ROC 2315 Operation Manual CCT 7320
ROC 2315 Operation Manual CCT 7320
ROC 2315 Operation Manual CCT 7320
User Manual
(Version 21)
1. Overview......................................................................................................................1
2. Features....................................................................................................................... 1
3. Technical Data............................................................................................................. 3
3.1 Operating Environment.......................................................................................3
3.2 Nominal Diameter...............................................................................................3
3.3 Pressure...............................................................................................................3
3.4 Measuring Range Ratio.......................................................................................4
3.5 Accuracy.............................................................................................................. 4
3.6 Repeatability....................................................................................................... 4
3.7 Explosion-proof Grade........................................................................................ 4
3.8 Shell Material...................................................................................................... 4
3.9 Electrical Performance Indicators.......................................................................4
4. Introduction.................................................................................................................7
4.1 Working Principle................................................................................................ 7
4.2 Working Principle Diagram................................................................................. 7
4.3 Structure Drawing............................................................................................... 8
4.4 Dimension........................................................................................................... 8
4.5 Selection of Flow Meter......................................................................................9
5.Installation..................................................................................................................11
5.1 Straight Pipe Requirements:............................................................................. 12
5.2 Pipeline Requirements:.....................................................................................12
5.3 Bypass Pipe Requirements:...............................................................................12
5.4 Environment Requirements:.............................................................................12
5.5 Impurities in the Medium:................................................................................12
5.6 Installation Place:.............................................................................................. 12
5.7 Installation and Welding Requirements:.......................................................... 12
5.8 Grounding:........................................................................................................ 12
5.9 Explosion Proof Requirements:........................................................................ 13
5.10 Installation Diagram:.......................................................................................13
6. Flow Meter Display/Parameters Setting...................................................................13
6.1 Working Condition............................................................................................ 13
6.2 Function Description of Keys............................................................................ 14
7. Terminal Structure & Connection Instruction of Flow meter.................................. 15
7.1 Connection........................................................................................................ 15
7.2 External Terminal Definition............................................................................. 15
7.3 Output Wiring Instructions...............................................................................16
8. Application Note....................................................................................................... 18
9. Notification for Explosion-proof Products................................................................19
9.1 Intrinsically Safe Flow Meter Should Follow the Following Items................... 19
9.2 Explosion-proof Flow Meters Should Follow the Following Items:.............. 20
10. Maintenance and Troubleshooting.........................................................................20
11. Transportation and Storage.................................................................................... 22
11.1 The Flow Meter Should be Well Packed.........................................................22
11.2 The Storage Location Should Meet the Following Conditions.......................22
12. Unpacking and Inspection...................................................................................... 22
12.1 Check the Integrity of The External Packaging When Unpacking..................22
12.2 Accessories......................................................................................................22
13.Communication Protocol(RTU) (V1.0)..................................................................... 22
13.1 Data Format Description.................................................................................22
13.2 Command Description.................................................................................... 23
1. Overview
The gas turbine flow meter is a precision measuring instrument used for gas flow
measurement.It has small pressure loss, high accuracy, and low dynamic flow, great
anti-vibration and anti-pulsation performance, wide range ratio, excellent low and
high-pressure measurement performance, multiple signal output methods and low
sensitivity to fluid disturbances.
Gas turbine flow meter take into account the compressibility of gases, and the
correlation between volume, temperature and pressure of the medium. To convert
Process Work Condition medium to Standard Condition, temperature and pressure
sensors are added to track temperature and pressure changes of the measuring
medium.
Gas turbine flowmeters are widely used in gas metering and gas pressure regulating
stations for petroleum gas, chemical gas, electric power and industrial boilers, as
well as gas transmission and distribution pipeline networks, urban natural gas
metering. It is the preferred instrument for trade settlements.
2. Features
●2.1 Advanced rectification technology assures the reliability of metering accuracy
under unsatisfactory installation conditions such as short front and rear straight pipe
sections, vibrations, or large variations of flow rate;
● 2.2 The advanced dust-proof structure effectively prevent the rapid wear and
stuck of bearing caused by the impurities in the medium;
●2.5 Built-In temperature and pressure sensors can measure temperature, pressure
and flow rate of gases. The sensors are used to do compensation for temperature
and pressure change automatically. Instantaneous flow and accumulated flow are
displayed in normal condition units.
● 2.6 The intrinsically safe and flameproof circuit design is suitable for different
explosion-proof requirements;
●2.9 According to user needs, the GPRS network function can be provided to realize
low-cost, long-distance wireless data real-time transmission; IoT interface function is
reserved to realize the IoT function.
●2.10 Internal battery low-voltage alarm reminds users to replace batteries in time;
●2.11 Intelligent flow Totalizer can rotate 350° counterclockwise, convenient for
data reading in different directions.
●2.12 Time display and real-time data storage ensure that the internal data will not
be lost and can be stored permanently.
● 2.13 Large-screen LCD, displaying rich and clear contents; The LCD screen of the
Totalizer can withstand a high temperature of 80℃.
●2.14 Flow upper limit and pressure upper alarm error display and record feature,
allow users to analyze flow patterns.
2
● 2.15 Working modes can be switched automatically, battery-powered, two-wire
system, and three-wire system.
●2.16 When the system module fails, it will display the fault content and initiate the
corresponding mechanism.
● 2.17 Diversified pressure ports, supports digital pressure sensor and pressure
sensor; PT100 or PT1000 temperature sensors are supported.
● 2.19 Unique reverse thrust structure design reduces and balances the bearing
force, ensuring a reliable long-term use of the bearing.
● 2.20 The unique pressure balance design of the sealed chamber can effectively
reduce wearing or stuck of the bearing caused by dust or impurities.
3. Technical Data
3.1 Operating Environment
3.3 Pressure
(0.5~4.0) MPa, higher pressure versions gas turbine flow meter can be manufactured
upon request.
3
3.4 Measuring Range Ratio
Under standard environmental conditions (P=101.325kPa, T=293.15K), the range can
reach 40:1 or wider.
(*Note: For some smaller diameter turbine flow meters, the ratio will be reduced).
3.5 Accuracy
(*Note: Qmin is the minimum flow rate that can be measured within the flow rate
range, and Qmax is the maximum flow rate that can be measured within the flow
rate range.
Special order meters are delivered according to 1.5 grades, and the other accuracy
grades need to be specified when ordering)
3.6 Repeatability
Better than ±0.2%.
5
3.9.8 Flow Range
4. Introduction
4.1 Working Principle
When the gas through the flow meter, it is rectified and accelerated as it passes
through the integrated two-stage rectifier, then it acts on the turbine blades at a
certain angle to the flow direction. Under the momentum of the gas, because the
turbine blades are at a certain angle with the flow direction of the gas, the turbine
generates a rotational torque at this time, the turbine begins to rotate after it
overcomes the resistance torque and the friction torque.
When the torques are balanced, the rotation speed is constant, and the turbine
rotation angular velocity has a linear relationship with the flow rate. Using the
principle of electromagnetic induction, a rotating turbine drives the top magnetizer
of the signal generator to periodically change the magnetic resistance, so that the
magnetic field also changes accordingly, thereby inducing a pulse signal proportional
to the fluid volume flow.
The signal is amplified by the preamplifier, and after shaping, the pressure and
temperature signals detected by the pressure sensor and the temperature sensor
are input to the flow totalizer for calculation processing and converted into a flow
value, which directly displays the standard instantaneous volume flow and volume
total flow.
7
4.3 Structure Drawing
4.4 Dimension
8
Nominal Dia. L D K N-∅h H W Notes
In Formula:
Qn: Corrected volume flow (m3/h)
Qg: Uncorrected volume flow (m3/h)
Pa: Local atmospheric pressure (kPa)
Pg: Gauge pressure at the pressure detection point of the flowmeter (kPa)
Pn: Standard atmospheric pressure (101.325kPa)
Tn: Absolute temperature under standard state 293.15K (20℃)
Tg: The absolute temperature of the medium (273.15K+T)
T: Celsius temperature of the measured medium (℃)
Zn: Media compressibility under standard conditions
Zg: Media compression factor under working conditions
(*Note: For natural gas Zn/Zg=(FZ)2, FZ is the super compressibility factor, calculated
9
according to the formula in China National Petroleum Corporation ’ s standard
SY/T6143-1996) (circuit)
In Formula:
Tg, Pg, Pa same as above
Qg is working condition volumetric flow
Qn is the standard volumetric flow
The same we can get the min volumetric flow is 236 m3/h
Thus we need to choose DN150mm gas turbine flow meter.
In Formula:
ρn:Density of gas in standard state
△Pmax:Max. pressure lose in standard state(medium is dry air)
(20℃,101.325kPa, ρ=1.205kg/m3)
Pa:Local atmospheric pressure(kPa)
Pg:Medium meter pressure(kPa)
Pn:Standard atmospheric pressure(kPa)
Tn:Absolute temperature under standard condition(273.15+20℃)
Tg:Absolute temperature under working condition(273.15+T)
T:Tested medium temperature(℃)
Zn:Gas compressibility under standard conditions
Zg:Gas compressibility under working conditions
Q:flow under working condition(m3/h)
Qmax:Max flow under working condition(m3/h)
5.Installation
For high accuracy measuning, gas turbine flow meter should be installed correctly.
11
5.1 Straight Pipe Requirements:
1)Flow meter should be installed on the pipe horizontally(The inclination is within 5°).
The axis of the flow meter should be concentric with the axis of the pipeline during
installation, and the flow direction should be same as flow meter's
measuredirection.
2)There should have straight pipe not less than 2D upstream of the flow meter. If it's
possible, it is recommended that the upstream straight pipe section be 20D and the
downstream be 5D.
5.8 Grounding:
Flow meter should be grounded reliably, and it can not share ground wire with any
strong other current system.
12
5.9 Explosion Proof Requirements:
To ensure safety, please check whether the working environment of the
explosion-proof flow meter conforms to the user's explosion-proof requirements
and regulations. Please strictly abide by the national explosion-proof product
requirements during installation and using. User is not allowed to change the
connection method of the explosion-proof system and is not allowed to open the
front and back cover, pressure port and other components of the flow meter when
flow meter is working.
Main interface
①: Total Flow
②: Working Condition
③: Standard Condition
④: Pressure
⑤: Temperature
13
1) “OK”: The running status of the flow meter. If it displays “OK”, it means the flow
meter is working well. if it display“ERR”, please check the self check menu for more
information.
2) “OV”: The operating parameter of the instrument overflows. If the operating
parameter of the instrument overflows, it will display “OV”. If it is normal, it will
display empty (overflow includes the parameter that cannot be negative is negative,
and the value that cannot be zero is zero, and the data exceeds the display range);
3) “mA: The indicator of the current output overflow of the instrument, if the
current overflows, it will display “mA”, if it is normal it will be empty;
4) “II” and “III”: Operating power supply mode display. If it is in battery mode, the
current battery level will be displayed. When the two-wire current output is
connected, the number sign “II” will be displayed. If it is three-wire system, the
number sign “III” will be displayed.
5) “IR”:Remote control button prompt, when this symbol appears, it indicates that
the remote control button is available.
6) Wireless communication, prompting the communication signal strength;
7) Total amount: cumulative flow, the display value can retain 5 decimal places, the
maximum value is 999999999; the unit is m3, Nm3 is optional.
8) Flow rate under working conditions: the minimum display value is 3 decimal
places, and the maximum value is 99999m3/h.
9) Flow rate under standard conditions: the minimum displayed value is 3 decimal
places, and the maximum value is 99999Nm3/h.
10) Pressure: The minimum display value is 3 decimal places, the maximum value is
99999, and the unit Kpa and Mpa are optional.
11) Temperature: display value range is -50℃~+300℃;
12) Operation power supply mode display, and displays battery power.
Warning: Don’t open the cover when there is explosive gas on site!
1)The flow meter can receive processed signals and can supply power to the signal
processing board. The wiring is as followings:
VCC: supply power 3V
PIN: frequency In
GND: ground
3)Pressure Sensor:
IP+,pressure sensor power supply +
VP+,pressure sensor signal +
VP-,pressure sensor signal -
IP-,pressure sensor power supply -
16
2) Three-wire system current connection method:
17
5) RS485 Communication connection:
8. Application Note
8.1 The selection should be within the specified flow range to prevent long-term
overload operation to ensure the desired accuracy and normal service life.
8.2 When the flow meter is installed and put into operation, the front valve should
be opened slowly, and then the rear valve should be opened to prevent
instantaneous airflow from damaging the turbine.
8.3 Lubricating oil should be operated in accordance with the refueling sign. The
number of refueling depends on the cleanliness of the temperament, usually every 2
to 3 months.
8.4 Prevent the turbine from over-speeding due to pressure test, purging pipes or
exhaust, and the turbine running in reverse flow may damage the flow meter.
8.5 It is not allowed to open the front cover at will when the flow meter is running
(there is a circuit board in the cover, and an accidental short circuit will cause electric
sparks. When there is flammable and explosive gas at the scene, it will cause serious
accidents), and change the operating parameters (changing the parameters will
affect The normal operation of the flow meter).(Circuit)
8.6 Install gaskets carefully to ensure that no protrusions enter the pipeline to
prevent interference with normal flow measurement.
8.7 When the flow meter is calibrated, the pressure should be collected on the
18
pressure port of the flow meter. After the calibration is completed, the pressure port
bolt should be tightened in time to prevent air leakage during use.
8.8 The upper limit pressure should be correctly selected according to the actual
working pressure. The working pressure range of the corrector is required to be 20%
Pmax ~ Pmax. Too small a pressure will affect the measurement accuracy, and if the
upper limit pressure is too large, the pressure sensor will be damaged.(Circuit)
8.9 When the electronic volume corrector is in operation, it is not allowed to open
the back cover or change the internal related parameters, otherwise it will affect its
operation.(Circuit)
8.10 If the volume corrector outputs a 4-20mA current signal, in order to improve its
accuracy, the user should set the value corresponding to 20mA according to the
actual maximum value. (Circuit)
1) Ambient temperature:-20℃~+60℃.
2) Please contact manufacturer for repairs involving flameproof joints.
3) Measures should be taken to avoid the risk of ignition caused by electrostatic
charges on exposed non-metallic parts of the product.
4) There is no harmful gas corrosive to aluminum alloy at the installation site.
5) The shell grounding wire should be reliably grounded.
6) Strictly abide by “It is strictly forbidden to open the cover when power is on”
when using and maintaining on site.
7) The user shall not replace the parts of the product by himself.
8) When installing, the cable entry must be equipped with a cable entry device that
has been approved by the explosion-proof inspection and has a thread specification
of M16X1.5, the corresponding explosion-proof grade, and the temperature
resistance is not less than 90°C and is compatible with the product.
9) When installing, using and maintaining the product, the user must strictly abide
by the product instruction manual.
20
Flow rate is lower than the
starting flow
Impurities in the pipeline
jam the impeller
3.Pressure difference
Replace instrument or use
between the two ends of the
No display when gas smaller size
instrument is too large to
flows through the Clean Impurities
cause shock
flow meter Return to factory
4.The over-range causes the
over-speed to damage the
bearing
21
11. Transportation and Storage
12.2 Accessories
1) Filter gasket (1 piece)
2) Rubber gasket (1 piece)
3) Bearing lubricant (1 bottle)
22
13.1.1 Communication Mode
This meter adopts MODBUS RTU Format.
The protocol is used for data communication in master-slave query mode.
Note: T1, T2, T3, T4 are the time intervals between each frame, and the transmission
between two frames must be greater than the interval time.
13.1.3 Address
The address of the instrument is specified in the protocol as “0-255”, the “0” address
is used for broadcasting (this protocol does not support broadcasting), and the rest is
reserved.
31 30-23 22-0
S Level Code Tail Code
The 31st bit is the sign bit (S), 1 indicates that the number is negative, 0 otherwise;
30-23 bit,Total 8 bit level code;
22-0 bit,Total 23 bit tail code.
23
Command 3 Format As Below: (Read Register Command):
MODBUS Query:
MODBUS Response:
Example:
Query Respond
Domain Data(HEX) Domain Data(HEX)
Meter Address Code 01 Meter Address Code 01
Function Code 03 Function Code 03
Starting Address High (byte) 00 Byte Count 08
Starting Address Low (byte) 00 Register High (0001) 0C
Read Data Volume High (Byte) 00 Register Low (0001) E8
Read Data Volume Low (Byte) 04 Register High (0002) C2
Register Low (0002) FB
Register High (0003) C9
Register Low (0003) 26
Register High (0004) C3
Register Low (0004) 7B
CRC Check Parity bit CRC Check Parity bit
24
Data Definition
Register
Read-Write Address Length Data Type Discription
R 40001-2 2 SINGLE Medium Temperature (℃)
R 40003-4 2 SINGLE Medium Pressure(kPa)
R 40005-6 2 SINGLE Instant Flow(m3/h)
R 40007-8 2 SINGLE Nominal Instant Flow(Nm3/h)
Accumulative Flow Above
R 40009-10 2 SINGLE Hundred’s Digit
Accumulative Flow Below
R 40011-12 2 SINGLE Hundred’s Digit
R 40013-14 2 SINGLE Sensor Frequency(Hz)
R 40015-16 2 Retain Retain
R 40017-18 2 SINGLE Cv Values
R 40019-20 2 Backup Retain
Flow k factor: 1
25
Temperature 20℃
Pressure 800KPa
Working condition instantaneous flow 5.0037 m3/h;
Standard condition instantaneous flow 44.5095 Nm3/h
Total flow above hundred 3 Nm3
Total flow under hundred 60.4897 Nm3
Flow sensor frequency 50Hz
Flow K factor 1.000
Read register data (in this example, read the data displayed in the current converter)
Master request:
01 03 28 00 00 41 A0 00 00 44 48 16 84 40 A0 01 6A 42 32 00 00 40 40 74 5E 42 86
1C 24 42 48 00 00 FF 00 00 00 3F 80 00 00 00 00 9A 67
26
Flow coefficient communication modification method (modified by Modscan 32
software):
If the meter address is 1, write the coefficient 1.0, and send the data as follows:
Send: 01 10 00 55 00 02 04 00 00 3F 80 26 FC
01 10 Add, Command No
00 55 Write start add
00 02 Write length
04 Send data byte length
00 00 3F 80 K factor(Float)
26 FC CRC Check