ACB

BAC Series Low Voltage


Air Circuit Breaker
ACB Air Circuit Breaker 3

ACB
BAC Series Low Voltage Air Circuit Breaker

Wider Range
Extended down to 400A, fully satisfying onsite
requirements

More Complete
Several protection units available for flexible selection
√ Over current protection
√ Quick break protection
√ Short circuit short delay protection
√ Grounding fault protection

Stronger Performance
Six short circuit capacity levels, up to 135kA

PT. Australindo Graha Nusa www.australindo.co.id


ACB Air Circuit Breaker 4 ACB Air Circuit Breaker 5

Preface
Leading technical future, presenting superior performance Perfect protections, complete measurement functions
BAC series air circuit breakers are the newest generation of products manufactured by A variety of optional protection tripping unit are available, meeting various protection
BΩSS, based on years of dedication to design, R&D and professional manufacturing demands such as overload long delay, short circuit short delay, short circuit
technology in electrical distribution products, meeting basic requirements such as instantaneous, and grounding fault protections, also satisfying special requirements
safety and reliability, also integrated into new concepts of intelligent and intensive such as voltage protection and generator protection. The device can measure electrical
design. In this way, the device will bring you comprehensive and new experience with parameters including current, voltage, and harmonic.
electric power product applications. Combined with internationally advanced online
monitoring assembly line production process, and carefully selected components and
parts, each device will be able to offer optimum performance. Complete intelligent communication function, easy for network
integration
BAC series air circuit breakers and its MCU series tripping units can offer intelligent
communication function, providing complete communication interfaces and
protocols, ensuring uploading and acquisition of the circuit breaker's operating states
and electrical parameters, reviewing event logs and maintenance information, to
optimize maintenance and operation functions.

BAC 08-16
BAC 08-25
Broad applications
BAC 32-40
BAC 50-63 BAC series air circuit breakers conform to relevant international and national
standards (IEC/GB), and have passed related testing and CB certification, applicable
for all kinds of power grid systems of 690V and below, with wide applications.
Smaller size, more superior breaking performance
BAC air circuit breakers offer 4 dimensional sizes from 800A to 6300A.
- BAC08~16N1, N2 refers to the same size. Easy and simple installation
- BAC08~25H1, H2 refers to the same size. - No need for distinguishing incoming and outgoing ends, with same outstanding
- BAC32~40H2, H3 refers to the same size. performance, meeting all kinds of incoming and outgoing requirements.
- BAC50~63H3, H4 refers to the same size. - Safety clearance is not necessary.
- Saftisying horizontal or vertical wiring requirements, allowing adjustment by customers

Breaking capacity: up to 135kA Ics=100% Icu (full range) - Meeting standard cabinet requirement in terms of size, according to standard
switchgear design
- Easy for busbar wiring, also convenient for cable connection

Environmental friendly
- BAC series air circuit breakers use the materials causing no pollution or potential
harzards to the environments;
- The materials can be classified for recycling and reuse;
- The manufacuturing factory complys with ISO 14000 environmental accrediation

N1 N2 H1 H2 H3 H4

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
PRODUCT STRUCTURE BAC
BAC Series Low Voltage Air Circuit Breaker

Contents
BiBV
Encapsulated Medium Voltage
Vacuum Circuit Breaker
1 General description 02

2 Normal operating conditions 02

3 Common electrical features 03

4 Electrical data of circuit 04


breakers

5 MCU control unit functions 08


MVset and features
Medium Voltage Metal-Clad
Withdrawable Switchgear
XGreen XGreen-P
Solid-insulated Solid-insulated
Ring Main Unit Ring Main Unit 6 Accessory functions and 33
features

TR1 TR2 7 Altitude, temperature, and 39


derated coefficiet

8 Dimension and wiring 40

BAC BCB 9 Electric circuit diagrams 62


Low Voltage Air Miniature Circuit
Circuit Breaker Breaker
10 Tripping curves 68

11 Ordering information 70

LVset
Intelligent Low Voltage Switchgear

MCCB
Low-Voltage Molded
BSBS
Case Circuit Breaker
Dual Power Automatic
Switching Device

PT. Australindo Graha Nusa www.australindo.co.id


ACB Air Circuit Breaker 02 ACB Air Circuit Breaker 03

1. General Description
Applications and applicable ranges Mounting category

BAC series low voltage air circuit breakers (hereafter as the circuit breaker) are used
The mounting cateory for the circuit breaker's main circuit and under voltage release
for power distribution and protection of AC 50Hz distribution main and branch
coil, power supply transformer's primary coil is Level IV, while the mounting category
circuits at 690V rated voltage, 1000V rated insulation voltage and 400A to 6300A
for the rest auxiliary circuits and the control devices is Level III.
rated current. The circuit breakers are designed to distribute electrical energy and
protect lines and power supply devices from overload, under voltage, short circuit
and grounding faults. Mounting requirements
As the newest generation, BAC series circuit breakers offer several functions,
including protection, measurement, communication and power management. ● Circuit breakers should be installed in the places where no explosion hazards,
conductive dust, corrosive action on metals, and damages to insulation exits;
● Circuit breakers should be mounted inside the cabinets, with IP40 protection
In accordance with the following standards degree after the frame is added.
- IEC60947-1 - GB/T14048.1 ● Circuit breakers should be mounted to the specifications on the instruction manual,
- IEC60947-2 - GB/T14048.2 with vertical slope not exceeding 5 degree.

3. Common ElectricalFeatures
2. Normal Operating Conditions
Common electrical features
Ambient temperature and altitude Rated voltage
Rated insulation voltage (V) Ui 1000
● Upper limit: ≤+60°C; lower limit: ≥-5°C, the average within 24h:≤+35°C.
Rated impulse withstand voltage (kV) Uimp 12
Remark: ① The lower limit refers to the working condition at -5°C or -25°C. Users must specifiy it to the
manufacturer when ordering! Rated operating voltage (V) Ue AC50/60 Hz 380/400, 660/690
② The upper limit refers to the working condition above +60°C or lower than -25°C. Users should Isolation IEC/EN60947-2 Yes
negotiate with the manufacturer!
Utilization category B
● The altitude in the mounting location should not exceed 2000m. Derated is
Pollution degree IEC60664-1 IV
required for use when exceeding 2000m.
Number of poles 3P, 4P
th
Rated current of the 4 pole 100%In
Atmospheric conditions

The atmostpheric relative humidity should not exceed 50% when the ambient
air temperature is +40°C. Higher relative humidity may be allowed under lower
temperature. The average maximum relative humidity in the wettest month is 90%.
Meanwhile, the average minimum temperature of the same month is 25°C, taking into
account the condensation on the surface of the device due to temperature changes.

Pollution degre

The device is in accordance with IEC60664-1 standard, with the pollution degree of
Level IV.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 04 ACB Air Circuit Breaker 05

4. Electrical data of circuit breakers


(in accordance with IEC60947-2)
BAC04-16N1, N2
BAC04 BAC06 BAC08 BAC10 BAC12 BAC16
Breaking level N1 N2 N1 N2 N1 N2 N1 N2 N1 N2 N1 N2

Rated current (A) In 40°C 400 630 800 1000 1250 1600
Ultimate breaking capacity (kA rms)
Icu AC50/60 Hz (RMS) 380/400V 50 55 50 55 50 55 50 55 50 55 50 55
440V 50 55 50 55 50 55 50 55 50 55 50 55
525V 30 35 30 35 30 35 30 35 30 35 30 35
660/690V 30 35 30 35 30 35 30 35 30 35 30 35
Utilizing breaking
Ics AC50/60 Hz (RMS) %Icu 100% 100%
capacity (kA rms)
Short time withstand
Icw AC50/60 Hz (RMS) 0.5s 380/400V 50 55 50 55 50 55 50 55 50 55 50 55
current (kA rms)
0.5s 660/690V 30 35 30 35 30 35 30 35 30 35 30 35
1s 380/400V 42 50 42 50 42 50 42 50 42 50 42 50
1s 660/690V 30 35 30 35 30 35 30 35 30 35 30 35
3s 380/400V 20 20 20 20 20 20 20 20 20 20 20 20
3s 660/690V 20 20 20 20 20 20 20 20 20 20 20 20
Closing capacity (kA)
Icm AC50/60 Hz (peak) 380/400V 105 115 105 115 105 115 105 115 105 115 105 115
440V 105 115 105 115 105 115 105 115 105 115 105 115
525V 63 70 63 70 63 70 63 70 63 70 63 70
660/690V 63 70 63 70 63 70 63 70 63 70 63 70
Breaking time (ms) 25~30
Closing time (ms) <70
Maintenance free operation 15000
Mechanical
With maintenance operation 30000
Life (C-O cycle)
AC 440V operation 6500
Electrical
AC 690V operation 3000
Protections Drawout/fixed type
Protections
Long delay, instanteneous LI MCU-2 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Long delay, short delay,
LSI MCU-3 (A) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous
Long delay, short delay,
LSIG MCU-4 (A, E, P, H, G) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous, grounding
Drawout type 3P 248×360×301
Drawout type 4P 318×360×301
Dimension (mm) W×H×D
Fixed type 3P 254×328.5×209
Fixed type 4P 324×328.5×209
Drawout type 3P 36 36 36 36 38 38 38 38 40 40 40 40
Drawout type 4P 48 48 48 48 50 50 50 50 52 52 52 52
Weight (kg)
Fixed type 3P 19 19 19 19 20 20 20 20 21 21 21 21
Fixed type 4P 25 25 25 25 28 28 28 28 30 30 30 30

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 06 ACB Air Circuit Breaker 07

BAC08-63H1, H2, H3, H4


BAC08 BAC10 BAC12 BAC16 BAC20 BAC25 BAC32 BAC40 BAC50 BAC63
Breaking level H1 H2 H1 H2 H1 H2 H1 H2 H1 H2 H1 H2 H2 H3 H2 H3 H3 H4 H3 H4

Rated current (A) In 40°C 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

Ultimate breaking capacity (kA rms)

Icu AC50/60 Hz (RMS) 380/400V 70 85 70 85 70 85 70 85 70 85 70 85 85 100 85 100 100 135 100 135

440V 70 85 70 85 70 85 70 85 70 85 70 85 85 100 85 100 100 135 100 135

525V 55 65 55 65 55 65 55 65 55 65 55 65 75 85 75 85 85 100 85 100

660/690V 55 65 55 65 55 65 55 65 55 65 55 65 75 85 75 85 85 100 85 100


Utilizing breaking
Ics AC50/60 Hz (RMS) %Icu 100% 100%
capacity (kA rms)
Short time withstand
Icw AC50/60 Hz (RMS) 1s 380/400V 70 85 70 85 70 85 70 85 70 85 70 85 85 100 85 100 100 135 100 135
current (kA rms)
1s 660/690V 55 65 55 65 55 65 55 65 55 65 55 65 75 85 75 85 85 100 85 100

3s 380/400V 50 50 50 50 50 50 50 50 50 50 50 50 65 75 65 75 85 85 85 85

3s 660/690V 50 50 50 50 50 50 50 50 50 50 50 50 65 75 65 75 85 85 85 85

Closing capacity (kA)

Icm AC50/60 Hz (peak) 380/400V 143 187 143 187 143 187 143 187 143 187 143 187 187 220 187 220 220 330 220 330

440V 143 187 143 187 143 187 143 187 143 187 143 187 187 220 187 220 220 330 220 330

525V 110 143 110 143 110 143 110 143 110 143 110 143 165 187 165 187 187 220 187 220

660/690V 110 143 110 143 110 143 110 143 110 143 110 143 165 187 165 187 187 220 187 220

Breaking time (ms) 25~30

Closing time (ms) <70

Maintenance free operation 12500 12500 10000 6500


Mechanical
With maintenance operation 25000 25000 20000 13000
Life (C-O cycle)
AC 440V operation 8000 8000 2000 1500
Electrical
AC 690V operation 2500 2500 1500 1000

Mounting type Drawout/fixed type

Protections

Long delay, instanteneous LI MCU-2 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■


Long delay, short delay,
LSI MCU-3 (A) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous
Long delay, short delay,
LSIG MCU-4 (A, E, P, H, G) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
instanteneous, grounding
Drawout type 3P 347×450×395 347×450×395 440×450×395 818×490×395

Drawout type 4P 442×450×395 442×450×395 566×450×395 1070×450×395


Dimension (mm) W×H×D
Fixed type 3P 368×420×298 368×420×298 461×420×298 839×420×298

Fixed type 4P 463×420×298 463×420×298 587×420×298 1091×420×298

Drawout type 3P 84 84 84 84 84 84 84 84 84 84 89 89 114 114 120 120 210 210 225 225

Drawout type 4P 107 107 107 107 107 107 107 107 107 107 113 113 140 140 151 151 260 260 285 285
Weight (kg)
Fixed type 3P 49 49 49 49 49 49 49 49 49 49 51 51 62 62 68 68 110 110 120 120

Fixed type 4P 63 63 63 63 63 63 63 63 63 63 66 66 80 80 88 88 145 145 160 160

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 08 ACB Air Circuit Breaker 09

5. MCU Control Unit Functions and Features


Basic protections MCU-2
L (long delay)
Control units MCU-2, 3, 4 "Basic type" Current setting (A) IR = In × … 0.4 0.5 0.6 0.7 0.8 0.85 0.9 0.95 1
OFF position can be used for removing this protection
MCU-2/3/4 control unit is Basic protections Tripping when between 1.05 to 1.2 times of IR
designed to protect power Portection settings and tripping time are set up by the adjusting knob. Time delay tR ( s ) 15 30 45 60 90 120 180 240 360 480
supply circuit. Type 3 (1) Overload protection Accuracy ±10% tR ( 1.5 IR ) 15 30 45 60 90 120 180 240 360 480
protection unit offers short tR ( 2.0 IR ) 8.4 16.9 25.3 33.8 50.6 67.5 101 135 203 270
● RMS long delay protection;
tR ( 6.0 IR ) 0.94 1.88 3.81 3.75 5.62 7.5 11.3 15 22.5 30
delay protection, whiel Type ● Thermal memory function; tR ( 7.2 IR ) 0.65 1.3 1.95 2.6 3.9 5.2 7.74 10 15.6 21
4 protection unit provides tR ( 10.0 IR ) 0.34 0.68 1.01 1.35 2.03 2.7 4.05 5.4 8.1 10.8
● OFF position for removing overload protection.
grounding fault protection. Thermal memory 10-minute cooling reset or controller powers off for clearing
(2) Short circuit protection I (instantaneous)
Current setting (A) I i = In × … 1 2 4 6 8 10 12 15 20
● Short delay (RMS)and instantaneous protections;
OFF position can be used for removing this protection
● Optional I2t (On or Off ) when in delay protection; Time delay (ms) Accuracy±10% < 30
● OFF position for removing short delay protection and instatenenous
protection. Basic protections MCU-3/4
L (long delay) MCU-3/4
1 (3) Grounding faults Current setting (A) IR = In × … 0.4 0.5 0.6 0.7 0.8 0.85 0.9 0.95 1
● Optional I2t function (ON or OFF); OFF position can be used for removing this protection
Tripping when between 1.05 to 1.2 times of IR
2 ● OFF position for removing grounding protection.
Time delay tR ( s ) 15 30 45 60 90 120 180 240 360 480
(4) Neutral-pole protection Accuracy ±10% tR ( 1.5 IR ) 15 30 45 60 90 120 180 240 360 480
● On 4-pole circuit breakers, the actuation value is equal to the setting tR ( 2.0 IR ) 8.4 16.9 25.3 33.8 50.6 67.5 101 135 203 270
for the concerned fault protection, in case of overload long delay, short tR ( 6.0 IR ) 0.94 1.88 3.81 3.75 5.62 7.5 11.3 15 22.5 30
tR ( 7.2 IR ) 0.65 1.3 1.95 2.6 3.9 5.2 7.74 10 15.6 21
circuit short delay, and short circuit instantenous faults on the neutral
tR ( 10.0 IR ) 0.34 0.68 1.01 1.35 2.03 2.7 4.05 5.4 8.1 10.8
pole;
3 Thermal memory 10-minute cooling reset or controller powers off for clearing
● On 3-pole circuit breakers, optional NCT external current transformer S (short delay) MCU-3/4
4 can be equipped to achieve 100% neutral pole fault protection. Current setting (A) Isd=IR × … 1.5 2 3 4 6 8 10 12 15
OFF position can be used for removing this protection
5 Optional protections Time delay tsd (s)
Accuracy ±10% Setting I2t OFF 0.1 0.2 0.3 0.4
6 (1) MCR function:
Setting I2t ON 0.1 0.2 0.3 0.4
● During closing operation, if the making current exceeds the setting,
Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
7 MCR function will become active, and the circuit breaker has no I (instantaneous) MCU-3/4
manually delayed disconnection; Current setting (A) I i=In × … 1 2 4 6 8 10 12 15 20
OFF position can be used for removing this protection
(2) Load monitoring:
Time delay (ms) Accuracy ±10% < 30
● The control unit monitors the load state, and sends alarming signal G (grounding fault) MCU-4
through the realy, after 50% of the long delay protection energy Ig=In × … In≤1250 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
1 Operation state indicator threshold is exceeded. Current setting (A)
I g= … I n>1250 500 600 700 800 850 900 1000 1100 1200
2 Load rate indicator OFF position can be used for removing this protection
Indication function Time delay tg (s)
3 Analogue testing area
The states of the loads can be indicated with the load rate indicator on Accuracy ±10% Setting I2t OFF 1.0
4 Long delay, current setting, fault Setting I2t ON 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
the panel; in case of fault tripping of the circuit breaker, relevant fault
indicator and tripping delay
indicator will light up. Optional protections MCU-2/3/4
5 Short delay, current setting, fault
MCR protection
indicator and tripping delay Testing function Current setting (A) IMCR = In × … 10
6 Instanteneous protection current The button in the analogue testing area can be used for operations such Tripping when between 0.85 to 1.15 times of IMCR
setting and fault indicator as test tripping, inquiring fault types, and clearing reset on the circuit Time delay (ms) <30
Load monitoring
7 Grounding fault, current setting, breaker.
Monitoring type Energy
fault indicator and tripping delay Monitoring range 50% of long delay protection energy threshold
Implementation method Relay output

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 10 ACB Air Circuit Breaker 11

MCU- 3A/4A "Current-type" Basic protections MCU-3A/4A

MCU-3A/4A control unit is Basic protections L (long delay) MCU-3A/4A


designed to protect power supply Portection settings and tripping time are set up by the adjusting knob,
Current setting (A) IR = In× … 0.4 0.5 0.6 0.7 0.8 0.85 0.9 0.95 1
and the current and time values can be displayed in the LCD display.
circuit, offering measurement,
(1) Overload protection OFF position can be used for removing this protection
display and current values. ● RMS long delay protection;
Tripping when between 1.05 to 1.2 times of IR
Type 4 protection unit provides ● Thermal memory function;
● OFF position for removing overload protection. Time delay (s) tR ( s ) 15 30 45 60 90 120 180 240 360 480
grounding fault protection
(2) Short circuit protection Accuracy±10% tR ( 1.5 IR ) 15 30 45 60 90 120 180 240 360 480
● Short delay (RMS) and instantaneous protections; tR ( 2.0 IR ) 8.4 16.9 25.3 33.8 50.6 67.5 101 135 203 270
● Optional I2t function (On or Off ) when in delay protection;
tR ( 6.0 IR ) 0.94 1.88 3.81 3.75 5.62 7.5 11.3 15 22.5 30
● OFF position for removing short delay protection and instatenenous
tR ( 7.2 IR ) 0.65 1.3 1.95 2.6 3.9 5.2 7.74 10 15.6 21
protection.
tR ( 10.0 IR ) 0.34 0.68 1.01 1.35 2.03 2.7 4.05 5.4 8.1 10.8
(3) Grounding faults
● Optional I2t (ON or OFF); Thermal memory 10-minute cooling reset or controller powers off for clearing
● OFF position for removing grounding protection
S (short delay)
(4) Neutral pole protection Current setting (A) Isd=IR × … 1.5 2 3 4 6 8 10 12 15
● On 4-pole circuit breakers, the actuation value is equal to the setting for
OFF position can remove this protection
the concerned fault protection, in case of overload long delay, short circuit
1 Time delay tsd (s)
short delay, and short circuit instantenous faults on the neutral pole;
● On 3-pole circuit breakers, optional NCT external current transformer Accuracy±10% Setting I2t OFF 0.1 0.2 0.3 0.4
2 can be equipped to achieve 100% neutral pole fault protection 2
Setting I t ON 0.1 0.2 0.3 0.4
Optional protections Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
(1) MCR function: I (instantaneous)
● During closing operation, if the making current exceeds the setting,
Current setting (A) Ii=In × … 1 2 4 6 8 10 12 15 20
MCR function will become active, and the circuit breaker has no
manually delayed disconnection; OFF position can be used for removing this protection

3 (2) Zone selectivity interlocking (ZSI); Time delay (ms) Accuracy±10% < 30
● ZSI function becomes effective, in case of fixed-time short delay G (grounding fault) MCU-4A
4 protection or grounding protection on the circuit breaker; Current setting (A) Ig=In × … In≤1250 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
(3) Load monitoring;
Ig= … In>1250 500 600 700 800 850 900 1000 1100 1200
5 ● The control unit monitors the load state, and sends alarming signal
through the realy, after 50% of the long delay protection energy OFF position can be used for removing this protection
6 threshold is exceeded. Time delay (s) tg (s)
(4) Overload pre-alarming Accuracy±10% Setting I2t OFF 1.0
7 ● The control unit monitors the current, and sends alarming signal Setting I2t ON 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
through the realy, after the long delay setting is exceeded.
Measurement function
Ammeter
● MCU-A type controller measures RMS current; the accuracy is ±1.5% when
1 Operation state indicator the current is <2In, the accuracy =±5% when the current is >2In;
2 LCD display ● The LCD display can display maximum load phase current, and shifts
the display of current waveform of each phase with up and down keys;
3 Analogue testing area
Maintenance function
4 Long delay, current setting, fault
Historic logging and maintenance indication:
indicator and tripping delay
● Inquiring historically maximum current and the latest 10 fault records;
5 Short delay, current setting, fault ● Contact wear-out indication, and local acquisition of hot-line operation

indicator and tripping delay times of the controller;


● Test tripping and controller self-diagnosis are available
6 Instanteneous protection current
setting and fault indicator Communication function
Communication options (com)
7 Grounding fault, current setting,
Communication options can be equipped to transmit the following data:
fault indicator and tripping delay ● Settings and measurements of the protection functions;
● Historical records and maintenance indication;
● Alarming and tripping signals.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 12 ACB Air Circuit Breaker 13

MCU-4E "All power type"


Optional protections MCU-3A/4A
Basic protections
MCR protection MCU-4E type control unit Portection function keys and navigation keys are used to set protection current
Current setting (A) IMCR= In × … 10 is designed to protect the values. The navigation keys or communication options can be used for fine
Tripping when between 0.85 to 1.15 times of IMCR power supply circuit, offering tuning the currents, within the permissible scope.
Time delay (ms) <30
(1) Overload protection
measurement, display and ● RMS long delay protection;
Zone selectivity interlocking (ZSI) communication of all power ● Adjustable multi curves for different selectivity requirements, improving

Maximum distance between two circuit breakers (m) 3000 values. Grounding fault power supply reliability;
● Thermal memory function;
Maximum allowable number of units 100 protection is available. ● OFF position for removing overload protection.
Load monitoring (2) Short circuit protection
Monitoring type Energy ● Short delay (RMS)and instantaneous protections;
● Optional I2t (On or Off) when in delay protection, capable of fine tuning the
Monitoring range 50% of long delay protection energy threshold
protection current;
Implementation method Relay output ● OFF position for removing short delay protection and instatenenous protection.

Overload pre-alarming (3) Grounding faults


● Fixed time protection, adjustable time delay 0.1 to 1.0s, setting step length as 01s;
Monitoring type Current
● OFF position for removing grounding protection.
Monitoring range Long delay settings (4) Neutral pole protection
Implementation method Relay output ● On 4-pole circuit breakers, the actuation value is equal to the setting for the
concerned fault protection, in case of overload long delay, short circuit short
delay, and short circuit instantenous faults on the neutral pole;
● On 3-pole circuit breakers, optional NCT external current transformer can be
equipped to achieve 100% neutral pole fault protection.
Measurement function MCU-3A/4A
Alarm and other protections
Ammeter
Offering current imbalance protection, demand current protection, and phase
Current measurement loss protection function;
Measurement Ia Ib Ic In Ig
Optional protections
When I<2In, accuracy =±1.5%; 1
I>40%I n when there is no auxiliary power supply (1) MCR function:
When I>2In, accuracy =±5.0%
● During closing operation, if the making current exceeds the setting, MCR
Maximum values Iamax Ibmax Icmax I nmax Igmax 2
function will become active, and the circuit breaker has no manually delayed
3 disconnection;
(2) Zone selectivity interlocking (ZSI);
● ZSI function becomes effective, in case of fixed-time short delay protection or
6 grounding protection on the circuit breaker;
Historical records and maintenance indication MCU-3A/4A 4 (3) Load monitoring;
7
Tripping historic record (the latest 10 events) will be logged 5 ● The control unit monitors the load state, and sends alarming signal through

Fault type
the realy, after 50% of the long delay protection energy threshold is exceeded.
8 (4) Overload pre-alarming
Date and time ● The control unit monitors the current, and sends alarming signal through the
Currents measured in case of a fault realy, after the long delay setting is exceeded.
Alarming historic log (the latest 10 events) will be logged Measurement function
1 Operation state indicator
Alarm type MCU-4 type controllers can offer realtime measurement and display the following
Date and time 2 Status indicator electrical parameters:
3 Tripping curve and fault indicator Current (I), voltage (U), frequency (F), electrical energy (E), and power (P).
Currents measured in case of alarming
Maintenance indication can display 4 Parameter measurement key Maintenance function
Operations, including total numbers/hot-line 5 Function setting key Historic record logging and maintenance indication:
● Inquiry of historically maximum current and the latest 10 fault records;
operations
6 Protection parameter setting key ● Contact wear-out indication, and local acquisition of hot-line operation times
Contact wear rate (%)
7 Historic data and alarming key of the controller;
● Test tripping and controller self-diagnosis are available
8 Navigation key
Communication function
Communication options (com)
Communication options can be equipped to transmit the following data:
● Remote reading or setting up of electrical parameters;
● Transmitting all measured and computed data;
● Sending alarming and tripping signals.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 14 ACB Air Circuit Breaker 15

Basic protections MCU-4E Alarm and other protections MCU-4E


L (long delay) MCU-4E Current Threshold Time delay
Current setting (A) IR = In ×( 0.4~1.0 ) Setting step-length as 1A Current imbalance protection Iimbalance 0.05-0.6Iaverage 0.1-40s
OFF position can be used for removing this protection Max. demand current protection Imax demand value 0.2-1.0In 15-1500s
Tripping when between 1.05 to 1.2 times of IR
Time delay (s)
Characteristic
curve
tR (s) I=1.5IR

Accuracy I 2t : 15 30 60 120 240 360 480 600 720 840 960 — — — — —


±10% 4
I t: 2.46 3.94 5.9 9.85 14.8 19.7 24.6 33.2 44.3 68.9 98.5 147 197 246 295 344
EI (M) 6.22 9.96 14.9 24.9 37.3 49.8 62.2 84 112 174 249 373 498 622 747 871
EI (G) 8 12.8 19.2 32 48 64 80 108 144 224 320 480 640 800 960 1120
VI 2 3.2 4.8 8 12 16 20 27 36 56 80 120 160 200 240 280
Current unload MCU-4E
SI 0.61 0.98 1.47 2.46 3.68 4.91 6.14 8.29 11.1 17.2 24.6 36.8 49.1 61.4 73.7 86
Measured value Threshold Time delay
Thermal memory 10-minute cooling reset or controller powers off for clearing
Current I 0.2-1.0I n 0.2-0.8tR
S (short delay)
Current setting (A) Isd = IR ×( 1.5~15 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A
OFF position can remove this protection
Time delay (s) tsd (s)
Accuracy Setting 0.1 0.2 0.3 0.4
±10% I2t OFF
Setting
≥1.1
I2t ON
Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
I (instantaneous)
Current setting (A) I i=In ×( 1.0~20 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A Optional protections MCU-4E
OFF position can be used for removing this protection MCR protection
Time delay (ms) Accuracy ±10% < 30 Current setting (A) IMCR=In × … 10
G (grounding fault) MCU-4E Tripping when between 0.85 to 1.15 times of IMCR
Current setting (A) Ig=In×( 0.4~0.8 ) In≤1250 setting step-length:1A Time delay (ms) <30
Ig= ( 500~1200 ) In>1250 setting step-length: 2A Zone selective interlocking (ZSI)
OFF position can be used for removing this protection Maximum distance between two circuit
3000
breakers (m)
Time delay (s) tg (s)
Maximum allowable number of units 100
Accuracy Setting ≥1.0
I2t OFF Load monitoring
±10%
Setting Monitoring type Energy
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2t ON
Monitoring range 50% of long delay protection energy threshold
Implementation method Relay output
Overload pre-alarming
Monitoring type Current
Monitoring range Long delay settings
Implementation method Relay output

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 16 ACB Air Circuit Breaker 17

MCU-4P "All power+voltage protection type"


Measurement function MCU-4E
Current MCU-4P type control units Basic protections
Instantaneous value A Ia Ib Ic In Ig include all the functions of On the basis of MCU-4E type protection functions, the device also offers
Maximum value A Ia Ib Ic In Ig MCU-4E type, also offering voltage protection, including:
Demand value A Ia Ib Ic In voltge protection.
Imbalance rate % Ia Ib Ic
● Under voltage protection;

Present thermal capacity % ● Over voltage protection;


Voltage ● Voltage imbalance protection;
Instantaneous value V Uab Ubc Uca Uan Ubn Ucn ● Phase sequence protection
Average value V (Uab+Ubc+Uca)/3
Imbalance rate % Uan Ubn Ucn
Measurement function
Frequency
F Hz Uan Ubn Ucn MCU-4 type controllers can offer realtime measurement and display the
Electrical energy following electrical parameters:
E.P active energy kwh Total/input/output Current (I), voltage (U), frequency (F), electrical energy (E), and power (P).
E.Q reactive energy kvarh Total/input/output
E.S apparent energy kvah Total
Maintenance function
Power
P active power kw Total Historic logging and maintenance indication:
Q reactive power kvar Total ● Inquiry of historically maximum current and the latest 10 fault records;
1
S apparent power kva Total ● Contact wear-out indication, and local acquisition of hot-line operation
2 times of the controller;
PF power factor Total
3
P, Q, S demand value 5min kw, kvar, kva Total ● Test tripping and controller self-diagnosis are available

6 Communication function
4 7
Historical records and maintenance indication MCU-4E 5 Communication options (com)
Tripping historical log (the last 10 events) can record: 8 Communication options can be equipped to transmit the following data:
Fault type ● Remote reading or setting up of electrical parameters;
Date and time
● Transmitting all measured and computed data;
Current measured in case of a fault
● Sending alarming and tripping signals
Alarming historic log (the latest 10 events) can record
Alarm type
Date and time 1 Reset button
Current measured in case of alarming 2 Status indicator
Maintenance indication can display
3 Tripping curve and fault indicator
Operations, including total numbers/hot-line operations
4 Parameter measurement key
Contact wear rate (%)
5 Function setting key
6 Protection parameter setting key
7 Historic data and alarming key
8 Navigation key

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 18 ACB Air Circuit Breaker 19

Basic protections MCU-4P Alarm and other protections MCU-4P


L (long delay) MCU-4P Current Threshold Time delay
Current setting (A) IR = In ×( 0.4~1.0 ) setting step-length 1A Current imbalance protection Iimbalance 0.05-0.6 Iaverage 0.1-40s
OFF position can be used for removing this protection Max. demand current protection Imax demand value 0.2-1.0In 15-1500s
Tripping when between 1.05 to 1.2 times of IR Voltage
Time delay (s) Characteristic Under voltage protection Umin. 0.35-0.7Ue 0.2-60s
curve
tR (s) I=1.5IR
Accuracy 2 Over voltage protection Umax. 1.15-1.3Ue 0.2-60s
I t: 15 30 60 120 240 360 480 600 720 840 960 — — — — —
±10% Voltage imbalance protection Uimbalance 0.02-0.3Ue 0.2-60s
I 4t : 2.46 3.94 5.9 9.85 14.8 19.7 24.6 33.2 44.3 68.9 98.5 147 197 246 295 344
Phase sequence
EI (M) 6.22 9.96 14.9 24.9 37.3 49.8 62.2 84 112 174 249 373 498 622 747 871
Phase sequence protection Δ∮ A/B/C or A/C/B 0.3s
EI (G) 8 12.8 19.2 32 48 64 80 108 144 224 320 480 640 800 960 1120
VI 2 3.2 4.8 8 12 16 20 27 36 56 80 120 160 200 240 280
SI 0.61 0.98 1.47 2.46 3.68 4.91 6.14 8.29 11.1 17.2 24.6 36.8 49.1 61.4 73.7 86
Thermal memory 10-minute cooling reset or controller powers off for clearing
Current unload MCU-4P
S (short delay)
Measured value Threshold Time delay
Current setting (A) Isd = In ×( 1.5~15 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A
Current I 0.2-1.0I n 0.2-0.8tR
OFF position can be used for removing this protection
Time delay tsd (s)
Accuracy Setting
0.1 0.2 0.3 0.4
±10% I2t OFF
Setting
≥1.1
I2t ON
Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
I (instantaneous)
Current setting (A) I i=In ×( 1.0~20 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A
OFF position can be used for removing this protection Optional protections MCU-4P
Time delay (ms) Accuracy ±10% < 30 MCR protection
G (grounding fault) MCU-4P Current setting (A) IMCR=In × … 10
Current setting (A) Ig=In×( 0.4~0.8 ) In≤1250 setting step-length:1A; Tripping when between 0.85 to 1.15 times of IMCR
Ig= ( 500~1200 ) In>1250 setting step-length: 2A Time delay (ms) <30
OFF position can be used for removing this protection Zone selectivity interlocking (ZSI)
Time delay (s) tg (s) Maximum distance between two circuit breakers (m) 3000
Accuracy Setting Maximum allowable number of units 100
≥1.0
±10% I2t OFF
Load monitoring
Setting
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Monitoring type Energy
I2t ON
Monitoring range 50% of long delay protection energy threshold
Implementation method Relay output
Overload pre-alarming
Monitoring type Current
Monitoring range Long delay settings
Implementation method Relay output

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 20 ACB Air Circuit Breaker 21

MCU-4H "All power +voltage protection+harmonic


Measurement function MCU-4P
MCU-4H type control units type"
Current
include all the functions of MCU-
Instantaneous value A Ia Ib Ic In Ig
4P type, while offering harmonic Basic protections
Maximum value A Ia Ib Ic In Ig
and fundamental computation,
Demand value A Ia Ib Ic In The device offers all the protection functions of the MCU-4P type control
enabling accurate analysis of
Imbalance rate % Ia Ib Ic units.
power quality and helping
Present thermal capacity %
diagnose and analyze events.
Voltage
Measurement function
Instantaneous value V Uab Ubc Uca Uan Ubn Ucn
On the basis of MCU-4P type, the device also offers harmonic analysis and
Average value V (Uab+Ubc+Uca)/3
waveform display functions.
Imbalance rate % Uan Ubn Ucn
Frequency
F Hz Uan Ubn Ucn Maintenance function
Electrical energy
Historic logging and maintenance indication:
E.P active energy kwh Total/input/output
● Inquiry of historically maximum current and the latest 10 fault records;
E.Q reactive energy kvarh Total/input/output
E.S apparent energy kvah Total ● Contact wear-out indication, and local acquisition of hot-line operation
Power times of the controller;
P active power kw Total ● Test tripping and controller self-diagnosis are available.
Q reactive power kvar Total
S apparent power kva Total 1
PF power factor Total
Communication function
2
P, Q, S demand value 5 min kw, kvar, kva Total 3 Communication options (com)
Communication options can be equipped to transmit the following data:

6
● Remote reading or setting up of electrical parameters;
4 Transmitting all measured and computed data;
Historical records and maintenance indication MCU-4P 7 ●
5
Tripping historical log (the last 10 events) can record: ● Sending alarming and tripping signals
Fault type 8

Date and time


Current measured in case of a fault
Alarming historic log (the latest 10 events) can record
Alarm type
Date and time 1 Reset button
Current measured in case of alarming 2 Status indicator
Maintenance indication can display 3 Tripping curve and fault indicator
Operations, including total numbers/hot-line operations
4 Parameter measurement key
Contact wear rate (%)
5 Function setting key
6 Protection parameter setting key
7 Historic data and alarming key
8 Navigation key

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 22 ACB Air Circuit Breaker 23

Basic protections MCU-4H Alarm and other protections MCU-4H


L (long delay) MCU-4H Current Threshold Time delay
Current setting (A) IR = In ×( 0.4~1.0 ) setting step-length as 1A Current imbalance protection Iimbalance 0.05-0.6Iaverage 0.1-40s
OFF position can be used for removing this protection Max. demand current protection Imax demand value 0.2-1.0In 15-1500s
Tripping when between 1.05 to 1.2 times of IR Voltage
Time delay (s) Characteristic
tR (s) I=1.5IR Under voltage protection Umin. 0.35-0.7Ue 0.2-60s
curve
Accuracy 2 Over voltage protection Umax. 1.15-1.3Ue 0.2-60s
I t: 15 30 60 120 240 360 480 600 720 840 960 — — — — —
±10% Voltage imbalance protection Uimbalance 0.02-03 Ue 0.2-60s
I 4t : 2.46 3.94 5.9 9.85 14.8 19.7 24.6 33.2 44.3 68.9 98.5 147 197 246 295 344
Phase sequence
EI (M) 6.22 9.96 14.9 24.9 37.3 49.8 62.2 84 112 174 249 373 498 622 747 871
Phase sequence protection Δ∮ A/B/C or A/C/B 0.3s
EI (G) 8 12.8 19.2 32 48 64 80 108 144 224 320 480 640 800 960 1120
VI 2 3.2 4.8 8 12 16 20 27 36 56 80 120 160 200 240 280
SI 0.61 0.98 1.47 2.46 3.68 4.91 6.14 8.29 11.1 17.2 24.6 36.8 49.1 61.4 73.7 86
Thermal memory 10-minute cooling reset or controller powers off for clearing
Current unload MCU-4H
S (short delay)
Measured value Threshold Time delay
Current setting (A) Isd = IR×( 1.5~15 ) I n<2500, setting step-length:1A; In≥2500, setting step-length: 2A.
Current I 0.2-1.0In 0.2-0.8tR
OFF position can be used for removing this protection
Time delay (s) tsd (s)
Accuracy Setting
±10% 0.1 0.2 0.3 0.4
I2t OFF
Setting
≥1.1
I2t ON
Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
I (instantaneous)
Current setting (A) I i=In ×( 1.0~20 ) I n<2500, setting step-length:1A; In≥2500, setting step-length: 2A Optional protections MCU-4H
OFF position can be used for removing this protection MCR protection

Time delay (ms) Accuracy±10% < 30 Current setting (A) IMCR=In × … 10

G (grounding fault) MCU-4H Tripping when between 0.85 to 1.15 times of IMCR
Current setting (A) Ig=In×( 0.4~0.8 ) In≤1250, setting step-length:1A; Time delay (ms) <30

Ig= ( 500~1200 ) In>1250, setting step-length: 2A Zone selectivity interlocking (ZSI)

OFF position can be used for removing this protection Maximum distance between two circuit breakers (m) 3000
Time delay (s) tg (s) Maximum allowable number of units 100
Accuracy Setting Load monitoring
±10% ≥1.0
I2t OFF Monitoring type Energy
Setting Monitoring range 50% of long delay protection energy threshold
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2t ON
Implementation method Relay output
Overload pre-alarming
Monitoring type Current
Monitoring range Long delay settings
Implementation method Relay output

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 24 ACB Air Circuit Breaker 25

MCU-4G "All power +voltage protection+ frequency


Measurement function MCU-4H
protection type"
Current MCU-4G type control units
Instantaneous value A Ia Ib Ic In Ig include all the functions of Basic protections
Maximum value A Ia Ib Ic In Ig MCU-4P type, while offering
Demand value A Ia Ib Ic In Based on the protections of MCU-4P type, the device offers also frequency
frequency and power prrotectins,
and power protection, including:
Imbalance rate % Ia Ib Ic enhancing the protection to the
Present thermal capacity % loads. ● Under frequency protection
Voltage ● Over frequency protection
Instantaneous value V Uab Ubc Uca Uan Ubn Ucn ● Reverse power protection
Average value V (Uab+Ubc+Uca)/3
Imbalance rate % Uan Ubn Ucn
Measurement function
Frequency
F Hz Uan Ubn Ucn The device includes all the measurement functions of the MCU-4P type,
Electrical energy with optional harmonic analysis and waveform display functions.
E.P active energy kwh Total/input/output
E.Q reactive energy kvarh Total/input/output
Maintenance function
E.S apparent energy kvah Total
Power
Historic logging and maintenance indication:

P active power kw Total ● Inquiry of historically maximum current and the latest 10 fault records;
Q reactive power kvar Total ● Contact wear-out indication, and local acquisition of hot-line operation
1
S apparent power kva Total times of the controller;
PF power factor Total 2 ● Test tripping and controller self-diagnosis are available
P, Q, S demand value 5min kw, kvar, kva Total 3

Power quality indication (harmonic)


Communication function
Fundamental wave U I
6
THD % U I 4 Communication options (com)
7
Current and voltage harmonic Amplitude 3, 5, 7, 9, 11, 13…31 5 Communication options can be equipped to transmit the following data:
The controller will display the 3rd to 31st harmonic FFT amplitude in rectangular graph, generating wave spectrum analysis of the harmonics 8 ● Remote reading or setting up of electrical parameters;
● Transmitting all measured and computed data;
● Sending alarming and tripping signals
Historical records and maintenance indication MCU-4H 1 Reset button
Tripping historical log (the last 10 events) can record: 2 Status indicator
Fault type 3 Tripping curve and fault indicator
Date and time 4 Parameter measurement key
Current measured in case of a fault
5 Function setting key
Alarming historic log (the latest 10 events) can record
6 Protection parameter setting key
Alarm type
7 Historic data and alarming key
Date and time
8 Navigation key
Current measured in case of alarming
Maintenance indication can display
Operations, including total numbers/hot-line operations
Contact wear rate (%)

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 26 ACB Air Circuit Breaker 27

Basic protections MCU-4G Alarm and other protections MCU-4G


L (long delay) MCU-4G Current Threshold Time delay
Current setting (A) IR = In ×( 0.4~1.0 ) setting step-length as 1A Current imbalance protection Iimbalance 0.05-0.6Iaverage 0.1-40s
OFF position can be used for removing this protection Imax demand
Max. demand current protection 0.2-1.0In 15-1500s
value
Tripping when between 1.05 to 1.2 times of IR
Voltage
Time delay (s) Characteristic
tR (s) I=1.5IR
curve Under voltage protection Umin 0.35-0.7Ue 0.2-60s
Accuracy I2t : 15 30 60 120 240 360 480 600 720 840 960 — — — — — Over voltage protection Umax 1.15-1.3Ue 0.2-60s
±10%
4
I t: 2.46 3.94 5.9 9.85 14.8 19.7 24.6 33.2 44.3 68.9 98.5 147 197 246 295 344 Voltage imbalance protection Uimbalance 0.02-0.3Ue 0.2-60s
EI (M) 6.22 9.96 14.9 24.9 37.3 49.8 62.2 84 112 174 249 373 498 622 747 871 Phase sequence
EI (G) 8 12.8 19.2 32 48 64 80 108 144 224 320 480 640 800 960 1120 Phase sequence protection Δ∮ A/B/C or A/C/B 0.3s
VI 2 3.2 4.8 8 12 16 20 27 36 56 80 120 160 200 240 280 Frequency
SI 0.61 0.98 1.47 2.46 3.68 4.91 6.14 8.29 11.1 17.2 24.6 36.8 49.1 61.4 73.7 86 Under frequency protection Fmin 45Hz-Starting value 0.2-0.5s
Thermal memory 10-minute cooling reset or controller powers off for clearing Over frequency protection Fmax Starting value-65Hz 0.2-5.0s

S (short delay) Power

Current setting (A) Isd = IR ×( 1.5~15 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A Reverse power protection rP 5-500kW 0.2-20s

OFF position can be used for removing this protection


Time delay (S) tsd (s)
Current unload MCU-4G
Accuracy Setting
±10% 0.1 0.2 0.3 0.4 Measured value Threshold Time delay
I2t OFF
Setting Current I 0.2-1.0In 0.2-0.8tR
≥1.1
I2t ON
Inverse time thermal memory 5-minute cooling reset or controller powers off for clearing
I (instantaneous)
Current setting (A) Ii=In ×( 1.0~20 ) In<2500, setting step-length:1A; In≥2500, setting step-length: 2A
OFF position can be used for removing this protection
Time delay (ms) Accuracy ±10% < 30
G (grounding fault) MCU-4G
Current setting (A) Ig=In×( 0.4~0.8 ) In≤1250, setting step-length:1A
Optional protections MCU-4G
Ig= ( 500~1200 ) In>1250, setting step-length: 2A
MCR protection
OFF position can be used for removing this protection
Current setting (A) IMCR=In × … 10
Time delay (s) tg (s)
Tripping when between 0.85 to 1.15 times of IMCR
Accuracy Setting
±10% ≥1.0 Time delay (ms) <30
I2t OFF
Setting Zone selectivity interlocking (ZSI)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
I2t ON Maximum distance between two circuit breakers (m) 3000
Maximum allowable number of units 100
Load monitoring
Monitoring type Energy
Monitoring range 50% of long delay protection energy threshold
Implementation method Relay output
Overload pre-alarming
Monitoring type Current
Monitoring range Long delay settings
Implementation method Relay output

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 28 ACB Air Circuit Breaker 29

Function list of the releases

Measurement function MCU-4G Release models


Current
Function description MCU-2 MCU-3 MCU-4 MCU-3A MCU-4A MCU-4E MCU-4P MCU-4H MCU-4G
Instantaneous value A Ia Ib Ic In Ig
Overload long delay protection ■ ■ ■ ■ ■ ■ ■ ■ ■
Maximum value A Ia Ib Ic In Ig
Short circuit short delay protection - ■ ■ ■ ■ ■ ■ ■ ■
Demand value A Ia Ib Ic In
Imbalance rate % Ia Ib Ic Short circuit instantaneous protection ■ ■ ■ ■ ■ ■ ■ ■ ■

Present thermal capacity % Grounding Vector and ground


- - ■ - ■ ■ ■ ■ ■
protection fault protection fault (T)
Voltage
Neutral pole protection ■ ■ ■ ■ ■ ■ ■ ■ ■
Instantaneous value V Uab Ubc Uca Uan Ubn Ucn
Average value V (Uab+Ubc+Uca)/3 Thermal memory ■ ■ ■ ■ ■ ■ ■ ■ ■

Imbalance rate % Uan Ubn Ucn Fault tripping indication ■ ■ ■ ■ ■ ■ ■ ■ ■


Frequency
Current imbalance protection - - - - - ■ ■ ■ ■
F Hz Uan Ubn Ucn
Demand current protection - - - - - ■ ■ ■ ■

P r o t e c t i on s
Electrical energy
Phase loss protection - - - - - ■ ■ ■ ■
E.P active energy kwh Total/input/output
E.Q reactive energy kvarh Total/input/output Under voltage protection - - - - - - ■ ■ ■

E.S apparent energy kvah Total Over voltage protection - - - - - - ■ ■ ■


Power
Voltage imbalance protection - - - - - - ■ ■ ■
P active power kw Total
Phase sequence protection - - - - - - ■ ■ ■
Q reactive power kvar Total
Under frequency protection - - - - - - - - ■
S apparent power kva Total
PF power factor Total Over frequency protection - - - - - - - - ■

P, Q, S demand value 5min kw, kvar, kva Total Reverse power protection - - - - - - - - ■
Power quality indication (harmonic)
MCR function □ □ □ □ □ □ □ □ □
Fundamental wave U I Zone selectivity interlocking (relay
- - - □ □ □ □ □ □
THD % U I output)
Current and voltage harmonic amplitude 3, 5, 7, 9, 11, 13…31 Load monitoring (relay output) □ □ □ □ □ □ □ □ □
The controller will display the 3rd to 31st harmonic FFT amplitude in rectangular graph, generating wave spectrum analysis of the harmonics Overload pre-alarming - - - □ □ □ □ □ □

Current: 3-phase, neutral pole, grounding - - - ■ ■ ■ ■ ■ ■

Voltage: line, phase, average,


- - - - - ■ ■ ■ ■
Historical records and maintenance indication MCU-4G imbalance level
Tripping historical log (the last 10 events) can record: Power - - - - - ■ ■ ■ ■

Me a s u r eme n t s
Fault type Frequency - - - - - ■ ■ ■ ■
Date and time
Energy: active, reactive, apparent - - - - - ■ ■ ■ ■
Current measured in case of a fault
Thermal capacity - - - - - ■ ■ ■ ■
Alarming historic log (the latest 10 events) can record
Phase sequence - - - - - ■ ■ ■ ■
Alarm type
Date and time Demand values: current and power - - - - - ■ ■ ■ ■

Current measured in case of alarming Harmonic analysis - - - - - - - ■ □


Maintenance indication can display
Waveform display - - - - - - - ■ □
Operations, including total numbers/hot-line operations
Contact wear rate (%)

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 30 ACB Air Circuit Breaker 31

Release models Release unit accessorie

Function description MCU-2 MCU-3 MCU-4 MCU-3A MCU-4A MCU-4E MCU-4P MCU-4H MCU-4G
● EPM external power supply module
Test tripping ■ ■ ■ ■ ■ ■ ■ ■ ■
When the working voltage is DC 220/110V, the control unit
Contact wear
- - - ■ ■ ■ ■ ■ ■ must be equipped with an external DC power supply module
indication
Maintenance Number of operations for normal operation.
of the circuit of the controller when - - - ■ ■ ■ ■ ■ ■
breaker energized Features
Input voltage V DC220V/110V ±15%
Self diagnosis function ■ ■ ■ ■ ■ ■ ■ ■ ■
Output voltage V DC24V ±5%
Current waveform
- - - ■ ■ ■ ■ ■ ■ Output current A 0.2
display
Historic maximum EPM external power supply module
current
- - - ■ ■ ■ ■ ■ ■
(displayed by the
controller)
10 alarming records
(displayed by the - - - - - ■ ■ ■ ■
controller) display)
Historic fault record ● NCT external current transformer
(one-time indication )
(3 types of faults When a 3-pole circuit breaker is used in a 3–phase 4-wire
M ai n t en a n c e

■ - - - - - - - -
such as long delay,
instantaneous, and system, NCT external current transformer is used as ground fault
neutral pole)
protection or neutral pole over current protection sampling
Historic fault record
(one-time indication) component, for use with the controller. The device needs to be
(4 types of faults such installed by the users.
- ■ - - - - - - -
as long delay, short
delay, instantaneous,
Historic logging and neutral pole) Specification
Current A Inner hole dimension mm Housing dimension mm
Historic fault record
(one-time indication) 400-1600A * 102×32 145×130
(5 types of faults such NCT external current transformer
as long delay, short - - ■ - - - - - - 800-4000A** 128×61 175×179
delay, instantaneous,
5000-6300A*** 164×104 265×210
ground and neutral
pole)
Remark: * refers to breaking capacity 04 to 16 for BAC N1/N2;
Historic fault record ** refers to breaking capacity 08 to 40 for BAC H1/H2/H3;
(10-time indication,
*** refers to breaking capacity 50 to 63 for BAC H3/H4
displayed by the
- - - ■ ■ ■ ■ ■ ■ For any need of N-pole 0.5In protection, please specify it when ordering.
controller) (all the
information opened by
the protections)

Clock function (year,


month, day, hour, - - - - - ■ ■ ■ ■
minute, second)

Modbus - - - □ □ □ □ □ □

Communication
output includes: 1.
Information opened by
protection functions;
O t h er s

2. Information opened
Communication by measurement
function; 3. - - - □ □ □ □ □ □
Information opened by
maintenance function;
4. Historic maximum
current; 5. Alarm
records; 6. Historic
fault records.

Remark: 1. ■ refers to standard configuration, □ refers to optional


2. When the working power supply of the circuit breaker is DC, a power supply module must be equipped.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 32 ACB Air Circuit Breaker 33

6. Accessory Functions and Features


COM communication options Remote operation and indication accessory

COM communication options are made up of built-in communication ● Charging motor (MTC)
modules inside the controller, offering status signals by a series of auxiliary When the circuit breaker is closed, the energy of the mechanism
is released instantaneously, and the charging motor (MTC) is
contacts, enabling ONR and SHT coils to offer communication functions
automatically charged. When the mechasnim is opened, it can
through expansion.
ensure the circuit breaker to be closed instantaneously.
The status indication contacts of the COM communication options are
Features
mutually independent from the state indication contacts of the circuit
AC 220/380 ±15%
breaker. These indication contacts are still effective for normal operation. Rated voltage Un V
DC 110/220 ±15%
ONR and SHT coils, through functional expansion, offer communication
Acutuation voltage V 85% ~ 110% Un
function, capable of remotely controlling switch opening and closing states. Power loss W 90
Charging time s <7
Communication structure diagram
Charging motor (MTC)
● Closing coil (ONR)
In the mornitoring system, The closing coil is used for electrical closing of the circuit breaker.
the integration of the circuit In case of spring charging, the coil can achieve remote closing.
breaker or switch disconnector
Features
requires COM options; Modbus AC 220/380 ±15%
communication protocol is used Rated voltage Un V
DC 110/220 ±15%
for communication. Acutuation voltage V 70% ~ 110% Un
Charging time ms ≤100
Instanteneous power loss VA 200

Closing coil (ONR)


● Opening coil (SHT)
The opening coil is used for electrical opening of the circuit
breaker. After energized, the coil will switch off the circuit breaker
instantaneously.
Features
AC 220/380 ±15%
Rated voltage Un V
DC 110/220 ±15%
Acutuation voltage V 70% ~ 110% Un
Opening time ms ≤100
Instanteneous power loss VA 200
Opening coil ((SHT)

● Under voltage release UVT


When the supply voltage decreases to any value from 35% to
75% of the rated voltage, the release will cause the circuit breaker
to switch off instantaneously. If the under voltage release is
Device wiring not energized, the circuit breaker will not be closed, no matter
Commmunication fieldbus manually or electrically. Only when the supply voltage of the
release rises to above 85% of the rated voltage, the circuit breaker
is allowed to conduct closing operation.
1. Basic device communication module (built inside the controller)
Features
2. Micro switch of the controller (built inside the controller)
Rated voltage Un V AC 220/380 ±15%
3. ONR (closing coil), SHT (shunt coil) Under voltage coil (UVT)
Acutuated 35% ~ 70% Un
Acutuation voltage V
4. Cassette 3-position indication module Not acutuated 85% ~ 110% Un
5. Cassette communication module Acutuation time ms ≤100
Holding power loss VA 12

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 34 ACB Air Circuit Breaker 35

● UVT delay unit ● OK closing ready contact

The unit is used in thunderstorm regions and in the power grid with The contact consists of one mechanical indication contact and changeover
unstable power supply voltage, to prevent the circuit breaker from tripping contact, for use with the interlocking mechanism on the mechanism,
due to short-time voltage drop. indicating:
- The circuit breaker is in opened state;
Features
- The spring is charged;
Rated voltage Un V AC 220/380 ±15%
Start-up delay Adjustable (Rr) 0.5s/1s/1.5s/2s/2.5s/3s ±10%
- The shunt coil (S H T)is not energized;
- The closing coil (ONR)is not energized;
UVT delay unit - No fault tripping; OK closing ready contact

- OFF/opening position lock is unlocked;


● ON/OFF indication contact (AU)
- The circuit breaker is not in the middle state in the drawout frame;
The contact is used to indicate ON or OFF position of the circuit breaker, for The contact is for the customer to use.
the customers to use, including:
1NO-C is available.
4NO-C
4NO+4NC Features
6NO-C AC 220/380 ±15%
6NO+6NC Rated voltage Un V
DC 110/220 ±15%

Features Utilization category AC-15 DC-13

AC 220/380 ±15% Conventional thermal curent IA 10


Rated voltage Un V Rated capacity 800 VA ( AC ) 66 W (DC )
DC 110/220 ±15%
ON/OFF indication contact
Utilization category AC-15 DC-13
Conventional thermal
10
curent IA
Rated capacity 800 VA ( AC ) 66 W ( DC ) ● PI cassette 3-position indication module

Remark: For BAC04-16 N1 and N2 type, only 4NO-C and 6NO-C are available. When the basic device of the draw-out circuit breaker and its cassette are
in separation, test, and connection positions separately, the electrical signal
output device in the 3 positions will output electrical state signals of each
related position separately.

● Fault tripping indication contact(TAU) Features


Rated voltage Un V AC 220/380 ±15%
The contact is built inside the control unit, offering indication in case of fault
Utilization category AC-12
tripping of the circuit breaker, for the customers to use.1NO-C is available.
Conventional thermal curent IA 4
Features Rated capacity 800 VA PI cassette 3-position
AC 220/380 ±15% indication module
Connection 1NO
Rated voltage Un V Number of the contacts Test 1NO
DC 110/220 ±15%
Seperation 1NO
Utilization category AC-12 DC-12
Conventional thermal
10
curent IA
Rated capacity 2000 VA ( AC ) 66 W ( DC )

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 36 ACB Air Circuit Breaker 37

Connection and mechanical accessories

● Busbar wiring accessories ● Door interlocking

The upper and lower wiring accessories offer horizontal and The door interlocking device can be installed on the left
vertical types, meeting different mounting requirements. Please or right side of the cassette. When the basic device of the
specify it when ordering, or adjust it based on your actual needs. circuit breaker is in "Connection or Test" position, the circuit
Busbar wiring accessories breaker compartment door is forbidden to open. When the
door is opened, and the circuit breaker is in Connection
position, the circuit breaker door can be closed without Door interlocking
operation.
● Phase partition / Interphase barrier

The partition is usded for strengthening the insulation between ● Interlocking between circuit breakers
busbars.
Some electrical systems have two power supply systems for
the continuity of power supply, including the following two
circuit breakers:
Phase partition
- Normal power supply circuit breaker A ;
- Backup power supply circuit breaker B.
● Button lockup device
Circuit breaker A Circuit breaker B
The device is composed of a transparent cover and a padlock
0 0
(not supplied), to prevent closing or opening button from mal
operation. (N1/N2 type is not optional). I 0
Interlocking between circuit breakers
0 I

The maximum distance between two circuit breakers' fixed panels


shall not exceed 2 meters.
● OFF opening position lock
Button lockup device
The opening button of the circuit is locked in pressed-down
state with the key lock, locking the circuit breaker in OFF ● Secondary terminal cover (CTC)
position. Only when the lock is in lock up position, the key can Secondary terminal cover CTC
The cover is mounted on the cassette, to prevent from acess
be pulled out.
to the secondary wiring terminal.
The following configuration is available:
- 1 lock;
- 1 lock +1 lock with same key (H1 type and the breakers with ● Operation counter (CQ)
above breaking capacity are optional); The counter is used to count the number of operations and
OFF opening position lock
- 2 locks with different keys (H1 type and the breaker with above display the readings on the front panel, compatible with
breaking capacity are optional). manually and electrically operated functions. Operation counter CQ

● Separation position lock

The lock is installed on the cassette, to lock up the circuit breaker ● Door frame (DP)
in its position in the cassette. The following two lockup methods The frame is mounted on the door, to improve the
are available: protection degree of the circuit breaker to IP40; both fixed
- Padlock device (equipped in standard, the lock is supplied by type and drawout type frame can be mounted.
the user);
Padlock device
- Key lock (optional); Key lock

Based on the requirements, the separation position lock can be


adjusted, to lock up the circuit breaker in "separation" , "test" , Separation position lock
and "connection" positions. Drawout door frame Fixed-type door frame

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 39

7. Altitude, Temperature, and Derated Coefficient


Temperature derated coefficient of the circuit breaker

When the ambient temperature exceeds 40°C, the operating current will be corrected according to the following table:

Ambient temperature + 40°C + 45°C + 50°C + 55°C + 60°C


1600A In 0.95In 0.90In 0.85In 0.80In

Maximum operating current of the 2500A In 0.95In 0.90In 0.85In 0.80In


circuit breaker 4000A In 0.95In 0.90In 0.85In 0.80In

6300A In 0.92In 0.86In 0.80In 0.74In

Altitude derated coefficient of the circuit breaker

When the altitude exceeds 2000m, the performance can be corrected according to the following table.

Altitude (m) 2000 3000 4000 5000

Average insulation level (V) 1000 900 700 600

Max. operating voltage (V) 690 590 520 460

Ambient temperature 40°C (A) 1×In 0.98×In 0.95×In 0.93×In

Advanced Standardized Delicate

BAC
Series of Low-Voltage
Air Circuit Breaker
PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 40 ACB Air Circuit Breaker 41

8. Dimension and Wiring


BAC04~16N1 and N2 fixed type
Dimension Wiring

Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 10 30

Remark: X and Y are the axis of symmetry of the circuit breaker;


F is the reference point.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 42 ACB Air Circuit Breaker 43

BAC04~16N1 and N2 draw out type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 10 30

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 44 ACB Air Circuit Breaker 45

BAC08H1, H2~BAC25H1 and H2 fixed type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 10 30

Remark: X and Y are the axis of symmetry of the circuit breaker;F is


the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 46 ACB Air Circuit Breaker 47

BAC08H1, H2~BAC25H1 and H2 draw out type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section

A 0 0
B 70 70

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 48 ACB Air Circuit Breaker 49

BAC32H2 and H3 fixed type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 10 30

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 50 ACB Air Circuit Breaker 51

BAC32H2 and H3 drawout type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 70 70

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 52 ACB Air Circuit Breaker 53

BAC40H2 and H3 fixed type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 10 30

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 54 ACB Air Circuit Breaker 55

BAC40H2 and H3 drawout type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 70 70

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 56 ACB Air Circuit Breaker 57

BAC50H3, H4~BAC63H3 and H4 fixed type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 70 70

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 58 ACB Air Circuit Breaker 59

BAC50H3, H4~BAC63H3 and H4 drawout type

Dimension Wiring
Horizontal rear wiring Detailed drawing

Fastening on the foundation panel Detailed drawing for fastening

Vertical rear wiring Detailed drawing

Safety clearance Door cutout

Insulation section Metal section


A 0 0
B 70 70

Remark: X and Y are the axis of symmetry of the circuit breaker;F


is the reference point..

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 60 ACB Air Circuit Breaker 61

BAC external modules

EPM external power supply module COM cassette communication module

7.5

NCT external current transformer UVT delay unit

Dimension
Current W H L a b c
400-1600A * 145 130 50 102 32 75
800-4000A** 175 179 60 128 61 95
5000-6300A*** 265 210 60 164 104 110

Remarke: * referst to breaking capacity 04 to 16 for BAC N1/N2;


** refers to breaking capacity 08 to 40 for BAC H1/H2/H3;
*** refers to breaking capacity 50 to 63 for BAC H3/H4;
If any need for N-pole 0.5In protection, please specify it when ordering.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 62 ACB Air Circuit Breaker 63

9. Electric circuit diagrams


BAC 04~16 N1, N2
Position indication contact PI
BAC 04~16 N1, N2 type (400~1600A) fixed and drawout types
The electric schematic diagram is the wiring diagram when the circuit breaker is in disconnected state, uncharged,
and the controller has no fault indication

Main circ Control unit Remote operation

ON/OFF indication contact mode

Symbol definition Wiring terminal number definition


SB1 Under voltage button Control unit power supply input, "+" for 27, 28 Empty, terminal(backup)
1, 2 DC1, "-"for DC2.
SB2 Closing button Voltage indication N, A, B, C 4-phase NCT external current transformer input
3, 33, 36, 39 29, 30
voltage input terminal (optional function) (optional function)
SB3 Shunt button
7, 8, 9 Fault tripping indication signal output Under voltage(or time delay)release power
J1 Remote closing relay 31, 32
10, 11, 12 Closing indication signal output supply input
J2 Remote opening relay 13, 14, 15 Opening indication signal output 34, 35 Closing coil power supply input
ONR Closing coil Overload pre-alarming/programmable
16, 17 output 1(optional function) 37, 38 Opening coil power supply input
SHT Shunt coil Load monitoring/programmable output 2
18, 19 Charging motor power supply input and
MTC Charging motor (optional function) 40, 41, 42
charging ready signal output
ZSI signal output, Terminal 20 to connect
SA Motor limit switch 20, 21 ZS1", Terminal 21 to connect ZS2 " (optional OK closing ready signal output
43, 44, 45
function) (optional function)
XT Wiring terminal 4NO-C 6NO-C
ZSI signal input, Terminal 22 to connect
UVT Under voltage coil ON/OFF indication contact mode(see
22, 23 "ZS3 ", Terminal 23 to connect "ZS4" 49~66
Figure 1 for the modes)
(optional function)
Intelligent controller communication Cassette 3-position signal output(optional
port, Terminal 24 for SH shielding layer, A1~A6
function)
Terminal 25 to connect A, Terminal 26
to connect B; in the case of cassette B1~B6 Empty, terminal(backup)
24, 25, 26 communication module, be connected
to the cassette communication module Cassette 3-position signal input(optional
T1~T4
input, Terminal 24 to connect S', Terminal function)
25 to connect A', Terminal 26 to connect B'
(optional function) S, A, B Communication output(optional function)

Remark:
1. The dotted lines are for wiring by users. The diagram is only for reference;
2. Terminal 1 and 2 are control unit’s power supply. The power supply can be connected to AC 230V or AC 400V, depending on
secondary circuit working voltage. If the working voltage is DC110V and DC220V, the control unit can be connected after
transformation through an external DC power

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 64 ACB Air Circuit Breaker 65

BAC 08~63 H1, H2, H3, H4


BAC 08~63 H1, H2, H3 and H4 (800~6300A) fixed and drawout type Position indication contact PI

The electric schematic diagram is the wiring diagram when the circuit breaker is in disconnected state, uncharged,
and the controller has no fault indication.

Main circ Control unit Remote operation

ON/OFF indication contact mode

Symbol definition Wiring terminal number definition


Under voltage 1, 2
Control unit power supply input, "+" for DC1,
29, 30
NCT external current transformer input
SB1 "-" for DC2. (optional function)
button
Voltage indication N, A, B, C 4-phase voltage Under voltage(or time delay)release power
SB2 Closing button 3, 4, 5, 6
input terminal (optional function)
31, 32
supply input
SB3 Shunt button 7, 8, 9 Fault tripping indication signal output 34, 35 Closing coil power supply input
J1 Remote closing relay 10, 11, 12 Closing indication signal output
37, 38 Opening coil power supply input
Remote opening 13, 14, 15 Opening indication signal output
J2 Charging motor power supply input and
relay Overload pre-alarming/programmable 40, 41, 42
16, 17 charging ready signal
output 1(optional function)
ONR Closing coil OK closing ready signal output 4NO-C 6NO-C
Load monitoring/programmable 43, 44, 45
18, 19 (optional function)
SHT Shunt coil output2(optional function)
ZSI signal output, Terminal 20 to connect 46, 47, 48 Empty, terminal(backup)
MTC Charging motor 20, 21 ZS1", Terminal 21 to connect ZS2 "(optional
function) 49, 50, 51 Empty, terminal(backup)
SA Motor limit switch
ZSI signal input, Terminal 22 to connect 52, 53, 54 Empty, terminal(backup)
XT Wiring terminal 22, 23 "ZS3" , Terminal 23 to connect "ZS4" (optional
function) ON/OFF indication contact mode(see Figure
UVT Under voltage coil 55~78
Intelligent controller communication port, 1 for the modes)
Terminal 24 for SH shielding layer, Terminal Cassette 3-position signal output(optional
A1~A6
25 to connect A, Terminal 26 to connect function)
B, in the case of cassette communication
24, 25, 26 B1~B6 Empty, terminal(backup)
module, be connected to the cassette
communication module input, Terminal Cassette 3-position signal input(optional
24 to connect S', Terminal25 to connect A', T1~T4
function)
Terminal 26 to connect B'(optional function)
Communication output(optional
27, 28 Empty, terminal(backup) S, A, B
function)

Remark:
4NO+NC 6NO+NC
1. The dotted lines are for wiring by users. Tthe diagram is only for reference;
2. Terminal 1 and 2 are control unit’s power supply. The power supply can be connected to AC 230V or AC 400V, depending
on secondary circuit working voltage. If the working voltage is DC110V and DC220V, the control unit can be connected after
transformation through an external DC power supply module

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 66 ACB Air Circuit Breaker 67

BAC series circuit breaker's communication options Zone selectivity interlocking

COM communication accessory wiring Zone selectivity interlocking

Defintions of wiring terminal numbers The control line can interlock several circuit breakers equipped with MCU control units, as shown in the diagram;
Intelligent controller communication port, Terminal 24 for SH shielding layer, Terminal 25 to connect A, Terminal
The control unit, when detecting a fault, will send a signal to the upstream circuit breaker and detect the signals to the
24, 25, 26 26 to connect B; in the case of cassette communication module, be connected to the cassette communication
module input, Terminal 24 to connect S', Terminal25 to connect A', Terminal 26 to connect B'(optional function) downstream circuit breaker. When the signal sent by the downstream circuit breaker is detected, the circuit breaker will
A1~A6 Cassette 3-position signal output(optional function) remain closed during tripping delay period. If the downstream breaker does not send signals, the circuit breaker will be
T1~T4 Cassette 3-position signal input(optional function) disconnected instantaneously.
S, A, B Communication output(optional function)
Fault 1: only the circuit breaker A detects the fault. Because not receiving the signal sent by the downstream circuit breaker,
the circuit breaker A will trip instantaneously.
Remark:
1. The cassette communication module requires DC24V power supply ( to be supplied by the customer himself );
Fault 2: circuit breaker A and B detect the signal. The circuit breaker A receives the signal sent bym the circuit breaker B and
2. The cassette communication module 3-position signal samling are treated through opto-coupler isolation.
remains closed within 0.3 seconds of tripping delay. The circuit breaker B will trip instantaneously for it does not
receive the signal from its downstream circuit breaker.

Remark: the maximum distance between two circuit breakers is 300 meters. The maximum number of circuit breakers for wiring is 100 devices.

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 68 ACB Air Circuit Breaker 69

10. Tripping Curves


MCU control unit's tripping curves Grounding faults

ln ≤1250A
lg = In x... 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
ln >1250A
Ig = ...(A) 500 600 700 800 850 900 1000 1100 1200

PT. Australindo Graha Nusa Product specification and Information in this publication can change at any time without prior notice. Product specification and Information in this publication can change at any time without prior notice. www.australindo.co.id
ACB Air Circuit Breaker 70 ACB Air Circuit Breaker 71

11. Ordering Information


Model instruction Selection table of BAC series air circuit breakers

Tick (√) your choice in the corresponding box √ □ and fill relevant information in the rectangular box
BAC 06 N1 3P D/O + MCU - 2
Circuit breaker's basic device Indication contact
Quantity (4NO-C) □
Maximum operating current A ON/OFF indication contact (6NO-C) □
Rated current A (AU) (4NO+4NC) □

MCU control unit Breaking level N1 N2 H1 H2 H3 H4 (6NO+6NC) □


Number of poles 3P□ 4P □ Fault tripping indication
2, 3, 4 contact (TAU) □
4E, 4P, 4H, 4G Drawout type (D/O) □
Type OK closing ready contact □
Fixed type (F) □
Cassette 3-position indication
contact(PI) □

MCU control unit


AC 220/380 V Remote operation
Operating voltage
DC 220/110 V Charging motor AC 220/380 V
( MTC ) DC 220/110 V
MCU-2 □
D/O (drawout type, no need for marking), F (fixed type) Basic type MCU-3 □ Closing coil AC 220/380 V
( ONR ) DC 220/110 V
3P (no need for marking), 4P MCU-4 □
MCU-3A □ Shunt coil AC 220/380 V
N1, N2, H1, H2, H3, H4
Current type ( SHT )
MCU-4A □ DC 220/110 V
04, 06, 08, 10, 12, 16, 20, 25, 32, 40, 50, 63
All power type MCU-4E □ AC 380/220 V
Air Circuit Breaker Series Under voltage release
( UVT ) Adjustable delay unit(Rr)
All power + voltage protection type MCU-4P □ □
0.5s/1s/1.5s/2s/2.5s/3s
All power + harmonic + voltage
MCU-4H □
protection type
All power + voltage and Locks
MCU-4G □
frequency protection type
Button locking device
( basic device ) □
OFF opening position lock 1 lock*
MCU control unit options ( basic device ) □
COM options Modbus □ 1 lock+1 lock,
with same keys * □
MCR functional options □
2 locks
( different keys) * □
ZSI interlocking(relay output) □
Separation position lock
Load monitoring □ ( cassette ) □

Overload pre-alarming □
Harmonic analysis and waveform H type: standard, Mechanical interlock
display G type: optional □
Door interlocking □
Load monitoring □
Interlocking between
Overload pre-alarming □ devices* □

Harmonic analysis and waveform display


Wiring accesories Accessories
Upper □ Secondary terminal cover
(CTC)(drawout type) □
Vertical wiring
Lower □
Mechanical counter(CQ) □
Upper □
Horizontal wiring Door frame(DP) □
Lower □
Interphase partition 3P□ 4P □ " *" : when in use with other switches for interlocking function, please
specify it when ordering.