A
11KV HT OUTDOOR PANEL (GENERAL TECHNICAL PARTICULAR) 11KV HT OUTDOOR PANEL (GENERAL TECHNICAL PARTICULAR ) A
01 SYSTEM PARAMETER:- 05 PAINTING:-
a) MAIN SYSTEM 3 PHASE , 3 WIRE, AC 50Hz a) SURFACE FINISH EP POWDER COATING STRUCTURE FINISH WITH 7 TANK
PRE-TREATED PROCESS
b) RATED OPERATIONAL VOLTAGE 12 kV
b) PAINT SHADE INSIDE RAL-7032
c) SYSTEM FAULT LVEL 20kA FOR 3 SEC.
c) PAINT SHADE OUTSIDE RAL-7032
d) APPLICABLE STANDARD IEC-62271-200
d) BASE FRAME BLACK
02 CONSTRUCTION:-
B e) COATING THICKNESS APPROX 60-80 MICRONS B
a) LOCATION / MOUNTING OUTDOOR INSTALLATION, FLOOR (FREE STANDING)
06 CONTROL TERMINALS:-
b) LIFTING ARRANGEMENT LIFTING ANGLE
a) DISCONNECTING TYPE CT's
c) FUTURE EXTENSION EXTENDIBLE ON EITHER SIDE
b) SCREW TYPE AC/DC INCOMINGS & PT SECONNDRY
d) DEGREE OF PROTECTION IP-55
e) LOAD BEARING MEMBERS 2.0 mm CRCA c) NON-DISCONNECTION TYPE FOR REST CONTROL CIRCUIT
f) NON-LOAD BEARING MEMBERS 1.6 mm CRCA 07 MINIMUM RECOMMENDED ACCESS AREA:-
g) EQUIPMENT MOUNTING PLATE 2.0 mm CRCA a) FRONT 1500mm
C h) UNDRILLED REMOVAL GLAND PLATE 3.0 mm CRCA FOR MULTI CORE POWER CABLES b) REAR & TOP 1000mm C
j) BASE FRAME 50mm c) FROM L.H.S & R.H.S 600mm
03 BUS BAR:-
08 THE APPROX CLEARREANCE BETWEEN VCB INCOMING/OUTGOING LINKS SHALL BE:-
a) MAIN BUS BAR SIZE & MATERIAL ALIMUNIUM EC GRADE 63401 -1 x 50 x 12 SQ.MM. PER PHASE FOR MAIN
a)PHASE TO PHASE 110mm APPROX.
b) EARTH BUS BAR SIZE & MATERIAL ALIMUNIUM EC GRADE 63401 -1 x 50 x 6 SQ.MM. FOR MAIN EARTH
b)PHASE TO EARTH 80mm APPROX.
b) P.T DROPER SIZE & MATERIAL ALIMUNIUM EC GRADE 63401 -1 x 25 x 3 SQ.MM. FOR P.T. DROPPER
c) BUS BAR INSULATION HEAT SHRINKABLE PVC SLEEVE FOR BUS BAR 09 GASKETS:-
04 WIRING:- a) EPDM RUBBER FOR DOOR
D D
a) INSULATION GRADE 1100V b) EPDM FOAM FOR TOP- BOTTOM PLATE COVER
b) TYPE FRLS 10 FERRULES BLACK LETTER ON WHITE TUBE
c) AC VOLTAGE CIRCUIT 1.5 sqmm RED, YELLOW, BLUE & BLACK 11 NAME PLATE COMPUTRISED ALIMUNIUM ON EACH FEEDER AND PANEL IT SELF
d) CURRENT CIRCUIT 2.5 sqmm RED, YELLOW, BLUE & BLACK WITH WHITE LETTER ON BLACK BACKGROUND
e) CONTROL CIRCUIT: PHASE 1.5 sqmm RED 12 CUBICLE ILLUMINATION LED LAMP
f) CONTROL CIRCUIT: NEUTRAL 1.5 sqmm BLACK 13 HEATING SPACE HEATER WITH THERMOSTAT
g) DC CIRCUIT 1.5 sqmm GREY
14 CABLE ENTRY BOTTOM
h) GROUNDING 2.5 sqmm GREEN
15 APPROXIMATE WEIGHT OF SWITCHGEARS 500kgs./Vert.
E E
16 DANGER PLATE SHALL BE PROVIDED AT REAR SIDE OF PANEL
17 GIVEN THE SYMMETRY OF RELAYS & METERS, THEIR CUTOUT POSITION MAY BE CHANGE DURING MANUFACTURING
18 SPARE CONTROL TERMINAL SHALL BE PROVIDED AS PER SCHEMATIC DIAGRAM
NAME TITLE GENERAL NOTES JOB NO SR / 24-25 / 0810
F DRAWN ATUL YADAV Plot No. 126A, Sector 59, HSIIDC Industrial Estate PROJECT 12kV 800A, 20kA ABB VD4 OUTDOOR TYPE VCB PANEL REV R0 DATE 25.10.2024 F
FBD 121004 (INDIA) Email ID - [email protected]
CHECKED S.B CLIENT M/S AMBIENCE INTERIORS PVT LTD SHEET NO. 3 Of 15
SCALE : NTS
APPROVED S.B NO. OF SHEETS 15
1 2 3 4 5 6 7 8