth voltage measurement is selected, the function automatically


introduces division of the base value by the square root of three.

8.1.7.2 Time delay M15326-10 v14

The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay three different modes are available:

• inverse curve A
• inverse curve B
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ Un < -U ö
ç ÷
è Un < ø
EQUATION1431 V2 EN-US (Equation 75)

where:
Un< Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

Transformer protection RET650 221


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

k × 480
t= 2.0
+ 0.055
æ Un < - U ö
ç 32 × - 0.5 ÷
è Un < ø
EQUATION1432 V2 EN-US (Equation 76)

The customer programmable curve can be created as:

é ù
ê ú
ê k×A ú
t=ê pú
+D
ê æ Un < - U ö ú
êçB × -C÷ ú
ëè Un < ø û
EQUATION1433 V2 EN-US (Equation 77)

When the denominator in the expression is equal to zero the time delay will be infinity. There will be
an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un< down to Un< · (1.0 – CrvSatn/100) the used voltage will be:
Un< · (1.0 – CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 78)

If the Programmable inverse curve is chosen for operation and Equation 78 does not
satisfy based on the set values, no TRIP signal is issued. However, START signal is set
and maintained as long as the measured quantity for operation is below the set start level
of step.

The lowest voltage is always used for the inverse time delay integration. The details of the different
inverse time characteristics are shown in section "Inverse characteristics".

Voltage

UL1
UL2
UL3

IDMT Voltage

Time

IEC12000186-1-en.vsd

IEC12000186 V1 EN-US

Figure 104: Voltage used for the inverse time characteristic integration

222 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

TRIP signal issuing requires that the undervoltage condition continues for at least the user set time
delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by some
special voltage level dependent time curves for the inverse time mode (IDMT). If the start condition,
with respect to the measured voltage, ceases during the delay time, and is not fulfilled again within a
user-defined reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 pickup
for the inverse time) the corresponding start output is reset. After leaving the hysteresis area, the
start condition must be fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. For the undervoltage function the IDMT reset time is constant and does not depend
on the voltage fluctuations during the drop-off period. However, there are three ways to reset the
timer: the timer is reset instantaneously, the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 105 and figure 106.

tIReset1
Voltage Measured
START Voltage
HystAbs1
TRIP

U1<

Time

START

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous
decreased IEC05000010-5-en.vsdx

IEC05000010 V5 EN-US

Figure 105: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

Transformer protection RET650 223


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

tIReset1
Voltage
START
START
HystAbs1 Measured Voltage
TRIP

U1<

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Instantaneous Linearly decreased
IEC05000011-en-4.vsdx

IEC05000011 V4 EN-US

Figure 106: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different
reset types
Definite timer delay

When definite time delay is selected the function will operate as shown in figure 107. Detailed
information about individual stage reset/operation behavior is shown in figure 108 and figure 109
respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed
stage is ensured.

224 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

ST1

U t1
a tReset1
TR1
t
a<b t
U1< R
b
AND

IEC09000785-3-en.vsd
IEC09000785 V3 EN-US

Figure 107: Logic diagram for step 1, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 108: Example for Definite Time Delay stage1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 109: Example for Definite Time Delay stage1 operation

Transformer protection RET650 225


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.1.7.3 Blocking M15326-20 v9

It is possible to block Two step undervoltage protection UV2PTUV partially or completely, by binary
input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the trip output of
step 1, or both the trip and the START outputs of step 1, are blocked. The characteristic of the
blocking is set by the IntBlkSel1 parameter. This internal blocking can also be set to Off resulting in
no voltage based blocking. Corresponding settings and functionality are valid also for step 2.

In case of disconnection of the high voltage component the measured voltage will get very low. The
event will START both the under voltage function and the blocking function, as seen in figure 110.
The delay of the blocking function must be set less than the time delay of under voltage function.

U Disconnection

Normal voltage

U1<

U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2

Time

Block step 1

Block step 2
en05000466.vsd
IEC05000466 V1 EN-US

Figure 110: Blocking function

226 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.1.7.4 Design M15326-35 v10

The voltage measuring elements continuously measure the three phase-to-neutral voltages or the
three phase-to-phase voltages. Recursive fourier filters or true RMS filters of input voltage signals
are used. The voltages are individually compared to the set value, and the lowest voltage is used for
the inverse time characteristic integration. A special logic is included to achieve the 1 out of 3, 2 out
of 3 and 3 out of 3 criteria to fulfill the START condition. The design of Two step undervoltage
protection UV2PTUV is schematically shown in Figure 111.

UL1 Comparator ST1L1


UL1 < U1< Voltage Phase Phase 1
Selector
OpMode1 ST1L2
UL2 Comparator Phase 2
1 out of 3
UL2 < U1< 2 out of 3 ST1L3
3 out of 3 Phase 3 Start t1
UL3 Comparator t1Reset
UL3 < U1< IntBlkStVal1 &
OR ST1
Trip
Output
START Logic TR1L1

Step 1 TR1L2
Time integrator TRIP
MinVoltSelector tIReset1
ResetTypeCrv1 TR1L3

TR1
OR

Comparator ST2L1
UL1 < U2< Voltage Phase Phase 1
Selector
OpMode2 ST2L2
Comparator Phase 2
UL2 < U2< 1 out of 3
2 out of 3 Start t2 ST2L3
3 out of 3 Phase 3 t2Reset
Comparator IntBlkStVal2 &
UL3 < U2< Trip ST2
Output OR
Logic
START TR2L1

Step 2
TR2L2
Time integrator TRIP
MinVoltSelector tIReset2
ResetTypeCrv2 TR2L3

TR2
OR
START
OR

TRIP
OR

IEC05000834-2-en.vsd
IEC05000834 V2 EN-US

Figure 111: Schematic design of Two step undervoltage protection UV2PTUV

Transformer protection RET650 227


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.1.8 Technical data IP13001-1 v1

M13290-1 v17

Table 144: UV2PTUV technical data

Function Range or value Accuracy


Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of Ur
Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur
Internal blocking level, step 1 and step 2 (1–50)% of UBase ±0.5% of Ur
Inverse time characteristics for step 1 and - See table 758
step 2, see table 758
Definite time delay, step 1 at 1.2 x Uset to (0.00-6000.00) s ±0.2% or ±40ms whichever is greater
0
Definite time delay, step 2 at 1.2 x Uset to (0.000-60.000) s ±0.2% or ±40ms whichever is greater
0
Minimum operate time, inverse (0.000–60.000) s ±0.5% or ±40ms whichever is greater
characteristics
Operate time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Operate time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Reset time, start at 0 to 1.2 x Uset Min. = 15 ms -
Max. = 35 ms
Critical impulse time 5 ms typically at 1.2 x Uset to 0 -
Impulse margin time 15 ms typically -

8.2 Two step overvoltage protection OV2PTOV IP14545-1 v3

8.2.1 Identification
M17002-1 v8

Function description IEC 61850 IEC 60617 identification ANSI/IEEE C37.2


identification device number
Two step overvoltage protection OV2PTOV 59

3U>

SYMBOL-C-2U-SMALLER-THAN V2 EN-US

8.2.2 Functionality OV2PTOV M13798-3 v17

Overvoltages may occur in the power system during abnormal conditions such as sudden power
loss, tap changer regulating failures, and open line ends on long lines.

Two step overvoltage protection (OV2PTOV) function can be used to detect open line ends, normally
then combined with a directional reactive over-power function to supervise the system voltage. When
triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks.

OV2PTOV has a high reset ratio to allow settings close to system service voltage.

228 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.2.3 Function block M13803-3 v6

OV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000277-2-en.vsd
IEC06000277 V2 EN-US

Figure 112: OV2PTOV function block

8.2.4 Signals
PID-3535-INPUTSIGNALS v7

Table 145: OV2PTOV Input signals

Name Type Default Description


U3P GROUP - Group signal for three phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3535-OUTPUTSIGNALS v7

Table 146: OV2PTOV Output signals

Name Type Description


TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
Table continues on next page

Transformer protection RET650 229


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Name Type Description


ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

8.2.5 Settings
PID-3535-SETTINGS v7

Table 147: OV2PTOV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 1
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3) from step 1
3 out of 3
U1> 1.0 - 200.0 %UB 0.1 120.0 Voltage setting/start val (DT & IDMT) in %
of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 2
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3) from step 2
3 out of 3
U2> 1.0 - 200.0 %UB 0.1 150.0 Voltage setting/start val (DT & IDMT) in %
of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

230 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Table 148: OV2PTOV Group settings (advanced)

Name Values (Range) Unit Step Default Description


tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 1
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage IDMT
curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 2
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage IDMT
curve, step 2

Table 149: OV2PTOV Non group settings (basic)

Name Values (Range) Unit Step Default Description


ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh DFT
PhN RMS
PhPh RMS
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Transformer protection RET650 231


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.2.6 Monitored data


PID-3535-MONITOREDDATA v6

Table 150: OV2PTOV Monitored data

Name Type Values (Range) Unit Description


UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

8.2.7 Operation principle M15330-3 v11

Two step overvoltage protection OV2PTOV is used to detect high power system voltage. OV2PTOV
has two steps with separate time delays. If one-, two- or three-phase voltages increase above the set
value, a corresponding START signal is issued. OV2PTOV can be set to START/TRIP, based on 1
out of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being above the set point. If the voltage
remains above the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued.

The time delay characteristic is individually chosen for the two steps, and can be either definite time
or inverse time delayed.

The voltage related settings are made in percent of the global set base voltage UBase, which is set
in kV, phase-to-phase.

OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase fundamental


value, phase-to-earth RMS value or phase-to-phase RMS value. The choice of measuring is done by
the parameter ConnType.

The setting of the analog inputs are given as primary phase-to-earth or phase-to-phase voltage.
OV2PTOV will operate if the voltage gets higher than the set percentage of the set base voltage
UBase. This means operation for phase-to-earth voltage over:

U > (%) × UBase( kV )


3
EQUATION1434 V1 EN-US (Equation 79)

and operation for phase-to-phase voltage over:

U > (%) × UBase(kV)


EQUATION1993 V1 EN-US (Equation 80)

When phase-to-earth voltage measurement is selected the function automatically


introduces division of the base value by the square root of three.

8.2.7.1 Measurement principle M15330-6 v6

All the three voltages are measured continuously, and compared with the set values, U1> for Step 1
and U2> for Step 2. The parameters OpMode1 and OpMode2 influence the requirements to activate
the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of 3 measured voltages have to be higher
than the corresponding set point to issue the corresponding START signal.

To avoid oscillations of the output START signal, a hysteresis is included.

232 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.2.7.2 Time delay M15330-10 v13

The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay four different modes are available:

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 81)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US (Equation 82)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U n > ø
IECEQUATION2425 V1 EN-US (Equation 83)

The customer programmable curve is defined by the below equation, where A, B, C, D, k and p are
settings:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 84)

When the denominator in the expression is equal to zero the time delay will be infinity. There will be
an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used voltage will be:
Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:

Transformer protection RET650 233


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 85)

If the Programmable inverse curve is chosen for operation and Equation 85 does not
satisfy based on the set values, no TRIP signal is issued. However, START signal is set
and maintained as long as the measured quantity for operation is above the set start level
of step.

The highest phase (or phase-to-phase) voltage is always used for the inverse time delay integration,
see figure 113. The details of the different inverse time characteristics are shown in section "Inverse
characteristics".

Voltage
IDMT Voltage

UL1
UL2
UL3

Time

IEC05000016-2-en.vsd
IEC05000016 V2 EN-US

Figure 113: Voltage used for the inverse time characteristic integration
Operation of the trip signal requires that the overvoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by
selected voltage level dependent time curves for the inverse time mode (IDMT). If the START
condition, with respect to the measured voltage ceases during the delay time, and is not fulfilled
again within a user defined reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2 for the inverse time) the corresponding START output is reset, after that the defined reset
time has elapsed. Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to the hysteresis area.
The hysteresis value for each step is settable HystAbsn (where n means either 1 or 2 respectively) to
allow a high and accurate reset of the function. For OV2PTOV the IDMT reset time is constant and
does not depend on the voltage fluctuations during the drop-off period. However, there are three
ways to reset the timer: either the timer is reset instantaneously, or the timer value is frozen during
the reset time, or the timer value is linearly decreased during the reset time.

234 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 114: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

Transformer protection RET650 235


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 115: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at different
reset types
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 116. Detailed
information about individual stage reset/operation behavior is shown in figure 117 and figure 118
respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2 respectively),
instantaneous reset of the definite time delayed stage is ensured.

236 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 116: Logic diagram for step 1, definite time delay, DT operation

U1>

START

TRIP

tReset1

t1

IEC10000037-2-en.vsd
IEC10000037 V2 EN-US

Figure 117: Example for step 1, Definite Time Delay stage 1 reset

U1>

START

TRIP

tReset1

t1

IEC10000038-2-en.vsd
IEC10000038 V2 EN-US

Figure 118: Example for Definite Time Delay stage 1 operation

Transformer protection RET650 237


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.2.7.3 Blocking M15330-20 v8

It is possible to block Two step overvoltage protection OV2PTOV partially or completely, by binary
input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

8.2.7.4 Design M15330-34 v8

The voltage measuring elements continuously measure the three phase-to-earth voltages or the
three phase-to-phase voltages. Recursive Fourier filters or true RMS filters of input voltage signals
are used. The phase voltages are individually compared to the set value, and the highest voltage is
used for the inverse time characteristic integration. A special logic is included to achieve the 1 out of
3, 2 out of 3 or 3 out of 3 criteria to fulfill the START condition. The design of Two step overvoltage
protection (OV2PTOV) is schematically described in figure 119.

238 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

UL1 Comparator ST1L1


UL1 > U1> Phase 1
Voltage Phase
Selector ST1L2
UL2 Comparator OpMode1 Phase 2
UL2 > U1> 1 out of 3
Start ST1L3
2 out of 3
3 out of 3 Phase 3 t1
UL3 Comparator t1Reset
UL3 > U1> & ST1
OR
Trip
START Output TR1L1
Logic

Time integrator Step 1 TR1L2


TRIP
MaxVoltSelect tIreset1
ResetTypeCrv1 TR1L3

OR TR1

Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
Start ST2L3
2 out of 3
Phase 3 t2
3 out of 3
Comparator t2Reset
UL3 > U2> & ST2
OR
Trip
START Output TR2L1
Logic

Time integrator Step 2 TR2L2


MaxVoltSelect tIreset2 TRIP
ResetTypeCrv2 TR2L3

TR2
OR

START
OR

TRIP
OR

IEC05000013-2-en.vsd
IEC05000013-WMF V2 EN-US

Figure 119: Schematic design of Two step overvoltage protection OV2PTOV

8.2.8 Technical data IP13013-1 v1

M13304-1 v16

Table 151: OV2PTOV technical data

Function Range or value Accuracy


Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Inverse time characteristics for steps 1 and - See table 757
2, see table 757
Definite time delay, low step (step 1) at 0 to (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
1.2 x Uset
Definite time delay, high step (step 2) at 0 (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
to 1.2 x Uset

Table continues on next page

Transformer protection RET650 239


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Function Range or value Accuracy


Minimum operate time, Inverse (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
characteristics
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Uset -
Impulse margin time 15 ms typically -

8.3 Two step residual overvoltage protection ROV2PTOV IP14546-1 v4

8.3.1 Function revision history GUID-22110E0B-DEFB-461F-A437-4D221DB88799 v3

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.1 PTP Enhancement
E 2.2.4 -
H 2.2.6 -
J 2.2.6 -

8.3.2 Identification
SEMOD54295-2 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step residual overvoltage protection ROV2PTOV 59N
2(U0>)

IEC15000108 V1 EN-US

8.3.3 Functionality M13808-3 v12

Residual voltages may occur in the power system during earth faults.

Two step residual overvoltage protection (ROV2PTOV) function calculates the residual voltage from
the three-phase voltage input transformers or measures it from a single voltage input transformer fed
from an open delta or neutral point voltage transformer.

A reset delay ensures operation for intermittent earth faults.

240 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.3.4 Function block M13812-3 v6

ROV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR2
BLKST1 START
BLKTR2 ST1
BLKST2 ST2

IEC06000278-2-en.vsd
IEC06000278 V2 EN-US

Figure 120: ROV2PTOV function block

8.3.5 Signals
PID-7438-INPUTSIGNALS v1

Table 152: ROV2PTOV Input signals

Name Type Default Description


U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-7438-OUTPUTSIGNALS v1

Table 153: ROV2PTOV Output signals

Name Type Description


TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2

8.3.6 Settings
PID-7438-SETTINGS v1

Table 154: ROV2PTOV Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Transformer protection RET650 241


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Table 155: ROV2PTOV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 1
Inverse curve B
Inverse curve C
Prog. inv. curve
U1> 1.0 - 200.0 %UB 0.1 30.0 Voltage setting/start val (DT & IDMT),
step 1 in % of UBase
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for step
Inverse curve A 2
Inverse curve B
Inverse curve C
Prog. inv. curve
U2> 1.0 - 200.0 %UB 0.1 45.0 Voltage setting/start val (DT & IDMT),
step 2 in % of UBase
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 156: ROV2PTOV Group settings (advanced)

Name Values (Range) Unit Step Default Description


tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 1
Linearly decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage IDMT
curve, step 1
Table continues on next page

242 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Name Values (Range) Unit Step Default Description


tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in DT reset (s), step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve type
Frozen timer for step 2
Linearly decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage IDMT
curve, step 2

8.3.7 Monitored data


PID-7438-MONITOREDDATA v1

Table 157: ROV2PTOV Monitored data

Name Type Values (Range) Unit Description


ULevel REAL - kV Magnitude of measured voltage

8.3.8 Operation principle M15331-3 v9

Two step residual overvoltage protection ROV2PTOV is used to detect a high residual voltage. The
residual voltage can be measured directly from a voltage transformer in the neutral of a power
transformer or from a three-phase voltage transformer, where the secondary windings are connected
in an open delta. Another possibility is to measure the three phase-to-earth voltages, and calculate
the corresponding residual voltage internally in the IED. ROV2PTOV has two steps with separate
time delays. If the residual voltage remains above the set value for a time period corresponding to
the chosen time delay, the corresponding TRIP signal is issued.

The time delay characteristic is individually chosen for the two steps and can be either definite time
delay or inverse time delay.

The voltage-related settings are made in percent of the base voltage, which is set in kV, phase-
phase. The set UBase value is divided by sqrt(3) before the set value is calculated.

8.3.8.1 Measurement principle M15331-6 v6

The residual voltage is measured continuously, and compared with the set values, U1> and U2>.

To avoid oscillations of the output START signal, a settable hysteresis has been included.

8.3.8.2 Time delay M15331-10 v12

The time delay for the two steps can be either definite time delay (DT) or inverse time delay (IDMT).
For the inverse time delay four different modes are available:

Transformer protection RET650 243


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 86)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US (Equation 87)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U > ø
IECEQUATION2421 V1 EN-US (Equation 88)

The customer programmable curve can be created as:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 89)

When the denominator in the expression is equal to zero, the time delay will be infinite. There will be
an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this
phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used voltage will be:
Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter must be calculated so
that:

CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN-US (Equation 90)

244 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

If the Programmable inverse curve is chosen for operation and Equation 90 does not
satisfy based on the set values, no TRIP signal is issued. However, START signal is set
and maintained as long as the measured quantity for operation is above the set start level
of step.

The details of the different inverse time characteristics are shown in section "Inverse characteristics".

TRIP signal issuing requires that the residual overvoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by some
special voltage level dependent time curves for the inverse time mode (IDMT).

If the START condition, with respect to the measured voltage ceases during the delay time, and is
not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time and
tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after the
defined reset time has elapsed.

Here it should be noted that after leaving the hysteresis area, the START condition must be fulfilled
again and it is not sufficient for the signal to only return back to the hysteresis area. Also, notice that
for the overvoltage function, IDMT reset time is constant and does not depend on the voltage
fluctuations during the drop-off period.

There are three ways to reset the timer: the timer is reset instantaneously, the timer value is frozen
during the reset time, or the timer value is linearly decreased during the reset time. See figure 121
and figure 122.

Transformer protection RET650 245


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 121: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

246 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 122: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 123. Detailed
information about individual stage reset/operation behavior is shown in figure 124 and figure 125
respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed
stage is ensured.

Transformer protection RET650 247


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 123: Logic diagram for step 1, Definite time delay, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 124: Example for Definite Time Delay stage 1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 125: Example for Definite Time Delay stage 1 operation

248 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.3.8.3 Blocking M15331-18 v7

It is possible to block two step residual overvoltage protection ROV2PTOV partially or completely by
binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip inputs related to step 2

8.3.8.4 Design M15331-32 v7

The voltage measuring elements continuously measure the residual voltage. Recursive Fourier filters
filter the input voltage signal for the rated frequency. The residual voltage is compared to the set
value, and is also used for the inverse time characteristic integration. The design of the function is
schematically described in figure 126.

UN Comparator Phase 1 ST1


UN > U1>
Start TR1
START t1
tReset1
&
Trip
Time integrator Output
tIReset1 TRIP
Logic
ResetTypeCrv1
Step 1

ST2
Comparator Phase 1
UN > U2> TR2
Start
t2
START tReset2
& START
Trip OR
Time integrator Output
TRIP Logic
tIReset2
ResetTypeCrv2 TRIP
Step 2 OR

IEC05000748_2_en.vsd
IEC05000748 V2 EN-US

Figure 126: Schematic design of Two step residual overvoltage protection ROV2PTOV

Transformer protection RET650 249


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.3.9 Technical data


M13317-2 v16

Table 158: ROV2PTOV technical data

Function Range or value Accuracy


Operate voltage, (1.0-200.0)% of UBase ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur
(0.0–50.0)% of UBase ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur
Inverse time characteristics for low and - See table 757
high step, see table
Definite time delay low step (step 1) at 0 (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is
to 1.2 x Uset greater
Definite time delay high step (step 2) at 0 (0.000–60.000) s ± 0.2% or ± 45 ms whichever is
to 1.2 x Uset greater
(0.000-60.000) s
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x U set -
Impulse margin time 15 ms typically -

8.4 Overexcitation protection OEXPVPH IP14547-1 v3

8.4.1 Identification
M14867-1 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overexcitation protection OEXPVPH 24

U/f >

SYMBOL-Q V1 EN-US

8.4.2 Functionality M13319-3 v9

When the laminated core of a power transformer or generator is subjected to a magnetic flux density
beyond its design limits, stray flux will flow into non-laminated components that are not designed to
carry flux. This will cause eddy currents to flow. These eddy currents can cause excessive heating
and severe damage to insulation and adjacent parts in a relatively short time. The function has
settable inverse operating curves and independent alarm stages.

250 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.4.3 Function block M13326-3 v5

OEXPVPH
I3P* TRIP
U3P* START
BLOCK ALARM
RESET

IEC05000329-2-en.vsd
IEC05000329 V3 EN-US

Figure 127: OEXPVPH function block

8.4.4 Signals
PID-8005-INPUTSIGNALS v1

Table 159: OEXPVPH Input signals

Name Type Default Description


I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
RESET BOOLEAN 0 Reset operation

PID-8005-OUTPUTSIGNALS v1

Table 160: O2RWPTOV Output signals

Name Type Description


TRIP BOOLEAN General trip signal
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2 if ConnType is set to PhN
DFT/PhN RMS
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2 if ConnType is set to PhN
DFT/PhN RMS

8.4.5 Settings
PID-8005-SETTINGS v1

Table 161: OEXPVPH Non group settings (basic)

Name Values (Range) Unit Step Default Description


MeasuredU PosSeq - - L1L2 Selection of measured voltage
L1L2
L2L3
L3L1
MeasuredI L1L2 - - L1L2 Selection of measured current
L2L3
L3L1
PosSeq
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Transformer protection RET650 251


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Table 162: OEXPVPH Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
V/Hz> 100.0 - 180.0 %UB/f 0.1 110.0 Operate level of V/Hz at no load and
rated freq in % of (UBase/frated)
V/Hz>> 100.0 - 200.0 %UB/f 0.1 140.0 High level of V/Hz above which tMin is
used, in % of (UBase/frated)
XLeak 0.000 - 200.000 Ohm 0.001 0.000 Winding leakage reactance in primary
ohms
TrPulse 0.000 - 60.000 s 0.001 0.100 Length of the pulse for trip signal (in sec)
tMin 0.000 - 60.000 s 0.001 7.000 Minimum trip delay for V/Hz inverse
curve, in sec
tMax 0.00 - 9000.00 s 0.01 1800.00 Maximum trip delay for V/Hz inverse
curve, in sec
tCooling 0.10 - 9000.00 s 0.01 1200.00 Transformer magnetic core cooling time
constant, in sec
CurveType IEEE - - IEEE Inverse time curve selection, IEEE/Tailor
Tailor made made
kForIEEE 1 - 60 - 1 1 Time multiplier for IEEE inverse type
curve
AlarmLevel 50.0 - 120.0 % 0.1 100.0 Alarm operate level as % of operate level
tAlarm 0.00 - 9000.00 s 0.01 5.00 Alarm time delay, in sec

Table 163: OEXPVPH Group settings (advanced)

Name Values (Range) Unit Step Default Description


t1Tailor 0.00 - 9000.00 s 0.01 7200.00 Time delay t1 (longest) for tailor made
curve, in sec
t2Tailor 0.00 - 9000.00 s 0.01 3600.00 Time delay t2 for tailor made curve, in sec
t3Tailor 0.00 - 9000.00 s 0.01 1800.00 Time delay t3 for tailor made curve, in sec
t4Tailor 0.00 - 9000.00 s 0.01 900.00 Time delay t4 for tailor made curve, in sec
t5Tailor 0.00 - 9000.00 s 0.01 450.00 Time delay t5 for tailor made curve, in sec
t6Tailor 0.00 - 9000.00 s 0.01 225.00 Time delay t6 (shortest) for tailor made
curve, in sec

8.4.6 Monitored data


PID-8005-MONITOREDDATA v1

Table 164: OEXPVPH Monitored data

Name Type Values (Range) Unit Description


TMTOTRIP REAL - s Calculated time to trip for overexcitation,
in sec
VPERHZ REAL - V/Hz Voltage to frequency ratio in per-unit
THERMSTA REAL - % Overexcitation thermal status in % of trip
level

8.4.7 Operation principle


M5854-3 v9
The importance of Overexcitation protection (OEXPVPH) function is growing as the power
transformers as well as other power system elements today operate near their designated limits most
of the time.

252 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Modern design transformers are more sensitive to overexcitation than earlier types. This is a result of
the more efficient designs and designs which rely on the improvement in the uniformity of the
excitation level of modern systems. If an emergency that causes overexcitation does occur,
transformers may be damaged unless corrective action is taken. Transformer manufacturers
recommend an overexcitation protection as a part of the transformer protection system.

Overexcitation results from excessive applied voltage, possibly in combination with below-normal
frequency. Such conditions may occur when a transformer unit is loaded, but are more likely to arise
when the transformer is unloaded, or when loss of load occurs. Transformers directly connected to
generators are in particular danger to experience an overexcitation conditions. It follows from the
fundamental transformer equation, see equation 91, that the peak flux density Bmax is directly
proportional to induced voltage E, and inversely proportional to frequency f and turns n.

E = 4.44 × f × n × B max× A
EQUATION898 V2 EN-US (Equation 91)

The relative excitation M is therefore according to equation 92.

E f
M ( p.u.) =
( Ur ) ( fr )
IECEQUATION2296 V1 EN-US (Equation 92)

Disproportional variations in quantities E and f may give rise to core overfluxing. If the core flux
density Bmax increases to a point above saturation level (typically 1.9 Tesla), the flux will no longer
be contained within the core, but will extend into other (non-laminated) parts of the power transformer
and give rise to eddy current circulations.

Overexcitation will result in:

• overheating of the non-laminated metal parts


• a large increase in magnetizing currents
• an increase in core and winding temperature
• an increase in transformer vibration and noise

Protection against overexcitation is based on calculation of the relative volt per hertz (V/Hz) ratio.
Protection initiates a reduction of excitation, and if this fails, or if this is not possible, the TRIP signal
will disconnect the transformer from the source after a delay ranging from seconds to minutes,
typically 5-10 seconds.

Overexcitation protection may be of particular concern on directly connected generator unit Step-up
Transformer. Directly connected generator-transformers are subjected to a wide range of frequencies
during the acceleration and deceleration of the turbine. In such cases, OEXPVPH (24) may trip the
field breaker during a start-up of a machine, by means of the overexcitation ALARM signal. If this is
not possible, the power transformer can be disconnected from the source, after a delay, by the TRIP
signal.

The IEC 60076 - 1 standard requires that transformers operate continuously at not more than 10%
above rated voltage at no load, and rated frequency. At no load, the ratio of the actual generator
terminal voltage to the actual frequency should not exceed 1.1 times the ratio of transformer rated
voltage to the rated frequency on a sustained basis, see equation 93.

E
---- £ 1.1 × Ur
------
f fr
EQUATION900 V1 EN-US (Equation 93)

or equivalently, with 1.1 · Ur = V/Hz> according to equation 94.

Transformer protection RET650 253


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

E V Hz >
£
f fr
IECEQUATION2297 V2 EN-US (Equation 94)

where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.

V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does not know exactly
what to set, then the default value for V/Hz> = 110 % given by the IEC 60076-1 standard shall be
used.

In OEXPVPH, the relative excitation M is expressed according to equation 95.

E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 95)

It is clear from the above formula that, for an unloaded power transformer, M = 1 for any E and f,
where the ratio E/f is equal to Ur/fr. A power transformer is not overexcited as long as the relative
excitation is M ≤ V/Hz>, V/Hz> expressed in % of Ur/fr.

The overexcitation protection algorithm is fed with an input voltage U which is in general not the
induced voltage E from the fundamental transformer equation. For no load condition, these two
voltages are the same, but for a loaded power transformer the internally induced voltage E may be
lower or higher than the voltage U which is measured and fed to OEXPVPH , depending on the
direction of the power flow through the power transformer, the power transformer side where
OEXPVPH is applied, and the power transformer leakage reactance of the winding. It is important to
specify in the application configuration on which side of the power transformer OEXPVPH is placed.

As an example, at a transformer with a 15% short circuit impedance Xsc, the full load, 0.8 power
factor, 105% voltage on the load side, the actual flux level in the transformer core, will not be
significantly different from that at the 110% voltage, no load, rated frequency, provided that the short
circuit impedance X can be equally divided between the primary and the secondary winding: Xleak =
Xleak1 = Xleak2 = Xsc / 2 = 0.075 pu.

OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage reactance of the
winding where OEXPVPH is connected) is known to the user. The assumption taken for two-winding
power transformers that Xleak = Xsc / 2 is unfortunately most often not true. For a two-winding power
transformer the leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers the situation is
still more complex. If a user has the knowledge on the leakage reactance, then it should applied. If a
user has no idea about it, Xleak can be set to Xc/2. OEXPVPH protection will then take the given
measured voltage U, as the induced voltage E.

It is assumed that overexcitation is a symmetrical phenomenon, caused by events such as loss-of-


load, etc. A high phase-to-earth voltage does not mean overexcitation. For example, in an unearthed
power system, a single phase-to-earth fault means high voltages of the “healthy” two phases-to-
earth, but no overexcitation on any winding. The phase-to-phase voltages will remain essentially
unchanged. The important voltage is the voltage between the two ends of each winding.

8.4.7.1 Measured voltage M5854-39 v9

If one phase-to-phase voltage is available from the side where overexcitation protection is applied,
then Overexcitation protection OEXPVPH shall be set to measure this voltage, MeasuredU. The
particular voltage which is used determines the two currents that must be used. This must be chosen
with the setting MeasuredI.

254 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

It is extremely important that MeasuredU and MeasuredI are set to same value.

If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2 must be applied. From
these two input currents, current IL1L2 = IL1 - IL2 is calculated internally by the OEXPVPH algorithm.
The phase-to-phase magnitude and frequency of the voltage must be both higher than 20% of the
rated value, when any of the two quantities are below this threshold, otherwise the protection
algorithm exits without calculating the excitation. ERROR output is set to 1, and the displayed value
of relative excitation V/Hz shows 0.000.

If three phase-to-earth voltages are available from the side where overexcitation is connected, then
OEXPVPH shall be set to measure positive sequence voltage and current. In this case the positive
sequence voltage and the positive sequence current are used by OEXPVPH. A check is made if the
positive sequence magnitude and frequency are higher than 20% of the rated phase-to-earth voltage
and rated frequency respectively, when any of the two quantities are below this threshold, OEXPVPH
exits immediately, and no excitation is calculated. ERROR output is set to 1, and the displayed value
of relative excitation V/Hz shows 0.000.

• OEXPVPH can be connected to any power transformer side, independent from the power flow.
• The side with a possible load tap changer must not be used.

8.4.7.2 Operate time of the overexcitation protection M5854-52 v8

The operate time of OEXPVPH is a function of the relative overexcitation.

Basically there are two different delay laws available to choose between:

• the so called IEEE law, and


• a tailor-made law.

The so called IEEE law approximates a square law and has been chosen based on analysis of the
various transformers’ overexcitation capability characteristics. They can match the transformer core
capability well.

The square law is according to equation 96.

0.18 × k 0.18 × k
top = 2
= 2
æ M ö overexcitation
ç V Hz> - 1 ÷
è ø
IECEQUATION2298 V2 EN-US (Equation 96)

where:
M the relative excitation
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier for inverse time functions, see figure 129.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.

The relative excitation M is calculated using equation97

æ Umeasured ö
ç ÷ Umeasured frated

fmeasured ø
M = ×
æ UBase ö UBase fmeasured
ç ÷
è frated ø
IECEQUATION2404 V1 EN-US (Equation 97)

Transformer protection RET650 255


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

An analog overexcitation relay would have to evaluate the following integral expression, which
means to look for the instant of time t = top according to equation 98.

top

ò (M (t) - V Hz > ) dt ³ 0.18 × k


2

IECEQUATION2300 V1 EN-US (Equation 98)

A digital, numerical relay will instead look for the lowest j (that is, j = n) where it becomes true that:

n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k
EQUATION906 V1 EN-US (Equation 99)

where:
Dt is the time interval between two successive executions of OEXPVPH and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is given as Ur/fr.

As long as M > V/Hz> (that is, overexcitation condition), the above sum can only be larger with time,
and if the overexcitation persists, the protected transformer will be tripped at j = n.

Inverse delays as per figure 129, can be modified (limited) by two special definite delay settings,
namely tMax and tMin, see figure 128.

delay in s

tMax

under - inverse delay law


excitation

overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>

M=V/Hz> Mmax Excitation M

V/Hz> Emax E (only if f = fr = const)

99001067.vsd
IEC99001067 V1 EN-US

Figure 128: Restrictions imposed on inverse delays by tMax and tMin


A definite maximum time, tMax, can be used to limit the operate time at low degrees of
overexcitation. Inverse delays longer than tMax will not be allowed. In case the inverse delay is
longer than tMax, OEXPVPH trips after tMax seconds.

A definite minimum time, tMin, can be used to limit the operate time at high degrees of
overexcitation. In case the inverse delay is shorter than tMin, OEXPVPH function trips after tMin
seconds. The inverse delay law is not valid for values exceeding Mmax. The delay will be tMin,
irrespective of the overexcitation level, when values exceed Mmax (that is, M>V/Hz>).

256 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

Time (s) IEEE OVEREXCITATION CURVES

1000

100

k = 60

k = 20

k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3

k=2

k=1
1
1 2 3 4 5 10 20 30 40

OVEREXCITATION IN % (M-Emaxcont)*100)

en01000373.vsd
IEC01000373 V1 EN-US

Figure 129: Delays inversely proportional to the square of the overexcitation


The critical value of excitation M is determined indirectly via OEXPVPH setting V/Hz>>. V/Hz>> can
be thought of as a no-load voltage at rated frequency, where the inverse law should be replaced by a
short definite delay, tMin. If, for example, V/Hz>> = 140 %, then M is according to equation 100.

(V Hz>> ) / f
M= = 1.40
Ur/fr
IECEQUATION2286 V1 EN-US (Equation 100)

The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this case the interval
between M = V/Hz>, and M = Mmax is automatically divided into five equal subintervals, with six
delays. (settings t1, t2, t3, t4, t5 and t6) as shown in figure 130. These times should be set so that t1
=> t2 => t3 => t4 => t5 => t6.

The lower V/Hz limit is always the set value V/Hz> in %.

The upper V/Hz limit for the Tailor-Made characteristic is always the greater value among the
following two values in %:

• 1.10 x V/Hz>
• V/Hz>>

The reason is to prevent the loss of accuracy of the Tailor-Made characteristic when small set value
for V/Hz>> is used.

Transformer protection RET650 257


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

delay in s

tMax

under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M

Emaxcont Mmax
99001068.vsd
IEC99001068 V1 EN-US

Figure 130: An example of a Tailor-Made delay characteristic


Delays between two consecutive points, for example t3 and t4, are obtained by linear interpolation.

Should it happen that tMax be lower than, for example, delays t1, and t2, the actual delay would be
tMax. Above Mmax, the delay can only be tMin.

8.4.7.3 Cooling M5854-92 v6

Overexcitation protection OEXPVPH is basically a thermal protection; therefore a cooling process


has been introduced. Exponential cooling process is applied. Parameter Setting tool is an OEXPVPH
setting, with a default time constant tCooling of 20 minutes. This means that if the voltage and
frequency return to their previous normal values (no more overexcitation), the normal temperature is
assumed to be reached not before approximately 5 times tCooling minutes. If an overexcitation
condition would return before that, the time to trip will be shorter than it would be otherwise.

8.4.7.4 Overexcitation protection function measurands M5854-95 v8

A monitored data value, TMTOTRIP, is available on the local HMI and in PCM600. This value is an
estimation of the remaining time to trip (in seconds), if the overexcitation remained on the level it had
when the estimation was done. This information can be useful during small or moderate
overexcitation situations.

If the overexcitation is so low that the valid delay is tMax, then the estimation of the remaining time to
trip is done against tMax.

The relative excitation M, shown on the local HMI and in PCM600 has a monitored data value
VPERHZ and is calculated from the expression:

E f
M ( p.u.) =
Ur fr
IECEQUATION2299 V1 EN-US (Equation 101)

If VPERHZ value is less than setting V/Hz> (in %), the power transformer is underexcited. If
VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal to the power transformer continuous
capability. If VPERHZ is higher than V/Hz>, the protected power transformer is overexcited. For
example, if VPERHZ = 1.100, while V/Hz> = 110 %, then the power transformer is exactly on its
maximum continuous excitation limit.

The monitored data value THERMSTA shows the thermal status of the protected power transformer
iron core. THERMSTA gives the thermal status in % of the trip value which corresponds to 100%.
THERMSTA should reach 100% at the same time, as TMTOTRIP reaches 0 seconds. If the

258 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

protected power transformer is then for some reason not switched off, THERMSTA shall go over
100%.

If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin, then the Thermal
status will generally not reach 100% at the same time, when tTRIP reaches 0 seconds. For example,
if, at low degrees of overexcitation, the very long delay is limited by tMax, then the OEXPVPH TRIP
output signal will be set to 1 before the Thermal status reaches 100%.

8.4.7.5 Overexcitation alarm M5854-123 v6

A separate step, AlarmLevel, is provided for alarming purpose. It is normally set 2% lower than (V/
Hz>) and has a definite time delay, tAlarm. This will give the operator an early warning.

8.4.7.6 Logic diagram M13333-9 v4

BLOCK
AlarmLevel
tAlarm ALARM
&
t

M>V/Hz>
TRIP
&
V/Hz>
U3P Calculation
Ei k
M
of internal M=
I3P induced (Ei / f) IEEE law &
voltage Ei (Ur / fr) tMax ³1
M t
Tailor-made law
M>V/Hz>>
tMin
Xleak
t
V/Hz>>

M = relative V/Hz as service value


IEC05000162-3-en.vsd
IEC05000162 V3 EN-US

Figure 131: A simplified logic diagram of the Overexcitation protection OEXPVPH


Simplification of the diagram is in the way the IEEE and Tailor-made delays are calculated. The
cooling process is not shown. It is not shown that voltage and frequency are separately checked
against their respective limit values.

8.4.8 Technical data


M13338-2 v13

Table 165: OEXPVPH technical data

Function Range or value Accuracy


Operate value, start (100–180)% of (UBase/frated) ±0.5% of U
Operate value, alarm (50–120)% of start level ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Operate value, high level ±0.5% of U
Reset Ratio > 99%
Table continues on next page

Transformer protection RET650 259


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Function Range or value Accuracy


Curve type IEEE

(0.18 × k )
IEEE : t =
( M - 1) 2

EQUATION1319 V1 EN-US (Equation 102)

where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s
function
Maximum time delay for inverse (0.00–9000.00) s
function
Alarm time delay (0.00–9000.00)

The healthy condition close to the rated values (that is, V/Hz below the set pickup value)
must be applied first when the operate time of a function is tested. Otherwise, an
additional delay of up to 50 ms should be added to stated operate times.

8.5 Voltage differential protection VDCPTDV SEMOD153860-1 v3

8.5.1 Function revision history GUID-04679E4E-E0D2-4BA6-A002-4020E52DB973 v2

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.1 PTP Enhancement
E 2.2.4 -
H 2.2.6 -
J 2.2.6 Function name changed from VDCPTOV to VDCPTDV

8.5.2 Identification
SEMOD167723-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage differential protection VDCPTDV - 87V

8.5.3 Functionality SEMOD153862-5 v8

A voltage differential monitoring function is available. It compares the voltages from two three phase
sets of voltage transformers and has one sensitive alarm step and one trip step.

260 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.5.4 Function block SEMOD159374-4 v3

VDCPTDV
U3P1* TRIP
U3P2* START
BLOCK ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF
IEC06000528 V3 EN-US

Figure 132: VDCPTDV function block

8.5.5 Signals
PID-8244-INPUTSIGNALS v1

Table 166: VDCPTDV Input signals

Name Type Default Description


U3P1 GROUP - Bus voltage
SIGNAL
U3P2 GROUP - Capacitor voltage
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-8244-OUTPUTSIGNALS v1

Table 167: VDCPTDV Output signals

Name Type Description


TRIP BOOLEAN Voltage differential protection operated
START BOOLEAN Start of voltage differential protection
ALARM BOOLEAN Voltage differential protection alarm
U1LOW BOOLEAN Loss of U1 voltage
U2LOW BOOLEAN Loss of U2 voltage
UL1DIFF REAL Differential voltage phase L1
UL2DIFF REAL Differential voltage phase L2
UL3DIFF REAL Differential voltage phase L3

8.5.6 Settings
GUID-7C74203F-0C71-4177-AAE2-CB3210CB6B1C v1

Table 168: VDCPTDV Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Table 169: VDCPTDV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
BlkDiffAtULow No - - Yes Block operation at low voltage
Yes
UDTrip 2.0 - 100.0 %UB 0.1 5.0 Operate level, in % of UBase
Table continues on next page

Transformer protection RET650 261


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

Name Values (Range) Unit Step Default Description


tTrip 0.000 - 60.000 s 0.001 1.000 Time delay for voltage differential operate,
in seconds
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for voltage differential reset, in
seconds
UDAlarm 2.0 - 100.0 %UB 0.1 2.0 Alarm level, in % of UBase
tAlarm 0.000 - 60.000 s 0.001 2.000 Time delay for voltage differential alarm,
in seconds
U1Low 1.0 - 100.0 %UB 0.1 70.0 Input 1 undervoltage level, in % of UBase
U2Low 1.0 - 100.0 %UB 0.1 70.0 Input 2 undervoltage level, in % of UBase
tBlock 0.000 - 60.000 s 0.001 0.000 Reset time for undervoltage block

Table 170: VDCPTDV Group settings (advanced)

Name Values (Range) Unit Step Default Description


RFL1 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L1
U2L1*RFL1=U1L1
RFL2 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L2
U2L2*RFL2=U1L2
RFL3 0.000 - 3.000 - 0.001 1.000 Ratio compensation factor phase L3
U2L3*RFL3=U1L3

8.5.7 Monitored data


GUID-4AA9B710-4BFD-42E2-8446-E6A2CECAF4E1 v1

Table 171: VDCPTDV Monitored data

Name Type Values (Range) Unit Description


UL1DIFF REAL - kV Differential voltage phase L1
UL2DIFF REAL - kV Differential voltage phase L2
UL3DIFF REAL - kV Differential voltage phase L3

8.5.8 Operation principle SEMOD153866-61 v5

The Voltage differential protection function VDCPTDV (87V) is based on comparison of the
amplitudes of the two voltages connected in each phase. Possible differences between the ratios of
the two Voltage/Capacitive voltage transformers can be compensated for with a ratio correction
factors RFLx. The voltage difference is evaluated and if it exceeds the alarm level UDAlarm or trip
level UDATrip signals for alarm (ALARM output) or trip (TRIP output) is given after definite time delay
tAlarm respectively tTrip. The two three phase voltage supplies are also supervised with
undervoltage settings U1Low and U2Low. The outputs for loss of voltage U1LOW resp U2LOW will
be activated. The U1 voltage is supervised for loss of individual phases whereas the U2 voltage is
supervised for loss of all three phases.

Loss of all U1 or all U2 voltages will block the differential measurement. This blocking can be
switched off with setting BlkDiffAtULow = No.

VDCPTDV function can be blocked from an external condition with the binary BLOCK input. It can,
for example, be activated from Fuse failure supervision function FUFSPVC.

To allow easy commissioning the measured differential voltage is available as service value. This
allows simple setting of the ratio correction factor to achieve full balance in normal service.

The principle logic diagram is shown in figure 133.

262 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

UDTripL1>
AND

UDTripL2> O tReset tTrip


AND
R t t
AND TRIP

UDTripL3>
AND
AND START

UDAlarmL1>
AND

UDAlarmL2> O tAlarm
AND
R t AND ALARM

UDAlarmL3>
AND

U1<L1
tAlarm
U1<L2 AND t U1LOW
AND

U1<L3 AND

OR
BlkDiffAtULow

U2<L1
t1
U2<L2 AND t U2LOW
AND

U2<L3

BLOCK

en06000382-2.vsd
IEC06000382 V3 EN-US

Figure 133: Principle logic for Voltage differential function VDCPTDV

8.5.9 Technical data


SEMOD166919-2 v8

Table 172: VDCPTDV technical data

Function Range or value Accuracy


Voltage difference for alarm and trip (2.0–100.0) % of UBase ±0.5% of Ur
Under voltage level (1.0–100.0) % of UBase ±0.5% of Ur
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
alarm at 0.8 x UDAlarm to 1.2 x UDAlarm
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
trip at 0.8 x UDTrip to 1.2 x UDTrip
Independent time delay for voltage differential (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
reset at 1.2 x UDTrip to 0.8 x UDTrip

Transformer protection RET650 263


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

8.6 Loss of voltage check LOVPTUV SEMOD171453-1 v3

8.6.1 Identification
SEMOD171954-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Loss of voltage check LOVPTUV - 27

8.6.2 Functionality SEMOD171457-5 v8

Loss of voltage check (LOVPTUV ) is suitable for use in networks with an automatic system
restoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, if all three
phase voltages fall below the set value for a time longer than the set time and the circuit breaker
remains closed.

The operation of LOVPTUV is supervised by the fuse failure supervision FUFSPVC.

8.6.3 Function block SEMOD171785-4 v4

LOVPTUV
U3P* TRIP
BLOCK START
CBOPEN
VTSU

IEC07000039-2-en.vsd
IEC07000039 V2 EN-US

Figure 134: LOVPTUV function block

8.6.4 Signals
PID-3519-INPUTSIGNALS v6

Table 173: LOVPTUV Input signals

Name Type Default Description


U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block the all outputs
CBOPEN BOOLEAN 0 Circuit breaker open
VTSU BOOLEAN 0 Block from voltage circuit supervision

PID-3519-OUTPUTSIGNALS v6

Table 174: LOVPTUV Output signals

Name Type Description


TRIP BOOLEAN Trip signal
START BOOLEAN Start signal

264 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 8
Voltage protection

8.6.5 Settings
PID-3519-SETTINGS v6

Table 175: LOVPTUV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
UPE 1 - 100 %UB 1 70 Operate voltage in % of base voltage
UBase
tTrip 0.000 - 60.000 s 0.001 7.000 Operate time delay

Table 176: LOVPTUV Group settings (advanced)

Name Values (Range) Unit Step Default Description


tPulse 0.050 - 60.000 s 0.001 0.150 Duration of TRIP pulse
tBlock 0.000 - 60.000 s 0.001 5.000 Time delay to block when all 3ph voltages
are not low
tRestore 0.000 - 60.000 s 0.001 3.000 Time delay for enable the function after
restoration

Table 177: LOVPTUV Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

8.6.6 Operation principle SEMOD171765-4 v6

The operation of Loss of voltage check LOVPTUV is based on line voltage measurement. LOVPTUV
is provided with a logic, which automatically recognizes if the line was restored for at least tRestore
before starting the tTrip timer. All three phases are required to be low before the output TRIP is
activated. The START output signal indicates start.

Additionally, LOVPTUV is automatically blocked if only one or two phase voltages have been
detected low for more than tBlock.

LOVPTUV operates again only if the line has been restored to full voltage for at least tRestore.
Operation of the function is also inhibited by fuse failure and open circuit breaker information signals,
by their connection to dedicated inputs of the function block.

Due to undervoltage conditions being continuous the trip pulse is limited to a length set by setting
tPulse.

The operation of LOVPTUV is supervised by the fuse-failure function (BLKU input) and the
information about the open position (CBOPEN) of the associated circuit breaker.

The BLOCK input can be connected to a binary input of the IED in order to receive a block command
from external devices or can be software connected to other internal functions of the IED itself in
order to receive a block command from internal functions. LOVPTUV is also blocked when the IED is
in TEST status and the function has been blocked from the HMI test menu. (Blocked=Yes).

Transformer protection RET650 265


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 8 1MRK504170-UEN Rev. J
Voltage protection

TEST

TEST-ACTIVE
&
Blocked = Yes

START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t

STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&

tBlock
>1 t

CBOPEN Reset Enable


>1
&
VTSU
tRestore
>1 Set Enable
t
>1
Line restored for
at least 3 s

IEC07000089_2_en.vsd

IEC07000089 V2 EN-US

Figure 135: Simplified diagram of Loss of voltage check LOVPTUV

8.6.7 Technical data


SEMOD175210-2 v7

Table 178: LOVPTUV technical data

Function Range or value Accuracy


Operate voltage UBase ±0.5% of Ur
Pulse timer when disconnecting all three (0.050–60.000) s
phases
Time delay for enabling the functions after (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
restoration
Operate time delay when disconnecting all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phases
Time delay to block when all three phase (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
voltages are not low

266 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

Section 9 Frequency protection


9.1 Underfrequency protection SAPTUF IP15746-1 v3

9.1.1 Identification
M14865-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Underfrequency protection SAPTUF 81

f<

SYMBOL-P V1 EN-US

9.1.2 Functionality M13349-3 v13

Underfrequency occurs as a result of a lack of generation in the network.

Underfrequency protection (SAPTUF) measures frequency with high accuracy, and is used for load
shedding systems, remedial action schemes, gas turbine startup and so on. Separate definite time
delays are provided for operate and restore.

SAPTUF is provided with undervoltage blocking.

The operation is based on positive sequence voltage measurement and requires two phase-phase or
three phase-neutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual /IED application /Analog inputs /Setting guidelines .

9.1.3 Function block M13352-3 v6

SAPTUF
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN
FREQ

IEC06000279_2_en.vsd
IEC06000279 V2 EN-US

Figure 136: SAPTUF function block

9.1.4 Signals
PID-6752-INPUTSIGNALS v2

Table 179: SAPTUF Input signals

Name Type Default Description


U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output
BLKREST BOOLEAN 0 Blocking restore output

Transformer protection RET650 267


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

PID-6752-OUTPUTSIGNALS v2

Table 180: SAPTUF Output signals

Name Type Description


TRIP BOOLEAN General trip signal
START BOOLEAN General start signal
RESTORE BOOLEAN Restore signal for load restoring purposes
BLKDMAGN BOOLEAN Blocking indication due to low amplitude
FREQ REAL Measured frequency

9.1.5 Settings
PID-6752-SETTINGS v2

Table 181: SAPTUF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 75.00 Hz 0.01 48.80 Frequency set value
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency value
TimerMode Definite timer - - Definite timer Setting for choosing timer mode
Volt based timer
UNom 50.0 - 150.0 %UB 1.0 100.0 Nominal voltage for voltage based timer
in % of UBase
UMin 50.0 - 150.0 %UB 1.0 90.0 Lower operation limit for voltage based
timer in % of UBase
Exponent 0.0 - 5.0 - 0.1 1.0 For calculation of the curve form for
voltage based timer
tMax 0.010 - 60.000 s 0.001 1.000 Maximum time operation limit for voltage
based timer
tMin 0.010 - 60.000 s 0.001 1.000 Minimum time operation limit for voltage
based timer

Table 182: SAPTUF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

9.1.6 Operation principle M13354-3 v9

Underfrequency protection SAPTUF is used to detect low power system frequency. SAPTUF can
either have a definite time delay or a voltage magnitude dependent time delay. If the voltage
magnitude dependent time delay is applied, the time delay will be longer if the voltage is higher, and
the delay will be shorter if the voltage is lower. If the frequency remains below the set value for a time
period corresponding to the chosen time delay, the corresponding trip signal is issued. To avoid an
unwanted trip due to uncertain frequency measurement at low voltage magnitude, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than the set blocking
voltage IntBlockLevel, the function is blocked and no START or TRIP signal is issued.

268 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

9.1.6.1 Measurement principle M13354-6 v8

The fundamental frequency of the measured input voltage is measured continuously, and compared
with the set value, StartFrequency. The frequency function is dependent on the voltage magnitude. If
the voltage magnitude decreases below the setting IntBlockLevel, SAPTUF gets blocked, and the
output BLKDMAGN is issued. All voltage settings are made in percent of the setting UBase, which
should be set as a phase-phase voltage in kV.

To avoid oscillations of the output START signal, a hysteresis has been included.

9.1.6.2 Time delay M13354-10 v10

The time delay for underfrequency protection SAPTUF can be either a settable definite time delay or
a voltage magnitude dependent time delay, where the time delay depends on the voltage level; a
high voltage level gives a longer time delay and a low voltage level causes a short time delay. For the
definite time delay, the setting tDelay sets the time delay.

For the voltage dependent time delay the measured voltage level and the settings UNom, UMin,
Exponent, tMax and tMin set the time delay according to Figure 137 and Equation 103. The setting
TimerMode is used to decide what type of time delay to apply.

Trip signal issuing requires that the underfrequency condition continues for at least the user set time
delay tDelay. If the START condition, with respect to the measured frequency ceases during this user
set delay time, and is not fulfilled again within a user defined reset time, tReset, the START output is
reset, after that the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area.

The total time delay consists of the set value for time delay plus the minimum operate
time of the start function (80-90 ms).

On the RESTORE output of SAPTUF a 100ms pulse is issued, after a time delay corresponding to
the setting of tRestore, when the measured frequency returns to the level corresponding to the
setting RestoreFreq, after an issue of the TRIP output signal. If tRestore is se to 0.000 s the restore
functionality is disabled, and no output will be given.

9.1.6.3 Voltage dependent time delay M13354-19 v6

Since the fundamental frequency in a power system is the same all over the system, except some
deviations during power oscillations, another criterion is needed to decide, where to take actions,
based on low frequency. In many applications the voltage level is very suitable, and in most cases is
load shedding preferable in areas with low voltage. Therefore, a voltage dependent time delay has
been introduced, to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to Equation 103
undervoltage and overvoltage functions.

Transformer protection RET650 269


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

Exponent
é U - UMin ù
t=ê × ( tMax - tMin) + tMin
ëUNom - UMin úû

U = U measured

EQUATION1182 V2 EN-US (Equation 103)

where:
t is the voltage dependent time delay (at constant voltage),
U is the measured voltage
Exponent is a setting,
UMin, UNom are voltage settings corresponding to
tMax, tMin are time settings.

The inverse time characteristics are shown in Figure 137, for:

UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3, and 4

1
0
1
Exponenent
TimeDlyOperate [s]

2
3
0.5 4

0
90 95 100

U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN-US

Figure 137: Voltage dependent inverse time characteristics for underfrequency protection
SAPTUF. The time delay to operate is plotted as a function of the measured
voltage, for the Exponent = 0, 1, 2, 3, 4 respectively.

9.1.6.4 Blocking M13354-50 v7

It is possible to block underfrequency protection SAPTUF partially or completely, by binary input


signals or by parameter settings, where:

BLOCK: blocks the START, TRIP and


RESTORE outputs
BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

270 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.

9.1.6.5 Design M13354-63 v10

The frequency measuring element continuously measures the frequency of the positive sequence
voltage and compares it to the setting StartFrequency. The frequency signal is filtered to avoid
transients due to switchings and faults. The time integrator can operate either due to a definite delay
time or to the special voltage dependent delay time. When the frequency has returned back to the
setting of RestoreFreq, the RESTORE output is issued after the time delay tRestore. The design of
underfrequency protection SAPTUF is schematically described in figure 138.

BLKDMAGN

BLOCK

block START
OR

U < IntBlockLevel

Start
&
start Trip
Voltage
output
Definite timer
logic TRIP
or
Voltage based timer
Frequency
f < StartFrequency
tReset trip
tDelay RESTORE
AND

BLKTRIP

f > RestoreFreq tRestore


restore
AND
BLKREST

IEC16000041-1-en.vsdx
IEC16000041 V1 EN-US

Figure 138: Simplified logic diagram for SAPTUF

Transformer protection RET650 271


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

9.1.7 Technical data


M13360-1 v17

Table 183: SAPTUF technical data

Function Range or Value Accuracy


Operate value, start function, at (35.00 - 75.00) Hz ±2.0 mHz
symmetrical three phase voltage,
StartFrequency 1)
Reset hysteresis 10.0 mHz fixed ±2.0 mHz
Operate time 1) Start time measurement Min. = 175 ms -
with sudden frequency
Max. = 195 ms
change
fr = 50 Hz
Start time measurement Min. = 70 ms
with frequency ramp
Max. = 90 ms
Start time measurement Min. = 150 ms -
with sudden frequency
Max. = 165 ms
change
fr = 60 Hz
Start time measurement Min. = 60 ms
with frequency ramp
Max. = 75 ms
Disengaging time 1) Start time measurement Min. = 170 ms -
with sudden frequency
Max. =195 ms
change
fr = 50 Hz
Start time measurement Min. = 75 ms
with frequency ramp
Max. = 100 ms
Start time measurement Min. = 140 ms -
with sudden frequency
Max. =165 ms
change
fr = 60 Hz
Start time measurement Min. = 65 ms
with frequency ramp
Max. = 90 ms
Operate time delay, fr = 50 Hz ±0.2% or ±200 ms
tDelay 1) whichever is greater
(0.000-60.000)s
fr = 60 Hz ±0.2% or ±175 ms
whichever is greater
Voltage dependent Settings: ±1.0% or ±120 ms
time delay UNom = (50-150)% of UBase whichever is greater
UMin = (50-150)% of UBase
Exponent = 0.0-5.0
tMax = (0.010-60.000)s
tMin = (0.010- 60.000)s

Exponent
é U - UMin ù
t=ê × ( tMax - tMin) + tMin
ëUNom - UMin úû

U = U measured
EQUATION1182 V2 EN-US

Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.

1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).

9.2 Overfrequency protection SAPTOF IP15747-1 v3

272 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

9.2.1 Identification
M14866-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Overfrequency protection SAPTOF 81

f>

SYMBOL-O V1 EN-US

9.2.2 Functionality M14953-3 v12

Overfrequency protection function (SAPTOF) is applicable in all situations, where reliable detection
of high fundamental power system frequency is needed.

Overfrequency occurs because of sudden load drops or shunt faults in the power network. Close to
the generating plant, generator governor problems can also cause over frequency.

SAPTOF measures frequency with high accuracy, and is used mainly for generation shedding and
remedial action schemes. It is also used as a frequency stage initiating load restoring. A definite time
delay is provided for operate.

SAPTOF is provided with an undervoltage blocking.

The operation is based on positive sequence voltage measurement and requires two phase-phase or
three phase-neutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual /IED application /Analog inputs /Setting guidelines .

9.2.3 Function block M14956-3 v5

SAPTOF
U3P* TRIP
BLOCK START
BLKTRIP BLKDMAGN
FREQ

IEC06000280_2_en.vsd
IEC06000280 V2 EN-US

Figure 139: SAPTOF function block

9.2.4 Signals
PID-6751-INPUTSIGNALS v2

Table 184: SAPTOF Input signals

Name Type Default Description


U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output

Transformer protection RET650 273


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

PID-6751-OUTPUTSIGNALS v2

Table 185: SAPTOF Output signals

Name Type Description


TRIP BOOLEAN General trip signal
START BOOLEAN General start signal
BLKDMAGN BOOLEAN Blocking indication due to low amplitude
FREQ REAL Measured frequency

9.2.5 Settings
PID-6751-SETTINGS v2

Table 186: SAPTOF Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
StartFrequency 35.00 - 90.00 Hz 0.01 51.20 Frequency set value
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.000 Operate time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset

Table 187: SAPTOF Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

9.2.6 Operation principle M14958-3 v7

Overfrequency protection SAPTOF is used to detect high power system frequency. SAPTOF has a
settable definite time delay. If the frequency remains above the set value for a time period
corresponding to the chosen time delay, the corresponding TRIP signal is issued. To avoid an
unwanted TRIP due to uncertain frequency measurement at low voltage magnitude, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than the set blocking
voltage IntBlockLevel, the function is blocked and no START or TRIP signal is issued.

9.2.6.1 Measurement principle M14958-6 v9

The fundamental frequency of the positive sequence voltage is measured continuously, and
compared with the set value, StartFrequency. Overfrequency protection SAPTOF is dependent on
the voltage magnitude. If the voltage magnitude decreases below the setting IntBlockLevel, SAPTOF
is blocked and the output BLKDMAGN is issued. All voltage settings are made in percent of the
UBase, which should be set as a phase-phase voltage in kV. To avoid oscillations of the output
START signal, a hysteresis has been included.

9.2.6.2 Time delay M14958-9 v8

The time delay for Overfrequency protection SAPTOF is a settable definite time delay, specified by
the setting tDelay.

TRIP signal issuing requires that the overfrequency condition continues for at least the user set time
delay, tDelay. If the START condition, with respect to the measured frequency ceases during this
user set delay time, and is not fulfilled again within a user defined reset time, tReset, the START
output is reset, after that the defined reset time has elapsed. It is to be noted that after leaving the

274 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

hysteresis area, the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area.

The total time delay consists of the set value for time delay plus minimum operate time of
the start function (80 - 90 ms).

9.2.6.3 Blocking M14958-13 v7

It is possible to block overfrequency protection SAPTOF partially or completely, by binary input


signals or by parameter settings, where:

BLOCK: blocks the START and TRIP outputs


BLKTRIP: blocks the TRIP output

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.

9.2.6.4 Design M14958-24 v9

The frequency measuring element continuously measures the frequency of the positive sequence
voltage and compares it to the setting StartFrequency. The frequency signal is filtered to avoid
transients due to switchings and faults in the power system. The time integrator operates due to a
definite delay time. The design of overfrequency protection SAPTOF is schematically described in
figure 140.

BLKDMAGN

BLOCK

block START
OR

U < IntBlockLevel

Start
&
start Trip
Voltage
output
logic TRIP
Definite timer
Frequency
f > StartFrequency tReset
trip
tDelay

AND

BLKTRIP

IEC16000042-1-en.vsdx
IEC16000042 V1 EN-US

Figure 140: Simplified logic diagram for SAPTOF

Transformer protection RET650 275


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

9.2.7 Technical data


M14964-1 v14

Table 188: SAPTOF technical data

Function Range or Value Accuracy


Operate value, start function, (35.00 - 90.00) Hz ±2.0 mHz
at symmetrical three phase
voltage, StartFrequency 1)
Reset hysteresis 1) 10.0 mHz fixed ±2.0 mHz

Operate time 1) Start time measurement with Min. = 175 ms -


sudden frequency change
Max. = 195 ms
fr = 50 Hz
Start time measurement with Min. = 70 ms
frequency ramp
Max. = 90 ms
Start time measurement with Min. = 150 ms -
sudden frequency change
Max. = 165 ms
fr = 60 Hz
Start time measurement with Min. = 60 ms
frequency ramp
Max. = 75 ms
Disengaging time 1) Start time measurement with Min. = 170 ms -
sudden frequency change
Max. = 195 ms
fr = 50 Hz
Start time measurement with Min. = 75 ms
frequency ramp
Max. = 100 ms
Start time measurement with Min. = 140 ms -
sudden frequency change
Max. = 165 ms
fr = 60 Hz
Start time measurement with Min. = 65 ms
frequency ramp
Max. = 90 ms
Operate time delay, fr = 50 Hz ±0.2% or ±200 ms
tDelay 1) whichever is greater
(0.000-60.000)s
fr = 60 Hz ±0.2% or ±175 ms
whichever is greater
Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.

1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).

9.3 Rate-of-change of frequency protection SAPFRC IP15748-1 v4

9.3.1 Identification
M14868-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Rate-of-change of frequency protection SAPFRC 81

df/dt >
<

SYMBOL-N V1 EN-US

9.3.2 Functionality M14965-3 v14

The rate-of-change of frequency protection function (SAPFRC) gives an early indication of a main
disturbance in the system. SAPFRC measures frequency with high accuracy, and can be used for

276 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

generation shedding, load shedding and remedial action schemes. SAPFRC can discriminate
between a positive or negative change of frequency. A definite time delay is provided for operate.

SAPFRC is provided with an undervoltage blocking. The operation is based on positive sequence
voltage measurement and requires two phase-phase or three phase-neutral voltages to be
connected. For information about how to connect analog inputs, refer to Application manual/IED
application/Analog inputs/Setting guidelines .

9.3.3 Function block M14968-3 v6

SAPFRC
U3P* TRIP
BLOCK START
BLKTRIP RESTORE
BLKREST BLKDMAGN

IEC06000281-2-en.vsd
IEC06000281 V2 EN-US

Figure 141: SAPFRC function block

9.3.4 Signals
PID-6754-INPUTSIGNALS v2

Table 189: SAPFRC Input signals

Name Type Default Description


U3P GROUP - Three phase group signal for voltage inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output
BLKREST BOOLEAN 0 Blocking restore output

PID-6754-OUTPUTSIGNALS v2

Table 190: SAPFRC Output signals

Name Type Description


TRIP BOOLEAN Trip signal
START BOOLEAN Start signal
RESTORE BOOLEAN Restore signal for load restoring purposes
BLKDMAGN BOOLEAN Blocking indication due to low amplitude

9.3.5 Settings
PID-6754-SETTINGS v2

Table 191: SAPFRC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
StartFreqGrad -10.00 - 10.00 Hz/s 0.01 0.50 Frequency gradient start value, the sign
defines direction
IntBlockLevel 0.0 - 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 - 60.000 s 0.001 0.200 Operate time delay
RestoreFreq 45.00 - 65.00 Hz 0.01 49.90 Restore frequency value
tRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset

Transformer protection RET650 277


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

Table 192: SAPFRC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

9.3.6 Operation principle M14970-3 v9

Rate-of-change frequency protection SAPFRC is used to detect fast power system frequency
changes at an early stage. SAPFRC has a settable definite time delay. If the rate-of-change of
frequency remains below the set value, for negative rate-of-change, for a time period equal to the
chosen time delay, the TRIP signal is issued. If the rate-of-change of frequency remains above the
set value, for positive rate-of-change, for a time period equal to the chosen time delay, the TRIP
signal is issued. To avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude a voltage controlled blocking of the function is available, that is, if the voltage is lower than
the set blocking voltage IntBlockLevel the function is blocked and no START or TRIP signal is issued.
If the frequency recovers, after a frequency decrease, a restore signal is issued.

9.3.6.1 Measurement principle M14970-6 v8

The rate-of-change of the fundamental frequency of the selected voltage is measured continuously,
and compared with the set value, StartFreqGrad. Rate-of-change frequency protection SAPFRC is
also dependent on the voltage magnitude. If the voltage magnitude decreases below the setting
IntBlockLevel , SAPFRC is blocked, and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad, controls if SAPFRC reacts on a positive or on a negative change in frequency. If
SAPFRC is used for decreasing frequency that is, the setting StartFreqGrad has been given a
negative value, and a trip signal has been issued, then a 100 ms pulse is issued on the RESTORE
output, when the frequency recovers to a value higher than the setting RestoreFreq. A positive
setting of StartFreqGrad, sets SAPFRC to START and TRIP for frequency increases.

To avoid oscillations of the output START signal, a hysteresis has been included.

9.3.6.2 Time delay M14970-10 v7

Rate-of-change frequency protection SAPFRC has a settable definite time delay, tDelay.

Trip signal issuing requires that the rate-of-change of frequency condition continues for at least the
user set time delay, tDelay. If the START condition, with respect to the measured frequency ceases
during the delay time, and is not fulfilled again within a user defined reset time, tReset, the START
output is reset, after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is not sufficient for the
signal to only return back into the hysteresis area.

The RESTORE output of SAPFRC is set, after a time delay equal to the setting of tDelay, when the
measured frequency has returned to the level corresponding to RestoreFreq, after an issue of the
TRIP output signal. If tRestore is set to 0.000 s the restore functionality is disabled, and no output will
be given. The restore functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the restore period,
defined by the settings RestoreFreq and tRestore.

9.3.6.3 Blocking M14970-23 v6

Rate-of-change frequency protection (SAPFRC) can be partially or totally blocked, by binary input
signals or by parameter settings, where:

278 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

BLOCK: blocks the START and TRIP outputs


BLKTRIP: blocks the TRIP output
BLKREST: blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the START and the
TRIP outputs are blocked.

9.3.6.4 Design M14970-34 v7

Rate-of-change frequency protection (SAPFRC) measuring element continuously measures the


frequency of the selected voltage and compares it to the setting StartFreqGrad. The frequency signal
is filtered to avoid transients due to power system switchings and faults. The time integrator operates
with a definite delay time. When the frequency has returned back to the setting of RestoreFreq, the
RESTORE output is issued after the time delay tRestore, if the TRIP signal has earlier been issued.
The sign of the setting StartFreqGrad is essential, and controls if the function is used for raising or
lowering frequency conditions. The design of SAPFRC is schematically described in figure 142.

BLKDMAGN

BLOCK
block
OR
Voltage
U < IntBlockLevel

START

Start
Rate-of-change
&
of Frequency start
If Trip
[StartFreqGrad<0 output
AND logic
Definite timer
df/dt < StartFreqGrad]
start TRIP
OR
tReset
[StartFreqGrad>0
AND
tDelay
df/dt > StartFreqGrad]
Then
START trip
AND
BLKTRIP
RESTORE

Frequency restore
f > RestoreFreq
> tRestore
AND
BLKREST

IEC16000040-1-en.vsdx
IEC16000040 V1 EN-US

Figure 142: Simplified logic diagram for SAPFRC

Transformer protection RET650 279


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9 1MRK504170-UEN Rev. J
Frequency protection

9.3.7 Technical data


M14976-1 v11

Table 193: SAPFRC technical data

Function Range and value Accuracy


Operate value, start function, at Positive gradient: from 0.05 to 10.00 Hz/s ** ±10.0 mHz/s
symmetrical three phase voltage Negative gradient: from -0.05 to -10.00 Hz/s **
*, StartFreqGrad or Gs per IEC
60255-181 standard
Reset hysteresis * < 15.0 mHz/s
Operate value, restore enable (45.00 - 65.00) Hz ±2.0 mHz
frequency, at symmetrical three
phase voltage, RestoreFreq
Restore time delay, tRestore fr = 50 Hz (0.025 - 60.000) s ±0.2% or ±110 ms
whichever is greater
Test conditions: fr = 60 Hz ±0.2% or ±100 ms
Restore time delay measurement whichever is greater
with sudden frequency change
from RestoreFreq -0.02 Hz to
RestoreFreq + 0.02 Hz
Start time * fr = 50 Hz Gs: ±0.05 & ±0.50 Hz/s Min. = 110 ms
Tested frequency slope:
Max. = 290 ms
1.2, 2.0, 5.0, 10.0 x Gs
Gs: ±1.00 Hz/s Min. = 180 ms
Tested frequency slope:
Max. = 300 ms
1.2, 2.0, 5.0 x Gs
Gs: ±3.00, ±6.00 & ±10.00 Min. = 300 ms
Hz/s
Max. = 390 ms
Tested frequency slope:
1.2, 2.0 x Gs
fr = 60 Hz Gs: ±0.05 & ±0.50 Hz/s Min. = 90 ms
Tested frequency slope:
Max. = 220 ms
1.2, 2.0, 5.0, 10.0 x Gs
Gs: ±1.00 Hz/s Min. = 140 ms
Tested frequency slope:
Max. = 240 ms
1.2, 2.0, 5.0 x Gs
Gs: ±3.00, ±6.00 & ±10.00 Min. = 180 ms
Hz/s
Max. = 300 ms
Tested frequency slope:
1.2, 2.0 x Gs
Disengaging time * fr = 50 Hz Gs: ±0.05 Hz/s Min. = 130 ms
Tested frequency slope:
Max. = 270 ms
1.2, 2.0, 5.0, 10.0 x Gs
Gs: ±5.00 Hz/s Min. = 130 ms
Tested frequency slope:
Max. = 210 ms
1.2, 2.0 x Gs
Gs: ±10.00 Hz/s Min. = 130 ms
Tested frequency slope:
Max. = 160 ms
1.2 x Gs
fr = 60 Hz Gs: ±0.05 Hz/s Min. = 100 ms
Tested frequency slope:
Max. = 210 ms
1.2, 2.0, 5.0, 10.0 x Gs
Gs: ±5.00 Hz/s Min. = 100 ms
Tested frequency slope:
Max. = 170 ms
1.2, 2.0 x Gs
Gs: ±10.00 Hz/s Min. = 100 ms
Tested frequency slope:
Max. = 130 ms
1.2 x Gs
Table continues on next page

280 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 9
Frequency protection

Function Range and value Accuracy


Operate time delay *, tDelay fr = 50 Hz (0.000-60.000) s ±0.2% or ±220 ms
Test conditions: whichever is greater
Gs: ± 0.2 Hz/s
fr = 60 Hz ±0.2% or ±180 ms
Frequency slope: 0.4 Hz/s
whichever is greater
Test points: 10%, 20%, 30%,
50% and 100% of the time delay
setting range
Reset time delay, tReset fr = 50 Hz (0.000-60.000) s ±0.2% or ±220 ms
Test conditions: whichever is greater
Gs: ±0.2 Hz/s
fr = 60 Hz ±0.2% or ±180 ms
Frequency slope: 0.4 Hz/s
whichever is greater
* The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
** The value ±0.05 Hz/s is used as minimum pickup value for frequency gradient.
Note! The stated accuracy is valid for phase-to-earth voltage range from 50 V to 250 V secondary. During testing three phase-to-earth
voltages with magnitude of 110/sqrt(3)=63.5 V were always used.

Transformer protection RET650 281


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
282
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Section 10 Secondary system supervision


10.1 Current circuit supervision CCSSPVC IP14555-1 v5

10.1.1 Identification
M14870-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current circuit supervision CCSSPVC - 87

10.1.2 Functionality M12444-3 v10

Open or short circuited current transformer cores can cause unwanted operation of many protection
functions such as differential, earth-fault current and negative-sequence current functions.

Current circuit supervision (CCSSPVC) compares the residual current from a three phase set of
current transformer cores with the neutral point current on a separate input taken from another set of
cores on the current transformer.

A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection
functions expected to give inadvertent tripping.

10.1.3 Function block M12436-3 v9

CCSSPVC
I3P* FAIL
IREF* ALARM
BLOCK
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US

Figure 143: CCSSPVC function block

Signal ISIREF must be connected in the configuration.

10.1.4 Signals
PID-6806-INPUTSIGNALS v2

Table 194: CCSSPVC Input signals

Name Type Default Description


I3P GROUP - Group signal for three phase current input
SIGNAL
IREF GROUP - Residual reference current input
SIGNAL
BLOCK BOOLEAN 0 Block of function

Transformer protection RET650 283


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

PID-6806-OUTPUTSIGNALS v2

Table 195: CCSSPVC Output signals

Name Type Description


FAIL BOOLEAN Detection of current circuit failure
ALARM BOOLEAN Alarm for current circuit failure

10.1.5 Settings
PID-6806-SETTINGS v2

Table 196: CCSSPVC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IMinOp 10 - 200 %IB 1 20 Minimum operate current differential level
in % of IBase

Table 197: CCSSPVC Group settings (advanced)

Name Values (Range) Unit Step Default Description


Ip>Block 20 - 500 %IB 1 150 Block of the function at high phase
current, in % of IBase

Table 198: CCSSPVC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

10.1.6 Operation principle M12396-5 v10

Current circuit supervision CCSSPVC compares the absolute value of the vectorial sum of the three
phase currents |ΣIphase| and the absolute value of the residual current |Iref| from another current
transformer set, see figure 144.

The FAIL output will be set to high when the following criteria are fulfilled:

• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the numerical value
of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the set operate
value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSSPVC is enabled by setting Operation = On.

The FAIL output remains activated 100 ms after the AND-gate resets when being activated for more
than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be issued. In this case the FAIL
and ALARM will remain activated 1 s after the AND-gate resets. This prevents unwanted resetting of
the blocking function when phase current supervision element(s) operate, for example, during a fault.

284 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

IL1 IL1 I>1.054 * IMinOp


IL2 IL2 +
IL3 IL3  -
+ +
I ref Iref + x -
0,8
I>IP>Block
10 ms AND
OR FAIL
OR t

40 ms 100 ms

170 ms 3000 ms ALARM


OPERATION
BLOCK

IEC05000463-3-en.vsd
IEC05000463 V3 EN-US

Figure 144: Simplified logic diagram for Current circuit supervision CCSSPVC
The operate characteristic is percentage restrained, which is shown in Figure 145.

| åI phase | - | I ref |

Slope = 1

Operation
Slope = 0.8
area
I MinOp

| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN-US

Figure 145: Operate characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I phase | + | I ref |
respectively, the slope can not be above 1.

10.1.7 Technical data


M12358-1 v11

Table 199: CCSSPVC technical data

Function Range or value Accuracy


Operate current (10-200)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio, Operate current >90%
Block current (20-500)% of IBase ±5.0% of Ir at I ≤ Ir
±5.0% of I at I > Ir
Reset ratio, Block current >90% at (50-500)% of IBase

Transformer protection RET650 285


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.2 Fuse failure supervision FUFSPVC IP14556-1 v3

10.2.1 Identification
M14869-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fuse failure supervision FUFSPVC - -

10.2.2 Functionality SEMOD113820-4 v13

The aim of the fuse failure supervision function (FUFSPVC) is to block voltage measuring functions
at failures in the secondary circuits between the voltage transformer and the IED in order to avoid
inadvertent operations that otherwise might occur.

The fuse failure supervision function basically has three different detection methods, negative
sequence and zero sequence based detection and an additional delta voltage and delta current
detection.

A criterion based on delta current and delta voltage measurements can be added to the fuse failure
supervision function in order to detect a three phase fuse failure, which in practice is more associated
with voltage transformer switching during station operations.

10.2.3 Function block M13678-3 v9

FUFSPVC
I3P* BLKZ
U3P* BLKU
BLOCK 3PH
CBCLOSED DLD1PH
MCBOP DLD3PH
DISCPOS STDI
BLKTRIP STDIL1
STDIL2
STDIL3
STDU
STDUL1
STDUL2
STDUL3

IEC14000065-1-en.vsd
IEC14000065 V1 EN-US

Figure 146: FUFSPVC function block

10.2.4 Signals
PID-3492-INPUTSIGNALS v9

Table 200: FUFSPVC Input signals

Name Type Default Description


I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
CBCLOSED BOOLEAN 0 Active when circuit breaker is closed
Table continues on next page

286 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Name Type Default Description


MCBOP BOOLEAN 0 Active when external MCB opens protected voltage circuit
DISCPOS BOOLEAN 0 Active when line disconnector is open
BLKTRIP BOOLEAN 0 Blocks operation of function when active

PID-3492-OUTPUTSIGNALS v9

Table 201: FUFSPVC Output signals

Name Type Description


BLKZ BOOLEAN Start of current and voltage controlled function
BLKU BOOLEAN General start of function
3PH BOOLEAN Three-phase start of function
DLD1PH BOOLEAN Dead line condition in at least one phase
DLD3PH BOOLEAN Dead line condition in all three phases
STDI BOOLEAN Common start signal of sudden change in current
STDIL1 BOOLEAN Start signal of sudden change in current, phase L1
STDIL2 BOOLEAN Start signal of sudden change in current, phase L2
STDIL3 BOOLEAN Start signal of sudden change in current, phase L3
STDU BOOLEAN Common start signal of sudden change in voltage
STDUL1 BOOLEAN Start signal of sudden change in voltage, phase L1
STDUL2 BOOLEAN Start signal of sudden change in voltage, phase L2
STDUL3 BOOLEAN Start signal of sudden change in voltage, phase L3

10.2.5 Settings
PID-3492-SETTINGS v9

Table 202: FUFSPVC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OpMode Off - - UZsIZs Operating mode selection
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltage
element in % of UBase
3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrent
element in % of IBase
3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltage
element in % of UBase
3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrent
element in % of IBase
OpDUDI Off - - Off Operation of change based function
On Off/On
DU> 1 - 100 %UB 1 60 Operate level of change in phase voltage
in % of UBase
DI< 1 - 100 %IB 1 15 Operate level of change in phase current
in % of IBase
UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of
UBase
Table continues on next page

Transformer protection RET650 287


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

Name Values (Range) Unit Step Default Description


IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of
IBase
SealIn Off - - On Seal in functionality Off/On
On
USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage in
% of UBase
IDLD< 1 - 100 %IB 1 5 Operate level for open phase current
detection in % of IBase
UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltage
detection in % of UBase

Table 203: FUFSPVC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

10.2.6 Monitored data


PID-3492-MONITOREDDATA v8

Table 204: FUFSPVC Monitored data

Name Type Values (Range) Unit Description


3I0 REAL - A Magnitude of zero sequence current
3I2 REAL - A Magnitude of negative sequence current
3U0 REAL - kV Magnitude of zero sequence voltage
3U2 REAL - kV Magnitude of negative sequence voltage

10.2.7 Operation principle

10.2.7.1 Zero and negative sequence detection M13677-3 v5

The zero and negative sequence function continuously measures the currents and voltages in all
three phases and calculates, see figure 147:

• the zero-sequence voltage 3U0


• the zero-sequence current 3I0
• the negative sequence current 3I2
• the negative sequence voltage 3U2

The measured signals are compared with their respective set values 3U0> and 3I0<, 3U2> and 3I2<.

The function enable the internal signal FuseFailDetZeroSeq if the measured zero-sequence voltage
is higher than the set value 3U0> and the measured zero-sequence current is below the set value
3I0<.

The function enable the internal signal FuseFailDetNegSeq if the measured negative sequence
voltage is higher than the set value 3U2> and the measured negative sequence current is below the
set value 3I2<.

A drop out delay of 100 ms for the measured zero-sequence and negative sequence current will
prevent a false fuse failure detection at un-equal breaker opening at the two line ends.

288 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq

Negative
sequence a 3U2
a>b
UL3 filter b

3U2>

IEC10000036-2-en.vsd
IEC10000036 V2 EN-US

Figure 147: Simplified logic diagram for sequence detection part


The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local HMI and
monitoring tool in PCM600.

Input and output signals M13677-19 v6


The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and DLD3PH from dead
line detections are blocked if any of the following conditions occur:

• The input BLOCK is activated


• The input BLKTRIP is activated and the internal signal FuseFailStarted is not present
• The operation mode selector OpMode is set to Off
• The IED is in TEST status (TEST-ACTIVE is high) and the function has been blocked from the
HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure supervision function.
It can be connected to a binary input of the IED in order to receive a block command from external
devices or can be software connected to other internal functions of the IED itself in order to receive a
block command from internal functions. Through OR gate it can be connected to both binary inputs
and internal function outputs.

The input BLKTRIP is intended to be connected to the trip output from any of the protection functions
included in the IED. When activated for more than 20 ms, the operation of the fuse failure is blocked;
a fixed drop-out timer prolongs the block for 100 ms. The aim is to increase the security against
unwanted operations during the opening of the breaker, which might cause unbalance conditions for
which the fuse failure might operate.

The output signal BLKZ will also be blocked if the internal dead line detection is activated. The dead
line detection signal has a 200 ms drop-out time delay.

The input signal MCBOP is supposed to be connected via a terminal binary input to the N.C. auxiliary
contact of the miniature circuit breaker protecting the VT secondary circuit. The MCBOP signal sets
the output signals BLKU and BLKZ in order to block all the voltage related functions when the MCB is
open independent of the setting of OpMode selector. The additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of voltage dependent
function due to non simultaneous closing of the main contacts of the miniature circuit breaker.

Transformer protection RET650 289


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in order
to block the voltage related functions when the line disconnector is open. The impedance protection
function is not affected by the position of the line disconnector since there will be no line currents that
can cause malfunction of the distance protection. If DISCPOS=0 it signifies that the line is connected
to the system and when the DISCPOS=1 it signifies that the line is disconnected from the system
and the block signal BLKU is generated.

The output BLKU can be used for blocking the voltage related measuring functions (undervoltage
protection, energizing check and so on) except for the impedance protection.

The function output BLKZ shall be used for blocking the impedance protection function.

10.2.7.2 Delta current and delta voltage detection M13685-3 v8

A simplified diagram for the functionality is found in figure 148. The calculation of the changes of
currents and voltages is based on a sample analysis algorithm. The calculated delta quantities are
compared with their respective set values DI< and DU>. The algorithm detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in each phase
separately. The following quantities are calculated in all three phases:

• The change in voltage DU


• The change in current DI

The internal FuseFailDetDUDI signal is activated if the following conditions are fulfilled:

• The magnitude of the phase-ground voltage has been above UPh> for more than 1.5 cycles (i.e.
30 ms in a 50 Hz system)
• The magnitudes of DU in three phases are higher than the corresponding setting DU>
• The magnitudes of DI in three phases are below the setting DI<
• The magnitude of voltages drop in all three phases
• The zero sequence voltage is smaller than 3U0>

In addition to the above conditions, at least one of the following conditions shall be fulfilled in order to
activate the internal FuseFailDetDUDI signal:

• The magnitude of the phase currents in three phases are higher than the setting IPh>
• The circuit breaker is closed (CBCLOSED = True)

The first criterion means that detection of failure in three phases together with high current for the
three phases will set the output. The measured phase current is used to reduce the risk of false fuse
failure detection. If the current on the protected line is low, a voltage drop in the system (not caused
by fuse failure) may be followed by current change lower than the setting DI<, and therefore a false
fuse failure might occur.

The second criterion requires that the delta condition shall be fulfilled at the same time as circuit
breaker is closed. If CBCLOSED input is connected to FALSE , then only the first criterion can enable
the delta function. If the DUDI detections of three phases set the internal signal FuseFailDetDUDI at
the level high, then the signal FuseFailDetDUDI will remain high as long as the voltages of three
phases are lower then the setting Uph>.

In addition to fuse failure detection, two internal signals DeltaU and DeltaI are also generated by the
delta current and delta voltage DUDI detection algorithm. The internal signals DelatU and DeltaI are
activated when a sudden change of voltage, or respectively current, is detected. The detection of the
sudden change is based on a sample analysis algorithm. In particular DelatU is activated if at least
three consecutive voltage samples are higher then the setting DU>. In a similar way DelatI is
activated if at least three consecutive current samples are higher then the setting DI<. When DeltaU
or DeltaI are active, the output signals STDUL1, STDUL2, STDUL3 and respectively STDIL1,
STDIL2, STDIL3, based on a sudden change of voltage or current detection, are activated with a 20
ms time off delay. The common start output signals STDU or STDI are activated with a 60 ms time off
delay, if any sudden change of voltage or current is detected.

290 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

The delta function (except the sudden change of voltage and current detection) is
deactivated by setting the parameter OpDUDI to Off.

DUDI Detection
DUDI detection Phase 1
DeltaIL1
IL1
IL2
IL3 DI detection based on sample analysis OR

DI<

UL1

DU detection based on sample analysis


AND
DU>
1.5 cycle 20 ms DeltaUL1
a
a>b t t
UPh> b

IL1 DeltaIL2
IL2 DUDI detection Phase 2
DeltaUL2
IL3
UL2 Same logic as for phase 1

IL1 DeltaIL3
DUDI detection Phase 3
IL2
DeltaUL3
IL3
UL3 Same logic as for phase 1

UL1
a
a<b
b

IL1
a
a>b
IPh> b AND

OR AND
CBCLOSED AND OR

UL2
a
a<b
b

IL2
a
a>b
b AND

OR AND
AND OR

UL3
a
a<b
b

IL3
a
a>b
b AND

OR AND
AND OR FuseFailDetDUDI
AND

IEC12000166-3-en.vsd

IEC12000166 V3 EN-US

Figure 148: Simplified logic diagram for the DU/DI detection part

Transformer protection RET650 291


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

intBlock
STDI
AND

20 ms
DeltaIL1 STDIL1
t AND
OR
20 ms
DeltaIL2
t STDIL2
AND
20 ms
DeltaIL3
t
STDIL3
AND

STDU
AND

20 ms
DeltaUL1 STDUL1
t AND
OR
20 ms
DeltaUL2
t STDUL2
AND
20 ms
DeltaUL3
t
STDUL3
AND

IEC12000165-1-en.vsd
IEC12000165 V1 EN-US

Figure 149: Internal signals DeltaU or DeltaI and the corresponding output signals

10.2.7.3 Dead line detection M13679-44 v4

A simplified diagram for the functionality is found in figure 150. A dead phase condition is indicated if
both the voltage and the current in one phase is below their respective setting values UDLD< and
IDLD<. If at least one phase is considered to be dead the output DLD1PH and the internal signal
DeadLineDet1Ph is activated. If all three phases are considered to be dead the output DLD3PH is
activated

292 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Dead Line Detection


IL1
a
a<b AllCurrLow
b
AND
IL2
a
a<b
b

IL3
a
a<b
b

IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b

UDLD<

intBlock

IEC10000035-1-en.vsd
IEC10000035 V2 EN-US

Figure 150: Simplified logic diagram for Dead Line detection part

10.2.7.4 Main logic GUID-D474A49E-D3A8-438C-B7E4-E527FEC2F335 v6

A simplified diagram for the functionality is found in figure 151. The fuse failure supervision function
(FUFSPVC) can be switched on or off by the setting parameter Operation to On or Off.

For increased flexibility and adaptation to system requirements an operation mode selector, OpMode,
has been introduced to make it possible to select different operating modes for the negative and zero
sequence based algorithms. The different operation modes are:

• Off. The negative and zero sequence function is switched off.


• UNsINs. Negative sequence is selected.
• UZsIZs. Zero sequence is selected.
• UZsIZs OR UNsINs. Both negative and zero sequence are activated and work in parallel (OR-
condition for operation).
• UZsIZs AND UNsINs. Both negative and zero sequence are activated and work in series (AND-
condition for operation).
• OptimZsNs. Optimum of negative and zero sequence current (the function that has the highest
magnitude of measured negative and zero sequence current will be activated).

The delta function can be activated by setting the parameter OpDUDI to On. When selected it
operates in parallel with the sequence based algorithms.

As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq, FuseFailDetNegSeq


or FuseFailDetDUDI, and the specific functionality is released, the function will activate the output
signal BLKU. The output signal BLKZ will be activated as well if the internal dead phase detection,
DeadLineDet1Ph, is not activated at the same time. The output BLKU can be used for blocking
voltage related measuring functions (under voltage protection, energizing check, and so on). The
output BLKZ shall be used to block the impedance protection functions.

If the fuse failure situation is present for more than 5 seconds and the setting parameter SealIn is set
to On it will be sealed in as long as at least one phase voltages is below the set value USealIn<. This
will keep the BLKU and BLKZ signals activated as long as any phase voltage is below the set value
USealIn<. If all three phase voltages drop below the set value USealIn< and the setting parameter

Transformer protection RET650 293


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

SealIn is set to On the output signal 3PH will also be activated. The signals 3PH, BLKU and BLKZ
will now be active as long as any phase voltage is below the set value USealIn<.

If SealIn is set to On the fuse failure condition lasting more then 5 seconds is stored in the non-
volatile memory in the IED. At start-up of the IED (due to auxiliary power interruption or re-start due
to configuration change) it uses the stored value in its non-volatile memory and re-establishes the
conditions that were present before the shut down. All phase voltages must be restored above
USealIn< before fuse failure is de-activated and resets the signals BLKU, BLKZ and 3PH.

The output signal BLKU will also be active if all phase voltages have been above the setting
USealIn< for more than 60 seconds, the zero or negative sequence voltage has been above the set
value 3U0> and 3U2> for more than 5 seconds, all phase currents are below the setting IDLD<
(criteria for open phase detection) and the circuit breaker is closed (input CBCLOSED is activated).

If a MCB is used then the input signal MCBOP is to be connected via a binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The MCBOP
signal sets the output signals BLKU and BLKZ in order to block all the voltage related functions when
the MCB is open independent of the setting of OpMode or OpDUDI. An additional drop-out timer of
150 ms prolongs the presence of MCBOP signal to prevent the unwanted operation of voltage
dependent function due to non simultaneous closing of the main contacts of the miniature circuit
breaker.

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in order
to block the voltage related functions when the line disconnector is open. The impedance protection
function does not have to be affected since there will be no line currents that can cause malfunction
of the distance protection.

294 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Fuse failure detection


Main logic
TEST

TEST ACTIVE
AND
BlocFuse = Yes

BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
FusefailStarted

All UL < USealIn<


OR
AND
3PH
AND
SealIn = On AND

AND
Any UL < UsealIn<

FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND

AND

FuseFailDetNegSeq
AND

UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b

AND

DeadLineDet1Ph 200 ms
AND BLKZ
t OR AND
150 ms
MCBOP t

AND BLKU
60 s
t OR OR
All UL > UsealIn<
AND

VoltZeroSeq 5s
VoltNegSeq OR t

AllCurrLow
CBCLOSED

DISCPOS IEC10000033-2-en.vsd

IEC10000033 V2 EN-US

Figure 151: Simplified logic diagram for fuse failure supervision function, Main logic

Transformer protection RET650 295


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.2.8 Technical data


M16069-1 v13

Table 205: FUFSPVC technical data

Function Range or value Accuracy


Operate voltage, zero sequence ±0.5% of Ur
Operate current, zero sequence ±0.5% of Ir
Operate voltage, negative sequence ±0.5% of Ur
Operate current, negative sequence ±0.5% of Ir
Operate voltage change level ±10.0% of Ur
Operate current change level ±10.0% of Ir
Operate phase voltage ±0.5% of Ur
Operate phase current ±0.5% of Ir
Operate phase dead line voltage ±0.5% of Ur
Operate phase dead line current
Operate time, start, 1 ph, at 1 x Ur to 0 Min. = 10 ms -
Max. = 25 ms
Reset time, start, 1 ph, at 0 to 1 x Ur Min. = 15 ms -
Max. = 30 ms

10.3 Voltage based delta supervision DELVSPVC GUID-579ED249-B8C9-4755-9E80-28E2BA8E5377 v2

10.3.1 Identification
GUID-C7108931-DECA-4397-BCAF-8BFF3B57B4EF v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Voltage based delta supervision DELVSPVC – 7V_78V

10.3.2 Functionality GUID-6188C4C1-E1D5-421A-B496-96676287EBB2 v2

Delta supervision function is used to quickly detect (sudden) changes in the network. This can, for
example, be used to detect faults in the power system networks and islanding in grid networks.
Voltage based delta supervision (DELVSPVC) is needed at the grid interconnection point.

296 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

10.3.3 Function block GUID-06FEC7EF-B37E-4D42-99DA-868453E6FDBF v2

DELVSPVC
U3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
DELMAGL1
DELMAGL2
DELMAGL3

IEC18000007‐1‐en.vsdx
IEC18000007 V1 EN-US

Figure 152: DELVSPVC function block

10.3.4 Signals
PID-7097-INPUTSIGNALS v1

Table 206: DELVSPVC Input signals

Name Type Default Description


U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-7097-OUTPUTSIGNALS v1

Table 207: DELVSPVC Output signals

Name Type Description


START BOOLEAN General start of function
STARTL1 BOOLEAN Start of L1
STARTL2 BOOLEAN Start of L2
STARTL3 BOOLEAN Start of L3
STRISE BOOLEAN Common rise signal when input has increased
STRISEL1 BOOLEAN L1/L12 delta value increased
STRISEL2 BOOLEAN L2/L23 delta value increased
STRISEL3 BOOLEAN L3/L31 delta value increased
STLOW BOOLEAN Common low signal when input has decreased
STLOWL1 BOOLEAN L1/L12 delta value decreased
STLOWL2 BOOLEAN L2/L23 delta value decreased
STLOWL3 BOOLEAN L3/L31 delta value decreased
DELMAGL1 REAL Delta magnitude of L1 / L12
DELMAGL2 REAL Delta magnitude of L2 / L23
DELMAGL3 REAL Delta magnitude of L3 / L31

Transformer protection RET650 297


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.3.5 Settings
PID-7097-SETTINGS v1

Table 208: DELVSPVC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
OpMode Instantaneous 1 - - DFT mag Operation mode
cycle
Instantaneous 2
cycle
RMS
DFT mag
DFT Angle (Vector
shift)
MeasMode Phase to phase - - Phase to ground Measurement type: Phase to ground /
Phase to ground Phase to phase

Table 209: DELVSPVC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
UMin 1.0 - 50.0 %UB 0.1 5.0 Minimum start value of voltage for release
of delta function
DeltaT 1 - 10 cycle 1 2 Number of old power cycles for delta
calculation
DelU> 2.0 - 500.0 %UB 0.1 40.0 Magnitude start level for magnitude, RMS
and sample based delta comparison
DelUAng> 2.0 - 40.0 Deg 1.0 8.0 Start level for angle based delta detection
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal

10.3.6 Monitored data


PID-7097-MONITOREDDATA v1

Table 210: DELVSPVC Monitored data

Name Type Values (Range) Unit Description


UL1 REAL - kV RMS magnitude of L1 /L12
UL2 REAL - kV RMS magnitude of L2 /L23
UL3 REAL - kV RMS magnitude of L3 /L31

10.3.7 Operation principle GUID-7F65AD13-1F0E-402A-8B9C-3B1D6ED0D2BB v3

The delta supervision function DELVSPVC is a phase segregated function with the following
features.

• Check of the minimum signal level


• Five different modes of operation
• Frequency stabilization for angle shift

The general design of DELVSPVC is shown in Figure 153:

298 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

opMode = Instantaneous 1cycle/2 cycle


Sample delta STARTSAMPLE
U3P calculation
opMode = DFTAngle
Frequency
estimation and Frequency stabilization STARTANGLE
angle shift based on 2 cycle old
calculation frequency
1 START
AND

Signal pre‐processing
  fundamental DFT
opMode= RMS/DFTMag
  harmonic extraction
Magnitude based STARTMAG
delta calculation DELMAGLx

MinValueCheck AND

BLOCK
IEC18000008-1-en.vsdx
IEC18000008 V1 EN-US

Figure 153: Simplified logic diagram for voltage based delta supervision DELVSPVC

10.3.7.1 Minimum signal level check GUID-FE5377C8-E4CF-43D3-B1EC-C886E76377A6 v2

The setting Umin is used to check and release the signals for the delta supervision. The delta
detection is blocked for 2 cycles by Umin comparator for angle shift mode.

10.3.7.2 Mode of operation GUID-B4EDA716-DB28-422A-88E3-F41D5D7BB6A4 v3

DELVSPVC can be selected for phase-to-ground or phase-to-phase measurements using the


MeasMode setting. If the setting is selected as phase-to-phase, then outputs with L1 and L2 will
represent L12, L23, and L31 phase-to-phase quantities, respectively. Following are the modes of
operations for the OpMode setting:

• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag
• Vector Shift

These modes of operation are explained in following sections.

10.3.7.3 Instantaneous 1 cycle / 2 cycle GUID-BAF266E2-A0A0-4848-9DFB-776C197B4A7F v2

This method uses the instantaneous samples for delta detection. The logic of this scheme is shown
in Figure 154. The instantaneous difference between the present sample and the one cycle (or two
cycle) old sample is used for the delta detection. The change (delta) is verified for three continuous
samples in order to release the start signal. Once the start signal is set, any subsequent change in
sample values within 60 ms will not be detected. The DELU> setting will be set in % of UB. The
sample based delta is selectable for one cycle/two cycle operation, based on the OpMode setting.

Old value buffer


Voltage sample input
  1 cycle /
  2 cycle

‐ Abs
60ms
>
StartSampleDelta
AND t

DelU>
q‐1

q‐1

IEC17000199-2-en.vsdx

IEC17000199 V2 EN-US

Figure 154: Simplified logic diagram for sample based delta detection

Transformer protection RET650 299


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.3.7.4 RMS/DFT based supervision GUID-B299BE6C-AD89-4DFE-AFFC-E3DD252A260A v2

This mode uses the RMS or DFT magnitude value of the voltage signal for the delta detection. The
logic of this scheme is given in Figure 155. Difference between the present value and the old value is
used for the delta detection. The old value is chosen based on the setting DeltaT, which is defined as
the number of old power cycles.

The function has an execution cycle time of 3 ms. For a DeltaT setting of 3, the old value
is 60 ms. Therefore, accuracy of the old cycle data depends upon the execution cycle.

The output of the comarator is ascertained for half a cycle before releasing a STARTMAG signal. In
DELVSPVC, the DelU> setting is set in % of UB. RMS based delta will have poor accuracy if the
signal contains harmonics and other frequency components. DFT Mag based delta will operate better
in these conditions.

Additional information for the STARTRISE and STARTLOW outputs of the delta are also available in
this mode. The STARTRISE and STARTLOW outputs will be sealed by the start signal. These
outputs explains the reason for the STARTMAG signal.

Seal‐in STARTLOW
logic

0.1
>

RMS input / Seal‐in STARTRISE


> logic
DFT mag Delay defined by ‐0.1
DeltaT
0. 3 cycle
‐ Abs
> t
DelU>

IEC17000200-2-en.vdsx

IEC17000200 V2 EN-US

Figure 155: Simplified logic diagram for RMS/DFT based delta detection

10.3.7.5 Angle based supervision or vector shift supervision GUID-26960EA3-233A-4B76-8C11-245334012C76 v3

The Vector shift selection in the OpMode setting is used to set the DELVSPVC function to operate. A
change in magnitude will not have any impact on this supervision. Angle shift is measured based on
the half cycle time (HCTime) as shown in Figure 156. The figure shows a waveform shift of 40
degree in the voltage waveform. There are two half cycle times which are affected by this angle shift
namely, HCTime(k-1) and HCTime(k). A cumulative difference of two HCTime difference is calculated
to get an accurate estimate of the angle shift. This angle shift is compared with DelUang> setting to
release the STARTANGLE signal.

The logic for this mode is given in Figure 157. The DelUAng> setting will be set in absolute degrees.

300 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

Voltage

Angle shift= [{Hctime(k) ‐ Hctime(k‐2)} + {Hctime(k‐1) ‐ Hctime(k‐3)}]

Angle shift

HC time (k‐3) HC time (k‐2) HC time (k‐1) HC time (k)


Time

IEC17000210-1-en.vsdx
IEC17000210 V1 EN-US

Figure 156: Angle shift


Angle measurement is affected by system parameters such as frequency, load or generation. Hence,
a stabilization of the angle is also present in this mode of operation. The measured frequency is
compared with the 2 cycles old value. If the change is greater than 0.2 Hz, the STARTANGLE signal
is blocked. The output will release Angle shift mode when the measured frequency difference is
continuously less than 0.2 Hz for 2 cycles. The general logic is presented in Figure 157. In this mode
STLOW, STRISE, STLOWLx and STRISELx outputs will not be used and set as FALSE.

ULx Angle shift


calculation
0.5 cycle
Abs Delta Angle
> t

DelUang> STARTANGLE
Frequency difference of last 2 cycles AND
> AND
0.2 Hz

IEC18000902-1-en.vsdx

IEC18000902 V1 EN-US

Figure 157: Simplified logic diagram for angle based delta detection

Transformer protection RET650 301


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.3.8 Technical data


GUID-DAECF9F5-1D0B-43FC-AD29-8F96E05DD0DA v4

Table 211: DELVSPVC technical data

Function Range or value Accuracy


Minimum Voltage (5.0 - 50.0)% of UBase ±0.5% of Ur at U ≤ Ur
DelU> (2.0 - 500.0)% of UBase Instantaneous 1 cycle &
Instantaneous 2 cycle mode:
±20% of Ur at U ≤ Ur±20% of U at
U > Ur
RMS & DFT Mag mode:±10% of
Ur at U ≤ Ur±10% of U at U > Ur
DelUAng> (2.0 - 40.0) degrees ±2.0 degrees
Operate time for changeat Ur to (Ur + 2 x DelU>)at Ur Instantaneous 1 cycle &
to (Ur + 5 x DelU>) Instantaneous 2 cycle mode -
<20msRMS & DFT Mag mode -
<30ms
Operate time for jump from Zero degrees to Vector shift mode - <60ms
'AngStVal' + 2 degrees

10.4 Current based delta supervision DELISPVC GUID-4F012876-FA0A-4A97-9E23-387974304CED v2

10.4.1 Identification
GUID-0B735A27-6A7D-40E1-B981-91B689608495 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current based delta supervision DELISPVC – 7I < >

10.4.2 Functionality GUID-30A00AE0-8D3A-4CE8-9379-8D1A0A6078E3 v2

Delta supervision function is used to quickly detect (sudden) changes in the network. This can, for
example, be used to detect disturbances in the power system network. Current based delta
supervision (DELISPVC) provides selectivity between load change and the fault.

Present power system has many power electronic devices or FACTS devices, which injects a large
number of harmonics into the system. The function has additional features of 2nd harmonic blocking
and 3rd harmonic start level adaption. The 2nd harmonic blocking secures the operation during the
transformer charging, when high inrush currents are supplied into the system.

302 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

10.4.3 Function block GUID-D1467592-DD2D-488F-94CA-66BD0FA57A8D v2

DELISPVC
I3P* START
BLOCK STARTL1
STARTL2
STARTL3
STRISE
STRISEL1
STRISEL2
STRISEL3
STLOW
STLOWL1
STLOWL2
STLOWL3
ADAPTVAL
HARM2BLK
DELMAGL1
DELMAGL2
DELMAGL3
IEC18000005-1-en.vsdx
IEC18000005 V1 EN-US

Figure 158: DELISPVC function block

10.4.4 Signals
PID-7098-INPUTSIGNALS v1

Table 212: DELISPVC Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function

PID-7098-OUTPUTSIGNALS v1

Table 213: DELISPVC Output signals

Name Type Description


START BOOLEAN General start of function
STARTL1 BOOLEAN Start of L1
STARTL2 BOOLEAN Start of L2
STARTL3 BOOLEAN Start of L3
STRISE BOOLEAN Common rise signal when input has increased
STRISEL1 BOOLEAN L1/L12 delta value increased
STRISEL2 BOOLEAN L2/L23 delta value increased
STRISEL3 BOOLEAN L3/L31 delta value increased
STLOW BOOLEAN Common low signal when input has decreased
STLOWL1 BOOLEAN L1/L12 delta value decreased
STLOWL2 BOOLEAN L2/L23 delta value decreased
STLOWL3 BOOLEAN L3/L31 delta value decreased
ADAPTVAL BOOLEAN Delta start level changed by 3rd harmonic
HARM2BLK BOOLEAN 2nd harmonic blocking active
DELMAGL1 REAL Delta magnitude of L1 / L12
DELMAGL2 REAL Delta magnitude of L2 / L23
DELMAGL3 REAL Delta magnitude of L3 / L31

Transformer protection RET650 303


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.4.5 Settings
PID-7098-SETTINGS v1

Table 214: DELISPVC Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
OpMode Instantaneous 1 - - DFT mag Operation mode
cycle
Instantaneous 2
cycle
RMS
DFT mag
MeasMode Phase to phase - - Phase to ground Measurement type: Phase to ground /
Phase to ground Phase to phase

Table 215: DELISPVC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
IMin 1.0 - 50.0 %IB 0.1 10.0 Minimum current start value for release of
delta function
DeltaT 1 - 10 cycle 1 2 Number of old power cycles for delta
calculation
DelI> 2.0 - 500.0 %IB 0.1 40.0 Magnitude start level for magnitude, RMS
and sample based delta comparison
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal
EnaHarm2Blk Off - - Off Enable 2nd harmonic blocking
On
HarmBlkLevel 5.0 - 100.0 % 0.1 15.0 Harmonic blocking level for 2nd harmonic
in % of fundamental
EnStValAdap Off - - Off Enable set level setting adaption based
On on 3rd harmonic
Harm3Level 5.0 - 100.0 % 0.1 15.0 3rd Harmonic level in % of fundamental
for enabling adaptive start value
StValGrad -90.00 - 500.00 % 0.10 -10.00 Gradient for adapting magnitude set level
during 3rd harmonic in % of DelI>

10.4.6 Monitored data


PID-7098-MONITOREDDATA v1

Table 216: DELISPVC Monitored data

Name Type Values (Range) Unit Description


IL1 REAL - A RMS magnitude of L1 /L12
IL2 REAL - A RMS magnitude of L2 /L23
IL3 REAL - A RMS magnitude of L3 /L31

10.4.7 Operation principle GUID-27E7C6C8-83B1-4CA6-9B4E-38FDED3FD360 v2

The delta supervision function is a phase segregated function. Following are the features of
DELISPVC:

304 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

• Check of the minimum signal level


• Four different modes of operation
• 2nd harmonic blocking of delta function
• 3rd harmonic based adaption of starting value

The general design of DELISPVC is shown in Figure 159:

opMode = Instantaneous 1cycle/2 cycle


I3P Sample delta STARTSAMPLE
calculation
1 AND START

Signal pre‐processing
  fundamental DFT
opMode= RMS/DFTMag
  harmonic extraction
Magnitude based STARTMAG
delta calculation DELMAGLx
DFTMagToComp
rd
3 harmonic based ADAPTVAL
adaption nd HARM2BLK
2 harmonic
blocking
AND
MinValueCheck

BLOCK
IEC18000006-1-en.vsdx
IEC18000006 V1 EN-US

Figure 159: Simplified logic diagram for current based delta supervision DELISPVC

10.4.7.1 Minimum signal level check GUID-5E5503ED-1A61-4927-86F0-6ABDC7E2AA2B v3

The setting Imin is used to check and release the signals for the delta supervision. This setting can
be used to obtain selectivity between load current and fault current.

10.4.7.2 Mode of operation GUID-2B87BAB6-A0D4-4A3D-8116-88F1598C1AC6 v2

DELISPVC can be selected for phase-to-ground or phase-to-phase measurements using the


MeasMode setting. If the setting is selected as phase-to-phase, then outputs with L1 will represent
L12 phase-to-phase quantities and so on. Following are the modes of operations for the OpMode
setting:

• Instantaneous 1 cycle
• Instantaneous 2 cycle
• True RMS
• DFT mag

These modes of operation are explained in following sections.

10.4.7.3 Instantaneous 1 cycle / 2 cycle GUID-4FD743D6-DB93-4C76-819D-E81C562B762A v2

This method uses the buffer of instantaneous sample for delta detection. The logic of this scheme is
given in Figure 160. The instantaneous difference between the present sample and the one cycle (or
two cycle) old sample is used for the delta detection. The change (vectorial delta) is verified for three
continuous samples in order to release the start signal. This delta calculation is affected by angle or
magnitude or both changes in the signal in the last one cycle/two cycle. It is also known as vectorial
delta scheme. Once the start signal is set, any subsequent change in sample values within 60 ms will
not be detected. The DelI> setting will be set in % of IB. The sample based delta is selectable for one
cycle/two cycle operation, based on the OpMode setting.

Transformer protection RET650 305


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

Old value buffer


Current Samples   1 cycle /
  2 cycle


60ms
Abs
> AND
StartSampleDelta
t

DelI>
q‐1

q‐1

IEC17000191-2-en.vsdx

IEC17000191 V2 EN-US

Figure 160: Simplified logic diagram for sample based delta detection

10.4.7.4 RMS/DFT based supervision GUID-427A82EF-1BB6-45C5-BAEB-2DF50A9D99BD v2

This mode uses the RMS or DFT magnitude value of the current signal for the delta detection. The
logic of this scheme is given in Figure 161. Difference between the present value and the old value is
used for the delta detection. The old value is chosen based on the setting DeltaT, which is defined as
the number of old power cycles.

The function has an execution cycle of 3 ms. For a DeltaT setting of 3, the old value is 60
ms. Therefore, accuracy of the old cycle data depends upon the execution cycle.

The output of the comparator is ascertained for half a cycle before releasing a STARTMAG signal. In
DELISPVC, the DelI> setting is set in % of IB.

Additional information for the STARTRISE and STARTLOW outputs of the delta are also available in
this mode. The STARTRISE and STARTLOW outputs will be sealed by the start signal. These
outputs explains the reason for the STARTMAG signal.

Seal‐in STARTLOW
logic

0.1
>

Seal‐in STARTRISE
> logic
RMS Input Delay defined by ‐0.1
DeltaT
0. 5 cycle
‐ Abs STARTMAG
> t
DelI>

IEC17000192-2-en.vsdx

IEC17000192 V2 EN-US

Figure 161: Simplified logic diagram for RMS based delta detection

10.4.7.5 2nd Harmonic blocking GUID-BE749AFA-992C-44A6-8C12-12BA4D1AA674 v2

Presence of the harmonics is another reason for maloperation of the delta based protection. The 2nd
harmonic blocking is an additional security feature in this function. It can be enabled by the
EnaHarm2Blk setting. If the ratio of 2nd harmonic frequency signal magnitude to the fundamental
frequency magnitude is greater than the set level harmBlkLev, then this feature will block the start
signal of the delta protection. The logic for this functionality is shown in Figure 162. The tON of 1.25
cycle is added to ensure a reliable harmonic blocking. The tOFF of 2 cycles is added to block the
operation during any sudden increase in the current load.

306 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

EnaHarm2Blk
2 cycles
t HARM2BLK
DFTInput‐2ndHarm AND
< 1.25 cycle
t
DFTInput ‐ fundamental
X
HarmBlkLev
IEC17000194-2-en.vsdx

IEC17000194 V2 EN-US

Figure 162: Simplified logic diagram for 2nd harmonic blocking logic

10.4.7.6 3rd Harmonic based adaption GUID-02A00917-EAB6-47F9-8375-643F76AA0D2B v2

Present days power system network has high amount of the 3rd harmonics presence due to heavy
power electronic devices. In such case, many networks modify the settings based on the 3rd
harmonic present in the system. Delta supervision can be adapted based on the 3rd harmonic
present in the signal. When OpMode is set to DFTMag and EnStValAdap is set to is Enable, then the
setting DelI> will change based on the StValGrad setting if the third harmonic is greater than the set
level defined by the Harm3Level setting. The logic for this functionality is shown in Figure 163.

 DelI  New  DelI 1  StValGrad 

DeltaMode = DFTMag

EnStValAdap = Enable/Disable
2 cycle
t ADAPTSTLEV
rd
DFTInput ‐ 3 Harmonics AND
< 1.25 cycle
DFTInput ‐ fundamental t
X
Harm3Lev
StValGrad X T DeltaMagToComp
F
DelI>

IEC17000195-2-en.vsdx
IEC17000195 V2 EN-US

Figure 163: Simplified logic diagram for 3rd harmonic restrain of MagStVal setting
Since this mode is adaptably changing the setting, the tOFF time is mandatory to ensure the reliable
operation during any sudden change.

Transformer protection RET650 307


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

10.4.8 Technical data


GUID-ED3FE722-1F29-4340-94E9-6C907C4474F2 v3

Table 217: DELISPVC technical data

Function Range or value Accuracy


Minimum current (5.0 - 50.0)% of IBase ±1.0% of Ir at I ≤ Ir±1.0% of I at I
> Ir
DelI> (10.0 - 500.0)% of IBase Instantaneous 1 cycle &
Instantaneous 2 cycle mode:
±20% of Ir at I ≤ Ir±20% of I at I >
Ir
RMS & DFT Mag mode:
±10% of Ir at I ≤ Ir±10% of I at I >
Ir
Second harmonic blocking (5.0 - 100.0)% of ±2.0% of Ir
fundamental
Third harmonic restraining (5.0 - 100.0)% of ±2.0% of Ir
fundamental
Operate time for changeat Ir to (Ir + 2 x DelI>)at Ir to Instantaneous 1 cycle &
(Ir + 5 x DelI>) Instantaneous 2 cycle mode -
<20ms
RMS & DFT Mag mode - <30ms

10.5 Delta supervision of real input DELSPVC GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1

10.5.1 Identification
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Delta supervision of real input DELSPVC – –

10.5.2 Functionality GUID-8FAD2CCF-091F-4CDB-8ABF-1BDC874A8403 v2

Delta supervision functions are used to quickly detect (sudden) changes in the power system. Real
input delta supervision (DELSPVC) function is a general delta function. It is used to detect the
change measured qualities over a settable time period, such as:

• Power
• Reactive power
• Temperature
• Frequency
• Power factor

10.5.3 Function block GUID-1472A816-E653-4828-8F03-4B26B93E7EF9 v1

DELSPVC
BLOCK START
INPUT STRISE
STLOW
DELREAL
IEC17000202-1-en.vsdx
IEC17000202 V1 EN-US

Figure 164: DELSPVC function block

308 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 10
Secondary system supervision

10.5.4 Signals
PID-7096-INPUTSIGNALS v1

Table 218: DELSPVC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT REAL 0 Real Input

PID-7096-OUTPUTSIGNALS v1

Table 219: DELSPVC Output signals

Name Type Description


START BOOLEAN Start of function
STRISE BOOLEAN Rise signal when input has increased
STLOW BOOLEAN Low signal when input has decreased
DELREAL REAL Delta value of real input

10.5.5 Settings
PID-7096-SETTINGS v1

Table 220: DELSPVC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
MinStVal 0.1 - 99999.9 - 0.1 1.0 Minimum start value for release of delta
function
DeltaT 6 - 100 cycle 1 10 Number of old execution cycle for delta
calculation
DelSt> 0.1 - 9999999.9 - 0.1 10.0 Delta start level for real input
tHold 0.10 - 60.00 s 0.01 0.10 Hold time for start signal

10.5.6 Operation principle GUID-CA9B38EB-26E4-4286-8517-C5ECDA730236 v1

Delta supervision of real input DELSPVC is a general delta function with the following features:

• Check of the minimum signal level


• Detect an increase or decrease of the measured value

The general design of DELSPVC is shown in Figure 165.

Seal‐in STARTLOW
Logic

>
0.1
Seal‐in STARTRISE
Logic
REALIN Delay defined by >
‐0.1
DeltaT
0. 5 cycle
‐ Abs
> t
DelStLevel
tHold
& t
>
MinStVal

IEC17000203-1-en.vsdx
IEC17000203 V1 EN-US

Figure 165: Simplified logic diagram for DELSPVC

Transformer protection RET650 309


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10 1MRK504170-UEN Rev. J
Secondary system supervision

The setting MinStVal is used to check and release the signals for the delta supervision. In its initial
condition, during the first time a real value signal is detected (ascertained by the MinStVal
comparator), the delta detection is blocked for operation for the next 11 cycles. These 11 cycles are
used to block any unwanted operation during the initialization of the function.

The outputs STARTRISE and STARTLOW are released based on the difference (respectively above
and below) from the old value at the instant when the START signal is released.

310 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Section 11 Control
11.1 Synchrocheck, energizing check, and synchronizing
SESRSYN IP14558-1 v4

11.1.1 Identification
M14889-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Synchrocheck, energizing check, and SESRSYN 25
synchronizing
sc/vc

SYMBOL-M V1 EN-US

11.1.2 Functionality M12480-3 v16

The Synchronizing function allows closing of asynchronous networks at the correct moment including
the breaker closing time, which improves the network stability.

Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks that the voltages
on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that
closing can be done safely.

SESRSYN function includes a built-in voltage selection scheme for double bus and 1½ breaker or
ring busbar arrangements.

Manual closing as well as automatic reclosing can be checked by the function and can have different
settings.

For systems, which can run asynchronously, a synchronizing feature is also provided. The main
purpose of the synchronizing feature is to provide controlled closing of circuit breakers when two
asynchronous systems are in phase and can be connected. The synchronizing feature evaluates
voltage difference, phase angle difference, slip frequency and frequency rate of change before
issuing a controlled closing of the circuit breaker. Breaker closing time is a setting.

Transformer protection RET650 311


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.1.3 Function block M12431-3 v7

SESRSYN
U3PBB1* SYNOK
U3PBB2* AUTOSYOK
U3PLN1* AUTOENOK
U3PLN2* MANSYOK
BLOCK MANENOK
BLKSYNCH TSTSYNOK
BLKSC TSTAUTSY
BLKENERG TSTMANSY
B1QOPEN TSTENOK
B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
LN1QOPEN LN1SEL
LN1QCLD LN2SEL
LN2QOPEN SYNPROGR
LN2QCLD SYNFAIL
UB1OK UOKSYN
UB1FF UDIFFSYN
UB2OK FRDIFSYN
UB2FF FRDIFFOK
ULN1OK FRDERIVA
ULN1FF UOKSC
ULN2OK UDIFFSC
ULN2FF FRDIFFA
STARTSYN PHDIFFA
TSTSYNCH FRDIFFM
TSTSC PHDIFFM
TSTENERG INADVCLS
AENMODE UDIFFME
MENMODE FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN

IEC10000046-1-en.vsd
IEC10000046 V1 EN-US

Figure 166: SESRSYN function block

11.1.4 Signals
PID-6724-INPUTSIGNALS v1

Table 221: SESRSYN Input signals

Name Type Default Description


U3PBB1 GROUP - Group signal for phase to earth voltage input L1, busbar 1
SIGNAL
U3PBB2 GROUP - Group signal for phase to earth voltage input L1, busbar 2
SIGNAL
U3PLN1 GROUP - Group signal for phase to earth voltage input L1, line 1
SIGNAL
U3PLN2 GROUP - Group signal for phase to earth voltage input L1, line 2
SIGNAL
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus2
LN1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line1
Table continues on next page

312 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Type Default Description


LN1QCLD BOOLEAN 0 Close status for CB or disconnector connected to line1
LN2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line2
LN2QCLD BOOLEAN 0 Close status for CB or disconnector connected to line2
UB1OK BOOLEAN 0 Bus1 voltage transformer OK
UB1FF BOOLEAN 0 Bus1 voltage transformer fuse failure
UB2OK BOOLEAN 0 Bus2 voltage transformer OK
UB2FF BOOLEAN 0 Bus2 voltage transformer fuse failure
ULN1OK BOOLEAN 0 Line1 voltage transformer OK
ULN1FF BOOLEAN 0 Line1 voltage transformer fuse failure
ULN2OK BOOLEAN 0 Line2 voltage transformer OK
ULN2FF BOOLEAN 0 Line2 voltage transformer fuse failure
STARTSYN BOOLEAN 0 Start synchronizing
TSTSYNCH BOOLEAN 0 Set synchronizing in test mode
TSTSC BOOLEAN 0 Set synchro check in test mode
TSTENERG BOOLEAN 0 Set energizing check in test mode
AENMODE INTEGER 0 Input for setting of automatic energizing mode
MENMODE INTEGER 0 Input for setting of manual energizing mode

PID-6724-OUTPUTSIGNALS v1

Table 222: SESRSYN Output signals

Name Type Description


SYNOK BOOLEAN Synchronizing OK output
AUTOSYOK BOOLEAN Auto synchro check OK
AUTOENOK BOOLEAN Automatic energizing check OK
MANSYOK BOOLEAN Manual synchro check OK
MANENOK BOOLEAN Manual energizing check OK
TSTSYNOK BOOLEAN Synchronizing OK test output
TSTAUTSY BOOLEAN Auto synchro check OK test output
TSTMANSY BOOLEAN Manual synchro check OK test output
TSTENOK BOOLEAN Energizing check OK test output
USELFAIL BOOLEAN Selected voltage transformer fuse failed
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
LN1SEL BOOLEAN Line1 selected
LN2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
UOKSYN BOOLEAN Voltage amplitudes for synchronizing above set limits
UDIFFSYN BOOLEAN Voltage difference out of limit for synchronizing
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDIFFOK BOOLEAN Frequency difference in band for synchronizing
FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
UOKSC BOOLEAN Voltage amplitudes above set limits
UDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual operation
Table continues on next page

Transformer protection RET650 313


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Type Description


PHDIFFM BOOLEAN Phase angle difference out of limit for Manual Operation
INADVCLS BOOLEAN Inadvertent circuit breaker closing
UDIFFME REAL Calculated difference of voltage in p.u of set voltage base value
FRDIFFME REAL Calculated difference of frequency
PHDIFFME REAL Calculated difference of phase angle
UBUS REAL Bus voltage
ULINE REAL Line voltage
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing

11.1.5 Settings
PID-6724-SETTINGS v2

Table 223: SESRSYN Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
OperationSynch Off - - Off Operation for synchronizing function
On Off/On
UHighBusSynch 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for synchronizing in
% of UBaseBus
UHighLineSynch 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for synchronizing in
% of UBaseLine
UDiffSynch 0.02 - 0.50 pu 0.01 0.10 Voltage difference limit for synchronizing
in p.u of set voltage base value
FreqDiffMin 0.003 - 0.250 Hz 0.001 0.010 Minimum frequency difference limit for
synchronizing
FreqDiffMax 0.050 - 1.000 Hz 0.001 0.200 Maximum frequency difference limit for
synchronizing
CloseAngleMax 15.0 - 30.0 Deg 1.0 15.0 Maximum closing angle between bus and
line for synchronizing
FreqRateChange 0.000 - 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of
change
tBreaker 0.000 - 1.000 s 0.001 0.080 Closing time of the breaker
tClosePulse 0.050 - 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 - 6000.00 s 0.01 600.00 Resets synch if no close has been made
before set time
tMinSynch 0.000 - 60.000 s 0.001 2.000 Minimum time to accept synchronizing
conditions
OperationSC Off - - On Operation for synchronism check function
On Off/On
UHighBusSC 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for synchrocheck in
% of UBaseBus
UHighLineSC 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for synchrocheck in
% of UBaseLine
UDiffSC 0.02 - 0.50 pu 0.01 0.15 Voltage difference limit for synchrocheck
in p.u of set voltage base value
FreqDiffA 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Auto
FreqDiffM 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between bus
and line Manual
Table continues on next page

314 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Values (Range) Unit Step Default Description


PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between bus
and line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between bus
and line Manual
tSCA 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck Auto
tSCM 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Manual
AutoEnerg Off - - DLLB Automatic energizing check mode
DLLB
DBLL
Both
ManEnerg Off - - Both Manual energizing check mode
DLLB
DBLL
Both
ManEnergDBDL Off - - Off Manual dead bus, dead line energizing
On
UHighBusEnerg 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for energizing
check in % of UBaseBus
UHighLineEnerg 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for energizing check
in % of UBaseLine
ULowBusEnerg 10.0 - 80.0 %UBB 1.0 40.0 Voltage low limit bus for energizing check
in % of UBaseBus
ULowLineEnerg 10.0 - 80.0 %UBL 1.0 40.0 Voltage low limit line for energizing check
in % of UBaseLine
UMaxEnerg 50.0 - 180.0 %UB 1.0 115.0 Maximum voltage for energizing in % of
UBase, Line and/or Bus
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing
check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing check

Table 224: SESRSYN Non group settings (basic)

Name Values (Range) Unit Step Default Description


SelPhaseBus1 Phase L1 - - Phase L1 Select phase for busbar1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
GblBaseSelBus 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Line
SelPhaseBus2 Phase L1 - - Phase L1 Select phase for busbar2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Table continues on next page

Transformer protection RET650 315


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Values (Range) Unit Step Default Description


SelPhaseLine1 Phase L1 - - Phase L1 Select phase for line1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine2 Phase L1 - - Phase L1 Select phase for line2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
CBConfig No voltage sel. - - No voltage sel. Select CB configuration
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB

Table 225: SESRSYN Non group settings (advanced)

Name Values (Range) Unit Step Default Description


PhaseShift -180 - 180 Deg 1 0 Additional phase angle for selected line
voltage

11.1.6 Monitored data


PID-6724-MONITOREDDATA v1

Table 226: SESRSYN Monitored data

Name Type Values (Range) Unit Description


UDIFFME REAL - - Calculated difference of voltage in p.u of
set voltage base value
FRDIFFME REAL - Hz Calculated difference of frequency
PHDIFFME REAL - deg Calculated difference of phase angle
UBUS REAL - kV Bus voltage
ULINE REAL - kV Line voltage

11.1.7 Operation principle

11.1.7.1 Basic functionality M14832-3 v9

The synchrocheck feature measures the conditions across the circuit breaker and compares them to
set limits. The output for closing operation is given when all measured quantities are simultaneously
within their set limits.

The energizing check feature measures the bus and line voltages and compares them to both high
and low threshold detectors. The output is given only when the actual measured quantities match the
set conditions.

The synchronizing feature measures the conditions across the circuit breaker, and also determines
the angle change occurring during the closing delay of the circuit breaker, from the measured slip
frequency. The output is given only when all measured conditions are simultaneously within their set
limits. The closing of the output is timed to give closure at the optimal time including the time needed
for the circuit breaker and the closing circuit operation.

316 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

The voltage difference, frequency difference and phase angle difference values are measured in the
IED centrally and are available for the SESRSYN function for evaluation. By setting the phases used
for SESRSYN, with the settings SelPhaseBus1, SelPhaseBus2, SelPhaseLine1 and SelPhaseLine2,
a compensation is made automatically for the voltage amplitude difference and the phase angle
difference caused if different setting values are selected for both sides of the breaker. If needed, an
additional phase angle adjustment can be done for selected line voltage with the PhaseShift setting.

Some restrictions when using CBConfig selections 1½ bus CB, 1½ bus alt.CB and Tie
CB are described in Table 227 Such restriction are applicable only when a power
transformer is connected in the diameter and VT used for synchrocheck function is
located on the other side of the transformer.

For double bus single circuit breaker and 1½ circuit breaker arrangements, the SESRSYN function
blocks have the capability to make the necessary voltage selection. For double bus single circuit
breaker arrangements, selection of the correct voltage is made using auxiliary contacts of the bus
disconnectors. For 1½ circuit breaker arrangements, correct voltage selection is made using auxiliary
contacts of the bus disconnectors as well as the circuit breakers.

The internal logic for each function block as well as, the input and outputs, and the setting
parameters with default setting and setting ranges is described in this document. For application
related information, please refer to the application manual.

11.1.7.2 Logic diagrams IP14739-1 v2

M14833-3 v5
The logic diagrams that follow illustrate the main principles of the SESRSYN function components
such as Synchrocheck, Synchronizing, Energizing check and Voltage selection, and are intended to
simplify the understanding of the function.

Synchrocheck M14834-3 v15


When the function is set to OperationSC = On, the measuring will start.

The function will compare the bus and line voltage values with the set values for UHighBusSC and
UHighLineSC.

If both sides are higher than the set values, the measured values are compared with the set values
for acceptable frequency, phase angle and voltage difference: FreqDiffA, FreqDiffM, PhaseDiffA,
PhaseDiffM and U DiffSC. If additional phase angle adjustment is done with the PhaseShift setting,
the adjustment factor is deducted from the line voltage before the comparison of the phase angle
values.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than ±5Hz. The frequency difference between the bus
frequency and the line frequency is measured and may not exceed the set value FreqDiff.

Two sets of settings for frequency difference and phase angle difference are available and used for
the manual closing and autoreclose functions respectively, as required.

The inputs BLOCK and BLKSC are available for total block of the complete SESRSYN function and
selective block of the Synchrocheck function respectively. Input TSTSC will allow testing of the
function where the fulfilled conditions are connected to a separate test output.

The outputs MANSYOK and AUTOSYOK are activated when the actual measured conditions match
the set conditions for the respective output. The output signal can be delayed independently for
MANSYOK and AUTOSYOK conditions.

A number of outputs are available as information about fulfilled checking conditions. UOKSC shows
that the voltages are high, UDIFFSC, FRDIFFA, FRDIFFM, PHDIFFA, PHDIFFM shows when the
voltage difference, frequency difference and phase angle difference are out of limits.

Transformer protection RET650 317


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Output INADVCLS, inadvertent circuit breaker closing, indicates that the circuit breaker has been
closed at wrong phase angle by mistake. The output is activated, if the voltage conditions are fulfilled
at the same time the phase angle difference between bus and line is suddenly changed from being
larger than 60 degrees to smaller than 5 degrees.

Note! Similar logic for Manual Synchrocheck.

OperationSC = On
AND TSTAUTSY
AND

invalidSelection AND
OR AUTOSYOK
AND
0-60 s
AND t
tSCA

UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1

1
FRDIFFA
FreqDiffA

1
PHDIFFA
PhaseDiffA

UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue

32 ms 100 ms
AND t INADVCLS
PhDiff > 60° AND

PhDiff < 5°

IEC07000114-6-en.vsdx

IEC07000114 V6 EN-US

Figure 167: Simplified logic diagram for the auto synchrocheck function

Synchronizing SEMOD171603-4 v13


When the function is set to OperationSynch = On the measuring will be performed.

The function will compare the values for the bus and line voltage with the set values for
UHighBusSynch and UHighLineSynch, which is a supervision that the voltages are both live. Also the
voltage difference is checked to be smaller than the set value for UDiffSynch, which is a p.u value of
set voltage base values. If both sides are higher than the set values and the voltage difference
between bus and line is acceptable, the measured values are compared with the set values for
acceptable frequency FreqDiffMax and FreqDiffMin, rate of change of frequency FreqRateChange
and phase angle CloseAngleMax.

The measured frequencies between the settings for the maximum and minimum frequency will
initiate the measuring and the evaluation of the angle change to allow operation to be sent at the
right moment including the set tBreaker time. The calculation of the operation pulse sent in advance
is using the measured SlipFrequency and the set tBreaker time. To prevent incorrect closing pulses,
a maximum closing angle between bus and line is set with CloseAngleMax. To minimize the moment

318 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

stress when synchronizing near a power station, a narrower limit for CloseAngleMax needs to be
used.

When setting the value for tBreaker the following should be considered:

• The closing time of contact on a Binary Out Module (BOM) is appr.4ms and on a Static Output
Module (SOM) appr. 1ms.
• The operating time of any auxilliary relays in the closing circuit.
• Mechanical closing time of the breaker primary contacts.

The setting CloseAngleMax is only a limitation under which which combination of the SlipFrequency
and CB closing time the Synchronizing feature is capable to operate.

Theoretically the following equation is valid for the Synchronizing feature:

SlipFrequency[Hz] * tBreaker[s] < CloseAngleMax[deg] / 360

For example, when CloseAngleMax = 30 deg. and tBreaker = 0.1 s then the Synchronizing feature
can handle up to 0.833 Hz as shown below:

SlipFrequency[Hz] < (30 / 360) / 0.1 = 0.833 Hz

Figure 168 below shows the dependencies between tBreaker and slip frequency for the SYNOK
release with CloseAngleMax set to 15 or 30 degrees.

1000

800

15 30
600
tBreaker [ms]

400

15 30
200

30
15
15
0

0 200 400 600 800 1000

Slip frequency [mHz]


IEC20230601 V1 EN-US

Figure 168: Dependencies between tBreaker and Slip frequency with different
CloseAngleMax values

Energizing check M14835-3 v12


Voltage values are measured in the IED and are available for evaluation by the Energizing check
function.

The function measures voltages on the busbar and the line to verify whether they are live or dead.
This is done by comparing with the set values UHighBusEnerg and ULowBusEnerg for bus
energizing and UHighLineEnerg and ULowLineEnerg for line energizing.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than +/-5Hz.

Transformer protection RET650 319


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

The Energizing direction can be selected individually for the Manual and the Automatic functions
respectively. When the conditions are met the outputs AUTOENOK and MANENOK respectively will
be activated if the fuse supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing direction can also be
selected by an integer input AENMODE respective MENMODE, which for example, can be
connected to a Binary to Integer function block (B16I). Integers supplied shall be 1=Off, 2=DLLB,
3=DBLL and 4= Both. Not connected input will mean that the setting is done from Parameter Setting
tool. The active position can be read on outputs MODEAEN resp MODEMEN. The modes are
0=OFF, 1=DLLB, 2=DBLL and 3=Both.

The inputs BLOCK and BLKENERG are available for total block of the complete SESRSYN function
respective block of the Energizing check function. TSTENERG will allow testing of the function where
the fulfilled conditions are connected to a separate test output.

manEnergOpenBays
MANENOK
OR

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB 50ms tManEnerg
AND
OR t t
AND
OR
ULowLineEnerg AND

ManEnerg BOTH

ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
ManEnergDBDL AND AND

UMaxEnerg
fBus and fLine ±5 Hz

IEC14000031-2-en.vsdx

IEC14000031 V2 EN-US

Figure 169: Manual energizing

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB 50ms tAutoEnerg
AND
OR t t
AND OR
AUTOENOK
ULowLineEnerg AND
BOTH
AutoEnerg
ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
UMaxEnerg AND

fBus and fLine ±5 Hz

IEC14000030-2-en.vsdx
IEC14000030 V2 EN-US

Figure 170: Automatic energizing

320 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

BLKENERG
BLOCK OR manEnergOpenBays
AND

ManEnerg

1½ bus CB
CBConfig AND

B1QOPEN
LN1QOPEN AND
OR
B1QCLD
B2QOPEN
AND

LN2QOPEN

1½ bus alt. CB AND OR


AND
OR

B2QCLD
AND

Tie CB
AND
AND
OR

AND

IEC14000032-1-en.vsd
IEC14000032 V1 EN-US

Figure 171: Open bays

Fuse failure supervision M14837-3 v11


External fuse failure signals or signals from a tripped fuse switch/MCB are connected to binary inputs
that are configured to the inputs of SESRSYN function in the IED. Alternatively, the internal signals
from fuse failure supervision can be used when available. There are two alternative connection
possibilities. Inputs labelled OK must be connected if the available contact indicates that the voltage
circuit is healthy. Inputs labelled FF must be connected if the available contact indicates that the
voltage circuit is faulty.

The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage and the ULN1OK/
ULN2OK and ULN1FF/ULN2FF inputs are related to the line voltage. Configure them to the binary
input or function outputs that indicate the status of the external fuse failure of the busbar and line
voltages. In the event of a fuse failure, the energizing check function is blocked. The synchronizing
and the synchrocheck function requires full voltage on both sides, thus no blocking at fuse failure is
needed.

Voltage selection M14836-3 v9


The voltage selection module including supervision of included voltage transformers for the different
arrangements is a basic part of the SESRSYN function and determines the voltages fed to the
Synchronizing, Synchrocheck and Energizing check functions. This includes the selection of the
appropriate Line and Bus voltages and MCB supervision.

The voltage selection type to be used is set with the parameter CBConfig.

If No voltage sel. is set the voltages used will be U-Line1 and U-Bus1. This setting is also used in the
case when external voltage selection is provided. Fuse failure supervision for the used inputs must
also be connected.

The voltage selection function, selected voltages, and fuse conditions are used for the
Synchronizing, Synchrocheck and Energizing check inputs.

Transformer protection RET650 321


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts to supply
Disconnector Open and Closed positions but, it is also possible to use an inverter for one of the
positions.

If breaker or disconnector positions not are available for deciding if energizing is allowed, it is
considered to be allowed to manually energize. This is only allowed for manual energizing in 1½
breaker and Tie breaker arrangements. Manual energization of a completely open diameter in 1 1/2
CB switchgear is allowed by internal logic.

Voltage selection for a single circuit breaker with double busbars M14838-3 v11
The setting CBConfig selected for Double Bus activates the voltage selection for single CB and
double busbars. This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select between bus 1 and bus
2 voltages. If the disconnector connected to bus 1 is closed and the disconnector connected to bus 2
is opened or both disconnectors are closed, the bus 1 voltage is used. All other combinations use the
bus 2 voltage. The outputs B1SEL and B2SEL respectively indicate the selected Bus voltage.

The function checks the fuse failure signals for bus 1, bus 2 and line voltage transformers. Inputs
UB1OK-UB1FF supervise the MCB for Bus 1 and UB2OK-UB2FF supervises the MCB for Bus 2.
ULN1OK and ULN1FF supervises the MCB for the Line voltage transformer. The inputs fail (FF) or
healthy (OK) can alternatively be used dependent on the available signal. If a VT failure is detected
in the selected voltage source an output signal USELFAIL is set. This output signal is true if the
selected bus or line voltages have a VT failure. This output as well as the function can be blocked
with the input signal BLOCK. The function logic diagram is shown in figure 172.

B1QOPEN
B1SEL
B1QCLD AND

B2QOPEN B2SEL
AND
1
B2QCLD
invalidSelection
AND

bus1Voltage busVoltage

bus2Voltage

UB1OK AND
UB1FF OR
OR selectedFuseOK
AND
UB2OK AND
UB2FF OR USELFAIL
AND

ULN1OK
ULN1FF OR

BLOCK

en05000779-2.vsd
IEC05000779 V2 EN-US

Figure 172: Logic diagram for the voltage selection function of a single circuit breaker with double busbars

322 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Voltage selection for a 1½ circuit breaker arrangement M14839-3 v9


Note that with 1½ breaker schemes three Synchrocheck functions must be used for the complete
diameter. Below, the scheme for one Bus breaker and the Tie breaker is described.

With the setting parameter CBConfig the selection of actual CB location in the 1½ circuit breaker
switchgear is done. The settings are: 1½ bus CB, 1½ alt. bus CB or Tie CB.

This voltage selection function uses the binary inputs from the disconnectors and circuit breakers
auxiliary contacts to select the right voltage for the SESRSYN function. For the bus circuit breaker
one side of the circuit breaker is connected to the busbar and the other side is connected either to
line 1, line 2 or the other busbar depending on the selection of voltage circuit.

Inputs LN1QOPEN-LN1QCLD, B1QOPEN-B1QCLD, B2QOPEN-B2QCLD, LN2QOPEN-LN2QCLD


are inputs for the position of the Line disconnectors respectively the Bus and Tie breakers. The
outputs LN1SEL, LN2SEL and B2SEL will give indication of the selected Line voltage as a reference
to the fixed Bus 1 voltage, which indicates B1SEL.

The fuse supervision is connected to ULN1OK-ULN1FF, ULN2OK-ULN2FF and with alternative


Healthy or Failing fuse signals depending on what is available from each fuse (MCB).

The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the other side is
connected either to bus 2 or line 2 voltage. Four different output combinations are possible, bus to
bus, bus to line, line to bus and line to line.

• The line 1 voltage is selected if the line 1 disconnector is closed.


• The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1 circuit breaker is
closed.
• The line 2 voltage is selected if the line 2 disconnector is closed.
• The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2 circuit breaker is
closed.

Some restrictions when using CBConfig selections 1½ bus CB, 1½ bus alt.CB and Tie
CB are described in Table 227. Such restriction are applicable only when a power
transformer is connected in the diameter and VT used for synchrocheck function is
located on the other side of the transformer.

Table 227: Limitations for VT selection regarding selected value for CBConfig

CBConfig setting Possible closing Used GblBaseSel settings PhaseShift setting Conclusion
between has impact on
1½ bus CB Bus1 - Line1 GblBaseSelBus => Bus1 Line1
GblBaseSelLine => Line1
Bus1 - Line2 GblBaseSelBus => Bus1 Line2
GblBaseSelLine => Line2
Bus1 - Bus2 GblBaseSelBus => Bus1 No impact Bus1 and Bus2 must have
GblBaseSelBus => Bus2 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
1½ bus alt.CB Bus2 - Line2 GblBaseSelBus => Bus2 Line2
GblBaseSelLine => Line2
Bus2 - Line1 GblBaseSelBus => Bus2 Line1
GblBaseSelLine => Line1
Bus2 - Bus1 GblBaseSelBus => Bus2 No impact Bus2 and Bus1 must have
GblBaseSelBus => Bus1 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
Table continues on next page

Transformer protection RET650 323


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

CBConfig setting Possible closing Used GblBaseSel settings PhaseShift setting Conclusion
between has impact on
Tie CB Bus1 - Line2 GblBaseSelBus => Bus1 Line2
GblBaseSelLine => Line2
Bus1 - Bus2 GblBaseSelBus => Bus1 No impact Bus1 and Bus2 must have
GblBaseSelBus => Bus2 same base voltage.
GblBaseSelLine has no impact PhaseShift setting has no
impact.
Bus2 - Line1 GblBaseSelBus => Bus2 Line1
GblBaseSelLine => Line1
Line1 - Line2 GblBaseSelLine => Line1 Line2 Line1 and Line2 must have
GblBaseSelLine => Line2 same base voltage.
GblBaseSelBus has no affect

The function also checks the fuse failure signals for bus 1, bus 2, line 1 and line 2. If a VT failure is
detected in the selected voltage an output signal USELFAIL is set. This output signal is true if the
selected bus or line voltages have a MCB trip. This output as well as the function can be blocked with
the input signal BLOCK. The function block diagram for the voltage selection of a bus circuit breaker
is shown in figure 173 and for the tie circuit breaker in figure 174.

324 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD

B1QOPEN
LN2SEL
B1QCLD AND AND
B2SEL
OR
LN2QOPEN
AND invalidSelection
LN2QCLD AND
AND
B2QOPEN
B2QCLD AND

line1Voltage lineVoltage

line2Voltage

bus2Voltage

UB1OK
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000780-2.vsd
IEC05000780 V2 EN-US

Figure 173: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement

Transformer protection RET650 325


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD
B1SEL
1

B1QOPEN AND
AND
B1QCLD AND

line1Voltage busVoltage

bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
invalidSelection
OR
B2QOPEN AND
AND
B2QCLD AND

line2Voltage lineVoltage

bus2Voltage

UB1OK AND
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000781-2.vsd
IEC05000781 V2 EN-US

Figure 174: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.

11.1.8 Technical data


M12359-1 v16

Table 228: SESRSYN technical data

Function Range or value Accuracy


Phase shift, jline - jbus (-180 to 180) degrees -
Voltage high limit for synchronizing and (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
synchrocheck ±0.5% of U at U > Ur
Reset ratio, synchrocheck > 95% -
Frequency difference limit between bus and (0.003-1.000) Hz ±2.5 mHz
line for synchrocheck
Table continues on next page

326 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Function Range or value Accuracy


Phase angle difference limit between bus and (5.0-90.0) degrees ±2.0 degrees
line for synchrocheck
Voltage difference limit between bus and line ±0.5% of Ur
for synchronizing and synchrocheck
Time delay output for synchrocheck when (0.000-60.000) s
angle difference between bus and line jumps
from “PhaseDiff” + 2 degrees to “PhaseDiff” -
2 degrees
Frequency difference minimum limit for (0.003-0.250) Hz
synchronizing
Frequency difference maximum limit for (0.050-1.000) Hz
synchronizing
Maximum allowed frequency rate of change (0.000-0.500) Hz/s ±10.0 mHz/s
Maximum closing angle between bus and line (15-30) degrees ±2.0 degrees
for synchronizing
Breaker closing pulse duration (0.050-1.000) s
tMaxSynch, which resets synchronizing (0.000-6000.00) s
function if no close has been made before set
time
Minimum time to accept synchronizing (0.000-60.000) s
conditions
Voltage high limit for energizing check (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Reset ratio, voltage high limit > 95% -
Voltage low limit for energizing check (10.0-80.0)% of UBase ±0.5% of Ur
Reset ratio, voltage low limit < 105% -
Maximum voltage for energizing (50.0-180.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Time delay for energizing check when voltage (0.000-60.000) s ±0.2% or ±100 ms whichever is
jumps from 0 to 90% of Urated greater
Operate time for synchrocheck function when Min. = 15 ms –
angle difference between bus and line jumps Max. = 30 ms
from “PhaseDiff” + 2 degrees to “PhaseDiff” -
2 degrees
Operate time for energizing function when Min. = 70 ms –
voltage jumps from 0 to 90% of Urated Max. = 90 ms

11.2 Interlocking IP15572-1 v2

11.2.1 Functionality M15106-3 v7

The interlocking functionality blocks the possibility to operate high-voltage switching devices, for
instance when a disconnector is under load, in order to prevent material damage and/or accidental
human injury.

Each control IED has interlocking functions for different switchyard arrangements, each handling the
interlocking of one bay. The interlocking functionality in each IED is not dependent on any central
function. For the station-wide interlocking, the IEDs communicate via the station bus or by using hard
wired binary inputs/outputs.

The interlocking conditions depend on the circuit configuration and status of the system at any given
time.

Transformer protection RET650 327


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.2.2 Operation principle M13528-4 v7

The interlocking function consists of software modules located in each control IED. The function is
distributed and not dependent on any central function. Communication between modules in different
bays is performed via the station bus.

The reservation function (see section "Functionality") is used to ensure that HV apparatuses that
might affect the interlock are blocked during the time gap, which arises between position updates.
This can be done by means of the communication system, reserving all HV apparatuses that might
influence the interlocking condition of the intended operation. The reservation is maintained until the
operation is performed.

After the selection and reservation of an apparatus, the function has complete data on the status of
all apparatuses in the switchyard that are affected by the selection. Other operators cannot interfere
with the reserved apparatus or the status of switching devices that may affect it.

The open or closed positions of the HV apparatuses are inputs to software modules distributed in the
control IEDs. Each module contains the interlocking logic for a bay. The interlocking logic in a module
is different, depending on the bay function and the switchyard arrangements, that is, double-breaker
or 1 1/2 breaker bays have different modules. Specific interlocking conditions and connections
between standard interlocking modules are performed with an engineering tool. Bay-level interlocking
signals can include the following kind of information:

• Positions of HV apparatuses (sometimes per phase)


• Valid positions (if evaluated in the control module)
• External release (to add special conditions for release)
• Line voltage (to block operation of line earthing switch)
• Output signals to release the HV apparatus

The interlocking module is connected to the surrounding functions within a bay as shown in figure
175.

Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI

Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module

Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI

IEC04000526 V1 EN-US

Figure 175: Interlocking module on bay level


Bays communicate via the station bus and can convey information regarding the following:

• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid

Figure 176 illustrates the data exchange principle.

328 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Station bus

Bay 1 Bay n Bus coupler

Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn

...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay

..
WA1

WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2

QA1 QA1 QA1

QB9 QB9

en05000494.vsd
IEC05000494 V1 EN-US

Figure 176: Data exchange between interlocking modules


When invalid data such as intermediate position, loss of a control IED, or input board error are used
as conditions for the interlocking condition in a bay, a release for execution of the function will not be
given.

On the local HMI an override function exists, which can be used to bypass the interlocking function in
cases where not all the data required for the condition is valid.

For all interlocking modules these general rules apply:

• The interlocking conditions for opening or closing of disconnectors and earthing switches are
always identical.
• Earthing switches on the line feeder end, for example, rapid earthing switches, are normally
interlocked only with reference to the conditions in the bay where they are located, not with
reference to switches on the other side of the line. So a line voltage indication may be included
into line interlocking modules. If there is no line voltage supervision within the bay, then the
appropriate inputs must be set to no voltage, and the operator must consider this when
operating.
• Earthing switches can only be operated on isolated sections for example, without load/voltage.
Circuit breaker contacts cannot be used to isolate a section, that is, the status of the circuit
breaker is irrelevant as far as the earthing switch operation is concerned.
• Disconnectors cannot break power current or connect different voltage systems. Disconnectors
in series with a circuit breaker can only be operated if the circuit breaker is open, or if the
disconnectors operate in parallel with other closed connections. Other disconnectors can be
operated if one side is completely isolated, or if the disconnectors operate in parallel to other
closed connections, or if they are earthed on both sides.
• Circuit breaker closing is only interlocked against running disconnectors in its bay or additionally
in a transformer bay against the disconnectors and earthing switch on the other side of the
transformer, if there is no disconnector between CB and transformer.
• Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar transfer is in
progress.

To make the implementation of the interlocking function easier, a number of standardized and tested
software interlocking modules containing logic for the interlocking conditions are available:

• Line for double and transfer busbars, ABC_LINE


• Bus for double and transfer busbars, ABC_BC
• Transformer bay for double busbars, AB_TRAFO
• Bus-section breaker for double busbars, A1A2_BS
• Bus-section disconnector for double busbars, A1A2_DC

Transformer protection RET650 329


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

• Busbar earthing switch, BB_ES


• Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
• 1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B

The interlocking conditions can be altered, to meet the customer specific requirements, by adding
configurable logic by means of the graphical configuration tool PCM600. The inputs Qx_EXy on the
interlocking modules are used to add these specific conditions.

The input signals EXDU_xx shall be set to true if there is no transmission error at the transfer of
information from other bays. Required signals with designations ending in TR are intended for
transfer to other bays.

11.2.3 Logical node for interlocking SCILO IP14138-1 v2

11.2.3.1 Identification
GUID-3EC5D7F1-FDA0-4F0E-9391-08D357689E0C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical node for interlocking SCILO - 3

11.2.3.2 Functionality M15048-3 v7

The Logical node for interlocking SCILO function is used to enable a switching operation if the
interlocking conditions permit. SCILO function itself does not provide any interlocking functionality.
The interlocking conditions are generated in separate function blocks containing the interlocking
logic.

11.2.3.3 Function block M15049-3 v6

SCILO
POSOPEN EN_OPEN
POSCLOSE EN_CLOSE
OPEN_EN
CLOSE_EN

IEC05000359-2-en.vsd
IEC05000359 V2 EN-US

Figure 177: SCILO function block

11.2.3.4 Signals
PID-3487-INPUTSIGNALS v7

Table 229: SCILO Input signals

Name Type Default Description


POSOPEN BOOLEAN 0 Open position of switch device
POSCLOSE BOOLEAN 0 Closed position of switch device
OPEN_EN BOOLEAN 0 Open operation from interlocking logic is enabled
CLOSE_EN BOOLEAN 0 Close operation from interlocking logic is enabled

330 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

PID-3487-OUTPUTSIGNALS v7

Table 230: SCILO Output signals

Name Type Description


EN_OPEN BOOLEAN Open operation at closed or interm. or bad pos. is enabled
EN_CLOSE BOOLEAN Close operation at open or interm. or bad pos. is enabled

11.2.3.5 Logic diagram M15086-3 v6

The function contains logic to enable the open and close commands respectively if the interlocking
conditions are fulfilled. That means also, if the switch has a defined end position for example, open,
then the appropriate enable signal (in this case EN_OPEN) is false. The enable signals EN_OPEN
and EN_CLOSE can be true at the same time only in the intermediate and bad position state and if
they are enabled by the interlocking function. The position inputs come from the logical nodes Circuit
breaker/Circuit switch (SXCBR/SXSWI) and the enable signals come from the interlocking logic. The
outputs are connected to the logical node Switch controller (SCSWI). One instance per switching
device is needed.

POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&

OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd

IEC04000525 V1 EN-US

Figure 178: SCILO function logic diagram

11.2.4 Interlocking for busbar earthing switch BB_ES IP14164-1 v4

11.2.4.1 Identification
GUID-F3CBAFDC-3723-429F-9183-45229A6F0A12 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for busbar earthing switch BB_ES - 3

11.2.4.2 Functionality M15015-3 v7

The interlocking for busbar earthing switch (BB_ES) function is used for one busbar earthing switch
on any busbar parts according to figure 179.

Transformer protection RET650 331


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

QC

en04000504.vsd
IEC04000504 V1 EN-US

Figure 179: Switchyard layout BB_ES

11.2.4.3 Function block M15069-3 v6

BB_ES
QC_OP QCREL
QC_CL QCITL
BB_DC_OP BBESOPTR
VP_BB_DC BBESCLTR
EXDU_BB

IEC05000347-2-en.vsd
IEC05000347 V2 EN-US

Figure 180: BB_ES function block

11.2.4.4 Logic diagram M15103-3 v4

BB_ES
VP_BB_DC QCREL
BB_DC_OP QCITL
EXDU_BB & 1

QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd

IEC04000546 V1 EN-US

11.2.4.5 Signals
PID-3494-INPUTSIGNALS v10

Table 231: BB_ES Input signals

Name Type Default Description


QC_OP BOOLEAN 0 Busbar earthing switch QC is in open position
QC_CL BOOLEAN 0 Busbar earthing switch QC is in closed position
BB_DC_OP BOOLEAN 0 All disconnectors on this busbar part are open
VP_BB_DC BOOLEAN 0 Status for all disconnectors on this busbar part are valid
EXDU_BB BOOLEAN 0 No transm error from bays with disc on this busbar part

PID-3494-OUTPUTSIGNALS v10

Table 232: BB_ES Output signals

Name Type Description


QCREL BOOLEAN Switching of QC is allowed
QCITL BOOLEAN Switching of QC is forbidden
BBESOPTR BOOLEAN QC on this busbar part is in open position
BBESCLTR BOOLEAN QC on this busbar part is in closed position

11.2.5 Interlocking for line bay ABC_LINE IP14139-1 v2

332 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.2.5.1 Identification
GUID-BEA26EA4-F402-4385-9238-1361E862D987 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for line bay ABC_LINE - 3

11.2.5.2 Functionality M13561-3 v8

The interlocking for line bay (ABC_LINE) function is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 181. The function can also be used for a
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.

WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1

QA1

QC2

QB9
QC9

en04000478.vsd
IEC04000478 V1 EN-US

Figure 181: Switchyard layout ABC_LINE

Transformer protection RET650 333


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.2.5.3 Function block M15108-3 v6

ABC_LINE
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB9_OP QB9REL
QB9_CL QB9ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QB7_OP QB7REL
QB7_CL QB7ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC9_OP QC9REL
QC9_CL QC9ITL
QC11_OP QB1OPTR
QC11_CL QB1CLTR
QC21_OP QB2OPTR
QC21_CL QB2CLTR
QC71_OP QB7OPTR
QC71_CL QB7CLTR
BB7_D_OP QB12OPTR
BC_12_CL QB12CLTR
BC_17_OP VPQB1TR
BC_17_CL VPQB2TR
BC_27_OP VPQB7TR
BC_27_CL VPQB12TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4

IEC05000357-2-en.vsd
IEC05000357 V2 EN-US

Figure 182: ABC_LINE function block

334 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.2.5.4 Logic diagram M15089-3 v5

ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2

en04000527.vsd
IEC04000527 V1 EN-US

Transformer protection RET650 335


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES

QB1_EX1

VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC

QB1_EX2

VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES

QB1EX3

en04000528.vsd

IEC04000528 V1 EN-US

336 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES

QB2_EX1

VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC

QB2_EX2

VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES

QB2_EX3

en04000529.vsd

IEC04000529 V1 EN-US

Transformer protection RET650 337


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB

BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1

VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_17_CL

EXDU_BC

QB7_EX2

IEC04000530 V1 EN-US

338 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
IEC04000531 V1 EN-US

Transformer protection RET650 339


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
IEC04000532 V1 EN-US

11.2.5.5 Signals
PID-3509-INPUTSIGNALS v10

Table 233: ABC_LINE Input signals

Name Type Default Description


QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar WA7 except in the own bay are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA2
BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar WA1 and WA7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar WA2 and WA7
Table continues on next page

340 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Type Default Description


BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar WA2 and WA7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar WA7 are valid
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are valid
VP_BC_17 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA7 are valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler app. between WA2 and WA7 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_BPB BOOLEAN 0 No transm error from any bay with disconnectors on WA7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7
QB7_EX3 BOOLEAN 0 External condition for apparatus QB7
QB7_EX4 BOOLEAN 0 External condition for apparatus QB7

PID-3509-OUTPUTSIGNALS v10

Table 234: ABC_LINE Output signals

Name Type Description


QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB7OPTR BOOLEAN QB7 is in open position
Table continues on next page

Transformer protection RET650 341


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Type Description


QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)

11.2.6 Interlocking for transformer bay AB_TRAFO IP14149-1 v2

11.2.6.1 Identification
GUID-AD839CAA-531B-43BC-B508-39AED3D0A97D v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Interlocking for transformer bay AB_TRAFO - 3

11.2.6.2 Functionality M13567-3 v7

The interlocking for transformer bay (AB_TRAFO) function is used for a transformer bay connected
to a double busbar arrangement according to figure 183. The function is used when there is no
disconnector between circuit breaker and transformer. Otherwise, the interlocking for line bay
(ABC_LINE) function can be used. This function can also be used in single busbar arrangements.

WA1 (A)
WA2 (B)
QB1 QB2
QC1

QA1
AB_TRAFO
QC2

QC3

QA2
QA2 and QC4 are not
QC4 used in this interlocking

QB3 QB4

en04000515.vsd
IEC04000515 V1 EN-US

Figure 183: Switchyard layout AB_TRAFO

342 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.2.6.3 Function block M13565-3 v6

AB_TRAFO
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB1REL
QB1_CL QB1ITL
QB2_OP QB2REL
QB2_CL QB2ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QB3_OP QB1OPTR
QB3_CL QB1CLTR
QB4_OP QB2OPTR
QB4_CL QB2CLTR
QC3_OP QB12OPTR
QC3_CL QB12CLTR
QC11_OP VPQB1TR
QC11_CL VPQB2TR
QC21_OP VPQB12TR
QC21_CL
BC_12_CL
VP_BC_12
EXDU_ES
EXDU_BC
QA1_EX1
QA1_EX2
QA1_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3

IEC05000358-2-en.vsd
IEC05000358 V2 EN-US

Figure 184: AB_TRAFO function block

11.2.6.4 Logic diagram M15097-3 v4

AB_TRAFO
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB3_OP
QB3_CL =1 VPQB3
QB4_OP
QB4_CL =1 VPQB4
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQC1 & 1

VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1

en04000538.vsd

IEC04000538 V1 EN-US

Transformer protection RET650 343


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3

en04000539.vsd

IEC04000539 V1 EN-US

VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3

en04000540.vsd

IEC04000540 V1 EN-US

VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd
IEC04000541 V1 EN-US

344 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.2.6.5 Signals
PID-3510-INPUTSIGNALS v10

Table 235: AB_TRAFO Input signals

Name Type Default Description


QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QB3_OP BOOLEAN 0 QB3 is in open position
QB3_CL BOOLEAN 0 QB3 is in closed position
QB4_OP BOOLEAN 0 QB4 is in open position
QB4_CL BOOLEAN 0 QB4 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 QC21 on busbar WA2 is in closed position
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA2
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QA1_EX1 BOOLEAN 0 External condition for apparatus QA1
QA1_EX2 BOOLEAN 0 External condition for apparatus QA1
QA1_EX3 BOOLEAN 0 External condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2

PID-3510-OUTPUTSIGNALS v10

Table 236: AB_TRAFO Output signals

Name Type Description


QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
Table continues on next page

Transformer protection RET650 345


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Type Description


QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)

11.2.7 Position evaluation POS_EVAL GUID-F20A8939-E91E-44F6-920C-083E5D3FCDFD v2

11.2.7.1 Identification
GUID-3C4B9379-C861-406C-9295-0309014D548E v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Position evaluation POS_EVAL - -

11.2.7.2 Functionality GUID-C3D07B40-FF01-45C5-A083-EED5643A5FCC v4

Position evaluation (POS_EVAL) function converts the input position data signal POSITION,
consisting of value, time and signal status, to binary signals OPENPOS or CLOSEPOS.

The output signals are used by other functions in the interlocking scheme.

11.2.7.3 Function block GUID-B5EF4A28-9C9F-4558-8CD6-453FB480314B v2

POS_EVAL
POSITION OPENPOS
CLOSEPOS

IEC09000079_1_en.vsd
IEC09000079 V1 EN-US

Figure 185: POS_EVAL function block

11.2.7.4 Logic diagram GUID-F0EF8D38-031B-4A8E-BD7D-60314F5DCD59 v2

POS_EVAL
Position including quality POSITION OPENPOS
Open/close position of
CLOSEPOS switch device

IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN-US

Only the value, open/close, and status is used in this function. Time information is not used.

346 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Input position (Value) Signal quality Output OPENPOS Output CLOSEPOS


0 (Breaker intermediate) Good 0 0
1 (Breaker open) Good 1 0
2 (Breaker closed) Good 0 1
3 (Breaker faulty) Good 0 0
Any Invalid 0 0
Any Oscillatory 0 0

11.2.7.5 Signals
PID-3555-INPUTSIGNALS v6

Table 237: POS_EVAL Input signals

Name Type Default Description


POSITION INTEGER 0 Position status including quality

PID-3555-OUTPUTSIGNALS v6

Table 238: POS_EVAL Output signals

Name Type Description


OPENPOS BOOLEAN Open position
CLOSEPOS BOOLEAN Close position

11.3 Apparatus control IP14560-1 v3

11.3.1 Functionality M13444-3 v16

The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given after evaluation of
conditions from other functions such as interlocking, synchrocheck, operator place selection and
external or internal blockings.

The apparatus control function APC5 for up to 5 apparatuses is used for control and supervision of
circuit breakers, disconnectors and earthing switches within a bay. Permission to operate is given
after evaluation of conditions from other functions such as interlocking, synchrocheck, operator place
selection and external or internal blockings.

Apparatus control features:

• Select-Execute principle to give high reliability


• Selection function to prevent simultaneous operation
• Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
• Substitution of position and quality indications
• Overriding of interlocking functions
• Overriding of synchrocheck
• Operation counter
• Suppression of mid position

Two types of command models can be used:

Transformer protection RET650 347


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

• Direct with normal security


• SBO (Select-Before-Operate) with enhanced security

In normal security, the command is processed and the resulting position is not supervised. However
with enhanced security, the command is processed and the resulting position is supervised.

Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command is evaluated with an additional supervision
of the status value of the control object. The command sequence with enhanced security is always
terminated by a CommandTermination service primitive and an AddCause telling if the command was
successful or if something went wrong.

Control operation can be performed from the local HMI with authority control if so defined.

The switch controller SCSWI initializes and supervises all functions to properly select and operate
switching primary apparatuses. Each of the 10 switch controllers SCSWI may handle and operate on
one three-phase apparatus.

Each of the 3 circuit breaker controllers SXCBR provides the actual position status and pass the
commands to the primary circuit breaker and supervises the switching operation and positions.

Each of the 9 circuit switch controllers SXSWI provides the actual position status and pass the
commands to the primary disconnectors and earthing switches and supervises the switching
operation and positions.

11.3.2 Operation principle M13423-4 v10

A bay can handle, for example a power line, a transformer, a reactor, or a capacitor bank. The
different primary apparatuses within the bay can be controlled via the apparatus control functions
directly by the operator or indirectly by automatic sequences.

Because a primary apparatus can be allocated to many functions within a Substation Automation
system, the object-oriented approach with a function block that handles the interaction and status of
each process object ensures consistency in the process information used by higher-level control
functions.

Primary apparatuses such as breakers and disconnectors are controlled and supervised by one
function block (SCSWI) each. Because the number and type of signals used for the control of a
breaker or a disconnector are almost the same, the same function block type is used to handle these
two types of apparatuses.

The SCSWI function block is connected to an SXCBR function block (for circuit breakers). The
physical process in the switchyard is connected to these two function blocks via binary inputs and
outputs.

Three types of function blocks are available to cover most of the control and supervision within the
bay. These function blocks are interconnected to form a control function reflecting the switchyard
configuration. The total number used depends on the switchyard configuration. These types are:

• Bay control QCBAY


• Switch controller SCSWI
• Circuit breaker SXCBR

Another function block type for supervision and control is the XLNPROXY. It is used for interfacing a
switch with its primary representation in an other device, such as a breaker IED or merging unit.
XLNPROXY facilitates a common interface with the SXCBR function towards the SCSWI function,
especially for command response and error handling.

The functions Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle the
local/remote switch, also belong to the apparatus control function.

348 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

The principles of operation, function blocks, input and output signals and setting parameters for all
these functions are described below.

11.3.3 Error handling GUID-6C31D291-74E8-46A3-8FC2-D3959C2458A5 v10

Depending on the error that occurs during the command sequence the error signal will be set with a
value. Table 239 describes the cause values given on local HMI. The translation to AddCause
values specified in IEC 61850-8-1 is shown in Table 240. For IEC 61850-8-1 edition 2 only
addcauses defined in the standard are used, for edition 1 also a number of vendor specific causes
are used. The values are available in the command response to commands from IE C61850-8-1
clients. An output L_CAUSE on the function block for Switch controller (SCSWI) and Circuit breaker
(SXCBR) indicates the value of the cause during the latest command if the function specific
command evaluation has been started. The causes that are not always reflected on the output
L_CAUSE, with description of the typical reason are listed in table 241.

Table 239: Values for "cause" signal

Cause Name Description Supported


number
0 None Control action successfully executed X
1 Not-supported Given for Cancel request with Direct Control in Ready state X
2 Blocked-by-switching- Not successful since one of the downstream Loc switches like in X
hierarchy CSWI has the value TRUE
3 Select-failed Cancelled due to an unsuccessful selection (select service) X
4 Invalid-position Control action is aborted due to invalid switch position (Pos in X
XCBR)
5 Position-reached Switch is already in the intended position (Pos in XCBR) X
6 Parameter-change-in- Control action is blocked due to running parameter change X
execution
7 Step-limit Control action is blocked, because tap changer has reached the
limit (EndPosR or EndPosL in YLTC)
8 Blocked-by-Mode Control action is blocked, because the LN (CSWI or XCBR) is in X
a mode (Mod) which doesn’t allow any switching
9 Blocked-by-process Control action is blocked due to some external event at process X
level that prevents a successful operation, for example blocking
indication (EEHealth in XCBR)
10 Blocked-by-interlocking Control action is blocked due to interlocking of switching devices X
(in CILO attribute EnaOpn.stVal=”FALSE” or
EnaCls.stVal=”FALSE”
11 Blocked-by- Control action with synchrocheck is aborted due to exceed of X
synchrocheck time limit and missing synchronism condition
12 Command-already-in- Control, select or cancel service is rejected, because control X
execution action is already running
13 Blocked-by-health Control action is blocked due to some internal event that X
prevents a successful operation (Health)
14 1-of-n-control Control action is blocked because another control action in a X
domain (for example, substation) is already running (in any
XCBR of that domain, the DPC.stSeld=”TRUE”)
15 Abortion-by-cancel Control action is aborted due to cancel service X
16 Time-limit-over Control action is terminated due to exceed of some time limit X
17 Abortion-by-trip Control action is aborted due to a trip (PTRC with
ACT.general=”TRUE”)
18 Object-not-selected Control action is rejected, because control object was not X
selected
19 Object-already-selected Select action is not executed because the addressed object is X
already selected
Table continues on next page

Transformer protection RET650 349


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Cause Name Description Supported


number
20 No-access-authority Control action is blocked due to lack of access authority
21 Ended-with-overshoot Control action executed but the end position has overshoot
22 Abortion-due-to- Control action is aborted due to deviation between the command
deviation value and the measured value
23 Abortion-by- Control action is aborted due to the loss of connection with the
communication-loss client that issued the control
24 Blocked-by-command Control action is blocked due to the data attribute CmdBlk.stVal X
is TRUE
26 Inconsistent-parameters The parameters between successive control services are not X
consistent, for example the ctlNum of Select and Operate service
are different
27 Locked-by-other-client Another client has already reserved the object X
-22 Wrong-Ctl-model Command from client uses wrong control model X
-23 Blocked-by-command Blocked by command X
-24 Blocked-for-open-cmd Blocked for Open command X
-25 Blocked-for-close-cmd Blocked for Close Command X
-30 Long-operation-time Operation time too long X
-31 Switch-not-start-moving Switch did not start moving X
-32 Persistent-intermediate- Switch stopped in intermediate state X
state
-33 Switch-returned-to-init- Switch returned to the initial position X
pos
-34 Switch-in-bad-state Switch is in a bad position state X
-35 Not-expected-final- Switch did not reach the expected final position X
position

Table 240: Translation of cause values for IEC 61850 edition 2 and edition 1

Internal Cause AddCause in IEC 61850-8-1 Name


Number
Ed 2 Ed 1
0 25 0 None
1 1 1 Not-supported
2 2 2 Blocked-by-switching-hierarchy
3 3 3 Select-failed
4 4 4 Invalid-position
5 5 5 Position-reached
6 6 6 Parameter-change-in-execution
7 7 7 Step-limit
8 8 8 Blocked-by-Mode
9 9 9 Blocked-by-process
10 10 10 Blocked-by-interlocking
11 11 11 Blocked-by-synchrocheck
12 12 12 Command-already-in-execution
13 13 13 Blocked-by-health
14 14 14 1-of-n-control
15 15 1 Abortion-by-cancel
16 16 16 Time-limit-over
17 17 17 Abortion-by-trip
Table continues on next page

350 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Internal Cause AddCause in IEC 61850-8-1 Name


Number
Ed 2 Ed 1
18 18 18 Object-not-selected
19 19 3 Object-already-selected
20 20 3 No-access-authority
24 24 -23 Blocked-by-command
26 26 6 Inconsistent-parameters
27 27 12 Locked-by-other-client
-22 0 -22 Wrong-Ctl-model
-23 24 -23 Blocked-by-command
-24 9 -24 Blocked-for-open-cmd
-25 9 -25 Blocked-for-close-cmd
-30 16 -30 Long-operation-time
-31 16 -31 Switch-not-start-moving
-32 4 -32 Persistent-intermediate-state
-33 4 -33 Switch-returned-to-init-pos
-34 4 -34 Switch-in-bad-state
-35 4 -35 Not-expected-final-position

The negative values are vendor-specific for Hitachi Energy.

Table 241: Cause values not reflected on the output L_CAUSE

Cause number Cause description Conditions


3 Select-failed Canceled due to an unsuccessful selection (select
service)
8 Blocked-by-Mode Control action is blocked because the LN (CSWI)
is in a mode (Mod) which doesn’t allow any
switching or does not match the mode of the
command.
12 Command-already-in-execution Control, select or cancel service is rejected
because control action is already running.
13 Blocked-by-health Control action is blocked due to some internal
event that prevents a successful operation
(Health).
16 Time-limit-over Control action is terminated due to exceed of some
time limit.
18 Object-not-selected Control action is rejected because control object
was not selected.
19 Object-already-selected Select action is not executed because the
addressed object is already selected.
20 No-access-authority Control action is blocked due to lack of access
authority.
26 Inconsistent-parameters The parameters between successive control
services are not consistent, for example the
ctlNum of Select and Operate service are different.
27 Locked-by-other-client Another client has already reserved the object.

11.3.4 Bay control QCBAY IP15597-1 v2

Transformer protection RET650 351


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.4.1 Functionality M13447-3 v8

The Bay control (QCBAY) function is used together with Local remote and local remote control
functions to handle the selection of the operator place per bay. QCBAY also provides blocking
functions that can be distributed to different apparatuses within the bay.

11.3.4.2 Function block M13469-3 v5

QCBAY
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID LOC
BL_UPD STA
BL_CMD REM

IEC10000048 V4 EN-US

Figure 186: QCBAY function block

11.3.4.3 Signals
PID-4086-INPUTSIGNALS v8

Table 242: QCBAY Input signals

Name Type Default Description


LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command

PID-4086-OUTPUTSIGNALS v8

Table 243: QCBAY Output signals

Name Type Description


PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
LOC BOOLEAN Local operation allowed
STA BOOLEAN Station operation allowed
REM BOOLEAN Remote operation allowed

11.3.4.4 Settings
PID-4086-SETTINGS v8

Table 244: QCBAY Non group settings (basic)

Name Values (Range) Unit Step Default Description


AllPSTOValid Priority - - Priority Override Priority of originators,
No priority commands from both local, station and
remote are allowed
RemoteIncStation No - - No Both Station and Remote control are
Yes allowed but not Local when local remote
switch is in remote

352 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.3.4.5 Operation principle


M13446-4 v8
The function sends information about the Permitted Source To Operate (PSTO) and blocking
conditions to other functions within the bay for example, switch control functions and voltage control
functions. The functionality of the Bay control (QCBAY) function is mainly described by the LLN0
node in the IEC 61850-8-1 edition 2 standard, applied to one bay. In IEC 61850 edition 1 the
functionality is not described by the LLN0 node or any other node, therefore the Bay control function
is represented as a vendor specific node in edition 1.

Local panel switch M13446-7 v8


The local panel switch is a switch that defines the operator place selection. The switch connected to
this function can have three positions (remote/local/off). The positions are here defined so that
remote means that operation is allowed from station and/or remote level and local means that
operation is allowed from the IED level. The local/remote switch is also on the control/protection IED
itself, which means that the position of the switch and its validity information are connected internally,
not via I/O boards. When the switch is mounted separately from the IED the signals are connected to
the function via I/O boards.

When the local panel switch (or LHMI selection, depending on the set source to select this) is in Off
position, all commands from remote and local level will be ignored. If the position for the local/remote
switch is not valid the PSTO output will always be set to faulty state (3), which means no possibility to
operate.

To adapt the signals from the local HMI or from an external local/remote switch, the function blocks
LOCREM and LOCREMCTRL are needed and connected to QCBAY.

Permitted Source To Operate (PSTO) M13446-16 v12


The actual state of the operator place is presented by the value of the Permitted Source To Operate,
PSTO signal. The PSTO value is evaluated from the local/remote switch position according to Table
245. In addition, there are two settings and one command that affect the value of the PSTO signal.

When the external switch is in Off position, or invalid position, the output always shows the actual
state of the switch (0 for Off and 3 for Invalid). In these cases, it is not possible to control anything,
and the setting AllPSTOValid has no effect on the PSTO output.

If the setting AllPSTOValid is set to No Priority and the LR-switch position is in Local or Remote
state, the PSTO output is set to 5 (all), that is, it is permitted to operate from local, station and remote
level without any priority.

The LocSta command value is forced to FALSE if AllPSTOValid is set to No priority.

If the setting RemoteIncStation is set to Yes and the LR-switch position is in Remote state, the PSTO
output is set to 2 (Station or Remote), that is, it is permitted to operate from both station and remote
level without any priority.

If the LR-switch position is in Remote state, and AllPSTOValid is set to Priority and RemoteIncStation
is set to No, the switching between station and remote level control is done through the command
LocSta. The command is accessible only through the IEC 61850 Edition 2 protocol.

Transformer protection RET650 353


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Table 245: PSTO values for different Local panel switch positions

Local panel AllPSTOVali RemoteInc LocSta.CtlVa PSTO LED Possible


switch d Station l (command) value indications on locations that
positions (setting) (setting) LHMI shall be able
to operate
0 = Off - - - 0 Remote and Not possible to
Local Off operate
1 = Local Priority - - 1 Remote Off, Local Panel
Local On
1 = Local No priority - - 5 Remote and Local, Station
Local On or Remote
level without
any priority
2 = Remote Priority No TRUE 6 Remote On, Station level
Local Off
2 = Remote Priority No FALSE 7 Remote On, Remote level
Local Off
2 = Remote Priority Yes - 2 Remote On, Station or
Local Off Remote level
2 = Remote No priority - - 5 Remote and Local, Station
Local On or Remote
level without
any priority
3 = Faulty - - - 3 Remote and Not possible to
Local Flashing operate

The PSTO value can be read via IEC 61850 DO CtrlAuthInd.

Blockings M13446-50 v6
The blocking states for position indications and commands are intended to provide the possibility for
the user to make common blockings for the functions configured within a complete bay.

The blocking facilities provided by the bay control function are the following:

• Blocking of position indications, BL_UPD. This input will block all inputs related to apparatus
positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all configured functions
within the bay.

The switching of the Local/Remote switch requires at least system operator level. The password will
be requested at an attempt to operate if authority levels have been defined in the IED, otherwise the
default authority level can handle the control without LogOn. The users and passwords are defined
with the IED Users tool in PCM600.

11.3.5 Local/Remote switch LOCREM IP16319-1 v3

M17086-3 v12
The signals from the local HMI or from an external local/remote switch are connected via the function
blocks local remote (LOCREM) and local remote control (LOCREMCTRL) to the Bay control
(QCBAY) function block. The parameter ControlMode in function block LOCREM is set to choose if
the switch signals are coming from the local HMI or from an external hardware switch connected via
binary inputs.

354 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.3.5.1 Function block M17088-3 v4

LOCREM
CTRLOFF OFF
LOCCTRL LOCAL
REMCTRL REMOTE
LHMICTRL VALID

IEC05000360 V4 EN-US

Figure 187: LOCREM function block

LOCREMCTRL
^PSTO1 HMICTR1
^PSTO2 HMICTR2
^PSTO3 HMICTR3
^PSTO4 HMICTR4
^PSTO5 HMICTR5
^PSTO6 HMICTR6
^PSTO7 HMICTR7
^PSTO8 HMICTR8
^PSTO9 HMICTR9
^PSTO10 HMICTR10
^PSTO11 HMICTR11
^PSTO12 HMICTR12

IEC05000361 V4 EN-US

Figure 188: LOCREMCTRL function block

11.3.5.2 Signals
PID-3944-INPUTSIGNALS v7

Table 246: LOCREM Input signals

Name Type Default Description


CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control

PID-3944-OUTPUTSIGNALS v7

Table 247: LOCREM Output signals

Name Type Description


OFF BOOLEAN Control is disabled
LOCAL BOOLEAN Local control is activated
REMOTE BOOLEAN Remote control is activated
VALID BOOLEAN Outputs are valid

PID-3943-INPUTSIGNALS v6

Table 248: LOCREMCTRL Input signals

Name Type Default Description


PSTO1 INTEGER 0 PSTO input channel 1
PSTO2 INTEGER 0 PSTO input channel 2
PSTO3 INTEGER 0 PSTO input channel 3
PSTO4 INTEGER 0 PSTO input channel 4
PSTO5 INTEGER 0 PSTO input channel 5
PSTO6 INTEGER 0 PSTO input channel 6
PSTO7 INTEGER 0 PSTO input channel 7
PSTO8 INTEGER 0 PSTO input channel 8
Table continues on next page

Transformer protection RET650 355


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Type Default Description


PSTO9 INTEGER 0 PSTO input channel 9
PSTO10 INTEGER 0 PSTO input channel 10
PSTO11 INTEGER 0 PSTO input channel 11
PSTO12 INTEGER 0 PSTO input channel 12

PID-3943-OUTPUTSIGNALS v6

Table 249: LOCREMCTRL Output signals

Name Type Description


HMICTR1 INTEGER Bitmask output 1 to local remote LHMI input
HMICTR2 INTEGER Bitmask output 2 to local remote LHMI input
HMICTR3 INTEGER Bitmask output 3 to local remote LHMI input
HMICTR4 INTEGER Bitmask output 4 to local remote LHMI input
HMICTR5 INTEGER Bitmask output 5 to local remote LHMI input
HMICTR6 INTEGER Bitmask output 6 to local remote LHMI input
HMICTR7 INTEGER Bitmask output 7 to local remote LHMI input
HMICTR8 INTEGER Bitmask output 8 to local remote LHMI input
HMICTR9 INTEGER Bitmask output 9 to local remote LHMI input
HMICTR10 INTEGER Bitmask output 10 to local remote LHMI input
HMICTR11 INTEGER Bitmask output 11 to local remote LHMI input
HMICTR12 INTEGER Bitmask output 12 to local remote LHMI input

11.3.5.3 Settings
PID-3944-SETTINGS v7

Table 250: LOCREM Non group settings (basic)

Name Values (Range) Unit Step Default Description


ControlMode Internal LR-switch - - Internal LR-switch Control mode for internal/external LR-
External LR-switch switch

PID-3943-SETTINGS v2

11.3.5.4 Operation principle M17087-3 v9

The function block Local remote (LOCREM) handles the signals coming from the local/remote switch.
The connections are seen in Figure 189, where the inputs on function block LOCREM are connected
to binary inputs if an external switch is used. When the local HMI is used, the inputs are not used.
The switching between external and local HMI source is done through the parameter ControlMode.
The outputs from the LOCREM function block control the output PSTO (Permitted Source To
Operate) on Bay control (QCBAY).

356 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO 10 HMICTR 10
PSTO 11 HMICTR 11
PSTO 12 HMICTR 12

IEC10000052 V3 EN-US

Figure 189: Configuration for the local/remote handling for a local HMI with two bays and two
screen pages
If the IED contains control functions for several bays, the local/remote position can be different for the
included bays. When the local HMI is used the position of the local/remote switch can be different
depending on which single line diagram screen page that is presented on the local HMI. The function
block Local remote control (LOCREMCTRL) controls the presentation of the LEDs for the local/
remote position to applicable bay and screen page.

The switching of the local/remote switch requires at least system operator level. The password will be
requested at an attempt to operate if authority levels have been defined in the IED. Otherwise the
default authority level, SuperUser, can handle the control without LogOn. The users and passwords
are defined with the IED Users tool in PCM600.

11.3.6 Switch controller SCSWI IP15603-1 v2

11.3.6.1 Functionality M13486-3 v11

The Switch controller (SCSWI) initializes and supervises all functions to properly select and operate
switching primary apparatuses. The Switch controller may handle and operate on one multi-phase
device or up to three one-phase devices.

Transformer protection RET650 357


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.6.2 Function block M13482-3 v5

SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SEL_OP
L_OPEN SEL_CL
L_CLOSE SELECTED
AU_OPEN RES_RQ
AU_CLOSE RES_RQ_OP
BL_CMD RES_RQ_CL
RES_GRT START_SY
RES_EXT CANC_SY
SY_INPRO POSITION
SYNC_OK OPENPOS
EN_OPEN CLOSEPOS
EN_CLOSE POLEDISC
XPOSL1* POS_INTR
XPOSL2* CMD_BLK
XPOSL3* L_CAUSE
XEXINF

IEC05000337 V7 EN-US

Figure 190: SCSWI function block

11.3.6.3 Signals
PID-8269-INPUTSIGNALS v1

Table 251: SCSWI Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
L_SEL BOOLEAN 0 Select signal from local panel
L_OPEN BOOLEAN 0 Open signal from local panel
L_CLOSE BOOLEAN 0 Close signal from local panel
AU_OPEN BOOLEAN 0 Open signal from local automation function
AU_CLOSE BOOLEAN 0 Close signal from local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted at set to true by the synchrocheck
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOSL1 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL2 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL3 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL

358 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

PID-8269-OUTPUTSIGNALS v1

Table 252: SCSWI Output signals

Name Type Description


EXE_OP BOOLEAN Execute command for open direction
EXE_CL BOOLEAN Execute command for close direction
SEL_OP BOOLEAN Selected for open command
SEL_CL BOOLEAN Selected for close command
SELECTED BOOLEAN Select conditions are fulfilled
RES_RQ BOOLEAN Request signal to the reservation function
RES_RQ_OP BOOLEAN Request signal for open direction to the reservation function
RES_RQ_CL BOOLEAN Request signal for close direction to the reservation function
START_SY BOOLEAN Starts the external synchronizing function
CANC_SY BOOLEAN Cancels the external synchronizing function, started through
START_SY
POSITION INTEGER Position indication
OPENPOS BOOLEAN Open position indication
CLOSEPOS BOOLEAN Closed position indication
POLEDISC BOOLEAN The positions for poles L1-L3 are not equal after a set time
POS_INTR BOOLEAN Stopped in intermediate position
CMD_BLK BOOLEAN Commands are blocked
L_CAUSE INTEGER Latest value of the error indication during command
XEXINF GROUP SIGNAL Execution information to XCBR, XSWI & XLNPROXY

GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v4

AU_OPEN and AU_CLOSE are used to issue automated commands. They work without
regard to how the operator place selector, PSTO, is set. In order to have effect on the
outputs EXE_OP and EXE_CL, the corresponding enable input, EN_OPEN respectively
EN_CLOSE must be set, and that no interlocking is active.

L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected to
binary inputs. In order to have effect, the operator place selector, PSTO, must be set to
local or to remote with no priority. Also, the corresponding enable input must be set, and
no interlocking is active. The L_SEL input must always be set before L_OPEN or
L_CLOSE, regardless of the control model. This is to ensure no accidental operations
occur.

If one multi-phase XCBR or two single-phase XCBR is used for a two- or three-phase
system, two or more of the inputs XPOSL1, XPOSL2 and XPOSL3 are connected to the
same source.

Transformer protection RET650 359


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.6.4 Settings
PID-8269-SETTINGS v1

Table 253: SCSWI Non group settings (basic)

Name Values (Range) Unit Step Default Description


CtlModel Dir Norm - - SBO Enh Specifies control model type
Dir Enh
SBO Enh
PosDependent Always permitted - - Always permitted Permission to operate depending on the
Not perm 00/11 position
Not perm cPos
Not perm cPos/
00/11
tSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select and
execute signals
tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request to
reservation granted
tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfil
close conditions
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command execution
to termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy
between the poles
SuppressMidPos Off - - On Mid-position is suppressed during time
On tIntermediate; tIntermediate is set on
each connected XCBR/XSWI function
individually
InterlockChk Sel & Op phase - - Sel & Op phase Selection if interlock check should be
Op phase done in select phase

11.3.6.5 Operation principle


M13484-4 v4
The Switch controller (SCSWI) is provided with verification checks for the select - execute sequence,
that is, checks the conditions prior each step of the operation are fulfilled. The involved functions for
these condition verifications are interlocking, reservation, blockings and synchrocheck.

Control handling M13484-6 v8


.
Two types of control models can be used. The two control models are "direct with normal security"
and "SBO (Select-Before-Operate) with enhanced security". The parameter CtlModel defines which
one of the two control models is used. The control model "direct with normal security" does not
require a select whereas, the "SBO with enhanced security" command model requires a select
before execution. The command sequence for a command with control mode SBO with enhanced
security is shown in figure 191, with control mode direct with normal security is shown in figure 192.

360 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Reservation
Client SCSWI SXCBR
logic
select

SEL_CL = TRUE

RES_RQ = TRUE

tReservation
Response

tSelect
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0

requestedPosition = 10

opRcvd = TRUE
EXE_CL

opOK = TRUE, tOpOk


operateAck/AddCause = 0
operateAck/AddCause = 0
tExecutionFB

POSITION = 00, timeStamp


POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0

POSITION = 10, timeStamp


cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE

RES_RQ = FALSE

RES_GRT = FALSE

IEC16000083=1=en=Original.vsdx
IEC16000083 V1 EN-US

Figure 191: Example of command sequence for a successful close command when the
control model SBO with enhanced security is used

Reservation SwitchCtrl Switch


client
core core core

requestedPosition = 10

opRcvd = TRUE

RES_RQ
tReservation
Response

RES_GRT = TRUE
EXE_CL

opOK = TRUE, tOpOk

operateAck/AddCause = 0 operateAck/AddCause = 0

POSITION = 00, timeStamp POSITION = 00, timeStamp

POSITION = 10, timeStamp


cmdTermination/
POSITION = 10, timeStamp AddCause = 0

RES_RQ = FALSE

RES_GRT = FALSE

IEC15000417-1-en.vsdx

IEC15000417 V1 EN-US

Figure 192: Example of command sequence for a successful close command when the
control model direct with normal security is used
Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command sequence is supervised in three steps, the
selection, command evaluation and the supervision of position. Each step ends up with a pulsed
signal to indicate that the respective step in the command sequence is finished. If an error occurs in
one of the steps in the command sequence, the sequence is terminated. The last error (L_CAUSE)
can be read from the function block and used for example at commissioning.

Before an execution command, an evaluation of the position is done. If the parameter PosDependent
is set to Not perm 00/11 or Not perm cPos/00/11, and the position is in intermediate state or in bad

Transformer protection RET650 361


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

state, the command is rejected with the cause Invalid-position. If the parameter is set to Not perm
cPos or Not perm cPos/00/11 and the command is to move to the current position, the command is
rejected with the cause Position-reached. If the parameter is set to Always permitted the execution
command is sent independent of the position value.

Evaluation of position M13484-14 v5


The position output from the switch (SXCBR) is connected to the switch controller SCSWI. The
XPOSL1, XPOSL2 and XPOSL3 input signals receive the position, time stamps and quality attributes
of the position which is used for further evaluation.

In the case when there are two or more one-phase switches connected to the switch control function,
the switch control will "merge" the position of the switches to the resulting multi-phase position. In the
case when the position differ between the one-phase switches, following principles will be applied:

All switches in open position: switch control position = open


All switches in closed position: switch control position = closed
At least one switch in open position and the switch control position = intermediate
other(s) in closed position:
Any switch in intermediate position: switch control position = intermediate
Any switch in bad state: switch control position = bad state

The time stamp of the output multi-phase position from switch control will have the time stamp of the
last changed phase when it reaches the end position. When it goes to intermediate position or bad
state, it will get the time stamp of the first changed phase.

In addition, there is also the possibility that one of the one-phase switches will change position at any
time due to a trip. Such situation is here called pole discordance and is supervised by this function. In
case of a pole discordance situation, that is, the positions of the one-phase switches are not equal for
a time longer than the setting tPoleDiscord, an error signal POLEDISC will be set.

In the supervision phase, the switch controller function evaluates the "cause" values from the switch
module circuit breaker (SXCBR). At error the "cause" value with highest priority is shown.

Blocking principles M13484-37 v6


The blocking signals are normally coming from the bay control function (QCBAY) or via the IEC
61850 communication from the operator place.

The different blocking possibilities are:

• Block/deblock of command. It is used to block command for operation of position.


• Blocking of function, BLOCK. If the BLOCK signal is set, it means that the function is active, but
no outputs are generated, no reporting, control commands are rejected and functional and
configuration data is visible.

The different block conditions will only affect the operation of this function, that is, no
blocking signals will be "forwarded" to other functions. The above blocking outputs are
stored in a non-volatile memory.

Dependence on operator place GUID-AB327F15-AF44-4ACC-8FA5-2A52AE4AE090 v5


For the commands from a communication protocol, such as IEC 61850-8-1, and through the inputs
L_SEL, L_OPEN and L_CLOSE, the operator place is evaluated, and only the commands from actual
operator place are accepted, see Table 245. Commands through the inputs L_SEL, L_OPEN and
L_CLOSE are always from the local operator place. For commands through the inputs AU_OPEN and
AU_CLOSE, the operator place is only evaluated so that it is not set to Off or is invalid.

362 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Interaction with synchrocheck and synchronizing functions M13484-47 v5


The Switch controller (SCSWI) works in conjunction with the synchrocheck and the synchronizing
function (SESRSYN). It is assumed that the synchrocheck function is continuously in operation and
gives the result to SCSWI. The result from the synchrocheck function is evaluated during the close
execution. If the operator performs an override of the synchrocheck, the evaluation of the
synchrocheck state is omitted. When there is a positive confirmation from the synchrocheck function,
SCSWI will send the close signal EXE_CL to the switch function Circuit breaker (SXCBR).

When there is no positive confirmation from the synchrocheck function, SCSWI will send a start
signal START_SY to the synchronizing function, which will send the closing command to SXCBR
when the synchronizing conditions are fulfilled, see Figure 193. If no synchronizing function is
included, the timer for supervision of the "synchronizing in progress signal" is set to 0, which means
no start of the synchronizing function. SCSWI will then set the attribute "blocked-by-synchrocheck" in
the "cause" signal. See also the time diagram in Figure 197.

SCSWI SXCBR
EXE_CL
OR CLOSE

SYNC_OK
START_SY
CANC_SY
SY_INPRO
SESRSYN

CLOSECB
Synchro Synchronizing
check function

IEC09000209-2-en.vsd
IEC09000209 V2 EN-US

Figure 193: Example of interaction between SCSWI, SESRSYN (synchrocheck and


synchronizing function) and SXCBR function

Time diagrams M13484-51 v8


The Switch controller (SCSWI) function has timers for evaluating different time supervision
conditions. These timers are explained here.

The timer tSelect is used for supervising the time between the select and the execute command
signal, that is, the time the operator has to perform the command execution after the selection of the
object to operate.

select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set

en05000092.vsd
IEC05000092 V1 EN-US

Figure 194: tSelect

Transformer protection RET650 363


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

The Long-operation-time cause (-30) is only given on the output L_CAUSE. It is not sent
on protocols since the selection has already received a positive response, and no
operation has been issued. If an operation is issued after the time out, the negative
response is Object-not-selected.

The parameter tResResponse is used to set the maximum allowed time to make the reservation, that
is, the time between reservation request and the feedback reservation granted from all bays involved
in the reservation function.

select

reservation request RES_RQ

reservation granted RES_GRT


t1>tResResponse, then 1-
tResResponse
of-n-control in 'cause' is
timer t1
set
IEC05000093-2-en.vsd
IEC05000093 V2 EN-US

Figure 195: tResResponse


The timer tExecutionFB supervises the time between the execute command and the command
termination, see Figure 196.

execute command

position L1 open

close

position L2 open

close

position L3 open

close

cmd termination L1

cmd termination L2

cmd termination L3

cmd termination *

position open

close

t1>tExecutionFB, then
tExecutionFB timer long-operation-time in
t1 'cause' is set

* The cmd termination will be delayed one execution sample . APCtExecutionFB=IEC0


5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US

Figure 196: tExecutionFB


The parameter tSynchrocheck is used to define the maximum allowed time between the execute
command and the input SYNC_OK to become true. If SYNC_OK=true at the time the execute
command signal is received, the timer "tSynchrocheck" will not start. The start signal for the
synchronizing is obtained if the synchrocheck conditions are not fulfilled.

364 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

The parameter tSynchronizing is used to define the maximum allowed time between the start signal
for synchronizing and the confirmation that synchronizing is in progress.

execute command

SYNC_OK

tSynchrocheck
t1
START_SY

SY_INPRO

tSynchronizing t2>tSynchronizing, then


t2 blocked-by-synchrocheck in
'cause' is set

en05000095.vsd
IEC05000095 V1 EN-US

Figure 197: tSynchroCheck and tSynchronizing

11.3.6.6 Interaction with switch on process bus GUID-1E243260-55FC-4DA6-A314-649E0B95A2B9 v2

When the switches are modelled and controlled in a breaker IED, the information from the switches is
limited to those described in the IEC 61850 standard.

Since there is no expression for distributing the cause of failure over GOOSE, the XLNPROXY
function is used for evaluating the causes normally evaluated by the SXCBR function.

Further, in some cases selection may also be used on the model of the switch in the breaker IED, in
case multiple controllers may access it via GOOSE. In such a case, if the input for the stSeld data
attribute in the XLNPROXY function is connected, SCSWI automatically awaits that the switch is
selected before accepting the selection. Also, if the seSeld data attribute is set before the selection is
requested, the selection request fails.
Reservation
Client SCSWI XLNPROXY XCBR
logic
select

SEL_CL = TRUE SelCls.stVal = TRUE

RES_RQ = TRUE SEL_CL = TRUE


tReservation
Response

tSelect

RES_GRT = TRUE
SELECTED = TRUE Pos.stSeld = TRUE
SELECTED = TRUE
selectAck/AddCause = 0

requestedPosition = 10

opRcvd = TRUE
OpCls.stVal = TRUE

opOK = TRUE, tOpOk Pos.OpRcvd = TRUE

operateAck/AddCause = 0 operateAck/AddCause = 0 Pos.OpOk = TRUE


POSITION = 00
tExecutionFB

timeStamp = Pos.t Pos.stVal = 00, Pos.t


POSITION = 00, timeStamp
POSITION = 10,
timeStamp = Pos.t
cmdTermination/AddCause = 0 Pos.stVal = 10, Pos.t

POSITION = 10, timeStamp SELECTED = FALSE Pos.stSeld = FALSE

cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE

RES_RQ = FALSE

RES_GRT = FALSE

IEC16000084=1=en=Original.vsdx

IEC16000084 V1 EN-US

Figure 198: Example of command sequence for a successful close command when the
control model SBO with enhanced security is used and selection is used for the
XCBR in the breaker IED

Transformer protection RET650 365


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.7 Circuit breaker SXCBR IP15614-1 v3

11.3.7.1 Functionality M13489-3 v6

The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and to perform
the control operations, that is, pass all the commands to primary apparatuses in the form of circuit
breakers via binary output boards and to supervise the switching operation and position.

11.3.7.2 Function block M13500-3 v5

SXCBR
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
CBOPCAP CLOSEPOS
TR_OPEN TR_POS
TR_CLOSE CNT_VAL
RS_CNT L_CAUSE
EEH_WARN EEHEALTH
EEH_ALM CBOPCAP
XIN
IEC05000338-6-en.vsdx
IEC05000338 V6 EN-US

Figure 199: SXCBR function block

11.3.7.3 Signals
PID-6799-INPUTSIGNALS v3

Table 254: SXCBR Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
CBOPCAP INTEGER 3 Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO, 5
= COCO, 6+ = More
TR_OPEN BOOLEAN 0 Signal for open position of truck from I/O
TR_CLOSE BOOLEAN 0 Signal for close position of truck from I/O
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

366 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

PID-6799-OUTPUTSIGNALS v3

Table 255: SXCBR Output signals

Name Type Description


XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm, 2=Warning,
3=Alarm
CBOPCAP INTEGER Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO, 5
= COCO, 6+ = More

11.3.7.4 Settings
PID-6799-SETTINGS v3

Table 256: SXCBR Non group settings (basic)

Name Values (Range) Unit Step Default Description


tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial count
value)

11.3.7.5 Operation principle


M13487-4 v9
The circuit breaker function (SXCBR) is used by other functions such as, for example, switch
controller, protection functions, autorecloser function or an IEC 61850 client residing in another IED
or the operator place. The SXCBR function executes commands, evaluates block conditions and
evaluates different time supervision conditions. Only if all conditions indicate a switch operation to be
allowed, the function performs the execution command. In case of erroneous conditions, the function
indicates an appropriate "cause" value, see Table 239.

SXCBR has an operation counter for closing and opening commands. The counter value can be read
remotely from the operator place. The value is reset from local HMI, a binary input or remotely from
the operator place by configuring a signal from the Single Point Generic Control 8 signals
(SPC8GAPC) for example. The health of the external equipment, the switch, can be monitored
according to IEC 61850-8-1. The operation counter functionality and the external equipment health
supervision are independent sub-functions of the circuit breaker function.

Transformer protection RET650 367


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Local/Remote switch M13487-7 v4


One binary input signal LR_SWI is included in SXCBR to indicate the local/remote switch position
from switchyard provided via the I/O board. If this signal is set to TRUE it means that change of
position is allowed only from switchyard level. If the signal is set to FALSE it means that command
from IED or higher level is permitted. When the signal is set to TRUE all commands (for change of
position) are rejected, even trip commands from protection functions are rejected. The functionality of
the local/remote switch is described in Figure 200.

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 200: Local/Remote switch

Blocking principles M13487-12 v7


SXCBR includes several blocking principles. The basic principle for all blocking signals is that they
will affect commands from all other clients for example, switch controller, protection functions and
autoreclosure.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for the open command. Note that
this block signal also affects the input OPEN for immediate command.
• Block/deblock for close command. It is used to block operation for the close command. Note that
this block signal also affects the input CLOSE for immediate command.
• Update block/deblock of positions. It is used to block the updating of position values. Other
signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional and
configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M13487-22 v5
The substitution part in SXCBR is used for manual set of the position and quality of the switch. The
typical use of substitution is that an operator enters a manual value because that the real process
value is erroneous for some reason. SXCBR will then use the manually entered value instead of the
value for positions determined by the process.

It is always possible to make a substitution, independently of the position indication and


the status information of the I/O board. When substitution is enabled, the other signals
related to the position follow the substituted position. The substituted values are stored in
a non-volatile memory. If the function is blocked or blocked for update when the
substitution is released, the position value is kept the same as the last substitution value,
but the quality is changed to "questionable, old data", indicating that the value is old and
not reliable.

When the position of the SXCBR is substituted, its IEC 61850-8-1 data object is marked
as “substituted", in addition to the substituted quality, but the position quality of the
connected SCSWI is not dependent on the substitution indication in the quality, so it does
not show that it is derived from a substituted value.

368 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Time diagrams M13487-28 v6


There are two timers for supervising of the execute phase, tStartMove and tIntermediate. tStartMove
supervises that the primary device starts moving after the execute output pulse is sent. tIntermediate
defines the maximum allowed time for intermediate position. Figure 201 explains these two timers
during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 201: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the minimum length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration parameter
AdaptivePulse. Figure 202 shows the principle of the execute output pulse. The AdaptivePulse
parameter will have effect on both execute output pulses. However, as long as the OPEN or CLOSE
inputs are active, the corresponding execute output will remain active if the operation is allowed, thus
overriding AdaptivePulse parameter.

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 202: Execute output pulse


If the pulse is set to be adaptive and the activating input is not still active, it is not possible for the
pulse to exceed tOpenPulse or tClosePulse.

The execute output pulses are reset when the activating input is reset and either of the following
happens:

Transformer protection RET650 369


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

• the new expected final position is reached and the configuration parameter AdaptivePulse is set
to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch not start moving, that is tStartMove has elapsed for normal
commands, or tIntermediate has elapsed starting from intermediate position, and the position
indications are valid.

If either of the position inputs are invalid or unconnected, the combined position is considered as
invalid. Then the execute output pulse resets at earliest when time tOpenPulse or tClosePulse has
elapsed.

If the breaker reaches the final position before the execution pulse time has elapsed, and
AdaptivePulse is not true, then the function waits for the end of the execution pulse
before indicating the activating function that the command is complete.

If the activating input remains active when the breaker has reached its final position and
the execution pulse time has elapsed, then the function waits for the reset of the
activating input before indicating that the command is complete.

There is one exception to the first item above: if the primary device is in open position and an open
command is executed or if the primary device is in closed position and a close command is executed.
In these cases, with the additional condition that the configuration parameter AdaptivePulse is true,
the execute output pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false, the execution output remains active until the
pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS=1) when a
command is executed, the execute output pulse resets at earliest when timer tOpenPulse
or tClosePulse has elapsed.

An example of when a primary device is open and an open command is executed is shown in
Figure 203 .

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 203: Open command when valid open position is indicated

11.3.8 Circuit switch SXSWI IP15620-1 v2

370 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.3.8.1 Functionality M16492-3 v6

The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to primary apparatuses in the form of
disconnectors or earthing switches via binary output boards and to supervise the switching operation
and position.

11.3.8.2 Function block M13504-3 v5

SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
SWOPCAP CLOSEPOS
RS_CNT CNT_VAL
EEH_WARN L_CAUSE
EEH_ALM EEHEALTH
XIN SWOPCAP

IEC05000339-5-en.vsdx
IEC05000339 V5 EN-US

Figure 204: SXSWI function block

11.3.8.3 Signals
PID-6800-INPUTSIGNALS v4

Table 257: SXSWI Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
SWOPCAP INTEGER 4 Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

PID-6800-OUTPUTSIGNALS v4

Table 258: SXSWI Output signals

Name Type Description


XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
Table continues on next page

Transformer protection RET650 371


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Type Description


OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm, 2=Warning,
3=Alarm
SWOPCAP INTEGER Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C

11.3.8.4 Settings
PID-6800-SETTINGS v4

Table 259: SXSWI Non group settings (basic)

Name Values (Range) Unit Step Default Description


tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break - - Disconnector 1=LoadBreak,2=Disconnector,3=EarthSw,
Disconnector 4=HighSpeedEarthSw
Earthing Switch
HS Earthing Switch
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial count
value)

11.3.8.5 Operation principle


M16494-3 v9
The users of the Circuit switch (SXSWI) are other functions such as for example, switch controller,
protection functions, autorecloser function, or a 61850 client residing in another IED or the operator
place. SXSWI executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate that a switch operation is to be allowed, SXSWI
performs the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value, see Table 239.

SXSWI has an operation counter for closing and opening commands. The counter value can be read
remotely from the operator place. The value is reset from a binary input or remotely from the operator
place by configuring a signal from the Single Point Generic Control 8 signals (SPC8GAPC), for
example.

Also, the health of the external equipment, the switch, can be monitored according to IEC 61850-8-1.

Local/Remote switch M16494-6 v5


One binary input signal LR_SWI is included in SXSWI to indicate the local/remote switch position
from switchyard provided via the I/O board. If this signal is set to TRUE it means that change of
position is allowed only from switchyard level. If the signal is set to FALSE it means that command
from IED or higher level is permitted. When the signal is set to TRUE all commands (for change of
position) from internal IED clients are rejected. The functionality of the local/remote switch is
described in Figure 205.

372 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 205: Local/Remote switch

Blocking principles M16494-11 v6


SXSWI includes several blocking principles. The basic principle for all blocking signals is that they
will affect commands from all other clients for example, switch controller, protection functions and
autorecloser.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for open command.
• Block/deblock for close command. It is used to block operation for close command.
• Update block/deblock of positions. It is used to block the updating of position values. Other
signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional and
configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M16494-21 v7
The substitution part in SXSWI is used for manual set of the position and quality of the switch. The
typical use of substitution is that an operator enters a manual value because the real process value is
erroneous of some reason. SXSWI will then use the manually entered value instead of the value for
positions determined by the process.

It is always possible to make a substitution, independently of the position indication and


the status information of the I/O board. When substitution is enabled, the other signals
related to the position follow the substituted position. The substituted values are stored in
a non-volatile memory. If the function is blocked or blocked for update when the
substitution is released, the position value is kept the same as the last substitution value,
but the quality is changed to "questionable, old data", indicating that the value is old and
not reliable.

When the position of the SXSWI is substituted, its IEC 61850-8-1 data object is marked
as “substituted", in addition to the substituted quality, but the position quality of the
connected SCSWI is not dependent on the substitution indication in the quality, so it does
not show that it is derived from a substituted value.

Time diagrams M16494-26 v7


There are two timers for supervising of the execute phase, tStartMove and tIntermediate. tStartMove
supervises that the primary device starts moving after the execute output pulse is sent. tIntermediate
defines the maximum allowed time for intermediate position. Figure 206 explains these two timers
during the execute phase.

Transformer protection RET650 373


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 206: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be sent to the
primary equipment. Note that the output pulses for open and close command can have different
pulse lengths. The pulses can also be set to be adaptive with the configuration parameter
AdaptivePulse. Figure 207 shows the principle of the execute output pulse. The AdaptivePulse
parameter will have effect on both execute output pulses.

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 207: Execute output pulse


If the pulse is set to be adaptive and the activating input is not still active, it is not possible for the
pulse to exceed tOpenPulse or tClosePulse.

For the SXSWI the activating inputs should be pulsed, however, the functionality of following them is
the same as for SXCBR.

The execute output pulses are reset when the activating input is reset and either of the following
happens:

374 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

• the new expected final position is reached and the configuration parameter AdaptivePulse is set
to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch not start moving, that is tStartMove has elapsed for normal
commands, or tIntermediate has elapsed starting from intermediate position, and the position
indications are valid.

If either of the position inputs are invalid or unconnected, the combined position is considered as
invalid. Then the execute output pulse resets at earliest when time tOpenPulse or tClosePulse has
elapsed.

If the controlled primary device reaches the final position before the execution pulse time
has elapsed, and AdaptivePulse is not true, the function waits for the end of the execution
pulse before indicating the activating function that the command is completed.

If the activating input remains active when the switch has reached its final position and
the execution pulse time has elapsed, the function waits for the reset of the activating
input before indicating that the command is completed.

There is one exception from the first item above. If the primary device is in open position and an
open command is executed or if the primary device is in close position and a close command is
executed. In these cases, with the additional condition that the configuration parameter
AdaptivePulse is true, the execute output pulse is always activated and resets when tStartMove has
elapsed. If the configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when a
command is executed the execute output pulse resets only when timer tOpenPulse or
tClosePulse has elapsed.

An example when a primary device is open and an open command is executed is shown in
Figure 208.

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 208: Open command with open position indication

Transformer protection RET650 375


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.9 Proxy for signals from switching device via GOOSE XLNPROXY

11.3.9.1 Functionality GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1

The proxy for signals from switching device via GOOSE (XLNPROXY) gives an internal
representation of the position status and control response for a switch modelled in a breaker IED.
This representation is identical to that of an SXCBR function.

11.3.9.2 Function block GUID-408513CD-A87E-45E8-8E44-24E153947F02 v1

XLNPROXY
BEH* XPOS
BEH_VALID* SELECTED
LOC* OP_BLKD
LOC_VALID* CL_BLKD
BLKOPN* OPENPOS
BLKOPN_V* CLOSEPOS
BLKCLS* CNT_VAL
BLKCLS_V* L_CAUSE
POSVAL* EEHEALTH
POSVAL_V* OPCAP
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN

IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US

Figure 209: XLNPROXY function block

11.3.9.3 Signals
PID-6712-INPUTSIGNALS v3

Table 260: XLNPROXY Input signals

Name Type Default Description


BEH INTEGER -1 Behaviour
BEH_VLD BOOLEAN 0 Valid data on BEH input
LOC BOOLEAN 0 Local control behaviour
LOC_VLD BOOLEAN 0 Valid data on LOC input
BLKOPN BOOLEAN 0 Block opening
BLKOPN_VLD BOOLEAN 0 Valid data on BLKOPN input
BLKCLS BOOLEAN 0 Block closing
BLKCLS_VLD BOOLEAN 0 Valid data on BLKCLS input
POSVAL INTEGER 0 Switch position, Pos.stVal
POSVAL_VLD BOOLEAN 0 Valid data on POSVAL input
OPCNT INTEGER -1 Operation counter
OPCNT_VLD BOOLEAN 0 Valid data on OPCNT input
BLK BOOLEAN 0 Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN 0 Valid data on BLK input
Table continues on next page

376 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Type Default Description


STSELD BOOLEAN 0 The controllable data is in the status "selected”
STSELD_VLD BOOLEAN 0 Valid data on STSELD input
OPRCVD BOOLEAN 0 Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN 0 Valid data on OPRCVD input
OPOK BOOLEAN 0 Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN 0 Valid data on OPOK input
EEHEALTH INTEGER -1 External equipment health
EEHEALTH_VLD BOOLEAN 0 Valid data on EEHEALTH input
OPCAP INTEGER -1 Operating capability
OPCAP_VLD BOOLEAN 0 Valid data on OPCAP input
COMMVALID BOOLEAN 0 Communication valid
XIN GROUP - Execution information from CSWI
SIGNAL

PID-6712-OUTPUTSIGNALS v3

Table 261: XLNPROXY Output signals

Name Type Description


XPOS GROUP SIGNAL Group connection to CSWI
SELECTED BOOLEAN Select conditions are fulfilled
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm, 2=Warning,
3=Alarm
OPCAP INTEGER Switch / breaker operating capability

11.3.9.4 Settings
PID-6712-SETTINGS v3

Table 262: XLNPROXY Non group settings (basic)

Name Values (Range) Unit Step Default Description


SwitchType Circuit Breaker - - Circuit Breaker 0 = CB, 1 = Load Break, 2 =
Load Break Disconnector, 3 = Earthing Switch, 4 =
Disconnector High Speed Earthing Switch
Earthing Switch
HS Earth Switch
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position

GUID-A4CCC681-D4D8-4534-905D-1D8AD40E923B v1

The default values of the inputs BEH, OPCNT, EEHEALTH and OPCAP are set to -1 to
denote that they are not connected.

Transformer protection RET650 377


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.9.5 Operation principle GUID-D2679E0E-ABB5-46F0-AD9C-F6E8E8099534 v1

The proxy for signals from switching device via GOOSE (XLNPROXY) is intended to be used when
the switch (XCBR) is modelled and controlled in a breaker IED or similar unit on the process bus.
XLNPROXY packages the signals from the GOOSE receive function, normally GOOSEXLNRCV, into
the same format as used from SXCBR to SCSWI. It makes a similar evaluation of the command
response as SXCBR when a command is issued from the connected SCSWI.

11.3.9.6 Position supervision GUID-95C72346-A577-4F0A-8584-8E1593B9B947 v1

XLNPROXY has two outputs for position indication: OPENPOS and CLOSEPOS. Position is a
double point indication and the OPENPOS and CLOSEPOS are binary outputs intended to be used
for condition logics to protection and control functions

Normally, the position outputs, OPENPOS and CLOSEPOS, follow the value of the input POSVAL.
However, if the POSVAL_V input is FALSE, the communication is lost (COMMVALID = FALSE), or
the quality of the position received is bad, the OPENPOS and CLOSEPOS are both set to FALSE.

11.3.9.7 Command response evaluation GUID-A2CDC1AE-A6F5-478B-B6E5-3442C54212D8 v3

The command evaluation is triggered through the group input XIN that is connected to the SCSWI
function controlling the switch.

If an operation is initiated by the SCSWI, the XLNPROXY function checks if the switch is blocked for
the operation direction and that the position moves to the desired position within the two time limits
tStartMove and tIntermediate. The default values for tStartMove and tIntermediate are for a breaker.
The typical values for a disconnector are:

• tStartMove = 3s
• tIntermediate = 15s

In most cases, tStartMove and tIntermediate can be set to the same values as in the
source XCBR function. However, if the time limits are set very close to the actual
movement times of the apparatus, compensation may be needed for the communication
delays and differences in cycle time of the XLNPROXY function and the source function.
The compensation should be in the range of 0 - 5ms.

When the switch has started moving, it issues a response to the SCSWI function that the operation
has started. If it does not start moving within tStartMove, the command is deemed as failed, and a
cause is raised on the L_CAUSE output and sent to the SCSWI. The different causes it can identify
are listed in order of priority in table 1. The detection of the different ways of blocking is done while
waiting for movement of the switch, but the cause is not given until the tStartMove has elapsed.

Table 263: Possible cause values from XLNPROXY

IEC 61850 IEC 61850 Cause Description Conditions


ED1 ED2
8 8 Blocked-by-Mode The BEH input is 5.
2 2 Blocked-by-switching-hierarchy The LOC input indicates that only local commands are
allowed for the breaker IED function.
-24 9 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is
blocked for open commands.
-25 9 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is blocked
for close commands.
9 9 Blocked-by-process If the Blk input is connected and active indicating that the
switch is dynamically blocked. Or if the OPCAP input is
connected, it indicates that the operation capability of the
switch is not enough to perform the command.
Table continues on next page

378 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

IEC 61850 IEC 61850 Cause Description Conditions


ED1 ED2
5 5 Position-reached Switch is already in the intended position.
-33 16 Switch-not-start-moving Switch did not start moving within tStartMove.
-34 4 Persistent-intermediate-state The switch stopped in intermediate state for longer than
tIntermediate.
-35 4 Switch-returned-to-init-pos Switch returned to the initial position.
-32 4 Switch-in-bad-state Switch is in a bad position.
-33 4 Not-expected-final-position Switch did not reach the expected final position.

The L_CAUSE output keeps its output value until a new command sequence has been started.

If the quality of the position or the communication becomes bad, the command evaluation replaces
the uncertain position value with intermediate position. Thus, as long as the quality is bad, all
commands will result in the cause Persistant-intermediate-state, -32.

If the switch in the merging unit has the behaviour set to Test or Test blocked, when the IED has
the behaviour On or Blocked, all data from the switch is regarded as invalid. Thus, any command
will fail with the cause PersistantiIntermediate-state, -32, and if selection is used for the switch, all
attempts to select the connected SCSWI will fail with the cause Select-failed, 3, from the SCSWI.

It is possible to speed up the command response for when the command has been started by the
switch in the breaker IED by connecting the inputs OPOK and OPOK_VAL. Then the blocking check
is only done until OPOK is activated and confirmation of that the command has been started is given
to the SCSWI function.

If the inputs STSELD and STSELD_V are connected, the switch in the breaker IED is assumed to
use selection. Then the SCSWI will wait for a selected indication, STSELD input of XLNPROXY,
before accepting selection, this information is transferred to the SCSWI function from the
XLNPROXY through the group connection XPOS. If STSELD is not activated within tSelect of the
SCSWI function, the selection is deemed failed and it gives a negative selection acknowledgement to
the command issuer with the cause Select-failed. Further, if the communication is lost, or the data
received is deemed invalid, the selection will also fail with cause Select-failed from the SCSWI.

11.3.10 Bay reserve QCRSV IP15629-1 v2

11.3.10.1 Functionality M13506-3 v5

The purpose of the reservation (QCRSV) function is primarily to transfer interlocking information
between IEDs in a safe way and to prevent double operation in a bay, switchyard part, or complete
substation.

Transformer protection RET650 379


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.3.10.2 Function block M13509-3 v3

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
IEC05000340-3-en.vsdx
IEC05000340 V3 EN-US

Figure 210: QCRSV function block

11.3.10.3 Signals
PID-3561-INPUTSIGNALS v7

Table 264: QCRSV Input signals

Name Type Default Description


EXCH_IN INTEGER 0 Used for exchange signals between different BayRes blocks
RES_RQ1 BOOLEAN 0 Signal for app. 1 that requests to do a reservation
RES_RQ2 BOOLEAN 0 Signal for app. 2 that requests to do a reservation
RES_RQ3 BOOLEAN 0 Signal for app. 3 that requests to do a reservation
RES_RQ4 BOOLEAN 0 Signal for app. 4 that requests to do a reservation
RES_RQ5 BOOLEAN 0 Signal for app. 5 that requests to do a reservation
RES_RQ6 BOOLEAN 0 Signal for app. 6 that requests to do a reservation
RES_RQ7 BOOLEAN 0 Signal for app. 7 that requests to do a reservation
RES_RQ8 BOOLEAN 0 Signal for app. 8 that requests to do a reservation
BLOCK BOOLEAN 0 Reservation is not possible and the output signals are reset
OVERRIDE BOOLEAN 0 Signal to override the reservation
RES_DATA INTEGER 0 Reservation data coming from function block ResIn

PID-3561-OUTPUTSIGNALS v7

Table 265: QCRSV Output signals

Name Type Description


RES_GRT1 BOOLEAN Reservation is made and the app. 1 is allowed to operate
RES_GRT2 BOOLEAN Reservation is made and the app. 2 is allowed to operate
RES_GRT3 BOOLEAN Reservation is made and the app. 3 is allowed to operate
RES_GRT4 BOOLEAN Reservation is made and the app. 4 is allowed to operate
RES_GRT5 BOOLEAN Reservation is made and the app. 5 is allowed to operate
RES_GRT6 BOOLEAN Reservation is made and the app. 6 is allowed to operate
RES_GRT7 BOOLEAN Reservation is made and the app. 7 is allowed to operate
RES_GRT8 BOOLEAN Reservation is made and the app. 8 is allowed to operate
RES_BAYS BOOLEAN Request for reservation of other bays
ACK_TO_B BOOLEAN Acknowledge to other bays that this bay is reserved
RESERVED BOOLEAN Indicates that the bay is reserved
EXCH_OUT INTEGER Used for exchange signals between different BayRes blocks

380 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.3.10.4 Settings
PID-3561-SETTINGS v7

Table 266: QCRSV Non group settings (basic)

Name Values (Range) Unit Step Default Description


tCancelRes 0.000 - 60.000 s 0.001 10.000 Supervision time for canceling the
reservation
ParamRequest1 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 1
ParamRequest2 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 2
ParamRequest3 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 3
ParamRequest4 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 4
ParamRequest5 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 5
ParamRequest6 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 6
ParamRequest7 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 7
ParamRequest8 Other bays res. - - Only own bay res. Reservation of the own bay only, at
Only own bay res. selection of apparatus 8

11.3.10.5 Operation principle


M13505-4 v3
The Bay reserve (QCRSV) function handles the reservation. QCRSV function starts to operate in two
ways. It starts when there is a request for reservation of the own bay or if there is a request for
reservation from another bay. It is only possible to reserve the function if it is not currently reserved.
The signal that can reserve the own bay is the input signal RES_RQx (x=1-8) coming from switch
controller (SCWI). The signals for request from another bay are the outputs RE_RQ_B and
V_RE_RQ from function block RESIN. These signals are included in signal EXCH_OUT from RESIN
and are connected to RES_DATA in QCRSV.

The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay only (TRUE) or
other bays (FALSE). To reserve the own bay only means that no reservation request RES_BAYS is
created.

Reservation request of own bay M13505-7 v2


If the reservation request comes from the own bay, the function QCRSV has to know which
apparatus the request comes from. This information is available with the input signal RES_RQx and
parameter ParamRequestx (where x=1-8 is the number of the requesting apparatus). In order to
decide if a reservation request of the current bay can be permitted QCRSV has to know whether the
own bay already is reserved by itself or another bay. This information is available in the output signal
RESERVED.

If the RESERVED output is not set, the selection is made with the output RES_GRTx (where x=1-8 is
the number of the requesting apparatus), which is connected to switch controller SCSWI. If the bay
already is reserved the command sequence will be reset and the SCSWI will set the attribute "1-of-n-
control" in the "cause" signal.

Reservation of other bays M13505-11 v2


When the function QCRSV receives a request from an apparatus in the own bay that requires other
bays to be reserved as well, it checks if it already is reserved. If not, it will send a request to the other
bays that are predefined (to be reserved) and wait for their response (acknowledge). The request of
reserving other bays is done by activating the output RES_BAYS.

Transformer protection RET650 381


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

When it receives acknowledge from the bays via the input RES_DATA, it sets the output RES_GRTx
(where x=1-8 is the number of the requesting apparatus). If not acknowledgement from all bays is
received within a certain time defined in SCSWI (tResResponse), the SCSWI will reset the
reservation and set the attribute "1-of-n-control" in the "cause" signal.

Reservation request from another bay M13505-15 v2


When another bay requests for reservation, the input BAY_RES in corresponding function block
RESIN is activated. The signal for reservation request is grouped into the output signal EXCH_OUT
in RESIN, which is connected to input RES_DATA in QCRSV. If the bay is not reserved, the bay will
be reserved and the acknowledgment from output ACK_T_B is sent back to the requested bay. If the
bay already is reserved the reservation is kept and no acknowledgment is sent.

Blocking and overriding of reservation M13505-18 v4


If QCRSV function is blocked (input BLOCK is set to true) the reservation is blocked. That is, no
reservation can be made from the own bay or any other bay. This can be set, for example, via a
binary input from an external device to prevent operations from another operator place at the same
time.

The reservation function can also be overridden in the own bay with the OVERRIDE input signal, that
is, reserving the own bay without waiting for the external acknowledge.

Bay with more than eight apparatuses M13505-22 v6


If only one instance of QCRSV is used for a bay that is, use of up to eight apparatuses, the input
EXCH_IN must be set to zero.

If there are more than eight apparatuses in the bay, there has to be one additional QCRSV. The two
QCRSV functions have to communicate and this is done through the input EXCH_IN and
EXCH_OUT according to Figure 211. If more than one QCRSV are used, the execution order is very
important. The execution order must be in the way that the first QCRSV has a lower number than the
next one.

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLOCK ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS

1
BLOCK ACK_TO_B RESERVED
OVERRIDE RESERVED
RES_DATA EXCH_OUT

IEC05000088-3-en.vsdx
IEC05000088 V3 EN-US

Figure 211: Connection of two QCRSV function blocks

382 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.3.11 Reservation input RESIN IP15650-1 v2

11.3.11.1 Functionality M16501-3 v6

The Reservation input (RESIN) function receives the reservation information from other bays. The
number of instances is the same as the number of involved bays (up to 60 instances are available).

11.3.11.2 Function block M13512-3 v4

RESIN1
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

IEC05000341-2-en.vsd
IEC05000341 V2 EN-US

Figure 212: RESIN1 function block

RESIN2
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN-US

Figure 213: RESIN2 function block

11.3.11.3 Signals
PID-3629-INPUTSIGNALS v7

Table 267: RESIN1 Input signals

Name Type Default Description


BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req. from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

PID-3629-OUTPUTSIGNALS v7

Table 268: RESIN1 Output signals

Name Type Description


ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn blocks

Transformer protection RET650 383


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

PID-3630-INPUTSIGNALS v7

Table 269: RESIN2 Input signals

Name Type Default Description


EXCH_IN INTEGER 5 Used for exchange signals between different ResIn blocks
BAY_ACK BOOLEAN 0 Another bay has acknow. the reservation req. from this bay
BAY_VAL BOOLEAN 0 The reserv. and acknow. signals from another bay are valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay

PID-3630-OUTPUTSIGNALS v7

Table 270: RESIN2 Output signals

Name Type Description


ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn blocks

11.3.11.4 Settings
PID-3629-SETTINGS v7

Table 271: RESIN1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


FutureUse Bay in use - - Bay in use The bay for this ResIn block is for future
Bay future use use

PID-3630-SETTINGS v7

Table 272: RESIN2 Non group settings (basic)

Name Values (Range) Unit Step Default Description


FutureUse Bay in use - - Bay in use The bay for this ResIn block is for future
Bay future use use

11.3.11.5 Operation principle M16503-3 v7

The reservation input (RESIN) function is based purely on Boolean logic conditions. The logic
diagram in Figure 214 shows how the output signals are created. The inputs of the function block are
connected to a receive function block representing signals transferred over the station bus from
another bay.

384 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

EXCH_IN INT

BIN

ACK_F_B
&
FutureUse
³1

ANY_ACK
BAY_ACK ³1

VALID_TX
&

BAY_VAL ³1

RE_RQ_B
³1

BAY_RES &
V _RE_RQ
³1

BIN
EXCH_OUT
INT

en05000089.vsd
IEC05000089 V1 EN-US

Figure 214: Logic diagram for RESIN


Figure 215 describes the principle of the data exchange between all RESIN modules in the current
bay. There is one RESIN function block per "other bay" used in the reservation mechanism. The
output signal EXCH_OUT in the last RESIN functions are connected to the module bay reserve
(QCRSV) that handles the reservation function in the own bay.

Transformer protection RET650 385


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA

en05000090.vsd
IEC05000090 V2 EN-US

Figure 215: Diagram of the chaining principle for RESIN

11.4 Voltage control SEMOD158732-1 v3

11.4.1 Function revision history GUID-7745F0C2-DA10-4855-AEE1-E6E344668647 v1

Document revision Product revision History


A 2.2.4 -
A 2.2.5 -
B 2.2.6 Execution described when command URAISE or ULOWER is given to
the tap changer mechanism.
tStable setting influence described when reporting a new tap changer
position.
Binary input BLOCK added to the tap changer function.

11.4.2 Identification
SEMOD173054-2 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Automatic voltage control for tap TR1ATCC 90
changer, single control
U

IEC10000165 V1 EN-US

Tap changer control and supervision, 6 TCMYLTC 84


binary inputs

IEC10000165000 V1 EN-US

386 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.4.3 Functionality M5864-3 v13

Automatic voltage control for tap changer, single control (TR1ATCC ) and Tap changer control and
supervision, 6 binary inputs (TCMYLTC) are used for control of power transformers with an on-load
tap changer. The functions provide automatic regulation of the voltage on the secondary side of
transformers or alternatively on a load point further out in the network.

Voltage control includes many extra features such as extensive tap changer monitoring including
contact wear and hunting detection, monitoring of the power flow in the transformer so that, for
example, the voltage control can be blocked if the power reverses, etc.

11.4.4 Automatic voltage control for tap changer, TR1ATCC SEMOD158820-1 v4

SEMOD158823-5 v6
The Automatic voltage control for tap changer function controls the voltage on the LV side of a
transformer either automatically or manually. The automatic control can be for a single transformer.

11.4.4.1 Operation principle


SEMOD158880-5 v7
The LV-side of the transformer is used as the voltage measuring point. If necessary, the LV side
current is used as load current to calculate the line-voltage drop to the regulation point.

In addition, all three-phase currents from the HV-winding (usually the winding where the tap changer
is situated) are used by the Automatic voltage control for tap changer function for over current
blocking.

The setting MeasMode is a selection of single-phase, or phase-phase, or positive sequence quantity.


It is to be used for voltage and current measurement on the LV-side. The involved phases are also
selected. Thus, single-phases as well as phase-phase or three-phase feeding on the LV-side is
possible but it is commonly selected for current and voltage.

The analog input signals are normally common for other functions in the IED for example, protection
functions.

The measured LV-busbar voltage is designated UB, the measured load current IL and the
caluculated load point voltage UL.

The UB magnitude value is always given as the corresponding phase-to-phase voltage magnitude
irrespective of actually used measurement mode. Additionally, its magnitude value is internally
derived as an average value among the last 20 measurements. That increases the ATCC function
accuracy but make its time response somewhat slower for a step change in the input voltage signal.

Automatic voltage control for tap changer, single control TR1ATCC SEMOD158887-4 v7
Automatic voltage control for tap changer, single control TR1ATCC measures the magnitude of the
busbar voltage UB. If no other additional features are enabled (line voltage drop compensation), this
voltage is further used for voltage regulation.

TR1ATCC then compares this voltage with the set voltage, USet and decides which action should be
taken. To avoid unnecessary commands around the setpoint, a deadband (degree of insensitivity) is
introduced. The deadband is symmetrical around USet, see figure 216, and it is arranged in such a
way that there is an outer and an inner deadband. Measured voltages outside the outer deadband
start the timer to initiate tap commands, whilst the sequence resets when the measured voltage is
once again back inside the inner deadband. One half of the outer deadband is denoted ΔU. The
setting of ΔU, setting Udeadband should be set to a value near to the power transformer’s tap
changer voltage step (typically 75–125% of the tap changer step).

Transformer protection RET650 387


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Security Range

*) *) *)
Raise Cmd DU DU Lower Cmd
DUin DUin

0 Ublock Umin U1 Uset U2 Umax Voltage Magnitude

*) Action in accordance with setting

IEC06000489_2_en.vsd
IEC06000489 V2 EN-US

Figure 216: Control actions on a voltage scale


During normal operating conditions the busbar voltage UB, stays within the outer deadband (interval
between U1 and U2 in figure 216). In that case no actions will be taken by the TR1ATCC. However, if
UB becomes smaller than U1, or greater than U2, an appropriate lower or raise timer will start. The
timer will run as long as the measured voltage stays outside the inner deadband. If this condition
persists longer than the preset time delay, TR1ATCC will initiate the appropriate ULOWER or
URAISE command to be sent from YLTC function block. If necessary, the procedure will be repeated
until the magnitude of the busbar voltage again falls within the inner deadband. One half of the inner
deadband is denoted ΔUin. The inner deadband ΔUin, setting UDeadbandInner should be set to a
value smaller than ΔU. It is recommended to set the inner deadband to 25-70% of the ΔU value. The
higher value in this range is recommended for single control applications and lower value in this
range for parallel control applications.

This way of working is used by TR1ATCC while the busbar voltage is within the security range
defined by settings Umin and Umax

A situation where UB falls outside this range will be regarded as an abnormal situation.

Instead of controlling the voltage at the LV busbar in the same substation as the transformer itself, it
is possible to control the voltage at a load point out in the network, downstream from the transformer.
The Line Voltage Drop Compensation (LDC) can be selected by a setting parameter, and it works
such that the voltage drop from the transformer location to the load point is calculated based on the
measured load current and the known line impedance.

In order to prevent unnecessary load tap changer operations caused by temporary voltage
fluctuations and to coordinate load tap changer operations in radial networks, a time delay is used for
the tapping command to the load tap changer. The time delay can be either definite time or inverse
time and two time settings are used, the first (t1) for the initial delay of a tap command, and the
second (t2) for consecutive tap commands.

388 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Logic diagrams SEMOD158887-166 v2

AUTO

UL a
a<b
< &
U1 INNER DB b &

a
a>b
>
U2 INNER DB b &

a
a<b
>1 URAISE
<
U1 DB b

a
a>b
>1
> >1 ULOWER
U2 DB b

UB a
a>b
>
U MAX b &

FSD &

en06000509.vsd
IEC06000509 V1 EN-US

Figure 217: Simplified logic for automatic control in single mode operation

11.4.5 Tap changer control and supervision, 6 binary inputs TCMYLTC SEMOD171455-1 v6

SEMOD171466-5 v7
The Tap changer control and supervision, 6 binary inputs TCMYLTC gives the tap commands to the
tap changer, and supervises that commands are carried through correctly. It has built-in extensive
possibilities for tap changer position measurement, as well as supervisory and monitoring features.
This is used in the voltage control and can also give information about tap position to the transformer
differential protection.

11.4.5.1 Operation principle


Reading of tap changer position SEMOD159170-10 v4
The tap changer position can be received to the tap changer control and supervision, 6 binary inputs
TCMYLTC function block in the following ways:

1. Via binary input signals, one per tap position (max. 6 or 32 positions).
2. Via coded binary (Binary), binary coded decimal (BCD) signals, or Gray coded binary signals.
3. Via a mA input signal.

Via binary input signals, one per tap position SEMOD159170-21 v7


In this option, each tap position has a separate contact that is hard wired to a binary input in the IED.
Via the Signal Matrix tool in PCM600, the contacts on the binary input card are then directly
connected to the

• inputs B1 – B6 on TCMYLTC function

Transformer protection RET650 389


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Via coded binary (Binary), binary coded decimal (BCD) signals or Gray coded binary
signals SEMOD159170-24 v5
The Tap changer control and supervision, TCMYLTC decodes binary data from up to six binary
inputs to an integer value. The input pattern may be decoded either as BIN, BCD or GRAY format
depending on the setting of the parameter CodeType.

It is also possible to use even parity check of the input binary signal. Whether the parity check shall
be used or not is set with the setting parameter UseParity.

The input BIERR on TCMYLTC can be used as supervisory input for indication of any external error
( Binary Input Module) in the system for reading of tap changer position. Likewise, the input OUTERR
can be used as a supervisory of the Binary Input Module.

The truth table (see table 273) shows the conversion for Binary, Binary Coded Decimal, and Gray
coded signals.

Table 273: Binary, BCD and Gray conversion

IEC06000522 V1 EN-US

390 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

The Gray code conversion above is not complete and therefore the conversion from decimal
numbers to Gray code is given below.

Table 274: Gray code conversion

IEC06000523 V1 EN-US

Via a mA input signal SEMOD159170-35 v5


Any of the six inputs on the mA card (MIM) can be used for the purpose of tap changer position
reading connected to the Tap changer control and supervision, 6 binary inputs TCMYLTC.

The measurement of the tap changer position via MIM module is based on the principle that the
specified mA input signal range (usually 4-20 mA) is divided into N intervals corresponding to the
number of positions available on the tap changer. All mA values within one interval are then
associated with one tap changer position value.

Transformer protection RET650 391


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

The number of available tap changer positions N is defined by the setting parameters LowVoltTap
and HighVoltTap, which define the tap position for lowest voltage and highest voltage respectively.

Reporting of new tap changer position GUID-BA1F88B1-1E1A-4771-9419-65DE27F3EB68 v1


The new tap changer position will be reported from YLTC function towards ATCC function, TxWPDIF
function as well as towards the SCADA system only when its value is stable for at least a period of
time defined by setting tStable. During timing of this tStable timer the last know tap position value will
be still reported as shown in Figure 218. This is necessary in order to prevent undefined or wrong
position being reported during movement/operation of the OLTC mechanism.

OLTC position indication


on the IED inputs

Undefined
N
(in-between
two positions)
N-1

Time
Reported OLTC position
from YLTC function

N
tStable
N-1

Time

1.0 s
NEWPOS
binary signal

GUID-694A24F3-9075-49E0-91FE-69071FB4AAD3 V1 EN-US

Figure 218: Example of YLTC reporting during a change from position N to position N-1
The set value for tStable shall be adjusted for every particular installation on-site because it depends
on transient behavior of the used OLTC mechanism and/or used mA/BCD/Gray-code transducer.
Give special observation for the mid-tap position because typically tapping from/to this position can
take a longer time than for any other tap.

Tap changer extreme positions SEMOD159053-339 v4


This feature supervises the extreme positions of the tap changer according to the settings
LowVoltTap and HighVoltTap. When the tap changer reaches its lowest/highest position, the
corresponding ULOWER/URAISE command is prevented in both automatic and manual mode.

Blocking of tap changer function GUID-D64914BC-C8E7-4086-9E53-0D5C36116C4C v1


The tap changer function can be blocked via the binary input BLOCK on TCMYLTC or TCLYLTC
function block. The outputs URAISE, ULOWER, POSERRAL, CMDERRAL, TCERRAL, POSOUT,
CONVERR, NEWPOS, HIDIFPOS and INVALPOS will be blocked when the binary BLOCK input is
activated.

392 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.4.6 Function block SEMOD172939-1 v2

SEMOD173000-4 v4

TR1ATCC
I3P1* ATCCOUT
I3P2* MAN
U3P2* AUTO
BLOCK IBLK
MANCTRL PGTFWD
AUTOCTRL PLTREV
PSTO QGTFWD
RAISEV QLTREV
LOWERV REVACBLK
EAUTOBLK UHIGH
DEBLKAUT ULOW
LVA1 UBLK
LVA2 HOURHUNT
LVA3 DAYHUNT
LVA4 HUNTING
LVARESET TIMERON
RSTERR TOTBLK
ATCCIN AUTOBLK
UGTUPPDB
ULTLOWDB

IEC07000041_2_en.vsd
IEC07000041 V2 EN-US

Figure 219: TR1ATCC function block


SEMOD173008-4 v4

TCMYLTC
YLTCIN* URAISE
BLOCK ULOWER
TCINPROG HIPOSAL
INERR LOPOSAL
RESETERR POSERRAL
OUTERR CMDERRAL
RS_CLCNT TCERRAL
RS_OPCNT POSOUT
PARITY CONVERR
BIERR NEWPOS
B1 HIDIFPOS
B2 INVALPOS
B3 TCPOS
B4 YLTCOUT
B5
B6
MA

IEC07000038 V5 EN-US

Figure 220: TCMYLTC function block


SEMOD173145-4 v3

VCTRRCV
BLOCK VCTR_REC
COMVALID
DATVALID

IEC07000045-2-en.vsd
IEC07000045 V2 EN-US

Figure 221: VCTRRCV function block

Transformer protection RET650 393


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.4.7 Signals
PID-6562-INPUTSIGNALS v3

Table 275: TR1ATCC Input signals

Name Type Default Description


I3P1 GROUP - Input group for current on HV side
SIGNAL
I3P2 GROUP - Input group for current on LV side
SIGNAL
U3P2 GROUP - Input group for voltage on LV side
SIGNAL
BLOCK BOOLEAN 0 Block of function
MANCTRL BOOLEAN 0 Binary "MAN" command
AUTOCTRL BOOLEAN 0 Binary "AUTO" command
PSTO INTEGER 0 Operator place selection
RAISEV BOOLEAN 0 Binary "UP" command
LOWERV BOOLEAN 0 Binary "DOWN" command
EAUTOBLK BOOLEAN 0 Block the voltage control in automatic control mode
DEBLKAUT BOOLEAN 0 Binary "Deblock Auto" command
LVA1 BOOLEAN 0 Activation of load voltage adjust. factor 1
LVA2 BOOLEAN 0 Activation of load voltage adjust. factor 2
LVA3 BOOLEAN 0 Activation of load voltage adjust. factor 3
LVA4 BOOLEAN 0 Activation of load voltage adjust. factor 4
LVARESET BOOLEAN 0 Reset LVA adjustment to 0
RSTERR BOOLEAN 0 Resets the automatic control commands raise and lower
ATCCIN GROUP - Group connection from YLTCOUT
SIGNAL

PID-6562-OUTPUTSIGNALS v3

Table 276: TR1ATCC Output signals

Name Type Description


ATCCOUT GROUP SIGNAL Group connection to horizontal communication and YLTCIN
MAN BOOLEAN The control is in manual mode
AUTO BOOLEAN Automatic control mode is active
IBLK BOOLEAN One phase current is above the settable limit
PGTFWD BOOLEAN Active power above the settable limit powerActiveForw
PLTREV BOOLEAN Active power below the settable limit powerActiveRev
QGTFWD BOOLEAN Reactive power above the settable limit powerReactiveForw
QLTREV BOOLEAN Reactive power below the settable limit powerReactiveRev
REVACBLK BOOLEAN Block caused by reversed action
UHIGH BOOLEAN Busbar voltage above the settable limit voltBusbMaxLimit
ULOW BOOLEAN Busbar voltage below the settable limit voltBusbMinLimit
UBLK BOOLEAN Busbar voltage below the settable limit voltBusbBlockLimit
HOURHUNT BOOLEAN Alarm for too many tap changer operations during the last hour
DAYHUNT BOOLEAN Alarm for too many tap changer operations during the last 24
hours
HUNTING BOOLEAN Alarm for too many contradictory tap changer operations within the
time sliding window
TIMERON BOOLEAN Raise or lower command to the tap activated
TOTBLK BOOLEAN Block of auto and manual commands
Table continues on next page

394 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Type Description


AUTOBLK BOOLEAN Block of auto commands
UGTUPPDB BOOLEAN Voltage greater than deadband-high, ULOWER command to come
ULTLOWDB BOOLEAN Voltage lower than deadband-low, URAISE command to come

PID-8243-INPUTSIGNALS v1

Table 277: TCMYLTC Input signals

Name Type Default Description


YLTCIN GROUP - Group connection from ATCCOUT
SIGNAL
BLOCK BOOLEAN 0 Block of function
TCINPROG BOOLEAN 0 Indication that tap is moving
INERR BOOLEAN 0 Supervision signal of the input board
RESETERR BOOLEAN 0 Reset of command and tap error
OUTERR BOOLEAN 0 Supervision off the digital output board
RS_CLCNT BOOLEAN 0 Reset of the contact life counter
RS_OPCNT BOOLEAN 0 Resets the operation counter
PARITY BOOLEAN 0 Parity bit from tap changer for the tap position
BIERR BOOLEAN 0 Error bit from tap changer for the tap position
B1 BOOLEAN 0 Bit 1 from tap changer for the tap position
B2 BOOLEAN 0 Bit 2 from tap changer for the tap position
B3 BOOLEAN 0 Bit 3 from tap changer for the tap position
B4 BOOLEAN 0 Bit 4 from tap changer for the tap position
B5 BOOLEAN 0 Bit 5 from tap changer for the tap position
B6 BOOLEAN 0 Bit 6 from tap changer for the tap position
MA REAL 0 mA from tap changer for the tap position

PID-8243-OUTPUTSIGNALS v1

Table 278: TCMYLTC Output signals

Name Type Description


URAISE BOOLEAN Raise voltage command to tap changer
ULOWER BOOLEAN Lower voltage command to tap changer
HIPOSAL BOOLEAN Alarm for tap in highest volt position
LOPOSAL BOOLEAN Alarm for tap in lowest volt position
POSERRAL BOOLEAN Alarm that indicates a problem with the position indication
CMDERRAL BOOLEAN Alarm for a command without an expected position change
TCERRAL BOOLEAN Alarm for none or illegal tap position change
POSOUT BOOLEAN Tap position outside min and max position
CONVERR BOOLEAN General tap position conversion error
NEWPOS BOOLEAN A new tap position is reported, 1 sec pulse
HIDIFPOS BOOLEAN Tap position has changed more than one position
INVALPOS BOOLEAN Last position change was an invalid change
TCPOS INTEGER Integer value corresponding to actual tap position
YLTCOUT GROUP SIGNAL Group connection to ATCCIN

PID-923-INPUTSIGNALS v6

Table 279: VCTRRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function

Transformer protection RET650 395


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

PID-923-OUTPUTSIGNALS v6

Table 280: VCTRRCV Output signals

Name Type Description


VCTR_REC GROUP SIGNAL Received data from horizontal communication
COMVALID BOOLEAN Communication is valid
DATVALID BOOLEAN Data valid

11.4.8 Settings
PID-6562-SETTINGS v3

Table 281: TR1ATCC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
MeasMode L1 - - PosSeq Selection of measured voltage and
L2 current
L3
L1L2
L2L3
L3L1
PosSeq
TotalBlock Off - - Off Total block of the voltage control function
On
AutoBlock Off - - Off Block of the automatic mode in voltage
On control function
FSDMode Off - - Off Fast step down function activation mode
Auto
AutoMan
tFSD 1.0 - 100.0 s 0.1 15.0 Time delay for lower command when fast
step down mode is activated
USet 85.0 - 120.0 %UB 0.1 100.0 Voltage control set voltage, % of rated
voltage
UDeadband 0.2 - 9.0 %UB 0.1 1.2 Outer voltage deadband, % of rated
voltage
UDeadbandInner 0.1 - 9.0 %UB 0.1 0.9 Inner voltage deadband, % of rated
voltage
Umax 80 - 180 %UB 1 105 Upper lim of busbar voltage, % of rated
voltage
Umin 70 - 120 %UB 1 80 Lower lim of busbar voltage, % of rated
voltage
Ublock 50 - 120 %UB 1 80 Undervoltage block level, % of rated
voltage
t1Use Constant - - Constant Activation of long inverse time delay
Inverse
t1 3 - 1000 s 1 60 Time delay (long) for automatic control
commands
t2Use Constant - - Constant Activation of short inverse time delay
Inverse
t2 1 - 1000 s 1 15 Time delay (short) for automatic control
commands
tMin 3 - 120 s 1 5 Minimum operating time in inverse mode
OperationLDC Off - - Off Operation line voltage drop compensation
On
OperCapaLDC Off - - Off LDC compensation for capacitive load
On
Table continues on next page

396 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Values (Range) Unit Step Default Description


Rline 0.00 - 150.00 ohm 0.01 0.0 Line resistance, primary values, in ohm
Xline -150.00 - 150.00 ohm 0.01 0.0 Line reactance, primary values, in ohm
LVAConst1 -20.0 - 20.0 %UB 0.1 0.0 Constant 1 for LVA, % of regulated
voltage
LVAConst2 -20.0 - 20.0 %UB 0.1 0.0 Constant 2 for LVA, % of regulated
voltage
LVAConst3 -20.0 - 20.0 %UB 0.1 0.0 Constant 3 for LVA, % of regulated
voltage
LVAConst4 -20.0 - 20.0 %UB 0.1 0.0 Constant 4 for LVA, % of regulated
voltage
VRAuto -20.0 - 20.0 %UB 0.1 0.0 Load voltage auto correction, % of rated
voltage
OperationRA Off - - Off Enable block from reverse action
On supervision
tRevAct 30 - 6000 s 1 60 Duration time for the reverse action block
signal
RevActLim 0 - 100 %IB1 1 95 Current limit for reverse action block in %
of I1Base
Iblock 5 - 250 %IB1 1 150 Overcurrent block level, % of rated
current
HourHuntDetect 0 - 30 Op/H 1 30 Level for number of counted raise/lower
within one hour
DayHuntDetect 0 - 100 Op/D 1 100 Level for number of counted raise/lower
within 24 hour
tWindowHunt 1 - 120 Min 1 60 Time window for hunting alarm, minutes
NoOpWindow 3 - 30 Op/W 1 30 Hunting detection alarm, max operations/
window
P> -9999.99 - 9999.99 MW 0.01 1000 Alarm level of active power in forward
direction
P< -9999.99 - 9999.99 MW 0.01 -1000 Alarm level of active power in reverse
direction
Q> -9999.99 - 9999.99 MVAr 0.01 1000 Alarm level of reactive power in forward
direction
Q< -9999.99 - 9999.99 MVAr 0.01 -1000 Alarm level of reactive power in reverse
direction
tPower 1 - 6000 s 1 10 Time delay for alarms from power
supervision

Table 282: TR1ATCC Group settings (advanced)

Name Values (Range) Unit Step Default Description


UseCmdUSet Off - - Off Enable command input for voltage control
On set voltage

Table 283: TR1ATCC Non group settings (basic)

Name Values (Range) Unit Step Default Description


Xr2 0.1 - 200.0 Ohm 0.1 0.5 Transformer reactance in primary ohms
on ATCC side
CmdErrBk Alarm - - Auto Block Alarm, auto block or auto&man block for
Auto Block command error
Auto&Man Block
OCBk Alarm - - Auto&Man Block Alarm, auto block or auto&man block for
Auto Block overcurrent
Auto&Man Block
Table continues on next page

Transformer protection RET650 397


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

Name Values (Range) Unit Step Default Description


OVPartBk Alarm - - Auto&Man Block Alarm or auto&man partial block for
Auto&Man Block overvoltage
RevActPartBk Alarm - - Alarm Alarm or auto partial block for reverse
Auto Block action
TapChgBk Alarm - - Auto Block Alarm, auto block or auto&man block for
Auto Block tap changer error
Auto&Man Block
TapPosBk Alarm - - Auto Block Alarm, auto or auto&man block for pos
Auto Block sup
Auto&Man Block
UVBk Alarm - - Auto Block Alarm, auto block or auto&man block for
Auto Block undervoltage
Auto&Man Block
UVPartBk Alarm - - Alarm Alarm or auto&man partial block for
Auto&Man Block undervoltage
GlobalBaseSel1 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, winding 1
GlobalBaseSel2 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, winding 2

PID-6506-SETTINGS v5

Table 284: TCMYLTC Non group settings (basic)

Name Values (Range) Unit Step Default Description


LowVoltTap 1 - 63 - 1 1 Tap position for lowest voltage
HighVoltTap 1 - 63 - 1 33 Tap position for highest voltage
mALow 0.000 - 25.000 mA 0.001 4.000 mA for lowest voltage tap position
mAHigh 0.000 - 25.000 mA 0.001 20.000 mA for highest voltage tap position
CodeType BIN - - BIN Type of code conversion
BCD
Gray
SINGLE
mA
UseParity Off - - Off Enable parity check
On
tStable 1 - 60 s 1 2 Time after position change before the
value is accepted
CLFactor 1.0 - 3.0 - 0.1 2.0 Adjustable factor for contact life function
InitCLCounter 0 - 9999999 - 1 250000 CL counter start value
EnabTapCmd Off - - On Enable commands to tap changer
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups

Table 285: TCMYLTC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
tTCTimeout 1 - 120 s 1 5 Tap changer constant time-out
tPulseDur 0.5 - 10.0 s 0.1 1.5 Raise/lower command output pulse
duration

398 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.4.9 Monitored data


PID-6562-MONITOREDDATA v3

Table 286: TR1ATCC Monitored data

Name Type Values (Range) Unit Description


BUSVOLT REAL - kV The average of the measured busbar
voltage (service value)
VOLTDEV REAL - % Voltage deviation compared to dead band
(%)
TRLDCURR REAL - A Amplitude of own load current
USETOUT REAL - kV Voltage setpoint used in single mode
(service value)
ULOAD REAL - kV Calculated compensated voltage (service
value)
P REAL - MW Calculated active power (service value)
Q REAL - MVAr Calculated reactive power (service value)
IPRIM REAL - A Max of 3 phase currents (service value)

PID-6506-MONITOREDDATA v5

Table 287: TCMYLTC Monitored data

Name Type Values (Range) Unit Description


TCPOS INTEGER - - Integer value corresponding to actual tap
position

PID-3669-MONITOREDDATA v2

Table 288: TCMYLTC Monitored data

Name Type Values (Range) Unit Description


CNT_VAL INTEGER - - Number of operations on tap changer
CLCNT_VAL REAL - - Remaining number of operations at rated
load
TCPOS INTEGER - - Integer value corresponding to actual tap
position

11.4.10 Operation principle M6500-430 v12

• Automatic voltage control for tap changer


• TR1ATCC for single control
• Tap changer control and supervision
• TCMYLTC, 6 binary inputs

TR1ATCC are designed to automatically maintain the voltage at the LV-side side of a power
transformer within given limits around a set target voltage. A raise or lower command is generated
whenever the measured voltage, for a given period of time, deviates from the set target value by
more than the preset deadband value that is, degree of insensitivity. A time-delay (inverse or definite
time) is set to avoid unnecessary operation during shorter voltage deviations from the target value,
and in order to coordinate with other automatic voltage controllers in the system.

TCMYLTC is an interface between TR1ATCC and the transformer load tap changer. More specifically
this means that it receives information from TR1ATCC and based on this it gives command-pulses to
a power transformer motor driven on-load tap changer and also receives information from the on-
load tap changer regarding tap position, progress of given commands, and so on.

TCMYLTC also serve the purpose of giving information about tap position to the transformer
differential protection T2WPDIF and T3WPDIF.

Transformer protection RET650 399


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.4.11 Technical data


SEMOD175215-2 v16

Table 289: TR1ATCC/TCMYLTC technical data

Function Range or value Accuracy


Transformer reactance (0.1–200.0) Ω, primary -
Time delay for lower command when fast (1.0–100.0) s -
step down mode is activated
Voltage control set voltage (85.0–120.0)% of UBase ±0.25% of Ur
Outer voltage deadband (0.2–9.0)% of UBase -
Inner voltage deadband (0.1–9.0)% of UBase -
Upper limit of busbar voltage (80–180)% of UBase ±0.5% of Ur
Lower limit of busbar voltage (70–120)% of UBase ±0.5% of Ur
Undervoltage block level (50–120)% of UBase ±0.5% of Ur
Time delay (long) for automatic control (3–1000) s ±0.2% or ±600 ms
commands whichever is greater
Time delay (short) for automatic control (1–1000) s ±0.2% or ±600 ms
commands whichever is greater
Minimum operating time in inverse mode (3–120) s ±0.2% or ±600 ms
whichever is greater
Line resistance (0.00–150.00) Ω, primary -
Line reactance (-150.00–150.00) Ω, primary -
Load voltage adjustment constants (-20.0–20.0)% of UBase -
Load voltage auto correction (-20.0–20.0)% of UBase -
Duration time for the reverse action block (30–6000) s ±0.2% or ±600 ms
signal whichever is greater
Current limit for reverse action block (0–100)% of I1Base -
Overcurrent block level (5–250)% of I1Base ±1.0% of Ir at I≤Ir
±1.0% of I at I>Ir
Level for number of counted raise/lower (0–30) operations/hour -
within one hour
Level for number of counted raise/lower (0–100) operations/day -
within 24 hours
Time window for hunting alarm (1–120) minutes -
Hunting detection alarm, max. operations/ (3–30) operations/window -
window
Alarm level of active power in forward and (-9999.99–9999.99) MW ±1.0% of Sr
reverse direction at (10-200)% of Sr and
(85-120)% of UBase
Alarm level of reactive power in forward and (-9999.99–9999.99) MVAr ±1.0% of Sr
reverse direction at (10-200)% of Sr and
(85-120)% of UBase
Time delay for alarms from power supervision (1–6000) s ±0.2% or ±600 ms
whichever is greater
Tap position for lowest and highest voltage (1–63) -
mA for lowest and highest voltage tap (0.000–25.000) mA -
position
Type of code conversion BIN, BCD, GRAY, SINGLE, mA -
Table continues on next page

400 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Function Range or value Accuracy


Time after position change before the value is (1–60) s ±0.2% or ±200 ms
accepted whichever is greater
Tap changer constant time-out (1–120) s ±0.2% or ±200 ms
whichever is greater
Raise/lower command output pulse duration (0.5–10.0) s ±0.2% or ±200 ms
whichever is greater

11.5 Logic rotating switch for function selection and LHMI


presentation SLGAPC SEMOD114936-1 v6

11.5.1 Identification
SEMOD167845-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic rotating switch for function SLGAPC - -
selection and LHMI presentation

11.5.2 Functionality SEMOD114908-4 v11

The logic rotating switch for function selection and LHMI presentation (SLGAPC) (or the selector
switch function block) is used to get an enhanced selector switch functionality compared to the one
provided by a hardware selector switch. Hardware selector switches are used extensively by utilities,
in order to have different functions operating on pre-set values. Hardware switches are however
sources for maintenance issues, lower system reliability and an extended purchase portfolio. The
selector switch function eliminates all these problems.

Transformer protection RET650 401


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.5.3 Function block SEMOD114954-4 v6

SLGAPC
BLOCK ^P01
PSTO ^P02
UP ^P03
DOWN ^P04
^P05
^P06
^P07
^P08
^P09
^P10
^P11
^P12
^P13
^P14
^P15
^P16
^P17
^P18
^P19
^P20
^P21
^P22
^P23
^P24
^P25
^P26
^P27
^P28
^P29
^P30
^P31
^P32
SWPOSN
IEC14000005 V2 EN-US

Figure 222: SLGAPC function block

11.5.4 Signals
PID-6641-INPUTSIGNALS v3

Table 290: SLGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
UP BOOLEAN 0 Binary "UP" command
DOWN BOOLEAN 0 Binary "DOWN" command

PID-6641-OUTPUTSIGNALS v3

Table 291: SLGAPC Output signals

Name Type Description


P01 BOOLEAN Selector switch position 1
P02 BOOLEAN Selector switch position 2
P03 BOOLEAN Selector switch position 3
P04 BOOLEAN Selector switch position 4
P05 BOOLEAN Selector switch position 5
P06 BOOLEAN Selector switch position 6
P07 BOOLEAN Selector switch position 7
P08 BOOLEAN Selector switch position 8
P09 BOOLEAN Selector switch position 9
P10 BOOLEAN Selector switch position 10
Table continues on next page

402 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Name Type Description


P11 BOOLEAN Selector switch position 11
P12 BOOLEAN Selector switch position 12
P13 BOOLEAN Selector switch position 13
P14 BOOLEAN Selector switch position 14
P15 BOOLEAN Selector switch position 15
P16 BOOLEAN Selector switch position 16
P17 BOOLEAN Selector switch position 17
P18 BOOLEAN Selector switch position 18
P19 BOOLEAN Selector switch position 19
P20 BOOLEAN Selector switch position 20
P21 BOOLEAN Selector switch position 21
P22 BOOLEAN Selector switch position 22
P23 BOOLEAN Selector switch position 23
P24 BOOLEAN Selector switch position 24
P25 BOOLEAN Selector switch position 25
P26 BOOLEAN Selector switch position 26
P27 BOOLEAN Selector switch position 27
P28 BOOLEAN Selector switch position 28
P29 BOOLEAN Selector switch position 29
P30 BOOLEAN Selector switch position 30
P31 BOOLEAN Selector switch position 31
P32 BOOLEAN Selector switch position 32
SWPOSN INTEGER Switch position (integer)

11.5.5 Settings
PID-6641-SETTINGS v3

Table 292: SLGAPC Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
NrPos 2 - 32 - 1 32 Number of positions in the switch
OutType Pulsed - - Steady Output type, steady or pulse
Steady
tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]
tDelay 0.000 - 60000.000 s 0.010 0.000 Time delay on the output, in [s]
StopAtExtremes Disabled - - Disabled Stop when min or max position is reached
Enabled

11.5.6 Monitored data


PID-6641-MONITOREDDATA v3

Table 293: SLGAPC Monitored data

Name Type Values (Range) Unit Description


SWPOSN INTEGER - - Switch position (integer)

Transformer protection RET650 403


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.5.7 Operation principle


SEMOD114931-4 v8
The logic rotating switch for function selection and LHMI presentation (SLGAPC) function has two
operating inputs – UP and DOWN. When a signal is received on the UP input, the function will
activate the output next to the present activated output, in ascending order (for example if the present
activated output is P03 and one activates the UP input then the output P04 will be activated). When a
signal is received on the DOWN input, the function will activate the output next to the present
activated output, in descending order (for example if the present activated output is P03 and one
activates the DOWN input then the output P02 will be activated). Depending on the output settings
the output signals can be steady or pulsed. In case of steady signals, the output will be active till the
time it receives next operation of UP/DOWN inputs. Also, depending on the settings one can have a
time delay between activation of the UP or DOWN input signals and the output activation.

Besides the inputs visible in the application configuration in the Application Configuration Tool, there
are other possibilities that will allow an user to set the desired position directly (without activating the
intermediate positions), either locally or remotely, using a “select before execute” dialog. One can
block the function operation, by activating the BLOCK input. In this case, the present position will be
kept and further operation will be blocked. The operator place (local or remote) is specified through
the PSTO input. If any operation is allowed the signal INTONE from the Fixed signal function block
can be connected. SLGAPC function block has also an integer value output, that generates the
actual position number. The positions and the block names are fully settable by the user. These
names will appear in the menu, so the user can see the position names instead of a number.

11.5.7.1 Graphical display SEMOD114931-35 v4

There are two possibilities for SLGAPC

• if it is used just for the monitoring, the switches will be listed with their actual position names, as
defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions, but only the first
three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it when building the
Graphical Display Editor, under the "Caption". If used for the control, the following sequence of
commands will ensure:

404 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

From the graphical display:

Control
Control Single Line Diagram
Measurements Commands
Events
Disturbance records
Settings
Diagnostics
Test
Change to the "Switches" page Reset
of the SLD by left-right arrows. Authorization
Select switch by up-down Language
arrows

../Control/SLD/Switch
O I ../Control/SLD/Switch
SMBRREC control SMBRREC control
WFM Select switch. Press the
WFM
I or O key. A dialog box
Pilot setup appears.
Pilot setup
OFF OFF
Damage control
P: Disc N: Disc Fe
DAL
The pos will not be modified
(outputs will not be activated) until OK Cancel
you press the Enter button for O.K.

../Control/SLD/Switch

SMBRREC control
WFM

Pilot setup
OFF

Damage control
DFW

IEC06000421 V4 EN-US

Figure 223: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

11.6 Selector mini switch VSGAPC SEMOD158754-1 v3

11.6.1 Identification
SEMOD167850-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Selector mini switch VSGAPC - 43

11.6.2 Functionality SEMOD158756-5 v11

The Selector mini switch (VSGAPC) function block is a multipurpose function used for a variety of
applications, as a general purpose switch.

Transformer protection RET650 405


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

VSGAPC can be controlled from a symbol on the single line diagram (SLD) on the local HMI or from
binary inputs.

11.6.3 Function block SEMOD158768-4 v3

VSGAPC
BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1
IPOS2 POS2
CMDPOS12
CMDPOS21
IEC14000066 V2 EN-US

Figure 224: VSGAPC function block

11.6.4 Signals
PID-7478-INPUTSIGNALS v1

Table 294: VSGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input

PID-7478-OUTPUTSIGNALS v1

Table 295: VSGAPC Output signals

Name Type Description


BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1

11.6.5 Settings
PID-7478-SETTINGS v1

Table 296: VSGAPC Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
CtlModel Dir Norm - - Dir Norm Specifies the type for control model
SBO Enh according to IEC 61850
Mode Steady - - Pulsed Operation mode
Pulsed
tSelect 0.000 - 600.000 s 0.001 30.000 Max time between select and execute
signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght

406 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.6.6 Operation principle SEMOD158762-4 v7

Selector mini switch (VSGAPC) function can be used for double purpose, in the same way as switch
controller (SCSWI) functions are used:

• for indication on the single line diagram (SLD). Position is received through the IPOS1 and
IPOS2 inputs and distributed in the configuration through the POS1 and POS2 outputs, or to
IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from the local
HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from the local
HMI when the SLD is displayed and the object is chosen.

It is important for indication in the SLD that a symbol is associated with a controllable
object, otherwise the symbol won't be displayed on the screen. A symbol is created and
configured in GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of operators place,
operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE connection from Fixed
signal function block (FXDSIGN) will allow operation from local HMI.

As it can be seen, both indications and commands are done in double-bit representation, where a
combination of signals on both inputs/outputs generate the desired result.

The following table shows the relationship between IPOS1/IPOS2 inputs and the name of the string
that is shown on the SLD. The value of the strings are set in PST.

IPOS1 IPOS2 Name of displayed string Default string value


0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11

11.7 Generic communication function for double point


indication DPGAPC SEMOD55384-1 v5

11.7.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generic communication function for DPGAPC - -
double point indication

11.7.2 Functionality SEMOD55850-5 v8

Generic communication function for double point indication (DPGAPC) function block is used to send
double point position indications to other systems, equipment or functions in the substation through
IEC 61850-8-1 or other communication protocols. It is especially intended to be used in the
interlocking station-wide logics.

Transformer protection RET650 407


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.7.3 Function block SEMOD54710-4 v5

DPGAPC
OPEN POSITION
CLOSE
VALID
IEC13000081 V2 EN-US

Figure 225: DPGAPC function block

11.7.4 Signals SEMOD55883-1 v2

PID-4139-INPUTSIGNALS v12

Table 297: DPGAPC Input signals

Name Type Default Description


OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication

PID-4139-OUTPUTSIGNALS v12

Table 298: DPGAPC Output signals

Name Type Description


POSITION INTEGER double point indication

11.7.5 Settings ABBD8E283863 v4

The function does not have any parameters available in the local HMI or PCM600.

11.7.6 Operation principle SEMOD55861-5 v8

When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the systems,
equipment or functions that requests and thus subscribes on these signals. To be able to get the
signals into other systems, equipment or functions, one must use other tools, described in the
Engineering manual, and define which function block in which systems, equipment or functions
should receive this information.

More specifically, DPGAPC function reports a combined double point position indication output
POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN and CLOSE,
together with the logical input signal VALID.

When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the two-
bit integer value of the output POSITION. The timestamp of the output POSITION will have the latest
updated timestamp of the inputs OPEN and CLOSE.

When the input signal VALID is inactive, DPGAPC function forces the position to intermediated state.

When the value of the input signal VALID changes, the timestamp of the output POSITION will be
updated as the time when DPGAPC function detects the change.

Refer to Table 299 for the description of the input-output relationship in terms of the value and the
quality attributes.

408 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

Table 299: Description of the input-output relationship

POSITION
VALID OPEN CLOSE
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State

11.8 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3

11.8.1 Identification
SEMOD176456-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single point generic control 8 signals SPC8GAPC - -

11.8.2 Functionality SEMOD176462-4 v11

The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single point
commands that can be used for direct commands for example reset of LEDs or putting IED in
"ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands is supposed to be
achieved by other means, such as binary inputs and SPGAPC function blocks. The commands can
be pulsed or steady with a settable pulse time.

11.8.3 Function block SEMOD176479-4 v5

SPC8GAPC
BLOCK ^OUT1
PSTO ^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8

IEC07000143 V4 EN-US

Figure 226: SPC8GAPC function block

11.8.4 Signals
PID-3575-INPUTSIGNALS v8

Table 300: SPC8GAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Blocks the function operation
PSTO INTEGER 1 Operator place selection

Transformer protection RET650 409


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

PID-3575-OUTPUTSIGNALS v8

Table 301: SPC8GAPC Output signals

Name Type Description


OUT1 BOOLEAN Command output 1
OUT2 BOOLEAN Command output 2
OUT3 BOOLEAN Command output 3
OUT4 BOOLEAN Command output 4
OUT5 BOOLEAN Command output 5
OUT6 BOOLEAN Command output 6
OUT7 BOOLEAN Command output 7
OUT8 BOOLEAN Command output 8

11.8.5 Settings
PID-3575-SETTINGS v8

Table 302: SPC8GAPC Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
PulseMode1 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Pulse time output 1
PulseMode2 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Pulse time output 2
PulseMode3 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Pulse time output 3
PulseMode4 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Pulse time output 4
PulseMode5 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Pulse time output 5
PulseMode6 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Pulse time output 6
PulseMode7 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Pulse time output 7
PulseMode8 Pulsed - - Pulsed Setting for pulsed/latched mode for output
Latched 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Pulse time output 8

11.8.6 Operation principle SEMOD176471-4 v7

The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight outputs is
activated based on the command sent from the operator place selected. The settings Latchedx and
tPulsex (where x is the respective output) will determine if the signal will be pulsed (and how long the
pulse is) or latched (steady). BLOCK will block the operation of the function – in case a command is
sent, no output will be activated.

410 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

PSTO is the universal operator place selector for all control functions. Although, PSTO
can be configured to use LOCAL or ALL operator places, only REMOTE operator place is
used in SPC8GAPC function.

11.9 AutomationBits, command function for DNP3.0


AUTOBITS SEMOD158589-1 v3

11.9.1 Identification
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
AutomationBits, command function for
AUTOBITS - -
DNP3

11.9.2 Functionality SEMOD158591-5 v9

The Automation bits function (AUTOBITS) is used to configure the DNP3 protocol command
handling. Each of the 3 AUTOBITS available has 32 individual outputs available, each can be
mapped as a binary output point in DNP3.

11.9.3 Function block SEMOD158603-4 v3

AUTOBITS
BLOCK ^CMDBIT1
PSTO ^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32

IEC09000925-1-en.vsd
IEC09000925 V1 EN-US

Figure 227: AUTOBITS function block

Transformer protection RET650 411


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.9.4 Signals
PID-3776-INPUTSIGNALS v6

Table 303: AUTOBITS Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection

PID-3776-OUTPUTSIGNALS v6

Table 304: AUTOBITS Output signals

Name Type Description


CMDBIT1 BOOLEAN Command out bit 1
CMDBIT2 BOOLEAN Command out bit 2
CMDBIT3 BOOLEAN Command out bit 3
CMDBIT4 BOOLEAN Command out bit 4
CMDBIT5 BOOLEAN Command out bit 5
CMDBIT6 BOOLEAN Command out bit 6
CMDBIT7 BOOLEAN Command out bit 7
CMDBIT8 BOOLEAN Command out bit 8
CMDBIT9 BOOLEAN Command out bit 9
CMDBIT10 BOOLEAN Command out bit 10
CMDBIT11 BOOLEAN Command out bit 11
CMDBIT12 BOOLEAN Command out bit 12
CMDBIT13 BOOLEAN Command out bit 13
CMDBIT14 BOOLEAN Command out bit 14
CMDBIT15 BOOLEAN Command out bit 15
CMDBIT16 BOOLEAN Command out bit 16
CMDBIT17 BOOLEAN Command out bit 17
CMDBIT18 BOOLEAN Command out bit 18
CMDBIT19 BOOLEAN Command out bit 19
CMDBIT20 BOOLEAN Command out bit 20
CMDBIT21 BOOLEAN Command out bit 21
CMDBIT22 BOOLEAN Command out bit 22
CMDBIT23 BOOLEAN Command out bit 23
CMDBIT24 BOOLEAN Command out bit 24
CMDBIT25 BOOLEAN Command out bit 25
CMDBIT26 BOOLEAN Command out bit 26
CMDBIT27 BOOLEAN Command out bit 27
CMDBIT28 BOOLEAN Command out bit 28
CMDBIT29 BOOLEAN Command out bit 29
CMDBIT30 BOOLEAN Command out bit 30
CMDBIT31 BOOLEAN Command out bit 31
CMDBIT32 BOOLEAN Command out bit 32

412 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.9.5 Settings
PID-3776-SETTINGS v6

Table 305: AUTOBITS Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

11.9.6 Operation principle SEMOD158597-4 v5

AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining
parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.

There is a BLOCK input signal, which will disable the operation of the function, in the same way the
setting Operation: On/Off does. That means that, upon activation of the BLOCK input, all 32
CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still receives data
from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the
DNP3 master again, momentarily. For AUTOBITS , the PSTO input determines the operator place.
The command can be written to the block while in “Remote”. If PSTO is in “Local” then no change is
applied to the outputs.

11.10 Single command, 16 inputs SINGLECMD SEMOD119849-1 v3

11.10.1 Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single command, 16 inputs SINGLECMD - -

11.10.2 Functionality M12446-6 v7

The IEDs can receive commands either from a substation automation system or from the local HMI.
The command function block has outputs that can be used, for example, to control high voltage
apparatuses or for other user defined functionality.

Transformer protection RET650 413


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 11 1MRK504170-UEN Rev. J
Control

11.10.3 Function block SEMOD116040-4 v2

SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

IEC05000698-2-en.vsd
IEC05000698 V3 EN-US

Figure 228: SINGLECMD function block

11.10.4 Signals
PID-6189-INPUTSIGNALS v7

Table 306: SINGLECMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block single command function

PID-6189-OUTPUTSIGNALS v7

Table 307: SINGLECMD Output signals

Name Type Description


OUT1 BOOLEAN Single command output 1
OUT2 BOOLEAN Single command output 2
OUT3 BOOLEAN Single command output 3
OUT4 BOOLEAN Single command output 4
OUT5 BOOLEAN Single command output 5
OUT6 BOOLEAN Single command output 6
OUT7 BOOLEAN Single command output 7
OUT8 BOOLEAN Single command output 8
OUT9 BOOLEAN Single command output 9
OUT10 BOOLEAN Single command output 10
OUT11 BOOLEAN Single command output 11
OUT12 BOOLEAN Single command output 12
OUT13 BOOLEAN Single command output 13
OUT14 BOOLEAN Single command output 14
OUT15 BOOLEAN Single command output 15
OUT16 BOOLEAN Single command output 16

414 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 11
Control

11.10.5 Settings
PID-6189-SETTINGS v7

Table 308: SINGLECMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
Steady
Pulsed

11.10.6 Operation principle M12447-3 v4

Single command, 16 inputs (SINGLECMD) function has 16 binary output signals. The outputs can be
individually controlled from a substation automation system or from the local HMI. Each output signal
can be given a name with a maximum of 13 characters in PCM600.

The output signals can be of the types Off, Steady, or Pulse. This configuration setting is done via the
local HMI or PCM600 and is common for the whole function block. The length of the output pulses
are 100 ms. In steady mode, SINGLECMD function has a memory to remember the output values at
power interruption of the IED. Also a BLOCK input is available used to block the updating of the
outputs.

The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via the
configuration logic circuits to the binary outputs of the IED.

Transformer protection RET650 415


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
416
1MRK504170-UEN Rev. J Section 12
Logic

Section 12 Logic
12.1 Tripping logic SMPPTRC IP14576-1 v4

12.1.1 Function revision history GUID-ADA72CE6-B6ED-48B3-A897-A7B42ECDEBB4 v3

Document Product History


revision revision
A 2.2.1 STN (Start neutral) output added. IEC 61850 mapping is made for the added output.
B 2.2.1 -
C 2.2.1 -
D 2.2.4 Added TRINN (Trip neutral) input and TRN (trip neutral) outputs. TRINALL (Trip all
phases) input is changed from TRIN. IEC 61850 mapping is made for the added output.
The block logic is corrected for the lockout functionality.
E 2.2.5 -
H 2.2.6 -
J 2.2.6 Fault current and voltage reporting is added

12.1.2 Identification
SEMOD56226-2 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Tripping logic SMPPTRC 94
1 -> 0
IEC15000314 V1 EN-US

12.1.3 Functionality M12275-3 v16

A function block for protection tripping and general start indication is always provided as a basic
function for each circuit breaker. It provides a settable pulse prolongation time to ensure a trip pulse
of sufficient length, as well as all functionality necessary for correct co-operation with autoreclosing
functions.

The trip function block includes a settable latch function for the trip signal and circuit breaker lockout.

The trip function can collect start and directional signals from different application functions. The
aggregated start and directional signals are mapped to the IEC 61850 logical node data model.

The function also captures and reports the magnitude, angle of the voltage and current of each
phase and neutral at the instant of fault to IEC 61850, LHMI, signal monitoring tool triggered by
TRINx signal activation.

Transformer protection RET650 417


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.1.4 Function block M12638-3 v9

SMPPTRC
I3P TRIP
U3P TRL1
BLOCK TRL2
BLKLKOUT TRL3
TRINALL TRN
TRINL1 TR1P
TRINL2 TR2P
TRINL3 TR3P
TRINN CLLKOUT
PSL1 START
PSL2 STL1
PSL3 STL2
1PTRZ STL3
1PTREF STN
P3PTR FW
SETLKOUT REV
RSTLKOUT FLTIL1MAG
STDIR FLTIL1ANG
RSTFLTUI FLTIL2MAG
FLTIL2ANG
FLTIL3MAG
FLTIL3ANG
FLTINMAG
FLTINANG
FLTUL1MAG
FLTUL1ANG
FLTUL2MAG
FLTUL2ANG
FLTUL3MAG
FLTUL3ANG
FLTUNMAG
FLTUNANG

IEC05000707 V6 EN-US

Figure 229: SMPPTRC function block

12.1.5 Signals
PID-8233-INPUTSIGNALS v1

Table 309: SMPPTRC Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKLKOUT BOOLEAN 0 Blocks circuit breaker lockout output (CLLKOUT)
TRINALL BOOLEAN 0 Trip all phases
TRINL1 BOOLEAN 0 Trip phase L1
TRINL2 BOOLEAN 0 Trip phase L2
TRINL3 BOOLEAN 0 Trip phase L3
TRINN BOOLEAN 0 Trip neutral, trips all phases
PSL1 BOOLEAN 0 Functional input for phase selection in phase L1
PSL2 BOOLEAN 0 Functional input for phase selection in phase L2
PSL3 BOOLEAN 0 Functional input for phase selection in phase L3
1PTRZ BOOLEAN 0 Input for phase selective carrier aided trip
1PTREF BOOLEAN 0 Input for phase selective earth fault trip
P3PTR BOOLEAN 0 Prepare all tripping to be three-phase
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
Table continues on next page

418 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Name Type Default Description


RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout function
STDIR INTEGER 0 General start direction input
RSTFLTUI BOOLEAN 0 Reset the stored fault data

PID-8233-OUTPUTSIGNALS v1

Table 310: SMPPTRC Output signals

Name Type Description


TRIP BOOLEAN General trip signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TRN BOOLEAN Trip signal from neutral
TR1P BOOLEAN Trip single-pole
TR2P BOOLEAN Trip two-pole
TR3P BOOLEAN Trip three-pole
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)
START BOOLEAN General start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STN BOOLEAN Start signal from neutral
FW BOOLEAN General forward signal
REV BOOLEAN General reverse signal
FLTIL1MAG REAL Fundamental DFT magnitude of current of phase L1 of the last
event
FLTIL1ANG REAL Fundamental DFT angle of current of phase L1 of the last event
FLTIL2MAG REAL Fundamental DFT magnitude of current of phase L2 of the last
event
FLTIL2ANG REAL Fundamental DFT angle of current of phase L2 of the last event
FLTIL3MAG REAL Fundamental DFT magnitude of current of phase L3 of the last
event
FLTIL3ANG REAL Fundamental DFT angle of current of phase L3 of the last event
FLTINMAG REAL Magnitude of neutral current of the last event
FLTINANG REAL Angle of neutral current of the last event
FLTUL1MAG REAL Fundamental DFT magnitude of voltage of phase L1 of the last
event
FLTUL1ANG REAL Fundamental DFT angle of voltage of phase L1 of the last event
FLTUL2MAG REAL Fundamental DFT magnitude of voltage of phase L2 of the last
event
FLTUL2ANG REAL Fundamental DFT angle of voltage of phase L2 of the last event
FLTUL3MAG REAL Fundamental DFT magnitude of voltage of phase L3 of the last
event
FLTUL3ANG REAL Fundamental DFT angle of voltage of phase L3 of the last event
FLTUNMAG REAL Magnitude of neutral voltage of the last event
FLTUNANG REAL Angle of neutral voltage of the last event

Transformer protection RET650 419


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.1.6 Settings
PID-8233-SETTINGS v1

Table 311: SMPPTRC Non group settings (basic)

Name Values (Range) Unit Step Default Description


CondBlkMode Common - - Common Conditional blocking mode of function due
Function specific to analog data quality
FltValRepMode Do not report - - Report at trip Selection of trigger for fault record 0-Do
Report at trip not report 1-Report at trip

Table 312: SMPPTRC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
Program 3 phase - - 1ph/3ph Three ph; single or three ph; single, two
1ph/3ph or three ph trip
1ph/2ph/3ph
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secure 3-pole trip when phase selection
failed

Table 313: SMPPTRC Group settings (advanced)

Name Values (Range) Unit Step Default Description


TripLockout Off - - Off Latch TRIP output when SETLKOUT
On input is activated
AutoLock Off - - Off Activate CLLKOUT output when TRIP
On output is activated
tEvolvingFault 0.000 - 60.000 s 0.001 2.000 Secure 3-pole tripping at evolving faults

12.1.7 Operation principle M12255-3 v15

There is a single input (TRINALL) through which all trip output signals from the protection functions
within the IED or from external protection functions via one or more of the IEDs' binary inputs are
routed. It has a three-phase trip output (TRIP) to connect to one or more of the IEDs' binary outputs,
as well as to other functions within the IED requiring this signal.

420 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Simplified logic where setting


Program = 3 phase
BLOCK
BLKLKOUT Final Tripping Circuits
BLOCK
3 phase
BLKLKOUT TRIP TRIP
BLOCK TRIPALL TRIPALL TRL1 TRL1
TRINALL TRINALL TRIPL1 TRL2 TRL2
TRINL1 TRINL1 TRIPL2 TRL3 TRL3
TRINL2 TRINL2 TRIPL3 TRN TRN
TRINL3 TRINL3 TRIPN TR1P
1PTRZ 1PTRZ SETLKOUT TR2P
1PTREF 1PTREF RSTLKOUT TR3P TR3P
CLLKOUT CLLKOUT
TRINN
SETLKOUT
RSTLKOUT

Simplified logic where setting


BLOCK Program = 1ph/3ph
BLKLKOUT Final Tripping Circuits
BLOCK
TRIP
BLKLKOUT TRIP
1ph/3ph TRIPALL TRL1
TRL1
Phase Segregated TRIPL1 TRL2
TRL2
BLOCK TRIPL1
TRINALL TRL3
TRINALL L1TRIP L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 TRN
TRINL1 L2TRIP L2TRIP TRIPL3 TRIPL3 TRN
TRINL2 TR1P
TRINL2 L3TRIP L3TRIP TRIPN TR1P
TRINL3 SETLKOUT TR2P
TRINL3 P3PTR
PSL1 TR3P
PSL1 RSTLKOUT TR3P
PSL2 CLLKOUT
PSL2 CLLKOUT
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
TRINN
SETLKOUT
RSTLKOUT

Simplified logic where setting


BLOCK Program = 1ph/2ph/3ph

BLKLKOUT Final Tripping Circuits


BLOCK
TRIP
BLKLKOUT TRIP
1ph/2ph/3ph TRIPALL TRL1 TRL1
Phase Segregated TRIPL1 TRL2 TRL2
BLOCK TRIPL1
TRINALL L1TRIP TRL3
TRINALL L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 L2TRIP TRN
TRINL1 L2TRIP TRIPL3 TRIPL3 TRN
TRINL2 L3TRIP TR1P
TRINL2 L3TRIP TRIPN TR1P
TRINL3 SETLKOUT TR2P TR2P
TRINL3 P3PTR
PSL1 TR3P
PSL1 RSTLKOUT TR3P
PSL2 CLLKOUT
PSL2 CLLKOUT
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
TRINN
SETLKOUT
RSTLKOUT

IEC10000266 V4 EN-US

Figure 230: Simplified logic diagrams with different program modes


SMPPTRC function has separate inputs (TRINL1, TRINL2, TRINL3) which are used for single-phase
and two-phase tripping from the functions which offer phase segregated trip outputs.

The input TRINN can be activated from functions which provide data for trip in the neutral.

The inputs 1PTRZ and 1PTREF enable single- phase and two-phase tripping for those functions
which do not have their own phase selection capability (that is, which have just a single trip output).
An example of such a protection function is the residual overcurrent protection. The SMPPTRC
function has two inputs for these functions, one for impedance tripping (1PTRZ used for carrier-aided
tripping commands from the scheme communication logic), and one for earth fault tripping (1PTREF
used for tripping from a residual overcurrent protection). External phase selection for these two trip
signals shall be provided via inputs PSL1, PSL2, and PSL3.

Transformer protection RET650 421


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

A timer tWaitForPHS, secures a three-phase trip command for these two trip signals in the absence
of the external phase selection signals.

The SMPPTRC function has three trip outputs TRL1, TRL2, TRL3 (besides the three-phase trip
output TRIP), one per phase, to connect to one or more of the IEDs’ binary outputs, as well as to
other functions within the IED requiring these signals. These three output signals shall be used as
trip signals for individual circuit breaker poles. These signals are important for cooperation with the
autorecloser SMBRREC function.

The outputs TRN and TRIP are activated when the input TRINN is activated.

The SMPPTRC function is equipped with logic which secures correct operation for evolving faults as
well as for reclosing on to persistent faults. A binary input P3PTR is provided which will force all
tripping to be three-phase. This input is required in order to cooperate with the SMBRREC function.

In multi-breaker arrangements, one SMPPTRC function block is used for each circuit breaker.

The lockout function


The SMPPTRC function block is provided with possibilities to initiate lockout. The lockout can be set
to only activate the circuit breaker lockout output CLLKOUT or to both initiate the circuit breaker
lockout output and to maintain the trip signal outputs TRIP, TRL1, TRL2, TRL3, and TR3P (latched).

If external conditions are required to initiate a circuit breaker lockout, it can be achieved by activating
input SETLKOUT. The settingAutoLock = Off means that the internal three-phase trip will not activate
lockout so only initiation of the input SETLKOUT will result in lockout. This is normally the case for
overhead line protection where most faults are transient. Unsuccessful autoreclosing and back-up
zone tripping can in such cases be connected to initiate lockout by activating the input SETLKOUT.

If CLLKOUT is set by an external trip signal from another protection function, that is by activating
SETLKOUT input, or internally by a three-phase trip, that is with the setting AutoLock = On and the
setting TripLockout = On, then also all trip outputs are set latched.

The lockout can manually be reset after checking the primary fault by activating the reset lockout
input RSTLKOUT.

The BLKLKOUT input blocks the circuit breaker lockout output CLLKOUT.

The following three sequences in the following table shows the interaction between the inputs
BLOCK, BLKLKOUT, SETLKOUT, RSTLKOUT and the output CLLKOUT.

Table 314: Lockout related signal interactions

Inputs Output
BLOCK BLKLKOUT SETLKOUT RSTLKOUT CLLKOUT
Active - - - False
Active - Active - False
- - - - False

- - Active - True
Active - - - True
Active - - Activated True
- - - - True

- Active - - False
Table continues on next page

422 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Inputs Output
BLOCK BLKLKOUT SETLKOUT RSTLKOUT CLLKOUT
- Active Active - False
- - - - True
- - - Activated False

Directional data
Merged directional data from application functions can be provided to the trip function (SMPPTRC)
via the start matrix function (SMAGAPC) connected to the STDIR input.

The directional input signal STDIR is a coded integer signal which contains 15 individual Boolean
signals, see Figure 236:

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (start L1)
b4= FWL1 (forward L1)
b5= REVL1 (reverse L1)
b6= STL2 (start L2)
b7= FWL2 (forward L2)
b8= REVL2 (reverse L2)
b9= STL3 (start L3)
b10= FWL3 (forward L3)
b11= REVL3 (reverse L3)
b12= STN (start N)
b13= FWN (forward N)
b14= REVN (reverse N)

The indications for general start START and phase-wise starts STL1, STL2 and STL3, and neutral
STN and general directional forward FW and reverse REV are all available as outputs on the trip
function.

All start and directional outputs are mapped to the IEC 61850 logical node data model of the trip
function. The time stamping is updated each time an operate or start signal is changed:

• The common DIR output (general) is mapped as:

dirGeneral
0 unknown
1 forward
2 backward (reverse)
3 both

• The phase wise directional outputs (DIRL1, DIRL2, DIRL3, and DIRN) are mapped as:

Transformer protection RET650 423


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

dirPhsA, dirPhsB, dirPhsC, dirNeut


0 unknown
1 forward
2 backward (reverse)

Fault current and voltage reporting


The snapshot of each phase current DFT values (FLTILxMAG/FLTILxANG), each phase voltage DFT
values (FLTULxMAG/FLTULxANG), neutral current magnitude and angle (FLTINMAG/FLTINANG),
and neutral voltage magnitude and angle (FLTUNMAG/FLTUNANG) will be taken at the positive
edge of the TRIP activation. These values also will be stored and reported to IEC 61850, LHMI, and
the monitoring tool at the instant of TRIP activation, for example, if the TRIP signal of PHPIOC is
connected to the TRINALL signal of the SMPPTRC function. The functionality is shown in Figure
231.

TRIP

Instantaneous samples

DFT values (SMAI o/p)

FLTIL1MAG

IL1

FLTIL2MAG

IL2

FLTIL3MAG

IL3

GUID-8178BD9C-69CB-4C1C-905E-59626FD6B5ED V1 EN-US

Figure 231: Reporting of fault current


The reported outputs (FLTILxMAG/FLTILxANG, FLTULxMAG/FLTULxANG, FLTINMAG/FLTINANG,
and FLTUNMAG/FLTUNANG) show the previous event values until a new positive edge trigger is
received by TRINx input.

424 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

If the signal RESET is HIGH, SMPPTRC will set all the reported current magnitudes to
-1.000A, voltage magnitudes to -0.001kV, current and voltage angles to -1.000deg values
respectively.

If the group connections of current and voltage are not connected to SMAI or the signal
quality is bad, the SMPPTRC function will set all the reported current magnitudes to
-2.000A, voltage magnitudes to -0.002kV, current and voltage angles to -2.000deg values
respectively, indicating Invalid data.

12.1.7.1 Logic diagram M12258-7 v8

tTripMin
BLOCK TRIPALL
OR
AND t

TRINL1
TRINL2
TRINL3
TRINALL OR
1PTREF
1PTRZ

IEC05000517 V6 EN-US

Figure 232: Three-phase front logic — simplified logic diagram

Transformer protection RET650 425


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

TRINALL
TRINL1
OR L1TRIP
PSL1
AND

TRINL2
OR L2TRIP
PSL2
AND

TRINL3
OR L3TRIP
PSL3
AND

-LOOP

OR OR
OR

AND
AND

OR
tWaitForPHS
-LOOP t

OR

1PTRE AND
F AND

1PTRZ OR

IEC10000056 V6 EN-US

Figure 233: Phase segregated front logic

tTripMin
BLOCK
OR TRIPL1
L1TRIP AND t OR

tEvolvingFault

t TRIP
AND

L2TRIP
L3TRIP
OR
P3PTR

IEC17000065 V3 EN-US

Figure 234: Simplified additional logic per phase, Program = 1ph/3ph or 1ph/2ph/3ph

426 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

TRIPL1
OR TRL1
OR

TRIPL2
OR TRL2
OR

TRIPL3
OR TRL3
OR
TRIPN TRN

OR OR TRIP
OR
TRIPALL
OR -LOOP

OR
-LOOP AND
AND TR3P
OR
AND OR
AND
10 ms To ensure that the
fault is single phase TR1P
AND t

OR To ensure that the


5 ms
fault is two phase TR2P
t
OR

AND

AND OR AND
OR

-LOOP
AND

TripLockout
AND AND
AutoLock -LOOP

SETLKOUT OR
OR AND CLLKOUT
AND AND

RSTLKOUT
AND
AND
BLOCK

BLKLKOUT

IEC17000066 V4 EN-US

Figure 235: Final tripping circuits

Transformer protection RET650 427


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Directional logic

IntToBits
STDIR START START
in b0
FW STL1
b1
REV STL2
b2
STL1 STL3
b3
FWL1 STN
b4
REVL1
b5
STL2
b6
FWL2 FW
b7
REVL2 BitsToInt
b8 dirGeneral (61850 Standard)
STL3
b9 0 = unknown
FWL3 b0 out
b10 DIR 1 = forward
REVL3 b1 2 = backward (reverse)
b11
STN 3 = both
b12
FWN REV
b13
REVN
b14
b15

BitsToInt dirPhsA (61850 Standard)


0 = unknown
AND b0 out DIRL1
b0 = START 1 = forward
b1 2 = backward (reverse)
b1 = FW
b2 = REV
b3 = STL1 XOR
b4 = FWL1
b5 = REVL1
b6 = STL2 AND
b7 = FWL2
b8 = REVL2
b9 = STL3 BitsToInt dirPhsB (61850 Standard)
b10 = FWL3
0 = unknown
b11 = REVL3 AND b0 out DIRL2
1 = forward
b12 = STN b1 2 = backward (reverse)
b13 = FWN
b14 = REVN
b15 = N/A XOR

AND

BitsToInt dirPhsC (61850 Standard)


0 = unknown
AND b0 out DIRL3
1 = forward
b1 2 = backward (reverse)

XOR

AND

BitsToInt dirNeut (61850 Standard)


0 = unknown
AND b0 out DIRN
1 = forward
b1 2 = backward (reverse)

XOR

AND

IEC16000179 V3 EN-US

Figure 236: The directional logic

12.1.8 Technical data


M12380-1 v16

Table 315: SMPPTRC technical data

Function Range or value Accuracy


Trip action, Program 3 phase, 1ph/2ph, 1ph/2ph/3ph -
Minimum trip pulse length, tTripMin (0.000 - 60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay, tWaitForPHS (0.020 - 0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay, (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
tEvolvingFault

428 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.2 General start matrix block SMAGAPC

12.2.1 Identification GUID-C6D3DE50-03D2-4F27-82FF-623E81D019F4 v1

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generat start matrix block SMAGAPC - -

12.2.2 Functionality GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3

The Start Matrix (SMAGAPC) merges start and directional output signals from different application
functions and creates a common start and directional output signal (STDIR) to be connected to the
Trip function, see Figure 237.

The purpose of this functionality is to provide general start and directional information for the IEC
61850 trip logic data model SMPPTRC.

12.2.3 Function block GUID-99B1DF71-F7C4-4954-8688-BC709C3C2A16 v1

SMAGAPC
BLOCK STDIR
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16

IEC16000165-1-en.vsdx
IEC16000165 V1 EN-US

Figure 237: SMAGAPC function block

12.2.4 Signals
PID-6906-INPUTSIGNALS v2

Table 316: SMAGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
STDIR1 INTEGER 0 Start direction input 1
STDIR2 INTEGER 0 Start direction input 2
STDIR3 INTEGER 0 Start direction input 3
STDIR4 INTEGER 0 Start direction input 4
STDIR5 INTEGER 0 Start direction input 5
STDIR6 INTEGER 0 Start direction input 6
STDIR7 INTEGER 0 Start direction input 7
STDIR8 INTEGER 0 Start direction input 8
Table continues on next page

Transformer protection RET650 429


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Name Type Default Description


STDIR9 INTEGER 0 Start direction input 9
STDIR10 INTEGER 0 Start direction input 10
STDIR11 INTEGER 0 Start direction input 11
STDIR12 INTEGER 0 Start direction input 12
STDIR13 INTEGER 0 Start direction input 13
STDIR14 INTEGER 0 Start direction input 14
STDIR15 INTEGER 0 Start direction input 15
STDIR16 INTEGER 0 Start direction input 16

PID-6906-OUTPUTSIGNALS v2

Table 317: SMAGAPC Output signals

Name Type Description


STDIR INTEGER Common start direction output

12.2.5 Settings
PID-6906-SETTINGS v2

Table 318: SMAGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

12.2.6 Operation principle GUID-02403756-5715-4D6B-9308-540D72979BD0 v3

Start matrix
The Start Matrix function requires that a protection function delivers the directional output signals in a
fixed order to Start Matrix.

A directional input signal STDIRX of the Start Matrix is of type word. Each input contains 14
individual Boolean signals, which are positioned as, see Figure 239.

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

430 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

The StartMatrix function contains two function: the START criteria and the DIRECTION criteria, see
Figure 238.

The START criteria is to ensure that a forward and reverse signal shall come together with a start
signal to pass through the block. This is done individually for each protection function connected to
the StartMatrix via the STDIRX inputs, see Figure 239.

All STDIROUT signals are then connected via an OR gate, see Figure 238.

The DIRECTION criteria allow either forward or reverse (phase-wise forward FWLx or forward
neutral FWN or phase-wise reverse REVLx or reverse neutral REVN) to pass through to the general
STDIR output. If both forward and reverse are active phase-wise (e.g. REVLx=FWLx = True) or at
neutral (e.g. FWN = REVN = True) at the same time, none will be shown, see Figure 240.

SMAGAPC
(StartMatrix)

START Criteria
STDIR1
STDIRX STDIROUT

START Criteria
STDIR2
STDIRX STDIROUT

START Criteria
STDIR3
STDIRX STDIROUT
DIRECTION Criteria
STDIR
≥1 STDIRIN STDIR
START Criteria
STDIR4
STDIRX STDIROUT

START Criteria
STDIR5
STDIRX STDIROUT

START Criteria
STDIR6
STDIRX STDIROUT

START Criteria
STDIR7
STDIRX STDIROUT

START Criteria
STDIR8
STDIRX STDIROUT

START Criteria
STDIR9
STDIRX STDIROUT

START Criteria
STDIR10
STDIRX STDIROUT

START Criteria
STDIR11
STDIRX STDIROUT

START Criteria
STDIR12
STDIRX STDIROUT

START Criteria
STDIR13
STDIRX STDIROUT

START Criteria
STDIR14
STDIRX STDIROUT

START Criteria
STDIR15
STDIRX STDIROUT

START Criteria
STDIR16
STDIRX STDIROUT

IEC16000161-2-en.vsdx
IEC16000161 V2 EN-US

Figure 238: The StartMatrix function

Transformer protection RET650 431


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

START Criteria

START (in)
STL1 (in)
STL2 (in) ≥1 START (out)
STL3 (in)
IntToBits STN (in) BitsToint
STDIRX STDIROUT
in b0 START (in) STL1 (out) START (out) b0 out
b1 FW (in) STL2 (out) FW (out) b1
b2 REV (in) STL3 (out) REV (out) b2
b3 STL1 (in) STN (out) STL1 (out) b3
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
&
b6 STL2 (in) FW (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
≥1 FW (out)
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) & REVL3 (out) b11
REV (in)
b12 STN (in) STN (out) b12
b13 FWN (in) ≥1 REV (out) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15

& FWL1 (out)


FWL1 (in)

& REVL1 (out)


REVL1 (in)

& FWL2 (out)


FWL2 (in)

& REVL2 (out)


REVL2 (in)

& FWL3 (out)


FWL3 (in)

& REVL3 (out)


REVL3 (in)

& FWN (out)


FWN (in)

& REVN (out)


REVN (in)

IEC16000162-2-en.vsdx

IEC16000162 V2 EN-US

Figure 239: The START Criteria function

DIRECTION Criteria

START (in) START (out)


IntToBits STL1 (in) STL1 (out) BitsToint
STDIRIN STL2 (in) STL2 (out) STDIR
in b0 START (in) START (out) b0 out
STL3 (in) STL3 (out)
b1 FW (in) FW (out) b1
STN (in) STN (out)
b2 REV (in) REV (out) b2
b3 STL1 (in) STL1 (out) b3
FW (in)
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
≥1 FW (out)
b6 STL2 (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
REV (in)
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) REVL3 (out) b11
≥1 REV (out)
b12 STN (in) STN (out) b12
b13 FWN (in) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15
& FWL1 (out)

FWL1 (in)
=1
REVL1 (in)

& REVL1 (out)

& FWL2 (out)

FWL2 (in)
=1
REVL2 (in)

& REVL2 (out)

& FWL3 (out)

FWL3 (in)
=1
REVL3 (in)

& REVL3 (out)

& FWN (out)

FWN (in)
=1
REVN (in)

& REVN (out)

IEC16000163-2-en.vsdx

IEC16000163 V2 EN-US

Figure 240: The DIRECTION Criteria function

STARTCOMB
To make it possible to provide the directional information from a protection function, a STARTCOMB
block is used in between the application function and the Start Matrix function.

The STARTCOMB function has one block input and 14 Boolean inputs that convert the 14 Boolean
inputs into a WORD output STDIR, see Figure 241.

432 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

STARTCOMB
BLOCK STDI R
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US

Figure 241: STARTCOMB

Protection functions
Some protection functions are provided with start and directional outputs, for example:

• Protection 1: General START, FW and REV


• Protection 2: Phase-wise STLx, FWLx and REVLx (where x = 1, 2 and 3)
• Protection 3: STN, FWN and REVN
• Protection 4: STDIR

Connection example
In Figure 242 below is an example how to connect start and directional signals from protection
functions via STARTCOMB and SMAGAPC to SMPPTRC.

Transformer protection RET650 433


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

SMAGAPC
STARTCOMB BLOCK STDIR
PROTECTION 1 BLOCK STDIR STDIR1
START START STDIR2
FW FW STDIR3
REV REV STDIR4
STL1 STDIR5
FWL1 STDIR6 SMPPTRC
REVL1 STDIR7 BLOCK TRIP
STL2 STDIR8 BLKLKOUT TRL1
FWL2 STDIR9 TRIN TRL2
REVL2 STDIR10 TRINL1 TRL3
STL3 STDIR11 TRINL2 TR1P
FWL3 STDIR12 TRINL3 TR2P
REVL3 STDIR13 PSL1 TR3P
STN STDIR14 PSL2 CLLKOUT
FWN STDIR15 PSL3 START
REVN STDIR16 1PTRZ STL1
1PTREF STL2
P3PTR STL3
STARTCOMB SETLKOUT STN
BLOCK STDIR RSTLKOUT FW
START STDIR REV
FW
PROTECTION 2 REV
STL1 STL1
FWL1 FWL1
REVL1 REVL1
STL2 STL2
FWL2 FWL2
REVL2 REVL2
STL3 STL3
FWL3 FWL3
REVL3 REVL3
STN
FWN
REVN

STARTCOMB
BLOCK STDIR
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
PROTECTION 4
FWL3
-
PROTECTION 3 REVL3
STDIR
STN STN
-
FWN FWN
-
REVN REVN
IEC16000164-2-en.vsdx
IEC16000164 V2 EN-US

Figure 242: Connection example of protection functions using STARTCOMB, SMAGAPC to


SMPPTRC

12.3 Trip matrix logic TMAGAPC IP15121-1 v4

12.3.1 Identification
SEMOD167882-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Trip matrix logic TMAGAPC - -

434 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.3.2 Functionality M15321-3 v14

The trip matrix logic function has 3 output signals and these outputs can be connected to physical
tripping outputs according to the specific application needs for settable pulse or steady output.

12.3.3 Function block SEMOD54400-4 v6

TMAGAPC
BLOCK OUTPUT1
BLK1 OUTPUT2
BLK2 OUTPUT3
BLK3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32
IEC13000197 V2 EN-US

Figure 243: TMAGAPC function block

12.3.4 Signals
PID-6513-INPUTSIGNALS v4

Table 319: TMAGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
BLK1 BOOLEAN 0 Block of output 1
BLK2 BOOLEAN 0 Block of output 2
BLK3 BOOLEAN 0 Block of output 3
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
Table continues on next page

Transformer protection RET650 435


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Name Type Default Description


INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16
INPUT17 BOOLEAN 0 Binary input 17
INPUT18 BOOLEAN 0 Binary input 18
INPUT19 BOOLEAN 0 Binary input 19
INPUT20 BOOLEAN 0 Binary input 20
INPUT21 BOOLEAN 0 Binary input 21
INPUT22 BOOLEAN 0 Binary input 22
INPUT23 BOOLEAN 0 Binary input 23
INPUT24 BOOLEAN 0 Binary input 24
INPUT25 BOOLEAN 0 Binary input 25
INPUT26 BOOLEAN 0 Binary input 26
INPUT27 BOOLEAN 0 Binary input 27
INPUT28 BOOLEAN 0 Binary input 28
INPUT29 BOOLEAN 0 Binary input 29
INPUT30 BOOLEAN 0 Binary input 30
INPUT31 BOOLEAN 0 Binary input 31
INPUT32 BOOLEAN 0 Binary input 32

PID-6513-OUTPUTSIGNALS v5

Table 320: TMAGAPC Output signals

Name Type Description


OUTPUT1 BOOLEAN OR function between inputs 1 to 16
OUTPUT2 BOOLEAN OR function between inputs 17 to 32
OUTPUT3 BOOLEAN OR function between inputs 1 to 32

12.3.5 Settings
PID-6513-SETTINGS v4

Table 321: TMAGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
ModeOutput1 Steady - - Steady Mode for output ,1 steady or pulsed
Pulsed
ModeOutput2 Steady - - Steady Mode for output 2, steady or pulsed
Pulsed
ModeOutput3 Steady - - Steady Mode for output 3, steady or pulsed
Pulsed

436 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.3.6 Operation principle SEMOD52537-5 v9

The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3 output signals. The
function block incorporates internal logic OR gates in order to provide grouping of connected input
signals to the three output signals from the function block.

Internal built-in OR logic is made in accordance with the following three rules:

1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the first output
signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value 1 the
second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the third output
signal (OUTPUT3) will get logical value 1.

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime, OnDelay and


OffDelay the behavior of each output can be customized. The OnDelay is always active and will
delay the input to output transition by the set time. The ModeOutput for respective output decides
whether the output shall be steady with an drop-off delay as set by OffDelay or if it shall give a pulse
with duration set by PulseTime. Note that for pulsed operation and that the inputs are connected in
an OR-function, a new pulse will only be given on the output if all related inputs are reset and then
one is activated again. For steady operation the OffDelay will start when all related inputs have reset.
Detailed logical diagram is shown in Figure 244

PulseTime

t
&
ModeOutput1=Pulsed
INPUT 1
OUTPUT 1
Ondelay Offdelay
&
1
1 t t

PulseTime

t
&
ModeOutput2=Pulsed

OUTPUT 2
Ondelay Offdelay
&
1
1 t t

PulseTime
t
&

ModeOutput3=Pulsed

OUTPUT 3
Ondelay Offdelay
&
1
1 t t

IEC09000612 V4 EN-US

Figure 244: Trip matrix internal logic


Output signals from TMAGAPC are typically connected to other logic blocks or directly to output
contacts in the IED. When used for direct tripping of the circuit breaker(s) the pulse time shall be set
to at least 0.150 seconds in order to obtain satisfactory minimum duration of the trip pulse to the
circuit breaker trip coils.

Transformer protection RET650 437


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.3.7 Technical data


GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3

Table 322: Number of TMAGAPC instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
TMAGAPC 6 6 -

12.4 Logic for group alarm ALMCALH GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

12.4.1 Identification GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group alarm ALMCALH - -

12.4.2 Functionality GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4

The group alarm logic function (ALMCALH) is used to route several alarm signals to a common
indication, LED and/or contact, in the IED.

12.4.3 Function block GUID-EA192656-71DD-4D44-A1D5-96B1B4937971 v1

ALMCALH
BLOCK ALARM
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000181 V2 EN-US

12.4.4 Signals
PID-6510-INPUTSIGNALS v5

Table 323: ALMCALH Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
Table continues on next page

438 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Name Type Default Description


INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-6510-OUTPUTSIGNALS v6

Table 324: ALMCALH Output signals

Name Type Description


ALARM BOOLEAN OR function between inputs 1 to 16

12.4.5 Settings
PID-6510-SETTINGS v5

Table 325: ALMCALH Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

12.4.6 Operation principle GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2

The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output ALARM signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.

Input 1
200 ms
ALARM
1 t

IEC13000191 V2 EN-US

Figure 245: Group alarm logic

Transformer protection RET650 439


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.4.7 Technical data


GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2

Table 326: Number of ALMCALH instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
ALMCALH - - 5

12.5 Logic for group warning WRNCALH

12.5.1 Identification GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group warning WRNCALH - -

12.5.2 Functionality GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4

The group warning logic function (WRNCALH) is used to route several warning signals to a common
indication, LED and/or contact, in the IED.

12.5.3 Function block GUID-C909E4FB-3F7A-47F7-8988-36B159E2C7B2 v1

WRNCALH
BLOCK WARNING
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000182 V2 EN-US

12.5.4 Signals
PID-4127-INPUTSIGNALS v3

Table 327: WRNCALH Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
Table continues on next page

440 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Name Type Default Description


INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4127-OUTPUTSIGNALS v3

Table 328: WRNCALH Output signals

Name Type Description


WARNING BOOLEAN OR function betweeen inputs 1 to 16

12.5.5 Settings
PID-4127-SETTINGS v3

Table 329: WRNCALH Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

12.5.6 Operation principle GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2

The logic for group warning WRNCALH block is provided with 16 input signals and 1 WARNING
output signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output WARNING signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the WARNING output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.

INPUT1
200 ms
WARNING
³1 t
INPUT16

IEC13000192-1-en.vsd
IEC13000192 V1 EN-US

Transformer protection RET650 441


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.5.7 Technical data


GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2

Table 330: Number of WRNCALH instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
WRNCALH - - 5

12.6 Logic for group indication INDCALH

12.6.1 Identification GUID-3B5D4371-420D-4249-B6A4-5A168920D635 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group indication INDCALH - -

12.6.2 Functionality GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4

The group indication logic function (INDCALH) is used to route several indication signals to a
common indication, LED and/or contact, in the IED.

12.6.3 Function block GUID-9D89E183-449A-4016-AB83-E57C8DDBA843 v1

INDCALH
BLOCK IND
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC13000183 V2 EN-US

12.6.4 Signals
PID-4128-INPUTSIGNALS v4

Table 331: INDCALH Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
Table continues on next page

442 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Name Type Default Description


INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4128-OUTPUTSIGNALS v4

Table 332: INDCALH Output signals

Name Type Description


IND BOOLEAN OR function betweeen inputs 1 to 16

12.6.5 Settings
PID-4128-SETTINGS v4

Table 333: INDCALH Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

12.6.6 Operation principle GUID-72B1B4E8-BC6C-4AF7-8B41-058241B944F8 v2

The logic for group indication INDCALH block is provided with 16 input signals and 1 IND output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output IND signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND output signal
will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.

INPUT1
200 ms
IND
1 t
INPUT16

IEC13000193 V2 EN-US

12.6.7 Technical data


GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2

Table 334: Number of INDCALH instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
INDCALH - 5 -

Transformer protection RET650 443


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.7 Basic configurable logic blocks M11396-4 v20

The basic configurable logic blocks do not propagate the time stamp and quality of signals. The list
below shows a summary of the function blocks and their features.

The logic blocks are available as a part of an extension logic package. The list below is a summary of
the function blocks and their features.

• AND function block. The AND function is used to form general combinatory expressions with
boolean variables. The AND function block has up to four inputs and two outputs.

• GATE function block is used for whether or not a signal should be able to pass from the input to
the output.

• INVERTER function block that inverts the input signal to the output.

• LLD function block. Loop delay used to delay the output signal one execution cycle.

• OR function block. The OR function is used to form general combinatory expressions with
boolean variables. The OR function block has up to six inputs and two outputs. One of the
outputs is inverted.

• PULSETIMER function block can be used, for example, for pulse extensions or limiting of
operation of outputs, settable pulse time.

• RSMEMORY function block is a flip-flop that can reset or set an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting controls if,
after a power interruption, the flip-flop resets or returns to the state it had before the power
interruption. RESET input has priority.

• SRMEMORY function block is a flip-flop that can set or reset an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting controls if
the block's output should reset or return to the state it was, after a power interruption. The SET
input has priority if both SET and RESET inputs are operated simultaneously.

• TIMERSET function has pick-up and drop-out delayed outputs related to the input signal. The
timer has a settable time delay and must be On for the input signal to activate the output with
the appropriate time delay.

• XOR is used to generate combinatory expressions with boolean variables. XOR has two inputs
and two outputs. One of the outputs is inverted. The output signal OUT is 1 if the input signals
are different and 0 if they are the same.

12.7.1 AND function block IP11013-1 v3

M11453-3 v4
The AND function is used to form general combinatory expressions with boolean variables. The AND
function block has up to four inputs and two outputs. One of the outputs is inverted.

12.7.1.1 Function block


M11452-3 v2

AND
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
IEC14000071 V2 EN-US

Figure 246: AND function block

444 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.7.1.2 Signals
PID-3437-INPUTSIGNALS v7

Table 335: AND Input signals

Name Type Default Description


INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4

PID-3437-OUTPUTSIGNALS v7

Table 336: AND Output signals

Name Type Description


OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

12.7.1.3 Technical data


GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3

Table 337: Number of AND instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
AND 60 60 160

12.7.2 Controllable gate function block GATE IP11021-1 v2

M11489-3 v2
The Controllable gate function block (GATE) is used for controlling if a signal should be able to pass
from the input to the output or not depending on a setting.

12.7.2.1 Function block


M11490-3 v2

GATE
INPUT OUT

IEC04000410-2-en.vsd
IEC04000410 V2 EN-US

Figure 247: GATE function block

12.7.2.2 Signals
PID-3801-INPUTSIGNALS v6

Table 338: GATE Input signals

Name Type Default Description


INPUT BOOLEAN 0 Input to gate

PID-3801-OUTPUTSIGNALS v5

Table 339: GATE Output signals

Name Type Description


OUT BOOLEAN Output from gate

Transformer protection RET650 445


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.7.2.3 Settings
PID-3801-SETTINGS v6

Table 340: GATE Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

12.7.2.4 Technical data


GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3

Table 341: Number of GATE instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
GATE 10 10 20

12.7.3 Inverter function block INV IP11011-1 v2

12.7.3.1 Function block


M11445-3 v1

INV
INPUT OUT
IEC04000404 V3 EN-US

Figure 248: INV function block

12.7.3.2 Signals
PID-3803-INPUTSIGNALS v5

Table 342: INV Input signals

Name Type Default Description


INPUT BOOLEAN 0 Input

PID-3803-OUTPUTSIGNALS v4

Table 343: INV Output signals

Name Type Description


OUT BOOLEAN Output

12.7.3.3 Technical data


GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3

Table 344: Number of INV instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
INV 90 90 240

12.7.4 Loop delay function block LLD GUID-05D959B5-A55B-437C-8E8F-831A4A357E24 v2

GUID-64B24094-010D-4B8F-8B7B-DDD49499AAE5 v3
The Logic loop delay function block (LLD) function is used to delay the output signal one execution
cycle, that is, the cycle time of the function blocks used.

446 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.7.4.1 Function block


GUID-EE44CFDF-C8F7-4870-BD1C-98D9CD91FD97 v4

LLD
INPUT OUT
IEC15000144 V2 EN-US

Figure 249: LLD function block

12.7.4.2 Signals
PID-3805-INPUTSIGNALS v5

Table 345: LLD Input signals

Name Type Default Description


INPUT BOOLEAN 0 Input signal

PID-3805-OUTPUTSIGNALS v5

Table 346: LLD Output signals

Name Type Description


OUT BOOLEAN Output signal delayed one execution cycle

12.7.4.3 Technical data


GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2

Table 347: Number of LLD instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
LLD 10 10 20

12.7.5 OR function block IP11012-1 v3

M11449-3 v2
The OR function is used to form general combinatory expressions with boolean variables. The OR
function block has up to six inputs and two outputs. One of the outputs is inverted.

12.7.5.1 Function block


M11448-3 v1

OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6
IEC04000405 V3 EN-US

Figure 250: OR function block

Transformer protection RET650 447


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.7.5.2 Signals
PID-3806-INPUTSIGNALS v5

Table 348: OR Input signals

Name Type Default Description


INPUT1 BOOLEAN 0 Input 1 to OR gate
INPUT2 BOOLEAN 0 Input 2 to OR gate
INPUT3 BOOLEAN 0 Input 3 to OR gate
INPUT4 BOOLEAN 0 Input 4 to OR gate
INPUT5 BOOLEAN 0 Input 5 to OR gate
INPUT6 BOOLEAN 0 Input 6 to OR gate

PID-3806-OUTPUTSIGNALS v5

Table 349: OR Output signals

Name Type Description


OUT BOOLEAN Output from OR gate
NOUT BOOLEAN Inverted output from OR gate

12.7.5.3 Technical data


GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4

Table 350: Number of OR instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
OR 78 60 160

12.7.6 Pulse timer function block PULSETIMER IP11016-1 v2

M11466-3 v3
The pulse (PULSETIMER) function can be used, for example, for pulse extensions or limiting the
operation time of outputs. The PULSETIMER has a settable length. When the input is 1, the output
will be 1 for the time set by the time delay parameter t. Then it returns to 0.

12.7.6.1 Function block


M11465-3 v4

PULSETIMER
INPUT OUT
IEC04000407 V4 EN-US

Figure 251: PULSETIMER function block

12.7.6.2 Signals
PID-6985-INPUTSIGNALS v1

Table 351: PULSETIMER Input signals

Name Type Default Description


INPUT BOOLEAN 0 Input to pulse timer

448 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

PID-6985-OUTPUTSIGNALS v1

Table 352: PULSETIMER Output signals

Name Type Description


OUT BOOLEAN Output from pulse timer

12.7.6.3 Settings
PID-6985-SETTINGS v1

Table 353: PULSETIMER Non group settings (basic)

Name Values (Range) Unit Step Default Description


t 0.000 - 90000.000 s 0.001 0.010 Time delay of function

12.7.6.4 Technical data


GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2

Table 354: Number of PULSETIMER instances

Logic block Quantity with cycle time Range or Value Accuracy


3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms

12.7.7 Reset-set with memory function block RSMEMORY GUID-9C93669F-078B-49EA-85B8-C4BB6A434734 v1

GUID-4C804DEA-3C83-4C20-82C6-BAD03BD48242 v6
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory that can reset or
set an output from two inputs respectively. Each RSMEMORY function block has two outputs, where
one is inverted. The memory setting controls if, after a power interruption, the flip-flop resets or
returns to the state it had before the power interruption. For a Reset-Set flip-flop, RESET input has
higher priority over SET input.

Table 355: Truth table for RSMEMORY function block

SET RESET OUT NOUT


0 0 Last value Inverted last
value
0 1 0 1
1 0 1 0
1 1 1 0

12.7.7.1 Function block


GUID-50D5A4C0-59BF-44DE-86AC-47640ACD35A7 v3

RSMEMORY
SET OUT
RESET NOUT
IEC09000294 V2 EN-US

Figure 252: RSMEMORY function block

Transformer protection RET650 449


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.7.7.2 Signals
PID-3811-INPUTSIGNALS v5

Table 356: RSMEMORY Input signals

Name Type Default Description


SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3811-OUTPUTSIGNALS v5

Table 357: RSMEMORY Output signals

Name Type Description


OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

12.7.7.3 Settings
PID-3811-SETTINGS v5

Table 358: RSMEMORY Group settings (basic)

Name Values (Range) Unit Step Default Description


Memory Off - - On Operating mode of the memory function
On

12.7.7.4 Technical data


GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2

Table 359: Number of RSMEMORY instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
RSMEMORY 10 10 20

12.7.8 Set-reset with memory function block SRMEMORY IP11020-1 v2

M11485-3 v4
The Set-reset with memory function block (SRMEMORY) is a flip-flop with memory that can set or
reset an output from two inputs respectively. Each SRMEMORY function block has two outputs,
where one is inverted. The memory setting controls if, after a power interruption, the flip-flop resets or
returns to the state it had before the power interruption. The input SET has priority.

Table 360: Truth table for SRMEMORY function block

SET RESET OUT NOUT


0 0 Last value Inverted
last value
0 1 0 1
1 0 1 0
1 1 1 0

450 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.7.8.1 Function block


M11484-3 v3

SRMEMORY
SET OUT
RESET NOUT
IEC04000408 V3 EN-US

Figure 253: SRMEMORY function block

12.7.8.2 Signals
PID-3813-INPUTSIGNALS v5

Table 361: SRMEMORY Input signals

Name Type Default Description


SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3813-OUTPUTSIGNALS v5

Table 362: SRMEMORY Output signals

Name Type Description


OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

12.7.8.3 Settings
PID-3813-SETTINGS v5

Table 363: SRMEMORY Group settings (basic)

Name Values (Range) Unit Step Default Description


Memory Off - - On Operating mode of the memory function
On

12.7.8.4 Technical data


GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2

Table 364: Number of SRMEMORY instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
SRMEMORY 10 10 20

12.7.9 Settable timer function block TIMERSET IP11022-1 v2

M11494-3 v3
The Settable timer function block (TIMERSET) timer has two outputs for the delay of the input signal
at drop-out and at pick-up. The timer has a settable time delay. It also has an Operation setting On
and Off that controls the operation of the timer.

Transformer protection RET650 451


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Input
tdelay

On

Off
tdelay

t
IEC08000289 V3 EN-US

Figure 254: TIMERSET status diagram

12.7.9.1 Function block


M11495-3 v3

TIMERSET
INPUT ON
OFF
IEC04000411 V3 EN-US

Figure 255: TIMERSET function block

12.7.9.2 Signals
PID-6976-INPUTSIGNALS v1

Table 365: TIMERSET Input signals

Name Type Default Description


INPUT BOOLEAN 0 Input to timer

PID-6976-OUTPUTSIGNALS v1

Table 366: TIMERSET Output signals

Name Type Description


ON BOOLEAN Output from timer, pick-up delayed
OFF BOOLEAN Output from timer, drop-out delayed

12.7.9.3 Settings
PID-6976-SETTINGS v1

Table 367: TIMERSET Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n

452 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.7.9.4 Technical data


GUID-C6C98FE0-F559-45EE-B853-464516775417 v3

Table 368: Number of TIMERSET instances

Logic block Quantity with cycle time Range or Value Accuracy


3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms

12.7.10 Exclusive OR function block XOR IP11018-1 v2

M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions with boolean
variables. XOR has two inputs and two outputs. One of the outputs is inverted. The output signal
OUT is 1 if the input signals are different and 0 if they are the same.

Table 369: Truth table for XOR function block

INPUT1 INPUT2 OUT NOUT


0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1

12.7.10.1 Function block


M11476-3 v1

XOR
INPUT1 OUT
INPUT2 NOUT
IEC04000409 V3 EN-US

Figure 256: XOR function block

12.7.10.2 Signals
PID-3817-INPUTSIGNALS v2

Table 370: XOR Input signals

Name Type Default Description


INPUT1 BOOLEAN 0 Input 1 to XOR gate
INPUT2 BOOLEAN 0 Input 2 to XOR gate

PID-3817-OUTPUTSIGNALS v2

Table 371: XOR Output signals

Name Type Description


OUT BOOLEAN Output from XOR gate
NOUT BOOLEAN Inverted output from XOR gate

Transformer protection RET650 453


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.7.10.3 Technical data


GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2

Table 372: Number of XOR instances

Logic block Quantity with cycle time


3 ms 8 ms 100 ms
XOR 10 10 20

12.8 Extension logic package IP11362-1 v2

When extra configurable logic blocks are required, an additional package can be ordered.
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8

12.9 Fixed signals FXDSIGN

12.9.1 Functionality M15322-3 v16

The Fixed signals function (FXDSIGN) has nine pre-set (fixed) output signals that can be used in the
configuration of an IED, either for forcing the unused inputs in other function blocks to a certain level/
value, or for creating certain logic. Boolean, integer, floating point, string types of signals are
available.

One FXDSIGN function block is included in all IEDs.

12.9.2 Function block SEMOD54909-4 v4

FXDSIGN
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF

IEC05000445-3-en.vsd
IEC05000445 V3 EN-US

Figure 257: FXDSIGN function block

12.9.3 Signals
PID-6191-OUTPUTSIGNALS v6

Table 373: FXDSIGN Output signals

Name Type Description


OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
INTALONE INTEGER Integer signal fixed all ones
REALZERO REAL Real signal fixed zero
Table continues on next page

454 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

Name Type Description


STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off

12.9.4 Settings
PID-1325-SETTINGS v12
The function does not have any settings available in Local HMI or Protection and Control IED
Manager (PCM600).

12.9.5 Operation principle SEMOD54827-5 v6

There are nine outputs from FXDSIGN function block:

• OFF is a boolean signal, fixed to OFF (boolean 0) value


• ON is a boolean signal, fixed to ON (boolean 1) value
• INTZERO is an integer number, fixed to integer value 0
• INTONE is an integer number, fixed to integer value 1
• INTALONE is an integer value FFFF (hex)
• REALZERO is a floating point real number, fixed to 0.0 value
• STRNULL is a string, fixed to an empty string (null) value
• ZEROSMPL is a channel index, fixed to 0 value
• GRP_OFF is a group signal, fixed to 0 value

12.10 Boolean 16 to Integer conversion B16I SEMOD175715-1 v1

12.10.1 Identification
SEMOD175721-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean 16 to integer conversion B16I - -

12.10.2 Functionality SEMOD175725-4 v5

Boolean to integer conversion, 16 bit (B16I) is used to transform a set of 16 boolean (logical) signals
into an integer.

Transformer protection RET650 455


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.10.3 Function block SEMOD175798-5 v4

B16I
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
IEC07000128 V3 EN-US

Figure 258: B16I function block

12.10.4 Signals
PID-3606-INPUTSIGNALS v4

Table 374: B16I Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-3606-OUTPUTSIGNALS v3

Table 375: B16I Output signals

Name Type Description


OUT INTEGER Output value

456 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.10.5 Monitored data


PID-3606-MONITOREDDATA v4

Table 376: B16I Monitored data

Name Type Values (Range) Unit Description


OUT INTEGER - - Output value

12.10.6 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

12.10.7 Operation principle SEMOD175737-4 v5

The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16 binary
inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sum of all the values
on the activated INx will be available on the output OUT as a sum of the integer values of all the
inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) are activated, that is =
Boolean 1, it corresponds to that integer 65535 is available on the output OUT. The B16I function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.

Values of each of the different OUTx from function block B16I for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block B16I

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.

Transformer protection RET650 457


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.10.8 Technical data


GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v4

Table 377: Number of B16I instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
B16I 6 4 8

12.11 Boolean to integer conversion with logical node


representation, 16 bit BTIGAPC SEMOD175753-1 v4

12.11.1 Identification
SEMOD175757-2 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean to integer conversion with BTIGAPC - -
logical node representation, 16 bit

12.11.2 Functionality SEMOD175781-4 v8

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to
transform a set of 16 boolean (logical) signals into an integer. The block input will freeze the output at
the last value.

12.11.3 Function block SEMOD175801-5 v4

BTIGAPC
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
IEC13000303 V2 EN-US

Figure 259: BTIGAPC function block

458 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.11.4 Signals
PID-6944-INPUTSIGNALS v2

Table 378: BTIGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-6944-OUTPUTSIGNALS v2

Table 379: BTIGAPC Output signals

Name Type Description


OUT INTEGER Output value

12.11.5 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

12.11.6 Monitored data


PID-6944-MONITOREDDATA v2

Table 380: BTIGAPC Monitored data

Name Type Values (Range) Unit Description


OUT INTEGER - - Output value

12.11.7 Operation principle SEMOD158425-4 v7

The Boolean 16 to integer conversion with logic node representation function (BTIGAPC) will transfer
a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a
value according to the table below from 0 to 32768. This follows the general formula: INx = 2x-1
where 1≤x≤16. The sum of all the values on the activated INx will be available on the output OUT as
a sum of the integer values of all the inputs INx that are activated. OUT is an integer. When all INx
(where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to that integer 65535 is available on
the output OUT. If the BLOCK input is activated, it will freeze the logical outputs at the last value.

Transformer protection RET650 459


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Table 381: Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

12.11.8 Technical data


GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2

Table 382: Number of BTIGAPC instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
BTIGAPC 4 4 8

12.12 Integer to boolean 16 conversion IB16

12.12.1 Identification
SEMOD167941-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion IB16 - -

12.12.2 Functionality SEMOD158373-5 v7

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
boolean (logical) signals.

460 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.12.3 Function block SEMOD158389-4 v4

IB16
BLOCK OUT1
INP OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC06000501 V4 EN-US

Figure 260: IB16 function block

12.12.4 Signals
PID-6938-INPUTSIGNALS v1

Table 383: IB16 Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INP INTEGER 0 Integer Input

PID-6938-OUTPUTSIGNALS v1

Table 384: IB16 Output signals

Name Type Description


OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

12.12.5 Setting parameters ABBD8E242451 v4

The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)

Transformer protection RET650 461


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.12.6 Operation principle SEMOD158385-4 v4

With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the remaining OUTx = 0
for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with the
table IB16_1. When not activated the OUTx has the value 0.

In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2 has a
value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx is equal to 1 + 2
+ 4 + 8 = 15.

This follows the general formulae: The sum of the values of all OUTx = 2x-1 where 1≤x≤16 will be
equal to the integer value on the input INP.

The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value between 0
to 65535 connected to the input INP to a combination of activated outputs OUTx where 1≤x≤16. The
sum of the values of all OUTx will then be equal to the integer on input INP. The values of the
different OUTx are according to the table below. When an OUTx is not activated, its value is 0.

When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535
is connected to input INP. The IB16 function is designed for receiving the integer input locally. If the
BLOCK input is activated, it will freeze the logical outputs at the last value.

Values of each of the different OUTx from function block IB16 for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block IB16.

Name of OUTx Type Description Value when activated Value when


deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

The sum of the numbers in column “Value when activated” when all OUTx (where x = 1 to 16) are
active that is=1; is 65535. 65535 is the highest integer that can be converted by the IB16 function
block.

462 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.12.7 Technical data


GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v3

Table 385: Number of IB16 instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
IB16 12 4 8

12.13 Integer to boolean conversion with logical node


representation, 16 bit ITBGAPC SEMOD158419-1 v4

12.13.1 Identification
SEMOD167944-2 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean conversion with ITBGAPC - -
logical node representation, 16 bit

12.13.2 Functionality SEMOD158421-5 v10

Integer to boolean conversion with logic node representation function (ITBGAPC) is used to
transform an integer which is transmitted over IEC 61850 and received by the function to 16 boolean
(logic) output signals.

ITBGAPC function can only receive remote values over IEC 61850 when the R/L (Remote/Local)
push button on the front HMI indicates that the control mode for the operator is in position R (Remote
i.e. the LED adjacent to R is lit), and the corresponding signal is connected to the input PSTO
ITBGAPC function block. The input BLOCK will freeze the output at the last received value and
blocks new integer values to be received and converted to binary coded outputs.

12.13.3 Function block SEMOD158435-4 v4

ITBGAPC
BLOCK OUT1
PSTO OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC14000012 V2 EN-US

Figure 261: ITBGAPC function block

Transformer protection RET650 463


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.13.4 Signals
PID-3627-INPUTSIGNALS v7

Table 386: ITBGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection

PID-3627-OUTPUTSIGNALS v7

Table 387: ITBGAPC Output signals

Name Type Description


OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

12.13.5 Settings
GUID-F573CA16-4821-4203-970A-F7D01AF5E63B v1
This function does not have any setting parameters.

12.13.6 Operation principle SEMOD176587-4 v7

An example is used to explain the principle of operation: With integer 15 sent to and received by the
ITBGAPC function on the IEC 61850 the OUTx changes from 0 to 1 on each of the OUT1; OUT2
OUT3 and OUT4. All other OUTx (5≤x≤16) remains 0. The boolean interpretation of this is
represented by the assigned values of each of the outputs OUT1 = 1; and OUT2 = 2; and OUT3= 4;
and OUT4 = 8. The sum of these OUTx (1≤x≤4) is equal to the integer 15 received via the IEC 61850
network. The remaining OUTx = 0 for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with the
Table 388. When not activated the OUTx has the value 0.

The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx = 2x-1 The sum of
the values of all activated OUTx = 2x-1 where 1≤x≤16 will be equal to the integer value received over
IEC 61850 to the ITBGAPC_1 function block.

The Integer to boolean conversion with logical node representation, 16 bit function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC 61850 and connected to
the ITBGAPC function block to a combination of activated outputs OUTx where 1≤x≤16. The values
represented by the different OUTx are according to Table 388. When an OUTx is not activated, its
value is 0.

464 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

The ITBGAPC function is designed for receiving the integer input from a station computer - for
example, over IEC 61850. If the BLOCK input is activated, it will freeze the logical outputs at the last
value.

Table 388: Outputs and their values when activated

Name of OUTx Type Description Value when activated Value when


deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active equals
65535. This is the highest integer that can be converted to boolean by the ITBGAPC function block.

The operator position input (PSTO) determines the operator place. The integer number that is
communicated to the ITBGAPC can only be written to the block while the PSTO is in position
“Remote”. If PSTO is in position ”Off” or ”Local”, then no changes are applied to the outputs.

12.13.7 Technical data


GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2

Table 389: Number of ITBGAPC instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
ITBGAPC 4 4 8

12.14 Elapsed time integrator with limit transgression and


overflow supervision TEIGAPC

12.14.1 Identification GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 device


identification identification number
Elapsed time integrator TEIGAPC - -

Transformer protection RET650 465


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.14.2 Functionality GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3

Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed time when a
given binary signal has been high, see also Figure 262.

BLOCK
RESET
IN Time Integration ACCTIME
with Retain

q-1

a
OVERFLOW
AND
a>b
999 999 s b

a
WARNING
AND
a>b
tWarning b

a
ALARM
AND
a>b
tAlarm b

q-1 = unit delay IEC13000290-2-en.vsd

IEC13000290 V2 EN-US

Figure 262: TEIGAPC logics


The main features of TEIGAPC

• Applicable to long time integration up to 999 999.9 seconds


• Supervision of overflow
• Possibility to define a warning and an alarm with the resolution of 10 milliseconds
• Retain the integration value
• Possibilities for blocking and reset of the total integrated time
• Report of the integrated time

12.14.3 Function block GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2

TEIGAPC
BLOCK WARNING
IN ALARM
RESET OVERFLOW
ACCTIME

IEC14000014-1-en.vsd
IEC14000014 V1 EN-US

Figure 263: TEIGAPC function block

12.14.4 Signals
PID-6836-INPUTSIGNALS v3

Table 390: TEIGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Freeze the integration and block the other outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time, when its
value is high
RESET BOOLEAN 0 Reset the integration time

466 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

PID-6836-OUTPUTSIGNALS v4

Table 391: TEIGAPC Output signals

Name Type Description


WARNING BOOLEAN Indicator of the integrated time has reached the warning limit
ALARM BOOLEAN Indicator of the integrated time has reached the alarm limit
OVERFLOW BOOLEAN Indicator of the integrated time has reached the overflow limit
ACCTIME REAL Integrated elapsed time in seconds

12.14.5 Settings
PID-6836-SETTINGS v2

Table 392: TEIGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
tWarning 1.00 - 999999.00 s 0.01 600.00 Time limit for warning supervision
tAlarm 1.00 - 999999.00 s 0.01 1200.00 Time limit for alarm supervision

12.14.6 Operation principle GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3

The elapsed time integrator (TEIGAPC) provides

• time integration, accumulating the elapsed time when a given binary signal has been high
• blocking and reset of the total integrated time
• supervision of limit transgression and overflow, the overflow limit is fixed to 999999.9 seconds
• retaining of the integrated value

Figure 264 describes the simplified logic of the function where the block “Time Integration“ covers the
logics for the first two items listed above while the block “Transgression Supervision Plus
Retain“ contains the logics for the last two.

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACCTIME
Time Integration
IN

Loop Delay

IEC12000195-4-en.vsd

IEC12000195 V4 EN-US

Figure 264: TEIGAPC Simplified logic


TEIGAPC main functionalities

Transformer protection RET650 467


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

• integration of the elapsed time when IN has been high


• applicable to long time integration (≤999 999.9 seconds)
• output ACCTIME presents integrated value in seconds
• integrated value is retained in nonvolatile memory
• any retained value with a warning/alarm/overflow is used as initiation value for the
integration following by a restart
• RESET: Reset of the integration value. Consequently all other outputs are also reset
• unconditionally on the input IN value
• reset the value of the nonvolatile memory to zero
• BLOCK: Freeze the integration and block/reset the other outputs
• unconditionally on the signal value
• BLOCK request overrides RESET request
• Monitor and report the conditions of limit transgression
• overflow if output ACCTIME >999999.9 seconds
• alarm if ACCTIME > tAlarm
• warning if ACCTIME > tWarning

The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm and tWarning
are the time limit parameters in seconds.

tAlarm and tWarning are user settable limits. They are also independent, that is, there is no check if
tAlarm > tWarning.

tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on the level of
the defined values for the parameters.

The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if an overflow
occurs.

12.14.6.1 Operation accuracy GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3

The accuracy of TEIGAPC depends on essentially three factors

• function cycle time


• the pulse length
• the number of pulses, that is, the number of rising and falling flank pairs

In principle, a shorter function cycle time, longer integrated time length or more pulses may lead to
reduced accuracy.

12.14.6.2 Memory storage GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3

The value of the integrated elapsed time is retained in a non-volatile memory.

468 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.14.7 Technical data


GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4

Table 393: TEIGAPC Technical data

Function Cycle time (ms) Range or value Accuracy


Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is
greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever
is greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever
is greater

Table 394: Number of TEIGAPC instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
TEIGAPC 4 4 4

12.15 Comparator for integer inputs INTCOMP

12.15.1 Identification GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparison of integer values INTCOMP Int<=>

12.15.2 Functionality GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1

The function gives the possibility to monitor the level of integer values in the system relative to each
other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision,
interlocking and other logics.

12.15.3 Function block GUID-EB28F45B-B1D0-452F-98B4-F96D7FA34069 v1

INTCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000052-1-en.vsdx
IEC15000052 V1 EN-US

12.15.4 Signals
PID-6928-INPUTSIGNALS v3

Table 395: INTCOMP Input signals

Name Type Default Description


INPUT INTEGER 0 Input value to be compared with reference value
REF INTEGER 0 Reference value to be compared with input value

Transformer protection RET650 469


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

PID-6928-OUTPUTSIGNALS v3

Table 396: INTCOMP Output signals

Name Type Description


INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

12.15.5 Settings
PID-6928-SETTINGS v2

Table 397: INTCOMP Group settings (basic)

Name Values (Range) Unit Step Default Description


EnaAbs Signed - - Signed Selection for absolute or signed
Absolute comparison
RefSource Set Value - - Set Value Selection for reference value either input
Input REF or setting
SetValue -2000000000 - - 1 100 Set value for reference
2000000000

12.15.6 Monitored data


PID-6928-MONITOREDDATA v1

Table 398: INTCOMP Monitored data

Name Type Values (Range) Unit Description


INEQUAL BOOLEAN - - Input value is equal to the reference value
INHIGH BOOLEAN - - Input value is higher than the reference
value
INLOW BOOLEAN - - Input value is lower than the reference
value

12.15.7 Operation principle GUID-E9C1B863-ACA7-45C0-91F1-A51FE38755FE v3

The comparison can be done in two ways,

• Between 2 inputs, INPUT and REF


• Between INPUT and the value set by the user SetValue.

The selection of reference value for comparison is done through setting RefSource. If RefSource is
selected as "Input REF" then the reference value for comparison is taken from second input signal
(REF). If RefSource is selected as "Set Value" then the reference value for comparison is taken from
setting (SetValue).

The comparison can be done either between absolute values or signed values, which is governed by
on the setting EnaAbs. If EnaAbs is selected as "Absolute" then both input and reference values are
converted into absolute values and comparison is done. If EnaAbs is selected as "Signed" then the
comparison is done without any conversion.

The function has three binary outputs representing the result of the comparison:

• If the input is above the reference value then INHIGH is set HIGH
• If the input is below the reference value then INLOW is set HIGH
• If the input is equal to reference value then INEQUAL is set HIGH

470 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.16 Comparator for real inputs REALCOMP

12.16.1 Identification GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparator for real inputs REALCOMP Real<=>

12.16.2 Functionality GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1

The function gives the possibility to monitor the level of real value signals in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.

12.16.3 Function block GUID-8752DF2A-D131-4461-80C6-C52F9980D228 v1

REALCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000053-1-en.vsdx
IEC15000053 V1 EN-US

12.16.4 Signals
PID-7248-INPUTSIGNALS v2

Table 399: REALCOMP Input signals

Name Type Default Description


INPUT REAL 0.000 Input value to be compared with reference value
REF REAL 0.000 Reference value to be compared with input value

PID-7248-OUTPUTSIGNALS v2

Table 400: REALCOMP Output signals

Name Type Description


INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

12.16.5 Settings

12.16.6 Operation principle GUID-3FA699A8-D076-4E5E-BCB8-C6B7907573D1 v3

The comparison can be done in two ways,

1. Between 2 inputs, INPUT and REF


2. Between INPUT and the SetValue setting

The selection of reference value for comparison is done through setting RefSource. If RefSource is
selected as "Input REF" then the reference value for comparison is taken from second input signal
(REF). If RefSource is selected as "Set Value" then the reference value for comparison is taken from
setting (SetValue).

Transformer protection RET650 471


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

Generally the inputs to the function are in units, but when the comparison is to be done with respect
to set level, then the user can scale the reference value in steps of 1000, as per the setting RefPrefix.
Internally the function handles the reference value for comparator as SetValue*RefPrefix.

Additionally the comparison can be done either between absolute values or signed values, which is
determined by the setting EnaAbs. If EnaAbs is selected as "Absolute" then both input and reference
values are converted into absolute values and then comparison is done. If EnaAbs is selected as
"Signed" then the comparison is done without absolute conversion.

This function has two settings EqualBandHigh and EqualBandLow to provide margins from reference
value for equal to condition. When the INPUT value is within high and low band around the reference
value, output INEQUAL will get set.

In order to avoid oscillations at boundary conditions of equal band low limit and high limit, hysteresis
has been provided. If the INPUT is above the equal high level margin including hysteresis, then
INHIGH will set. Similarly if the INPUT is below the equal low level margin including hysteresis, then
INLOW will set.

INEQUAL Reset / INHIGH Set INEQUAL Set / INHIGH Reset

EqualBandHigh

Internal
Equal Band REF or SetValue Hysteresis for
equal band

EqualBandLow

INEQUAL Reset / INLOW Set INEQUAL Set / INLOW Reset


IEC15000261-1-en.vsdx

IEC15000261 V1 EN-US

Figure 265: Operation principle of REALCOMP

When EnaAbs is set as absolute comparison and SetValue is set less than 0.1% of the
set unit then INLOW output will never pick up. During the above mentioned condition, due
to marginal value for avoiding oscillations of function outputs, the INLOW output will
never set.

12.16.7 Technical data


GUID-62792FCB-B436-4034-9A08-C9FF918FF547 v1
REALCOMP function can compare the values from milli value level to giga value level and the
maximum expectable accuracy level from the function is 10 µ.
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4

Table 401: Number of REALCOMP instances

Function Quantity with cycle time


3 ms 8 ms 100 ms
REALCOMP 10 10 10

472 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.17 Hold maximum and minimum of input HOLDMINMAX GUID-18E05AF9-05D1-49C0-BD89-9BCB4F168907 v1

12.17.1 Identification GUID-18E05AF9-05D1-49C0-BD89-9BCB4F168907 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Hold maximum and minimum of input HOLDMINMAX - -

12.17.2 Functionality GUID-7DA0AA9A-CCEA-4467-B67E-45B9C1DC145A v1

Hold minimum and maximum of input (HOLDMINMAX) function will acquire, compare and hold the
minimum and maximum values of INPUT as soon as the START input goes to 1, the outputs are
updated as long as the START is 1. After START goes to 0, the last updated value is stored. The
outputs are reset when the RESET is 1.

12.17.3 Function block GUID-8CA6CD4E-1080-4849-B146-25C19DEDFA66 v1

HOLDMAXMIN
HOLDMINMAX
INPUT MAX
START MIN
RESET

IEC21000053-1-en.vsdx
IEC21000053 V1 EN-US

Figure 266: HOLDMINMAX function block

12.17.4 Signals
GUID-5B941634-5868-427A-80F8-9CA5740D3039 v1

Table 402: HOLDMINMAX Input signals

Name Type Default Description


INPUT REAL 0 Input
START BOOLEAN 0 Start
RESET BOOLEAN 0 Reset

PID-7882-OUTPUTSIGNALS v1

Table 403: HOLDMINMAX Output signals

Name Type Description


MAX REAL Maximum value
MIN REAL Minimum value

Transformer protection RET650 473


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.18 Converter for Integer to Real INT_REAL GUID-B9C23419-0B94-4D72-B88D-4FB7C8C6E388 v1

12.18.1 Identification GUID-B9C23419-0B94-4D72-B88D-4FB7C8C6E388 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Converter for Integer to Real INT_REAL - -

12.18.2 Functionality GUID-B5E646B7-07AC-448E-B75E-773452157369 v1

The converter integer to real (INT_REAL) function can be used to convert integer to real values.

12.18.3 Function block GUID-B4606AFC-9B6D-4452-9DD2-6258CBE7A571 v1

INT_REAL
INT_REAL
INT REAL

IEC21000055-1-en.vsdx
IEC21000055 V1 EN-US

Figure 267: INT_REAL function block

12.18.4 Signals
PID-7883-INPUTSIGNALS v1

Table 404: INT_REAL Input signals

Name Type Default Description


INT INTEGER 0 Integer input

PID-7883-OUTPUTSIGNALS v1

Table 405: INT_REAL Output signals

Name Type Description


REAL REAL Real output

12.19 Definable constant for logic function CONST_INT GUID-67FDADEA-EF3B-4759-8FD2-6BDE6C757C22 v1

12.19.1 Identification GUID-67FDADEA-EF3B-4759-8FD2-6BDE6C757C22 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Definable constant for logic function CONST_INT - -

12.19.2 Functionality GUID-4EF2869F-48F1-4B7B-B99B-FEAAC9431A9B v1

The definable constant for logic function CONST_INT can be used to provide a constant output in an
integer format based on the set value in PST.

474 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.19.3 Function block GUID-BAADB2EE-4C9F-40EA-BE40-F14490E1C3D2 v1

CONST_INT
CONST_INT
OUT

IEC21000056-1-en.vsdx
IEC21000056 V1 EN-US

Figure 268: CONST_INT function block

12.19.4 Signals
PID-7894-OUTPUTSIGNALS v1

Table 406: CONST_INT Output signals

Name Type Description


OUT INTEGER Output

12.19.5 Settings
PID-7894-SETTINGS v1

Table 407: CONST_INT Non group settings (basic)

Name Values (Range) Unit Step Default Description


Constant -999999 - 999999 - 1 0.1 Constant value

12.20 Analog input selector for integer values INTSEL GUID-1B14ACDB-43FD-4B87-B714-B661A5B90C75 v1

12.20.1 Identification GUID-1B14ACDB-43FD-4B87-B714-B661A5B90C75 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Analog input selector for integer values INTSEL - -

12.20.2 Functionality GUID-567B1181-BDE7-497B-8020-FDB798F0FCB5 v1

Analog input selector for integer values (INTSEL) selects one out of eight possible integer inputs.
Each input (INPUTx) has its dedicated select input (SELx). The function provides the output for the
value of the selected input, and its respective select number (INSEL).

If more than one input is selected, the output will be the lowest in order INPUT value. If inputs are not
selected, the select value number shall be 0.

Transformer protection RET650 475


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.20.3 Function block GUID-94FEDCA6-DABD-4D20-A6F3-A95DED7C3777 v1

INTSEL
INTSEL
INPUT1 VALUE
INPUT2 INSEL
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8

IEC21000057-1-en.vsdx
IEC21000057 V1 EN-US

Figure 269: INTSEL function block

12.20.4 Signals
PID-7884-INPUTSIGNALS v1

Table 408: INTSEL Input signals

Name Type Default Description


INPUT1 INTEGER 0 Input 1
INPUT2 INTEGER 0 Input 2
INPUT3 INTEGER 0 Input 3
INPUT4 INTEGER 0 Input 4
INPUT5 INTEGER 0 Input 5
INPUT6 INTEGER 0 Input 6
INPUT7 INTEGER 0 Input 7
INPUT8 INTEGER 0 Input 8
SEL1 BOOLEAN 0 Selector 1
SEL2 BOOLEAN 0 Selector 2
SEL3 BOOLEAN 0 Selector 3
SEL4 BOOLEAN 0 Selector 4
SEL5 BOOLEAN 0 Selector 5
SEL6 BOOLEAN 0 Selector 6
SEL7 BOOLEAN 0 Selector 7
SEL8 BOOLEAN 0 Selector 8

PID-7884-OUTPUTSIGNALS v1

Table 409: INTSEL Output signals

Name Type Description


VALUE INTEGER Value
INSEL INTEGER Selector

476 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.21 Definable limiter LIMITER GUID-8C44B106-7C1F-452F-B8C5-0C7B889C08F2 v1

12.21.1 Identification GUID-8C44B106-7C1F-452F-B8C5-0C7B889C08F2 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Definable limiter LIMITER - -

12.21.2 Functionality GUID-BD0E0AB5-03AD-469E-AE25-D92BD9555FC5 v1

The definable limiter (LIMITER) function can be used to limit the output values within the minimum
and maximum limits set in the PST. If the input is outside the set range then the value OUTLIMIT is
set to 1 to indicate the output value is limited.

12.21.3 Function block GUID-A64AFC93-0840-4828-949A-84180D485B81 v1

LIMITER
LIMITER
IN OUT
OUTLIMIT

IEC21000064-1-en.vsdx
IEC21000064 V1 EN-US

Figure 270: LIMITER function block

12.21.4 Signals
PID-7881-INPUTSIGNALS v1

Table 410: LIMITER Input signals

Name Type Default Description


IN REAL 0 Input value

PID-7881-OUTPUTSIGNALS v1

Table 411: LIMITER Output signals

Name Type Description


OUT REAL Output value
OUTLIMIT BOOLEAN Input is out of limit

12.21.5 Settings
PID-7881-SETTINGS v1

Table 412: LIMITER Non group settings (basic)

Name Values (Range) Unit Step Default Description


MinLim -999999.9 - - 0.1 -1.0 Minimum limit
999999.9
MaxLim -999999.9 - - 0.1 1.0 Maximum limit
999999.9

Transformer protection RET650 477


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.22 Absolute value ABS GUID-D0CC5BFF-4F4F-41A9-9C5F-615496D010B0 v1

12.22.1 Identification GUID-D0CC5BFF-4F4F-41A9-9C5F-615496D010B0 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Absolute value ABS - -

12.22.2 Functionality GUID-A5BF20EF-F04B-4546-B6D0-C1343A56ED72 v1

The absolute value (ABS) function gives the absolute value of the input.

12.22.3 Function block GUID-17CD947C-B18A-429C-BDE8-763065C1CD6F v1

ABS
ABS
IN OUT

IEC21000063-1-en.vsdx
IEC21000063 V1 EN-US

Figure 271: ABS function block

12.22.4 Signals
PID-7885-INPUTSIGNALS v1

Table 413: ABS Input signals

Name Type Default Description


IN REAL 0 Input

PID-7885-OUTPUTSIGNALS v1

Table 414: ABS Output signals

Name Type Description


OUT REAL Output

12.23 Polar to rectangular converter POL_REC GUID-EFB73717-DE3D-4C41-801A-82A8A30821E6 v1

12.23.1 Identification GUID-EFB73717-DE3D-4C41-801A-82A8A30821E6 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Polar to rectangular converter POL_REC - -

12.23.2 Functionality GUID-C2265D29-5169-4E04-B706-15B8A42F1D3E v1

The polar to rectangular converter (POL_REC) function gives the possibility to convert an input
values in polar form to a rectangular form.

478 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.23.3 Function block GUID-BD520B52-92ED-4690-A6E8-0DA821FDB6DB v2

POL_REC
MAG REAL
ANGLE IMAG
IEC22005900 V1 EN-US

Figure 272: POL_REC function block

12.23.4 Signals
PID-7887-INPUTSIGNALS v1

Table 415: POL_REC Input signals

Name Type Default Description


MAG REAL 0 Magnitude
ANGLE REAL 0 Angle in radians

PID-7887-OUTPUTSIGNALS v1

Table 416: POL_REC Output signals

Name Type Description


REAL REAL Real component
IMAG REAL imaginary component

12.24 Radians to degree angle converter RAD_DEG GUID-85E9D856-B4BB-4875-9042-46AA6F398955 v1

12.24.1 Identification GUID-85E9D856-B4BB-4875-9042-46AA6F398955 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Radians to degree angle converter RAD_DEG - -

12.24.2 Functionality GUID-40A32941-6633-4ABE-B123-9CCAAACC093A v1

The radians to degree angle converter (RAD_DEG) function gives the possibility to convert an input
value from radian angles to degree angles.

12.24.3 Function block GUID-5FA30AD4-77B9-4CD1-801C-3406A1892394 v1

RAD_DEG
RAD_DEG
RAD DEG

IEC21000058-1-en.vsdx
IEC21000058 V1 EN-US

Figure 273: RAD_DEG function block

Transformer protection RET650 479


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.24.4 Signals
PID-7886-INPUTSIGNALS v1

Table 417: RAD_DEG Input signals

Name Type Default Description


RAD REAL 0 Angle in radians

PID-7886-OUTPUTSIGNALS v1

Table 418: RAD_DEG Output signals

Name Type Description


DEG REAL Angle in degree

12.24.5 Monitored data


PID-7886-MONITOREDDATA v1

Table 419: RAD_DEG Monitored data

Name Type Values (Range) Unit Description


DEG REAL - deg Angle in degree

12.25 Definable constant for logic function CONST_REAL GUID-98C89599-1535-44A5-9773-D755D9362DA0 v1

12.25.1 Identification GUID-98C89599-1535-44A5-9773-D755D9362DA0 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Definable constant for logic function CONST_REAL - -

12.25.2 Functionality GUID-3B03B1AD-54AF-4FC7-9472-4295D920BA4A v1

The definable constant for logic function (CONST_REAL) can be used to provide a constant output in
an real format based on the set value in PST.

12.25.3 Function block GUID-9E9A4FA6-498F-4D8F-AA47-47D49AE840A8 v1

CONST_REAL
CONST_REAL
OUT

IEC21000059-1-en.vsdx
GUID-6A878306-1E98-469E-9E4F-1B0C46381ADE V1 EN-US

Figure 274: CONST_REAL function block

480 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.25.4 Signals
PID-7888-OUTPUTSIGNALS v1

Table 420: CONST_REAL Output signals

Name Type Description


OUT REAL Output

12.25.5 Signals
PID-7888-SETTINGS v1

Table 421: CONST_REAL Non group settings (basic)

Name Values (Range) Unit Step Default Description


Constant -999999.9 - - 0.1 1.0 Constant value
999999.9

12.26 Analog input selector for real values REALSEL GUID-FF9DD985-AF26-48B1-80F9-8A7C70189A77 v1

12.26.1 Identification GUID-FF9DD985-AF26-48B1-80F9-8A7C70189A77 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Analog input selector for real values REALSEL - -

12.26.2 Functionality GUID-CDE0D96C-B328-4B10-A88C-1648D1E9A521 v1

Analog input selector for real values (REALSEL) function selects one out of eight possible real
inputs. Each input (INPUTx) has its dedicated select input (SELx).

The function provides the output for the value of the selected input and its respective select number
(INSEL). If more than one input is selected, the output will be the lowest in order INPUT value. If
inputs are not selected, the select value number shall be 0.

Transformer protection RET650 481


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.26.3 Function block GUID-C8C6B16A-FDDE-4315-A07F-7D5AB8C969B9 v1

REALSEL
REALSEL
INPUT1 VALUE
INPUT2 INSEL
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
SEL1
SEL2
SEL3
SEL4
SEL5
SEL6
SEL7
SEL8

IEC21000062-1-en.vsdx
IEC21000062 V1 EN-US

Figure 275: REALSEL function block

12.26.4 Signals
PID-7889-INPUTSIGNALS v1

Table 422: REALSEL Input signals

Name Type Default Description


INPUT1 REAL 0 Input 1
INPUT2 REAL 0 Input 2
INPUT3 REAL 0 Input 3
INPUT4 REAL 0 Input 4
INPUT5 REAL 0 Input 5
INPUT6 REAL 0 Input 6
INPUT7 REAL 0 Input 7
INPUT8 REAL 0 Input 8
SEL1 BOOLEAN 0 Selector 1
SEL2 BOOLEAN 0 Selector 2
SEL3 BOOLEAN 0 Selector 3
SEL4 BOOLEAN 0 Selector 4
SEL5 BOOLEAN 0 Selector 5
SEL6 BOOLEAN 0 Selector 6
SEL7 BOOLEAN 0 Selector 7
SEL8 BOOLEAN 0 Selector 8

PID-7889-OUTPUTSIGNALS v1

Table 423: REALSEL Output signals

Name Type Description


VALUE REAL Value
INSEL INTEGER Selector

482 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.27 Store value for integer inputs STOREINT GUID-7DF1E9B4-C065-4905-99AF-EDAAB2AF4F80 v1

12.27.1 Identification GUID-7DF1E9B4-C065-4905-99AF-EDAAB2AF4F80 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Store value for integer inputs STOREINT - -

12.27.2 Functionality GUID-48902D3D-BE8B-4159-B8A2-A596912BAE76 v1

The store value for integer inputs (STOREINT) function can be used to store the integer value upon
the trigger, the minimum trigger duration for it to be stored is 100ms. The stored value is reset to 0
when the RESET input is set to 1.

12.27.3 Function block GUID-314823EB-C9E0-498D-958E-0FA32DE941BF v1

GUID-4AF5186E-2BF2-4D6D-AEAC-D1854A0D04EB V1 EN-US

Figure 276: STOREINT function block

12.27.4 Signals
PID-7890-INPUTSIGNALS v1

Table 424: STOREINT Input signals

Name Type Default Description


INPUT INTEGER 0 Input
TRIGGER BOOLEAN 0 Trigger, if high for more than 100 ms the input value is stored
RESET BOOLEAN 0 Reset stored value

PID-7890-OUTPUTSIGNALS v1

Table 425: STOREINT Output signals

Name Type Description


STOREDVAL INTEGER Stored value

12.28 Store value for real inputs STOREREAL GUID-B44812FC-7808-4AF5-A8C3-140A9365A72A v1

12.28.1 Identification GUID-B44812FC-7808-4AF5-A8C3-140A9365A72A v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Store value for real inputs STOREREAL - -

Transformer protection RET650 483


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 12 1MRK504170-UEN Rev. J
Logic

12.28.2 Functionality GUID-A3DF152A-7BAA-4BBE-BBB8-12F513C92317 v1

The store value for real inputs (STOREREAL) function can be used to store the real value upon the
trigger, the minimum trigger duration for it to be stored is 100ms. The stored value is reset to 0 when
the RESET input is set to 1.

12.28.3 Function block GUID-4AF2FAEA-97E0-40C3-9503-6AED8066E8BB v1

STOREREAL
STOREREAL
IN STOREDVAL
TRIGGER
RESET

IEC21000060-1-en.vsdx

IEC21000060 V1 EN-US

Figure 277: STOREREAL function block

12.28.4 Signals
PID-7891-INPUTSIGNALS v1

Table 426: STOREREAL Input signals

Name Type Default Description


IN REAL 0 Input
TRIGGER BOOLEAN 0 Trigger, if high for more than 100 ms the input value is stored
RESET BOOLEAN 0 Reset stored value

PID-7891-OUTPUTSIGNALS v1

Table 427: STOREREAL Output signals

Name Type Description


STOREDVAL REAL Stored value

12.29 Degree to radians angle converter DEG_RAD GUID-D6D9BCBF-799F-465E-8AB7-480DB0124081 v1

12.29.1 Identification GUID-D6D9BCBF-799F-465E-8AB7-480DB0124081 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Degree to radians angle converter DEG_RAD - -

12.29.2 Functionality GUID-51608C56-7ED9-4FAD-A5BF-5EA4991F83D2 v1

The degree to radians angle converter (DEG_RAD) function gives the possibility to convert an input
value from degree angles to radian angles.

484 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 12
Logic

12.29.3 Function block GUID-933FD746-C986-4774-A4C3-B8C19357DF09 v2

DEG_RAD

DEG_RAD
DEG RAD

IEC21000052-2-en.vsdx
IEC21000052 V2 EN-US

Figure 278: DEG_RAD function block

12.29.4 Signals
PID-7893-INPUTSIGNALS v1

Table 428: DEG_RAD Input signals

Name Type Default Description


DEG REAL 0 Angle in degree

PID-7893-OUTPUTSIGNALS v1

Table 429: DEG_RAD Output signals

Name Type Description


RAD REAL Angle in radians

12.29.5 Monitored data


PID-7893-MONITOREDDATA v1

Table 430: DEG_RAD Monitored data

Name Type Values (Range) Unit Description


RAD REAL - deg Angle in radians

Transformer protection RET650 485


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
486
1MRK504170-UEN Rev. J Section 13
Monitoring

Section 13 Monitoring
13.1 Measurements IP14593-1 v4

13.1.1 Function revision history GUID-8EAA18E2-28AF-498A-889A-24AB7518ADDA v2

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.1 PTP Enhancement
E 2.2.4 -
H 2.2.6 -
J 2.2.6 -

13.1.2 Identification
SEMOD56123-2 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power system measurements CVMMXN -
P, Q, S, I, U, f

SYMBOL-RR V1 EN-US

Phase current measurement CMMXU -

SYMBOL-SS V1 EN-US

Phase-phase voltage measurement VMMXU -

SYMBOL-UU V1 EN-US

Current sequence component CMSQI -


measurement
I1, I2, I0

SYMBOL-VV V1 EN-US

Voltage sequence component VMSQI -


measurement
U1, U2, U0

SYMBOL-TT V1 EN-US

Phase-neutral voltage measurement VNMMXU -

SYMBOL-UU V1 EN-US

Transformer protection RET650 487


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.1.3 Functionality SEMOD54488-4 v13

Measurement functions are used for power system measurement, supervision and reporting to the
local HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850. The
possibility to continuously monitor measured values of active power, reactive power, currents,
voltages, frequency, power factor etc. is vital for efficient production, transmission and distribution of
electrical energy. It provides to the system operator fast and easy overview of the present status of
the power system. Additionally, it can be used during testing and commissioning of protection and
control IEDs in order to verify proper operation and connection of instrument transformers (CTs and
VTs). During normal service by periodic comparison of the measured value from the IED with other
independent meters the proper operation of the IED analog measurement chain can be verified.
Finally, it can be used to verify proper direction orientation for distance or directional overcurrent
protection function.

The available measured values from an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-low limit, low limit, high
limit and high-high limit. A zero clamping reduction is also supported, that is, the measured value
below a settable limit is forced to zero which reduces the impact of noise in the inputs.

Dead-band supervision can be used to report measured signal value to station level when change in
measured value is above set threshold limit or time integral of all changes since the last time value
updating exceeds the threshold limit. Measure value can also be based on periodic reporting.

All measurement functions use fundamental frequency phasors (that is, DFT filtering) for internal
calculations and for reporting of measured values. However, from the following three measurement
functions CMMXU, VMMXU and VNMMXU it is also possible to report the total measured quantity
(that is, true RMS filtering). By selecting the RMS mode, the reported value will be in addition to the
fundamental magnitude also include harmonics.

Main menu /Measurement /Monitoring /Service values /CVMMXN

The measurement function, CVMMXN, provides the following power system quantities:

• P, Q and S: three phase active, reactive and apparent power


• PF: power factor
• U: phase-to-phase voltage amplitude
• I: phase current amplitude
• F: power system frequency

,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical quantities:

• I: phase currents (amplitude and angle) (CMMXU)


• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle) (VMMXU,
VNMMXU)

Fundamental frequency filtered values (DFT) or true RMS values can be selected as a measurement
type in CMMXU, VMMXU and VNMMXU functions.

The CVMMXN function calculates three-phase power quantities by using fundamental frequency
phasors (DFT values) of the measured current and voltage signals. The measured power quantities
are available either, as instantaneously calculated quantities or, averaged values over a period of
time (low pass filtered) depending on the selected settings.

It is possible to calibrate the measuring function above to get better then class 0.5 presentation. This
is accomplished by angle and amplitude compensation at 5, 30 and 100% of rated current and at
100% of rated voltage.

488 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

The power system quantities provided, depends on the actual hardware, (TRM) and the
logic configuration made in PCM600.

The measuring functions CMSQI and VMSQI provide sequence component quantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)


• U: sequence voltages (positive, zero and negative sequence, amplitude and angle).

13.1.4 Function block SEMOD130334-4 v7

The available function blocks of an IED are depending on the actual hardware (TRM) and the logic
configuration made in PCM600.

CVMMXN
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE

IEC10000016-1-en.vsd
IEC10000016 V1 EN-US

Figure 279: CVMMXN function block

CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC05000699 V3 EN-US

Figure 280: CMMXU function block

VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL
IEC05000701 V3 EN-US

Figure 281: VMMXU function block

Transformer protection RET650 489


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703 V3 EN-US

Figure 282: CMSQI function block

VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL
IEC05000704 V3 EN-US

Figure 283: VMSQI function block

VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC09000850 V2 EN-US

Figure 284: VNMMXU function block

13.1.5 Signals
PID-6713-INPUTSIGNALS v3

Table 431: CVMMXN Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6713-OUTPUTSIGNALS v3

Table 432: CVMMXN Output signals

Name Type Description


S REAL Apparent Power magnitude of deadband value
S_RANGE INTEGER Apparent Power range
P_INST REAL Active Power
P REAL Active Power magnitude of deadband value
P_RANGE INTEGER Active Power range
Q_INST REAL Reactive Power
Q REAL Reactive Power magnitude of deadband value
Q_RANGE INTEGER Reactive Power range
PF REAL Power Factor magnitude of deadband value
Table continues on next page

490 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Type Description


PF_RANGE INTEGER Power Factor range
ILAG BOOLEAN Current is lagging voltage
ILEAD BOOLEAN Current is leading voltage
U REAL Calculated voltage magnitude of deadband value
U_RANGE INTEGER Calculated voltage range
I REAL Calculated current magnitude of deadband value
I_RANGE INTEGER Calculated current range
F REAL System frequency magnitude of deadband value
F_RANGE INTEGER System frequency range

PID-7953-INPUTSIGNALS v1

Table 433: CMMXU Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL

PID-7953-OUTPUTSIGNALS v1

Table 434: CMMXU Output signals

Name Type Description


IL1 REAL IL1 Amplitude, magnitude of reported value
IL1RANG INTEGER IL1 Amplitude range
IL1ANGL REAL IL1 Angle, magnitude of reported value
IL2 REAL IL2 Amplitude, magnitude of reported value
IL2RANG INTEGER IL2 Amplitude range
IL2ANGL REAL IL2 Angle, magnitude of reported value
IL3 REAL IL3 Amplitude, magnitude of reported value
IL3RANG INTEGER IL3 Amplitude range
IL3ANGL REAL IL3 Angle, magnitude of reported value

PID-7956-INPUTSIGNALS v1

Table 435: VMMXU Input signals

Name Type Default Description


U3P GROUP - Group signal for voltage input
SIGNAL

PID-7956-OUTPUTSIGNALS v1

Table 436: VMMXU Output signals

Name Type Description


UL12 REAL UL12 Amplitude, magnitude of reported value
UL12RANG INTEGER UL12 Amplitude range
UL12ANGL REAL UL12 Angle, magnitude of reported value
UL23 REAL UL23 Amplitude, magnitude of reported value
UL23RANG INTEGER UL23 Amplitude range
UL23ANGL REAL UL23 Angle, magnitude of reported value
UL31 REAL UL31 Amplitude, magnitude of reported value
UL31RANG INTEGER UL31 Amplitude range
UL31ANGL REAL UL31 Angle, magnitude of reported value

Transformer protection RET650 491


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-6736-INPUTSIGNALS v3

Table 437: CMSQI Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL

PID-6736-OUTPUTSIGNALS v3

Table 438: CMSQI Output signals

Name Type Description


3I0 REAL 3I0 Amplitude, magnitude of reported value
3I0RANG INTEGER 3I0 Amplitude range
3I0ANGL REAL 3I0 Angle, magnitude of reported value
I1 REAL I1 Amplitude, magnitude of reported value
I1RANG INTEGER I1 Amplitude range
I1ANGL REAL I1 Angle, magnitude of reported value
I2 REAL I2 Amplitude, magnitude of reported value
I2RANG INTEGER I2 Amplitude range
I2ANGL REAL I2 Angle, magnitude of reported value

PID-6739-INPUTSIGNALS v2

Table 439: VMSQI Input signals

Name Type Default Description


U3P GROUP - Group signal for voltage input
SIGNAL

PID-6739-OUTPUTSIGNALS v2

Table 440: VMSQI Output signals

Name Type Description


3U0 REAL 3U0 Amplitude, magnitude of reported value
3U0RANG INTEGER 3U0 Amplitude range
3U0ANGL REAL 3U0 Angle, magnitude of reported value
U1 REAL U1 Amplitude, magnitude of reported value
U1RANG INTEGER U1 Amplitude range
U1ANGL REAL U1 Angle, magnitude of reported value
U2 REAL U2 Amplitude, magnitude of reported value
U2RANG INTEGER U2 Amplitude range
U2ANGL REAL U2 Angle, magnitude of reported value

PID-7955-INPUTSIGNALS v1

Table 441: VNMMXU Input signals

Name Type Default Description


U3P GROUP - Group signal for voltage input
SIGNAL

PID-7955-OUTPUTSIGNALS v1

Table 442: VNMMXU Output signals

Name Type Description


UL1 REAL UL1 Amplitude, magnitude of reported value
UL1RANG INTEGER UL1 Amplitude range
UL1ANGL REAL UL1 Angle, magnitude of reported value
Table continues on next page

492 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Type Description


UL2 REAL UL2 Amplitude, magnitude of reported value
UL2RANG INTEGER UL2 Amplitude range
UL2ANGL REAL UL2 Angle, magnitude of reported value
UL3 REAL UL3 Amplitude, magnitude of reported value
UL3RANG INTEGER UL3 Amplitude range
UL3ANGL REAL UL3 Angle, magnitude of reported value

13.1.6 Settings SEMOD130322-4 v7

The available setting parameters of the measurement function (MMXU, MSQI) are depending on the
actual hardware (TRM) and the logic configuration made in PCM600.

These six functions are not handled as a group, so parameter settings are only available in the first
setting group.

The following terms are used in the Unit and Description columns:

• UBase (UB): Base voltage in primary kV. This voltage is used as reference for voltage setting. It
can be suitable to set this parameter to the rated primary voltage supervised object.
• IBase (IB): Base current in primary A. This current is used as reference for current setting. It can
be suitable to set this parameter to the rated primary current of the supervised object.
• SBase (SB): Base setting for power values in MVA.

PID-6713-SETTINGS v3

Table 443: CVMMXN Non group settings (basic)

Name Values (Range) Unit Step Default Description


SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
Table continues on next page

Transformer protection RET650 493


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UMin 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UMax 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
URepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IMin 0.0 - 500.0 %IB 0.1 5.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode L1, L2, L3 - - L1, L2, L3 Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, U and I

Table 444: CVMMXN Non group settings (advanced)

Name Values (Range) Unit Step Default Description


SDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
SZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
Table continues on next page

494 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
PDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
PZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
QDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
QZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
QHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
QHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
QLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
QLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
PFDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
PFZeroDb 0 - 100000 m% 100 500 Magnitude zero point clamping in 0,001%
of range
PFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)
PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)
PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)
PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)
PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
UZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UHiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UHiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
ULowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
ULowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
IDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
IZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
ILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
ILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
Table continues on next page

Transformer protection RET650 495


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
FrDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
FrZeroDb 0 - 100000 m% 10 100 Magnitude zero point clamping in 0,001%
of range
FrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)
FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)
FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UGenZeroDb 1 - 100 %UB 1 5 Zero point clamping in % of UBase
IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IBase
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at 5%
of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir

PID-7953-SETTINGS v1

Table 445: CMMXU Non group settings (basic)

Name Values (Range) Unit Step Default Description


IL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
IL1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
IL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
IL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
IL2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
Table continues on next page

496 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


IL2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
IL3Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL3Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 446: CMMXU Non group settings (advanced)

Name Values (Range) Unit Step Default Description


IL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
IL1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at 5%
of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IL1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
IL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
IL2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IL2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
IL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
IL3HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL3HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
Table continues on next page

Transformer protection RET650 497


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


IL3LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL3LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits

PID-7956-SETTINGS v1

Table 447: VMMXU Non group settings (basic)

Name Values (Range) Unit Step Default Description


UL12DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL12ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL12Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL12Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL12RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
UL12AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL23DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
UL23ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL23Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL23Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL23RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL23AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL31DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
UL31ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL31Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL31Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL31RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL31AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

498 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Table 448: VMMXU Non group settings (advanced)

Name Values (Range) Unit Step Default Description


UL12HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL12HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL12LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL12LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL23HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL23HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL23LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL23LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL31HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL31HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL31LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL31LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits

PID-6736-SETTINGS v3

Table 449: CMSQI Non group settings (basic)

Name Values (Range) Unit Step Default Description


3I0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
3I0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
3I0Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
3I0Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
3I0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
3I0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Operation Off - - Off Operation Mode On / Off
On
I1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
I1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
I1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
I1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
Table continues on next page

Transformer protection RET650 499


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


I1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
I2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
I2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
I2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
I2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
I2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
I2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 450: CMSQI Non group settings (advanced)

Name Values (Range) Unit Step Default Description


3I0HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
3I0HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
3I0LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
3I0LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
I2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase

PID-6739-SETTINGS v2

Table 451: VMSQI Non group settings (basic)

Name Values (Range) Unit Step Default Description


3U0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
3U0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
3U0Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
3U0Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Table continues on next page

500 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


3U0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
3U0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Operation Off - - Off Operation Mode On / Off
On
U1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
U1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
U1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
U1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
U2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
U2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
U2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
U2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 5% of Ur
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 30% of Ur
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 100% of Ur

Table 452: VMSQI Non group settings (advanced)

Name Values (Range) Unit Step Default Description


3U0HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
3U0HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
3U0LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
3U0LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
Table continues on next page

Transformer protection RET650 501


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


U1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

PID-7955-SETTINGS v1

Table 453: VNMMXU Non group settings (basic)

Name Values (Range) Unit Step Default Description


UL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
UL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
UL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
UL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in 0,001%
of range
UL3Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
Table continues on next page

502 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


UL3Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 454: VNMMXU Non group settings (advanced)

Name Values (Range) Unit Step Default Description


UL1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at
100% of Ur
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
UL3HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL3HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL3LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL3LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits

13.1.7 Monitored data


PID-6713-MONITOREDDATA v3

Table 455: CVMMXN Monitored data

Name Type Values (Range) Unit Description


S REAL - MVA Apparent Power magnitude of deadband
value
P REAL - MW Active Power magnitude of deadband
value
Q REAL - MVAr Reactive Power magnitude of deadband
value
PF REAL - - Power Factor magnitude of deadband
value
U REAL - kV Calculated voltage magnitude of
deadband value
I REAL - A Calculated current magnitude of
deadband value
F REAL - Hz System frequency magnitude of
deadband value

Transformer protection RET650 503


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-7953-MONITOREDDATA v1

Table 456: CMMXU Monitored data

Name Type Values (Range) Unit Description


IL1 REAL - A IL1 Amplitude, magnitude of reported
value
IL1ANGL REAL - deg IL1 Angle, magnitude of reported value
IL2 REAL - A IL2 Amplitude, magnitude of reported
value
IL2ANGL REAL - deg IL2 Angle, magnitude of reported value
IL3 REAL - A IL3 Amplitude, magnitude of reported
value
IL3ANGL REAL - deg IL3 Angle, magnitude of reported value

PID-7956-MONITOREDDATA v1

Table 457: VMMXU Monitored data

Name Type Values (Range) Unit Description


UL12 REAL - kV UL12 Amplitude, magnitude of reported
value
UL12ANGL REAL - deg UL12 Angle, magnitude of reported value
UL23 REAL - kV UL23 Amplitude, magnitude of reported
value
UL23ANGL REAL - deg UL23 Angle, magnitude of reported value
UL31 REAL - kV UL31 Amplitude, magnitude of reported
value
UL31ANGL REAL - deg UL31 Angle, magnitude of reported value

PID-6736-MONITOREDDATA v3

Table 458: CMSQI Monitored data

Name Type Values (Range) Unit Description


3I0 REAL - A 3I0 Amplitude, magnitude of reported
value
3I0ANGL REAL - deg 3I0 Angle, magnitude of reported value
I1 REAL - A I1 Amplitude, magnitude of reported value
I1ANGL REAL - deg I1 Angle, magnitude of reported value
I2 REAL - A I2 Amplitude, magnitude of reported value
I2ANGL REAL - deg I2 Angle, magnitude of reported value

PID-6739-MONITOREDDATA v2

Table 459: VMSQI Monitored data

Name Type Values (Range) Unit Description


3U0 REAL - kV 3U0 Amplitude, magnitude of reported
value
3U0ANGL REAL - deg 3U0 Angle, magnitude of reported value
U1 REAL - kV U1 Amplitude, magnitude of reported
value
U1ANGL REAL - deg U1 Angle, magnitude of reported value
U2 REAL - kV U2 Amplitude, magnitude of reported
value
U2ANGL REAL - deg U2 Angle, magnitude of reported value

504 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

PID-7955-MONITOREDDATA v1

Table 460: VNMMXU Monitored data

Name Type Values (Range) Unit Description


UL1 REAL - kV UL1 Amplitude, magnitude of reported
value
UL1ANGL REAL - deg UL1 Angle, magnitude of reported value
UL2 REAL - kV UL2 Amplitude, magnitude of reported
value
UL2ANGL REAL - deg UL2 Angle, magnitude of reported value
UL3 REAL - kV UL3 Amplitude, magnitude of reported
value
UL3ANGL REAL - deg UL3 Angle, magnitude of reported value

13.1.8 Operation principle

13.1.8.1 Measurement supervision SEMOD54417-130 v4

The protection, control, and monitoring IEDs have functionality to measure and further process
information for currents and voltages obtained from the pre-processing blocks. The number of
processed alternate measuring quantities depends on the type of IED and built-in options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report function

Phase angle reference SEMOD54417-303 v5


All phase angles are presented in relation to a defined reference channel. The General setting
parameter PhaseAngleRef defines the reference, see section "Analog inputs".

Zero point clamping SEMOD54417-137 v4


Measured value below zero point clamping limit is forced to zero. This allows the noise in the input
signal to be ignored. The zero point clamping limit is a general setting (XZeroDb where X equals S,
P, Q, PF, U, I, F, IL1-3, UL1-3, UL12-31, I1, I2, 3I0, U1, U2 or 3U0). Observe that this measurement
supervision zero point clamping might be overridden by the zero point clamping used for the
measurement values within CVMMXN.

Continuous monitoring of the measured quantity SEMOD54417-140 v5


Users can continuously monitor the measured quantity available in the function block by means of
four defined operating thresholds, see figure 285. The monitoring has two different modes of
operating:

• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high limit
(XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or Low-
low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 285.

Transformer protection RET650 505


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Y = Magnitude of the Measured Quantity

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

IEC05000657 V4 EN-US

Figure 285: Presentation of operating limits


Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit exceeded,
2: below Low limit and 4: below Low-low limit).

The logical value of the functional output signals changes according to figure 285.

The user can set the hysteresis (XLimHyst), which determines the difference between the operating
and reset value at each operating point, in wide range for each measuring channel separately. The
hysteresis is common for all operating values within one channel.

Actual value of the measured quantity SEMOD54417-150 v5


The actual value of the measured quantity is available locally and remotely. The measurement is
continuous for each measured quantity separately, but the reporting of the value to the higher levels
depends on the selected reporting mode. The following basic reporting modes are available:

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)
• Amplitude Deadband and 5s cyclic
• Amplitude Deadband and 30s cyclic
• Amplitude Deadband and 1min cyclic
• Dynamic Amplitude Deadband
• Dynamic Amplitude Deadband and 5s cyclic
• Dynamic Amplitude Deadband and 30s cyclic
• Dynamic Amplitude Deadband and 60s cyclic

Cyclic reporting SEMOD54417-158 v3


The cyclic reporting of measured value is performed according to chosen setting (XRepTyp). The
measuring channel reports the value independent of amplitude or integral dead-band reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.

506 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5
(*)Set value for t: XDbRepInt
IEC05000500 V3 EN-US

Figure 286: Periodic reporting

Amplitude dead-band supervision SEMOD54417-163 v6


If a measuring value is changed, compared to the last reported value, and the change is larger than
the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the measuring channel reports the
new value to a higher level. This limits the information flow to a minimum necessary. Figure 287
shows an example with the amplitude dead-band supervision. The picture is simplified: the process is
not continuous but the values are evaluated with a time interval of one execution cycle from each
other.

Transformer protection RET650 507


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Value Reported
Y
Value Reported Value Reported
Value Reported
(1st)
Y3 Y
Y
Y2 Y
Y
Y
Y
Y1

IEC99000529 V3 EN-US

Figure 287: Amplitude dead-band supervision reporting


After the new value is reported, the ±ΔY limits for dead-band are automatically set around it. The new
value is reported only if the measured quantity changes more than defined by the ±ΔY set limits.

Integral dead-band reporting SEMOD54417-167 v4


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 288, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated with a
time interval of one execution cycle from each other.

The last value reported, Y1 in figure 288 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is multiplied by
the time increment (discrete integral). The absolute values of these integral values are added until
the pre-set value is exceeded. This occurs with the value Y2 that is reported and set as a new base
for the following measurements (as well as for the values Y3, Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals with small variations
that can last for relatively long periods.

508 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Y A1 >=
A >= pre-set value A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported

t
IEC99000530 V3 EN-US

Figure 288: Reporting with integral dead-band supervision

13.1.8.2 Measurements CVMMXN SEMOD54417-172 v3

Mode of operation SEMOD54417-174 v7


The measurement function must be connected to three-phase current and three-phase voltage input
in the configuration tool (group signals), but it is capable to measure and calculate above mentioned
quantities in nine different ways depending on the available VT inputs connected to the IED. The end
user can freely select by a parameter setting, which one of the nine available measuring modes shall
be used within the function. Available options are summarized in the following table:

Set value Formula used for complex, Formula used for voltage Comment
for three-phase power calculation and current magnitude
parameter calculation
“Mode”
1 L1, L2, L3 Used when three phase-to-
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3 earth voltages are available
EQUATION1385 V1 EN-US (Equation 104) I = ( I L1 + I L 2 + I L 3 ) / 3

EQUATION1386 V1 EN-US (Equation 105)


2 Arone Used when two phase-to-
S = U L1 L 2 × I L*1 - U L 2 L 3 × I L* 3 U = ( U L1 L 2 + U L 2 L 3 ) / 2 phase voltages are available
(Equation 106)
EQUATION1387 V1 EN-US
I = ( I L1 + I L 3 ) / 2
EQUATION1388 V1 EN-US (Equation 107)
3 PosSeq Used when only symmetrical
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq three phase power shall be
measured
(Equation 108)
EQUATION1389 V1 EN-US
I = I PosSeq
EQUATION1390 V1 EN-US (Equation 109)
4 L1L2 Used when only UL1L2 phase-
S = U L1 L 2 × ( I L*1 - I L* 2 ) U = U L1 L 2 to-phase voltage is available
(Equation 110)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN-US

EQUATION1392 V1 EN-US (Equation 111)


Table continues on next page

Transformer protection RET650 509


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Set value Formula used for complex, Formula used for voltage Comment
for three-phase power calculation and current magnitude
parameter calculation
“Mode”
5 L2L3 Used when only UL2L3 phase-
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3 to-phase voltage is available
(Equation 112)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN-US

EQUATION1394 V1 EN-US (Equation 113)


6 L3L1 Used when only UL3L1 phase-
S = U L 3 L1 × ( I L 3 - I L1 )
* *
U = U L 3 L1 to-phase voltage is available
(Equation 114)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN-US

EQUATION1396 V1 EN-US (Equation 115)


7 L1 Used when only UL1 phase-to-
S = 3 × U L1 × I L*1 U = 3 × U L1 earth voltage is available

(Equation 116)
I = I L1
EQUATION1397 V1 EN-US

EQUATION1398 V1 EN-US (Equation 117)


8 L2 Used when only UL2 phase-to-
S = 3 × U L 2 × I L* 2 U = 3 × U L2 earth voltage is available

(Equation 118)
I = IL2
EQUATION1399 V1 EN-US

EQUATION1400 V1 EN-US (Equation 119)


9 L3 Used when only UL3 phase-to-
S = 3 × U L 3 × I L* 3 U = 3 × U L3 earth voltage is available

(Equation 120)
I = I L3
EQUATION1401 V1 EN-US

EQUATION1402 V1 EN-US (Equation 121)


* means complex conjugated value

It shall be noted that only in the first two operating modes that is, 1 & 2 the measurement function
calculates the three-phase power accurately. In other operating modes that is, from 3 to 9 it
calculates the three-phase power under assumption that the power system is fully symmetrical. Once
the complex apparent power is calculated then the P, Q, S, & PF are calculated in accordance with
the following formulas:

P = Re( S )
EQUATION1403 V1 EN-US (Equation 122)

Q = Im( S )
EQUATION1404 V1 EN-US (Equation 123)

S = S = P2 + Q2
EQUATION1405 V1 EN-US (Equation 124)

PF = cosj = P
S
EQUATION1406 V1 EN-US (Equation 125)

510 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Additionally to the power factor value, the two binary output signals from the function are provided
which indicates the angular relationship between the current and voltage phasors. Binary output
signal ILAG is set TRUE when current phasor is lagging behind voltage phasor. Binary output signal
ILEAD is set TRUE when current phasor is leading the voltage phasor.

Each analogue output has a corresponding supervision level output (X_RANGE). The output signal is
an integer in the interval 0-4, see section "Measurement supervision".

Calibration of analog inputs SEMOD54417-293 v5


Measured currents and voltages used in the CVMMXN function can be calibrated to get 0.5 class
measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and 100% of
rated current and voltage. The compensation below 5% and above 100% is constant and linear in
between, see example in figure 289.

IEC05000652 V2 EN-US

Figure 289: Calibration curves


The first current and voltage phase signal, in the group signals will be used as reference. The
amplitude and angle compensation will be used for other related input signals.

Low pass filtering SEMOD54417-233 v4


In order to minimize the influence of the noise signal on the measurement it is possible to introduce
the recursive, low pass filtering of the measured values for P, Q, S, U, I and power factor. This will
make slower measurement response to the step changes in the measured quantity. Filtering is
performed in accordance with the following recursive formula:

Transformer protection RET650 511


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN-US (Equation 126)

where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle
XCalculated is the new calculated value in the present execution cycle
k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is, without any additional delay). When k is set to value bigger than 0,
the filtering is enabled. Appropriate value of k shall be determined separately for every application.
Some typical value for k =0.14.

Zero point clamping SEMOD54417-250 v5


In order to avoid erroneous measurements when either current or voltage signal is not present, it is
possible for the end user to set the amplitudeIGenZeroDb level for current and voltage measurement
UGenZeroDb is forced to zero. When either current or voltage measurement is forced to zero
automatically the measured values for power (P, Q and S) and power factor are forced to zero as
well. Since the measurement supervision functionality, included in CVMMXN, is using these values
the zero clamping will influence the subsequent supervision (observe the possibility to do zero point
clamping within measurement supervision, see section "Measurement supervision").

Compensation facility SEMOD54417-253 v5


In order to compensate for small amplitude and angular errors in the complete measurement chain
(CT error, VT error, IED input transformer errors and so on.) it is possible to perform on site
calibration of the power measurement. This is achieved by setting the complex constant which is
then internally used within the function to multiply the calculated complex apparent power S. This
constant is set as amplitude (setting parameter PowAmpFact, default value 1.000) and angle (setting
parameter PowAngComp, default value 0.0 degrees). Default values for these two parameters are
done in such way that they do not influence internally calculated value (complex constant has default
value 1). In this way calibration, for specific operating range (for example, around rated power) can
be done at site. However, to perform this calibration it is necessary to have an external power meter
with high accuracy class available.

Directionality SEMOD54417-256 v7
If CT earthing parameter is set as described in section "Analog inputs", active and reactive power will
be always measured towards the protected object. This is shown in the following figure 290.

512 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Busbar

IED

P Q

Protected
Object

IEC09000038-1-EN V2 EN-US

Figure 290: Internal IED directionality convention for P & Q measurements


Practically, it means that active and reactive power will have positive values when they flow from the
busbar towards the protected object and they will have negative values when they flow from the
protected object towards the busbar.

In some application, for example, when power is measured on the secondary side of the power
transformer it might be desirable, from the end client point of view, to have actually opposite
directional convention for active and reactive power measurements. This can be easily achieved by
setting parameter PowAngComp to value of 180.0 degrees. With such setting the active and reactive
power will have positive values when they flow from the protected object towards the busbar.

Frequency SEMOD54417-261 v2
Frequency is actually not calculated within measurement block. It is simply obtained from the pre-
processing block and then just given out from the measurement block as an output.

13.1.8.3 Phase current measurement CMMXU SEMOD54417-264 v8

The Phase current measurement (CMMXU) function must be connected to three-phase current input
in the configuration tool to be operable. Currents handled in the function can be calibrated to get
better then 0.5 class measuring accuracy for internal use, on the outputs and IEC 61850. This is
achieved by amplitude and angle compensation at 5, 30 and 100% of rated current. The
compensation below 5% and above 100% is constant and linear in between, see figure 289.

There are two types of measurement available in the function through the MeasurementType setting:

• DFT
• RMS

DFT is used to calculate amplitude and angle values for the fundamental frequency component (that
is, phasor) in the current waveform. This method uses full cycle fourier filtering.

RMS calculates a true RMS value over one cycle of data. Hence, it has both the fundamental
frequency and harmonics frequency component in its measurement.

When RMS measurement mode is selected, all phase angles are forced to zero degree.

Transformer protection RET650 513


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Phase currents (amplitude and angle) are available on the outputs and each amplitude output has a
corresponding supervision level output (ILx_RANG). The supervision output signal is an integer in
the interval 0-4, see section "Measurement supervision".

13.1.8.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU SEMOD54417-268 v7

The voltage function must be connected to three-phase voltage input in the configuration tool to be
operable. Voltages are handled in the same way as currents when it comes to class 0.5 calibrations,
see above.

DFT and RMS measurement types are available in VMMXU and VNMMXU functions also, as
explained in CMMXU function.

The voltages (phase-to-earth or phase-to-phase voltage, amplitude and angle) are available on the
outputs and each amplitude output has a corresponding supervision level output (ULxy_RANG). The
supervision output signal is an integer in the interval 0-4, see section "Measurement supervision".

13.1.8.5 Voltage and current sequence measurements VMSQI, CMSQI SEMOD54417-299 v6

The measurement functions must be connected to three-phase current (CMSQI) or voltage (VMSQI)
input in the configuration tool to be operable. No outputs, other than X_RANG, are calculated within
the measuring blocks and it is not possible to calibrate the signals. Input signals are obtained from
the pre-processing block and transferred to corresponding output.

Positive, negative and three times zero sequence quantities are available on the outputs (voltage and
current, amplitude and angle). Each amplitude output has a corresponding supervision level output
(X_RANGE). The output signal is an integer in the interval 0-4, see section "Measurement
supervision".

13.1.9 Technical data


M12386-1 v17

Table 461: Power system measurement CVMMXN technical data

Function Range or value Accuracy


Frequency (0.8-1.2) x fr ±5.0 mHz for U at 0.2 × Ur ≤ U < 0.5 × Ur
±3.0 mHz for U at 0.5 × Ur ≤ U < 1.0 × Ur
±2.0 mHz for U at U ≥ Ur
Voltage (10 to 300) V ±0.3% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Current (0.1-4.0) x Ir ±0.8% of I at 0.1 x Ir < I < 0.2 x Ir
± 0.5% of I at 0.2 x Ir < I < 0.5 x Ir
±0.2% of I at 0.5 x Ir < I < 4.0 x Ir
Active power, P (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr
(100 to 220) V ±0.2% of P
(0.5-2.0) x Ir
cos φ > 0.7
Reactive power, Q (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr
(100 to 220) V ±0.2% of Q
(0.5-2.0) x Ir
cos φ < 0.7
Table continues on next page

514 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Function Range or value Accuracy


Apparent power, S (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S >0.5 x Sr
(100 to 220) V ±0.2% of S
(0.5-2.0) x Ir
Power factor, cos (φ) (10 to 300) V <0.02
(0.1-4.0) x Ir
(100 to 220) V <0.01
(0.5-2.0) x Ir

GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6

Table 462: CMMXU technical data

Function Range or value Accuracy


Current at symmetrical load (0.1-4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
±0.3% of I at I > 0.5 × Ir
Phase angle at symmetrical load (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5

Table 463: VMMXU technical data

Function Range or value Accuracy


Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5

Table 464: CMSQI technical data

Function Range or value Accuracy


Current positive sequence, I1 (0.1–4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
Three phase settings ±0.3% of I at I > 0.5 × Ir
Current zero sequence, 3I0 Three (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
phase settings ±0.3% of I at I > 0.5 × Ir
Current negative sequence, I2 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
Three phase settings ±0.3% of I at I > 0.5 × Ir
Phase angle (0.1–4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6

Table 465: VMSQI technical data

Function Range or value Accuracy


Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

Transformer protection RET650 515


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6

Table 466: VNMMXU technical data

Function Range or value Accuracy


Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

13.2 Insulation gas monitoring function SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v4

13.2.1 Function revision history GUID-7F31EFA5-F8D8-4D8D-85DA-3418F70ABE94 v3

Document Product History


revision revision
A 2.2.1 -
B 2.2.2 -
C 2.2.1 -
D 2.2.4 Binary quality inputs SENLVLQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there
is no sensor, the quality of the binary input will be low. If sensor quality is low, then lockout
and alarm signals will get reset.
E 2.2.5 -
H 2.2.6 -
J 2.2.6 -

13.2.2 Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation gas monitoring function SSIMG - 63

13.2.3 Functionality GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v8

Insulation supervision for gas medium (SSIMG ) is used for monitoring the circuit breaker condition.
Binary information based on the gas pressure in the circuit breaker can be used as input to the
function. In addition, the function can be used with an analog value of gas pressure and temperature
of the insulation medium and binary inputs. The SSIMG function generates alarms based on the
received information.

516 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.2.4 Function block


GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v4

SSIMG
BLOCK LOCKOU T
BLKALM PRESLO
SENPRES TEMPLO
SENTEMP ALARM
SENPRESQ PRESALM
SENTEMP Q TEMPALM
SENPRESALM PRESSURE
SENPRESLO TEMP
SETP LO
SETTLO
RESETLO

IEC09000129-3-en.vsdx
IEC09000129 V3 EN-US

Figure 291: SSIMG function block

13.2.5 Signals
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v3

PID-7402-INPUTSIGNALS v2

Table 467: SSIMG Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENPRES REAL 0.0 Pressure input from transformer
SENTEMP REAL 0.0 Temperature of the insulation medium from transformer
SENPRESQ BOOLEAN 0 Quality status of pressure
SENTEMPQ BOOLEAN 0 Quality status of temperature sensor signals
SENPRESALM BOOLEAN 0 Pressure alarm signal
SENPRESLO BOOLEAN 0 Pressure lockout signal
SETPLO BOOLEAN 0 Set pressure lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset pressure and temperature lockout

PID-7402-OUTPUTSIGNALS v2

Table 468: SSIMG Output signals

Name Type Description


LOCKOUT BOOLEAN Pressure below lockout level or temperature above lockout level
PRESLO BOOLEAN Pressure below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Pressure below alarm level or temperature above alarm level
PRESALM BOOLEAN Pressure below alarm level
TEMPALM BOOLEAN Temperature above alarm level
PRESSURE REAL Pressure service value
TEMP REAL Temperature of the insulation medium

Transformer protection RET650 517


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.2.6 Settings
PID-7402-SETTINGS v2

Table 469: SSIMG Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
PresAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for pressure
PresLOLimit 1.00 - 100.00 - 0.01 3.00 Pressure lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the medium
tPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarm
tPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetPresAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarm
tResetPresLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockout

13.2.7 Monitored data


PID-7402-MONITOREDDATA v2

Table 470: SSIMG Monitored data

Name Type Values (Range) Unit Description


PRESSURE REAL - - Pressure service value
TEMP REAL - deg Temperature of the insulation medium

13.2.8 Operation principle GUID-359458EA-FFAA-4A44-A8E8-9469CA069C80 v9

Gas medium supervision SSIMG is used to monitor the gas pressure in the circuit breaker and
temperature of the medium. The gas pressure is monitored to detect low pressure. Binary inputs of
gas density SENPRESALM, SENPRESLO, and gas pressure signal SENPRES are considered to
initiate the gas pressure alarm PRESALM and the gas pressure lockout PRESLO.

If any gas pressure sensor measurement is available and connected to the function input, then gas
pressure sensor quality input also considered for pressure alarm and lockout detections.

Gas pressure alarm PRESALM is activated when any of the following condition occurs,

• If binary signal from CB SENPRESALM is high.


• If gas pressure SENPRES goes below the setting PresAlmLimit and quality input SENPRESQ is
high.

Gas pressure lockout PRESLO is activated when any of the following condition occurs,

• If binary signal from CB SENPRESLO is high or binary input SETPLO is high.


• If gas pressure SENPRES goes below the setting PresLOLimit and quality input SENPRESQ is
high.

Thus, the function can be used without any sensor inputs and allowing alarm and lockout outputs
based on binary inputs.

518 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

To avoid false alarms due to a sudden change in gas pressure, two time delays tPressureAlarm or
tPressureLO are included. If the pressure goes below the settings for more than these time delays,
the corresponding alarm PRESALM or lockout PRESLO will be initiated. The SETPLO binary input is
used for setting the gas pressure lockout PRESLO. The PRESLO output retains the last value until it
is reset by using the binary input RESETLO. The binary input BLKALM can be used to block the
alarms, and the BLOCK input can be used to block both alarm and the lockout indications.

Temperature of the medium is available from the input signal of temperature SENTEMP. The signal is
monitored to detect high temperature. If any gas temperature sensor measurement is available and
connected to the function input, then gas temperature sensor quality input also considered for
temperature alarm and lockout detections.

Temperature alarm TEMPALM is activated if temperature SENTEMP goes above the setting
TempAlarmLimit and quality input SENTEMPQ is high.

Temperature lockout TEMPLO is activated when any of the following condition occurs,

• If binary input SETTLO is high.


• If temperature SENTEMP goes above the setting TempLOLimit and quality input SENTEMPQ is
high.

To avoid false alarms due to a sudden change in temperature, two time delays tTempAlarm or
tTempLockOut are included. If the temperature goes below the settings for more than these time
delays, the corresponding alarm TEMPALM or lockout TEMPLO will be initiated. The SETTLO binary
input is used for setting the gas pressure lockout TEMPLO. The TEMPLO output retains the last
value until it is reset by using the binary input RESETLO. The binary input BLKALM can be used to
block the alarms, and the BLOCK input can be used to block both alarm and the lockout indications.

The output ALARM goes high if the pressure alarm condition or the temperature alarm condition
exists. The output ALARM can be blocked by activating BLOCK or BLKALM inputs.

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists and it gets reset by activating binary input RESETLO. The output LOCKOUT can be
blocked by activating BLOCK input.

13.2.9 Technical data


GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v10

Table 471: SSIMG Technical data

Function Range or value Accuracy


Pressure alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever
is greater
Pressure lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever
is greater
Temperature alarm level -40.00-200.00 ±2.5% of set value or 1 whichever is
greater
Temperature lockout level -40.00-200.00 ±2.5% of set value or 1 whichever is
greater
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater
Table continues on next page

Transformer protection RET650 519


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Function Range or value Accuracy


Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater

13.3 Insulation liquid monitoring function SSIML GUID-37669E94-4830-4C96-8A67-09600F847F23 v4

13.3.1 Function revision history GUID-751C8C78-891D-423B-825A-0774D0B6C658 v3

Document Product History


revision revision
A 2.2.1 -
B 2.2.2 -
C 2.2.1 -
D 2.2.4 Binary quality inputs SENLVLQ and SENTEMPQ have been added for pressure and
temperature sensor signals in order to control alarm and lockout signals. Whenever there
is no sensor, the quality of the binary input will be low. If sensor quality is low, then lockout
and alarm signals will get reset.
E 2.2.5 -
H 2.2.6 -

13.3.2 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation liquid monitoring function SSIML - 71

13.3.3 Functionality GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v8

Insulation supervision for liquid medium (SSIML) is used for monitoring the oil insulated device
condition. For example, transformers, shunt reactors, and so on. Binary information based on the
liquid level in the circuit breaker can be used as input to the function. In addition, the function can be
used with an analog value of liquid level and temperature of the insulation medium and binary inputs.
The function generates alarms based on the received information.

520 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.3.4 Function block GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3

SSIML
BLOCK LOCKOU T
BLKALM LVLLO
SENLEVEL TEMPLO
SENTEMP ALARM
SENLVLQ LVLALM
SENTEMP Q TEMPALM
SENLVLALM LEVEL
SENLVLLO TEMP
SETLLO
SETTLO
RESETLO

IEC09000128-3-en.vsdx
IEC09000128 V3 EN-US

Figure 292: SSIML function block

13.3.5 Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v3

PID-7403-INPUTSIGNALS v2

Table 472: SSIML Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENLEVEL REAL 0.0 Level input from transformer
SENTEMP REAL 0.0 Temperature of the insulation medium from transformer
SENLVLQ BOOLEAN 0 Quality status of pressure
SENTEMPQ BOOLEAN 0 Quality status of temperature sensor signals
SENLVLALM BOOLEAN 0 Level alarm signal
SENLVLLO BOOLEAN 0 Level lockout signal
SETLLO BOOLEAN 0 Set level lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset level and temperature lockout

PID-7403-OUTPUTSIGNALS v2

Table 473: SSIML Output signals

Name Type Description


LOCKOUT BOOLEAN Level below lockout level or temperature above lockout level
LVLLO BOOLEAN Level below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Level below alarm level or temperature above alarm level
LVLALM BOOLEAN Level below alarm level
TEMPALM BOOLEAN Temperature above alarm level
LEVEL REAL Level service value
TEMP REAL Temperature of the insulation medium

Transformer protection RET650 521


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.3.6 Settings
PID-7403-SETTINGS v2

Table 474: SSIML Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
LevelAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for level
LevelLOLimit 1.00 - 100.00 - 0.01 3.00 Level lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the medium
tLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarm
tLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarm
tResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockout

13.3.7 Monitored data


PID-7403-MONITOREDDATA v2

Table 475: SSIML Monitored data

Name Type Values (Range) Unit Description


LEVEL REAL - - Level service value
TEMP REAL - deg Temperature of the insulation medium

13.3.8 Operation principle GUID-F4340B59-90D0-4EA7-9FD8-F21D425C884A v9

Liquid medium supervision SSIML is used to monitor the oil level and temperature of oil in the oil
insulated devices. The liquid level is monitored to detect low liquid level. Binary inputs of oil level
SENLVLALM, SENLVLLO, and gas pressure signal SENLEVEL are considered to initiate the liquid
level alarm LVLALM and the liquid level alarm lockout LVLLO.

If any liquid level sensor measurement is available and connected to the function input, then liquid
level sensor quality input also considered for level alarm and lockout detections.

Liquid level alarm LVLALM is activated when any of the following condition occurs,

• If binary signal from CB SENLVLALM is high.


• If liquid level SENLEVEL goes below the setting LevelAlmLimit and quality input SENLEVELQ is
high.

Liquid level lockout LVLLO is activated when any of the following condition occurs,

• If binary signal from CB SENLVLLO is high or SETLLO input is high.


• If liquid level SENLEVEL goes below the setting LevelLOLimit and quality input SENLEVELQ is
high.

Thus, the function can be used without any sensor inputs and allowing alarm and lockout outputs
based on binary inputs.

522 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

To avoid false alarm due to the sudden change in the oil level, two time delays tLevelAlarm or
tLevelLockOut are included. If the pressure goes below the settings for more than these time delays,
the corresponding alarm LVLALM or lockout LVLLO will be initiated. The SETLLO binary input is
used for setting the liquid level lockout LVLLO. The LVLLO output retains the last value until it is reset
by using the binary input RESETLO. The binary input BLKALM can be used to block the alarms, and
the BLOCK input can be used to block both alarm and the lockout indications.

Temperature of the medium is available from the input signal of temperature. The signal is monitored
to detect high temperature. If any oil temperature sensor measurement is available and connected to
the function input, then oil temperature sensor quality input also considered for temperature alarm
and lockout detections.

Temperature alarm TEMPALM is activated if temperature SENTEMP goes above the setting
TempAlarmLimit and quality input SENTEMPQ is high.

Temperature lockout TEMPLO is activated when any of the following condition occurs,

• If binary input SETTLO is high.


• If temperature SENTEMP goes above the setting TempLOLimit and quality input SENTEMPQ is
high.

To avoid false alarm due to the sudden change in the temperature, two time delays tTempAlarm or
tTempLockOut are included. If the temperature goes below the settings for more than these time
delays, the corresponding alarm TEMPALM or lockout TEMPLO will be initiated. The SETTLO binary
input is used for setting the gas pressure lockout TEMPLO. The TEMPLO output retains the last
value until it is reset by using the binary input RESETLO. The binary input BLKALM can be used to
block the alarms, and the BLOCK input can be used to block both alarm and the lockout indications.

The output ALARM goes high if the pressure alarm condition or the temperature alarm condition
exists. The output ALARM can be blocked by activating BLOCK or BLKALM inputs.

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists and it gets reset by activating binary input RESETLO. The output LOCKOUT can be
blocked by activating BLOCK input.

13.3.9 Technical data


GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9

Table 476: SSIML Technical data

Function Range or value Accuracy


Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever
is greater
Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever
is greater
Temperature alarm level -40.00-200.00 ±2.5% of set value or 1 whichever is
greater
Temperature lockout level -40.00-200.00 ±2.5% of set value or 1 whichever is
greater
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Table continues on next page

Transformer protection RET650 523


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Function Range or value Accuracy


Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater

13.4 Breaker monitoring SSCBR

13.4.1 Function revision history GUID-154C2266-3A9B-4007-A759-17105FC2BDD3 v1

Document Product History


revision revision
H 2.2.6 -
J 2.2.6 Binary inputs EXEOPNCSWI, EXEOPNXCBR and binary output COLOPN have been
added to indicate that the trip coil is operated through an open command

13.4.2 Identification GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker monitoring SSCBR - -

13.4.3 Functionality GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v14

The circuit breaker condition monitoring function (SSCBR) is used to monitor different parameters of
the breaker condition. The breaker requires maintenance when the number of operations reaches a
predefined value. For a proper functioning of the circuit breaker, it is essential to monitor the circuit
breaker operation, spring charge indication or breaker wear, travel time, number of operation cycles
and estimate the accumulated energy during arcing periods. Each SCCBR function instance is made
to be used with a 1-pole, 1-phase breaker.

524 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.4.4 Function block GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v12

SSCBR
I3P* OPNPOS
BLOCK CLSPOS
BLKALM INVDPOS
TRIND COLOPN
POSOPN OPTMOPNALM
POSCLS OPTMCLSALM
PRESALM OPCNTWRN
PRESLO OPCNTALM
SPC RMNLIFEALM
SPD MONALM
RSRMNLIFE ACCMABRWRN
RSOPTM ACCMABRALM
RSACCMABR SPCALM
RSSPCTM GPRESALM
EXEOPNXCBR GPRESLO
EXEOPNCSWI

IEC13000231 V4 EN-US

Figure 293: SSCBR function block

13.4.5 Signals
PID-8315-INPUTSIGNALS v1

Table 477: SSCBR Input signals

Name Type Default Description


I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of the function
BLKALM BOOLEAN 0 Block all the alarms
TRIND BOOLEAN 0 Trip command from trip circuit
POSOPN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLS BOOLEAN 0 Signal for close position of apparatus from I/O
PRESALM BOOLEAN 0 Pressure alarm indication from CB
PRESLO BOOLEAN 0 Pressure lockout indication from CB
SPC BOOLEAN 0 CB spring charging started indication signal
SPD BOOLEAN 0 CB spring charged indication signal
RSRMNLIFE BOOLEAN 0 Reset of CB remaining life and operation counter
RSOPTM BOOLEAN 0 Reset of CB closing and opening operation time
RSACCMABR BOOLEAN 0 Reset of accumulated contact abrasion
RSSPCTM BOOLEAN 0 Reset of CB spring charging time
EXEOPNCSWI BOOLEAN 0 Open command from CSWI
EXEOPNXCBR BOOLEAN 0 Open command from XCBR

Transformer protection RET650 525


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-8315-OUTPUTSIGNALS v1

Table 478: SSCBR Output signals

Name Type Description


OPNPOS BOOLEAN CB is in open position
CLSPOS BOOLEAN CB is in closed position
INVDPOS BOOLEAN CB is in Invalid Position
OPTMOPNALM BOOLEAN Operation time of main contact exceeded set value
'OpTmOpnAlmLev' during open operation
OPTMCLSALM BOOLEAN Operation time of main contact exceeded set value
'OpTmClsAlmLev' during close operation
OPCNTWRN BOOLEAN Number of CB operations exceeded warning level
OPCNTALM BOOLEAN Number of CB operations exceeded alarm level
RMNLIFEALM BOOLEAN Remaining life of CB reduced to Life alarm level
MONALM BOOLEAN Alarm issued when CB not operated for long time
ACCMABRWRN BOOLEAN The accumulated contact abrasion exceeded warning level
ACCMABRALM BOOLEAN The accumulated contact abrasion exceeded alarm level
SPCALM BOOLEAN Spring charging time exceeded the set value
GPRESALM BOOLEAN Pressure below alarm level
GPRESLO BOOLEAN Pressure below lockout level
COLOPN BOOLEAN Opening coil has been operated through the open command

13.4.6 Settings
PID-8315-SETTINGS v1

Table 479: SSCBR Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
RatedOpCur 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the breaker
OpNumRatedCur 1 - 99999 - 1 10000 Number of operations possible at rated
current
RatedFltCur 500.00 - 99999.99 A 0.01 5000.00 Rated fault current of the breaker
OpNumFltCur 1 - 10000 - 1 1000 Number of operations possible at rated
fault current
OpTmOpnAlmLev 0.000 - 0.200 s 0.001 0.040 Alarm level for open operation time
OpTmClsAlmLev 0.000 - 0.200 s 0.001 0.040 Alarm level for close operation time
OpNumWrnLev 0 - 9999 - 1 200 Warning level for number of operations
OpNumAlmLev 0 - 9999 - 1 300 Alarm level for number of operations
AccmAbrClcMod Aux Contact - - Trip Signal Accumulated contact abrasion calculation
Trip Signal mode
CurExponent 0.50 - 3.00 - 0.01 2.00 Current exponent value used for
accumulated contact abrasion calculation
AccmAbrStopCur 5.00 - 100.00 %IB 0.01 10.00 RMS current level below which
accumulated contact abrasion stops
AccmAbrWrnLev 0.00 - 20000.00 - 0.01 2500.00 Accumulated contact abrasion threshold
for warning state
AccmAbrAlmLev 0.00 - 20000.00 - 0.01 2500.00 Accumulated contact abrasion threshold
for alarm state
SpcTmAlmLev 0.00 - 60.00 s 0.01 1.00 Alarm level for spring charging time
Table continues on next page

526 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


phSel Phase L1 - - Phase L1 Phase selection
Phase L2
Phase L3
InitRmnLife 1 - 99999 - 1 10000 Initial value for remaining life estimates
InaDayAlmLev 0 - 9999 Day 1 2000 Alarm level for inactive days counter

Table 480: SSCBR Non group settings (advanced)

Name Values (Range) Unit Step Default Description


OpTmOpnCor -0.100 - 0.100 s 0.001 0.010 Correction for open operation time
OpTmClsCor -0.100 - 0.100 s 0.001 0.010 Correction for close operation time
DirCff -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life
calculation
RmnLifeAlmLev 1 - 99999 - 1 5000 Alarm level for CB remaining life
OpnTmTrvlCor -0.010 - 0.010 s 0.001 0.005 Correction for time difference in auxiliary
and main contacts open time
OpTmDelay 0.000 - 0.200 s 0.001 0.020 Time delay between change of status of
trip output and start of main contact
separation
tGasPresAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarm
tGasPresLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockout
InitCntVal 0 - 9999 - 1 0 Initial value for number of operations
InitAccmAbr 0.00 - 9999.99 - 0.01 0.00 Initial value for accumulated contact
abrasion
InitInaDay 0 - 9999 Day 1 0 Initial value for inactive days
InaDayAlmTmh 0 - 23 Hour 1 0 Alarm time for inactive days counter in
hours

13.4.7 Monitored data


PID-8315-MONITOREDDATA v1

Table 481: SSCBR Monitored data

Name Type Values (Range) Unit Description


OPTMOPN REAL - ms Operation time of main contact during
open operation
OPTMCLS REAL - ms Operation time of main contact during
close operation
OPNUM INTEGER - - Number of CB operation cycle
RMNLIFE INTEGER - - CB Remaining life of respective phase
INADAYS INTEGER - - The number of days CB has been inactive
ACCMABR REAL - - Accumulated contact abrasion integrated
over CB open travel time
SPCTM REAL - s The charging time of the CB spring

13.4.8 Operation principle GUID-3902D69C-1858-40DD-AD63-C33C381697BA v14

The breaker monitoring function includes metering and monitoring subfunctions. The subfunctions
can be enabled and disabled with the Operation setting. The corresponding parameter values are On
and Off.

The operation of the subfunctions is described by the module diagram as shown in figure 294. All the
modules in the diagram are explained in subsequent sections.

Transformer protection RET650 527


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

IRMSPh OPTMOPN
POSCLS OPTMCLS
POSOPN CB Contact Operation OPTMOPNALM
BLOCK Time OPTMCLSALM
BLKALM OPTMOPNDIFALM
RSOPTM OPTMCLSDIFALM

OPNPOS
CB Status CLSPOS
INVDPOS

RMNLIFEALM
Remaining Life of CB
RMNLIFE
RSRMNLIFE

ACCMABRWRN
Accumulated
contact abrasion ACCMABRALM
IL
TRIND ACCMABR
RSACCMABR

CB Operation OPCNTWRN
Cycles OPNUM

CB Operation MONALM
Monitoring INADAYS

SPCALM
SPC CB Spring Charge SPCTM
SPD Monitoring
RSSPCTM

CB Gas Pressure GPRESALM


PRESALM Indication GPRESLO
PRESLO

EXEOPNXCBR Coil Open


Indication COLOPN
EXEOPNCSWI

GUID-BC6063F6-8206-4E20-BE3A-7859C9A24836 V1 EN-US

Figure 294: Functional module diagram of breaker monitoring

528 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.4.8.1 Circuit breaker contact operation time GUID-3AF0EE8D-AA8E-4F83-9916-61B5D0D6B05B v14

The circuit breaker contact operation time sub function calculates the breaker contact operation time
for opening and closing operations. The operation of the breaker contact operation time
measurement is described in Figure 295.

POSCLS OPTMOPN
Contact
POSOPN operation time OPTMCLS
calculation
RSOPTM OPTMOPNALM

Alarm limit OPTMCLSALM


BLOCK check OPTMOPNDIFALM
BLKALM
OPTMCLSDIFALM

GUID-B421E15B-2ED1-400D-92A8-E0E03C4F366B V1 EN-US

Figure 295: Functional module diagram for circuit breaker contact operation time

Contact operation time calculation


The contact operation time of the breaker is calculated from the time between the state of change of
auxiliary contacts. The opening operation time is measured between the opening of the POSCLS and
closing of the POSOPN auxiliary contacts. Similarly, the closing operation time is measured between
the opening of the POSOPN and closing of the POSCLS auxiliary contacts. A compensation factor has
been added to consider the time difference between auxiliary contact operation and the actual
physical opening of the breaker main contact.

Transformer protection RET650 529


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Main Contact
1

0
POSCLS
1

POSOPN
1

t1 tOpen t2 t3 tClose t4

Open operation time = tOpen + t1 + t2 Close operation time = tClose + t3 + t4


OpTmOpnCor= t1 + t2 OpTmClsCor = t3 + t4

GUID-352EA7A6-004C-4D3A-AF87-52210EC81707 V1 EN-US

Main Contact
1

0
POSCLS
1

POSOPN
1

t1 tOpen t2 t3 tClose t4

Open operation time = tOpen + t1 + t2 Close operation time = tClose + t3 + t4


OpTmOpnCor= t1 + t2 OpTmClsCor = t3 + t4

GUID-352EA7A6-004C-4D3A-AF87-52210EC81707 V1 EN-US

Figure 296: Operation time calculation


There is a time difference t1 between the start of the main contact opening and the opening of the
POSCLS auxiliary contact. Similarly, there is a time difference t2 between the time when the POSOPN
auxiliary contact opens and the main contact is completely open. Therefore, a correction factor needs
to be added to get the actual opening time. This factor is added with the OpTmOpnCor (t1+t2)
setting. The closing time is calculated by adding the value set with the OpTmClsCor (t3+t4) setting to
the measured closing time.

The last measured opening operation time (OPTMOPN) and the closing operation time (OPTMCLS) are
given as service values.

The values can be reset using the Clear menu on the LHMI or by activation of the input RSRMNLIFE.

Alarm limit check


When the measured opening operation time is longer than the value set in the OpTmOpnAlmLev
setting, the OPTMOPNALM output is activated. Similarly, when the measured closing operation time is
longer than the value set in the OpTmClsAlmLev setting, the OPTMCLSALM output is activated.

It is also possible to block the OPTMCLSALM and OPTMOPNALM alarm signals by activating the
BLKALM input.

530 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.4.8.2 Circuit breaker status GUID-390A1250-B258-4023-9A7D-0D7E19E13A6C v13

The circuit breaker status subfunction monitors the position of the circuit breaker, that is, whether the
breaker is in the open, closed or error position. The operation is described in figure 297.

IRMSPH Phase current


check

OPNPOS
Contact position
POSCLS CLSPOS
indicator
POSOPN INVDPOS

GUID-E78F2E25-2D81-40AC-B044-058D03488A4E V1 EN-US

Figure 297: Functional module diagram for monitoring circuit breaker status

Phase current check


The module compares the phase current IRMSPh to the AccmAbrStopCur setting. If the current in
the selected phase exceeds the set level, it is reported to the contact position indicator module as
closed circuit breaker.

Contact position indicator


The circuit breaker status is open when the auxiliary input contact POSCLS is low, the POSOPN input
is high and the phase current is less than the setting AccmAbrStopCur value. The circuit breaker is
closed when the POSOPN input is low and the POSCLS input is high. The breaker is in the error state if
both auxiliary contacts have the same value or if the auxiliary input contact POSCLS is low and the
POSOPN input is high but the current is above the setting AccmAbrStopCur.

The status of the breaker is indicated with the binary outputs OPNPOS, CLSPOS and INVDPOS for
open, closed and error position respectively.

13.4.8.3 Remaining life of circuit breaker GUID-C347406A-2B6F-42BD-B70B-51489AB51EAE v14

The Remaining life of circuit breaker subfunction is used to give an indication on the wear and tear of
the circuit breaker. Every time the breaker operates, the life of the circuit breaker reduces due to
wear. The breaker wear depends on the interrupted current. The remaining life of the breaker is
estimated from the circuit breaker trip curve provided by the manufacturer. The remaining life is
decreased by at least one when the circuit breaker is opened. The operation of the remaining life of
circuit breaker subfunction is described in figure 298.

IRMSPH
CB remaining RMNLIFE
POSCLS life estimation

RSRMNLIFE

Alarm limit
BLOCK RMNLIFEALM
Check
BLKALM

GUID-BBBAC955-DE50-4FC8-90DB-A5D180251BF2 V1 EN-US

Figure 298: Functional module diagram for estimating the life of the circuit breaker

Transformer protection RET650 531


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Circuit breaker remaining life estimation


If the interrupted current is less than the rated operating current set using the RatedOpCur setting,
the remaining operations of the breaker are reduced by one operation. If the interrupted current is
more than the rated fault current set using the RatedFltCur setting, the remaining operations of the
circuit breaker are reduced by the set OpNumRatedCur divided by the set OpNumFltCur value. If the
tripping current is between these two values, the remaining life of the circuit breaker is calculated
based on the maintenance curve equation given by the manufacturer. The OpNumRatedCur
parameter sets the number of operations the breaker can perform at the rated current. The
OpNumFltCur parameter sets the number of operations the breaker can perform at the rated fault
current.

Alarm limit check


When the remaining life of a circuit breaker phase drops below the RmnLifeAlmLev setting, the life
alarm RMNLIFEALM is activated.

It is possible to deactivate the RMNLIFEALM alarm signal by activating the binary input BLKALM.

The old circuit breaker operation counter value can be used by adding the value to the InitRmnLife
parameter. The value can be reset using the Clear menu from LHMI or by activating the input
RSRMNLIFE.

13.4.8.4 Accumulated contact abrasion GUID-0163FF0F-6E18-4CDC-87AA-578304E0872E v13

The Accumulated contact abrasion subfunction calculates the accumulated contact abrasion (Iyt)
based on current samples, where the setting CurExponent (y) ranges from 0.5 to 3.0. The operation
is described in figure 299.

The TRCMD output is enabled when either of the trip indications from the trip coil circuit TRIND is high
or the breaker status isOPNPOS.

IL

IRMSPH Accumulated
ACCMABR
POSCLS contact
abrasion
TRIND calculation

RSACCMABR
ACCMABRWRN
Alarm limit
BLOCK
Check ACCMABRALM
BLKALM

GUID-F430402D-11DC-4381-AF58-8322329A8E30 V1 EN-US

Figure 299: Functional module diagram for estimating accumulated contact abrasion

Accumulated contact abrasion calculation


Accumulated contact abrasion can be calculated either with TRIND or POSCLS by selecting the
AccmAbrClcMod parameter value accordingly.

The calculation is initiated with the POSCLS or TRIND input events. It ends when the RMS current is
lower than the AccmAbrStopCur setting.

The OpnTmTrvlCor setting is used to determine the accumulated contact abrasion in relation to the
time the main contact opens. If the setting is positive, the calculation of contact abrasion starts after
the auxiliary contact has opened and the delay equal to the value of the OpnTmTrvlCor setting has
passed. When the setting is negative, the calculation starts in advance by the correction time in
relation to when the auxiliary contact opened.

532 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

close close
Main Contact Main Contact

open open
1 1
POSCLS POSCLS

0 0

Energy Energy
Accumulation Accumulation
starts starts

OpnTmTrvlCor OpnTmTrvlCor
(Negative) (Positive)

GUID-D03E3522-BFD0-4129-A3A9-700367E5B37E V1 EN-US

Figure 300: Significance of correction factor setting


Accumulated contact abrasion can also be calculated by using the change of state of the trip output.
TRIND is used to get the instance of the trip output and the time delay between the trip initiation and
the opening of the main contact is introduced by the setting OpTmDelay.

The accumulated contact abrasion output ACCMABR is provided as a service value. The value can be
reset by enabling RSACCMABR through LHMI or activating the input RSACCMABR.

Alarm limit check


The ACCMABRWRN warning is activated when the accumulated contact abrasion exceeds the set
value AccmAbrWrnLev.

ACCMABRALM is activated when the accumulated contact abrasion exceeds the limit of the
AccmAbrAlmLev setting.

The ACCMABRWRN and ACCMABRALM outputs can be blocked by activating the binary input BLKALM.

13.4.8.5 Circuit breaker operation cycles GUID-D3481D26-2E42-455E-8DB2-91538421F3B1 v11

The circuit breaker operation cycles subfunction counts the number of closing-opening sequences of
the breaker. The operation counter value is updated after each closing-opening sequence. The
operation is described in figure301.

POSCLS
Operation
POSOPN OPNUM
counter
RSRMNLIFE

OPCNTWRN
Alarm limit
BLOCK
Check
OPCNTALM
BLKALM

GUID-A50229B5-B78C-4043-807D-ECFCE9440A2B V1 EN-US

Figure 301: Functional module diagram for circuit breaker operation cycles

Operation counter
The operation counter counts the number of operations based on the state of change of the auxiliary
contact inputs POSCLS and POSOPN.

The number of operations OPNUM is given as a service value. The old circuit breaker operation
counter value can be used by adding the value to the InitCntVal parameter and can be reset by
activating the input RSRMNLIFE.

Transformer protection RET650 533


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Alarm limit check


OPCNTWRN is generated when the number of operations exceeds the set value of the OpNumWrnLev
threshold setting.

If the number of operations increases and exceeds the limit value set with the OpNumAlmLev setting,
the OPCNTALM output is activated.

The binary outputs OPCNTWRN and OPCNTALM are deactivated when the BLKALM input is activated.

13.4.8.6 Circuit breaker operation monitoring GUID-6DAE4C6B-BD66-49CD-817D-08E4EBF47DE0 v10

The circuit breaker operation monitoring subfunction indicates the inactive days of the circuit breaker
and gives an alarm when the number of days exceed the set level. The operation of the circuit
breaker operation monitoring is shown in figure 302.

POSCLS
Inactive timer INADAYS
POSOPN

Alarm limit MONALM


BLOCK
Check
BLKALM

GUID-B761217E-CE5D-4F76-9B73-0093097D34F9 V1 EN-US

Figure 302: Functional module diagram for circuit breaker operation monitoring

Inactive timer
The Inactive timer module calculates the number of days the circuit breaker has remained in the
same open or closed state. The value is calculated by monitoring the states of the POSOPN and
POSCLS auxiliary contacts.

The number of inactive days INADAYS is available as a service value. The initial number of inactive
days is set using the InitInaDay parameter.

Alarm limit check


MONALM is initiated when the number of inactive days and hours exceed the limit value defined by the
InaDayAlmLev and InaDayAlmTmh setting. The alarm signal MONALM can be blocked by activating
the binary input BLKALM.

13.4.8.7 Circuit breaker spring charge monitoring GUID-F850A940-7890-4C37-8B31-6C7D5B30E582 v13

The circuit breaker spring charge monitoring subfunction calculates the spring charging time. The
operation is described in figure 303.

534 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

SPC
Spring charging
SPD time SPCTM
measurement
RSSPCTM

Alarm limit
BLOCK SPCALM
Check
BLKALM

GUID-3DB117D1-A927-47CF-937D-0AC0BAB5A25F V1 EN-US

Figure 303: Functional module diagram for circuit breaker spring charge indication

Spring charging time measurement


Spring charging time calculation will be initiated as soon as the circuit breaker is closed and charging
motor starts (NO contact of the device is connected to SPRCHRST) to store the energy in the close
spring. An indicator provided in the circuit breaker is displayed when the spring is completely
charged. This status is taken through NO contact and then connected to SPD.

The binary input SPC indicates the start of circuit breaker spring charging time. SPD indicates that the
circuit breaker spring is charged. The spring charging time is calculated from the difference of these
two signal timings. Spring charging indication is described in figure 303.

The last measured spring charging time SPCTM is provided as a service value. The spring charging
time SPCTM can be reset on the LHMI or by activating the input RSSPCTM.

Alarm limit check


If the time taken by the spring to charge is more than the value set with the SpcTmAlmLev setting,
the subfunction generates the SPCALM alarm.

It is possible to block the SPCALM alarm signal by activating the BLKALM binary input.

13.4.8.8 Circuit breaker gas pressure indication GUID-9D070D52-B499-4D45-9195-60181819184E v11

The circuit breaker gas pressure indication subfunction monitors the gas pressure inside the arc
chamber. The operation is described in figure 304.

PRESALM
tON
BLOCK AND t GPRESALM

BLKALM

tON
PRESLO AND t GPRESLO

GUID-ADE5256E-4676-4EA9-AFF6-6B4EC9079A12 V1 EN-US

Figure 304: Functional module diagram for circuit breaker gas pressure indication
When the PRESALM binary input is activated, the GPRESALM output is activated after a time delay set
with the tGasPresAlm setting. The GPRESALM alarm can be blocked by activating the BLKALM input.

If the pressure drops further to a very low level, the PRESLO binary input goes high, activating the
lockout alarm GPRESLO after a time delay set with the tGasPresLO setting. The GPRESLO alarm can
be blocked by activating the BLKALM input.

Transformer protection RET650 535


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

The binary input BLOCK can be used to block the function. The activation of the BLOCK input
deactivates all outputs and resets internal timers. The alarm signals from the function can be blocked
by activating the binary input BLKALM.

13.4.8.9 Coil Open Indication GUID-A7DB31BD-105B-40CF-94E2-378852FA094F v1

The output COLOPN indicates that opening coil has been operated through the open command. The
binary inputs EXEOPNXCBR and EXEOPNCSWI are open command from the control function, not from
the protection function. COLOPN is achieved by AND operation between EXEOPNXCBR and
EXEOPNCSWI. The output can be blocked by the BLOCK binary input signal.

EXEOPNXCBR
Coil Open
EXEOPNCSWI Indication COLOPN
BLOCK

GUID-AAEBD59C-5DDD-40A0-913E-6E20F3E61E3C V1 EN-US

Figure 305: Functional module diagram for coil open indication

13.4.9 Technical data


GUID-B6799420-D726-460E-B02F-C7D4F1937432 v10

Table 482: SSCBR Technical data

Function Range or value Accuracy


Alarm level for open and close operation time (0 – 200) ms ±3 ms
Alarm level for number of operations (0 – 9999)
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
CB Contact Operation Time, opening and ±3 ms
closing
Remaining Life of CB ±2 operations
Accumulated contact abrasion ±1.0% or ±0.5 whichever is greater

13.5 Event function EVENT SEMOD120002-1 v2

13.5.1 Identification
SEMOD167950-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Event function EVENT -
S00946 V1 EN-US

13.5.2 Functionality M12805-6 v11

When using a Substation Automation system with LON or SPA communication, time-tagged events
can be sent at change or cyclically from the IED to the station level. These events are created from

536 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

any available signal in the IED that is connected to the Event function (EVENT). The EVENT function
block is used for LON and SPA communication.

Analog, integer and double indication values are also transferred through the EVENT function.

13.5.3 Function block SEMOD116030-4 v2

EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000697-2-en.vsd
IEC05000697 V2 EN-US

Figure 306: EVENT function block

13.5.4 Signals IP11335-1 v2

PID-4145-INPUTSIGNALS v6

Table 483: EVENT Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 GROUP 0 Input 1
SIGNAL
INPUT2 GROUP 0 Input 2
SIGNAL
INPUT3 GROUP 0 Input 3
SIGNAL
INPUT4 GROUP 0 Input 4
SIGNAL
INPUT5 GROUP 0 Input 5
SIGNAL
INPUT6 GROUP 0 Input 6
SIGNAL
INPUT7 GROUP 0 Input 7
SIGNAL
INPUT8 GROUP 0 Input 8
SIGNAL
INPUT9 GROUP 0 Input 9
SIGNAL
INPUT10 GROUP 0 Input 10
SIGNAL
INPUT11 GROUP 0 Input 11
SIGNAL
INPUT12 GROUP 0 Input 12
SIGNAL
Table continues on next page

Transformer protection RET650 537


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Type Default Description


INPUT13 GROUP 0 Input 13
SIGNAL
INPUT14 GROUP 0 Input 14
SIGNAL
INPUT15 GROUP 0 Input 15
SIGNAL
INPUT16 GROUP 0 Input 16
SIGNAL

13.5.5 Settings IP11336-1 v2

PID-4145-SETTINGS v6

Table 484: EVENT Non group settings (basic)

Name Values (Range) Unit Step Default Description


SPAChannelMask Off - - Off SPA channel mask
Channel 1-8
Channel 9-16
Channel 1-16
LONChannelMask Off - - Off LON channel mask
Channel 1-8
Channel 9-16
Channel 1-16
EventMask1 NoEvents - - AutoDetect Reporting criteria for input 1
OnSet
OnReset
OnChange
AutoDetect
EventMask2 NoEvents - - AutoDetect Reporting criteria for input 2
OnSet
OnReset
OnChange
AutoDetect
EventMask3 NoEvents - - AutoDetect Reporting criteria for input 3
OnSet
OnReset
OnChange
AutoDetect
EventMask4 NoEvents - - AutoDetect Reporting criteria for input 4
OnSet
OnReset
OnChange
AutoDetect
EventMask5 NoEvents - - AutoDetect Reporting criteria for input 5
OnSet
OnReset
OnChange
AutoDetect
EventMask6 NoEvents - - AutoDetect Reporting criteria for input 6
OnSet
OnReset
OnChange
AutoDetect
EventMask7 NoEvents - - AutoDetect Reporting criteria for input 7
OnSet
OnReset
OnChange
AutoDetect
Table continues on next page

538 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


EventMask8 NoEvents - - AutoDetect Reporting criteria for input 8
OnSet
OnReset
OnChange
AutoDetect
EventMask9 NoEvents - - AutoDetect Reporting criteria for input 9
OnSet
OnReset
OnChange
AutoDetect
EventMask10 NoEvents - - AutoDetect Reporting criteria for input 10
OnSet
OnReset
OnChange
AutoDetect
EventMask11 NoEvents - - AutoDetect Reporting criteria for input 11
OnSet
OnReset
OnChange
AutoDetect
EventMask12 NoEvents - - AutoDetect Reporting criteria for input 12
OnSet
OnReset
OnChange
AutoDetect
EventMask13 NoEvents - - AutoDetect Reporting criteria for input 13
OnSet
OnReset
OnChange
AutoDetect
EventMask14 NoEvents - - AutoDetect Reporting criteria for input 14
OnSet
OnReset
OnChange
AutoDetect
EventMask15 NoEvents - - AutoDetect Reporting criteria for input 15
OnSet
OnReset
OnChange
AutoDetect
EventMask16 NoEvents - - AutoDetect Reporting criteria for input 16
OnSet
OnReset
OnChange
AutoDetect
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
Table continues on next page

Transformer protection RET650 539


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

13.5.6 Operation principle M12807-6 v6

The main purpose of the Event function (EVENT) is to generate events when the state or value of
any of the connected input signals is in a state, or is undergoing a state transition, for which event
generation is enabled.

Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a name from the
Application Configuration tool. The inputs are normally used to create single events, but are also
intended for double indication events. For double indications, only the first eight inputs, 1–8, must be
used. Inputs 9–16 can be used for other types of events in the same EVENT block.

The EVENT function also has an input BLOCK to block the generation of events.

Events that are sent from the IED can originate from both internal logical signals and binary input
channels. The internal signals are time-tagged in the main processing module, while the binary input
channels are time-tagged directly on the input module. Time-tagging of the events that are originated
from internal logical signals have a resolution corresponding to the execution cycle-time of the source
application. Time-tagging of the events that are originated from binary input signals have a resolution
of 1 ms.

The outputs from the EVENT function are formed by the reading of status, events and alarms by the
station level on every single input. The user-defined name for each input is intended to be used by
the station level.

All events according to the event mask are stored in a buffer, which contains up to 1000 events. If
new events appear before the oldest event in the buffer is read, the oldest event is overwritten and
an overflow alarm appears.

Events are produced according to set event masks. The event masks are treated commonly for both
the LON and SPA communication. An EventMask can be set individually for each input channel.
These settings are available:

• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect

It is possible to define which part of the EVENT function generates the events. This can be
performed individually for communication types SPAChannelMask and LONChannelMask. For each
communication type these settings are available:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

For LON communication, events are normally sent to station level at change. It is also possible to set
a time for cyclic sending of the events individually for each input channel.

To protect the SA system from signals with a high change rate that can easily saturate the EVENT
function or the communication subsystems behind it, a quota limiter is implemented. If an input
creates events at a rate that completely consume the granted quota then further events from the
channel will be blocked. This block will be removed when the input calms down and the accumulated

540 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

quota reach 66% of the maximum burst quota. The maximum burst quota per input channel is 45
events per second.

13.6 Disturbance report DRPRDRE IP14584-1 v2

13.6.1 Identification
M16055-1 v10

Function description IEC 61850 identification IEC 60617 ANSI/IEEE C37.2


identification device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A3RADR - -
Disturbance report B1RBDR - B22RBDR - -
Disturbance report C1RADR - -

13.6.2 Functionality M12153-3 v16

Complete and reliable information about disturbances in the primary and/or in the secondary system
together with continuous event-logging is accomplished by the disturbance report functionality.

Disturbance report (DRPRDRE), always included in the IED, acquires sampled data of all selected
analog input and binary signals connected to the function block with a maximum of 40 analog and
352 binary signals.

The Disturbance report functionality is a common name for several functions:

• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Fault locator
• Settings information

The Disturbance report function is characterized by great flexibility regarding configuration, starting
conditions, recording times, and large storage capacity.

A disturbance is defined as an activation of an input to the AnRADR or BnRBDR or CnRADR


function blocks, which are set to trigger the disturbance recorder. All connected signals from start of
pre-fault time to the end of post-fault time will be included in the recording. Disturbance record will
have visible settings from all function instances that are configured in the application configuration
tool.

Every disturbance report recording is saved in the IED in the standard COMTRADE format. In the
COMTRADE1999 format it is saved as a header file HDR, a configuration file CFG, and a data file
DAT. In the COMTRADE2013 format, it is saved as CFF single file format. The same applies to all
events, which are continuously saved in a ring-buffer. The local HMI is used to get information about
the recordings. The disturbance report files can be uploaded to PCM600 for further analysis using
the disturbance handling tool.

IED must be configured with COMTRADE1999 format for disturbance recorder


communication with IEC 60870-5-103 protocol.

Transformer protection RET650 541


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.6.3 Function block IP806-1 v1

M12510-3 v3

DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC05000406 V4 EN-US

Figure 307: DRPRDRE function block


SEMOD54837-4 v5

A1RADR
^GRPINPUT1
^GRPINPUT2
^GRPINPUT3
^GRPINPUT4
^GRPINPUT5
^GRPINPUT6
^GRPINPUT7
^GRPINPUT8
^GRPINPUT9
^GRPINPUT10
IEC05000430 V5 EN-US

Figure 308: A1RADR function block example


GUID-A25A01B8-E17E-4624-9B1A-CCA73D24A812 v1

C1RADR
^INPUT41
^INPUT42
^INPUT43
^INPUT44
^INPUT45
^INPUT46
^INPUT47
^INPUT48
^INPUT49
^INPUT50
GUID-7F42F48F-7E32-412E-8E61-D3753C8A4926 V1 EN-US

Figure 309: C1RADR function block


SEMOD54845-4 v6

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432 V4 EN-US

Figure 310: B1RBDR function block, binary inputs, example for B1RBDR - B22RBDR

542 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.6.4 Signals
PID-7839-OUTPUTSIGNALS v1

Table 485: DRPRDRE Output signals

Name Type Description


DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used

GUID-48019111-7303-40FE-A292-65FDFB6AE686 v2

MEMUSED is indicated based on the percentage of number of recordings to total number


of recordings (200 records). When the number of recordings reaches the maximum limit,
the oldest record will be deleted.
PID-4014-INPUTSIGNALS v6

Table 486: A1RADR Input signals

Name Type Default Description


GRPINPUT1 GROUP - Group signal for input 1
SIGNAL
GRPINPUT2 GROUP - Group signal for input 2
SIGNAL
GRPINPUT3 GROUP - Group signal for input 3
SIGNAL
GRPINPUT4 GROUP - Group signal for input 4
SIGNAL
GRPINPUT5 GROUP - Group signal for input 5
SIGNAL
GRPINPUT6 GROUP - Group signal for input 6
SIGNAL
GRPINPUT7 GROUP - Group signal for input 7
SIGNAL
GRPINPUT8 GROUP - Group signal for input 8
SIGNAL
GRPINPUT9 GROUP - Group signal for input 9
SIGNAL
GRPINPUT10 GROUP - Group signal for input 10
SIGNAL

GUID-D025D5D9-A0F3-4A00-891A-63AD5F609A77
PID-8028-INPUTSIGNALS v3
v1

Table 487: C1RADR Input signals

Name Type Default Description


INPUT41 REAL 0 Analog channel 41
INPUT42 REAL 0 Analog channel 42
INPUT43 REAL 0 Analog channel 43
INPUT44 REAL 0 Analog channel 44
INPUT45 REAL 0 Analog channel 45
INPUT46 REAL 0 Analog channel 46
INPUT47 REAL 0 Analog channel 47
INPUT48 REAL 0 Analog channel 48
INPUT49 REAL 0 Analog channel 49
INPUT50 REAL 0 Analog channel 50

Transformer protection RET650 543


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-3798-INPUTSIGNALS v6

Table 488: B1RBDR Input signals

Name Type Default Description


INPUT1 BOOLEAN 0 Binary channel 1
INPUT2 BOOLEAN 0 Binary channel 2
INPUT3 BOOLEAN 0 Binary channel 3
INPUT4 BOOLEAN 0 Binary channel 4
INPUT5 BOOLEAN 0 Binary channel 5
INPUT6 BOOLEAN 0 Binary channel 6
INPUT7 BOOLEAN 0 Binary channel 7
INPUT8 BOOLEAN 0 Binary channel 8
INPUT9 BOOLEAN 0 Binary channel 9
INPUT10 BOOLEAN 0 Binary channel 10
INPUT11 BOOLEAN 0 Binary channel 11
INPUT12 BOOLEAN 0 Binary channel 12
INPUT13 BOOLEAN 0 Binary channel 13
INPUT14 BOOLEAN 0 Binary channel 14
INPUT15 BOOLEAN 0 Binary channel 15
INPUT16 BOOLEAN 0 Binary channel 16

GUID-D3A8067F-80F8-4174-BD2D-4C43F4B99020 v3
B2RBDR to B22RBDR functions have the same input signal specifications as B1RBDR but with
different numbering:

• B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32)


• B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48)
• B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64)
• B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80)
• B6RBDR: INPUT81 to INPUT96 (binary channels 81 to 96)
• B7RBDR: INPUT97 to INPUT112 (binary channels 97 to 112)
• B8RBDR: INPUT113 to INPUT128 (binary channels 113 to 128)
• B9RBDR: INPUT129 to INPUT144 (binary channels 129 to 144)
• B10RBDR: INPUT145 to INPUT160 (binary channels 145 to 160)
• B11RBDR: INPUT161 to INPUT176 (binary channels 161 to 176)
• B12RBDR: INPUT177 to INPUT192 (binary channels 177 to 192)
• B13RBDR: INPUT193 to INPUT208 (binary channels 193 to 208)
• B14RBDR: INPUT209 to INPUT224 (binary channels 209 to 224)
• B15RBDR: INPUT225 to INPUT240 (binary channels 225 to 240)
• B16RBDR: INPUT241 to INPUT256 (binary channels 241 to 256)
• B17RBDR: INPUT257 to INPUT272 (binary channels 257 to 272)
• B18RBDR: INPUT273 to INPUT288 (binary channels 273 to 288)
• B19RBDR: INPUT289 to INPUT304 (binary channels 289 to 304)
• B20RBDR: INPUT305 to INPUT320 (binary channels 305 to 320)
• B21RBDR: INPUT321 to INPUT336 (binary channels 321 to 336)
• B22RBDR: INPUT337 to INPUT352 (binary channels 337 to 352)

544 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.6.5 Settings
PID-7839-SETTINGS v1

Table 489: DRPRDRE Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
COMTRADEFormat 1999(Int16) - - 2013(Float32) COMTRADEFormat
2013(Int16)
2013(Float32)
PreFaultRecT 0.05 - 9.90 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off - - Off Post-fault retrig enabled (On) or not (Off)
On
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off - - Off Operation mode during test mode
On
SetInfoInDRep Disable - - Enable Enable Disturbance report settings
Enable functionality

PID-4014-SETTINGS v7

Table 490: A1RADR Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation01 Off - - Off Operation On/Off
On
Operation02 Off - - Off Operation On/Off
On
Operation03 Off - - Off Operation On/Off
On
Operation04 Off - - Off Operation On/Off
On
Operation05 Off - - Off Operation On/Off
On
Operation06 Off - - Off Operation On/Off
On
Operation07 Off - - Off Operation On/Off
On
Operation08 Off - - Off Operation On/Off
On
Operation09 Off - - Off Operation On/Off
On
Operation10 Off - - Off Operation On/Off
On

Table 491: A1RADR Non group settings (advanced)

Name Values (Range) Unit Step Default Description


NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 1
UnderTrigOp01 Off - - Off Use under level trigger for analog channel
On 1 (on) or not (off)
UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analog channel 1 in
% of signal
Table continues on next page

Transformer protection RET650 545


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


OverTrigOp01 Off - - Off Use over level trigger for analog channel
On 1 (on) or not (off)
OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analog channel 1 in
% of signal
NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 2
UnderTrigOp02 Off - - Off Use under level trigger for analog channel
On 2 (on) or not (off)
UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analog channel 2 in
% of signal
OverTrigOp02 Off - - Off Use over level trigger for analog channel
On 2 (on) or not (off)
OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analog channel 2 in
% of signal
NomValue03 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 3
UnderTrigOp03 Off - - Off Use under level trigger for analog channel
On 3 (on) or not (off)
UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analog channel 3 in
% of signal
OverTrigOp03 Off - - Off Use over level trigger for analog channel
On 3 (on) or not (off)
OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analog channel 3 in
% of signal
NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 4
UnderTrigOp04 Off - - Off Use under level trigger for analog channel
On 4 (on) or not (off)
UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analog channel 4 in
% of signal
OverTrigOp04 Off - - Off Use over level trigger for analog channel
On 4 (on) or not (off)
OverTrigLe04 0 - 5000 % 1 200 Over trigger level for analog channel 4 in
% of signal
NomValue05 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 5
UnderTrigOp05 Off - - Off Use under level trigger for analog channel
On 5 (on) or not (off)
UnderTrigLe05 0 - 200 % 1 50 Under trigger level for analog channel 5 in
% of signal
OverTrigOp05 Off - - Off Use over level trigger for analog channel
On 5 (on) or not (off)
OverTrigLe05 0 - 5000 % 1 200 Over trigger level for analog channel 5 in
% of signal
NomValue06 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 6
UnderTrigOp06 Off - - Off Use under level trigger for analog channel
On 6 (on) or not (off)
UnderTrigLe06 0 - 200 % 1 50 Under trigger level for analog channel 6 in
% of signal
OverTrigOp06 Off - - Off Use over level trigger for analog channel
On 6 (on) or not (off)
OverTrigLe06 0 - 5000 % 1 200 Over trigger level for analog channel 6 in
% of signal
NomValue07 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 7
UnderTrigOp07 Off - - Off Use under level trigger for analog channel
On 7 (on) or not (off)
UnderTrigLe07 0 - 200 % 1 50 Under trigger level for analog channel 7 in
% of signal
Table continues on next page

546 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


OverTrigOp07 Off - - Off Use over level trigger for analog channel
On 7 (on) or not (off)
OverTrigLe07 0 - 5000 % 1 200 Over trigger level for analog channel 7 in
% of signal
NomValue08 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 8
UnderTrigOp08 Off - - Off Use under level trigger for analog channel
On 8 (on) or not (off)
UnderTrigLe08 0 - 200 % 1 50 Under trigger level for analog channel 8 in
% of signal
OverTrigOp08 Off - - Off Use over level trigger for analog channel
On 8 (on) or not (off)
OverTrigLe08 0 - 5000 % 1 200 Over trigger level for analog channel 8 in
% of signal
NomValue09 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 9
UnderTrigOp09 Off - - Off Use under level trigger for analog channel
On 9 (on) or not (off)
UnderTrigLe09 0 - 200 % 1 50 Under trigger level for analog channel 9 in
% of signal
OverTrigOp09 Off - - Off Use over level trigger for analog channel
On 9 (on) or not (off)
OverTrigLe09 0 - 5000 % 1 200 Over trigger level for analog channel 9 in
% of signal
NomValue10 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 10
UnderTrigOp10 Off - - Off Use under level trigger for analog channel
On 10 (on) or not (off)
UnderTrigLe10 0 - 200 % 1 50 Under trigger level for analog channel 10
in % of signal
OverTrigOp10 Off - - Off Use over level trigger for analog channel
On 10 (on) or not (off)
OverTrigLe10 0 - 5000 % 1 200 Over trigger level for analog channel 10 in
% of signal

GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v2
A2RADR and A3RADR functions have the same Non group settings (basic) as A1RADR but with
different numbering:

• A2RADR: Operation11 to Operation20


• A3RADR: Operation21 to Operation30

A2RADR and A3RADR functions have the same Non group settings (advanced) as A1RADR but
with different numbering (examples given in brackets):

• A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)


• A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
PID-8028-SETTINGS v1

Table 492: C1RADR Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation41 Off - - Off Operation On/off
On
Operation42 Off - - Off Operation On/off
On
Operation43 Off - - Off Operation On/off
On
Operation44 Off - - Off Operation On/off
On
Table continues on next page

Transformer protection RET650 547


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


Operation45 Off - - Off Operation On/off
On
Operation46 Off - - Off Operation On/off
On
Operation47 Off - - Off Operation On/off
On
Operation48 Off - - Off Operation On/off
On
Operation49 Off - - Off Operation On/off
On
Operation50 Off - - Off Operation On/off
On

Table 493: C1RADR Non group settings (advanced)

Name Values (Range) Unit Step Default Description


NomValue41 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 41
UnderTrigOp41 Off - - Off Use under level trigger for analog channel
On 41 (on) or not (off)
UnderTrigLe41 0 - 200 % 1 50 Under trigger level for analog channel 41
in % of signal
OverTrigOp41 Off - - Off Use over level trigger for analog channel
On 41 (on) or not (off)
OverTrigLe41 0 - 5000 % 1 200 Over trigger level for analog channel 41 in
% of signal
NomValue42 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 42
UnderTrigOp42 Off - - Off Use under level trigger for analog channel
On 42 (on) or not (off)
UnderTrigLe42 0 - 200 % 1 50 Under trigger level for analog channel 42
in % of signal
OverTrigOp42 Off - - Off Use over level trigger for analog channel
On 42 (on) or not (off)
OverTrigLe42 0 - 5000 % 1 200 Over trigger level for analog channel 42 in
% of signal
NomValue43 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 43
UnderTrigOp43 Off - - Off Use under level trigger for analog channel
On 43 (on) or not (off)
UnderTrigLe43 0 - 200 % 1 50 Under trigger level for analog channel 43
in % of signal
OverTrigOp43 Off - - Off Use over level trigger for analog channel
On 43 (on) or not (off)
OverTrigLe43 0 - 5000 % 1 200 Overtrigger level for analog channel 43 in
% of signal
NomValue44 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 44
UnderTrigOp44 Off - - Off Use under level trigger for analog channel
On 44 (on) or not (off)
UnderTrigLe44 0 - 200 % 1 50 Under trigger level for analog channel 44
in % of signal
OverTrigOp44 Off - - Off Use over level trigger for analog channel
On 44 (on) or not (off)
OverTrigLe44 0 - 5000 % 1 200 Over trigger level for analog channel 44 in
% of signal
NomValue45 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 45
UnderTrigOp45 Off - - Off Use under level trigger for analog channel
On 45 (on) or not (off)
Table continues on next page

548 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


UnderTrigLe45 0 - 200 % 1 50 Under trigger level for analog channel 45
in % of signal
OverTrigOp45 Off - - Off Use over level trigger for analog channel
On 45 (on) or not (off)
OverTrigLe45 0 - 5000 % 1 200 Over trigger level for analog channel 45 in
% of signal
NomValue46 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 46
UnderTrigOp46 Off - - Off Use under level trigger for analog channel
On 46 (on) or not (off)
UnderTrigLe46 0 - 200 % 1 50 Under trigger level for analog channel 46
in % of signal
OverTrigOp46 Off - - Off Use over level trigger for analog channel
On 46 (on) or not (off)
OverTrigLe46 0 - 5000 % 1 200 Over trigger level for analog channel 46 in
% of signal
NomValue47 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 47
UnderTrigOp47 Off - - Off Use under level trigger for analog channel
On 47 (on) or not (off)
UnderTrigLe47 0 - 200 % 1 50 Under trigger level for analog channel 47
in % of signal
OverTrigOp47 Off - - Off Use over level trigger for analog channel
On 47 (on) or not (off)
OverTrigLe47 0 - 5000 % 1 200 Over trigger level for analog channel 47 in
% of signal
NomValue48 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 48
UnderTrigOp48 Off - - Off Use under level trigger for analog channel
On 48 (on) or not (off)
UnderTrigLe48 0 - 200 % 1 50 Under trigger level for analog channel 48
in % of signal
OverTrigOp48 Off - - Off Use over level trigger for analog channel
On 48 (on) or not (off)
OverTrigLe48 0 - 5000 % 1 200 Over trigger level for analog channel 48 in
% of signal
NomValue49 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 49
UnderTrigOp49 Off - - Off Use under level trigger for analog channel
On 49 (on) or not (off)
UnderTrigLe49 0 - 200 % 1 50 Under trigger level for analog channel 49
in % of signal
OverTrigOp49 Off - - Off Use over level trigger for analog channel
On 49 (on) or not (off)
OverTrigLe49 0 - 5000 % 1 200 Over trigger level for analog channel 49 in
% of signal
NomValue50 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 50
UnderTrigOp50 Off - - Off Use under level trigger for analog channel
On 50 (on) or not (off)
UnderTrigLe50 0 - 200 % 1 50 Under trigger level for analog channel 50
in % of signal
OverTrigOp50 Off - - Off Use over level trigger for analog channel
On 50 (on) or not (off)
OverTrigLe50 0 - 5000 % 1 200 Over trigger level for analog channel 50 in
% of signal

Transformer protection RET650 549


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-3798-SETTINGS v6

Table 494: B1RBDR Non group settings (basic)

Name Values (Range) Unit Step Default Description


TrigDR01 Off - - Off Trigger operation On/Off
On
SetLED01 Off - - Off Set LED on HMI for binary channel 1
Start
Trip
Start and Trip
TrigDR02 Off - - Off Trigger operation On/Off
On
SetLED02 Off - - Off Set LED on HMI for binary channel 2
Start
Trip
Start and Trip
TrigDR03 Off - - Off Trigger operation On/Off
On
SetLED03 Off - - Off Set LED on HMI for binary channel 3
Start
Trip
Start and Trip
TrigDR04 Off - - Off Trigger operation On/Off
On
SetLED04 Off - - Off Set LED on HMI for binary channel 4
Start
Trip
Start and Trip
TrigDR05 Off - - Off Trigger operation On/Off
On
SetLED05 Off - - Off Set LED on HMI for binary channel 5
Start
Trip
Start and Trip
TrigDR06 Off - - Off Trigger operation On/Off
On
SetLED06 Off - - Off Set LED on HMI for binary channel 6
Start
Trip
Start and Trip
TrigDR07 Off - - Off Trigger operation On/Off
On
SetLED07 Off - - Off Set LED on HMI for binary channel 7
Start
Trip
Start and Trip
TrigDR08 Off - - Off Trigger operation On/Off
On
SetLED08 Off - - Off Set LED on HMI for binary channel 8
Start
Trip
Start and Trip
TrigDR09 Off - - Off Trigger operation On/Off
On
SetLED09 Off - - Off Set LED on HMI for binary channel 9
Start
Trip
Start and Trip
TrigDR10 Off - - Off Trigger operation On/Off
On
Table continues on next page

550 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


SetLED10 Off - - Off Set LED on HMI for binary channel 10
Start
Trip
Start and Trip
TrigDR11 Off - - Off Trigger operation On/Off
On
SetLED11 Off - - Off Set LED on HMI for binary channel 11
Start
Trip
Start and Trip
TrigDR12 Off - - Off Trigger operation On/Off
On
SetLED12 Off - - Off Set LED on HMI for binary channel 12
Start
Trip
Start and Trip
TrigDR13 Off - - Off Trigger operation On/Off
On
SetLED13 Off - - Off Set LED on HMI for binary channel 13
Start
Trip
Start and Trip
TrigDR14 Off - - Off Trigger operation On/Off
On
SetLED14 Off - - Off Set LED on HMI for binary channel 14
Start
Trip
Start and Trip
TrigDR15 Off - - Off Trigger operation On/Off
On
SetLED15 Off - - Off Set LED on HMI for binary channel 15
Start
Trip
Start and Trip
TrigDR16 Off - - Off Trigger operation On/Off
On
SetLED16 Off - - Off Set LED on HMI for binary channel 16
Start
Trip
Start and Trip
FunType1 0 - 255 - 1 0 Function type for binary channel 1 (IEC
-60870-5-103)
InfNo1 0 - 255 - 1 0 Information number for binary channel 1
(IEC -60870-5-103)
FunType2 0 - 255 - 1 0 Function type for binary channel 2 (IEC
-60870-5-103)
InfNo2 0 - 255 - 1 0 Information number for binary channel 2
(IEC -60870-5-103)
FunType3 0 - 255 - 1 0 Function type for binary channel 3 (IEC
-60870-5-103)
InfNo3 0 - 255 - 1 0 Information number for binary channel 3
(IEC -60870-5-103)
FunType4 0 - 255 - 1 0 Function type for binary channel 4 (IEC
-60870-5-103)
InfNo4 0 - 255 - 1 0 Information number for binary channel 4
(IEC -60870-5-103)
FunType5 0 - 255 - 1 0 Function type for binary channel 5 (IEC
-60870-5-103)
Table continues on next page

Transformer protection RET650 551


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


InfNo5 0 - 255 - 1 0 Information number for binary channel 5
(IEC -60870-5-103)
FunType6 0 - 255 - 1 0 Function type for binary channel 6 (IEC
-60870-5-103)
InfNo6 0 - 255 - 1 0 Information number for binary channel 6
(IEC -60870-5-103)
FunType7 0 - 255 - 1 0 Function type for binary channel 7 (IEC
-60870-5-103)
InfNo7 0 - 255 - 1 0 Information number for binary channel 7
(IEC -60870-5-103)
FunType8 0 - 255 - 1 0 Function type for binary channel 8 (IEC
-60870-5-103)
InfNo8 0 - 255 - 1 0 Information number for binary channel 8
(IEC -60870-5-103)
FunType9 0 - 255 - 1 0 Function type for binary channel 9 (IEC
-60870-5-103)
InfNo9 0 - 255 - 1 0 Information number for binary channel 9
(IEC -60870-5-103)
FunType10 0 - 255 - 1 0 Function type for binary channel 10 (IEC
-60870-5-103)
InfNo10 0 - 255 - 1 0 Information number for binary channel 10
(IEC -60870-5-103)
FunType11 0 - 255 - 1 0 Function type for binary channel 11 (IEC
-60870-5-103)
InfNo11 0 - 255 - 1 0 Information number for binary channel 11
(IEC -60870-5-103)
FunType12 0 - 255 - 1 0 Function type for binary channel 12 (IEC
-60870-5-103)
InfNo12 0 - 255 - 1 0 Information number for binary channel 12
(IEC -60870-5-103)
FunType13 0 - 255 - 1 0 Function type for binary channel 13 (IEC
-60870-5-103)
InfNo13 0 - 255 - 1 0 Information number for binary channel 13
(IEC -60870-5-103)
FunType14 0 - 255 - 1 0 Function type for binary channel 14 (IEC
-60870-5-103)
InfNo14 0 - 255 - 1 0 Information number for binary channel 14
(IEC -60870-5-103)
FunType15 0 - 255 - 1 0 Function type for binary channel 15 (IEC
-60870-5-103)
InfNo15 0 - 255 - 1 0 Information number for binary channel 15
(IEC -60870-5-103)
FunType16 0 - 255 - 1 0 Function type for binary channel 16 (IEC
-60870-5-103)
InfNo16 0 - 255 - 1 0 Information number for binary channel 16
(IEC -60870-5-103)

Table 495: B1RBDR Non group settings (advanced)

Name Values (Range) Unit Step Default Description


TrigLevel01 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 1
IndicationMa01 Hide - - Show Indication mask for binary channel 1
Show
TrigLevel02 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 2
Table continues on next page

552 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Values (Range) Unit Step Default Description


IndicationMa02 Hide - - Show Indication mask for binary channel 2
Show
TrigLevel03 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 3
IndicationMa03 Hide - - Show Indication mask for binary channel 3
Show
TrigLevel04 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 4
IndicationMa04 Hide - - Show Indication mask for binary channel 4
Show
TrigLevel05 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 5
IndicationMa05 Hide - - Show Indication mask for binary channel 5
Show
TrigLevel06 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 6
IndicationMa06 Hide - - Show Indication mask for binary channel 6
Show
TrigLevel07 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 7
IndicationMa07 Hide - - Show Indication mask for binary channel 7
Show
TrigLevel08 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 8
IndicationMa08 Hide - - Show Indication mask for binary channel 8
Show
TrigLevel09 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 9
IndicationMa09 Hide - - Show Indication mask for binary channel 9
Show
TrigLevel10 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 10
IndicationMa10 Hide - - Show Indication mask for binary channel 10
Show
TrigLevel11 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 11
IndicationMa11 Hide - - Show Indication mask for binary channel 11
Show
TrigLevel12 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 12
IndicationMa12 Hide - - Show Indication mask for binary channel 12
Show
TrigLevel13 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 13
IndicationMa13 Hide - - Show Indication mask for binary channel 13
Show
TrigLevel14 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 14
IndicationMa14 Hide - - Show Indication mask for binary channel 14
Show
TrigLevel15 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 15
Table continues on next page

Transformer protection RET650 553


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


IndicationMa15 Hide - - Show Indication mask for binary channel 15
Show
TrigLevel16 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 16
IndicationMa16 Hide - - Show Indication mask for binary channel 16
Show

GUID-8702C5B9-05A3-4E61-8952-C66483FFDFE2 v4
B2RBDR to B22RBDR functions have the same Non group settings (basic) as B1RBDR but with
different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (SetLED17, set LED on HMI for binary channel 17)


• B3RBDR: 33 to 48 (SetLED33, set LED on HMI for binary channel 33)
• B4RBDR: 49 to 64 (SetLED49, set LED on HMI for binary channel 49)
• B5RBDR: 65 to 80 (SetLED65, set LED on HMI for binary channel 65)
• B6RBDR: 81 to 96 (SetLED81, set LED on HMI for binary channel 81)
• B7RBDR: 97 to 112 (SetLED97, set LED on HMI for binary channel 97)
• B8RBDR: 113 to 128 (SetLED113, set LED on HMI for binary channel 113)
• B9RBDR: 129 to 144 (SetLED129, set LED on HMI for binary channel 129)
• B10RBDR: 145 to 160 (SetLED145, set LED on HMI for binary channel 145)
• B11RBDR: 161 to 176 (SetLED161, set LED on HMI for binary channel 161)
• B12RBDR: 177 to 192 (SetLED177, set LED on HMI for binary channel 177)
• B13RBDR: 193 to 208 (SetLED193, set LED on HMI for binary channel 193)
• B14RBDR: 209 to 224 (SetLED209, set LED on HMI for binary channel 209)
• B15RBDR: 225 to 240 (SetLED225, set LED on HMI for binary channel 225)
• B16RBDR: 241 to 256 (SetLED241, set LED on HMI for binary channel 241)
• B17RBDR: 257 to 272 (SetLED257, set LED on HMI for binary channel 257)
• B18RBDR: 273 to 288 (SetLED273, set LED on HMI for binary channel 273)
• B19RBDR: 289 to 304 (SetLED289, set LED on HMI for binary channel 289)
• B20RBDR: 305 to 320 (SetLED305, set LED on HMI for binary channel 305)
• B21RBDR: 321 to 336 (SetLED321, set LED on HMI for binary channel 321)
• B22RBDR: 337 to 352 (SetLED337, set LED on HMI for binary channel 337)

B2RBDR to B22RBDR functions have the same Non group settings (advanced) as B1RBDR but with
different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (IndicationMa17, indication mask for binary channel 17)


• B3RBDR: 33 to 48 (IndicationMa33, indication mask for binary channel 33)
• B4RBDR: 49 to 64 (IndicationMa49, indication mask for binary channel 49)
• B5RBDR: 65 to 80 (IndicationMa65, indication mask for binary channel 65)
• B6RBDR: 81 to 96 (IndicationMa81, indication mask for binary channel 81)
• B7RBDR: 97 to 112 (IndicationMa97, indication mask for binary channel 97)
• B8RBDR: 113 to 128 (IndicationMa113, indication mask for binary channel 113)
• B9RBDR: 129 to 144 (IndicationMa129, indication mask for binary channel 129)
• B10RBDR: 145 to 160 (IndicationMa145, indication mask for binary channel 145)
• B11RBDR: 161 to 176 (IndicationMa161, indication mask for binary channel 161)
• B12RBDR: 177 to 192 (IndicationMa177, indication mask for binary channel 177)
• B13RBDR: 193 to 208 (IndicationMa193, indication mask for binary channel 193)
• B14RBDR: 209 to 224 (IndicationMa209, indication mask for binary channel 209)
• B15RBDR: 225 to 240 (IndicationMa225, indication mask for binary channel 225)
• B16RBDR: 241 to 256 (IndicationMa241, indication mask for binary channel 241)
• B17RBDR: 257 to 272 (IndicationMa257, indication mask for binary channel 257)
• B18RBDR: 273 to 288 (IndicationMa273, indication mask for binary channel 273)
• B19RBDR: 289 to 304 (IndicationMa289, indication mask for binary channel 289)
• B20RBDR: 305 to 320 (IndicationMa305, indication mask for binary channel 305)
• B21RBDR: 321 to 336 (IndicationMa321, indication mask for binary channel 321)
• B22RBDR: 337 to 352 (IndicationMa337, indication mask for binary channel 337)

554 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.6.6 Monitored data


PID-3949-MONITOREDDATA v2

Table 496: DRPRDRE Monitored data

Name Type Values (Range) Unit Description


MemoryUsed INTEGER - % Memory usage (0-100%)
UnTrigStatCh1 BOOLEAN - - Under level trig for analog channel 1
activated
OvTrigStatCh1 BOOLEAN - - Over level trig for analog channel 1
activated
UnTrigStatCh2 BOOLEAN - - Under level trig for analog channel 2
activated
OvTrigStatCh2 BOOLEAN - - Over level trig for analog channel 2
activated
UnTrigStatCh3 BOOLEAN - - Under level trig for analog channel 3
activated
OvTrigStatCh3 BOOLEAN - - Over level trig for analog channel 3
activated
UnTrigStatCh4 BOOLEAN - - Under level trig for analog channel 4
activated
OvTrigStatCh4 BOOLEAN - - Over level trig for analog channel 4
activated
UnTrigStatCh5 BOOLEAN - - Under level trig for analog channel 5
activated
OvTrigStatCh5 BOOLEAN - - Over level trig for analog channel 5
activated
UnTrigStatCh6 BOOLEAN - - Under level trig for analog channel 6
activated
OvTrigStatCh6 BOOLEAN - - Over level trig for analog channel 6
activated
UnTrigStatCh7 BOOLEAN - - Under level trig for analog channel 7
activated
OvTrigStatCh7 BOOLEAN - - Over level trig for analog channel 7
activated
UnTrigStatCh8 BOOLEAN - - Under level trig for analog channel 8
activated
OvTrigStatCh8 BOOLEAN - - Over level trig for analog channel 8
activated
UnTrigStatCh9 BOOLEAN - - Under level trig for analog channel 9
activated
OvTrigStatCh9 BOOLEAN - - Over level trig for analog channel 9
activated
UnTrigStatCh10 BOOLEAN - - Under level trig for analog channel 10
activated
OvTrigStatCh10 BOOLEAN - - Over level trig for analog channel 10
activated
UnTrigStatCh11 BOOLEAN - - Under level trig for analog channel 11
activated
OvTrigStatCh11 BOOLEAN - - Over level trig for analog channel 11
activated
UnTrigStatCh12 BOOLEAN - - Under level trig for analog channel 12
activated
OvTrigStatCh12 BOOLEAN - - Over level trig for analog channel 12
activated
UnTrigStatCh13 BOOLEAN - - Under level trig for analog channel 13
activated
Table continues on next page

Transformer protection RET650 555


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Type Values (Range) Unit Description


OvTrigStatCh13 BOOLEAN - - Over level trig for analog channel 13
activated
UnTrigStatCh14 BOOLEAN - - Under level trig for analog channel 14
activated
OvTrigStatCh14 BOOLEAN - - Over level trig for analog channel 14
activated
UnTrigStatCh15 BOOLEAN - - Under level trig for analog channel 15
activated
OvTrigStatCh15 BOOLEAN - - Over level trig for analog channel 15
activated
UnTrigStatCh16 BOOLEAN - - Under level trig for analog channel 16
activated
OvTrigStatCh16 BOOLEAN - - Over level trig for analog channel 16
activated
UnTrigStatCh17 BOOLEAN - - Under level trig for analog channel 17
activated
OvTrigStatCh17 BOOLEAN - - Over level trig for analog channel 17
activated
UnTrigStatCh18 BOOLEAN - - Under level trig for analog channel 18
activated
OvTrigStatCh18 BOOLEAN - - Over level trig for analog channel 18
activated
UnTrigStatCh19 BOOLEAN - - Under level trig for analog channel 19
activated
OvTrigStatCh19 BOOLEAN - - Over level trig for analog channel 19
activated
UnTrigStatCh20 BOOLEAN - - Under level trig for analog channel 20
activated
OvTrigStatCh20 BOOLEAN - - Over level trig for analog channel 20
activated
UnTrigStatCh21 BOOLEAN - - Under level trig for analog channel 21
activated
OvTrigStatCh21 BOOLEAN - - Over level trig for analog channel 21
activated
UnTrigStatCh22 BOOLEAN - - Under level trig for analog channel 22
activated
OvTrigStatCh22 BOOLEAN - - Over level trig for analog channel 22
activated
UnTrigStatCh23 BOOLEAN - - Under level trig for analog channel 23
activated
OvTrigStatCh23 BOOLEAN - - Over level trig for analog channel 23
activated
UnTrigStatCh24 BOOLEAN - - Under level trig for analog channel 24
activated
OvTrigStatCh24 BOOLEAN - - Over level trig for analog channel 24
activated
UnTrigStatCh25 BOOLEAN - - Under level trig for analog channel 25
activated
OvTrigStatCh25 BOOLEAN - - Over level trig for analog channel 25
activated
UnTrigStatCh26 BOOLEAN - - Under level trig for analog channel 26
activated
OvTrigStatCh26 BOOLEAN - - Over level trig for analog channel 26
activated
Table continues on next page

556 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh27 BOOLEAN - - Under level trig for analog channel 27
activated
OvTrigStatCh27 BOOLEAN - - Over level trig for analog channel 27
activated
UnTrigStatCh28 BOOLEAN - - Under level trig for analog channel 28
activated
OvTrigStatCh28 BOOLEAN - - Over level trig for analog channel 28
activated
UnTrigStatCh29 BOOLEAN - - Under level trig for analog channel 29
activated
OvTrigStatCh29 BOOLEAN - - Over level trig for analog channel 29
activated
UnTrigStatCh30 BOOLEAN - - Under level trig for analog channel 30
activated
OvTrigStatCh30 BOOLEAN - - Over level trig for analog channel 30
activated
UnTrigStatCh31 BOOLEAN - - Under level trig for analog channel 31
activated
OvTrigStatCh31 BOOLEAN - - Over level trig for analog channel 31
activated
UnTrigStatCh32 BOOLEAN - - Under level trig for analog channel 32
activated
OvTrigStatCh32 BOOLEAN - - Over level trig for analog channel 32
activated
UnTrigStatCh33 BOOLEAN - - Under level trig for analog channel 33
activated
OvTrigStatCh33 BOOLEAN - - Over level trig for analog channel 33
activated
UnTrigStatCh34 BOOLEAN - - Under level trig for analog channel 34
activated
OvTrigStatCh34 BOOLEAN - - Over level trig for analog channel 34
activated
UnTrigStatCh35 BOOLEAN - - Under level trig for analog channel 35
activated
OvTrigStatCh35 BOOLEAN - - Over level trig for analog channel 35
activated
UnTrigStatCh36 BOOLEAN - - Under level trig for analog channel 36
activated
OvTrigStatCh36 BOOLEAN - - Over level trig for analog channel 36
activated
UnTrigStatCh37 BOOLEAN - - Under level trig for analog channel 37
activated
OvTrigStatCh37 BOOLEAN - - Over level trig for analog channel 37
activated
UnTrigStatCh38 BOOLEAN - - Under level trig for analog channel 38
activated
OvTrigStatCh38 BOOLEAN - - Over level trig for analog channel 38
activated
UnTrigStatCh39 BOOLEAN - - Under level trig for analog channel 39
activated
OvTrigStatCh39 BOOLEAN - - Over level trig for analog channel 39
activated
Table continues on next page

Transformer protection RET650 557


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh40 BOOLEAN - - Under level trig for analog channel 40
activated
OvTrigStatCh40 BOOLEAN - - Over level trig for analog channel 40
activated
FaultNumber INTEGER - - Disturbance fault number

13.6.7 Operation principle


M12155-6 v15
Disturbance report DRPRDRE is a common name for several functions to supply the operator,
analysis engineer, and so on, with sufficient information about events in the system.

The functions included in the disturbance report are:

• Event list (EL)


• Indications (IND)
• Event recorder (ER)
• Trip value recorder (TVR)
• Disturbance recorder (DR)
• Fault locator (FL)
• Settings information

Figure 311 shows the relations between Disturbance Report, included functions and function blocks.
Event list (EL), Event recorder (ER) and Indications (IND) use information from the binary input
function blocks (BxRBDR). Trip value recorder (TVR) use analog information from the analog input
function blocks (AxRADR) which is used by FL after estimation by TVR. Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.

AxRADR Disturbance Report

DRPRDRE FL
Analog signals
Trip value rec Fault locator

BxRBDR Disturbance
recorder

Binary signals

Event list

Event recorder

Indications

IEC09000336 V4 EN-US

Figure 311: Disturbance report functions and related function blocks


The whole disturbance report can contain information for a number of recordings, each with the data
coming from all the parts mentioned above. The event list function is working continuously,

558 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

independent of disturbance triggering, recording time, and so on. Settings information function
contains all the visible settings, parameter information of components configured in ACT, runtime
status and IEC 61850 behavior that is added to the disturbance record header file. These settings
information is recorded in XML format and then grouped for each function instance in the HDR file.
The function, setting names and Enum values are same as in the HMI and can be translated to the
selected HMI language. All setting values are updated along with the units. If the setting values are
related to the global base value, then the setting value is scaled and updated with corresponding
global base unit. All information in the disturbance report is stored in non-volatile flash memories.
This implies that no information is lost in case of loss of auxiliary power. Each report will get an
identification number in the interval from 0-999.

Disturbance report

Record no. N Record no. N+1 Record no. N+200

General dist.
Trip Event Disturbance
Information & Setting Indications Fault locator Event list
values recordings recording
infotrmation

IEC20000223 V2 EN-US

Figure 312: Disturbance report structure


Up to 200 disturbance reports can be stored. If a new disturbance is to be recorded when the
maximum recording limit is reached, the oldest disturbance report is overwritten by the new one.

The IED flash disk should not be used to store any user files. This causes lack of space
for new disturbance recordings.

Disturbance information M12155-175 v4


Date and time of the disturbance, the indications, events, fault location and the trip values are
available on the local HMI. To acquire a complete disturbance report the user must use a PC and -
either the PCM600 Disturbance handling tool - or a FTP or MMS (over 61850) client. The PC can be
connected to the IED front, rear or remotely via the station bus (Ethernet ports).

Indications (IND) M12155-87 v5


Indications is a list of signals that were activated during the total recording time of the disturbance
(not time-tagged).

Event recorder (ER) M12155-89 v6


The event recorder may contain a list of up to 150 time-tagged events, which have occurred during
the disturbance. The information is available via the local HMI or PCM600.

Event list (EL) M12155-177 v8


The event list may contain a list of totally 5000 time-tagged events. The list information is
continuously updated when selected binary signals change state. The oldest data is overwritten. The
logged signals may be presented via the local HMI or PCM600.

Trip value recorder (TVR) M12155-91 v5


The recorded trip values include phasors of selected analog signals before the fault and during the
fault.

Disturbance recorder (DR) M12155-97 v5


Disturbance recorder records analog and binary signal data before, during and after the fault.

Transformer protection RET650 559


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Settings information GUID-892F72ED-CC6C-469B-90CA-73E9E1181187 v3


For each disturbance recording, the setting values of the configured components are read twice;
once during the trigger of disturbance record and again during post processing of the disturbance
record.

During post processing of the disturbance record, the header file is updated with a section called
Settings . Settings has complete setting values of the configured components that are read during
the trigger time. The setting values, runtime status and the behavior of each component are
compared between the trigger and the post processing time. If there are any differences, then it will
be added in the header file under section Changed_settings.

In the HDR file, section tag Settings has an attribute tag called function which includes parameters
that are grouped based on the function instance. The function tag has content called name which is
the function name provided together with the user-defined name in brackets similar to the HMI.
Status content will indicate the runtime status of the function and beh content will indicate the IEC
61850 behavior of the components, if supported. Non runtime components will not have status and
beh tag contents.

Parameters of the function are listed as a child tag Set with contents name, value and unit:

• name — parameter name same as HMI


• value — actual parameter value
• unit — parameter unit

The changed_settings attribute tag is similar to the settings section. It contains functions which have
changes in parameter value or runtime status or IEC 61850 behavior when compared with trigger
and post-processing settings values.

Time tagging M12155-194 v1


The IED has a built-in real-time calendar and clock. This function is used for all time tagging within
the disturbance report

Recording times M12155-99 v5


Disturbance report DRPRDRE records information about a disturbance during a settable time frame.
The recording times are valid for the whole disturbance report. Disturbance recorder (DR), event
recorder (ER) and indication function register disturbance data and events during tRecording, the
total recording time.

The total recording time, tRecording, of a recorded disturbance is:

tRecording = PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on


which criterion stops the current disturbance recording

560 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Trig point
TimeLimit

PreFaultRecT PostFaultRecT

1 2 3

en05000487.vsd
IEC05000487 V1 EN-US

Figure 313: The recording times definition

PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the operate time of the
trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as any valid trigger
condition, binary or analog, persists (unless limited by TimeLimit the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all activated triggers
are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording was triggered. The
limit time is used to eliminate the consequences of a trigger that does not reset within a reasonable
time interval. It limits the maximum recording time of a recording and prevents subsequent
overwriting of already stored disturbances. Use the setting TimeLimit to set this time.

Analog signals M12155-160 v10


Up to 40 analog signals can be selected for recording by the Disturbance recorder and triggering of
the Disturbance report function. Out of these 40, 30 are reserved for external analog signals from
analog input modules (TRM) and line data communication module (LDCM) via preprocessing
function blocks (SMAI) and summation block (3PHSUM). The last 10 channels may be connected to
internally calculated analog signals available as function block output signals (mA input signals,
phase differential currents, bias currents and so on).

SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...

C1RADR

INPUT41
INPUT42
INPUT43
Internal analogue signals INPUT44
INPUT45
INPUT46

...

INPUT50
GUID-E3F03091-00C5-402B-ABCE-E8F356186ED5 V1 EN-US

Figure 314: Analog input function blocks

Transformer protection RET650 561


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

The external input signals will be acquired, filtered and skewed and (after configuration) available as
an input signal on the AxRADR function block via the SMAI function block. The information is saved
at the Disturbance report base sampling rate (1000 or 1200 Hz). Internally calculated signals are
updated according to the cycle time of the specific function. If a function is running at lower speed
than the base sampling rate, Disturbance recorder will use the latest updated sample until a new
updated sample is available.

If the IED is preconfigured the only tool needed for analog configuration of the Disturbance report is
the Signal Matrix Tool (SMT, external signal configuration). In case of modification of a preconfigured
IED or general internal configuration the Application Configuration tool within PCM600 is used.

The preprocessor function block (SMAI) calculates the residual quantities in cases where only the
three phases are connected (AI4-input not used). SMAI makes the information available as a group
signal output, phase outputs and calculated residual output (AIN-output). In situations where AI4-
input is used as an input signal the corresponding information is available on the non-calculated
output (AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.

For each of the analog signals, Operation = On means that it is recorded by the disturbance recorder.
The trigger is independent of the setting of Operation, and triggers even if operation is set to Off.
Both undervoltage and overvoltage can be used as trigger conditions. The same applies for the
current signals.

If Operation = Off, no waveform (samples) will be recorded and reported in graph. However, Trip
value, pre-fault and fault value will be recorded and reported. The input channel can still be used to
trig the disturbance recorder.

If Operation = On, waveform (samples) will also be recorded and reported in graph.

The analog signals are presented only in the disturbance recording, but they affect the entire
disturbance report when being used as triggers.

Binary signals M12155-162 v10


Up to 352 binary signals can be selected to be handled by disturbance report. The signals can be
selected from internal logical and binary input signals. A binary signal is selected to be recorded
when:

• the corresponding function block is included in the configuration


• the signal is connected to the input of the function block

Each of the 352 signals can be selected as a trigger of the disturbance report (Operation = On). A
binary signal can be selected to activate the red LED on the local HMI (SetLED = On ).

The selected signals are presented in the event recorder, event list and the disturbance recording.
But they affect the whole disturbance report when they are used as triggers. The indications are also
selected from these 352 signals with local HMI IndicationMask = Show/Hide.

Trigger signals M12155-164 v3


The trigger conditions affect the entire disturbance report, except the event list, which runs
continuously. As soon as at least one trigger condition is fulfilled, a complete disturbance report is
recorded. On the other hand, if no trigger condition is fulfilled, there is no disturbance report, no
indications, and so on. This implies the importance of choosing the right signals as trigger conditions.

A trigger can be of type:

• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)

562 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Manual trigger M12155-167 v5


A disturbance report can be manually triggered from the local HMI, PCM600 or via station bus (IEC
61850). When the trigger is activated, the manual trigger signal is generated. This feature is
especially useful for testing. Refer to the operator's manual for procedure.

Binary-signal trigger M12155-169 v4


Any binary signal state (logic one or a logic zero) can be selected to generate a trigger ( Triglevel =
Trig on 0/Trig on 1). When a binary signal is selected to generate a trigger from a logic zero, the
selected signal will not be listed in the indications list of the disturbance report.

Analog-signal trigger M12155-171 v6


All analog signals are available for trigger purposes, no matter if they are recorded in the disturbance
recorder or not. The settings are OverTrigOp, UnderTrigOp, OverTrigLe and UnderTrigLe.

The check of the trigger condition is based on peak-to-peak values. When this is found, the absolute
average value of these two peak values is calculated. If the average value is above the threshold
level for an overvoltage or overcurrent trigger, this trigger is indicated with a greater than (>) sign with
the user-defined name.

If the average value is below the set threshold level for an undervoltage or undercurrent trigger, this
trigger is indicated with a less than (<) sign with its name. The procedure is separately performed for
each channel.

This method of checking the analog start conditions gives a function which is insensitive to DC offset
in the signal. The operate time for this start is typically in the range of one cycle, 20 ms for a 50 Hz
network.

All under/over trig signal information is available on the local HMI and PCM600.

13.6.8 Technical data


M12760-1 v14

Table 497: DRPRDRE technical data

Function Range or value Accuracy


Pre-fault time (0.05–9.90) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–10.0) s -
Maximum number of recordings 200, first in - first out -
Time tagging resolution 1 ms See table 674
Maximum number of analog inputs 40 + 30 (external + internally -
derived)
Maximum number of binary inputs 352 -
Maximum number of phasors in the Trip Value 30 -
recorder per recording
Maximum number of indications in a disturbance 352 -
report
Maximum number of events in the Event recording per 1056 -
recording
Maximum number of events in the Event list 5000, first in - first out -
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -

Transformer protection RET650 563


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.7 Logical signal status report BINSTATREP GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2

13.7.1 Identification GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical signal status report BINSTATREP - -

13.7.2 Functionality GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3

The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to poll
signals from various other functions.

13.7.3 Function block GUID-BA0A5BC3-493B-4FE3-B4A9-14F60A88A22F v2

BINSTATREP
BLOCK OUTPUT1
^INPUT1 OUTPUT2
^INPUT2 OUTPUT3
^INPUT3 OUTPUT4
^INPUT4 OUTPUT5
^INPUT5 OUTPUT6
^INPUT6 OUTPUT7
^INPUT7 OUTPUT8
^INPUT8 OUTPUT9
^INPUT9 OUTPUT10
^INPUT10 OUTPUT11
^INPUT11 OUTPUT12
^INPUT12 OUTPUT13
^INPUT13 OUTPUT14
^INPUT14 OUTPUT15
^INPUT15 OUTPUT16
^INPUT16

IEC09000730-1-en.vsd
IEC09000730 V1 EN-US

Figure 315: BINSTATREP function block

13.7.4 Signals
PID-4144-INPUTSIGNALS v6

Table 498: BINSTATREP Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Single status report input 1
INPUT2 BOOLEAN 0 Single status report input 2
INPUT3 BOOLEAN 0 Single status report input 3
INPUT4 BOOLEAN 0 Single status report input 4
INPUT5 BOOLEAN 0 Single status report input 5
INPUT6 BOOLEAN 0 Single status report input 6
INPUT7 BOOLEAN 0 Single status report input 7
INPUT8 BOOLEAN 0 Single status report input 8
INPUT9 BOOLEAN 0 Single status report input 9
Table continues on next page

564 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Type Default Description


INPUT10 BOOLEAN 0 Single status report input 10
INPUT11 BOOLEAN 0 Single status report input 11
INPUT12 BOOLEAN 0 Single status report input 12
INPUT13 BOOLEAN 0 Single status report input 13
INPUT14 BOOLEAN 0 Single status report input 14
INPUT15 BOOLEAN 0 Single status report input 15
INPUT16 BOOLEAN 0 Single status report input 16

PID-4144-OUTPUTSIGNALS v6

Table 499: BINSTATREP Output signals

Name Type Description


OUTPUT1 BOOLEAN Logical status report output 1
OUTPUT2 BOOLEAN Logical status report output 2
OUTPUT3 BOOLEAN Logical status report output 3
OUTPUT4 BOOLEAN Logical status report output 4
OUTPUT5 BOOLEAN Logical status report output 5
OUTPUT6 BOOLEAN Logical status report output 6
OUTPUT7 BOOLEAN Logical status report output 7
OUTPUT8 BOOLEAN Logical status report output 8
OUTPUT9 BOOLEAN Logical status report output 9
OUTPUT10 BOOLEAN Logical status report output 10
OUTPUT11 BOOLEAN Logical status report output 11
OUTPUT12 BOOLEAN Logical status report output 12
OUTPUT13 BOOLEAN Logical status report output 13
OUTPUT14 BOOLEAN Logical status report output 14
OUTPUT15 BOOLEAN Logical status report output 15
OUTPUT16 BOOLEAN Logical status report output 16

13.7.5 Settings
PID-4144-SETTINGS v6

Table 500: BINSTATREP Non group settings (basic)

Name Values (Range) Unit Step Default Description


t 0.0 - 60.0 s 0.1 10.0 Time delay of function

13.7.6 Operation principle GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3

The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs. The output
status follows the inputs and can be read from the local HMI or via SPA communication.

When an input is set, the respective output is set for a user defined time. If the input signal remains
set for a longer period, the output will remain set until the input signal resets.

Transformer protection RET650 565


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

INPUTn

OUTPUTn
t t

IEC09000732-1-en.vsd
IEC09000732 V1 EN-US

Figure 316: BINSTATREP logical diagram

13.8 Measured values expander block RANGE_XP SEMOD52451-1 v3

13.8.1 Identification
SEMOD113212-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Measured values expander block RANGE_XP - -

13.8.2 Functionality SEMOD52450-4 v9

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGAPC) are provided with measurement supervision functionality. All
measured values can be supervised with four settable limits: low-low limit, low limit, high limit and
high-high limit. The measure value expander block (RANGE_XP) has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary signals: below low-low
limit, below low limit, normal, above high limit or above high-high limit. The output signals can be
used as conditions in the configurable logic or for alarming purpose.

13.8.3 Function block SEMOD54336-4 v3

RANGE_XP
RANGE* HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346 V3 EN-US

Figure 317: RANGE_XP function block

13.8.4 Signals SEMOD53803-1 v2

PID-3819-INPUTSIGNALS v5

Table 501: RANGE_XP Input signals

Name Type Default Description


RANGE INTEGER 0 Measured value range

566 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

PID-3819-OUTPUTSIGNALS v5

Table 502: RANGE_XP Output signals

Name Type Description


HIGHHIGH BOOLEAN Measured value is above high-high limit
HIGH BOOLEAN Measured value is between high and high-high limit
NORMAL BOOLEAN Measured value is between high and low limit
LOW BOOLEAN Measured value is between low and low-low limit
LOWLOW BOOLEAN Measured value is below low-low limit

13.8.5 Operation principle SEMOD52462-4 v7

The input signal must be connected to a range output of a measuring function block (CVMMXN,
CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The function block converts the input
integer value to five binary output signals according to Table 503.

Table 503: Input integer value converted to binary output signals

Measured supervised below low- between low‐ between low between above high-high limit
value is: low limit low and low and high limit high-high and
Output: limit high limit
LOWLOW High
LOW High
NORMAL High
HIGH High
HIGHHIGH High

13.9 Limit counter L4UFCNT GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1

13.9.1 Identification
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Limit counter L4UFCNT -

13.9.2 Functionality GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6

The Limit counter (L4UFCNT) provides a settable counter with four independent limits where the
number of positive and/or negative flanks on the input signal are counted against the setting values
for limits. The output for each limit is activated when the counted value reaches that limit.

Overflow indication is included for each up-counter.

13.9.3 Operation principle


GUID-4D58423F-329C-4553-9FAF-E55A368849A5 v2
Limit counter (L4UFCNT) counts the number of positive and/or negative flanks on the binary input
signal depending on the function settings. L4UFCNT also checks if the accumulated value is equal or
greater than any of its four settable limits. The four limit outputs will be activated relatively on reach of
each limit and remain activated until the reset of the function. Moreover, the content of L4UFCNT is
stored in flash memory and will not be lost at an auxiliary power interruption.

Transformer protection RET650 567


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.9.3.1 Design GUID-B643C994-D0BA-4BE9-BACB-ADEA0197CAE4 v2

Figure 318 illustrates the general logic diagram of the function.

BLOCK

INPUT
Operation
Counter
RESET
VALUE
Overflow
CountType Detection OVERFLOW

OnMaxValue

Limit LIMIT1 … 4
MaxValue Check

CounterLimit1...4

Error ERROR
Detection
InitialValue

IEC12000625 V2 EN-US

Figure 318: Logic diagram


The counter can be initialized to count from a settable non-zero value after reset of the function. The
function has also a maximum counted value check. The three possibilities after reaching the
maximum counted value are:

• Stops counting and activates a steady overflow indication for the next count
• Rolls over to zero and activates a steady overflow indication for the next count
• Rolls over to zero and activates a pulsed overflow indication for the next count

The pulsed overflow output lasts up to the first count after rolling over to zero, as illustrated in Figure
319.

Overflow indication

Actual value ... Max value -1 Max value  Max value +1 Max value +2  Max value +3 ...

Counted value ... Max value -1 Max value  0  1  2 ...

IEC12000626 V2 EN-US

Figure 319: Overflow indication when OnMaxValue is set to rollover pulsed


The Error output is activated as an indicator of setting the counter limits and/or initial value setting(s)
greater than the maximum value. The counter stops counting the input and all the outputs except the
error output remains at zero state. The error condition remains until the correct settings for counter
limits and/or initial value setting(s) are applied.

The function can be blocked through a block input. During the block time, input is not counted and
outputs remain in their previous states. However, the counter can be initialized after reset of the
function. In this case the outputs remain in their initial states until the release of the block input.

568 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.9.3.2 Reporting GUID-7DF874A7-F7DA-48DD-8760-5E4CF05FD870 v2

The content of the counter can be read on the local HMI.

Reset of the counter can be performed from the local HMI or via a binary input.

Reading of content and resetting of the function can also be performed remotely, for example from a
IEC 61850 client. The value can also be presented as a measurement on the local HMI graphical
display.

13.9.4 Function block GUID-C90E7375-F3CC-414A-93FC-9AC4A9156FFC v1

L4UFCNT
BLOCK ERROR
INPUT OVERFLOW
RESET LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE
IEC12000029 V2 EN-US

Figure 320: L4UFCNT function block

13.9.5 Signals
PID-6966-INPUTSIGNALS v2

Table 504: L4UFCNT Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT BOOLEAN 0 Input for counter
RESET BOOLEAN 0 Reset of function

PID-6966-OUTPUTSIGNALS v2

Table 505: L4UFCNT Output signals

Name Type Description


ERROR BOOLEAN Error indication on counter limit and/or initial value settings
OVERFLOW BOOLEAN Overflow indication on count of greater than MaxValue
LIMIT1 BOOLEAN Counted value is larger than or equal to CounterLimit1
LIMIT2 BOOLEAN Counted value is larger than or equal to CounterLimit2
LIMIT3 BOOLEAN Counted value is larger than or equal to CounterLimit3
LIMIT4 BOOLEAN Counted value is larger than or equal to CounterLimit4
VALUE INTEGER Counted value

13.9.6 Settings
PID-6966-SETTINGS v2

Table 506: L4UFCNT Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
CountType Positive edge - - Positive edge Select counting on positive and/or
Negative edge negative flanks
Both edges
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
Table continues on next page

Transformer protection RET650 569


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Values (Range) Unit Step Default Description


CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop - - Stop Select if counter stops or rolls over after
Rollover Steady reaching maxValue with steady or pulsed
Rollover Pulsed overflow flag
InitialValue 0 - 65535 - 1 0 Initial count value after reset of the
function

13.9.7 Monitored data


PID-6966-MONITOREDDATA v2

Table 507: L4UFCNT Monitored data

Name Type Values (Range) Unit Description


VALUE INTEGER - - Counted value

13.9.8 Technical data


GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v4

Table 508: L4UFCNT technical data

Function Range or value Accuracy


Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -

13.10 Running hour-meter TEILGAPC

13.10.1 Identification GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v2

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Running hour-meter TEILGAPC - -

13.10.2 Functionality GUID-464FB24F-B367-446C-963A-A14841943B87 v3

The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time when
a given binary signal has been high, see also Figure 321.

570 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

BLOCK
RESET
IN Time Accumulation ACC_HOUR
ADDTIME with Retain
ACC_DAY
tAddToTime

q-1

OVERFLOW
a
&
a>b
99 999.9 h b

WARNING
a
&
a>b
tWarning b

ALARM
a
&
a>b
tAlarm b

q-1 = unit delay


IEC15000321 V2 EN-US

Figure 321: TEILGAPC logics


The main features of TEILGAPC are:

• Applicable to very long time accumulation (≤ 99999.9 hours)


• Supervision of limit transgression conditions and rollover/overflow
• Possibility to define a warning and alarm with the resolution of 0.1 hours
• Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time

13.10.3 Function block GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1

TEILGAPC
BLOCK ALARM
IN WARNING
ADDTIME OVERFLOW
RESET ACC_HOUR
ACC_DAY

IEC15000323.vsdx

IEC15000323 V1 EN-US

Figure 322: TEILGAPC function block

13.10.4 Signals
PID-6998-INPUTSIGNALS v1

Table 509: TEILGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Freeze the accumulation and block the outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time, when its
value is high
ADDTIME BOOLEAN 0 Add time to the accumulation
RESET BOOLEAN 0 Reset accumulated time

Transformer protection RET650 571


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

PID-6998-OUTPUTSIGNALS v1

Table 510: TEILGAPC Output signals

Name Type Description


ALARM BOOLEAN Indicator that accumulated time has reached alarm limit
WARNING BOOLEAN Indicator that accumulated time has reached warning limit
OVERFLOW BOOLEAN Indicator that accumulated time has reached overflow limit
ACC_HOUR REAL Accumulated time in hours
ACC_DAY REAL Accumulated time in days

13.10.5 Settings
PID-6998-SETTINGS v1

Table 511: TEILGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On
tAlarm 1.0 - 99999.9 Hour 0.1 90000.0 Time limit for alarm supervision
tWarning 1.0 - 99999.9 Hour 0.1 50000.0 Time limit for warning supervision
tAddToTime 0.0 - 99999.9 Hour 0.1 0.0 Time to add to the accumulation

13.10.6 Operation principle GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v4

Figure 323 describes the simplified logic of the function.

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACC_HOUR
Time Accumulation
IN
ADDTIME ACC_DAY

tAddToTime

Loop Delay

IEC15000322 V2 EN-US

Figure 323: TEILGAPC Simplified logic


TEILGAPC main functionalities

• IN: Accumulation of the elapsed time when input IN is high

572 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

• applicable to very long time accumulation (≤99999.9 hours)


• output ACC_HOUR presents accumulated value in hours and ACC_DAY presents
accumulated value in days
• accumulated value is retained in a non-volatile memory
• any retained value is used as initiation value for the integration following by a restart
• RESET: Reset of the accumulated value. Consequently all other outputs are also reset
• independent of the input IN value
• reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is high during the
reset.
• reset can be made by activation of input RESET or from LHMI or with IEC 61850
command
• ADDTIME: Manually add time to the currently accumulated time
• the amount of time to be added is defined by a setting tAddToTime
• time is added through activation of input ADDTIME or from LHMI or with IEC 61850
command
• BLOCK: Freeze the accumulation and block/reset the other outputs
• independent of the input IN value
• BLOCK request overrides RESETrequest
• Monitor and report the conditions of limit transgression
• overflow if output ACC_HOUR > 99 999.9 hours
• alarm if output ACC_HOUR > tAlarm
• warning if output ACC_HOUR > tWarning

The ACC_HOURoutput represents the accumulated time in hours and the ACC_DAY output
represents the accumulated time in days.

tAlarm and tWarning are user settable time limit parameters in hours. They are also independent of
each other, that is, there is no check if tAlarm > tWarning.

tAddToTime is a user settable time parameter in hours.

tAlarm, tWarning and tAddToTime are possible to be defined with a resolution of 0.1 hours (6
minutes).

The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will reset and the
accumulated time will reset and start from zero if an overflow occurs.

13.10.6.1 Operation accuracy GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1

The accuracy of TEILGAPC depends on essentially two factors

• the pulse length


• the number of pulses, that is, the number of rising and falling flank pairs

In principle, more pulses may lead to reduced accuracy.

13.10.6.2 Memory storage GUID-B49698FF-0AB2-4792-A7CB-5534313B6CA0 v2

The value of the accumulated time is retained in a non-volatile memory,

• at every falling edge of the input IN


• at every even 6 minutes, after a rising edge of the input IN
• after a manual addition of time

Consequently in case of a power failure, there is a risk of losing the difference in time between actual
time and last time stored in the non-volatile memory.

Transformer protection RET650 573


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

13.10.7 Technical data


GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1

Table 512: TEILGAPC Technical data

Function Range or value Accuracy


Time limit for alarm supervision, (0 - 99999.9) hours ±0.1% of set value
tAlarm
Time limit for warning supervision, (0 - 99999.9) hours ±0.1% of set value
tWarning
Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%

13.11 Fault current and voltage monitoring function


FLTMMXU GUID-B976D374-CB18-441E-9A12-D4B351D6BF7F v1

13.11.1 Function revision history GUID-0AA99E78-0C76-48B5-AA00-8E3201C0D263 v2

Document Product History


revision revision
A 2.2.1 -
B 2.2.1 -
C 2.2.1 -
D 2.2.1 -
E 2.2.4 -
F 2.2.5 -
H 2.2.6 -
J 2.2.6 Dead band supervision removed from the reporting outputs. PreTrig value range changed
from 0-10 to 0-50. PostTrig value range changed from 1-50 to 0-50.

13.11.2 Identification GUID-A5B9E605-328B-4168-BEE3-7BF30BC7E701 v1

Function description IEC 61850 identification IEC 60617 identification ANSI/IEEE C37.2 device
number
Fault current and voltage FLTMMXU - -
monitoring function

13.11.3 Functionality GUID-2EC2A5A0-CFA9-4241-90F3-706F5269435A v1

The fault current and voltage monitoring function (FLTMMXU) monitors and reports the maximum
peak current per phase, maximum RMS current per phase, DFT values of current per phase and
three phase to ground voltages, as well as DFT values of neutral current and neutral voltage upon a
trip event occurrence.

The FLTMMXU function monitors the voltage and current data for a predefined time window and
stores their values when the binary input TRIGFLTUI becomes active. The trip signal from any
protection/monitoring function should be connected to TRIGFLTUI input for the data monitoring. The
time window for calculation of maximum peak and RMS current of individual phases can be set using
the setting parameters PreTrig and PostTrig .

574 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

13.11.4 Function block GUID-8769C5A2-5164-4EE9-9DE8-B04869DA8C54 v1

FLTMMXU
I3P* REPREADY
U3P* FLTIL1MAG
BLOCK FLTIL1ANG
TRGFLTUI FLTIL2MAG
RSTFLTUI FLTIL2ANG
FLTIL3MAG
FLTIL3ANG
FLTINMAG
FLTINANG
FLTUL1MAG
FLTUL1ANG
FLTUL2MAG
FLTUL2ANG
FLTUL3MAG
FLTUL3ANG
FLTUNMAG
FLTUNANG
IMAX
IL1MAXPK
IL2MAXPK
IL3MAXPK
IL1MAX
IL2MAX
IL3MAX

IEC21000225 V2 EN-US

Figure 324: FLTMMXU function block

13.11.5 Signals GUID-08275B60-9D37-449B-9970-63FA6853AF0A v1

PID-7997-INPUTSIGNALS v1

Table 513: FLTMMXU Input signals

Name Type Default Description


I3P GROUP - Group input for three-phase current
SIGNAL
U3P GROUP - Group input for three-phase voltage
SIGNAL
BLOCK BOOLEAN 0 Block the function
TRGFLTUI BOOLEAN 0 Trigger fault record
RSTFLTUI BOOLEAN 0 Reset last fault values

PID-7997-OUTPUTSIGNALS v1

Table 514: FLTMMXU Output signals

Name Type Description


REPREADY BOOLEAN Indicates that the fault data ready to be reported
FLTIL1MAG REAL Fundamental DFT magnitude of current of phase L1 of the last
event
FLTIL1ANG REAL Fundamental DFT angle of current of phase L1 of the last event
FLTIL2MAG REAL Fundamental DFT magnitude of current of phase L2 of the last
event
FLTIL2ANG REAL Fundamental DFT angle of current of phase L2 of the last event
FLTIL3MAG REAL Fundamental DFT magnitude of current of phase L3 of the last
event
FLTIL3ANG REAL Fundamental DFT angle of current of phase L3 of the last event
FLTINMAG REAL Fundamental DFT magnitude of neutral current of the last event
Table continues on next page

Transformer protection RET650 575


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

Name Type Description


FLTINANG REAL Fundamental DFT angle of neutral current of the last event
FLTUL1MAG REAL Fundamental DFT magnitude of voltage of phase L1 of the last
event
FLTUL1ANG REAL Fundamental DFT angle of voltage of phase L1 of the last event
FLTUL2MAG REAL Fundamental DFT magnitude of voltage of phase L2 of the last
event
FLTUL2ANG REAL Fundamental DFT angle of voltage of phase L2 of the last event
FLTUL3MAG REAL Fundamental DFT magnitude of voltage of phase L3 of the last
event
FLTUL3ANG REAL Fundamental DFT angle of voltage of phase L3 of the last event
FLTUNMAG REAL Fundamental DFT magnitude of neutral voltage of the last event
FLTUNANG REAL Fundamental DFT angle of neutral voltage of the last event
IMAX REAL Maximum RMS current of all phases of the last event
IL1MAXPK REAL Maximum peak current of phase L1 of the last event
IL2MAXPK REAL Maximum peak current of phase L2 of the last event
IL3MAXPK REAL Maximum peak current of phase L3 of the last event
IL1MAX REAL Maximum RMS current of phase L1 of the last event
IL2MAX REAL Maximum RMS current of phase L2 of the last event
IL3MAX REAL Maximum RMS current of phase L3 of the last event

13.11.6 Settings GUID-84784563-FCA9-46D2-B921-5F50741178E2 v1

PID-7997-SETTINGS v1

Table 515: FLTMMXU Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
PreTrig 0 - 50 cycles 1 5 The number of cycles considered for fault
data calculation prior to positive edge of
the binary input TRIGFLTUI
PostTrig 0 - 50 cycles 1 5 The number of cycles considered for fault
data calculation post to positive edge of
the binary input TRIGFLTUI

Table 516: FLTMMXU Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

13.11.7 Monitored data


PID-7997-MONITOREDDATA v1

Table 517: FLTMMXU Monitored data

Name Type Values (Range) Unit Description


TRIGTIME GROUP - - Date and time at instant of input
SIGNAL TRIGFLTUI input active
TRIGDUR REAL - ms Indicates pulse duration of TRIGFLTUI
input
FLTIL1MAG REAL - A Fundamental DFT magnitude of current of
phase L1 of the last event
Table continues on next page

576 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Name Type Values (Range) Unit Description


FLTIL1ANG REAL - deg Fundamental DFT angle of current of
phase L1 of the last event
FLTIL2MAG REAL - A Fundamental DFT magnitude of current of
phase L2 of the last event
FLTIL2ANG REAL - deg Fundamental DFT angle of current of
phase L2 of the last event
FLTIL3MAG REAL - A Fundamental DFT magnitude of current of
phase L3 of the last event
FLTIL3ANG REAL - deg Fundamental DFT angle of current of
phase L3 of the last event
FLTINMAG REAL - A Fundamental DFT magnitude of neutral
current of the last event
FLTINANG REAL - deg Fundamental DFT angle of neutral current
of the last event
FLTUL1MAG REAL - kV Fundamental DFT magnitude of voltage
of phase L1 of the last event
FLTUL1ANG REAL - deg Fundamental DFT angle of voltage of
phase L1 of the last event
FLTUL2MAG REAL - kV Fundamental DFT magnitude of voltage
of phase L2 of the last event
FLTUL2ANG REAL - deg Fundamental DFT angle of voltage of
phase L2 of the last event
FLTUL3MAG REAL - kV Fundamental DFT magnitude of voltage
of phase L3 of the last event
FLTUL3ANG REAL - deg Fundamental DFT angle of voltage of
phase L3 of the last event
FLTUNMAG REAL - kV Fundamental DFT magnitude of neutral
voltage of the last event
FLTUNANG REAL - deg Fundamental DFT angle of neutral
voltage of the last event
IMAX REAL - A Maximum RMS current of all phases of
the last event
IL1MAXPK REAL - A Maximum peak current of phase L1 of the
last event
IL2MAXPK REAL - A Maximum peak current of phase L2 of the
last event
IL3MAXPK REAL - A Maximum peak current of phase L3 of the
last event
IL1MAX REAL - A Maximum RMS current of phase L1 of the
last event
IL2MAX REAL - A Maximum RMS current of phase L2 of the
last event
IL3MAX REAL - A Maximum RMS current of phase L3 of the
last event
IL1 REAL - A Measured RMS current of phase L1
IL2 REAL - A Measured RMS current of phase L2
IL3 REAL - A Measured RMS current of phase L3
UL1 REAL - kV Measured RMS voltage of phase L1
UL2 REAL - kV Measured RMS voltage of phase L2
UL3 REAL - kV Measured RMS voltage of phase L3

13.11.8 Operation principle GUID-99D2F5E9-0C83-4EAC-824B-38916832AC21 v1

The overall functionality of FLTMMXU function is shown in Figure 325.

Transformer protection RET650 577


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

I3P
U3P ILx
BLOCK ULx
TRIGFLTUI ILxMAXPK
Maximum RMS current ILxMAX
and maximum peak
IMAX
current calculation
RSTFLTUI TRIGTIME
TRIGDUR
PreTrig
PostTrig

FLTILxMAG
FLTILxANG
Fundamental DFT FLTINMAG
current and voltage
FLTINANG
values snapshot
captured at the time of FLTULxMAG
TRIGFLTUI signal FLTULxANG
becomes TRUE FLTUNMAG
FLTUNANG

Where Lx = Phase L1, L2 and L3


IEC21000226 V1 EN-US

Figure 325: Overall functionality of FLTMMXU


The FLTMMXU function should be connected to SMAI functions for U3P and I3P signals. The
TRIGFLTUI signal should be connected to general trip signal of protection/ monitoring function in the
ACT configuration.

The function is triggered when the TRIGFLTUI binary input of the function is TRUE, for example, if
TRIGFLTUI is connected to general TRIP signal of SMPPTRC function. The duration for calculation
of maximum peak current for each phase and maximum RMS current for each phase is set using the
setting parameters PreTrig and PostTrig as shown in Figure 326.

578 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 13
Monitoring

Instantaneous samples
Peak value(SMAI o/p)
RMS value(SMAI o/p)

PreTrig PostTrig
TRIGFLTUI
Time duration for maximum peak and
RMS current calculation

IL1MAXPK
IL1MAX
FLTIL1MAG

IL1

IL2MAXPK
IL2MAX
FLTIL2MAG

IL2

IL3MAXPK
IL3MAX
FLTIL3MAG

IL3

IEC21000227 V1 EN-US

Figure 326: Maximum peak and RMS current calculation


The maximum peak and RMS current in individual phases are evaluated for the time duration from
PreTrig to PostTrig. At the end of PostTrig, the maximum peak and RMS current of each phase are
reported to IEC 61850, LHMI and monitoring tool.

The fundamental DFT magnitude and angle of phase currents (FLTILxMAG/FLTILxANG), phase
voltages (FLTULxMAG/FLTULxANG), neutral current (FLTINMAG/FLTINANG) and neutral voltage

Transformer protection RET650 579


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 13 1MRK504170-UEN Rev. J
Monitoring

(FLTUNMAG/FLTUNANG) are read and stored at the positive edge of the binary input TRIGFLTUI.
These values are also reported to IEC 61850, LHMI, monitoring tool at the end of PostTrig.

The reference for the angle outputs can be set by DFTReference setting parameter in
SMAI function.

The reported outputs (ILxMAXPK, ILxMAX, IMAX, FLTILxMAG/FLTILxANG, FLTULxMAG/


FLTULxANG, FLTINMAG/FLTINANG, and FLTUNMAG/FLTUNANG ) show the previous event values
till a new positive edge trigger is received by TRIGFLTUI input.

The output TRIGTIME shows the date and time of the instant when TRIGFLTUI input has changed
the state to TRUE from FALSE.

TRIGDUR output indicates the time duration of TRIGFLTUI input active in ms.

A reset command input RSTFLTUI is provided to reset all the monitored/reported output values to
zero.

If the RSTFLTUI signal remains TRUE and a new trigger for TRIGFLTUI input is received,
the FLTMMXU will report the new set of values. Only the positive edge of the RSTFLTUI
input is considered to reset the values which were reported/monitored in the previous
event.

BLOCK input is provided to stop the internal calculations. When BLOCK input is active, activation of
TRIGFLTUI input will not trigger the fault data calculations. The ILxMAXPK, ILxMAX, IMAX,
FLTILxMAG/FLTILxANG, FLTULxMAG/FLTULxANG, FLTINMAG/FLTINANG and FLTUNMAG/
FLTUNANG outputs will retain the previous fault event values.

13.11.9 Technical data


GUID-74F6F38A-8DF9-4343-910D-4E0594C6E21F v2

Table 518: FLTMMXU technical data

Function Range or value Accuracy


Voltage, FLTULxMAG (1 to 300) V ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Current, FLTILxMAG (0.1-10.0) x Ir ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Phase angle, FLTULxANG (1 to 300) V ±2 degrees at U ≤ 5 V
±0.5 degrees at U > 5 V
Phase angle, FLTILxANG (0.1-10.0) x Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir
±0.5 degrees at 0.5 × Ir < I ≤ 10.0 × Ir

580 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 14
Metering

Section 14 Metering
14.1 Pulse-counter logic PCFCNT IP14600-1 v3

14.1.1 Identification
M14879-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pulse-counter logic PCFCNT -

S00947 V1 EN-US

14.1.2 Functionality M13394-3 v7

Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy consumption values. The
pulses are captured by the binary input module and then read by the PCFCNT function. A scaled
service value is available over the station bus. The special Binary input module with enhanced pulse
counting capabilities must be ordered to achieve this functionality.

14.1.3 Function block M13400-3 v5

PCFCNT
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
SCAL_VAL

IEC14000043-1-en.vsd
IEC09000335 V3 EN-US

Figure 327: PCFCNT function block

14.1.4 Signals
PID-6509-INPUTSIGNALS v4

Table 519: PCFCNT Input signals

Name Type Default Description


BI_PULSE BOOLEAN 0 Connect binary input channel for metering
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
RS_CNT BOOLEAN 0 Resets pulse counter value

Transformer protection RET650 581


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 14 1MRK504170-UEN Rev. J
Metering

PID-6509-OUTPUTSIGNALS v4

Table 520: PCFCNT Output signals

Name Type Description


INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete integration cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information

14.1.5 Settings
PID-6509-SETTINGS v4

Table 521: PCFCNT Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
EventMask NoEvents - - NoEvents Report mask for analog events from pulse
ReportEvents counter
CountCriteria Off - - RisingEdge Pulse counter criteria
RisingEdge
Falling edge
OnChange
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to
unit per counted value
Quantity Count - - Count Measured quantity for SCAL_VAL output
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value

14.1.6 Monitored data


PID-6509-MONITOREDDATA v4

Table 522: PCFCNT Monitored data

Name Type Values (Range) Unit Description


SCAL_VAL REAL - - Scaled value with time and status
information

14.1.7 Operation principle IP14087-1 v2

M13397-3 v5
The registration of pulses is done for positive transitions (0->1) on one of the 16 binary input
channels located on the Binary Input Module (BIM). Pulse counter values are sent to the station HMI
with predefined cyclicity without reset.

The reporting time period can be set in the range from 1 second to 60 minutes and is synchronized
with absolute system time. Interrogation of additional pulse counter values can be done with a
command (intermediate reading) for a single counter. All active counters can also be read by the
LON General Interrogation command (GI) or IEC 61850.

Pulse-counter logic (PCFCNT) function in the IED supports unidirectional incremental counters. That
means only positive values are possible. The counter uses a 32 bit format, that is, the reported value

582 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 14
Metering

is a 32-bit, signed integer with a range 0...+2147483647. The counter is reset at initialization of the
IED.

The reported value to station HMI over the station bus contains Identity, Scaled Value (pulse count x
scale), Time, and Pulse Counter Quality. The Pulse Counter Quality consists of:

• Invalid (board hardware error or configuration error)


• Wrapped around
• Blocked
• Adjusted

The transmission of the counter value by SPA can be done as a service value, that is, the value
frozen in the last integration cycle is read by the station HMI from the database. PCFCNT updates
the value in the database when an integration cycle is finished and activates the NEW_VAL signal in
the function block. This signal can be connected to an Event function block, be time tagged, and
transmitted to the station HMI. This time corresponds to the time when the value was frozen by the
function.

The pulse-counter logic function requires a binary input card, BIMp, that is specially
adapted to the pulse-counter logic function.

M13399-3 v9
Figure 328 shows the pulse-counter logic function block with connections of the inputs and outputs.

SingleCmdFunc PulseCounter EVENT


OUTx BLOCK
INVALID INPUT1
SingleCmdFunc Pulse RESTART INPUT2
OUTx INPUT OUT READ_VAL
Pulse length >1s BLOCKED INPUT3
I/O-module NEW_VAL INPUT4
BI_PULSE
”Reset counter” RS_CNT
NAME
SCAL_VAL IEC EVENT

SMS settings Database


1.Operation = Off/On Pulse counter value:
2.tReporting = 0s...60min 0...2147483647
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
en05000744.vsd
IEC05000744 V1 EN-US

Figure 328: Overview of the pulse-counter logic function


The BLOCK and READ_VAL inputs can be connected to Single Command logics, which are intended
to be controlled either from the station HMI or/and the local HMI. As long as the BLOCK signal is set,
the pulse counter is blocked. The signal connected to READ_VAL performs one additional reading
per positive flank. The signal must be a pulse with a length >1 second.

The BI_PULSE input is connected to the used input of the function block for the Binary Input Module
(BIM).

The RS_CNT input is used for resetting the counter.

Each pulse-counter logic function block has four binary output signals that can be connected to an
Event function block for event recording: INVALID, RESTART, BLOCKED and NEW_VAL. The
SCAL_VAL signal can be connected to the IEC Event function block.

The INVALID signal is a steady signal and is set if the Binary Input Module, where the pulse counter
input is located, fails or has wrong configuration.

Transformer protection RET650 583


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 14 1MRK504170-UEN Rev. J
Metering

The RESTART signal is a steady signal and is set when the reported value does not comprise a
complete integration cycle. That is, in the first message after IED start-up, in the first message after
deblocking, and after the counter has wrapped around during last integration cycle.

The BLOCKED signal is a steady signal and is set when the counter is blocked. There are two
reasons why the counter is blocked:

• The BLOCK input is set, or


• The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was updated since last
report.

Note, the pulse is short, one cycle.

The SCAL_VAL signal consists of scaled value (according to parameter Scale), time and status
information.

14.1.8 Technical data IP14092-1 v1

M13404-2 v5

Table 523: PCFCNT technical data

Function Setting range Accuracy


Input frequency See Binary Input Module (BIM) -
Cycle time for report of counter (1–3600) s -
value

14.2 Function for energy calculation and demand handling


ETPMMTR SEMOD153638-1 v2

14.2.1 Identification
SEMOD175537-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Function for energy calculation and ETPMMTR W_Varh -
demand handling

14.2.2 Functionality GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3

Power system measurement (CVMMXN) can be used to measure active as well as reactive power
values. Function for energy calculation and demand handling (ETPMMTR) uses measured active
and reactive power as input and calculates the accumulated active and reactive energy pulses, in
forward and reverse direction. Energy values can be read or generated as pulses. Maximum demand
power values are also calculated by the function. This function includes zero point clamping to
remove noise from the input signal. As output of this function: periodic energy calculations,
integration of energy values, calculation of energy pulses, alarm signals for limit violation of energy
values and maximum power demand, can be found.

584 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 14
Metering

The values of active and reactive energies are calculated from the input power values by integrating
them over a selected time tEnergy. The integration of active and reactive energy values will happen
in both forward and reverse directions. These energy values are available as output signals and also
as pulse outputs. Integration of energy values can be controlled by inputs (STARTACC and STOPACC)
and EnaAcc setting and it can be reset to initial values with RSTACC input.

The maximum demand for active and reactive powers are calculated for the set time interval tEnergy
and these values are updated every minute through output channels. The active and reactive
maximum power demand values are calculated for both forward and reverse direction and these
values can be reset with RSTDMD input.

14.2.3 Function block SEMOD175502-4 v5

ETPMMTR
P* ACCINPRG
Q* EAFPULSE
STARTACC EARPULSE
STOPACC ERFPULSE
RSTACC ERRPULSE
RSTDMD EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD

IEC14000019-1-en.vsd
IEC14000019 V1 EN-US

Figure 329: ETPMMTR function block

14.2.4 Signals
PID-6872-INPUTSIGNALS v3

Table 524: ETPMMTR Input signals

Name Type Default Description


P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STARTACC BOOLEAN 0 Start to accumulate energy values
STOPACC BOOLEAN 0 Stop to accumulate energy values.
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading

PID-6872-OUTPUTSIGNALS v3

Table 525: ETPMMTR Output signals

Name Type Description


ACCINPRG BOOLEAN Accumulation of energy values in progress
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in set interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in set interval
Table continues on next page

Transformer protection RET650 585


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 14 1MRK504170-UEN Rev. J
Metering

Name Type Description


ERFALM BOOLEAN Alarm for reactive forward energy exceed limit in set interval
ERRALM BOOLEAN Alarm for reactive reverse energy exceed limit in set interval
EAFACC REAL Accumulated forward active energy value
EARACC REAL Accumulated reverse active energy value
ERFACC REAL Accumulated forward reactive energy value
ERRACC REAL Accumulated reverse reactive energy value
MAXPAFD REAL Maximum forward active power demand value for set interval
MAXPARD REAL Maximum reverse active power demand value for set interval
MAXPRFD REAL Maximum forward reactive power demand value for set interval
MAXPRRD REAL Maximum reverse reactive power demand value for set interval

14.2.5 Settings
PID-6872-SETTINGS v3

Table 526: ETPMMTR Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
EnaAcc Off - - Off Activate the accumulation of energy
On values
tEnergy 1 Minute - - 1 Minute Time interval for energy calculation
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls 0.100 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in
secs
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value

Table 527: ETPMMTR Non group settings (advanced)

Name Values (Range) Unit Step Default Description


EALim 0.001 - MWh 0.001 1000000.000 Active energy limit
10000000000.000
ERLim 0.001 - MVArh 0.001 1000.000 Reactive energy limit
10000000000.000
EnZeroClamp Off - - On Enable of zero point clamping detection
On function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
Table continues on next page

586 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 14
Metering

Name Values (Range) Unit Step Default Description


DirEnergyAct Forward - - Forward Direction of active energy flow Forward/
Reverse Reverse
DirEnergyReac Forward - - Forward Direction of reactive energy flow Forward/
Reverse Reverse
EAFPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for forward active
100000000.000 energy
EARPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for reverse active
100000000.000 energy
ERFPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for forward reactive
100000000.000 energy
ERRPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for reverse reactive
100000000.000 energy

14.2.6 Monitored data


PID-6872-MONITOREDDATA v3

Table 528: ETPMMTR Monitored data

Name Type Values (Range) Unit Description


EAFACC REAL - MWh Accumulated forward active energy value
EARACC REAL - MWh Accumulated reverse active energy value
ERFACC REAL - MVArh Accumulated forward reactive energy
value
ERRACC REAL - MVArh Accumulated reverse reactive energy
value
MAXPAFD REAL - MW Maximum forward active power demand
value for set interval
MAXPARD REAL - MW Maximum reverse active power demand
value for set interval
MAXPRFD REAL - MVAr Maximum forward reactive power demand
value for set interval
MAXPRRD REAL - MVAr Maximum reverse reactive power demand
value for set interval

14.2.7 Operation principle GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v4

The instantaneous output values of active and reactive power from the Measurements function
CVMMXN are used and integrated over a selected time tEnergy to measure the integrated energy.
Figure 330 shows the overall functionality of the energy calculation and demand handling function
ETPMMTR.

Transformer protection RET650 587


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 14 1MRK504170-UEN Rev. J
Metering

MAXPAFD
RSTDMD
MAXPARD
MAXPRFD
P
MAXPRRD
Zero Clamping Maximum Power
EAFALM
Detection Demand Calculation
Q EARALM
ERFALM
ERRALM

ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
Energy Accumulation ERRPULSE
STARTACC
Calculation EAFACC
EARACC
STOPACC
ERFACC
ERRACC
RSTACC

IEC13000185-2-en.vsd
IEC13000185 V2 EN-US

Figure 330: ETPMMTR Functional overview logical diagram


The integration of energy values is enabled by the setting EnaAcc and controlled by the STARTACC
and STOPACC inputs. If the integration is in progress, the output ACCINPRG is high. Otherwise, it is
low. Figure 331 shows the logic of the ACCINPRG output. ACCINPRG is active when the STARTACC
input is active and the EnaAcc setting is enabled. When the RSTACC input is in the active state, the
output ACCINPRG is low even if the integration of energy is enabled. ACCINPRG is deactivated by
activating the STOPACC input.

STOPACC

FALSE
STARTACC T
³1
& F ACCINPRG
EnaAcc &

q-1

RSTACC

q-1 = unit delay IEC13000186-4-en.vsd


IEC13000186 V4 EN-US

Figure 331: ACCINPRG Logic diagram


The accumulated energy values (in MWh and MVArh) are available as service values and also as
pulsed output depending on the ExxAccPlsQty setting, which can be connected to a pulse counter.
Accumulated energy outputs are available for forward as well as reverse direction. The accumulated
energy values can be reset to initial accumulated energy values (ExxPrestVal) from the local HMI
reset menu or with the input signal RSTACC. Figure 332 shows the logic for integration of energy in
active forward direction. Similarly, the integration of energy in active reverse, reactive forward and
reactive reverse is done.

588 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 14
Metering

RSTACC

EAFPrestVal

ACCINPRG

P* (ACTIVE FORWARD)
X
 T
T EAFACC
60.0
F
F

&

q-1

1000 GWh T
-1 F
q 0.0

a
a>b
b
-1
q = unit delay
IEC13000187-5-en.vsdx
IEC13000187 V5 EN-US

Figure 332: Logic for integration of active forward energy


The energy pulses generated by using internally calculated accumulated energy values and energy
per pulse (ExxAccPlsQty) setting. The accumulated energy values are divided by the energy-per-
pulse value to get the number of pulses. The number of pulses can be reset to zero by activating
RSTACC input or by using the local HMI reset menu. The pulse on and off time duration is set by the
settings tEnergyOnPls and tEnergyOffPls. Figure 333 shows the logic for pulse output generation for
the integrated energy in the active forward direction. Similarly, the pulse generation for integrated
energy in the active reverse, reactive forward and reactive reverse is done.

tEnergyOffPls
EAFACC

a Counter q-1
a>b CU
1000 GWh b CV
Rst
tOff
t
R I q-1

0
÷ X
 R I T
EAFPULSE
a TP
a>b F
b
EAFAccPlsQty ÷ 0
Counter
CU
CV
RSTACC
Rst

q-1

tEnergyOnPls

q-1 = unit delay


IEC13000188-5-en.vsdx
IEC13000188 V5 EN-US

Figure 333: Logic for pulse generation of integrated active forward energy
The maximum demand values for active and reactive power are calculated for the set time interval
tEnergy. The maximum values are updated every minute and stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD and MAXPRRD for the active and

Transformer protection RET650 589


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 14 1MRK504170-UEN Rev. J
Metering

reactive power forward and reverse direction. When the RSTDMD input is active from the local HMI
reset menu, these outputs are reset to zero. The energy alarm is activated once the periodic energy
value crosses the energy limit ExLim. Figure 334 shows the logic of alarm for active forward energy
exceeds limit and Maximum forward active power demand value. Similarly, the maximum power
calculation and energy alarm outputs in the active reverse, reactive forward and reactive reverse is
implemented.

P (ACTIVE FORWARD)
Average Power
X a EAFALM
tEnergy Calculation a>b
b

EALim

RSTMAXD

0.0 T MAXPAFD
MAX F

q-1
q-1 = unit delay
IEC13000189-4-en.vsd
IEC13000189 V4 EN-US

Figure 334: Logic for maximum power demand calculation and energy alarm

14.2.8 Technical data


SEMOD153707-2 v7

Table 529: ETPMMTR technical data

Function Range or value Accuracy


Active Energy, Wp (10 to 300) V ±1.0% of Wp
(Export/Import) (0.1-4.0) x Ir
at unity power factor
Reactive Energy, Wq (10 to 300) V ±1.0% of Wq
(Export/Import) (0.1-4.0) x Ir
at zero power factor
Maximum power demand (10 to 300) V ±1.0% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±1.0% of S at S > 0.5 x Sr

590 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

Section 15 Ethernet
15.1 Access point

15.1.1 Introduction GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v4

An access point is an Ethernet communication interface for single or redundant station


communication. Each access point is allocated with one physical Ethernet port, two physical Ethernet
ports (marked A and B) are allocated if redundant communication is activated for the access point.

Device 1 Device 1

AP1 AP2 AP3 AP1 AP2 AP3


SFP_301 SFP_302
SFP_301 SFP_302 SFP_303 A B SFP_303

IEC16000092-2-en.vsdx
IEC16000092 V2 EN-US

Figure 335: Access points, non redundant (left) and redundant communication (right)

15.1.2 Settings
PID-8307-SETTINGS v1

Table 530: AP_1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation on/off of the access point
On
Redundancy None - - None Ethernet redundancy mode
PRP-0
PRP-1
HSR
RSTP
IPAddress 0 - 18 IP 1 192.168.1.10 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 Station bus User editable access point description
[1-18 char]
PTP Off - - Off Precision time protocol
On
Slave only
PTPVLANTag 0 - 4095 - 1 0 PTP VLAN identifier [0-4095]
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
DNP3 Off - - On DNP3 slave
On
SNTPServer Off - - On SNTP server
On
Table continues on next page

Transformer protection RET650 591


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

Name Values (Range) Unit Step Default Description


FSTAccess Off - - On Field Service Tool access
On
C37.118TCP Off - - On IEEE 1344 and C37.118 TCP server
On
C37.118UDP1 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP2 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP3 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP4 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP5 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
C37.118UDP6 Off - - On IEEE 1344 and C37.118 UDP stream and
On the TCP control server
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address
RIA600 Off - - On Remote IED Access
On
SNMP Off - - On SNMP server
On

MANUALPID-17002 v1

Table 531: AP_FRONT Non group settings (basic)

Name Values (Range) Unit Step Default Description


IPAddress 0 - 18 IP 1 10.1.150.3 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 FrontPort User editable access point description
[1-18 char]
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
SNTPServer Off - - On SNTP Server
On
FSTAccess Off - - On Field Service Tool access
On
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address

15.2 Access point diagnostics

15.2.1 Functionality GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v4

The access point diagnostics function blocks (RCHLCCH, SCHLCCH and FRONTSTATUS)
supervise communication. SCHLCCH is used for communication over the rear Ethernet ports,
RCHLCCH is used for redundant communications over the rear Ethernet ports and FRONTSTATUS

592 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

is used for communication over the front port. All access point function blocks include output signal
for denial of service. To get this denial of service, that is reported on the communication, the
DOSALARM output from these blocks must be connected to a communication function.

For RSTP, the frame error rate on an individual link cannot be extrapolated accurately to
that of which is received by the IED. Hence, the frame error rate on link A (LCCH.FerCh)
and the frame error rate on link B (LCCH.RedFerCh) cannot be calculated and are 0
always.

15.2.2 Function block GUID-727BF536-1D60-4060-A674-5D73F252CCB7 v2

SCHLCCH
LINKUP
DOSALARM
IEC16000044 V2 EN-US

Figure 336: SCHLCCH Function block

RCHLCCH
REDLINKA
REDLINKB
DOSALARM
IEC16000045 V2 EN-US

Figure 337: RCHLCCH Function block

15.2.3 Signals
PID-6818-OUTPUTSIGNALS v2

Table 532: SCHLCCH Output signals

Name Type Description


LINKUP BOOLEAN Access point link status
DOSALARM BOOLEAN Denial of service alarm

PID-6819-OUTPUTSIGNALS v2

Table 533: RCHLCCH Output signals

Name Type Description


REDLINKA BOOLEAN Channel A redundancy status
REDLINKB BOOLEAN Channel B redundancy status
DOSALARM BOOLEAN Denial of service alarm (A + B)

15.2.4 Monitored data


PID-6818-MONITOREDDATA v2

Table 534: SCHLCCH Monitored data

Name Type Values (Range) Unit Description


GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

Transformer protection RET650 593


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

PID-6819-MONITOREDDATA v2

Table 535: RCHLCCH Monitored data

Name Type Values (Range) Unit Description


GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

15.3 Redundant communication

15.3.1 Identification
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
IEC 62439-3 Parallel redundancy PRP - -
protocol
IEC 62439-3 High-availability seamless HSR - -
redundancy
Access point diagnostic for redundant RCHLCCH - -
Ethernet ports

15.3.2 Functionality GUID-494FACF7-4BE0-4B9F-A18F-47CD1E92C0F9 v3

PRP IEC 62439-3 redundant communication


Redundant communication according to IEC 62439-3 Edition 1, PRP-0, and IEC 62439-3 Edition 3,
PRP-1, parallel redundancy protocol (PRP) is available as an option when ordering IEDs. PRP
according to IEC 62439-3 uses two optical/Galvanic(RJ45) Ethernet ports.

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


Redundant station bus communication according to IEC 62439-3 Edition 3, High-availability
seamless redundancy (HSR) is available as an option when ordering IEDs. Redundant station bus
communication according to 62439-3 uses two optical Ethernet ports.

15.3.3 Operation principle GUID-73DB23CD-A924-4B89-8AAB-1E79D44DE429 v1

PRP IEC 62439-3 redundant communication


The communication is performed in parallel, that is the same data package is transmitted on both
channels simultaneously. The received package identity from one channel is compared with data
package identity from the other channel, if they are the same, the last package is discarded.

The RCHLCCH function block supervise the redundant communication on the two channels. If no
data package has been received on one (or both) channels within the last 10 s, the output LinkAUp
and/or LinkBUp is set to 0 which indicates an error.

594 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

Switch A Switch B

PhyPortA PhyPortB PhyPortA PhyPortB


AP1 AP1

Device 3 Device 4

IEC09000758 V5 EN-US

Figure 338: Redundant station bus

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


HSR applies the principle of parallel operation to a single ring.

For each message sent, the node sends two frames, one through each port. Both the frames
circulate in opposite directions over the ring. Every node forwards the frames it receives from one
port to another to reach the next node. When the originating sender node receives the frame it sent,
the sender node discards the frame to avoid loops

The RCHLCCH function block supervise the redundant communication on the two channels. If no
data package has been received on one (or both) channels within the last 10 s, the output LinkAUp
and/or LinkBUp is set to 0 which indicates an error.

If IEEE1588 (PTP) is used an accuracy of 1 µs can be guaranteed for up to 15 devices in one HSR-
ring.

Transformer protection RET650 595


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

PhyPortB PhyPortA PhyPortB PhyPortA


AP1 AP1

Device 3 Device 4

IEC16000038 V2 EN-US

Figure 339: HSR ring

15.4 Rapid spanning tree protocol (RSTP)

15.4.1 Introduction GUID-A065494F-F472-4177-A93F-D5FDF49B414F v1

Rapid Spanning Tree Protocol (RSTP) is a network protocol built for loop free network topology and
redundancy/backup connections between switches.

• Support for RSTP will be available on the Station level network communication.
• RSTP will only be available on the Access Point (AP) AP1 or AP3. AP1 uses port 1 and port 2;
AP3 uses port 3 and port 4.
• RSTP will not be available on Optical Ethernet Module (OEM02) hardware (that is, on interface
AP5).
• RSTP can be configured using Ethernet configuration tool (ECT) and PST in PCM600.

15.4.2 Configuring RSTP in the IED GUID-D6BC55E2-9652-4A53-BCEA-B7352DFC8BCC v2

Access points can be configured to use the RSTP using ECT in PCM600. Either AP1 or AP3 can be
configured with RSTP and not both at the same time. ECT will not allow the RSTP on another AP if
RSTP is already configured on any of the APs. Settings related to the RSTP are available under PST
in PCM600 or on LHMI (under Configuration menu/Communication/Ethernet Configuration/
RSTP).

596 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

GUID-B6D6F552-B316-4B31-A93A-89C7CC9E96C0 V1 EN-US

Figure 340: AP1 configured with RSTP

GUID-44BD3474-C865-4CE2-8198-030AF1753ADF V1 EN-US

Figure 341: AP3 configured with RSTP

RSTP will only be available either on the Access Point, AP 1 or AP 3. AP1 uses port 1
and port 2; AP3 uses port 3 and port 4.

When any of the Access Point is configured with RSTP or changed from RSTP, the IED
will reboot to load the new ethernet configuration.

The IED will display hints on LHMI if any error in the configuration is detected.

For IEC 61850 ED2, the new sub-network can be changed but it is recommend to
configure all the devices in a ring to the same access point. Due to a limitation in ECT, it
does not allow to edit the subnet for WA1 because it is dedicated to a station bus access
point, and AP1 is configured by default in the IED SCL model.

Transformer protection RET650 597


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

15.4.3 RSTP parameters


MANUALPID-21001 v1

Table 536: RSTPCONFIG Non group settings (basic)

Name Values (Range) Unit Step Default Description


BridgePriority 0 - 61440 - 4096 32768 Priority of the bridge
Port1Priority 0 - 240 - 16 128 Priority of port1
Port2Priority 0 - 240 - 16 128 Priority of port2
HelloTime 1-2 s 1 2 Time interval in seconds for HelloTime
(BPDU) messages
MaxAge 6 - 40 - 1 20 Maximum age to wait for Hello messages
ForwardDelay 4 - 30 s 1 15 Time needed for the port to change its
state from blocking to forwarding
AutoEdgePort1 Off - - Off Auto edge port detection on Port1
On
AutoEdgePort2 Off - - Off Auto edge port detection on Port2
On

GUID-10173961-FCCC-4EEE-9848-0D0DAA3649F1 v1
Changes to parameters, such as priority of the bridge/ports, can result in reconfiguration of RSTP in
the network. It is recommended to use the default values of the RSTP parameters.

15.4.4 Supported network topologies GUID-A3596B3C-AA6B-4234-B3E7-515648C57BC4 v1

All the devices in the network must support RSTP. Before configuring RSTP, the network topology
should be carefully planned by the network administrator. The administrator should determine which
switch will be the root bridge and configure the switches or devices (IED) appropriately (see Section
15.4.5).

If the root bridge is down, the protocol automatically assigns a new root bridge based on
BridgePriority, switch/device with the lowest priority will be considered as the root bridge. The
network configuration, that is, bridge priorities, must be configured such that the redundant switch if
any takes over as the root bridge if the first root bridge is out-of-service.

If all the devices in the network have the same BridgePriority, such as the default priority, and the
root bridge goes down, a tie situation arises, and the protocol will assign a device as the root bridge
based on the lowest MAC address.

In any kind of network topology, the configuration must be done such that the switch is
used as the root bridge.

Once the device have been assigned a bridge priority, the best path to the root bridge is calculated
based on the path cost and port priority. The path cost is determined based on the bandwidth of a
link, however, links between switches or IEDs may have the same bandwidth. The bandwidth
supported by the IED is 100 Mbps. This cannot be configured by the user.

The selection of how other switches/IEDs in the topology choose their root port, or the least cost path
to the root bridge, can be influenced by the port priority. The highest priority means the path will
ultimately be less preferred. If all ports of a switch have the same priority, the port with the lowest
number (port number) is chosen to forward frames.

15.4.4.1 Star topology GUID-82CED5AD-2A92-432A-8D79-AD64969F00BD v1

In star topology, the IED is connected to two different switches. Switch Sw1 should be configured as
the root bridge. In this case, all the IEDs will communicate with Sw1; only in case of a link failure or
other failure in the switch, the redundant link will be activated. With this topology, RSTP can only be

598 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

used for attaining the redundancy. In case of failure of main link, the backup link will be activated and
the IED will receive messages from Sw1 through Sw2.

IEC21000009 V2 EN-US

Figure 342: Star topology

15.4.4.2 Ring and star topology GUID-2EC678AE-F26E-4999-80AF-5725B6D6DEDB v1

In ring and star topology, switches are connected in ring and devices are connected in star topology.
The IED is connected to two different switches. Switch Sw1 (or Sw2) should be configured as the
root bridge.

In this case, all the IEDs will communicate with Sw1; only in case of a link failure or other failure in
the switch Sw1 the redundant link via Sw2 will be activated.

IEC21000005 V2 EN-US

Figure 343: Ring and star topology

15.4.4.3 Ring topology GUID-2035405C-3BA7-4360-B4A0-CB5ECCE5EE15 v2

In ring topology, IEDs and switch are connected to form a ring. Ring is the most preferred topology
with RSTP. In Figure 344, switch Sw1 is the root bridge, if the priority of Sw2 is greater than that of

Transformer protection RET650 599


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

the IEDs, then the alternate port (backup link) will be placed between IED3 and IED4 (for
representation and this depends on the configuration).

If any of the link breaks in the loop, then the backup link/alternate link will be activated. For example,
if a link between IED1 and IED2 fails, then the alternate link is activated after the recovery time; all
the devices in the ring will communicate with the new alternate link established. In the example
topology, after the recovery time, IED2 and IED3 will now communicate in the ring through IED4.

IEC21000008 V2 EN-US

Figure 344: Ring topology, single ring


In the topology shown in Figure 345, there are three rings, Sw1 to Sw4 form one ring, Sw1- Sw2-
IED4 to IED1 forms the second ring, Sw3-Sw4-IED8 to IED5 forms the third ring. If the root port is
Sw1 and if the priority of other switches is lesser than that of the IEDs, then the alternate port or the
backup link could be between Sw3 and Sw4, IED3-IED4, IED7-IED8 (for representation and this
depends on the configuration).

IEC21000006 V2 EN-US

Figure 345: Ring topology, three rings


In the topology shown in Figure 346, there are five rings. Sw1 to Sw4 forms one ring, Sw1-Sw2-IED4
to IED1 forms the second ring, Sw1-Sw2-IED8 to IED5 forms the third ring, Sw3-Sw4-IED12 to IED9
forms the fourth ring, and Sw3-Sw4-IED16 to IED13 forms the fifth ring. If the root port is Sw1 and if
the priority of other switches is lesser than that of the IEDs, then the alternate port or the backup link
could be between Sw3 and Sw4, IED3-IED4, IED7-IED8, IED11-IED12, IED15-IED16 (for
representation and this depends on the configuration).

600 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

IEC21000007 V2 EN-US

Figure 346: Ring topology with multiple rings

15.4.5 RSTP status GUID-8D473FBD-7022-4B94-8455-5252C2EBA225 v1

Depending on the configuration, the diagnostics information related to RSTP would be available
under Test/Function status/Communication/Station communication/RSTPDiagnostics/
RSTPSTATUS on LHMI.

Table 537: RSTP status

Name Type Values (Range) Default Description


ACCESSPOINT INTEGER 0=Off Off Access points on which
1=AP1 RSTP is active
2=AP3
BRIDGEPRIORITY - - 32768 Priority of the bridge
BRIDGEMAC - MAC address -- MAC of the bridge
PORT1STATUS INTEGER 0=Disabled -- Status of Port1
1=Blocking
2=Learning
3=Forwarding
4=Listening
PORT1ROLE INTEGER 0=Disabled -- Role of Port1
1=Root
2=Designated
3=Alternate
4=Backup
PORT1COST - - 0 Determined port1 cost
based on link speed
PORT2STATUS INTEGER 0=Disabled -- Status of Port2
1=Blocking
2=Learning
3=Forwarding
4=Listening
PORT2ROLE INTEGER 0=Disabled -- Role of Port2
1=Root
2=Designated
3=Alternate
4=Backup
PORT2COST - - 0 Determined port2 cost
based on link speed

Transformer protection RET650 601


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

15.4.6 Performance measurements GUID-E9DD125E-7EDF-4964-A4B5-3075DD1826F8 v1

The test setup consisted of IEDs and a switch in a ring, and UDP multicast frames were sent at 5 ms
interval to measure the single link failure recovery time.

Table 538 lists the results of the measurements.

Table 538: Performance measurements

Protocol Topology Recovery time from single link failure


9 IEDs + 1 Switch 39 IEDs + 1 switch
RSTP (802.1D – 2004) Ring < 45 ms < 185 ms

The recovery time of a link failure on RSTP with the IEDs that are using Galvanic ports is
higher than the IEDs with the Optical ports.

15.4.7 Reset to factory defaults GUID-13F6F3BF-1621-41E0-A422-C2B6BA3F5A1E v1

If a reset to factory default is performed on an IED with RSTP, then the IED will be reverted to the
factory settings with default values and RSTP will be disabled.
GUID-D4AFB582-036A-4A98-88A5-40884091AFD7 v1

Table 539: RSTP technical data

Function Value
Protocol IEEE 802.1D Rapid spanning tree protocol (RSTP)
Communication speed 100Base-FX
Connectors Optical, type LC or Galvanic, type RJ45
Supported topologies Star, Ring, Ring and star
Maximum number of 39 IEDs
nodes in a ring
Performance Recovery time from single link failure for 9 IEDs + 1 switch is < 45 ms and for 39 IEDs + 1
measurements switch is < 185 ms in ring topology

15.5 Merging unit

15.5.1 Introduction GUID-E630C16F-EDB8-40AE-A8A2-94189982D15F v1

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to communicate
with devices providing measured values in digital format, commonly known as Merging Units (MU).
The rear access points are used for the communication.

The merging units (MU) are called so because they can gather analog values from one or more
measuring transformers, sample the data and send the data over process bus to other clients (or
subscribers) in the system. Some merging units are able to get data from classical measuring
transformers, others from non-conventional measuring transducers and yet others can pick up data
from both types.

602 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

15.5.2 Settings
PID-8088-SETTINGS v1

Table 540: MU1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


APConnection None - - None Access point connection for the merging
AP1 unit
AP2
AP3
AP4
SvCBRef 0 - 39 - 1 Reference to the subscribed SV control
block [0-39 char]

PID-7549-SETTINGS v1

Table 541: MU1_HW Non group settings (basic)

Name Values (Range) Unit Step Default Description


CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

15.5.3 Monitored data


PID-7549-MONITOREDDATA v1

Table 542: MU1_HW Monitored data

Name Type Values (Range) Unit Description


MUDATA BOOLEAN 0=Ok - Fatal error, serious data loss
1=Error
SYNCH BOOLEAN 0=Ok - MU clock synchronized to same clock as
1=Error IED
SMPLLOST BOOLEAN 0=No - Sample lost
1=Yes
MUSYNCH BOOLEAN 0=Ok - Synchronization lost in MU
1=Error
TESTMODE BOOLEAN 0=No - MU in test mode
1=Yes
SIMMODE BOOLEAN 0=No - Simulation mode
1=Yes
BadReference BOOLEAN 0=No - BadReference indication output for I1
1=Yes
Derived BOOLEAN 0=No - Derived indication output for I1
1=Yes
Failure BOOLEAN 0=No - Failure indication output for I1
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for I1
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for I1
1=Yes
OldData BOOLEAN 0=No - OldData indication output for I1
1=Yes
Table continues on next page

Transformer protection RET650 603


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

Name Type Values (Range) Unit Description


OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for I1
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for I1
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for I1
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for I1
1=Yes
Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 0=No - Test indication output for I1
1=Yes
Validity INTEGER 0=Good - Validity indication output I1
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for I2
1=Yes
Derived BOOLEAN 0=No - Derived indication output for I2
1=Yes
Failure BOOLEAN 0=No - Failure indication output for I2
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for I2
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for I2
1=Yes
OldData BOOLEAN 0=No - OldData indication output for I2
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for I2
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for I2
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for I2
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for I2
1=Yes
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 0=No - Test indication output for I2
1=Yes
Validity INTEGER 0=Good - Validity indication output I2
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for I3
1=Yes
Derived BOOLEAN 0=No - Derived indication output for I3
1=Yes
Failure BOOLEAN 0=No - Failure indication output for I3
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for I3
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for I3
1=Yes
Table continues on next page

604 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

Name Type Values (Range) Unit Description


OldData BOOLEAN 0=No - OldData indication output for I3
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for I3
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for I3
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for I3
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for I3
1=Yes
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 0=No - Test indication output for I3
1=Yes
Validity INTEGER 0=Good - Validity indication output I3
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for I4
1=Yes
Derived BOOLEAN 0=No - Derived indication output for I4
1=Yes
Failure BOOLEAN 0=No - Failure indication output for I4
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for I4
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for I4
1=Yes
OldData BOOLEAN 0=No - OldData indication output for I4
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for I4
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for I4
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for I4
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for I4
1=Yes
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 0=No - Test indication output for I4
1=Yes
Validity INTEGER 0=Good - Validity indication output I4
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for U1
1=Yes
Derived BOOLEAN 0=No - Derived indication output for U1
1=Yes
Failure BOOLEAN 0=No - Failure indication output for U1
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for U1
1=Yes
Table continues on next page

Transformer protection RET650 605


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 0=No - Inconsistent indication output for U1
1=Yes
OldData BOOLEAN 0=No - OldData indication output for U1
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for U1
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for U1
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for U1
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for U1
1=Yes
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 0=No - Test indication output for U1
1=Yes
Validity INTEGER 0=Good - Validity indication output U1
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for U2
1=Yes
Derived BOOLEAN 0=No - Derived indication output for U2
1=Yes
Failure BOOLEAN 0=No - Failure indication output for U2
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for U2
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for U2
1=Yes
OldData BOOLEAN 0=No - OldData indication output for U2
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for U2
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for U2
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for U2
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for U2
1=Yes
Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 0=No - Test indication output for U2
1=Yes
Validity INTEGER 0=Good - Validity indication output U2
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for U3
1=Yes
Derived BOOLEAN 0=No - Derived indication output for U3
1=Yes
Failure BOOLEAN 0=No - Failure indication output for U3
1=Yes
Table continues on next page

606 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 15
Ethernet

Name Type Values (Range) Unit Description


Inaccurate BOOLEAN 0=No - Inaccurate indication output for U3
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for U3
1=Yes
OldData BOOLEAN 0=No - OldData indication output for U3
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for U3
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for U3
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for U3
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for U3
1=Yes
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 0=No - Test indication output for U3
1=Yes
Validity INTEGER 0=Good - Validity indication output U3
1=Invalid
2=Reserved
3=Questionable
4=Not Used
BadReference BOOLEAN 0=No - BadReference indication output for U4
1=Yes
Derived BOOLEAN 0=No - Derived indication output for U4
1=Yes
Failure BOOLEAN 0=No - Failure indication output for U4
1=Yes
Inaccurate BOOLEAN 0=No - Inaccurate indication output for U4
1=Yes
Inconsistent BOOLEAN 0=No - Inconsistent indication output for U4
1=Yes
OldData BOOLEAN 0=No - OldData indication output for U4
1=Yes
OperatorBlocked BOOLEAN 0=No - OperatorBlocked indication output for U4
1=Yes
Oscillatory BOOLEAN 0=No - Oscillatory indication output for U4
1=Yes
OutOfRange BOOLEAN 0=No - OutOfRange indication output for U4
1=Yes
Overflow BOOLEAN 0=No - Overflow indication output for U4
1=Yes
Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 0=No - Test indication output for U4
1=Yes
Validity INTEGER 0=Good - Validity indication output U4
1=Invalid
2=Reserved
3=Questionable
4=Not Used

Transformer protection RET650 607


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15 1MRK504170-UEN Rev. J
Ethernet

15.6 Routes

15.6.1 Introduction GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v2

A route is a specified path for data to travel between the source device in a subnetwork to the
destination device in a different subnetwork. A route consists of a destination address and the
address of the gateway to be used when sending data to the destination device, see Figure 347.

Default gateway

Gateway

Source Destination
IEC16000095 V2 EN-US

Figure 347: Route from source to destination through gateway

15.6.2 Settings
PID-6761-SETTINGS v2

Table 543: ROUTE_1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation on/off of the route
On
IPAddress 0 - 18 IP 1 0.0.0.0 IP address of the gateway
Address
DestIPAddress 0 - 18 IP 1 0.0.0.0 Destination IP address
Address
DestSubnetMask 0 - 18 IP 1 255.255.255.255 Destination IP subnet mask
Address
Name 1 - 18 - 1 Route1 User configurable name of the route [1-18
char]

15.6.3 Monitored data


PID-6761-MONITOREDDATA v2

Table 544: ROUTE_1 Monitored data

Name Type Values (Range) Unit Description


RouteConfig INTEGER 0=Ok - Route configuration status
1=Error
-1=Off

608 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Section 16 Station communication


16.1 Communication protocols M14815-3 v16

Each IED is provided with several communication interfaces enabling it to connect to one or many
substation level systems or equipment, either on the Substation Automation (SA) bus or Substation
Monitoring (SM) bus.

Available communication protocols are:

• IEC 61850-8-1 communication protocol


• IEC/UCA 61850-9-2LE communication protocol
• LON communication protocol
• SPA communication protocol
• IEC 60870-5-103 communication protocol
• Syslog (RFC 5424) standard

Several protocols can be combined in the same IED.

The LPHD.PhyHealth reflects the physical health of the IED. The status is set to Alarm
when there is an internal failure in the IED or Warning if any active communication link
fails.

16.2 Communication protocol diagnostics GUID-6BC4671F-6D06-4BBD-B1FF-2F03FF16A856 v1

Status of the protocols can be viewed in the LHMI under Main menu /Diagnostics /IED status /
Protocol diagnostics. The diagnostic values are:

Diagnostic value Description


Off Protocol is turned off
Error An error has occured, refer to event list for more
information
Warning Configuration inconsistency. Unable to locate data point.
Ready Protocol is ready

Transformer protection RET650 609


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

IEC15000400 V2 EN-US

Figure 348: Protocol diagnostic screen in LHMI

16.3 Simple Network Management Protocol (SNMP) GUID-D8409938-380E-4393-A271-423C311B089C v1

16.3.1 Introduction GUID-B03C5450-3659-4D62-B439-EAEB93F3D402 v1

Simple Network Management Protocol (SNMP) is an internet standard protocol to get and set data of
the connected network devices. It uses UDP protocol for communication.

Here it is used to provide information of the hardware devices, software and attached network
interface to the SNMP manager.

The SNMP agent supports the following,

1. SNMPv2c and SNMPv3 are supported and both are enabled by default.
1.1. SNMPv2c sends community strings which are used for authentication in clear text format.
1.2. User based security model (USM) for SNMPv3 require the users/ password and the
encryption password to be predefined. A maximum of 2 users are supported.
2. Public IF-MIB and Hitachi Energy MIB with specific objects (Object Identifiers) are supported.
3. User profiles can be configured from the PCM600 tool and only these users are supported for
SNMP communication.
4. Traps are not supported.

16.3.1.1 Configuration of SNMP parameters GUID-3F498071-09A8-4F9C-AEBB-964A5DF63DD2 v1

SNMP parameters can be configured from the PCM600 tool.

610 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Enabling the SNMP server for the Access points GUID-29934241-FF83-4506-A936-44A14A867E2F v1


From the ECT tool in PCM600, enable the SNMP server support for the each access point that are
supporting the SNMP communication

GUID-191FB872-2134-411E-905F-2CDF232E657F V1 EN-US

Figure 349: SNMP server enabled for all access points

Configuration of SNMP parameters GUID-F2DFC93F-FD94-4BF9-8122-6B716E0B9AD9 v1


SNMP parameters are set in Parameter Setting tool (PST) of PCM600. The parameters could be
found under IED Configuration/ Ethernet Configuration.

There is one component for the server configuration and two components for the different users
configuration.

Errors in configuring the SNMP parameters will be shown as a hint in LHMI.

GUID-A0899C80-FB05-41AA-AE79-B3D21C07DC4D V1 EN-US

Figure 350: SNMP parameters table in PCM600 tool

SNMP Server Parameters GUID-0E9069DB-1311-406C-9A36-88C22D88DAA9 v1


SNMP server parameters configured from the PCM600 are needed for SNMPv2c support.

Table 545 shows the SNMP server parameters that are to be configured.

Settings PID-8317-SETTINGS v1

Transformer protection RET650 611


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Table 545: SNMPSERVERCONF Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation
On
ROCommunity 0 - 32 - 1 Read-only community
RWCommunity 0 - 32 - 1 Read-write community
Location 0 - 32 - 1 Location of the system
Contact 0 - 32 - 1 Contact person
SystemName 0 - 32 - 1 Name of the system

Setting Guidelines GUID-0090546F-C881-4C3F-AEF9-94E36D8AE8EC v1


Operation: Default value is Off. This must be set to On to start the SNMP server in the IED.

Minimum configuration to start SNMP is to make SNMP server parameter Operation to


"ON" and fill ROCommunity value with some valid string.

ROCommunity: This information is need by SNMP manager to get read-only Object Identifiers from
SNMP agent/IED using SNMPv2c protocol. This information is mandatory for SNMPv2c protocol.

RWCommunity: This information is need by SNMP manager to get and set Object Identifiers from
SNMP agent/IED using SNMPv2c protocol. This information is mandatory for SNMPv2c protocol.

Location, Contact and SystemName parameters are system general information.

If SNMP server parameters are not configured, then the SNMP engineID parameter will
be empty.

Below is the snapshot of the server parameters from PCM600 tool

GUID-A6B6C5F6-997C-4172-95D6-C84BA43B4FFA V1 EN-US

Figure 351: SNMP server parameters configuration from PCM600

SNMP User Parameters GUID-16B9CC9A-727D-440D-92B7-1F336B02C110 v1


SNMP user parameters configured from the PCM600 are needed for SNMPv3 support.

Maximum of 2 user profiles are supported.

612 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

• The user definition for SNMP includes username and password. The password and the
encryption key will only support ASCII characters. Any password policies will not be enforced.
• Password parameters will have the PAD lock, so they need to be unlocked to be written.
• Password parameters are hidden (shown in the Figure 352).
• Minimum password length supported for the user configurations is 8 characters and maximum is
62 characters.
• Based on the security level parameter the respective parameters need to be updated.

For security level NoAuthNoPriv Only Username can be modified.


For security level AuthNoPriv Username, Authentication protocol and Authentication password can
be modified.
For security level AuthPriv Username, Authentication protocol, Authentication password,
Encryption type and Encryption key can be modified.

GUID-76F7BBA7-3FEC-4C57-857C-42DDC098E451 V1 EN-US

Figure 352: SNMP user parameters configuration from PCM600


Table 2 shows the SNMP User parameters that are to be configured.

Settings PID-8318-SETTINGS v1

Table 546: SNMPUSERCONF Non group settings (basic)

Name Values (Range) Unit Step Default Description


UserName 0 - 32 - 1 User name
Privileges Read-only - - Read-only Privileges on user
Read-write
SecurityLevel NoAuthNoPriv - - NoAuthNoPriv Security level for the user
AuthNoPriv
AuthPriv
AuthProtocol SHA - - None Authentication protocol
SHA224
SHA256
SHA384
SHA512
None
AuthPassword 0 - 62 - 1 Authentication password
EncType AES - - None Encryption type
AES128
AES192
AES192C
AES256
AES256C
None
EncKey 0 - 62 - 1 Encryption key

User information is needed for SNMPv3.

Transformer protection RET650 613


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

SNMP EngineID GUID-4A77A940-5178-4A60-9723-CE32BC6D585C v1


SNMP EngineID is unique for each IED. The unique engineID is generated using the front port MAC
address of the IED. The generated EngineID is shown under IED Summary in PCM600 tool. If SNMP
is not started, then the SNMP EngineID parameter will be empty

GUID-FFD0764F-95B0-4722-AB27-5D34C284FFBA V1 EN-US

Figure 353: Generated EngineID information in PCM600 tool

16.3.1.2 Object Identifiers Information supported GUID-7C09F294-66AD-4236-A6C4-F9604339E97F v1

Management Information Base(MIB) GUID-F07583D6-E19F-4DD5-91BC-806D27BACFFC v1


The Object Identifiers that are supported are part of the below MIB's :

Supported MIBs Reference


SNMPv2-MIB Rfc3418
IF-MIB Rfc2863
FLOAT-TC-MIB Hitachi Energy Proprietary MIB
HITACHI-ENERGY-AC-MIB Hitachi Energy Proprietary MIB
HITACHI-ENERGY-AC-COMMON-PRODUCT-MIB Hitachi Energy Proprietary MIB
HITACHI-ENERGY-AC-RELION-MIB Hitachi Energy Proprietary MIB

IF-MIB is a part of public MIBs and can be downloaded from SNMP portal
HITACHI-ENERGY-AC-MIB can be downloaded from https://library.abb.com/

Object Identifiers supported by the product are listed below. SNMP Get request on the unsupported
MIB will result in a noSuchObject response.

614 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Object Object Identifiers Remarks


system 1.3.6.1.2.1.1 System Information
interfaces.ifTable.ifEntry 1.3.6.1.2.1.2.2.1 Network interface details defined in
IF-MIB
acProductInfo.acIdentifier.acIdSerialNumber 1.3.6.1.4.1.60038.4.1.1.8.1 Serial number of the IED defined in
Hitachi Energy AC MIB
acProductHardwareModule.mTable.mEntry 1.3.6.1.4.1.60038.4.1.3.2.1 Hardware information of the IED
defined in Hitachi Energy AC MIB
acProductSoftwareComponent.coTable.coEnt 1.3.6.1.4.1.60038.4.1.4.2.1 Software information defined in
ry Hitachi Energy AC MIB

System information object GUID-11137810-E5DD-4C48-B603-E5E5FBA74D81 v1


Request on this object gets the information of the system where SNMP is running. This is part of the
public MIB and not part of the Hitachi Energy MIB.

Object Identifiers Description Type Remarks


system.sysDescr Get the name of the system's String
hardware Information
system.sysObjectID OID information of the respective Object Identifier
product (OID)
system.sysUpTime Time since the system was last String
re-initialized
system.sysContact Contact information of the person String This information can be provided
from PCM600 tool
system.sysName Contact person name String This information can be provided
from PCM600 tool
system.sysLocation Contact person’s location String This information can be provided
from PCM600 tool

Hardware Information object GUID-993A2A17-757F-4874-9773-A0C89FCB6065 v1


Request on this object gets the details of the hardware cards present in the IED. This object can be
polled as a table.

As part of the Hitachi Energy MIB, options for many Object Identifiers are provided. However, for
2.2.6 release only a below listed Object Identifiers are supported.

Object Identifiers Description Type Values


hwModules.mTable.mEntry. Get the type of the Enumerator 0 - undefined
mModuleType module 1 - enclosure
2 - cpuModule
3 - binaryInputOutputCard
4 - analogInputOutputCard
5 - powerSupply
hwModules.mTable.mEntry. Factory where HW String Hitachi Energy
mFactory module was produced
hwModules.mTable.mEntry. Name of the HW String
mIdentifier.mName module
hwModules.mTable.mEntry. Serial number of the String Serial number of the HW.
mIdentifier.mSerialNumber module

In 670, 650 and SAM600-


IO it is not possible to get
the serial number of BIM,
BOM, IOM and SOM.

Table continues on next page

Transformer protection RET650 615


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Object Identifiers Description Type Values


hwModules.mTable.mEntry. Module identifier String Article number of the HW card
mIdentifier.mModuleID
hwModules.mTable.mEntry. Get the version Integer Revision index of the HW
mVersion.mVersionId number of the module
hwModules.mTable.mEntry. Get the healthy state Enumerator 0 - undefined
mHealth of the module 1 - ok
2 - warning
3 - alarm

If the HW module is
healthy from supervision it
will be reported as ok. In
case of HW failure, it will
be reported as warning.

Software Information object GUID-9F0580D5-A38E-4A62-8B94-01136707E7C2 v1


Request on this object will report the software information of the IED. This object can be polled as a
table but only the firmware version will be reported.

Object Identifiers Description Type Values


swComponent.coTable.coEntry.co Get the type of the Enumerator 0 - undefined
ComponentType component 1 - operatingSystem
2 - virtualOperatingSystem
3 - osKernel
4 - container
5 - linuxPackage
6 - softwareApplication
7 - firmware
8 - driver
9 - fpga
10 - service
11 - hotfix

IED reports
only firmware

swComponent.coTable.coEntry.co Get the editor name of the String Hitachi Energy


Vendor component
swComponent.coTable.coEntry.co Get the name of the String IED600
Name component
swComponent.coTable.coEntry.co Get the version number of String
Version.coVersionId the component

16.4 IEC 61850-8-1 communication protocol IP14616-1 v2

16.4.1 Functionality M14787-3 v18

IEC 61850 Ed. 1, Ed. 2 or Ed. 2.1 can be chosen by a setting in PCM600. The IED is equipped with
four optical Ethernet rear ports for IEC 61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the electrical Ethernet front port. IEC 61850-8-1 protocol allows
intelligent electrical devices (IEDs) from different vendors to exchange information and simplifies
system engineering. IED-to-IED communication using GOOSE and client-server communication over
MMS are supported. Disturbance recording file (COMTRADE) uploading can be done over MMS or
FTP.

616 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

The front port is only intended for PCM600 communication, maintenance, training and
test purposes due to risk of interference during normal operation.

16.4.2 Communication interfaces and protocols GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v9

Table 547: Supported station communication interfaces and protocols

Protocol Ethernet Serial


100BASE-FX (ST connector) Glass fiber (ST connector) EIA-485
IEC 61850–8–1 ● - -
DNP3 ● ● ●
IEC 60870-5-103 - ● ●
● = Supported

16.4.3 Settings
PID-7437-SETTINGS v2

Table 548: IEC61850-8-1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On
GOOSEPortEd1 AP_FRONT - - AP_1 Selection of GOOSE port (only for
AP_1 IEC61850 Ed1)
AP_2
AP_3
AP_4
AP_5
AP_6
ProtocolEdition Ed 1 - - Ed 1 Protocol Edition
Ed 2
RemModControl Off - - Off Remote Mode Control
Maintenance
All levels
RemSetControlEd2 Disabled - - Disabled Changing settings over 61850 enabled
Enabled (only for IEC61850 Ed2)
ResvTmsEd2 1 - 3600 s 1 60 Reservation time (only for IEC61850 Ed2)

16.4.4 Technical data IP14434-1 v1

M15031-1 v9

Table 549: Communication protocols

Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 60870–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–115200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
Table continues on next page

Transformer protection RET650 617


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Function Value
Protocol LON
Communication speed for the IEDs 1.25 Mbit/s
Protocol SPA
Communication speed for the IEDs 300–38400 Bd

16.4.5 Generic communication function for single point indication


SPGAPC, SP16GAPC SEMOD55999-1 v5

16.4.5.1 Functionality SEMOD55713-5 v9

Generic communication function for single point indication (SPGAPC) is used to send one single
logical signal to other systems or equipment in the substation.

16.4.5.2 Function block SEMOD54714-4 v4

SPGAPC
BLOCK
^IN
IEC14000021 V2 EN-US

Figure 354: SPGAPC function block

SP16GAPC
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC14000020 V2 EN-US

Figure 355: SP16GAPC function block

16.4.5.3 Signals SEMOD55830-1 v2

PID-3780-INPUTSIGNALS v6

Table 550: SPGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status

618 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

PID-3781-INPUTSIGNALS v6

Table 551: SP16GAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1 status
IN2 BOOLEAN 0 Input 2 status
IN3 BOOLEAN 0 Input 3 status
IN4 BOOLEAN 0 Input 4 status
IN5 BOOLEAN 0 Input 5 status
IN6 BOOLEAN 0 Input 6 status
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status

16.4.5.4 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

16.4.5.5 Monitored data


PID-3780-MONITOREDDATA v3

Table 552: SPGAPC Monitored data

Name Type Values (Range) Unit Description


OUT GROUP - - Output status
SIGNAL

PID-3781-MONITOREDDATA v3

Table 553: SP16GAPC Monitored data

Name Type Values (Range) Unit Description


OUT1 GROUP - - Output 1 status
SIGNAL
OUT2 GROUP - - Output 2 status
SIGNAL
OUT3 GROUP - - Output 3 status
SIGNAL
OUT4 GROUP - - Output 4 status
SIGNAL
OUT5 GROUP - - Output 5 status
SIGNAL
OUT6 GROUP - - Output 6 status
SIGNAL
OUT7 GROUP - - Output 7 status
SIGNAL
Table continues on next page

Transformer protection RET650 619


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Values (Range) Unit Description


OUT8 GROUP - - Output 8 status
SIGNAL
OUT9 GROUP - - Output 9 status
SIGNAL
OUT10 GROUP - - Output 10 status
SIGNAL
OUT11 GROUP - - Output 11 status
SIGNAL
OUT12 GROUP - - Output 12 status
SIGNAL
OUT13 GROUP - - Output 13 status
SIGNAL
OUT14 GROUP - - Output 14 status
SIGNAL
OUT15 GROUP - - Output 15 status
SIGNAL
OUT16 GROUP - - Output 16 status
SIGNAL
OUTOR GROUP - - Output status logic OR gate for input 1 to
SIGNAL 16

16.4.5.6 Operation principle SEMOD55725-5 v9

Upon receiving a signal at its input, Generic communication function for single point indication
(SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment or system that requests
this signal. Additional configuration is needed with PCM600 or IET600 to get the IEC 61850-8-1
communication established. For more information, refer to the Engineering manual.

16.4.6 Generic communication function for Measured Value MVGAPC SEMOD55402-1 v3

16.4.6.1 Functionality SEMOD55872-5 v10

Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It can also
be used inside the same IED, to attach a RANGE aspect to an analog value and to permit
measurement supervision on that value.

16.4.6.2 Function block SEMOD54712-4 v4

MVGAPC
BLOCK ^VALUE
^IN RANGE

IEC14000022 V2 EN-US

Figure 356: MVGAPC function block

620 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.6.3 Signals SEMOD55948-1 v2

PID-6753-INPUTSIGNALS v2

Table 554: MVGAPC Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value

PID-6753-OUTPUTSIGNALS v2

Table 555: MVGAPC Output signals

Name Type Description


VALUE REAL Magnitude of deadband value
RANGE INTEGER Range

16.4.6.4 Settings SEMOD55954-1 v2

PID-6753-SETTINGS v3

Table 556: MVGAPC Non group settings (basic)

Name Values (Range) Unit Step Default Description


BasePrefix micro - - unit Base prefix (multiplication factor)
milli
unit
kilo
Mega
Giga
Tera
MV db 1 - 100000 Type 1 10000 Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
MV zeroDb 0 - 100000 m% 500 1000 Zero point clamping in 0,001% of range
MV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix
(multiplication factor)
MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the base
prefix (multiplication factor)
MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the base
prefix (multiplication factor)
MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType Cyclic - - Deadband Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)

Transformer protection RET650 621


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.4.6.5 Monitored data


PID-6753-MONITOREDDATA v2

Table 557: MVGAPC Monitored data

Name Type Values (Range) Unit Description


VALUE REAL - - Magnitude of deadband value
RANGE INTEGER 0=Normal - Range
1=High
2=Low
3=High-High
4=Low-Low

16.4.6.6 Operation principle SEMOD55936-5 v9

Upon receiving an analog signal at its input, Generic communication function for Measured Value
(MVGAPC) will give the instantaneous value of the signal and the range, as output values. Additional
configuration is needed with PCM600 or IET600 to get the IEC 61850-8-1 communication
established. For more information, see Engineering manual.

The principles of zero-point clamping, range supervision, and value reporting are explained in
Section. For MVGAPC, the measurement range is defined by the MV min and MV max settings.

16.4.7 GOOSE function block to receive a protection activation


information GOOSEACRCV

16.4.7.1 Identification GUID-0F11B3B5-2227-41FD-977C-83BB0717A46F v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a protection GOOSEACRCV - -
activation information

16.4.7.2 Functionality GUID-30E3812C-215D-4338-91B6-7B0EBCA68221 v1

The GOOSE AC Receive (GOOSEACRCV) component collects information from another device’s
Data Object (DO) of common data class type ACD (normally start data from the sending IED) or ACT
(normally operate DO), that is, a DO with several values (general and individual phases) and
common quality and time for those sent via GOOSE. The GOOSE AC Receive component includes
five different outputs with defined names to ease the IEC 61850 mapping of the GOOSE signals in
the configuration process and three additional outputs to convey the validity of the data, the
communication, and if the data received is in test mode.

16.4.7.3 Function block GUID-98577C91-697A-49CA-82E0-84BE4ED0E2CC v1

GOOSEACRCV
BLOCK ^GENERAL
^SRCGENERAL ^PHSA
^SRCPHSA ^PHSB
^SRCPHSB ^PHSC
^SRCPHSC ^NEUT
^SRCNEUT DATAVALID
COMMVALID
TEST
GUID-65039D30-1CBB-4964-AC2A-9905E7E04D6F V1 EN-US

Figure 357: GOOSEACRCV function block

622 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.7.4 Signals GUID-1EFC1786-159A-4DF6-8B48-18BD64C2E0A1 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections in the Signal Matrix Tool (SMT). These connections are visible
and possible to make only if Easy GOOSE engineering is enabled. For instructions on
how to enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.
PID-8324-INPUTSIGNALS v1

Table 558: GOOSEACRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of output signals
SRCGENERAL BOOLEAN 0 Source to General output
SRCPHSA BOOLEAN 0 Source to PhsA output
SRCPHSB BOOLEAN 0 Source to PhsB output
SRCPHSC BOOLEAN 0 Source to PhsC output
SRCNEUT BOOLEAN 0 Source to NEUT output

PID-8324-OUTPUTSIGNALS v1

Table 559: GOOSEACRCV Output signals

Name Type Description


GENERAL BOOLEAN General indication of a command operation or of a protection
activation
PHSA BOOLEAN Value true indicates a command, a trip or a start event of phase A
PHSB BOOLEAN Value true indicates a command, a trip or a start event of phase B
PHSC BOOLEAN Value true indicates a command, a trip or a start event of phase C
NEUT BOOLEAN Value true indicates a start event with earth current
DATAVALID BOOLEAN Data valid
COMMVALID BOOLEAN Communication valid
TEST BOOLEAN Test output

16.4.7.5 Settings GUID-ADCA32A6-F166-4489-8139-3A7C3177DB1E v1

PID-8324-SETTINGS v1

Table 560: GOOSEACRCV Group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off / On
On

16.4.7.6 Operation principle GUID-7AF2B2A3-39C4-43DA-945B-7DC25193BBEA v1

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under a total failure condition
and the GOOSE transmission from the sending IED does not occur.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid 0 0 1 0
Table continues on next page

Transformer protection RET650 623


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication error 0 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked in SMT by a cross or in
ACT by means of a GOOSE connection (if easy GOOSE engineering is enabled) to
receive any data. Only those outputs whose source input is linked or connected will be
updated.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD, then the DATAVALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE, or OLD DATA, then the
DATAVALID output will be LOW.

16.4.8 GOOSE function block to receive a double point value


GOOSEDPRCV

16.4.8.1 Identification
GUID-8C11DB9A-7844-4E1F-A6BB-D97ECE350FC1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEDPRCV - -
double point value

16.4.8.2 Functionality GUID-1D2DBC22-4F04-4809-B34E-8939D442C185 v5

GOOSEDPRCV is used to receive a double point value using IEC 61850 protocol via GOOSE.

The DPOUT output is timestamped.

If the time information is received along with Goose message at input (source of output) from the
Goose sender, the same time information is available at the output signal.

If non signal goose message is received from the sender, the goose output will have the time
information of the receiver IED at which goose message is received.

16.4.8.3 Function block GUID-ED277880-FB5D-4630-872F-9F343D449FFE v1

GOOSEDPRCV
BLOCK ^DPOUT
^SRCDPOUT DATAVALID
COMMVALID
TEST
IEC10000249 V3 EN-US

Figure 358: GOOSEDPRCV function block

624 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.8.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6828-INPUTSIGNALS v3

Table 561: GOOSEDPRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
SRCDPOUT INTEGER 0 Source to double point output

PID-6828-OUTPUTSIGNALS v3

Table 562: GOOSEDPRCV Output signals

Name Type Description


DPOUT INTEGER Double point output
DATAVALID BOOLEAN Data valid for double point output
COMMVALID BOOLEAN Communication valid for double point output
TEST BOOLEAN Test output

16.4.8.5 Settings
PID-6828-SETTINGS v3

Table 563: GOOSEDPRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.8.6 Operation principle GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v5

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication error 0 0 0 0
Table continues on next page

Transformer protection RET650 625


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross or in
ACT by means of a GOOSE connection (if easy GOOSE engineering is enabled) to
receive the double point values.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the DATAVALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

16.4.9 GOOSE function block to receive an integer value


GOOSEINTRCV

16.4.9.1 Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive an GOOSEINTRCV - -
integer value

16.4.9.2 Functionality GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v5

GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via GOOSE.

The INTOUT output is timestamped.

If the time information is received along with Goose message at input (source of output) from the
Goose sender, the same time information is available at the output signal.

If non signal goose message is received from the sender, the goose output will have the time
information of the receiver IED at which goose message is received.

16.4.9.3 Function block GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1

GOOSEINTRCV
BLOCK ^INTOUT
^SRCINTOUT DATAVALID
COMMVALID
TEST
IEC10000250 V3 EN-US

Figure 359: GOOSEINTRCV function block

626 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.9.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6829-INPUTSIGNALS v3

Table 564: GOOSEINTRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
SRCINTOUT INTEGER 0 Source to integer output

PID-6829-OUTPUTSIGNALS v3

Table 565: GOOSEINTRCV Output signals

Name Type Description


INTOUT INTEGER Integer output
DATAVALID BOOLEAN Data valid for integer output
COMMVALID BOOLEAN Communication valid for integer output
TEST BOOLEAN Test output

16.4.9.5 Settings
PID-6829-SETTINGS v3

Table 566: GOOSEINTRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.9.6 Operation principle GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v5

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Receiver in block and communication error Freeze 0 0 0
Table continues on next page

Transformer protection RET650 627


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Receiver in test mode and incoming data with Updated 1 1 0
q= Normal
Receiver in test mode and incoming data with Updated 1 1 1
q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross or in
ACT by means of a GOOSE connection (if easy GOOSE engineering is enabled) to
receive the integer values.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the DATAVALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

16.4.10 GOOSE function block to receive a measurand value


GOOSEMVRCV

16.4.10.1 Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEMVRCV - -
measurand value

16.4.10.2 Functionality GUID-759CB016-2B4D-4D98-82E1-592044983D53 v5

GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via GOOSE.

The MVOUT output is timestamped.

If the time information is received along with Goose message at input (source of output) from the
Goose sender, the same time information is available at the output signal.

If non signal goose message is received from the sender, the goose output will have the time
information of the receiver IED at which goose message is received.

16.4.10.3 Function block GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1

GOOSEMVRCV
BLOCK ^MVOUT
^SRCMVOUT DATAVALID
COMMVALID
TEST
IEC10000251 V3 EN-US

Figure 360: GOOSEMVRCV function block

628 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.10.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6830-INPUTSIGNALS v3

Table 567: GOOSEMVRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
SRCMVOUT REAL 0 Source to measurand value output

PID-6830-OUTPUTSIGNALS v3

Table 568: GOOSEMVRCV Output signals

Name Type Description


MVOUT REAL Measurand value output
DATAVALID BOOLEAN Data valid for measurand value output
COMMVALID BOOLEAN Communication valid for measurand value output
TEST BOOLEAN Test output

16.4.10.5 Settings
PID-6830-SETTINGS v3

Table 569: GOOSEMVRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.10.6 Operation principle GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v6

The DATAVALID output will be HIGH if the incoming message is with valid data.

If the incoming data is outside the range [-1e30, 1e30], the input will be considered invalid, and the
DATAVALID output will be LOW.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Receiver in block and communication error Freeze 0 0 0
Table continues on next page

Transformer protection RET650 629


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Receiver in test mode and incoming data with Updated 1 1 0
q= Normal
Receiver in test mode and incoming data with Updated 1 1 1
q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross or in
ACT by means of a GOOSE connection (in case easy GOOSE engineering is enabled) to
receive the measured value.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the DATAVALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

16.4.11 GOOSE function block to receive a single point value


GOOSESPRCV

16.4.11.1 Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSESPRCV - -
single point value

16.4.11.2 Functionality GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v5

GOOSESPRCV is used to receive a single point value (SPS or SPC) using IEC 61850 protocol via
GOOSE.

The SPOUT output is timestamped.

If the time information is received along with Goose message at input (source of output) from the
Goose sender, the same time information is available at the output signal.

If non signal goose message is received from the sender, the goose output will have the time
information of the receiver IED at which goose message is received.

16.4.11.3 Function block GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1

GOOSESPRCV
BLOCK ^SPOUT
^SRCSPOUT DATAVALID
COMMVALID
TEST
IEC10000248 V3 EN-US

Figure 361: GOOSESPRCV function block

630 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.11.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6832-INPUTSIGNALS v3

Table 570: GOOSESPRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
SRCSPOUT BOOLEAN 0 Source to single point output

PID-6832-OUTPUTSIGNALS v3

Table 571: GOOSESPRCV Output signals

Name Type Description


SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output

16.4.11.5 Settings
PID-6832-SETTINGS v3

Table 572: GOOSESPRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.11.6 Operation principle GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v5

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication error 0 0 0 0
Table continues on next page

Transformer protection RET650 631


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross or in
ACT by means of a GOOSE connection (if easy GOOSE engineering is enabled) to
receive the binary single point values.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the DATAVALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.

16.4.12 Horizontal communication via GOOSE for interlocking


GOOSEINTLKRCV SEMOD173197-1 v2

16.4.12.1 Functionality GUID-92ECE152-892C-4214-95DE-B92718689434 v3

GOOSE communication can be used for exchanging information between IEDs via the IEC
61850-8-1 station communication bus. This is typically used for sending apparatus position
indications for interlocking or reservation signals for 1-of-n control. GOOSE can also be used to
exchange any boolean, integer, double point and analog measured values between IEDs.

Outputs APPx_OP and APPx_CL are timestamped.

If the time information is received along with Goose message at input(source of output) from the
Goose sender, the same time information is available at the output signal.

If non signal goose message is received from the sender, the goose output will have the time
information of the receiver IED at which goose message is received.

632 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.12.2 Function block SEMOD173210-4 v5

GOOSEINTLKRCV
BLOCK ^RESREQ
^SRCRESREQ ^RESGRANT
^SRCRESGR ^APP1_OP
^SRCAPP1 ^APP1_CL
^SRCAPP2 APP1VAL
^SRCAPP3 ^APP2_OP
^SRCAPP4 ^APP2_CL
^SRCAPP5 APP2VAL
^SRCAPP6 ^APP3_OP
^SRCAPP7 ^APP3_CL
^SRCAPP8 APP3VAL
^SRCAPP9 ^APP4_OP
^SRCAPP10 ^APP4_CL
^SRCAPP11 APP4VAL
^SRCAPP12 ^APP5_OP
^SRCAPP13 ^APP5_CL
^SRCAPP14 APP5VAL
^SRCAPP15 ^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COMMVALID
TEST
IEC07000048-4-en.vsd
IEC07000048 V4 EN-US

Figure 362: GOOSEINTLKRCV function block

16.4.12.3 Signals SEMOD173205-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6831-INPUTSIGNALS v3

Table 573: GOOSEINTLKRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of output signals
SRCRESREQ BOOLEAN 0 Source to reservation request
SRCRESGR BOOLEAN 0 Source to reservation granted
Table continues on next page

Transformer protection RET650 633


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Default Description


SRCAPP1 INTEGER 0 Source to apparatus 1 position
SRCAPP2 INTEGER 0 Source to apparatus 2 position
SRCAPP3 INTEGER 0 Source to apparatus 3 position
SRCAPP4 INTEGER 0 Source to apparatus 4 position
SRCAPP5 INTEGER 0 Source to apparatus 5 position
SRCAPP6 INTEGER 0 Source to apparatus 6 position
SRCAPP7 INTEGER 0 Source to apparatus 7 position
SRCAPP8 INTEGER 0 Source to apparatus 8 position
SRCAPP9 INTEGER 0 Source to apparatus 9 position
SRCAPP10 INTEGER 0 Source to apparatus 10 position
SRCAPP11 INTEGER 0 Source to apparatus 11 position
SRCAPP12 INTEGER 0 Source to apparatus 12 position
SRCAPP13 INTEGER 0 Source to apparatus 13 position
SRCAPP14 INTEGER 0 Source to apparatus 14 position
SRCAPP15 INTEGER 0 Source to apparatus 15 position

PID-6831-OUTPUTSIGNALS v3

Table 574: GOOSEINTLKRCV Output signals

Name Type Description


RESREQ BOOLEAN Reservation request
RESGRANT BOOLEAN Reservation granted
APP1_OP BOOLEAN Apparatus 1 position is open
APP1_CL BOOLEAN Apparatus 1 position is closed
APP1VAL BOOLEAN Apparatus 1 position is valid
APP2_OP BOOLEAN Apparatus 2 position is open
APP2_CL BOOLEAN Apparatus 2 position is closed
APP2VAL BOOLEAN Apparatus 2 position is valid
APP3_OP BOOLEAN Apparatus 3 position is open
APP3_CL BOOLEAN Apparatus 3 position is closed
APP3VAL BOOLEAN Apparatus 3 position is valid
APP4_OP BOOLEAN Apparatus 4 position is open
APP4_CL BOOLEAN Apparatus 4 position is closed
APP4VAL BOOLEAN Apparatus 4 position is valid
APP5_OP BOOLEAN Apparatus 5 position is open
APP5_CL BOOLEAN Apparatus 5 position is closed
APP5VAL BOOLEAN Apparatus 5 position is valid
APP6_OP BOOLEAN Apparatus 6 position is open
APP6_CL BOOLEAN Apparatus 6 position is closed
APP6VAL BOOLEAN Apparatus 6 position is valid
APP7_OP BOOLEAN Apparatus 7 position is open
APP7_CL BOOLEAN Apparatus 7 position is closed
APP7VAL BOOLEAN Apparatus 7 position is valid
APP8_OP BOOLEAN Apparatus 8 position is open
APP8_CL BOOLEAN Apparatus 8 position is closed
APP8VAL BOOLEAN Apparatus 8 position is valid
APP9_OP BOOLEAN Apparatus 9 position is open
APP9_CL BOOLEAN Apparatus 9 position is closed
Table continues on next page

634 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Type Description


APP9VAL BOOLEAN Apparatus 9 position is valid
APP10_OP BOOLEAN Apparatus 10 position is open
APP10_CL BOOLEAN Apparatus 10 position is closed
APP10VAL BOOLEAN Apparatus 10 position is valid
APP11_OP BOOLEAN Apparatus 11 position is open
APP11_CL BOOLEAN Apparatus 11 position is closed
APP11VAL BOOLEAN Apparatus 11 position is valid
APP12_OP BOOLEAN Apparatus 12 position is open
APP12_CL BOOLEAN Apparatus 12 position is closed
APP12VAL BOOLEAN Apparatus 12 position is valid
APP13_OP BOOLEAN Apparatus 13 position is open
APP13_CL BOOLEAN Apparatus 13 position is closed
APP13VAL BOOLEAN Apparatus 13 position is valid
APP14_OP BOOLEAN Apparatus 14 position is open
APP14_CL BOOLEAN Apparatus 14 position is closed
APP14VAL BOOLEAN Apparatus 14 position is valid
APP15_OP BOOLEAN Apparatus 15 position is open
APP15_CL BOOLEAN Apparatus 15 position is closed
APP15VAL BOOLEAN Apparatus 15 position is valid
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

16.4.12.4 Settings SEMOD173168-1 v2

PID-6831-SETTINGS v3

Table 575: GOOSEINTLKRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.12.5 Operation principle GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v3

The APPxVAL output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when at least one of the subscribed GOOSE datasets is
not received at the Function Block.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication error 0 0 0 0
Table continues on next page

Transformer protection RET650 635


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Data Value Data Valid Comm Valid Test


Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked either in SMT by means of
a cross or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive any data. Only those outputs whose source input is linked/connected
will be updated.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the APPxVAL output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
APPxVAL output will be LOW.

16.4.13 GOOSE binary receive GOOSEBINRCV SEMOD173158-1 v3

16.4.13.1 Function block SEMOD173175-4 v2

GOOSEBINRCV
BLOCK ^OUT1
^SRCOUT1 DVALID1
^SRCOUT2 ^OUT2
^SRCOUT3 DVALID2
^SRCOUT4 ^OUT3
^SRCOUT5 DVALID3
^SRCOUT6 ^OUT4
^SRCOUT7 DVALID4
^SRCOUT8 ^OUT5
^SRCOUT9 DVALID5
^SRCOUT10 ^OUT6
^SRCOUT11 DVALID6
^SRCOUT12 ^OUT7
^SRCOUT13 DVALID7
^SRCOUT14 ^OUT8
^SRCOUT15 DVALID8
^SRCOUT16 ^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST
IEC07000047 V5 EN-US

Figure 363: GOOSEBINRCV function block

636 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.4.13.2 Signals SEMOD173166-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6827-INPUTSIGNALS v3

Table 576: GOOSEBINRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of output signals
SRCOUT1 BOOLEAN 0 Source to binary output 1
SRCOUT2 BOOLEAN 0 Source to binary output 2
SRCOUT3 BOOLEAN 0 Source to binary output 3
SRCOUT4 BOOLEAN 0 Source to binary output 4
SRCOUT5 BOOLEAN 0 Source to binary output 5
SRCOUT6 BOOLEAN 0 Source to binary output 6
SRCOUT7 BOOLEAN 0 Source to binary output 7
SRCOUT8 BOOLEAN 0 Source to binary output 8
SRCOUT9 BOOLEAN 0 Source to binary output 9
SRCOUT10 BOOLEAN 0 Source to binary output 10
SRCOUT11 BOOLEAN 0 Source to binary output 11
SRCOUT12 BOOLEAN 0 Source to binary output 12
SRCOUT13 BOOLEAN 0 Source to binary output 13
SRCOUT14 BOOLEAN 0 Source to binary output 14
SRCOUT15 BOOLEAN 0 Source to binary output 15
SRCOUT16 BOOLEAN 0 Source to binary output 16

PID-6827-OUTPUTSIGNALS v3

Table 577: GOOSEBINRCV Output signals

Name Type Description


OUT1 BOOLEAN Binary output 1
DVALID1 BOOLEAN Valid data on binary output 1
OUT2 BOOLEAN Binary output 2
DVALID2 BOOLEAN Valid data on binary output 2
OUT3 BOOLEAN Binary output 3
DVALID3 BOOLEAN Valid data on binary output 3
OUT4 BOOLEAN Binary output 4
DVALID4 BOOLEAN Valid data on binary output 4
OUT5 BOOLEAN Binary output 5
DVALID5 BOOLEAN Valid data on binary output 5
OUT6 BOOLEAN Binary output 6
DVALID6 BOOLEAN Valid data on binary output 6
OUT7 BOOLEAN Binary output 7
DVALID7 BOOLEAN Valid data on binary output 7
OUT8 BOOLEAN Binary output 8
DVALID8 BOOLEAN Valid data on binary output 8
OUT9 BOOLEAN Binary output 9
Table continues on next page

Transformer protection RET650 637


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Description


DVALID9 BOOLEAN Valid data on binary output 9
OUT10 BOOLEAN Binary output 10
DVALID10 BOOLEAN Valid data on binary output 10
OUT11 BOOLEAN Binary output 11
DVALID11 BOOLEAN Valid data on binary output 11
OUT12 BOOLEAN Binary output 12
DVALID12 BOOLEAN Valid data on binary output 12
OUT13 BOOLEAN Binary output 13
DVALID13 BOOLEAN Valid data on binary output 13
OUT14 BOOLEAN Binary output 14
DVALID14 BOOLEAN Valid data on binary output 14
OUT15 BOOLEAN Binary output 15
DVALID15 BOOLEAN Valid data on binary output 15
OUT16 BOOLEAN Binary output 16
DVALID16 BOOLEAN Valid data on binary output 16
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

16.4.13.3 Settings SEMOD173168-1 v2

PID-6827-SETTINGS v3

Table 578: GOOSEBINRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.13.4 Operation principle GUID-950F2501-9183-43C0-A193-7D15124F6CCE v3

The DVALIDx output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Updated 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication error 0 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error 0 0 0 0

638 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

At least one of the inputs of this GOOSE block must be linked either in SMT by means of
a cross or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive any data. Only those outputs whose source input is linked/connected
will be updated.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the DVALIDx output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DVALIDx output will be LOW.

16.4.14 GOOSE function block to receive a switching device


GOOSEXLNRCV

16.4.14.1 Identification
GUID-4B23D0CF-F298-4BBC-B833-1B8CC98D1604 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEXLNRCV - -
switching device

16.4.14.2 Functionality GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1

The GOOSE XLN Receive component is used to collect information from another device’s XCBR/
XSWI logical node sent over process bus via GOOSE. The GOOSE XLN Receive component
includes 12 different outputs (and their respective channel valid bits) with defined names to ease the
61850 mapping of the GOOSE signals in the configuration process.

16.4.14.3 Function block GUID-690FD935-5344-4D6F-AB94-F9FD5FD35B23 v1

GOOSEXLNRCV
BLOCK ^BEH
^SRCBEH BEH_VALID
^SRCLOC ^LOC
^SRCBLKOPN LOC_VALID
^SRCBLKCLS ^BLKOPN
^SRCPOS BLKOPN_VALID
^SRCOPCNT ^BLKCLS
^SRCBLK BLKCLS_VALID
^SRCSTSELD ^POSVAL
^SRCOPRCVD POSVAL_VALID
^SRCOPOK ^OPCNT
^SRCEEHLT OPCNT_VALID
^SRCOPCAP ^BLK
BLK_VALID
^STSELD
STSELD_VALID
^OPRCVD
OPRCVD_VALID
^OPOK
OPOK_VALID
^EEHEALTH
EEHEALTH_VALID
^OPCAP
OPCAP_VALID
COMMVALID
TEST
IEC16000036-1-en.vsdx
IEC16000036 V1 EN-US

Figure 364: GOOSEXLNRCV function block

Transformer protection RET650 639


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.4.14.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block are used
for GOOSE connections. These connections are visible and possible to make only if Easy
GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE
engineering in PCM600, refer to the Engineering Manual.
PID-6643-INPUTSIGNALS v3

Table 579: GOOSEXLNRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of output signals
SRCBEH INTEGER 0 Source to behaviour output
SRCLOC BOOLEAN 0 Source to local control behaviour output
SRCBLKOPN BOOLEAN 0 Source to block opening
SRCBLKCLS BOOLEAN 0 Source to block closing
SRCPOS INTEGER 0 Source to switch position
SRCOPCNT INTEGER 0 Source to operation counter
SRCBLK BOOLEAN 0 Source to dynamic blocking of function described by the LN
SRCSTSELD BOOLEAN 0 Source to the controllable data is in the status "selected”
SRCOPRCVD BOOLEAN 0 Source to operate command for a controllable data object received
SRCOPOK BOOLEAN 0 Source to operate command for a controllable data object
accepted
SRCEEHLT INTEGER 0 Source to external equipment health
SRCOPCAP INTEGER 0 Source to operating capability

PID-6643-OUTPUTSIGNALS v3

Table 580: GOOSEXLNRCV Output signals

Name Type Description


BEH INTEGER Behaviour
BEH_VLD BOOLEAN Valid data on Beh output
LOC BOOLEAN Local control behaviour
LOC_VLD BOOLEAN Valid data on Loc output
BLKOPN BOOLEAN Block opening
BLKOPN_VLD BOOLEAN Valid data on BlkOpn output
BLKCLS BOOLEAN Block closing
BLKCLS_VLD BOOLEAN Valid data on BlkCls output
POSVAL INTEGER Switch position
POSVAL_VLD BOOLEAN Valid data on PosVal output
OPCNT INTEGER Operation counter
OPCNT_VLD BOOLEAN Valid data on OpCnt output
BLK BOOLEAN Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN Valid data on Blk output
STSELD BOOLEAN The controllable data is in the status "selected”
STSELD_VLD BOOLEAN Valid data on stSeld output
OPRCVD BOOLEAN Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN Valid data on opRcvd output
OPOK BOOLEAN Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN Valid data on opOk output
Table continues on next page

640 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Type Description


EEHEALTH INTEGER External equipment health
EEHEALTH_VLD BOOLEAN Valid data on EEHealth output
OPCAP INTEGER Operating capability
OPCAP_VLD BOOLEAN Valid data on OpCap output
COMMVALID BOOLEAN Communication valid
TEST BOOLEAN Test output

16.4.14.5 Settings
PID-6643-SETTINGS v3

Table 581: GOOSEXLNRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Off/On
On

16.4.14.6 Operation principle GUID-903B5E3F-DC92-4D0A-B4D5-59DD01F36458 v1

The xxx_VALID outputs will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure condition and
the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

At least one of the inputs of this GOOSE block must be linked either in SMT by means of
a cross or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive any data. Only those outputs whose source input is linked/connected
will be updated.

The implementation for IEC 61850 quality data handling is restricted to a simple level. If
quality data validity is GOOD then the xxx_VALID output will be HIGH. If quality data
validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
xxx_VALID output will be LOW.

16.5 IEC/UCA 61850-9-2LE communication protocol GUID-6814F62B-8D99-4679-A11E-68048D1AC424 v2

16.5.1 Introduction GUID-FE2AC08A-2E04-4E73-8CA4-905522B1026A v2

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to communicate
with devices providing measured values in digital format, commonly known as Merging Units (MU).
The rear access points are used for the communication.

16.5.2 Function block GUID-2581F3AD-7487-4C80-BDF3-9C6EC9F2E43C v3

The function blocks are not represented in the configuration tool. The signals appear only
in the SMT tool when merging units (MU) are included in the configuration with the
Ethernet configuration tool. In the SMT tool they can be mapped to the desired virtual
input (SMAI) of the IED and used internally in the configuration.

Transformer protection RET650 641


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.5.3 Signals

16.5.3.1 Output signals SEMOD166622-1 v1

GUID-942C81AD-22D9-438F-95FA-1972BA2BE2E5 v1
The output signals are the same for all MUs so only the table for MU1_HW is included in this manual.
PID-6850-OUTPUTSIGNALS v3

Table 582: MU1_HW Output signals

Name Type Description


I1 STRING Analogue input I1
I2 STRING Analogue input I2
I3 STRING Analogue input I3
I4 STRING Analogue input I4
U1 STRING Analogue input U1
U2 STRING Analogue input U2
U3 STRING Analogue input U3
U4 STRING Analogue input U4
MUDATA BOOLEAN Fatal error, data not received, transmission errors, time-sync
issues or inconsistent sample rate
SYNCH BOOLEAN High when IED clock is not within configured accuracy or time
domain
SMPLLOST BOOLEAN Fatal error or recovery state after fatal error. High if any subscribed
channel has bad quality or TEST while IED not in test mode.
MUSYNCH BOOLEAN MU not synced or MU clock not synced to same clock as IED
TESTMODE BOOLEAN Quality of one or more subscribed analogue channels is TEST
SIMMODE BOOLEAN MU delivers simulated data accepted by IED
I1QUALITY INTEGER Binary coded quality information for I1
I2QUALITY INTEGER Binary coded quality information for I2
I3QUALITY INTEGER Binary coded quality information for I3
I4QUALITY INTEGER Binary coded quality information for I4
U1QUALITY INTEGER Binary coded quality information for U1
U2QUALITY INTEGER Binary coded quality information for U2
U3QUALITY INTEGER Binary coded quality information for U3
U4QUALITY INTEGER Binary coded quality information for U4

16.5.4 Settings SEMOD166625-1 v2

PID-6850-SETTINGS v3

Table 583: MU1_HW Non group settings (basic)

Name Values (Range) Unit Step Default Description


CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

642 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.5.5 Monitored data


PID-6850-MONITOREDDATA v3

Table 584: MU1_HW Monitored data

Name Type Values (Range) Unit Description


MUDATA BOOLEAN 0=Ok - Fatal error, data not received,
1=Error transmission errors, time-sync issues or
inconsistent sample rate
SYNCH BOOLEAN 0=Ok - High when IED clock is not within
1=Error configured accuracy or time domain
SMPLLOST BOOLEAN 1=Yes - Fatal error or recovery state after fatal
0=No error. High if any subscribed channel has
bad quality or TEST while IED not in test
mode.
MUSYNCH BOOLEAN 0=Ok - MU not synced or MU clock not synced to
1=Error same clock as IED
TESTMODE BOOLEAN 1=Yes - Quality of one or more subscribed
0=No analogue channels is TEST
SIMMODE BOOLEAN 1=Yes - MU delivers simulated data accepted by
0=No IED
BadReference BOOLEAN 1=Yes - BadReference indication output for I1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for I1
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I1
0=No
Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I1
0=No
Validity INTEGER 0=Good - Validity indication output I1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I2
0=No
Table continues on next page

Transformer protection RET650 643


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for I2
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I2
0=No
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I2
0=No
Validity INTEGER 0=Good - Validity indication output I2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for I3
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I3
0=No
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I3
0=No
Validity INTEGER 0=Good - Validity indication output I3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I4
0=No
Table continues on next page

644 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for I4
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I4
0=No
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I4
0=No
Validity INTEGER 0=Good - Validity indication output I4
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for U1
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U1
0=No
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U1
0=No
Validity INTEGER 0=Good - Validity indication output U1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U2
0=No
Table continues on next page

Transformer protection RET650 645


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for U2
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U2
0=No
Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U2
0=No
Validity INTEGER 0=Good - Validity indication output U2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for U3
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U3
0=No
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U3
0=No
Validity INTEGER 0=Good - Validity indication output U3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U4
0=No
Table continues on next page

646 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for U4
0=No
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U4
0=No
Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U4
0=No
Validity INTEGER 0=Good - Validity indication output U4
2=Reserved
1=Invalid
3=Questionable

16.5.6 Operation principle GUID-A1D31CDA-1FE2-4BC0-A472-1B35E73CA1F2 v6

The merging units (MUs) are situated close to the primary equipment, like circuit breakers, isolators,
etc. The MUs have the capability to gather measured values from measuring transformers, non-
conventional transducers or both. The gathered data are then transmitted to subscribers over the
process bus, utilizing the IEC/UCA 61850-9-2LE protocol.

The IED communicates with the MUs over the process bus via the rear access points. For the user,
the MU appears in the IED as a normal analogue input module and is engineered in the very same
way.

Transformer protection RET650 647


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

IED

Application

Station Wide
Preprocessing blocks Preprocessing blocks GPS Clock
SMAI SMAI

MU1 MU2
Splitter
Electrical-to-
Optical Converter

1PPS
TRM module

Access Point
110 V 1A 1A

IEC/UCA 61850-9-2LE

Ethernet Switch

IEC/UCA 61850-9-2LE

IEC/UCA 61850-9-2LE

Merging 1PPS Merging 1PPS


Unit Unit

Combi Combi
CT CT
Sensor Sensor

Conventional VT

IEC08000072 V4 EN-US

Figure 365: Example of signal path for sampled analogue values from MU and conventional
CT/VT
The function has the following alarm signals:

• MUDATA:
• Ok[0] indicates that the merging unit samples are received from the merging unit and are
accepted.
• ERROR[1] indicates that the merging unit samples are generated by internal substitution.
• SYNCH:
• OK[0] indicates

648 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

• when SyncLostMode = Block, and the time quality of the hardware is within the set
value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockOnLostUTC, the time quality of the hardware is within
the set value [SyncAccLevel=1us, 4us or Unspecified] [AND] IED receives global
common time[UTC] from any of the FineSyncSource like IRIG-B, PTP or GPS.
• when SyncLostMode = NoBlock
• ERROR[1] indicates
• when SyncLostMode = Block, and the time quality of the hardware is not within the
set value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockonLostUTC, the time quality of the hardware is not
within the set value [SyncAccLevel=1us, 4us or Unspecified] [OR] IED doesn't
receive global common time[UTC] from any of the FineSyncSource like IRIG-B,
PTP or GPS.

• SMPLLOST:
• NO[0] indicates that the merging unit samples are received from the merging unit and are
accepted
• YES[1] indicates
• when merging unit data are generated by internal substitution
• when one/more channel's Quality is not good
• when merging unit is in Testmode/detailed quality=Test, IED is not in test mode

• MUSYNCH:
• OK[0] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the hardware is
within the set value [SyncAccLevel=1us, 4us or Unspecified] [AND] merging unit is
time synchronized [smpSynch flag in datastream is not equal to 0] [AND] the
hardware time matches the time in the datastream within 10 ms.
• when SyncLostMode = NoBlock, the merging unit samples are received
• ERROR[1] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the hardware is
not within the set value [SyncAccLevel=1us, 4us or Unspecified] [OR] merging unit
is not time synchronized [smpSynch flag in datastream is equal to 0] [OR] the
hardware time is out of 10 ms from the time in the datastream.
• when SyncLostMode = NoBlock, the merging unit samples are not received

• TESTMODE:
• NO[0] indicates that No merging unit analog channels are in testmode
• YES[1] indicates that one/more subscribed channels are in testmode
• SIMMODE:
• NO[0] indicates that normal data is received and are accepted
• YES[1] indicates that the received datastream is tagged as simulated and are accepted

Internal substitution can happen during the following conditions:

1. Transient block after receive error (sample loss)


2. Transient block after Simulated/Real Sample value stream transition
3. Transient block after recovery from substitution
4. No data from merging unit
5. Bad data from merging unit
6. Merging unit report lost sync[smpSynch=0] and SyncLostMode = Block/BlockOnLostUTC
7. IED time quality of hardware is not good [not within set value SyncAccLevel] and SyncLostMode
= Block/BlockOnLostUTC
8. Merging unit channel reported with quality other than good
9. Merging unit channel/channels is/are in testmode and the IED is not in testmode

Transformer protection RET650 649


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

During Internal substitution, the functions connected to that particular merging unit will be blocked
and the merging unit channel's analog values will be forced to 0 with quality as Invalid, Substituted,
Failure.

Timeout

TSYNCERR Indicates that there is some timeout on any configured time source or the time quality is
worse than specified in SynchAccLevel. The timeout is individually specified per time source (PPS,
IRIG-B, SNTP etc.) See section "Time synchronization TIMESYNCHGEN"

16.5.6.1 Conditional blocking GUID-D129543D-82BE-4F8A-9333-4C3470693F98 v1

Introduction GUID-9D9A73FA-505E-4936-BB55-E7D86AB8023B v2
Conditional blocking is a concept in the 670 series which improves resilience against errors in
network communication, time synchronization, and hardware. This is important for digital substations
where analogue data (some or even all) is sourced from the IEC 61850 9-2 MUs (merging units).

Conditional blocking functionality GUID-C12A5162-7F49-4FF0-98AA-BA362BC48070 v1


The overall idea with conditional blocking is to avoid blocking of the parts of an IED which can safely
continue the operation in presence of certain error conditions (listed below).

To make conditional blocking work as intended, there are configuration rules that need to be
followed. If an incorrect configuration is deployed, the IED functionality may be blocked inadvertently,
thereby reducing the availability of protection functions. An incorrect configuration also increases the
sensitivity to single point failures.

With a proper configuration, on the other hand, only functions directly affected by an error will be
blocked, while other functions will continue to operate.

Implementation GUID-D9880430-E6D6-42EE-B315-7E9279BEC913 v1
In Figure 366, two functions are shown, F1 and F2, where F1 takes data only from MU1, while F2
takes data from both MU1 and MU2.

3Ph Group
MU1 SMAI F1

3Ph Group
MU2 SMAI F2
IEC18001012 V2 EN-US

Figure 366: Implementation schematic


When F1 and F2 start-up, each function analyzes the analogue data which is driving it. This
information is used to determine how the function should be blocked during error conditions
separately.

Function F1 is independent of MU2, if MU2 is lost, this will not affect F1. It will execute its algorithms
as long as data from MU1 is available. Note that F1 will operate even with poor time synchronization.
This is possible because F1 only depends on data from a single MU.

Function F2 on the other hand, depends on the correct information and time synchronized data being
available from both MU1 and MU2. If any of the MUs fail, or if any of them indicates the loss of time
synchronization, F2 will be blocked.

650 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Examples of error conditions GUID-AFB2C078-59A8-4DFD-AD6C-B458695E4FA5 v1


This section contains examples of error conditions that can trigger function blocking.

• Time synchronization is not available/correctly configured in the IED

• Time synchronization quality is poor

• Analogue MU data indicates bad time quality in the MU

• Analogue MU data indicates data error in the MU

• Analogue MU data is unavailable (for example, if a connection to an IEC 9-2 MU is lost)

• Hardware errors (for example, network switches and fibers, station clock failures etc.)

Depending on how the IED is configured, these kinds of errors will have a bigger or smaller impact
on how much of the IED functionality that is blocked.

Incorrect configuration GUID-7857CC4E-A7DF-4B85-BF4E-9470A02903E5 v2


As an example, consider an instance of OC4PTOC, which has four steps of functionality. In Figure
367, it is configured with two 3-phase groups, one for current and one for voltage. The analogue data
comes from two different MUs.

IEC18001013 V2 EN-US

Figure 367: Incorrect configuration


Assume, that the user has configured one step in the OC4PTOC as non-directional, and another step
as directional. Because the analogue data comes from two different MUs, the user should
understand that the data from both MUs must be available and both must indicate that they are time
synchronized, for the directional step to operate.

Due to the way conditional blocking works, if one or both of the MUs indicate poor time
synchronization, then the entire function will be blocked. Unfortunately, in this example, this will also
block the non-directional over-current step, although it would be perfectly capable of operating
without time synchronization.

This shows the incorrect configuration from a conditional blocking perspective.

Transformer protection RET650 651


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Correct configuration GUID-AA803422-5774-4BDE-B84E-2FCF465EE4D0 v2


In Figure 368, the configuration is changed so the user have two instances of the function, where the
non-directional over-current instance uses only currents from one MU, while the directional over-
current instance uses current and voltage from both the MUs.

IEC18001014 V2 EN-US

Figure 368: Correct configuration


If the time synchronization is lost, or if there is an error in the voltage modules of the MU, or if the
voltage MU is lost altogether, the non-directional instance will still be operative.

This is an example of how the user needs to configure the IED to ensure conditional blocking works
as intended.

Another way to avoid conditional blocking is to take currents as well as voltages from the same MU.
Thus, the usage of multiple SMAIs in itself is not a trigger of conditional blocking, but the usage of
multiple MUs can be. This also implies that hardware-wise, one should try to not divide a 3-phase
group of currents and voltages over multiple MUs, when this is possible (this is really a consideration
for the substation hardware setup).

Functions with multiple internal steps GUID-D067CD74-43CD-480E-9A50-4F978A8DF5D8 v2


The following functions have internal steps/functions, which also can be configured incorrectly similar
to the above description.

NS4PTOC, OC4PTOC, EF4PTOC

• Each step can be set differently with respect to directionality

Time synchronization GUID-5DD58144-76EA-4019-A8EA-354E263810FB v3


A correct configuration also has to consider how the time synchronization is set up.

To begin with, a suitable station clock must be available. Hitachi Energy recommends that PTP is
used as a time synchronization protocol.

Further, it is recommended that at least two station clocks are connected to the substation network.
This is to avoid the single point of failure. If one clock encounters an error, or loses its connection to
the network, the other clock will seamlessly take over the time synchronization task, and thus avoid
blocking due to lost time synchronization.

It is also required that PTP is active on all ports that send or receive sampled data on all devices, to
secure that the system time is common for all devices.

652 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Synchronization via PTP GUID-F7D9C58F-CB87-4D2A-BC64-2B34D41557A4 v2


While synchronizing a station via PTP (IEC 61850-9-3), the time propagates from the clock through
the system to each IED.

This means that during a transition, for example, when a clock regains time from the GPS system
after drifting for some time, there can be different times in different parts of a substation.

Refer the following figure for a simple system:

GMC

MU2

REX 670

MU1 MU3

SAM600 - TS CT VT
IEC18001015 V2 EN-US

Figure 369: Synchronization via PTP

If the station clock is out of order for some time and then regains good synch from, for example, the
satellite system, the correct time will reach MU2 and the 670 first. Then, it will propagate to MU1 and
MU3 through the boundary clock in the 670. This means, that for a short duration, MU1 and MU2 will
both appear to be synchronized, but they will in practice have different times. If the protection is not
blocked during this condition, user will get a false trip.

To fix this problem, the synch-lost signal from the merging units is prolonged for 16 seconds in the
670. The synch-lost signal is used for conditional blocking of protections which use data from the
TRM of the IED in combination with a merging unit. The maximum time frame specified by IEC
61850-9-3 to propagate the time and resynchronize is 16 seconds.

The same time frame applies for the internal synchronization of the 670. In the scenario where PTP
is used in combination with 9-2, the synch-lost signal is also prolonged with 16 seconds. Again, this
delay is needed to ensure that the correct time has propagated to all units before blocked functions
are released for operation.

16.5.6.2 IEC 61850 quality expander QUALEXP GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v2

The quality expander component is used to display the detailed quality of an IEC/UCA 61850-9-2LE
analog channel. The component expands the channel quality output of a Merging Unit analog

Transformer protection RET650 653


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

channel received in the IED as per the IEC 61850-7-3 standard. This component can be used during
the ACT monitoring to get the particular channel quality of the Merging Unit.

The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard. When written to
IED, the configuration will show the expanded form of the respective MU channel quality information
during the online monitoring in the ACT.

The validity status of the quality as described in IEC 61850-7-3 is expanded to Good, Invalid,
Reserved and Questionable (QUEST) outputs.

The detailed quality as described in IEC 61850-7-3 is expanded to Overflow, Out of Range
(OUTRANGE), Bad reference (BADREF), Oscillatory (OSC), Failure, old data, inconsistent
(INCONS) and inaccurate (INACC) outputs.

The source status of the quality as described in IEC 61850-7-3 is expanded to Process and
Substituted (SUBST) outputs.

The other quality statuses (Test, Operator Blocked (OPBLKD) and Derived) are shown as they are.

The derived quality is the extension to IEC 61850-7-3. If the derived bit is set to 1, it indicates that
there is no physical sensor within the system to determine the value, but the value is derived from a
combination of values from other physical sensors. Typically, I4 or U4 are derived if they are
calculated as the sum of the three phase quantities.

The configured MU channel quality as described in IEC 61850-7-3 is available on LHMI. This can be
viewed under Main Menu /Diagnostics /Merging units /MUX:XXXX/XX Quality .

IEC16000074 V2 EN-US

Figure 370: Configured MU channel quality in LHMI

16.5.7 Technical data SEMOD172233-1 v1

SEMOD172236-2 v3

Table 585: IEC/UCA 61850-9-2LE communication protocol

Functions Value
Protocol IEC/UCA 61850-9-2LE
Communication speed for the IEDs 100BASE-FX

654 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.6 LON communication protocol IP14420-1 v1

16.6.1 Functionality M11924-3 v6

An optical network can be used within the substation automation system. This enables
communication with the IED through the LON bus from the operator’s workplace, from the control
center and also from other terminals.

LON communication protocol is specified in LonTalkProtocol Specification Version 3 from Echelon


Corporation and is designed for communication in control networks. These networks are
characterized by high speed for data transfer, short messages (few bytes), peer-to-peer
communication, multiple communication media, low maintenance, multivendor equipment, and low
support costs. LonTalk supports the needs of applications that cover a range of requirements. The
protocol follows the reference model for open system interconnection (OSI) designed by the
International Standardization Organization (ISO).

In this document the most common addresses for commands and events are available. For other
addresses, refer to section Related documents.

It is assumed that the reader is familiar with LON communication protocol in general.

16.6.2 Settings IP14441-1 v2

PID-593-SETTINGS v11

Table 586: HORZCOMM Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation
On

PID-4147-SETTINGS v7

Table 587: ADE Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation
On
TimerClass Slow - - Slow Timer class
Normal
Fast
TimeDomain Local without DST - - Local with DST Time domain
Local with DST

16.6.3 Operation principle IP14439-1 v2

M15083-3 v3
The speed of the network depends on the medium and transceiver design. With protection and
control devices, fiber optic media is used, which enables the use of the maximum speed of 1.25
Mbits/s. The protocol is a peer-to-peer protocol where all the devices connected to the network can
communicate with each other. The own subnet and node number are identifying the nodes (max. 255
subnets, 127 nodes per one subnet).

The LON bus links the different parts of the protection and control system. The measured values,
status information, and event information are spontaneously sent to the higher-level devices. The
higher-level devices can read and write memorized values, setting values, and other parameter data
when required. The LON bus also enables the bay level devices to communicate with each other to
deliver, for example, interlocking information among the terminals without the need of a bus master.

The LonTalk protocol supports two types of application layer objects: network variables and explicit
messages. Network variables are used to deliver short messages, such as measuring values, status

Transformer protection RET650 655


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

information, and interlocking/blocking signals. Explicit messages are used to transfer longer pieces of
information, such as events and explicit read and write messages to access device data.

The benefits achieved from using the LON bus in protection and control systems include direct
communication among all terminals in the system and support for multi-master implementations. The
LON bus also has an open concept, so that the terminals can communicate with external devices
using the same standard of network variables.

Introduction of LON protocol M15083-8 v2


For more information, refer to LON bus, LonWorks Network in Protection and Control, User’s manual
and Technical description.

LON protocol M15083-11 v1

Configuration of LON M15083-13 v4


LON network tool (LNT) is a multi-purpose tool for LonWorks network configuration. All the functions
required for setting up and configuring a LonWorks network, is easily accessible on a single tool
program.

Activate LON Communication M15083-16 v3


Activate LON communication in the Parameter Setting tool under Main Menu /Configuration /
Communication /Station communication / LON /HORZCOMM:1 , where Operation must be set to
ON.

Add LON Device Types LNT M15083-19 v5


A new device is added to LON Network Tool from the Device menu or by installing the device from
the Hitachi Energy s LON Device Types package for LNT 505 using SLDT package version 1p2 r04.

LON net address M15083-22 v3


To establish a LON connection, the IED has to be given a unique net address. The net address
consists of a subnet and node number. This is accomplished with the LON Network Tool by creating
one device for each IED.

Vertical communication M15083-25 v1


Vertical communication describes communication between the monitoring devices and protection and
control IEDs. This communication includes sending of changed process data to monitoring devices
as events and transfer of commands, parameter data and disturbance recorder files. This
communication is implemented using explicit messages.

Events and indications M15083-28 v3


Events are sent to the monitoring devices using explicit messages (message code 44H) with
unacknowledged transport service of the LonTalk protocol. When a signal is changed in the IED, one
message with the value, quality and time is transmitted from terminal.

Binary events M15083-31 v6


Binary events are generated in Event function blocks EVENT:1 to EVENT:20 in the IEDs. The EVENT
function blocks have predefined LON addresses. Table 588 shows the LON addresses to the first
input on the EVENT function blocks. Addresses to the other inputs on the EVENT function block are
consecutive after the first input. For example, input 15 on EVENT:17 function block has the address
1280 + 14 (15-1) = 1294.

For double indications, only the first eight inputs 1–8 must be used. Inputs 9–16 can be used for
other types of events at the same EVENT block.

Three EVENT function blocks EVENT:1 to EVENT:3 running with a fast loop time (3 ms) are available
as basic in the IEDs.. The remaining EVENT function blocks EVENT:4 to EVENT:9 run with a loop
time of 8 ms and EVENT:10 to EVENT:20 run with a loop time of 100 ms. The EVENT blocks are
used to send binary signals, integers, real time values like analogue data from measuring functions
and mA input modules as well as pulse counter signals.

16 pulse counter value function blocks PCFCNT:1 to PCFCNT:16 are available in the IEDs.

656 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

The first LON address in every EVENT function block is found in table 588. The formula for
calculating the LON address is:

LON Address = (EVBlkNr-1)×16 + signalNr +1023

For instance, the first pin at Event block number 2 has the address: (2-1)×16 +1 +1023 = 1040

Table 588: LON adresses for EVENT functions

Function block First LON address in


function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328

Event masks M15083-78 v4


Event mask for each input can be set individually from Parameter Setting Tool (PST) under:
Settings /IED settings / Monitoring / Event Function or via parameter setting tool (PST) as
follows:

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, the EVENT function makes the reporting decision (reporting criteria for integers has
no semantic, prefer to be set by the user)

Single indication M15083-123 v3


Directly connected binary IO signal via binary input function block (SMBI) is always reported on
change, no changed detection is done in the EVENT function block. Other Boolean signals, for
example a start or a trip signal from a protection function is event masked in the EVENT function
block.

Double indications M15083-126 v3


Double indications can only be reported for the first 8 inputs on an EVENT function block.

Transformer protection RET650 657


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

• 00 generates an intermediate event with the read status 0


• 01 generates an open event with the read status 1
• 10 generates a close event with the read status 2
• 11 generates an undefined event with the read status 3

Analog value M15083-135 v4


All analog values are reported cyclic. The reporting interval is taken from the connected function if
there is a limit supervised signal. Otherwise it is taken from the EVENT function block.

Command handling M15083-80 v4


Commands are transferred using transparent SPA-bus messages. The transparent SPA-bus
message is an explicit LON message which contains an ASCII character message following the
coding rules of the SPA-bus protocol. The message is sent using explicit messages with message
code 41H and using acknowledged transport service.

Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are sent using
the same message code. It is mandatory that one device sends out only one SPA-bus message at a
time to one node and waits for the reply before sending the next message.

For commands from the operator workplace to the IED for apparatus control, that is the function
blocks type SCSWI 1 to 30, SXCBR 1 to 18 and SXSWI 1 to 24, the SPA addresses are according to
table 589.
SEMOD116913-2 v2

Table 589: SPA addresses for commands from the operator workplace to the IED for apparatus control

Name Function SPA Description


block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
BL_CMD SCSWI05 1 I 5210 SPA parameters for block
command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block
command
BL_CMD SCSWI07 1 I 5258 SPA parameters for block
command
BL_CMD SCSWI08 1 I 5283 SPA parameters for block
command
BL_CMD SCSWI09 1 I 5307 SPA parameters for block
command
BL_CMD SCSWI10 1 I 5331 SPA parameters for block
command
BL_CMD SCSWI11 1 I 5355 SPA parameters for block
command
BL_CMD SCSWI12 1 I 5379 SPA parameters for block
command
BL_CMD SCSWI13 1 I 5403 SPA parameters for block
command
BL_CMD SCSWI14 1 I 5427 SPA parameters for block
command
BL_CMD SCSWI15 1 I 5451 SPA parameters for block
command
Table continues on next page

658 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Function SPA Description


block address
BL_CMD SCSWI16 1 I 5475 SPA parameters for block
command
BL_CMD SCSWI17 1 I 5499 SPA parameters for block
command
BL_CMD SCSWI18 1 I 5523 SPA parameters for block
command
BL_CMD SCSWI19 1 I 5545 SPA parameters for block
command
BL_CMD SCSWI20 1 I 5571 SPA parameters for block
command
BL_CMD SCSWI21 1 I 5594 SPA parameters for block
command
BL_CMD SCSWI22 1 I 5619 SPA parameters for block
command
BL_CMD SCSWI23 1 I 5643 SPA parameters for block
command
BL_CMD SCSWI24 1 I 5667 SPA parameters for block
command
BL_CMD SCSWI25 1 I 5691 SPA parameters for block
command
BL_CMD SCSWI26 1 I 5715 SPA parameters for block
command
BL_CMD SCSWI27 1 I 5739 SPA parameters for block
command
BL_CMD SCSWI28 1 I 5763 SPA parameters for block
command
BL_CMD SCSWI29 1 I 5787 SPA parameters for block
command
BL_CMD SCSWI30 1 I 5811 SPA parameters for block
command
BL_CMD SCSWI31 1 I 5835 SPA parameters for block
command
BL_CMD SCSWI32 1 I 5859 SPA parameters for block
command
CANCEL SCSWI01 1 I 5107 SPA parameters for cancel
command
CANCEL SCSWI02 1 I 5131 SPA parameters for cancel
command
CANCEL SCSWI03 1 I 5153 SPA parameters for cancel
command
CANCEL SCSWI04 1 I 5178 SPA parameters for cancel
command
CANCEL SCSWI05 1 I 5202 SPA parameters for cancel
command
CANCEL SCSWI06 1 I 5226 SPA parameters for cancel
command
CANCEL SCSWI07 1 I 5250 SPA parameters for cancel
command
CANCEL SCSWI08 1 I 5275 SPA parameters for cancel
command
CANCEL SCSWI09 1 I 5299 SPA parameters for cancel
command
CANCEL SCSWI10 1 I 5323 SPA parameters for cancel
command
Table continues on next page

Transformer protection RET650 659


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Function SPA Description


block address
CANCEL SCSWI11 1 I 5347 SPA parameters for cancel
command
CANCEL SCSWI12 1 I 5371 SPA parameters for cancel
command
CANCEL SCSWI13 1 I 5395 SPA parameters for cancel
command
CANCEL SCSWI14 1 I 5419 SPA parameters for cancel
command
CANCEL SCSWI15 1 I 5443 SPA parameters for cancel
command
CANCEL SCSWI16 1 I 5467 SPA parameters for cancel
command
CANCEL SCSWI17 1 I 5491 SPA parameters for cancel
command
CANCEL SCSWI18 1 I 5515 SPA parameters for cancel
command
CANCEL SCSWI19 1 I 5537 SPA parameters for cancel
command
CANCEL SCSWI20 1 I 5563 SPA parameters for cancel
command
CANCEL SCSWI21 1 I 5586 SPA parameters for cancel
command
CANCEL SCSWI22 1 I 5611 SPA parameters for cancel
command
CANCEL SCSWI23 1 I 5635 SPA parameters for cancel
command
CANCEL SCSWI24 1 I 5659 SPA parameters for cancel
command
CANCEL SCSWI25 1 I 5683 SPA parameters for cancel
command
CANCEL SCSWI26 1 I 5707 SPA parameters for cancel
command
CANCEL SCSWI27 1 I 5731 SPA parameters for cancel
command
CANCEL SCSWI28 1 I 5755 SPA parameters for cancel
command
CANCEL SCSWI29 1 I 5779 SPA parameters for cancel
command
CANCEL SCSWI30 1 I 5803 SPA parameters for cancel
command
CANCEL SCSWI31 1 I 5827 SPA parameters for cancel
command
CANCEL SCSWI32 1 I 5851 SPA parameters for cancel
command
SELECTOpen=00, SCSWI01 1 I 5105 SPA parameters for select (Open/
SELECTClose=01, Close) command
SELOpen+ILO=10, Note: Send select command before
SELClose+ILO=11, operate command
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31
SELECTOpen=00, SCSWI02 1 I 5129 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI03 1 I 5151 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
Table continues on next page

660 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI04 1 I 5176 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI05 1 I 5200 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI06 1 I 5224 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI07 1 I 5248 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI08 1 I 5273 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI09 1 I 5297 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI10 1 I 5321 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI11 1 I 5345 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI12 1 I 5369 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI13 1 I 5393 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI14 1 I 5417 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI15 1 I 5441 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI16 1 I 5465 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI17 1 I 5489 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI18 1 I 5513 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI19 1 I 5535 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI20 1 I 5561 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI21 1 I 5584 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI22 1 I 5609 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI23 1 I 5633 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI24 1 I 5657 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI25 1 I 5681 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI26 1 I 5705 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI27 1 I 5729 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI28 1 I 5753 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI29 1 I 5777 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI30 1 I 5801 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
Table continues on next page

Transformer protection RET650 661


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI31 1 I 5825 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
SELECTOpen=00, SCSWI32 1 I 5849 SPA parameters for select (Open/
SELECTClose=01, so on. Close) command
ExcOpen=00, SCSWI01 1 I 5106 SPA parameters for operate (Open/
ExcClose=01, Close) command
ExcOpen+ILO=10, Note: Send select command before
ExcClose+ILO=11, operate command
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31
ExcOpen=00, SCSWI02 1 I 5130 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI02 1 I 5152 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI04 1 I 5177 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI05 1 I 5201 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI06 1 I 5225 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI07 1 I 5249 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI08 1 I 5274 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI09 1 I 5298 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI10 1 I 5322 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI11 1 I 5346 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI12 1 I 5370 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI13 1 I 5394 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI14 1 I 5418 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI15 1 I 5442 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI16 1 I 5466 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI17 1 I 5490 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI18 1 I 5514 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI19 1 I 5536 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI20 1 I 5562 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI21 1 I 5585 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI22 1 I 5610 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI23 1 I 5634 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
Table continues on next page

662 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Function SPA Description


block address
ExcOpen=00, SCSWI24 1 I 5658 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI25 1 I 5682 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI26 1 I 5706 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI27 1 I 5730 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI28 1 I 5754 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI29 1 I 5778 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI30 1 I 5802 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI31 1 I 5826 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
ExcOpen=00, SCSWI32 1 I 5850 SPA parameters for operate (Open/
ExcClose=01, so on. Close) command
Sub Value SXCBR01 2 I 7854 SPA parameter for position to be
substituted
Note: Send the value before Enable
Sub Value SXCBR02 2 I 7866 SPA parameter for position to be
substituted
Sub Value SXCBR03 2 I 7884 SPA parameter for position to be
substituted
Sub Value SXCBR04 2 I 7904 SPA parameter for position to be
substituted
Sub Value SXCBR05 2 I 7923 SPA parameter for position to be
substituted
Sub Value SXCBR06 2 I 7942 SPA parameter for position to be
substituted
Sub Value SXCBR07 2 I 7961 SPA parameter for position to be
substituted
Sub Value SXCBR08 2 I 7980 SPA parameter for position to be
substituted
Sub Value SXCBR09 3I7 SPA parameter for position to be
substituted
Sub Value SXCBR10 3 I 26 SPA parameter for position to be
substituted
Sub Value SXCBR11 3 I 45 SPA parameter for position to be
substituted
Sub Value SXCBR12 3 I 56 SPA parameter for position to be
substituted
Sub Value SXCBR13 3 I 74 SPA parameter for position to be
substituted
Sub Value SXCBR14 3 I 94 SPA parameter for position to be
substituted
Sub Value SXCBR15 3 I 120 SPA parameter for position to be
substituted
Sub Value SXCBR16 3 I 133 SPA parameter for position to be
substituted
Sub Value SXCBR17 3 I 158 SPA parameter for position to be
substituted
Sub Value SXCBR18 3 I 179 SPA parameter for position to be
substituted
Table continues on next page

Transformer protection RET650 663


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Function SPA Description


block address
Sub Value SXSWI01 3 I 196 SPA parameter for position to be
substituted
Sub Value SXSWI02 3 I 216 SPA parameter for position to be
substituted
Sub Value SXSWI03 3 I 235 SPA parameter for position to be
substituted
Sub Value SXSWI04 3 I 254 SPA parameter for position to be
substituted
Sub Value SXSWI05 3 I 272 SPA parameter for position to be
substituted
Sub Value SXSWI06 3 I 292 SPA parameter for position to be
substituted
Sub Value SXSWI07 3 I 310 SPA parameter for position to be
substituted
Sub Value SXSWI08 3 I 330 SPA parameter for position to be
substituted
Sub Value SXSWI09 3 I 348 SPA parameter for position to be
substituted
Sub Value SXSWI10 3 I 359 SPA parameter for position to be
substituted
Sub Value SXSWI11 3 I 378 SPA parameter for position to be
substituted
Sub Value SXSWI12 3 I 397 SPA parameter for position to be
substituted
Sub Value SXSWI13 3 I 416 SPA parameter for position to be
substituted
Sub Value SXSWI14 3 I 435 SPA parameter for position to be
substituted
Sub Value SXSWI15 3 I 454 SPA parameter for position to be
substituted
Sub Value SXSWI16 3 I 473 SPA parameter for position to be
substituted
Sub Value SXSWI17 3 I 492 SPA parameter for position to be
substituted
Sub Value SXSWI18 3 I 511 SPA parameter for position to be
substituted
Sub Value SXSWI19 3 I 530 SPA parameter for position to be
substituted
Sub Value SXSWI20 3 I 549 SPA parameter for position to be
substituted
Sub Value SXSWI21 3 I 568 SPA parameter for position to be
substituted
Sub Value SXSWI22 3 I 587 SPA parameter for position to be
substituted
Sub Value SXSWI23 3 I 606 SPA parameter for position to be
substituted
Sub Value SXSWI24 3 I 625 SPA parameter for position to be
substituted
Sub Value SXSWI25 3 I 644 SPA parameter for position to be
substituted
Sub Value SXSWI26 3 I 663 SPA parameter for position to be
substituted
Sub Value SXSWI27 3 I 682 SPA parameter for position to be
substituted
Table continues on next page

664 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Function SPA Description


block address
Sub Value SXSWI28 3 I 701 SPA parameter for position to be
substituted
Sub Enable SXCBR01 2 I 7855 SPA parameter for substitute
enable command
Note: Send the Value before Enable
Sub Enable SXCBR02 2 I 7865 SPA parameter for substitute
enable command
Sub Enable SXCBR03 2 I 7885 SPA parameter for substitute
enable command
Sub Enable SXCBR04 2 I 7903 SPA parameter for substitute
enable command
Sub Enable SXCBR05 2 I 7924 SPA parameter for substitute
enable command
Sub Enable SXCBR06 2 I 7941 SPA parameter for substitute
enable command
Sub Enable SXCBR07 2 I 7962 SPA parameter for substitute
enable command
Sub Enable SXCBR08 2 I 7979 SPA parameter for substitute
enable command
Sub Enable SXCBR09 3I8 SPA parameter for substitute
enable command
Sub Enable SXCBR10 3 I 25 SPA parameter for substitute
enable command
Sub Enable SXCBR11 3 I 46 SPA parameter for substitute
enable command
Sub Enable SXCBR12 3 I 55 SPA parameter for substitute
enable command
Sub Enable SXCBR13 3 I 75 SPA parameter for substitute
enable command
Sub Enable SXCBR14 3 I 93 SPA parameter for substitute
enable command
Sub Enable SXCBR15 3 I 121 SPA parameter for substitute
enable command
Sub Enable SXCBR16 3 I 132 SPA parameter for substitute
enable command
Sub Enable SXCBR17 3 I 159 SPA parameter for substitute
enable command
Sub Enable SXCBR18 3 I 178 SPA parameter for substitute
enable command
Sub Enable SXSWI01 3 I 197 SPA parameter for substitute
enable command
Sub Enable SXSWI02 3 I 215 SPA parameter for substitute
enable command
Sub Enable SXSWI03 3 I 234 SPA parameter for substitute
enable command
Sub Enable SXSWI04 3 I 252 SPA parameter for substitute
enable command
Sub Enable SXSWI05 3 I 271 SPA parameter for substitute
enable command
Sub Enable SXSWI06 3 I 290 SPA parameter for substitute
enable command
Sub Enable SXSWI07 3 I 309 SPA parameter for substitute
enable command
Sub Enable SXSWI08 3 I 328 SPA parameter for substitute
enable command
Table continues on next page

Transformer protection RET650 665


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Function SPA Description


block address
Sub Enable SXSWI09 3 I 347 SPA parameter for substitute
enable command
Sub Enable SXSWI10 3 I 360 SPA parameter for substitute
enable command
Sub Enable SXSWI11 3I 379 SPA parameter for substitute
enable command
Sub Enable SXSWI12 3 I 398 SPA parameter for substitute
enable command
Sub Enable SXSWI13 3 I 417 SPA parameter for substitute
enable command
Sub Enable SXSWI14 3 I 436 SPA parameter for substitute
enable command
Sub Enable SXSWI15 3 I 455 SPA parameter for substitute
enable command
Sub Enable SXSWI16 3 I 474 SPA parameter for substitute
enable command
Sub Enable SXSWI17 3 I 493 SPA parameter for substitute
enable command
Sub Enable SXSWI18 3 I 512 SPA parameter for substitute
enable command
Sub Enable SXSWI19 3 I 531 SPA parameter for substitute
enable command
Sub Enable SXSWI20 3 I 550 SPA parameter for substitute
enable command
Sub Enable SXSWI21 3 I 569 SPA parameter for substitute
enable command
Sub Enable SXSWI22 3 I 588 SPA parameter for substitute
enable command
Sub Enable SXSWI23 3 I 607 SPA parameter for substitute
enable command
Sub Enable SXSWI24 3 I 626 SPA parameter for substitute
enable command
Sub Enable SXSWI25 3 I 645 SPA parameter for substitute
enable command
Sub Enable SXSWI26 3 I 664 SPA parameter for substitute
enable command
Sub Enable SXSWI27 3 I 683 SPA parameter for substitute
enable command
Sub Enable SXSWI28 3 I 702 SPA parameter for substitute
enable command
Update Block SXCBR01 2 I 7853 SPA parameter for update block
command
Update Block SXCBR02 2 I 7864 SPA parameter for update block
command
Update Block SXCBR03 2 I 7883 SPA parameter for update block
command
Update Block SXCBR04 2 I 7905 SPA parameter for update block
command
Update Block SXCBR05 2 I 7922 SPA parameter for update block
command
Update Block SXCBR06 2 I 7943 SPA parameter for update block
command
Update Block SXCBR07 2 I 7960 SPA parameter for update block
command
Table continues on next page

666 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Function SPA Description


block address
Update Block SXCBR08 2 I 7981 SPA parameter for update block
command
Update Block SXCBR09 3I6 SPA parameter for update block
command
Update Block SXCBR10 3 I 27 SPA parameter for update block
command
Update Block SXCBR11 3 I 44 SPA parameter for update block
command
Update Block SXCBR12 3 I 57 SPA parameter for update block
command
Update Block SXCBR13 3 I 73 SPA parameter for update block
command
Update Block SXCBR14 3 I 92 SPA parameter for update block
command
Update Block SXCBR15 3 I 122 SPA parameter for update block
command
Update Block SXCBR16 3 I 131 SPA parameter for update block
command
Update Block SXCBR17 3 I 160 SPA parameter for update block
command
Update Block SXCBR18 3 I 177 SPA parameter for update block
command
Update Block SXSWI01 3 I 198 SPA parameter for update block
command
Update Block SXSWI02 3 I 214 SPA parameter for update block
command
Update Block SXSWI03 3 I 236 SPA parameter for update block
command
Update Block SXSWI04 3 I 253 SPA parameter for update block
command
Update Block SXSWI05 3 I 273 SPA parameter for update block
command
Update Block SXSWI06 3 I 291 SPA parameter for update block
command
Update Block SXSWI07 3 I 311 SPA parameter for update block
command
Update Block SXSWI08 3 I 329 SPA parameter for update block
command
Update Block SXSWI09 3 I 349 SPA parameter for update block
command
Update Block SXSWI10 3 I 358 SPA parameter for update block
command
Update Block SXSWI11 3 I 377 SPA parameter for update block
command
Update Block SXSWI12 3 I 396 SPA parameter for update block
command
Update Block SXSWI13 3 I 415 SPA parameter for update block
command
Update Block SXSWI14 3 I 434 SPA parameter for update block
command
Update Block SXSWI15 3 I 453 SPA parameter for update block
command
Update Block SXSWI16 3 I 472 SPA parameter for update block
command
Table continues on next page

Transformer protection RET650 667


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Function SPA Description


block address
Update Block SXSWI17 3 I 491 SPA parameter for update block
command
Update Block SXSWI18 3 I 510 SPA parameter for update block
command
Update Block SXSWI19 3 I 529 SPA parameter for update block
command
Update Block SXSWI20 3 I 548 SPA parameter for update block
command
Update Block SXSWI21 3 I 567 SPA parameter for update block
command
Update Block SXSWI22 3 I 586 SPA parameter for update block
command
Update Block SXSWI23 3 I 605 SPA parameter for update block
command
Update Block SXSWI24 3 I 624 SPA parameter for update block
command
Update Block SXSWI25 3 I 643 SPA parameter for update block
command
Update Block SXSWI26 3 I 662 SPA parameter for update block
command
Update Block SXSWI27 3 I 681 SPA parameter for update block
command
Update Block SXSWI28 3 I 700 SPA parameter for update block
command

Horizontal communication M15083-86 v4


Network variables are used for communication between 500 and 650 series IEDs The supported
network variable type is SNVT_state (NV type 83). SNVT_state is used to communicate the state of
a set of 1 to 16 Boolean values.

Multiple command send function block (MULTICMDSND) is used to pack the information to one
value. This value is transmitted to the receiving node and presented for the application by a multiple
command receive function block (MULTICMDRCV). With horizontal communication, the input
BOUND on MULTICMDSND must be set to 1. There are 10 MULTICMDSND and 60
MULTICMDRCV function blocks available. These function blocks are connected using the LON
network tool (LNT). The tool also defines the service and addressing on LON.

This is an overview for configuring the network variables for the IEDs.

Configuration of LON network variables M15083-92 v3


Configure the Network variables according to the specific application using the LON network tool
(LNT). The following is an example of how to configure network variables concerning, for example,
interlocking between two IEDs.

668 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

LON

BAY E1 BAY E3 BAY E4


MULTICMDSND: 7 MULTICMDSND: 9 MULTICMDSND: 9

en05000718.vsd
IEC05000718 V2 EN-US

Figure 371: Examples connections between MULTICMDSND and MULTICMDRCV function


blocks in three IEDs
The network variable connections are done from the NV Connection window. From LNT window
select Connections / NVConnections / New .

en05000719.vsd
IEC05000719 V1 EN-US

Figure 372: The network variables window in LNT


There are two ways of downloading NV connections. Either the users can use the drag-and-drop
method where they can select all nodes in the device window, drag them to the Download area in the
bottom of the program window and drop them there; or, they can perform it by selecting the
traditional menu, Configuration / Download .

Transformer protection RET650 669


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

en05000720.vsd
IEC05000720 V1 EN-US

Figure 373: The download configuration window in LNT

Communication ports M15083-97 v6


The serial communication module (SLM) is a mezzanine module placed on the first analog digital
conversion module (ADM), and it is used for LON, SPA, IEC 60870-5-103 and DNP communication.

In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for LON
protocol.

IEC16000079-1-en.vsd
IEC16000079 V1 EN-US

Figure 374: Rear view of 1/2 x 19” casing with 1 TRM slot

670 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

There are two types of IO connectors: snap-in connectors for plastic fiber cables and ST/bayonet
connectors for glass fiber cables. The SLM can be equipped with either type of connector or a
combination of both connectors. This is identified by a tag.

Connect the incoming optical fiber to the RX receiver input, and the outgoing optical fiber to the TX
transmitter output. Pay special attention to the instructions concerning handling and connection of
fiber cables.

16.6.4 Technical data IP14442-1 v1

M11927-1 v2

Table 590: LON communication protocol

Function Value
Protocol LON
Communication speed 1.25 Mbit/s

16.7 SPA communication protocol IP14614-1 v1

16.7.1 Functionality M11897-3 v6

In this section the most common addresses for commands and events are available. For other
addresses, refer to section Related documents.

It is assumed that the reader is familiar with the SPA communication protocol in general.

16.7.2 Design M11877-3 v7

Using the rear SPA port for either local or remote communication with a PC requires the following
equipment:

• Optical fibers
• Opto/electrical converter for the PC
• PC

SPA cannot be accessed via PCM600.

When communicating between the local HMI and a PC, the only hardware required is a front-
connection cable.

SPA can be accessed via LHMI front only when using the Field Service Tool Access
(FSTACCS).

Transformer protection RET650 671


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.7.3 Settings IP14403-1 v2

PID-6195-SETTINGS v5

Table 591: SPA Non group settings (basic)

Name Values (Range) Unit Step Default Description


SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd - - 9600 Bd Baudrate on serial line
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

PID-6194-SETTINGS v5

Table 592: LONSPA Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation
On
SlaveAddress 1 - 899 - 1 30 Slave address

16.7.4 Operation principle IP14401-1 v3

M11880-3 v2
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data bits + even
parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more information on recommended
baud rate for each type of IED, refer to Technical reference manual. Messages on the bus consist of
ASCII characters.

Introduction of SPA protocol M11880-7 v2


The basic construction of the protocol assumes that the slave has no self-initiated need to talk to the
master but the master is aware of the data contained in the slaves and, consequently, can request
required data. In addition, the master can send data to the slave. Requesting by the master can be
performed either by sequenced polling (for example, for event information) or only on demand.

The master requests slave information using request messages and sends information to the slave in
write messages. Furthermore, the master can send all slaves in common a broadcast message
containing time or other data. The inactive state of bus transmit and receive lines is a logical "1".

SPA protocol M11880-10 v5


The tables below specify the SPA addresses for reading data from and writing data to an IED with
the SPA communication protocol implemented.

The SPA addresses for the pulse counter values PCFCNT:1 to PCFCNT:16 are found in table 593.

Table 593: SPA addresses for the PCFCNT function

Function block SPA address CNT_VAL SPA address NEW_VAL


PCFCNT:1 6-O-2788 6-O-2787
PCFCNT:2 6-O-2794 6-O-2793
PCFCNT:3 6-O-2800 6-O-2799
PCFCNT:4 6-O-2806 6-O-2805
PCFCNT:5 6-O-2812 6-O-2811
PCFCNT:6 6-O-2818 6-O-2817
PCFCNT:7 6-O-2824 6-O-2823
PCFCNT:8 6-O-2830 6-O-2829
Table continues on next page

672 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Function block SPA address CNT_VAL SPA address NEW_VAL


PCFCNT:9 6-O-2836 6-O-2835
PCFCNT:10 6-O-2842 6-O-2841
PCFCNT:11 6-O-2848 6-O-2847
PCFCNT:12 6-O-2854 6-O-2853
PCFCNT:13 6-O-2860 6-O-2859
PCFCNT:14 6-O-2866 6-O-2865
PCFCNT:15 6-O-2872 6-O-2871
PCFCNT:16 6-O-2878 6-O-2877

I/O modules M11880-16 v4


To read binary inputs, the SPA-addresses for the outputs of the I/O-module function block are used,
that is, the addresses for BI1 – BI16. For SPA addresses, refer to section Related documents in
Product Guide.
M11880-35 v1

Single command, 16 signals M11880-51 v5


The IEDs can be provided with a function to receive signals either from a substation automation
system or from the local HMI. That receiving function block has 16 outputs that can be used, for
example, to control high voltage apparatuses in switchyards. For local control functions, the local
HMI can also be used.

The single command, 16 signals function consists of four function blocks: SINGLECMD:1 to
SINGLECMD:4 for 16 binary output signals each.

The signals can be individually controlled from the operator station, remote-control gateway, or from
the local HMI on the IED. For Single command, 3 signals function block, SINGLECMD:1 to
SINGLECMD:3, the address is for the first output. The other outputs follow consecutively after the
first one. For example, output 7 on the SINGLECMD:2 function block has the 5O533 address.

The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to SINGLECMD:4 are
found in table 594.

Table 594: SPA addresses for SINGLECMD function

Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd1 4-S-4639 5-O-511
SINGLECMD1-Cmd2 4-S-4640 5-O-512
SINGLECMD1-Cmd3 4-S-4641 5-O-513
SINGLECMD1-Cmd4 4-S-4642 5-O-514
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
Table continues on next page

Transformer protection RET650 673


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Function block SPA address CMD Input SPA address CMD output
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558
SINGLECMD4-Cmd1 4-S-4738 5-O-559
SINGLECMD4-Cmd2 4-S-4739 5-O-560
SINGLECMD4-Cmd3 4-S-4740 5-O-561
SINGLECMD4-Cmd4 4-S-4741 5-O-562
SINGLECMD4-Cmd5 4-S-4742 5-O-563
SINGLECMD4-Cmd6 4-S-4743 5-O-564
SINGLECMD4-Cmd7 4-S-4744 5-O-565
SINGLECMD4-Cmd8 4-S-4745 5-O-566
SINGLECMD4-Cmd9 4-S-4746 5-O-567
SINGLECMD4-Cmd10 4-S-4747 5-O-568
SINGLECMD4-Cmd11 4-S-4748 5-O-569
SINGLECMD4-Cmd12 4-S-4749 5-O-570
SINGLECMD4-Cmd13 4-S-4750 5-O-571
Table continues on next page

674 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Function block SPA address CMD Input SPA address CMD output
SINGLECMD4-Cmd14 4-S-4751 5-O-572
SINGLECMD4-Cmd15 4-S-4752 5-O-573
SINGLECMD4-Cmd16 4-S-4753 5-O-574

Figure 375 shows an application example of how the user can, in a simplified way, connect the
command function via the configuration logic circuit in a protection IED for control of a circuit breaker.

A pulse via the binary outputs of the IED normally performs this type of command control. The SPA
addresses to control the outputs OUT1 – OUT16 in SINGLECMD:1 are shown in table 594.

SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
#CD01-CMDOUT1 ^OUT2
#CD01-CMDOUT2 ^OUT3
#CD01-CMDOUT3 ^OUT4
#CD01-CMDOUT4 ^OUT5 AND PULSETIMER
^OUT6 INPUT1 OUT INPUT OUT To output board, OPEN
#CD01-CMDOUT5
^OUT7 INPUT2 NOUT
#CD01-CMDOUT6
#CD01-CMDOUT7 ^OUT8 INPUT3
#CD01-CMDOUT8 ^OUT9 INPUT4
#CD01-CMDOUT9 ^OUT10
#CD01-CMDOUT10 ^OUT11
#CD01-CMDOUT11 ^OUT12
#CD01-CMDOUT12 ^OUT13
#CD01-CMDOUT13 ^OUT14
#CD01-CMDOUT14 ^OUT15
#CD01-CMDOUT15 ^OUT16
#CD01-CMDOUT16

SYNCH OK

IEC05000717-4-en.vsd
IEC05000717 V4 EN-US

Figure 375: Application example showing a simplified logic diagram for control of a circuit
breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or setable pulse
length signals. This is set in Parameter Setting Tool (PST) under: Main Menu /Settings / IED
Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST).

Event function EVENT M11880-82 v6


The Event function (EVENT) sends time-tagged events to the station level (for example, operator
workplace) over the station bus. On the station level, events are presented in an event list. Events
can be created from both internal logical signals and binary input channels. All the internal signals
are time tagged in the main processing module, while the binary input channels are time tagged
directly on each I/O module. Events are produced according to a set of event masks. These masks
are treated commonly for both LON and SPA channels.

Two special signals for event registration purposes are available in the IED: Terminal Restarted
(0E50) and Event buffer overflow (0E51).

The status and event codes for the EVENT function are found in Table 595.

Transformer protection RET650 675


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Table 595: Status and event codes

Single indication1) Double indication


Event block Status Set event Reset Intermedi Closed Open Undefined
event ate 00 10 01 11
EVENT:1
Input 1 22O1 22E33 22E32 22E0 22E1 22E2 22E3
Input 2 22O2 22E35 22E34 22E4 22E5 22E6 22E7
Input 3 22O3 22E37 22E36 22E8 22E9 22E10 22E11
Input 4 22O4 22E39 22E38 22E12 22E13 22E14 22E15
Input 5 22O5 22E41 22E40 22E16 22E17 22E18 22E19
Input 6 22O6 22E43 22E42 22E20 22E21 22E22 22E23
Input 7 22O7 22E45 22E44 22E24 22E25 22E26 22E27
Input 8 22O8 22E47 22E46 22E28 22E29 22E30 22E31
Input 9 22O9 22E49 22E48 - - - -
Input 10 22O10 22E51 22E50 - - - -
Input 11 22O11 22E53 22E52 - - - -
Input 12 22O12 22E55 22E54 - - - -
Input 13 22O13 22E57 22E56 - - - -
Input 14 22O14 22E59 22E58 - - - -
Input 15 22O15 22E61 22E60 - - - -
Input 16 22O16 22E63 22E62 - - - -

EVENT:2 230.. 23E.. 23E.. 23E.. 23E.. 23E.. 23E..


EVENT:3 240.. 24E.. 24E.. 24E.. 23E.. 24E.. 24E..
- - - - - - - -
- - - - - - - -
- - - - - - - -
EVENT:20 410.. 41E.. 41E.. 41E.. 41E.. 41E.. 41E..

These values are only applicable if the event mask is masked ≠ OFF.

Connection of signals as events M11880-311 v5


Signals coming from different protection and control functions and sent as events to the station level
over the SPA-bus (or LON-bus), are connected to the EVENT function block as specified in Figure
376.

EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC07000065-2-en.vsd
IEC07000065 V2 EN-US

Figure 376: Connection of protection signals for event handling

676 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.7.4.1 Communication ports M11880-315 v7

The serial communication module (SLM) is a mezzanine module placed on the first analog digital
conversion module (ADM). It is used for LON, SPA, IEC 60870-5-103 and DNP communication.

In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for LON
protocol.

IEC16000079-1-en.vsd
IEC16000079 V1 EN-US

Figure 377: Rear view of 1/2 x 19” casing with 1 TRM slot
There are two types of IO connectors: snap-in connector for plastic fiber cables and ST/bayonet
connector for glass fiber cables. The SLM can be equipped with either type or connector or with a
combination of both types of connectors. This is identified with a tag.

Connect the incoming optical fiber to the RX receiver input, and the outgoing optical fiber to the TX
transmitter output. Pay special attention to the instructions concerning handling and connection of
fiber cables.

For setting the transfer rate (baud rate) and slave number, please refer to the Application manual and
Commissioning manual respectively.

16.7.5 Technical data IP14404-1 v1

M11901-1 v2

Table 596: SPA communication protocol

Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899

Transformer protection RET650 677


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8 IEC 60870-5-103 communication protocol IP14615-1 v2

16.8.1 Introduction M11910-3 v3

IEC 60870-5-103 communication protocol is mainly used when a protection IED communicates with
a third party control or monitoring system. This system must have software that can interpret the IEC
60870-5-103 communication messages.

16.8.2 Measurands for IEC 60870-5-103 I103MEAS

16.8.2.1 Functionality GUID-557FB587-9127-4D99-B2C6-16445E06F220 v3

103MEAS is a function block that reports all valid measuring types depending on connected signals.

The set of connected input will control which ASDUs (Application Service Data Units) are generated.

• 9 Will be generated if at least IL1 is connected. IL2, IL3, UL1, UL2, UL3, P, Q, F are optional but
there can be no holes.
• 3.4 Will be generated if IN and UN are present.
• 3.3 Will be generated if IL2, Ul1L2, P and Q present.
• 3.2 Will be generated if IL2, UL1L2 and P or Q missing.
• 3.1 Will be generated if IL2 present and IL1 missing (otherwise IL2 in 9).

Description for I103MEAS function block:


9 = IL1
3.4 = IN AND UN
3.3 = IL2 AND UL1L2 AND P AND Q
3.2 = IL2 AND UL1L2 AND NOT 3.3
3.1 = IL2 AND NOT (3.2 OR 3.3 OR 9)

16.8.2.2 Identification
GUID-3E1AB624-1B68-4018-B1BA-BC2C811F8F74 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Measurands for IEC 60870-5-103 I103MEAS - -

16.8.2.3 Function block GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2

I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F

IEC10000287-1-en.vsd
IEC10000287 V1 EN-US

Figure 378: I103MEAS function block

678 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.2.4 Signals
PID-6625-INPUTSIGNALS v4

Table 597: I103MEAS Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of service value reporting
IL1 REAL 0.0 Service value for current phase L1
IL2 REAL 0.0 Service value for current phase L2
IL3 REAL 0.0 Service value for current phase L3
IN REAL 0.0 Service value for residual current IN
UL1 REAL 0.0 Service value for voltage phase L1
UL2 REAL 0.0 Service value for voltage phase L2
UL3 REAL 0.0 Service value for voltage phase L3
UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2
UN REAL 0.0 Service value for residual voltage UN
P REAL 0.0 Service value for active power
Q REAL 0.0 Service value for reactive power
F REAL 0.0 Service value for system frequency

16.8.2.5 Settings
PID-6625-SETTINGS v4

Table 598: I103MEAS Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)
MaxIL1 1 - 99999 A 1 3000 Maximum current phase L1
MaxIL2 1 - 99999 A 1 3000 Maximum current phase L2
MaxIL3 1 - 99999 A 1 3000 Maximum current phase L3
MaxIN 1 - 99999 A 1 3000 Maximum residual current IN
MaxUL1 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L1
MaxUL2 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L2
MaxUL3 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L3
MaxUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase L1-L2
MaxUN 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage UN
MaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active power
MaxQ 0.00 - 2000.00 MVAr 0.05 1200.00 Maximum value for reactive power
MaxF 15.0 - 66.0 Hz 1.0 51.0 Maximum system frequency

16.8.3 Measurands user defined signals for IEC 60870-5-103


I103MEASUSR

16.8.3.1 Functionality GUID-FC9ED4BD-F11C-4BDA-8CDB-3ACF00931D3A v1

I103MEASUSR is a function block with user defined input measurands in monitor direction. These
function blocks include the FunctionType parameter for each block in the private range, and the
Information number parameter for each block.

Transformer protection RET650 679


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.3.2 Identification
GUID-A9E21066-354B-453D-8D9B-E86EE31CF5F9 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Measurands user defined signals for I103MEASUSR - -
IEC 60870-5-103

16.8.3.3 Function block GUID-C234101E-F9B9-4DB0-874C-C51BB50588CB v1

I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9

IEC10000288-1-en.vsd
IEC10000288 V1 EN-US

Figure 379: I103MEASUSR function block

16.8.3.4 Signals
PID-3791-INPUTSIGNALS v5

Table 599: I103MEASUSR Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of service value reporting
INPUT1 REAL 0.0 Service value for measurement on input 1
INPUT2 REAL 0.0 Service value for measurement on input 2
INPUT3 REAL 0.0 Service value for measurement on input 3
INPUT4 REAL 0.0 Service value for measurement on input 4
INPUT5 REAL 0.0 Service value for measurement on input 5
INPUT6 REAL 0.0 Service value for measurement on input 6
INPUT7 REAL 0.0 Service value for measurement on input 7
INPUT8 REAL 0.0 Service value for measurement on input 8
INPUT9 REAL 0.0 Service value for measurement on input 9

16.8.3.5 Settings
PID-3791-SETTINGS v5

Table 600: I103MEASUSR Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 25 Function type (1-255)
InfNo 1 - 255 - 1 1 Information number for measurands
(1-255)
MaxMeasur1 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 1
MaxMeasur2 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 2
Table continues on next page

680 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Values (Range) Unit Step Default Description


MaxMeasur3 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 3
MaxMeasur4 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 4
MaxMeasur5 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 5
MaxMeasur6 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 6
MaxMeasur7 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 7
MaxMeasur8 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 8
MaxMeasur9 0.05 - - 0.05 1000.00 Maximum value for measurement on input
10000000000.00 9

16.8.4 Function status auto-recloser for IEC 60870-5-103 I103AR

16.8.4.1 Functionality GUID-7A132276-35A2-402C-9722-6259D65998F5 v1

I103AR is a function block with defined functions for autorecloser indications in monitor direction.
This block includes the FunctionType parameter, and the information number parameter is defined
for each output signal.

16.8.4.2 Identification
GUID-7B066282-79D7-480B-BEDE-3C04F0FCBF05 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status auto-recloser for IEC I103AR - -
60870-5-103

16.8.4.3 Function block GUID-FAC5A3DF-73CB-4A39-A213-5C21ACA05756 v1

I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD

IEC10000289-2-en.vsd
IEC10000289 V2 EN-US

Figure 380: I103AR function block

16.8.4.4 Signals
PID-3973-INPUTSIGNALS v5

Table 601: I103AR Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
16_ARACT BOOLEAN 0 Information number 16, auto-recloser active
128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-recloser
130_BLKD BOOLEAN 0 Information number 130, auto-recloser blocked

Transformer protection RET650 681


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.4.5 Settings
PID-3973-SETTINGS v5

Table 602: I103AR Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)

16.8.5 Function status earth-fault for IEC 60870-5-103 I103EF GUID-F23B392E-B55D-4BC3-A0A6-B7992D551092 v1

16.8.5.1 Functionality GUID-13F90E95-7C8C-4DCB-A9D8-2489B66DB81A v2

I103EF is a function block with defined functions for earth fault indications in monitor direction. This
block includes the FunctionType parameter, and the information number parameter is defined for
each output signal.

16.8.5.2 Identification
GUID-033731B7-1B71-4CCC-8356-1C03CBCB23FA v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status earth-fault for IEC I103EF - -
60870-5-103

16.8.5.3 Function block GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1

I103EF
BLOCK
51_EFFW
52_EFREV

IEC10000290-1-en.vsd
IEC10000290 V1 EN-US

Figure 381: I103EF function block

16.8.5.4 Signals
PID-3974-INPUTSIGNALS v5

Table 603: I103EF Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, earth-fault forward
52_EFREV BOOLEAN 0 Information number 52, earth-fault reverse

16.8.5.5 Settings
PID-3974-SETTINGS v5

Table 604: I103EF Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 160 Function type (1-255)

682 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.6 Function status fault protection for IEC 60870-5-103


I103FLTPROT

16.8.6.1 Functionality GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1

I103FLTPROT is used for fault indications in monitor direction. Each input on the function block is
specific for a certain fault type and therefore must be connected to a correspondent signal present in
the configuration. For example: 68_TRGEN represents the General Trip of the device, and therefore
must be connected to the general trip signal SMPPTRC_TRIP or equivalent.

The delay observed in the protocol is the time difference in between the signal that is triggering the
Disturbance Recorder and the respective configured signal to the IEC 60870-5-103 I103FLTPROT.

16.8.6.2 Identification
GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status fault protection for IEC I103FLTPROT - -
60870-5-103

16.8.6.3 Function block GUID-F0ED13B8-6B82-4CA7-8F22-C200C33EBB7E v2

I103FLTPROT
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
83_ZONE6
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291-2-en.vsdx

IEC10000291 V2 EN-US

Figure 382: I103FLTPROT function block

Transformer protection RET650 683


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.6.4 Signals
PID-6864-INPUTSIGNALS v1

Table 605: I103FLTPROT Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting.
64_STL1 BOOLEAN 0 Information number 64, start phase L1
65_STL2 BOOLEAN 0 Information number 65, start phase L2
66_STL3 BOOLEAN 0 Information number 66, start phase L3
67_STIN BOOLEAN 0 Information number 67, start residual current IN
68_TRGEN BOOLEAN 0 Information number 68, trip general
69_TRL1 BOOLEAN 0 Information number 69, trip phase L1
70_TRL2 BOOLEAN 0 Information number 70, trip phase L2
71_TRL3 BOOLEAN 0 Information number 71, trip phase L3
72_TRBKUP BOOLEAN 0 Information number 72, back up trip I>>
73_SCL REAL 0 Information number 73, fault location in ohm
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/busbar
76_TRANS BOOLEAN 0 Information number 76, signal transmitted
77_RECEV BOOLEAN 0 Information number 77, signal received
78_ZONE1 BOOLEAN 0 Information number 78, zone 1
79_ZONE2 BOOLEAN 0 Information number 79, zone 2
80_ZONE3 BOOLEAN 0 Information number 80, zone 3
81_ZONE4 BOOLEAN 0 Information number 81, zone 4
82_ZONE5 BOOLEAN 0 Information number 82, zone 5
83_ZONE6 BOOLEAN 0 Information number 83, zone 6
84_STGEN BOOLEAN 0 Information number 84, start general
85_BFP BOOLEAN 0 Information number 85, breaker failure
86_MTRL1 BOOLEAN 0 Information number 86, trip measuring system phase L1
87_MTRL2 BOOLEAN 0 Information number 87, trip measuring system phase L2
88_MTRL3 BOOLEAN 0 Information number 88, trip measuring system phase L3
89_MTRN BOOLEAN 0 Information number 89, trip measuring system neutral N
90_IOC BOOLEAN 0 Information number 90, over current trip, stage low
91_IOC BOOLEAN 0 Information number 91, over current trip, stage high
92_IEF BOOLEAN 0 Information number 92, earth-fault trip, stage low
93_IEF BOOLEAN 0 Information number 93, earth-fault trip, stage high
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-CALCMADE)

16.8.6.5 Settings
PID-6864-SETTINGS v1

Table 606: I103FLTPROT Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 128 Function type (1-255)

684 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.7 IED status for IEC 60870-5-103 I103IED

16.8.7.1 Functionality GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1

I103IED is a function block with defined IED functions in monitor direction. This block uses parameter
as FunctionType, and information number parameter is defined for each input signal.

16.8.7.2 Identification
GUID-5EEBE11C-C8E3-4A8A-814F-840E137DB5B5 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED status for IEC 60870-5-103 I103IED - -

16.8.7.3 Function block GUID-421D5C37-27A5-476A-A7D9-40E70AFDFDC8 v1

I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4

IEC10000292-2-en.vsd
IEC10000292 V2 EN-US

Figure 383: I103IED function block

16.8.7.4 Signals
PID-3975-INPUTSIGNALS v5

Table 607: I103IED Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
22_SETCH BOOLEAN 0 Information number 22, setting changed
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active

16.8.7.5 Settings
PID-3975-SETTINGS v5

Table 608: I103IED Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)

Transformer protection RET650 685


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.8 Supervison status for IEC 60870-5-103 I103SUPERV

16.8.8.1 Functionality GUID-E7A28D8D-398E-437C-9B58-AE125BC38058 v1

I103SUPERV is a function block with defined functions for supervision indications in monitor
direction. This block includes the FunctionType parameter, and the information number parameter is
defined for each output signal.

16.8.8.2 Identification
GUID-C8113B08-3586-412C-A750-606159B1E97E v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Supervison status for IEC 60870-5-103 I103SUPERV - -

16.8.8.3 Function block GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1

I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL

IEC10000293-1-en.vsd
IEC10000293 V1 EN-US

Figure 384: I103SUPERV function block

16.8.8.4 Signals
PID-3976-INPUTSIGNALS v5

Table 609: I103SUPERV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm

16.8.8.5 Settings
PID-3976-SETTINGS v5

Table 610: I103SUPERV Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)

686 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.9 Status for user defined signals for IEC 60870-5-103


I103USRDEF

16.8.9.1 Functionality GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3

I103USRDEF is a function block with user defined input signals in monitor direction. Each instance is
associated with a Function Type (FUN) and each input signal with an Information Number (INF).
Additionally, all input signals may be defined to use relative time and how to respond to a GI request.

The user is responsible for assigning a proper FUN value and proper INF values to all connected
inputs. See Settings for details.

16.8.9.2 Identification
GUID-474FDF39-CEFC-4370-9393-13BE62159969 v2

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Status for user defined signals for IEC I103USRDEF - -
60870-5-103

16.8.9.3 Function block GUID-B8312E77-514D-4117-BB31-B9907755580C v1

I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START

IEC10000294-3-en.vsdx

IEC10000294 V3 EN-US

Figure 385: I103USRDEF function block

16.8.9.4 Signals
PID-6485-INPUTSIGNALS v5

Table 611: I103USRDEF Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
INPUT1 BOOLEAN 0 Binary signal Input 1
INPUT2 BOOLEAN 0 Binary signal input 2
INPUT3 BOOLEAN 0 Binary signal input 3
INPUT4 BOOLEAN 0 Binary signal input 4
INPUT5 BOOLEAN 0 Binary signal input 5
INPUT6 BOOLEAN 0 Binary signal input 6
Table continues on next page

Transformer protection RET650 687


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Name Type Default Description


INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8
RT_START BOOLEAN 0 Trig to set base of relative time

GUID-9E29DE39-EA74-4D62-A2BA-F8E31A3D8757 v2
RT_START registers the positive transition (0->1) of a pulse and sets the time from which relative
time is derived. Relative time is assigned only to inputs where the corresponding TypNo parameter is
set to Relative. The maximum relative time and unit conform to the IEC 60870-5-103 standard.

16.8.9.5 Settings
PID-6485-SETTINGS v5

Table 612: I103USRDEF Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 5 Function type (1-255)
InfNo1 1 - 255 - 1 1 Information number for binary input 1
(1-255)
InfNo2 1 - 255 - 1 2 Information number for binary input 2
(1-255)
InfNo3 1 - 255 - 1 3 Information number for binary input 3
(1-255)
InfNo4 1 - 255 - 1 4 Information number for binary input 4
(1-255)
InfNo5 1 - 255 - 1 5 Information number for binary input 5
(1-255)
InfNo6 1 - 255 - 1 6 Information number for binary input 6
(1-255)
InfNo7 1 - 255 - 1 7 Information number for binary input 7
(1-255)
InfNo8 1 - 255 - 1 8 Information number for binary input 8
(1-255)
TypNo1 Absolute - - Absolute Type identification (TYP)
Relative
TypNo2 Absolute - - Absolute Type identification (TYP)
Relative
TypNo3 Absolute - - Absolute Type identification (TYP)
Relative
TypNo4 Absolute - - Absolute Type identification (TYP)
Relative
TypNo5 Absolute - - Absolute Type identification (TYP)
Relative
TypNo6 Absolute - - Absolute Type identification (TYP)
Relative
TypNo7 Absolute - - Absolute Type identification (TYP)
Relative
TypNo8 Absolute - - Absolute Type identification (TYP)
Relative
GiNo1 Excluded - - Included Response and status change (GI)
Included
GiNo2 Excluded - - Included Response and status change (GI)
Included
GiNo3 Excluded - - Included Response and status change (GI)
Included
GiNo4 Excluded - - Included Response and status change (GI)
Included
Table continues on next page

688 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Values (Range) Unit Step Default Description


GiNo5 Excluded - - Included Response and status change (GI)
Included
GiNo6 Excluded - - Included Response and status change (GI)
Included
GiNo7 Excluded - - Included Response and status change (GI)
Included
GiNo8 Excluded - - Included Response and status change (GI)
Included

GUID-86DE9DBA-BE2F-4CC9-B447-1D2D86849EFF v2
The FunctionType parameter associates a particular instance of the function block with a FUN.
Refer to the IEC 60870-5-103 standard for details.

The InfNon parameters are used to associate each individual input signal with a userdefined INF.
Refer to the IEC 60870-5-103 standard for details.

The TypNon parameters determine if messages use absolute or relative time. This adheres to the
TYPE IDENTIFICATION (TYP) message types 1 (time-tagged message) and 2 (time-tagged
message with relative time) of the IEC 60870-5-103 standard.

The GiNon parameters determine whether a message is sent as a part of a GI reply or not. Refer to
the IEC 60870-5-103 standard for details.

16.8.10 Function commands for IEC 60870-5-103 I103CMD

16.8.10.1 Functionality GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v2

I103CMD is a command function block in control direction with pre-defined output signals. The
signals are in steady state, not pulsed, and stored in the IED in case of restart.

16.8.10.2 Identification
GUID-CFD43980-0791-40D1-9136-CF4CCC35549A v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands for IEC I103CMD - -
60870-5-103

16.8.10.3 Function block GUID-C0680812-C488-4546-AA65-F590955DBF0C v1

I103CMD
BLOCK 16-AR
17-DIFF
18-PROT

IEC10000282-1-en.vsd
IEC10000282 V1 EN-US

Figure 386: I103CMD function block

16.8.10.4 Signals
PID-3969-INPUTSIGNALS v5

Table 613: I103CMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of commands

Transformer protection RET650 689


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

PID-3969-OUTPUTSIGNALS v5

Table 614: I103CMD Output signals

Name Type Description


16-AR BOOLEAN Information number 16, off/on of autorecloser
17-DIFF BOOLEAN Information number 17, block of differential protection
18-PROT BOOLEAN Information number 18, block of protection

16.8.10.5 Settings
PID-3969-SETTINGS v5

Table 615: I103CMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)

16.8.11 IED commands for IEC 60870-5-103 I103IEDCMD

16.8.11.1 Functionality GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5

I103IEDCMD is a command block in control direction with defined IED functions. All outputs are
pulsed and they are NOT stored. Pulse length is fixed to 400ms.

16.8.11.2 Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED commands for IEC 60870-5-103 I103IEDCMD - -

16.8.11.3 Function block GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1

I103IEDCMD
BLOCK 19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4

IEC10000283-1-en.vsd
IEC10000283 V1 EN-US

Figure 387: I103IEDCMD function block

16.8.11.4 Signals
PID-3788-INPUTSIGNALS v5

Table 616: I103IEDCMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of commands

690 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

PID-3788-OUTPUTSIGNALS v5

Table 617: I103IEDCMD Output signals

Name Type Description


19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4

16.8.11.5 Settings
PID-3788-SETTINGS v5

Table 618: I103IEDCMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 255 Function type (1-255)

16.8.12 Function commands user defined for IEC 60870-5-103


I103USRCMD

16.8.12.1 Functionality GUID-2989EAC8-20BE-46EE-93FE-C70188D0BC89 v1

I103USRCMD is a command block in control direction with user defined output signals. These
function blocks include the FunctionType parameter for each block in the private range, and the
Information number parameter for each output signal.

16.8.12.2 Identification
GUID-9D6D1636-36C6-4C4E-B157-2D827820DDC7 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands user defined for I103USRCMD - -
IEC 60870-5-103

16.8.12.3 Function block GUID-5EBEAED5-ABD9-4257-B879-DF7FD9F7805A v1

I103USRCMD
BLOCK ^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8

IEC10000284-1-en.vsd
IEC10000284 V1 EN-US

Figure 388: I103USRCMD function block

Transformer protection RET650 691


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.12.4 Signals
PID-3790-INPUTSIGNALS v5

Table 619: I103USRCMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of commands

PID-3790-OUTPUTSIGNALS v5

Table 620: I103USRCMD Output signals

Name Type Description


OUTPUT1 BOOLEAN Command output 1
OUTPUT2 BOOLEAN Command output 2
OUTPUT3 BOOLEAN Command output 3
OUTPUT4 BOOLEAN Command output 4
OUTPUT5 BOOLEAN Command output 5
OUTPUT6 BOOLEAN Command output 6
OUTPUT7 BOOLEAN Command output 7
OUTPUT8 BOOLEAN Command output 8

16.8.12.5 Settings
PID-3790-SETTINGS v5

Table 621: I103USRCMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseMode Steady - - Pulsed Pulse mode
Pulsed
PulseLength 0.200 - 60.000 s 0.001 0.400 Pulse length
InfNo_1 1 - 255 - 1 1 Information number for output 1 (1-255)
InfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)
InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)
InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)
InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)
InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)
InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)
InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)

16.8.13 Function commands generic for IEC 60870-5-103 I103GENCMD

16.8.13.1 Functionality GUID-729E9AFD-0468-4BBD-B54A-A6CDCC68A9B2 v3

I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The function has
two outputs signals CMD_OFF and CMD_ON that can be used to implement double-point command
schemes.

The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steady ON/OFF
outputs. The ON output is pulsed with a command with value 2, while the OFF output is pulsed with a
command value 1. If in steady mode is ON asserted and OFF deasserted with command 2 and vice
versa with command 1. Steady mode is selected by setting PulseLength=0. The I103GENCMD is
retained, and a command in steady mode will be reissued on restart.

692 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.13.2 Identification
GUID-1933A30C-5214-4116-8CD3-91BD975FACED v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands generic for IEC I103GENCMD - -
60870-5-103

16.8.13.3 Function block GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1

I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON

IEC10000285-1-en.vsd
IEC10000285 V1 EN-US

Figure 389: I103GENCMD function block

16.8.13.4 Signals
PID-3970-INPUTSIGNALS v5

Table 622: I103GENCMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of command

PID-3970-OUTPUTSIGNALS v5

Table 623: I103GENCMD Output signals

Name Type Description


CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON

16.8.13.5 Settings
PID-3970-SETTINGS v5

Table 624: I103GENCMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 1 - 255 - 1 1 Information number for command output
(1-255)

16.8.14 IED commands with position and select for IEC 60870-5-103
I103POSCMD

16.8.14.1 Functionality GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v8

I103POSCMD is a transceiver function that monitors activity on its input signals and interprets any
state transition into commands then sent over an established IEC 60870-5-103 link. Additionally, it
listens for general interrogation (GI) requests and replies to those with a GI response message with
the current state of each connected input.

Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However, the

Transformer protection RET650 693


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

intermediate and faulty states may be suppressed by setting the Report Intermediate Position = Off.
See the settings for RS485 and optical serial communication for more information.

Input SELECT is a single-indication signal, and it is also GI enabled. State transitions to ON and OFF
are reported spontaneously.

When input BLOCK is ON, the function will ignore GI requests and cease all monitoring activity.
Consequently, no transitions will be detected.

The I103POSCMD function is also equipped with three additional commands: Select, Operate and
Cancel. These are hidden in ACT and respond only to the base INF+1, INF+2 and INF+3
respectively. The base INF (Information Number) parameter is an IEC 60870-5-103 identifier that
associates a function in a 103 Master (such as Scada) with its equivalent in the IED.

16.8.14.2 Identification
GUID-ABF81C27-4605-4A15-9CF5-77FF82DE8747 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED commands with position and select I103POSCMD - -
for IEC 60870-5-103

16.8.14.3 Function block GUID-3A31C1F2-1FB5-4DB0-A698-AD3F55738DB1 v1

I103POSCMD
BLOCK
POSITION
SELECT

IEC10000286-1-en.vsd
IEC10000286 V1 EN-US

Figure 390: I103POSCMD function block

16.8.14.4 Signals
PID-6997-INPUTSIGNALS v1

Table 625: I103POSCMD Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of status reporting
POSITION INTEGER 0 Position of controllable object
SELECT BOOLEAN 0 Select of controllable object

16.8.14.5 Settings
PID-6997-SETTINGS v1

Table 626: I103POSCMD Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type
InfNo 160 - 236 - 4 160 Information number for command output

694 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.8.15 IED commands with position for IEC 60870-5-103


I103POSCMDV

16.8.15.1 Functionality GUID-CF04D9AC-40BE-46A3-A418-77204D2B0F27 v3

I103POSCMDV is a transceiver function that monitors activity on its input signals and interprets any
state transition into commands sent over an established IEC 60870-5-103 link. Additionally, it listens
for general interrogation (GI) requests, and replies to those with a GI response message with the
current state of each connected input.

Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However, the
intermediate and faulty states may be suppressed by setting the Report Intermediate Position = Off.
See the settings for RS485 and optical serial communication for more information.

When input BLOCK is ON, the function ignores GI requests and ceases all monitoring activity.
Consequently, no transitions will be detected.

16.8.15.2 Identification
GUID-2249B679-03E4-43CC-B690-916246FE6A31 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED direct commands with position for I103POSCMDV - -
IEC 60870-5-103

16.8.15.3 Function block GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1

I103POSCMDV
BLOCK
POSITION
IEC15000081-2-en.vsdx

IEC15000081 V2 EN-US

Figure 391: I103POSCMDV function block

16.8.15.4 Signals
PID-6578-INPUTSIGNALS v5

Table 627: I103POSCMDV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of command
POSITION INTEGER 0 Position of controllable object

Transformer protection RET650 695


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.8.15.5 Settings
PID-6578-SETTINGS v6

Table 628: I103POSCMDV Non group settings (basic)

Name Values (Range) Unit Step Default Description


FunctionType 1 - 255 - 1 1 Function type
InfNo 160 - 209 - 1 160 Information number for command output

16.8.16 Operation principle IP14407-1 v3

16.8.16.1 General M11874-3 v5

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication


exchanging information with a control system, and with a data transfer rate up to 38400 bit/s. In IEC
terminology, a primary station is a master and a secondary station is a slave. The communication is
based on a point-to-point principle. The master must have software that can interpret IEC
60870-5-103 communication messages.

Introduction to IEC 60870–5–103 protocol M11874-6 v3


IEC 60870-5-103 protocol functionality consists of the following functions:

• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization

For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part 5:
Transmission protocols, and to the section 103: Companion standard for the informative interface of
protection equipment.

IEC 60870-5-103 vendor specific implementation M11874-23 v4


The signal and setting tables specify the information types supported by the IEDs with the
communication protocol IEC 60870-5-103 implemented.

The information types are supported when corresponding functions are included in the protection and
control IED.

Be aware of that different cycle times for function blocks must be considered to ensure
correct time stamping.

Commands in control direction M11874-27 v1


Commands in control direction, I103IEDCMD M11874-29 v6
Command block in control direction with defined output signals.

Number of instances: 1

Function type is selected with parameter FunctionType.

696 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Information number is defined for each output signals.

Table 629: I103IEDCMD supported indications

INF Description
19 LED Reset
23 Activate setting group 1
24 Activate setting group 2
25 Activate setting group 3
26 Activate setting group 4

Function commands in control direction, pre-defined I103CMD M11874-53 v6


Function command block in control direction with defined output signals.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signals.

Table 630: Pre-defined I103CMD supported indications

INF Description
16 Auto-recloser on/off
17 Teleprotection on/off
18 Protection on/off

Function commands in control direction, user-defined, I103USRCMD M11874-72 v6


Function command blocks in control direction with user-defined output signals.

Number of instances: 4

Function type for each function block instance in private range is selected with parameter
FunctionType.

Information number must be selected for each output signal. Default values are 1 - 8.

Table 631: I103USRCMD supported indications

INF 1) Description
1 Output signal 01
2 Output signal 02
3 Output signal 03
4 Output signal 04
5 Output signal 05
6 Output signal 06
7 Output signal 07
8 Output signal 08

1) User defined information number

Status M11874-107 v1
Terminal status indications in monitor direction, I103IED M11874-109 v7
Indication block for status in monitor direction with defined IED functions.

Number of instances: 1

Transformer protection RET650 697


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Function type is selected with parameter FunctionType.

Information number is defined for each input signals.

Table 632: I103IED supported functions

INF Description
19 LED reset
21 TestMode
22 Local Parameter setting
23 Setting group 1 active
24 Setting group 2 active
25 Setting group 3 active
26 Setting group 4 active

Function status indications in monitor direction, user-defined, I103USRDEF M11874-137 v7


Function indication block in monitor direction with user-defined input signals.

Number of instances: 20

Function type is selected with parameter FunctionType.

Information number is required for each input signal.

Table 633: I103USRDEF Information number default values

INF Description GI TYP COT


11) Input signal 01 x/- 1/2 1,7,(9)
2* Input signal 02 x/- 1/2 1,7,(9)
3* Input signal 03 x/- 1/2 1,7,(9)
4* Input signal 04 x/- 1/2 1,7,(9)
5* Input signal 05 x/- 1/2 1,7,(9)
6* Input signal 06 x/- 1/2 1,7,(9)
7* Input signal 07 x/- 1/2 1,7,(9)
8* Input signal 08 x/- 1/2 1,7,(9)

1) * User defined information number

Supervision indications in monitor direction, I103SUPERV M11874-171 v7


Indication block for supervision in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for output signals.

Table 634: I103SUPERV supported functions

INF Description TYP GI COT


32 Measurand supervision I 1 Y 1,7,9
33 Measurand supervision U 1 Y 1,7,9
37 I>>back-up operation 1 Y 1,7,9
Table continues on next page

698 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

INF Description TYP GI COT


38 VT fuse failure 1 Y 1,7,9
46 Group warning 1 Y 1,7,9
47 Group alarm 1 Y 1,7,9

Earth fault indications in monitor direction, I103EF M11874-199 v8


Indication block for earth fault in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signal.

Table 635: I103EF supported indications

INF Description
51 Earth fault forward
52 Earth fault reverse

Autorecloser indications in monitor direction, I103AR M11874-363 v6


Indication block for autorecloser in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signal.

Table 636: I103AR supported indications

INF Description
16 Autorecloser active
128 CB on by Autorecloser
130 Autorecloser blocked

Function status fault protection for IEC 60870-5-103, I103FLTPROT GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6


Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each input signal.

Table 637: I103FLTPROT supported functions

INF Description TYP GI COT


64 Start phase L1 2 Y 1,7,9
65 Start phase L2 2 Y 1,7,9
66 Start phase L3 2 Y 1,7,9
67 Start residual current IN 2 Y 1,7,9
68 Trip general 2 N 1,7
69 Trip phase L1 2 N 1,7
70 Trip phase L2 2 N 1,7
71 Trip phase L3 2 N 1,7
Table continues on next page

Transformer protection RET650 699


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

INF Description TYP GI COT


72 Back up trip I>> 2 N 1,7
73 Fault location in ohm 4 N 1,7
74 Forward/line 2 N 1,7
75 Reverse/busbar 2 N 1,7
76 Signal transmitted 2 N 1,7
77 Signal received 2 N 1,7
78 Zone 1 2 N 1,7
79 Zone 2 2 N 1,7
80 Zone 3 2 N 1,7
81 Zone 4 2 N 1,7
82 Zone 5 2 N 1,7
83 Zone 6 2 N 1,7
84 Start general 2 Y 1,7,9
85 Breaker failure 2 N 1,7
86 Trip measuring system phase L1 2 N 1,7
87 Trip measuring system phase L2 2 N 1,7
88 Trip measuring system phase L3 2 N 1,7
89 Trip measuring system neutral N 2 N 1,7
90 Over current trip, stage low 2 N 1,7
91 Over current trip, stage high 2 N 1,7
92 Earth-fault trip, stage low 2 N 1,7
93 Earth-fault trip, stage high 2 N 1,7

Measurands M11874-382 v2
Function blocks in monitor direction for input measurands. Typically connected to monitoring function,
for example to power measurement CVMMXN.

Measurands in public range, I103MEAS M11874-385 v8


Number of instances: 1

The IED reports all valid measuring types depending on connected signals.

Upper limit for measured currents, active/reactive-power is 2.4 times rated value.

Upper limit for measured voltages and frequency is 1.2 times rated value.

The upper limit is the maximum value that can be encoded into the ASDU (Application Service Data
Unit). Any value higher than this value will be tagged as OVERFLOW. The factors 1.2 and 2.4 are
taken from the 103 standard and require that a rated value to use as base exists, and then use 1.2 or
2.4 times <rated> as maxVal. You can use 2.4 times rated as maxVal, but as there is no way to
propagate value to client, the use of a scale factor on <rated> does not make much difference.

You can configure client:client-scaled-max ::= 1.2 * <rated> or client-scaled-


max ::= 1.0 * <maxVal>

If the client has a hard-coded gain of 1.2 * <rated> then client-scaled-max ::= 1.2 times
<maxVal>/1.2

Resolution is <maxVal> / 4095 and hence the lowest possible maxVal yields the best accuracy.

700 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Table 638: I103MEAS supported indications

INF Description
148 IL1
144, 145, IL2
146, 148
148 IL3
147 IN, Neutral current
148 UL1
148 UL2
148 UL3
145, 146 UL1-UL2
147 UN, Neutral voltage
146, 148 P, active power
146, 148 Q, reactive power
148 f, frequency

Measurands in private range, I103MEASUSR M11874-431 v5


Number of instances: 3

Function type parameter for each block in private range.

Information number must be selected for measurands.

Table 639: I103MEASUSR supported indications

INF FUN GI TYP COT Description


*1) *2) No, polled *3) 2,7 Meas1
with CL2
* * No, polled * 2,7 Meas2
with CL2
* * No, polled * 2,7 Meas3
with CL2
* * No, polled * 2,7 Meas4
with CL2
* * No, polled * 2,7 Meas5
with CL2
* * No, polled * 2,7 Meas6
with CL2
* * No, polled * 2,7 Meas7
with CL2
* * No, polled * 2,7 Meas8
with CL2
* * No, polled * 2,7 Meas9
with CL2

1) * User defined information value (PARAM.3)


2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is defined by
semantics of connected source.

<Number of information elements> is defined by index of first input not connected.

Example: Input1, Input2, and Input4 are connected, Input3 is not connected.

<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that is, only Input1 and
Input2 will be transmitted.

Transformer protection RET650 701


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Disturbance recordings M11874-467 v7


The following elements are used in the ASDUs (Application Service Data Units) defined in the
standard.

Analog signals, 40-channels: the channel number for each channel has to be specified. Channels
used in the public range are 1 to 8 and with:

• IL1 connected to channel 1 on disturbance function block A1RADR


• IL2 connected to channel 2 on disturbance function block A1RADR
• IL3 connected to channel 3 on disturbance function block A1RADR
• IN connected to channel 4 on disturbance function block A1RADR
• UL1E connected to channel 5 on disturbance function block A1RADR
• UL2E connected to channel 6 on disturbance function block A1RADR
• UL3E connected to channel 7 on disturbance function block A1RADR
• UEN connected to channel 8 on disturbance function block A1RADR

Channel number used for the remaining 32 analog signals are numbers in the private range 64 to 95.

Binary signals, 128-channels: for each channel the user can specify a FUNCTION TYPE and an
INFORMATION NUMBER.
M11874-629 v7
Disturbance upload

All analog and binary signals that are recorded with disturbance recorder can be reported to the
master. The last eight disturbances that are recorded are available for transfer to the master. A
successfully transferred disturbance (acknowledged by the master) will not be reported to the master
again.

When a new disturbance is recorded by the IED a list of available recorded disturbances will be sent
to the master, an updated list of available disturbances can be sent whenever something has
happened to disturbances in this list. For example, when a disturbance is deleted (by other client, for
example, SPA) or when a new disturbance has been recorded or when the master has uploaded a
disturbance.

Deviations from the standard

Information sent in the disturbance upload is specified by the standard; however, some of the
information are adapted to information available in disturbance recorder in the IED series.

This section describes all data that is not exactly as specified in the standard.

ASDU23

In ‘list of recorded disturbances’ (ASDU23) an information element named SOF (status of fault)
exists. This information element consists of 4 bits and indicates whether:

• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event than start

The only information that is easily available is test-mode status. The other information is always set
(hard coded) to:

TP Recorded fault with trip. [1]


TM Disturbance data waiting for transmission [0]
OTEV Disturbance data initiated by other events [1]

702 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Another information element in ASDU23 is the FAN (fault number). According to the standard this is
a number that is incremented when a protection function takes action. FAN is equal to disturbance
number, which is incremented for each disturbance.

ASDU26 / ASDU31

When a disturbance has been selected by the master by sending ASDU24, the protection equipment
answers by sending ASDU26, which contains an information element named NOF (number of grid
faults). This number must indicate fault number in the power system,that is, a fault in the power
system with several trip and auto-reclosing has the same NOF (while the FAN must be incremented).
NOF is just as FAN, equal to disturbance number.

Interoperability, physical layer M11874-482 v4

Supported
Electrical Interface
EIA RS-485 Yes
number of loads 32
Optical interface
glass fiber Yes
plastic fiber
Transmission speed
9600 bit/s Yes
19200 bit/s Yes
Link Layer
DFC-bit used Yes
Connectors
connector F-SMA No
connector BFOC/2.5 Yes

Interoperability, application layer M11874-524 v3

Supported
Selection of standard ASDUs in monitoring direction
ASDU Yes
1 Time-tagged message Yes
2 Time-tagged message with rel. time Yes
3 Measurands I Yes
4 Time-tagged message with rel. time Yes
5 Identification Yes
6 Time synchronization Yes
8 End of general interrogation Yes
9 Measurands II Yes
10 Generic data No
11 Generic identification No
23 List of recorded disturbances Yes
26 Ready for transm. of disturbance data Yes
27 Ready for transm. of a channel Yes
28 Ready for transm of tags Yes
29 Transmission of tags Yes
Table continues on next page

Transformer protection RET650 703


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

Supported
30 Transmission fo disturbance data Yes
31 End of transmission Yes
Selection of standard ASDUs in control direction
ASDU Yes
6 Time synchronization Yes
7 General interrogation Yes
10 Generic data No
20 General command Yes
21 Generic command Yes
24 Order for disturbance data transmission Yes
25 Acknowledgement for distance data transmission Yes
Selection of basic application functions
Test mode No
Blocking of monitoring direction Yes
Disturbance data Yes
Private data Yes
Generic services No

16.8.16.2 Communication ports M11874-626 v4

The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP and LON
communication. This module is a mezzanine module, and is placed assembled on the Numerical
module (NUM). The serial communication module can have connectors for two plastic fiber cables
(snap-in) or two glass fiber cables (ST, bayonet) or a combination of plastic and glass fiber. Three
different types are available depending on type of fiber.

The incoming optical fiber is connected to the RX receiver input, and the outgoing optical fiber to the
TX transmitter output. When the fiber optic cables are laid out, pay special attention to the
instructions concerning the handling and connection of the optical fibers. The module is identified
with a number on the label on the module.

16.8.17 Technical data IP14417-1 v1

M11921-1 v4

Table 640: IEC 60870-5-103 communication protocol

Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd

16.9 MULTICMDRCV and MULTICMDSND SEMOD119881-1 v3

GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Multiple command and receive MULTICMDRCV - -
Multiple command and send MULTICMDSND - -

704 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

16.9.1 Functionality M14790-3 v5

The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has 16
binary outputs.

16.9.2 Design SEMOD119958-1 v1

16.9.2.1 General M14792-3 v3

The common behavior for all 16 outputs of the MULTICMDRCV is set to either of two modes: Steady
or Pulse.

• 1 = Steady: This mode simply forwards the received signals to the binary outputs.
• 2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with a duration of
exactly one execution cycle is triggered on the corresponding binary output. This means that no
connected function block may have a cycle time that is higher than the execution cycle time of
the particular MULTICMDRCV instance.

16.9.3 Function block SEMOD119978-1 v1

SEMOD119976-5 v2

MULTICMDRCV
BLOCK ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID

IEC06000007-2-en.vsd
IEC06000007 V2 EN-US

Figure 392: MULTICMDRCV function block


SEMOD120009-4 v2

MULTICMDSND
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC06000008-2-en.vsd
IEC06000008 V2 EN-US

Figure 393: MULTICMDSND function block

Transformer protection RET650 705


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.9.4 Signals SEMOD119963-1 v2

PID-400-INPUTSIGNALS v10

Table 641: MULTICMDRCV Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function

PID-399-INPUTSIGNALS v10

Table 642: MULTICMDSND Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Input 1
INPUT2 BOOLEAN 0 Input 2
INPUT3 BOOLEAN 0 Input 3
INPUT4 BOOLEAN 0 Input 4
INPUT5 BOOLEAN 0 Input 5
INPUT6 BOOLEAN 0 Input 6
INPUT7 BOOLEAN 0 Input 7
INPUT8 BOOLEAN 0 Input 8
INPUT9 BOOLEAN 0 Input 9
INPUT10 BOOLEAN 0 Input 10
INPUT11 BOOLEAN 0 Input 11
INPUT12 BOOLEAN 0 Input 12
INPUT13 BOOLEAN 0 Input 13
INPUT14 BOOLEAN 0 Input 14
INPUT15 BOOLEAN 0 Input 15
INPUT16 BOOLEAN 0 Input 16

PID-400-OUTPUTSIGNALS v10

Table 643: MULTICMDRCV Output signals

Name Type Description


ERROR BOOLEAN MultiReceive error
NEWDATA BOOLEAN New data is received
OUTPUT1 BOOLEAN Output 1
OUTPUT2 BOOLEAN Output 2
OUTPUT3 BOOLEAN Output 3
OUTPUT4 BOOLEAN Output 4
OUTPUT5 BOOLEAN Output 5
OUTPUT6 BOOLEAN Output 6
OUTPUT7 BOOLEAN Output 7
OUTPUT8 BOOLEAN Output 8
OUTPUT9 BOOLEAN Output 9
OUTPUT10 BOOLEAN Output 10
OUTPUT11 BOOLEAN Output 11
OUTPUT12 BOOLEAN Output 12
OUTPUT13 BOOLEAN Output 13
OUTPUT14 BOOLEAN Output 14
Table continues on next page

706 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

Name Type Description


OUTPUT15 BOOLEAN Output 15
OUTPUT16 BOOLEAN Output 16
VALID BOOLEAN Output data is valid

PID-399-OUTPUTSIGNALS v10

Table 644: MULTICMDSND Output signals

Name Type Description


ERROR BOOLEAN MultiSend error

16.9.5 Settings SEMOD119927-1 v2

PID-400-SETTINGS v10

Table 645: MULTICMDRCV Non group settings (basic)

Name Values (Range) Unit Step Default Description


tMaxCycleTime 0.050 - 200.000 s 0.001 11.000 Maximum cycle time between receptions
of input data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum cycle time between receptions
of input data
Mode Steady - - Steady Mode for output signals
Pulsed
tPulseTime 0.000 - 60.000 s 0.001 0.200 Pulse length for multi command outputs

PID-399-SETTINGS v10

Table 646: MULTICMDSND Non group settings (basic)

Name Values (Range) Unit Step Default Description


tMaxCycleTime 0.000 - 200.000 s 0.001 5.000 Maximum time interval between
transmission of output data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum time interval between
transmission of output data

16.9.6 Operation principle M14793-3 v3

There are 10 instances of the MULTICMDSND function block. The first two are fast (8 ms cycle time)
while the others are slow (100 ms cycle time). Each instance has 16 binary inputs, to which 16
independent signals can be connected. Connected signals are sent through MULTICMDSND to the
receiving equivalent, MULTICMDRCV, located on a different IED.

The MULTICMDRCV function block has 16 binary outputs, all controlled through the command block
of one or many MULTICMDSND function blocks. There are 60 instances of the MULTICMDRCV
where the first 12 are fast (8 ms), and the others are slow (100 ms). Additionally, the MULTICMDRCV
has a supervision function, which sets the output connector "VALID" to 0 (zero) if its block does not
receive any data within the time defined by tMaxCycleTime.

LON connections are established using LON network tool (LNT).

16.10 Activity logging parameters ACTIVLOG

16.10.1 Activity logging ACTIVLOG GUID-BED7C3D6-6BE3-4DAC-84B3-92239E819CC0 v3

ACTIVLOG contains all settings for activity logging.

Transformer protection RET650 707


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

There can be 6 external log servers to send syslog events to. Each server can be configured with IP
address; IP port number and protocol format. The format can be either syslog (RFC 3164 or RFC
5424) or Common Event Format (CEF) from ArcSight.

16.10.2 Settings
PID-7978-SETTINGS v1

Table 647: ACTIVLOG Non group settings (basic)

Name Values (Range) Unit Step Default Description


SysLogFormat RFC 3164 - - RFC 3164 Parameter for selecting the Syslog format
RFC 5424
ExtLogSrv1Type Off - - Off External log server 1 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv1Port 1 - 65535 - 1 514 External log server 1 port number
ExtLogSrv1IP 0 - 18 IP 1 127.0.0.1 External log server 1 IP-address
Address
ExtLogSrv2Type Off - - Off External log server 2 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv2Port 1 - 65535 - 1 514 External log server 2 port number
ExtLogSrv2IP 0 - 18 IP 1 127.0.0.1 External log server 2 IP-address
Address
ExtLogSrv3Type Off - - Off External log server 3 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv3Port 1 - 65535 - 1 514 External log server 3 port number
ExtLogSrv3IP 0 - 18 IP 1 127.0.0.1 External log server 3 IP-address
Address
ExtLogSrv4Type Off - - Off External log server 4 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv4Port 1 - 65535 - 1 514 External log server 4 port number
ExtLogSrv4IP 0 - 18 IP 1 127.0.0.1 External log server 4 IP-address
Address
ExtLogSrv5Type Off - - Off External log server 5 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv5Port 1 - 65535 - 1 514 External log server 5 port number
ExtLogSrv5IP 0 - 18 IP 1 127.0.0.1 External log server 5 IP-address
Address
ExtLogSrv6Type Off - - Off External log server 6 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv6Port 1 - 65535 - 1 514 External log server 6 port number
ExtLogSrv6IP 0 - 18 IP 1 127.0.0.1 External log server 6 IP-address
Address

708 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 16
Station communication

GUID-CFD1D67E-27D3-453C-803C-820E7566CDB1 v1

If the ExtLogSrvXType parameter is SYSLOG UDP/IP or SYSLOG TXP/IP, then the


format of the syslog messages will be reported with RFC that is set on SysLogFormat
parameter.

16.11 IEC61850SIM

16.11.1 IEC 61850 simulation mode GUID-D31B9ECA-4C84-4CC7-BFE2-63FAFEA230EF v2

16.11.1.1 Identification GUID-3B85BB88-0C56-45D4-B99F-62C7F2F208D2 v2

Table 648: Identification

Function description Function block name IEC 60617 identification ANSI/IEEE C37.2 device
number
IEC 61850 simulation mode IEC61850SIM - -

16.11.1.2 Functionality GUID-472D29F9-3C0C-43D5-8C3E-8F97BD8B1F52 v2

This function is indicates simulation mode status to external world. LPHD has simulation status
output but it is not available in ACT, so IEC 61850 SIM component is added and it is just a
placeholder for simulation status which is configurable in ACT. This simulation status is displayed in
LHMI in this navigation mode Main menu -> Test -> IEC61850 simulation -> IEC61850SIM:1.

16.11.1.3 Function block GUID-14742551-70C1-4A80-805D-79195A51B4CE v1

IEC61850SIM
SIM
IEC20000107 V2 EN-US

Figure 394: IEC61850SIM function block

16.11.1.4 Signals
PID-7436-OUTPUTSIGNALS v2

Table 649: IEC61850SIM Output signals

Name Type Description


SIM BOOLEAN Simulation mode indication

16.11.1.5 Settings
PID-7436-SETTINGS v2

Table 650: IEC61850SIM Non group settings (basic)

Name Values (Range) Unit Step Default Description


AllowSimulation No - - No Allow simulated GOOSE values or
Yes simulated sampled measurand values

Transformer protection RET650 709


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 16 1MRK504170-UEN Rev. J
Station communication

16.11.1.6 Monitored Data


PID-7436-MONITOREDDATA v2

Table 651: IEC61850SIM Monitored data

Name Type Values (Range) Unit Description


ALLOWSIM BOOLEAN 0=No - Status of AllowSimulation setting
1=Yes
SIM BOOLEAN 0=Inactive - Simulation mode indication
1=Active

710 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

Section 17 Security
17.1 Authority check ATHCHCK

17.1.1 Identification
GUID-FBEF319B-94E6-41FB-BB9F-D870E0425128 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority check ATHCHCK - -

17.1.2 Functionality SEMOD117051-23 v7

To safeguard the interests of our customers, both the IED and the tools that are accessing the IED
are protected, by means of authorization handling. The authorization handling of the IED and the
PCM600 is implemented at both access points to the IED:

• local, through the local HMI


• remote, through the communication ports

The IED users can be created, deleted and edited with PCM600 IED user management tool.

IEC12000202 V3 EN-US

Figure 395: PCM600 user management tool

17.1.3 Operation principle GUID-B555EDD0-BAF1-4F0E-9162-BDB3A3468CF2 v10

There are different levels (or types) of users that can access or operate different areas of the IED
and tools functionality. The pre-defined user types are given in Table 652.

Transformer protection RET650 711


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

Ensure that the user logged on to the IED has the required access when writing particular
data to the IED from PCM600. For more information about setting user access rights, see
the PCM600 documentation.

The meaning of the legends used in the table:

• X= Full access rights


• R= Only reading rights
• - = No access rights

Table 652: Predefined user roles according to IEC 62351-8

Access rights VIEWER OPERATOR ENGINEER INSTALLER SECADM SECAUD RBACMNT ADMINISTRATOR
Config – Basic - - X X - - - -
Config – - - X X - - -
-
Advanced
FileTransfer – - - X X - - -
-
Tools
UserAdministratio - - - - X - X
X
n
Setting – Basic R - X X - - - -
Setting – R - X X - - -
-
Advanced
Control – Basic - X X - - - - -
Control – - X X - - - -
-
Advanced
IEDCmd – Basic - X X - - - - -
IEDCmd – - - X - - - -
-
Advanced
FileTransfer – - X X X X X X
X
Limited
DB Access normal - X X X X X X X
Audit log read - - - - - X - X
Setting – Change - X X X - - -
-
Setting Group
Security Advanced - - - - X - - X

Table 653: Access rights explanation

Access rights Explanation


Config – Basic Configuration – Basic is intended for engineers that only adapt an existing configuration e.g. the
I/O-Configuration using SMT
Config – Advanced Configuration – Advanced is intended for engineers that do the whole application engineering and
using e.g. ACT
FileTransfer – Tools FileTransfer – Tools is used for some configuration files for the configuration and shall have the
same value as Config – Advanced
UserAdministration UserAdministration is used to handle user management e.g. adding new user
Setting – Basic Setting – Basic is used for basic settings e.g. control settings and limit supervision
Setting – Advanced Setting – Advanced is used for the relay engineer to set settings e.g. for the protection functions
Control – Basic Control – Basic is used for a normal operator without possibility to bypass safety functions e.g.
interlock or synchro-check bypass
Control – Advanced Control – Advanced is used for an operator that is trusted to do process commands that can be
dangerous
IEDCmd – Basic IEDCmd – Basic is used for commands to the IED that are not critical e.g. Clear LEDs, manual
triggering of disturbances
Table continues on next page

712 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

Access rights Explanation


IEDCmd – Advanced IEDCmd – Advanced is used for commands to the IED that can hide information e.g. Clear
disturbance record
FileTransfer – Limited FileTransfer - Limited is used for access to disturbance files e.g. through FTP
DB Access normal Database access for normal user. This is needed for all users that access data from PCM
Audit log read Audit log read allows reading the audit log from the IED
Setting – Change Setting Group Setting – Change Setting Group is separated to be able to include the possibility to change the
setting group without changing any other setting
Security Advanced Security Advanced is the privilege required to do some of the more advanced security-related
settings

The IED users can be created, deleted and edited only with the IED User Management within
PCM600. The user can only LogOn or LogOff on the local HMI on the IED, there are no users,
groups or functions that can be defined on local HMI.

If the IED is Central Account Management enabled, users can only be created, deleted or
edited in the Central Account Management server. In that case, only the user rights can
be edited using the PCM600 tool. See Cyber Security Deployment Guidelines manual.

Only characters A - Z, a - z and 0 - 9 should be used in user names and passwords.


The maximum of characters in a password is 18.

At least one user must be included in the UserAdministrator group to be able to write
users, created in PCM600, to IED.

SEMOD176296-5 v10
At delivery the default user is the SuperUser. No Log on is required to operate the IED until a user
has been created with the IED User Management..

Once a user is created and downloaded to the IED, that user can perform a Log on, introducing the
password assigned in the tool.

If there is no user created, an attempt to log on will display a message box: “No user defined!”

If one user leaves the IED without logging off, then after the timeout (set in Main menu/Settings /
General Settings/HMI /Screen/Display Timeout ) elapses, the IED returns to Guest state, when
only reading is possible. The display time out is set to 10 minutes at delivery.

If there are one or more users created with the IED User Management and downloaded into the IED,
then, when a user intentionally attempts a Log on or when the user attempts to perform an operation
that is password protected, the Log on window will appear.

The cursor is focused on the User identity field, so upon pressing the key, the user can change
the user name, by browsing the list of users, with the “up” and “down” arrows. After choosing the right
user name, the user must press the “E” key again. When it comes to password, upon pressing the
key, the following character will show up: “$”. After all the letters are introduced (passwords are
case sensitive) choose OK and press the key again.

If everything is alright at a voluntary Log on, the local HMI returns to the Authorization screen. If the
Log on is OK, when required to change for example a password protected setting, the local HMI
returns to the actual setting folder. If the Log on has failed, then the Log on window opens again, until
either the user makes it right or presses “Cancel”.

Transformer protection RET650 713


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

17.1.3.1 Authorization with Central Account Management enabled IED GUID-1A836989-5D89-4F3D-B3A2-3BABCDFFB440 v3

The user rights can be edited in the IED by using the PCM600 user tool.

One user can have one or several user roles. By default, the users in Table 654 are created in the
IED, and when creating new users in the CAM server, the predefined roles from Table 655 can be
used.

At delivery, the IED user has full access as SuperUser when using the LHMI and as
Administrator when using FTP or PCM600 until Central Account Management is
activated.

Table 654: Default users

User name User rights


SuperUser Full rights, only presented in LHMI. LHMI is logged on by default until other users are defined
Guest Only read rights, only presented in LHMI. LHMI is logged on by default when other users are
defined (same as VIEWER)
Administrator Full rights. Password: Administrator. This user has to be used when reading out disturbances with
third party FTP-client.

Table 655: Predefined user roles according to IEC 62351-8

User roles Role explanation User rights


VIEWER Viewer Can read parameters and browse the menus from LHMI
OPERATOR Operator Can read parameters and browse the menus as well as perform control
actions
ENGINEER Engineer Can create and load configurations and change settings for the IED and
also run commands and manage disturbances
INSTALLER Installer Can load configurations and change settings for the IED
SECADM Security Can change role assignments and security settings. Can deploy
administrator certificates.
SECAUD Security auditor Can view audit logs
RBACMNT RBAC Can change role assignment
management
ADMINISTRATOR Administrator Sum of all rights for SECADM, SECAUD and RBACMNT
rights

This User role is vendor specific and not defined in


IEC 62351–8

Changes in user management settings do not cause an IED reboot.

The successful activation of Central Account Management will disable built-in users or remove all
local created users from PCM600.

Management of user credentials and roles is handled on the Central Account Management server
e.g. SDM600. The IED employs two strategies to ensure availability of the authentication system
even if there is a problem with the network or authentication server:

714 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

• A substation can be equipped with two redundant authentication servers operating in a hot
standby mode.
• If configured by the security administrator, the IED itself maintains a local replica in the database
with selected users. This database is periodically updated with data from the server and used as
fallback if none of the servers are reachable.
• If there is no replication support in the CAM server, then there is a possibility to configure the
emergency account in the IED, which gets activated when CAM server is offline.

Note that not all users in the SDM600 server are part of the replica. There might be users that are not
assigned to any replication group. IED only replicates those users which are part of replication group
configured in the IED.

All communication between the central management and the IEDs is protected using secure
communication. Customers are required to generate and distribute certificates during the engineering
process of the substation. These certificates ensure mutual trust between IED and CAM server for
example SDM600.

Table 656: Authority-related IED functions

Function Description
Authority status This function is an indication function block for user logon activity.
ATHSTAT User denied attempt to logon and user successful logon are reported.
Authority check To safeguard the interests of our customers, both the IED and the tools that are accessing
ATHCHCK the IED are protected, by means of authorization handling. The authorization handling of the
IED and the PCM600 is implemented at both access points to the IED:

• local, through the local HMI


• remote, through the communication ports

The IED users can be created, deleted and edited only in the CAM server.
Authority management This function enables/disables the maintenance menu. It also controls the maintenance
AUTHMAN menu logon time out.

For more information on the functions Authority Management (AUTHMAN), Authority Status
(ATHSTAT), and Authority Check (ATHCHCK) functions, refer to chapter “Basic IED functions” in the
Technical Manual.

17.2 Authority management AUTHMAN

17.2.1 Identification
GUID-7925E6A3-301D-44A5-982F-167805EEA473 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority management AUTHMAN - -

17.2.2 AUTHMAN GUID-AF7EDB44-42AA-4D49-BFA0-DA6A9B43973E v1

This function enables/disables the maintenance menu. It also controls the maintenance menu log on
time out.

Transformer protection RET650 715


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

17.2.3 Settings
PID-7492-SETTINGS v2

Table 657: AUTHMAN Non group settings (basic)

Name Values (Range) Unit Step Default Description


MaintMenuEnable Disable - - Enable Maintenance menu enable
Enable
AuthTimeout 600 - 3600 s 600 600 Authority blocking timeout
TLSMinVersion 0 - 255 - 1 0 Minimum version of TLS
TLSMaxVersion 0 - 255 - 1 0 Maximum version of TLS

17.3 FTP access with password FTPACCS

17.3.1 Identification
GUID-C037D0B0-1AA0-4592-9293-92C7EDED3261 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
FTP access with SSL FTPACCS - -

17.3.2 FTP access with TLS, FTPACCS GUID-9E64EA68-6FA9-4576-B5E9-92E3CC6AA7FD v5

The FTP client defaults to the best possible security mode when trying to negotiate with TLS. The
automatic negotiation mode is used by the client to negotiate with explicit TLS via AUTH TLS.

It is only possible to access disturbance records from the IED if FTP without TLS encryption is used.

If clear text FTP is required to read out disturbance recordings, create a specific account
for this purpose with rights only to do File transfer. The password of this user will be
exposed in clear text on the wire.

Setting FTP to OFF on an access point does not switch off FTP as the service will still be used by
PCM600 and FST. So to completely switch off the port number 21 access the following parameters
must be set to OFF.

• FTP = OFF
• PCMAccess = OFF
• FSTAccess = OFF

17.3.3 Settings
PID-6703-SETTINGS v3

Table 658: FTPACCS Non group settings (basic)

Name Values (Range) Unit Step Default Description


SSLMode FTP+FTPS - - FTPS Support for AUTH TLS/SSL
FTPS
TCPPortFTP 1 - 65535 - 1 21 TCP port for FTP and FTP with Explicit
SSL
PasvPortStart 0 - 65515 - 1 49200 First TCP data port for PASV
PasvPortEnd 0 - 65535 - 1 49232 Last TCP data port for PASV

716 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

17.4 Authority status ATHSTAT

17.4.1 Identification
GUID-79C63688-4D7D-4954-AC3C-B9484D084F6F v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority status ATHSTAT - -

17.4.2 Functionality SEMOD158529-5 v6

Authority status ATHSTAT function is an indication function block for user log-on activity.

User denied attempt to log-on and user successful log-on are reported.

17.4.3 Function block SEMOD158547-4 v4

ATHSTAT
USRBLKED
LOGGEDON
IEC06000503 V3 EN-US

Figure 396: ATHSTAT function block

17.4.4 Signals
PID-3773-OUTPUTSIGNALS v6

Table 659: ATHSTAT Output signals

Name Type Description


USRBLKED BOOLEAN At least one user is blocked by invalid password
LOGGEDON BOOLEAN At least one user is logged on

GUID-87CF079A-64C8-46AE-B7E4-A0B2EEAC92E9 v1

The output signal USRBLKED is not valid if the IED is Centralized Account Management
enabled.

17.4.5 Settings GUID-ECE18AA9-15CC-4522-AA31-78C4F0F052E4 v4

The function does not have any parameters available in Local HMI or in Protection and Control IED
Manager (PCM600)

17.4.6 Operation principle SEMOD158543-4 v6

Authority status (ATHSTAT) function informs about two events related to the IED and the user
authorization:

• the fact that at least one user has tried to log on wrongly into the IED and it was blocked (the
output USRBLKED)
• the fact that at least one user is logged on (the output LOGGEDON)

Whenever one of the two events occurs, the corresponding output (USRBLKED or LOGGEDON) is
activated. The output can for example, be connected on Event (EVENT) function block for LON/
SPA.The signals are also available on IEC 61850 station bus.

Transformer protection RET650 717


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

17.5 Self supervision with internal event list INTERRSIG IP1721-1 v2

17.5.1 Functionality M11399-3 v8

Self supervision with internal event list function listens and reacts to internal system events,
generated by the different built-in self-supervision elements. The internal events are saved in an
internal event list presented on the LHMI and in PCM600 event viewer tool.

17.5.2 Function block M11402-3 v6

INTERRSIG
FAIL
WARNING
TSYNCERR
RTCERR
STUPBLK
LHMIERROR
IEC09000787 V4 EN-US

Figure 397: INTERRSIG function block

17.5.3 Signals IP9674-1 v2

PID-8298-OUTPUTSIGNALS v1

Table 660: INTERRSIG Output signals

Name Type Description


FAIL BOOLEAN Internal fail
WARNING BOOLEAN Internal warning
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error
STUPBLK BOOLEAN Application startup block
LHMIERROR BOOLEAN LHMI error

17.5.4 Settings ABBD8E15533 v4

The function does not have any parameters available in the local HMI or PCM600.

17.5.5 Operation principle IP11943-1 v2

M11401-3 v13
The self-supervision operates continuously and includes:

• Normal micro-processor watchdog function.


• Checking of digitized measuring signals.
• Other alarms, for example hardware and time synchronization.

The self-supervision function status can be monitored from the local HMI or from the Event Viewer in
PCM600.

Under the Diagnostics menu in the local HMI, the actual information from the self-supervision
function can be reviewed. The information can be found under Main menu/Diagnostics /Internal
events or Main menu/Diagnostics /IED status/General . The information from the self-supervision
function is also available in the Event Viewer in PCM600.

718 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

IEC15000414 V3 EN-US

Figure 398: IED general status in local HM


The self supervision records internal signal changes in an internal event list. A maximum of 40
internal events are stored in a first-in, first-out manner.

GUID-B481701F-05B4-4B29-83D4-18F13886FEBE V1 EN-US

Figure 399: Self-supervision event list in local HMI


A self-supervision summary can be obtained by means of an output relay with potential free alarm
contact (INTERNAL FAIL) located on the power supply module. This contact is closed when the IED
either does not have auxiliary power, or when one or more error conditions are present in the IED (for
example harware error).

Some output signals are available from the INTERRSIG function block. The signals from this function
block are sent as events via IEC 61850 to the station level of the control system. These signals can
also be connected to binary outputs for signalization via output relays or they can be used as
conditions for other functions if required/desired.

Individual error signals from I/O modules can be obtained from respective module in the Signal
Matrix tool. Error signals from time synchronization can be obtained from the INTERRSIG function
block via two outputs TSYNCERR and RTCERR .

17.5.5.1 Internal signals M11401-173 v12

Self supervision provides several status signals that give information about the internal status of the
IED. For this reason they are also called internal signals. These internal signals, available on local
HMI under Main menu/Diagnostics/IED status/General, can be divided into two groups.

• Standard signals are always presented in the IED, see table 661.
• Hardware dependent internal signals are collected depending on the hardware configuration,
see table 662.

Transformer protection RET650 719


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

Table 661: Self-supervision's standard internal signals

Name of signal Description Displayed on Reasons for activation


local HMI as
FAIL Internal Fail Internal fail This signal will be active if one or more of the following
status internal signals are active; LMDERROR, WATCHDOG,
APPERROR, RTEERROR, or any of the HW dependent
signals
WARNING Internal Internal warning This signal will be active if one or more of the following
Warning internal signals are active; RTCERROR, IEC61850ERROR
status
RTCERROR Real Time Real time clock This signal will be active when there is a hardware error
Clock status with the real time clock.
TIMESYNCHERROR Time Time synch This signal will be active when the source of the time
Synchronizati synchronization is lost, or when the time system has to
on status make a time reset.
RTEERROR Runtime Runtime This signal will be active if the Runtime Engine failed to do
Execution execution some actions with the application threads. The actions can
Error status be loading of settings or parameters for components,
changing of setting groups, loading or unloading of
application threads.
IEC61850ERROR IEC 61850 IEC 61850 This signal will be active if the IEC 61850 stack did not
Error status succeed in some actions like reading IEC 61850
configuration, startup, for example
DNP3 DNP3 error DNP3 This signal will be active when DNP3 detects any
status configuration error during startup.
LMDERROR LON/Mip SLM301 LON network interface, MIP/DPS, is in an unrecoverable
Device Error error state.
status
APPERROR Runtime Runtime App This signal will be active if one or more of the application
Application Error threads are not in the state that Runtime Engine expects.
Error status The states can be CREATED, INITIALIZED, RUNNING, for
example
SETCHGD Settings Settings This signal will generate an Internal Event to the Internal
changed changed Event list if any settings are changed.
SETGRPCHGD Setting Settings This signal will generate an Internal Event to the Internal
groups changed Event list if any setting groups are changed.
changed

Table 662: Self-supervision's hardware dependent internal signals

Card Name of signal Description Displayed on Reasons for activation


local HMI as
PSM PSM-Error Power Supply PSM1 Activated if the module has a hardware error.
Module Error
status
BIM BIM-Error Binary In BIMn Activated if the module has a hardware error.
Module Error n = slot number
status
BOM BOM-Error Binary Out BOMn Activated if the module has a hardware error.
Module Error n = slot number
status
IOM IOM-Error In/Out Module IOMn Activated if the module has a hardware error.
Error status n = slot number
SOM SOM-Error Static Out SOMn Activated if the module has a hardware error.
Module Error n = slot number
status
NUM NUM-Error Numerical/CP NUM30 Activated if the module has a hardware or software
U Module error.
Error status
Table continues on next page

720 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

Card Name of signal Description Displayed on Reasons for activation


local HMI as
ADM ADM-Error A/D Module ADM32 Activated if the module has a hardware error.
Error status
LDCM LDCM-Error Line LDCM3nn Activated if the module has a hardware error.
Differential n = slot number
Communicatio
n Module
Error status
TRM TRM-Error Transformer TRM40 Activated if the module fails detection on IED
Module Error startup.
status
TRM TRM-Error Transformer TRM41 Activated if the module fails detection on IED
Module Error startup.
status

If the RTC is faulty, the IED will start up with a time of 2004-01-01 and start advancing from there.
This time will also be reset to the same date every time the IED is restarted. Provided that the IED is
time synchronized, this is unlikely to be an issue, since the IED will be brought back in sync in a short
time.

When settings are changed in the IED, the protection and control applications restart in order to take
effect of the changes. During restart, internal events get generated and Runtime App error will be
displayed. These events are only indications and will be for short duration during the restart.

IED will not be operational during applications restart.

17.5.5.2 Supervision of analog inputs M11401-136 v7

The analog signals to the A/D converter is internally distributed into two different converters, one with
low amplification and one with high amplification.

When the signal is within measurable limits on both channels, a direct comparison of the two A/D
converter channels can be performed. If the validation fails, the CPU will be informed and an alarm
will be given for A/D converter failure.

17.5.6 Technical data IP10272-1 v2

M11963-1 v5

Table 663: Self supervision with internal event list

Data Value
Recording manner Continuous, event controlled
List size 40 events, first in-first out

17.6 Change Lock function CHNGLCK GUID-E8A1C33A-DD65-42B5-BA13-CFAE40C2C9AD v3

17.6.1 Functionality GUID-00784FC0-B39D-462D-854B-AAF62626DD0A v3

Change lock function CHNGLCK is used to block further changes to the IED configuration and
settings once the commissioning is complete. The purpose is to block inadvertent IED configuration
changes beyond a certain point in time.

Transformer protection RET650 721


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 17 1MRK504170-UEN Rev. J
Security

The change lock function activation is normally connected to a binary input.

17.6.2 Function block GUID-15AA1D42-912E-4085-8166-33FDC327CEB5 v2

CHNGLCK
LOCK* ACTIVE
OVERRIDE
IEC09000946.vsd

IEC09000946 V2 EN-US

Figure 400: CHNGLCK function block

17.6.3 Signals GUID-1B253577-C81B-40E3-B406-1F6586DCE545 v2

PID-3786-INPUTSIGNALS v6

Table 664: CHNGLCK Input signals

Name Type Default Description


LOCK BOOLEAN 0 Activate change lock

PID-3786-OUTPUTSIGNALS v7

Table 665: CHNGLCK Output signals

Name Type Description


ACTIVE BOOLEAN Change lock active
OVERRIDE BOOLEAN Change lock override

17.6.4 Operation principle GUID-74581AA2-6EB4-4CFA-92DA-90FB89F9A62C v6

The Change lock function (CHNGLCK) is configured using ACT.

The function, when activated, will still allow the following changes of the IED state that does not
involve reconfiguring of the IED:

• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group

The binary input signal LOCK controlling the function is defined in ACT or SMT:

Binary input Function


1 Activated
0 Deactivated

722 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 17
Security

Change lock functionality can be temporarily disabled/overridden using Maintenance menu.


Maintenance menu/Recovery Menu (Password Protected)/Turn off Change-lock (Temporary).

Turning off the change lock will override the change lock function until the next reboot of the IED. In
this case, the change lock function cannot be activated, and the Override output will indicate that the
change-lock is overridden.

17.7 Denial of service DOS

17.7.1 Functionality GUID-407250CA-0076-41E1-AD2D-434077AC3F1D v5

The Denial of service functionality limits overload on the IED produced by heavy Ethernet network
traffic. The communication facilities must not be allowed to compromise the primary functionality of
the device. All inbound network traffic will be quota controlled so that too heavy network loads can be
controlled. Heavy network load might for instance be the result of malfunctioning equipment
connected to the network.

17.7.2 Operation principle GUID-94340D4F-4D32-409B-BA1A-BA49A0C3F297 v6

The denial of service protection is designed to protect the IED from overload when exposed to high
amount of Ethernet network traffic. The communication facilities must not be allowed to compromise
the primary functionality of the device. All inbound network traffic is quota controlled, so that a too
heavy network load can be controlled. Heavy network load might for instance be the result of
malfunctioning equipment connected to the network.

The denial of service functionality in SCHLCCH and RCHLCCH measures the IED load from
communication and, if necessary, limits it from jeopardizing the IED's control and protection
functionality. The function has the following outputs:

• RCHLCCH
• LinkAUp and LinkBUp indicates the Ethernet link status for the rear ports channel A and
B
• DOSLINKA and DOSLINKB indicates that DOS functionality is active on channel A and
channel B
• DOSALARM indicates that DOS functionality is active on the access point
• SCHLCCH
• LINKUP indicates the Ethernet link status
• DOSALARM indicates that DOS functionality is active on the access point

The DOS functionality activates when the inbound traffic rate exceeds 3000 packets per
second.

Transformer protection RET650 723


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
724
1MRK504170-UEN Rev. J Section 18
Basic IED functions

Section 18 Basic IED functions


18.1 Time synchronization TIMESYNCHGEN IP1750-1 v2

18.1.1 Functionality M11344-3 v12

The time synchronization function is used to select a common source of absolute time for the
synchronization of the IED when it is a part of a protection system. This makes it possible to compare
events and disturbance data between all IEDs within a station automation system and in between
sub-stations. A common source shall be used for IED and merging unit when IEC/UCA 61850-9-2LE
process bus communication is used.

MicroSCADA OPC server should not be used as a time synchronization source.

The IED supports SNTPv4 (RFC2030).

18.1.2 Settings IP9657-1 v2

SEMOD55141-5 v7
There are two groups of parameter settings related to time:

• System time
• Synchronization

The System time group relates to setting the on/off and start/end of the Daylight Saving Time (DST)
for the local time zone in relation to Coordinated Universal Time (UTC). The Synchronization group
relates to selecting the coarse and fine synchronization sources.

All the settings and parameters related to time are available via Local HMI under Main menu/
Configuration/Time/System time and via PCM600 under IED Configuration/Time .
MANUALPID-6638-SETTINGS v2

Table 666: TIMESYNCHGEN Non group settings (basic)

Name Values (Range) Unit Step Default Description


CoarseSyncSrc Off - - Off Coarse time synchronization source
SPA
LON
DNP
IEC103
FineSyncSource Off - - Off Fine time synchronization source
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
SyncMaster Off - - Off Activate IEDas synchronization master
SNTP-Server
Table continues on next page

Transformer protection RET650 725


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

Name Values (Range) Unit Step Default Description


TimeAdjustRate Slow - - Fast Adjust rate for time synchronization
Fast Slow is meant to be used in cases where
differential protection is used in GPS
mode and echo is used as the GPS error
method.
This will ensure that the adjustment of
internal time in the IED won’t interfere
with the echo method synchronization in
case of regaining the GPS signal after
GPS loss.
In the case where the GPS error method
is set to block, the TimeAdjustRate should
be set to Fast since the differential
protection is already blocked due to the
GPS loss.
HWSyncSrc Off - - Off Hardware time synchronization source
GPS
IRIG-B
PPS
SyncLostMode NoBlock - - NoBlock Behavior of dependent protection
Block functions when time synchronization
BlockOnLostUTC quality is inadequate
SyncAccLevel Class T5 (1us) - - Unspecified Wanted time synchronization accuracy
Class T4 (4us)
Unspecified
CurrentSyncSource 0 - 16 - 1 - Current synchronization source
SNTPSource 0 - 16 - 1 - The source of the SNTP time
SNTPMaster 0 - 16 - 1 - The IP-adress of the SNTP master
GPSNumberOfSats -1 - 12 - 1 0 GPS satellites used in calculation of time
PTPOwnId 0 - 16 - 1 - PTP own clock identity

GUID-CD154442-0F80-4B69-8C43-22445FD7F865 v1

GPS settings are not supported by 650 due to hardware restrictions.

PID-6188-SETTINGS v6

Table 667: BININPUT Non group settings (basic)

Name Values (Range) Unit Step Default Description


ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge - - PositiveEdge Positive or negative edge detection
NegativeEdge

PID-6608-SETTINGS v4

Table 668: SNTP Non group settings (basic)

Name Values (Range) Unit Step Default Description


ServerIP-Add 0 - 18 IP 1 0.0.0.0 Server IP-address
Address
RedServIP-Add 0 - 18 IP 1 0.0.0.0 Redundant server IP-address
Address
LocalPort 0 - 65535 - 1 49152 Port number in the IED to communicate
with the SNTP server

726 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

PID-6212-SETTINGS v5

Table 669: DSTENABLE Non group settings (basic)

Name Values (Range) Unit Step Default Description


DST Enable Off - - On Enables or disables the use of Daylight
On Saving Time

PID-3967-SETTINGS v7

Table 670: DSTBEGIN Non group settings (basic)

Name Values (Range) Unit Step Default Description


MonthInYear January - - March Month in year when daylight time starts
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time starts
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time starts
First
Second
Third
Fourth
UTCTimeOfDay -24:00 - - 1:00 UTC Time of day in hours when daylight
-23:30 time starts
...
-00:30
00:00
00:30
...
48:00

Transformer protection RET650 727


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

PID-3968-SETTINGS v7

Table 671: DSTEND Non group settings (basic)

Name Values (Range) Unit Step Default Description


MonthInYear January - - October Month in year when daylight time ends
February
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time ends
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time ends
First
Second
Third
Fourth
UTCTimeOfDay -24:00 - - 1:00 UTC Time of day in hours when daylight
-23:30 time ends
...
-00:30
00:00
00:30
...
48:00

728 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

PID-4138-SETTINGS v5

Table 672: TIMEZONE Non group settings (basic)

Name Values (Range) Unit Step Default Description


TimeZone -12:00 - - 1:00 Local time from UTC
-11:00
-10:00
-9:30
-9:00
-8:00
-7:00
-6:00
-5:00
-4:30
-4:00
-3:30
-3:00
-2:00
-1:00
0:00
1:00
2:00
3:00
3:30
4:00
4:30
5:00
5:30
5:45
6:00
6:30
7:00
8:00
8:45
9:00
9:30
10:00
10:30
11:00
11:30
12:00
12:45
13:00
14:00

PID-6630-SETTINGS v3

Table 673: PTP Non group settings (advanced)

Name Values (Range) Unit Step Default Description


Domain 0 - 255 - 1 0 0 = Default domain, 1-3 = Alternative
domain, 4-127 = User-defined domains,
128-255 = Reserved
Priority1 0 - 255 - 1 128 The clock with the lowest priority 1
becomes the reference clock (Grand
Master)
Priority2 0 - 255 - 1 128 If all the relevant values for selecting the
reference clock are the same for multiple
devices, the clock with the lowest priority
2 is selected as the reference clock
(Grand Master)

18.1.3 Description of SyncLostMode GUID-9BD77B8E-37F2-480F-89D6-9CE251403761 v1

If the time synchronization between the different sources of sampled values are lost, then the
protection function blocking behavior is different based on the parameter SyncLostMode.

Transformer protection RET650 729


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

The parameter can have three different values:

• NoBlock
• Block
• BlockOnLostUTC

NoBlock
The protection functions are not blocked due to the lost time synchronization. This is mainly used
when all sample values are produced in one source.

Block
The block can be used if there are several data sources that can be synchronized to each other.
However, the relation to UTC time is not required.

As soon as the protection detects a change or uncertainty in time from a data source, the protections
are blocked. This is detected by the jump in sample count or when the data remains unsynchronized.

When a block occurs, the block stays for an extra blocking time after all the sources are
synchronized again, to secure that the time has propagated to the other sources.

Data stream 1
Time shift
Extra blocking time
on-going

Data stream 2
Time shift
Extra blocking time
on-going

Data stream 3
Time shift
Extra blocking time
on-going

Total protection blocking time

IEC19000001 V2 EN-US

Figure 401: Principle blocking when SyncLostMode is set to block


For more information, refer to section Time synchronization

BlockOnLostUTC
When BlockOnLostUTC is selected, all the data must be synchronized to UTC, to avoid blocking of
the protection functions.

This cannot be used by the process bus sampled values, since IEC 61859-9-2 LE only contains the
information regarding the synchronized or unsynchronized data.

For example, the BlockOnLostUTC can be used for a phasor measurement unit where the data is
compared between different stations.

18.1.4 Operation principle IP12360-1 v4

18.1.4.1 General concepts M11346-77 v2

730 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

Time definitions M11346-80 v3


The error of a clock is the difference between the actual time of the clock, and the time the clock is
intended to have. Clock accuracy indicates the increase in error, that is, the time gained or lost by the
clock. A disciplined clock knows its own faults and tries to compensate for them.

Design of the time system (clock synchronization) GUID-E2B9E81C-5733-4521-B27F-BF33E05CCFB0 v11


The time system is based on software and hardware clocks that run independently from each other
(see Figure 402).

PTP(IEEE 1588)
External
synchronization Off
sources On
Time tagging and general synchronization
Slave only
Off
Commu- Protection
LON Events
Time nication and control
SPA regulator functions
Min. pulse
(Setting:
SNTP SW time
see
DNP Technical
manual)
IRIG-B
PPS

Synchronization for differential protection


(Echo mode)
Off Time
IRIG-B regulator HW time
(fast or slow)
PPS

A/D Diff. Merging


converter commu- units*
nication

*IEC 61850-9-2
IEC16000002-2-en.vsdx
IEC16000002 V2 EN-US

Figure 402: Design of the time system (clock synchronization)


All time tagging is performed by the software clock. When, for example, a status signal is changed in
the protection system of a function based on the free running hardware clock, the event is time
tagged by the software clock when it reaches the event recorder. The hardware clock can thus run
independently.

The echo mode of the line differential protection function is based on the hardware clock. Thus, there
is no need to synchronize the hardware clock and the software clock.

Synchronization of the hardware clock to the software clock is necessary only when IRIG B 00X with
optical fiber, IEEE 1344 is used for differential protection. The two clock systems are synchronized by
a special clock synchronization unit with two modes, fast and slow. A special feature, an automatic
fast clock time regulator is used. The automatic fast mode makes the synchronization time as short
as possible during start-up. The Fast and Slow settings are also available on the local HMI.

SyncLostMode is not required to set as Block/BlockonLostUTC when differential protection is based


on ECHO mode.

Transformer protection RET650 731


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

Fast clock synchronization mode


At start-up and after interruptions in the IRIG B time signals, the deviation between the external time
system and the internal differential time system can be substantial. A new start-up is also required,
for example, after maintenance of the auxiliary voltage system.

When the time difference is > 16 μs, the line differential protection function is blocked and the time
regulator for the hardware clock automatically uses a fast mode to synchronize the clock systems.
Time adjustment is made with an exponential function, that is, with big time adjustment steps in the
beginning, and then smaller steps until a time deviation of < 16 μs between the external time system
and the internal differential time system has been reached. The protection function is then enabled
and the synchronization remains in fast mode or switches to slow mode depending on the setting.

Slow clock synchronization mode


When Echo mode is used as GPS-error method, (GPSerr setting), a slow synchronization mode
might be preferred.

This prevents the hardware clock to make too big time steps and allows the ECHO method to "keep
up" so that no block will occur while regaining GPS synchronization.

At start-up a fast adjustment will be used in order to get synchronized as fast as possible.

When GPS synchronization is reached, and the protection is unblocked, slow clock synchronization
mode is activated (if selected).

Synchronization principle M11346-83 v4


From a general point of view synchronization can be seen as a hierarchical structure. A function is
synchronized from a higher level and provides synchronization to lower levels.

Synchronization from
a higher level

Function

Optional synchronization of
modules at a lower level

IEC09000342 V2 EN-US

Figure 403: Synchronization principle


A function is said to be synchronized when it periodically receives synchronization messages from a
higher level. As the level decreases, the accuracy of the synchronization decreases as well. A
function can have several potential sources of synchronization, with different maximum errors. This
gives the function the possibility to choose the source with the best quality, and to adjust its internal
clock based on this source. The maximum error of a clock can be defined as:

• The maximum error of the last used synchronization message


• The time since the last used synchronization message
• The rate accuracy of the internal clock in the function.

18.1.4.2 Real-time clock (RTC) operation M11346-57 v5

The IED has a built-in real-time clock (RTC) with a resolution of one millisecond. The clock has a
built-in calendar that handles leap years through 2100.

732 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

Real-time clock at power off M11346-60 v3


During power off, the system time in the IED is kept by a capacitor-backed real-time clock that will
provide 5 ppm accuracy for at least two days. This means that if the power is off, the time in the IED
may drift with maximum 0.5 second per day for two days, and after this the time will be lost.

Real-time clock at startup M11346-63 v4

Time synchronization startup procedure M11346-66 v10


The first message that contains the full time (as for instance LON and SNTP) gives an accurate time
to the IED. After the initial setting of the clock, one of the three following conditions happens with
each of the coming synchronization messages configured as FineSynchSource:

• If the synchronization message, which is similar to the other messages, has an offset compared
to the internal time in the IED, the message is used directly for synchronization, which means,
for adjusting the internal clock to obtain zero offset at the next coming time message.
• If the synchronization message has a large offset compared to the other messages, a spike-filter
in the IED removes this time-message.
• If the synchronization message has a large offset and the following message also has a large
offset, the spike filter does not act and the offset in the synchronization message is compared to
a threshold that defaults to 500 milliseconds. If the offset is more than the threshold, the clock
jumps a whole number of seconds so the remaining offset is less than 500ms. The remaining
offset is then slowly adjusted with 1000 ppm until the offset is removed. With an adjustment of
1000ppm it takes 500 seconds to remove an offset of 500 milliseconds.

Synchronization messages configured as coarse are only used for initial setting of the time. After this
has been done, the messages are checked against the internal time and only an offset of more than
10 seconds resets the time.

Rate accuracy M11346-93 v7


The rate accuracy is the accuracy of the internal clock while the external time signal is lost. In the
IED, the rate accuracy at cold start is 2 ppm but if the IED is synchronized for a while, the rate
accuracy is approximately 0.2 ppm if the surrounding temperature is constant.

Time-out on synchronization sources M11346-96 v3


All synchronization interfaces have a time-out, and a configured interface must receive time
synchronization messages regularly in order not to give an error signal (TSYNCERR) that is reported
from the INTERRSIG function block. The time-out is such that one message can be lost without
getting a TSYNCERR, but if more than one message is lost, a TSYNCERR is given.

18.1.4.3 Synchronization alternatives M11346-3 v7

Three main alternatives of external synchronization sources are available. The synchronization
message is applied:

• via any of the communication ports of the IED as a telegram message including date and time
• as a minute pulse connected to a binary input
• via IRIG-B or PPS

Synchronization via SNTP M11346-33 v9


SNTP provides a ping-pong method of synchronization. A message is sent from an IED to an SNTP
server, and the SNTP server returns the message after filling in a reception time and a transmission
time. SNTP operates via the normal Ethernet network that connects IEDs together in an IEC 61850
network. For SNTP to operate properly, there must be an SNTP server present, preferably in the
same station. The SNTP synchronization provides an accuracy that gives +/- 1 ms accuracy for
binary inputs. The IED itself can be set as an SNTP-time server.

SNTP provides complete time-information and shall normally be used as fine time synch source only.

Transformer protection RET650 733


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

SNTP server requirements GUID-588FCD12-C494-445E-8488-8287B34EFD9A v5


The SNTP server to be used is connected to the local network, that is not more than 4-5 switches or
routers away from the IED. The SNTP server is dedicated for its task, or at least equipped with a
real-time operating system, that is not a PC with SNTP server software. The SNTP server should be
stable, that is, either synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server in a redundant
configuration is not recommended.

The IED supports SNTPv4 (RFC2030).

Synchronization via serial communication module (SLM) M11346-50 v7


On the serial buses (both LON and SPA) two types of synchronization messages are sent.

• Coarse message is sent every minute and comprises complete date and time, that is, year,
month, day, hours, minutes, seconds and milliseconds.
• Fine message is sent every second and comprises only seconds and milliseconds.

The SLM module is located on the first analog digital conversion module (ADM)

Synchronization via binary input M11346-42 v6


The IED accepts minute pulses to a binary input. These minute pulses can be generated from, for
example station master clock. If the station master clock is not synchronized from a world wide
source, time will be a relative time valid for the substation. Both positive and negative edge on the
signal can be accepted. This signal is also considered as a fine time synchronization signal.

The minute pulse is connected to any channel on any Binary Input Module in the IED. The electrical
characteristic is thereby the same as for any other binary input.

If the objective of synchronization is to achieve a relative time within the substation and if no station
master clock with minute pulse output is available, a simple minute pulse generator can be designed
and used for synchronization of the IEDs. The minute pulse generator can be created using the
logical elements and timers available in the IED.

The definition of a minute pulse is that it occurs one minute after the last pulse. As only the flanks are
detected, the flank of the minute pulse shall occur one minute after the last flank.

Binary minute pulses are checked with reference to frequency.

Pulse data:

• Period time (a) should be 60 seconds.


• Pulse length (b):
• Minimum pulse length should be >50 ms.
• Maximum pulse length is optional.
• Amplitude (c) - please refer to section "Binary input module (BIM)".

Deviations in the period time (a) larger than 50 ms will cause TSYNCERR.

734 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

en05000251.vsd
IEC05000251 V1 EN-US

Figure 404: Binary minute pulses


The default time-out-time for a minute pulse is two minutes, and if no valid minute pulse is received
within two minutes a SYNCERR will be given.

If contact bounce occurs, only the first pulse will be detected as a minute pulse. The next minute
pulse will be registered first 60 s - 50 ms after the last contact bounce.

If the minute pulses are perfect, for example, it is exactly 60 seconds between the pulses, contact
bounces might occur 49 ms after the actual minute pulse without effecting the system. If contact
bounce occurs more than 50 ms, for example, it is less than 59950 ms between the two most
adjacent positive (or negative) flanks, the minute pulse will not be accepted.

Binary synchronization example M11346-74 v5


An IED is configured to use only binary input for time synchronization, and a valid binary input is
applied to a binary input card. The HMI is used to tell the IED the approximate time, and the minute
pulse is then used to synchronize the IED. Minute pulse means that each pulse occurs one minute
after the previous pulse, so the first pulse is not used at all. The second pulse will probably be
rejected due to the spike filter. The third pulse will give the IED a good time, and will reset the time so
that the fourth pulse will occur on a minute border. After the first three minutes, the time in the IED
will be good if the coarse time is set properly via the HMI or if the RTC backup still keeps the time
since last up-time. If the minute pulse is removed, for example, for an hour, the internal time will drift
by maximum the error rate in the internal clock. If the minute pulse is returned, the first pulse is
automatically rejected. The second pulse will possibly be rejected due to the spike filter. The third
pulse will set the time if the time offset is more than 500 ms or adjust the time if the time offset is
small enough. If the time is set, the application will be brought to a safe state before the time is set. If
the time is adjusted, the time will reach its destination within one minute.

Synchronization via IRIG-B module M11346-146 v8


IRIG-B is a protocol used only for time synchronization. A clock can provide local time of the year in
this format. The “B” in IRIG-B states that 100 bits per second are transmitted and the message is
sent every second. After IRIG-B there are numbers stating if and how the signal is modulated and the
information transmitted.

To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic BNC connector and
one optical ST connector. IRIG-B 12x messages can be supplied via the galvanic interface, and
IRIG-B 00x messages can be supplied via either the galvanic interface or the optical interface, where
x (in 00x or 12x) means a number in the range of 0-7.

“00” means that a base band is used, and the information can be fed into the IRIG-B module via the
BNC contact or an optical fiber. “12” means that a 1 kHz modulation is used. In this case the
information must go into the module via the BNC connector.

If the x in 00x or 12x is 4, 5, 6 or 7, the time message from IRIG-B contains information of the year. If
the x is 0, 1, 2 or 3, the information contains only the time within the year, and year information has to
be set via PCM600 or local HMI.

Transformer protection RET650 735


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B clocks, as IRIG-
B previously did not have any year information. IEEE1344 is compatible with IRIG-B and contains
year information and information of the time-zone.

18.1.4.4 Process bus IEC/UCA 61850-9-2LE synchronization GUID-6E384BDB-5598-4108-99B4-0B4A4E1828B2 v5

When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it is essential that the
merging units are synchronized with the hardware time of the IED (see Technical manual, section
Design of the time system (clock synchronization) ). To achieve this, PTP, PPS or IRIG-B can be
used depending of the facilities of the merging unit.

If the merging unit supports PTP, use PTP. If PTP is used in the IED and the merging unit cannot be
synchronized from the IED, then use GPS-based clocks to provide PTP synch as well as sync to the
merging unit.

If synchronization of the IED and the merging unit is based on GPS, set the parameter
SyncLostMode to BlockOnLostUTC in order to provide a block of protection functions whenever the
global common time is lost.

If PTP is not used, use the same synchronization method for the HwSyncSrc as the merging unit
provides. For instance, if the merging unit provides PPS as synchronization, use PPS as HwSyncSrc.
If LDCM in GPS-mode is used, that is, the hardware and software clocks are connected to each
other, HwSyncSrc is not used and other means to synchronize the merging unit to the IED is
required. For instance, FineSyncSource is set to the same source that the merging unit uses.

If the IED is used together with a merging unit and no time synchronization is available,
for example, in the laboratory test, the IED will synchronize to the SV data stream. During
the re-synchronization, the protection functions will be blocked once a second for about
45 ms, and this will continue for up to 10 minutes. To avoid this, configure PTP (IEEE
1588) to On for the access point where the merging unit is configured.

18.1.4.5 Precision Time Protocol (PTP) GUID-4F2B68B8-CCC8-4173-A644-D1674D3146F8 v4

PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3 for power utility
automation is a synchronization method that differs from SNTP, for instance, by providing much
better accuracy and by being not predefined. By not predefined is meant that it is not mandatory to
have a predefined synchronization tree, as the master (Grand Master) may shift.

Consider instead PTP as a synchronization grouping, i.e. all devices connected to the PTP group will
be synchronized to the same source or, if there is no external source the group will at least maintain
a common time. The group is synchronized by connecting one or more “Grand Master” clocks to it.
The clocks can be part of the devices in the group or be specialized synchronization devices, as for
instance a GPS clock or similar. If several synchronization devices are connected to the group, the
“Best Master Algorithm” in the PTP protocol will assure that only one is the “Grand Master”. The IED
can act as a synchronization device and supply any synchronization source (like SNTP, SPA) as
clock input, that will synchronize the whole PTP group if there is no better source available in the
group. The IED can be connected to several groups and thereby connect them to each other, by
acting as a “Boundary Clock”. If PTP is “On” on several Access Points, the IED connects the Access
Points via a boundary clock. If PTP is “On” on redundant Access Points, the IED acts as a
“Transparent Clock”.

In a network there may be variety of possible masters that are connected together where the masters
by selection, using the priority of PTP (also called the Best Master Algorithm, or BMC) to determine
which of them that is the best master.

Priority order according to PTP

1. Priority 1

736 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

setting for each device, default 128, set to a lower number if this device shall be the Grand
Master.
2. GM class
given from the type of device, for instance “6” for a GPS clock, “7” for a GPS clock that has lost
synch during a hold-over time, “187” for a clock that can also be a slave.
3. GM Accuracy
how accurate the time is as a enumerated value
4. Offset Scaled Variance
calculated value that shows the oscillator quality
5. Priority 2
setting for each device, default 128, set to a lower number if this device is preferred to be the
Grand Master, if Priority 1, GM class, GM accuracy and OffsetScaledVariance are the same for
all devices.
6. Identity, that is the MAC-adress of the port.

MAC address of the access points can be seen in LHMI under the settings of each
access point.

To setup a PTP network with no obvious Grand Master, you simply connect the IEDs to one network
and configure PTP to be “on” on all IEDs. On one IED, the one from which you want to set the time in
the station, you set the Priority2 to 127, instead of default 128. Now, this IED has higher priority than
the rest of the IEDs and will thereby act as “Grand Master”.

PTP is not set from TIMESYNCGEN:1 General, as SNTP is. Instead PTP is set via a parameter of
each Access Point. For more information, refer to section Time synchronization.

It shall be noted that an IED synchronized to local time in a PTP network is seen as local
synchronized, if the grand master is not synchronized. If an IED is the grand master
without any synchronization from somewhere else, then this grand master IED is seen as
not synchronized. This is reflected in the time quality of the events in IEC 61850 in the
field ClockNotSynchronized.

18.1.5 Technical data IP9658-1 v1

M12331-1 v9

Table 674: Time synchronization, time tagging

Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse synchronization), ± 1.0 ms typically
events and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically

GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2

Table 675: Time synchronization PTP: IEC/IEEE 61850-9-3

Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock
(TC)
Accuracy According to standard IEC/IEEE 61850-9-3
Number of nodes According to standard IEC/IEEE 61850-9-3
Ports supported All rear Ethernet ports

Transformer protection RET650 737


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

18.2 Parameter setting groups IP1745-1 v2

18.2.1 Functionality M12006-6 v9

Use the six different groups of settings to optimize the IED operation for different power system
conditions. Creating and switching between fine-tuned setting sets from the local HMI, configurable
binary inputs, IEC 61850, or PCM600/PST. This results in a highly adaptable IED that can be applied
to a variety of power system scenarios.

18.2.2 Function block IP9661-1 v1

M12010-3 v3

ACTVGRP
ACTGRP1 GRP1
ACTGRP2 GRP2
ACTGRP3 GRP3
ACTGRP4 GRP4
ACTGRP5 GRP5
ACTGRP6 GRP6
SETCHGD
IEC05000433 V5 EN-US

Figure 405: ActiveGroup function block

18.2.3 Signals IP14073-1 v2

PID-6558-INPUTSIGNALS v6

Table 676: ACTVGRP Input signals

Name Type Default Description


ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
ACTGRP5 BOOLEAN 0 Selects setting group 5 as active
ACTGRP6 BOOLEAN 0 Selects setting group 6 as active

PID-6558-OUTPUTSIGNALS v6

Table 677: ACTVGRP Output signals

Name Type Description


GRP1 BOOLEAN Setting group 1 is active
GRP2 BOOLEAN Setting group 2 is active
GRP3 BOOLEAN Setting group 3 is active
GRP4 BOOLEAN Setting group 4 is active
GRP5 BOOLEAN Setting group 5 is active
GRP6 BOOLEAN Setting group 6 is active
SETCHGD BOOLEAN Pulse when setting changed
REMSETEN BOOLEAN Settings over IEC 61850 enabled

738 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

18.2.4 Settings IP11026-1 v3

PID-8211-SETTINGS v1

Table 678: SETGRPS Non group settings (basic)

Name Values (Range) Unit Step Default Description


ActiveSetGrp SettingGroup1 - - SettingGroup1 Active setting group
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
ActSGChangeMode LastComeLastServe - - LastComeLastServ Active setting group change mode
d ed
BinaryInputOnly
MaxNoSetGrp 1-6 - 1 1 Max number of setting groups 1-6

18.2.5 Operation principle M12008-6 v3

M12008-8 v12
Parameter setting groups ActiveGroup function has six functional inputs, each corresponding to one
of the setting groups stored in the IED. Activation of any of these inputs changes the active setting
group. Eight functional output signals are available for configuration purposes, so that information on
the active setting group is always available.

A setting group is selected by using the local HMI, from a front connected personal computer,
remotely from the station control or station monitoring system or by activating the corresponding
input to the ActiveGroup function block.

Each input of the function block can be configured to connect to any of the binary inputs in the IED.
To do this PCM600 must be used.

The external control signals are used for activating a suitable setting group when adaptive
functionality is necessary. Input signals that should activate setting groups must be either constantly
active or a pulse exceeding 400 ms.

If an input signal is constantly active, then it will not be possible to change the active
setting group from LHMI, PCM600 or IEC 61850. This ensures that only the active input
signals control which setting group is active. If the user desire to change active setting
group also from LHMI, PCM600 and IEC 61850, then the input signals must be at a
logical zero in the normal state. This behavior is the default.

If the user wants the binary inputs to be the only entity that can change the active setting
group, then set the parameter ActSGChangeMode to BinaryInputOnly. Then, changes
attempted from LHMI, PCM600 and IEC 61850 will be rejected, even when all input
signals are zero.

More than one input may be activated at the same time. In such cases the lower order setting group
has priority. This means that if for example both group four and group two are set to be activated,
group two will be the one activated.

Every time a setting is changed, the output signal SETCHGD is sending a pulse. Activating or
deactivating test mode is made by changing a parameter, consequently this will also cause a pulse
on the SETCHGD output.

The parameter MaxNoSetGrp defines the maximum number of setting groups in use to switch
between.

The output REMSETEN indicates whether setting changes over IEC 61850 are enabled or not. Per
default, this is not enabled, which results in REMSETEN being at a logical low level. If setting
changes via IEC 61850 are enabled, then REMSETEN will be a logical high. The setting changes

Transformer protection RET650 739


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

over IEC 61850 is enabled with the setting EnableSettings in the IEC 61850-8-1 configuration under
Main menu /Configuration /Communication /Station communication /IEC 61850-8-1 /IEC
61850-8-1 . Please refer to documentation for IEC 61850 for further details.

Switching can only be done within that number of groups. The number of setting groups selected to
be used will be filtered so only the setting groups used will be shown on the Parameter Setting Tool.

ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
+RL2 ACTIVATE GROUP 1
ACTVGRP
IOx-Bly1
 ACTGRP1 GRP1

IOx-Bly2
 ACTGRP2 GRP2

IOx-Bly3
 ACTGRP3 GRP3

IOx-Bly4
 ACTGRP4 GRP4

IOx-Bly5
 ACTGRP5 GRP5

IOx-Bly6
 ACTGRP6 GRP6

SETCHGD

REMSETEN

IEC05000119 V4 EN-US

Figure 406: Connection of the function to external circuits


The above example also includes six output signals, for confirmation of which group that is active.

18.3 Test mode functionality TESTMODE IP1647-1 v4

18.3.1 Functionality M4803-3 v11

When entering IED test mode there is an option to block all functions. Active test mode is indicated
by a flashing yellow Start LED on the LHMI. After that, it is possible to block/unblock arbitrarily
selected functions from the LHMI to perform required tests.

When leaving TESTMODE, all blockings are removed (except for functions that have their block input
active), and the IED resumes normal operation. However, if during TESTMODE operation, power is
removed and later restored, the IED will remain in TESTMODE with the same protection functions
blocked or unblocked as before the power was removed. All testing will be done with actually set and
configured values within the IED. No settings will be changed, thus mistakes are avoided.

Forcing of binary input and output signals is only possible when the IED is in IED test mode.

18.3.2 Function block SEMOD54888-4 v5

TESTMODE
IED_TEST TEST
IED_TEST
BLOCK
NOEVENT
INPUT
SETTING
IEC61850
IEC09000219 V3 EN-US

Figure 407: TESTMODE function block

740 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

18.3.3 Signals IP9680-1 v3

PID-6730-INPUTSIGNALS v1

Table 679: TESTMODE Input signals

Name Type Default Description


IED_TEST BOOLEAN 0 Activate IED test mode

PID-6730-OUTPUTSIGNALS v1

Table 680: TESTMODE Output signals

Name Type Description


TEST BOOLEAN In test via IED TEST or via LD0 Mode
IED_TEST BOOLEAN IED test mode is active
BLOCK BOOLEAN Active when LD0 is blocked or test blocked
NOEVENT BOOLEAN Event disabled during test mode
INPUT BOOLEAN IED TEST input is active
SETTING BOOLEAN IED test mode setting is On
IEC61850 BOOLEAN Active when LD0 Mode is in Blocked, Test or Test blocked

18.3.4 Settings IP11343-1 v2

GUID-D1206681-E341-4F6A-99E4-F168C79E4BE0 v1

Table 681: TESTMODE Input signals

Name Type Default Description


IED_TEST BOOLEAN 0 Activate IED test mode

18.3.5 Operation principle IP12116-1 v4

M12015-4 v11
Set the IED in test mode by

• configuration, activating the input SIGNAL on the function block TESTMODE.


• setting TestMode to On in the local HMI, under Main menu/TEST/IED test mode.

While the IED is in test mode, the output ACTIVE of the function block TESTMODE is activated. The
outputs of the function block TESTMODE shows the cause of the “Test mode: being in On” state. If
the input from the configuration (OUTPUT signal is activated) or setting from local HMI (SETTING
signal is activated).

While the IED is in test mode, the yellow Start LED will flash and all functions can be blocked
depending on the configuration of the testmode component. Any function can be unblocked
individually regarding functionality and event signalling.
M11828-3 v9
The deblocking operation will reset when exiting the test mode.

The blocking of a function concerns all output signals from the actual function, so no outputs will be
activated.

If the IED is restarted while set to IED TESTMODE by a binary input all functions will be
temporarily unblocked during startup, which might cause unwanted operations.

The TESTMODE function block might be used to automatically block functions when a test handle is
inserted in a test switch. A contact in the test switch (RTXP24 contact 29-30) can supply a binary
input which in turn is configured to the TESTMODE function block.

Each of the functions includes the blocking from the TESTMODE function block.

Transformer protection RET650 741


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

The functions can also be blocked from sending events over IEC 61850 station bus to prevent filling
station and SCADA databases with test events, for example during a commissioning or maintenance
test.

18.4 IED identifiers TERMINALID IP15060-1 v2

18.4.1 Functionality M15324-3 v7

IED identifiers (TERMINALID) function allows the user to identify the individual IED in the system, not
only in the substation, but in a whole region or a country.

Use only characters A-Z, a-z and 0-9 in station, object and unit names.

18.4.2 Settings GUID-3C49A222-FFE4-492B-A96C-9E9965FA2CB4 v2

PID-6801-SETTINGS v1

Table 682: TERMINALID Non group settings (basic)

Name Values (Range) Unit Step Default Description


StationName 0 - 18 - 1 Station name Station name
StationNumber 0 - 99999 - 1 0 Station number
ObjectName 0 - 18 - 1 Object name Object name
ObjectNumber 0 - 99999 - 1 0 Object number
UnitName 0 - 18 - 1 Unit name Unit name
UnitNumber 0 - 99999 - 1 0 Unit number
IEDMainFunType 0 - 255 - 1 0 IED main function type for
IEC60870-5-103
TechnicalKey 0 - 16 - 1 AA0B0Q0A0 Technical key (part 1)
0 - 16 - 1 Technical key (part 2)
0 - 16 - 1 Technical key (part 3)
0 - 16 - 1 Technical key (part 4)

18.5 Product information PRODINF GUID-F67243CA-2429-4118-BBFF-3D62BF55E080 v2

18.5.1 Functionality GUID-D78786E6-C34A-4E63-9D1E-0582C8F1F7E1 v11

Product information contains unchangeable data that uniquely identifies the IED.

Product information data is visible on the local HMI under Main menu/Diagnostics/IED status/
Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers:

Product information data is visible on the local HMI under Main menu/Diagnostics/IED status/
Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers.

• ProductVer
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate
• IEDProdType

742 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

Figure 408: IED summary


This information is very helpful when interacting with Hitachi Energy product support (for example
during repair and maintenance).

18.5.2 Settings GUID-168CD792-8811-43B5-8760-74ED82DE17F7 v5

The function does not have any parameters available in the local HMI or PCM600.

18.5.3 Factory defined settings M11789-39 v11

The factory defined settings are very useful for identifying a specific version and very helpful in the
case of maintenance, repair, interchanging IEDs between different Substation Automation Systems
and upgrading. The factory made settings can not be changed by the customer. They can only be
viewed. The settings are found in the local HMI under Main menu/Diagnostics /IED status/Product
identifiers

The following identifiers are available:

• IEDProdType
• Describes the type of the IED. Example: REL650
• ProductDef
• Describes the release number from the production. Example: 2.1.0
• FirmwareVer
• Describes the firmware version.
• The firmware version can be checked from Main menu/Diagnostics/IED status/Product
identifiers
• Firmware version numbers run independently from the release production numbers. For
every release number there can be one or more firmware versions depending on the small
issues corrected in between releases.
• ProductVer
• Describes the product version. Example: 2.1.0

1 is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware added to
the product
3 is the Major revision of the manufactured product this means, functions or hardware is either changed
or enhanced in the product

• IEDMainFunType
• Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
• SerialNo
• OrderingNo
• ProductionDate

18.6 Signal matrix for binary inputs SMBI SEMOD55793-1 v2

18.6.1 Functionality M15302-3 v5

The Signal matrix for binary inputs (SMBI) function is used within the Application Configuration Tool
(ACT) in direct relation with the Signal Matrix Tool (SMT), see the application manual to get
information about how binary inputs are brought in for one IED configuration.

Transformer protection RET650 743


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

18.6.2 Function block M15306-3 v3

SMBI
^VIN1 ^BI1
^VIN2 ^BI2
^VIN3 ^BI3
^VIN4 ^BI4
^VIN5 ^BI5
^VIN6 ^BI6
^VIN7 ^BI7
^VIN8 ^BI8
^VIN9 ^BI9
^VIN10 ^BI10

IEC05000434-2-en.vsd
IEC05000434 V2 EN-US

Figure 409: SMBI function block

18.6.3 Signals SEMOD55814-1 v2

PID-3940-INPUTSIGNALS v5

Table 683: SMBI Input signals

Name Type Default Description


BI1 BOOLEAN 0 SMT Connect input
BI2 BOOLEAN 0 SMT Connect input
BI3 BOOLEAN 0 SMT Connect input
BI4 BOOLEAN 0 SMT Connect input
BI5 BOOLEAN 0 SMT Connect input
BI6 BOOLEAN 0 SMT Connect input
BI7 BOOLEAN 0 SMT Connect input
BI8 BOOLEAN 0 SMT Connect input
BI9 BOOLEAN 0 SMT Connect input
BI10 BOOLEAN 0 SMT Connect input

PID-3940-OUTPUTSIGNALS v5

Table 684: SMBI Output signals

Name Type Description


BI1 BOOLEAN Binary input 1
BI2 BOOLEAN Binary input 2
BI3 BOOLEAN Binary input 3
BI4 BOOLEAN Binary input 4
BI5 BOOLEAN Binary input 5
BI6 BOOLEAN Binary input 6
BI7 BOOLEAN Binary input 7
BI8 BOOLEAN Binary input 8
BI9 BOOLEAN Binary input 9
BI10 BOOLEAN Binary input 10

18.6.4 Operation principle M15305-3 v5

The Signal matrix for binary inputs (SMBI) function , see figure 409, receives its inputs from the real
(hardware) binary inputs via the Signal Matrix Tool (SMT) or ACT, and makes them available to the
rest of the configuration via its outputs, BI1 to BI10. The inputs and outputs, as well as the whole
block, can be given a user defined name. These names will be represented in SMT as information

744 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

which signals shall be connected between physical IO and SMBI function. The input/output user
defined name will also appear on the respective output/input signal.

18.7 Signal matrix for binary outputs SMBO SEMOD55215-1 v2

18.7.1 Functionality M15311-3 v5

The Signal matrix for binary outputs (SMBO) function is used within the Application Configuration
Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see the application manual to get
information about how binary inputs are sent from one IED configuration.

18.7.2 Function block SEMOD54860-4 v3

SMBO
BO1 ^BO1
BO2 ^BO2
BO3 ^BO3
BO4 ^BO4
BO5 ^BO5
BO6 ^BO6
BO7 ^BO7
BO8 ^BO8
BO9 ^BO9
BO10 ^BO10
IEC05000439 V3 EN-US

Figure 410: SMBO function block

18.7.3 Signals SEMOD55887-1 v2

PID-3831-INPUTSIGNALS v5

Table 685: SMBO Input signals

Name Type Default Description


BO1 BOOLEAN 0 Signal name for BO1 in Signal Matrix Tool
BO2 BOOLEAN 0 Signal name for BO2 in Signal Matrix Tool
BO3 BOOLEAN 0 Signal name for BO3 in Signal Matrix Tool
BO4 BOOLEAN 0 Signal name for BO4 in Signal Matrix Tool
BO5 BOOLEAN 0 Signal name for BO5 in Signal Matrix Tool
BO6 BOOLEAN 0 Signal name for BO6 in Signal Matrix Tool
BO7 BOOLEAN 0 Signal name for BO7 in Signal Matrix Tool
BO8 BOOLEAN 0 Signal name for BO8 in Signal Matrix Tool
BO9 BOOLEAN 0 Signal name for BO9 in Signal Matrix Tool
BO10 BOOLEAN 0 Signal name for BO10 in Signal Matrix Tool

18.7.4 Operation principle SEMOD55864-4 v7

The Signal matrix for binary outputs (SMBO) function , see figure 410, receives logical signal from
the IED configuration, which is transferring to the real (hardware) outputs, via the Signal Matrix Tool
(SMT) or ACT. The inputs in SMBO are BO1 to BO10 and they, as well as the whole function block,
can be tag-named. The name tags will appear in SMT as information which signals shall be
connected between physical IO and the SMBO.

18.8 Signal matrix for analog inputs SMAI SEMOD55751-1 v2

Transformer protection RET650 745


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

18.8.1 Functionality SEMOD55744-4 v10

Signal matrix for analog inputs (SMAI), also known as the preprocessor function block, analyses the
connected four analog signals (three phases and neutral) and calculates all relevant information from
them like the phasor magnitude, phase angle, frequency, true RMS value, harmonics, sequence
components and so on. This information is then used by the respective functions connected to this
SMAI block in ACT (for example protection, measurement or monitoring functions).

18.8.2 Function block SEMOD55766-1 v3

SEMOD54868-4 v12

SMAI_20_10
BLOCK AI3P
REVROT AI1
^GRP10L1 AI2
^GRP10L2 AI3
^GRP10L3 AI4
^GRP10N AIN

IEC14000027 V2 EN-US

Figure 411: SMAI1 function block


Figure 411 is an example of SMAI1:n in each of the four task time groups 1, 2, 3 or 4 where:

• n=1 in task group 1


• n=13 in task group 2
• n=25 in task group 3
• n=37 in task group 4

The number of available task time groups depend on product and configuration. Up to four task time
groups are available in a product. The task time defines the execution repetition rate for the task time
groups. The task times valid for a product are found in PCM600, Application configuration tool.
SEMOD54997-4 v11

SMAI2
BLOCK G2AI3P
REVROT G2AI1
^GRP2L1 G2AI2
^GRP2L2 G2AI3
^GRP2L3 G2AI4
^GRP2N G2N

IEC14000028 V2 EN-US

Figure 412: SMAI2 function block


Figure 412 is an example of SMAI2:n to SMAI12:m in each of the four task time groups 1, 2, 3 or 4
where:

• n=2 and m=12 in task group 1


• n=14 and m=24 in task group 2
• n=26 and m=36 in task group 3
• n=38 and m=48 in task group 4

The number of available task time groups depend on product and configuration. Up to four task time
groups are available in a product. The task time defines the execution repetition rate for the task time
groups. The task times valid for a product are found in PCM600, Application configuration tool.

746 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

18.8.3 Signals SEMOD55773-1 v2

PID-3405-INPUTSIGNALS v6

Table 686: SMAI1 Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block group 1
DFTSPFC REAL 20.0 Number of samples per fundamental cycle used for DFT
calculation
REVROT BOOLEAN 0 Reverse rotation group 1
GRP1L1 STRING - First analog input used for phase L1 or L1-L2 quantity
GRP1L2 STRING - Second analog input used for phase L2 or L2-L3 quantity
GRP1L3 STRING - Third analog input used for phase L3 or L3-L1 quantity
GRP1N STRING - Fourth analog input used for residual or neutral quantity

PID-3405-OUTPUTSIGNALS v5

Table 687: SMAI1 Output signals

Name Type Description


SPFCOUT REAL Number of samples per fundamental cycle from internal DFT
reference function
G1AI3P GROUP SIGNAL Group 1 analog input 3-phase group
G1AI1 GROUP SIGNAL Group 1 analog input 1
G1AI2 GROUP SIGNAL Group 1 analog input 2
G1AI3 GROUP SIGNAL Group 1 analog input 3
G1AI4 GROUP SIGNAL Group 1 analog input 4
G1N GROUP SIGNAL Group parameter for residual sample

PID-3406-INPUTSIGNALS v6

Table 688: SMAI2 Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block group 2
REVROT BOOLEAN 0 Reverse rotation group 2
GRP2L1 STRING - First analog input used for phase L1 or L1-L2 quantity
GRP2L2 STRING - Second analog input used for phase L2 or L2-L3 quantity
GRP2L3 STRING - Third analog input used for phase L3 or L3-L1 quantity
GRP2N STRING - Fourth analog input used for residual or neutral quantity

PID-3406-OUTPUTSIGNALS v5

Table 689: SMAI2 Output signals

Name Type Description


G2AI3P GROUP SIGNAL Group 2 analog input 3-phase group
G2AI1 GROUP SIGNAL Group 2 analog input 1
G2AI2 GROUP SIGNAL Group 2 analog input 2
G2AI3 GROUP SIGNAL Group 2 analog input 3
G2AI4 GROUP SIGNAL Group 2 analog input 4
G2N GROUP SIGNAL Group parameter for residual sample

Transformer protection RET650 747


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

18.8.4 Settings SEMOD55783-1 v2

SEMOD130357-4 v3

Settings DFTRefExtOut and DFTReference shall be set to default value InternalDFTRef if


no VT inputs are available. Internal nominal frequency DFT reference is then the
reference.
PID-3405-SETTINGS v5

Table 690: SMAI1 Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current

Table 691: SMAI1 Non group settings (advanced)

Name Values (Range) Unit Step Default Description


Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase

748 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

PID-3406-SETTINGS v5

Table 692: SMAI2 Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current

Table 693: SMAI2 Non group settings (advanced)

Name Values (Range) Unit Step Default Description


Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase

18.8.5 Operation principle SEMOD55746-4 v14

Every Signal matrix for analog inputs function (SMAI) can receive four analog signals (three phases
and one neutral or residual value), either voltage or current, see figure 411 and figure 412. SMAI
outputs give information about every aspect of the 3ph analog signals acquired (phase angle, RMS
value, frequency and frequency derivates etc. – 244 values in total). The BLOCK input will force all
outputs to value zero if BLOCK is TRUE (1). However, when the disturbance recorder is connected to
the single-phase outputs of SMAI, the sample data to the disturbance recorder will not be blocked.
The disturbance recorder bypasses SMAI to the sample data channels.

System phase rotation and frequency are defined using the PhaseRotation and Frequency settings in
the primary system values PRIMVAL function. Logic 1 in the REVROT input to the SMAI function
means that the phase rotation is changed relative to the set PhaseRotation in PRIMVAL.

The output signal AI1 to AI4 are single phase outputs which directly represent the four inputs
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. GxN (x = 1-12) is always calculated residual sum
from the first three inputs. A3P is grouped, three-phase information containing all relevant information
about four connected inputs. Note that all other functions, with a few exceptions, use this output in
configuration. Note that the SMAI function will always calculate the residual sum of current/voltage if
the input GRPxN is not connected in SMT. Applications with a few exceptions shall always be
connected to AI3P.

18.8.5.1 Frequency values GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5

The SMAI function includes a functionality based on the level of positive sequence voltage,
MinValFreqMeas, to validate if the frequency measurement is valid or not. If the positive sequence

Transformer protection RET650 749


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

voltage is lower than MinValFreqMeas, the function freezes the frequency output value for 500 ms
and after that the frequency output is set to the nominal value. A signal is available for the SMAI
function to prevent operation due to non-valid frequency values. MinValFreqMeas is set as % of
UBase/√3

If SMAI setting ConnectionType is Ph-Ph, at least two of the inputs GRPxL1, GRPxL2 and GRPxL3,
where 1≤x≤12, must be connected in order to calculate the positive sequence voltage. Note that
phase to phase inputs shall always be connected as follows: L1-L2 to GRPxL1, L2-L3 to GRPxL2,
L3-L1 to GRPxL3. If SMAI setting ConnectionType is Ph-N, all three inputs GRPxL1, GRPxL2 and
GRPxL3 must be connected in order to calculate the positive sequence voltage.

If only one phase-phase voltage is available and SMAI setting ConnectionType is Ph-Ph, the user is
advised to connect two (not three) of the inputs GRPxL1, GRPxL2 and GRPxL3 to the same voltage
input as shown in figure 413 to make SMAI calculate a positive sequence voltage.

SMAI1
BLOCK SPFCOUT SAPTOF
DFTSPFC G1AI3P U3P* TRIP SAPTOF(1)_TRIP
UL1L2 BLOCK START
REVROT G1AI1
PHASEL1 G1AI2 BLKTRIP BLKDMAGN
^GRP1L1 G1AI4 FREQ
TRM_40.CH7(U) PHASEL2
G1N
^GRP1L2
PHASEL3
^GRP1L3
NEUTRAL
^GRP1N

IEC10000060 V4 EN-US

Figure 413: Connection example

The above described scenario does not work if SMAI setting ConnectionType is Ph-N. If
only one phase-earth voltage is available, the same type of connection can be used but
the SMAI ConnectionType setting must still be Ph-Ph and this has to be accounted for
when setting MinValFreqMeas. If SMAI setting ConnectionType is Ph-N and the same
voltage is connected to all three SMAI inputs, the positive sequence voltage will be zero
and the frequency functions will not work properly.

The outputs from the above configured SMAI block shall only be used for Overfrequency
protection (SAPTOF), Underfrequency protection (SAPTUF) and Rate-of-change
frequency protection (SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.

18.8.6 SMAI incorrect calculated phase-earth GUID-7AE6FC17-74AA-403B-8559-3B9D6DA1E433 v1

In some configurations SMAI may produce incorrectly calculated phase-earth values, when this is the
case, a hint will be available in LHMI with text as below.

Calculated phase-earth values are used from one or more SMAIs configured for phase-phase inputs,
without connection to N input.

However, this configuration, combined with unbalanced three-phase input, results in incorrect
calculated phase-earth values.

This in turn may result in maloperation of functions connected to SMAIs configured in this way, if the
function uses phase-earth based values.

Further, if SUM3PH is connected to such a SMAI, then its output values will be incorrect, and the
connected functions may maloperate.

To rectify this situation, revise the configuration from this perspective.

750 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 18
Basic IED functions

18.9 Summation block 3 phase 3PHSUM SEMOD55968-1 v2

18.9.1 Functionality SEMOD55976-4 v4

Summation block 3 phase function 3PHSUM is used to get the sum of two sets of three-phase
analog signals (of the same type) for those IED functions that might need it.

18.9.2 Function block SEMOD54885-4 v4

3PHSUM
BLOCK SPFCOUT
BLKGR1 AI3P
BLKGR2 AI1
REVROT AI2
^G1AI3P* AI3
^G2AI3P* AI4
IEC05000441-4-en.vsdx
IEC05000441 V4 EN-US

Figure 414: 3PHSUM function block

18.9.3 Signals SEMOD55989-1 v2

PID-6428-INPUTSIGNALS v3

Table 694: 3PHSUM Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block
BLKGR1 BOOLEAN 0 Block input for group 1
BLKGR2 BOOLEAN 0 Block input for group 2
REVROT BOOLEAN 0 Reverse rotation
G1AI3P GROUP - Group 1 three phase analog input from first SMAI
SIGNAL
G2AI3P GROUP - Group 2 three phase analog input from second SMAI
SIGNAL

PID-6428-OUTPUTSIGNALS v4

Table 695: 3PHSUM Output signals

Name Type Description


SPFCOUT REAL Number of samples per fundamental cycle from internal DFT
reference function
AI3P GROUP SIGNAL Linear combination of two connected three phase inputs
AI1 GROUP SIGNAL Linear combination of input 1 signals from both SMAI blocks
AI2 GROUP SIGNAL Linear combination of input 2 signals from both SMAI blocks
AI3 GROUP SIGNAL Linear combination of input 3 signals from both SMAI blocks
AI4 GROUP SIGNAL Linear combination of input 4 signals from both SMAI blocks

18.9.4 Settings SEMOD55995-1 v2

SEMOD130361-4 v2

Settings DFTRefExtOut and DFTReference shall be set to default value InternalDFTRef if


no VT inputs are available.

Transformer protection RET650 751


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 18 1MRK504170-UEN Rev. J
Basic IED functions

PID-6428-SETTINGS v3

Table 696: 3PHSUM Non group settings (basic)

Name Values (Range) Unit Step Default Description


GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
SummationType Group1+Group2 - - Group1+Group2 Summation type
Group1-Group2
Group2-Group1
-(Group1+Group2)
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
External DFT ref
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
DFTRefGrp1
External DFT ref

Table 697: 3PHSUM Non group settings (advanced)

Name Values (Range) Unit Step Default Description


FreqMeasMinVal 5 - 200 % 1 10 Amplitude limit for frequency calculation in
% of UBase

18.9.5 Operation principle SEMOD55749-4 v6

Summation block 3 phase 3PHSUM receives the three-phase signals from Signal matrix for analog
inputs function (SMAI). The BLOCK input will reset all the outputs of the function to 0.

18.10 Primary system values PRIMVAL

18.10.1 Identification
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Primary system values PRIMVAL - -

18.10.2 Functionality M15288-3 v6

The rated system frequency and phase rotation direction are set under Main menu /Configuration /
Power system / Primary Values in the local HMI and PCM600 parameter setting tree.

18.10.3 Settings
PID-1626-SETTINGS v17

Table 698: PRIMVAL Non group settings (basic)

Name Values (Range) Unit Step Default Description


Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
PhaseRotation Normal=L1L2L3 - - Normal=L1L2L3 System phase rotation
Inverse=L3L2L1

752 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Section 19 IED hardware


19.1 Overview IP14270-1 v1

19.1.1 Variants of case size with local HMI display M15024-3 v7

IEC04000458 V3 EN-US

Figure 415: 1/2 19” case with local HMI display.

Transformer protection RET650 753


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.1.2 Case from the front and rear sides IP16286-1 v2

M16105-3 v11

Table 699: Designations for 1/2 x 19” casing with 1 TRM slot

1/2x19"
Front view Rear position Module
p40 p31 p30 p5 p4 p3 p1
X11 PSM
P30:1
P30:2

X31 and X32 etc. to X51 and X52 BIM, BOM or IOM
P30:3

X301, X302, X303, X304 SFP


P30:4

X305 LDCM
P31:1

6U X306 LDCM
X311: A, B, C, D SLM
X312 IRIG-B or RS485
P31:2
P30:5

X313 IRIG-B or RS485


P31:3
P30:6

X401 TRM

Rear view
X11 X31 X41 X51 X401
X301

X302

X303

X311
A

X304
B

X32 X42 X52 D

X305 X312

X306 X313

IEC17000067 V1 EN-US

19.2 Hardware modules IP14529-1 v1

19.2.1 Overview M11562-3 v11

Table 700: Basic modules

Module Description
Power supply module (PSM) Including a regulated DC/DC converter that supplies auxiliary
voltage to all static circuits.

• An internal fail alarm output is available.

Numerical module (NUM) Module for overall application control. All information is processed
or passed through this module, such as configuration, settings and
communication. The module provides four SFPs for Ethernet
traffic.
Local Human machine interface (LHMI) The module consists of LEDs, an LCD, a push button keyboard
and an ethernet connector used to connect a PC to the IED.
Transformer input module (TRM) Transformer module that galvanically separates the internal circuits
from the VT and CT circuits. It has 12 analog inputs.
Table continues on next page

754 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Module Description
Analog digital conversion module (ADM) The module converts the VT and CT analog signals from the TRM
to digital signals processed by the NUM. Carrier for communication
boards.
Note: TRM module is not included in SAM600-IO, so ADM module
is only used for internal communication carrier for IO modules.
Combined backplane module (CBM) The module has two main purposes: to distribute supply voltages
from the PSM to the other modules and to act as a communication
carrier via its two buses, CompactPCI for fast I/O and
communication and CAN for slow I/O.
Universal backplane module (UBM) The module is used to interconnect the TRM and the ADM. It also
connects the NUM with the LHMI

Table 701: Application specific modules

Module Description
Binary input module (BIM) Module with 16 optically isolated binary inputs
Binary output module (BOM) Module with 24 single outputs or 12 double-pole command outputs
including supervision function
Binary I/O module (IOM) Module with 8 optically isolated binary inputs, 10 outputs and 2 fast
signalling outputs.
Serial SPA/LON/IEC 60870-5-103 Used for SPA/LON/IEC 60870–5–103 communication
communication modules (SLM)
Optical Ethernet SFP Small form factor pluggable for Ethernet communication
Galvanic RJ45 Ethernet SFP Small form factor pluggable for Ethernet communication
Galvanic RS485 communication module Module used for DNP3 and IEC 60870-5-103 communication
(RS485)
IRIG-B Time synchronization module (IRIG-B) Module with 2 inputs. One is used for handling both pulse-width
modulated signals and amplitude modulated signals and one is
used for optical input type ST for PPS time synchronization.

19.2.2 Numeric module (NUM) IP14288-1 v2

19.2.2.1 Introduction M12643-3 v5

The numeric processing module (NUM) is a CPU module that handles all protection functions and
logic.

For communication with high speed modules, for example analog input modules and high speed
serial interfaces, NUM is equipped with a Compact PCI bus. NUM is a compact PCI system card,
that is, it controls bus mastering, clock distribution and receives interrupts.

NUM provides up to 4 optical (type LC) or galvanic (type RJ45) Ethernet ports (one basic and three
optional).

Ethernet ports can be configured as four separate or in redundant mode PRP, HSR, or RSTP. The
combination supports two PRP, two HSR networks, or one RSTP network.

19.2.2.2 Functionality M12644-3 v7

The numeric module (NUM) is a high-performance CPU module based on a dual-core processor. It is
6U high and occupies one slot. Contact with the backplane is achieved via a compact PCI connector
and an euro connector.

The NUM has two PC-MIP expansion slots where mezzanine cards, such as the LDCM, can be
mounted. It also has four SFP cages for Ethernet communication. Up to four SFP transceivers for

Transformer protection RET650 755


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

optical 100BASE-FX or galvanic RJ45 100BASE-TX communication can be mounted in the SFP
cages.

Only SFP transceivers approved by Hitachi Energy (1MRK005500) are compatible with
the SFP cages.

Application code and configuration data are stored in flash memory, and non-volatile RAM is used to
store log data.

The NUM is equipped with a real time clock. It uses a capacitor to keep track of the time when the
IED is not energized.

The NUM is passively cooled, which is possible due to its low power dissipation.

19.2.2.3 Technical data SEMOD55319-1 v1

SEMOD55310-2 v16

Table 702: SFP - Optical ethernet port

Quantity Rated value


Number of channels 4 single or 2 redundant can be used for single or redundant communication using
any protocol
Standard IEEE 802.3u 100BASE-FX
Type of fiber 1MRK005500-AA: 62.5/125 mm, 50/125 mm multimode
OM1, OM2, OM3, OM4
1MRK005500-DA: 9/125 mm single mode fiber, OS1, OS2
1MRK005500-EA: 9/125 mm single mode fiber, OS2
1MRK005500-FA: 9/125 mm single mode fiber, OS2
Wavelength and distance 1MRK005500-AA: 1310 nm, 1 m - 2 km
1MRK005500-DA: 1310 nm, 1 m - 10 km (OS1), 1 m - 30 km (OS21))
1)
1MRK005500-EA: 1310 nm, 10 km - 60 km (OS2 )
1)
1MRK005500-FA: 1550 nm, 10 km - 120 km (OS2 )
(All are Class 1 laser safety)
Optical connector Type LC
Communication speed Fast Ethernet 100 Mbit/s

1) For distances above approximately 60% of maximum specified fiber length special care needs to be taken and fiber
used should have an attenuation <0.25 dB/km

Table 703: SFP - Galvanic RJ45

Quantity Rated value


Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Standard IEEE 802.3u 100BASE-TX
Type of cable Cat5e FTP
Connector Type RJ45
Communication Speed Fast Ethernet 100 Mbit/s

GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3

Table 704: NUM: Communication ports

NUM 4 Ethernet ports


1 Basic, 3 Optional
Ethernet connection type SFP Optical LC or Galvanic RJ45

756 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.2.3 Power supply module (PSM) IP15594-1 v1

19.2.3.1 Introduction M11595-3 v6

The power supply module is used to provide the correct internal voltages and full isolation between
the IED and the battery system. An internal fail alarm output is available.

Alternative connectors of Ring lug or Compression type can be ordered.

19.2.3.2 Design IP14278-1 v1

M6377-3 v2
There are two types of the power supply module. They are designed for different DC input voltage
ranges see table 705. The power supply module contains a built-in, self-regulated DC/DC converter
that provides full isolation between the terminal and the external battery system.

The DC input is protected against inverse polarity within the rated DC voltage range.

Connection diagram M6377-8 v3

IEC08000476 V2 EN-US

Figure 416: PSM Connection diagram.

19.2.3.3 Technical data SEMOD52801-1 v1

M12286-1 v9

Table 705: PSM - Power supply module

Quantity Rated value Nominal range


Auxiliary DC voltage, EL (input) EL = (24-60) V EL ±20%
EL = (90-250) V EL ±20%
Power consumption 32 W typically -
Auxiliary DC power in-rush < 10 A during 0.1 s -
Supply interruption bridging time < 50 ms -

GUID-61AA4AEF-D09C-4BA6-9142-B5CA857C0574 v2

Table 706: IRF - Internal Fail relay output

Quantity Rated value


Max. system voltage 250 V DC
Min. load voltage 24 V DC
Number of outputs 1
Test voltage across open contact, 1 min 1000 V rms
Table continues on next page

Transformer protection RET650 757


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Quantity Rated value


Current carrying capacity:
Continuous 4A
1.0 s 8A
Making capacity at capacitive load with the maximum
capacitance of 0.2 μF: 20 A
0.2 s 8A
1.0 s
Making capacity for DC with L/R > 10 ms:
0.2 s 20 A
1.0 s 8A
Making capacity at resistive load
0.2 s 20 A
1.0 s 8A
Breaking capacity for DC with L/R ≤ 40 ms 48 V/1 A
(According to IEC 61810-1) 110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Breaking capacity for DC with L/R=100 ms 110 V/0.3 A
Breaking capacity for DC with resistive load 48 V/2 A
110 V/0.5 A
125 V/0.45 A
220 V/0.35 A
250 V/0.3 A
Max. operations with inductive load L/R ≤ 40 ms 1000
Max. operations with resistive load 2000
Max. operations with no load 30 million

19.2.4 Local human-machine interface (Local HMI) SEMOD56218-5 v4

Refer to section Local HMI for information.

19.2.5 Transformer input module (TRM) IP15581-1 v1

19.2.5.1 Introduction M14875-3 v10

The transformer input module is used to galvanically separate and adapt the secondary currents and
voltages generated by the measuring transformers. The module has twelve inputs in different
combinations of currents and voltage inputs.

Ring lug or compression type connectors can be ordered.

19.2.5.2 Design M14858-3 v8

The transformer module has 10 voltage and 2 current input transformers.

TRM variants are available depending on the product. The rated values and channel type of the
current inputs are selected at order.

Transformer input module for measuring should not be used with current transformers
intended for protection purposes, due to limitations in overload characteristics.

The TRM is connected to the ADM and NUM.

758 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

For configuration of the input and output signals, refer to section "Signal matrix for analog inputs
SMAI".

1MRK006501-AF-TRM-IEC-6502P1 V1 EN-US

Figure 417: TRM connection diagram

19.2.5.3 Technical data SEMOD55412-1 v1

M16988-1 v11

Table 707: TRM - Energizing quantities, rated values and limits for protection transformer

Description Value
Frequency
Rated frequency fr 50/60 Hz
Operating range fr ± 10%
Current inputs
Rated current Ir 1 or 5 A
Operating range (0-100) x Ir
Thermal withstand 100 × Ir for 1 s *)
30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously
Dynamic withstand 250 × Ir one half wave
Burden < 20 mVA at Ir = 1 A
< 150 mVA at Ir = 5 A
*) max. 350 A for 1 s when COMBITEST test switch is included.
Voltage inputs **)
Table continues on next page

Transformer protection RET650 759


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Description Value
Rated voltage Ur 110 or 220 V
Operating range 0 - 340 V
Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

19.2.6 Binary input module (BIM) IP14535-1 v1

19.2.6.1 Introduction M1769-3 v4

The binary input module has 16 optically isolated inputs and is available in two versions, one
standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse
counter function. The binary inputs are freely programmable and can be used for the input of logical
signals to any of the functions. They can also be included in the disturbance recording and event-
recording functions. This enables extensive monitoring and evaluation of operation of the IED and for
all associated electrical circuits.

19.2.6.2 Design M11586-3 v6

The Binary input module contains 16 optical isolated binary inputs. The voltage level of the binary
input is selected at order.

For configuration of the input signals, refer to section "Signal matrix for binary inputs SMBI".

A signal discriminator detects and blocks oscillating signals. When blocked, a hysteresis function
may be set to release the input at a chosen frequency, making it possible to use the input for pulse
counting. The blocking frequency may also be set.

Well defined input high and input low voltages ensure normal operation at battery supply earth faults,
see figure 418 The figure shows the typical operating characteristics of the binary inputs of the four
voltage levels.

The standard version of binary inputs gives an improved capability to withstand disturbances and
should generally be used when pulse counting is not required. Inputs are debounced by software.

I/O events are time stamped locally on each module for minimum time deviance and stored by the
event recorder if present.

760 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

[V]

300

176
144
88
72
38
32
19
17

24/30V 48/60V 110/125V 220/250V

xx06000391-2-en.vsd
IEC06000391 V2 EN-US

Figure 418: Voltage dependence for the binary inputs

Operation

Operation uncertain

No operation
IEC99000517-ABC V1 EN-US

This binary input module communicates with the Numerical module (NUM).

The design of all binary inputs enables the burn off of the oxide of the relay contact connected to the
input, despite the low, steady-state power consumption, which is shown in figure 419 and 420.

[mA]
50

55 [ms]

en07000104-3.vsd
IEC07000104 V3 EN-US

Figure 419: Approximate binary input inrush current for the standard version of BIM.

Transformer protection RET650 761


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

[mA]
50

5.5 [ms]

en07000105-1.vsd
IEC07000105 V2 EN-US

Figure 420: Approximate binary input inrush current for the BIM version with enhanced pulse
counting capabilities.

IEC99000503 V3 EN-US

Figure 421: Connection diagram

762 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.2.6.3 Signals
PID-6435-OUTPUTSIGNALS v5

Table 708: BIM Output signals

Name Type Description


STATUS BOOLEAN Binary input module status
BI1 BOOLEAN Binary input 1 value
BI2 BOOLEAN Binary input 2 value
BI3 BOOLEAN Binary input 3 value
BI4 BOOLEAN Binary input 4 value
BI5 BOOLEAN Binary input 5 value
BI6 BOOLEAN Binary input 6 value
BI7 BOOLEAN Binary input 7 value
BI8 BOOLEAN Binary input 8 value
BI9 BOOLEAN Binary input 9 value
BI10 BOOLEAN Binary input 10 value
BI11 BOOLEAN Binary input 11 value
BI12 BOOLEAN Binary input 12 value
BI13 BOOLEAN Binary input 13 value
BI14 BOOLEAN Binary input 14 value
BI15 BOOLEAN Binary input 15 value
BI16 BOOLEAN Binary input 16 value
OSCWRN BOOLEAN Oscillation warning

19.2.6.4 Settings
PID-3473-SETTINGS v2

Table 709: BIM Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Operation Off/On
On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

19.2.6.5 Monitored data


PID-3473-MONITOREDDATA v2

Table 710: BIM Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Binary input module status
1=Error

Transformer protection RET650 763


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.2.6.6 Technical data SEMOD55338-1 v1

M12576-1 v13

Table 711: BIM - Binary input module

Quantity Rated value Nominal range


Binary inputs 16 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter Settable 1–20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

M50609-2 v10

Table 712: BIM - Binary input module with enhanced pulse counting capabilities

Quantity Rated value Nominal range


Binary inputs 16 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

764 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Table 713: IOM - Binary input/output module

Quantity Rated value Nominal range


Binary inputs 8 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Counter input frequency 10 pulses/s max
Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

19.2.7 Binary output modules (BOM) IP14536-1 v1

19.2.7.1 Introduction M6938-3 v4

The binary output module has 24 independent output relays and is used for trip output or any
signaling purpose.

19.2.7.2 Design M1819-3 v4

The binary output module (BOM) has 24 software supervised output relays. Each pair of relays have
a common power source input to the contacts, see figure 422. This should be considered when
connecting the wiring to the connection terminal on the back of the IED.

The high closing and carrying current capability allows connection directly to breaker trip and closing
coils. If breaking capability is required to manage fail of the breaker auxiliary contacts normally
breaking the trip coil current, a parallel reinforcement is required.

For configuration of the output signals, refer to section "Signal matrix for binary outputs SMBO".

Transformer protection RET650 765


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Output module

xx00000299.vsd

IEC00000299 V1 EN-US

Figure 422: Relay pair example

1 Output connection from relay 1


2 Output signal power source connection
3 Output connection from relay 2

IEC99000505 V5 EN-US

Figure 423: Connection diagram

19.2.7.3 Signals
PID-3439-INPUTSIGNALS v2

Table 714: BOM Input signals

Name Type Default Description


BLOCK BOOLEAN 0 Block binary outputs
BO1 BOOLEAN 0 Binary output 1
BO2 BOOLEAN 0 Binary output 2
BO3 BOOLEAN 0 Binary output 3
BO4 BOOLEAN 0 Binary output 4
BO5 BOOLEAN 0 Binary output 5
Table continues on next page

766 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Name Type Default Description


BO6 BOOLEAN 0 Binary output 6
BO7 BOOLEAN 0 Binary output 7
BO8 BOOLEAN 0 Binary output 8
BO9 BOOLEAN 0 Binary output 9
BO10 BOOLEAN 0 Binary output 10
BO11 BOOLEAN 0 Binary output 11
BO12 BOOLEAN 0 Binary output 12
BO13 BOOLEAN 0 Binary output 13
BO14 BOOLEAN 0 Binary output 14
BO15 BOOLEAN 0 Binary output 15
BO16 BOOLEAN 0 Binary output 16
BO17 BOOLEAN 0 Binary output 17
BO18 BOOLEAN 0 Binary output 18
BO19 BOOLEAN 0 Binary output 19
BO20 BOOLEAN 0 Binary output 20
BO21 BOOLEAN 0 Binary output 21
BO22 BOOLEAN 0 Binary output 22
BO23 BOOLEAN 0 Binary output 23
BO24 BOOLEAN 0 Binary output 24

PID-3439-OUTPUTSIGNALS v1

Table 715: BOM Output signals

Name Type Description


STATUS BOOLEAN Binary output part of IOM module status

19.2.7.4 Settings
PID-3439-SETTINGS v2

Table 716: BOM Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Operation Off/On
On

19.2.7.5 Monitored data


PID-3439-MONITOREDDATA v2

Table 717: BOM Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Binary output part of IOM module status
1=Error
BO1VALUE BOOLEAN 1=1 - Binary output 1 value
0=0
BO1FORCE BOOLEAN 0=Normal - Binary output 1 force
1=Forced
BO1 BOOLEAN 0=Normal - Binary output 1 status
1=Forced
2=Blocked
BO2VALUE BOOLEAN 1=1 - Binary output 2 value
0=0
Table continues on next page

Transformer protection RET650 767


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Name Type Values (Range) Unit Description


BO2FORCE BOOLEAN 0=Normal - Binary output 2 force
1=Forced
BO2 BOOLEAN 0=Normal - Binary output 2 status
1=Forced
2=Blocked
BO3VALUE BOOLEAN 1=1 - Binary output 3 value
0=0
BO3FORCE BOOLEAN 0=Normal - Binary output 3 force
1=Forced
BO3 BOOLEAN 0=Normal - Binary output 3 status
1=Forced
2=Blocked
BO4VALUE BOOLEAN 1=1 - Binary output 4 value
0=0
BO4FORCE BOOLEAN 0=Normal - Binary output 4 force
1=Forced
BO4 BOOLEAN 0=Normal - Binary output 4 status
1=Forced
2=Blocked
BO5VALUE BOOLEAN 1=1 - Binary output 5 value
0=0
BO5FORCE BOOLEAN 0=Normal - Binary output 5 force
1=Forced
BO5 BOOLEAN 0=Normal - Binary output 5 status
1=Forced
2=Blocked
BO6VALUE BOOLEAN 1=1 - Binary output 6 value
0=0
BO6FORCE BOOLEAN 0=Normal - Binary output 6 force
1=Forced
BO6 BOOLEAN 0=Normal - Binary output 6 status
1=Forced
2=Blocked
BO7VALUE BOOLEAN 1=1 - Binary output 7 value
0=0
BO7FORCE BOOLEAN 0=Normal - Binary output 7 force
1=Forced
BO7 BOOLEAN 0=Normal - Binary output 7 status
1=Forced
2=Blocked
BO8VALUE BOOLEAN 1=1 - Binary output 8 value
0=0
BO8FORCE BOOLEAN 0=Normal - Binary output 8 force
1=Forced
BO8 BOOLEAN 0=Normal - Binary output 8 status
1=Forced
2=Blocked
BO9VALUE BOOLEAN 1=1 - Binary output 9 value
0=0
BO9FORCE BOOLEAN 0=Normal - Binary output 9 force
1=Forced
BO9 BOOLEAN 0=Normal - Binary output 9 status
1=Forced
2=Blocked
BO10VALUE BOOLEAN 1=1 - Binary output 10 value
0=0
Table continues on next page

768 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Name Type Values (Range) Unit Description


BO10FORCE BOOLEAN 0=Normal - Binary output 10 force
1=Forced
BO10 BOOLEAN 0=Normal - Binary output 10 status
1=Forced
2=Blocked
BO11VALUE BOOLEAN 1=1 - nary output 11 value
0=0
BO11FORCE BOOLEAN 0=Normal - Binary output 11 force
1=Forced
BO11 BOOLEAN 0=Normal - Binary output 11 status
1=Forced
2=Blocked
BO12VALUE BOOLEAN 1=1 - Binary output 12 value
0=0
BO12FORCE BOOLEAN 0=Normal - Binary output 12 force
1=Forced
BO12 BOOLEAN 0=Normal - Binary output 12 status
1=Forced
2=Blocked
BO13VALUE BOOLEAN 1=1 - Binary output 13 value
0=0
BO13FORCE BOOLEAN 0=Normal - Binary output 13 force
1=Forced
BO13 BOOLEAN 0=Normal - Binary output 13 status
1=Forced
2=Blocked
BO14VALUE BOOLEAN 1=1 - Binary output 14 value
0=0
BO14FORCE BOOLEAN 0=Normal - Binary output 14 force
1=Forced
BO14 BOOLEAN 0=Normal - Binary output 14 status
1=Forced
2=Blocked
BO15VALUE BOOLEAN 1=1 - Binary output 15 value
0=0
BO15FORCE BOOLEAN 0=Normal - Binary output 15 force
1=Forced
BO15 BOOLEAN 0=Normal - Binary output 15 status
1=Forced
2=Blocked
BO16VALUE BOOLEAN 1=1 - Binary output 16 value
0=0
BO16FORCE BOOLEAN 0=Normal - Binary output 16 force
1=Forced
BO16 BOOLEAN 0=Normal - Binary output 16 status
1=Forced
2=Blocked
BO17VALUE BOOLEAN 1=1 - Binary output 17 value
0=0
B017FORCE BOOLEAN 0=Normal - Binary output 17 force
1=Forced
BO17 BOOLEAN 0=Normal - Binary output 17 status
1=Forced
2=Blocked
BO18VALUE BOOLEAN 1=1 - Binary output 18 value
0=0
Table continues on next page

Transformer protection RET650 769


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Name Type Values (Range) Unit Description


BO18FORCE BOOLEAN 0=Normal - Binary output 18 force
1=Forced
BO18 BOOLEAN 0=Normal - Binary output 18 status
1=Forced
2=Blocked
BO19VALUE BOOLEAN 1=1 - Binary output 19 value
0=0
BO19FORCE BOOLEAN 1=Forced - Binary output 19 force
0=Normal
BO19 BOOLEAN 0=Normal - Binary output 19 status
1=Forced
2=Blocked
BO20VALUE BOOLEAN 1=1 - Binary output 20 value
0=0
BO20FORCE BOOLEAN 0=Normal - Binary output 20 force
1=Forced
BO20 BOOLEAN 0=Normal - Binary output 20 status
1=Forced
2=Blocked
BO21VALUE BOOLEAN 1=1 - Binary output 21 value
0=0
BO21FORCE BOOLEAN 0=Normal - Binary output 21 force
1=Forced
BO21 BOOLEAN 0=Normal - Binary output 21 status
1=Forced
2=Blocked
BO22VALUE BOOLEAN 1=1 - Binary output 22 value
0=0
BO22FORCE BOOLEAN 0=Normal - Binary output 22 force
1=Forced
BO22 BOOLEAN 0=Normal - Binary output 22 status
1=Forced
2=Blocked
BO23VALUE BOOLEAN 1=1 - Binary output 23 value
0=0
BO23FORCE BOOLEAN 0=Normal - Binary output 23 force
1=Forced
BO23 BOOLEAN 0=Normal - Binary output 23 status
1=Forced
2=Blocked
BO24VALUE BOOLEAN 1=1 - Binary output 24 value
0=0
BO24FORCE BOOLEAN 0=Normal - nary output 24 force
1=Forced
BO24 BOOLEAN 0=Normal - Binary output 24 status
1=Forced
2=Blocked

770 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.2.7.6 Technical data SEMOD55355-1 v1

M12441-1 v13

Table 718: BOM - Binary output module contact data (reference standard: IEC 61810-1)

Function or quantity Trip and Signal relays


Binary outputs 24
Max system voltage 250 V AC/DC
Min load voltage 24 V DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A
Max operations with inductive load L/R ≤ 40 ms 1000
Max operations with resistive load 2000
Max operations with load 1000
Max operations with no load 30 million
Making capacity for DC with L/R > 10 ms:
0.2 s 30 A
1.0 s 10 A
Making capacity at resistive load
0.2 s 30 A
1.0 s 10 A
Breaking capacity for AC, cos j > 0.4 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Breaking capacity for DC with L/R=100ms 110 V / 0.3 A
Breaking capacity for DC with resistive load 48 V / 2 A
110 V / 0.5 A
125 V / 0.45 A
220 V / 0.35 A
250 V / 0.3 A
Operating time < 6 ms

Maximum 72 outputs may be activated simultaneously with influencing factors within


nominal range. After 6 ms an additional 24 outputs may be activated. The activation time
for the 96 outputs must not exceed 200 ms. 48 outputs can be activated during 1 s.
Continued activation is possible with respect to current consumption but after 5 minutes
the temperature rise will adversely affect the hardware life. Maximum two relays per
BOM/IOM should be activated continuously due to power dissipation.

The stated operate time for functions include the operating time for the binary inputs and
outputs.

19.2.8 Binary input/output module (IOM) IP15582-1 v1

19.2.8.1 Introduction M6939-3 v6

The binary input/output module is used when only a few input and output channels are needed. The
ten standard output channels are used for trip output or any signaling purpose. The two high speed

Transformer protection RET650 771


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

signal output channels are used for applications where short operating time is essential. Eight
optically isolated binary inputs cater for required binary input information.

19.2.8.2 Design IP10635-1 v2

M1718-3 v4
The binary input/output module is available in two basic versions, one with unprotected contacts and
one with MOV (Metal Oxide Varistor) protected contacts.

Inputs are designed to allow oxide burn-off from connected contacts, and increase the disturbance
immunity during normal protection operate times. This is achieved with a high peak inrush current
while having a low steady-state current, see figure 419. Inputs are debounced by software.

Well defined input high and input low voltages ensures normal operation at battery supply earth
faults, see figure 418.

The voltage level of the inputs is selected when ordering. Alternative connectors of Ring lug or
Compression type can be ordered.

I/O events are time stamped locally on each module for minimum time deviance and stored by the
event recorder if present.
M1898-3 v3
The binary I/O module, IOM, has eight optically isolated inputs and ten output relays. One of the
outputs has a change-over contact. The nine remaining output contacts are connected in two groups.
One group has five contacts with a common and the other group has four contacts with a common, to
be used as single-output channels, see figure 424.

The binary I/O module also has two high speed output channels where a reed relay is connected in
parallel to the standard output relay.

For configuration of the input and output signals, refer to sections "Signal matrix for binary inputs
SMBI" and "Signal matrix for binary outputs SMBO".

The making capacity of the reed relays are limited.

772 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

IEC1MRK002801-AA11-UTAN-RAM V2 EN-US

Figure 424: Binary in/out module (IOM), input contacts named XA corresponds to rear
position X31, X41, and so on, and output contacts named XB to rear position X32,
X42, and so on
SEMOD175370-4 v1
The binary input/output module version with MOV protected contacts can for example be used in
applications where breaking high inductive load would cause excessive wear of the contacts.

The test voltage across open contact is lower for this version of the binary input/output
module.

xx04000069.vsd

IEC04000069 V1 EN-US

Figure 425: IOM with MOV protection, relay example

Transformer protection RET650 773


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.2.8.3 Signals
PID-6434-OUTPUTSIGNALS v4

Table 719: IOMIN Output signals

Name Type Description


STATUS BOOLEAN Binary input part of IOM module status
BI1 BOOLEAN Binary input 1 value
BI2 BOOLEAN Binary input 2 value
BI3 BOOLEAN Binary input 3 value
BI4 BOOLEAN Binary input 4 value
BI5 BOOLEAN Binary input 5 value
BI6 BOOLEAN Binary input 6 value
BI7 BOOLEAN Binary input 7 value
BI8 BOOLEAN Binary input 8 value
OSCWRN BOOLEAN Oscillation warning

PID-4049-INPUTSIGNALS v2

Table 720: IOMOUT Input signals

Name Type Default Description


BLKOUT BOOLEAN 0 Block binary outputs
BO1 BOOLEAN 0 Binary output 1
BO2 BOOLEAN 0 Binary output 2
BO3 BOOLEAN 0 Binary output 3
BO4 BOOLEAN 0 Binary output 4
BO5 BOOLEAN 0 Binary output 5
BO6 BOOLEAN 0 Binary output 6
BO7 BOOLEAN 0 Binary output 7
BO8 BOOLEAN 0 Binary output 8
BO9 BOOLEAN 0 Binary output 9
BO10 BOOLEAN 0 Binary output 10
BO11 BOOLEAN 0 Binary output 11
BO12 BOOLEAN 0 Binary output 12

19.2.8.4 Settings
PID-4050-SETTINGS v2

Table 721: IOMIN Non group settings (basic)

Name Values (Range) Unit Step Default Description


Operation Off - - On Binary input/output module in operation
On (On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

774 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.2.8.5 Monitored data


PID-4050-MONITOREDDATA v2

Table 722: IOMIN Monitored data

Name Type Values (Range) Unit Description


STATUS BOOLEAN 0=Ok - Binary input part of IOM module status
1=Error

PID-4049-MONITOREDDATA v2

Table 723: IOMOUT Monitored data

Name Type Values (Range) Unit Description


BO1VALUE BOOLEAN 1=1 - Binary output 1 value
0=0
BO1FORCE BOOLEAN 0=Normal - Binary output 1 force
1=Forced
BO1 BOOLEAN 0=Normal - Binary output 1 status
1=Forced
2=Blocked
BO2VALUE BOOLEAN 1=1 - Binary output 2 value
0=0
BO2FORCE BOOLEAN 0=Normal - Binary output 2 force
1=Forced
BO2 BOOLEAN 0=Normal - Binary output 2 status
1=Forced
2=Blocked
BO3VALUE BOOLEAN 1=1 - Binary output 3 value
0=0
BO3FORCE BOOLEAN 0=Normal - Binary output 3 force
1=Forced
BO3 BOOLEAN 0=Normal - Binary output 3 status
1=Forced
2=Blocked
BO4VALUE BOOLEAN 1=1 - Binary output 4 value
0=0
BO4FORCE BOOLEAN 0=Normal - Binary output 4 force
1=Forced
BO4 BOOLEAN 0=Normal - Binary output 4 status
1=Forced
2=Blocked
BO5VALUE BOOLEAN 1=1 - Binary output 5 value
0=0
BO5FORCE BOOLEAN 0=Normal - Binary output 5 force
1=Forced
BO5 BOOLEAN 0=Normal - Binary output 5 status
1=Forced
2=Blocked
BO6VALUE BOOLEAN 1=1 - Binary output 6 value
0=0
BO6FORCE BOOLEAN 0=Normal - Binary output 6 force
1=Forced
BO6 BOOLEAN 0=Normal - Binary output 6 status
1=Forced
2=Blocked
BO7VALUE BOOLEAN 1=1 - Binary output 7 value
0=0
BO7FORCE BOOLEAN 0=Normal - Binary output 7 force
1=Forced
Table continues on next page

Transformer protection RET650 775


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

Name Type Values (Range) Unit Description


BO7 BOOLEAN 0=Normal - Binary output 7 status
1=Forced
2=Blocked
BO8VALUE BOOLEAN 1=1 - Binary output 8 value
0=0
BO8FORCE BOOLEAN 0=Normal - Binary output 8 force
1=Forced
BO8 BOOLEAN 0=Normal - Binary output 8 status
1=Forced
2=Blocked
BO9VALUE BOOLEAN 1=1 - Binary output 9 value
0=0
BO9FORCE BOOLEAN 0=Normal - Binary output 9 force
1=Forced
BO9 BOOLEAN 0=Normal - Binary output 9 status
1=Forced
2=Blocked
BO10VALUE BOOLEAN 1=1 - Binary output 10 value
0=0
BO10FORCE BOOLEAN 0=Normal - Binary output 10 force
1=Forced
BO10 BOOLEAN 0=Normal - Binary output 10 status
1=Forced
2=Blocked
BO11VALUE BOOLEAN 1=1 - Binary output 11 value
0=0
BO11FORCE BOOLEAN 0=Normal - Binary output 11 force
1=Forced
BO11 BOOLEAN 0=Normal - Binary output 11 status
1=Forced
2=Blocked
BO12VALUE BOOLEAN 1=1 - Binary output 12 value
0=0
BO12FORCE BOOLEAN 0=Normal - Binary output 12 force
1=Forced
BO12 BOOLEAN 0=Normal - Binary output 12 status
1=Forced
2=Blocked

19.2.8.6 Technical data IP10636-1 v1

M12573-1 v11

Table 724: IOM - Binary input/output module

Quantity Rated value Nominal range


Binary inputs 8 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Counter input frequency 10 pulses/s max
Table continues on next page

776 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Quantity Rated value Nominal range


Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

The stated operate time for functions include the operating time for the binary inputs and
outputs.

M12318-1 v13

Table 725: IOM - Binary input/output module contact data (reference standard: IEC 61810-1)

Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 21)
Max system voltage 250 V AC/DC 250 V DC
Min load voltage 24 V DC —
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A
Making capacity for DC with L/R > 10 ms:

0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Making capacity at resistive load
220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A
(According to IEC 61810-1) 110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Breaking capacity for DC with L/R=100ms 110 V / 0.3 A 110 V / 0.3 A
Breaking capacity for DC with resistive load 48 V / 2 A 48 V / 2 A
110 V / 0.5 A 110 V / 0.5 A
125 V / 0.45 A 125 V / 0.45 A
220 V / 0.35 A 220 V / 0.35 A
250 V / 0.3 A 250 V / 0.3 A
Maximum capacitive load - 10 nF
Max operations with inductive load L/R ≤ 40 ms 1000
Max operations with resistive load 2000
Max operations with no load 30 million
Operating time < 6 ms <= 1 ms

1) These reed relays have been excluded from UL evaluation.

Transformer protection RET650 777


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

M12584-1 v13

Table 726: IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1)

Function or quantity Trip and Signal relays Fast signal relays (parallel reed
relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC/ DC 250 V DC
Min load voltage 24 V DC -
Test voltage across open contact, 1 min 250 V rms 250 V rms
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A
Making capacity for DC with L/R > 10 ms:
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Making capacity at resistive load
220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos j > 0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A
(According to IEC 61810-1) 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Breaking capacity for DC with L/R=100ms 110 V / 0.3 A 110 V / 0.3 A
Breaking capacity for DC with resistive load 48 V / 2 A 48 V / 2 A
110 V / 0.5 A 110 V / 0.5 A
125 V / 0.45 A 125 V / 0.45 A
220 V / 0.35 A 220 V / 0.35 A
250 V / 0.3 A 250 V / 0.3 A
Maximum capacitive load - 10 nF
Max operations with inductive load L/R ≤ 40 ms 1000 -
Max operations with resistive load 2000
Max operations with no load 30 million -
Operating time < 6 ms <= 1 ms

19.2.9 Serial and LON communication module (SLM) IP15583-1 v2

19.2.9.1 Introduction M14933-3 v6

The Serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103, DNP3 and
LON communication. SLM has two optical communication ports for plastic/plastic, plastic/glass or
glass/glass fiber cables. One port is used for serial communication (SPA, IEC 60870-5-103 or DNP3
port) and the other port is used for LON communication.

19.2.9.2 Design M17126-3 v7

SLM is a PMC card and it is factory mounted as a mezzanine card on the first Analog digital
conversion module (ADM). Three variants of SLM are available with different combinations of optical
fiber connectors, see figure 426. The plastic fiber connectors are of snap-in type and the glass fiber
connectors are of ST type.

778 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

I
EC0500760=1=en=Or
igi
nal
.psd
IEC05000760 V2 EN-US

Figure 426: SLM variants, component side view

1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103/DNP3
4 Transmitter, SPA/IEC 60870-5-103/DNP3
A Snap-in connector for plastic fiber
B ST connector for glass fiber

In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D
are for LON protocol.

IEC21000051 V1 EN-US

Figure 427: X311 ports

Transformer protection RET650 779


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.2.9.3 Technical data SEMOD117454-1 v1

M12589-1 v6

Table 727: SLM – LON port

Quantity Range or value


Optical connector Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
Plastic fiber: 7 dB (10m/35 ft typically *)
Fiber diameter Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm
*) depending on optical budget calculation

SEMOD117441-2 v7

Table 728: SLM – SPA/IEC 60870-5-103/DNP3 port

Quantity Range or value


Optical connector Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
Plastic fiber: 7 dB (25m/80 ft typically *)
Fiber diameter Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm
*) depending on optical budget calculation

19.2.10 Galvanic RS485 communication module SEMOD174899-1 v1

19.2.10.1 Introduction SEMOD158664-5 v3

The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC 60870-5-103
communication. The module has one RS485 communication port. The RS485 is a balanced serial
communication that can be used either in 2-wire or 4-wire connections. A 2-wire connection uses the
same signal for RX and TX and is a multidrop communication with no dedicated Master or slave. This
variant requires however a control of the output. The 4-wire connection has separated signals for RX
and TX multidrop communication with a dedicated Master and the rest are slaves. No special control
signal is needed in this case.

19.2.10.2 Design SEMOD158668-1 v1

SEMOD158670-4 v3
RS485 is a PC-MIP card, and it is factory mounted as a mezzanine card on the Analog digital
conversion module (ADM).

RS485 connector pinouts SEMOD158670-10 v1


The arrangement for the pins in the RS485 connector (figure 428) are presented in table 729:

Table 729: The arrangement for the pins

Pin Name 2-wire Name 4-wire Description


1 RS485+ TX+ Receive/transmit high or transmit high
2 RS485– TX– Receive/transmit
3 Term T-Term Termination resistor for transmitter (and receiver in 2–wir case)
(connect to TX+)
Table continues on next page

780 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

4 N.A. R-Term Termination resistor for receiver (connect to RX+)


5 N.A. RX– Receive low
6 N.A. RX+ Receive high

Angle
bracket

Screw
1
terminal
X3 2
1
2 RS485
3 PWB
Screw
4
terminal
5
X1
6

Backplane

IEC06000517 V1 EN-US

Figure 428: RS485 connector

• 2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5

• Termination (2-wire): Connect pin 1 to pin 3

• Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6

Soft ground connector pinouts SEMOD158670-45 v1


A second 2-pole screw connector is used for the connection of IO-ground. It can be used in two
combinations like:

• Unconnected: No ground of the IO-part · .

• Soft grounded: The IO is connected to the GND with an RC net parallel with a MOV

19.2.10.3 Serial optical and RS485 communication channel settings GUID-E86643AC-2771-47CE-89D7-7FC9F47ED9E1 v4

RS485 specific communication channel settings, RS485GEN


Wiremode determines the wire mode if the device is configured for RS485. RS485 is a balanced
serial communication that can be used in two ways:

• Two-wire
• Four-wire

A two-wire connection uses the same signal for RX and TX, and is a multidrop communication with
no dedicated master or slave. This variant requires however a control of the output. The four-wire
connection has separate signals for RX and TX multidrop communication with a dedicated master
and the rest are slaves. No special control signal is needed in this case.

Operation selection for RS485 and optical serial communication,


OPTICALPROT and RS485PROT
ProtocolSel selects if the communication in RS485 and optical serial modes happens via DNP or IEC
103 communication protocol. It can be Off via Parameter Setting tool or local HMI.

Transformer protection RET650 781


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

DNP3.0 for optical RS-232 and EIA-485 communication protocol,


OPTICALDNP and RS485DNP
BaudRate specifies the baud rate on the serial.

DLinkConfirm determines when the stack should ask for link layer confirmations. Since DNP3
supports breaking an application layer message into multiple link layer frames, set to the following
based on the desired operation for a specific communication session:

• Never - not for any frame


• Sometimes - only for multiframe message fragments
• Always - for all frames

tDLinkTimeout specifies the maximum amount of time to wait for a link level confirm if requested (that
is, if DLinkConfirm is On). Even if DLinkConfirm is set to Never, this will be used for linktest frame
and request link status if they are sent.

DLinkRetries is the maximum number of link layer retries if data-link layer confirms time up.

tRxToTxMinDel is the minimum time (in seconds) after receiving a character, before another attempt
to transmit a character on this channel. This is generally useful when using a modem or some other
communication device that requires a minimum time between receive and transmit.

ApLayMaxRxSize specifies the maximum application fragment size received in octets.

ApLayMaxTxSize specifies the maximum application fragment size transmitted in octets.

Stopbit defines the number of stop bits for the serial port.

Parity defines the parity to use for the serial port it can be set to:

• None - no parity used


• Even - even parity used
• Odd - odd parity used

tRTSWarmUp configures transmitter warm-up and warm-down delay times (in milliseconds). If warm-
up is configured to non-zero then at start of the send, the transmitter is On. This means that the line
is driven but the data send of the start is delayed by the warm-up delay time.

tRTSWarmDown specifies that if warm-down is configured to non zero then at end of the send, the
transmitter deactivation is delayed by the warm-down time.

tBackOffDelay specifies that if the data send is started, a check is made if data is being received at
that time. If yes, a back-off timer is started and when it times out, a check is made again to see if line
is idle. If no, a new back-off timer is started. This is repeated until the line is idle and send can start.
Line idle is determined when nothing is received for more than a character time. The back-off time
consists of a configurable fixed time and a random time where the maximum random time is also
configurable. The back-off feature is always on.

tMaxRndDelBkOf specifies the configurable RS485 maximum back-off random time delay in
seconds.

HWCollisionDetect, a new collision detect feature in hardware is implemented to improve the


sensitivity for collision detection. The performance of this feature depends on parameters of the
RS485 network as well as the protocol behaviour. It can even have negative impact on performance
in some circumstances, therefore usage of the feature should be tested and adapted for each
specific installation.

HWCollisionDetect is only used for RS485 networks, thus is only available in RS485DNP
function.

782 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Master session settings for RS485 communication channel, MSTSERIAL


ChToAssociate defines the channel, to which this master session should be associated to.

The MSTSERIAL function includes the same settings as the MS1TCP to MS4TCP
functions, except the ChToAssociate setting which is used to select either the serial
optical or RS485 communication interface on hardware modules.

19.2.10.4 Parameter list for optical and RS485 communication channel


PID-4060-SETTINGS v5

Table 730: RS485GEN Non group settings (basic)

Name Values (Range) Unit Step Default Description


WireMode Four-wire - - Four-wire Two or four wire mode
Two-wire

19.2.10.5 Technical data SEMOD158678-1 v1

SEMOD158710-2 v3

Table 731: Galvanic RS485 communication module

Quantity Range or value


Communication speed 2400–19200 bauds
External connectors RS-485 6-pole connector
Soft ground 2-pole connector

19.2.11 IRIG-B time synchronization module IRIG-B SEMOD141102-1 v1

19.2.11.1 Introduction SEMOD141113-4 v9

The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from a
station clock.

The Pulse Per Second (PPS) input is supported.

Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.

19.2.11.2 Design SEMOD141098-4 v5

The IRIG-B module has two inputs. One input is for the IRIG-B that can handle both a pulse-width
modulated signal (also called unmodulated) and an amplitude modulated signal (also called sine
wave modulated). The other is an optical input type ST for optical pulse-width modulated signal
(IRIG-B 00X). The IRIG-B module is mounted as a mezzanine card on the Analog digital conversion
module (ADM).

Transformer protection RET650 783


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

ST

Y2

A1

IEC06000304=1=en=Original.ai
IEC06000304 V2 EN-US

Figure 429: IRIG-B PC-MIP board with top left ST connector for optical IRIG-B 00X 820 nm
multimode fiber optic signal input and lower left BNC connector for IRIG-B signal
input

19.2.11.3 Encoding GUID-9F0D795F-80D6-46D2-A5CC-F34F701C8E85 v1

This type of encoding consists of the following options:

• IRIG-B. This encoding is based on the legacy of (pre-2004) IRIG-B standard which is without
any time zone information. IRIG-B uses the timecoding available in IRIG-B 00x and IRIG-B 12x,
where x = 0-7. When x is set in the range from 4-7, the year information is provided along with
year and time data.
• 1344. This encoding is based on the current (2004) IRIG-B standard. IED uses the time zone
information from TIMEZONE:1. The setting 1344 refers to the Annex F in IEEE1344, which adds
information regarding quality of the time using the control bits in the IRIG-B message. This
annex also contains the year information with the variable x that ranges from 4-7 in the 2004
version of IRIG-B.
• 1344TZ. This encoding is based on the current (2004) IRIG-B standard. This time zone
information from IRIG-B overrides the TIMEZONE:1 settings. This setting” uses the information
as 1344, overriding the TIMEZONE setting.

19.2.11.4 TimeZoneAs1344 GUID-39AACFEA-2E3E-4B39-9D7A-E49DA5DE3506 v1

This type of encoding consists of the following options:

• MinusTZ. Encoded IRIG time minus time zone offset equals UTC at all times.
• PlusTZ. Encoded IRIG time plus time zone offset equals UTC at all times.

784 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.2.11.5 Settings
PID-5187-SETTINGS v5

Table 732: IRIG-B Non group settings (basic)

Name Values (Range) Unit Step Default Description


SynchType BNC - - Opto Type of synchronization
Opto
TimeDomain LocalTime - - LocalTime Time domain
UTC
Encoding IRIG-B - - IRIG-B Type of encoding
1344
1344TZ
TimeZoneAs1344 MinusTZ - - PlusTZ Time zone as in 1344 standard
PlusTZ

19.2.11.6 Technical data SEMOD141132-1 v1

SEMOD141136-2 v10

Table 733: IRIG-B

Quantity Rated value


Number of channels IRIG-B 1
Number of optical channels 1
Electrical connector:
Electrical connector IRIG-B BNC
Pulse-width modulated 5 Vpp
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Supported formats IRIG-B 00x, IRIG-B 12x
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Input impedance 100 k ohm
Optical connector:
Optical connector IRIG-B Type ST
Type of fiber 62.5/125 μm multimode fiber
Supported formats IRIG-B 00x
Accuracy +/- 1μs

Transformer protection RET650 785


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.3 Dimensions IP11490-1 v3

19.3.1 Case with protective cover SEMOD53199-1 v2

M11985-110 v7

IEC08000163 V4 EN-US

Figure 430: Case with protective cover

786 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

IEC08000165 V4 EN-US

Figure 431: Case with protective cover and 19” rack mounting kit

Transformer protection RET650 787


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

IEC05000503 V4 EN-US

Figure 432: Protective cover case with details


M11985-120 v6

Case size A B C D E F G H I
(mm)
6U, 1/2 x 19” 265.9 223.7 247.5 255.0 205.8 190.5 466.5 232.5 482.6
The G and I dimensions are defined by the 19” rack mounting kit.

788 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.3.2 Case without protective cover SEMOD53195-1 v2

M2152-3 v8

IEC08000164 V5 EN-US

Figure 433: Case without protective cover

Transformer protection RET650 789


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

IEC08000166 V4 EN-US

Figure 434: Case without protective cover with 19” rack mounting kit
M2152-11 v5

Case size
A B C D E F G H I
(mm)
6U, 1/2 x 19” 265.9 223.7 204.1 249.9 205.8 190.5 466.5 189.1 482.6
The G and I dimensions are defined by the 19” rack mounting kit

790 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.3.3 Flush mounting dimensions M11571-3 v6

A C

E
D

IEC04000465 V4 EN-US

Figure 435: Flush mounting

Cut-out dimensions (mm)


Case size
A B C D
Tolerance
+/-1 +/-1
6U, 1/2 x 19" 210.1 254.3 4.0-10.0 13.5
E = 191.1 mm without rear protection cover, 231.8 mm with rear protection cover

19.3.4 Side-by-side flush mounting dimensions M11984-3 v6

IEC06000182 V3 EN-US

Figure 436: A 1/2 x 19” size IED side-by-side with RHGS6

Transformer protection RET650 791


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

D
B
E

F
C
xx05000505.vsd
IEC05000505 V1 EN-US

Figure 437: Panel-cut out dimensions for side-by-side flush mounting

Case size A B C D E F G
(mm) ±1 ±1 ±1 ±1 ±1 ±1 ±1
Tolerance
6U, 1/2 x 19” 214.0 259.3 240.4 190.5 34.4 13.2 6.4 diam

19.3.5 Wall mounting dimensions M11569-3 v5

IEC04000471 V3 EN-US

Figure 438: Wall mounting

Case size (mm) A B C D E


6U, 1/2 x 19” 292.0 267.1 272.8 390.0 243.0

792 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.4 Mounting alternatives IP11721-1 v1

19.4.1 Flush mounting IP10303-1 v1

19.4.1.1 Overview M11967-3 v5

The flush mounting kit can be used for the 1/2 x 19” case size.

Only a single case can be mounted in each cut-out on the cubicle panel, for class IP54 protection.
The screws from the IED shall be used to fasten the fasteners to the IED.

Flush mounting cannot be used for side-by-side mounted IEDs when IP54 class must be
fulfilled. Only IP20 class can be obtained when mounting two cases side-by-side in one
(1) cut-out.

To obtain IP54 class protection, an additional factory mounted sealing must be ordered
when ordering the IED.

19.4.1.2 Mounting procedure for flush mounting M11942-2 v6

IEC16000080 V2 EN-US

Figure 439: Flush mounting details.

Transformer protection RET650 793


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

PosNo Description Quantity Type


1 Sealing strip, used to obtain IP54 - -
class. The sealing strip is factory
mounted between the case and front
plate.
2 Joining point of sealing strip - -
3 Flush mounting rail 2 -
4 Nut 4 M8
5 Mounting kit 2 -
6 Spring lock washer 4 M8
7 Panel 1 -
8 Fastening foot 4 -

19.4.2 Wall mounting IP10316-1 v1

19.4.2.1 Overview M11973-3 v7

The IED can be mounted on a wall, a panel or in a cubicle.

Use only the screws included in the mounting kit when mounting the plates and the
angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED.

If fiber cables are bent too much, the signal can be weakened. Wall mounting is therefore
not recommended for any communication modules with fiber connection.

19.4.2.2 Mounting procedure for wall mounting M11949-2 v4

2
3
1 4

IEC13000266 V2 EN-US

Figure 440: Wall mounting details.

794 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

PosNo Description Quantity Type


1 Bushing 4 -
2 Screw 8 M4x10
3 Screw 4 M6x12 or
corresponding
4 Mounting bar 2 -
5 Screw 6 M5x8
6 Side plate 2 -

19.4.2.3 How to reach the rear side of the IED M11941-2 v5

The IED can be equipped with a rear protection cover recommended to be used with this type of
mounting. See figure 441.

To reach the rear side of the IED, a free space of 80 mm is required on the unhinged side.

3
1

80 mm 2

IEC06000135 V4 EN-US

Figure 441: How to reach the connectors on the rear side of the IED.

PosNo Description Type


1 Screw M4x10
2 Screw M5x8
3 Rear protection cover (Ordered separately)

19.4.3 19” panel rack mounting IP10313-1 v1

19.4.3.1 Overview SEMOD127656-5 v4

The IED can be mounted in a standard 19” cubicle rack by using a mounting kit consisting of two
mounting angles and their fastening screws.

The mounting angles are reversible which enables mounting of the IED either to the left or the right
side of the cubicle.

Transformer protection RET650 795


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

A separately ordered rack mounting kit for side-by-side mounted IEDs or IEDs together
with RHGS cases should be selected so that the total size equals 19”.

Use only the screws included in the mounting kit when mounting the plates and the
angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED.

19.4.3.2 Mounting procedure for 19” panel rack mounting M11948-2 v7

1a

1b

IEC04000452-3-en.vsd
IEC04000452 V4 EN-US

Figure 442: 19” panel rack mounting details

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1a, 1b Mounting angles, can be mounted either 2 -
to the left or the right side of the case
2 Screw 8 M4x6
3 Washer 8 M4x6

19.4.4 Side-by-side 19” rack mounting IP10323-1 v1

19.4.4.1 Overview M11974-3 v3

IED case size 1/2 x 19” and RHGS cases can be mounted side-by-side up to a maximum size of 19”.
For side-by-side rack mounting, the side-by-side mounting kit together with the 19” rack panel
mounting kit must be used. The mounting kit has to be ordered separately.

796 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Use only the screws included in the mounting kit when mounting the plates and the
angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED.

19.4.4.2 Mounting procedure for side-by-side rack mounting M11955-2 v4

3 1
2

IEC04000456 V4 EN-US

Figure 443: Side-by-side rack mounting details.

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw 16 M4x6
4 Mounting angle 2 -
5 Washer 16 M4x6

19.4.4.3 IED mounted with a RHGS6 case M11953-3 v4

A 1/2 x 19” size IED can be mounted with a RHGS case (6 or 12). The RHGS case can be used for
mounting a test switch of type RTXP 24. It also has enough space for a terminal base of RX 2 type
for mounting of, for example, a DC-switch or two auxiliary relays.

Transformer protection RET650 797


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

1 2 1 2

1 1 1 1

2 2 2 2

3 3 3 3

4 4 4 4

5 5 5 5

6 6 6 6

7 7 7 7

8 8 8 8

IEC06000180 V3 EN-US

Figure 444: IED (1/2 x 19”) mounted with a RHGS6 case containing a test switch module
equipped with only a test switch and a RX2 terminal base

19.4.5 Side-by-side flush mounting IP10329-1 v1

19.4.5.1 Overview M11975-3 v3

If IP54 is required it is not allowed to flush mount side by side mounted cases. If your application
demands side-by-side flush mounting, the side-by-side mounting details kit and the 19” panel rack
mounting kit must be used. The mounting kit has to be ordered separately. The maximum size of the
panel cut out is 19”.

With side-by-side flush mounting installation, only IP class 20 is obtained. To reach IP


class 54, it is required to mount the IEDs separately. For cut out dimensions of separately
mounted IEDs, see section "Flush mounting".

Use only the screws included in the mounting kit when mounting the plates and the
angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED.

Please contact factory for special add on plates for mounting FT switches on the side (for
1/2 19" case) or bottom of the relay.

798 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

19.4.5.2 Mounting procedure for side-by-side 19" rack mounting M12730-6 v5

1 2

IEC06000181 V3 EN-US

Figure 445: Side-by-side rack mounting details (RHGS6 side-by-side with 1/2 x 19” IED).

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw, washer 16 M4x6
4 Mounting angle 2 -

19.5 Technical data IP16276-1 v2

19.5.1 Enclosure IP16278-1 v1

M11778-1 v8

Table 734: Case

Material Steel sheet


Front plate Stainless steel with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)

M12327-1 v6

Table 735: Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)


Sides, top and bottom IP40
Rear side IP20 with screw compression type
IP10 with ring lug terminals

Transformer protection RET650 799


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

M11777-1 v8

Table 736: Weight

Case size Weight


6U, 1/2 x 19” £ 7.5 kg/16 lb

19.5.2 Electrical safety GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1

GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v3

Table 737: Electrical safety according to IEC 60255-27

Equipment class I (protective earthed)


Overvoltage category III
Pollution degree 2 (normally only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation
is to be expected)

19.5.3 Connection system SEMOD53371-1 v1

SEMOD53376-2 v6

Table 738: CT and VT circuit connectors

Connector type Rated voltage and current Maximum conductor area


Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm 2 (AWG12)

M12583-1 v8

Table 739: Auxiliary power supply connectors

Connector type Rated voltage Maximum conductor area


Screw compression type 250 V AC 2.5 mm2 (AWG14)
2 × 1 mm 2 (2 x AWG18)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)

Table 740: Binary I/O connectors

Connector type Rated voltage Maximum conductor area


Screw compression type 250 V AC 2.5 mm2 (AWG14)
2 × 1 mm 2 (2 x AWG18)

19.5.4 Influencing factors SEMOD52785-1 v1

M16705-1 v18

Table 741: Temperature and humidity influence

Parameter Reference value Nominal range Influence


Ambient temperature, +20±5°C -25°C to +55°C 0.02%/°C
operate value
Relative humidity 45-75% 10-90% -
Operative range 0-95%

800 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Table 742: Auxiliary DC supply voltage influence on functionality during operation

Dependence on Reference value Within nominal Influence


range
Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%
Operative range Full wave rectified
Auxiliary voltage dependence, operate ±20% of EL 0.01%/%
value
Interrupted auxiliary DC voltage 24-60 V DC ± 20%

Interruption interval 90-250 V DC ± 20%


0–50 ms
No restart
0–∞ s Correct behaviour at power
down
Restart time < 300 s

Table 743: Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence


Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0%/Hz
fr ±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ±1.0%
content)
Harmonic frequency dependence for high 2nd, 3rd and 5th harmonic of fr ±10.0%
impedance differential protection (10%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr ±3.0%
restricted earth fault protection
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr ±3.0%
overcurrent protection

Table 744: Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence


Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0%/Hz
fr ±3.0 Hz for 60 Hz
Frequency dependence for differential fr ±2.5 Hz for 50 Hz ±2.0%/Hz
protection fr ±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ±1.0%
content)
Harmonic frequency dependence for high 2nd, 3rd and 5th harmonic of fr ±5.0%
impedance differential protection (10%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr ±3.0%
restricted earth fault protection (20%
content)

Transformer protection RET650 801


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19 1MRK504170-UEN Rev. J
IED hardware

19.5.5 Type tests according to standard IP16288-1 v1

M16706-1 v15

Table 745: Electromagnetic compatibility

Test Type test values Reference standards


1 MHz burst disturbance 2.5 kV IEC 60255-26
100 kHz slow damped oscillatory wave 2.5 kV IEC 61000-4-18, Level 3
immunity test
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Level 4
Electrostatic discharge 15 kV air discharge IEC 60255-26
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Level 4
Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.3
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge
Fast transient disturbance 4 kV IEC 60255-26, Zone A
2 kV, SFP galvanic RJ45
2 kV, MIM mA-inputs IEC 60255-26, Zone B
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B
Power frequency immunity test 150-300 V, 50 Hz IEC 60255-26, Zone A
Conducted common mode immunity test 30-3 V, 15-150 Hz IEC 61000-4-16, Level 4
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Level 5
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Level 5
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Level 5
Radiated electromagnetic field 20 V/m IEC 60255-26
disturbance 80-1000 MHz IEEE/ANSI C37.90.2
1.4-2.7 GHz EN 50121-5
10 V/m, 2.7-6.0 GHz
Radiated emission 30-6000 MHz IEC 60255-26
30-8500 MHz IEEE/ANSI C63.4, FCC
Conducted emission 0.15-30 MHz IEC 60255-26

Table 746: Insulation

Test Type test values Reference standard


Dielectric test 2.0 kV AC, 1 min. IEC 60255-27
1.0 kV AC, 1 min.: ANSI C37.90
-SFP galvanic RJ45 IEEE 802.3-2015, Environment A
- X.21-LDCM
Impulse voltage test 5 kV, 1.2/50ms, 0.5 J
1 kV, 1.2/50 ms 0.5 J:
-SFP galvanic RJ45
- X.21-LDCM
Insulation resistance > 100 MW at 500 VDC

802 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 19
IED hardware

Table 747: Environmental conditions

Description Value
Operating temperature range -25°C to +55°C (continuous)
Short-time service temperature range -40°C to +70°C (<16h)
Note: Degradation in MTBF and HMI performance
outside the temperature range of -25°C to +55°C
Relative humidity <93%, non-condensing
Atmospheric pressure 86 kPa to 106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40°C to +85°C

Table 748: Environmental tests

Test Type test value Reference standard


Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1
Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1
Dry heat operation test Test Bd for 16 h at +70°C IEC 60068-2-2
Dry heat storage test Test Bb for 16 h at +85°C IEC 60068-2-2
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 56 days at +40°C and humidity IEC 60068-2-78
93%
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)

Table 749: CE compliance

Test According to
Electromagnetic compatibility (EMC) EN 60255–26
Low voltage (LVD) EN 60255–27

Table 750: Mechanical tests

Test Type test values Reference standards


Vibration response test Class II: Rack mount IEC 60255-21-1
Class I: Flush and wall mount
Vibration endurance test Class I: Rack, flush and wall mount IEC 60255-21-1
Shock response test Class I: Rack, flush and wall mount IEC 60255-21-2
Shock withstand test Class I: Rack, flush and wall mount IEC 60255-21-2
Bump test Class I: Rack, flush and wall mount IEC 60255-21-2
Seismic test Class II: Rack mount IEC 60255-21-3
Class I: Flush and wall mount

Transformer protection RET650 803


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
804
1MRK504170-UEN Rev. J Section 20
Labels

Section 20 Labels
20.1 Labels on IED SEMOD168249-4 v6

Front view of IED

5
2

9
3
IEC16000081 V2 EN-US

Figure 446: Example of IED label

1 QR-code containing the complete ordering code


2 Power supply module (PSM)
3 Ordering and serial number
4 Transformer designations
5 Transformer input module, rated currents and voltages
6 Optional, customer specific information
7 Order number, dc supply voltage and rated frequency
8 Product type, description and serial number
9 Product type

Transformer protection RET650 805


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 20 1MRK504170-UEN Rev. J
Labels

Rear view of IED

IEC15000573=2=en=Original.wsdx
IEC15000573 V2 EN-US

1 Warning label
2 Caution label
3 Class 1 laser product label It is used when an optical SFP or an MR LDCM is configured in the
product.

IEC06000575 V1 EN-US

806 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 21
Connection diagrams

Section 21 Connection diagrams GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v10

The connection diagrams are delivered in the IED Connectivity package as part of the product
delivery.

The latest versions of the connection diagrams can be downloaded from


http://www.hitachienergy.com/protection-control.

Connection diagrams for Configured products

Connection diagram, RET650 2.2, A01X00 1MRK006507-TA

Connection diagram, RET650 2.2, A05X00 1MRK006507-TB

Connection diagrams for Customized products

Connection diagram, 650 series 2.2 IEC 1MRK006501-AG

Connection diagram, 650 series 2.2 ANSI 1MRK006502-AG

Transformer protection RET650 807


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
808
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

Section 22 Inverse time characteristics


22.1 Application M16686-3 v5

In order to assure time selectivity between different overcurrent protections at different points in the
network different time delays for the different protections are normally used. The simplest way to do
this is to use definite time-lag. In more sophisticated applications current dependent time
characteristics are used. Both alternatives are shown in a simple application with three overcurrent
protections operating in series.

I> I> I>


xx05000129.vsd
IEC05000129 V1 EN-US

Figure 447: Three overcurrent protections operating in series

Stage 3

Time
Stage 2 Stage 2

Stage 1 Stage 1 Stage 1

Fault point
position

en05000130.vsd
IEC05000130 V1 EN-US

Figure 448: Definite time overcurrent characteristics

Time

Fault point
position

en05000131.vsd
IEC05000131 V1 EN-US

Figure 449: Inverse time overcurrent characteristics with inst. function


The inverse time characteristic makes it possible to minimize the fault clearance time and still assure
the selectivity between protections.

Transformer protection RET650 809


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

To assure selectivity between protections there must be a time margin between the operation time of
the protections. This required time margin is dependent of following factors, in a simple case with two
protections in series:

• Difference between pickup time of the protections to be co-ordinated


• Opening time of the breaker closest to the studied fault
• Reset times of the protections
• Margin dependent of the time delay inaccuracy of the protections

Assume we have the following network case.

A1 B1
Feeder

I> I>

Time axis

t=0 t=t1 t=t2 t=t3

en05000132.vsd
IEC05000132 V1 EN-US

Figure 450: Selectivity steps for a fault on feeder B1

where:
t=0 is The fault occurs
t=t1 is Protection B1 trips
t=t2 is Breaker at B1 opens
t=t3 is Protection A1 resets

In the case protection B1 shall operate without any intentional delay (instantaneous). When the fault
occurs the protections start to detect the fault current. After the time t1 the protection B1 send a trip
signal to the circuit breaker. The protection A1 starts its delay timer at the same time, with some
deviation in time due to differences between the two protections. There is a possibility that A1 will
start before the trip is sent to the B1 circuit breaker. At the time t2 the circuit breaker B1 has opened
its primary contacts and thus the fault current is interrupted. The breaker time (t2 - t1) can differ
between different faults. The maximum opening time can be given from manuals and test protocols.
Still at t2 the timer of protection A1 is active. At time t3 the protection A1 is reset, that is the timer is
stopped.

In most applications it is required that the times shall reset as fast as possible when the current fed to
the protection drops below the set current level, the reset time shall be minimized. In some
applications it is however beneficial to have some type of delayed reset time of the overcurrent
function. This can be the case in the following applications:

• If there is a risk of intermittent faults. If the current IED, close to the faults, starts and resets
there is a risk of unselective trip from other protections in the system.
• Delayed resetting could give accelerated fault clearance in case of automatic reclosing to a
permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for other protection
functions. It can often be valuable to have a reset delay to assure the release function.

810 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

22.2 Principle of operation IP15777-1 v2

22.2.1 Mode of operation M16687-3 v8

The function can operate in a definite time-lag mode or in a current definite inverse time mode. For
the inverse time characteristic both ANSI and IEC based standard curves are available. Also
programmable curve types are supported via the component inputs: p, A, B, C pr, tr, and cr.

Different characteristics for reset delay can also be chosen.

If current in any phase exceeds the set start current value (here internal signal startValue), a timer,
according to the selected operating mode, is started. The component always uses the maximum of
the three phase current values as the current level used in timing calculations.

In case of definite time-lag mode the timer will run constantly until the time is reached or until the
current drops below the reset value (start value minus the hysteresis) and the reset time has
elapsed.

For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are chosen.

The general expression for inverse time curves is according to equation 127.

æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN-US (Equation 127)

where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.

For inverse time characteristics a time will be initiated when the current reaches the set start level.
From the general expression of the characteristic the following can be seen:

ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN-US (Equation 128)

where:
top is the operating time of the protection

The time elapsed to the moment of trip is reached when the integral fulfils according to equation 129,
in addition to the constant time delay:

t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø
EQUATION1191 V1 EN-US (Equation 129)

Transformer protection RET650 811


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

For the numerical protection the sum below must fulfil the equation for trip.

æ æ i( j ) ö p
n ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN-US (Equation 130)

where:
j=1 is the first protection execution cycle when a fault has been detected, that
is, when

i
>1
in >
EQUATION1193 V1 EN-US

Dt is the time interval between two consecutive executions of the protection


algorithm,
n is the number of the execution of the algorithm when the trip time equation
is fulfilled, that is, when a trip is given and
i (j) is the fault current at time j

For inverse time operation, the inverse time characteristic is selectable. Both the IEC and ANSI/IEEE
standardized inverse time characteristics are supported.

For the IEC curves there is also a setting of the minimum time-lag of operation, see figure 451.

Operate
time

tMin

Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN-US

Figure 451: Minimum time-lag operation for the IEC curves


In order to fully comply with IEC curves definition setting parameter tMin shall be set to the value
which is equal to the operating time of the selected IEC inverse time curve for measured current of
twenty times the set current start value. Note that the operating time value is dependent on the
selected setting value for time multiplier k.

In addition to the ANSI and IEC standardized characteristics, there are also two additional inverse
curves available; the RI curve and the RD curve.

812 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

The RI inverse time curve emulates the characteristic of the electromechanical ASEA relay RI. The
curve is described by equation 131:

æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN-US (Equation 131)

where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current

The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection RXIDG. The
curve enables a high degree of selectivity required for sensitive residual earth-fault current
protection, with ability to detect high-resistive earth faults. The curve is described by equation 132:

æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN-US (Equation 132)

where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current

If the curve type programmable is chosen, the user can make a tailor made inverse time curve
according to the general equation 133.

æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1196 V1 EN-US (Equation 133)

Also the reset time of the delayed function can be controlled. There is the possibility to choose
between three different reset time-lags.

• Instantaneous Reset
• IEC Reset
• ANSI Reset.

If instantaneous reset is chosen the timer will be reset directly when the current drops below the set
start current level minus the hysteresis.

If IEC reset is chosen the timer will be reset after a set constant time when the current drops below
the set start current level minus the hysteresis.

If ANSI reset time is chosen the reset time will be dependent of the current after fault clearance
(when the current drops below the start current level minus the hysteresis). The timer will reset
according to equation 134.

Transformer protection RET650 813


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
2

çç ÷ -1 ÷
è è in > ø ø
EQUATION1197 V2 EN-US (Equation 134)

where:
The set value tr is the reset time in case of zero current after fault clearance.

The possibility of choice of reset characteristics is to some extent dependent of the choice of time
delay characteristic.

For the definite time delay characteristics the possible reset time settings are instantaneous and IEC
constant time reset.

For ANSI inverse time delay characteristics all three types of reset time characteristics are available;
instantaneous, IEC constant time reset and ANSI current dependent reset time.

For IEC inverse time delay characteristics the possible delay time settings are instantaneous and IEC
set constant time reset).

For the programmable inverse time delay characteristics all three types of reset time characteristics
are available; instantaneous, IEC constant time reset and ANSI current dependent reset time. If the
current dependent type is used settings pr, tr and cr must be given, see equation 135:

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
pr

çç ÷ - cr ÷
è è in > ø ø
EQUATION1198 V2 EN-US (Equation 135)

For RI and RD inverse time delay characteristics the possible delay time settings are instantaneous
and IEC constant time reset.
GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4

When inverse time overcurrent characteristic is selected, the operate time of the stage
will be the sum of the inverse time delay and the set definite time delay. Thus, if only the
inverse time delay is required, it is important to set the definite time delay for that stage to
zero.

814 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

22.3 Inverse characteristics IP15797-1 v3

M12388-1 v25

Table 751: ANSI Inverse time characteristics

Function Range or value Accuracy


Operating characteristic: 0.01 ≤ k ≤ 15.00 ANSI/IEEE C37.112 ,
1.2 x Iset ±7.0% or ±80 ms
whichever is greater
 A 
t = P + B⋅k 0.01 ≤ k ≤ 15.00 ANSI/IEEE C37.112 ,
(
 I −1 
 ) 1.5 x Iset ≤ I ≤ 20 x Iset ±3.0% or ±50 ms
EQUATION1249-SMALL V3 EN-US
whichever is greater
Operate time for Iset = 10%, 195%, 400%
of IBase (for all curves)
Reset characteristic for ANSI curves: 0.01 ≤ k ≤ 15.00 ANSI/IEEE C37.112 ,
0 x Iset - 0.8 x Iset ±8.0% or ±350 ms
tr whichever is greater
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset
Reset time for Iset = 10%, 195%, 400% of
IBase
Definite reset timer (0.000 - 60.000) s ANSI/IEEE C37.112 ,
0 x Iset - 0.8 x Iset ±2.0% or ±40 ms
whichever is greater
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1
ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

Table 752: IEC Inverse time characteristics

Function Range or value Accuracy


Operating characteristic: 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±7.0%
1.2 x Iset or ±80 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷ 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±3.0%
è ø 1.5 x Iset ≤ I ≤ 20 x Iset or ±50 ms whichever is
EQUATION1251-SMALL V1 EN-US greater
Operate time for Iset = 10%, 195%, 400%
of IBase (for all curves)
IEC Normal Inverse A=0.14, P=0.02
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Table continues on next page

Transformer protection RET650 815


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

Function Range or value Accuracy


Programmable characteristic 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±7.0%
Operate characteristic: 1.2 x Iset or ±80 ms whichever is
greater*
æ A ö 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±3.0%
t = ç P + B÷ × k
ç (I - C ) ÷ 1.5 x Iset ≤ I ≤ 20 x Iset or ±50 ms whichever is
è ø greater*
EQUATION1370-SMALL V1 EN-US

Operate time for Iset = 10%, 195%, 400%


of IBase
Reset characteristic: 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±8.0%
0 x Iset - 0.8 x Iset or ±350 ms whichever is
TR greater*
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset
Reset time for Iset = 10%, 195%, 400% of
IBase
k = (0.01 - 999.00) in steps of 0.01 *Data evaluated at
A = (0.005 - 200.000) in steps of 0.001 default parameter values
B = (0.00 - 20.00) in steps of 0.01
C = (0.1 - 10.0) in steps of 0.1
P = (0.005 - 3.000) in steps of 0.001
TR = (0.005 - 100.000) in steps of 0.001
CR = (0.1 - 10.0) in steps of 0.1
PR = (0.005 - 3.000) in steps of 0.001

The parameter setting Characteristn = Reserved (where, n = 1 - 4) shall not be used,


since this parameter setting is for future use and not implemented yet.

Table 753: RI and RD type inverse time characteristics

Function Range or value Accuracy


RI type inverse characteristic 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±2.0%
1.2 x Iset or ±20 ms whichever is
1 greater
t = ×k
0.236 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±2.0%
0.339 - 1.5 x Iset ≤ I ≤ 20 x Iset or ±20 ms whichever is
I greater
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset
RD type logarithmic inverse characteristic 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±2.0%
1.2 x Iset or ±50 ms whichever is
æ I ö greater
t = 5.8 - ç 1.35 × In ÷
è k ø 0.01 ≤ k ≤ 15.00 IEC 60255-151, ±2.0%
EQUATION1138-SMALL V1 EN-US 1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever is
greater
I = Imeasured/Iset

816 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v6

Table 754: ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection

Function Range or value Accuracy


Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 ,
1.5 x Iset ≤ I ≤ 20 x Iset ±5.0% or ±160 ms
whichever is greater
 A 
t = P + B⋅k
 (
 I −1 
 )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1
ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

Table 755: IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection

Function Range or value Accuracy


Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever is
æ A ö greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset
IEC Normal Inverse A=0.14, P=0.02
IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-2.00) in steps of 0.01
Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷ TR=(0.005-100.000) in steps of 0.001
è ø CR=(0.1-10.0) in steps of 0.1
EQUATION1370-SMALL V1 EN-US
PR=(0.005-3.000) in steps of 0.001
Reset characteristic:

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset

Transformer protection RET650 817


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

The parameter setting TimeChar = Reserved shall not be used, since this parameter
setting is for future use and not implemented yet.

Table 756: RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power
protection

Function Range or value Accuracy


RI type inverse characteristic 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever is
1 greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset
RD type logarithmic inverse characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US

I = Imeasured/Iset

SEMOD116978-2 v11

Table 757: Inverse time characteristics for overvoltage protection

Function Range or value Accuracy


Type A curve: k = (0.05-1.10) in steps of 0.01

k
t =
æU -U >ö
ç ÷
è U > ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US

Type C curve: k = (0.05-1.10) in steps of 0.01

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U > ø
IECEQUATION2421 V1 EN-US

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
k×A B = (0.50-100.00) in steps of 0.01
t = +D C = (0.0-1.0) in steps of 0.1
P
æB × U -U > ö D = (0.000-60.000) in steps of 0.001
ç -C÷
P = (0.000-3.000) in steps of 0.001
è U > ø
EQUATION1439-SMALL V1 EN-US

818 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

Table 758: Inverse time characteristics for undervoltage protection

Function Range or value Accuracy


Type A curve: k = (0.05-1.10) in steps of 0.01

k
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN-US

U< = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US

U< = Uset
U = Umeasured
Programmable curve: k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of 0.001
é ù B = (0.50-100.00) in steps of 0.01
ê k×A
ú C = (0.0-1.0) in steps of 0.1
t =ê ú+D D = (0.000-60.000) in steps of 0.001
ê æ U < -U ö
P
ú P = (0.000-3.000) in steps of 0.001
êçB × -C÷ ú
ëè U < ø û
EQUATION1433-SMALL V1 EN-US

U< = Uset
U = Umeasured

Transformer protection RET650 819


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

Table 759: Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy


Type A curve: k = (0.05-1.10) in steps of 0.01

k
t =
æU -U >ö
ç ÷
è U > ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured
Type B curve: k = (0.05-1.10) in steps of 0.01

k ⋅ 480
t = + 0.035
2.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1437-SMALL V2 EN-US

Type C curve: k = (0.05-1.10) in steps of 0.01

k ⋅ 480
t = + 0.035
3.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1438-SMALL V2 EN-US

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of 0.001
k×A B = (0.50-100.00) in steps of 0.01
t = +D C = (0.0-1.0) in steps of 0.1
P
æB × U - U > ö D = (0.000-60.000) in steps of 0.001
ç -C÷
P = (0.000-3.000) in steps of 0.001
è U > ø
EQUATION1439-SMALL V1 EN-US

820 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

SEMOD118114-4 v5

A070750 V2 EN-US

Figure 452: ANSI Extremely inverse time characteristics

Transformer protection RET650 821


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070751 V2 EN-US

Figure 453: ANSI Very inverse time characteristics

822 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070752 V2 EN-US

Figure 454: ANSI Normal inverse time characteristics

Transformer protection RET650 823


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070753 V2 EN-US

Figure 455: ANSI Moderately inverse time characteristics

824 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070817 V2 EN-US

Figure 456: Long time extremely inverse time characteristics

Transformer protection RET650 825


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070818 V2 EN-US

Figure 457: Long time very inverse time characteristics

826 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070819 V2 EN-US

Figure 458: Long time inverse time characteristics

Transformer protection RET650 827


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070820 V2 EN-US

Figure 459: IEC Normal inverse time characteristics

828 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070821 V2 EN-US

Figure 460: IEC Very inverse time characteristics

Transformer protection RET650 829


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070822 V2 EN-US

Figure 461: IEC Inverse time characteristics

830 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070823 V2 EN-US

Figure 462: IEC Extremely inverse time characteristics

Transformer protection RET650 831


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070824 V2 EN-US

Figure 463: IEC Short time inverse time characteristics

832 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070825 V2 EN-US

Figure 464: IEC Long time inverse time characteristics

Transformer protection RET650 833


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

A070826 V2 EN-US

Figure 465: RI-type inverse time characteristics

834 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

A070827 V2 EN-US

Figure 466: RD-type inverse time characteristics

Transformer protection RET650 835


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN-US

Figure 467: Inverse curve A characteristic of overvoltage protection

836 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN-US

Figure 468: Inverse curve B characteristic of overvoltage protection

Transformer protection RET650 837


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN-US

Figure 469: Inverse curve C characteristic of overvoltage protection

838 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 22
Inverse time characteristics

GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN-US

Figure 470: Inverse curve A characteristic of undervoltage protection

Transformer protection RET650 839


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 22 1MRK504170-UEN Rev. J
Inverse time characteristics

GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN-US

Figure 471: Inverse curve B characteristic of undervoltage protection

840 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 23
Glossary

Section 23 Glossary M14893-1 v20

AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AP Access Point

AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fiber optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs
CAM Central Account Management
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and Telephony. A United
Nations-sponsored standards body within the International
Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second

Transformer protection RET650 841


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 23 1MRK504170-UEN Rev. J
Glossary

CMT Communication Management tool in PCM600


CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves two twisted pairs
making it possible to transmit information in both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchange format for
Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC
60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four twisted pairs,
two of which are used for transmitting data in both directions and two for
transmitting clock signals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The US developer of the
TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
ECT Ethernet configuration tool
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility

842 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 23
Glossary

EMF Electromotive force


EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fiber connector
FAN Fault number
FIPS Federal Information Processing Standards
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech, data and
protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of up to seven
duplex channels of digital data over optical fibers
FPN Flexible product naming
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines used by local telephone
companies. Can be transported over balanced and unbalanced lines
GCM Communication interface module with carrier of GPS receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLC standard
HFBR connector type Plastic fiber connector
HLV circuit Hazardous Live Voltage according to IEC60255-27
HMI Human-machine interface
HSAR High speed autoreclosing
HSR High-availability Seamless Redundancy
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for
protective current transformers for transient performance
IEC 60870-5-103 Communication standard for protection equipment. A serial master/slave
protocol for point-to-point communication
IEC 61850 Substation automation communication standard

Transformer protection RET650 843


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 23 1MRK504170-UEN Rev. J
Glossary

IEC 61850–8–1 Communication protocol standard


IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-pair or
optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. References the
CMC (IEEE P1386, also known as Common Mezzanine Card) standard for
the mechanics and the PCI specifications from the PCI SIG (Special
Interest Group) for the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber Security
Capabilities
IED Intelligent electronic device
IET600 Integrated engineering tool
I-GIS Intelligent gas-insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available in the IED,
they are referred to as instances of that function. One instance of a function
is identical to another of the same kind but has a different number in the
IED user interfaces. The word "instance" is sometimes defined as an item of
information that is representative of a type. In the same way an instance of
a function in the IED is representative of a type of function.
IP 1. Internet protocol. The network layer for the TCP/IP protocol suite widely
used on Ethernet networks. IP is a connectionless, best-effort packet-
switching protocol. It provides packet routing, fragmentation and
reassembly through the data link layer.
2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level 20
IP 40 Ingression protection, according to IEC 60529, level 40
IP 54 Ingression protection, according to IEC 60529, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDAPS Lightweight Directory Access Protocol
LDCM Line data communication module
LDD Local detection device
LED Light-emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MPM Main processing module
MVAL Value of measurement

844 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 23
Glossary

MVB Multifunction vehicle bus. Standardized serial bus originally developed for
use in trains.
NCC National Control Centre
NOF Number of grid faults
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than start/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a fault condition. For
example, a distance relay is overreaching when the impedance presented
to it is smaller than the apparent impedance to the fault applied to the
balance point, that is, the set reach. The relay “sees” the fault but perhaps it
should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PELV circuit Protected Extra-Low Voltage circuit type according to IEC60255-27
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near proximity to the
measured and/or controlled components
PRP Parallel redundancy protocol
PSM Power supply module
PST Parameter setting tool within PCM600
PTP Precision time protocol
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital data in point-to-
point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close

Transformer protection RET650 845


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 23 1MRK504170-UEN Rev. J
Glossary

SCL Short circuit location


SCS Station control system
SCADA Supervision, control and data acquisition
SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SELV circuit Safety Extra-Low Voltage circuit type according to IEC60255-27
SFP Small form-factor pluggable (abbreviation)
Optical Ethernet port (explanation)

SLM Serial communication module.


SMA connector Subminiature version A, A threaded connector with constant impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize computer clocks on
local area networks. This reduces the requirement to have accurate
hardware clocks in every embedded system in a network. Each embedded
node can instead synchronize with a remote clock, providing the required
accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocol for
point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport layer protocol
used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de facto standard
Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP was developed
by DARPA for Internet working and encompasses both network layer and
transport layer protocols. While TCP and IP specify two protocols at specific
protocol layers, TCP/IP is often used to refer to the entire US Department of
Defense protocol suite based upon these, including Telnet, FTP, UDP and
RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedance version of a
BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and voltages taken
from the process into levels suitable for further signal processing.
TYP Type identification

846 Transformer protection RET650


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK504170-UEN Rev. J Section 23
Glossary

UMT User management tool


Underreach A term used to describe how the relay behaves during a fault condition. For
example, a distance relay is underreaching when the impedance presented
to it is greater than the apparent impedance to the fault applied to the
balance point, that is, the set reach. The relay does not “see” the fault but
perhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale, maintained by the
Bureau International des Poids et Mesures (BIPM), which forms the basis of
a coordinated dissemination of standard frequencies and time signals. UTC
is derived from International Atomic Time (TAI) by the addition of a whole
number of "leap seconds" to synchronize it with Universal Time 1 (UT1),
thus allowing for the eccentricity of the Earth's orbit, the rotational axis tilt
(23.5 degrees), but still showing the Earth's irregular rotation, on which UT1
is based. The Coordinated Universal Time is expressed using a 24-hour
clock, and uses the Gregorian calendar. It is used for aeroplane and ship
navigation, where it is also sometimes known by the military name, "Zulu
time." "Zulu" in the phonetic alphabet stands for "Z", which stands for
longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
3IO Three times zero-sequence current.Often referred to as the residual or the
earth-fault current
3UO Three times the zero sequence voltage. Often referred to as the residual
voltage or the neutral point voltage

Transformer protection RET650 847


Technical manual
© 2017 - 2023 Hitachi Energy. All rights reserved
848
849
Hitachi Energy Sweden AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 10 738 00 00

https://hitachienergy.com/protection-control Scan this QR code to visit our website


1MRK504170-UEN

© 2017 - 2023 Hitachi Energy.


All rights reserved

You might also like