ABB Utilities GmbH RTU560

Remote Terminal Unit


Connection and Settings
Bus Connection Unit 560BCU03

Applications, characteristics and technical data have Mounting the Module


to be taken from the hardware data sheet
The module must be mounted of the existing PBP
560BCU03 1KGT 150 410 connectors X1 and X2 on the back plane of the com-
munication subrack 23ET23. The 560BCU03 have to
be pluged to the Sub-D connector and will be fixed
with attached screws and contact slides.
Operation
Connections to the RTU560 Module is made by plug
The 560BCU03 may only be mounted at slot 69/4 and the attached ribble cable with sub connectors in the
77/2. The module will pluged of the plug-in terminal processing connectors of the 23ET23. The process-
strips in the communication subrack 23ET23. ing connectors are at Slot/module address 69/4 and
77/2 (see Fig. 1 : ).
The 560BCU03
The EMV values are only valid when the front plate is
V Supervised the system activation screwed tightly.
V Signalls the ALARM and WARNING The 24 V connecting cable of the 560BCU01 have to
V Signalls the I/O synchronization be pluged of the 24 V connector on 23ET23.

S1

560BCU03 23ET23

24 V connecting
cable

Fig. 1 : Mounting the 560BCU03 on back side the extension sub rack 23ET23

Dok. Nr.: 1KGT 150 461 V000 1 47


ABB Utilities GmbH

Connections and Setting 560BCU03 RTU560

Watchdog Minute pulse input TSI


The activity on the RTU560 bus is supervise by a re- The RTU560 communication units can be synchro-
triggering monoflop. ALARM and WARNING are acti- nized by the TSI input. Connecting the minute puls in-
vated if the RTU modules do not respond within about put TSI.
30 seconds.
Minute pulse output TSO
Alarm und Warning
The RTU560 communication units generate an inter-
ALARM and WARNING are activated by the watch- nal filtered minute pulse TSO. With this signal the
dog or by a RTU560 communication unit. On signal- other moduls will be synchronized. Connecting the
ling ALARM the signal WARNING is also activated. minute puls output TSO.

Plug--in terminal strip

ALR WRN TSO TSI


ALR

WRN

TSI +
TSI --
TSO +
GND

24 V DC

R 19
3.3 k
1

+ 24
V
30 s

Optocoupler
WRN
ALR
ATR

Watchdog supervision ALARM / WARNING Minute pulse output TSO Minute pulse input TSI

Fig. 2 : Logic block diagram of internal plug-in terminal strip wiring

48 Dok. Nr.: 1KGT 150 461 V000 1


ABB Utilities GmbH

RTU560 Connections and Setting 560BCU03

560BCU03
1KGT008000R0001

X2B X1B

ALR WRN TS0 TSI

Ribble cabe
Ribble cable

Sub connector
24 V Connecting cable

Front side

X2 X1

Back side

Fig. 3 : Front- and back view of the 23BCU03

Dok. Nr.: 1KGT 150 461 V000 1 49


ABB Utilities GmbH

Connections and Setting 560BCU03 RTU560

ABB Utilities GmbH


68309 Mannheim (Germany)
Telephone +49 (0) 621 381-7592
Telefax +49 (0) 621 381-7622 03/2001 Subject to alteration

50 Dok. Nr.: 1KGT 150 461 V000 1