03 30014 04 en - IP IO Specification Sheet 3.0
03 30014 04 en - IP IO Specification Sheet 3.0
com/buildings | 1
IP-IO
SmartX IP Controller
IP-IO
SmartX IP Controller
Configurations Digital Inputs Universal I/O Relay Outputs High Power Relay
Type Ub Form A Outputs
Form A
Digital inputs yes yes - -
Counter inputs yes yes - -
Supervised inputs - yes - -
Voltage inputs - yes - -
(0 to 10 VDC)
Current inputs - yes - -
(0 to 20 mA)
Temperature inputs - yes - -
Resistive inputs - yes - -
2-wire RTD temperature - yes - -
inputs
Voltage outputs - yes - -
(0 to 10 VDC)
Digital outputs - - yes yes
Digital pulsed outputs - - yes yes
PWM outputs - - yes yes
Tristate outputs - - yes -
Tristate pulsed outputs - - yes -
IP-IO
SmartX IP Controller
IP-IO
SmartX IP Controller
IP-IO
SmartX IP Controller
Part Numbers
Specifications
For specifications and information on the restrictions that apply to the Smoke Control (SMK) models, see the
EcoStruxure Building Management - Smoke Control System Design Guide, 04-16014-XX-en.
AC input
Nominal voltage......................................................................................................................................................24 VAC
Operating voltage range........................................................................................................................................+/-20 %
IP-IO
SmartX IP Controller
Frequency ............................................................................................................................................................50/60 Hz
Maximum power consumption ..................................................................................................................................17 VA
Power input protection................................................................................................MOV suppression and internal fuse
DC input
Nominal voltage.............................................................................................................................................24 to 30 VDC
Operating voltage range ...............................................................................................................................21 to 33 VDC
Maximum power consumption .....................................................................................................................................9 W
Power input protection................................................................................................MOV suppression and internal fuse
Environment
Ambient temperature, operating .................................................................0 to 50 °C (32 to 122 °F) at normal operationa
..........................................................-40 to +60 °C (-40 to +140 °F) for rooftop applications, horizontal installation onlya
a) MP-C Display has an operating temperature range of -30 to +60 °C (-22 to +140 °F).
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating ...............................................................................................................................................UL94-5V
Ingress protection rating ............................................................................................................................................IP 20
Mechanical
Dimensions...................................................................................... 153 W x 110 H x 64 D mm (6.0 W x 4.3 H x 2.5 D in.)
Weight, IP-IO-DI10
Including terminal blocks .....................................................................................................................0.337 kg (0.742 lb)
Weight, IP-IO-UIO10
Including terminal blocks .....................................................................................................................0.336 kg (0.740 lb)
Weight, IP-IO-UIO5DOFA4
Including terminal blocks..................................................................................................................... 0.357 kg (0.787 lb)
Installation.....................................................................................................DIN rail or other flat surface inside a cabinet
Terminal blocks ................................................................................................................................................Removable
IP-IO
SmartX IP Controller
Software compatibility
EcoStruxure Building Operation software .............................................................................................version 2.0 or later
Agency compliances
Emission...............................................................RCM; EN 61000-6-3; EN 50491-5-2; FCC Part 15, Sub-part B, Class B
Immunity ...............................................................................................................................EN 61000-6-2; EN 50491-5-3
Safety standards........................................................EN 60730-1; EN 60730-2-11; EN 50491-3; UL 916 C-UL US Listed
Smoke control product safetya, b ..............................................................................................................................UL 864
a) Applies to the IP-IO SMK models: IP-IO-DI10-SMK, IP-IO-UIO10-SMK, and IP-IO-UIO5DOFA4-SMK.
b) The IP-IO SMK models are shipped with a validated UL 864 software version, which can differ from the latest
released software. For more information, see EcoStruxure Building Management - Smoke Control System Design
Guide, 04-16014-XX-en.
Real-time clock
Accuracy, at 25 °C (77 °F) ..............................................................................................................+/-1 minute per month
Backup time, at 25 °C (77 °F) ...................................................................................................................7 days minimum
Communication ports
Ethernet ................................................................................................................................ Dual 10/100BASE-TX (RJ45)
USB ....................................................................................................................................1 USB 2.0 device port (mini-B)
........................................................................................................................1 USB 2.0 host port (type-A), 5 VDC, 2.5 W
Communications
BACnet..........................................................................................................BACnet/IP, port configurable, default 47808
.......................................................................................................BTL B-ASC (BACnet Application Specific Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home
page.
CPU
Frequency ........................................................................................................................................................... 500 MHz
Type...........................................................................................................................................ARM Cortex-A7 dual-core
DDR3 SDRAM ........................................................................................................................................................128 MB
NOR flash memory ...................................................................................................................................................32 MB
Memory backup.......................................................................................................................128 kB, FRAM, non-volatile
MP-C Display (Optional)
Removable .....................................................................................................................................................................No
Display size .................................................................................................................36 W x 17 H mm (1.4 W x 0.7 H in.)
Display resolution .......................................................................................................................................128 x 64 pixels
Display type......................................................................... FSTN monochrome LCD, white color transflective backlight
Power consumption............................................................................................................. max. 0.15 W (45 mA at 3.3 V)
Ambient temperature, operating .........................................................................................-30 to +60 °C (-22 to +140 °F)
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Weight ..................................................................................................................................................0.035 kg (0.077 lb)
Compliance with standards ......................................................................................................................EN ISO 16484-2
IP-IO
SmartX IP Controller
Digital inputs, DI
Channels, IP-IO-DI10..................................................................................................................................10, DI1 to DI10
Channels, IP-IO-UIO10.....................................................................................................................................................0
Channels, IP-IO-UIO5DOFA4 ...........................................................................................................................................0
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
Digital input protection........................................................................Transient voltage suppressor on each digital input
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Universal inputs/outputs, Ub
Channels, IP-IO-DI10........................................................................................................................................................0
Channels, IP-IO-UIO10 ...................................................................................................................... 10 Ub, Ub1 to Ub10
Channels, IP-IO-UIO5DOFA4 .................................................................................................................5 Ub, Ub1 to Ub5
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
A/D converter resolution ..........................................................................................................................................16 bits
Universal input/output protection........................................Transient voltage suppressor on each universal input/output
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
IP-IO
SmartX IP Controller
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm
Type II (I/NET) .......................................................................................................................................................10 kohm
Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
...................................................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
10 kohm, 2.2 kohm, and 1.8 kohm.......................................................-50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
..........................................................................................................-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
Linearized 10 kohm .................................................................................-50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
...............................................................................................................-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
1 kohm ..............................................................................................-50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)
RTD temperature inputs
Supported RTDs ..............................................................................................................Pt1000, Ni1000, and LG-Ni1000
Pt1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
IP-IO
SmartX IP Controller
Continued
Ni1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
LG-Ni1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)
IP-IO
SmartX IP Controller
IP-IO-DI10
IP-IO
SmartX IP Controller
IP-IO-UIO10
IP-IO
SmartX IP Controller
IP-IO-UIO5DOFA4
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2014/35/EU Low Voltage Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
any interference received, including interference that may cause undesired operation. 2015/863/EU amending Annex II to Directive 2011/65/EU
This equipment complies with the rules, of the Official Journal of the European Union, for
Industry Canada governing the Self Declaration of the CE Marking for the European Union as specified in the
This Class B digital apparatus complies with Canadian ICES-003. above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 11, and EN 50491-3 Safety Standards.
UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.
UL 864 Listed products for the United States. 10th Edition Smoke Control System.
UL file S5527.
IP-IO
SmartX IP Controller
www.schneider-electric.com