SEE Safety

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

TAIA

TRUTHALONE TRIUMPH

SAVE NATION
SAVE ENERGY
GOVERNMENT OF TAMIL NADU
ELECTRICAL INSPECTORATE
Phone: 22500 184, 22500 227.
Web Site: www.tnei.tn.gOv.in 22500 430, 22500 796
E-mail: ceig @tn.gov.in 22500 036
Fax:
From TM/s. Saran Electric Energy Private Limited,
The Chief Electrical Inspector to Government,
Post Box No. 1152, No. 8/649. Saran Garden.
Thiru-Vi-Ka Industrial Estate, Arulpuram, Palladam Road,
Guindy, Chennai -32. Tirupur- 641 605.

Letter No. 1051/SPP/CEIG/D3/SC/2023-2, Dated: 23.11.2023


Sir, Installations of voltage
Sub: Electricity - 1MVW Solar Power Plant - New Electrical
650\Vat the premises
exceeding 650V and upto and including 33 kV and uptoNos. 9/2A, 9/2B, 10/1,
SF.
of M/s. Saran Electric Energy Private Limited, Inspection under
10/2, Mangalur Village, Veppur Taluk, Cuddalore District - relating to
Regulation 45 of Central Electricity Authority (Measures
2023, on 20.11.2023 - Approval -
Safety and Electric Supply) Regulations,
accorded.
Ref: 1. This office letter No. 1051/SPPICEIG/D3/Drg/2023, dt. 16.10.2023.
2. Your letter No. & dt. Nil, received on 14.11.2023.
3. This office letter No. 1051/SPP/CEIG/D3/Reg-45 Inspection/2023, dt. 14.11.2023.
4. The Electrical lInspector/Cuddalore letter No. 1051/SPP/EI-CUDIR45/2023, dt.
20.11.2023.
5. Your letter No. & dt. Nil, received on 23.11.2023.
6. This office letter No. 1051/SPPICEIG/D3/TCI2023-1, dt. 23.11.2023.
*****

Approval is hereby accorded under Regulation 45 (4) of Central Electricity


Authority (Measures relating to safety and Electric Supply) Regulations, 2023 to
commission the Electrical Installations inspected on 20.11.2023 at the above premises for
1x 1200 kVÀ Solar Inverter Duty Transformer, 4 x 295 kW Solar Inverters and other
equipments as detailed in annexure subject to complying with the terms and conditions of
the supplier.
The date of energisation of the installation should be intimated to this office. The
equipment's permitted should be commissioned within six months from the date of issue of
this letter failing which fresh permission should be obtained.
Under Regulation 48 (7) of Central Electricity Authority (Measures relating to
Safety and Electric Supply) Regulations, 2023,the owner of the installation shal maintain
and operate the installations in a condition free from danger and as recommended by the
manufacturer or by the relevant Standards.
(Sd/-xxx)
Chief Electrical Inspector toGovernment
ITrue Copy/Forwarded//
Assistant Electrical Inspector/Technical
Enc: Annexure containing List of Electrical Equipments (05 Pages)
Copy to: M/s. Sri Padmavathi Engineering and Enterprises, Plot No. 18, Harshita Flats, Sri
Balaji Nagar,4th Street, Aditnaath Avenue, Santhosapuram, Chennai -73.
(With Annexure)
Copy to: The Superintending Engineer/TANGEDCo Ltd/Cçddalore Electricity Distribution
Circle/Capper Hills, Cuddalore - 4. (With Annexure)
Copy to: The Electrical Inspector/Cuddalore (With Annexure)
Annxure to this Office Letter Eo.
10515PPICEIGLD3/S<|2023 Date 23-1/- 2023
M/s.Saran Electric Energy Private Limited,
SF.New No.9/2A, 9/2B, 10/1, 10/2, Mangalur Village,
Veppur Taluk, Cuddalore Dist

SUPPLY
I. 33KV DP STRUCTURE AT POINT OF
33KV DP Structure comprising of
2Nos
200 x 125mm, 10.5Mtrs Height RSJ Poles
1Set
33KV Disc Insulator
1Set
33KV Lightning Arrester
1Set
33KV AB Switch double break (800A)
1Set
33KV Pin Insulator
1Set
33KV HG Fuse
1Set
"0" Copper Flat for Inter connection
1Set
Stay Insulator
MS Cross Channels 1Set

H.T CABLE::
from Consumer DP
Cable Size: 1R x 3C x 185sq.mm 33KV HT XLPE Cable
Structure to 33KV HT Outdoor 800A 1PANEL VCB Incoming side

I. 800A 33KV HT 1 PANEL VCB(OUTDOOR) DrawOut Type:


INCOMER
Make MEGAWIN

Voltage 36KV

Amps 800A,36KA, 3sec


S. No 231188/16174

:1Rx 3C x 185sg.mm 33KV H.T. XLPE to to 1200KVA Transformer


Pnary Side
II. OUTDOOR TYPE 1200KVA TRANSFORMER
1200KVA
Capacity
Make I.P.L. PRODUCTS

S. No IPL/01400

Pri.Voltage 33000V

Sec. Voltage 800V

Pri. Amps (HV SIDE) 20.99

Sec. Amps (LV SIDE) 866.05


OFF CIRCUITE TAP CHANGER
Tap Changer
Busduct: 1Rx 125 x 12mm Alu Flat / PH from Transformer Secondary side
to 05 IN 1 OUT MAIN LT PANEL

IV. MAIN LT PANEL


Incoming :1250A TP, ACB MDO -1Nos
:400A TP MCCB - 5Nos
Outgoing :125A TP MCCB-1No
IVC CABLE SIZE :1Rx 125 x 12mm Alu Flat /PH from Transformer
Secondary side

V. SUNGROW- STRING INVERTER-1:


Make :SUNGROW
SINo :12381200263
Rated Power :295 KW
Rated Voltage :DC 500 V-1500V
AC 800 V
/C CABLE SIZE :1Rx3Cx240Sqmm Ar.AlXLPE Cable from MAIN LT PANEL
30A DCFUSE (1000V-14Nos. IN BUILT IN INVERTER)
FED FROM :JINKO SOLAR MONO PERC MOUDLES
(EACHSPVM ARE 575W,42.44V, 13.55A)
(572Nos x575Wp)= 328.90KWp
STRING-1TO STRING -10 (Each 52)
STRING-11 (Each 26)
546 x575Wp =313.95KWp
SOLAR MODULES DETAIL:
JINKO SOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W, 42.44V,13.55A)
ARRAY-1
x 575Wp = 299.0KWp
STRING-1 TO10 EACH STRING 52MODULES (10 x52) = 520 Modules 575Wp = 14.95KWp
STRING-11 EACH STRING 26MODULES (1 x 26) = 26 Modules x
TOTAL = 313.95KWp
VI. SUNGROW- STRINGINVERTER-2:
Make :SUNGROW
SI No : 12381200286
Rated Power :295 KVN
Rated Voltage :DC 500V-1500V
AC 800 V
MAIN LT PANEL
I/CCABLE SIZE:1Rx3Cx240Samm Ar.AIXLPE Cable from
30A DC FUSE (1000V 14Nos. IN BUILT IN INVERTER)
FED FROM JINKO SOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W, 42.44V, 13.55A)
(572Nos x 575Wp)= 328.90KWp
STRING-1 TO STRING -11 (Each 52)
572 x575Wp =328.9OKWp
SOLAR MODULES DETAIL:
JINKOSOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W,42.44V, 13.55A)
ARRAY-2
STRING-1 TO 11 EACH STRING 52MODULES (11 x 52)= 572 Modules x 575Wp 328.90KVWp
TOTAL =328.90KWp
VIl. SUNGROW- STRINGINVERTER-3:
Make SUNGROW
SINo :12381200219
Rated Power 295 KW
Rated Voltage :DC 500V-1500V
AC800 V
/C CABLE SIZE :1R3Cx240Sqmm Ar.AlXLPE Cable from MAIN LT PANEL
30A DC FUSE (1000\V14Nos. IN BUILT IN INVERTER)
FED FROM JINKO SOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W,42.44V, 13.55A)
(572Nos x575Wp)= 328.90KWp
STRING-1 TO STRING -11 (Each 52)
572 x575Wp =328.90KWp
ARMODU SDNAIL:
OSOLAR MONOPRCMOUDLES
iHo2.44V,13.55A) 3

6DA-32
JARRAY-3
STRING-1 TO 11 EACH STRING 52MODULES (11 x 52) =572 Modules x 575Wp = 328.90KWp
TOTAL = 328.90KWp
VIlII. SUNGROW- STRING INVERTER-4:
Make SUNGROW
SINo : 12381200253
Rated Power :295 KW ted,
Rated Voltage DC 500 V- 1500V
AC800 V
LT PANEL
/C CABLE SIZE :1Rx3Cx240Sgmm Ar.AI XLPE Cable from MAIN
30A DC FUSE (1000V- 14Nos. IN BUILT IN INVERTER)
FED FROM :JINKO SOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W, 42.44V, 13.55A)
(572Nos x 575Wp)= 328.90KWp
STRING-1 TOSTRING -11 (Each 52)
572 x 575Wp = 328.90KWp
SOLAR MODULESDETAIL:
JINKO SOLAR MONO PERC MOUDLES
(EACH SPVM ARE 575W, 42.44V, 13.55A)
ARRAY-4 3
328.90KWp
STRING-1 TO 11 EACH STRING 52MODULES (11x52)= 572 Modules x575Wp =
TOTAL =328.90KWp
DX. 15KVA 800/415V AC AUXILARY TRANSFORMER:
15KVA
Capacity
Volts 800VI415V

Make INTELLE POWER


Pri.Voltage(lnput) 800V

Sec. Voltage (Output) 415V


Cable: 1Rx 3.5C x 35sqmm AI. Ar. Cable from INVERTER AUXIALLARY OUTPUT.
X. MAIN AUX PANEL
Incoming :32A 4P, MCB
Outgoing :6A 2P MCB- 2Nos
:20A 2P MCB1 Nos
:16A 4P MCB-2Nos
:10A 4P MCB-1Nos
:6A 4P MCB-1 Nos
x 35sqmm Al. Ar. Cable from 15KVA Aux Transformer

DgI-32
Xl. LIGHTING PANEL:
Incoming :25A, 30mA, 4P, ELCB
Outgoing :6A 4P MCB 2Nos
16A 4P MCB1 no
6A 2P MCB -2 nos
1Rx20x06mm AL.
Bus bar: Phase: 1Rx25x06mm AI. Neutral:

Xl. UPS PANEL:


Incoming :20A 2P, MCB
:16A 2P MCB - 2Nos
Outgoing :10A 2P MCB 1Nos
: 6A SP MCB -5 Nos 1Rx20x06mm AL.
Al. Neutral:
Bus bar: Phase: 1Rx25x06mm
UPS:3KVA
Lighting Load: 2KW.

1
6 )0
L )0

Technical
Assistant Electrical Inspector/
Guindy, Chennai-600032.