BAC Series Low Voltage Air Circuit Breaker
BAC Series Low Voltage Air Circuit Breaker
ACB
BAC Series Low Voltage Air Circuit Breaker
Wider Range
Extended down to 400A, fully satisfying onsite
requirements
More Complete
Several protection units available for flexible selection
√ Over current protection
√ Quick break protection
√ Short circuit short delay protection
√ Grounding fault protection
Stronger Performance
Six short circuit capacity levels, up to 135kA
Preface
Leading technical future, presenting superior performance Perfect protections, complete measurement functions
BAC series air circuit breakers are the newest generation of products manufactured by A variety of optional protection tripping unit are available, meeting various protection
BΩSS, based on years of dedication to design, R&D and professional manufacturing demands such as overload long delay, short circuit short delay, short circuit
technology in electrical distribution products, meeting basic requirements such as instantaneous, and grounding fault protections, also satisfying special requirements
safety and reliability, also integrated into new concepts of intelligent and intensive such as voltage protection and generator protection. The device can measure electrical
design. In this way, the device will bring you comprehensive and new experience with parameters including current, voltage, and harmonic.
electric power product applications. Combined with internationally advanced online
monitoring assembly line production process, and carefully selected components and
parts, each device will be able to offer optimum performance. Complete intelligent communication function, easy for network
integration
BAC series air circuit breakers and its MCU series tripping units can offer intelligent
communication function, providing complete communication interfaces and
protocols, ensuring uploading and acquisition of the circuit breaker's operating states
and electrical parameters, reviewing event logs and maintenance information, to
optimize maintenance and operation functions.
BAC 08-16
BAC 08-25
Broad applications
BAC 32-40
BAC 50-63 BAC series air circuit breakers conform to relevant international and national
standards (IEC/GB), and have passed related testing and CB certification, applicable
for all kinds of power grid systems of 690V and below, with wide applications.
Smaller size, more superior breaking performance
BAC air circuit breakers offer 4 dimensional sizes from 800A to 6300A.
- BAC08~16N1, N2 refers to the same size. Easy and simple installation
- BAC08~25H1, H2 refers to the same size. - No need for distinguishing incoming and outgoing ends, with same outstanding
- BAC32~40H2, H3 refers to the same size. performance, meeting all kinds of incoming and outgoing requirements.
- BAC50~63H3, H4 refers to the same size. - Safety clearance is not necessary.
- Saftisying horizontal or vertical wiring requirements, allowing adjustment by customers
Breaking capacity: up to 135kA Ics=100% Icu (full range) - Meeting standard cabinet requirement in terms of size, according to standard
switchgear design
- Easy for busbar wiring, also convenient for cable connection
Environmental friendly
- BAC series air circuit breakers use the materials causing no pollution or potential
harzards to the environments;
- The materials can be classified for recycling and reuse;
- The manufacuturing factory complys with ISO 14000 environmental accrediation
N1 N2 H1 H2 H3 H4
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
PRODUCT STRUCTURE BAC
BAC Series Low Voltage Air Circuit Breaker
Contents
BiBV
Encapsulated Medium Voltage
Vacuum Circuit Breaker
1 General description 02
11 Ordering information 70
LVset
Intelligent Low Voltage Switchgear
MCCB
Low-Voltage Molded
BSBS
Case Circuit Breaker
Dual Power Automatic
Switching Device
1. General Description
Applications and applicable ranges Mounting category
BAC series low voltage air circuit breakers (hereafter as the circuit breaker) are used
The mounting cateory for the circuit breaker's main circuit and under voltage release
for power distribution and protection of AC 50Hz distribution main and branch
coil, power supply transformer's primary coil is Level IV, while the mounting category
circuits at 690V rated voltage, 1000V rated insulation voltage and 400A to 6300A
for the rest auxiliary circuits and the control devices is Level III.
rated current. The circuit breakers are designed to distribute electrical energy and
protect lines and power supply devices from overload, under voltage, short circuit
and grounding faults. Mounting requirements
As the newest generation, BAC series circuit breakers offer several functions,
including protection, measurement, communication and power management. ● Circuit breakers should be installed in the places where no explosion hazards,
conductive dust, corrosive action on metals, and damages to insulation exits;
● Circuit breakers should be mounted inside the cabinets, with IP40 protection
In accordance with the following standards degree after the frame is added.
- IEC60947-1 - GB/T14048.1 ● Circuit breakers should be mounted to the specifications on the instruction manual,
- IEC60947-2 - GB/T14048.2 with vertical slope not exceeding 5 degree.
3. Common ElectricalFeatures
2. Normal Operating Conditions
Common electrical features
Ambient temperature and altitude Rated voltage
Rated insulation voltage (V) Ui 1000
● Upper limit: ≤+60°C; lower limit: ≥-5°C, the average within 24h:≤+35°C.
Rated impulse withstand voltage (kV) Uimp 12
Remark: ① The lower limit refers to the working condition at -5°C or -25°C. Users must specifiy it to the
manufacturer when ordering! Rated operating voltage (V) Ue AC50/60 Hz 380/400, 660/690
② The upper limit refers to the working condition above +60°C or lower than -25°C. Users should Isolation IEC/EN60947-2 Yes
negotiate with the manufacturer!
Utilization category B
● The altitude in the mounting location should not exceed 2000m. Derated is
Pollution degree IEC60664-1 IV
required for use when exceeding 2000m.
Number of poles 3P, 4P
th
Rated current of the 4 pole 100%In
Atmospheric conditions
The atmostpheric relative humidity should not exceed 50% when the ambient
air temperature is +40°C. Higher relative humidity may be allowed under lower
temperature. The average maximum relative humidity in the wettest month is 90%.
Meanwhile, the average minimum temperature of the same month is 25°C, taking into
account the condensation on the surface of the device due to temperature changes.
Pollution degre
The device is in accordance with IEC60664-1 standard, with the pollution degree of
Level IV.
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 04 ACB Air Circuit Breaker 05
Rated current (A) In 40°C 400 630 800 1000 1250 1600
Ultimate breaking capacity (kA rms)
Icu AC50/60 Hz (RMS) 380/400V 50 55 50 55 50 55 50 55 50 55 50 55
440V 50 55 50 55 50 55 50 55 50 55 50 55
525V 30 35 30 35 30 35 30 35 30 35 30 35
660/690V 30 35 30 35 30 35 30 35 30 35 30 35
Utilizing breaking
Ics AC50/60 Hz (RMS) %Icu 100% 100%
capacity (kA rms)
Short time withstand
Icw AC50/60 Hz (RMS) 0.5s 380/400V 50 55 50 55 50 55 50 55 50 55 50 55
current (kA rms)
0.5s 660/690V 30 35 30 35 30 35 30 35 30 35 30 35
1s 380/400V 42 50 42 50 42 50 42 50 42 50 42 50
1s 660/690V 30 35 30 35 30 35 30 35 30 35 30 35
3s 380/400V 20 20 20 20 20 20 20 20 20 20 20 20
3s 660/690V 20 20 20 20 20 20 20 20 20 20 20 20
Closing capacity (kA)
Icm AC50/60 Hz (peak) 380/400V 105 115 105 115 105 115 105 115 105 115 105 115
440V 105 115 105 115 105 115 105 115 105 115 105 115
525V 63 70 63 70 63 70 63 70 63 70 63 70
660/690V 63 70 63 70 63 70 63 70 63 70 63 70
Breaking time (ms) 25~30
Closing time (ms) <70
Maintenance free operation 15000
Mechanical
With maintenance operation 30000
Life (C-O cycle)
AC 440V operation 6500
Electrical
AC 690V operation 3000
Protections Drawout/fixed type
Protections
Long delay, instanteneous LI MCU-2 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Long delay, short delay,
LSI MCU-3 (A) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous
Long delay, short delay,
LSIG MCU-4 (A, E, P, H, G) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous, grounding
Drawout type 3P 248×360×301
Drawout type 4P 318×360×301
Dimension (mm) W×H×D
Fixed type 3P 254×328.5×209
Fixed type 4P 324×328.5×209
Drawout type 3P 36 36 36 36 38 38 38 38 40 40 40 40
Drawout type 4P 48 48 48 48 50 50 50 50 52 52 52 52
Weight (kg)
Fixed type 3P 19 19 19 19 20 20 20 20 21 21 21 21
Fixed type 4P 25 25 25 25 28 28 28 28 30 30 30 30
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 06 ACB Air Circuit Breaker 07
Rated current (A) In 40°C 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Icu AC50/60 Hz (RMS) 380/400V 70 85 70 85 70 85 70 85 70 85 70 85 85 100 85 100 100 135 100 135
3s 380/400V 50 50 50 50 50 50 50 50 50 50 50 50 65 75 65 75 85 85 85 85
3s 660/690V 50 50 50 50 50 50 50 50 50 50 50 50 65 75 65 75 85 85 85 85
Icm AC50/60 Hz (peak) 380/400V 143 187 143 187 143 187 143 187 143 187 143 187 187 220 187 220 220 330 220 330
440V 143 187 143 187 143 187 143 187 143 187 143 187 187 220 187 220 220 330 220 330
525V 110 143 110 143 110 143 110 143 110 143 110 143 165 187 165 187 187 220 187 220
660/690V 110 143 110 143 110 143 110 143 110 143 110 143 165 187 165 187 187 220 187 220
Protections
Drawout type 3P 84 84 84 84 84 84 84 84 84 84 89 89 114 114 120 120 210 210 225 225
Drawout type 4P 107 107 107 107 107 107 107 107 107 107 113 113 140 140 151 151 260 260 285 285
Weight (kg)
Fixed type 3P 49 49 49 49 49 49 49 49 49 49 51 51 62 62 68 68 110 110 120 120
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 08 ACB Air Circuit Breaker 09
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 10 ACB Air Circuit Breaker 11
3 (2) Zone selectivity interlocking (ZSI); Time delay (ms) Accuracy±10% < 30
● ZSI function becomes effective, in case of fixed-time short delay G (grounding fault) MCU-4A
4 protection or grounding protection on the circuit breaker; Current setting (A) Ig=In × … In≤1250 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
(3) Load monitoring;
Ig= … In>1250 500 600 700 800 850 900 1000 1100 1200
5 ● The control unit monitors the load state, and sends alarming signal
through the realy, after 50% of the long delay protection energy OFF position can be used for removing this protection
6 threshold is exceeded. Time delay (s) tg (s)
(4) Overload pre-alarming Accuracy±10% Setting I2t OFF 1.0
7 ● The control unit monitors the current, and sends alarming signal Setting I2t ON 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
through the realy, after the long delay setting is exceeded.
Measurement function
Ammeter
● MCU-A type controller measures RMS current; the accuracy is ±1.5% when
1 Operation state indicator the current is <2In, the accuracy =±5% when the current is >2In;
2 LCD display ● The LCD display can display maximum load phase current, and shifts
the display of current waveform of each phase with up and down keys;
3 Analogue testing area
Maintenance function
4 Long delay, current setting, fault
Historic logging and maintenance indication:
indicator and tripping delay
● Inquiring historically maximum current and the latest 10 fault records;
5 Short delay, current setting, fault ● Contact wear-out indication, and local acquisition of hot-line operation
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 12 ACB Air Circuit Breaker 13
Maximum distance between two circuit breakers (m) 3000 values. Grounding fault power supply reliability;
● Thermal memory function;
Maximum allowable number of units 100 protection is available. ● OFF position for removing overload protection.
Load monitoring (2) Short circuit protection
Monitoring type Energy ● Short delay (RMS)and instantaneous protections;
● Optional I2t (On or Off) when in delay protection, capable of fine tuning the
Monitoring range 50% of long delay protection energy threshold
protection current;
Implementation method Relay output ● OFF position for removing short delay protection and instatenenous protection.
Fault type
the realy, after 50% of the long delay protection energy threshold is exceeded.
8 (4) Overload pre-alarming
Date and time ● The control unit monitors the current, and sends alarming signal through the
Currents measured in case of a fault realy, after the long delay setting is exceeded.
Alarming historic log (the latest 10 events) will be logged Measurement function
1 Operation state indicator
Alarm type MCU-4 type controllers can offer realtime measurement and display the following
Date and time 2 Status indicator electrical parameters:
3 Tripping curve and fault indicator Current (I), voltage (U), frequency (F), electrical energy (E), and power (P).
Currents measured in case of alarming
Maintenance indication can display 4 Parameter measurement key Maintenance function
Operations, including total numbers/hot-line 5 Function setting key Historic record logging and maintenance indication:
● Inquiry of historically maximum current and the latest 10 fault records;
operations
6 Protection parameter setting key ● Contact wear-out indication, and local acquisition of hot-line operation times
Contact wear rate (%)
7 Historic data and alarming key of the controller;
● Test tripping and controller self-diagnosis are available
8 Navigation key
Communication function
Communication options (com)
Communication options can be equipped to transmit the following data:
● Remote reading or setting up of electrical parameters;
● Transmitting all measured and computed data;
● Sending alarming and tripping signals.
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 14 ACB Air Circuit Breaker 15
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 16 ACB Air Circuit Breaker 17
6 Communication function
4 7
Historical records and maintenance indication MCU-4E 5 Communication options (com)
Tripping historical log (the last 10 events) can record: 8 Communication options can be equipped to transmit the following data:
Fault type ● Remote reading or setting up of electrical parameters;
Date and time
● Transmitting all measured and computed data;
Current measured in case of a fault
● Sending alarming and tripping signals
Alarming historic log (the latest 10 events) can record
Alarm type
Date and time 1 Reset button
Current measured in case of alarming 2 Status indicator
Maintenance indication can display
3 Tripping curve and fault indicator
Operations, including total numbers/hot-line operations
4 Parameter measurement key
Contact wear rate (%)
5 Function setting key
6 Protection parameter setting key
7 Historic data and alarming key
8 Navigation key
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 18 ACB Air Circuit Breaker 19
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 20 ACB Air Circuit Breaker 21
6
● Remote reading or setting up of electrical parameters;
4 Transmitting all measured and computed data;
Historical records and maintenance indication MCU-4P 7 ●
5
Tripping historical log (the last 10 events) can record: ● Sending alarming and tripping signals
Fault type 8
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 22 ACB Air Circuit Breaker 23
G (grounding fault) MCU-4H Tripping when between 0.85 to 1.15 times of IMCR
Current setting (A) Ig=In×( 0.4~0.8 ) In≤1250, setting step-length:1A; Time delay (ms) <30
OFF position can be used for removing this protection Maximum distance between two circuit breakers (m) 3000
Time delay (s) tg (s) Maximum allowable number of units 100
Accuracy Setting Load monitoring
±10% ≥1.0
I2t OFF Monitoring type Energy
Setting Monitoring range 50% of long delay protection energy threshold
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2t ON
Implementation method Relay output
Overload pre-alarming
Monitoring type Current
Monitoring range Long delay settings
Implementation method Relay output
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 24 ACB Air Circuit Breaker 25
P active power kw Total ● Inquiry of historically maximum current and the latest 10 fault records;
Q reactive power kvar Total ● Contact wear-out indication, and local acquisition of hot-line operation
1
S apparent power kva Total times of the controller;
PF power factor Total 2 ● Test tripping and controller self-diagnosis are available
P, Q, S demand value 5min kw, kvar, kva Total 3
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 26 ACB Air Circuit Breaker 27
Current setting (A) Isd = IR ×( 1.5~15 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A Reverse power protection rP 5-500kW 0.2-20s
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 28 ACB Air Circuit Breaker 29
P r o t e c t i on s
Electrical energy
Phase loss protection - - - - - ■ ■ ■ ■
E.P active energy kwh Total/input/output
E.Q reactive energy kvarh Total/input/output Under voltage protection - - - - - - ■ ■ ■
P, Q, S demand value 5min kw, kvar, kva Total Reverse power protection - - - - - - - - ■
Power quality indication (harmonic)
MCR function □ □ □ □ □ □ □ □ □
Fundamental wave U I Zone selectivity interlocking (relay
- - - □ □ □ □ □ □
THD % U I output)
Current and voltage harmonic amplitude 3, 5, 7, 9, 11, 13…31 Load monitoring (relay output) □ □ □ □ □ □ □ □ □
The controller will display the 3rd to 31st harmonic FFT amplitude in rectangular graph, generating wave spectrum analysis of the harmonics Overload pre-alarming - - - □ □ □ □ □ □
Me a s u r eme n t s
Fault type Frequency - - - - - ■ ■ ■ ■
Date and time
Energy: active, reactive, apparent - - - - - ■ ■ ■ ■
Current measured in case of a fault
Thermal capacity - - - - - ■ ■ ■ ■
Alarming historic log (the latest 10 events) can record
Phase sequence - - - - - ■ ■ ■ ■
Alarm type
Date and time Demand values: current and power - - - - - ■ ■ ■ ■
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 30 ACB Air Circuit Breaker 31
Function description MCU-2 MCU-3 MCU-4 MCU-3A MCU-4A MCU-4E MCU-4P MCU-4H MCU-4G
● EPM external power supply module
Test tripping ■ ■ ■ ■ ■ ■ ■ ■ ■
When the working voltage is DC 220/110V, the control unit
Contact wear
- - - ■ ■ ■ ■ ■ ■ must be equipped with an external DC power supply module
indication
Maintenance Number of operations for normal operation.
of the circuit of the controller when - - - ■ ■ ■ ■ ■ ■
breaker energized Features
Input voltage V DC220V/110V ±15%
Self diagnosis function ■ ■ ■ ■ ■ ■ ■ ■ ■
Output voltage V DC24V ±5%
Current waveform
- - - ■ ■ ■ ■ ■ ■ Output current A 0.2
display
Historic maximum EPM external power supply module
current
- - - ■ ■ ■ ■ ■ ■
(displayed by the
controller)
10 alarming records
(displayed by the - - - - - ■ ■ ■ ■
controller) display)
Historic fault record ● NCT external current transformer
(one-time indication )
(3 types of faults When a 3-pole circuit breaker is used in a 3–phase 4-wire
M ai n t en a n c e
■ - - - - - - - -
such as long delay,
instantaneous, and system, NCT external current transformer is used as ground fault
neutral pole)
protection or neutral pole over current protection sampling
Historic fault record
(one-time indication) component, for use with the controller. The device needs to be
(4 types of faults such installed by the users.
- ■ - - - - - - -
as long delay, short
delay, instantaneous,
Historic logging and neutral pole) Specification
Current A Inner hole dimension mm Housing dimension mm
Historic fault record
(one-time indication) 400-1600A * 102×32 145×130
(5 types of faults such NCT external current transformer
as long delay, short - - ■ - - - - - - 800-4000A** 128×61 175×179
delay, instantaneous,
5000-6300A*** 164×104 265×210
ground and neutral
pole)
Remark: * refers to breaking capacity 04 to 16 for BAC N1/N2;
Historic fault record ** refers to breaking capacity 08 to 40 for BAC H1/H2/H3;
(10-time indication,
*** refers to breaking capacity 50 to 63 for BAC H3/H4
displayed by the
- - - ■ ■ ■ ■ ■ ■ For any need of N-pole 0.5In protection, please specify it when ordering.
controller) (all the
information opened by
the protections)
Modbus - - - □ □ □ □ □ □
Communication
output includes: 1.
Information opened by
protection functions;
O t h er s
2. Information opened
Communication by measurement
function; 3. - - - □ □ □ □ □ □
Information opened by
maintenance function;
4. Historic maximum
current; 5. Alarm
records; 6. Historic
fault records.
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 32 ACB Air Circuit Breaker 33
COM communication options are made up of built-in communication ● Charging motor (MTC)
modules inside the controller, offering status signals by a series of auxiliary When the circuit breaker is closed, the energy of the mechanism
is released instantaneously, and the charging motor (MTC) is
contacts, enabling ONR and SHT coils to offer communication functions
automatically charged. When the mechasnim is opened, it can
through expansion.
ensure the circuit breaker to be closed instantaneously.
The status indication contacts of the COM communication options are
Features
mutually independent from the state indication contacts of the circuit
AC 220/380 ±15%
breaker. These indication contacts are still effective for normal operation. Rated voltage Un V
DC 110/220 ±15%
ONR and SHT coils, through functional expansion, offer communication
Acutuation voltage V 85% ~ 110% Un
function, capable of remotely controlling switch opening and closing states. Power loss W 90
Charging time s <7
Communication structure diagram
Charging motor (MTC)
● Closing coil (ONR)
In the mornitoring system, The closing coil is used for electrical closing of the circuit breaker.
the integration of the circuit In case of spring charging, the coil can achieve remote closing.
breaker or switch disconnector
Features
requires COM options; Modbus AC 220/380 ±15%
communication protocol is used Rated voltage Un V
DC 110/220 ±15%
for communication. Acutuation voltage V 70% ~ 110% Un
Charging time ms ≤100
Instanteneous power loss VA 200
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 34 ACB Air Circuit Breaker 35
The unit is used in thunderstorm regions and in the power grid with The contact consists of one mechanical indication contact and changeover
unstable power supply voltage, to prevent the circuit breaker from tripping contact, for use with the interlocking mechanism on the mechanism,
due to short-time voltage drop. indicating:
- The circuit breaker is in opened state;
Features
- The spring is charged;
Rated voltage Un V AC 220/380 ±15%
Start-up delay Adjustable (Rr) 0.5s/1s/1.5s/2s/2.5s/3s ±10%
- The shunt coil (S H T)is not energized;
- The closing coil (ONR)is not energized;
UVT delay unit - No fault tripping; OK closing ready contact
Remark: For BAC04-16 N1 and N2 type, only 4NO-C and 6NO-C are available. When the basic device of the draw-out circuit breaker and its cassette are
in separation, test, and connection positions separately, the electrical signal
output device in the 3 positions will output electrical state signals of each
related position separately.
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 36 ACB Air Circuit Breaker 37
The upper and lower wiring accessories offer horizontal and The door interlocking device can be installed on the left
vertical types, meeting different mounting requirements. Please or right side of the cassette. When the basic device of the
specify it when ordering, or adjust it based on your actual needs. circuit breaker is in "Connection or Test" position, the circuit
Busbar wiring accessories breaker compartment door is forbidden to open. When the
door is opened, and the circuit breaker is in Connection
position, the circuit breaker door can be closed without Door interlocking
operation.
● Phase partition / Interphase barrier
The partition is usded for strengthening the insulation between ● Interlocking between circuit breakers
busbars.
Some electrical systems have two power supply systems for
the continuity of power supply, including the following two
circuit breakers:
Phase partition
- Normal power supply circuit breaker A ;
- Backup power supply circuit breaker B.
● Button lockup device
Circuit breaker A Circuit breaker B
The device is composed of a transparent cover and a padlock
0 0
(not supplied), to prevent closing or opening button from mal
operation. (N1/N2 type is not optional). I 0
Interlocking between circuit breakers
0 I
The lock is installed on the cassette, to lock up the circuit breaker ● Door frame (DP)
in its position in the cassette. The following two lockup methods The frame is mounted on the door, to improve the
are available: protection degree of the circuit breaker to IP40; both fixed
- Padlock device (equipped in standard, the lock is supplied by type and drawout type frame can be mounted.
the user);
Padlock device
- Key lock (optional); Key lock
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 39
When the ambient temperature exceeds 40°C, the operating current will be corrected according to the following table:
When the altitude exceeds 2000m, the performance can be corrected according to the following table.
BAC
Series of Low-Voltage
Air Circuit Breaker
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 40 ACB Air Circuit Breaker 41
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 42 ACB Air Circuit Breaker 43
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 44 ACB Air Circuit Breaker 45
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 46 ACB Air Circuit Breaker 47
Dimension Wiring
Horizontal rear wiring Detailed drawing
A 0 0
B 70 70
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 48 ACB Air Circuit Breaker 49
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 50 ACB Air Circuit Breaker 51
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 52 ACB Air Circuit Breaker 53
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 54 ACB Air Circuit Breaker 55
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 56 ACB Air Circuit Breaker 57
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 58 ACB Air Circuit Breaker 59
Dimension Wiring
Horizontal rear wiring Detailed drawing
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 60 ACB Air Circuit Breaker 61
7.5
Dimension
Current W H L a b c
400-1600A * 145 130 50 102 32 75
800-4000A** 175 179 60 128 61 95
5000-6300A*** 265 210 60 164 104 110
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 62 ACB Air Circuit Breaker 63
Remark:
1. The dotted lines are for wiring by users. The diagram is only for reference;
2. Terminal 1 and 2 are control unit’s power supply. The power supply can be connected to AC 230V or AC 400V, depending on
secondary circuit working voltage. If the working voltage is DC110V and DC220V, the control unit can be connected after
transformation through an external DC power
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 64 ACB Air Circuit Breaker 65
The electric schematic diagram is the wiring diagram when the circuit breaker is in disconnected state, uncharged,
and the controller has no fault indication.
Remark:
4NO+NC 6NO+NC
1. The dotted lines are for wiring by users. Tthe diagram is only for reference;
2. Terminal 1 and 2 are control unit’s power supply. The power supply can be connected to AC 230V or AC 400V, depending
on secondary circuit working voltage. If the working voltage is DC110V and DC220V, the control unit can be connected after
transformation through an external DC power supply module
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 66 ACB Air Circuit Breaker 67
Defintions of wiring terminal numbers The control line can interlock several circuit breakers equipped with MCU control units, as shown in the diagram;
Intelligent controller communication port, Terminal 24 for SH shielding layer, Terminal 25 to connect A, Terminal
The control unit, when detecting a fault, will send a signal to the upstream circuit breaker and detect the signals to the
24, 25, 26 26 to connect B; in the case of cassette communication module, be connected to the cassette communication
module input, Terminal 24 to connect S', Terminal25 to connect A', Terminal 26 to connect B'(optional function) downstream circuit breaker. When the signal sent by the downstream circuit breaker is detected, the circuit breaker will
A1~A6 Cassette 3-position signal output(optional function) remain closed during tripping delay period. If the downstream breaker does not send signals, the circuit breaker will be
T1~T4 Cassette 3-position signal input(optional function) disconnected instantaneously.
S, A, B Communication output(optional function)
Fault 1: only the circuit breaker A detects the fault. Because not receiving the signal sent by the downstream circuit breaker,
the circuit breaker A will trip instantaneously.
Remark:
1. The cassette communication module requires DC24V power supply ( to be supplied by the customer himself );
Fault 2: circuit breaker A and B detect the signal. The circuit breaker A receives the signal sent bym the circuit breaker B and
2. The cassette communication module 3-position signal samling are treated through opto-coupler isolation.
remains closed within 0.3 seconds of tripping delay. The circuit breaker B will trip instantaneously for it does not
receive the signal from its downstream circuit breaker.
Remark: the maximum distance between two circuit breakers is 300 meters. The maximum number of circuit breakers for wiring is 100 devices.
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 68 ACB Air Circuit Breaker 69
ln ≤1250A
lg = In x... 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
ln >1250A
Ig = ...(A) 500 600 700 800 850 900 1000 1100 1200
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 70 ACB Air Circuit Breaker 71
Tick (√) your choice in the corresponding box √ □ and fill relevant information in the rectangular box
BAC 06 N1 3P D/O + MCU - 2
Circuit breaker's basic device Indication contact
Quantity (4NO-C) □
Maximum operating current A ON/OFF indication contact (6NO-C) □
Rated current A (AU) (4NO+4NC) □
Overload pre-alarming □
Harmonic analysis and waveform H type: standard, Mechanical interlock
display G type: optional □
Door interlocking □
Load monitoring □
Interlocking between
Overload pre-alarming □ devices* □
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB.AW.01/02-20