Micrologic ACB Sitting
Micrologic ACB Sitting
com
Protections
Functions of protections
The MicroLogic X control unit is suitable for different systems of voltage, three or four wires up to 690 V AC, 50/60 Hz
and for all earthing systems as defined per IEC or North American standards (TNC, TNS, TT, IT, HRG).
MicroLogic 2.0 X
Long-time ANSI 49RMS/51
Current setting (A) Ir = In x … Ir = 0.4 In to In, step 1 A
B
DB419088.eps
MicroLogic 6.0 X
Earth fault ANSI 50N-TD/51N
Pick-up (A) Ig = In x … Ig = 0.2 [3] In to In, step 0.1 In [4] and OFF protection
DB419090.eps
Accuracy: ±10 %
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time non tripping time (ms) 20 80 140 230 350
max breaking time (ms) 80 140 200 320 500
MicroLogic 7.0 X
Residual earth ANSI 50G-TD
leakage (Vigi)
Sensitivity (A) IΔn 0.5 A to 30 A, step 0.1 A
DB419091.eps
B-8