Prefab wall analysis

Input data
Project
Date : 10/2/2024

Settings
Standard - safety factors
Materials and standards
Concrete structures : EN 1992-1-1 (EC2)
Coefficients EN 1992-1-1 : standard

Wall analysis
Active earth pressure calculation : Coulomb
Passive earth pressure calculation : Caquot-Kerisel
Earthquake analysis : Mononobe-Okabe
Shape of earth wedge : Calculate as skew
Allowable eccentricity : 0.333
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor for overturning : SFo = 1.50 [–]
Safety factor for sliding resistance : SFs = 1.50 [–]
Safety factor for bearing capacity : SFb = 1.50 [–]
Safety factor for sliding along geo-reinforcement : SFsr = 1.50 [–]
Geometry of structure
Slope of wall = 0.00 °
Width Height Offset Offs.(L) Offs.(R) Self w. Friction Cohesion Shear bear.cap.
No.
b [m] h [m] k [m] o1 [m] o2 [m] [kN/m3] [–] [kPa] Rs [kN/m]
9 6.00 2.40 0.00 0.00 0.00 25.00 1.000 0.00 0.00
8 6.00 2.00 0.00 0.00 0.00 23.50 1.000 0.00 0.00
7 7.00 1.60 0.00 0.00 0.00 23.50 1.000 0.00 0.00
6 7.00 1.60 0.00 0.00 0.00 23.50 1.000 0.00 0.00
5 8.00 1.60 0.00 0.00 0.00 23.50 1.000 0.00 0.00
4 8.00 1.60 0.00 0.00 0.00 23.50 1.000 0.00 0.00
3 8.50 1.60 1.00 0.00 0.00 23.50 1.000 0.00 0.00
2 9.50 1.60 1.00 0.00 0.00 23.50 1.000 0.00 0.00
1 10.50 1.00 0.00 0.00 0.00 23.50 - - -
Note: Blocks are ordered from bottom to the top

Basic soil parameters


ef cef  su 
No. Name Pattern
[°] [kPa] [kN/m3] [kN/m3] [°]

1 Gravel 40.00 1.00 20.00 11.00 20.00

All soils are considered as cohesionless for at rest pressure analysis.

1
[GEO5 - Prefab Wall (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Soil parameters
Gravel
Unit weight :  = 20.00 kN/m3
Stress-state : effective
Angle of internal friction : ef = 40.00 °
Cohesion of soil : cef = 1.00 kPa
Angle of friction struc.-soil :  = 20.00 °
Soil : cohesionless
Saturated unit weight : sat = 21.00 kN/m3

Backfill
Assigned soil : Gravel
Slope = 45.00 °

Geological profile and assigned soils


Thickness of layer Depth
No. Assigned soil Pattern
t [m] z [m]

1 - 0.00 ..  Gravel

Foundation
Type of foundation : soil from geological profile

Terrain profile
Terrain behind construction has the slope 1: 520.87 (slope angle is 0.11 °).

Water influence
GWT behind the structure lies at a depth of 2.15 m
GWT in front of the structure lies at a depth of 3.25 m
Subgrade at the heel is not permeable.
Uplift in foot. bottom due to different pressures is not considered.

Input surface surcharges


Surcharge Mag.1 Mag.2 Ord.x Length Depth
No. Action
new change [kN/m2] [kN/m2] x [m] l [m] z [m]
1 Yes permanent 30.00 on terrain
No. Name
1 Live Load
Resistance on front face of the structure
Resistance on front face of the structure is not considered.

Applied forces acting on the structure


Force Fx Fz M x z
No. Name Action
new edit [kN/m] [kN/m] [kNm/m] [m] [m]
1 Yes Bollard permanent -56.00 0.00 0.00 -5.33 0.00

2
[GEO5 - Prefab Wall (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Global settings
Settings of the stage of construction
Design situation : permanent

Verification No. 1 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -7.57 1751.55 5.52 1.000
Weight - earth wedge 0.00 -4.56 2.95 10.17 1.000
Weight - earth wedge 0.00 -8.12 11.81 9.33 1.000
Weight - earth wedge 0.00 -11.32 11.81 8.33 1.000
Active pressure 287.38 -5.43 278.72 9.66 1.000
Water pressure 135.30 -6.15 0.00 8.00 1.000
Live Load 89.20 -7.58 94.85 9.33 1.000
Bollard 56.00 -15.00 0.00 2.67 1.000
Verification of complete wall
Check for overturning stability
Resisting moment Mres = 13490.08 kNm/m
Overturning moment Movr = 3909.59 kNm/m

Safety factor = 3.45 > 1.50


Wall for overturning is SATISFACTORY

Check for slip


Resisting horizontal force Hres = 1814.39 kN/m
Active horizontal force Hact = 567.87 kN/m

Safety factor = 3.20 > 1.50


Wall for slip is SATISFACTORY

Overall check - WALL is SATISFACTORY

Dimensioning No. 1 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -7.19 1609.80 4.55 1.000
Weight - earth wedge 0.00 -3.56 2.95 9.17 1.000
Weight - earth wedge 0.00 -7.12 11.81 8.33 1.000
Weight - earth wedge 0.00 -10.32 11.81 7.33 1.000
Active pressure 254.60 -5.07 266.79 8.62 1.000
Water pressure 124.30 -5.65 0.00 7.00 1.000
Live Load 83.57 -7.05 92.81 8.31 1.000
Bollard 56.00 -14.00 0.00 1.67 1.000

3
[GEO5 - Prefab Wall (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Verification of construction joint above the block No.: 1
Check for overturning stability
Resisting moment Mres = 10603.16 kNm/m
Overturning moment Movr = 3366.59 kNm/m

Safety factor = 3.15 > 1.50


Joint for overturning stability is SATISFACTORY

Check for slip


Resisting horizontal force Hres = 1995.97 kN/m
Active horizontal force Hact = 518.47 kN/m

Safety factor = 3.85 > 1.50


Joint for slip is SATISFACTORY

Input data (Stage of construction 2)


Geological profile and assigned soils
Thickness of layer Depth
No. Assigned soil Pattern
t [m] z [m]

1 - 0.00 ..  Gravel

Foundation
Type of foundation : soil from geological profile

Terrain profile
Terrain behind construction has the slope 1: 520.87 (slope angle is 0.11 °).

Water influence
GWT behind the structure lies at a depth of 2.15 m
GWT in front of the structure lies at a depth of 3.25 m
Subgrade at the heel is not permeable.
Uplift in foot. bottom due to different pressures is not considered.

Input surface surcharges


Surcharge Mag.1 Mag.2 Ord.x Length Depth
No. Action
new change [kN/m2] [kN/m2] x [m] l [m] z [m]
1 No No permanent 30.00 on terrain
No. Name
1 Live Load
Resistance on front face of the structure
Resistance on front face of the structure is not considered.

Applied forces acting on the structure


Force Fx Fz M x z
No. Name Action
new edit [kN/m] [kN/m] [kNm/m] [m] [m]
1 No No Bollard permanent -56.00 0.00 0.00 -5.33 0.00