Saved Configuration ITM509-XXXX Model Number ITM509-00XXXXXX

ITM 509 Intelligent Transformer Monitor Configuration Form


Company Name: Date:
Contact Person: E-mail:
Billing Address: Requested Delivery Date:
Shipping Address: Quantity:
Telephone #: Fax #:
End User: Site:

Qualitrol Contact Information: [email protected] (USA) 585-586-1515, option “1” Fax: 585-377-0220

509 INTELLIGENT TEMPERATURE MONITORS


(All Clip on CT Current Sensors are supplied with unit, all other sensors must be ordered separately)
ITM509-100 Basic Intelligent Temperature Monitor
BASE SYSTEM ITM509-200 Cooling Monitor (Requires a minimum of one current input to monitor fan motor current)
(CHECK ONE)
ITM509-300 Load Tap Changer Monitor (Recommend a minimum of one current input to monitor LTC motor current)

MOUNTING AND HEATER SECTION


Standard Fiberglass NEMA 4X Enclosure (14”h x 12”w x8”d) With 5KV Surge Protection With High Vibration Mounting
Fiberglass NEMA 4X Enclosure (18”h x 16”w x10”d) With 5KV Surge Protection
Enclosure Steel NEMA 3R Enclosure (22”h x 15”w x 11”d) With 5KV Surge Protection
(Check One) Panel Mount (13”h x 11”w x 3”d) With 5KV Surge Protection
19” Rack Mount (Panel Mount Unit with a Rack Mounting Kit
With 5KV Surge Protection
KIT-035-1, SOLD SEPARATELY,14”h x 19”w x 3”d, excl. handles
Graphic Overlay STANDARD (Standard, French or Eaton)

Heater None 120 VAC 240 VAC


(Check One)

Form 0-954 Revision I Page 1 of 17 QUALITROL Company LLC


Saved Configuration ITM509-XXXX Model Number ITM509-00XXXXXX
PRIMARY SENSOR INPUT SECTION

* L & M are for self-powered transducers, N & O are for unpowered transducers.

Form 0-954 Revision I Page 2 of 17 QUALITROL Company LLC


Saved Configuration ITM509-XXXX Model Number ITM509-00XXXXXX

Expansion Module Sensor Input Section


Expansion Module Input Modules
(Up to 8 additional inputs can be installed)

SELECT FUNCTION NAME


FOR LCD
ITM 509 7 CHARACTERS
REF MAXIMUM

INPUT 9 X

INPUT 10 X

INPUT 11 X

INPUT 12 X

INPUT 13 X

INPUT 14 X

INPUT 15 X

INPUT 16 X

 
Please mark ALL boxes.
Choose X for Empty slots. Can be changed in
Please show amps after configuration
C_ or I_, e.g. C10 for 10 software
amp CT.

Form 0-954 Revision I Page 3 of 17 QUALITROL Company LLC


MODULE REFERENCE TYPE “V” – TAP POSITION
3RD PARTY DEVICE SIGNAL TYPES DESCRIPTION (CHOOSE ONLY ONE)

0 to 125 VDC

0 to 48 VDC

Unpowered (Dry Bridge)


Resistor Bridge Supply Voltage
(Requires an existing resistor 0 to 10 VDC
Bridge/Network to Detect Tap Position) +/- 10 VDC
0 to 5 VDC

+/- 5 VDC

0 to 1 VDC
OR
0 to 1mA DC
Current Output
(Requires a “Third Party” Device that
generates a current output proportional
4 to 20mA DC
to Tap Position)
FRONT PANEL LAYOUT SECTION

RELAY DESIGNATION FOR FRONT PANEL

(12 Character maximum, including spaces)

(Defaults to RELAY 1 through RELAY 8 if not specified)

PHASE A
PHASE B
PHASE C

SPARE

SPARE

SPARE

SPARE
SPARE

NOTE: RELAY DESIGNATIONS ARE


PERMANENTLY SEALED BEHIND
OVERLAY AND CANNOT BE CHANGED
ONCE INSTALLED
DIRECT WINDING Yes No

Units of CAB-699-4 at 4 Meters Length


Units of CAB-699-6 at 6 Meters Length
1 Neoptix© T2™ Fiber Optic Temperature Sensors Units of CAB-699-7 at 7 Meters Length
Units of CAB-699-8 at 8 Meters Length
Units of CAB-699-10 at 10 Meters Length
Bolt On
Steel (standard)
Tank Wall Plate Assembly (PLT-202)
2 or
(Includes COV-121-1 and CON-159-1**) Weld On
Stainless Steel
(PLT-201)
Units of CAB-700-5 at 5 Meters Length
Units of CAB-700-7 at 7 Meters Length
3 Fiber Optic Extension Cable
Units of CAB-700-10 at 10 Meters Length
Units of CAB-700-15 at 15 Meters Length
Units of MOD-638-4 with 4 Channels per Unit
Hot Spot Module Channels*
4 Units of MOD-638-6 with 6 Channels per Unit
( Interface between fibers and ITM 509)
Units of MOD-638-8 with 8 Channels per Unit
Portable Fiber Optic Thermometer Optional Accessory (KIT-057-1)

* The first 16 fiber inputs are digitally connected to the 509. If more than 16 inputs are needed, please contact your Applications Engineer.
** Optical Feed Through connectors (CON-659-1) are available separately as well.
COMMUNICATIONS SECTION

What remote communications protocols do you need?


ITM Manager Protocol Configuration software (Included)
DNP 3.0 level 3, Slave For use with SERIAL or TCP/IP options
MODBUS For use with SERIAL or TCP/IP options
ASCII For use with SERIAL or TCP/IP options
IEC 60870 For use with SERIAL or TCP/IP options
IEC 61850 For use with TCP/IP options ONLY

What remote communications ports do you need?


Analog SCADA Outputs Four fully programmable milliamp outputs (Included)

RS-485 2- or 4-wire connectivity (Included)


Serial

Fiber optics Echo and Repeat, Standard ST connection

Copper Ethernet TX, RJ45 Connection


(Does not include FX)

Fiber Optic Ethernet FX, ST Connection


TCP/IP *

(Multimode Transducer)
(Purchase of FX includes TX)
Required for IEC 61850
Fiber Optic Ethernet FX, SC Connection;1300 nm
(Single mode Transducer- Only 1 FX module may be
installed)
(Purchase of FX includes TX)

*Only one Ethernet(Copper or Fiber optic) port can be active at one time – either TX or FX.
NERC-CIP COMPLIANCE MODULE(* REQUIRES ETHERNET)

Below table lists the NERC-CIP sections and their description that our ITM509 monitor will be compliant with if the above module is purchased.
SECTION DESCRIPTION

CIP-003 R6 Configuration and Change management

CIP-004- R4 List/Audit personnel with cyber rights

CIP-005 R1.4 Protect ALL ESP devices(prevent stepping stone)

CIP-005 R2 Restrict traffic, implicit deny at AP

CIP-005 R3 Monitor and Logging access at AP

CIP-005 R4 Perform Cyber-vulnerability assessment of AP

CIP-005 R5.3 Preserve logs>= 90 days

CIP-007 R4 Malicious Software detection

CIP-007 R6 Monitor Cyber System Events

CIP-008 R2 Cyber-security incident document/retention

CIP-009 R4 Recovery Plans for CCA(backup and restore)


SOFTWARE SECTION

What control, alarm, and analysis function do you need?

TransLife™ Includes automatic Consumed Life, Critical Forecast, and Temperature Profiler functions
(Included)

Low Temperature Lockout – minimizes static electrification and arcing by ensuring pumps remain off (ambient
sensor sold separately) (Included)

Pre-cooling – limits damaging high temperatures produced by overloads by initiating cooling early
Advanced Cooling (Included)
Control Seasonal Setback – customize cooling schemes based on the time of the year (ambient sensor sold
separately)

Adaptive Ambient Control – adaptive cooling based on ambient temperature forecast (ambient sensor sold
separately)

Logs up to 20 parameters with a selectable sample rate and 256 Mb of non-volatile internal memory
Data Logging
(e.g., 14 parameters, sampled and stored once a minute, will be logged for 90 days before being overwritten.)

Event Recording Records time and date or a complete system snap shot, capable of storing over 60,000 events
All the following software options are field configurable and are not
required to create a model number.
Default options shown will be preselected.

All accessories shown must be ordered separately.


ADDITIONAL ACCESSORIES SECTION
(All Accessories and Sensors Selected Here Must Be Ordered as Separate Line Items on Purchase Order and Will Be Invoiced as Such)

Yes
Hard Copy of Instruction Manual (All units come standard with an electronic copy)
Quantity

Representative Connector Connector


Accessory: Units Qty.
Model Number Units Length

100 Ω 103-023-01
Traditional RTD Sensor Standard RTD Well Mount 7/8 - 14 thread, 513/16 Feet
inch length Meters
10 Ω 103-022-01

100 Ω 103-044-XX Feet


New Universal One Piece RTD/Cable Assembly
10 Ω 103-045-XX Meters
Magnetic Clamp-on Pt100 RTD with 25 ft. cable 25’
100 Ω 103-025-01
(Order in pairs if used for Differential Temperature Function) (Standard)
Magnetic Clamp-on Pt100 RTD with 50 ft. cable 50’
100 Ω 103-025-02
(Order in pairs if used for Differential Temperature Function) (Standard)
Traditional Ambient RTD 100 Ω 103-049-01 Feet
Traditional Ambient RTD 10 Ω 103-026-01 Meters
100 Ω 103-047-XX Feet
New Universal One Piece Ambient RTD/Cable Assembly
10 Ω 103-046-XX Meters
Thermal Well For Well Mounted RTDs With Outside Thread of: 3/4” 167-50-3L
Thermal Well For Well Mounted RTDs With Outside Thread of: 1/2” 167-50-3D
Thermal Well For Well Mounted RTDs With Outside Thread of: 7/8” 167-50-3E
DISSOLVED GAS ANALYSIS ACCESSORIES SECTION
(All Accessories and Sensors Selected Here Must Be Ordered as Separate Line Items on Purchase Order and Will Be Invoiced as Such)

Accessory: Medium Model Number Qty.

Gas DGA-150-G-1 ea
Single Gas Hydrogen Sensor Drain valve mount, 1 ½” NPT thread union fitting – THREAD MOUNT
Oil DGA-150-L-1 ea

Gas DGA-250-G-1 ea
Single Gas Hydrogen Sensor, with Pressure Sensor, 2 ½” NPT thread union fitting – THREAD MOUNT
Oil DGA-250-L-1 ea
Gas DGA-400-G-1 ea
Single Gas Hydrogen Sensor, with Pressure Sensor – FLANGE MOUNT
Oil DGA-400-L-1 ea

Hydrogen Sensor Universal Power Supply – 24VDC – 1 per DGA sensor required PWR-025-1 ea

Sensor cable, 13 Conductor, 3 twisted pairs, plus power CAB-295-1 ft or m


Sensor cable, 10 Conductor, 2 twisted pairs, plus power CAB-295-2 ft or m
Sensor cable, 5 Conductor, 1 twisted pair plus power CAB-295-3 ft or m
CONFIGURATION COMMUNICATION ACCESORIES SECTION

RS232 Cable, 6 ft. (CAB-044-1 will appear as separate line item) Yes?
RS232 Cable, 10 ft. (CAB-044-2 will appear as separate line item) Yes?
USB to DB-9, 1 ft. (CAB-049-1 will appear as separate line item) Yes?
USB-A TO USB-B, 6 ft. (CAB-050-1 will appear as separate line item) Yes?

CONFIGURATION ACCESORIES SECTION

Interposing Relays(REL-042-1) (model number) QTY

SERVICE, TRAINING, MAINTENANCE CONTRACT AND EXTENDED WARRANTY OPTIONS


509 Commissioning – One day on-site 509 installation supervision, setup and commissioning (W-509-COMMIS) Yes
(up to two 509s per site per day) No
509 On-site Training - (EDU-509-CUST)
Yes
This one-day course for six students covers the basic hardware installation, configuration, and maintenance for the 509 series monitors.
Additional topics include 509 features, system capabilities, using the maintenance configuration port and system level troubleshooting.
No
509 Web Training – EDU-509-WEB
This four-hour course for up to ten students covers an overview of basic transformer heating concepts, 509 hardware, its benefits in Yes
extending transformer life and monitoring real-time values. Configuration of the device is also covered in detail, leaving the student with a No
complete understanding of the transformer monitoring device.
Yes
1 -Year Extension of the Standard warranty beyond a period of 5 years from date of purchase at a cost of 2% of purchase price. (SERVICE-1YR)
No
Yes
2- Year Extension of the Standard warranty beyond a period of 5 years from date of purchase at a cost of 4% of purchase price. (SERVICE-2YR)
No
Yes
3- Year Extension of the Standard warranty beyond a period of 5 years from date of purchase at a cost of 6% of purchase price. (SERVICE-3YR)
No
Yes
4- Year Extension of the Standard warranty beyond a period of 5 years from date of purchase at a cost of 8% of purchase price. (SERVICE-4YR)
No
OUTPUT RELAY PROPERTIES SECTION (Defaults are preselected, all are field configurable)

Select the following properties for each relay: RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 RELAY 6 RELAY 7 RELAY 8

Enabled Yes Yes Yes Yes Yes Yes Yes Yes


No No No No No No No No
Failsafe Yes Yes Yes Yes Yes Yes Yes Yes
(switch is open when power is off) No No No No No No No No
Test Lock Out On On On On On On On On
(Relay will not activate in Test Mode) Off Off Off Off Off Off Off Off
Latching On On On On On On On On
Off Off Off Off Off Off Off Off
Manual On On On On On On On On On
(Off = Automatic) Off Off Off Off Off Off Off Off
Actuates on Errors Yes Yes Yes Yes Yes Yes Yes Yes
No No No No No No No No
Seasonal Set Point Yes Yes Yes Yes Yes Yes Yes Yes
No No No No No No No No
Ambient Temperature Forecast Yes Yes Yes Yes Yes Yes Yes Yes
No No No No No No No No
Cooling Equipment Exerciser On On On On On On On On
Off Off Off Off Off Off Off Off
OUTPUT RELAY CONTROL LOGIC SECTION (Defaults are preselected, all are field configurable)

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 50 OR
Relay 1

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 60 OR
Relay 2

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 70 OR
Relay 3

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 80 OR
Relay 4

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS
MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No
SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 90 OR
Relay 5

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 100 OR
Relay 6

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 110 OR
Relay 7

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No

SETTINGS Input 1
Input or Relay # Input or Relay # Input or Relay # OR Input or Relay #
OR
Set Point 120 OR
Relay 8

Matrix Control Hysteresis 10


AND AND
Activation
AND
Direction UP DOWN UP DOWN UP DOWN UP DOWN
MINUS
MINUS
Alarm Control ITM509-200 or ITM-300 Alarm Yes No
OUTPUT CURRENT LOOP SETUP SECTION (Defaults are preselected, all are field configurable)

Enabled Yes No 1st Input # 2nd Input # 3rd Input #


0 — 1 mA
Current Loop Type 4 — 20 mA
Loop Output Other 1
OR OR

#1 Custom Range
Maximum
Input #
MINUS
Yes No
Minimum Input # Input #

Enabled Yes No st
1 Input # nd
2 Input # rd
3 Input #
0 — 1 mA
Current Loop Type 4 — 20 mA
Loop Output Other 1
OR OR

#2 Custom Range
Maximum
Input #
MINUS
Yes No
Minimum Input # Input #

Enabled Yes No st
1 Input # nd
2 Input # rd
3 Input #
0 — 1 mA
Current Loop Type 4 — 20 mA
Loop Output Other 1
OR OR

#3 Custom Range
Maximum
Input #
MINUS
Yes No
Minimum Input # Input #

Enabled Yes No st
1 Input # nd
2 Input # rd
3 Input #

Current 0 — 1 mA
Loop Type 4 — 20 mA
Loop Output Other 1
OR OR

#4 Custom Range
Maximum
Input #
MINUS
Yes No Minimum Input # Input #