Day5 IPED2024 ValueBasedOffer
Day5 IPED2024 ValueBasedOffer
[email protected] [email protected]
Wide Portfolio for the Ultra Low Harmonic & Regenerative Drives
Low Harmonic content, <3% THDi Unity Power Factor, at all loads Reactive Power Control
The drive produces exceptionally low harmonic content and ABB’s ultra-low harmonic drives have been designed to be ABB’s ultra-low Before compensation After compensation
exceeds the requirements of harmonic recommendations, neutral from the network point of view. Drive reaches unity harmonic drives
such as IEEE 519 and G5/4. The total harmonic current power factor. This high power-factor indicates that electrical have the built-in Active power
Active power
distortion is typically <3% in nominal situation and energy is used efficiently. feature for
undistorted network. reactive power
compensation, Reactive power
Reactive power
Diode supply Active supply 0,7 1 without any Q Q
additional
components
P P
Standard 6-pulse drive ABB ultra-low harmonnic drive
cosφ = 0,80 cosφ = 0,95
without input choke
What is THDi?
– THDi is the total harmonic distortion of the current waveform
– The total amount of harmonics is expressed as a THD% value
Why lower THDi is better?
– Less heating, less losses, lower energy cost
– Less heating, less premature component failures, longer
lifetime
– Less disturbances on the network, less interference with other
components, more reliable and stable system
What it says in the spec and how to comply?
– referring to standards IEEE519:2014 or G5/4
– THDi limit < 8% → Offer majority as ULH drives
– 8%< limit < 40% → Offer minimum amount of ULH, Calculate
system harmonics
– If limit >40% → Use 6-pulse units
4.5 %
4.0 %
Line Active
supply unit
filter 3.5 % THDi <
3.0 % 3%
2.5 %
2.0 %
M
1.5 %
1.0 %
0.5 %
0.0 %
50 150 250 350 450 550 650 750 850 950 1050 1150 1250 1350 1450 1550 1650
❑ ABB’s ultra-low harmonic drives have been designed to be neutral from the network point of view.
• Drive reaches unity power factor. This high power factor indicates that electrical energy is used efficiently.
❑ The lower the power factor, the more reactive power the network needs to provide.
• Larger equipment (cables, switchgears, transformers) is required to supply power 1
• Operating costs are higher PFtotal = cos fundamental
THD + 1 2
0.7 1
Standard 6-pulse drive without input choke ABB ultra-low harmonic drive
Active power
Active power
Reactive power
Reactive power
Q Q
P P
• Due to low harmonic content, transformer load ability is 1. When also 0.7
efficiencies, power factor and voltage drop are taken into account,
k - factor
0.6
apparent power required to be supplied by the transformer is
0.5
dimensioning. 0.1
0
500 1000 1500 2000 2500 3000 4000
ULH drive
Up to 25% smaller transformers sizing Sn (kVA)
+
Ultra-low
harmonic drive
Un
Flux:
… voltage drop is critical because the motor may not have enough f
torque to start the load!
Supply voltage Voltage drop over supply cables Input voltage Motor voltage
400 V 370 V 370 V
Transformer 6-pulse drive Motor
Supply voltage Voltage drop over supply cables Input voltage Motor voltage
400 V 370 V 400 V
Transformer ABB ULH drive Motor
10%
harmonic
content
Network Passive filter 6-pulse drive Actual motor efficiency due to drive Motor voltage after Network eff x PF eff x Drive eff x Motor eff
Supply voltage
efficiency efficiency efficiency waveform and lower motor voltage system losses = 0.98 x 0.985 x 0.98 x 0.92 =
400 V/480 V
~ 98% 98.5%1 98% 92% ~ 370 V/ 450 V 87%
5%
harmonic
content
Supply voltage Network Active filter 6-pulse drive Actual motor efficiency Motor voltage after Network eff x AF eff x Drive eff x Motor eff
400 V/480 V efficiency rated efficiency efficiency at nominal motor voltage system losses = 0.98 x 0.97 x 0.98 x 0.92 =
~ 98% 97% 98% 92% ~ 380 V/ 460 V 85.7%
3%
harmonic
content
Network ABB AFE drive Actual motor efficiency Motor voltage after Network eff x Drive eff x Motor eff
Supply voltage
efficiency efficiency at nominal motor voltage system losses = 0.98 x 0.97 x 0.925 =
400 V/480V
~ 98% 97% 92.5% ~ 400 V/ 480 V 87.9%
ABB regenerative drives have all inside: line filter, active supply unit and
inverter come in one extremely compact package Resistor braking
• Small footprint Drive Chopper Resistor Cooling
• No need for additional engineering
• No need for additional braking choppers or resistors + + +
• No need to add cooling to remove the heat generated
by mechanical or resistor braking
• Possibility for cabinet free installation
Regenerative braking
Line Filter Active Supply Unit Inverter Unit
+ +
Benefits
• Share braking energy in DC link
• Return excess braking energy to the supply
Common DC link
• ACS880-11/14 rated for continuous full power regeneration
• Voltage stabilization feature maintains constant DC link voltage
even if AC supply voltage is unstable
• Connection to supply network is clean; Meets IEEE519,
IEC61000-3-12 and G5/5 harmonic standards at all load
conditions
• Unity power factor reduces supply losses
—
Harmonic Estimator
Results
Real time calculation summary is shown in Colour coding makes it easy to wether
right side of the main view. the total values meet the requirements
or not
Calculated Current Total Demand
Distortion (TDD) compared to limit / Green colour and symbol indicates that
recommendations. calculated value is under the limit
Calculated Voltage Total Harmonics
Red colour and symbol indicates that
Distortion (THD) compared to limit /
calculated results are exceeding the
recommendations.
limits
Short circuit current and load current
ratio Limit/Recommendation is shown next
after calculated value and valid for short
Primary side summary is always visible circuit ratio
Secondary side summary is shown if the
PCC is at secondary side of transformer
S
l ©July
202424,
ABB.2024
All rights reserved. Slide 21
i
CONFIDENTIAL
—
Harmonic Estimator
Report sheet
Project data, results, Harmonics content in Harmonic components in Network, loads and details
statements and notes graphical form numerical form
Offered in ACS580 / ACH580 / ACQ580 Ready to use Plug and Play wall mount unit
Available in IP21 or IP55 ingress protection ABB Standard design and dimensions
Offered in Inline design in R1 to R4 (upto 45kW) Built-in protection devices and disconnect option
Offered with separate IP55 disconnector box in All-Compatible features and parameterization
R5 to R8 (45kW to 160kW)
Fully enclosed design for human and machine safety
How to calculate motor efficiency with VSD supply Performance at nominal speed
if only motor DOL efficiency is known? IE class acc. Motor Typical IE3
to IEC TS efficiency with induction
Add additional losses as given in IEC TS 60034-30-2 60034-30-2 VSD supply motor
• 15% additional losses for motors up to 90kW TN=100% efficiency with
Output kW Type designation Product code nN=100% VSD supply1
• 25% additional losses for motors above 90kW 1500 r/min (50 Hz) 400 V network
15 kW IE3 motor DOL efficiency 92,1% 5.5 M3AL 132SMA 4 3GAL132213-•SC IE5 93.7 88.2
Same motor with VSD supply 91,0% 7.5 M3AL 132SMB 4 3GAL132223-•SC IE5 93.7 89.1
This is the right value to compare against SynRM 11 M3AL 132SMC 4 3GAL132233-•SC IE5 94.2 90.2
94,8% 11 M3BL 160MLA 4 3GBL162413-•SC IE5 94.0 90.2
Typical IE3 induction motor efficiency with VSD supply are precalculated in SynRM catalogue