Datasheet Oil Shell Diala S4 ZX I
Datasheet Oil Shell Diala S4 ZX I
Datasheet Oil Shell Diala S4 ZX I
• Extra Performance
Shell Diala S4 ZX-I • Meets IEC 60296 - Higher Oxidation
Stability & Low Sulphur content
Shell Diala S4 ZX-I is the new electrical insulating oil from Shell designed to meet the challenges presented by the latest
power transformers. It offers an extended oil life with the peace of mind of zero sulphur content.
Shell Diala S4 ZX-I is manufactured from zero sulphur base oils produced using Shell’s GTL (gas-to-liquid) technology.
These base oils offer a high degree of compositional consistency and have an excellent response to anti-oxidant. In
addition they are globally available and free from PCBs, DBDS and passivators.
Shell Diala S4 ZX-I meets both the established and new industry copper corrosion tests.
Performance, Features & Benefits Shell Diala S4 ZX-I is specially dried and handled to achieve a
· Extended oil life low water content and retain a high breakdown voltage at point
of delivery. This enables it to be used in many applications
Shell Diala S4 ZX-I is a fully inhibited oil giving outstanding
without further treatment.
oxidation performance and an extended oil life. Shell Diala S4
ZX-I is also suitable for use in highly loaded applications. Main Applications
· Transformer protection
Shell Diala S4 ZX-I is manufactured from a zero sulphur* base
oil, making it intrinsically non-corrosive towards copper,
without the need for passivation or other additives. Specifications, Approvals & Recommendations
Shell Diala S4 ZX-I meets all relevant tests for copper
corrosion, namely the established DIN 51353 (Silver Strip
· IEC 60296 (2012): Table 2 Transformer Oil (I) (Inhibited Oil)
Section 7.1 ("Higher oxidation stability and low sulphur
Test), ASTM D1275, and also the latest more severe tests: IEC
content").
62535 and ASTM D1275B.
For a full listing of equipment approvals and recommendations,
*Sulphur content below 1ppm detection limit of ASTM D5185
please consult your local Shell Technical Help Desk.
· System efficiency
The good low temperature viscometric properties of the oil
ensure proper heat transfer inside the transformer, even from
very low starting temperatures.
Properties Method IEC 60296 Table 2 + section Shell Diala S4 ZX-I Typical
7.1
Appearance IEC 60296 Clear, free from sediment and Complies
suspended matter
Density @200C kg/m3 ISO 3675 Max. 895 805
Flashpoint P.M. 0
C ISO 2719 Min. 135 191
Pour Point 0
C ISO 3016 Max. -40 -42
Dielectric Dissipation Factor @900C DDF IEC 60247 Max 0.005 <0.001
2-Furfural and related compounds mg/kg IEC 61198 Not detectable Complies
content
These characteristics are typical of current production. Whilst future production will conform to Shell's specification, variations in
these characteristics may occur.
Health, Safety & Environment
Avoid contact with skin. Use impervious gloves with used oil. After skin contact, wash immediately with soap and water.
Guidance on Health and Safety is available on the appropriate Material Safety Data Sheet, which can be obtained from your Shell
representative.
Additional Information
Storage precautions
The critical electrical properties of Shell Diala are easily compromised by trace contamination with foreign material. Typically
encountered contaminants include moisture, particles, fibres and surfactants. Therefore, it is imperative that electrical insulating oils
be kept clean and dry.
It is strongly recommended that storage containers be dedicated for electrical service and include air-tight seals. It is further
recommended that electrical insulating oils are stored indoors in climate-controlled environments.
Advice
Advice on applications not covered here may be obtained from your shell representative.
- FINAL REPORT -
Dear Sir,
Enclosed you will find the FINAL REPORT of the acceptance tests as per most recent IEC 60296 (Ed. 5, 06/2020) and
ENGIE Laborelec Purchase Specification (Ed. 05/2020) for mineral transformer oil for your reference sample
RLI2000046 - Diala S4 ZX I, received in our labs in November 2020.
We stay of course at your disposition for any further comments and remain,
Yours sincerely,
Steve Eeckhoudt
Senior Expert Insulating fluids & lubricants LABORELEC
Key Expert ENGIE
www.laborelec.com Page 1 of 6
LABORELEC
The tested and reported oil analysis results on the next pages show that this reference sample does comply with the
criteria mentioned in IEC 60296 (Ed. 5, 06/2020) for fully inhibited mineral transformer oil (TYPE A, as per table 3).
The tested and reported oil analysis results on the next pages show that this reference sample does comply with the
criteria mentioned in ENGIE Laborelec Purchase Specification (Ed. 05/2020) for mineral transformer oil (High Grade type).
www.laborelec.com Page 2 of 6
LABORELEC
Viscosity at -30°C mm²/sec ASTM D7042 Max. 1800 Max. 1800 443
Viscosity at 40°C mm²/sec ISO 3104 Max. 12 Max. 12 10.0
Pour point °C ISO 3016 Max. -40 (1) -51
Breakdown voltage kV IEC 60156 Min. 30 Min. 30 63
Breakdown voltage after kV IEC 60156 / IEC 60296 Min. 70 Min. 70 >80
laboratory filtration (2)
Water content mg/kg IEC 60814 Max. 30/40 Max. 30 14
Density at 20°C kg/m³ ASTM D4052 Max. 895 Max. 895 805
DDF at 90°C IEC 60247 Max. 0.005 Max. 0.005 ND (<0.0003)
ND : Not Detectable (if not mentioned specifically in table above, detection limit of used analysis standard is applicable)
NGR : No general requirement in IEC 60296
AGREED : To be agreed upon between supplier and user
- : Not determined yet
/ : Not requested by customer
(1) : To be agreed between supplier and customer in specific very hot/cold climates. Pour point should be at least 10°C
under Lowest Cold Start Energizing Temperature of the transformer.
(2) : Filtration of oil before measuring breakdown voltage consists of filtration of oil at 60°C under vacuum pressure of max.
2.5 kPa, using a sintered glass filter with a maximum pore size of 2.5 µm.
www.laborelec.com Page 3 of 6
LABORELEC
Flash point (PMCC-method) °C ISO 2719 Min. 135 Min. 135 197
PCA content % IP 346 Max. 3 Max. 3 ND (<1)
PCB content mg/kg IEC 61619 ND (<2) ND (<2) ND (<2)
ND : Not Detectable (if not mentioned specifically in table above, detection limit of used analysis standard is applicable)
NGR : No general requirement in IEC 60296
AGREED : To be agreed upon between supplier and user
- : Not determined yet
/ : Not requested by customer
www.laborelec.com Page 4 of 6
LABORELEC
Annex 1
H2 in µl/l ND (<5)
O2 in µl/l >20000
N2 in µl/l >50000
CO in µl/l ND (<25)
CO2 in µl/l ND (<25)
CH4 in µl/l ND (<1)
C2H2 in µl/l ND (<1)
C2H4 in µl/l ND (<1)
C2H6 in µl/l ND (<1)
Minimum requirement Minimum requirement
DGA after stray gassing test (2) ANALYSIS IEC 60296 Ed.5 Laborelec Purchase
(according IEC 60567) RESULT (table 3, TYPE A oil) Specification for mineral
transformer oil (version
05/2020 – high grade oil)
H2 in µl/l <5 < 50 Max. 50
O2 in µl/l >20000 NGR NGR
N2 in µl/l >50000 NGR NGR
CO in µl/l <25 NGR NGR
CO2 in µl/l 53 NGR NGR
CH4 in µl/l <1 < 50 Max. 50
C2H2 in µl/l <1 NGR NGR
C2H4 in µl/l <1 NGR NGR
C2H6 in µl/l <1 < 50 Max. 50
ND : Not Detectable (if not mentioned specifically in table above, detection limit of used analysis standard is applicable)
NGR : No general requirement
- : Not determined yet
/ : Not requested by customer
(1): AIR-stripped conditions, 0h incubation, 100ml syringes, all tests performed in duplo
(2): AIR-stripped conditions, 48 h incubation at 105°C with presence of Cu-strip, 100ml syringes, all tests performed in duplo
(3): AIR-stripped conditions, 48 h incubation at 105°C without Cu-strip, 100ml syringes, all tests performed in duplo
www.laborelec.com Page 5 of 6
LABORELEC
Annex 2
H2 in µl/l ND (<5)
O2 in µl/l >20000
N2 in µl/l >50000
CO in µl/l ND (<25)
CO2 in µl/l ND (<25)
CH4 in µl/l ND (<1)
C2H2 in µl/l ND (<1)
C2H4 in µl/l ND (<1)
C2H6 in µl/l ND (<1)
Minimum requirement Minimum requirement
DGA after stray gassing test (2) ANALYSIS IEC 60296 Ed.5 Laborelec Purchase
(according IEC 60567) RESULT (table 3, TYPE A oil) Specification for mineral
transformer oil (version
05/2020 – high grade oil)
H2 in µl/l 16 NGR Max. 100
O2 in µl/l >20000 NGR NGR
N2 in µl/l >50000 NGR NGR
CO in µl/l 331 NGR NGR
CO2 in µl/l 739 NGR NGR
CH4 in µl/l 3 NGR Max. 20
C2H2 in µl/l <1 NGR NGR
C2H4 in µl/l 6 NGR NGR
C2H6 in µl/l 4 NGR Max. 20
ND : Not Detectable (if not mentioned specifically in table above, detection limit of used analysis standard is applicable)
NGR : No general requirement
- : Not determined yet
/ : Not requested by customer
(1): AIR-stripped conditions, 0h incubation, 100ml syringes, all tests performed in duplo
(2): AIR-stripped conditions, 164 h incubation at 120°C without presence of Cu-strip, 100ml syringes, all tests performed in duplo
www.laborelec.com Page 6 of 6
Summary of compatibility tests/considerations with Diala S4 ZX-I
Joerg Friedel
10.05.2013
Tests Dongnam Trans ES 1 4 – Diala S4 ZX I
2
MARCH 28, 2018
AUTHOR:
KIERON RUCK
BACKGROUND
AIM
To test the specified Nebars in the two oils and conclude which grades are
suitable with each oil.
CONCLUSION
The following grades are deemed suitable for use with Nynas Nytro 10XN:
Nebar Grey
Nebar Red
Nebar White
The following grades are deemed suitable for use with Diala S4 ZX-1:
Nebar Grey
Nebar Orange
Nebar White
N75
To test Nebar grades:- Grey, White, Purple, Orange, Red and N75.
All grades of Nebar were 3mm thick with the excep�on of N75 (4mm).
The compressibility and recovery control relate to material not immersed in any
oil, taken from the same material as the tested samples.
NEBAR ORANGE
NEBAR WHITE
N75
NEBAR GREY
NEBAR RED
NEBAR PURPLE
NEBAR ORANGE
NEBAR WHITE
N75
NEBAR GREY
NEBAR RED
NEBAR PURPLE
Historical informa�on and performance show that a small amount of posi�ve swell
in a material provides the best sealing system. The logic being that over �me as
compression set takes place this is countered by the natural swell of the sealing
product. Too much swell typically causes the sealing product to so�en and rupture,
likewise nega�ve swell may lead to hardening of the material and a reduc�on in
the sealing pressure. This may differ for certain applica�ons but this holds true for
most sealing applica�ons.
The compressibility and recovery results indicate that Nebar Orange and Purple
may be unsuitable for sealing applica�ons in the presence of Nynas Nytro 10XN,
despite comparable volume swell. The figures show a marked reduc�on in
comparison to White and Red.
It is important to note that the range of Nebar products have been developed over
�me to cover a range of applica�ons which goes beyond just the oil resistance. The
sealing pressures and hardness of the flanges must also be taken into considera�on
when choosing the most suitable grades.
Based on these results the following conclusions may be drawn; that when
compared with standard test results.
Nebars Grey, Red and White appear to be the most suitable for use with Nynas
Nytro 10XN oil.
Nebars Grey, Orange, White and N75 appear to be the most suitable for use with
Diala S4 ZX-1 oil.
March 2021
Your ref: .
Our ref: 2021.3.18.DialaS4mixletter
Dear reader,
Shell Diala S4 ZX-I and Diala S4 ZX-IG are typically miscible and compatible with other Shell Diala
types as Diala S5 BD, Diala D/DX, Diala B, Diala S2 ZU-I, Diala S2 ZX-A, Diala S3 ZX-I/IG as well as
with other conventional mineral oil-based transformer oils (as described in the IEC 60296).
In case of topping up and mixing with heavily aged oil, consider the IEC 60422 for further guidance
on miscibility.
Yours sincerely
Shell Downstream Services International (SDSI) B.V.
Ed van Schaik
Product Application Specialist (Power/FPM)
Gevestigd te Rotterdam
Handelregister Rotterdam Nr. 24112907