Basic Elect - Mod.E-09 (CABLES)
Basic Elect - Mod.E-09 (CABLES)
Basic Elect - Mod.E-09 (CABLES)
MODULE E- 9
Cables
[email protected]
Basic Training Course Cables & Joints Electrical
1. General
Cables form an important part of any installation but, because they are static,
and in normal service are very reliable, they do not always receive the attention
that they deserve.
2 Power Cables
Cables are designed for both high voltage and low-voltage transmission of
power. Though the general construction is similar in both cases, high-voltage
cables have thicker insulation and usually have smaller conductors, since low-
voltage cables carrying bulk power handle the heavier Currents. مهم
Fig.1
Three Core Power Cable
[email protected]
Basic Training Course Cables & Joints Electrical
2.2 Conductors
The size of the copper conductor forming one of the cores of a cable is
expressed in square millimeters (mm2), and the current rating of the
cable is dependent upon the cross-sectional area of each core. The very
smallest cables have conductors consisting of only one strand of copper;
larger cables however have stranded conductors consisting of many
individual strands or wires laid up together; this gives flexibility, allowing
the cable to be bent more readily during installation. To achieve a circular
conductor, the number of strands follows a particular progression: 3, 7,
19, 37, 61, 127 etc, the diameter of each strand being chosen to achieve
the desired cross-sectional area of tile whole conductor.
As seen in Figure 2, 3-core and 4-core cables in the larger sizes have
conductors with the strands laid up in a segmental formation; this
achieves a better space factor and reduces the overall diameter of the
cable. It also reduces the inductance of the cable due to decreased
spacing between phases.
Fig.2
Segmental Cores
[email protected]
Basic Training Course Cables & Joints Electrical
[email protected]
Basic Training Course Cables & Joints Electrical
Fig.3
Voltage Gradient Across High Voltage Cable Insulation
Core insulation may be coloured red, yellow, blue and black to identify the
three phases and neutral. Twin cores are coloured red and black. Single-
core cables are identified by coloured PVC tape applied to the outer
sheath.
2.5 Bedding
The bedding consists of a layer of PVC extruded over the core insulation
as a base for the armouring.
2.6 Armouring
[email protected]
Basic Training Course Cables & Joints Electrical
The outer sheath of extruded PVC protects the armouring and the cable
against moisture and generally provides an overall protective covering.
[email protected]
Basic Training Course Cables & Joints Electrical
[email protected]
Basic Training Course Cables & Joints Electrical
3 Control Cables
Mineral-insulated (MI) cables are used where the integrity سالمهof a circuit is of
great importance. They are particularly resistant to fire and are used in
circuits, such as communications or emergency lighting, which must continue
operational as long as possible after fire has broken out. They are also very
robust and resistant to mechanical damage.
Fig.4
Mineral Insulated Two Core Cable
[email protected]
Basic Training Course Cables & Joints Electrical
(Reference) (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
Abbreviation 0.6/1kV STR CU/PVC/PVC/SWA/PVC/HO2/HCL
3-core, l50mm2
[email protected]
Basic Training Course Cables & Joints Electrical
The last two items (9 and 10) indicate the flammability and the toxicity of the
synthetic materials used in the cable. HO2 indicates that a high level of oxygen
is required to sustain يعززcombustion: in the case of the Shell specification this
means more than 30% oxygen in the atmosphere. HCL denotes 'Hydrochloric
Level' showing that, when the synthetic materials burn, they produce
hydrochloric acid gas (HCI) which is highly poisonous and very corrosive.
In particular PVC, when burnt, releases large quantities of HCI and also
produces dense black smoke; for example, a 1m Iength of cable containing, say,
6kg of PVC can completely black out a room 1000m3 in site within five minutes of
the fire starting.
6 Installation
[email protected]
Basic Training Course Cables & Joints Electrical
Fig.5
Single Core Cables Laid in Trefoil
At any instant in time the net magnetic flux outside the group of cables
due to the three line currents in them approximates to zero because of
the symmetrical cable Iayout.
[email protected]
Basic Training Course Cables & Joints Electrical
Fig.6
Low Voltage Cable Termination
Conductors are terminated either with lugs bolted to the fixed bushing stems
as shown in Figure 6 or, for heavier currents, with cylindrical ferrules which are
clamped into terminal blocks. In either case the terminations are crimped onto
the conductors using either hand or hydraulic crimping tools. To make a good
connection it is vital that the lug or ferrule is the correct size for the
particular conductor and that the correct die is used in the crimping tool.
[email protected]
Basic Training Course Cables & Joints Electrical
Fig.7
High Voltage Cable Termination
The conductor of a single-core cable and its surrounding metallic armouring act
as a current transformer having a 1:1 turns ratio; load current passing through
the conductor produces a magnetic flux which, linking with the wires of the
armouring, induces an emf in them. If a circuit is provided between the
armouring at one end of the cable and at the other, a current flows in the
armouring which, if sufficiently large, causes heating. This is shown in Figure
8(a).
To control these circulating currents insulated cable gland adapters are used
whereby the body of the gland, and consequently the wire armouring of the
cable, is electrically isolated from the earthed gland plate of the cable box by a
layer of insulation. Figure 8(b) shows a 3-phase circuit run with single-core
cables using insulated cable glands. To control the voltage of the armouring it
must be bonded to earth; this is done by deliberately bridging the gland
insulation using bonding links. The armouring can be bonded in one of two ways.
In Figure 2.8{a) it is bonded at both ends of the cable run (shown in red); the
emf induced in the armouring causes currents (IA) to circulate in the armouring
which in heavy current circuits may lead to an undesirable temperature rise in
the armouring. Alternatively, the armouring may be bonded at one end only as in
Figure 2.8(b); there is no circuit for current to flow, but a voltage (EA) is
developed across the gland insulation at the unbonded end. Where one end of
the circuit is in a hazardous area, it is customary to bond this end so that any
arcing that may occur due to emfs induced in the armouring can only take place
in the non-hazardous area.
[email protected]
Basic Training Course Cables & Joints Electrical
There is one other magnetic problem associated with single-core cables: where
such cables enter a cable box or pass through partitions the conductors must
pass through holes in the gland plate. If these plates are made of a magnetic
material such as steel, the magnetic fields due to the load currents in the
conductors induce eddy currents in the gland plate which may cause it to
become very hot. For terminating or passing a.c. circuits using single-core
cables, gland plates of non-magnetic material must be used.
Fig. 8
Insulated Cable Glands
[email protected]
Basic Training Course Cables & Joints Electrical
Control cables are also terminated using compression glands. The sheathing and
armouring are stripped back to leave tails of the required length. Each core is
identified using plastic ferrules bearing the wire number, and terminated using a
crimped connector. The cores are either laced up into suitable runs using plastic
cable ties, or secured to cable racks within a control panel.
Standard colours are used in Shell installations to identify the system to which
the various cables belong; they are:
[email protected]
Basic Training Course Cables & Joints Electrical
Types of Cables
[email protected]
Basic Training Course Cables & Joints Electrical
Abbreviations