Select your MicroLogic X control unit www.se.

com

Protections
Functions of protections

The MicroLogic X control unit is suitable for different systems of voltage, three or four wires up to 690 V AC, 50/60 Hz
and for all earthing systems as defined per IEC or North American standards (TNC, TNS, TT, IT, HRG).

MicroLogic 2.0 X
Long-time ANSI 49RMS/51
Current setting (A) Ir = In x … Ir = 0.4 In to In, step 1 A
B
DB419088.eps

Tripping between 1.05 and 1.20 Ir


Time setting tr = 0.5 s to 24 s, step 0.5 s for 6 Ir
Time setting exemple: Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
time delay (s) Accuracy: 0 to -20 % 6 x Ir 0.5 [1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.34 [2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory After tripping
Instantaneous ANSI 50
Pick-up (A) Isd = Ir x … Isd = 1.5 to 10 Ir, step 0.5 Ir [4]
Accuracy: ±10 %
Operating time (ms) Non tripping time: 20
Max breaking time: 80

MicroLogic 5.0 X - 6.0 X - 7.0 X


Long-time ANSI 49RMS/51
Current setting (A) Ir = In x … Ir = 0.4 In to In, step 1 A
DB419089.eps

Tripping between 1.05 and 1.20 x Ir


Time setting tr = 0.5 s to 24 s, step 0.5 s for 6 Ir
Time setting exemple: Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
time delay (s) Accuracy: 0 to -20 % 6 x Ir 0.5 [1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.34 [2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory After tripping
Short-time ANSI 50TD/51
Pick-up (A) Isd = Ir x … Isd = 1.5 Ir to 10 Ir, step 0.5 Ir [4]
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time at 10 x Ir non tripping time (ms) 20 80 140 230 350
I2t Off or I2t On max breaking time (ms) 80 140 200 320 500
Instantaneous ANSI 50
Pick-up (A) Ii = In x … Ii = 2 In to 15 In, step 0.5 In [4] and OFF protection
Accuracy: ±10 %
Ii tripping mode Standard Fast
Operating time non tripping time (ms) 20 0
max breaking time (ms) 50 30

MicroLogic 6.0 X
Earth fault ANSI 50N-TD/51N
Pick-up (A) Ig = In x … Ig = 0.2 [3] In to In, step 0.1 In [4] and OFF protection
DB419090.eps

Accuracy: ±10 %
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time non tripping time (ms) 20 80 140 230 350
max breaking time (ms) 80 140 200 320 500

MicroLogic 7.0 X
Residual earth ANSI 50G-TD
leakage (Vigi)
Sensitivity (A) IΔn 0.5 A to 30 A, step 0.1 A
DB419091.eps

Accuracy complies with IEC/EN 60947-2 Annex B


Time delay Δt (ms) Settings 60 150 230 350 800
non tripping time (ms) 60 150 230 350 800
max breaking time (ms) 140 230 320 500 1000
[1] 0 to -40 % [4] F
 iner resolution settings are possible with EcoStruxure Power Commission
[2] 0 to -60 % software and Ecostruxure Power Device App app.
[3] 0.3 In to In for In y 400 A

B-8