SWP Series Measure Indicate Control
SWP Series Measure Indicate Control
MAIN FEATURES:
. All new concept of digitized automatic adjustment
. Support multi-units data communications, user-programmable protocol
. Unique fully accessible user-programmable setting
. Setting of input signal . Setting of zero and range of measuring value
. Alarm setting . Setting of outputs
. Parameters saved in memory to against power failure and password protection
. Total digitized cold-junction compensation
.Variety of external dimensions
.AC/DC switching power supply
1. SPECIFICATIONS:
2. OPERATION THEORY
(1)Input Signal Conversion and Indication:
The thermoemf from thermocouple or the resistance of RTD is converted to the voltage signal through the
input circuit (Stansdard signal through electrical filter circuit), it will be fed to the amplifier after the interference of
high frequency signal is filtered by the anti-disturbance circuit.
The DC amplifier, which composed of high accuracy, low zero shifting linear amplifier and multi-switching
circuit with microprocessor-based automatic zero adjustment will eliminate efficiently, the zero shifting caused by
the amplifier internally and will amplify the input signal to a preset value, and then fed to the Analog
Digital(A/D)converter.
The A/D converter which made of accurate 4 1/2 digit double integral type A/D converter, has high
anti-disturbance and good linearity characteristic. The DC voltage signal amplified, which is converted to the
corresponding pulses signal by the A/D converter, will be fed into the microprocessor(CPU).
2
NEW SWP Series MC Based Digital Controllers
The computing (conversion between thermo-electric and function, adjustment of non-linearity, etc.)in the CPU
depending on the input type which set by the instrument, the result of computing will be converted to the
corresponding BCD code and the scanning signal of positioning, as well as the display of LED.
NAME DESCRIPTION
. recording previous set value
Parameter Setting Selection Key . change parameters setting mode in turn
. change display or parameters setting
. used for increment the value when changing setting continuous
Operation Setting Point Decrement Key
depressing will increment quickly
Key
. used for decrement the value when changing setting continuous
Setting Point Increment Key
depressing will decrement quickly
Reset Key
. used for program zeroing (self-testing)
(Not be shown on Front Pane)
. display measuring value
Display Measuring Value PV Display . display symbol or setting value when in the parameter setting
mode
. light on when high alarm ON
First Limit Alarm Indicator . light on when input wire broken
Indicator . out-of-limit indicator when used in time ratio mode
. light on when low alarm ON
Second Limit Alarm Indicator
. output indicator when used in time ratio mode
4. OPERATION
(1). Flow Chat of Operation
* display input type and symbol
Power On Self Test at Start Up
* display input range
(3). Power on
There is not power switch on the unit, therefore, the unit will be start-up as soon as power is connected.
4
NEW SWP Series MC Based Digital Controllers
When PV displays the measuring value, depress SET key, the parameter setting mode is entered, the
symbol AL1 of Alarm1 parameter will be displayed.
When PV displays AL1, depress SET key, PV will display the manufacturer’s preset value of Alarm 1.
When PV displays preset value of Alarm 1 ,press setting value increment key, PV value will be
increased quickly. Adjust the value to 100.
5
NEW SWP Series MC Based Digital Controllers
Depress SET key, accept the correct setting value and go to the next parameter setting. The parameter
setting of Alarm 1 is done.
. using the same method, you can continue to set AL2, ALH1, ALH2, etc. as well as locking
(CLK)parameter settings.
Note:
• After parameter is changed, the value must be stored by pressing the SET key.
• If parameter value can not be modified, because of the locked parameter setting, you need to change
the CLK value to 00 for unlocking.
• To set the negative value, depressing the DECREMENT key to reduce setting value toward zero,
continue pressing the key, the negative value will be appeared.
• As soon the parameter are accepted, they will be kept permanently even though the power is
removed.
6.OUTPUT
(1). Description of AL1 and AL2
7. EXAMPLES:
Heating System Control
Requirement: Control Temperature 800℃
. High Alarm 820℃; . Low Alarm 790℃
. High/Low Relay Output Hysteresis 3℃
Sensor Type: Thermocouple E
Unit Selection: SWP-C803-01-E-HL
(1). Operation
Check all the connections are correct, power on and unit goes to working condition.
Confirm that the specification, input type and range, are met the requirement.
(2). Parameter Setting
1).Alarm 1 (AL1)Setting
Press SET key, when PV displays the measuring value, PV display change to:
7
NEW SWP Series MC Based Digital Controllers
In this Situation, pressing INCREMENT/DECREMENT key to change setting value to meet the control
requirement. In this example the setting value is 3℃.
AH1 ——LOCK/UNLOCK
Press SET key again, PV display changes to:
In this Situation, pressing INCREMENT/DECREMENT key to change setting value to meet the control
requirement. In this example the setting value is 1.
Note:
. Now, all the parameter settings are locked and no parameters can be changed. If you need to modify the
parameters, unlocking can be done by setting CLK to 00.
. After finishing the parameter modifications, pressing SET key to accept the changes, the parameter setting
will complete.
. Return to operation mode , the modified parameters will be used for the real time control by the instrument.
(2)The selection of frequency, the filters’ characteristics are the important factors to obtain a good noise
reduction.
1)It is efficacious against noise induction to twist the power wires. The shorter pitch of the twisted wire, the
better noise reduction.
2)It is necessary for the filter to install on the panel with good grounding, and minimize the distance of wire
connection between filter and instrument power terminals.
Note: Long distance wire connection between filter and instrument power terminal will greatly reduce the
efficient of the filter.
3)If the fuses is installed in the line of filter output, the efficient of filter will also be greatly reduced.
4)Use wires with National Standard Code (using wire with cross area 1.5-2.0mm2 , and minimized its
connection distance to ground).
5)There is 2-3 seconds delay on the contact output after power on. If the contact output is used for the signal
of external loop, it is recommended that time delay relay should be used.
8
NEW SWP Series MC Based Digital Controllers
9.WIRING DIAGRAM
Note: The wiring diagram for the special model instruments, please refer to wiring diagram put on the instrument.
★ output method:
Code 0 1 2 3 4 5 6 7 8
Output No Relay SCR SSR Special
4~20mA 0~10mA 1~5V 0~5V
method output contacts Output Output Output
9
NEW SWP Series MC Based Digital Controllers
★ Input Type:
Measure Measure Measure
Code Input type Code Input type Code Input type
Range Range Range
01 B 400~1800 ℃ 09 Pt100.1 -99.9~199.9℃ 17 30~350Ω -1999~9999 d
02 S 0 ~1600 ℃ 10 Cu50 -50.0~150.0 ℃ 18 Special By user
03 K 0 ~1300 ℃ 11 Cu100 -50.0~150.0 ℃ 19 4~20 mA s.r. -1999~9999 d
04 E 0 ~1000 ℃ 12 4~20 mA -1999~9999 d 20 0~10mA s.r. -1999~9999 d
05 T -200~400 ℃ 13 0~10 mA -1999~9999 d 21 1~ 5 V s.r. -1999~9999 d
06 J 0 ~1200 ℃ 14 1~5 V -1999~9999 d 22 0~5 V s.r. -1999~9999 d
07 WRe 0 ~3200 ℃ 15 0~5 V -1999~9999 d 23 Switch input
Frequency
08 Pt100 -200~650 ℃ 16 0~20 mA -1999~9999 d 24 0~5kHz
input
11. SETTING the 2nd PARAMETERS
Under the state of setting the 1st parameters, after changing CLK =132, press SET key again
Warning! Non-engineering designer is NOT allowed to change the 2nd
parameters. Otherwise the instrument will control in error!
till the parameter CLK appears and the value is 132. Then loosen SET key. Again, simultaneously
press key and key for 30 seconds, the instrument goes into the state of setting the 2nd
parameters. Under this state, every time pressing SET key will switch as the following order (turn
after turn).
The 2nd parameters are listed as follows:
Set Range
Parameter Name Explanation
(byte)
SL0 Input scale 0~20 .set type of input scale(NOTE :6)
SL1=0 .NO Decimal Point
SL1=1 . Decimal point is at tenth digit.(display XXX.X)
SL1 Decimal Point
SL1=2 . Decimal point is at hundredth digit(display XX.XX)
SL1=3 . Decimal point is at thousandth digit(displays X.XXX)
SL2=0 . No alarm
SL2 The 1st Alarm Type SL2=1 The 1st Alarm Type is Low limit alarm
st
SL2=2 .The 1 Alarm Type is High limit alarm
SL3=0 . No alarm
SL3 The 2st Alarm Type SL3=1 The 2st Alarm Type is Low limit alarm
st
SL3=2 .The 2 Alarm Type is High limit alarm
SL2.=0 . No alarm
SL2. The 3st Alarm Type SL2.=1 The 3st Alarm Type is Low limit alarm
st
SL2.=2 .The 3 Alarm Type is High limit alarm
SL3.=0 . No alarm
SL3. The 4st Alarm Type SL3.=1 The 4st Alarm Type is Low limit alarm
st
SL3.=2 .The 4 Alarm Type is High limit alarm
SL5=0 . NO flicker Alarm
SL5 flicker Alarm
SL5=1 . flicker Alarm
10
NEW SWP Series MC Based Digital Controllers
Set Range
Parameter Name Explanation
(byte)
11
昌 晖 自 动 化 系 统 有 限 公 司 制 造 商
CHARM FAITH AUTOSYSTEM CO.,LTD.
香港中环红棉路八号东昌大厦十七楼
17th Floor,Fairmont House,8 Cotton Tree Drive,Central,Hong Kong
Tel:00852-31190198 Fax:00852-25305488
Web:http://www.swp.com.cn Email: [email protected]