All Drawings
All Drawings
GENERAL NOTES:-
8500 1. THESE ARE SOFTWARE GENERATED HYDRAULIC AND PROCESS
DRAWINGS.
7300
2. RL'S AND INTERNAL SIZES ARE MANDATORY. FOR WALL THICKNESS AND
6100 OTHER DETAILS PLEASE REFER WORKING DRAWINGS.
3. ALL DIMENTIONS ARE IN MM, LEVELS AND CO-ORDINATES ARE IN METERS
4900 UNLESS OTHERWISE NOTED.
3700 4. DO NOT SCALE THE DRAWINGS PLEASE REFER TO WRITTEN DIMENTION
ONLY.
5. VALES, PIPES, PUMPS, BLOWERS, MOTORS, ETC. SHALL BE OF STANDARD
MAKE AS PER TENDER SPECIFICATION.
2500 6. ADMIN BUILDING LAYOUT TO BE INCORPORATE AS PER REQUIREMENT
WITH FILTER BED IN WORKING DRAWINGS.
7. ALL CHANNELS ARE TO BE CORVED WITH PRECAST SLAB.
8. RAILING, LIGHTING ARRESTOR AND HIDDEN DETAILS ARE AS PER UNIT
WHEREVER APPLICABLE.
9. LENGTH OF PIPELINE TO BE TAKEN AS PER SITE LAYOUT AND WORKING
148.78 DRAWINGS.
10. SYMBOLS USE IN DRAWINGS:-
1. RL IN PLAN VIEW
BYPASS CHANNEL
1200MM WIDE
900 WIDE INLET PIPE TO
WALKWAY
CLARIFOCCULATOR
1100 MM Ø
C
150.00
149.70
149.40
B
149.10
148.80
148.78 148.50
148.48 MOTOR &
148.47 148.76
GEAR BOX
148.50
147.73 148.46 148.50
A CHIEF ENGINEER SUPERINTENDANT ENGINEER
148.02 148.01
148.00 148.00
147.32 147.32 147.46 147.55 147.55
GL 1100 GL
142.80
PROOF CONSULTANT CONSULTANT
OPENING OF
DUCK FOOT 1800 x 750 MM
BEND SECTION A-A
- - - -
- - - -
OUTLET CHAMBER - - - -
143.99 - - - -
1322 600 900 - - - -
148.76
148.50 DETAILS OF 5 STEP AERATION FOUNTAIN,PARSHALL
TITLE FLUME,FLASH MIXER FOR 40 MLD WTP
148.47 148.76
148.76
147.73 225 PROJECT 40MLD WTP Project by iNODE WTP Software
148.46 75
148.01
148.46
147.32
147.46 SECTIONAL ELEVATION AT D-D OWNER iNODE SOFTWARE CO.
• Pune Branch • Office 508 • Nyati Emporius Near The Orchid Hotel • Baner •
Pune • India
147.32
D D CLIENT
iNODE SOFTWARE CO.
831 300 600
DETAIL AT - B SECTION B-B
SECTION C-C 1350
PMC
iNODE SOFTWARE CO.
GL PRECAST SLAB/
3. WATER LEVEL
0 STEP 0.15
4. WATER FLOW DIRECTION
GL CLARIFIER ZONE CLARIFIER ZONE
0 0 11. LEGEND:-
142.8
EL - ELEVATED LEVEL
144.49 144.49 WW-V1 - WASHWATER ISOLATION TANK VALVE
WW-V2 - WASHWATER INLET VALVE
PW-V1 - WASHWATER INLET VALVE
OPENING 144.99 OPENING OPENING 144.99 WW-V2 - PUREWATER OUTLET VALVE
1800 x 1200 x 750 MM PW-V2 - PUREWATER SUMP INLET VALVE
143.49 800 800 143.49
D-V1 - DRAIN VALVE
143.99 142.97 142.97
SLUDGE D-V2 - WASHWATER DISPOSAL VALVE
SLUICE VALVE
600
600
DRAIN PIPE S-V1 - SLUICE VALVE
150 DIA 150 Ø
142.47
1100 Ø C.I. INLET PIPE TO CLF 1300
142.32
SLUDGE
J
CENTRAL WELL DRAIN ARRANGEMENT
1100
OF 1500 Ø
SECTION A-A
148.49
144.49 144.49
50000
148.19 541
147.99 148.19
600 MM STEP FSL OF CLF
ELECTRICAL CONDUIT CENTRAL
PLACED 1500 MM C/C 63 mm Ø PVC PIPE WELL 600 Ø
350 800 1100 800
SETTLED WATER 143.49 143.49
WEIR OPENING DRAIN PIT
COLLECTION CHANNEL 147.84 142.97 142.97
DRAIN TO FINAL DISPOSAL 147.84
1000 WIDE
600
CHIEF ENGINEER SUPERINTENDANT ENGINEER
600
1100 OPENING
Ø 50000 SLUDGE 541 x 350 DETAIL OF PORT
Ø C.I. INLET
DRAIN ARRANGEMENT (5NOS) SLUDGE
PIPE TO CLF IN CENTRAL SHAFT
OF 1500 Ø DRAIN PIPE
1300
(5NOS) 150 DIA
HAND RAILING DETAIL AT -H
1100 Ø C.I. INLET
15000
PIPE TO CLF
RCC COLUMNS TYPICAL OPENING PRECAST DETALS AT - J PRECAST EXECUTIVE ENGINEER DEPUTY ENGINEER
148.49 148.49
541 x 350 STUB COLUMNS 72 NOS. ELECTRICAL OPENING STEPS STEPS
(5NOS) (MAX. WIDTH 200 EACH) CONDUIT 541 x 350 147.99 147.99
63 Ø (5NOS) FSL OF CLF FSL OF CLF
PVC PIPE
Ø 15000 147.92 147.99 147.99 147.92
147.99
147.97
147.02 147
A A
COLLECTION COLLECTION
LAUNDER OF LAUNDER OF
PLAN OF OPENING CLARIFLOCCULATOR
CLARIFLOCCULATOR
AT R.L. 147.84 AT START AT END
148.5 148.5 DETAIL AT -G DETAIL AT -K
1100 ROTATING BRIDGE - - - -
- - - -
WITH SCRAPER 148.49
- - - -
FLOCCULATION ZONE (SHOWN INDICATIVE ONLY) CLARIFIER
100 147.99 - - - -
147.97 148.12 - - - -
148 147.92 COLLECTION CHANNEL
147.55 DATE DESCRIPTION REVISION NO. ENGINEER
X 147.5 148 200 LAUNDER 147.96
OPENING 147 DETAILS OF CLARIFLOCCULATOR FOR 40 MLD WTP
TITLE
146.48
FLASH MIXER
400 400 400 400
PROJECT 40MLD WTP Project by iNODE WTP Software
BASE SLAB
CONSULTANT iNODE SOFTWARE CO.
450 2720 450 2720 450
PLAN OF CLARIFLOCCULATOR DETAILS OF OPENING FLOCCULATOR WALL @ BOTTOM DWG. NO: 7001-01-GA-40WTP-02
SHEET NO - 3
GENERAL NOTES:-
C C 1. THESE ARE SOFTWARE GENERATED HYDRAULIC AND PROCESS DRAWINGS.
3500 MIN 3250 500 3250 3250 500 3250 3250 500 3250 3250 500 3250 2. RL'S AND INTERNAL SIZES ARE MANDATORY. FOR WALL THICKNESS AND
OTHER DETAILS PLEASE REFER WORKING DRAWINGS.
1200 CHAMBER 1200 B 1200 CHAMBER CHAMBER 1200 B 1200 CHAMBER 3. ALL DIMENTIONS ARE IN MM, LEVELS AND CO-ORDINATES ARE IN METERS
CHAMBER
UNLESS OTHERWISE NOTED.
D-V2 D-V2 D-V2 D-V2 4. DO NOT SCALE THE DRAWINGS PLEASE REFER TO WRITTEN DIMENTION
1200
1200
1200
1200
1200
ONLY.
LATERALS 50 MM Ø LATERALS 50 MM Ø
150 NOS/UNIT 1175 1175 1175 1175 150 NOS/UNIT 1175 1175 1175 1175 5. VALES, PIPES, PUMPS, BLOWERS, MOTORS, ETC. SHALL BE OF STANDARD
DOOR (PVC 8 KG/CM2) (PVC 8 KG/CM2) MAKE AS PER TENDER SPECIFICATION.
6. ADMIN BUILDING LAYOUT TO BE INCORPORATE AS PER REQUIREMENT
WITH FILTER BED IN WORKING DRAWINGS.
D D D D 7. ALL CHANNELS ARE TO BE CORVED WITH PRECAST SLAB.
ELECTRICAL ROOM 8. RAILING, LIGHTING ARRESTOR AND HIDDEN DETAILS ARE AS PER UNIT
& RAPID SAND WHEREVER APPLICABLE.
PANEL ROOM FILTER 9. LENGTH OF PIPELINE TO BE TAKEN AS PER SITE LAYOUT AND WORKING
RAPID RAPID SAND RAPID DRAWINGS.
SAND FILTER SAND 10. SYMBOLS USE IN DRAWINGS:-
FILTER FILTER
8500
2. RL IN SECTION VIEW
GL + 0.6
3. WATER LEVEL
1200
1200
PIT
1200
RATE
1200
RATE RATE
CONTROL CONTROL CONTROL CONTROL
WW-V1 - WASHWATER ISOLATION TANK VALVE
Varies
600
600
600
600
PUMP ROOM
WW-V2 - PUREWATER OUTLET VALVE
INSPECTION INSPECTION INSPECTION INSPECTION
CHAMBER CHAMBER CHAMBER CHAMBER PW-V2 - PUREWATER SUMP INLET VALVE
F P1
WASH WATER SUMP
F D-V1 - DRAIN VALVE
144.46
PURE WATER CHANNEL
F PURE WATER CHANNEL D-V2 - WASHWATER DISPOSAL VALVE
P1 144.96 144.96
600
600
600
600
600
Varies
1200
1200
1200
1200
FILTER FILTER
500 500
PANEL ROOM
&
ELECTRICAL ROOM
D D D D
LATERALS 50 MM Ø
DOOR LATERALS 50 MM Ø 1175 1175 1175 1175 150 NOS/UNIT 1175 1175 1175 1175 EXECUTIVE ENGINEER DEPUTY ENGINEER
150 NOS/UNIT (PVC 8 KG/CM2)
1200
1200
1200
1200
1200
(PVC 8 KG/CM2)
D-V2 D-V2 D-V2 D-V2
CHAMBER CHAMBER CHAMBER CHAMBER 1200 CHAMBER
1200 1200 1200 1200
LAYOUT PLAN OF RAPID SAND FILTER AT BELOW CROSS TROUGH
(BACK WASHING PROCESS FROM OVERHEAD BACK WASH TANK PIPE TO WATER FOR RECYCLING)
DETAIL-A
149.06 149.06 149.06
149.06
147.46 147.46 WW-V2 PW-V1 149.06 147.96
147.46 146.48
GL + 0.6
GL GL
. 147.19 147.09 147.19 . GL - - - -
147.19 . - - - -
146.76 146.76 WALKWAY PURE WATER CHANNEL - - - -
CROSS TROUGH 500 CROSS TROUGH CROSS TROUGH 500 CROSS TROUGH 146.76 146.76 146.76
- - - -
146.46 146.46 - - - -
145.86 145.86 146.45
SAND SAND SAND SAND 144.96 DATE DESCRIPTION REVISION NO. ENGINEER
GRAVELS 145.36 GRAVELS GRAVELS GRAVELS 145.36 LAYOUT PLAN AND DETAILS OF RAPID SAND FILTER
TITLE FOR 40 MLD WTP
3500 MIN 144.46 144.46
MANIFOLD PIPE 144.46 144.46 144.46
MANIFOLD PIPE PROJECT 40MLD WTP Project by iNODE WTP Software
Ø 800 MM 900 DETAIL-D 900 900 Ø 800 MM 900
PE
SR. NO. SYMBOL INDICATE
SL
O
O
SL
PE
LADDER 1. RL IN PLAN VIEW
ROLLING SHUTTER
2. RL IN SECTION VIEW
W W 11. LEGEND:-
30000
WW-V2 - WASHWATER INLET VALVE
30000
SL
PE
W W
O
O
PE
SL
1000
MIN
WALL THK/2
152.14 SUCTION PIPE
CONCRETE
SIZE
PUMP HOUSE 143.08 MIN 1000 WALL EXECUTIVE ENGINEER DEPUTY ENGINEER
ELEVATION
RCC GIRDER
500
MIN
142.58
6030
D Ø × 8 THK
PLATE
PUMP
147.61 VENT PIPE 'A' NB - - - -
WITH BEND - - - -
GL - - - -
- - - -
INSECT NOTE:- - - - -
M
'C' SQ. 8 THK PLATE OWNER iNODE SOFTWARE CO.
IS:2062 Gr.-A INSIDE FACE • Pune Branch • Office 508 • Nyati Emporius Near The Orchid Hotel • Baner
SUCTION PIT • Pune • India
143.08 OF TANK
SLOPE SLOPE
CLIENT
iNODE SOFTWARE CO.
DETAIL FOR VENT PIPE
142.58 RCC RAFT PCC
PMC
iNODE SOFTWARE CO.
30000
CONSULTANT
iNODE SOFTWARE CO.
SECTION A-A
DWG. NO: 7001-01-GA-40WTP-07
SHEET NO - 11
GENERAL NOTES:-
MECHANICAL COMPONENT LIST SUMMARY LIST
1. THESE ARE SOFTWARE GENERATED HYDRAULIC AND PROCESS
DRAWINGS.
AREATION FOUNTAIN AND FLASH MIXER MOTORS 2. RL'S AND INTERNAL SIZES ARE MANDATORY. FOR WALL THICKNESS AND
OTHER DETAILS PLEASE REFER WORKING DRAWINGS.
Sr. No. LEGEND DESCRIPTION NUMBERS/LENGTH SIZE/CAPACITY Sr. No. LEGEND NUMBERS CAPACITY 3. ALL DIMENTIONS ARE IN MM, LEVELS AND CO-ORDINATES ARE IN METERS
UNLESS OTHERWISE NOTED.
1 M1 MOTOR WITH GEAR 1 5 HP 1 M1 1 5 HP 4. DO NOT SCALE THE DRAWINGS PLEASE REFER TO WRITTEN DIMENTION
ONLY.
5. VALES, PIPES, PUMPS, BLOWERS, MOTORS, ETC. SHALL BE OF STANDARD
2 G1 GATE-1 1 900 X 1450 2 M2 2 5 HP
MAKE AS PER TENDER SPECIFICATION.
6. ADMIN BUILDING LAYOUT TO BE INCORPORATE AS PER REQUIREMENT
3 G2 GATE-2 1 900 X 1450 GATES WITH FILTER BED IN WORKING DRAWINGS.
7. ALL CHANNELS ARE TO BE CORVED WITH PRECAST SLAB.
4 - FLASH MIXER OUTLET PIPE 2.5 M 1100 MM SR. NO. LEGEND NUMBERS CAPACITY 8. RAILING, LIGHTING ARRESTOR AND HIDDEN DETAILS ARE AS PER UNIT
WHEREVER APPLICABLE.
CLARIFLOCCULATOR 1 G1 1 900 X 1450 9. LENGTH OF PIPELINE TO BE TAKEN AS PER SITE LAYOUT AND WORKING
DRAWINGS.
10. SYMBOLS USE IN DRAWINGS:-
SR. NO. LEGEND DESCRIPTION NUMBERS/LENGTH SIZE/CAPACITY 2 G2 1 900 X 1450
2 ROTATING BRIDGE WITH SCRAPPER 1 15 SR. NO. LEGEND NUMBERS CAPACITY 1. RL IN PLAN VIEW
2. RL IN SECTION VIEW
3 S-V1 SLUICE VALVE 1 150 MM 1 S-V1 1 150 MM
3. WATER LEVEL
* NOTE : PIPE LENGTH WILL FINALIZE AS PER THE WORKING DRAWING. 3 BP-V 2 1200 MM 11. legend:-
EL - ELEVATED LEVEL
FILTER BED 4 PW-V1 12 700 MM
WW-V1 - WASHWATER ISOLATION TANK VALVE
SR. NO. LEGEND DESCRIPTION NUMBERS/LENGTH SIZE/CAPACITY 5 PW-V2 1 1200 MM WW-V2 - WASHWATER INLET VALVE
PW-V1 - WASHWATER INLET VALVE
1 FI-V FILTER INLET VALVE 6 400 MM 6 WW-V1 2 800 MM
WW-V2 - PUREWATER OUTLET VALVE
2 BP-V BYPASS VALVE 2 1200 MM 7 WW-V2 12 800 MM PW-V2 - PUREWATER SUMP INLET VALVE
3 PW-V1 PUREWATER OUTLET VALVE 12 400 MM 8 D-V1 2 800 MM D-V1 - DRAIN VALVE
D-V2 - WASHWATER DISPOSAL VALVE
4 WW-V1 WASHWATER ISOLATION TANK VALVE 2 800 MM 9 D-V2 12 800 MM
S-V1 - SLUICE VALVE
8 P1 WASHWATER PUMP 1 22 HP 2 P2 1 -
- - - -
- - - -
- - - -
- - - -
- - - -
CLIENT
INODE SOFTWARE CO.
PMC
INODE SOFTWARE CO.
CONSULTANT
INODE SOFTWARE CO.