RET 670 RELAY

TO COMMUNICATE ABB RET 670 FIRST SET RELAY IP ADRESS IN BOTH LATOP & PCM600

IDENTIFY RELAY IP ADRESS


• SETTING → GENERAL SETTING→COMMUNICATION→TCP-IP CONFIGURATION→FRONT PORT .
IP ADRESS ADD ON LAPTOP
• SETTING → NETWORK & INTERNET→ETHERNET→IP ASSIGNMENT SETTING → IPV4(ON)→ADD IP & SUBNET MASK .

THEN ADD IP ADRESS ON PCM600 .


AFTER DO THESE STEPS PCM 600 READY TO READ/WRITE FILES FROM RET670 RELAY .
FOR RELAY TO LAPTOP COMMUNICATION CHECK
• WINDOWS+R→PING(IP ADRESS OF RELAY)-t
Port type -Front port
Ip-type increase last number of existing IED ip adress.

100 MVA GT
HV-220kV , LV-11kV
CTR HV-400/1→FLC→262.43(PRI)→0.656(SEC)
LV-6000/1→FLC→5248.63(PRI)→0.874(SEC)
EXISTING RELAY SETTINGS

Idiff MINIMUM 0.20 IB Id2-Id1


SLOPE FORMULA =
END SEC-1 1.25 IB Ib2-Ib1
END SEC-2 3.00 IB
SLOPE SECTION-2 40%
Ib = I1 + I2
SLOPE SECTION-3 80%
Id Ume 10.00 IB 2

HIGH SET 120 90


VALUE
150 60
80%
30

180 0
40%
210 330
0.2 SECTION-1 SECTION-2 SECTION-3
240 270 300
0 END SEC-1 END SEC-2 10
1.25 3

PREPARE BY : LOKANATH PANIGRAHI


DT-11-05-2023