CLL Exp1
CLL Exp1
Fig: 1. Block Diagram of a Control Loop for Measurement of Process Reaction Curve.
G(s)K
e− L s (1)
1 Ts
Zeigler and Nichols suggested setting the values of Kc, Ti, and Td according to the formula
shown in Table 1. Refer to Fig. 2 for the symbol meaning for tuning the controller via Z-N
settings.
Table 1. Z-N Settings for Tuning Different Controllers
Type of Controller Kc Ti Td
Proportional (P) T/L
Proportional - Integral (PI) 0.9T/L L/0.3
Proportional - Integral – Derivative (PID) 1.2T/L 2L 0.5L
Fig: 2. Typical Process Reaction Curve (First Order with Transportation lag)
The value of Kp can be found using Kp = Bu / M, where Bu is the ultimate value of B at large
time t. (Refer to Fig. 1).
PROCEDURE:
1. Process Tank filled with water is made available. Temperature Control Trainer is
active.
2. Log in the system and select the “INTERFACE” mode for experimentation.
3. Turn on the water supply and maintain the inlet flow rate of water to the process tank
through a rotameter maintained at 20-30 LPH. Please verify it.
4. Due to some external disturbances, the liquid flow rate may show some significant
change in its value. Please keep an eye on the rotameter reading to dampen such
changes by careful adjustment of the rotameter itself. Please note that a change in
mass flow rate is not desired in the undertaken experiment.
5. Run the process as directed below:
Select the MANUAL MODE with an output of 0 %.
Wait till a steady state is reached for the process value.
Log on to a file for saving transient data.
Give a STEP RESPONSE to the output. Change it from 0% to 100%.
Wait till a steady state is reached. Please do not rush.
Log Off from the data-saving procedure.
Make the output 0%.
6. With the help of the saved data file, draw the Process Reaction Curve between process
value and time.
7. Find the control setting parameters from Cohen-Coon (C-C) & Ziegler-Nichols (Z-N)
rules.
8. Tabulate the control setting parameters for each type of controlling mode e.g. P-
mode, PI-mode, PID-mode; obtained from both the rules, C-C & Z-N.
9. Run the process with the suggested controlling parameters for each type of control
mode, obtained from both methods. Please follow the instructions directed below
carefully.
Select the MANUAL MODE with an output of 0%.
Set P / PI / PID parameters as obtained from Z-N rules. For the first time, set for P-
mode. You will have the opportunity of tuning PI & PID modes in the next RUN
sequences.
Wait till a steady state is reached.
Once a steady state is reached, make the set point equal to the process value.
LOG on to a file for saving the transient response of the system. It is advised to
save the data file with a name explaining: the group name, controller mode, etc.
Give a STEP change of 10 units to the set point.
Select AUTO MODE.
Wait till a steady state is reached. Please do not rush.
Log Off from the data saving procedure.
Put on the manual mode.
10. Repeat the procedure for obtaining the process transient response for different
control mode e.g. PI and PID.
11. Repeat for controlling parameters as obtained previously from C-C rules.
12. Draw the excel plots for all the above sets of transient responses. Plot process value
and the set point of the process on the same graph against time.
13. Report the best possible controlling mode for the step-change made. Justify your
decision on both, qualitative and quantitative scale.