NFPA 82-1999 - Incinerators and Waste and Linen Handling Systems and Equip
NFPA 82-1999 - Incinerators and Waste and Linen Handling Systems and Equip
NFPA 82-1999 - Incinerators and Waste and Linen Handling Systems and Equip
3.1. Definitions. The three types of systems approved to handle waste and linen, each with separate fire safety criteria, are defined in
3.1.1 through 3.1.3.
3.1.1. Gravity Waste or Linen Chutes. An enclosed vertical passageway (riser) in a building, used for transferring trash or linen by
gravity to a room at the bottom or to an interface to a compactor. A gravity chute also can be used to interface with a pneumatic
transport system. Access of chute intake doors might or might not be limited to the use of keys.
3.1.2. Full Pneumatic Waste or Linen Conveying Systems. A closed system consisting of loading stations with inner doors and a
fire-rated, normally locked, outer (intake) door; normally closed air damper above the topmost loading station; transport piping,
both vertical and horizontal; waste or linen collector; fan with a fan damper; and a central process controller.
3.1.3. Gravity Pneumatic Waste or Linen Conveying Systems. A system using a combination of the gravity waste or linen chutes
defined in 3.1.1 and a pneumatic conveying system that receives the material from the chute by gravity. This system consists of
gravity chutes; a material damper to interface between the chute and the transport piping; the transport pipe; waste or linen
collector; fan with fan damper; and a central process controller.
Page 1 of 3
NFPA 82 1999 Edition
3.2.2.6. Lined Metal Waste Chutes. Metal waste chutes shall be permitted to be lined with low-duty refractory brick (as defined
in ASTM C27) not less than 2 ½ in. (63.5 mm) thick or equivalent castable refractories. All unlined steel chutes shall be
protected internally by automatic sprinklers. (See 3.2.5.1)
3.2.2.7. Chute Wall Thickness. Metal waste or linen chutes shall be made of stainless steel, galvanized steel or aluminum-
coated steel with no screws, rivets or other projections on the interior surface of the chute. Laps or joints shall be
designed so that the liquid will drain to the interior of the chute. The steel shall not be lighter than 16 U.S. gauge. Special
waste chutes designed to handle dense or heavy material over 10 lb/ft3 (1500 kg/m3) shall be made of steel not lighter
than 14 U.S. gauge.
3.2.2.8. Medium-Heat Chimneys. Listed medium-heat appliance chimney sections shall be acceptable for use as a trash chute.
3.2.2.9. Chute Discharge Doors. Gravity chutes shall be constructed so that the base opening of the chute or shaft, or both, shall
be protected by an approved automatic-closing or self-closing 1-hour fire door suitable for a Class B opening.
3.2.3. Chute Enclosure (Chase). Vertical waste or linen chutes in all stories above the storage or compacting room shall be enclosed
within a continuous enclosure constructed of noncombustible materials and extending from the ceiling of the storage or
compacting room to or through the roof so as to retain the integrity of the fire separation. The walls of the enclosure, or the
walls of the masonry chute, shall have a fire resistance of not less than 1 hour if the building is less than 4 stories and not less
than 2 hours if the building is 4 or more stories in height.
3.2.4. Chute Loading Doors.
3.2.4.1. General Access Gravity Waste Chutes. All chute loading doors into a waste chute shall be provided with a self-
closing, positive latching frame and gasketed fire door assembly approved for Class B openings and having a fire
resistance rating of not less than 1 hour. The door frame shall be fastened into the chute and the shaft wall. The design
and installation shall be such that no part of the frame or door projects into the chute. The area of each chute loading door
shall be limited to one-third of the cross-sectional area of a square chute and 44 percent of the area of a round chute.
3.2.4.2. Limited Access Gravity Chutes. All chute loading doors into a linen or waste chute shall be provided with a self-
closing, positive-latching frame and gasketed fire door assembly approved for Class B openings and having a rating of
not less than 1 hour. The door frame shall be fastened into the chute and the shaft wall. The design and installation shall
be such that no part of the frame or door projects into the chute. A key shall be required to open the door. The area of
each waste chute loading door shall be limited to two-thirds of the cross-sectional area of the chute. The area of each linen
chute loading door shall not exceed the cross-sectional area of the chute.
3.2.4.3. Service Opening Rooms. Every service opening shall be in a room or compartment that is separated from the other parts
of the building by a wall, partition, floor-ceiling assemblies having a fire resistance rating of not less than the required
rating of the chute enclosure. Openings into such a room or compartment shall be protected by approved self-closing
doors that are appropriate for protecting the openings and suitable for Class B openings, or not less than 1-hour partition
rating with a ¾ hour door.
3.2.4.3.1. The size of the opening room or compartment shall not be less than that required to maintain a minimum 6 in.
(152.4 mm) clearance between the opening loading door and the closed service opening room door.
3.2.4.3.2. Service Opening Room Key. If entrance to a limited-access service opening is gained by key, theservice opening
door shall not require a key to be opened. One opening or the other shall be keyed. Keying shall be required only
for limited-access installations.
Page 2 of 3
NFPA 82 1999 Edition
Page 3 of 3