Raychem DS H86869 HTV en
Raychem DS H86869 HTV en
Raychem DS H86869 HTV en
Heating Cable Construction Certified for use in hazardous and ordinary areas and comes
with a 10 year product warranty.
Design life: 30+ years of design life, depending on application.
nVent RAYCHEM HTV cables meet the requirements of the
U.S. National Electrical Code and the Canadian Electrical
Code. For additional information, contact your nVent
representative or call (800) 545‑6258.
APPLICATION
Area classification Nonhazardous and hazardous locations
Traced surface type Metal
Chemical resistance Organic and aqueous inorganic chemicals and corrosives
SUPPLY VOLTAGE
HTV1 100–130 Vac
HTV2 200–277 Vac
RAYCHEM-DS-H86869-HTV-EN-2404 nVent.com/RAYCHEM | 1
SPECIFICATIONS
Maximum maintain or continuous 400°F (205°C)
operating temperature (power on)
Maximum intermittent exposure 500°F (260°C) for 2000 hours cumulative.
temperature (power on/off) Longer durations allowed between 500°F (260°C) and 400°F (205°C)
Temperature classification T2B 464°F (240°C) 28HTV2-CT
(T-Rating or Temperature ID numbers) T2D 419°F (215°C) 20HTV1-CT; 20HTV2-CT
Temperature ID numbers are consistent with T3 400°F (200°C) 5
, 8, 10, 12, 15 HTV1-CT
North America National Electrical Codes 5, 8, 10, 12, 15 HTV2-CT
T3A 356°F (180°C) 3HTV1-CT, 3HTV2-CT
Minimum installation temperature –76°F(–60°C)
Bus-Wire size 14 AWG
Thickness (nominal) 0.28 in (7.1 mm)
Width (nominal) 0.429 in (10.9 mm)
Weight (nominal) 114 lb/1000 ft (170 g/m)
Minimum bend radius –76°F (–60°C) ≤ T< –4°F (–20°C): 1" (25 mm)
–4°F (–20°C) ≤ T< 14°F (–10°C): 0.8" (20 mm)
14°F (–10°C) ≤ T< 50°F (+10°C): 0.6" (15 mm)
T≥ 50°F (+10°C): 0.5" (13 mm)
Design Life 30 years or more depending on application
(contact nVent for more details)
Power Retention Minimum 95% after 10 years at maximum
operating temperature of 400°F (205°C)
APPROVALS
For HTV Cable
Class I Division 1 (Zone 1*), Groups A, B, C, D Class I Zone 1 Group IIC Class II/III Division 1 (Zone 21*)
Class I Division 2 (Zone 2*), Groups A, B, C, D Groups E, F, G Zone 21 IIIC
-WS for Canada. * Per CE Code Table 18 Class I Zone 2 Group IIC Class II/III Division 2 (Zone 22*)
Groups F, G Zone 22 IIIB
Ex 60079-30-1 IIC T** Gb
Ex 60079-30-1 IIIC T** Db
Class I Zone 1 AEx eb IIC T** Gb
Zone 21 AEx tb IIIC T** Db
-WS for Canada
IECEx PTB 21.0007X
Ex 60079-30-1 IIC T** Gb
Ex 60079-30-1 IIIC T** Db
System's hazardous area location rating and ambient temperature range depend on the connection kits used (see schedule).
IEx 21.0097X
Ex eb mb 60079-30-1 IIC 85°C (T6)...215°C (T2) Gb
Ex tb 60079-30-1 IIIC T85°C...T215°C Db
** For system T-rating, refer to design document or see schedule.
RAYCHEM-DS-H86869-HTV-EN-2404 nVent.com/RAYCHEM | 2
Power Adjustment Factors
Voltage
15HTV2-CT 0.91 1.05
20HTV2-CT 0.92 1.04
28HTV2-CT 0.96 1.02
RAYCHEM-DS-H86869-HTV-EN-2404 nVent.com/RAYCHEM | 3
Ambient Maximum circuit length (in feet) per circuit breaker
temperature at
start-up 120 V 240 V
°F °C 15 A 20 A 30 A 40 A 50 A 15 A 20 A 30 A 40 A 50 A
50 10 96 128 192 226 226 192 256 384 462 462
0 –18 85 114 171 226 226 167 223 335 446 462
12HTV-CT
–20 –29 81 109 163 217 226 160 213 319 426 462
–40 –40 78 104 156 207 226 153 204 305 407 462
50 10 75 101 151 201 201 151 202 302 400 400
0 –18 67 89 133 177 201 132 176 264 352 400
15HTV-CT
–20 –29 63 84 127 169 201 126 168 252 336 397
–40 –40 60 80 121 161 193 120 160 240 320 381
50 10 60 80 120 160 169 115 154 230 307 330
0 –18 53 71 106 141 155 101 135 203 271 294
20HTV-CT
–20 –29 51 68 101 135 149 97 129 194 259 283
–40 –40 49 65 97 130 144 93 124 186 248 273
50 10 n/a n/a n/a n/a n/a 86 114 172 229 231
0 –18 n/a n/a n/a n/a n/a 76 101 152 202 208
28HTV2-CT
–20 –29 n/a n/a n/a n/a n/a 73 97 145 194 200
–40 –40 n/a n/a n/a n/a n/a 70 93 139 185 193
ORDERING DETAILS
GROUND-FAULT PROTECTION
To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to
comply with the requirements of nVent, agency certifications, and national electrical codes, ground-fault equipment protection
must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.
Many nVent RAYCHEM control and monitoring systems meet the ground-fault protection requirement.