NetSure™ 701NVBB DC Power System

System Application Guide

SYSTEM OVERVIEW
Description: -48VDC @ up to 4000 Amperes Power System
This power system is designed to power a load while charging a positive grounded battery. This
system is capable of operating in a batteryless installation or off battery for maintenance purposes.
The system is designed for operation with the positive output grounded.
The NetSure 701NVBB DC Power System is a complete integrated power system containing rectifiers
(PCUs), intelligent control, metering, monitoring, and distribution. This power system consists of the
following components.
• Distribution Cabinet
The system always includes a minimum of one Distribution Cabinet, which provides DC
distribution through fuses and/or circuit breakers.
Four different sizes of Distribution Cabinets may be ordered to accept from one (1) to four (4)
Distribution Bus Modules. A variety of Distribution Bus Modules are available that provide
combinations of load distribution, battery distribution, low voltage load or battery disconnect, and
manual battery disconnect. The Distribution Cabinet is factory mounted in the relay rack
specified when ordered.
Most of the Distribution Bus Modules accept either TPS/TLS-type fuseholders or Bullet Nose-
type circuit breakers. TPH-type fuses and GJ/218-type circuit breakers are also available in
ratings up to 600 amps.
• Meter-Control-Alarm (MCA) Assembly
The system contains one MCA. The MCA controls the
operation of the Rectifier Modules (PCUs). The MCA also
provides power system control, metering, monitoring, and
alarm functions.
• Rectifier Module (PCU)
Mounting Shelves
The system contains one or more Rectifier Module (PCU)
Mounting Shelves, each of which houses up to six (6)
Rectifier Modules (PCUs). Refer to PD588705000 for more
information.
• Rectifier Modules (PCUs)
The system contains Rectifier Modules (PCUs), which
provide load power, battery float current, and battery
recharge current during normal operating conditions. Refer
to UM1R483500e (Rectifier User Instructions) for more
information.
• DC-DC Converter System
Where +24VDC load power is required, DC-DC Converters
are available in this power system.
• Monitoring System
An LMS1000 Monitoring System may also be furnished. Refer to SAG586505500 for more
information.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 1 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Family: NetSure
Spec. No.: 582126000
Model: 701NVBB
Output Voltage: -48 Volts DC
Rectifier System Input Voltage Nominal 208/240 volts AC, single phase, 50/60 Hz, with an operating range of
176 to 264 volts. Acceptable input frequency range is 45 to 65 Hz.
Output Capacity:
System: 4000 Amperes, maximum
Bay: 2000 Amperes, maximum (1500A maximum when equipped with List AH;
1200A maximum when equipped with List RA or RB)
Distribution Bus Module: 500 Amperes, maximum (List ND rated for 960A)
Rectifier Module (PCU)
1R483200 and 1R483200e: 55.2A @ -58VDC to 66.6A @ -48VDC
Agency Approval: UL 1801 Listed (“c UL”), NEBS
Framework Type: Relay Rack
Mounting Width: 23 Inches, nominal
Mounting Depth:
Distribution Cabinet: 18 Inches (single-bay), 21 Inches (multi-bay)
(List RC, RD, and RE adds 5.25 inches to back of system, see Overall
Dimensions Illustrations)
Rectifier Module
Mounting Shelf: 18 Inches
Battery Tray: 24.4 Inches
Access: Front, Sides, and Rear for Installation and Maintenance,
Front for Operation
Supplemental Bay(s) Available: One
Control: Microprocessor
Color: Bay and Rectifier Module Faceplates: Textured Gray (Spec. M500-147)
Rectifier Shelf and Rectifier Modules Bodies: Bright Zinc Plating (Spec. M500-
53)
Environment: -40°C to +40°C (-40°F to +104°F)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 2 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
TABLE OF CONTENTS
SYSTEM OVERVIEW ........................................................................................................................................................................................................................ 1
MAIN COMPONENTS ILLUSTRATIONS ................................................................................................................................................................................ 6
582126000 ......................................................................................................................................................................................................................................................................6
LIST DESCRIPTIONS ....................................................................................................................................................................................................................... 7
List Numbers .................................................................................................................................................................................................................................................................7
List 1: Main Bay Common Equipment (Power and Distribution).........................................................................................................................................7
List 2: Supplemental Bay Common Equipment (Power and Distribution) (located next to Main Bay) .....................................................8
List 4: “Distribution Only” Option for Lists 2 or 5.........................................................................................................................................................................9
List 5: Supplemental Bay Common Equipment (Power and Distribution) (located away from Main Bay)..............................................9
List 10: MCA (Standard Application) ................................................................................................................................................................................................ 10
List 11: MCA (Special Application) ...................................................................................................................................................................................................... 10
List 12: MCA (Special Application) ..................................................................................................................................................................................................... 10
List 13: MCA (Special Application) .......................................................................................................................................................................................................11
List 21: One-Row Distribution Cabinet ...............................................................................................................................................................................................11
List 22: Two-Row Distribution Cabinet .............................................................................................................................................................................................12
List 23: Three-Row Distribution Cabinet .........................................................................................................................................................................................12
List 24: Four-Row Distribution Cabinet ............................................................................................................................................................................................13
List 29: Top Shield for Distribution Cabinet ..................................................................................................................................................................................13
List 31: Rectifier Module Mounting Shelf Interface Components ....................................................................................................................................13
List 45: Top Mount AC Input Termination Panel for Single Phase Input....................................................................................................................14
List 46: Top Mount AC Input Termination Panel for Three Phase Input ....................................................................................................................14
List 62: Optional 20A Converter Module .........................................................................................................................................................................................14
List 63: Optional 160A Converter Shelf (Initial Shelf)..............................................................................................................................................................15
List 64: Optional 160A Converter Shelf (Expansion Shelf) ..................................................................................................................................................15
List 71: Optional Audible Alarm and Alarm Termination Circuit Card...........................................................................................................................15
List 72: MCA Interface Modem Option ..............................................................................................................................................................................................16
List 73: MCA Interface WinLink Software .......................................................................................................................................................................................16
List 74: MCA Interface Combination Modem/RS-232 Option ............................................................................................................................................ 17
List 75: MCA Interface Ethernet Option: Modbus® TCP + Web Interface ................................................................................................................... 17
List 76: MCA Interface Ethernet Option: Modbus® TCP + Web Interface + SNMP ............................................................................................... 17
List 77: MCA Interface Ethernet Option: Modbus® TCP + Web Interface + Battery Monitoring ..................................................................18
List 78: MCA Interface Ethernet Option: Modbus® TCP + Web Interface + SNMP + Battery Monitoring..............................................18
List 79: Capacitor Precharge Assembly ...........................................................................................................................................................................................19
List 80: LMS1000 Monitoring System ...............................................................................................................................................................................................19
List 92: Battery Stand Interface Components ..............................................................................................................................................................................19
List 93: Battery Tray, Pre-Cabled ........................................................................................................................................................................................................20
Distribution Panels .................................................................................................................................................................................................................................................24
List AA: Distribution Bus Module (P/N 509840) (24) Fuse/Circuit Breaker System Positions ..................................................................24
List AB: Distribution Bus Module (P/N 428316100) (3) GJ/218 Circuit Breaker System Positions ........................................................... 25
List AC: Distribution Bus Module (P/N 507198) (3) GJ/218 Circuit Breaker System Positions ................................................................... 26
List AD: Distribution Bus Module (P/N 509565) (8) GJ/218 Circuit Breaker System Positions (Upper Two Rows) ..................... 27
List AE: Distribution Bus Module (P/N 509648) (8) GJ/218 Circuit Breaker System Positions (Lower Two Rows) ..................... 28
List AG: Distribution Bus Module (P/N 514010) (2) TPH Fuse System Positions ................................................................................................29
List AH: Distribution Bus Module Ground Bar Assembly (P/N 500676) for Use with Up to (2) List AG, AJ, CG, or
CJ; or (1) List AP ..............................................................................................................................................................................................................................................30
List AJ: Distribution Bus Module (P/N 520819) (2) TPH Fuse System Positions with Load Metering Shunts .................................. 31
List AK: Distribution Bus Module (P/N 520805) (24) Fuse/Circuit Breaker System Positions ................................................................... 32
List AL: Distribution Bus Module Ground Bar Assembly for Use with Up to (2) List AK................................................................................. 33
List AM: Distribution Bus Module (P/N 524632) (20) Fuse/Circuit Breaker System Positions (1) 3-Pole Input
Disconnect Fuse/Circuit Breaker Position ......................................................................................................................................................................................34
List AN: Distribution Bus Module (P/N 541386) (24) Fuse/Circuit Breaker System Positions .................................................................... 35
List AP: Distribution Bus Module (P/N 541537) (4) TPH Fuse System Positions ................................................................................................36
List BA: Distribution Bus Module (P/N 520600) (12) Fuse/Circuit Breaker System Positions with LVD (8)
Fuse/Circuit Breaker System Positions without LVD .............................................................................................................................................................. 37
List CA: Distribution Bus Module (P/N 509846) (20) Fuse/Circuit Breaker System Positions w/LVLD .............................................. 38
List CB: Distribution Bus Module (P/N 509904) (3) GJ/218 Circuit Breaker System Positions w/LVLD ............................................. 39
List CD: Distribution Bus Module (P/N 507197) (3) GJ/218 Circuit Breaker System Positions w/LVLD .............................................. 40

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 3 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CE: Distribution Bus Module (P/N 509563) (8) GJ/218 Circuit Breaker System Positions w/LVLD (Upper Two
Rows) .......................................................................................................................................................................................................................................................................41
List CF: Distribution Bus Module (P/N 509646) (8) GJ/218 Circuit Breaker System Positions w/LVLD (Lower Two
Rows) ......................................................................................................................................................................................................................................................................42
List CG: Distribution Bus Module (P/N 514037) (2) TPH Distribution Fuse Positions w/LVLD..................................................................43
List CJ: Distribution Bus Module (P/N 520937) (2) TPH Distribution Fuse Positions with Load Metering Shunts
and LVLD .............................................................................................................................................................................................................................................................44
List EA: Distribution Bus Module (P/N 509852) (16) Fuse/Circuit Breaker System Positions and (4) Fuse/Circuit
Breaker Battery Disconnect Positions ..............................................................................................................................................................................................45
List GB: Distribution Bus Module (P/N 513963) (8) Fuse/Circuit Breaker System Positions w/LVD and (1) TPH
Fuse Battery Disconnect Position ........................................................................................................................................................................................................46
List JA: Distribution Bus Module (Part No. 524482) (4) –48V Fuse/Circuit Breaker System Positions and (16)
+24V Fuse/Circuit Breaker Subsystem Positions ......................................................................................................................................................................47
List JB: Distribution Bus Module (Part No. 524496) (12) –48V Fuse/Circuit Breaker System Positions and (8)
+24V Fuse/Circuit Breaker Subsystem Positions ......................................................................................................................................................................48
List JC: Distribution Bus Module (Part No. 524620) (14) –48V Fuse/Circuit Breaker System Positions and (6)
+24V Fuse/Circuit Breaker Subsystem Positions ......................................................................................................................................................................49
List JD: Distribution Bus Module (Part No. 524788) (14) –48V Fuse/Circuit Breaker System Positions and (8)
+24V Fuse/Circuit Breaker Subsystem Positions ......................................................................................................................................................................50
List KA: Distribution Bus Module (Part No. 524571) (4) –48V Fuse/Circuit Breaker System Positions and (16)
+24V Fuse/Circuit Breaker Subsystem Positions .......................................................................................................................................................................51
List LB: Distribution Bus Module (Part No. 524578) (8) –48V Fuse/Circuit Breaker System Positions w/LVD and
(8) +24V Fuse/Circuit Breaker Subsystem Positions .............................................................................................................................................................. 52
List LC: Distribution Bus Module (Part No. 524583) (12) –48V Fuse/Circuit Breaker System Positions w/LVD and
(4) +24V Fuse/Circuit Breaker Subsystem Positions.............................................................................................................................................................. 53
List NA: Distribution Bus Module (P/N 514336) (20) Fuse/Circuit Breaker Battery Disconnect Positions .........................................54
List NB: Distribution Bus Module (P/N 513809) (3) GJ/218 Circuit Breaker Battery Disconnect Positions........................................ 55
List NC: Distribution Bus Module (P/N 514025) (1) TPH Fuse Battery Disconnect Position ........................................................................56
List ND: Distribution Bus Module (P/N 514030) (2) TPH Fuse Battery Disconnect Positions .................................................................... 57
Battery Disconnect .................................................................................................................................................................................................................................................58
List RA: 1200A Low Voltage Battery Disconnect (LVBD) Contactor and Control Circuit (P/N 528442) ............................................. 58
List RB: 1200A Manual Battery Disconnect Contactor with Local and Remote Alarm (P/N 528443) ....................................................59
List RC: 2000A Manual Battery Disconnect Contactor with Local and Remote Alarm (P/N 528446) ................................................. 60
List RD: 2000A Low Voltage/Manual Battery Disconnect Contactor with Battery Current Monitoring (P/N
528447) ..................................................................................................................................................................................................................................................................61
List RE: 2000A Low Voltage Battery Disconnect Contactor with Battery Current Monitoring (P/N 535064)................................. 62
Bulk Feed Panels......................................................................................................................................................................................................................................................63
List TA: 800A Bulk Feed Distribution Bus Module (P/N 541530) (Internal Shunt).............................................................................................63
List TB: 1200A Bulk Feed Distribution Bus Module (P/N 541530), Bypass Shunt Busbar (P/N 541535), and External
Shunt Monitoring Kit (P/N 541134) (External Shunt) ..............................................................................................................................................................64
ACCESSORY DESCRIPTIONS ................................................................................................................................................................................................... 65
Rectifier Modules .....................................................................................................................................................................................................................................................65
Rectifier Module (PCU), High-Efficiency (P/N 1R483200e) ................................................................................................................................................65
Rectifier Module (PCU) (P/N 1R483200) .........................................................................................................................................................................................65
Relay Racks .................................................................................................................................................................................................................................................................66
Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries ............................................................................................................... 67
Distribution Devices ..............................................................................................................................................................................................................................................68
GMT Load Distribution Fuse Block Assembly Kit (P/N 514432) (10) GMT Fuse Positions.............................................................................68
GMT-Type Load Distribution Fuses ...................................................................................................................................................................................................70
Replacement Alarm, Reference, and Control Fuses ..................................................................................................................................................................71
TPH-Type Fuses ............................................................................................................................................................................................................................................. 72
GJ/218-Type Circuit Breakers ................................................................................................................................................................................................................ 73
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TPS/TLS Fuses....................................................................... 75
Rectifier Module Mounting Position Blank Cover Panel (P/N 21140440) ........................................................................................................................... 79
Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation (P/Ns 107021 and 106824) .................. 79
Battery Charge Temperature Compensation Probe Concentrator for Multiple Probe Use (TXM) ....................................................................80
Battery Temperature Probe Concentrator Kit (P/N 524570) .............................................................................................................................................80
Analog Battery Temperature Probe (P/N 521262) ....................................................................................................................................................................80
TXM Extension Cable (P/N 514153) ....................................................................................................................................................................................................80
Adding Additional Shelf in Field Output Busbar Kit (P/N 529139) ...........................................................................................................................................81

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 4 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Battery Busbar Kits ................................................................................................................................................................................................................................................82
Battery Busbar Extension Kit (P/N 514713)....................................................................................................................................................................................82
Battery Busbar Extension Kit (P/N 529143) ..................................................................................................................................................................................82
Battery Landing Busbar Kit (P/N 541371)........................................................................................................................................................................................82
Lug Adapter Busbars ............................................................................................................................................................................................................................................82
Lug Adapter Busbar for up to 500 MCM Cable on a two-pole GJ Breaker (P/N 559643) .............................................................................. 82
Lug Adapter Busbar for 225-250 Amp Bullet Nose Type Circuit Breaker (P/N 514717) ................................................................................... 83
Lug Adapter Busbar Kit for 125-200 Amp Bullet Nose Type Circuit Breaker (P/N 534449) ......................................................................... 83
Lug Adapter Busbar Kit for 225-250 Amp Bullet Nose Type Circuit Breaker (P/N 514714) ........................................................................... 83
Lug Hardware Kits ..................................................................................................................................................................................................................................................84
Bullet Distribution Assembly Lug Hardware Kit (P/N 520332) .........................................................................................................................................84
Bullet Distribution Assembly Lug Hardware Kit (P/N 101212) ...........................................................................................................................................84
LVD Contactor Bypass Kits (P/Ns 514910 and 514912) ..................................................................................................................................................................84
External Shunt Monitoring Kit (P/N 541134) ..........................................................................................................................................................................................84
System Load Shunt Test Point Kit (P/N 545569) ..............................................................................................................................................................................85
Optional Front Battery Cover Kits ................................................................................................................................................................................................................85
Optional eSure™ Power Extend Converter..............................................................................................................................................................................................86
Replacement Cables ..............................................................................................................................................................................................................................................87
Replacement Components ............................................................................................................................................................................................................................... 90
RECOMMENDED WIRE SIZES, BRANCH CIRCUIT PROTECTION, AND CRIMP LUGS ....................................................................................91
Load Distribution Wire Sizes and Lugs Selection .......................................................................................................................................................................91
Input Battery Wire Sizes and Lugs Selection ................................................................................................................................................................................92
Standard Crimp Lug Tables .....................................................................................................................................................................................................................94
Special Application Crimp Lug / Strap Combination Table .................................................................................................................................................95
Wire Size and Lug Selection Tables for Load and Battery Connections to TPS/TLS Fuses and Bullet Nose-Type
Circuit Breakers or Battery Branch Circuits ..................................................................................................................................................................................96
Wire Size and Lug Selection Tables for Load and Battery Connections to TPH Fuses and GJ/218-Type Circuit
Breakers or Battery Branch Circuits ...................................................................................................................................................................................................98
AC Input Branch Circuit Protection and Wire Size Selection (when Optional List 45 Top Mount AC Input
Termination Panel is Furnished) ........................................................................................................................................................................................................ 100
AC Input Branch Circuit Protection and Wire Size Selection (when Optional List 46 Top Mount AC Input
Termination Panel is Furnished) ......................................................................................................................................................................................................... 101
AC Input Branch Circuit Protection and Wire Size Selection (when wiring to Rectifier Module Mounting Shelf[s]) ...................102
Relay Rack Frame Grounding Requirements ..............................................................................................................................................................................102
External Alarm, Reference, and Control Wire Sizes ................................................................................................................................................................102
SPECIFICATIONS.......................................................................................................................................................................................................................... 103
1.1 Environmental Ratings ............................................................................................................................................................................................................................103
1.2 Compliance Information .........................................................................................................................................................................................................................103
1.3 MCA Features ...............................................................................................................................................................................................................................................103
MECHANICAL SPECIFICATIONS ........................................................................................................................................................................................... 113
Overall Dimensions ................................................................................................................................................................................................................................................113
List 24 (Four Bus Row Cabinet) ............................................................................................................................................................................................................113
List 23 (Three Bus Row Cabinet) .........................................................................................................................................................................................................114
List 22 (Two Bus Row Cabinet).............................................................................................................................................................................................................115
List 21 (One Bus Row Cabinet) ..............................................................................................................................................................................................................116
List 31 (Rectifier Module Mounting Shelf), List 45 or 46 (Top Mount AC Termination Panel), List 80 (LMS1000
Monitoring System), List 92 (Battery Stands), and List RC, RD, and RE (Battery Disconnects) ................................................................ 117
List 93 (Battery Tray)..................................................................................................................................................................................................................................118
Optional Digital Battery Charge Temperature Compensation Probe (P/N 107021 and 106824) ...............................................................119
Optional Analog Battery Temperature Probe (P/N 521262) ..............................................................................................................................................119
Electrical Connection Locations and Dimensions ............................................................................................................................................................................120
Input Battery ....................................................................................................................................................................................................................................................120
Load Distribution ..........................................................................................................................................................................................................................................125
AC Input ..............................................................................................................................................................................................................................................................125
External Alarm, Reference, and Control .........................................................................................................................................................................................128
RELATED DOCUMENTATION ................................................................................................................................................................................................ 129
BATTERY MANUFACTURER INFORMATION ................................................................................................................................................................. 130

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 5 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
MAIN COMPONENTS ILLUSTRATIONS
582126000
Main Bay:…………………………………………………………………….......…List 1
Supplemental Bay (located next to Main Bay):….………List 2
Supplemental Bay 'Distribution Only' Option:…………....List 4
Supplemental Bay (located away from Main Bay):..….List 5

List 45, 46: Top Mount AC Distribution Assembly List AA, AB, AC, AD,
Input Termination Panel AE, AG, AH, AJ, AK, AL, AM, AN, AP, BA, CA,
CB, CD, CE, CF, CG, CJ, EA, GB, JA, JB, JC,
JD, KA, LB, LC, NA, NB, NC, ND, TA, TB
List RA: LV Battery Disconnect
Distribution Bus List RB, RC: Manual Battery Disconnect
List RD: LV/Manual Battery Disconnect
Row D (Row 4) List RE: LV Battery Disconnect

Distribution Bus
Row C (Row 3) Other Options
List 29: Distribution Cabinet Top Shield
Distribution Cabinet Distribution Bus List 62: 20A Converter Module
List 24 (4-Row) Row B (Row 2) List 63, 64: 160A DC-DC Converter
List 23 (3-Row) Shelves
List 22 (2-Row) List 71: Optional Audible Alarm and Alarm
List 21 (1-Row) Distribution Bus Termination Circuit Card
Row A (Row 1) List 72: MCA Interface Modem Option
MCA List 73:MCA Interface WinLink Software
List 10, 11, 12, 13 List 74: MCA Interface Combination
Modem/RS-232 Option
LMS1000
List 75: MCA Interface Ethernet Option:
Modbus TCP + Web Interface
Monitoring System
List 80 List 76: MCA Interface Ethernet Option:
Modbus TCP + Web Interface + SNMP
List 77: MCA Interface Ethernet Option:
Modbus TCP + Web Interface + Battery
Monitoring
List 78: MCA Interface Ethernet Option:
Rectifier Module Modbus TCP + Web Interface + SNMP +
Mounting Shelf Components Battery Monitoring
List 31 List 79: Capacitor Precharge Assembly
List 92: Battery System
Rectifier Module List 93: Battery Tray
P/N 1R483200e or
P/N 1R483200

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 6 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
LIST DESCRIPTIONS
List Numbers
List 1: Main Bay Common Equipment (Power and Distribution)
Features
♦ Provides common equipment for one “power and distribution” bay rated for up to 2000 amperes of distribution.
♦ Accepts one (1) Distribution Cabinet (options are 1-Row, 2-Row, 3-Row, or 4-Row cabinet).
♦ Accepts up to six (6) Rectifier Module Mounting Shelf(s).
♦ Accepts one (1) Meter-Control-Alarm (MCA) Assembly.
Restrictions
Cannot use a List 21 in a List 1 when List 1 is used with a List 2.
(List 21 is not provided with connection points for inter-bay busbars.)
Ordering Notes
1) Order a relay rack per 'Relay Racks' under ACCESSORY DESCRIPTIONS. If required, order Relay Rack Transition Plates
per 'Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries' under ACCESSORY DESCRIPTIONS. A
ship loose option is available, as described in 'Relay Racks' under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 21, 22, 23, or 24 Distribution Cabinet.
3) Order up to four (4) Distribution Bus Modules as required per 'Distribution Bus Modules' and the capacity of the
Distribution Cabinet ordered.
4) Order one (1) List 10, 11, 12, or 13 MCA.
5) Order as required;
the LMS1000 Monitoring System per List 80,
or
an MCA Interface option per Lists 72, 74, 75, 76, 77, and 78.
Also order, as required, WinLink Software per List 73.
6) Order interface components for Rectifier Module Mounting Shelf(s) as required per List 31. Order Rectifier Module
Mounting Shelf(s) per PD588705000.
7) Order Rectifier Modules as required per P/N 1R483200e or 1R483200.
8) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting
position in the system.
9) Order converter shelves and modules, as required, per Lists 62, 63, and 64.
10) Order fuses and/or circuit breakers, as required, per 'Distribution Devices' under ACCESSORY DESCRIPTIONS.
11) Order input and load distribution lugs, as required, per 'Wiring Components' under ACCESSORY DESCRIPTIONS.
12) Order additional List Options, as required, per Lists 29, 45, 46, 71, 79, 92, and 93.
13) Order any additional Accessory Options described under ACCESSORY DESCRIPTIONS.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 7 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 2: Supplemental Bay Common Equipment (Power and Distribution)
(located next to Main Bay)
Features
♦ Provides common equipment for one bussed “power and distribution” bay rated for up to 2000 amperes of distribution.
Includes interbay power busbars and communications cabling.
♦ Mounts to either left or right side of List 1 Main Bay.
♦ Accepts one (1) Distribution Cabinet (options are 2-Row, 3-Row, or 4-Row cabinet).
♦ Accepts up to six (6) Rectifier Module Mounting Shelf(s).
or
Can be configured for “distribution only” (no Rectifier Module Mounting Shelf).
Restrictions
Will not accept List 21 Distribution Cabinet.
(List 21 is not provided with connection points for interbay bus bars.)
Order maximum of one (1) List 2 or List 5 per Power System. Cannot be used when List 5 is ordered. Order List 2 or List 5,
not both.
Rear access required for installation of inter-bay busbars.
Ordering Notes
1) Order a relay rack per 'Relay Racks' under ACCESSORY DESCRIPTIONS. If required, order Relay Rack Transition Plates
per 'Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries' under ACCESSORY DESCRIPTIONS.
Relay rack must be same height as relay rack ordered for List 1. A ship loose option is available, as described in 'Relay
Racks' under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 22, 23, or 24 Distribution Cabinet.
3) Order up to four (4) Distribution Bus Modules as required per 'Distribution Bus Modules' and the capacity of the
Distribution Cabinet ordered.
4) Order interface components for Rectifier Module Mounting Shelf(s) as required per List 31. Order Rectifier Module
Mounting Shelf(s) per PD588705000.
or
Order Supplemental Bay 'Distribution Only' option per List 4.
5) Order Rectifier Modules as required per P/N 1R483200e or 1R483200.
6) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting
position in the system.
7) Order fuses and/or circuit breakers, as required, per 'Distribution Devices' under ACCESSORY DESCRIPTIONS.
8) Order input and load distribution lugs, as required, per 'Wiring Components' under ACCESSORY DESCRIPTIONS.
9) Order additional List Options, as required, per Lists 29, 45, 46, 79, 92, and 93.
10) Order any additional Accessory Options described under ACCESSORY DESCRIPTIONS.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 8 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 4: “Distribution Only” Option for Lists 2 or 5
Features
♦ Provides components needed to convert one List 2 or 5 bay from “power and distribution” to “distribution only”.
Restrictions
Rectifier Module Mounting Shelf(s) cannot be mounted in a bay when List 4 is installed.
Ordering Notes
1) Order one List 4 for each List 2 or 5 being ordered for distribution only.

List 5: Supplemental Bay Common Equipment (Power and Distribution)


(located away from Main Bay)
Features
♦ Provides common equipment for one remote “power and distribution” bay rated for up to 2000 amperes of distribution.
Includes interbay communications cabling.
♦ Accepts one (1) Distribution Cabinet (options are 1-Row, 2-Row, 3-Row, or 4-Row cabinet).
♦ Accepts up to six (6) Rectifier Module Mounting Shelf(s).
or
Can be configured for “distribution only” (no Rectifier Module Mounting Shelf).
Restrictions
Order maximum of one (1) List 2 or List 5 per Power System. Cannot be used when List 2 is ordered. Order List 2 or List 5, not
both.
Interbay power cabling is not included, and must be separately provided per site requirements.
Ordering Notes
1) Order a relay rack per 'Relay Racks' under ACCESSORY DESCRIPTIONS. If required, order Relay Rack Transition Plates
per 'Transition Plates to Mount Relay Rack on Top of GNB Absolyte IIP Batteries' under ACCESSORY DESCRIPTIONS. A
ship loose option is available, as described in 'Relay Racks' under ACCESSORY DESCRIPTIONS.
2) Order one (1) List 21, 22, 23, or 24 Distribution Cabinet.
3) Order up to four (4) Distribution Bus Modules as required per 'Distribution Bus Modules' and the capacity of the
Distribution Cabinet ordered.
4) Order interface components for Rectifier Module Mounting Shelf(s) as required per List 31. Order Rectifier Module
Mounting Shelf(s) per PD588705000.
or
Order Supplemental Bay 'Distribution Only' option per List 4.
5) Order Rectifier Modules as required per P/N 1R483200e or 1R483200.
6) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting
position in the system.
7) Order fuses and/or circuit breakers, as required, per 'Distribution Devices' under ACCESSORY DESCRIPTIONS.
8) Order input and load distribution lugs, as required, per 'Wiring Components' under ACCESSORY DESCRIPTIONS.
9) Order additional List Options, as required, per Lists 29, 45, 46, 79, 92, and 93.
10) Order any additional Accessory Options described under ACCESSORY DESCRIPTIONS.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 9 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 10: MCA (Standard Application)
Features
♦ Provides one standard application Meter-Control-Alarm (MCA) assembly
(Configuration No. 534876). Refer to SPECIFICATIONS for a description
of MCA functions.
♦ Alarms: Major, Minor, High Voltage #1, High Voltage #2, Battery on Discharge, 50% Battery On Discharge, AC Fail, MCA
Audible, Test/Equalize Mode.
Restrictions
Only one (1) MCA per power system is required.
Mounts in the Main Bay Distribution Cabinet.
Cannot be ordered with List 2 or List 5.
Ordering Notes
1) Order one (1) List 10, 11, 12, or 13 as required per power system.

List 11: MCA (Special Application)


Features
♦ Provides one special application Meter-Control-Alarm (MCA) assembly
(Configuration No. 534877). Refer to SPECIFICATIONS for a description
of MCA functions.
♦ Alarms: Major, Minor, High Voltage #1, Rectifier Module Fail Major, Battery On Discharge, Rectifier Module Fail Minor, AC
Fail, MCA Audible, Fuse/Circuit Breaker.
Restrictions
Only one (1) MCA per power system is required.
Mounts in the Main Bay Distribution Cabinet.
Cannot be ordered with List 2 or List 5.
Ordering Notes
1) Order one (1) List 10, 11, 12, or 13 as required per power system.

List 12: MCA (Special Application)


Features
♦ Provides one special application Meter-Control-Alarm (MCA) assembly (Configuration No. 534878). Refer to
SPECIFICATIONS for a description of MCA functions.
♦ Alarms: Major, Minor, High Voltage #1, MCA Fail, Battery on Discharge, Very Low Voltage, AC Fail, Fuse/Circuit Breaker,
Rectifier Module Fail.
Restrictions
Only one (1) MCA per power system is required.
Mounts in the Main Bay Distribution Cabinet.
Cannot be ordered with List 2 or List 5.
Ordering Notes
1) Order one (1) List 10, 11, 12, or 13 as required per power system.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 10 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 13: MCA (Special Application)
Features
♦ Provides one special application Meter-Control-Alarm (MCA) assembly
(Configuration No. 534879). Refer to SPECIFICATIONS for a description of
MCA functions.
♦ Alarms: Major, Minor, Test/Equalize 2, Fuse/Circuit Breaker, Battery on Discharge, 50% Battery On Discharge, AC Fail,
Low Voltage Disconnect, Test/Equalize 1.
Restrictions
Only one (1) MCA per power system is required.
Mounts in the Main Bay Distribution Cabinet.
Cannot be ordered with List 2 or List 5.
Ordering Notes
1) Order one (1) List 10, 11, 12, or 13 as required per power system.

List 21: One-Row Distribution Cabinet


Features
♦ Accepts one (1) Distribution Bus Module.
♦ Rated for up to 500 amperes of distribution (960 amperes when equipped
with List ND).
♦ Available for use in List 1 and List 5 bays.
♦ One (1) Quad Shunt circuit card (P/N 507431) is provided with each
distribution cabinet. This circuit card can monitor up to four (4) system
distribution load shunts. All shunt cards interface with the MCA for system
distribution load current monitoring.
♦ A Low Voltage Disconnect (LVD) circuit card (P/N 509477) is provided in
each Distribution Cabinet that…
 Contains one or more distribution rows that are equipped with a low
voltage disconnect contactor, or
 Controls a Low Voltage Battery Disconnect (LVBD) contactor located in an associated Battery Stand.
The LVD circuit card provides three separate control circuits. Each control circuit can be programmed, through the
MCA, with its own disconnect voltage setpoint and one global reconnect setpoint. One LVD circuit card can control up to
four (4) contactors. Any contactor can be controlled by any of the three control circuits on the card by setting of user-
selectable switches.

Where more than one Distribution Cabinet contains an LVD control circuit card, the control circuits on all LVD circuit
cards can be set to any of the three MCA-controlled disconnect setpoints independently with user-selectable switches.

Each of the three control circuits on any LVD card consists of two individual battery voltage monitors, both of which
must sense low system voltage before disconnection can occur. This redundancy prevents a control circuit failure from
unnecessarily disconnecting loads or batteries.

The user can set the low voltage disconnect circuits for either automatic or manual reconnect.
 Automatic Reconnect: When system bus voltage recovers to a preset adjustable value, the low voltage disconnect
circuits automatically reconnect the loads (or battery) to the system bus.
 Manual Reconnect: When system bus voltage has recovered to a preset adjustable value, the user must issue a
command via the MCA to reconnect loads (or battery) to the system bus.
A local switch provided in each Distribution Cabinet can be set to inhibit LVD operation for adjustment, maintenance, and
repair purposes. A local indicator illuminates when the low voltage disconnect circuit has been inhibited. LVD operation is
not inhibited in any other Distribution Cabinets in the power system.
Restrictions
Not available for List 2 bays (no interbay busbar landings available).
Cannot be ordered with List 1 if it is to be used with a List 2.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 11 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Ordering Notes
1) Order one (1) Distribution Bus Module for each List 21 per 'Distribution Bus Modules'.
2) Order fuses and/or circuit breakers, as required, per 'Distribution Devices' under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, as required, per 'Wiring Components' under ACCESSORY DESCRIPTIONS.

List 22: Two-Row Distribution Cabinet


Features
♦ Accepts up to two (2) Distribution Bus Module.
♦ Rated for up to 1,000 amperes of distribution.
♦ Available for use in List 1, List 2, and List 5 bays.
♦ See also the description of the Quad Shunt circuit card under List 21
features.
♦ See also the description of the Low Voltage Disconnect circuit card
under List 21 features.
Ordering Notes
1) Order up to two (2) Distribution Bus Modules for each List 22 per
'Distribution Bus Modules'.
2) Order fuses and/or circuit breakers, as required, per 'Distribution
Devices' under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, as required, per 'Wiring
Components' under ACCESSORY DESCRIPTIONS.

List 23: Three-Row Distribution Cabinet


Features
♦ Accepts up to three (3) Distribution Bus Modules.
♦ Rated for up to 1500 amperes of distribution.
♦ Available for use in List 1, List 2, and List 5 bays.
♦ See also the description of the Quad Shunt circuit card under List 21 features.
♦ See also the description of the Low Voltage Disconnect circuit card under List
21 features.
Ordering Notes
1) Order up to three (3) Distribution Bus Modules for each List 23 per
'Distribution Bus Modules'.
2) Order fuses and/or circuit breakers, as required, per 'Distribution Devices'
under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, as required, per 'Wiring Components'
under ACCESSORY DESCRIPTIONS.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 12 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 24: Four-Row Distribution Cabinet
Features
♦ Accepts up to four (4) Distribution Bus Modules.
♦ Rated for up to 2000 amperes of distribution.
♦ Available for use in List 1, List 2, and List 5 bays.
♦ See also the description of the Quad Shunt circuit card under List 21
features.
♦ See also the description of the Low Voltage Disconnect circuit card under
List 21 features.
Ordering Notes
1) Order up to four (4) Distribution Bus Modules for each List 24 per
'Distribution Bus Modules'.
2) Order fuses and/or circuit breakers, as required, per 'Distribution Devices'
under ACCESSORY DESCRIPTIONS.
3) Order input and load distribution lugs, as required, per 'Wiring Components'
under ACCESSORY DESCRIPTIONS.

List 29: Top Shield for Distribution Cabinet


Features
♦ Plastic shield covers all wiring access openings in top of Distribution
Cabinet. Individual cutouts can be removed for wiring as required for
specific installation.
Ordering Notes
1) Where closed top cover is required, order one (1) List 29 for each List
21, 22, 23, and 24 ordered.

List 31: Rectifier Module Mounting Shelf Interface Components


Features
♦ Provides components to add one (1) to six (6) Rectifier Module Mounting Shelf(s) (Spec. No. 588705000) to a Main or
Supplemental Bay.
Restrictions
Includes 'Rectifier Module Mounting Shelf-to-Power System/Distribution Cabinet'
interconnect components only.
Rear access required for AC input connections when List 45 or 46 are not ordered.
Maximum of six (6) List 31.
Only two List 31 rectifier shelves can be added to a system in the field for
expansion.
Ordering Notes
1) Specify how many Rectifier Module Mounting Shelf(s) are to be installed in
the bay so correct busbars can be provided, and if space between
Distribution Cabinet and 1st Rectifier Module Mounting Shelf is either 0U or
2U. Provides busbars and
2) Order Rectifier Module Mounting Shelf(s) as required per PD588705000. interconnect hardware
(Single-phase and three-phase input options are available.) only, order shelf(s) per
3) Order Rectifier Modules as required per P/N 1R483200e or 1R483200. PD588705000.
4) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting
position in the system.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 13 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 45: Top Mount AC Input Termination Panel
for Single Phase Input
Features
♦ Consists of a pre-wired, top-mount AC input termination panel. Provides input terminations for up to
six (6) List 31 Rectifier Module Mounting Shelves (36 individual feeds). Panel accepts (12) 3/4"
conduit fittings (six per side).
♦ 4U high termination panel mounts on top of Distribution Cabinet, and can extend above relay rack.
Distribution Cabinet can be mounted so that List 45 uses 0U, 1U, 3U, or 4U of rack space.
Restrictions
For use with List 1 of 588705000 only (single-phase input). NOT FOR USE WITH LIST 11 OF 588705000
(SHELF W/ AC INPUT LINE CORDS).
Factory installed only.
For initial installation only. Initial rectifier shelves are factory wired to List 45. If rectifier shelves are
added to the system, AC inputs MUST be wired directly to the shelves.
CANNOT be installed where List 45 uses exactly 2U of rack space.
Ordering Notes
1) For top-mount AC input termination, order one (1) List 45 per Bay.
2) Specify 0U, 1U, 3U, or 4U of rack space List 45 is to occupy. (List 45 can extend above top of relay rack.)

List 46: Top Mount AC Input Termination Panel


for Three Phase Input
Features
♦ Consists of a pre-wired, top-mount AC input termination panel. Provides two (2) three-phase input
circuits for each of up to six (6) List 31 Rectifier Module Mounting Shelves (12 three-phase feeds
total). Panel accepts (12) 3/4" conduit fittings (six per side).
♦ 4U high termination panel mounts on top of Distribution Cabinet, and can extend above relay rack.
Distribution Cabinet can be mounted so that List 46 uses 0U, 1U, 3U, or 4U of rack space.
Restrictions
For use with List 3 of 588705000 only (three-phase input).
Factory installed only.
For initial installation only. Initial rectifier shelves are factory wired to List 46. If rectifier shelves are
added to the system, AC inputs MUST be wired directly to the shelves.
CANNOT be installed where List 46 uses exactly 2U of rack space.
Ordering Notes
1) For top-mount AC input termination, order one (1) List 46 per Bay.
2) Specify 0U, 1U, 3U, or 4U of rack space List 46 is to occupy. (List 46 can extend above top of relay rack.)

List 62: Optional 20A Converter Module


Features
♦ Provides Model MHSB20A, Spec. No. 486800128, -48V to +24V (20 ampere) Converter Module.
♦ For more information, refer to System Application Guide SAG588249700 in the Power System User
Manual.
Restrictions
For use with List 63 and 64 only.
Ordering Notes
1) Order as required.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 14 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 63: Optional 160A Converter Shelf (Initial Shelf)
Features
♦ Provides (1) Model MHSB160CAB, Spec. No. 588249700, -48V to +24V DC-DC 160A
Converter Mounting Shelf. Includes input busbars and output cabling. Includes
alarm cabling for List 63 and List 64.
♦ Holds up to eight (8) List 62 Converter Modules.
♦ For more information, refer to SAG588249700 in the Power System User Manual.
Restrictions
Maximum of one (1) List 63 per Power System. For more capacity, order (1) List 64.
Must be installed in Main Bay only.
Must be used in conjunction with a dual voltage bus distribution panel assembly (List JA, JB, JC, JD, KA, LB, or LC).
Must be located directly beneath bottom (last) PCU Mounting Shelf.
List 92 is not available when List 63 is ordered.
Bay will accommodate a maximum total of (4) List 63, List 64 and List 93.
Ordering Notes
1) For initial Converter Mounting Shelf, order (1) List 63.
2) For an additional Converter Mounting Shelf, order (1) List 64.
3) Order up to eight (8) converter modules (List 62) for List 63.

List 64: Optional 160A Converter Shelf (Expansion Shelf)


Features
♦ Provides (1) Model MHSB160CAB, Spec. No. 588249700, -48V to +24V DC-DC
160A Converter Mounting Shelf. Includes input busbars and output cabling to a
dual voltage bus distribution assembly.
♦ Holds up to eight (8) List 62 Converter Modules.
♦ For more information, refer to SAG588249700 in the Power System User Manual.
Restrictions
Maximum of one (1) List 64 per Power System.
Must be installed in Main Bay only.
Must be used in conjunction with a List 63 and a dual voltage bus distribution panel assembly (List JA, JB, JC, JD, KA, LB, or
LC).
Must be located directly beneath List 63.
List 92 is not available when List 64 is ordered.
Bay will accommodate a maximum total of (4) List 63, List 64 and List 93.
Ordering Notes
1) For initial Converter Mounting Shelf, order (1) List 63.
2) For an additional Converter Mounting Shelf, order (1) List 64.
3) Order up to eight (8) converter modules (List 62) for List 64.

List 71: Optional Audible Alarm and Alarm Termination Circuit Card
Features
♦ Provides an Audible Alarm and Alarm Termination circuit card (524734).
This circuit card is interconnected to the MCA. The circuit card provides
spring-clamp type terminals for connection of customer wiring to the
MCA's external alarm circuits in lieu of the standard alarm cable.
♦ Includes a local audible alarm-sounding device connected to the external
audible alarm contacts. The audible alarm can be silenced locally.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 15 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Restrictions
Must be located in Main Bay (List 1) only.
Audible alarm is inoperative when used with List 12 or 13 MCA (no audible alarm relay contacts available).
Ordering Notes
1) Order per site requirements.

List 72: MCA Interface Modem Option


Features
♦ Provides a 2400 bits/s Modem circuit card, Spec. No. 486781300, plus associated hardware.
♦ This option plugs into the MCA.
♦ Allows MCA interface via a modem port.
♦ See also WinLink Software (List 73).
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WinLink Software (List 73) via modem.

List 73: MCA Interface WinLink Software


Features
♦ Provides Spec. No. 041182000 (WinLink Software).
♦ WinLink Software provides the user the ability to remotely communicate with multiple Power Systems equipped with an
MCA. Only one Power System (MCA) can be remotely connected at a time. This allows a user to remotely monitor,
control, and adjust the Power System via WinLink. Remote communications can be done over dial-up phone lines when
the Power System is equipped with the List 72 Modem or List 74 RS-232/Modem MCA Interface Option. Remote
communications can be done via an RS-232 connection when the Power System is equipped with the List 74
RS-232/Modem MCA Interface Option. Remote communications can be done via a TCP/IP connection when the Power
System is equipped with the Ethernet MCA Interface Option (List 75, 76, 77, or 78).
♦ With WinLink Software, most tasks accomplished via the Power System's MCA local interface pad can be done remotely.
This includes alarm monitoring, voltage/current monitoring, and adjustment of alarm and control circuits.
♦ Runs under Windows 98, ME, NT 4.0, 2000, or XP.
♦ See also Modem (List 72), RS-232/Modem (List 74), or Ethernet (List 75, 76, 77, or 78) MCA Interface Options.
Restrictions
Not required for Lists 75, 76, 77, or 78.
Ordering Notes
1) Only one List 73 required for each computer installation.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 16 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 74: MCA Interface Combination Modem/RS-232 Option
Features
♦ Provides a Modem circuit card, an RS-232 circuit card, and associated mounting
hardware.
♦ This option plugs into the MCA.
♦ Allows MCA interface via an RS-232 and Modem port.
♦ See also WinLink Software (List 73).
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WinLink Software via modem or RS-232.

List 75: MCA Interface Ethernet Option:


Modbus® TCP + Web Interface
Features
♦ Provides an Ethernet circuit card (P/N 524541) and associated mounting hardware.
♦ Ethernet circuit card provides a Modbus® TCP Interface and a Web Interface.
♦ This option plugs into the MCA.
♦ Allows MCA interface via an Ethernet port.
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
The Ethernet card requires an MCA with firmware version 5.2.0 or later.
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WEB Interface.
2) Order optional Front Access Ethernet Connector Kit P/N 525110, as required. This includes an RJ45 connector, mounting
bracket, and jumper that mounts in the cutout provided on the front of the MCA Panel. CANNOT be used when System
Load Shunt Test Point Kit is required.

List 76: MCA Interface Ethernet Option:


Modbus® TCP + Web Interface + SNMP
Features
♦ Provides an Ethernet circuit card (P/N 524541) and associated mounting hardware.
♦ Ethernet circuit card provides a Modbus® TCP Interface, a Web Interface, and SNMP.
♦ This option plugs into the MCA.
♦ Allows MCA interface via an Ethernet port.
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
The Ethernet card requires an MCA with firmware version 5.2.0 or later.
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WEB Interface.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 17 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
2) Order optional Front Access Ethernet Connector Kit P/N 525110, as required. This includes an RJ45 connector, mounting
bracket, and jumper that mounts in the cutout provided on the front of the MCA Panel. CANNOT be used when System
Load Shunt Test Point Kit is required.

List 77: MCA Interface Ethernet Option:


Modbus® TCP + Web Interface + Battery Monitoring
Features
♦ Provides an Ethernet circuit card (P/N 524541) and associated mounting hardware.
♦ Ethernet circuit card provides a Modbus® TCP Interface, a Web Interface, and Battery Monitoring.
♦ This option plugs into the MCA.
♦ Allows MCA interface via an Ethernet port.
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
The Ethernet card requires an MCA with firmware version 5.2.0 or later.
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WEB Interface.
2) Order optional Front Access Ethernet Connector Kit P/N 525110, as required. This includes an RJ45 connector, mounting
bracket, and jumper that mounts in the cutout provided on the front of the MCA Panel. CANNOT be used when System
Load Shunt Test Point Kit is required.

List 78: MCA Interface Ethernet Option:


Modbus® TCP + Web Interface + SNMP + Battery Monitoring
Features
♦ Provides an Ethernet circuit card (P/N 524541) and associated mounting hardware.
♦ Ethernet circuit card provides a Modbus® TCP Interface, a Web Interface, Battery Monitoring, and
SNMP.
♦ This option plugs into the MCA.
♦ Allows MCA interface via an Ethernet port.
Restrictions
Must be located in Main Bay (List 1) only.
Only one interface option (List 72, 74, 75, 76, 77, 78 or RS-485) can be installed.
Do not order this option when the power system is equipped with List 80 (LMS1000 Monitoring System).
The Ethernet card requires an MCA with firmware version 5.2.0 or later.
Ordering Notes
1) Order this option for each Power System (MCA) to be accessed via WEB Interface.
2) Order optional Front Access Ethernet Connector Kit P/N 525110, as required. This includes an RJ45 connector, mounting
bracket, and jumper that mounts in the cutout provided on the front of the MCA Panel. CANNOT be used when System
Load Shunt Test Point Kit is required.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 18 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 79: Capacitor Precharge Assembly
Features
♦ Precharges load capacitors through the terminals of a GJ/218-type circuit breaker or TPH type
fuseholder.
♦ Includes 3 ft. long clip leads.
♦ Includes mounting bracket.
Ordering Notes
1) Order per site requirements.

List 80: LMS1000 Monitoring System


Features
♦ Provides a Model LMS1000, Spec. No. 586505500, Master Node cabinet and CPU circuit card. The
LMS1000 is a programmable monitoring, controlling, and data
acquisition system designed for use in telecommunications power
sites. Refer to SAG586505500 for further information.
♦ Also supplied is an RS-485 Communications Interface Circuit Card
Assembly, Spec. No. 486781400. This assembly plugs onto the MCA
circuit card, and allows the MCA to interface with the LMS1000, via an
RS-485 port.
♦ Also provided is an interface cable that interconnects the MCA and the
LMS1000.
Restrictions
Must be located in Main Bay only.
A maximum of one (1) List 80 can be used per power system, and must be mounted in a 2U space between the distribution
enclosure and the top Rectifier Module Mounting Shelf in the Main Bay.
Do not order List 72, 74, 75, 76, 77 or 78 when List 80 is ordered.
Ordering Notes
1) Order per site requirements.
2) Order LMS1000 options as required per SAG586505500 (example; input/output cards to monitor points external to the
power system).

List 92: Battery Stand Interface Components


Features
♦ Complete battery stand platform, including monitoring options. For more
information, refer to SAG588820000.
♦ When List 92 is ordered as part of the system, the power system can be mounted in a
relay rack on top of the battery stand.
Restrictions
Cannot be ordered with Lists RA, RB, RC, RD, RE, 63, 64, or 93.
Power system must be mounted in one of these relay racks: 543151, 543152, 543153,
543154, 543155, 543156, and 543157.
Ordering Notes
1) Order per site requirements.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 19 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 93: Battery Tray, Pre-Cabled
Features
♦ Provides one battery tray that mounts four (4) 12V front terminal VLRA
batteries. Batteries are configured as one (1) 48V string. Battery cabling is
factory-connected to Power System main bus.
♦ Accepts various Valve Regulated Lead Acid (VLRA) batteries. See Ordering
Notes below.
♦ Tray dimensions are 21.3” wide X 22.4” deep. See 'List 93 (Battery Tray)' under
PHYSICAL SIZE INFORMATION for a typical battery tray arrangement.
♦ Trays can be ordered with or without Battery Disconnect circuit breakers.
When circuit breakers are ordered, one is provided in the –48V lead of each
battery string (1 circuit breaker per tray).
Restrictions
Cannot be used with Lists RA, RB, RC, RD, RE, or 92.
Maximum number of List 93’s per bay is four (4).
A single List 93 must mount at bottom of bay. Multiple List 93’s must mount starting at bottom of bay and working upward.
Not a stand-alone battery system. Must be used as part of a power system that includes List 1, List 2 or List 5 with List 21, 22,
23, or 24 and List 31.
Ordering Notes
1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions above.
2) Order batteries separately. Table A lists batteries recommended for use with List 93.
3) Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for battery clearance. See
Table A.
4) Specify the batteries you intend to use with each List 93 ordered. Lugs for battery connections vary according to the
batteries to be installed. Battery cables will be lugged as shown in Table B. Table B is provided for reference only.
5) Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be furnished with or
without Battery Disconnect circuit breakers as specified for the first tray ordered.
6) An assembly for connection of all List 93’s is automatically added to the order. Part number depends on system
configuration.
7) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from
Table C. For double-pole circuit breakers, also order an optional circuit breaker guard
(P/N 548014) per circuit breaker if desired.
8) If ordering List 93 with circuit breakers, specify breaker mounting on left side or right
side of tray.
9) If optional front battery covers are desired, order per Optional Front Battery Covers in
the ACCESSORY DESCRIPTIONS section.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 20 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Vertiv Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
C&D TEL12-105F 514368 100 4.94 x 22.51 x 9.00 6U 84.9
C&D TEL12-160F 140456 157 4.95 x 22.01 x 11.14 7U 115
C&D TEL12-180F -- 181 4.95 x 22.01 x 12.60 8U 131
Deka 12AVR-150ET 122018 150 4.90 X 22.00 X 11.75 8u 115
Deka 12AVR-170ET 541381 170 4.91 x 22.16 x 12.60 8U 120
Deka HR5500ET -- 152 4.90 x 22.00 x 11.75 8U 120
Douglas DSN12-110F -- 110 4.92 x 22.05 x 8.94 6U 86.4
Douglas DSN12-170F 127691 171 4.92 x 22.05 x 12.60 8U 129.6
Douglas DST12-170F -- 170 4.96 x 21.97 x12.64 8U 132
Enersys 12TX105F -- 100 4.90 x 22.10 x 9.30 6U 105.8
Enersys 12V100F -- 100 4.9 x 22.00 x 9.00 6U 104.7
Enersys 12V155FS 122010 155 4.9 x 22.10 x 11.10 7U 125.6
Enersys 12V170F -- 170 4.90 x 22.10 x 12.40 8U 147.7
Enersys 12VF105F -- 107 4.90 x 22.10 x 9.30 6U 101.4
Enersys 12VX100F -- 100 4.9 x 22.00 x 9.00 6U 104.7
Enersys SBS 170F -- 170 4.90 x 22.10 x 11.10 7U 115.7
Enersys SBS 190F -- 190 4.90 x 22.10 x 12.40 8U 132.3
Fiamm 12FAT100 -- 100 4.96 x 21.97 x 9.06 6U 90.39
Fiamm 12FAT125 -- 125 4.96 x 21.97 x 10.67 7U 110.23
Fiamm 12FAT155 -- 155 4.96 x 21.97 x12.64 8U 132.28
Fiamm 12UMTx100FT -- 100 4.96 x 21.97 x 9.06 6U 83.6
Fiamm 12UMTX110FT -- 110 4.96 x 21.97 x 9.06 6U 90.36
Fiamm 12UMTX140FT -- 140 4.96 x 21.97 x 10.67 7U 110
Fiamm 12UMTX155FT -- 155 4.96 x 21.97 x12.64 8U 129.8
Fiamm 12UMTX170FT -- 170 4.96 x 21.97 x 12.64 8U 132
Fiamm 12UMTX180FT -- 180 4.96 x 21.97 x12.64 8U 134
GNB M12V125FT 123617 125 4.88 x 22.01 x 11.14 7U 104.7
GNB M12V155FT 112795 155 4.88 x 22.01 x 11.14 7U 118.4
GNB M12V180FT -- 180 4.88 x 22.01 x 12.5 8U 133
Northstar NSB110FT -- 110 4.92 X 22.05 X 8.94 6U 91.3
Northstar NSB12-600FT -- -- 4.90 X 22.10 X 12.60 8U 131.2
Northstar NSB155FT -- 148 4.92 X 22.05 X 11.14 7U 131.2
127002,
Northstar NSB170FT 168 4.92 x 22.05 x 12.60 8U 131
126111
* See Battery Manufacturer Information located at the end of this document.

Table A

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 21 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Battery Lug Kit Part Numbers


(Kit provides two lugs for one tray.)
Battery Ordered Without Ordered With Circuit Breaker Ordered With Circuit Breaker
Specified Circuit Breaker 125A or Higher 100A or Lower
C&D TEL12-105F 528235 528235 528234
C&D TEL12-160F 528235 528235 528234
C&D TEL12-180F 528235 528235 528234
Deka 12AVR-150ET 528235 528235 528234
Deka 12AVR-170ET 528235 528235 528234
Deka HR5500ET 528235 528235 528234
Douglas DSN12-110F 528235 528235 528234
Douglas DSN12-170F 528235 528235 528234
Douglas DST12-170F 528235 528235 528234
Enersys 12TX105F 528235 528235 528234
Enersys 12V100F 528235 528235 528234
Enersys 12V155FS 528235 528235 528234
Enersys 12V170F 528235 528235 528234
Enersys 12VF105F 528235 528235 528234
Enersys 12VX100F 528235 528235 528234
Enersys SBS 170F 528235 528235 528234
Enersys SBS 190F 528235 528235 528234
Fiamm 12FAT 100 528235 528235 528234
Fiamm 12FAT125 528235 528235 528234
Fiamm 12FAT155 528235 528235 528234
Fiamm 12UMTX 100FT 528235 528235 528234
Fiamm 12UMTX 110FT 528235 528235 528234
Fiamm 12UMTX 140FT 528235 528235 528234
Fiamm 12UMTX 155FT 528235 528235 528234
Fiamm 12UMTX170FT 528235 528235 528234
Fiamm 12UMTX180FT 528235 528235 528234
GNB M12V125FT 528235 528235 528234
GNB M12V155FT 528235 528235 528234
GNB M12V180FT 528235 528235 528234
Northstar NSB110FT 528235 528235 528234
Northstar NSB12-600FT 528235 528235 528234
Northstar NSB155FT 528235 528235 528234
Northstar NSB170FT 528235 528235 528234
Table B

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 22 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Ampere Part Number


Rating Electrical/Mechanical Trip1 (Black Handle) Electrical Trip2 (White Handle)
50 256694300 256694400
60 256694700 256694800
70 256695100 256695200
75 256695500 256695600
100 256695900 256696000
125 100765 100762
150 100763 100764
200 121810 121809
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
Table C

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 23 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Distribution Panels
List AA: Distribution Bus Module (P/N 509840)
(24) Fuse/Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (24) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 48 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
GROUND 3/4"
BUSBAR

LOAD RETURN
5/8" CONNECTIONS

LOAD
5/8" CONNECTIONS

LOADS
1/4-20 THREADED HOLE, 48 PLACES
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 24 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AB: Distribution Bus Module (P/N 428316100)
(3) GJ/218 Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
Restrictions
Can be installed in bus positions A-C (row 1-3) of a 1-, 2-, 3-, or 4-bus row cabinet. Cannot be installed in bus position D (row
4) of a 4-bus row cabinet. See also List AC for similar application in bus position D (row 4).
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

LOAD 3/8-16 CAPTIVE NUT, 12 PLACES


CONNECTIONS (CUSTOMER MUST SUPPLY LUG
LOAD RETURN
CONNECTIONS BOLTS AND ADDITIONAL
GROUND HARDWARE. BOLT LENGTH: 1-1/4")
BUSBAR 1.5" 1"

1"

1"

1"

LOADS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 25 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AC: Distribution Bus Module (P/N 507198)
(3) GJ/218 Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
Restrictions
For use in a 4-bus row cabinet only. Must be installed in bus position D (row 4). See also List AB for similar application in bus
positions A-C (rows 1-3).
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

LOAD 3/8-16 CAPTIVE NUT, 12 PLACES


CONNECTIONS LOAD RETURN (CUSTOMER MUST SUPPLY LUG
CONNECTIONS BOLTS AND ADDITIONAL
GROUND HARDWARE. BOLT LENGTH: 1-1/4")
BUSBAR 1.5" 1"

1"

1"

1"

LOADS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 26 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AD: Distribution Bus Module (P/N 509565)
(8) GJ/218 Circuit Breaker System Positions (Upper Two Rows)
Features
♦ Single Voltage Distribution (-48V).
♦ 1,000A Maximum Capacity (500A per side).
♦ (8) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
Restrictions
Occupies two distribution rows.
For use in a 4-bus row cabinet only. Must be installed in bus positions C and D (rows 3 and 4). See also List AE for similar
application in bus positions A and B (rows 1 and 3) or B and C (rows 2 and 3).
Panel is designed to mount circuit breakers in the following possible combinations per side:
(4) 100A to 250A
(2) 100A to 250A and (1) 300A or 400A
(2) 300A or 400A
(1) 600A and (1) 100A to 250A
Unless otherwise specified circuit breakers are divided between the two sides, and are mounted from left to right, starting
with the highest capacity and working to the lowest capacity on each side.
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3) Order adapter Busbar 559643 as required, per Accessory Descriptions.

3/8-16 CAPTIVE NUT, 32 PLACES (CUSTOMER MUST PROVIDE LUG


BOLTS AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

LOAD CONNECTIONS

1-7/8"

GROUND
BUSBAR

1"
LOAD RETURN
CONNECTIONS

1"
1"

LOADS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 27 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AE: Distribution Bus Module (P/N 509648)
(8) GJ/218 Circuit Breaker System Positions (Lower Two Rows)
Features
♦ Single Voltage Distribution (-48V).
♦ 1,000A Maximum Capacity (500A per side).
♦ (8) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
Restrictions
Occupies two distribution rows.
For use in a 2-, 3-, or 4-bus row cabinet. Must be installed in bus positions A and B (rows 1 and 2), or B and C (rows 2 and 3).
See also List AD for similar application in bus positions C and D (rows 3 and 4).
Panel is designed to mount circuit breakers in the following possible combinations per side:
(4) 100A to 250A
(2) 100A to 250A and (1) 300A or 400A
(2) 300A or 400A
(1) 600A and (1) 100A to 250A
Unless otherwise specified circuit breakers are divided between the two sides, and are mounted from left to right, starting
with the highest capacity and working to the lowest capacity on each side.
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3) Order adapter Busbar 559643 as required, per Accessory Descriptions.

3/8-16 CAPTIVE NUT, 32 PLACES (CUSTOMER MUST PROVIDE LUG


BOLTS AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

LOAD CONNECTIONS

1-7/8"
GROUND
BUSBAR

1"
LOAD RETURN
CONNECTIONS

1"
1"

LOADS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 28 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AG: Distribution Bus Module (P/N 514010)
(2) TPH Fuse System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (2) Distribution Fuse Mounting Positions
(70 to 600A TPH-Type).
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AH for up to two (2) List AG.
2) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 3/8-16 CAPTIVE NUT,


6 PLACES (CUSTOMER 6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4") BOLT LENGTH: 1-1/4")

2-1/8" 2-1/8" 2-1/8" 2-1/8"

LOAD 1" LOAD


CONNECTIONS CONNECTIONS

LOAD LOAD

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 29 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AH: Distribution Bus Module Ground Bar Assembly (P/N 500676)
for Use with Up to (2) List AG, AJ, CG, or CJ;
or (1) List AP
Features
♦ Single Voltage Distribution (-48V).
♦ 1000A Maximum Capacity.
♦ Groundbar Assembly for Use with Up to Two (2) List AG, AJ, CG, or CJ; or one (1) List AP if internal load returns are
required.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) To terminate load returns within the distribution cabinet,
order one (1) List AH for up to two (2) List AG, AJ, CG, or CJ;
or one (1) List AH for each (1) List AP.

3/8-16 CAPTIVE NUT, 24 PLACES


(CUSTOMER MUST SUPPLY
GROUND LUG BOLTS AND ADDITIONAL
BUSBAR HARDWARE. BOLT
2" 2" 2" 2" 2" LENGTH: 1-1/4")
1"
LOAD RETURN
CONNECTIONS

1"

2" 2" 2" 2" 2"

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 30 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AJ: Distribution Bus Module (P/N 520819)
(2) TPH Fuse System Positions with Load Metering Shunts
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (2) Distribution Fuse Mounting Positions
(70 to 600A TPH-Type).
♦ (1) Load Shunt (800A, 50mV) per load fuse is provided. Extended shunt leads are 22 AWG stranded wire, approximately
7-10 ft. long from exit point at bottom of Distribution Cabinet. Each shunt lead is equipped with a 49.9 ohm current
limiting resistor. If a List 80 is ordered, shunt leads in the Main Bay are factory-connected to the LMS1000 unless
otherwise specified.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AH for up to two (2) List AJ.
2) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 3/8-16 CAPTIVE NUT,


6 PLACES (CUSTOMER 6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4") BOLT LENGTH: 1-1/4")

2-1/8" 2-1/8" 2-1/8" 2-1/8"

LOAD 1" LOAD


CONNECTIONS CONNECTIONS

LOAD

LOAD

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 31 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AK: Distribution Bus Module (P/N 520805)
(24) Fuse/Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (24) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
Restrictions
Provides no ground return busbar. Ground return connections must be made outside of Power Distribution Cabinet, or to List
AL.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet. NOTE: Additional restrictions apply if
used in conjunction with a List AL. See List AL for restrictions.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

3/4"

LOAD
5/8" CONNECTIONS

LOADS
1/4-20 THREADED HOLE, 48 PLACES
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 32 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AL: Distribution Bus Module Ground Bar Assembly
for Use with Up to (2) List AK
Features
♦ Groundbar Assembly for Use with Up to Two (2) List AK when Internal Load Returns are Required.
♦ 1000A Maximum Capacity.
Restrictions
Can be installed in a 2- or 3-bus row cabinet (List 22 or 23). Must be installed in top row.
Must be installed in the same bus row as a List AK.
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AL for up to two (2) List AK.

1/4-20 STUD, 48 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

5/8"

5/8"
LOAD RETURN
CONNECTIONS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 33 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AM: Distribution Bus Module (P/N 524632)
(20) Fuse/Circuit Breaker System Positions
(1) 3-Pole Input Disconnect Fuse/Circuit Breaker Position
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (20) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ (1) Input Disconnect Fuse / Circuit Breaker 3-Pole Mounting Position (3 to 100A TPS/TLS-Type Fuse / 1 to 250A Bullet
Nose Type Circuit Breaker). Disconnects all loads in row from system main bus.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 40 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
GROUND
3/4"
BUSBAR

LOAD RETURN
5/8" CONNECTIONS

LOAD
5/8" CONNECTIONS

LOADS
1/4-20 THREADED HOLE, 40 PLACES EMPTY INPUT
(CUSTOMER MUST SUPPLY LUG BOLTS AND MOUNTIG DISCONNECT
ADDITIONAL HARDWARE. BOLT LENGTH: 3/4") POSITION

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 34 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AN: Distribution Bus Module (P/N 541386)
(24) Fuse/Circuit Breaker System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (24) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 101212, as required. Kit provides all hardware required to connect load and ground lugs for
two (2) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 48 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
GROUND 3/4"
BUSBAR

LOAD RETURN
5/8" CONNECTIONS

LOAD
5/8" CONNECTIONS

LOADS
1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 35 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List AP: Distribution Bus Module (P/N 541537)
(4) TPH Fuse System Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (4) Distribution Fuse Mounting Positions
(70 to 400A TPH-Type).
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AH for (1) List AP.
2) Order fuses (up to 400A) as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT,


16 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS
LOAD AND ADDITIONAL HARDWARE.
CONNECTIONS BOLT LENGTH: 1-1/4")

1.87" 1.87" 1.87" 1.87"


1"

LOAD LOAD LOAD LOAD

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 36 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List BA: Distribution Bus Module (P/N 520600)
(12) Fuse/Circuit Breaker System Positions with LVD
(8) Fuse/Circuit Breaker System Positions without LVD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (12) LVD-Controlled Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to
250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ (8) Non-LVD-Controlled Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1
to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ Low Voltage Load Disconnect Contactor
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 40 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
GROUND 3/4"
BUSBAR

LOAD RETURN
5/8" CONNECTIONS

LOAD
5/8" CONNECTIONS

BUS A LOADS BUS B LOADS


(NO LVD) (LVD) LVD
1/4-20 THREADED HOLE, 40 PLACES CONTACTOR
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT
LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 37 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CA: Distribution Bus Module (P/N 509846)
(20) Fuse/Circuit Breaker System Positions w/LVLD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (20) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
Circuit breakers with greater than 100 ampere rating occupy two mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 40 PLACES


(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
GROUND 3/4"
BUSBAR
LOAD RETURN
CONNECTIONS
5/8"
LOAD
5/8" CONNECTIONS

LOADS
LVD
1/4-20 THREADED HOLE, 40 PLACES CONTACTOR
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 38 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CB: Distribution Bus Module (P/N 509904)
(3) GJ/218 Circuit Breaker System Positions w/LVLD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Can be installed in any bus position A-C (row 1-3) of a 1-, 2-, 3-, or 4-bus row cabinet. Cannot be installed in bus position D
(row 4) of a four-bus row cabinet. See also List CD for similar application in bus position D (row 4).
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 12 PLACES


(CUSTOMER MUST SUPPLY
BOLTS AND ADDITIONAL
LOAD LOAD RETURN HARDWARE. BOLT LENGTH: 1-1/4")
GROUND CONNECTIONS CONNECTIONS
BUSBAR 1.5" 1"

1"

1"

1"

LOADS LVD
CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 39 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CD: Distribution Bus Module (P/N 507197)
(3) GJ/218 Circuit Breaker System Positions w/LVLD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (3) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
♦ Low Voltage Load Disconnect Contactor.
Restrictions
For use in a 4-bus row cabinet only. Must be installed in bus position D (row 4).. See also List CB for similar application in bus
positions A-C (rows 1-3).
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 12 PLACES


(CUSTOMER MUST SUPPLY
LOAD BOLTS AND ADDITIONAL
CONNECTIONS LOAD RETURN HARDWARE. BOLT LENGTH: 1-1/4")
CONNECTIONS
GROUND
BUSBAR 1.5" 1"

1"

1"

1"

LOADS LVD
CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 40 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CE: Distribution Bus Module (P/N 509563)
(8) GJ/218 Circuit Breaker System Positions w/LVLD (Upper Two Rows)
Features
♦ Single Voltage Distribution (-48V).
♦ 1,000A Maximum Capacity (500A per side).
♦ (8) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Occupies two distribution rows.
For use in a 4-bus row cabinet only. Must be installed in bus positions C and D (rows 3 and 4). See also List CF for similar
application in bus positions A and B (rows 1 and 2).
Panel is designed to mount circuit breakers in the following possible combinations per side:
(4) 100A to 250A
(2) 100A to 250A and (1) 300A or 400A
(2) 300A or 400A
(1) 600A and (1) 100A to 250A
Unless otherwise specified circuit breakers are divided between the two sides, and are mounted from left to right, starting
with the highest capacity and working to the lowest capacity on each side.
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 32 PLACES(CUSTOMER MUST SUPPLY


BOLTS AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

LOAD CONNECTIONS
UPPER LVD
GROUND 1-7/8" CONTACTOR
BUSBAR

1"
LOAD RETURN
CONNECTIONS
1"
1"

LOADS LOADS LOWER LVD


CONTROLLED BY UPPER CONTROLLED BY LOWER CONTACTOR
LVD CONTACTOR LVD CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 41 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CF: Distribution Bus Module (P/N 509646)
(8) GJ/218 Circuit Breaker System Positions w/LVLD (Lower Two Rows)
Features
♦ Single Voltage Distribution (-48V).
♦ 1,000A Maximum Capacity (500A per side).
♦ (8) Load Distribution Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Occupies two distribution rows.
For use in a 2-, 3-, or 4-bus row cabinet. Must be installed in bus positions A and B (rows 1 and 2), or B and C (rows 2 and 3).
See also List CE for similar application in bus positions C and D (rows 3 and 4).
Panel is designed to mount circuit breakers in the following possible combinations per side:
(4) 100A to 250A
(2) 100A to 250A and (1) 300A or 400A
(2) 300A or 400A
(1) 600A and (1) 100A to 250A
Unless otherwise specified circuit breakers are divided between the two sides, and are mounted from left to right, starting
with the highest capacity and working to the lowest capacity on each side.
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 32 PLACES(CUSTOMER MUST SUPPLY


BOLTS AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

LOAD CONNECTIONS
UPPER LVD
1-7/8" CONTACTOR
GROUND
BUSBAR

1"
LOAD RETURN
CONNECTIONS
1"
1"

LOADS LOADS LOWER LVD


CONTROLLED BY UPPER CONTROLLED BY LOWER CONTACTOR
LVD CONTACTOR LVD CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 42 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CG: Distribution Bus Module (P/N 514037)
(2) TPH Distribution Fuse Positions w/LVLD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (2) Distribution Fuse Mounting Positions
(70 to 600A TPH-Type).
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AH for up to two (2) List CG.
2) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 3/8-16 CAPTIVE NUT,


6 PLACES (CUSTOMER 6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4") BOLT LENGTH: 1-1/4")

2-1/8" 2-1/8" 2-1/8" 2-1/8" LOAD


LOAD CONNECTIONS
CONNECTIONS 1"

LOAD LOAD LVD CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 43 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List CJ: Distribution Bus Module (P/N 520937)
(2) TPH Distribution Fuse Positions with Load Metering Shunts and LVLD
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (2) Distribution Fuse Mounting Positions
(70 to 600A TPH-Type).
♦ (1) Load Shunt (800A, 50mV) per load fuse is provided. Extended shunt leads are 22 AWG stranded wire, approximately
7-10 ft. long from exit point at bottom of Distribution Cabinet. Each shunt lead is equipped with a 49.9 ohm current
limiting resistor. If a List 80 is ordered, shunt leads in the Main Bay are factory-connected to the LMS1000 unless
otherwise specified.
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Does not provide connection for load returns (see Ordering Notes).
Ordering Notes
1) To terminate load returns within the distribution cabinet, order one (1) List AH for up to two (2) List CJ.
2) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
3) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 3/8-16 CAPTIVE NUT,


6 PLACES (CUSTOMER 6 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4") BOLT LENGTH: 1-1/4")

LOAD 2-1/8" 2-1/8" 2-1/8" 2-1/8" LOAD


CONNECTIONS CONNECTIONS
1"

LOAD LVD CONTACTOR


LOAD

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 44 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List EA: Distribution Bus Module (P/N 509852)
(16) Fuse/Circuit Breaker System Positions and (4) Fuse/Circuit Breaker Battery Disconnect Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (16) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ (4) Battery Disconnect Fuse / Circuit Breaker Mounting Positions
(3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose-Type Circuit Breakers).
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A or B (row 1 or 2) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in second row of a 3-bus row cabinet in List 1 if used with List 2.
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Cannot be used in second row of a 3-bus row cabinet in List 2.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 48 PLACES
LOAD RETURN (CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
CONNECTIONS 3/4"
GROUND
BUSBAR
5/8"
LOAD
CONNECTIONS BATTERY
5/8" (LOAD SIDE)
CONNECTIONS

LOADS
1/4-20 THREADED HOLE, 40 PLACES (CUSTOMER BATTERY
MUST SUPPLY LUG BOLTS AND ADDITIONAL DISCONNNECTS
HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 45 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List GB: Distribution Bus Module (P/N 513963)
(8) Fuse/Circuit Breaker System Positions w/LVD and (1) TPH Fuse Battery Disconnect Position
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (8) Load Distribution Fuse / Circuit Breaker Mounting Positions (3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose
Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ (1) Battery Disconnect Fuse Mounting Position (70 to 600A TPH-Type).
♦ Low Voltage Load Disconnect Contactor.
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single TPS/TLS-type fuseholder or Bullet Nose-type circuit breaker position is 2
AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order load distribution fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order battery disconnect fuse as required per Table 4. Order replacement alarm fuse (1/4A) per Table 3.
4) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
5) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.
6) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
3/8-16 CAPTIVE NUT, 6 PLACES (CUSTOMER MUST
1/4-20 STUD, 16 PLACES PROVIDE LUG BOLTS AND ADDITIONAL
CUSTOMER MUST SUPPLY HARDWARE. BOLT LENGTH: 1-14")
ADDITIONAL HARDWARE)
1-3/4" BATTERY (LOAD SIDE)
2-1/2" CONNECTIONS
LOAD RETURN 3/4"
CONNECTIONS 1"
GROUND
BUSBAR
5/8"
LOAD
CONNECTIONS
5/8"

1/4-20 THREADED HOLE,


16 PLACES (CUSTOMER
MUST SUPPLY LUG BOLTS
AND ADDITIONAL
HARDWARE. LOADS BATTERY LVD
BOLT LENGTH: 3/4") DISCONNECT CONTACTOR

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 46 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List JA: Distribution Bus Module (Part No. 524482)
(4) –48V Fuse/Circuit Breaker System Positions and
(16) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (4) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type Fuses
/ 1 to 250A Bullet Nose Type Circuit Breakers).
♦ (16) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND
BUSBAR LOAD RETURN
CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8" (SYSTEM)

+24V LOADS (SUBSYSTEM)


1/4-20 THREADED HOLE, 40 PLACES -48V LOADS
(CUSTOMER MUST SUPPLY LUG BOLTS (SYSTEM)
AND ADDITIONAL HARDWARE. BOLT +24V INPUT
LENGTH: 3/4") (Factory Connection)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 47 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List JB: Distribution Bus Module (Part No. 524496)
(12) –48V Fuse/Circuit Breaker System Positions and
(8) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (12) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
♦ (8) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, GB, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND
BUSBAR LOAD RETURN
CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8"
(SYSTEM)

+24V LOADS -48V LOADS


(SUBSYSTEM) +24V INPUT (SYSTEM)
(Factory
1/4-20 THREADED HOLE, 40 PLACES Connection)
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 48 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List JC: Distribution Bus Module (Part No. 524620)
(14) –48V Fuse/Circuit Breaker System Positions and
(6) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (14) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
♦ (6) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, GB, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND
BUSBAR LOAD RETURN
CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8" (SYSTEM)

+24V LOADS +24V INPUT -48V LOADS


(SUBSYSTEM) (Factory (SYSTEM)
Connection)
1/4-20 THREADED HOLE, 40 PLACES (CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 49 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List JD: Distribution Bus Module (Part No. 524788)
(14) –48V Fuse/Circuit Breaker System Positions and
(8) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (14) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
♦ (8) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, GB, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
+24V SUBSYSTEM -48V SYSTEM
LOAD CONNECTIONS LOAD
CONNECTIONS
LOAD RETURN
CONNECTIONS

+24V LOADS -48V LOADS


(SUBSYSTEM) (SYSTEM)
+24V INPUT
(Factory
Connection)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 50 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List KA: Distribution Bus Module (Part No. 524571)
(4) –48V Fuse/Circuit Breaker System Positions and
(16) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 320A Maximum –48V System bus capacity, 480A Maximum +24V Subsystem bus capacity.
♦ (4) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type Fuses
/ 1 to 250A Bullet Nose Type Circuit Breakers.
♦ (16) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Must be installed in bus position A (row 1) of a 1-, 2-, 3- or 4-bus row cabinet.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 48 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND
BUSBAR LOAD RETURN
CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8"
(SYSTEM)

+24V LOADS (SUBSYSTEM)


-48V LOADS
1/4-20 THREADED HOLE, 40 PLACES (SYSTEM)
(CUSTOMER MUST SUPPLY LUG BOLTS +24V INPUT
AND ADDITIONAL HARDWARE. BOLT (Factory Connection)
LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 51 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List LB: Distribution Bus Module (Part No. 524578)
(8) –48V Fuse/Circuit Breaker System Positions w/LVD and
(8) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (8) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type Fuses
/ 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N 514432).
♦ (8) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
♦ Low Voltage System Load Disconnect Contactor.
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, GB, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 40 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND LOAD RETURN


BUSBAR CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8" (SYSTEM)

+24V LOADS -48V LOADS


(SUBSYSTEM) (SYSTEM) LVD
+24V INPUT CONTACTOR
(Factory
1/4-20 THREADED HOLE, 32 PLACES Connection)
(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 52 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List LC: Distribution Bus Module (Part No. 524583)
(12) –48V Fuse/Circuit Breaker System Positions w/LVD and
(4) +24V Fuse/Circuit Breaker Subsystem Positions
Features
♦ Dual Voltage Distribution (–48V and +24V).
♦ 500A Maximum Total Capacity, 200A Maximum +24V Subsystem Capacity.
♦ (12) Load Distribution Fuse / Circuit Breaker Mounting Positions (–48V System Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers), or accepts GMT Load Distribution Fuse Block Assembly Kit (P/N
514432).
♦ (4) Load Distribution Fuse / Circuit Breaker Mounting Positions (+24V Subsystem Voltage) (3 to 100A TPS/TLS-Type
Fuses / 1 to 250A Bullet Nose Type Circuit Breakers).
♦ Low Voltage System Load Disconnect Contactor.
Restrictions
Limit one dual voltage bus (List JA, JB, JC, JD, KA, LB, LC) per power system.
Must be installed in Main Bay only.
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3- or 4-bus row cabinet. If a distribution bus module is mounted
directly beneath, that module must be a List AA, AE, AK, AM, AN, BA, CA, CF, EA, GB, NA, NB, RA or RB.
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order load lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position per Table 10 or
12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.
1/4-20 STUD, 40 PLACES
(CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
3/4"

GROUND LOAD RETURN


BUSBAR CONNECTIONS
5/8"
+24V LOAD
CONNECTIONS -48V LOAD
(SUBSYSTEM) CONNECTIONS
5/8" (SYSTEM)

+24V -48V LOADS


LOADS +24V INPUT (SYSTEM) LVD
(SUB- CONTACTOR
(Factory
SYSTEM) Connection)

1/4-20 THREADED HOLE, 32 PLACES


(CUSTOMER MUST SUPPLY LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 53 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List NA: Distribution Bus Module (P/N 514336)
(20) Fuse/Circuit Breaker Battery Disconnect Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (20) Battery Disconnect Fuse / Circuit Breaker Mounting Positions
(3 to 100A TPS/TLS-Type Fuses / 1 to 250A Bullet Nose-Type Circuit Breakers).
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Unless otherwise specified fuses and/or circuit breakers are mounted from left to right, starting with the highest capacity and
working to the lowest capacity.
125A, 150A, 175A, and 200A circuit breakers occupy two mounting positions. 225A and 250A circuit breakers occupy three
mounting positions.
Caution: A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 gauge.
Ordering Notes
1) Order circuit breakers as required per Table 7 or Table 8.
2) Order fuses as required per Table 9.
Also order one (1) P/N 117201 bullet nose-type fuseholder per fuse ordered.
3) Order battery and return lugs (two hole, 1/4” bolt clearance hole, 5/8” centers) as required for each distribution position
per Table 10 or 12.
4) Order lug hardware kit, P/N 520332, as required. Kit provides all hardware required to connect load and ground lugs for
four (4) positions of a bullet nose-type distribution assembly.

1/4-20 STUD, 40 PLACES


GROUND (CUSTOMER MUST SUPPLY ADDITIONAL HARDWARE)
BUSBAR
3/4"
BATT. RETURN
5/8" CONNECTIONS

BATTERY
5/8" CONNECTIONS

BATTERY DISCONNECTS
1/4-20 THREADED HOLE, 40 PLACES (CUSTOMER MUST
SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 3/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 54 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List NB: Distribution Bus Module (P/N 513809)
(3) GJ/218 Circuit Breaker Battery Disconnect Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (3) Battery Disconnect Circuit Breaker Mounting Positions
(100 to 600A GJ/218-Type). NOTE RESTRICTIONS.
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A or B (row 1 or 2) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Panel is designed to mount circuit breakers in the following possible combinations:
(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A
Ordering Notes
1) Order circuit breakers and associated jumper kits as required per Tables 5 and 6.
2) Order battery lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

BATTERY (LOAD SIDE) 3/8-16 CAPTIVE NUT, 6 PLACES


CONNECTIONS (CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")

1"

1"

1"

BATTERY DISCONNECT

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 55 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List NC: Distribution Bus Module (P/N 514025)
(1) TPH Fuse Battery Disconnect Position
Features
♦ Single Voltage Distribution (-48V).
♦ 500A Maximum Capacity.
♦ (1) Battery Disconnect Fuse Mounting Position
(70 to 600A TPH-Type).
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 12 PLACES (CUSTOMER MUST


SUPPLY LUG BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")

BATTERY BATTERY (LOAD SIDE)


(RETURN SIDE) CONNECTIONS
2-1/8" 2-1/8"
CONNECTIONS 2-1/8" 2-1/8" 1" 1"

GROUND
BUSBAR

BATTERY
DISCONNECT

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 56 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List ND: Distribution Bus Module (P/N 514030)
(2) TPH Fuse Battery Disconnect Positions
Features
♦ Single Voltage Distribution (-48V).
♦ 960A Maximum Capacity.
♦ (2) Battery Disconnect Fuse Mounting Positions
(70 to 600A TPH-Type).
Restrictions
Limit one bus arrangement of this type per Distribution Cabinet.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Ordering Notes
1) Order fuses as required per Table 4. Order replacement alarm fuses (1/4A) per Table 3.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT, 12 PLACES (CUSTOMER MUST


SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")

2-1/8" 2-1/8" 2-1/8" 2-1/8"


BATTERY BATTERY
(LOAD SIDE) 1" (LOAD SIDE)
CONNECTIONS CONNECTIONS

BATTERY DISCONNECTS

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 57 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Battery Disconnect
List RA: 1200A Low Voltage Battery Disconnect (LVBD) Contactor and Control Circuit (P/N 528442)
Features
♦ Provides a battery disconnect contactor, which is mounted in bus position A (row 1) of the Distribution Cabinet.
Restrictions
Limit one bus arrangement of this type per System.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Cannot be used with List 92, 93, RB, RC, RD, or RE.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table 11.

3/8-16 CAPTIVE NUT, 4 PLACES


(CUSTOMER MUST PROVIDE LUG
1-1/4" 1-1/4"
BATTERY BOLTS AND ADDITIONAL HARDWARE.
(LOAD SIDE) BOLT LENGTH: 1-1/4")
CONNECTIONS
1"

CLEARANCE HOLES FOR 3/8 BOLT, 2 PLACES


FOR MOUNTING LUG ON BACK SIDE OF BUSBAR
(CUSTOMER MUST PROVIDE LUG BOLTS, NUTS AND
ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 58 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List RB: 1200A Manual Battery Disconnect Contactor with Local and Remote Alarm (P/N 528443)
Features
♦ Provides a battery disconnect contactor with manual control circuit, which is mounted in bus position A (row 1) of the
Distribution Cabinet.
♦ Also provides one set of Form C relay contacts for connection to customer external alarms.
Restrictions
Limit one bus arrangement of this type per System.
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet.
Cannot be used in a 2-bus row cabinet in List 1 if List 1 is used with List 2. (Can be used in a 2-bus row cabinet in List 1 if List
1 is used alone or with List 5.)
Cannot be used in a 2-bus row cabinet in List 2. (Can be used in a 2 bus-row cabinet in List 5.)
Cannot be used with List 92, 93, RA, RC, RD, or RE.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table 11.

3/8-16 CAPTIVE NUT, 4 PLACES


1-1/4" 1-1/4" (CUSTOMER MUST PROVIDE LUG
BATTERY BOLTS AND ADDITIONAL HARDWARE.
(LOAD SIDE) BOLT LENGTH: 1-1/4")
CONNECTIONS
1"

CLEARANCE HOLES FOR 3/8 BOLT,


2 PLACES FOR MOUNTING LUG ON
BACK SIDE OF BUSBAR (CUSTOMER MANUAL BATTERY
MUST PROVIDE LUG BOLTS, NUTS DISCONNECT SWITCH
AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 59 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List RC: 2000A Manual Battery Disconnect Contactor with Local and Remote Alarm (P/N 528446)
Features
♦ Provides a battery disconnect contactor with manual control circuit.
♦ Mounted on external rear of the Distribution Cabinet; uses no distribution row positions inside cabinet.
♦ Includes (1) extension plate (P/N 514713) for the Distribution Cabinet ground return busbar. Plate provides three pairs of
clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug landing for up to six lugs. See "Electrical
Connection Locations and Dimensions, Input Battery (Connections to Optional Battery Busbar Extension Kit P/N 514713
Installed in Lists 21 through 24 Distribution Cabinets)" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
♦ Also provides one set of Form C relay contacts for connection to customer external alarms.
Restrictions
Must be installed in Main Bay (List 1) only.
Limit one List RC per Distribution Cabinet.
Cannot be used in a 1-bus row cabinet.
Cannot be used if List 1 is used with List 2. (Can be used if List 1 is used alone or with List 5.)
Cannot be used with List 92, 93, RA, RB, RD, or RE.
Rear access required for installation and maintenance.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table 11.

FRONT VIEW

BATTERY
NORM DISC (LOAD SIDE)
BAT DISC
CONNECTIONS
2"

1"
MANUAL BATTERY
DISCONNECT SWITCH

3/8-16 CAPTIVE NUT, 12 PLACES


(CUSTOMER MUST PROVIDE LUG
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")

(1) GROUND RETURN BUSBAR EXTENSION


PLATE PROVIDED. SEE "DIMENSIONS OF
BATTERY BUSBAR EXTENSION KIT, PART
NO. 514713" FOR DIMENSIONS.

REAR VIEW

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 60 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List RD: 2000A Low Voltage/Manual Battery Disconnect
Contactor with Battery Current Monitoring (P/N 528447)
Features
♦ Provides a battery disconnect contactor with Low Voltage and manual control.
♦ Includes shunt for battery charge/discharge current monitoring (25mV @ 2000A).
♦ Mounted on external rear of the Distribution Cabinet; uses no distribution row positions inside cabinet.
♦ Includes (1) extension plate (P/N 514713) for the Distribution Cabinet ground return busbar. Plate provides three pairs of
clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug landing for up to six lugs. See "Electrical
Connection Locations and Dimensions, Input Battery (Connections to Optional Battery Busbar Extension Kit P/N 514713
Installed in Lists 21 through 24 Distribution Cabinets)" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
♦ Also provides one set of Form C relay contacts for connection to customer external alarms.
Restrictions
Must be installed in Main Bay (List 1) only.
Limit one List RD per Distribution Cabinet.
Cannot be used in a 1-bus row cabinet.
Cannot be used if List 1 is used with List 2. (Can be used if List 1 is used alone or with List 5.)
Cannot be used with List 92, 93, RA, RB, RC, or RE.
Rear access required for installation and maintenance.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table 11.

FRONT VIEW

BATTERY
NORM DISC (LOAD SIDE)
BAT DISC
CONNECTIONS 2"

1"
MANUAL BATTERY
DISCONNECT SWITCH

3/8-16 CAPTIVE NUT, 12 PLACES


(CUSTOMER MUST PROVIDE LUG
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")

(1) GROUND RETURN BUSBAR EXTENSION


PLATE PROVIDED. SEE "DIMENSIONS OF
BATTERY BUSBAR EXTENSION KIT, PART
NO. 514713" FOR DIMENSIONS.

REAR VIEW

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 61 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List RE: 2000A Low Voltage Battery Disconnect
Contactor with Battery Current Monitoring (P/N 535064)
Features
♦ Provides a battery disconnect contactor with low voltage control.
♦ Includes shunt for battery charge/discharge current monitoring (25mV @ 2000A).
♦ Mounted on external rear of the Distribution Cabinet; uses no distribution row positions inside cabinet.
♦ Includes (1) extension plate (P/N 514713) for the Distribution Cabinet ground return busbar. Plate provides three pairs of
clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug landing for up to six lugs. See "Electrical
Connection Locations and Dimensions, Input Battery (Connections to Optional Battery Busbar Extension Kit P/N 514713
Installed in Lists 21 through 24 Distribution Cabinets)" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
♦ Also provides one set of Form C relay contacts for connection to customer external alarms.
Restrictions
Same as List RD except does NOT include manual battery disconnect switch.
Must be installed in Main Bay (List 1) only.
Limit one List RE per Distribution Cabinet.
Cannot be used in a 1-bus row cabinet.
Cannot be used if List 1 is used with List 2. (Can be used if List 1 is used alone or with List 5.)
Cannot be used with List 92, 93, RA, RB, RC, or RD.
Rear access required for installation and maintenance.
Ordering Notes
1) Order as required.
2) Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required Table 11.

BATTERY
(LOAD SIDE)
CONNECTIONS 2"

1"

3/8-16 CAPTIVE NUT, 12 PLACES


(CUSTOMER MUST PROVIDE LUG
BOLTS AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")

(1) GROUND RETURN BUSBAR EXTENSION


PLATE PROVIDED. SEE "DIMENSIONS OF
BATTERY BUSBAR EXTENSION KIT, PART
NO. 514713" FOR DIMENSIONS.

REAR VIEW

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 62 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Bulk Feed Panels
List TA: 800A Bulk Feed Distribution Bus Module (P/N 541530)
(Internal Shunt)
Features
♦ Single Voltage Bulk Feed Distribution (-48V).
♦ 800A Maximum Capacity.
♦ Uses the Internal Bus Module Shunt Monitoring Circuit.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) Order as required.
2) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

3/8-16 CAPTIVE NUT,


16 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE.
LOAD RETURN LOAD
GROUND BOLT LENGTH: 1-1/4")
CONNECTIONS CONNECTIONS
BUSBAR
1.88"
1"

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 63 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List TB: 1200A Bulk Feed Distribution Bus Module (P/N 541530),
Bypass Shunt Busbar (P/N 541535), and External Shunt Monitoring Kit (P/N 541134)
(External Shunt)
Features
♦ Single Voltage Bulk Feed Distribution (-48V).
♦ 1200A Maximum Capacity.
♦ Provides a Bypass Shunt Busbar (to bypass internal shunt monitoring) and an External Shunt Monitoring Kit to Monitor a
Remote Shunt.
Restrictions
Can be installed in any bus position A-D (row 1-4) of a 1-, 2-, 3-, or 4-bus row cabinet.
Ordering Notes
1) Order as required.
2) Order load lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position per Table 11.

Also included is P/N 541134 3/8-16 CAPTIVE NUT,


External Shunt Monitoring Kit 16 PLACES (CUSTOMER
MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE.
LOAD RETURN LOAD
GROUND BOLT LENGTH: 1-1/4")
CONNECTIONS CONNECTIONS
BUSBAR
1.88"
1"

Bypass
Shunt
Busbar

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 64 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
ACCESSORY DESCRIPTIONS
Rectifier Modules
Rectifier Module (PCU), High-Efficiency (P/N 1R483200e)
Features
♦ Provides one (1) Model R48-3200e, Spec. No. 1R483200e, 3200 watt / 48 volt rectifier
module.
♦ Refer to UM1R483500e (Rectifier User Instructions) for Rectifier Module specifications.
Restrictions
For use in Spec. No. 588705000 Rectifier Module Mounting Shelve(s).
Ordering Notes
1) Order as required. Each shelf holds up to six (6) Rectifier Modules.

Rectifier Module (PCU) (P/N 1R483200)


Features
♦ Provides one (1) Model R48-3200, Spec. No. 1R483200, 3200 watt / 48 volt rectifier module.
♦ Refer to UM1R483500e (Rectifier User Instructions) for Rectifier Module specifications.
Restrictions
For use in Spec. No. 588705000 Rectifier Module Mounting Shelve(s).
Ordering Notes
1) Order as required. Each shelf holds up to six (6) Rectifier Modules.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 65 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Relay Racks
Features
♦ The system is factory mounted to the relay rack specified when ordered.
♦ All relay racks are 23” standard mounting with 3” deep uprights.
♦ System components may be ordered without a relay rack. When ordered without a relay rack, the system is mounted on
shipping brackets bolted to a shipping skid. The shipping brackets can mount a system up to 20U high.
Ordering Notes
1) Order from relay racks listed in Table 1.

Part Available Mounting


Size Notes
Number Positions (1RU = 1-3/4”)
543151 25.656”H x 24.376”W x 15”D 13RU Welded (Notes 1, 3)
543152 27.406”H x 24.376”W x 15”D 14RU Welded (Notes 1, 3)
543153 36.156”H x 24.376”W x 15”D 19RU Welded (Notes 1, 3)
543154 39.656”H x 24.376”W x 15”D 21RU Welded (Notes 1, 3)
543155 43.156”H x 24.376”W x 15”D 23RU Welded (Notes 1, 3)
543156 51.906”H x 24.376”W x 15”D 28RU Welded
543157 71.156”H x 24.376”W x 15”D 39RU Welded
543161 6’0”H x 24.375”W x 15”D 37RU Welded
543162 7’0”H x 24.375”W x 15”D 45RU Welded
543160 7’0”H x 25.0”W x 15”D 45RU Seismic (Notes 1, 2, and 3)
543163 7’6”H x 24.375”W x 15”D 48RU Welded
543164 8’0””H x 24.375”W x 15”D 51RU Welded
Note 1: Complies with Bellcore Seismic Zone 4 requirements.
Note 2: The DC output cabling may be restricted by the top angle of the relay rack.
Note 3: Seismic (Zone 4) compliant ONLY when system DOES NOT contain any of the following
components: List 93 Battery Tray
Table 1
Available Relay Racks

Ship Loose Option

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 66 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Transition Plates to Mount Relay Rack
on Top of GNB Absolyte IIP Batteries
Features
♦ Transition Plate Kits can be ordered to mount relay rack P/Ns 543151, 543152, 543153, 543154, 543155, 543156, and 543157
on top of GNB Absolyte IIP Battery Stands.
♦ Each kit consists of two transition plates with three hole patterns and hardware (3/8") to mount the plates to the above
listed relay racks. Customer must supply hardware to mount the transition plates to the battery stands.
Restrictions
Used with relay rack P/Ns 543151, 543152, 543153, 543154, 543155, 543156, and 543157only.
Ordering Notes
1) Order P/N 509819 for a Transition Plate Kit to mount relay rack on top of battery with outside dimensions of…
26.75" x 26.38",
35.75" x 26.38", or
42.50" x 26.38".
2) Order P/N 514880 for a Transition Plate Kit to mount relay rack on top of battery with outside dimensions of…
29.00" x 26.38",
35.50" x 26.35", or
40.25" x 26.38".

TRANSITION
PLATES

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 67 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Distribution Devices
GMT Load Distribution Fuse Block Assembly Kit (P/N 514432)
(10) GMT Fuse Positions
Features
♦ Provides ten (10) load distribution fuse positions (1/4A to 15A GMT alarm-type fuses).
♦ Single voltage distribution (-48V).
♦ Mounts in five (5) distribution positions of any “Bullet Nose” Distribution Bus Module.
♦ Screw clamp type load and load return terminals provided.
♦ Includes ten (10) dummy fuses equipped with safety fuse covers.
♦ Includes 35A input fuse and associate alarm fuse.
Restrictions
30A maximum capacity.
Terminal block wire size capacity: 24 to 14 AWG.
Can be used in a List AA, AK, AM, AN, BA, CA, EA, GB, JA, JB, JC, JD, KA, LB, and LC Distribution Bus Module only.
When factory-ordered, installation order of the assembly will be from top to bottom and right to left (see illustration below for
4-row example), unless otherwise specified.
Ordering Notes
1) Order kit P/N 514432 as required. Provides one (1) 10-Position GMT Fuse Distribution Assembly P/N 509128, one (1)
Ground Return Link, and hardware.
2) Order fuses as required per Table 2 (GMT Fuses).
3) Located on the P/N 509128 Assembly is an input fuse. If this fuse opens, an alarm type fuse (fuse position #11) also
opens to activate the system's fuse alarm circuit. For replacement fuses, order as follows:
Input Fuse F12: P/N 110982 (Bussmann TPS-35LB, 35A)
Alarm Fuse F11: P/N 248610200 (Bussmann GMT-1/4, 1/4A)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 68 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

TB1
5th GMT 1st GMT
Fuse Fuse
Assy. Assy.

6th GMT 2nd GMT


F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 Fuse Fuse
Assy. Assy.

7th GMT 3rd GMT


F11 Fuse Fuse
F12
Assy. Assy.

8th GMT 4th GMT


Fuse Fuse
Part No. 509128 Assy. Assy.

Mounting Order for Multiple Part No. 509128


(4 Row Cabinet Shown)
Rear View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 69 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
GMT-Type Load Distribution Fuses
Features
♦ An optional 'GMT Load Distribution Fuse Block Assembly Kit (P/N 514432)' (see previous section) is available for
additional load distribution.
Restrictions
When used for power distribution, load should not exceed 80% of device rating.
Ordering Notes
1) Order fuses as required per Table 2 (GMT Fuses).

Ampere Rating Part Number Fuse Color


18/100 (GMT-A) 248610301 ---
1/4 248610200 VIOLET
1/2 248610300 RED
3/4 248610500 BROWN
1-1/3 248610700 WHITE
2 248610800 ORANGE
3 248610900 BLUE
5 248611000 GREEN
7-1/2 248611300 BLACK-WHITE
10 248611200 RED-WHITE
15 248611500 RED-BLUE
Replacement Safety
102774 ---
Fuse Cover (GMT-Y)
Replacement
248872600 ---
Dummy Fuse
Table 2
GMT Fuses

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 70 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Replacement Alarm, Reference, and Control Fuses
Ordering Notes
1) Order replacement fuses as required per Table 3 (Replaceable Alarm, Reference, and Control Fuses).

Size
Assembly Desig. Function Type Part No.
(Amperes)
Subsystem Voltage Monitoring
F1 (not used - a subsystem is not installed in 1-1/3 Bussmann GMT 248610700
this power system)
F2 System Voltage Monitoring 1-1/3 Bussmann GMT 248610700
F3 Fuse Alarm 1-1/3 Bussmann GMT 248610700
F4 LVD Side A 1-1/3 Bussmann GMT 248610700
Interconnect/
LVD Inhibit F5 LVD Side B 1-1/3 Bussmann GMT 248610700
Circuit Card A1 Converter Fail Alarm Relays (List 71 only)
(P/N 509532) F6 1-1/3 Bussmann GMT 248610700
(not used in this system)
F7 LMS1000 Input 5 Bussmann GMT 248611000
F8 Sense Voltage 1-1/3 Bussmann GMT 248610700
F9 Battery Stand Shunt POD Circuit Card 1-1/3 Bussmann GMT 248610700
Safety Fuse Cover
-- -- -- 248898700
(GMT-X)
Distribution Bus FA Fuse Alarm 1/4 Bussmann GMT 248610200
Module with
TPH Fuse Safety Fuse Cover
Block(s) -- -- -- 248898700
(GMT-X)
TPS/TLS FA Fuse Alarm 18/100 Bussmann GMT-A 248610301
Fuseholders Safety Fuse Cover
(P/N 117201) -- -- -- 248898700
(GMT-X)
GMT
Fuse Block See "GMT Load Distribution Fuse Block Assembly Kit (P/N 514432)" under ACCESSORY DESCRIPTIONS
Assembly for replaceable fuses part numbers.
(P/N 509128)
Table 3
Replaceable Alarm, Reference, and Control Fuses

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 71 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
TPH-Type Fuses
Restrictions
A bus arrangement must be specified that contains a TPH-type fuseholder.
Load should not exceed 80% of device rating.
Ordering Notes
1) Order fuses as required per Table 4 (TPH Fuses).

TPH Fuse

for wire size and


lug selection,
Ampere Rating Part Number
refer to the
following table
70 119437
80 119438
100 119440
150 119581
200 119582
225 119583 Table 14
250 119584
300 119585
400 119586
500 119587
600 119588
Table 4
TPH Fuses

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 72 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
GJ/218-Type Circuit Breakers
Restrictions
A bus arrangement must be specified that contains GJ/218-type circuit breaker positions.
Load should not exceed 80% of device rating.
Refer to Table 5 for required distribution row mounting positions.
Ordering Notes
1) Order circuit breakers as required per Table 5 (GJ/218 Circuit Breakers).
2) Order a jumper kit as required for each circuit breaker per Table 6 (Breaker Jumper Kits).

GJ/218 Circuit Breakers

P/N P/N P/N P/N


Electrical/ Electrical Trip2 Electrical Trip2 Electrical/
for wire size and
Mechanical Trip1 Mechanical Trip1
Ampere Number of lug selection,
without without with with
Rating Positions refer to the
Internal Shunt Internal Shunt Internal Shunt Internal Shunt
following table
(25mV @ full (25mV @ full rated
rated load) 3 load) 3
100 1 256621700 256621300 516184 123580
125 1 256621600 256621400 516187 123631
150 1 256621800 256622400 516185 123632
175 1 256621900 256622500 516186 123633
200 1 256622200 256622600 516188 123634
Table 14
225 1 256622900 256622700 516189 123635
250 1 256623500 256623400 516190 123636
300 2 256625300 103572 -- --
400 2 256626200 256626300 -- --
600 3 256628200 103571 -- --
1, 2
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
3
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of Distribution
Cabinet. Each shunt lead is equipped with a 49.9 ohm current limiting resistor. If a List 80 is ordered, shunt leads in the
Main Bay are factory-connected to the LMS1000 unless otherwise specified. The LMS1000 must be equipped with the
appropriate quantity of analog input cards capable of reading the shunts to have the factory connections made.
Table 5
GJ/218 Circuit Breakers

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 73 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Breaker Jumper Kit P/N Breaker Jumper Kit P/N


Breaker Ampere Distribution Bus (Order 1 of the following kits (Order 1 of the following kits
Rating Module List No. for each circuit breaker W/O an for each circuit breaker WITH
internal shunt.) an internal shunt.)
AB, AC, AD, AE, CB, CD,
100A-250A 503787 513731
CE, CF, NB
AB, CB, NB 500133 --
300A, 400A AC, CD 509060 --
AD, AE, CE, CF 513961 --
AB, CB, NB 500131 --
600A AC, CD 509061 --
AD, AE, CE, CF 513957 --
Table 6
GJ/218 Circuit Breaker Jumper Kits

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 74 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TPS/TLS Fuses
Features
♦ Each circuit breaker (as listed in Table 7 and Table 8) plugs into one, two, or three mounting position(s) on a Distribution
Bus Module containing Bullet Nose-type distribution positions.
♦ A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS-type or Littelfuse TLS-type fuse (as
listed in Table 9). This fuseholder plugs into a single mounting position on a Distribution Bus Module containing Bullet
Nose-type distribution positions. This fuseholder provides a GMT-A alarm type fuse, which operates open to provide an
alarm indication if the associated distribution fuse opens.
Restrictions
Load should not exceed 80% of device rating.
Install distribution devices from left to right, starting with the highest capacity and working to the lowest capacity.
Caution: A circuit breaker with a rating greater than 150 amperes SHALL HAVE an empty mounting position between
it and any other overcurrent protective device.
Ordering Notes
1) Order circuit breakers as required per Table 7 (Toggle Handle Bullet Nose Circuit Breakers) or
Table 8 (Rocker Handle Bullet Nose Circuit Breakers).
2) Order fuses as required per Table 9 (Bullet Nose-Type Fuseholders and TPS/TLS Fuses). For each fuse ordered, also
order one (1) P/N 117201 bullet nose-type fuseholder.
3) When ordering 125A, 150A, 175A, 200A, 225A, or 250A circuit breakers, associated crimp lugs must be ordered from Table
12 (Special Application Crimp Lug / Strap Combination) or see the following part numbers in ACCESSORY
DESCRIPTIONS for available adapter bus bars: 514717, 53449, 514714.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 75 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Part Number for wire size and


Number of Poles
Ampere Electrical/ lug selection,
(and Mounting Electrical Trip1
Rating Mechanical Trip2 refer to the
Positions) (White Handle)
(Black Handle) following table
1 1 102272 101596
3 1 102273 101597
5 1 102274 101598
10 1 102275 101599
15 1 102276 101600
20 1 102277 101601
25 1 102278 101602
30 1 102279 101603
35 1 102280 101604
40 1 102281 101605
45 1 121998 121997
Table 13
50 1 102282 101606
60 1 102283 101607
70 1 102284 101608
75 1 102285 101609
80 1 121996 121995
90 1 138887 138888
100 1 102286 101610
125 2 516991 516838
150 2 516993 516839
175 2 144883 144884
200 2 121831 121832
225 3 144885 144886 Order (1) P/N 514717
adapter kit per 225A
or 250A Bullet Nose
250 3 121835 121836 Type circuit breaker
ordered. Order lugs
per Table 12.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note: See the following part numbers in ACCESSORY DESCRIPTIONS for available adapter bus bars: 514717, 53449,
514714.
Table 7
Toggle Handle Bullet Nose Circuit Breakers

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 76 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Part Number for wire size and


Number of Poles
Ampere Electrical/ lug selection,
(and Mounting Electrical Trip1
Rating Mechanical Trip2 refer to the
Positions) (White Handle)
(Black Handle) following table
1 1 142856 142878
3 1 142857 142879
5 1 142858 142880
10 1 142859 142881
15 1 142861 142882
20 1 142862 142883
25 1 142863 142884
30 1 142864 142885
35 1 142865 142886
40 1 142866 142887
Table 13
45 1 142867 142888
50 1 142868 142889
60 1 142869 142890
70 1 142870 142891
75 1 142871 142892
80 1 142872 142901
100 1 142873 142902
125 2 142874 142903
150 2 142875 142904
200 2 142876 142905
Order (1) P/N 514717
adapter kit per 225A
or 250A Bullet Nose
250 3 142877 142906
Type circuit breaker
ordered. Order lugs
per Table 12.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note: See the following part numbers in ACCESSORY DESCRIPTIONS for available adapter bus bars: 514717, 53449,
514714.
Table 8
Rocker Handle Bullet Nose Circuit Breakers

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 77 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

for wire size and


Ampere Part lug selection,
Bussmann P/N Littelfuse P/N
Rating Number refer to the
following table
3 248230900 TPS-3 TLS003
5 248231000 TPS-5 TLS005
6 248231200 TPS-6 TLS006
10 248231500 TPS-10 TLS010
15 248231800 TPS-15 TLS015
20 248232100 TPS-20 TLS020
25 248232400 TPS-25 TLS025
30 248232700 TPS-30 TLS030 Table 13
40 248233300 TPS-40 TLS040
50 248233900 TPS-50 TLS050
60 248234200 TPS-60 TLS060
70 248234500 TPS-70 TLS070
80 118413 -- TLS080
90 118414 -- TLS090
100 118415 -- TLS100
P/N 117201
Bullet Nose-Type Fuseholder (Includes Fuseholder, 18/100A GMT-A
Alarm Fuse, and GMT-X Safety Fuse Cover)
Table 9
Bullet Nose-Type Fuseholders and TPS/TLS Fuses

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 78 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Rectifier Module Mounting Position Blank Cover Panel (P/N 21140440)
Features
♦ Covers one (1) unused Rectifier Module mounting position.
Ordering Notes
1) Order a Rectifier Module Mounting Position Blank Cover Panel, P/N 21140440, for each empty rectifier module mounting
position in the system.

Battery Charge Temperature Compensation Probe


for Single Probe Digital Compensation (P/Ns 107021 and 106824)
Features
♦ This system can be used with a Battery Charge Temperature Compensation Probe. This probe must be mounted near
the battery to sense battery ambient temperature. The probe connects to and allows the MCA to automatically increase
or decrease the output voltage of the system to maintain battery float current as battery ambient temperature decreases
or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to
temperature is maintained. Two probes are available. P/N 107021 has a 25-foot long cord. P/N 106824 has a 100 foot-
long cord. See "Overall Dimensions, Optional Digital Battery Charge Temperature Compensation Probe (P/N 107021 and
106824)" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
♦ Allows Rectifier Module Battery Charge Temperature Compensation.
♦ Temperature Curve: Refer to Figure 1.
MAX W/T
Adjustable from
Float to 58.0V max.*
Increasing

SLOPE
Adjustable from 0.0 V / °C
to 0.2 V / °C

FLOAT
Voltage

Determines Float Mode


Output Voltage at 25°C.
Adjustable from 46.0V
to 57.0V max.* MIN W/T
Adjustable from
Float to 44V
Decreasing

* Maximum setting is automatically


limited to 1.0 volt less than HVSD setting.

Temperature
Decreasing Increasing

+25°C
(+77°F)

Figure 1
Typical Float Charge Thermal Characteristics
Using Optional Battery Charge Digital Temperature Compensation Probe
(Indicated parameters are user-adjustable via the associated MCA.)

Ordering Notes
1) Order one Battery Charge Temperature Compensation Probe per power system, as required.
2) Order 1 or more extension cable P/N 514153 as required to extend the length of the temperature probe in 25’ increments.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 79 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Battery Charge Temperature Compensation Probe Concentrator
for Multiple Probe Use (TXM)
Battery Temperature Probe Concentrator Kit (P/N 524570)
Features
♦The Battery Temperature Probe Concentrator (TXM) expands battery temperature
monitoring capabilities by providing a means of monitoring up to eight (8) analog
battery temperature probes. The TXM provides a digital output for connection to the
MCA’s battery temperature probe connector. The MCA can be programmed to
compensate for the hottest probe reading, the average temperature of all connected
probes, or the probe connected to the lowest numbered connector. The kit includes 521211
one TXM (P/N 521211) and one 25 ft. interface cable (P/N 521228) for connecting the
TXM to the MCA.
Restrictions
Requires P/N 521262 analog probes. Cannot be used with digital probes (P/N 106824 and
107021).
Ordering Notes
1) Order one Battery Charge Temperature Compensation Probe Concentrator Kit (P/N
524570) per power system, and up to eight P/N 521262 probes, as required. Order
extension cable P/N 514153 as required.
521228
Analog Battery Temperature Probe (P/N 521262)
Features
♦ An analog probe designed to sense internal battery temperature. Mounts on the negative terminal of the battery;
mounting hole clears 5/16” hardware. Includes 15 ft. cable with connector. See "Overall Dimensions, Optional Analog
Battery Temperature Probe (P/N 521262)" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
Ordering Notes
1) See above Ordering Notes.

TXM Extension Cable (P/N 514153)


Features
♦ 25 ft. long cable. Can be used between a P/N 521262 Analog Battery Temperature
Probe and the TXM; or to extend a P/N 521228 interface cable between the TXM and
MCA.
♦ Can also be used to extend Battery Charge Temperature Compensation Digital
Probes (P/Ns 106824 and 107021).
Ordering Notes
514153
1) See above Ordering Notes.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 80 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Adding Additional Shelf in Field Output Busbar Kit
(P/N 529139)
Features
♦ Kit to tie the DC output busbars in a field installed Rectifier Module Mounting Shelf
to the DC busbars in a Spec. No. 582126000 NetSure Power System.
Restrictions
Only two rectifier shelves can be added to a system in the field for expansion.
Ordering Notes
1) Order kit P/N 529139 for each Rectifier Module Mounting Shelf to be added. Shelf Mounting Hardware

Interconnecting Busbars
and Hardware

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 81 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Battery Busbar Kits
Battery Busbar Extension Kit (P/N 514713)
Features
♦ Provides busbar extension plates and mounting hardware for extending battery busbars
through the top of a Distribution Cabinet. Each busbar extension plate provides three pairs
of clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug landing for up
to six lugs per polarity. See "Electrical Connection Locations and Dimensions, Input Battery
(Connections to Optional Battery Busbar Extension Kit P/N 514713 Installed in Lists 21
through 24 Distribution Cabinets)" under PHYSICAL SIZE INFORMATION.
Restrictions
Required for cable connections between 1200A and 2000A per bay when interbay busbars are not provided.
Ordering Notes
1) Order one (1) kit P/N 514713 per bay that busbars are to be extended, as required.

Battery Busbar Extension Kit (P/N 529143)


Features
♦ Provides busbar extension plates, mounting hardware, and rear plastic cover for extending battery busbars through the
top of a Distribution Cabinet. Each busbar extension plate provides six pairs of
clearance holes for 3/8” hardware on 1” centers. Allows back-to-back lug
landing for up to twelve lugs per polarity. See "Electrical Connection Locations
and Dimensions, Input Battery (Connections to Optional Battery Busbar
Extension Kit P/N 529143 Installed in Lists 21 through 24 Distribution Cabinets)"
under PHYSICAL SIZE INFORMATION.
Restrictions
Required for cable connections between 1200A and 2000A per bay when interbay busbars are not provided.
Cannot be used with List 45 and List 46 top mount AC input termination panels due to interference.
Ordering Notes
1) Order one (1) kit P/N 529143 per bay that busbars are to be extended, as required.

Battery Landing Busbar Kit (P/N 541371)


Features
♦ Provides a Battery Landing Busbar Kit that attaches to the distribution cabinet’s battery
busbars and hangs off the back of the cabinet. Six (6) battery landing positions are
provided (per polarity) (1/4-20 x 0.875” studs on 0.625” centers). See "Electrical Connection
Locations and Dimensions, Input Battery (Connections to Optional Battery Landing Busbar
Kit P/N 541371 Installed in Lists 21 through 24 Distribution Cabinets)" under PHYSICAL SIZE
INFORMATION.
Restrictions
FACTORY INSTALLED ONLY
CANNOT be used with List 2.
Ordering Notes
1) Order one (1) kit P/N 541371 per bay, as required.
Lug Adapter Busbars
Lug Adapter Busbar for up to 500 MCM Cable on a two-pole GJ Breaker (P/N 559643)
Features
♦ Provides a busbar that can be used in positions 1-2, 3-4, 5-6 or 7-8 of 582126000 List AD and AE. It lands lugs for up to
500 MCM cable on a two-pole GJ Breaker. It can provide enough surface area to completely cover a lug with tongue
width of 1.85 inches. This will let the adapter plate accommodate up to a 500 MCM standard lug.
Ordering Notes
1) Order one (1) P/N 559643 per two-pole GJ Breaker.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 82 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Lug Adapter Busbar for 225-250 Amp Bullet Nose Type Circuit Breaker (P/N 514717)
Features
♦ Provides a busbar that mounts on the three lug landing positions of a 225A or 250A bullet nose circuit breaker, and
provides a landing for a Special Application Crimp Lug / Strap Combination, which accepts
required wire size.
Ordering Notes
1) Order one (1) P/N 514717 per 225A or 250A Bullet Nose circuit breaker ordered.

Lug Adapter Busbar Kit for 125-200 Amp Bullet Nose Type Circuit Breaker (P/N 534449)
Features
♦ Includes one (1) busbar that mounts on the two lug landing positions of a 125-200A bullet nose circuit
breaker, and provides a landing for one standard two-hole lug having 3/8" bolt clearance holes on 1"
centers. Also includes one (1) busbar that mounts on two landings of the system ground return bar, and
provides one landing for a standard two-hole lug having 3/8" bolt clearance Holes on 1" centers. All busbar
and lug mounting hardware is included.
Ordering Notes
1) Order (1) Part No. 534449 per 125-200A Bullet Nose circuit breaker ordered.

Lug Adapter Busbar Kit for 225-250 Amp Bullet Nose Type Circuit Breaker (P/N 514714)
Features
♦ Includes one (1) busbar that mounts on the three lug landing positions of a 225A or 250A bullet nose
circuit breaker, and provides one landing for a standard two-hole lug having 3/8" bolt clearance holes
on 1" centers. Also includes one (1) busbar that mounts on three landings of the system ground return
bar, and provides one landing for a standard two-hole lug having 3/8" bolt clearance Holes on 1"
centers. All busbar and lug mounting hardware is included.
Ordering Notes
1) Order (1) Part No. 514714 per 225-250A Bullet Nose circuit breaker ordered.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 83 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Lug Hardware Kits
Bullet Distribution Assembly Lug Hardware Kit (P/N 520332)
Features
♦ Kit provides all hardware required to connect load and ground lugs for four (4) positions of a bullet nose-type distribution
assembly (all bullet nose-type distribution Lists except AN). Kit includes (8) 1/4-20 x 3/4" Bolt, (8) 1/4-20 Nut, (16) 1/4"
Flat Washer, (16) 1/4" Lock Washer.
Restrictions
For Distribution Bus Modules that have studs on the ground bar and threaded holes on the load connections.
Ordering Notes
1) Order Kit P/N 520332, as required.

Bullet Distribution Assembly Lug Hardware Kit (P/N 101212)


Features
♦ Kit provides all hardware required to connect load and ground lugs for two (2) positions of a List AN bullet nose-type
distribution assembly. Kit includes (8) 1/4-20 Nut, (8) 1/4" Flat Washer, (8) 1/4" Lock Washer.
Restrictions
For Distribution Bus Modules that have studs on the ground bar and studs on the load connections.
Ordering Notes
1) Order Kit P/N 101212, as required.

LVD Contactor Bypass Kits (P/Ns 514910 and 514912)


Features
♦ Designed for field installation in a bullet nose type distribution bus module where the LVD function is no longer required.
Each kit provides a busbar designed to bypass one (1) low voltage disconnect contactor
in a List BA, CA, or GB.
Restrictions
Kit P/N 514910 may be installed with power applied to system.
Kit P/N 514912 must be installed with power removed from system.
Ordering Notes Kit P/N 514910
1) To bypass a contactor without removing it, order one (1) P/N 514910 kit
(may be installed with power applied to system). Includes hardware.
2) To replace a contactor with busbar, order one (1) P/N 514912 kit
(must be installed with power removed from system). Includes hardware.

External Shunt Monitoring Kit (P/N 541134)


Features Kit P/N 514912
♦ Allows an external shunt to be connected to and monitored by the power system.
Ordering Notes
1) Order kit P/N 541134 to connect an external shunt to the power system.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 84 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
System Load Shunt Test Point Kit (P/N 545569)
Features
♦ Provides customer access test points for measuring the system load Ribbon Cable
Label
shunts with a multimeter (800A @ 50mV).
♦ Field installable in systems manufactured after the introduction of this
kit (see Restrictions).
♦ Mounts to a cutout located on the MCA panel in a Main Bay and the
similar blank panel in a Supplemental Bay.
Restrictions
CANNOT be used when the optional Front Access Ethernet Connector Kit
(P/N 525110) is required (uses the same cutout for mounting).
For Installation into Systems in the Field:
Requires redesigned Quad Shunt Card (P/N 507431, Issue AE or greater), and
(if being installed in a Supplemental Bay) requires a cutout in the blank panel shown below.

Connector
J2 Required
for Kit
Supplemental
Bay Blank Panel

Cutout Required for Kit

Quad
Shunt
Card

Ordering Notes
1) Order System Load Shunt Test Point Kit (P/N 545569) as required.

Optional Front Battery Cover Kits


Features
♦ Provides a front battery cover to the List 93 battery tray.
Restrictions
For 23” battery trays only.
Ordering Notes
1) Order one (1) kit per tray, as required, from the following table.

Part Number Height


548020 8U
548021 7U
548022 6U

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 85 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Optional eSure™ Power Extend Converter
Features
♦ The eSure Power Extend Converter (Model C48/58-1000B, Spec. No. 1C48581000B) is a
compact DC/DC converter unit which offers efficient power conversion. It operates from a
nominal -48 VDC source to provide regulated -58 VDC to the load for continuous operation to
end of battery discharge. Refer to UM565050 and IM565391 for further information.
Restrictions
Only install the power extend converter into a -48 VDC distribution position. Non-repairable damage
will occur if the power extend converter is plugged into a +24 VDC distribution position.
Ordering Notes
1) To add an eSure Power Extend Converter to a 582126000 List AA, AM, AN (24-position bullet)
distribution panel or List JA, JB, JC (20-position bullet dual voltage) or List JD (22-position
bullet dual voltage) distribution panel; refer to the material list in the eSure Power Extend
Converter Calculator (link provided below).

https://www.vertiv.com/en-us/products-catalog/critical-power/dc-power-systems/esure-power-extend-converter-
c4858-1000/#/downloads

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 86 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Replacement Cables
Ordering Notes
1) Refer to the following table and illustration.

Item Part Number / Description


Standard External Alarm Interconnect One 15 ft. cable is provided with List 1. For a replacement cable, order
Cable (cannot be used with List 71): P/N 514327. Also available is P/N 514380 (60 ft. cable).
Provides pre-assembled cable and mating connector for connecting the
MCA external alarm connector to customer circuits.
Connects to J8 on the MCA Main Controller circuit card P/N 534868
located in the Main Bay Distribution Cabinet, and provides
unterminated 28 AWG leads for splicing to customer leads.
Bay's Rectifier Shelf Interface Circuit Card P/N 509071
to MCA Interconnect Cable: Provides pre-assembled cable and mating connectors for connecting
the Bay's Rectifier Shelf Interface circuit card to the MCA (via the
“Interconnect/Inhibit” circuit card).
Connects between the Rectifier Shelf Interface circuit card P/N 535250
located in the Bay's Distribution Cabinet and the “Interconnect/Inhibit”
circuit card located in the same Distribution Cabinet.
Bay's Internal P/N 529120
'Rectifier Module Control' Provides pre-assembled cable and mating connectors for connecting
Interconnect Cable: the Bay's Rectifier Shelf Interface circuit card to the top most Rectifier
Module Mounting Shelf.
Connects between the pigtail located on Rectifier Shelf Interface circuit
card P/N 535250 located in the Bay's Distribution Cabinet and the
connector exiting the top of the top most installed Rectifier Module
Mounting Shelf.
Note that subsequent Rectifier Module Mounting Shelves located
within the same bay are interconnected via the shelf's internal wiring
harness. Connect the mating connector of the cable exiting the bottom
of one Rectifier Module Mounting Shelf with the connector exiting the
top of the shelf installed below it.
Bay-to-Bay A 6 ft. cable is provided with List 2. For a replacement cable, order P/N
'Distribution Control' 514334.
Interconnect Cable: A 25 ft. cable is provided with List 5. For a replacement cable, order
P/N 100916.
Provides pre-assembled cable and mating connectors for connecting
the alarm, reference, and control leads of the Supplemental Bay
distribution to those of the Main Bay distribution (and to the MCA).
Connects between J1 on “Interconnect/Inhibit” circuit card 509532
located within the Main Bay Distribution Cabinet and J2 on
“Interconnect/Inhibit” circuit card 509532 located within the
Supplemental Bay Distribution Cabinet.
Bay-to-Bay A 7-1/2 ft. cable is provided with List 2. For a replacement cable, order
'Rectifier Module Control' P/N 514335.
Interconnect Cable: A 25 ft. cable is provided with List 5. For a replacement cable, order
P/N 100575.
Provides pre-assembled cable and mating connectors for Rectifier
Module control signal interconnection between the MCA (in the Main
Bay) and Rectifier Module Mounting Shelves located in the
Supplemental Bay.
Connects between J8, J9, or J10 on "Interconnect/Inhibit" circuit card
509532 located in the Main Bay Distribution Cabinet and J8, J9, or J10
on "Interconnect/Inhibit" circuit card 509532 located in the
Supplemental Bay Distribution Cabinet.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 87 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Item Part Number / Description


MCA to LMS1000 Interface Cable: P/N 500819
Provided with List 80. Connects between the RS-485 circuit card
installed on the MCA located within the Main Bay Distribution Cabinet
and the OEM3 jack labeled "Vortex RS485" located on back of the
LMS1000 shelf.
LMS1000 Input Power Cable: P/N 514608
Provided with List 80. Connects between the input power connector
located on back of the LMS1000 shelf and the "Internally Fused Voltage
Source" terminals located on “Interconnect/Inhibit” circuit card 509532
located within the Main Bay Distribution Cabinet.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 88 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

External Alarm Cable


Interconnect/ Interconnect/ P/N 514327 Connects Here
LVD Inhibit Rectifier Shelf LVD Inhibit Rectifier Shelf (if List 71 not installed)
Circuit Card Cable Interface Circuit Card Circuit Card Cable Interface Circuit Card on MCA Main Controller
P/N 509532 P/N 509071 P/N 535250 P/N 509532 P/N 509071 P/N 535250 Circuit Card P/N 534868

Front Front
Cable
Pigtail P/N 514334 Pigtail
or 100916
RS-485 MCA
Interface Circuit Card
Cable (if List 80 installed)
P/N 514335
or 100575 Cable P/N 500819
from RS-485 Circuit Card
Cable to LMS1000 (if installed)
Distribution Cabinet P/N 529120 Distribution Cabinet
(inside view) (inside view)
Cable
Connect Cable P/N 529120 between P/N 514608
pigtail on Circuit Card P/N 535250 and
connector coming out of top of Rectifier Shelf.
Optional LMS1000 Monitoring System

Note 1 Rectifier Shelf (rear view) Note 1 Rectifier Shelf (rear view)

Note 1 Rectifier Shelf (rear view) Note 1 Rectifier Shelf (rear view)

Note 1 Rectifier Shelf (rear view) Note 1 Rectifier Shelf (rear view)

Note 1 Rectifier Shelf (rear view) Note 1 Rectifier Shelf (rear view)

Note 1 Rectifier Shelf (rear view) Note 1 Rectifier Shelf (rear view)

Rectifier Shelf (rear view) Rectifier Shelf (rear view)


Supplemental Bay Main Bay

Note 1: P/O Rectifier Shelf internal wire harness.


Mating connectors provided so that harness
exiting bottom of one cabinet plugs into harness
exiting top of cabinet installed beneath it.
Replacement Cable Diagram

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 89 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Replacement Components
Ordering Notes
1) Refer to the following table. Refer also to "Replacement Components" in PD588705000.

Item Part Number


Rectifier Module: Order via P/N 1R483200e or 1R483200.
MCA
MCA Main Controller Circuit Card:
534868 with 534876 Configuration (List 10
Standard Configuration)

534868 with 534877 Configuration (List 11


Special Application Configuration)

534868 with 534878 Configuration (List 12


Special Application Configuration)

534868 with 534879 Configuration (List 13


Special Application Configuration.)

288710900
MCA Keypad/Display Circuit Card: 514362
MCA Power Supply Circuit Card:
Rectifier Shelf Interface Circuit Card: 535250
MCA Interface Circuit Cards: Order via Lists 72, 74, 75, 76, 77, 78
Audible Alarm and Alarm Termination
Order via List 71
Circuit Card
Quad Low Voltage
509477
Disconnect Circuit Card
Interconnect/LVD Inhibit Circuit Card 509532
Quad Shunt POD Circuit Card 507431
Bypass Circuit Card (required for unused
Quad LVD circuit card and Quad Shunt 513737
POD circuit card mounting positions)
Shunt POD Circuit Card (List RD and RE
501981
Battery Disconnect Assembly with Shunt)
Converter Module: 486800128
DC-DC Converters Blank Module: 509288
Alarm Circuit Card: 514957

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 90 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
RECOMMENDED WIRE SIZES, BRANCH CIRCUIT PROTECTION, AND CRIMP LUGS
Load Distribution Wire Sizes and Lugs Selection
Features
♦ When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet Nose-Type Circuit
Breakers) are Provided: Lug-terminated load leads are connected to the individual load busbars located on the
Distribution Bus Module and the respective distribution ground busbar.
The individual load busbars provide 1/4-20 threaded holes or studs for installation of customer-provided two-hole lugs
that have 5/8 inch centers and 1/4 inch bolt clearance holes. Customer must provide additional hardware.
The distribution ground busbar provides 1/4-20 studs for installation of the same type of customer-provided lugs.
Customer must provide lug mounting hardware.
Refer to the illustrations under the LIST DESCRIPTIONS for a dimensional drawing.
Maximum size of wire to be connected to a single fuseholder/circuit breaker position is 2 AWG. For wiring up to 350
kcmil, see Table 12 (Special Application Crimp Lug / Strap Combination), or see the following part numbers in
ACCESSORY DESCRIPTIONS for available adapter busbars: 514717, 534449, and 514714.
♦ When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided: Lug-terminated load
leads are connected to the individual load busbars located on the Distribution Bus Module and the respective distribution
ground busbar.
The individual load busbars provide 3/8-16 captive nuts for installation of customer-provided two-hole lugs that have 1
inch centers and 3/8 inch bolt clearance holes. Customer must provide lug mounting bolts and hardware.
The distribution ground busbar provides 3/8-16 captive nuts for installation of the same type of customer-provided lugs.
Customer must provide lug mounting bolts and hardware.
Refer to the illustrations under the LIST DESCRIPTIONS for a dimensional drawing.
Restrictions
See 'Features' above.
Ordering Notes
1) The rating of the distribution device determines the load lead wire size requirement. The Distribution Bus Module
ordered determines the lug hole size and spacing requirements. For wire size and lug selection; refer to the following.
a) When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet Nose-Type
Circuit Breakers) are Provided: The individual load busbars and associated ground busbar are designed to
accommodate the lugs listed in Tables 10 and 12. Use Table 13 to select recommended load distribution wire sizes
and lugs for various loop lengths per fuse/circuit breaker ampere rating.
b) When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided: The individual load
busbars and associated ground busbar are designed to accommodate the lugs listed in Table 11. Use Table 14 to
select recommended load distribution wire sizes and lugs for various loop lengths per fuse/circuit breaker ampere
rating. Also use these tables when using lug adapters 534449 or 514714 for bullet panels.

2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 91 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Input Battery Wire Sizes and Lugs Selection
Features
♦ When Distribution Bus Modules Providing Battery Disconnect Fuse/Circuit Breaker Positions are Provided:
a) When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet Nose-Type
Circuit Breakers) are Provided: Lug-terminated input battery leads are connected to the individual battery busbars
located on the Distribution Bus Module and the respective battery return busbar.
Battery Load Side: The individual input battery busbars provide 1/4-20 threaded holes for installation of
customer-provided two-hole lugs that have 5/8 inch centers and 1/4 inch bolt clearance holes. Refer to the
illustrations under the LIST DESCRIPTIONS for a dimensional drawing. Maximum size of wire to be connected
to a single fuseholder/circuit breaker position is 2 AWG. For wiring up to 350 kcmil, see Table 12 (Special
Application Crimp Lug / Strap Combination), or see the following part numbers in ACCESSORY DESCRIPTIONS
for available adapter busbars: 514717, 534449, and 514714.
Battery Return Side: The battery return busbar provides 3/8-16 and 1/4-20 captive nuts for installation of
customer-provided two-hole lugs that have 1 or 5/8 inch centers and 3/8 or 1/4 inch bolt clearance holes,
respectively. Refer to "Electrical Connection Locations and Dimensions" under PHYSICAL SIZE INFORMATION
for a dimensional drawing. Customer must provide lug mounting bolts and hardware.
b) When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided: Lug-terminated
input battery leads are connected to the individual battery busbars located on the Distribution Bus Module and the
respective battery return busbar.
Battery Load Side: The individual input battery busbars provide 3/8-16 captive nuts for installation of
customer-provided two-hole lugs that have 1 inch centers and 3/8 inch bolt clearance holes. Refer to the
illustrations under the LIST DESCRIPTIONS for a dimensional drawing. Customer must provide lug mounting
bolts and hardware.
Battery Return Side: The battery return busbar provides 3/8-16 and 1/4-20 captive nuts for installation of
customer-provided two-hole lugs that have 1 or 5/8 inch centers and 3/8 or 1/4 inch bolt clearance holes,
respectively. Refer to "Electrical Connection Locations and Dimensions" under PHYSICAL SIZE INFORMATION
for a dimensional drawing. Customer must provide lug mounting bolts and hardware.
♦ When Distribution Bus Modules with Battery Disconnect Fuse/Circuit Breaker Positions are NOT Provided: Lug-
terminated input battery leads are connected to the battery busbar and battery return busbar. These busbars provide
3/8-16 and 1/4-20 captive nuts for installation of customer-provided two hole lugs that have 1 or 5/8 inch centers and 3/8
or 1/4 inch bolt clearance holes, respectively. Customer must provide lug mounting bolts and hardware. Refer to
"Electrical Connection Locations and Dimensions" under PHYSICAL SIZE INFORMATION for a dimensional drawing.
Restrictions
See 'Features' above.
Ordering Notes
1) When Distribution Bus Modules Providing Battery Disconnect Fuse/Circuit Breaker Positions are Provided: The
rating of the disconnect device determines the input battery lead wire size requirement. The Distribution Bus Module
ordered determines the lug hole size and spacing requirements. For wire size and lug selection; refer to the following.
a) When Distribution Bus Modules Using Bullet Nose-Type Devices (TPS/TLS Fuses and/or Bullet Nose-Type
Circuit Breakers) are Provided: The individual input battery busbars and associated battery return busbar are
designed to accommodate the lugs listed in Tables 10 and 12. Use Table 13 to select recommended battery wire
sizes and lugs for various loop lengths per battery disconnect fuse/circuit breaker ampere rating. Table 14 may be
used to select two-hole lugs with 3/8 inch bolt clearance holes and 1 inch centers for the battery return busbar.
b) When Distribution Bus Modules Using GJ/218 Circuit Breakers or TPH Fuses are Provided: The individual input
battery busbars and associated battery return busbar are designed to accommodate the lugs listed in Table 11. Use
Table 14 to select recommended battery wire sizes and lugs for various loop lengths per battery disconnect
fuse/circuit breaker ampere rating.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 92 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
3) When Distribution Bus Modules with Battery Disconnect Fuse/Circuit Breaker Positions are NOT Provided: Battery
wire size and lug requirements are determined by site requirements. For wire size and lug selection; refer to the
following.
The battery busbars are designed to accommodate the lugs listed in Tables 10 and 11. Use Table 14 to select
recommended battery wire sizes and lugs for various loop lengths per required battery branch circuit ampere rating.
Table 13 may be used to select two-hole lugs with 1/4 inch bolt clearance holes and 5/8 inch centers.
Note: Lists RA, RB, RC, RD, and RE do not provide 1/4-20 captive nuts on the battery busbar; only 3/8-16 captive
nuts are furnished.
4) For other available lugs and hardware, refer to drawings 031110100 through 031110300.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 93 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Standard Crimp Lug Tables

Lead Size Part Number


14-10 AWG 245342300
8 AWG 245390200
6 AWG 245346700
4 AWG 245346800
2 AWG 245346900
Table 10
Crimp Lug
Two-Hole, 1/4” Bolt Clearance Hole, 5/8” Centers

Lead Size Part Number


6 AWG 245349900
4 AWG 245350000
2 AWG 245348200
1/0 AWG 245347100
2/0 AWG 245347200
3/0 AWG 245347300
4/0 AWG 245347400
250 kcmil 245347500
300 kcmil 245347600
350 kcmil 245347700
400 kcmil 245347800
500 kcmil 245347900
600 kcmil 245348000
750 kcmil 245348100
Table 11
Crimp Lug
Two-Hole, 3/8” Bolt Clearance Hole, 1” Centers

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 94 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Special Application Crimp Lug / Strap Combination Table
Features
♦ Straps two fuseholder/circuit breaker wiring positions together, and provides a crimp-type lug which allows distribution
wiring up to 350 kcmil size (maximum size of wire to be connected to a single position is 2 AWG). Designed for use with
125 ampere and larger bullet nose-type circuit breakers or TPS/TLS-type fuses, which require at least two mounting
positions.
Restrictions
If used with bullet nose-type circuit breakers or TPS/TLS-type fuses smaller than 125 amperes, an empty mounting position is
required adjacent to the distribution device.
Ordering Notes
1) Specify part number from Table 12 for desired lead size.

Lead Size Part Number


1/0 AWG 245393500
2/0 AWG 245393600
3/0 AWG 245393700
4/0 AWG 245393800
250 kcmil 514872
350 kcmil 514873
Table 12
Special Application Crimp Lug / Strap Combination
(Two-Hole Lug, 1/4” Bolt Clearance Hole, 5/8” Centers)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 95 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Wire Size and Lug Selection Tables for Load and Battery Connections
to TPS/TLS Fuses and Bullet Nose-Type Circuit Breakers or Battery Branch Circuits

Fuse/ Recm 90°C Wire Size (1)


Circuit
14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG 1/0 AWG
Breaker
Amperage Loop Length (feet) (2)
1, 3, 5,
37 (3, 4) 58 (3, 4) 93 (3, 4) -- -- -- -- --
6, 10A
15A 24 (3, 4) 39 (3, 4) 62 (3, 4) -- -- -- -- --
20A -- 29 (3, 4)
46 (3, 4)
74 (3, 4)
-- -- -- --
25A -- -- 37 (3, 4) 59 (3, 4) 94 (3, 4) -- -- --
30A -- -- 31 (3, 4)
49 (3, 4)
78 (3, 4)
-- -- --
35A -- -- -- 42 (3, 4) 67 (3, 4) 107 (3, 4) -- --
40A -- -- -- 37 (3, 4)
59 (3, 4)
94 (3, 4)
-- --
45A -- -- -- 33 (3, 4) 52 (3, 4) 83 (3, 4) -- --
50A -- -- -- 29 (3, 4) 47 (3, 4) 75 (3, 4) -- --
60A -- -- -- -- 39 (3, 4)
62 (3, 4)
99 (3, 4)
--
70A -- -- -- -- 33 (3) 53 (3, 4) 85 (3, 4) 135 (4)
75A -- -- -- -- 31 (3) 50 (3, 4) 79 (3, 4) 126 (4)
80A -- -- -- -- -- 47 (3, 4) 74 (3, 4) 118 (3, 4)
Recommended Crimp Lug (5)
Lug 245342300 245342300 245342300 245390200 245346700 245346800 245346900 245393500 (6)

1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature operating in ambients of 30°C and 40°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.
6
Special application crimp lug / strap combination.
Table 13 (cont'd on next page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPS/TLS Fuses and Bullet Nose-Type Circuit Breakers
or Battery Branch Circuits

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 96 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Fuse/ Recm 90°C Wire Size (1)


Circuit
4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 350 kcmil
Breaker
Amperage Loop Length (feet) (2)
90A 41 (3) 66 (3, 4) 105 (3, 4) 133 (4) -- -- -- --
100A -- 59 (3, 4) 95 (3, 4) 119 (3, 4) -- -- -- --
125A -- 47 (3)
76 (3, 4)
95 (3, 4)
120 (4)
-- -- --
150A -- -- 63 (3, 4) 79 (3, 4) 100 (3, 4) -- -- --
175A -- -- -- 68 (3, 4)
86 (3, 4)
108 (3, 4)
-- --
200A -- -- -- -- 75 (3, 4) 95 (3, 4) 112 (3, 4) --
225A -- -- -- -- 67 (3)
84 (3, 4)
100 (3, 4)
--
250A -- -- -- -- -- 76 (3, 4, 7) 90 (3, 4, 7) 126 (3, 4, 7)
Recommended Crimp Lug
Lug (5) 245346800 245346900 245393500 (6) 245393600 (6) 245393700 (6) 245393800 (6) 514872 (6) 514873 (6)
Lug (8, 9) -- 245348200 245347100 245347200 245347300 245347400 245347500 245347700
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature operating in ambients of 30°C and 40°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.
6
Special application crimp lug / strap combination.
7
MUST USE P/N 514717 Lug Adapter Busbar for lugs having 1/4" bolt clearance hole, 5/8" centers.
8
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping information.
9
MUST USE P/N 534449 Lug Adapter Busbar Kit for 125-200A circuit breakers, or P/N 514714 Lug Adapter Busbar Kit for
225A-250A circuit breakers.
Table 13 (cont'd from previous page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPS/TLS Fuses and Bullet Nose-Type Circuit Breakers
or Battery Branch Circuits

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 97 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Wire Size and Lug Selection Tables for Load and Battery Connections
to TPH Fuses and GJ/218-Type Circuit Breakers or Battery Branch Circuits

Fuse/ Recm 90°C Wire Size (1)


Circuit
6 AWG 4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil
Breaker
Amperage Loop Length (feet) (2)
70A 33 (3) 53 (3, 4) 85 (3, 4) 135 (4) -- -- -- --
80A -- 47 (3, 4) 74 (3, 4) 118 (3, 4) -- -- -- --
100A -- -- 59 (3, 4) 95 (3, 4) 119 (3, 4) -- -- --
125A -- -- 47 (3) 76 (3, 4) 95 (3, 4) 120 (4) -- --
150A -- -- -- 63 (3, 4)
79 (3, 4)
100 (3, 4)
-- --
175A -- -- -- -- 68 (3, 4) 86 (3, 4) 108 (3, 4) --
200A -- -- -- -- -- 75 (3, 4)
95 (3, 4)
112 (3, 4)
Recommended Crimp Lug (5)
Lug 245349900 245350000 245348200 245347100 245347200 245347300 245347400 245347500
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature operating in ambients of 30°C and 40°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping information.
Table 14 (cont'd on next page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPH Fuses and GJ/218-Circuit Breakers
or Battery Branch Circuits

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 98 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

Fuse/ Recm 90°C Wire Size (1)


Circuit
2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil
Breaker
Amperage Loop Length (feet) (2)
225A -- 67 (3) 84 (3, 4) 100 (3, 4) 120 (4) -- -- --
250A -- -- 76 (3) 90 (3, 4) 108 (3, 4) 126 (4) -- --
159 (4)
300A -- -- -- 90 (3) 105 (3, 4) 120 (3, 4) --
(2) Wires
75 (3, 4) 95 (3, 4) 112 (3, 4)
400A -- -- -- -- --
(2) Wires (2) Wires (2) Wires
76 (3) 90 (3, 4) 108 (3, 4) 126 (4)
500A -- -- -- --
(2) Wires (2) Wires (2) Wires (2) Wires
105 (3, 4)
90 (3) (2) Wires 120 (3, 4)
600A -- -- -- -- --
(2) Wires 157 (4) (2) Wires
(3) Wires
Recommended Crimp Lug (5)
245347200 245347300 245347400 245347500 245347600 245347700 245347800 245347900
Lug
(per cable) (per cable) (per cable) (per cable) (per cable) (per cable) (per cable) (per cable)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature operating in ambients of 30°C and 40°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping information.
Table 14 (cont'd from previous page)
Recommended Wire Sizes and Lugs for Load and Battery Connections
to Various TPH Fuses and GJ/218-Circuit Breakers
or Battery Branch Circuits

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 99 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
AC Input Branch Circuit Protection and Wire Size Selection
(when Optional List 45 Top Mount AC Input Termination Panel is Furnished)
Features
♦ See List 45 under LIST DESCRIPTIONS.
♦ See “Electrical Connections Locations and Dimensions, AC Input (to Optional List 45 Top Mount AC Input Termination
Panel)” under PHYSICAL SIZE INFORMATION for illustration.
Ordering Notes
1) Refer to Table 15 for recommended wire sizes and branch circuit protection.

AC INPUT (to Optional List 45 Top Mount AC Input Termination Panel)


Connection Points for Individual Rectifier Module AC Input Branch Circuits are Provided
Operating Recm AC Input Terminals
Recm 90°C
Ambient Branch Circuit
Wire Size (1) Capacity Type
Temperature (1) Protection (2, 3)

30°C
25 Amperes 10 AWG 10 to 24 AWG Screw Clamp
40°C

AC INPUT GROUND (to Optional List 45 Top Mount AC Input Termination Panel)
A Ground Bar is Provided on Each Side of the List 45 AC Input Termination Panel
Operating Ground Bar Terminals (4)
Recm 90°C
Ambient
Wire Size (5) Capacity Type
Temperature (1)

30°C
10 AWG 10 to 14 AWG Screw Clamp
40°C
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature, operating in ambients of 30°C and 40°C was used. For operation in other ambients, apply derating
factors listed in Table 310-16 of the NEC. For operation in countries where the NEC is not recognized, follow
applicable codes.
2
The AC input branch circuit protective device should be of the time-delay or high inrush type.
3
Recommendations based on Nominal Line Full Load Input Current of 18 Amperes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the panel. Frame
ground terminals must be connected to earth ground, not power system neutral.
5
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If
aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor
size. For operation in countries where the NEC is not recognized, follow applicable codes.
Table 15
Recommended AC Input Branch Circuit Protection and Wire Size
when Using List 45 Top Mount AC Input Termination Panel

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 100 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
AC Input Branch Circuit Protection and Wire Size Selection
(when Optional List 46 Top Mount AC Input Termination Panel is Furnished)
Features
♦ See List 46 under LIST DESCRIPTIONS.
♦ See “Electrical Connections Locations and Dimensions, AC Input (to Optional List 46 Top Mount AC Input Termination
Panel)” under PHYSICAL SIZE INFORMATION for illustration.
Ordering Notes
1) Refer to Table 16 for recommended wire sizes and branch circuit protection.

AC INPUT (to Optional List 46 Top Mount AC Input Termination Panel)


Connection Points for Two 3-Phase AC Input Feeds per Shelf are Provided
Operating Recm AC Input Terminals
Recm 90°C
Ambient Branch Circuit
Wire Size (1) Capacity Type
Temperature (1) Protection (2, 3)

30°C
40 Amperes,
8 AWG 6 to 14 AWG Screw Clamp
3-Pole
40°C

AC INPUT GROUND (to Optional List 45 Top Mount AC Input Termination Panel)
A Ground Bar is Provided on Each Side of the List 45 AC Input Termination Panel
Operating Ground Bar Terminals (4)
Recm 90°C
Ambient
Wire Size (5) Capacity Type
Temperature (1)

30°C
10 AWG 10 to 14 AWG Screw Clamp
40°C
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor
temperature, operating in ambients of 30°C and 40°C was used. For operation in other ambients, apply derating
factors listed in Table 310-16 of the NEC. For operation in countries where the NEC is not recognized, follow
applicable codes.
2
The AC input branch circuit protective device should be of the time-delay or high inrush type.
3
Recommendations based on Nominal Line Full Load Input Current of 29.3 Amperes.
4
Equipment grounding conductors must be provided with the AC input conductors supplied to the panel. Frame
ground terminals must be connected to earth ground, not power system neutral.
5
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. If
aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for increased conductor
size. For operation in countries where the NEC is not recognized, follow applicable codes.
Table 16
Recommended AC Input Branch Circuit Protection and Wire Size
when Using List 45 Top Mount AC Input Termination Panel

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 101 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
AC Input Branch Circuit Protection and Wire Size Selection
(when wiring to Rectifier Module Mounting Shelf[s])
Refer to PD588705000.
Relay Rack Frame Grounding Requirements
Ordering Notes
1) For relay rack grounding requirements, refer to the current edition of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NPFA) National Electrical Code (NEC), applicable local codes, and your
specific site requirements.

A customer's grounding network lead can be attached to the top of each relay rack. Provision is made for installing a
lead with a two-hole lug that has 1/4" bolt clearance holes on 5/8" centers. Refer to Table 10 for lug selection.
External Alarm, Reference, and Control Wire Sizes
Features
♦ External alarm, reference, and control connection points are located on…
• the optional List 80 LMS1000 Monitoring System
(refer to the documentation furnished with the LMS1000),
• J1-J4 on the optional List 71 Audible Alarm and Alarm Termination Circuit Card P/N 524734,
• TB1 on circuit card P/N 509532,
• and J8 on circuit card P/N 534868 (if List 71 not installed).
♦ See “Electrical Connections Locations and Dimensions; External Alarm, Reference, and Control Connections” under
PHYSICAL SIZE INFORMATION for illustration.

J1-J4 on Optional List 71 Audible Alarm and


Alarm Termination Circuit Card P/N 524734
Terminals Recm
Capacity Type Wire Size
22 AWG for Loop Lengths Up to 200 ft.
26 to 16 AWG Spring-Clamp
18-20 AWG for Loop Lengths Over 200 ft.

TB1 on Circuit Card P/N 509532


Terminals Recm
Capacity Type Wire Size
22 AWG for Loop Lengths Up to 200 ft.
26 to 16 AWG Spring-Clamp
18-20 AWG for Loop Lengths Over 200 ft.

J8 on Circuit Card P/N 534868


Terminals Recm Wire Size
22 AWG for Loop Lengths Up to 200 ft.
D-Type Connector
18-20 AWG for Loop Lengths Over 200 ft.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 102 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
SPECIFICATIONS
Note: For List 31 and 51 Rectifier Shelf specifications, refer to PD588705000.
For Rectifier specifications; refer to UM1R483500e (Rectifier User Instructions).
For List 63, 64, and 62 DC-DC Converter specifications, refer to SAG588249700.
For List 80 LMS1000 Monitoring System specifications, refer to SAG586505500.
For List 92 Battery Stand specifications, refer to SAG588820000.
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range: -40°C to +40°C (-40°F to +104°F).
1.1.2 Storage Ambient Temperature Range: -40°C to +85°C (-40°F to +185°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of 0% to 95%, non-
condensing.
1.1.4 Altitude: see PD588705000
1.1.5 Mounting: This equipment is intended only for installation in a Restricted Access Location on or above a non-
combustible surface. Clearance requirements are:
(A) Recommended minimum aisle space clearance for the front of each bay is 2' 6".
(B) Recommended minimum aisle space clearance for the rear of each bay is 2’ 0” for any of the following
conditions:
1. Multiple bay arrangements that incorporate rear inter-bay busbars (List 2 bays).
2. Any bay equipped with a List RC, RD or RE battery disconnect option.
3. Making AC input connections to Spec. No. 5887005000 Rectifier Mounting Shelves (List 31) when a
List 45 or 46Top Mount AC Input Termination Panel is not ordered.
4. Addition of a Rectifier Mounting Shelf in the field.
5. Addition of any DC-DC Converter Mounting Shelf or Frame (List 63 or 64) in the field.
For all other conditions, required minimum spacing from the rear of the bay to a wall or other solid surface is
that which is specified for proper Rectifier Mounting Shelf ventilation. Refer to the specific Rectifier Mounting
Shelf Power Data Sheet for ventilation spacing requirements. Note: Minimum spacing specified for ventilation
may not permit replacement of certain components such as busbars or Rectifier Mounting Shelves.
1.1.6 Heat Dissipation: 402.6 Watts per square foot / foot. Special equipment room cooling may be required.
1.2 Compliance Information
1.2.1 Safety Compliance: This power board is UL Listed ("c UL") as a DC Power Distribution Center for
Communications Equipment. This unit meets the requirements of CSA 22.2, No. 225 and is tested and Certified
by UL ("c UL") as a Custom Built Power Distribution Center for Communications Equipment.
1.2.2 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-
CORE and GR-63-CORE. Contact Vertiv Network Power for NEBS compliance reports.
1.3 MCA Features
1.3.1 MCA Interface: You can operate the MCA locally via the front panel accessed interface pad, or remotely via
the WinLink option, WEB Pages, or Modbus® TCP. The following Interface Options are available for use with
WinLink: Modem and RS-232/Modem. The following Interface Options are available for use with WEB Pages:
Ethernet.
In lieu of WinLink, MCA operation can be controlled remotely by other equipment via the LMS1000.
Note: Only one interface (Modem, Combination Modem/RS-232, Ethernet, or RS-485) can be installed on the
MCA.
Note: Wiring options are provided to lockout changing Power System adjustment/configuration/ calibration
settings locally and/or remotely.
In addition, the Ethernet Interface Option provides a Web-Browser and a Modbus® TCP Interface. The following
software options are also available.
SNMP Interface: Provides an Ethernet port for MCA connection into a TCP/IP network and support for
SNMP V2 (Simple Network Management Protocol). Communications to and from the MCA is accomplished
via a MIB (Management Information Browser). SNMP Traps are provided for alarms listed on the MCA
Menu Tree under the "Alarms Menu".
Battery Monitoring: Provides Battery Monitoring via the Web Browser Interface.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 103 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
1.3.2 Float Charging Output Mode: In this mode of operation, system output voltage is constant and output current
does not exceed the current limit setting. During normal operation, the battery is not required to furnish load
current and remains in a fully charged condition.
Note: If the current demanded by the load exceeds the current limit setting of the system, the battery is
required to furnish the difference in load current and begins discharging.
Note: If the system is used with a digital battery charge temperature compensation probe or TXM, the MCA
automatically adjusts system output. This ensures proper voltage to the battery as battery ambient
temperature fluctuates.
1.3.3 Test/Equalize Charging Output Mode: This mode of operation is used if higher output voltage is required for
equalizing the charge on all battery cells of a conventional flooded cell battery, or for recharging the battery
following a commercial power failure.
If the installation site does not require system equalize mode of operation, the equalize feature can be used as
a test feature. System equalize voltage can be adjusted to a test voltage value. Placing the system into the
test/equalize mode causes system output voltage to increase or decrease to this test voltage value.
Note: If the system is used with a battery charge digital temperature compensation probe or TXM, typical
equalize mode of operation is not used.
1.3.4 Output Mode of Operation Selection: There are four methods of placing the system from the float mode to the
test/equalize mode.
(A) Method 1 (Manual Test/Equalize): A user manually places the system into the test/equalize mode via the
MCA interface. A user must manually return the system to the float mode via the MCA interface.
(B) Method 2 (Manually Initiated Timed Test/Equalize): A user manually places the system into the
test/equalize mode via the MCA interface. The system automatically returns to the float mode after a
preset programmable time period (1-99 hours, in increments of one hour).
(C) Method 3 (Automatic Test/Equalize):
THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET CELL BATTERIES.
USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS NOT RECOMMENDED.
This feature can be enabled or disabled by a user via the MCA. The default state is disabled.
The Automatic Equalize feature is a time based function that is controlled by a customer selectable
multiplier and by the Battery On Discharge (BOD) alarm setpoint. The MCA’s default setting is for a
multiplier of zero, which disables the Automatic Equalize feature.
When the Automatic Equalize feature is enabled, if system voltage drops to less than the BOD alarm
setpoint, the MCA initiates a timing cycle to measure the discharge time period. The MCA requires at
least 15 minutes of continuous BOD alarm in order to prevent nuisance equalization cycles. When system
voltage rises to above the BOD alarm setpoint, the MCA ends the discharge timing cycle and (assuming a
minimum of 15 minutes has elapsed) places the Rectifier Modules into the equalize mode for a customer
selectable multiple of the discharge time period (the discharge time period includes the initial 15 minutes).
The equalize time period can be set for 0 to 15 times the discharge time period, up to a maximum of 300
hours. A zero (0) setting disables the feature.
(D) Method 4 (External Test/Equalize): A user (or external equipment) places the system into the
test/equalize mode by applying an external signal to the system. The system returns to the float mode
when the external signal is removed. This method overrides the other three methods.
1.3.5 Remote On/Off (TR): The operation of any or all Rectifier Modules can be inhibited (TR) via the LMS1000, the
WinLink option, the Ethernet option, or from the MCA front panel accessed interface pad.
1.3.6 MCA Local Display: Provides digital metering of system load voltage and current, individual Rectifier Module
current, subsystem load voltage and current (a subsystem is not installed in this power system), and load
current of subsystem, system, and/or battery shunts. Also displays system alarm messages and adjustment
information, as detailed in Section 1.3.10 "MCA Display".
The MCA contains a "Power Down" mode. The MCA turns off its display and Rectifier Module communications
to conserve power when system voltage falls below 40 volts. Full operation is restored when system voltage
recovers to 47.0 volts. The display and communications can be temporarily reactivated by the user.
1.3.7 MCA Meter Accuracy: ±0.01 V, ±0.005% / °C
1.3.8 MCA Universal Adjustment Circuit: Provides single point control of float output voltage, test/equalize output
voltage, high voltage shutdown, and current limit adjustments.
Note: If the MCA should fail, the Rectifier Modules remember the float and high voltage shutdown settings
last delivered by the MCA. The current limit setting of each Rectifier Module goes to 66 amperes.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 104 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Provides adjustments for all MCA alarm and control circuits. Adjustment ranges and factory settings as
follows.
All adjustments can be performed locally via the MCA front panel accessed interface pad, and most can be
performed remotely via the LMS1000 Remote Equipment Interface Link option, the WinLink option, or the
Ethernet (Web-Browser Interface) option.
(A) Rectifier Module Output Voltage:
(1) Without Battery Charge Temperature Compensation: Float voltage is adjustable from 47.00 to 58.00
volts DC. Test/equalize voltage is adjustable from 44.00 to 58.00 volts DC. The output voltage
temperature coefficient does not exceed 0.01% per degree centigrade from -40°C to +65°C. Factory
set as follows unless otherwise specified.

Power System List No. 10 11 12 13


MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 54.48 54.00 54.48 54.48

(2) With Battery Charge Digital Temperature Compensation Probe or TXM (multiple probe concentrator
module): With an optional battery charge digital temperature compensation probe or TXM installed,
the MCA automatically increases or decreases the output voltage as battery ambient temperature
decreases or increases, respectively. The float and test/equalize voltage range is the same as
without battery charge digital temperature compensation. Float voltage is factory set as follows at
25°C battery ambient.

Power System List No. 10 11 12 13


MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 54.48 54.00 54.48 54.48

Using battery and equipment manufacturers’ recommendations, the user selects the following
temperature compensation curve parameters via the MCA. Refer to the Temperature Compensation
Probe Curve provided in Figure 1.
a) The temperature compensation slope in volts/°C. Adjustable from zero to 200 millivolts/°C.
Factory set at 0V/°C (DIGITAL TC OFF).
b) The maximum voltage limit in volts DC. Adjustable from float up to 58.00 volts DC, but
automatically limited to 1.0 volt below the High Voltage Shutdown setting. Factory set as
follows.

Power System List No. 10 11 12 13


MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 56.50 55.50 56.50 56.50

c) The minimum voltage limit in volts DC. Adjustable from float down to 44.00 volts DC, but
automatically limited to 1.0 volt above the Low Voltage Disconnect Reconnect setting. Factory
set as follows.

Power System List No. 10 11 12 13


MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 50.00 51.00 50.00 50.00
(B) Rectifier Module Current Limit: Adjustable from 10% to 121% of total system capacity at maximum rated
output voltage. Factory set at 100% of rated full load, unless otherwise specified.
The MCA automatically adjusts the current limit circuit on each Rectifier Module so that this value is not
exceeded. If a Rectifier Module fails, the MCA automatically resets each remaining Rectifier Module's
current limit point to maintain this value. The MCA also insures that the current limit circuit on any
Rectifier Module is not set above 121% of its capacity. The default current limit setting is the sum of each
installed Rectifier Modules output rating. If an additional Rectifier Module is added to the system, the

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 105 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
system current limit is automatically increased by the rating of the new Rectifier Module and the new
current limit value is displayed.
(C) Rectifier Module High Voltage Shutdown: Adjustable from 48.00 to 59.00 volts DC. Factory set at 57.50
volts, unless otherwise specified.
(D) High Voltage Alarm 1: Adjustable from 48.00 to 59.00 volts DC. Factory set as follows, unless otherwise
specified.
Power System List No. 10 11 12 13
MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 55.50 55.40 55.50 55.50
(E) High Voltage Alarm 2: Adjustable from 48.00 to 59.00 volts DC. Factory set as follows, unless otherwise
specified.
Power System List No. 10 11 12 13
MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 56.50 56.00 56.50 56.50
(F) Battery On Discharge Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory set as follows, unless
otherwise specified.
Power System List No. 10 11 12 13
MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 48.00 47.00 48.00 48.00
(G) 50% Battery On Discharge (Very Low Voltage) Alarm: Adjustable from 40.00 to 56.00 volts DC. Factory
set per table below, unless otherwise specified.
Power System List No. 10 11 12 13
MCA Configuration No. 534876 534877 534878 534879
Factory Setting (Volts) 46.00 44.50 46.00 46.00
(H) System Load Current Alarm: Adjustable from 0 to 60,000 amperes. Factory set at 2,000 amperes, unless
otherwise specified.
(I) High Battery Ambient Temperature Alarm (if battery charge digital temperature compensation probe or
TXM installed): Adjustable from -50°C to +99°C. Factory set to off, unless otherwise specified. (If TXM
installed, each temperature probe has an associated alarm.)
(J) Low Battery Ambient Temperature Alarm (if battery charge digital temperature compensation probe or
TXM installed): Adjustable from -49°C to +100°C. Factory set to off, unless otherwise specified. (If TXM
installed, each temperature probe has an associated alarm.)
(K) Low Voltage Disconnect (if LVD installed): Low voltage disconnect is adjustable from 40.0 to 50.0 volts
DC. Reconnect is adjustable from 47.0 to 57.0 volts DC. The factory disconnect and reconnect settings
are as follows, unless otherwise specified.
Power System List No. 10 11 12 13
MCA Configuration No. 534876 534877 534878 534879
Factory Disconnect
42.0 43.5 42.0 42.0
Setting (Volts)
Factory Reconnect
49.0 50.5 49.0 49.0
Setting (Volts)
(L) Audible Alarm Cutoff Reset Feature: Adjustable from 0 to 15 minutes, in one minute intervals. A zero
setting disables the feature. Factory set at 15 minutes, unless otherwise specified.
(M) Timed Test/Equalize Period (also enables/disables the manually initiated timed test/equalize feature):
Adjustable from 1 to 99 hours, in one hour intervals. When a value is set, the feature is enabled. You

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 106 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
disable the feature by selecting the setting above 99. Factory set at 1 (one) hour, unless otherwise
specified.
(N) Automatic Test/Equalize Period (also enables/disables the automatic test/equalize feature): Adjustable
from 0 to 15 times the discharge time period, up to a maximum of 300 hours. A zero (0) setting disables
the feature. Factory set at zero (0), unless otherwise specified.
(O) Relay Test Seconds: Adjustable from 5 to 120 seconds, in one second intervals. Factory set at 45
seconds, unless otherwise specified.
1.3.9 MCA Audible Alarm Cutoff (List 10 and List 11 MCA only): An audible alarm can be connected to the MCA that
sounds when any alarm condition monitored by the MCA occurs. The alarm can be manually silenced (cut off)
by pressing a local pushbutton. A local indicator illuminates when the audible alarm has been cut off. The
alarm remains silenced for the current alarm condition only. If another alarm condition occurs, the audible
alarm again sounds.
A programmable audible alarm cutoff reset feature is provided. Once an audible alarm has been cut off, it
automatically resets (and sounds if the alarm condition is still present) after the time period programmed
expires. If the audible alarm is again cut off while the same alarm condition is still present, the reset feature is
inoperable, and the audible alarm remains silenced. If another alarm condition occurs, the audible alarm again
sounds.
Note: External MCA audible alarm relay contacts are not available if the power system is equipped with a
List 12 or List 13 special application MCA.
1.3.10 Low Voltage Disconnect (if associated components are furnished in a Distribution Cabinet): Protects the
battery from complete discharge. Automatically disconnects the battery and system output from the
controlled load(s) (LVLD) or battery from system and loads (LVBD) if battery voltage decreases below a preset
adjustable value. This can occur during a prolonged commercial AC power failure, where the battery is
required to furnish power to the load, and subsequently starts to discharge.
For further information, refer to the description of the Low Voltage Disconnect circuit card under List 21
Features in the List Descriptions section of this document.
1.3.11 Load Sharing: Digital active load sharing circuitry in each Rectifier Module balances the load proportionately
among all rectifiers in a bay. The MCA provides a load sharing feature that automatically balances the load
among multiple bays.
1.3.12 MCA Load Share Alarm: If Rectifier Modules fail to share the load the MCA turns on a Load Share Alarm. This
alarm can be enabled or disabled by the customer. The factory default setting is to have the MCA Load Share
Alarm 'enabled'.
1.3.13 Local Controls: Refer to the "System Operating Procedures" chapter in the Power System User Instructions
(Section 5975) for a complete description.
Location NAME / Description Type
FUNCTION SELECT UP and DOWN Pushbutton Switches
FUNCTION SET ENTER Pushbutton Switch
MCA
FUNCTION SET YES (+) and NO (-) Pushbutton Switches
ALARM CUTOFF Pushbutton Switch
1.3.14 Local Status and Alarm Indicators: Refer to the "System Operating Procedures" chapter in the Power System
User Instructions (Section 5975) for a complete description.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 107 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Location NAME / Description Type

Rectifier
See PD588705000.
Module

Message Display, Shows...


• Active Alarms or "SYSTEM OK"
• Various Measurement Items and Values
• Various Adjustment Items and Values ---
• Various Configuration Items and Settings
• Various Calibration Items and Settings
MCA See Paragraph 1.3.10. "MCA Display"
ALARM CUTOFF LED - yellow
MAJOR LED - flashing red
MINOR LED - red
AC LED - green/red
TEST/EQ LED - yellow
1.3.15 MCA Display: The following are illustrations from the MCA Menu Tree (Section 6022). Refer to the latest
version of Section 6022 for the most recent MCA Menu Tree. Refer to the "Navigating the MCA" and "System
Operating Procedures" chapters of the Power System User Instructions (Section 5975) for complete
descriptions of menu items.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 108 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide

NETSURE™ MCA Menu Tree


(Sheet 1 of 2)
STARTUP SEQUENCE NORMAL DISPLAY W/ ALARMS
MAIN ALARM MENU
133
SPEC NO. ###### ## ALARMS ACTIVE
MCA SWV ######## 2 ALARM EMERG STOP 1
1 NOT RUNNING YET! LVD ALARM MENU
Initializing....## 11 …………………………. 3 ALARM LVD ACTIVE 4
22 LVD** ACTIVATED
ALARM SYS 50%BOD 1
SET ###V DEFAULTS 4 ALM VERY LO VOLT 1,14 RECONNECT LVD**
134
MUST SET SYS = ###V ALARM LO VOLTAGE 1,15
23 ARE YOU SURE? +- 9
Local Lockout On 9
LOADING ###V..## ALARM SYSTEM BOD 1
5
ALARM LO FLOAT 1,15 24 MAIN ALARM MENU

ALARM SYSTEM HV1 1 25 NORMAL DISPLAY


134A MUST SET SPEC NO. 6
ALARM HIGH FLOAT 1,15
SET ###### @ ###V 16
ALARM SYSTEM HV2 1
7
CHANGE SPEC...## ALARM HI VOLTAGE 1,15
8 ALARM SUBSYS LV 1

INITIALIZATION MENU 9 ALARM SUBSYS HV 1

135 CHECK SETPOINTS! 12 10 ALARM SYSTEM FA 1 PCU ALARM MENU


PCU DETAIL MENU
136 FLOAT = ###.##V 11 ALARM SUBSYS FA 1 26 PCU ** FAILURE 47 PCU## EMERG STOP
137 TEST/EQ = ###.##V 12 ALM SUBSYS MAJOR 1 27 MAIN ALARM MENU 48 PCU## AC FAIL
138 SET HVS = ###.##V
13 ALARM ALL AC OFF 1 28 NORMAL DISPLAY 49 PCU## HI AC LINE
139 CURRLIM = #####A
CURRLIM = #####MAX
14 ALARM HI AC LINE 3 TEMPERATURE ALARM MENU 50 PCU## FAN FAIL
ALM ## PCUs FAIL 3 TEMP SENSOR** HI
139A BATTLIM DISABLED ALARM MRFA 1,15
28A 51 PCU## BRKR OFF
15
BATTLIM = #####A ALARM 1 RFA 2,15 28B TEMP SENSOR** LO 52 PCU## HVS ACTIVE
NO PCUs FOUND 1
140 SYS HV1 = ###.##V 28C MAIN ALARM MENU
HI FLOAT = ###.##V 15 15B ALM PCU## SHARE 1 53 PCU## A/D FAIL

SYS HV2 = ###.##V


28D NORMAL DISPLAY 54 PCU## CONVERTER
141 15A ALM TEMP SENSOR 1
HI VOLTAGE = ###.##V 15
MCA ALARM MENU
16 ALM SYSTEM CURR 2 55 PCU## HIGH TEMP.
142 SYS BOD = ###.##V 29 MCA BOARD FAIL 1
LOW FLOAT = ###.##V 15 17 ALM SUBSYS CURR 2 56 PCU## OPEN SENSE
SYS 50% = ###.##V
30 A/D INPUT FUSE 5
57 PCU## SWITCH OFF
143 VERYLOVOLT = ###.## 14
17A ALM BAT CHG CURR 2

LO VOLTAGE = ###.## 15
31 NO SYSTEM VOLTS 1
58 PCU## NO REPLY
18 ALM SUBSYS MINOR 2
144 SYSCURR = #####A 32 NO SUBSYS VOLTS 1
59 PCU ALARM MENU
19 ALARM MCA/SHELF
145 SUB HV = ###.##V 33 NO SENSE VOLTS 2 60 NORMAL DISPLAY
20 FUNCTION MENU SENSE VOLT ERROR 2
146 SUB LV = ###.##V
21
NORMAL DISPLAY 13 34 SHUNT** NO REPLY 2
147 SUBCURR = #####A SHUNT** BAD TYPE 2
NORMAL DISPLAY NO ALARMS
147A BAT CHG = #####A 34A BAT CL INHIBITED 2
0 SYSTEM OK
148 LVD ** = ##.#V
LVD** NO REPLY 1
149
LV RECON = ##.#V LVD** EPROM FAIL 1
MANUAL RECONNECT 35 LVD** A/D FAILED 1

A
LVD** RELAY FAIL 1
ANALOG TC OFF NOTES: LVD** NO MCA CMD 1
150 TC CAL = ##.##V 1 Major Alarm
TempCmp Hardware 36 LVDs INHIBITED 2
2 Minor Alarm
REMOTE NO REPLY
to Sheet 2
37 2
DIGITAL TC OFF 3 Minor Alarm = 1 PCU
150A SLOPE = .###V/°C Major Alarm = >1 PCU
TempCmp Hardware 38 DISPLAY NO REPLY 2
4 Minor Alarm = A or B

Major Alarm = A and B 38A TEMP** NO REPLY 1


150B MAX W/T = ##.##V
5 Minor Alarm = Sense Fuse

150C MIN W/T = ##.##V Major Alarm = System Fuse


39 MAIN ALARM MENU
6 ## = Substitute appropriate number 8
HI TEMP** = ###°C 40 NORMAL DISPLAY
150D
HI TEMP** IS OFF 7 ** = Scroll through appropriate numbers 8

8 Applies to all menu items


150E
LO TEMP** = ###°C
LO TEMP** IS OFF 9 Applies to all "Adjustable Settings"

151 ****A PLACES = ## 10 All "Adjustable Settings" indicate changeable parameter


Color Code
11 Exit to menu item 0 or 1 if all PCU serial #s match
152 START THE SYSTEM
12 Exit to menu item 0 or 1 if some PCU serial #s match Initializing Normal Configuration Menu
13 All "Normal" menu items lead to item 0 or 1

14 MCA P/N 534878 Only


Measurements Adjustment Menu Function
15 MCA P/N 534871 Only Adjustable Settings Alarms Calibration Menu
16 Press ACO/UP/DOWN simultaneously to reach this item.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 109 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
from Sheet 1 NETSURE™ MCA Menu Tree
A (Sheet 2 of 2)
MEASUREMENT MENU SYSTEM LOAD MENU

61 SYSTEM ###.##VDC 86 SYSLOAD** #####A


FUNCTION MENU 62 SYS LOAD #####A 87
MEASUREMENT MENU

41 MEASUREMENT MENU 63 PCU LOAD #####A 88 NORMAL DISPLAY


SET TEST/EQ MODE 64 SUBSYS ###.##VDC
42 SET FLOAT MODE
TestEq Switch On 65 SUB LOAD #####A
43 ADJUSTMENT MENU BAT CHG #####A PCU LOAD MENU
65A BAT CHGCL #####A
44 CONFIGURE MENU BAT DIS #####A 89 PCU** LOAD #####A
45 CALIBRATION MENU 65B T SENSOR** ###°C 90 MEASUREMENT MENU
46 NORMAL DISPLAY 66 FUNCTION MENU 91 NORMAL DISPLAY
67 NORMAL DISPLAY

CONFIGURE MENU
SUBSYSTEM LOAD MENU
73 VERIFY INVENTORY ADJUSTMENT MENU
SYSTEM ADJUSTMENT MENU 92 SUBLOAD** #####A
SHARE ALARM OFF
73A
SHARE ALARM ON 68 ADJUST SYSTEM 93
95 FLOAT = ###.##V MEASUREMENT MENU
EMERG STOP OFF 69 ADJUST ALARMS 96 TEST/EQ = ###.##V 94
NORMAL DISPLAY
73B EMERG STOP ON 70 ADJUST LVDs 97 SET HVS = ###.##V
REMOTE HVS OFF
REMOTE HVS ON
71 FUNCTION MENU
73D
99 CURR LIM = ####A
72 NORMAL DISPLAY CURRLIM = #####MAX
73C
DISPLAY ROLL OFF BATTERY LOAD MENU
DISPLAY ROLL ON BATTLIM DISABLED
99A
74 SET PCU ON / OFF BATTLIM = #####A 94A BAT** CHG #####A
BAT** DIS #####A
74A LO SPEED FAN OFF 100 100% CURR: ####A
LO SPEED FAN ON INVENTORY MENU 94B
MEASUREMENT MENU
101 ADJUSTMENT MENU
75 NAG MINUTES = ## PCU** TYPE ####A 94C NORMAL DISPLAY
AUDIBLE NAG OFF 118 PCU** TYPE ####+ 102 NORMAL DISPLAY
TEST/EQ HRS = ## NO PCUs FOUND
76 TEST/EQ MAN STOP
END TEQ ##.##HRS 119 VACANT ****A= ##
****A PLACES= ##
AUTO EQ DISABLED
76A AUTO EQ MUL = ## SHUNT** TYPE SYS ALARM ADJUSTMENT MENU
END AUTO ##.## HR 120 SHUNT** TYPE SUB
SHUNT** TYPE BAT SYS HV1 = ###.##V
77 RELAYTEST = ###SEC NO SHUNTS FOUND 103
HI FLOAT = ###.##V 15

77A
SET SPANISH TEXT
121 LVD** INSTALLED 104 SYS HV2 = ###.##V
78 FUNCTION MENU NO LVDs FOUND HI VOLTAGE = ###.##V 15

79 NORMAL DISPLAY ANALOG TC FOUND SYS BOD = ###.##V


105
121A T SENSOR** INST LO FLOAT = ###.##V 15
NO TEMP SENSORS
SYS 50% = ###.##V
122 SUBSYS INSTALLED 106 VERYLOVOLT = ###.## 14
NO SUBSYS FOUND
LO VOLTAGE = ###.##V 15
REMOTE INSTALLED
123 REMOTE ACTIVE
107 SYSCURR = #####A
NO REMOTE FOUND 108 SUB HV = ###.##V
124 UPDATE INVENTORY
PLEASE WAIT...
109 SUB LV = ###.##V
REPLACE ** PCUs? 110 SUBCURR = #####A
125
CONFIGURE MENU 110A BAT CHG = #####A
CALIBRATION MENU
126 NORMAL DISPLAY HI TEMP** = ###°C
80 CAL SYS = ###.##V 110B
HI TEMP** IS OFF
127 SPEC NO. #########
81 CAL SUB = ###.##V
LO TEMP** = ###°C
128 MCA SWV ######## 110C
LO TEMP** IS OFF
82 RESTORE MFG CAL
129 REM SWV ######## TEST RELAYS
ANALOG TC OFF
83 TC CAL = ##.##V 111 TESTING RELAY #
TempCmp Hardware Alarm(s) Active
112
PCU ENABLE MENU ADJUSTMENT MENU
DIGITAL TC OFF
83A SLOPE = .###V/°C 113
NORMAL DISPLAY
TempCmp Hardware PCU** ON:SET OFF
130 PCU** OFF:SET ON
83B MAX W/T = ##.##V Energy Mgmt. On LVD ADJUSTMENT MENU
131
83C MIN W/T = ##.##V CONFIGURE MENU 114 LVD ** = ##.#V

TCOMP ON SENSOR1
132 NORMAL DISPLAY LV RECON = ##.#V
115
83D TCOMP ON AVERAGE MANUAL RECONNECT
TCOMP ON HIGHEST 116
ADJUSTMENT MENU
84 FUNCTION MENU 117
NORMAL DISPLAY
85 NORMAL DISPLAY

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 110 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
1.3.16 External Alarm Circuits: Nine (9) Form-C alarm relay contacts are provided and mapped by the MCA as
detailed in the following table. Alarm relay contacts are rated for 0.5A at 125VAC, 1.0A at 30VDC, and 0.3A at
110VDC. Relay operation can be tested via an Alarm Relay Test feature. When activated, this feature
consecutively places each relay in the alarm state for the programmed time period.
• Refer to the "Making Electrical Connections" chapter of the Power System Installation Instructions
(Section 5974) for connection details.
• Refer to the "Navigating the MCA" and "System Operating Procedures" chapters of the Power System User
Instructions (Section 5975) for alarm conditions. Additional descriptions are provided in a) and b) below.
a) MCA Audible Alarm: These contacts change state if any alarm condition monitored by the MCA
occurs, and are provided for connection to an audible alarm circuit.
b) Test/Equalize Indication: These contacts change state if the system is placed in the test/equalize
mode, locally or remotely.

Power System
10 11 12 13
List No.
MCA
534876 534877 534878 534879
Configuration No.
Major Major Major Major
Relay K1
Alarm Alarm Alarm Alarm
Minor Minor Minor Minor
Relay K2
Alarm Alarm Alarm Alarm
High High High Test/EQ
Relay K3 Voltage 1 Voltage 1 Voltage 1 Mode
Alarm Alarm Alarm Indication 2
Rectifier
High MCA
Module Fail
Relay K4 Voltage 2 Fail Fuse Alarm
Major
Alarm Alarm
Alarm
Battery On Battery On Battery On Battery On
Relay K5 Discharge Discharge Discharge Discharge
Alarm Alarm Alarm Alarm
50% Rectifier
Very Low AC
Battery On Module Fail
Relay K6 Voltage Major
Discharge Minor
Alarm Alarm
Alarm Alarm
AC AC AC AC
Relay K7 Fail Fail Fail Fail
Alarm Alarm Alarm Alarm
Audible Audible
Relay K8 Fuse Alarm LVD Alarm
Alarm Alarm
Test/EQ Rectifier Test/EQ
Relay K9 Mode Fuse Alarm Module Fail Mode
Indication Alarm Indication
1.3.17 External Monitoring, Reference, and Control Signals
The MCA is connected to an “Interconnect/LVD Inhibit” circuit card. This circuit card provides spring-clamp type
terminals for connection of customer wiring, as described below.
(A) Remote Test/Equalize: All Rectifier Modules can be placed into the test/equalize mode by applying an
external ground signal. The Rectifier Modules operate in the float mode when the signal is absent.
(B) External "System Voltage" Meter Reading: Leads can be extended from the Power System to an external
voltage source. This is the voltage source the MCA monitors for system alarms and displays as "System
Output Voltage".
(C) External Voltage Sensing: Leads can be extended from the Power System to the point at which output
voltage is to regulate, such as the battery.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 111 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
(D) Emergency Shutdown and Fire Alarm Disconnect: Operation of the Rectifier Modules can be inhibited
through application of an external ground signal. Manual restart is required (by turning AC power to the
Rectifier Modules off then on, or by removing and re-inserting the Rectifier Modules). If low voltage
disconnect is furnished, the battery and system output can be wired to also disconnect from the
controlled load(s). If List RA is furnished, battery also disconnects from the system.
(E) System Fuse Alarm Input: The system fuse alarm circuit activates when a ±18 to 60 volts DC signal is
applied this terminal.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 112 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
MECHANICAL SPECIFICATIONS
Overall Dimensions
Refer to PD588705000 for Rectifier Module Mounting Shelf dimensions.
Refer to Table 1 for relay rack dimensions.
List 24 (Four Bus Row Cabinet)

Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(minus relay rack)
Four Bus Row Cabinet
Net:
Shipping: Top View
3. Finish: Textured Gray (M500-147)
17.50
24.75
(typical) 6.00 11.50

33.25
(19U)

Refer to PD588705000
for Rectifier Module
Mounting Shelf
dimensions.

Left Side View Front View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 113 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 23 (Three Bus Row Cabinet)
Refer to Table 1 for relay rack dimensions.
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(minus relay rack)
Three Bus Row Cabinet
Net:
Shipping: Top View
3. Finish: Textured Gray (M500-147)
17.50
24.75
(typical) 6.00 11.50

26.25
(15U)

Refer to PD588705000
for Rectifier Module
Mounting Shelf
dimensions.

Left Side View Front View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 114 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 22 (Two Bus Row Cabinet)
Refer to Table 1 for relay rack dimensions.
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(minus relay rack)
Two Bus Row Cabinet
Net:
Shipping: Top View
3. Finish: Textured Gray (M500-147)
17.50
24.75
(typical) 6.00 11.50

19.25
(11U)

Refer to PD588705000
for Rectifier Module
Mounting Shelf
dimensions.

Left Side View Front View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 115 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 21 (One Bus Row Cabinet)
Refer to Table 1 for relay rack dimensions.
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(minus relay rack)
One Bus Row Cabinet
Net:
Shipping: Top View
3. Finish: Textured Gray (M500-147)

17.50
24.75
(typical) 6.00 11.50

12.25
(7U)

Refer to PD588705000
for Rectifier Module
Mounting Shelf
dimensions.

Left Side View Front View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 116 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 31 (Rectifier Module Mounting Shelf), List 45 or 46 (Top Mount AC Termination Panel), List 80 (LMS1000 Monitoring
System), List 92 (Battery Stands), and List RC, RD, and RE (Battery Disconnects)

Notes:
1. All dimensions are in inches,
unless otherwise specified.
3. Finish: Textured Gray (M500-147) except
Rectifier Shelf and Rectifier Module Bodies:
Bright Zinc Plating (M500-53)
Rectifier Module Face Plates are
Textured Gray (M500-147)
5. Housing present only if equipped with
List RC, RD, RE (Battery Diconnects).
6. Housing present only if equipped with
List 45 or 46 (Top Mount AC Termination Panel). Knockouts Sized
7. See SAG586505500 for LMS1000 for 3/4" Conduit Fittings
Monitoring System (List 80) dimensions. See Note 5
8. See PD588705000 for Rectifier Module
Mounting Shelf (List 31) dimensions.
9. See PD588820000 for Battery See Note 6 See Note 6
Stand (List 92) dimensions.

See Note 6
Top View 8.25
See Note 5 5.25

6.88
See Note 6

15.44 See Note 5

See Note 7

See Note 8

Left Side View Front View Rear View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 117 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
List 93 (Battery Tray)
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
(per tray, less batteries)
With Circuit Breaker Option
Net: 33
Shipping:
Without Circuit Breaker Option
Net: 29
Shipping:
Optional Battery Disconnect Circuit Breakers 3. Finish: Textured Gray (M500-147)
(Shown on Right Side, Available on Either Side) 4. Maximum trays available per rack is four (4).

Distribution Cabinet
Not Shown

9.781

12.25
or
14.00
(as ordered)

12.25
or
14.00
(as ordered)

12.25
or
14.00
(as ordered)

24.437
ISO View Front View Right Side View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 118 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Optional Digital Battery Charge Temperature Compensation Probe (P/N 107021 and 106824)
0.25 (6.35) DIA.

0.75
(19.05)

3.00 (76.2)

0.75 (19.05) 2.25 (57.15)

300 (7,620)
0.35 (8.89) or
1200 (30,480)

Part No. 107021 (25 foot)


Part No. 106824 (100 foot)
Note: All dimensions are in inches and (millimeters).

Optional Analog Battery Temperature Probe (P/N 521262)


PROBE
ATTACH TO NEGATIVE BATTERY TERMINAL
(CLEARANCE FOR 5/16 (7.94) HARDWARE)

180 ±3.00 (4,572 ± 76)

NOTE: All dimensions are in inches and (millimeters).

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 119 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Electrical Connection Locations and Dimensions
Input Battery
Connections to Lists 21 through 24 Distribution Cabinets
Note: Battery busbars within distribution cabinets are rated for 2000A max.
For 2000A-4000A in List 2, make additional battery connections to interbay busbars.
3/8-16 CAPTIVE NUT, 14 PLACES (CUSTOMER MUST
SUPPLY LUG, BOLTS, AND ADDITIONAL HARDWARE.
BOLT LENGTH: 1-1/4")
1/4-20 CAPTIVE NUT, 20 PLACES (CUSTOMER
MUST SUPPLY LUG, BOLTS, AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")

0.625 2.000
TOP OF
Central DISTRIBUTION
Office 0.750
CABINET
Ground 0.625 2.000

1.000

0.625

BATTERY BATTERY
(RETURN SIDE) 0.625 0.625 0.750 (LOAD SIDE)
BUSBAR BUSBAR
0.750 0.750 0.750
0.625 0.625

FRONT VIEW
GND RTN -48V SUPPLY

(One Row
Cabinet Shown,
Others Similar)

ISO View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 120 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Optional Battery Busbar Extension Kit P/N 514713
Installed in Lists 21 through 24 Distribution Cabinets
Note: See Battery Busbar Extension Kit (P/N 514713) under ACCESSORY DESCRIPTIONS for description.
3/8 CLEARANCE HOLES, 12 PLACES (CUSTOMER MUST SUPPLY LUG,
BOLTS, AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

2.000 2.000
2.000 2.000

TOP OF
1.000 DISTRIBUTION
Central CABINET
Office
Ground

BATTERY BATTERY
(RETURN SIDE) (LOAD SIDE)
BUSBAR FRONT VIEW
BUSBAR

GND RTN -48V SUPPLY

(One Row
Cabinet Shown,
Others Similar)

ISO View

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 121 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Optional Battery Busbar Extension Kit P/N 529143
Installed in Lists 21 through 24 Distribution Cabinets
Note: See Battery Busbar Extension Kit (P/N 529143) under ACCESSORY DESCRIPTIONS for description.
3/8 CLEARANCE HOLES, 24 PLACES
(CUSTOMER MUST SUPPLY LUG, BOLTS,
AND ADDITIONAL HARDWARE.
Central TOP OF DISTRIBUTION CABINET
BOLT LENGTH: 1-1/4")
Office
Ground 1.312 1.312

1.000

48V

FRONT
VIEW

GND RTN
-48V SUPPLY

BATTERY BATTERY
(RETURN SIDE) (LOAD SIDE)
BUSBAR BUSBAR

Plastic Shield

(One Row
Cabinet Shown,
Others Similar)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 122 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Optional Battery Landing Busbar Kit P/N 541371
Installed in Lists 21 through 24 Distribution Cabinets
Note: See Battery Busbar Extension Kit (P/N 541371) under ACCESSORY DESCRIPTIONS for description.

1/4-20 x 0.875" Studs


on 0.625" Centers,
24 Places (Customer must
supply additional hardware.)

Rear View

(Two Row
Cabinet Shown,
Plastic Shield Others Similar)

-48V SUPPLY GND RTN


Up to Six (6) Battery Leads (per polarity)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 123 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Interbay Busbars (P/O List 2)
Note: Battery busbars within distribution cabinets are rated for 2000A max.
For 2000A-4000A in List 2, make battery connections to interbay busbars, shown here.

Battery Lug
Landing Points
See Detail A

GND RETURN
Interbay Busbar Assembly

-48V SUPPLY
Interbay Busbar Assembly

3/8-16 CAPTIVE NUT, 8 PLACES PER BUS


(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

2-3/8" 2-3/8" 2-3/8"


13/16" 13/16"
13/16" 13/16"

Rear View

1" 5/8"

3/4" 3/4" 3/4"

1-5/8" 1-5/8"

1/4-20 CAPTIVE NUT, 12 PLACES PER BUS


(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")
DETAIL A

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 124 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Battery Disconnect Circuit Breakers
and Low Battery Voltage Disconnect Options
Refer to the illustrations located under the Bus Module and Low Battery Voltage Disconnect List descriptions in this
document.

Load Distribution
Refer to the illustrations located under the Bus Module List descriptions in this document.

AC Input
Connections to 588705000 Rectifier Module Mounting Shelf(s)
Refer to the documentation package furnished with the Rectifier Module Mounting Shelf.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 125 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Optional List 45 Top Mount AC Input Termination Panel (Single-Phase)

See See
Detail A Detail B

Rear

Rectifier (PCU) Shelves are Number


from #1 to #6 from Top to Bottom

Rectifiers (PCUs) are Numbered


from #1 to #6 from Left to Right
as Viewed from the Front of the System

GND GND
AC Cover BAR AC Cover BAR
Removed Removed
in Illustration in Illustration

SHELF 2 SHELF 1 SHELF 1 SHELF 2


PCU4 PCU5 PCU6 PCU4 PCU5 PCU6 PCU1 PCU2 PCU3 PCU1 PCU2 PCU3
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

SHELF 4 SHELF 3 SHELF 3 SHELF 4


PCU4 PCU5 PCU6 PCU4 PCU5 PCU6 PCU1 PCU2 PCU3 PCU1 PCU2 PCU3
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

SHELF 6 SHELF 5 SHELF 5 SHELF 6


PCU4 PCU5 PCU6 PCU4 PCU5 PCU6 PCU1 PCU2 PCU3 PCU1 PCU2 PCU3
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

Inside View Inside View


Detail A Detail B

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 126 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
Connections to Optional List 46 Top Mount AC Input Termination Panel (Three-Phase)

Rear

Rectifier (PCU) Shelves are Number


Cover Cover
from #1 to #6 from Top to Bottom
Removed Removed
Rectifiers (PCUs) are numbered 1-6 from
left to right as viewed from the front.

GND GND
BAR BAR

SHELF 3 PCU4-6 SHELF 2 PCU4-6 SHELF 1 PCU4-6 SHELF 1 PCU1-3 SHELF 2 PCU1-3 SHELF 3 PCU1-3
ØC ØB ØA ØC ØB ØA ØC ØB ØA ØA ØB ØC ØA ØB ØC ØA ØB ØC

SHELF 6 PCU4-6 SHELF 5 PCU4-6 SHELF 4 PCU4-6 SHELF 4 PCU1-3 SHELF 5 PCU1-3 SHELF 6 PCU1-3
ØC ØB ØA ØC ØB ØA ØC ØB ØA ØA ØB ØC ØA ØB ØC ØA ØB ØC

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 127 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
External Alarm, Reference, and Control
External alarm, reference, and control connection points are located on…
• The optional List 80 LMS1000 Monitoring System (refer to the documentation furnished with the LMS1000 for
connection point locations),
• J1-J4 on the optional List 71 Audible Alarm and Alarm Termination Circuit Card P/N 524734,
• TB1 on circuit card P/N 509532,
• J8 on circuit card P/N 534868 (if List 71 not installed).

JI
(Typical location on Modem or RS-485
crcuit card, Ethernet and RS-232/Modem
card slightly different configuration.)

VIEW WITH DOOR OPEN LOOKING


DOWN AT BOTTOM OF CABINET

J8 Front
TB1
J4 J1 J2 J3

ALARM TERMINATION/ INTERCONNECT/


MCA MAIN CONTROLLER
AUDIBLE ALARM LVD INHIBIT CIRCUIT CARD,
CIRCUIT CARD, P/N 534868
CIRCUIT CARD, P/N 524734 P/N 509532
(MAIN BAY ONLY)
(LIST 71 OPTION) (ALL BAYS)
(MAIN BAY ONLY)

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 128 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
RELATED DOCUMENTATION
Power Data Sheets: PD588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf)
System Application Guides: SAG588249700 (Model MHSB160CAB Converter Mounting Shelf)
Schematic Diagrams: SD582126000 (NetSure™ Power System)
SD588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf)
SD528409 (1-Row Distribution Cabinet)
SD528414 (2-Row Distribution Cabinet)
SD528419 (3-Row Distribution Cabinet)
SD528340 (4-Row Distribution Cabinet)
Wiring Diagrams: T582126000 (NetSure™ Power System)
T588705000 (Model PSS4850-23GV Rectifier Module Mounting Shelf)
T528409 (1-Row Distribution Cabinet)
T528414 (2-Row Distribution Cabinet)
T528419 (3-Row Distribution Cabinet)
T528340 (4-Row Distribution Cabinet)
Color MCA Menu Tree: Section 6022
Instructions: Section 5974, System Installation Instructions
(NetSure™ Power System, Spec. No. 582126000)
Section 5975, System User Instructions
(NetSure™ Power System, Spec. No. 582126000)
Section 5823, Installation and User Instructions
(Capacitor Precharge Assembly, Spec. No. 510142)
Section 5940, Installation and User Instructions
(Battery Temperature Probe Concentrator Module, P/N 521211)
Section 5949, Installation Instructions
(MCA Interface Option Kits)
Section 5982, User Instructions
(MCA Ethernet Interface Option -
Using Ethernet Card Web Interface)
UM1R483500e, Rectifier Instructions
Load and Battery 031110100
Lug Detail Drawings: 031110200
031110300

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 129 Revision BA, November 23, 2020
NetSure™ 701NVBB DC Power System
System Application Guide
BATTERY MANUFACTURER INFORMATION
Some equipment described in this System Application Guide is designed to accommodate batteries from various
manufacturers. The following are referenced in this document.
C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858
Deka®: East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147
Douglas®: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159
Fiamm: FIAMM T.I, 23880 Industrial Park Drive, Farmington Hills, Detroit, MI 48335
MarathonTM: GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543.
Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803
PowerSafe EnersysTM: EnerSys Inc., Reading, PA, 196212-4145

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and
logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and
completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or
omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.

Spec. No: 582126000 SAG582126000


Model No: 701NVBB 130 Revision BA, November 23, 2020