1MRK504087-UEN B en OperatorAs Manual Transformer Protection IED RET 670 1.1
1MRK504087-UEN B en OperatorAs Manual Transformer Protection IED RET 670 1.1
1MRK504087-UEN B en OperatorAs Manual Transformer Protection IED RET 670 1.1
Manufacturer:
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Table of contents
Table of contents
Section 1 Introduction.....................................................................11
Introduction to the operator’s manual...............................................11
About the complete set of manuals for an IED............................11
About the operator’s manual.......................................................12
Intended audience.......................................................................13
Related documents......................................................................13
Revision notes.............................................................................14
Section 3 Overview........................................................................17
Operator overview............................................................................17
Identify the IED.................................................................................17
Communication............................................................................39
Overview................................................................................39
TCP-IP ...................................................................................39
SPA, LON and IEC 60870–5–103 settings.............................40
LDCM.....................................................................................41
Station communication...........................................................41
Analog modules...........................................................................42
Overview................................................................................42
Analog modules......................................................................42
I/O modules............................................................................43
HMI..............................................................................................43
Overview................................................................................43
LEDs.......................................................................................43
Screen ...................................................................................44
Functions................................................................................44
Change lock...........................................................................44
Differential protection...................................................................44
Overview................................................................................44
Transformer differential protection, two winding (PDIF,
87T) .......................................................................................44
Transformer differential protection, three winding (PDIF,
87T) .......................................................................................44
Control.........................................................................................45
Overview................................................................................45
Bay control (CBAY)................................................................45
Reservation input ..................................................................45
Bay reserve (CRSV)...............................................................45
Switch controller (CSWI)........................................................45
Circuit breaker (XCBR)...........................................................45
Circuit switch (XSWI)..............................................................46
Local/Remote switch (LocalRemote, LocRemControl)...........46
Control commands......................................................................46
Single command.....................................................................46
Logic rotating switch (GGIO)..................................................46
Selector mini switch (GGIO)...................................................46
Tap changer control and supervision (YLTC, 84) ..................46
Tap changer control and supervision (YLTC, 84)...................47
Automatic voltage control for tapchanger (ATCC, 90) ...........47
Automatic voltage control for tapchanger (ATCC, 90) ...........47
Monitoring....................................................................................47
Overview................................................................................47
Measurements (MMXU).........................................................47
Current phasors......................................................................47
Voltage phasors.....................................................................47
Current protection........................................................................53
Overview................................................................................53
Instantaneous phase overcurrent protection (PIOC, 50)........54
Four step phase overcurrent protection (PTOC, 51/67).........54
Instantaneous residual overcurrent protection (PIOC,
50N)........................................................................................54
Four step residual overcurrent protection (PTOC, 51N/
67N)........................................................................................54
Thermal overload protection, two time constants (PTTR,
49) .........................................................................................54
Breaker failure protection (RBRF, 50BF)...............................55
Pole discordance protection (RPLD, 52PD)...........................55
Broken conductor check (PTOC, 46).....................................55
Directional over-power protection (PDOP, 32).......................55
Directional under-power protection (PDUP, 37).....................55
Sensitive directional residual over current and power
protection (PSDE, 67N) .........................................................55
Voltage protection........................................................................56
Overview................................................................................56
Two step undervoltage protection (PTUV, 27).......................56
Two step overvoltage protection (PTOV, 59).........................56
Two step residual overvoltage protection (PTOV, 59N).........56
Overexcitation protection (PVPH, 24)....................................56
Loss of voltage check (PTUV 27)...........................................56
Voltage differential protection (PTOV 60)...............................56
Frequency protection...................................................................57
Overview................................................................................57
Underfrequency protection (PTUF, 81)..................................57
Overfrequency protection (PTOF, 81)....................................57
Rate-of-change frequency protection (PFRC, 81)..................57
Multipurpose protection...............................................................57
Overview................................................................................57
General current and voltage protection (GAPC)....................58
Secondary system supervision....................................................58
Overview................................................................................58
Current circuit supervision (RDIF)..........................................58
Fuse failure supervision (RFUF)............................................58
Control.........................................................................................58
Overview................................................................................58
Synchrocheck and energizing check (RSYN, 25)..................58
Logic rotating switch (GGIO)..................................................59
Tap changer control and supervision, 6 binary inputs
(YLTC, 84) .............................................................................59
Current protection........................................................................68
Voltage protection........................................................................68
Frequency protection...................................................................68
Multipurpose protection...............................................................68
Scheme communication..............................................................68
Secondary system protection......................................................69
Control.........................................................................................69
Monitoring....................................................................................69
Logic............................................................................................69
Function status.................................................................................69
Overview......................................................................................69
View differential protection values...............................................69
Transformer differential protection, two winding (PDIF,
87T) .......................................................................................69
Transformer differential protection, three winding (PDIF,
87T) .......................................................................................70
Restricted earth fault protection, low impedance (PDIF,
87N)........................................................................................70
High impedance differential protection (PDIF, 87).................70
Impedance protection .................................................................70
Phase selection with load encroachment (PDIS, 21).............70
Distance protection zones (PDIS, 21)....................................70
Directional impedance (RDIR)................................................71
Power swing detection (RPSB, 78)........................................71
Full-scheme distance protection, mho characteristic
(PDIS, 21) ..............................................................................71
Additional distance protection directional function for
earth faults (RDIR) ................................................................71
Mho Impedance supervision logic (GAPC)............................71
Power swing logic (RPSL)......................................................71
Full-scheme distance protection, quadrilateral for mho
(PDIS, 21) ..............................................................................71
Phase preference logic (PDIS, 21).........................................72
Current protection........................................................................72
Instantaneous phase overcurrent protection (PIOC, 50)........72
Four step phase overcurrent protection (PTOC, 51/67).........72
Instantaneous residual overcurrent protection (PIOC,
50N)........................................................................................72
Four step residual overcurrent protection (PTOC, 51N/
67N)........................................................................................72
Thermal overload protection, two time constants (PTTR,
49) .........................................................................................72
Breaker failure protection (RBRF, 50BF)...............................73
Pole discordance protection (RPLD, 52PD)...........................73
Bay reserve............................................................................79
Commands..................................................................................79
Single command.....................................................................79
Selector switch.......................................................................79
IEC60870–5–103....................................................................80
Automation bits, command function for DNP3.0
(AutomationBits) ....................................................................80
Selector mini switch (GGIO)...................................................80
Logic............................................................................................80
Tripping logic (PTRC, 94).......................................................80
Event counter.........................................................................80
Trip matrix logic (GGIO, 94X).................................................81
Logic gate...............................................................................81
Logic SR memory...................................................................81
Logic timer set........................................................................81
Boolean 16 to Integer conversion ..........................................81
Integer to Boolean 16 conversion...........................................81
Monitoring....................................................................................81
Disturbance report (RDRE)....................................................82
Generic measured value (GGIO)...........................................82
Measured value expander block............................................82
LEDs.......................................................................................82
Global positioning system......................................................82
Binary signal status report......................................................83
Event counter (GGIO)............................................................83
IEC61850 generic communication I/O functions 16 inputs
(GGIO) ...................................................................................83
IEC61850 generic communication I/O functions (GGIO).......83
Metering.......................................................................................83
Pulse counter logic (GGIO)....................................................83
Communications..........................................................................83
Remote communication..........................................................83
View station communication values.......................................84
View setting groups.....................................................................84
View test data..............................................................................85
Authorization................................................................................85
Test LEDs.........................................................................................85
Section 13 Reset..............................................................................91
Reset guide......................................................................................91
Reset LEDs.................................................................................91
Start and trip LEDs.................................................................91
All indication LEDs.................................................................91
Reset lockout...............................................................................91
Reset counters............................................................................92
Circuit breaker........................................................................92
Circuit switch..........................................................................92
Reset pulse counter...............................................................92
Function for energy calculation and demand handling
(MMTR) .................................................................................92
Tap changer control and supervision (YLTC).........................92
LDCM clear counters..............................................................92
Reset temperature functions.......................................................92
Section 14 Authorization..................................................................95
Overview...........................................................................................95
LogOn or logOff...........................................................................95
Authorization handling in the IED................................................96
Section 15 Glossary.........................................................................97
Glossary...........................................................................................97
Section 1 Introduction
en06000097.vsd
The Operator’s Manual (OM) contains instructions on how to operate the protection
IED during normal service once it has been commissioned. The operator’s manual
can be used to find out how to handle disturbances or how to view calculated and
measured network data in order to determine the cause of a fault.
The IED 670 Engineering guide (EG) contains instructions on how to engineer the
IED 670 products. The manual guides to use the different tool components for IED
670 engineering. It also guides how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. The third
part is an introduction about the diagnostic tool components available for IED 670
products and the PCM 600 tool.
The IEC 61850 Station Engineering guide contains descriptions of IEC 61850
station engineering and process signal routing. The manual presents the PCM 600
and CCT tool used for station engineering. It describes the IEC 61850 attribute editor
and how to set up projects and communication.
• The chapter “Safety information” presents warnings and notices, which the user
should pay attention to.
• The chapter “Overview” describes operations an operator may perform on a daily
basis or when the need arises.
• The chapter “Understand the local human-machine interface” describes how to
use the human-machine interface.
• The chapter “Understand the HMI tree” describes the different menu trees.
• The chapter “Read measured values” describes how to locate and identify
available measurement data.
• The chapter “Event list” describes the location and nature of recorded events.
• The chapter “Handle disturbances” describes how to retrieve disturbance
information and reset alarms.
• The chapter “Read and change settings” describes how to locate, and change
settings and parameters.
• The chapter “Diagnose IED status” describes the location and use of available
diagnostic tools.
• The chapter “Test the IED” describes the tests applicable to the IED.
• The chapter “Control and supervise the bay” describes how to use the Single
Line Diagram to open and close primary apparatuses.
• The chapter “Reset” describes resetting procedures.
• The chapter “Authorization”describes user categories and password procedures.
• The chapter “Glossary” describes words and acronyms used in the literature
describing the IED.
This manual does not contain any instructions for commissioning or testing.
Requirement
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027-UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179-UEN
2.1 Warnings
Always avoid touching the circuitry when the cover is removed. The
product contains electronic circuitries which can be damaged if
exposed to static electricity (ESD). The electronic circuitries also
contain high voltage which is lethal to humans.
Section 3 Overview
The Human machine interface (HMI) on the IED provides an ideal mechanism for
the day to day operation and even advanced use of the IED. The keypad, LCD and
LEDs on the front of the IED are what constitute the HMI. Troubleshooting, apparatus
control, monitoring, setting and configuring are all possible via this interface.
Through the screens and menu elements available, as well as the keypad, the user is
able to navigate throughout the menu structure and move from screen to screen. This
document is, to a great extent, arranged in the same way as the IED software is
structured and describes all aspects of operation via the HMI.
The operator can document disturbances so that their causes can be analyzed and
evaluated for future reference. For example, the fault currents and voltages at the time
of the fault can be documented. The operator can also retrieve data about protected
objects, providing further information for fault analysis. This implies viewing the
mean value of current, voltage, power and frequency or primary and secondary
measured phasors. The operator can check the IED status at any time.
In some cases the operator may need to change the way the IED operates. This might
include changing the active setting group or a parameter value. This must always be
done strictly according to applicable regulations because un-authorized changes may
lead to severe damage of the protected object especially if a fault is not properly
disconnected.
To identify the IED, open the diagnostics menu. The identity of the IED along with
other data is found under:
4.1 Overview
The human machine interface is used to monitor and to some extent control the way
the IED operates. The configuration designer can add functions that alert to events
requiring the attention of the operator.
Figure 1: 1/2 x 19” case and 1/1 x 19” case with small and medium LCDs
4.2 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs in the IED 670 series. LCD screens and other details may differ
but the way the keys function is identical. The keypad is illustrated in figure 2.
The keys used to operate the IED are described below in table 1.
The help key brings up two submenus. Key operation and IED information.
Opens the main menu, and used to move to the default screen.
The Local/Remote key is used to set the IED in local or remote control mode.
The E key starts editing mode and confirms setting changes when in editing mode.
Key Function
The right arrow key navigates forward between screens and moves right in editing mode.
The left arrow key navigates backwards between screens and moves left in editing mode.
The up arrow key is used to move up in the single line diagram and in menu tree.
The down arrow key is used to move down in the single line diagram and in menu tree.
• General operation
The General Operation submenu provides information about the IED keypad.
The I and O keys are used to open (OFF) and close (ON) breakers and disconnectors
when using the Single Line Diagram (SLD) in direct control situations.
• Reset LEDs
• Reset lockout
• Reset counters
• Reset temperature functions
The Reset LEDs submenu consists of two lower level menus which are the “Start and
trip LEDs” and “All indication LEDs” submenus. To reset a counter, the actual
counter must first be selected. The submenus and the their structures are discussed in
the “Reset” chapter of this document.
4.4 LCD
4.4.1 Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and time.
The remaining 5 lines are dynamic. This LCD has no graphic display potential.
4.4.2 Medium
The 1/2, 3/4 and 1/1 x 19” cases can be equipped with the medium size LCD. This is
a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28 lines
with up to 40 characters per line. To display the single line diagram, this LCD is
required.
4.5 LED
The LED module is a unidirectional means of communicating. This means that events
may occur that activate a LED in order to draw the operators attention to something
that has occurred and needs some sort of action.
The LED indication module comprising 15 LEDs is standard in IED 670s. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.
There are alarm indication LEDs and hardware associated LEDs on the right hand
side of the front panel. The alarm LEDs are found to the right of the LCD screen.
They can show steady or flashing light. Flashing would normally indicate an alarm.
The alarm LEDs are configurable using the PCM 600 tool. This is because they are
dependent on the binary input logic and can therefore not be configured locally on
the HMI. Some typical alarm examples follow:
The RJ45 port has a yellow LED indicating that communication has been established
between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
The contrast setting of the LCD can be adjusted from the LHMI menu tree when the
IED has started or from the PST tool in PCM 600. The contrast setting adjusted with
one of these methods is an offset to a factory set basic contrast setting.
Normally the basic contrast setting is not changed, but can if needed be adjusted as
follows:
Activate the setup and test screen for the LHMI by keeping the Reset key pressed
immediately after the dc power to the IED has been applied.
Press the I key to save and exit the screen and wait for the IED to start. Observe that
only the basic contrast setting will be saved.
4.7.1 Read
To read values and access information about the objects being monitored the operator
must navigate the menu tree using the arrow keys. The active submenu or value is
highlighted.
Navigation is as follows:
4.7.2 Change
To change a parameter setting the following steps should be followed:
4.7.3 Control
The HMI offers the operator the opportunity to exercise direct local control over
breakers and other apparatuses in the bay using the graphic display and designated
keys on the front panel of the IED.
By pressing the L/R key until the uppermost of the two LEDs next to the key lights
up, local operator control can be exercised from the HMI.
An apparatus is selected using the up and down arrow keys. The active apparatus is
highlighted in the display.
5.1 Overview
• Control
• Measurements
• Events
• Disturbance records
• Settings
• Diagnostics
• Test
• Reset
• Authorization
• Language
6.1 Overview
1. Analog primary values are the quantities measured on the primary side of the
current and voltage transformers (CTs and VTs).
2. Analog secondary values are the quantities measured on the secondary side of
the current and voltage transformers. These are the quantities measured on the
Transformer module (TRM) inputs.
3. Analog mean values are the quantities measured at the inputs of the milliampere
module (MIM).
4. Under Monitoring a number of submenus are available. These include Service
values, Current phasors, Voltage phasors, Current sequence components and
Voltage sequence components.
5. Metering displays the pulse counter function. The measurements available here
show pulse counter status data.
6.2.1 Overview
The analog primary values are analog quantities measured on the primary side of the
TRM and reflect the actual current or voltage on the primary side of the VTs and CTs.
The ratio is adjusted under settings and also depends on the rating of the TRM. 24
primary values and phase angles are displayed in this view.
6.3.1 Overview
Analog secondary values shows secondary CT currents and VT voltages. These are
the actual current and voltage values at the TRM inputs.
6.4.1 Overview
Measurements from the Milliampere Input Module (MIM) are found in this part of
the measurements menu. Data from either the hard wired mA module or the Signal
Matrix Tool mA modules are shown here.
on the settings for the Milli-ampere Module. In the menu for settings, the range and
a transformation factor can be adjusted to suit the application. This means that an
input 3 mA may be displayed as temperature of 45 degrees. The output values shown
are without units.
Measurements/Monitoring/Voltage phasors/VP
Phase to phase voltages and phase angles are displayed here. Up to three sets of
voltage data can be displayed.
Measurement/Monitoring/Phase-Earth/VN
Phase to earth voltages and phase angles are displayed here. Up to three sets of voltage
data can be displayed.
The current sequence component under monitoring displays the positive (I1),
negative (I2) and zero sequence (I0) current values for a three phase line, both
magnitude and phase angle for each component are displayed. These indicate how
well balanced a system is. In an ideal balanced system the zero sequence current
should be zero, the positive sequence current should be equal to the current of each
phase with the same phase angle (relative to GPS) as the L1 phase signal and the
negative sequence current should be zero.
Measurements/Metering/Pulse counter/PC
The output data generated from the pulse counter function include data about the
status of the counter and counter values.
Measurements/Metering/ThreePhEnergMeas/ETP
The output data generated from the energy measuring function includes active
forward/reverse energy and reactive forward/reverse energy.
7.1.1 Overview
Events displays recorded events such as trips and breaker opened or closed.
Events
Displays a list of events in chronological order and where each event has a time stamp.
The latest event is at the top of the list.
Using the manual trigger generates an instant disturbance report. Use this function to
get a snapshot of the monitored line. Follow the path below and answer yes in the
Execute manual trig dialog box.
It takes a minimum of three minutes for the IED to save the new
settings, during this time the DC supply must not be turned off.
9.1.2.1 Overview
The synchronization settings are divided into categories Time synch, Time synch
BIN, Time synch SNTP, Time synch DST Begin, Time synch DST End, Time synch
time zone and Time synch IRIG-B. The settable parameters are found under each
category.
9.1.2.2 TimeSynch
Settings/Time/Synchronization/TimeSynch
Here the parameters FineSyncSource, CourseSyncSrc and SyncMaster are switched
on or off.
9.1.2.3 TimeSynchBIN
Settings/Time/Synchronization/TimeSynchBIN
Binary input synchronization settings available here are the position of the of the
module, the number of the binary input and the detection mode.
9.1.2.4 TimeSynchSNTP
Settings/Time/Synchronization/TimeSynchSNTP
Here the IP addresses for the Simple Network Time Protocol servers are set.
9.1.2.5 TimeSynchDSTBegin
Settings/Time/Synchonization/TimeSynchDSTBegin
The starting point for Daylight Savings Time is set here.
9.1.2.6 TimeSynchDSTEnd
Setttings/Time/Synchronization/TimeSynchDSTEnd
The end point of Daylight Savings Time is set here.
9.1.2.7 TimeZone
Settings/Time/Synchronization/TimeSynchTimeZone
The time zone according to Coordinated Universal Time (UTC) is set here.
Settings/Time/Synchronization/TimeSynchIRIG-B
The type of input, time domain, type of encoding and time zone for IRIG-B are set
here.
Parameters under General settings that are changed will cause the IED to restart. This
occurs automatically and requires no manual intervention.
9.2.1.1 Overview
Under Power system in General settings there are four parameter categories. These
are Identifiers, Primary values, three phase analog group and three phase analog sum
group.
9.2.1.2 Identifiers
9.2.2 Communication
9.2.2.1 Overview
The parameter settings for communications are found under General Settings
\Communications. Communication settings cover network interfaces, protocol,
remote communication and reception of interlocking information.
9.2.2.2 TCP-IP
Settings/General settings/Communication/TCP-IP/Gateway
If a gateway is used to access the system the address to that gateway is entered here.
SPA and IEC cannot run at the same time and in this submenu one of the options is
chosen.
9.2.2.4 LDCM
Each instance of CRB has seven settable parameters where the channel mode can be
set on or off, terminal numbers can be entered, synchronization can be set to master
or slave and opto power can be set high or low.
Each instance of CRM has 17 settable parameters. These include those above and
others such as transmission delay and transmission current.
Multicommand send
Settings/General settings/Communication/Station communication/
MulticommandSend/MT
The up to ten instances of MulticommandSend settings allow the user to adjust the
maximum and minimum cycle time.
Multicommand receive
Settings/General settings/Communication/Station communication/
Multicommand receive/CM
The up to 60 instances of MulticommandReceive settings available here allow the
user to adjust the maximum and minimum cycle time, the pulse duration and mode
of operation. The mode of operation is either steady or pulsed.
Includes settings for the IED name, operation (on/off) and GOOSE.
9.2.3.1 Overview
Under Analog modules in the General settings menu there are settings for Analog
inputs and I/O modules. Within each instance of analog input there are settings for
all 12 channels that include the name of the channel, star point of the CT circuit, the
primary and secondary values from the measuring transformers (CTs and VTs). The
channel type and ratings are shown but cannot be changed.
The settings for binary inputs and outputs even include the milliampere input
modules. A mix of up to 14 instances of BIM, BOM and IOM is possible depending
on the physical configuration of the IED. Operation ON or OFF can be set for all of
these and for the BIMs oscillation release and oscillation block settings are available.
These settings are on board level and apply to all binary inputs or outputs on a board.
Here, settings for the Fourier filters, the minimum system voltage required to measure
frequency, the item designation of CTs or VTs, and the system voltage are set. These
settings are required by the preprocessing blocks and are usually only adjusted during
the initial engineering phase.
The milliampere modules (MIMs) are also found in the I/O Modules folder.
Parameters possible to set here are dead band settings and various current threshold
values.
9.2.4 HMI
9.2.4.1 Overview
Under HMI in General settings there are submenus for LEDs, Screen, Functions,
Reference channel service values and the Change lock function. In the LED submenu
there are settings for operation, illumination times, and sequence types for the LEDs
on the IED front panel. In the Screen submenu Contrast level, Default screen, Auto
repeat and Timeout display can be set. In the Functions submenu the Event list sorting
order and Distance presentation can be set.
9.2.4.2 LEDs
Settings/General settings/HMI/LEDs
9.2.4.3 Screen
Settings/General Settings/HMI/Screen
Local HMI setting parameters such as Language, Contrast level and Default menu
can be set here.
9.2.4.4 Functions
Settings/General Settings/HMI/Functions
The settings here are used to determine the way information is presented in the HMI.
9.2.5.1 Overview
Settings/GeneralSettings/Differential protection/
TransformerDiff2Wind(PDIF)/T2D
Parameters for available instances of T2D can be set here. These include the rated
voltages and currents for windings, the connection types, the current transformer
ratings and various other parameters.
Parameters for T3D can be set here. These include rated voltages and currents,
connection types (Y, D), current transformer ratings and various other parameters.
9.2.6 Control
9.2.6.1 Overview
Under Control in General settings, parameters for Apparatus control can be adjusted.
These are the parameters for among others Bay control, Switch controller,
Reservation input, Circuit breakers and Circuit switches. The parameters include
delay times, dependencies, pulse times and characteristics.
require different pulse lengths to react. The setting tOpenPulse is used to set the length
of the pulse required to open a breaker.
Settings/General settings/Control/TransformerTapControl/TCL
Tap changer parameters such as tap positions for low and high voltage and type of
code conversion are set here.
Settings/General settings/Control/TransformerTapControl/TCM
Tap changer parameters such as tap positions for low and high voltage and type of
code conversion are set here.
9.2.8 Monitoring
9.2.8.1 Overview
Under monitoring there are parameters for setting Service values, current phasors,
Voltage phasors, Disturbance reports and the Measured value expander block.
Settings/General Settings/Monitoring/ServiceValues/SVR
Displays three instances of SVR.
Displays available instances of the voltage phasor function (VP) with output data for
phase to phase voltage, (amplitude, phase angle). The setting parameters for
supervision levels, deadband etc. are set here
There are sets of settings with some categories of parameter settings per set (CSQ)
There are sets of settings with some categories of parameter settings per set (VSQ)
9.2.9 Metering
9.2.9.1 Overview
Under metering there are settings for the Pulse counter function. There are some
instances of the Pulse counter function. Each instance can be switched on or off and
a number of parameters can be adjusted.
Settings/General settings/Metering/PulseCounter/PC
In the Pulse counter folder there are a number of instances of the pulse counter
function (PC). Each instance has a setting and some settable parameters. The setting
“operation” is used to turn the function on or off. The parameters are adjusted to
change cycle times, pulse counter criteria and the like.
Settings/General settings/Metering/ThreePhEnergMeas/ETP
Parameters for activating the function, activate accumulation of energy values,
selection of time interval for energy calculation and forward/reverse pulse quantities
for accumulated energy values are found here.
9.3.1 Overview
There are some default setting groups. Under general settings, parameters in these
groups can be changed to suit the needs of an application. The default settings have
been chosen according to established practice in the industry but will usually require
a certain amount of adjustment to suit the requirements of individual applications.
9.3.2.1 Overview
The settings available for differential protection in Setting group N are not the same
as those under General settings. The main difference is that settings in the Setting
group N category can be changed on the fly without the IED requiring a restart. A
dialog box appears when attempting to make changes to setting group N. Choose OK
to proceed, or cancel to abort.
9.3.3.1 Overview
Under Impedance protection there are settings for Distance zones, Phase selection,
directional impedance, Power swing detection, and Automatic switch onto fault
protection. Each instance of a function can be switched on or off with the operation
parameter and the remaining parameter settings like rated current and voltage are data
required for the function to operate.
9.3.4.1 Overview
Under Current protection there are settings for Instantaneous phase overcurrent,
Phase overcurrent four step, Instantaneous residual overcurrent, Residual overcurrent
four step, Thermal overload with two time constants, Pole discordance and Breaker
failure. There are several instances of each function with parameter settings for rated
data, operation and many others. The thermal overload functions have temperature
threshold settings as well as many others necessary for adapting the function to a
particular application.
9.3.5.1 Overview
For Voltage protection there are settings for Under-voltage, Over-voltage, Residual
over-voltage and Overexcitation protection. There are three instances of parameters
in each category except in the case of Overexcitation which has two instances. Each
instance consists of a number of parameters that make it possible to switch the
function On or Off, set rated quantities or make other adjustments necessary for the
fine tuning of the function itself.
9.3.6.1 Overview
For Frequency protection there are settings for Underfrequency, Overfrequency and
Rate of change of frequency. Each category has some instances of parameters. All
functions can be set On or Off and have a number of other settable parameters such
as rated voltage and time delay before tripping.
9.3.7.1 Overview
Under Multipurpose protection there are several instances of General current and
voltage parameters. This function has current and voltage inputs. The parameters
available are based on the data from these inputs. Within each instance operation for
the included functions can be set to On or Off and a large number of parameters can
be set.
9.3.8.1 Overview
Under Secondary circuit supervision there are settings for Current circuit supervision
and Fuse failure. There are five instances of Current circuit supervision with
parameters for minimum operation current, rated current and operation. There are six
instances of Fuse failure supervision parameters for setting rated current, voltage,
operation mode and several other parameters.
9.3.9 Control
9.3.9.1 Overview
Under Control in the Setting group N menu settings for Synchrocheck, are available.
Some instances of settings are available meaning that the settings for all available
apparatuses can be made here. The synchrocheck settings include the selection of
voltage from busses or lines and the configuration parameters for circuit breakers.
Displays available instances of the synchrocheck function (SYN) with several settings
per instance. There are settings for operation, voltage differences and limits, time
delays etc.
9.3.9.4 Tap changer control and supervision, 6 binary inputs (YLTC, 84)
9.3.9.5 Tap changer control and supervision, 32 binary inputs (YLTC, 84)
9.3.9.6 Automatic voltage control for tapchanger, single control (ATCC, 90)
9.3.9.7 Automatic voltage control for tapchanger, parallel control (ATCC, 90)
9.3.10.1 Overview
Under Scheme communication there are settings for Zone scheme communication,
Zone current reversal, Local acceleration logic, EF Scheme communication and EF
Current reversal weak end infeed. In each category the function can be switched On
or Off and time delays, ratings and parameters can be set.
9.3.10.3 Current reversal and weak-end infeed logic for residual overcurrent
protection (PSCH, 85)
9.3.11 Logic
9.3.11.1 Overview
Under Logic there are settings for Trip logic, Trip matrix, Event counter, Logic gate,
Logic SR memory and Logic timer set. Under each of these function categories there
are a number of instances, each with a parameter set.
Displays available instances of the trip logic function (TR), each with settable
parameters for operation, selections, delay times, and pulse times.
9.3.11.4 LogicGate
9.3.11.5 LogicSRMemory
9.3.11.6 LogicTimerSet
9.3.12 Monitoring
9.3.12.1 Overview
Fault locator settings are found under Monitoring in the Setting Group N menu.
9.5 Language
Under the language part of the main menu the language options available in the HMI
are located. These vary depending on the configuration ordered.
Diagnostics/IED Status/General
Messages such as On, Ready and Fail indicate the status of each item on the list.
To identify the type of IED you are confronted with, navigate to identifiers using the
keypad. The path to identity parameters is shown below.
By following the menu path below the configuration of all hardware in the IED is
displayed as a list.
Diagnostics/IED Status/Installed HW
The list includes the slot number, the module name (Card) and its article number.
11.1 Overview
The test part of the tree view in the HMI has a number of submenus for test and
viewing activities. When IED test mode is set to ON functions are inactivated so that
no signals are transmitted during testing. Under Function test modes individual
functions can be activated. The LED test are also activated here.
The submenus for binary inputs and outputs as well as the submenu titled Function
status are used to view data generated by the system. These categories of data are
outlined below.
1. Binary output values has two submenus. These are Binary output modules
(BOM) and SMT binary outputs. Under these the status of binary outputs and
SMT outputs is displayed.
2. Binary input values has two submenus. These are Binary input modules (BIM)
and SMT binary inputs. These screens show the state of all the inputs on the
Binary input modules (BIM). These are represented as digits but may also be a
number if the input is being used to receive pulses for power measurement.
3. Differential Protection displays a choice of differential functions available to the
operator. Function related measurements can be viewed by navigating to the
screen for each individual function.
4. Distance protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each individual function.
5. Current protection displays a choice of functions. To view data related to these
functions it is necessary to choose one from the list and navigate to the screen
for the function in question.
6. Voltage protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each of the four functions available. Data shown here is mainly trip and start
related.
7. Frequency protection includes measurements from frequency functions.
Measurements show trip, start and similar data.
8. Multipurpose protection includes measurements showing data regarding trip
signals, start signals, current and voltage values.
11.3.1 Overview
Binary input values display the state of each individual input in the Binary input
modules (BIM). These are indicated with a 1 or 0 depending on whether a signal is
present or not. Binary input modules with enhanced pulse counting capabilities can
receive pulses used for power measurement. The number of pulses received is used
to measure power.
11.4.1 Overview
Binary output values show the status of each individual output in the Binary output
module (BOM). If the signal matrix tool is used binary outputs are depicted as virtual
outputs. Note, that only modules installed in the IED are shown in the HMI.
11.5.1 Overview
With the IED, in test mode the different protections (except line differential
protection) can be individually released for test here. Events can be disabled or
enabled.
Test of scheme communication logic, for residual overcurrent protection and distance
protection, as well as current reversal and weak end infeed logic, for distance
protection and residual overcurrent protection.
11.5.10 Control
Test/Function test modes/Control
Test of synchrocheck and energizing check function.
11.5.11 Monitoring
Test/Function test modes/Monitoring
Test of monitoring functions such as event counter and disturbance report.
11.5.12 Logic
Test/Function test modes/Logic
Test of trip logic and event counter functions.
11.6.1 Overview
In the Function status section of the Test menu, data useful to the user in Test mode
can be found. The information available here is not limited to test applications alone
and provides information about the system as a whole.
Displays available instances of T2WPDIF with several measured values each. The
data available here ranges from the general common trip signal to the magnitude of
the bias current. The magnitude of the second and fifth harmonic differential current
for all phases, block signals and start signals make up the bulk of the data presented
in this view.
Displays available instances of ZM with nine measurements per instance of ZM. The
output quantities shown here indicate trip and start signal status.
Test/Function status/Current/InstPhaseOverCurrent(PIOC)/IOC
Displays available instances of IOC with a number of measurements per instance
showing the trip status in general and per phase.
Test/Function status/Current/PhaseOverCurrent4Step(PTOC)/TOC
Displays instances of POCM with several measurements per instance. These
measurements are primarily trip and start signal indications from each phase and from
the various steps in the protection scheme.
Test/Function status/Current/InstResidualOverCurrent(PIOC)/IEF
Displays available instances of IEF with one trip value per instance.
Test/Function status/Current/ResidualOverCurrent4Step(PTOC)/TEF
Displays available instances of TEF with a number of measurements per instance.
The measurements indicate trip and start signal status as well as the 2nd harmonic
block signal status.
Displays available instances of TUV with several measurements per instance. The
measurement data includes operate/trip signals and start signals.
Displays available instances of EFC with some measurements indicating carrier and
trip status.
11.6.6.2 Current reversal and weak-end infeed logic for residual overcurrent
protection (PSCH, 85)
11.6.10 Control
There are large amounts of output data from the control functions. The main
categories of data are found under Synchrocheck, and Apparatus control. Apparatus
control has by far the largest amount of data since this includes all the interlocking
information for several different breaker arrangements.
Test/Function status/Control/Synchronizing(RSYN)/SYN
Displays available instances of SYN with a number of measurements per instance.
These include information about which lines and buses selected, various voltage and
frequency differences and feedback on synchronization status.
11.6.11.1 Interlocking
Displays available instances of the function (IF) with several boolean outputs per
instance. These indicate for which disconnect devices closing and switching of is
allowed and also indicate the status and validity of devices. For example, the
measurement named QB12OPTR indicates whether or not QB1 and QB2 are in the
open position. If the output for this measurement is 1 then QB1 and QB2 are in the
open position. A zero indicates that they are closed.
11.6.12 Commands
In the commands menu it is possible to view three sets of values. These are found
under the submenus Single command, Selector switch and IEC60870–5–103.
11.6.12.3 IEC60870–5–103
Test/Function Status/Control/Commands/IEC60870–5–103
Under this part of the HMI tree there are the following three submenus:
• IED Commands
• Function Commands
• User Defined Commands
Various IED, function and user defined command data can be viewed here.
11.6.13 Logic
Under the Logic function folder there is viewable data for trip logic (showing number
of poles that have tripped and trip signal information), event counter values, Logic
gate outputs, Logic SR memory output states and Logic timer set output states are
also shown here.
Test/Function status/Logic/TripLogic(PTRC)/TRP
Displays available instances of the function (TRP) with some measurements per
instance. The output data from each measurement is boolean and indicates the
existence of various trip signals. For example, if the output from parameter TRL1 is
one, this indicates that a trip signal from phase L1 has been generated.
Test/Function status/Logic/TripMatrix(GGIO)/TR
Displays available instances of the function (TRO) with some boolean output values
per instance. The output signals from this function block are typically connected to
other logic blocks or directly to IED output contacts.
Test/Function status/Logic/LogicGate/GT
Displays available instances of the gate output. The output data type is an integer with
a possible value from 0 to 255.
Test/Function status/Logic/LogicSRMemory/SN
Displays available instances of the function (SM). There are two measurement
parameters per instance, SMnn OUT (Output) and SMnn N_OUT (Output inverted).
The output data presented in the HMI is boolean and indicates whether or not a signal
is present. For example, an output of one from SM01 OUT indicates that a signal
exists on that output.
Test/Function status/Logic/LogicTimerSet/TS
Displays available instances of the function (TS). Each instance has output
parameters, TSxx_ON and TSxx_OFF where xx stands for the number of the instance.
The output data type is boolean and indicates whether the output from the timer pickup
is delayed (ON) or if the drop out (OFF) is delayed.
Test/Function status/Logic/Bool16ToInt
Displays the output data of the Bool16ToInt function.
Test/Function status/Logic/IntToBool16
Displays the output data of the IntToBool16 function.
11.6.14 Monitoring
Test/Function status/Monitoring/DisturbanceReport
Displays data about disturbance reports. The disturbance report can be switched off,
a disturbance report that has been initiated is indicated by a boolean number, as are
completed reports and cleared reports. The parameter MEM USED indicates that more
than 80% of the memory space available for disturbance report data has been used
and the need to clear the memory is pressing. The Memory USED parameter generates
an integer value showing the actual amount of memory used by the disturbance record
repository. The maximum number of incoming analog channels is 40 and their Trig
status is indicated here. The Fault number parameter generates an integer indicating
the number of faults recorded since the last clearing of the memory.
Test/Function status/Monitoring/MeasValExpander
Displays available instances of the function block (XP). These show the boolean
values assigned to the integer values generated by analog inputs.
11.6.14.4 LEDs
Test/Function status/Monitoring/GPS
Displays the number of satellites supplying positioning and timing data to the GPS
module.
Test/Function status/Monitoring/BinarySigStatusReport
Displays sets of output measurements with several outputs per set of measurements.
Test/Function/Monitoring/Event counter/CNT
Display the output data of the CNT function.
11.6.15 Metering
Test/Function status/Metering/PulseCounter/PC
Displays up to four instances of PC with measurement data. Each instance displays
five data outputs that include pulse counter validity, reported value of complete
integration cycle, generation of new pulse counter value, pulse counter blocked and
user defined string is used for the pulse counter.
11.6.16 Communications
The communication output data available under Test includes remote communication
and station communication.
MultiCommand send
Test/Function status/Communication/Station communication/
MultiCommandSend/MT
The MultiCommand Send indication is used to display data from the Local Optical
network (LON).
MultiCommand receive
Test/Function status/Communication/Station communication/
MultiCommandReceive/CM
The MultiCommand Receive indications displayed here show available sets of output
data. Each set of output data has a number of signals. Other information displayed
here shows whether there has been a change in data and whether data is valid.
11.6.19 Authorization
Test/Function status/Authorization
Shows if any user is logged on and if any user is blocked by invalid password.
Test/LED test
The Test LEDs menu enables the operator to activate LEDs manually. LEDs that do
not light up are defective. Defective LEDs are also logged in Disturbance records
under Monitoring.
12.1 Overview
The control menu in the HMI includes the Single line diagram, Single command and
Selector switch functions.
The Single Line Diagram (SLD) is used to control and supervise the bay by allowing
the operator to close and open apparatuses using keys on the front panel of the IED.
This is primarily intended as a backup for higher level control systems. If for example
MicroSCADA were to malfunction, then bay level switches and circuit breakers can
be controlled directly from the HMI.
The Single command function is used to view LON interlocking data and is only
visible if LON is configured and used in the system.
The Selector Switch function is configured in the PCM 600 tool and the switch
position can be changed in the HMI. The selector switch has the same function as a
rotating switch with up to 32 positions. Each position is configured in the PCM 600
to match a certain application. Each position number corresponds to the equivalent
position of a rotating switch. It is only visible if it has been configured in the PCM
600.
to symbol using the keypad. An apparatus is opened using the green Ored Close key
and closed using the red I key.
The symbols used in the Single Line Diagram (SLD) are described in the table below
Symbol Description
Autotransformer
xx05000227.vsd
Busbar
xx05000228.vsd
Capacitor
xx05000231.vsd
Circuit breaker
xx05000232.vsd
Damping Coil
xx05000233.vsd
Current Transformer
xx05000234.vsd
Earth
xx05000235.vsd
Feeder system
xx05000236.vsd
Generator
xx05000237.vsd
Disconnector
xx05000238.vsd
Junction
xx05000240.vsd
Motor
xx05000241.vsd
Symbol Description
Reactor
xx05000242.vsd
Surge arrestor
xx05000243.vsd
Trafo 2 windings
xx05000244.vsd
Trafo 3 windings
xx05000245.vsd
Truck
xx05000248.vsd
VT 2 windings
xx05000247.vsd
Section 13 Reset
By activating this reset, the colored LEDs above the LCD, if they are latched, will be
reset.
Activating the Reset of indication LEDs will zero all fifteen LEDs to the right of the
LCD.
The circuit breaker counter is reset under the following menu in the HMI tree.
The circuit switch counter reset function is found under Reset counters in the HMI
tree.
The Pulse counter reset function is found in the Reset counters menu in the HMI tree.
Reset/Reset counters/ThreePhEnergMeas/ETP
Resetting accumulated energy values and the maximum demand values.
Section 14 Authorization
14.1 Overview
To safeguard the interests of our customers, both the IED 670 and the tools that are
accessing the IED 670 are protected, subject of authorization handling. The concept
of authorization, as it is implemented in the IED 670 and the associated tools is based
on the following facts:
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM 600. The user can only LogOn or LogOff on the LHMI of
the IED, there are no users, groups or functions that can be defined on the IED LHMI.
Authorization
Once a user is created and downloaded into the IED, that user can perform a LogOn,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will cause the display to show a message
box saying: “No user defined!”
If one user leaves the IED without logging off, then after the timeout (set in Settings
\General Settings\HMI\Screen\ Display Timeout ) elapses, the IED will return to a
Guest state, when only reading is possible. The display time out is set to 60 minutes
at delivery.
If there are one or more users created with the UMT and downloaded into the IED,
then, when a user intentionally attempts a LogOn or when the user attempts to perform
an operation that is password protected, the LogOn window will appear
The cursor is focused on the “User identity” field, so upon pressing the “E” key, one
can change the user name, by browsing the list of users, with the “up” and “down”
arrows. After choosing the right user name, the user must press the “E” key again.
When it comes to password, upon pressing the “E” key, the following character will
show up: “$”. The user must scroll for every letter in the pasword. After all the letters
are introduced (passwords are case sensitive!) choose OK and press “E” key again.
Section 15 Glossary
15.1 Glossary
AC Alternating current
A/D converter Analog to digital converter
ADBS Amplitude dead -band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CAP 531 Configuration and programming tool
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined mega pulses per second
CO cycle Close-open cycle
Co-directional Way of transmitting G.703 over a balanced line. Involves two
twisted pairs making it possible to transmit information in both
directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four
twisted pairs of with two are used for transmitting data in both
directions, and two pairs for transmitting clock signals
CPU Central processor unit
CR Carrier receive
CRC Cyclic redundancy check
CS Carrier send
CT Current transformer
CVT Capacitive voltage transformer
DAR Delayed auto-reclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFT Discrete Fourier transform
DIP-switch Small switch mounted on a printed circuit board
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE/ANSI Std.
1379-2000
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler