POWER PLANT DCS

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT COVER SHEET
DIG-A-1401-S118-EL-1402-R03 1 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

110 VDC 110 VDC


BATTERY PANEL BATTERY PANEL -XAC 1 230VAC
L1
-XAC 2
-XDCIN1 +
1 2 -XDCIN2 +
1 2 N1
TERMINAL 4 - TERMINAL 4 -

R1A N1A R1B N1B


1 3 1 3
-FDC1 -FDC2
TYPE B 2 4 TYPE B 2 4
2P/20A R2A N2A 2P/20A R2B N2B
-PS1 -PS2
POWER SUPPLY DC POWER SUPPLY DC
110VDC TO 24VDC 110VDC TO 24VDC
40A AC 40A AC 1 3 1 3

PS1 PS2 -F900 -F901


/30.6 /30.6 FUSE FUSE
DC DC 2P/6A 2 4 2P/6A 2 4
6/32 6/32
+24A -24A +24B -24B
NS
PE
S1
2 PE 1
-PS3
POWER SUPPLY DC -SO
RM40 Socket
1PH+N+PE
16A 250VAC

DC
+DC -DC
1 3 5 LH

-Q1
MCCB I> I> I>
+DC/A
3P/80A
2 4 6

11 11 1 1
+24 / 3.0
+24 -B901 -B902 -LS902 -LS901
12 12 2 2
-24 / 3.0
-24 H1 H3 H6 H7
1 3 1 3
-FDC4 -FDC5
TYPE C 2 4 TYPE C 2 4
2P/36A 2P/10A
-XL 1 1
1 1 1 1
1

-HT901 -FA902
M -FA901
M -LT901 -LT901
RD1 ND1 RD2 ND2 1~ 1~
HEATER 2 FAN FAN
2 2 2 2
-XL 2 2

-XPO 1 2 3 4
NH
TERMINAL 1.5

CENTRAL POST MAIN LV

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT VOLTAGE CONTROL
DIG-A-1401-S118-EL-1402-R03 2 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

+24VDC
2.3 / +24 +24 / 4.0
-24VDC +24
2.3 / -24 -24 / 4.0
-24
-XDI 1 -XDI 3 5 7 9
11 SIZE 1.5

ML/JC1

RELAY OPERATED

/ 11.3

/ 11.1
/19.2 14

CB OPEN
JC1

JC1
JM1 PANEL-F2

JM1 PANEL-F1
A1
-LC5/JC1 30
WOODWARD
LS521
R1 -XDI 2 -XDI 4 6 8 10
SIZE 1.5
.6
31 A10 A12 A14 1 3

A2 A4 -FWW1
2P/6A 2 4
A6 A8
A16
-XF 1 2 3 4 5 6 7 8
FUSE
TERMINAL PE
SIZE 0.75
1.5A

A3 A5 A7 A9 A11 A13 A15 A17 RD3 ND3


-LC5/JC1
30 31 32 33 34 35 36 37 38 39 40 41 42
WOODWARD 43 44 45 46 47 48 49 50 51 53 54 55
LS521 COM DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 - + PE
CIRCUIT SYSTEM A
VOLTAGE HEALTHY
CIRCUIT SYSTEM B

VOLTAGE HEALTHY
MONITORING LOCK

RELAY OPERATED

CB OPEN STATUS
R1 R2 R3 R4 R5 R5 R6
.1 /4.1 /4.1 /4.2 /4.3 /4.3 /4.4

SUPPLY
DISCRETE INPUT RELAY OUTPUTS

SYSTEM A SYSTEM B ANALOG INPUT SYSTEM A CAN1 RS485 EARTH


SYSTEM B
CURRENT CURRENT 0 TO 20 mA VOLTAGE VOLTAGE
L1 L2 L3 N L1 L2 L3 N
120 480 120 480 120 480 120 480 120 480 120 480 120 480 120 480
S2 S1 S2 S1 S2 S1 S2 S1 GND AI 01 VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC CAN-L CAN-H TXD- TXD+ PE
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 56 57 58 59 55

R1A S1A T1A N1A R3A S3A T3A N3A


X1A X2A X3A X4A X5A X6A 1 3 5 11 1 3 5 11
-F1 -F2
TYPE B 2 4 6 13 TYPE B 2 4 6 13

/11.1

/11.3
-XIW1 1 2 3 4 5 6 3P/2A 3P/2A
CT TERMINAL
SIZE 2.5

R2A R4A
S2A
S4A
N1A T4A S4A R4A
T2A T4A
N3A
N1A T2A S2A R2A

/ 7.4

/ 7.4

/ 7.4

/ 7.5
-XVW1 1 2 3 4 -XVW1 5 6 7 8
TERMINAL TERMINAL

/ 7.8

/ 7.8

/ 7.8

/ 7.8
SIZE 2.5 SIZE 2.5

SYSTEM A-JC2-L3

SYSTEM A-JC2-L2

SYSTEM A-JC2-L1
SYSTEM A-JC2-N
SYSTEM B-JC4-L3

SYSTEM B-JC4-L2

SYSTEM B-JC4-L1
-XC1 1 2 3 4 5 6 -XVA1 L1 L2 L3 N SYSTEM B-JC4-N -XVB1 L1 L2 L3 N
FROM FROM JM1 PANEL FROM JM2 PANEL
JC1 PANEL

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT WWT1-LS521
DIG-A-1401-S118-EL-1402-R03 3 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

+24VDC
3.9 / +24 +24 / 5.0
+24

-LC5/JC1
WOODWARD
LS521 32 34 36 38 42

R2 R3 R4 R5 R5 R6
/3.6 /3.7 /3.7 /3.8 /3.8 /3.9

33 35 37 40 39 41

A18 A19 A20 A21 A22

A1 A1 A1 A1 A1
-R2-1 -R3-1 -R4-1 -CBA1 -CBC1
Syn. A2 A2 A2 CBA A2 CBA A2
Permission OPEN CLOSE

-24VDC
3.9 / -24 -24 / 5.0
-24

14 14 14 14 14
11 /13.0 11 /13.4 11 /13.7 11 /13.0 11 /13.4
12 12 12 12 12
24 24 24 24 24
21 /13.2 21 /13.5 21 /13.9 21 /13.2 21 /13.5
22 22 22 22 22

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT T1 SELECTOR
DIG-A-1401-S118-EL-1402-R03 4 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

+24VDC
4.9 / +24 +24 / 6.0
-24VDC +24
4.9 / -24 -24 / 6.0
-24
-XDI 11 13 15 17 19
11 SIZE 1.5

ML/JC2

RELAY OPERATED

/ 11.4

/ 11.5
/19.3 14

CB OPEN
JC2

JC2
JM2 PANEL-F3

JM2 PANEL-F4
B1
-LS5/JC2 30
WOODWARD +24
LS521
R1 -XDI 12 14 16 18 20

.6
SIZE 1.5 -24
31 B10 B12 B14 B16 1 3

B2 B4 -FWW2
2P/6A 2 4
B6 B8
-XF 9 10 11 12 13 14 15 16
FUSE
TERMINAL PE
SIZE 0.75
1.5A

B3 B5 B7 B9 B11 B13 B15 B17 RD4 ND4


-LS5/JC2
30 31 32 33 34 35 36 37 38 39 40 41 42
WOODWARD 43 44 45 46 47 48 49 50 51 53 54 55
LS521 COM DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 - + PE
CIRCUIT SYSTEM A
VOLTAGE HEALTHY
CIRCUIT SYSTEM B

VOLTAGE HEALTHY
MONITORING LOCK

RELAY OPERATED

CB OPEN STATUS
R1 R2 R3 R4 R5 R5 R6
.1 /6.1 /6.1 /6.2 /6.3 /6.3 /6.4

SUPPLY
DISCRETE INPUT RELAY OUTPUTS

SYSTEM A SYSTEM B ANALOG INPUT SYSTEM A CAN1 RS485 EARTH


SYSTEM B
CURRENT CURRENT 0 TO 20 mA VOLTAGE VOLTAGE
L1 L2 L3 N L1 L2 L3 N
120 480 120 480 120 480 120 480 120 480 120 480 120 480 120 480
S2 S1 S2 S1 S2 S1 S2 S1 GND AI 01 VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC CAN-L CAN-H TXD- TXD+ PE
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 56 57 58 59 55

R5A S5A T5A R6A S6A T6A N6A


X1B X2B X3B X4B X5B X6B 1 3 5 11 1 3 5 11
-F3 -F4
TYPE B 2 4 6 13 TYPE B 2 4 6 13

/11.4

/11.5
-XIW2 1 2 3 4 5 6 3P/2A 3P/2A
CT TERMINAL
SIZE 2.5
S7A T7A
R4A S4A T4A N3A R7A

-XVW2 1 2 3 4
TERMINAL
SIZE 2.5

/ 9.5

/ 9.4

/ 9.4

/ 9.4
-XVB2 L1 L2 L3 N
SYSTEM B-JC1-L1 / 9.6

SYSTEM B-JC1-L2 / 9.7

SYSTEM B-JC1-L3 / 9.7

/ 9.7

SYSTEM A-JC3-L3

SYSTEM A-JC3-L2

SYSTEM A-JC3-L1
SYSTEM A-JC3-N
FROM JM3 PANEL
SYSTEM B-JC1-N

-XC2 1 2 3 4 5 6
FROM
JC2 PANEL

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT WWT2-LS521
DIG-A-1401-S118-EL-1402-R03 5 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

5.9 / +24 +24 / 7.0


+24

-LS5/JC2
WOODWARD
LS521 32 34 36 38 42

R2 R3 R4 R5 R5 R6
/5.6 /5.7 /5.7 /5.8 /5.8 /5.9

33 35 37 40 39 41

B18 B19 B20 B21 B22

A1 A1 A1 A1 A1
-R2-2 -R3-2 -R4-2 -CBA2 -CBC2
Syn. A2 A2 A2 CBA A2 CBA A2
Permission OPEN CLOSE

5.9 / -24 -24 / 7.0


-24

14 14 14 14 14
11 /13.7 11 /13.0 11 /13.4 11 /13.7 11 /14.0
12 12 12 12 12
24 24 24 24 24
21 /13.9 21 /13.2 21 /13.5 21 /13.9 21 /14.2
22 22 22 22 22

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT T2 SELECTOR
DIG-A-1401-S118-EL-1402-R03 6 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

+24VDC
6.9 / +24 +24 / 8.0
-24VDC +24
6.9 / -24 -24 / 8.0
-24
-XDI 21 -XDI 23 -XDI 25 -XDI 27 -XDI 29
11 SIZE 1.5

ML/JC3

RELAY OPERATED

/ 11.6

/ 11.7
/19.3 14

JC3 OPEN

CB OPEN
JC3
JM3 PANEL-F5

JM3 PANEL-F6
C1
-LC5/JC3 30
WOODWARD +24
LS521
R1 -XDI 22 -XDI 24 -XDI 26 -XDI 28 -XDI 30

.6
SIZE 1.5 -24
31
1 3

C2 C4 -FWW3
2P/6A 2 4
C6 C8 C10 C12 C14 C16
-XF2 1 2 3 4 5 6 7 8
FUSE
TERMINAL PE
SIZE 0.75
1.5A

C3 C5 C7 C9 C11 C13 C15 C17 RD5 ND5


-LC5/JC3
30 31 32 33 34 35 36 37 38 39 40 41 42
WOODWARD 43 44 45 46 47 48 49 50 51 53 54 55
LS521 COM DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 - + PE
CIRCUIT SYSTEM A
VOLTAGE HEALTHY
CIRCUIT SYSTEM B

VOLTAGE HEALTHY
MONITORING LOCK

RELAY OPERATED

CB OPEN STATUS
R1 R2 R3 R4 R5 R5 R6
.1

SUPPLY
DISCRETE INPUT RELAY OUTPUTS

SYSTEM A SYSTEM B ANALOG INPUT SYSTEM A CAN1 RS485 EARTH


SYSTEM B
CURRENT CURRENT 0 TO 20 mA VOLTAGE VOLTAGE
L1 L2 L3 N L1 L2 L3 N
120 480 120 480 120 480 120 480 120 480 120 480 120 480 120 480
S2 S1 S2 S1 S2 S1 S2 S1 GND AI 01 VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC CAN-L CAN-H TXD- TXD+ PE
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 56 57 58 59 55

R8A S8A T8A N6A R9A S9A T9A N9A


X1C X2C X3C X4C X5C X6C 1 3 5 11 1 3 5 11
-F5 -F6
TYPE B 2 4 6 13 TYPE B 2 4 6 13

/11.6

/11.7
-XIW3 1 2 3 4 5 6 3P/2A 3P/2A
CT TERMINAL
SIZE 2.5
R7A S7A T7A
R10A S10A T10A

-XVW3 1 2 3 4
TERMINAL
/ 3.8

/ 3.8

/ 3.8

/ 3.8

/ 3.5

/ 3.5

/ 3.5

/ 3.6
SIZE 2.5
SYSTEM A-JC2-L3

SYSTEM A-JC2-L2

SYSTEM A-JC2-L1

SYSTEM B-JC4-L3

SYSTEM B-JC4-L2

SYSTEM B-JC4-L1
SYSTEM A-JC2-N

SYSTEM B-JC4-N
-XC3 1 2 3 4 5 6 -XVB1 L1 L2 L3 N
FROM FROM JM4 PANEL
JC3 PANEL

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT WWT3-LS521
DIG-A-1401-S118-EL-1402-R03 7 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

7.9 / +24 +24 / 9.0


+24

-LS5/JC3
WOODWARD
LS521 32 34 36 38 42

R2 R3 R4 R5 R5 R6

33 35 37 40 39 41

C18 C19 C20 C21 C22

A1 A1 A1 A1 A1
-R2-3 -R3-3 -R4-3 -CBA3 -CBC3
Syn. A2 A2 A2 CBA A2 CBA A2
Permission OPEN CLOSE

7.9 / -24 -24 / 9.0


-24

14 14 14 14 14
11 /14.4 11 /14.7 11 /14.0 11 /14.4 11 /14.7
12 12 12 12 12
24 24 24 44 24
21 /14.5 21 /14.9 21 /14.2 41 /14.5 21 /14.9
22 22 22 42 22

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT T3 SELECTOR
DIG-A-1401-S118-EL-1402-R03 8 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

+24VDC
8.9 / +24 +24 / 10.0
-24VDC +24
8.9 / -24 -24 / 10.0
-24
-XDI 31 -XDI 33 -XDI 35 -XDI 37 -XDI 39
11 SIZE 1.5

ML/JC4

RELAY OPERATED

/ 11.8

/ 11.2
/19.4 14

CB OPEN
JC4

JC4
JM4 PANEL-F7

JM4 PANEL-F8
D1
-LC5/JC4 30
WOODWARD +24
LS521
R1 -XDI 32 -XDI 34 -XDI 36 -XDI 38 -XDI 40

.6
SIZE 1.5 -24
31
1 3

D2 D4 -FWW4
2P/6A 2 4
D6 D8 D10 D12 D14 D16
-XF2 9 10 11 12 13 14 15 16
FUSE
TERMINAL PE
SIZE 0.75
1.5A

D3 D5 D7 D9 D11 D13 D15 D17 RD6 ND6


-LC5/JC4
30 31 32 33 34 35 36 37 38 39 40 41 42
WOODWARD 43 44 45 46 47 48 49 50 51 53 54 55
LS521 COM DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 - + PE
CIRCUIT SYSTEM A
VOLTAGE HEALTHY
CIRCUIT SYSTEM B

VOLTAGE HEALTHY
MONITORING LOCK

RELAY OPERATED

CB OPEN STATUS
R1 R2 R3 R4 R5 R5 R6
.1

SUPPLY
DISCRETE INPUT RELAY OUTPUTS

SYSTEM A SYSTEM B ANALOG INPUT SYSTEM A CAN1 RS485 EARTH


SYSTEM B
CURRENT CURRENT 0 TO 20 mA VOLTAGE VOLTAGE
L1 L2 L3 N L1 L2 L3 N
120 480 120 480 120 480 120 480 120 480 120 480 120 480 120 480
S2 S1 S2 S1 S2 S1 S2 S1 GND AI 01 VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC VAC CAN-L CAN-H TXD- TXD+ PE
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 56 57 58 59 55

R12A S12A T12A N1A


R11A S11A T11A N9A
X1D X2D X3D X4D X5D X6D 1 3 5 11 1 3 5 11
-F7 -F8
TYPE B 2 4 6 13 TYPE B 2 4 6 13

/11.8

/11.2
-XIW4 1 2 3 4 5 6 3P/2A 3P/2A
CT TERMINAL
SIZE 2.5
R2A S2A T2A
R10A S10A T10A
SYSTEM A-JC3-L1 / 5.8

SYSTEM A-JC3-L2 / 5.8

SYSTEM A-JC3-L3 / 5.8

/ 5.8

SYSTEM B-JC1-L1 / 5.4

SYSTEM B-JC1-L2 / 5.4

SYSTEM B-JC1-L3 / 5.4

/ 5.5
SYSTEM A-JC3-N

SYSTEM B-JC1-N
-XC4 1 2 3 4 5 6
FROM
JC1 PANEL

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT WWT4-LS521
DIG-A-1401-S118-EL-1402-R03 9 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

9.9 / +24 +24 / 19.0


+24

-LS5/JC4
WOODWARD
LS521 32 34 36 38 42

R2 R3 R4 R5 R5 R6

33 35 37 40 39 41

D18 D19 D20 D21 D22

A1 A1 A1 A1 A1
-R2-4 -R3-4 -R4-4 -CBA4 -CBC4
Syn. A2 A2 A2 CBA A2 CBA A2
Permission OPEN CLOSE

9.9 / -24 -24 / 11.0


-24

14 14 14 14 14
11 /14.0 11 /14.4 11 /14.7 11 /15.0 11 /15.4
12 12 12 12 12
24 24 24 24 24
21 /14.2 21 /14.5 21 /14.9 21 /15.2 21 /15.5
22 22 22 22 22

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT T4 SELECTOR
DIG-A-1401-S118-EL-1402-R03 10 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-24VDC
10.9 / -24 -24 / 19.0
-24

-XT1 1 -XT1 3 -XT1 5 -XT1 7


TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 1.5 SIZE 1.5 SIZE 1.5 SIZE 1.5

VOLTAGE SAMPLE HEALTHY

VOLTAGE SAMPLE HEALTHY

VOLTAGE SAMPLE HEALTHY

VOLTAGE SAMPLE HEALTHY


JM1 PANEL

JM2 PANEL

JM3 PANEL

JM4 PANEL
-XT1 2 -XT1 4 -XT1 6 -XT1 8
TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 1.5 SIZE 1.5 SIZE 1.5 SIZE 1.5

A23 B23 C23 D23

11 11 11 11 11 11 11 11
-F1 -F8 -F2 -F3 -F4 -F5 -F6 -F7
13 13 13 13 13 13 13 13
/3.4 /9.6 /3.6 /5.4 /5.6 /7.4 /7.6 /9.4

A8 D8 A6 B6 B8 C6 C8 D6
/ 9.2

/ 3.2

/ 5.2

/ 5.2

/ 7.2

/ 7.2

/ 9.2
/ 3.2

JM4 PANEL-F8

JM1 PANEL-F2

JM2 PANEL-F3

JM2 PANEL-F4

JM3 PANEL-F5

JM3 PANEL-F6

JM4 PANEL-F7
JM1 PANEL-F1

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT VOLTAGE HEALTHY
DIG-A-1401-S118-EL-1402-R03 11 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 21 11 21 11 21
-R2-1 -R2-1 -R3-1 -R3-1 -R4-1 -R4-1
SYN. SYN. /4.1 /4.1 /4.2 /4.2
PERMISSION 14 12 PERMISSION 24 22 14 12 24 22 14 12 24 22
/4.1 /4.1

H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 H13 H14 H15 H16 H17 H18

-XWO1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

11 21 11 21 11 21
-CBA1 -CBA1 -CBC1 -CBC1 -R2-2 -R2-2
CBA CBA CBA CBA SYN. SYN.
OPEN 14 12 OPEN 24 22 CLOSE 14 12 CLOSE 24 22 PERMISSION 14 12 PERMISSION 24 22
/4.3 /4.3 /4.4 /4.4 /6.1 /6.1

H19 H20 H21 H22 H23 H24 H25 H26 H27 H28 H29 H30 H31 H32 H33 H34 H35 H36

-XWO1 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

11 21 11 21 11 21
-R3-2 -R3-2 -R4-2 -R4-2 -CBA2 -CBA2
/6.1 /6.1 /6.2 /6.2 CBA CBA
14 12 24 22 14 12 24 22 OPEN 14 12 OPEN 24 22
/6.3 /6.3

H37 H38 H39 H40 H41 H42 H43 H44 H45 H46 H47 H48 H49 H50 H51 H52 H53 H54

-XWO1 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 13 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 21 11 21 11 21
-CBC2 -CBC2 -R2-3 -R2-3 -R3-3 -R3-3
CBA CBA SYN. SYN. /8.1 /8.1
CLOSE 14 12 CLOSE 24 22 PERMISSION 14 12 PERMISSION 24 22 14 12 24 22
/6.4 /6.4 /8.1 /8.1

H55 H56 H57 H58 H59 H60 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12

-XWO1 55 56 57 58 59 60 -XWO2 1 2 3 4 5 6 7 8 9 10 11 12

11 21 11 41 11 21
-R4-3 -R4-3 -CBA3 -CBA3 -CBC3 -CBC3
/8.2 /8.2 CBA CBA CBA CBA
14 12 24 22 OPEN 14 12 OPEN 44 42 CLOSE 14 12 CLOSE 24 22
/8.3 /8.3 /8.4 /8.4

M13 M14 M15 M16 M17 M18 M19 M20 M21 M22 M23 M24 M25 M26 M27 M28 M29 M30

-XWO2 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

11 21 11 21 11 21
-R2-4 -R2-4 -R3-4 -R3-4 -R4-4 -R4-4
SYN. SYN. /10.1 /10.1 /10.2 /10.2
PERMISSION 14 12 PERMISSION 24 22 14 12 24 22 14 12 24 22
/10.1 /10.1

M31 M32 M33 M34 M35 M36 M37 M38 M39 M40 M41 M42 M43 M44 M45 M46 M47 M48

-XWO2 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 14 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 21 11 21
-CBA4 -CBA4 -CBC4 -CBC4
CBA CBA CBA CBA
OPEN 14 12 OPEN 24 22 CLOSE 14 12 CLOSE 24 22
/10.3 /10.3 /10.4 /10.4

M49 M50 M51 M52 M53 M54 M55 M56 M57 M58 M59 M60

-XWO2 49 50 51 52 53 54 55 56 57 58 59 60

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 15 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-XCAN 1 1 3 5 7 9 -XCAN 3
CAN INPUT 2 2 4 6 8 10 4
CAN OUTPUT
-XCAN -XCAN

-XCAN 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

-LS5/T1 -LS5/T2 -LS5/T3 -LS5/T4


WOODWARD CAN-L 56 CAN-H 57 WOODWARD CAN-L 56 CAN-H 57 WOODWARD CAN-L 56 CAN-H 57 WOODWARD CAN-L 56 CAN-H 57
LS522 LS522 LS522 LS522
24VDC

CAN1 CAN1 CAN1 CAN1 +24


RS485 RS485 RS485 RS485 -XP 7
FUSE
TERMINAL
SIZE 2.5
TXD-:58 TXD+:59 TXD-:58 TXD+:59 TXD-:58 TXD+:59 TXD-:58 TXD+:59
0.5A -24
+24A

H72 H73 H72 H73


+ -

P1 P2 P3 P4 P5

-XE 1 2 3 4 5 6 7 8 -XE 9 10 11 12 13 14 15 16
SIZE 1.5 SIZE 1.5

H70 H71 H72 H73 H74 H75 H80 H81 H82 H83 H84 H85

-S/CPU
-S1/MDB -S2/MDB
T1-T2 T3-T4
X1-P1 X1-P2

X20 M X20 TA X20 T_RAX20 T_RB X20 TB X20 RTS X20 M X20 TA X20 T_RAX20 T_RB X20 TB X20 RTS

CB 1241 RS485 SIEMENS CB 1241 RS485 SIEMENS

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT MODBUS RS485
DIG-A-1401-S118-EL-1402-R03 16 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S1/CPU -S1/DIO1

24VDC INPUTS
X11 X10
X11
X10
L+ M L+ M 1M .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 2M 0 1 3M 0 1
DI a DI b AQ AI
24VDC 24VDC 24VDC INPUTS ANALOG ANALOG
OUTPUTS INPUTS
24
VDC L+ M 1M .0 .1 .2 .3 DI a

X50
MC 2M .4 .5 .6 .7
RUN / STOP
ERROR
MAINT

.0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .0 .1 .2 .3 .4 .5 .6 .7

DIAG
DI a DI b DI a
SM 1223
CPU 1215C
DC/DC/DC DC/DC
DQ a DQ b DQ a
.0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .0 .1 .2 .3 .4 .5 .6 .7

LINK 215-1AG40-0XB0 X12 .0 .1 .2 .3


Rx / Tx X13 .4 .5 .6 .7 DQ a

24VDC OUTPUTS
6ES7223-1BH32-0XB0
24VDC OUTPUTS
X1 P1 X1 P2 X12 DQ a DQ b
4L+4M .0 .1 .2 .3 .4 .5 .6 .7 .0 .1
PROFINET (LAN)
MAC ADRESS

-S/MDB
CB 1241 RS485

6ES7241-1CH30-1XB0
RxD
TxD

X20:RS485
T/RA
T/RB

RTS
TA

TB
M

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S1/VIEW
DIG-A-1401-S118-EL-1402-R03 17 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S1/CPU
/19.0

S7-1200 SIEMENS
CPU 1215C DC/DC/DC

P1 R
PN
P2 R
PN
DC
/19.0
-X10:1 + - -X11:1
/19.8
L+ 2M
-X10:2 -X11:2
/19.0 QWX /19.9 SPARE
M AQ 0
-X10:3 -X11:3
/19.1 QWX+2 /19.9 SPARE
FE AQ 1
-X10:4
/19.1
L+
-X10:5 -X11:4
/19.1 /19.8
M 3M
-X10:6 - + -X11:5
/19.1 -+ IWX /19.9 SPARE
1M AI 0
-X10:7 -X11:6
TCS STATUS OF JC1 /19.2 IX.0 -+ IWX+2 /19.9 SPARE
DI a.0 AI 1
-X10:8
SERVICE POSITION OF CB OF JC1 /19.2 IX.1
DI a.1

SELECTOR ON REMOTE OF JC1 /19.3


-X10:9
IX.2
- + -X12:1
/19.1
DI a.2 4L+
-X10:10 -X12:2
SELECTOR ON SCYN CHECK OF JC1 /19.3 IX.3 /19.2
DI a.3 4M
-X10:11 -X12:3
SPARE /19.4 IX.4 QX.0 /19.2 PLC MONITORING LOCK JC1
DI a.4 DQ a.0
-X10:12 -X12:4
TCS STATUS OF JC2 /19.4 IX.5 QX.1 /19.3 PLC MONITORING LOCK JC2
DI a.5 DQ a.1
-X10:13 -X12:5
SERVICE POSITION OF CB OF JC2 /19.5 IX.6 QX.2 /19.3 PLC MONITORING LOCK JC3
DI a.6 DQ a.2
-X10:14 -X12:6
SELECTOR ON REMOTE OF JC2 /19.5 IX.7 QX.3 /19.4 PLC MONITORING LOCK JC4
DI a.7 DQ a.3
-X10:15 -X12:7
SELECTOR ON SCYN CHECK OF JC2 /19.5 IX+1.0 QX.4 /19.4 SPARE1
DI b.0 DQ a.4
-X10:16 -X12:8
SPARE /19.6 IX+1.1 QX.5 /19.5 SPARE2
DI b.1 DQ a.5
-X10:17 -X12:9
TCS STATUS OF JC3 /19.6 IX+1.2 QX.6 /19.6 SPARE3
DI b.2 DQ a.6
-X10:18 -X12:10
SERVICE POSITION OF CB OF JC3 /19.7 IX+1.3 QX.7 /19.6 SPARE4
DI b.3 DQ a.7
-X10:19 -X12:11
SELECTOR ON REMOTE OF JC3 /19.7 IX+1.4 QX+1.0 /19.7 SPARE5
DI b.4 DQ b.0
-X10:20 -X12:12
SELECTOR ON SCYN CHECK OF JC3 /19.8 IX+1.5 QX+1.1 /19.7 SPARE6
DI b.5 DQ b.1

6ES7215-1AG40-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S1/CPU
DIG-A-1401-S118-EL-1402-R03 18 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

10.9 / +24 +24 / 19.0


+24
11.9 / -24 -24 / 19.0
-24 1
-XR 1 -XR 6 -XR 8 -XR 13 -XR 15
-XF 17 JC1 PANEL JC2 PANEL JC3 PANEL
FUSE -F3V

SERVICE POSITION OF

SERVICE POSITION OF

SERVICE POSITION OF
SELECTOR ON SCYN

SELECTOR ON SCYN

SELECTOR ON SCYN
TCS STATUS OF JC1

TCS STATUS OF JC2

TCS STATUS OF JC3


TERMINAL FUSE
SIZE 2.5 2P/6A 2

REMOTE OF JC1

REMOTE OF JC2

REMOTE OF JC3
CHECK OF JC1

CHECK OF JC2

CHECK OF JC3
2A

SPARE

SPARE
6/32

SELECTOR ON

SELECTOR ON

SELECTOR ON
CB OF JC1

CB OF JC2

CB OF JC3
-XPO 5 6
SIZE 1.5

-XSO2 141 142


-XR 2 3 4 5 -XR 7 -XR 9 10 11 12 -XR 14 -XR 16 17 18 19
SIZE 1.5

-XSI 1 2 3 4
E1 E5 E7 E9 E11 E13 E15 E17 E19 E21 E23 E25 E27 E29 E31 SIZE 2.5
E2 E4

E34 E36
-XF 18 -XF 19 -XF 20 -XF 21 -XF 22 -XF 23 -XF 24 -XF 25 -XF 26 -XF 27 -XF 28 -XF 29 -XF 30 -XF 31 -XF 32 -XF 33 -XF 34
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
1A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
-S1/CPU CE
/18.3 E3 E6 E8 E10 E12 E14 E16 E18 E20 E22 E24 E26 E28 E30 E32 E33 E35 E37

-X10 L+ M FE L+ M 1M DI a.0 DI a.1 DI a.2 DI a.3 DI a.4 DI a.5 DI a.6 DI a.7 DI b.0 DI b.1 DI b.2 DI b.3 DI b.4 DI b.5 -X11 3M AI 0 AI 1

IWX+2
IX+1.0

IX+1.1

IX+1.2

IX+1.3

IX+1.4

IX+1.5
/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.3

/18.5

/18.5

/18.5
IWX
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
+

-
-

+
- -
+

6ES7215-1AG40-0XB0 CPU 1215C DC/DC/DC S7-1200 SIEMENS

-
+

QWX+2
QX+1.0

QX+1.1
/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5

/18.5
QWX
QX.0

QX.1

QX.2

QX.3

QX.4

QX.5

QX.6

QX.7
-X12 4L+ 4M DQ a.0 DQ a.1 DQ a.2 DQ a.3 DQ a.4 DQ a.5 DQ a.6 DQ a.7 DQ b.0 DQ b.1 -X11 2M AQ 0 AQ 1

E50 E52

-XF 35 -XF 36
FUSE FUSE
E38 E39 E40 E41 E42 E43 E44 E45 E46 E47 TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5
0.5A 0.5A
A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
E48 E49 E51
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2
-ML/JC1 -ML/JC2 -ML/JC3 -ML/JC4 -SP1 -SP2 -SP3 -SP4 -SP5 -SP6
PLC MONITORING PLC MONITORING PLC MONITORING PLC MONITORING SPARE1 SPARE2 SPARE3 SPARE4 SPARE5 SPARE6
LOCK JC1 LOCK JC2 LOCK JC3 LOCK JC4 -XSI 5 6 7 8
SIZE 2.5
19.9 / -24 -24 / 21.0
-24
19.9 / +24 +24 / 21.0
+24 11 14 /3.1 11 14 /5.1 11 14 /7.1 11 14 /9.1 14
11 /31.1
14
11 /31.3
14
11 /31.4
14
11 /31.6
14
11 /31.8
14
11 /31.1
12 12 12 12 12 12

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S1/CPU
DIG-A-1401-S118-EL-1402-R03 19 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S1/DIO1
/21.0

S7-1200 SIEMENS
SM1223 DI 8x24VDC / DO 8x24VDC

/21.0
-X10:1 + - -X12:1
L+ n.c.
-X10:2 -X12:2
/21.0
M n.c.
-X10:3 -X12:3
/21.1 - +
1M n.c.
-X10:4 -X12:4
SPARE /21.1 IX.0 QX.0 /21.1 SPARE
DI a.0 DQ a.0
-X10:5 -X12:5
TCS STATUS OF JC4 /21.2 IX.1 QX.1 /21.2 SPARE
DI a.1 DQ a.1
-X10:6 -X12:6
SERVICE POSITION OF CB OF JC4 /21.2 IX.2 QX.2 /21.2 SPARE
DI a.2 DQ a.2
-X10:7 -X12:7
SELECTOR ON REMOTE OF JC4 /21.3 IX.3 QX.3 /21.3 SPARE
DI a.3 DQ a.3

-X11:1 -X13:1
/21.6
FE n.c.
-X11:2 -X13:2
n.c. n.c.
-X11:3 -X13:3
/21.5 - +
2M n.c.
-X11:4 -X13:4
SELECTOR ON SCYN CHECK OF JC4 /21.3 IX.4 QX.4 /21.3 SPARE
DI a.4 DQ a.4
-X11:5 -X13:5
Emergency Permission from Control Room /21.4 IX.5 QX.5 /21.4 SPARE
DI a.5 DQ a.5
-X11:6 -X13:6
SPARE /21.4 IX.6 QX.6 /21.5 SPARE
DI a.6 DQ a.6
-X11:7 -X13:7
SPARE /21.5 IX.7 QX.7 /21.5 SPARE
DI a.7 DQ a.7

6ES7223-1BH32-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S1/DIO1
DIG-A-1401-S118-EL-1402-R03 20 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

19.9 / +24 +24 / 24.0


+24
19.9 / -24 -24 / 24.0
-24
-XR 20 -XR 22 -XR 27 -XR 29 -XR 31
-XF 37 JC4 PANEL
FUSE

from Control Room


SERVICE POSITION OF

SELECTOR ON SCYN
TCS STATUS OF JC4
TERMINAL
SIZE 2.5

Emergency
Permission
REMOTE OF JC4

CHECK OF JC4
2A

SPARE

SPARE

SPARE
SELECTOR ON
CB OF JC4
-XR 21 -XR 23 24 25 26 -XR 28 -XR 30 -XR 32

E54 E56 E58 E60 E62 E64 E66 E68


E53

-XF 38 -XF 39 -XF 40 -XF 41 -XF 42 -XF 43 -XF 44 -XF 45


FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
-S1/DIO1 CE
/20.3 E55 E57 E59 E61 E63 E65 E67 E69

-X10 L+ M 1M DI a.0 DI a.1 DI a.2 DI a.3 DI a.4 DI a.5 DI a.6 DI a.7 2M -X11 FE
/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3

/20.3
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
+ - -
- + +

6ES7223-1BH32-0XB0 SM1223 DI 8x24VDC / DO 8x24VDC S7-1200 SIEMENS


/20.5

/20.5

/20.5

/20.5

/20.5

/20.5

/20.5

/20.5
QX.0

QX.1

QX.2

QX.3

QX.4

QX.5

QX.6

QX.7
-X12 DQ a.0 DQ a.1 DQ a.2 DQ a.3 -X13 DQ a.4 DQ a.5 DQ a.6 DQ a.7

E70 E71 E72 E73 E74 E75 E76 E77

A1 A1 A1 A1 A1 A1 A1 A1

A2 A2 A2 A2 A2 A2 A2 A2
-SP7 -SP8 -SP9 -SP10 -SP11 -SP12 -SP13 -SP14
SPARE7 SPARE8 SPARE9 SPARE10 SPARE11 SPARE12 SPARE13 SPARE14

21.9 / -24 -24 / 21.0


-24
21.9 / +24 +24 / 21.0
14
11 /31.3
14
11 /31.4
14
11 /31.6
14
11 /31.8
14
11 /31.1
14
11 /31.3
14
11 /31.4
14
11 /31.6 +24
12 12 12 12 12 12 12 12

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S1/DIO1
DIG-A-1401-S118-EL-1402-R03 21 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S/CPU -S/DIO1 -S/DI1 -S/DI2

24VDC INPUTS

24VDC INPUTS

24VDC INPUTS
X10

X11
X10
L+ M L+ M 1M .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 2M 0 1 3M 0 1
DI a DI b AQ AI
24VDC 24VDC 24VDC INPUTS ANALOG ANALOG
OUTPUTS INPUTS X11
24
VDC L+ M 1M .0 .1 .2 .3 .4 .5 .6 .7 DI a X10 1M .0 .1 .2 .3 DI a X10 1M .0 .1 .2 .3 DI a

X50
MC 2M .0 .1 .2 .3 .4 .5 .6 .7 DI b X11 2M .4 .5 .6 .7 X11 2M .4 .5 .6 .7
RUN / STOP
ERROR
MAINT

.0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7

DIAG

DIAG

DIAG
DI a DI b DI a DI b DI a DI a
SM 1221 SM 1221
CPU 1215C SM 1223
DC/DC/DC DC/DC DC DC
DQ a DQ b DQ a DQ b DI b DI b
.0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7 .0 .1 .2 .3 .4 .5 .6 .7

6ES7223-1BL32-0XB0
LINK 215-1AG40-0XB0 .0 .1 .2 .3 .4 .5 .6 .7 DQ a X12 3M .0 .1 .2 .3 X12 3M .0 .1 .2 .3
Rx / Tx .0 .1 .2 .3 .4 .5 .6 .7 DQ b X13 4M .4 .5 .6 .7 DI b X13 4M .4 .5 .6 .7 DI b

24VDC OUTPUTS

6ES7221-1BH32-0XB0

6ES7221-1BH32-0XB0
24VDC INPUTS

24VDC INPUTS
X12
24VDC OUTPUTS
X1 P1 X1 P2 X12 DQ a DQ b
4L+4M .0 .1 .2 .3 .4 .5 .6 .7 .0 .1
PROFINET (LAN)
MAC ADRESS X13

-S/MDB
CB 1241 RS485

6ES7241-1CH30-1XB0
RxD
TxD

X20:RS485
T/RA
T/RB

RTS
TA

TB
M

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT VIEW/S2
DIG-A-1401-S118-EL-1402-R03 22 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S2/CPU
/24.0

S7-1200 SIEMENS
CPU 1215C DC/DC/DC

P1 R
PN
P2 R
PN
DC
/24.0
-X10:1 + - -X11:1
/24.8
L+ 2M
-X10:2 -X11:2
/24.0 QWX /24.9 SPARE
M AQ 0
-X10:3 -X11:3
/24.1 QWX+2 /24.9 SPARE
FE AQ 1
-X10:4
/24.1
L+
-X10:5 -X11:4
/24.1 /24.8
M 3M
-X10:6 - + -X11:5
/24.1 -+ IWX /24.9 SPARE
1M AI 0
-X10:7 -X11:6
TCS STATUS OF JU1 /24.2 IX.0 -+ IWX+2 /24.9 SPARE
DI a.0 AI 1
-X10:8
OPEN STATUS OF JU1 /24.2 IX.1
DI a.1

EARTH CLOSE STATUS OF JU1 /24.3


-X10:9
IX.2
- + -X12:1
/24.1
DI a.2 4L+
-X10:10 -X12:2
SERVICE POSITION OF CB OF JU1 /24.3 IX.3 /24.2
DI a.3 4M
-X10:11 -X12:3
RELAY OPERATED OF JU1 /24.4 IX.4 QX.0 /24.2 CLOSE CMD OF JU1
DI a.4 DQ a.0
-X10:12 -X12:4
SELECTOR ON REMOTEOF JU1 /24.4 IX.5 QX.1 /24.3 OPEN CMD OF JU1
DI a.5 DQ a.1
-X10:13 -X12:5
VOLTAGE HEALTHY SAMPEL OF JU1 /24.5 IX.6 QX.2 /24.3 CLOSE CMD OF JU2
DI a.6 DQ a.2
-X10:14 -X12:6
TCS STATUS OF JU2 /24.5 IX.7 QX.3 /24.4 OPEN CMD OF JU2
DI a.7 DQ a.3
-X10:15 -X12:7
OPEN STATUS OF JU2 /24.5 IX+1.0 QX.4 /24.4 CLOSE CMD OF JU3
DI b.0 DQ a.4
-X10:16 -X12:8
EARTH CLOSE STATUS OF JU2 /24.6 IX+1.1 QX.5 /24.5 OPEN CMD OF JU3
DI b.1 DQ a.5
-X10:17 -X12:9
SERVICE POSITION OF CB OF JU2 /24.6 IX+1.2 QX.6 /24.6 CLOSE CMD OF JU4
DI b.2 DQ a.6
-X10:18 -X12:10
RELAY OPERATED OF JU2 /24.7 IX+1.3 QX.7 /24.6 OPEN CMD OF JU4
DI b.3 DQ a.7
-X10:19 -X12:11
SELECTOR ON REMOTEOF JU2 /24.7 IX+1.4 QX+1.0 /24.7 CLOSE CMD OF JT1
DI b.4 DQ b.0
-X10:20 -X12:12
VOLTAGE HEALTHY SAMPEL OF JU2 /24.8 IX+1.5 QX+1.1 /24.7 OPEN CMD OF JT1
DI b.5 DQ b.1

6ES7215-1AG40-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/CPU
DIG-A-1401-S118-EL-1402-R03 23 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

21.9 / +24 +24 / 26.0


+24
21.9 / -24 -24 / 26.0
-24 1 3
-XR 33 -XR 41
-XF 46 JU1 PANEL JU2 PANEL
FUSE -F31V
FUSE

OPEN STATUS OF JU1

OPEN STATUS OF JU2


SERVICE POSITION

SERVICE POSITION
VOLTAGE HEALTHY

VOLTAGE HEALTHY
TERMINAL

TCS STATUS OF JU1

TCS STATUS OF JU2


RELAY OPERATED

RELAY OPERATED
SIZE 2.5 2P/6A 2 4

SAMPEL OF JU1

SAMPEL OF JU2
STATUS OF JU1

STATUS OF JU2
REMOTEOF JU1

REMOTEOF JU2
2A

OF CB OF JU1

OF CB OF JU2
6/32

SELECTOR ON

SELECTOR ON
EARTH CLOSE

EARTH CLOSE
OF JU1

OF JU2
-XPO 7 8
SIZE 1.5

-XSO 1 2
-XR 34 35 36 37 38 39 40 -XR 42 43 44 45 46 47 48
SIZE 1.5

-XSI 9 10 11 12
F1 F5 F7 F9 F11 F13 F15 F17 F19 F21 F23 F25 F27 F29 F31
F2 F4 SIZE 2.5

F34 F36
-XF 47 -XF 48 -XF 49 -XF 50 -XF 51 -XF 52 -XF 53 -XF 54 -XF 55 -XF 56 -XF 57 -XF 58 -XF 59 -XF 60 -XF 61 -XF 62 -XF 64
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
1A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
-S2/CPU CE
/23.3 F3 F6 F8 F10 F12 F14 F16 F18 F20 F22 F24 F26 F28 F30 F32 F33 F35 F37

-X10 L+ M FE L+ M 1M DI a.0 DI a.1 DI a.2 DI a.3 DI a.4 DI a.5 DI a.6 DI a.7 DI b.0 DI b.1 DI b.2 DI b.3 DI b.4 DI b.5 -X11 3M AI 0 AI 1

IWX+2
IX+1.0

IX+1.1

IX+1.2

IX+1.3

IX+1.4

IX+1.5
/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.3

/23.5

/23.5

/23.5
IWX
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
+

-
-

+
- -
+

6ES7215-1AG40-0XB0 CPU 1215C DC/DC/DC S7-1200 SIEMENS

-
+

QWX+2
QX+1.0

QX+1.1
/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5

/23.5
QWX
QX.0

QX.1

QX.2

QX.3

QX.4

QX.5

QX.6

QX.7
-X12 4L+ 4M DQ a.0 DQ a.1 DQ a.2 DQ a.3 DQ a.4 DQ a.5 DQ a.6 DQ a.7 DQ b.0 DQ b.1 -X11 2M AQ 0 AQ 1

F49 F51

-XF 63 -XF 65
FUSE FUSE
F38 F39 F40 F41 F42 F43 F44 F45 F46 F47 TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5
0.5A 0.5A
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2
F48 F50 F52
A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
-CC/JU1 -OC/JU1 -CC/JU2 -OC/JU2 -CC/JU3 -OC/JU3 -CC/JU4 -OC/JU4 -CC/JT1 -OC/JT1
CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD
OF JU1 OF JU1 OF JU2 OF JU2 OF JU3 OF JU3 OF JU4 OF JU4 OF JT1 OF JT1 -XSI 13 14 15 16
SIZE 2.5
24.9 / -24 -24 / 24.0
-24
24.9 / +24 +24 / 24.0
+24 14
11 /31.8
14
11 /32.1
14
11 /32.3
14
11 /32.4
14
11 /32.6
14
11 /32.8
14
11 /32.1
14
11 /32.3
14
11 /32.4
14
11 /32.6
12 12 12 12 12 12 12 12 12 12

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/CPU
DIG-A-1401-S118-EL-1402-R03 24 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S2/DIO1
/26.0

S7-1200 SIEMENS
SM1223 DI 16x24VDC / DO 16x24VDC

/26.0
-X10:1 + - -X12:1
L+ n.c.
-X10:2 -X12:2
/26.0
M n.c.
-X10:3 -X12:3
/26.1 - +
1M n.c.
-X10:4 -X12:4
TCS STATUS OF JU3 /26.1 IX.0 QX.0 /26.0 CLOSE CMD OF JT2
DI a.0 DQ a.0
-X10:5 -X12:5
OPEN STATUS OF JU3 /26.2 IX.1 QX.1 /26.1 OPEN CMD OF JT2
DI a.1 DQ a.1
-X10:6 -X12:6
EARTH CLOSE STATUS OF JU3 /26.2 IX.2 QX.2 /26.1 CLOSE CMD OF JAUX
DI a.2 DQ a.2
-X10:7 -X12:7
SERVICE POSITION OF CB OF JU3 /26.3 IX.3 QX.3 /26.2 OPEN CMD OF JAUX
DI a.3 DQ a.3
-X10:8 -X12:8
RELAY OPERATED OF JU3 /26.3 IX.4 QX.4 /26.3 PARALLEL MODE TO PLT1 N1
DI a.4 DQ a.4
-X10:9 -X12:9
SELECTOR ON REMOTEOF JU3 /26.4 IX.5 QX.5 /26.3 PARALLEL MODE TO PLT1 N2
DI a.5 DQ a.5
-X10:10 -X12:10
VOLTAGE HEALTHY SAMPEL OF JU3 /26.4 IX.6 QX.6 /26.4 PARALLEL MODE TO PLT2 N2
DI a.6 DQ a.6
-X10:11 -X12:11
TCS STATUS OF JU4 /26.5 IX.7 QX.7 /26.4 PARALLEL MODE TO PLT2 N2
DI a.7 DQ a.7

-X11:1 -X13:1
/26.5
FE n.c.
-X11:2 -X13:2
n.c. n.c.
-X11:3 -X13:3
/26.5 - +
2M n.c.
-X11:4 -X13:4
OPEN STATUS OF JU4 /26.6 IX+1.0 QX+1.0 /26.5 PARALLEL MODE TO PLT3 N1
DI b.0 DQ b.0
-X11:5 -X13:5
EARTH CLOSE STATUS OF JU4 /26.6 IX+1.1 QX+1.1 /26.5 PARALLEL MODE TO PLT3 N2
DI b.1 DQ b.1
-X11:6 -X13:6
SERVICE POSITION OF CB OF JU4 /26.7 IX+1.2 QX+1.2 /26.6 PARALLEL MODE TO PLT4
DI b.2 DQ b.2
-X11:7 -X13:7
RELAY OPERATED OF JU4 /26.7 IX+1.3 QX+1.3 /26.7 SPARE30
DI b.3 DQ b.3
-X11:8 -X13:8
SELECTOR ON REMOTEOF JU4 /26.8 IX+1.4 QX+1.4 /26.7 SPARE31
DI b.4 DQ b.4
-X11:9 -X13:9
VOLTAGE HEALTHY SAMPEL OF JU4 /26.8 IX+1.5 QX+1.5 /26.8 SPARE32
DI b.5 DQ b.5
-X11:10 -X13:10
TCS STATUS OF JT1 /26.8 IX+1.6 QX+1.6 /26.8 SPARE33
DI b.6 DQ b.6
-X11:11 -X13:11
OPEN STATUS OF JT1 /26.9 IX+1.7 QX+1.7 /26.9 SPARE34
DI b.7 DQ b.7

6ES7223-1BL32-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DIO1
DIG-A-1401-S118-EL-1402-R03 25 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

24.9 / +24 +24 / 28.0


+24
24.9 / -24 -24 / 28.0
-24
-XR 49 -XR 57 -XR 59 -XR 66
-XF 66 JU3 PANEL JU4 PANEL
FUSE

OPEN STATUS OF JU3

OPEN STATUS OF JU4

OPEN STATUS OF JT1


SERVICE POSITION

SERVICE POSITION
VOLTAGE HEALTHY
TERMINAL

TCS STATUS OF JU3

TCS STATUS OF JU4

TCS STATUS OF JT1


VOLTAGE HEALTHY
RELAY OPERATED

RELAY OPERATED
SIZE 2.5

SAMPEL OF JU3
STATUS OF JU3

STATUS OF JU4

SAMPEL OF JU4
REMOTEOF JU3

REMOTEOF JU4
2A

OF CB OF JU3

OF CB OF JU4
SELECTOR ON

SELECTOR ON
EARTH CLOSE

EARTH CLOSE
R1

OF JU3

OF JU4
-XR 50 51 52 53 54 55 56 -XR 58 -XR 60 61 62 63 64 65 -XR 67 68

G1 G2 G4 G6 G8 G10 G12 G14 G16 G18 G20 G22 G24 G26 G28 G30 G32

-XF 67 -XF 68 -XF 69 -XF 70 -XF 71 -XF 72 -XF 73 -XF 74 -XF 75 -XF 76 -XF 77 -XF 78 -XF 79 -XF 80 -XF 81 -XF 82
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
S2/DIO1 CE
/25.3 G3 G5 G7 G9 G11 G13 G15 G17 G19 G21 G23 G25 G27 G29 G31 G33

-X10 L+ M 1M DI a.0 DI a.1 DI a.2 DI a.3 DI a.4 DI a.5 DI a.6 DI a.7-X11 FE 2M DI b.0 DI b.1 DI b.2 DI b.3 DI b.4 DI b.5 DI b.6 DI b.7

IX+1.0

IX+1.1

IX+1.2

IX+1.3

IX+1.4

IX+1.5

IX+1.6

IX+1.7
/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3

/25.3
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
+ - -
- + +

6ES7223-1BL32-0XB0 SM1223 DI 16x24VDC / DO 16x24VDC S7-1200 SIEMENS

QX+1.0

QX+1.1

QX+1.2

QX+1.3

QX+1.4

QX+1.5

QX+1.6

QX+1.7
/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5

/25.5
QX.0

QX.1

QX.2

QX.3

QX.4

QX.5

QX.6

QX.7
-X12 DQ a.0 DQ a.1 DQ a.2 DQ a.3 DQ a.4 DQ a.5 DQ a.6 DQ a.7 -X13 DQ b.0 DQ b.1 DQ b.2 DQ b.3 DQ b.4 DQ b.5 DQ b.6 DQ b.7

G34 G35 G36 G37 G38 G39 G40 G41 G42 G43 G44 G45 G46 G47 G48 G49

A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1

A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2
-CC/JT2 -OC/JT2 -CC/JAUX -OC/JAUX -SP23 -SP24 -SP25 -SP26 -SP27 -SP28 -SP29 -SP30 -SP31 -SP32 -SP33 -SP34
CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE SPARE30 SPARE31 SPARE32 SPARE33 SPARE34
OF JT2 OF JT2 OF JAUX OF JAUX TO PLT1 N1 TO PLT1 N2 TO PLT2 N2 TO PLT2 N2 TO PLT3 N1 TO PLT3 N2 TO PLT4

26.9 / -24 -24 / 26.0


+24 -24
26.9 / +24 +24 / 26.0
14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14
11 /32.8 11 /32.1 11 /32.3 11 /32.4 11 /32.6 11 /32.8 11 /33.1 11 /33.3 11 /33.4 11 /33.6 11 /33.8 11 /33.1 11 /33.3 11 /33.4 11 /33.6 11 /33.8
12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
24 24 24 24 24 24 24
21 /34.0 21 /34.5 21 /34.0 21 /34.5 21 /34.0 21 /34.5 21 /35.0
22 22 22 22 22 22 22
34 34 34 34 34 34 34
31 /34.2 31 /34.7 31 /34.2 31 /34.7 31 /34.2 31 /34.7 31 /35.2
32 32 32 32 32 32 32
44 44 44 44 44 44 44
42
41 /34.4
42
41 /34.9
42
41 /34.4
42
41 /34.9
42
41 /34.4
42
41 /34.9
42
41 /35.4
POWER PLANT DCS
CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DIO1
DIG-A-1401-S118-EL-1402-R03 26 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S2/DI1
/28.0

S7-1200 SIEMENS
SM1221 DI 16 x 24 VDC

-X10:1 -X12:1
n.c. n.c.
-X10:2 -X12:2
n.c. n.c.
-X10:3 -X12:3
/28.0 - + + - /28.5
1M 3M
-X10:4 -X12:4
EARTH CLOSE STATUS OF JT1 /28.1 IX.0 IX+1.0 /28.5 RELAY OPERATED OF JT2
DI a.0 DI b.0
-X10:5 -X12:5
SERVICE POSITION OF CB OF JT1 /28.1 IX.1 IX+1.1 /28.6 SELECTOR ON REMOTE OF JT2
DI a.1 DI b.1
-X10:6 -X12:6
RELAY OPERATED OF JT1 /28.2 IX.2 IX+1.2 /28.6 RELAY OPERATED OF JM1
DI a.2 DI b.2
-X10:7 -X12:7
SELECTOR ON REMOTE OF JT1 /28.2 IX.3 IX+1.3 /28.7 RELAY OPERATE OF JM2
DI a.3 DI b.3

-X11:1 -X13:1
/28.2
FE n.c.
-X11:2 -X13:2
n.c. n.c.
-X11:3 -X13:3
/28.2 - + + - /28.7
2M 4M
-X11:4 -X13:4
TCS STATUS OF T2 /28.3 IX.4 IX+1.4 /28.8 RELAY OPERATED OF JM4
DI a.4 DI b.4
-X11:5 -X13:5
OPEN STATUS OF JT2 /28.3 IX.5 IX+1.5 /28.8 RELAY OPERATED OF JM5
DI a.5 DI b.5
-X11:6 -X13:6
EARTH CLOSE STATUS OF JT2 /28.4 IX.6 IX+1.6 /28.8 TCS STATUS OF JAUX
DI a.6 DI b.6
-X11:7 -X13:7
SERVICE POSITION OF CB OF JT2 /28.4 IX.7 IX+1.7 /28.9 OPEN STATUS OF JAUX
DI a.7 DI b.7

6ES7221-1BH32-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DI1
DIG-A-1401-S118-EL-1402-R03 27 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

26.9 / +24 +24 / 30.0


+24
26.9 / -24 -24 / 30.0
-24
-XR 69 -XR 74 -XR 79 -XR 82 -XR 84 -XR 86 -XR 88 -XR 90

OPEN STATUS OF JAUX


TCS STATUS OF JAUX
SERVICE POSITION

SERVICE POSITION
RELAY OPERATED

RELAY OPERATED

RELAY OPERATED

RELAY OPERATED

RELAY OPERATED
RELAY OPERATE
REMOTE OF JT1
STATUS OF JT1

REMOTE OF JT2
STATUSOF JT2
SELECTOR ON

OPEN STATUS
EARTH CLOSE

EARTH CLOSE

SELECTOR ON
OF CB OF JT1

OF CB OF JT2
TCS STATUS

OF JM1

OF JM2

OF JM4

OF JM5
OF JT1

OF JT2

OF JT2
OF T2
-XR 70 71 72 73 -XR 75 76 77 78 -XR 80 81 -XR 83 -XR 85 -XR 87 -XR 89 -XR 91 92

K1 K3 K5 K7 K9 K11 K13 K15 K17 K19 K21 K23 K25 K27 K29 K31

-XF 83 -XF 84 -XF 85 -XF 86 -XF 87 -XF 88 -XF 89 -XF 90 -XF 91 -XF 92 -XF 93 -XF 94 -XF 95 -XF 96 -XF 97 -XF 98
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
-S2/DI1 K2 K4 K6 K8 CE K10 K12 K14 K16 K18 K20 K22 K24 K26 K28 K30 K32
/27.3

-X10 1M DI a.0 DI a.1 DI a.2 DI a.3 -X11 FE 2M DI a.4 DI a.5 DI a.6 DI a.7 n.c. -X12 3M DI b.0 DI b.1 DI b.2 DI b.3 -X13 4M DI b.4 DI b.5 DI b.6 DI b.7

IX+1.0

IX+1.1

IX+1.2

IX+1.3

IX+1.4

IX+1.5

IX+1.6

IX+1.7
/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.3

/27.5

/27.5

/27.5

/27.5

/27.5

/27.5

/27.5

/27.5

/27.5

/27.5
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
- - - -
+ + + +

6ES7221-1BH32-0XB0 SM1221 DI 16 x 24 VDC S7-1200 SIEMENS

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DI1
DIG-A-1401-S118-EL-1402-R03 28 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

-S/DI2
/30.0

S7-1200 SIEMENS
SM1221 DI 16 x 24 VDC

-X10:1 -X12:1
n.c. n.c.
-X10:2 -X12:2
n.c. n.c.
-X10:3 -X12:3
/30.0 - + + - /30.5
1M 3M
-X10:4 -X12:4
EARTH CLOSE STATUS OF JAUX /30.1 IX.0 IX+1.0 /30.5 EARTH SWITCH STATUS OF DS02
DI a.0 DI b.0
-X10:5 -X12:5
RELAY OPERATED OF JAUX /30.1 IX.1 IX+1.1 /30.6 SPARE7
DI a.1 DI b.1
-X10:6 -X12:6
SELECTOR ON REMOTE OF JAUX /30.2 IX.2 IX+1.2 /30.6 SPARE8
DI a.2 DI b.2
-X10:7 -X12:7
TRANSFORMER TRIP JAUX /30.2 IX.3 IX+1.3 /30.7 SPARE9
DI a.3 DI b.3

-X11:1 -X13:1
/30.2
FE n.c.
-X11:2 -X13:2
n.c. n.c.
-X11:3 -X13:3
/30.2 - + + - /30.7
2M 4M
-X11:4 -X13:4
TRANSFORMER ALARM JAUX /30.3 IX.4 IX+1.4 /30.8 SPARE10
DI a.4 DI b.4
-X11:5 -X13:5
OPEN STATUS OF DS01 /30.3 IX.5 IX+1.5 /30.8 SPARE11
DI a.5 DI b.5
-X11:6 -X13:6
EARTH SWITCH STATUS OF DS01 /30.4 IX.6 IX+1.6 /30.8 SPARE12
DI a.6 DI b.6
-X11:7 -X13:7
OPEN STATUS OF DS02 /30.4 IX.7 IX+1.7 /30.9 SPARE13
DI a.7 DI b.7

6ES7221-1BH32-0XB0

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DI2
DIG-A-1401-S118-EL-1402-R03 29 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

28.9 / +24
+24
28.9 / -24
-24
-XR 93 98 100 102 104 106
108 110 112 114 116 118 120

RELAY OPERATED

REMOTE OF JAUX

STATUS OF DS01

STATUS OF DS02
STATUS OF JAUX

EARTH SWITCH

EARTH SWITCH
TRANSFORMER

TRANSFORMER
T1A

SELECTOR ON

OPEN STATUS

OPEN STATUS
EARTH CLOSE
11

ALARM JAUX

DS01 PANEL

DS02 PANEL
TRIP JAUX

SPARE10

SPARE11

SPARE12

SPARE13
SPARE8

SPARE9
PS1

OF DS01

OF DS02
OF JAUX
/2.1 14
T2A
-XR 94 95 -XR 96 97 99 101 103 105 107 11 111 113 115 117 119 121
PS2
/2.3 14

T3A
109

I1 I3 I5 I7 I9 I11 I13 I15 I17 I19 I21 I23 I25 I27 I29 I31

-XF 99 -XF 100 -XF 101 -XF 102 -XF 103 -XF 104 -XF 105 -XF 106 -XF 107 -XF 108 -XF 109 -XF 110 -XF 111 -XF 112 -XF 113 -XF 114
FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE FUSE
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL
SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5 SIZE 2.5
0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A 0.5A
-S/DI2 I2 I4 I6 I8 CE I10 I12 I14 I16 I18 I20 I22 I24 I26 I28 I30 I32
/29.3

-X10 1M DI a.0 DI a.1 DI a.2 DI a.3 -X11 FE 2M DI a.4 DI a.5 DI a.6 DI a.7 n.c. -X12 3M DI b.0 DI b.1 DI b.2 DI b.3 -X13 4M DI b.4 DI b.5 DI b.6 DI b.7

IX+1.0

IX+1.1

IX+1.2

IX+1.3

IX+1.4

IX+1.5

IX+1.6

IX+1.7
/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.3

/29.5

/29.5

/29.5

/29.5

/29.5

/29.5

/29.5

/29.5

/29.5

/29.5
IX.0

IX.1

IX.2

IX.3

IX.4

IX.5

IX.6

IX.7
- - - -
+ + + +

6ES7221-1BH32-0XB0 SM1221 DI 16 x 24 VDC S7-1200 SIEMENS

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT S2/DI2
DIG-A-1401-S118-EL-1402-R03 30 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 11 11 11 11
-SP1 -SP2 -SP3 -SP4 -SP5
SPARE1 SPARE2 SPARE13 SPARE4 SPARE5
/19.4 14 12 /19.5 14 12 /19.6 14 12 /19.6 14 12 /19.7 14 12

K33 K34 K35 K36 K37 K38 K39 K40 K41 K42 K43 K44 K45 K46 K47

-XSO1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

11 11 11 11 11
-SP6 -SP7 -SP8 -SP9 -SP10
SPARE6 SPARE7 SPARE8 SPARE9 SPARE10
/19.7 14 12 /21.1 14 12 /21.2 14 12 /21.2 14 12 /21.3 14 12

K48 K49 K50 K51 K52 K53 K54 K55 K56 K57 K58 K59 K60 K61 K62

-XSO1 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

11 11 11 11 11
-SP11 -SP12 -SP13 -SP14 -CC/JU1
SPARE11 SPARE12 SPARE13 SPARE14 CLOSE CMD
/21.3 14 12 /21.4 14 12 /21.5 14 12 /21.5 14 12 OF JU1 14 12
/24.2

K63 K64 K65 K66 K67 K68 K69 K70 K71 K72 K73 K74 K75 K76 K77

-XSO1 31 32 33 34 35 36 37 38 39 40 41 42 -XSO2 1 2 3

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 31 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 11 11 11 11
-OC/JU1 -CC/JU2 -OC/JU2 -CC/JU3 -OC/JU3
OPEN CMD CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD
OF JU1 14 12 OF JU2 14 12 OF JU2 14 12 OF JU3 14 12 OF JU3 14 12
/24.3 /24.3 /24.4 /24.4 /24.5

I33 I34 I35 I36 I37 I38 I39 I40 I41 I42 I43 I44 I45 I46 I47

-XSO2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

11 11 11 11 11
-CC/JU4 -OC/JU4 -CC/JT1 -OC/JT1 -CC/JT2
CLOSE CMD OPEN CMD CLOSE CMD OPEN CMD CLOSE CMD
OF JU4 14 12 OF JU4 14 12 OF JT1 14 12 OF JT1 14 12 OF JT2 14 12
/24.6 /24.6 /24.7 /24.7 /26.0

I48 I49 I50 I51 I52 I53 I54 I55 I56 I57 I58 I59 I60 I61 I62

-XSO2 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

11 11 11 11 11
-OC/JT2 -CC/JAUX -OC/JAUX -SP23 -SP24
OPEN CMD CLOSE CMD OPEN CMD PARALLEL MODE PARALLEL MODE
OF JT2 14 12 OF JAUX 14 12 OF JAUX 14 12 TO PLT1 14 12 TO PLT1 14 12
/26.1 /26.1 /26.2 /26.3 /26.3

I63 I64 I65 I66 I67 I68 I69 I70 I71 I72 I73 I74 I75 I76 I77

-XSO2 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 32 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

11 11 11 11 11
-SP25 -SP26 -SP27 -SP28 -SP29
PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE
TO PLT2 14 12 TO PLT2 14 12 TO PLT3 14 12 TO PLT3 14 12 TO PLT4 14 12
/26.4 /26.4 /26.5 /26.5 /26.6

K78 K79 K80 K81 K82 K83 K84 K85 K86 K87 K88 K89 K90 K91 K92

-XSO2 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

11 11 11 11 11
-SP30 -SP31 -SP32 -SP33 -SP34
SPARE30 SPARE31 SPARE32 SPARE33 SPARE34
/26.7 14 12 /26.7 14 12 /26.8 14 12 /26.8 14 12 /26.9 14 12

I78 I79 I80 I81 I82 I83 I84 I85 I86 I87 I88 I89 I90 I91 I92

-XSO2 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 33 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

21 31 41 21 31 41
-SP23 -SP23 -SP23 -SP24 -SP24 -SP24
PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE
TO PLT1 24 22 TO PLT1 34 32 TO PLT1 44 42 TO PLT1 24 22 TO PLT1 34 32 TO PLT1 44 42
/26.3 /26.3 /26.3 /26.3 /26.3 /26.3

P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18

-XSO2 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96

21 31 41 21 31 41
-SP25 -SP25 -SP25 -SP26 -SP26 -SP26
PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE
TO PLT2 24 22 TO PLT2 34 32 TO PLT2 44 42 TO PLT2 24 22 TO PLT2 34 32 TO PLT2 44 42
/26.4 /26.4 /26.4 /26.4 /26.4 /26.4

P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 P33 P34 P35 P36

-XSO2 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114

21 31 41 21 31 41
-SP27 -SP27 -SP27 -SP28 -SP28 -SP28
PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE PARALLEL MODE
TO PLT3 24 22 TO PLT3 34 32 TO PLT3 44 42 TO PLT3 24 22 TO PLT3 34 32 TO PLT3 44 42
/26.5 /26.5 /26.5 /26.5 /26.5 /26.5

P37 P38 P39 P40 P41 P42 P43 P44 P45 P46 P47 P48 P49 P50 P51 P52 P53 P54

-XSO2 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 34 /34
APPROVED M.A
0 1 2 3 4 5 6 7 8 9

21 31 41
-SP29 -SP29 -SP29
PARALLEL MODE PARALLEL MODE PARALLEL MODE
TO PLT4 24 22 TO PLT4 34 32 TO PLT4 44 42
/26.6 /26.6 /26.6

P55 P56 P57 P58 P59 P60 P61 P62 P63

-XSO2 133 134 135 136 137 138 139 140 141

POWER PLANT DCS


CLIENT CONTRACTOR VENDOR PROJECT SUBJECT VENDOR
POWER PLANT DCS DESIGNED V.N CLIENT NO:
Rev:03
DRAWN E.GROUP
30 MW
IRAN KHODRO CO. PART NIROO SHIRVAN APEX CONTROLLED V.N VENDOR NO: SHEET
POWER PLANT TERMINAL TO OUT
DIG-A-1401-S118-EL-1402-R03 35 /34
APPROVED M.A