Relay Coordination
Relay Coordination
Relay Coordination
Dr. Ir. Redy Mardiana Laboratorium Teknik Tegangan dan Arus Tinggi Sekolah Teknik Elektro dan Informatika Institut Teknologi Bandung
Radial System
R1 provides primary protection to line 1 R2 provides primary protection to line 2 & remote backup for line 1 Farthest relay from the source is set first Relays located on source side of the line
Trip direction towards the line The radial system is inherently directional
Dr.Ir. Redy Mardiana - STEI ITB
Inverse Characteristic
PSM =
Pickup Current which relate to Pickup Setting Multiplier (PSM) (also known as Plug Multiplier Setting)
To set pickup current for relay to operate
T = the required time of operation Tm= the time obtained from the relay characteristic curve at TDS = 1.0 Example: If the time obtained from relay characteristic curve (TDS=1.0) is 4.0 , while the required time to operate the relay is 0.4s , then TDS is set to 0.4/4.0 = 0,1.
Example: If fault current IF is 3000A and primary pickup current is 200A, then PSM = 3000/200=15. If the installed CT has a ratio of 400/5 then the relay current setting is 200 x 5/400 = 2.5A. (or the relay tap = 2.5A)
PSM =
* Pickup current sometimes refers to relay current setting if it is seen from secondary side of CT
Dr.Ir. Redy Mardiana - STEI ITB
I F MIN 1.3 I 2 ; I = 3 I3 2
I FL < I PU
3 I 3 = 0.33I 3 1.3 2 2
1. 2. 3. 4. 5.
1. Choose tCTI and calculate tOP-R2 2. Calculate IPU 3. Calculate IF-MAX (at closest to R1) 4. Calculate PSM 5. Determine TDS time from curves
Inverse used when IF is dependent on generation not fault location Very Inverse used when IF is dependent on fault location used when IF independent of normal changes in generating capacity Extremely Inverse used when IF is dependent on fault location used when IF independent of normal changes in generating capacity Ease coordinates with fuses and reclosers
Dr.Ir. Redy Mardiana - STEI ITB
T=
T=
T=
80 TDS 2 PSM 1
3 TDS log10 ( PSM )
T = Relay operating time; TDS = Time Dial Setting; PSM= Pickup setting Multiplier
Dr.Ir. Redy Mardiana - STEI ITB
Upstream relay has longer tOP than downstream relay Very undesirable for the fault closes to the source, IF will be very large but the relay operating time is longer. This will damages the equipment (the source) Combine inverse and instantaneous overcurrent relay to reduce fault clearing time
Dr.Ir. Redy Mardiana - STEI ITB
The most significant reduction in operating time is on line section 4 Instantaneous relay provides primary protection mainly for close-in faults
Dr.Ir. Redy Mardiana - STEI ITB
F1 is the closest to R1
Use to reduce fault clearing times Provide no backup protection IOC relay must NEVER operate for faults beyond line section end Setting Pickup for IOC:
I PU = k I 3
MAX
(at F1)
1.25 k 1.5
Cara 2
R S T
Jika terjadi gangguan ke tanah dimana Igangguan < Ibeban, maka relay tak beroperasi
Dr.Ir. Redy Mardiana - STEI ITB
Cara 2
R S T
*Setting pickup ground fault relay jauh lebih rendah dari overcurrent.
Dr.Ir. Redy Mardiana - STEI ITB
Residual current and voltage only exists when a fault current flows to earth, Need to coordinate with similar relays downstream.
Dr.Ir. Redy Mardiana - STEI ITB
Current flowing on relay is quite high due to solidly or low resistance groundings. Rarely used for high resistance grounding system. Fault current is higher compared to ungrounded or high resistance grounding systems.
Configuration (c) consists of two phases since these will detect any interphase fault; the connections to the earth-fault relay are unaffected by this consideration. The typical settings for earth-fault relays are 30%-40% of the full-load current or minimum earth-fault current on the part Dr.Ir. of the system being protected. Redy Mardiana - STEI ITB