Tech Specs

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND

DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

2.3 TECHNICAL SPECIFICATION

The following terms may be encountered in this specification document and shall be
interpreted as follows:

Hz - Hertz
kW (MW) - kilowatt (megawatt)
VA, (kVA, MVA) - volt-ampere (kilovolt-ampere, megavolt-ampere)
A (kA) - Ampere (kiloAmpere)
V (kV) - Volt (kiloVolt)
AC - Alternating Current
DC - Direct Current
IN - Nominal current
UN - Nominal voltage
Ah - Ampere-Hours
Min/(Max.) - Minimum (Maximum)
µ (prefix) micro -
n (prefix) nano -
rms - Root Mean Square
p.u. - per unit
p/p - peak to peak
F - Farad
°C - degrees centigrade
K - kelvin
J - Joules
N - Newton
Ω (kΩ, TΩ) - Ohms (kilo-ohms, Tera-ohms)
Nm - Newton meter
Pa, - Pascal, Newton per square meter
Bar - 1 bar 0.1MPa
IEC - International Electro-technical Commission
IP - Ingress Protection
EMC - Electromagnetic Compatibility
RTU - Remote Terminal Unit
TCP/IP - Transmission Communication Protocol/ Internet Protocol
LAN - Local Area Network
IED - Intelligent Electronic Device
LED - Light Emitting Diode

Page 16 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

2.3.1 SCOPE

The scope covers the design, manufacture, supply and delivery of twenty (20) pre-wired
protection and control panels. The supply requirements for the protection and control panels
are as follows:

Panel Type Quantity Description


Main 1 10 Main 1 Protection and control Panel For
Protection and Transmission Feeders with Main 1 protection
Control relay
Main 2 10 Main 2 Protection and control Panel For
Protection and Transmission Feeders with Main 2 protection
Control relay and Bay Control Unit

2.3.2 PARTICULARS OF THE ELECTRICAL SYSTEM

The electrical system in which the protection and control relays installed on the above
mention panels will be used in is:
• Three phase 3 wire AC overhead-line and underground system at 400kV, 330kV, 220kV,
132kV, 110kV, 88kV, 66kV 33kV and 11kV.
• Three phase-4 wire AC Low voltage of 390V
• Secondary system is at 110V and 1A AC nominal values.
• Control system at 110V DC.
• AC system operated at 50 Hz, with approximately sinusoidal waveform with the frequency
variation not exceeding 2.5% from 50Hz. Designs should allow for these variations.
• The highest system voltage not normally exceeding the nominal system voltage by more
than 10%. The nominal system voltages are 400kV, 330kV, 132kV, 110kV, 88kV, 66kV,
33kV and 11kV.

Page 17 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

2.3.3 PARTICULARS OF THE ENVIRONMENT

The altitudes of the plants shall be taken as 1500 meters above mean sea level typical air
pressure 860 mbar.
The protection and control relays should be capable of being used under the following
environmental conditions.
• Ambient temperatures:

(i) Maximum: 50 °C

(ii) Minimum: minus 10 °C

(iii) Maximum daily average: 35 °C

• Altitude:

Average altitude of 1 500 metres above sea level.

 Humidity:
Relative Humidity of 80%.

• Dust:

Particular attention should be paid in the design of all equipment to ensure that there
is no damage to insulation through the ingress of dust, insects, and vermin and
relevant IP standards should be followed.

2.3.4 PARTICULARS OF THE SPECIFICATION

LANGUAGE, UNITS AND STANDARDS

All tenders, correspondence, description on drawings, illustrations or instructions shall be in


unambiguous English Language. SI units of measurements shall be used throughout.
The following standards shall apply;

IEC 60255, IEC 61850 and IEC 60529, standards. In the case of conflict between the
above stated standards and this specification, the ruling of this specification shall prevail.

Page 18 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


2.4 DESIGN AND PROPERTIES

The pre-wired protection and control panels shall be used on the transmission and sub-
transmission circuits on the ZETDC power network. The installed protection and control
relays should provide maximum protection for ZETDC power circuits.
2.4.1 All equipment specified in this specification shall be new, free from defects, of finest
quality, and produced by manufacturers engaged in the manufacture of these
products.

2.4.2 All the hardware and software supplied must be of most recent technology and be in
the supplier’s product line. Equipment must be fully supported by the product
supplier at time of delivery and must remain on the manufacturer’s list of supported
products for at least 5 years from date of delivery.

2.4.3 Relays shall be fully numerical microprocessor based complying with IEC 60255.
They shall have approved characteristics and be flush mounted draw out type in dust
proof cases. The relay operating time should not exceed 30ms. All relays shall have
self-supervision and self-monitoring facilities.

2.4.4 All protection functions in the relays to be supplied shall be freely configurable.

2.4.5 At least five years of proven field experience for the protection relay types is required.

2.4.6 The protection and control relays shall be of robust type, insensitive to changes of
temperature, vibration, dustproof etc.

2.4.8 Output contacts shall make firmly without bounce and the whole of the relay
mechanisms shall be unaffected by vibration or external magnetic fields.

2.4.9 All of the installed protection and control relays must be engineered for IEC 61850
integration.

2.4.10 MATERIAL

The protection and control panels alongside the installed accessories shall be of superior
quality. The material shall be of latest design and conform to the best engineering practices
adopted in the field.

2.4.11 PACKING

The packing should be able to withstand rough handling during transit of material at various
destinations. Each pre-wired protection and control panel shall be packed appropriately to
prevent damage.

Page 19 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


2.4.12 TYPE TEST

Results of Type tests or type test reports/certificates carried out by an independent


Technical Institute on previously manufactured protection and control relays must be
submitted with the bid.
The type tests shall include but not limited to:

 Dielectric tests.
 EMC tests.
 Mechanical tests.

2.4.13 TRAINING

 Training on the supplied relays shall be provided to the Engineers through transfer of
technical knowledge in English.
 Training shall include classroom training, instruction and explanation or onsite
demonstrations concerning the commissioning, operation and maintenance of the
protection and control relays supplied.
 5.6.3 The training shall be performed by qualified English speaking personnel.
 5.6.4 The training program and the competencies of the trainer(s) shall be subject
to approval by ZETDC.
 5.6.5 The training courses shall be designed to:

 Enable Engineers to configure and calculate settings for the protection relays/IEDs.
 Enable Engineers and Technicians to use the application software to interrogate the
IEDs.
 Enable Engineers and Technicians to carry out commissioning and routine testing of
the IEDs.
 Enable Engineers and Technicians to interrogate the IEDs from the Human User
Interface.

Training documentation;

 Documentation shall be provided covering each course to a level of detail so that the
text is self-explanatory and sufficient as future reference.
 Prior to the start of a course, each trainee shall receive at least one (1) set of
documentation covering that course.

 ZETDC shall be given adequate notice prior to the training, at least one week
notice prior to date of commencement of the training

Page 20 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


2.5 DELIVERABLES AND ACCESSORIES

 The winning bidder shall design, manufacture, supply and deliver 20 fully
dressed protection and control panels as guided by this specification. The 20 panels
shall include:
 10 x Main 1 Protection and control Panels with Main 1 protection relay,
 10 x Main 2 Protection and control Panels with Main 2 protection relay and a Bay
Control Unit.
 Main 1 and Main 2 relays shall be of different makes/manufacturers.
 The supplier shall provide engineering tools including but not limited to, application
software, 2 laptops and accessories for installation, commissioning and maintenance
of the relays
 The supplier shall provide all the engineering manuals for installation, commissioning
and maintenance.
 The supplier shall make provision for FAT of the protection and control system for
two ZETDC engineers.
 The Protection Relays shall be engineered for IEC 61850 communication.
 Design the protection drawings as guided by ZETDC. The protection philosophy and
system parameters required shall be provided by ZETDC. All protection and control
drawings shall be produced in AutoCAD format
 Training shall be provided to at least 15 Engineers upon delivery.

Page 21 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: xXXxxxxxxxxxxxxxxxxxxxxx


ZETDC/INTER/11/2024
2.6 TECHNICAL GUARANTEE SCHEDULE FOR 330KV FEEDER PROTECTION AND
CONTROL PANELS.

Please complete this schedule by stating the actual tendered specification and sign as
indicated.

Name of Manufacturer: ______________________________________


Model: ______________________________________
Type: ______________________________________
Data about offered equipment shall be filled in by the bidder in table below which
must be duly signed and dated. The following compliance schedule must be
completed and supported by technical specs/datasheets/brochures from
manufacturer. Please indicate in the last column where proof of compliance can be
located from the manufacturer’s spec sheet. Failure to attach the necessary proof
will result in automatic disqualification.

Important Note: The panel is to be supplied with at least the following equipment
installed:

 1 x Feeder Main Protection IED for Main 1 Protection Panel.


 1 x Feeder Main Protection IED and Bay Control Unit for Main 2 Protection and
Control Panel.
 Master Trip and Lockout Relays
 Trip Circuit Supervision Relays to monitor the circuit breaker trip circuit in the
closed and open states.
 Testing blocks to enable injection of test voltages and currents to protection
and metering units installed
 IEDs and lockout relays reset push buttons.

Page 22 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

2.6.1 TECHNICAL GUARANTEE SCHEDULE FOR 20(TWENTY) x 330KV FEEDER


PROTECTION & CONTROL PANEL

Reference
document
Tendered Remarks page (e.g.
ZETDC Found on
Item Description Unit
Requirement page 3,
section 3.1 of
brochure/data
sheet/manual/
drawing etc.)
ENCLOSURE

1. Material 3mm Mild Steel


Plate
2. Colour Hz Light Grey (G29)

3. OVERAL DIMENSIONS -

Length 800mm

4. Width 800mm

Height - 2200mm
5.
ACCESS

Rear Access
6.
Hind Access door,
Relays mounted on
fixed front panel
and flush mounted.
7.
Shall be fitted with
glazed front door to
cover the front
panel.
Doors shall be
provided with
8.
integral handles for
locking
It shall be possible
9. to securely fix the
Page 23 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


hinged front door in
open position
CABLE ENTRY
Type of entry Bottom centre entry
A
10. with removable
gland plates
ENVIRONMENTAL CONDITIONS

Service Temperature -5˚C to 55˚C


11. Range V
Temperature 0.1%/°C
12. influence V
Relative humidity 0 to 95% non-
13. V condensing
Degree of protection (IEC 60529), IP 54

PANEL WIRING AND TERMINAL BLOCKS

Connections Screw terminals for


connection of wires
14. using ring lug
terminal lugs for all
AC inputs
4mm2 connection
terminals for all AC
15. wiring and shall be
suitable for ring lug
termination
2.5mm2 connection
terminals and screw
16.
compression type
for all dc wiring
No cables shall be
17. visible from the front
face.
Outgoing Provision for
Connections outgoing
Provision connections from
18. the protection
cubicles shall be
made for multi-core
cables
Ferruling Standards All panel wiring
shall be identified
19.
by ferrules at all
terminations. No
Page 24 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


ferrule number shall
appear on more
than one circuit
Ferrule number
shall change at
every break in the
20.
circuit, i.e. all
switches, coils,
contacts, etc
Particular attention
shall be paid to
ensuring that ferrule
21.
numbers conform to
those on the wiring
diagram
Colour coding for all
AC wiring in the
22. panel required for
easier identification
of ac wiring cables
The format of the
ferrule number shall
include the cable
core identity and
sitting position. For
example k510/
23.
x310.28 where k510
is the cable core
identity and x310 is
the terminal block,
28 is the terminal
number
Core Sleeving Each cable core in
the tripping circuit
24.
shall have a red
sleeve
Trip Links Trip circuits shall be
wired via test
25.
switches and Trip
Links
Terminal Terminals should be
Arrangement arranged so that
terminations of any
incoming wiring
26.
provided at site
under separate
contract are directly
visible.
Page 25 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Terminal blocks
shall be placed in
accessible positions
27.
adjacent to the
incoming cable
entries.
Terminations shall
be grouped
according to their
functions and labels
shall be provided on
28.
the fixed portion of
the terminal blocks
showing the
functions of the
groups
All terminal blocks
shall have a
29.
minimum of 20%
spare terminals.
Terminations All incoming and
outgoing
connections shall
be terminated at a
terminal block.
30.
Direct termination
on to auxiliary
switches, links and
fuses will not be
accepted.
Panel Trunking Panel wiring shall
be adequately
31.
accommodated in
panel trunking.
All panel trunking
32. shall have covers
Testing Facilities Panel shall be
provided with test
terminal blocks that
will isolate plant
33. from relay circuit in
order to facilitate
maintenance testing
(isolate all ac and
dc circuits)
The appropriate test
34. plugs shall be
provided.
Page 26 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Panel dc and ac All ac and dc
circuits protection circuits shall be
35. protected by
appropriate rated
MCBs
Anti-condensation Low energy heaters
Heaters shall be provided in
each panel to
prevent
condensation and
36. - the internal design
shall be such as to
permit free
circulation of air
without the ingress
of dust or vermin;
A manual heater
control switch shall
37. -
be provided inside
the cubicle.
Panel Lighting The panel shall be
provided with
sufficient lighting of
38. -
the energy saver
type and socket
outlet
A door position
switch to be fitted
for automatically
39. -
switching on panel
lighting when the
door is open(ed)
VOLTAGE WITHSTAND TESTS -
Tests All secondary and
panel wiring shall
withstand a test
40. -
voltage of 2 kV to
earth for one
minute.
PANEL LABELS -
Panel Identification The panel shall
have a label for the
protected circuit at
41. -
the top , ie
WARREN 330kV
FEEDER

Page 27 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Protection Function Each relay on the
panel face shall
have a label
42. - indicating the main
function of the relay
e.g. MASTER TRIP,
etc
Relay Scheme The rear of each
Identity relay or switch in
the scheme shall
have a label
carrying its scheme
identity e.g. F10,
F210, etc
43.
All panel
accessories and
relays must be able
to operate with the
station voltage
which is 50V dc and
or 220V ac

Page 28 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


2.6.2 TECHNICAL GUARANTEE SCHEDULE FOR 330KV FEEDER MAIN PROTECTION
RELAY.

Please complete this schedule by stating the actual tendered specification and sign as
indicated.

Name of Manufacturer: ______________________________________


Model: ______________________________________
Type: ______________________________________
Data about offered equipment shall be filled in by the bidder in table below which
must be duly signed and dated. The following compliance schedule must be
completed and supported by technical specs/datasheets/brochures from
manufacturer. Please indicate in the last column where proof of compliance can be
located from the manufacturer’s spec sheet. Failure to attach the necessary proof
will result in automatic disqualification.

Reference
document
Tendered Remarks page (e.g.
ZETDC Found on
Item Description Unit
Requirement page 3,
section 3.1 of
brochure/data
sheet/manual/
drawing etc.)
1. Relay Type - Numeric

2. Enclosure Material Metallic plate

3. Frequency Hz 50

4. Rotation - ABC

ENVIRONMENTAL
CONDITIONS
5. Operating ˚C -5 to +55
temperature range
Degree of protection - At least IP 30
6. by enclosure when
panel-mounted

Page 29 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


POWER SUPPLY

Nominal voltage V 110VDC / 220VDC


7.
AC INPUT
CURRENTS
Nominal current, A 1A, 3phase,
8.
Continuous withstand A ≥3x
9.
Short time withstand A ≥ 10 x for 1s
10.
AC INPUT
VOLTAGES
Nominal Voltage, 110VAC phase to
11. V phase
Continuous withstand ≥1.5 x
12. V
Short time withstand ≥2x for 1s
13. V
TRIP OUTPUTS

Rated Voltage 250


14. V DC
Continuous current ≥6
15. withstand A
Make current ≥ 30A at 250V dc
16. A
Thermal withstand ≥ 30A for 1 s
17. A
CONTROL SIGNAL
OUTPUTS
Rated Voltage 250V dc
18. V DC
Continuous current ≥6
19. withstand A
Make current ≥ 10A at 250V DC
20. A
Thermal Withstand ≥ 15A for 1 s
21. A
CONTROL SIGNAL
INPUTS

Page 30 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Rated Voltage 110/125VDC
22. V DC 220/250VDC
TERMINAL BLOCK
CONNECTIONS
Ac Inputs Shall be suitable for
4 mm2
23. -
compression/ ring
lug
Binary I/0 Shall be 1.5-2.5
mm2 and
24. -
compression/ ring
lug
TYPE TESTS Type tests to
conform to IEC
-
60255

GENERAL

Human Machine (HMI) indicates:


Interface (HMI) measurement
values, operating
25. - messages, and
device
maintenance
messages
A minimum of 4
lines for clear
26. - annunciation of
alarm conditions on
the display unit
A minimum of 15
27. - configurable LEDs
Keypad to select
the following
operations: display
of metering and
operating data,
alarm messages,
28. -
clearing of alarms
and resetting,
acknowledgement,
and access to
protection and
other relay settings
PROTECTION
FUNCTIONS
Page 31 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Line Differential Phase segregated
Protection (function current differential
29. -
87L) protection with high
sensitivity.
Two settable slopes
with adjustable
- intersection points
and minimum pick-
up values
Through-fault
- stabilization
Distance Full Scheme type
Protection(21) - for phase-earth and
phase-phase faults
At least four
Independent
measuring zones of
protection using
both polygon and
mho characteristic
for all fault types
At least one
reverse measuring
zone
At least two
overreaching zones
Power swing
blocking facility
Load encroachment
functionality
Switch-onto-fault
capabilities
Line check function

Voltage transformer
supervision
Definite Time And At least three, four-
Inverse Time step overcurrent
Overcurrent elements per group
Protection (functions shall be included to
30. -
50/51) provide phase,
negative-sequence
and residual
protection.
Definite time and At least three, four-
31. Inverse Time Earth step ground fault
Page 32 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Fault Protection overcurrent
(50N/51N) elements per
group.
Over/Under voltage At least two stage
32. Protection (functions - Overvoltage
27/59) protection
At least two stage
- Under voltage
protection
Over/Under At least two stage
frequency protection over-frequency and
- two-stage
underfrequency
protection.
Circuit Breaker Circuit breaker
Failure Protection failure protection
33. -
(RBRF/50BF) with adjustable
RBRF operate time
CBFO Mode Both current
detection and
34. - circuit breaker
status options shall
be available
Auto reclose(79) Selectable high
speed or delayed
auto reclose with a
35. - minimum five (5)
shots.

CONTROL
FUNCTIONS
Control and Apparatus control
Interlocks for a complete
transformer bay
with at least five (5)
switches. Ready to
36.
use interlocking
modules for
different switchgear
arrangements

Based on Select-
37. Before-Operate
Principle
Selection and
38. reservation function

Page 33 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


to prevent
simultaneous
operation
Selection and
39. supervision of
operator place
Command
40. supervision
Blocking and
41. deblocking of
operation
Blocking and
deblocking of
42.
updating of position
indications
Overriding of
43. interlocking
functions
Overriding of
44. synchro check
Pole discordance
45. supervision
Operations counter
46. and breaker
monitoring
Trip circuit
47. supervision for two
(2) trip circuits
Synchronising or
48. synchro-check
facility
ANCILLARY
FEATURES
Disturbance/ Event Disturbance
Recording recorder capable of
49. -
recording analogue
and digital signals
Signals to be used
50. - for triggering must
be selectable
At least 70
51. - Disturbance/ Event
records
At least 72
52. - channels for binary
signals

Page 34 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


At least 20
53. - channels for
analogue signals
Minimum pre-fault
54. - time of 5 cycles per
event
Minimum fault time
55. - of 25 cycles per
event
At least 8 LEDs to
facilitate post fault
Diagnostics analysis including
56. -
identification of the
faulted phase and
type of fault
Long term storage
of the indication is
57. - not dependent
upon an auxiliary
supply
All indication shall
be clearly visible
58. -
without opening of
relay cases.
All LEDs shall be
capable of being
59. - reset without the
necessity of
opening the case.
Parameter Subset At least two setting
Selection groups to enable
60. - relay use under
different operational
configurations
Password Protection Provision for level
61. - access control by
password
INPUT/ OUTPUT

Digital Output At least six fast trip,


heavy-duty digital
62. - output contacts, as
specified in 14, 15,
16 and 17.
At least thirty
63. - flexible and
configurable output

Page 35 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


relays as specified
in 18, 19, 20 and21
External Input At least thirty
configurable
64.
external control
inputs.
COMMUNICATION/
INTERGRATION
Standard and IEC 61850, TCP/ IP
65. Protocol - protocols
Communication Ports One front Ethernet
66. - communication port
Rear Port. At least
67. - two Fibre Optic
Ethernet ports
Fibre Optic
(1310nm single
68. mode/850nm multi-
mode optical fibre
link(0-15km)
Relay Interrogation Windows-based PC
software for
69. -
settings and report
retrieval
Operating System
70. - to be WINDOWS
10 or higher
METERING &
MEASUREMENT
3 Phase Active
71. The following shall be MW Power
measured
3 Phase Reactive
72. MVar Power
3 Phase Apparent
73. MVA Power
Power Factor
74. -
Phase – Phase
75. V Voltage magnitude
Phase current
76. A magnitude
Power System
77. Hz Frequency

Page 36 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

2.6.3 TECHNICAL GUARANTEE SCHEDULE FOR 330KV FEEDER BAY CONTROL


UNIT

Please complete this schedule by stating the actual tendered specification and sign as
indicated.

Name of Manufacturer: ______________________________________


Model: ______________________________________
Type: ______________________________________
Data about offered equipment shall be filled in by the bidder in table below which
must be duly signed and dated. The following compliance schedule which must be
met 100% must be accompanied by technical specs/datasheets/brochures from
manufacturer. Please indicate in the last column where proof of compliance can be
located from the manufacturer’s spec sheet. Failure to attach the necessary proof
will result in automatic disqualification.

TECHNICAL GUARANTEE SCHEDULE FOR 330KV FEEDER BAY CONTROLLER


RELAY.

Corresponding
reference page
ZETDC in spec sheet
Item Description Unit Tendered (e.g. found on
Requirement Remarks page 3,
section 3.2
paragraph/line
etc.)
1. Relay Type - Numeric

2. Enclosure Material Metallic plate

3. Frequency Hz 50

4. Rotation - ABC

ENVIRONMENTAL
CONDITIONS
Operating ˚C -5 to +55
5. temperature range
Degree of - At least IP 30
6. protection by
Page 37 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


enclosure when
panel-mounted
POWER SUPPLY

Nominal voltage V 110VDC / 220VDC


7. (DC)

AC INPUT
CURRENTS
Nominal current, A 1A, 3phase,
8.
Continuous A ≥3x
9. withstand
Short time A ≥ 10 x for 1s
10. withstand
AC INPUT
VOLTAGES
Nominal Voltage, 110VAC phase to
11. V phase
Continuous ≥1.5 x
12. withstand V
Short time ≥2x for 1s
13. withstand V
TRIP OUTPUTS

Rated Voltage 250


14. V DC
Continuous current ≥6
15. withstand A
Make current ≥ 30A at 250V dc
16. A
Thermal withstand ≥ 30A for 1 s
17. A
CONTROL SIGNAL
OUTPUTS
Rated Voltage 250V dc
18. V DC
Continuous current ≥6
19. withstand A
Make current ≥ 10A at 250V DC
20. A

Page 38 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Thermal Withstand ≥ 15A for 1 s
21. A
CONTROL SIGNAL
INPUTS
Rated Voltage 110/125VDC
22. V DC 220/250VDC
TERMINAL BLOCK
CONNECTIONS
AC Inputs Shall be suitable for
4 mm2
23. -
compression/ ring
lug
Binary I/0 Shall be 1.5-2.5
mm2 and
24. -
compression/ ring
lug
TYPE TESTS Type tests to
25. - conform to IEC
60255
GENERAL

Human Machine (HMI) indicates:


Interface (HMI) measurement
values, operating
26. -
messages, and
device maintenance
messages
A minimum of 8
lines for clear
- annunciation of
alarm conditions on
the display unit
A minimum of 15
- configurable LEDs
HMI language :
- English
Keypad to select
the following
operations: display
of metering and
operating data,
-
alarm messages,
clearing of alarms
and resetting,
acknowledgement,
and access to
Page 39 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


protection and other
relay settings
PROTECTION
FUNCTIONS
Definite Time And At least three
Inverse Time overcurrent
Overcurrent elements per group
Protection (50/51) shall be included to
27. -
provide phase,
negative-sequence
and residual
protection.
Definite time and Earth fault elements
Inverse Time Earth shall be included to
28. Fault Protection provide neutral and
(50N/51N) residual (ground)
protection
At least three earth
fault elements per
parameter setting
group are required
Circuit Breaker Circuit breaker
Failure Protection failure protection
29. (CBFP/50BF) - with adjustable
CBFP operate time.

CBFO Mode Both current


detection and circuit
-
breaker status
options available.
ANCILLARY
FEATURES
Disturbance/ Event Disturbance
Recording recorder capable of
30. -
recording analogue
and digital signals
At least 70
- Disturbance/ Event
records
At least 72 channels
- for binary signals
At least 20 channels
- for analogue signals
Minimum pre-fault
- time of 5 cycles per
event

Page 40 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


Minimum fault time
- of 25 cycles per
event
Diagnostics At least 16 LEDs to
facilitate post fault
analysis including
31. -
identification of the
faulted phase and
type of fault
Long term storage
of the indication is
-
not dependent upon
an auxiliary supply
All indication shall
be clearly visible
-
without opening of
relay cases.
All LEDs shall be
capable of being
- reset without the
necessity of
opening the case.
Parameter Subset At least two setting
Selection groups to enable
32. - relay use under
different operational
configurations
Password Provision for level
33. Protection - access control by
password
INPUT/ OUTPUT

Digital Output At least six (6) fast


trip, heavy-duty
digital output
34. -
contacts, as
specified in 14, 15,
16 and 17.
At least 32 digital
output contacts, as
35.
specified in 14, 15,
16 and 17.
External Input At least 64
configurable
36.
external control
inputs.

Page 41 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024


COMMUNICATION/
INTERGRATION
Standard and IEC 61850, TCP/ IP
37. Protocol - protocols
Communication One front
38. Ports - communication port
Rear Port. At least
- two(2) Fibre Optic
Ethernet port
Relay Interrogation Windows-based PC
39. - software for settings
and report retrieval
Operating System
- to be WINDOWS
10 or higher
METERING &
MEASUREMENT
3 Phase Active
40. The following shall MW Power
be measured
3 Phase Reactive
MVar Power
3 Phase Apparent
MVA Power
Power Factor
-
Phase – Phase
V Voltage magnitude
Phase current
A magnitude
Power System
Hz Frequency

CONTROL
FUNCTIONS
Control and Apparatus control
Interlocks for a complete
feeder bay with 5
switches.
41. Ready to use
interlocking
modules for
different switchgear
arrangements

Page 42 of 49
STANDARD BIDDING DOCUMENT FOR THE DESIGN, MANUFACTURE, SUPPLY AND
DELIVERY 0F 20 PRE-WIRED 330KV PROTECTION CONTROL PANELS

Procurement Reference Number: ZETDC/INTER/11/2024

Based on Select-
42. Before-Operate
Principle
Selection and
reservation function
43. to prevent
simultaneous
operation
Selection and
44. supervision of
operator place
Command
45. supervision
Blocking and
46. deblocking of
operation
Blocking and
deblocking of
47.
updating of position
indications
Overriding of
48. interlocking
functions
Overriding of
49. synchro check
Pole discordance
50. supervision
Pole discordance
51. supervision
Synchronising or
52. synchro-check
facility
Trip circuit Trip circuit
Supervision supervision for two
53.
(2) coils.

Page 43 of 49