Ducts Pressure Losses Board: CFM 201 M 30.00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT: ROSHN SEDRA 1B SITE : RIYADH

DUCT NAME : EX.F-05 BUILDING : TYPICAL

GENERAL DATA
DUCT MATERIAL : G. I. Sheet
ROUGHNESS COEF. : 0.93
ALTITUDE : 640 Meters
ALTITUDE COEF. : 0.935
AIR DENSITY : 1.09 Kg/m3
DUCTS PRESSURE LOSSES BOARD
SECTION 1 2 3 4 5 6 7 8 TOTAL
FLOW CFM 201
FLOW M3/H 341.7
LENGTH M 30.00 30.0 ml
DIAM. mm 206.77
DIAM. EQUIV. 206.77
WIDTH mm 400
HEIGHT mm 100
AREA M2 0.03
VELOCITY M/S 2.83
PD per Meter Pa 0.60
PD x LENGTH Pa 17.85 17.85 Pa

Co 1 2 3 4 5 6 7 8 TOTAL
ELBOW 30° 0.07
ELBOW 45° 0.09
ELBOW 90° 0.15 4
TEE 45° 0.3
TEE 90° 1 5
END TEE 1.5
BRANCH TEE 0.05
TRANSITION 0.22 2
CONTRACTION 0.05

TOTAL Co 6.04 6.04


DUCTS PD Pa 26.30 26.30 Pa
PRESSURE DROP Pa 44.16 44.16 Pa

SPECIAL FITTING PRESSURE DROPS


0.64 W.g
DESIGNATION PD (PA) QTY TOTAL 159 Pa
FIRE DAMPER 10 1 10 342 m³/h
VOLUME DAMPER 10 2 20 44 Pa
SUPPLY GRILLE 15 115 Pa
EXHAUST GRILLE 10
FRESH AIR LOUVER 20 0.70 W.g
SAND TRAP LOUVER 100 175 Pa
ALUMINUM FILTER 80 376 m³/h
BAG FILTER 150 49 Pa
GREASE FILTER 100 127 Pa
DUCT HEATER 5
DISC EXHAUST VALVE 70 1 70 0.77 W.g
FLEXIBLE DUCT CONNECTION 15 1 15 191 Pa
SOUND ATTENUATOR 40 413 m³/h
TOTAL 115 Pa 53 Pa
138 Pa

FAHU ESP Calculations.xlsx - EX.F-05 G.M.RAYEES 4/7/2024 Page 1