Load Schedule
Load Schedule
:
ILF DOCUMENT NO.:
REV. NO.:
#REF!
6.6kV SWITCHBOARD
EQUIPMENT
LOAD CALCULATION CONSUMED LOAD
Classification of Load
Absorbed Load Equipment Load Factor Efficiency at Power Factor at Load Load Duty: Continuous Intermittent and Spares Stand-By
Rating Load Factor Factor C/I/S (x%=100) (y%=30) (z%=10)
C = A/B
KW = A/D
Reacceleration
kVAr = kW . tan
Feeder Type
Voltage (kV)
Load Type
Essential
A B C D E F G
Normal
Vital
Bus
kW kW pu pu cos Ø kW kVAr kW kVAr kW kVAr
1 PS0800PS-P001 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 01 13.80 M A X 2358.0 2500.0 0.94 0.95 0.95 C 2482.1 815.8
2 PS0800PS-P002 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 02 13.80 M A X 2358.0 2500.0 0.94 0.95 0.95 C 2482.1 815.8
3 PS0800PS-P003 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 03 13.80 M A X 2358.0 2500.0 0.94 0.95 0.95 C 2482.1 815.8
2 PS0800PS-P004 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 04 13.80 M A X 2358.0 2500.0 0.94 0.95 0.95 S 2482.1 815.8
3 PS0800PS-P005 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 05 13.80 M B X 2358.0 2500.0 0.94 0.95 0.95 C 2482.1 815.8
4 PS0800PS-P006 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 06 13.80 M B X 2358.0 2500.0 0.95 0.95 C 2482.1 815.8
3 PS0800PS-P007 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 07 13.80 M B X 2358.0 2500.0 0.95 0.95 C 2482.1 815.8
4 PS0800PS-P008 VFD 13.8/4.16kV for MAIN TSE PUMP MOTOR - 08 13.80 M B X 2250.0 2500.0 0.95 0.95 S 2368.4 778.5
MDB-01 MAIN LOW VOLTAGE SWGR LOADS 1090.3 817.7 41.7 31.3 42.7 32.0
MDB-02 MAIN PUMP MOTOR SWGR LOADS 1820.6 1137.3 58.2 36.1
Total Plant Running Load (TPRL): ( x% of 'E' ) + ( y% of 'F' ) 17816.0 kW 6859.4 kVAr 19090.9 kVA TOTALS In kW and kVAr 17803.5 6850.0 12.5 9.4 495.1 166.2
Total Plant Running Load (TPRL) With 20% future growth factor 21379.2 kW 8231.2 kVAr 22909.0 kVA
𝑘𝑉𝐴 = 𝑘𝑊 2 + 𝑘𝑉𝐴𝑅2 19075.8 15.6 522.3
Power factor (cos Ø) 0.93
Total Plant Peak Load (TPPL): ( x% of 'E' ) + ( y% of 'F' ) + ( z% of 'G' ) 18311.1 kW 7025.6 kVAr 19612.7 kVA
Total Plant Peak Load (TPPL) With 20% future growth factor 21973.4 kW 8430.7 kVAr 23535.2 kVA
Page 1 of 5
COMPANY DOCUMENT NO.:
ILF DOCUMENT NO.:
REV. NO.:
#REF!
400V ESSENTIAL SWITCHBOARD
EQUIPMENT
LOAD CALCULATION CONSUMED LOAD
Classification of Load
Absorbed Load Equipment Load Factor Efficiency at Power Factor at Load Duty: Continuous Intermittent and Spares Stand-By
Rating Load Factor Load Factor C/I/S (x%=100) (y%=30) (z%=10)
C = A/B
Reacceleration
kVAr = kW . tan
Feeder Type
Voltage (kV)
Load Type
Essential
A B C D E F G
Normal
Vital
Bus
kW kW pu pu cos Ø kW kVAr kW kVAr kW kVAr
4
LIFT PUMP STATION AUXILIARIES DISTRIBUTION BOARD
(MOTORIZED VALVES
SDB - SER - LS 0.4 S B X X 25.5 32.0 0.80 0.90 0.80 C 28.4 21.3
DRAIN PUMPS, CRANES, LIGHTING & SMALL
POWER,HVAC….. )
5 SDB - LAY LAYOUT LIGHTING DISTRIBUTION PANEL 0.4 S B X X 25.0 32.0 0.78 0.90 0.80 C 27.8 20.8
OPERATION & AMENITY LIGHTING & SMALL POWER MAIN
6 SDB - OP 0.4 S B X X 35.6 45.0 0.79 0.90 0.80 C 39.6 29.7
DISTRIBUTION PANEL
7 SDB - VAC - OP OPERATION & AMENITY HVAC DISTRIBUTION PANEL 0.4 S B X X 7.0 12.0 0.58 0.90 0.80 C 7.8 5.8
8 UDB - OP OPERATION & AMENITY UPS DISTRIBUTION PANEL 0.4 S A X X 12.4 16.0 0.78 0.90 0.80 C 13.8 10.3
9 MAIN SUBSTATION LIGHTING, SMALL POWER & HVAC MAIN
MDB - MSUB 0.4 S B X X 114.8 120.0 0.96 0.90 0.80 C 127.5 95.7
DISTRIBUTION PANEL
10 UDB - MSUB - SUB MAIN SUBSTATION UPS DISTRIBUTION PANEL 0.4 S B X X 11.4 16.0 0.71 0.90 0.80 C 12.7 9.5
11 GUARD HOUSE LIGHTING, SMALL POWER & HVAC MAIN
SDB - GH 0.4 S A X X 8.0 12.0 0.67 0.90 0.80 C 8.9 6.7
DISTRIBUTION PANEL
12 UDB - GH GUARD HOUSE UPS DISTRIBUTION PANEL 0.4 S A X X 1.8 6.0 0.30 0.90 0.80 C 2.0 1.5
13 MCC - WAH 01 WATER HAMMER MOTOR CONTROL CENTER 0.4 S A X X 15.0 20.0 0.75 0.90 0.80 I 16.7 12.5
14 MCC - CHL CHLORINATION BUILDING MOTOR CONTROL CENTER 0.4 S B X X 65.0 75.0 0.87 0.90 0.80 C 72.2 54.2
15 UDB - CHL CHLORINATION BUILDING UPS DISTRIBUTION PANEL 0.4 S A X X 2.0 6.0 0.33 0.90 0.80 C 2.2 1.7
16
FIRE TANK & PUMP STATION AUXILIARIES DISTRIBUTION
SDB - SER - FP BOARD (MOTORIZED VALVES DRAIN PUMPS, CRANES, 0.4 S A X X 35.9 45.0 0.80 0.90 0.80 S 39.9 29.9
LIGHTING & SMALL POWER,HVAC….. )
16
FIRE TANK & PUMP STATION AUXILIARIES DISTRIBUTION
SDB - SER - FP BOARD (MOTORIZED VALVES DRAIN PUMPS, CRANES, 0.4 S B X X 35.9 45.0 0.80 0.90 0.80 C 39.9 29.9
LIGHTING & SMALL POWER,HVAC….. )
17 ELECTRICAL FIRE PUMP 0.4 M A X X 110.0 125.0 0.88 0.90 0.80 I 122.2 91.7 DOL
18 WQM LIGHTING, SMALL POWER & HVAC MAIN
SDB - WQM 0.4 S A X X 23.0 30.0 0.77 0.90 0.80 C 25.6 19.2
DISTRIBUTION PANEL
19 UDB - WQM WQM UPS DISTRIBUTION PANEL 0.4 S A X X 23.0 30.0 0.77 0.90 0.80 C 25.6 19.2
20
Total Plant Running Load (TPRL): ( x% of 'E' ) + ( y% of 'F' ) 1132.0 kW 849.0 kVAr 1415.0 kVA TOTALS In kW and kVAr 1090.3 817.7 41.7 31.3 42.7 32.0
Total Plant Running Load (TPRL) With 20% future growth factor 1358.4 kW 1018.8 kVAr 1698.0 kVA
𝑘𝑉𝐴 = 𝑘𝑊 2 + 𝑘𝑉𝐴𝑅2 1362.9 52.1 53.3
Power factor (cos Ø) 0.80
Total Plant Peak Load (TPPL): ( x% of 'E' ) + ( y% of 'F' ) + ( z% of 'G' ) 1174.6 kW 881.0 kVAr 1468.3 kVA
Total Plant Peak Load (TPPL) With 20% future growth factor 1409.6 kW 1057.2 kVAr 1761.9 kVA
Page 2 of 5
COMPANY DOCUMENT NO.:
ILF DOCUMENT NO.:
REV. NO.:
#REF!
400V ESSENTIAL SWITCHBOARD
EQUIPMENT
LOAD CALCULATION CONSUMED LOAD
Classification of Load
Absorbed Load Equipment Load Factor Efficiency at Power Factor at Load Duty: Continuous Intermittent and Spares Stand-By
Rating Load Factor Load Factor C/I/S (x%=100) (y%=30) (z%=10)
C = A/B
Reacceleration
kVAr = kW . tan
Feeder Type
Voltage (kV)
Load Type
Essential
A B C D E F G
Normal
Vital
Bus
kW kW pu pu cos Ø kW kVAr kW kVAr kW kVAr
1 PS0800PS-P009 LIFT PUMP MOTOR - 01 0.4 M A X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
2 PS0800PS-P010 LIFT PUMP MOTOR - 02 0.4 M B X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
3 PS0800PS-P011 LIFT PUMP MOTOR - 03 0.4 M A X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
4 PS0800PS-P012 LIFT PUMP MOTOR - 04 0.4 M B X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
5 PS0800PS-P013 LIFT PUMP MOTOR - 05 0.4 M A X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
6 PS0800PS-P014 LIFT PUMP MOTOR - 06 0.4 M B X X 270.5 315.0 0.86 0.93 0.85 C 290.9 180.3 SOFT STARTER DRIVEN MOTORS
7 PS0800PS-P015 LIFT PUMP MOTOR - 07 0.4 M A X X 270.5 315.0 0.86 0.93 0.85 S 290.9 180.3 SOFT STARTER DRIVEN MOTORS
8 PS0800PS-P016 LIFT PUMP MOTOR - 08 0.4 M B X X 270.5 315.0 0.86 0.93 0.85 S 290.9 180.3 SOFT STARTER DRIVEN MOTORS
9 CAP-BANK A CAPACITOR BANK 0.4 S A X X #DIV/0! 0.80 0.80 S
10 UDB-SEC SEC S/S BUILDING LV BOARD 0.4 S A X X 2.4 2.4 1.00 0.80 0.90 C 3.0 1.5
11 CAP-BANK B CAPACITOR BANK 0.4 S B X X #DIV/0!
Rated power0.80
shall be higher0.80 S
12 UDB-SEC SEC S/S BUILDING LV BOARD 0.4 S B X
270.53 X
Absorbed Power derived 65.0 65.0 1.00 Absorbed
than 0.90Power which 0.80 is C 72.2 54.2
13 from Mechanical power / motor 270.53. Hence, consider next
As per BOD Section 9.17, The
14 efficiency higher rating for Standard MOtor
15 motor of power higher than Power which is 315 kW.
16 DC to revise design to consider
250KW to be connected to MV
Lift Pump Motors to be
voltage level. Revise and update connected to MV System.
Total Plant Running Load (TPRL): ( x% of 'E' ) + ( y% of 'F' ) 1820.6 kW 1137.3 kVAr 2146.6 kVA TOTALS In kW and kVAr 1820.6 1137.3 0.0 0.0 58.2 36.1
Update Load list and other
Load List and other relavant relevant documents (SLD, PBS,
Total Plant Running Load (TPRL) With 20% future growth factor 2184.7 kW 1364.8 kVAr 2575.9 kVA
documents. System Study 𝑘𝑉𝐴 = 𝑘𝑊 2 + 𝑘𝑉𝐴𝑅2
etc)` 2146.6 0.0 68.4
Power factor (cos Ø) 0.85
Total Plant Peak Load (TPPL): ( x% of 'E' ) + ( y% of 'F' ) + ( z% of 'G' ) 1878.8 kW 1173.3 kVAr 2215.1 kVA
Total Plant Peak Load (TPPL) With 20% future growth factor 2254.5 kW 1408.0 kVAr 2658.1 kVA
Page 3 of 5
COMPANY DOCUMENT NO.:
ILF DOCUMENT NO.:
REV. NO.:
#REF!
400V ESSENTIAL SWITCHBOARD
EQUIPMENT
LOAD CALCULATION CONSUMED LOAD
Classification of Load
Absorbed Load Equipment Load Factor Efficiency at Power Factor at Load Duty: Continuous Intermittent and Spares Stand-By
Rating Load Factor Load Factor C/I/S (x%=100) (y%=30) (z%=10)
C = A/B
Reacceleration
kVAr = kW . tan
Feeder Type
Voltage (kV)
Load Type
Essential
A B C D E F G
Normal
Vital
Bus
kW kW pu pu cos Ø kW kVAr kW kVAr kW kVAr
4
LIFT PUMP STATION AUXILIARIES DISTRIBUTION BOARD
(MOTORIZED VALVES
SDB - SER - LS 0.4 S B X X 25.5 32.0 0.80 0.90 0.80 C 28.4 21.3
DRAIN PUMPS, CRANES, LIGHTING & SMALL
POWER,HVAC….. )
5 SDB - LAY LAYOUT LIGHTING DISTRIBUTION PANEL 0.4 S B X X 25.0 32.0 0.78 0.90 0.80 C 27.8 20.8
OPERATION & AMENITY LIGHTING & SMALL POWER MAIN
6 SDB - OP 0.4 S B X X 35.6 45.0 0.79 0.90 0.80 C 39.6 29.7
DISTRIBUTION PANEL
7 SDB - VAC - OP OPERATION & AMENITY HVAC DISTRIBUTION PANEL 0.4 S B X X 7.0 12.0 0.58 0.90 0.80 C 7.8 5.8
8 UDB - OP OPERATION & AMENITY UPS DISTRIBUTION PANEL 0.4 S A X X 12.4 16.0 0.78 0.90 0.80 C 13.8 10.3
9 MAIN SUBSTATION LIGHTING, SMALL POWER & HVAC MAIN
MDB - MSUB 0.4 S B X X 114.8 120.0 0.96 0.90 0.80 C 127.5 95.7
DISTRIBUTION PANEL
10 UDB - MSUB - SUB MAIN SUBSTATION UPS DISTRIBUTION PANEL 0.4 S B X X 11.4 16.0 0.71 0.90 0.80 C 12.7 9.5
11 GUARD HOUSE LIGHTING, SMALL POWER & HVAC MAIN
SDB - GH 0.4 S A X X 8.0 12.0 0.67 0.90 0.80 C 8.9 6.7
DISTRIBUTION PANEL
12 UDB - GH GUARD HOUSE UPS DISTRIBUTION PANEL 0.4 S A X X 1.8 6.0 0.30 0.90 0.80 C 2.0 1.5
13 MCC - WAH 01 WATER HAMMER MOTOR CONTROL CENTER 0.4 S A X X 15.0 20.0 0.75 0.90 0.80 I 16.7 12.5
14 MCC - CHL CHLORINATION BUILDING MOTOR CONTROL CENTER 0.4 S B X X 65.0 75.0 0.87 0.90 0.80 C 72.2 54.2
15 UDB - CHL CHLORINATION BUILDING UPS DISTRIBUTION PANEL 0.4 S A X X 2.0 6.0 0.33 0.90 0.80 C 2.2 1.7
16
FIRE TANK & PUMP STATION AUXILIARIES DISTRIBUTION
SDB - SER - FP BOARD (MOTORIZED VALVES DRAIN PUMPS, CRANES, 0.4 S A X X 35.9 45.0 0.80 0.90 0.80 S 39.9 29.9
LIGHTING & SMALL POWER,HVAC….. )
16
FIRE TANK & PUMP STATION AUXILIARIES DISTRIBUTION
SDB - SER - FP BOARD (MOTORIZED VALVES DRAIN PUMPS, CRANES, 0.4 S B X X 35.9 45.0 0.80 0.90 0.80 C 39.9 29.9
LIGHTING & SMALL POWER,HVAC….. )
17 ELECTRICAL FIRE PUMP 0.4 M A X X 110.0 125.0 0.88 0.90 0.80 I 122.2 91.7 DOL
18 WQM LIGHTING, SMALL POWER & HVAC MAIN
SDB - WQM 0.4 S A X X 23.0 30.0 0.77 0.90 0.80 C 25.6 19.2
DISTRIBUTION PANEL
19 UDB - WQM WQM UPS DISTRIBUTION PANEL 0.4 S A X X 23.0 30.0 0.77 0.90 0.80 C 25.6 19.2
20
Total Plant Running Load (TPRL): ( x% of 'E' ) + ( y% of 'F' ) 1132.0 kW 849.0 kVAr 1415.0 kVA TOTALS In kW and kVAr 1090.3 817.7 41.7 31.3 14.2 10.7
Total Plant Running Load (TPRL) With 20% future growth factor 1358.4 kW 1018.8 kVAr 1698.0 kVA
𝑘𝑉𝐴 = 𝑘𝑊 2 + 𝑘𝑉𝐴𝑅2 1362.9 52.1 17.8
Power factor (cos Ø) 0.80
Total Plant Peak Load (TPPL): ( x% of 'E' ) + ( y% of 'F' ) + ( z% of 'G' ) 1146.2 kW 859.6 kVAr 1432.7 kVA
Total Plant Peak Load (TPPL) With 20% future growth factor 1375.4 kW 1031.6 kVAr 1719.3 kVA
Page 4 of 5
COMPANY DOCUMENT NO.:
ILF DOCUMENT NO.:
REV. NO.:
#REF!
400V ESSENTIAL SWITCHBOARD
EQUIPMENT
LOAD CALCULATION CONSUMED LOAD
Classification of Load
Absorbed Load Equipment Load Factor Efficiency at Power Factor at Load Duty: Continuous Intermittent and Spares Stand-By
Rating Load Factor Load Factor C/I/S (x%=100) (y%=30) (z%=10)
C = A/B
Reacceleration
kVAr = kW . tan
Feeder Type
Voltage (kV)
Load Type
Essential
A B C D E F G
Normal
Vital
Bus
kW kW pu pu cos Ø kW kVAr kW kVAr kW kVAr
1 PS0800PS-P009 LIFT PUMP MOTOR - 01 0.4 M A X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
2 PS0800PS-P010 LIFT PUMP MOTOR - 02 0.4 M B X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
3 PS0800PS-P011 LIFT PUMP MOTOR - 03 0.4 M A X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
4 PS0800PS-P012 LIFT PUMP MOTOR - 04 0.4 M B X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
5 PS0800PS-P013 LIFT PUMP MOTOR - 05 0.4 M A X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
6 PS0800PS-P014 LIFT PUMP MOTOR - 06 0.4 M B X X 250.0 270.0 0.93 0.93 0.85 C 268.8 166.6 SOFT STARTER DRIVEN MOTORS
7 PS0800PS-P015 LIFT PUMP MOTOR - 07 0.4 M A X X 250.0 270.0 0.93 0.93 0.85 S 268.8 166.6 SOFT STARTER DRIVEN MOTORS
8 PS0800PS-P016 LIFT PUMP MOTOR - 08 0.4 M B X X 250.0 270.0 0.93 0.93 0.85 S 268.8 166.6 SOFT STARTER DRIVEN MOTORS
9 CAP-BANK A CAPACITOR BANK 0.4 S A X X #DIV/0! 0.80 0.80 S
10 UDB-SEC SEC S/S BUILDING LV BOARD 0.4 S A X X 2.4 2.4 1.00 0.80 0.90 C 3.0 1.5
11 CAP-BANK B CAPACITOR BANK 0.4 S B X X #DIV/0! 0.80 0.80 S
12 UDB-SEC SEC S/S BUILDING LV BOARD 0.4 S B X X 65.0 65.0 1.00 0.90 0.80 C 72.2 54.2
13
14
15
16
Total Plant Running Load (TPRL): ( x% of 'E' ) + ( y% of 'F' ) 1688.1 kW 1055.2 kVAr 1990.8 kVA TOTALS In kW and kVAr 1688.1 1055.2 0.0 0.0 53.8 33.3
Total Plant Running Load (TPRL) With 20% future growth factor 2025.8 kW 1266.2 kVAr 2388.9 kVA
𝑘𝑉𝐴 = 𝑘𝑊 2 + 𝑘𝑉𝐴𝑅2 1990.8 0.0 63.3
Power factor (cos Ø) 0.85
Total Plant Peak Load (TPPL): ( x% of 'E' ) + ( y% of 'F' ) + ( z% of 'G' ) 1741.9 kW 1088.5 kVAr 2054.0 kVA
Total Plant Peak Load (TPPL) With 20% future growth factor 2090.3 kW 1306.2 kVAr 2464.8 kVA