Lenze SMD Basic Manual
Lenze SMD Basic Manual
EN Operating Instructions
C0000
Copyright © 2005 AC Technology Corporation
All rights reserved. No part of this manual may be reproduced or transmitted in any form
without written permission from AC Technology Corporation. The information and technical
data in this manual are subject to change without notice. AC Technology Corporation makes
no warranty of any kind with respect to this material, including, but not limited to, the implied
warranties of it’s merchantability and fitness for a given purpose. AC Technology Corporation
assumes no responsibility for any errors that may appear in this manual.
All information given in this documentation has been carefully selected and tested for
compliance with the hardware and software described. Nevertheless, discrepancies cannot
be ruled out. We do not accept any responsibility nor liability for damages that may occur.
Any necessary corrections will be implemented in subsequent editions.
This document printed in the United States
Contents
1 Safety information.................................................................3
1.1 Pictographs used in these instructions......................................................4
2 Technical data.......................................................................5
2.1 Standards and application conditions.......................................................5
2.2 Ratings.......................................................................................................6
3 Installation.............................................................................7
3.1 Mechanical installation..............................................................................7
3.1.1 Dimensions and mounting.........................................................................7
3.2 Electrical installation..................................................................................8
3.2.1 Installation according to EMC requirements.............................................8
3.2.2 Fuses/cable cross-sections.......................................................................8
3.2.3 Connection diagram..................................................................................9
3.2.4 Control terminals......................................................................................10
4 Commissioning...................................................................11
4.1 Parameter setting.....................................................................................11
4.2 Electronic programming module (EPM)..................................................11
4.3 Parameter menu......................................................................................12
4.4 CANopen mapping details......................................................................23
4.4.1 RPDO mapping details (h66 / h76)..........................................................23
4.4.2 TPDO mapping details (h86 / h96)..........................................................26
4.5 Quick CAN set-up....................................................................................30
About these instructions
This documentation applies to the smd frequency inverter, and contains important technical data and
describes installation, operation, and commissioning.
These instructions are only valid for smd frequency inverters with software rev 20 (see drive
nameplate).
A B C D E F
C0001
• 1 smd inverter (ESMD...) After receipt of the delivery, check immediately whether the items
with EPM installed delivered match the accompanying papers. Lenze does not accept any
(see Section 4.2) liability for deficiencies claimed subsequently.
• 1 Operating Instructions Claim
• visible transport damage immediately to the forwarder.
• visible deficiencies/incompleteness immediately to your Lenze
representative.
© 2004 Lenze AG
No part of this documentation may be copied or made available to third parties without the explicit written approval of
Lenze AG.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and
software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for
damages that may occur. Any necessary corrections will be implemented in subsequent editions.
Safety information
1 Safety information
General
Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live,
moving and rotating. Some surfaces can be hot.
Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation
creates the risk of severe injury to personnel or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must
be carried out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100 and
IEC report 664 or DIN VDE0110 and national regulations for the prevention of accidents must be
observed).
According to this basic safety information, qualified skilled personnel are persons who are familiar with
the installation, assembly, commissioning, and operation of the product and who have the qualifications
necessary for their occupation.
Application as directed
Drive controllers are components which are designed for installation in electrical systems or machinery.
They are not to be used as appliances. They are intended exclusively for professional and commercial
purposes according to EN 61000-3-2. The documentation includes information on compliance with
the EN 61000-3-2.
When installing the drive controllers in machines, commissioning (i.e. the starting of operation as
directed) is prohibited until it is proven that the machine complies with the regulations of the EC Directive
98/37/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with
the EMC Directive (89/336/EEC).
The drive controllers meet the requirements of the Low Voltage Directive 73/23/EEC. The harmonised
standards of the series EN 50178/DIN VDE 0160 apply to the controllers.
Note: The availability of controllers is restricted according to EN 61800-3.These products can cause
radio interference in residential areas. In this case, special measures can be necessary.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and
do not change any insulation distances during transport or handling. Do not touch any electronic
components and contacts.
Controllers contain electrostatically sensitive components, which can easily be damaged by inappropriate
handling. Do not damage or destroy any electrical components since this might endanger your
health!
Electrical connection
When working on live drive controllers, applicable national regulations for the prevention of accidents
(e.g. VBG 4) must be observed.
The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-
sections, fuses, PE connection). Additional information can be obtained from the documentation.
The documentation contains information about installation in compliance with EMC (shielding, grounding,
filters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit values
demanded by EMC legislation.
Safety information
Operation
Systems including controllers must be equipped with additional monitoring and protection devices
according to the corresponding standards (e.g. technical equipment, regulations for prevention
of accidents, etc.). You are allowed to adapt the controller to your application as described in the
documentation.
DANGER!
• After the controller has been disconnected from the supply voltage, live components
and power connection must not be touched immediately, since capacitors could be
charged. Please observe the corresponding notes on the controller.
• Do not continuously cycle input power to the controller more than once every three
minutes.
• Please close all protective covers and doors during operation.
• Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum
(400/500 V devices) respectively
Warnings! • Use minimum 75 °C copper wire only.
• Shall be installed in a pollution degree 2 macro-environment.
Reference to an imminent
danger that may result in death
Warning of Hazardous
DANGER! or serious personal injury if the
Electrical Voltage.
corresponding measures are not
taken.
Technical data
2 Technical data
2.1 Standards and application conditions
Technical data
2.2 Ratings
Mains Output Current (3)
Power
Type
[kW] Current IN Imax for 60 s
Voltage, frequency
[A] (3) [A] (1) [A] (2) [A] (1) [A] (2)
1~ 3~ 3~ 3~ 3~ 3~
ESMD371C2YXA 0.37 1/N/PE 230 V OR 4.7 2.7 2.2 2.0 3.3 3.0
ESMD751C2YXA 0.75 3/PE 230 V 8.4 4.8 4.0 3.7 6.0 5.6
ESMD112C2YXA 1.1 (180 V -0%…264 V +0%) 12.0 6.9 6.0 5.5 9.0 8.3
ESMD152C2YXA 1.5 50/60 Hz 12.9 7.9 6.8 6.3 10.2 9.5
ESMD222C2YXA 2.2 (48 Hz -0%…62 Hz +0%) 17.1 10.8 9.6 8.8 14.4 13.2
ESMD302C2TXA 3.0 13.5 12.0 11.0 18.0 16.5
ESMD402C2TXA 4.0 3/PE 230 V 17.1 15.2 14.0 23 21
ESMD552C2TXA 5.5 (180 V -0%…264 V +0%) 25 22 20 33 30
ESMD752C2TXA 7.5 50/60 Hz 32 28 26 42 39
ESMD113C2TXA 11 (48 Hz -0%…62 Hz +0%) 48 42 39 63 58
ESMD153C2TXA 15 59 54 50 81 75
400V 480V 400V 480V 400V 480V 400V 480V 400V 480V
ESMD371C4TXA 0.37 1.6 1.4 1.3 1.1 1.2 1.0 2.0 1.7 1.8 1.5
ESMD751C4TXA 0.75 3.0 2.5 2.5 2.1 2.3 1.9 3.8 3.2 3.5 2.9
ESMD112C4TXA 1.1 4.3 3.6 3.6 3.0 3.3 2.8 5.4 4.5 5.0 4.2
ESMD152C4TXA 1.5 4.8 4.0 4.1 3.4 3.8 3.1 6.2 5.1 5.7 4.7
ESMD222C4TXA 2.2 6.4 5.4 5.8 4.8 5.3 4.4 8.7 7.2 8.0 6.6
3/PE 400/480 V
ESMD302C4TXA 3.0 8.3 7.0 7.6 6.3 7.0 5.8 11.4 9.5 10.5 8.7
(320 V -0%…528 V +0%)
ESMD402C4TXA 4.0 10.6 8.8 9.4 7.8 8.6 7.2 14.1 11.7 12.9 10.8
50/60 Hz
ESMD552C4TXA 5.5 (48 Hz -0%…62 Hz +0%) 14.2 12.4 12.6 11.0 11.6 10.1 18.9 16.5 17.4 15.2
ESMD752C4TXA 7.5 18.1 15.8 16.1 14.0 14.8 12.9 24 21 22 19.4
ESMD113C4TXA 11 27 24 24 21 22 19.3 36 32 34 29
ESMD153C4TXA 15 35 31 31 27 29 25 47 41 43 37
ESMD183C4TXA 18.5 44 38 39 34 36 31 59 51 54 47
ESMD223C4TXA 22 52 45 46 40 42 37 69 60 64 55
(1) For rated mains voltage and carrier frequencies 4, 6, and 8 kHz
(2) For rated mains voltage and carrier frequency 10 kHz
(3) Maximum current is a function of setting C90 (input voltage selection)
Installation
3 Installation
3.1 Mechanical installation
s2
b2
A 4 x M4
B 1.2 Nm
C 10 lb-in
b1
s1 s1
b
4 x M6
D 2.8 Nm
24 lb-in
s2
a1
a c
smd402
a a1 b b1 b2 c s1 s2 m
Type
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
ESMD371C2YXA
93 84 146 128 17 100 15 50 0.6
ESMD371C4TXA
ESMD751C2YXA
93 84 146 128 17 120 15 50 0.9
ESMD751C4TXA
ESMD112C4TXA 93 84 146 128 17 146 15 50 1.0
ESMD112C2YXA
114 105 146 128 17 133 15 50 1.4
ESMD152C4TXA, ESMD222C4TXA
ESMD152C2YXA, ESMD222C2YXA
ESMD302C2TXA 114 105 146 128 17 171 15 50 2.0
ESMD302C4TXA
ESMD402C2TXA
114 105 146 100 17 171 15 50 2.0
ESMD402C4TXA, ESMD552C4TXA
ESMD552C2TXA, ESMD752C2TXA
146 137 197 140 17 182 30 100 3.2
ESMD752C4TXA, ESMD113C4TXA
ESMD113C2TXA, ESMD153C2TXA
195 183 248 183 23 203 30 100 6.4
ESMD153C4TXA... ESMD223C4TXA
WARNING!
Drives must not be installed where subjected to adverse environmental conditions
such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive
vibration or excessive temperatures. Contact Lenze for more information.
Installation
Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint filter and the motor cable length does not B
exceed 10m
E
A Screen clamps
B Control cable C
C Low-capacitance motor cable A D
(core/core < 75 pF/m, core/screen < 150 pF/m)
Installation
L1 L2/N L1 L2/N L1 L2 L3
L1 L2 L3
0.5 Nm/ 4.5 lb-in 1.2 Nm/ 10 lb-in 2.0 Nm/ 18 lb-in
COM
+10V
+12V
COM
CAN
AIN
PES
PE PES
7 8 28 E1 E2 E3 7
M PES
3~
0 … 20 mA PE
4 … 20 mA + -
+12 VDC
… -0%
+30 VDC + 0 % C0002
Danger!
• Hazard of electrical shock! Circuit potentials are up to 240 VAC above earth ground.
Capacitors retain charge after power is removed. Disconnect power and wait until
the voltage between B+ and B- is 0 VDC before servicing the drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to
the drive will result.
• Do not cycle mains power more than once every three minutes. Damage to the
drive will result.
Installation
7 Reference potential
10
Commissioning
4 Commissioning
4.1 Parameter setting
C0003
NOTE
If the password function is enabled, the password must be entered into C00 to
access the parameters. C00 will not appear unless the password function is enabled.
See C94.
The EPM contains the controller’s memory. Whenever parameter settings are changed,
the values are stored in the EPM. It can be removed, but must be installed for the
controller to operate (a missing EPM will trigger an F1 fault). The controller ships with
Tmd007
protective tape over the EPM that can be removed after installation.
An optional EPM Programmer (model EEPM1RA ) is available that allows: the controller to be programmed
without power; OEM settings to be default settings; fast copying of EPMs when multiple controllers
require identical settings. It can also store up to 60 custom parameter files for even faster controller
programming.
11
Commissioning
C02 Load Lenze setting 0 No action/loading complete • C02 = 1...4 only possible with
OFF or 1nh
1 Load 50 Hz Lenze settings • C02 = 2 : C11, C15 = 60 Hz
4 Translate
WARNING!
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes
CE1...CE3.
NOTE
If an EPM that contains compatible data from a previous software version is
installed, C02 = 4 converts the data to the current version.
12
Commissioning
13
Commissioning
C11 Maximum output 50.0 7.5 {Hz} 240 • Output frequency at 100% analog
frequency setpoint
• C11 is never exceeded
WARNING!
Consult motor/machine manufacturer before operating above rated frequency.
Overspeeding the motor/machine may cause damage to equipment and injury to
personnel!
C12 Acceleration time 5.0 0.0 {s} 999 • C12 = frequency change 0 Hz...C11
• C13 = frequency change C11...0 Hz
C13 Deceleration time 5.0 0.0 {s} 999 • For S-ramp accel/decel, adjust c82
C14 Operating Mode 2 0 Linear characteristic with • Linear characteristic: for standard
Auto-Boost applications
• Square-law characteristic: for fans
1 Square-law characteristic with
and pumps with square-law load
Auto-Boost
characteristic
2 Linear characteristic with constant • Auto boost: load-dependent output
Vmin boost voltage for low-loss operation
3 Square-law characteristic with
constant Vmin boost
C21 Slip compensation 0.0 0.0 {%} 40.0 Change C21 until the motor speed no
longer changes between no load and
maximum load
C22 Current limit 150 30 {%} 150 • When the limit value is reached, either
the acceleration time increases or the
Reference: smd rated output current output frequency decreases
• When C90 = 2, max setting is 180%
C24 Accel boost 0.0 0.0 {%} 20.0 Accel boost is only active during
acceleration
14
Commissioning
C36 Voltage - DC 4.0 0.0 {%} 50.0 • See CE1...CE3 and c06
injection brake • Confirm motor suitability for use with
(DCB) DC braking
C87 Motor rated speed 1390 300 {RPM} 65000 Set to motor nameplate speed
c06 Holding time - 0.0 0.0 {s} 999 • Automatic motor braking below 0.1 Hz
automatic DC by means of motor DC current for the
injection brake 0.0 = not active entire holding time (afterwards: U, V,
(Auto-DCB) 999 = continuous brake W inhibited)
• Confirm motor suitability for use with
DC braking
c08 Analog output 100 1.0 999 When 10 VDC is output at terminal 62, it
scaling will equal this value (see c11)
15
Commissioning
c40 Frequency setpoint 0.0 0.0 {Hz} 240 Only active if C01 = 1
via keys
c42 Start condition 1 0 Start after LOW-HIGH change at See also c70
(with mains on) terminal 28
1 Auto start if terminal 28 = HIGH
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that is
inaccessible to personnel.
c60 Mode selection 0 0 Monitoring only c60 = 1 allows the keys to adjust
for c61 speed setpoint (c40) while monitoring
1 Monitoring and editing c61
c71 Auto-TRIP reset delay 0.0 0.0 {s} 60.0 See c70
16
Commissioning
2 transition to stopped
h46 Message monitoring 0 0 {ms} 65535 • h46 and h47 can be used to monitor
time all valid messages (e.g. SDO, SYNC,
PDO...)
h47 Message monitoring 0 0 Not active
• h46 = 0 or h47 = 0 disables message
time out reaction
1 Inhibit monitoring function
• h47 is only active when C01 = 3
2 Quick stop
17
Commissioning
h53(1) Parameter channel 2 0 0 Enable: Node ID range (1...63) • h53 = 0, 1: CAN address 1...63;
(SDO#2) with default COB ID for SYNC, 64...127 used for SDO2
RPDO, and TPDO • SDO#1 COB ID = 1536 + Node ID
• SDO#2 COB ID = 1600 + Node ID (if
1 Enable: Node ID range (1...63)
enabled)
with programmable COB ID using
h54, h60, h70, h80, h90
2 Disable: Node ID range (1...127)
with default COB ID for SYNC,
RPDO, and TPDO
3 Disable: Node ID range (1...127)
with programmable COB ID using
h54, h60, h70, h80, h90
h54(1) SYNC COB ID 128 0 2047 Note: Controller does not generate
SYNC object
h55(1) Boot up time 3000 0 {ms} 65535 Controller sends “NMT start all nodes”
message after this delay (active only
when h52 = 2)
h65 RPDO#1 time out 0 0 Not active Only active when C01 = 3
reaction
1 Inhibit
2 Quick stop
h66 (1) RPDO#1 mapping 0 0 C0135 control word + C46 signed C46 scaling: + 50 = + 1.0 Hz
(see RPDO mapping
1 C0135 control word + C46 C46 scaling: 10 = 1.0 Hz
details)
unsigned
2 402 Drives and Motion Control:
PDO Controlword 0x6040
3 402 Drives and Motion Control: • vl target velocity units = signed RPM
PDO Controlword 0x6040 + • RPM calculation based on C87 and
vl target velocity 0x6042 C89
4 C0135 Controlword + C46 scaling: +/- 16384 = C11
C46 signed and scaled +
Digital output + analog output
h69 RPDO#1 status 0 255 • Read-only
• Number of received RPDO#1
messages
• Above 255, starts over at 0
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”
19
Commissioning
h75 RPDO#2 time out 0 0 Not active Only active when C01 = 3
reaction
1 Inhibit
2 Quick stop
h76(1) RPDO#2 mapping 0 0 C0135 control word + C46 signed C46 scaling: + 50 = + 1.0 Hz
(see RPDO mapping
1 C0135 control word + C46 C46 scaling: 10 = 1.0 Hz
details)
unsigned
2 402 Drives and Motion Control:
PDO Controlword 0x6040
3 402 Drives and Motion Control: • vl target velocity units = signed RPM
PDO Controlword 0x6040 + • RPM calculation based on C87 and
vl target velocity 0x6042 C89
4 C0135 Controlword + C46 scaling: +/- 16384 = C11
C46 signed and scaled +
Digital output + analog output
h79 RPDO#2 status 0 255 • Read-only
• Number of received RPDO#2
messages
• Above 255, starts over at 0
20
Commissioning
h84 TPDO#1 event timer 0 0 {ms} 65535 • Sets the fixed interval for TPDO#1
transmission
• h84 = 0: disables event timer
h93(1) TPDO#2 inhibit time 50 0 {0.1 ms} 65535 Sets minimum time between TPDO#2
transmissions (h93 = 50 = 5.0 ms)
h94 TPDO#2 event timer 0 0 {ms} 65535 • Sets the fixed interval for TPDO#2
transmission
• h94 = 0: disables event timer
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”
21
Commissioning
n20 Power up state 0 0 Quick stop Selects controller power up state when
C01 = 3 (CANopen control)
1 Inhibit
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”
22
Commissioning
WORD1
23
Commissioning
DC brake DC brake
14 0 = DC brake not active 14 0 = DC brake not active
1 = DC brake active 1 = DC brake active
15 reserved 15 reserved
• Signed vl target velocity 0x6042 (RPM)
• RPM is calculated based on C87 and C89
• Example 1 (C87 = 1390 RPM, C89 = 50 Hz):
WORD1
(2)
Implemented as inhibit; all indicated bits must be in opposite state for controller to be enabled.
24
Commissioning
Direction of rotation
2 0 = CW (forward)
1 = CCW (reverse)
Quick stop
3 0 = Quick stop not active
WORD0 - C0135 control word
25
Commissioning
0 reserved 0 reserved
0 = Pulses to power stage enabled 0 = Pulses to power stage enabled
1 1
1 = Pulses to power stage Inhibited 1 = Pulses to power stage Inhibited
0 = Current limit not reached 0 = Current limit not reached
2 2
1 = Current limit reached 1 = Current limit reached
3 reserved 3 reserved
0 = Actual frequency < > setpoint 0 = Actual frequency < > setpoint
4 4
1 = Actual frequency = setpoint 1 = Actual frequency = setpoint
WORD0 - C0150 Status word
0 = Not above threshold (C17) WORD0 - C0150 Status word 0 = Not above threshold (C17)
5 5
1 = Above threshold (C17) 1 = Above threshold (C17)
0 = Actual frequency < > 0 Hz 0 = Actual frequency < > 0 Hz
6 6
1 = Actual frequency = 0 Hz 1 = Actual frequency = 0 Hz
0 = No controller inhibit 0 = No controller inhibit
7 7
1 = Controller inhibit 1 = Controller inhibit
8 8
9 Controller status 9 Controller status
0 = no fault 0 = no fault
10 8 = fault present 10 8 = fault present
11 11
0 = No overtemperature warning 0 = No overtemperature warning
12 12
1 = Overtemperature warning 1 = Overtemperature warning
0 = No DC bus overvoltage 0 = No DC bus overvoltage
13 13
1 = DC bus overvoltage 1 = DC bus overvoltage
Direction of rotation Direction of rotation
14 0 = CW (forward) 14 0 = CW (forward)
1 = CCW (reverse) 1 = CCW (reverse)
0 = Not ready 0 = Not ready
15 15
1 = Ready (no faults) 1 = Ready (no faults)
• Signed output frequency read from C50 • Unsigned output frequency read from C50
• Scaling = C50 x 50 • Scaling = C50 x 10
WORD1
WORD1
reserved
WORD3
reserved
26
Commissioning
5 reserved 5 reserved
6 reserved 6 reserved
7 reserved 7 reserved
8 reserved 8 reserved
Controller inhibit Controller inhibit
9 0 = No controller inhibit 9 0 = No controller inhibit
1 = Controller inhibit 1 = Controller inhibit
10 reserved 10 reserved
WORD1
reserved
WORD3
reserved
27
Commissioning
28
Commissioning
0 reserved
0 = Pulses to power stage enabled
1
1 = Pulses to power stage Inhibited
0 = Current limit not reached
2
1 = Current limit reached
3 reserved
0 = Actual frequency < > setpoint
4
1 = Actual frequency = setpoint
WORD0 - C0150 Status word
Direction = Sign(0x2C29) = CW
Frequency = ABS(0x2C29) * C11 /16384
= 11305*50/16384 = 34.5 Hz CW
• Example 2: WORD1 = 0xC70A, C11 = 50.0Hz
Direction = Sign(0xC70A) = CCW
Frequency = ABS(0xC70A) * C11 /16384
= 14582*50/16384 = 44.5 Hz CCW
Digital inputs status (TB28,E1,E2,E3)
WORD2
29
Commissioning
Example: Controller #2 needs to follow the operation of controller #1 (start/stop, speed, etc).
Controller #1 can be controlled by CANopen or traditional control elements (relays, etc).
After setting the parameters, perform Node reset using parameter h58 or cycle the power.
After these controllers are configured as above, controller #2 will follow the operation of
controller #1 including: Inhibit state, Quick Stop, DC brake, JOG speed selections, direction,
and speed. For additional safety, controller #2 will transition to inhibit state if valid PDO is
not received from controller #1 within 50ms.
30
Troubleshooting and fault elimination
1nh Inhibit Controller is set up for CANopen Start the controller via CANopen
(outputs U, V, W inhibited) operation (see C01)
stP Output frequency = 0 Hz Setpoint = 0 Hz (C31 = 0) Setpoint selection
(outputs U, V, W inhibited)
Quick stop activated through digital Deactivate Quick stop
input
br DC-injection brake active DC-injection brake activated Deactivate DC-injection brake
• via digital input • digital input = LOW
• automatically • automatically after holding time
c06 has expired
CL Current limit reached Controllable overload Automatically (see C22)
LU Undervoltage on DC bus Mains voltage too low Check mains voltage
dEC Overvoltage on DC bus during Excessively short deceleration time Automatically if overvoltage
deceleration (warning) (C13) < 1 s, OU, if overvoltage > 1 s
nEd No access to code Can only be changed when the Set terminal 28 to LOW or inhibit
controller is in OFF or 1nh through CANopen
(1) The drive can only be restarted if the error message has been reset; see c70
31
Troubleshooting and fault elimination
(1) The drive can only be restarted if the error message has been reset; see c70
32
Notes
33
Notes
34
Document
SC03B-en3