Modelamiento de Generadores
Modelamiento de Generadores
4
Synchronous Machine: Steady State
and Transient Operations
4.1 INTRODUCTION
One of the important elements of a powers system is the synchronous generators, which greatly
influences the system behaviour during both steady-state and transients conditions. The
synchronous machine model in steady-state and transient conditions are presented in this
chapter.
FGH IJK
dt
p
\ Ea = Emax cos wt - ...(4.2)
2
Synchronous Machine: Steady State and Transient Operations 81
FG P IJ FG n IJ
f= H 2 K H 60 K
s
...(4.6)
Ic = Imax
FH
sin G wt - f -
4pI
JK
3
From eqn. (4.2), it is seen that the generated emf Ea is maximum when rotor magnetic axis
is under phase a. In Fig. 4.1, when line pq reaches the axis of coil aa¢, current in phase a reaches
it maximum value. At any instant of time, each phase winding of synchronous machine produces
a sinusoidally distributed mmf wave with its peak along the axis of the phase winding. These
mmf amplitudes are proportional to the instantaneous value of the phase current, i.e.,
Fa = K.Ia
Fb = K.Ib ...(4.8)
Fc = K.Ic
Using eqns. (4.8) and (4.7) we get,
Fa = Fm sin (wt f)
FGH 2p I
J
3K
Fb = Fm sin wt - f - ...(4.9)
FH 4pI
sin G wt - f - J
Fc = Fm
K
3
where Fm = K.Imax ...(4.10)
where K is proportional to the number of armature turns per phase and is a function of the
winding type. Now the resultant mmf may be obtained by projecting these mmf on line pq and
obtain the resultant in-phase and quadrature-phase components. The resultant in-phase
components are
82 Electrical Power Systems
LM FG IJ FG IJ
H K H K
2p 2p
N
Fp = Fm sin(wt f) cos(wt f) + sin wt - f -
3
cos wt - f -
3
FG IJ FG IJ OP
H K H KQ
4p 4p
+ sin wt - f - cos wt - f -
3 3
LM FG IJ FG IJ OP
H K H KQ
Fm 2p 4p
\ Fp =
2 N
sin 2 (wt - f) + sin 2 wt - f -
3
+ sin 2 wt - f -
3
\ Fp = 0 ...(4.11)
The sum of quadrature components results in
LM FG IJ FG IJ
H K H K
2p 2p
NF
Fq = Fm sin(wt f)sin(wt f) + sin wt - f -
4p I F 4pI O
3
sin wt - f -
3
+ sinG wt - f - J sinG wt - f - J
H 3K H 3 K PQ
3
\ Fq = F ...(4.12)
2 m
Therefore, resultant armature mmf or stator mmf becomes
3
Fs = Fp + Fq = Fm ...(4.13)
2
We therefore conclude that the resultant mmf has a constant amplitude perpendicular to
line pq.
Field alignment for synchronous generator is shown in Fig. 4.2 using space vectors to
represent the different fields.
At no load (armature current is zero), the field mmf Fr produces the no-load generated emf
E and this voltage is proportional to the field current known as excitation voltage. It is worth
mentioning that in Fig. 4.2 mmfs are space vectors whereas the emfs are time phasors.
When the synchronous generator is loaded, i.e., the armature is carrying balanced three
phase currents. The interaction of armature mmf and the field mmf, known as armature
reaction and produced resultant air gap mmf Fsr. Fsr is responsible for the resultant air gap flux
fsr which induces the generated emf on load Esr. Fs induces the emf Ear, known as the armature
reaction voltage. The voltage Ear leads the armature current Ia by 90° and thus can be represented
by a voltage drop across a reactance xar due to the current Ia. xar is known as armature reaction
reactance.
From Fig. 4.2,
E = Esr + j xar Ia ...(4.14)
Esr = V + raIa + j xl Ia ...(4.15)
From eqns. (4.14) and (4.15), we get
E = V + {ra + j(xl + xar)}Ia
\ E = V + {ra + jxs)Ia ...(4.16)
where xs = (xl + xar) is known as synchronous reactance.
The cosine of the angle between Ia and V represents the power factor (cos q) at the generator
terminals. The relative positions of Fr and Fsr dictates the action of the synchronous machine.
When Fr is ahead of Fsr by an angle dr, the machine is operating as a generator and when Fr falls
behind Fsr, the machine will act as a motor. Figure 4.3 shows equivalent circuit of nonsalient
pole synchronous machine.
Figure 4.4 shows the phasor diagram of the generator for lagging, unity and leading power
factors.
|E||V| |V|2
P3 f = 3 cos(b - d ) -3 cos b ...(4.21)
|Z s| |Z s|
|E||V| |V|2
Q3 f = 3 sin(b - d) -3 sin b ...(4.22)
|Z s| |Z s|
If ra is neglected, then Zs = jxs and b = 90º,
Therefore,
|E||V|
P3 f = 3 sin d ...(4.23)
Xs
|V|
Q3 f = 3 (|E|cos d -|V|) ...(4.24)
Xs
Example 4.1: A 50 MVA, 13.8 kV, three-phase, 50 Hz synchronous generator has a synchronous
reactance of 3 W/phase and ra » 0. One generator is delivering rated power at a 0.85 pf lagging
at the rated terminal voltage to an infinite bus.
(a) Compute the excitation voltage per phase E and the power angle d.
(b) With the excitation held constant at the value found in (a), the driving torque is reduced
until the generator is delivering 22 MW. Determine the armature current and the power
factor.
(c) If the generator is operating at the excitation voltage of part (a), what is the maximum
power the machine can deliver before losing synchronism?
Solution:
(a) cos q = 0.85 \ q = 31.8º
S3f = 50 31.8 º = (42.5 + j26.34) MVA
Synchronous Machine: Steady State and Transient Operations 85
13.8
\ V= = 7.96 kv
3
Using eqn. (4.18),
S3*f 50 -31.80 ´ 10 3
Ia = = Amp.
3V * 3 ´ 7.96 0 º
\ Ia = 2093.8 -318
. º Amp.
Using eqn. (4.16)
( j3) * 2093.8
E = 7.96 + -318
. º
1000
\ E = 7.96 + 6.28 58.2 º = 1127
. + j 5.33
\ E = 12.46 25.3º kV.
Therefore the excitation voltage magnitude is 12.46 kv and power angle is 25.3º.
Example 4.2: A 80 MVA, 69.3 kV, three-phase, synchronous generator has a synchronous
reactance of 10 W per phase and ra » 0. The generator is delivering rated power at 0.8 pf lagging
at the rated terminal voltage to an infinite bus bar. Determine the magnitude of the generated
emf per phase and the power angle d.
Solution:
cos q = 0.8 \ q = 36.87º
69.3
The rated voltage per phase is V = kV = 40.01 kV
3
\ V = 40.01 0 º kV
86 Electrical Power Systems
25
The bare power is SB = = 8.333 MVA
3
FG 13.8 IJ 2
E B2 H 3K
The base impedance is ZB = =
FG 25 IJ
SB
H3K
\ ZB = 7.6176 W .
(b) The synchronous reactance is
xs = xs(pu) × ZB = 1.2 × 7.6176 = 9.14112 W .
(c) The resistance per phase is
R = R (pu) × ZB = 0.02 × 7.6176 = 0.1523 W
Note that all the impedance value are on per phase basis.
|E||V| 12 ´ 9.988 1
P= sin d = ´ MW = 6.658 MW.
xs 9 2
|E||V| 12 ´ 9.988
\ P= sin 90 º = = 13.317 MW.
x 9
Maximum these-phase power output of the alternator
F 1 + 1 + 1 IJ
+G
-1
x d² = x l
Hx x x K
a f d
...(4.32)
The direct axis subtransient reactance xd² is only used if the initial current is important, for
example to determine the short-circuit rating of circuit breaker.
The short-circuit subtransient time constant of damper winding is very small (about 0.03 to
0.04 seeads) and this component of current decays very quickly.
Therefore, one can ignore the branch of the equivalent circuit which takes into account the
damper winding. Equivalent circuit is shown in Fig. 4.10.
The equivalent reactance of Fig. 4.10 is known as short circuit transient reactance and is
given by
FG 1 + 1 IJ -1
x d¢ = x l +
Hx x K
a f
...(4.33)
xd = xl + xa ...(4.34)
92 Electrical Power Systems
Similar equivalent circuits can be obtained for reactances along the quadrature axis. These
reactances, x²q, x¢q, and xq may be considered for cases when the circuit resistance results in a
power factor above zero and the armature reaction is not totally on the direct axis.
The armature current following sudden short circuit to the armature of an initially unloaded
machine can be expressed as:
LMF 1 - 1 I e FG 1 - 1 IJ e OP
MNGH X ¢¢ X ¢ JK
-t t d¢¢ - t t d¢
1
ia(t) = 2 Eo
d d
+
H X¢ X K
d d
+
Xd PQ
sin (wt + d ) ...(4.35)
Where
t²d = direct axis short-circuit subtransient time constant
t¢d = direct axis short-circuit transient time constant.
Therefore, the maximum rms current at the beginning of the short circuit is
Synchronous Machine: Steady State and Transient Operations 93
FG E IJ + FG 2 E IJ
2 2
H X ¢¢ K H X ¢¢ K
max o o
\ iasy = ...(4.40)
d d
from which
FG E IJ
H X ¢¢ K
max o
iasy = 3 ...(4.41)
d
The momentary duty of a circuit breaker is given in terms of the asymmetrical short-circuit
current.
Fig. 4.12: (=) Single line diageram of a loaded generator (>) Phasor diagram.
are to be made for a fault at F, at the motor terminals. Figure 4.13(b) shows the circuit
considering transient reactances (or subtransient reactances if subtransient currents are of
interest) in series with voltages behind transient reactances.
Figure 4.13 (c) shows the Thevenins equivalent circuit. This circuit comprises prefault
voltage V0 in series with the passive Thevenins impedance network. Figure 4.13 (d) shows the
Thevenin equivalent of the system feeding the fault impedance.
( X dg
¢ + X ¢)
DIm = . If ...(4.45)
( X dg
¢ + X ¢ + X dm
¢ )
Postfault currents and voltages are obtained using superposition:
Igf = Io + DIg ...(4.46)
Imf = Io DIm (in the direction of Io)
Synchronous Machine: Steady State and Transient Operations 95
Postfault voltage
Vf = Vo + (jXTH If ) = Vo + DV ...(4.47)
EXERCISE
4.1. A three phase synchronous generator produces an open circuit line voltage of 6000 volt when the
dc exciting current is 50 Amp. The ac terminals are then shrot circuited, and the three line currents
are found to be 660 Amp. Calculate (a) the synchronous reactance per phase (b) the terminal
voltage if three 12 ohm resistors are connected in Y across the terminals.
Ans. (a) 5.248 ohm (b) 5.5 kv.
4.2. A three phase, 50 Hz synchronous generator is driven at constant synchronous speed by a prime
mover. The armature windings are initially open-circuited and field voltage is adjusted so that the
armature terminal voltage is at the rated value (i.e., 1.0 pu). The machine has x²d = 0.15 pu,
x¢d = 0.40 pu and xd = 1.20 pu. Determine the steady state, transient and subtransient short circuit
currents.
Ans. 0.833 pu, 2.50 pu, 6.67 pu