DMP Programming Manual
DMP Programming Manual
When using the XR150INT/XR550INT Series panel for any listing organization’s approved methods, refer
to the Compliance Listing Guide (LT-1330INT). This document outlines the installation and programming
requirements of all applications for which XR150INT/XR550INT Series control panels are approved.
893A ......................................................................................... 9
INITIALIZATION......................................5
Alarm Switch ......................................................................... 9
Initialization ........................................................................... 5
Duplicate Alarms ................................................................. 9
Clear All Memory ................................................................. 5
Alarm Reports ...................................................................... 9
Clear All Codes..................................................................... 5
Supervisory/Trouble Reports ......................................... 9
Clear All Schedules............................................................. 5
Opening/Closing and User Reports ............................. 10
Clear Display Events Memory......................................... 5
Door Access Report ........................................................... 10
Clear Zone Information ..................................................... 5
Panic Test (Network Only)............................................... 10
Clear Area Information...................................................... 5
Send Communication Trouble ........................................ 10
Clear Output Information................................................. 5
Send Path Information ...................................................... 10
Clear Communication and Remote Options............. 5
WPS .......................................................................................... 11
COMMUNICATION ..................................6
List............................................................................................. 11
Communication .................................................................... 6
Manual ..................................................................................... 11
Account Number ................................................................. 6
Test ............................................................................................ 12
Transmit Delay ...................................................................... 6
Wireless Security Type ...................................................... 12
Communication Path ......................................................... 6
Wireless Network Key ....................................................... 12
Communication Type ......................................................... 6
IPV6 .......................................................................................... 12
Passphrase (XR550INT with Encryption Only) ....... 13 Zone 3 REX Strike Time .................................................... 20
Late To Open......................................................................... 28
BELL OPTIONS........................................36
Early To Close ....................................................................... 28
Bell Options ........................................................................... 36
Style .......................................................................................... 54
AREA INFORMATION .............................47
Expander Serial Number .................................................. 54
Area Information ................................................................. 47
Next Zone............................................................................... 54
Exit Delay ............................................................................... 47
Wireless ................................................................................... 54
Closing Check ....................................................................... 47
Serial Number Entry ........................................................... 55
Closing Code ......................................................................... 47
Contact .................................................................................... 55
Any Bypass ............................................................................ 47
Supervision Time ................................................................. 55
Area Schedules .................................................................... 47
LED Operation ...................................................................... 55
Early Morning Ambush (Network Panels Only) ...... 48
Disarm/Disable..................................................................... 55
Area Number......................................................................... 48
PIR Pulse Count ................................................................... 56
All/Perimeter Programming............................................ 48
PIR Sensitivity....................................................................... 56
Home/Sleep/Away Programming................................. 48
Pet Immunity ......................................................................... 56
Area Name ............................................................................. 48
Next Zone ............................................................................... 56
Account Number ................................................................. 48
Alarm Action ......................................................................... 56
Opening/Closing Reports ................................................ 48
Disarmed Open .................................................................... 56
Automatic Arming .............................................................. 49
Report to Transmit .............................................................. 56
Bad Zones .............................................................................. 49
Output Number.................................................................... 57
Automatic Disarming ......................................................... 49
Output Action ....................................................................... 57
Burglary Bell Output .......................................................... 49
Disarmed Short, Armed Open, and
Armed Output Number .................................................... 49 Armed Short.......................................................................... 57
Late Output Number.......................................................... 49 Swinger Bypass .................................................................... 57
Report with Account Number for Area ...................... 59 Zone Types ............................................................................ 72
1144INT Series Key Fobs ................................................... 60 Trip Counter For DMP Wireless Check-in Test
(WLS) ....................................................................................... 73
Key Fob User Number ....................................................... 60
Test End Warning ................................................................ 73
Key Fob Serial Number ..................................................... 60
Wireless Check-in and Supervision Denitions ....... 74
Key Fob Supervision Time ............................................... 60
Keypad Speaker Operation ............................................. 74
Number of Key Fob Buttons ........................................... 60
Cross Zoning ......................................................................... 74
Key Fob Button Selection (Four Buttons)................. 60
User Proles .......................................................................... 74
Key Fob Button Selection (Two Buttons) .................. 60
User Proles Record........................................................... 75
Button Action ....................................................................... 61
Zone Type Descriptions .................................................... 75
Button Press Time ............................................................... 61
Common Keypad Messages ............................................ 77
Arm/Disarm Area Selection ............................................ 61
Area Account Number Messages.................................. 78
Output Number.................................................................... 61
FEATURE UPGRADE...............................65
Feature Upgrade ................................................................. 65
Encryption.............................................................................. 65
APPENDIX................................................67
False Alarm Reduction ...................................................... 67
In addition to this guide, you should also read and be familiar with the following documents:
Internal Programmer
The panel contains all of its programming information in an on-board processor and does not require an external
programmer. You can perform all programming tasks through a 32-character DMP alphanumeric keypad set to address
one, or through Dealer Admin, Tech APP, and Remote Link.
GETTING STARTED
Before starting to program the panel, make sure the panel is properly grounded and AC and battery power is applied
to the appropriate panel terminals. All wiring connections and grounding instructions are detailed in the XR150INT/
XR550INT Series Installation Guide (LT-1233INT).
An XR550INT panel with encryption communicates using 128-bit or 256-bit AES encryption. If you currently have an
XR550INT panel with network installed, you may purchase a separate feature key to activate encrypted communications
using the Feature Upgrade process. Encrypted communication cannot be enabled on a standard XR550INT panel. For
more information on the Feature Upgrade process see Section 21 in this document.
Programming Item Section in This Manual Programming Item Section in This Manual
Initialization 2 Output Information 12
Communication 3 Output Groups 13
Network Options 4 Menu Display 14
Device Setup 6 PC Log Reports 16
Remote Options 7 Area Information 17
System Reports 8 Zone Information 18
System Options 9 Stop 19
Bell Options 10 Set Lockout Code 20
Output Options 11 Feature Upgrade 21
To choose a section for programming, press any select key or area when the keypad displays the name of that section.
Sections 2 through 21 contain detailed instructions for each programming step.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press CMD to advance
through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any select key or area. The
keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code and press CMD. The keypad displays
ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to 5 digit code a second time and press CMD. The keypad
displays CODE CHANGED. The panel does not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number. Write the Lockout Code number down and keep it
in a secure place with access limited to authorized persons only. Lost Lockout Codes require the panel to be sent back to
DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set Lockout Code command.
RESET TIMEOUT
The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the panel. After 30
minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad displays: RESET PANEL. You must
reset the panel and enter the program code then begin programming within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30 minutes, the panel
terminates programming. All data entered up to that time is not saved unless you run the Stop routine.
Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM” to save all
programming changes entered.
POWER UP
When the panel is powered up after an AC power failure, any zone transitions are not recognized for 60 seconds. Normal
zone processing resumes at the end of the 60 seconds.
SPECIAL KEYS
The following special keys/areas are common to all DMP keypads.
CMD is also used to enter information into the panel’s memory such as phone numbers or zone names. Press CMD after
entering information.
During programming, the select keys or areas also allow you to change information currently in panel memory by
pressing the appropriate select key or area under or on the display. You then enter the new information using the keypad
data entry digit keys.
When there are more than four response options available, press CMD to display the remaining options. Pressing the
Back Arrow key allows you to review the previous four choices.
The select keys or areas are also used for choosing a section from the programming menu. Press any select key or touch
the select area when the programming section name you want displays.
On Wireless, Thinline and Aqualite keypads, when instructed to press the rst select key, press the far left select key; the
second select key is the second from the left; third select key is second from the right; and the fourth select key is the far
right key.
On Graphic Touchscreen Keypads, when instructed to press the rst select key, touch select area 1; the second select key
touch select area 2; third select key touch select area 3; and the fourth select key touch select area 4.
Key Number Select Key or Select Key or Select Key Select Key or
Area 1 Area 2 or Area 3 Area 4
1 A B C (
2 D E F )
3 G H I !
4 J K L ?
5 M N O /
6 P Q R &
7 S T U @
8 V W X ,
9 Y Z space _
0 - . * #
Press the number(s) on the keypad you want to enter as the new number for that option. It is not necessary to enter
numbers with leading zeros. The panel automatically right justies the number when you press CMD.
To change a programming option that requires a NO or YES response, press the select key or touch the select area for
the response not selected.
For example, if the current option is selected as YES and you want to change it to NO, on Thinline or Aqualite keypads
press the third select key. On Graphic Touchscreen keypads touch select area 3. The display changes to NO. Press CMD
to display the next option.
MULTIPLE DISPLAYS
For many programming and user options, such as Area selections, Menu Displays, and Status Lists, there are several
displays containing programming. For example, when programming Menu Displays, keypads 1 through 16 display on two
separate displays. First, keypads 1 through 8 display. Press CMD to display keypads 9 through 16. This same scheme is
used for areas 1 through 32. Areas not pre-programmed at installation to display at this keypad cannot be viewed.
ASTERISKS IN PROGRAMMING
Asterisks display next to a programming option that is already selected. As shown in the example, options that are
selected to display the current programming selection have an asterisk next to the number. Those that are not selected
simply display the number. In the Devices example, keypads 3, 8, 9, and 15 are not selected. In the Areas example, areas
3, 8, 9, 15, 19, 23, 25, and 31 are not selected. In both examples the numbers with asterisks are selected.
To select or deselect a number, simply enter the number using the digit keys on the keypad. This same scheme is used
when viewing the panel armed status and other programming and operational functions. Remember to press CMD to
display the rest of the device or area numbers.
COMPLIANCE INSTRUCTIONS
This product incorporates eld-programmable software. Refer to the XR150INT/XR550INT Compliance Listing Guide
(LT-1330INT) for additional compliance information.
Clear Wi-Fi
WIFI? NO YES NO leaves existing Wi-Fi programming intact.
YES reset Wi-Fi programming to factory defaults.
Account Number
ACCOUNT NO: 12345 The Account Number is a 1 to 5 digit number used to identify which panel is sending a
message. Enter the account number sent to the SCS-1R or SCS-VR Receiver. The default is
12345.
The range of valid account numbers for a panel is 1 to 65535. For accounts of four digits or
less, do not enter leading zeros.
Transmit Delay
XMIT DELAY: 30 Enter the number of seconds (15 to 45) the panel waits before sending burglary zone
(Night, Day, or Exit) reports to the receiver. Other zone type reports are sent immediately.
Alarm bells and relay outputs are not delayed during this period. Program Burglary
Outputs for pulsed or steady, and set Abort Reports to YES if Opening and Closing reports
are not being sent. Enter 0 (zero) to disable this function. The default is 30.
If the area where the alarm occurred is disarmed during the Transmit Delay time, only an
Abort Report (S45) message is sent to the receiver. If the area where the alarm occurred
is disarmed after the alarm message is sent to the receiver but before the Bell Cuto
time expires even if the alarm was silenced, an Alarm Cancelled (S49) message is sent.
Otherwise the alarm is sent at the end of the delay.
Communication Path
PATH: - Up to eight communication paths may be programmed. Each path is designated as a
primary or backup communication route. Path 1 is always Primary but other paths may be
programmed as additional primary or backup.
Each primary path establishes a new path group. A path group is made up of the primary
path and its subsequent backup paths. Typical communication takes place on the primary
path with backup paths being used only when the primary path fails or when the backup
path is programmed to duplicate messages. There is no option to backup path 8.
Communication Type
COMM TYPE: NONE Species the communication method the panel uses on this path to report system events
to DMP SCS-1R or SCS-VR Receivers. Default is NONE for Path 1-8.
NONE - For local systems. Selecting NONE ends communication programming.
DD - Digital Dialer communications to a DMP SCS-1R Receiver.
NONE DD NET CID
NET - Network communication using the panel onboard network connection. The DMP
Network/Output reporting format is transmitted over a data network to the SCS-1R or
SCS-VR Receiver.
CID - This option allows the panel to communicate to DMP and non-DMP receivers using
the Contact ID format.
CELL - This option allows communication over the cellular network using the 263LTE
CELL WIFI Cellular Communicator.
WIFI - Network communication to DMP Model SCS-1R or SCS-VR Receivers.
Test Frequency
TEST FREQ: 1 DY Test Frequency determines the frequency of the test report. Enter a number from 1 to 60
and select DY (Day) or HR (Hour) by pressing the far right select key or area. Default is 1
Day.
Test Day
TEST DAY: SUN Use this option to set the day of the Test Report. This option appears only when Test Report
is Yes, Test Frequency is Day and a multiple of seven. Press CMD to display the rst four
days of the week. Press CMD to display the last three days. Select the day of the week to
send the test report. Default is SUNDAY.
Check In
TEST DAY: SUN This option displays if the COMM TYPE is NET, WIFI, or CELL. Check-in reports are a
method of supervising the panel for communication with the receiver. For NET the default
is YES. For CELL the default is YES.
CHECKIN Select RND (Random) for the panel to check-in at random times from 6 to 60 minutes when
NO YES RND ADPT all areas are disarmed. If any area is armed a check-in is sent every 6 minutes.
Select ADPT (Adaptive) for a backup path to adapt to the check-in programming from
this groups primary path if the primary path becomes unavailable. Check-in programming
includes Check-in and Fail Time.
Select ADP3 (Adaptive 3) for a backup path to adapt using a 3 minute Check-in and Fail
CHECKIN
Time if the primary path becomes unavailable. This option also indicates a Communication
ADP3
Trouble (S10) if the cell tower is unavailable for 3 minutes.
When YES is selected, enter the number of minutes between check-in reports, from 2 to
CHECKIN MINS: 200 240 for NET or 3 to 240 for CELL, when the panel is armed or disarmed. For CELL the
default is 0. For NET the default is 200.
Fail Time
FAIL MINS: 240 This option displays if CHECKIN is set to YES. Entering a FAIL TIME allows the receiver to
miss multiple check-ins before logging that the panel is missing. The maximum fail time is
240 minutes. For example, if CHECKIN is 10 and FAIL TIME is 30, the receiver only indicates
a Panel Not Responding after 30 minutes. The FAIL TIME must be equal to or greater than
the CHECKIN time. Default is equal to CHECKIN for CELL. Default is 240 for NET.
RECEIVER IP Receiver IP
000.000.000 This option displays if the Communication Type is NET or CELL. Enter the Receiver IP
address where the panel sends network messages. The Receiver IP Address must be
unique and cannot be duplicated on the network. Enter all 12 digits and leave out the
periods. For example, enter IP address 192.168.0.250 as 192168000250. The periods
display automatically. If IPV6 is selected the receiver IP will need to be an IPV6 address. If
changing from IPV6 YES to IPV6 NO, you will need to modify their IP address to IPV4.
Advanced Programming
ADVANCED? NO YES Select YES to enter the Advanced Programming menu for the communication
path currently being programmed. Selecting NO ends programming of the current
communication path and takes users back to the Communication Path option to program a
secondary path.
APN APN
SECURECOM400 Enter the rst APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two lines
of 16 characters to equal 32 characters. Default is set to SECURECOM400.
Protocol
PROTOCOL: TCP This option displays only if Communication Type is NET.
Select TCP to communicate over the network using TCP protocol. Select UDP to
communicate using UDP protocol. Default is TCP.
Retry Seconds
RETRY SECONDS: 6 This option displays only when Communication type is NET.
Enter the number of seconds (between 6 and 15) the panel should wait before retrying to
send a message to the receiver if an acknowledgment was not received. The panel retries
as many times as possible for a period of one minute before sending a network trouble
message. The default Retry Time is 6 seconds.
893A
893A: NO YES This option displays when the Communication Type is DD or CID.
The 893A option allows reports to be sent to the receiver on a second DD line using the
893A module. Default is NO.
When using an 893A, Test Report messages (S07 Automatic Recall Test or S88
Unrestored System Recall Test) are sent to the receiver at the frequency programmed in
Test Frequency, alternating between the rst and second phone line.
Alarm Switch
ALARM SWITCH: 1 This option displays only if using the DD or CID Communication Types.
Enter the number of attempts to send an alarm message before switching to the next path.
Range is from 1 to 10. All non-alarm messages are sent for 10 attempts on the dialer before
a switch is initiated. If the path immediately following this channel is not a backup path, this
option has no eect. Default is 1.
Duplicate Alarms
DUPLICATE ALARMS
NO YES This option displays for BACKUP paths. If Yes is selected, the current backup path
duplicates all alarms occurring on its group primary path. Default is NO.
Alarm Reports
ALARM YES This option displays when the Path Type is Primary. All backup paths within the group
follow the same programming for Alarm Reports. Default is YES.
When YES is selected, the following reports are sent to the receiver for all zone types:
Supervisory/Trouble Reports
SPV/TRBL YES This option displays when the Path Type is Primary. All backup paths within the group
follow the same programming for Supervisory/Trouble Reports. Default is YES.
When YES is selected, the following reports are sent for all zone types:
NO YES FIRE • Trouble • Low Battery • Missing • Fault
When FIRE is selected, the following reports are sent for Fire, Fire Verify, and Supervisory
Zones:
• Trouble • Low Battery • Missing • Fault
Serviceman reports are sent regardless of the selection made for Supervisory/Trouble
reports.
When YES is selected, the following reports by user are sent to this receiver.
• Opening • Code changes (including adding, deleting, changing)
• Reset
WPS
SEARCHING When WPS is selected, SEARCHING displays. Press the WPS button on the Wi-Fi network
router to which you are attempting to connect. SEARCHING displays for up to two minutes
or until connected to the WPS enabled router. Refer to the router’s instruction manual for
sending a security key to the XR150INT/XR550INT Series panel.
If the panel fails to connect to the WPS enabled router, WPS FAILED RETRY? NO YES
displays. Press the fourth select key or area to RETRY or press the third select key or area
to display WPS LIST MANUAL.
Manual
WPS LIST MANUAL This option allows you to enter the desired network name using the keypad. When
MANUAL is selected, the current settings display. Press CMD to continue with no change.
WIFI SETUP SecureCom is the default.
ENTER SSID Once the SSID is entered, press CMD and SEARCHING displays.
When an SSID is entered for the rst time or changed, the panel searches for the SSID
entered to ensure communication. The keypad displays SSID FOUND or SSID NOT FOUND.
SSID When the SSID is found, the security type is also detected.
SSID FOUND Enter up to 32 characters for the SSID from the network router to identify the network LAN.
The SSID is blank by default. Use the chart below to enter lowercase or special characters.
Each successive press of the select key or area gives additional options.
Key Number Select Key Select Key Select Key Select Key
or area 1 or area 2 or area 3 or area 4
1 A, a, B, b C, c (, [, {
2 D, d E, e F, f ), ], }
3 G, g H, h I, i !, ^, ~
4 J, j K, k L, l ?, ", |
5 M, m N, n O, o /, \, `
6 P, p Q, q R, r &, $
7 S, s T, t U, u @, %
8 V, v W, w X, x ,=
9 Y, y Z, z space, : _, ;
0 -, + ., ' *, < #, >
SSID If the 763 is unable to connect to the desired network and SSID NOT FOUND displays,
SSID NOT FOUND press CMD to return to the main menu and WPS LIST MANUAL displays. Press CMD again
to display TEST.
DHCP
DHCP NO YES If the panel uses a dynamic IP address select YES. When set to YES, the panel operates
using DHCP and does not use the Local IP Address number. When the DHCP option is set
to NO, the panel uses the IP address entered in Local IP Address. The default value for
DHCP mode is YES.
Device Number
DEVICE NO: - Enter the address of the device you are programming. After you program each option for
the rst device, repeat these programming steps for each additional device. Programmable
devices are KEYPAD, DOOR, FIRE, and EXPANDER. The available addresses are 1 - 16 on
the panel keypad bus, and 500 - 999 on the LX-Bus. The valid range for KEYPAD, FIRE, and
EXPANDER type devices is 1 - 16 on the panel keypad bus. The valid range for DOOR type
devices is 1 - 16 on the panel keypad bus and 501 - 961 on the AX-Bus.
See the AX Bus Addresses and 734INT Zone Numbers chart on the next page. Wireless
keypads and network door controllers are not able to occupy address 1.
AX-Bus Operation for 734INT Access Control Modules
Once a 734INT address has been programmed for the bus, the LX-Bus is automatically
converted from a hardwire zone expansion bus to a hardwire Access Expansion Bus
(AX-Bus) and the bus begins to operate as shown below.
• Each 734INT module provides one door relay and four protection zones to connect
switches such as door and window contacts.
• 16 doors of access can be programmed per AX-Bus to a maximum of eighty (80)
734INT modules. Please see the table below for available addresses.
• Any unused AX-Bus zone numbers may be programmed as wireless zones. Hardwired
zone expansion modules such as the 711, 714, 715-16 and others are incompatible with
bus operation and cannot be used.
• Device Setup programming for AX-Bus address are automatically programmed as a
door type. Device Type, Communication Type and Display Areas are not shown. Only
734INT module programming is shown.
An AX-Bus operation is compatible with 734INT modules and XR550INT Series control
panels. AX-Bus operation is incompatible with XR150INT Series control panels.
Device Name
* UNUSED * A device name must be given to each device in the system. To add a device name, press
any select key or area. The default device name (DEVICE X) displays. Select CMD to
accept the default name or press any select key or area to enter a new name up to 32
alphanumeric characters. Press CMD.
To remove a device from the system, delete the device name by pressing any select key or
area, then press CMD. The panel automatically programs the name as * UNUSED *.
DOOR - The device is an access control device and is either a keypad using door strike
functions or a Wiegand Interface Module. Devices with an address higher than 16 are
VPX
automatically assigned as a DOOR device type.
Private Door
PRIVATE DR NO YES Select YES to assign this address as a private door, which will not be assigned to an access
area. The private door can then be added to a prole. Up to four private doors can be
assigned to an individual prole.
Select NO to not allow a door to be designated as a private door. Default is NO.
DEVICE COMM TYPE DOOR - For wired devices, select KPD BUS for addresses 1-16 or select AX BUS for
NETWORK WLS addresses 501-964. For network devices, select NETWORK.
Serial Number
SERIAL #:XXXXXXXX This option only displays if Device Type is KEYPAD and Device Comm Type is WIRELESS.
Enter the eight-digit serial number found on the wireless keypad.
Access Areas
ACCESS AREAS Press CMD to program Access Areas. To select an area, enter the area number using the
digit keys on the keypad. When an area is selected, an asterisk appears next to the area
number. Enter the number again to deselect the area. Press CMD to display the next set of
areas.
Users must have matching access area numbers assigned to their code to receive a door
access at this device.
For an All/Perimeter, Home/Sleep/Away, or Home/Sleep/Away with Guest system, Access
Areas should be left at factory default settings.
Egress Areas
EGRESS AREAS Press CMD to program Egress Areas. To select an area, enter the area number using the
digit keys on the keypad. When an area is selected, an asterisk appears next to the area
number. Enter the number again to deselect the area. Press CMD to display the next set of
areas.
Use this option to detect Anti-passback violations. Anti-passback requires a user to
properly exit (egress) an area they have previously accessed. If users fail to exit through the
proper card reader location they are not granted access on their next attempt.
Display Areas
DISPLAY AREAS Press CMD to program Display Areas. To select an area, enter the area number using the
keypad digit keys. When an area is selected, an asterisk appears next to the area number.
Enter the number again to deselect the area. Press CMD to display the next set of areas.
Default is all area numbers.
Display Areas allows the panels burglary activities to be segmented so that only specic
area(s) and their associated operation appear at a particular keypad. Area number(s)
selected in this eld aect the way users interact with the system from this particular
device. This allows specic area control from specic keypads, as well as annunciation of
zones assigned to those area(s).
When Display Areas is left defaulted (all areas selected), Menu Display and Status List
items determine whether zone alarms and troubles display at this device, regardless of area
assignment. Also, all system areas may be armed and disarmed from this device.
For an All/Perimeter or Home/Sleep/Away system, Display Areas should be left at factory
default settings.
For Home/Sleep/Away with Guest arming systems, the Display Areas selection determines
which system the keypad arms and disarms. With areas 1, 2 or 3 being the rst areas
selected, the keypad is assigned to the Main system. With area 4, 5 or 6 being the rst
areas selected, the keypad is assigned to the Guest 1 system. With area 7, 8 or 9 being the
rst areas selected, the keypad is assigned to the Guest 2 system (Guest 2 only applies to
XR550INT systems). Keypads can have additional areas assigned for Event Display.
• Arming or Disarming of the area(s) selected from the ARM or DISARM menu
• Door Schedules changes are allowed for devices that have a matching area(s)
as dened in Device Access Areas
• Door On/O Menu operation is allowed for devices that have a matching area(s)
as dened in Device Access Areas
The user actions also require the matching area(s) be programmed in User Prole: Arm/
Disarm area(s).
• Zone Alarms and troubles for burglary (NT, DY, EX, A1, A2) type zones assigned to the
selected area(s)
• Zone Status (normal/fault) of zones that are assigned to the selected area(s)
• Display Events
Strike Time
STRIKE TIME: 5 Enter a door access time, between 1 and 250 seconds, during which a keypad or access
control device relay is activated. Magnetic locks or electric door strikes are connected to
the relay and released for the length of the strike time. Default is 5 seconds.
Enter 0 (zero) to activate the device relay with a toggle action. This allows the user to
activate or deactivate the device relay each time a valid user code is entered. The device
relay is activated or deactivated until a user code is entered again.
Strike Delay
STRIKE DELAY: 0 Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered
or a card read occurs. When a valid code or card read is received, the activation of the
door strike is delayed for the number of minutes programmed. The standard door strike
message is sent to the Central Station receiver. During this delay, all subsequent codes
entered or cards presented to the reader for a door strike are ignored and no record of the
attempt is stored. Enter 0 (zero) to disable. Default is 0 (zero).
Public Door
PUBLIC DR NO YES Select YES to allow the door access relay at this address to be locked whenever the
Lockdown command is issued from the keypad User Menu or remote command.
Select NO to not allow the door access relay at this address to be released. Default is NO.
Output Group
OUT GROUP NO YES Select YES to allow the output group (relays) assigned to the user prole to turn ON when
the device relay is activated for the programmed strike time. Default is NO. See the User
Proles section in the Appendix of this document for more information about proles.
Schedule Override
OVERRIDE NO YES Use this option to allow door ON/OFF schedules to be overridden by the armed condition
of the system. Selecting YES causes the on time for a door schedule to be ignored when
all areas assigned to Access Areas for this device are armed. Should any area become
disarmed after the door schedule on time, the device output turns on. A door output which
is on during a disarmed period automatically turns o when all access areas assigned
to the device become armed, even if the scheduled o time has not been reached. This
feature can be used to keep doors locked when a factory opens late, or is forced to close
early, due to a snow storm or other cause.
Select NO to allow door schedules to operate independent of system armed status.
When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS, the
door schedule for that device does not work. Either set OVERRIDE to NO or enter an area
number in ACCESS AREAS.
Remote Key
REMOTE KEY This option allows you to enter a code of up to 16 characters. Remote Link™ and Dealer
Admin must give the correct key to the panel before being allowed any remote functions.
All panels are shipped from the factory with the key preset as blank. This can be an optional
or required option
To enter a remote key or change the current one, press a select key or area and enter any
combination of up to 16 digits. Press CMD. The current key displays as asterisks.
PC Modem
PC MODEM NO YES YES allows the panel to answer the telco link and connect with Remote Link™ through the
PC Modem at 2400 baud. NO disables PC Modem communication.
DMP remote service is provided on a read only basis: DMP technicians can look at the
system programming and make suggestions only. Alterations can only be accomplished by
installing company service personnel.
NETWORK PROG
Network Programming Port
PORT: 2001 Enter the programming port number. The programming port identies the port used to
communicate messages to the panel. The default Programming Port setting is 2001.
Entré Connection
ENTRE
CONNECTION: NONE This option displays if the panel has network or cellular capability. Select NET to allow a
dedicated network connection with Entré. Options are NONE, NET, or CELL. Default is
NONE.
Entré IP Address
ENTRE IP This option displays only if NET is chosen for the Entré connection. Enter the Entré IP
address where the panel sends network messages. The Entré IP Address must be unique
and cannot be duplicated on the network. Enter all 12 digits and leave out the periods.
For example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically. Default is 0.0.0.0.
Zone Reports
ZONE: NO YES Sends changes in the status of active zones. Includes the zone number, name, type,
the action (alarm, trouble, bypass, etc.), user number (if applicable), and area name. If
performing a Walk Test, Zone Verify and Zone Fail messages are sent for each zone.
Supervisory Reports
SUPV MSG: NO YES Sends system monitor reports, such as AC and battery, and system event reports.
Supervisory Reports also sends the following reports:
• Abort • Exit Error • Ambush
• System Recently Armed • Alarm Bell Silenced • Unauthorized Entry
• Late to Close*
* Only sent as a Supervisory Report if Area Schedules is not enabled, Closing Check is
enabled, and an opening/closing schedule has been programmed.
To send these reports to the PC Log, you must enable SUPV MSG.
Video Reports
VIDEO: NO YES Enabling this feature will allow the panel to send video system reports to Entré when an
OpenEye® event message has been received from a camera.
Integrator Reports
INTGRTR REPORTS This option displays only if NET is chosen for the integrator connection. Choose which
types of system reports are sent to the integrator. Press CMD to view all of the integrator
report options. Choose YES to enable arming/disarming, zone, user code, door access, or
supervisory message reports. All reports default to YES.
Zone Reports
ZONE: NO YES Sends changes in the status of active zones. Includes the zone number, name, type,
the action (alarm, trouble, bypass, etc.), user number (if applicable), and area name. If
performing a Walk Test, Zone Verify and Zone Fail messages are sent for each zone.
App Key
APP KEY: Enter the 8-digit App Key obtained in your Dealer Settings tab at
dealer.securecomwireless.com.
This option is a security feature of the Virtual Keypad iPhone/Android App used only
when your Dealer Settings at dealer.securecomwireless.com have EASYconnect set as the
Communication Type.
This communication option is only available for panels with onboard network and is used to
eliminate the need for a static IP address programmed in Network Options. To enter a new
App Key, press any select key or area and enter any combination of 8 digits. Press CMD.
REQUIRE SITE Require Site Code (If Card Format is Set to DMP)
CODE: NO YES Press the select key or area under YES to use a site code.
In addition to User Code verication, door access is only granted when any one site code
programmed at the SITE CODE ENTRY option matches the site code received in the
Wiegand string.
Press the second select key or area to choose SITE (Accept Site Code) — Door access is
NO COMM WITH PNL
SITE granted when the Wiegand site code string received matches any site code programmed
at SITE CODE ENTRY. For details refer back to the REQUIRE SITE CODE option.
Press the third select key or area to choose ANY (Any Wiegand Read) — Door access is
NO COMM WITH PNL
ANY granted when any Wiegand string is received.
Press the fourth select key or area to choose ON (Relay Always On) — The relay is always
NO COMM WITH PNL
ON on.
NO COMM WITH PNL Press the rst select key or area to choose LAST (Keep Last State) — The relay remains in
LAST the same state and does not change when communication is lost.
After choosing the action, the NO COMM WITH PNL option and the newly dened action
display. Programming is now complete. Press CMD to display DEVICE NO.
Abort Report
ABORT NO YES YES allows the panel to send an alarm abort report to the receiver any time an area is
disarmed during Transmit Delay before an alarm report is sent and the Bell Cuto Time has
not expired. After disarming an area, if any other area remains armed and has zone(s) in
alarm, the alarm abort report is not sent. Abort Reports are not sent for Fire, Fire Verify, or
Supervisory type zones.
Restoral Reports
RESTORAL: YES This option allows you to control when and if a zone restoral report is sent to the central
station receiver. Press any select key or area to display the following options:
NO - Disables the zone restoral report option. Zones continue to operate normally but do
not send restoral reports to the receiver.
NO YES DISARM
YES - Enables the zone restoral report option. Zone restorals are sent whenever a zone
restores from a trouble or alarm condition.
DISARM - Causes the panel to send restoral reports for a non-24-hour zone whenever a
zone that has restored from a trouble or alarm condition is disarmed. All 24-hour zones
send restoral reports as they restore.
Bypass Reports
BYPASS NO YES YES allows the panel to send all zone bypasses, resets, and force arm reports to the
receiver. The bypass report includes the zone number, zone name, and the user name
and number of the individual operating the system. Reports are only sent if O/C User in
Communications is set YES for Receiver 1 or Receiver 2.
Access Keypads
ACCESS KEYPADS Select the keypad addresses (1 through 16) that send door access reports to the receiver.
Enter the keypad number using the digit keys. An asterisk next to the number indicates
that the keypad is selected. Press CMD to display the next set of keypads.
A report is sent with each door access made from the selected keypads. Keypads at
addresses not selected still operate the door relay but do not send access reports. The
report includes the user number, user name, keypad address, and device name.
Ambush
AMBUSH NO YES YES allows an ambush report to be sent anytime user code number 1 is entered at a
keypad. NO disables the ambush report and allows user number 1 to operate the same as
all other codes.
System
SYSTEM: AREA This option allows you to program how the areas operate for arming and disarming. The
system types are:
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the
Bedrooms. With the HOME/SLEEP/AWAY option, the user can:
1. Select HOME to arm just the perimeter.
2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
3. Select AWAY to arm all three areas.
A Home/Sleep/Away system can be congured to use all three areas or only use the Home
and Away areas.
HOME/SLEEP/AWAY WITH GUEST- This allows the alarm system to be divided into a main
house HOME/SLEEP/AWAY system and two other guest houses that also are set up as
HOME/SLEEP/AWAY systems.
Areas 1, 2, and 3 are the Perimeter, Interior, and Bedrooms for the Main house system. Areas
4, 5, and 6 are the Perimeter, Interior, and Bedrooms for the Guest 1 house system. Areas
7, 8, and 9 are the Perimeter, Interior, and Bedrooms for the Guest 2 house system. These
areas are automatically assigned per system and cannot be changed. See Display Areas in
Device Setup to assign keypads to a system. Zones are assigned to a system by assigning
the system’s area numbers to the zone in Zone Information programming.
When either All/Perimeter or Home/Sleep/Away is selected, the area names are
automatically assigned and cannot be modied.
Areas 3-32 in an All/Perimeter system, areas 4-32 in a Home/Sleep/Away system, and areas
9-32 in a Home/Sleep/Away with Guest system are not available for use and are initialized.
Instant Arming
INST ARM NO YES When YES is selected, the arming keypad displays INSTANT for selection during the exit
countdown delay when arming fewer than all areas of the system. At the time instant
arming is selected, any entry and exit delays programmed for the areas being armed are
ignored. The entry delay for previously armed areas is not aected by instant arming.
When NO is selected, INSTANT does not display during arming. Default is NO for an Area
System, and YES for an All/Perimeter or Home/Sleep/Away system.
Closing Wait
CLS WAIT NO YES When YES is selected, the keypad displays ONE MOMENT... while waiting for an
acknowledgement from the receiver before arming the selected area(s) and performing
a Bell Test (if selected). Exit delays begin after the Closing Wait. Opening/Closing reports
must be YES to enable Closing Wait.
When time zone is programmed YES, enter the number (0-23) that indicates the dierence
HRS FROM GMT: 6 between the Greenwich Mean Time (GMT) and where the panel is located. The default is 6.
*Arizona, Hawaii, American Samoa, Guam, Puerto Rico, and the Virgin Islands do not observe daylight savings time.
Bypass Limit
BYPASS LIMIT 0 Enter the maximum number of zones (0 to 8) that can be bypassed in any single area when
that area is being armed at a keypad. If more zones than the limit are in a non-normal state
or already bypassed at arming, arming does not occur and Arming Stopped displays. The
Bypass limit does not aect auto arming, keyswitch arming, or remote arming. Entering 0
(zero) allows no limit. Default is 0 (zero).
When a burglar alarm occurs in an area system and a user code is entered at a keypad
Status List, keypads programmed as KPD in Device Setup display IS THIS A FALSE
ALARM? NO YES or CANCEL VERIFY. The option is not displayed at devices programmed
as DOOR. Selecting NO or Verify sends an alarm message to the Central Station. Selecting
YES or CANCEL sends an alarm cancelled message to the Central Station and disarms the
areas that the user has the authority to disarm. This display remains on the keypad until
a selection is made, the Back Arrow is pressed, or the internal system bell cuto timer
expires.
EOL Selection
EOL VALUE: XXXX Select the resistance value in kOhms that the system will expect for end of line resistors.
Values can be set at either 1k, 2.2k, 3.3k, or 4.7k. This adjusts the voltage threshold used to
determine open, short, or normal zone conditions for zones 1-8 on XR International Series
panels. Default is 1k.
Zones 9-10 on XR International Series panels are defaulted to 3.3k.
Bell Output
BELL OUTPUT: 0 Enter the output/Favorite number when needed to follow the panel Bell Output operation
for all action and o conditions. Enter 0 (zero) to disable.
Bell Action
BELL ACTION . . . . . This section denes the type of Bell Output for zone alarms. Press CMD to display the
default Bell Output for each zone type. Press any select key or area and enter S for a
Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output, 4 for a Temporal
Code 4 output, and N for no Bell Output (default). Enable this feature to latch a bell action
to a keypad for Panic zones. Trouble conditions do not activate the Bell Output.
Strobe
STROBE: NO YES Denes whether or not a system is using a strobe on site. The default is NO.
Cuto Output
CO OUTS: - - - - - - Outputs 1 to 6 can be entered here to turn o after a time specied in CUTOFF TIME. To
disable this option, press any select key or area to clear the display then press CMD. The
Cuto Output displays dashes when no outputs are selected.
Ambush Output
AMBUSH OUT: 0 Enter the output/Favorite number to turn on when an Ambush code is entered at a keypad.
The output is turned o using the Sensor Reset option. Enter 0 (zero) to disable.
Entry Output
ENTRY OUT: 0 Enter the output/Favorite number to turn on at the start of the entry delay time. The
output turns o when the area is disarmed or the entry delay time expires. Enter 0 (zero)
to disable.
Ready Output
READY OUT: 0 Enter the output/Favorite number to turn on when all disarmed burglary zones are in a
normal state. The output is turned o when any disarmed burglary type zone is in a bad
state. Enter 0 (zero) to disable. This output is not compatible with Cuto Outputs.
Disarmed Output
DISARMED OUT: 0 This output/Favorite turns on when all areas of the panel are disarmed. The output turns
o when an area is armed.
Arm-Alarm Output
ARM-ALARM OUT: 0 Enter the output/Favorite number to turn on steady when any area of the system is armed.
If an alarm occurs causing the keypads to turn Red, this output pulses and continues to
pulse for approximately ve (5) minutes after the panel is disarmed. Enter 0 (zero) to
disable.
To operate the Arm-Alarm output within one second, program a fast response number
from 480 to 499. Fast response operation reduces overall wireless output battery life.
To operate the Arm-Alarm output within 15 seconds, program a slow response number
from 450 to 474. Slow response operation increases overall wireless output battery life.
Supervisory Alarm Output
SUPV ALM OUT: 0 Enter the output/Favorite number to turn on when a supervisory zone type is placed into
an alarm. The output turns o when all supervisory type zones are restored to normal.
Enter 0 (zero) to disable. Default is 0.
Output Name
OUTPUT NAME This section allows you to dene a 32 character alphanumeric name for any output
numbers. See the XR150INT/XR550INT Users Guide (LT-1278INT) Appendix for browser
operation.
Serial Number
SERIAL#: XXXXXXXX If a house code is programmed in system options, then this option and the next option
only display when the output number entered is for a wireless output. Enter the eight-digit
serial number found on the wireless device.
ALREADY IN USE Already In Use displays when the serial number is already programmed for another output.
OUTPUT NO: XXX
The programmed output number displays.
Group Number
GROUP NO: - Enter a group number from 1 to 20. Up to 20 dierent groups may be assigned.
Group Name
GROUP NAME X X The group name displays. To change the default name, press any select key or area then
enter up to 32 characters for the group name. Press CMD to enter the outputs to be
assigned to the group.
Output Number
OUTPUT NO: 1 Enter the Output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999
(outputs), F1 to F20 (favorites), D01 to D16 (doors), and G1 to G20 (groups). The maximum
number of outputs that can be assigned to a specic group is eight.
An output group may be assigned as one of the output numbers in another output group.
Output groups 1 to 10 can be assigned by a user prole for applications such as elevator
control. See the XR150INT/XR550INT Users Guide (LT-1278INT) Output Group section for
additional information.
Output groups 11 to 20 cannot be assigned to a prole and are available for installation
applications such as special lighting, etc.
Armed Status
ARMED STATUS Enter the keypad addresses (1 through 16) that show the armed areas. The User Menu
Armed Areas function also displays the custom area name you enter in Area Information.
*1 *2 *3 *4 When only areas one to eight are used, the Armed Status display is 1 2 3 4 5 6 7 8. When
*5 *6 *7 *8 areas nine or higher are used the system Armed Status display reads ALL SYSTEM ON or
SYSTEM ON. Press CMD to display additional areas.
*9 *10 *11 *12
*13 *14 *15 *16
Time
TIME DISPLAY
Enter the keypad addresses that can display the time and day of the week.
*1 *2 *3 *4
*5 *6 *7 *8
Arm/Disarm
ARM/DIS DISPLAY Enter the keypad addresses from which users can arm and disarm areas.
*1 *2 *3 *4
*5 *6 *7 *8
Display Keypads
DISPLAY KEYPADS This option denes which keypad addresses display the various status information. Any
combination of addresses can be entered to display the status items that follow. If you do
not want a particular status item to display, do not enter any addresses.
Fire Zones
FIRE ZONES: Species the keypad addresses (1 through 16) where all re zone alarms and troubles
display. The zone name displays and, if it is a trouble condition, the keypad steady trouble
buzzer sounds. The buzzer remains on until any select key or area is pressed and a user
code is entered. If a trouble condition remains in the display, the buzzer sounds at 10:00
am daily until the trouble is cleared from the Status List.
Burglary Zones
BURGLARY ZONES: Species the keypad addresses (1 through 16) where all burglary zone alarms and troubles
display. Burglary zones include Night, Day, and Exit type zones. Burglary zone troubles
remain in the list until the zone restores. All keypads are selected by default.
For zone alarms, only the last burglary zone tripped remains in the list. The alarm remains
in the list until another burglary zone goes into alarm, any area of the system is disarmed,
or 10 minutes elapse without an alarm. This ensures that if a burglary is in progress the last
zone tripped remains in the list even if the zone is restored.
The keypad buzzer sounds for one second on burglary alarms.
You can further dene which keypad address shows a Burglary Zone event by entering that
area number in the Display Areas menu during Device Setup.
Panic Zones
PANIC ZONES: Species the keypad addresses (1 through 16) where all panic zone alarms and troubles
display. The name of the zone remains in the list until a Sensor Reset is performed. The
keypad will sound if the Bell Action is enabled in Bell Options.
Emergency Zones
EMERGENCY ZONES: Species the keypad addresses (1 through 16) where all emergency zone alarms and
troubles display. The name of the zone remains in the list until the zone restores. The
keypad buzzer does not sound for emergency alarms or troubles.
Auxiliary 1 Zones
AUX 1 ZONES: Species the keypad addresses (1 through 16) where all Auxiliary 1 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores. The
keypad buzzer does not sound for Auxiliary 1 alarms or troubles. You can further dene
which keypad address shows an Auxiliary 1 Zone event by entering that area number in the
Display Areas menu during Device Setup.
Auxiliary 2 Zones
AUX 2 ZONES: Species the keypad addresses (1 through 16) where all Auxiliary 2 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores. The
keypad buzzer does not sound for Auxiliary 2 alarms or troubles.
You can further dene which keypad address shows an Auxiliary 2 Zone event by entering
that area number in the Display Areas menu during Device Setup.
Net Port
NET PORT 2001 This option displays when Communication Type for PC Log Reports is Net. Enter the Port
number. Valid numbers are from 0 to 65535. Default is 2001.
Zone Reports
ZONE NO YES Sends changes in the status of active zones. Includes the zone number, name, type, the
action (alarm, trouble, bypass, etc.), user number (if applicable), and area name. For a Walk
Test, zone verify and zone fail messages are sent for each zone.
Supervisory Reports
SUPV MSG NO YES Sends system monitor reports, such as AC and battery, and system event reports.
Supervisory Reports also sends the following reports:
• Abort
• Exit Error
• Ambush
• System Recently Armed
• Alarm Bell Silenced
• Unauthorized Entry
• Late to Close*
*Only sent as a Supervisory Report if Area Schedules is not enabled, Closing Check is
enabled, and an opening/closing schedule has been programmed.
To send these reports to the PC Log, you must enable SUPV MSG.
Exit Delay
EXIT DELAY: 60 Enter the exit delay time for all Exit type zones in this area. When the exit delay time starts,
all activity on that zone and other non-24-hour zone types in the area is ignored until the
exit delay expires. The keypad displays the Exit Delay time countdown and annunciates
the Exit Delay tone at 8 second intervals until the last 10 seconds when annunciation is at 3
second intervals.
The exit delay can be from 30 to 250 seconds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay timer
restarts. This restart can occur only once.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end of the
exit delay then one of two sequences occur:
For Entry Delay 1 EX type zones:
• The bell sounds for the length of time set in Bell Cuto programming
• The Entry Delay operation starts requiring code entry to disarm
• If not disarmed, a zone alarm and an exit error are sent to the receiver
For Entry Delay 2-4 EX type zones:
• The zone is force armed and a zone force arm message is sent to the receiver
• An Exit Error is sent to the receiver
• The bell sounds for the length of time set in Bell Cuto programming
Closing Check
CLS CHK NO YES Select YES to enable the panel to verify that all areas in the system are armed after
permanent or extended schedules expire. If the Closing Check nds any areas disarmed
past the scheduled time, the keypads selected to display System Trouble Status displays
CLOSING TIME! and emits a steady beep. When Area Schedules is set to YES in Area
Information, the specic area and name display followed by — LATE.
When Auto Arm is NO, if within ten minutes the system is not armed or if the schedule is
not extended, a Late to Close report is sent to the SCS-1R Receiver. When Auto Arm is YES,
the area arms.
If the area becomes disarmed outside of any schedule, the Closing Check sequence occurs
after the Late Arm Delay time.
When Closing Check is NO and Auto Arm is YES, the system immediately arms when the
schedule expires. No warning tone occurs.
In addition, when Closing Check is NO, the option to extend a schedule does not display
when the schedule expires.
Closing Code
CLS CODE NO YES When YES is selected, a code number is required for system arming. If NO is selected, a
code number is not required for system arming.
Any Bypass
ANY BYPS NO YES When YES is selected, zones can be bypassed without a code number during the arming
sequence. A code number is always required to use the Bypass Zones option from the
menu.
Area Schedules
AREA SCH NO YES Select YES to allow each area to follow individual sets of area schedules programmed in
the User Menu. Select NO for all areas to follow only one set of schedules in the User Menu.
See the panel User Guide (LT-1278INT) to add schedules to the panel. Area Schedules are
not designed to operate with All/Perimeter or Home/Sleep/Away systems.
XR150INT/XR550INT Series Programming Guide Digital Monitoring Products
47
Early Morning Ambush (Network Panels Only)
EARLY AMBUSH: 0 Enter the number of minutes (1 to 15) before a silent alarm (Early Morning Ambush S33)
is sent to the central station using the area 1 account number. Enter 0 (zero) to disable this
option.
When a user code is entered to disarm area 1 at a keypad or reader with Access Areas
assigned to area 1, the same or dierent user code must be entered within the programmed
number of minutes to prevent an ambush message from being sent to the receiver. The
second user code also must have authority to disarm area 1.
In addition, a zone activation with Alarm Action Message C also cancels the Early Morning
Ambush timer and stops an Ambush message from being sent to the receiver. See Report
to Transmit section in Zone Information.
The keypad does not display any indication that the ambush timer is running.
Indications can be provided by assigning an output number to Entry Out and Ambush Out
in Output Options. Entry Out turns on one minute before the timer expires and turns o at
expiration. Ambush Out turns on at the timers’ expiration and turns o when Sensor reset
is performed.
Area Number
AREA NO: - Enter the number of the area to program. Press CMD to continue. Only Area systems allow
the area name to be changed. When All/Perimeter or Home/Sleep/Away is selected as the
system type, the Area Number does not display.
All/Perimeter Programming
INT PERIM When All/Perimeter is selected as the system type, program the Interior and Perimeter
areas as needed.
Home/Sleep/Away Programming
INT BDRM PERIM When Home/Sleep/Away is selected as the system type, program the Interior, Bedroom,
and Perimeter areas as needed.
Area Name
* UNUSED * The area name can be up to 32 alphanumeric characters. To add an area name to the system,
press any select key or area and then enter up to 32 characters for the new area name. Press
CMD to continue. Inactive areas are marked * UNUSED *. Only systems programmed for Area
arming have the option available to change the area name.
To mark an active area unused, press any select key or area to delete the old name, then
press CMD. The programmer automatically programs the name as *UNUSED*. If you have
already cleared Area Information during Initialization, all areas are marked * UNUSED *.
Home/Sleep/Away with Guest systems display the area name, but the names cannot be
changed. The following are the display names that appear on the keypad:
Account Number
ACCOUNT NO: 12345 Enter the account number to be sent to the receiver for this area. Choose an account number
compatible with the Communication Type selected in Communications. The default Account
Number is the one previously entered in Communications. This account number is used when
sending area messages and events to the central station.
Opening/Closing Reports
O/C RPTS NO YES This option allows an Opening/Closing report to be sent to the receiver when this area is
disarmed or armed.
Bad Zones
BAD ZONES: BYP At the time of automatic arming, some zones in the area may not be in a normal condition.
This option allows you to program the panel response to these bad zones. This option does
not display if AUTO ARM is NO.
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if Bypass
BYP FORC REF Reports is YES. The report indicates SCH as the user number.
FORC - All bad zones are force armed. Zones force armed in a bad condition are capable
of restoring and reporting an alarm if tripped. A forced zone report is transmitted if Bypass
Reports is YES. The report indicates SCH as the user number.
REF - The automatic arming is refused and no arming takes place. A No Closing report is
sent to the receiver regardless of the Closing Check selection.
Automatic Disarming
AUTO DIS NO YES NO disables automatic disarming by schedule for this area. When YES is selected, the
area automatically disarms according to permanent or temporary schedules. If an opening
report is sent to the receiver, the user number is indicated as SCH.
Common Area
COMMON NO YES Select YES to enable this area to operate as a common area. This area is armed when
the last area in the system is armed and is disarmed when the rst area in the system is
disarmed. You can have multiple common areas in each system. For the common area to
work properly, do not assign the common area to any user code.
Zone Number
ZONE NO: - Enter the number of the zone you intend to program. Available zone numbers are shown in
the table below.
Zone Name
* UNUSED * Zone names can have up to 32 alphanumeric characters. A name must be given to each
zone in the system. The name can display at the keypads during arming and disarming so
the user does not have to memorize zone numbers. A zone that is not part of the system
must be marked unused.
To add a zone name to the system, press any select key or area and then enter up to 32
characters for the new zone name. Press CMD to continue.
To mark a zone unused, delete the old name by pressing any select key or area, then press
CMD. The programmer automatically programs the name as * UNUSED *. If you have
already cleared Zone Information during Initialization, the zones is marked * UNUSED *.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, Arming, Final Exit, or Tamper as
the Zone Type, the zone must be assigned to an active area. If you select Fire, Fire Verify,
Panic, Emergency, Supervisory, or CO as the Zone Type, it is a 24-hour zone that is always
armed and no area assignment is needed.
Area Assignment
AREA NO: - Enter the area number where the Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Instant zone
is being assigned. For an Area system, area numbers 1-32 can be assigned. For a Home/
Sleep/Away with Guest system, area numbers 1-9 can be assigned.
In an All/Perimeter or Home/Sleep/Away system, the currently selected area, Perimeter,
AREA: PERIMETER Interior, Bedroom displays.
On an All/Perimeter system, select INT to program zones for the interior area and select
INT PERIM PERIM to program zones for the perimeter area.
On a Home/Sleep/Away system, select INT to program zones for the interior area, select
INT BDRM PERIM BDRM to program zones for the bedroom area, and select PERIM to program zones for the
perimeter area.
Note: Triple EOL operation only works with Optex FLX Series Anti-Masking PIRs. All
other products use single or dual EOL operation.
This output can be connected to a lamp, LED, or buzzer using the DMP Model 716 Output
Expansion Module.
When the zone changes from normal to shorted, the programmed areas toggle between
the armed or disarmed condition using the Style programming below. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported and
the zone is disabled until you disarm the area(s) from either a keypad, Virtual Keypad, or
Remote Link™ computer.
To visually indicate the armed state of the area(s), you can assign an Armed Output to
ARM AREAS: PERIM individual areas and use remote LEDs at the keyswitch. The LED turns on or o to indicate
to the user the armed state of the area(s).
Perimeter/All - Specify whether the arming zone arms just the Perimeter (PERIM) or the
PERIM ALL Perimeter and Interior areas (ALL) for All/Perimeter systems. When disarming, all areas are
disarmed.
Home/Sleep/Away - Specify whether the arming zone arms the Perimeter (HOME), the
HOME SLEEP AWAY Perimeter and Interior (SLEEP), or all three areas (AWAY). When disarming, all areas are
disarmed.
Arming Zone Operation
If any bad zones are present when the Arming zone is shorted, the LED delays lighting for
5 seconds. If during the 5-second delay the Arming zone is shorted again no arming takes
place. If 5 seconds expire without the zone shorting again or restoring to normal, the areas
arm and bad zones are force armed. To allow bad zones to be force armed, the Any Bypass
option must be set to YES. If Any Bypass option is set to NO, arming does not occur. See
the Area Information - Any Bypass section. A priority zone cannot be force armed.
Next Zone
NEXT ZN? NO YES Select YES to terminate zone programming. The display returns to Zone Number, allowing
you to enter a new zone number. Select NO to make alterations to the Alarm Action for a
zone.
To program zones for wireless operation, select NO at the NEXT ZONE - NO YES option.
The WIRELESS NO YES option displays. If the zone you are programming is intended for
wireless devices, select YES. Select NO to continue programming non-wireless zones in the
500 to 999 range.
• Zones 400 to 449 can be programmed for 1144 Series Key Fobs
• Zones 500 through 599 can be programmed for DMP 1100 Series Wireless on an
XR150INT Series panel
• Zones 500 through 999 can be programmed for DMP 1100 Series Wireless on an
XR550INT Series panel
TRANSMITTER Contact
CONTACT: XXXXXXXX Transmitter Contact displays if the serial number entered is for an 1101, 1103, or 1106
Universal Transmitter or 1114INT Wireless Four-Zone Expander. Press any select key or area
to select the contact.
TRANSMTR CONTACT Select INT to use the internal reed switch contacts. Select EXT to connect an external
INT EXT device to the 1101, 1103, or 1106 terminal block. Default is INT.
By allowing both of the transmitter contacts (INT and EXT) to be used at the same time,
two zones may be programmed from one transmitter. When using both contacts, you must
use consecutive zone numbers. The same serial number is used for both zones.
Contact Selection option displays when programming the 1114 Wireless Four-Zone
TRANSMTR CONTACT
Expander with four input contacts. The same serial number is used for all four contacts.
1 2 3 4
Select the contact number to program. When using the contacts, you must use consecutive
zone numbers. Default is Contact 1.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
Already In Use message displays when the Contact is already programmed for another
ALREADY IN USE
ZONE NUMBER: XXX zone. The programmed zone number displays.
When EXT is selected as the Contact type, external devices connected to the 1101, 1103 or
ZONE INFORMATION
NORM OPN NO YES 1106 terminal block, select NO to use normally closed (N/C) contacts. Select YES to use
normally open (N/O) contacts. Default is NO.
Next Zone
NEXT ZONE NO YES Select YES to return to the ZONE NO: - option to program a new zone. Select NO to
display the Alarm Action option. Press CMD to continue.
Alarm Action
ALARM ACTION . . . . This option allows you to change any Zone Type standard denitions. When the Zone Type
is specied, the Alarm Action for that zone is stored in memory.
Disarmed Open
DISARMED OPEN Denes the action taken by the panel when the zone is opened while the area is disarmed.
There are three actions to dene: Report to transmit, Relay Output to activate, and Relay
Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press CMD to continue.
CANCEL AMBUSH - Select C for the zone to cancel the Early Morning Ambush timer and
stop an Ambush message from being sent to the receiver. Faulting the zone takes the
place of a second user code being entered at the keypad and is only available for non-re
type zones. Area assignment for the zone does not aect this option. See Early Morning
Ambush in Area Information programming.
Output Number
OUTPUT NO: 0 You can specify any of the Relay Outputs on the panel to be activated by a zone condition
(1 to 6, 500 to 999 if Model 716 used, D01 to D16, G1 to G20). The output can be activated
regardless of the report to transmit or whether or not the zone is programmed as local. An
output activated by an armed zone is turned o when the zone area is disarmed by a user.
To enter an output number, press any select key or area followed by the output number.
Press CMD.
Output Action
OUTPUT: NONE Output Action allows you to assign an output action to the relay: Steady, Pulse, Momentary,
or Follow.
STEADY - The output is turned on and remains on until the area is disarmed, an output
STD PLS MOM FOLW cuto time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second o.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an o normal, or
bad condition. When the zone restores, the output is turned o.
For Day Zone types, when an output is turned on, a user code with silence authority can
turn the output o.
Swinger Bypass
SWGR BYP NO YES Selecting YES allows the zone to be swinger bypassed by the panel according to the
specications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The Bypass
condition displays in the keypad Status List. Selecting NO disables swinger bypassing for
this zone.
If within one hour, a zone trips the total number of times as specied in Swinger Bypass
Trips, the panel bypasses it until the following conditions occur;
• The area in which the zone is assigned is disarmed
• The zone is manually reset through the Bypass Zones? keypad User Menu
function
• The zone remains normal for one hour and the Reset Swinger Bypass is YES.
If the zone trips fewer than the specied times within one hour, the bypass trip counter
returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
Chime
CHIME: DOORBELL Option is only shown for Night, Exit, and Instant zones. Select either NONE, DB (doorbell),
ASC (ascend), or DSC (descend) to assign that tone to a zone. Default is DOORBELL for
Exit zones and NONE for Night zones.
Entry Delay
ENTRY DELAY: 1 Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System Options.
Fast Response
FAST RSP NO YES Select YES to provide a zone response time of 167ms. Select NO to provide a normal zone
response time of 500ms. Zones 500 to 999 have a xed response time and do not display
this option.
Cross Zone
CRS ZONE NO YES Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed
zones to fault within a programmed time before an alarm report is sent to the receiver.
When the rst cross zoned zone trips, the cross zone time specied in System Options
begins to count down. When a second cross zoned zone trips or the rst zone trips a
second time before the end of the count down, the bell action assigned to the zone
activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel sends only
a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning for
Fire verify zones or for any Fire zones that have Retard Delay enabled.
Priority
PRIORITY NO YES Select YES to provide additional protection for the premises by requiring this zone to be in
a normal condition before its assigned area can be armed.
Area Follower
FOLLOW AREA: 0 Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit or
entry delay that is currently running in the area that is specied. Default is 0.
LOCKDOWN: Lockdown
NO YES This option is available when programming a Panic type zone. Selecting YES triggers a
lockdown when a panic zone is tripped. Default is NO.
USER XXXX User Not in Use displays when the User Number entered does not exist in User Code
NOT IN USE programming. The key fob can be added, but the user must eventually be added to cause
the key fob to operate.
Output Number
OUTPUT NO: XXX You can specify any relay Output/Favorite to operate when OUT (Output), PN (Panic), PN2
(Panic 2), EM (Emergency), or EM2 (Emergency 2) is selected for a key fob Button Action
and the button is pressed. Valid range is 1 to 6, 500 to 999, D01 to D16, F1 to F20, or G1 to
G20. For an output turned on by a PN, PN2, EM, or EM2 button action, the output turns o
when any area is disarmed.
To enter an output/Favorite number, press any select key or area followed by the output/
Favorite number. Press CMD.
Once you have changed the code, it is important to write it down somewhere and store
it in a safe place. Lost Lockout Codes require the panel to be sent back to DMP for repair.
You may cancel a Lockout Code by entering 00000 at the Set Lockout Code command.
ENCRYPTION Encryption
DISABLED Enable this feature to provide 128-bit or 256-bit AES data encryption. This feature upgrade
can only be enabled on an XR550INT panel with network. To verify encryption installation,
access System Status in the User Menu to verify the encryption status (OFF, ON). If the
status displays OFF, a Passphrase has not been entered in Network Options and data
transmissions are not encrypted. See Network Options to set up a Passphrase.
User Menu
Service User? NO YES
After navigating past REQUEST SERVICE in the User Menu, SERVICE USER? NO YES is
displayed to determine the authority level of the service user to access PROG, DIAG and
User Menu.
When Yes is selected the Service User can add, edit and delete users. Service User can
enter panel programming. When EN50131 GRADE option is set to 3, any code assigned
prole 99 operates as a Level 3 user.
Only a Level 3 (Service User or user code with prole 99) user can arm the system if any of
the following conditions exist:
• Panel Tamper
• Transmitter Missing
• Device Missing
If any of those conditions exists, any other user that attempts to Arm or Disarm the system
will prompt Invalid Level to display on the keypad.
Closing Code
If AC POWER or BATTERY troubles exist in the Status List, a code is required to arm,
regardless of the Closing Code setting.
LED Indication
If there is more than 1 item other than time, weather, or ready status in the Status List, the
Status LED blinks at 1 sec o, 1 sec on.
ANTI-MASKING FEATURE
The triple EOL conguration is only designed to work with Optex FLX Series Anti-Masking PIRs. Although this device is
normally closed, it should be programmed in the following ways:
DisarmedArmed Short - The alarm contact is faulted on the PIR, and the normally closed contact is open.
DisarmedArmed Open - The trouble contact is faulted on the PIR, and the normally closed contact is open.
TamperAnti-Masking Detection - Both alarm and trouble contacts are faulted, and both contacts are open.
Tamper -The zone wires connected to the PIR are cut or shorted.
DIAGNOSTICS FUNCTION
The panel contains a Diagnostics function that allows you to test the communication integrity of the LX-Bus™, identify
individual zones, and also display the present electrical state of any zone. The Diagnostics function also allows you
to test the integrity of the cellular communication, and cellular signal.. To use Diagnostics, reset the panel, enter the
Diagnostics code 2313 (DIAG), and press CMD.
Test LX-Bus
This function allows you to test the ability of the panel to communicate with zone and output expander modules
connected to the LX-Bus circuits.
To continue, press any select key or area. The keypad displays LX-BUS:. Using the digit keys, enter the LX-Bus number, 1
to 5, to test that LX-Bus circuit. The keypad now displays ADDRESS: - . Enter a 2-digit LX-Bus device address and press
CMD. When testing LX-Bus devices, enter only the addresses to which the modules have been set. Press any select key
or area when TEST LX-BUS displays.
A device address is not the same as a zone number. If you are testing 714 or 715 Zone Expander Modules, which each
contain four zones, the device address is the rst zone number. When the panel polls a 714 on the LX-Bus, it recognizes
it as a four zone device and does not poll the remaining three zones. The 714 module internally polls the remaining zones
and transmits any status changes to the panel. This greatly reduces the amount of time it takes the panel to poll all LX-
Bus devices.
The keypad next displays TESTING . . . STOP during the device testing. At any time, you can select STOP to end polling.
The panel records the number of no responses from the device. If all polls are received back by the panel correctly, the
keypad displays 00000/65535 FAIL.
If one or more polling attempts fail, the keypad displays * * * * */65535 FAIL with the * representing the number of failed
polling attempts. A display of 65535/65535 FAIL indicates a problem with the interface card or its LX-Bus wiring such
as a bad or broken wire, harness not properly connected, or excessive noise or distance. It can also mean that a zone
number was entered that did not match a device address. Press the Back Arrow key to enter a new device address or
press CMD to exit the TEST LX-BUS.
Zone Finder
The second Diagnostic function is the Zone Finder. Press CMD to display ZONE FINDER. This function
allows you to identify individual zones on devices connected to the LX-Bus of an interface card, the panel, or any zones
on the keypad data bus. To use ZONE FINDER, press any select key or area. The display changes to FAULT ZONE. The
next zone on the system that changes from a normal to an open or shorted state is displayed as ZONE NO: * * *. To
continue, press the Back Arrow key.
LX-Bus Status
The fourth Diagnostic function is the LX-BUS STATUS. This function allows the panel to poll all devices connected to the
LX-Bus of an interface card and check for any Overlapped, Missing, or Extra addresses. Below is a description of each
status item:
Overlap - An overlap occurs when one device address is the same as any of the last three zones on another 714 or 715.
The overlap feature cannot determine when two devices have the same address.
Missing - A missing occurs when a zone between 500 and 999 has been programmed in ZONE INFORMATION and no
device with that zone address has been installed on the LX-Bus. To correct the problem, check your zone programming
and zone expansion module addressing.
Extra - A device is installed on the LX-Bus but none of its zones are programmed into the system.
MAC Address
Short for Media Access Control address. This hardware address uniquely identies each network node. Not to be
confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the panel on-board
network hardware address. Press any select key or area to display the panel MAC address. Press CMD to view the next
option.
Serial Number
This number is the network communicator serial number. Reference this number for communicator date-of-manufacture,
hardware version, etc. Press any select key or area to display the Serial Number. Press CMD to view the next option.
Loader Version
This display is for factory use only. Press any select key or area to display the factory Loader Version. Press CMD to view
the next option.
Current Flash
This option displays Flash 1 or Flash 2 indicating which physical ash chip the panel is currently using. Press select key or
area to display the current ash information. Press CMD to view the next option.
Cellular Results:
SIGNAL: ▐▐▐▐▐▐▐ This displays the cellular signal strength of the nearest tower for the SIM card carrier.
The ▐’s represent the signal strength 0-7. Select YES to continue through the remaining
CONTINUE? NO YES
component tests. Select NO to stop testing and return to the COMM STATUS option.
Network Results:
When using the 399 cable to program the panel, the connection type should be “Direct” and the baud rate set to 38400.
This connection may be used for all Remote Programming, including Remote Update.
Z-Wave Information
This option allows the installer to view the hardware and software level of the 738Z that is connected to the system.
The name of the device displays above the device number. The current number of successful communications followed
by the total number of attempts displays to the right of the device number. The test stops after 99 attempts.
Press CMD until STOP displays. Press any select key or area. The keypad returns to the Status List display.
The function 984 + CMD can be entered at the keypad, and a remote options menu appears. This menu contains the
following options:
NUMBER: Enter a phone number into the keypad for the panel to dial. Enter any required prexes and area codes.
The panel dials each number as it is pressed. If you make a mistake, press the Back Arrow key. The panel stops dialing
and return to the Status List.
You can enter up to 32 characters for the phone number. Once you have entered 16 characters the LCD display is
full: Press CMD to enter the nal 16 characters. Program a pause by entering the letter P. Program CID message
communication by entering the letter T in the rst position. Cancel call waiting by entering *70P as the rst characters.
Press CMD after you enter the phone number.
The panel calls the receiver connected to Remote Link™ to download the new programming. Remote Link™ then traps
the panel.
The panel makes ten attempts to reach the receiver. While attempting to contact the receiver, if the panel needs to send
an alarm report, the panel stops dialing and uses the phone line to send its report.
TEST: The panel allows you to perform a Communication Status Test on each component of the panel’s cellular or
network communication paths. Press the select key or area under TEST to allow the panel to perform a Communication
Status Test. The display prompts the user for a user code to be entered. The user code must have the authority to
perform a System Test.
Upon entry of a Cell or Network path when prompted, the test runs and the results display on the keypad. See
Diagnostic Functions section for a description of the Communication Status results.
PICKUP: The panel picks up the phone line when Remote Link™ calls in. The phone must be ringing before selecting
PICKUP. After completing panel programming in Remote Link™, connect to the panel by selecting Panel > Connect. Refer
to the Remote Link™ User’s Guide (LT-0565), or Help File for complete information about connecting to panels.
While the panel displays in the status list and the telephone line at the panel rings, enter 984 and press CMD. The keypad
display changes to NBR TEST PICKUP. Press the select key or area under PICKUP to allow the panel to seize the line.
The panel immediately seizes the phone line and sends a carrier tone to the receiver. A verication process occurs and, if
successful, the panel grants remote access to its programming and Event Buer.
After the panel has seized the line, send the le from Remote Link™ by selecting Panel > Send. Remote Link™ then
uploads the new programming into the panel. You may also Request Events by selecting Panel > Request Events in
Remote Link™. The panel begins sending the rst event or access that occurred on or after the start date specied by
Remote Link™ and nishes by sending the last event or access that occurred on or before the end date specied by
Remote Link™. If necessary, a Request Events upload in progress can be cancelled.
KEYPAD DISPLAYS
When the PICKUP option is used, the keypad displays LINE SEIZED. This indicates that the panel has seized the line and
is executing its program. If the line cannot be accessed, or if the PICKUP option is used before all connect attempts are
made, the keypad displays SYSTEM BUSY.
Zone Types
BG FI PN SV Select the zone type you want to test. An asterisk next to the zone type indicates the zone
type chosen for testing. Press the select key or area again to deselect the zone type. When
you have selected all the zone types you want for testing, press CMD to display the next
Walk Test option.
BG (Burglary zones) - Select BG to test hardwired burglary zones. Includes all NT, DY, EX,
A1, and A2 zones.
FI (Fire zones) - Select FI to test hardwired re zones. Includes all FI and FV zones.
PN (Panic zones) - Select PN to test hardwired panic zones. Includes all PN and EM zones.
SV (Supervisory zones) - Select SV to test hardwired supervisory zones. Includes all SV
zones.
During the Walk Test, trip each zone device or button on the system for 1 to 2 seconds.
You do NOT have to hold the zones for 2 seconds in normal mode for PN type zones. You
are only required to hold the panic during the Walk Test because the zone takes additional
time to report when the system is in test mode.
WLS (Wireless Check-in Test) - Select WLS to automatically test wireless transmitter
WLS PIR communications. Includes all wireless devices except key fobs and transmitters
programmed for a supervision time of 0 (zero).
PIR (Wireless PIR Walk Test) - The PIR Walk Test allows the installer to verify the 1122, 1126,
or 1127 operation. When enabled, the PIR LED ashes each time motion is detected for up
to 30 minutes. This is a local test only and no messages are sent to the Central Station.
Bell Action
BELL NO YES PULS This option selects the bell output action when a zone under test faults. This option allows
the panel bell, and/or burglary bell, and/or re bell to turn ON and then OFF each time a
zone is tripped (opened or shorted).
NO - Select NO for no bell output action during Walk Test.
YES - Select YES to turn on any bell output for 2 seconds during Walk Test.
PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any LX-Bus
device output turns on for 1.6 seconds due to the polling cycle.
For all other zone types, the Verify message is sent when the zone restores. This allows the
Central Station to count the number of devices per zone.
END - Select END to stop the Walk Test. When the Walk Test ends or a 20-minute time-out
expires, a nal Sensor Reset occurs. The System Test End message is sent to the receiver
along with Verify and Fail messages for each zone under test. Faulted zones then display
on the keypad.
IN PROGRESS XMIN Trip Counter For DMP Wireless Check-in Test (WLS)
CHECKIN: CC/TT END Displays the number of wireless zones that automatically communicate a supervisory
check-in message. The test will run for a total of 5 minutes. During the 5 minutes the
transmitters are being tested multiple times. At the end of the 5 minutes the results will be
displayed. A timer will be displayed at the keypad to indicate that the test is in progress.
In order for a transmitter to pass it must have checked in 3 or more times. The results will
display which transmitters have failed the test.
• The number of zones that check in. (CC in the example).
• The total number of wireless zones programmed for supervision that should check in.
(TT in the example).
END - Select END to stop the Wireless Test. When the test ends or a 5-minute time-out
CKIN:XXX/ZZZ END expires, normal wireless zone processing returns. If all transmitters check-in, both numbers
match within ve (5) minutes. If a transmitter has multiple zones (1101, 1114, etc.), all zones
are included in the counts. Failed wireless zones display on the keypad.
Fire On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
O - Alarm Silence.
Burglary On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
O - Alarm Silence.
Zone Monitor On - One time only when a monitored zone is tripped.
O - After one tone.
CO On - CO zone alarm and Bell Output are ON.
O - Using Sensor Reset option while no additional CO type zones are in alarm.
Prewarn On - During Entry Delay.
O - When Entry Delay expires.
CROSS ZONING
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to allow an
intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an intruder to trip the
devices and allow only a zone fault report be sent to the central station.
When a Cross Zoned zone trips a FAULT report is sent to the SCS-1R or SCS-VR Receiver. When two Cross Zoned zones
trip within the Cross Zone Time, both zones send ALARM signals to the receiver.
USER PROFILES
A prole denes the authority of each user code in the system. Proles are programmed in the Keypad User Menu.
Several characteristics associated with each User Prole dene its authority within the system. To eectively program an
XR150INT/XR550INT Series system, you must understand the interrelationship between proles, devices, output groups,
and areas. Below is a brief explanation of the User Prole elements. For more information about user proles, refer to the
User Proles Record and the XR150INT/XR550INT Users Guide (LT-1278INT).
Proles cannot be changed via keypad in an All/Perimeter or Home/Sleep/Away system. Use the default proles 1
through 10.
Prole Number - Each prole may be assigned a unique number from 1 to 99.
Prole Name - Each prole may be assigned a 32-character name. The Prole Number is the default name.
Area Number - Each prole may be assigned specic areas of the system for arming and disarming. When creating
proles 1 to 98, NO areas are assigned by default. The default for prole 99 is ALL areas assigned. Prole 99 is
preprogrammed in the system at the factory.
Access Area Number - Each prole may be assigned door access area assignments. Default for prole 1 to 98 is NO areas
assigned. Default for prole 99 is ALL areas assigned. Prole 99 is preprogrammed at the factory.
Output Group Assignment - Each prole may be assigned an output group number from 1 to 10. Default for prole 1 to
98 is NO output group assigned. Default for prole 99 is output group 10. Your system may by programmed to turn on
an output group at certain keypads when door access occurs.
User Menu Assignments - Each user prole may have any of the menus assigned to it as shown in the following
User Prole Record. The User Prole Record lists the user menu prole assignments and the system functions users
are allowed to access based on the prole numbers assigned to their codes. Always make sure that at least one
administrator in your system has a prole with all authorities and areas.
First Access/Second Access - Each prole may be assigned two schedules to allow or restrict access and disarming
times.
Door Lock/Unlock
Extend Schedules
Easy Arm/Disarm
Second Access, 1-99
Temp User Code
Service Request
Technician User
Fourth Access, 1-99
Dual Authority
Display Events
Anti-passback
Alarm Silence
Sec Language
Re Arm Delay
Zone Monitor
Inactive User
Sensor Reset
Access Areas
User Proles
Door Access
Arm/Disarm
System Test
Armed Area
Zone Status
Wi-Fi Setup
User Codes
Lockdown
Schedules
Fire Drill
Prole #
Disarm
Prole
Areas
Time
Arm
Name
-- (Blank Zone)
Customizable zone type. By default, no actions are programmed to occur with Blank Zone. A zone name must be
entered to use this zone type: This zone type is not the same as an *UNUSED* zone.
NT (Night Zone)
Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and Glassbreak
detectors.
DY (Day zone)
Used for emergency doors or re doors to sound the keypad buzzer and display the zone name when the zone is
faulted. Day zones also send alarm reports to the receiver during the system armed periods.
EX (Exit zone)
Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an exit delay timer to allow a user
to exit an area after the arming process starts.
FI (Fire zone)
Used for any type of powered or mechanical re detection device. Typical applications are for smoke detectors, sprinkler
owswitches, manual pull stations, and beam detectors. Retard, cross zoning, and presignal options are available for the
Fire zone type.
PN (Panic zone)
Used for connecting to mechanical devices that allow a user to signal an emergency alarm. Panic zones can provide
either a silent or audible alarm with or without reporting to a central station receiver.
EM (Emergency zone)
These are used for reporting medical or other non-panic emergencies to the central station receiver.
SV (Supervisory zone)
Used to provide 24-hour zone supervision to devices associated with re systems. Typical applications are tamper
switches on Post Indicator Valves (PIVs), gate valves, and low and high temperature gauges.
AR (Arming zone)
This zone allows you to connect a keyswitch to a zone and use it to arm and disarm one or more areas.
CO (Carbon Monoxide)
This output turns on any time a Carbon Monoxide Zone (CO) is placed in alarm. The output is turned o using Sensor
Reset option while no additional CO type zones are in alarm.
IN (Instant)
This provides a zone that does not follow entry or exit zones. Choose Instant if you need a zone that will not follow Entry
or Exit delay.
DB (Doorbell)
This zone type is intended for use for zones that are assigned to doorbells.
FX (Final Exit)
This zone type is used to identify a zone that must be tripped before the system will arm.
TP (Tamper)
This zone type is used to identify zones that are being used for enclosure tamper switches.
The panel sends the following messages using the area account number based on the lowest area number in Display
Areas programming from the keypad being used:
• User Code Add/Change/Delete
• Door Access/Denied
• User 1 Ambush and Early Morning Ambush
• System Test Begin/End
• Unauthorized Entry
• Service Code and Service Request
The panel sends the following messages using the area account number based on the area number:
• Late to Arm for area schedules
INTERNATIONAL CERTIFICATIONS
INTERTEK (ETL) LISTED
EN 50130-4:2011+A1:2014 Alarm systems. Electromagnetic compatibility. Product amily
standard: Immunity requirements or components o re,
intruder, hold up, CCTV, access control and social alarm
systems.
EN 50130-5:2011 Alarm systems. Environmental test methods.
EN 50131-1:2006+A1:2009 Alarm systems. Intrusion and hold-up systems. System
requirements.
EN 50131-3:2009 Alarm systems. Intrusion and hold-up systems. Control and
indicating equipment.
EN 50131-5-3:2005+A1:2008 Alarm systems. Intrusion systems. Requirements or
interconnections equipment using radio requency techniques.
EN 50131-6:2008 Alarm systems. Intrusion systems. Power supplies.
EN 50136-1:2012 Alarm systems. Alarm transmission systems and equipment.
General requirements or alarm transmission systems.
EN 50136-2:2013 Alarm systems. Alarm transmission systems and equipment.
Requirements or Supervised Premises Transceiver (SPT).
EN 61000-3-2:2006+A1+A2 Electromagnetic compatibility (EMC) — Part 3 – 2: Limits —
Limits or harmonic current emissions.
EN 61000-3-3:2013 Electromagnetic compatibility (EMC) - Part 3-3: Limits-
Limitation o voltage changes, voltage fuctuations and ficker
in public low-voltage supply systems, or equipment with
rated current ≤16 A per phase and not subject to conditional
connection.
EN 61000-6-4:2007 Emission standard or industrial environments.