UNIT 4 Protection of Alternator and Transformer
UNIT 4 Protection of Alternator and Transformer
UNIT 4
Alternator Protection
Faults
1) Stator winding faults.
2) Thermal overheating.
3) Rotor winding faults.
4) Loss of field.
5) Under/Over frequency.
6) Vibration &Bearing overheating.
7) Motoring of generator.
8) Faults because of external causes.
9) Over voltages.
10) Over speed.
11) Over current.
Differential Protection
Over current Protection
Under normal operating conditions, the currents in the pilot wires fed from CT connections are
equal. The differential current flowing through operating coil of relay is zero (I1-I2=0). When fault
occurs in the protected zone, balance is disturbed, the differential current flows through the operating
coil of relay causing its operation. Relay sends signal to the CB thereby alternator circuit is tripped.
Operation/Working:
When the generator is in a normal operating condition the sum of the currents flow in the secondary of
the current transformers is zero and the current flow into secondary to neutral is also zero. Thus the relay
remains de-energized. When the fault occurs in the protected zone (left of the line) the fault current flow
through the primary of current transformers and the corresponding secondary current flow through the
relay which trips the circuit breaker. When the fault develops external of the protective zone (right of the
current transformer) the sum of the currents at the terminal of the generator is exactly equal to the
current in the neutral connection. Hence, no current flows through the relay operating coil.
Overheating Protection of Alternator
Overheating are due to following reason
1. Overload
2. Failure of the ventilation or hydrogen cooling system
3. Shorted laminations in the stator iron
4. Core bolt insulation failures in the stator iron
Excessive overload is not likely since the prime mover rating is usually not much greater than the
generator rating. There is the possibility of overload due to high active power load coupled with high
excitation. If the power factor is below rating, this will give an alarm for high excitation. Failure of
the cooling system is also likely to be detected by operator alarms,
The other failure, involving core failures and heating will develop slowly and must be detected by
temperature measurements of some kind.
Loss of field or excitation can be caused in the generator due to excitation failure. In larger sized generator,
energy for excitation is often taken from a separate auxiliary source or from a separately driven DC
generator. The failure of auxiliary supply or failure of driving motor can also cause the loss of excitation in
a generator. Failure of excitation that is failure of field system in the generator makes the generator run at a
speed above the synchronous speed.
In that situation the generator or alternator becomes an induction generator which draws magnetizing
current from the system. The protective system in case of field failure by using under current relay
Stator winding of generator is connected to the common bus bar. Rotor field winding receives excitation
from the exciter. In the field circuit an under current relay coil is connected across a low resistance shunt. In
normal condition the voltage drop across a shunt is very minor & relay does not operate. But under field
failure the excitation current becomes much more & a considerable voltage drop appears across the shunt
which sends the current in relay trip coil which operates the relay & CB contacts are opened.
The turbine drives alternator. Alternator is connected to supply system through transformers, busbars
etc. and similarly so many alternators are connected to supply system. If input to any one turbine is
disturbed or stopped, then that alternator behaves as a synchronous motor by drawing power from
the lines. This is the reverse power flow condition that is undesirable and detected by using
directional relay in any one phase. Figure shows the induction type directional relay used for the
reverse power protection of alternator. Here the shunt magnet coil and series magnet coil are exited
from alternator to whom protection is to be provided. When power flow direction is correct, the disc
rotates in the normal direction and does not close trip contacts. But when the power flow reverses,
the disc rotates in opposite direction causing closure of trip contacts.
Numerical
1. The neutral point of a three phase 20 MVA, 11kV alternator is earthed through a resistance of 5Ω.
The relay is set to operate when there is an out of balance current of1.5A. The CTs have a ratio of
1000/5. What is the percentage of winding protected?
Minimum fault current which will operate the relay = 1000/5 × 1.5 = 300𝐴
𝑥
E.m.f. induced in x % winding = 𝑉 × = 6350.82(𝑥)/earth resistance = 63.508(𝑥) 𝑣𝑙𝑜𝑡𝑠
This current must be equal to minimum fault current which will operate the relay.
∴ 12.70(𝑥) = 300
∴ 𝑥 = 23.6188 %
10000=√ 3 *11*I
I =525A
Used for transformer winding faults detection. Works on the principle of balancing of currents of
primary & secondary sides under healthy conditions. Any path of fault current in between the placement
location of the CTs on the two sides of the transformer to be protected creates a difference of currents in
the CT secondaries current in the relays that operate to trip the CB. The CT ratios are so adjusted such
that under healthy conditions the secondary currents are equal and their resultant in the relay is zero.
The three leads of the primary winding of star–delta transformer are taken through the core of a current
transformer which carries a single secondary winding. The operating coil of a relay is connected to this
secondary. Under normal conditions(i.e.no fault to earth), the vector sum of the three phase currents is
zero and there is no resultant flux in the core of current transformer no matter how much the load is out
of balance. Consequently, no current flows through the relay and it remains inoperative. However, on
the occurrence of an earth fault, the vector sum of three phase currents is no longer zero. The resultant
current sets up flux in the core of CT, ultimately induces an e.m.f. in the secondary winding which
energizes the trip coil and protects the faulty transformer
Restricted earth fault protection provided for Delta / Star power transformer
In transformers, earth faults on secondary side are not reflected on primary side, when the primary winding is
delta connected or has unearthed star point. In such cases, an earth fault relay connected in residual circuit of
three CTs on primary side operates on internal earth faults in primary windings only. Because earth faults on
secondary side does not produce zero sequence currents on primary side. Restricted earth fault protection may be
then used for high speed tripping for faults on star connected earthed secondary winding of power transformer.
The restricted earth fault relay does not operate for earth fault beyond the protected zone of the transformer.
When fault occurs very near to the neutral point of transformer, the voltage available for driving earth fault
current is small. Hence fault current would be low. If the relay is set too sensitive to sense such faults, then it
may operate for external faults and switching surges also. Therefore relay setting is adjusted in such a way that it
operates for earth fault current of the order of 15 % of rated winding current. Such setting protects restricted
portion of the winding. Hence it is called as restricted earth fault protection.
Delta-Delta transformer
Overheating Protection
Temperature sensors like resistance temperature detectors (RTD), thermocouple are kept in transformer
winding assembly to sense the temperature.
-The sensor (RTD) is connected in wheatstone bridge circuit form as shown. Under normal working
condition R is adjusted such that bridge is balanced.
-When temperature of transformer increases beyond limit, the voltage drop across temperature sensor
(RTD) changes hence bridge is now imbalance. A voltage appears across point a & b. This voltage
output can be fed to alarm circuit or trip circuit of circuit breaker.
-The alarm is sounded, the operator can attend the fault. In case of severe fault, the temperature rise is
drastic, hence the circuit breaker operates.
Buchholz relay
location of buchholz relay
-Fluid actuated relay placed between the conservator and the tank containing the components
- to be protected such as the windings of transformers
- where abnormal arcing occurs such as in tap changing chambers (studs/contacts etc.)
The relay is located in the path of the oil from transformer tank to conservator. As seen from diagram, the
upper mercury switch operates the alarm circuit due to tilting of the float by accumulation of gas evolved
slowly in the transformer tank due to minor faults which may develop into major ones if the alarm is not
investigated. Further lower mercury switch operates the trip circuit to switch off the circuit breaker related
to the transformer when there is a sudden flow of oil from the transformer tank to conservator. Such flow
occurs when there is serious fault in the transformer tank. Here the float (lower) is placed in such a manner
that it senses the sudden violent movement of oil from transformer tank to conservator.
1. A three phase transformer having line voltage ratio of 0.4 kV/11kV is connected Star / Delta and
protective transformers on the 0.4 KV side have a current ratio of 500/5. What must be ratio of the
protective transformers on 11 kV Side? Draw a neat circuit diagram and indicate the given values at
appropriate places.
Ans –
Above parameters are sensed by appropriate sensors. The sensor output is fed to analog to digital
converter. It converts the respective analog signals into digital form
The microprocessor has set reference values stored in the memory.
The input voltage, oil level, temperature, output current are continuously monitored.
These values can be seen on LCD display which is interfaced with microprocessor.
When any parameters exceeds the permissible limit or set reference, the microprocessor sends command
to relay driver circuit.
The relay driver circuits operates respective relays (R1 or R2) depending upon the command.
QUESTION BANK
1. State the abnormalities and faults in alternator with necessary protection
2. State the common faults occurs in power transformer. Suggests the protection for these faults.
3. What are the difficulties in differential protection scheme used for transformer ?
4. Draw a diagram of differential protection scheme for a star connected alternator and explain its
working.
5. State salient features of microprocessor based protection relay. Draw block diagram of
microprocessor based over current relay.
6. Draw neat labelled diagram of Buchholz relay. B
7. State the specifications of CT and PT as a protective transformer.
8. How negative phase sequence current are set up in an alternator ? Draw protective scheme for same.
9. Describe restricted earth fault-protection scheme for 3 phase Delta/Star transformer with neat
diagram.
10. Give location of Buchholz relay and state application of it for transformer protection.
11. Draw the restricted earth fault protection scheme for 250 MVA delta/delta transformer.
12. Explain limitation of differential protection in a transformer.
13. How are the negative phase sequence currents setup in an alternator ? Suggest the protective scheme
for the same.
14. Suggest the type of protection necessary for following abnormal condition/fault in case of power
transformer : (i) Over heating (ii) Faults in tap changer (iii) Earth faults (iv) Inter-turn fault
15. Explain over heating protection scheme of 3 phase transformer.