CM 2 : Ventilation Fan:-
CM 2 : Separator Fan:-
Fully open/ 40 %
*****
Corrected Kw
Check 1
Design Actual
45720 m3/h 38527 m3/h
30771 Nm3/h 27120 Nm3/h
Title : Site Performance Test Report
Power kw
Current A
Speed rpm
Volts V
Power Factor Cos ф
Frequency Hz
Design Actual
173880 m3/h 171732 m3/h
122238 Nm3/h 130228 Nm3/h
Title : Site Performance Test Report
Power kw
Current A
Speed rpm
Volts V
Power Factor Cos ф
Frequency Hz
Velocity 13.63 m/s
Flow (wet) 10.70 m3/s
Flow (wet) 7.53 Nm3/s
Flow (wet) 38,527 m3/h
Flow (wet) 27,120 Nm3/h
Design Actual
45720 m3/h 38527 m3/h
30771 Nm3/h 27120 Nm3/h
Title : Site Performance Test Report
Power kw
Current A
Speed rpm
Volts V
Power Factor Cos ф
Frequency Hz
Velocity 16.82 m/s
Flow (wet) 47.70 m3/s
Flow (wet) 36.17 Nm3/s
Flow (wet) 171,732 m3/h
Flow (wet) 130,228 Nm3/h
*******
m3 to Nm3
xxx
173,880 m3/h
Design Actual
48.300 m /s 173880 m3/h 171732 m3/h
3
76 °C
-5,729 Pa 122238 Nm3/h 130228 Nm3/h
96,780 Pa (P° baro)
1.422 0.703
122,238 Nm3/h
33.955 Nm3/s
Title : Site Performance Test Report
Power kw
Current A
Speed rpm
Volts V
Power Factor Cos ф
Frequency Hz
Aeraulic surface 2.84 m2
Avg. Dyn. Pressure 271.18 Pa
RHO w/o dust (wet) 0.972 kg/m3
RHO with dust (wet) 0.972 kg/m3