Duct Design and Installation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 61
At a glance
Powered by AI
The document discusses proper duct design and installation based on industry standards like ACCA manuals. Key factors for an efficient system include proper sizing, sealing, insulation, and layout.

Proper duct design involves estimating heating and cooling loads, determining airflow requirements, selecting register locations and sizing the ductwork to available pressure based on manuals like ACCA T and D.

Factors that contribute to an efficient duct system include low duct leakage through sealing, short runs with fewer larger diameters, insulation, and using metal ducts and fittings.

Duct Design and Installation

John Proctor, P.E. Proctor Engineering Group, Ltd. San Rafael, CA

1-888-455-5742 [email protected] www.proctoreng.com 2004 Proctor Engineering Group, Ltd.

Duct Design
ACCA Manuals J, T, and D or Equivalent

Proper Design & Selection Estimate Loads


1. Determine Design Heating Loads 2. Determine Design Cooling Loads Sensible and Latent 3. Determine the airflow required to each room

Proper Design

1. Determine the best locations for the air terminals (registers) Use ACCA Manual T 2. Design the duct system to the available pressure and minimize the effective length Use ACCA Manual D or Equivalent

A Good Duct Design Provides


Quiet Efficient Comfort

Recommended Velocity (in fpm)


Supply Duct Type Trunk Branch Outlet Return Grille Face Filter Grille Rigid 700 600 Size for Throw <500 <300 Flex 600 600 Return Rigid 600 400 Flex 600 400

Efficient
FAN WATT DRAW REDUCTION SUFFICIENT AIRFLOW LOW DUCT LEAKAGE
SEAL WITH MASTIC OR SNAP-DUCT PUT INSIDE THE CONDITIONED SPACE

LOW CONDUCTION LOSS


SHORT RUNS FEWER LARGER DIAMETER RUNS PUT INSIDE THE CONDITIONED SPACE USE METAL DUCT AND FITTINGS

Comfort
TEMPERATURE DIFFERENCE BETWEEN ROOMS < 2 F IDEAL 4F MAXIMUM SO USE A CONTINUOUS FAN?

NO

Why not just add an Electrically Commutated Motor (ECM) and use a continuous fan?
Continuous Fan 5000 Annual kWh 4000 3000 2000 1000 0 PSC Motor ECM Auto Fan

1. An ECM uses as much power running continuously as a PSC motor does running on Auto
(Scott Pigg, Wisconsin Study)

2. Continuous duct leakage losses and conduction losses 3. ECM motors are not magic When pressures are too high they can use more electricity and burnout

ECM Motors Maintain Airflow (up to a point) but can use more watts than a PSC
1,800 1,600 1,400 1,200 Airflow (CFM) Watts 1,000 800 600 400 200 0 0.0 0.2 0.4 0.6 0.8 1.0 Static Pressure (IW) ECM 800 700 600 500 PSC 400 300 200 100 0 0.0 0.2 0.4 0.6 0.8 1.0 Static Pressure (IW) ECM PSC

Comfort comes from a designed system


Duct System Must Be Designed to Deliver Correct Amount of Air to Each Supply Terminal AND Each Supply Terminal Must Be Carefully Sized and Located AND Each Supply Terminal Must Be Chosen With Adequate Mixing and Throw AND There Must Be an Adequate Return Path for Each Supply

Terminals
SUPPLY LOCATION (old recommendation) PERIMETER UP OUTSIDE WALL (HEATING) CEILING PARALLEL TO CEILING OUT TO WALLS (COOLING) HIGH INSIDE WALL PARALLEL TO CEILING TO OUTSIDE WALL (COOLING)

Returns Adequate Air Pathways


Return Type Single Advantages Disadvantages

Low Cost Potential for Inadequate Provides Accessible Filter Return Pathways (Pressure) Location Potential for Noise Low Surface Area Adequate Return Paths High Cost Excessive Duct Leakage Unnecessary in Open Floor Plan

Every Room

Return Location
Mixing in a Room is Largely Unaffected by Return Location Return Location MAY Have a Small Effect on House Level Stratification House Level Stratification is More Affected by AC Size

Duct Design Considerations


WHAT DETERMINES FLOW THROUGH UNIT? EXTERNAL SYSTEM PRESSURE DROP = EQUIPMENT PRESSURE GAIN

AT DESIRED FLOW

External System Pressure Drop = Equipment Pressure Gain


Fan Pressure Gain External System Pressure Drop

Operating Point

Generic External System Pressure Drops


DEVICE Standard Filter High Efficiency Filter Humidifiers/Electric Heaters Supply Outlet Return Grille Balancing Damper Coil Duct System PRESSURE DROP .10 Clean .20 Clean .10 to .20 .03 .03 .03 Open .15 to .45 wet coil

What is left

Coil Pressure Drop

CFM 1000 1200 1400

Static Pressure (Wet Coil) 0.23 0.33 0.45

G2FD036(S,H)21(T)

Filter pressure drop is .05 0.24 in H2O Median is 0.15


Cooling Filter Pressure Drop
0.25 0.20 0.15 0.10 0.05 1 6 11 16 21 26 31 36 41 46 Number

in of w a te r

20" X 20" MERV 8 Air Filter


1 0.9

Static Pressure Drop

0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 200 400 600 800 1000 1200 New Filter Filter Loading

Air Flow (CFM)

Example Pressure Drop


DEVICE Supply Register Return Grille Balancing Damper Coil Total EXCLUDING DUCTS PRESSURE DROP .03 .03 .03 .33 wet coil

.42

Equipment Pressure Gain

.45 IWC at 1200 cfm

Cannot work only .03 IWC available for duct system


WHAT DETERMINES FLOW THROUGH UNIT? EXTERNAL SYSTEM PRESSURE DROP = EQUIPMENT PRESSURE GAIN

0.42 IWC + Ducts

0.45 IWC

AT DESIRED FLOW

1200 cfm

Stick with Smaller Air Handler Smaller Fan Motor

Solution
Keep smaller air handler Use a less restrictive coil (0.21 IWC) Drop the dampers External system pressure drop becomes:
Return Grille Supply Register Coil TOTAL .03 .03 .21 .27 + Ducts 0.45

Equipment Pressure
at Med. Hi and 1200 cfm

Available for ducts

0.45 0.27 = 0.18

Now we need to know the friction rate (IWC/100 ft.)


We have an available static pressure of 0.18 Inches of Water Column What do we want to divide that by to get the friction rate?

The Total Effective Length

How Long is the Duct System? (from an air molecule's view)


A 200 ft. straight pipe is 200 feet long

This 4 ft. section of pipe is how long?

Supply Boots
4-G
Fitting Number 4-G 4-J Effective Length 80 ft. 30 ft.

4-J

Supply Plenums and Takeoffs


Fitting Number 1-O 1-P with Vanes Effective Length 60 ft. 40 ft.

1-O

1-P

2-A
Downstream Branches 2-A 2-B 0 35 20 1 45 30 2 55 35

2-B
3 65 40 4 70 45 5 or + 80 50

A Simple Duct Design


4-G

10 ft.

Run 1 5 ft.

15 ft.

2-A 1-O
Plenum Trunk

2-B
Run 2

10 ft.

Furnace

4-J

A Less Simple Duct Design


550 CFM

4-J
20 ft.

4-J

4-J

4-J

18 ft.

Run 1

Run 2

12 ft.

160 ft EL Return

10 ft.

2-B
5 ft. 5 ft.

2-B 1-P 2-B


Run 3

2-B

2-B
5 ft.

5 ft. 5 ft. Trunk

5 ft.

Plenum

2-B
Run 6

12 ft.

12 ft.

Furnace

4-J

4-J
90 CFM

Calculate the Total Effective Length from the return grille to the supply register

A simple takeoff can be as little as 10 feet Or as much as 115 feet Through good design we got the overall equivalent length to 300 feet So we have 0.18 IWC available static pressure over 300 ft. The friction factor is .06 IWC per 100 ft (0.18/300 = 0.06)

Recommended Velocity (in fpm)


Supply Duct Type Trunk Branch Outlet Return Grille Face Filter Grille Rigid 700 600 Size for Throw <500 <300 Flex 600 600 Return Rigid 600 400 Flex 600 400

Why not just use 0.10 IWC /100 ft. Friction Rate on a Ductalator?
BECAUSE DESIGN VALUE FOR FRICTION RATE IS NOT ARBITRARY FRICTION RATE DESIGN VALUE DEPENDS ON AVAILABLE STATIC PRESSURE AND TOTAL EFFECTIVE LENGTH

Desirable Design
SHORT DUCT RUNS LOW STATIC PRESSURES INSIDE CONDITIONED SPACE GOOD THROW ON REGISTERS

Duct Installation
Put in what is designed Straight Leakless Proper Flow Proper Distribution

Duct Testing
Leakage Flow Distribution

Duct Leakage in Existing Homes


12% 10%
% of Sample

8% 6% 4% 2% 0% 5% 15% 25% 35% 45% 55% 65% 75% >80%


CFM 25 / Nominal Airflow
Sample size: 1210 (no mobile homes) Test method: Duct Blaster at 25 pa. (0.10WC) Source: CheckMe! database

Duct Sealing Saves Energy and Peak


Required Sensible Cooling (BTUh)
25,000

20,000

15,000

10,000
Manual J7 16% Supply Leakage, 11% Return Leakage 2%Supply Leakage, 11% Return Leakage 2% Supply Leakage, 3% Return Leakage

5,000

0
80 85 90 95 100 105 110 115 120

DUCT LEAKAGE TESTING


Total Leakage Leakage to Outside Supply Side Leakage Return Side Leakage Operating Leakage

TOTAL LEAKAGE SET-UP


REMOVE FILTERS MOUNT DUCT BLASTER @ AH OR RETURN GRILLE ALL SUPPLY REGISTERS COVERED ALL RETURN GRILLES COVERED DUCT TEST REFERENCE PRESSURE IN SUPPLY PLENUM (STATIC PRESSURE PROBE)

Duct Blaster Test Method


MEASURE CFM TO KEEP DUCTS AT 25 PA MEASURE CFM TO KEEP DUCTS AT 25 PA

DUCT TESTING PROCEDURE


KEEP FAN PRESSURE ABOVE 30 PASCALS (SWITCH FLOW RING IF NEEDED) FLOW RING SELECTION
OPEN RING 1 RING 2 RING 3 1,500 TO 500 800 TO 200 300 TO 75 125 TO 30

Duct Leakage Standards


CFM 25 as % of Cooling Nominal Flow
Nominal Flow as 400 CFM per ton 5%, 6%, 8%

CFM 25 as % of Actual Flow CFM 25 as % of Floor Area

Low Airflow
Arizona New Construction Blasnik et al. 1996

All of the audited forced air systems showed low air handler flow Danny Parker Florida Study 1997

Measuring Airflow
Temperature Split Method

Duct Blaster Flow Capture Hood Flow Grid


Coil Pressure Drop Fan Curve Pitot Tube Traverse Anemometer

AC Temperature Split
Run to steady state (15 minutes) Measure return wet bulb and dry bulb temperatures Measure the supply dry bulb temperature This is the most critical part of the procedure
System stabilized The measured temperatures as close to the mixed PLENUM AIR TEMPERATURES

55

80 67 wb

Determining Target Temperature Split


Target temperature split is not constant
Target temperature split varies with Return dry bulb Return wet bulb

Determine the target temperature split


Based on chart or slide rule

Maximum Temperature Split Table


50 23.9 24.9 26 27.1 52 23.6 24.7 25.8 26.9 54 23.1 24.2 25.3 26.4 27.5 Return Air Wet-Bulb (F) 56 58 60 62 64 22.5 21.7 20.7 19.5 18.2 23.6 22.8 21.8 20.6 19.3 24.7 23.9 22.9 21.7 20.4 25.8 25 24 22.8 21.5 26.9 26.1 25.1 23.9 22.5 28 27.2 26.2 25 23.6 28.2 27.2 26.1 24.7 28.3 27.2 25.8 66 16.7 17.7 18.8 19.9 21 22.1 23.2 24.3 68 14.9 16 17.1 18.2 19.3 20.4 21.5 22.5 70 13 14.1 15.2 16.3 17.4 18.5 19.6 20.6 72 12 13.1 14.2 15.3 16.4 17.5 18.6 74

Return Air DryBulb (F)

70 72 74 76 78 80 82 84

11.9 13 14.1 15.2 16.3

TrueFlow Flow Grid

Grid Installs in Filter Slot

Duct Blaster Test Method


Take supply static pressure with air conditioner running Block blower compartment from return system Install Duct Blaster on the blower compartment door Turn on air handler Adjust Duct Blaster speed to duplicate supply static Read airflow from Duct Blaster

Desired Air Flow


SHR Below 0.74 0.74 to 0.79 0.80 to 0.85 Above 0.85 CFM per Ton 300 350 400 450

Flow to Rooms
Within +- 10% +- 20% Max.

Write the Specifications Sign the Contract Breathe Easy --- NOT
Any equipment installed must perform as intended

These items are accomplished by human beings and are subject to error.

With Initial Feedback the Crews Learned Rapidly. With Continued Feedback They Maintained Good Savings When Feedback Was Removed the Savings Dropped to 30% of the Maximum
Measured Savings as a Percent of Achievable Savings (running average)

100% 80% 60% 40% 20% 0%


Program Startup, Learning Curve with Technician Feedback Production with Feedback M aintained Disaster when Feedback was Removed

You might also like