CTSpec
CTSpec
CTSpec
1 This specification covers manufacture, test, & supply of LT Current transformers of class 0.5 accuracy. 1.2 The CTs shall be suitable for metering purpose. 2.0 TYPE: 2.1 The CTs shall be of ring type or window type (bar type or bus-bar type CTs shall not be accepted). 2.2 The secondary leads shall be terminated with Tinned Cooper rose contact terminals with arrangements for sealing purposes. 2.3 Polarity (both for primary and second leads) shall be marked. 2.4 The CTs shall be varnished, fiberglass tape insulated or cast resin, air-cooled type. Only super enameled electrolytic grade copper wires shall be used. 2.5 The CTs shall conform to IS 2705:Part-I & II/IEC:185 with latest amendments. 3.0 TECHNICAL DETAILS: 3.1 Technical details shall be as given below: 1. 2. 3. 4. 5. 6. 7. Class of Accuracy Rated Burden Power Frequency Withstand Voltage Highest System Voltage Nominal System Voltage Frequency Supply System 0.5 5.00 VA 3KV 433 V 400 V 50 Hz 3 Ph. Solidly grounded Neutral System
3.2 Transformation ratio shall be specified from the following standard ratings as per requirement : Ratio 50/5 150/5 300/5 400/5 1000/5
(Secondary with 1 A may be specified by the utility incase the same is desired.) 3.3 Bore diameter of the CT shall not be less than 40 mm. Ring type CTs shall have suitable clamp to fix the CT to panel Board, wherever required. 3.4 The limits of current error and phase angle displacement as per IS:2705 at several defined percentage of rated current are: Accuracy % Ratio error at % of rated Phase displacement in minutes at %
Class 0.5
100 0.5
120 0.5
120 30
Note : Current error and phase displacement at rated frequency is required to be as above when the secondary burden from 25% to 100% of the rated burden i.e. 50 V A. 3.5 Rated extended primary current shall be 120% of rated primary Current in accordance with IS:2705 Pt-II. 3.6 Rated ISF (Instrument Security Factor) shall be declared by the manufacturer & marked on the CT. 3.7 CTs shall be made with good engineering practices. Core winding shall evenly spread stress & avoid stress concentration at any one point. Cast resin CTs sha;; be processed by hot curing method under controlled vacuum conditions. 3.8 The base shall be of hot dip galvanised steel. 4.0 TESTS: 4.1. TYPE TESTS: 4.1.1 Copies of all type tests as per IS.2705 Part-I and II including short time current & temperature rise tests in NABL accredited laboratory shall be submitted and got approved before commencement of supply. 4.2 ROUTINE TESTS: 4.2.1 The supplier shall conduct all the routine tests such as Ratio test, phase angle error test for 0.5 accuracy class as per IS 2705 Part I & II. 4.3 COMMISSIONING TEST : 4.3.1 In accordance with IS:2705, Power frequency test on primary winding shall be carried out after erection on site on sample basis. 5.0 MARKING : 5.1 The CTs shall have marking and nameplate as per IS 2705 in addition to class of insulation & ISF. The markings shall be indellible. The nameplate shall be securely fixed to the body of the CT. 6.0 PACKING: 6.1 Each CT shall be securely packed so as to withstand rough handling during transit and storage. 7.0 QUALITY ASSURANCE PLAN: 7.1 The requirements of clause 29.0 of Section I of main specification for Energy Meters shall apply.
GUARANTEED TEHNICAL PARTICULARS FOR CURRENT TRANSFORMERS S.No. 1. 2. 3. a) b) c) e) f) 4. 5. a) b) c) d) 6. a) b) c) 7. 8. 9. DESCRIPTION Makers Name & address Type and capacity Rated voltage Highest system Voltage Rated Primary Current Rated Secondary Current Rated Output Rated continuous thermal current Temperature rise over ambient Power Frequency WithstandVoltage Class of Accuracy Material Core Conductor Insulation Base MS Zinc plated Dimension in mm Inner Dia. of CT Outer Dia. of CT Height of center of CT from base Secondary termination ISF Extended primary current 150/5A