SpaceLogic CRS-HIO-DIDO-8 Multi I - O Module Specification Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CRS-HIO-DIDO-8

SpaceLogic™ RP Controller Expansion Modules

Specification Sheet

Green Premium™ ecolabel


product – Sustainable
performance, by design
Multi I/O module
Introduction The Multi I/O module is part of the EcoStruxure Connected
Room Solutions for Hotels. It can be combined with other
As part of the EcoStruxure™ Connected Room Solutions for modules from this product range and is designed for hotel
Hotels solution, the Multi I/O module offers additional support guest room applications.
for the SpaceLogic™ RP-C Pro controller with a maximum
of 8 digital inputs and 8 indicator outputs. The inputs can be
connected to maintained switches or press buttons that are Features
used to control lighting (on/off or dimming signals), blinds and The Multi I/O module offers the following features:
scenes. The indicator outputs are used to drive such things as
switch LED indicators at a voltage level of 5 Vdc. • Cost-effective I/O module

The Multi I/O module is sized to be inserted in a wall box, and • Offers 8 digital inputs and 8 indicator outputs
installed behind a traditional multi-gang mechanical switch • Indicator output controls the on/off status of LED indicators,
or push button set, enabling the connection of up to 8 inputs which are installed in the switch (e.g. Control Switch on/off
complete with LED indicator outputs, providing significant cost status, DND, MUR, etc.)
savings on wiring and installation costs. The additional support
• Configured using the Hotel Application under EcoStruxure
provided by the Multi I/O module for bespoke design switch
Building Operation 5.0 (and later)
plates that use traditional switches and push buttons allows
hotels to focus on a personalized guest experience. • Power and communications for the Multi I/O module are
provided via the room bus connection

www.se.com/buildings
CRS-HIO-DIDO-8
• Prewired harnesses simplify wiring and reduce cabling Room Bus
required, whilst reductions in engineering time also assist in
The RP-C Pro controller room bus supports up to 9 connected
reduced installation costs
room solution expansion modules, 8 of which may be Multi I/O
• The ability to provide bespoke switch panels offers the guest modules. Refer to the Architectural Guidelines for Hotels for
a more personalized experience which helps drive loyalty further information and clarification on system architectures. It
is a supplementary document to the Architectural Guidelines –
Connected Room Solutions for Hotels EcoStruxure Building Management.
This solution easily transforms hotels. Its extensive architecture
As per the Architectural Guidelines, the maximum total length of
is designed for a wide range of modular components including
the room bus is 72 m (236 ft) without an RS-485 power adapter.
temperature, light and blind control interfaces, as well as
If the room bus total wiring length exceeds 72 m (to a maximum
bedside panels, sensors, thermostats, plus a wide range of
of 150 m or 492 ft), refer to SpaceLogic Hardware Reference
HMIs (such as mechanical switches and Modbus glass touch
Guide for additional information on hardware requirements.
panels). Get the latest wireless capabilities with the Commission
mobile application for commissioning and the open protocols to
interface with industry-standard IoT devices.

Assa Abloy
Door Lock DI

I/O Indicator
Sensors Output
Courtesy Panel Mechanical Switch
Room Bus, Max. 72 m (236 ft)

(DND/MUR/Bell) (Push Button)


Modbus RTU

Modbus Glass Touch Panels


Thermostat

Multi I/O Modules 0-10 V DALI 10Ch Relay

Room Bus, Max. 150 m (492 ft)

Termination Multi I/O Modules RS-485 0-10 V DALI 10Ch Relay RS-485
RS-485 Power Adapter Power Adapter
Power Adapter

Part Numbers
Product Part number
CRS-HIO-DIDO-8 SXWHIO8DIDO10001
Includes 2 x wiring harnesses, installation instructions

CRS-HIO-CABLE-8 SXWHIO8CABLE10001
Includes 2 x wiring harnesses

CRS-HIO-DIDO-8 Life is On | Schneider Electric 2


CRS-HIO-DIDO-8
Specifications
CRS-HIO-DIDO-8
Electrical
Nominal voltage 24 VDC
Powered by the RP-C through the room bus (RJ45)
Maximum power consumption 0.3 W
Port types
Room bus RS-485
Dual RJ45 ports for daisy-chain configurations
Environment
Environmental conditions Indoor use only
Ambient temperature, operating 0 to 50 °C (32 to 122 °F)
Humidity, operating 20 to 90 % RH non-condensing
Ambient temperature, storage -20 to 65 °C (-4 to 149 °F)
Humidity, storage 20 to 90 % RH non-condensing
Mechanical
Dimensions Module: 50 L x 50 W x 21.2 H mm (1.97 L x 1.97 W x 0.84 H in)
Wall box minimum: 60 L x 60 W x 35 H mm (2.36 L x 2.36 W x 1.38 H in)
Weight 20 g (0.04 lb)
LED indicator Dual status LED (green and red)
Material
Digital inputs 8 (voltage free)
Indicator outputs 8 transistors
Indicator output voltage 5V
Enclosure Plastic
Ingress protection rating IP 20
Plastic flame rating UL94 V-0
Color Gray
Surface finish Matte
Installation
Placement Inside a wall box connected to a mechanical switch (push button switch) via digital input
Installation equipment, included 2 x wiring harnesses, installation instructions

CRS-HIO-DIDO-8 Life is On | Schneider Electric 3


CRS-HIO-DIDO-8
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the 2014/35/EU Low Voltage Directive
following two conditions: (1) This device may not cause harmful interference. 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
(2) This device must accept any interference received, including interference that 2015/863/EU amending Annex II to Directive 2011/65/EU
may cause undesired operation. This equipment complies with the rules, of the Official Journal of the European
Union, for governing the Self Declaration of the CE Marking for the European
Union as specified in the above directive(s).

UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.
China RoHS SJ/T 11364-2014

www.se.com/buildings

© 2023 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
998-22314256-2-en September 2023

You might also like