Bill of Material - 20kW
Bill of Material - 20kW
Bill of Material - 20kW
Bill of Material – 20 kW
Sr. No. Particulars Rating Quantity
1 Solar PV Module 66
Capacity 310 Wp
Type of cell Poly crystalline silicon
Lamination type Vacuum laminated Glass
Efficiency >15%
Degradation/year <1%
Lifecycle 25 years
Size
Make Waaree/Eqv.
Standard IEC 61215/IS 14286 – Design Qualification
IEC 61730 – Safety Qualification
IEC 61701 – Salt Mist Corrosion
IEC 62716 – Ammonia Corrosion (Optional)
IEC TS 62804-1 – Potential Induced
Degradation
IEC 62759-1- Transportation & Shipping
IEC 61853/IS16170 – Performance & Energy
2 Inverter 1
Capacity 20kW/ 20kVA
Type Grid tied String
Make Delta/Ujaas/Eqv.
Efficiency >97%
Waveform Sinewave
Protection IP65 (Outdoor)/IP54 ( Indoor)
Operating Temperature
Voltage
Output Frequency 1 phase, 50 Hz
Instrumentation Output voltage, current & kWh
Power Device IGBT/MOSFET
Power Factor 0.8
Size
Weight
Standard IEC 62109-1,2 – Safety Compliance
IEC/IS 61683 – Stand Alone System
BS EN 50530 / IEC 62819 – Grid Connected
IEC 62116 / UL 1741 / IEEE 1547 – Islanding
Prevention
IEC 60255-27 – Safety Requirement
IEC 60068-2 – Environmental Testing
IEC 610000-2,3,5 – EMI & EMC
3 Roof Mounting Structure (RMS)
Profile 2x1
Type Mild Steel-Hot Dipped Galvanized
Galvanizing thickness 85 micron
Designed wind speed 150 km/hr
Standard IS
Cold formed C channel – 682 mm 40 mm x 40 mm x 2 mm 66
Cold formed C channel – 1112 mm 40 mm x 40 mm x 2 mm 66
Cold formed C channel – 2084 mm 40 mm x 40 mm x 2 mm 66
Cleat angle 60 mm x 60 mm x 5 mm 264
Bolting inclusive of 2 plain washers, M8 x 25 mm
1 EPDM washer, 1 spring washer
726
Anchor Bolt 10 mm x 126 mm 264
End clamp 30 mm x 26 mm x 3 mm 132
Mid clamp 30 mm x 26 mm x 3 mm 66
Bolting inclusive of washers M6 x 25 mm 264
Standard IS - 2062/IS - 4759
4 Connectors 6
MC4 connectors sets – Male & 4mm (diameter) contact pin
Female
Current rating 30 Amp
Voltage rating 600/1000/1500 V
Degree of protection IP67
Make Ujaas/Eqv.
Application Module interconnection
Standard IEC
5 Array Junction Box 1
Type SPD, type-II
Input 4
Output 4
Application Module interconnection
Make
Standard IEC - 60529
6 DC Cable
A Connecting Cable - 4 sq. mm
Rating 1.1 kV (DC)
Type Cu
Grade UV resistant
Length
Application Module interconnection
Standard IEC 60227/ IS694
IEC 60502/ IS 1554
BS EN 50618
2
Length 3 meters
Application Inverter Earthing
Standard IEC 60227/ IS694
IEC 60502/ IS 1554
C Communication cable
Type CAT6
Length 30 meters
Application Communication
7 AC Cable
A 1.1 kV XLPE cable
Type Cu Armored, XLPE
Rating 1.1 kV x 4 Core x 4 sq. mm
Application Inverter to LT Panel
LT Panel to Recto feeder Panel
Length 40 meters
8 Transformer
9 LT Panel 1
A ACDB
Type Wall mounted
Rating 415 V, 50 Hz
Incomers/ Outgoing 25A 4P, 25kA MCCB
10 SCADA
11 Energy Meter 1
Standard IS – 16444 or As per Discom
12 Miscellaneous 1
Dr Fixit water Proofing agent 1 liter
Fischer Tube 16 pieces
Sticker for Inverter 1
Sticker for Danger 1
Rubber mats 1
Fire Extinguser (ABC DCP stored
1
pressure 4Kgs. Capacity)
Do's & Don't Board 1
3
First Aid Box 1
PVC Conduit 1 inch 30
FASTENER FOR INVERTER & LT
10
PANEL MOUNTING M8
NUMBERING FERRULE (6MM) 2
Lugs- Ring type Copper 25
8
sq.mm
Lugs- Ring type BI Metalic CU 25
8
sq.mm
Cable Tie Black UV Resistant
2
300mm or Equ
Chamber Pit cover of 1 fit X 1 Fit
4
with Petroleum jelly
600VA UPS for Data Logger 1
NOTES 1. All cables including DC, AC and earthing cables shall be made available to
customer in standard packing as mentioned in final BoM. Any additional
requirement due to change in equipment relocation shall be charged extra on
actuals.