DTSU666 and DTSU666-CT three phase Smart meter

ZTY0.464.1267
(Din-rail)
Operation manual Page 8, Total 18

5: Odd parity, 1 stop bit, O.1;


Communication baud rate:
0:1.200;
0:1200 bps;
1:2.400;
1:2400 bps;
2:4.800;
2:4800 bps;
3:9.600;
3:9600 bps;
1~247 Communication address
Option for wiring mode:
0:n.34;
0:n.34 represents three phase four wire;
1:n.33;
1:n.33 represents three phase three wire.
The setting is 1, representing the allowed instrument energy data clearance,
0:no;1:E
which will be zero reset after clearing.
0:P;1:Q; Pulse output:
2:S; 0:actsive energy pulse; 1: reactive energy pulse; 2:Others.
Display in turns(second)
0~30
0:Timely display; 1~30:Time interval of actual display.
4.2.2. Programming operation

Button description: “SET” button represents “confirmation”, or “cursor shift” (when input digits),

“ESC” button represents “exit”, “→” button represents “add”. The input code is (default 701).

Figure 3 Setting examples for current and potential transformer ratio


DTSU666 and DTSU666-CT three phase Smart meter
ZTY0.464.1267
(Din-rail)
Operation manual Page 9, Total 18

Figure 4 Setting examples for communication address and Baud Rate


When input digits, “SET” can be used as cursor “_”motion button; “→”is “add” button, “ESC

”is Exit the programming operation interface or switch to the character interface from digit modification

interface, add from the beginning after setting the digit to the maximum value.

4.3. Communication function

Characterized with a RS485 communication interface, the baud rate can be changed between

1200bps, 2400bps, 4800bps and 9600bps.

Factory default communication parameter is ModBus-RTU protocol, the baud rate is 9600bps,

with the calibration bit and stop bit to be n.1, and the instrument address to be 1. The following table

is the common ModBus protocol address table, can be asked for specified communication protocol

by calling. ModBus_RTU protocol read command is 03H, write command is 10H.

Table 10 ModBus protocol address table


Data
Parameter Parameter Read
Instructions of parameters Data type length
address code Write
Word
Keyboard parameters (specific parameters see the instructions of programming parameters, the actual value
with (*) parameter= communication parameter value × 0.1)
0000H REV. Software Version Signed 1 R
0001H UCode Programming code codE(1~9999) Signed 1 R/W
0002H ClrE Power reset CLr.E(1:energy clear) Signed 1 R/W
0003H Network selection (0:three phase four Signed 1 R/W