0% found this document useful (0 votes)
32 views60 pages

Aim 200

Uploaded by

mvargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views60 pages

Aim 200

Uploaded by

mvargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

FC-2000 Technical Manual 406

Addressable Intelligent Module Section


Technical Bulletin
Issue Date 0794

Introduction Page 3
Description 3
Inventory 4
Optional Peripherals 6

Installing the AIM-200 9


Installing the AIM-200 9
Wiring the Communications Loop Circuit 12
M500XJ Isolator Module 24
M500MJ Monitor Module 25
M501MJ Monitor Module 26
M500MJ and M501MJ Monitor Module Technical Notes 26
M510CJ Control Module 29
BGX-101 Addressable Manual Pull Station 33
Intelligent Detectors 34
Inserting the AIM-200 Cards 34

Programming the AIM-200 37


Programming Display 37
Auto-Program Mode 40

AIM-200 Power Requirements 41


Regulated Power Required in Standby 41
Regulated Power Required in Alarm 41

© 1994 Johnson Controls, Inc. 1


Order No. 406-080
AIM-200 Point Annunciation Page 43
Program Clear 44
Default Zone Map 45
Display Status 45
Program Edit 47
Alarm Bus 48
General Alarm Service 49
Backup Alarm Bus 50
Signal Silence Function 50
Operating M510CJ Control Modules 51
General Alarm 51
Control-by-Zone 52
Control-by-Module 52
Control-by-Detector 53
General M510CJ Trouble 53
Non-Silenceable Indicating Appliance Circuit 53
Non-Silenceable Form-C Relays 53
Supervisory Zones 53
Alarm Verification 54
Waterflow Zones 54
Walk Test 54
Trouble Condition 54
Step Switches 55
Loop Fault LED and RESET 55
ON-LINE LED and SKIP Switch 55
ENTER LED and Switch 55
Display Status LED and Switch 55
Automatic Detector Test 55

Operating the AIM-200 59


Zone Display 59

2 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Introduction

Description Note: AIM-200 features discussed in this document are available with
AIM-200 software part number 73264 or greater.
The Addressable Intelligent Module (AIM-200) functions as an interface
between the FC-2000 Fire Alarm Control Panel andintelligent/addressable
devices. To the FC-2000, the AIM-200 looks like an IZM-8 Initiating
Zone Module. On its single communications loop, the AIM -200 will
communicate with up to 99 addressable modules and 99 intelligent
detectors. The AIM-200 will communicate with the following:
2551J Intelligent Photoelectric Smoke Detector
1551J Intelligent Ionization Smoke Detector
5551J Intelligent Thermal Sensor
M500MJ Addressable Monitor Module
M502MJ Addressable Monitor Module
M501MJ Miniature Monitor Module
M510CJ Addressable Control Module
BGX-101L Addressable Manual Pull Station
DH-500J Intelligent Duct Detector Housing
The 198 devices are mapped into eight software zones by the AIM -200.
The status of these zones is reported to the CPU -2000. The AIM-200
includes a digital display for identifying the exact device address within a
zone. The display is also used to display device types and analog detector
sensitivity values.
Although the AIM-200 is intended primarily as an initiating input module,
it can support M510CJ Control Modules on the loop. The M510CJ
modules may be mapped to AIM -200 zones much like outputs are mapped
to inputs during standard FC-2000 programming.
The AIM-200 may be mixed in a system with any of these system modules:
IZM-8 Initiating Zone Module
IZE-A Initiating Zone Expander
ICM-4 Indicating Circuit Module
ICE-4 Initiating Circuit Expander
CRM-4 Control Relay Module
CRE-4 Control Relay Expander

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 3


VCM-4 Voice Control Module
VCE-4 Voice Control Expander
DCM-4 Dual Channel Module
TCM-2 Time Control Module (Single hazard release)
TCM-4 Time Control Module (Multiple hazard release)
In addition, ACM remote annunciators, AMG -1 and FFT-7
voice/telephone modules, and several power supplies can be employed with
an AIM-200.
Up to ten AIM-200s may be installed in one FC -2000 for a capacity of
1,980 points (subject to limitations of system power supply). Refer to the
AIM-200 Power Requirementssection of this document.

Inventory
AIM-200
Addressable
Intelligent Module

Figure 1: AIM-200 Addressable Intelligent Module

4 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


The AIM-200 communicates with up to 99 intelligent detectors and up to
99 addressable modules. The AIM -200 reports device alarm or trouble
activity back to the CPU as one of eight mapped zones.

Label Inserts

Figure 2: AIM-200 Label Inserts

The slide-in labels are printed with identification for system


-defined LEDs
and switches. Space is provided to type in custom information for the
eight user-defined zones.

Card File

Figure 3: AIM-200 Card File

A special card file is attached to the bottom front of the AIM


-200. Several
standard 4 in. by 2-1/4 in. cards are provided and may be marked with
device information by the installer. A reference card, which defines all
display codes, is included.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 5


Optional
Peripherals
Intelligent
Detectors
B501BJ Base
These intelligent, addressable detectors provide analog information to
the AIM-200. The AIM-200 processes this analog information and
continually makes decisions on the alarm, maintenance, or normal status
of each device. Each detector head mounts to a B501BJ base for ease of
installation or replacement. The sensitivity of each detector can be set
by the programmer at the AIM-200 for one of three levels (low,
medium, and high). Each detector responds to an address that is set in
the head via built-in rotary decimal switches.

2551J
An intelligent photoelectric smoke detector that provides analog
measurements of the optical smoke level in its chamber to the AIM-200
panel.

1551J
An intelligent ionization smoke detector that measures the level of
combustion products in its chamber using the ionization principle and
reports this measurement to the AIM-200.

5551J
An intelligent thermal sensor (135
-degree F fixed temperature).

RA400Z
A remote single LED annunciator that can be wired directly off of an
addressable detector for annunciation of that detector’s alarm status.

Control and Monitor Modules


The M510CJ control module and the M500MJ monitor module provide
the interface between the FC-2000 and conventional initiating and
indicating devices. Both types of modules respond to an address that is
set by the installer with built
-in rotary decimal switches. A flashing LED
indicates power is applied. A thermoplastic cover (illustrated at left) is
provided with each module for mounting to a-inch4 square mounting
box.

6 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


M500MJ
An addressable monitor module that can be used to monitor
conventional normally open contact alarm initiating devices, such as
manual pull stations, 4-wire smoke detectors, heat detectors, waterflow,
and supervisory devices. Supervised circuit can be wired NFPA Style B
or Style D.

M502MJ
An addressable monitor module that monitors conventional-wire
2
smoke detectors. Supervised circuits can be wired NFPA Style B or
Style D. M502MJ supervises initiating device circuit wiring,
communication loop, and input power.

M510CJ
An addressable control module that can be used as an indicating
appliance circuit for powering and supervising compatible, UL Listed
indicating appliances. Supervised circuits can be wired NFPA Style Y or
Style Z. By breaking two built-in tabs, the M510CJ can be employed as
a Form-C control relay.

M500XJ
The loop isolator module is an automatic switch that opens the circuit
voltage to a predetermined communications loop branch(es) whenever a
fault is detected on that circuit. The remainder of the communications
loop leading up to the M500XJ will continue to operate, unaffected by
the fault.

M501MJ
An addressable module that is functionally identical to an M500MJ
monitor module (Style B circuits only), but offered in a smaller package
for mounting directly in the electrical box of the device being monitored.

BGX-101L
The addressable manual pull station features a key-lock reset. The pull
station responds to an address set by the installer with built
-in rotary
decimal switches. Includes key.

A2143-00
The 47K end-of-line resistor assembly is used in the supervision of
M500MJ Monitor and M510CJ Control Module circuits. It is included
with each M500MJ or M510CJ module.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 7


A77-716-02B
The end-of-line power supervision relay is used to supervise the power
to 4-wire smoke detectors and indicting appliances.

N-ELR
The N-ELR resistor assortment is required for use in Canada. It
provides a variety of resistor values to mount to a single ELR plate
(included). Resistors can be used for the supervision of an M500MJ
monitor module or M510CJ control module circuit.
Resistors included:
120 ohms, 470 ohms, 1.8K, 2.2K, 4.7K, 6.8K, 10K, 27K, and 47K.

8 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Installing the AIM-200

This section outlines the installation procedure for the AIM-200. For
information on installing other FC -2000 equipment, refer to the Installing
the FC-2000 Technical Bulletin in this manual.

Installing the Complete the following steps to install the AIM


-200 onto the CHS-4
AIM-200 Chassis.
1. Mount the AIM-200 to a CHS-4 Chassis.
2. Insert the tab on the bottom of the AIM-200 into the slot on the
bottom of the CHS-4.
3. Fasten the AIM-200 to the top of the CHS-4 using the two captive
screws in the top corners of the module. Refer to Figure 4.
Note: If point annunciation (192 intelligent AIM-200 points and
56 standard system circuits) of a single AIM-200 is desired, the
AIM-200 must be mounted in the second slot of the first chassis
(directly to the right of the CPU). This annunciation option must
also be selected in system programming.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 9


Figure 4: Mounting the AIM-200

10 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


4. Connect the ribbon cable. See Figure 5.

Figure 5: Connecting the Ribbon Cable

Connecting the Connect the alarm bus cable following the steps below. Use the alarm bus
Alarm Bus Cable cable (Part No. 71033) included with the AIM-200.
1. Remove the 2-pin connector on one end of the cable.
2. Separate and strip the wires, leaving about half an inch of bare wire
exposed.
3. Connect wires to Terminals 14 and 15 on the CPU.
4. Connect the other end of the trouble cable to the left
-most 2-pin
terminal on the bottom left-hand corner of the AIM-200. If additional
AIM-200s are employed, see Figure 6.

! CAUTION: Do not connect any other device or circuit to the


alarm relay contacts on the CPU -2000 while the alarm
bus cable (Part No. 71033) is installed in the system.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 11


Figure 6: Connecting the Alarm Bus Cable

Wiring the The AIM-200 communicates with intelligent and addressable initiating,
Communications monitor and control devices through a communications loop. The
Loop Circuit FC-2000 can support up to ten communications loops, each controlled by
an AIM-200 module. The communications loops can be wired as
non-redundant (Figure 9), redundant (Figure 12), or isolated redundant
(Figure 13).

Isolator Modules Isolator modules (M500XJ) permit a zone of detectors and modules to be
electrically isolated from the remainder of the communications loop,
allowing critical loop components to function in the event of a circuit fault
(see Figures 13 and 18).

Monitor Modules Addressable monitor modules (M500MJ, M502MJ, and M501MJ) allow
the AIM-200 to monitor entire circuits of conventional normally open
contacts, alarm initiating devices, manual pull stations,-wire
4 smoke
detectors, heat detectors, and waterflow and supervisory devices
(Figures 21 and 22). A type ofmonitor module, the addressable
BGX-101L, provides point annunciation of manual pull stations
(Figure 27).

12 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Control Modules Through addressable control modules (M510CJ), the FC -2000 can
selectively activate indicating appliance circuits or Form
-C output relays
(see Figures 23 through 27).

Intelligent Through the communications loop, the AIM -200 communicates with
Detectors intelligent ionization, photoelectric, and thermal detectors (Figure 28).

Loop Capacity The capacity of each AIM-200 includes up to 99 intelligent detectors and
an additional combination of up to 99 addressable pull stations, control
modules, and monitor modules. One to ten AIM -200s can be employed,
depending on system requirements.
Notes:
1. Communications loop is supervised and power limited.
2. Maximum loop length is 10,000 feet (total twisted pair length).
3. Maximum loop voltage: 27.6 VDC.
4. Maximum loop current: 200 mA (short circuit) 100 mA (normal
operation)
5. Maximum loop resistance: 40 ohms.
6. Refer to the proper installation drawing supplied with each
communications loop appliance.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 13


Table 1: Communications Loop Performance
Fault Condition
Single Single Loop has
Loop Loop Loop Communication
Open on Ground Been Shorted Shorted Opened Loss with
Loop on Loop Shorted
and and and Control Panel
Opened Grounded Grounded
Non-Redundant (2-Wire) Loop Operation
Trouble Trouble with Trouble Trouble Trouble Trouble Trouble
(Note 1) Alarm
Capability
(Note 2)
Redundant (4-Wire) Loop Operation
Trouble with Trouble with Trouble Trouble Trouble Trouble with Trouble
Alarm Alarm Alarm
Capability Capability Capability
Isolated Redundant (4-Wire) Loop Operation (Note 3)
Trouble with Trouble with Trouble with Trouble Trouble with Trouble with Trouble
Alarm Alarm Alarm Alarm Alarm
Capability Capability Capability Capability Capability

Notes:
1. Trouble indicates that a trouble signal will be generated at the control
panel under the abnormal condition.
2. Alarm capability indicates whether or not an alarm signal can be
transmitted to the control panel during the abnormal condition.
3. Isolated redundant loop operation is a method of protecting, or
isolating, entire physical zones of devices on the communications loop
from faults that occur within other areas of the loop.

14 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


AIM-200 Wiring Non-Redundant Circuit
Requirements

Figure 7: Non-Redundant Circuit

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 15


Branch Resistance
Short the termination point of one branch at a time and measure DC
resistance from the beginning of the loop to the end of that particular
branch. The total DC resistance from panel to branch end cannot exceed
40 ohms. Repeat this procedure for all remaining branches.

Figure 8: Non-Redundant Circuit Branch Resistance

16 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 9: Non-Redundant Communications Loop

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 17


Redundant Circuit

Figure 10: Redundant Circuit

Total length of the communications loop pair cannot exceed 10,000 feet
(measured from the control panel out, and back to the control panel).
The DC resistance of the communications loop pair cannot exceed
40 ohms. This measurement may be modeled by disconnecting loop out
and return at the control panel, shorting the two leads of communications
loop return together and metering loop out.

18 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 11: Redundant Circuit Branch Resistance

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 19


Figure 12: Redundant Communications Loop

20 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Isolated-Redundant Circuit
By flanking each communications loop device with a pair of M500XJ fault
isolator modules, each device is protected from short circuit faults that may
occur on other devices. For example, a fault on Zone 2 will not effect
Zones 1 and 3. The isolator modules on either side of Zone 2 will open the
loop. Zone 1 will still operate from power on loop out and Zone 3 will
operate from loop return. Since the system will no longer be able to
communicate with Zone 2, a trouble signal(s) will be generated for that
device.
This circuit is a variation of the redundant circuit, therefore, no-tapping
T
or branching is allowed. The ratings and characteristics are the same as for
the redundant circuit.

Figure 13: Isolated-Redundant Communications Loop

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 21


Shield Termination in No Conduit
Do not allow the shield drain wire to enter the control panel cabinet.
Connect the drain wire to the outside of the cabinet via a BX
-type
connector.

Figure 14: Shield Termination in No Conduit

Shield Termination in Full Conduit


The shield drain wire must be connected to the negative-)(side of the
loop. Do not allow the shield drain wire or the shield foil to touch the
control panel cabinet.
Note: For redundant or isolated redundant field wiring of the
communications loop, connect each end of the shield to the
negative side of the respective channel.

Figure 15: Shield Termination in Full Conduit

Shield Termination in Partial Conduit


Do not allow the shield drain wire to enter the control panel cabinet or the
conduit. Connect the drain wire to the termination point of the conduit run
(such as a single-gang box as illustrated in Figure 16). The conduit cannot
be longer than 20 feet.

22 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 16: Shied Termination in Partial Conduit

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 23


M500XJ Isolator
Module

Figure 17: M500XJ Isolator Module

The loop isolator module (M500XJ) is used to protect critical elements of


the communications loop from faults on other branches or sections of the
loop. The M500XJ continuously monitors the circuit connected to
Terminals 3 (-) and 4 (+). Upon power up, an integral relay is latched on.
The M500XJ periodically pulses the coil of this relay. A short circuit on
the loop resets the relay. The M500XJ sees this short and disconnects the
faulted branch by opening the positive side of the loop (Terminal 4). This
effectively isolates the faulted branch from the remainder of the loop. Once
the fault is removed, the M500XJ automatically -applies
re power to the
communications loop branch. Figure 18 illustrates the use of an M500XJ
on a non-redundant communications loop. For employing M500XJs on a
redundant or isolated-redundant communications loop, see Figure 13.
Note: During a fault condition, the FC-2000 will register a trouble
condition for each zone mapped to the isolated loop branch.

Figure 18: Isolating Non-Redundant Communications Loops

Shorts on this branch of an isolated non-redundant communications loop


will be isolated from all devices installed both upstream of the M500XJ and
on the continuation of the loop (shown as dotted line).

24 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


M500MJ
Monitor Module

Figure 19: M500MJ Monitor Module

The M500MJ monitor module is an addressable module that monitors


normally open contacts, shorting type alarm initiating devices. The
supervised M500MJ circuit can be wired as an NFPA Style B or Style D
initiating device circuit. There is no limit to the number of contact type
devices installed on a monitor module circuit. Refer to Figures 21 and 22
for M500MJ wiring diagrams.

Communications Connect the communications loop to M500MJ Terminals -) 1(and 2 (+).


Loop The M500MJ occupies one module address on the loop. Set the rotary
Connections switches on the M500MJ to the particular loop address required.

NFPA Style B Connect the normally open contacts of the alarm initiating devices to a
Initiating Device single two-wire circuit. This circuit cannot be T
-tapped or branched in any
Circuit fashion, and must be terminated across the last device by a listed 47K,
1/2
watt ELR (Part No. A2143-00, supplied with module). Connect the circuit
to M500MJ Terminals 6 -() and 7 (+).

NFPA Style D Connect the normally open contacts of the alarm initiating devices to a
Initiating Device single four-wire circuit. This circuit cannot be T
-tapped or branched in any
Circuit fashion. No external ELR is required for Style D wiring. Connect the
4-wire circuit to M500MJ Terminals 6-)( and 9 (-), then 7 (+) and 8 (+).

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 25


M501MJ
Monitor Module

Figure 20: M501MJ Monitor Module

The M501MJ monitor module is an addressable module that is functionally


and electrically identical to an M500MJ monitor module (Style B circuits
only), but offered in a smaller package for mounting directly in the
electrical box of the contact-type device being monitored.

NFPA Style B Terminate with a A2143-00 ELR (N-ELR in Canada).


Initiating Device
Circuit
M500MJ and 1. Initiating device circuit is supervised and current
-limited to
M501MJ 210 microamps @ 24 VDC (nominal).
Monitor Module 2. Initiating device circuit provides the following services (do not mix):
Technical Notes
a) Fire alarm service
b) Automatic/manual waterflow alarm service with normally open
contact devices
c) Sprinkler supervision with normally ope
n contact devices
3. Maximum loop resistance due to wiring is 65 ohms.

26 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 21: NFPA Style B Initiating Device Circuit

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 27


Figure 22: NFPA Style D Initiating Device Circuit

28 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


M510CJ Control The M510CJ control module is an addressable module that supervises and
Module switches power to an indicating appliance circuit. The M510CJ circuit can
be wired as an NFPA Style Y or Style Z indicating appliance circuit.
Alternately, the M510CJ can be employed as a Form -C control relay.

Figure 23: M510CJ Control Module (Alarm Polarity Shown)

Communications Connect the communications loop to M510CJ Terminals -) 1(and 2 (+).


Loop The M510CJ occupies one module address on the loop. Set the rotary
Connections switches on the M510CJ to the particular loop address required.

NFPA Style Y Connect polarized alarm indicating appliances to a single-wire


2 circuit.
Indicating This circuit cannot be T-tapped or branched in any fashion and must be
Appliance Circuit terminated across the last device by a 47K, 1/2
-watt ELR
(Part No. A2143-00). Connect the circuit to M510CJ Terminals 6 (+)
and 7 (-). See Figure 25.

NFPA Style Z Connect polarized alarm indicating appliances to a single two-wire circuit.
Indicating This circuit cannot be T-tapped or branched in any fashion. No external
Appliance Circuit ELR is required for Style Z wiring. Connect the-wire
4 circuit to M510CJ
Terminals 6 (+) and 9 (+), then 7 -)
( and 8 (-). See Figure 26.

Indicating Connect indicating appliance power to M510CJ Terminal 3 (common) and


Appliance Power Terminal 4 (+ 24 VDC). This power must be supervised by a UL Listed
power supervision relay, wired as shown in Figure 25 or 26.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 29


Figure 24: M510CJ Control Module (Form -C Relay)

Break Tabs To configure a M510CJ as a Form -C relay, the two tabs must be broken
off of the module. Use a pair of needle
-nose pliers to break off each tab.

Communications Connect the communications loop to M510CJ Terminals -) 1(and 2 (+).


Loop The M510CJ occupies one module address on the loop. Set the rotary
Connections switches on the M510CJ to the particular loop address required.

Contact Wire the common and the normally


-open or normally-closed contacts to
Connections the M510CJ as needed.

Contact Ratings Resistive: 2 amps @ 30 VDC


Inductive: 1 amp @ 30 VDC (0.6 pf)
0.3 amps @ 120 VDC (0.35 pf)
Contacts are not rated for pilot duty or motor loads.

30 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 25: NFPA Style Y Indicating Appliance Circuit

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 31


Figure 26: NFPA Style Z Indicating Appliance Circuit

32 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


BGX-101
Addressable
Manual Pull
Station
BGX-101L The BGX-101L is an addressable manual pull station with a key
-lock reset
Installation feature.

1. Connect the communications loop to BGX -101L red wire (+) and
black wire (-). If additional devices are to be connected to the SLC
loop after the BGX-101L, wire-nut the continuance of the loop to the
red and black wires.
2. The BGX-101L is factory preset with address “00.” Set the address
for the pull station by using a screwdriver to turn the rotary address
switches on the back of the unit to the appropriate settings.

Figure 27: Wiring Addressable Manual Pull Stations

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 33


Intelligent The B501BJ base provides the connection between the AIM-200
Detectors communications loop and 2551J, 1551J, and 5551J intelligent detectors.

Installation 1. Connect the communications loop to Terminal 1(


-) and Terminal 2(+)
on the B501BJ.
2. If employing an RA400Z remote LED annunciator, connect the
RA400Z positive terminal to B501BJ Terminal 3 and the negative
Terminal to B501BJ terminal 1.
3. Before installing the appropriate intelligent detector head, set the
detector’s address on the head with a small slotted screwdriver.
Mark this address on the base and on the head.

Figure 28: Wiring the B501BJ Detector Base

Inserting the Seven AIM-200 cards are provided in a plastic pouch. Remove and
AIM-200 Cards discard the cover card.

Figure 29: AIM-200 Cover Card

After the appropriate point information has been entered onto the cards,
they may be inserted into the module as shown in Figure 31.

34 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 30: Organizing AIM-200 Cards for Placement

Organize the cards in sequence, with number “1” on top and number “6”
on the bottom. Carefully press-fit the cards over the holding clips on the
module and close the front door.

Figure 31: Inserting AIM-200 Cards

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 35


36 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module
Programming the AIM-200

Programming the AIM-200 involves two modes of operation:


Auto-Program, (password 231-1332) and Program Edit
(password 231-3112). A third function, Display Status, allows the
programmer to review the entire AIM -200 program. Program Clear
(password 231-5678), allows the clearing of an existing program from
non-volatile memory.

Programming
Display
Device Type Green LEDs indicate whether the device is a detector or a module.

Figure 32: Device Type

Device The device’s type and address are alternately displayed on the-digit
2
7-segment display.

Left Digit Right Digit


P = Photo Detector Blank = Normal Sensitivity (for detectors), or
Indicating Circuit Selected (for M510CJs)
I = Ion Detector L = Low Sensitivity (detectors only)
H = Heat Detector H = High Sensitivity (detectors only)
G = Monitor Module or Pull Station d = Disabled
C = Control Module O = Form-C Selected (M510CJs)
E = No response from a device (the
AIM-200 is programmed for a device which
is in trouble or not physically installed on the
loop).

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 37


Mapped Zones A zone that the device has been mapped to is indicated by the red zone
alarm LED. Devices may be mapped to any one or all of the eight
AIM-200 zones. The AIM-200 will require that each M500MJ, M501MJ,
or M502MJ Monitor Module or intelligent detector be mapped to at least
one zone (one zone must be selected at any point in time). M510CJ
Control Modules may or may not be mapped to a zone, depending on the
particular application (see theOperating M510CJ Control Modulessection
of this document).

Selecting Mapped Zones


Mapped zones may be selected or deselected by pressing the switch on
each respective zone (switch toggles selection of the zone).

Figure 33: Mapped Zone Selection Switches

Detector To change the sensitivity of an intelligent detector, press the


Sensitivity STEP-FORWARD or STEP-REVERSE switch. The right-hand display
digit will read “L” for low, “H” for high, and blank for normal sensitivity.
Either of these switches can also be used to disable the detector (right
-hand
digit displays “d”).

38 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Figure 34: Detector and Control Module LEDs

Control Module To program a M510CJ control module to function as an indicating


(IAC) appliance circuit, press the STEP
-FORWARD switch until the right
-hand
display digit is blank.
Note: The function tabs on the M510CJ must not be broken for this type
of operation.

Control Module To program a M510CJ control module as a Form


-C relay, press the
(Form-C) STEP-FORWARD switch until the right-hand display digit reads “0.” The
STEP-REVERSE switch can be used to disable the control module
(right-hand digit displays a “d”).

Programming Accepting or Rejecting Devices


Switches
The ENTER and SKIP LEDs will flash while the AIM
-200 is in
Auto-Program or Program Edit mode.

Auto-Program
To accept a new device, press the ENTER switch. To reject a device,
press the SKIP switch. In either case, the AIM
-200 will advance to the
next address.

Program Edit
To store newly edited information on the device displayed, press the
ENTER switch. To leave device unchanged, press the SKIP switch. In
either case, the AIM-200 will advance to the next address.
Note: Holding in the SKIP switch will cause the AIM
-200 to advance
through successive addresses quickly (10 per second).

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 39


Style 6 Loop Operation
This LED indicates that the AIM-200 has been programmed for redundant
communications loop operation. Select or deselect for the entire loop by
pressing the control switch.
Note 1: To function as a redundant communications loop, the AIM
-200
loop must be wired in accordance with Figure 12.
Note 2: An isolated-redundant circuit is a variati
on of a redundant circuit
(see Figure 13). If wired as an isolated
-redundant
communications loop, the AIM -200 should be programmed for
redundant circuit operation.

Auto-Program Auto-Program is used when a system is first installed, or when device


Mode additions or deletions are necessary. It determines the number, address and
type of devices to be programmed by polling the addressable loop. The
AIM-200 determines which devices have been physically installed on the
loop and compares this information against the program stored in memory.
If a particular device responds differently, the AIM
-200 displays the new
address and type. If accepted by the programmer, the information is stored
in the non-volatile memory. Certain other parameters are pre -selected by
the AIM-200, such as zone assignment and detector sensitivity, with the
installer given an opportunity to change those parameters as desired.

Entering Once in Auto-Program mode, the AIM-200 turns off all LEDs, places a
Auto-Program flashing “AP” on the digital display, and begins polling all 198 possible
Mode addresses. It stores the address and type of each device as found. It then
compares each new address/type with the old information stored in its
memory. If the old and new address/type match, the AIM -200 proceeds to
the next address, and repeats. This process could take several seconds to
complete all devices. Only removal of the PK -1 key can abort the process.
If a mismatch is found between the actual devices installed on the loop and
the information in memory, information about the actual device is
displayed. The operator may accept the new device by pressing ENTER,
or reject the device and retain the information that was in memory by
pressing SKIP. Mismatches include an installed device that is not in
memory, a non-existing device that is in memory, or a different Type code.
After any mismatches are accepted or rejected, the AIM
-200 displays a
count of the number of programmed detectors, alternating with a count of
programmed modules. The operator may exit to: Program Edit mode by
pressing ENTER; Auto-Program mode (repeat) by pressing SKIP; or
normal operation by removing the PK-1 key.

40 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


AIM-200 Power Requirements

Regulated Use Table 2 to determine the amount of current drawn by the AIM -200(s)
Power Required during non-alarm conditions. Place the total standby current obtained in
in Standby the Installing the FC-2000 Technical Bulletinin this document when
calculating secondary power standby requirements for the control panel.

Table 2: Standby Regulated Power Requirements


Device Type Device Current Total Current
Number (amps)
AIM-200 [ ] X 0.050 =
(Note 1)
Detectors and [ ] X 0.000210 =
Modules
1551J, 2551J,
2551TH,
5551J,
M500MJ,
M501MJ,
M510CJ,
BGX-101L
M500XJ [ ] X 0.000420 =
Total Standby Current = amps

1. Maximum number of AIM -200s is determined by power supply


loading limits in theInstalling the FC-2000 Technical Bulletinin this
manual but may never exceed the following limits: 10 with the
MPS-24A; 2 with the MPS-24B.

Regulated Use Table 3 to determine the amount of current drawn by the AIM -200(s)
Power Required in the FC-2000 during an alarm. Place the Total Alarm Current obtained in
in Alarm the Installing the FC-2000 Technical Bulletinin this manual when
calculating regulated requirements in the alarm state for the control panel.

Table 3: Alarm State Regulated Power Requirements


Device Type Device Current Total Current
Number (amps)
AIM-200 [ ] X 0.075 =
Total AIM-200 Current (from Table 2) =
Total Alarm Current = amps

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 41


42 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module
AIM-200 Point Annunciation

Note: For the following feature to be enabled, the AIM


-200 requires
software Part No. 73264 or higher.
The CPU can be programmed for an alternate method of annunciating the
AIM-200. Up to 192 intelligent devices can be annunciated on a single
AIM-200 with ACM or LDM series annunciators, or the LCD -80 Liquid
Crystal Display on the RS-485 interface. The FC-2000 annunciates the
AIM-200 installed directly tothe right of the CPU. Note that an
annunciator cannot be used to execute manual ON/OFF control of
intelligent AIM-200 points, only standard FC-2000 zones. The option
provides annunciation of up to 256 points for the FC
-2000, broken down
as follows:

Figure 35: AIM-200 Point Location

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 43


Table 4: Point Annunciation for the AIM -200
Annunciator Address 1 8 CPU points (CPU point shift not an option).
8 unusable points.
48 points mapped to the next six modules
installed in the FC-2000 (which can also be
AIM-200s for annunciation of their eight
software zones).
Annunciator Address 2 Intelligent detectors, addressed 1-64 on the
AIM-200 installed next to the CPU-2000.
Annunciator Address 3 Addressable Modules, addressed 1-64, on
the AIM-200 installed next to the CPU-2000.
Annunciator Address 4 Intelligent detectors, addressed 65-96,
followed by addressable modules, addressed
65-96, on the AIM-200 installed next to the
CPU-2000.

Note: AIM-200 detector and module Addresses 97, 98, and 99 may be
used, but cannot be point-annunciated.

Program Clear The Program Clear function allows the programmer to clear an existing
program from AIM-200 memory. After clearing memory, the AIM -200
must be completely reprogrammed, beginning with Auto
-Program.

Table 5: Clearing AIM-200 Memory


Programmer FC-2000
1. Insert the PK-1 Programming Key. CPU-2000 will register a System Trouble
condition.
Red alarm LEDs on Zones 1, 2, and 3 and
the DISPLAY STATUS and ENTER LEDs
will flash at the faster rate.

will be displayed for “Enter


Password”
2. Acknowledge the System Trouble The CPU-2000 piezo-sounder will silence.
(if desired).
3. Enter the Program Clear password: The LEDs illuminated on the AIM-200 will
231-5678. flash at the slower rate.

Push ENTER.
will be displayed for “Program
Clear.”
4. You can now clear AIM-200 memory After the AIM-200 erased stored
by pressing ENTER. Pressing SKIP or information,
removing the programming key aborts
Program Clear.
will be displayed for “Enter
Password”.
Continued on next page . . .

44 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Programmer (Cont.) FC-2000
5. At this point, you must execute Auto- Refer to Table 7.
Program so that the AIM-200 can
determine which devices are installed
on the loop.
At least one device must be installed
on the AIM-200 loop. If the
programming key is removed after
Program Clear and before Auto-
Program is executed, the AIM-200 will
register a trouble condition by
illuminating the yellow trouble LEDs on
Zones 1, 3, 5, and 7.

Default Zone Upon initial power up, and after clearing AIM -200 memory (Program
Map Clear), intelligent detectors and addressable modules installed on an
AIM-200 loop are automatically mapped to default zones. Any changes to
this map must be made through Program Edit. This default map is
illustrated in Figure 36.

Figure 36: Default Zone Map

Display Status When the operator wishes to view the status and program for a device, the
Display Status/Sensitivity function is used. This function is entered directly
by inserting the PK-1 Programming Key and pressing the DISPLAY
STATUS switch. No password is required.
Note: The AIM-200 will cease monitoring its devices while in this mode
and the CPU-2000 will report System Trouble.
Alternately, this mode may be entered without key or password by pressing
and holding the DISPLAY STATUS switch in for two seconds. Continue
to hold the DISPLAY STATUS switch in with one hand while performing
the Step function with the other hand.
Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 45
Displaying the When the Display Status mode is entered, the digital display will repeatedly
Status of flash the address, type and sensitivity of the detector assigned to the lowest
Intelligent address. The user can scroll through all detectors using the
Detectors STEP-FORWARD and STEP-REVERSE switches. The SKIP switch
advances addresses rapidly.

Figure 37: Displaying the Status of Intelligent Detectors

Detector Device Type/Status


The Device Type/Status field displays two characters for intelligent
detectors, outlined below.

Table 6: Device Type/Status Field Display


Left Digit Right Digit
P = Photo Detector Blank = Normal Sensitivity
I = Ion Detector L = Low Sensitivity
H = Heat Detector H = High Sensitivity
A = Alarm
F = Fault (Maintenance Alert)
d = Disabled
E = Error--No response from a device (the AIM-200 is
programmed for a device that is in trouble or not physically
installed on the loop).
U = Unsatisfactory (failed automatic detector test).

Alarm Threshold The percent of alarm threshold for detectors are displayed with a decimal
Percentage point as illustrated below.

Figure 38: Alarm Threshold Percentage

46 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Table 7: Auto-Programming the AIM-200
Programmer FC-2000
1. Insert the PK-1 Programming Key. CPU-2000 will register a System Trouble
condition.
Red alarm LEDs on Zones 1, 2, and 3 and
the DISPLAY STATUS and ENTER LEDs
will flash at the faster rate.

will be displayed for “Enter


Password.”
2. Acknowledge the System Trouble The CPU-2000 piezo sounder will silence.
(if desired).
3. Enter the Auto-Program password: The LEDs illuminated on the AIM-200 will
231-1332. flash at the slower rate.
All LEDs will be turned off and a flashing
Push ENTER.

will be displayed for “Auto-


Program.”
The AIM-200 polls all 198 possible device
addresses. It stores the address and type
of each device found installed on the loop
(this process could take several seconds).
It then compares each device against the
old information stored in its memory.
If a mismatch is found between the devices
installed on the loop and the information in
memory, information about the new device
is displayed.
4. The device information can be See the Display Status section of this
changed by the AIM-200 programmer. document.
5. You may accept the new device by The AIM-200 proceeds to the next
pressing ENTER, or reject the device mismatch, and repeats the process.
and retain the information that was in After all mismatches are accepted or
memory by pressing SKIP. rejected, the AIM-200 displays a count of
the number of programmed detectors,
alternating with a count of programmed
modules.
6. You may advance to Program Edit
mode by pressing ENTER; return to
Auto-Program mode by pressing
SKIP, or resume normal operation by
removing the PK-1 key.

Program Edit The Program Edit function allows the programmer to change an existing
program in the AIM-200 memory. If Program Edit mode is entered
directly from Auto-Program mode, the programmer will enter the Program
Edit mode at Step 5 of the following instructions.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 47


Table 8: Editing the AIM-200 Memory
Programmer FC-2000
1. Insert the PK-1 Programming Key. CPU-2000 will register a System Trouble
condition.
Red alarm LEDs on Zones 1, 2, and 3 and
the DISPLAY STATUS and ENTER LEDs
will flash at the after rate.

will be displayed for “Enter


Password.”
2. Acknowledge the system Trouble The CPU-2000 piezo sounder will silence.
(if desired).
3. Enter the Program Edit password: The LEDs illuminated on the AIM-200 will
231-3112. flash at the slower rate.
4. Press ENTER. The AIM-200 will alternately display the
address and device type of the lowest
addressed detector.
5. The STEP-FORWARD and The AIM-200 will continue to alternately
STEP-REVERSE switches allow the display the address and device type during
programmer to change detector status editing.
(high, normal, low, or disabled) and The AIM-200 steps through all detectors
module status (Form-C, indicating and then all modules installed on the loop.
circuit, or disabled). To store newly After the last module is edited, the AIM-200
edited information, press the ENTER will begin again at the first detector on the
switch. To leave a device unchanged, loop.
press the SKIP switch. The AIM-200
will advance to the next address.
Note: Holding in the SKIP switch will
cause the AIM-200 to advance
through successive addresses
quickly (10 per second).

6 . After all desired changes have been The AIM-200 will return to normal
made, remove the programming key. operation.

Alarm Bus The alarm bus is implemented with a two wire daisy chain that connects to
each AIM-200. It is used to provide a manual evacuation control of
M510CJ modules and to manually silence these modules; for general alarm
control functions, and to provide a backup connection between multiple
AIM-200s so that the panel may still function in general alarm even if the
CPU fails.

48 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


General Alarm M510CJ modules will be activated under a general alarm condition
Service provided that the module address is set to “59” or below and the module is
not mapped to any zone. In addition, the alarm bus cable must be
connected between the CPU and the AIM -200 (see Figure 6). This
connection puts the normally open contacts of the CPU Alarm Relay across
the pin connector on the AIM-200. When an alarm occurs, the alarm relay
changes state, closing the connection to the AIM-200 and signaling a
general alarm condition.
Note: The CPU alarm relay is dedicated to this function and should not be
connected to other circuits.
To ensure that general alarm functions properly, adhere to the following:
1. The CPU default program automatically maps the Form -C alarm relay
to all initiating zones in the system. While this is a default map, the
AIM-200 programmer should ensure that this relay is indeed mapped
to all initiating circuits, including the eight zones on each AIM
-200.
This guarantees that any alarm in the system will activate the alarm
relay, which will in turn signal a general alarm throughout all
AIM-200s on the alarm bus connection.
2. The alarm relay must be programmed as a non -coded point. If it is
not, the alarm relay contacts will pulse general alarm bus connection,
causing the AIM-200(s) to oscillate in and out of alarm.
3. The CPU alarm relay must be programmed as silenceable, permitting

the silencing of general alarm modules with software type


(see Figure 39).

Figure 39: Alarm Bus Activity


Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 49
Backup Alarm The interconnection of alarm bus cables between each AIM-200 provides
Bus backup general alarm capability in the event of communications failure with
the CPU. Under this condition, the following events will take place.
When an alarm occurs on an AIM -200, output modules mapped to the
alarmed zone will be activated. The AIM -200, unable to communicate
with the CPU, will assume general alarm responsibility and will close its
own alarm bus cable connection. This has the same effect as a signal from
the alarm relay--all AIM-200s receive a alarm bus cable closure and enter a
general alarm condition.

Signal Silence
Function Signal Silence will only function for those M510CJs that have been

programmed as indicating appliance modules (software type )


and have been programmed for general alarm service (see the
General
Alarm Service section of this document).
The Signal Silence function is exercised by first closing, then opening, the
alarm bus cable connection. The closure occurs after initiation of an alarm-
-when the alarm relay changes state. The opening occurs when the
SIGNAL SILENCE switch is pressed--the Alarm Relay is silenced,
opening the alarm bus connection. This signals the AIM -200(s) to silence
all general alarm M510CJ modules.
Signal Silence has no effect on M510CJ Control Modules that are Form
-C

(Type ), address 60 or higher, or that are mapped to any AIM


-200
zone. These modules can only be silenced by the RESET switch on the
CPU.

50 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Operating M510CJ Control
Modules

Optional M510CJ control modules can be installed on the AIM -200


addressable loop. When using one or more M510CJs, four types of control
options are available: General Alarm, Control
-by-Zone,
Control-by-Module, and Control-by-Detector. The M510CJ zone mapping
and address assignments required for each control option are described
below.

General Alarm To set up General Alarm, set M510CJ module address in the range of
01-59 and ensure that it has not been mapped to any zones. If an alarm
occurs on the alarm bus (see Figure 6 for wiring information), the M510CJ
will be activated. This type of control can also be executed using the
manual switch on the CPU board alarm relay (manual evacuation).

Table 9: Activating M510CJs Based on an Alarm Anywhere in the


System
Alarm M510CJ M510CJ Mapped Results
From Address to Zone(s)?
Alarm Bus 01-59 No M510CJ will be activated if not
mapped to any zone.
Alarm Bus 01-59 Yes M510CJ will not be activated if
mapped to a zone.
Alarm Bus 60-99 * M510CJ will not be activated if not
in the address range of 01-59.
* Result is the same whether M510CJ is mapped to any zone or not.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 51


Control-by- Control-by-Zone is suited forcontrol-by-floor and floor above/floor below
Zone applications. No special treatment is required to execute Control
-by-Zone.
If the AIM-200 detects an alarm from an intelligent detector or addressable
monitor module, it activates which ever zone(s) are mapped to this device.
All M510CJ modules assigned to the alarmed zone(s) will be activated.

Table 10: Activating M510CJs Based on Zone Activity


Alarm Detector or M510CJ Results
From M500MJ/M501MJ/ Address
M502MJ Address
Detector or 01-99 01-99 M510CJ will be activated if not
Monitor mapped to the same zone as the
Module alarmed device.
Detector or 01-99 01-99 M510CJ will be activated if not
Monitor mapped to the same zone as the
Module alarmed device.

Control-by- Control-by-Module is a useful function for Air Handling Units (AHUs)


Module controlled by 4-wire duct detectors. To set up Control-by-Module, set the
monitor module address in the range 60 -69. Ensure that a M510CJ module
exists in the address range 70
-79 with the same least significant addres
s
digit as the M500MJ, M501MJ, M502MJ(s) and that the M510CJ module
has not been mapped to any zones.

Table 11: Activating M510CJs Based on Module Activity


Alarm Monitor M510CJ Address M510CJ Mapped Results
From Module to Zone(s)?
Address
M500MJ, 60-69 70-79 No M510CJ will be activated if it
M501MJ, or shares the same least significant
M502MJ digit with the alarmed device and
is not mapped to any zones.
M500MJ, 60-69 70-79 Yes M510CJ will not be activated if
M501MJ, or mapped to a zone.
M502MJ
M500MJ, 1-59, ** * M510CJ will not be activated if the
M501MJ, or 70-99 address of the alarmed device is
M502MJ not within the range of 60-69.
* Result is the same whether M510CJ is mapped to any zone or not.
** Result is the same regardless of M510CJ address.

52 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Control-by- Control-by-Detector is a useful function for activating sounders in the same
Detector room or location as the alarmed intelligent detector. To set up
Control-by-Detector, set detector address in the range 80-99. Ensure that
a M510CJ module exists with the same address as the detector, and that
the M510CJ has not been mapped to any zones.

Table 12: Activating M510CJs Based on Detector Activity


Alarm Detector M510CJ Address M510CJ Mapped Results
From Address to Zone(s)?
Detector 80-99 Same as detector No M510CJ will be activated if it
shares the same least significant
digit with the alarmed device and
is not mapped to any zones.
Detector 80-99 Same as detector Yes M510CJ will not be activated if it
shares the address of the alarmed
device but is mapped to a zone.
Detector 80-99 Other than detector * M510CJ will not be activated if it
does not share the address of the
alarmed device.
Detector 1-79 ** * M510CJ will not be activated if the
address of the alarmed device is
not within the range of 80-99.
* Result is the same whether M510CJ is mapped to any zone or not.
** Result is the same regardless of M510CJ address.

General M510CJ modules programmed for General Alarm, Control -by-Module, or


M510CJ Trouble Control-by-Detector do not have a zone assignment. If a trouble occurs on
one of these devices, it is reported as trouble on Zone 1.

Non- An M510CJ configured as an indicating appliance system (tabs intact) can


Silenceable be programmed in AIM-200 memory as a Form-C module. The module
Indicating will still function as a supervised indicating appliance circuit, but will be
Appliance non-silenceable. This feature is suitable in applications that require strobe
Circuit lights to continue flashing after the signals have been silenced during an
alarm.

Non-
Silenceable A M510CJ configured as a Form -C Relay (type ) cannot be
Form-C Relays silenced by the SIGNAL SILENCE switch on the CPU. These modules,
regardless of their mapping assignments, can only be silenced by the
RESET switch on the CPU.

Supervisory This supervisory monitoring function (tamper valves, etc.) is transparent to


Zones the AIM-200. This programming selection is performed at the CPU.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 53


Alarm The AIM-200 performs alarm verification if this feature is programmed at
Verification the CPU. Verification delays are performed for alarms from detectors
only.

Waterflow This FC-2000 function (non-silenceable alarm) is transparent to the


Zones AIM-200. If used, the installer should assign only flow switches to the
zone.

Walk Test The AIM-200 module will perform a single


-person test of all devices as
follows:
1. Disable all eight AIM-200 zones using the DISABLE/ENABLE
control on the CPU.
2. Disable all M510CJ modules on the AIM
-200 by entering Program

Edit mode and selecting the code for each module. Remove
the programming key.
3. Reset the system. (The remainder of the system, including other
AIM-200s, continues to provide fire protection.)
4. Activate (alarm) each initiating device on the AIM
-200.
5. Return to the panel and verify that the AIM
-200 2 digit display is
stepping through all devices that were alarmed.
6. Reset the system and enable all eight AIM
-200 zones.
7. Enable all M510CJ modules on the AIM
-200. Be sure to select the
proper type.
8. Reset the system.

Trouble During a trouble condition (with no alarm present) the digital display will
Condition show the address of the trouble. The detector and module LEDs will be
used to indicate the category of device in trouble.
Note: If a Style 6 loop fault exists, the display indicates “LF”
(Loop Fault). If communication is lost with the CPU -2000,
“SF” (System Failure) is displayed.
If multiple trouble conditions exist, the digital display steps through all
troubles automatically at a rate of one trouble per second. The STEP
switches may be used to manually control the digital display. Once a STEP
switch is pressed, the display advance is under control of these switches. If
a trouble(s) has been silenced and an device mapped to the same software
zone goes into trouble, the AIM-200 will resound the trouble signal and
flash appropriate LEDs.

54 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Step Switches Two switches, STEP FORWARD and STEP REVERSE, are provided for
advancing the display. If multiple alarms or troubles exist in the AIM
-200,
and the display is automatically advancing through them, pressing either of
these two switches will stop the automatic advance and allow the operator
to control the advancement through the display. If these two switches are
not pressed again during a period of about one minute, the display will
automatically resume stepping through existing events.
Each time a STEP switch is pressed, the digital display advances to the
next higher/lower address that is also in alarm or trouble. After all
addresses in alarm or trouble have been displayed, it returns to the first
address and continues.

Loop Fault LED NFPA Style 6 field wiring may be used to ensure full operation in the event
and RESET of a single break in the loop wiring. When set for Style 6, the AIM-200
latches a wire failure and then must be manually reset to-test
re and clear
the fault. When the loop fault is latched on, the AIM
-200 turns on the
yellow LOOP FAULT LED and reports trouble for all zones that are not in
alarm. If there is no alarm, “LF” is placed on the digital display. The
RESET switch or the System RESET clears the latch. If a loop fault still
exists, the trouble will then resound and re
-latch.
T-tap wiring is not allowed in the Style 6 configuration. Field wiring must
be returned to the AIM-200 terminal block as illustrated in Figure
12.

ON-LINE LED The green ON-LINE LED will flicker when communications occur on the
and SKIP interface to the CPU. The SKIP switch is used in programming the
Switch AIM-200. (See the Programming the AIM-200 section of this document.)

ENTER LED and This LED and switch are used in programming the AIM-200 (see the
Switch Programming the AIM-200 section of this document).

Display Status This LED and switch are used in programming the AIM-200 (see the
LED and Switch Programming the AIM-200 section of this document).

Automatic The AIM-200 automatically test all detectors on its SLC loop. This test is
Detector Test similar to activating a detector with a test magnet.
The module periodically commands each detector, one at a time, to
respond with an appropriate alarm -like signal (pulse on the SLC loop). If
the proper response is not returned, the AIM -200 will register a trouble
condition for that detector. The trouble LED of the zone which that
detector is mapped to will illuminate and the piezo will sound.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 55


To determine which detector has failed the test, use the Display Status
function. The status of the faulty detector will be indicated by a “U”

(Unsatisfactory test) in the right digit of the display ( , ,

or ).
The RESET switch on the CPU must be pushed to clear the trouble status
from the device. Unless the detector has been repaired or replaced, the
AIM-200 will again register a trouble condition with the next device test.
Each detector will be tested at least every 24 hours.
The automatic test is not conducted for modules.

Table 13: AIM-200 Event Codes


Device Type Status
P Photo Detector Normal, med. sensitivity
PL Photo Detector Normal, low sensitivity
PH Photo Detector Normal, high sensitivity
PA Photo Detector Alarm
PF Photo Detector Trouble
PE Photo Detector No answer
Pd Photo Detector Disabled
PU Photo Detector Unsatisfactory (failed
automatic self-test)
I Ion Detector Normal, med. sensitivity
IL Ion Detector Normal, low sensitivity
IH Ion Detector Normal, high sensitivity
IA Ion Detector Alarm
IF Ion Detector Trouble
IE Ion Detector No answer
Id Ion Detector Disabled
IU Ion Detector Unsatisfactory (failed
automatic self-test)
H Heat Detector Normal
HA Heat Detector Alarm
HF Heat Detector Trouble
HE Heat Detector No answer
Hd Heat Detector Disabled
HU Heat Detector Unsatisfactory (failed
automatic self-test)
Continued on next page . . .

56 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Device Type (Cont.) Status
G Monitor Module Normal
GA Monitor Module Alarm
GF Monitor Module Trouble
GE Monitor Module No answer
Gd Monitor Module Disabled
C Control Module (IAC) Normal
CA Control Module (IAC) Alarm output
CF Control Module (IAC) Trouble
CE Control Module (IAC) No answer
Cd Control Module (IAC) Disabled
CO Control Module (Relay) Open (OFF)
CC Control Module (Relay) Closed (ON)
CF Control Module (Relay) Trouble
Cd Control Module (Relay) Disabled
LF Line Fault (Style 6)
SF CPU loss of communication
EP Enter Password
AP Auto-Program

Note: Invalid device type = “E” left digit. Maintenance Alert = “F” left
digit.

Displaying the After the AIM-200 has stepped through all detectors, it will begin displaying all
Status of modules. The digital display will repeatedly flash between the address and
Addressable type/status of the module assigned to the lowest address. The user can scroll
Modules through all modules using the STEP-FORWARD and STEP-REVERSE
switches. The SKIP switch advances through addresses rapidly.

Module Device Type/Status


The Device Type/Status field displays two characters for modules, outlined
below.

Table 14: Device Type/Status Field Characters


Left Digit Right Digit
G = Monitor Module or Pull Station Blank = Indicating circuit selected
C = Control Module A = Alarm
F = Fault--Trouble (open monitor module
zone; open or short M510CJ)
d = Disabled
O = Open (Form-C)
C = Closed (Form-C)
E = Error--No response from a device (the
AIM-200 is programmed for a device that is in
trouble or not physically installed on the loop).

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 57


Advancing to an Address Range
By pressing any one of Zone Switches 1 through 8, the operator can
advance directly to a desired range of addresses. The AIM
-200 will jump
to the lowest address of a programmed device within that range. The
STEP-FORWARD and STEP-REVERSE switches can be used to move to
devices within each range.

Figure 40: Default Zone Map

Display Status Tips:


1. To view module status directly upon entering Display Status mode,
press the switch on Zone 8 and advance through devices 80
-99 (if
present). The AIM-200 will begin displaying modules directly after
the last detector.
2. The STEP-REVERSE switch can be used to back into a lower address
range. For example, to view the status of a device with Address “39,”
press the switch for Zone 4, then press the STEP
-REVERSE switch
once.

58 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module


Operating the AIM-200

Zone Display For each of the eight zone displays, a red LED, yellow LED and a switch
are provided. The 198-point capacity of the AIM-200 is assigned to these
zones using a “mapping” technique. Each of the 198 devices may be
mapped to one or more zones. If an initiating device mapped to more than
one zone is alarmed, all mapped zones will be placed into alarm. This type
of zoning could be used to provide a matrix, where one zone indicates the
area and another the type of device. For example, four zones could be
used to indicate floor of alarm, and three zones could be used to indicate
smoke alarm, manual station, and waterflow alarm. The eighth zone could
be used for supervisory devices (the supervisory devices would not be
mapped into a floor zone).

Figure 41: Zone Switch and LED Location

M510CJ Control Modules are activated by the AIM -200 when the zone
that they are mapped to enters an alarm condition. If a M510CJ is mapped
to more than one zone, it will be activated when any of the zones are in
alarm.
The zone LEDs and switches emulate the functions of an IZM -8 module
except when in Program/Display mode. Pressing the switch in
Program/Display mode displays all output circuits in the system that are
mapped to that zone.

Addressable Intelligent Module—AIM-200 Addressable Intelligent Module 59


The AIM-200 zone assumes the status of any device mapped to that zone
that enters an alarm or trouble condition. If any of the initiating devices are
in alarm, the zone is reported in alarm. If one or more devices (including
M510CJ modules) are in trouble, and no alarms exist, trouble is reported
for the zone.
One trouble condition, called “Maintenance Alert,” will be reported for
analog detectors that give readings in the -19%
0 or 80-99% range. This
trouble condition will result only if the detector remains at this value
continuously for 24 hours (smoldering fires could linger here before
passing 100%). After the detector remains at this level for about 24 hours,
trouble is reported for that detector.

Digital Display The digital display provides two numeric digits. It displays the device
numeric address (01-99). To the right of the digital display are two green
LED’s: “Detector” and “Module.” When there are no devices in alarm or
trouble, and the system is not in a programming mode, the digital display is
blank.

Figure 42: Digital Display

Alarm Condition
When an alarm condition occurs, the address of the alarmed device will
appear in the 2-digit, 7-segment display. If multiple alarms occur, the
display will automatically advance through all alarms. The STEP switches
may be used to manually advance the display one alarm at a time. If it is
necessary to display trouble addresses when an alarm exists, the program
key must be inserted and the Display Status functions followed. If an
alarm(s) has been silenced, and an initiating device mapped to the same
software zone goes into alarm, the AIM -200 will resound the alarm signals
and flash appropriate LEDs.

Controls Group FAN 406


507 E. Michigan Street FC-2000 Technical Manual
P.O. Box 423 Rev. Level —
Milwaukee, WI 53201 Printed in U.S.A.

60 Addressable Intelligent Module—AIM-200 Addressable Intelligent Module

You might also like