AKM 345 Gen2 Instruction Manual (Rev No.

ECN-27992)

The AKM 345 TD50(5 AMP) option allows for the input of up to 5 amps winding temperature
simulation current without the expense or additional wiring required by an external matching
unit. It is available with up to 4 switches. The 5 amp option employs an internal CT which
accepts 5 amps at the primary and outputs 2.2 amps at the secondary. The secondary
current is in parallel with a standard TD50 matching resistance and heater. For temperature
rise calculations please refer to Figure 3.

• Accuracy of 2.2A output at 5A input:


+/-5% at 0 - 1.6 secondary load
+/-10% at 1.6 - 1.8 secondary load
• Max continuous primary current: 6A
• Max primary current: 10 a for 2 minutes

5.5. Setting the Matching Resistance


There are two methods of setting the matching resistance depending on the accuracy
required. Use Method A for maximum ease of use and Method B for maximum accuracy.

5.5.1. Method A
• Disconnect the white separable connector and using an ohmmeter at the "R" pins,
adjust the matching resistance to meet the target R5-5 value which will provide the
desired heater current (see Section 5.1 instructions).
• Re-connect the white separable connector. After the matching resistance has been set
and the white connector is re-mated, the winding simulation input current is wired to
the terminal block at the 5-5 positions as shown.

5.5.2. Method B
• Disconnect the white separable connector and using an ohmmeter at the “R” pins,
adjust the matching resistance to meet the target R5-5 value which will provide the
desired heater current (see Section 5.1instructions).
• Jumper between one pin of the "R" connector and one pin of the “I” connector, and
connect an ammeter between the remaining two pins, as shown.
• Input the desired primary current at positions 5-5 on the terminal block and note the
current flowing in the circuit. You now have the exact ratio of input to output current at
secondary load. Disconnect power before disconnecting the ammeter and jumper– the
secondary leads must always be connected in-circuit or shorted when the CT is
powered.
• Using the measured secondary current, re-calculate the desired R5-5 value which will
provide the exact heater current necessary for the desired winding simulation. Using
an ohmmeter at the “R” pins, adjust the matching resistance to meet this R5-5 value.

7 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

• Re-connect the white separable connector. After the matching resistance has been set
and the white connector is re-mated, the winding simulation input current is wired to
the terminal block at the 5-5 positions as shown.

TD50 HEATER
POT

WHITE CONNECTOR
"FEMALE PINS"

R
JUMPER
Ammeter to 5-5 POSITIONS

I
WHITE CONNECTOR
"MALE PINS"
BLK WHT
Optional
Current
OUT 2.2A CT IN 5A

Measurement BLK WHT

Figure 4.2 – TD50 / 5 Amp Wiring Example

8 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

6. Mounting Styles and Dimensions


6.1. Seismic Mount

Figure 5 – Siesmic Mount

Special mounting for high amplitude, low frequency conditions

6.2. Universal Mount

Figure 6 – Universal Mount

Adaptor plate for many different mounting bolt patterns

9 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

6.3. Anti-Vibration (Standard) Mount

Figure 7 – Anti-Vibration (Standard) Mount

Standard mounting, highest instrument isolation available

10 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

7. Front Cover Removal


11.88 [302]

4.09
[104] 3.68 [93]

11.93
[303]

Figure 8 – Cover Hinge Side View

Figure 9 – Front Cover Removal

Cable glands: M25 (max 3) and M20 (max 2)

After unlocking the front cover, lift the front cover up fully, slide the top cover to
the right and remove. To refit, reverse the above instructions.

11 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

8. Contact Rating / Breaking capacity


RATED RESISTIVE INDUCTIVE
VOLTAGE LOAD LOAD
125 VAC 15 A 15 A
250 VAC 15 A 15 A
STANDARD
30 VDC 15 A 10 A
SWITCH
125 VDC 0.75 A 0.4 A
250 VDC 0.3 A 0.3 A
125 VAC 10 A 6A
250 VAC 3A 1.5 A
MBO 30 VDC 10 A 10 A
125 VDC 10 A 6A
250 VDC 3A 1.5 A
30 VDC 0.1 A -
GOLD
125 VDC 0.1 A -
125 VAC 10 A 6A
250 VAC 10 A 4A
DPDT 30 VDC 10 A 4A
125 VDC 0.5 A 0.05 A
250 VDC 0.25 A 0.03 A
125 VAC 15 A 15 A
250 VAC 15 A 15 A
GW 30 VDC 6A 5A
125 VDC 0.5 A 0.05 A
250 VDC 0.25 A 0.03 A
Figure 10 – Switch Selection

• MBO = Magnetic Blow Out, high DC switching, minimum Electrical Operations =


100,000 Cycles, all others 500,000 cycles minimum.
• GOLD = Typically used for low current low voltage applications, e.g., SCADA or
computer connections.
• DPDT = Double Pole Double Throw, 2 x changeover contacts.
• GW = Similar to Gold and used for high DC voltage and low current applications.

Switch Selection: Select switch type (default is 15A), this will be applied to all
switches. Select the number of switches to be adjustable, (default is 0), then
select the switch differential of the remaining switches. This will automatically
default to 12± 2°C.

12 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

9. Terminal Block Arrangements

Figure 11 – 2 to 4 Switches w/Optional Heater and Remotes

Figure 11.1 – 2 to 4 Switches w/Optional Heater and Remotes


(TD50 5 Amp)

Figure 11.2 – 2 to 4 Switches w/Optional Heater and Remotes


(Double Gradient)

13 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

Figure 12 – 5 to 6 Switches only

Figure 13 – 5 to 6 Switches w/Optional heater and Remotes

For options not shown, please consult Configuration Form or contact


QUALITROL Customer Service Centre.

14 www.qualitrolcorp.com
AKM 345 Gen2 Instruction Manual (Rev No. ECN-27992)

10. Pocket/Well Installation

Figure 14 – Pocket/Well Installation

15 www.qualitrolcorp.com